AH1-357 Phase I Study Report

v1.00 released 2025-10-29 19:59

Pierce Brook-Lewis Run 230kV

12.0 MW Capacity / 20.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is McKean County Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Mid-Atlantic Interstate Transmission, LLC.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Mid-Atlantic Interstate Transmission, LLC zone — McKean County, Pennsylvania. This project is an increase to the developer’s AG2-456/AG2-457 project(s), which will share the same Point of Interconnection. The AH1-357 project is a 20.0 MW uprate (12.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 180.0 MW with 123.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-357
Project Name:
Pierce Brook-Lewis Run 230kV
Project Developer Name:
McKean County Solar, LLC
State:
Pennsylvania
County:
McKean
Transmission Owner:
Mid-Atlantic Interstate Transmission, LLC
MFO:
180.0
MWE:
20.0
MWC:
12.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-357 will interconnect on the Mid-Atlantic Interstate Transmission, LLC transmission system tapping the Pierce Brook to Lewis Run 230 kV line as an uprate to AG2-456/AG2-457. AH1-357 is uprated by AH1-358/AH1-359/AH1-360.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-357 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-357Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$140,035$0
Other Scope$10,133$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$1,997,665$1,997,665
Network Upgrades$435,142$435,142
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$14,473,306$14,473,306
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$17,056,281$16,906,113

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-357

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-357 Project due at DP1
ABA - B
AH1-357$1,690,611$80,000$1,610,611

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construction of (1) span of conductor between the new Interconnection substation takeoff structure and Developer owned dead end structure.$776,370 $129,395 (See Note 1)
(Pending)Integrate Interconnection Facilities protection and controls to the Transmission Owner system.$63,840 $10,640 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construct a new 230 kV 3-breaker ring bus Interconnection substation.$15,981,321 $1,997,665 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Revise relay settings at Pierce Brook substation as required.$53,200 $6,650 (See Note 1)
(Pending)Revise relay settings at Lewis Run substation as required.$53,200 $6,650 (See Note 1)
(Pending)Cut the existing 230 kV line and Loop in the new Interconnection substation.$3,374,732 $421,842 (See Note 1)
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install 230 kV revenue metering within new Interconnection substation.$60,800 $10,133 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 49 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AH1-357 did not contribute to any overloads on the FE transmission <100 kV system.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-357 was evaluated as a 20.0 MW (12.0 MW Capacity) injection in the PENELEC area.

AH1-357 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-3_WP-138-171A_SRT-A
BreakerAC150.5 %151.0B227.250.96
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-2_WP-138-054A_SRT-A
BusAC149.99 %151.0B226.480.95
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC142.46 %151.0B215.111.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC142.46 %151.0B215.111.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC138.88 %151.0B209.71.07
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC138.88 %151.0B209.71.07
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC121.3 %151.0B183.160.67
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.58 %151.0B157.920.82
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-2_WP-138-055_SRT-A
BusAC104.36 %151.0B157.580.81
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
AP_P2-2_WP-138-058_SRT-A
BusAC157.77 %209.0B329.751.16
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
AP_P2-3_WP-138-194T_SRT-A
BreakerAC140.36 %209.0B293.361.05
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC127.91 %209.0B267.341.19
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC127.91 %209.0B267.341.19
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC127.2 %209.0B265.861.2
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC121.14 %209.0B253.191.07
GD2AP
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC108.44 %209.0B226.630.87
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC125.11 %659.0B824.453.08
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC125.11 %659.0B824.453.08
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC125.01 %659.0B823.83.08
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-345-997-DRT-031_SRT-SL
BreakerAC102.96 %659.0B678.51.36
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC181.73 %151.0B274.411.27
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC179.52 %151.0B271.071.27
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC179.52 %151.0B271.071.27
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P2-3_WP-138-177_A_SRT-A
BreakerAC168.0 %151.0B253.681.03
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC164.29 %151.0B248.081.11
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-054_SRT-A
TowerAC149.48 %151.0B225.720.85
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC143.83 %151.0B217.180.71
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC133.67 %151.0B201.840.73
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P2-2_WP-138-057_SRT-A
BusAC131.28 %151.0B198.240.91
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-2_PN-345-002T-DRT-003_SRT-A
BusAC124.22 %151.0B187.570.93
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-067_SRT-A
TowerAC118.35 %151.0B178.720.87
GD2AP
01DALE-01SHINGL 230.0 kV Ckt 1 line
PN_P2-3_PN-230-703T_SRT-A
BreakerAC104.3 %523.0B545.491.45
GD2AP
01DALE-01SHINGL 230.0 kV Ckt 1 line
AP_P2-2_WP-230-006T_SRT-A
BusAC102.38 %523.0B535.441.47
GD2AP
01DALE-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-459T_SRT-A
BreakerAC102.37 %523.0B535.411.47
GD2AP
01ELKO-01CARB J 138.0 kV Ckt 1 line
AP_P2-2_WP-230-002_SRT-A
BusAC101.85 %192.0B195.551.02
GD2AP
01ELKO-01CARB J 138.0 kV Ckt 1 line
AP_P2-3_WP-230-442_SRT-A
BreakerAC101.85 %192.0B195.541.02
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC183.35 %151.0B276.861.27
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC181.14 %151.0B273.521.27
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC181.14 %151.0B273.521.27
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P2-3_WP-138-177_A_SRT-A
BreakerAC168.97 %151.0B255.151.03
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC165.68 %151.0B250.181.11
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-054_SRT-A
TowerAC150.85 %151.0B227.780.85
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC144.37 %151.0B218.00.71
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC134.03 %151.0B202.390.73
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P2-2_WP-138-057_SRT-A
BusAC132.4 %151.0B199.920.91
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-2_PN-345-002T_SRT-A
BusAC125.54 %151.0B189.570.93
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-067_SRT-A
TowerAC119.71 %151.0B180.750.87
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC142.81 %192.0B274.21.24
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC142.81 %192.0B274.21.24
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC131.54 %192.0B252.561.28
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC131.54 %192.0B252.561.28
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC131.08 %192.0B251.671.28
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC128.11 %192.0B245.971.1
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
AP_P2-2_WP-230-005T_SRT-A
BusAC105.32 %192.0B202.220.92
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC100.95 %192.0B193.820.94
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC119.89 %268.0B321.311.31
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC119.89 %268.0B321.311.31
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC109.92 %268.0B294.61.35
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC108.63 %268.0B291.141.34
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC108.63 %268.0B291.141.34
GD2AP
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC107.72 %268.0B288.71.15
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-3_WP-138-171A_SRT-A
BreakerAC148.95 %151.0B224.920.96
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-2_WP-138-054A_SRT-A
BusAC148.43 %151.0B224.130.95
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC141.31 %151.0B213.371.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC141.31 %151.0B213.371.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC137.47 %151.0B207.581.07
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC137.47 %151.0B207.581.07
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC119.95 %151.0B181.130.67
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.78 %151.0B158.220.82
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-2_WP-138-055_SRT-A
BusAC102.82 %151.0B155.250.81
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0310-B_SRT-A
BreakerAC134.58 %612.0B823.641.98
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0310-A_SRT-A
BreakerAC134.58 %612.0B823.61.98
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0014-01_SRT-A
BreakerAC134.57 %612.0B823.561.98
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0014-02_SRT-A
BreakerAC133.52 %612.0B817.121.98
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0310-C_SRT-A
BreakerAC132.54 %612.0B811.171.96
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-2_PN-345-1185-2_SRT-A
BusAC123.1 %612.0B753.363.28
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC119.03 %612.0B728.441.99
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-2_PN-230-009_SRT-A
BusAC118.05 %612.0B722.472.23
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-020T_SRT-A
TowerAC117.04 %612.0B716.262.04
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-2_PN-115-022_SRT-A
BusAC116.81 %612.0B714.92.02
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PL_08_P22_102799_SRT-A
BusAC116.7 %612.0B714.181.92
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P2-2_PN-115-059B_SRT-A
BusAC116.57 %612.0B713.391.69
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P1-2_PN-230-020A_SRT-A
SingleAC113.22 %612.0B692.911.38
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Base Case
SingleAC111.67 %512.0A571.731.34
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P1-2_PN-230-019_SRT-A
SingleAC111.12 %612.0B680.041.37
GD2AP/PENELEC
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC114.88 %294.0B337.740.87
GD2PENELEC
26CANYON-26N.MESHPN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-997-DRT-053_SRT-SL
BreakerAC100.41 %666.0B668.731.16
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC106.31 %1001.0B1064.173.13
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC106.31 %1001.0B1064.173.13
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC106.31 %1001.0B1064.163.13
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC104.94 %1001.0B1050.423.09
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0183-208_SRT-A
BreakerAC103.22 %1001.0B1033.262.99
GD2PENELEC
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line
PN_P2-3_PN-230-997-DRT-053_SRT-SL
BreakerAC101.77 %666.0B677.761.16
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-26A2_SRT-A
BreakerAC106.13 %666.0B706.858.69
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-3_PN-345-997-DRT-051_SRT-SL
BreakerAC106.13 %666.0B706.858.69
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-3_PN-230-26A1_SRT-A
BreakerAC104.21 %666.0B694.057.11
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-3_PN-345-997-DRT-052_SRT-SL
BreakerAC104.21 %666.0B694.057.11
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-3_PN-345-1185-A_SRT-A
BreakerAC103.99 %666.0B692.587.0
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
PN_P2-2_PN-345-1185-2_SRT-A
BusAC103.98 %666.0B692.527.0
GD2PENELEC
26GLADE-26WARREN 230.0 kV Ckt 1 line
AP_P2-2_WP-230-005T_SRT-A
BusAC100.6 %666.0B669.973.79
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC133.72 %827.0B1105.844.88
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-301_SRT-A
BreakerAC133.72 %827.0B1105.844.88
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-230-001T_SRT-A
BusAC133.05 %827.0B1100.295.16
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC133.04 %827.0B1100.255.16
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-345-001T-DRT-001_SRT-A
BusAC131.95 %827.0B1091.25.16
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-345-001T_SRT-A
BusAC131.95 %827.0B1091.25.16
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-230-0183-207_SRT-A
BreakerAC129.11 %827.0B1067.775.12
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC128.09 %827.0B1059.335.08
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P2-2_WP-138-059_SRT-A
BusAC121.05 %827.0B1001.094.54
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P1-2_WP-345-311T_SRT-A
SingleAC120.13 %827.0B993.453.4
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P2-2_WP-230-005T_SRT-A
BusAC115.4 %827.0B954.324.35
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Base Case
SingleAC113.83 %647.0A736.472.85
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC113.78 %827.0B940.964.4
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC112.55 %827.0B930.833.6
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC108.7 %827.0B898.944.22
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC132.2 %980.0B1295.554.0
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC131.02 %980.0B1284.023.98
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC131.02 %980.0B1284.023.98
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC131.01 %980.0B1283.854.06
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC121.6 %980.0B1191.643.96
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC121.6 %980.0B1191.643.96
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_WP-138-059_SRT-A
BusAC112.4 %980.0B1101.513.48
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-2_PN-115-016A_SRT-A
BusAC109.01 %980.0B1068.293.27
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC108.9 %980.0B1067.23.39
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC108.04 %980.0B1058.753.24
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT18_SRT-A
BusAC106.12 %980.0B1040.013.15
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC105.44 %980.0B1033.272.78
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC105.43 %980.0B1033.252.78
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.72 %980.0B1026.223.25
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Base Case
SingleAC100.25 %809.0A811.022.2
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301_SRT-A
BreakerAC133.88 %827.0B1107.154.88
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC133.88 %827.0B1107.154.88
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-230-001T_SRT-A
BusAC132.97 %827.0B1099.75.16
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC132.97 %827.0B1099.665.16
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-345-001T_SRT-A
BusAC131.9 %827.0B1090.835.16
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-345-001T-DRT-001_SRT-A
BusAC131.9 %827.0B1090.835.16
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-230-0183-207_SRT-A
BreakerAC129.01 %827.0B1066.945.12
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC128.09 %827.0B1059.315.08
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P2-2_WP-138-059_SRT-A
BusAC121.08 %827.0B1001.364.54
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P1-2_WP-345-311T_SRT-A
SingleAC120.28 %827.0B994.753.4
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P2-2_WP-230-005T_SRT-A
BusAC115.44 %827.0B954.654.35
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Base Case
SingleAC113.82 %647.0A736.422.85
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P7-1_WPP-138-053A_SRT-A
TowerAC113.78 %827.0B940.954.4
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC112.51 %827.0B930.453.6
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P7-1_WPP-138-051A_SRT-A
TowerAC108.69 %827.0B898.894.22
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT27_SRT-SL
BreakerAC118.81 %639.0B759.232.35
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-004-DRT-003_SRT-SL
BreakerAC118.81 %639.0B759.232.35
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT26_SRT-SL
BreakerAC118.75 %639.0B758.812.35
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-004-DRT-004_SRT-SL
BreakerAC118.75 %639.0B758.82.35
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-2_PN-500-004A-DRT_SRT-SL
BusAC112.01 %639.0B715.772.35
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC111.27 %639.0B711.022.2
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-A_SRT-A
BreakerAC156.72 %618.0B968.541.99
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-B_SRT-A
BreakerAC156.7 %618.0B968.431.99
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT31_SRT-SL
BreakerAC155.32 %618.0B959.881.9
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-008_SRT-SL
BreakerAC155.32 %618.0B959.881.9
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-D_SRT-A
BreakerAC154.64 %618.0B955.661.99
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-030_SRT-A
BusAC149.64 %618.0B924.752.0
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-031_SRT-A
BusAC144.8 %618.0B894.871.95
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC142.79 %618.0B882.462.01
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
AP_P2-2_WP-138-074_SRT-A
BusAC136.41 %618.0B843.021.83
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_08_P22_102799_SRT-A
BusAC136.19 %618.0B841.641.79
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_48_P71_102649_SRT-A
TowerAC135.55 %618.0B837.691.79
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
TowerAC135.09 %618.0B834.831.79
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Base Case
SingleAC131.72 %493.0A649.41.25
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P1-2_PN-115-094_A_SRT-A
SingleAC127.45 %618.0B787.651.39
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P12_000085_SRT-A
SingleAC127.27 %618.0B786.51.28
GD2PENELEC
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer
PN_P2-3_PN-230-17B25_SRT-A
BreakerAC111.44 %377.0B420.141.26
GD2PENELEC
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer
PN_P2-3_PN-230-997-DRT-067_SRT-SL
BreakerAC111.05 %377.0B418.651.26
GD2PENELEC
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
AP_P2-3_WP-230-708C_SRT-A
BreakerAC100.64 %174.0B175.121.55
GD2PENELEC
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
AP_P2-3_WP-230-708DT_SRT-A
BreakerAC100.51 %174.0B174.881.55
GD2PENELEC
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
AP_P2-3_WP-230-708AT_SRT-A
BreakerAC100.35 %174.0B174.611.55
GD2PENELEC
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
AP_P2-3_WP-230-708C_SRT-A
BreakerAC103.55 %191.0B197.780.98
GD2PENELEC
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
AP_P2-3_WP-230-708DT_SRT-A
BreakerAC103.35 %191.0B197.40.98
GD2PENELEC
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
AP_P2-3_WP-230-708AT_SRT-A
BreakerAC103.23 %191.0B197.170.98
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-456_SRT-A
BreakerAC120.17 %587.0B705.381.54
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-2_WP-230-004_SRT-A
BusAC120.16 %587.0B705.321.54
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-643_SRT-A
BreakerAC120.15 %587.0B705.291.54
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-450T_SRT-A
BreakerAC106.33 %587.0B624.151.54
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-449T_SRT-A
BreakerAC106.27 %587.0B623.821.54
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P1-2_WP-230-005A_SRT-A
SingleAC105.13 %587.0B617.141.08
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P1-3_WP-230-005_SRT-A
SingleAC105.12 %587.0B617.051.08
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P2-3_WP-230-0403-A_SRT-A
BreakerAC102.96 %587.0B604.381.44
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC133.95 %980.0B1312.714.07
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC133.46 %980.0B1307.884.06
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC133.46 %980.0B1307.884.06
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC133.4 %980.0B1307.344.1
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC122.69 %980.0B1202.44.03
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC122.69 %980.0B1202.44.03
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-033T_SRT-A
BusAC110.79 %980.0B1085.773.37
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-059_SRT-A
BusAC110.5 %980.0B1082.933.45
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC108.43 %980.0B1062.613.28
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-036_SRT-A
BusAC108.01 %980.0B1058.483.28
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC107.82 %980.0B1056.63.4
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-083_SRT-A
TowerAC105.56 %980.0B1034.463.28
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC104.25 %980.0B1021.652.83
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC104.25 %980.0B1021.632.83
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P2-3_PN-230-8I_SRT-A
BreakerAC178.33 %160.0B285.322.53
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P7-1_PN-230-002A_SRT-A
TowerAC178.33 %160.0B285.322.53
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1185-2_SRT-A
BusAC156.57 %160.0B250.513.02
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P1-2_PN-230-006_SRT-A
SingleAC140.24 %160.0B224.381.36
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P2-2_PN-115-064_SRT-A
BusAC133.9 %160.0B214.241.45
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P1-2_PN-230-028_SRT-A-1
SingleAC133.21 %160.0B213.141.83
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC129.36 %160.0B206.971.33
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Base Case
SingleAC116.79 %133.0A155.340.93
GD2AP
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
PN_P2-3_PN-230-703T_SRT-A
BreakerAC106.08 %688.0B729.821.55
GD2AP
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
AP_P2-2_WP-230-006T_SRT-A
BusAC105.73 %688.0B727.431.55
GD2AP
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
AP_P2-3_WP-230-459T_SRT-A
BreakerAC105.73 %688.0B727.391.55
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P2-3_PN-230-8I_SRT-A
BreakerAC126.8 %160.0B202.872.54
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P7-1_PN-230-002A_SRT-A
TowerAC126.8 %160.0B202.872.54
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P2-3_PN-230-39C_SRT-A
BreakerAC123.08 %160.0B196.922.64
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1185-2_SRT-A
BusAC110.12 %160.0B176.193.03
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P1-2_PN-230-006_SRT-A
SingleAC109.94 %160.0B175.911.37
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT27_SRT-SL
BreakerAC119.18 %639.0B761.592.35
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-004-DRT-003_SRT-SL
BreakerAC119.18 %639.0B761.582.35
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT26_SRT-SL
BreakerAC119.09 %639.0B761.02.35
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-004-DRT-004_SRT-SL
BreakerAC119.09 %639.0B760.992.35
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-2_PN-500-004A-DRT_SRT-SL
BusAC112.2 %639.0B716.992.35
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC111.54 %639.0B712.742.2
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT32_SRT-A
BreakerAC107.79 %2078.0B2239.811.95
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-002_SRT-SL
BreakerAC107.79 %2078.0B2239.811.95
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-2_PN-230-036_SRT-A
SingleAC156.49 %128.0B200.310.45
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-018_SRT-A
SingleAC139.93 %128.0B179.120.45
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1154-W_SRT-A
BusAC124.81 %128.0B159.760.62
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Base Case
SingleAC116.38 %114.0A132.680.45
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
AP_P2-2_WP-230-001T_SRT-A
BusAC113.06 %128.0B144.710.72
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-3_PN-230-020-DRT_SRT-SL
BreakerAC137.24 %128.0B175.670.57
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-3_PN-230-997-DRT-068_SRT-SL
BreakerAC137.09 %128.0B175.480.57
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-3_PN-230-3C_SRT-A
BreakerAC137.09 %128.0B175.480.57
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-3_PN-230-997-DRT-055_SRT-SL
BreakerAC137.09 %128.0B175.480.57
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-3_PN-230-997-DRT-067_SRT-SL
BreakerAC134.2 %128.0B171.780.55
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-2_PN-115-068T_SRT-A
BusAC120.1 %128.0B153.730.53
⚠
GD2NYISO/PENELEC
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
PN_P2-2_PN-115-069_SRT-A
BusAC118.91 %128.0B152.210.53
⚠

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-171A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-171A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.5 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:227.25
MW Contribution:0.96
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.101
971183AH1-050 GEN
Solar/Wind Harmer
3.056
970647AG2-420 GEN
Solar/Wind Harmer
0.169
20082826HNSMLK 1
Adder
4.017
20083026HNSMLK 3
Adder
4.017
203860AG1-193 C
Solar/Wind Harmer
0.198
971865AH1-452 GEN
Solar/Wind Harmer
1.037
970267AG2-176 GEN
Solar/Wind Harmer
8.051
970713AG2-456 GEN
Solar/Wind Harmer
3.839
971705AH1-358 GEN
Solar/Wind Harmer
1.116
971709AH1-360 GEN
Solar/Wind Harmer
1.116
961971AG1-040 GEN
Solar/Wind Harmer
0.29
203954AE2-126 C
Solar/Wind Harmer
0.286
20072226SHAWVL 2
Adder
6.145
203813AE2-344_GEN
Solar/Wind Harmer
5.097
20091326SHAW-D
Adder
0.286
972169AH1-667 GEN
Solar/Wind Harmer
0.783
20060826PINEY #1
50/50
0.054
971055AG2-654 GEN
Solar/Wind Harmer
1.941
970663AG2-429 GEN
Solar/Wind Harmer
8.559
970663AG2-429 GEN
Solar/Wind Harmer
1.393
203846AF2-130 C
Solar/Wind Harmer
0.471
20083226HNSMLK 5
Adder
4.017
20083926HOMER C3
Adder
37.854
20083826HOMER C2
Adder
35.758
970677AG2-438 GEN
Solar/Wind Harmer
0.502
203804AE2-113_GEN
Solar/Wind Harmer
2.367
966771AG1-548 GEN
Solar/Wind Harmer
7.169
966771AG1-548 GEN
Solar/Wind Harmer
1.389
940863AE2-074 GEN
Solar/Wind Harmer
0.802
203855AF2-088 C
Solar/Wind Harmer
0.086
20083726HOMER C1
Adder
21.846
23513401AL&D6
50/50
0.042
946381AF1-302 GEN
Solar/Wind Harmer
2.052
203848AF2-166 C
Solar/Wind Harmer
1.647
238217AF1-153 C O1
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.182
971933AH1-491 GEN
Solar/Wind Harmer
1.003
203980AG1-197 GEN
Solar/Wind Harmer
0.222
972075AH1-587 GEN
Solar/Wind Harmer
9.775
972077AH1-588 GEN
Solar/Wind Harmer
11.517
972079AH1-589 GEN
Solar/Wind Harmer
9.486
970715AG2-457 GEN
Solar/Wind Harmer
3.839
970305AG2-200 GEN
Solar/Wind Harmer
0.909
971931AH1-490 GEN
Solar/Wind Harmer
0.884
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.882
238219AF1-167 C
Solar/Wind Harmer
1.621
971185AH1-051 GEN
Solar/Wind Harmer
1.833
971355AH1-158 GEN
Solar/Wind Harmer
2.132
203856AF2-165 C
Solar/Wind Harmer
0.88
970647AG2-420 GEN
Solar/Wind Harmer
1.45
20082926HNSMLK 2
Adder
4.017
20083126HNSMLK 4
Adder
4.017
945751AF1-240 GEN
Solar/Wind Harmer
1.058
959441AF2-235 GEN
Solar/Wind Harmer
0.2
957161AF2-010 GEN
Solar/Wind Harmer
3.921
203830AF1-094 GEN
Solar/Wind Harmer
0.304
971703AH1-357 GEN
Solar/Wind Harmer
0.96
971707AH1-359 GEN
Solar/Wind Harmer
0.96
20120126WRREN CT
Adder
2.873
962511AG1-100 GEN
Solar/Wind Harmer
0.267
20334926Z1-069 C
Solar/Wind Harmer
0.923
203962AF1-287 GEN
Solar/Wind Harmer
0.879
203854AF2-039 C
Solar/Wind Harmer
0.178
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.896
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.635
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.905
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-054A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-054A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:149.99 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:226.48
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.041
946381AF1-302 GEN
Solar/Wind Harmer
2.041
203848AF2-166 C
Solar/Wind Harmer
1.637
238217AF1-153 C O1
Solar/Wind Harmer
0.376
203979AG1-198 GEN
Solar/Wind Harmer
0.181
971933AH1-491 GEN
Solar/Wind Harmer
0.997
972075AH1-587 GEN
Solar/Wind Harmer
9.72
203980AG1-197 GEN
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
11.453
972079AH1-589 GEN
Solar/Wind Harmer
9.433
970715AG2-457 GEN
Solar/Wind Harmer
3.818
970305AG2-200 GEN
Solar/Wind Harmer
0.903
971931AH1-490 GEN
Solar/Wind Harmer
0.879
20060826PINEY #1
50/50
0.054
970663AG2-429 GEN
Solar/Wind Harmer
8.508
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.468
20083226HNSMLK 5
Adder
3.994
20083926HOMER C3
Adder
37.649
20083826HOMER C2
Adder
35.564
970677AG2-438 GEN
Solar/Wind Harmer
0.499
203804AE2-113_GEN
Solar/Wind Harmer
2.354
966771AG1-548 GEN
Solar/Wind Harmer
7.125
966771AG1-548 GEN
Solar/Wind Harmer
1.381
940863AE2-074 GEN
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.085
20083726HOMER C1
Adder
21.733
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
238219AF1-167 C
Solar/Wind Harmer
1.603
971185AH1-051 GEN
Solar/Wind Harmer
1.822
971355AH1-158 GEN
Solar/Wind Harmer
2.119
203856AF2-165 C
Solar/Wind Harmer
0.874
970647AG2-420 GEN
Solar/Wind Harmer
1.441
20082926HNSMLK 2
Adder
3.994
20083126HNSMLK 4
Adder
3.994
945751AF1-240 GEN
Solar/Wind Harmer
1.051
959441AF2-235 GEN
Solar/Wind Harmer
0.199
957161AF2-010 GEN
Solar/Wind Harmer
3.897
203830AF1-094 GEN
Solar/Wind Harmer
0.302
971703AH1-357 GEN
Solar/Wind Harmer
0.954
971707AH1-359 GEN
Solar/Wind Harmer
0.954
20120126WRREN CT
Adder
2.856
962511AG1-100 GEN
Solar/Wind Harmer
0.266
20334926Z1-069 C
Solar/Wind Harmer
0.918
203962AF1-287 GEN
Solar/Wind Harmer
0.874
203854AF2-039 C
Solar/Wind Harmer
0.177
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.078
971183AH1-050 GEN
Solar/Wind Harmer
3.037
970647AG2-420 GEN
Solar/Wind Harmer
0.168
20082826HNSMLK 1
Adder
3.994
20083026HNSMLK 3
Adder
3.994
203860AG1-193 C
Solar/Wind Harmer
0.197
971865AH1-452 GEN
Solar/Wind Harmer
0.981
970267AG2-176 GEN
Solar/Wind Harmer
8.003
970713AG2-456 GEN
Solar/Wind Harmer
3.818
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
961971AG1-040 GEN
Solar/Wind Harmer
0.288
203954AE2-126 C
Solar/Wind Harmer
0.284
20072226SHAWVL 2
Adder
6.11
203813AE2-344_GEN
Solar/Wind Harmer
5.067
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.779
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.853
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.138
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.46 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:215.11
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.152
20083026HNSMLK 3
Adder
4.152
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.97
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.346
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.447
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.167
971709AH1-360 GEN
Solar/Wind Harmer
1.167
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.152
970677AG2-438 GEN
Solar/Wind Harmer
0.643
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
966771AG1-548 GEN
Solar/Wind Harmer
9.338
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.753
20083826HOMER C2
Adder
32.828
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.403
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.053
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.436
20082926HNSMLK 2
Adder
4.152
20083126HNSMLK 4
Adder
4.152
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.047
972079AH1-589 GEN
Solar/Wind Harmer
9.923
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.881
G-007ALTFEXP_G-007A->PJM
CMTX
1.776
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.18
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.46 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:215.11
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.053
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.436
20082926HNSMLK 2
Adder
4.152
20083126HNSMLK 4
Adder
4.152
959441AF2-235 GEN
Solar/Wind Harmer
0.21
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.152
20083026HNSMLK 3
Adder
4.152
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.97
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.346
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.447
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.167
971709AH1-360 GEN
Solar/Wind Harmer
1.167
203954AE2-126 C
Solar/Wind Harmer
0.277
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.152
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.338
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.753
20083826HOMER C2
Adder
32.828
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.403
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.047
972079AH1-589 GEN
Solar/Wind Harmer
9.923
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.881
G-007ALTFEXP_G-007A->PJM
CMTX
1.776
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.18
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:209.7
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.309
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.577
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.294
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.558
961971AG1-040 GEN
Solar/Wind Harmer
0.276
970663AG2-429 GEN
Solar/Wind Harmer
6.703
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.743
20083826HOMER C2
Adder
48.877
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.645
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.91
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.908
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.546
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.073
971707AH1-359 GEN
Solar/Wind Harmer
1.073
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.599
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.873
944411AF1-106 GEN
Solar/Wind Harmer
0.098
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.882
972079AH1-589 GEN
Solar/Wind Harmer
10.61
970715AG2-457 GEN
Solar/Wind Harmer
4.294
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.315
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.924
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.022
G-007ALTFEXP_G-007A->PJM
CMTX
0.924
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.625
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:209.7
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.309
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.577
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.294
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.558
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.908
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.546
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.073
971707AH1-359 GEN
Solar/Wind Harmer
1.073
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.599
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.873
944411AF1-106 GEN
Solar/Wind Harmer
0.098
970663AG2-429 GEN
Solar/Wind Harmer
6.703
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.743
20083826HOMER C2
Adder
48.877
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.645
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.91
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.882
972079AH1-589 GEN
Solar/Wind Harmer
10.61
970715AG2-457 GEN
Solar/Wind Harmer
4.294
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.315
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.924
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.022
G-007ALTFEXP_G-007A->PJM
CMTX
0.924
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.625
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.3 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:183.16
MW Contribution:0.67
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.041
203848AF2-166 C
Solar/Wind Harmer
1.142
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.696
972075AH1-587 GEN
Solar/Wind Harmer
6.782
203980AG1-197 GEN
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
7.99
972079AH1-589 GEN
Solar/Wind Harmer
9.433
970715AG2-457 GEN
Solar/Wind Harmer
3.096
970305AG2-200 GEN
Solar/Wind Harmer
0.63
971931AH1-490 GEN
Solar/Wind Harmer
0.613
20060826PINEY #1
50/50
0.054
20066226SCRUB GR
50/50
0.379
20083226HNSMLK 5
50/50
4.238
970663AG2-429 GEN
Solar/Wind Harmer
6.337
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.082
20083926HOMER C3
Adder
37.649
20083826HOMER C2
Adder
35.564
970677AG2-438 GEN
Solar/Wind Harmer
0.388
203804AE2-113_GEN
Solar/Wind Harmer
0.003
966771AG1-548 GEN
Solar/Wind Harmer
1.134
966771AG1-548 GEN
Solar/Wind Harmer
1.418
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.733
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
20082926HNSMLK 2
50/50
4.238
20083126HNSMLK 4
50/50
4.238
238219AF1-167 C
Solar/Wind Harmer
1.117
971185AH1-051 GEN
Solar/Wind Harmer
1.57
971355AH1-158 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
1.005
945751AF1-240 GEN
Solar/Wind Harmer
0.854
957161AF2-010 GEN
Solar/Wind Harmer
2.707
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.666
971707AH1-359 GEN
Solar/Wind Harmer
0.666
20120126WRREN CT
Adder
2.856
20334926Z1-069 C
Solar/Wind Harmer
0.23
203962AF1-287 GEN
Solar/Wind Harmer
0.61
203854AF2-039 C
Solar/Wind Harmer
0
20060826PINEY #1
50/50
0.061
20082826HNSMLK 1
50/50
4.238
20083026HNSMLK 3
50/50
4.238
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
0.168
203860AG1-193 C
Solar/Wind Harmer
0
971865AH1-452 GEN
Solar/Wind Harmer
0.564
970267AG2-176 GEN
Solar/Wind Harmer
5.584
970713AG2-456 GEN
Solar/Wind Harmer
3.096
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
203954AE2-126 C
Solar/Wind Harmer
0
20072226SHAWVL 2
Adder
6.11
203813AE2-344_GEN
Solar/Wind Harmer
3.535
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.543
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.853
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.138
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.904
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:157.92
MW Contribution:0.82
Bus #Bus NameTypeMW Contribution
971055AG2-654 GEN
Solar/Wind Harmer
1.558
970663AG2-429 GEN
Solar/Wind Harmer
7.159
970663AG2-429 GEN
Solar/Wind Harmer
1.165
203846AF2-130 C
Solar/Wind Harmer
0.398
20083226HNSMLK 5
Adder
3.365
20083926HOMER C3
Adder
32.597
23503001MHNG-T155
50/50
0.018
238219AF1-167 C
Solar/Wind Harmer
1.452
203932AE1-123
Adder
1.503
971185AH1-051 GEN
Solar/Wind Harmer
1.549
971355AH1-158 GEN
Solar/Wind Harmer
1.801
203856AF2-165 C
Solar/Wind Harmer
0.743
970647AG2-420 GEN
Solar/Wind Harmer
1.224
945751AF1-240 GEN
Solar/Wind Harmer
0.922
20082926HNSMLK 2
Adder
3.365
20083126HNSMLK 4
Adder
3.365
959441AF2-235 GEN
Solar/Wind Harmer
0.169
971703AH1-357 GEN
Solar/Wind Harmer
0.821
971707AH1-359 GEN
Solar/Wind Harmer
0.821
971865AH1-452 GEN
Solar/Wind Harmer
1.68
238183AE2-316 GEN
Solar/Wind Harmer
3.43
971183AH1-050 GEN
Solar/Wind Harmer
2.581
970647AG2-420 GEN
Solar/Wind Harmer
0.142
20082826HNSMLK 1
Adder
3.365
20083026HNSMLK 3
Adder
3.365
203860AG1-193 C
Solar/Wind Harmer
0.167
970267AG2-176 GEN
Solar/Wind Harmer
6.754
970713AG2-456 GEN
Solar/Wind Harmer
3.282
971705AH1-358 GEN
Solar/Wind Harmer
0.954
971709AH1-360 GEN
Solar/Wind Harmer
0.954
23513401AL&D6
50/50
0.044
946381AF1-302 GEN
Solar/Wind Harmer
1.716
203848AF2-166 C
Solar/Wind Harmer
1.394
238217AF1-153 C O1
Solar/Wind Harmer
0.322
972075AH1-587 GEN
Solar/Wind Harmer
8.365
972077AH1-588 GEN
Solar/Wind Harmer
9.847
972079AH1-589 GEN
Solar/Wind Harmer
8.11
970715AG2-457 GEN
Solar/Wind Harmer
3.282
20083826HOMER C2
Adder
30.791
20083726HOMER C1
Adder
19.751
G-007ALTFEXP_G-007A->PJM
CMTX
1.392
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.658
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.089
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.592
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.844
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-055_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-055_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.36 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:157.58
MW Contribution:0.81
Bus #Bus NameTypeMW Contribution
971055AG2-654 GEN
Solar/Wind Harmer
1.278
970663AG2-429 GEN
Solar/Wind Harmer
6.915
970663AG2-429 GEN
Solar/Wind Harmer
1.126
203846AF2-130 C
Solar/Wind Harmer
0.386
20083226HNSMLK 5
Adder
3.264
20083926HOMER C3
Adder
32.146
20083826HOMER C2
Adder
30.366
20083726HOMER C1
Adder
19.961
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.314
203932AE1-123
Adder
1.455
971185AH1-051 GEN
Solar/Wind Harmer
1.499
971355AH1-158 GEN
Solar/Wind Harmer
1.743
203856AF2-165 C
Solar/Wind Harmer
0.719
970647AG2-420 GEN
Solar/Wind Harmer
1.184
945751AF1-240 GEN
Solar/Wind Harmer
0.9
20082926HNSMLK 2
Adder
3.264
20083126HNSMLK 4
Adder
3.264
959441AF2-235 GEN
Solar/Wind Harmer
0.164
971703AH1-357 GEN
Solar/Wind Harmer
0.805
971707AH1-359 GEN
Solar/Wind Harmer
0.805
23513401AL&D6
50/50
0.037
946381AF1-302 GEN
Solar/Wind Harmer
1.665
203848AF2-166 C
Solar/Wind Harmer
1.35
238217AF1-153 C O1
Solar/Wind Harmer
0.314
972075AH1-587 GEN
Solar/Wind Harmer
8.204
972077AH1-588 GEN
Solar/Wind Harmer
9.656
972079AH1-589 GEN
Solar/Wind Harmer
7.953
970715AG2-457 GEN
Solar/Wind Harmer
3.219
971865AH1-452 GEN
Solar/Wind Harmer
1.465
238183AE2-316 GEN
Solar/Wind Harmer
3.328
971183AH1-050 GEN
Solar/Wind Harmer
2.498
970647AG2-420 GEN
Solar/Wind Harmer
0.138
20082826HNSMLK 1
Adder
3.264
20083026HNSMLK 3
Adder
3.264
203860AG1-193 C
Solar/Wind Harmer
0.162
970267AG2-176 GEN
Solar/Wind Harmer
6.529
970713AG2-456 GEN
Solar/Wind Harmer
3.219
971705AH1-358 GEN
Solar/Wind Harmer
0.936
971709AH1-360 GEN
Solar/Wind Harmer
0.936
G-007ALTFEXP_G-007A->PJM
CMTX
1.582
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.382
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.65
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.926
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-058_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-058_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:157.77 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:329.75
MW Contribution:1.16
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
2.592
203848AF2-166 C
Solar/Wind Harmer
1.516
238217AF1-153 C O1
Solar/Wind Harmer
0.414
972075AH1-587 GEN
Solar/Wind Harmer
11.683
972077AH1-588 GEN
Solar/Wind Harmer
13.963
972079AH1-589 GEN
Solar/Wind Harmer
11.501
970715AG2-457 GEN
Solar/Wind Harmer
4.654
203980AG1-197 GEN
Solar/Wind Harmer
0.262
203979AG1-198 GEN
Solar/Wind Harmer
0.2
971933AH1-491 GEN
Solar/Wind Harmer
1.101
970305AG2-200 GEN
Solar/Wind Harmer
1.08
971931AH1-490 GEN
Solar/Wind Harmer
1.05
203963AG1-253 GEN
Solar/Wind Harmer
0.191
203947AF1-006 C
Solar/Wind Harmer
0.264
20398826ARMNA MT
Solar/Wind Harmer
1.076
203853AF1-134 C O1
Solar/Wind Harmer
0.268
203952AE2-129 C
Solar/Wind Harmer
0.265
203946AE2-131 C
Solar/Wind Harmer
0.265
962411AG1-090 GEN
Solar/Wind Harmer
4.157
20083226HNSMLK 5
50/50
5.395
970663AG2-429 GEN
Solar/Wind Harmer
6.336
970663AG2-429 GEN
Solar/Wind Harmer
1.031
203846AF2-130 C
Solar/Wind Harmer
0.433
20083926HOMER C3
Adder
48.076
20083826HOMER C2
Adder
45.414
203804AE2-113_GEN
Solar/Wind Harmer
2.812
940863AE2-074 GEN
Solar/Wind Harmer
0.975
970677AG2-438 GEN
Solar/Wind Harmer
0.551
966771AG1-548 GEN
Solar/Wind Harmer
7.932
966771AG1-548 GEN
Solar/Wind Harmer
1.537
203855AF2-088 C
Solar/Wind Harmer
0.097
20084926LAKVU GN
Adder
0.093
970555AG2-356 GEN
Solar/Wind Harmer
0.882
965121AG1-377 GEN
Solar/Wind Harmer
0.875
20083726HOMER C1
Adder
26.814
20082926HNSMLK 2
50/50
5.395
20083126HNSMLK 4
50/50
5.395
203932AE1-123
Adder
1.559
971185AH1-051 GEN
Solar/Wind Harmer
1.792
971355AH1-158 GEN
Solar/Wind Harmer
2.084
970647AG2-420 GEN
Solar/Wind Harmer
1.45
203856AF2-165 C
Solar/Wind Harmer
0.864
959441AF2-235 GEN
Solar/Wind Harmer
0.201
945751AF1-240 GEN
Solar/Wind Harmer
0.96
971703AH1-357 GEN
Solar/Wind Harmer
1.164
971707AH1-359 GEN
Solar/Wind Harmer
1.164
238219AF1-167 C
Solar/Wind Harmer
0.772
957161AF2-010 GEN
Solar/Wind Harmer
4.282
203830AF1-094 GEN
Solar/Wind Harmer
0.334
20120126WRREN CT
Adder
3.416
20334926Z1-069 C
Solar/Wind Harmer
1.125
962511AG1-100 GEN
Solar/Wind Harmer
0.317
203962AF1-287 GEN
Solar/Wind Harmer
1.043
203854AF2-039 C
Solar/Wind Harmer
0.202
203948AG1-140 C
Solar/Wind Harmer
0.125
238202AE2-262_GEN
Solar/Wind Harmer
1.209
971627AH1-313 GEN
Solar/Wind Harmer
4.741
20084926LAKVU GN
Adder
0.083
944411AF1-106 GEN
Solar/Wind Harmer
0.103
960051AF2-296 GEN
Solar/Wind Harmer
0.887
965131AG1-378 GEN
Solar/Wind Harmer
0.875
20082826HNSMLK 1
50/50
5.395
20083026HNSMLK 3
50/50
5.395
238183AE2-316 GEN
Solar/Wind Harmer
5.181
971183AH1-050 GEN
Solar/Wind Harmer
2.987
970647AG2-420 GEN
Solar/Wind Harmer
0.169
203860AG1-193 C
Solar/Wind Harmer
0.215
970267AG2-176 GEN
Solar/Wind Harmer
9.453
970713AG2-456 GEN
Solar/Wind Harmer
4.654
971705AH1-358 GEN
Solar/Wind Harmer
1.353
971709AH1-360 GEN
Solar/Wind Harmer
1.353
961971AG1-040 GEN
Solar/Wind Harmer
0.343
203954AE2-126 C
Solar/Wind Harmer
0.329
203813AE2-344_GEN
Solar/Wind Harmer
6.049
20072226SHAWVL 2
Adder
7.005
20091326SHAW-D
Adder
0.324
972169AH1-667 GEN
Solar/Wind Harmer
0.888
203835AF1-098 GEN
Solar/Wind Harmer
1.194
238206AE2-263_GEN
Solar/Wind Harmer
1.127
20084926LAKVU GN
Adder
0.083
20326126BLOSSBCT
Adder
1.064
20335026MILZ1-092
Adder
1.039
944411AF1-106 GEN
Solar/Wind Harmer
0.957
959471AF2-238 GEN
Solar/Wind Harmer
0.267
970337AG2-221 GEN
Solar/Wind Harmer
0.882
G-007ALTFEXP_G-007A->PJM
CMTX
1.529
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.725
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.279
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.216
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.671
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.956
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-194T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-194T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.36 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:293.36
MW Contribution:1.05
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
5.6
20083126HNSMLK 4
50/50
5.6
203932AE1-123
Adder
1.572
971185AH1-051 GEN
Solar/Wind Harmer
1.815
971355AH1-158 GEN
Solar/Wind Harmer
2.111
970647AG2-420 GEN
Solar/Wind Harmer
1.469
203856AF2-165 C
Solar/Wind Harmer
0.874
959441AF2-235 GEN
Solar/Wind Harmer
0.202
945751AF1-240 GEN
Solar/Wind Harmer
0.956
20082826HNSMLK 1
50/50
5.6
20083026HNSMLK 3
50/50
5.6
971183AH1-050 GEN
Solar/Wind Harmer
3.025
970647AG2-420 GEN
Solar/Wind Harmer
0.171
203860AG1-193 C
Solar/Wind Harmer
0.219
970267AG2-176 GEN
Solar/Wind Harmer
9.606
961971AG1-040 GEN
Solar/Wind Harmer
0.345
970713AG2-456 GEN
Solar/Wind Harmer
4.216
971705AH1-358 GEN
Solar/Wind Harmer
1.226
971709AH1-360 GEN
Solar/Wind Harmer
1.226
203813AE2-344_GEN
Solar/Wind Harmer
6.03
203835AF1-098 GEN
Solar/Wind Harmer
1.14
20084926LAKVU GN
Adder
0.081
238183AE2-316 GEN
Solar/Wind Harmer
1.82
20083226HNSMLK 5
50/50
5.6
970663AG2-429 GEN
Solar/Wind Harmer
6.405
970663AG2-429 GEN
Solar/Wind Harmer
1.043
203846AF2-130 C
Solar/Wind Harmer
0.437
20083926HOMER C3
Adder
49.315
20083826HOMER C2
Adder
46.583
970677AG2-438 GEN
Solar/Wind Harmer
0.545
966771AG1-548 GEN
Solar/Wind Harmer
7.844
966771AG1-548 GEN
Solar/Wind Harmer
1.52
940863AE2-074 GEN
Solar/Wind Harmer
0.891
203804AE2-113_GEN
Solar/Wind Harmer
2.339
20084926LAKVU GN
Adder
0.091
20083726HOMER C1
Adder
27.306
203848AF2-166 C
Solar/Wind Harmer
1.53
203980AG1-197 GEN
Solar/Wind Harmer
0.264
203979AG1-198 GEN
Solar/Wind Harmer
0.198
971933AH1-491 GEN
Solar/Wind Harmer
1.091
972077AH1-588 GEN
Solar/Wind Harmer
12.648
972079AH1-589 GEN
Solar/Wind Harmer
10.417
970715AG2-457 GEN
Solar/Wind Harmer
4.216
971931AH1-490 GEN
Solar/Wind Harmer
1.049
972075AH1-587 GEN
Solar/Wind Harmer
9.961
238217AF1-153 C O1
Solar/Wind Harmer
0.287
970305AG2-200 GEN
Solar/Wind Harmer
0.949
203947AF1-006 C
Solar/Wind Harmer
0.26
203963AG1-253 GEN
Solar/Wind Harmer
0.186
946381AF1-302 GEN
Solar/Wind Harmer
0.911
238219AF1-167 C
Solar/Wind Harmer
0.786
957161AF2-010 GEN
Solar/Wind Harmer
4.244
203830AF1-094 GEN
Solar/Wind Harmer
0.33
971703AH1-357 GEN
Solar/Wind Harmer
1.054
971707AH1-359 GEN
Solar/Wind Harmer
1.054
962511AG1-100 GEN
Solar/Wind Harmer
0.317
203962AF1-287 GEN
Solar/Wind Harmer
1.039
20334926Z1-069 C
Solar/Wind Harmer
1.039
20120126WRREN CT
Adder
2.999
203948AG1-140 C
Solar/Wind Harmer
0.122
20084926LAKVU GN
Adder
0.081
G-007ALTFEXP_G-007A->PJM
CMTX
1.365
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.148
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.04
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.819
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.096
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.582
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.827
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.91 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:267.34
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.681
20082826HNSMLK 1
Adder
4.328
20083026HNSMLK 3
Adder
4.328
971183AH1-050 GEN
Solar/Wind Harmer
2.785
970647AG2-420 GEN
Solar/Wind Harmer
0.156
203860AG1-193 C
Solar/Wind Harmer
0.194
970713AG2-456 GEN
Solar/Wind Harmer
4.771
971705AH1-358 GEN
Solar/Wind Harmer
1.387
971709AH1-360 GEN
Solar/Wind Harmer
1.387
970267AG2-176 GEN
Solar/Wind Harmer
8.427
961971AG1-040 GEN
Solar/Wind Harmer
0.308
20326126BLOSSBCT
Adder
1.098
20335026MILZ1-092
Adder
1.09
944411AF1-106 GEN
Solar/Wind Harmer
1.004
203813AE2-344_GEN
Solar/Wind Harmer
5.495
203835AF1-098 GEN
Solar/Wind Harmer
1.105
959471AF2-238 GEN
Solar/Wind Harmer
0.274
970337AG2-221 GEN
Solar/Wind Harmer
0.908
203954AE2-126 C
Solar/Wind Harmer
0.272
970511AG2-327 GEN
Solar/Wind Harmer
0.438
20084926LAKVU GN
Adder
0.076
946381AF1-302 GEN
Solar/Wind Harmer
1.842
203848AF2-166 C
Solar/Wind Harmer
1.441
972077AH1-588 GEN
Solar/Wind Harmer
14.313
972079AH1-589 GEN
Solar/Wind Harmer
11.789
970715AG2-457 GEN
Solar/Wind Harmer
4.771
238217AF1-153 C O1
Solar/Wind Harmer
0.346
972075AH1-587 GEN
Solar/Wind Harmer
11.387
203980AG1-197 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.186
971933AH1-491 GEN
Solar/Wind Harmer
1.021
970305AG2-200 GEN
Solar/Wind Harmer
1.008
20398826ARMNA MT
Solar/Wind Harmer
1.131
971931AH1-490 GEN
Solar/Wind Harmer
0.951
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203859AF2-294 C
Solar/Wind Harmer
0.758
970313AG2-206 GEN
Solar/Wind Harmer
2.104
203947AF1-006 C
Solar/Wind Harmer
0.242
203932AE1-123
Adder
1.501
20082926HNSMLK 2
Adder
4.328
20083126HNSMLK 4
Adder
4.328
971185AH1-051 GEN
Solar/Wind Harmer
1.671
971355AH1-158 GEN
Solar/Wind Harmer
1.943
203856AF2-165 C
Solar/Wind Harmer
0.805
970647AG2-420 GEN
Solar/Wind Harmer
1.343
238219AF1-167 C
Solar/Wind Harmer
0.907
959441AF2-235 GEN
Solar/Wind Harmer
0.188
971703AH1-357 GEN
Solar/Wind Harmer
1.193
971707AH1-359 GEN
Solar/Wind Harmer
1.193
20334926Z1-069 C
Solar/Wind Harmer
1.18
945751AF1-240 GEN
Solar/Wind Harmer
0.844
957161AF2-010 GEN
Solar/Wind Harmer
3.971
203830AF1-094 GEN
Solar/Wind Harmer
0.309
20120126WRREN CT
Adder
3.185
944411AF1-106 GEN
Solar/Wind Harmer
0.108
962511AG1-100 GEN
Solar/Wind Harmer
0.288
203962AF1-287 GEN
Solar/Wind Harmer
0.947
203948AG1-140 C
Solar/Wind Harmer
0.117
970335AG2-220 GEN
Solar/Wind Harmer
1.365
971127AH1-005 GEN
Solar/Wind Harmer
0.881
20084926LAKVU GN
Adder
0.076
970663AG2-429 GEN
Solar/Wind Harmer
7.288
970663AG2-429 GEN
Solar/Wind Harmer
1.186
20083926HOMER C3
Adder
58.145
20083826HOMER C2
Adder
54.924
20083226HNSMLK 5
Adder
4.328
203846AF2-130 C
Solar/Wind Harmer
0.412
940863AE2-074 GEN
Solar/Wind Harmer
1.012
203804AE2-113_GEN
Solar/Wind Harmer
2.68
970677AG2-438 GEN
Solar/Wind Harmer
0.51
966771AG1-548 GEN
Solar/Wind Harmer
7.348
966771AG1-548 GEN
Solar/Wind Harmer
1.424
970555AG2-356 GEN
Solar/Wind Harmer
0.908
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
4.376
G-007ALTFEXP_G-007A->PJM
CMTX
0.722
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.283
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.091
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.104
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.458
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.91 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:267.34
MW Contribution:1.19
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.681
946381AF1-302 GEN
Solar/Wind Harmer
1.842
203848AF2-166 C
Solar/Wind Harmer
1.441
972077AH1-588 GEN
Solar/Wind Harmer
14.313
972079AH1-589 GEN
Solar/Wind Harmer
11.789
970715AG2-457 GEN
Solar/Wind Harmer
4.771
238217AF1-153 C O1
Solar/Wind Harmer
0.346
972075AH1-587 GEN
Solar/Wind Harmer
11.387
203980AG1-197 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.186
971933AH1-491 GEN
Solar/Wind Harmer
1.021
970305AG2-200 GEN
Solar/Wind Harmer
1.008
20398826ARMNA MT
Solar/Wind Harmer
1.131
971931AH1-490 GEN
Solar/Wind Harmer
0.951
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203859AF2-294 C
Solar/Wind Harmer
0.758
970313AG2-206 GEN
Solar/Wind Harmer
2.104
203947AF1-006 C
Solar/Wind Harmer
0.242
203932AE1-123
Adder
1.501
20082926HNSMLK 2
Adder
4.328
20083126HNSMLK 4
Adder
4.328
971185AH1-051 GEN
Solar/Wind Harmer
1.671
971355AH1-158 GEN
Solar/Wind Harmer
1.943
203856AF2-165 C
Solar/Wind Harmer
0.805
970647AG2-420 GEN
Solar/Wind Harmer
1.343
238219AF1-167 C
Solar/Wind Harmer
0.907
959441AF2-235 GEN
Solar/Wind Harmer
0.188
971703AH1-357 GEN
Solar/Wind Harmer
1.193
970663AG2-429 GEN
Solar/Wind Harmer
7.288
970663AG2-429 GEN
Solar/Wind Harmer
1.186
20083926HOMER C3
Adder
58.145
20083826HOMER C2
Adder
54.924
20083226HNSMLK 5
Adder
4.328
203846AF2-130 C
Solar/Wind Harmer
0.412
940863AE2-074 GEN
Solar/Wind Harmer
1.012
203804AE2-113_GEN
Solar/Wind Harmer
2.68
970677AG2-438 GEN
Solar/Wind Harmer
0.51
966771AG1-548 GEN
Solar/Wind Harmer
7.348
966771AG1-548 GEN
Solar/Wind Harmer
1.424
970555AG2-356 GEN
Solar/Wind Harmer
0.908
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
4.376
971707AH1-359 GEN
Solar/Wind Harmer
1.193
20334926Z1-069 C
Solar/Wind Harmer
1.18
945751AF1-240 GEN
Solar/Wind Harmer
0.844
957161AF2-010 GEN
Solar/Wind Harmer
3.971
203830AF1-094 GEN
Solar/Wind Harmer
0.309
20120126WRREN CT
Adder
3.185
944411AF1-106 GEN
Solar/Wind Harmer
0.108
962511AG1-100 GEN
Solar/Wind Harmer
0.288
203962AF1-287 GEN
Solar/Wind Harmer
0.947
203948AG1-140 C
Solar/Wind Harmer
0.117
970335AG2-220 GEN
Solar/Wind Harmer
1.365
971127AH1-005 GEN
Solar/Wind Harmer
0.881
20084926LAKVU GN
Adder
0.076
20082826HNSMLK 1
Adder
4.328
20083026HNSMLK 3
Adder
4.328
971183AH1-050 GEN
Solar/Wind Harmer
2.785
970647AG2-420 GEN
Solar/Wind Harmer
0.156
203860AG1-193 C
Solar/Wind Harmer
0.194
970713AG2-456 GEN
Solar/Wind Harmer
4.771
971705AH1-358 GEN
Solar/Wind Harmer
1.387
971709AH1-360 GEN
Solar/Wind Harmer
1.387
970267AG2-176 GEN
Solar/Wind Harmer
8.427
961971AG1-040 GEN
Solar/Wind Harmer
0.308
20326126BLOSSBCT
Adder
1.098
20335026MILZ1-092
Adder
1.09
944411AF1-106 GEN
Solar/Wind Harmer
1.004
203813AE2-344_GEN
Solar/Wind Harmer
5.495
203835AF1-098 GEN
Solar/Wind Harmer
1.105
959471AF2-238 GEN
Solar/Wind Harmer
0.274
970337AG2-221 GEN
Solar/Wind Harmer
0.908
203954AE2-126 C
Solar/Wind Harmer
0.272
970511AG2-327 GEN
Solar/Wind Harmer
0.438
20084926LAKVU GN
Adder
0.076
G-007ALTFEXP_G-007A->PJM
CMTX
0.722
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.283
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.091
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.104
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.458
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.2 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:265.86
MW Contribution:1.2
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.692
20082826HNSMLK 1
Adder
4.333
20083026HNSMLK 3
Adder
4.333
971183AH1-050 GEN
Solar/Wind Harmer
2.789
970647AG2-420 GEN
Solar/Wind Harmer
0.156
203860AG1-193 C
Solar/Wind Harmer
0.195
970713AG2-456 GEN
Solar/Wind Harmer
4.787
971705AH1-358 GEN
Solar/Wind Harmer
1.391
971709AH1-360 GEN
Solar/Wind Harmer
1.391
970267AG2-176 GEN
Solar/Wind Harmer
8.44
961971AG1-040 GEN
Solar/Wind Harmer
0.309
20326126BLOSSBCT
Adder
1.102
20335026MILZ1-092
Adder
1.094
944411AF1-106 GEN
Solar/Wind Harmer
1.008
203813AE2-344_GEN
Solar/Wind Harmer
5.505
203835AF1-098 GEN
Solar/Wind Harmer
1.107
959471AF2-238 GEN
Solar/Wind Harmer
0.275
970337AG2-221 GEN
Solar/Wind Harmer
0.911
203954AE2-126 C
Solar/Wind Harmer
0.274
970511AG2-327 GEN
Solar/Wind Harmer
0.44
20084926LAKVU GN
Adder
0.076
970663AG2-429 GEN
Solar/Wind Harmer
7.295
970663AG2-429 GEN
Solar/Wind Harmer
1.188
20083926HOMER C3
Adder
58.222
20083826HOMER C2
Adder
54.997
20083226HNSMLK 5
Adder
4.333
203846AF2-130 C
Solar/Wind Harmer
0.412
940863AE2-074 GEN
Solar/Wind Harmer
1.016
203804AE2-113_GEN
Solar/Wind Harmer
2.693
970677AG2-438 GEN
Solar/Wind Harmer
0.511
966771AG1-548 GEN
Solar/Wind Harmer
7.362
966771AG1-548 GEN
Solar/Wind Harmer
1.427
970555AG2-356 GEN
Solar/Wind Harmer
0.911
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
4.384
203932AE1-123
Adder
1.503
20082926HNSMLK 2
Adder
4.333
20083126HNSMLK 4
Adder
4.333
971185AH1-051 GEN
Solar/Wind Harmer
1.673
971355AH1-158 GEN
Solar/Wind Harmer
1.946
203856AF2-165 C
Solar/Wind Harmer
0.807
970647AG2-420 GEN
Solar/Wind Harmer
1.345
238219AF1-167 C
Solar/Wind Harmer
0.908
959441AF2-235 GEN
Solar/Wind Harmer
0.188
971703AH1-357 GEN
Solar/Wind Harmer
1.197
971707AH1-359 GEN
Solar/Wind Harmer
1.197
20334926Z1-069 C
Solar/Wind Harmer
1.184
945751AF1-240 GEN
Solar/Wind Harmer
0.845
957161AF2-010 GEN
Solar/Wind Harmer
3.978
203830AF1-094 GEN
Solar/Wind Harmer
0.31
20120126WRREN CT
Adder
3.198
944411AF1-106 GEN
Solar/Wind Harmer
0.108
962511AG1-100 GEN
Solar/Wind Harmer
0.288
203962AF1-287 GEN
Solar/Wind Harmer
0.949
203948AG1-140 C
Solar/Wind Harmer
0.117
970335AG2-220 GEN
Solar/Wind Harmer
1.37
971127AH1-005 GEN
Solar/Wind Harmer
0.884
20084926LAKVU GN
Adder
0.076
946381AF1-302 GEN
Solar/Wind Harmer
1.848
203848AF2-166 C
Solar/Wind Harmer
1.443
972077AH1-588 GEN
Solar/Wind Harmer
14.36
972079AH1-589 GEN
Solar/Wind Harmer
11.828
970715AG2-457 GEN
Solar/Wind Harmer
4.787
238217AF1-153 C O1
Solar/Wind Harmer
0.348
972075AH1-587 GEN
Solar/Wind Harmer
11.438
203980AG1-197 GEN
Solar/Wind Harmer
0.236
203979AG1-198 GEN
Solar/Wind Harmer
0.186
971933AH1-491 GEN
Solar/Wind Harmer
1.023
970305AG2-200 GEN
Solar/Wind Harmer
1.011
20398826ARMNA MT
Solar/Wind Harmer
1.135
971931AH1-490 GEN
Solar/Wind Harmer
0.953
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203859AF2-294 C
Solar/Wind Harmer
0.76
970313AG2-206 GEN
Solar/Wind Harmer
2.112
203947AF1-006 C
Solar/Wind Harmer
0.242
G-007ALTFEXP_G-007A->PJM
CMTX
0.731
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.323
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.115
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.325
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.461
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.14 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:253.19
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
203932AE1-123
Adder
1.585
20082926HNSMLK 2
Adder
4.519
20083126HNSMLK 4
Adder
4.519
971185AH1-051 GEN
Solar/Wind Harmer
1.871
971355AH1-158 GEN
Solar/Wind Harmer
2.176
203856AF2-165 C
Solar/Wind Harmer
0.912
970647AG2-420 GEN
Solar/Wind Harmer
1.526
959441AF2-235 GEN
Solar/Wind Harmer
0.224
957161AF2-010 GEN
Solar/Wind Harmer
5.322
203830AF1-094 GEN
Solar/Wind Harmer
0.417
962511AG1-100 GEN
Solar/Wind Harmer
0.413
203962AF1-287 GEN
Solar/Wind Harmer
1.36
238219AF1-167 C
Solar/Wind Harmer
0.902
20084926LAKVU GN
Adder
0.115
203948AG1-140 C
Solar/Wind Harmer
0.168
945751AF1-240 GEN
Solar/Wind Harmer
0.965
20120126WRREN CT
Adder
3.732
971703AH1-357 GEN
Solar/Wind Harmer
1.07
971707AH1-359 GEN
Solar/Wind Harmer
1.07
20334926Z1-069 C
Solar/Wind Harmer
0.995
203854AF2-039 C
Solar/Wind Harmer
0.178
238183AE2-316 GEN
Solar/Wind Harmer
3.654
20082826HNSMLK 1
Adder
4.519
20083026HNSMLK 3
Adder
4.519
971183AH1-050 GEN
Solar/Wind Harmer
3.119
970647AG2-420 GEN
Solar/Wind Harmer
0.177
203860AG1-193 C
Solar/Wind Harmer
0.227
970267AG2-176 GEN
Solar/Wind Harmer
10.753
961971AG1-040 GEN
Solar/Wind Harmer
0.421
203813AE2-344_GEN
Solar/Wind Harmer
7.921
20084926LAKVU GN
Adder
0.115
203835AF1-098 GEN
Solar/Wind Harmer
1.557
970713AG2-456 GEN
Solar/Wind Harmer
4.282
971705AH1-358 GEN
Solar/Wind Harmer
1.245
971709AH1-360 GEN
Solar/Wind Harmer
1.245
203954AE2-126 C
Solar/Wind Harmer
0.292
20072226SHAWVL 2
Adder
6.138
972169AH1-667 GEN
Solar/Wind Harmer
0.785
20091326SHAW-D
Adder
0.287
970663AG2-429 GEN
Solar/Wind Harmer
7.167
970663AG2-429 GEN
Solar/Wind Harmer
1.167
203846AF2-130 C
Solar/Wind Harmer
0.448
20083226HNSMLK 5
Adder
4.519
970677AG2-438 GEN
Solar/Wind Harmer
0.689
966771AG1-548 GEN
Solar/Wind Harmer
10.012
966771AG1-548 GEN
Solar/Wind Harmer
1.94
20084926LAKVU GN
Adder
0.129
203804AE2-113_GEN
Solar/Wind Harmer
2.527
20083926HOMER C3
Adder
37.003
20083826HOMER C2
Adder
34.953
940863AE2-074 GEN
Solar/Wind Harmer
0.872
203855AF2-088 C
Solar/Wind Harmer
0.086
20083726HOMER C1
Adder
21.752
946381AF1-302 GEN
Solar/Wind Harmer
1.828
203848AF2-166 C
Solar/Wind Harmer
1.57
203980AG1-197 GEN
Solar/Wind Harmer
0.318
203979AG1-198 GEN
Solar/Wind Harmer
0.25
971933AH1-491 GEN
Solar/Wind Harmer
1.377
971931AH1-490 GEN
Solar/Wind Harmer
1.367
203947AF1-006 C
Solar/Wind Harmer
0.371
203963AG1-253 GEN
Solar/Wind Harmer
0.256
238217AF1-153 C O1
Solar/Wind Harmer
0.36
970305AG2-200 GEN
Solar/Wind Harmer
1.18
972077AH1-588 GEN
Solar/Wind Harmer
12.845
972079AH1-589 GEN
Solar/Wind Harmer
10.579
970715AG2-457 GEN
Solar/Wind Harmer
4.282
972075AH1-587 GEN
Solar/Wind Harmer
10.512
G-007ALTFEXP_G-007A->PJM
CMTX
1.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.894
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.601
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.253
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.106
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.786
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.135
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTR-01KITTAN 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.44 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:226.63
MW Contribution:0.87
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
1.839
203848AF2-166 C
Solar/Wind Harmer
1.396
238217AF1-153 C O1
Solar/Wind Harmer
0.331
972075AH1-587 GEN
Solar/Wind Harmer
8.808
203979AG1-198 GEN
Solar/Wind Harmer
0.159
971933AH1-491 GEN
Solar/Wind Harmer
0.876
972077AH1-588 GEN
Solar/Wind Harmer
10.41
972079AH1-589 GEN
Solar/Wind Harmer
8.574
970715AG2-457 GEN
Solar/Wind Harmer
3.47
203980AG1-197 GEN
Solar/Wind Harmer
0.197
203932AE1-123
Adder
1.492
971185AH1-051 GEN
Solar/Wind Harmer
1.569
971355AH1-158 GEN
Solar/Wind Harmer
1.825
203856AF2-165 C
Solar/Wind Harmer
0.753
970647AG2-420 GEN
Solar/Wind Harmer
1.245
20082926HNSMLK 2
Adder
3.613
20083126HNSMLK 4
Adder
3.613
945751AF1-240 GEN
Solar/Wind Harmer
0.918
959441AF2-235 GEN
Solar/Wind Harmer
0.172
238219AF1-167 C
Solar/Wind Harmer
0.617
957161AF2-010 GEN
Solar/Wind Harmer
3.422
203830AF1-094 GEN
Solar/Wind Harmer
0.265
971703AH1-357 GEN
Solar/Wind Harmer
0.868
971707AH1-359 GEN
Solar/Wind Harmer
0.868
238183AE2-316 GEN
Solar/Wind Harmer
3.675
971183AH1-050 GEN
Solar/Wind Harmer
2.615
970647AG2-420 GEN
Solar/Wind Harmer
0.145
20082826HNSMLK 1
Adder
3.613
20083026HNSMLK 3
Adder
3.613
203860AG1-193 C
Solar/Wind Harmer
0.173
970267AG2-176 GEN
Solar/Wind Harmer
7.122
970713AG2-456 GEN
Solar/Wind Harmer
3.47
971705AH1-358 GEN
Solar/Wind Harmer
1.009
971709AH1-360 GEN
Solar/Wind Harmer
1.009
970663AG2-429 GEN
Solar/Wind Harmer
7.325
970663AG2-429 GEN
Solar/Wind Harmer
1.192
203846AF2-130 C
Solar/Wind Harmer
0.399
20083226HNSMLK 5
Adder
3.613
20083926HOMER C3
Adder
34.842
20083826HOMER C2
Adder
32.912
203804AE2-113_GEN
Solar/Wind Harmer
2.129
970677AG2-438 GEN
Solar/Wind Harmer
0.438
20083726HOMER C1
Adder
20.778
G-007ALTFEXP_G-007A->PJM
CMTX
1.384
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.135
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.045
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.853
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.19
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.09
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.591
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.842
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.11 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:824.45
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
36.967
972079AH1-589 GEN
Solar/Wind Harmer
30.448
970715AG2-457 GEN
Solar/Wind Harmer
12.322
20398826ARMNA MT
Solar/Wind Harmer
3.222
203980AG1-197 GEN
Solar/Wind Harmer
0.587
203859AF2-294 C
Solar/Wind Harmer
2.162
971931AH1-490 GEN
Solar/Wind Harmer
2.398
972075AH1-587 GEN
Solar/Wind Harmer
23.958
970313AG2-206 GEN
Solar/Wind Harmer
5.725
203963AG1-253 GEN
Solar/Wind Harmer
0.459
203947AF1-006 C
Solar/Wind Harmer
0.614
970305AG2-200 GEN
Solar/Wind Harmer
2.05
203979AG1-198 GEN
Solar/Wind Harmer
0.297
971933AH1-491 GEN
Solar/Wind Harmer
1.633
946381AF1-302 GEN
Solar/Wind Helper
0.27
20083926HOMER C3
50/50
226.957
20083826HOMER C2
50/50
214.387
20083226HNSMLK 5
50/50
15.84
940863AE2-074 GEN
Solar/Wind Harmer
2.709
970555AG2-356 GEN
Solar/Wind Harmer
2.454
20084926LAKVU GN
Adder
0.218
203804AE2-113_GEN
Solar/Wind Harmer
5.066
966771AG1-548 GEN
Solar/Wind Harmer
12.388
966771AG1-548 GEN
Solar/Wind Harmer
2.401
970677AG2-438 GEN
Solar/Wind Harmer
0.817
203926AA2-133 GEN
Adder
1.897
20334726NME_Y1-047
Adder
1.725
20390726Y2-042
Adder
1.383
20083726HOMER C1
Adder
13.453
20082926HNSMLK 2
50/50
15.84
20083126HNSMLK 4
50/50
15.84
20334926Z1-069 C
Solar/Wind Harmer
3.275
971703AH1-357 GEN
Solar/Wind Harmer
3.081
971707AH1-359 GEN
Solar/Wind Harmer
3.081
944411AF1-106 GEN
Solar/Wind Harmer
0.309
970335AG2-220 GEN
Solar/Wind Harmer
3.722
971127AH1-005 GEN
Solar/Wind Harmer
2.401
962511AG1-100 GEN
Solar/Wind Harmer
0.725
203962AF1-287 GEN
Solar/Wind Harmer
2.366
203948AG1-140 C
Solar/Wind Harmer
0.301
20084926LAKVU GN
Adder
0.194
20120126WRREN CT
Adder
6.48
20328326MANOR_T86
Adder
0.126
20335126GROZ1-110
Adder
2.063
20335226CANZ2-011
Adder
2.006
203830AF1-094 GEN
Solar/Wind Harmer
0.495
957161AF2-010 GEN
Solar/Wind Harmer
6.121
972271AH1-720 GEN
Adder
5.081
941421AE2-139 GEN
Solar/Wind Harmer
2.266
200917MEHOOPANY_G
Solar/Wind Harmer
2.568
970679AG2-439 GEN
Solar/Wind Harmer
0.578
20082826HNSMLK 1
50/50
15.84
20083026HNSMLK 3
50/50
15.84
20335026MILZ1-092
50/50
3.306
20326126BLOSSBCT
50/50
3.142
970713AG2-456 GEN
Solar/Wind Harmer
12.322
971705AH1-358 GEN
Solar/Wind Harmer
3.582
971709AH1-360 GEN
Solar/Wind Harmer
3.582
970267AG2-176 GEN
Solar/Wind Harmer
20.835
944411AF1-106 GEN
Solar/Wind Harmer
2.87
961971AG1-040 GEN
Solar/Wind Harmer
0.769
959471AF2-238 GEN
Solar/Wind Harmer
0.742
970337AG2-221 GEN
Solar/Wind Harmer
2.454
970511AG2-327 GEN
Solar/Wind Harmer
1.193
203813AE2-344_GEN
Solar/Wind Harmer
13.77
20084926LAKVU GN
Adder
0.194
203835AF1-098 GEN
Solar/Wind Harmer
2.614
203860AG1-193 C
Solar/Wind Harmer
0.303
24035802GEN-Y1-012
Adder
0.247
961581Q1080_CY23
External Queue
32.24351119995117
G-007ALTFEXP_G-007A->PJM
CMTX
0.335
WECLTFEXP_WEC->PJM
CLTF
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.225
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.037
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.031
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.801
MECLTFEXP_MEC->PJM
CLTF
0.025

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.11 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:824.45
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
36.967
972079AH1-589 GEN
Solar/Wind Harmer
30.448
970715AG2-457 GEN
Solar/Wind Harmer
12.322
20398826ARMNA MT
Solar/Wind Harmer
3.222
203980AG1-197 GEN
Solar/Wind Harmer
0.587
203859AF2-294 C
Solar/Wind Harmer
2.162
971931AH1-490 GEN
Solar/Wind Harmer
2.398
972075AH1-587 GEN
Solar/Wind Harmer
23.958
970313AG2-206 GEN
Solar/Wind Harmer
5.725
20083926HOMER C3
50/50
226.957
20083826HOMER C2
50/50
214.387
20083226HNSMLK 5
50/50
15.84
940863AE2-074 GEN
Solar/Wind Harmer
2.709
970555AG2-356 GEN
Solar/Wind Harmer
2.454
20084926LAKVU GN
Adder
0.218
203804AE2-113_GEN
Solar/Wind Harmer
5.066
966771AG1-548 GEN
Solar/Wind Harmer
12.388
966771AG1-548 GEN
Solar/Wind Harmer
2.401
970677AG2-438 GEN
Solar/Wind Harmer
0.817
203926AA2-133 GEN
Adder
1.897
20334726NME_Y1-047
Adder
1.725
20390726Y2-042
Adder
1.383
20083726HOMER C1
Adder
13.453
20082926HNSMLK 2
50/50
15.84
20083126HNSMLK 4
50/50
15.84
20334926Z1-069 C
Solar/Wind Harmer
3.275
971703AH1-357 GEN
Solar/Wind Harmer
3.081
971707AH1-359 GEN
Solar/Wind Harmer
3.081
944411AF1-106 GEN
Solar/Wind Harmer
0.309
970335AG2-220 GEN
Solar/Wind Harmer
3.722
971127AH1-005 GEN
Solar/Wind Harmer
2.401
962511AG1-100 GEN
Solar/Wind Harmer
0.725
203962AF1-287 GEN
Solar/Wind Harmer
2.366
203948AG1-140 C
Solar/Wind Harmer
0.301
20084926LAKVU GN
Adder
0.194
20120126WRREN CT
Adder
6.48
20328326MANOR_T86
Adder
0.126
20335126GROZ1-110
Adder
2.063
20335226CANZ2-011
Adder
2.006
203830AF1-094 GEN
Solar/Wind Harmer
0.495
957161AF2-010 GEN
Solar/Wind Harmer
6.121
972271AH1-720 GEN
Adder
5.081
941421AE2-139 GEN
Solar/Wind Harmer
2.266
200917MEHOOPANY_G
Solar/Wind Harmer
2.568
970679AG2-439 GEN
Solar/Wind Harmer
0.578
20082826HNSMLK 1
50/50
15.84
20083026HNSMLK 3
50/50
15.84
20335026MILZ1-092
50/50
3.306
20326126BLOSSBCT
50/50
3.142
970713AG2-456 GEN
Solar/Wind Harmer
12.322
971705AH1-358 GEN
Solar/Wind Harmer
3.582
971709AH1-360 GEN
Solar/Wind Harmer
3.582
970267AG2-176 GEN
Solar/Wind Harmer
20.835
944411AF1-106 GEN
Solar/Wind Harmer
2.87
961971AG1-040 GEN
Solar/Wind Harmer
0.769
959471AF2-238 GEN
Solar/Wind Harmer
0.742
970337AG2-221 GEN
Solar/Wind Harmer
2.454
970511AG2-327 GEN
Solar/Wind Harmer
1.193
203813AE2-344_GEN
Solar/Wind Harmer
13.77
20084926LAKVU GN
Adder
0.194
203835AF1-098 GEN
Solar/Wind Harmer
2.614
203860AG1-193 C
Solar/Wind Harmer
0.303
24035802GEN-Y1-012
Adder
0.247
203963AG1-253 GEN
Solar/Wind Harmer
0.459
203947AF1-006 C
Solar/Wind Harmer
0.614
970305AG2-200 GEN
Solar/Wind Harmer
2.05
203979AG1-198 GEN
Solar/Wind Harmer
0.297
971933AH1-491 GEN
Solar/Wind Harmer
1.633
946381AF1-302 GEN
Solar/Wind Helper
0.27
961581Q1080_CY23
External Queue
32.24351119995117
G-007ALTFEXP_G-007A->PJM
CMTX
0.335
WECLTFEXP_WEC->PJM
CLTF
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.225
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.219
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.037
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.801
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.025

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.01 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:823.8
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
226.986
20083826HOMER C2
50/50
214.415
20083226HNSMLK 5
50/50
15.842
940863AE2-074 GEN
Solar/Wind Harmer
2.71
970555AG2-356 GEN
Solar/Wind Harmer
2.455
20082926HNSMLK 2
50/50
15.842
20083126HNSMLK 4
50/50
15.842
20334926Z1-069 C
Solar/Wind Harmer
3.276
971703AH1-357 GEN
Solar/Wind Harmer
3.082
971707AH1-359 GEN
Solar/Wind Harmer
3.082
944411AF1-106 GEN
Solar/Wind Harmer
0.309
970335AG2-220 GEN
Solar/Wind Harmer
3.723
971127AH1-005 GEN
Solar/Wind Harmer
2.402
962511AG1-100 GEN
Solar/Wind Harmer
0.725
203962AF1-287 GEN
Solar/Wind Harmer
2.367
203948AG1-140 C
Solar/Wind Harmer
0.301
20084926LAKVU GN
Adder
0.194
20120126WRREN CT
Adder
6.484
20328326MANOR_T86
Adder
0.127
20335126GROZ1-110
Adder
2.065
20335226CANZ2-011
Adder
2.007
203830AF1-094 GEN
Solar/Wind Harmer
0.495
957161AF2-010 GEN
Solar/Wind Harmer
6.123
972271AH1-720 GEN
Adder
5.085
941421AE2-139 GEN
Solar/Wind Harmer
2.268
200917MEHOOPANY_G
Solar/Wind Harmer
2.57
970679AG2-439 GEN
Solar/Wind Harmer
0.578
20084926LAKVU GN
Adder
0.218
203804AE2-113_GEN
Solar/Wind Harmer
5.071
966771AG1-548 GEN
Solar/Wind Harmer
12.393
966771AG1-548 GEN
Solar/Wind Harmer
2.402
970677AG2-438 GEN
Solar/Wind Harmer
0.817
203926AA2-133 GEN
Adder
1.898
20334726NME_Y1-047
Adder
1.726
20390726Y2-042
Adder
1.384
20083726HOMER C1
Adder
13.456
20082826HNSMLK 1
50/50
15.842
20083026HNSMLK 3
50/50
15.842
20335026MILZ1-092
50/50
3.307
20326126BLOSSBCT
50/50
3.144
970713AG2-456 GEN
Solar/Wind Harmer
12.328
971705AH1-358 GEN
Solar/Wind Harmer
3.584
971709AH1-360 GEN
Solar/Wind Harmer
3.584
970267AG2-176 GEN
Solar/Wind Harmer
20.839
944411AF1-106 GEN
Solar/Wind Harmer
2.871
961971AG1-040 GEN
Solar/Wind Harmer
0.769
959471AF2-238 GEN
Solar/Wind Harmer
0.742
970337AG2-221 GEN
Solar/Wind Harmer
2.455
970511AG2-327 GEN
Solar/Wind Harmer
1.193
203813AE2-344_GEN
Solar/Wind Harmer
13.774
20084926LAKVU GN
Adder
0.194
203835AF1-098 GEN
Solar/Wind Harmer
2.615
203860AG1-193 C
Solar/Wind Harmer
0.303
24035802GEN-Y1-012
Adder
0.247
972077AH1-588 GEN
Solar/Wind Harmer
36.984
972079AH1-589 GEN
Solar/Wind Harmer
30.462
970715AG2-457 GEN
Solar/Wind Harmer
12.328
20398826ARMNA MT
Solar/Wind Harmer
3.224
203980AG1-197 GEN
Solar/Wind Harmer
0.587
203859AF2-294 C
Solar/Wind Harmer
2.163
971931AH1-490 GEN
Solar/Wind Harmer
2.398
972075AH1-587 GEN
Solar/Wind Harmer
23.976
970313AG2-206 GEN
Solar/Wind Harmer
5.727
203963AG1-253 GEN
Solar/Wind Harmer
0.459
203947AF1-006 C
Solar/Wind Harmer
0.614
970305AG2-200 GEN
Solar/Wind Harmer
2.051
203979AG1-198 GEN
Solar/Wind Harmer
0.297
971933AH1-491 GEN
Solar/Wind Harmer
1.634
946381AF1-302 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
32.23988342285156
G-007ALTFEXP_G-007A->PJM
CMTX
0.338
WECLTFEXP_WEC->PJM
CLTF
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.24
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.228
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.033
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.795
MECLTFEXP_MEC->PJM
CLTF
0.024

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-345-997-DRT-031_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-345-997-DRT-031_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:678.5
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.239
20398826ARMNA MT
Solar/Wind Harmer
1.738
203859AF2-294 C
Solar/Wind Harmer
1.155
972077AH1-588 GEN
Solar/Wind Harmer
16.27
972079AH1-589 GEN
Solar/Wind Harmer
13.4
970715AG2-457 GEN
Solar/Wind Harmer
5.423
203839AF1-321 GEN
Solar/Wind Harmer
1.306
20084626FORWARD
Solar/Wind Harmer
0.513
970313AG2-206 GEN
Solar/Wind Harmer
3.085
203857AF2-221 C
Solar/Wind Harmer
0.96
970123AG2-090 GEN
Solar/Wind Harmer
0.896
20088626ARWF_N39
Solar/Wind Harmer
1.105
20303426NA_O38_P22
Solar/Wind Harmer
0.894
20088926STNY CRK
Solar/Wind Harmer
0.709
971427AH1-205 GEN
Solar/Wind Harmer
0.857
20083426SW_E13_K22
Solar/Wind Harmer
0.171
203940AF1-140 C
Solar/Wind Harmer
0.275
971441AH1-212 GEN
Solar/Wind Harmer
1.004
972075AH1-587 GEN
Solar/Wind Harmer
9.648
944781AF1-143 GEN
Solar/Wind Harmer
1.447
946381AF1-302 GEN
Solar/Wind Helper
0.342
238217AF1-153 C O1
Solar/Wind Helper
0.126
20083226HNSMLK 5
50/50
21.026
20083926HOMER C3
50/50
137.1
20083826HOMER C2
50/50
129.507
20083726HOMER C1
50/50
74.399
940863AE2-074 GEN
Solar/Wind Harmer
1.3
970555AG2-356 GEN
Solar/Wind Harmer
1.313
203961AE2-224 GEN
Solar/Wind Harmer
1.908
20092526R32
Solar/Wind Harmer
1.054
203844AF2-092 C
Solar/Wind Harmer
0.698
203850AG1-041 C
Solar/Wind Harmer
0.692
203926AA2-133 GEN
Adder
1.045
20091526CHSTN_FL
Solar/Wind Harmer
0.391
203846AF2-130 C
Solar/Wind Helper
0.558
20082926HNSMLK 2
50/50
21.026
20083126HNSMLK 4
50/50
21.026
20334926Z1-069 C
Solar/Wind Harmer
1.642
944411AF1-106 GEN
Solar/Wind Harmer
0.163
971703AH1-357 GEN
Solar/Wind Harmer
1.356
971707AH1-359 GEN
Solar/Wind Harmer
1.356
203841AF2-001_GEN
Solar/Wind Harmer
1.306
970335AG2-220 GEN
Solar/Wind Harmer
2.006
971127AH1-005 GEN
Solar/Wind Harmer
1.294
971879AH1-460 GEN
Solar/Wind Harmer
4.261
970125AG2-091 GEN
Solar/Wind Harmer
0.384
971419AH1-201 GEN
Solar/Wind Harmer
1.842
20079426CONEMAGH
Adder
0.668
20328326MANOR_T86
Adder
0.068
20089126CSLMN_L13
Solar/Wind Harmer
0.422
20089026BF_G21_K23
Solar/Wind Harmer
0.334
20335126GROZ1-110
Adder
1.058
20335226CANZ2-011
Adder
1.028
959441AF2-235 GEN
Solar/Wind Helper
0.184
20082826HNSMLK 1
50/50
21.026
20083026HNSMLK 3
50/50
21.026
20335026MILZ1-092
Adder
1.649
944411AF1-106 GEN
Solar/Wind Harmer
1.519
20326126BLOSSBCT
Adder
1.564
970713AG2-456 GEN
Solar/Wind Harmer
5.423
971705AH1-358 GEN
Solar/Wind Harmer
1.577
971709AH1-360 GEN
Solar/Wind Harmer
1.577
959471AF2-238 GEN
Solar/Wind Harmer
0.397
970337AG2-221 GEN
Solar/Wind Harmer
1.313
203843AF2-002_GEN
Solar/Wind Harmer
0.653
970631AG2-411 GEN
Solar/Wind Harmer
4.085
970511AG2-327 GEN
Solar/Wind Harmer
0.643
957561AF2-050 GEN
Solar/Wind Harmer
3.149
20088826HIGHLAND
Solar/Wind Harmer
0.983
971423AH1-203 GEN
Solar/Wind Harmer
4.045
964201AG1-281 GEN
Solar/Wind Harmer
0.315
20089226LOOKOUT
Solar/Wind Harmer
0.411
203860AG1-193 C
Solar/Wind Helper
0.159
961581Q1080_CY23
External Queue
23.753013610839844
G-007ALTFEXP_G-007A->PJM
CMTX
2.924
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.196
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.877
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
8.066
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.387
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.14
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.201
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.728
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.73 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:274.41
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.966
203848AF2-166 C
Solar/Wind Harmer
1.578
972077AH1-588 GEN
Solar/Wind Harmer
15.298
972079AH1-589 GEN
Solar/Wind Harmer
12.6
970715AG2-457 GEN
Solar/Wind Harmer
5.099
238217AF1-153 C O1
Solar/Wind Harmer
0.373
972075AH1-587 GEN
Solar/Wind Harmer
12.162
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.108
970305AG2-200 GEN
Solar/Wind Harmer
1.082
971931AH1-490 GEN
Solar/Wind Harmer
1.029
20398826ARMNA MT
Solar/Wind Harmer
1.201
203963AG1-253 GEN
Solar/Wind Harmer
0.193
203859AF2-294 C
Solar/Wind Harmer
0.804
203947AF1-006 C
Solar/Wind Harmer
0.262
970313AG2-206 GEN
Solar/Wind Harmer
2.232
20083926HOMER C3
50/50
65.798
20083826HOMER C2
50/50
62.154
970663AG2-429 GEN
Solar/Wind Harmer
7.966
970663AG2-429 GEN
Solar/Wind Harmer
1.297
20083226HNSMLK 5
Adder
4.637
203846AF2-130 C
Solar/Wind Harmer
0.451
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.08
203804AE2-113_GEN
Solar/Wind Harmer
2.862
970677AG2-438 GEN
Solar/Wind Harmer
0.554
966771AG1-548 GEN
Solar/Wind Harmer
7.972
966771AG1-548 GEN
Solar/Wind Harmer
1.545
970555AG2-356 GEN
Solar/Wind Harmer
0.963
20084926LAKVU GN
Adder
0.093
20083726HOMER C1
Adder
4.668
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.468
203932AE1-123
Adder
1.649
20082926HNSMLK 2
Adder
4.637
20083126HNSMLK 4
Adder
4.637
971185AH1-051 GEN
Solar/Wind Harmer
1.823
971355AH1-158 GEN
Solar/Wind Harmer
2.12
203856AF2-165 C
Solar/Wind Harmer
0.879
970647AG2-420 GEN
Solar/Wind Harmer
1.464
959441AF2-235 GEN
Solar/Wind Harmer
0.205
971703AH1-357 GEN
Solar/Wind Harmer
1.275
971707AH1-359 GEN
Solar/Wind Harmer
1.275
20334926Z1-069 C
Solar/Wind Harmer
1.258
945751AF1-240 GEN
Solar/Wind Harmer
0.899
957161AF2-010 GEN
Solar/Wind Harmer
4.311
203830AF1-094 GEN
Solar/Wind Harmer
0.336
20120126WRREN CT
Adder
3.42
962511AG1-100 GEN
Solar/Wind Harmer
0.311
203962AF1-287 GEN
Solar/Wind Harmer
1.025
944411AF1-106 GEN
Solar/Wind Harmer
0.115
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.448
971127AH1-005 GEN
Solar/Wind Harmer
0.934
238183AE2-316 GEN
Solar/Wind Harmer
3.929
20082826HNSMLK 1
Adder
4.637
20083026HNSMLK 3
Adder
4.637
971183AH1-050 GEN
Solar/Wind Harmer
3.039
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.099
971705AH1-358 GEN
Solar/Wind Harmer
1.482
971709AH1-360 GEN
Solar/Wind Harmer
1.482
970267AG2-176 GEN
Solar/Wind Harmer
9.102
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.943
20326126BLOSSBCT
Adder
1.167
20335026MILZ1-092
Adder
1.158
944411AF1-106 GEN
Solar/Wind Harmer
1.067
203835AF1-098 GEN
Solar/Wind Harmer
1.193
959471AF2-238 GEN
Solar/Wind Harmer
0.291
970337AG2-221 GEN
Solar/Wind Harmer
0.963
203954AE2-126 C
Solar/Wind Harmer
0.288
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.465
20072226SHAWVL 2
Adder
5.916
G-007ALTFEXP_G-007A->PJM
CMTX
0.536
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.106
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.697
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.367
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.259
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.52 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:271.07
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.467
203932AE1-123
Adder
1.647
20082926HNSMLK 2
Adder
4.631
20083126HNSMLK 4
Adder
4.631
971185AH1-051 GEN
Solar/Wind Harmer
1.821
971355AH1-158 GEN
Solar/Wind Harmer
2.117
203856AF2-165 C
Solar/Wind Harmer
0.877
970647AG2-420 GEN
Solar/Wind Harmer
1.462
959441AF2-235 GEN
Solar/Wind Harmer
0.204
971703AH1-357 GEN
Solar/Wind Harmer
1.27
971707AH1-359 GEN
Solar/Wind Harmer
1.27
20334926Z1-069 C
Solar/Wind Harmer
1.254
945751AF1-240 GEN
Solar/Wind Harmer
0.897
957161AF2-010 GEN
Solar/Wind Harmer
4.302
203830AF1-094 GEN
Solar/Wind Harmer
0.335
20120126WRREN CT
Adder
3.407
962511AG1-100 GEN
Solar/Wind Harmer
0.31
203962AF1-287 GEN
Solar/Wind Harmer
1.023
944411AF1-106 GEN
Solar/Wind Harmer
0.114
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.442
971127AH1-005 GEN
Solar/Wind Harmer
0.931
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.96
203848AF2-166 C
Solar/Wind Harmer
1.576
972077AH1-588 GEN
Solar/Wind Harmer
15.245
972079AH1-589 GEN
Solar/Wind Harmer
12.556
970715AG2-457 GEN
Solar/Wind Harmer
5.082
238217AF1-153 C O1
Solar/Wind Harmer
0.37
972075AH1-587 GEN
Solar/Wind Harmer
12.105
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.106
970305AG2-200 GEN
Solar/Wind Harmer
1.078
971931AH1-490 GEN
Solar/Wind Harmer
1.027
20398826ARMNA MT
Solar/Wind Harmer
1.197
203963AG1-253 GEN
Solar/Wind Harmer
0.192
203859AF2-294 C
Solar/Wind Harmer
0.801
203947AF1-006 C
Solar/Wind Harmer
0.261
970313AG2-206 GEN
Solar/Wind Harmer
2.223
238183AE2-316 GEN
Solar/Wind Harmer
3.917
20082826HNSMLK 1
Adder
4.631
20083026HNSMLK 3
Adder
4.631
971183AH1-050 GEN
Solar/Wind Harmer
3.034
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.082
971705AH1-358 GEN
Solar/Wind Harmer
1.477
971709AH1-360 GEN
Solar/Wind Harmer
1.477
970267AG2-176 GEN
Solar/Wind Harmer
9.088
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.932
20326126BLOSSBCT
Adder
1.162
20335026MILZ1-092
Adder
1.154
944411AF1-106 GEN
Solar/Wind Harmer
1.064
203835AF1-098 GEN
Solar/Wind Harmer
1.189
959471AF2-238 GEN
Solar/Wind Harmer
0.29
970337AG2-221 GEN
Solar/Wind Harmer
0.959
203954AE2-126 C
Solar/Wind Harmer
0.285
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.463
20083926HOMER C3
50/50
65.706
20083826HOMER C2
50/50
62.067
970663AG2-429 GEN
Solar/Wind Harmer
7.958
970663AG2-429 GEN
Solar/Wind Harmer
1.296
20083226HNSMLK 5
Adder
4.631
203846AF2-130 C
Solar/Wind Harmer
0.45
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.077
203804AE2-113_GEN
Solar/Wind Harmer
2.847
970677AG2-438 GEN
Solar/Wind Harmer
0.553
966771AG1-548 GEN
Solar/Wind Harmer
7.956
966771AG1-548 GEN
Solar/Wind Harmer
1.542
970555AG2-356 GEN
Solar/Wind Harmer
0.959
20084926LAKVU GN
Adder
0.092
20083726HOMER C1
Adder
4.658
G-007ALTFEXP_G-007A->PJM
CMTX
0.527
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.652
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.571
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.256
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.52 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:271.07
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.467
203932AE1-123
Adder
1.647
20082926HNSMLK 2
Adder
4.631
20083126HNSMLK 4
Adder
4.631
971185AH1-051 GEN
Solar/Wind Harmer
1.821
971355AH1-158 GEN
Solar/Wind Harmer
2.117
203856AF2-165 C
Solar/Wind Harmer
0.877
970647AG2-420 GEN
Solar/Wind Harmer
1.462
959441AF2-235 GEN
Solar/Wind Harmer
0.204
971703AH1-357 GEN
Solar/Wind Harmer
1.27
971707AH1-359 GEN
Solar/Wind Harmer
1.27
20334926Z1-069 C
Solar/Wind Harmer
1.254
945751AF1-240 GEN
Solar/Wind Harmer
0.897
957161AF2-010 GEN
Solar/Wind Harmer
4.302
203830AF1-094 GEN
Solar/Wind Harmer
0.335
20120126WRREN CT
Adder
3.407
962511AG1-100 GEN
Solar/Wind Harmer
0.31
203962AF1-287 GEN
Solar/Wind Harmer
1.023
944411AF1-106 GEN
Solar/Wind Harmer
0.114
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.442
971127AH1-005 GEN
Solar/Wind Harmer
0.931
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.96
203848AF2-166 C
Solar/Wind Harmer
1.576
972077AH1-588 GEN
Solar/Wind Harmer
15.245
972079AH1-589 GEN
Solar/Wind Harmer
12.556
970715AG2-457 GEN
Solar/Wind Harmer
5.082
238217AF1-153 C O1
Solar/Wind Harmer
0.37
972075AH1-587 GEN
Solar/Wind Harmer
12.105
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.106
970305AG2-200 GEN
Solar/Wind Harmer
1.078
971931AH1-490 GEN
Solar/Wind Harmer
1.027
20398826ARMNA MT
Solar/Wind Harmer
1.197
203963AG1-253 GEN
Solar/Wind Harmer
0.192
203859AF2-294 C
Solar/Wind Harmer
0.801
203947AF1-006 C
Solar/Wind Harmer
0.261
970313AG2-206 GEN
Solar/Wind Harmer
2.223
238183AE2-316 GEN
Solar/Wind Harmer
3.917
20082826HNSMLK 1
Adder
4.631
20083026HNSMLK 3
Adder
4.631
20083926HOMER C3
50/50
65.706
20083826HOMER C2
50/50
62.067
970663AG2-429 GEN
Solar/Wind Harmer
7.958
970663AG2-429 GEN
Solar/Wind Harmer
1.296
20083226HNSMLK 5
Adder
4.631
203846AF2-130 C
Solar/Wind Harmer
0.45
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.077
203804AE2-113_GEN
Solar/Wind Harmer
2.847
970677AG2-438 GEN
Solar/Wind Harmer
0.553
966771AG1-548 GEN
Solar/Wind Harmer
7.956
966771AG1-548 GEN
Solar/Wind Harmer
1.542
970555AG2-356 GEN
Solar/Wind Harmer
0.959
20084926LAKVU GN
Adder
0.092
20083726HOMER C1
Adder
4.658
971183AH1-050 GEN
Solar/Wind Harmer
3.034
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.082
971705AH1-358 GEN
Solar/Wind Harmer
1.477
971709AH1-360 GEN
Solar/Wind Harmer
1.477
970267AG2-176 GEN
Solar/Wind Harmer
9.088
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.932
20326126BLOSSBCT
Adder
1.162
20335026MILZ1-092
Adder
1.154
944411AF1-106 GEN
Solar/Wind Harmer
1.064
203835AF1-098 GEN
Solar/Wind Harmer
1.189
959471AF2-238 GEN
Solar/Wind Harmer
0.29
970337AG2-221 GEN
Solar/Wind Harmer
0.959
203954AE2-126 C
Solar/Wind Harmer
0.285
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.463
G-007ALTFEXP_G-007A->PJM
CMTX
0.527
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.652
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.571
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.256
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-177_A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-177_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.0 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:253.68
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.029
946381AF1-302 GEN
Solar/Wind Harmer
2.238
203848AF2-166 C
Solar/Wind Harmer
1.782
238217AF1-153 C O1
Solar/Wind Harmer
0.407
203979AG1-198 GEN
Solar/Wind Harmer
0.198
971933AH1-491 GEN
Solar/Wind Harmer
1.092
203980AG1-197 GEN
Solar/Wind Harmer
0.242
972075AH1-587 GEN
Solar/Wind Harmer
10.438
972077AH1-588 GEN
Solar/Wind Harmer
12.308
972079AH1-589 GEN
Solar/Wind Harmer
10.138
970715AG2-457 GEN
Solar/Wind Harmer
4.103
970305AG2-200 GEN
Solar/Wind Harmer
0.98
971931AH1-490 GEN
Solar/Wind Harmer
0.967
203963AG1-253 GEN
Solar/Wind Harmer
0.173
203947AF1-006 C
Solar/Wind Harmer
0.241
20060826PINEY #1
50/50
0.059
970663AG2-429 GEN
Solar/Wind Harmer
9.339
970663AG2-429 GEN
Solar/Wind Harmer
1.52
971055AG2-654 GEN
Solar/Wind Harmer
1.148
203846AF2-130 C
Solar/Wind Harmer
0.509
20083226HNSMLK 5
Adder
4.379
20083926HOMER C3
Adder
40.151
20083826HOMER C2
Adder
37.927
970677AG2-438 GEN
Solar/Wind Harmer
0.546
966771AG1-548 GEN
Solar/Wind Harmer
7.806
966771AG1-548 GEN
Solar/Wind Harmer
1.513
203804AE2-113_GEN
Solar/Wind Harmer
2.528
940863AE2-074 GEN
Solar/Wind Harmer
0.855
203855AF2-088 C
Solar/Wind Harmer
0.09
20083726HOMER C1
Adder
22.048
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.033
238219AF1-167 C
Solar/Wind Harmer
1.746
971185AH1-051 GEN
Solar/Wind Harmer
1.987
971355AH1-158 GEN
Solar/Wind Harmer
2.311
203856AF2-165 C
Solar/Wind Harmer
0.954
970647AG2-420 GEN
Solar/Wind Harmer
1.572
20082926HNSMLK 2
Adder
4.379
20083126HNSMLK 4
Adder
4.379
959441AF2-235 GEN
Solar/Wind Harmer
0.217
945751AF1-240 GEN
Solar/Wind Harmer
1.121
957161AF2-010 GEN
Solar/Wind Harmer
4.268
203830AF1-094 GEN
Solar/Wind Harmer
0.331
971703AH1-357 GEN
Solar/Wind Harmer
1.026
971707AH1-359 GEN
Solar/Wind Harmer
1.026
20120126WRREN CT
Adder
3.099
962511AG1-100 GEN
Solar/Wind Harmer
0.292
203962AF1-287 GEN
Solar/Wind Harmer
0.961
20334926Z1-069 C
Solar/Wind Harmer
0.981
203854AF2-039 C
Solar/Wind Harmer
0.187
238202AE2-262_GEN
Solar/Wind Harmer
1.12
971627AH1-313 GEN
Solar/Wind Harmer
4.389
203948AG1-140 C
Solar/Wind Harmer
0.114
20060826PINEY #1
50/50
0.066
238183AE2-316 GEN
Solar/Wind Harmer
4.473
971183AH1-050 GEN
Solar/Wind Harmer
3.312
970647AG2-420 GEN
Solar/Wind Harmer
0.183
20082826HNSMLK 1
Adder
4.379
20083026HNSMLK 3
Adder
4.379
203860AG1-193 C
Solar/Wind Harmer
0.216
970267AG2-176 GEN
Solar/Wind Harmer
8.783
961971AG1-040 GEN
Solar/Wind Harmer
0.317
970713AG2-456 GEN
Solar/Wind Harmer
4.103
971705AH1-358 GEN
Solar/Wind Harmer
1.193
971709AH1-360 GEN
Solar/Wind Harmer
1.193
203954AE2-126 C
Solar/Wind Harmer
0.304
971865AH1-452 GEN
Solar/Wind Harmer
0.846
203813AE2-344_GEN
Solar/Wind Harmer
5.571
20072226SHAWVL 2
Adder
6.51
972169AH1-667 GEN
Solar/Wind Harmer
0.824
20091326SHAW-D
Adder
0.301
203835AF1-098 GEN
Solar/Wind Harmer
1.093
238206AE2-263_GEN
Solar/Wind Harmer
1.043
G-007ALTFEXP_G-007A->PJM
CMTX
1.254
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.519
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.576
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.822
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:164.29 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:248.08
MW Contribution:1.11
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.013
946381AF1-302 GEN
Solar/Wind Harmer
1.925
203848AF2-166 C
Solar/Wind Harmer
1.692
203980AG1-197 GEN
Solar/Wind Harmer
0.335
203979AG1-198 GEN
Solar/Wind Harmer
0.265
971933AH1-491 GEN
Solar/Wind Harmer
1.456
971931AH1-490 GEN
Solar/Wind Harmer
1.437
203947AF1-006 C
Solar/Wind Harmer
0.39
203963AG1-253 GEN
Solar/Wind Harmer
0.269
238217AF1-153 C O1
Solar/Wind Harmer
0.381
970305AG2-200 GEN
Solar/Wind Harmer
1.234
972077AH1-588 GEN
Solar/Wind Harmer
13.31
972079AH1-589 GEN
Solar/Wind Harmer
10.963
970715AG2-457 GEN
Solar/Wind Harmer
4.437
972075AH1-587 GEN
Solar/Wind Harmer
10.904
20060826PINEY #1
50/50
0.053
970663AG2-429 GEN
Solar/Wind Harmer
7.76
970663AG2-429 GEN
Solar/Wind Harmer
1.263
203846AF2-130 C
Solar/Wind Harmer
0.483
20083226HNSMLK 5
Adder
4.736
970677AG2-438 GEN
Solar/Wind Harmer
0.728
966771AG1-548 GEN
Solar/Wind Harmer
10.575
966771AG1-548 GEN
Solar/Wind Harmer
2.049
20084926LAKVU GN
Adder
0.135
971055AG2-654 GEN
Solar/Wind Harmer
0.835
203804AE2-113_GEN
Solar/Wind Harmer
2.624
20083926HOMER C3
Adder
37.811
20083826HOMER C2
Adder
35.717
940863AE2-074 GEN
Solar/Wind Harmer
0.901
203855AF2-088 C
Solar/Wind Harmer
0.088
20083726HOMER C1
Adder
21.283
23503001MHNG-T155
50/50
0.013
20060826PINEY #1
50/50
0.057
203932AE1-123
50/50
1.823
238219AF1-167 C
Solar/Wind Harmer
1.449
971185AH1-051 GEN
Solar/Wind Harmer
2.005
971355AH1-158 GEN
Solar/Wind Harmer
2.331
203856AF2-165 C
Solar/Wind Harmer
0.976
970647AG2-420 GEN
Solar/Wind Harmer
1.631
20082926HNSMLK 2
Adder
4.736
20083126HNSMLK 4
Adder
4.736
959441AF2-235 GEN
Solar/Wind Harmer
0.239
957161AF2-010 GEN
Solar/Wind Harmer
5.628
203830AF1-094 GEN
Solar/Wind Harmer
0.441
962511AG1-100 GEN
Solar/Wind Harmer
0.435
203962AF1-287 GEN
Solar/Wind Harmer
1.43
20084926LAKVU GN
Adder
0.12
203948AG1-140 C
Solar/Wind Harmer
0.176
945751AF1-240 GEN
Solar/Wind Harmer
1.018
20120126WRREN CT
Adder
3.9
971703AH1-357 GEN
Solar/Wind Harmer
1.109
971707AH1-359 GEN
Solar/Wind Harmer
1.109
20334926Z1-069 C
Solar/Wind Harmer
1.026
203854AF2-039 C
Solar/Wind Harmer
0.183
20060826PINEY #1
50/50
0.06
238183AE2-316 GEN
Solar/Wind Harmer
3.848
971183AH1-050 GEN
Solar/Wind Harmer
3.341
970647AG2-420 GEN
Solar/Wind Harmer
0.19
20082826HNSMLK 1
Adder
4.736
20083026HNSMLK 3
Adder
4.736
203860AG1-193 C
Solar/Wind Harmer
0.241
970267AG2-176 GEN
Solar/Wind Harmer
11.328
961971AG1-040 GEN
Solar/Wind Harmer
0.443
203813AE2-344_GEN
Solar/Wind Harmer
8.328
20084926LAKVU GN
Adder
0.12
203835AF1-098 GEN
Solar/Wind Harmer
1.634
970713AG2-456 GEN
Solar/Wind Harmer
4.437
971705AH1-358 GEN
Solar/Wind Harmer
1.29
971709AH1-360 GEN
Solar/Wind Harmer
1.29
203954AE2-126 C
Solar/Wind Harmer
0.303
20072226SHAWVL 2
Adder
6.358
972169AH1-667 GEN
Solar/Wind Harmer
0.807
20091326SHAW-D
Adder
0.295
G-007ALTFEXP_G-007A->PJM
CMTX
1.515
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.954
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.224
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.24
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.745
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.078
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-054_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-054_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:149.48 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:225.72
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
1.913
203848AF2-166 C
Solar/Wind Harmer
1.509
238217AF1-153 C O1
Solar/Wind Harmer
0.341
203979AG1-198 GEN
Solar/Wind Harmer
0.169
971933AH1-491 GEN
Solar/Wind Harmer
0.931
203980AG1-197 GEN
Solar/Wind Harmer
0.208
972075AH1-587 GEN
Solar/Wind Harmer
8.631
972077AH1-588 GEN
Solar/Wind Harmer
10.19
972079AH1-589 GEN
Solar/Wind Harmer
8.393
970715AG2-457 GEN
Solar/Wind Harmer
3.397
970663AG2-429 GEN
Solar/Wind Harmer
8.01
970663AG2-429 GEN
Solar/Wind Harmer
1.304
203846AF2-130 C
Solar/Wind Harmer
0.431
971055AG2-654 GEN
Solar/Wind Harmer
0.806
20083226HNSMLK 5
Adder
3.738
970677AG2-438 GEN
Solar/Wind Harmer
0.466
20083926HOMER C3
Adder
32.796
20083826HOMER C2
Adder
30.979
966771AG1-548 GEN
Solar/Wind Harmer
6.66
966771AG1-548 GEN
Solar/Wind Harmer
1.291
203804AE2-113_GEN
Solar/Wind Harmer
2.091
20083726HOMER C1
Adder
16.47
23503001MHNG-T155
50/50
0.015
238219AF1-167 C
Solar/Wind Harmer
1.49
203932AE1-123
Adder
1.619
971185AH1-051 GEN
Solar/Wind Harmer
1.685
971355AH1-158 GEN
Solar/Wind Harmer
1.96
203856AF2-165 C
Solar/Wind Harmer
0.809
970647AG2-420 GEN
Solar/Wind Harmer
1.335
20082926HNSMLK 2
Adder
3.738
20083126HNSMLK 4
Adder
3.738
959441AF2-235 GEN
Solar/Wind Harmer
0.185
945751AF1-240 GEN
Solar/Wind Harmer
0.913
957161AF2-010 GEN
Solar/Wind Harmer
3.639
203830AF1-094 GEN
Solar/Wind Harmer
0.282
971703AH1-357 GEN
Solar/Wind Harmer
0.849
971707AH1-359 GEN
Solar/Wind Harmer
0.849
238183AE2-316 GEN
Solar/Wind Harmer
3.822
971183AH1-050 GEN
Solar/Wind Harmer
2.809
970647AG2-420 GEN
Solar/Wind Harmer
0.155
20082826HNSMLK 1
Adder
3.738
20083026HNSMLK 3
Adder
3.738
203860AG1-193 C
Solar/Wind Harmer
0.184
970267AG2-176 GEN
Solar/Wind Harmer
7.51
961971AG1-040 GEN
Solar/Wind Harmer
0.271
970713AG2-456 GEN
Solar/Wind Harmer
3.397
971705AH1-358 GEN
Solar/Wind Harmer
0.987
971709AH1-360 GEN
Solar/Wind Harmer
0.987
G-007ALTFEXP_G-007A->PJM
CMTX
0.681
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.109
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.76
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.946
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.343
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.49
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.83 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:217.18
MW Contribution:0.71
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.029
20082926HNSMLK 2
50/50
4.644
20083126HNSMLK 4
50/50
4.644
238219AF1-167 C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
1.71
971355AH1-158 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
1.096
945751AF1-240 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
2.963
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.714
971707AH1-359 GEN
Solar/Wind Harmer
0.714
20120126WRREN CT
Adder
3.096
203962AF1-287 GEN
Solar/Wind Harmer
0.671
20334926Z1-069 C
Solar/Wind Harmer
0.245
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.054
203948AG1-140 C
Solar/Wind Harmer
0.086
23513401AL&D6
50/50
0.029
203848AF2-166 C
Solar/Wind Harmer
1.242
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.762
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.269
972077AH1-588 GEN
Solar/Wind Harmer
8.573
972079AH1-589 GEN
Solar/Wind Harmer
10.121
970715AG2-457 GEN
Solar/Wind Harmer
3.322
970305AG2-200 GEN
Solar/Wind Harmer
0.683
971931AH1-490 GEN
Solar/Wind Harmer
0.675
203963AG1-253 GEN
Solar/Wind Harmer
0.136
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.059
20066226SCRUB GR
50/50
0.413
20083226HNSMLK 5
50/50
4.644
970663AG2-429 GEN
Solar/Wind Harmer
6.947
970663AG2-429 GEN
Solar/Wind Harmer
1.518
971055AG2-654 GEN
Solar/Wind Harmer
0.933
20083926HOMER C3
Adder
40.066
20083826HOMER C2
Adder
37.847
970677AG2-438 GEN
Solar/Wind Harmer
0.425
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.553
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.944
20060826PINEY #1
50/50
0.066
20082826HNSMLK 1
50/50
4.644
20083026HNSMLK 3
50/50
4.644
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
0.183
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.126
970713AG2-456 GEN
Solar/Wind Harmer
3.322
971705AH1-358 GEN
Solar/Wind Harmer
1.191
971709AH1-360 GEN
Solar/Wind Harmer
1.191
203954AE2-126 C
Solar/Wind Harmer
0.001
203813AE2-344_GEN
Solar/Wind Harmer
3.887
20072226SHAWVL 2
Adder
6.494
971865AH1-452 GEN
Solar/Wind Harmer
0.451
20091326SHAW-D
Adder
0.3
972169AH1-667 GEN
Solar/Wind Harmer
0.574
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
G-007ALTFEXP_G-007A->PJM
CMTX
1.215
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.982
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.415
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.79
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.67 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:201.84
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.068
20082826HNSMLK 1
50/50
4.728
20083026HNSMLK 3
50/50
4.728
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
0.186
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.236
970713AG2-456 GEN
Solar/Wind Harmer
3.392
971705AH1-358 GEN
Solar/Wind Harmer
1.216
971709AH1-360 GEN
Solar/Wind Harmer
1.216
203954AE2-126 C
Solar/Wind Harmer
0.001
971865AH1-452 GEN
Solar/Wind Harmer
0.487
203813AE2-344_GEN
Solar/Wind Harmer
3.956
20072226SHAWVL 2
Adder
6.64
20091326SHAW-D
Adder
0.308
972169AH1-667 GEN
Solar/Wind Harmer
0.587
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.077
23503001MHNG-T155
50/50
0.018
20060826PINEY #1
50/50
0.065
203932AE1-123
50/50
2.068
20082926HNSMLK 2
50/50
4.728
20083126HNSMLK 4
50/50
4.728
238219AF1-167 C
Solar/Wind Harmer
1.237
971185AH1-051 GEN
Solar/Wind Harmer
1.742
971355AH1-158 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
1.116
945751AF1-240 GEN
Solar/Wind Harmer
0.929
957161AF2-010 GEN
Solar/Wind Harmer
3.017
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.73
971707AH1-359 GEN
Solar/Wind Harmer
0.73
20120126WRREN CT
Adder
3.157
203962AF1-287 GEN
Solar/Wind Harmer
0.682
20334926Z1-069 C
Solar/Wind Harmer
0.251
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.124
203948AG1-140 C
Solar/Wind Harmer
0.087
20084926LAKVU GN
Adder
0.077
960051AF2-296 GEN
Solar/Wind Harmer
0.603
203848AF2-166 C
Solar/Wind Harmer
1.265
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.775
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.424
972077AH1-588 GEN
Solar/Wind Harmer
8.754
972079AH1-589 GEN
Solar/Wind Harmer
10.335
970715AG2-457 GEN
Solar/Wind Harmer
3.392
970305AG2-200 GEN
Solar/Wind Harmer
0.697
971931AH1-490 GEN
Solar/Wind Harmer
0.686
203963AG1-253 GEN
Solar/Wind Harmer
0.139
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.06
20066226SCRUB GR
50/50
0.421
20083226HNSMLK 5
50/50
4.728
970663AG2-429 GEN
Solar/Wind Harmer
7.068
970663AG2-429 GEN
Solar/Wind Harmer
1.545
971055AG2-654 GEN
Solar/Wind Harmer
0.966
20083926HOMER C3
Adder
40.966
20083826HOMER C2
Adder
38.697
970677AG2-438 GEN
Solar/Wind Harmer
0.433
966771AG1-548 GEN
Solar/Wind Harmer
1.265
966771AG1-548 GEN
Solar/Wind Harmer
1.581
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
22.622
G-007ALTFEXP_G-007A->PJM
CMTX
1.282
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.258
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.599
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.826
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-057_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-057_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.28 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:198.24
MW Contribution:0.91
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
1.974
203848AF2-166 C
Solar/Wind Harmer
1.556
238217AF1-153 C O1
Solar/Wind Harmer
0.357
203979AG1-198 GEN
Solar/Wind Harmer
0.174
971933AH1-491 GEN
Solar/Wind Harmer
0.959
203980AG1-197 GEN
Solar/Wind Harmer
0.213
972075AH1-587 GEN
Solar/Wind Harmer
9.212
972077AH1-588 GEN
Solar/Wind Harmer
10.87
972079AH1-589 GEN
Solar/Wind Harmer
8.953
970715AG2-457 GEN
Solar/Wind Harmer
3.623
970305AG2-200 GEN
Solar/Wind Harmer
0.864
970663AG2-429 GEN
Solar/Wind Harmer
8.167
970663AG2-429 GEN
Solar/Wind Harmer
1.33
203846AF2-130 C
Solar/Wind Harmer
0.444
20083226HNSMLK 5
Adder
3.865
20083926HOMER C3
Adder
35.571
20083826HOMER C2
Adder
33.601
970677AG2-438 GEN
Solar/Wind Harmer
0.48
966771AG1-548 GEN
Solar/Wind Harmer
6.857
966771AG1-548 GEN
Solar/Wind Harmer
1.329
203804AE2-113_GEN
Solar/Wind Harmer
2.23
940863AE2-074 GEN
Solar/Wind Harmer
0.755
20083726HOMER C1
Adder
19.645
23503001MHNG-T155
50/50
0.009
238219AF1-167 C
Solar/Wind Harmer
1.375
203932AE1-123
Adder
1.67
971185AH1-051 GEN
Solar/Wind Harmer
1.738
971355AH1-158 GEN
Solar/Wind Harmer
2.021
203856AF2-165 C
Solar/Wind Harmer
0.834
970647AG2-420 GEN
Solar/Wind Harmer
1.376
20082926HNSMLK 2
Adder
3.865
20083126HNSMLK 4
Adder
3.865
959441AF2-235 GEN
Solar/Wind Harmer
0.19
945751AF1-240 GEN
Solar/Wind Harmer
0.982
957161AF2-010 GEN
Solar/Wind Harmer
3.747
203830AF1-094 GEN
Solar/Wind Harmer
0.29
971703AH1-357 GEN
Solar/Wind Harmer
0.906
971707AH1-359 GEN
Solar/Wind Harmer
0.906
20120126WRREN CT
Adder
2.732
238183AE2-316 GEN
Solar/Wind Harmer
3.945
971183AH1-050 GEN
Solar/Wind Harmer
2.896
970647AG2-420 GEN
Solar/Wind Harmer
0.16
20082826HNSMLK 1
Adder
3.865
20083026HNSMLK 3
Adder
3.865
203860AG1-193 C
Solar/Wind Harmer
0.189
970267AG2-176 GEN
Solar/Wind Harmer
7.731
961971AG1-040 GEN
Solar/Wind Harmer
0.279
970713AG2-456 GEN
Solar/Wind Harmer
3.623
971705AH1-358 GEN
Solar/Wind Harmer
1.053
971709AH1-360 GEN
Solar/Wind Harmer
1.053
203954AE2-126 C
Solar/Wind Harmer
0.268
G-007ALTFEXP_G-007A->PJM
CMTX
1.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.13
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.887
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.109
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.161
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.084
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.501
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.713
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-2_PN-345-002T-DRT-003_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-002T-DRT-003_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.22 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:187.57
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.341
203932AE1-123
Adder
1.483
971185AH1-051 GEN
Solar/Wind Harmer
1.581
971355AH1-158 GEN
Solar/Wind Harmer
1.838
203856AF2-165 C
Solar/Wind Harmer
0.76
20082926HNSMLK 2
Adder
3.716
20083126HNSMLK 4
Adder
3.716
970647AG2-420 GEN
Solar/Wind Harmer
1.259
959441AF2-235 GEN
Solar/Wind Harmer
0.175
970663AG2-429 GEN
Solar/Wind Harmer
7.235
970663AG2-429 GEN
Solar/Wind Harmer
1.178
203846AF2-130 C
Solar/Wind Harmer
0.399
971055AG2-654 GEN
Solar/Wind Harmer
0.796
20083226HNSMLK 5
Adder
3.716
20083926HOMER C3
Adder
40.8
20083826HOMER C2
Adder
38.54
203804AE2-113_GEN
Solar/Wind Harmer
2.19
970677AG2-438 GEN
Solar/Wind Harmer
0.454
940863AE2-074 GEN
Solar/Wind Harmer
0.782
966771AG1-548 GEN
Solar/Wind Harmer
6.513
966771AG1-548 GEN
Solar/Wind Harmer
1.262
20083726HOMER C1
Adder
10.121
945751AF1-240 GEN
Solar/Wind Harmer
0.835
971703AH1-357 GEN
Solar/Wind Harmer
0.931
971707AH1-359 GEN
Solar/Wind Harmer
0.931
957161AF2-010 GEN
Solar/Wind Harmer
3.543
203830AF1-094 GEN
Solar/Wind Harmer
0.275
20334926Z1-069 C
Solar/Wind Harmer
0.903
23513401AL&D6
50/50
0.013
946381AF1-302 GEN
Solar/Wind Harmer
1.751
203848AF2-166 C
Solar/Wind Harmer
1.396
238217AF1-153 C O1
Solar/Wind Harmer
0.322
972077AH1-588 GEN
Solar/Wind Harmer
11.174
972079AH1-589 GEN
Solar/Wind Harmer
9.204
970715AG2-457 GEN
Solar/Wind Harmer
3.725
972075AH1-587 GEN
Solar/Wind Harmer
9.172
203979AG1-198 GEN
Solar/Wind Harmer
0.165
971933AH1-491 GEN
Solar/Wind Harmer
0.908
203980AG1-197 GEN
Solar/Wind Harmer
0.205
238183AE2-316 GEN
Solar/Wind Harmer
3.499
971183AH1-050 GEN
Solar/Wind Harmer
2.635
20082826HNSMLK 1
Adder
3.716
20083026HNSMLK 3
Adder
3.716
970647AG2-420 GEN
Solar/Wind Harmer
0.146
203860AG1-193 C
Solar/Wind Harmer
0.177
970267AG2-176 GEN
Solar/Wind Harmer
7.382
970713AG2-456 GEN
Solar/Wind Harmer
3.725
971705AH1-358 GEN
Solar/Wind Harmer
1.083
971709AH1-360 GEN
Solar/Wind Harmer
1.083
961971AG1-040 GEN
Solar/Wind Harmer
0.268
G-007ALTFEXP_G-007A->PJM
CMTX
0.682
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.103
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.706
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.956
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.104
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.322
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.459
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-067_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-067_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.35 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:178.72
MW Contribution:0.87
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.055
970663AG2-429 GEN
Solar/Wind Harmer
8.405
970663AG2-429 GEN
Solar/Wind Harmer
1.368
203846AF2-130 C
Solar/Wind Harmer
0.468
971055AG2-654 GEN
Solar/Wind Harmer
0.806
20083226HNSMLK 5
Adder
3.724
970677AG2-438 GEN
Solar/Wind Harmer
0.484
966771AG1-548 GEN
Solar/Wind Harmer
6.9
966771AG1-548 GEN
Solar/Wind Harmer
1.337
20083926HOMER C3
Adder
33.598
20083826HOMER C2
Adder
31.737
203804AE2-113_GEN
Solar/Wind Harmer
2.166
20083726HOMER C1
Adder
18.155
23503001MHNG-T155
50/50
0.014
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.884
238219AF1-167 C
Solar/Wind Harmer
1.595
971185AH1-051 GEN
Solar/Wind Harmer
1.804
971355AH1-158 GEN
Solar/Wind Harmer
2.097
203856AF2-165 C
Solar/Wind Harmer
0.865
970647AG2-420 GEN
Solar/Wind Harmer
1.42
945751AF1-240 GEN
Solar/Wind Harmer
1.028
959441AF2-235 GEN
Solar/Wind Harmer
0.196
20082926HNSMLK 2
Adder
3.724
20083126HNSMLK 4
Adder
3.724
957161AF2-010 GEN
Solar/Wind Harmer
3.784
203830AF1-094 GEN
Solar/Wind Harmer
0.293
971703AH1-357 GEN
Solar/Wind Harmer
0.874
971707AH1-359 GEN
Solar/Wind Harmer
0.874
20060826PINEY #1
50/50
0.062
238183AE2-316 GEN
Solar/Wind Harmer
3.802
971183AH1-050 GEN
Solar/Wind Harmer
3.006
970647AG2-420 GEN
Solar/Wind Harmer
0.165
20082826HNSMLK 1
Adder
3.724
20083026HNSMLK 3
Adder
3.724
203860AG1-193 C
Solar/Wind Harmer
0.191
970267AG2-176 GEN
Solar/Wind Harmer
7.646
961971AG1-040 GEN
Solar/Wind Harmer
0.276
970713AG2-456 GEN
Solar/Wind Harmer
3.496
971705AH1-358 GEN
Solar/Wind Harmer
1.016
971709AH1-360 GEN
Solar/Wind Harmer
1.016
203954AE2-126 C
Solar/Wind Harmer
0.262
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.902
203848AF2-166 C
Solar/Wind Harmer
1.638
238217AF1-153 C O1
Solar/Wind Harmer
0.357
203979AG1-198 GEN
Solar/Wind Harmer
0.176
971933AH1-491 GEN
Solar/Wind Harmer
0.967
203980AG1-197 GEN
Solar/Wind Harmer
0.211
972075AH1-587 GEN
Solar/Wind Harmer
8.927
972077AH1-588 GEN
Solar/Wind Harmer
10.489
972079AH1-589 GEN
Solar/Wind Harmer
8.639
970715AG2-457 GEN
Solar/Wind Harmer
3.496
G-007ALTFEXP_G-007A->PJM
CMTX
0.886
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.119
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.254
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.505
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.076
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.429
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.612
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01DALE-01SHINGL 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-703T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01DALE-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-703T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.3 %
Rating:523.0 MVA
Rating Type:B
MVA to Mitigate:545.49
MW Contribution:1.45
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
28.317
20091326SHAW-D
50/50
1.152
20064926PENNTECH
50/50
0.383
200643SENECA#2
50/50
1.293
238206AE2-263_GEN
Solar/Wind Harmer
7.577
972169AH1-667 GEN
Solar/Wind Harmer
2.973
203954AE2-126 C
Solar/Wind Harmer
0.923
238215AE2-248 C
Solar/Wind Harmer
2.035
238183AE2-316 GEN
Solar/Wind Harmer
4.639
970713AG2-456 GEN
Solar/Wind Harmer
5.805
971705AH1-358 GEN
Solar/Wind Harmer
1.687
971709AH1-360 GEN
Solar/Wind Harmer
1.687
20326126BLOSSBCT
Adder
1.544
959471AF2-238 GEN
Solar/Wind Harmer
0.381
970337AG2-221 GEN
Solar/Wind Harmer
1.261
970511AG2-327 GEN
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
1.245
944411AF1-106 GEN
Solar/Wind Harmer
1.147
203835AF1-098 GEN
Solar/Wind Harmer
1.176
964391AG1-301 GEN
Solar/Wind Helper
0.234
200644SENECA#3
50/50
0.178
238202AE2-262_GEN
Solar/Wind Harmer
8.129
971627AH1-313 GEN
Solar/Wind Harmer
31.874
203854AF2-039 C
Solar/Wind Harmer
0.675
965131AG1-378 GEN
Solar/Wind Harmer
2.365
960051AF2-296 GEN
Solar/Wind Harmer
2.242
20335126GROZ1-110
Adder
1.979
20335226CANZ2-011
Adder
1.924
20120126WRREN CT
Adder
4.968
941421AE2-139 GEN
Solar/Wind Harmer
2.219
20066526SHAWVL 3
50/50
2.16
20066626SHAWVL 4
50/50
2.158
20071526SHAWVL 1
50/50
1.41
216419AE2-001 C
Solar/Wind Harmer
5.831
238217AF1-153 C O1
Solar/Wind Harmer
0.927
203952AE2-129 C
Solar/Wind Harmer
0.716
203946AE2-131 C
Solar/Wind Harmer
0.715
962411AG1-090 GEN
Solar/Wind Harmer
11.235
203853AF1-134 C O1
Solar/Wind Harmer
0.678
946381AF1-302 GEN
Solar/Wind Harmer
2.321
972075AH1-587 GEN
Solar/Wind Harmer
19.127
970305AG2-200 GEN
Solar/Wind Harmer
1.571
972077AH1-588 GEN
Solar/Wind Harmer
17.415
972079AH1-589 GEN
Solar/Wind Harmer
14.344
970715AG2-457 GEN
Solar/Wind Harmer
5.805
970313AG2-206 GEN
Solar/Wind Harmer
2.818
20398826ARMNA MT
Solar/Wind Harmer
1.327
203859AF2-294 C
Solar/Wind Harmer
0.835
20390526W1-045 C
Solar/Wind Helper
0.166
200642SENECA#1
50/50
1.386
203855AF2-088 C
Solar/Wind Harmer
0.325
965121AG1-377 GEN
Solar/Wind Harmer
2.365
203804AE2-113_GEN
Solar/Wind Harmer
5.028
20090526Q36
Solar/Wind Harmer
1.241
203993AD2-133_GEN1
Solar/Wind Harmer
1.241
940863AE2-074 GEN
Solar/Wind Harmer
1.2
970555AG2-356 GEN
Solar/Wind Harmer
1.261
203926AA2-133 GEN
Adder
1.269
20334726NME_Y1-047
Adder
1.11
20083926HOMER C3
Adder
17.923
20083826HOMER C2
Adder
16.93
20083726HOMER C1
Adder
8.674
203975AE1-071-GEN
Solar/Wind Helper
1.684
959381AF2-229 GEN
Solar/Wind Helper
0.169
203818AF1-086 GEN
Solar/Wind Harmer
1.858
971703AH1-357 GEN
Solar/Wind Harmer
1.451
971707AH1-359 GEN
Solar/Wind Harmer
1.451
972271AH1-720 GEN
Adder
4.286
20334926Z1-069 C
Solar/Wind Harmer
1.333
20328326MANOR_T86
Adder
0.086
970335AG2-220 GEN
Solar/Wind Harmer
1.817
971127AH1-005 GEN
Solar/Wind Harmer
1.173
944411AF1-106 GEN
Solar/Wind Harmer
0.123
200917MEHOOPANY_G
Solar/Wind Harmer
1.653
238219AF1-167 C
Solar/Wind Harmer
0.608
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.783
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.72
LAGNLTFEXP_LAGN->PJM
CLTF
0.333
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.013
TVALTFEXP_TVA->PJM
CLTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.416
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01DALE-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-2_WP-230-006T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01DALE-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-006T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.38 %
Rating:523.0 MVA
Rating Type:B
MVA to Mitigate:535.44
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
28.754
20091326SHAW-D
50/50
1.17
20064926PENNTECH
50/50
0.389
200643SENECA#2
50/50
1.313
238206AE2-263_GEN
Solar/Wind Harmer
7.694
238215AE2-248 C
Solar/Wind Harmer
3.327
972169AH1-667 GEN
Solar/Wind Harmer
3.019
203954AE2-126 C
Solar/Wind Harmer
0.937
238183AE2-316 GEN
Solar/Wind Harmer
4.711
970713AG2-456 GEN
Solar/Wind Harmer
5.895
971705AH1-358 GEN
Solar/Wind Harmer
1.714
971709AH1-360 GEN
Solar/Wind Harmer
1.714
20066526SHAWVL 3
50/50
2.194
20066626SHAWVL 4
50/50
2.191
20071526SHAWVL 1
50/50
1.432
216419AE2-001 C
Solar/Wind Harmer
6.635
238217AF1-153 C O1
Solar/Wind Harmer
0.942
203952AE2-129 C
Solar/Wind Harmer
0.727
203946AE2-131 C
Solar/Wind Harmer
0.726
962411AG1-090 GEN
Solar/Wind Harmer
11.408
203853AF1-134 C O1
Solar/Wind Harmer
0.688
946381AF1-302 GEN
Solar/Wind Harmer
2.357
972075AH1-587 GEN
Solar/Wind Harmer
19.423
970305AG2-200 GEN
Solar/Wind Harmer
1.596
972077AH1-588 GEN
Solar/Wind Harmer
17.684
972079AH1-589 GEN
Solar/Wind Harmer
14.565
970715AG2-457 GEN
Solar/Wind Harmer
5.895
970313AG2-206 GEN
Solar/Wind Harmer
2.861
20398826ARMNA MT
Solar/Wind Harmer
1.347
203859AF2-294 C
Solar/Wind Harmer
0.848
20390526W1-045 C
Solar/Wind Helper
0.169
200642SENECA#1
50/50
1.408
203855AF2-088 C
Solar/Wind Harmer
0.33
965121AG1-377 GEN
Solar/Wind Harmer
2.402
203804AE2-113_GEN
Solar/Wind Harmer
5.105
20090526Q36
Solar/Wind Harmer
1.261
203993AD2-133_GEN1
Solar/Wind Harmer
1.261
200644SENECA#3
50/50
0.181
238202AE2-262_GEN
Solar/Wind Harmer
8.255
971627AH1-313 GEN
Solar/Wind Harmer
32.367
203854AF2-039 C
Solar/Wind Harmer
0.686
965131AG1-378 GEN
Solar/Wind Harmer
2.402
960051AF2-296 GEN
Solar/Wind Harmer
2.277
20335126GROZ1-110
Adder
2.01
20335226CANZ2-011
Adder
1.954
20120126WRREN CT
Adder
5.045
941421AE2-139 GEN
Solar/Wind Harmer
2.254
203818AF1-086 GEN
Solar/Wind Harmer
1.887
971703AH1-357 GEN
Solar/Wind Harmer
1.474
971707AH1-359 GEN
Solar/Wind Harmer
1.474
972271AH1-720 GEN
Adder
4.352
20334926Z1-069 C
Solar/Wind Harmer
1.353
20328326MANOR_T86
Adder
0.088
970335AG2-220 GEN
Solar/Wind Harmer
1.846
971127AH1-005 GEN
Solar/Wind Harmer
1.191
944411AF1-106 GEN
Solar/Wind Harmer
0.125
200917MEHOOPANY_G
Solar/Wind Harmer
1.678
238219AF1-167 C
Solar/Wind Harmer
0.617
20326126BLOSSBCT
Adder
1.568
959471AF2-238 GEN
Solar/Wind Harmer
0.387
970337AG2-221 GEN
Solar/Wind Harmer
1.28
970511AG2-327 GEN
Solar/Wind Harmer
0.596
20335026MILZ1-092
Adder
1.264
944411AF1-106 GEN
Solar/Wind Harmer
1.164
203835AF1-098 GEN
Solar/Wind Harmer
1.195
964391AG1-301 GEN
Solar/Wind Helper
0.237
940863AE2-074 GEN
Solar/Wind Harmer
1.219
970555AG2-356 GEN
Solar/Wind Harmer
1.28
203926AA2-133 GEN
Adder
1.289
20334726NME_Y1-047
Adder
1.128
20083926HOMER C3
Adder
18.2
20083826HOMER C2
Adder
17.192
20083726HOMER C1
Adder
8.808
203975AE1-071-GEN
Solar/Wind Helper
1.71
959381AF2-229 GEN
Solar/Wind Helper
0.172
LGEELTFEXP_LGEE->PJM
CLTF
0.168
WECLTFEXP_WEC->PJM
CLTF
0.105
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.762
LAGNLTFEXP_LAGN->PJM
CLTF
0.339
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.013
TVALTFEXP_TVA->PJM
CLTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.567
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01DALE-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-459T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01DALE-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-459T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.37 %
Rating:523.0 MVA
Rating Type:B
MVA to Mitigate:535.41
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.408
203855AF2-088 C
Solar/Wind Harmer
0.33
965121AG1-377 GEN
Solar/Wind Harmer
2.402
203804AE2-113_GEN
Solar/Wind Harmer
5.105
20090526Q36
Solar/Wind Harmer
1.261
203993AD2-133_GEN1
Solar/Wind Harmer
1.261
940863AE2-074 GEN
Solar/Wind Harmer
1.219
970555AG2-356 GEN
Solar/Wind Harmer
1.28
203926AA2-133 GEN
Adder
1.289
20334726NME_Y1-047
Adder
1.128
20083926HOMER C3
Adder
18.2
20083826HOMER C2
Adder
17.192
20083726HOMER C1
Adder
8.808
20066526SHAWVL 3
50/50
2.194
20066626SHAWVL 4
50/50
2.191
20071526SHAWVL 1
50/50
1.432
216419AE2-001 C
Solar/Wind Harmer
6.635
238217AF1-153 C O1
Solar/Wind Harmer
0.942
203952AE2-129 C
Solar/Wind Harmer
0.727
203946AE2-131 C
Solar/Wind Harmer
0.726
962411AG1-090 GEN
Solar/Wind Harmer
11.408
203853AF1-134 C O1
Solar/Wind Harmer
0.688
946381AF1-302 GEN
Solar/Wind Harmer
2.357
972075AH1-587 GEN
Solar/Wind Harmer
19.423
970305AG2-200 GEN
Solar/Wind Harmer
1.596
972077AH1-588 GEN
Solar/Wind Harmer
17.684
972079AH1-589 GEN
Solar/Wind Harmer
14.565
970715AG2-457 GEN
Solar/Wind Harmer
5.895
970313AG2-206 GEN
Solar/Wind Harmer
2.861
20398826ARMNA MT
Solar/Wind Harmer
1.347
203859AF2-294 C
Solar/Wind Harmer
0.848
20390526W1-045 C
Solar/Wind Helper
0.169
203975AE1-071-GEN
Solar/Wind Helper
1.71
959381AF2-229 GEN
Solar/Wind Helper
0.172
200644SENECA#3
50/50
0.181
238202AE2-262_GEN
Solar/Wind Harmer
8.255
971627AH1-313 GEN
Solar/Wind Harmer
32.367
203854AF2-039 C
Solar/Wind Harmer
0.686
965131AG1-378 GEN
Solar/Wind Harmer
2.402
960051AF2-296 GEN
Solar/Wind Harmer
2.277
20335126GROZ1-110
Adder
2.01
20335226CANZ2-011
Adder
1.954
20120126WRREN CT
Adder
5.045
941421AE2-139 GEN
Solar/Wind Harmer
2.254
203818AF1-086 GEN
Solar/Wind Harmer
1.887
971703AH1-357 GEN
Solar/Wind Harmer
1.474
971707AH1-359 GEN
Solar/Wind Harmer
1.474
972271AH1-720 GEN
Adder
4.352
20334926Z1-069 C
Solar/Wind Harmer
1.353
20328326MANOR_T86
Adder
0.088
970335AG2-220 GEN
Solar/Wind Harmer
1.846
971127AH1-005 GEN
Solar/Wind Harmer
1.191
944411AF1-106 GEN
Solar/Wind Harmer
0.125
200917MEHOOPANY_G
Solar/Wind Harmer
1.678
238219AF1-167 C
Solar/Wind Harmer
0.617
20072226SHAWVL 2
50/50
28.754
20091326SHAW-D
50/50
1.17
20064926PENNTECH
50/50
0.389
200643SENECA#2
50/50
1.313
238206AE2-263_GEN
Solar/Wind Harmer
7.694
238215AE2-248 C
Solar/Wind Harmer
3.327
972169AH1-667 GEN
Solar/Wind Harmer
3.019
203954AE2-126 C
Solar/Wind Harmer
0.937
238183AE2-316 GEN
Solar/Wind Harmer
4.711
970713AG2-456 GEN
Solar/Wind Harmer
5.895
971705AH1-358 GEN
Solar/Wind Harmer
1.714
971709AH1-360 GEN
Solar/Wind Harmer
1.714
20326126BLOSSBCT
Adder
1.568
959471AF2-238 GEN
Solar/Wind Harmer
0.387
970337AG2-221 GEN
Solar/Wind Harmer
1.28
970511AG2-327 GEN
Solar/Wind Harmer
0.596
20335026MILZ1-092
Adder
1.264
944411AF1-106 GEN
Solar/Wind Harmer
1.164
203835AF1-098 GEN
Solar/Wind Harmer
1.195
964391AG1-301 GEN
Solar/Wind Helper
0.237
LGEELTFEXP_LGEE->PJM
CLTF
0.168
WECLTFEXP_WEC->PJM
CLTF
0.105
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.021
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.762
LAGNLTFEXP_LAGN->PJM
CLTF
0.339
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.013
TVALTFEXP_TVA->PJM
CLTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.567
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01ELKO-01CARB J 138.0 kV Ckt 1 line l/o AP_P2-2_WP-230-002_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ELKO-01CARB J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-002_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:195.55
MW Contribution:1.02
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
3.349
20083926HOMER C3
Adder
9.57
20083826HOMER C2
Adder
9.04
20083726HOMER C1
Adder
3.175
203855AF2-088 C
Solar/Wind Helper
0.151
20090526Q36
Solar/Wind Helper
0.602
203993AD2-133_GEN1
Solar/Wind Helper
0.602
946381AF1-302 GEN
Solar/Wind Harmer
3.486
970305AG2-200 GEN
Solar/Wind Harmer
1.286
972075AH1-587 GEN
Solar/Wind Harmer
12.707
972077AH1-588 GEN
Solar/Wind Harmer
12.285
20120126WRREN CT
Adder
4.064
971703AH1-357 GEN
Solar/Wind Harmer
1.024
971707AH1-359 GEN
Solar/Wind Harmer
1.024
238202AE2-262_GEN
Solar/Wind Helper
1.263
203854AF2-039 C
Solar/Wind Helper
0.314
20064926PENNTECH
50/50
0.257
238183AE2-316 GEN
Solar/Wind Harmer
6.967
970713AG2-456 GEN
Solar/Wind Harmer
4.095
971705AH1-358 GEN
Solar/Wind Harmer
1.19
971709AH1-360 GEN
Solar/Wind Harmer
1.19
238206AE2-263_GEN
Solar/Wind Helper
1.201
972079AH1-589 GEN
Solar/Wind Harmer
10.119
970715AG2-457 GEN
Solar/Wind Harmer
4.095
238217AF1-153 C O1
Solar/Wind Helper
0.19
203952AE2-129 C
Solar/Wind Helper
0.362
203946AE2-131 C
Solar/Wind Helper
0.362
203853AF1-134 C O1
Solar/Wind Helper
0.291
CPLELTFEXP_CPLE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.868
LAGNLTFEXP_LAGN->PJM
CLTF
0.536
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.508
TVALTFEXP_TVA->PJM
CLTF
0.264
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.162
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.022
MECLTFEXP_MEC->PJM
CLTF
0.529
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 01ELKO-01CARB J 138.0 kV Ckt 1 line l/o AP_P2-3_WP-230-442_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ELKO-01CARB J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-442_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.85 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:195.54
MW Contribution:1.02
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
3.349
20083926HOMER C3
Adder
9.57
20083826HOMER C2
Adder
9.04
20083726HOMER C1
Adder
3.175
203855AF2-088 C
Solar/Wind Helper
0.151
20090526Q36
Solar/Wind Helper
0.602
203993AD2-133_GEN1
Solar/Wind Helper
0.602
20120126WRREN CT
Adder
4.064
971703AH1-357 GEN
Solar/Wind Harmer
1.024
971707AH1-359 GEN
Solar/Wind Harmer
1.024
238202AE2-262_GEN
Solar/Wind Helper
1.263
203854AF2-039 C
Solar/Wind Helper
0.314
946381AF1-302 GEN
Solar/Wind Harmer
3.486
970305AG2-200 GEN
Solar/Wind Harmer
1.286
972075AH1-587 GEN
Solar/Wind Harmer
12.707
972077AH1-588 GEN
Solar/Wind Harmer
12.285
972079AH1-589 GEN
Solar/Wind Harmer
10.119
970715AG2-457 GEN
Solar/Wind Harmer
4.095
238217AF1-153 C O1
Solar/Wind Helper
0.19
203952AE2-129 C
Solar/Wind Helper
0.362
203946AE2-131 C
Solar/Wind Helper
0.362
203853AF1-134 C O1
Solar/Wind Helper
0.291
20064926PENNTECH
50/50
0.257
238183AE2-316 GEN
Solar/Wind Harmer
6.967
970713AG2-456 GEN
Solar/Wind Harmer
4.095
971705AH1-358 GEN
Solar/Wind Harmer
1.19
971709AH1-360 GEN
Solar/Wind Harmer
1.19
238206AE2-263_GEN
Solar/Wind Helper
1.201
NYPJM->LTFIMP_NY
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.126
CPLELTFEXP_CPLE->PJM
CLTF
0.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.868
LAGNLTFEXP_LAGN->PJM
CLTF
0.536
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.508
TVALTFEXP_TVA->PJM
CLTF
0.264
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.162
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.022
MECLTFEXP_MEC->PJM
CLTF
0.529
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:183.35 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:276.86
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
65.798
20083826HOMER C2
50/50
62.154
970663AG2-429 GEN
Solar/Wind Harmer
7.966
970663AG2-429 GEN
Solar/Wind Harmer
1.297
20083226HNSMLK 5
Adder
4.637
203846AF2-130 C
Solar/Wind Harmer
0.451
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.08
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.468
203932AE1-123
Adder
1.649
20082926HNSMLK 2
Adder
4.637
20083126HNSMLK 4
Adder
4.637
971185AH1-051 GEN
Solar/Wind Harmer
1.823
971355AH1-158 GEN
Solar/Wind Harmer
2.12
203856AF2-165 C
Solar/Wind Harmer
0.879
970647AG2-420 GEN
Solar/Wind Harmer
1.464
959441AF2-235 GEN
Solar/Wind Harmer
0.205
971703AH1-357 GEN
Solar/Wind Harmer
1.275
971707AH1-359 GEN
Solar/Wind Harmer
1.275
20334926Z1-069 C
Solar/Wind Harmer
1.258
945751AF1-240 GEN
Solar/Wind Harmer
0.899
957161AF2-010 GEN
Solar/Wind Harmer
4.311
203830AF1-094 GEN
Solar/Wind Harmer
0.336
20120126WRREN CT
Adder
3.42
962511AG1-100 GEN
Solar/Wind Harmer
0.311
203962AF1-287 GEN
Solar/Wind Harmer
1.025
944411AF1-106 GEN
Solar/Wind Harmer
0.115
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.448
971127AH1-005 GEN
Solar/Wind Harmer
0.934
238183AE2-316 GEN
Solar/Wind Harmer
3.929
20082826HNSMLK 1
Adder
4.637
20083026HNSMLK 3
Adder
4.637
971183AH1-050 GEN
Solar/Wind Harmer
3.039
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.099
971705AH1-358 GEN
Solar/Wind Harmer
1.482
971709AH1-360 GEN
Solar/Wind Harmer
1.482
970267AG2-176 GEN
Solar/Wind Harmer
9.102
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.943
20326126BLOSSBCT
Adder
1.167
20335026MILZ1-092
Adder
1.158
944411AF1-106 GEN
Solar/Wind Harmer
1.067
203835AF1-098 GEN
Solar/Wind Harmer
1.193
959471AF2-238 GEN
Solar/Wind Harmer
0.291
970337AG2-221 GEN
Solar/Wind Harmer
0.963
203954AE2-126 C
Solar/Wind Harmer
0.288
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.465
20072226SHAWVL 2
Adder
5.916
203804AE2-113_GEN
Solar/Wind Harmer
2.862
970677AG2-438 GEN
Solar/Wind Harmer
0.554
966771AG1-548 GEN
Solar/Wind Harmer
7.972
966771AG1-548 GEN
Solar/Wind Harmer
1.545
970555AG2-356 GEN
Solar/Wind Harmer
0.963
20084926LAKVU GN
Adder
0.093
20083726HOMER C1
Adder
4.668
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.966
203848AF2-166 C
Solar/Wind Harmer
1.578
972077AH1-588 GEN
Solar/Wind Harmer
15.298
972079AH1-589 GEN
Solar/Wind Harmer
12.6
970715AG2-457 GEN
Solar/Wind Harmer
5.099
238217AF1-153 C O1
Solar/Wind Harmer
0.373
972075AH1-587 GEN
Solar/Wind Harmer
12.162
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.108
970305AG2-200 GEN
Solar/Wind Harmer
1.082
971931AH1-490 GEN
Solar/Wind Harmer
1.029
20398826ARMNA MT
Solar/Wind Harmer
1.201
203963AG1-253 GEN
Solar/Wind Harmer
0.193
203859AF2-294 C
Solar/Wind Harmer
0.804
203947AF1-006 C
Solar/Wind Harmer
0.262
970313AG2-206 GEN
Solar/Wind Harmer
2.232
G-007ALTFEXP_G-007A->PJM
CMTX
0.536
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.106
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.697
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.597
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.367
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.259
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.14 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:273.52
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.467
203932AE1-123
Adder
1.647
20082926HNSMLK 2
Adder
4.631
20083126HNSMLK 4
Adder
4.631
971185AH1-051 GEN
Solar/Wind Harmer
1.821
971355AH1-158 GEN
Solar/Wind Harmer
2.117
203856AF2-165 C
Solar/Wind Harmer
0.877
970647AG2-420 GEN
Solar/Wind Harmer
1.462
959441AF2-235 GEN
Solar/Wind Harmer
0.204
971703AH1-357 GEN
Solar/Wind Harmer
1.27
971707AH1-359 GEN
Solar/Wind Harmer
1.27
20334926Z1-069 C
Solar/Wind Harmer
1.254
945751AF1-240 GEN
Solar/Wind Harmer
0.897
957161AF2-010 GEN
Solar/Wind Harmer
4.302
203830AF1-094 GEN
Solar/Wind Harmer
0.335
20120126WRREN CT
Adder
3.407
962511AG1-100 GEN
Solar/Wind Harmer
0.31
203962AF1-287 GEN
Solar/Wind Harmer
1.023
944411AF1-106 GEN
Solar/Wind Harmer
0.114
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.442
971127AH1-005 GEN
Solar/Wind Harmer
0.931
238183AE2-316 GEN
Solar/Wind Harmer
3.917
20082826HNSMLK 1
Adder
4.631
20083026HNSMLK 3
Adder
4.631
971183AH1-050 GEN
Solar/Wind Harmer
3.034
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.082
971705AH1-358 GEN
Solar/Wind Harmer
1.477
971709AH1-360 GEN
Solar/Wind Harmer
1.477
970267AG2-176 GEN
Solar/Wind Harmer
9.088
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.932
20326126BLOSSBCT
Adder
1.162
20335026MILZ1-092
Adder
1.154
944411AF1-106 GEN
Solar/Wind Harmer
1.064
203835AF1-098 GEN
Solar/Wind Harmer
1.189
959471AF2-238 GEN
Solar/Wind Harmer
0.29
970337AG2-221 GEN
Solar/Wind Harmer
0.959
203954AE2-126 C
Solar/Wind Harmer
0.285
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.463
20083926HOMER C3
50/50
65.706
20083826HOMER C2
50/50
62.067
970663AG2-429 GEN
Solar/Wind Harmer
7.958
970663AG2-429 GEN
Solar/Wind Harmer
1.296
20083226HNSMLK 5
Adder
4.631
203846AF2-130 C
Solar/Wind Harmer
0.45
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.077
203804AE2-113_GEN
Solar/Wind Harmer
2.847
970677AG2-438 GEN
Solar/Wind Harmer
0.553
966771AG1-548 GEN
Solar/Wind Harmer
7.956
966771AG1-548 GEN
Solar/Wind Harmer
1.542
970555AG2-356 GEN
Solar/Wind Harmer
0.959
20084926LAKVU GN
Adder
0.092
20083726HOMER C1
Adder
4.658
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.96
203848AF2-166 C
Solar/Wind Harmer
1.576
972077AH1-588 GEN
Solar/Wind Harmer
15.245
972079AH1-589 GEN
Solar/Wind Harmer
12.556
970715AG2-457 GEN
Solar/Wind Harmer
5.082
238217AF1-153 C O1
Solar/Wind Harmer
0.37
972075AH1-587 GEN
Solar/Wind Harmer
12.105
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.106
970305AG2-200 GEN
Solar/Wind Harmer
1.078
971931AH1-490 GEN
Solar/Wind Harmer
1.027
20398826ARMNA MT
Solar/Wind Harmer
1.197
203963AG1-253 GEN
Solar/Wind Harmer
0.192
203859AF2-294 C
Solar/Wind Harmer
0.801
203947AF1-006 C
Solar/Wind Harmer
0.261
970313AG2-206 GEN
Solar/Wind Harmer
2.223
G-007ALTFEXP_G-007A->PJM
CMTX
0.527
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.652
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.571
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.063
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.256
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:181.14 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:273.52
MW Contribution:1.27
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.014
238219AF1-167 C
Solar/Wind Harmer
1.467
203932AE1-123
Adder
1.647
20082926HNSMLK 2
Adder
4.631
20083126HNSMLK 4
Adder
4.631
971185AH1-051 GEN
Solar/Wind Harmer
1.821
971355AH1-158 GEN
Solar/Wind Harmer
2.117
203856AF2-165 C
Solar/Wind Harmer
0.877
970647AG2-420 GEN
Solar/Wind Harmer
1.462
959441AF2-235 GEN
Solar/Wind Harmer
0.204
971703AH1-357 GEN
Solar/Wind Harmer
1.27
971707AH1-359 GEN
Solar/Wind Harmer
1.27
20334926Z1-069 C
Solar/Wind Harmer
1.254
945751AF1-240 GEN
Solar/Wind Harmer
0.897
957161AF2-010 GEN
Solar/Wind Harmer
4.302
203830AF1-094 GEN
Solar/Wind Harmer
0.335
20120126WRREN CT
Adder
3.407
962511AG1-100 GEN
Solar/Wind Harmer
0.31
203962AF1-287 GEN
Solar/Wind Harmer
1.023
944411AF1-106 GEN
Solar/Wind Harmer
0.114
203948AG1-140 C
Solar/Wind Harmer
0.126
20084926LAKVU GN
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.442
971127AH1-005 GEN
Solar/Wind Harmer
0.931
238183AE2-316 GEN
Solar/Wind Harmer
3.917
20082826HNSMLK 1
Adder
4.631
20083026HNSMLK 3
Adder
4.631
971183AH1-050 GEN
Solar/Wind Harmer
3.034
970647AG2-420 GEN
Solar/Wind Harmer
0.17
203860AG1-193 C
Solar/Wind Harmer
0.211
970713AG2-456 GEN
Solar/Wind Harmer
5.082
971705AH1-358 GEN
Solar/Wind Harmer
1.477
971709AH1-360 GEN
Solar/Wind Harmer
1.477
970267AG2-176 GEN
Solar/Wind Harmer
9.088
961971AG1-040 GEN
Solar/Wind Harmer
0.333
203813AE2-344_GEN
Solar/Wind Harmer
5.932
20326126BLOSSBCT
Adder
1.162
20335026MILZ1-092
Adder
1.154
944411AF1-106 GEN
Solar/Wind Harmer
1.064
203835AF1-098 GEN
Solar/Wind Harmer
1.189
959471AF2-238 GEN
Solar/Wind Harmer
0.29
970337AG2-221 GEN
Solar/Wind Harmer
0.959
203954AE2-126 C
Solar/Wind Harmer
0.285
20084926LAKVU GN
Adder
0.082
970511AG2-327 GEN
Solar/Wind Harmer
0.463
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.96
203848AF2-166 C
Solar/Wind Harmer
1.576
972077AH1-588 GEN
Solar/Wind Harmer
15.245
972079AH1-589 GEN
Solar/Wind Harmer
12.556
970715AG2-457 GEN
Solar/Wind Harmer
5.082
238217AF1-153 C O1
Solar/Wind Harmer
0.37
972075AH1-587 GEN
Solar/Wind Harmer
12.105
203980AG1-197 GEN
Solar/Wind Harmer
0.254
203979AG1-198 GEN
Solar/Wind Harmer
0.201
971933AH1-491 GEN
Solar/Wind Harmer
1.106
970305AG2-200 GEN
Solar/Wind Harmer
1.078
971931AH1-490 GEN
Solar/Wind Harmer
1.027
20398826ARMNA MT
Solar/Wind Harmer
1.197
203963AG1-253 GEN
Solar/Wind Harmer
0.192
20083926HOMER C3
50/50
65.706
20083826HOMER C2
50/50
62.067
970663AG2-429 GEN
Solar/Wind Harmer
7.958
970663AG2-429 GEN
Solar/Wind Harmer
1.296
20083226HNSMLK 5
Adder
4.631
203846AF2-130 C
Solar/Wind Harmer
0.45
971055AG2-654 GEN
Solar/Wind Harmer
0.847
940863AE2-074 GEN
Solar/Wind Harmer
1.077
203804AE2-113_GEN
Solar/Wind Harmer
2.847
970677AG2-438 GEN
Solar/Wind Harmer
0.553
966771AG1-548 GEN
Solar/Wind Harmer
7.956
966771AG1-548 GEN
Solar/Wind Harmer
1.542
970555AG2-356 GEN
Solar/Wind Harmer
0.959
20084926LAKVU GN
Adder
0.092
20083726HOMER C1
Adder
4.658
203859AF2-294 C
Solar/Wind Harmer
0.801
203947AF1-006 C
Solar/Wind Harmer
0.261
970313AG2-206 GEN
Solar/Wind Harmer
2.223
G-007ALTFEXP_G-007A->PJM
CMTX
0.527
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.652
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.571
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.063
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.256
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-177_A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-177_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.97 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:255.15
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.033
238219AF1-167 C
Solar/Wind Harmer
1.746
971185AH1-051 GEN
Solar/Wind Harmer
1.987
971355AH1-158 GEN
Solar/Wind Harmer
2.311
203856AF2-165 C
Solar/Wind Harmer
0.954
970647AG2-420 GEN
Solar/Wind Harmer
1.572
20082926HNSMLK 2
Adder
4.379
20083126HNSMLK 4
Adder
4.379
959441AF2-235 GEN
Solar/Wind Harmer
0.217
945751AF1-240 GEN
Solar/Wind Harmer
1.121
957161AF2-010 GEN
Solar/Wind Harmer
4.268
203830AF1-094 GEN
Solar/Wind Harmer
0.331
971703AH1-357 GEN
Solar/Wind Harmer
1.026
971707AH1-359 GEN
Solar/Wind Harmer
1.026
20120126WRREN CT
Adder
3.099
962511AG1-100 GEN
Solar/Wind Harmer
0.292
203962AF1-287 GEN
Solar/Wind Harmer
0.961
20334926Z1-069 C
Solar/Wind Harmer
0.981
203854AF2-039 C
Solar/Wind Harmer
0.187
238202AE2-262_GEN
Solar/Wind Harmer
1.12
971627AH1-313 GEN
Solar/Wind Harmer
4.389
203948AG1-140 C
Solar/Wind Harmer
0.114
20060826PINEY #1
50/50
0.066
238183AE2-316 GEN
Solar/Wind Harmer
4.473
971183AH1-050 GEN
Solar/Wind Harmer
3.312
970647AG2-420 GEN
Solar/Wind Harmer
0.183
20082826HNSMLK 1
Adder
4.379
20083026HNSMLK 3
Adder
4.379
203860AG1-193 C
Solar/Wind Harmer
0.216
970267AG2-176 GEN
Solar/Wind Harmer
8.783
961971AG1-040 GEN
Solar/Wind Harmer
0.317
970713AG2-456 GEN
Solar/Wind Harmer
4.103
971705AH1-358 GEN
Solar/Wind Harmer
1.193
971709AH1-360 GEN
Solar/Wind Harmer
1.193
203954AE2-126 C
Solar/Wind Harmer
0.304
971865AH1-452 GEN
Solar/Wind Harmer
0.846
203813AE2-344_GEN
Solar/Wind Harmer
5.571
20072226SHAWVL 2
Adder
6.51
972169AH1-667 GEN
Solar/Wind Harmer
0.824
20091326SHAW-D
Adder
0.301
203835AF1-098 GEN
Solar/Wind Harmer
1.093
238206AE2-263_GEN
Solar/Wind Harmer
1.043
20060826PINEY #1
50/50
0.059
970663AG2-429 GEN
Solar/Wind Harmer
9.339
970663AG2-429 GEN
Solar/Wind Harmer
1.52
971055AG2-654 GEN
Solar/Wind Harmer
1.148
203846AF2-130 C
Solar/Wind Harmer
0.509
20083226HNSMLK 5
Adder
4.379
20083926HOMER C3
Adder
40.151
20083826HOMER C2
Adder
37.927
970677AG2-438 GEN
Solar/Wind Harmer
0.546
966771AG1-548 GEN
Solar/Wind Harmer
7.806
966771AG1-548 GEN
Solar/Wind Harmer
1.513
203804AE2-113_GEN
Solar/Wind Harmer
2.528
940863AE2-074 GEN
Solar/Wind Harmer
0.855
203855AF2-088 C
Solar/Wind Harmer
0.09
20083726HOMER C1
Adder
22.048
23513401AL&D6
50/50
0.029
946381AF1-302 GEN
Solar/Wind Harmer
2.238
203848AF2-166 C
Solar/Wind Harmer
1.782
238217AF1-153 C O1
Solar/Wind Harmer
0.407
203979AG1-198 GEN
Solar/Wind Harmer
0.198
971933AH1-491 GEN
Solar/Wind Harmer
1.092
203980AG1-197 GEN
Solar/Wind Harmer
0.242
972075AH1-587 GEN
Solar/Wind Harmer
10.438
972077AH1-588 GEN
Solar/Wind Harmer
12.308
972079AH1-589 GEN
Solar/Wind Harmer
10.138
970715AG2-457 GEN
Solar/Wind Harmer
4.103
970305AG2-200 GEN
Solar/Wind Harmer
0.98
971931AH1-490 GEN
Solar/Wind Harmer
0.967
203963AG1-253 GEN
Solar/Wind Harmer
0.173
203947AF1-006 C
Solar/Wind Harmer
0.241
G-007ALTFEXP_G-007A->PJM
CMTX
1.254
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.519
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.576
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.822
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.68 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:250.18
MW Contribution:1.11
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.013
20060826PINEY #1
50/50
0.057
203932AE1-123
50/50
1.823
238219AF1-167 C
Solar/Wind Harmer
1.449
971185AH1-051 GEN
Solar/Wind Harmer
2.005
971355AH1-158 GEN
Solar/Wind Harmer
2.331
203856AF2-165 C
Solar/Wind Harmer
0.976
970647AG2-420 GEN
Solar/Wind Harmer
1.631
20082926HNSMLK 2
Adder
4.736
20083126HNSMLK 4
Adder
4.736
959441AF2-235 GEN
Solar/Wind Harmer
0.239
957161AF2-010 GEN
Solar/Wind Harmer
5.628
203830AF1-094 GEN
Solar/Wind Harmer
0.441
962511AG1-100 GEN
Solar/Wind Harmer
0.435
203962AF1-287 GEN
Solar/Wind Harmer
1.43
20084926LAKVU GN
Adder
0.12
203948AG1-140 C
Solar/Wind Harmer
0.176
945751AF1-240 GEN
Solar/Wind Harmer
1.018
20120126WRREN CT
Adder
3.9
971703AH1-357 GEN
Solar/Wind Harmer
1.109
971707AH1-359 GEN
Solar/Wind Harmer
1.109
20334926Z1-069 C
Solar/Wind Harmer
1.026
203854AF2-039 C
Solar/Wind Harmer
0.183
20060826PINEY #1
50/50
0.06
238183AE2-316 GEN
Solar/Wind Harmer
3.848
971183AH1-050 GEN
Solar/Wind Harmer
3.341
970647AG2-420 GEN
Solar/Wind Harmer
0.19
20082826HNSMLK 1
Adder
4.736
20083026HNSMLK 3
Adder
4.736
203860AG1-193 C
Solar/Wind Harmer
0.241
970267AG2-176 GEN
Solar/Wind Harmer
11.328
961971AG1-040 GEN
Solar/Wind Harmer
0.443
203813AE2-344_GEN
Solar/Wind Harmer
8.328
20084926LAKVU GN
Adder
0.12
203835AF1-098 GEN
Solar/Wind Harmer
1.634
970713AG2-456 GEN
Solar/Wind Harmer
4.437
971705AH1-358 GEN
Solar/Wind Harmer
1.29
971709AH1-360 GEN
Solar/Wind Harmer
1.29
203954AE2-126 C
Solar/Wind Harmer
0.303
20072226SHAWVL 2
Adder
6.358
972169AH1-667 GEN
Solar/Wind Harmer
0.807
20091326SHAW-D
Adder
0.295
20060826PINEY #1
50/50
0.053
970663AG2-429 GEN
Solar/Wind Harmer
7.76
970663AG2-429 GEN
Solar/Wind Harmer
1.263
203846AF2-130 C
Solar/Wind Harmer
0.483
20083226HNSMLK 5
Adder
4.736
970677AG2-438 GEN
Solar/Wind Harmer
0.728
966771AG1-548 GEN
Solar/Wind Harmer
10.575
966771AG1-548 GEN
Solar/Wind Harmer
2.049
20084926LAKVU GN
Adder
0.135
971055AG2-654 GEN
Solar/Wind Harmer
0.835
203804AE2-113_GEN
Solar/Wind Harmer
2.624
20083926HOMER C3
Adder
37.811
20083826HOMER C2
Adder
35.717
940863AE2-074 GEN
Solar/Wind Harmer
0.901
203855AF2-088 C
Solar/Wind Harmer
0.088
20083726HOMER C1
Adder
21.283
23513401AL&D6
50/50
0.013
946381AF1-302 GEN
Solar/Wind Harmer
1.925
203848AF2-166 C
Solar/Wind Harmer
1.692
203980AG1-197 GEN
Solar/Wind Harmer
0.335
203979AG1-198 GEN
Solar/Wind Harmer
0.265
971933AH1-491 GEN
Solar/Wind Harmer
1.456
971931AH1-490 GEN
Solar/Wind Harmer
1.437
203947AF1-006 C
Solar/Wind Harmer
0.39
203963AG1-253 GEN
Solar/Wind Harmer
0.269
238217AF1-153 C O1
Solar/Wind Harmer
0.381
970305AG2-200 GEN
Solar/Wind Harmer
1.234
972077AH1-588 GEN
Solar/Wind Harmer
13.31
972079AH1-589 GEN
Solar/Wind Harmer
10.963
970715AG2-457 GEN
Solar/Wind Harmer
4.437
972075AH1-587 GEN
Solar/Wind Harmer
10.904
G-007ALTFEXP_G-007A->PJM
CMTX
1.515
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.954
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.224
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.24
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.745
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.078
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-054_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-054_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:150.85 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:227.78
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
970663AG2-429 GEN
Solar/Wind Harmer
8.01
970663AG2-429 GEN
Solar/Wind Harmer
1.304
203846AF2-130 C
Solar/Wind Harmer
0.431
971055AG2-654 GEN
Solar/Wind Harmer
0.806
20083226HNSMLK 5
Adder
3.738
970677AG2-438 GEN
Solar/Wind Harmer
0.466
20083926HOMER C3
Adder
32.796
20083826HOMER C2
Adder
30.979
966771AG1-548 GEN
Solar/Wind Harmer
6.66
966771AG1-548 GEN
Solar/Wind Harmer
1.291
203804AE2-113_GEN
Solar/Wind Harmer
2.091
20083726HOMER C1
Adder
16.47
23503001MHNG-T155
50/50
0.015
238219AF1-167 C
Solar/Wind Harmer
1.49
203932AE1-123
Adder
1.619
971185AH1-051 GEN
Solar/Wind Harmer
1.685
971355AH1-158 GEN
Solar/Wind Harmer
1.96
203856AF2-165 C
Solar/Wind Harmer
0.809
970647AG2-420 GEN
Solar/Wind Harmer
1.335
20082926HNSMLK 2
Adder
3.738
20083126HNSMLK 4
Adder
3.738
959441AF2-235 GEN
Solar/Wind Harmer
0.185
945751AF1-240 GEN
Solar/Wind Harmer
0.913
957161AF2-010 GEN
Solar/Wind Harmer
3.639
203830AF1-094 GEN
Solar/Wind Harmer
0.282
971703AH1-357 GEN
Solar/Wind Harmer
0.849
971707AH1-359 GEN
Solar/Wind Harmer
0.849
946381AF1-302 GEN
Solar/Wind Harmer
1.913
203848AF2-166 C
Solar/Wind Harmer
1.509
238217AF1-153 C O1
Solar/Wind Harmer
0.341
203979AG1-198 GEN
Solar/Wind Harmer
0.169
971933AH1-491 GEN
Solar/Wind Harmer
0.931
203980AG1-197 GEN
Solar/Wind Harmer
0.208
972075AH1-587 GEN
Solar/Wind Harmer
8.631
972077AH1-588 GEN
Solar/Wind Harmer
10.19
972079AH1-589 GEN
Solar/Wind Harmer
8.393
970715AG2-457 GEN
Solar/Wind Harmer
3.397
238183AE2-316 GEN
Solar/Wind Harmer
3.822
971183AH1-050 GEN
Solar/Wind Harmer
2.809
970647AG2-420 GEN
Solar/Wind Harmer
0.155
20082826HNSMLK 1
Adder
3.738
20083026HNSMLK 3
Adder
3.738
203860AG1-193 C
Solar/Wind Harmer
0.184
970267AG2-176 GEN
Solar/Wind Harmer
7.51
961971AG1-040 GEN
Solar/Wind Harmer
0.271
970713AG2-456 GEN
Solar/Wind Harmer
3.397
971705AH1-358 GEN
Solar/Wind Harmer
0.987
971709AH1-360 GEN
Solar/Wind Harmer
0.987
G-007ALTFEXP_G-007A->PJM
CMTX
0.681
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.109
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.76
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.946
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.343
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.49
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.37 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:218.0
MW Contribution:0.71
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.029
203848AF2-166 C
Solar/Wind Harmer
1.242
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.762
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.269
972077AH1-588 GEN
Solar/Wind Harmer
8.573
972079AH1-589 GEN
Solar/Wind Harmer
10.121
970715AG2-457 GEN
Solar/Wind Harmer
3.322
970305AG2-200 GEN
Solar/Wind Harmer
0.683
971931AH1-490 GEN
Solar/Wind Harmer
0.675
203963AG1-253 GEN
Solar/Wind Harmer
0.136
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.059
20066226SCRUB GR
50/50
0.413
20083226HNSMLK 5
50/50
4.644
970663AG2-429 GEN
Solar/Wind Harmer
6.947
970663AG2-429 GEN
Solar/Wind Harmer
1.518
971055AG2-654 GEN
Solar/Wind Harmer
0.933
20083926HOMER C3
Adder
40.066
20083826HOMER C2
Adder
37.847
970677AG2-438 GEN
Solar/Wind Harmer
0.425
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.553
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.944
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.029
20082926HNSMLK 2
50/50
4.644
20083126HNSMLK 4
50/50
4.644
238219AF1-167 C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
1.71
971355AH1-158 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
1.096
945751AF1-240 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
2.963
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.714
971707AH1-359 GEN
Solar/Wind Harmer
0.714
20120126WRREN CT
Adder
3.096
203962AF1-287 GEN
Solar/Wind Harmer
0.671
20334926Z1-069 C
Solar/Wind Harmer
0.245
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.054
203948AG1-140 C
Solar/Wind Harmer
0.086
20060826PINEY #1
50/50
0.066
20082826HNSMLK 1
50/50
4.644
20083026HNSMLK 3
50/50
4.644
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
0.183
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.126
970713AG2-456 GEN
Solar/Wind Harmer
3.322
971705AH1-358 GEN
Solar/Wind Harmer
1.191
971709AH1-360 GEN
Solar/Wind Harmer
1.191
203954AE2-126 C
Solar/Wind Harmer
0.001
203813AE2-344_GEN
Solar/Wind Harmer
3.887
20072226SHAWVL 2
Adder
6.494
971865AH1-452 GEN
Solar/Wind Harmer
0.451
20091326SHAW-D
Adder
0.3
972169AH1-667 GEN
Solar/Wind Harmer
0.574
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
G-007ALTFEXP_G-007A->PJM
CMTX
1.215
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.982
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.554
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.79
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.03 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:202.39
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.068
20082826HNSMLK 1
50/50
4.728
20083026HNSMLK 3
50/50
4.728
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
0.186
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.236
970713AG2-456 GEN
Solar/Wind Harmer
3.392
971705AH1-358 GEN
Solar/Wind Harmer
1.216
971709AH1-360 GEN
Solar/Wind Harmer
1.216
203954AE2-126 C
Solar/Wind Harmer
0.001
971865AH1-452 GEN
Solar/Wind Harmer
0.487
203813AE2-344_GEN
Solar/Wind Harmer
3.956
20072226SHAWVL 2
Adder
6.64
20091326SHAW-D
Adder
0.308
972169AH1-667 GEN
Solar/Wind Harmer
0.587
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.077
23503001MHNG-T155
50/50
0.018
20060826PINEY #1
50/50
0.065
203932AE1-123
50/50
2.068
20082926HNSMLK 2
50/50
4.728
20083126HNSMLK 4
50/50
4.728
238219AF1-167 C
Solar/Wind Harmer
1.237
971185AH1-051 GEN
Solar/Wind Harmer
1.742
971355AH1-158 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
1.116
945751AF1-240 GEN
Solar/Wind Harmer
0.929
957161AF2-010 GEN
Solar/Wind Harmer
3.017
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.73
971707AH1-359 GEN
Solar/Wind Harmer
0.73
20120126WRREN CT
Adder
3.157
203962AF1-287 GEN
Solar/Wind Harmer
0.682
20334926Z1-069 C
Solar/Wind Harmer
0.251
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.124
203948AG1-140 C
Solar/Wind Harmer
0.087
20084926LAKVU GN
Adder
0.077
960051AF2-296 GEN
Solar/Wind Harmer
0.603
203848AF2-166 C
Solar/Wind Harmer
1.265
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.775
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.424
972077AH1-588 GEN
Solar/Wind Harmer
8.754
972079AH1-589 GEN
Solar/Wind Harmer
10.335
970715AG2-457 GEN
Solar/Wind Harmer
3.392
970305AG2-200 GEN
Solar/Wind Harmer
0.697
971931AH1-490 GEN
Solar/Wind Harmer
0.686
203963AG1-253 GEN
Solar/Wind Harmer
0.139
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.06
20066226SCRUB GR
50/50
0.421
20083226HNSMLK 5
50/50
4.728
970663AG2-429 GEN
Solar/Wind Harmer
7.068
970663AG2-429 GEN
Solar/Wind Harmer
1.545
971055AG2-654 GEN
Solar/Wind Harmer
0.966
20083926HOMER C3
Adder
40.966
20083826HOMER C2
Adder
38.697
970677AG2-438 GEN
Solar/Wind Harmer
0.433
966771AG1-548 GEN
Solar/Wind Harmer
1.265
966771AG1-548 GEN
Solar/Wind Harmer
1.581
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
22.622
G-007ALTFEXP_G-007A->PJM
CMTX
1.282
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.258
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.599
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.826
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-057_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-057_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.4 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:199.92
MW Contribution:0.91
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
1.974
203848AF2-166 C
Solar/Wind Harmer
1.556
238217AF1-153 C O1
Solar/Wind Harmer
0.357
203979AG1-198 GEN
Solar/Wind Harmer
0.174
971933AH1-491 GEN
Solar/Wind Harmer
0.959
203980AG1-197 GEN
Solar/Wind Harmer
0.213
972075AH1-587 GEN
Solar/Wind Harmer
9.212
972077AH1-588 GEN
Solar/Wind Harmer
10.87
972079AH1-589 GEN
Solar/Wind Harmer
8.953
970715AG2-457 GEN
Solar/Wind Harmer
3.623
970305AG2-200 GEN
Solar/Wind Harmer
0.864
970663AG2-429 GEN
Solar/Wind Harmer
8.167
970663AG2-429 GEN
Solar/Wind Harmer
1.33
203846AF2-130 C
Solar/Wind Harmer
0.444
20083226HNSMLK 5
Adder
3.865
20083926HOMER C3
Adder
35.571
20083826HOMER C2
Adder
33.601
970677AG2-438 GEN
Solar/Wind Harmer
0.48
966771AG1-548 GEN
Solar/Wind Harmer
6.857
966771AG1-548 GEN
Solar/Wind Harmer
1.329
203804AE2-113_GEN
Solar/Wind Harmer
2.23
940863AE2-074 GEN
Solar/Wind Harmer
0.755
20083726HOMER C1
Adder
19.645
23503001MHNG-T155
50/50
0.009
238219AF1-167 C
Solar/Wind Harmer
1.375
203932AE1-123
Adder
1.67
971185AH1-051 GEN
Solar/Wind Harmer
1.738
971355AH1-158 GEN
Solar/Wind Harmer
2.021
203856AF2-165 C
Solar/Wind Harmer
0.834
970647AG2-420 GEN
Solar/Wind Harmer
1.376
20082926HNSMLK 2
Adder
3.865
20083126HNSMLK 4
Adder
3.865
959441AF2-235 GEN
Solar/Wind Harmer
0.19
945751AF1-240 GEN
Solar/Wind Harmer
0.982
957161AF2-010 GEN
Solar/Wind Harmer
3.747
203830AF1-094 GEN
Solar/Wind Harmer
0.29
971703AH1-357 GEN
Solar/Wind Harmer
0.906
971707AH1-359 GEN
Solar/Wind Harmer
0.906
20120126WRREN CT
Adder
2.732
238183AE2-316 GEN
Solar/Wind Harmer
3.945
971183AH1-050 GEN
Solar/Wind Harmer
2.896
970647AG2-420 GEN
Solar/Wind Harmer
0.16
20082826HNSMLK 1
Adder
3.865
20083026HNSMLK 3
Adder
3.865
203860AG1-193 C
Solar/Wind Harmer
0.189
970267AG2-176 GEN
Solar/Wind Harmer
7.731
961971AG1-040 GEN
Solar/Wind Harmer
0.279
970713AG2-456 GEN
Solar/Wind Harmer
3.623
971705AH1-358 GEN
Solar/Wind Harmer
1.053
971709AH1-360 GEN
Solar/Wind Harmer
1.053
203954AE2-126 C
Solar/Wind Harmer
0.268
G-007ALTFEXP_G-007A->PJM
CMTX
1.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.13
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.887
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.109
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.161
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.084
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.501
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.713
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-2_PN-345-002T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-002T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.54 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:189.57
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.013
946381AF1-302 GEN
Solar/Wind Harmer
1.751
203848AF2-166 C
Solar/Wind Harmer
1.396
238217AF1-153 C O1
Solar/Wind Harmer
0.322
970663AG2-429 GEN
Solar/Wind Harmer
7.235
970663AG2-429 GEN
Solar/Wind Harmer
1.178
203846AF2-130 C
Solar/Wind Harmer
0.399
971055AG2-654 GEN
Solar/Wind Harmer
0.796
20083226HNSMLK 5
Adder
3.716
20083926HOMER C3
Adder
40.8
20083826HOMER C2
Adder
38.54
203804AE2-113_GEN
Solar/Wind Harmer
2.19
970677AG2-438 GEN
Solar/Wind Harmer
0.454
940863AE2-074 GEN
Solar/Wind Harmer
0.782
966771AG1-548 GEN
Solar/Wind Harmer
6.513
966771AG1-548 GEN
Solar/Wind Harmer
1.262
20083726HOMER C1
Adder
10.121
972077AH1-588 GEN
Solar/Wind Harmer
11.174
972079AH1-589 GEN
Solar/Wind Harmer
9.204
970715AG2-457 GEN
Solar/Wind Harmer
3.725
972075AH1-587 GEN
Solar/Wind Harmer
9.172
203979AG1-198 GEN
Solar/Wind Harmer
0.165
971933AH1-491 GEN
Solar/Wind Harmer
0.908
203980AG1-197 GEN
Solar/Wind Harmer
0.205
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.341
203932AE1-123
Adder
1.483
971185AH1-051 GEN
Solar/Wind Harmer
1.581
971355AH1-158 GEN
Solar/Wind Harmer
1.838
203856AF2-165 C
Solar/Wind Harmer
0.76
20082926HNSMLK 2
Adder
3.716
20083126HNSMLK 4
Adder
3.716
970647AG2-420 GEN
Solar/Wind Harmer
1.259
959441AF2-235 GEN
Solar/Wind Harmer
0.175
945751AF1-240 GEN
Solar/Wind Harmer
0.835
971703AH1-357 GEN
Solar/Wind Harmer
0.931
971707AH1-359 GEN
Solar/Wind Harmer
0.931
957161AF2-010 GEN
Solar/Wind Harmer
3.543
203830AF1-094 GEN
Solar/Wind Harmer
0.275
20334926Z1-069 C
Solar/Wind Harmer
0.903
238183AE2-316 GEN
Solar/Wind Harmer
3.499
971183AH1-050 GEN
Solar/Wind Harmer
2.635
20082826HNSMLK 1
Adder
3.716
20083026HNSMLK 3
Adder
3.716
970647AG2-420 GEN
Solar/Wind Harmer
0.146
203860AG1-193 C
Solar/Wind Harmer
0.177
970267AG2-176 GEN
Solar/Wind Harmer
7.382
970713AG2-456 GEN
Solar/Wind Harmer
3.725
971705AH1-358 GEN
Solar/Wind Harmer
1.083
971709AH1-360 GEN
Solar/Wind Harmer
1.083
961971AG1-040 GEN
Solar/Wind Harmer
0.268
G-007ALTFEXP_G-007A->PJM
CMTX
0.682
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.103
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.706
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.956
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.104
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.322
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.459
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-067_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-067_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.71 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:180.75
MW Contribution:0.87
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.055
970663AG2-429 GEN
Solar/Wind Harmer
8.405
970663AG2-429 GEN
Solar/Wind Harmer
1.368
203846AF2-130 C
Solar/Wind Harmer
0.468
971055AG2-654 GEN
Solar/Wind Harmer
0.806
20083226HNSMLK 5
Adder
3.724
970677AG2-438 GEN
Solar/Wind Harmer
0.484
966771AG1-548 GEN
Solar/Wind Harmer
6.9
966771AG1-548 GEN
Solar/Wind Harmer
1.337
20083926HOMER C3
Adder
33.598
20083826HOMER C2
Adder
31.737
203804AE2-113_GEN
Solar/Wind Harmer
2.166
20083726HOMER C1
Adder
18.155
23503001MHNG-T155
50/50
0.014
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.884
238219AF1-167 C
Solar/Wind Harmer
1.595
971185AH1-051 GEN
Solar/Wind Harmer
1.804
971355AH1-158 GEN
Solar/Wind Harmer
2.097
203856AF2-165 C
Solar/Wind Harmer
0.865
970647AG2-420 GEN
Solar/Wind Harmer
1.42
945751AF1-240 GEN
Solar/Wind Harmer
1.028
959441AF2-235 GEN
Solar/Wind Harmer
0.196
20082926HNSMLK 2
Adder
3.724
20083126HNSMLK 4
Adder
3.724
957161AF2-010 GEN
Solar/Wind Harmer
3.784
203830AF1-094 GEN
Solar/Wind Harmer
0.293
971703AH1-357 GEN
Solar/Wind Harmer
0.874
971707AH1-359 GEN
Solar/Wind Harmer
0.874
20060826PINEY #1
50/50
0.062
238183AE2-316 GEN
Solar/Wind Harmer
3.802
971183AH1-050 GEN
Solar/Wind Harmer
3.006
970647AG2-420 GEN
Solar/Wind Harmer
0.165
20082826HNSMLK 1
Adder
3.724
20083026HNSMLK 3
Adder
3.724
203860AG1-193 C
Solar/Wind Harmer
0.191
970267AG2-176 GEN
Solar/Wind Harmer
7.646
961971AG1-040 GEN
Solar/Wind Harmer
0.276
970713AG2-456 GEN
Solar/Wind Harmer
3.496
971705AH1-358 GEN
Solar/Wind Harmer
1.016
971709AH1-360 GEN
Solar/Wind Harmer
1.016
203954AE2-126 C
Solar/Wind Harmer
0.262
23513401AL&D6
50/50
0.014
946381AF1-302 GEN
Solar/Wind Harmer
1.902
203848AF2-166 C
Solar/Wind Harmer
1.638
238217AF1-153 C O1
Solar/Wind Harmer
0.357
203979AG1-198 GEN
Solar/Wind Harmer
0.176
971933AH1-491 GEN
Solar/Wind Harmer
0.967
203980AG1-197 GEN
Solar/Wind Harmer
0.211
972075AH1-587 GEN
Solar/Wind Harmer
8.927
972077AH1-588 GEN
Solar/Wind Harmer
10.489
972079AH1-589 GEN
Solar/Wind Harmer
8.639
970715AG2-457 GEN
Solar/Wind Harmer
3.496
G-007ALTFEXP_G-007A->PJM
CMTX
0.886
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.119
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.254
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.505
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.076
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.429
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.612
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.81 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:274.2
MW Contribution:1.24
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.091
203932AE1-123
50/50
2.894
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.2
971185AH1-051 GEN
Solar/Wind Harmer
2.83
971355AH1-158 GEN
Solar/Wind Harmer
3.29
203856AF2-165 C
Solar/Wind Harmer
1.369
970647AG2-420 GEN
Solar/Wind Harmer
2.244
959441AF2-235 GEN
Solar/Wind Harmer
0.324
945751AF1-240 GEN
Solar/Wind Harmer
1.625
957161AF2-010 GEN
Solar/Wind Harmer
6.952
203830AF1-094 GEN
Solar/Wind Harmer
0.542
20082926HNSMLK 2
Adder
4.978
20083126HNSMLK 4
Adder
4.978
962511AG1-100 GEN
Solar/Wind Harmer
0.497
203962AF1-287 GEN
Solar/Wind Harmer
1.635
20084926LAKVU GN
Adder
0.136
203948AG1-140 C
Solar/Wind Harmer
0.199
20120126WRREN CT
Adder
4.458
971703AH1-357 GEN
Solar/Wind Harmer
1.241
971707AH1-359 GEN
Solar/Wind Harmer
1.241
970899AG2-561 GEN
Solar/Wind Harmer
1.165
203818AF1-086 GEN
Solar/Wind Harmer
1.443
960051AF2-296 GEN
Solar/Wind Harmer
1.122
203854AF2-039 C
Solar/Wind Harmer
0.227
20334926Z1-069 C
Solar/Wind Harmer
1.136
238202AE2-262_GEN
Solar/Wind Harmer
1.323
971627AH1-313 GEN
Solar/Wind Harmer
5.187
965131AG1-378 GEN
Solar/Wind Harmer
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.103
971541AH1-268 GEN
Solar/Wind Harmer
1.517
203848AF2-166 C
Solar/Wind Harmer
2.55
946381AF1-302 GEN
Solar/Wind Harmer
1.976
203979AG1-198 GEN
Solar/Wind Harmer
0.325
971933AH1-491 GEN
Solar/Wind Harmer
1.789
203980AG1-197 GEN
Solar/Wind Harmer
0.385
971931AH1-490 GEN
Solar/Wind Harmer
1.642
238217AF1-153 C O1
Solar/Wind Harmer
0.482
203947AF1-006 C
Solar/Wind Harmer
0.443
203963AG1-253 GEN
Solar/Wind Harmer
0.304
970305AG2-200 GEN
Solar/Wind Harmer
1.41
972075AH1-587 GEN
Solar/Wind Harmer
12.421
972077AH1-588 GEN
Solar/Wind Harmer
14.891
972079AH1-589 GEN
Solar/Wind Harmer
12.265
970715AG2-457 GEN
Solar/Wind Harmer
4.964
203853AF1-134 C O1
Solar/Wind Harmer
0.339
203952AE2-129 C
Solar/Wind Harmer
0.298
203946AE2-131 C
Solar/Wind Harmer
0.298
962411AG1-090 GEN
Solar/Wind Harmer
4.676
216419AE2-001 C
Solar/Wind Harmer
0.91
20398826ARMNA MT
Solar/Wind Harmer
1.057
20060826PINEY #1
50/50
0.084
20066226SCRUB GR
50/50
0.589
970663AG2-429 GEN
Solar/Wind Harmer
10.771
970663AG2-429 GEN
Solar/Wind Harmer
1.753
203846AF2-130 C
Solar/Wind Harmer
0.728
970677AG2-438 GEN
Solar/Wind Harmer
0.894
966771AG1-548 GEN
Solar/Wind Harmer
12.893
966771AG1-548 GEN
Solar/Wind Harmer
2.499
20083226HNSMLK 5
Adder
4.978
20084926LAKVU GN
Adder
0.153
203804AE2-113_GEN
Solar/Wind Harmer
3.011
940863AE2-074 GEN
Solar/Wind Harmer
1.003
203855AF2-088 C
Solar/Wind Harmer
0.109
20083926HOMER C3
Adder
39.517
20083826HOMER C2
Adder
37.329
965121AG1-377 GEN
Solar/Wind Harmer
0.985
20060826PINEY #1
50/50
0.095
971183AH1-050 GEN
Solar/Wind Harmer
4.716
970647AG2-420 GEN
Solar/Wind Harmer
0.261
203860AG1-193 C
Solar/Wind Harmer
0.304
238183AE2-316 GEN
Solar/Wind Harmer
3.949
970267AG2-176 GEN
Solar/Wind Harmer
13.094
20082826HNSMLK 1
Adder
4.978
20083026HNSMLK 3
Adder
4.978
961971AG1-040 GEN
Solar/Wind Harmer
0.509
203813AE2-344_GEN
Solar/Wind Harmer
9.519
20084926LAKVU GN
Adder
0.136
203835AF1-098 GEN
Solar/Wind Harmer
1.864
970713AG2-456 GEN
Solar/Wind Harmer
4.964
971705AH1-358 GEN
Solar/Wind Harmer
1.443
971709AH1-360 GEN
Solar/Wind Harmer
1.443
203954AE2-126 C
Solar/Wind Harmer
0.365
20072226SHAWVL 2
Adder
7.727
20091326SHAW-D
Adder
0.366
972169AH1-667 GEN
Solar/Wind Harmer
1.001
238206AE2-263_GEN
Solar/Wind Harmer
1.233
20326126BLOSSBCT
Adder
1.058
20094526CT_V3-030
Solar/Wind Harmer
0.326
20335026MILZ1-092
Adder
1.038
944411AF1-106 GEN
Solar/Wind Harmer
0.956
238215AE2-248 C
Solar/Wind Harmer
0.711
959471AF2-238 GEN
Solar/Wind Harmer
0.264
970337AG2-221 GEN
Solar/Wind Harmer
0.875
971279AH1-102 GEN
Solar/Wind Harmer
3.564
20090526Q36
Solar/Wind Harmer
0.686
203993AD2-133_GEN1
Solar/Wind Harmer
0.686
970555AG2-356 GEN
Solar/Wind Harmer
0.875
20083726HOMER C1
Adder
24.202
G-007ALTFEXP_G-007A->PJM
CMTX
1.526
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.168
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.818
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.264
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.836
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.81 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:274.2
MW Contribution:1.24
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.091
203932AE1-123
50/50
2.894
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.2
971185AH1-051 GEN
Solar/Wind Harmer
2.83
971355AH1-158 GEN
Solar/Wind Harmer
3.29
203856AF2-165 C
Solar/Wind Harmer
1.369
970647AG2-420 GEN
Solar/Wind Harmer
2.244
959441AF2-235 GEN
Solar/Wind Harmer
0.324
945751AF1-240 GEN
Solar/Wind Harmer
1.625
957161AF2-010 GEN
Solar/Wind Harmer
6.952
203830AF1-094 GEN
Solar/Wind Harmer
0.542
20082926HNSMLK 2
Adder
4.978
20083126HNSMLK 4
Adder
4.978
962511AG1-100 GEN
Solar/Wind Harmer
0.497
203962AF1-287 GEN
Solar/Wind Harmer
1.635
20084926LAKVU GN
Adder
0.136
203948AG1-140 C
Solar/Wind Harmer
0.199
20120126WRREN CT
Adder
4.458
971703AH1-357 GEN
Solar/Wind Harmer
1.241
971707AH1-359 GEN
Solar/Wind Harmer
1.241
970899AG2-561 GEN
Solar/Wind Harmer
1.165
203818AF1-086 GEN
Solar/Wind Harmer
1.443
960051AF2-296 GEN
Solar/Wind Harmer
1.122
203854AF2-039 C
Solar/Wind Harmer
0.227
20334926Z1-069 C
Solar/Wind Harmer
1.136
238202AE2-262_GEN
Solar/Wind Harmer
1.323
971627AH1-313 GEN
Solar/Wind Harmer
5.187
965131AG1-378 GEN
Solar/Wind Harmer
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.103
971541AH1-268 GEN
Solar/Wind Harmer
1.517
203848AF2-166 C
Solar/Wind Harmer
2.55
946381AF1-302 GEN
Solar/Wind Harmer
1.976
203979AG1-198 GEN
Solar/Wind Harmer
0.325
971933AH1-491 GEN
Solar/Wind Harmer
1.789
203980AG1-197 GEN
Solar/Wind Harmer
0.385
971931AH1-490 GEN
Solar/Wind Harmer
1.642
238217AF1-153 C O1
Solar/Wind Harmer
0.482
203947AF1-006 C
Solar/Wind Harmer
0.443
203963AG1-253 GEN
Solar/Wind Harmer
0.304
970305AG2-200 GEN
Solar/Wind Harmer
1.41
972075AH1-587 GEN
Solar/Wind Harmer
12.421
972077AH1-588 GEN
Solar/Wind Harmer
14.891
972079AH1-589 GEN
Solar/Wind Harmer
12.265
970715AG2-457 GEN
Solar/Wind Harmer
4.964
203853AF1-134 C O1
Solar/Wind Harmer
0.339
203952AE2-129 C
Solar/Wind Harmer
0.298
203946AE2-131 C
Solar/Wind Harmer
0.298
962411AG1-090 GEN
Solar/Wind Harmer
4.676
216419AE2-001 C
Solar/Wind Harmer
0.91
20398826ARMNA MT
Solar/Wind Harmer
1.057
20060826PINEY #1
50/50
0.095
971183AH1-050 GEN
Solar/Wind Harmer
4.716
970647AG2-420 GEN
Solar/Wind Harmer
0.261
203860AG1-193 C
Solar/Wind Harmer
0.304
238183AE2-316 GEN
Solar/Wind Harmer
3.949
970267AG2-176 GEN
Solar/Wind Harmer
13.094
20082826HNSMLK 1
Adder
4.978
20083026HNSMLK 3
Adder
4.978
961971AG1-040 GEN
Solar/Wind Harmer
0.509
203813AE2-344_GEN
Solar/Wind Harmer
9.519
20084926LAKVU GN
Adder
0.136
203835AF1-098 GEN
Solar/Wind Harmer
1.864
970713AG2-456 GEN
Solar/Wind Harmer
4.964
971705AH1-358 GEN
Solar/Wind Harmer
1.443
971709AH1-360 GEN
Solar/Wind Harmer
1.443
203954AE2-126 C
Solar/Wind Harmer
0.365
20072226SHAWVL 2
Adder
7.727
20091326SHAW-D
Adder
0.366
972169AH1-667 GEN
Solar/Wind Harmer
1.001
238206AE2-263_GEN
Solar/Wind Harmer
1.233
20326126BLOSSBCT
Adder
1.058
20094526CT_V3-030
Solar/Wind Harmer
0.326
20335026MILZ1-092
Adder
1.038
944411AF1-106 GEN
Solar/Wind Harmer
0.956
238215AE2-248 C
Solar/Wind Harmer
0.711
959471AF2-238 GEN
Solar/Wind Harmer
0.264
970337AG2-221 GEN
Solar/Wind Harmer
0.875
971279AH1-102 GEN
Solar/Wind Harmer
3.564
20060826PINEY #1
50/50
0.084
20066226SCRUB GR
50/50
0.589
970663AG2-429 GEN
Solar/Wind Harmer
10.771
970663AG2-429 GEN
Solar/Wind Harmer
1.753
203846AF2-130 C
Solar/Wind Harmer
0.728
970677AG2-438 GEN
Solar/Wind Harmer
0.894
966771AG1-548 GEN
Solar/Wind Harmer
12.893
966771AG1-548 GEN
Solar/Wind Harmer
2.499
20083226HNSMLK 5
Adder
4.978
20084926LAKVU GN
Adder
0.153
203804AE2-113_GEN
Solar/Wind Harmer
3.011
940863AE2-074 GEN
Solar/Wind Harmer
1.003
203855AF2-088 C
Solar/Wind Harmer
0.109
20083926HOMER C3
Adder
39.517
20083826HOMER C2
Adder
37.329
965121AG1-377 GEN
Solar/Wind Harmer
0.985
20090526Q36
Solar/Wind Harmer
0.686
203993AD2-133_GEN1
Solar/Wind Harmer
0.686
970555AG2-356 GEN
Solar/Wind Harmer
0.875
20083726HOMER C1
Adder
24.202
G-007ALTFEXP_G-007A->PJM
CMTX
1.526
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.168
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.818
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.264
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.836
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.54 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:252.56
MW Contribution:1.28
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.089
971183AH1-050 GEN
Solar/Wind Harmer
4.203
970647AG2-420 GEN
Solar/Wind Harmer
0.229
238183AE2-316 GEN
Solar/Wind Harmer
3.857
203860AG1-193 C
Solar/Wind Harmer
0.255
20082826HNSMLK 1
Adder
4.459
20083026HNSMLK 3
Adder
4.459
970267AG2-176 GEN
Solar/Wind Harmer
9.825
970713AG2-456 GEN
Solar/Wind Harmer
5.108
971705AH1-358 GEN
Solar/Wind Harmer
1.485
971709AH1-360 GEN
Solar/Wind Harmer
1.485
961971AG1-040 GEN
Solar/Wind Harmer
0.356
203954AE2-126 C
Solar/Wind Harmer
0.331
203813AE2-344_GEN
Solar/Wind Harmer
6.3
203835AF1-098 GEN
Solar/Wind Harmer
1.254
20326126BLOSSBCT
Adder
1.156
20072226SHAWVL 2
Adder
6.903
20335026MILZ1-092
Adder
1.136
944411AF1-106 GEN
Solar/Wind Harmer
1.047
20084926LAKVU GN
Adder
0.086
20091326SHAW-D
Adder
0.32
972169AH1-667 GEN
Solar/Wind Harmer
0.877
959471AF2-238 GEN
Solar/Wind Harmer
0.288
970337AG2-221 GEN
Solar/Wind Harmer
0.954
238206AE2-263_GEN
Solar/Wind Harmer
1.095
970511AG2-327 GEN
Solar/Wind Harmer
0.46
20060826PINEY #1
50/50
0.079
20066226SCRUB GR
50/50
0.515
970663AG2-429 GEN
Solar/Wind Harmer
10.687
970663AG2-429 GEN
Solar/Wind Harmer
1.74
203846AF2-130 C
Solar/Wind Harmer
0.67
20083926HOMER C3
Adder
57.387
20083826HOMER C2
Adder
54.209
20083226HNSMLK 5
Adder
4.459
970677AG2-438 GEN
Solar/Wind Harmer
0.655
966771AG1-548 GEN
Solar/Wind Harmer
9.318
966771AG1-548 GEN
Solar/Wind Harmer
1.806
203804AE2-113_GEN
Solar/Wind Harmer
2.99
940863AE2-074 GEN
Solar/Wind Harmer
1.074
20084926LAKVU GN
Adder
0.096
203855AF2-088 C
Solar/Wind Harmer
0.096
970555AG2-356 GEN
Solar/Wind Harmer
0.954
20083726HOMER C1
Adder
4.528
203848AF2-166 C
Solar/Wind Harmer
2.345
946381AF1-302 GEN
Solar/Wind Harmer
1.93
238217AF1-153 C O1
Solar/Wind Harmer
0.452
203979AG1-198 GEN
Solar/Wind Harmer
0.238
971933AH1-491 GEN
Solar/Wind Harmer
1.309
972077AH1-588 GEN
Solar/Wind Harmer
15.325
972079AH1-589 GEN
Solar/Wind Harmer
12.622
970715AG2-457 GEN
Solar/Wind Harmer
5.108
972075AH1-587 GEN
Solar/Wind Harmer
12.541
203980AG1-197 GEN
Solar/Wind Harmer
0.272
970305AG2-200 GEN
Solar/Wind Harmer
1.135
971931AH1-490 GEN
Solar/Wind Harmer
1.091
20398826ARMNA MT
Solar/Wind Harmer
1.178
203963AG1-253 GEN
Solar/Wind Harmer
0.2
203947AF1-006 C
Solar/Wind Harmer
0.274
203853AF1-134 C O1
Solar/Wind Harmer
0.283
203859AF2-294 C
Solar/Wind Harmer
0.788
970313AG2-206 GEN
Solar/Wind Harmer
2.207
20060826PINEY #1
50/50
0.086
203932AE1-123
50/50
2.739
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
2.522
971355AH1-158 GEN
Solar/Wind Harmer
2.932
203856AF2-165 C
Solar/Wind Harmer
1.208
970647AG2-420 GEN
Solar/Wind Harmer
1.968
945751AF1-240 GEN
Solar/Wind Harmer
1.472
959441AF2-235 GEN
Solar/Wind Harmer
0.273
20082926HNSMLK 2
Adder
4.459
20083126HNSMLK 4
Adder
4.459
957161AF2-010 GEN
Solar/Wind Harmer
5.131
203830AF1-094 GEN
Solar/Wind Harmer
0.397
971703AH1-357 GEN
Solar/Wind Harmer
1.277
971707AH1-359 GEN
Solar/Wind Harmer
1.277
20334926Z1-069 C
Solar/Wind Harmer
1.242
20120126WRREN CT
Adder
3.588
962511AG1-100 GEN
Solar/Wind Harmer
0.33
203962AF1-287 GEN
Solar/Wind Harmer
1.087
203948AG1-140 C
Solar/Wind Harmer
0.131
944411AF1-106 GEN
Solar/Wind Harmer
0.113
20084926LAKVU GN
Adder
0.086
203854AF2-039 C
Solar/Wind Harmer
0.199
960051AF2-296 GEN
Solar/Wind Harmer
0.935
970335AG2-220 GEN
Solar/Wind Harmer
1.431
971127AH1-005 GEN
Solar/Wind Harmer
0.923
238202AE2-262_GEN
Solar/Wind Harmer
1.175
971627AH1-313 GEN
Solar/Wind Harmer
4.606
970899AG2-561 GEN
Solar/Wind Harmer
0.91
203818AF1-086 GEN
Solar/Wind Harmer
1.158
G-007ALTFEXP_G-007A->PJM
CMTX
0.5
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.113
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.358
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.498
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.325
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.463
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.54 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:252.56
MW Contribution:1.28
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.089
971183AH1-050 GEN
Solar/Wind Harmer
4.203
970647AG2-420 GEN
Solar/Wind Harmer
0.229
238183AE2-316 GEN
Solar/Wind Harmer
3.857
203860AG1-193 C
Solar/Wind Harmer
0.255
20082826HNSMLK 1
Adder
4.459
20083026HNSMLK 3
Adder
4.459
970267AG2-176 GEN
Solar/Wind Harmer
9.825
970713AG2-456 GEN
Solar/Wind Harmer
5.108
971705AH1-358 GEN
Solar/Wind Harmer
1.485
971709AH1-360 GEN
Solar/Wind Harmer
1.485
961971AG1-040 GEN
Solar/Wind Harmer
0.356
203954AE2-126 C
Solar/Wind Harmer
0.331
203813AE2-344_GEN
Solar/Wind Harmer
6.3
203835AF1-098 GEN
Solar/Wind Harmer
1.254
20326126BLOSSBCT
Adder
1.156
20072226SHAWVL 2
Adder
6.903
20335026MILZ1-092
Adder
1.136
944411AF1-106 GEN
Solar/Wind Harmer
1.047
20084926LAKVU GN
Adder
0.086
20091326SHAW-D
Adder
0.32
972169AH1-667 GEN
Solar/Wind Harmer
0.877
959471AF2-238 GEN
Solar/Wind Harmer
0.288
970337AG2-221 GEN
Solar/Wind Harmer
0.954
238206AE2-263_GEN
Solar/Wind Harmer
1.095
970511AG2-327 GEN
Solar/Wind Harmer
0.46
20060826PINEY #1
50/50
0.079
20066226SCRUB GR
50/50
0.515
970663AG2-429 GEN
Solar/Wind Harmer
10.687
970663AG2-429 GEN
Solar/Wind Harmer
1.74
203846AF2-130 C
Solar/Wind Harmer
0.67
20083926HOMER C3
Adder
57.387
20083826HOMER C2
Adder
54.209
20083226HNSMLK 5
Adder
4.459
970677AG2-438 GEN
Solar/Wind Harmer
0.655
966771AG1-548 GEN
Solar/Wind Harmer
9.318
966771AG1-548 GEN
Solar/Wind Harmer
1.806
203804AE2-113_GEN
Solar/Wind Harmer
2.99
940863AE2-074 GEN
Solar/Wind Harmer
1.074
20084926LAKVU GN
Adder
0.096
203855AF2-088 C
Solar/Wind Harmer
0.096
970555AG2-356 GEN
Solar/Wind Harmer
0.954
20083726HOMER C1
Adder
4.528
203848AF2-166 C
Solar/Wind Harmer
2.345
946381AF1-302 GEN
Solar/Wind Harmer
1.93
238217AF1-153 C O1
Solar/Wind Harmer
0.452
203979AG1-198 GEN
Solar/Wind Harmer
0.238
971933AH1-491 GEN
Solar/Wind Harmer
1.309
972077AH1-588 GEN
Solar/Wind Harmer
15.325
972079AH1-589 GEN
Solar/Wind Harmer
12.622
970715AG2-457 GEN
Solar/Wind Harmer
5.108
972075AH1-587 GEN
Solar/Wind Harmer
12.541
203980AG1-197 GEN
Solar/Wind Harmer
0.272
970305AG2-200 GEN
Solar/Wind Harmer
1.135
971931AH1-490 GEN
Solar/Wind Harmer
1.091
20398826ARMNA MT
Solar/Wind Harmer
1.178
203963AG1-253 GEN
Solar/Wind Harmer
0.2
203947AF1-006 C
Solar/Wind Harmer
0.274
203853AF1-134 C O1
Solar/Wind Harmer
0.283
203859AF2-294 C
Solar/Wind Harmer
0.788
970313AG2-206 GEN
Solar/Wind Harmer
2.207
20060826PINEY #1
50/50
0.086
203932AE1-123
50/50
2.739
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
2.522
971355AH1-158 GEN
Solar/Wind Harmer
2.932
203856AF2-165 C
Solar/Wind Harmer
1.208
970647AG2-420 GEN
Solar/Wind Harmer
1.968
945751AF1-240 GEN
Solar/Wind Harmer
1.472
959441AF2-235 GEN
Solar/Wind Harmer
0.273
20082926HNSMLK 2
Adder
4.459
20083126HNSMLK 4
Adder
4.459
957161AF2-010 GEN
Solar/Wind Harmer
5.131
203830AF1-094 GEN
Solar/Wind Harmer
0.397
971703AH1-357 GEN
Solar/Wind Harmer
1.277
971707AH1-359 GEN
Solar/Wind Harmer
1.277
20334926Z1-069 C
Solar/Wind Harmer
1.242
20120126WRREN CT
Adder
3.588
962511AG1-100 GEN
Solar/Wind Harmer
0.33
203962AF1-287 GEN
Solar/Wind Harmer
1.087
203948AG1-140 C
Solar/Wind Harmer
0.131
944411AF1-106 GEN
Solar/Wind Harmer
0.113
20084926LAKVU GN
Adder
0.086
203854AF2-039 C
Solar/Wind Harmer
0.199
960051AF2-296 GEN
Solar/Wind Harmer
0.935
970335AG2-220 GEN
Solar/Wind Harmer
1.431
971127AH1-005 GEN
Solar/Wind Harmer
0.923
238202AE2-262_GEN
Solar/Wind Harmer
1.175
971627AH1-313 GEN
Solar/Wind Harmer
4.606
970899AG2-561 GEN
Solar/Wind Harmer
0.91
203818AF1-086 GEN
Solar/Wind Harmer
1.158
G-007ALTFEXP_G-007A->PJM
CMTX
0.5
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.113
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.358
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.498
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.325
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.463
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.08 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:251.67
MW Contribution:1.28
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.079
20066226SCRUB GR
50/50
0.516
970663AG2-429 GEN
Solar/Wind Harmer
10.696
970663AG2-429 GEN
Solar/Wind Harmer
1.741
203846AF2-130 C
Solar/Wind Harmer
0.671
20083926HOMER C3
Adder
57.493
20083826HOMER C2
Adder
54.308
20083226HNSMLK 5
Adder
4.465
970677AG2-438 GEN
Solar/Wind Harmer
0.656
966771AG1-548 GEN
Solar/Wind Harmer
9.337
966771AG1-548 GEN
Solar/Wind Harmer
1.81
203804AE2-113_GEN
Solar/Wind Harmer
3.008
940863AE2-074 GEN
Solar/Wind Harmer
1.079
203855AF2-088 C
Solar/Wind Harmer
0.097
20084926LAKVU GN
Adder
0.097
970555AG2-356 GEN
Solar/Wind Harmer
0.959
20083726HOMER C1
Adder
4.54
20060826PINEY #1
50/50
0.09
971183AH1-050 GEN
Solar/Wind Harmer
4.208
970647AG2-420 GEN
Solar/Wind Harmer
0.229
238183AE2-316 GEN
Solar/Wind Harmer
3.872
203860AG1-193 C
Solar/Wind Harmer
0.255
20082826HNSMLK 1
Adder
4.465
20083026HNSMLK 3
Adder
4.465
970267AG2-176 GEN
Solar/Wind Harmer
9.843
970713AG2-456 GEN
Solar/Wind Harmer
5.13
971705AH1-358 GEN
Solar/Wind Harmer
1.491
971709AH1-360 GEN
Solar/Wind Harmer
1.491
961971AG1-040 GEN
Solar/Wind Harmer
0.357
203954AE2-126 C
Solar/Wind Harmer
0.334
203813AE2-344_GEN
Solar/Wind Harmer
6.314
203835AF1-098 GEN
Solar/Wind Harmer
1.258
20072226SHAWVL 2
Adder
6.998
20326126BLOSSBCT
Adder
1.162
20335026MILZ1-092
Adder
1.141
944411AF1-106 GEN
Solar/Wind Harmer
1.052
20091326SHAW-D
Adder
0.325
972169AH1-667 GEN
Solar/Wind Harmer
0.89
20084926LAKVU GN
Adder
0.086
959471AF2-238 GEN
Solar/Wind Harmer
0.29
970337AG2-221 GEN
Solar/Wind Harmer
0.959
238206AE2-263_GEN
Solar/Wind Harmer
1.112
970511AG2-327 GEN
Solar/Wind Harmer
0.462
20060826PINEY #1
50/50
0.086
203932AE1-123
50/50
2.742
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.168
971185AH1-051 GEN
Solar/Wind Harmer
2.525
971355AH1-158 GEN
Solar/Wind Harmer
2.936
203856AF2-165 C
Solar/Wind Harmer
1.21
970647AG2-420 GEN
Solar/Wind Harmer
1.97
945751AF1-240 GEN
Solar/Wind Harmer
1.475
959441AF2-235 GEN
Solar/Wind Harmer
0.273
20082926HNSMLK 2
Adder
4.465
20083126HNSMLK 4
Adder
4.465
957161AF2-010 GEN
Solar/Wind Harmer
5.142
203830AF1-094 GEN
Solar/Wind Harmer
0.397
971703AH1-357 GEN
Solar/Wind Harmer
1.282
971707AH1-359 GEN
Solar/Wind Harmer
1.282
20334926Z1-069 C
Solar/Wind Harmer
1.247
20120126WRREN CT
Adder
3.605
962511AG1-100 GEN
Solar/Wind Harmer
0.33
203962AF1-287 GEN
Solar/Wind Harmer
1.09
203948AG1-140 C
Solar/Wind Harmer
0.131
944411AF1-106 GEN
Solar/Wind Harmer
0.113
203854AF2-039 C
Solar/Wind Harmer
0.202
20084926LAKVU GN
Adder
0.086
960051AF2-296 GEN
Solar/Wind Harmer
0.946
238202AE2-262_GEN
Solar/Wind Harmer
1.194
971627AH1-313 GEN
Solar/Wind Harmer
4.68
970335AG2-220 GEN
Solar/Wind Harmer
1.438
971127AH1-005 GEN
Solar/Wind Harmer
0.928
203818AF1-086 GEN
Solar/Wind Harmer
1.168
970899AG2-561 GEN
Solar/Wind Harmer
0.914
20335126GROZ1-110
Adder
1.012
20335226CANZ2-011
Adder
0.983
203848AF2-166 C
Solar/Wind Harmer
2.348
946381AF1-302 GEN
Solar/Wind Harmer
1.938
238217AF1-153 C O1
Solar/Wind Harmer
0.455
203979AG1-198 GEN
Solar/Wind Harmer
0.238
971933AH1-491 GEN
Solar/Wind Harmer
1.312
972077AH1-588 GEN
Solar/Wind Harmer
15.389
972079AH1-589 GEN
Solar/Wind Harmer
12.675
970715AG2-457 GEN
Solar/Wind Harmer
5.13
972075AH1-587 GEN
Solar/Wind Harmer
12.611
203980AG1-197 GEN
Solar/Wind Harmer
0.273
970305AG2-200 GEN
Solar/Wind Harmer
1.14
971931AH1-490 GEN
Solar/Wind Harmer
1.093
20398826ARMNA MT
Solar/Wind Harmer
1.183
203963AG1-253 GEN
Solar/Wind Harmer
0.2
203947AF1-006 C
Solar/Wind Harmer
0.275
203853AF1-134 C O1
Solar/Wind Harmer
0.286
203859AF2-294 C
Solar/Wind Harmer
0.792
970313AG2-206 GEN
Solar/Wind Harmer
2.218
G-007ALTFEXP_G-007A->PJM
CMTX
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.113
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.414
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.531
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.106
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.329
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.468
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.11 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:245.97
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.015
20060826PINEY #1
50/50
0.096
203932AE1-123
50/50
3.054
238219AF1-167 C
Solar/Wind Harmer
2.467
971185AH1-051 GEN
Solar/Wind Harmer
2.737
971355AH1-158 GEN
Solar/Wind Harmer
3.182
203856AF2-165 C
Solar/Wind Harmer
1.308
945751AF1-240 GEN
Solar/Wind Harmer
1.69
970647AG2-420 GEN
Solar/Wind Harmer
2.12
959441AF2-235 GEN
Solar/Wind Harmer
0.292
20082926HNSMLK 2
Adder
4.424
20083126HNSMLK 4
Adder
4.424
957161AF2-010 GEN
Solar/Wind Harmer
5.269
203830AF1-094 GEN
Solar/Wind Harmer
0.406
970899AG2-561 GEN
Solar/Wind Harmer
1.157
203818AF1-086 GEN
Solar/Wind Harmer
1.427
960051AF2-296 GEN
Solar/Wind Harmer
1.105
971703AH1-357 GEN
Solar/Wind Harmer
1.104
971707AH1-359 GEN
Solar/Wind Harmer
1.104
203854AF2-039 C
Solar/Wind Harmer
0.223
20120126WRREN CT
Adder
3.436
962511AG1-100 GEN
Solar/Wind Harmer
0.326
203962AF1-287 GEN
Solar/Wind Harmer
1.074
238202AE2-262_GEN
Solar/Wind Harmer
1.299
971627AH1-313 GEN
Solar/Wind Harmer
5.092
20334926Z1-069 C
Solar/Wind Harmer
1.043
965131AG1-378 GEN
Solar/Wind Harmer
0.96
203948AG1-140 C
Solar/Wind Harmer
0.125
20084926LAKVU GN
Adder
0.083
20060826PINEY #1
50/50
0.1
971183AH1-050 GEN
Solar/Wind Harmer
4.561
238183AE2-316 GEN
Solar/Wind Harmer
4.499
970647AG2-420 GEN
Solar/Wind Harmer
0.247
203860AG1-193 C
Solar/Wind Harmer
0.268
20082826HNSMLK 1
Adder
4.424
20083026HNSMLK 3
Adder
4.424
970267AG2-176 GEN
Solar/Wind Harmer
9.922
961971AG1-040 GEN
Solar/Wind Harmer
0.356
203954AE2-126 C
Solar/Wind Harmer
0.353
20072226SHAWVL 2
Adder
7.607
970713AG2-456 GEN
Solar/Wind Harmer
4.417
971705AH1-358 GEN
Solar/Wind Harmer
1.284
971709AH1-360 GEN
Solar/Wind Harmer
1.284
20091326SHAW-D
Adder
0.358
972169AH1-667 GEN
Solar/Wind Harmer
0.981
203813AE2-344_GEN
Solar/Wind Harmer
6.223
238206AE2-263_GEN
Solar/Wind Harmer
1.211
203848AF2-166 C
Solar/Wind Harmer
2.585
946381AF1-302 GEN
Solar/Wind Harmer
2.251
238217AF1-153 C O1
Solar/Wind Harmer
0.495
203979AG1-198 GEN
Solar/Wind Harmer
0.244
971933AH1-491 GEN
Solar/Wind Harmer
1.34
203980AG1-197 GEN
Solar/Wind Harmer
0.272
972075AH1-587 GEN
Solar/Wind Harmer
11.458
203853AF1-134 C O1
Solar/Wind Harmer
0.334
972077AH1-588 GEN
Solar/Wind Harmer
13.25
972079AH1-589 GEN
Solar/Wind Harmer
10.913
970715AG2-457 GEN
Solar/Wind Harmer
4.417
970305AG2-200 GEN
Solar/Wind Harmer
1.087
971931AH1-490 GEN
Solar/Wind Harmer
1.079
203952AE2-129 C
Solar/Wind Harmer
0.291
203946AE2-131 C
Solar/Wind Harmer
0.29
962411AG1-090 GEN
Solar/Wind Harmer
4.559
203947AF1-006 C
Solar/Wind Harmer
0.267
203963AG1-253 GEN
Solar/Wind Harmer
0.191
216419AE2-001 C
Solar/Wind Harmer
0.889
203835AF1-098 GEN
Solar/Wind Harmer
1.215
20084926LAKVU GN
Adder
0.083
20094526CT_V3-030
Solar/Wind Harmer
0.318
971865AH1-452 GEN
Solar/Wind Harmer
0.749
238215AE2-248 C
Solar/Wind Harmer
0.694
20326126BLOSSBCT
Adder
0.986
20060826PINEY #1
50/50
0.088
20066226SCRUB GR
50/50
0.554
970663AG2-429 GEN
Solar/Wind Harmer
12.229
970663AG2-429 GEN
Solar/Wind Harmer
1.991
203846AF2-130 C
Solar/Wind Harmer
0.738
20083226HNSMLK 5
Adder
4.424
970677AG2-438 GEN
Solar/Wind Harmer
0.67
966771AG1-548 GEN
Solar/Wind Harmer
9.498
966771AG1-548 GEN
Solar/Wind Harmer
1.841
203804AE2-113_GEN
Solar/Wind Harmer
2.797
20083926HOMER C3
Adder
40.376
20083826HOMER C2
Adder
38.14
203855AF2-088 C
Solar/Wind Harmer
0.107
940863AE2-074 GEN
Solar/Wind Harmer
0.914
965121AG1-377 GEN
Solar/Wind Harmer
0.96
20084926LAKVU GN
Adder
0.093
971055AG2-654 GEN
Solar/Wind Harmer
0.56
20083726HOMER C1
Adder
23.686
G-007ALTFEXP_G-007A->PJM
CMTX
1.066
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.149
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.208
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.184
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.096
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.571
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.815
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:202.22
MW Contribution:0.92
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.081
203932AE1-123
50/50
2.566
23503001MHNG-T155
50/50
0.011
238219AF1-167 C
Solar/Wind Harmer
2.04
971185AH1-051 GEN
Solar/Wind Harmer
2.265
971355AH1-158 GEN
Solar/Wind Harmer
2.634
203856AF2-165 C
Solar/Wind Harmer
1.083
945751AF1-240 GEN
Solar/Wind Harmer
1.429
970647AG2-420 GEN
Solar/Wind Harmer
1.749
959441AF2-235 GEN
Solar/Wind Harmer
0.242
20082926HNSMLK 2
Adder
3.367
20083126HNSMLK 4
Adder
3.367
238202AE2-262_GEN
Solar/Wind Harmer
1.443
971627AH1-313 GEN
Solar/Wind Harmer
5.656
957161AF2-010 GEN
Solar/Wind Harmer
4.331
203830AF1-094 GEN
Solar/Wind Harmer
0.334
203854AF2-039 C
Solar/Wind Harmer
0.221
960051AF2-296 GEN
Solar/Wind Harmer
1.035
203818AF1-086 GEN
Solar/Wind Harmer
1.278
970899AG2-561 GEN
Solar/Wind Harmer
0.996
203848AF2-166 C
Solar/Wind Harmer
2.16
946381AF1-302 GEN
Solar/Wind Harmer
1.807
238217AF1-153 C O1
Solar/Wind Harmer
0.448
216419AE2-001 C
Solar/Wind Harmer
1.117
203979AG1-198 GEN
Solar/Wind Harmer
0.2
971933AH1-491 GEN
Solar/Wind Harmer
1.101
203853AF1-134 C O1
Solar/Wind Harmer
0.313
972075AH1-587 GEN
Solar/Wind Harmer
9.934
203980AG1-197 GEN
Solar/Wind Harmer
0.218
970305AG2-200 GEN
Solar/Wind Harmer
0.929
972077AH1-588 GEN
Solar/Wind Harmer
11.093
972079AH1-589 GEN
Solar/Wind Harmer
9.136
970715AG2-457 GEN
Solar/Wind Harmer
3.698
203952AE2-129 C
Solar/Wind Harmer
0.277
203946AE2-131 C
Solar/Wind Harmer
0.276
962411AG1-090 GEN
Solar/Wind Harmer
4.342
971931AH1-490 GEN
Solar/Wind Harmer
0.868
20060826PINEY #1
50/50
0.074
20066226SCRUB GR
50/50
0.456
970663AG2-429 GEN
Solar/Wind Harmer
9.921
970663AG2-429 GEN
Solar/Wind Harmer
1.615
203846AF2-130 C
Solar/Wind Harmer
0.617
20083226HNSMLK 5
Adder
3.367
970677AG2-438 GEN
Solar/Wind Harmer
0.551
203855AF2-088 C
Solar/Wind Harmer
0.107
966771AG1-548 GEN
Solar/Wind Harmer
7.798
966771AG1-548 GEN
Solar/Wind Harmer
1.511
203804AE2-113_GEN
Solar/Wind Harmer
2.456
965121AG1-377 GEN
Solar/Wind Harmer
0.914
940863AE2-074 GEN
Solar/Wind Harmer
0.763
20083926HOMER C3
Adder
30.633
20083826HOMER C2
Adder
28.936
20083726HOMER C1
Adder
18.098
20120126WRREN CT
Adder
2.937
971703AH1-357 GEN
Solar/Wind Harmer
0.924
971707AH1-359 GEN
Solar/Wind Harmer
0.924
965131AG1-378 GEN
Solar/Wind Harmer
0.914
962511AG1-100 GEN
Solar/Wind Harmer
0.263
203962AF1-287 GEN
Solar/Wind Harmer
0.866
20060826PINEY #1
50/50
0.084
971183AH1-050 GEN
Solar/Wind Harmer
3.775
970647AG2-420 GEN
Solar/Wind Harmer
0.203
238183AE2-316 GEN
Solar/Wind Harmer
3.612
203860AG1-193 C
Solar/Wind Harmer
0.217
20082826HNSMLK 1
Adder
3.367
20083026HNSMLK 3
Adder
3.367
20072226SHAWVL 2
Adder
7.814
238206AE2-263_GEN
Solar/Wind Harmer
1.345
238215AE2-248 C
Solar/Wind Harmer
0.892
203954AE2-126 C
Solar/Wind Harmer
0.336
972169AH1-667 GEN
Solar/Wind Harmer
0.974
20091326SHAW-D
Adder
0.356
970267AG2-176 GEN
Solar/Wind Harmer
7.909
961971AG1-040 GEN
Solar/Wind Harmer
0.285
970713AG2-456 GEN
Solar/Wind Harmer
3.698
971705AH1-358 GEN
Solar/Wind Harmer
1.075
971709AH1-360 GEN
Solar/Wind Harmer
1.075
203813AE2-344_GEN
Solar/Wind Harmer
5.015
G-007ALTFEXP_G-007A->PJM
CMTX
0.505
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.109
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.476
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.119
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.371
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.531
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.95 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:193.82
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.086
203932AE1-123
50/50
2.744
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
2.185
971185AH1-051 GEN
Solar/Wind Harmer
2.435
971355AH1-158 GEN
Solar/Wind Harmer
2.832
203856AF2-165 C
Solar/Wind Harmer
1.164
945751AF1-240 GEN
Solar/Wind Harmer
1.51
970647AG2-420 GEN
Solar/Wind Harmer
1.882
959441AF2-235 GEN
Solar/Wind Harmer
0.259
20082926HNSMLK 2
Adder
3.769
20083126HNSMLK 4
Adder
3.769
957161AF2-010 GEN
Solar/Wind Harmer
4.627
203830AF1-094 GEN
Solar/Wind Harmer
0.356
970899AG2-561 GEN
Solar/Wind Harmer
1.015
203818AF1-086 GEN
Solar/Wind Harmer
1.246
960051AF2-296 GEN
Solar/Wind Harmer
0.961
971703AH1-357 GEN
Solar/Wind Harmer
0.944
971707AH1-359 GEN
Solar/Wind Harmer
0.944
203854AF2-039 C
Solar/Wind Harmer
0.193
20120126WRREN CT
Adder
2.961
962511AG1-100 GEN
Solar/Wind Harmer
0.283
203962AF1-287 GEN
Solar/Wind Harmer
0.931
238202AE2-262_GEN
Solar/Wind Harmer
1.12
971627AH1-313 GEN
Solar/Wind Harmer
4.392
20060826PINEY #1
50/50
0.09
971183AH1-050 GEN
Solar/Wind Harmer
4.059
970647AG2-420 GEN
Solar/Wind Harmer
0.219
238183AE2-316 GEN
Solar/Wind Harmer
3.832
203860AG1-193 C
Solar/Wind Harmer
0.235
20082826HNSMLK 1
Adder
3.769
20083026HNSMLK 3
Adder
3.769
970267AG2-176 GEN
Solar/Wind Harmer
8.609
961971AG1-040 GEN
Solar/Wind Harmer
0.308
203954AE2-126 C
Solar/Wind Harmer
0.305
20072226SHAWVL 2
Adder
6.572
970713AG2-456 GEN
Solar/Wind Harmer
3.776
971705AH1-358 GEN
Solar/Wind Harmer
1.098
971709AH1-360 GEN
Solar/Wind Harmer
1.098
20091326SHAW-D
Adder
0.31
972169AH1-667 GEN
Solar/Wind Harmer
0.848
203813AE2-344_GEN
Solar/Wind Harmer
5.392
238206AE2-263_GEN
Solar/Wind Harmer
1.044
203835AF1-098 GEN
Solar/Wind Harmer
1.051
203848AF2-166 C
Solar/Wind Harmer
2.313
946381AF1-302 GEN
Solar/Wind Harmer
1.918
238217AF1-153 C O1
Solar/Wind Harmer
0.433
203979AG1-198 GEN
Solar/Wind Harmer
0.214
971933AH1-491 GEN
Solar/Wind Harmer
1.176
203980AG1-197 GEN
Solar/Wind Harmer
0.236
972075AH1-587 GEN
Solar/Wind Harmer
9.826
203853AF1-134 C O1
Solar/Wind Harmer
0.29
972077AH1-588 GEN
Solar/Wind Harmer
11.329
972079AH1-589 GEN
Solar/Wind Harmer
9.331
970715AG2-457 GEN
Solar/Wind Harmer
3.776
970305AG2-200 GEN
Solar/Wind Harmer
0.937
971931AH1-490 GEN
Solar/Wind Harmer
0.935
20060826PINEY #1
50/50
0.079
20066226SCRUB GR
50/50
0.491
970663AG2-429 GEN
Solar/Wind Harmer
10.838
970663AG2-429 GEN
Solar/Wind Harmer
1.764
203846AF2-130 C
Solar/Wind Harmer
0.661
20083226HNSMLK 5
Adder
3.769
970677AG2-438 GEN
Solar/Wind Harmer
0.588
966771AG1-548 GEN
Solar/Wind Harmer
8.325
966771AG1-548 GEN
Solar/Wind Harmer
1.613
203804AE2-113_GEN
Solar/Wind Harmer
2.402
20083926HOMER C3
Adder
34.009
20083826HOMER C2
Adder
32.125
203855AF2-088 C
Solar/Wind Harmer
0.093
940863AE2-074 GEN
Solar/Wind Harmer
0.78
20083726HOMER C1
Adder
19.799
G-007ALTFEXP_G-007A->PJM
CMTX
0.787
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.123
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.509
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.242
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.146
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.454
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.647
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.89 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:321.31
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.096
203932AE1-123
50/50
3.05
20082926HNSMLK 2
50/50
5.567
20083126HNSMLK 4
50/50
5.567
238219AF1-167 C
Solar/Wind Harmer
2.105
971185AH1-051 GEN
Solar/Wind Harmer
2.982
971355AH1-158 GEN
Solar/Wind Harmer
3.468
203856AF2-165 C
Solar/Wind Harmer
1.443
970647AG2-420 GEN
Solar/Wind Harmer
2.365
959441AF2-235 GEN
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.714
957161AF2-010 GEN
Solar/Wind Harmer
7.328
203830AF1-094 GEN
Solar/Wind Harmer
0.571
962511AG1-100 GEN
Solar/Wind Harmer
0.523
203962AF1-287 GEN
Solar/Wind Harmer
1.723
20084926LAKVU GN
Adder
0.144
203948AG1-140 C
Solar/Wind Harmer
0.21
20120126WRREN CT
Adder
4.699
971703AH1-357 GEN
Solar/Wind Harmer
1.309
971707AH1-359 GEN
Solar/Wind Harmer
1.309
970899AG2-561 GEN
Solar/Wind Harmer
1.229
203818AF1-086 GEN
Solar/Wind Harmer
1.523
960051AF2-296 GEN
Solar/Wind Harmer
1.184
203854AF2-039 C
Solar/Wind Harmer
0.24
20334926Z1-069 C
Solar/Wind Harmer
1.199
238202AE2-262_GEN
Solar/Wind Harmer
1.396
971627AH1-313 GEN
Solar/Wind Harmer
5.472
965131AG1-378 GEN
Solar/Wind Harmer
1.039
944411AF1-106 GEN
Solar/Wind Harmer
0.109
971541AH1-268 GEN
Solar/Wind Harmer
1.602
970335AG2-220 GEN
Solar/Wind Harmer
1.388
971127AH1-005 GEN
Solar/Wind Harmer
0.896
20335126GROZ1-110
Adder
1.033
20335226CANZ2-011
Adder
1.004
20060826PINEY #1
50/50
0.088
20066226SCRUB GR
50/50
0.621
20083226HNSMLK 5
50/50
5.567
970663AG2-429 GEN
Solar/Wind Harmer
11.349
970663AG2-429 GEN
Solar/Wind Harmer
1.848
203846AF2-130 C
Solar/Wind Harmer
0.768
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
13.589
966771AG1-548 GEN
Solar/Wind Harmer
2.633
20084926LAKVU GN
Adder
0.162
203804AE2-113_GEN
Solar/Wind Harmer
3.175
940863AE2-074 GEN
Solar/Wind Harmer
1.058
203855AF2-088 C
Solar/Wind Harmer
0.115
20083926HOMER C3
Adder
41.707
20083826HOMER C2
Adder
39.397
965121AG1-377 GEN
Solar/Wind Harmer
1.039
20090526Q36
Solar/Wind Harmer
0.724
203993AD2-133_GEN1
Solar/Wind Harmer
0.724
970555AG2-356 GEN
Solar/Wind Harmer
0.924
20083726HOMER C1
Adder
25.611
20060826PINEY #1
50/50
0.1
20082826HNSMLK 1
50/50
5.567
20083026HNSMLK 3
50/50
5.567
971183AH1-050 GEN
Solar/Wind Harmer
4.971
970647AG2-420 GEN
Solar/Wind Harmer
0.275
203860AG1-193 C
Solar/Wind Harmer
0.32
238183AE2-316 GEN
Solar/Wind Harmer
4.159
970267AG2-176 GEN
Solar/Wind Harmer
13.8
961971AG1-040 GEN
Solar/Wind Harmer
0.536
203813AE2-344_GEN
Solar/Wind Harmer
10.032
20084926LAKVU GN
Adder
0.144
203835AF1-098 GEN
Solar/Wind Harmer
1.964
970713AG2-456 GEN
Solar/Wind Harmer
5.235
971705AH1-358 GEN
Solar/Wind Harmer
1.522
971709AH1-360 GEN
Solar/Wind Harmer
1.522
203954AE2-126 C
Solar/Wind Harmer
0.385
20072226SHAWVL 2
Adder
8.15
20091326SHAW-D
Adder
0.386
972169AH1-667 GEN
Solar/Wind Harmer
1.056
238206AE2-263_GEN
Solar/Wind Harmer
1.301
20326126BLOSSBCT
Adder
1.117
20094526CT_V3-030
Solar/Wind Harmer
0.344
20335026MILZ1-092
Adder
1.096
944411AF1-106 GEN
Solar/Wind Harmer
1.009
238215AE2-248 C
Solar/Wind Harmer
0.751
959471AF2-238 GEN
Solar/Wind Harmer
0.279
970337AG2-221 GEN
Solar/Wind Harmer
0.924
971279AH1-102 GEN
Solar/Wind Harmer
3.765
970511AG2-327 GEN
Solar/Wind Harmer
0.447
203848AF2-166 C
Solar/Wind Harmer
2.688
946381AF1-302 GEN
Solar/Wind Harmer
2.081
203979AG1-198 GEN
Solar/Wind Harmer
0.343
971933AH1-491 GEN
Solar/Wind Harmer
1.886
203980AG1-197 GEN
Solar/Wind Harmer
0.405
971931AH1-490 GEN
Solar/Wind Harmer
1.731
238217AF1-153 C O1
Solar/Wind Harmer
0.507
203947AF1-006 C
Solar/Wind Harmer
0.467
203963AG1-253 GEN
Solar/Wind Harmer
0.321
970305AG2-200 GEN
Solar/Wind Harmer
1.486
972075AH1-587 GEN
Solar/Wind Harmer
13.098
972077AH1-588 GEN
Solar/Wind Harmer
15.705
972079AH1-589 GEN
Solar/Wind Harmer
12.936
970715AG2-457 GEN
Solar/Wind Harmer
5.235
203853AF1-134 C O1
Solar/Wind Harmer
0.358
203952AE2-129 C
Solar/Wind Harmer
0.315
203946AE2-131 C
Solar/Wind Harmer
0.314
962411AG1-090 GEN
Solar/Wind Harmer
4.935
216419AE2-001 C
Solar/Wind Harmer
0.961
20398826ARMNA MT
Solar/Wind Harmer
1.117
203859AF2-294 C
Solar/Wind Harmer
0.767
970313AG2-206 GEN
Solar/Wind Harmer
2.143
G-007ALTFEXP_G-007A->PJM
CMTX
1.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.536
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.624
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.289
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.899
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.3
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.89 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:321.31
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.096
203932AE1-123
50/50
3.05
20082926HNSMLK 2
50/50
5.567
20083126HNSMLK 4
50/50
5.567
238219AF1-167 C
Solar/Wind Harmer
2.105
971185AH1-051 GEN
Solar/Wind Harmer
2.982
971355AH1-158 GEN
Solar/Wind Harmer
3.468
203856AF2-165 C
Solar/Wind Harmer
1.443
970647AG2-420 GEN
Solar/Wind Harmer
2.365
959441AF2-235 GEN
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.714
20060826PINEY #1
50/50
0.088
20066226SCRUB GR
50/50
0.621
20083226HNSMLK 5
50/50
5.567
970663AG2-429 GEN
Solar/Wind Harmer
11.349
970663AG2-429 GEN
Solar/Wind Harmer
1.848
203846AF2-130 C
Solar/Wind Harmer
0.768
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
13.589
966771AG1-548 GEN
Solar/Wind Harmer
2.633
20084926LAKVU GN
Adder
0.162
203804AE2-113_GEN
Solar/Wind Harmer
3.175
940863AE2-074 GEN
Solar/Wind Harmer
1.058
203855AF2-088 C
Solar/Wind Harmer
0.115
20083926HOMER C3
Adder
41.707
20083826HOMER C2
Adder
39.397
965121AG1-377 GEN
Solar/Wind Harmer
1.039
20090526Q36
Solar/Wind Harmer
0.724
203993AD2-133_GEN1
Solar/Wind Harmer
0.724
970555AG2-356 GEN
Solar/Wind Harmer
0.924
20083726HOMER C1
Adder
25.611
957161AF2-010 GEN
Solar/Wind Harmer
7.328
203830AF1-094 GEN
Solar/Wind Harmer
0.571
962511AG1-100 GEN
Solar/Wind Harmer
0.523
203962AF1-287 GEN
Solar/Wind Harmer
1.723
20084926LAKVU GN
Adder
0.144
203948AG1-140 C
Solar/Wind Harmer
0.21
20120126WRREN CT
Adder
4.699
971703AH1-357 GEN
Solar/Wind Harmer
1.309
971707AH1-359 GEN
Solar/Wind Harmer
1.309
970899AG2-561 GEN
Solar/Wind Harmer
1.229
203818AF1-086 GEN
Solar/Wind Harmer
1.523
960051AF2-296 GEN
Solar/Wind Harmer
1.184
203854AF2-039 C
Solar/Wind Harmer
0.24
20334926Z1-069 C
Solar/Wind Harmer
1.199
238202AE2-262_GEN
Solar/Wind Harmer
1.396
971627AH1-313 GEN
Solar/Wind Harmer
5.472
965131AG1-378 GEN
Solar/Wind Harmer
1.039
944411AF1-106 GEN
Solar/Wind Harmer
0.109
971541AH1-268 GEN
Solar/Wind Harmer
1.602
970335AG2-220 GEN
Solar/Wind Harmer
1.388
971127AH1-005 GEN
Solar/Wind Harmer
0.896
20335126GROZ1-110
Adder
1.033
20335226CANZ2-011
Adder
1.004
20060826PINEY #1
50/50
0.1
20082826HNSMLK 1
50/50
5.567
20083026HNSMLK 3
50/50
5.567
971183AH1-050 GEN
Solar/Wind Harmer
4.971
970647AG2-420 GEN
Solar/Wind Harmer
0.275
203860AG1-193 C
Solar/Wind Harmer
0.32
238183AE2-316 GEN
Solar/Wind Harmer
4.159
970267AG2-176 GEN
Solar/Wind Harmer
13.8
961971AG1-040 GEN
Solar/Wind Harmer
0.536
203813AE2-344_GEN
Solar/Wind Harmer
10.032
20084926LAKVU GN
Adder
0.144
203835AF1-098 GEN
Solar/Wind Harmer
1.964
970713AG2-456 GEN
Solar/Wind Harmer
5.235
971705AH1-358 GEN
Solar/Wind Harmer
1.522
971709AH1-360 GEN
Solar/Wind Harmer
1.522
203954AE2-126 C
Solar/Wind Harmer
0.385
20072226SHAWVL 2
Adder
8.15
20091326SHAW-D
Adder
0.386
972169AH1-667 GEN
Solar/Wind Harmer
1.056
238206AE2-263_GEN
Solar/Wind Harmer
1.301
20326126BLOSSBCT
Adder
1.117
20094526CT_V3-030
Solar/Wind Harmer
0.344
20335026MILZ1-092
Adder
1.096
944411AF1-106 GEN
Solar/Wind Harmer
1.009
238215AE2-248 C
Solar/Wind Harmer
0.751
959471AF2-238 GEN
Solar/Wind Harmer
0.279
970337AG2-221 GEN
Solar/Wind Harmer
0.924
971279AH1-102 GEN
Solar/Wind Harmer
3.765
970511AG2-327 GEN
Solar/Wind Harmer
0.447
203848AF2-166 C
Solar/Wind Harmer
2.688
946381AF1-302 GEN
Solar/Wind Harmer
2.081
203979AG1-198 GEN
Solar/Wind Harmer
0.343
971933AH1-491 GEN
Solar/Wind Harmer
1.886
203980AG1-197 GEN
Solar/Wind Harmer
0.405
971931AH1-490 GEN
Solar/Wind Harmer
1.731
238217AF1-153 C O1
Solar/Wind Harmer
0.507
203947AF1-006 C
Solar/Wind Harmer
0.467
203963AG1-253 GEN
Solar/Wind Harmer
0.321
970305AG2-200 GEN
Solar/Wind Harmer
1.486
972075AH1-587 GEN
Solar/Wind Harmer
13.098
972077AH1-588 GEN
Solar/Wind Harmer
15.705
972079AH1-589 GEN
Solar/Wind Harmer
12.936
970715AG2-457 GEN
Solar/Wind Harmer
5.235
203853AF1-134 C O1
Solar/Wind Harmer
0.358
203952AE2-129 C
Solar/Wind Harmer
0.315
203946AE2-131 C
Solar/Wind Harmer
0.314
962411AG1-090 GEN
Solar/Wind Harmer
4.935
216419AE2-001 C
Solar/Wind Harmer
0.961
20398826ARMNA MT
Solar/Wind Harmer
1.117
203859AF2-294 C
Solar/Wind Harmer
0.767
970313AG2-206 GEN
Solar/Wind Harmer
2.143
G-007ALTFEXP_G-007A->PJM
CMTX
1.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.536
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.624
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.289
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.899
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.3
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.92 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:294.6
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
203848AF2-166 C
Solar/Wind Harmer
2.471
946381AF1-302 GEN
Solar/Wind Harmer
2.038
238217AF1-153 C O1
Solar/Wind Harmer
0.478
203979AG1-198 GEN
Solar/Wind Harmer
0.251
20060826PINEY #1
50/50
0.084
20066226SCRUB GR
50/50
0.543
970663AG2-429 GEN
Solar/Wind Harmer
11.261
970663AG2-429 GEN
Solar/Wind Harmer
1.833
203846AF2-130 C
Solar/Wind Harmer
0.706
20083926HOMER C3
Adder
60.44
20083826HOMER C2
Adder
57.092
20083226HNSMLK 5
Adder
4.692
970677AG2-438 GEN
Solar/Wind Harmer
0.689
966771AG1-548 GEN
Solar/Wind Harmer
9.81
966771AG1-548 GEN
Solar/Wind Harmer
1.901
203804AE2-113_GEN
Solar/Wind Harmer
3.163
940863AE2-074 GEN
Solar/Wind Harmer
1.134
203855AF2-088 C
Solar/Wind Harmer
0.103
20084926LAKVU GN
Adder
0.101
970555AG2-356 GEN
Solar/Wind Harmer
1.009
965121AG1-377 GEN
Solar/Wind Harmer
0.879
20083726HOMER C1
Adder
4.774
20060826PINEY #1
50/50
0.091
203932AE1-123
50/50
2.888
238219AF1-167 C
Solar/Wind Harmer
2.071
971185AH1-051 GEN
Solar/Wind Harmer
2.657
971355AH1-158 GEN
Solar/Wind Harmer
3.089
203856AF2-165 C
Solar/Wind Harmer
1.273
970647AG2-420 GEN
Solar/Wind Harmer
2.073
945751AF1-240 GEN
Solar/Wind Harmer
1.553
959441AF2-235 GEN
Solar/Wind Harmer
0.287
20082926HNSMLK 2
Adder
4.692
20083126HNSMLK 4
Adder
4.692
957161AF2-010 GEN
Solar/Wind Harmer
5.403
203830AF1-094 GEN
Solar/Wind Harmer
0.417
971703AH1-357 GEN
Solar/Wind Harmer
1.348
971707AH1-359 GEN
Solar/Wind Harmer
1.348
20334926Z1-069 C
Solar/Wind Harmer
1.312
20120126WRREN CT
Adder
3.787
962511AG1-100 GEN
Solar/Wind Harmer
0.347
203962AF1-287 GEN
Solar/Wind Harmer
1.144
944411AF1-106 GEN
Solar/Wind Harmer
0.119
203948AG1-140 C
Solar/Wind Harmer
0.138
203854AF2-039 C
Solar/Wind Harmer
0.213
20084926LAKVU GN
Adder
0.09
960051AF2-296 GEN
Solar/Wind Harmer
0.997
238202AE2-262_GEN
Solar/Wind Harmer
1.257
971627AH1-313 GEN
Solar/Wind Harmer
4.927
970335AG2-220 GEN
Solar/Wind Harmer
1.514
971127AH1-005 GEN
Solar/Wind Harmer
0.977
970899AG2-561 GEN
Solar/Wind Harmer
0.964
203818AF1-086 GEN
Solar/Wind Harmer
1.232
20335126GROZ1-110
Adder
1.065
20335226CANZ2-011
Adder
1.035
965131AG1-378 GEN
Solar/Wind Harmer
0.879
20060826PINEY #1
50/50
0.094
971183AH1-050 GEN
Solar/Wind Harmer
4.428
970647AG2-420 GEN
Solar/Wind Harmer
0.241
238183AE2-316 GEN
Solar/Wind Harmer
4.072
203860AG1-193 C
Solar/Wind Harmer
0.268
20082826HNSMLK 1
Adder
4.692
20083026HNSMLK 3
Adder
4.692
970267AG2-176 GEN
Solar/Wind Harmer
10.339
970713AG2-456 GEN
Solar/Wind Harmer
5.393
971705AH1-358 GEN
Solar/Wind Harmer
1.568
971709AH1-360 GEN
Solar/Wind Harmer
1.568
961971AG1-040 GEN
Solar/Wind Harmer
0.375
203954AE2-126 C
Solar/Wind Harmer
0.352
203813AE2-344_GEN
Solar/Wind Harmer
6.627
203835AF1-098 GEN
Solar/Wind Harmer
1.321
20072226SHAWVL 2
Adder
7.366
20326126BLOSSBCT
Adder
1.223
20335026MILZ1-092
Adder
1.201
944411AF1-106 GEN
Solar/Wind Harmer
1.106
20091326SHAW-D
Adder
0.342
972169AH1-667 GEN
Solar/Wind Harmer
0.937
20084926LAKVU GN
Adder
0.09
959471AF2-238 GEN
Solar/Wind Harmer
0.305
970337AG2-221 GEN
Solar/Wind Harmer
1.009
238206AE2-263_GEN
Solar/Wind Harmer
1.171
970511AG2-327 GEN
Solar/Wind Harmer
0.486
971933AH1-491 GEN
Solar/Wind Harmer
1.378
972077AH1-588 GEN
Solar/Wind Harmer
16.178
972079AH1-589 GEN
Solar/Wind Harmer
13.325
970715AG2-457 GEN
Solar/Wind Harmer
5.393
972075AH1-587 GEN
Solar/Wind Harmer
13.26
203980AG1-197 GEN
Solar/Wind Harmer
0.287
970305AG2-200 GEN
Solar/Wind Harmer
1.198
971931AH1-490 GEN
Solar/Wind Harmer
1.147
20398826ARMNA MT
Solar/Wind Harmer
1.245
203963AG1-253 GEN
Solar/Wind Harmer
0.21
203947AF1-006 C
Solar/Wind Harmer
0.288
203853AF1-134 C O1
Solar/Wind Harmer
0.301
203859AF2-294 C
Solar/Wind Harmer
0.833
970313AG2-206 GEN
Solar/Wind Harmer
2.334
203952AE2-129 C
Solar/Wind Harmer
0.266
203946AE2-131 C
Solar/Wind Harmer
0.266
962411AG1-090 GEN
Solar/Wind Harmer
4.177
G-007ALTFEXP_G-007A->PJM
CMTX
0.586
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.121
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.069
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.117
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.363
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.517
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.63 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:291.14
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.083
20066226SCRUB GR
50/50
0.542
970663AG2-429 GEN
Solar/Wind Harmer
11.251
970663AG2-429 GEN
Solar/Wind Harmer
1.832
203846AF2-130 C
Solar/Wind Harmer
0.705
20083926HOMER C3
Adder
60.33
20083826HOMER C2
Adder
56.988
20083226HNSMLK 5
Adder
4.685
970677AG2-438 GEN
Solar/Wind Harmer
0.688
966771AG1-548 GEN
Solar/Wind Harmer
9.79
966771AG1-548 GEN
Solar/Wind Harmer
1.897
203804AE2-113_GEN
Solar/Wind Harmer
3.144
940863AE2-074 GEN
Solar/Wind Harmer
1.129
203855AF2-088 C
Solar/Wind Harmer
0.101
20084926LAKVU GN
Adder
0.101
970555AG2-356 GEN
Solar/Wind Harmer
1.004
20083726HOMER C1
Adder
4.762
20060826PINEY #1
50/50
0.091
203932AE1-123
50/50
2.885
238219AF1-167 C
Solar/Wind Harmer
2.069
971185AH1-051 GEN
Solar/Wind Harmer
2.654
971355AH1-158 GEN
Solar/Wind Harmer
3.085
203856AF2-165 C
Solar/Wind Harmer
1.271
970647AG2-420 GEN
Solar/Wind Harmer
2.07
945751AF1-240 GEN
Solar/Wind Harmer
1.551
959441AF2-235 GEN
Solar/Wind Harmer
0.287
20082926HNSMLK 2
Adder
4.685
20083126HNSMLK 4
Adder
4.685
957161AF2-010 GEN
Solar/Wind Harmer
5.392
203830AF1-094 GEN
Solar/Wind Harmer
0.417
971703AH1-357 GEN
Solar/Wind Harmer
1.343
971707AH1-359 GEN
Solar/Wind Harmer
1.343
20334926Z1-069 C
Solar/Wind Harmer
1.306
20120126WRREN CT
Adder
3.77
962511AG1-100 GEN
Solar/Wind Harmer
0.346
203962AF1-287 GEN
Solar/Wind Harmer
1.141
944411AF1-106 GEN
Solar/Wind Harmer
0.118
203948AG1-140 C
Solar/Wind Harmer
0.137
203854AF2-039 C
Solar/Wind Harmer
0.21
20084926LAKVU GN
Adder
0.09
960051AF2-296 GEN
Solar/Wind Harmer
0.985
970335AG2-220 GEN
Solar/Wind Harmer
1.506
971127AH1-005 GEN
Solar/Wind Harmer
0.972
238202AE2-262_GEN
Solar/Wind Harmer
1.237
971627AH1-313 GEN
Solar/Wind Harmer
4.851
970899AG2-561 GEN
Solar/Wind Harmer
0.96
203818AF1-086 GEN
Solar/Wind Harmer
1.221
20335126GROZ1-110
Adder
1.058
20335226CANZ2-011
Adder
1.028
20060826PINEY #1
50/50
0.094
971183AH1-050 GEN
Solar/Wind Harmer
4.423
970647AG2-420 GEN
Solar/Wind Harmer
0.241
238183AE2-316 GEN
Solar/Wind Harmer
4.056
203860AG1-193 C
Solar/Wind Harmer
0.268
20082826HNSMLK 1
Adder
4.685
20083026HNSMLK 3
Adder
4.685
970267AG2-176 GEN
Solar/Wind Harmer
10.321
970713AG2-456 GEN
Solar/Wind Harmer
5.37
971705AH1-358 GEN
Solar/Wind Harmer
1.561
971709AH1-360 GEN
Solar/Wind Harmer
1.561
961971AG1-040 GEN
Solar/Wind Harmer
0.374
203954AE2-126 C
Solar/Wind Harmer
0.348
203813AE2-344_GEN
Solar/Wind Harmer
6.613
203835AF1-098 GEN
Solar/Wind Harmer
1.317
20326126BLOSSBCT
Adder
1.217
20072226SHAWVL 2
Adder
7.267
20335026MILZ1-092
Adder
1.196
944411AF1-106 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.337
972169AH1-667 GEN
Solar/Wind Harmer
0.923
20084926LAKVU GN
Adder
0.09
959471AF2-238 GEN
Solar/Wind Harmer
0.304
970337AG2-221 GEN
Solar/Wind Harmer
1.004
238206AE2-263_GEN
Solar/Wind Harmer
1.153
970511AG2-327 GEN
Solar/Wind Harmer
0.484
203848AF2-166 C
Solar/Wind Harmer
2.468
946381AF1-302 GEN
Solar/Wind Harmer
2.03
238217AF1-153 C O1
Solar/Wind Harmer
0.475
203979AG1-198 GEN
Solar/Wind Harmer
0.25
971933AH1-491 GEN
Solar/Wind Harmer
1.376
972077AH1-588 GEN
Solar/Wind Harmer
16.11
972079AH1-589 GEN
Solar/Wind Harmer
13.269
970715AG2-457 GEN
Solar/Wind Harmer
5.37
972075AH1-587 GEN
Solar/Wind Harmer
13.187
203980AG1-197 GEN
Solar/Wind Harmer
0.286
970305AG2-200 GEN
Solar/Wind Harmer
1.192
971931AH1-490 GEN
Solar/Wind Harmer
1.145
20398826ARMNA MT
Solar/Wind Harmer
1.24
203963AG1-253 GEN
Solar/Wind Harmer
0.21
203947AF1-006 C
Solar/Wind Harmer
0.288
203853AF1-134 C O1
Solar/Wind Harmer
0.298
203859AF2-294 C
Solar/Wind Harmer
0.83
970313AG2-206 GEN
Solar/Wind Harmer
2.323
G-007ALTFEXP_G-007A->PJM
CMTX
0.573
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.011
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.703
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.116
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.36
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.63 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:291.14
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.083
20066226SCRUB GR
50/50
0.542
970663AG2-429 GEN
Solar/Wind Harmer
11.251
970663AG2-429 GEN
Solar/Wind Harmer
1.832
203846AF2-130 C
Solar/Wind Harmer
0.705
20083926HOMER C3
Adder
60.33
20083826HOMER C2
Adder
56.988
20083226HNSMLK 5
Adder
4.685
970677AG2-438 GEN
Solar/Wind Harmer
0.688
966771AG1-548 GEN
Solar/Wind Harmer
9.79
966771AG1-548 GEN
Solar/Wind Harmer
1.897
203804AE2-113_GEN
Solar/Wind Harmer
3.144
940863AE2-074 GEN
Solar/Wind Harmer
1.129
203855AF2-088 C
Solar/Wind Harmer
0.101
20084926LAKVU GN
Adder
0.101
970555AG2-356 GEN
Solar/Wind Harmer
1.004
20083726HOMER C1
Adder
4.762
20060826PINEY #1
50/50
0.091
203932AE1-123
50/50
2.885
238219AF1-167 C
Solar/Wind Harmer
2.069
971185AH1-051 GEN
Solar/Wind Harmer
2.654
971355AH1-158 GEN
Solar/Wind Harmer
3.085
203856AF2-165 C
Solar/Wind Harmer
1.271
970647AG2-420 GEN
Solar/Wind Harmer
2.07
945751AF1-240 GEN
Solar/Wind Harmer
1.551
959441AF2-235 GEN
Solar/Wind Harmer
0.287
20082926HNSMLK 2
Adder
4.685
20083126HNSMLK 4
Adder
4.685
957161AF2-010 GEN
Solar/Wind Harmer
5.392
203830AF1-094 GEN
Solar/Wind Harmer
0.417
971703AH1-357 GEN
Solar/Wind Harmer
1.343
971707AH1-359 GEN
Solar/Wind Harmer
1.343
20334926Z1-069 C
Solar/Wind Harmer
1.306
20120126WRREN CT
Adder
3.77
962511AG1-100 GEN
Solar/Wind Harmer
0.346
203962AF1-287 GEN
Solar/Wind Harmer
1.141
944411AF1-106 GEN
Solar/Wind Harmer
0.118
203948AG1-140 C
Solar/Wind Harmer
0.137
203854AF2-039 C
Solar/Wind Harmer
0.21
20084926LAKVU GN
Adder
0.09
960051AF2-296 GEN
Solar/Wind Harmer
0.985
970335AG2-220 GEN
Solar/Wind Harmer
1.506
971127AH1-005 GEN
Solar/Wind Harmer
0.972
238202AE2-262_GEN
Solar/Wind Harmer
1.237
971627AH1-313 GEN
Solar/Wind Harmer
4.851
970899AG2-561 GEN
Solar/Wind Harmer
0.96
203818AF1-086 GEN
Solar/Wind Harmer
1.221
20335126GROZ1-110
Adder
1.058
20335226CANZ2-011
Adder
1.028
20060826PINEY #1
50/50
0.094
971183AH1-050 GEN
Solar/Wind Harmer
4.423
970647AG2-420 GEN
Solar/Wind Harmer
0.241
238183AE2-316 GEN
Solar/Wind Harmer
4.056
203860AG1-193 C
Solar/Wind Harmer
0.268
20082826HNSMLK 1
Adder
4.685
20083026HNSMLK 3
Adder
4.685
970267AG2-176 GEN
Solar/Wind Harmer
10.321
970713AG2-456 GEN
Solar/Wind Harmer
5.37
971705AH1-358 GEN
Solar/Wind Harmer
1.561
971709AH1-360 GEN
Solar/Wind Harmer
1.561
961971AG1-040 GEN
Solar/Wind Harmer
0.374
203954AE2-126 C
Solar/Wind Harmer
0.348
203813AE2-344_GEN
Solar/Wind Harmer
6.613
203835AF1-098 GEN
Solar/Wind Harmer
1.317
20326126BLOSSBCT
Adder
1.217
20072226SHAWVL 2
Adder
7.267
20335026MILZ1-092
Adder
1.196
944411AF1-106 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.337
972169AH1-667 GEN
Solar/Wind Harmer
0.923
20084926LAKVU GN
Adder
0.09
959471AF2-238 GEN
Solar/Wind Harmer
0.304
970337AG2-221 GEN
Solar/Wind Harmer
1.004
238206AE2-263_GEN
Solar/Wind Harmer
1.153
970511AG2-327 GEN
Solar/Wind Harmer
0.484
203848AF2-166 C
Solar/Wind Harmer
2.468
946381AF1-302 GEN
Solar/Wind Harmer
2.03
238217AF1-153 C O1
Solar/Wind Harmer
0.475
203979AG1-198 GEN
Solar/Wind Harmer
0.25
971933AH1-491 GEN
Solar/Wind Harmer
1.376
972077AH1-588 GEN
Solar/Wind Harmer
16.11
972079AH1-589 GEN
Solar/Wind Harmer
13.269
970715AG2-457 GEN
Solar/Wind Harmer
5.37
972075AH1-587 GEN
Solar/Wind Harmer
13.187
203980AG1-197 GEN
Solar/Wind Harmer
0.286
970305AG2-200 GEN
Solar/Wind Harmer
1.192
971931AH1-490 GEN
Solar/Wind Harmer
1.145
20398826ARMNA MT
Solar/Wind Harmer
1.24
203963AG1-253 GEN
Solar/Wind Harmer
0.21
203947AF1-006 C
Solar/Wind Harmer
0.288
203853AF1-134 C O1
Solar/Wind Harmer
0.298
203859AF2-294 C
Solar/Wind Harmer
0.83
970313AG2-206 GEN
Solar/Wind Harmer
2.323
G-007ALTFEXP_G-007A->PJM
CMTX
0.573
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.011
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.703
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.116
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.074
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.36
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KISSNG-01KARNSC 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KISSNG-01KARNSC 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:288.7
MW Contribution:1.15
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.093
20066226SCRUB GR
50/50
0.58
970663AG2-429 GEN
Solar/Wind Harmer
12.802
970663AG2-429 GEN
Solar/Wind Harmer
2.084
203846AF2-130 C
Solar/Wind Harmer
0.774
20083226HNSMLK 5
Adder
4.618
970677AG2-438 GEN
Solar/Wind Harmer
0.7
966771AG1-548 GEN
Solar/Wind Harmer
9.925
966771AG1-548 GEN
Solar/Wind Harmer
1.923
203804AE2-113_GEN
Solar/Wind Harmer
2.925
20083926HOMER C3
Adder
42.233
20083826HOMER C2
Adder
39.894
203855AF2-088 C
Solar/Wind Harmer
0.112
940863AE2-074 GEN
Solar/Wind Harmer
0.956
965121AG1-377 GEN
Solar/Wind Harmer
1.005
20084926LAKVU GN
Adder
0.097
20090526Q36
Solar/Wind Harmer
0.697
203993AD2-133_GEN1
Solar/Wind Harmer
0.697
20083726HOMER C1
Adder
24.849
20060826PINEY #1
50/50
0.105
971183AH1-050 GEN
Solar/Wind Harmer
4.775
238183AE2-316 GEN
Solar/Wind Harmer
4.699
970647AG2-420 GEN
Solar/Wind Harmer
0.258
203860AG1-193 C
Solar/Wind Harmer
0.28
20082826HNSMLK 1
Adder
4.618
20083026HNSMLK 3
Adder
4.618
970267AG2-176 GEN
Solar/Wind Harmer
10.363
961971AG1-040 GEN
Solar/Wind Harmer
0.371
203954AE2-126 C
Solar/Wind Harmer
0.369
20072226SHAWVL 2
Adder
7.961
970713AG2-456 GEN
Solar/Wind Harmer
4.618
971705AH1-358 GEN
Solar/Wind Harmer
1.342
971709AH1-360 GEN
Solar/Wind Harmer
1.342
20091326SHAW-D
Adder
0.375
20060826PINEY #1
50/50
0.1
203932AE1-123
50/50
3.2
23503001MHNG-T155
50/50
0.009
238219AF1-167 C
Solar/Wind Harmer
2.368
971185AH1-051 GEN
Solar/Wind Harmer
2.865
971355AH1-158 GEN
Solar/Wind Harmer
3.331
203848AF2-166 C
Solar/Wind Harmer
2.708
203856AF2-165 C
Solar/Wind Harmer
1.37
945751AF1-240 GEN
Solar/Wind Harmer
1.772
970647AG2-420 GEN
Solar/Wind Harmer
2.22
959441AF2-235 GEN
Solar/Wind Harmer
0.306
20082926HNSMLK 2
Adder
4.618
20083126HNSMLK 4
Adder
4.618
957161AF2-010 GEN
Solar/Wind Harmer
5.507
203830AF1-094 GEN
Solar/Wind Harmer
0.424
970899AG2-561 GEN
Solar/Wind Harmer
1.213
203818AF1-086 GEN
Solar/Wind Harmer
1.496
960051AF2-296 GEN
Solar/Wind Harmer
1.158
971703AH1-357 GEN
Solar/Wind Harmer
1.154
971707AH1-359 GEN
Solar/Wind Harmer
1.154
203854AF2-039 C
Solar/Wind Harmer
0.233
20120126WRREN CT
Adder
3.589
962511AG1-100 GEN
Solar/Wind Harmer
0.341
203962AF1-287 GEN
Solar/Wind Harmer
1.121
238202AE2-262_GEN
Solar/Wind Harmer
1.359
971627AH1-313 GEN
Solar/Wind Harmer
5.33
20334926Z1-069 C
Solar/Wind Harmer
1.091
965131AG1-378 GEN
Solar/Wind Harmer
1.005
203948AG1-140 C
Solar/Wind Harmer
0.13
20084926LAKVU GN
Adder
0.086
971541AH1-268 GEN
Solar/Wind Harmer
1.536
944411AF1-106 GEN
Solar/Wind Harmer
0.099
972169AH1-667 GEN
Solar/Wind Harmer
1.027
203813AE2-344_GEN
Solar/Wind Harmer
6.494
238206AE2-263_GEN
Solar/Wind Harmer
1.267
203835AF1-098 GEN
Solar/Wind Harmer
1.268
20084926LAKVU GN
Adder
0.086
20094526CT_V3-030
Solar/Wind Harmer
0.333
238215AE2-248 C
Solar/Wind Harmer
0.727
20326126BLOSSBCT
Adder
1.032
971279AH1-102 GEN
Solar/Wind Harmer
3.61
20335026MILZ1-092
Adder
0.995
944411AF1-106 GEN
Solar/Wind Harmer
0.916
946381AF1-302 GEN
Solar/Wind Harmer
2.351
238217AF1-153 C O1
Solar/Wind Harmer
0.518
203979AG1-198 GEN
Solar/Wind Harmer
0.255
971933AH1-491 GEN
Solar/Wind Harmer
1.401
203980AG1-197 GEN
Solar/Wind Harmer
0.284
972075AH1-587 GEN
Solar/Wind Harmer
11.981
203853AF1-134 C O1
Solar/Wind Harmer
0.35
972077AH1-588 GEN
Solar/Wind Harmer
13.853
972079AH1-589 GEN
Solar/Wind Harmer
11.41
970715AG2-457 GEN
Solar/Wind Harmer
4.618
970305AG2-200 GEN
Solar/Wind Harmer
1.135
971931AH1-490 GEN
Solar/Wind Harmer
1.126
203952AE2-129 C
Solar/Wind Harmer
0.304
203946AE2-131 C
Solar/Wind Harmer
0.304
962411AG1-090 GEN
Solar/Wind Harmer
4.775
203947AF1-006 C
Solar/Wind Harmer
0.279
203963AG1-253 GEN
Solar/Wind Harmer
0.199
216419AE2-001 C
Solar/Wind Harmer
0.931
20398826ARMNA MT
Solar/Wind Harmer
1.029
G-007ALTFEXP_G-007A->PJM
CMTX
1.156
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.737
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.197
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.613
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.875
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-171A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-171A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.95 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:224.92
MW Contribution:0.96
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.882
238219AF1-167 C
Solar/Wind Harmer
1.621
971185AH1-051 GEN
Solar/Wind Harmer
1.834
971355AH1-158 GEN
Solar/Wind Harmer
2.132
203856AF2-165 C
Solar/Wind Harmer
0.88
970647AG2-420 GEN
Solar/Wind Harmer
1.45
20082926HNSMLK 2
Adder
4.017
20083126HNSMLK 4
Adder
4.017
945751AF1-240 GEN
Solar/Wind Harmer
1.058
959441AF2-235 GEN
Solar/Wind Harmer
0.2
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.102
971183AH1-050 GEN
Solar/Wind Harmer
3.056
970647AG2-420 GEN
Solar/Wind Harmer
0.169
20082826HNSMLK 1
Adder
4.017
20083026HNSMLK 3
Adder
4.017
203860AG1-193 C
Solar/Wind Harmer
0.198
971865AH1-452 GEN
Solar/Wind Harmer
1.037
970267AG2-176 GEN
Solar/Wind Harmer
8.052
970713AG2-456 GEN
Solar/Wind Harmer
3.84
971705AH1-358 GEN
Solar/Wind Harmer
1.116
971709AH1-360 GEN
Solar/Wind Harmer
1.116
961971AG1-040 GEN
Solar/Wind Harmer
0.29
203954AE2-126 C
Solar/Wind Harmer
0.286
20072226SHAWVL 2
Adder
6.146
203813AE2-344_GEN
Solar/Wind Harmer
5.098
20091326SHAW-D
Adder
0.286
972169AH1-667 GEN
Solar/Wind Harmer
0.783
20060826PINEY #1
50/50
0.054
971055AG2-654 GEN
Solar/Wind Harmer
1.941
970663AG2-429 GEN
Solar/Wind Harmer
8.56
970663AG2-429 GEN
Solar/Wind Harmer
1.393
203846AF2-130 C
Solar/Wind Harmer
0.471
20083226HNSMLK 5
Adder
4.017
20083926HOMER C3
Adder
37.859
20083826HOMER C2
Adder
35.762
970677AG2-438 GEN
Solar/Wind Harmer
0.502
203804AE2-113_GEN
Solar/Wind Harmer
2.367
966771AG1-548 GEN
Solar/Wind Harmer
7.17
966771AG1-548 GEN
Solar/Wind Harmer
1.39
940863AE2-074 GEN
Solar/Wind Harmer
0.802
203855AF2-088 C
Solar/Wind Harmer
0.086
20083726HOMER C1
Adder
21.851
946381AF1-302 GEN
Solar/Wind Harmer
2.052
203848AF2-166 C
Solar/Wind Harmer
1.648
238217AF1-153 C O1
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.182
971933AH1-491 GEN
Solar/Wind Harmer
1.003
203980AG1-197 GEN
Solar/Wind Harmer
0.222
972075AH1-587 GEN
Solar/Wind Harmer
9.777
972077AH1-588 GEN
Solar/Wind Harmer
11.519
972079AH1-589 GEN
Solar/Wind Harmer
9.487
970715AG2-457 GEN
Solar/Wind Harmer
3.84
970305AG2-200 GEN
Solar/Wind Harmer
0.909
971931AH1-490 GEN
Solar/Wind Harmer
0.885
957161AF2-010 GEN
Solar/Wind Harmer
3.922
203830AF1-094 GEN
Solar/Wind Harmer
0.304
971703AH1-357 GEN
Solar/Wind Harmer
0.96
971707AH1-359 GEN
Solar/Wind Harmer
0.96
20120126WRREN CT
Adder
2.873
962511AG1-100 GEN
Solar/Wind Harmer
0.267
20334926Z1-069 C
Solar/Wind Harmer
0.923
203962AF1-287 GEN
Solar/Wind Harmer
0.88
203854AF2-039 C
Solar/Wind Harmer
0.178
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.9
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.145
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.903
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-054A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-054A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:148.43 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:224.13
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
2.041
203848AF2-166 C
Solar/Wind Harmer
1.637
238217AF1-153 C O1
Solar/Wind Harmer
0.376
203979AG1-198 GEN
Solar/Wind Harmer
0.181
971933AH1-491 GEN
Solar/Wind Harmer
0.997
972075AH1-587 GEN
Solar/Wind Harmer
9.722
203980AG1-197 GEN
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
11.454
972079AH1-589 GEN
Solar/Wind Harmer
9.434
970715AG2-457 GEN
Solar/Wind Harmer
3.818
970305AG2-200 GEN
Solar/Wind Harmer
0.904
971931AH1-490 GEN
Solar/Wind Harmer
0.879
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
238219AF1-167 C
Solar/Wind Harmer
1.603
971185AH1-051 GEN
Solar/Wind Harmer
1.822
971355AH1-158 GEN
Solar/Wind Harmer
2.119
203856AF2-165 C
Solar/Wind Harmer
0.874
970647AG2-420 GEN
Solar/Wind Harmer
1.441
20082926HNSMLK 2
Adder
3.994
20083126HNSMLK 4
Adder
3.994
945751AF1-240 GEN
Solar/Wind Harmer
1.051
959441AF2-235 GEN
Solar/Wind Harmer
0.199
957161AF2-010 GEN
Solar/Wind Harmer
3.898
203830AF1-094 GEN
Solar/Wind Harmer
0.302
971703AH1-357 GEN
Solar/Wind Harmer
0.955
971707AH1-359 GEN
Solar/Wind Harmer
0.955
20120126WRREN CT
Adder
2.857
962511AG1-100 GEN
Solar/Wind Harmer
0.266
20334926Z1-069 C
Solar/Wind Harmer
0.918
203962AF1-287 GEN
Solar/Wind Harmer
0.874
203854AF2-039 C
Solar/Wind Harmer
0.177
20060826PINEY #1
50/50
0.054
970663AG2-429 GEN
Solar/Wind Harmer
8.508
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.468
20083226HNSMLK 5
Adder
3.994
20083926HOMER C3
Adder
37.654
20083826HOMER C2
Adder
35.569
970677AG2-438 GEN
Solar/Wind Harmer
0.499
203804AE2-113_GEN
Solar/Wind Harmer
2.354
966771AG1-548 GEN
Solar/Wind Harmer
7.126
966771AG1-548 GEN
Solar/Wind Harmer
1.381
940863AE2-074 GEN
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.085
20083726HOMER C1
Adder
21.738
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.079
971183AH1-050 GEN
Solar/Wind Harmer
3.037
970647AG2-420 GEN
Solar/Wind Harmer
0.168
20082826HNSMLK 1
Adder
3.994
20083026HNSMLK 3
Adder
3.994
203860AG1-193 C
Solar/Wind Harmer
0.197
971865AH1-452 GEN
Solar/Wind Harmer
0.981
970267AG2-176 GEN
Solar/Wind Harmer
8.004
970713AG2-456 GEN
Solar/Wind Harmer
3.818
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
961971AG1-040 GEN
Solar/Wind Harmer
0.288
203954AE2-126 C
Solar/Wind Harmer
0.284
20072226SHAWVL 2
Adder
6.111
203813AE2-344_GEN
Solar/Wind Harmer
5.068
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.779
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.633
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.31 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:213.37
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.437
20082926HNSMLK 2
Adder
4.153
20083126HNSMLK 4
Adder
4.153
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.049
972079AH1-589 GEN
Solar/Wind Harmer
9.924
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.883
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.944
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.153
20083026HNSMLK 3
Adder
4.153
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.971
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.347
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.448
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.168
971709AH1-360 GEN
Solar/Wind Harmer
1.168
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.153
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.339
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.758
20083826HOMER C2
Adder
32.833
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.408
G-007ALTFEXP_G-007A->PJM
CMTX
1.778
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.926
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.817
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.31 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:213.37
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.437
20082926HNSMLK 2
Adder
4.153
20083126HNSMLK 4
Adder
4.153
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.944
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.153
20083026HNSMLK 3
Adder
4.153
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.971
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.347
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.448
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.168
971709AH1-360 GEN
Solar/Wind Harmer
1.168
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.153
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.339
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.758
20083826HOMER C2
Adder
32.833
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.408
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.049
972079AH1-589 GEN
Solar/Wind Harmer
9.924
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.883
G-007ALTFEXP_G-007A->PJM
CMTX
1.778
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.926
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.817
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.47 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:207.58
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
238183AE2-316 GEN
Solar/Wind Harmer
3.31
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.578
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.295
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.559
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.986
944411AF1-106 GEN
Solar/Wind Harmer
0.908
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.547
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.074
971707AH1-359 GEN
Solar/Wind Harmer
1.074
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.6
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.874
944411AF1-106 GEN
Solar/Wind Harmer
0.098
970663AG2-429 GEN
Solar/Wind Harmer
6.704
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.748
20083826HOMER C2
Adder
48.882
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.646
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.915
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.884
972079AH1-589 GEN
Solar/Wind Harmer
10.611
970715AG2-457 GEN
Solar/Wind Harmer
4.295
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.317
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.925
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.023
G-007ALTFEXP_G-007A->PJM
CMTX
0.926
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.11
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.631
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.126
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.393
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.558
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.47 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:207.58
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
970663AG2-429 GEN
Solar/Wind Harmer
6.704
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.748
20083826HOMER C2
Adder
48.882
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.646
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.915
238183AE2-316 GEN
Solar/Wind Harmer
3.31
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.578
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.295
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.559
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.986
944411AF1-106 GEN
Solar/Wind Harmer
0.908
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.547
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.074
971707AH1-359 GEN
Solar/Wind Harmer
1.074
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.6
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.874
944411AF1-106 GEN
Solar/Wind Harmer
0.098
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.884
972079AH1-589 GEN
Solar/Wind Harmer
10.611
970715AG2-457 GEN
Solar/Wind Harmer
4.295
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.317
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.925
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.023
G-007ALTFEXP_G-007A->PJM
CMTX
0.926
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.11
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.631
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.126
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.393
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.558
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.95 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:181.13
MW Contribution:0.67
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.061
20082826HNSMLK 1
50/50
4.239
20083026HNSMLK 3
50/50
4.239
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
0.168
203860AG1-193 C
Solar/Wind Harmer
0
971865AH1-452 GEN
Solar/Wind Harmer
0.564
970267AG2-176 GEN
Solar/Wind Harmer
5.584
970713AG2-456 GEN
Solar/Wind Harmer
3.097
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
203954AE2-126 C
Solar/Wind Harmer
0
20072226SHAWVL 2
Adder
6.111
203813AE2-344_GEN
Solar/Wind Harmer
3.536
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.543
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
20082926HNSMLK 2
50/50
4.239
20083126HNSMLK 4
50/50
4.239
238219AF1-167 C
Solar/Wind Harmer
1.117
971185AH1-051 GEN
Solar/Wind Harmer
1.57
971355AH1-158 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
1.005
945751AF1-240 GEN
Solar/Wind Harmer
0.854
957161AF2-010 GEN
Solar/Wind Harmer
2.708
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.666
971707AH1-359 GEN
Solar/Wind Harmer
0.666
20120126WRREN CT
Adder
2.857
20334926Z1-069 C
Solar/Wind Harmer
0.23
203962AF1-287 GEN
Solar/Wind Harmer
0.61
203854AF2-039 C
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
1.142
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.696
972075AH1-587 GEN
Solar/Wind Harmer
6.783
203980AG1-197 GEN
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
7.991
972079AH1-589 GEN
Solar/Wind Harmer
9.434
970715AG2-457 GEN
Solar/Wind Harmer
3.097
970305AG2-200 GEN
Solar/Wind Harmer
0.63
971931AH1-490 GEN
Solar/Wind Harmer
0.613
20060826PINEY #1
50/50
0.054
20066226SCRUB GR
50/50
0.379
20083226HNSMLK 5
50/50
4.239
970663AG2-429 GEN
Solar/Wind Harmer
6.337
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.082
20083926HOMER C3
Adder
37.654
20083826HOMER C2
Adder
35.569
970677AG2-438 GEN
Solar/Wind Harmer
0.388
203804AE2-113_GEN
Solar/Wind Harmer
0.003
966771AG1-548 GEN
Solar/Wind Harmer
1.134
966771AG1-548 GEN
Solar/Wind Harmer
1.418
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.738
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.633
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:158.22
MW Contribution:0.82
Bus #Bus NameTypeMW Contribution
971865AH1-452 GEN
Solar/Wind Harmer
1.68
238183AE2-316 GEN
Solar/Wind Harmer
3.43
971183AH1-050 GEN
Solar/Wind Harmer
2.582
970647AG2-420 GEN
Solar/Wind Harmer
0.142
20082826HNSMLK 1
Adder
3.366
20083026HNSMLK 3
Adder
3.366
203860AG1-193 C
Solar/Wind Harmer
0.167
970267AG2-176 GEN
Solar/Wind Harmer
6.755
970713AG2-456 GEN
Solar/Wind Harmer
3.283
971705AH1-358 GEN
Solar/Wind Harmer
0.954
971709AH1-360 GEN
Solar/Wind Harmer
0.954
946381AF1-302 GEN
Solar/Wind Harmer
1.716
203848AF2-166 C
Solar/Wind Harmer
1.395
238217AF1-153 C O1
Solar/Wind Harmer
0.322
972075AH1-587 GEN
Solar/Wind Harmer
8.367
972077AH1-588 GEN
Solar/Wind Harmer
9.849
972079AH1-589 GEN
Solar/Wind Harmer
8.112
970715AG2-457 GEN
Solar/Wind Harmer
3.283
971055AG2-654 GEN
Solar/Wind Harmer
1.558
970663AG2-429 GEN
Solar/Wind Harmer
7.159
970663AG2-429 GEN
Solar/Wind Harmer
1.165
203846AF2-130 C
Solar/Wind Harmer
0.398
20083226HNSMLK 5
Adder
3.366
20083926HOMER C3
Adder
32.602
20083826HOMER C2
Adder
30.796
20083726HOMER C1
Adder
19.756
23503001MHNG-T155
50/50
0.018
238219AF1-167 C
Solar/Wind Harmer
1.452
203932AE1-123
Adder
1.503
971185AH1-051 GEN
Solar/Wind Harmer
1.549
971355AH1-158 GEN
Solar/Wind Harmer
1.801
203856AF2-165 C
Solar/Wind Harmer
0.743
970647AG2-420 GEN
Solar/Wind Harmer
1.224
945751AF1-240 GEN
Solar/Wind Harmer
0.922
20082926HNSMLK 2
Adder
3.366
20083126HNSMLK 4
Adder
3.366
959441AF2-235 GEN
Solar/Wind Harmer
0.169
971703AH1-357 GEN
Solar/Wind Harmer
0.821
971707AH1-359 GEN
Solar/Wind Harmer
0.821
G-007ALTFEXP_G-007A->PJM
CMTX
1.394
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.662
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.875
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.088
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.19
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.591
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.842
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-055_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-055_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.82 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:155.25
MW Contribution:0.81
Bus #Bus NameTypeMW Contribution
971055AG2-654 GEN
Solar/Wind Harmer
1.278
970663AG2-429 GEN
Solar/Wind Harmer
6.916
970663AG2-429 GEN
Solar/Wind Harmer
1.126
203846AF2-130 C
Solar/Wind Harmer
0.386
20083226HNSMLK 5
Adder
3.264
20083926HOMER C3
Adder
32.151
20083826HOMER C2
Adder
30.371
20083726HOMER C1
Adder
19.966
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.314
203932AE1-123
Adder
1.455
971185AH1-051 GEN
Solar/Wind Harmer
1.499
971355AH1-158 GEN
Solar/Wind Harmer
1.743
203856AF2-165 C
Solar/Wind Harmer
0.719
970647AG2-420 GEN
Solar/Wind Harmer
1.184
945751AF1-240 GEN
Solar/Wind Harmer
0.9
20082926HNSMLK 2
Adder
3.264
20083126HNSMLK 4
Adder
3.264
959441AF2-235 GEN
Solar/Wind Harmer
0.164
971703AH1-357 GEN
Solar/Wind Harmer
0.805
971707AH1-359 GEN
Solar/Wind Harmer
0.805
946381AF1-302 GEN
Solar/Wind Harmer
1.665
203848AF2-166 C
Solar/Wind Harmer
1.35
238217AF1-153 C O1
Solar/Wind Harmer
0.314
972075AH1-587 GEN
Solar/Wind Harmer
8.206
972077AH1-588 GEN
Solar/Wind Harmer
9.657
972079AH1-589 GEN
Solar/Wind Harmer
7.954
970715AG2-457 GEN
Solar/Wind Harmer
3.219
971865AH1-452 GEN
Solar/Wind Harmer
1.465
238183AE2-316 GEN
Solar/Wind Harmer
3.328
971183AH1-050 GEN
Solar/Wind Harmer
2.499
970647AG2-420 GEN
Solar/Wind Harmer
0.138
20082826HNSMLK 1
Adder
3.264
20083026HNSMLK 3
Adder
3.264
203860AG1-193 C
Solar/Wind Harmer
0.162
970267AG2-176 GEN
Solar/Wind Harmer
6.53
970713AG2-456 GEN
Solar/Wind Harmer
3.219
971705AH1-358 GEN
Solar/Wind Harmer
0.936
971709AH1-360 GEN
Solar/Wind Harmer
0.936
G-007ALTFEXP_G-007A->PJM
CMTX
1.584
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.832
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.388
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.093
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.649
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.924
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0310-B_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0310-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.58 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:823.64
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
38.952
20091326SHAW-D
50/50
1.605
20064926PENNTECH
50/50
0.501
200643SENECA#2
50/50
1.711
20326126BLOSSBCT
50/50
2.096
238215AE2-248 C
Solar/Wind Harmer
6.571
238206AE2-263_GEN
Solar/Wind Harmer
7.671
972169AH1-667 GEN
Solar/Wind Harmer
4.142
203954AE2-126 C
Solar/Wind Harmer
1.248
238183AE2-316 GEN
Solar/Wind Harmer
6.048
970713AG2-456 GEN
Solar/Wind Harmer
7.919
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
959471AF2-238 GEN
Solar/Wind Harmer
0.485
970337AG2-221 GEN
Solar/Wind Harmer
1.604
970511AG2-327 GEN
Solar/Wind Harmer
0.747
20335026MILZ1-092
Adder
1.625
944411AF1-106 GEN
Solar/Wind Harmer
1.497
20094526CT_V3-030
Solar/Wind Harmer
0.481
203835AF1-098 GEN
Solar/Wind Harmer
1.626
20084926LAKVU GN
Adder
0.1
971183AH1-050 GEN
Solar/Wind Harmer
2.303
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
6.109
203860AG1-193 C
Solar/Wind Harmer
0.158
961971AG1-040 GEN
Solar/Wind Harmer
0.31
970267AG2-176 GEN
Solar/Wind Harmer
7.516
971279AH1-102 GEN
Solar/Wind Harmer
4.003
20082826HNSMLK 1
Adder
2.765
20083026HNSMLK 3
Adder
2.765
964201AG1-281 GEN
Solar/Wind Harmer
0.28
209067AE2-060 GEN
Solar/Wind Helper
0.05
200642SENECA#1
50/50
1.834
203855AF2-088 C
Solar/Wind Harmer
0.453
965121AG1-377 GEN
Solar/Wind Harmer
3.566
203804AE2-113_GEN
Solar/Wind Harmer
6.682
20090526Q36
Solar/Wind Harmer
2.112
203993AD2-133_GEN1
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
1.63
970555AG2-356 GEN
Solar/Wind Harmer
1.604
20091526CHSTN_FL
Solar/Wind Harmer
0.629
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
4.216
970663AG2-429 GEN
Solar/Wind Harmer
0.686
203846AF2-130 C
Solar/Wind Harmer
0.343
20334726NME_Y1-047
Adder
1.345
970677AG2-438 GEN
Solar/Wind Harmer
0.573
966771AG1-548 GEN
Solar/Wind Harmer
8.375
966771AG1-548 GEN
Solar/Wind Harmer
1.623
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.765
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.049
20083826HOMER C2
Adder
30.274
203850AG1-041 C
Solar/Wind Harmer
0.516
20083726HOMER C1
Adder
22.467
203975AE1-071-GEN
Solar/Wind Helper
2.841
959381AF2-229 GEN
Solar/Wind Helper
0.285
20066626SHAWVL 4
50/50
2.968
20066526SHAWVL 3
50/50
2.946
20071526SHAWVL 1
50/50
1.942
216419AE2-001 C
Solar/Wind Harmer
7.963
238217AF1-153 C O1
Solar/Wind Harmer
1.185
203952AE2-129 C
Solar/Wind Harmer
1.08
203946AE2-131 C
Solar/Wind Harmer
1.078
962411AG1-090 GEN
Solar/Wind Harmer
16.937
203853AF1-134 C O1
Solar/Wind Harmer
0.978
946381AF1-302 GEN
Solar/Wind Harmer
3.026
972075AH1-587 GEN
Solar/Wind Harmer
25.57
970305AG2-200 GEN
Solar/Wind Harmer
2.097
972077AH1-588 GEN
Solar/Wind Harmer
23.757
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
7.919
970313AG2-206 GEN
Solar/Wind Harmer
3.587
20398826ARMNA MT
Solar/Wind Harmer
1.728
203859AF2-294 C
Solar/Wind Harmer
1.087
203848AF2-166 C
Solar/Wind Harmer
1.2
203963AG1-253 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.147
203947AF1-006 C
Solar/Wind Harmer
0.298
971931AH1-490 GEN
Solar/Wind Harmer
1.032
203980AG1-197 GEN
Solar/Wind Harmer
0.231
971441AH1-212 GEN
Solar/Wind Harmer
1.005
203940AF1-140 C
Solar/Wind Harmer
0.231
946071AF1-272 GEN
Solar/Wind Harmer
1.498
20390526W1-045 C
Solar/Wind Helper
0.279
209137AF2-361 C
Solar/Wind Helper
0.847
200644SENECA#3
50/50
0.235
20120126WRREN CT
50/50
7.033
20335126GROZ1-110
50/50
2.564
20335226CANZ2-011
50/50
2.492
238202AE2-262_GEN
Solar/Wind Harmer
8.231
971627AH1-313 GEN
Solar/Wind Harmer
32.271
203854AF2-039 C
Solar/Wind Harmer
0.941
965131AG1-378 GEN
Solar/Wind Harmer
3.566
960051AF2-296 GEN
Solar/Wind Harmer
3.237
203818AF1-086 GEN
Solar/Wind Harmer
2.84
971703AH1-357 GEN
Solar/Wind Harmer
1.98
971707AH1-359 GEN
Solar/Wind Harmer
1.98
941421AE2-139 GEN
Solar/Wind Harmer
2.682
20334926Z1-069 C
Solar/Wind Harmer
1.801
972271AH1-720 GEN
Adder
5.197
970335AG2-220 GEN
Solar/Wind Harmer
2.316
971127AH1-005 GEN
Solar/Wind Harmer
1.494
20328326MANOR_T86
Adder
0.106
944411AF1-106 GEN
Solar/Wind Harmer
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.32
238219AF1-167 C
Solar/Wind Harmer
0.871
945751AF1-240 GEN
Solar/Wind Harmer
1.006
203932AE1-123
Adder
1.228
203948AG1-140 C
Solar/Wind Harmer
0.154
959441AF2-235 GEN
Solar/Wind Harmer
0.174
200917MEHOOPANY_G
Solar/Wind Harmer
2.001
957161AF2-010 GEN
Solar/Wind Harmer
4.415
203830AF1-094 GEN
Solar/Wind Harmer
0.347
20084926LAKVU GN
Adder
0.1
203856AF2-165 C
Solar/Wind Harmer
0.68
971185AH1-051 GEN
Solar/Wind Harmer
1.382
971355AH1-158 GEN
Solar/Wind Harmer
1.607
970647AG2-420 GEN
Solar/Wind Harmer
1.119
203962AF1-287 GEN
Solar/Wind Harmer
1.055
962511AG1-100 GEN
Solar/Wind Harmer
0.312
971541AH1-268 GEN
Solar/Wind Harmer
1.703
20082926HNSMLK 2
Adder
2.765
20083126HNSMLK 4
Adder
2.765
970679AG2-439 GEN
Solar/Wind Harmer
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.318
WECLTFEXP_WEC->PJM
CLTF
0.194
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.515
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.371
LAGNLTFEXP_LAGN->PJM
CLTF
0.687
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.244
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.337
MECLTFEXP_MEC->PJM
CLTF
0.791
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0310-A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0310-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.58 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:823.6
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.235
20120126WRREN CT
50/50
7.034
20335126GROZ1-110
50/50
2.564
20335226CANZ2-011
50/50
2.493
238202AE2-262_GEN
Solar/Wind Harmer
8.231
971627AH1-313 GEN
Solar/Wind Harmer
32.273
203854AF2-039 C
Solar/Wind Harmer
0.941
965131AG1-378 GEN
Solar/Wind Harmer
3.567
960051AF2-296 GEN
Solar/Wind Harmer
3.237
203818AF1-086 GEN
Solar/Wind Harmer
2.84
971703AH1-357 GEN
Solar/Wind Harmer
1.98
971707AH1-359 GEN
Solar/Wind Harmer
1.98
941421AE2-139 GEN
Solar/Wind Harmer
2.682
20334926Z1-069 C
Solar/Wind Harmer
1.801
972271AH1-720 GEN
Adder
5.198
970335AG2-220 GEN
Solar/Wind Harmer
2.316
971127AH1-005 GEN
Solar/Wind Harmer
1.494
20328326MANOR_T86
Adder
0.106
944411AF1-106 GEN
Solar/Wind Harmer
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.32
238219AF1-167 C
Solar/Wind Harmer
0.871
945751AF1-240 GEN
Solar/Wind Harmer
1.006
203932AE1-123
Adder
1.228
203948AG1-140 C
Solar/Wind Harmer
0.154
959441AF2-235 GEN
Solar/Wind Harmer
0.174
200917MEHOOPANY_G
Solar/Wind Harmer
2.001
957161AF2-010 GEN
Solar/Wind Harmer
4.415
203830AF1-094 GEN
Solar/Wind Harmer
0.347
20084926LAKVU GN
Adder
0.1
203856AF2-165 C
Solar/Wind Harmer
0.68
971185AH1-051 GEN
Solar/Wind Harmer
1.382
971355AH1-158 GEN
Solar/Wind Harmer
1.607
970647AG2-420 GEN
Solar/Wind Harmer
1.119
203962AF1-287 GEN
Solar/Wind Harmer
1.055
962511AG1-100 GEN
Solar/Wind Harmer
0.312
971541AH1-268 GEN
Solar/Wind Harmer
1.703
20082926HNSMLK 2
Adder
2.765
20083126HNSMLK 4
Adder
2.765
970679AG2-439 GEN
Solar/Wind Harmer
0.449
20072226SHAWVL 2
50/50
38.955
20091326SHAW-D
50/50
1.605
20064926PENNTECH
50/50
0.501
200643SENECA#2
50/50
1.711
20326126BLOSSBCT
50/50
2.096
238215AE2-248 C
Solar/Wind Harmer
6.571
238206AE2-263_GEN
Solar/Wind Harmer
7.672
972169AH1-667 GEN
Solar/Wind Harmer
4.142
203954AE2-126 C
Solar/Wind Harmer
1.249
238183AE2-316 GEN
Solar/Wind Harmer
6.048
970713AG2-456 GEN
Solar/Wind Harmer
7.919
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
959471AF2-238 GEN
Solar/Wind Harmer
0.485
970337AG2-221 GEN
Solar/Wind Harmer
1.604
970511AG2-327 GEN
Solar/Wind Harmer
0.747
20335026MILZ1-092
Adder
1.625
944411AF1-106 GEN
Solar/Wind Harmer
1.497
20094526CT_V3-030
Solar/Wind Harmer
0.481
203835AF1-098 GEN
Solar/Wind Harmer
1.626
20084926LAKVU GN
Adder
0.1
971183AH1-050 GEN
Solar/Wind Harmer
2.303
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
6.109
203860AG1-193 C
Solar/Wind Harmer
0.158
961971AG1-040 GEN
Solar/Wind Harmer
0.31
970267AG2-176 GEN
Solar/Wind Harmer
7.516
971279AH1-102 GEN
Solar/Wind Harmer
4.002
20082826HNSMLK 1
Adder
2.765
20083026HNSMLK 3
Adder
2.765
964201AG1-281 GEN
Solar/Wind Harmer
0.28
209067AE2-060 GEN
Solar/Wind Helper
0.05
200642SENECA#1
50/50
1.834
203855AF2-088 C
Solar/Wind Harmer
0.453
965121AG1-377 GEN
Solar/Wind Harmer
3.567
203804AE2-113_GEN
Solar/Wind Harmer
6.683
20090526Q36
Solar/Wind Harmer
2.113
203993AD2-133_GEN1
Solar/Wind Harmer
2.113
940863AE2-074 GEN
Solar/Wind Harmer
1.63
970555AG2-356 GEN
Solar/Wind Harmer
1.604
20091526CHSTN_FL
Solar/Wind Harmer
0.63
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
4.216
970663AG2-429 GEN
Solar/Wind Harmer
0.686
203846AF2-130 C
Solar/Wind Harmer
0.343
20334726NME_Y1-047
Adder
1.345
970677AG2-438 GEN
Solar/Wind Harmer
0.573
966771AG1-548 GEN
Solar/Wind Harmer
8.375
966771AG1-548 GEN
Solar/Wind Harmer
1.623
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.765
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.043
20083826HOMER C2
Adder
30.269
203850AG1-041 C
Solar/Wind Harmer
0.516
20083726HOMER C1
Adder
22.459
203975AE1-071-GEN
Solar/Wind Helper
2.841
959381AF2-229 GEN
Solar/Wind Helper
0.284
20066626SHAWVL 4
50/50
2.968
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.942
216419AE2-001 C
Solar/Wind Harmer
7.963
238217AF1-153 C O1
Solar/Wind Harmer
1.185
203952AE2-129 C
Solar/Wind Harmer
1.08
203946AE2-131 C
Solar/Wind Harmer
1.078
962411AG1-090 GEN
Solar/Wind Harmer
16.942
203853AF1-134 C O1
Solar/Wind Harmer
0.979
946381AF1-302 GEN
Solar/Wind Harmer
3.027
972075AH1-587 GEN
Solar/Wind Harmer
25.571
970305AG2-200 GEN
Solar/Wind Harmer
2.097
972077AH1-588 GEN
Solar/Wind Harmer
23.758
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
7.919
970313AG2-206 GEN
Solar/Wind Harmer
3.587
20398826ARMNA MT
Solar/Wind Harmer
1.728
203859AF2-294 C
Solar/Wind Harmer
1.087
203848AF2-166 C
Solar/Wind Harmer
1.2
203963AG1-253 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.147
203947AF1-006 C
Solar/Wind Harmer
0.298
971931AH1-490 GEN
Solar/Wind Harmer
1.032
203980AG1-197 GEN
Solar/Wind Harmer
0.231
971441AH1-212 GEN
Solar/Wind Harmer
1.006
203940AF1-140 C
Solar/Wind Harmer
0.231
946071AF1-272 GEN
Solar/Wind Harmer
1.498
20390526W1-045 C
Solar/Wind Helper
0.279
209137AF2-361 C
Solar/Wind Helper
0.847
LGEELTFEXP_LGEE->PJM
CLTF
0.318
WECLTFEXP_WEC->PJM
CLTF
0.194
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.516
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.369
LAGNLTFEXP_LAGN->PJM
CLTF
0.687
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.244
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.222
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.336
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0014-01_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0014-01_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.57 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:823.56
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.834
203855AF2-088 C
Solar/Wind Harmer
0.453
965121AG1-377 GEN
Solar/Wind Harmer
3.568
203804AE2-113_GEN
Solar/Wind Harmer
6.683
20090526Q36
Solar/Wind Harmer
2.115
203993AD2-133_GEN1
Solar/Wind Harmer
2.115
940863AE2-074 GEN
Solar/Wind Harmer
1.63
970555AG2-356 GEN
Solar/Wind Harmer
1.605
20091526CHSTN_FL
Solar/Wind Harmer
0.63
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
4.216
970663AG2-429 GEN
Solar/Wind Harmer
0.686
203846AF2-130 C
Solar/Wind Harmer
0.343
20334726NME_Y1-047
Adder
1.345
970677AG2-438 GEN
Solar/Wind Harmer
0.573
966771AG1-548 GEN
Solar/Wind Harmer
8.375
966771AG1-548 GEN
Solar/Wind Harmer
1.623
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.764
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.037
20083826HOMER C2
Adder
30.262
203850AG1-041 C
Solar/Wind Harmer
0.516
20083726HOMER C1
Adder
22.45
203975AE1-071-GEN
Solar/Wind Helper
2.84
959381AF2-229 GEN
Solar/Wind Helper
0.284
20072226SHAWVL 2
50/50
38.959
20091326SHAW-D
50/50
1.605
20064926PENNTECH
50/50
0.501
200643SENECA#2
50/50
1.711
20326126BLOSSBCT
50/50
2.096
238215AE2-248 C
Solar/Wind Harmer
6.572
238206AE2-263_GEN
Solar/Wind Harmer
7.672
972169AH1-667 GEN
Solar/Wind Harmer
4.143
203954AE2-126 C
Solar/Wind Harmer
1.249
238183AE2-316 GEN
Solar/Wind Harmer
6.049
970713AG2-456 GEN
Solar/Wind Harmer
7.919
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
959471AF2-238 GEN
Solar/Wind Harmer
0.485
970337AG2-221 GEN
Solar/Wind Harmer
1.605
970511AG2-327 GEN
Solar/Wind Harmer
0.747
20335026MILZ1-092
Adder
1.625
944411AF1-106 GEN
Solar/Wind Harmer
1.497
20094526CT_V3-030
Solar/Wind Harmer
0.481
203835AF1-098 GEN
Solar/Wind Harmer
1.627
20084926LAKVU GN
Adder
0.1
971183AH1-050 GEN
Solar/Wind Harmer
2.303
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
6.109
203860AG1-193 C
Solar/Wind Harmer
0.158
961971AG1-040 GEN
Solar/Wind Harmer
0.31
970267AG2-176 GEN
Solar/Wind Harmer
7.516
971279AH1-102 GEN
Solar/Wind Harmer
4.001
20082826HNSMLK 1
Adder
2.764
20083026HNSMLK 3
Adder
2.764
964201AG1-281 GEN
Solar/Wind Harmer
0.28
209067AE2-060 GEN
Solar/Wind Helper
0.05
200644SENECA#3
50/50
0.235
20120126WRREN CT
50/50
7.034
20335126GROZ1-110
50/50
2.565
20335226CANZ2-011
50/50
2.493
238202AE2-262_GEN
Solar/Wind Harmer
8.232
971627AH1-313 GEN
Solar/Wind Harmer
32.276
203854AF2-039 C
Solar/Wind Harmer
0.941
965131AG1-378 GEN
Solar/Wind Harmer
3.568
960051AF2-296 GEN
Solar/Wind Harmer
3.237
203818AF1-086 GEN
Solar/Wind Harmer
2.84
971703AH1-357 GEN
Solar/Wind Harmer
1.98
971707AH1-359 GEN
Solar/Wind Harmer
1.98
941421AE2-139 GEN
Solar/Wind Harmer
2.682
20334926Z1-069 C
Solar/Wind Harmer
1.801
972271AH1-720 GEN
Adder
5.198
970335AG2-220 GEN
Solar/Wind Harmer
2.316
971127AH1-005 GEN
Solar/Wind Harmer
1.494
20328326MANOR_T86
Adder
0.106
944411AF1-106 GEN
Solar/Wind Harmer
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.32
238219AF1-167 C
Solar/Wind Harmer
0.871
945751AF1-240 GEN
Solar/Wind Harmer
1.006
203932AE1-123
Adder
1.228
203948AG1-140 C
Solar/Wind Harmer
0.154
959441AF2-235 GEN
Solar/Wind Harmer
0.174
200917MEHOOPANY_G
Solar/Wind Harmer
2.002
957161AF2-010 GEN
Solar/Wind Harmer
4.415
203830AF1-094 GEN
Solar/Wind Harmer
0.347
20084926LAKVU GN
Adder
0.1
203856AF2-165 C
Solar/Wind Harmer
0.68
971185AH1-051 GEN
Solar/Wind Harmer
1.382
971355AH1-158 GEN
Solar/Wind Harmer
1.607
970647AG2-420 GEN
Solar/Wind Harmer
1.119
203962AF1-287 GEN
Solar/Wind Harmer
1.055
962511AG1-100 GEN
Solar/Wind Harmer
0.312
971541AH1-268 GEN
Solar/Wind Harmer
1.703
20082926HNSMLK 2
Adder
2.764
20083126HNSMLK 4
Adder
2.764
970679AG2-439 GEN
Solar/Wind Harmer
0.449
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.942
216419AE2-001 C
Solar/Wind Harmer
7.964
238217AF1-153 C O1
Solar/Wind Harmer
1.186
203952AE2-129 C
Solar/Wind Harmer
1.081
203946AE2-131 C
Solar/Wind Harmer
1.079
962411AG1-090 GEN
Solar/Wind Harmer
16.949
203853AF1-134 C O1
Solar/Wind Harmer
0.979
946381AF1-302 GEN
Solar/Wind Harmer
3.027
972075AH1-587 GEN
Solar/Wind Harmer
25.572
970305AG2-200 GEN
Solar/Wind Harmer
2.097
972077AH1-588 GEN
Solar/Wind Harmer
23.758
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
7.919
970313AG2-206 GEN
Solar/Wind Harmer
3.587
20398826ARMNA MT
Solar/Wind Harmer
1.728
203859AF2-294 C
Solar/Wind Harmer
1.087
203848AF2-166 C
Solar/Wind Harmer
1.2
203963AG1-253 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.147
203947AF1-006 C
Solar/Wind Harmer
0.298
971931AH1-490 GEN
Solar/Wind Harmer
1.032
203980AG1-197 GEN
Solar/Wind Harmer
0.231
971441AH1-212 GEN
Solar/Wind Harmer
1.006
203940AF1-140 C
Solar/Wind Harmer
0.231
946071AF1-272 GEN
Solar/Wind Harmer
1.498
20390526W1-045 C
Solar/Wind Helper
0.279
209137AF2-361 C
Solar/Wind Helper
0.847
LGEELTFEXP_LGEE->PJM
CLTF
0.318
WECLTFEXP_WEC->PJM
CLTF
0.194
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.517
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.368
LAGNLTFEXP_LAGN->PJM
CLTF
0.686
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.243
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.336
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0014-02_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0014-02_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.52 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:817.12
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
38.959
20091326SHAW-D
50/50
1.605
20064926PENNTECH
50/50
0.501
200643SENECA#2
50/50
1.711
20326126BLOSSBCT
50/50
2.096
238215AE2-248 C
Solar/Wind Harmer
6.572
238206AE2-263_GEN
Solar/Wind Harmer
7.672
972169AH1-667 GEN
Solar/Wind Harmer
4.143
203954AE2-126 C
Solar/Wind Harmer
1.249
238183AE2-316 GEN
Solar/Wind Harmer
6.049
970713AG2-456 GEN
Solar/Wind Harmer
7.919
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
959471AF2-238 GEN
Solar/Wind Harmer
0.485
970337AG2-221 GEN
Solar/Wind Harmer
1.605
970511AG2-327 GEN
Solar/Wind Harmer
0.747
20335026MILZ1-092
Adder
1.625
944411AF1-106 GEN
Solar/Wind Harmer
1.497
20094526CT_V3-030
Solar/Wind Harmer
0.481
203835AF1-098 GEN
Solar/Wind Harmer
1.627
20084926LAKVU GN
Adder
0.1
971183AH1-050 GEN
Solar/Wind Harmer
2.303
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
6.109
203860AG1-193 C
Solar/Wind Harmer
0.158
961971AG1-040 GEN
Solar/Wind Harmer
0.31
970267AG2-176 GEN
Solar/Wind Harmer
7.516
971279AH1-102 GEN
Solar/Wind Harmer
4.002
20082826HNSMLK 1
Adder
2.764
20083026HNSMLK 3
Adder
2.764
964201AG1-281 GEN
Solar/Wind Harmer
0.28
209067AE2-060 GEN
Solar/Wind Helper
0.05
200642SENECA#1
50/50
1.834
203855AF2-088 C
Solar/Wind Harmer
0.453
965121AG1-377 GEN
Solar/Wind Harmer
3.568
203804AE2-113_GEN
Solar/Wind Harmer
6.683
20090526Q36
Solar/Wind Harmer
2.115
203993AD2-133_GEN1
Solar/Wind Harmer
2.115
940863AE2-074 GEN
Solar/Wind Harmer
1.63
970555AG2-356 GEN
Solar/Wind Harmer
1.605
20091526CHSTN_FL
Solar/Wind Harmer
0.63
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
4.216
970663AG2-429 GEN
Solar/Wind Harmer
0.686
203846AF2-130 C
Solar/Wind Harmer
0.343
20334726NME_Y1-047
Adder
1.345
970677AG2-438 GEN
Solar/Wind Harmer
0.573
966771AG1-548 GEN
Solar/Wind Harmer
8.375
966771AG1-548 GEN
Solar/Wind Harmer
1.623
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.764
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.037
20083826HOMER C2
Adder
30.263
203850AG1-041 C
Solar/Wind Harmer
0.516
20083726HOMER C1
Adder
22.45
203975AE1-071-GEN
Solar/Wind Helper
2.84
959381AF2-229 GEN
Solar/Wind Helper
0.284
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.942
216419AE2-001 C
Solar/Wind Harmer
7.964
238217AF1-153 C O1
Solar/Wind Harmer
1.186
203952AE2-129 C
Solar/Wind Harmer
1.081
203946AE2-131 C
Solar/Wind Harmer
1.079
962411AG1-090 GEN
Solar/Wind Harmer
16.949
203853AF1-134 C O1
Solar/Wind Harmer
0.979
946381AF1-302 GEN
Solar/Wind Harmer
3.027
972075AH1-587 GEN
Solar/Wind Harmer
25.572
970305AG2-200 GEN
Solar/Wind Harmer
2.097
972077AH1-588 GEN
Solar/Wind Harmer
23.758
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
7.919
970313AG2-206 GEN
Solar/Wind Harmer
3.587
20398826ARMNA MT
Solar/Wind Harmer
1.728
203859AF2-294 C
Solar/Wind Harmer
1.087
203848AF2-166 C
Solar/Wind Harmer
1.2
203963AG1-253 GEN
Solar/Wind Harmer
0.235
203979AG1-198 GEN
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.147
203947AF1-006 C
Solar/Wind Harmer
0.298
971931AH1-490 GEN
Solar/Wind Harmer
1.032
203980AG1-197 GEN
Solar/Wind Harmer
0.231
971441AH1-212 GEN
Solar/Wind Harmer
1.006
203940AF1-140 C
Solar/Wind Harmer
0.231
946071AF1-272 GEN
Solar/Wind Harmer
1.498
20390526W1-045 C
Solar/Wind Helper
0.279
209137AF2-361 C
Solar/Wind Helper
0.847
200644SENECA#3
50/50
0.235
20120126WRREN CT
50/50
7.034
20335126GROZ1-110
50/50
2.565
20335226CANZ2-011
50/50
2.493
238202AE2-262_GEN
Solar/Wind Harmer
8.232
971627AH1-313 GEN
Solar/Wind Harmer
32.276
203854AF2-039 C
Solar/Wind Harmer
0.941
965131AG1-378 GEN
Solar/Wind Harmer
3.568
960051AF2-296 GEN
Solar/Wind Harmer
3.237
203818AF1-086 GEN
Solar/Wind Harmer
2.84
971703AH1-357 GEN
Solar/Wind Harmer
1.98
971707AH1-359 GEN
Solar/Wind Harmer
1.98
941421AE2-139 GEN
Solar/Wind Harmer
2.682
20334926Z1-069 C
Solar/Wind Harmer
1.801
972271AH1-720 GEN
Adder
5.198
970335AG2-220 GEN
Solar/Wind Harmer
2.316
971127AH1-005 GEN
Solar/Wind Harmer
1.494
20328326MANOR_T86
Adder
0.106
944411AF1-106 GEN
Solar/Wind Harmer
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.32
238219AF1-167 C
Solar/Wind Harmer
0.871
945751AF1-240 GEN
Solar/Wind Harmer
1.006
203932AE1-123
Adder
1.228
203948AG1-140 C
Solar/Wind Harmer
0.154
959441AF2-235 GEN
Solar/Wind Harmer
0.174
200917MEHOOPANY_G
Solar/Wind Harmer
2.002
957161AF2-010 GEN
Solar/Wind Harmer
4.415
203830AF1-094 GEN
Solar/Wind Harmer
0.347
20084926LAKVU GN
Adder
0.1
203856AF2-165 C
Solar/Wind Harmer
0.68
971185AH1-051 GEN
Solar/Wind Harmer
1.382
971355AH1-158 GEN
Solar/Wind Harmer
1.607
970647AG2-420 GEN
Solar/Wind Harmer
1.119
203962AF1-287 GEN
Solar/Wind Harmer
1.055
962511AG1-100 GEN
Solar/Wind Harmer
0.312
971541AH1-268 GEN
Solar/Wind Harmer
1.703
20082926HNSMLK 2
Adder
2.764
20083126HNSMLK 4
Adder
2.764
970679AG2-439 GEN
Solar/Wind Harmer
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.318
WECLTFEXP_WEC->PJM
CLTF
0.194
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.516
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.368
LAGNLTFEXP_LAGN->PJM
CLTF
0.686
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.243
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.336
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0310-C_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0310-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.54 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:811.17
MW Contribution:1.96
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
38.96
20091326SHAW-D
50/50
1.593
20064926PENNTECH
50/50
0.499
200643SENECA#2
50/50
1.703
238215AE2-248 C
Solar/Wind Harmer
6.616
238206AE2-263_GEN
Solar/Wind Harmer
7.704
972169AH1-667 GEN
Solar/Wind Harmer
4.11
203954AE2-126 C
Solar/Wind Harmer
1.242
238183AE2-316 GEN
Solar/Wind Harmer
6.03
970713AG2-456 GEN
Solar/Wind Harmer
7.856
971705AH1-358 GEN
Solar/Wind Harmer
2.284
971709AH1-360 GEN
Solar/Wind Harmer
2.284
20326126BLOSSBCT
Adder
1.966
959471AF2-238 GEN
Solar/Wind Harmer
0.483
970337AG2-221 GEN
Solar/Wind Harmer
1.598
970511AG2-327 GEN
Solar/Wind Harmer
0.744
20335026MILZ1-092
Adder
1.615
944411AF1-106 GEN
Solar/Wind Harmer
1.488
203835AF1-098 GEN
Solar/Wind Harmer
1.611
20094526CT_V3-030
Solar/Wind Harmer
0.449
20084926LAKVU GN
Adder
0.099
971183AH1-050 GEN
Solar/Wind Harmer
2.265
970647AG2-420 GEN
Solar/Wind Harmer
0.128
203813AE2-344_GEN
Solar/Wind Harmer
6.031
203860AG1-193 C
Solar/Wind Harmer
0.155
961971AG1-040 GEN
Solar/Wind Harmer
0.305
970267AG2-176 GEN
Solar/Wind Harmer
7.4
971279AH1-102 GEN
Solar/Wind Harmer
3.801
20082826HNSMLK 1
Adder
2.71
20083026HNSMLK 3
Adder
2.71
964391AG1-301 GEN
Solar/Wind Helper
0.403
209067AE2-060 GEN
Solar/Wind Helper
0.049
200642SENECA#1
50/50
1.826
203855AF2-088 C
Solar/Wind Harmer
0.449
965121AG1-377 GEN
Solar/Wind Harmer
3.408
203804AE2-113_GEN
Solar/Wind Harmer
6.65
20090526Q36
Solar/Wind Harmer
1.912
203993AD2-133_GEN1
Solar/Wind Harmer
1.912
940863AE2-074 GEN
Solar/Wind Harmer
1.617
970555AG2-356 GEN
Solar/Wind Harmer
1.598
203926AA2-133 GEN
Adder
1.549
20091526CHSTN_FL
Solar/Wind Harmer
0.535
970663AG2-429 GEN
Solar/Wind Harmer
4.156
970663AG2-429 GEN
Solar/Wind Harmer
0.676
203846AF2-130 C
Solar/Wind Harmer
0.337
20334726NME_Y1-047
Adder
1.345
20084926LAKVU GN
Adder
0.112
966771AG1-548 GEN
Solar/Wind Harmer
8.271
966771AG1-548 GEN
Solar/Wind Harmer
1.603
970677AG2-438 GEN
Solar/Wind Harmer
0.566
20083226HNSMLK 5
Adder
2.71
20390726Y2-042
Adder
1.078
20083926HOMER C3
Adder
31.006
20083826HOMER C2
Adder
29.289
20083726HOMER C1
Adder
21.198
203975AE1-071-GEN
Solar/Wind Helper
2.759
959381AF2-229 GEN
Solar/Wind Helper
0.276
941231AE2-117 GEN
Solar/Wind Helper
0.328
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.935
216419AE2-001 C
Solar/Wind Harmer
8.016
238217AF1-153 C O1
Solar/Wind Harmer
1.184
203952AE2-129 C
Solar/Wind Harmer
1.032
203946AE2-131 C
Solar/Wind Harmer
1.03
962411AG1-090 GEN
Solar/Wind Harmer
16.189
203853AF1-134 C O1
Solar/Wind Harmer
0.966
946381AF1-302 GEN
Solar/Wind Harmer
3.017
972075AH1-587 GEN
Solar/Wind Harmer
25.427
970305AG2-200 GEN
Solar/Wind Harmer
2.085
972077AH1-588 GEN
Solar/Wind Harmer
23.567
972079AH1-589 GEN
Solar/Wind Harmer
19.411
970715AG2-457 GEN
Solar/Wind Harmer
7.856
970313AG2-206 GEN
Solar/Wind Harmer
3.572
20398826ARMNA MT
Solar/Wind Harmer
1.717
203859AF2-294 C
Solar/Wind Harmer
1.081
203848AF2-166 C
Solar/Wind Harmer
1.18
203963AG1-253 GEN
Solar/Wind Harmer
0.233
203979AG1-198 GEN
Solar/Wind Harmer
0.206
971933AH1-491 GEN
Solar/Wind Harmer
1.132
203947AF1-006 C
Solar/Wind Harmer
0.295
971931AH1-490 GEN
Solar/Wind Harmer
1.019
203980AG1-197 GEN
Solar/Wind Harmer
0.228
971441AH1-212 GEN
Solar/Wind Harmer
0.878
946071AF1-272 GEN
Solar/Wind Harmer
1.439
20390526W1-045 C
Solar/Wind Helper
0.271
209137AF2-361 C
Solar/Wind Helper
0.822
200644SENECA#3
50/50
0.234
20120126WRREN CT
50/50
6.995
20335126GROZ1-110
50/50
2.562
20335226CANZ2-011
50/50
2.491
238202AE2-262_GEN
Solar/Wind Harmer
8.266
971627AH1-313 GEN
Solar/Wind Harmer
32.41
203854AF2-039 C
Solar/Wind Harmer
0.934
965131AG1-378 GEN
Solar/Wind Harmer
3.408
960051AF2-296 GEN
Solar/Wind Harmer
3.196
203818AF1-086 GEN
Solar/Wind Harmer
2.783
971703AH1-357 GEN
Solar/Wind Harmer
1.964
971707AH1-359 GEN
Solar/Wind Harmer
1.964
941421AE2-139 GEN
Solar/Wind Harmer
2.683
20334926Z1-069 C
Solar/Wind Harmer
1.787
972271AH1-720 GEN
Adder
5.198
20328326MANOR_T86
Adder
0.106
970335AG2-220 GEN
Solar/Wind Harmer
2.306
971127AH1-005 GEN
Solar/Wind Harmer
1.488
944411AF1-106 GEN
Solar/Wind Harmer
0.16
970899AG2-561 GEN
Solar/Wind Harmer
1.277
238219AF1-167 C
Solar/Wind Harmer
0.859
945751AF1-240 GEN
Solar/Wind Harmer
0.982
203932AE1-123
Adder
1.208
203948AG1-140 C
Solar/Wind Harmer
0.152
200917MEHOOPANY_G
Solar/Wind Harmer
2.003
20084926LAKVU GN
Adder
0.099
959441AF2-235 GEN
Solar/Wind Harmer
0.171
203830AF1-094 GEN
Solar/Wind Harmer
0.343
957161AF2-010 GEN
Solar/Wind Harmer
4.359
203856AF2-165 C
Solar/Wind Harmer
0.669
971185AH1-051 GEN
Solar/Wind Harmer
1.359
971355AH1-158 GEN
Solar/Wind Harmer
1.58
970647AG2-420 GEN
Solar/Wind Harmer
1.101
203962AF1-287 GEN
Solar/Wind Harmer
1.041
962511AG1-100 GEN
Solar/Wind Harmer
0.308
971541AH1-268 GEN
Solar/Wind Harmer
1.618
20082926HNSMLK 2
Adder
2.71
20083126HNSMLK 4
Adder
2.71
970679AG2-439 GEN
Solar/Wind Harmer
0.451
LGEELTFEXP_LGEE->PJM
CLTF
0.308
WECLTFEXP_WEC->PJM
CLTF
0.188
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.603
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.19
LAGNLTFEXP_LAGN->PJM
CLTF
0.663
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.227
TVALTFEXP_TVA->PJM
CLTF
0.32
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.29
MECLTFEXP_MEC->PJM
CLTF
0.765
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1185-2_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1185-2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.1 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:753.36
MW Contribution:3.28
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
3.241
20066526SHAWVL 3
50/50
3.218
20071526SHAWVL 1
50/50
2.108
216419AE2-001 C
Solar/Wind Harmer
8.661
238217AF1-153 C O1
Solar/Wind Harmer
1.315
972075AH1-587 GEN
Solar/Wind Harmer
36.414
203952AE2-129 C
Solar/Wind Harmer
1.079
203946AE2-131 C
Solar/Wind Harmer
1.078
962411AG1-090 GEN
Solar/Wind Harmer
16.93
203853AF1-134 C O1
Solar/Wind Harmer
1.01
972077AH1-588 GEN
Solar/Wind Harmer
39.406
972079AH1-589 GEN
Solar/Wind Harmer
32.457
970715AG2-457 GEN
Solar/Wind Harmer
13.135
946381AF1-302 GEN
Solar/Wind Harmer
3.272
970305AG2-200 GEN
Solar/Wind Harmer
2.665
970313AG2-206 GEN
Solar/Wind Harmer
3.516
20398826ARMNA MT
Solar/Wind Harmer
1.676
203963AG1-253 GEN
Solar/Wind Harmer
0.242
203979AG1-198 GEN
Solar/Wind Harmer
0.215
971933AH1-491 GEN
Solar/Wind Harmer
1.185
203848AF2-166 C
Solar/Wind Harmer
1.124
203947AF1-006 C
Solar/Wind Harmer
0.314
203859AF2-294 C
Solar/Wind Harmer
0.923
971931AH1-490 GEN
Solar/Wind Harmer
1.051
203980AG1-197 GEN
Solar/Wind Harmer
0.229
20390526W1-045 C
Solar/Wind Helper
0.217
200642SENECA#1
50/50
2.392
203855AF2-088 C
Solar/Wind Harmer
0.488
203804AE2-113_GEN
Solar/Wind Harmer
9.081
965121AG1-377 GEN
Solar/Wind Harmer
3.564
940863AE2-074 GEN
Solar/Wind Harmer
2.443
20090526Q36
Solar/Wind Harmer
1.883
203993AD2-133_GEN1
Solar/Wind Harmer
1.883
970555AG2-356 GEN
Solar/Wind Harmer
1.59
203926AA2-133 GEN
Adder
1.545
20084926LAKVU GN
Adder
0.121
966771AG1-548 GEN
Solar/Wind Harmer
8.693
966771AG1-548 GEN
Solar/Wind Harmer
1.685
970677AG2-438 GEN
Solar/Wind Harmer
0.593
20334726NME_Y1-047
Adder
1.339
970663AG2-429 GEN
Solar/Wind Harmer
3.915
970663AG2-429 GEN
Solar/Wind Harmer
0.637
203846AF2-130 C
Solar/Wind Harmer
0.321
20390726Y2-042
Adder
1.098
20083926HOMER C3
Adder
17.455
20083826HOMER C2
Adder
16.488
20083726HOMER C1
Adder
8.411
203975AE1-071-GEN
Solar/Wind Helper
2.192
959381AF2-229 GEN
Solar/Wind Helper
0.221
941231AE2-117 GEN
Solar/Wind Helper
0.226
200644SENECA#3
50/50
0.307
20120126WRREN CT
50/50
8.939
20335126GROZ1-110
50/50
2.666
20335226CANZ2-011
50/50
2.591
238202AE2-262_GEN
Solar/Wind Harmer
8.982
971627AH1-313 GEN
Solar/Wind Harmer
35.218
203854AF2-039 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
3.564
960051AF2-296 GEN
Solar/Wind Harmer
3.339
971703AH1-357 GEN
Solar/Wind Harmer
3.284
971707AH1-359 GEN
Solar/Wind Harmer
3.284
20334926Z1-069 C
Solar/Wind Harmer
2.405
203818AF1-086 GEN
Solar/Wind Harmer
2.731
941421AE2-139 GEN
Solar/Wind Harmer
2.765
972271AH1-720 GEN
Adder
5.301
20328326MANOR_T86
Adder
0.106
970335AG2-220 GEN
Solar/Wind Harmer
2.269
971127AH1-005 GEN
Solar/Wind Harmer
1.464
20084926LAKVU GN
Adder
0.108
238219AF1-167 C
Solar/Wind Harmer
0.828
944411AF1-106 GEN
Solar/Wind Harmer
0.138
203948AG1-140 C
Solar/Wind Harmer
0.159
203830AF1-094 GEN
Solar/Wind Harmer
0.359
957161AF2-010 GEN
Solar/Wind Harmer
4.552
203932AE1-123
Adder
1.142
200917MEHOOPANY_G
Solar/Wind Harmer
1.993
945751AF1-240 GEN
Solar/Wind Harmer
0.887
959441AF2-235 GEN
Solar/Wind Harmer
0.169
970899AG2-561 GEN
Solar/Wind Harmer
1.087
203962AF1-287 GEN
Solar/Wind Harmer
1.084
203856AF2-165 C
Solar/Wind Harmer
0.64
971185AH1-051 GEN
Solar/Wind Harmer
1.291
971355AH1-158 GEN
Solar/Wind Harmer
1.501
962511AG1-100 GEN
Solar/Wind Harmer
0.318
970647AG2-420 GEN
Solar/Wind Harmer
1.05
970679AG2-439 GEN
Solar/Wind Harmer
0.459
20072226SHAWVL 2
50/50
42.536
20091326SHAW-D
50/50
1.729
20064926PENNTECH
50/50
0.589
200643SENECA#2
50/50
2.232
20326126BLOSSBCT
50/50
2.16
238215AE2-248 C
Solar/Wind Harmer
7.143
238206AE2-263_GEN
Solar/Wind Harmer
8.371
972169AH1-667 GEN
Solar/Wind Harmer
4.462
203954AE2-126 C
Solar/Wind Harmer
1.402
970713AG2-456 GEN
Solar/Wind Harmer
13.135
971705AH1-358 GEN
Solar/Wind Harmer
3.818
971709AH1-360 GEN
Solar/Wind Harmer
3.818
238183AE2-316 GEN
Solar/Wind Harmer
6.538
959471AF2-238 GEN
Solar/Wind Harmer
0.481
970337AG2-221 GEN
Solar/Wind Harmer
1.59
203835AF1-098 GEN
Solar/Wind Harmer
1.841
970511AG2-327 GEN
Solar/Wind Harmer
0.733
20084926LAKVU GN
Adder
0.108
20335026MILZ1-092
Adder
1.396
944411AF1-106 GEN
Solar/Wind Harmer
1.286
203813AE2-344_GEN
Solar/Wind Harmer
6.269
971183AH1-050 GEN
Solar/Wind Harmer
2.152
970647AG2-420 GEN
Solar/Wind Harmer
0.122
961971AG1-040 GEN
Solar/Wind Harmer
0.309
203860AG1-193 C
Solar/Wind Harmer
0.147
970267AG2-176 GEN
Solar/Wind Harmer
7.222
20094526CT_V3-030
Solar/Wind Harmer
0.335
964391AG1-301 GEN
Solar/Wind Helper
0.289
LGEELTFEXP_LGEE->PJM
CLTF
0.223
WECLTFEXP_WEC->PJM
CLTF
0.14
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.653
LAGNLTFEXP_LAGN->PJM
CLTF
0.445
TVALTFEXP_TVA->PJM
CLTF
0.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.874
MECLTFEXP_MEC->PJM
CLTF
0.561
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.03 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:728.44
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.242
20335126GROZ1-110
50/50
2.687
20335226CANZ2-011
50/50
2.612
20120126WRREN CT
50/50
7.199
238202AE2-262_GEN
Solar/Wind Harmer
8.76
971627AH1-313 GEN
Solar/Wind Harmer
34.347
203854AF2-039 C
Solar/Wind Harmer
0.974
965131AG1-378 GEN
Solar/Wind Harmer
3.438
960051AF2-296 GEN
Solar/Wind Harmer
3.246
203818AF1-086 GEN
Solar/Wind Harmer
2.706
971703AH1-357 GEN
Solar/Wind Harmer
1.99
971707AH1-359 GEN
Solar/Wind Harmer
1.99
941421AE2-139 GEN
Solar/Wind Harmer
2.835
20334926Z1-069 C
Solar/Wind Harmer
1.809
972271AH1-720 GEN
Adder
5.494
20328326MANOR_T86
Adder
0.111
970335AG2-220 GEN
Solar/Wind Harmer
2.382
971127AH1-005 GEN
Solar/Wind Harmer
1.537
944411AF1-106 GEN
Solar/Wind Harmer
0.163
238219AF1-167 C
Solar/Wind Harmer
0.932
203932AE1-123
Adder
1.248
200917MEHOOPANY_G
Solar/Wind Harmer
2.134
945751AF1-240 GEN
Solar/Wind Harmer
0.951
203948AG1-140 C
Solar/Wind Harmer
0.153
959441AF2-235 GEN
Solar/Wind Harmer
0.174
957161AF2-010 GEN
Solar/Wind Harmer
4.408
203856AF2-165 C
Solar/Wind Harmer
0.682
203830AF1-094 GEN
Solar/Wind Harmer
0.347
971185AH1-051 GEN
Solar/Wind Harmer
1.388
971355AH1-158 GEN
Solar/Wind Harmer
1.614
20084926LAKVU GN
Adder
0.1
970899AG2-561 GEN
Solar/Wind Harmer
1.133
970647AG2-420 GEN
Solar/Wind Harmer
1.122
203962AF1-287 GEN
Solar/Wind Harmer
1.045
962511AG1-100 GEN
Solar/Wind Harmer
0.309
970679AG2-439 GEN
Solar/Wind Harmer
0.489
20082926HNSMLK 2
Adder
2.696
20083126HNSMLK 4
Adder
2.696
20066626SHAWVL 4
50/50
3.13
20066526SHAWVL 3
50/50
3.107
20071526SHAWVL 1
50/50
2.031
216419AE2-001 C
Solar/Wind Harmer
8.519
238217AF1-153 C O1
Solar/Wind Harmer
1.249
203952AE2-129 C
Solar/Wind Harmer
1.041
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.333
203853AF1-134 C O1
Solar/Wind Harmer
0.981
946381AF1-302 GEN
Solar/Wind Harmer
3.218
972075AH1-587 GEN
Solar/Wind Harmer
26.166
970305AG2-200 GEN
Solar/Wind Harmer
2.146
972077AH1-588 GEN
Solar/Wind Harmer
23.884
972079AH1-589 GEN
Solar/Wind Harmer
19.672
970715AG2-457 GEN
Solar/Wind Harmer
7.961
970313AG2-206 GEN
Solar/Wind Harmer
3.691
20398826ARMNA MT
Solar/Wind Harmer
1.756
203859AF2-294 C
Solar/Wind Harmer
1.109
203848AF2-166 C
Solar/Wind Harmer
1.213
203963AG1-253 GEN
Solar/Wind Harmer
0.234
203979AG1-198 GEN
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.145
203947AF1-006 C
Solar/Wind Harmer
0.296
971931AH1-490 GEN
Solar/Wind Harmer
1.021
203980AG1-197 GEN
Solar/Wind Harmer
0.228
20390526W1-045 C
Solar/Wind Helper
0.217
20072226SHAWVL 2
50/50
41.077
20091326SHAW-D
50/50
1.662
20064926PENNTECH
50/50
0.522
200643SENECA#2
50/50
1.759
20326126BLOSSBCT
50/50
2.147
238215AE2-248 C
Solar/Wind Harmer
7.035
238206AE2-263_GEN
Solar/Wind Harmer
8.164
972169AH1-667 GEN
Solar/Wind Harmer
4.289
203954AE2-126 C
Solar/Wind Harmer
1.297
238183AE2-316 GEN
Solar/Wind Harmer
6.431
970713AG2-456 GEN
Solar/Wind Harmer
7.961
971705AH1-358 GEN
Solar/Wind Harmer
2.314
971709AH1-360 GEN
Solar/Wind Harmer
2.314
959471AF2-238 GEN
Solar/Wind Harmer
0.498
970337AG2-221 GEN
Solar/Wind Harmer
1.649
970511AG2-327 GEN
Solar/Wind Harmer
0.769
20335026MILZ1-092
Adder
1.65
944411AF1-106 GEN
Solar/Wind Harmer
1.52
203835AF1-098 GEN
Solar/Wind Harmer
1.634
971183AH1-050 GEN
Solar/Wind Harmer
2.313
20084926LAKVU GN
Adder
0.1
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
6.048
203860AG1-193 C
Solar/Wind Harmer
0.157
961971AG1-040 GEN
Solar/Wind Harmer
0.306
970267AG2-176 GEN
Solar/Wind Harmer
7.416
20094526CT_V3-030
Solar/Wind Harmer
0.348
20082826HNSMLK 1
Adder
2.696
20083026HNSMLK 3
Adder
2.696
964391AG1-301 GEN
Solar/Wind Helper
0.289
200642SENECA#1
50/50
1.886
203855AF2-088 C
Solar/Wind Harmer
0.469
965121AG1-377 GEN
Solar/Wind Harmer
3.438
203804AE2-113_GEN
Solar/Wind Harmer
6.873
20090526Q36
Solar/Wind Harmer
1.827
203993AD2-133_GEN1
Solar/Wind Harmer
1.827
940863AE2-074 GEN
Solar/Wind Harmer
1.638
970555AG2-356 GEN
Solar/Wind Harmer
1.649
203926AA2-133 GEN
Adder
1.638
970663AG2-429 GEN
Solar/Wind Harmer
4.526
970663AG2-429 GEN
Solar/Wind Harmer
0.737
20334726NME_Y1-047
Adder
1.433
203846AF2-130 C
Solar/Wind Harmer
0.347
970677AG2-438 GEN
Solar/Wind Harmer
0.572
966771AG1-548 GEN
Solar/Wind Harmer
8.357
966771AG1-548 GEN
Solar/Wind Harmer
1.62
20084926LAKVU GN
Adder
0.112
20390726Y2-042
Adder
1.17
20083226HNSMLK 5
Adder
2.696
20083926HOMER C3
Adder
26.77
20083826HOMER C2
Adder
25.287
20083726HOMER C1
Adder
13.472
203975AE1-071-GEN
Solar/Wind Helper
2.207
959381AF2-229 GEN
Solar/Wind Helper
0.222
941231AE2-117 GEN
Solar/Wind Helper
0.227
LGEELTFEXP_LGEE->PJM
CLTF
0.211
WECLTFEXP_WEC->PJM
CLTF
0.133
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.445
LAGNLTFEXP_LAGN->PJM
CLTF
0.418
TVALTFEXP_TVA->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.822
MECLTFEXP_MEC->PJM
CLTF
0.531
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-2_PN-230-009_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-230-009_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.05 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:722.47
MW Contribution:2.23
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
2.244
203855AF2-088 C
Solar/Wind Harmer
0.48
965121AG1-377 GEN
Solar/Wind Harmer
3.521
203804AE2-113_GEN
Solar/Wind Harmer
7.351
20090526Q36
Solar/Wind Harmer
1.875
203993AD2-133_GEN1
Solar/Wind Harmer
1.875
940863AE2-074 GEN
Solar/Wind Harmer
1.774
970555AG2-356 GEN
Solar/Wind Harmer
1.694
203926AA2-133 GEN
Adder
1.683
20334726NME_Y1-047
Adder
1.475
970663AG2-429 GEN
Solar/Wind Harmer
3.938
970663AG2-429 GEN
Solar/Wind Harmer
0.641
203846AF2-130 C
Solar/Wind Harmer
0.302
20390726Y2-042
Adder
1.208
970677AG2-438 GEN
Solar/Wind Harmer
0.443
966771AG1-548 GEN
Solar/Wind Harmer
6.445
966771AG1-548 GEN
Solar/Wind Harmer
1.249
20083926HOMER C3
Adder
25.526
20083826HOMER C2
Adder
24.112
20083726HOMER C1
Adder
13.05
203975AE1-071-GEN
Solar/Wind Helper
2.177
959381AF2-229 GEN
Solar/Wind Helper
0.219
200644SENECA#3
50/50
0.288
20120126WRREN CT
50/50
9.127
20335126GROZ1-110
50/50
2.755
20335226CANZ2-011
50/50
2.678
238202AE2-262_GEN
Solar/Wind Harmer
8.896
971627AH1-313 GEN
Solar/Wind Harmer
34.88
203854AF2-039 C
Solar/Wind Harmer
0.996
965131AG1-378 GEN
Solar/Wind Harmer
3.521
960051AF2-296 GEN
Solar/Wind Harmer
3.305
971703AH1-357 GEN
Solar/Wind Harmer
2.235
971707AH1-359 GEN
Solar/Wind Harmer
2.235
203818AF1-086 GEN
Solar/Wind Harmer
2.733
941421AE2-139 GEN
Solar/Wind Harmer
2.907
20334926Z1-069 C
Solar/Wind Harmer
1.93
972271AH1-720 GEN
Adder
5.638
20328326MANOR_T86
Adder
0.114
970335AG2-220 GEN
Solar/Wind Harmer
2.448
971127AH1-005 GEN
Solar/Wind Harmer
1.579
944411AF1-106 GEN
Solar/Wind Harmer
0.167
200917MEHOOPANY_G
Solar/Wind Harmer
2.195
238219AF1-167 C
Solar/Wind Harmer
0.825
203932AE1-123
Adder
1.111
945751AF1-240 GEN
Solar/Wind Harmer
0.885
970899AG2-561 GEN
Solar/Wind Harmer
1.12
970679AG2-439 GEN
Solar/Wind Harmer
0.505
971185AH1-051 GEN
Solar/Wind Harmer
1.186
971355AH1-158 GEN
Solar/Wind Harmer
1.379
203856AF2-165 C
Solar/Wind Harmer
0.58
959441AF2-235 GEN
Solar/Wind Harmer
0.144
970647AG2-420 GEN
Solar/Wind Harmer
0.949
957161AF2-010 GEN
Solar/Wind Harmer
3.426
203830AF1-094 GEN
Solar/Wind Harmer
0.269
203948AG1-140 C
Solar/Wind Harmer
0.115
20066626SHAWVL 4
50/50
3.195
20066526SHAWVL 3
50/50
3.172
20071526SHAWVL 1
50/50
2.075
216419AE2-001 C
Solar/Wind Harmer
8.61
238217AF1-153 C O1
Solar/Wind Harmer
1.283
203952AE2-129 C
Solar/Wind Harmer
1.066
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.724
203853AF1-134 C O1
Solar/Wind Harmer
0.999
946381AF1-302 GEN
Solar/Wind Harmer
3.211
972075AH1-587 GEN
Solar/Wind Harmer
28.152
970305AG2-200 GEN
Solar/Wind Harmer
2.721
972077AH1-588 GEN
Solar/Wind Harmer
26.825
972079AH1-589 GEN
Solar/Wind Harmer
22.094
970715AG2-457 GEN
Solar/Wind Harmer
8.942
970313AG2-206 GEN
Solar/Wind Harmer
3.793
20398826ARMNA MT
Solar/Wind Harmer
1.806
203859AF2-294 C
Solar/Wind Harmer
1.136
203848AF2-166 C
Solar/Wind Harmer
1.057
203979AG1-198 GEN
Solar/Wind Harmer
0.161
971933AH1-491 GEN
Solar/Wind Harmer
0.887
203963AG1-253 GEN
Solar/Wind Harmer
0.176
20390526W1-045 C
Solar/Wind Helper
0.214
20072226SHAWVL 2
50/50
41.926
20091326SHAW-D
50/50
1.7
20064926PENNTECH
50/50
0.55
200643SENECA#2
50/50
2.094
20326126BLOSSBCT
50/50
2.213
238215AE2-248 C
Solar/Wind Harmer
7.105
238206AE2-263_GEN
Solar/Wind Harmer
8.291
972169AH1-667 GEN
Solar/Wind Harmer
4.387
203954AE2-126 C
Solar/Wind Harmer
1.344
238183AE2-316 GEN
Solar/Wind Harmer
6.417
970713AG2-456 GEN
Solar/Wind Harmer
8.942
971705AH1-358 GEN
Solar/Wind Harmer
2.599
971709AH1-360 GEN
Solar/Wind Harmer
2.599
959471AF2-238 GEN
Solar/Wind Harmer
0.512
970337AG2-221 GEN
Solar/Wind Harmer
1.694
970511AG2-327 GEN
Solar/Wind Harmer
0.79
20335026MILZ1-092
Adder
1.689
944411AF1-106 GEN
Solar/Wind Harmer
1.556
203835AF1-098 GEN
Solar/Wind Harmer
1.495
20094526CT_V3-030
Solar/Wind Harmer
0.35
971183AH1-050 GEN
Solar/Wind Harmer
1.977
970647AG2-420 GEN
Solar/Wind Harmer
0.11
964391AG1-301 GEN
Solar/Wind Helper
0.281
LGEELTFEXP_LGEE->PJM
CLTF
0.177
WECLTFEXP_WEC->PJM
CLTF
0.112
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.046
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.834
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.336
TVALTFEXP_TVA->PJM
CLTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.873
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.666
MECLTFEXP_MEC->PJM
CLTF
0.444
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-020T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-020T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.04 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:716.26
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.971
203855AF2-088 C
Solar/Wind Harmer
0.489
965121AG1-377 GEN
Solar/Wind Harmer
3.588
203804AE2-113_GEN
Solar/Wind Harmer
7.209
20090526Q36
Solar/Wind Harmer
1.908
203993AD2-133_GEN1
Solar/Wind Harmer
1.908
940863AE2-074 GEN
Solar/Wind Harmer
1.672
970555AG2-356 GEN
Solar/Wind Harmer
1.676
203926AA2-133 GEN
Adder
1.681
20334726NME_Y1-047
Adder
1.472
20084926LAKVU GN
Adder
0.109
966771AG1-548 GEN
Solar/Wind Harmer
7.849
966771AG1-548 GEN
Solar/Wind Harmer
1.521
970677AG2-438 GEN
Solar/Wind Harmer
0.536
203846AF2-130 C
Solar/Wind Harmer
0.295
20390726Y2-042
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
3.406
970663AG2-429 GEN
Solar/Wind Harmer
0.555
20083926HOMER C3
Adder
22.907
20083826HOMER C2
Adder
21.638
20083726HOMER C1
Adder
11.476
203975AE1-071-GEN
Solar/Wind Helper
2.164
959381AF2-229 GEN
Solar/Wind Helper
0.218
200644SENECA#3
50/50
0.253
20335126GROZ1-110
50/50
2.768
20335226CANZ2-011
50/50
2.691
20120126WRREN CT
50/50
7.448
238202AE2-262_GEN
Solar/Wind Harmer
9.041
971627AH1-313 GEN
Solar/Wind Harmer
35.448
203854AF2-039 C
Solar/Wind Harmer
1.016
965131AG1-378 GEN
Solar/Wind Harmer
3.588
960051AF2-296 GEN
Solar/Wind Harmer
3.352
203818AF1-086 GEN
Solar/Wind Harmer
2.747
971703AH1-357 GEN
Solar/Wind Harmer
2.039
971707AH1-359 GEN
Solar/Wind Harmer
2.039
941421AE2-139 GEN
Solar/Wind Harmer
2.924
20334926Z1-069 C
Solar/Wind Harmer
1.835
972271AH1-720 GEN
Adder
5.657
20328326MANOR_T86
Adder
0.114
970335AG2-220 GEN
Solar/Wind Harmer
2.418
971127AH1-005 GEN
Solar/Wind Harmer
1.56
944411AF1-106 GEN
Solar/Wind Harmer
0.165
20072226SHAWVL 2
50/50
42.823
20091326SHAW-D
50/50
1.733
20064926PENNTECH
50/50
0.555
200643SENECA#2
50/50
1.839
20326126BLOSSBCT
50/50
2.183
238215AE2-248 C
Solar/Wind Harmer
7.176
238206AE2-263_GEN
Solar/Wind Harmer
8.426
972169AH1-667 GEN
Solar/Wind Harmer
4.473
238183AE2-316 GEN
Solar/Wind Harmer
9.782
203954AE2-126 C
Solar/Wind Harmer
1.365
970713AG2-456 GEN
Solar/Wind Harmer
8.157
971705AH1-358 GEN
Solar/Wind Harmer
2.371
971709AH1-360 GEN
Solar/Wind Harmer
2.371
959471AF2-238 GEN
Solar/Wind Harmer
0.507
970337AG2-221 GEN
Solar/Wind Harmer
1.676
970511AG2-327 GEN
Solar/Wind Harmer
0.781
20335026MILZ1-092
Adder
1.662
944411AF1-106 GEN
Solar/Wind Harmer
1.531
203835AF1-098 GEN
Solar/Wind Harmer
1.615
20084926LAKVU GN
Adder
0.097
971183AH1-050 GEN
Solar/Wind Harmer
1.98
203813AE2-344_GEN
Solar/Wind Harmer
5.675
20094526CT_V3-030
Solar/Wind Harmer
0.346
970647AG2-420 GEN
Solar/Wind Harmer
0.112
961971AG1-040 GEN
Solar/Wind Harmer
0.281
203860AG1-193 C
Solar/Wind Harmer
0.135
970267AG2-176 GEN
Solar/Wind Harmer
6.624
964391AG1-301 GEN
Solar/Wind Helper
0.278
200917MEHOOPANY_G
Solar/Wind Harmer
2.191
203948AG1-140 C
Solar/Wind Harmer
0.149
238219AF1-167 C
Solar/Wind Harmer
0.751
20084926LAKVU GN
Adder
0.097
970899AG2-561 GEN
Solar/Wind Harmer
1.098
945751AF1-240 GEN
Solar/Wind Harmer
0.85
203830AF1-094 GEN
Solar/Wind Harmer
0.324
957161AF2-010 GEN
Solar/Wind Harmer
4.115
203932AE1-123
Adder
1.049
970679AG2-439 GEN
Solar/Wind Harmer
0.504
959441AF2-235 GEN
Solar/Wind Harmer
0.155
203856AF2-165 C
Solar/Wind Harmer
0.588
203962AF1-287 GEN
Solar/Wind Harmer
0.981
971185AH1-051 GEN
Solar/Wind Harmer
1.188
971355AH1-158 GEN
Solar/Wind Harmer
1.381
970647AG2-420 GEN
Solar/Wind Harmer
0.965
962511AG1-100 GEN
Solar/Wind Harmer
0.288
20066626SHAWVL 4
50/50
3.263
20066526SHAWVL 3
50/50
3.24
20071526SHAWVL 1
50/50
2.118
216419AE2-001 C
Solar/Wind Harmer
8.702
946381AF1-302 GEN
Solar/Wind Harmer
4.895
238217AF1-153 C O1
Solar/Wind Harmer
1.355
203952AE2-129 C
Solar/Wind Harmer
1.087
203946AE2-131 C
Solar/Wind Harmer
1.085
962411AG1-090 GEN
Solar/Wind Harmer
17.042
203853AF1-134 C O1
Solar/Wind Harmer
1.013
972075AH1-587 GEN
Solar/Wind Harmer
27.307
970305AG2-200 GEN
Solar/Wind Harmer
2.22
972077AH1-588 GEN
Solar/Wind Harmer
24.472
972079AH1-589 GEN
Solar/Wind Harmer
20.156
970715AG2-457 GEN
Solar/Wind Harmer
8.157
970313AG2-206 GEN
Solar/Wind Harmer
3.748
20398826ARMNA MT
Solar/Wind Harmer
1.771
203859AF2-294 C
Solar/Wind Harmer
1.116
203963AG1-253 GEN
Solar/Wind Harmer
0.227
203979AG1-198 GEN
Solar/Wind Harmer
0.195
971933AH1-491 GEN
Solar/Wind Harmer
1.071
203848AF2-166 C
Solar/Wind Harmer
1.032
203947AF1-006 C
Solar/Wind Harmer
0.283
971931AH1-490 GEN
Solar/Wind Harmer
0.953
203980AG1-197 GEN
Solar/Wind Harmer
0.209
20390526W1-045 C
Solar/Wind Helper
0.213
LGEELTFEXP_LGEE->PJM
CLTF
0.192
WECLTFEXP_WEC->PJM
CLTF
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.102
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.37
TVALTFEXP_TVA->PJM
CLTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.73
MECLTFEXP_MEC->PJM
CLTF
0.484
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-022_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-022_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.81 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:714.9
MW Contribution:2.02
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
3.323
20066526SHAWVL 3
50/50
3.299
20071526SHAWVL 1
50/50
2.213
216419AE2-001 C
Solar/Wind Harmer
8.741
203853AF1-134 C O1
Solar/Wind Harmer
1.611
238217AF1-153 C O1
Solar/Wind Harmer
1.297
203952AE2-129 C
Solar/Wind Harmer
1.165
203946AE2-131 C
Solar/Wind Harmer
1.163
962411AG1-090 GEN
Solar/Wind Harmer
18.267
946381AF1-302 GEN
Solar/Wind Harmer
3.228
972075AH1-587 GEN
Solar/Wind Harmer
27.127
970305AG2-200 GEN
Solar/Wind Harmer
2.19
972077AH1-588 GEN
Solar/Wind Harmer
24.234
972079AH1-589 GEN
Solar/Wind Harmer
19.96
970715AG2-457 GEN
Solar/Wind Harmer
8.078
970313AG2-206 GEN
Solar/Wind Harmer
3.756
20398826ARMNA MT
Solar/Wind Harmer
1.775
203859AF2-294 C
Solar/Wind Harmer
1.118
203963AG1-253 GEN
Solar/Wind Harmer
0.228
203979AG1-198 GEN
Solar/Wind Harmer
0.194
971933AH1-491 GEN
Solar/Wind Harmer
1.066
203947AF1-006 C
Solar/Wind Harmer
0.284
203848AF2-166 C
Solar/Wind Harmer
0.99
971931AH1-490 GEN
Solar/Wind Harmer
0.963
203980AG1-197 GEN
Solar/Wind Harmer
0.212
20390526W1-045 C
Solar/Wind Helper
0.213
200642SENECA#1
50/50
1.939
203855AF2-088 C
Solar/Wind Harmer
0.528
965121AG1-377 GEN
Solar/Wind Harmer
3.846
203804AE2-113_GEN
Solar/Wind Harmer
7.163
20090526Q36
Solar/Wind Harmer
2.029
203993AD2-133_GEN1
Solar/Wind Harmer
2.029
940863AE2-074 GEN
Solar/Wind Harmer
1.662
970555AG2-356 GEN
Solar/Wind Harmer
1.68
203926AA2-133 GEN
Adder
1.685
20334726NME_Y1-047
Adder
1.475
20084926LAKVU GN
Adder
0.109
970663AG2-429 GEN
Solar/Wind Harmer
3.757
970663AG2-429 GEN
Solar/Wind Harmer
0.612
966771AG1-548 GEN
Solar/Wind Harmer
7.82
966771AG1-548 GEN
Solar/Wind Harmer
1.516
970677AG2-438 GEN
Solar/Wind Harmer
0.533
20390726Y2-042
Adder
1.209
203846AF2-130 C
Solar/Wind Harmer
0.283
20083926HOMER C3
Adder
23.334
20083826HOMER C2
Adder
22.042
20083726HOMER C1
Adder
10.403
203975AE1-071-GEN
Solar/Wind Helper
2.161
959381AF2-229 GEN
Solar/Wind Helper
0.218
200644SENECA#3
50/50
0.249
20335126GROZ1-110
50/50
2.778
20335226CANZ2-011
50/50
2.7
20120126WRREN CT
50/50
7.346
238202AE2-262_GEN
Solar/Wind Harmer
9.082
971627AH1-313 GEN
Solar/Wind Harmer
35.61
203854AF2-039 C
Solar/Wind Harmer
1.096
960051AF2-296 GEN
Solar/Wind Harmer
5.329
203818AF1-086 GEN
Solar/Wind Harmer
6.782
965131AG1-378 GEN
Solar/Wind Harmer
3.846
971703AH1-357 GEN
Solar/Wind Harmer
2.019
971707AH1-359 GEN
Solar/Wind Harmer
2.019
941421AE2-139 GEN
Solar/Wind Harmer
2.934
20334926Z1-069 C
Solar/Wind Harmer
1.829
972271AH1-720 GEN
Adder
5.674
20328326MANOR_T86
Adder
0.115
970335AG2-220 GEN
Solar/Wind Harmer
2.423
971127AH1-005 GEN
Solar/Wind Harmer
1.564
944411AF1-106 GEN
Solar/Wind Harmer
0.165
200917MEHOOPANY_G
Solar/Wind Harmer
2.196
238219AF1-167 C
Solar/Wind Harmer
0.787
203948AG1-140 C
Solar/Wind Harmer
0.149
20084926LAKVU GN
Adder
0.097
203830AF1-094 GEN
Solar/Wind Harmer
0.323
957161AF2-010 GEN
Solar/Wind Harmer
4.094
970679AG2-439 GEN
Solar/Wind Harmer
0.505
203932AE1-123
Adder
0.992
959441AF2-235 GEN
Solar/Wind Harmer
0.152
203962AF1-287 GEN
Solar/Wind Harmer
0.99
203856AF2-165 C
Solar/Wind Harmer
0.574
962511AG1-100 GEN
Solar/Wind Harmer
0.291
971185AH1-051 GEN
Solar/Wind Harmer
1.159
971355AH1-158 GEN
Solar/Wind Harmer
1.348
970647AG2-420 GEN
Solar/Wind Harmer
0.948
20072226SHAWVL 2
50/50
43.61
20091326SHAW-D
50/50
1.87
20064926PENNTECH
50/50
0.552
200643SENECA#2
50/50
1.809
20326126BLOSSBCT
50/50
2.187
238215AE2-248 C
Solar/Wind Harmer
7.208
238206AE2-263_GEN
Solar/Wind Harmer
8.465
972169AH1-667 GEN
Solar/Wind Harmer
4.826
203954AE2-126 C
Solar/Wind Harmer
1.419
238183AE2-316 GEN
Solar/Wind Harmer
6.451
970713AG2-456 GEN
Solar/Wind Harmer
8.078
971705AH1-358 GEN
Solar/Wind Harmer
2.348
971709AH1-360 GEN
Solar/Wind Harmer
2.348
959471AF2-238 GEN
Solar/Wind Harmer
0.508
970337AG2-221 GEN
Solar/Wind Harmer
1.68
970511AG2-327 GEN
Solar/Wind Harmer
0.783
20335026MILZ1-092
Adder
1.665
944411AF1-106 GEN
Solar/Wind Harmer
1.534
203835AF1-098 GEN
Solar/Wind Harmer
1.611
20084926LAKVU GN
Adder
0.097
203813AE2-344_GEN
Solar/Wind Harmer
5.73
971183AH1-050 GEN
Solar/Wind Harmer
1.931
970647AG2-420 GEN
Solar/Wind Harmer
0.11
961971AG1-040 GEN
Solar/Wind Harmer
0.285
970267AG2-176 GEN
Solar/Wind Harmer
6.752
203860AG1-193 C
Solar/Wind Harmer
0.136
964391AG1-301 GEN
Solar/Wind Helper
0.276
LGEELTFEXP_LGEE->PJM
CLTF
0.203
WECLTFEXP_WEC->PJM
CLTF
0.128
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.039
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.288
LAGNLTFEXP_LAGN->PJM
CLTF
0.396
TVALTFEXP_TVA->PJM
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.605
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.779
MECLTFEXP_MEC->PJM
CLTF
0.51
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PL_08_P22_102799_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PL_08_P22_102799_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.7 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:714.18
MW Contribution:1.92
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
3.091
20066526SHAWVL 3
50/50
3.068
20071526SHAWVL 1
50/50
2.004
216419AE2-001 C
Solar/Wind Harmer
8.462
238217AF1-153 C O1
Solar/Wind Harmer
1.22
203952AE2-129 C
Solar/Wind Harmer
1.023
203946AE2-131 C
Solar/Wind Harmer
1.021
962411AG1-090 GEN
Solar/Wind Harmer
16.046
203853AF1-134 C O1
Solar/Wind Harmer
0.962
946381AF1-302 GEN
Solar/Wind Harmer
3.057
972075AH1-587 GEN
Solar/Wind Harmer
25.397
970305AG2-200 GEN
Solar/Wind Harmer
2.074
972077AH1-588 GEN
Solar/Wind Harmer
22.977
972079AH1-589 GEN
Solar/Wind Harmer
18.925
970715AG2-457 GEN
Solar/Wind Harmer
7.659
970313AG2-206 GEN
Solar/Wind Harmer
3.558
20398826ARMNA MT
Solar/Wind Harmer
1.686
203859AF2-294 C
Solar/Wind Harmer
1.062
203963AG1-253 GEN
Solar/Wind Harmer
0.221
203848AF2-166 C
Solar/Wind Harmer
1.084
200642SENECA#1
50/50
1.83
203855AF2-088 C
Solar/Wind Harmer
0.462
965121AG1-377 GEN
Solar/Wind Harmer
3.378
203804AE2-113_GEN
Solar/Wind Harmer
6.687
20090526Q36
Solar/Wind Harmer
1.785
203993AD2-133_GEN1
Solar/Wind Harmer
1.785
940863AE2-074 GEN
Solar/Wind Harmer
1.575
970555AG2-356 GEN
Solar/Wind Harmer
1.591
203926AA2-133 GEN
Adder
1.585
20334726NME_Y1-047
Adder
1.385
970663AG2-429 GEN
Solar/Wind Harmer
3.857
970663AG2-429 GEN
Solar/Wind Harmer
0.628
203846AF2-130 C
Solar/Wind Harmer
0.31
20084926LAKVU GN
Adder
0.106
966771AG1-548 GEN
Solar/Wind Harmer
7.788
966771AG1-548 GEN
Solar/Wind Harmer
1.509
970677AG2-438 GEN
Solar/Wind Harmer
0.532
20390726Y2-042
Adder
1.128
20083926HOMER C3
Adder
23.802
20083826HOMER C2
Adder
22.484
20083726HOMER C1
Adder
11.769
203975AE1-071-GEN
Solar/Wind Helper
2.229
959381AF2-229 GEN
Solar/Wind Helper
0.224
941231AE2-117 GEN
Solar/Wind Helper
0.237
200644SENECA#3
50/50
0.235
20335126GROZ1-110
50/50
2.62
20335226CANZ2-011
50/50
2.547
20120126WRREN CT
50/50
6.958
238202AE2-262_GEN
Solar/Wind Harmer
8.677
971627AH1-313 GEN
Solar/Wind Harmer
34.02
203854AF2-039 C
Solar/Wind Harmer
0.96
965131AG1-378 GEN
Solar/Wind Harmer
3.378
960051AF2-296 GEN
Solar/Wind Harmer
3.182
203818AF1-086 GEN
Solar/Wind Harmer
2.628
971703AH1-357 GEN
Solar/Wind Harmer
1.915
971707AH1-359 GEN
Solar/Wind Harmer
1.915
941421AE2-139 GEN
Solar/Wind Harmer
2.761
20334926Z1-069 C
Solar/Wind Harmer
1.736
972271AH1-720 GEN
Adder
5.34
20328326MANOR_T86
Adder
0.108
970335AG2-220 GEN
Solar/Wind Harmer
2.295
971127AH1-005 GEN
Solar/Wind Harmer
1.481
944411AF1-106 GEN
Solar/Wind Harmer
0.157
238219AF1-167 C
Solar/Wind Harmer
0.807
200917MEHOOPANY_G
Solar/Wind Harmer
2.061
203932AE1-123
Adder
1.109
203948AG1-140 C
Solar/Wind Harmer
0.145
945751AF1-240 GEN
Solar/Wind Harmer
0.868
20084926LAKVU GN
Adder
0.094
970899AG2-561 GEN
Solar/Wind Harmer
1.074
203830AF1-094 GEN
Solar/Wind Harmer
0.323
957161AF2-010 GEN
Solar/Wind Harmer
4.097
959441AF2-235 GEN
Solar/Wind Harmer
0.159
203856AF2-165 C
Solar/Wind Harmer
0.613
971185AH1-051 GEN
Solar/Wind Harmer
1.244
971355AH1-158 GEN
Solar/Wind Harmer
1.447
20072226SHAWVL 2
50/50
40.565
20091326SHAW-D
50/50
1.638
20064926PENNTECH
50/50
0.511
200643SENECA#2
50/50
1.707
238215AE2-248 C
Solar/Wind Harmer
6.99
238206AE2-263_GEN
Solar/Wind Harmer
8.087
972169AH1-667 GEN
Solar/Wind Harmer
4.228
203954AE2-126 C
Solar/Wind Harmer
1.275
238183AE2-316 GEN
Solar/Wind Harmer
6.109
970713AG2-456 GEN
Solar/Wind Harmer
7.659
971705AH1-358 GEN
Solar/Wind Harmer
2.226
971709AH1-360 GEN
Solar/Wind Harmer
2.226
20326126BLOSSBCT
Adder
1.954
959471AF2-238 GEN
Solar/Wind Harmer
0.481
970337AG2-221 GEN
Solar/Wind Harmer
1.591
970511AG2-327 GEN
Solar/Wind Harmer
0.741
20335026MILZ1-092
Adder
1.583
944411AF1-106 GEN
Solar/Wind Harmer
1.458
203835AF1-098 GEN
Solar/Wind Harmer
1.554
20084926LAKVU GN
Adder
0.094
971183AH1-050 GEN
Solar/Wind Harmer
2.073
970647AG2-420 GEN
Solar/Wind Harmer
0.117
203813AE2-344_GEN
Solar/Wind Harmer
5.641
961971AG1-040 GEN
Solar/Wind Harmer
0.283
203860AG1-193 C
Solar/Wind Harmer
0.141
20094526CT_V3-030
Solar/Wind Harmer
0.33
970267AG2-176 GEN
Solar/Wind Harmer
6.778
964391AG1-301 GEN
Solar/Wind Helper
0.299
209067AE2-060 GEN
Solar/Wind Helper
0.04
203979AG1-198 GEN
Solar/Wind Harmer
0.194
971933AH1-491 GEN
Solar/Wind Harmer
1.065
203947AF1-006 C
Solar/Wind Harmer
0.278
971931AH1-490 GEN
Solar/Wind Harmer
0.95
203980AG1-197 GEN
Solar/Wind Harmer
0.211
20390526W1-045 C
Solar/Wind Helper
0.22
209137AF2-361 C
Solar/Wind Helper
0.67
970647AG2-420 GEN
Solar/Wind Harmer
1.008
203962AF1-287 GEN
Solar/Wind Harmer
0.975
970679AG2-439 GEN
Solar/Wind Harmer
0.471
962511AG1-100 GEN
Solar/Wind Harmer
0.287
LGEELTFEXP_LGEE->PJM
CLTF
0.22
WECLTFEXP_WEC->PJM
CLTF
0.137
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.214
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.606
LAGNLTFEXP_LAGN->PJM
CLTF
0.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.013
TVALTFEXP_TVA->PJM
CLTF
0.211
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.966
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.867
MECLTFEXP_MEC->PJM
CLTF
0.551
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-059B_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-059B_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.57 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:713.39
MW Contribution:1.69
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.234
20335126GROZ1-110
50/50
2.604
20335226CANZ2-011
50/50
2.531
20120126WRREN CT
50/50
6.915
238202AE2-262_GEN
Solar/Wind Harmer
8.846
971627AH1-313 GEN
Solar/Wind Harmer
34.683
203854AF2-039 C
Solar/Wind Harmer
0.995
965131AG1-378 GEN
Solar/Wind Harmer
3.506
960051AF2-296 GEN
Solar/Wind Harmer
3.292
203818AF1-086 GEN
Solar/Wind Harmer
2.711
941421AE2-139 GEN
Solar/Wind Harmer
2.754
971703AH1-357 GEN
Solar/Wind Harmer
1.689
971707AH1-359 GEN
Solar/Wind Harmer
1.689
972271AH1-720 GEN
Adder
5.3
20328326MANOR_T86
Adder
0.106
970335AG2-220 GEN
Solar/Wind Harmer
2.207
971127AH1-005 GEN
Solar/Wind Harmer
1.424
20334926Z1-069 C
Solar/Wind Harmer
1.472
944411AF1-106 GEN
Solar/Wind Harmer
0.149
238219AF1-167 C
Solar/Wind Harmer
0.821
200917MEHOOPANY_G
Solar/Wind Harmer
2.026
203932AE1-123
Adder
1.124
945751AF1-240 GEN
Solar/Wind Harmer
0.884
970899AG2-561 GEN
Solar/Wind Harmer
1.099
203948AG1-140 C
Solar/Wind Harmer
0.141
20084926LAKVU GN
Adder
0.093
203830AF1-094 GEN
Solar/Wind Harmer
0.319
957161AF2-010 GEN
Solar/Wind Harmer
4.056
959441AF2-235 GEN
Solar/Wind Harmer
0.158
200642SENECA#1
50/50
1.821
203855AF2-088 C
Solar/Wind Harmer
0.479
203804AE2-113_GEN
Solar/Wind Harmer
10.519
965121AG1-377 GEN
Solar/Wind Harmer
3.506
20090526Q36
Solar/Wind Harmer
1.859
203993AD2-133_GEN1
Solar/Wind Harmer
1.859
970555AG2-356 GEN
Solar/Wind Harmer
1.534
940863AE2-074 GEN
Solar/Wind Harmer
1.28
203926AA2-133 GEN
Adder
1.559
20334726NME_Y1-047
Adder
1.361
970663AG2-429 GEN
Solar/Wind Harmer
3.909
970663AG2-429 GEN
Solar/Wind Harmer
0.636
203846AF2-130 C
Solar/Wind Harmer
0.312
20084926LAKVU GN
Adder
0.104
966771AG1-548 GEN
Solar/Wind Harmer
7.703
966771AG1-548 GEN
Solar/Wind Harmer
1.493
970677AG2-438 GEN
Solar/Wind Harmer
0.527
20390726Y2-042
Adder
1.113
20083926HOMER C3
Adder
22.318
203856AF2-165 C
Solar/Wind Harmer
0.615
971185AH1-051 GEN
Solar/Wind Harmer
1.248
971355AH1-158 GEN
Solar/Wind Harmer
1.451
970647AG2-420 GEN
Solar/Wind Harmer
1.009
203962AF1-287 GEN
Solar/Wind Harmer
0.96
970679AG2-439 GEN
Solar/Wind Harmer
0.465
962511AG1-100 GEN
Solar/Wind Harmer
0.283
20066626SHAWVL 4
50/50
3.177
20066526SHAWVL 3
50/50
3.153
20071526SHAWVL 1
50/50
2.067
216419AE2-001 C
Solar/Wind Harmer
8.575
972075AH1-587 GEN
Solar/Wind Harmer
43.963
238217AF1-153 C O1
Solar/Wind Harmer
1.268
203952AE2-129 C
Solar/Wind Harmer
1.062
203946AE2-131 C
Solar/Wind Harmer
1.06
962411AG1-090 GEN
Solar/Wind Harmer
16.655
203853AF1-134 C O1
Solar/Wind Harmer
0.995
946381AF1-302 GEN
Solar/Wind Harmer
3.17
970305AG2-200 GEN
Solar/Wind Harmer
2.061
972077AH1-588 GEN
Solar/Wind Harmer
20.266
972079AH1-589 GEN
Solar/Wind Harmer
16.692
970715AG2-457 GEN
Solar/Wind Harmer
6.755
970313AG2-206 GEN
Solar/Wind Harmer
3.423
20398826ARMNA MT
Solar/Wind Harmer
1.598
203859AF2-294 C
Solar/Wind Harmer
1.01
203848AF2-166 C
Solar/Wind Harmer
1.093
203963AG1-253 GEN
Solar/Wind Harmer
0.216
203979AG1-198 GEN
Solar/Wind Harmer
0.192
971933AH1-491 GEN
Solar/Wind Harmer
1.054
203947AF1-006 C
Solar/Wind Harmer
0.274
971931AH1-490 GEN
Solar/Wind Harmer
0.936
203980AG1-197 GEN
Solar/Wind Harmer
0.208
20390526W1-045 C
Solar/Wind Helper
0.217
20083826HOMER C2
Adder
21.082
20083726HOMER C1
Adder
11.145
203975AE1-071-GEN
Solar/Wind Helper
2.199
959381AF2-229 GEN
Solar/Wind Helper
0.221
941231AE2-117 GEN
Solar/Wind Helper
0.226
20072226SHAWVL 2
50/50
41.687
20091326SHAW-D
50/50
1.698
20064926PENNTECH
50/50
0.585
200643SENECA#2
50/50
1.699
238215AE2-248 C
Solar/Wind Harmer
7.078
238206AE2-263_GEN
Solar/Wind Harmer
8.245
972169AH1-667 GEN
Solar/Wind Harmer
4.381
203954AE2-126 C
Solar/Wind Harmer
1.384
238183AE2-316 GEN
Solar/Wind Harmer
6.335
970713AG2-456 GEN
Solar/Wind Harmer
6.755
971705AH1-358 GEN
Solar/Wind Harmer
1.964
971709AH1-360 GEN
Solar/Wind Harmer
1.964
20326126BLOSSBCT
Adder
1.866
959471AF2-238 GEN
Solar/Wind Harmer
0.464
970337AG2-221 GEN
Solar/Wind Harmer
1.534
970511AG2-327 GEN
Solar/Wind Harmer
0.713
20335026MILZ1-092
Adder
1.509
944411AF1-106 GEN
Solar/Wind Harmer
1.39
203835AF1-098 GEN
Solar/Wind Harmer
1.533
20084926LAKVU GN
Adder
0.093
971183AH1-050 GEN
Solar/Wind Harmer
2.08
970647AG2-420 GEN
Solar/Wind Harmer
0.117
20094526CT_V3-030
Solar/Wind Harmer
0.341
203813AE2-344_GEN
Solar/Wind Harmer
5.557
203860AG1-193 C
Solar/Wind Harmer
0.14
961971AG1-040 GEN
Solar/Wind Harmer
0.279
970267AG2-176 GEN
Solar/Wind Harmer
6.688
964391AG1-301 GEN
Solar/Wind Helper
0.288
LGEELTFEXP_LGEE->PJM
CLTF
0.217
WECLTFEXP_WEC->PJM
CLTF
0.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.564
LAGNLTFEXP_LAGN->PJM
CLTF
0.436
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.014
TVALTFEXP_TVA->PJM
CLTF
0.209
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.894
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.857
MECLTFEXP_MEC->PJM
CLTF
0.545
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-020A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-020A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.22 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:692.91
MW Contribution:1.38
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
38.959
20091326SHAW-D
50/50
1.605
20064926PENNTECH
50/50
0.501
200643SENECA#2
50/50
1.711
20326126BLOSSBCT
50/50
2.096
238215AE2-248 C
Solar/Wind Harmer
4.585
238206AE2-263_GEN
Solar/Wind Harmer
0.014
972169AH1-667 GEN
Solar/Wind Harmer
2.89
203954AE2-126 C
Solar/Wind Harmer
0.002
238183AE2-316 GEN
Solar/Wind Harmer
0.005
970713AG2-456 GEN
Solar/Wind Harmer
6.423
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
970337AG2-221 GEN
Solar/Wind Harmer
1.231
970511AG2-327 GEN
Solar/Wind Harmer
0.521
20335026MILZ1-092
Adder
1.625
944411AF1-106 GEN
Solar/Wind Harmer
1.658
20094526CT_V3-030
Solar/Wind Harmer
0.08
203835AF1-098 GEN
Solar/Wind Harmer
0.003
20084926LAKVU GN
Adder
0.1
971183AH1-050 GEN
Solar/Wind Harmer
1.984
970647AG2-420 GEN
Solar/Wind Harmer
0.13
203813AE2-344_GEN
Solar/Wind Harmer
4.262
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
5.244
971279AH1-102 GEN
Solar/Wind Harmer
3.617
20082826HNSMLK 1
Adder
2.764
20083026HNSMLK 3
Adder
2.764
209067AE2-060 GEN
Solar/Wind Helper
0.05
200644SENECA#3
50/50
0.235
20120126WRREN CT
50/50
7.034
20335126GROZ1-110
50/50
2.565
20335226CANZ2-011
50/50
2.493
238202AE2-262_GEN
Solar/Wind Harmer
0.014
971627AH1-313 GEN
Solar/Wind Harmer
22.518
203854AF2-039 C
Solar/Wind Harmer
0.002
965131AG1-378 GEN
Solar/Wind Harmer
1.245
960051AF2-296 GEN
Solar/Wind Harmer
2.259
203818AF1-086 GEN
Solar/Wind Harmer
0.667
972323AH1-746 GEN
Solar/Wind Harmer
2.583
971703AH1-357 GEN
Solar/Wind Harmer
1.381
971707AH1-359 GEN
Solar/Wind Harmer
1.381
941421AE2-139 GEN
Solar/Wind Harmer
0
20334926Z1-069 C
Solar/Wind Harmer
0.451
972271AH1-720 GEN
Adder
5.198
970335AG2-220 GEN
Solar/Wind Harmer
1.668
971127AH1-005 GEN
Solar/Wind Harmer
1.216
20328326MANOR_T86
Adder
0.106
970899AG2-561 GEN
Solar/Wind Harmer
0.921
238219AF1-167 C
Solar/Wind Harmer
0.607
945751AF1-240 GEN
Solar/Wind Harmer
0.817
203932AE1-123
Adder
1.228
203948AG1-140 C
Solar/Wind Harmer
0.116
200917MEHOOPANY_G
Solar/Wind Harmer
0.201
957161AF2-010 GEN
Solar/Wind Harmer
3.067
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20084926LAKVU GN
Adder
0.1
971185AH1-051 GEN
Solar/Wind Harmer
1.19
971355AH1-158 GEN
Solar/Wind Harmer
1.984
970647AG2-420 GEN
Solar/Wind Harmer
0.781
203962AF1-287 GEN
Solar/Wind Harmer
0.736
971541AH1-268 GEN
Solar/Wind Harmer
2.088
20082926HNSMLK 2
Adder
2.764
20083126HNSMLK 4
Adder
2.764
970679AG2-439 GEN
Solar/Wind Harmer
0.282
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.942
216419AE2-001 C
Solar/Wind Harmer
5.556
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.224
972075AH1-587 GEN
Solar/Wind Harmer
17.841
970305AG2-200 GEN
Solar/Wind Harmer
1.463
972077AH1-588 GEN
Solar/Wind Harmer
16.576
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
6.423
970313AG2-206 GEN
Solar/Wind Harmer
2.503
20398826ARMNA MT
Solar/Wind Harmer
0.029
203859AF2-294 C
Solar/Wind Harmer
0.759
203848AF2-166 C
Solar/Wind Harmer
0.837
203963AG1-253 GEN
Solar/Wind Harmer
0.185
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.8
203947AF1-006 C
Solar/Wind Harmer
0.025
971931AH1-490 GEN
Solar/Wind Harmer
0.72
203980AG1-197 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.702
203940AF1-140 C
Solar/Wind Harmer
0
946071AF1-272 GEN
Solar/Wind Harmer
0
20390526W1-045 C
Solar/Wind Helper
0.279
209137AF2-361 C
Solar/Wind Helper
0.847
200642SENECA#1
50/50
1.834
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.245
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.478
203993AD2-133_GEN1
Solar/Wind Harmer
0.473
970555AG2-356 GEN
Solar/Wind Harmer
1.119
20091526CHSTN_FL
Solar/Wind Harmer
0.09
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
3.14
970663AG2-429 GEN
Solar/Wind Harmer
0.686
20334726NME_Y1-047
Adder
1.345
970677AG2-438 GEN
Solar/Wind Harmer
0.447
966771AG1-548 GEN
Solar/Wind Harmer
1.333
966771AG1-548 GEN
Solar/Wind Harmer
1.666
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.764
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.037
20083826HOMER C2
Adder
30.262
203850AG1-041 C
Solar/Wind Harmer
0.36
20083726HOMER C1
Adder
22.45
203975AE1-071-GEN
Solar/Wind Helper
2.84
959381AF2-229 GEN
Solar/Wind Helper
0.284
LGEELTFEXP_LGEE->PJM
CLTF
0.318
WECLTFEXP_WEC->PJM
CLTF
0.194
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.517
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.368
LAGNLTFEXP_LAGN->PJM
CLTF
0.686
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.243
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.336
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.67 %
Rating:512.0 MVA
Rating Type:A
MVA to Mitigate:571.73
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
3.092
20066526SHAWVL 3
50/50
3.069
20071526SHAWVL 1
50/50
2.005
216419AE2-001 C
Solar/Wind Harmer
5.905
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
5.895
972075AH1-587 GEN
Solar/Wind Harmer
17.731
970305AG2-200 GEN
Solar/Wind Harmer
1.448
972077AH1-588 GEN
Solar/Wind Harmer
16.045
972079AH1-589 GEN
Solar/Wind Harmer
18.942
970715AG2-457 GEN
Solar/Wind Harmer
6.217
970313AG2-206 GEN
Solar/Wind Harmer
2.485
20398826ARMNA MT
Solar/Wind Harmer
0.029
203859AF2-294 C
Solar/Wind Harmer
0.742
203963AG1-253 GEN
Solar/Wind Harmer
0.174
203848AF2-166 C
Solar/Wind Harmer
0.758
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.744
203947AF1-006 C
Solar/Wind Harmer
0.024
971931AH1-490 GEN
Solar/Wind Harmer
0.664
203980AG1-197 GEN
Solar/Wind Harmer
0
20390526W1-045 C
Solar/Wind Helper
0.219
200642SENECA#1
50/50
1.831
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.179
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.404
203993AD2-133_GEN1
Solar/Wind Harmer
0.4
970555AG2-356 GEN
Solar/Wind Harmer
1.112
203926AA2-133 GEN
Adder
1.587
20334726NME_Y1-047
Adder
1.387
970663AG2-429 GEN
Solar/Wind Harmer
2.877
970663AG2-429 GEN
Solar/Wind Harmer
0.629
20084926LAKVU GN
Adder
0.106
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.552
970677AG2-438 GEN
Solar/Wind Harmer
0.416
20390726Y2-042
Adder
1.13
20083926HOMER C3
Adder
23.864
20083826HOMER C2
Adder
22.542
20083726HOMER C1
Adder
11.828
203975AE1-071-GEN
Solar/Wind Helper
2.227
959381AF2-229 GEN
Solar/Wind Helper
0.224
941231AE2-117 GEN
Solar/Wind Helper
0.237
200644SENECA#3
50/50
0.235
20335126GROZ1-110
50/50
2.622
20335226CANZ2-011
50/50
2.549
20120126WRREN CT
50/50
6.964
238202AE2-262_GEN
Solar/Wind Harmer
0.015
971627AH1-313 GEN
Solar/Wind Harmer
23.741
203854AF2-039 C
Solar/Wind Harmer
0.002
965131AG1-378 GEN
Solar/Wind Harmer
1.179
960051AF2-296 GEN
Solar/Wind Harmer
2.221
203818AF1-086 GEN
Solar/Wind Harmer
0.618
972323AH1-746 GEN
Solar/Wind Harmer
2.392
971703AH1-357 GEN
Solar/Wind Harmer
1.337
971707AH1-359 GEN
Solar/Wind Harmer
1.337
941421AE2-139 GEN
Solar/Wind Harmer
0
20334926Z1-069 C
Solar/Wind Harmer
0.435
972271AH1-720 GEN
Adder
5.345
20328326MANOR_T86
Adder
0.108
970335AG2-220 GEN
Solar/Wind Harmer
1.655
971127AH1-005 GEN
Solar/Wind Harmer
1.207
238219AF1-167 C
Solar/Wind Harmer
0.563
200917MEHOOPANY_G
Solar/Wind Harmer
0.208
203932AE1-123
Adder
1.111
203948AG1-140 C
Solar/Wind Harmer
0.109
945751AF1-240 GEN
Solar/Wind Harmer
0.706
20084926LAKVU GN
Adder
0.095
970899AG2-561 GEN
Solar/Wind Harmer
0.751
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
2.851
971185AH1-051 GEN
Solar/Wind Harmer
1.074
971355AH1-158 GEN
Solar/Wind Harmer
1.789
970647AG2-420 GEN
Solar/Wind Harmer
0.704
203962AF1-287 GEN
Solar/Wind Harmer
0.681
970679AG2-439 GEN
Solar/Wind Harmer
0.297
20072226SHAWVL 2
50/50
40.577
20091326SHAW-D
50/50
1.639
20064926PENNTECH
50/50
0.512
200643SENECA#2
50/50
1.708
20326126BLOSSBCT
50/50
2.075
238215AE2-248 C
Solar/Wind Harmer
4.877
238206AE2-263_GEN
Solar/Wind Harmer
0.014
972169AH1-667 GEN
Solar/Wind Harmer
2.951
203954AE2-126 C
Solar/Wind Harmer
0.002
238183AE2-316 GEN
Solar/Wind Harmer
0.005
970713AG2-456 GEN
Solar/Wind Harmer
6.217
971705AH1-358 GEN
Solar/Wind Harmer
2.228
971709AH1-360 GEN
Solar/Wind Harmer
2.228
970337AG2-221 GEN
Solar/Wind Harmer
1.223
970511AG2-327 GEN
Solar/Wind Harmer
0.518
20335026MILZ1-092
Adder
1.585
944411AF1-106 GEN
Solar/Wind Harmer
1.617
203835AF1-098 GEN
Solar/Wind Harmer
0.003
20084926LAKVU GN
Adder
0.095
971183AH1-050 GEN
Solar/Wind Harmer
1.789
970647AG2-420 GEN
Solar/Wind Harmer
0.117
203813AE2-344_GEN
Solar/Wind Harmer
3.943
203860AG1-193 C
Solar/Wind Harmer
0
20094526CT_V3-030
Solar/Wind Harmer
0.055
970267AG2-176 GEN
Solar/Wind Harmer
4.738
964391AG1-301 GEN
Solar/Wind Helper
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.723
LAGNLTFEXP_LAGN->PJM
CLTF
0.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.04
TVALTFEXP_TVA->PJM
CLTF
0.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.094
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.9
MECLTFEXP_MEC->PJM
CLTF
0.566
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-019_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-019_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:680.04
MW Contribution:1.37
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.948
20071526SHAWVL 1
50/50
1.934
216419AE2-001 C
Solar/Wind Harmer
5.6
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
5.898
972075AH1-587 GEN
Solar/Wind Harmer
17.723
970305AG2-200 GEN
Solar/Wind Harmer
1.453
972077AH1-588 GEN
Solar/Wind Harmer
16.418
972079AH1-589 GEN
Solar/Wind Harmer
19.382
970715AG2-457 GEN
Solar/Wind Harmer
6.362
970313AG2-206 GEN
Solar/Wind Harmer
2.49
20398826ARMNA MT
Solar/Wind Harmer
0.029
203859AF2-294 C
Solar/Wind Harmer
0.753
203848AF2-166 C
Solar/Wind Harmer
0.821
203963AG1-253 GEN
Solar/Wind Harmer
0.182
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.788
203947AF1-006 C
Solar/Wind Harmer
0.025
971931AH1-490 GEN
Solar/Wind Harmer
0.709
203980AG1-197 GEN
Solar/Wind Harmer
0
20390526W1-045 C
Solar/Wind Helper
0.269
209137AF2-361 C
Solar/Wind Helper
0.817
200642SENECA#1
50/50
1.824
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.18
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.424
203993AD2-133_GEN1
Solar/Wind Harmer
0.42
970555AG2-356 GEN
Solar/Wind Harmer
1.114
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
3.087
970663AG2-429 GEN
Solar/Wind Harmer
0.675
20091526CHSTN_FL
Solar/Wind Harmer
0.074
20334726NME_Y1-047
Adder
1.346
20084926LAKVU GN
Adder
0.111
966771AG1-548 GEN
Solar/Wind Harmer
1.313
966771AG1-548 GEN
Solar/Wind Harmer
1.642
970677AG2-438 GEN
Solar/Wind Harmer
0.44
20083226HNSMLK 5
Adder
2.699
20390726Y2-042
Adder
1.079
20083926HOMER C3
Adder
30.8
20083826HOMER C2
Adder
29.094
20083726HOMER C1
Adder
20.945
203975AE1-071-GEN
Solar/Wind Helper
2.743
941231AE2-117 GEN
Solar/Wind Helper
0.407
959381AF2-229 GEN
Solar/Wind Helper
0.275
200644SENECA#3
50/50
0.234
20120126WRREN CT
50/50
6.988
20335126GROZ1-110
50/50
2.562
20335226CANZ2-011
50/50
2.49
238202AE2-262_GEN
Solar/Wind Harmer
0.014
971627AH1-313 GEN
Solar/Wind Harmer
22.632
203854AF2-039 C
Solar/Wind Harmer
0.002
965131AG1-378 GEN
Solar/Wind Harmer
1.18
960051AF2-296 GEN
Solar/Wind Harmer
2.225
203818AF1-086 GEN
Solar/Wind Harmer
0.651
972323AH1-746 GEN
Solar/Wind Harmer
2.521
971703AH1-357 GEN
Solar/Wind Harmer
1.368
971707AH1-359 GEN
Solar/Wind Harmer
1.368
941421AE2-139 GEN
Solar/Wind Harmer
0
20334926Z1-069 C
Solar/Wind Harmer
0.447
972271AH1-720 GEN
Adder
5.199
20328326MANOR_T86
Adder
0.106
970335AG2-220 GEN
Solar/Wind Harmer
1.66
971127AH1-005 GEN
Solar/Wind Harmer
1.21
970899AG2-561 GEN
Solar/Wind Harmer
0.885
238219AF1-167 C
Solar/Wind Harmer
0.597
945751AF1-240 GEN
Solar/Wind Harmer
0.794
203932AE1-123
Adder
1.204
203948AG1-140 C
Solar/Wind Harmer
0.115
200917MEHOOPANY_G
Solar/Wind Harmer
0.201
20084926LAKVU GN
Adder
0.099
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
3.021
971185AH1-051 GEN
Solar/Wind Harmer
1.167
971355AH1-158 GEN
Solar/Wind Harmer
1.945
970647AG2-420 GEN
Solar/Wind Harmer
0.766
203962AF1-287 GEN
Solar/Wind Harmer
0.725
971541AH1-268 GEN
Solar/Wind Harmer
1.963
20082926HNSMLK 2
Adder
2.699
20083126HNSMLK 4
Adder
2.699
970679AG2-439 GEN
Solar/Wind Harmer
0.284
20072226SHAWVL 2
50/50
38.968
20091326SHAW-D
50/50
1.591
20064926PENNTECH
50/50
0.499
200643SENECA#2
50/50
1.702
20326126BLOSSBCT
50/50
2.084
238215AE2-248 C
Solar/Wind Harmer
4.623
238206AE2-263_GEN
Solar/Wind Harmer
0.014
972169AH1-667 GEN
Solar/Wind Harmer
2.864
203954AE2-126 C
Solar/Wind Harmer
0.002
238183AE2-316 GEN
Solar/Wind Harmer
0.005
970713AG2-456 GEN
Solar/Wind Harmer
6.362
971705AH1-358 GEN
Solar/Wind Harmer
2.28
971709AH1-360 GEN
Solar/Wind Harmer
2.28
970337AG2-221 GEN
Solar/Wind Harmer
1.225
970511AG2-327 GEN
Solar/Wind Harmer
0.519
20335026MILZ1-092
Adder
1.613
944411AF1-106 GEN
Solar/Wind Harmer
1.646
203835AF1-098 GEN
Solar/Wind Harmer
0.003
20094526CT_V3-030
Solar/Wind Harmer
0.074
20084926LAKVU GN
Adder
0.099
971183AH1-050 GEN
Solar/Wind Harmer
1.945
970647AG2-420 GEN
Solar/Wind Harmer
0.128
203813AE2-344_GEN
Solar/Wind Harmer
4.197
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
5.148
971279AH1-102 GEN
Solar/Wind Harmer
3.4
20082826HNSMLK 1
Adder
2.699
20083026HNSMLK 3
Adder
2.699
964391AG1-301 GEN
Solar/Wind Helper
0.489
209067AE2-060 GEN
Solar/Wind Helper
0.048
LGEELTFEXP_LGEE->PJM
CLTF
0.306
WECLTFEXP_WEC->PJM
CLTF
0.187
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.658
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.224
TVALTFEXP_TVA->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.28
MECLTFEXP_MEC->PJM
CLTF
0.76
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:294.0 MVA
Rating Type:B
MVA to Mitigate:337.74
MW Contribution:0.87
Bus #Bus NameTypeMW Contribution
20080526COLVER13
50/50
0.77
971279AH1-102 GEN
Solar/Wind Harmer
9.503
20094526CT_V3-030
Solar/Wind Harmer
0.696
203843AF2-002_GEN
Solar/Wind Harmer
0.948
20088826HIGHLAND
Solar/Wind Harmer
1.534
970631AG2-411 GEN
Solar/Wind Harmer
5.905
971423AH1-203 GEN
Solar/Wind Harmer
6.012
964201AG1-281 GEN
Solar/Wind Harmer
0.505
20216026CON.GEN2
50/50
0.042
20079426CONEMAGH
50/50
1.557
971541AH1-268 GEN
Solar/Wind Harmer
4.044
970899AG2-561 GEN
Solar/Wind Harmer
2.199
970125AG2-091 GEN
Solar/Wind Harmer
0.573
971879AH1-460 GEN
Solar/Wind Harmer
6.284
203841AF2-001_GEN
Solar/Wind Harmer
1.895
203818AF1-086 GEN
Solar/Wind Harmer
2.364
971419AH1-201 GEN
Solar/Wind Harmer
2.755
960051AF2-296 GEN
Solar/Wind Harmer
1.482
945751AF1-240 GEN
Solar/Wind Harmer
1.094
20089126CSLMN_L13
Solar/Wind Harmer
0.612
20089026BF_G21_K23
Solar/Wind Harmer
0.485
965131AG1-378 GEN
Solar/Wind Harmer
1.167
202652Y1-033 WT C
Solar/Wind Harmer
0.48
203854AF2-039 C
Solar/Wind Harmer
0.202
971703AH1-357 GEN
Solar/Wind Harmer
0.87
971707AH1-359 GEN
Solar/Wind Harmer
0.87
237043AE2-125 C
Solar/Wind Helper
0.184
946071AF1-272 GEN
Solar/Wind Harmer
5.475
203857AF2-221 C
Solar/Wind Harmer
1.433
970123AG2-090 GEN
Solar/Wind Harmer
1.338
203839AF1-321 GEN
Solar/Wind Harmer
1.895
971441AH1-212 GEN
Solar/Wind Harmer
1.875
20084626FORWARD
Solar/Wind Harmer
0.741
203940AF1-140 C
Solar/Wind Harmer
0.446
20088926STNY CRK
Solar/Wind Harmer
1.061
971427AH1-205 GEN
Solar/Wind Harmer
1.281
20083426SW_E13_K22
Solar/Wind Harmer
0.25
203853AF1-134 C O1
Solar/Wind Harmer
0.448
20088626ARWF_N39
Solar/Wind Harmer
1.36
20303426NA_O38_P22
Solar/Wind Harmer
1.101
944781AF1-143 GEN
Solar/Wind Harmer
2.099
203952AE2-129 C
Solar/Wind Harmer
0.354
203946AE2-131 C
Solar/Wind Harmer
0.353
962411AG1-090 GEN
Solar/Wind Harmer
5.546
203955AF1-039 C O1
Solar/Wind Harmer
0.234
972077AH1-588 GEN
Solar/Wind Harmer
10.442
972079AH1-589 GEN
Solar/Wind Harmer
8.6
970715AG2-457 GEN
Solar/Wind Harmer
3.481
972075AH1-587 GEN
Solar/Wind Harmer
8.637
23652301WDPWR_K20
Solar/Wind Helper
0.075
20215826CON.GEN1
50/50
0.022
20063626IUP CO-G
50/50
0.125
20050326C.SLOPE
50/50
0.306
20092526R32
Solar/Wind Harmer
1.644
203850AG1-041 C
Solar/Wind Harmer
1.084
203844AF2-092 C
Solar/Wind Harmer
1.083
20083726HOMER C1
Adder
56.049
20091526CHSTN_FL
Solar/Wind Harmer
0.715
203961AE2-224 GEN
Solar/Wind Harmer
2.291
20090526Q36
Solar/Wind Harmer
1.023
203993AD2-133_GEN1
Solar/Wind Harmer
1.023
20083926HOMER C3
Adder
44.365
20083826HOMER C2
Adder
41.908
965121AG1-377 GEN
Solar/Wind Harmer
1.167
941231AE2-117 GEN
Solar/Wind Harmer
0.35
203855AF2-088 C
Solar/Wind Harmer
0.097
940863AE2-074 GEN
Solar/Wind Harmer
0.761
957561AF2-050 GEN
Solar/Wind Harmer
3.782
20089226LOOKOUT
Solar/Wind Harmer
0.596
203987AE2-118 C
Solar/Wind Harmer
1.237
964391AG1-301 GEN
Solar/Wind Harmer
0.344
20091326SHAW-D
Adder
0.325
972169AH1-667 GEN
Solar/Wind Harmer
0.891
203954AE2-126 C
Solar/Wind Harmer
0.272
970713AG2-456 GEN
Solar/Wind Harmer
3.481
971705AH1-358 GEN
Solar/Wind Harmer
1.012
971709AH1-360 GEN
Solar/Wind Harmer
1.012
G-007ALTFEXP_G-007A->PJM
CMTX
1.994
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.59
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.519
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.313
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.149
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.971
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.401
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-997-DRT-053_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26CANYON-26N.MESHPN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-997-DRT-053_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:668.73
MW Contribution:1.16
Bus #Bus NameTypeMW Contribution
970313AG2-206 GEN
Solar/Wind Harmer
10.918
20398826ARMNA MT
Solar/Wind Harmer
4.415
238217AF1-153 C O1
Solar/Wind Harmer
0.383
972075AH1-587 GEN
Solar/Wind Harmer
12.603
216419AE2-001 C
Solar/Wind Harmer
1.187
972077AH1-588 GEN
Solar/Wind Harmer
13.897
972079AH1-589 GEN
Solar/Wind Harmer
11.446
970715AG2-457 GEN
Solar/Wind Harmer
4.632
203952AE2-129 C
Solar/Wind Harmer
0.325
203946AE2-131 C
Solar/Wind Harmer
0.324
962411AG1-090 GEN
Solar/Wind Harmer
5.091
946381AF1-302 GEN
Solar/Wind Harmer
1.058
203853AF1-134 C O1
Solar/Wind Harmer
0.298
970305AG2-200 GEN
Solar/Wind Harmer
0.963
209029WAYMART-WD
Solar/Wind Helper
0.543
20326126BLOSSBCT
50/50
4.823
20335026MILZ1-092
50/50
4.171
970511AG2-327 GEN
Solar/Wind Harmer
2.275
959471AF2-238 GEN
Solar/Wind Harmer
1.319
970337AG2-221 GEN
Solar/Wind Harmer
4.362
944411AF1-106 GEN
Solar/Wind Harmer
3.621
238206AE2-263_GEN
Solar/Wind Harmer
1.743
20072226SHAWVL 2
Adder
9.833
203922AA1-082 G1
50/50
9.374
203923AA1-082 G2
50/50
9.374
203926AA2-133 GEN
50/50
2.329
970555AG2-356 GEN
Solar/Wind Harmer
4.362
940863AE2-074 GEN
Solar/Wind Harmer
1.477
203855AF2-088 C
Solar/Wind Harmer
0.127
203804AE2-113_GEN
Solar/Wind Harmer
3.044
965121AG1-377 GEN
Solar/Wind Harmer
1.072
20090526Q36
Solar/Wind Harmer
0.692
203993AD2-133_GEN1
Solar/Wind Harmer
0.692
20083926HOMER C3
Adder
23.539
20083826HOMER C2
Adder
22.235
20083726HOMER C1
Adder
15.456
961261AF2-417 GEN
Solar/Wind Helper
0.226
972271AH1-720 GEN
50/50
26.818
20335126GROZ1-110
50/50
7.016
20335226CANZ2-011
50/50
6.819
20328326MANOR_T86
50/50
0.406
941421AE2-139 GEN
Solar/Wind Harmer
11.19
970335AG2-220 GEN
Solar/Wind Harmer
7
971127AH1-005 GEN
Solar/Wind Harmer
4.516
944411AF1-106 GEN
Solar/Wind Harmer
0.389
20334926Z1-069 C
Solar/Wind Harmer
2.238
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.334
203854AF2-039 C
Solar/Wind Harmer
0.265
971703AH1-357 GEN
Solar/Wind Harmer
1.158
971707AH1-359 GEN
Solar/Wind Harmer
1.158
965131AG1-378 GEN
Solar/Wind Harmer
1.072
960051AF2-296 GEN
Solar/Wind Harmer
0.985
20120126WRREN CT
Adder
3.044
200917MEHOOPANY_G
Solar/Wind Helper
3.253
972169AH1-667 GEN
Solar/Wind Harmer
1.166
20091326SHAW-D
Adder
0.426
203954AE2-126 C
Solar/Wind Harmer
0.391
970713AG2-456 GEN
Solar/Wind Harmer
4.632
971705AH1-358 GEN
Solar/Wind Harmer
1.347
971709AH1-360 GEN
Solar/Wind Harmer
1.347
238215AE2-248 C
Solar/Wind Harmer
0.912
238183AE2-316 GEN
Solar/Wind Harmer
2.114
LGEELTFEXP_LGEE->PJM
CLTF
0.293
WECLTFEXP_WEC->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
0.178
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.27
LAGNLTFEXP_LAGN->PJM
CLTF
0.728
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.664
TVALTFEXP_TVA->PJM
CLTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.995
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.391
MECLTFEXP_MEC->PJM
CLTF
0.722
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
961581Q1080_CY23
External Queue
19.463396072387695
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
961581Q1080_CY23
External Queue
19.46338653564453
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-A_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.16
MW Contribution:3.13
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
961581Q1080_CY23
External Queue
19.463396072387695
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1050.42
MW Contribution:3.09
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.883
20079426CONEMAGH
50/50
3.851
970125AG2-091 GEN
Solar/Wind Harmer
1.677
971879AH1-460 GEN
Solar/Wind Harmer
18.223
203841AF2-001_GEN
Solar/Wind Harmer
5.431
971541AH1-268 GEN
Solar/Wind Harmer
9.304
971419AH1-201 GEN
Solar/Wind Harmer
8.004
970899AG2-561 GEN
Solar/Wind Harmer
4.534
203818AF1-086 GEN
Solar/Wind Harmer
5.258
20089126CSLMN_L13
Solar/Wind Harmer
1.809
20089026BF_G21_K23
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
3.589
945751AF1-240 GEN
Solar/Wind Harmer
2.752
965131AG1-378 GEN
Solar/Wind Harmer
3.444
202652Y1-033 WT C
Solar/Wind Harmer
1.474
971703AH1-357 GEN
Solar/Wind Harmer
3.089
971707AH1-359 GEN
Solar/Wind Harmer
3.089
20334926Z1-069 C
Solar/Wind Harmer
3.079
203854AF2-039 C
Solar/Wind Harmer
0.59
203932AE1-123
Adder
2.648
20082926HNSMLK 2
Adder
7.863
20083126HNSMLK 4
Adder
7.863
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.475
970647AG2-420 GEN
Solar/Wind Harmer
2.464
944411AF1-106 GEN
Solar/Wind Harmer
0.277
20120126WRREN CT
Adder
7.7
238202AE2-262_GEN
Solar/Wind Harmer
3.02
20080926SITHE
50/50
0.647
203857AF2-221 C
Solar/Wind Harmer
4.193
970123AG2-090 GEN
Solar/Wind Harmer
3.913
203839AF1-321 GEN
Solar/Wind Harmer
5.431
20084626FORWARD
Solar/Wind Harmer
2.135
971441AH1-212 GEN
Solar/Wind Harmer
5.336
203940AF1-140 C
Solar/Wind Harmer
1.313
20088626ARWF_N39
Solar/Wind Harmer
4.901
20303426NA_O38_P22
Solar/Wind Harmer
3.968
20088926STNY CRK
Solar/Wind Harmer
3.084
971427AH1-205 GEN
Solar/Wind Harmer
3.723
20083426SW_E13_K22
Solar/Wind Harmer
0.724
946071AF1-272 GEN
Solar/Wind Harmer
7.688
944781AF1-143 GEN
Solar/Wind Harmer
6.199
203853AF1-134 C O1
Solar/Wind Harmer
1.085
203952AE2-129 C
Solar/Wind Harmer
1.043
203946AE2-131 C
Solar/Wind Harmer
1.041
962411AG1-090 GEN
Solar/Wind Harmer
16.36
203955AF1-039 C O1
Solar/Wind Harmer
0.717
972077AH1-588 GEN
Solar/Wind Harmer
37.067
972079AH1-589 GEN
Solar/Wind Harmer
30.53
970715AG2-457 GEN
Solar/Wind Harmer
12.356
972075AH1-587 GEN
Solar/Wind Harmer
29.887
203848AF2-166 C
Solar/Wind Harmer
2.585
238217AF1-153 C O1
Solar/Wind Harmer
0.765
946381AF1-302 GEN
Solar/Wind Harmer
2.644
20398826ARMNA MT
Solar/Wind Harmer
2.923
970305AG2-200 GEN
Solar/Wind Harmer
2.435
203859AF2-294 C
Solar/Wind Harmer
1.92
970313AG2-206 GEN
Solar/Wind Harmer
5.384
216419AE2-001 C
Solar/Wind Harmer
2.24
203979AG1-198 GEN
Solar/Wind Harmer
0.379
971933AH1-491 GEN
Solar/Wind Harmer
2.086
203980AG1-197 GEN
Solar/Wind Harmer
0.471
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.963
203947AF1-006 C
Solar/Wind Harmer
0.52
971627AH1-313 GEN
Solar/Wind Harmer
11.841
959441AF2-235 GEN
Solar/Wind Harmer
0.355
238219AF1-167 C
Solar/Wind Harmer
1.567
970335AG2-220 GEN
Solar/Wind Harmer
3.494
971127AH1-005 GEN
Solar/Wind Harmer
2.254
957161AF2-010 GEN
Solar/Wind Harmer
8.077
203830AF1-094 GEN
Solar/Wind Harmer
0.632
20335126GROZ1-110
Adder
2.405
20335226CANZ2-011
Adder
2.338
203948AG1-140 C
Solar/Wind Harmer
0.261
203962AF1-287 GEN
Solar/Wind Harmer
1.968
962511AG1-100 GEN
Solar/Wind Harmer
0.593
20084926LAKVU GN
Adder
0.167
20328326MANOR_T86
Adder
0.129
941421AE2-139 GEN
Solar/Wind Harmer
2.625
972271AH1-720 GEN
Adder
5.537
200917MEHOOPANY_G
Solar/Wind Harmer
2.511
970643AG2-418 GEN
Solar/Wind Harmer
1.331
970679AG2-439 GEN
Solar/Wind Harmer
0.553
20088826HIGHLAND
Solar/Wind Harmer
4.549
957561AF2-050 GEN
Solar/Wind Harmer
13.832
203843AF2-002_GEN
Solar/Wind Harmer
2.715
970631AG2-411 GEN
Solar/Wind Harmer
17.019
971279AH1-102 GEN
Solar/Wind Harmer
21.862
964201AG1-281 GEN
Solar/Wind Harmer
1.524
971423AH1-203 GEN
Solar/Wind Harmer
17.45
20094526CT_V3-030
Solar/Wind Harmer
1.725
20089226LOOKOUT
Solar/Wind Harmer
1.761
203987AE2-118 C
Solar/Wind Harmer
3.93
964391AG1-301 GEN
Solar/Wind Harmer
1.083
970713AG2-456 GEN
Solar/Wind Harmer
12.356
971705AH1-358 GEN
Solar/Wind Harmer
3.592
971709AH1-360 GEN
Solar/Wind Harmer
3.592
20091326SHAW-D
Adder
0.949
972169AH1-667 GEN
Solar/Wind Harmer
2.597
203954AE2-126 C
Solar/Wind Harmer
0.846
20082826HNSMLK 1
Adder
7.863
20083026HNSMLK 3
Adder
7.863
20072226SHAWVL 2
Adder
17.575
238183AE2-316 GEN
Solar/Wind Harmer
5.284
971183AH1-050 GEN
Solar/Wind Harmer
5.068
20326126BLOSSBCT
Adder
2.857
970647AG2-420 GEN
Solar/Wind Harmer
0.286
20335026MILZ1-092
Adder
2.802
944411AF1-106 GEN
Solar/Wind Harmer
2.581
203860AG1-193 C
Solar/Wind Harmer
0.362
238206AE2-263_GEN
Solar/Wind Harmer
2.815
959471AF2-238 GEN
Solar/Wind Harmer
0.708
970337AG2-221 GEN
Solar/Wind Harmer
2.341
970511AG2-327 GEN
Solar/Wind Harmer
1.122
238215AE2-248 C
Solar/Wind Harmer
1.775
970267AG2-176 GEN
Solar/Wind Harmer
16.374
961971AG1-040 GEN
Solar/Wind Harmer
0.62
203835AF1-098 GEN
Solar/Wind Harmer
2.467
203813AE2-344_GEN
Solar/Wind Harmer
11.413
20084926LAKVU GN
Adder
0.167
970643AG2-418 GEN
Solar/Wind Harmer
0.619
971865AH1-452 GEN
Solar/Wind Harmer
0.967
24035802GEN-Y1-012
Adder
0.202
20050326C.SLOPE
50/50
0.894
20092526R32
Solar/Wind Harmer
4.874
20083726HOMER C1
Adder
189.504
203961AE2-224 GEN
Solar/Wind Harmer
8.378
203850AG1-041 C
Solar/Wind Harmer
3.171
203844AF2-092 C
Solar/Wind Harmer
3.165
20091526CHSTN_FL
Solar/Wind Harmer
2.127
20083926HOMER C3
Adder
158.653
20083826HOMER C2
Adder
149.866
20090526Q36
Solar/Wind Harmer
3.039
203993AD2-133_GEN1
Solar/Wind Harmer
3.039
941231AE2-117 GEN
Solar/Wind Harmer
1.097
965121AG1-377 GEN
Solar/Wind Harmer
3.444
940863AE2-074 GEN
Solar/Wind Harmer
2.641
203804AE2-113_GEN
Solar/Wind Harmer
7.05
203855AF2-088 C
Solar/Wind Harmer
0.284
20083226HNSMLK 5
Adder
7.863
203846AF2-130 C
Solar/Wind Harmer
0.738
970663AG2-429 GEN
Solar/Wind Harmer
8.343
970663AG2-429 GEN
Solar/Wind Harmer
1.358
970555AG2-356 GEN
Solar/Wind Harmer
2.341
970677AG2-438 GEN
Solar/Wind Harmer
1.043
966771AG1-548 GEN
Solar/Wind Harmer
15.105
966771AG1-548 GEN
Solar/Wind Harmer
2.927
20084926LAKVU GN
Adder
0.188
971321AH1-140 GEN
Solar/Wind Harmer
12.535
971321AH1-140 GEN
Solar/Wind Harmer
2.429
203926AA2-133 GEN
Adder
1.9
20334726NME_Y1-047
Adder
1.687
20390726Y2-042
Adder
1.324
971055AG2-654 GEN
Solar/Wind Harmer
0.609
961581Q1080_CY23
External Queue
18.953319549560547
LGEELTFEXP_LGEE->PJM
CLTF
0.266
WECLTFEXP_WEC->PJM
CLTF
0.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.439
LAGNLTFEXP_LAGN->PJM
CLTF
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.029
TVALTFEXP_TVA->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.052
MECLTFEXP_MEC->PJM
CLTF
0.688
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0183-208_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0183-208_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.22 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1033.26
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
187.733
203961AE2-224 GEN
Solar/Wind Harmer
8.147
20092526R32
Solar/Wind Harmer
4.61
203850AG1-041 C
Solar/Wind Harmer
2.985
203844AF2-092 C
Solar/Wind Harmer
2.977
20091526CHSTN_FL
Solar/Wind Harmer
2.007
20083926HOMER C3
Adder
156.059
20083826HOMER C2
Adder
147.416
20090526Q36
Solar/Wind Harmer
2.845
203993AD2-133_GEN1
Solar/Wind Harmer
2.845
941231AE2-117 GEN
Solar/Wind Harmer
1.048
965121AG1-377 GEN
Solar/Wind Harmer
3.201
940863AE2-074 GEN
Solar/Wind Harmer
2.56
203804AE2-113_GEN
Solar/Wind Harmer
6.747
203855AF2-088 C
Solar/Wind Harmer
0.261
20083226HNSMLK 5
Adder
7.58
203846AF2-130 C
Solar/Wind Harmer
0.664
970555AG2-356 GEN
Solar/Wind Harmer
2.272
970663AG2-429 GEN
Solar/Wind Harmer
7.716
970663AG2-429 GEN
Solar/Wind Harmer
1.256
970677AG2-438 GEN
Solar/Wind Harmer
0.98
966771AG1-548 GEN
Solar/Wind Harmer
14.226
966771AG1-548 GEN
Solar/Wind Harmer
2.757
20084926LAKVU GN
Adder
0.18
203926AA2-133 GEN
Adder
1.839
20334726NME_Y1-047
Adder
1.634
971321AH1-140 GEN
Solar/Wind Harmer
8.786
971321AH1-140 GEN
Solar/Wind Harmer
1.703
20390726Y2-042
Adder
1.283
971055AG2-654 GEN
Solar/Wind Harmer
0.555
20083326SEWRDB34
50/50
11.609
20079426CONEMAGH
50/50
3.593
970125AG2-091 GEN
Solar/Wind Harmer
1.58
971879AH1-460 GEN
Solar/Wind Harmer
17.118
203841AF2-001_GEN
Solar/Wind Harmer
5.082
971419AH1-201 GEN
Solar/Wind Harmer
7.507
971541AH1-268 GEN
Solar/Wind Harmer
8.155
20089126CSLMN_L13
Solar/Wind Harmer
1.693
20089026BF_G21_K23
Solar/Wind Harmer
1.34
970899AG2-561 GEN
Solar/Wind Harmer
3.549
203818AF1-086 GEN
Solar/Wind Harmer
4.301
965131AG1-378 GEN
Solar/Wind Harmer
3.201
960051AF2-296 GEN
Solar/Wind Harmer
3.058
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
202652Y1-033 WT C
Solar/Wind Harmer
1.378
945751AF1-240 GEN
Solar/Wind Harmer
2.28
20334926Z1-069 C
Solar/Wind Harmer
2.988
203854AF2-039 C
Solar/Wind Harmer
0.541
20082926HNSMLK 2
Adder
7.58
20083126HNSMLK 4
Adder
7.58
944411AF1-106 GEN
Solar/Wind Harmer
0.27
203932AE1-123
Adder
2.352
20120126WRREN CT
Adder
7.362
971185AH1-051 GEN
Solar/Wind Harmer
2.776
971355AH1-158 GEN
Solar/Wind Harmer
3.228
203856AF2-165 C
Solar/Wind Harmer
1.349
970647AG2-420 GEN
Solar/Wind Harmer
2.262
238202AE2-262_GEN
Solar/Wind Harmer
2.83
971627AH1-313 GEN
Solar/Wind Harmer
11.095
970335AG2-220 GEN
Solar/Wind Harmer
3.393
971127AH1-005 GEN
Solar/Wind Harmer
2.189
959441AF2-235 GEN
Solar/Wind Harmer
0.327
238219AF1-167 C
Solar/Wind Harmer
1.437
20335126GROZ1-110
Adder
2.316
20335226CANZ2-011
Adder
2.251
957161AF2-010 GEN
Solar/Wind Harmer
7.586
203830AF1-094 GEN
Solar/Wind Harmer
0.594
203948AG1-140 C
Solar/Wind Harmer
0.25
203962AF1-287 GEN
Solar/Wind Harmer
1.875
962511AG1-100 GEN
Solar/Wind Harmer
0.565
20084926LAKVU GN
Adder
0.16
20328326MANOR_T86
Adder
0.125
941421AE2-139 GEN
Solar/Wind Harmer
2.528
972271AH1-720 GEN
Adder
5.344
200917MEHOOPANY_G
Solar/Wind Harmer
2.433
970643AG2-418 GEN
Solar/Wind Harmer
1.273
970679AG2-439 GEN
Solar/Wind Harmer
0.536
957561AF2-050 GEN
Solar/Wind Harmer
13.449
20088826HIGHLAND
Solar/Wind Harmer
4.302
203843AF2-002_GEN
Solar/Wind Harmer
2.541
970631AG2-411 GEN
Solar/Wind Harmer
15.933
964201AG1-281 GEN
Solar/Wind Harmer
1.443
971279AH1-102 GEN
Solar/Wind Harmer
19.163
971423AH1-203 GEN
Solar/Wind Harmer
16.357
20094526CT_V3-030
Solar/Wind Harmer
1.513
20089226LOOKOUT
Solar/Wind Harmer
1.648
203987AE2-118 C
Solar/Wind Harmer
3.76
964391AG1-301 GEN
Solar/Wind Harmer
1.036
970713AG2-456 GEN
Solar/Wind Harmer
11.953
971705AH1-358 GEN
Solar/Wind Harmer
3.475
971709AH1-360 GEN
Solar/Wind Harmer
3.475
972169AH1-667 GEN
Solar/Wind Harmer
2.382
20091326SHAW-D
Adder
0.87
203954AE2-126 C
Solar/Wind Harmer
0.787
20082826HNSMLK 1
Adder
7.58
20083026HNSMLK 3
Adder
7.58
20326126BLOSSBCT
Adder
2.771
20335026MILZ1-092
Adder
2.724
944411AF1-106 GEN
Solar/Wind Harmer
2.51
20072226SHAWVL 2
Adder
16.351
238183AE2-316 GEN
Solar/Wind Harmer
4.969
971183AH1-050 GEN
Solar/Wind Harmer
4.627
959471AF2-238 GEN
Solar/Wind Harmer
0.687
970337AG2-221 GEN
Solar/Wind Harmer
2.272
970647AG2-420 GEN
Solar/Wind Harmer
0.263
203860AG1-193 C
Solar/Wind Harmer
0.338
238206AE2-263_GEN
Solar/Wind Harmer
2.637
970511AG2-327 GEN
Solar/Wind Harmer
1.089
238215AE2-248 C
Solar/Wind Harmer
1.668
970267AG2-176 GEN
Solar/Wind Harmer
15.562
961971AG1-040 GEN
Solar/Wind Harmer
0.591
203835AF1-098 GEN
Solar/Wind Harmer
2.356
20080926SITHE
50/50
0.641
203857AF2-221 C
Solar/Wind Harmer
3.95
970123AG2-090 GEN
Solar/Wind Harmer
3.686
20088626ARWF_N39
Solar/Wind Harmer
4.759
20303426NA_O38_P22
Solar/Wind Harmer
3.853
203839AF1-321 GEN
Solar/Wind Harmer
5.082
20084626FORWARD
Solar/Wind Harmer
1.999
203940AF1-140 C
Solar/Wind Harmer
1.239
971441AH1-212 GEN
Solar/Wind Harmer
4.999
20088926STNY CRK
Solar/Wind Harmer
2.892
971427AH1-205 GEN
Solar/Wind Harmer
3.492
20083426SW_E13_K22
Solar/Wind Harmer
0.678
944781AF1-143 GEN
Solar/Wind Harmer
5.802
203952AE2-129 C
Solar/Wind Harmer
0.969
203946AE2-131 C
Solar/Wind Harmer
0.968
962411AG1-090 GEN
Solar/Wind Harmer
15.203
203853AF1-134 C O1
Solar/Wind Harmer
0.925
972077AH1-588 GEN
Solar/Wind Harmer
35.86
972079AH1-589 GEN
Solar/Wind Harmer
29.536
970715AG2-457 GEN
Solar/Wind Harmer
11.953
203955AF1-039 C O1
Solar/Wind Harmer
0.671
972075AH1-587 GEN
Solar/Wind Harmer
28.698
20398826ARMNA MT
Solar/Wind Harmer
2.842
238217AF1-153 C O1
Solar/Wind Harmer
0.716
946381AF1-302 GEN
Solar/Wind Harmer
2.487
970305AG2-200 GEN
Solar/Wind Harmer
2.329
203848AF2-166 C
Solar/Wind Harmer
2.325
946071AF1-272 GEN
Solar/Wind Harmer
3.833
203859AF2-294 C
Solar/Wind Harmer
1.868
970313AG2-206 GEN
Solar/Wind Harmer
5.227
216419AE2-001 C
Solar/Wind Harmer
2.105
203980AG1-197 GEN
Solar/Wind Harmer
0.448
203979AG1-198 GEN
Solar/Wind Harmer
0.356
971933AH1-491 GEN
Solar/Wind Harmer
1.961
203963AG1-253 GEN
Solar/Wind Harmer
0.382
971931AH1-490 GEN
Solar/Wind Harmer
1.87
203947AF1-006 C
Solar/Wind Harmer
0.497
203813AE2-344_GEN
Solar/Wind Harmer
10.878
20084926LAKVU GN
Adder
0.16
970643AG2-418 GEN
Solar/Wind Harmer
0.592
971865AH1-452 GEN
Solar/Wind Harmer
0.859
24035802GEN-Y1-012
Adder
0.193
961581Q1080_CY23
External Queue
19.001585006713867
LGEELTFEXP_LGEE->PJM
CLTF
0.253
WECLTFEXP_WEC->PJM
CLTF
0.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.226
LAGNLTFEXP_LAGN->PJM
CLTF
0.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.031
TVALTFEXP_TVA->PJM
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.002
MECLTFEXP_MEC->PJM
CLTF
0.655
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-997-DRT-053_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-997-DRT-053_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.77 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:677.76
MW Contribution:1.16
Bus #Bus NameTypeMW Contribution
970313AG2-206 GEN
Solar/Wind Harmer
10.918
20398826ARMNA MT
Solar/Wind Harmer
4.415
238217AF1-153 C O1
Solar/Wind Harmer
0.383
972075AH1-587 GEN
Solar/Wind Harmer
12.603
216419AE2-001 C
Solar/Wind Harmer
1.187
972077AH1-588 GEN
Solar/Wind Harmer
13.897
972079AH1-589 GEN
Solar/Wind Harmer
11.446
970715AG2-457 GEN
Solar/Wind Harmer
4.632
203952AE2-129 C
Solar/Wind Harmer
0.325
203946AE2-131 C
Solar/Wind Harmer
0.324
962411AG1-090 GEN
Solar/Wind Harmer
5.091
203922AA1-082 G1
50/50
9.374
203923AA1-082 G2
50/50
9.374
203926AA2-133 GEN
50/50
2.329
970555AG2-356 GEN
Solar/Wind Harmer
4.362
940863AE2-074 GEN
Solar/Wind Harmer
1.477
203855AF2-088 C
Solar/Wind Harmer
0.127
203804AE2-113_GEN
Solar/Wind Harmer
3.044
965121AG1-377 GEN
Solar/Wind Harmer
1.072
20090526Q36
Solar/Wind Harmer
0.692
203993AD2-133_GEN1
Solar/Wind Harmer
0.692
20083926HOMER C3
Adder
23.539
20083826HOMER C2
Adder
22.235
20083726HOMER C1
Adder
15.456
961261AF2-417 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Harmer
1.058
203853AF1-134 C O1
Solar/Wind Harmer
0.298
970305AG2-200 GEN
Solar/Wind Harmer
0.963
209029WAYMART-WD
Solar/Wind Helper
0.543
972271AH1-720 GEN
50/50
26.818
20335126GROZ1-110
50/50
7.016
20335226CANZ2-011
50/50
6.819
20328326MANOR_T86
50/50
0.406
941421AE2-139 GEN
Solar/Wind Harmer
11.19
970335AG2-220 GEN
Solar/Wind Harmer
7
971127AH1-005 GEN
Solar/Wind Harmer
4.516
944411AF1-106 GEN
Solar/Wind Harmer
0.389
20334926Z1-069 C
Solar/Wind Harmer
2.238
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.334
203854AF2-039 C
Solar/Wind Harmer
0.265
971703AH1-357 GEN
Solar/Wind Harmer
1.158
971707AH1-359 GEN
Solar/Wind Harmer
1.158
965131AG1-378 GEN
Solar/Wind Harmer
1.072
960051AF2-296 GEN
Solar/Wind Harmer
0.985
20120126WRREN CT
Adder
3.044
200917MEHOOPANY_G
Solar/Wind Helper
3.253
20326126BLOSSBCT
50/50
4.823
20335026MILZ1-092
50/50
4.171
970511AG2-327 GEN
Solar/Wind Harmer
2.275
959471AF2-238 GEN
Solar/Wind Harmer
1.319
970337AG2-221 GEN
Solar/Wind Harmer
4.362
944411AF1-106 GEN
Solar/Wind Harmer
3.621
238206AE2-263_GEN
Solar/Wind Harmer
1.743
20072226SHAWVL 2
Adder
9.833
972169AH1-667 GEN
Solar/Wind Harmer
1.166
20091326SHAW-D
Adder
0.426
203954AE2-126 C
Solar/Wind Harmer
0.391
970713AG2-456 GEN
Solar/Wind Harmer
4.632
971705AH1-358 GEN
Solar/Wind Harmer
1.347
971709AH1-360 GEN
Solar/Wind Harmer
1.347
238215AE2-248 C
Solar/Wind Harmer
0.912
238183AE2-316 GEN
Solar/Wind Harmer
2.114
LGEELTFEXP_LGEE->PJM
CLTF
0.293
WECLTFEXP_WEC->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
0.178
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.888
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.27
LAGNLTFEXP_LAGN->PJM
CLTF
0.728
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.664
TVALTFEXP_TVA->PJM
CLTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.995
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.391
MECLTFEXP_MEC->PJM
CLTF
0.722
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-26A2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-26A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:706.85
MW Contribution:8.69
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
6.547
203804AE2-113_GEN
Solar/Wind Harmer
8.259
203855AF2-088 C
Solar/Wind Harmer
0.245
940863AE2-074 GEN
Solar/Wind Harmer
2.022
965121AG1-377 GEN
Solar/Wind Harmer
1.947
20090526Q36
Solar/Wind Harmer
1.173
203993AD2-133_GEN1
Solar/Wind Harmer
1.173
200643SENECA#2
50/50
6.107
20064926PENNTECH
50/50
0.549
20072226SHAWVL 2
50/50
19.428
20091326SHAW-D
50/50
0.868
970713AG2-456 GEN
Solar/Wind Harmer
34.765
971705AH1-358 GEN
Solar/Wind Harmer
10.106
971709AH1-360 GEN
Solar/Wind Harmer
10.106
203954AE2-126 C
Solar/Wind Harmer
0.994
972169AH1-667 GEN
Solar/Wind Harmer
2.238
238206AE2-263_GEN
Solar/Wind Harmer
2.89
238183AE2-316 GEN
Solar/Wind Harmer
4.413
238215AE2-248 C
Solar/Wind Harmer
1.608
20326126BLOSSBCT
Adder
1.001
203835AF1-098 GEN
Solar/Wind Helper
3.366
961971AG1-040 GEN
Solar/Wind Helper
0.403
200644SENECA#3
50/50
0.84
971703AH1-357 GEN
Solar/Wind Harmer
8.691
971707AH1-359 GEN
Solar/Wind Harmer
8.691
203854AF2-039 C
Solar/Wind Harmer
0.508
238202AE2-262_GEN
Solar/Wind Harmer
3.101
971627AH1-313 GEN
Solar/Wind Harmer
12.157
965131AG1-378 GEN
Solar/Wind Harmer
1.947
20334926Z1-069 C
Solar/Wind Harmer
1.793
960051AF2-296 GEN
Solar/Wind Harmer
1.657
203818AF1-086 GEN
Solar/Wind Harmer
1.328
20335126GROZ1-110
Adder
1.178
20335226CANZ2-011
Adder
1.145
941421AE2-139 GEN
Solar/Wind Harmer
1.307
203830AF1-094 GEN
Solar/Wind Helper
0.473
962511AG1-100 GEN
Solar/Wind Helper
0.45
959441AF2-235 GEN
Solar/Wind Helper
0.126
20066626SHAWVL 4
50/50
1.48
20066526SHAWVL 3
50/50
1.472
20071526SHAWVL 1
50/50
1.005
972077AH1-588 GEN
Solar/Wind Harmer
104.295
972079AH1-589 GEN
Solar/Wind Harmer
85.902
970715AG2-457 GEN
Solar/Wind Harmer
34.765
972075AH1-587 GEN
Solar/Wind Harmer
32.888
238217AF1-153 C O1
Solar/Wind Harmer
0.925
946381AF1-302 GEN
Solar/Wind Harmer
2.208
216419AE2-001 C
Solar/Wind Harmer
2.07
203952AE2-129 C
Solar/Wind Harmer
0.59
203946AE2-131 C
Solar/Wind Harmer
0.589
962411AG1-090 GEN
Solar/Wind Harmer
9.248
203853AF1-134 C O1
Solar/Wind Harmer
0.501
203947AF1-006 C
Solar/Wind Helper
0.585
203979AG1-198 GEN
Solar/Wind Helper
0.284
203980AG1-197 GEN
Solar/Wind Helper
0.289
G-007ALTFEXP_G-007A->PJM
CMTX
2.29
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.113
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.472
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.184
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.466
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.147
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-345-997-DRT-051_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-345-997-DRT-051_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:706.85
MW Contribution:8.69
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
6.547
203804AE2-113_GEN
Solar/Wind Harmer
8.259
203855AF2-088 C
Solar/Wind Harmer
0.245
940863AE2-074 GEN
Solar/Wind Harmer
2.022
965121AG1-377 GEN
Solar/Wind Harmer
1.947
20090526Q36
Solar/Wind Harmer
1.173
203993AD2-133_GEN1
Solar/Wind Harmer
1.173
200643SENECA#2
50/50
6.107
20064926PENNTECH
50/50
0.549
20072226SHAWVL 2
50/50
19.428
20091326SHAW-D
50/50
0.868
970713AG2-456 GEN
Solar/Wind Harmer
34.765
971705AH1-358 GEN
Solar/Wind Harmer
10.106
971709AH1-360 GEN
Solar/Wind Harmer
10.106
203954AE2-126 C
Solar/Wind Harmer
0.994
972169AH1-667 GEN
Solar/Wind Harmer
2.238
238206AE2-263_GEN
Solar/Wind Harmer
2.89
238183AE2-316 GEN
Solar/Wind Harmer
4.413
238215AE2-248 C
Solar/Wind Harmer
1.608
20326126BLOSSBCT
Adder
1.001
203835AF1-098 GEN
Solar/Wind Helper
3.366
961971AG1-040 GEN
Solar/Wind Helper
0.403
200644SENECA#3
50/50
0.84
971703AH1-357 GEN
Solar/Wind Harmer
8.691
971707AH1-359 GEN
Solar/Wind Harmer
8.691
203854AF2-039 C
Solar/Wind Harmer
0.508
238202AE2-262_GEN
Solar/Wind Harmer
3.101
971627AH1-313 GEN
Solar/Wind Harmer
12.157
965131AG1-378 GEN
Solar/Wind Harmer
1.947
20334926Z1-069 C
Solar/Wind Harmer
1.793
960051AF2-296 GEN
Solar/Wind Harmer
1.657
203818AF1-086 GEN
Solar/Wind Harmer
1.328
20335126GROZ1-110
Adder
1.178
20335226CANZ2-011
Adder
1.145
941421AE2-139 GEN
Solar/Wind Harmer
1.307
203830AF1-094 GEN
Solar/Wind Helper
0.473
962511AG1-100 GEN
Solar/Wind Helper
0.45
959441AF2-235 GEN
Solar/Wind Helper
0.126
20066626SHAWVL 4
50/50
1.48
20066526SHAWVL 3
50/50
1.472
20071526SHAWVL 1
50/50
1.005
972077AH1-588 GEN
Solar/Wind Harmer
104.295
972079AH1-589 GEN
Solar/Wind Harmer
85.902
970715AG2-457 GEN
Solar/Wind Harmer
34.765
972075AH1-587 GEN
Solar/Wind Harmer
32.888
238217AF1-153 C O1
Solar/Wind Harmer
0.925
946381AF1-302 GEN
Solar/Wind Harmer
2.208
216419AE2-001 C
Solar/Wind Harmer
2.07
203952AE2-129 C
Solar/Wind Harmer
0.59
203946AE2-131 C
Solar/Wind Harmer
0.589
962411AG1-090 GEN
Solar/Wind Harmer
9.248
203853AF1-134 C O1
Solar/Wind Harmer
0.501
203947AF1-006 C
Solar/Wind Helper
0.585
203979AG1-198 GEN
Solar/Wind Helper
0.284
203980AG1-197 GEN
Solar/Wind Helper
0.289
G-007ALTFEXP_G-007A->PJM
CMTX
2.29
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.113
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.472
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.184
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.466
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.147
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-26A1_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-26A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.21 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:694.05
MW Contribution:7.11
Bus #Bus NameTypeMW Contribution
200643SENECA#2
50/50
5.638
20064926PENNTECH
50/50
0.614
20072226SHAWVL 2
50/50
19.851
20091326SHAW-D
50/50
0.899
970713AG2-456 GEN
Solar/Wind Harmer
28.425
971705AH1-358 GEN
Solar/Wind Harmer
8.263
971709AH1-360 GEN
Solar/Wind Harmer
8.263
203954AE2-126 C
Solar/Wind Harmer
1.082
972169AH1-667 GEN
Solar/Wind Harmer
2.32
238206AE2-263_GEN
Solar/Wind Harmer
2.949
238183AE2-316 GEN
Solar/Wind Harmer
4.439
238215AE2-248 C
Solar/Wind Harmer
1.643
20326126BLOSSBCT
Adder
1.579
959471AF2-238 GEN
Solar/Wind Harmer
0.324
970337AG2-221 GEN
Solar/Wind Harmer
1.073
970511AG2-327 GEN
Solar/Wind Harmer
0.492
203835AF1-098 GEN
Solar/Wind Helper
3.621
961971AG1-040 GEN
Solar/Wind Helper
0.433
20066626SHAWVL 4
50/50
1.513
20066526SHAWVL 3
50/50
1.504
20071526SHAWVL 1
50/50
1.034
972077AH1-588 GEN
Solar/Wind Harmer
85.275
972079AH1-589 GEN
Solar/Wind Harmer
70.237
970715AG2-457 GEN
Solar/Wind Harmer
28.425
972075AH1-587 GEN
Solar/Wind Harmer
56.581
238217AF1-153 C O1
Solar/Wind Harmer
0.932
216419AE2-001 C
Solar/Wind Harmer
2.115
946381AF1-302 GEN
Solar/Wind Harmer
2.221
203952AE2-129 C
Solar/Wind Harmer
0.612
203946AE2-131 C
Solar/Wind Harmer
0.611
962411AG1-090 GEN
Solar/Wind Harmer
9.593
203853AF1-134 C O1
Solar/Wind Harmer
0.519
20398826ARMNA MT
Solar/Wind Harmer
1.223
970313AG2-206 GEN
Solar/Wind Harmer
2.361
203947AF1-006 C
Solar/Wind Helper
0.628
203979AG1-198 GEN
Solar/Wind Helper
0.306
203980AG1-197 GEN
Solar/Wind Helper
0.311
200642SENECA#1
50/50
6.045
203804AE2-113_GEN
Solar/Wind Harmer
13.049
940863AE2-074 GEN
Solar/Wind Harmer
4.232
203855AF2-088 C
Solar/Wind Harmer
0.254
965121AG1-377 GEN
Solar/Wind Harmer
2.02
20090526Q36
Solar/Wind Harmer
1.218
203993AD2-133_GEN1
Solar/Wind Harmer
1.218
970555AG2-356 GEN
Solar/Wind Harmer
1.073
941231AE2-117 GEN
Solar/Wind Harmer
0.269
200644SENECA#3
50/50
0.776
971703AH1-357 GEN
Solar/Wind Harmer
7.106
971707AH1-359 GEN
Solar/Wind Harmer
7.106
20334926Z1-069 C
Solar/Wind Harmer
3.68
203854AF2-039 C
Solar/Wind Harmer
0.527
238202AE2-262_GEN
Solar/Wind Harmer
3.164
971627AH1-313 GEN
Solar/Wind Harmer
12.406
965131AG1-378 GEN
Solar/Wind Harmer
2.02
960051AF2-296 GEN
Solar/Wind Harmer
1.718
20335126GROZ1-110
Adder
1.464
20335226CANZ2-011
Adder
1.423
203818AF1-086 GEN
Solar/Wind Harmer
1.378
941421AE2-139 GEN
Solar/Wind Harmer
1.55
970335AG2-220 GEN
Solar/Wind Harmer
1.529
971127AH1-005 GEN
Solar/Wind Harmer
0.986
972271AH1-720 GEN
Adder
3.055
20328326MANOR_T86
Adder
0.062
203830AF1-094 GEN
Solar/Wind Helper
0.51
962511AG1-100 GEN
Solar/Wind Helper
0.484
959441AF2-235 GEN
Solar/Wind Helper
0.137
G-007ALTFEXP_G-007A->PJM
CMTX
2.55
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.01
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
7.069
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.563
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.289
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-345-997-DRT-052_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-345-997-DRT-052_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.21 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:694.05
MW Contribution:7.11
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
6.045
203804AE2-113_GEN
Solar/Wind Harmer
13.049
940863AE2-074 GEN
Solar/Wind Harmer
4.232
203855AF2-088 C
Solar/Wind Harmer
0.254
965121AG1-377 GEN
Solar/Wind Harmer
2.02
20090526Q36
Solar/Wind Harmer
1.218
203993AD2-133_GEN1
Solar/Wind Harmer
1.218
970555AG2-356 GEN
Solar/Wind Harmer
1.073
941231AE2-117 GEN
Solar/Wind Harmer
0.269
200644SENECA#3
50/50
0.776
971703AH1-357 GEN
Solar/Wind Harmer
7.106
971707AH1-359 GEN
Solar/Wind Harmer
7.106
20334926Z1-069 C
Solar/Wind Harmer
3.68
203854AF2-039 C
Solar/Wind Harmer
0.527
238202AE2-262_GEN
Solar/Wind Harmer
3.164
971627AH1-313 GEN
Solar/Wind Harmer
12.406
965131AG1-378 GEN
Solar/Wind Harmer
2.02
960051AF2-296 GEN
Solar/Wind Harmer
1.718
20335126GROZ1-110
Adder
1.464
20335226CANZ2-011
Adder
1.423
203818AF1-086 GEN
Solar/Wind Harmer
1.378
941421AE2-139 GEN
Solar/Wind Harmer
1.55
970335AG2-220 GEN
Solar/Wind Harmer
1.529
971127AH1-005 GEN
Solar/Wind Harmer
0.986
972271AH1-720 GEN
Adder
3.055
20328326MANOR_T86
Adder
0.062
203830AF1-094 GEN
Solar/Wind Helper
0.51
962511AG1-100 GEN
Solar/Wind Helper
0.484
959441AF2-235 GEN
Solar/Wind Helper
0.137
200643SENECA#2
50/50
5.638
20064926PENNTECH
50/50
0.614
20072226SHAWVL 2
50/50
19.851
20091326SHAW-D
50/50
0.899
970713AG2-456 GEN
Solar/Wind Harmer
28.425
971705AH1-358 GEN
Solar/Wind Harmer
8.263
971709AH1-360 GEN
Solar/Wind Harmer
8.263
203954AE2-126 C
Solar/Wind Harmer
1.082
972169AH1-667 GEN
Solar/Wind Harmer
2.32
238206AE2-263_GEN
Solar/Wind Harmer
2.949
238183AE2-316 GEN
Solar/Wind Harmer
4.439
238215AE2-248 C
Solar/Wind Harmer
1.643
20326126BLOSSBCT
Adder
1.579
959471AF2-238 GEN
Solar/Wind Harmer
0.324
970337AG2-221 GEN
Solar/Wind Harmer
1.073
970511AG2-327 GEN
Solar/Wind Harmer
0.492
20066626SHAWVL 4
50/50
1.513
20066526SHAWVL 3
50/50
1.504
20071526SHAWVL 1
50/50
1.034
972077AH1-588 GEN
Solar/Wind Harmer
85.275
972079AH1-589 GEN
Solar/Wind Harmer
70.237
970715AG2-457 GEN
Solar/Wind Harmer
28.425
972075AH1-587 GEN
Solar/Wind Harmer
56.581
238217AF1-153 C O1
Solar/Wind Harmer
0.932
216419AE2-001 C
Solar/Wind Harmer
2.115
946381AF1-302 GEN
Solar/Wind Harmer
2.221
203952AE2-129 C
Solar/Wind Harmer
0.612
203946AE2-131 C
Solar/Wind Harmer
0.611
962411AG1-090 GEN
Solar/Wind Harmer
9.593
203853AF1-134 C O1
Solar/Wind Harmer
0.519
20398826ARMNA MT
Solar/Wind Harmer
1.223
970313AG2-206 GEN
Solar/Wind Harmer
2.361
203947AF1-006 C
Solar/Wind Helper
0.628
203979AG1-198 GEN
Solar/Wind Helper
0.306
203980AG1-197 GEN
Solar/Wind Helper
0.311
203835AF1-098 GEN
Solar/Wind Helper
3.621
961971AG1-040 GEN
Solar/Wind Helper
0.433
G-007ALTFEXP_G-007A->PJM
CMTX
2.55
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.01
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
7.069
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.563
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.289
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-3_PN-345-1185-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-345-1185-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.99 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:692.58
MW Contribution:7.0
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
6.011
203804AE2-113_GEN
Solar/Wind Harmer
13.373
940863AE2-074 GEN
Solar/Wind Harmer
4.381
203855AF2-088 C
Solar/Wind Harmer
0.254
965121AG1-377 GEN
Solar/Wind Harmer
2.024
20090526Q36
Solar/Wind Harmer
1.221
203993AD2-133_GEN1
Solar/Wind Harmer
1.221
970555AG2-356 GEN
Solar/Wind Harmer
1.096
941231AE2-117 GEN
Solar/Wind Harmer
0.27
200644SENECA#3
50/50
0.772
971703AH1-357 GEN
Solar/Wind Harmer
6.999
971707AH1-359 GEN
Solar/Wind Harmer
6.999
20334926Z1-069 C
Solar/Wind Harmer
3.808
203854AF2-039 C
Solar/Wind Harmer
0.528
238202AE2-262_GEN
Solar/Wind Harmer
3.168
971627AH1-313 GEN
Solar/Wind Harmer
12.423
965131AG1-378 GEN
Solar/Wind Harmer
2.024
960051AF2-296 GEN
Solar/Wind Harmer
1.722
20335126GROZ1-110
Adder
1.483
20335226CANZ2-011
Adder
1.442
203818AF1-086 GEN
Solar/Wind Harmer
1.382
941421AE2-139 GEN
Solar/Wind Harmer
1.566
970335AG2-220 GEN
Solar/Wind Harmer
1.563
971127AH1-005 GEN
Solar/Wind Harmer
1.008
972271AH1-720 GEN
Adder
3.092
20328326MANOR_T86
Adder
0.063
203830AF1-094 GEN
Solar/Wind Helper
0.512
962511AG1-100 GEN
Solar/Wind Helper
0.486
959441AF2-235 GEN
Solar/Wind Helper
0.138
200643SENECA#2
50/50
5.607
20064926PENNTECH
50/50
0.619
20072226SHAWVL 2
50/50
19.88
20091326SHAW-D
50/50
0.902
970713AG2-456 GEN
Solar/Wind Harmer
27.996
971705AH1-358 GEN
Solar/Wind Harmer
8.138
971709AH1-360 GEN
Solar/Wind Harmer
8.138
203954AE2-126 C
Solar/Wind Harmer
1.088
972169AH1-667 GEN
Solar/Wind Harmer
2.326
238206AE2-263_GEN
Solar/Wind Harmer
2.953
238183AE2-316 GEN
Solar/Wind Harmer
4.44
238215AE2-248 C
Solar/Wind Harmer
1.646
20326126BLOSSBCT
Adder
1.618
959471AF2-238 GEN
Solar/Wind Harmer
0.331
970337AG2-221 GEN
Solar/Wind Harmer
1.096
970511AG2-327 GEN
Solar/Wind Harmer
0.503
203835AF1-098 GEN
Solar/Wind Helper
3.638
961971AG1-040 GEN
Solar/Wind Helper
0.435
20066626SHAWVL 4
50/50
1.515
20066526SHAWVL 3
50/50
1.506
20071526SHAWVL 1
50/50
1.036
972077AH1-588 GEN
Solar/Wind Harmer
83.989
972079AH1-589 GEN
Solar/Wind Harmer
69.177
970715AG2-457 GEN
Solar/Wind Harmer
27.996
972075AH1-587 GEN
Solar/Wind Harmer
58.184
238217AF1-153 C O1
Solar/Wind Harmer
0.932
216419AE2-001 C
Solar/Wind Harmer
2.118
946381AF1-302 GEN
Solar/Wind Harmer
2.222
203952AE2-129 C
Solar/Wind Harmer
0.613
203946AE2-131 C
Solar/Wind Harmer
0.612
962411AG1-090 GEN
Solar/Wind Harmer
9.616
203853AF1-134 C O1
Solar/Wind Harmer
0.521
20398826ARMNA MT
Solar/Wind Harmer
1.255
970313AG2-206 GEN
Solar/Wind Harmer
2.412
203947AF1-006 C
Solar/Wind Helper
0.631
203979AG1-198 GEN
Solar/Wind Helper
0.307
203980AG1-197 GEN
Solar/Wind Helper
0.312
G-007ALTFEXP_G-007A->PJM
CMTX
2.567
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.138
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
7.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.505
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.196
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.569
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.298
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1185-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1185-2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.98 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:692.52
MW Contribution:7.0
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
1.515
20066526SHAWVL 3
50/50
1.506
20071526SHAWVL 1
50/50
1.036
972077AH1-588 GEN
Solar/Wind Harmer
83.989
972079AH1-589 GEN
Solar/Wind Harmer
69.177
970715AG2-457 GEN
Solar/Wind Harmer
27.996
972075AH1-587 GEN
Solar/Wind Harmer
58.184
238217AF1-153 C O1
Solar/Wind Harmer
0.932
216419AE2-001 C
Solar/Wind Harmer
2.118
946381AF1-302 GEN
Solar/Wind Harmer
2.222
203952AE2-129 C
Solar/Wind Harmer
0.613
203946AE2-131 C
Solar/Wind Harmer
0.612
962411AG1-090 GEN
Solar/Wind Harmer
9.616
203853AF1-134 C O1
Solar/Wind Harmer
0.521
20398826ARMNA MT
Solar/Wind Harmer
1.255
970313AG2-206 GEN
Solar/Wind Harmer
2.412
203947AF1-006 C
Solar/Wind Helper
0.631
200642SENECA#1
50/50
6.011
203804AE2-113_GEN
Solar/Wind Harmer
13.373
940863AE2-074 GEN
Solar/Wind Harmer
4.381
203855AF2-088 C
Solar/Wind Harmer
0.254
965121AG1-377 GEN
Solar/Wind Harmer
2.024
20090526Q36
Solar/Wind Harmer
1.221
203993AD2-133_GEN1
Solar/Wind Harmer
1.221
970555AG2-356 GEN
Solar/Wind Harmer
1.096
941231AE2-117 GEN
Solar/Wind Harmer
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.307
203980AG1-197 GEN
Solar/Wind Helper
0.312
200644SENECA#3
50/50
0.772
971703AH1-357 GEN
Solar/Wind Harmer
6.999
971707AH1-359 GEN
Solar/Wind Harmer
6.999
20334926Z1-069 C
Solar/Wind Harmer
3.808
203854AF2-039 C
Solar/Wind Harmer
0.528
238202AE2-262_GEN
Solar/Wind Harmer
3.168
971627AH1-313 GEN
Solar/Wind Harmer
12.423
965131AG1-378 GEN
Solar/Wind Harmer
2.024
960051AF2-296 GEN
Solar/Wind Harmer
1.722
20335126GROZ1-110
Adder
1.483
20335226CANZ2-011
Adder
1.442
203818AF1-086 GEN
Solar/Wind Harmer
1.382
941421AE2-139 GEN
Solar/Wind Harmer
1.566
970335AG2-220 GEN
Solar/Wind Harmer
1.563
971127AH1-005 GEN
Solar/Wind Harmer
1.008
972271AH1-720 GEN
Adder
3.092
20328326MANOR_T86
Adder
0.063
203830AF1-094 GEN
Solar/Wind Helper
0.512
962511AG1-100 GEN
Solar/Wind Helper
0.486
959441AF2-235 GEN
Solar/Wind Helper
0.138
200643SENECA#2
50/50
5.607
20064926PENNTECH
50/50
0.619
20072226SHAWVL 2
50/50
19.88
20091326SHAW-D
50/50
0.902
970713AG2-456 GEN
Solar/Wind Harmer
27.996
971705AH1-358 GEN
Solar/Wind Harmer
8.138
971709AH1-360 GEN
Solar/Wind Harmer
8.138
203954AE2-126 C
Solar/Wind Harmer
1.088
972169AH1-667 GEN
Solar/Wind Harmer
2.326
238206AE2-263_GEN
Solar/Wind Harmer
2.953
238183AE2-316 GEN
Solar/Wind Harmer
4.44
238215AE2-248 C
Solar/Wind Harmer
1.646
20326126BLOSSBCT
Adder
1.618
959471AF2-238 GEN
Solar/Wind Harmer
0.331
970337AG2-221 GEN
Solar/Wind Harmer
1.096
970511AG2-327 GEN
Solar/Wind Harmer
0.503
203835AF1-098 GEN
Solar/Wind Helper
3.638
961971AG1-040 GEN
Solar/Wind Helper
0.435
G-007ALTFEXP_G-007A->PJM
CMTX
2.567
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.138
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
7.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.505
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.196
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.569
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.298
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26GLADE-26WARREN 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.6 %
Rating:666.0 MVA
Rating Type:B
MVA to Mitigate:669.97
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
1.569
20066526SHAWVL 3
50/50
1.56
20071526SHAWVL 1
50/50
1.056
972077AH1-588 GEN
Solar/Wind Harmer
45.538
972079AH1-589 GEN
Solar/Wind Harmer
37.507
970715AG2-457 GEN
Solar/Wind Harmer
15.179
972075AH1-587 GEN
Solar/Wind Harmer
33.812
238217AF1-153 C O1
Solar/Wind Harmer
0.863
216419AE2-001 C
Solar/Wind Harmer
2.808
203952AE2-129 C
Solar/Wind Harmer
0.615
203946AE2-131 C
Solar/Wind Harmer
0.614
962411AG1-090 GEN
Solar/Wind Harmer
9.644
946381AF1-302 GEN
Solar/Wind Harmer
2.11
203853AF1-134 C O1
Solar/Wind Harmer
0.536
20398826ARMNA MT
Solar/Wind Harmer
1.523
970313AG2-206 GEN
Solar/Wind Harmer
3.028
203859AF2-294 C
Solar/Wind Harmer
0.94
203947AF1-006 C
Solar/Wind Helper
0.682
203979AG1-198 GEN
Solar/Wind Helper
0.331
203980AG1-197 GEN
Solar/Wind Helper
0.326
200642SENECA#1
50/50
4.841
203804AE2-113_GEN
Solar/Wind Harmer
8.241
940863AE2-074 GEN
Solar/Wind Harmer
2.402
203855AF2-088 C
Solar/Wind Harmer
0.255
965121AG1-377 GEN
Solar/Wind Harmer
2.03
20090526Q36
Solar/Wind Harmer
1.226
203993AD2-133_GEN1
Solar/Wind Harmer
1.226
970555AG2-356 GEN
Solar/Wind Harmer
1.328
203926AA2-133 GEN
Adder
1.273
20334726NME_Y1-047
Adder
1.16
20390726Y2-042
Adder
1.01
20083926HOMER C3
Adder
21.491
20083826HOMER C2
Adder
20.301
20083726HOMER C1
Adder
15.009
200644SENECA#3
50/50
0.622
971703AH1-357 GEN
Solar/Wind Harmer
3.795
971707AH1-359 GEN
Solar/Wind Harmer
3.795
238202AE2-262_GEN
Solar/Wind Harmer
3.619
971627AH1-313 GEN
Solar/Wind Harmer
14.189
203854AF2-039 C
Solar/Wind Harmer
0.529
20334926Z1-069 C
Solar/Wind Harmer
2.357
965131AG1-378 GEN
Solar/Wind Harmer
2.03
960051AF2-296 GEN
Solar/Wind Harmer
1.774
20335126GROZ1-110
Adder
1.726
20335226CANZ2-011
Adder
1.677
941421AE2-139 GEN
Solar/Wind Harmer
1.953
970335AG2-220 GEN
Solar/Wind Harmer
1.958
971127AH1-005 GEN
Solar/Wind Harmer
1.263
972271AH1-720 GEN
Adder
3.956
944411AF1-106 GEN
Solar/Wind Harmer
0.134
20328326MANOR_T86
Adder
0.084
203818AF1-086 GEN
Solar/Wind Harmer
1.495
200917MEHOOPANY_G
Solar/Wind Harmer
1.727
970679AG2-439 GEN
Solar/Wind Harmer
0.422
203830AF1-094 GEN
Solar/Wind Helper
0.551
962511AG1-100 GEN
Solar/Wind Helper
0.516
959441AF2-235 GEN
Solar/Wind Helper
0.142
200643SENECA#2
50/50
4.516
20064926PENNTECH
50/50
0.493
20072226SHAWVL 2
50/50
20.595
20091326SHAW-D
50/50
0.902
970713AG2-456 GEN
Solar/Wind Harmer
15.179
971705AH1-358 GEN
Solar/Wind Harmer
4.413
971709AH1-360 GEN
Solar/Wind Harmer
4.413
203954AE2-126 C
Solar/Wind Harmer
0.945
238206AE2-263_GEN
Solar/Wind Harmer
3.373
238215AE2-248 C
Solar/Wind Harmer
2.241
972169AH1-667 GEN
Solar/Wind Harmer
2.328
238183AE2-316 GEN
Solar/Wind Harmer
4.217
20326126BLOSSBCT
Adder
1.69
959471AF2-238 GEN
Solar/Wind Harmer
0.401
970337AG2-221 GEN
Solar/Wind Harmer
1.328
970511AG2-327 GEN
Solar/Wind Harmer
0.631
20335026MILZ1-092
Adder
1.358
944411AF1-106 GEN
Solar/Wind Harmer
1.251
203835AF1-098 GEN
Solar/Wind Helper
4.064
961971AG1-040 GEN
Solar/Wind Helper
0.456
G-007ALTFEXP_G-007A->PJM
CMTX
2.302
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.262
CBM NorthLTFEXP_CBM-N->PJM
CBM
14.561
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.438
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.468
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.456
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
2.138
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.72 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1105.84
MW Contribution:4.88
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
940863AE2-074 GEN
Solar/Wind Harmer
4.363
970555AG2-356 GEN
Solar/Wind Harmer
4.026
203804AE2-113_GEN
Solar/Wind Harmer
9.082
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
9.309
966771AG1-548 GEN
Solar/Wind Harmer
1.804
970677AG2-438 GEN
Solar/Wind Harmer
0.626
203855AF2-088 C
Solar/Wind Harmer
0.111
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
19.506
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
4.586
959471AF2-238 GEN
Solar/Wind Harmer
1.217
970337AG2-221 GEN
Solar/Wind Harmer
4.026
970511AG2-327 GEN
Solar/Wind Harmer
1.95
203954AE2-126 C
Solar/Wind Harmer
0.535
203835AF1-098 GEN
Solar/Wind Harmer
2.074
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
2.617
203813AE2-344_GEN
Solar/Wind Harmer
7.125
238206AE2-263_GEN
Solar/Wind Harmer
1.438
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
1.018
961971AG1-040 GEN
Solar/Wind Harmer
0.341
970267AG2-176 GEN
Solar/Wind Harmer
7.665
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.713
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
5.269
971703AH1-357 GEN
Solar/Wind Harmer
4.876
971707AH1-359 GEN
Solar/Wind Harmer
4.876
944411AF1-106 GEN
Solar/Wind Harmer
0.493
970335AG2-220 GEN
Solar/Wind Harmer
6.083
971127AH1-005 GEN
Solar/Wind Harmer
3.924
941421AE2-139 GEN
Solar/Wind Harmer
3.942
200917MEHOOPANY_G
Solar/Wind Harmer
4.284
970679AG2-439 GEN
Solar/Wind Harmer
0.971
203948AG1-140 C
Solar/Wind Harmer
0.232
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.379
957161AF2-010 GEN
Solar/Wind Harmer
4.762
203962AF1-287 GEN
Solar/Wind Harmer
1.232
238202AE2-262_GEN
Solar/Wind Harmer
1.543
971627AH1-313 GEN
Solar/Wind Harmer
6.05
962511AG1-100 GEN
Solar/Wind Harmer
0.359
203854AF2-039 C
Solar/Wind Harmer
0.231
959441AF2-235 GEN
Solar/Wind Harmer
0.14
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
972077AH1-588 GEN
Solar/Wind Harmer
58.517
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
19.506
20398826ARMNA MT
Solar/Wind Harmer
5.218
972075AH1-587 GEN
Solar/Wind Harmer
41.314
203859AF2-294 C
Solar/Wind Harmer
3.446
970313AG2-206 GEN
Solar/Wind Harmer
9.361
970305AG2-200 GEN
Solar/Wind Harmer
2.62
203963AG1-253 GEN
Solar/Wind Harmer
0.354
238217AF1-153 C O1
Solar/Wind Harmer
0.466
203947AF1-006 C
Solar/Wind Harmer
0.365
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.252
946381AF1-302 GEN
Solar/Wind Harmer
1.31
971931AH1-490 GEN
Solar/Wind Harmer
1.186
203980AG1-197 GEN
Solar/Wind Harmer
0.251
216419AE2-001 C
Solar/Wind Harmer
0.937
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-301_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-301_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.72 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1105.84
MW Contribution:4.88
Bus #Bus NameTypeMW Contribution
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
5.269
971703AH1-357 GEN
Solar/Wind Harmer
4.876
971707AH1-359 GEN
Solar/Wind Harmer
4.876
944411AF1-106 GEN
Solar/Wind Harmer
0.493
970335AG2-220 GEN
Solar/Wind Harmer
6.083
971127AH1-005 GEN
Solar/Wind Harmer
3.924
941421AE2-139 GEN
Solar/Wind Harmer
3.942
200917MEHOOPANY_G
Solar/Wind Harmer
4.284
970679AG2-439 GEN
Solar/Wind Harmer
0.971
203948AG1-140 C
Solar/Wind Harmer
0.232
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.379
957161AF2-010 GEN
Solar/Wind Harmer
4.762
203962AF1-287 GEN
Solar/Wind Harmer
1.232
238202AE2-262_GEN
Solar/Wind Harmer
1.543
971627AH1-313 GEN
Solar/Wind Harmer
6.05
962511AG1-100 GEN
Solar/Wind Harmer
0.359
203854AF2-039 C
Solar/Wind Harmer
0.231
959441AF2-235 GEN
Solar/Wind Harmer
0.14
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
19.506
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
4.586
959471AF2-238 GEN
Solar/Wind Harmer
1.217
970337AG2-221 GEN
Solar/Wind Harmer
4.026
970511AG2-327 GEN
Solar/Wind Harmer
1.95
203954AE2-126 C
Solar/Wind Harmer
0.535
203835AF1-098 GEN
Solar/Wind Harmer
2.074
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
2.617
203813AE2-344_GEN
Solar/Wind Harmer
7.125
238206AE2-263_GEN
Solar/Wind Harmer
1.438
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
1.018
961971AG1-040 GEN
Solar/Wind Harmer
0.341
970267AG2-176 GEN
Solar/Wind Harmer
7.665
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.713
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
940863AE2-074 GEN
Solar/Wind Harmer
4.363
970555AG2-356 GEN
Solar/Wind Harmer
4.026
203804AE2-113_GEN
Solar/Wind Harmer
9.082
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
9.309
966771AG1-548 GEN
Solar/Wind Harmer
1.804
970677AG2-438 GEN
Solar/Wind Harmer
0.626
203855AF2-088 C
Solar/Wind Harmer
0.111
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
972077AH1-588 GEN
Solar/Wind Harmer
58.517
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
19.506
20398826ARMNA MT
Solar/Wind Harmer
5.218
972075AH1-587 GEN
Solar/Wind Harmer
41.314
203859AF2-294 C
Solar/Wind Harmer
3.446
970313AG2-206 GEN
Solar/Wind Harmer
9.361
970305AG2-200 GEN
Solar/Wind Harmer
2.62
203963AG1-253 GEN
Solar/Wind Harmer
0.354
238217AF1-153 C O1
Solar/Wind Harmer
0.466
203947AF1-006 C
Solar/Wind Harmer
0.365
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.252
946381AF1-302 GEN
Solar/Wind Harmer
1.31
971931AH1-490 GEN
Solar/Wind Harmer
1.186
203980AG1-197 GEN
Solar/Wind Harmer
0.251
216419AE2-001 C
Solar/Wind Harmer
0.937
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.05 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1100.29
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.04 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1100.25
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-345-001T-DRT-001_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-345-001T-DRT-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.95 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1091.2
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-345-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-345-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.95 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1091.2
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-230-0183-207_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-230-0183-207_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.11 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1067.77
MW Contribution:5.12
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.737
20083126HNSMLK 4
50/50
14.737
971703AH1-357 GEN
Solar/Wind Harmer
5.125
971707AH1-359 GEN
Solar/Wind Harmer
5.125
20083926HOMER C3
50/50
340.465
20083826HOMER C2
50/50
321.609
20083226HNSMLK 5
50/50
14.737
940863AE2-074 GEN
Solar/Wind Harmer
4.454
20083726HOMER C1
Adder
-144.162
203804AE2-113_GEN
Solar/Wind Harmer
9.857
970555AG2-356 GEN
Solar/Wind Harmer
3.948
970663AG2-429 GEN
Solar/Wind Harmer
10.921
970663AG2-429 GEN
Solar/Wind Harmer
1.778
20084926LAKVU GN
Adder
0.296
966771AG1-548 GEN
Solar/Wind Harmer
21.818
966771AG1-548 GEN
Solar/Wind Harmer
4.228
970677AG2-438 GEN
Solar/Wind Harmer
1.492
203846AF2-130 C
Solar/Wind Harmer
0.768
203926AA2-133 GEN
Adder
3.075
20334726NME_Y1-047
Adder
2.764
20390726Y2-042
Adder
2.182
203855AF2-088 C
Solar/Wind Harmer
0.129
971055AG2-654 GEN
Solar/Wind Harmer
0.793
203961AE2-224 GEN
Solar/Wind Helper
3.145
20092526R32
Solar/Wind Helper
1.329
20091526CHSTN_FL
Solar/Wind Helper
0.439
941231AE2-117 GEN
Solar/Wind Helper
0.253
972077AH1-588 GEN
Solar/Wind Harmer
61.494
972079AH1-589 GEN
Solar/Wind Harmer
50.65
970715AG2-457 GEN
Solar/Wind Harmer
20.498
972075AH1-587 GEN
Solar/Wind Harmer
44.13
20398826ARMNA MT
Solar/Wind Harmer
5.104
203859AF2-294 C
Solar/Wind Harmer
3.385
970313AG2-206 GEN
Solar/Wind Harmer
9.157
970305AG2-200 GEN
Solar/Wind Harmer
3.532
203980AG1-197 GEN
Solar/Wind Harmer
0.742
203963AG1-253 GEN
Solar/Wind Harmer
0.636
971931AH1-490 GEN
Solar/Wind Harmer
3.095
203979AG1-198 GEN
Solar/Wind Harmer
0.542
971933AH1-491 GEN
Solar/Wind Harmer
2.984
946381AF1-302 GEN
Solar/Wind Harmer
3.122
20334926Z1-069 C
Solar/Wind Harmer
5.297
944411AF1-106 GEN
Solar/Wind Harmer
0.486
970335AG2-220 GEN
Solar/Wind Harmer
5.951
971127AH1-005 GEN
Solar/Wind Harmer
3.839
20120126WRREN CT
Adder
11.166
203948AG1-140 C
Solar/Wind Harmer
0.417
962511AG1-100 GEN
Solar/Wind Harmer
0.936
203962AF1-287 GEN
Solar/Wind Harmer
3.094
970647AG2-420 GEN
Solar/Wind Harmer
3.055
20335126GROZ1-110
Adder
3.563
20335226CANZ2-011
Adder
3.463
20084926LAKVU GN
Adder
0.263
203830AF1-094 GEN
Solar/Wind Harmer
0.904
957161AF2-010 GEN
Solar/Wind Harmer
11.478
971185AH1-051 GEN
Solar/Wind Harmer
3.608
971355AH1-158 GEN
Solar/Wind Harmer
4.196
203856AF2-165 C
Solar/Wind Harmer
1.767
959441AF2-235 GEN
Solar/Wind Harmer
0.444
20328326MANOR_T86
Adder
0.207
238219AF1-167 C
Solar/Wind Harmer
1.891
972271AH1-720 GEN
Adder
8.501
941421AE2-139 GEN
Solar/Wind Harmer
3.883
203932AE1-123
Adder
2.444
200917MEHOOPANY_G
Solar/Wind Harmer
4.114
970679AG2-439 GEN
Solar/Wind Harmer
0.912
238202AE2-262_GEN
Solar/Wind Harmer
1.827
971627AH1-313 GEN
Solar/Wind Harmer
7.164
203854AF2-039 C
Solar/Wind Harmer
0.268
945751AF1-240 GEN
Solar/Wind Harmer
0.867
20089126CSLMN_L13
Solar/Wind Helper
0.489
20089026BF_G21_K23
Solar/Wind Helper
0.387
202652Y1-033 WT C
Solar/Wind Helper
0.363
20082826HNSMLK 1
50/50
14.737
20083026HNSMLK 3
50/50
14.737
20335026MILZ1-092
50/50
5.207
20326126BLOSSBCT
50/50
5.086
970713AG2-456 GEN
Solar/Wind Harmer
20.498
971705AH1-358 GEN
Solar/Wind Harmer
5.959
971709AH1-360 GEN
Solar/Wind Harmer
5.959
944411AF1-106 GEN
Solar/Wind Harmer
4.52
959471AF2-238 GEN
Solar/Wind Harmer
1.194
970337AG2-221 GEN
Solar/Wind Harmer
3.948
970511AG2-327 GEN
Solar/Wind Harmer
1.908
970267AG2-176 GEN
Solar/Wind Harmer
25.838
203860AG1-193 C
Solar/Wind Harmer
0.515
961971AG1-040 GEN
Solar/Wind Harmer
0.978
203835AF1-098 GEN
Solar/Wind Harmer
3.788
203813AE2-344_GEN
Solar/Wind Harmer
17.961
970647AG2-420 GEN
Solar/Wind Harmer
0.355
20084926LAKVU GN
Adder
0.263
971183AH1-050 GEN
Solar/Wind Harmer
6.014
238183AE2-316 GEN
Solar/Wind Harmer
6.239
203954AE2-126 C
Solar/Wind Harmer
0.637
20072226SHAWVL 2
Adder
10.919
24035802GEN-Y1-012
Adder
0.325
238206AE2-263_GEN
Solar/Wind Harmer
1.703
20091326SHAW-D
Adder
0.431
972169AH1-667 GEN
Solar/Wind Harmer
1.178
971865AH1-452 GEN
Solar/Wind Harmer
1.096
238215AE2-248 C
Solar/Wind Harmer
0.763
20088826HIGHLAND
Solar/Wind Helper
1.026
964201AG1-281 GEN
Solar/Wind Helper
0.467
20089226LOOKOUT
Solar/Wind Helper
0.476
20094526CT_V3-030
Solar/Wind Helper
0.295
964391AG1-301 GEN
Solar/Wind Helper
0.262
203947AF1-006 C
Solar/Wind Harmer
0.819
203848AF2-166 C
Solar/Wind Harmer
2.689
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.022
20088626ARWF_N39
Solar/Wind Helper
1.462
20303426NA_O38_P22
Solar/Wind Helper
1.199
20084626FORWARD
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.407
20088926STNY CRK
Solar/Wind Helper
0.814
20083426SW_E13_K22
Solar/Wind Helper
0.054
944781AF1-143 GEN
Solar/Wind Helper
2.029
946071AF1-272 GEN
Solar/Wind Helper
2.016
203955AF1-039 C O1
Solar/Wind Helper
0.239
961581Q1080_CY23
External Queue
46.2189826965332
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.25
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.463
LAGNLTFEXP_LAGN->PJM
CLTF
0.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.137
TVALTFEXP_TVA->PJM
CLTF
0.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.535
MECLTFEXP_MEC->PJM
CLTF
0.999
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.09 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1059.33
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
16.171
20083026HNSMLK 3
50/50
16.171
970713AG2-456 GEN
Solar/Wind Harmer
20.337
971705AH1-358 GEN
Solar/Wind Harmer
5.912
971709AH1-360 GEN
Solar/Wind Harmer
5.912
970267AG2-176 GEN
Solar/Wind Harmer
33.863
961971AG1-040 GEN
Solar/Wind Harmer
1.351
203813AE2-344_GEN
Solar/Wind Harmer
25.804
20084926LAKVU GN
Adder
0.386
203835AF1-098 GEN
Solar/Wind Harmer
5.278
203860AG1-193 C
Solar/Wind Harmer
0.636
20335026MILZ1-092
Adder
4.716
944411AF1-106 GEN
Solar/Wind Harmer
4.345
20326126BLOSSBCT
Adder
4.603
959471AF2-238 GEN
Solar/Wind Harmer
1.148
970337AG2-221 GEN
Solar/Wind Harmer
3.798
970647AG2-420 GEN
Solar/Wind Harmer
0.435
970511AG2-327 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
7.295
238183AE2-316 GEN
Solar/Wind Harmer
6.529
203954AE2-126 C
Solar/Wind Harmer
0.73
20072226SHAWVL 2
Adder
13.13
238206AE2-263_GEN
Solar/Wind Harmer
2.077
20091326SHAW-D
Adder
0.549
972169AH1-667 GEN
Solar/Wind Harmer
1.503
971865AH1-452 GEN
Solar/Wind Harmer
1.125
238215AE2-248 C
Solar/Wind Harmer
1.032
20088826HIGHLAND
Solar/Wind Helper
0.735
20089226LOOKOUT
Solar/Wind Helper
0.398
964201AG1-281 GEN
Solar/Wind Helper
0.309
972077AH1-588 GEN
Solar/Wind Harmer
61.011
972079AH1-589 GEN
Solar/Wind Harmer
50.252
970715AG2-457 GEN
Solar/Wind Harmer
20.337
203980AG1-197 GEN
Solar/Wind Harmer
1.017
203963AG1-253 GEN
Solar/Wind Harmer
0.892
971931AH1-490 GEN
Solar/Wind Harmer
4.439
972075AH1-587 GEN
Solar/Wind Harmer
44.277
203947AF1-006 C
Solar/Wind Harmer
1.229
970305AG2-200 GEN
Solar/Wind Harmer
4.224
20398826ARMNA MT
Solar/Wind Harmer
4.863
203979AG1-198 GEN
Solar/Wind Harmer
0.755
971933AH1-491 GEN
Solar/Wind Harmer
4.156
203859AF2-294 C
Solar/Wind Harmer
3.269
970313AG2-206 GEN
Solar/Wind Harmer
8.823
203848AF2-166 C
Solar/Wind Harmer
3.205
946381AF1-302 GEN
Solar/Wind Harmer
3.267
238217AF1-153 C O1
Solar/Wind Harmer
0.803
216419AE2-001 C
Solar/Wind Harmer
1.355
203853AF1-134 C O1
Solar/Wind Harmer
0.282
20082926HNSMLK 2
50/50
16.171
20083126HNSMLK 4
50/50
16.171
971703AH1-357 GEN
Solar/Wind Harmer
5.084
971707AH1-359 GEN
Solar/Wind Harmer
5.084
20334926Z1-069 C
Solar/Wind Harmer
5.092
203948AG1-140 C
Solar/Wind Harmer
0.584
962511AG1-100 GEN
Solar/Wind Harmer
1.342
203962AF1-287 GEN
Solar/Wind Harmer
4.429
20084926LAKVU GN
Adder
0.386
20120126WRREN CT
Adder
13.354
203830AF1-094 GEN
Solar/Wind Harmer
1.259
944411AF1-106 GEN
Solar/Wind Harmer
0.467
957161AF2-010 GEN
Solar/Wind Harmer
15.93
959441AF2-235 GEN
Solar/Wind Harmer
0.57
970647AG2-420 GEN
Solar/Wind Harmer
3.743
970335AG2-220 GEN
Solar/Wind Harmer
5.73
971127AH1-005 GEN
Solar/Wind Harmer
3.697
203856AF2-165 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
4.377
971355AH1-158 GEN
Solar/Wind Harmer
5.09
20335126GROZ1-110
Adder
3.54
20335226CANZ2-011
Adder
3.441
238219AF1-167 C
Solar/Wind Harmer
1.987
20328326MANOR_T86
Adder
0.205
203932AE1-123
Adder
2.816
972271AH1-720 GEN
Adder
8.529
941421AE2-139 GEN
Solar/Wind Harmer
3.915
200917MEHOOPANY_G
Solar/Wind Harmer
4.134
970679AG2-439 GEN
Solar/Wind Harmer
0.936
238202AE2-262_GEN
Solar/Wind Harmer
2.229
971627AH1-313 GEN
Solar/Wind Harmer
8.739
203854AF2-039 C
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.249
960051AF2-296 GEN
Solar/Wind Harmer
0.933
965131AG1-378 GEN
Solar/Wind Harmer
0.901
20089126CSLMN_L13
Solar/Wind Helper
0.408
20089026BF_G21_K23
Solar/Wind Helper
0.323
202652Y1-033 WT C
Solar/Wind Helper
0.302
20083926HOMER C3
50/50
297.76
20083826HOMER C2
50/50
281.269
20083226HNSMLK 5
50/50
16.171
940863AE2-074 GEN
Solar/Wind Harmer
4.324
20084926LAKVU GN
Adder
0.434
966771AG1-548 GEN
Solar/Wind Harmer
30.55
966771AG1-548 GEN
Solar/Wind Harmer
5.921
203804AE2-113_GEN
Solar/Wind Harmer
10.01
970677AG2-438 GEN
Solar/Wind Harmer
2.078
970555AG2-356 GEN
Solar/Wind Harmer
3.798
970663AG2-429 GEN
Solar/Wind Harmer
11.217
970663AG2-429 GEN
Solar/Wind Harmer
1.826
203846AF2-130 C
Solar/Wind Harmer
0.916
20083726HOMER C1
Adder
-95.563
203926AA2-133 GEN
Adder
3.065
20334726NME_Y1-047
Adder
2.777
20390726Y2-042
Adder
2.24
203855AF2-088 C
Solar/Wind Harmer
0.164
971055AG2-654 GEN
Solar/Wind Harmer
0.819
965121AG1-377 GEN
Solar/Wind Harmer
0.901
203961AE2-224 GEN
Solar/Wind Helper
2.002
20092526R32
Solar/Wind Helper
0.952
203952AE2-129 C
Solar/Wind Harmer
0.273
203946AE2-131 C
Solar/Wind Harmer
0.272
962411AG1-090 GEN
Solar/Wind Harmer
4.281
20084626FORWARD
Solar/Wind Helper
0.323
20083426SW_E13_K22
Solar/Wind Helper
0.045
20088926STNY CRK
Solar/Wind Helper
0.657
20088626ARWF_N39
Solar/Wind Helper
0.915
20303426NA_O38_P22
Solar/Wind Helper
0.75
203940AF1-140 C
Solar/Wind Helper
0.284
944781AF1-143 GEN
Solar/Wind Helper
1.695
203955AF1-039 C O1
Solar/Wind Helper
0.199
961581Q1080_CY23
External Queue
34.45887756347656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.127
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.016

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.05 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1001.09
MW Contribution:4.54
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
307.624
20083826HOMER C2
50/50
290.586
20083226HNSMLK 5
50/50
15.38
940863AE2-074 GEN
Solar/Wind Harmer
3.956
203804AE2-113_GEN
Solar/Wind Harmer
8.493
970555AG2-356 GEN
Solar/Wind Harmer
3.525
20084926LAKVU GN
Adder
0.275
20083726HOMER C1
Adder
-94.167
966771AG1-548 GEN
Solar/Wind Harmer
18.967
966771AG1-548 GEN
Solar/Wind Harmer
3.676
970677AG2-438 GEN
Solar/Wind Harmer
1.286
203926AA2-133 GEN
Adder
2.747
20334726NME_Y1-047
Adder
2.477
20390726Y2-042
Adder
1.965
203846AF2-130 C
Solar/Wind Harmer
0.435
203855AF2-088 C
Solar/Wind Harmer
0.098
20092526R32
Solar/Wind Helper
1.034
203961AE2-224 GEN
Solar/Wind Helper
2.14
20091526CHSTN_FL
Solar/Wind Helper
0.327
972077AH1-588 GEN
Solar/Wind Harmer
54.501
972079AH1-589 GEN
Solar/Wind Harmer
44.89
970715AG2-457 GEN
Solar/Wind Harmer
18.167
20398826ARMNA MT
Solar/Wind Harmer
4.57
972075AH1-587 GEN
Solar/Wind Harmer
38.382
203859AF2-294 C
Solar/Wind Harmer
3.039
970313AG2-206 GEN
Solar/Wind Harmer
8.187
970305AG2-200 GEN
Solar/Wind Harmer
3.117
203980AG1-197 GEN
Solar/Wind Harmer
0.702
203963AG1-253 GEN
Solar/Wind Harmer
0.589
971931AH1-490 GEN
Solar/Wind Harmer
2.914
203947AF1-006 C
Solar/Wind Harmer
0.765
203979AG1-198 GEN
Solar/Wind Harmer
0.467
971933AH1-491 GEN
Solar/Wind Harmer
2.572
946381AF1-302 GEN
Solar/Wind Harmer
1.69
238217AF1-153 C O1
Solar/Wind Harmer
0.481
203848AF2-166 C
Solar/Wind Harmer
1.524
20084626FORWARD
Solar/Wind Helper
0.342
20083426SW_E13_K22
Solar/Wind Helper
0.048
20088926STNY CRK
Solar/Wind Helper
0.705
20088626ARWF_N39
Solar/Wind Helper
0.995
20303426NA_O38_P22
Solar/Wind Helper
0.816
203940AF1-140 C
Solar/Wind Helper
0.318
944781AF1-143 GEN
Solar/Wind Helper
1.809
203955AF1-039 C O1
Solar/Wind Helper
0.214
946071AF1-272 GEN
Solar/Wind Helper
1.561
20082926HNSMLK 2
50/50
15.38
20083126HNSMLK 4
50/50
15.38
971703AH1-357 GEN
Solar/Wind Harmer
4.542
971707AH1-359 GEN
Solar/Wind Harmer
4.542
20334926Z1-069 C
Solar/Wind Harmer
4.72
944411AF1-106 GEN
Solar/Wind Harmer
0.436
970335AG2-220 GEN
Solar/Wind Harmer
5.32
971127AH1-005 GEN
Solar/Wind Harmer
3.432
20120126WRREN CT
Adder
9.854
203948AG1-140 C
Solar/Wind Harmer
0.385
962511AG1-100 GEN
Solar/Wind Harmer
0.881
203962AF1-287 GEN
Solar/Wind Harmer
2.903
20084926LAKVU GN
Adder
0.245
20335126GROZ1-110
Adder
3.141
20335226CANZ2-011
Adder
3.053
20328326MANOR_T86
Adder
0.184
203830AF1-094 GEN
Solar/Wind Harmer
0.779
957161AF2-010 GEN
Solar/Wind Harmer
9.836
972271AH1-720 GEN
Adder
7.549
970647AG2-420 GEN
Solar/Wind Harmer
2.29
941421AE2-139 GEN
Solar/Wind Harmer
3.432
959441AF2-235 GEN
Solar/Wind Harmer
0.334
203856AF2-165 C
Solar/Wind Harmer
1.263
200917MEHOOPANY_G
Solar/Wind Harmer
3.687
971185AH1-051 GEN
Solar/Wind Harmer
2.552
971355AH1-158 GEN
Solar/Wind Harmer
2.967
970679AG2-439 GEN
Solar/Wind Harmer
0.821
238202AE2-262_GEN
Solar/Wind Harmer
1.405
971627AH1-313 GEN
Solar/Wind Harmer
5.509
203932AE1-123
Adder
1.034
203854AF2-039 C
Solar/Wind Harmer
0.204
20089126CSLMN_L13
Solar/Wind Helper
0.436
20089026BF_G21_K23
Solar/Wind Helper
0.345
202652Y1-033 WT C
Solar/Wind Helper
0.325
20082826HNSMLK 1
50/50
15.38
20083026HNSMLK 3
50/50
15.38
20335026MILZ1-092
50/50
4.667
20326126BLOSSBCT
50/50
4.534
970713AG2-456 GEN
Solar/Wind Harmer
18.167
971705AH1-358 GEN
Solar/Wind Harmer
5.281
971709AH1-360 GEN
Solar/Wind Harmer
5.281
944411AF1-106 GEN
Solar/Wind Harmer
4.052
959471AF2-238 GEN
Solar/Wind Harmer
1.066
970337AG2-221 GEN
Solar/Wind Harmer
3.525
970511AG2-327 GEN
Solar/Wind Harmer
1.706
970267AG2-176 GEN
Solar/Wind Harmer
24.571
961971AG1-040 GEN
Solar/Wind Harmer
0.924
203860AG1-193 C
Solar/Wind Harmer
0.449
203813AE2-344_GEN
Solar/Wind Harmer
16.864
203835AF1-098 GEN
Solar/Wind Harmer
3.467
20084926LAKVU GN
Adder
0.245
970647AG2-420 GEN
Solar/Wind Harmer
0.266
971183AH1-050 GEN
Solar/Wind Harmer
4.253
203954AE2-126 C
Solar/Wind Harmer
0.507
238183AE2-316 GEN
Solar/Wind Harmer
3.378
24035802GEN-Y1-012
Adder
0.304
20072226SHAWVL 2
Adder
8.297
238206AE2-263_GEN
Solar/Wind Harmer
1.31
20091326SHAW-D
Adder
0.329
972169AH1-667 GEN
Solar/Wind Harmer
0.9
20088826HIGHLAND
Solar/Wind Helper
0.798
20089226LOOKOUT
Solar/Wind Helper
0.424
964201AG1-281 GEN
Solar/Wind Helper
0.354
20094526CT_V3-030
Solar/Wind Helper
0.236
961581Q1080_CY23
External Queue
42.076351165771484
LGEELTFEXP_LGEE->PJM
CLTF
0.243
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
40.823
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
0.472
TVALTFEXP_TVA->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.21
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.908
MECLTFEXP_MEC->PJM
CLTF
0.662
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P1-2_WP-345-311T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P1-2_WP-345-311T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.13 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:993.45
MW Contribution:3.4
Bus #Bus NameTypeMW Contribution
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
1.319
971703AH1-357 GEN
Solar/Wind Harmer
3.402
971707AH1-359 GEN
Solar/Wind Harmer
3.402
970335AG2-220 GEN
Solar/Wind Harmer
4.381
971127AH1-005 GEN
Solar/Wind Harmer
3.194
941421AE2-139 GEN
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.431
970679AG2-439 GEN
Solar/Wind Harmer
0.611
203948AG1-140 C
Solar/Wind Harmer
0.175
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
3.308
203962AF1-287 GEN
Solar/Wind Harmer
0.86
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.221
203854AF2-039 C
Solar/Wind Harmer
0
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
972077AH1-588 GEN
Solar/Wind Harmer
40.826
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
15.82
20398826ARMNA MT
Solar/Wind Harmer
0.088
972075AH1-587 GEN
Solar/Wind Harmer
28.824
203859AF2-294 C
Solar/Wind Harmer
2.404
970313AG2-206 GEN
Solar/Wind Harmer
6.531
970305AG2-200 GEN
Solar/Wind Harmer
1.828
203963AG1-253 GEN
Solar/Wind Harmer
0.278
203947AF1-006 C
Solar/Wind Harmer
0.031
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.874
971931AH1-490 GEN
Solar/Wind Harmer
0.828
203980AG1-197 GEN
Solar/Wind Harmer
0
216419AE2-001 C
Solar/Wind Harmer
0.653
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
970555AG2-356 GEN
Solar/Wind Harmer
2.809
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
1.482
966771AG1-548 GEN
Solar/Wind Harmer
1.852
970677AG2-438 GEN
Solar/Wind Harmer
0.488
203855AF2-088 C
Solar/Wind Harmer
0
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
15.82
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
5.079
970337AG2-221 GEN
Solar/Wind Harmer
3.09
970511AG2-327 GEN
Solar/Wind Harmer
1.361
203954AE2-126 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.004
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
0.002
203813AE2-344_GEN
Solar/Wind Harmer
4.971
238206AE2-263_GEN
Solar/Wind Harmer
0.003
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
0.71
970267AG2-176 GEN
Solar/Wind Harmer
5.348
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.497
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:954.32
MW Contribution:4.35
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
12.11
20083126HNSMLK 4
50/50
12.11
971703AH1-357 GEN
Solar/Wind Harmer
4.348
971707AH1-359 GEN
Solar/Wind Harmer
4.348
20334926Z1-069 C
Solar/Wind Harmer
4.463
944411AF1-106 GEN
Solar/Wind Harmer
0.409
970335AG2-220 GEN
Solar/Wind Harmer
5.061
971127AH1-005 GEN
Solar/Wind Harmer
3.265
20120126WRREN CT
Adder
9.788
20335126GROZ1-110
Adder
3.176
20335226CANZ2-011
Adder
3.087
203948AG1-140 C
Solar/Wind Harmer
0.352
203962AF1-287 GEN
Solar/Wind Harmer
2.601
962511AG1-100 GEN
Solar/Wind Harmer
0.786
970647AG2-420 GEN
Solar/Wind Harmer
2.57
20084926LAKVU GN
Adder
0.223
203830AF1-094 GEN
Solar/Wind Harmer
0.764
20328326MANOR_T86
Adder
0.18
957161AF2-010 GEN
Solar/Wind Harmer
9.707
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.49
959441AF2-235 GEN
Solar/Wind Harmer
0.375
238219AF1-167 C
Solar/Wind Harmer
1.615
941421AE2-139 GEN
Solar/Wind Harmer
3.471
972271AH1-720 GEN
Adder
7.506
203932AE1-123
Adder
2.09
238202AE2-262_GEN
Solar/Wind Harmer
2.629
971627AH1-313 GEN
Solar/Wind Harmer
10.307
200917MEHOOPANY_G
Solar/Wind Harmer
3.564
203854AF2-039 C
Solar/Wind Harmer
0.337
970679AG2-439 GEN
Solar/Wind Harmer
0.792
945751AF1-240 GEN
Solar/Wind Harmer
0.788
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.365
972077AH1-588 GEN
Solar/Wind Harmer
52.179
972079AH1-589 GEN
Solar/Wind Harmer
42.977
970715AG2-457 GEN
Solar/Wind Harmer
17.393
972075AH1-587 GEN
Solar/Wind Harmer
38.609
20398826ARMNA MT
Solar/Wind Harmer
4.304
203859AF2-294 C
Solar/Wind Harmer
2.847
970313AG2-206 GEN
Solar/Wind Harmer
7.793
970305AG2-200 GEN
Solar/Wind Harmer
3.096
946381AF1-302 GEN
Solar/Wind Harmer
2.897
203980AG1-197 GEN
Solar/Wind Harmer
0.621
203963AG1-253 GEN
Solar/Wind Harmer
0.538
971931AH1-490 GEN
Solar/Wind Harmer
2.598
203979AG1-198 GEN
Solar/Wind Harmer
0.459
971933AH1-491 GEN
Solar/Wind Harmer
2.523
203947AF1-006 C
Solar/Wind Harmer
0.691
238217AF1-153 C O1
Solar/Wind Harmer
0.737
203848AF2-166 C
Solar/Wind Harmer
2.285
216419AE2-001 C
Solar/Wind Harmer
1.962
20084626FORWARD
Solar/Wind Helper
0.391
20088626ARWF_N39
Solar/Wind Helper
1.229
20303426NA_O38_P22
Solar/Wind Helper
1.008
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.051
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.501
20083926HOMER C3
50/50
275.49
20083826HOMER C2
50/50
260.232
20083226HNSMLK 5
50/50
12.11
940863AE2-074 GEN
Solar/Wind Harmer
3.768
203804AE2-113_GEN
Solar/Wind Harmer
8.756
970555AG2-356 GEN
Solar/Wind Harmer
3.367
20083726HOMER C1
Adder
-110.032
970663AG2-429 GEN
Solar/Wind Harmer
9.226
970663AG2-429 GEN
Solar/Wind Harmer
1.502
20084926LAKVU GN
Adder
0.25
966771AG1-548 GEN
Solar/Wind Harmer
18.453
966771AG1-548 GEN
Solar/Wind Harmer
3.576
970677AG2-438 GEN
Solar/Wind Harmer
1.262
203846AF2-130 C
Solar/Wind Harmer
0.653
203926AA2-133 GEN
Adder
2.669
20334726NME_Y1-047
Adder
2.394
203855AF2-088 C
Solar/Wind Harmer
0.162
20390726Y2-042
Adder
1.895
971055AG2-654 GEN
Solar/Wind Harmer
0.672
203961AE2-224 GEN
Solar/Wind Helper
2.595
20092526R32
Solar/Wind Helper
1.18
20091526CHSTN_FL
Solar/Wind Helper
0.359
941231AE2-117 GEN
Solar/Wind Helper
0.246
20082826HNSMLK 1
50/50
12.11
20083026HNSMLK 3
50/50
12.11
20335026MILZ1-092
50/50
4.385
20326126BLOSSBCT
50/50
4.34
970713AG2-456 GEN
Solar/Wind Harmer
17.393
971705AH1-358 GEN
Solar/Wind Harmer
5.056
971709AH1-360 GEN
Solar/Wind Harmer
5.056
944411AF1-106 GEN
Solar/Wind Harmer
3.807
959471AF2-238 GEN
Solar/Wind Harmer
1.018
970337AG2-221 GEN
Solar/Wind Harmer
3.367
970511AG2-327 GEN
Solar/Wind Harmer
1.623
970267AG2-176 GEN
Solar/Wind Harmer
21.537
203860AG1-193 C
Solar/Wind Harmer
0.429
238183AE2-316 GEN
Solar/Wind Harmer
5.79
961971AG1-040 GEN
Solar/Wind Harmer
0.819
203835AF1-098 GEN
Solar/Wind Harmer
3.232
203813AE2-344_GEN
Solar/Wind Harmer
15.097
970647AG2-420 GEN
Solar/Wind Harmer
0.299
20084926LAKVU GN
Adder
0.223
971183AH1-050 GEN
Solar/Wind Harmer
5.068
203954AE2-126 C
Solar/Wind Harmer
0.674
238206AE2-263_GEN
Solar/Wind Harmer
2.45
20072226SHAWVL 2
Adder
13.73
238215AE2-248 C
Solar/Wind Harmer
1.548
20091326SHAW-D
Adder
0.542
972169AH1-667 GEN
Solar/Wind Harmer
1.484
24035802GEN-Y1-012
Adder
0.274
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20088826HIGHLAND
Solar/Wind Helper
0.91
964201AG1-281 GEN
Solar/Wind Helper
0.414
20089226LOOKOUT
Solar/Wind Helper
0.481
964391AG1-301 GEN
Solar/Wind Helper
0.26
20094526CT_V3-030
Solar/Wind Helper
0.226
961581Q1080_CY23
External Queue
35.905757904052734
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.22
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.687
LAGNLTFEXP_LAGN->PJM
CLTF
0.702
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.117
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.063
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.353
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:736.47
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
11.769
20083026HNSMLK 3
50/50
11.769
20335026MILZ1-092
50/50
4.157
20326126BLOSSBCT
50/50
4.059
970713AG2-456 GEN
Solar/Wind Harmer
13.266
971705AH1-358 GEN
Solar/Wind Harmer
4.755
971709AH1-360 GEN
Solar/Wind Harmer
4.755
944411AF1-106 GEN
Solar/Wind Harmer
3.997
970337AG2-221 GEN
Solar/Wind Harmer
2.419
970511AG2-327 GEN
Solar/Wind Harmer
1.062
970267AG2-176 GEN
Solar/Wind Harmer
14.386
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
10
970647AG2-420 GEN
Solar/Wind Harmer
0.283
20084926LAKVU GN
Adder
0.21
971183AH1-050 GEN
Solar/Wind Harmer
4.125
238183AE2-316 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
8.587
24035802GEN-Y1-012
Adder
0.26
238206AE2-263_GEN
Solar/Wind Harmer
0.002
971865AH1-452 GEN
Solar/Wind Harmer
0.503
20091326SHAW-D
Adder
0.334
972169AH1-667 GEN
Solar/Wind Harmer
0.639
20088826HIGHLAND
Solar/Wind Helper
0.93
20089226LOOKOUT
Solar/Wind Helper
0.49
964201AG1-281 GEN
Solar/Wind Helper
0.416
20094526CT_V3-030
Solar/Wind Helper
0.257
20082926HNSMLK 2
50/50
11.769
20083126HNSMLK 4
50/50
11.769
971703AH1-357 GEN
Solar/Wind Harmer
2.853
971707AH1-359 GEN
Solar/Wind Harmer
2.853
20334926Z1-069 C
Solar/Wind Harmer
1.059
970335AG2-220 GEN
Solar/Wind Harmer
3.421
971127AH1-005 GEN
Solar/Wind Harmer
2.494
20120126WRREN CT
Adder
8.901
203948AG1-140 C
Solar/Wind Harmer
0.251
203962AF1-287 GEN
Solar/Wind Harmer
1.723
970647AG2-420 GEN
Solar/Wind Harmer
1.698
20335126GROZ1-110
Adder
2.841
20335226CANZ2-011
Adder
2.761
20084926LAKVU GN
Adder
0.21
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
6.358
971185AH1-051 GEN
Solar/Wind Harmer
2.475
971355AH1-158 GEN
Solar/Wind Harmer
4.125
20328326MANOR_T86
Adder
0.165
238219AF1-167 C
Solar/Wind Harmer
1.049
972271AH1-720 GEN
Adder
6.781
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.94
200917MEHOOPANY_G
Solar/Wind Harmer
0.33
970679AG2-439 GEN
Solar/Wind Harmer
0.458
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.936
203854AF2-039 C
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Helper
0.504
20089026BF_G21_K23
Solar/Wind Helper
0.399
202652Y1-033 WT C
Solar/Wind Helper
0.372
20083926HOMER C3
50/50
272.069
20083826HOMER C2
50/50
257.001
20083226HNSMLK 5
50/50
11.769
20083726HOMER C1
Adder
-111.627
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.199
970663AG2-429 GEN
Solar/Wind Harmer
6.483
970663AG2-429 GEN
Solar/Wind Harmer
1.417
20084926LAKVU GN
Adder
0.236
966771AG1-548 GEN
Solar/Wind Harmer
2.769
966771AG1-548 GEN
Solar/Wind Harmer
3.462
970677AG2-438 GEN
Solar/Wind Harmer
0.927
203926AA2-133 GEN
Adder
2.454
20334726NME_Y1-047
Adder
2.206
972077AH1-588 GEN
Solar/Wind Harmer
34.236
972079AH1-589 GEN
Solar/Wind Harmer
40.417
970715AG2-457 GEN
Solar/Wind Harmer
13.266
20390726Y2-042
Adder
1.742
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.52
203961AE2-224 GEN
Solar/Wind Helper
2.523
20092526R32
Solar/Wind Helper
1.205
20091526CHSTN_FL
Solar/Wind Helper
0.389
972075AH1-587 GEN
Solar/Wind Harmer
24.541
20398826ARMNA MT
Solar/Wind Harmer
0.069
203859AF2-294 C
Solar/Wind Harmer
1.886
970313AG2-206 GEN
Solar/Wind Harmer
5.1
970305AG2-200 GEN
Solar/Wind Harmer
1.964
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.723
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Harmer
0.056
203848AF2-166 C
Solar/Wind Harmer
1.492
20084626FORWARD
Solar/Wind Helper
0.399
20088926STNY CRK
Solar/Wind Helper
0.82
20083426SW_E13_K22
Solar/Wind Helper
0.056
20088626ARWF_N39
Solar/Wind Helper
1.176
20303426NA_O38_P22
Solar/Wind Helper
0.964
203940AF1-140 C
Solar/Wind Helper
0.372
944781AF1-143 GEN
Solar/Wind Helper
2.09
203955AF1-039 C O1
Solar/Wind Helper
0.245
946071AF1-272 GEN
Solar/Wind Helper
1.627
961581Q1080_CY23
External Queue
36.97114562988281
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.012
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.369
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.185
LAGNLTFEXP_LAGN->PJM
CLTF
0.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
TVALTFEXP_TVA->PJM
CLTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.231
MECLTFEXP_MEC->PJM
CLTF
0.801
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.78 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:940.96
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
285.029
20082826HNSMLK 1
50/50
13.162
20083026HNSMLK 3
50/50
13.162
20335026MILZ1-092
50/50
4.448
20326126BLOSSBCT
50/50
4.359
970713AG2-456 GEN
Solar/Wind Harmer
17.6
971705AH1-358 GEN
Solar/Wind Harmer
5.116
971709AH1-360 GEN
Solar/Wind Harmer
5.116
944411AF1-106 GEN
Solar/Wind Harmer
3.862
959471AF2-238 GEN
Solar/Wind Harmer
1.024
970337AG2-221 GEN
Solar/Wind Harmer
3.385
970511AG2-327 GEN
Solar/Wind Harmer
1.636
203860AG1-193 C
Solar/Wind Harmer
0.475
970267AG2-176 GEN
Solar/Wind Harmer
23.253
238183AE2-316 GEN
Solar/Wind Harmer
6.305
970647AG2-420 GEN
Solar/Wind Harmer
0.338
961971AG1-040 GEN
Solar/Wind Harmer
0.876
971183AH1-050 GEN
Solar/Wind Harmer
5.782
203835AF1-098 GEN
Solar/Wind Harmer
3.35
203813AE2-344_GEN
Solar/Wind Harmer
16.003
20084926LAKVU GN
Adder
0.232
203954AE2-126 C
Solar/Wind Harmer
0.595
20072226SHAWVL 2
Adder
10.566
238206AE2-263_GEN
Solar/Wind Harmer
1.658
24035802GEN-Y1-012
Adder
0.283
971865AH1-452 GEN
Solar/Wind Harmer
1.144
20091326SHAW-D
Adder
0.426
972169AH1-667 GEN
Solar/Wind Harmer
1.167
238215AE2-248 C
Solar/Wind Harmer
0.78
20088826HIGHLAND
Solar/Wind Helper
0.858
20089226LOOKOUT
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.375
20082926HNSMLK 2
50/50
13.162
20083126HNSMLK 4
50/50
13.162
971703AH1-357 GEN
Solar/Wind Harmer
4.4
971707AH1-359 GEN
Solar/Wind Harmer
4.4
20334926Z1-069 C
Solar/Wind Harmer
4.526
944411AF1-106 GEN
Solar/Wind Harmer
0.415
970335AG2-220 GEN
Solar/Wind Harmer
5.101
971127AH1-005 GEN
Solar/Wind Harmer
3.291
20120126WRREN CT
Adder
9.836
238219AF1-167 C
Solar/Wind Harmer
2.025
970647AG2-420 GEN
Solar/Wind Harmer
2.905
971185AH1-051 GEN
Solar/Wind Harmer
3.469
971355AH1-158 GEN
Solar/Wind Harmer
4.034
203856AF2-165 C
Solar/Wind Harmer
1.693
203948AG1-140 C
Solar/Wind Harmer
0.367
959441AF2-235 GEN
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.834
203962AF1-287 GEN
Solar/Wind Harmer
2.757
957161AF2-010 GEN
Solar/Wind Harmer
10.433
203830AF1-094 GEN
Solar/Wind Harmer
0.82
20084926LAKVU GN
Adder
0.232
20335126GROZ1-110
Adder
3.099
20335226CANZ2-011
Adder
3.012
203932AE1-123
Adder
2.515
20328326MANOR_T86
Adder
0.179
972271AH1-720 GEN
Adder
7.405
941421AE2-139 GEN
Solar/Wind Harmer
3.392
200917MEHOOPANY_G
Solar/Wind Harmer
3.576
970679AG2-439 GEN
Solar/Wind Harmer
0.798
238202AE2-262_GEN
Solar/Wind Harmer
1.779
971627AH1-313 GEN
Solar/Wind Harmer
6.977
203854AF2-039 C
Solar/Wind Harmer
0.265
945751AF1-240 GEN
Solar/Wind Harmer
1.012
20089126CSLMN_L13
Solar/Wind Helper
0.471
20089026BF_G21_K23
Solar/Wind Helper
0.373
202652Y1-033 WT C
Solar/Wind Helper
0.351
972077AH1-588 GEN
Solar/Wind Harmer
52.799
972079AH1-589 GEN
Solar/Wind Harmer
43.488
970715AG2-457 GEN
Solar/Wind Harmer
17.6
972075AH1-587 GEN
Solar/Wind Harmer
38.338
20398826ARMNA MT
Solar/Wind Harmer
4.359
203859AF2-294 C
Solar/Wind Harmer
2.894
970313AG2-206 GEN
Solar/Wind Harmer
7.852
970305AG2-200 GEN
Solar/Wind Harmer
3.111
946381AF1-302 GEN
Solar/Wind Harmer
3.155
203980AG1-197 GEN
Solar/Wind Harmer
0.665
203963AG1-253 GEN
Solar/Wind Harmer
0.56
971931AH1-490 GEN
Solar/Wind Harmer
2.76
203979AG1-198 GEN
Solar/Wind Harmer
0.492
971933AH1-491 GEN
Solar/Wind Harmer
2.707
203848AF2-166 C
Solar/Wind Harmer
2.673
203947AF1-006 C
Solar/Wind Harmer
0.726
238217AF1-153 C O1
Solar/Wind Harmer
0.695
216419AE2-001 C
Solar/Wind Harmer
1.035
20084626FORWARD
Solar/Wind Helper
0.371
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.761
20088626ARWF_N39
Solar/Wind Helper
1.075
20303426NA_O38_P22
Solar/Wind Helper
0.881
203940AF1-140 C
Solar/Wind Helper
0.339
944781AF1-143 GEN
Solar/Wind Helper
1.956
203955AF1-039 C O1
Solar/Wind Helper
0.231
946071AF1-272 GEN
Solar/Wind Helper
1.436
20083826HOMER C2
50/50
269.243
20083226HNSMLK 5
50/50
13.162
940863AE2-074 GEN
Solar/Wind Harmer
3.814
203804AE2-113_GEN
Solar/Wind Harmer
8.618
970555AG2-356 GEN
Solar/Wind Harmer
3.385
970663AG2-429 GEN
Solar/Wind Harmer
11.496
970663AG2-429 GEN
Solar/Wind Harmer
1.871
20083726HOMER C1
Adder
-104.741
970677AG2-438 GEN
Solar/Wind Harmer
1.353
966771AG1-548 GEN
Solar/Wind Harmer
19.741
966771AG1-548 GEN
Solar/Wind Harmer
3.826
203846AF2-130 C
Solar/Wind Harmer
0.764
20084926LAKVU GN
Adder
0.261
203926AA2-133 GEN
Adder
2.667
20334726NME_Y1-047
Adder
2.402
20390726Y2-042
Adder
1.91
971055AG2-654 GEN
Solar/Wind Harmer
0.981
203855AF2-088 C
Solar/Wind Harmer
0.128
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.322
20091526CHSTN_FL
Solar/Wind Helper
0.335
961581Q1080_CY23
External Queue
37.79337692260742
LGEELTFEXP_LGEE->PJM
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.058
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.028
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
0.47
TVALTFEXP_TVA->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.907
MECLTFEXP_MEC->PJM
CLTF
0.656
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.55 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:930.83
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
16.726
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
5.039
970337AG2-221 GEN
Solar/Wind Harmer
3.049
970511AG2-327 GEN
Solar/Wind Harmer
1.34
970267AG2-176 GEN
Solar/Wind Harmer
18.137
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.007
203813AE2-344_GEN
Solar/Wind Harmer
12.608
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
5.201
238183AE2-316 GEN
Solar/Wind Harmer
0.006
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
0.003
971865AH1-452 GEN
Solar/Wind Harmer
0.634
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
0.805
238215AE2-248 C
Solar/Wind Harmer
0.525
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
3.597
971707AH1-359 GEN
Solar/Wind Harmer
3.597
20334926Z1-069 C
Solar/Wind Harmer
1.335
970335AG2-220 GEN
Solar/Wind Harmer
4.313
971127AH1-005 GEN
Solar/Wind Harmer
3.145
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.316
203962AF1-287 GEN
Solar/Wind Harmer
2.172
970647AG2-420 GEN
Solar/Wind Harmer
2.14
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.002
957161AF2-010 GEN
Solar/Wind Harmer
8.016
971185AH1-051 GEN
Solar/Wind Harmer
3.121
971355AH1-158 GEN
Solar/Wind Harmer
5.201
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.323
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
0.416
970679AG2-439 GEN
Solar/Wind Harmer
0.577
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.962
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.687
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
972077AH1-588 GEN
Solar/Wind Harmer
43.163
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
16.726
972075AH1-587 GEN
Solar/Wind Harmer
30.94
20398826ARMNA MT
Solar/Wind Harmer
0.087
203859AF2-294 C
Solar/Wind Harmer
2.377
970313AG2-206 GEN
Solar/Wind Harmer
6.43
970305AG2-200 GEN
Solar/Wind Harmer
2.477
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.503
971931AH1-490 GEN
Solar/Wind Harmer
2.172
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
2.093
203947AF1-006 C
Solar/Wind Harmer
0.07
203848AF2-166 C
Solar/Wind Harmer
1.881
216419AE2-001 C
Solar/Wind Harmer
0.704
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
0.011
970555AG2-356 GEN
Solar/Wind Harmer
2.772
970663AG2-429 GEN
Solar/Wind Harmer
8.174
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
3.492
966771AG1-548 GEN
Solar/Wind Harmer
4.365
970677AG2-438 GEN
Solar/Wind Harmer
1.168
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.655
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:898.94
MW Contribution:4.22
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
277.61
20083826HOMER C2
50/50
262.235
20083226HNSMLK 5
50/50
12.408
940863AE2-074 GEN
Solar/Wind Harmer
3.667
203804AE2-113_GEN
Solar/Wind Harmer
8.186
970555AG2-356 GEN
Solar/Wind Harmer
3.251
20083726HOMER C1
Adder
-109.082
970663AG2-429 GEN
Solar/Wind Harmer
9.987
970663AG2-429 GEN
Solar/Wind Harmer
1.626
970677AG2-438 GEN
Solar/Wind Harmer
1.264
966771AG1-548 GEN
Solar/Wind Harmer
18.467
966771AG1-548 GEN
Solar/Wind Harmer
3.579
20084926LAKVU GN
Adder
0.248
203846AF2-130 C
Solar/Wind Harmer
0.679
203926AA2-133 GEN
Adder
2.542
20334726NME_Y1-047
Adder
2.287
20390726Y2-042
Adder
1.81
203855AF2-088 C
Solar/Wind Harmer
0.112
971055AG2-654 GEN
Solar/Wind Harmer
0.641
20092526R32
Solar/Wind Helper
1.178
203961AE2-224 GEN
Solar/Wind Helper
2.456
20091526CHSTN_FL
Solar/Wind Helper
0.371
20082826HNSMLK 1
50/50
12.408
20083026HNSMLK 3
50/50
12.408
20335026MILZ1-092
50/50
4.281
20326126BLOSSBCT
50/50
4.187
970713AG2-456 GEN
Solar/Wind Harmer
16.899
971705AH1-358 GEN
Solar/Wind Harmer
4.912
971709AH1-360 GEN
Solar/Wind Harmer
4.912
944411AF1-106 GEN
Solar/Wind Harmer
3.717
959471AF2-238 GEN
Solar/Wind Harmer
0.983
970337AG2-221 GEN
Solar/Wind Harmer
3.251
970511AG2-327 GEN
Solar/Wind Harmer
1.571
970267AG2-176 GEN
Solar/Wind Harmer
21.827
203860AG1-193 C
Solar/Wind Harmer
0.44
961971AG1-040 GEN
Solar/Wind Harmer
0.824
238183AE2-316 GEN
Solar/Wind Harmer
5.58
970647AG2-420 GEN
Solar/Wind Harmer
0.308
203835AF1-098 GEN
Solar/Wind Harmer
3.172
203813AE2-344_GEN
Solar/Wind Harmer
15.102
971183AH1-050 GEN
Solar/Wind Harmer
5.235
20084926LAKVU GN
Adder
0.22
203954AE2-126 C
Solar/Wind Harmer
0.542
20072226SHAWVL 2
Adder
9.429
24035802GEN-Y1-012
Adder
0.271
238206AE2-263_GEN
Solar/Wind Harmer
1.476
20091326SHAW-D
Adder
0.373
972169AH1-667 GEN
Solar/Wind Harmer
1.02
971865AH1-452 GEN
Solar/Wind Harmer
0.761
20088826HIGHLAND
Solar/Wind Helper
0.908
20089226LOOKOUT
Solar/Wind Helper
0.481
964201AG1-281 GEN
Solar/Wind Helper
0.403
20094526CT_V3-030
Solar/Wind Helper
0.241
20082926HNSMLK 2
50/50
12.408
20083126HNSMLK 4
50/50
12.408
971703AH1-357 GEN
Solar/Wind Harmer
4.225
971707AH1-359 GEN
Solar/Wind Harmer
4.225
20334926Z1-069 C
Solar/Wind Harmer
4.357
944411AF1-106 GEN
Solar/Wind Harmer
0.4
970335AG2-220 GEN
Solar/Wind Harmer
4.898
971127AH1-005 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
9.318
203948AG1-140 C
Solar/Wind Harmer
0.348
970647AG2-420 GEN
Solar/Wind Harmer
2.646
962511AG1-100 GEN
Solar/Wind Harmer
0.787
203962AF1-287 GEN
Solar/Wind Harmer
2.602
971185AH1-051 GEN
Solar/Wind Harmer
3.141
971355AH1-158 GEN
Solar/Wind Harmer
3.653
203856AF2-165 C
Solar/Wind Harmer
1.536
238219AF1-167 C
Solar/Wind Harmer
1.719
959441AF2-235 GEN
Solar/Wind Harmer
0.383
957161AF2-010 GEN
Solar/Wind Harmer
9.735
203830AF1-094 GEN
Solar/Wind Harmer
0.766
20335126GROZ1-110
Adder
2.949
20335226CANZ2-011
Adder
2.867
20084926LAKVU GN
Adder
0.22
20328326MANOR_T86
Adder
0.171
203932AE1-123
Adder
2.197
972271AH1-720 GEN
Adder
7.041
941421AE2-139 GEN
Solar/Wind Harmer
3.22
200917MEHOOPANY_G
Solar/Wind Harmer
3.404
970679AG2-439 GEN
Solar/Wind Harmer
0.756
238202AE2-262_GEN
Solar/Wind Harmer
1.583
971627AH1-313 GEN
Solar/Wind Harmer
6.208
203854AF2-039 C
Solar/Wind Harmer
0.232
945751AF1-240 GEN
Solar/Wind Harmer
0.814
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.366
972077AH1-588 GEN
Solar/Wind Harmer
50.696
972079AH1-589 GEN
Solar/Wind Harmer
41.756
970715AG2-457 GEN
Solar/Wind Harmer
16.899
972075AH1-587 GEN
Solar/Wind Harmer
36.551
20398826ARMNA MT
Solar/Wind Harmer
4.195
203859AF2-294 C
Solar/Wind Harmer
2.784
970313AG2-206 GEN
Solar/Wind Harmer
7.539
970305AG2-200 GEN
Solar/Wind Harmer
2.947
203980AG1-197 GEN
Solar/Wind Harmer
0.626
203963AG1-253 GEN
Solar/Wind Harmer
0.532
946381AF1-302 GEN
Solar/Wind Harmer
2.792
971931AH1-490 GEN
Solar/Wind Harmer
2.603
203979AG1-198 GEN
Solar/Wind Harmer
0.46
971933AH1-491 GEN
Solar/Wind Harmer
2.528
203947AF1-006 C
Solar/Wind Harmer
0.687
203848AF2-166 C
Solar/Wind Harmer
2.378
238217AF1-153 C O1
Solar/Wind Harmer
0.626
216419AE2-001 C
Solar/Wind Harmer
0.898
20084626FORWARD
Solar/Wind Helper
0.391
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
20088626ARWF_N39
Solar/Wind Helper
1.142
20303426NA_O38_P22
Solar/Wind Helper
0.936
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.052
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.602
961581Q1080_CY23
External Queue
37.30971908569336
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.867
LAGNLTFEXP_LAGN->PJM
CLTF
0.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.036
TVALTFEXP_TVA->PJM
CLTF
0.277
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.138
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.2 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1295.55
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
957561AF2-050 GEN
Solar/Wind Harmer
14.434
203843AF2-002_GEN
Solar/Wind Harmer
2.795
970631AG2-411 GEN
Solar/Wind Harmer
17.564
20088826HIGHLAND
Solar/Wind Harmer
4.455
971423AH1-203 GEN
Solar/Wind Harmer
17.686
964201AG1-281 GEN
Solar/Wind Harmer
1.503
20089226LOOKOUT
Solar/Wind Harmer
1.785
203987AE2-118 C
Solar/Wind Harmer
4.021
970713AG2-456 GEN
Solar/Wind Harmer
16.005
971705AH1-358 GEN
Solar/Wind Harmer
4.652
971709AH1-360 GEN
Solar/Wind Harmer
4.652
971279AH1-102 GEN
Solar/Wind Harmer
16.075
20094526CT_V3-030
Solar/Wind Harmer
1.376
964391AG1-301 GEN
Solar/Wind Harmer
1.116
20082826HNSMLK 1
Adder
10.051
20083026HNSMLK 3
Adder
10.051
20326126BLOSSBCT
Adder
3.791
20335026MILZ1-092
Adder
3.765
944411AF1-106 GEN
Solar/Wind Harmer
3.468
959471AF2-238 GEN
Solar/Wind Harmer
0.945
970337AG2-221 GEN
Solar/Wind Harmer
3.124
203954AE2-126 C
Solar/Wind Harmer
0.919
970511AG2-327 GEN
Solar/Wind Harmer
1.504
972169AH1-667 GEN
Solar/Wind Harmer
2.64
20091326SHAW-D
Adder
0.964
238183AE2-316 GEN
Solar/Wind Harmer
6.084
20072226SHAWVL 2
Adder
18.929
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.311
971183AH1-050 GEN
Solar/Wind Harmer
5.394
970267AG2-176 GEN
Solar/Wind Harmer
19.756
238206AE2-263_GEN
Solar/Wind Harmer
3.094
961971AG1-040 GEN
Solar/Wind Harmer
0.749
203835AF1-098 GEN
Solar/Wind Harmer
2.998
238215AE2-248 C
Solar/Wind Harmer
1.943
203813AE2-344_GEN
Solar/Wind Harmer
13.78
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.691
24035802GEN-Y1-012
Adder
0.229
971865AH1-452 GEN
Solar/Wind Harmer
0.847
20080926SITHE
50/50
0.921
203857AF2-221 C
Solar/Wind Harmer
4.203
970123AG2-090 GEN
Solar/Wind Harmer
3.923
203839AF1-321 GEN
Solar/Wind Harmer
5.589
20084626FORWARD
Solar/Wind Harmer
2.204
20088626ARWF_N39
Solar/Wind Harmer
5.112
20303426NA_O38_P22
Solar/Wind Harmer
4.138
203940AF1-140 C
Solar/Wind Harmer
1.284
20088926STNY CRK
Solar/Wind Harmer
3.117
971427AH1-205 GEN
Solar/Wind Harmer
3.764
971441AH1-212 GEN
Solar/Wind Harmer
4.958
20083426SW_E13_K22
Solar/Wind Harmer
0.738
944781AF1-143 GEN
Solar/Wind Harmer
6.285
972077AH1-588 GEN
Solar/Wind Harmer
48.014
972079AH1-589 GEN
Solar/Wind Harmer
39.546
970715AG2-457 GEN
Solar/Wind Harmer
16.005
972075AH1-587 GEN
Solar/Wind Harmer
37.507
203952AE2-129 C
Solar/Wind Harmer
1.045
203946AE2-131 C
Solar/Wind Harmer
1.043
962411AG1-090 GEN
Solar/Wind Harmer
16.386
20398826ARMNA MT
Solar/Wind Harmer
3.926
203955AF1-039 C O1
Solar/Wind Harmer
0.721
203859AF2-294 C
Solar/Wind Harmer
2.598
970313AG2-206 GEN
Solar/Wind Harmer
7.221
970305AG2-200 GEN
Solar/Wind Harmer
2.986
946381AF1-302 GEN
Solar/Wind Harmer
3.044
203853AF1-134 C O1
Solar/Wind Harmer
0.868
238217AF1-153 C O1
Solar/Wind Harmer
0.857
203848AF2-166 C
Solar/Wind Harmer
2.614
203980AG1-197 GEN
Solar/Wind Harmer
0.568
216419AE2-001 C
Solar/Wind Harmer
2.453
203963AG1-253 GEN
Solar/Wind Harmer
0.49
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.419
971931AH1-490 GEN
Solar/Wind Harmer
2.369
203947AF1-006 C
Solar/Wind Harmer
0.629
20083326SEWRDB34
50/50
11.281
970125AG2-091 GEN
Solar/Wind Harmer
1.681
971879AH1-460 GEN
Solar/Wind Harmer
18.472
203841AF2-001_GEN
Solar/Wind Harmer
5.589
971419AH1-201 GEN
Solar/Wind Harmer
8.093
20079426CONEMAGH
Adder
3.005
20089126CSLMN_L13
Solar/Wind Harmer
1.834
20089026BF_G21_K23
Solar/Wind Harmer
1.452
971703AH1-357 GEN
Solar/Wind Harmer
4.001
971707AH1-359 GEN
Solar/Wind Harmer
4.001
971541AH1-268 GEN
Solar/Wind Harmer
6.841
20334926Z1-069 C
Solar/Wind Harmer
4.066
965131AG1-378 GEN
Solar/Wind Harmer
3.45
20082926HNSMLK 2
Adder
10.051
20083126HNSMLK 4
Adder
10.051
944411AF1-106 GEN
Solar/Wind Harmer
0.373
202652Y1-033 WT C
Solar/Wind Harmer
1.48
970335AG2-220 GEN
Solar/Wind Harmer
4.687
971127AH1-005 GEN
Solar/Wind Harmer
3.024
20120126WRREN CT
Adder
9.44
203854AF2-039 C
Solar/Wind Harmer
0.6
960051AF2-296 GEN
Solar/Wind Harmer
2.87
203818AF1-086 GEN
Solar/Wind Harmer
3.609
970647AG2-420 GEN
Solar/Wind Harmer
2.671
971185AH1-051 GEN
Solar/Wind Harmer
3.237
971355AH1-158 GEN
Solar/Wind Harmer
3.764
20335126GROZ1-110
Adder
3.122
20335226CANZ2-011
Adder
3.034
203856AF2-165 C
Solar/Wind Harmer
1.577
970899AG2-561 GEN
Solar/Wind Harmer
2.635
945751AF1-240 GEN
Solar/Wind Harmer
2.06
238202AE2-262_GEN
Solar/Wind Harmer
3.32
971627AH1-313 GEN
Solar/Wind Harmer
13.017
203932AE1-123
Adder
2.564
959441AF2-235 GEN
Solar/Wind Harmer
0.387
238219AF1-167 C
Solar/Wind Harmer
1.674
203948AG1-140 C
Solar/Wind Harmer
0.321
957161AF2-010 GEN
Solar/Wind Harmer
9.338
20328326MANOR_T86
Adder
0.172
203830AF1-094 GEN
Solar/Wind Harmer
0.733
203962AF1-287 GEN
Solar/Wind Harmer
2.376
962511AG1-100 GEN
Solar/Wind Harmer
0.716
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.451
972271AH1-720 GEN
Adder
7.368
200917MEHOOPANY_G
Solar/Wind Harmer
3.45
970679AG2-439 GEN
Solar/Wind Harmer
0.782
970643AG2-418 GEN
Solar/Wind Harmer
1.486
20083726HOMER C1
50/50
286.383
20083926HOMER C3
50/50
233.562
20083826HOMER C2
50/50
220.627
20050326C.SLOPE
50/50
0.843
203961AE2-224 GEN
Solar/Wind Harmer
8.743
20092526R32
Solar/Wind Harmer
4.774
203844AF2-092 C
Solar/Wind Harmer
3.155
203850AG1-041 C
Solar/Wind Harmer
3.148
20091526CHSTN_FL
Solar/Wind Harmer
2.073
940863AE2-074 GEN
Solar/Wind Harmer
3.456
20090526Q36
Solar/Wind Harmer
3.014
203993AD2-133_GEN1
Solar/Wind Harmer
3.014
941231AE2-117 GEN
Solar/Wind Harmer
1.126
203804AE2-113_GEN
Solar/Wind Harmer
8.719
965121AG1-377 GEN
Solar/Wind Harmer
3.45
20083226HNSMLK 5
Adder
10.051
970555AG2-356 GEN
Solar/Wind Harmer
3.124
203855AF2-088 C
Solar/Wind Harmer
0.289
970663AG2-429 GEN
Solar/Wind Harmer
9.219
970663AG2-429 GEN
Solar/Wind Harmer
1.501
203846AF2-130 C
Solar/Wind Harmer
0.747
970677AG2-438 GEN
Solar/Wind Harmer
1.209
966771AG1-548 GEN
Solar/Wind Harmer
17.6
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.229
203926AA2-133 GEN
Adder
2.573
20334726NME_Y1-047
Adder
2.318
20390726Y2-042
Adder
1.871
971055AG2-654 GEN
Solar/Wind Harmer
0.552
961581Q1080_CY23
External Queue
28.047279357910156
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.231
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.124
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.14
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.211
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.273

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1283.85
MW Contribution:4.06
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.653
970631AG2-411 GEN
Solar/Wind Harmer
16.66
957561AF2-050 GEN
Solar/Wind Harmer
12.617
20088826HIGHLAND
Solar/Wind Harmer
4.07
971423AH1-203 GEN
Solar/Wind Harmer
16.651
964201AG1-281 GEN
Solar/Wind Harmer
1.366
970713AG2-456 GEN
Solar/Wind Harmer
16.23
971705AH1-358 GEN
Solar/Wind Harmer
4.718
971709AH1-360 GEN
Solar/Wind Harmer
4.718
20089226LOOKOUT
Solar/Wind Harmer
1.689
203987AE2-118 C
Solar/Wind Harmer
3.598
971279AH1-102 GEN
Solar/Wind Harmer
14.659
20094526CT_V3-030
Solar/Wind Harmer
1.254
20082826HNSMLK 1
Adder
10.267
20083026HNSMLK 3
Adder
10.267
20335026MILZ1-092
Adder
3.824
944411AF1-106 GEN
Solar/Wind Harmer
3.523
20326126BLOSSBCT
Adder
3.84
964391AG1-301 GEN
Solar/Wind Harmer
1
959471AF2-238 GEN
Solar/Wind Harmer
0.957
970337AG2-221 GEN
Solar/Wind Harmer
3.165
970511AG2-327 GEN
Solar/Wind Harmer
1.524
203954AE2-126 C
Solar/Wind Harmer
0.895
238183AE2-316 GEN
Solar/Wind Harmer
6.061
972169AH1-667 GEN
Solar/Wind Harmer
2.525
20091326SHAW-D
Adder
0.922
203860AG1-193 C
Solar/Wind Harmer
0.421
970647AG2-420 GEN
Solar/Wind Harmer
0.312
970267AG2-176 GEN
Solar/Wind Harmer
20.083
971183AH1-050 GEN
Solar/Wind Harmer
5.417
20072226SHAWVL 2
Adder
18.247
961971AG1-040 GEN
Solar/Wind Harmer
0.761
203835AF1-098 GEN
Solar/Wind Harmer
3.037
238206AE2-263_GEN
Solar/Wind Harmer
2.973
203813AE2-344_GEN
Solar/Wind Harmer
14.003
20084926LAKVU GN
Adder
0.206
238215AE2-248 C
Solar/Wind Harmer
1.842
970643AG2-418 GEN
Solar/Wind Harmer
0.625
24035802GEN-Y1-012
Adder
0.234
971865AH1-452 GEN
Solar/Wind Harmer
0.861
20080926SITHE
50/50
0.948
203839AF1-321 GEN
Solar/Wind Harmer
5.307
20084626FORWARD
Solar/Wind Harmer
2.09
203857AF2-221 C
Solar/Wind Harmer
3.907
970123AG2-090 GEN
Solar/Wind Harmer
3.647
20088926STNY CRK
Solar/Wind Harmer
2.928
971427AH1-205 GEN
Solar/Wind Harmer
3.536
20088626ARWF_N39
Solar/Wind Harmer
4.477
20303426NA_O38_P22
Solar/Wind Harmer
3.625
203940AF1-140 C
Solar/Wind Harmer
1.175
20083426SW_E13_K22
Solar/Wind Harmer
0.698
971441AH1-212 GEN
Solar/Wind Harmer
4.486
972077AH1-588 GEN
Solar/Wind Harmer
48.69
972079AH1-589 GEN
Solar/Wind Harmer
40.103
970715AG2-457 GEN
Solar/Wind Harmer
16.23
944781AF1-143 GEN
Solar/Wind Harmer
5.944
972075AH1-587 GEN
Solar/Wind Harmer
37.76
20398826ARMNA MT
Solar/Wind Harmer
3.987
203952AE2-129 C
Solar/Wind Harmer
0.978
203946AE2-131 C
Solar/Wind Harmer
0.976
962411AG1-090 GEN
Solar/Wind Harmer
15.339
203859AF2-294 C
Solar/Wind Harmer
2.639
970313AG2-206 GEN
Solar/Wind Harmer
7.317
970305AG2-200 GEN
Solar/Wind Harmer
3.008
203955AF1-039 C O1
Solar/Wind Harmer
0.681
946381AF1-302 GEN
Solar/Wind Harmer
3.033
238217AF1-153 C O1
Solar/Wind Harmer
0.842
203853AF1-134 C O1
Solar/Wind Harmer
0.816
203848AF2-166 C
Solar/Wind Harmer
2.611
203980AG1-197 GEN
Solar/Wind Harmer
0.577
203963AG1-253 GEN
Solar/Wind Harmer
0.498
203979AG1-198 GEN
Solar/Wind Harmer
0.445
971933AH1-491 GEN
Solar/Wind Harmer
2.447
971931AH1-490 GEN
Solar/Wind Harmer
2.408
216419AE2-001 C
Solar/Wind Harmer
2.331
203947AF1-006 C
Solar/Wind Harmer
0.639
20083326SEWRDB34
50/50
8.898
20079426CONEMAGH
50/50
2.901
203841AF2-001_GEN
Solar/Wind Harmer
5.307
971879AH1-460 GEN
Solar/Wind Harmer
17.329
970125AG2-091 GEN
Solar/Wind Harmer
1.563
971419AH1-201 GEN
Solar/Wind Harmer
7.603
971703AH1-357 GEN
Solar/Wind Harmer
4.058
971707AH1-359 GEN
Solar/Wind Harmer
4.058
20334926Z1-069 C
Solar/Wind Harmer
4.13
20089126CSLMN_L13
Solar/Wind Harmer
1.734
20089026BF_G21_K23
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
6.238
20082926HNSMLK 2
Adder
10.267
20083126HNSMLK 4
Adder
10.267
944411AF1-106 GEN
Solar/Wind Harmer
0.379
965131AG1-378 GEN
Solar/Wind Harmer
3.229
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.064
20120126WRREN CT
Adder
9.509
202652Y1-033 WT C
Solar/Wind Harmer
1.4
203854AF2-039 C
Solar/Wind Harmer
0.573
960051AF2-296 GEN
Solar/Wind Harmer
2.698
970647AG2-420 GEN
Solar/Wind Harmer
2.687
971185AH1-051 GEN
Solar/Wind Harmer
3.25
971355AH1-158 GEN
Solar/Wind Harmer
3.779
20335126GROZ1-110
Adder
3.135
20335226CANZ2-011
Adder
3.047
203856AF2-165 C
Solar/Wind Harmer
1.584
203818AF1-086 GEN
Solar/Wind Harmer
3.348
203932AE1-123
Adder
2.548
959441AF2-235 GEN
Solar/Wind Harmer
0.389
945751AF1-240 GEN
Solar/Wind Harmer
1.977
238202AE2-262_GEN
Solar/Wind Harmer
3.19
971627AH1-313 GEN
Solar/Wind Harmer
12.507
238219AF1-167 C
Solar/Wind Harmer
1.682
203948AG1-140 C
Solar/Wind Harmer
0.326
957161AF2-010 GEN
Solar/Wind Harmer
9.444
203830AF1-094 GEN
Solar/Wind Harmer
0.741
20328326MANOR_T86
Adder
0.174
970899AG2-561 GEN
Solar/Wind Harmer
2.417
203962AF1-287 GEN
Solar/Wind Harmer
2.414
962511AG1-100 GEN
Solar/Wind Harmer
0.728
20084926LAKVU GN
Adder
0.206
941421AE2-139 GEN
Solar/Wind Harmer
3.462
972271AH1-720 GEN
Adder
7.407
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.345
20083726HOMER C1
50/50
294.677
20083926HOMER C3
50/50
239.758
20083826HOMER C2
50/50
226.48
20050326C.SLOPE
50/50
0.759
203961AE2-224 GEN
Solar/Wind Harmer
7.642
20092526R32
Solar/Wind Harmer
4.361
203844AF2-092 C
Solar/Wind Harmer
2.929
203850AG1-041 C
Solar/Wind Harmer
2.914
20091526CHSTN_FL
Solar/Wind Harmer
1.885
940863AE2-074 GEN
Solar/Wind Harmer
3.506
203804AE2-113_GEN
Solar/Wind Harmer
8.75
20090526Q36
Solar/Wind Harmer
2.784
203993AD2-133_GEN1
Solar/Wind Harmer
2.784
20083226HNSMLK 5
Adder
10.267
941231AE2-117 GEN
Solar/Wind Harmer
1.012
965121AG1-377 GEN
Solar/Wind Harmer
3.229
970555AG2-356 GEN
Solar/Wind Harmer
3.165
203855AF2-088 C
Solar/Wind Harmer
0.276
970663AG2-429 GEN
Solar/Wind Harmer
9.296
970663AG2-429 GEN
Solar/Wind Harmer
1.513
203846AF2-130 C
Solar/Wind Harmer
0.746
970677AG2-438 GEN
Solar/Wind Harmer
1.223
966771AG1-548 GEN
Solar/Wind Harmer
17.81
966771AG1-548 GEN
Solar/Wind Harmer
3.452
20084926LAKVU GN
Adder
0.232
203926AA2-133 GEN
Adder
2.594
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.883
971055AG2-654 GEN
Solar/Wind Harmer
0.566
961581Q1080_CY23
External Queue
29.164003372192383
WECLTFEXP_WEC->PJM
CLTF
0.019
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.208
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.884
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.059
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
MECLTFEXP_MEC->PJM
CLTF
0.022

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:3.96
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
971865AH1-452 GEN
Solar/Wind Harmer
0.778
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
961581Q1080_CY23
External Queue
20.78413963317871
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:3.96
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
971865AH1-452 GEN
Solar/Wind Harmer
0.778
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
961581Q1080_CY23
External Queue
20.78413963317871
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.4 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
243.439
20083926HOMER C3
50/50
210.642
20083826HOMER C2
50/50
198.976
20050326C.SLOPE
50/50
0.616
203961AE2-224 GEN
Solar/Wind Harmer
6.321
20092526R32
Solar/Wind Harmer
3.549
203844AF2-092 C
Solar/Wind Harmer
2.38
203850AG1-041 C
Solar/Wind Harmer
2.367
940863AE2-074 GEN
Solar/Wind Harmer
3.015
20091526CHSTN_FL
Solar/Wind Harmer
1.526
20083226HNSMLK 5
Adder
10.092
203804AE2-113_GEN
Solar/Wind Harmer
7.305
20090526Q36
Solar/Wind Harmer
2.226
203993AD2-133_GEN1
Solar/Wind Harmer
2.226
970555AG2-356 GEN
Solar/Wind Harmer
2.752
941231AE2-117 GEN
Solar/Wind Harmer
0.83
965121AG1-377 GEN
Solar/Wind Harmer
2.555
203855AF2-088 C
Solar/Wind Harmer
0.215
20084926LAKVU GN
Adder
0.202
966771AG1-548 GEN
Solar/Wind Harmer
14.481
966771AG1-548 GEN
Solar/Wind Harmer
2.806
970677AG2-438 GEN
Solar/Wind Harmer
0.986
203926AA2-133 GEN
Adder
2.278
20334726NME_Y1-047
Adder
2.067
203846AF2-130 C
Solar/Wind Harmer
0.43
20390726Y2-042
Adder
1.69
20083326SEWRDB34
50/50
7.4
20079426CONEMAGH
50/50
2.323
203841AF2-001_GEN
Solar/Wind Harmer
4.32
971879AH1-460 GEN
Solar/Wind Harmer
14.111
970125AG2-091 GEN
Solar/Wind Harmer
1.273
971419AH1-201 GEN
Solar/Wind Harmer
6.178
971703AH1-357 GEN
Solar/Wind Harmer
3.475
971707AH1-359 GEN
Solar/Wind Harmer
3.475
20082926HNSMLK 2
Adder
10.092
20083126HNSMLK 4
Adder
10.092
20334926Z1-069 C
Solar/Wind Harmer
3.568
20089126CSLMN_L13
Solar/Wind Harmer
1.405
20089026BF_G21_K23
Solar/Wind Harmer
1.112
944411AF1-106 GEN
Solar/Wind Harmer
0.33
971541AH1-268 GEN
Solar/Wind Harmer
4.643
970335AG2-220 GEN
Solar/Wind Harmer
4.14
971127AH1-005 GEN
Solar/Wind Harmer
2.671
965131AG1-378 GEN
Solar/Wind Harmer
2.555
20120126WRREN CT
Adder
8.032
202652Y1-033 WT C
Solar/Wind Harmer
1.127
20335126GROZ1-110
Adder
2.696
20335226CANZ2-011
Adder
2.62
203854AF2-039 C
Solar/Wind Harmer
0.446
203948AG1-140 C
Solar/Wind Harmer
0.284
20328326MANOR_T86
Adder
0.152
962511AG1-100 GEN
Solar/Wind Harmer
0.64
203962AF1-287 GEN
Solar/Wind Harmer
2.116
20084926LAKVU GN
Adder
0.18
238202AE2-262_GEN
Solar/Wind Harmer
2.525
971627AH1-313 GEN
Solar/Wind Harmer
9.899
941421AE2-139 GEN
Solar/Wind Harmer
3
203830AF1-094 GEN
Solar/Wind Harmer
0.597
957161AF2-010 GEN
Solar/Wind Harmer
7.569
972271AH1-720 GEN
Adder
6.453
960051AF2-296 GEN
Solar/Wind Harmer
1.946
970647AG2-420 GEN
Solar/Wind Harmer
1.901
959441AF2-235 GEN
Solar/Wind Harmer
0.277
203856AF2-165 C
Solar/Wind Harmer
1.079
971185AH1-051 GEN
Solar/Wind Harmer
2.193
971355AH1-158 GEN
Solar/Wind Harmer
2.55
203818AF1-086 GEN
Solar/Wind Harmer
2.263
200917MEHOOPANY_G
Solar/Wind Harmer
3.077
970899AG2-561 GEN
Solar/Wind Harmer
1.478
970679AG2-439 GEN
Solar/Wind Harmer
0.706
945751AF1-240 GEN
Solar/Wind Harmer
1.071
203932AE1-123
Adder
1.25
970643AG2-418 GEN
Solar/Wind Harmer
1.143
20080926SITHE
50/50
0.783
203839AF1-321 GEN
Solar/Wind Harmer
4.32
20084626FORWARD
Solar/Wind Harmer
1.702
203857AF2-221 C
Solar/Wind Harmer
3.182
970123AG2-090 GEN
Solar/Wind Harmer
2.97
20088626ARWF_N39
Solar/Wind Harmer
3.702
20303426NA_O38_P22
Solar/Wind Harmer
2.997
20088926STNY CRK
Solar/Wind Harmer
2.379
971427AH1-205 GEN
Solar/Wind Harmer
2.873
203940AF1-140 C
Solar/Wind Harmer
0.954
20083426SW_E13_K22
Solar/Wind Harmer
0.567
971441AH1-212 GEN
Solar/Wind Harmer
3.609
972077AH1-588 GEN
Solar/Wind Harmer
41.7
972079AH1-589 GEN
Solar/Wind Harmer
34.346
970715AG2-457 GEN
Solar/Wind Harmer
13.9
944781AF1-143 GEN
Solar/Wind Harmer
4.814
972075AH1-587 GEN
Solar/Wind Harmer
31.782
20398826ARMNA MT
Solar/Wind Harmer
3.475
203859AF2-294 C
Solar/Wind Harmer
2.31
970313AG2-206 GEN
Solar/Wind Harmer
6.378
203952AE2-129 C
Solar/Wind Harmer
0.774
203946AE2-131 C
Solar/Wind Harmer
0.772
962411AG1-090 GEN
Solar/Wind Harmer
12.137
970305AG2-200 GEN
Solar/Wind Harmer
2.54
203955AF1-039 C O1
Solar/Wind Harmer
0.548
203980AG1-197 GEN
Solar/Wind Harmer
0.51
203963AG1-253 GEN
Solar/Wind Harmer
0.433
971931AH1-490 GEN
Solar/Wind Harmer
2.117
946381AF1-302 GEN
Solar/Wind Harmer
2.173
238217AF1-153 C O1
Solar/Wind Harmer
0.613
203947AF1-006 C
Solar/Wind Harmer
0.558
203979AG1-198 GEN
Solar/Wind Harmer
0.359
971933AH1-491 GEN
Solar/Wind Harmer
1.973
203853AF1-134 C O1
Solar/Wind Harmer
0.588
216419AE2-001 C
Solar/Wind Harmer
1.864
203848AF2-166 C
Solar/Wind Harmer
1.507
946071AF1-272 GEN
Solar/Wind Helper
1.501
203843AF2-002_GEN
Solar/Wind Harmer
2.16
970631AG2-411 GEN
Solar/Wind Harmer
13.565
957561AF2-050 GEN
Solar/Wind Harmer
10.435
20088826HIGHLAND
Solar/Wind Harmer
3.312
971423AH1-203 GEN
Solar/Wind Harmer
13.529
964201AG1-281 GEN
Solar/Wind Harmer
1.112
970713AG2-456 GEN
Solar/Wind Harmer
13.9
971705AH1-358 GEN
Solar/Wind Harmer
4.041
971709AH1-360 GEN
Solar/Wind Harmer
4.041
20082826HNSMLK 1
Adder
10.092
20083026HNSMLK 3
Adder
10.092
20089226LOOKOUT
Solar/Wind Harmer
1.368
203987AE2-118 C
Solar/Wind Harmer
2.954
20335026MILZ1-092
Adder
3.336
944411AF1-106 GEN
Solar/Wind Harmer
3.073
20326126BLOSSBCT
Adder
3.329
959471AF2-238 GEN
Solar/Wind Harmer
0.832
970337AG2-221 GEN
Solar/Wind Harmer
2.752
964391AG1-301 GEN
Solar/Wind Harmer
0.822
971279AH1-102 GEN
Solar/Wind Harmer
10.909
970511AG2-327 GEN
Solar/Wind Harmer
1.329
20094526CT_V3-030
Solar/Wind Harmer
0.939
970267AG2-176 GEN
Solar/Wind Harmer
17.808
203954AE2-126 C
Solar/Wind Harmer
0.708
203860AG1-193 C
Solar/Wind Harmer
0.342
961971AG1-040 GEN
Solar/Wind Harmer
0.671
972169AH1-667 GEN
Solar/Wind Harmer
1.964
20091326SHAW-D
Adder
0.717
203835AF1-098 GEN
Solar/Wind Harmer
2.618
203813AE2-344_GEN
Solar/Wind Harmer
12.284
20072226SHAWVL 2
Adder
14.287
238183AE2-316 GEN
Solar/Wind Harmer
4.342
20084926LAKVU GN
Adder
0.18
238206AE2-263_GEN
Solar/Wind Harmer
2.353
970647AG2-420 GEN
Solar/Wind Harmer
0.221
238215AE2-248 C
Solar/Wind Harmer
1.476
971183AH1-050 GEN
Solar/Wind Harmer
3.655
970643AG2-418 GEN
Solar/Wind Harmer
0.531
24035802GEN-Y1-012
Adder
0.199
961581Q1080_CY23
External Queue
25.98905372619629
G-007ALTFEXP_G-007A->PJM
CMTX
0.762
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
CBM NorthLTFEXP_CBM-N->PJM
CBM
32.723
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.438
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.168
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.643
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.926
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-016A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-016A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1068.29
MW Contribution:3.27
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
239.414
20083926HOMER C3
50/50
193.563
20083826HOMER C2
50/50
182.843
20050326C.SLOPE
50/50
0.672
20092526R32
Solar/Wind Harmer
3.88
203844AF2-092 C
Solar/Wind Harmer
2.616
203850AG1-041 C
Solar/Wind Harmer
2.599
203961AE2-224 GEN
Solar/Wind Harmer
6.52
20091526CHSTN_FL
Solar/Wind Harmer
1.648
940863AE2-074 GEN
Solar/Wind Harmer
2.833
20090526Q36
Solar/Wind Harmer
2.379
203993AD2-133_GEN1
Solar/Wind Harmer
2.379
203804AE2-113_GEN
Solar/Wind Harmer
7.059
941231AE2-117 GEN
Solar/Wind Harmer
0.874
20083226HNSMLK 5
Adder
8.075
965121AG1-377 GEN
Solar/Wind Harmer
2.713
970555AG2-356 GEN
Solar/Wind Harmer
2.592
203855AF2-088 C
Solar/Wind Harmer
0.226
970663AG2-429 GEN
Solar/Wind Harmer
7.026
970663AG2-429 GEN
Solar/Wind Harmer
1.144
203846AF2-130 C
Solar/Wind Harmer
0.565
970677AG2-438 GEN
Solar/Wind Harmer
0.946
966771AG1-548 GEN
Solar/Wind Harmer
13.787
966771AG1-548 GEN
Solar/Wind Harmer
2.672
203926AA2-133 GEN
Adder
2.166
20084926LAKVU GN
Adder
0.181
20334726NME_Y1-047
Adder
1.966
20390726Y2-042
Adder
1.612
20083326SEWRDB34
50/50
7.671
20079426CONEMAGH
50/50
2.697
203841AF2-001_GEN
Solar/Wind Harmer
4.807
971879AH1-460 GEN
Solar/Wind Harmer
15.62
970125AG2-091 GEN
Solar/Wind Harmer
1.404
971419AH1-201 GEN
Solar/Wind Harmer
6.844
20089126CSLMN_L13
Solar/Wind Harmer
1.564
20089026BF_G21_K23
Solar/Wind Harmer
1.238
971703AH1-357 GEN
Solar/Wind Harmer
3.267
971707AH1-359 GEN
Solar/Wind Harmer
3.267
20334926Z1-069 C
Solar/Wind Harmer
3.345
971541AH1-268 GEN
Solar/Wind Harmer
5.374
20082926HNSMLK 2
Adder
8.075
20083126HNSMLK 4
Adder
8.075
944411AF1-106 GEN
Solar/Wind Harmer
0.309
965131AG1-378 GEN
Solar/Wind Harmer
2.713
202652Y1-033 WT C
Solar/Wind Harmer
1.256
970335AG2-220 GEN
Solar/Wind Harmer
3.897
971127AH1-005 GEN
Solar/Wind Harmer
2.514
20120126WRREN CT
Adder
7.571
203854AF2-039 C
Solar/Wind Harmer
0.469
20335126GROZ1-110
Adder
2.585
20335226CANZ2-011
Adder
2.513
960051AF2-296 GEN
Solar/Wind Harmer
2.104
238202AE2-262_GEN
Solar/Wind Harmer
2.632
971627AH1-313 GEN
Solar/Wind Harmer
10.32
970647AG2-420 GEN
Solar/Wind Harmer
2.057
971185AH1-051 GEN
Solar/Wind Harmer
2.482
971355AH1-158 GEN
Solar/Wind Harmer
2.886
203856AF2-165 C
Solar/Wind Harmer
1.21
20328326MANOR_T86
Adder
0.144
959441AF2-235 GEN
Solar/Wind Harmer
0.298
203818AF1-086 GEN
Solar/Wind Harmer
2.51
203948AG1-140 C
Solar/Wind Harmer
0.255
203932AE1-123
Adder
1.915
941421AE2-139 GEN
Solar/Wind Harmer
2.882
957161AF2-010 GEN
Solar/Wind Harmer
7.302
203830AF1-094 GEN
Solar/Wind Harmer
0.573
972271AH1-720 GEN
Adder
6.174
203962AF1-287 GEN
Solar/Wind Harmer
1.874
962511AG1-100 GEN
Solar/Wind Harmer
0.565
238219AF1-167 C
Solar/Wind Harmer
1.261
945751AF1-240 GEN
Solar/Wind Harmer
1.444
20084926LAKVU GN
Adder
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.694
200917MEHOOPANY_G
Solar/Wind Harmer
2.926
970679AG2-439 GEN
Solar/Wind Harmer
0.674
970643AG2-418 GEN
Solar/Wind Harmer
1.197
20080926SITHE
50/50
0.77
20081226ALY HYDR
50/50
0.182
203839AF1-321 GEN
Solar/Wind Harmer
4.807
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.509
970123AG2-090 GEN
Solar/Wind Harmer
3.275
20088926STNY CRK
Solar/Wind Harmer
2.635
971427AH1-205 GEN
Solar/Wind Harmer
3.183
20083426SW_E13_K22
Solar/Wind Harmer
0.631
203940AF1-140 C
Solar/Wind Harmer
1.043
20088626ARWF_N39
Solar/Wind Harmer
3.825
20303426NA_O38_P22
Solar/Wind Harmer
3.097
971441AH1-212 GEN
Solar/Wind Harmer
3.949
944781AF1-143 GEN
Solar/Wind Harmer
5.362
972077AH1-588 GEN
Solar/Wind Harmer
39.202
972079AH1-589 GEN
Solar/Wind Harmer
32.288
970715AG2-457 GEN
Solar/Wind Harmer
13.067
972075AH1-587 GEN
Solar/Wind Harmer
30.457
20398826ARMNA MT
Solar/Wind Harmer
3.257
203952AE2-129 C
Solar/Wind Harmer
0.822
203946AE2-131 C
Solar/Wind Harmer
0.82
962411AG1-090 GEN
Solar/Wind Harmer
12.886
203955AF1-039 C O1
Solar/Wind Harmer
0.611
203859AF2-294 C
Solar/Wind Harmer
2.162
970313AG2-206 GEN
Solar/Wind Harmer
6.005
970305AG2-200 GEN
Solar/Wind Harmer
2.395
946381AF1-302 GEN
Solar/Wind Harmer
2.384
238217AF1-153 C O1
Solar/Wind Harmer
0.675
203853AF1-134 C O1
Solar/Wind Harmer
0.636
203848AF2-166 C
Solar/Wind Harmer
1.977
203980AG1-197 GEN
Solar/Wind Harmer
0.448
203963AG1-253 GEN
Solar/Wind Harmer
0.389
216419AE2-001 C
Solar/Wind Harmer
1.945
203979AG1-198 GEN
Solar/Wind Harmer
0.344
971933AH1-491 GEN
Solar/Wind Harmer
1.893
971931AH1-490 GEN
Solar/Wind Harmer
1.868
203947AF1-006 C
Solar/Wind Harmer
0.496
946071AF1-272 GEN
Solar/Wind Helper
2.07
203843AF2-002_GEN
Solar/Wind Harmer
2.403
970631AG2-411 GEN
Solar/Wind Harmer
15.016
20088826HIGHLAND
Solar/Wind Harmer
3.621
957561AF2-050 GEN
Solar/Wind Harmer
10.764
971423AH1-203 GEN
Solar/Wind Harmer
15.011
964201AG1-281 GEN
Solar/Wind Harmer
1.202
20089226LOOKOUT
Solar/Wind Harmer
1.523
970713AG2-456 GEN
Solar/Wind Harmer
13.067
971705AH1-358 GEN
Solar/Wind Harmer
3.799
971709AH1-360 GEN
Solar/Wind Harmer
3.799
203987AE2-118 C
Solar/Wind Harmer
3.112
971279AH1-102 GEN
Solar/Wind Harmer
12.627
20094526CT_V3-030
Solar/Wind Harmer
1.037
964391AG1-301 GEN
Solar/Wind Harmer
0.865
20082826HNSMLK 1
Adder
8.075
20083026HNSMLK 3
Adder
8.075
20335026MILZ1-092
Adder
3.123
944411AF1-106 GEN
Solar/Wind Harmer
2.877
20326126BLOSSBCT
Adder
3.137
959471AF2-238 GEN
Solar/Wind Harmer
0.784
970337AG2-221 GEN
Solar/Wind Harmer
2.592
970511AG2-327 GEN
Solar/Wind Harmer
1.251
203954AE2-126 C
Solar/Wind Harmer
0.727
972169AH1-667 GEN
Solar/Wind Harmer
2.063
20091326SHAW-D
Adder
0.754
238183AE2-316 GEN
Solar/Wind Harmer
4.765
20072226SHAWVL 2
Adder
14.939
203860AG1-193 C
Solar/Wind Harmer
0.325
970267AG2-176 GEN
Solar/Wind Harmer
15.603
238206AE2-263_GEN
Solar/Wind Harmer
2.453
970647AG2-420 GEN
Solar/Wind Harmer
0.239
971183AH1-050 GEN
Solar/Wind Harmer
4.136
203835AF1-098 GEN
Solar/Wind Harmer
2.378
961971AG1-040 GEN
Solar/Wind Harmer
0.591
238215AE2-248 C
Solar/Wind Harmer
1.541
203813AE2-344_GEN
Solar/Wind Harmer
10.868
20084926LAKVU GN
Adder
0.161
970643AG2-418 GEN
Solar/Wind Harmer
0.557
961581Q1080_CY23
External Queue
23.454303741455078
G-007ALTFEXP_G-007A->PJM
CMTX
0.859
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.291
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.653
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.682
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.713
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.03
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.9 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1067.2
MW Contribution:3.39
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.225
20079426CONEMAGH
50/50
2.285
203841AF2-001_GEN
Solar/Wind Harmer
4.231
971879AH1-460 GEN
Solar/Wind Harmer
13.827
970125AG2-091 GEN
Solar/Wind Harmer
1.248
971419AH1-201 GEN
Solar/Wind Harmer
6.062
971703AH1-357 GEN
Solar/Wind Harmer
3.389
971707AH1-359 GEN
Solar/Wind Harmer
3.389
20334926Z1-069 C
Solar/Wind Harmer
3.451
20089126CSLMN_L13
Solar/Wind Harmer
1.376
20089026BF_G21_K23
Solar/Wind Harmer
1.089
20082926HNSMLK 2
Adder
8.888
20083126HNSMLK 4
Adder
8.888
944411AF1-106 GEN
Solar/Wind Harmer
0.318
971541AH1-268 GEN
Solar/Wind Harmer
4.764
965131AG1-378 GEN
Solar/Wind Harmer
2.667
970335AG2-220 GEN
Solar/Wind Harmer
4.008
971127AH1-005 GEN
Solar/Wind Harmer
2.586
20120126WRREN CT
Adder
8.023
238219AF1-167 C
Solar/Wind Harmer
1.644
971185AH1-051 GEN
Solar/Wind Harmer
2.873
971355AH1-158 GEN
Solar/Wind Harmer
3.341
970647AG2-420 GEN
Solar/Wind Harmer
2.365
202652Y1-033 WT C
Solar/Wind Harmer
1.103
203854AF2-039 C
Solar/Wind Harmer
0.481
203856AF2-165 C
Solar/Wind Harmer
1.398
203932AE1-123
Adder
2.301
20335126GROZ1-110
Adder
2.667
20335226CANZ2-011
Adder
2.592
959441AF2-235 GEN
Solar/Wind Harmer
0.34
238202AE2-262_GEN
Solar/Wind Harmer
2.732
971627AH1-313 GEN
Solar/Wind Harmer
10.713
960051AF2-296 GEN
Solar/Wind Harmer
2.134
957161AF2-010 GEN
Solar/Wind Harmer
8.095
203830AF1-094 GEN
Solar/Wind Harmer
0.635
203948AG1-140 C
Solar/Wind Harmer
0.274
20328326MANOR_T86
Adder
0.149
945751AF1-240 GEN
Solar/Wind Harmer
1.622
203962AF1-287 GEN
Solar/Wind Harmer
2.05
962511AG1-100 GEN
Solar/Wind Harmer
0.619
20084926LAKVU GN
Adder
0.174
203818AF1-086 GEN
Solar/Wind Harmer
2.522
941421AE2-139 GEN
Solar/Wind Harmer
2.971
972271AH1-720 GEN
Adder
6.359
20080926SITHE
50/50
0.762
203839AF1-321 GEN
Solar/Wind Harmer
4.231
20084626FORWARD
Solar/Wind Harmer
1.668
203857AF2-221 C
Solar/Wind Harmer
3.12
970123AG2-090 GEN
Solar/Wind Harmer
2.912
20088626ARWF_N39
Solar/Wind Harmer
3.636
20303426NA_O38_P22
Solar/Wind Harmer
2.943
20088926STNY CRK
Solar/Wind Harmer
2.334
971427AH1-205 GEN
Solar/Wind Harmer
2.819
203940AF1-140 C
Solar/Wind Harmer
0.941
20083426SW_E13_K22
Solar/Wind Harmer
0.556
971441AH1-212 GEN
Solar/Wind Harmer
3.578
972077AH1-588 GEN
Solar/Wind Harmer
40.664
972079AH1-589 GEN
Solar/Wind Harmer
33.493
970715AG2-457 GEN
Solar/Wind Harmer
13.555
972075AH1-587 GEN
Solar/Wind Harmer
31.692
944781AF1-143 GEN
Solar/Wind Harmer
4.717
20398826ARMNA MT
Solar/Wind Harmer
3.349
946381AF1-302 GEN
Solar/Wind Harmer
2.826
203952AE2-129 C
Solar/Wind Harmer
0.808
203946AE2-131 C
Solar/Wind Harmer
0.806
962411AG1-090 GEN
Solar/Wind Harmer
12.668
203859AF2-294 C
Solar/Wind Harmer
2.224
970313AG2-206 GEN
Solar/Wind Harmer
6.176
970305AG2-200 GEN
Solar/Wind Harmer
2.538
238217AF1-153 C O1
Solar/Wind Harmer
0.739
203955AF1-039 C O1
Solar/Wind Harmer
0.537
203848AF2-166 C
Solar/Wind Harmer
2.332
203980AG1-197 GEN
Solar/Wind Harmer
0.493
203853AF1-134 C O1
Solar/Wind Harmer
0.645
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.095
203963AG1-253 GEN
Solar/Wind Harmer
0.419
971931AH1-490 GEN
Solar/Wind Harmer
2.046
216419AE2-001 C
Solar/Wind Harmer
1.996
203947AF1-006 C
Solar/Wind Harmer
0.539
946071AF1-272 GEN
Solar/Wind Helper
1.397
200917MEHOOPANY_G
Solar/Wind Harmer
3.008
970899AG2-561 GEN
Solar/Wind Harmer
1.709
970679AG2-439 GEN
Solar/Wind Harmer
0.692
970643AG2-418 GEN
Solar/Wind Harmer
1.17
203843AF2-002_GEN
Solar/Wind Harmer
2.116
970631AG2-411 GEN
Solar/Wind Harmer
13.291
957561AF2-050 GEN
Solar/Wind Harmer
10.23
20088826HIGHLAND
Solar/Wind Harmer
3.255
971423AH1-203 GEN
Solar/Wind Harmer
13.269
964201AG1-281 GEN
Solar/Wind Harmer
1.098
970713AG2-456 GEN
Solar/Wind Harmer
13.555
971705AH1-358 GEN
Solar/Wind Harmer
3.94
971709AH1-360 GEN
Solar/Wind Harmer
3.94
20089226LOOKOUT
Solar/Wind Harmer
1.34
20082826HNSMLK 1
Adder
8.888
20083026HNSMLK 3
Adder
8.888
203987AE2-118 C
Solar/Wind Harmer
2.942
20326126BLOSSBCT
Adder
3.229
20335026MILZ1-092
Adder
3.213
944411AF1-106 GEN
Solar/Wind Harmer
2.96
971279AH1-102 GEN
Solar/Wind Harmer
11.195
20094526CT_V3-030
Solar/Wind Harmer
0.97
964391AG1-301 GEN
Solar/Wind Harmer
0.822
238183AE2-316 GEN
Solar/Wind Harmer
5.648
959471AF2-238 GEN
Solar/Wind Harmer
0.806
970337AG2-221 GEN
Solar/Wind Harmer
2.667
970511AG2-327 GEN
Solar/Wind Harmer
1.287
203954AE2-126 C
Solar/Wind Harmer
0.756
203860AG1-193 C
Solar/Wind Harmer
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.788
970647AG2-420 GEN
Solar/Wind Harmer
0.275
972169AH1-667 GEN
Solar/Wind Harmer
2.116
20091326SHAW-D
Adder
0.773
970267AG2-176 GEN
Solar/Wind Harmer
17.249
20072226SHAWVL 2
Adder
15.552
961971AG1-040 GEN
Solar/Wind Harmer
0.65
238206AE2-263_GEN
Solar/Wind Harmer
2.547
203835AF1-098 GEN
Solar/Wind Harmer
2.563
203813AE2-344_GEN
Solar/Wind Harmer
11.887
20084926LAKVU GN
Adder
0.174
238215AE2-248 C
Solar/Wind Harmer
1.577
970643AG2-418 GEN
Solar/Wind Harmer
0.544
971865AH1-452 GEN
Solar/Wind Harmer
0.783
24035802GEN-Y1-012
Adder
0.187
20083726HOMER C1
50/50
236.905
20083926HOMER C3
50/50
197.325
20083826HOMER C2
50/50
186.396
20050326C.SLOPE
50/50
0.607
203961AE2-224 GEN
Solar/Wind Harmer
6.197
20092526R32
Solar/Wind Harmer
3.488
203844AF2-092 C
Solar/Wind Harmer
2.34
203850AG1-041 C
Solar/Wind Harmer
2.329
20091526CHSTN_FL
Solar/Wind Harmer
1.52
940863AE2-074 GEN
Solar/Wind Harmer
2.929
203804AE2-113_GEN
Solar/Wind Harmer
7.361
20083226HNSMLK 5
Adder
8.888
20090526Q36
Solar/Wind Harmer
2.277
203993AD2-133_GEN1
Solar/Wind Harmer
2.277
941231AE2-117 GEN
Solar/Wind Harmer
0.831
965121AG1-377 GEN
Solar/Wind Harmer
2.667
970555AG2-356 GEN
Solar/Wind Harmer
2.667
970663AG2-429 GEN
Solar/Wind Harmer
9.078
970663AG2-429 GEN
Solar/Wind Harmer
1.478
203855AF2-088 C
Solar/Wind Harmer
0.231
203846AF2-130 C
Solar/Wind Harmer
0.666
970677AG2-438 GEN
Solar/Wind Harmer
1.048
966771AG1-548 GEN
Solar/Wind Harmer
15.227
966771AG1-548 GEN
Solar/Wind Harmer
2.951
20084926LAKVU GN
Adder
0.196
203926AA2-133 GEN
Adder
2.229
20334726NME_Y1-047
Adder
2.021
20390726Y2-042
Adder
1.655
971055AG2-654 GEN
Solar/Wind Harmer
0.64
961581Q1080_CY23
External Queue
23.464759826660156
G-007ALTFEXP_G-007A->PJM
CMTX
0.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.335
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.644
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.93
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1058.75
MW Contribution:3.24
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.282
20079426CONEMAGH
50/50
2.35
203841AF2-001_GEN
Solar/Wind Harmer
4.57
971879AH1-460 GEN
Solar/Wind Harmer
14.79
20089126CSLMN_L13
Solar/Wind Harmer
1.958
20089026BF_G21_K23
Solar/Wind Harmer
1.55
970125AG2-091 GEN
Solar/Wind Harmer
1.325
202652Y1-033 WT C
Solar/Wind Harmer
2.051
971419AH1-201 GEN
Solar/Wind Harmer
6.959
971703AH1-357 GEN
Solar/Wind Harmer
3.236
971707AH1-359 GEN
Solar/Wind Harmer
3.236
20334926Z1-069 C
Solar/Wind Harmer
3.31
971541AH1-268 GEN
Solar/Wind Harmer
4.83
20082926HNSMLK 2
Adder
8.089
20083126HNSMLK 4
Adder
8.089
944411AF1-106 GEN
Solar/Wind Harmer
0.306
20081326YOUGH
50/50
0.084
203843AF2-002_GEN
Solar/Wind Harmer
2.285
970631AG2-411 GEN
Solar/Wind Harmer
14.34
20089226LOOKOUT
Solar/Wind Harmer
1.907
971423AH1-203 GEN
Solar/Wind Harmer
15.451
20088826HIGHLAND
Solar/Wind Harmer
3.408
957561AF2-050 GEN
Solar/Wind Harmer
10.299
964201AG1-281 GEN
Solar/Wind Harmer
1.141
970713AG2-456 GEN
Solar/Wind Harmer
12.945
971705AH1-358 GEN
Solar/Wind Harmer
3.763
971709AH1-360 GEN
Solar/Wind Harmer
3.763
203987AE2-118 C
Solar/Wind Harmer
2.967
971279AH1-102 GEN
Solar/Wind Harmer
11.348
20082826HNSMLK 1
Adder
8.089
20083026HNSMLK 3
Adder
8.089
20094526CT_V3-030
Solar/Wind Harmer
0.981
964391AG1-301 GEN
Solar/Wind Harmer
0.825
20335026MILZ1-092
Adder
3.086
944411AF1-106 GEN
Solar/Wind Harmer
2.843
20326126BLOSSBCT
Adder
3.098
959471AF2-238 GEN
Solar/Wind Harmer
0.774
970337AG2-221 GEN
Solar/Wind Harmer
2.56
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203954AE2-126 C
Solar/Wind Harmer
0.714
238183AE2-316 GEN
Solar/Wind Harmer
4.786
972169AH1-667 GEN
Solar/Wind Harmer
2.015
20091326SHAW-D
Adder
0.736
203860AG1-193 C
Solar/Wind Harmer
0.327
20072226SHAWVL 2
Adder
14.642
970267AG2-176 GEN
Solar/Wind Harmer
15.673
970647AG2-420 GEN
Solar/Wind Harmer
0.241
971183AH1-050 GEN
Solar/Wind Harmer
4.173
238206AE2-263_GEN
Solar/Wind Harmer
2.401
203835AF1-098 GEN
Solar/Wind Harmer
2.379
961971AG1-040 GEN
Solar/Wind Harmer
0.594
238215AE2-248 C
Solar/Wind Harmer
1.501
203813AE2-344_GEN
Solar/Wind Harmer
10.913
20084926LAKVU GN
Adder
0.161
970643AG2-418 GEN
Solar/Wind Harmer
0.531
965131AG1-378 GEN
Solar/Wind Harmer
2.615
970335AG2-220 GEN
Solar/Wind Harmer
3.847
971127AH1-005 GEN
Solar/Wind Harmer
2.482
20120126WRREN CT
Adder
7.527
203854AF2-039 C
Solar/Wind Harmer
0.458
20335126GROZ1-110
Adder
2.548
20335226CANZ2-011
Adder
2.476
970647AG2-420 GEN
Solar/Wind Harmer
2.074
971185AH1-051 GEN
Solar/Wind Harmer
2.504
971355AH1-158 GEN
Solar/Wind Harmer
2.911
960051AF2-296 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
1.221
238202AE2-262_GEN
Solar/Wind Harmer
2.577
971627AH1-313 GEN
Solar/Wind Harmer
10.102
20328326MANOR_T86
Adder
0.142
959441AF2-235 GEN
Solar/Wind Harmer
0.301
203932AE1-123
Adder
1.94
203948AG1-140 C
Solar/Wind Harmer
0.255
203818AF1-086 GEN
Solar/Wind Harmer
2.451
238219AF1-167 C
Solar/Wind Harmer
1.294
957161AF2-010 GEN
Solar/Wind Harmer
7.338
203830AF1-094 GEN
Solar/Wind Harmer
0.576
203962AF1-287 GEN
Solar/Wind Harmer
1.882
962511AG1-100 GEN
Solar/Wind Harmer
0.567
941421AE2-139 GEN
Solar/Wind Harmer
2.837
972271AH1-720 GEN
Adder
6.077
20084926LAKVU GN
Adder
0.161
945751AF1-240 GEN
Solar/Wind Harmer
1.446
970899AG2-561 GEN
Solar/Wind Harmer
1.668
200917MEHOOPANY_G
Solar/Wind Harmer
2.878
970679AG2-439 GEN
Solar/Wind Harmer
0.661
970643AG2-418 GEN
Solar/Wind Harmer
1.142
20080926SITHE
50/50
0.76
20084126DEEPCRK2
50/50
0.139
20084026DEEPCRK1
50/50
0.137
203839AF1-321 GEN
Solar/Wind Harmer
4.57
20084626FORWARD
Solar/Wind Harmer
1.799
20083426SW_E13_K22
Solar/Wind Harmer
0.666
944781AF1-143 GEN
Solar/Wind Harmer
6.712
203857AF2-221 C
Solar/Wind Harmer
3.312
970123AG2-090 GEN
Solar/Wind Harmer
3.091
203955AF1-039 C O1
Solar/Wind Harmer
0.999
971427AH1-205 GEN
Solar/Wind Harmer
3.237
20088926STNY CRK
Solar/Wind Harmer
2.676
203940AF1-140 C
Solar/Wind Harmer
0.989
20088626ARWF_N39
Solar/Wind Harmer
3.659
20303426NA_O38_P22
Solar/Wind Harmer
2.962
971441AH1-212 GEN
Solar/Wind Harmer
3.68
972077AH1-588 GEN
Solar/Wind Harmer
38.835
972079AH1-589 GEN
Solar/Wind Harmer
31.986
970715AG2-457 GEN
Solar/Wind Harmer
12.945
972075AH1-587 GEN
Solar/Wind Harmer
30.135
20398826ARMNA MT
Solar/Wind Harmer
3.218
203952AE2-129 C
Solar/Wind Harmer
0.792
203946AE2-131 C
Solar/Wind Harmer
0.79
962411AG1-090 GEN
Solar/Wind Harmer
12.419
203859AF2-294 C
Solar/Wind Harmer
2.136
970313AG2-206 GEN
Solar/Wind Harmer
5.928
970305AG2-200 GEN
Solar/Wind Harmer
2.381
946381AF1-302 GEN
Solar/Wind Harmer
2.395
238217AF1-153 C O1
Solar/Wind Harmer
0.67
203853AF1-134 C O1
Solar/Wind Harmer
0.621
203848AF2-166 C
Solar/Wind Harmer
1.999
203980AG1-197 GEN
Solar/Wind Harmer
0.45
203963AG1-253 GEN
Solar/Wind Harmer
0.39
203979AG1-198 GEN
Solar/Wind Harmer
0.346
971933AH1-491 GEN
Solar/Wind Harmer
1.902
216419AE2-001 C
Solar/Wind Harmer
1.896
971931AH1-490 GEN
Solar/Wind Harmer
1.876
203947AF1-006 C
Solar/Wind Harmer
0.498
946071AF1-272 GEN
Solar/Wind Helper
1.373
20083726HOMER C1
50/50
236.179
20083926HOMER C3
50/50
191.618
20083826HOMER C2
50/50
181.005
20050326C.SLOPE
50/50
0.624
203844AF2-092 C
Solar/Wind Harmer
2.526
20092526R32
Solar/Wind Harmer
3.652
203850AG1-041 C
Solar/Wind Harmer
2.501
203961AE2-224 GEN
Solar/Wind Harmer
6.239
20091526CHSTN_FL
Solar/Wind Harmer
1.558
940863AE2-074 GEN
Solar/Wind Harmer
2.804
20090526Q36
Solar/Wind Harmer
2.274
203993AD2-133_GEN1
Solar/Wind Harmer
2.274
203804AE2-113_GEN
Solar/Wind Harmer
6.982
941231AE2-117 GEN
Solar/Wind Harmer
0.834
20083226HNSMLK 5
Adder
8.089
965121AG1-377 GEN
Solar/Wind Harmer
2.615
970555AG2-356 GEN
Solar/Wind Harmer
2.56
203855AF2-088 C
Solar/Wind Harmer
0.22
970663AG2-429 GEN
Solar/Wind Harmer
7.189
970663AG2-429 GEN
Solar/Wind Harmer
1.17
203846AF2-130 C
Solar/Wind Harmer
0.571
970677AG2-438 GEN
Solar/Wind Harmer
0.951
966771AG1-548 GEN
Solar/Wind Harmer
13.849
966771AG1-548 GEN
Solar/Wind Harmer
2.684
20084926LAKVU GN
Adder
0.181
203926AA2-133 GEN
Adder
2.133
20334726NME_Y1-047
Adder
1.933
20390726Y2-042
Adder
1.582
961581Q1080_CY23
External Queue
23.213441848754883
G-007ALTFEXP_G-007A->PJM
CMTX
0.613
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.296
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.012
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.02
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.198
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.618
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT18_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT18_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.12 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1040.01
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.024
20079426CONEMAGH
50/50
2.216
203841AF2-001_GEN
Solar/Wind Harmer
4.112
971879AH1-460 GEN
Solar/Wind Harmer
13.433
970125AG2-091 GEN
Solar/Wind Harmer
1.212
971419AH1-201 GEN
Solar/Wind Harmer
5.884
971703AH1-357 GEN
Solar/Wind Harmer
3.146
971707AH1-359 GEN
Solar/Wind Harmer
3.146
20334926Z1-069 C
Solar/Wind Harmer
3.218
20089126CSLMN_L13
Solar/Wind Harmer
1.338
20089026BF_G21_K23
Solar/Wind Harmer
1.059
20082926HNSMLK 2
Adder
7.869
20083126HNSMLK 4
Adder
7.869
944411AF1-106 GEN
Solar/Wind Harmer
0.297
971541AH1-268 GEN
Solar/Wind Harmer
4.514
965131AG1-378 GEN
Solar/Wind Harmer
2.474
970335AG2-220 GEN
Solar/Wind Harmer
3.732
971127AH1-005 GEN
Solar/Wind Harmer
2.408
20120126WRREN CT
Adder
7.293
202652Y1-033 WT C
Solar/Wind Harmer
1.075
203854AF2-039 C
Solar/Wind Harmer
0.436
20335126GROZ1-110
Adder
2.463
20335226CANZ2-011
Adder
2.394
970647AG2-420 GEN
Solar/Wind Harmer
1.999
971185AH1-051 GEN
Solar/Wind Harmer
2.411
971355AH1-158 GEN
Solar/Wind Harmer
2.803
203856AF2-165 C
Solar/Wind Harmer
1.176
238202AE2-262_GEN
Solar/Wind Harmer
2.465
971627AH1-313 GEN
Solar/Wind Harmer
9.667
20328326MANOR_T86
Adder
0.137
960051AF2-296 GEN
Solar/Wind Harmer
1.928
959441AF2-235 GEN
Solar/Wind Harmer
0.29
203948AG1-140 C
Solar/Wind Harmer
0.248
203932AE1-123
Adder
1.856
957161AF2-010 GEN
Solar/Wind Harmer
7.097
238219AF1-167 C
Solar/Wind Harmer
1.243
203830AF1-094 GEN
Solar/Wind Harmer
0.557
203962AF1-287 GEN
Solar/Wind Harmer
1.825
962511AG1-100 GEN
Solar/Wind Harmer
0.55
941421AE2-139 GEN
Solar/Wind Harmer
2.737
972271AH1-720 GEN
Adder
5.866
20084926LAKVU GN
Adder
0.156
203818AF1-086 GEN
Solar/Wind Harmer
2.272
945751AF1-240 GEN
Solar/Wind Harmer
1.357
200917MEHOOPANY_G
Solar/Wind Harmer
2.776
970899AG2-561 GEN
Solar/Wind Harmer
1.52
970679AG2-439 GEN
Solar/Wind Harmer
0.636
970643AG2-418 GEN
Solar/Wind Harmer
1.086
20080926SITHE
50/50
0.743
203839AF1-321 GEN
Solar/Wind Harmer
4.112
20084626FORWARD
Solar/Wind Harmer
1.62
203857AF2-221 C
Solar/Wind Harmer
3.029
970123AG2-090 GEN
Solar/Wind Harmer
2.827
20088626ARWF_N39
Solar/Wind Harmer
3.519
20303426NA_O38_P22
Solar/Wind Harmer
2.849
20088926STNY CRK
Solar/Wind Harmer
2.266
971427AH1-205 GEN
Solar/Wind Harmer
2.737
203940AF1-140 C
Solar/Wind Harmer
0.91
20083426SW_E13_K22
Solar/Wind Harmer
0.54
971441AH1-212 GEN
Solar/Wind Harmer
3.448
972077AH1-588 GEN
Solar/Wind Harmer
37.752
972079AH1-589 GEN
Solar/Wind Harmer
31.094
970715AG2-457 GEN
Solar/Wind Harmer
12.584
944781AF1-143 GEN
Solar/Wind Harmer
4.587
972075AH1-587 GEN
Solar/Wind Harmer
29.223
20398826ARMNA MT
Solar/Wind Harmer
3.125
203952AE2-129 C
Solar/Wind Harmer
0.749
203946AE2-131 C
Solar/Wind Harmer
0.748
962411AG1-090 GEN
Solar/Wind Harmer
11.75
203859AF2-294 C
Solar/Wind Harmer
2.073
970313AG2-206 GEN
Solar/Wind Harmer
5.75
970305AG2-200 GEN
Solar/Wind Harmer
2.307
203955AF1-039 C O1
Solar/Wind Harmer
0.523
946381AF1-302 GEN
Solar/Wind Harmer
2.308
238217AF1-153 C O1
Solar/Wind Harmer
0.644
203853AF1-134 C O1
Solar/Wind Harmer
0.583
203980AG1-197 GEN
Solar/Wind Harmer
0.437
203848AF2-166 C
Solar/Wind Harmer
1.918
203963AG1-253 GEN
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.334
971933AH1-491 GEN
Solar/Wind Harmer
1.84
971931AH1-490 GEN
Solar/Wind Harmer
1.82
216419AE2-001 C
Solar/Wind Harmer
1.812
203947AF1-006 C
Solar/Wind Harmer
0.482
946071AF1-272 GEN
Solar/Wind Helper
1.553
20083726HOMER C1
50/50
231.121
20083926HOMER C3
50/50
187.218
20083826HOMER C2
50/50
176.849
20050326C.SLOPE
50/50
0.587
203961AE2-224 GEN
Solar/Wind Harmer
6.006
20092526R32
Solar/Wind Harmer
3.381
203844AF2-092 C
Solar/Wind Harmer
2.268
203850AG1-041 C
Solar/Wind Harmer
2.256
20091526CHSTN_FL
Solar/Wind Harmer
1.458
940863AE2-074 GEN
Solar/Wind Harmer
2.726
203804AE2-113_GEN
Solar/Wind Harmer
6.763
20090526Q36
Solar/Wind Harmer
2.143
203993AD2-133_GEN1
Solar/Wind Harmer
2.143
20083226HNSMLK 5
Adder
7.869
941231AE2-117 GEN
Solar/Wind Harmer
0.792
970555AG2-356 GEN
Solar/Wind Harmer
2.483
965121AG1-377 GEN
Solar/Wind Harmer
2.474
203855AF2-088 C
Solar/Wind Harmer
0.21
970663AG2-429 GEN
Solar/Wind Harmer
6.927
970663AG2-429 GEN
Solar/Wind Harmer
1.128
203846AF2-130 C
Solar/Wind Harmer
0.548
970677AG2-438 GEN
Solar/Wind Harmer
0.92
966771AG1-548 GEN
Solar/Wind Harmer
13.401
966771AG1-548 GEN
Solar/Wind Harmer
2.597
20084926LAKVU GN
Adder
0.176
203926AA2-133 GEN
Adder
2.06
20334726NME_Y1-047
Adder
1.865
20390726Y2-042
Adder
1.521
203843AF2-002_GEN
Solar/Wind Harmer
2.056
970631AG2-411 GEN
Solar/Wind Harmer
12.913
957561AF2-050 GEN
Solar/Wind Harmer
9.916
20088826HIGHLAND
Solar/Wind Harmer
3.155
971423AH1-203 GEN
Solar/Wind Harmer
12.885
964201AG1-281 GEN
Solar/Wind Harmer
1.06
970713AG2-456 GEN
Solar/Wind Harmer
12.584
971705AH1-358 GEN
Solar/Wind Harmer
3.658
971709AH1-360 GEN
Solar/Wind Harmer
3.658
20089226LOOKOUT
Solar/Wind Harmer
1.303
203987AE2-118 C
Solar/Wind Harmer
2.817
20082826HNSMLK 1
Adder
7.869
20083026HNSMLK 3
Adder
7.869
20335026MILZ1-092
Adder
2.997
944411AF1-106 GEN
Solar/Wind Harmer
2.761
20326126BLOSSBCT
Adder
3.007
971279AH1-102 GEN
Solar/Wind Harmer
10.606
964391AG1-301 GEN
Solar/Wind Harmer
0.784
20094526CT_V3-030
Solar/Wind Harmer
0.914
959471AF2-238 GEN
Solar/Wind Harmer
0.751
970337AG2-221 GEN
Solar/Wind Harmer
2.483
970511AG2-327 GEN
Solar/Wind Harmer
1.198
203954AE2-126 C
Solar/Wind Harmer
0.684
238183AE2-316 GEN
Solar/Wind Harmer
4.613
972169AH1-667 GEN
Solar/Wind Harmer
1.919
20091326SHAW-D
Adder
0.701
203860AG1-193 C
Solar/Wind Harmer
0.316
20072226SHAWVL 2
Adder
14.003
970267AG2-176 GEN
Solar/Wind Harmer
15.199
970647AG2-420 GEN
Solar/Wind Harmer
0.232
971183AH1-050 GEN
Solar/Wind Harmer
4.018
238206AE2-263_GEN
Solar/Wind Harmer
2.298
203835AF1-098 GEN
Solar/Wind Harmer
2.306
961971AG1-040 GEN
Solar/Wind Harmer
0.576
203813AE2-344_GEN
Solar/Wind Harmer
10.582
238215AE2-248 C
Solar/Wind Harmer
1.433
20084926LAKVU GN
Adder
0.156
970643AG2-418 GEN
Solar/Wind Harmer
0.505
961581Q1080_CY23
External Queue
22.834562301635742
G-007ALTFEXP_G-007A->PJM
CMTX
0.334
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.821
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.552
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.801
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.27
MW Contribution:2.78
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.25
MW Contribution:2.78
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.72 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1026.22
MW Contribution:3.25
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.078
970631AG2-411 GEN
Solar/Wind Harmer
13.05
957561AF2-050 GEN
Solar/Wind Harmer
10.037
20088826HIGHLAND
Solar/Wind Harmer
3.191
20083326SEWRDB34
50/50
7.099
20079426CONEMAGH
50/50
2.238
203841AF2-001_GEN
Solar/Wind Harmer
4.155
971879AH1-460 GEN
Solar/Wind Harmer
13.575
970125AG2-091 GEN
Solar/Wind Harmer
1.225
971419AH1-201 GEN
Solar/Wind Harmer
5.949
971703AH1-357 GEN
Solar/Wind Harmer
3.253
971707AH1-359 GEN
Solar/Wind Harmer
3.253
20334926Z1-069 C
Solar/Wind Harmer
3.321
20089126CSLMN_L13
Solar/Wind Harmer
1.352
20089026BF_G21_K23
Solar/Wind Harmer
1.07
20082926HNSMLK 2
Adder
8.333
20083126HNSMLK 4
Adder
8.333
944411AF1-106 GEN
Solar/Wind Harmer
0.306
971541AH1-268 GEN
Solar/Wind Harmer
4.602
965131AG1-378 GEN
Solar/Wind Harmer
2.555
970335AG2-220 GEN
Solar/Wind Harmer
3.853
971127AH1-005 GEN
Solar/Wind Harmer
2.486
20120126WRREN CT
Adder
7.621
202652Y1-033 WT C
Solar/Wind Harmer
1.085
203854AF2-039 C
Solar/Wind Harmer
0.455
20335126GROZ1-110
Adder
2.552
20335226CANZ2-011
Adder
2.481
970647AG2-420 GEN
Solar/Wind Harmer
2.163
971185AH1-051 GEN
Solar/Wind Harmer
2.617
971355AH1-158 GEN
Solar/Wind Harmer
3.044
203856AF2-165 C
Solar/Wind Harmer
1.275
203932AE1-123
Adder
2.053
238219AF1-167 C
Solar/Wind Harmer
1.404
20080926SITHE
50/50
0.751
203839AF1-321 GEN
Solar/Wind Harmer
4.155
20084626FORWARD
Solar/Wind Harmer
1.637
203857AF2-221 C
Solar/Wind Harmer
3.062
970123AG2-090 GEN
Solar/Wind Harmer
2.858
20088626ARWF_N39
Solar/Wind Harmer
3.564
20303426NA_O38_P22
Solar/Wind Harmer
2.886
20088926STNY CRK
Solar/Wind Harmer
2.291
971427AH1-205 GEN
Solar/Wind Harmer
2.767
203940AF1-140 C
Solar/Wind Harmer
0.921
20083426SW_E13_K22
Solar/Wind Harmer
0.546
971441AH1-212 GEN
Solar/Wind Harmer
3.496
972077AH1-588 GEN
Solar/Wind Harmer
39.042
972079AH1-589 GEN
Solar/Wind Harmer
32.156
970715AG2-457 GEN
Solar/Wind Harmer
13.014
944781AF1-143 GEN
Solar/Wind Harmer
4.635
972075AH1-587 GEN
Solar/Wind Harmer
30.314
20398826ARMNA MT
Solar/Wind Harmer
3.223
203952AE2-129 C
Solar/Wind Harmer
0.774
203946AE2-131 C
Solar/Wind Harmer
0.772
962411AG1-090 GEN
Solar/Wind Harmer
12.137
203859AF2-294 C
Solar/Wind Harmer
2.139
970313AG2-206 GEN
Solar/Wind Harmer
5.937
946381AF1-302 GEN
Solar/Wind Harmer
2.543
970305AG2-200 GEN
Solar/Wind Harmer
2.411
203955AF1-039 C O1
Solar/Wind Harmer
0.528
238217AF1-153 C O1
Solar/Wind Harmer
0.686
203848AF2-166 C
Solar/Wind Harmer
2.102
203980AG1-197 GEN
Solar/Wind Harmer
0.462
203853AF1-134 C O1
Solar/Wind Harmer
0.609
203963AG1-253 GEN
Solar/Wind Harmer
0.397
203979AG1-198 GEN
Solar/Wind Harmer
0.355
971933AH1-491 GEN
Solar/Wind Harmer
1.956
971931AH1-490 GEN
Solar/Wind Harmer
1.924
216419AE2-001 C
Solar/Wind Harmer
1.892
203947AF1-006 C
Solar/Wind Harmer
0.509
946071AF1-272 GEN
Solar/Wind Helper
1.512
971423AH1-203 GEN
Solar/Wind Harmer
13.025
964201AG1-281 GEN
Solar/Wind Harmer
1.074
970713AG2-456 GEN
Solar/Wind Harmer
13.014
971705AH1-358 GEN
Solar/Wind Harmer
3.783
971709AH1-360 GEN
Solar/Wind Harmer
3.783
20089226LOOKOUT
Solar/Wind Harmer
1.317
203987AE2-118 C
Solar/Wind Harmer
2.867
20082826HNSMLK 1
Adder
8.333
20083026HNSMLK 3
Adder
8.333
20335026MILZ1-092
Adder
3.092
944411AF1-106 GEN
Solar/Wind Harmer
2.848
20326126BLOSSBCT
Adder
3.104
971279AH1-102 GEN
Solar/Wind Harmer
10.813
964391AG1-301 GEN
Solar/Wind Harmer
0.8
20094526CT_V3-030
Solar/Wind Harmer
0.935
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.564
970511AG2-327 GEN
Solar/Wind Harmer
1.237
238183AE2-316 GEN
Solar/Wind Harmer
5.082
203954AE2-126 C
Solar/Wind Harmer
0.715
203860AG1-193 C
Solar/Wind Harmer
0.339
972169AH1-667 GEN
Solar/Wind Harmer
2.004
20091326SHAW-D
Adder
0.732
970647AG2-420 GEN
Solar/Wind Harmer
0.252
971183AH1-050 GEN
Solar/Wind Harmer
4.362
970267AG2-176 GEN
Solar/Wind Harmer
16.135
20072226SHAWVL 2
Adder
14.679
238206AE2-263_GEN
Solar/Wind Harmer
2.406
961971AG1-040 GEN
Solar/Wind Harmer
0.609
203835AF1-098 GEN
Solar/Wind Harmer
2.424
203813AE2-344_GEN
Solar/Wind Harmer
11.182
20084926LAKVU GN
Adder
0.164
238215AE2-248 C
Solar/Wind Harmer
1.496
970643AG2-418 GEN
Solar/Wind Harmer
0.522
20083726HOMER C1
50/50
233.467
20083926HOMER C3
50/50
191.631
20083826HOMER C2
50/50
181.017
20050326C.SLOPE
50/50
0.594
203961AE2-224 GEN
Solar/Wind Harmer
6.08
20092526R32
Solar/Wind Harmer
3.419
203844AF2-092 C
Solar/Wind Harmer
2.294
203850AG1-041 C
Solar/Wind Harmer
2.283
20091526CHSTN_FL
Solar/Wind Harmer
1.482
940863AE2-074 GEN
Solar/Wind Harmer
2.816
203804AE2-113_GEN
Solar/Wind Harmer
7.027
20083226HNSMLK 5
Adder
8.333
20090526Q36
Solar/Wind Harmer
2.198
203993AD2-133_GEN1
Solar/Wind Harmer
2.198
941231AE2-117 GEN
Solar/Wind Harmer
0.808
970555AG2-356 GEN
Solar/Wind Harmer
2.564
965121AG1-377 GEN
Solar/Wind Harmer
2.555
970663AG2-429 GEN
Solar/Wind Harmer
7.896
970663AG2-429 GEN
Solar/Wind Harmer
1.285
203855AF2-088 C
Solar/Wind Harmer
0.219
203846AF2-130 C
Solar/Wind Harmer
0.601
970677AG2-438 GEN
Solar/Wind Harmer
0.978
966771AG1-548 GEN
Solar/Wind Harmer
14.232
966771AG1-548 GEN
Solar/Wind Harmer
2.758
20084926LAKVU GN
Adder
0.185
203926AA2-133 GEN
Adder
2.133
20334726NME_Y1-047
Adder
1.933
20390726Y2-042
Adder
1.579
959441AF2-235 GEN
Solar/Wind Harmer
0.313
238202AE2-262_GEN
Solar/Wind Harmer
2.582
971627AH1-313 GEN
Solar/Wind Harmer
10.123
960051AF2-296 GEN
Solar/Wind Harmer
2.013
20328326MANOR_T86
Adder
0.142
203948AG1-140 C
Solar/Wind Harmer
0.26
957161AF2-010 GEN
Solar/Wind Harmer
7.551
203830AF1-094 GEN
Solar/Wind Harmer
0.592
203962AF1-287 GEN
Solar/Wind Harmer
1.928
962511AG1-100 GEN
Solar/Wind Harmer
0.582
20084926LAKVU GN
Adder
0.164
941421AE2-139 GEN
Solar/Wind Harmer
2.84
945751AF1-240 GEN
Solar/Wind Harmer
1.47
203818AF1-086 GEN
Solar/Wind Harmer
2.371
972271AH1-720 GEN
Adder
6.081
200917MEHOOPANY_G
Solar/Wind Harmer
2.877
970899AG2-561 GEN
Solar/Wind Harmer
1.592
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.122
961581Q1080_CY23
External Queue
23.09714698791504
G-007ALTFEXP_G-007A->PJM
CMTX
0.493
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.262
CBM NorthLTFEXP_CBM-N->PJM
CBM
29.912
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.687
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.154
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.176
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.548
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.792
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:809.0 MVA
Rating Type:A
MVA to Mitigate:811.02
MW Contribution:2.2
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.032
20079426CONEMAGH
50/50
2.219
203841AF2-001_GEN
Solar/Wind Harmer
2.872
971879AH1-460 GEN
Solar/Wind Harmer
9.383
970125AG2-091 GEN
Solar/Wind Harmer
0.846
971419AH1-201 GEN
Solar/Wind Harmer
5.18
971703AH1-357 GEN
Solar/Wind Harmer
2.198
971707AH1-359 GEN
Solar/Wind Harmer
2.198
20334926Z1-069 C
Solar/Wind Harmer
0.807
20089126CSLMN_L13
Solar/Wind Harmer
0.07
20089026BF_G21_K23
Solar/Wind Harmer
0.071
20082926HNSMLK 2
Adder
7.883
20083126HNSMLK 4
Adder
7.883
971541AH1-268 GEN
Solar/Wind Harmer
5.544
965131AG1-378 GEN
Solar/Wind Harmer
0.865
970335AG2-220 GEN
Solar/Wind Harmer
2.693
971127AH1-005 GEN
Solar/Wind Harmer
1.964
20120126WRREN CT
Adder
7.308
202652Y1-033 WT C
Solar/Wind Harmer
0.001
203854AF2-039 C
Solar/Wind Harmer
0.001
20335126GROZ1-110
Adder
2.469
20335226CANZ2-011
Adder
2.399
970647AG2-420 GEN
Solar/Wind Harmer
1.398
971185AH1-051 GEN
Solar/Wind Harmer
2.082
971355AH1-158 GEN
Solar/Wind Harmer
3.471
238202AE2-262_GEN
Solar/Wind Harmer
0.004
971627AH1-313 GEN
Solar/Wind Harmer
6.761
20328326MANOR_T86
Adder
0.138
960051AF2-296 GEN
Solar/Wind Harmer
1.349
203948AG1-140 C
Solar/Wind Harmer
0.187
203932AE1-123
Adder
1.861
957161AF2-010 GEN
Solar/Wind Harmer
4.943
238219AF1-167 C
Solar/Wind Harmer
0.869
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203962AF1-287 GEN
Solar/Wind Harmer
1.276
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
5.882
20084926LAKVU GN
Adder
0.157
203818AF1-086 GEN
Solar/Wind Harmer
0.535
972323AH1-746 GEN
Solar/Wind Harmer
2.072
945751AF1-240 GEN
Solar/Wind Harmer
1.105
200917MEHOOPANY_G
Solar/Wind Harmer
0.28
970899AG2-561 GEN
Solar/Wind Harmer
1.064
970679AG2-439 GEN
Solar/Wind Harmer
0.401
970643AG2-418 GEN
Solar/Wind Harmer
0.761
20080926SITHE
50/50
0.744
203839AF1-321 GEN
Solar/Wind Harmer
2.872
20084626FORWARD
Solar/Wind Harmer
0
203857AF2-221 C
Solar/Wind Harmer
1.481
970123AG2-090 GEN
Solar/Wind Harmer
1.975
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.25
971427AH1-205 GEN
Solar/Wind Harmer
3.453
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
2.409
203843AF2-002_GEN
Solar/Wind Harmer
1.436
970631AG2-411 GEN
Solar/Wind Harmer
9.712
957561AF2-050 GEN
Solar/Wind Harmer
6.927
20088826HIGHLAND
Solar/Wind Harmer
0.001
971423AH1-203 GEN
Solar/Wind Harmer
9.001
970713AG2-456 GEN
Solar/Wind Harmer
10.222
971705AH1-358 GEN
Solar/Wind Harmer
3.664
971709AH1-360 GEN
Solar/Wind Harmer
3.664
20089226LOOKOUT
Solar/Wind Harmer
0.201
203987AE2-118 C
Solar/Wind Harmer
1.969
20082826HNSMLK 1
Adder
7.883
20083026HNSMLK 3
Adder
7.883
20335026MILZ1-092
Adder
3.003
944411AF1-106 GEN
Solar/Wind Harmer
3.064
20326126BLOSSBCT
Adder
3.012
971279AH1-102 GEN
Solar/Wind Harmer
9.604
20094526CT_V3-030
Solar/Wind Harmer
0.152
970337AG2-221 GEN
Solar/Wind Harmer
1.909
970511AG2-327 GEN
Solar/Wind Harmer
0.837
203954AE2-126 C
Solar/Wind Harmer
0.001
238183AE2-316 GEN
Solar/Wind Harmer
0.004
972169AH1-667 GEN
Solar/Wind Harmer
1.342
20091326SHAW-D
Adder
0.702
203860AG1-193 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
14.036
970267AG2-176 GEN
Solar/Wind Harmer
10.629
970647AG2-420 GEN
Solar/Wind Harmer
0.233
971183AH1-050 GEN
Solar/Wind Harmer
3.471
238206AE2-263_GEN
Solar/Wind Harmer
0.004
203835AF1-098 GEN
Solar/Wind Harmer
0.004
203813AE2-344_GEN
Solar/Wind Harmer
7.402
238215AE2-248 C
Solar/Wind Harmer
1.003
20084926LAKVU GN
Adder
0.157
970643AG2-418 GEN
Solar/Wind Harmer
0.507
20083726HOMER C1
50/50
231.295
20083926HOMER C3
50/50
187.4
20083826HOMER C2
50/50
177.021
20050326C.SLOPE
50/50
0.588
203961AE2-224 GEN
Solar/Wind Harmer
0.011
20092526R32
Solar/Wind Harmer
0.408
203844AF2-092 C
Solar/Wind Harmer
1.584
203850AG1-041 C
Solar/Wind Harmer
1.576
20091526CHSTN_FL
Solar/Wind Harmer
0.208
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.485
203993AD2-133_GEN1
Solar/Wind Harmer
0.48
20083226HNSMLK 5
Adder
7.883
970555AG2-356 GEN
Solar/Wind Harmer
1.736
965121AG1-377 GEN
Solar/Wind Harmer
0.865
203855AF2-088 C
Solar/Wind Harmer
0
970663AG2-429 GEN
Solar/Wind Harmer
5.172
970663AG2-429 GEN
Solar/Wind Harmer
1.13
970677AG2-438 GEN
Solar/Wind Harmer
0.719
966771AG1-548 GEN
Solar/Wind Harmer
2.139
966771AG1-548 GEN
Solar/Wind Harmer
2.673
20084926LAKVU GN
Adder
0.176
203926AA2-133 GEN
Adder
2.065
20334726NME_Y1-047
Adder
1.87
20390726Y2-042
Adder
1.527
972077AH1-588 GEN
Solar/Wind Harmer
26.379
972079AH1-589 GEN
Solar/Wind Harmer
31.142
970715AG2-457 GEN
Solar/Wind Harmer
10.222
944781AF1-143 GEN
Solar/Wind Harmer
-0.001
972075AH1-587 GEN
Solar/Wind Harmer
20.422
20398826ARMNA MT
Solar/Wind Harmer
0.053
203952AE2-129 C
Solar/Wind Harmer
0.001
962411AG1-090 GEN
Solar/Wind Harmer
4.323
203859AF2-294 C
Solar/Wind Harmer
1.449
970313AG2-206 GEN
Solar/Wind Harmer
4.019
970305AG2-200 GEN
Solar/Wind Harmer
1.613
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203848AF2-166 C
Solar/Wind Harmer
1.342
203963AG1-253 GEN
Solar/Wind Harmer
0.297
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.287
971931AH1-490 GEN
Solar/Wind Harmer
1.273
216419AE2-001 C
Solar/Wind Harmer
1.268
203947AF1-006 C
Solar/Wind Harmer
0.041
946071AF1-272 GEN
Solar/Wind Helper
1.546
961581Q1080_CY23
External Queue
22.834562301635742
G-007ALTFEXP_G-007A->PJM
CMTX
0.401
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.959
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.427
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.162
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.145
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.88 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1107.15
MW Contribution:4.88
Bus #Bus NameTypeMW Contribution
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
19.506
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
4.586
959471AF2-238 GEN
Solar/Wind Harmer
1.217
970337AG2-221 GEN
Solar/Wind Harmer
4.026
970511AG2-327 GEN
Solar/Wind Harmer
1.95
203954AE2-126 C
Solar/Wind Harmer
0.535
203835AF1-098 GEN
Solar/Wind Harmer
2.074
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
2.617
203813AE2-344_GEN
Solar/Wind Harmer
7.125
238206AE2-263_GEN
Solar/Wind Harmer
1.438
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
1.018
961971AG1-040 GEN
Solar/Wind Harmer
0.341
970267AG2-176 GEN
Solar/Wind Harmer
7.665
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.713
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
940863AE2-074 GEN
Solar/Wind Harmer
4.363
970555AG2-356 GEN
Solar/Wind Harmer
4.026
972077AH1-588 GEN
Solar/Wind Harmer
58.517
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
19.506
20398826ARMNA MT
Solar/Wind Harmer
5.218
972075AH1-587 GEN
Solar/Wind Harmer
41.314
203859AF2-294 C
Solar/Wind Harmer
3.446
970313AG2-206 GEN
Solar/Wind Harmer
9.361
970305AG2-200 GEN
Solar/Wind Harmer
2.62
203963AG1-253 GEN
Solar/Wind Harmer
0.354
238217AF1-153 C O1
Solar/Wind Harmer
0.466
203947AF1-006 C
Solar/Wind Harmer
0.365
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.252
946381AF1-302 GEN
Solar/Wind Harmer
1.31
971931AH1-490 GEN
Solar/Wind Harmer
1.186
203980AG1-197 GEN
Solar/Wind Harmer
0.251
216419AE2-001 C
Solar/Wind Harmer
0.937
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
5.269
971703AH1-357 GEN
Solar/Wind Harmer
4.876
971707AH1-359 GEN
Solar/Wind Harmer
4.876
944411AF1-106 GEN
Solar/Wind Harmer
0.493
970335AG2-220 GEN
Solar/Wind Harmer
6.083
971127AH1-005 GEN
Solar/Wind Harmer
3.924
941421AE2-139 GEN
Solar/Wind Harmer
3.942
200917MEHOOPANY_G
Solar/Wind Harmer
4.284
970679AG2-439 GEN
Solar/Wind Harmer
0.971
203948AG1-140 C
Solar/Wind Harmer
0.232
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.379
957161AF2-010 GEN
Solar/Wind Harmer
4.762
203962AF1-287 GEN
Solar/Wind Harmer
1.232
238202AE2-262_GEN
Solar/Wind Harmer
1.543
971627AH1-313 GEN
Solar/Wind Harmer
6.05
962511AG1-100 GEN
Solar/Wind Harmer
0.359
203854AF2-039 C
Solar/Wind Harmer
0.231
959441AF2-235 GEN
Solar/Wind Harmer
0.14
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
203804AE2-113_GEN
Solar/Wind Harmer
9.082
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
9.309
966771AG1-548 GEN
Solar/Wind Harmer
1.804
970677AG2-438 GEN
Solar/Wind Harmer
0.626
203855AF2-088 C
Solar/Wind Harmer
0.111
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.88 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1107.15
MW Contribution:4.88
Bus #Bus NameTypeMW Contribution
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
5.269
971703AH1-357 GEN
Solar/Wind Harmer
4.876
971707AH1-359 GEN
Solar/Wind Harmer
4.876
944411AF1-106 GEN
Solar/Wind Harmer
0.493
970335AG2-220 GEN
Solar/Wind Harmer
6.083
971127AH1-005 GEN
Solar/Wind Harmer
3.924
941421AE2-139 GEN
Solar/Wind Harmer
3.942
200917MEHOOPANY_G
Solar/Wind Harmer
4.284
970679AG2-439 GEN
Solar/Wind Harmer
0.971
203948AG1-140 C
Solar/Wind Harmer
0.232
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.379
957161AF2-010 GEN
Solar/Wind Harmer
4.762
203962AF1-287 GEN
Solar/Wind Harmer
1.232
238202AE2-262_GEN
Solar/Wind Harmer
1.543
971627AH1-313 GEN
Solar/Wind Harmer
6.05
962511AG1-100 GEN
Solar/Wind Harmer
0.359
203854AF2-039 C
Solar/Wind Harmer
0.231
959441AF2-235 GEN
Solar/Wind Harmer
0.14
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
19.506
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
4.586
959471AF2-238 GEN
Solar/Wind Harmer
1.217
970337AG2-221 GEN
Solar/Wind Harmer
4.026
970511AG2-327 GEN
Solar/Wind Harmer
1.95
203954AE2-126 C
Solar/Wind Harmer
0.535
203835AF1-098 GEN
Solar/Wind Harmer
2.074
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
2.617
203813AE2-344_GEN
Solar/Wind Harmer
7.125
238206AE2-263_GEN
Solar/Wind Harmer
1.438
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
1.018
961971AG1-040 GEN
Solar/Wind Harmer
0.341
970267AG2-176 GEN
Solar/Wind Harmer
7.665
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.713
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
940863AE2-074 GEN
Solar/Wind Harmer
4.363
970555AG2-356 GEN
Solar/Wind Harmer
4.026
203804AE2-113_GEN
Solar/Wind Harmer
9.082
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
9.309
966771AG1-548 GEN
Solar/Wind Harmer
1.804
970677AG2-438 GEN
Solar/Wind Harmer
0.626
203855AF2-088 C
Solar/Wind Harmer
0.111
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
972077AH1-588 GEN
Solar/Wind Harmer
58.517
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
19.506
20398826ARMNA MT
Solar/Wind Harmer
5.218
972075AH1-587 GEN
Solar/Wind Harmer
41.314
203859AF2-294 C
Solar/Wind Harmer
3.446
970313AG2-206 GEN
Solar/Wind Harmer
9.361
970305AG2-200 GEN
Solar/Wind Harmer
2.62
203963AG1-253 GEN
Solar/Wind Harmer
0.354
238217AF1-153 C O1
Solar/Wind Harmer
0.466
203947AF1-006 C
Solar/Wind Harmer
0.365
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.252
946381AF1-302 GEN
Solar/Wind Harmer
1.31
971931AH1-490 GEN
Solar/Wind Harmer
1.186
203980AG1-197 GEN
Solar/Wind Harmer
0.251
216419AE2-001 C
Solar/Wind Harmer
0.937
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.97 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1099.7
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.97 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1099.66
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-345-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-345-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.9 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1090.83
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-345-001T-DRT-001_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-345-001T-DRT-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.9 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1090.83
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-230-0183-207_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-230-0183-207_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.01 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1066.94
MW Contribution:5.12
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
14.737
20083026HNSMLK 3
50/50
14.737
20335026MILZ1-092
50/50
5.207
20326126BLOSSBCT
50/50
5.086
970713AG2-456 GEN
Solar/Wind Harmer
20.498
971705AH1-358 GEN
Solar/Wind Harmer
5.959
971709AH1-360 GEN
Solar/Wind Harmer
5.959
944411AF1-106 GEN
Solar/Wind Harmer
4.52
959471AF2-238 GEN
Solar/Wind Harmer
1.194
970337AG2-221 GEN
Solar/Wind Harmer
3.948
970511AG2-327 GEN
Solar/Wind Harmer
1.908
970267AG2-176 GEN
Solar/Wind Harmer
25.838
203860AG1-193 C
Solar/Wind Harmer
0.515
961971AG1-040 GEN
Solar/Wind Harmer
0.978
203835AF1-098 GEN
Solar/Wind Harmer
3.788
203813AE2-344_GEN
Solar/Wind Harmer
17.961
970647AG2-420 GEN
Solar/Wind Harmer
0.355
20084926LAKVU GN
Adder
0.263
971183AH1-050 GEN
Solar/Wind Harmer
6.014
238183AE2-316 GEN
Solar/Wind Harmer
6.239
203954AE2-126 C
Solar/Wind Harmer
0.637
20072226SHAWVL 2
Adder
10.919
24035802GEN-Y1-012
Adder
0.325
238206AE2-263_GEN
Solar/Wind Harmer
1.703
20091326SHAW-D
Adder
0.431
972169AH1-667 GEN
Solar/Wind Harmer
1.178
971865AH1-452 GEN
Solar/Wind Harmer
1.096
238215AE2-248 C
Solar/Wind Harmer
0.763
20088826HIGHLAND
Solar/Wind Helper
1.026
964201AG1-281 GEN
Solar/Wind Helper
0.467
20089226LOOKOUT
Solar/Wind Helper
0.476
20094526CT_V3-030
Solar/Wind Helper
0.295
964391AG1-301 GEN
Solar/Wind Helper
0.262
972077AH1-588 GEN
Solar/Wind Harmer
61.494
972079AH1-589 GEN
Solar/Wind Harmer
50.65
970715AG2-457 GEN
Solar/Wind Harmer
20.498
972075AH1-587 GEN
Solar/Wind Harmer
44.13
20398826ARMNA MT
Solar/Wind Harmer
5.104
203859AF2-294 C
Solar/Wind Harmer
3.385
970313AG2-206 GEN
Solar/Wind Harmer
9.157
970305AG2-200 GEN
Solar/Wind Harmer
3.532
203980AG1-197 GEN
Solar/Wind Harmer
0.742
203963AG1-253 GEN
Solar/Wind Harmer
0.636
971931AH1-490 GEN
Solar/Wind Harmer
3.095
203979AG1-198 GEN
Solar/Wind Harmer
0.542
971933AH1-491 GEN
Solar/Wind Harmer
2.984
946381AF1-302 GEN
Solar/Wind Harmer
3.122
203947AF1-006 C
Solar/Wind Harmer
0.819
203848AF2-166 C
Solar/Wind Harmer
2.689
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.022
20088626ARWF_N39
Solar/Wind Helper
1.462
20303426NA_O38_P22
Solar/Wind Helper
1.199
20084626FORWARD
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.407
20088926STNY CRK
Solar/Wind Helper
0.814
20083426SW_E13_K22
Solar/Wind Helper
0.054
944781AF1-143 GEN
Solar/Wind Helper
2.029
946071AF1-272 GEN
Solar/Wind Helper
2.016
203955AF1-039 C O1
Solar/Wind Helper
0.239
20082926HNSMLK 2
50/50
14.737
20083126HNSMLK 4
50/50
14.737
971703AH1-357 GEN
Solar/Wind Harmer
5.125
971707AH1-359 GEN
Solar/Wind Harmer
5.125
20334926Z1-069 C
Solar/Wind Harmer
5.297
944411AF1-106 GEN
Solar/Wind Harmer
0.486
970335AG2-220 GEN
Solar/Wind Harmer
5.951
971127AH1-005 GEN
Solar/Wind Harmer
3.839
20120126WRREN CT
Adder
11.166
203948AG1-140 C
Solar/Wind Harmer
0.417
962511AG1-100 GEN
Solar/Wind Harmer
0.936
203962AF1-287 GEN
Solar/Wind Harmer
3.094
970647AG2-420 GEN
Solar/Wind Harmer
3.055
20335126GROZ1-110
Adder
3.563
20335226CANZ2-011
Adder
3.463
20084926LAKVU GN
Adder
0.263
203830AF1-094 GEN
Solar/Wind Harmer
0.904
957161AF2-010 GEN
Solar/Wind Harmer
11.478
971185AH1-051 GEN
Solar/Wind Harmer
3.608
971355AH1-158 GEN
Solar/Wind Harmer
4.196
203856AF2-165 C
Solar/Wind Harmer
1.767
959441AF2-235 GEN
Solar/Wind Harmer
0.444
20328326MANOR_T86
Adder
0.207
238219AF1-167 C
Solar/Wind Harmer
1.891
972271AH1-720 GEN
Adder
8.501
941421AE2-139 GEN
Solar/Wind Harmer
3.883
203932AE1-123
Adder
2.444
200917MEHOOPANY_G
Solar/Wind Harmer
4.114
970679AG2-439 GEN
Solar/Wind Harmer
0.912
238202AE2-262_GEN
Solar/Wind Harmer
1.827
971627AH1-313 GEN
Solar/Wind Harmer
7.164
203854AF2-039 C
Solar/Wind Harmer
0.268
945751AF1-240 GEN
Solar/Wind Harmer
0.867
20089126CSLMN_L13
Solar/Wind Helper
0.489
20089026BF_G21_K23
Solar/Wind Helper
0.387
202652Y1-033 WT C
Solar/Wind Helper
0.363
20083926HOMER C3
50/50
340.465
20083826HOMER C2
50/50
321.609
20083226HNSMLK 5
50/50
14.737
940863AE2-074 GEN
Solar/Wind Harmer
4.454
20083726HOMER C1
Adder
-144.162
203804AE2-113_GEN
Solar/Wind Harmer
9.857
970555AG2-356 GEN
Solar/Wind Harmer
3.948
970663AG2-429 GEN
Solar/Wind Harmer
10.921
970663AG2-429 GEN
Solar/Wind Harmer
1.778
20084926LAKVU GN
Adder
0.296
966771AG1-548 GEN
Solar/Wind Harmer
21.818
966771AG1-548 GEN
Solar/Wind Harmer
4.228
970677AG2-438 GEN
Solar/Wind Harmer
1.492
203846AF2-130 C
Solar/Wind Harmer
0.768
203926AA2-133 GEN
Adder
3.075
20334726NME_Y1-047
Adder
2.764
20390726Y2-042
Adder
2.182
203855AF2-088 C
Solar/Wind Harmer
0.129
971055AG2-654 GEN
Solar/Wind Harmer
0.793
203961AE2-224 GEN
Solar/Wind Helper
3.145
20092526R32
Solar/Wind Helper
1.329
20091526CHSTN_FL
Solar/Wind Helper
0.439
941231AE2-117 GEN
Solar/Wind Helper
0.253
961581Q1080_CY23
External Queue
46.2189826965332
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.25
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.463
LAGNLTFEXP_LAGN->PJM
CLTF
0.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.137
TVALTFEXP_TVA->PJM
CLTF
0.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.535
MECLTFEXP_MEC->PJM
CLTF
0.999
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.09 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1059.31
MW Contribution:5.08
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
16.171
20083026HNSMLK 3
50/50
16.171
970713AG2-456 GEN
Solar/Wind Harmer
20.337
971705AH1-358 GEN
Solar/Wind Harmer
5.912
971709AH1-360 GEN
Solar/Wind Harmer
5.912
970267AG2-176 GEN
Solar/Wind Harmer
33.863
961971AG1-040 GEN
Solar/Wind Harmer
1.351
203813AE2-344_GEN
Solar/Wind Harmer
25.804
20084926LAKVU GN
Adder
0.386
203835AF1-098 GEN
Solar/Wind Harmer
5.278
203860AG1-193 C
Solar/Wind Harmer
0.636
20335026MILZ1-092
Adder
4.716
944411AF1-106 GEN
Solar/Wind Harmer
4.345
20326126BLOSSBCT
Adder
4.603
959471AF2-238 GEN
Solar/Wind Harmer
1.148
970337AG2-221 GEN
Solar/Wind Harmer
3.798
970647AG2-420 GEN
Solar/Wind Harmer
0.435
970511AG2-327 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
7.295
238183AE2-316 GEN
Solar/Wind Harmer
6.529
203954AE2-126 C
Solar/Wind Harmer
0.73
20072226SHAWVL 2
Adder
13.13
238206AE2-263_GEN
Solar/Wind Harmer
2.077
20091326SHAW-D
Adder
0.549
972169AH1-667 GEN
Solar/Wind Harmer
1.503
971865AH1-452 GEN
Solar/Wind Harmer
1.125
238215AE2-248 C
Solar/Wind Harmer
1.032
20088826HIGHLAND
Solar/Wind Helper
0.735
20089226LOOKOUT
Solar/Wind Helper
0.398
964201AG1-281 GEN
Solar/Wind Helper
0.309
20082926HNSMLK 2
50/50
16.171
20083126HNSMLK 4
50/50
16.171
971703AH1-357 GEN
Solar/Wind Harmer
5.084
971707AH1-359 GEN
Solar/Wind Harmer
5.084
20334926Z1-069 C
Solar/Wind Harmer
5.092
203948AG1-140 C
Solar/Wind Harmer
0.584
962511AG1-100 GEN
Solar/Wind Harmer
1.342
203962AF1-287 GEN
Solar/Wind Harmer
4.429
20084926LAKVU GN
Adder
0.386
20120126WRREN CT
Adder
13.354
203830AF1-094 GEN
Solar/Wind Harmer
1.259
944411AF1-106 GEN
Solar/Wind Harmer
0.467
957161AF2-010 GEN
Solar/Wind Harmer
15.93
959441AF2-235 GEN
Solar/Wind Harmer
0.57
970647AG2-420 GEN
Solar/Wind Harmer
3.743
970335AG2-220 GEN
Solar/Wind Harmer
5.73
971127AH1-005 GEN
Solar/Wind Harmer
3.697
203856AF2-165 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
4.377
971355AH1-158 GEN
Solar/Wind Harmer
5.09
20335126GROZ1-110
Adder
3.54
20335226CANZ2-011
Adder
3.441
238219AF1-167 C
Solar/Wind Harmer
1.987
20328326MANOR_T86
Adder
0.205
20083926HOMER C3
50/50
297.76
20083826HOMER C2
50/50
281.269
20083226HNSMLK 5
50/50
16.171
940863AE2-074 GEN
Solar/Wind Harmer
4.324
20084926LAKVU GN
Adder
0.434
966771AG1-548 GEN
Solar/Wind Harmer
30.55
966771AG1-548 GEN
Solar/Wind Harmer
5.921
203804AE2-113_GEN
Solar/Wind Harmer
10.01
970677AG2-438 GEN
Solar/Wind Harmer
2.078
970555AG2-356 GEN
Solar/Wind Harmer
3.798
970663AG2-429 GEN
Solar/Wind Harmer
11.217
970663AG2-429 GEN
Solar/Wind Harmer
1.826
203846AF2-130 C
Solar/Wind Harmer
0.916
20083726HOMER C1
Adder
-95.563
203926AA2-133 GEN
Adder
3.065
20334726NME_Y1-047
Adder
2.777
20390726Y2-042
Adder
2.24
203855AF2-088 C
Solar/Wind Harmer
0.164
971055AG2-654 GEN
Solar/Wind Harmer
0.819
965121AG1-377 GEN
Solar/Wind Harmer
0.901
203961AE2-224 GEN
Solar/Wind Helper
2.002
20092526R32
Solar/Wind Helper
0.952
203932AE1-123
Adder
2.816
972271AH1-720 GEN
Adder
8.529
941421AE2-139 GEN
Solar/Wind Harmer
3.915
200917MEHOOPANY_G
Solar/Wind Harmer
4.134
970679AG2-439 GEN
Solar/Wind Harmer
0.936
238202AE2-262_GEN
Solar/Wind Harmer
2.229
971627AH1-313 GEN
Solar/Wind Harmer
8.739
203854AF2-039 C
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.249
960051AF2-296 GEN
Solar/Wind Harmer
0.933
965131AG1-378 GEN
Solar/Wind Harmer
0.901
20089126CSLMN_L13
Solar/Wind Helper
0.408
20089026BF_G21_K23
Solar/Wind Helper
0.323
202652Y1-033 WT C
Solar/Wind Helper
0.302
972077AH1-588 GEN
Solar/Wind Harmer
61.011
972079AH1-589 GEN
Solar/Wind Harmer
50.252
970715AG2-457 GEN
Solar/Wind Harmer
20.337
203980AG1-197 GEN
Solar/Wind Harmer
1.017
203963AG1-253 GEN
Solar/Wind Harmer
0.892
971931AH1-490 GEN
Solar/Wind Harmer
4.439
972075AH1-587 GEN
Solar/Wind Harmer
44.277
203947AF1-006 C
Solar/Wind Harmer
1.229
970305AG2-200 GEN
Solar/Wind Harmer
4.224
20398826ARMNA MT
Solar/Wind Harmer
4.863
203979AG1-198 GEN
Solar/Wind Harmer
0.755
971933AH1-491 GEN
Solar/Wind Harmer
4.156
203859AF2-294 C
Solar/Wind Harmer
3.269
970313AG2-206 GEN
Solar/Wind Harmer
8.823
203848AF2-166 C
Solar/Wind Harmer
3.205
946381AF1-302 GEN
Solar/Wind Harmer
3.267
238217AF1-153 C O1
Solar/Wind Harmer
0.803
216419AE2-001 C
Solar/Wind Harmer
1.355
203853AF1-134 C O1
Solar/Wind Harmer
0.282
203952AE2-129 C
Solar/Wind Harmer
0.273
203946AE2-131 C
Solar/Wind Harmer
0.272
962411AG1-090 GEN
Solar/Wind Harmer
4.281
20084626FORWARD
Solar/Wind Helper
0.323
20083426SW_E13_K22
Solar/Wind Helper
0.045
20088926STNY CRK
Solar/Wind Helper
0.657
20088626ARWF_N39
Solar/Wind Helper
0.915
20303426NA_O38_P22
Solar/Wind Helper
0.75
203940AF1-140 C
Solar/Wind Helper
0.284
944781AF1-143 GEN
Solar/Wind Helper
1.695
203955AF1-039 C O1
Solar/Wind Helper
0.199
961581Q1080_CY23
External Queue
34.45887756347656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.127
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.016

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.08 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1001.36
MW Contribution:4.54
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
54.501
972079AH1-589 GEN
Solar/Wind Harmer
44.89
970715AG2-457 GEN
Solar/Wind Harmer
18.167
20398826ARMNA MT
Solar/Wind Harmer
4.57
972075AH1-587 GEN
Solar/Wind Harmer
38.382
203859AF2-294 C
Solar/Wind Harmer
3.039
970313AG2-206 GEN
Solar/Wind Harmer
8.187
970305AG2-200 GEN
Solar/Wind Harmer
3.117
203980AG1-197 GEN
Solar/Wind Harmer
0.702
203963AG1-253 GEN
Solar/Wind Harmer
0.589
971931AH1-490 GEN
Solar/Wind Harmer
2.914
203947AF1-006 C
Solar/Wind Harmer
0.765
203979AG1-198 GEN
Solar/Wind Harmer
0.467
971933AH1-491 GEN
Solar/Wind Harmer
2.572
946381AF1-302 GEN
Solar/Wind Harmer
1.69
238217AF1-153 C O1
Solar/Wind Harmer
0.481
203848AF2-166 C
Solar/Wind Harmer
1.524
20084626FORWARD
Solar/Wind Helper
0.342
20083426SW_E13_K22
Solar/Wind Helper
0.048
20088926STNY CRK
Solar/Wind Helper
0.705
20088626ARWF_N39
Solar/Wind Helper
0.995
20303426NA_O38_P22
Solar/Wind Helper
0.816
203940AF1-140 C
Solar/Wind Helper
0.318
944781AF1-143 GEN
Solar/Wind Helper
1.809
203955AF1-039 C O1
Solar/Wind Helper
0.214
946071AF1-272 GEN
Solar/Wind Helper
1.561
20083926HOMER C3
50/50
307.624
20083826HOMER C2
50/50
290.586
20083226HNSMLK 5
50/50
15.38
940863AE2-074 GEN
Solar/Wind Harmer
3.956
203804AE2-113_GEN
Solar/Wind Harmer
8.493
970555AG2-356 GEN
Solar/Wind Harmer
3.525
20084926LAKVU GN
Adder
0.275
20083726HOMER C1
Adder
-94.167
966771AG1-548 GEN
Solar/Wind Harmer
18.967
966771AG1-548 GEN
Solar/Wind Harmer
3.676
970677AG2-438 GEN
Solar/Wind Harmer
1.286
203926AA2-133 GEN
Adder
2.747
20334726NME_Y1-047
Adder
2.477
20390726Y2-042
Adder
1.965
203846AF2-130 C
Solar/Wind Harmer
0.435
203855AF2-088 C
Solar/Wind Harmer
0.098
20092526R32
Solar/Wind Helper
1.034
203961AE2-224 GEN
Solar/Wind Helper
2.14
20091526CHSTN_FL
Solar/Wind Helper
0.327
20082926HNSMLK 2
50/50
15.38
20083126HNSMLK 4
50/50
15.38
971703AH1-357 GEN
Solar/Wind Harmer
4.542
971707AH1-359 GEN
Solar/Wind Harmer
4.542
20334926Z1-069 C
Solar/Wind Harmer
4.72
944411AF1-106 GEN
Solar/Wind Harmer
0.436
970335AG2-220 GEN
Solar/Wind Harmer
5.32
971127AH1-005 GEN
Solar/Wind Harmer
3.432
20120126WRREN CT
Adder
9.854
203948AG1-140 C
Solar/Wind Harmer
0.385
962511AG1-100 GEN
Solar/Wind Harmer
0.881
203962AF1-287 GEN
Solar/Wind Harmer
2.903
20084926LAKVU GN
Adder
0.245
20335126GROZ1-110
Adder
3.141
20335226CANZ2-011
Adder
3.053
20328326MANOR_T86
Adder
0.184
203830AF1-094 GEN
Solar/Wind Harmer
0.779
957161AF2-010 GEN
Solar/Wind Harmer
9.836
972271AH1-720 GEN
Adder
7.549
970647AG2-420 GEN
Solar/Wind Harmer
2.29
941421AE2-139 GEN
Solar/Wind Harmer
3.432
959441AF2-235 GEN
Solar/Wind Harmer
0.334
203856AF2-165 C
Solar/Wind Harmer
1.263
200917MEHOOPANY_G
Solar/Wind Harmer
3.687
971185AH1-051 GEN
Solar/Wind Harmer
2.552
971355AH1-158 GEN
Solar/Wind Harmer
2.967
970679AG2-439 GEN
Solar/Wind Harmer
0.821
238202AE2-262_GEN
Solar/Wind Harmer
1.405
971627AH1-313 GEN
Solar/Wind Harmer
5.509
203932AE1-123
Adder
1.034
203854AF2-039 C
Solar/Wind Harmer
0.204
20089126CSLMN_L13
Solar/Wind Helper
0.436
20089026BF_G21_K23
Solar/Wind Helper
0.345
202652Y1-033 WT C
Solar/Wind Helper
0.325
20082826HNSMLK 1
50/50
15.38
20083026HNSMLK 3
50/50
15.38
20335026MILZ1-092
50/50
4.667
20326126BLOSSBCT
50/50
4.534
970713AG2-456 GEN
Solar/Wind Harmer
18.167
971705AH1-358 GEN
Solar/Wind Harmer
5.281
971709AH1-360 GEN
Solar/Wind Harmer
5.281
944411AF1-106 GEN
Solar/Wind Harmer
4.052
959471AF2-238 GEN
Solar/Wind Harmer
1.066
970337AG2-221 GEN
Solar/Wind Harmer
3.525
970511AG2-327 GEN
Solar/Wind Harmer
1.706
970267AG2-176 GEN
Solar/Wind Harmer
24.571
961971AG1-040 GEN
Solar/Wind Harmer
0.924
203860AG1-193 C
Solar/Wind Harmer
0.449
203813AE2-344_GEN
Solar/Wind Harmer
16.864
203835AF1-098 GEN
Solar/Wind Harmer
3.467
20084926LAKVU GN
Adder
0.245
970647AG2-420 GEN
Solar/Wind Harmer
0.266
971183AH1-050 GEN
Solar/Wind Harmer
4.253
203954AE2-126 C
Solar/Wind Harmer
0.507
238183AE2-316 GEN
Solar/Wind Harmer
3.378
24035802GEN-Y1-012
Adder
0.304
20072226SHAWVL 2
Adder
8.297
238206AE2-263_GEN
Solar/Wind Harmer
1.31
20091326SHAW-D
Adder
0.329
972169AH1-667 GEN
Solar/Wind Harmer
0.9
20088826HIGHLAND
Solar/Wind Helper
0.798
20089226LOOKOUT
Solar/Wind Helper
0.424
964201AG1-281 GEN
Solar/Wind Helper
0.354
20094526CT_V3-030
Solar/Wind Helper
0.236
961581Q1080_CY23
External Queue
42.076351165771484
LGEELTFEXP_LGEE->PJM
CLTF
0.243
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CBM NorthLTFEXP_CBM-N->PJM
CBM
40.823
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
0.472
TVALTFEXP_TVA->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.21
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.908
MECLTFEXP_MEC->PJM
CLTF
0.662
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P1-2_WP-345-311T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P1-2_WP-345-311T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.28 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:994.75
MW Contribution:3.4
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
40.826
972079AH1-589 GEN
Solar/Wind Harmer
48.197
970715AG2-457 GEN
Solar/Wind Harmer
15.82
20398826ARMNA MT
Solar/Wind Harmer
0.088
972075AH1-587 GEN
Solar/Wind Harmer
28.824
203859AF2-294 C
Solar/Wind Harmer
2.404
970313AG2-206 GEN
Solar/Wind Harmer
6.531
970305AG2-200 GEN
Solar/Wind Harmer
1.828
203963AG1-253 GEN
Solar/Wind Harmer
0.278
203947AF1-006 C
Solar/Wind Harmer
0.031
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.874
971931AH1-490 GEN
Solar/Wind Harmer
0.828
203980AG1-197 GEN
Solar/Wind Harmer
0
216419AE2-001 C
Solar/Wind Harmer
0.653
20084626FORWARD
Solar/Wind Helper
0.221
20083426SW_E13_K22
Solar/Wind Helper
0.031
20088926STNY CRK
Solar/Wind Helper
0.451
20088626ARWF_N39
Solar/Wind Helper
0.611
20303426NA_O38_P22
Solar/Wind Helper
0.501
203940AF1-140 C
Solar/Wind Helper
0.196
944781AF1-143 GEN
Solar/Wind Helper
1.173
20083926HOMER C3
50/50
365.385
20083826HOMER C2
50/50
345.149
200642SENECA#1
50/50
2.28
203926AA2-133 GEN
50/50
3.366
203922AA1-082 G1
50/50
3.223
203923AA1-082 G2
50/50
3.223
970555AG2-356 GEN
Solar/Wind Harmer
2.809
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20334726NME_Y1-047
Adder
2.878
20390726Y2-042
Adder
2.323
20083726HOMER C1
Adder
-62.328
20084926LAKVU GN
Adder
0.146
966771AG1-548 GEN
Solar/Wind Harmer
1.482
966771AG1-548 GEN
Solar/Wind Harmer
1.852
970677AG2-438 GEN
Solar/Wind Harmer
0.488
203855AF2-088 C
Solar/Wind Harmer
0
20083226HNSMLK 5
Adder
2.659
20092526R32
Solar/Wind Helper
0.654
203961AE2-224 GEN
Solar/Wind Helper
1.337
20335126GROZ1-110
50/50
3.801
20335226CANZ2-011
50/50
3.695
200644SENECA#3
50/50
0.293
20328326MANOR_T86
50/50
0.225
972271AH1-720 GEN
50/50
9.221
20120126WRREN CT
50/50
8.789
20334926Z1-069 C
Solar/Wind Harmer
1.319
971703AH1-357 GEN
Solar/Wind Harmer
3.402
971707AH1-359 GEN
Solar/Wind Harmer
3.402
970335AG2-220 GEN
Solar/Wind Harmer
4.381
971127AH1-005 GEN
Solar/Wind Harmer
3.194
941421AE2-139 GEN
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.431
970679AG2-439 GEN
Solar/Wind Harmer
0.611
203948AG1-140 C
Solar/Wind Harmer
0.175
20084926LAKVU GN
Adder
0.13
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
3.308
203962AF1-287 GEN
Solar/Wind Harmer
0.86
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.221
203854AF2-039 C
Solar/Wind Harmer
0
20082926HNSMLK 2
Adder
2.659
20083126HNSMLK 4
Adder
2.659
20089126CSLMN_L13
Solar/Wind Helper
0.283
20089026BF_G21_K23
Solar/Wind Helper
0.224
20335026MILZ1-092
50/50
5.283
20326126BLOSSBCT
50/50
5.16
200643SENECA#2
50/50
2.127
970713AG2-456 GEN
Solar/Wind Harmer
15.82
971705AH1-358 GEN
Solar/Wind Harmer
5.67
971709AH1-360 GEN
Solar/Wind Harmer
5.67
944411AF1-106 GEN
Solar/Wind Harmer
5.079
970337AG2-221 GEN
Solar/Wind Harmer
3.09
970511AG2-327 GEN
Solar/Wind Harmer
1.361
203954AE2-126 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.004
20084926LAKVU GN
Adder
0.13
20072226SHAWVL 2
Adder
8.919
238183AE2-316 GEN
Solar/Wind Harmer
0.002
203813AE2-344_GEN
Solar/Wind Harmer
4.971
238206AE2-263_GEN
Solar/Wind Harmer
0.003
20091326SHAW-D
Adder
0.372
972169AH1-667 GEN
Solar/Wind Harmer
0.71
970267AG2-176 GEN
Solar/Wind Harmer
5.348
20082826HNSMLK 1
Adder
2.659
20083026HNSMLK 3
Adder
2.659
238215AE2-248 C
Solar/Wind Harmer
0.497
20088826HIGHLAND
Solar/Wind Helper
0.505
20089226LOOKOUT
Solar/Wind Helper
0.275
961581Q1080_CY23
External Queue
54.8271484375
G-007ALTFEXP_G-007A->PJM
CMTX
0.611
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.789
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.355
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.44 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:954.65
MW Contribution:4.35
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
275.49
20082826HNSMLK 1
50/50
12.11
20083026HNSMLK 3
50/50
12.11
20335026MILZ1-092
50/50
4.385
20326126BLOSSBCT
50/50
4.34
970713AG2-456 GEN
Solar/Wind Harmer
17.393
971705AH1-358 GEN
Solar/Wind Harmer
5.056
971709AH1-360 GEN
Solar/Wind Harmer
5.056
944411AF1-106 GEN
Solar/Wind Harmer
3.807
959471AF2-238 GEN
Solar/Wind Harmer
1.018
970337AG2-221 GEN
Solar/Wind Harmer
3.367
970511AG2-327 GEN
Solar/Wind Harmer
1.623
970267AG2-176 GEN
Solar/Wind Harmer
21.537
203860AG1-193 C
Solar/Wind Harmer
0.429
238183AE2-316 GEN
Solar/Wind Harmer
5.79
961971AG1-040 GEN
Solar/Wind Harmer
0.819
203835AF1-098 GEN
Solar/Wind Harmer
3.232
203813AE2-344_GEN
Solar/Wind Harmer
15.097
970647AG2-420 GEN
Solar/Wind Harmer
0.299
20084926LAKVU GN
Adder
0.223
971183AH1-050 GEN
Solar/Wind Harmer
5.068
203954AE2-126 C
Solar/Wind Harmer
0.674
238206AE2-263_GEN
Solar/Wind Harmer
2.45
20072226SHAWVL 2
Adder
13.73
238215AE2-248 C
Solar/Wind Harmer
1.548
20091326SHAW-D
Adder
0.542
972169AH1-667 GEN
Solar/Wind Harmer
1.484
24035802GEN-Y1-012
Adder
0.274
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20088826HIGHLAND
Solar/Wind Helper
0.91
964201AG1-281 GEN
Solar/Wind Helper
0.414
20089226LOOKOUT
Solar/Wind Helper
0.481
964391AG1-301 GEN
Solar/Wind Helper
0.26
20094526CT_V3-030
Solar/Wind Helper
0.226
972077AH1-588 GEN
Solar/Wind Harmer
52.179
972079AH1-589 GEN
Solar/Wind Harmer
42.977
970715AG2-457 GEN
Solar/Wind Harmer
17.393
972075AH1-587 GEN
Solar/Wind Harmer
38.609
20398826ARMNA MT
Solar/Wind Harmer
4.304
203859AF2-294 C
Solar/Wind Harmer
2.847
970313AG2-206 GEN
Solar/Wind Harmer
7.793
970305AG2-200 GEN
Solar/Wind Harmer
3.096
946381AF1-302 GEN
Solar/Wind Harmer
2.897
203980AG1-197 GEN
Solar/Wind Harmer
0.621
203963AG1-253 GEN
Solar/Wind Harmer
0.538
971931AH1-490 GEN
Solar/Wind Harmer
2.598
203979AG1-198 GEN
Solar/Wind Harmer
0.459
971933AH1-491 GEN
Solar/Wind Harmer
2.523
203947AF1-006 C
Solar/Wind Harmer
0.691
238217AF1-153 C O1
Solar/Wind Harmer
0.737
203848AF2-166 C
Solar/Wind Harmer
2.285
216419AE2-001 C
Solar/Wind Harmer
1.962
20084626FORWARD
Solar/Wind Helper
0.391
20088626ARWF_N39
Solar/Wind Helper
1.229
20303426NA_O38_P22
Solar/Wind Helper
1.008
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.051
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.501
20083826HOMER C2
50/50
260.232
20083226HNSMLK 5
50/50
12.11
940863AE2-074 GEN
Solar/Wind Harmer
3.768
203804AE2-113_GEN
Solar/Wind Harmer
8.756
970555AG2-356 GEN
Solar/Wind Harmer
3.367
20083726HOMER C1
Adder
-110.032
970663AG2-429 GEN
Solar/Wind Harmer
9.226
970663AG2-429 GEN
Solar/Wind Harmer
1.502
20084926LAKVU GN
Adder
0.25
966771AG1-548 GEN
Solar/Wind Harmer
18.453
966771AG1-548 GEN
Solar/Wind Harmer
3.576
970677AG2-438 GEN
Solar/Wind Harmer
1.262
203846AF2-130 C
Solar/Wind Harmer
0.653
203926AA2-133 GEN
Adder
2.669
20334726NME_Y1-047
Adder
2.394
203855AF2-088 C
Solar/Wind Harmer
0.162
20390726Y2-042
Adder
1.895
971055AG2-654 GEN
Solar/Wind Harmer
0.672
203961AE2-224 GEN
Solar/Wind Helper
2.595
20092526R32
Solar/Wind Helper
1.18
20091526CHSTN_FL
Solar/Wind Helper
0.359
941231AE2-117 GEN
Solar/Wind Helper
0.246
20082926HNSMLK 2
50/50
12.11
20083126HNSMLK 4
50/50
12.11
971703AH1-357 GEN
Solar/Wind Harmer
4.348
971707AH1-359 GEN
Solar/Wind Harmer
4.348
20334926Z1-069 C
Solar/Wind Harmer
4.463
944411AF1-106 GEN
Solar/Wind Harmer
0.409
970335AG2-220 GEN
Solar/Wind Harmer
5.061
971127AH1-005 GEN
Solar/Wind Harmer
3.265
20120126WRREN CT
Adder
9.788
20335126GROZ1-110
Adder
3.176
20335226CANZ2-011
Adder
3.087
203948AG1-140 C
Solar/Wind Harmer
0.352
203962AF1-287 GEN
Solar/Wind Harmer
2.601
962511AG1-100 GEN
Solar/Wind Harmer
0.786
970647AG2-420 GEN
Solar/Wind Harmer
2.57
20084926LAKVU GN
Adder
0.223
203830AF1-094 GEN
Solar/Wind Harmer
0.764
20328326MANOR_T86
Adder
0.18
957161AF2-010 GEN
Solar/Wind Harmer
9.707
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.49
959441AF2-235 GEN
Solar/Wind Harmer
0.375
238219AF1-167 C
Solar/Wind Harmer
1.615
941421AE2-139 GEN
Solar/Wind Harmer
3.471
972271AH1-720 GEN
Adder
7.506
203932AE1-123
Adder
2.09
238202AE2-262_GEN
Solar/Wind Harmer
2.629
971627AH1-313 GEN
Solar/Wind Harmer
10.307
200917MEHOOPANY_G
Solar/Wind Harmer
3.564
203854AF2-039 C
Solar/Wind Harmer
0.337
970679AG2-439 GEN
Solar/Wind Harmer
0.792
945751AF1-240 GEN
Solar/Wind Harmer
0.788
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.365
961581Q1080_CY23
External Queue
35.905757904052734
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.22
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.687
LAGNLTFEXP_LAGN->PJM
CLTF
0.702
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.117
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.063
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.353
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.82 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:736.42
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
11.769
20083126HNSMLK 4
50/50
11.769
971703AH1-357 GEN
Solar/Wind Harmer
2.853
971707AH1-359 GEN
Solar/Wind Harmer
2.853
20334926Z1-069 C
Solar/Wind Harmer
1.059
970335AG2-220 GEN
Solar/Wind Harmer
3.421
971127AH1-005 GEN
Solar/Wind Harmer
2.494
20120126WRREN CT
Adder
8.901
203948AG1-140 C
Solar/Wind Harmer
0.251
203962AF1-287 GEN
Solar/Wind Harmer
1.723
970647AG2-420 GEN
Solar/Wind Harmer
1.698
20335126GROZ1-110
Adder
2.841
20335226CANZ2-011
Adder
2.761
20084926LAKVU GN
Adder
0.21
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
6.358
971185AH1-051 GEN
Solar/Wind Harmer
2.475
971355AH1-158 GEN
Solar/Wind Harmer
4.125
20328326MANOR_T86
Adder
0.165
238219AF1-167 C
Solar/Wind Harmer
1.049
972271AH1-720 GEN
Adder
6.781
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.94
200917MEHOOPANY_G
Solar/Wind Harmer
0.33
970679AG2-439 GEN
Solar/Wind Harmer
0.458
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.936
203854AF2-039 C
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Helper
0.504
20089026BF_G21_K23
Solar/Wind Helper
0.399
202652Y1-033 WT C
Solar/Wind Helper
0.372
972077AH1-588 GEN
Solar/Wind Harmer
34.236
972079AH1-589 GEN
Solar/Wind Harmer
40.417
970715AG2-457 GEN
Solar/Wind Harmer
13.266
972075AH1-587 GEN
Solar/Wind Harmer
24.541
20398826ARMNA MT
Solar/Wind Harmer
0.069
203859AF2-294 C
Solar/Wind Harmer
1.886
970313AG2-206 GEN
Solar/Wind Harmer
5.1
970305AG2-200 GEN
Solar/Wind Harmer
1.964
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.723
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Harmer
0.056
203848AF2-166 C
Solar/Wind Harmer
1.492
20084626FORWARD
Solar/Wind Helper
0.399
20088926STNY CRK
Solar/Wind Helper
0.82
20083426SW_E13_K22
Solar/Wind Helper
0.056
20088626ARWF_N39
Solar/Wind Helper
1.176
20303426NA_O38_P22
Solar/Wind Helper
0.964
203940AF1-140 C
Solar/Wind Helper
0.372
944781AF1-143 GEN
Solar/Wind Helper
2.09
203955AF1-039 C O1
Solar/Wind Helper
0.245
946071AF1-272 GEN
Solar/Wind Helper
1.627
20083926HOMER C3
50/50
272.069
20083826HOMER C2
50/50
257.001
20083226HNSMLK 5
50/50
11.769
20083726HOMER C1
Adder
-111.627
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.199
970663AG2-429 GEN
Solar/Wind Harmer
6.483
970663AG2-429 GEN
Solar/Wind Harmer
1.417
20084926LAKVU GN
Adder
0.236
966771AG1-548 GEN
Solar/Wind Harmer
2.769
966771AG1-548 GEN
Solar/Wind Harmer
3.462
970677AG2-438 GEN
Solar/Wind Harmer
0.927
203926AA2-133 GEN
Adder
2.454
20334726NME_Y1-047
Adder
2.206
20390726Y2-042
Adder
1.742
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.52
203961AE2-224 GEN
Solar/Wind Helper
2.523
20092526R32
Solar/Wind Helper
1.205
20091526CHSTN_FL
Solar/Wind Helper
0.389
20082826HNSMLK 1
50/50
11.769
20083026HNSMLK 3
50/50
11.769
20335026MILZ1-092
50/50
4.157
20326126BLOSSBCT
50/50
4.059
970713AG2-456 GEN
Solar/Wind Harmer
13.266
971705AH1-358 GEN
Solar/Wind Harmer
4.755
971709AH1-360 GEN
Solar/Wind Harmer
4.755
944411AF1-106 GEN
Solar/Wind Harmer
3.997
970337AG2-221 GEN
Solar/Wind Harmer
2.419
970511AG2-327 GEN
Solar/Wind Harmer
1.062
970267AG2-176 GEN
Solar/Wind Harmer
14.386
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
10
970647AG2-420 GEN
Solar/Wind Harmer
0.283
20084926LAKVU GN
Adder
0.21
971183AH1-050 GEN
Solar/Wind Harmer
4.125
238183AE2-316 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
8.587
24035802GEN-Y1-012
Adder
0.26
238206AE2-263_GEN
Solar/Wind Harmer
0.002
971865AH1-452 GEN
Solar/Wind Harmer
0.503
20091326SHAW-D
Adder
0.334
972169AH1-667 GEN
Solar/Wind Harmer
0.639
20088826HIGHLAND
Solar/Wind Helper
0.93
20089226LOOKOUT
Solar/Wind Helper
0.49
964201AG1-281 GEN
Solar/Wind Helper
0.416
20094526CT_V3-030
Solar/Wind Helper
0.257
961581Q1080_CY23
External Queue
36.97114562988281
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.012
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.369
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.185
LAGNLTFEXP_LAGN->PJM
CLTF
0.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
TVALTFEXP_TVA->PJM
CLTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.231
MECLTFEXP_MEC->PJM
CLTF
0.801
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.78 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:940.95
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
52.799
972079AH1-589 GEN
Solar/Wind Harmer
43.488
970715AG2-457 GEN
Solar/Wind Harmer
17.6
972075AH1-587 GEN
Solar/Wind Harmer
38.338
20398826ARMNA MT
Solar/Wind Harmer
4.359
203859AF2-294 C
Solar/Wind Harmer
2.894
970313AG2-206 GEN
Solar/Wind Harmer
7.852
20083926HOMER C3
50/50
285.029
20083826HOMER C2
50/50
269.243
20083226HNSMLK 5
50/50
13.162
940863AE2-074 GEN
Solar/Wind Harmer
3.814
203804AE2-113_GEN
Solar/Wind Harmer
8.618
970555AG2-356 GEN
Solar/Wind Harmer
3.385
970663AG2-429 GEN
Solar/Wind Harmer
11.496
970663AG2-429 GEN
Solar/Wind Harmer
1.871
20083726HOMER C1
Adder
-104.741
970677AG2-438 GEN
Solar/Wind Harmer
1.353
966771AG1-548 GEN
Solar/Wind Harmer
19.741
966771AG1-548 GEN
Solar/Wind Harmer
3.826
203846AF2-130 C
Solar/Wind Harmer
0.764
20084926LAKVU GN
Adder
0.261
203926AA2-133 GEN
Adder
2.667
20334726NME_Y1-047
Adder
2.402
20390726Y2-042
Adder
1.91
971055AG2-654 GEN
Solar/Wind Harmer
0.981
203855AF2-088 C
Solar/Wind Harmer
0.128
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.322
20091526CHSTN_FL
Solar/Wind Helper
0.335
20082926HNSMLK 2
50/50
13.162
20083126HNSMLK 4
50/50
13.162
971703AH1-357 GEN
Solar/Wind Harmer
4.4
20082826HNSMLK 1
50/50
13.162
20083026HNSMLK 3
50/50
13.162
20335026MILZ1-092
50/50
4.448
20326126BLOSSBCT
50/50
4.359
970713AG2-456 GEN
Solar/Wind Harmer
17.6
971705AH1-358 GEN
Solar/Wind Harmer
5.116
971709AH1-360 GEN
Solar/Wind Harmer
5.116
944411AF1-106 GEN
Solar/Wind Harmer
3.862
959471AF2-238 GEN
Solar/Wind Harmer
1.024
970337AG2-221 GEN
Solar/Wind Harmer
3.385
970511AG2-327 GEN
Solar/Wind Harmer
1.636
203860AG1-193 C
Solar/Wind Harmer
0.475
970267AG2-176 GEN
Solar/Wind Harmer
23.253
238183AE2-316 GEN
Solar/Wind Harmer
6.305
970647AG2-420 GEN
Solar/Wind Harmer
0.338
961971AG1-040 GEN
Solar/Wind Harmer
0.876
971183AH1-050 GEN
Solar/Wind Harmer
5.782
203835AF1-098 GEN
Solar/Wind Harmer
3.35
203813AE2-344_GEN
Solar/Wind Harmer
16.003
20084926LAKVU GN
Adder
0.232
203954AE2-126 C
Solar/Wind Harmer
0.595
20072226SHAWVL 2
Adder
10.566
238206AE2-263_GEN
Solar/Wind Harmer
1.658
24035802GEN-Y1-012
Adder
0.283
971865AH1-452 GEN
Solar/Wind Harmer
1.144
20091326SHAW-D
Adder
0.426
972169AH1-667 GEN
Solar/Wind Harmer
1.167
238215AE2-248 C
Solar/Wind Harmer
0.78
20088826HIGHLAND
Solar/Wind Helper
0.858
20089226LOOKOUT
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.375
971707AH1-359 GEN
Solar/Wind Harmer
4.4
20334926Z1-069 C
Solar/Wind Harmer
4.526
944411AF1-106 GEN
Solar/Wind Harmer
0.415
970335AG2-220 GEN
Solar/Wind Harmer
5.101
971127AH1-005 GEN
Solar/Wind Harmer
3.291
20120126WRREN CT
Adder
9.836
238219AF1-167 C
Solar/Wind Harmer
2.025
970647AG2-420 GEN
Solar/Wind Harmer
2.905
971185AH1-051 GEN
Solar/Wind Harmer
3.469
971355AH1-158 GEN
Solar/Wind Harmer
4.034
203856AF2-165 C
Solar/Wind Harmer
1.693
203948AG1-140 C
Solar/Wind Harmer
0.367
959441AF2-235 GEN
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.834
203962AF1-287 GEN
Solar/Wind Harmer
2.757
957161AF2-010 GEN
Solar/Wind Harmer
10.433
203830AF1-094 GEN
Solar/Wind Harmer
0.82
20084926LAKVU GN
Adder
0.232
20335126GROZ1-110
Adder
3.099
20335226CANZ2-011
Adder
3.012
203932AE1-123
Adder
2.515
20328326MANOR_T86
Adder
0.179
972271AH1-720 GEN
Adder
7.405
941421AE2-139 GEN
Solar/Wind Harmer
3.392
200917MEHOOPANY_G
Solar/Wind Harmer
3.576
970679AG2-439 GEN
Solar/Wind Harmer
0.798
238202AE2-262_GEN
Solar/Wind Harmer
1.779
971627AH1-313 GEN
Solar/Wind Harmer
6.977
203854AF2-039 C
Solar/Wind Harmer
0.265
945751AF1-240 GEN
Solar/Wind Harmer
1.012
20089126CSLMN_L13
Solar/Wind Helper
0.471
20089026BF_G21_K23
Solar/Wind Helper
0.373
202652Y1-033 WT C
Solar/Wind Helper
0.351
970305AG2-200 GEN
Solar/Wind Harmer
3.111
946381AF1-302 GEN
Solar/Wind Harmer
3.155
203980AG1-197 GEN
Solar/Wind Harmer
0.665
203963AG1-253 GEN
Solar/Wind Harmer
0.56
971931AH1-490 GEN
Solar/Wind Harmer
2.76
203979AG1-198 GEN
Solar/Wind Harmer
0.492
971933AH1-491 GEN
Solar/Wind Harmer
2.707
203848AF2-166 C
Solar/Wind Harmer
2.673
203947AF1-006 C
Solar/Wind Harmer
0.726
238217AF1-153 C O1
Solar/Wind Harmer
0.695
216419AE2-001 C
Solar/Wind Harmer
1.035
20084626FORWARD
Solar/Wind Helper
0.371
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.761
20088626ARWF_N39
Solar/Wind Helper
1.075
20303426NA_O38_P22
Solar/Wind Helper
0.881
203940AF1-140 C
Solar/Wind Helper
0.339
944781AF1-143 GEN
Solar/Wind Helper
1.956
203955AF1-039 C O1
Solar/Wind Helper
0.231
946071AF1-272 GEN
Solar/Wind Helper
1.436
961581Q1080_CY23
External Queue
37.79337692260742
LGEELTFEXP_LGEE->PJM
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.058
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.028
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
0.47
TVALTFEXP_TVA->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.907
MECLTFEXP_MEC->PJM
CLTF
0.656
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:930.45
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
3.597
971707AH1-359 GEN
Solar/Wind Harmer
3.597
20334926Z1-069 C
Solar/Wind Harmer
1.335
970335AG2-220 GEN
Solar/Wind Harmer
4.313
971127AH1-005 GEN
Solar/Wind Harmer
3.145
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.316
203962AF1-287 GEN
Solar/Wind Harmer
2.172
970647AG2-420 GEN
Solar/Wind Harmer
2.14
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.002
957161AF2-010 GEN
Solar/Wind Harmer
8.016
971185AH1-051 GEN
Solar/Wind Harmer
3.121
971355AH1-158 GEN
Solar/Wind Harmer
5.201
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.323
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
0.416
970679AG2-439 GEN
Solar/Wind Harmer
0.577
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.962
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.687
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
972077AH1-588 GEN
Solar/Wind Harmer
43.163
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
16.726
972075AH1-587 GEN
Solar/Wind Harmer
30.94
20398826ARMNA MT
Solar/Wind Harmer
0.087
203859AF2-294 C
Solar/Wind Harmer
2.377
970313AG2-206 GEN
Solar/Wind Harmer
6.43
970305AG2-200 GEN
Solar/Wind Harmer
2.477
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.503
971931AH1-490 GEN
Solar/Wind Harmer
2.172
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
2.093
203947AF1-006 C
Solar/Wind Harmer
0.07
203848AF2-166 C
Solar/Wind Harmer
1.881
216419AE2-001 C
Solar/Wind Harmer
0.704
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
0.011
970555AG2-356 GEN
Solar/Wind Harmer
2.772
970663AG2-429 GEN
Solar/Wind Harmer
8.174
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
3.492
966771AG1-548 GEN
Solar/Wind Harmer
4.365
970677AG2-438 GEN
Solar/Wind Harmer
1.168
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.655
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
16.726
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
5.039
970337AG2-221 GEN
Solar/Wind Harmer
3.049
970511AG2-327 GEN
Solar/Wind Harmer
1.34
970267AG2-176 GEN
Solar/Wind Harmer
18.137
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.007
203813AE2-344_GEN
Solar/Wind Harmer
12.608
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
5.201
238183AE2-316 GEN
Solar/Wind Harmer
0.006
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
0.003
971865AH1-452 GEN
Solar/Wind Harmer
0.634
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
0.805
238215AE2-248 C
Solar/Wind Harmer
0.525
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:898.89
MW Contribution:4.22
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
50.696
972079AH1-589 GEN
Solar/Wind Harmer
41.756
970715AG2-457 GEN
Solar/Wind Harmer
16.899
972075AH1-587 GEN
Solar/Wind Harmer
36.551
20398826ARMNA MT
Solar/Wind Harmer
4.195
203859AF2-294 C
Solar/Wind Harmer
2.784
970313AG2-206 GEN
Solar/Wind Harmer
7.539
970305AG2-200 GEN
Solar/Wind Harmer
2.947
203980AG1-197 GEN
Solar/Wind Harmer
0.626
203963AG1-253 GEN
Solar/Wind Harmer
0.532
946381AF1-302 GEN
Solar/Wind Harmer
2.792
971931AH1-490 GEN
Solar/Wind Harmer
2.603
203979AG1-198 GEN
Solar/Wind Harmer
0.46
971933AH1-491 GEN
Solar/Wind Harmer
2.528
203947AF1-006 C
Solar/Wind Harmer
0.687
203848AF2-166 C
Solar/Wind Harmer
2.378
238217AF1-153 C O1
Solar/Wind Harmer
0.626
216419AE2-001 C
Solar/Wind Harmer
0.898
20082826HNSMLK 1
50/50
12.408
20083026HNSMLK 3
50/50
12.408
20335026MILZ1-092
50/50
4.281
20326126BLOSSBCT
50/50
4.187
970713AG2-456 GEN
Solar/Wind Harmer
16.899
971705AH1-358 GEN
Solar/Wind Harmer
4.912
971709AH1-360 GEN
Solar/Wind Harmer
4.912
944411AF1-106 GEN
Solar/Wind Harmer
3.717
959471AF2-238 GEN
Solar/Wind Harmer
0.983
970337AG2-221 GEN
Solar/Wind Harmer
3.251
970511AG2-327 GEN
Solar/Wind Harmer
1.571
970267AG2-176 GEN
Solar/Wind Harmer
21.827
203860AG1-193 C
Solar/Wind Harmer
0.44
961971AG1-040 GEN
Solar/Wind Harmer
0.824
238183AE2-316 GEN
Solar/Wind Harmer
5.58
970647AG2-420 GEN
Solar/Wind Harmer
0.308
203835AF1-098 GEN
Solar/Wind Harmer
3.172
203813AE2-344_GEN
Solar/Wind Harmer
15.102
971183AH1-050 GEN
Solar/Wind Harmer
5.235
20084926LAKVU GN
Adder
0.22
203954AE2-126 C
Solar/Wind Harmer
0.542
20072226SHAWVL 2
Adder
9.429
24035802GEN-Y1-012
Adder
0.271
238206AE2-263_GEN
Solar/Wind Harmer
1.476
20091326SHAW-D
Adder
0.373
972169AH1-667 GEN
Solar/Wind Harmer
1.02
971865AH1-452 GEN
Solar/Wind Harmer
0.761
20088826HIGHLAND
Solar/Wind Helper
0.908
20089226LOOKOUT
Solar/Wind Helper
0.481
964201AG1-281 GEN
Solar/Wind Helper
0.403
20094526CT_V3-030
Solar/Wind Helper
0.241
20084626FORWARD
Solar/Wind Helper
0.391
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
20088626ARWF_N39
Solar/Wind Helper
1.142
20303426NA_O38_P22
Solar/Wind Helper
0.936
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.052
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.602
20083926HOMER C3
50/50
277.61
20083826HOMER C2
50/50
262.235
20083226HNSMLK 5
50/50
12.408
940863AE2-074 GEN
Solar/Wind Harmer
3.667
203804AE2-113_GEN
Solar/Wind Harmer
8.186
970555AG2-356 GEN
Solar/Wind Harmer
3.251
20083726HOMER C1
Adder
-109.082
970663AG2-429 GEN
Solar/Wind Harmer
9.987
970663AG2-429 GEN
Solar/Wind Harmer
1.626
970677AG2-438 GEN
Solar/Wind Harmer
1.264
966771AG1-548 GEN
Solar/Wind Harmer
18.467
966771AG1-548 GEN
Solar/Wind Harmer
3.579
20084926LAKVU GN
Adder
0.248
203846AF2-130 C
Solar/Wind Harmer
0.679
203926AA2-133 GEN
Adder
2.542
20334726NME_Y1-047
Adder
2.287
20390726Y2-042
Adder
1.81
203855AF2-088 C
Solar/Wind Harmer
0.112
971055AG2-654 GEN
Solar/Wind Harmer
0.641
20092526R32
Solar/Wind Helper
1.178
203961AE2-224 GEN
Solar/Wind Helper
2.456
20091526CHSTN_FL
Solar/Wind Helper
0.371
20082926HNSMLK 2
50/50
12.408
20083126HNSMLK 4
50/50
12.408
971703AH1-357 GEN
Solar/Wind Harmer
4.225
971707AH1-359 GEN
Solar/Wind Harmer
4.225
20334926Z1-069 C
Solar/Wind Harmer
4.357
944411AF1-106 GEN
Solar/Wind Harmer
0.4
970335AG2-220 GEN
Solar/Wind Harmer
4.898
971127AH1-005 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
9.318
203948AG1-140 C
Solar/Wind Harmer
0.348
970647AG2-420 GEN
Solar/Wind Harmer
2.646
962511AG1-100 GEN
Solar/Wind Harmer
0.787
203962AF1-287 GEN
Solar/Wind Harmer
2.602
971185AH1-051 GEN
Solar/Wind Harmer
3.141
971355AH1-158 GEN
Solar/Wind Harmer
3.653
203856AF2-165 C
Solar/Wind Harmer
1.536
238219AF1-167 C
Solar/Wind Harmer
1.719
959441AF2-235 GEN
Solar/Wind Harmer
0.383
957161AF2-010 GEN
Solar/Wind Harmer
9.735
203830AF1-094 GEN
Solar/Wind Harmer
0.766
20335126GROZ1-110
Adder
2.949
20335226CANZ2-011
Adder
2.867
20084926LAKVU GN
Adder
0.22
20328326MANOR_T86
Adder
0.171
203932AE1-123
Adder
2.197
972271AH1-720 GEN
Adder
7.041
941421AE2-139 GEN
Solar/Wind Harmer
3.22
200917MEHOOPANY_G
Solar/Wind Harmer
3.404
970679AG2-439 GEN
Solar/Wind Harmer
0.756
238202AE2-262_GEN
Solar/Wind Harmer
1.583
971627AH1-313 GEN
Solar/Wind Harmer
6.208
203854AF2-039 C
Solar/Wind Harmer
0.232
945751AF1-240 GEN
Solar/Wind Harmer
0.814
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.366
961581Q1080_CY23
External Queue
37.30971908569336
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.867
LAGNLTFEXP_LAGN->PJM
CLTF
0.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.036
TVALTFEXP_TVA->PJM
CLTF
0.277
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.138
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT27_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT27_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:759.23
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-004-DRT-003_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:759.23
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT26_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT26_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.75 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:758.81
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-004-DRT-004_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-004_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.75 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:758.8
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-2_PN-500-004A-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-2_PN-500-004A-DRT_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.01 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:715.77
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20080526COLVER13
50/50
1.087
203843AF2-002_GEN
Solar/Wind Harmer
1.642
970631AG2-411 GEN
Solar/Wind Harmer
10.3
20088826HIGHLAND
Solar/Wind Harmer
2.567
971279AH1-102 GEN
Solar/Wind Harmer
12.766
957561AF2-050 GEN
Solar/Wind Harmer
7.496
20094526CT_V3-030
Solar/Wind Harmer
1.056
971423AH1-203 GEN
Solar/Wind Harmer
10.375
964201AG1-281 GEN
Solar/Wind Harmer
0.864
20089226LOOKOUT
Solar/Wind Harmer
1.049
970713AG2-456 GEN
Solar/Wind Harmer
9.421
971705AH1-358 GEN
Solar/Wind Harmer
2.739
971709AH1-360 GEN
Solar/Wind Harmer
2.739
203987AE2-118 C
Solar/Wind Harmer
2.243
964391AG1-301 GEN
Solar/Wind Harmer
0.625
20082826HNSMLK 1
Adder
5.966
20083026HNSMLK 3
Adder
5.966
20326126BLOSSBCT
Adder
2.23
20091326SHAW-D
Adder
0.639
972169AH1-667 GEN
Solar/Wind Harmer
1.749
203954AE2-126 C
Solar/Wind Harmer
0.588
20335026MILZ1-092
Adder
2.205
944411AF1-106 GEN
Solar/Wind Harmer
2.032
959471AF2-238 GEN
Solar/Wind Harmer
0.556
970337AG2-221 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
3.669
238183AE2-316 GEN
Solar/Wind Harmer
3.802
970647AG2-420 GEN
Solar/Wind Harmer
0.208
970511AG2-327 GEN
Solar/Wind Harmer
0.885
20072226SHAWVL 2
Adder
12.056
203860AG1-193 C
Solar/Wind Harmer
0.266
238206AE2-263_GEN
Solar/Wind Harmer
1.93
970267AG2-176 GEN
Solar/Wind Harmer
12.084
961971AG1-040 GEN
Solar/Wind Harmer
0.456
238215AE2-248 C
Solar/Wind Harmer
1.193
203835AF1-098 GEN
Solar/Wind Harmer
1.806
203813AE2-344_GEN
Solar/Wind Harmer
8.348
20084926LAKVU GN
Adder
0.122
20080926SITHE
50/50
0.52
946071AF1-272 GEN
Solar/Wind Harmer
6.958
203839AF1-321 GEN
Solar/Wind Harmer
3.284
20084626FORWARD
Solar/Wind Harmer
1.292
203857AF2-221 C
Solar/Wind Harmer
2.437
970123AG2-090 GEN
Solar/Wind Harmer
2.275
203940AF1-140 C
Solar/Wind Harmer
0.747
20088926STNY CRK
Solar/Wind Harmer
1.827
971441AH1-212 GEN
Solar/Wind Harmer
2.99
971427AH1-205 GEN
Solar/Wind Harmer
2.207
20083426SW_E13_K22
Solar/Wind Harmer
0.434
20088626ARWF_N39
Solar/Wind Harmer
2.671
20303426NA_O38_P22
Solar/Wind Harmer
2.162
944781AF1-143 GEN
Solar/Wind Harmer
3.692
203853AF1-134 C O1
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
28.263
972079AH1-589 GEN
Solar/Wind Harmer
23.279
970715AG2-457 GEN
Solar/Wind Harmer
9.421
972075AH1-587 GEN
Solar/Wind Harmer
22.395
203952AE2-129 C
Solar/Wind Harmer
0.657
203946AE2-131 C
Solar/Wind Harmer
0.656
962411AG1-090 GEN
Solar/Wind Harmer
10.305
20398826ARMNA MT
Solar/Wind Harmer
2.3
203955AF1-039 C O1
Solar/Wind Harmer
0.423
203848AF2-166 C
Solar/Wind Harmer
1.855
946381AF1-302 GEN
Solar/Wind Harmer
1.902
970305AG2-200 GEN
Solar/Wind Harmer
1.796
203859AF2-294 C
Solar/Wind Harmer
1.523
238217AF1-153 C O1
Solar/Wind Harmer
0.541
970313AG2-206 GEN
Solar/Wind Harmer
4.249
203980AG1-197 GEN
Solar/Wind Harmer
0.346
203979AG1-198 GEN
Solar/Wind Harmer
0.276
971933AH1-491 GEN
Solar/Wind Harmer
1.518
216419AE2-001 C
Solar/Wind Harmer
1.511
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.436
203947AF1-006 C
Solar/Wind Harmer
0.379
20083726HOMER C1
50/50
161.556
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.462
20083826HOMER C2
50/50
126.07
20092526R32
Solar/Wind Harmer
2.751
203844AF2-092 C
Solar/Wind Harmer
1.843
203850AG1-041 C
Solar/Wind Harmer
1.837
203961AE2-224 GEN
Solar/Wind Harmer
4.541
20091526CHSTN_FL
Solar/Wind Harmer
1.215
20090526Q36
Solar/Wind Harmer
1.835
203993AD2-133_GEN1
Solar/Wind Harmer
1.835
940863AE2-074 GEN
Solar/Wind Harmer
2.03
203804AE2-113_GEN
Solar/Wind Harmer
5.24
965121AG1-377 GEN
Solar/Wind Harmer
2.169
941231AE2-117 GEN
Solar/Wind Harmer
0.635
20083226HNSMLK 5
Adder
5.966
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.53
970555AG2-356 GEN
Solar/Wind Harmer
1.838
970663AG2-429 GEN
Solar/Wind Harmer
6.046
970663AG2-429 GEN
Solar/Wind Harmer
0.984
970677AG2-438 GEN
Solar/Wind Harmer
0.759
966771AG1-548 GEN
Solar/Wind Harmer
10.997
966771AG1-548 GEN
Solar/Wind Harmer
2.131
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.532
20334726NME_Y1-047
Adder
1.382
971321AH1-140 GEN
Solar/Wind Harmer
8.457
971321AH1-140 GEN
Solar/Wind Harmer
1.639
20390726Y2-042
Adder
1.122
20083326SEWRDB34
50/50
5.324
20079426CONEMAGH
50/50
2.015
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.284
971879AH1-460 GEN
Solar/Wind Harmer
10.772
970125AG2-091 GEN
Solar/Wind Harmer
0.975
971541AH1-268 GEN
Solar/Wind Harmer
5.433
970899AG2-561 GEN
Solar/Wind Harmer
3.104
971419AH1-201 GEN
Solar/Wind Harmer
4.744
203818AF1-086 GEN
Solar/Wind Harmer
3.548
20089126CSLMN_L13
Solar/Wind Harmer
1.077
20089026BF_G21_K23
Solar/Wind Harmer
0.853
945751AF1-240 GEN
Solar/Wind Harmer
1.918
960051AF2-296 GEN
Solar/Wind Harmer
2.42
971703AH1-357 GEN
Solar/Wind Harmer
2.355
971707AH1-359 GEN
Solar/Wind Harmer
2.355
20334926Z1-069 C
Solar/Wind Harmer
2.383
965131AG1-378 GEN
Solar/Wind Harmer
2.169
20082926HNSMLK 2
Adder
5.966
20083126HNSMLK 4
Adder
5.966
203854AF2-039 C
Solar/Wind Harmer
0.397
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.888
202652Y1-033 WT C
Solar/Wind Harmer
0.869
971185AH1-051 GEN
Solar/Wind Harmer
2.202
971355AH1-158 GEN
Solar/Wind Harmer
2.56
20120126WRREN CT
Adder
5.678
203856AF2-165 C
Solar/Wind Harmer
1.068
970647AG2-420 GEN
Solar/Wind Harmer
1.789
970335AG2-220 GEN
Solar/Wind Harmer
2.757
971127AH1-005 GEN
Solar/Wind Harmer
1.779
959441AF2-235 GEN
Solar/Wind Harmer
0.257
238219AF1-167 C
Solar/Wind Harmer
1.122
238202AE2-262_GEN
Solar/Wind Harmer
2.071
971627AH1-313 GEN
Solar/Wind Harmer
8.119
20335126GROZ1-110
Adder
1.864
20335226CANZ2-011
Adder
1.812
957161AF2-010 GEN
Solar/Wind Harmer
5.877
203830AF1-094 GEN
Solar/Wind Harmer
0.46
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.44
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.434
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.069
972271AH1-720 GEN
Adder
4.404
200917MEHOOPANY_G
Solar/Wind Harmer
2.057
970679AG2-439 GEN
Solar/Wind Harmer
0.469
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.173
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.51
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.376
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:711.02
MW Contribution:2.2
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.493
946071AF1-272 GEN
Solar/Wind Harmer
6.65
203839AF1-321 GEN
Solar/Wind Harmer
3.098
20084626FORWARD
Solar/Wind Harmer
1.219
203857AF2-221 C
Solar/Wind Harmer
2.292
970123AG2-090 GEN
Solar/Wind Harmer
2.139
203940AF1-140 C
Solar/Wind Harmer
0.7
20088926STNY CRK
Solar/Wind Harmer
1.725
971427AH1-205 GEN
Solar/Wind Harmer
2.084
971441AH1-212 GEN
Solar/Wind Harmer
2.794
20083426SW_E13_K22
Solar/Wind Harmer
0.411
20088626ARWF_N39
Solar/Wind Harmer
2.475
20303426NA_O38_P22
Solar/Wind Harmer
2.004
944781AF1-143 GEN
Solar/Wind Harmer
3.533
203853AF1-134 C O1
Solar/Wind Harmer
0.681
972077AH1-588 GEN
Solar/Wind Harmer
26.452
972079AH1-589 GEN
Solar/Wind Harmer
21.787
970715AG2-457 GEN
Solar/Wind Harmer
8.817
972075AH1-587 GEN
Solar/Wind Harmer
20.869
203952AE2-129 C
Solar/Wind Harmer
0.606
203946AE2-131 C
Solar/Wind Harmer
0.605
962411AG1-090 GEN
Solar/Wind Harmer
9.501
203955AF1-039 C O1
Solar/Wind Harmer
0.412
20398826ARMNA MT
Solar/Wind Harmer
2.11
203848AF2-166 C
Solar/Wind Harmer
1.73
970305AG2-200 GEN
Solar/Wind Harmer
1.677
946381AF1-302 GEN
Solar/Wind Harmer
1.756
238217AF1-153 C O1
Solar/Wind Harmer
0.496
203859AF2-294 C
Solar/Wind Harmer
1.387
970313AG2-206 GEN
Solar/Wind Harmer
3.861
203980AG1-197 GEN
Solar/Wind Harmer
0.326
203979AG1-198 GEN
Solar/Wind Harmer
0.259
971933AH1-491 GEN
Solar/Wind Harmer
1.425
203963AG1-253 GEN
Solar/Wind Harmer
0.276
971931AH1-490 GEN
Solar/Wind Harmer
1.353
216419AE2-001 C
Solar/Wind Harmer
1.35
203947AF1-006 C
Solar/Wind Harmer
0.357
20216026CON.GEN2
50/50
0.019
20083326SEWRDB34
50/50
4.935
20079426CONEMAGH
50/50
1.887
203841AF2-001_GEN
Solar/Wind Harmer
3.098
971879AH1-460 GEN
Solar/Wind Harmer
10.144
970125AG2-091 GEN
Solar/Wind Harmer
0.917
971541AH1-268 GEN
Solar/Wind Harmer
5.102
970899AG2-561 GEN
Solar/Wind Harmer
2.926
971419AH1-201 GEN
Solar/Wind Harmer
4.481
203818AF1-086 GEN
Solar/Wind Harmer
3.327
20089126CSLMN_L13
Solar/Wind Harmer
1.031
20089026BF_G21_K23
Solar/Wind Harmer
0.816
945751AF1-240 GEN
Solar/Wind Harmer
1.798
960051AF2-296 GEN
Solar/Wind Harmer
2.253
971703AH1-357 GEN
Solar/Wind Harmer
2.204
971707AH1-359 GEN
Solar/Wind Harmer
2.204
20334926Z1-069 C
Solar/Wind Harmer
2.216
965131AG1-378 GEN
Solar/Wind Harmer
2
20082926HNSMLK 2
Adder
5.623
20083126HNSMLK 4
Adder
5.623
202652Y1-033 WT C
Solar/Wind Harmer
0.847
203854AF2-039 C
Solar/Wind Harmer
0.365
203932AE1-123
Adder
1.757
944411AF1-106 GEN
Solar/Wind Harmer
0.2
971185AH1-051 GEN
Solar/Wind Harmer
2.058
971355AH1-158 GEN
Solar/Wind Harmer
2.393
20120126WRREN CT
Adder
5.302
203856AF2-165 C
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
1.674
970335AG2-220 GEN
Solar/Wind Harmer
2.507
971127AH1-005 GEN
Solar/Wind Harmer
1.617
959441AF2-235 GEN
Solar/Wind Harmer
0.241
238219AF1-167 C
Solar/Wind Harmer
1.034
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.332
957161AF2-010 GEN
Solar/Wind Harmer
5.518
20335126GROZ1-110
Adder
1.677
20335226CANZ2-011
Adder
1.63
203830AF1-094 GEN
Solar/Wind Harmer
0.432
203948AG1-140 C
Solar/Wind Harmer
0.181
203962AF1-287 GEN
Solar/Wind Harmer
1.356
962511AG1-100 GEN
Solar/Wind Harmer
0.409
20084926LAKVU GN
Adder
0.115
20328326MANOR_T86
Adder
0.091
941421AE2-139 GEN
Solar/Wind Harmer
1.826
972271AH1-720 GEN
Adder
3.879
200917MEHOOPANY_G
Solar/Wind Harmer
1.778
20080526COLVER13
50/50
1.024
203843AF2-002_GEN
Solar/Wind Harmer
1.549
970631AG2-411 GEN
Solar/Wind Harmer
9.713
20088826HIGHLAND
Solar/Wind Harmer
2.407
971279AH1-102 GEN
Solar/Wind Harmer
11.989
971423AH1-203 GEN
Solar/Wind Harmer
9.809
957561AF2-050 GEN
Solar/Wind Harmer
6.963
20094526CT_V3-030
Solar/Wind Harmer
0.99
964201AG1-281 GEN
Solar/Wind Harmer
0.806
20089226LOOKOUT
Solar/Wind Harmer
1.004
970713AG2-456 GEN
Solar/Wind Harmer
8.817
971705AH1-358 GEN
Solar/Wind Harmer
2.563
971709AH1-360 GEN
Solar/Wind Harmer
2.563
203987AE2-118 C
Solar/Wind Harmer
2.054
20082826HNSMLK 1
Adder
5.623
20083026HNSMLK 3
Adder
5.623
964391AG1-301 GEN
Solar/Wind Harmer
0.569
203954AE2-126 C
Solar/Wind Harmer
0.541
20326126BLOSSBCT
Adder
2.045
20091326SHAW-D
Adder
0.586
972169AH1-667 GEN
Solar/Wind Harmer
1.605
20335026MILZ1-092
Adder
2.022
944411AF1-106 GEN
Solar/Wind Harmer
1.863
971183AH1-050 GEN
Solar/Wind Harmer
3.43
959471AF2-238 GEN
Solar/Wind Harmer
0.507
970337AG2-221 GEN
Solar/Wind Harmer
1.677
970647AG2-420 GEN
Solar/Wind Harmer
0.195
238183AE2-316 GEN
Solar/Wind Harmer
3.509
203860AG1-193 C
Solar/Wind Harmer
0.249
970511AG2-327 GEN
Solar/Wind Harmer
0.804
20072226SHAWVL 2
Adder
10.985
970267AG2-176 GEN
Solar/Wind Harmer
11.379
238206AE2-263_GEN
Solar/Wind Harmer
1.743
961971AG1-040 GEN
Solar/Wind Harmer
0.429
203835AF1-098 GEN
Solar/Wind Harmer
1.697
203813AE2-344_GEN
Solar/Wind Harmer
7.866
238215AE2-248 C
Solar/Wind Harmer
1.065
20084926LAKVU GN
Adder
0.115
20083726HOMER C1
50/50
153.413
20215826CON.GEN1
50/50
0.027
20063626IUP CO-G
50/50
0.154
20083926HOMER C3
50/50
126.285
20083826HOMER C2
50/50
119.291
20092526R32
Solar/Wind Harmer
2.579
203844AF2-092 C
Solar/Wind Harmer
1.732
203850AG1-041 C
Solar/Wind Harmer
1.726
203961AE2-224 GEN
Solar/Wind Harmer
4.218
20091526CHSTN_FL
Solar/Wind Harmer
1.131
20090526Q36
Solar/Wind Harmer
1.697
203993AD2-133_GEN1
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
1.893
203804AE2-113_GEN
Solar/Wind Harmer
4.875
965121AG1-377 GEN
Solar/Wind Harmer
2
20083226HNSMLK 5
Adder
5.623
941231AE2-117 GEN
Solar/Wind Harmer
0.579
203855AF2-088 C
Solar/Wind Harmer
0.176
203846AF2-130 C
Solar/Wind Harmer
0.494
970555AG2-356 GEN
Solar/Wind Harmer
1.677
970663AG2-429 GEN
Solar/Wind Harmer
5.593
970663AG2-429 GEN
Solar/Wind Harmer
0.911
970677AG2-438 GEN
Solar/Wind Harmer
0.713
966771AG1-548 GEN
Solar/Wind Harmer
10.331
966771AG1-548 GEN
Solar/Wind Harmer
2.002
20084926LAKVU GN
Adder
0.129
971321AH1-140 GEN
Solar/Wind Harmer
9.071
971321AH1-140 GEN
Solar/Wind Harmer
1.758
203926AA2-133 GEN
Adder
1.344
20334726NME_Y1-047
Adder
1.195
LGEELTFEXP_LGEE->PJM
CLTF
0.128
WECLTFEXP_WEC->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.284
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.569
MECLTFEXP_MEC->PJM
CLTF
0.336
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-A_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.72 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:968.54
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.491
20066526SHAWVL 3
50/50
2.472
20071526SHAWVL 1
50/50
1.675
216419AE2-001 C
Solar/Wind Harmer
6.264
203952AE2-129 C
Solar/Wind Harmer
1.18
203946AE2-131 C
Solar/Wind Harmer
1.178
962411AG1-090 GEN
Solar/Wind Harmer
18.509
200642SENECA#1
50/50
1.72
203975AE1-071-GEN
Solar/Wind Harmer
13.301
941231AE2-117 GEN
Solar/Wind Harmer
1.738
203855AF2-088 C
Solar/Wind Harmer
0.404
965121AG1-377 GEN
Solar/Wind Harmer
3.897
20090526Q36
Solar/Wind Harmer
2.895
203993AD2-133_GEN1
Solar/Wind Harmer
2.895
203961AE2-224 GEN
Solar/Wind Harmer
4.729
20091526CHSTN_FL
Solar/Wind Harmer
1.356
203804AE2-113_GEN
Solar/Wind Harmer
6.224
203850AG1-041 C
Solar/Wind Harmer
1.233
203844AF2-092 C
Solar/Wind Harmer
1.201
20092526R32
Solar/Wind Harmer
1.725
940863AE2-074 GEN
Solar/Wind Harmer
1.638
970555AG2-356 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.396
970663AG2-429 GEN
Solar/Wind Harmer
4.749
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.551
238202AE2-262_GEN
Solar/Wind Harmer
6.642
971627AH1-313 GEN
Solar/Wind Harmer
26.043
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.897
960051AF2-296 GEN
Solar/Wind Harmer
3.17
203818AF1-086 GEN
Solar/Wind Harmer
3.162
20120126WRREN CT
Adder
6.343
971703AH1-357 GEN
Solar/Wind Harmer
1.992
971707AH1-359 GEN
Solar/Wind Harmer
1.992
970899AG2-561 GEN
Solar/Wind Harmer
1.806
20335126GROZ1-110
Adder
2.098
20335226CANZ2-011
Adder
2.04
20334926Z1-069 C
Solar/Wind Harmer
1.817
970125AG2-091 GEN
Solar/Wind Harmer
0.515
971419AH1-201 GEN
Solar/Wind Harmer
2.682
971541AH1-268 GEN
Solar/Wind Harmer
2.916
971879AH1-460 GEN
Solar/Wind Harmer
5.499
945751AF1-240 GEN
Solar/Wind Harmer
1.26
203841AF2-001_GEN
Solar/Wind Harmer
1.597
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
2.261
203932AE1-123
Adder
1.419
238219AF1-167 C
Solar/Wind Harmer
0.957
970335AG2-220 GEN
Solar/Wind Harmer
2.16
971127AH1-005 GEN
Solar/Wind Harmer
1.394
944411AF1-106 GEN
Solar/Wind Harmer
0.157
972271AH1-720 GEN
Adder
4.391
971185AH1-051 GEN
Solar/Wind Harmer
1.605
971355AH1-158 GEN
Solar/Wind Harmer
1.866
203856AF2-165 C
Solar/Wind Harmer
0.786
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.446
957161AF2-010 GEN
Solar/Wind Harmer
4.846
203830AF1-094 GEN
Solar/Wind Harmer
0.381
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.458
20083126HNSMLK 4
Adder
3.458
203962AF1-287 GEN
Solar/Wind Harmer
1.168
962511AG1-100 GEN
Solar/Wind Harmer
0.348
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.647
20088626ARWF_N39
Solar/Wind Harmer
3.372
20303426NA_O38_P22
Solar/Wind Harmer
2.73
238217AF1-153 C O1
Solar/Wind Harmer
1.027
203853AF1-134 C O1
Solar/Wind Harmer
0.958
946381AF1-302 GEN
Solar/Wind Harmer
2.753
972075AH1-587 GEN
Solar/Wind Harmer
24.236
971441AH1-212 GEN
Solar/Wind Harmer
2.406
203940AF1-140 C
Solar/Wind Harmer
0.558
970305AG2-200 GEN
Solar/Wind Harmer
2.006
972077AH1-588 GEN
Solar/Wind Harmer
23.902
972079AH1-589 GEN
Solar/Wind Harmer
19.687
970715AG2-457 GEN
Solar/Wind Harmer
7.967
203857AF2-221 C
Solar/Wind Harmer
1.289
970123AG2-090 GEN
Solar/Wind Harmer
1.203
20088926STNY CRK
Solar/Wind Harmer
1.036
971427AH1-205 GEN
Solar/Wind Harmer
1.247
20084626FORWARD
Solar/Wind Harmer
0.653
203839AF1-321 GEN
Solar/Wind Harmer
1.597
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.678
970313AG2-206 GEN
Solar/Wind Harmer
3.34
946071AF1-272 GEN
Solar/Wind Harmer
2.309
203848AF2-166 C
Solar/Wind Harmer
1.385
944781AF1-143 GEN
Solar/Wind Harmer
1.93
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.256
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.047
203947AF1-006 C
Solar/Wind Harmer
0.325
203980AG1-197 GEN
Solar/Wind Harmer
0.262
971931AH1-490 GEN
Solar/Wind Harmer
1.15
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.407
20072226SHAWVL 2
50/50
32.684
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.443
200643SENECA#2
50/50
1.604
970643AG2-418 GEN
Solar/Wind Harmer
4.443
238215AE2-248 C
Solar/Wind Harmer
5.151
964391AG1-301 GEN
Solar/Wind Harmer
1.797
203987AE2-118 C
Solar/Wind Harmer
5.347
238206AE2-263_GEN
Solar/Wind Harmer
6.191
972169AH1-667 GEN
Solar/Wind Harmer
3.697
203954AE2-126 C
Solar/Wind Harmer
1.11
957561AF2-050 GEN
Solar/Wind Harmer
7.807
964201AG1-281 GEN
Solar/Wind Harmer
0.898
238183AE2-316 GEN
Solar/Wind Harmer
5.501
20094526CT_V3-030
Solar/Wind Harmer
0.812
970713AG2-456 GEN
Solar/Wind Harmer
7.967
971705AH1-358 GEN
Solar/Wind Harmer
2.316
971709AH1-360 GEN
Solar/Wind Harmer
2.316
20088826HIGHLAND
Solar/Wind Harmer
1.61
971279AH1-102 GEN
Solar/Wind Harmer
6.852
970631AG2-411 GEN
Solar/Wind Harmer
5.204
971423AH1-203 GEN
Solar/Wind Harmer
5.698
20326126BLOSSBCT
Adder
1.863
203843AF2-002_GEN
Solar/Wind Harmer
0.799
959471AF2-238 GEN
Solar/Wind Harmer
0.453
970337AG2-221 GEN
Solar/Wind Harmer
1.499
970511AG2-327 GEN
Solar/Wind Harmer
0.696
20335026MILZ1-092
Adder
1.584
944411AF1-106 GEN
Solar/Wind Harmer
1.459
203835AF1-098 GEN
Solar/Wind Harmer
1.684
971183AH1-050 GEN
Solar/Wind Harmer
2.674
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.458
20083026HNSMLK 3
Adder
3.458
203813AE2-344_GEN
Solar/Wind Harmer
6.77
970267AG2-176 GEN
Solar/Wind Harmer
8.701
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.084
970663AG2-429 GEN
Solar/Wind Harmer
0.773
20083926HOMER C3
Adder
48.654
20083826HOMER C2
Adder
45.959
20083726HOMER C1
Adder
45.378
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.155
966771AG1-548 GEN
Solar/Wind Harmer
1.774
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.458
203926AA2-133 GEN
Adder
1.313
20334726NME_Y1-047
Adder
1.107
LGEELTFEXP_LGEE->PJM
CLTF
0.561
WECLTFEXP_WEC->PJM
CLTF
0.331
CPLELTFEXP_CPLE->PJM
CLTF
0.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.847
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.861
LAGNLTFEXP_LAGN->PJM
CLTF
1.332
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.995
TVALTFEXP_TVA->PJM
CLTF
0.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.591
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.561
MECLTFEXP_MEC->PJM
CLTF
1.38
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-B_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.7 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:968.43
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.555
238202AE2-262_GEN
Solar/Wind Harmer
6.645
971627AH1-313 GEN
Solar/Wind Harmer
26.055
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.899
960051AF2-296 GEN
Solar/Wind Harmer
3.172
203818AF1-086 GEN
Solar/Wind Harmer
3.164
20120126WRREN CT
Adder
6.346
971703AH1-357 GEN
Solar/Wind Harmer
1.993
971707AH1-359 GEN
Solar/Wind Harmer
1.993
970899AG2-561 GEN
Solar/Wind Harmer
1.807
20335126GROZ1-110
Adder
2.101
20335226CANZ2-011
Adder
2.042
20334926Z1-069 C
Solar/Wind Harmer
1.818
970125AG2-091 GEN
Solar/Wind Harmer
0.516
971419AH1-201 GEN
Solar/Wind Harmer
2.683
971541AH1-268 GEN
Solar/Wind Harmer
2.918
971879AH1-460 GEN
Solar/Wind Harmer
5.502
945751AF1-240 GEN
Solar/Wind Harmer
1.261
203841AF2-001_GEN
Solar/Wind Harmer
1.598
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
2.265
203932AE1-123
Adder
1.42
238219AF1-167 C
Solar/Wind Harmer
0.957
970335AG2-220 GEN
Solar/Wind Harmer
2.164
971127AH1-005 GEN
Solar/Wind Harmer
1.396
944411AF1-106 GEN
Solar/Wind Harmer
0.157
972271AH1-720 GEN
Adder
4.399
971185AH1-051 GEN
Solar/Wind Harmer
1.605
971355AH1-158 GEN
Solar/Wind Harmer
1.867
203856AF2-165 C
Solar/Wind Harmer
0.786
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.446
957161AF2-010 GEN
Solar/Wind Harmer
4.848
203830AF1-094 GEN
Solar/Wind Harmer
0.381
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.459
20083126HNSMLK 4
Adder
3.459
203962AF1-287 GEN
Solar/Wind Harmer
1.168
962511AG1-100 GEN
Solar/Wind Harmer
0.348
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.652
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.492
20066526SHAWVL 3
50/50
2.473
20071526SHAWVL 1
50/50
1.676
216419AE2-001 C
Solar/Wind Harmer
6.267
203952AE2-129 C
Solar/Wind Harmer
1.181
203946AE2-131 C
Solar/Wind Harmer
1.179
962411AG1-090 GEN
Solar/Wind Harmer
18.518
20088626ARWF_N39
Solar/Wind Harmer
3.374
20303426NA_O38_P22
Solar/Wind Harmer
2.731
238217AF1-153 C O1
Solar/Wind Harmer
1.028
203853AF1-134 C O1
Solar/Wind Harmer
0.959
946381AF1-302 GEN
Solar/Wind Harmer
2.754
972075AH1-587 GEN
Solar/Wind Harmer
24.25
971441AH1-212 GEN
Solar/Wind Harmer
2.407
203940AF1-140 C
Solar/Wind Harmer
0.559
970305AG2-200 GEN
Solar/Wind Harmer
2.007
972077AH1-588 GEN
Solar/Wind Harmer
23.917
972079AH1-589 GEN
Solar/Wind Harmer
19.699
970715AG2-457 GEN
Solar/Wind Harmer
7.972
203857AF2-221 C
Solar/Wind Harmer
1.289
970123AG2-090 GEN
Solar/Wind Harmer
1.203
20088926STNY CRK
Solar/Wind Harmer
1.036
971427AH1-205 GEN
Solar/Wind Harmer
1.248
20084626FORWARD
Solar/Wind Harmer
0.653
203839AF1-321 GEN
Solar/Wind Harmer
1.598
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.68
970313AG2-206 GEN
Solar/Wind Harmer
3.345
946071AF1-272 GEN
Solar/Wind Harmer
2.31
203848AF2-166 C
Solar/Wind Harmer
1.386
944781AF1-143 GEN
Solar/Wind Harmer
1.93
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.257
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.049
203947AF1-006 C
Solar/Wind Harmer
0.325
203980AG1-197 GEN
Solar/Wind Harmer
0.263
971931AH1-490 GEN
Solar/Wind Harmer
1.151
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.402
20072226SHAWVL 2
50/50
32.7
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.605
970643AG2-418 GEN
Solar/Wind Harmer
4.444
238215AE2-248 C
Solar/Wind Harmer
5.154
964391AG1-301 GEN
Solar/Wind Harmer
1.798
203987AE2-118 C
Solar/Wind Harmer
5.349
238206AE2-263_GEN
Solar/Wind Harmer
6.194
972169AH1-667 GEN
Solar/Wind Harmer
3.699
203954AE2-126 C
Solar/Wind Harmer
1.111
957561AF2-050 GEN
Solar/Wind Harmer
7.812
964201AG1-281 GEN
Solar/Wind Harmer
0.898
238183AE2-316 GEN
Solar/Wind Harmer
5.504
20094526CT_V3-030
Solar/Wind Harmer
0.812
970713AG2-456 GEN
Solar/Wind Harmer
7.972
971705AH1-358 GEN
Solar/Wind Harmer
2.318
971709AH1-360 GEN
Solar/Wind Harmer
2.318
20088826HIGHLAND
Solar/Wind Harmer
1.611
971279AH1-102 GEN
Solar/Wind Harmer
6.857
970631AG2-411 GEN
Solar/Wind Harmer
5.207
20326126BLOSSBCT
Adder
1.865
971423AH1-203 GEN
Solar/Wind Harmer
5.7
203843AF2-002_GEN
Solar/Wind Harmer
0.799
959471AF2-238 GEN
Solar/Wind Harmer
0.454
970337AG2-221 GEN
Solar/Wind Harmer
1.501
970511AG2-327 GEN
Solar/Wind Harmer
0.697
20335026MILZ1-092
Adder
1.586
944411AF1-106 GEN
Solar/Wind Harmer
1.461
203835AF1-098 GEN
Solar/Wind Harmer
1.684
971183AH1-050 GEN
Solar/Wind Harmer
2.676
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.459
20083026HNSMLK 3
Adder
3.459
200642SENECA#1
50/50
1.721
203975AE1-071-GEN
Solar/Wind Harmer
13.306
941231AE2-117 GEN
Solar/Wind Harmer
1.739
203855AF2-088 C
Solar/Wind Harmer
0.405
965121AG1-377 GEN
Solar/Wind Harmer
3.899
20090526Q36
Solar/Wind Harmer
2.897
203993AD2-133_GEN1
Solar/Wind Harmer
2.897
203961AE2-224 GEN
Solar/Wind Harmer
4.732
20091526CHSTN_FL
Solar/Wind Harmer
1.357
203804AE2-113_GEN
Solar/Wind Harmer
6.227
203850AG1-041 C
Solar/Wind Harmer
1.234
203844AF2-092 C
Solar/Wind Harmer
1.201
20092526R32
Solar/Wind Harmer
1.726
940863AE2-074 GEN
Solar/Wind Harmer
1.639
970555AG2-356 GEN
Solar/Wind Harmer
1.501
203846AF2-130 C
Solar/Wind Harmer
0.396
970663AG2-429 GEN
Solar/Wind Harmer
4.752
970663AG2-429 GEN
Solar/Wind Harmer
0.774
20083926HOMER C3
Adder
48.691
20083826HOMER C2
Adder
45.994
20083726HOMER C1
Adder
45.416
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.158
966771AG1-548 GEN
Solar/Wind Harmer
1.775
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.459
203926AA2-133 GEN
Adder
1.316
20334726NME_Y1-047
Adder
1.11
203813AE2-344_GEN
Solar/Wind Harmer
6.772
970267AG2-176 GEN
Solar/Wind Harmer
8.703
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.083
LGEELTFEXP_LGEE->PJM
CLTF
0.556
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.203
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.764
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.969
TVALTFEXP_TVA->PJM
CLTF
0.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.495
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.533
MECLTFEXP_MEC->PJM
CLTF
1.368
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT31_SRT-SL


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT31_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.32 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:959.88
MW Contribution:1.9
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.208
970643AG2-418 GEN
Solar/Wind Harmer
6.622
238202AE2-262_GEN
Solar/Wind Harmer
6.045
971627AH1-313 GEN
Solar/Wind Harmer
23.703
203854AF2-039 C
Solar/Wind Harmer
0.772
965131AG1-378 GEN
Solar/Wind Harmer
3.597
960051AF2-296 GEN
Solar/Wind Harmer
2.963
203818AF1-086 GEN
Solar/Wind Harmer
3.016
20120126WRREN CT
Adder
6.03
971703AH1-357 GEN
Solar/Wind Harmer
1.9
971707AH1-359 GEN
Solar/Wind Harmer
1.9
970899AG2-561 GEN
Solar/Wind Harmer
1.781
970125AG2-091 GEN
Solar/Wind Harmer
0.512
971419AH1-201 GEN
Solar/Wind Harmer
2.657
971541AH1-268 GEN
Solar/Wind Harmer
2.896
971879AH1-460 GEN
Solar/Wind Harmer
5.479
20334926Z1-069 C
Solar/Wind Harmer
1.712
203841AF2-001_GEN
Solar/Wind Harmer
1.6
20335126GROZ1-110
Adder
1.866
20335226CANZ2-011
Adder
1.813
945751AF1-240 GEN
Solar/Wind Harmer
1.245
20079426CONEMAGH
Adder
0.951
203932AE1-123
Adder
1.406
238219AF1-167 C
Solar/Wind Harmer
0.947
971185AH1-051 GEN
Solar/Wind Harmer
1.598
971355AH1-158 GEN
Solar/Wind Harmer
1.858
203856AF2-165 C
Solar/Wind Harmer
0.782
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20089026BF_G21_K23
Solar/Wind Harmer
0.452
970647AG2-420 GEN
Solar/Wind Harmer
1.296
959441AF2-235 GEN
Solar/Wind Harmer
0.196
941421AE2-139 GEN
Solar/Wind Harmer
1.952
944411AF1-106 GEN
Solar/Wind Harmer
0.143
970335AG2-220 GEN
Solar/Wind Harmer
1.935
971127AH1-005 GEN
Solar/Wind Harmer
1.248
957161AF2-010 GEN
Solar/Wind Harmer
4.803
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203948AG1-140 C
Solar/Wind Harmer
0.162
20084926LAKVU GN
Adder
0.106
20082926HNSMLK 2
Adder
3.5
20083126HNSMLK 4
Adder
3.5
203962AF1-287 GEN
Solar/Wind Harmer
1.165
962511AG1-100 GEN
Solar/Wind Harmer
0.347
972271AH1-720 GEN
Adder
3.751
20328326MANOR_T86
Adder
0.079
202652Y1-033 WT C
Solar/Wind Harmer
0.485
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.224
212507AE2-042_GEN
Solar/Wind Helper
0.784
20081226ALY HYDR
50/50
0.387
20066626SHAWVL 4
50/50
2.277
20066526SHAWVL 3
50/50
2.261
20071526SHAWVL 1
50/50
1.535
216419AE2-001 C
Solar/Wind Harmer
5.683
203952AE2-129 C
Solar/Wind Harmer
1.089
203946AE2-131 C
Solar/Wind Harmer
1.087
962411AG1-090 GEN
Solar/Wind Harmer
17.085
20088626ARWF_N39
Solar/Wind Harmer
3.152
20303426NA_O38_P22
Solar/Wind Harmer
2.552
238217AF1-153 C O1
Solar/Wind Harmer
0.95
203853AF1-134 C O1
Solar/Wind Harmer
0.896
946381AF1-302 GEN
Solar/Wind Harmer
2.584
971441AH1-212 GEN
Solar/Wind Harmer
2.308
972075AH1-587 GEN
Solar/Wind Harmer
22.794
20390526W1-045 C
Solar/Wind Harmer
0.412
203940AF1-140 C
Solar/Wind Harmer
0.538
970305AG2-200 GEN
Solar/Wind Harmer
1.907
972077AH1-588 GEN
Solar/Wind Harmer
22.799
972079AH1-589 GEN
Solar/Wind Harmer
18.778
970715AG2-457 GEN
Solar/Wind Harmer
7.6
203857AF2-221 C
Solar/Wind Harmer
1.279
970123AG2-090 GEN
Solar/Wind Harmer
1.194
20088926STNY CRK
Solar/Wind Harmer
1.026
200642SENECA#1
50/50
1.622
941231AE2-117 GEN
Solar/Wind Harmer
1.585
203855AF2-088 C
Solar/Wind Harmer
0.372
965121AG1-377 GEN
Solar/Wind Harmer
3.597
20090526Q36
Solar/Wind Harmer
2.684
203993AD2-133_GEN1
Solar/Wind Harmer
2.684
203975AE1-071-GEN
Solar/Wind Harmer
4.801
203961AE2-224 GEN
Solar/Wind Harmer
4.461
20091526CHSTN_FL
Solar/Wind Harmer
1.276
203804AE2-113_GEN
Solar/Wind Harmer
5.831
959381AF2-229 GEN
Solar/Wind Harmer
0.8
203850AG1-041 C
Solar/Wind Harmer
1.2
203844AF2-092 C
Solar/Wind Harmer
1.171
20092526R32
Solar/Wind Harmer
1.686
940863AE2-074 GEN
Solar/Wind Harmer
1.552
20087026C_T85_W218
Adder
0.483
20083726HOMER C1
Adder
47.661
20083926HOMER C3
Adder
49.71
20083826HOMER C2
Adder
46.957
203846AF2-130 C
Solar/Wind Harmer
0.393
970663AG2-429 GEN
Solar/Wind Harmer
4.719
970663AG2-429 GEN
Solar/Wind Harmer
0.768
970555AG2-356 GEN
Solar/Wind Harmer
1.352
970677AG2-438 GEN
Solar/Wind Harmer
0.623
966771AG1-548 GEN
Solar/Wind Harmer
9.071
966771AG1-548 GEN
Solar/Wind Harmer
1.758
20084926LAKVU GN
Adder
0.119
20083226HNSMLK 5
Adder
3.5
203926AA2-133 GEN
Adder
1.099
23732901CHBRG_I12
Adder
1.106
959431AF2-234 GEN
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.225
20072226SHAWVL 2
50/50
29.887
20091326SHAW-D
50/50
1.316
20064926PENNTECH
50/50
0.411
200643SENECA#2
50/50
1.513
970643AG2-418 GEN
Solar/Wind Harmer
3.08
238215AE2-248 C
Solar/Wind Harmer
4.671
964391AG1-301 GEN
Solar/Wind Harmer
1.636
203987AE2-118 C
Solar/Wind Harmer
4.892
238206AE2-263_GEN
Solar/Wind Harmer
5.634
972169AH1-667 GEN
Solar/Wind Harmer
3.397
203954AE2-126 C
Solar/Wind Harmer
1.024
957561AF2-050 GEN
Solar/Wind Harmer
7.364
964201AG1-281 GEN
Solar/Wind Harmer
0.848
238183AE2-316 GEN
Solar/Wind Harmer
5.164
20094526CT_V3-030
Solar/Wind Harmer
0.782
20088826HIGHLAND
Solar/Wind Harmer
1.573
970713AG2-456 GEN
Solar/Wind Harmer
7.6
971705AH1-358 GEN
Solar/Wind Harmer
2.209
971709AH1-360 GEN
Solar/Wind Harmer
2.209
971279AH1-102 GEN
Solar/Wind Harmer
6.806
970631AG2-411 GEN
Solar/Wind Harmer
5.192
971423AH1-203 GEN
Solar/Wind Harmer
5.667
203843AF2-002_GEN
Solar/Wind Harmer
0.8
20326126BLOSSBCT
Adder
1.701
203835AF1-098 GEN
Solar/Wind Harmer
1.646
959471AF2-238 GEN
Solar/Wind Harmer
0.409
970337AG2-221 GEN
Solar/Wind Harmer
1.352
971183AH1-050 GEN
Solar/Wind Harmer
2.664
20089226LOOKOUT
Solar/Wind Harmer
0.556
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20335026MILZ1-092
Adder
1.445
944411AF1-106 GEN
Solar/Wind Harmer
1.331
970511AG2-327 GEN
Solar/Wind Harmer
0.623
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.106
20082826HNSMLK 1
Adder
3.5
20083026HNSMLK 3
Adder
3.5
970267AG2-176 GEN
Solar/Wind Harmer
8.732
203813AE2-344_GEN
Solar/Wind Harmer
6.753
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.224
946741AF1-338 GEN
Solar/Wind Helper
0.224
203982AD2-062_GEN
Solar/Wind Harmer
6.895
971427AH1-205 GEN
Solar/Wind Harmer
1.236
20084626FORWARD
Solar/Wind Harmer
0.651
203839AF1-321 GEN
Solar/Wind Harmer
1.6
20083426SW_E13_K22
Solar/Wind Harmer
0.224
946071AF1-272 GEN
Solar/Wind Harmer
2.407
203848AF2-166 C
Solar/Wind Harmer
1.375
20398826ARMNA MT
Solar/Wind Harmer
1.531
944781AF1-143 GEN
Solar/Wind Harmer
1.958
970313AG2-206 GEN
Solar/Wind Harmer
2.989
203979AG1-198 GEN
Solar/Wind Harmer
0.226
971933AH1-491 GEN
Solar/Wind Harmer
1.245
203963AG1-253 GEN
Solar/Wind Harmer
0.247
203980AG1-197 GEN
Solar/Wind Harmer
0.263
203947AF1-006 C
Solar/Wind Harmer
0.323
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203859AF2-294 C
Solar/Wind Harmer
0.938
203955AF1-039 C O1
Solar/Wind Harmer
0.236
209137AF2-361 C
Solar/Wind Helper
1.684
946751AF1-339 GEN
Solar/Wind Helper
0.224
209054AE2-059 GEN
Solar/Wind Helper
0.04
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.786
WECLTFEXP_WEC->PJM
CLTF
0.456
CPLELTFEXP_CPLE->PJM
CLTF
0.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.199
LAGNLTFEXP_LAGN->PJM
CLTF
1.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.779
MECLTFEXP_MEC->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-008_SRT-SL


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-008_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.32 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:959.88
MW Contribution:1.9
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.208
970643AG2-418 GEN
Solar/Wind Harmer
6.622
238202AE2-262_GEN
Solar/Wind Harmer
6.045
971627AH1-313 GEN
Solar/Wind Harmer
23.703
203854AF2-039 C
Solar/Wind Harmer
0.772
965131AG1-378 GEN
Solar/Wind Harmer
3.597
960051AF2-296 GEN
Solar/Wind Harmer
2.963
203818AF1-086 GEN
Solar/Wind Harmer
3.016
20120126WRREN CT
Adder
6.03
971703AH1-357 GEN
Solar/Wind Harmer
1.9
971707AH1-359 GEN
Solar/Wind Harmer
1.9
970899AG2-561 GEN
Solar/Wind Harmer
1.781
970125AG2-091 GEN
Solar/Wind Harmer
0.512
971419AH1-201 GEN
Solar/Wind Harmer
2.657
971541AH1-268 GEN
Solar/Wind Harmer
2.896
971879AH1-460 GEN
Solar/Wind Harmer
5.479
20334926Z1-069 C
Solar/Wind Harmer
1.712
203841AF2-001_GEN
Solar/Wind Harmer
1.6
20335126GROZ1-110
Adder
1.866
20335226CANZ2-011
Adder
1.813
945751AF1-240 GEN
Solar/Wind Harmer
1.245
20079426CONEMAGH
Adder
0.951
203932AE1-123
Adder
1.406
238219AF1-167 C
Solar/Wind Harmer
0.947
971185AH1-051 GEN
Solar/Wind Harmer
1.598
971355AH1-158 GEN
Solar/Wind Harmer
1.858
203856AF2-165 C
Solar/Wind Harmer
0.782
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20089026BF_G21_K23
Solar/Wind Harmer
0.452
970647AG2-420 GEN
Solar/Wind Harmer
1.296
959441AF2-235 GEN
Solar/Wind Harmer
0.196
941421AE2-139 GEN
Solar/Wind Harmer
1.952
944411AF1-106 GEN
Solar/Wind Harmer
0.143
970335AG2-220 GEN
Solar/Wind Harmer
1.935
971127AH1-005 GEN
Solar/Wind Harmer
1.248
957161AF2-010 GEN
Solar/Wind Harmer
4.803
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203948AG1-140 C
Solar/Wind Harmer
0.162
200642SENECA#1
50/50
1.622
941231AE2-117 GEN
Solar/Wind Harmer
1.585
203855AF2-088 C
Solar/Wind Harmer
0.372
965121AG1-377 GEN
Solar/Wind Harmer
3.597
20090526Q36
Solar/Wind Harmer
2.684
203993AD2-133_GEN1
Solar/Wind Harmer
2.684
203975AE1-071-GEN
Solar/Wind Harmer
4.801
203961AE2-224 GEN
Solar/Wind Harmer
4.461
20091526CHSTN_FL
Solar/Wind Harmer
1.276
203804AE2-113_GEN
Solar/Wind Harmer
5.831
959381AF2-229 GEN
Solar/Wind Harmer
0.8
203850AG1-041 C
Solar/Wind Harmer
1.2
203844AF2-092 C
Solar/Wind Harmer
1.171
20092526R32
Solar/Wind Harmer
1.686
940863AE2-074 GEN
Solar/Wind Harmer
1.552
20087026C_T85_W218
Adder
0.483
20083726HOMER C1
Adder
47.661
20083926HOMER C3
Adder
49.71
20083826HOMER C2
Adder
46.957
203846AF2-130 C
Solar/Wind Harmer
0.393
970663AG2-429 GEN
Solar/Wind Harmer
4.719
970663AG2-429 GEN
Solar/Wind Harmer
0.768
970555AG2-356 GEN
Solar/Wind Harmer
1.352
970677AG2-438 GEN
Solar/Wind Harmer
0.623
966771AG1-548 GEN
Solar/Wind Harmer
9.071
966771AG1-548 GEN
Solar/Wind Harmer
1.758
20084926LAKVU GN
Adder
0.119
20083226HNSMLK 5
Adder
3.5
203926AA2-133 GEN
Adder
1.099
23732901CHBRG_I12
Adder
1.106
959431AF2-234 GEN
Solar/Wind Helper
0.45
20072226SHAWVL 2
50/50
29.887
20091326SHAW-D
50/50
1.316
20064926PENNTECH
50/50
0.411
200643SENECA#2
50/50
1.513
970643AG2-418 GEN
Solar/Wind Harmer
3.08
238215AE2-248 C
Solar/Wind Harmer
4.671
964391AG1-301 GEN
Solar/Wind Harmer
1.636
203987AE2-118 C
Solar/Wind Harmer
4.892
238206AE2-263_GEN
Solar/Wind Harmer
5.634
972169AH1-667 GEN
Solar/Wind Harmer
3.397
203954AE2-126 C
Solar/Wind Harmer
1.024
957561AF2-050 GEN
Solar/Wind Harmer
7.364
964201AG1-281 GEN
Solar/Wind Harmer
0.848
238183AE2-316 GEN
Solar/Wind Harmer
5.164
20094526CT_V3-030
Solar/Wind Harmer
0.782
20088826HIGHLAND
Solar/Wind Harmer
1.573
970713AG2-456 GEN
Solar/Wind Harmer
7.6
971705AH1-358 GEN
Solar/Wind Harmer
2.209
971709AH1-360 GEN
Solar/Wind Harmer
2.209
971279AH1-102 GEN
Solar/Wind Harmer
6.806
970631AG2-411 GEN
Solar/Wind Harmer
5.192
971423AH1-203 GEN
Solar/Wind Harmer
5.667
203843AF2-002_GEN
Solar/Wind Harmer
0.8
20326126BLOSSBCT
Adder
1.701
203835AF1-098 GEN
Solar/Wind Harmer
1.646
959471AF2-238 GEN
Solar/Wind Harmer
0.409
970337AG2-221 GEN
Solar/Wind Harmer
1.352
971183AH1-050 GEN
Solar/Wind Harmer
2.664
20089226LOOKOUT
Solar/Wind Harmer
0.556
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20335026MILZ1-092
Adder
1.445
944411AF1-106 GEN
Solar/Wind Harmer
1.331
970511AG2-327 GEN
Solar/Wind Harmer
0.623
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.106
20082826HNSMLK 1
Adder
3.5
20083026HNSMLK 3
Adder
3.5
970267AG2-176 GEN
Solar/Wind Harmer
8.732
203813AE2-344_GEN
Solar/Wind Harmer
6.753
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.224
946741AF1-338 GEN
Solar/Wind Helper
0.224
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.225
20081226ALY HYDR
50/50
0.387
20066626SHAWVL 4
50/50
2.277
20066526SHAWVL 3
50/50
2.261
20071526SHAWVL 1
50/50
1.535
216419AE2-001 C
Solar/Wind Harmer
5.683
203952AE2-129 C
Solar/Wind Harmer
1.089
203946AE2-131 C
Solar/Wind Harmer
1.087
962411AG1-090 GEN
Solar/Wind Harmer
17.085
20088626ARWF_N39
Solar/Wind Harmer
3.152
20303426NA_O38_P22
Solar/Wind Harmer
2.552
238217AF1-153 C O1
Solar/Wind Harmer
0.95
203853AF1-134 C O1
Solar/Wind Harmer
0.896
946381AF1-302 GEN
Solar/Wind Harmer
2.584
971441AH1-212 GEN
Solar/Wind Harmer
2.308
972075AH1-587 GEN
Solar/Wind Harmer
22.794
20390526W1-045 C
Solar/Wind Harmer
0.412
203940AF1-140 C
Solar/Wind Harmer
0.538
970305AG2-200 GEN
Solar/Wind Harmer
1.907
972077AH1-588 GEN
Solar/Wind Harmer
22.799
972079AH1-589 GEN
Solar/Wind Harmer
18.778
970715AG2-457 GEN
Solar/Wind Harmer
7.6
203857AF2-221 C
Solar/Wind Harmer
1.279
970123AG2-090 GEN
Solar/Wind Harmer
1.194
20088926STNY CRK
Solar/Wind Harmer
1.026
203982AD2-062_GEN
Solar/Wind Harmer
6.895
971427AH1-205 GEN
Solar/Wind Harmer
1.236
20084626FORWARD
Solar/Wind Harmer
0.651
203839AF1-321 GEN
Solar/Wind Harmer
1.6
20083426SW_E13_K22
Solar/Wind Harmer
0.224
946071AF1-272 GEN
Solar/Wind Harmer
2.407
203848AF2-166 C
Solar/Wind Harmer
1.375
20398826ARMNA MT
Solar/Wind Harmer
1.531
944781AF1-143 GEN
Solar/Wind Harmer
1.958
970313AG2-206 GEN
Solar/Wind Harmer
2.989
203979AG1-198 GEN
Solar/Wind Harmer
0.226
971933AH1-491 GEN
Solar/Wind Harmer
1.245
203963AG1-253 GEN
Solar/Wind Harmer
0.247
203980AG1-197 GEN
Solar/Wind Harmer
0.263
203947AF1-006 C
Solar/Wind Harmer
0.323
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203859AF2-294 C
Solar/Wind Harmer
0.938
203955AF1-039 C O1
Solar/Wind Harmer
0.236
209137AF2-361 C
Solar/Wind Helper
1.684
946751AF1-339 GEN
Solar/Wind Helper
0.224
209054AE2-059 GEN
Solar/Wind Helper
0.04
20084926LAKVU GN
Adder
0.106
20082926HNSMLK 2
Adder
3.5
20083126HNSMLK 4
Adder
3.5
203962AF1-287 GEN
Solar/Wind Harmer
1.165
962511AG1-100 GEN
Solar/Wind Harmer
0.347
972271AH1-720 GEN
Adder
3.751
20328326MANOR_T86
Adder
0.079
202652Y1-033 WT C
Solar/Wind Harmer
0.485
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.224
212507AE2-042_GEN
Solar/Wind Helper
0.784
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.786
WECLTFEXP_WEC->PJM
CLTF
0.456
CPLELTFEXP_CPLE->PJM
CLTF
0.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.199
LAGNLTFEXP_LAGN->PJM
CLTF
1.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.779
MECLTFEXP_MEC->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-D_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.64 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:955.66
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.55
238202AE2-262_GEN
Solar/Wind Harmer
6.641
971627AH1-313 GEN
Solar/Wind Harmer
26.037
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.895
960051AF2-296 GEN
Solar/Wind Harmer
3.169
203818AF1-086 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
6.339
971703AH1-357 GEN
Solar/Wind Harmer
1.991
971707AH1-359 GEN
Solar/Wind Harmer
1.991
970899AG2-561 GEN
Solar/Wind Harmer
1.805
20335126GROZ1-110
Adder
2.097
20335226CANZ2-011
Adder
2.038
20334926Z1-069 C
Solar/Wind Harmer
1.816
970125AG2-091 GEN
Solar/Wind Harmer
0.515
971419AH1-201 GEN
Solar/Wind Harmer
2.68
971541AH1-268 GEN
Solar/Wind Harmer
2.914
971879AH1-460 GEN
Solar/Wind Harmer
5.495
945751AF1-240 GEN
Solar/Wind Harmer
1.259
203841AF2-001_GEN
Solar/Wind Harmer
1.596
20079426CONEMAGH
Adder
0.951
941421AE2-139 GEN
Solar/Wind Harmer
2.26
203932AE1-123
Adder
1.418
238219AF1-167 C
Solar/Wind Harmer
0.956
970335AG2-220 GEN
Solar/Wind Harmer
2.159
971127AH1-005 GEN
Solar/Wind Harmer
1.393
944411AF1-106 GEN
Solar/Wind Harmer
0.157
972271AH1-720 GEN
Adder
4.387
971185AH1-051 GEN
Solar/Wind Harmer
1.603
971355AH1-158 GEN
Solar/Wind Harmer
1.864
203856AF2-165 C
Solar/Wind Harmer
0.785
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.299
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.445
957161AF2-010 GEN
Solar/Wind Harmer
4.842
203830AF1-094 GEN
Solar/Wind Harmer
0.38
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.454
20083126HNSMLK 4
Adder
3.454
203962AF1-287 GEN
Solar/Wind Harmer
1.167
962511AG1-100 GEN
Solar/Wind Harmer
0.347
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.645
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.49
20066526SHAWVL 3
50/50
2.472
20071526SHAWVL 1
50/50
1.674
20390526W1-045 C
Solar/Wind Harmer
1.791
216419AE2-001 C
Solar/Wind Harmer
6.263
203952AE2-129 C
Solar/Wind Harmer
1.18
203946AE2-131 C
Solar/Wind Harmer
1.178
962411AG1-090 GEN
Solar/Wind Harmer
18.503
20088626ARWF_N39
Solar/Wind Harmer
3.371
20303426NA_O38_P22
Solar/Wind Harmer
2.729
238217AF1-153 C O1
Solar/Wind Harmer
1.027
203853AF1-134 C O1
Solar/Wind Harmer
0.958
946381AF1-302 GEN
Solar/Wind Harmer
2.752
972075AH1-587 GEN
Solar/Wind Harmer
24.224
971441AH1-212 GEN
Solar/Wind Harmer
2.405
203940AF1-140 C
Solar/Wind Harmer
0.558
970305AG2-200 GEN
Solar/Wind Harmer
2.005
972077AH1-588 GEN
Solar/Wind Harmer
23.888
972079AH1-589 GEN
Solar/Wind Harmer
19.675
970715AG2-457 GEN
Solar/Wind Harmer
7.963
203857AF2-221 C
Solar/Wind Harmer
1.288
970123AG2-090 GEN
Solar/Wind Harmer
1.202
20088926STNY CRK
Solar/Wind Harmer
1.035
971427AH1-205 GEN
Solar/Wind Harmer
1.246
20084626FORWARD
Solar/Wind Harmer
0.652
203839AF1-321 GEN
Solar/Wind Harmer
1.596
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.677
970313AG2-206 GEN
Solar/Wind Harmer
3.337
946071AF1-272 GEN
Solar/Wind Harmer
2.307
203848AF2-166 C
Solar/Wind Harmer
1.384
944781AF1-143 GEN
Solar/Wind Harmer
1.929
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.255
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.046
203947AF1-006 C
Solar/Wind Harmer
0.324
203980AG1-197 GEN
Solar/Wind Harmer
0.262
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.408
200642SENECA#1
50/50
1.719
203975AE1-071-GEN
Solar/Wind Harmer
13.299
959381AF2-229 GEN
Solar/Wind Harmer
3.476
941231AE2-117 GEN
Solar/Wind Harmer
1.738
203855AF2-088 C
Solar/Wind Harmer
0.404
965121AG1-377 GEN
Solar/Wind Harmer
3.895
20090526Q36
Solar/Wind Harmer
2.894
203993AD2-133_GEN1
Solar/Wind Harmer
2.894
203961AE2-224 GEN
Solar/Wind Harmer
4.727
20091526CHSTN_FL
Solar/Wind Harmer
1.355
203804AE2-113_GEN
Solar/Wind Harmer
6.221
203850AG1-041 C
Solar/Wind Harmer
1.233
203844AF2-092 C
Solar/Wind Harmer
1.2
20092526R32
Solar/Wind Harmer
1.724
940863AE2-074 GEN
Solar/Wind Harmer
1.637
970555AG2-356 GEN
Solar/Wind Harmer
1.497
203846AF2-130 C
Solar/Wind Harmer
0.395
970663AG2-429 GEN
Solar/Wind Harmer
4.745
970663AG2-429 GEN
Solar/Wind Harmer
0.772
20083926HOMER C3
Adder
48.613
20083826HOMER C2
Adder
45.92
20083726HOMER C1
Adder
45.338
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.147
966771AG1-548 GEN
Solar/Wind Harmer
1.773
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.454
203926AA2-133 GEN
Adder
1.312
20334726NME_Y1-047
Adder
1.105
20072226SHAWVL 2
50/50
32.675
20091326SHAW-D
50/50
1.432
20064926PENNTECH
50/50
0.443
200643SENECA#2
50/50
1.604
970643AG2-418 GEN
Solar/Wind Harmer
4.442
238215AE2-248 C
Solar/Wind Harmer
5.15
964391AG1-301 GEN
Solar/Wind Harmer
1.796
203987AE2-118 C
Solar/Wind Harmer
5.345
238206AE2-263_GEN
Solar/Wind Harmer
6.189
972169AH1-667 GEN
Solar/Wind Harmer
3.696
203954AE2-126 C
Solar/Wind Harmer
1.11
957561AF2-050 GEN
Solar/Wind Harmer
7.804
964201AG1-281 GEN
Solar/Wind Harmer
0.897
238183AE2-316 GEN
Solar/Wind Harmer
5.499
20094526CT_V3-030
Solar/Wind Harmer
0.811
970713AG2-456 GEN
Solar/Wind Harmer
7.963
971705AH1-358 GEN
Solar/Wind Harmer
2.315
971709AH1-360 GEN
Solar/Wind Harmer
2.315
20088826HIGHLAND
Solar/Wind Harmer
1.609
971279AH1-102 GEN
Solar/Wind Harmer
6.847
970631AG2-411 GEN
Solar/Wind Harmer
5.2
971423AH1-203 GEN
Solar/Wind Harmer
5.694
20326126BLOSSBCT
Adder
1.862
203843AF2-002_GEN
Solar/Wind Harmer
0.798
959471AF2-238 GEN
Solar/Wind Harmer
0.453
970337AG2-221 GEN
Solar/Wind Harmer
1.497
970511AG2-327 GEN
Solar/Wind Harmer
0.695
20335026MILZ1-092
Adder
1.583
944411AF1-106 GEN
Solar/Wind Harmer
1.458
203835AF1-098 GEN
Solar/Wind Harmer
1.682
971183AH1-050 GEN
Solar/Wind Harmer
2.672
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.185
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.454
20083026HNSMLK 3
Adder
3.454
203813AE2-344_GEN
Solar/Wind Harmer
6.763
970267AG2-176 GEN
Solar/Wind Harmer
8.692
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.084
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.206
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.814
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.783
LAGNLTFEXP_LAGN->PJM
CLTF
1.32
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.978
TVALTFEXP_TVA->PJM
CLTF
0.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
1.37
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-030_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-030_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:149.64 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:924.75
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.426
20066626SHAWVL 4
50/50
2.494
20066526SHAWVL 3
50/50
2.475
20071526SHAWVL 1
50/50
1.677
216419AE2-001 C
Solar/Wind Harmer
6.27
203952AE2-129 C
Solar/Wind Harmer
1.182
203946AE2-131 C
Solar/Wind Harmer
1.18
962411AG1-090 GEN
Solar/Wind Harmer
18.535
20088626ARWF_N39
Solar/Wind Harmer
3.377
20303426NA_O38_P22
Solar/Wind Harmer
2.734
238217AF1-153 C O1
Solar/Wind Harmer
1.029
203853AF1-134 C O1
Solar/Wind Harmer
0.96
946381AF1-302 GEN
Solar/Wind Harmer
2.758
972075AH1-587 GEN
Solar/Wind Harmer
24.286
971441AH1-212 GEN
Solar/Wind Harmer
2.411
200642SENECA#1
50/50
1.724
941231AE2-117 GEN
Solar/Wind Harmer
1.74
203855AF2-088 C
Solar/Wind Harmer
0.405
965121AG1-377 GEN
Solar/Wind Harmer
3.902
20090526Q36
Solar/Wind Harmer
2.9
203993AD2-133_GEN1
Solar/Wind Harmer
2.9
203961AE2-224 GEN
Solar/Wind Harmer
4.737
20091526CHSTN_FL
Solar/Wind Harmer
1.358
203804AE2-113_GEN
Solar/Wind Harmer
6.236
203850AG1-041 C
Solar/Wind Harmer
1.236
203844AF2-092 C
Solar/Wind Harmer
1.204
20092526R32
Solar/Wind Harmer
1.729
940863AE2-074 GEN
Solar/Wind Harmer
1.642
970555AG2-356 GEN
Solar/Wind Harmer
1.504
203846AF2-130 C
Solar/Wind Harmer
0.397
970663AG2-429 GEN
Solar/Wind Harmer
4.764
970663AG2-429 GEN
Solar/Wind Harmer
0.776
20083926HOMER C3
Adder
48.819
20083826HOMER C2
Adder
46.115
20083726HOMER C1
Adder
45.538
970677AG2-438 GEN
Solar/Wind Harmer
0.63
966771AG1-548 GEN
Solar/Wind Harmer
9.185
203940AF1-140 C
Solar/Wind Harmer
0.559
970305AG2-200 GEN
Solar/Wind Harmer
2.011
972077AH1-588 GEN
Solar/Wind Harmer
23.96
972079AH1-589 GEN
Solar/Wind Harmer
19.735
970715AG2-457 GEN
Solar/Wind Harmer
7.987
203857AF2-221 C
Solar/Wind Harmer
1.292
970123AG2-090 GEN
Solar/Wind Harmer
1.206
20088926STNY CRK
Solar/Wind Harmer
1.038
971427AH1-205 GEN
Solar/Wind Harmer
1.25
20084626FORWARD
Solar/Wind Harmer
0.655
203839AF1-321 GEN
Solar/Wind Harmer
1.602
20083426SW_E13_K22
Solar/Wind Harmer
0.224
20398826ARMNA MT
Solar/Wind Harmer
1.685
970313AG2-206 GEN
Solar/Wind Harmer
3.354
946071AF1-272 GEN
Solar/Wind Harmer
2.316
203848AF2-166 C
Solar/Wind Harmer
1.389
944781AF1-143 GEN
Solar/Wind Harmer
1.935
203979AG1-198 GEN
Solar/Wind Harmer
0.229
971933AH1-491 GEN
Solar/Wind Harmer
1.26
203963AG1-253 GEN
Solar/Wind Harmer
0.252
203859AF2-294 C
Solar/Wind Harmer
1.052
203947AF1-006 C
Solar/Wind Harmer
0.326
203980AG1-197 GEN
Solar/Wind Harmer
0.263
971931AH1-490 GEN
Solar/Wind Harmer
1.154
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.399
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.566
238202AE2-262_GEN
Solar/Wind Harmer
6.65
971627AH1-313 GEN
Solar/Wind Harmer
26.074
203854AF2-039 C
Solar/Wind Harmer
0.841
965131AG1-378 GEN
Solar/Wind Harmer
3.902
960051AF2-296 GEN
Solar/Wind Harmer
3.175
203818AF1-086 GEN
Solar/Wind Harmer
3.168
20120126WRREN CT
Adder
6.357
971703AH1-357 GEN
Solar/Wind Harmer
1.997
971707AH1-359 GEN
Solar/Wind Harmer
1.997
970899AG2-561 GEN
Solar/Wind Harmer
1.811
20335126GROZ1-110
Adder
2.105
20335226CANZ2-011
Adder
2.046
20334926Z1-069 C
Solar/Wind Harmer
1.822
970125AG2-091 GEN
Solar/Wind Harmer
0.517
971419AH1-201 GEN
Solar/Wind Harmer
2.689
971541AH1-268 GEN
Solar/Wind Harmer
2.924
971879AH1-460 GEN
Solar/Wind Harmer
5.514
945751AF1-240 GEN
Solar/Wind Harmer
1.263
203841AF2-001_GEN
Solar/Wind Harmer
1.602
20079426CONEMAGH
Adder
0.955
941421AE2-139 GEN
Solar/Wind Harmer
2.271
203932AE1-123
Adder
1.423
238219AF1-167 C
Solar/Wind Harmer
0.96
970335AG2-220 GEN
Solar/Wind Harmer
2.169
971127AH1-005 GEN
Solar/Wind Harmer
1.4
944411AF1-106 GEN
Solar/Wind Harmer
0.158
972271AH1-720 GEN
Adder
4.411
971185AH1-051 GEN
Solar/Wind Harmer
1.61
971355AH1-158 GEN
Solar/Wind Harmer
1.872
203856AF2-165 C
Solar/Wind Harmer
0.788
959441AF2-235 GEN
Solar/Wind Harmer
0.198
970647AG2-420 GEN
Solar/Wind Harmer
1.304
20328326MANOR_T86
Adder
0.093
20089126CSLMN_L13
Solar/Wind Harmer
0.565
20089026BF_G21_K23
Solar/Wind Harmer
0.447
957161AF2-010 GEN
Solar/Wind Harmer
4.862
203830AF1-094 GEN
Solar/Wind Harmer
0.382
203948AG1-140 C
Solar/Wind Harmer
0.165
20084926LAKVU GN
Adder
0.108
20082926HNSMLK 2
Adder
3.47
20083126HNSMLK 4
Adder
3.47
203962AF1-287 GEN
Solar/Wind Harmer
1.172
962511AG1-100 GEN
Solar/Wind Harmer
0.349
202652Y1-033 WT C
Solar/Wind Harmer
0.469
200917MEHOOPANY_G
Solar/Wind Harmer
1.659
966771AG1-548 GEN
Solar/Wind Harmer
1.78
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.47
203926AA2-133 GEN
Adder
1.32
20334726NME_Y1-047
Adder
1.114
20072226SHAWVL 2
50/50
32.726
20091326SHAW-D
50/50
1.435
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.608
970643AG2-418 GEN
Solar/Wind Harmer
4.449
238215AE2-248 C
Solar/Wind Harmer
5.157
964391AG1-301 GEN
Solar/Wind Harmer
1.799
203987AE2-118 C
Solar/Wind Harmer
5.352
238206AE2-263_GEN
Solar/Wind Harmer
6.198
972169AH1-667 GEN
Solar/Wind Harmer
3.702
203954AE2-126 C
Solar/Wind Harmer
1.112
957561AF2-050 GEN
Solar/Wind Harmer
7.821
964201AG1-281 GEN
Solar/Wind Harmer
0.899
238183AE2-316 GEN
Solar/Wind Harmer
5.512
20094526CT_V3-030
Solar/Wind Harmer
0.813
970713AG2-456 GEN
Solar/Wind Harmer
7.987
971705AH1-358 GEN
Solar/Wind Harmer
2.322
971709AH1-360 GEN
Solar/Wind Harmer
2.322
20088826HIGHLAND
Solar/Wind Harmer
1.614
971279AH1-102 GEN
Solar/Wind Harmer
6.871
970631AG2-411 GEN
Solar/Wind Harmer
5.218
20326126BLOSSBCT
Adder
1.87
971423AH1-203 GEN
Solar/Wind Harmer
5.712
203843AF2-002_GEN
Solar/Wind Harmer
0.801
959471AF2-238 GEN
Solar/Wind Harmer
0.455
970337AG2-221 GEN
Solar/Wind Harmer
1.504
970511AG2-327 GEN
Solar/Wind Harmer
0.699
20335026MILZ1-092
Adder
1.59
944411AF1-106 GEN
Solar/Wind Harmer
1.465
203835AF1-098 GEN
Solar/Wind Harmer
1.688
971183AH1-050 GEN
Solar/Wind Harmer
2.683
970647AG2-420 GEN
Solar/Wind Harmer
0.152
20089226LOOKOUT
Solar/Wind Harmer
0.55
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.108
20082826HNSMLK 1
Adder
3.47
20083026HNSMLK 3
Adder
3.47
203813AE2-344_GEN
Solar/Wind Harmer
6.793
970267AG2-176 GEN
Solar/Wind Harmer
8.73
961971AG1-040 GEN
Solar/Wind Harmer
0.351
209067AE2-060 GEN
Solar/Wind Helper
0.083
LGEELTFEXP_LGEE->PJM
CLTF
0.569
WECLTFEXP_WEC->PJM
CLTF
0.335
CPLELTFEXP_CPLE->PJM
CLTF
0.223
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.353
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.024
TVALTFEXP_TVA->PJM
CLTF
0.663
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.758
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.602
MECLTFEXP_MEC->PJM
CLTF
1.398
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-031_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-031_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:144.8 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:894.87
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.416
20066626SHAWVL 4
50/50
2.438
20066526SHAWVL 3
50/50
2.42
20071526SHAWVL 1
50/50
1.64
216419AE2-001 C
Solar/Wind Harmer
6.134
203952AE2-129 C
Solar/Wind Harmer
1.154
203946AE2-131 C
Solar/Wind Harmer
1.152
962411AG1-090 GEN
Solar/Wind Harmer
18.107
20088626ARWF_N39
Solar/Wind Harmer
3.299
20303426NA_O38_P22
Solar/Wind Harmer
2.671
238217AF1-153 C O1
Solar/Wind Harmer
1.006
203853AF1-134 C O1
Solar/Wind Harmer
0.938
946381AF1-302 GEN
Solar/Wind Harmer
2.695
972075AH1-587 GEN
Solar/Wind Harmer
23.718
971441AH1-212 GEN
Solar/Wind Harmer
2.353
203940AF1-140 C
Solar/Wind Harmer
0.546
970305AG2-200 GEN
Solar/Wind Harmer
1.965
972077AH1-588 GEN
Solar/Wind Harmer
23.389
972079AH1-589 GEN
Solar/Wind Harmer
19.264
970715AG2-457 GEN
Solar/Wind Harmer
7.796
203857AF2-221 C
Solar/Wind Harmer
1.26
970123AG2-090 GEN
Solar/Wind Harmer
1.176
20088926STNY CRK
Solar/Wind Harmer
1.013
971427AH1-205 GEN
Solar/Wind Harmer
1.221
20084626FORWARD
Solar/Wind Harmer
0.639
203839AF1-321 GEN
Solar/Wind Harmer
1.562
20083426SW_E13_K22
Solar/Wind Harmer
0.218
20398826ARMNA MT
Solar/Wind Harmer
1.637
946071AF1-272 GEN
Solar/Wind Harmer
2.258
970313AG2-206 GEN
Solar/Wind Harmer
3.257
203848AF2-166 C
Solar/Wind Harmer
1.356
944781AF1-143 GEN
Solar/Wind Harmer
1.893
203979AG1-198 GEN
Solar/Wind Harmer
0.224
971933AH1-491 GEN
Solar/Wind Harmer
1.231
203963AG1-253 GEN
Solar/Wind Harmer
0.246
203859AF2-294 C
Solar/Wind Harmer
1.02
203947AF1-006 C
Solar/Wind Harmer
0.318
203980AG1-197 GEN
Solar/Wind Harmer
0.257
971931AH1-490 GEN
Solar/Wind Harmer
1.128
203955AF1-039 C O1
Solar/Wind Harmer
0.224
209137AF2-361 C
Solar/Wind Helper
1.43
200642SENECA#1
50/50
1.684
941231AE2-117 GEN
Solar/Wind Harmer
1.693
203855AF2-088 C
Solar/Wind Harmer
0.396
965121AG1-377 GEN
Solar/Wind Harmer
3.812
20090526Q36
Solar/Wind Harmer
2.831
203993AD2-133_GEN1
Solar/Wind Harmer
2.831
203961AE2-224 GEN
Solar/Wind Harmer
4.626
20091526CHSTN_FL
Solar/Wind Harmer
1.326
203804AE2-113_GEN
Solar/Wind Harmer
6.091
203850AG1-041 C
Solar/Wind Harmer
1.206
203844AF2-092 C
Solar/Wind Harmer
1.174
20092526R32
Solar/Wind Harmer
1.687
940863AE2-074 GEN
Solar/Wind Harmer
1.602
970555AG2-356 GEN
Solar/Wind Harmer
1.462
203846AF2-130 C
Solar/Wind Harmer
0.387
970663AG2-429 GEN
Solar/Wind Harmer
4.65
970663AG2-429 GEN
Solar/Wind Harmer
0.757
20083926HOMER C3
Adder
47.576
20083826HOMER C2
Adder
44.941
20083726HOMER C1
Adder
44.35
970677AG2-438 GEN
Solar/Wind Harmer
0.616
966771AG1-548 GEN
Solar/Wind Harmer
8.972
966771AG1-548 GEN
Solar/Wind Harmer
1.739
20084926LAKVU GN
Adder
0.118
20083226HNSMLK 5
Adder
3.386
203926AA2-133 GEN
Adder
1.277
20334726NME_Y1-047
Adder
1.074
200644SENECA#3
50/50
0.216
238202AE2-262_GEN
Solar/Wind Harmer
6.504
971627AH1-313 GEN
Solar/Wind Harmer
25.5
203854AF2-039 C
Solar/Wind Harmer
0.822
965131AG1-378 GEN
Solar/Wind Harmer
3.812
960051AF2-296 GEN
Solar/Wind Harmer
3.103
203818AF1-086 GEN
Solar/Wind Harmer
3.094
20120126WRREN CT
Adder
6.211
971703AH1-357 GEN
Solar/Wind Harmer
1.949
971707AH1-359 GEN
Solar/Wind Harmer
1.949
970899AG2-561 GEN
Solar/Wind Harmer
1.767
20335126GROZ1-110
Adder
2.048
20335226CANZ2-011
Adder
1.991
20334926Z1-069 C
Solar/Wind Harmer
1.776
970125AG2-091 GEN
Solar/Wind Harmer
0.504
971419AH1-201 GEN
Solar/Wind Harmer
2.624
971541AH1-268 GEN
Solar/Wind Harmer
2.852
971879AH1-460 GEN
Solar/Wind Harmer
5.378
945751AF1-240 GEN
Solar/Wind Harmer
1.233
203841AF2-001_GEN
Solar/Wind Harmer
1.562
20079426CONEMAGH
Adder
0.931
941421AE2-139 GEN
Solar/Wind Harmer
2.204
203932AE1-123
Adder
1.389
238219AF1-167 C
Solar/Wind Harmer
0.937
970335AG2-220 GEN
Solar/Wind Harmer
2.107
971127AH1-005 GEN
Solar/Wind Harmer
1.359
944411AF1-106 GEN
Solar/Wind Harmer
0.153
972271AH1-720 GEN
Adder
4.276
971185AH1-051 GEN
Solar/Wind Harmer
1.571
971355AH1-158 GEN
Solar/Wind Harmer
1.827
203856AF2-165 C
Solar/Wind Harmer
0.77
959441AF2-235 GEN
Solar/Wind Harmer
0.193
970647AG2-420 GEN
Solar/Wind Harmer
1.273
20328326MANOR_T86
Adder
0.09
20089126CSLMN_L13
Solar/Wind Harmer
0.552
20089026BF_G21_K23
Solar/Wind Harmer
0.437
957161AF2-010 GEN
Solar/Wind Harmer
4.749
203830AF1-094 GEN
Solar/Wind Harmer
0.373
203948AG1-140 C
Solar/Wind Harmer
0.161
20084926LAKVU GN
Adder
0.105
20082926HNSMLK 2
Adder
3.386
20083126HNSMLK 4
Adder
3.386
203962AF1-287 GEN
Solar/Wind Harmer
1.145
962511AG1-100 GEN
Solar/Wind Harmer
0.341
202652Y1-033 WT C
Solar/Wind Harmer
0.46
200917MEHOOPANY_G
Solar/Wind Harmer
1.599
970643AG2-418 GEN
Solar/Wind Harmer
0.876
20072226SHAWVL 2
50/50
31.998
20091326SHAW-D
50/50
1.402
20064926PENNTECH
50/50
0.434
200643SENECA#2
50/50
1.571
238215AE2-248 C
Solar/Wind Harmer
5.045
964391AG1-301 GEN
Solar/Wind Harmer
1.749
203987AE2-118 C
Solar/Wind Harmer
5.213
238206AE2-263_GEN
Solar/Wind Harmer
6.062
972169AH1-667 GEN
Solar/Wind Harmer
3.619
203954AE2-126 C
Solar/Wind Harmer
1.087
957561AF2-050 GEN
Solar/Wind Harmer
7.637
964201AG1-281 GEN
Solar/Wind Harmer
0.878
238183AE2-316 GEN
Solar/Wind Harmer
5.386
20094526CT_V3-030
Solar/Wind Harmer
0.794
970713AG2-456 GEN
Solar/Wind Harmer
7.796
971705AH1-358 GEN
Solar/Wind Harmer
2.266
971709AH1-360 GEN
Solar/Wind Harmer
2.266
20088826HIGHLAND
Solar/Wind Harmer
1.574
971279AH1-102 GEN
Solar/Wind Harmer
6.701
970631AG2-411 GEN
Solar/Wind Harmer
5.09
971423AH1-203 GEN
Solar/Wind Harmer
5.576
20326126BLOSSBCT
Adder
1.819
203843AF2-002_GEN
Solar/Wind Harmer
0.781
959471AF2-238 GEN
Solar/Wind Harmer
0.442
970337AG2-221 GEN
Solar/Wind Harmer
1.462
203835AF1-098 GEN
Solar/Wind Harmer
1.65
970511AG2-327 GEN
Solar/Wind Harmer
0.679
20335026MILZ1-092
Adder
1.546
944411AF1-106 GEN
Solar/Wind Harmer
1.424
971183AH1-050 GEN
Solar/Wind Harmer
2.619
970647AG2-420 GEN
Solar/Wind Harmer
0.148
20089226LOOKOUT
Solar/Wind Harmer
0.538
203860AG1-193 C
Solar/Wind Harmer
0.182
20084926LAKVU GN
Adder
0.105
20082826HNSMLK 1
Adder
3.386
20083026HNSMLK 3
Adder
3.386
203813AE2-344_GEN
Solar/Wind Harmer
6.636
970267AG2-176 GEN
Solar/Wind Harmer
8.526
961971AG1-040 GEN
Solar/Wind Harmer
0.343
970643AG2-418 GEN
Solar/Wind Harmer
0.407
209067AE2-060 GEN
Solar/Wind Helper
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.574
WECLTFEXP_WEC->PJM
CLTF
0.337
CPLELTFEXP_CPLE->PJM
CLTF
0.259
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.153
LAGNLTFEXP_LAGN->PJM
CLTF
1.381
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.108
TVALTFEXP_TVA->PJM
CLTF
0.678
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.801
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.652
MECLTFEXP_MEC->PJM
CLTF
1.41
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:142.79 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:882.46
MW Contribution:2.01
Bus #Bus NameTypeMW Contribution
20050326C.SLOPE
50/50
0.379
941231AE2-117 GEN
Solar/Wind Harmer
1.659
203855AF2-088 C
Solar/Wind Harmer
0.387
965121AG1-377 GEN
Solar/Wind Harmer
3.79
20090526Q36
Solar/Wind Harmer
2.856
203993AD2-133_GEN1
Solar/Wind Harmer
2.856
203975AE1-071-GEN
Solar/Wind Harmer
4.947
203961AE2-224 GEN
Solar/Wind Harmer
4.956
20091526CHSTN_FL
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
6.118
203850AG1-041 C
Solar/Wind Harmer
1.366
959381AF2-229 GEN
Solar/Wind Harmer
0.831
20092526R32
Solar/Wind Harmer
1.947
203844AF2-092 C
Solar/Wind Harmer
1.335
940863AE2-074 GEN
Solar/Wind Harmer
1.655
20087026C_T85_W218
Adder
0.509
20083726HOMER C1
Adder
53.523
20083926HOMER C3
Adder
54.511
20083826HOMER C2
Adder
51.492
970555AG2-356 GEN
Solar/Wind Harmer
1.486
203846AF2-130 C
Solar/Wind Harmer
0.411
970663AG2-429 GEN
Solar/Wind Harmer
4.882
970663AG2-429 GEN
Solar/Wind Harmer
0.795
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.367
966771AG1-548 GEN
Solar/Wind Harmer
1.815
20083226HNSMLK 5
Adder
3.672
20084926LAKVU GN
Adder
0.123
203926AA2-133 GEN
Adder
1.263
23732901CHBRG_I12
Adder
1.154
20334726NME_Y1-047
Adder
1.055
20081226ALY HYDR
50/50
0.403
20066626SHAWVL 4
50/50
2.36
20066526SHAWVL 3
50/50
2.343
20071526SHAWVL 1
50/50
1.595
216419AE2-001 C
Solar/Wind Harmer
5.846
203952AE2-129 C
Solar/Wind Harmer
1.148
203946AE2-131 C
Solar/Wind Harmer
1.146
962411AG1-090 GEN
Solar/Wind Harmer
18.003
20088626ARWF_N39
Solar/Wind Harmer
3.448
20303426NA_O38_P22
Solar/Wind Harmer
2.791
238217AF1-153 C O1
Solar/Wind Harmer
0.985
203853AF1-134 C O1
Solar/Wind Harmer
0.947
971441AH1-212 GEN
Solar/Wind Harmer
2.601
946381AF1-302 GEN
Solar/Wind Harmer
2.679
203940AF1-140 C
Solar/Wind Harmer
0.609
972075AH1-587 GEN
Solar/Wind Harmer
23.976
20390526W1-045 C
Solar/Wind Harmer
0.428
972077AH1-588 GEN
Solar/Wind Harmer
24.128
972079AH1-589 GEN
Solar/Wind Harmer
19.873
970715AG2-457 GEN
Solar/Wind Harmer
8.043
203857AF2-221 C
Solar/Wind Harmer
1.495
970123AG2-090 GEN
Solar/Wind Harmer
1.395
970305AG2-200 GEN
Solar/Wind Harmer
1.987
20088926STNY CRK
Solar/Wind Harmer
1.18
971427AH1-205 GEN
Solar/Wind Harmer
1.421
20084626FORWARD
Solar/Wind Harmer
0.756
203839AF1-321 GEN
Solar/Wind Harmer
1.865
203982AD2-062_GEN
Solar/Wind Harmer
7.157
20083426SW_E13_K22
Solar/Wind Harmer
0.259
946071AF1-272 GEN
Solar/Wind Harmer
2.555
944781AF1-143 GEN
Solar/Wind Harmer
2.249
20398826ARMNA MT
Solar/Wind Harmer
1.685
203848AF2-166 C
Solar/Wind Harmer
1.437
970313AG2-206 GEN
Solar/Wind Harmer
3.31
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
203963AG1-253 GEN
Solar/Wind Harmer
0.255
203859AF2-294 C
Solar/Wind Harmer
1.049
203980AG1-197 GEN
Solar/Wind Harmer
0.271
203947AF1-006 C
Solar/Wind Harmer
0.331
971931AH1-490 GEN
Solar/Wind Harmer
1.182
203955AF1-039 C O1
Solar/Wind Harmer
0.267
209137AF2-361 C
Solar/Wind Helper
1.538
970643AG2-418 GEN
Solar/Wind Harmer
6.781
238202AE2-262_GEN
Solar/Wind Harmer
6.24
971627AH1-313 GEN
Solar/Wind Harmer
24.467
203854AF2-039 C
Solar/Wind Harmer
0.804
965131AG1-378 GEN
Solar/Wind Harmer
3.79
960051AF2-296 GEN
Solar/Wind Harmer
3.134
203818AF1-086 GEN
Solar/Wind Harmer
3.247
971703AH1-357 GEN
Solar/Wind Harmer
2.011
971707AH1-359 GEN
Solar/Wind Harmer
2.011
970125AG2-091 GEN
Solar/Wind Harmer
0.598
20120126WRREN CT
Adder
6.281
970899AG2-561 GEN
Solar/Wind Harmer
1.963
971879AH1-460 GEN
Solar/Wind Harmer
6.395
971541AH1-268 GEN
Solar/Wind Harmer
3.363
971419AH1-201 GEN
Solar/Wind Harmer
3.056
20079426CONEMAGH
Adder
1.155
203841AF2-001_GEN
Solar/Wind Harmer
1.865
20334926Z1-069 C
Solar/Wind Harmer
1.839
20335126GROZ1-110
Adder
2.027
20335226CANZ2-011
Adder
1.97
945751AF1-240 GEN
Solar/Wind Harmer
1.338
203932AE1-123
Adder
1.472
20089126CSLMN_L13
Solar/Wind Harmer
0.656
20089026BF_G21_K23
Solar/Wind Harmer
0.519
238219AF1-167 C
Solar/Wind Harmer
0.976
941421AE2-139 GEN
Solar/Wind Harmer
2.164
944411AF1-106 GEN
Solar/Wind Harmer
0.158
970335AG2-220 GEN
Solar/Wind Harmer
2.142
971127AH1-005 GEN
Solar/Wind Harmer
1.382
971185AH1-051 GEN
Solar/Wind Harmer
1.668
971355AH1-158 GEN
Solar/Wind Harmer
1.939
203856AF2-165 C
Solar/Wind Harmer
0.816
970647AG2-420 GEN
Solar/Wind Harmer
1.351
959441AF2-235 GEN
Solar/Wind Harmer
0.204
957161AF2-010 GEN
Solar/Wind Harmer
4.964
203830AF1-094 GEN
Solar/Wind Harmer
0.39
972271AH1-720 GEN
Adder
4.21
203948AG1-140 C
Solar/Wind Harmer
0.167
20082926HNSMLK 2
Adder
3.672
20083126HNSMLK 4
Adder
3.672
20328326MANOR_T86
Adder
0.089
20084926LAKVU GN
Adder
0.109
203962AF1-287 GEN
Solar/Wind Harmer
1.198
962511AG1-100 GEN
Solar/Wind Harmer
0.357
202652Y1-033 WT C
Solar/Wind Harmer
0.549
200917MEHOOPANY_G
Solar/Wind Harmer
1.57
20072226SHAWVL 2
50/50
30.97
20091326SHAW-D
50/50
1.372
20064926PENNTECH
50/50
0.428
970643AG2-418 GEN
Solar/Wind Harmer
3.154
238215AE2-248 C
Solar/Wind Harmer
4.803
964391AG1-301 GEN
Solar/Wind Harmer
1.711
203987AE2-118 C
Solar/Wind Harmer
5.15
238206AE2-263_GEN
Solar/Wind Harmer
5.816
972169AH1-667 GEN
Solar/Wind Harmer
3.54
203954AE2-126 C
Solar/Wind Harmer
1.067
957561AF2-050 GEN
Solar/Wind Harmer
8.182
964201AG1-281 GEN
Solar/Wind Harmer
0.934
238183AE2-316 GEN
Solar/Wind Harmer
5.355
20094526CT_V3-030
Solar/Wind Harmer
0.867
20088826HIGHLAND
Solar/Wind Harmer
1.817
970713AG2-456 GEN
Solar/Wind Harmer
8.043
971705AH1-358 GEN
Solar/Wind Harmer
2.338
971709AH1-360 GEN
Solar/Wind Harmer
2.338
971279AH1-102 GEN
Solar/Wind Harmer
7.901
970631AG2-411 GEN
Solar/Wind Harmer
6.024
971423AH1-203 GEN
Solar/Wind Harmer
6.528
203843AF2-002_GEN
Solar/Wind Harmer
0.933
20326126BLOSSBCT
Adder
1.852
20089226LOOKOUT
Solar/Wind Harmer
0.639
959471AF2-238 GEN
Solar/Wind Harmer
0.449
970337AG2-221 GEN
Solar/Wind Harmer
1.486
203835AF1-098 GEN
Solar/Wind Harmer
1.7
20335026MILZ1-092
Adder
1.592
944411AF1-106 GEN
Solar/Wind Harmer
1.467
970511AG2-327 GEN
Solar/Wind Harmer
0.69
971183AH1-050 GEN
Solar/Wind Harmer
2.779
970647AG2-420 GEN
Solar/Wind Harmer
0.157
203860AG1-193 C
Solar/Wind Harmer
0.194
20082826HNSMLK 1
Adder
3.672
20083026HNSMLK 3
Adder
3.672
20084926LAKVU GN
Adder
0.109
970267AG2-176 GEN
Solar/Wind Harmer
9.037
961971AG1-040 GEN
Solar/Wind Harmer
0.361
203813AE2-344_GEN
Solar/Wind Harmer
6.947
209067AE2-060 GEN
Solar/Wind Helper
0.091
LGEELTFEXP_LGEE->PJM
CLTF
0.626
WECLTFEXP_WEC->PJM
CLTF
0.365
CPLELTFEXP_CPLE->PJM
CLTF
0.386
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.244
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.43
TVALTFEXP_TVA->PJM
CLTF
0.765
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.048

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-074_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-074_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.41 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:843.02
MW Contribution:1.83
Bus #Bus NameTypeMW Contribution
20087026C_T85_W218
50/50
0.852
200642SENECA#1
50/50
1.586
941231AE2-117 GEN
Solar/Wind Harmer
1.604
203975AE1-071-GEN
Solar/Wind Harmer
6.398
203855AF2-088 C
Solar/Wind Harmer
0.374
965121AG1-377 GEN
Solar/Wind Harmer
3.599
959381AF2-229 GEN
Solar/Wind Harmer
1.268
20081226ALY HYDR
50/50
0.393
20066626SHAWVL 4
50/50
2.302
20066526SHAWVL 3
50/50
2.285
20071526SHAWVL 1
50/50
1.548
216419AE2-001 C
Solar/Wind Harmer
5.796
203952AE2-129 C
Solar/Wind Harmer
1.09
203946AE2-131 C
Solar/Wind Harmer
1.088
962411AG1-090 GEN
Solar/Wind Harmer
17.095
20390526W1-045 C
Solar/Wind Harmer
0.653
203982AD2-062_GEN
Solar/Wind Harmer
14.042
20088626ARWF_N39
Solar/Wind Harmer
3.113
20303426NA_O38_P22
Solar/Wind Harmer
2.52
238217AF1-153 C O1
Solar/Wind Harmer
0.949
203853AF1-134 C O1
Solar/Wind Harmer
0.885
946381AF1-302 GEN
Solar/Wind Harmer
2.541
972075AH1-587 GEN
Solar/Wind Harmer
22.338
971441AH1-212 GEN
Solar/Wind Harmer
2.217
203940AF1-140 C
Solar/Wind Harmer
0.514
970305AG2-200 GEN
Solar/Wind Harmer
1.851
972077AH1-588 GEN
Solar/Wind Harmer
22.004
972079AH1-589 GEN
Solar/Wind Harmer
18.124
970715AG2-457 GEN
Solar/Wind Harmer
7.335
203857AF2-221 C
Solar/Wind Harmer
1.185
970123AG2-090 GEN
Solar/Wind Harmer
1.106
20088926STNY CRK
Solar/Wind Harmer
0.954
971427AH1-205 GEN
Solar/Wind Harmer
1.149
20084626FORWARD
Solar/Wind Harmer
0.601
203839AF1-321 GEN
Solar/Wind Harmer
1.469
20083426SW_E13_K22
Solar/Wind Harmer
0.206
20398826ARMNA MT
Solar/Wind Harmer
1.528
203848AF2-166 C
Solar/Wind Harmer
1.275
946071AF1-272 GEN
Solar/Wind Harmer
2.118
970313AG2-206 GEN
Solar/Wind Harmer
3.036
944781AF1-143 GEN
Solar/Wind Harmer
1.786
203979AG1-198 GEN
Solar/Wind Harmer
0.211
971933AH1-491 GEN
Solar/Wind Harmer
1.158
203963AG1-253 GEN
Solar/Wind Harmer
0.231
203859AF2-294 C
Solar/Wind Harmer
0.949
203947AF1-006 C
Solar/Wind Harmer
0.3
203980AG1-197 GEN
Solar/Wind Harmer
0.242
971931AH1-490 GEN
Solar/Wind Harmer
1.061
203955AF1-039 C O1
Solar/Wind Harmer
0.212
209137AF2-361 C
Solar/Wind Helper
1.486
20090526Q36
Solar/Wind Harmer
2.673
203993AD2-133_GEN1
Solar/Wind Harmer
2.673
203961AE2-224 GEN
Solar/Wind Harmer
4.362
20091526CHSTN_FL
Solar/Wind Harmer
1.251
203804AE2-113_GEN
Solar/Wind Harmer
5.739
203850AG1-041 C
Solar/Wind Harmer
1.136
203844AF2-092 C
Solar/Wind Harmer
1.106
20092526R32
Solar/Wind Harmer
1.588
940863AE2-074 GEN
Solar/Wind Harmer
1.505
970555AG2-356 GEN
Solar/Wind Harmer
1.365
203846AF2-130 C
Solar/Wind Harmer
0.364
970663AG2-429 GEN
Solar/Wind Harmer
4.371
970663AG2-429 GEN
Solar/Wind Harmer
0.711
20083926HOMER C3
Adder
44.619
20083826HOMER C2
Adder
42.148
20083726HOMER C1
Adder
41.558
970677AG2-438 GEN
Solar/Wind Harmer
0.579
966771AG1-548 GEN
Solar/Wind Harmer
8.442
966771AG1-548 GEN
Solar/Wind Harmer
1.636
20084926LAKVU GN
Adder
0.111
20083226HNSMLK 5
Adder
3.182
203926AA2-133 GEN
Adder
1.181
200644SENECA#3
50/50
0.204
970643AG2-418 GEN
Solar/Wind Harmer
7.207
238202AE2-262_GEN
Solar/Wind Harmer
6.142
971627AH1-313 GEN
Solar/Wind Harmer
24.082
203854AF2-039 C
Solar/Wind Harmer
0.776
965131AG1-378 GEN
Solar/Wind Harmer
3.599
960051AF2-296 GEN
Solar/Wind Harmer
2.926
203818AF1-086 GEN
Solar/Wind Harmer
2.915
20120126WRREN CT
Adder
5.851
971703AH1-357 GEN
Solar/Wind Harmer
1.834
971707AH1-359 GEN
Solar/Wind Harmer
1.834
970899AG2-561 GEN
Solar/Wind Harmer
1.662
20335126GROZ1-110
Adder
1.915
20335226CANZ2-011
Adder
1.862
20334926Z1-069 C
Solar/Wind Harmer
1.666
970125AG2-091 GEN
Solar/Wind Harmer
0.474
971419AH1-201 GEN
Solar/Wind Harmer
2.471
971541AH1-268 GEN
Solar/Wind Harmer
2.68
971879AH1-460 GEN
Solar/Wind Harmer
5.058
945751AF1-240 GEN
Solar/Wind Harmer
1.16
203841AF2-001_GEN
Solar/Wind Harmer
1.469
20079426CONEMAGH
Adder
0.874
941421AE2-139 GEN
Solar/Wind Harmer
2.052
203932AE1-123
Adder
1.306
238219AF1-167 C
Solar/Wind Harmer
0.881
970335AG2-220 GEN
Solar/Wind Harmer
1.964
971127AH1-005 GEN
Solar/Wind Harmer
1.267
944411AF1-106 GEN
Solar/Wind Harmer
0.143
971185AH1-051 GEN
Solar/Wind Harmer
1.478
971355AH1-158 GEN
Solar/Wind Harmer
1.718
203856AF2-165 C
Solar/Wind Harmer
0.724
972271AH1-720 GEN
Adder
3.972
959441AF2-235 GEN
Solar/Wind Harmer
0.182
970647AG2-420 GEN
Solar/Wind Harmer
1.197
20089126CSLMN_L13
Solar/Wind Harmer
0.521
20089026BF_G21_K23
Solar/Wind Harmer
0.412
20328326MANOR_T86
Adder
0.083
957161AF2-010 GEN
Solar/Wind Harmer
4.468
203830AF1-094 GEN
Solar/Wind Harmer
0.351
203948AG1-140 C
Solar/Wind Harmer
0.152
20084926LAKVU GN
Adder
0.099
20082926HNSMLK 2
Adder
3.182
20083126HNSMLK 4
Adder
3.182
203962AF1-287 GEN
Solar/Wind Harmer
1.077
962511AG1-100 GEN
Solar/Wind Harmer
0.321
202652Y1-033 WT C
Solar/Wind Harmer
0.436
20072226SHAWVL 2
50/50
30.209
20091326SHAW-D
50/50
1.324
20064926PENNTECH
50/50
0.409
200643SENECA#2
50/50
1.48
970643AG2-418 GEN
Solar/Wind Harmer
3.352
238215AE2-248 C
Solar/Wind Harmer
4.767
964391AG1-301 GEN
Solar/Wind Harmer
1.658
203987AE2-118 C
Solar/Wind Harmer
4.936
238206AE2-263_GEN
Solar/Wind Harmer
5.725
972169AH1-667 GEN
Solar/Wind Harmer
3.416
203954AE2-126 C
Solar/Wind Harmer
1.026
957561AF2-050 GEN
Solar/Wind Harmer
7.202
964201AG1-281 GEN
Solar/Wind Harmer
0.828
238183AE2-316 GEN
Solar/Wind Harmer
5.077
20094526CT_V3-030
Solar/Wind Harmer
0.748
970713AG2-456 GEN
Solar/Wind Harmer
7.335
971705AH1-358 GEN
Solar/Wind Harmer
2.132
971709AH1-360 GEN
Solar/Wind Harmer
2.132
20088826HIGHLAND
Solar/Wind Harmer
1.482
971279AH1-102 GEN
Solar/Wind Harmer
6.298
970631AG2-411 GEN
Solar/Wind Harmer
4.787
971423AH1-203 GEN
Solar/Wind Harmer
5.251
20326126BLOSSBCT
Adder
1.702
203843AF2-002_GEN
Solar/Wind Harmer
0.735
959471AF2-238 GEN
Solar/Wind Harmer
0.413
970337AG2-221 GEN
Solar/Wind Harmer
1.365
203835AF1-098 GEN
Solar/Wind Harmer
1.553
20335026MILZ1-092
Adder
1.442
944411AF1-106 GEN
Solar/Wind Harmer
1.329
970511AG2-327 GEN
Solar/Wind Harmer
0.632
971183AH1-050 GEN
Solar/Wind Harmer
2.463
970647AG2-420 GEN
Solar/Wind Harmer
0.139
20089226LOOKOUT
Solar/Wind Harmer
0.507
20084926LAKVU GN
Adder
0.099
203860AG1-193 C
Solar/Wind Harmer
0.171
20082826HNSMLK 1
Adder
3.182
20083026HNSMLK 3
Adder
3.182
203813AE2-344_GEN
Solar/Wind Harmer
6.244
970267AG2-176 GEN
Solar/Wind Harmer
8.019
961971AG1-040 GEN
Solar/Wind Harmer
0.323
209067AE2-060 GEN
Solar/Wind Helper
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.56
WECLTFEXP_WEC->PJM
CLTF
0.328
CPLELTFEXP_CPLE->PJM
CLTF
0.296
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.695
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.976
LAGNLTFEXP_LAGN->PJM
CLTF
1.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.174
TVALTFEXP_TVA->PJM
CLTF
0.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.621
MECLTFEXP_MEC->PJM
CLTF
1.376
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_08_P22_102799_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_08_P22_102799_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.19 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:841.64
MW Contribution:1.79
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.251
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.673
203952AE2-129 C
Solar/Wind Harmer
1.065
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.711
20088626ARWF_N39
Solar/Wind Harmer
3.041
20303426NA_O38_P22
Solar/Wind Harmer
2.462
238217AF1-153 C O1
Solar/Wind Harmer
0.927
203853AF1-134 C O1
Solar/Wind Harmer
0.864
946381AF1-302 GEN
Solar/Wind Harmer
2.482
20390526W1-045 C
Solar/Wind Harmer
0.422
972075AH1-587 GEN
Solar/Wind Harmer
21.795
971441AH1-212 GEN
Solar/Wind Harmer
2.163
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.807
972077AH1-588 GEN
Solar/Wind Harmer
21.45
972079AH1-589 GEN
Solar/Wind Harmer
17.667
970715AG2-457 GEN
Solar/Wind Harmer
7.15
203982AD2-062_GEN
Solar/Wind Harmer
7.066
203857AF2-221 C
Solar/Wind Harmer
1.155
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.931
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.585
203839AF1-321 GEN
Solar/Wind Harmer
1.431
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.476
203848AF2-166 C
Solar/Wind Harmer
1.243
946071AF1-272 GEN
Solar/Wind Harmer
2.06
970313AG2-206 GEN
Solar/Wind Harmer
2.926
944781AF1-143 GEN
Solar/Wind Harmer
1.749
203979AG1-198 GEN
Solar/Wind Harmer
0.205
971933AH1-491 GEN
Solar/Wind Harmer
1.131
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.913
203947AF1-006 C
Solar/Wind Harmer
0.292
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.036
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.536
200642SENECA#1
50/50
1.549
941231AE2-117 GEN
Solar/Wind Harmer
1.569
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.518
203975AE1-071-GEN
Solar/Wind Harmer
4.874
20090526Q36
Solar/Wind Harmer
2.613
203993AD2-133_GEN1
Solar/Wind Harmer
2.613
203961AE2-224 GEN
Solar/Wind Harmer
4.26
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.601
959381AF2-229 GEN
Solar/Wind Harmer
0.82
203850AG1-041 C
Solar/Wind Harmer
1.108
203844AF2-092 C
Solar/Wind Harmer
1.079
20092526R32
Solar/Wind Harmer
1.548
940863AE2-074 GEN
Solar/Wind Harmer
1.465
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.318
203846AF2-130 C
Solar/Wind Harmer
0.355
970663AG2-429 GEN
Solar/Wind Harmer
4.26
970663AG2-429 GEN
Solar/Wind Harmer
0.693
20083926HOMER C3
Adder
43.363
20083826HOMER C2
Adder
40.962
20083726HOMER C1
Adder
40.346
970677AG2-438 GEN
Solar/Wind Harmer
0.565
966771AG1-548 GEN
Solar/Wind Harmer
8.24
966771AG1-548 GEN
Solar/Wind Harmer
1.597
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.101
203926AA2-133 GEN
Adder
1.127
23732901CHBRG_I12
Adder
1.143
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.674
238202AE2-262_GEN
Solar/Wind Harmer
6.009
971627AH1-313 GEN
Solar/Wind Harmer
23.56
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.518
960051AF2-296 GEN
Solar/Wind Harmer
2.859
203818AF1-086 GEN
Solar/Wind Harmer
2.845
20120126WRREN CT
Adder
5.712
971703AH1-357 GEN
Solar/Wind Harmer
1.787
971707AH1-359 GEN
Solar/Wind Harmer
1.787
970899AG2-561 GEN
Solar/Wind Harmer
1.619
20335126GROZ1-110
Adder
1.853
20335226CANZ2-011
Adder
1.802
20334926Z1-069 C
Solar/Wind Harmer
1.619
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.411
971541AH1-268 GEN
Solar/Wind Harmer
2.609
971879AH1-460 GEN
Solar/Wind Harmer
4.928
945751AF1-240 GEN
Solar/Wind Harmer
1.13
203841AF2-001_GEN
Solar/Wind Harmer
1.431
20079426CONEMAGH
Adder
0.85
941421AE2-139 GEN
Solar/Wind Harmer
1.976
203932AE1-123
Adder
1.274
238219AF1-167 C
Solar/Wind Harmer
0.859
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.893
971127AH1-005 GEN
Solar/Wind Harmer
1.221
971185AH1-051 GEN
Solar/Wind Harmer
1.441
971355AH1-158 GEN
Solar/Wind Harmer
1.675
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.167
972271AH1-720 GEN
Adder
3.813
20089126CSLMN_L13
Solar/Wind Harmer
0.51
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.361
203830AF1-094 GEN
Solar/Wind Harmer
0.342
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.101
20083126HNSMLK 4
Adder
3.101
203962AF1-287 GEN
Solar/Wind Harmer
1.052
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
20072226SHAWVL 2
50/50
29.543
20091326SHAW-D
50/50
1.294
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.445
970643AG2-418 GEN
Solar/Wind Harmer
3.104
238215AE2-248 C
Solar/Wind Harmer
4.666
964391AG1-301 GEN
Solar/Wind Harmer
1.622
203987AE2-118 C
Solar/Wind Harmer
4.828
238206AE2-263_GEN
Solar/Wind Harmer
5.6
972169AH1-667 GEN
Solar/Wind Harmer
3.34
203954AE2-126 C
Solar/Wind Harmer
1.002
957561AF2-050 GEN
Solar/Wind Harmer
7.033
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.96
20094526CT_V3-030
Solar/Wind Harmer
0.729
970713AG2-456 GEN
Solar/Wind Harmer
7.15
971705AH1-358 GEN
Solar/Wind Harmer
2.078
971709AH1-360 GEN
Solar/Wind Harmer
2.078
20088826HIGHLAND
Solar/Wind Harmer
1.444
971279AH1-102 GEN
Solar/Wind Harmer
6.131
970631AG2-411 GEN
Solar/Wind Harmer
4.665
971423AH1-203 GEN
Solar/Wind Harmer
5.124
20326126BLOSSBCT
Adder
1.647
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.318
203835AF1-098 GEN
Solar/Wind Harmer
1.516
20335026MILZ1-092
Adder
1.392
944411AF1-106 GEN
Solar/Wind Harmer
1.283
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.402
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.101
20083026HNSMLK 3
Adder
3.101
203813AE2-344_GEN
Solar/Wind Harmer
6.096
970267AG2-176 GEN
Solar/Wind Harmer
7.824
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
LGEELTFEXP_LGEE->PJM
CLTF
0.578
WECLTFEXP_WEC->PJM
CLTF
0.337
CPLELTFEXP_CPLE->PJM
CLTF
0.359
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.762
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.382
LAGNLTFEXP_LAGN->PJM
CLTF
1.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.327
TVALTFEXP_TVA->PJM
CLTF
0.707
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.667
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.747
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_48_P71_102649_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_48_P71_102649_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.55 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:837.69
MW Contribution:1.79
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.549
941231AE2-117 GEN
Solar/Wind Harmer
1.57
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.519
203975AE1-071-GEN
Solar/Wind Harmer
4.875
20090526Q36
Solar/Wind Harmer
2.613
203993AD2-133_GEN1
Solar/Wind Harmer
2.613
203961AE2-224 GEN
Solar/Wind Harmer
4.261
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.603
959381AF2-229 GEN
Solar/Wind Harmer
0.82
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.675
238202AE2-262_GEN
Solar/Wind Harmer
6.009
971627AH1-313 GEN
Solar/Wind Harmer
23.562
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.519
960051AF2-296 GEN
Solar/Wind Harmer
2.859
203818AF1-086 GEN
Solar/Wind Harmer
2.846
20120126WRREN CT
Adder
5.714
971703AH1-357 GEN
Solar/Wind Harmer
1.788
971707AH1-359 GEN
Solar/Wind Harmer
1.788
970899AG2-561 GEN
Solar/Wind Harmer
1.62
20335126GROZ1-110
Adder
1.854
20335226CANZ2-011
Adder
1.802
20334926Z1-069 C
Solar/Wind Harmer
1.619
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.412
971541AH1-268 GEN
Solar/Wind Harmer
2.61
971879AH1-460 GEN
Solar/Wind Harmer
4.929
945751AF1-240 GEN
Solar/Wind Harmer
1.13
203841AF2-001_GEN
Solar/Wind Harmer
1.432
20079426CONEMAGH
Adder
0.85
941421AE2-139 GEN
Solar/Wind Harmer
1.977
203932AE1-123
Adder
1.274
238219AF1-167 C
Solar/Wind Harmer
0.859
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.894
971127AH1-005 GEN
Solar/Wind Harmer
1.222
971185AH1-051 GEN
Solar/Wind Harmer
1.441
971355AH1-158 GEN
Solar/Wind Harmer
1.676
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.168
972271AH1-720 GEN
Adder
3.815
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.251
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.673
203952AE2-129 C
Solar/Wind Harmer
1.066
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.713
20088626ARWF_N39
Solar/Wind Harmer
3.042
20303426NA_O38_P22
Solar/Wind Harmer
2.463
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203853AF1-134 C O1
Solar/Wind Harmer
0.864
946381AF1-302 GEN
Solar/Wind Harmer
2.482
20390526W1-045 C
Solar/Wind Harmer
0.423
972075AH1-587 GEN
Solar/Wind Harmer
21.8
971441AH1-212 GEN
Solar/Wind Harmer
2.163
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.807
972077AH1-588 GEN
Solar/Wind Harmer
21.455
972079AH1-589 GEN
Solar/Wind Harmer
17.672
970715AG2-457 GEN
Solar/Wind Harmer
7.152
203982AD2-062_GEN
Solar/Wind Harmer
7.067
203857AF2-221 C
Solar/Wind Harmer
1.155
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.931
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.586
203839AF1-321 GEN
Solar/Wind Harmer
1.432
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.477
203848AF2-166 C
Solar/Wind Harmer
1.244
946071AF1-272 GEN
Solar/Wind Harmer
2.061
970313AG2-206 GEN
Solar/Wind Harmer
2.928
944781AF1-143 GEN
Solar/Wind Harmer
1.75
203979AG1-198 GEN
Solar/Wind Harmer
0.206
971933AH1-491 GEN
Solar/Wind Harmer
1.131
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.913
203947AF1-006 C
Solar/Wind Harmer
0.293
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.036
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.535
20072226SHAWVL 2
50/50
29.547
20091326SHAW-D
50/50
1.294
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.445
970643AG2-418 GEN
Solar/Wind Harmer
3.105
238215AE2-248 C
Solar/Wind Harmer
4.666
964391AG1-301 GEN
Solar/Wind Harmer
1.622
203987AE2-118 C
Solar/Wind Harmer
4.829
238206AE2-263_GEN
Solar/Wind Harmer
5.601
972169AH1-667 GEN
Solar/Wind Harmer
3.341
203954AE2-126 C
Solar/Wind Harmer
1.003
957561AF2-050 GEN
Solar/Wind Harmer
7.034
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.961
20094526CT_V3-030
Solar/Wind Harmer
0.73
970713AG2-456 GEN
Solar/Wind Harmer
7.152
971705AH1-358 GEN
Solar/Wind Harmer
2.079
971709AH1-360 GEN
Solar/Wind Harmer
2.079
20088826HIGHLAND
Solar/Wind Harmer
1.445
971279AH1-102 GEN
Solar/Wind Harmer
6.133
970631AG2-411 GEN
Solar/Wind Harmer
4.666
971423AH1-203 GEN
Solar/Wind Harmer
5.126
20326126BLOSSBCT
Adder
1.648
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.319
203835AF1-098 GEN
Solar/Wind Harmer
1.517
20335026MILZ1-092
Adder
1.393
944411AF1-106 GEN
Solar/Wind Harmer
1.283
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.402
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.102
20083026HNSMLK 3
Adder
3.102
203813AE2-344_GEN
Solar/Wind Harmer
6.098
970267AG2-176 GEN
Solar/Wind Harmer
7.827
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
203850AG1-041 C
Solar/Wind Harmer
1.109
203844AF2-092 C
Solar/Wind Harmer
1.079
20092526R32
Solar/Wind Harmer
1.548
940863AE2-074 GEN
Solar/Wind Harmer
1.465
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.355
970663AG2-429 GEN
Solar/Wind Harmer
4.261
970663AG2-429 GEN
Solar/Wind Harmer
0.694
20083926HOMER C3
Adder
43.379
20083826HOMER C2
Adder
40.977
20083726HOMER C1
Adder
40.361
970677AG2-438 GEN
Solar/Wind Harmer
0.566
966771AG1-548 GEN
Solar/Wind Harmer
8.243
966771AG1-548 GEN
Solar/Wind Harmer
1.597
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.102
203926AA2-133 GEN
Adder
1.128
23732901CHBRG_I12
Adder
1.144
20089126CSLMN_L13
Solar/Wind Harmer
0.511
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.362
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.102
20083126HNSMLK 4
Adder
3.102
203962AF1-287 GEN
Solar/Wind Harmer
1.052
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.361
LGEELTFEXP_LGEE->PJM
CLTF
0.579
WECLTFEXP_WEC->PJM
CLTF
0.338
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.779
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.412
LAGNLTFEXP_LAGN->PJM
CLTF
1.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.334
TVALTFEXP_TVA->PJM
CLTF
0.71
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.755
MECLTFEXP_MEC->PJM
CLTF
1.422
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.09 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:834.83
MW Contribution:1.79
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.252
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.674
203952AE2-129 C
Solar/Wind Harmer
1.066
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.716
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.676
238202AE2-262_GEN
Solar/Wind Harmer
6.01
971627AH1-313 GEN
Solar/Wind Harmer
23.565
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.519
960051AF2-296 GEN
Solar/Wind Harmer
2.86
203818AF1-086 GEN
Solar/Wind Harmer
2.846
20120126WRREN CT
Adder
5.716
971703AH1-357 GEN
Solar/Wind Harmer
1.789
971707AH1-359 GEN
Solar/Wind Harmer
1.789
970899AG2-561 GEN
Solar/Wind Harmer
1.62
20335126GROZ1-110
Adder
1.855
20335226CANZ2-011
Adder
1.803
20334926Z1-069 C
Solar/Wind Harmer
1.62
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.413
971541AH1-268 GEN
Solar/Wind Harmer
2.611
971879AH1-460 GEN
Solar/Wind Harmer
4.931
945751AF1-240 GEN
Solar/Wind Harmer
1.131
203841AF2-001_GEN
Solar/Wind Harmer
1.432
20079426CONEMAGH
Adder
0.851
941421AE2-139 GEN
Solar/Wind Harmer
1.977
203932AE1-123
Adder
1.275
238219AF1-167 C
Solar/Wind Harmer
0.859
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.895
971127AH1-005 GEN
Solar/Wind Harmer
1.222
971185AH1-051 GEN
Solar/Wind Harmer
1.442
971355AH1-158 GEN
Solar/Wind Harmer
1.677
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.168
972271AH1-720 GEN
Adder
3.817
20089126CSLMN_L13
Solar/Wind Harmer
0.511
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.365
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.104
20083126HNSMLK 4
Adder
3.104
203962AF1-287 GEN
Solar/Wind Harmer
1.053
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
20072226SHAWVL 2
50/50
29.551
20091326SHAW-D
50/50
1.295
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.446
970643AG2-418 GEN
Solar/Wind Harmer
3.105
238215AE2-248 C
Solar/Wind Harmer
4.667
964391AG1-301 GEN
Solar/Wind Harmer
1.623
203987AE2-118 C
Solar/Wind Harmer
4.829
238206AE2-263_GEN
Solar/Wind Harmer
5.602
972169AH1-667 GEN
Solar/Wind Harmer
3.341
203954AE2-126 C
Solar/Wind Harmer
1.003
957561AF2-050 GEN
Solar/Wind Harmer
7.035
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.962
20094526CT_V3-030
Solar/Wind Harmer
0.73
970713AG2-456 GEN
Solar/Wind Harmer
7.154
971705AH1-358 GEN
Solar/Wind Harmer
2.08
971709AH1-360 GEN
Solar/Wind Harmer
2.08
20088826HIGHLAND
Solar/Wind Harmer
1.445
971279AH1-102 GEN
Solar/Wind Harmer
6.136
970631AG2-411 GEN
Solar/Wind Harmer
4.668
971423AH1-203 GEN
Solar/Wind Harmer
5.128
20326126BLOSSBCT
Adder
1.648
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.32
203835AF1-098 GEN
Solar/Wind Harmer
1.517
20335026MILZ1-092
Adder
1.394
944411AF1-106 GEN
Solar/Wind Harmer
1.284
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.404
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.104
20083026HNSMLK 3
Adder
3.104
203813AE2-344_GEN
Solar/Wind Harmer
6.102
970267AG2-176 GEN
Solar/Wind Harmer
7.832
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
20088626ARWF_N39
Solar/Wind Harmer
3.042
20303426NA_O38_P22
Solar/Wind Harmer
2.463
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203853AF1-134 C O1
Solar/Wind Harmer
0.865
946381AF1-302 GEN
Solar/Wind Harmer
2.483
20390526W1-045 C
Solar/Wind Harmer
0.423
972075AH1-587 GEN
Solar/Wind Harmer
21.806
971441AH1-212 GEN
Solar/Wind Harmer
2.164
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.808
972077AH1-588 GEN
Solar/Wind Harmer
21.463
972079AH1-589 GEN
Solar/Wind Harmer
17.678
970715AG2-457 GEN
Solar/Wind Harmer
7.154
203982AD2-062_GEN
Solar/Wind Harmer
7.07
203857AF2-221 C
Solar/Wind Harmer
1.155
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.932
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.586
203839AF1-321 GEN
Solar/Wind Harmer
1.432
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.478
203848AF2-166 C
Solar/Wind Harmer
1.245
946071AF1-272 GEN
Solar/Wind Harmer
2.062
970313AG2-206 GEN
Solar/Wind Harmer
2.929
944781AF1-143 GEN
Solar/Wind Harmer
1.751
203979AG1-198 GEN
Solar/Wind Harmer
0.206
971933AH1-491 GEN
Solar/Wind Harmer
1.132
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.914
203947AF1-006 C
Solar/Wind Harmer
0.293
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.037
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.535
200642SENECA#1
50/50
1.55
941231AE2-117 GEN
Solar/Wind Harmer
1.57
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.519
203975AE1-071-GEN
Solar/Wind Harmer
4.876
20090526Q36
Solar/Wind Harmer
2.614
203993AD2-133_GEN1
Solar/Wind Harmer
2.614
203961AE2-224 GEN
Solar/Wind Harmer
4.262
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.604
959381AF2-229 GEN
Solar/Wind Harmer
0.82
203850AG1-041 C
Solar/Wind Harmer
1.109
203844AF2-092 C
Solar/Wind Harmer
1.08
20092526R32
Solar/Wind Harmer
1.549
940863AE2-074 GEN
Solar/Wind Harmer
1.466
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.32
203846AF2-130 C
Solar/Wind Harmer
0.356
970663AG2-429 GEN
Solar/Wind Harmer
4.263
970663AG2-429 GEN
Solar/Wind Harmer
0.694
20083926HOMER C3
Adder
43.401
20083826HOMER C2
Adder
40.997
20083726HOMER C1
Adder
40.382
970677AG2-438 GEN
Solar/Wind Harmer
0.566
966771AG1-548 GEN
Solar/Wind Harmer
8.247
966771AG1-548 GEN
Solar/Wind Harmer
1.598
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.104
203926AA2-133 GEN
Adder
1.129
23732901CHBRG_I12
Adder
1.144
CPLELTFEXP_CPLE->PJM
CLTF
0.365
LGEELTFEXP_LGEE->PJM
CLTF
0.581
WECLTFEXP_WEC->PJM
CLTF
0.339
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.454
LAGNLTFEXP_LAGN->PJM
CLTF
1.448
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.343
TVALTFEXP_TVA->PJM
CLTF
0.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.767
MECLTFEXP_MEC->PJM
CLTF
1.428
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:493.0 MVA
Rating Type:A
MVA to Mitigate:649.4
MW Contribution:1.25
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.573
20091326SHAW-D
50/50
1.296
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.448
970643AG2-418 GEN
Solar/Wind Harmer
3.106
238215AE2-248 C
Solar/Wind Harmer
3.258
203987AE2-118 C
Solar/Wind Harmer
3.371
238206AE2-263_GEN
Solar/Wind Harmer
0.01
972169AH1-667 GEN
Solar/Wind Harmer
2.333
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
4.914
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20094526CT_V3-030
Solar/Wind Harmer
0.122
970713AG2-456 GEN
Solar/Wind Harmer
5.812
971705AH1-358 GEN
Solar/Wind Harmer
2.083
971709AH1-360 GEN
Solar/Wind Harmer
2.083
20088826HIGHLAND
Solar/Wind Harmer
0.001
971279AH1-102 GEN
Solar/Wind Harmer
5.556
970631AG2-411 GEN
Solar/Wind Harmer
3.514
971423AH1-203 GEN
Solar/Wind Harmer
3.585
20326126BLOSSBCT
Adder
1.652
203843AF2-002_GEN
Solar/Wind Harmer
0.501
970337AG2-221 GEN
Solar/Wind Harmer
1.015
203835AF1-098 GEN
Solar/Wind Harmer
0.003
20335026MILZ1-092
Adder
1.397
944411AF1-106 GEN
Solar/Wind Harmer
1.425
970511AG2-327 GEN
Solar/Wind Harmer
0.427
971183AH1-050 GEN
Solar/Wind Harmer
2.076
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.077
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
3.113
20083026HNSMLK 3
Adder
3.113
203813AE2-344_GEN
Solar/Wind Harmer
4.269
970267AG2-176 GEN
Solar/Wind Harmer
5.48
209067AE2-060 GEN
Solar/Wind Helper
0.091
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
4.659
238202AE2-262_GEN
Solar/Wind Harmer
0.01
971627AH1-313 GEN
Solar/Wind Harmer
16.451
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.229
960051AF2-296 GEN
Solar/Wind Harmer
1.997
203818AF1-086 GEN
Solar/Wind Harmer
0.67
972323AH1-746 GEN
Solar/Wind Harmer
2.592
20120126WRREN CT
Adder
5.725
971703AH1-357 GEN
Solar/Wind Harmer
1.25
971707AH1-359 GEN
Solar/Wind Harmer
1.25
970899AG2-561 GEN
Solar/Wind Harmer
1.133
20335126GROZ1-110
Adder
1.858
20335226CANZ2-011
Adder
1.806
20334926Z1-069 C
Solar/Wind Harmer
0.406
970125AG2-091 GEN
Solar/Wind Harmer
0.323
971419AH1-201 GEN
Solar/Wind Harmer
2.125
971541AH1-268 GEN
Solar/Wind Harmer
3.208
971879AH1-460 GEN
Solar/Wind Harmer
3.447
945751AF1-240 GEN
Solar/Wind Harmer
0.92
203841AF2-001_GEN
Solar/Wind Harmer
1.001
20079426CONEMAGH
Adder
0.853
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.278
238219AF1-167 C
Solar/Wind Harmer
0.6
970335AG2-220 GEN
Solar/Wind Harmer
1.368
971127AH1-005 GEN
Solar/Wind Harmer
0.997
971185AH1-051 GEN
Solar/Wind Harmer
1.246
971355AH1-158 GEN
Solar/Wind Harmer
2.076
970647AG2-420 GEN
Solar/Wind Harmer
0.817
972271AH1-720 GEN
Adder
3.827
20089126CSLMN_L13
Solar/Wind Harmer
0.027
20089026BF_G21_K23
Solar/Wind Harmer
0.027
957161AF2-010 GEN
Solar/Wind Harmer
3.04
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.112
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.113
20083126HNSMLK 4
Adder
3.113
203962AF1-287 GEN
Solar/Wind Harmer
0.736
202652Y1-033 WT C
Solar/Wind Harmer
0
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.237
20071526SHAWVL 1
50/50
1.515
216419AE2-001 C
Solar/Wind Harmer
3.961
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.143
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
20390526W1-045 C
Solar/Wind Harmer
0.083
972075AH1-587 GEN
Solar/Wind Harmer
15.234
971441AH1-212 GEN
Solar/Wind Harmer
1.512
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.263
972077AH1-588 GEN
Solar/Wind Harmer
14.999
972079AH1-589 GEN
Solar/Wind Harmer
17.707
970715AG2-457 GEN
Solar/Wind Harmer
5.812
203982AD2-062_GEN
Solar/Wind Harmer
5.363
203857AF2-221 C
Solar/Wind Harmer
0.565
970123AG2-090 GEN
Solar/Wind Harmer
0.754
20088926STNY CRK
Solar/Wind Harmer
0.103
971427AH1-205 GEN
Solar/Wind Harmer
1.417
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.001
20398826ARMNA MT
Solar/Wind Harmer
0.025
203848AF2-166 C
Solar/Wind Harmer
0.87
946071AF1-272 GEN
Solar/Wind Harmer
0
970313AG2-206 GEN
Solar/Wind Harmer
2.048
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.792
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203859AF2-294 C
Solar/Wind Harmer
0.639
203947AF1-006 C
Solar/Wind Harmer
0.025
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.726
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.532
200642SENECA#1
50/50
1.552
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.229
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.591
203993AD2-133_GEN1
Solar/Wind Harmer
0.585
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.174
203804AE2-113_GEN
Solar/Wind Harmer
0.006
203850AG1-041 C
Solar/Wind Harmer
0.775
203844AF2-092 C
Solar/Wind Harmer
0.754
20092526R32
Solar/Wind Harmer
0.187
20087026C_T85_W218
Adder
0.504
970555AG2-356 GEN
Solar/Wind Harmer
0.923
970663AG2-429 GEN
Solar/Wind Harmer
3.183
970663AG2-429 GEN
Solar/Wind Harmer
0.696
20083926HOMER C3
Adder
43.507
20083826HOMER C2
Adder
41.097
20083726HOMER C1
Adder
40.483
970677AG2-438 GEN
Solar/Wind Harmer
0.442
966771AG1-548 GEN
Solar/Wind Harmer
1.316
966771AG1-548 GEN
Solar/Wind Harmer
1.645
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.113
203926AA2-133 GEN
Adder
1.132
23732901CHBRG_I12
Adder
1.148
LGEELTFEXP_LGEE->PJM
CLTF
0.592
WECLTFEXP_WEC->PJM
CLTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.877
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.655
LAGNLTFEXP_LAGN->PJM
CLTF
1.478
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.388
TVALTFEXP_TVA->PJM
CLTF
0.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.824
MECLTFEXP_MEC->PJM
CLTF
1.453
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P1-2_PN-115-094_A_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-115-094_A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.45 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:787.65
MW Contribution:1.39
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.7
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.605
970643AG2-418 GEN
Solar/Wind Harmer
4.444
238215AE2-248 C
Solar/Wind Harmer
3.596
203987AE2-118 C
Solar/Wind Harmer
3.732
238206AE2-263_GEN
Solar/Wind Harmer
0.011
972169AH1-667 GEN
Solar/Wind Harmer
2.581
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
5.45
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20094526CT_V3-030
Solar/Wind Harmer
0.135
970713AG2-456 GEN
Solar/Wind Harmer
6.466
971705AH1-358 GEN
Solar/Wind Harmer
2.318
971709AH1-360 GEN
Solar/Wind Harmer
2.318
20088826HIGHLAND
Solar/Wind Harmer
0.001
971279AH1-102 GEN
Solar/Wind Harmer
6.197
970631AG2-411 GEN
Solar/Wind Harmer
3.911
20326126BLOSSBCT
Adder
1.865
971423AH1-203 GEN
Solar/Wind Harmer
3.977
203843AF2-002_GEN
Solar/Wind Harmer
0.558
970337AG2-221 GEN
Solar/Wind Harmer
1.152
970511AG2-327 GEN
Solar/Wind Harmer
0.486
20335026MILZ1-092
Adder
1.586
944411AF1-106 GEN
Solar/Wind Harmer
1.618
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
2.305
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.084
203860AG1-193 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.459
20083026HNSMLK 3
Adder
3.459
203813AE2-344_GEN
Solar/Wind Harmer
4.724
970267AG2-176 GEN
Solar/Wind Harmer
6.072
209067AE2-060 GEN
Solar/Wind Helper
0.083
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
6.667
238202AE2-262_GEN
Solar/Wind Harmer
0.012
971627AH1-313 GEN
Solar/Wind Harmer
18.178
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.36
960051AF2-296 GEN
Solar/Wind Harmer
2.213
203818AF1-086 GEN
Solar/Wind Harmer
0.743
972323AH1-746 GEN
Solar/Wind Harmer
2.877
20120126WRREN CT
Adder
6.346
971703AH1-357 GEN
Solar/Wind Harmer
1.391
971707AH1-359 GEN
Solar/Wind Harmer
1.391
970899AG2-561 GEN
Solar/Wind Harmer
1.261
20335126GROZ1-110
Adder
2.101
20335226CANZ2-011
Adder
2.042
20334926Z1-069 C
Solar/Wind Harmer
0.455
970125AG2-091 GEN
Solar/Wind Harmer
0.36
971419AH1-201 GEN
Solar/Wind Harmer
2.358
971541AH1-268 GEN
Solar/Wind Harmer
3.577
971879AH1-460 GEN
Solar/Wind Harmer
3.839
945751AF1-240 GEN
Solar/Wind Harmer
1.024
203841AF2-001_GEN
Solar/Wind Harmer
1.115
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.42
238219AF1-167 C
Solar/Wind Harmer
0.667
970335AG2-220 GEN
Solar/Wind Harmer
1.558
971127AH1-005 GEN
Solar/Wind Harmer
1.136
972271AH1-720 GEN
Adder
4.399
971185AH1-051 GEN
Solar/Wind Harmer
1.383
971355AH1-158 GEN
Solar/Wind Harmer
2.305
970647AG2-420 GEN
Solar/Wind Harmer
0.907
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.03
20089026BF_G21_K23
Solar/Wind Harmer
0.03
957161AF2-010 GEN
Solar/Wind Harmer
3.367
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.124
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.459
20083126HNSMLK 4
Adder
3.459
203962AF1-287 GEN
Solar/Wind Harmer
0.815
202652Y1-033 WT C
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.166
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.492
20066526SHAWVL 3
50/50
2.473
20071526SHAWVL 1
50/50
1.676
216419AE2-001 C
Solar/Wind Harmer
4.372
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.8
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
972075AH1-587 GEN
Solar/Wind Harmer
16.919
971441AH1-212 GEN
Solar/Wind Harmer
1.68
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.4
972077AH1-588 GEN
Solar/Wind Harmer
16.686
972079AH1-589 GEN
Solar/Wind Harmer
19.699
970715AG2-457 GEN
Solar/Wind Harmer
6.466
203857AF2-221 C
Solar/Wind Harmer
0.63
970123AG2-090 GEN
Solar/Wind Harmer
0.84
20088926STNY CRK
Solar/Wind Harmer
0.114
971427AH1-205 GEN
Solar/Wind Harmer
1.572
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.115
20398826ARMNA MT
Solar/Wind Harmer
0.028
970313AG2-206 GEN
Solar/Wind Harmer
2.334
946071AF1-272 GEN
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
0.967
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.877
203963AG1-253 GEN
Solar/Wind Harmer
0.197
203859AF2-294 C
Solar/Wind Harmer
0.732
203947AF1-006 C
Solar/Wind Harmer
0.028
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.803
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.402
200642SENECA#1
50/50
1.721
203975AE1-071-GEN
Solar/Wind Harmer
0.044
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.36
20090526Q36
Solar/Wind Harmer
0.654
203993AD2-133_GEN1
Solar/Wind Harmer
0.648
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.193
203804AE2-113_GEN
Solar/Wind Harmer
0.007
203850AG1-041 C
Solar/Wind Harmer
0.861
203844AF2-092 C
Solar/Wind Harmer
0.838
20092526R32
Solar/Wind Harmer
0.208
970555AG2-356 GEN
Solar/Wind Harmer
1.047
970663AG2-429 GEN
Solar/Wind Harmer
3.539
970663AG2-429 GEN
Solar/Wind Harmer
0.774
20083926HOMER C3
Adder
48.691
20083826HOMER C2
Adder
45.994
20083726HOMER C1
Adder
45.416
970677AG2-438 GEN
Solar/Wind Harmer
0.49
966771AG1-548 GEN
Solar/Wind Harmer
1.458
966771AG1-548 GEN
Solar/Wind Harmer
1.822
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.459
203926AA2-133 GEN
Adder
1.316
20334726NME_Y1-047
Adder
1.11
LGEELTFEXP_LGEE->PJM
CLTF
0.556
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.203
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.763
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.969
TVALTFEXP_TVA->PJM
CLTF
0.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.533
MECLTFEXP_MEC->PJM
CLTF
1.368
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P12_000085_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P12_000085_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.27 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:786.5
MW Contribution:1.28
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.562
20091326SHAW-D
50/50
1.299
20064926PENNTECH
50/50
0.404
200643SENECA#2
50/50
1.48
970643AG2-418 GEN
Solar/Wind Harmer
3.069
238215AE2-248 C
Solar/Wind Harmer
3.237
203987AE2-118 C
Solar/Wind Harmer
3.373
238206AE2-263_GEN
Solar/Wind Harmer
0.01
972169AH1-667 GEN
Solar/Wind Harmer
2.339
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
5.007
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20094526CT_V3-030
Solar/Wind Harmer
0.126
200644SENECA#3
50/50
0.204
970643AG2-418 GEN
Solar/Wind Harmer
4.603
238202AE2-262_GEN
Solar/Wind Harmer
0.01
971627AH1-313 GEN
Solar/Wind Harmer
16.392
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.236
960051AF2-296 GEN
Solar/Wind Harmer
2.025
203818AF1-086 GEN
Solar/Wind Harmer
0.688
972323AH1-746 GEN
Solar/Wind Harmer
2.662
20120126WRREN CT
Adder
5.889
971703AH1-357 GEN
Solar/Wind Harmer
1.285
971707AH1-359 GEN
Solar/Wind Harmer
1.285
970899AG2-561 GEN
Solar/Wind Harmer
1.189
970125AG2-091 GEN
Solar/Wind Harmer
0.34
971419AH1-201 GEN
Solar/Wind Harmer
2.232
971541AH1-268 GEN
Solar/Wind Harmer
3.386
971879AH1-460 GEN
Solar/Wind Harmer
3.636
20334926Z1-069 C
Solar/Wind Harmer
0.414
20335126GROZ1-110
Adder
1.817
20335226CANZ2-011
Adder
1.766
945751AF1-240 GEN
Solar/Wind Harmer
0.973
203841AF2-001_GEN
Solar/Wind Harmer
1.059
20079426CONEMAGH
Adder
0.904
20088826HIGHLAND
Solar/Wind Harmer
0.001
970713AG2-456 GEN
Solar/Wind Harmer
5.973
971705AH1-358 GEN
Solar/Wind Harmer
2.141
971709AH1-360 GEN
Solar/Wind Harmer
2.141
971279AH1-102 GEN
Solar/Wind Harmer
5.865
970631AG2-411 GEN
Solar/Wind Harmer
3.708
971423AH1-203 GEN
Solar/Wind Harmer
3.774
203843AF2-002_GEN
Solar/Wind Harmer
0.53
20326126BLOSSBCT
Adder
1.644
203835AF1-098 GEN
Solar/Wind Harmer
0.003
970337AG2-221 GEN
Solar/Wind Harmer
1.002
971183AH1-050 GEN
Solar/Wind Harmer
2.218
970647AG2-420 GEN
Solar/Wind Harmer
0.146
20089226LOOKOUT
Solar/Wind Harmer
0.082
20335026MILZ1-092
Adder
1.389
944411AF1-106 GEN
Solar/Wind Harmer
1.417
970511AG2-327 GEN
Solar/Wind Harmer
0.419
203860AG1-193 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.103
20082826HNSMLK 1
Adder
3.354
20083026HNSMLK 3
Adder
3.354
970267AG2-176 GEN
Solar/Wind Harmer
5.887
203813AE2-344_GEN
Solar/Wind Harmer
4.571
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.225
946741AF1-338 GEN
Solar/Wind Helper
0.225
203932AE1-123
Adder
1.36
238219AF1-167 C
Solar/Wind Harmer
0.641
971185AH1-051 GEN
Solar/Wind Harmer
1.331
971355AH1-158 GEN
Solar/Wind Harmer
2.218
970647AG2-420 GEN
Solar/Wind Harmer
0.874
941421AE2-139 GEN
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Harmer
0.029
20089026BF_G21_K23
Solar/Wind Harmer
0.029
957161AF2-010 GEN
Solar/Wind Harmer
3.237
203830AF1-094 GEN
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
1.343
971127AH1-005 GEN
Solar/Wind Harmer
0.979
203948AG1-140 C
Solar/Wind Harmer
0.119
20084926LAKVU GN
Adder
0.103
20082926HNSMLK 2
Adder
3.354
20083126HNSMLK 4
Adder
3.354
203962AF1-287 GEN
Solar/Wind Harmer
0.788
972271AH1-720 GEN
Adder
3.634
20328326MANOR_T86
Adder
0.077
202652Y1-033 WT C
Solar/Wind Harmer
0
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.225
212507AE2-042_GEN
Solar/Wind Helper
0.788
20081226ALY HYDR
50/50
0.384
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.236
20071526SHAWVL 1
50/50
1.517
216419AE2-001 C
Solar/Wind Harmer
3.937
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.178
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
1.558
972075AH1-587 GEN
Solar/Wind Harmer
15.512
20390526W1-045 C
Solar/Wind Harmer
0.08
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.3
972077AH1-588 GEN
Solar/Wind Harmer
15.415
972079AH1-589 GEN
Solar/Wind Harmer
18.198
970715AG2-457 GEN
Solar/Wind Harmer
5.973
203982AD2-062_GEN
Solar/Wind Harmer
5.202
203857AF2-221 C
Solar/Wind Harmer
0.595
200642SENECA#1
50/50
1.586
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.236
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.596
203993AD2-133_GEN1
Solar/Wind Harmer
0.59
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.178
203804AE2-113_GEN
Solar/Wind Harmer
0.006
203850AG1-041 C
Solar/Wind Harmer
0.805
203844AF2-092 C
Solar/Wind Harmer
0.785
20092526R32
Solar/Wind Harmer
0.195
20087026C_T85_W218
Adder
0.48
970663AG2-429 GEN
Solar/Wind Harmer
3.405
970663AG2-429 GEN
Solar/Wind Harmer
0.744
20083926HOMER C3
Adder
46.584
20083826HOMER C2
Adder
44.004
970555AG2-356 GEN
Solar/Wind Harmer
0.911
20083726HOMER C1
Adder
43.869
970677AG2-438 GEN
Solar/Wind Harmer
0.471
966771AG1-548 GEN
Solar/Wind Harmer
1.401
966771AG1-548 GEN
Solar/Wind Harmer
1.752
20084926LAKVU GN
Adder
0.116
20083226HNSMLK 5
Adder
3.354
203926AA2-133 GEN
Adder
1.058
23732901CHBRG_I12
Adder
1.103
959431AF2-234 GEN
Solar/Wind Helper
0.452
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.226
970123AG2-090 GEN
Solar/Wind Harmer
0.794
20088926STNY CRK
Solar/Wind Harmer
0.108
971427AH1-205 GEN
Solar/Wind Harmer
1.488
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.059
946071AF1-272 GEN
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
0.928
20398826ARMNA MT
Solar/Wind Harmer
0.025
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.843
203963AG1-253 GEN
Solar/Wind Harmer
0.188
970313AG2-206 GEN
Solar/Wind Harmer
2.009
203947AF1-006 C
Solar/Wind Harmer
0.027
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.778
203859AF2-294 C
Solar/Wind Harmer
0.627
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.69
946751AF1-339 GEN
Solar/Wind Helper
0.225
209054AE2-059 GEN
Solar/Wind Helper
0.04
NYPJM->LTFIMP_NY
CLTF
0.234
LGEELTFEXP_LGEE->PJM
CLTF
0.793
WECLTFEXP_WEC->PJM
CLTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
0.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.334
LAGNLTFEXP_LAGN->PJM
CLTF
1.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.946
TVALTFEXP_TVA->PJM
CLTF
0.986
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.461
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.818
MECLTFEXP_MEC->PJM
CLTF
1.942
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-17B25_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-17B25_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.44 %
Rating:377.0 MVA
Rating Type:B
MVA to Mitigate:420.14
MW Contribution:1.26
Bus #Bus NameTypeMW Contribution
20328326MANOR_T86
50/50
0.353
972271AH1-720 GEN
50/50
14.213
20335126GROZ1-110
50/50
4.275
20335226CANZ2-011
50/50
4.155
200917MEHOOPANY_G
Solar/Wind Harmer
17.378
941421AE2-139 GEN
Solar/Wind Harmer
5.96
970335AG2-220 GEN
Solar/Wind Harmer
5.882
971127AH1-005 GEN
Solar/Wind Harmer
3.795
944411AF1-106 GEN
Solar/Wind Harmer
0.402
20334926Z1-069 C
Solar/Wind Harmer
2.285
971703AH1-357 GEN
Solar/Wind Harmer
1.256
971707AH1-359 GEN
Solar/Wind Harmer
1.256
238202AE2-262_GEN
Solar/Wind Harmer
1.244
971627AH1-313 GEN
Solar/Wind Harmer
4.878
20120126WRREN CT
Adder
2.975
203854AF2-039 C
Solar/Wind Harmer
0.188
20396426MEHP3X3003
50/50
2.053
20085126MEHOOP3
50/50
1.892
203859AF2-294 C
Solar/Wind Harmer
5.013
970313AG2-206 GEN
Solar/Wind Harmer
9.153
20398826ARMNA MT
Solar/Wind Harmer
3.96
972077AH1-588 GEN
Solar/Wind Harmer
15.067
972079AH1-589 GEN
Solar/Wind Harmer
12.41
970715AG2-457 GEN
Solar/Wind Harmer
5.022
972075AH1-587 GEN
Solar/Wind Harmer
12.445
238217AF1-153 C O1
Solar/Wind Harmer
0.286
970305AG2-200 GEN
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Helper
0.526
20334726NME_Y1-047
50/50
12.389
203926AA2-133 GEN
50/50
7.469
203922AA1-082 G1
50/50
4.968
203923AA1-082 G2
50/50
4.968
970555AG2-356 GEN
Solar/Wind Harmer
3.505
940863AE2-074 GEN
Solar/Wind Harmer
1.535
203804AE2-113_GEN
Solar/Wind Harmer
2.899
203855AF2-088 C
Solar/Wind Harmer
0.091
20083926HOMER C3
Adder
26.714
20083826HOMER C2
Adder
25.235
20083726HOMER C1
Adder
16.801
20335026MILZ1-092
50/50
4.308
20326126BLOSSBCT
50/50
3.735
970511AG2-327 GEN
Solar/Wind Harmer
1.907
944411AF1-106 GEN
Solar/Wind Harmer
3.74
959471AF2-238 GEN
Solar/Wind Harmer
1.06
970337AG2-221 GEN
Solar/Wind Harmer
3.505
970713AG2-456 GEN
Solar/Wind Harmer
5.022
971705AH1-358 GEN
Solar/Wind Harmer
1.46
971709AH1-360 GEN
Solar/Wind Harmer
1.46
203954AE2-126 C
Solar/Wind Harmer
0.299
20072226SHAWVL 2
Adder
6.765
238206AE2-263_GEN
Solar/Wind Harmer
1.159
972169AH1-667 GEN
Solar/Wind Harmer
0.829
20091326SHAW-D
Adder
0.303
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.191
CPLELTFEXP_CPLE->PJM
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.907
LAGNLTFEXP_LAGN->PJM
CLTF
0.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.787
TVALTFEXP_TVA->PJM
CLTF
0.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.744
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.567
MECLTFEXP_MEC->PJM
CLTF
0.804
SIGELTFEXP_SIGE->PJM
CLTF
0.025

Details for 26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-997-DRT-067_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-997-DRT-067_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.05 %
Rating:377.0 MVA
Rating Type:B
MVA to Mitigate:418.65
MW Contribution:1.26
Bus #Bus NameTypeMW Contribution
20328326MANOR_T86
50/50
0.353
972271AH1-720 GEN
50/50
14.213
20335126GROZ1-110
50/50
4.275
20335226CANZ2-011
50/50
4.155
200917MEHOOPANY_G
Solar/Wind Harmer
17.378
941421AE2-139 GEN
Solar/Wind Harmer
5.96
970335AG2-220 GEN
Solar/Wind Harmer
5.882
971127AH1-005 GEN
Solar/Wind Harmer
3.795
944411AF1-106 GEN
Solar/Wind Harmer
0.402
20334926Z1-069 C
Solar/Wind Harmer
2.285
971703AH1-357 GEN
Solar/Wind Harmer
1.256
20396426MEHP3X3003
50/50
2.053
20085126MEHOOP3
50/50
1.892
203859AF2-294 C
Solar/Wind Harmer
5.013
970313AG2-206 GEN
Solar/Wind Harmer
9.153
20398826ARMNA MT
Solar/Wind Harmer
3.96
972077AH1-588 GEN
Solar/Wind Harmer
15.067
972079AH1-589 GEN
Solar/Wind Harmer
12.41
970715AG2-457 GEN
Solar/Wind Harmer
5.022
972075AH1-587 GEN
Solar/Wind Harmer
12.445
238217AF1-153 C O1
Solar/Wind Harmer
0.286
970305AG2-200 GEN
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Helper
0.526
20334726NME_Y1-047
50/50
12.389
203926AA2-133 GEN
50/50
7.469
203922AA1-082 G1
50/50
4.968
203923AA1-082 G2
50/50
4.968
970555AG2-356 GEN
Solar/Wind Harmer
3.505
940863AE2-074 GEN
Solar/Wind Harmer
1.535
203804AE2-113_GEN
Solar/Wind Harmer
2.899
203855AF2-088 C
Solar/Wind Harmer
0.091
20083926HOMER C3
Adder
26.714
20083826HOMER C2
Adder
25.235
20083726HOMER C1
Adder
16.801
971707AH1-359 GEN
Solar/Wind Harmer
1.256
238202AE2-262_GEN
Solar/Wind Harmer
1.244
971627AH1-313 GEN
Solar/Wind Harmer
4.878
20120126WRREN CT
Adder
2.975
203854AF2-039 C
Solar/Wind Harmer
0.188
20335026MILZ1-092
50/50
4.308
20326126BLOSSBCT
50/50
3.735
970511AG2-327 GEN
Solar/Wind Harmer
1.907
944411AF1-106 GEN
Solar/Wind Harmer
3.74
959471AF2-238 GEN
Solar/Wind Harmer
1.06
970337AG2-221 GEN
Solar/Wind Harmer
3.505
970713AG2-456 GEN
Solar/Wind Harmer
5.022
971705AH1-358 GEN
Solar/Wind Harmer
1.46
971709AH1-360 GEN
Solar/Wind Harmer
1.46
203954AE2-126 C
Solar/Wind Harmer
0.299
20072226SHAWVL 2
Adder
6.765
238206AE2-263_GEN
Solar/Wind Harmer
1.159
972169AH1-667 GEN
Solar/Wind Harmer
0.829
20091326SHAW-D
Adder
0.303
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.191
CPLELTFEXP_CPLE->PJM
CLTF
0.22
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.907
LAGNLTFEXP_LAGN->PJM
CLTF
0.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.787
TVALTFEXP_TVA->PJM
CLTF
0.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.744
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.567
MECLTFEXP_MEC->PJM
CLTF
0.804
SIGELTFEXP_SIGE->PJM
CLTF
0.025

Details for 26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line l/o AP_P2-3_WP-230-708C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-708C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.64 %
Rating:174.0 MVA
Rating Type:B
MVA to Mitigate:175.12
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
26.805
970305AG2-200 GEN
Solar/Wind Harmer
1.683
972077AH1-588 GEN
Solar/Wind Harmer
18.647
972079AH1-589 GEN
Solar/Wind Harmer
15.358
970715AG2-457 GEN
Solar/Wind Harmer
6.216
203952AE2-129 C
Solar/Wind Helper
0.461
203946AE2-131 C
Solar/Wind Helper
0.462
203853AF1-134 C O1
Solar/Wind Helper
0.399
238217AF1-153 C O1
Solar/Wind Helper
0.136
200642SENECA#1
50/50
1.541
203804AE2-113_GEN
Solar/Wind Harmer
7.438
940863AE2-074 GEN
Solar/Wind Harmer
1.171
20083926HOMER C3
Adder
7.822
20083826HOMER C2
Adder
7.389
20083726HOMER C1
Adder
1.707
203855AF2-088 C
Solar/Wind Helper
0.198
20090526Q36
Solar/Wind Helper
0.754
203993AD2-133_GEN1
Solar/Wind Helper
0.754
200644SENECA#3
50/50
0.198
20120126WRREN CT
Adder
5.322
971703AH1-357 GEN
Solar/Wind Harmer
1.554
971707AH1-359 GEN
Solar/Wind Harmer
1.554
20334926Z1-069 C
Solar/Wind Harmer
1.054
203854AF2-039 C
Solar/Wind Helper
0.411
238202AE2-262_GEN
Solar/Wind Helper
0.65
203818AF1-086 GEN
Solar/Wind Helper
0.844
20064926PENNTECH
50/50
0.648
200643SENECA#2
50/50
1.438
203954AE2-126 C
Solar/Wind Harmer
2.914
970713AG2-456 GEN
Solar/Wind Harmer
6.216
971705AH1-358 GEN
Solar/Wind Harmer
1.807
971709AH1-360 GEN
Solar/Wind Harmer
1.807
203835AF1-098 GEN
Solar/Wind Harmer
1.05
238206AE2-263_GEN
Solar/Wind Helper
0.618
LGEELTFEXP_LGEE->PJM
CLTF
0.108
WECLTFEXP_WEC->PJM
CLTF
0.066
CPLELTFEXP_CPLE->PJM
CLTF
0.043
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.53
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.929
LAGNLTFEXP_LAGN->PJM
CLTF
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.192
TVALTFEXP_TVA->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.828
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.495
MECLTFEXP_MEC->PJM
CLTF
0.274
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line l/o AP_P2-3_WP-230-708DT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-708DT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.51 %
Rating:174.0 MVA
Rating Type:B
MVA to Mitigate:174.88
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.541
203804AE2-113_GEN
Solar/Wind Harmer
7.438
940863AE2-074 GEN
Solar/Wind Harmer
1.171
20083926HOMER C3
Adder
7.822
20083826HOMER C2
Adder
7.389
20083726HOMER C1
Adder
1.707
972075AH1-587 GEN
Solar/Wind Harmer
26.805
970305AG2-200 GEN
Solar/Wind Harmer
1.683
972077AH1-588 GEN
Solar/Wind Harmer
18.647
972079AH1-589 GEN
Solar/Wind Harmer
15.358
970715AG2-457 GEN
Solar/Wind Harmer
6.216
203952AE2-129 C
Solar/Wind Helper
0.461
203946AE2-131 C
Solar/Wind Helper
0.462
203853AF1-134 C O1
Solar/Wind Helper
0.399
238217AF1-153 C O1
Solar/Wind Helper
0.136
203855AF2-088 C
Solar/Wind Helper
0.198
20090526Q36
Solar/Wind Helper
0.754
203993AD2-133_GEN1
Solar/Wind Helper
0.754
200644SENECA#3
50/50
0.198
20120126WRREN CT
Adder
5.322
971703AH1-357 GEN
Solar/Wind Harmer
1.554
971707AH1-359 GEN
Solar/Wind Harmer
1.554
20334926Z1-069 C
Solar/Wind Harmer
1.054
203854AF2-039 C
Solar/Wind Helper
0.411
238202AE2-262_GEN
Solar/Wind Helper
0.65
203818AF1-086 GEN
Solar/Wind Helper
0.844
20064926PENNTECH
50/50
0.648
200643SENECA#2
50/50
1.438
203954AE2-126 C
Solar/Wind Harmer
2.914
970713AG2-456 GEN
Solar/Wind Harmer
6.216
971705AH1-358 GEN
Solar/Wind Harmer
1.807
971709AH1-360 GEN
Solar/Wind Harmer
1.807
203835AF1-098 GEN
Solar/Wind Harmer
1.05
238206AE2-263_GEN
Solar/Wind Helper
0.618
LGEELTFEXP_LGEE->PJM
CLTF
0.108
WECLTFEXP_WEC->PJM
CLTF
0.066
CPLELTFEXP_CPLE->PJM
CLTF
0.043
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.53
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.929
LAGNLTFEXP_LAGN->PJM
CLTF
0.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.192
TVALTFEXP_TVA->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.828
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.495
MECLTFEXP_MEC->PJM
CLTF
0.274
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line l/o AP_P2-3_WP-230-708AT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-708AT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.35 %
Rating:174.0 MVA
Rating Type:B
MVA to Mitigate:174.61
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
26.824
970305AG2-200 GEN
Solar/Wind Harmer
1.684
972077AH1-588 GEN
Solar/Wind Harmer
18.654
972079AH1-589 GEN
Solar/Wind Harmer
15.364
970715AG2-457 GEN
Solar/Wind Harmer
6.218
203952AE2-129 C
Solar/Wind Helper
0.458
203946AE2-131 C
Solar/Wind Helper
0.459
203853AF1-134 C O1
Solar/Wind Helper
0.397
238217AF1-153 C O1
Solar/Wind Helper
0.139
200642SENECA#1
50/50
1.542
203804AE2-113_GEN
Solar/Wind Harmer
7.444
940863AE2-074 GEN
Solar/Wind Harmer
1.172
20083926HOMER C3
Adder
7.764
20083826HOMER C2
Adder
7.334
20083726HOMER C1
Adder
1.687
203855AF2-088 C
Solar/Wind Helper
0.197
20090526Q36
Solar/Wind Helper
0.749
203993AD2-133_GEN1
Solar/Wind Helper
0.749
200644SENECA#3
50/50
0.198
20120126WRREN CT
Adder
5.323
971703AH1-357 GEN
Solar/Wind Harmer
1.555
971707AH1-359 GEN
Solar/Wind Harmer
1.555
20334926Z1-069 C
Solar/Wind Harmer
1.055
203854AF2-039 C
Solar/Wind Helper
0.408
238202AE2-262_GEN
Solar/Wind Helper
0.64
203818AF1-086 GEN
Solar/Wind Helper
0.839
20064926PENNTECH
50/50
0.648
200643SENECA#2
50/50
1.439
203954AE2-126 C
Solar/Wind Harmer
2.917
970713AG2-456 GEN
Solar/Wind Harmer
6.218
971705AH1-358 GEN
Solar/Wind Harmer
1.808
971709AH1-360 GEN
Solar/Wind Harmer
1.808
203835AF1-098 GEN
Solar/Wind Harmer
1.049
238206AE2-263_GEN
Solar/Wind Helper
0.609
LGEELTFEXP_LGEE->PJM
CLTF
0.107
WECLTFEXP_WEC->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.041
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.559
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.897
LAGNLTFEXP_LAGN->PJM
CLTF
0.254
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.188
TVALTFEXP_TVA->PJM
CLTF
0.124
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.788
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.486
MECLTFEXP_MEC->PJM
CLTF
0.269
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line l/o AP_P2-3_WP-230-708C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
Contingency Name:
AP_P2-3_WP-230-708C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.55 %
Rating:191.0 MVA
Rating Type:B
MVA to Mitigate:197.78
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
20071526SHAWVL 1
50/50
1.365
20066626SHAWVL 4
50/50
-1.002
203853AF1-134 C O1
Solar/Wind Harmer
1.777
972075AH1-587 GEN
Solar/Wind Harmer
16.762
970305AG2-200 GEN
Solar/Wind Harmer
1.076
972077AH1-588 GEN
Solar/Wind Harmer
11.797
972079AH1-589 GEN
Solar/Wind Harmer
9.716
970715AG2-457 GEN
Solar/Wind Harmer
3.932
203952AE2-129 C
Solar/Wind Helper
1.49
203946AE2-131 C
Solar/Wind Helper
1.493
238217AF1-153 C O1
Solar/Wind Helper
0.147
203854AF2-039 C
Solar/Wind Harmer
1.306
960051AF2-296 GEN
Solar/Wind Harmer
5.878
203818AF1-086 GEN
Solar/Wind Harmer
4.389
970899AG2-561 GEN
Solar/Wind Harmer
1.312
20120126WRREN CT
Adder
3.403
971703AH1-357 GEN
Solar/Wind Harmer
0.983
971707AH1-359 GEN
Solar/Wind Harmer
0.983
20091326SHAW-D
50/50
3.217
20064926PENNTECH
50/50
0.403
972169AH1-667 GEN
Solar/Wind Harmer
5.75
203954AE2-126 C
Solar/Wind Harmer
1.806
970713AG2-456 GEN
Solar/Wind Harmer
3.932
971705AH1-358 GEN
Solar/Wind Harmer
1.143
971709AH1-360 GEN
Solar/Wind Harmer
1.143
20094526CT_V3-030
Solar/Wind Harmer
0.321
238206AE2-263_GEN
Solar/Wind Helper
0.675
964391AG1-301 GEN
Solar/Wind Helper
0.282
203855AF2-088 C
Solar/Wind Harmer
0.629
203804AE2-113_GEN
Solar/Wind Harmer
4.645
20083926HOMER C3
Adder
6.362
20083826HOMER C2
Adder
6.01
20083726HOMER C1
Adder
2.751
20090526Q36
Solar/Wind Helper
2.35
203993AD2-133_GEN1
Solar/Wind Helper
2.35
20091526CHSTN_FL
Solar/Wind Helper
0.478
941231AE2-117 GEN
Solar/Wind Helper
0.33
238202AE2-262_GEN
Solar/Wind Helper
0.709
LGEELTFEXP_LGEE->PJM
CLTF
0.107
WECLTFEXP_WEC->PJM
CLTF
0.064
CPLELTFEXP_CPLE->PJM
CLTF
0.046
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.236
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.897
LAGNLTFEXP_LAGN->PJM
CLTF
0.257
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.199
TVALTFEXP_TVA->PJM
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.491
MECLTFEXP_MEC->PJM
CLTF
0.267
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line l/o AP_P2-3_WP-230-708DT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
Contingency Name:
AP_P2-3_WP-230-708DT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:191.0 MVA
Rating Type:B
MVA to Mitigate:197.4
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
203855AF2-088 C
Solar/Wind Harmer
0.629
203804AE2-113_GEN
Solar/Wind Harmer
4.645
20083926HOMER C3
Adder
6.362
20083826HOMER C2
Adder
6.01
20083726HOMER C1
Adder
2.751
20090526Q36
Solar/Wind Helper
2.35
203993AD2-133_GEN1
Solar/Wind Helper
2.35
20091526CHSTN_FL
Solar/Wind Helper
0.478
941231AE2-117 GEN
Solar/Wind Helper
0.33
203854AF2-039 C
Solar/Wind Harmer
1.306
960051AF2-296 GEN
Solar/Wind Harmer
5.878
203818AF1-086 GEN
Solar/Wind Harmer
4.389
970899AG2-561 GEN
Solar/Wind Harmer
1.312
20071526SHAWVL 1
50/50
1.365
20066626SHAWVL 4
50/50
-1.002
203853AF1-134 C O1
Solar/Wind Harmer
1.777
972075AH1-587 GEN
Solar/Wind Harmer
16.762
970305AG2-200 GEN
Solar/Wind Harmer
1.076
972077AH1-588 GEN
Solar/Wind Harmer
11.797
972079AH1-589 GEN
Solar/Wind Harmer
9.716
970715AG2-457 GEN
Solar/Wind Harmer
3.932
203952AE2-129 C
Solar/Wind Helper
1.49
203946AE2-131 C
Solar/Wind Helper
1.493
238217AF1-153 C O1
Solar/Wind Helper
0.147
20120126WRREN CT
Adder
3.403
971703AH1-357 GEN
Solar/Wind Harmer
0.983
971707AH1-359 GEN
Solar/Wind Harmer
0.983
238202AE2-262_GEN
Solar/Wind Helper
0.709
20091326SHAW-D
50/50
3.217
20064926PENNTECH
50/50
0.403
972169AH1-667 GEN
Solar/Wind Harmer
5.75
203954AE2-126 C
Solar/Wind Harmer
1.806
970713AG2-456 GEN
Solar/Wind Harmer
3.932
971705AH1-358 GEN
Solar/Wind Harmer
1.143
971709AH1-360 GEN
Solar/Wind Harmer
1.143
20094526CT_V3-030
Solar/Wind Harmer
0.321
238206AE2-263_GEN
Solar/Wind Helper
0.675
964391AG1-301 GEN
Solar/Wind Helper
0.282
LGEELTFEXP_LGEE->PJM
CLTF
0.107
WECLTFEXP_WEC->PJM
CLTF
0.064
CPLELTFEXP_CPLE->PJM
CLTF
0.046
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.236
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.897
LAGNLTFEXP_LAGN->PJM
CLTF
0.257
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.199
TVALTFEXP_TVA->PJM
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.491
MECLTFEXP_MEC->PJM
CLTF
0.267
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line l/o AP_P2-3_WP-230-708AT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line
Contingency Name:
AP_P2-3_WP-230-708AT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.23 %
Rating:191.0 MVA
Rating Type:B
MVA to Mitigate:197.17
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
203855AF2-088 C
Solar/Wind Harmer
0.631
203804AE2-113_GEN
Solar/Wind Harmer
4.652
20083926HOMER C3
Adder
6.295
20083826HOMER C2
Adder
5.947
20083726HOMER C1
Adder
2.729
20090526Q36
Solar/Wind Helper
2.344
203993AD2-133_GEN1
Solar/Wind Helper
2.344
20091526CHSTN_FL
Solar/Wind Helper
0.476
941231AE2-117 GEN
Solar/Wind Helper
0.328
20071526SHAWVL 1
50/50
1.373
20066626SHAWVL 4
50/50
-0.989
203853AF1-134 C O1
Solar/Wind Harmer
1.78
972075AH1-587 GEN
Solar/Wind Harmer
16.785
970305AG2-200 GEN
Solar/Wind Harmer
1.077
972077AH1-588 GEN
Solar/Wind Harmer
11.805
972079AH1-589 GEN
Solar/Wind Harmer
9.723
970715AG2-457 GEN
Solar/Wind Harmer
3.935
203952AE2-129 C
Solar/Wind Helper
1.487
203946AE2-131 C
Solar/Wind Helper
1.49
238217AF1-153 C O1
Solar/Wind Helper
0.15
203854AF2-039 C
Solar/Wind Harmer
1.31
960051AF2-296 GEN
Solar/Wind Harmer
5.889
203818AF1-086 GEN
Solar/Wind Harmer
4.397
970899AG2-561 GEN
Solar/Wind Harmer
1.313
20120126WRREN CT
Adder
3.404
971703AH1-357 GEN
Solar/Wind Harmer
0.984
971707AH1-359 GEN
Solar/Wind Harmer
0.984
238202AE2-262_GEN
Solar/Wind Helper
0.698
20091326SHAW-D
50/50
3.224
20064926PENNTECH
50/50
0.404
972169AH1-667 GEN
Solar/Wind Harmer
5.766
203954AE2-126 C
Solar/Wind Harmer
1.809
970713AG2-456 GEN
Solar/Wind Harmer
3.935
971705AH1-358 GEN
Solar/Wind Harmer
1.144
971709AH1-360 GEN
Solar/Wind Harmer
1.144
20094526CT_V3-030
Solar/Wind Harmer
0.322
238206AE2-263_GEN
Solar/Wind Helper
0.664
964391AG1-301 GEN
Solar/Wind Helper
0.281
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
0.044
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.86
LAGNLTFEXP_LAGN->PJM
CLTF
0.251
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.194
TVALTFEXP_TVA->PJM
CLTF
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.481
MECLTFEXP_MEC->PJM
CLTF
0.262
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-456_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-456_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.17 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:705.38
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.189
238202AE2-262_GEN
Solar/Wind Harmer
5.32
971627AH1-313 GEN
Solar/Wind Harmer
20.86
203854AF2-039 C
Solar/Wind Harmer
0.83
965131AG1-378 GEN
Solar/Wind Harmer
2.93
960051AF2-296 GEN
Solar/Wind Harmer
2.745
203818AF1-086 GEN
Solar/Wind Harmer
2.261
20120126WRREN CT
Adder
5.287
20335126GROZ1-110
Adder
1.874
20335226CANZ2-011
Adder
1.821
971703AH1-357 GEN
Solar/Wind Harmer
1.543
971707AH1-359 GEN
Solar/Wind Harmer
1.543
941421AE2-139 GEN
Solar/Wind Harmer
2.091
20334926Z1-069 C
Solar/Wind Harmer
1.381
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.768
971127AH1-005 GEN
Solar/Wind Harmer
1.141
944411AF1-106 GEN
Solar/Wind Harmer
0.122
238219AF1-167 C
Solar/Wind Harmer
0.655
203932AE1-123
Adder
0.907
945751AF1-240 GEN
Solar/Wind Harmer
0.723
970899AG2-561 GEN
Solar/Wind Harmer
0.917
200917MEHOOPANY_G
Solar/Wind Harmer
1.566
203948AG1-140 C
Solar/Wind Harmer
0.117
20084926LAKVU GN
Adder
0.076
203830AF1-094 GEN
Solar/Wind Harmer
0.261
957161AF2-010 GEN
Solar/Wind Harmer
3.32
20072226SHAWVL 2
50/50
35.26
20091326SHAW-D
50/50
1.415
20064926PENNTECH
50/50
0.417
200643SENECA#2
50/50
1.376
238206AE2-263_GEN
Solar/Wind Harmer
4.959
972169AH1-667 GEN
Solar/Wind Harmer
3.652
203954AE2-126 C
Solar/Wind Harmer
1.073
238183AE2-316 GEN
Solar/Wind Harmer
4.911
970713AG2-456 GEN
Solar/Wind Harmer
6.173
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
20326126BLOSSBCT
Adder
1.508
959471AF2-238 GEN
Solar/Wind Harmer
0.37
970337AG2-221 GEN
Solar/Wind Harmer
1.225
970511AG2-327 GEN
Solar/Wind Harmer
0.571
20335026MILZ1-092
Adder
1.229
944411AF1-106 GEN
Solar/Wind Harmer
1.132
203835AF1-098 GEN
Solar/Wind Harmer
1.254
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.232
200642SENECA#1
50/50
1.475
203855AF2-088 C
Solar/Wind Harmer
0.399
965121AG1-377 GEN
Solar/Wind Harmer
2.93
203804AE2-113_GEN
Solar/Wind Harmer
5.43
20090526Q36
Solar/Wind Harmer
1.558
203993AD2-133_GEN1
Solar/Wind Harmer
1.558
940863AE2-074 GEN
Solar/Wind Harmer
1.263
970555AG2-356 GEN
Solar/Wind Harmer
1.225
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
3.131
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20334726NME_Y1-047
Adder
1.052
203846AF2-130 C
Solar/Wind Harmer
0.253
20084926LAKVU GN
Adder
0.086
966771AG1-548 GEN
Solar/Wind Harmer
6.307
966771AG1-548 GEN
Solar/Wind Harmer
1.222
970677AG2-438 GEN
Solar/Wind Harmer
0.431
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
238217AF1-153 C O1
Solar/Wind Harmer
0.979
203952AE2-129 C
Solar/Wind Harmer
0.887
203946AE2-131 C
Solar/Wind Harmer
0.886
962411AG1-090 GEN
Solar/Wind Harmer
13.917
203853AF1-134 C O1
Solar/Wind Harmer
0.83
946381AF1-302 GEN
Solar/Wind Harmer
2.457
972075AH1-587 GEN
Solar/Wind Harmer
20.593
970305AG2-200 GEN
Solar/Wind Harmer
1.672
972077AH1-588 GEN
Solar/Wind Harmer
18.52
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
6.173
970313AG2-206 GEN
Solar/Wind Harmer
2.739
20398826ARMNA MT
Solar/Wind Harmer
1.307
203859AF2-294 C
Solar/Wind Harmer
0.824
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203848AF2-166 C
Solar/Wind Harmer
0.885
203979AG1-198 GEN
Solar/Wind Harmer
0.157
971933AH1-491 GEN
Solar/Wind Harmer
0.863
20390526W1-045 C
Solar/Wind Helper
0.177
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
MECLTFEXP_MEC->PJM
CLTF
0.47
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-2_WP-230-004_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-004_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:705.32
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.475
203855AF2-088 C
Solar/Wind Harmer
0.399
965121AG1-377 GEN
Solar/Wind Harmer
2.93
203804AE2-113_GEN
Solar/Wind Harmer
5.43
20090526Q36
Solar/Wind Harmer
1.558
203993AD2-133_GEN1
Solar/Wind Harmer
1.558
940863AE2-074 GEN
Solar/Wind Harmer
1.263
970555AG2-356 GEN
Solar/Wind Harmer
1.225
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
3.131
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
200644SENECA#3
50/50
0.189
238202AE2-262_GEN
Solar/Wind Harmer
5.32
971627AH1-313 GEN
Solar/Wind Harmer
20.86
203854AF2-039 C
Solar/Wind Harmer
0.83
965131AG1-378 GEN
Solar/Wind Harmer
2.93
960051AF2-296 GEN
Solar/Wind Harmer
2.745
203818AF1-086 GEN
Solar/Wind Harmer
2.261
20120126WRREN CT
Adder
5.287
20335126GROZ1-110
Adder
1.874
20335226CANZ2-011
Adder
1.821
971703AH1-357 GEN
Solar/Wind Harmer
1.543
971707AH1-359 GEN
Solar/Wind Harmer
1.543
941421AE2-139 GEN
Solar/Wind Harmer
2.091
20334926Z1-069 C
Solar/Wind Harmer
1.381
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.768
971127AH1-005 GEN
Solar/Wind Harmer
1.141
944411AF1-106 GEN
Solar/Wind Harmer
0.122
238219AF1-167 C
Solar/Wind Harmer
0.655
203932AE1-123
Adder
0.907
945751AF1-240 GEN
Solar/Wind Harmer
0.723
970899AG2-561 GEN
Solar/Wind Harmer
0.917
200917MEHOOPANY_G
Solar/Wind Harmer
1.566
203948AG1-140 C
Solar/Wind Harmer
0.117
20084926LAKVU GN
Adder
0.076
203830AF1-094 GEN
Solar/Wind Harmer
0.261
957161AF2-010 GEN
Solar/Wind Harmer
3.32
20334726NME_Y1-047
Adder
1.052
203846AF2-130 C
Solar/Wind Harmer
0.253
20084926LAKVU GN
Adder
0.086
966771AG1-548 GEN
Solar/Wind Harmer
6.307
966771AG1-548 GEN
Solar/Wind Harmer
1.222
970677AG2-438 GEN
Solar/Wind Harmer
0.431
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
20071526SHAWVL 1
50/50
1.73
238217AF1-153 C O1
Solar/Wind Harmer
0.979
203952AE2-129 C
Solar/Wind Harmer
0.887
203946AE2-131 C
Solar/Wind Harmer
0.886
962411AG1-090 GEN
Solar/Wind Harmer
13.917
203853AF1-134 C O1
Solar/Wind Harmer
0.83
946381AF1-302 GEN
Solar/Wind Harmer
2.457
972075AH1-587 GEN
Solar/Wind Harmer
20.593
970305AG2-200 GEN
Solar/Wind Harmer
1.672
972077AH1-588 GEN
Solar/Wind Harmer
18.52
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
6.173
970313AG2-206 GEN
Solar/Wind Harmer
2.739
20398826ARMNA MT
Solar/Wind Harmer
1.307
203859AF2-294 C
Solar/Wind Harmer
0.824
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203848AF2-166 C
Solar/Wind Harmer
0.885
203979AG1-198 GEN
Solar/Wind Harmer
0.157
971933AH1-491 GEN
Solar/Wind Harmer
0.863
20390526W1-045 C
Solar/Wind Helper
0.177
20072226SHAWVL 2
50/50
35.26
20091326SHAW-D
50/50
1.415
20064926PENNTECH
50/50
0.417
200643SENECA#2
50/50
1.376
238206AE2-263_GEN
Solar/Wind Harmer
4.959
972169AH1-667 GEN
Solar/Wind Harmer
3.652
203954AE2-126 C
Solar/Wind Harmer
1.073
238183AE2-316 GEN
Solar/Wind Harmer
4.911
970713AG2-456 GEN
Solar/Wind Harmer
6.173
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
20326126BLOSSBCT
Adder
1.508
959471AF2-238 GEN
Solar/Wind Harmer
0.37
970337AG2-221 GEN
Solar/Wind Harmer
1.225
970511AG2-327 GEN
Solar/Wind Harmer
0.571
20335026MILZ1-092
Adder
1.229
944411AF1-106 GEN
Solar/Wind Harmer
1.132
203835AF1-098 GEN
Solar/Wind Harmer
1.254
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.232
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
MECLTFEXP_MEC->PJM
CLTF
0.47
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-643_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-643_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.15 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:705.29
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.189
238202AE2-262_GEN
Solar/Wind Harmer
5.32
971627AH1-313 GEN
Solar/Wind Harmer
20.86
203854AF2-039 C
Solar/Wind Harmer
0.83
965131AG1-378 GEN
Solar/Wind Harmer
2.93
960051AF2-296 GEN
Solar/Wind Harmer
2.745
203818AF1-086 GEN
Solar/Wind Harmer
2.261
20120126WRREN CT
Adder
5.287
20335126GROZ1-110
Adder
1.874
20335226CANZ2-011
Adder
1.821
971703AH1-357 GEN
Solar/Wind Harmer
1.543
971707AH1-359 GEN
Solar/Wind Harmer
1.543
941421AE2-139 GEN
Solar/Wind Harmer
2.091
20334926Z1-069 C
Solar/Wind Harmer
1.381
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.768
971127AH1-005 GEN
Solar/Wind Harmer
1.141
944411AF1-106 GEN
Solar/Wind Harmer
0.122
238219AF1-167 C
Solar/Wind Harmer
0.655
203932AE1-123
Adder
0.907
945751AF1-240 GEN
Solar/Wind Harmer
0.723
970899AG2-561 GEN
Solar/Wind Harmer
0.917
200917MEHOOPANY_G
Solar/Wind Harmer
1.566
203948AG1-140 C
Solar/Wind Harmer
0.117
20084926LAKVU GN
Adder
0.076
203830AF1-094 GEN
Solar/Wind Harmer
0.261
957161AF2-010 GEN
Solar/Wind Harmer
3.32
20072226SHAWVL 2
50/50
35.26
20091326SHAW-D
50/50
1.415
20064926PENNTECH
50/50
0.417
200643SENECA#2
50/50
1.376
238206AE2-263_GEN
Solar/Wind Harmer
4.959
972169AH1-667 GEN
Solar/Wind Harmer
3.652
203954AE2-126 C
Solar/Wind Harmer
1.073
238183AE2-316 GEN
Solar/Wind Harmer
4.911
970713AG2-456 GEN
Solar/Wind Harmer
6.173
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
20326126BLOSSBCT
Adder
1.508
959471AF2-238 GEN
Solar/Wind Harmer
0.37
970337AG2-221 GEN
Solar/Wind Harmer
1.225
970511AG2-327 GEN
Solar/Wind Harmer
0.571
20335026MILZ1-092
Adder
1.229
944411AF1-106 GEN
Solar/Wind Harmer
1.132
203835AF1-098 GEN
Solar/Wind Harmer
1.254
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.232
200642SENECA#1
50/50
1.475
203855AF2-088 C
Solar/Wind Harmer
0.399
965121AG1-377 GEN
Solar/Wind Harmer
2.93
203804AE2-113_GEN
Solar/Wind Harmer
5.43
20090526Q36
Solar/Wind Harmer
1.558
203993AD2-133_GEN1
Solar/Wind Harmer
1.558
940863AE2-074 GEN
Solar/Wind Harmer
1.263
970555AG2-356 GEN
Solar/Wind Harmer
1.225
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
3.131
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20334726NME_Y1-047
Adder
1.052
203846AF2-130 C
Solar/Wind Harmer
0.253
20084926LAKVU GN
Adder
0.086
966771AG1-548 GEN
Solar/Wind Harmer
6.307
966771AG1-548 GEN
Solar/Wind Harmer
1.222
970677AG2-438 GEN
Solar/Wind Harmer
0.431
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
238217AF1-153 C O1
Solar/Wind Harmer
0.979
203952AE2-129 C
Solar/Wind Harmer
0.887
203946AE2-131 C
Solar/Wind Harmer
0.886
962411AG1-090 GEN
Solar/Wind Harmer
13.917
203853AF1-134 C O1
Solar/Wind Harmer
0.83
946381AF1-302 GEN
Solar/Wind Harmer
2.457
972075AH1-587 GEN
Solar/Wind Harmer
20.593
970305AG2-200 GEN
Solar/Wind Harmer
1.672
972077AH1-588 GEN
Solar/Wind Harmer
18.52
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
6.173
970313AG2-206 GEN
Solar/Wind Harmer
2.739
20398826ARMNA MT
Solar/Wind Harmer
1.307
203859AF2-294 C
Solar/Wind Harmer
0.824
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203848AF2-166 C
Solar/Wind Harmer
0.885
203979AG1-198 GEN
Solar/Wind Harmer
0.157
971933AH1-491 GEN
Solar/Wind Harmer
0.863
20390526W1-045 C
Solar/Wind Helper
0.177
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
MECLTFEXP_MEC->PJM
CLTF
0.47
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-450T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-450T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.33 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:624.15
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.523
203855AF2-088 C
Solar/Wind Harmer
0.482
965121AG1-377 GEN
Solar/Wind Harmer
3.589
20090526Q36
Solar/Wind Harmer
1.953
203993AD2-133_GEN1
Solar/Wind Harmer
1.953
203804AE2-113_GEN
Solar/Wind Harmer
5.671
940863AE2-074 GEN
Solar/Wind Harmer
1.152
970663AG2-429 GEN
Solar/Wind Harmer
3.329
970663AG2-429 GEN
Solar/Wind Harmer
0.542
203846AF2-130 C
Solar/Wind Harmer
0.271
20091526CHSTN_FL
Solar/Wind Harmer
0.406
970677AG2-438 GEN
Solar/Wind Harmer
0.446
966771AG1-548 GEN
Solar/Wind Harmer
6.52
966771AG1-548 GEN
Solar/Wind Harmer
1.264
20084926LAKVU GN
Adder
0.088
20083926HOMER C3
Adder
19.573
20083826HOMER C2
Adder
18.489
20083726HOMER C1
Adder
11.166
203975AE1-071-GEN
Solar/Wind Helper
1.636
200644SENECA#3
50/50
0.196
20120126WRREN CT
50/50
5.786
203854AF2-039 C
Solar/Wind Harmer
1.002
965131AG1-378 GEN
Solar/Wind Harmer
3.589
960051AF2-296 GEN
Solar/Wind Harmer
3.313
203818AF1-086 GEN
Solar/Wind Harmer
2.725
971703AH1-357 GEN
Solar/Wind Harmer
1.541
971707AH1-359 GEN
Solar/Wind Harmer
1.541
970899AG2-561 GEN
Solar/Wind Harmer
1.095
20334926Z1-069 C
Solar/Wind Harmer
1.129
945751AF1-240 GEN
Solar/Wind Harmer
0.817
238219AF1-167 C
Solar/Wind Harmer
0.697
203932AE1-123
Adder
0.98
959441AF2-235 GEN
Solar/Wind Harmer
0.136
203948AG1-140 C
Solar/Wind Harmer
0.117
957161AF2-010 GEN
Solar/Wind Harmer
3.439
203830AF1-094 GEN
Solar/Wind Harmer
0.27
203856AF2-165 C
Solar/Wind Harmer
0.531
971185AH1-051 GEN
Solar/Wind Harmer
1.08
971355AH1-158 GEN
Solar/Wind Harmer
1.256
20084926LAKVU GN
Adder
0.078
970647AG2-420 GEN
Solar/Wind Harmer
0.871
238202AE2-262_GEN
Solar/Wind Helper
3.084
20072226SHAWVL 2
50/50
42.725
20091326SHAW-D
50/50
1.709
20064926PENNTECH
50/50
0.448
200643SENECA#2
50/50
1.421
972169AH1-667 GEN
Solar/Wind Harmer
4.412
203954AE2-126 C
Solar/Wind Harmer
1.232
238183AE2-316 GEN
Solar/Wind Harmer
5.161
970713AG2-456 GEN
Solar/Wind Harmer
6.162
971705AH1-358 GEN
Solar/Wind Harmer
1.791
971709AH1-360 GEN
Solar/Wind Harmer
1.791
203835AF1-098 GEN
Solar/Wind Harmer
1.286
20094526CT_V3-030
Solar/Wind Harmer
0.361
971183AH1-050 GEN
Solar/Wind Harmer
1.8
20084926LAKVU GN
Adder
0.078
970647AG2-420 GEN
Solar/Wind Harmer
0.101
238206AE2-263_GEN
Solar/Wind Helper
2.933
20066626SHAWVL 4
50/50
3.256
20066526SHAWVL 3
50/50
3.231
20071526SHAWVL 1
50/50
2.102
203952AE2-129 C
Solar/Wind Harmer
1.087
203946AE2-131 C
Solar/Wind Harmer
1.085
962411AG1-090 GEN
Solar/Wind Harmer
17.049
238217AF1-153 C O1
Solar/Wind Harmer
1.028
203853AF1-134 C O1
Solar/Wind Harmer
1.002
946381AF1-302 GEN
Solar/Wind Harmer
2.582
972075AH1-587 GEN
Solar/Wind Harmer
21.27
970305AG2-200 GEN
Solar/Wind Harmer
1.725
972077AH1-588 GEN
Solar/Wind Harmer
18.486
972079AH1-589 GEN
Solar/Wind Harmer
15.226
970715AG2-457 GEN
Solar/Wind Harmer
6.162
203848AF2-166 C
Solar/Wind Harmer
0.949
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203979AG1-198 GEN
Solar/Wind Harmer
0.162
971933AH1-491 GEN
Solar/Wind Harmer
0.893
LGEELTFEXP_LGEE->PJM
CLTF
0.254
WECLTFEXP_WEC->PJM
CLTF
0.153
CPLELTFEXP_CPLE->PJM
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.373
LAGNLTFEXP_LAGN->PJM
CLTF
0.573
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.312
TVALTFEXP_TVA->PJM
CLTF
0.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.108
MECLTFEXP_MEC->PJM
CLTF
0.63
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-449T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-449T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.27 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:623.82
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.523
203855AF2-088 C
Solar/Wind Harmer
0.482
965121AG1-377 GEN
Solar/Wind Harmer
3.589
200644SENECA#3
50/50
0.196
20120126WRREN CT
50/50
5.786
203854AF2-039 C
Solar/Wind Harmer
1.002
965131AG1-378 GEN
Solar/Wind Harmer
3.589
960051AF2-296 GEN
Solar/Wind Harmer
3.313
203818AF1-086 GEN
Solar/Wind Harmer
2.725
971703AH1-357 GEN
Solar/Wind Harmer
1.541
971707AH1-359 GEN
Solar/Wind Harmer
1.541
970899AG2-561 GEN
Solar/Wind Harmer
1.095
20334926Z1-069 C
Solar/Wind Harmer
1.129
945751AF1-240 GEN
Solar/Wind Harmer
0.817
238219AF1-167 C
Solar/Wind Harmer
0.697
203932AE1-123
Adder
0.98
959441AF2-235 GEN
Solar/Wind Harmer
0.136
203948AG1-140 C
Solar/Wind Harmer
0.117
957161AF2-010 GEN
Solar/Wind Harmer
3.439
203830AF1-094 GEN
Solar/Wind Harmer
0.27
203856AF2-165 C
Solar/Wind Harmer
0.531
971185AH1-051 GEN
Solar/Wind Harmer
1.08
971355AH1-158 GEN
Solar/Wind Harmer
1.256
20084926LAKVU GN
Adder
0.078
970647AG2-420 GEN
Solar/Wind Harmer
0.871
238202AE2-262_GEN
Solar/Wind Helper
3.084
20066626SHAWVL 4
50/50
3.256
20066526SHAWVL 3
50/50
3.231
20071526SHAWVL 1
50/50
2.102
203952AE2-129 C
Solar/Wind Harmer
1.087
203946AE2-131 C
Solar/Wind Harmer
1.085
962411AG1-090 GEN
Solar/Wind Harmer
17.049
238217AF1-153 C O1
Solar/Wind Harmer
1.028
203853AF1-134 C O1
Solar/Wind Harmer
1.002
946381AF1-302 GEN
Solar/Wind Harmer
2.582
972075AH1-587 GEN
Solar/Wind Harmer
21.27
970305AG2-200 GEN
Solar/Wind Harmer
1.725
972077AH1-588 GEN
Solar/Wind Harmer
18.486
972079AH1-589 GEN
Solar/Wind Harmer
15.226
970715AG2-457 GEN
Solar/Wind Harmer
6.162
203848AF2-166 C
Solar/Wind Harmer
0.949
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203979AG1-198 GEN
Solar/Wind Harmer
0.162
971933AH1-491 GEN
Solar/Wind Harmer
0.893
20090526Q36
Solar/Wind Harmer
1.953
203993AD2-133_GEN1
Solar/Wind Harmer
1.953
203804AE2-113_GEN
Solar/Wind Harmer
5.671
940863AE2-074 GEN
Solar/Wind Harmer
1.152
20072226SHAWVL 2
50/50
42.725
20091326SHAW-D
50/50
1.709
20064926PENNTECH
50/50
0.448
200643SENECA#2
50/50
1.421
972169AH1-667 GEN
Solar/Wind Harmer
4.412
203954AE2-126 C
Solar/Wind Harmer
1.232
238183AE2-316 GEN
Solar/Wind Harmer
5.161
970713AG2-456 GEN
Solar/Wind Harmer
6.162
971705AH1-358 GEN
Solar/Wind Harmer
1.791
971709AH1-360 GEN
Solar/Wind Harmer
1.791
203835AF1-098 GEN
Solar/Wind Harmer
1.286
20094526CT_V3-030
Solar/Wind Harmer
0.361
971183AH1-050 GEN
Solar/Wind Harmer
1.8
20084926LAKVU GN
Adder
0.078
970647AG2-420 GEN
Solar/Wind Harmer
0.101
238206AE2-263_GEN
Solar/Wind Helper
2.933
970663AG2-429 GEN
Solar/Wind Harmer
3.329
970663AG2-429 GEN
Solar/Wind Harmer
0.542
203846AF2-130 C
Solar/Wind Harmer
0.271
20091526CHSTN_FL
Solar/Wind Harmer
0.406
970677AG2-438 GEN
Solar/Wind Harmer
0.446
966771AG1-548 GEN
Solar/Wind Harmer
6.52
966771AG1-548 GEN
Solar/Wind Harmer
1.264
20084926LAKVU GN
Adder
0.088
20083926HOMER C3
Adder
19.573
20083826HOMER C2
Adder
18.489
20083726HOMER C1
Adder
11.166
203975AE1-071-GEN
Solar/Wind Helper
1.636
LGEELTFEXP_LGEE->PJM
CLTF
0.254
WECLTFEXP_WEC->PJM
CLTF
0.153
CPLELTFEXP_CPLE->PJM
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.077
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.373
LAGNLTFEXP_LAGN->PJM
CLTF
0.573
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.312
TVALTFEXP_TVA->PJM
CLTF
0.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.108
MECLTFEXP_MEC->PJM
CLTF
0.63
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P1-2_WP-230-005A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-230-005A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.13 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:617.14
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.189
20120126WRREN CT
50/50
5.61
20335126GROZ1-110
50/50
1.989
20335226CANZ2-011
50/50
1.933
238202AE2-262_GEN
Solar/Wind Harmer
0.009
971627AH1-313 GEN
Solar/Wind Harmer
14.553
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.022
960051AF2-296 GEN
Solar/Wind Harmer
1.915
203818AF1-086 GEN
Solar/Wind Harmer
0.531
972323AH1-746 GEN
Solar/Wind Harmer
2.056
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
5.11
972075AH1-587 GEN
Solar/Wind Harmer
14.367
970305AG2-200 GEN
Solar/Wind Harmer
1.167
972077AH1-588 GEN
Solar/Wind Harmer
12.921
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
5.007
970313AG2-206 GEN
Solar/Wind Harmer
1.911
20398826ARMNA MT
Solar/Wind Harmer
0.022
203859AF2-294 C
Solar/Wind Harmer
0.575
203963AG1-253 GEN
Solar/Wind Harmer
0.14
203848AF2-166 C
Solar/Wind Harmer
0.617
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.602
20390526W1-045 C
Solar/Wind Helper
0.177
200642SENECA#1
50/50
1.475
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.022
203804AE2-113_GEN
Solar/Wind Harmer
0.006
20090526Q36
Solar/Wind Harmer
0.352
203993AD2-133_GEN1
Solar/Wind Harmer
0.348
970555AG2-356 GEN
Solar/Wind Harmer
0.854
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
2.332
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20334726NME_Y1-047
Adder
1.052
20084926LAKVU GN
Adder
0.086
966771AG1-548 GEN
Solar/Wind Harmer
1.004
966771AG1-548 GEN
Solar/Wind Harmer
1.255
970677AG2-438 GEN
Solar/Wind Harmer
0.336
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
971703AH1-357 GEN
Solar/Wind Harmer
1.077
971707AH1-359 GEN
Solar/Wind Harmer
1.077
941421AE2-139 GEN
Solar/Wind Harmer
0
20334926Z1-069 C
Solar/Wind Harmer
0.346
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.273
971127AH1-005 GEN
Solar/Wind Harmer
0.928
238219AF1-167 C
Solar/Wind Harmer
0.456
203932AE1-123
Adder
0.907
945751AF1-240 GEN
Solar/Wind Harmer
0.587
970899AG2-561 GEN
Solar/Wind Harmer
0.639
200917MEHOOPANY_G
Solar/Wind Harmer
0.157
203948AG1-140 C
Solar/Wind Harmer
0.088
20084926LAKVU GN
Adder
0.076
203830AF1-094 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
2.306
20072226SHAWVL 2
50/50
35.26
20091326SHAW-D
50/50
1.415
20064926PENNTECH
50/50
0.417
200643SENECA#2
50/50
1.376
20326126BLOSSBCT
50/50
1.6
238206AE2-263_GEN
Solar/Wind Harmer
0.009
972169AH1-667 GEN
Solar/Wind Harmer
2.548
203954AE2-126 C
Solar/Wind Harmer
0.002
238183AE2-316 GEN
Solar/Wind Harmer
0.004
970713AG2-456 GEN
Solar/Wind Harmer
5.007
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
970337AG2-221 GEN
Solar/Wind Harmer
0.94
970511AG2-327 GEN
Solar/Wind Harmer
0.398
20335026MILZ1-092
Adder
1.229
944411AF1-106 GEN
Solar/Wind Harmer
1.254
203835AF1-098 GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.232
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
MECLTFEXP_MEC->PJM
CLTF
0.47
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P1-3_WP-230-005_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-230-005_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.12 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:617.05
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
5.11
972075AH1-587 GEN
Solar/Wind Harmer
14.367
200642SENECA#1
50/50
1.475
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.022
203804AE2-113_GEN
Solar/Wind Harmer
0.006
20090526Q36
Solar/Wind Harmer
0.352
203993AD2-133_GEN1
Solar/Wind Harmer
0.348
970555AG2-356 GEN
Solar/Wind Harmer
0.854
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
2.332
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20334726NME_Y1-047
Adder
1.052
20084926LAKVU GN
Adder
0.086
966771AG1-548 GEN
Solar/Wind Harmer
1.004
966771AG1-548 GEN
Solar/Wind Harmer
1.255
970677AG2-438 GEN
Solar/Wind Harmer
0.336
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
200644SENECA#3
50/50
0.189
20120126WRREN CT
50/50
5.61
20335126GROZ1-110
50/50
1.989
20335226CANZ2-011
50/50
1.933
238202AE2-262_GEN
Solar/Wind Harmer
0.009
971627AH1-313 GEN
Solar/Wind Harmer
14.553
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.022
960051AF2-296 GEN
Solar/Wind Harmer
1.915
203818AF1-086 GEN
Solar/Wind Harmer
0.531
972323AH1-746 GEN
Solar/Wind Harmer
2.056
971703AH1-357 GEN
Solar/Wind Harmer
1.077
971707AH1-359 GEN
Solar/Wind Harmer
1.077
941421AE2-139 GEN
Solar/Wind Harmer
0
20334926Z1-069 C
Solar/Wind Harmer
0.346
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
970335AG2-220 GEN
Solar/Wind Harmer
1.273
971127AH1-005 GEN
Solar/Wind Harmer
0.928
238219AF1-167 C
Solar/Wind Harmer
0.456
203932AE1-123
Adder
0.907
945751AF1-240 GEN
Solar/Wind Harmer
0.587
970899AG2-561 GEN
Solar/Wind Harmer
0.639
200917MEHOOPANY_G
Solar/Wind Harmer
0.157
203948AG1-140 C
Solar/Wind Harmer
0.088
20084926LAKVU GN
Adder
0.076
203830AF1-094 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
2.306
20072226SHAWVL 2
50/50
35.26
20091326SHAW-D
50/50
1.415
20064926PENNTECH
50/50
0.417
200643SENECA#2
50/50
1.376
20326126BLOSSBCT
50/50
1.6
238206AE2-263_GEN
Solar/Wind Harmer
0.009
972169AH1-667 GEN
Solar/Wind Harmer
2.548
203954AE2-126 C
Solar/Wind Harmer
0.002
238183AE2-316 GEN
Solar/Wind Harmer
0.004
970713AG2-456 GEN
Solar/Wind Harmer
5.007
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
970337AG2-221 GEN
Solar/Wind Harmer
0.94
970511AG2-327 GEN
Solar/Wind Harmer
0.398
20335026MILZ1-092
Adder
1.229
944411AF1-106 GEN
Solar/Wind Harmer
1.254
203835AF1-098 GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.232
970305AG2-200 GEN
Solar/Wind Harmer
1.167
972077AH1-588 GEN
Solar/Wind Harmer
12.921
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
5.007
970313AG2-206 GEN
Solar/Wind Harmer
1.911
20398826ARMNA MT
Solar/Wind Harmer
0.022
203859AF2-294 C
Solar/Wind Harmer
0.575
203963AG1-253 GEN
Solar/Wind Harmer
0.14
203848AF2-166 C
Solar/Wind Harmer
0.617
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.602
20390526W1-045 C
Solar/Wind Helper
0.177
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
MECLTFEXP_MEC->PJM
CLTF
0.47
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-0403-A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-0403-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:604.38
MW Contribution:1.44
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
40.468
20091326SHAW-D
50/50
1.612
20064926PENNTECH
50/50
0.404
200643SENECA#2
50/50
1.284
972169AH1-667 GEN
Solar/Wind Harmer
4.161
203954AE2-126 C
Solar/Wind Harmer
1.14
238183AE2-316 GEN
Solar/Wind Harmer
4.546
970713AG2-456 GEN
Solar/Wind Harmer
5.765
20066626SHAWVL 4
50/50
3.084
20066526SHAWVL 3
50/50
3.06
20071526SHAWVL 1
50/50
1.987
203952AE2-129 C
Solar/Wind Harmer
1.021
203946AE2-131 C
Solar/Wind Harmer
1.019
962411AG1-090 GEN
Solar/Wind Harmer
16.007
203853AF1-134 C O1
Solar/Wind Harmer
0.942
238217AF1-153 C O1
Solar/Wind Harmer
0.902
946381AF1-302 GEN
Solar/Wind Harmer
2.275
972075AH1-587 GEN
Solar/Wind Harmer
19.606
970305AG2-200 GEN
Solar/Wind Harmer
1.563
972077AH1-588 GEN
Solar/Wind Harmer
17.296
972079AH1-589 GEN
Solar/Wind Harmer
14.246
970715AG2-457 GEN
Solar/Wind Harmer
5.765
20398826ARMNA MT
Solar/Wind Harmer
1.068
970313AG2-206 GEN
Solar/Wind Harmer
2.177
203848AF2-166 C
Solar/Wind Harmer
0.86
20390526W1-045 C
Solar/Wind Helper
0.165
200642SENECA#1
50/50
1.377
203855AF2-088 C
Solar/Wind Harmer
0.455
965121AG1-377 GEN
Solar/Wind Harmer
3.37
20090526Q36
Solar/Wind Harmer
1.82
203993AD2-133_GEN1
Solar/Wind Harmer
1.82
203804AE2-113_GEN
Solar/Wind Harmer
5.193
940863AE2-074 GEN
Solar/Wind Harmer
1.159
970555AG2-356 GEN
Solar/Wind Harmer
0.971
970663AG2-429 GEN
Solar/Wind Harmer
2.99
970663AG2-429 GEN
Solar/Wind Harmer
0.487
203846AF2-130 C
Solar/Wind Harmer
0.246
20083926HOMER C3
Adder
18.661
20083826HOMER C2
Adder
17.628
20083726HOMER C1
Adder
10.193
203975AE1-071-GEN
Solar/Wind Helper
1.676
959381AF2-229 GEN
Solar/Wind Helper
0.168
200644SENECA#3
50/50
0.177
203854AF2-039 C
Solar/Wind Harmer
0.945
965131AG1-378 GEN
Solar/Wind Harmer
3.37
960051AF2-296 GEN
Solar/Wind Harmer
3.115
203818AF1-086 GEN
Solar/Wind Harmer
2.549
20120126WRREN CT
Adder
4.941
971703AH1-357 GEN
Solar/Wind Harmer
1.441
971707AH1-359 GEN
Solar/Wind Harmer
1.441
20335126GROZ1-110
Adder
1.405
20335226CANZ2-011
Adder
1.365
20334926Z1-069 C
Solar/Wind Harmer
1.237
941421AE2-139 GEN
Solar/Wind Harmer
1.55
970899AG2-561 GEN
Solar/Wind Harmer
1.011
945751AF1-240 GEN
Solar/Wind Harmer
0.746
238219AF1-167 C
Solar/Wind Harmer
0.624
972271AH1-720 GEN
Adder
3.025
970335AG2-220 GEN
Solar/Wind Harmer
1.406
971127AH1-005 GEN
Solar/Wind Harmer
0.907
203932AE1-123
Adder
0.886
944411AF1-106 GEN
Solar/Wind Harmer
0.1
20328326MANOR_T86
Adder
0.063
238202AE2-262_GEN
Solar/Wind Helper
3.164
971705AH1-358 GEN
Solar/Wind Harmer
1.676
971709AH1-360 GEN
Solar/Wind Harmer
1.676
20326126BLOSSBCT
Adder
1.208
203835AF1-098 GEN
Solar/Wind Harmer
1.178
959471AF2-238 GEN
Solar/Wind Harmer
0.294
970337AG2-221 GEN
Solar/Wind Harmer
0.971
20094526CT_V3-030
Solar/Wind Harmer
0.331
970511AG2-327 GEN
Solar/Wind Harmer
0.453
20335026MILZ1-092
Adder
1.007
944411AF1-106 GEN
Solar/Wind Harmer
0.928
238206AE2-263_GEN
Solar/Wind Helper
3.01
LGEELTFEXP_LGEE->PJM
CLTF
0.203
WECLTFEXP_WEC->PJM
CLTF
0.125
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.434
LAGNLTFEXP_LAGN->PJM
CLTF
0.438
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.152
TVALTFEXP_TVA->PJM
CLTF
0.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.308
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.852
MECLTFEXP_MEC->PJM
CLTF
0.507
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.95 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1312.71
MW Contribution:4.07
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
3.043
970631AG2-411 GEN
Solar/Wind Harmer
19.093
20088826HIGHLAND
Solar/Wind Harmer
4.899
957561AF2-050 GEN
Solar/Wind Harmer
14.764
971279AH1-102 GEN
Solar/Wind Harmer
23.731
971423AH1-203 GEN
Solar/Wind Harmer
19.36
20094526CT_V3-030
Solar/Wind Harmer
1.946
964201AG1-281 GEN
Solar/Wind Harmer
1.65
20089226LOOKOUT
Solar/Wind Harmer
1.955
203987AE2-118 C
Solar/Wind Harmer
4.298
970713AG2-456 GEN
Solar/Wind Harmer
16.27
971705AH1-358 GEN
Solar/Wind Harmer
4.73
971709AH1-360 GEN
Solar/Wind Harmer
4.73
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.319
20083026HNSMLK 3
Adder
10.319
20091326SHAW-D
Adder
1.146
972169AH1-667 GEN
Solar/Wind Harmer
3.136
203954AE2-126 C
Solar/Wind Harmer
1.044
20326126BLOSSBCT
Adder
3.822
20335026MILZ1-092
Adder
3.771
944411AF1-106 GEN
Solar/Wind Harmer
3.474
238183AE2-316 GEN
Solar/Wind Harmer
6.681
971183AH1-050 GEN
Solar/Wind Harmer
6.421
959471AF2-238 GEN
Solar/Wind Harmer
0.951
970337AG2-221 GEN
Solar/Wind Harmer
3.145
20072226SHAWVL 2
Adder
21.511
970647AG2-420 GEN
Solar/Wind Harmer
0.364
203860AG1-193 C
Solar/Wind Harmer
0.463
970511AG2-327 GEN
Solar/Wind Harmer
1.512
238206AE2-263_GEN
Solar/Wind Harmer
3.447
970267AG2-176 GEN
Solar/Wind Harmer
21.074
238215AE2-248 C
Solar/Wind Harmer
2.148
961971AG1-040 GEN
Solar/Wind Harmer
0.796
203835AF1-098 GEN
Solar/Wind Harmer
3.159
203813AE2-344_GEN
Solar/Wind Harmer
14.605
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.73
971865AH1-452 GEN
Solar/Wind Harmer
1.131
24035802GEN-Y1-012
Adder
0.244
20083726HOMER C1
50/50
274.812
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.267
20083926HOMER C3
50/50
227.884
20083826HOMER C2
50/50
215.262
20092526R32
Solar/Wind Harmer
5.249
203961AE2-224 GEN
Solar/Wind Harmer
8.943
203844AF2-092 C
Solar/Wind Harmer
3.471
203850AG1-041 C
Solar/Wind Harmer
3.468
20091526CHSTN_FL
Solar/Wind Harmer
2.312
20090526Q36
Solar/Wind Harmer
3.421
203993AD2-133_GEN1
Solar/Wind Harmer
3.421
940863AE2-074 GEN
Solar/Wind Harmer
3.497
941231AE2-117 GEN
Solar/Wind Harmer
1.21
965121AG1-377 GEN
Solar/Wind Harmer
3.983
203804AE2-113_GEN
Solar/Wind Harmer
9.118
20083226HNSMLK 5
Adder
10.319
203855AF2-088 C
Solar/Wind Harmer
0.343
203846AF2-130 C
Solar/Wind Harmer
0.929
970555AG2-356 GEN
Solar/Wind Harmer
3.145
970663AG2-429 GEN
Solar/Wind Harmer
10.588
970663AG2-429 GEN
Solar/Wind Harmer
1.724
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.253
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.597
971321AH1-140 GEN
Solar/Wind Harmer
14.986
971321AH1-140 GEN
Solar/Wind Harmer
2.904
20334726NME_Y1-047
Adder
2.332
20390726Y2-042
Adder
1.874
971055AG2-654 GEN
Solar/Wind Harmer
0.689
20080926SITHE
50/50
0.884
946071AF1-272 GEN
Solar/Wind Harmer
11.274
203857AF2-221 C
Solar/Wind Harmer
4.592
970123AG2-090 GEN
Solar/Wind Harmer
4.286
203839AF1-321 GEN
Solar/Wind Harmer
6.086
20084626FORWARD
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
1.422
971441AH1-212 GEN
Solar/Wind Harmer
5.714
20088626ARWF_N39
Solar/Wind Harmer
5.246
20303426NA_O38_P22
Solar/Wind Harmer
4.247
20088926STNY CRK
Solar/Wind Harmer
3.415
971427AH1-205 GEN
Solar/Wind Harmer
4.123
20083426SW_E13_K22
Solar/Wind Harmer
0.807
944781AF1-143 GEN
Solar/Wind Harmer
6.882
203853AF1-134 C O1
Solar/Wind Harmer
1.304
972077AH1-588 GEN
Solar/Wind Harmer
48.81
972079AH1-589 GEN
Solar/Wind Harmer
40.202
970715AG2-457 GEN
Solar/Wind Harmer
16.27
203952AE2-129 C
Solar/Wind Harmer
1.206
203946AE2-131 C
Solar/Wind Harmer
1.204
962411AG1-090 GEN
Solar/Wind Harmer
18.919
972075AH1-587 GEN
Solar/Wind Harmer
38.875
203955AF1-039 C O1
Solar/Wind Harmer
0.791
20398826ARMNA MT
Solar/Wind Harmer
3.933
203848AF2-166 C
Solar/Wind Harmer
3.252
946381AF1-302 GEN
Solar/Wind Harmer
3.343
238217AF1-153 C O1
Solar/Wind Harmer
0.955
970305AG2-200 GEN
Solar/Wind Harmer
3.134
203859AF2-294 C
Solar/Wind Harmer
2.597
970313AG2-206 GEN
Solar/Wind Harmer
7.257
216419AE2-001 C
Solar/Wind Harmer
2.715
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.657
203963AG1-253 GEN
Solar/Wind Harmer
0.513
971931AH1-490 GEN
Solar/Wind Harmer
2.512
203947AF1-006 C
Solar/Wind Harmer
0.664
20083326SEWRDB34
50/50
11.475
20216026CON.GEN2
50/50
0.034
970125AG2-091 GEN
Solar/Wind Harmer
1.837
971879AH1-460 GEN
Solar/Wind Harmer
20.153
20079426CONEMAGH
Adder
3.673
203841AF2-001_GEN
Solar/Wind Harmer
6.086
971541AH1-268 GEN
Solar/Wind Harmer
10.099
971419AH1-201 GEN
Solar/Wind Harmer
8.865
970899AG2-561 GEN
Solar/Wind Harmer
5.475
203818AF1-086 GEN
Solar/Wind Harmer
6.305
20089126CSLMN_L13
Solar/Wind Harmer
2.008
20089026BF_G21_K23
Solar/Wind Harmer
1.589
960051AF2-296 GEN
Solar/Wind Harmer
4.314
945751AF1-240 GEN
Solar/Wind Harmer
3.376
971703AH1-357 GEN
Solar/Wind Harmer
4.068
971707AH1-359 GEN
Solar/Wind Harmer
4.068
965131AG1-378 GEN
Solar/Wind Harmer
3.983
20334926Z1-069 C
Solar/Wind Harmer
4.096
20082926HNSMLK 2
Adder
10.319
20083126HNSMLK 4
Adder
10.319
203854AF2-039 C
Solar/Wind Harmer
0.712
202652Y1-033 WT C
Solar/Wind Harmer
1.626
203932AE1-123
Adder
3.315
944411AF1-106 GEN
Solar/Wind Harmer
0.373
971185AH1-051 GEN
Solar/Wind Harmer
3.853
971355AH1-158 GEN
Solar/Wind Harmer
4.48
203856AF2-165 C
Solar/Wind Harmer
1.87
20120126WRREN CT
Adder
9.907
970647AG2-420 GEN
Solar/Wind Harmer
3.129
970335AG2-220 GEN
Solar/Wind Harmer
4.71
971127AH1-005 GEN
Solar/Wind Harmer
3.038
959441AF2-235 GEN
Solar/Wind Harmer
0.45
238219AF1-167 C
Solar/Wind Harmer
1.972
238202AE2-262_GEN
Solar/Wind Harmer
3.699
971627AH1-313 GEN
Solar/Wind Harmer
14.502
20335126GROZ1-110
Adder
3.201
20335226CANZ2-011
Adder
3.111
957161AF2-010 GEN
Solar/Wind Harmer
10.289
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.336
203962AF1-287 GEN
Solar/Wind Harmer
2.519
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.532
972271AH1-720 GEN
Adder
7.499
200917MEHOOPANY_G
Solar/Wind Harmer
3.471
970679AG2-439 GEN
Solar/Wind Harmer
0.783
970643AG2-418 GEN
Solar/Wind Harmer
1.57
237043AE2-125 C
Solar/Wind Harmer
0.185
961581Q1080_CY23
External Queue
26.21918487548828
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.035
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.214
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.23
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.809
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.089
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:4.06
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:4.06
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.34
MW Contribution:4.1
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
280.069
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.263
20083926HOMER C3
50/50
231.8
20083826HOMER C2
50/50
218.961
20092526R32
Solar/Wind Harmer
4.991
203844AF2-092 C
Solar/Wind Harmer
3.326
203850AG1-041 C
Solar/Wind Harmer
3.319
203961AE2-224 GEN
Solar/Wind Harmer
8.313
20091526CHSTN_FL
Solar/Wind Harmer
2.196
20090526Q36
Solar/Wind Harmer
3.279
203993AD2-133_GEN1
Solar/Wind Harmer
3.279
940863AE2-074 GEN
Solar/Wind Harmer
3.529
965121AG1-377 GEN
Solar/Wind Harmer
3.847
203804AE2-113_GEN
Solar/Wind Harmer
9.139
941231AE2-117 GEN
Solar/Wind Harmer
1.142
20083226HNSMLK 5
Adder
10.453
203855AF2-088 C
Solar/Wind Harmer
0.335
203846AF2-130 C
Solar/Wind Harmer
0.927
970555AG2-356 GEN
Solar/Wind Harmer
3.171
970663AG2-429 GEN
Solar/Wind Harmer
10.629
970663AG2-429 GEN
Solar/Wind Harmer
1.73
970677AG2-438 GEN
Solar/Wind Harmer
1.337
966771AG1-548 GEN
Solar/Wind Harmer
19.376
966771AG1-548 GEN
Solar/Wind Harmer
3.755
20084926LAKVU GN
Adder
0.243
203926AA2-133 GEN
Adder
2.612
971321AH1-140 GEN
Solar/Wind Harmer
14.65
971321AH1-140 GEN
Solar/Wind Harmer
2.839
20334726NME_Y1-047
Adder
2.345
20390726Y2-042
Adder
1.882
971055AG2-654 GEN
Solar/Wind Harmer
0.697
203843AF2-002_GEN
Solar/Wind Harmer
2.948
970631AG2-411 GEN
Solar/Wind Harmer
18.493
20088826HIGHLAND
Solar/Wind Harmer
4.657
971279AH1-102 GEN
Solar/Wind Harmer
22.722
957561AF2-050 GEN
Solar/Wind Harmer
13.724
971423AH1-203 GEN
Solar/Wind Harmer
18.68
20094526CT_V3-030
Solar/Wind Harmer
1.866
964201AG1-281 GEN
Solar/Wind Harmer
1.565
20089226LOOKOUT
Solar/Wind Harmer
1.89
970713AG2-456 GEN
Solar/Wind Harmer
16.414
971705AH1-358 GEN
Solar/Wind Harmer
4.771
971709AH1-360 GEN
Solar/Wind Harmer
4.771
203987AE2-118 C
Solar/Wind Harmer
4.049
964391AG1-301 GEN
Solar/Wind Harmer
1.125
20082826HNSMLK 1
Adder
10.453
20083026HNSMLK 3
Adder
10.453
20091326SHAW-D
Adder
1.119
972169AH1-667 GEN
Solar/Wind Harmer
3.064
203954AE2-126 C
Solar/Wind Harmer
1.029
20326126BLOSSBCT
Adder
3.854
20335026MILZ1-092
Adder
3.809
944411AF1-106 GEN
Solar/Wind Harmer
3.509
971183AH1-050 GEN
Solar/Wind Harmer
6.429
959471AF2-238 GEN
Solar/Wind Harmer
0.959
970337AG2-221 GEN
Solar/Wind Harmer
3.171
238183AE2-316 GEN
Solar/Wind Harmer
6.666
970647AG2-420 GEN
Solar/Wind Harmer
0.365
20072226SHAWVL 2
Adder
21.096
203860AG1-193 C
Solar/Wind Harmer
0.466
970511AG2-327 GEN
Solar/Wind Harmer
1.525
238206AE2-263_GEN
Solar/Wind Harmer
3.375
970267AG2-176 GEN
Solar/Wind Harmer
21.271
961971AG1-040 GEN
Solar/Wind Harmer
0.803
203835AF1-098 GEN
Solar/Wind Harmer
3.183
238215AE2-248 C
Solar/Wind Harmer
2.088
203813AE2-344_GEN
Solar/Wind Harmer
14.741
20084926LAKVU GN
Adder
0.216
970643AG2-418 GEN
Solar/Wind Harmer
0.692
971865AH1-452 GEN
Solar/Wind Harmer
1.138
24035802GEN-Y1-012
Adder
0.247
20083326SEWRDB34
50/50
10.123
20216026CON.GEN2
50/50
0.033
203841AF2-001_GEN
Solar/Wind Harmer
5.897
971879AH1-460 GEN
Solar/Wind Harmer
19.409
970125AG2-091 GEN
Solar/Wind Harmer
1.761
20079426CONEMAGH
Adder
3.479
971541AH1-268 GEN
Solar/Wind Harmer
9.67
971419AH1-201 GEN
Solar/Wind Harmer
8.545
970899AG2-561 GEN
Solar/Wind Harmer
5.321
203818AF1-086 GEN
Solar/Wind Harmer
6.126
20089126CSLMN_L13
Solar/Wind Harmer
1.942
20089026BF_G21_K23
Solar/Wind Harmer
1.537
945751AF1-240 GEN
Solar/Wind Harmer
3.316
960051AF2-296 GEN
Solar/Wind Harmer
4.2
971703AH1-357 GEN
Solar/Wind Harmer
4.103
971707AH1-359 GEN
Solar/Wind Harmer
4.103
20334926Z1-069 C
Solar/Wind Harmer
4.137
965131AG1-378 GEN
Solar/Wind Harmer
3.847
20082926HNSMLK 2
Adder
10.453
20083126HNSMLK 4
Adder
10.453
203854AF2-039 C
Solar/Wind Harmer
0.696
202652Y1-033 WT C
Solar/Wind Harmer
1.572
203932AE1-123
Adder
3.3
944411AF1-106 GEN
Solar/Wind Harmer
0.377
971185AH1-051 GEN
Solar/Wind Harmer
3.857
971355AH1-158 GEN
Solar/Wind Harmer
4.485
20120126WRREN CT
Adder
9.95
203856AF2-165 C
Solar/Wind Harmer
1.872
970647AG2-420 GEN
Solar/Wind Harmer
3.136
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.065
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.975
238202AE2-262_GEN
Solar/Wind Harmer
3.621
971627AH1-313 GEN
Solar/Wind Harmer
14.197
20335126GROZ1-110
Adder
3.21
20335226CANZ2-011
Adder
3.12
957161AF2-010 GEN
Solar/Wind Harmer
10.35
203830AF1-094 GEN
Solar/Wind Harmer
0.81
203948AG1-140 C
Solar/Wind Harmer
0.339
203962AF1-287 GEN
Solar/Wind Harmer
2.542
962511AG1-100 GEN
Solar/Wind Harmer
0.767
20328326MANOR_T86
Adder
0.175
20084926LAKVU GN
Adder
0.216
941421AE2-139 GEN
Solar/Wind Harmer
3.541
972271AH1-720 GEN
Adder
7.526
200917MEHOOPANY_G
Solar/Wind Harmer
3.49
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.488
237043AE2-125 C
Solar/Wind Harmer
0.181
20080926SITHE
50/50
0.901
946071AF1-272 GEN
Solar/Wind Harmer
11.144
203839AF1-321 GEN
Solar/Wind Harmer
5.897
20084626FORWARD
Solar/Wind Harmer
2.32
203857AF2-221 C
Solar/Wind Harmer
4.403
970123AG2-090 GEN
Solar/Wind Harmer
4.109
203940AF1-140 C
Solar/Wind Harmer
1.353
971441AH1-212 GEN
Solar/Wind Harmer
5.415
20088926STNY CRK
Solar/Wind Harmer
3.291
971427AH1-205 GEN
Solar/Wind Harmer
3.974
20083426SW_E13_K22
Solar/Wind Harmer
0.78
20088626ARWF_N39
Solar/Wind Harmer
4.882
20303426NA_O38_P22
Solar/Wind Harmer
3.952
944781AF1-143 GEN
Solar/Wind Harmer
6.655
203853AF1-134 C O1
Solar/Wind Harmer
1.27
972077AH1-588 GEN
Solar/Wind Harmer
49.242
972079AH1-589 GEN
Solar/Wind Harmer
40.557
970715AG2-457 GEN
Solar/Wind Harmer
16.414
972075AH1-587 GEN
Solar/Wind Harmer
39.041
203952AE2-129 C
Solar/Wind Harmer
1.165
203946AE2-131 C
Solar/Wind Harmer
1.163
962411AG1-090 GEN
Solar/Wind Harmer
18.273
20398826ARMNA MT
Solar/Wind Harmer
3.972
203955AF1-039 C O1
Solar/Wind Harmer
0.765
203848AF2-166 C
Solar/Wind Harmer
3.246
946381AF1-302 GEN
Solar/Wind Harmer
3.336
970305AG2-200 GEN
Solar/Wind Harmer
3.147
238217AF1-153 C O1
Solar/Wind Harmer
0.946
203859AF2-294 C
Solar/Wind Harmer
2.624
970313AG2-206 GEN
Solar/Wind Harmer
7.319
203980AG1-197 GEN
Solar/Wind Harmer
0.61
203979AG1-198 GEN
Solar/Wind Harmer
0.486
971933AH1-491 GEN
Solar/Wind Harmer
2.673
216419AE2-001 C
Solar/Wind Harmer
2.642
203963AG1-253 GEN
Solar/Wind Harmer
0.517
971931AH1-490 GEN
Solar/Wind Harmer
2.536
203947AF1-006 C
Solar/Wind Harmer
0.67
961581Q1080_CY23
External Queue
26.921693801879883
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.097
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.268
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.139
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:4.03
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
961581Q1080_CY23
External Queue
18.789121627807617
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:4.03
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
961581Q1080_CY23
External Queue
18.789121627807617
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-033T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-033T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.79 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1085.77
MW Contribution:3.37
Bus #Bus NameTypeMW Contribution
20215826CON.GEN1
50/50
0.045
20083726HOMER C1
50/50
230.721
20063626IUP CO-G
50/50
0.254
20083926HOMER C3
50/50
190.005
20083826HOMER C2
50/50
179.482
20092526R32
Solar/Wind Harmer
4.149
203844AF2-092 C
Solar/Wind Harmer
2.774
203850AG1-041 C
Solar/Wind Harmer
2.767
203961AE2-224 GEN
Solar/Wind Harmer
6.702
20091526CHSTN_FL
Solar/Wind Harmer
1.829
20090526Q36
Solar/Wind Harmer
2.744
203993AD2-133_GEN1
Solar/Wind Harmer
2.744
940863AE2-074 GEN
Solar/Wind Harmer
2.907
965121AG1-377 GEN
Solar/Wind Harmer
3.23
203804AE2-113_GEN
Solar/Wind Harmer
7.536
941231AE2-117 GEN
Solar/Wind Harmer
0.948
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
8.406
203846AF2-130 C
Solar/Wind Harmer
0.762
970555AG2-356 GEN
Solar/Wind Harmer
2.649
970663AG2-429 GEN
Solar/Wind Harmer
8.45
970663AG2-429 GEN
Solar/Wind Harmer
1.376
970677AG2-438 GEN
Solar/Wind Harmer
1.077
966771AG1-548 GEN
Solar/Wind Harmer
15.594
966771AG1-548 GEN
Solar/Wind Harmer
3.022
20084926LAKVU GN
Adder
0.194
203926AA2-133 GEN
Adder
2.229
20334726NME_Y1-047
Adder
2.018
20390726Y2-042
Adder
1.652
20216026CON.GEN2
50/50
0.04
20079426CONEMAGH
50/50
3.164
20083326SEWRDB34
50/50
7.896
203841AF2-001_GEN
Solar/Wind Harmer
4.93
971879AH1-460 GEN
Solar/Wind Harmer
16.196
970125AG2-091 GEN
Solar/Wind Harmer
1.467
971541AH1-268 GEN
Solar/Wind Harmer
8.477
970899AG2-561 GEN
Solar/Wind Harmer
4.805
971419AH1-201 GEN
Solar/Wind Harmer
7.128
203818AF1-086 GEN
Solar/Wind Harmer
5.441
960051AF2-296 GEN
Solar/Wind Harmer
3.667
20089126CSLMN_L13
Solar/Wind Harmer
1.613
20089026BF_G21_K23
Solar/Wind Harmer
1.277
945751AF1-240 GEN
Solar/Wind Harmer
2.88
971703AH1-357 GEN
Solar/Wind Harmer
3.369
971707AH1-359 GEN
Solar/Wind Harmer
3.369
20334926Z1-069 C
Solar/Wind Harmer
3.414
965131AG1-378 GEN
Solar/Wind Harmer
3.23
203854AF2-039 C
Solar/Wind Harmer
0.588
20082926HNSMLK 2
Adder
8.406
20083126HNSMLK 4
Adder
8.406
944411AF1-106 GEN
Solar/Wind Harmer
0.314
202652Y1-033 WT C
Solar/Wind Harmer
1.296
203932AE1-123
Adder
2.724
971185AH1-051 GEN
Solar/Wind Harmer
3.15
971355AH1-158 GEN
Solar/Wind Harmer
3.662
20120126WRREN CT
Adder
8.111
970335AG2-220 GEN
Solar/Wind Harmer
3.975
971127AH1-005 GEN
Solar/Wind Harmer
2.565
203856AF2-165 C
Solar/Wind Harmer
1.528
970647AG2-420 GEN
Solar/Wind Harmer
2.555
959441AF2-235 GEN
Solar/Wind Harmer
0.367
238202AE2-262_GEN
Solar/Wind Harmer
3.041
971627AH1-313 GEN
Solar/Wind Harmer
11.922
238219AF1-167 C
Solar/Wind Harmer
1.571
20335126GROZ1-110
Adder
2.703
20335226CANZ2-011
Adder
2.627
957161AF2-010 GEN
Solar/Wind Harmer
8.34
203830AF1-094 GEN
Solar/Wind Harmer
0.652
20328326MANOR_T86
Adder
0.149
203948AG1-140 C
Solar/Wind Harmer
0.272
203962AF1-287 GEN
Solar/Wind Harmer
2.032
962511AG1-100 GEN
Solar/Wind Harmer
0.612
941421AE2-139 GEN
Solar/Wind Harmer
3.012
20084926LAKVU GN
Adder
0.172
972271AH1-720 GEN
Adder
6.411
200917MEHOOPANY_G
Solar/Wind Harmer
3.003
970679AG2-439 GEN
Solar/Wind Harmer
0.69
970643AG2-418 GEN
Solar/Wind Harmer
1.293
20080926SITHE
50/50
0.742
946071AF1-272 GEN
Solar/Wind Harmer
10.956
203839AF1-321 GEN
Solar/Wind Harmer
4.93
20084626FORWARD
Solar/Wind Harmer
1.939
203857AF2-221 C
Solar/Wind Harmer
3.668
970123AG2-090 GEN
Solar/Wind Harmer
3.424
203940AF1-140 C
Solar/Wind Harmer
1.128
971441AH1-212 GEN
Solar/Wind Harmer
4.542
20088926STNY CRK
Solar/Wind Harmer
2.745
971427AH1-205 GEN
Solar/Wind Harmer
3.315
20083426SW_E13_K22
Solar/Wind Harmer
0.651
20088626ARWF_N39
Solar/Wind Harmer
3.947
20303426NA_O38_P22
Solar/Wind Harmer
3.195
203853AF1-134 C O1
Solar/Wind Harmer
1.109
944781AF1-143 GEN
Solar/Wind Harmer
5.53
972077AH1-588 GEN
Solar/Wind Harmer
40.423
972079AH1-589 GEN
Solar/Wind Harmer
33.294
970715AG2-457 GEN
Solar/Wind Harmer
13.474
203952AE2-129 C
Solar/Wind Harmer
0.978
203946AE2-131 C
Solar/Wind Harmer
0.977
962411AG1-090 GEN
Solar/Wind Harmer
15.344
972075AH1-587 GEN
Solar/Wind Harmer
32.161
20398826ARMNA MT
Solar/Wind Harmer
3.307
203955AF1-039 C O1
Solar/Wind Harmer
0.631
203848AF2-166 C
Solar/Wind Harmer
2.666
238217AF1-153 C O1
Solar/Wind Harmer
0.781
203859AF2-294 C
Solar/Wind Harmer
2.193
970305AG2-200 GEN
Solar/Wind Harmer
2.566
946381AF1-302 GEN
Solar/Wind Harmer
2.696
970313AG2-206 GEN
Solar/Wind Harmer
6.127
216419AE2-001 C
Solar/Wind Harmer
2.228
20080526COLVER13
50/50
1.682
203843AF2-002_GEN
Solar/Wind Harmer
2.465
970631AG2-411 GEN
Solar/Wind Harmer
15.45
971279AH1-102 GEN
Solar/Wind Harmer
19.918
20088826HIGHLAND
Solar/Wind Harmer
3.872
20094526CT_V3-030
Solar/Wind Harmer
1.616
971423AH1-203 GEN
Solar/Wind Harmer
15.583
957561AF2-050 GEN
Solar/Wind Harmer
11.064
964201AG1-281 GEN
Solar/Wind Harmer
1.3
20089226LOOKOUT
Solar/Wind Harmer
1.571
970713AG2-456 GEN
Solar/Wind Harmer
13.474
971705AH1-358 GEN
Solar/Wind Harmer
3.917
971709AH1-360 GEN
Solar/Wind Harmer
3.917
203987AE2-118 C
Solar/Wind Harmer
3.348
964391AG1-301 GEN
Solar/Wind Harmer
0.933
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.587
20082826HNSMLK 1
Adder
8.406
20083026HNSMLK 3
Adder
8.406
203954AE2-126 C
Solar/Wind Harmer
0.861
20326126BLOSSBCT
Adder
3.21
20335026MILZ1-092
Adder
3.17
944411AF1-106 GEN
Solar/Wind Harmer
2.921
959471AF2-238 GEN
Solar/Wind Harmer
0.801
970337AG2-221 GEN
Solar/Wind Harmer
2.649
971183AH1-050 GEN
Solar/Wind Harmer
5.249
20072226SHAWVL 2
Adder
17.701
238183AE2-316 GEN
Solar/Wind Harmer
5.388
970647AG2-420 GEN
Solar/Wind Harmer
0.297
970511AG2-327 GEN
Solar/Wind Harmer
1.276
203860AG1-193 C
Solar/Wind Harmer
0.377
238206AE2-263_GEN
Solar/Wind Harmer
2.834
970267AG2-176 GEN
Solar/Wind Harmer
17.067
238215AE2-248 C
Solar/Wind Harmer
1.762
961971AG1-040 GEN
Solar/Wind Harmer
0.643
203835AF1-098 GEN
Solar/Wind Harmer
2.559
203813AE2-344_GEN
Solar/Wind Harmer
11.778
20084926LAKVU GN
Adder
0.172
970643AG2-418 GEN
Solar/Wind Harmer
0.601
24035802GEN-Y1-012
Adder
0.184
203979AG1-198 GEN
Solar/Wind Harmer
0.391
971933AH1-491 GEN
Solar/Wind Harmer
2.153
203980AG1-197 GEN
Solar/Wind Harmer
0.488
203963AG1-253 GEN
Solar/Wind Harmer
0.415
971931AH1-490 GEN
Solar/Wind Harmer
2.026
203947AF1-006 C
Solar/Wind Harmer
0.534
961581Q1080_CY23
External Queue
21.849340438842773
G-007ALTFEXP_G-007A->PJM
CMTX
0.44
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.307
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.563
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.217
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.677
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.982
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1082.93
MW Contribution:3.45
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.501
20079426CONEMAGH
50/50
2.811
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.608
971879AH1-460 GEN
Solar/Wind Harmer
15.111
970125AG2-091 GEN
Solar/Wind Harmer
1.367
971541AH1-268 GEN
Solar/Wind Harmer
7.445
971419AH1-201 GEN
Solar/Wind Harmer
6.65
970899AG2-561 GEN
Solar/Wind Harmer
4.158
203818AF1-086 GEN
Solar/Wind Harmer
4.785
971703AH1-357 GEN
Solar/Wind Harmer
3.452
971707AH1-359 GEN
Solar/Wind Harmer
3.452
20089126CSLMN_L13
Solar/Wind Harmer
1.509
20089026BF_G21_K23
Solar/Wind Harmer
1.195
20082926HNSMLK 2
Adder
9.882
20083126HNSMLK 4
Adder
9.882
20334926Z1-069 C
Solar/Wind Harmer
3.506
960051AF2-296 GEN
Solar/Wind Harmer
3.283
965131AG1-378 GEN
Solar/Wind Harmer
2.997
945751AF1-240 GEN
Solar/Wind Harmer
2.353
944411AF1-106 GEN
Solar/Wind Harmer
0.323
203854AF2-039 C
Solar/Wind Harmer
0.545
970335AG2-220 GEN
Solar/Wind Harmer
4.059
971127AH1-005 GEN
Solar/Wind Harmer
2.618
20120126WRREN CT
Adder
8.274
202652Y1-033 WT C
Solar/Wind Harmer
1.216
970647AG2-420 GEN
Solar/Wind Harmer
2.331
20335126GROZ1-110
Adder
2.708
20335226CANZ2-011
Adder
2.632
971185AH1-051 GEN
Solar/Wind Harmer
2.79
971355AH1-158 GEN
Solar/Wind Harmer
3.244
203856AF2-165 C
Solar/Wind Harmer
1.361
238202AE2-262_GEN
Solar/Wind Harmer
2.845
971627AH1-313 GEN
Solar/Wind Harmer
11.155
959441AF2-235 GEN
Solar/Wind Harmer
0.336
203948AG1-140 C
Solar/Wind Harmer
0.289
962511AG1-100 GEN
Solar/Wind Harmer
0.66
203962AF1-287 GEN
Solar/Wind Harmer
2.182
957161AF2-010 GEN
Solar/Wind Harmer
8.315
203830AF1-094 GEN
Solar/Wind Harmer
0.653
20328326MANOR_T86
Adder
0.15
20084926LAKVU GN
Adder
0.184
203932AE1-123
Adder
2.047
941421AE2-139 GEN
Solar/Wind Harmer
3.007
972271AH1-720 GEN
Adder
6.426
200917MEHOOPANY_G
Solar/Wind Harmer
3.022
238219AF1-167 C
Solar/Wind Harmer
0.965
970679AG2-439 GEN
Solar/Wind Harmer
0.69
970643AG2-418 GEN
Solar/Wind Harmer
1.201
20080926SITHE
50/50
0.735
946071AF1-272 GEN
Solar/Wind Harmer
9.451
203839AF1-321 GEN
Solar/Wind Harmer
4.608
20084626FORWARD
Solar/Wind Harmer
1.813
203857AF2-221 C
Solar/Wind Harmer
3.418
970123AG2-090 GEN
Solar/Wind Harmer
3.19
203940AF1-140 C
Solar/Wind Harmer
1.046
20088926STNY CRK
Solar/Wind Harmer
2.561
971427AH1-205 GEN
Solar/Wind Harmer
3.093
971441AH1-212 GEN
Solar/Wind Harmer
4.171
20083426SW_E13_K22
Solar/Wind Harmer
0.608
20088626ARWF_N39
Solar/Wind Harmer
3.759
20303426NA_O38_P22
Solar/Wind Harmer
3.043
972077AH1-588 GEN
Solar/Wind Harmer
41.421
972079AH1-589 GEN
Solar/Wind Harmer
34.116
970715AG2-457 GEN
Solar/Wind Harmer
13.807
944781AF1-143 GEN
Solar/Wind Harmer
5.173
203853AF1-134 C O1
Solar/Wind Harmer
0.993
972075AH1-587 GEN
Solar/Wind Harmer
32.353
203952AE2-129 C
Solar/Wind Harmer
0.908
203946AE2-131 C
Solar/Wind Harmer
0.906
962411AG1-090 GEN
Solar/Wind Harmer
14.236
20398826ARMNA MT
Solar/Wind Harmer
3.393
203859AF2-294 C
Solar/Wind Harmer
2.251
970305AG2-200 GEN
Solar/Wind Harmer
2.617
970313AG2-206 GEN
Solar/Wind Harmer
6.254
203955AF1-039 C O1
Solar/Wind Harmer
0.592
946381AF1-302 GEN
Solar/Wind Harmer
2.467
238217AF1-153 C O1
Solar/Wind Harmer
0.705
203980AG1-197 GEN
Solar/Wind Harmer
0.527
203963AG1-253 GEN
Solar/Wind Harmer
0.442
971931AH1-490 GEN
Solar/Wind Harmer
2.182
203848AF2-166 C
Solar/Wind Harmer
2.163
203979AG1-198 GEN
Solar/Wind Harmer
0.392
971933AH1-491 GEN
Solar/Wind Harmer
2.157
216419AE2-001 C
Solar/Wind Harmer
2.082
203947AF1-006 C
Solar/Wind Harmer
0.573
20083726HOMER C1
50/50
228.436
20215826CON.GEN1
50/50
0.038
20063626IUP CO-G
50/50
0.219
20083926HOMER C3
50/50
199.576
20083826HOMER C2
50/50
188.522
20050326C.SLOPE
50/50
0.687
20092526R32
Solar/Wind Harmer
3.855
203844AF2-092 C
Solar/Wind Harmer
2.582
203850AG1-041 C
Solar/Wind Harmer
2.574
203961AE2-224 GEN
Solar/Wind Harmer
6.392
20091526CHSTN_FL
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
2.979
20083226HNSMLK 5
Adder
9.882
20090526Q36
Solar/Wind Harmer
2.547
203993AD2-133_GEN1
Solar/Wind Harmer
2.547
203804AE2-113_GEN
Solar/Wind Harmer
7.523
965121AG1-377 GEN
Solar/Wind Harmer
2.997
941231AE2-117 GEN
Solar/Wind Harmer
0.888
970555AG2-356 GEN
Solar/Wind Harmer
2.703
203855AF2-088 C
Solar/Wind Harmer
0.262
203846AF2-130 C
Solar/Wind Harmer
0.618
970677AG2-438 GEN
Solar/Wind Harmer
1.078
966771AG1-548 GEN
Solar/Wind Harmer
15.723
966771AG1-548 GEN
Solar/Wind Harmer
3.047
20084926LAKVU GN
Adder
0.207
203926AA2-133 GEN
Adder
2.246
20334726NME_Y1-047
Adder
2.031
971321AH1-140 GEN
Solar/Wind Harmer
10.681
971321AH1-140 GEN
Solar/Wind Harmer
2.07
20390726Y2-042
Adder
1.652
970663AG2-429 GEN
Solar/Wind Harmer
4.712
970663AG2-429 GEN
Solar/Wind Harmer
0.767
203843AF2-002_GEN
Solar/Wind Harmer
2.304
970631AG2-411 GEN
Solar/Wind Harmer
14.452
20088826HIGHLAND
Solar/Wind Harmer
3.597
971279AH1-102 GEN
Solar/Wind Harmer
17.493
957561AF2-050 GEN
Solar/Wind Harmer
10.553
971423AH1-203 GEN
Solar/Wind Harmer
14.544
20094526CT_V3-030
Solar/Wind Harmer
1.447
964201AG1-281 GEN
Solar/Wind Harmer
1.21
970713AG2-456 GEN
Solar/Wind Harmer
13.807
971705AH1-358 GEN
Solar/Wind Harmer
4.014
971709AH1-360 GEN
Solar/Wind Harmer
4.014
20089226LOOKOUT
Solar/Wind Harmer
1.469
20082826HNSMLK 1
Adder
9.882
20083026HNSMLK 3
Adder
9.882
203987AE2-118 C
Solar/Wind Harmer
3.142
964391AG1-301 GEN
Solar/Wind Harmer
0.875
20326126BLOSSBCT
Adder
3.276
20335026MILZ1-092
Adder
3.257
944411AF1-106 GEN
Solar/Wind Harmer
3
959471AF2-238 GEN
Solar/Wind Harmer
0.817
970337AG2-221 GEN
Solar/Wind Harmer
2.703
203954AE2-126 C
Solar/Wind Harmer
0.814
20091326SHAW-D
Adder
0.876
972169AH1-667 GEN
Solar/Wind Harmer
2.399
970511AG2-327 GEN
Solar/Wind Harmer
1.303
203860AG1-193 C
Solar/Wind Harmer
0.379
970267AG2-176 GEN
Solar/Wind Harmer
18.45
20072226SHAWVL 2
Adder
16.516
238183AE2-316 GEN
Solar/Wind Harmer
4.93
970647AG2-420 GEN
Solar/Wind Harmer
0.271
971183AH1-050 GEN
Solar/Wind Harmer
4.649
961971AG1-040 GEN
Solar/Wind Harmer
0.694
238206AE2-263_GEN
Solar/Wind Harmer
2.652
203835AF1-098 GEN
Solar/Wind Harmer
2.694
203813AE2-344_GEN
Solar/Wind Harmer
12.663
20084926LAKVU GN
Adder
0.184
238215AE2-248 C
Solar/Wind Harmer
1.646
970643AG2-418 GEN
Solar/Wind Harmer
0.558
24035802GEN-Y1-012
Adder
0.206
961581Q1080_CY23
External Queue
23.519622802734375
G-007ALTFEXP_G-007A->PJM
CMTX
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.83
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.433
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.149
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.152
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.463
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.671
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1062.61
MW Contribution:3.28
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
223.712
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.225
20083926HOMER C3
50/50
185.007
20083826HOMER C2
50/50
174.761
20050326C.SLOPE
50/50
0.703
203844AF2-092 C
Solar/Wind Harmer
2.767
20092526R32
Solar/Wind Harmer
4.007
203850AG1-041 C
Solar/Wind Harmer
2.745
203961AE2-224 GEN
Solar/Wind Harmer
6.382
20091526CHSTN_FL
Solar/Wind Harmer
1.749
20090526Q36
Solar/Wind Harmer
2.618
203993AD2-133_GEN1
Solar/Wind Harmer
2.618
20079426CONEMAGH
50/50
2.866
20083326SEWRDB34
50/50
7.468
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.929
971879AH1-460 GEN
Solar/Wind Harmer
16.011
20089126CSLMN_L13
Solar/Wind Harmer
2.122
20089026BF_G21_K23
Solar/Wind Harmer
1.68
970125AG2-091 GEN
Solar/Wind Harmer
1.438
202652Y1-033 WT C
Solar/Wind Harmer
2.225
971419AH1-201 GEN
Solar/Wind Harmer
7.565
971541AH1-268 GEN
Solar/Wind Harmer
7.677
970899AG2-561 GEN
Solar/Wind Harmer
4.351
203818AF1-086 GEN
Solar/Wind Harmer
4.985
945751AF1-240 GEN
Solar/Wind Harmer
2.685
960051AF2-296 GEN
Solar/Wind Harmer
3.403
971703AH1-357 GEN
Solar/Wind Harmer
3.277
971707AH1-359 GEN
Solar/Wind Harmer
3.277
20334926Z1-069 C
Solar/Wind Harmer
3.316
965131AG1-378 GEN
Solar/Wind Harmer
3.08
20082926HNSMLK 2
Adder
8.288
20083126HNSMLK 4
Adder
8.288
203854AF2-039 C
Solar/Wind Harmer
0.56
944411AF1-106 GEN
Solar/Wind Harmer
0.304
203932AE1-123
Adder
2.638
971185AH1-051 GEN
Solar/Wind Harmer
3.071
971355AH1-158 GEN
Solar/Wind Harmer
3.571
20120126WRREN CT
Adder
7.914
203856AF2-165 C
Solar/Wind Harmer
1.49
970647AG2-420 GEN
Solar/Wind Harmer
2.494
970335AG2-220 GEN
Solar/Wind Harmer
3.845
971127AH1-005 GEN
Solar/Wind Harmer
2.481
959441AF2-235 GEN
Solar/Wind Harmer
0.358
238219AF1-167 C
Solar/Wind Harmer
1.568
238202AE2-262_GEN
Solar/Wind Harmer
2.913
971627AH1-313 GEN
Solar/Wind Harmer
11.421
20335126GROZ1-110
Adder
2.606
20335226CANZ2-011
Adder
2.533
957161AF2-010 GEN
Solar/Wind Harmer
8.186
203830AF1-094 GEN
Solar/Wind Harmer
0.64
203948AG1-140 C
Solar/Wind Harmer
0.267
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.003
962511AG1-100 GEN
Solar/Wind Harmer
0.604
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.897
972271AH1-720 GEN
Adder
6.165
200917MEHOOPANY_G
Solar/Wind Harmer
2.882
970679AG2-439 GEN
Solar/Wind Harmer
0.659
970643AG2-418 GEN
Solar/Wind Harmer
1.212
20081326YOUGH
50/50
0.092
203843AF2-002_GEN
Solar/Wind Harmer
2.465
970631AG2-411 GEN
Solar/Wind Harmer
15.449
20089226LOOKOUT
Solar/Wind Harmer
2.066
971423AH1-203 GEN
Solar/Wind Harmer
16.774
20088826HIGHLAND
Solar/Wind Harmer
3.74
971279AH1-102 GEN
Solar/Wind Harmer
18.04
957561AF2-050 GEN
Solar/Wind Harmer
10.536
20094526CT_V3-030
Solar/Wind Harmer
1.499
964201AG1-281 GEN
Solar/Wind Harmer
1.255
970713AG2-456 GEN
Solar/Wind Harmer
13.107
971705AH1-358 GEN
Solar/Wind Harmer
3.81
971709AH1-360 GEN
Solar/Wind Harmer
3.81
203987AE2-118 C
Solar/Wind Harmer
3.189
964391AG1-301 GEN
Solar/Wind Harmer
0.888
20082826HNSMLK 1
Adder
8.288
20083026HNSMLK 3
Adder
8.288
20091326SHAW-D
Adder
0.9
972169AH1-667 GEN
Solar/Wind Harmer
2.463
203954AE2-126 C
Solar/Wind Harmer
0.826
20326126BLOSSBCT
Adder
3.108
20335026MILZ1-092
Adder
3.072
944411AF1-106 GEN
Solar/Wind Harmer
2.83
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.563
971183AH1-050 GEN
Solar/Wind Harmer
5.118
238183AE2-316 GEN
Solar/Wind Harmer
5.316
970647AG2-420 GEN
Solar/Wind Harmer
0.29
20072226SHAWVL 2
Adder
16.955
970511AG2-327 GEN
Solar/Wind Harmer
1.234
203860AG1-193 C
Solar/Wind Harmer
0.37
238206AE2-263_GEN
Solar/Wind Harmer
2.715
970267AG2-176 GEN
Solar/Wind Harmer
16.811
238215AE2-248 C
Solar/Wind Harmer
1.682
961971AG1-040 GEN
Solar/Wind Harmer
0.634
203835AF1-098 GEN
Solar/Wind Harmer
2.515
203813AE2-344_GEN
Solar/Wind Harmer
11.616
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.873
24035802GEN-Y1-012
Adder
0.187
20080926SITHE
50/50
0.719
20084126DEEPCRK2
50/50
0.151
20084026DEEPCRK1
50/50
0.149
946071AF1-272 GEN
Solar/Wind Harmer
9.629
203839AF1-321 GEN
Solar/Wind Harmer
4.929
20084626FORWARD
Solar/Wind Harmer
1.938
20083426SW_E13_K22
Solar/Wind Harmer
0.722
944781AF1-143 GEN
Solar/Wind Harmer
7.273
203857AF2-221 C
Solar/Wind Harmer
3.595
970123AG2-090 GEN
Solar/Wind Harmer
3.356
203955AF1-039 C O1
Solar/Wind Harmer
1.083
971427AH1-205 GEN
Solar/Wind Harmer
3.518
20088926STNY CRK
Solar/Wind Harmer
2.909
203940AF1-140 C
Solar/Wind Harmer
1.095
971441AH1-212 GEN
Solar/Wind Harmer
4.287
20088626ARWF_N39
Solar/Wind Harmer
3.758
20303426NA_O38_P22
Solar/Wind Harmer
3.042
203853AF1-134 C O1
Solar/Wind Harmer
1.029
972077AH1-588 GEN
Solar/Wind Harmer
39.32
972079AH1-589 GEN
Solar/Wind Harmer
32.386
970715AG2-457 GEN
Solar/Wind Harmer
13.107
972075AH1-587 GEN
Solar/Wind Harmer
31.212
203952AE2-129 C
Solar/Wind Harmer
0.933
203946AE2-131 C
Solar/Wind Harmer
0.931
962411AG1-090 GEN
Solar/Wind Harmer
14.63
20398826ARMNA MT
Solar/Wind Harmer
3.204
203848AF2-166 C
Solar/Wind Harmer
2.59
946381AF1-302 GEN
Solar/Wind Harmer
2.66
238217AF1-153 C O1
Solar/Wind Harmer
0.758
970305AG2-200 GEN
Solar/Wind Harmer
2.503
203859AF2-294 C
Solar/Wind Harmer
2.123
970313AG2-206 GEN
Solar/Wind Harmer
5.926
216419AE2-001 C
Solar/Wind Harmer
2.128
203980AG1-197 GEN
Solar/Wind Harmer
0.481
203979AG1-198 GEN
Solar/Wind Harmer
0.384
971933AH1-491 GEN
Solar/Wind Harmer
2.114
203963AG1-253 GEN
Solar/Wind Harmer
0.408
971931AH1-490 GEN
Solar/Wind Harmer
1.998
203947AF1-006 C
Solar/Wind Harmer
0.527
940863AE2-074 GEN
Solar/Wind Harmer
2.824
965121AG1-377 GEN
Solar/Wind Harmer
3.08
203804AE2-113_GEN
Solar/Wind Harmer
7.308
941231AE2-117 GEN
Solar/Wind Harmer
0.902
20083226HNSMLK 5
Adder
8.288
203855AF2-088 C
Solar/Wind Harmer
0.269
203846AF2-130 C
Solar/Wind Harmer
0.74
970555AG2-356 GEN
Solar/Wind Harmer
2.563
970663AG2-429 GEN
Solar/Wind Harmer
8.44
970663AG2-429 GEN
Solar/Wind Harmer
1.374
970677AG2-438 GEN
Solar/Wind Harmer
1.057
966771AG1-548 GEN
Solar/Wind Harmer
15.316
966771AG1-548 GEN
Solar/Wind Harmer
2.968
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.144
20334726NME_Y1-047
Adder
1.937
971321AH1-140 GEN
Solar/Wind Harmer
11.795
971321AH1-140 GEN
Solar/Wind Harmer
2.286
20390726Y2-042
Adder
1.578
961581Q1080_CY23
External Queue
21.336383819580078
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.865
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.164
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.693
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-036_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-036_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1058.48
MW Contribution:3.28
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.925
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20092526R32
Solar/Wind Harmer
3.878
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
971321AH1-140 GEN
Solar/Wind Harmer
26.397
971321AH1-140 GEN
Solar/Wind Harmer
5.116
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.355
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
961581Q1080_CY23
External Queue
21.315889358520508
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.82 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1056.6
MW Contribution:3.4
Bus #Bus NameTypeMW Contribution
20080526COLVER13
50/50
1.527
203843AF2-002_GEN
Solar/Wind Harmer
2.272
970631AG2-411 GEN
Solar/Wind Harmer
14.256
20088826HIGHLAND
Solar/Wind Harmer
3.558
971279AH1-102 GEN
Solar/Wind Harmer
17.777
957561AF2-050 GEN
Solar/Wind Harmer
10.408
20094526CT_V3-030
Solar/Wind Harmer
1.478
971423AH1-203 GEN
Solar/Wind Harmer
14.36
964201AG1-281 GEN
Solar/Wind Harmer
1.202
970713AG2-456 GEN
Solar/Wind Harmer
13.583
971705AH1-358 GEN
Solar/Wind Harmer
3.949
971709AH1-360 GEN
Solar/Wind Harmer
3.949
20089226LOOKOUT
Solar/Wind Harmer
1.449
203987AE2-118 C
Solar/Wind Harmer
3.141
20082826HNSMLK 1
Adder
8.956
20083026HNSMLK 3
Adder
8.956
964391AG1-301 GEN
Solar/Wind Harmer
0.878
238183AE2-316 GEN
Solar/Wind Harmer
6.048
203954AE2-126 C
Solar/Wind Harmer
0.858
20091326SHAW-D
Adder
0.927
972169AH1-667 GEN
Solar/Wind Harmer
2.536
20326126BLOSSBCT
Adder
3.208
971183AH1-050 GEN
Solar/Wind Harmer
5.635
20335026MILZ1-092
Adder
3.169
944411AF1-106 GEN
Solar/Wind Harmer
2.919
970647AG2-420 GEN
Solar/Wind Harmer
0.318
203860AG1-193 C
Solar/Wind Harmer
0.403
959471AF2-238 GEN
Solar/Wind Harmer
0.8
970337AG2-221 GEN
Solar/Wind Harmer
2.645
20072226SHAWVL 2
Adder
17.649
970511AG2-327 GEN
Solar/Wind Harmer
1.274
970267AG2-176 GEN
Solar/Wind Harmer
18.122
238206AE2-263_GEN
Solar/Wind Harmer
2.826
961971AG1-040 GEN
Solar/Wind Harmer
0.68
203835AF1-098 GEN
Solar/Wind Harmer
2.664
238215AE2-248 C
Solar/Wind Harmer
1.738
203813AE2-344_GEN
Solar/Wind Harmer
12.418
20084926LAKVU GN
Adder
0.18
970643AG2-418 GEN
Solar/Wind Harmer
0.572
971865AH1-452 GEN
Solar/Wind Harmer
1.032
24035802GEN-Y1-012
Adder
0.198
20080926SITHE
50/50
0.719
946071AF1-272 GEN
Solar/Wind Harmer
9.57
203839AF1-321 GEN
Solar/Wind Harmer
4.544
20084626FORWARD
Solar/Wind Harmer
1.789
203857AF2-221 C
Solar/Wind Harmer
3.373
970123AG2-090 GEN
Solar/Wind Harmer
3.149
203940AF1-140 C
Solar/Wind Harmer
1.038
971441AH1-212 GEN
Solar/Wind Harmer
4.156
20088926STNY CRK
Solar/Wind Harmer
2.53
971427AH1-205 GEN
Solar/Wind Harmer
3.055
20083426SW_E13_K22
Solar/Wind Harmer
0.6
20088626ARWF_N39
Solar/Wind Harmer
3.713
20303426NA_O38_P22
Solar/Wind Harmer
3.005
203853AF1-134 C O1
Solar/Wind Harmer
1.044
972077AH1-588 GEN
Solar/Wind Harmer
40.749
972079AH1-589 GEN
Solar/Wind Harmer
33.563
970715AG2-457 GEN
Solar/Wind Harmer
13.583
944781AF1-143 GEN
Solar/Wind Harmer
5.102
972075AH1-587 GEN
Solar/Wind Harmer
32.43
203952AE2-129 C
Solar/Wind Harmer
0.939
203946AE2-131 C
Solar/Wind Harmer
0.938
962411AG1-090 GEN
Solar/Wind Harmer
14.732
946381AF1-302 GEN
Solar/Wind Harmer
3.026
203848AF2-166 C
Solar/Wind Harmer
2.871
20398826ARMNA MT
Solar/Wind Harmer
3.303
238217AF1-153 C O1
Solar/Wind Harmer
0.814
970305AG2-200 GEN
Solar/Wind Harmer
2.629
203859AF2-294 C
Solar/Wind Harmer
2.19
203955AF1-039 C O1
Solar/Wind Harmer
0.584
970313AG2-206 GEN
Solar/Wind Harmer
6.115
203980AG1-197 GEN
Solar/Wind Harmer
0.517
203979AG1-198 GEN
Solar/Wind Harmer
0.413
971933AH1-491 GEN
Solar/Wind Harmer
2.274
216419AE2-001 C
Solar/Wind Harmer
2.202
203963AG1-253 GEN
Solar/Wind Harmer
0.432
971931AH1-490 GEN
Solar/Wind Harmer
2.138
203947AF1-006 C
Solar/Wind Harmer
0.561
20083726HOMER C1
50/50
223.475
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.224
20083926HOMER C3
50/50
189.284
20083826HOMER C2
50/50
178.8
20092526R32
Solar/Wind Harmer
3.812
203844AF2-092 C
Solar/Wind Harmer
2.555
203850AG1-041 C
Solar/Wind Harmer
2.548
203961AE2-224 GEN
Solar/Wind Harmer
6.304
20091526CHSTN_FL
Solar/Wind Harmer
1.696
940863AE2-074 GEN
Solar/Wind Harmer
2.921
20090526Q36
Solar/Wind Harmer
2.597
203993AD2-133_GEN1
Solar/Wind Harmer
2.597
203804AE2-113_GEN
Solar/Wind Harmer
7.605
965121AG1-377 GEN
Solar/Wind Harmer
3.102
20083226HNSMLK 5
Adder
8.956
941231AE2-117 GEN
Solar/Wind Harmer
0.892
970663AG2-429 GEN
Solar/Wind Harmer
10.063
970663AG2-429 GEN
Solar/Wind Harmer
1.638
203846AF2-130 C
Solar/Wind Harmer
0.82
203855AF2-088 C
Solar/Wind Harmer
0.277
970555AG2-356 GEN
Solar/Wind Harmer
2.645
970677AG2-438 GEN
Solar/Wind Harmer
1.137
966771AG1-548 GEN
Solar/Wind Harmer
16.455
966771AG1-548 GEN
Solar/Wind Harmer
3.189
20084926LAKVU GN
Adder
0.203
203926AA2-133 GEN
Adder
2.216
20334726NME_Y1-047
Adder
2.003
971321AH1-140 GEN
Solar/Wind Harmer
10.527
971321AH1-140 GEN
Solar/Wind Harmer
2.04
20390726Y2-042
Adder
1.633
971055AG2-654 GEN
Solar/Wind Harmer
0.739
20083326SEWRDB34
50/50
7.372
20079426CONEMAGH
50/50
2.786
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.544
971879AH1-460 GEN
Solar/Wind Harmer
14.908
970125AG2-091 GEN
Solar/Wind Harmer
1.349
970899AG2-561 GEN
Solar/Wind Harmer
4.363
971541AH1-268 GEN
Solar/Wind Harmer
7.566
971419AH1-201 GEN
Solar/Wind Harmer
6.568
203818AF1-086 GEN
Solar/Wind Harmer
5.016
945751AF1-240 GEN
Solar/Wind Harmer
2.826
960051AF2-296 GEN
Solar/Wind Harmer
3.452
971703AH1-357 GEN
Solar/Wind Harmer
3.396
971707AH1-359 GEN
Solar/Wind Harmer
3.396
20089126CSLMN_L13
Solar/Wind Harmer
1.489
20089026BF_G21_K23
Solar/Wind Harmer
1.178
20334926Z1-069 C
Solar/Wind Harmer
3.425
965131AG1-378 GEN
Solar/Wind Harmer
3.102
20082926HNSMLK 2
Adder
8.956
20083126HNSMLK 4
Adder
8.956
203932AE1-123
Adder
2.943
203854AF2-039 C
Solar/Wind Harmer
0.576
971185AH1-051 GEN
Solar/Wind Harmer
3.381
971355AH1-158 GEN
Solar/Wind Harmer
3.931
944411AF1-106 GEN
Solar/Wind Harmer
0.314
238219AF1-167 C
Solar/Wind Harmer
1.869
203856AF2-165 C
Solar/Wind Harmer
1.638
970647AG2-420 GEN
Solar/Wind Harmer
2.739
20120126WRREN CT
Adder
8.311
959441AF2-235 GEN
Solar/Wind Harmer
0.392
202652Y1-033 WT C
Solar/Wind Harmer
1.199
970335AG2-220 GEN
Solar/Wind Harmer
3.968
971127AH1-005 GEN
Solar/Wind Harmer
2.56
238202AE2-262_GEN
Solar/Wind Harmer
3.032
971627AH1-313 GEN
Solar/Wind Harmer
11.888
20335126GROZ1-110
Adder
2.697
20335226CANZ2-011
Adder
2.622
957161AF2-010 GEN
Solar/Wind Harmer
8.813
203830AF1-094 GEN
Solar/Wind Harmer
0.689
203948AG1-140 C
Solar/Wind Harmer
0.283
203962AF1-287 GEN
Solar/Wind Harmer
2.142
962511AG1-100 GEN
Solar/Wind Harmer
0.646
20328326MANOR_T86
Adder
0.148
20084926LAKVU GN
Adder
0.18
941421AE2-139 GEN
Solar/Wind Harmer
2.999
972271AH1-720 GEN
Adder
6.38
200917MEHOOPANY_G
Solar/Wind Harmer
2.981
970679AG2-439 GEN
Solar/Wind Harmer
0.682
970643AG2-418 GEN
Solar/Wind Harmer
1.229
961581Q1080_CY23
External Queue
21.48957061767578
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
CBM NorthLTFEXP_CBM-N->PJM
CBM
29.854
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.154
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.476
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.691
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-083_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-083_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.56 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1034.46
MW Contribution:3.28
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.926
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.356
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20092526R32
Solar/Wind Harmer
3.878
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
21.315900802612305
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.65
MW Contribution:2.83
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.147
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.63
MW Contribution:2.83
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.147
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-8I_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-8I_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:178.33 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:285.32
MW Contribution:2.53
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
2.53
971707AH1-359 GEN
Solar/Wind Harmer
2.53
20334926Z1-069 C
Solar/Wind Harmer
2.104
203854AF2-039 C
Solar/Wind Helper
0.265
238202AE2-262_GEN
Solar/Wind Helper
0.69
970713AG2-456 GEN
Solar/Wind Harmer
10.118
971705AH1-358 GEN
Solar/Wind Harmer
2.941
971709AH1-360 GEN
Solar/Wind Harmer
2.941
203954AE2-126 C
Solar/Wind Helper
0.708
238206AE2-263_GEN
Solar/Wind Helper
0.656
203804AE2-113_GEN
Solar/Wind Harmer
18.98
940863AE2-074 GEN
Solar/Wind Harmer
2.326
20083926HOMER C3
Adder
14.327
20083826HOMER C2
Adder
13.534
20083726HOMER C1
Adder
6.168
203855AF2-088 C
Solar/Wind Helper
0.127
972075AH1-587 GEN
Solar/Wind Harmer
65.567
972077AH1-588 GEN
Solar/Wind Harmer
30.354
972079AH1-589 GEN
Solar/Wind Harmer
25.001
970715AG2-457 GEN
Solar/Wind Harmer
10.118
238217AF1-153 C O1
Solar/Wind Helper
0.212
203952AE2-129 C
Solar/Wind Helper
0.296
203946AE2-131 C
Solar/Wind Helper
0.296
946381AF1-302 GEN
Solar/Wind Helper
0.132
203853AF1-134 C O1
Solar/Wind Helper
0.254
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.036
CPLELTFEXP_CPLE->PJM
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.091
LAGNLTFEXP_LAGN->PJM
CLTF
0.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
TVALTFEXP_TVA->PJM
CLTF
0.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.285
MECLTFEXP_MEC->PJM
CLTF
0.151
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:178.33 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:285.32
MW Contribution:2.53
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
65.567
972077AH1-588 GEN
Solar/Wind Harmer
30.354
972079AH1-589 GEN
Solar/Wind Harmer
25.001
970715AG2-457 GEN
Solar/Wind Harmer
10.118
238217AF1-153 C O1
Solar/Wind Helper
0.212
203952AE2-129 C
Solar/Wind Helper
0.296
203946AE2-131 C
Solar/Wind Helper
0.296
946381AF1-302 GEN
Solar/Wind Helper
0.132
203853AF1-134 C O1
Solar/Wind Helper
0.254
203804AE2-113_GEN
Solar/Wind Harmer
18.98
940863AE2-074 GEN
Solar/Wind Harmer
2.326
20083926HOMER C3
Adder
14.327
20083826HOMER C2
Adder
13.534
20083726HOMER C1
Adder
6.168
203855AF2-088 C
Solar/Wind Helper
0.127
971703AH1-357 GEN
Solar/Wind Harmer
2.53
971707AH1-359 GEN
Solar/Wind Harmer
2.53
20334926Z1-069 C
Solar/Wind Harmer
2.104
203854AF2-039 C
Solar/Wind Helper
0.265
238202AE2-262_GEN
Solar/Wind Helper
0.69
970713AG2-456 GEN
Solar/Wind Harmer
10.118
971705AH1-358 GEN
Solar/Wind Harmer
2.941
971709AH1-360 GEN
Solar/Wind Harmer
2.941
203954AE2-126 C
Solar/Wind Helper
0.708
238206AE2-263_GEN
Solar/Wind Helper
0.656
CPLELTFEXP_CPLE->PJM
CLTF
0.034
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.036
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.091
LAGNLTFEXP_LAGN->PJM
CLTF
0.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
TVALTFEXP_TVA->PJM
CLTF
0.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.285
MECLTFEXP_MEC->PJM
CLTF
0.151
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1185-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1185-2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.57 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:250.51
MW Contribution:3.02
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
75.952
972077AH1-588 GEN
Solar/Wind Harmer
36.242
972079AH1-589 GEN
Solar/Wind Harmer
29.85
970715AG2-457 GEN
Solar/Wind Harmer
12.081
203804AE2-113_GEN
Solar/Wind Harmer
21.67
940863AE2-074 GEN
Solar/Wind Harmer
2.809
971703AH1-357 GEN
Solar/Wind Harmer
3.02
971707AH1-359 GEN
Solar/Wind Harmer
3.02
20334926Z1-069 C
Solar/Wind Harmer
2.383
970713AG2-456 GEN
Solar/Wind Harmer
12.081
971705AH1-358 GEN
Solar/Wind Harmer
3.512
971709AH1-360 GEN
Solar/Wind Harmer
3.512
203954AE2-126 C
Solar/Wind Helper
0.413
LGEELTFEXP_LGEE->PJM
CLTF
0.025
WECLTFEXP_WEC->PJM
CLTF
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.002
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.527
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
0.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.102
MECLTFEXP_MEC->PJM
CLTF
0.066
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-006_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-006_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.24 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:224.38
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.132
20120126WRREN CT
50/50
3.799
971703AH1-357 GEN
Solar/Wind Harmer
1.363
971707AH1-359 GEN
Solar/Wind Harmer
1.363
20334926Z1-069 C
Solar/Wind Harmer
0.448
203854AF2-039 C
Solar/Wind Helper
0.28
238202AE2-262_GEN
Solar/Wind Helper
0.734
972075AH1-587 GEN
Solar/Wind Harmer
43.238
972077AH1-588 GEN
Solar/Wind Harmer
16.354
972079AH1-589 GEN
Solar/Wind Harmer
19.307
970715AG2-457 GEN
Solar/Wind Harmer
6.337
970305AG2-200 GEN
Solar/Wind Harmer
0.79
238217AF1-153 C O1
Solar/Wind Helper
0.224
203952AE2-129 C
Solar/Wind Helper
0.316
203946AE2-131 C
Solar/Wind Helper
0.316
946381AF1-302 GEN
Solar/Wind Helper
0.14
203853AF1-134 C O1
Solar/Wind Helper
0.271
200642SENECA#1
50/50
1.024
203804AE2-113_GEN
Solar/Wind Harmer
0.02
20083926HOMER C3
Adder
11.362
20083826HOMER C2
Adder
10.732
20083726HOMER C1
Adder
4.266
203855AF2-088 C
Solar/Wind Helper
0.135
20090526Q36
Solar/Wind Helper
0.516
203993AD2-133_GEN1
Solar/Wind Helper
0.516
200643SENECA#2
50/50
0.956
970713AG2-456 GEN
Solar/Wind Harmer
6.337
971705AH1-358 GEN
Solar/Wind Harmer
2.271
971709AH1-360 GEN
Solar/Wind Harmer
2.271
203954AE2-126 C
Solar/Wind Helper
0.741
238206AE2-263_GEN
Solar/Wind Helper
0.698
LGEELTFEXP_LGEE->PJM
CLTF
0.09
WECLTFEXP_WEC->PJM
CLTF
0.055
CPLELTFEXP_CPLE->PJM
CLTF
0.043
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.617
LAGNLTFEXP_LAGN->PJM
CLTF
0.219
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.418
MECLTFEXP_MEC->PJM
CLTF
0.227
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P2-2_PN-115-064_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-064_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.9 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:214.24
MW Contribution:1.45
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
63.854
972077AH1-588 GEN
Solar/Wind Harmer
17.344
972079AH1-589 GEN
Solar/Wind Harmer
14.285
970715AG2-457 GEN
Solar/Wind Harmer
5.781
238217AF1-153 C O1
Solar/Wind Helper
0.117
203804AE2-113_GEN
Solar/Wind Harmer
19.034
940863AE2-074 GEN
Solar/Wind Harmer
2.349
20083926HOMER C3
Adder
9.057
20083826HOMER C2
Adder
8.555
20083726HOMER C1
Adder
3.94
203855AF2-088 C
Solar/Wind Helper
0.081
20334926Z1-069 C
Solar/Wind Harmer
2.818
971703AH1-357 GEN
Solar/Wind Harmer
1.445
971707AH1-359 GEN
Solar/Wind Harmer
1.445
203854AF2-039 C
Solar/Wind Helper
0.169
970713AG2-456 GEN
Solar/Wind Harmer
5.781
971705AH1-358 GEN
Solar/Wind Harmer
1.681
971709AH1-360 GEN
Solar/Wind Harmer
1.681
203954AE2-126 C
Solar/Wind Helper
0.534
LGEELTFEXP_LGEE->PJM
CLTF
0.036
WECLTFEXP_WEC->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.647
LAGNLTFEXP_LAGN->PJM
CLTF
0.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.076
TVALTFEXP_TVA->PJM
CLTF
0.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.889
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.169
MECLTFEXP_MEC->PJM
CLTF
0.09
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-028_SRT-A-1


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-028_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:213.14
MW Contribution:1.83
Bus #Bus NameTypeMW Contribution
970713AG2-456 GEN
Solar/Wind Harmer
8.534
971705AH1-358 GEN
Solar/Wind Harmer
3.059
971709AH1-360 GEN
Solar/Wind Harmer
3.059
203954AE2-126 C
Solar/Wind Helper
0.589
238206AE2-263_GEN
Solar/Wind Helper
0.475
971703AH1-357 GEN
Solar/Wind Harmer
1.835
971707AH1-359 GEN
Solar/Wind Harmer
1.835
20334926Z1-069 C
Solar/Wind Harmer
0.554
203854AF2-039 C
Solar/Wind Helper
0.201
238202AE2-262_GEN
Solar/Wind Helper
0.499
972075AH1-587 GEN
Solar/Wind Harmer
47.648
972077AH1-588 GEN
Solar/Wind Harmer
22.023
972079AH1-589 GEN
Solar/Wind Harmer
26
970715AG2-457 GEN
Solar/Wind Harmer
8.534
238217AF1-153 C O1
Solar/Wind Helper
0.154
203952AE2-129 C
Solar/Wind Helper
0.221
203946AE2-131 C
Solar/Wind Helper
0.222
203804AE2-113_GEN
Solar/Wind Harmer
0.022
20083926HOMER C3
Adder
15.197
20083826HOMER C2
Adder
14.355
20083726HOMER C1
Adder
7.28
203855AF2-088 C
Solar/Wind Helper
0.097
G-007ALTFEXP_G-007A->PJM
CMTX
0.038
LGEELTFEXP_LGEE->PJM
CLTF
0.01
WECLTFEXP_WEC->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.891
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.182
VTFLTFEXP_VFT->PJM
CMTX
0.14
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.041
TVALTFEXP_TVA->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.053
MECLTFEXP_MEC->PJM
CLTF
0.022
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:129.36 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:206.97
MW Contribution:1.33
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
62.39
972077AH1-588 GEN
Solar/Wind Harmer
16.017
972079AH1-589 GEN
Solar/Wind Harmer
13.192
970715AG2-457 GEN
Solar/Wind Harmer
5.339
238217AF1-153 C O1
Solar/Wind Helper
0.121
970713AG2-456 GEN
Solar/Wind Harmer
5.339
971705AH1-358 GEN
Solar/Wind Harmer
1.552
971709AH1-360 GEN
Solar/Wind Harmer
1.552
203954AE2-126 C
Solar/Wind Helper
0.545
203804AE2-113_GEN
Solar/Wind Harmer
18.723
940863AE2-074 GEN
Solar/Wind Harmer
1.741
20083926HOMER C3
Adder
8.813
20083826HOMER C2
Adder
8.325
20083726HOMER C1
Adder
3.741
203855AF2-088 C
Solar/Wind Helper
0.083
20334926Z1-069 C
Solar/Wind Harmer
1.559
971703AH1-357 GEN
Solar/Wind Harmer
1.335
971707AH1-359 GEN
Solar/Wind Harmer
1.335
203854AF2-039 C
Solar/Wind Helper
0.173
CPLELTFEXP_CPLE->PJM
CLTF
0.015
LGEELTFEXP_LGEE->PJM
CLTF
0.035
WECLTFEXP_WEC->PJM
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.635
LAGNLTFEXP_LAGN->PJM
CLTF
0.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.063
TVALTFEXP_TVA->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.009
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.161
MECLTFEXP_MEC->PJM
CLTF
0.092
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.79 %
Rating:133.0 MVA
Rating Type:A
MVA to Mitigate:155.34
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
43.547
972077AH1-588 GEN
Solar/Wind Harmer
11.199
972079AH1-589 GEN
Solar/Wind Harmer
13.22
970715AG2-457 GEN
Solar/Wind Harmer
4.339
238217AF1-153 C O1
Solar/Wind Helper
0.121
203804AE2-113_GEN
Solar/Wind Harmer
0.021
20083926HOMER C3
Adder
8.904
20083826HOMER C2
Adder
8.411
20083726HOMER C1
Adder
3.82
203855AF2-088 C
Solar/Wind Helper
0.083
20334926Z1-069 C
Solar/Wind Harmer
0.391
971703AH1-357 GEN
Solar/Wind Harmer
0.933
971707AH1-359 GEN
Solar/Wind Harmer
0.933
203854AF2-039 C
Solar/Wind Helper
0.173
970713AG2-456 GEN
Solar/Wind Harmer
4.339
971705AH1-358 GEN
Solar/Wind Harmer
1.555
971709AH1-360 GEN
Solar/Wind Harmer
1.555
203954AE2-126 C
Solar/Wind Helper
0.545
LGEELTFEXP_LGEE->PJM
CLTF
0.029
WECLTFEXP_WEC->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.014
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.515
LAGNLTFEXP_LAGN->PJM
CLTF
0.07
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.056
TVALTFEXP_TVA->PJM
CLTF
0.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.72
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.134
MECLTFEXP_MEC->PJM
CLTF
0.072
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-703T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-703T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.08 %
Rating:688.0 MVA
Rating Type:B
MVA to Mitigate:729.82
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.485
203855AF2-088 C
Solar/Wind Harmer
0.348
965121AG1-377 GEN
Solar/Wind Harmer
2.534
203804AE2-113_GEN
Solar/Wind Harmer
5.386
20090526Q36
Solar/Wind Harmer
1.33
203993AD2-133_GEN1
Solar/Wind Harmer
1.33
940863AE2-074 GEN
Solar/Wind Harmer
1.286
970555AG2-356 GEN
Solar/Wind Harmer
1.351
203926AA2-133 GEN
Adder
1.359
20334726NME_Y1-047
Adder
1.19
970663AG2-429 GEN
Solar/Wind Harmer
3.113
970663AG2-429 GEN
Solar/Wind Harmer
0.507
20084926LAKVU GN
Adder
0.086
203846AF2-130 C
Solar/Wind Harmer
0.249
966771AG1-548 GEN
Solar/Wind Harmer
6.302
966771AG1-548 GEN
Solar/Wind Harmer
1.221
970677AG2-438 GEN
Solar/Wind Harmer
0.431
20083926HOMER C3
Adder
19.199
20083826HOMER C2
Adder
18.136
20083726HOMER C1
Adder
9.292
203975AE1-071-GEN
Solar/Wind Helper
1.804
959381AF2-229 GEN
Solar/Wind Helper
0.181
200644SENECA#3
50/50
0.191
20335126GROZ1-110
50/50
2.25
20335226CANZ2-011
50/50
2.187
238202AE2-262_GEN
Solar/Wind Harmer
8.708
971627AH1-313 GEN
Solar/Wind Harmer
34.144
203854AF2-039 C
Solar/Wind Harmer
0.723
965131AG1-378 GEN
Solar/Wind Harmer
2.534
960051AF2-296 GEN
Solar/Wind Harmer
2.402
20120126WRREN CT
Adder
5.321
941421AE2-139 GEN
Solar/Wind Harmer
2.377
203818AF1-086 GEN
Solar/Wind Harmer
1.99
971703AH1-357 GEN
Solar/Wind Harmer
1.555
971707AH1-359 GEN
Solar/Wind Harmer
1.555
972271AH1-720 GEN
Adder
4.591
20334926Z1-069 C
Solar/Wind Harmer
1.428
20328326MANOR_T86
Adder
0.092
970335AG2-220 GEN
Solar/Wind Harmer
1.947
971127AH1-005 GEN
Solar/Wind Harmer
1.256
944411AF1-106 GEN
Solar/Wind Harmer
0.132
200917MEHOOPANY_G
Solar/Wind Harmer
1.771
238219AF1-167 C
Solar/Wind Harmer
0.651
203932AE1-123
Adder
0.889
203948AG1-140 C
Solar/Wind Harmer
0.118
20084926LAKVU GN
Adder
0.077
945751AF1-240 GEN
Solar/Wind Harmer
0.683
203830AF1-094 GEN
Solar/Wind Harmer
0.261
957161AF2-010 GEN
Solar/Wind Harmer
3.314
20072226SHAWVL 2
50/50
30.333
20091326SHAW-D
50/50
1.234
20064926PENNTECH
50/50
0.41
200643SENECA#2
50/50
1.385
238206AE2-263_GEN
Solar/Wind Harmer
8.116
972169AH1-667 GEN
Solar/Wind Harmer
3.185
203954AE2-126 C
Solar/Wind Harmer
0.989
238183AE2-316 GEN
Solar/Wind Harmer
4.969
970713AG2-456 GEN
Solar/Wind Harmer
6.218
971705AH1-358 GEN
Solar/Wind Harmer
1.808
971709AH1-360 GEN
Solar/Wind Harmer
1.808
20326126BLOSSBCT
Adder
1.654
959471AF2-238 GEN
Solar/Wind Harmer
0.408
970337AG2-221 GEN
Solar/Wind Harmer
1.351
970511AG2-327 GEN
Solar/Wind Harmer
0.629
20335026MILZ1-092
Adder
1.333
944411AF1-106 GEN
Solar/Wind Harmer
1.228
203835AF1-098 GEN
Solar/Wind Harmer
1.26
20084926LAKVU GN
Adder
0.077
964391AG1-301 GEN
Solar/Wind Helper
0.25
20066526SHAWVL 3
50/50
2.314
20066626SHAWVL 4
50/50
2.311
20071526SHAWVL 1
50/50
1.511
238217AF1-153 C O1
Solar/Wind Harmer
0.993
203952AE2-129 C
Solar/Wind Harmer
0.767
203946AE2-131 C
Solar/Wind Harmer
0.766
962411AG1-090 GEN
Solar/Wind Harmer
12.035
203853AF1-134 C O1
Solar/Wind Harmer
0.726
946381AF1-302 GEN
Solar/Wind Harmer
2.487
972075AH1-587 GEN
Solar/Wind Harmer
20.489
970305AG2-200 GEN
Solar/Wind Harmer
1.683
972077AH1-588 GEN
Solar/Wind Harmer
18.655
972079AH1-589 GEN
Solar/Wind Harmer
15.365
970715AG2-457 GEN
Solar/Wind Harmer
6.218
970313AG2-206 GEN
Solar/Wind Harmer
3.018
20398826ARMNA MT
Solar/Wind Harmer
1.421
203859AF2-294 C
Solar/Wind Harmer
0.894
203963AG1-253 GEN
Solar/Wind Harmer
0.18
203848AF2-166 C
Solar/Wind Harmer
0.87
203979AG1-198 GEN
Solar/Wind Harmer
0.157
971933AH1-491 GEN
Solar/Wind Harmer
0.862
20390526W1-045 C
Solar/Wind Helper
0.178
LGEELTFEXP_LGEE->PJM
CLTF
0.178
WECLTFEXP_WEC->PJM
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.195
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.914
LAGNLTFEXP_LAGN->PJM
CLTF
0.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.014
TVALTFEXP_TVA->PJM
CLTF
0.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.818
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.701
MECLTFEXP_MEC->PJM
CLTF
0.445
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line l/o AP_P2-2_WP-230-006T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-006T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.73 %
Rating:688.0 MVA
Rating Type:B
MVA to Mitigate:727.43
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.19
20335126GROZ1-110
50/50
2.247
20335226CANZ2-011
50/50
2.184
238202AE2-262_GEN
Solar/Wind Harmer
8.698
971627AH1-313 GEN
Solar/Wind Harmer
34.106
203854AF2-039 C
Solar/Wind Harmer
0.722
965131AG1-378 GEN
Solar/Wind Harmer
2.531
960051AF2-296 GEN
Solar/Wind Harmer
2.399
20120126WRREN CT
Adder
5.316
941421AE2-139 GEN
Solar/Wind Harmer
2.375
203818AF1-086 GEN
Solar/Wind Harmer
1.988
971703AH1-357 GEN
Solar/Wind Harmer
1.553
971707AH1-359 GEN
Solar/Wind Harmer
1.553
972271AH1-720 GEN
Adder
4.586
20334926Z1-069 C
Solar/Wind Harmer
1.426
20328326MANOR_T86
Adder
0.092
970335AG2-220 GEN
Solar/Wind Harmer
1.945
20066526SHAWVL 3
50/50
2.312
20066626SHAWVL 4
50/50
2.309
20071526SHAWVL 1
50/50
1.509
238217AF1-153 C O1
Solar/Wind Harmer
0.992
203952AE2-129 C
Solar/Wind Harmer
0.766
203946AE2-131 C
Solar/Wind Harmer
0.765
962411AG1-090 GEN
Solar/Wind Harmer
12.021
203853AF1-134 C O1
Solar/Wind Harmer
0.725
946381AF1-302 GEN
Solar/Wind Harmer
2.484
972075AH1-587 GEN
Solar/Wind Harmer
20.466
970305AG2-200 GEN
Solar/Wind Harmer
1.681
972077AH1-588 GEN
Solar/Wind Harmer
18.634
972079AH1-589 GEN
Solar/Wind Harmer
15.348
970715AG2-457 GEN
Solar/Wind Harmer
6.211
970313AG2-206 GEN
Solar/Wind Harmer
3.015
20398826ARMNA MT
Solar/Wind Harmer
1.42
203859AF2-294 C
Solar/Wind Harmer
0.893
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203848AF2-166 C
Solar/Wind Harmer
0.869
203979AG1-198 GEN
Solar/Wind Harmer
0.156
971933AH1-491 GEN
Solar/Wind Harmer
0.861
20390526W1-045 C
Solar/Wind Helper
0.178
200642SENECA#1
50/50
1.483
203855AF2-088 C
Solar/Wind Harmer
0.348
965121AG1-377 GEN
Solar/Wind Harmer
2.531
203804AE2-113_GEN
Solar/Wind Harmer
5.38
20090526Q36
Solar/Wind Harmer
1.328
203993AD2-133_GEN1
Solar/Wind Harmer
1.328
940863AE2-074 GEN
Solar/Wind Harmer
1.284
970555AG2-356 GEN
Solar/Wind Harmer
1.349
203926AA2-133 GEN
Adder
1.358
20334726NME_Y1-047
Adder
1.188
970663AG2-429 GEN
Solar/Wind Harmer
3.11
970663AG2-429 GEN
Solar/Wind Harmer
0.506
20084926LAKVU GN
Adder
0.086
203846AF2-130 C
Solar/Wind Harmer
0.248
966771AG1-548 GEN
Solar/Wind Harmer
6.295
966771AG1-548 GEN
Solar/Wind Harmer
1.22
970677AG2-438 GEN
Solar/Wind Harmer
0.43
20083926HOMER C3
Adder
19.178
20083826HOMER C2
Adder
18.115
20083726HOMER C1
Adder
9.281
203975AE1-071-GEN
Solar/Wind Helper
1.802
959381AF2-229 GEN
Solar/Wind Helper
0.181
20072226SHAWVL 2
50/50
30.299
20091326SHAW-D
50/50
1.233
20064926PENNTECH
50/50
0.41
200643SENECA#2
50/50
1.384
238206AE2-263_GEN
Solar/Wind Harmer
8.107
972169AH1-667 GEN
Solar/Wind Harmer
3.181
203954AE2-126 C
Solar/Wind Harmer
0.988
238183AE2-316 GEN
Solar/Wind Harmer
4.964
970713AG2-456 GEN
Solar/Wind Harmer
6.211
971705AH1-358 GEN
Solar/Wind Harmer
1.806
971709AH1-360 GEN
Solar/Wind Harmer
1.806
20326126BLOSSBCT
Adder
1.652
959471AF2-238 GEN
Solar/Wind Harmer
0.408
971127AH1-005 GEN
Solar/Wind Harmer
1.255
944411AF1-106 GEN
Solar/Wind Harmer
0.132
200917MEHOOPANY_G
Solar/Wind Harmer
1.769
238219AF1-167 C
Solar/Wind Harmer
0.651
203932AE1-123
Adder
0.888
203948AG1-140 C
Solar/Wind Harmer
0.118
20084926LAKVU GN
Adder
0.076
945751AF1-240 GEN
Solar/Wind Harmer
0.682
203830AF1-094 GEN
Solar/Wind Harmer
0.261
970337AG2-221 GEN
Solar/Wind Harmer
1.349
970511AG2-327 GEN
Solar/Wind Harmer
0.628
20335026MILZ1-092
Adder
1.332
944411AF1-106 GEN
Solar/Wind Harmer
1.227
203835AF1-098 GEN
Solar/Wind Harmer
1.259
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.25
LGEELTFEXP_LGEE->PJM
CLTF
0.177
WECLTFEXP_WEC->PJM
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.911
LAGNLTFEXP_LAGN->PJM
CLTF
0.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.014
TVALTFEXP_TVA->PJM
CLTF
0.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.7
MECLTFEXP_MEC->PJM
CLTF
0.445
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line l/o AP_P2-3_WP-230-459T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
AE2-262_TAP-01MILESB 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-230-459T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.73 %
Rating:688.0 MVA
Rating Type:B
MVA to Mitigate:727.39
MW Contribution:1.55
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.19
20335126GROZ1-110
50/50
2.247
20335226CANZ2-011
50/50
2.184
238202AE2-262_GEN
Solar/Wind Harmer
8.698
971627AH1-313 GEN
Solar/Wind Harmer
34.106
203854AF2-039 C
Solar/Wind Harmer
0.722
965131AG1-378 GEN
Solar/Wind Harmer
2.531
960051AF2-296 GEN
Solar/Wind Harmer
2.399
20120126WRREN CT
Adder
5.316
941421AE2-139 GEN
Solar/Wind Harmer
2.375
203818AF1-086 GEN
Solar/Wind Harmer
1.988
971703AH1-357 GEN
Solar/Wind Harmer
1.553
971707AH1-359 GEN
Solar/Wind Harmer
1.553
972271AH1-720 GEN
Adder
4.586
20334926Z1-069 C
Solar/Wind Harmer
1.426
20328326MANOR_T86
Adder
0.092
970335AG2-220 GEN
Solar/Wind Harmer
1.945
971127AH1-005 GEN
Solar/Wind Harmer
1.255
944411AF1-106 GEN
Solar/Wind Harmer
0.132
200917MEHOOPANY_G
Solar/Wind Harmer
1.769
238219AF1-167 C
Solar/Wind Harmer
0.651
203932AE1-123
Adder
0.888
203948AG1-140 C
Solar/Wind Harmer
0.118
20084926LAKVU GN
Adder
0.076
945751AF1-240 GEN
Solar/Wind Harmer
0.682
203830AF1-094 GEN
Solar/Wind Harmer
0.261
20066526SHAWVL 3
50/50
2.312
20066626SHAWVL 4
50/50
2.309
20071526SHAWVL 1
50/50
1.509
238217AF1-153 C O1
Solar/Wind Harmer
0.992
203952AE2-129 C
Solar/Wind Harmer
0.766
203946AE2-131 C
Solar/Wind Harmer
0.765
962411AG1-090 GEN
Solar/Wind Harmer
12.021
203853AF1-134 C O1
Solar/Wind Harmer
0.725
946381AF1-302 GEN
Solar/Wind Harmer
2.484
972075AH1-587 GEN
Solar/Wind Harmer
20.466
970305AG2-200 GEN
Solar/Wind Harmer
1.681
972077AH1-588 GEN
Solar/Wind Harmer
18.634
972079AH1-589 GEN
Solar/Wind Harmer
15.348
970715AG2-457 GEN
Solar/Wind Harmer
6.211
970313AG2-206 GEN
Solar/Wind Harmer
3.015
20398826ARMNA MT
Solar/Wind Harmer
1.42
203859AF2-294 C
Solar/Wind Harmer
0.893
203963AG1-253 GEN
Solar/Wind Harmer
0.179
203848AF2-166 C
Solar/Wind Harmer
0.869
203979AG1-198 GEN
Solar/Wind Harmer
0.156
971933AH1-491 GEN
Solar/Wind Harmer
0.861
20390526W1-045 C
Solar/Wind Helper
0.178
20072226SHAWVL 2
50/50
30.299
20091326SHAW-D
50/50
1.233
20064926PENNTECH
50/50
0.41
200643SENECA#2
50/50
1.384
238206AE2-263_GEN
Solar/Wind Harmer
8.107
972169AH1-667 GEN
Solar/Wind Harmer
3.181
203954AE2-126 C
Solar/Wind Harmer
0.988
238183AE2-316 GEN
Solar/Wind Harmer
4.964
970713AG2-456 GEN
Solar/Wind Harmer
6.211
971705AH1-358 GEN
Solar/Wind Harmer
1.806
971709AH1-360 GEN
Solar/Wind Harmer
1.806
20326126BLOSSBCT
Adder
1.652
959471AF2-238 GEN
Solar/Wind Harmer
0.408
970337AG2-221 GEN
Solar/Wind Harmer
1.349
970511AG2-327 GEN
Solar/Wind Harmer
0.628
20335026MILZ1-092
Adder
1.332
944411AF1-106 GEN
Solar/Wind Harmer
1.227
203835AF1-098 GEN
Solar/Wind Harmer
1.259
20084926LAKVU GN
Adder
0.076
964391AG1-301 GEN
Solar/Wind Helper
0.25
200642SENECA#1
50/50
1.483
203855AF2-088 C
Solar/Wind Harmer
0.348
965121AG1-377 GEN
Solar/Wind Harmer
2.531
203804AE2-113_GEN
Solar/Wind Harmer
5.38
20090526Q36
Solar/Wind Harmer
1.328
203993AD2-133_GEN1
Solar/Wind Harmer
1.328
940863AE2-074 GEN
Solar/Wind Harmer
1.284
970555AG2-356 GEN
Solar/Wind Harmer
1.349
203926AA2-133 GEN
Adder
1.358
20334726NME_Y1-047
Adder
1.188
970663AG2-429 GEN
Solar/Wind Harmer
3.11
970663AG2-429 GEN
Solar/Wind Harmer
0.506
20084926LAKVU GN
Adder
0.086
203846AF2-130 C
Solar/Wind Harmer
0.248
966771AG1-548 GEN
Solar/Wind Harmer
6.295
966771AG1-548 GEN
Solar/Wind Harmer
1.22
970677AG2-438 GEN
Solar/Wind Harmer
0.43
20083926HOMER C3
Adder
19.178
20083826HOMER C2
Adder
18.115
20083726HOMER C1
Adder
9.281
203975AE1-071-GEN
Solar/Wind Helper
1.802
959381AF2-229 GEN
Solar/Wind Helper
0.181
LGEELTFEXP_LGEE->PJM
CLTF
0.177
WECLTFEXP_WEC->PJM
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.911
LAGNLTFEXP_LAGN->PJM
CLTF
0.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.014
TVALTFEXP_TVA->PJM
CLTF
0.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.7
MECLTFEXP_MEC->PJM
CLTF
0.445
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-8I_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-8I_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.8 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:202.87
MW Contribution:2.54
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
65.63
972077AH1-588 GEN
Solar/Wind Harmer
30.43
972079AH1-589 GEN
Solar/Wind Harmer
25.063
970715AG2-457 GEN
Solar/Wind Harmer
10.143
238217AF1-153 C O1
Solar/Wind Helper
0.212
203952AE2-129 C
Solar/Wind Helper
0.294
203946AE2-131 C
Solar/Wind Helper
0.295
946381AF1-302 GEN
Solar/Wind Helper
0.132
203853AF1-134 C O1
Solar/Wind Helper
0.252
940863AE2-074 GEN
Solar/Wind Harmer
2.332
20083926HOMER C3
Adder
14.551
20083826HOMER C2
Adder
13.745
20083726HOMER C1
Adder
6.382
203804AE2-113_GEN
Solar/Wind Helper
8.787
203855AF2-088 C
Solar/Wind Helper
0.127
971703AH1-357 GEN
Solar/Wind Harmer
2.536
971707AH1-359 GEN
Solar/Wind Harmer
2.536
20334926Z1-069 C
Solar/Wind Harmer
2.111
203854AF2-039 C
Solar/Wind Helper
0.264
238202AE2-262_GEN
Solar/Wind Helper
0.686
970713AG2-456 GEN
Solar/Wind Harmer
10.143
971705AH1-358 GEN
Solar/Wind Harmer
2.949
971709AH1-360 GEN
Solar/Wind Harmer
2.949
203954AE2-126 C
Solar/Wind Helper
0.706
238206AE2-263_GEN
Solar/Wind Helper
0.653
LGEELTFEXP_LGEE->PJM
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.048
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.516
LAGNLTFEXP_LAGN->PJM
CLTF
0.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.226
TVALTFEXP_TVA->PJM
CLTF
0.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.405
MECLTFEXP_MEC->PJM
CLTF
0.204
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.8 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:202.87
MW Contribution:2.54
Bus #Bus NameTypeMW Contribution
972075AH1-587 GEN
Solar/Wind Harmer
65.63
972077AH1-588 GEN
Solar/Wind Harmer
30.43
972079AH1-589 GEN
Solar/Wind Harmer
25.063
970715AG2-457 GEN
Solar/Wind Harmer
10.143
238217AF1-153 C O1
Solar/Wind Helper
0.212
203952AE2-129 C
Solar/Wind Helper
0.294
203946AE2-131 C
Solar/Wind Helper
0.295
946381AF1-302 GEN
Solar/Wind Helper
0.132
203853AF1-134 C O1
Solar/Wind Helper
0.252
940863AE2-074 GEN
Solar/Wind Harmer
2.332
20083926HOMER C3
Adder
14.551
20083826HOMER C2
Adder
13.745
20083726HOMER C1
Adder
6.382
203804AE2-113_GEN
Solar/Wind Helper
8.787
203855AF2-088 C
Solar/Wind Helper
0.127
971703AH1-357 GEN
Solar/Wind Harmer
2.536
971707AH1-359 GEN
Solar/Wind Harmer
2.536
20334926Z1-069 C
Solar/Wind Harmer
2.111
203854AF2-039 C
Solar/Wind Helper
0.264
238202AE2-262_GEN
Solar/Wind Helper
0.686
970713AG2-456 GEN
Solar/Wind Harmer
10.143
971705AH1-358 GEN
Solar/Wind Harmer
2.949
971709AH1-360 GEN
Solar/Wind Harmer
2.949
203954AE2-126 C
Solar/Wind Helper
0.706
238206AE2-263_GEN
Solar/Wind Helper
0.653
CPLELTFEXP_CPLE->PJM
CLTF
0.069
LGEELTFEXP_LGEE->PJM
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.048
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.516
LAGNLTFEXP_LAGN->PJM
CLTF
0.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.226
TVALTFEXP_TVA->PJM
CLTF
0.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.405
MECLTFEXP_MEC->PJM
CLTF
0.204
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-39C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-39C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:196.92
MW Contribution:2.64
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
2.637
971707AH1-359 GEN
Solar/Wind Harmer
2.637
20334926Z1-069 C
Solar/Wind Harmer
2.219
203854AF2-039 C
Solar/Wind Helper
0.2
238202AE2-262_GEN
Solar/Wind Helper
0.496
940863AE2-074 GEN
Solar/Wind Harmer
2.436
20083926HOMER C3
Adder
15.421
20083826HOMER C2
Adder
14.567
20083726HOMER C1
Adder
7.494
203804AE2-113_GEN
Solar/Wind Helper
8.475
203855AF2-088 C
Solar/Wind Helper
0.096
970713AG2-456 GEN
Solar/Wind Harmer
10.547
971705AH1-358 GEN
Solar/Wind Harmer
3.066
971709AH1-360 GEN
Solar/Wind Harmer
3.066
203954AE2-126 C
Solar/Wind Helper
0.587
238206AE2-263_GEN
Solar/Wind Helper
0.471
972075AH1-587 GEN
Solar/Wind Harmer
68.359
972077AH1-588 GEN
Solar/Wind Harmer
31.642
972079AH1-589 GEN
Solar/Wind Harmer
26.062
970715AG2-457 GEN
Solar/Wind Harmer
10.547
238217AF1-153 C O1
Solar/Wind Helper
0.153
G-007ALTFEXP_G-007A->PJM
CMTX
0.126
LGEELTFEXP_LGEE->PJM
CLTF
0.031
WECLTFEXP_WEC->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
0.049
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.607
VTFLTFEXP_VFT->PJM
CMTX
0.376
LAGNLTFEXP_LAGN->PJM
CLTF
0.092
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.136
TVALTFEXP_TVA->PJM
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.61
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.075
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1185-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1185-2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.12 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:176.19
MW Contribution:3.03
Bus #Bus NameTypeMW Contribution
940863AE2-074 GEN
Solar/Wind Harmer
2.815
203804AE2-113_GEN
Solar/Wind Helper
7.729
971703AH1-357 GEN
Solar/Wind Harmer
3.026
971707AH1-359 GEN
Solar/Wind Harmer
3.026
20334926Z1-069 C
Solar/Wind Harmer
2.389
972075AH1-587 GEN
Solar/Wind Harmer
76.015
972077AH1-588 GEN
Solar/Wind Harmer
36.317
972079AH1-589 GEN
Solar/Wind Harmer
29.913
970715AG2-457 GEN
Solar/Wind Harmer
12.106
970713AG2-456 GEN
Solar/Wind Harmer
12.106
971705AH1-358 GEN
Solar/Wind Harmer
3.519
971709AH1-360 GEN
Solar/Wind Harmer
3.519
203954AE2-126 C
Solar/Wind Helper
0.411
CPLELTFEXP_CPLE->PJM
CLTF
0.027
LGEELTFEXP_LGEE->PJM
CLTF
0.047
WECLTFEXP_WEC->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.854
LAGNLTFEXP_LAGN->PJM
CLTF
0.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.101
TVALTFEXP_TVA->PJM
CLTF
0.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.222
MECLTFEXP_MEC->PJM
CLTF
0.119
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-006_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-006_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.94 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:175.91
MW Contribution:1.37
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.132
20120126WRREN CT
50/50
3.821
971703AH1-357 GEN
Solar/Wind Harmer
1.367
971707AH1-359 GEN
Solar/Wind Harmer
1.367
20334926Z1-069 C
Solar/Wind Harmer
0.45
203854AF2-039 C
Solar/Wind Helper
0.279
238202AE2-262_GEN
Solar/Wind Helper
0.73
972075AH1-587 GEN
Solar/Wind Harmer
43.282
972077AH1-588 GEN
Solar/Wind Harmer
16.407
972079AH1-589 GEN
Solar/Wind Harmer
19.369
970715AG2-457 GEN
Solar/Wind Harmer
6.358
970305AG2-200 GEN
Solar/Wind Harmer
0.795
238217AF1-153 C O1
Solar/Wind Helper
0.223
203952AE2-129 C
Solar/Wind Helper
0.314
203946AE2-131 C
Solar/Wind Helper
0.315
946381AF1-302 GEN
Solar/Wind Helper
0.14
203853AF1-134 C O1
Solar/Wind Helper
0.269
200642SENECA#1
50/50
1.029
20083926HOMER C3
Adder
11.586
20083826HOMER C2
Adder
10.944
20083726HOMER C1
Adder
4.479
203804AE2-113_GEN
Solar/Wind Helper
9.089
203855AF2-088 C
Solar/Wind Helper
0.134
20090526Q36
Solar/Wind Helper
0.512
203993AD2-133_GEN1
Solar/Wind Helper
0.512
200643SENECA#2
50/50
0.96
970713AG2-456 GEN
Solar/Wind Harmer
6.358
971705AH1-358 GEN
Solar/Wind Harmer
2.279
971709AH1-360 GEN
Solar/Wind Harmer
2.279
203954AE2-126 C
Solar/Wind Helper
0.739
238206AE2-263_GEN
Solar/Wind Helper
0.695
LGEELTFEXP_LGEE->PJM
CLTF
0.112
WECLTFEXP_WEC->PJM
CLTF
0.067
CPLELTFEXP_CPLE->PJM
CLTF
0.077
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.101
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.042
LAGNLTFEXP_LAGN->PJM
CLTF
0.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.271
TVALTFEXP_TVA->PJM
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.776
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.538
MECLTFEXP_MEC->PJM
CLTF
0.28
SIGELTFEXP_SIGE->PJM
CLTF
0.009

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT27_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT27_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.59
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-004-DRT-003_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-004-DRT-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.58
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT26_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT26_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.09 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.0
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-004-DRT-004_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-004-DRT-004_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.09 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:760.99
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-2_PN-500-004A-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-2_PN-500-004A-DRT_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.2 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:716.99
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.556
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.462
20083826HOMER C2
50/50
126.07
20092526R32
Solar/Wind Harmer
2.751
203844AF2-092 C
Solar/Wind Harmer
1.843
203850AG1-041 C
Solar/Wind Harmer
1.837
203961AE2-224 GEN
Solar/Wind Harmer
4.541
20091526CHSTN_FL
Solar/Wind Harmer
1.215
20090526Q36
Solar/Wind Harmer
1.835
203993AD2-133_GEN1
Solar/Wind Harmer
1.835
940863AE2-074 GEN
Solar/Wind Harmer
2.03
203804AE2-113_GEN
Solar/Wind Harmer
5.24
965121AG1-377 GEN
Solar/Wind Harmer
2.169
941231AE2-117 GEN
Solar/Wind Harmer
0.635
20083226HNSMLK 5
Adder
5.966
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.53
970555AG2-356 GEN
Solar/Wind Harmer
1.838
970663AG2-429 GEN
Solar/Wind Harmer
6.046
970663AG2-429 GEN
Solar/Wind Harmer
0.984
970677AG2-438 GEN
Solar/Wind Harmer
0.759
966771AG1-548 GEN
Solar/Wind Harmer
10.997
966771AG1-548 GEN
Solar/Wind Harmer
2.131
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.532
20334726NME_Y1-047
Adder
1.382
971321AH1-140 GEN
Solar/Wind Harmer
8.457
971321AH1-140 GEN
Solar/Wind Harmer
1.639
20390726Y2-042
Adder
1.122
20083326SEWRDB34
50/50
5.324
20079426CONEMAGH
50/50
2.015
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.284
971879AH1-460 GEN
Solar/Wind Harmer
10.772
970125AG2-091 GEN
Solar/Wind Harmer
0.975
971541AH1-268 GEN
Solar/Wind Harmer
5.433
970899AG2-561 GEN
Solar/Wind Harmer
3.104
971419AH1-201 GEN
Solar/Wind Harmer
4.744
203818AF1-086 GEN
Solar/Wind Harmer
3.548
20089126CSLMN_L13
Solar/Wind Harmer
1.077
20089026BF_G21_K23
Solar/Wind Harmer
0.853
945751AF1-240 GEN
Solar/Wind Harmer
1.918
960051AF2-296 GEN
Solar/Wind Harmer
2.42
971703AH1-357 GEN
Solar/Wind Harmer
2.355
971707AH1-359 GEN
Solar/Wind Harmer
2.355
20334926Z1-069 C
Solar/Wind Harmer
2.383
965131AG1-378 GEN
Solar/Wind Harmer
2.169
20082926HNSMLK 2
Adder
5.966
20083126HNSMLK 4
Adder
5.966
203854AF2-039 C
Solar/Wind Harmer
0.397
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.888
202652Y1-033 WT C
Solar/Wind Harmer
0.869
971185AH1-051 GEN
Solar/Wind Harmer
2.202
971355AH1-158 GEN
Solar/Wind Harmer
2.56
20120126WRREN CT
Adder
5.678
203856AF2-165 C
Solar/Wind Harmer
1.068
970647AG2-420 GEN
Solar/Wind Harmer
1.789
970335AG2-220 GEN
Solar/Wind Harmer
2.757
971127AH1-005 GEN
Solar/Wind Harmer
1.779
959441AF2-235 GEN
Solar/Wind Harmer
0.257
238219AF1-167 C
Solar/Wind Harmer
1.122
238202AE2-262_GEN
Solar/Wind Harmer
2.071
971627AH1-313 GEN
Solar/Wind Harmer
8.119
20335126GROZ1-110
Adder
1.864
20335226CANZ2-011
Adder
1.812
957161AF2-010 GEN
Solar/Wind Harmer
5.877
203830AF1-094 GEN
Solar/Wind Harmer
0.46
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.44
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.434
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.069
972271AH1-720 GEN
Adder
4.404
200917MEHOOPANY_G
Solar/Wind Harmer
2.057
970679AG2-439 GEN
Solar/Wind Harmer
0.469
20080926SITHE
50/50
0.52
946071AF1-272 GEN
Solar/Wind Harmer
6.958
203839AF1-321 GEN
Solar/Wind Harmer
3.284
20084626FORWARD
Solar/Wind Harmer
1.292
203857AF2-221 C
Solar/Wind Harmer
2.437
970123AG2-090 GEN
Solar/Wind Harmer
2.275
203940AF1-140 C
Solar/Wind Harmer
0.747
20088926STNY CRK
Solar/Wind Harmer
1.827
971441AH1-212 GEN
Solar/Wind Harmer
2.99
971427AH1-205 GEN
Solar/Wind Harmer
2.207
20083426SW_E13_K22
Solar/Wind Harmer
0.434
20088626ARWF_N39
Solar/Wind Harmer
2.671
20303426NA_O38_P22
Solar/Wind Harmer
2.162
944781AF1-143 GEN
Solar/Wind Harmer
3.692
203853AF1-134 C O1
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
28.263
972079AH1-589 GEN
Solar/Wind Harmer
23.279
970715AG2-457 GEN
Solar/Wind Harmer
9.421
972075AH1-587 GEN
Solar/Wind Harmer
22.395
203952AE2-129 C
Solar/Wind Harmer
0.657
203946AE2-131 C
Solar/Wind Harmer
0.656
962411AG1-090 GEN
Solar/Wind Harmer
10.305
20398826ARMNA MT
Solar/Wind Harmer
2.3
203955AF1-039 C O1
Solar/Wind Harmer
0.423
203848AF2-166 C
Solar/Wind Harmer
1.855
946381AF1-302 GEN
Solar/Wind Harmer
1.902
970305AG2-200 GEN
Solar/Wind Harmer
1.796
203859AF2-294 C
Solar/Wind Harmer
1.523
238217AF1-153 C O1
Solar/Wind Harmer
0.541
970313AG2-206 GEN
Solar/Wind Harmer
4.249
203980AG1-197 GEN
Solar/Wind Harmer
0.346
203979AG1-198 GEN
Solar/Wind Harmer
0.276
971933AH1-491 GEN
Solar/Wind Harmer
1.518
216419AE2-001 C
Solar/Wind Harmer
1.511
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.436
203947AF1-006 C
Solar/Wind Harmer
0.379
20080526COLVER13
50/50
1.087
203843AF2-002_GEN
Solar/Wind Harmer
1.642
970631AG2-411 GEN
Solar/Wind Harmer
10.3
20088826HIGHLAND
Solar/Wind Harmer
2.567
971279AH1-102 GEN
Solar/Wind Harmer
12.766
957561AF2-050 GEN
Solar/Wind Harmer
7.496
20094526CT_V3-030
Solar/Wind Harmer
1.056
971423AH1-203 GEN
Solar/Wind Harmer
10.375
964201AG1-281 GEN
Solar/Wind Harmer
0.864
20089226LOOKOUT
Solar/Wind Harmer
1.049
970713AG2-456 GEN
Solar/Wind Harmer
9.421
971705AH1-358 GEN
Solar/Wind Harmer
2.739
971709AH1-360 GEN
Solar/Wind Harmer
2.739
203987AE2-118 C
Solar/Wind Harmer
2.243
964391AG1-301 GEN
Solar/Wind Harmer
0.625
20082826HNSMLK 1
Adder
5.966
20083026HNSMLK 3
Adder
5.966
20326126BLOSSBCT
Adder
2.23
20091326SHAW-D
Adder
0.639
972169AH1-667 GEN
Solar/Wind Harmer
1.749
203954AE2-126 C
Solar/Wind Harmer
0.588
20335026MILZ1-092
Adder
2.205
944411AF1-106 GEN
Solar/Wind Harmer
2.032
959471AF2-238 GEN
Solar/Wind Harmer
0.556
970337AG2-221 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
3.669
238183AE2-316 GEN
Solar/Wind Harmer
3.802
970647AG2-420 GEN
Solar/Wind Harmer
0.208
970511AG2-327 GEN
Solar/Wind Harmer
0.885
20072226SHAWVL 2
Adder
12.056
203860AG1-193 C
Solar/Wind Harmer
0.266
238206AE2-263_GEN
Solar/Wind Harmer
1.93
970267AG2-176 GEN
Solar/Wind Harmer
12.084
961971AG1-040 GEN
Solar/Wind Harmer
0.456
238215AE2-248 C
Solar/Wind Harmer
1.193
203835AF1-098 GEN
Solar/Wind Harmer
1.806
203813AE2-344_GEN
Solar/Wind Harmer
8.348
20084926LAKVU GN
Adder
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.173
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.51
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.376
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.54 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:712.74
MW Contribution:2.2
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
153.413
20215826CON.GEN1
50/50
0.027
20063626IUP CO-G
50/50
0.154
20083926HOMER C3
50/50
126.285
20083826HOMER C2
50/50
119.291
20092526R32
Solar/Wind Harmer
2.579
203844AF2-092 C
Solar/Wind Harmer
1.732
203850AG1-041 C
Solar/Wind Harmer
1.726
203961AE2-224 GEN
Solar/Wind Harmer
4.218
20091526CHSTN_FL
Solar/Wind Harmer
1.131
20090526Q36
Solar/Wind Harmer
1.697
203993AD2-133_GEN1
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
1.893
203804AE2-113_GEN
Solar/Wind Harmer
4.875
965121AG1-377 GEN
Solar/Wind Harmer
2
20083226HNSMLK 5
Adder
5.623
941231AE2-117 GEN
Solar/Wind Harmer
0.579
203855AF2-088 C
Solar/Wind Harmer
0.176
203846AF2-130 C
Solar/Wind Harmer
0.494
970555AG2-356 GEN
Solar/Wind Harmer
1.677
970663AG2-429 GEN
Solar/Wind Harmer
5.593
970663AG2-429 GEN
Solar/Wind Harmer
0.911
970677AG2-438 GEN
Solar/Wind Harmer
0.713
966771AG1-548 GEN
Solar/Wind Harmer
10.331
966771AG1-548 GEN
Solar/Wind Harmer
2.002
20084926LAKVU GN
Adder
0.129
971321AH1-140 GEN
Solar/Wind Harmer
9.071
971321AH1-140 GEN
Solar/Wind Harmer
1.758
203926AA2-133 GEN
Adder
1.344
20334726NME_Y1-047
Adder
1.195
20080526COLVER13
50/50
1.024
203843AF2-002_GEN
Solar/Wind Harmer
1.549
970631AG2-411 GEN
Solar/Wind Harmer
9.713
20088826HIGHLAND
Solar/Wind Harmer
2.407
971279AH1-102 GEN
Solar/Wind Harmer
11.989
971423AH1-203 GEN
Solar/Wind Harmer
9.809
957561AF2-050 GEN
Solar/Wind Harmer
6.963
20094526CT_V3-030
Solar/Wind Harmer
0.99
964201AG1-281 GEN
Solar/Wind Harmer
0.806
20089226LOOKOUT
Solar/Wind Harmer
1.004
970713AG2-456 GEN
Solar/Wind Harmer
8.817
971705AH1-358 GEN
Solar/Wind Harmer
2.563
971709AH1-360 GEN
Solar/Wind Harmer
2.563
203987AE2-118 C
Solar/Wind Harmer
2.054
20082826HNSMLK 1
Adder
5.623
20083026HNSMLK 3
Adder
5.623
964391AG1-301 GEN
Solar/Wind Harmer
0.569
203954AE2-126 C
Solar/Wind Harmer
0.541
20326126BLOSSBCT
Adder
2.045
20091326SHAW-D
Adder
0.586
972169AH1-667 GEN
Solar/Wind Harmer
1.605
20335026MILZ1-092
Adder
2.022
944411AF1-106 GEN
Solar/Wind Harmer
1.863
971183AH1-050 GEN
Solar/Wind Harmer
3.43
959471AF2-238 GEN
Solar/Wind Harmer
0.507
970337AG2-221 GEN
Solar/Wind Harmer
1.677
970647AG2-420 GEN
Solar/Wind Harmer
0.195
238183AE2-316 GEN
Solar/Wind Harmer
3.509
203860AG1-193 C
Solar/Wind Harmer
0.249
970511AG2-327 GEN
Solar/Wind Harmer
0.804
20072226SHAWVL 2
Adder
10.985
970267AG2-176 GEN
Solar/Wind Harmer
11.379
238206AE2-263_GEN
Solar/Wind Harmer
1.743
961971AG1-040 GEN
Solar/Wind Harmer
0.429
203835AF1-098 GEN
Solar/Wind Harmer
1.697
203813AE2-344_GEN
Solar/Wind Harmer
7.866
238215AE2-248 C
Solar/Wind Harmer
1.065
20084926LAKVU GN
Adder
0.115
20216026CON.GEN2
50/50
0.019
20083326SEWRDB34
50/50
4.935
20079426CONEMAGH
50/50
1.887
203841AF2-001_GEN
Solar/Wind Harmer
3.098
971879AH1-460 GEN
Solar/Wind Harmer
10.144
970125AG2-091 GEN
Solar/Wind Harmer
0.917
971541AH1-268 GEN
Solar/Wind Harmer
5.102
970899AG2-561 GEN
Solar/Wind Harmer
2.926
971419AH1-201 GEN
Solar/Wind Harmer
4.481
203818AF1-086 GEN
Solar/Wind Harmer
3.327
20089126CSLMN_L13
Solar/Wind Harmer
1.031
20089026BF_G21_K23
Solar/Wind Harmer
0.816
945751AF1-240 GEN
Solar/Wind Harmer
1.798
960051AF2-296 GEN
Solar/Wind Harmer
2.253
971703AH1-357 GEN
Solar/Wind Harmer
2.204
971707AH1-359 GEN
Solar/Wind Harmer
2.204
20334926Z1-069 C
Solar/Wind Harmer
2.216
965131AG1-378 GEN
Solar/Wind Harmer
2
20082926HNSMLK 2
Adder
5.623
20083126HNSMLK 4
Adder
5.623
202652Y1-033 WT C
Solar/Wind Harmer
0.847
203854AF2-039 C
Solar/Wind Harmer
0.365
203932AE1-123
Adder
1.757
944411AF1-106 GEN
Solar/Wind Harmer
0.2
971185AH1-051 GEN
Solar/Wind Harmer
2.058
971355AH1-158 GEN
Solar/Wind Harmer
2.393
20120126WRREN CT
Adder
5.302
203856AF2-165 C
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
1.674
970335AG2-220 GEN
Solar/Wind Harmer
2.507
971127AH1-005 GEN
Solar/Wind Harmer
1.617
959441AF2-235 GEN
Solar/Wind Harmer
0.241
238219AF1-167 C
Solar/Wind Harmer
1.034
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.332
957161AF2-010 GEN
Solar/Wind Harmer
5.518
20335126GROZ1-110
Adder
1.677
20335226CANZ2-011
Adder
1.63
203830AF1-094 GEN
Solar/Wind Harmer
0.432
203948AG1-140 C
Solar/Wind Harmer
0.181
203962AF1-287 GEN
Solar/Wind Harmer
1.356
962511AG1-100 GEN
Solar/Wind Harmer
0.409
20084926LAKVU GN
Adder
0.115
20328326MANOR_T86
Adder
0.091
941421AE2-139 GEN
Solar/Wind Harmer
1.826
972271AH1-720 GEN
Adder
3.879
200917MEHOOPANY_G
Solar/Wind Harmer
1.778
20080926SITHE
50/50
0.493
946071AF1-272 GEN
Solar/Wind Harmer
6.65
203839AF1-321 GEN
Solar/Wind Harmer
3.098
20084626FORWARD
Solar/Wind Harmer
1.219
203857AF2-221 C
Solar/Wind Harmer
2.292
970123AG2-090 GEN
Solar/Wind Harmer
2.139
203940AF1-140 C
Solar/Wind Harmer
0.7
20088926STNY CRK
Solar/Wind Harmer
1.725
971427AH1-205 GEN
Solar/Wind Harmer
2.084
971441AH1-212 GEN
Solar/Wind Harmer
2.794
20083426SW_E13_K22
Solar/Wind Harmer
0.411
20088626ARWF_N39
Solar/Wind Harmer
2.475
20303426NA_O38_P22
Solar/Wind Harmer
2.004
944781AF1-143 GEN
Solar/Wind Harmer
3.533
203853AF1-134 C O1
Solar/Wind Harmer
0.681
972077AH1-588 GEN
Solar/Wind Harmer
26.452
972079AH1-589 GEN
Solar/Wind Harmer
21.787
970715AG2-457 GEN
Solar/Wind Harmer
8.817
972075AH1-587 GEN
Solar/Wind Harmer
20.869
203952AE2-129 C
Solar/Wind Harmer
0.606
203946AE2-131 C
Solar/Wind Harmer
0.605
962411AG1-090 GEN
Solar/Wind Harmer
9.501
203955AF1-039 C O1
Solar/Wind Harmer
0.412
20398826ARMNA MT
Solar/Wind Harmer
2.11
203848AF2-166 C
Solar/Wind Harmer
1.73
970305AG2-200 GEN
Solar/Wind Harmer
1.677
946381AF1-302 GEN
Solar/Wind Harmer
1.756
238217AF1-153 C O1
Solar/Wind Harmer
0.496
203859AF2-294 C
Solar/Wind Harmer
1.387
970313AG2-206 GEN
Solar/Wind Harmer
3.861
203980AG1-197 GEN
Solar/Wind Harmer
0.326
203979AG1-198 GEN
Solar/Wind Harmer
0.259
971933AH1-491 GEN
Solar/Wind Harmer
1.425
203963AG1-253 GEN
Solar/Wind Harmer
0.276
971931AH1-490 GEN
Solar/Wind Harmer
1.353
216419AE2-001 C
Solar/Wind Harmer
1.35
203947AF1-006 C
Solar/Wind Harmer
0.357
LGEELTFEXP_LGEE->PJM
CLTF
0.128
WECLTFEXP_WEC->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.284
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.569
MECLTFEXP_MEC->PJM
CLTF
0.336
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT32_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT32_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-002_SRT-SL


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-002_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-036_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-036_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.49 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:200.31
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
5.337
972079AH1-589 GEN
Solar/Wind Harmer
6.301
970715AG2-457 GEN
Solar/Wind Harmer
2.068
20083926HOMER C3
Adder
15.014
20083826HOMER C2
Adder
14.183
20083726HOMER C1
Adder
8.768
971703AH1-357 GEN
Solar/Wind Harmer
0.445
971707AH1-359 GEN
Solar/Wind Harmer
0.445
941421AE2-139 GEN
Solar/Wind Helper
2.983
200917MEHOOPANY_G
Solar/Wind Helper
2.001
970713AG2-456 GEN
Solar/Wind Harmer
2.068
971705AH1-358 GEN
Solar/Wind Harmer
0.741
971709AH1-360 GEN
Solar/Wind Harmer
0.741
959471AF2-238 GEN
Solar/Wind Helper
0.262
CPLELTFEXP_CPLE->PJM
CLTF
0.182
LGEELTFEXP_LGEE->PJM
CLTF
0.202
WECLTFEXP_WEC->PJM
CLTF
0.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.721
LAGNLTFEXP_LAGN->PJM
CLTF
0.528
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.584
TVALTFEXP_TVA->PJM
CLTF
0.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.003
MECLTFEXP_MEC->PJM
CLTF
0.496
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-018_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-018_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:179.12
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1154-W_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1154-W_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.81 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:159.76
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
18.011
20083826HOMER C2
Adder
17.014
20083726HOMER C1
Adder
10.622
972211AH1-690 GEN
Adder
7.849
203859AF2-294 C
Solar/Wind Harmer
0.816
972077AH1-588 GEN
Solar/Wind Harmer
7.43
972079AH1-589 GEN
Solar/Wind Harmer
6.12
970715AG2-457 GEN
Solar/Wind Harmer
2.477
970935AG2-582 GEN
Adder
7.698
20398826ARMNA MT
Solar/Wind Helper
1.623
971703AH1-357 GEN
Solar/Wind Harmer
0.619
971707AH1-359 GEN
Solar/Wind Harmer
0.619
972191AH1-680 GEN
Adder
7.47
941421AE2-139 GEN
Solar/Wind Helper
3.345
200917MEHOOPANY_G
Solar/Wind Helper
2.227
970713AG2-456 GEN
Solar/Wind Harmer
2.477
971705AH1-358 GEN
Solar/Wind Harmer
0.72
971709AH1-360 GEN
Solar/Wind Harmer
0.72
959471AF2-238 GEN
Solar/Wind Helper
0.551
CPLELTFEXP_CPLE->PJM
CLTF
0.265
LGEELTFEXP_LGEE->PJM
CLTF
0.264
WECLTFEXP_WEC->PJM
CLTF
0.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.942
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.909
LAGNLTFEXP_LAGN->PJM
CLTF
0.704
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.823
TVALTFEXP_TVA->PJM
CLTF
0.349
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.333
MECLTFEXP_MEC->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.38 %
Rating:114.0 MVA
Rating Type:A
MVA to Mitigate:132.68
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o AP_P2-2_WP-230-001T_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:144.71
MW Contribution:0.72
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
16.064
20083826HOMER C2
Adder
15.174
20083726HOMER C1
Adder
9.328
972211AH1-690 GEN
Adder
7.602
971703AH1-357 GEN
Solar/Wind Harmer
0.725
971707AH1-359 GEN
Solar/Wind Harmer
0.725
972191AH1-680 GEN
Adder
7.211
941421AE2-139 GEN
Solar/Wind Helper
3.037
200917MEHOOPANY_G
Solar/Wind Helper
2.024
203859AF2-294 C
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
8.696
972079AH1-589 GEN
Solar/Wind Harmer
7.162
970715AG2-457 GEN
Solar/Wind Harmer
2.899
970935AG2-582 GEN
Adder
7.181
970713AG2-456 GEN
Solar/Wind Harmer
2.899
971705AH1-358 GEN
Solar/Wind Harmer
0.843
971709AH1-360 GEN
Solar/Wind Harmer
0.843
959471AF2-238 GEN
Solar/Wind Helper
0.265
CPLELTFEXP_CPLE->PJM
CLTF
0.244
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.144
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.655
LAGNLTFEXP_LAGN->PJM
CLTF
0.665
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.766
TVALTFEXP_TVA->PJM
CLTF
0.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.261
MECLTFEXP_MEC->PJM
CLTF
0.616
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-020-DRT_SRT-SL


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-020-DRT_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.24 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:175.67
MW Contribution:0.57
Bus #Bus NameTypeMW Contribution
20335026MILZ1-092
Adder
1.208
944411AF1-106 GEN
Solar/Wind Harmer
1.113
970713AG2-456 GEN
Solar/Wind Harmer
2.283
971705AH1-358 GEN
Solar/Wind Harmer
0.664
971709AH1-360 GEN
Solar/Wind Harmer
0.664
20083926HOMER C3
Adder
12.745
20083826HOMER C2
Adder
12.039
20083726HOMER C1
Adder
7.815
972077AH1-588 GEN
Solar/Wind Harmer
6.85
972079AH1-589 GEN
Solar/Wind Harmer
5.642
970715AG2-457 GEN
Solar/Wind Harmer
2.283
944411AF1-106 GEN
Solar/Wind Harmer
0.12
971703AH1-357 GEN
Solar/Wind Harmer
0.571
971707AH1-359 GEN
Solar/Wind Harmer
0.571
200917MEHOOPANY_G
Solar/Wind Helper
2.835
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.107
CPLELTFEXP_CPLE->PJM
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
13.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.925
MECLTFEXP_MEC->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-997-DRT-068_SRT-SL


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-997-DRT-068_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.09 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:175.48
MW Contribution:0.57
Bus #Bus NameTypeMW Contribution
20335026MILZ1-092
Adder
1.208
944411AF1-106 GEN
Solar/Wind Harmer
1.113
970713AG2-456 GEN
Solar/Wind Harmer
2.283
971705AH1-358 GEN
Solar/Wind Harmer
0.664
971709AH1-360 GEN
Solar/Wind Harmer
0.664
20083926HOMER C3
Adder
12.745
20083826HOMER C2
Adder
12.039
20083726HOMER C1
Adder
7.815
972077AH1-588 GEN
Solar/Wind Harmer
6.85
972079AH1-589 GEN
Solar/Wind Harmer
5.642
970715AG2-457 GEN
Solar/Wind Harmer
2.283
944411AF1-106 GEN
Solar/Wind Harmer
0.12
971703AH1-357 GEN
Solar/Wind Harmer
0.571
971707AH1-359 GEN
Solar/Wind Harmer
0.571
200917MEHOOPANY_G
Solar/Wind Helper
2.835
CPLELTFEXP_CPLE->PJM
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.107
CBM NorthLTFEXP_CBM-N->PJM
CBM
13.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.925
MECLTFEXP_MEC->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-3C_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-3C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.09 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:175.48
MW Contribution:0.57
Bus #Bus NameTypeMW Contribution
20335026MILZ1-092
Adder
1.208
944411AF1-106 GEN
Solar/Wind Harmer
1.113
970713AG2-456 GEN
Solar/Wind Harmer
2.283
971705AH1-358 GEN
Solar/Wind Harmer
0.664
944411AF1-106 GEN
Solar/Wind Harmer
0.12
971703AH1-357 GEN
Solar/Wind Harmer
0.571
971707AH1-359 GEN
Solar/Wind Harmer
0.571
200917MEHOOPANY_G
Solar/Wind Helper
2.835
971709AH1-360 GEN
Solar/Wind Harmer
0.664
20083926HOMER C3
Adder
12.745
20083826HOMER C2
Adder
12.039
20083726HOMER C1
Adder
7.815
972077AH1-588 GEN
Solar/Wind Harmer
6.85
972079AH1-589 GEN
Solar/Wind Harmer
5.642
970715AG2-457 GEN
Solar/Wind Harmer
2.283
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.107
CPLELTFEXP_CPLE->PJM
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
13.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.925
MECLTFEXP_MEC->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-997-DRT-055_SRT-SL


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-997-DRT-055_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.09 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:175.48
MW Contribution:0.57
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
12.745
20083826HOMER C2
Adder
12.039
20083726HOMER C1
Adder
7.815
20335026MILZ1-092
Adder
1.208
944411AF1-106 GEN
Solar/Wind Harmer
1.113
970713AG2-456 GEN
Solar/Wind Harmer
2.283
971705AH1-358 GEN
Solar/Wind Harmer
0.664
971709AH1-360 GEN
Solar/Wind Harmer
0.664
944411AF1-106 GEN
Solar/Wind Harmer
0.12
971703AH1-357 GEN
Solar/Wind Harmer
0.571
971707AH1-359 GEN
Solar/Wind Harmer
0.571
200917MEHOOPANY_G
Solar/Wind Helper
2.835
972077AH1-588 GEN
Solar/Wind Harmer
6.85
972079AH1-589 GEN
Solar/Wind Harmer
5.642
970715AG2-457 GEN
Solar/Wind Harmer
2.283
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.107
CPLELTFEXP_CPLE->PJM
CLTF
0.167
CBM NorthLTFEXP_CBM-N->PJM
CBM
13.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.43
LAGNLTFEXP_LAGN->PJM
CLTF
0.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.299
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.925
MECLTFEXP_MEC->PJM
CLTF
0.457
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-997-DRT-067_SRT-SL


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-997-DRT-067_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.2 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:171.78
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
944411AF1-106 GEN
Solar/Wind Harmer
0.113
971703AH1-357 GEN
Solar/Wind Harmer
0.551
971707AH1-359 GEN
Solar/Wind Harmer
0.551
200917MEHOOPANY_G
Solar/Wind Helper
3.024
20335026MILZ1-092
Adder
1.144
944411AF1-106 GEN
Solar/Wind Harmer
1.054
970713AG2-456 GEN
Solar/Wind Harmer
2.205
971705AH1-358 GEN
Solar/Wind Harmer
0.641
971709AH1-360 GEN
Solar/Wind Harmer
0.641
20083926HOMER C3
Adder
12.329
20083826HOMER C2
Adder
11.646
20083726HOMER C1
Adder
7.553
972077AH1-588 GEN
Solar/Wind Harmer
6.616
972079AH1-589 GEN
Solar/Wind Harmer
5.449
970715AG2-457 GEN
Solar/Wind Harmer
2.205
LGEELTFEXP_LGEE->PJM
CLTF
0.181
WECLTFEXP_WEC->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
0.164
CBM NorthLTFEXP_CBM-N->PJM
CBM
12.847
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.338
LAGNLTFEXP_LAGN->PJM
CLTF
0.474
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.526
TVALTFEXP_TVA->PJM
CLTF
0.235
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.178
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.9
MECLTFEXP_MEC->PJM
CLTF
0.444
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-2_PN-115-068T_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-068T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.1 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:153.73
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
12.097
20083826HOMER C2
Adder
11.427
20083726HOMER C1
Adder
7.286
971703AH1-357 GEN
Solar/Wind Harmer
0.528
971707AH1-359 GEN
Solar/Wind Harmer
0.528
200917MEHOOPANY_G
Solar/Wind Helper
2.732
941421AE2-139 GEN
Solar/Wind Helper
1.306
972077AH1-588 GEN
Solar/Wind Harmer
6.333
972079AH1-589 GEN
Solar/Wind Harmer
5.216
970715AG2-457 GEN
Solar/Wind Harmer
2.111
970713AG2-456 GEN
Solar/Wind Harmer
2.111
971705AH1-358 GEN
Solar/Wind Harmer
0.614
971709AH1-360 GEN
Solar/Wind Harmer
0.614
CPLELTFEXP_CPLE->PJM
CLTF
0.175
LGEELTFEXP_LGEE->PJM
CLTF
0.182
WECLTFEXP_WEC->PJM
CLTF
0.105
CBM NorthLTFEXP_CBM-N->PJM
CBM
14.303
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.38
LAGNLTFEXP_LAGN->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.551
TVALTFEXP_TVA->PJM
CLTF
0.239
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.915
MECLTFEXP_MEC->PJM
CLTF
0.448
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for OAKDL115-26LAUREL L 115.0 kV Ckt 1 line l/o PN_P2-2_PN-115-069_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-069_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.91 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:152.21
MW Contribution:0.53
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
12.097
20083826HOMER C2
Adder
11.427
20083726HOMER C1
Adder
7.286
944411AF1-106 GEN
Solar/Wind Harmer
0.166
971703AH1-357 GEN
Solar/Wind Harmer
0.528
971707AH1-359 GEN
Solar/Wind Harmer
0.528
200917MEHOOPANY_G
Solar/Wind Helper
2.732
941421AE2-139 GEN
Solar/Wind Helper
1.306
972077AH1-588 GEN
Solar/Wind Harmer
6.333
972079AH1-589 GEN
Solar/Wind Harmer
5.216
970715AG2-457 GEN
Solar/Wind Harmer
2.111
20335026MILZ1-092
Adder
1.68
944411AF1-106 GEN
Solar/Wind Harmer
1.548
970713AG2-456 GEN
Solar/Wind Harmer
2.111
971705AH1-358 GEN
Solar/Wind Harmer
0.614
971709AH1-360 GEN
Solar/Wind Harmer
0.614
LGEELTFEXP_LGEE->PJM
CLTF
0.182
WECLTFEXP_WEC->PJM
CLTF
0.105
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM NorthLTFEXP_CBM-N->PJM
CBM
14.303
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.38
LAGNLTFEXP_LAGN->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.551
TVALTFEXP_TVA->PJM
CLTF
0.239
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.915
MECLTFEXP_MEC->PJM
CLTF
0.448
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CONTINGENCY 'AP_P2-3_WP-138-171A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235153 TO BUS 235274 CKT 1   /*01CABOT      138.0 - 01WOODLD     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235274 TO BUS 235803 CKT 1   /*01WOODLD     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235274 TO BUS 236236 CKT 2   /*01WOODLD     138.0 - 01WOODLAND    25.0
END
CONTINGENCY 'AP_P2-2_WP-138-054A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041D_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238544 CKT 4   /*02S8-ATT     345.0 - 02ASH_3      138.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041E_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238542 CKT 9   /*02S8-ATT     345.0 - 02ASH_1      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1                /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                                /*26HOMER CT   230.0
 SET POSTCONTRATING 1000 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
 SET PRECONTRATING 830 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                   /*26HOMER CT   230.0
END
CONTINGENCY 'AP_P1-3_WP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235282 TO BUS 235240 CKT 1   /*01GAR RN     138.0 - 01COLMBGPN   138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-051A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1   /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235137 CKT 1   /*01BRACKENRDG 138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235202 CKT 1   /*01BRACKENR J 138.0 - 01KISKIV     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235245 CKT 1   /*01BRACKENR J 138.0 - 01SHFCRN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1   /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1   /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'AP_P2-2_WP-138-055_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235137 CKT 1   /*01KISKIV     138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235262 CKT 1   /*01KISKIV     138.0 - 01VANDRG     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235278 CKT 1   /*01KISKIV     138.0 - 01N WASH     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 2   /*01KISKIV     138.0 - 01KISKI VA    25.0
END
CONTINGENCY 'AP_P2-2_WP-138-058_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1   /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 970662 CKT 1   /*01ARMSTR     138.0 - AG2-429 TP   138.0
END
CONTINGENCY 'AP_P2-3_WP-138-194T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200827 TO BUS 235224 CKT 1   /*26BROOKVLE   138.0 - 01N BETH     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235224 CKT 1   /*01ARMSTR     138.0 - 01N BETH     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1   /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 970662 CKT 1   /*01ARMSTR     138.0 - AG2-429 TP   138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-4_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200758 CKT 1   /*26SEWARD 2   230.0 - 26JOHNSTWN   230.0
 OPEN BUS 200767                                   /*26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-345-997-DRT-031_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200595 TO BUS 200598 CKT 2          /*26WAYNE      345.0 - 26WAYNE      115.0
 DISCONNECT BRANCH FROM BUS 200595 TO BUS 200826 CKT 1          /*26WAYNE      345.0 - 26HANDSMLK   345.0
 SET POSTCONTRATING 1552 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W     345.0 - 26WAYNE      345.0
 SET PRECONTRATING 1269 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W     345.0 - 26WAYNE      345.0
END
CONTINGENCY 'AP_P2-3_WP-138-177_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235078 CKT ZB   /*01SPGDL-3    138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235603 CKT 1    /*01SPGDL-3    138.0 - 01PITTML     138.0
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235610 CKT 1    /*01SPGDL-3    138.0 - 01SPRGD1      13.8
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235611 CKT 1    /*01SPGDL-3    138.0 - 01SPRGD2      13.8
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 OPEN BUS 235132                                          /*01AL 4       138.0
 OPEN BUS 235138                                          /*01AL 4J      138.0
 OPEN BUS 235825                                          /*01ALL L4T    138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-054_SRT-A'
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
 DISCONNECT BRANCH FROM BUS 235245 TO BUS 235078 CKT 1    /*01SHFCRN     138.0 - 01SPGDL-2    138.0
END
CONTINGENCY 'AP_P1-2_WP-138-087_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235825 CKT 1   /*01BRACKENRDG 138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1   /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1   /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1   /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235825 TO BUS 235132 CKT 1   /*01ALL L4T    138.0 - 01AL 4       138.0
END
CONTINGENCY 'AP_P1-2_WP-138-103_SRT-A'
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235134 CKT 1   /*01AL&D6T     138.0 - 01AL&D6      138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235139 CKT 1   /*01KITTAN     138.0 - 01AL&D6T     138.0
 DISCONNECT BUS 235134                                   /*01AL&D6      138.0
END
CONTINGENCY 'AP_P2-2_WP-138-057_SRT-A'
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235139 CKT 1   /*01KITTAN     138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1   /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235865 CKT 2   /*01KITTAN     138.0 - 01KITTAN      25.0
END
CONTINGENCY 'PN_P2-2_PN-345-002T-DRT-003_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 TO BUS 202641 CKT S /*26HOMER CY   345.0 - 26HOMER CT   230.0 - 26HOMERCITYS  23.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'AP_P7-1_WPP-138-067_SRT-A'
 DISCONNECT BRANCH FROM BUS 235152 TO BUS 235153 CKT E   /*01BUTLER     138.0 - 01CABOT      138.0
 DISCONNECT BRANCH FROM BUS 235152 TO BUS 235197 CKT 1   /*01BUTLER     138.0 - 01KARNSC     138.0
END
CONTINGENCY 'PN_P2-3_PN-230-703T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235248 CKT 1   /*26SHAWVL 2   230.0 - 01SHINGL     230.0
END
CONTINGENCY 'AP_P2-2_WP-230-006T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 200726 CKT 1    /*01SHINGL     230.0 - 26SHAWVL 2   230.0
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 236711 CKT 81   /*01SHINGL     230.0 - 01SHINGLTN    46.0
END
CONTINGENCY 'AP_P2-3_WP-230-459T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235248 CKT 1    /*26SHAWVL 2   230.0 - 01SHINGL     230.0
 DISCONNECT BRANCH FROM BUS 236711 TO BUS 235248 CKT 81   /*01SHINGLTN    46.0 - 01SHINGL     230.0
END
CONTINGENCY 'AP_P2-2_WP-230-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235174 CKT 1   /*01ELKO       230.0 - 01ELKO       138.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235971 CKT 1   /*01ELKO       230.0 - 01SQUABHLLW  230.0
END
CONTINGENCY 'AP_P2-3_WP-230-442_SRT-A'
 DISCONNECT BRANCH FROM BUS 235174 TO BUS 235175 CKT 1   /*01ELKO       138.0 - 01ELKO       230.0
 DISCONNECT BRANCH FROM BUS 235971 TO BUS 235175 CKT 1   /*01SQUABHLLW  230.0 - 01ELKO       230.0
END
CONTINGENCY 'PN_P2-2_PN-345-002T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 TO BUS 202641 CKT S /*26HOMER CY   345.0 - 26HOMER CT   230.0 - 26HOMERCITYS  23.0
END
CONTINGENCY 'AP_P7-1_WPP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1    /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1    /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1    /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1    /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'AP_P2-2_WP-230-005T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 200513 CKT 1    /*01SHINGL     230.0 - 26LEWISTWN   230.0
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 235970 CKT 1    /*01SHINGL     230.0 - 01DALE       230.0
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 236711 CKT 82   /*01SHINGL     230.0 - 01SHINGLTN    46.0
END
CONTINGENCY 'PN_P2-3_PN-230-0310-B_SRT-A'
 OPEN BRANCH FROM BUS 200517 TO BUS 200513 CKT 1   /*26RAYSTOWN   230.0 - 26LEWISTWN   230.0
 OPEN BRANCH FROM BUS 200517 TO BUS 200539 CKT 2   /*26RAYSTOWN   230.0 - 26RAYSTOWN    46.0
END
CONTINGENCY 'PN_P2-3_PN-230-0310-A_SRT-A'
 OPEN BRANCH FROM BUS 200517 TO BUS 200513 CKT 1   /*26RAYSTOWN   230.0 - 26LEWISTWN   230.0
 OPEN BRANCH FROM BUS 200517 TO BUS 200539 CKT 1   /*26RAYSTOWN   230.0 - 26RAYSTOWN    46.0
 REDUCE BUS 200517 SHUNT BY 100 PERCENT            /*26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0014-01_SRT-A'
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200517 CKT 1   /*26LEWISTWN   230.0 - 26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0014-02_SRT-A'
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200517 CKT 1   /*26LEWISTWN   230.0 - 26RAYSTOWN   230.0
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200531 CKT 2   /*26LEWISTWN   230.0 - 26YEAGRTWN   230.0
 REDUCE BUS 200513 SHUNT BY 100 PERCENT                  /*26LEWISTWN   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0310-C_SRT-A'
 OPEN BRANCH FROM BUS 200517 TO BUS 200500 CKT 1   /*26RAYSTOWN   230.0 - 26ALTOONA    230.0
 OPEN BRANCH FROM BUS 200517 TO BUS 200539 CKT 2   /*26RAYSTOWN   230.0 - 26RAYSTOWN    46.0
END
CONTINGENCY 'PN_P2-2_PN-345-1185-2_SRT-A'
 OPEN BRANCH FROM BUS 200942 TO BUS 200943 CKT 1   /*26PIERCEBRK  345.0 - 26PIERCEBRK  230.0
 REMOVE SHUNT R2 FROM BUS 200942                   /*26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-2_PN-230-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 200918 TO BUS 200568 CKT ZB   /*26ERIE S TIE 230.0 - 26ERIE SO.   230.0
 DISCONNECT BRANCH FROM BUS 200918 TO BUS 200811 CKT 1    /*26ERIE S TIE 230.0 - 26WARREN     230.0
 DISCONNECT BRANCH FROM BUS 200918 TO BUS 200819 CKT ZB   /*26ERIE S TIE 230.0 - 26ERIE SE    230.0
 DISCONNECT BUS 200918                                    /*26ERIE S TIE 230.0
END
CONTINGENCY 'AP_P7-1_WPP-138-020T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200827 TO BUS 235224 CKT 1   /*26BROOKVLE   138.0 - 01N BETH     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235224 CKT 1   /*01ARMSTR     138.0 - 01N BETH     138.0
END
CONTINGENCY 'PN_P2-2_PN-115-022_SRT-A'
 DISCONNECT BRANCH FROM BUS 200524 TO BUS 200533 CKT 2   /*26SPANGLER   115.0 - 26SPANGLER    46.0
 DISCONNECT BRANCH FROM BUS 200801 TO BUS 200524 CKT 1   /*26GARMAN     115.0 - 26SPANGLER   115.0
 DISCONNECT BRANCH FROM BUS 200801 TO BUS 200755 CKT 1   /*26GARMAN     115.0 - 26WESTOVER   115.0
END
CONTINGENCY 'PL_08_P22_102799_SRT-A'
 DISCONNECT BUS 200080   /*HUST         500.0
END
CONTINGENCY 'PN_P2-2_PN-115-059B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200668 TO BUS 200696 CKT 1   /*26FARM VLY   115.0 - 26FARM.VA1    34.5
 DISCONNECT BRANCH FROM BUS 200668 TO BUS 972074 CKT 1   /*26FARM VLY   115.0 - AH1-587 TP   115.0
END
CONTINGENCY 'PN_P1-2_PN-230-020A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200517 CKT 1   /*26LEWISTWN   230.0 - 26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-019_SRT-A'
 DISCONNECT BRANCH FROM BUS 200500 TO BUS 200517 CKT 1   /*26ALTOONA    230.0 - 26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0201A-20_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200795 TO BUS 200810 CKT 1          /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-997-DRT-053_SRT-SL'
 DISCONNECT BRANCH FROM BUS 132004 TO BUS 130763 CKT 2          /*PAR          230.0 - HILSD230     230.0
 DISCONNECT BRANCH FROM BUS 200675 TO BUS 132004 CKT 1          /*26E.TWANDA   230.0 - PAR          230.0
 SET POSTCONTRATING 1156 BRANCH FROM BUS 200675 TO BUS 200949 CKT 1 /*26E.TWANDA   230.0 - AA1-082 MAIN 230.0
 SET PRECONTRATING 968 BRANCH FROM BUS 200675 TO BUS 200949 CKT 1 /*26E.TWANDA   230.0 - AA1-082 MAIN 230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-C_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-B_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-A_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-208_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200768 CKT 1   /*26HOMER CT   230.0 - 26QUEMAHON   230.0
 DISCONNECT BRANCH FROM BUS 200768 TO BUS 200796 CKT 1   /*26QUEMAHON   230.0 - 26HOOVRSVL   230.0
 OPEN BRANCH FROM BUS 200767 TO BUS 200795 CKT 1         /*26HOMER CT   230.0 - 26SHELOCTA   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-26A2_SRT-A'
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 200942 CKT 1   /*26PIERCEBRK  230.0 - 26PIERCEBRK  345.0
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 970712 CKT 1   /*26PIERCEBRK  230.0 - AG2-456 TP   230.0
END
CONTINGENCY 'PN_P2-3_PN-345-997-DRT-051_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200942 TO BUS 200943 CKT 1          /*26PIERCEBRK  345.0 - 26PIERCEBRK  230.0
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 970712 CKT 1          /*26PIERCEBRK  230.0 - AG2-456 TP   230.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 200942 TO BUS 135398 CKT 1 /*26PIERCEBRK  345.0 - 5MILE345     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 200942 TO BUS 135398 CKT 1 /*26PIERCEBRK  345.0 - 5MILE345     345.0
END
CONTINGENCY 'PN_P2-3_PN-230-26A1_SRT-A'
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 200942 CKT 1   /*26PIERCEBRK  230.0 - 26PIERCEBRK  345.0
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 200944 CKT 2   /*26PIERCEBRK  230.0 - 26PIERCEBRK  115.0
END
CONTINGENCY 'PN_P2-3_PN-345-997-DRT-052_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200942 TO BUS 200943 CKT 1          /*26PIERCEBRK  345.0 - 26PIERCEBRK  230.0
 DISCONNECT BRANCH FROM BUS 200943 TO BUS 200944 CKT 2          /*26PIERCEBRK  230.0 - 26PIERCEBRK  115.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 200942 TO BUS 135398 CKT 1 /*26PIERCEBRK  345.0 - 5MILE345     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 200942 TO BUS 135398 CKT 1 /*26PIERCEBRK  345.0 - 5MILE345     345.0
END
CONTINGENCY 'PN_P2-3_PN-345-1185-A_SRT-A'
 OPEN BRANCH FROM BUS 200942 TO BUS 200943 CKT 1   /*26PIERCEBRK  345.0 - 26PIERCEBRK  230.0
 REMOVE SHUNT R2 FROM BUS 200942                   /*26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1          /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1   /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
END
CONTINGENCY 'PN_P2-2_PN-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
 DISCONNECT BUS 200807                                   /*26PIERC230   230.0
 DISCONNECT BUS 200808                                   /*26PIERC138   138.0
 DISCONNECT BUS 200809                                   /*26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-210_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200807 TO BUS 200808 CKT 1   /*26PIERC230   230.0 - 26PIERC138   138.0
 DISCONNECT BRANCH FROM BUS 200808 TO BUS 200809 CKT 1   /*26PIERC138   138.0 - 26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T-DRT-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-207_SRT-A'
 OPEN BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 OPEN BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 OPEN BUS 200768                                   /*26QUEMAHON   230.0
END
CONTINGENCY 'AP_P2-2_WP-138-059_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235129 CKT 2   /*01ARMSTR     138.0 - 01ARMSTRONG  345.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235203 CKT 1   /*01ARMSTR     138.0 - 01KISSNG     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235224 CKT 1   /*01ARMSTR     138.0 - 01N BETH     138.0
END
CONTINGENCY 'AP_P1-2_WP-345-311T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235129 TO BUS 200769 CKT 1   /*01ARMSTRONG  345.0 - 26HOMER CY   345.0
END
CONTINGENCY 'PN_P1-3_DRT-230-003-DRT_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-2_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200741 CKT 9   /*26SEWARD 2   230.0 - 26SEWARD     115.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-003JT_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-2_PN-500-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-A_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-2_PN-115-016A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200729 CKT 8   /*26SEWARD     115.0 - 26SEWARD      23.0
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200742 CKT 1   /*26SEWARD     115.0 - 26TOWER 51   115.0
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200766 CKT 1   /*26SEWARD     115.0 - 26FLORENCE   115.0
END
CONTINGENCY 'AP_P2-2_MP-138-100_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235469 CKT 1   /*01ALBRIG     138.0 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 235469 TO BUS 235470 CKT 1   /*01GARRET     138.0 - 01GARRET     115.0
 DISCONNECT BRANCH FROM BUS 237410 TO BUS 235469 CKT 1   /*01GARRETT     34.5 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 970994 TO BUS 235469 CKT 1   /*AG2-615 TP   138.0 - 01GARRET     138.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT18_SRT-A'
 OPEN BRANCH FROM BUS 235118 TO BUS 235619 CKT 1                /*01SOBEND     500.0 - AD2-113 G1    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235620 CKT 1                /*01SOBEND     500.0 - AD2-113 G2    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235621 CKT 1                /*01SOBEND     500.0 - AD2-113 G3    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235622 CKT 1                /*01SOBEND     500.0 - AD2-113 G4    18.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P1-2_PN-230-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 200912 TO BUS 200793 CKT 1   /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P1-3_PN-500-003_SRT-A'
 OPEN BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT27_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200033 CKT 1                /*KEYSTONE     500.0 - KEYS G2       20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3          /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 DISCONNECT BUS 200033                                          /*KEYS G2       20.0
 REMOVE MACHINE H FROM BUS 200033                               /*KEYS G2       20.0
 REMOVE MACHINE L FROM BUS 200033                               /*KEYS G2       20.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT26_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200032 CKT 1                /*KEYSTONE     500.0 - KEYS G1       20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-004_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3          /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 DISCONNECT BUS 200032                                          /*KEYS G1       20.0
 REMOVE MACHINE H FROM BUS 200032                               /*KEYS G1       20.0
 REMOVE MACHINE L FROM BUS 200032                               /*KEYS G1       20.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-2_PN-500-004A-DRT_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT33_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235118 CKT 1                /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2526 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200532 CKT 2         /*26ROXBURY    115.0 - 26ROXBURY    138.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200860 CKT 3         /*26ROXBURY    115.0 - 26ROXB SB2    23.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT31_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200009 CKT 1                /*KEYSTONE     500.0 - JUNI         500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-008_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200009 CKT 1          /*KEYSTONE     500.0 - JUNI         500.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-D_SRT-A'
 OPEN BRANCH FROM BUS 200504 TO BUS 202803 CKT 2   /*26CARLISLE   115.0 - 26CARL PK2    23.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200504 CKT 1   /*26ROXBURY    115.0 - 26CARLISLE   115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200532 CKT 2   /*26ROXBURY    115.0 - 26ROXBURY    138.0
END
CONTINGENCY 'PN_P2-2_PN-115-030_SRT-A'
 DISCONNECT BUS 200522   /*26SHADE GP   115.0
END
CONTINGENCY 'PN_P2-2_PN-115-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 200512 TO BUS 200519 CKT 1   /*26LEWISTWN   115.0 - 26REED TAP   115.0
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200512 CKT 3   /*26LEWISTWN   230.0 - 26LEWISTWN   115.0
END
CONTINGENCY 'AP_P2-2_WP-138-074_SRT-A'
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235180 CKT 1   /*01GRANDP     138.0 - 01FAYETT     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235189 CKT 1   /*01GRANDP     138.0 - 01GUILFD     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235557 CKT 1   /*01GRANDP     138.0 - 01LETTER     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 237331 CKT 1   /*01GRANDP     138.0 - 01GRANDPOI    69.0
 DISCONNECT BUS 235187                                   /*01GRANDP     138.0
 REDUCE BUS 235187 SHUNT BY 100 PERCENT                  /*01GRANDP     138.0
END
CONTINGENCY 'PL_48_P71_102649_SRT-A'
 DISCONNECT BRANCH FROM BUS 207915 TO BUS 208113 CKT 1   /*GLBR         230.0 - SUSQ         230.0
 DISCONNECT BUS 208114                                   /*SUSQ G1      230.0
 DISCONNECT BUS 208124                                   /*SUSQ G1 TP   230.0
END
CONTINGENCY 'PECO_P7-1_220-9091_SRT-A
 DISCONNECT BUS 213616   /*FORDACT1      18.0
 DISCONNECT BUS 213617   /*FORDACT2      18.0
 DISCONNECT BUS 213618   /*FORDAST1      18.0
 DISCONNECT BUS 213619   /*FORDBCT1      18.0
 DISCONNECT BUS 213620   /*FORDBCT2      18.0
 DISCONNECT BUS 213621   /*FORDBST1      18.0
 DISCONNECT BUS 213622   /*FORDML90     230.0
 DISCONNECT BUS 213623   /*FORDML91     230.0
END
CONTINGENCY 'PN_P1-2_PN-115-094_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
END
CONTINGENCY 'PL_10_P12_000085_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 200011 CKT 1   /*JUNI         500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-230-17B25_SRT-A'
 DISCONNECT BRANCH FROM BUS 200675 TO BUS 200924 CKT 1   /*26E.TWANDA   230.0 - 26CANYON     230.0
 DISCONNECT BRANCH FROM BUS 200677 TO BUS 200706 CKT 4   /*26NO MESHO   115.0 - 26N.MESHPN   230.0
 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200924 CKT 1   /*26N.MESHPN   230.0 - 26CANYON     230.0
END
CONTINGENCY 'PN_P2-3_PN-230-997-DRT-067_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200677 CKT 4          /*26N.MESHPN   230.0 - 26NO MESHO   115.0
 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200924 CKT 1          /*26N.MESHPN   230.0 - 26CANYON     230.0
 SET POSTCONTRATING 813 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
 SET PRECONTRATING 678 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
END
CONTINGENCY 'AP_P2-3_WP-230-708C_SRT-A'
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235971 CKT 1   /*01ELKO       230.0 - 01SQUABHLLW  230.0
 DISCONNECT BRANCH FROM BUS 235971 TO BUS 235972 CKT 1   /*01SQUABHLLW  230.0 - 01SQUABHLLW  138.0
END
CONTINGENCY 'AP_P2-3_WP-230-708DT_SRT-A'
 DISCONNECT BRANCH FROM BUS 235971 TO BUS 200581 CKT 1   /*01SQUABHLLW  230.0 - 26FOREST     230.0
 DISCONNECT BRANCH FROM BUS 235971 TO BUS 235972 CKT 1   /*01SQUABHLLW  230.0 - 01SQUABHLLW  138.0
END
CONTINGENCY 'AP_P2-3_WP-230-708AT_SRT-A'
 DISCONNECT BRANCH FROM BUS 235971 TO BUS 200581 CKT 1   /*01SQUABHLLW  230.0 - 26FOREST     230.0
 REDUCE BUS 235709 SHUNT BY 100 PERCENT                  /*01SQUAB_SVC   24.0
END
CONTINGENCY 'AP_P2-3_WP-230-456_SRT-A'
 DISCONNECT BRANCH FROM BUS 235219 TO BUS 235970 CKT 1    /*01MILESB     230.0 - 01DALE       230.0
 DISCONNECT BRANCH FROM BUS 236745 TO BUS 235219 CKT 81   /*01MILESBG     46.0 - 01MILESB     230.0
 DISCONNECT BRANCH FROM BUS 236745 TO BUS 235219 CKT 82   /*01MILESBG     46.0 - 01MILESB     230.0
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1    /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
CONTINGENCY 'AP_P2-2_WP-230-004_SRT-A'
 DISCONNECT BRANCH FROM BUS 235219 TO BUS 236745 CKT 82   /*01MILESB     230.0 - 01MILESBG     46.0
 DISCONNECT BRANCH FROM BUS 235219 TO BUS 238198 CKT 1    /*01MILESB     230.0 - AE2-262_TAP  230.0
END
CONTINGENCY 'AP_P2-3_WP-230-643_SRT-A'
 DISCONNECT BRANCH FROM BUS 236745 TO BUS 235219 CKT 82   /*01MILESBG     46.0 - 01MILESB     230.0
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1    /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
CONTINGENCY 'AP_P2-3_WP-230-450T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200710 TO BUS 235220 CKT 1    /*26SHAWVL 1   230.0 - 01MOSHAN     230.0
 DISCONNECT BRANCH FROM BUS 200908 TO BUS 235220 CKT 1    /*26CHAPMAN+   230.0 - 01MOSHAN     230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235236 CKT 1    /*01ELKO       230.0 - 01QUEHAN     230.0
 DISCONNECT BRANCH FROM BUS 235220 TO BUS 235236 CKT 1    /*01MOSHAN     230.0 - 01QUEHAN     230.0
 DISCONNECT BRANCH FROM BUS 235220 TO BUS 238198 CKT 1    /*01MOSHAN     230.0 - AE2-262_TAP  230.0
 DISCONNECT BRANCH FROM BUS 235236 TO BUS 236732 CKT 81   /*01QUEHAN     230.0 - 01QUEHANNA    46.0
END
CONTINGENCY 'AP_P2-3_WP-230-449T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200710 TO BUS 235220 CKT 1   /*26SHAWVL 1   230.0 - 01MOSHAN     230.0
 DISCONNECT BRANCH FROM BUS 200908 TO BUS 235220 CKT 1   /*26CHAPMAN+   230.0 - 01MOSHAN     230.0
 DISCONNECT BRANCH FROM BUS 235220 TO BUS 235236 CKT 1   /*01MOSHAN     230.0 - 01QUEHAN     230.0
 DISCONNECT BRANCH FROM BUS 235220 TO BUS 238198 CKT 1   /*01MOSHAN     230.0 - AE2-262_TAP  230.0
END
CONTINGENCY 'AP_P1-2_WP-230-005A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1   /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
CONTINGENCY 'AP_P1-3_WP-230-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 235219 TO BUS 236745 CKT 82   /*01MILESB     230.0 - 01MILESBG     46.0
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1    /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
CONTINGENCY 'AP_P2-3_WP-230-0403-A_SRT-A'
 OPEN BRANCH FROM BUS 235220 TO BUS 200710 CKT 1   /*01MOSHAN     230.0 - 26SHAWVL 1   230.0
 OPEN BRANCH FROM BUS 235220 TO BUS 238198 CKT 1   /*01MOSHAN     230.0 - AE2-262_TAP  230.0
END
CONTINGENCY 'AP_P2-2_WP-138-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 200763 CKT 1   /*01SOCIAL     138.0 - 26BLAIRSVL   138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235241 CKT 1   /*01SOCIAL     138.0 - 01SALTSB     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235973 CKT 2   /*01SOCIAL     138.0 - 01SOCIAL H    25.0
 DISCONNECT BUS 235253                                   /*01SOCIAL     138.0
END
CONTINGENCY 'AP_P2-2_WP-138-036_SRT-A'
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235173 CKT 1    /*01LOYALH3    138.0 - 01EDGEWT     138.0
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235617 CKT ZB   /*01LOYALH3    138.0 - 01LOYALH2    138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-083_SRT-A'
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235596 CKT 1   /*01EDGEWT     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235618 CKT 1   /*01EDGEWT     138.0 - 01LOYALH3    138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 236469 CKT 1   /*01EDGEWT     138.0 - 01EDGEWATR    25.0
 DISCONNECT BRANCH FROM BUS 235178 TO BUS 235264 CKT 1   /*01ETHEL      138.0 - 01VASC       138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235596 CKT 1   /*01VASC       138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235975 CKT 1   /*01VASC       138.0 - 01VASCO       25.0
 DISCONNECT BRANCH FROM BUS 235617 TO BUS 235213 CKT 1   /*01LOYALH2    138.0 - 01LUXOR      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-8I_SRT-A'
 DISCONNECT BRANCH FROM BUS 200581 TO BUS 200593 CKT 1   /*26FOREST     230.0 - 26GLADE      230.0
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1   /*26GLADE      230.0 - 26LEWIS RN   230.0
END
CONTINGENCY 'PN_P7-1_PN-230-002A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200581 CKT 1   /*26GLADE      230.0 - 26FOREST     230.0
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1   /*26GLADE      230.0 - 26LEWIS RN   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-006_SRT-A'
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200581 CKT 1   /*26GLADE      230.0 - 26FOREST     230.0
END
CONTINGENCY 'PN_P2-2_PN-115-064_SRT-A'
 DISCONNECT BUS 200671   /*26NILES VA   115.0
END
CONTINGENCY 'PN_P1-2_PN-230-028_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 970712 CKT 1   /*26LEWIS RN   230.0 - AG2-456 TP   230.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'PN_P2-3_PN-230-39C_SRT-A'
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 200705 CKT 2   /*26LEWIS RN   230.0 - 26LEWS RN2    34.5
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 970712 CKT 1   /*26LEWIS RN   230.0 - AG2-456 TP   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT32_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235104 CKT 1                /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-002_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 235104 CKT 1          /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2426 BRANCH FROM BUS 200011 TO BUS 200009 CKT 1 /*KEYSTONE     500.0 - JUNI         500.0
END
CONTINGENCY 'PN_P1-2_PN-230-036_SRT-A'
 DISCONNECT BRANCH FROM BUS 200675 TO BUS 200949 CKT 1   /*26E.TWANDA   230.0 - AA1-082 MAIN 230.0
END
CONTINGENCY 'PN_P1-1_PN-230-018_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203923   /*AA1-082 G2    23.0
END
CONTINGENCY 'PN_P2-2_PN-345-1154-W_SRT-A'
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 1 STEP 1           /*26MAINESBURG 345.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 2 STEP 1           /*26MAINESBURG 345.0
END
CONTINGENCY 'AP_P2-2_WP-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 200726 CKT 1   /*01ELKO       230.0 - 26SHAWVL 2   230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235158 CKT 1   /*01ELKO       230.0 - 01CARB       230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235236 CKT 1   /*01ELKO       230.0 - 01QUEHAN     230.0
END
CONTINGENCY 'PN_P2-3_PN-230-020-DRT_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200924 CKT 1          /*26N.MESHPN   230.0 - 26CANYON     230.0
 SET POSTCONTRATING 813 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
 SET PRECONTRATING 678 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
END
CONTINGENCY 'PN_P2-3_PN-230-997-DRT-068_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200924 TO BUS 200675 CKT 1          /*26CANYON     230.0 - 26E.TWANDA   230.0
 DISCONNECT BRANCH FROM BUS 200924 TO BUS 200706 CKT 1          /*26CANYON     230.0 - 26N.MESHPN   230.0
 SET POSTCONTRATING 813 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
 SET PRECONTRATING 678 BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN   230.0 - 26OXBOW      230.0
END
CONTINGENCY 'PN_P2-3_PN-230-3C_SRT-A'
 DISCONNECT BRANCH FROM BUS 200675 TO BUS 200924 CKT 1   /*26E.TWANDA   230.0 - 26CANYON     230.0
 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200924 CKT 1   /*26N.MESHPN   230.0 - 26CANYON     230.0
END
CONTINGENCY 'PN_P2-3_PN-230-997-DRT-055_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200675 TO BUS 200924 CKT 1          /*26E.TWANDA   230.0 - 26CANYON     230.0
 DISCONNECT BRANCH FROM BUS 200924 TO BUS 200706 CKT 1          /*26CANYON     230.0 - 26N.MESHPN   230.0
 SET POSTCONTRATING 1156 BRANCH FROM BUS 200675 TO BUS 200949 CKT 1 /*26E.TWANDA   230.0 - AA1-082 MAIN 230.0
 SET PRECONTRATING 968 BRANCH FROM BUS 200675 TO BUS 200949 CKT 1 /*26E.TWANDA   230.0 - AA1-082 MAIN 230.0
END
CONTINGENCY 'PN_P2-2_PN-115-068T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200676 TO BUS 130836 CKT 1   /*26E.SAYRE    115.0 - N.WAV115     115.0
 DISCONNECT BRANCH FROM BUS 200676 TO BUS 200688 CKT 3   /*26E.SAYRE    115.0 - 26E SAYRE1    34.5
END
CONTINGENCY 'PN_P2-2_PN-115-069_SRT-A'
 DISCONNECT BRANCH FROM BUS 200676 TO BUS 200674 CKT 1   /*26E.SAYRE    115.0 - 26TOWANDA    115.0
 DISCONNECT BRANCH FROM BUS 200676 TO BUS 200882 CKT 1   /*26E.SAYRE    115.0 - 26E SAYRE2    34.5
END
235139 to 235138 ckt 1
235121 to 235204 ckt 1
235129 to 235121 ckt 2
235240 to 235202 ckt 1
235970 to 235248 ckt 1
235174 to 235159 ckt 1
235282 to 235240 ckt 1
235197 to 235152 ckt 1
235203 to 235197 ckt 1
235204 to 235139 ckt 1
235248 to 200513 ckt 1
200763 to 235253 ckt 1
200924 to 200706 ckt 1
200912 to 200005 ckt 3
200675 to 200924 ckt 1
200593 to 200811 ckt 1
999266 to 200767 ckt S
200767 to 200795 ckt 1
200769 to 999266 ckt S
200810 to 999278 ckt 4
200513 to 208004 ckt 1
200677 to 200706 ckt 3
200713 to 200714 ckt 1
200714 to 200727 ckt ZB
200726 to 235248 ckt 1
200795 to 200810 ckt 1
203800 to 200582 ckt 1
238198 to 235219 ckt 1
972074 to 203800 ckt 1
999278 to 200011 ckt 4
200011 to 235118 ckt 1
130836 to 200676 ckt 1
130838 to 200680 ckt 1

Winter Peak Analysis

The New Service Request AH1-357 was evaluated as a 20.0 MW (12.0 MW Capacity) injection in the PENELEC area.

AH1-357 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (20.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC100.08 %971.0B971.740.28
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301_SRT-A
BreakerAC100.08 %971.0B971.740.28

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:971.74
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
345.063
20083926HOMER C3
50/50
365.295
20088926STNY CRK
Solar/Wind Helper
0.103
20089026BF_G21_K23
Solar/Wind Helper
0.037
20089126CSLMN_L13
Solar/Wind Helper
0.041
20089226LOOKOUT
Solar/Wind Helper
0.08
20092526R32
Solar/Wind Helper
0.159
20326126BLOSSBCT
50/50
5.551
20328326MANOR_T86
50/50
0.276
20334926Z1-069 C
Solar/Wind Harmer
12.631
20335026MILZ1-092
50/50
5.33
20335126GROZ1-110
50/50
3.798
20335226CANZ2-011
50/50
0.204
20088626ARWF_N39
Solar/Wind Helper
0.039
20303426NA_O38_P22
Solar/Wind Helper
0.035
203922AA1-082 G1
50/50
3.809
203923AA1-082 G2
50/50
3.809
203940AF1-140 C
Solar/Wind Helper
0.045
203948AG1-140 C
Solar/Wind Harmer
0.013
203926AA2-133 GEN
50/50
1.068
238206AE2-263_GEN
Solar/Wind Harmer
0
238215AE2-248 C
Solar/Wind Harmer
0.041
216419AE2-001 C
Solar/Wind Harmer
0.054
203962AF1-287 GEN
Solar/Wind Harmer
0.071
20120126WRREN CT
50/50
9.435
203854AF2-039 C
Solar/Wind Harmer
0
203855AF2-088 C
Solar/Wind Harmer
0
203813AE2-344_GEN
Solar/Wind Harmer
0.413
203961AE2-224 GEN
Solar/Wind Helper
0.305
203804AE2-113_GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.021
203859AF2-294 C
Solar/Wind Harmer
0.2
200917MEHOOPANY_G
Solar/Wind Harmer
11.205
970679AG2-439 GEN
Solar/Wind Harmer
0.056
200642SENECA#1
50/50
2.253
200643SENECA#2
50/50
2.127
200644SENECA#3
50/50
0.289
944411AF1-106 GEN
Solar/Wind Harmer
0
944411AF1-106 GEN
Solar/Wind Harmer
5.045
944781AF1-143 GEN
Solar/Wind Helper
0.267
966771AG1-548 GEN
Solar/Wind Harmer
0.554
966771AG1-548 GEN
Solar/Wind Harmer
1.848
970267AG2-176 GEN
Solar/Wind Harmer
0.444
970305AG2-200 GEN
Solar/Wind Harmer
0.152
970313AG2-206 GEN
Solar/Wind Harmer
0.544
970335AG2-220 GEN
Solar/Wind Harmer
0.353
970337AG2-221 GEN
Solar/Wind Harmer
0.234
970511AG2-327 GEN
Solar/Wind Harmer
0.113
970555AG2-356 GEN
Solar/Wind Harmer
0.234
970677AG2-438 GEN
Solar/Wind Harmer
0.036
970713AG2-456 GEN
Solar/Wind Harmer
1.133
970715AG2-457 GEN
Solar/Wind Harmer
1.133
971127AH1-005 GEN
Solar/Wind Harmer
0.228
971627AH1-313 GEN
Solar/Wind Harmer
0.351
971703AH1-357 GEN
Solar/Wind Harmer
0.283
971705AH1-358 GEN
Solar/Wind Harmer
5.667
971707AH1-359 GEN
Solar/Wind Harmer
0.283
971709AH1-360 GEN
Solar/Wind Harmer
5.667
971931AH1-490 GEN
Solar/Wind Harmer
0.069
971933AH1-491 GEN
Solar/Wind Harmer
0.073
972075AH1-587 GEN
Solar/Wind Harmer
2.4
972077AH1-588 GEN
Solar/Wind Harmer
3.4
972079AH1-589 GEN
Solar/Wind Harmer
48.172
972169AH1-667 GEN
Solar/Wind Harmer
0.059
20398826ARMNA MT
Solar/Wind Harmer
13.727
941421AE2-139 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
0.276
961581Q1080_CY23
External Queue
3.189760208129883
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.709
G-007ALTFEXP_G-007A->PJM
CMTX
0.574
VFTLTFEXP_VFT->PJM
CMTX
2.069
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.395
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.085
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.265
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:971.74
MW Contribution:0.28
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
345.063
20083926HOMER C3
50/50
365.295
20088926STNY CRK
Solar/Wind Helper
0.103
20089026BF_G21_K23
Solar/Wind Helper
0.037
20089126CSLMN_L13
Solar/Wind Helper
0.041
20089226LOOKOUT
Solar/Wind Helper
0.08
20092526R32
Solar/Wind Helper
0.159
20326126BLOSSBCT
50/50
5.551
20328326MANOR_T86
50/50
0.276
20334926Z1-069 C
Solar/Wind Harmer
12.631
20335026MILZ1-092
50/50
5.33
20335126GROZ1-110
50/50
3.798
20335226CANZ2-011
50/50
0.204
20088626ARWF_N39
Solar/Wind Helper
0.039
20303426NA_O38_P22
Solar/Wind Helper
0.035
203922AA1-082 G1
50/50
3.809
203923AA1-082 G2
50/50
3.809
203940AF1-140 C
Solar/Wind Helper
0.045
203948AG1-140 C
Solar/Wind Harmer
0.013
203926AA2-133 GEN
50/50
1.068
238206AE2-263_GEN
Solar/Wind Harmer
0
238215AE2-248 C
Solar/Wind Harmer
0.041
216419AE2-001 C
Solar/Wind Harmer
0.054
203962AF1-287 GEN
Solar/Wind Harmer
0.071
20120126WRREN CT
50/50
9.435
203854AF2-039 C
Solar/Wind Harmer
0
203855AF2-088 C
Solar/Wind Harmer
0
203813AE2-344_GEN
Solar/Wind Harmer
0.413
203961AE2-224 GEN
Solar/Wind Helper
0.305
203804AE2-113_GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.021
203859AF2-294 C
Solar/Wind Harmer
0.2
200917MEHOOPANY_G
Solar/Wind Harmer
11.205
970679AG2-439 GEN
Solar/Wind Harmer
0.056
200642SENECA#1
50/50
2.253
200643SENECA#2
50/50
2.127
200644SENECA#3
50/50
0.289
944411AF1-106 GEN
Solar/Wind Harmer
0
944411AF1-106 GEN
Solar/Wind Harmer
5.045
944781AF1-143 GEN
Solar/Wind Helper
0.267
966771AG1-548 GEN
Solar/Wind Harmer
0.554
966771AG1-548 GEN
Solar/Wind Harmer
1.848
970267AG2-176 GEN
Solar/Wind Harmer
0.444
970305AG2-200 GEN
Solar/Wind Harmer
0.152
970313AG2-206 GEN
Solar/Wind Harmer
0.544
970335AG2-220 GEN
Solar/Wind Harmer
0.353
970337AG2-221 GEN
Solar/Wind Harmer
0.234
970511AG2-327 GEN
Solar/Wind Harmer
0.113
970555AG2-356 GEN
Solar/Wind Harmer
0.234
970677AG2-438 GEN
Solar/Wind Harmer
0.036
970713AG2-456 GEN
Solar/Wind Harmer
1.133
970715AG2-457 GEN
Solar/Wind Harmer
1.133
971127AH1-005 GEN
Solar/Wind Harmer
0.228
971627AH1-313 GEN
Solar/Wind Harmer
0.351
971703AH1-357 GEN
Solar/Wind Harmer
0.283
971705AH1-358 GEN
Solar/Wind Harmer
5.667
971707AH1-359 GEN
Solar/Wind Harmer
0.283
971709AH1-360 GEN
Solar/Wind Harmer
5.667
971931AH1-490 GEN
Solar/Wind Harmer
0.069
971933AH1-491 GEN
Solar/Wind Harmer
0.073
972075AH1-587 GEN
Solar/Wind Harmer
2.4
972077AH1-588 GEN
Solar/Wind Harmer
3.4
972079AH1-589 GEN
Solar/Wind Harmer
48.172
972169AH1-667 GEN
Solar/Wind Harmer
0.059
20398826ARMNA MT
Solar/Wind Harmer
13.727
941421AE2-139 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
0.276
961581Q1080_CY23
External Queue
3.189760208129883
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.709
G-007ALTFEXP_G-007A->PJM
CMTX
0.574
VFTLTFEXP_VFT->PJM
CMTX
2.069
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.395
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.085
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.265
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1          /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1   /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
END
200769 to 999266 ckt S

Light Load Analysis

The New Service Request AH1-357 was evaluated as a 20.0 MW injection

AH1-357 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 180.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC114.75 %151.0B173.270.59
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC104.16 %659.0B686.421.93
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC104.16 %659.0B686.421.93
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC104.15 %659.0B686.351.93
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC152.48 %151.0B230.250.79
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC152.48 %151.0B230.250.79
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC152.27 %151.0B229.930.8
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC123.04 %151.0B185.790.64
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC122.49 %151.0B184.970.65
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC154.09 %151.0B232.670.79
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC154.09 %151.0B232.670.79
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-4_SRT-A
BreakerAC153.87 %151.0B232.340.8
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC124.67 %151.0B188.250.64
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC124.12 %151.0B187.430.65
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC113.72 %151.0B171.710.59
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC128.94 %824.0B1062.513.05
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-301_SRT-A
BreakerAC128.94 %824.0B1062.513.05
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P1-2_WP-345-311T_SRT-A
SingleAC128.53 %824.0B1059.093.05
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC127.46 %824.0B1050.253.23
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-230-001T_SRT-A
BusAC127.46 %824.0B1050.253.23
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Base Case
SingleAC127.41 %647.0A824.372.56
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-345-001T_SRT-A
BusAC126.35 %824.0B1041.163.23
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC126.18 %824.0B1039.693.23
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-307-DRT-010_SRT-A
BreakerAC126.02 %824.0B1038.382.99
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-345-0183-308_SRT-A
BreakerAC126.02 %824.0B1038.382.99
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P7-1_PN-230-002A_SRT-A
TowerAC106.29 %824.0B875.843.06
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC106.03 %824.0B873.672.75
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC129.37 %824.0B1066.043.05
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-301_SRT-A
BreakerAC129.37 %824.0B1066.043.05
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P1-2_WP-345-311T_SRT-A
SingleAC128.96 %824.0B1062.633.05
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Base Case
SingleAC127.59 %647.0A825.52.56
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC127.54 %824.0B1050.963.23
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-230-001T_SRT-A
BusAC127.54 %824.0B1050.963.23
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-345-001T-DRT-001_SRT-A
BusAC126.48 %824.0B1042.233.23
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC126.3 %824.0B1040.753.23
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-308_SRT-A
BreakerAC126.18 %824.0B1039.722.99
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-345-0183-307-DRT-010_SRT-A
BreakerAC126.18 %824.0B1039.722.99
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P7-1_PN-230-002A_SRT-A
TowerAC106.46 %824.0B877.193.06
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P7-1_WPP-138-053A_SRT-A
TowerAC106.2 %824.0B875.062.75
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P1-2_PN-230-028_SRT-A-1
SingleAC148.81 %160.0B238.11.65
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P1-2_PN-230-008_SRT-A
SingleAC146.64 %160.0B234.621.65
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P2-3_PN-230-39C_SRT-A
BreakerAC145.42 %160.0B232.671.65
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P2-3_PN-230-39B_SRT-A
BreakerAC144.96 %160.0B231.941.65
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
PN_P7-1_PN-230-002A_SRT-A
TowerAC124.98 %160.0B199.971.59
GD2PENELEC
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Base Case
SingleAC105.8 %133.0A140.710.84
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P1-2_PN-230-028_SRT-A-1
SingleAC123.0 %160.0B196.811.66
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P1-2_PN-230-008_SRT-A
SingleAC120.85 %160.0B193.361.66
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P2-3_PN-230-39C_SRT-A
BreakerAC119.66 %160.0B191.461.66
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P2-3_PN-230-39B_SRT-A
BreakerAC119.22 %160.0B190.761.66
GD2PENELEC
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
PN_P7-1_PN-230-002A_SRT-A
TowerAC102.41 %160.0B163.861.6

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.75 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:173.27
MW Contribution:0.59
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.311
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.406
970647AG2-420 GEN
Solar/Wind Harmer
0.9
972079AH1-589 GEN
Solar/Wind Harmer
9.356
971703AH1-357 GEN
Solar/Wind Harmer
0.594
971707AH1-359 GEN
Solar/Wind Harmer
0.594
970715AG2-457 GEN
Solar/Wind Harmer
2.378
203962AF1-287 GEN
Solar/Wind Harmer
0.544
971185AH1-051 GEN
Solar/Wind Harmer
1.406
971933AH1-491 GEN
Solar/Wind Harmer
0.621
20083926HOMER C3
50/50
39.656
238219AF1-167 C
Solar/Wind Harmer
1.022
203848AF2-166 C
Solar/Wind Harmer
1.023
203813AE2-344_GEN
Solar/Wind Harmer
3.153
971355AH1-158 GEN
Solar/Wind Harmer
2.603
971709AH1-360 GEN
Solar/Wind Harmer
1.101
20334926Z1-069 C
Solar/Wind Harmer
1.546
970663AG2-429 GEN
Solar/Wind Harmer
3.451
971705AH1-358 GEN
Solar/Wind Harmer
1.101
971183AH1-050 GEN
Solar/Wind Harmer
2.343
957161AF2-010 GEN
Solar/Wind Harmer
2.428
966771AG1-548 GEN
Solar/Wind Harmer
4.557
20083826HOMER C2
50/50
33.153
972077AH1-588 GEN
Solar/Wind Harmer
7.133
966451AG1-514 GEN
50/50
Charging
0.98
972075AH1-587 GEN
Solar/Wind Harmer
6.055
945751AF1-240 GEN
Solar/Wind Harmer
0.656
970663AG2-429 GEN
Solar/Wind Harmer
5.424
971055AG2-654 GEN
Solar/Wind Harmer
0.936
971931AH1-490 GEN
Solar/Wind Harmer
0.547
970713AG2-456 GEN
Solar/Wind Harmer
2.378
970647AG2-420 GEN
Solar/Wind Harmer
0.417
971865AH1-452 GEN
Solar/Wind Harmer
0.694
970267AG2-176 GEN
Solar/Wind Harmer
4.989
970305AG2-200 GEN
Solar/Wind Harmer
0.562
G-007ALTFEXP_G-007A->PJM
CMTX
1.376
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.642
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.021
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.713
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.177
VFTLTFEXP_VFT->PJM
CMTX
3.845

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.16 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:686.42
MW Contribution:1.93
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.188
971933AH1-491 GEN
Solar/Wind Harmer
1.018
20083926HOMER C3
50/50
226.64
203813AE2-344_GEN
Solar/Wind Harmer
8.604
20083826HOMER C2
50/50
185.988
972077AH1-588 GEN
Solar/Wind Harmer
23.132
970313AG2-206 GEN
Solar/Wind Harmer
3.577
972075AH1-587 GEN
Solar/Wind Harmer
14.974
966771AG1-548 GEN
Solar/Wind Harmer
7.931
971705AH1-358 GEN
Solar/Wind Harmer
3.57
944411AF1-106 GEN
Solar/Wind Harmer
2.966
971931AH1-490 GEN
Solar/Wind Harmer
1.498
20334926Z1-069 C
Solar/Wind Harmer
5.546
971709AH1-360 GEN
Solar/Wind Harmer
3.57
972079AH1-589 GEN
Solar/Wind Harmer
30.343
971703AH1-357 GEN
Solar/Wind Harmer
1.928
971707AH1-359 GEN
Solar/Wind Harmer
1.928
20398826ARMNA MT
Solar/Wind Harmer
5.454
970335AG2-220 GEN
Solar/Wind Harmer
2.326
970715AG2-457 GEN
Solar/Wind Harmer
7.711
203962AF1-287 GEN
Solar/Wind Harmer
1.478
203963AG1-253 GEN
Solar/Wind Harmer
0.287
203859AF2-294 C
Solar/Wind Harmer
1.352
971127AH1-005 GEN
Solar/Wind Harmer
1.5
970555AG2-356 GEN
Solar/Wind Harmer
1.534
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
2.448
970677AG2-438 GEN
Solar/Wind Harmer
0.509
970267AG2-176 GEN
Solar/Wind Harmer
13.028
970305AG2-200 GEN
Solar/Wind Harmer
1.28
238183AE2-316 GEN
Solar/Wind Helper
3.229
970713AG2-456 GEN
Solar/Wind Harmer
7.711
944411AF1-106 GEN
Solar/Wind Harmer
-0.014
970337AG2-221 GEN
Solar/Wind Harmer
1.534
970511AG2-327 GEN
Solar/Wind Harmer
0.745
946381AF1-302 GEN
Solar/Wind Helper
1.73
961581Q1080_CY23
External Queue
14.219962120056152
G-007ALTFEXP_G-007A->PJM
CMTX
0.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.883
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.867
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.169
VFTLTFEXP_VFT->PJM
CMTX
0.711

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.16 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:686.42
MW Contribution:1.93
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.188
971933AH1-491 GEN
Solar/Wind Harmer
1.018
20083926HOMER C3
50/50
226.64
203813AE2-344_GEN
Solar/Wind Harmer
8.604
20083826HOMER C2
50/50
185.988
972077AH1-588 GEN
Solar/Wind Harmer
23.132
970313AG2-206 GEN
Solar/Wind Harmer
3.577
972075AH1-587 GEN
Solar/Wind Harmer
14.974
966771AG1-548 GEN
Solar/Wind Harmer
7.931
944411AF1-106 GEN
Solar/Wind Harmer
2.966
971931AH1-490 GEN
Solar/Wind Harmer
1.498
20334926Z1-069 C
Solar/Wind Harmer
5.546
971709AH1-360 GEN
Solar/Wind Harmer
3.57
972079AH1-589 GEN
Solar/Wind Harmer
30.343
971703AH1-357 GEN
Solar/Wind Harmer
1.928
971707AH1-359 GEN
Solar/Wind Harmer
1.928
20398826ARMNA MT
Solar/Wind Harmer
5.454
970335AG2-220 GEN
Solar/Wind Harmer
2.326
970715AG2-457 GEN
Solar/Wind Harmer
7.711
203962AF1-287 GEN
Solar/Wind Harmer
1.478
203963AG1-253 GEN
Solar/Wind Harmer
0.287
203859AF2-294 C
Solar/Wind Harmer
1.352
971127AH1-005 GEN
Solar/Wind Harmer
1.5
970555AG2-356 GEN
Solar/Wind Harmer
1.534
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
2.448
970677AG2-438 GEN
Solar/Wind Harmer
0.509
970267AG2-176 GEN
Solar/Wind Harmer
13.028
970305AG2-200 GEN
Solar/Wind Harmer
1.28
238183AE2-316 GEN
Solar/Wind Helper
3.229
970713AG2-456 GEN
Solar/Wind Harmer
7.711
944411AF1-106 GEN
Solar/Wind Harmer
-0.014
971705AH1-358 GEN
Solar/Wind Harmer
3.57
970337AG2-221 GEN
Solar/Wind Harmer
1.534
970511AG2-327 GEN
Solar/Wind Harmer
0.745
946381AF1-302 GEN
Solar/Wind Helper
1.73
961581Q1080_CY23
External Queue
14.219962120056152
G-007ALTFEXP_G-007A->PJM
CMTX
0.146
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.883
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.867
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.169
VFTLTFEXP_VFT->PJM
CMTX
0.711

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.15 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:686.35
MW Contribution:1.93
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.188
971933AH1-491 GEN
Solar/Wind Harmer
1.019
20083926HOMER C3
50/50
226.668
203813AE2-344_GEN
Solar/Wind Harmer
8.606
20083826HOMER C2
50/50
186.011
972077AH1-588 GEN
Solar/Wind Harmer
23.143
970313AG2-206 GEN
Solar/Wind Harmer
3.579
972075AH1-587 GEN
Solar/Wind Harmer
14.986
966771AG1-548 GEN
Solar/Wind Harmer
7.934
944411AF1-106 GEN
Solar/Wind Harmer
2.967
971931AH1-490 GEN
Solar/Wind Harmer
1.499
20334926Z1-069 C
Solar/Wind Harmer
5.548
971709AH1-360 GEN
Solar/Wind Harmer
3.571
972079AH1-589 GEN
Solar/Wind Harmer
30.357
971703AH1-357 GEN
Solar/Wind Harmer
1.929
971707AH1-359 GEN
Solar/Wind Harmer
1.929
20398826ARMNA MT
Solar/Wind Harmer
5.456
970335AG2-220 GEN
Solar/Wind Harmer
2.327
970715AG2-457 GEN
Solar/Wind Harmer
7.714
203962AF1-287 GEN
Solar/Wind Harmer
1.479
203963AG1-253 GEN
Solar/Wind Harmer
0.287
203859AF2-294 C
Solar/Wind Harmer
1.352
971127AH1-005 GEN
Solar/Wind Harmer
1.501
970555AG2-356 GEN
Solar/Wind Harmer
1.534
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
2.449
970677AG2-438 GEN
Solar/Wind Harmer
0.509
970267AG2-176 GEN
Solar/Wind Harmer
13.031
970305AG2-200 GEN
Solar/Wind Harmer
1.281
238183AE2-316 GEN
Solar/Wind Helper
3.227
970713AG2-456 GEN
Solar/Wind Harmer
7.714
944411AF1-106 GEN
Solar/Wind Harmer
-0.014
971705AH1-358 GEN
Solar/Wind Harmer
3.571
970337AG2-221 GEN
Solar/Wind Harmer
1.534
970511AG2-327 GEN
Solar/Wind Harmer
0.746
946381AF1-302 GEN
Solar/Wind Helper
1.729
961581Q1080_CY23
External Queue
14.218321800231934
G-007ALTFEXP_G-007A->PJM
CMTX
0.149
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.896
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.235
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.857
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.174
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.169
VFTLTFEXP_VFT->PJM
CMTX
0.718

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.48 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:230.25
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.345
966771AG1-548 GEN
Solar/Wind Harmer
1.572
970555AG2-356 GEN
Solar/Wind Harmer
0.246
970647AG2-420 GEN
Solar/Wind Harmer
0.913
972079AH1-589 GEN
Solar/Wind Harmer
12.489
971703AH1-357 GEN
Solar/Wind Harmer
0.793
971707AH1-359 GEN
Solar/Wind Harmer
0.793
20398826ARMNA MT
Solar/Wind Harmer
2.02
970715AG2-457 GEN
Solar/Wind Harmer
3.174
203962AF1-287 GEN
Solar/Wind Harmer
0.638
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.405
971933AH1-491 GEN
Solar/Wind Harmer
0.69
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.478
238219AF1-167 C
Solar/Wind Harmer
0.935
203848AF2-166 C
Solar/Wind Harmer
0.985
203813AE2-344_GEN
Solar/Wind Harmer
3.698
971355AH1-158 GEN
Solar/Wind Harmer
2.602
971709AH1-360 GEN
Solar/Wind Harmer
1.469
20334926Z1-069 C
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
3.229
971705AH1-358 GEN
Solar/Wind Harmer
1.469
970337AG2-221 GEN
Solar/Wind Harmer
0.598
971183AH1-050 GEN
Solar/Wind Harmer
2.342
957161AF2-010 GEN
Solar/Wind Harmer
2.684
20083826HOMER C2
50/50
53.733
972077AH1-588 GEN
Solar/Wind Harmer
9.521
972075AH1-587 GEN
Solar/Wind Harmer
7.557
966771AG1-548 GEN
Solar/Wind Harmer
5.095
970663AG2-429 GEN
Solar/Wind Harmer
5.074
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.64
944411AF1-106 GEN
Solar/Wind Harmer
1.096
970713AG2-456 GEN
Solar/Wind Harmer
3.174
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
945751AF1-240 GEN
Solar/Wind Harmer
0.559
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.673
970305AG2-200 GEN
Solar/Wind Harmer
0.672
G-007ALTFEXP_G-007A->PJM
CMTX
0.417
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.45
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.481
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.335
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.131
VFTLTFEXP_VFT->PJM
CMTX
1.275

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.48 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:230.25
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.345
966771AG1-548 GEN
Solar/Wind Harmer
1.572
970555AG2-356 GEN
Solar/Wind Harmer
0.246
970647AG2-420 GEN
Solar/Wind Harmer
0.913
972079AH1-589 GEN
Solar/Wind Harmer
12.489
971703AH1-357 GEN
Solar/Wind Harmer
0.793
971707AH1-359 GEN
Solar/Wind Harmer
0.793
20398826ARMNA MT
Solar/Wind Harmer
2.02
970715AG2-457 GEN
Solar/Wind Harmer
3.174
203962AF1-287 GEN
Solar/Wind Harmer
0.638
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.405
971933AH1-491 GEN
Solar/Wind Harmer
0.69
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.478
238219AF1-167 C
Solar/Wind Harmer
0.935
203848AF2-166 C
Solar/Wind Harmer
0.985
203813AE2-344_GEN
Solar/Wind Harmer
3.698
971355AH1-158 GEN
Solar/Wind Harmer
2.602
971709AH1-360 GEN
Solar/Wind Harmer
1.469
20334926Z1-069 C
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
3.229
971705AH1-358 GEN
Solar/Wind Harmer
1.469
970337AG2-221 GEN
Solar/Wind Harmer
0.598
20083826HOMER C2
50/50
53.733
972077AH1-588 GEN
Solar/Wind Harmer
9.521
972075AH1-587 GEN
Solar/Wind Harmer
7.557
971183AH1-050 GEN
Solar/Wind Harmer
2.342
957161AF2-010 GEN
Solar/Wind Harmer
2.684
966771AG1-548 GEN
Solar/Wind Harmer
5.095
970663AG2-429 GEN
Solar/Wind Harmer
5.074
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.64
944411AF1-106 GEN
Solar/Wind Harmer
1.096
970713AG2-456 GEN
Solar/Wind Harmer
3.174
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
945751AF1-240 GEN
Solar/Wind Harmer
0.559
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.673
970305AG2-200 GEN
Solar/Wind Harmer
0.672
G-007ALTFEXP_G-007A->PJM
CMTX
0.417
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.45
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.481
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.335
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.131
VFTLTFEXP_VFT->PJM
CMTX
1.275

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.27 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:229.93
MW Contribution:0.8
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.346
966771AG1-548 GEN
Solar/Wind Harmer
1.575
970555AG2-356 GEN
Solar/Wind Harmer
0.247
970647AG2-420 GEN
Solar/Wind Harmer
0.914
972079AH1-589 GEN
Solar/Wind Harmer
12.531
971703AH1-357 GEN
Solar/Wind Harmer
0.796
971707AH1-359 GEN
Solar/Wind Harmer
0.796
20398826ARMNA MT
Solar/Wind Harmer
2.027
970715AG2-457 GEN
Solar/Wind Harmer
3.184
203962AF1-287 GEN
Solar/Wind Harmer
0.639
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.407
971933AH1-491 GEN
Solar/Wind Harmer
0.691
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.564
238219AF1-167 C
Solar/Wind Harmer
0.936
203848AF2-166 C
Solar/Wind Harmer
0.986
203813AE2-344_GEN
Solar/Wind Harmer
3.705
971355AH1-158 GEN
Solar/Wind Harmer
2.605
971709AH1-360 GEN
Solar/Wind Harmer
1.474
20334926Z1-069 C
Solar/Wind Harmer
2.125
970663AG2-429 GEN
Solar/Wind Harmer
3.232
971705AH1-358 GEN
Solar/Wind Harmer
1.474
970337AG2-221 GEN
Solar/Wind Harmer
0.6
20083826HOMER C2
50/50
53.804
972077AH1-588 GEN
Solar/Wind Harmer
9.553
972075AH1-587 GEN
Solar/Wind Harmer
7.592
971183AH1-050 GEN
Solar/Wind Harmer
2.345
957161AF2-010 GEN
Solar/Wind Harmer
2.689
966771AG1-548 GEN
Solar/Wind Harmer
5.104
970663AG2-429 GEN
Solar/Wind Harmer
5.078
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.641
944411AF1-106 GEN
Solar/Wind Harmer
1.099
970713AG2-456 GEN
Solar/Wind Harmer
3.184
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
945751AF1-240 GEN
Solar/Wind Harmer
0.56
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.681
970305AG2-200 GEN
Solar/Wind Harmer
0.675
G-007ALTFEXP_G-007A->PJM
CMTX
0.424
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.491
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.08
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.339
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
VFTLTFEXP_VFT->PJM
CMTX
1.296

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.04 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:185.79
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.34
966771AG1-548 GEN
Solar/Wind Harmer
1.54
203804AE2-113_GEN
Solar/Wind Harmer
0
970647AG2-420 GEN
Solar/Wind Harmer
0.981
972079AH1-589 GEN
Solar/Wind Harmer
10.035
971703AH1-357 GEN
Solar/Wind Harmer
0.638
971707AH1-359 GEN
Solar/Wind Harmer
0.638
972169AH1-667 GEN
Solar/Wind Harmer
0.511
970715AG2-457 GEN
Solar/Wind Harmer
2.55
203962AF1-287 GEN
Solar/Wind Harmer
0.598
971185AH1-051 GEN
Solar/Wind Harmer
1.531
971933AH1-491 GEN
Solar/Wind Harmer
0.68
20083926HOMER C3
50/50
42.186
238219AF1-167 C
Solar/Wind Harmer
1.111
203848AF2-166 C
Solar/Wind Harmer
1.112
203813AE2-344_GEN
Solar/Wind Harmer
3.467
971355AH1-158 GEN
Solar/Wind Harmer
2.835
971709AH1-360 GEN
Solar/Wind Harmer
1.181
20334926Z1-069 C
Solar/Wind Harmer
1.648
970663AG2-429 GEN
Solar/Wind Harmer
3.783
971705AH1-358 GEN
Solar/Wind Harmer
1.181
971183AH1-050 GEN
Solar/Wind Harmer
2.551
957161AF2-010 GEN
Solar/Wind Harmer
2.658
966771AG1-548 GEN
Solar/Wind Harmer
4.99
20083826HOMER C2
50/50
35.268
972077AH1-588 GEN
Solar/Wind Harmer
7.65
966451AG1-514 GEN
50/50
Charging
0.673
972075AH1-587 GEN
Solar/Wind Harmer
6.488
945751AF1-240 GEN
Solar/Wind Harmer
0.698
970663AG2-429 GEN
Solar/Wind Harmer
5.945
971055AG2-654 GEN
Solar/Wind Harmer
0.806
971931AH1-490 GEN
Solar/Wind Harmer
0.602
970713AG2-456 GEN
Solar/Wind Harmer
2.55
970647AG2-420 GEN
Solar/Wind Harmer
0.454
970267AG2-176 GEN
Solar/Wind Harmer
5.472
970305AG2-200 GEN
Solar/Wind Harmer
0.609
971865AH1-452 GEN
Solar/Wind Harmer
0.553
G-007ALTFEXP_G-007A->PJM
CMTX
1.094
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.747
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.206
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
VFTLTFEXP_VFT->PJM
CMTX
3.089

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.49 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:184.97
MW Contribution:0.65
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.346
966771AG1-548 GEN
Solar/Wind Harmer
1.568
203804AE2-113_GEN
Solar/Wind Harmer
0
970647AG2-420 GEN
Solar/Wind Harmer
0.999
972079AH1-589 GEN
Solar/Wind Harmer
10.248
971703AH1-357 GEN
Solar/Wind Harmer
0.651
971707AH1-359 GEN
Solar/Wind Harmer
0.651
972169AH1-667 GEN
Solar/Wind Harmer
0.524
970715AG2-457 GEN
Solar/Wind Harmer
2.604
203962AF1-287 GEN
Solar/Wind Harmer
0.609
203963AG1-253 GEN
Solar/Wind Harmer
0.11
971185AH1-051 GEN
Solar/Wind Harmer
1.559
971933AH1-491 GEN
Solar/Wind Harmer
0.692
203948AG1-140 C
Solar/Wind Harmer
0.072
20083926HOMER C3
50/50
43.138
238219AF1-167 C
Solar/Wind Harmer
1.131
203848AF2-166 C
Solar/Wind Harmer
1.133
203813AE2-344_GEN
Solar/Wind Harmer
3.529
971355AH1-158 GEN
Solar/Wind Harmer
2.887
971709AH1-360 GEN
Solar/Wind Harmer
1.206
20334926Z1-069 C
Solar/Wind Harmer
1.684
970663AG2-429 GEN
Solar/Wind Harmer
3.85
971705AH1-358 GEN
Solar/Wind Harmer
1.206
971183AH1-050 GEN
Solar/Wind Harmer
2.599
957161AF2-010 GEN
Solar/Wind Harmer
2.706
966771AG1-548 GEN
Solar/Wind Harmer
5.08
20083826HOMER C2
50/50
36.064
972077AH1-588 GEN
Solar/Wind Harmer
7.813
966451AG1-514 GEN
50/50
Charging
0.725
972075AH1-587 GEN
Solar/Wind Harmer
6.626
945751AF1-240 GEN
Solar/Wind Harmer
0.714
970663AG2-429 GEN
Solar/Wind Harmer
6.049
971055AG2-654 GEN
Solar/Wind Harmer
0.836
971931AH1-490 GEN
Solar/Wind Harmer
0.612
970713AG2-456 GEN
Solar/Wind Harmer
2.604
970647AG2-420 GEN
Solar/Wind Harmer
0.462
970267AG2-176 GEN
Solar/Wind Harmer
5.571
971865AH1-452 GEN
Solar/Wind Harmer
0.599
970305AG2-200 GEN
Solar/Wind Harmer
0.621
G-007ALTFEXP_G-007A->PJM
CMTX
1.159
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.02
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.668
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
VFTLTFEXP_VFT->PJM
CMTX
3.268

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.09 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:232.67
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.345
966771AG1-548 GEN
Solar/Wind Harmer
1.572
970555AG2-356 GEN
Solar/Wind Harmer
0.246
970647AG2-420 GEN
Solar/Wind Harmer
0.913
972079AH1-589 GEN
Solar/Wind Harmer
12.489
971703AH1-357 GEN
Solar/Wind Harmer
0.793
971707AH1-359 GEN
Solar/Wind Harmer
0.793
20398826ARMNA MT
Solar/Wind Harmer
2.02
970715AG2-457 GEN
Solar/Wind Harmer
3.174
203962AF1-287 GEN
Solar/Wind Harmer
0.638
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.405
971933AH1-491 GEN
Solar/Wind Harmer
0.69
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.478
238219AF1-167 C
Solar/Wind Harmer
0.935
203848AF2-166 C
Solar/Wind Harmer
0.985
203813AE2-344_GEN
Solar/Wind Harmer
3.698
971355AH1-158 GEN
Solar/Wind Harmer
2.602
971709AH1-360 GEN
Solar/Wind Harmer
1.469
20334926Z1-069 C
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
3.229
971705AH1-358 GEN
Solar/Wind Harmer
1.469
970337AG2-221 GEN
Solar/Wind Harmer
0.598
971183AH1-050 GEN
Solar/Wind Harmer
2.342
957161AF2-010 GEN
Solar/Wind Harmer
2.684
966771AG1-548 GEN
Solar/Wind Harmer
5.095
20083826HOMER C2
50/50
53.733
972077AH1-588 GEN
Solar/Wind Harmer
9.521
972075AH1-587 GEN
Solar/Wind Harmer
7.557
945751AF1-240 GEN
Solar/Wind Harmer
0.559
970663AG2-429 GEN
Solar/Wind Harmer
5.074
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.64
944411AF1-106 GEN
Solar/Wind Harmer
1.096
970713AG2-456 GEN
Solar/Wind Harmer
3.174
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.673
970305AG2-200 GEN
Solar/Wind Harmer
0.672
G-007ALTFEXP_G-007A->PJM
CMTX
0.417
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.45
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.481
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.335
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.131
VFTLTFEXP_VFT->PJM
CMTX
1.275

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.09 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:232.67
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.345
966771AG1-548 GEN
Solar/Wind Harmer
1.572
970555AG2-356 GEN
Solar/Wind Harmer
0.246
970647AG2-420 GEN
Solar/Wind Harmer
0.913
972079AH1-589 GEN
Solar/Wind Harmer
12.489
971703AH1-357 GEN
Solar/Wind Harmer
0.793
971707AH1-359 GEN
Solar/Wind Harmer
0.793
20398826ARMNA MT
Solar/Wind Harmer
2.02
970715AG2-457 GEN
Solar/Wind Harmer
3.174
203962AF1-287 GEN
Solar/Wind Harmer
0.638
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.405
971933AH1-491 GEN
Solar/Wind Harmer
0.69
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.478
238219AF1-167 C
Solar/Wind Harmer
0.935
203848AF2-166 C
Solar/Wind Harmer
0.985
203813AE2-344_GEN
Solar/Wind Harmer
3.698
971355AH1-158 GEN
Solar/Wind Harmer
2.602
971709AH1-360 GEN
Solar/Wind Harmer
1.469
20334926Z1-069 C
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
3.229
971705AH1-358 GEN
Solar/Wind Harmer
1.469
970337AG2-221 GEN
Solar/Wind Harmer
0.598
971183AH1-050 GEN
Solar/Wind Harmer
2.342
957161AF2-010 GEN
Solar/Wind Harmer
2.684
966771AG1-548 GEN
Solar/Wind Harmer
5.095
20083826HOMER C2
50/50
53.733
972077AH1-588 GEN
Solar/Wind Harmer
9.521
972075AH1-587 GEN
Solar/Wind Harmer
7.557
945751AF1-240 GEN
Solar/Wind Harmer
0.559
970663AG2-429 GEN
Solar/Wind Harmer
5.074
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.64
944411AF1-106 GEN
Solar/Wind Harmer
1.096
970713AG2-456 GEN
Solar/Wind Harmer
3.174
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.673
970305AG2-200 GEN
Solar/Wind Harmer
0.672
G-007ALTFEXP_G-007A->PJM
CMTX
0.417
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.45
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.079
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.481
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.335
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.131
VFTLTFEXP_VFT->PJM
CMTX
1.275

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-4_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.87 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:232.34
MW Contribution:0.8
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.346
966771AG1-548 GEN
Solar/Wind Harmer
1.575
970555AG2-356 GEN
Solar/Wind Harmer
0.247
970647AG2-420 GEN
Solar/Wind Harmer
0.914
972079AH1-589 GEN
Solar/Wind Harmer
12.531
971703AH1-357 GEN
Solar/Wind Harmer
0.796
971707AH1-359 GEN
Solar/Wind Harmer
0.796
20398826ARMNA MT
Solar/Wind Harmer
2.027
970715AG2-457 GEN
Solar/Wind Harmer
3.184
203962AF1-287 GEN
Solar/Wind Harmer
0.639
203963AG1-253 GEN
Solar/Wind Harmer
0.12
971185AH1-051 GEN
Solar/Wind Harmer
1.407
971933AH1-491 GEN
Solar/Wind Harmer
0.691
203948AG1-140 C
Solar/Wind Harmer
0.079
20083926HOMER C3
50/50
65.564
238219AF1-167 C
Solar/Wind Harmer
0.936
203848AF2-166 C
Solar/Wind Harmer
0.986
203813AE2-344_GEN
Solar/Wind Harmer
3.705
971355AH1-158 GEN
Solar/Wind Harmer
2.605
971709AH1-360 GEN
Solar/Wind Harmer
1.474
20334926Z1-069 C
Solar/Wind Harmer
2.125
970663AG2-429 GEN
Solar/Wind Harmer
3.232
971705AH1-358 GEN
Solar/Wind Harmer
1.474
970337AG2-221 GEN
Solar/Wind Harmer
0.6
971183AH1-050 GEN
Solar/Wind Harmer
2.345
957161AF2-010 GEN
Solar/Wind Harmer
2.689
966771AG1-548 GEN
Solar/Wind Harmer
5.104
20083826HOMER C2
50/50
53.804
972077AH1-588 GEN
Solar/Wind Harmer
9.553
972075AH1-587 GEN
Solar/Wind Harmer
7.592
970663AG2-429 GEN
Solar/Wind Harmer
5.078
971055AG2-654 GEN
Solar/Wind Harmer
0.6
971931AH1-490 GEN
Solar/Wind Harmer
0.641
944411AF1-106 GEN
Solar/Wind Harmer
1.099
970713AG2-456 GEN
Solar/Wind Harmer
3.184
944411AF1-106 GEN
Solar/Wind Harmer
-0.005
945751AF1-240 GEN
Solar/Wind Harmer
0.56
970647AG2-420 GEN
Solar/Wind Harmer
0.423
970267AG2-176 GEN
Solar/Wind Harmer
5.681
970305AG2-200 GEN
Solar/Wind Harmer
0.675
G-007ALTFEXP_G-007A->PJM
CMTX
0.424
CBM NorthLTFEXP_CBM-N->PJM
CBM
11.491
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.08
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.339
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
VFTLTFEXP_VFT->PJM
CMTX
1.296

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.67 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:188.25
MW Contribution:0.64
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.34
966771AG1-548 GEN
Solar/Wind Harmer
1.54
203804AE2-113_GEN
Solar/Wind Harmer
0
970647AG2-420 GEN
Solar/Wind Harmer
0.981
972079AH1-589 GEN
Solar/Wind Harmer
10.035
971703AH1-357 GEN
Solar/Wind Harmer
0.638
971707AH1-359 GEN
Solar/Wind Harmer
0.638
972169AH1-667 GEN
Solar/Wind Harmer
0.511
970715AG2-457 GEN
Solar/Wind Harmer
2.55
203962AF1-287 GEN
Solar/Wind Harmer
0.598
971185AH1-051 GEN
Solar/Wind Harmer
1.531
971933AH1-491 GEN
Solar/Wind Harmer
0.68
20083926HOMER C3
50/50
42.186
238219AF1-167 C
Solar/Wind Harmer
1.111
203848AF2-166 C
Solar/Wind Harmer
1.112
203813AE2-344_GEN
Solar/Wind Harmer
3.467
971355AH1-158 GEN
Solar/Wind Harmer
2.835
971709AH1-360 GEN
Solar/Wind Harmer
1.181
20334926Z1-069 C
Solar/Wind Harmer
1.648
970663AG2-429 GEN
Solar/Wind Harmer
3.783
971705AH1-358 GEN
Solar/Wind Harmer
1.181
971183AH1-050 GEN
Solar/Wind Harmer
2.551
957161AF2-010 GEN
Solar/Wind Harmer
2.658
966771AG1-548 GEN
Solar/Wind Harmer
4.99
20083826HOMER C2
50/50
35.268
972077AH1-588 GEN
Solar/Wind Harmer
7.65
966451AG1-514 GEN
50/50
Charging
0.673
972075AH1-587 GEN
Solar/Wind Harmer
6.488
945751AF1-240 GEN
Solar/Wind Harmer
0.698
970663AG2-429 GEN
Solar/Wind Harmer
5.945
971055AG2-654 GEN
Solar/Wind Harmer
0.806
971931AH1-490 GEN
Solar/Wind Harmer
0.602
970713AG2-456 GEN
Solar/Wind Harmer
2.55
970647AG2-420 GEN
Solar/Wind Harmer
0.454
970267AG2-176 GEN
Solar/Wind Harmer
5.472
970305AG2-200 GEN
Solar/Wind Harmer
0.609
971865AH1-452 GEN
Solar/Wind Harmer
0.553
G-007ALTFEXP_G-007A->PJM
CMTX
1.094
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.747
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.206
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
VFTLTFEXP_VFT->PJM
CMTX
3.089

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.12 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:187.43
MW Contribution:0.65
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.346
966771AG1-548 GEN
Solar/Wind Harmer
1.568
203804AE2-113_GEN
Solar/Wind Harmer
0
970647AG2-420 GEN
Solar/Wind Harmer
0.999
972079AH1-589 GEN
Solar/Wind Harmer
10.248
971703AH1-357 GEN
Solar/Wind Harmer
0.651
971707AH1-359 GEN
Solar/Wind Harmer
0.651
972169AH1-667 GEN
Solar/Wind Harmer
0.524
970715AG2-457 GEN
Solar/Wind Harmer
2.604
203962AF1-287 GEN
Solar/Wind Harmer
0.609
203963AG1-253 GEN
Solar/Wind Harmer
0.11
971185AH1-051 GEN
Solar/Wind Harmer
1.559
971933AH1-491 GEN
Solar/Wind Harmer
0.692
203948AG1-140 C
Solar/Wind Harmer
0.072
20083926HOMER C3
50/50
43.138
238219AF1-167 C
Solar/Wind Harmer
1.131
203848AF2-166 C
Solar/Wind Harmer
1.133
203813AE2-344_GEN
Solar/Wind Harmer
3.529
971355AH1-158 GEN
Solar/Wind Harmer
2.887
971709AH1-360 GEN
Solar/Wind Harmer
1.206
20334926Z1-069 C
Solar/Wind Harmer
1.684
970663AG2-429 GEN
Solar/Wind Harmer
3.85
971705AH1-358 GEN
Solar/Wind Harmer
1.206
971183AH1-050 GEN
Solar/Wind Harmer
2.599
957161AF2-010 GEN
Solar/Wind Harmer
2.706
966771AG1-548 GEN
Solar/Wind Harmer
5.08
20083826HOMER C2
50/50
36.064
972077AH1-588 GEN
Solar/Wind Harmer
7.813
966451AG1-514 GEN
50/50
Charging
0.725
972075AH1-587 GEN
Solar/Wind Harmer
6.626
945751AF1-240 GEN
Solar/Wind Harmer
0.714
970663AG2-429 GEN
Solar/Wind Harmer
6.049
971055AG2-654 GEN
Solar/Wind Harmer
0.836
971931AH1-490 GEN
Solar/Wind Harmer
0.612
970713AG2-456 GEN
Solar/Wind Harmer
2.604
970647AG2-420 GEN
Solar/Wind Harmer
0.462
970267AG2-176 GEN
Solar/Wind Harmer
5.571
971865AH1-452 GEN
Solar/Wind Harmer
0.599
970305AG2-200 GEN
Solar/Wind Harmer
0.621
G-007ALTFEXP_G-007A->PJM
CMTX
1.159
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.02
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.668
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
VFTLTFEXP_VFT->PJM
CMTX
3.268

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.72 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:171.71
MW Contribution:0.59
Bus #Bus NameTypeMW Contribution
970677AG2-438 GEN
Solar/Wind Harmer
0.311
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.407
970647AG2-420 GEN
Solar/Wind Harmer
0.9
972079AH1-589 GEN
Solar/Wind Harmer
9.359
971703AH1-357 GEN
Solar/Wind Harmer
0.595
971707AH1-359 GEN
Solar/Wind Harmer
0.595
970715AG2-457 GEN
Solar/Wind Harmer
2.378
203962AF1-287 GEN
Solar/Wind Harmer
0.544
971185AH1-051 GEN
Solar/Wind Harmer
1.406
971933AH1-491 GEN
Solar/Wind Harmer
0.621
20083926HOMER C3
50/50
39.667
238219AF1-167 C
Solar/Wind Harmer
1.022
203848AF2-166 C
Solar/Wind Harmer
1.023
203813AE2-344_GEN
Solar/Wind Harmer
3.154
971355AH1-158 GEN
Solar/Wind Harmer
2.603
971709AH1-360 GEN
Solar/Wind Harmer
1.101
20334926Z1-069 C
Solar/Wind Harmer
1.546
970663AG2-429 GEN
Solar/Wind Harmer
3.452
971705AH1-358 GEN
Solar/Wind Harmer
1.101
971183AH1-050 GEN
Solar/Wind Harmer
2.343
957161AF2-010 GEN
Solar/Wind Harmer
2.429
966771AG1-548 GEN
Solar/Wind Harmer
4.558
20083826HOMER C2
50/50
33.162
972077AH1-588 GEN
Solar/Wind Harmer
7.135
966451AG1-514 GEN
50/50
Charging
0.98
972075AH1-587 GEN
Solar/Wind Harmer
6.056
945751AF1-240 GEN
Solar/Wind Harmer
0.656
970663AG2-429 GEN
Solar/Wind Harmer
5.424
971055AG2-654 GEN
Solar/Wind Harmer
0.936
971931AH1-490 GEN
Solar/Wind Harmer
0.547
970713AG2-456 GEN
Solar/Wind Harmer
2.378
970647AG2-420 GEN
Solar/Wind Harmer
0.417
971865AH1-452 GEN
Solar/Wind Harmer
0.694
970267AG2-176 GEN
Solar/Wind Harmer
4.99
970305AG2-200 GEN
Solar/Wind Harmer
0.563
G-007ALTFEXP_G-007A->PJM
CMTX
1.38
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.65
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.114
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.71
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
VFTLTFEXP_VFT->PJM
CMTX
3.855

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1062.51
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
20083426SW_E13_K22
Solar/Wind Helper
0.119
203962AF1-287 GEN
Solar/Wind Harmer
0.243
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
944411AF1-106 GEN
Solar/Wind Harmer
4.739
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
944411AF1-106 GEN
Solar/Wind Harmer
-0.022
203961AE2-224 GEN
Solar/Wind Helper
1.92
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-301_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-301_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1062.51
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
20083426SW_E13_K22
Solar/Wind Helper
0.119
203962AF1-287 GEN
Solar/Wind Harmer
0.243
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
944411AF1-106 GEN
Solar/Wind Harmer
4.739
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
944411AF1-106 GEN
Solar/Wind Harmer
-0.022
203961AE2-224 GEN
Solar/Wind Helper
1.92
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P1-2_WP-345-311T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P1-2_WP-345-311T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.53 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1059.09
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
203962AF1-287 GEN
Solar/Wind Harmer
0.762
20083426SW_E13_K22
Solar/Wind Helper
0.119
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
203813AE2-344_GEN
Solar/Wind Harmer
0.79
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
203961AE2-224 GEN
Solar/Wind Helper
1.92
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1050.25
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.486
966771AG1-548 GEN
Solar/Wind Harmer
4.343
970677AG2-438 GEN
Solar/Wind Harmer
0.937
20303426NA_O38_P22
Solar/Wind Helper
1.839
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.874
20091526CHSTN_FL
Solar/Wind Helper
0.744
971185AH1-051 GEN
Solar/Wind Harmer
1.267
20083926HOMER C3
50/50
342.464
203813AE2-344_GEN
Solar/Wind Harmer
11.292
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.739
971709AH1-360 GEN
Solar/Wind Harmer
5.978
20334926Z1-069 C
Solar/Wind Harmer
9.031
20088626ARWF_N39
Solar/Wind Helper
2.26
20094526CT_V3-030
Solar/Wind Helper
0.493
971355AH1-158 GEN
Solar/Wind Harmer
2.346
970715AG2-457 GEN
Solar/Wind Harmer
12.912
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.945
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.762
203955AF1-039 C O1
Solar/Wind Helper
0.441
972079AH1-589 GEN
Solar/Wind Harmer
50.81
971703AH1-357 GEN
Solar/Wind Harmer
3.228
971707AH1-359 GEN
Solar/Wind Harmer
3.228
20398826ARMNA MT
Solar/Wind Harmer
8.7
970335AG2-220 GEN
Solar/Wind Harmer
3.746
970647AG2-420 GEN
Solar/Wind Harmer
1.917
20083826HOMER C2
50/50
281.036
972077AH1-588 GEN
Solar/Wind Harmer
38.735
970313AG2-206 GEN
Solar/Wind Harmer
5.764
20089226LOOKOUT
Solar/Wind Helper
0.935
972075AH1-587 GEN
Solar/Wind Harmer
27.753
941231AE2-117 GEN
Solar/Wind Helper
0.385
966771AG1-548 GEN
Solar/Wind Harmer
14.071
957161AF2-010 GEN
Solar/Wind Harmer
7.209
964201AG1-281 GEN
Solar/Wind Helper
0.744
971183AH1-050 GEN
Solar/Wind Harmer
2.111
971705AH1-358 GEN
Solar/Wind Harmer
5.978
970337AG2-221 GEN
Solar/Wind Harmer
2.486
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.445
20088926STNY CRK
Solar/Wind Helper
1.562
944411AF1-106 GEN
Solar/Wind Harmer
4.704
970663AG2-429 GEN
Solar/Wind Harmer
6.985
971931AH1-490 GEN
Solar/Wind Harmer
1.946
20089126CSLMN_L13
Solar/Wind Helper
0.96
20084626FORWARD
Solar/Wind Helper
0.976
20088826HIGHLAND
Solar/Wind Helper
1.989
20089026BF_G21_K23
Solar/Wind Helper
0.76
946071AF1-272 GEN
Solar/Wind Helper
2.922
970713AG2-456 GEN
Solar/Wind Harmer
12.912
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.519
203859AF2-294 C
Solar/Wind Harmer
2.132
971127AH1-005 GEN
Solar/Wind Harmer
2.417
970647AG2-420 GEN
Solar/Wind Harmer
0.887
20092526R32
Solar/Wind Helper
2.295
964391AG1-301 GEN
Solar/Wind Helper
0.396
970305AG2-200 GEN
Solar/Wind Harmer
2.22
970267AG2-176 GEN
Solar/Wind Harmer
16.253
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.482
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.235
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.653
TVALTFEXP_TVA->PJM
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1050.25
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.874
20091526CHSTN_FL
Solar/Wind Helper
0.744
971185AH1-051 GEN
Solar/Wind Harmer
1.267
20083926HOMER C3
50/50
342.464
203813AE2-344_GEN
Solar/Wind Harmer
11.292
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.739
20083826HOMER C2
50/50
281.036
972077AH1-588 GEN
Solar/Wind Harmer
38.735
970313AG2-206 GEN
Solar/Wind Harmer
5.764
20089226LOOKOUT
Solar/Wind Helper
0.935
966771AG1-548 GEN
Solar/Wind Harmer
14.071
957161AF2-010 GEN
Solar/Wind Harmer
7.209
964201AG1-281 GEN
Solar/Wind Helper
0.744
971183AH1-050 GEN
Solar/Wind Harmer
2.111
944411AF1-106 GEN
Solar/Wind Harmer
4.704
970663AG2-429 GEN
Solar/Wind Harmer
6.985
971931AH1-490 GEN
Solar/Wind Harmer
1.946
20089126CSLMN_L13
Solar/Wind Helper
0.96
971709AH1-360 GEN
Solar/Wind Harmer
5.978
20334926Z1-069 C
Solar/Wind Harmer
9.031
20088626ARWF_N39
Solar/Wind Helper
2.26
20094526CT_V3-030
Solar/Wind Helper
0.493
971355AH1-158 GEN
Solar/Wind Harmer
2.346
972079AH1-589 GEN
Solar/Wind Harmer
50.81
971703AH1-357 GEN
Solar/Wind Harmer
3.228
971707AH1-359 GEN
Solar/Wind Harmer
3.228
20398826ARMNA MT
Solar/Wind Harmer
8.7
970335AG2-220 GEN
Solar/Wind Harmer
3.746
970647AG2-420 GEN
Solar/Wind Harmer
1.917
20084626FORWARD
Solar/Wind Helper
0.976
970715AG2-457 GEN
Solar/Wind Harmer
12.912
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.945
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.762
203955AF1-039 C O1
Solar/Wind Helper
0.441
946071AF1-272 GEN
Solar/Wind Helper
2.922
20088826HIGHLAND
Solar/Wind Helper
1.989
20089026BF_G21_K23
Solar/Wind Helper
0.76
203859AF2-294 C
Solar/Wind Harmer
2.132
971127AH1-005 GEN
Solar/Wind Harmer
2.417
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.486
966771AG1-548 GEN
Solar/Wind Harmer
4.343
970677AG2-438 GEN
Solar/Wind Harmer
0.937
20303426NA_O38_P22
Solar/Wind Helper
1.839
970647AG2-420 GEN
Solar/Wind Harmer
0.887
20092526R32
Solar/Wind Helper
2.295
964391AG1-301 GEN
Solar/Wind Helper
0.396
972075AH1-587 GEN
Solar/Wind Harmer
27.753
941231AE2-117 GEN
Solar/Wind Helper
0.385
970305AG2-200 GEN
Solar/Wind Harmer
2.22
970267AG2-176 GEN
Solar/Wind Harmer
16.253
970713AG2-456 GEN
Solar/Wind Harmer
12.912
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.519
971705AH1-358 GEN
Solar/Wind Harmer
5.978
970337AG2-221 GEN
Solar/Wind Harmer
2.486
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.445
20088926STNY CRK
Solar/Wind Helper
1.562
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.482
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.235
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.653
TVALTFEXP_TVA->PJM
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.41 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:824.37
MW Contribution:2.56
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
1.972
966771AG1-548 GEN
Solar/Wind Harmer
3.447
970677AG2-438 GEN
Solar/Wind Harmer
0.744
20303426NA_O38_P22
Solar/Wind Helper
1.457
972079AH1-589 GEN
Solar/Wind Harmer
40.313
971703AH1-357 GEN
Solar/Wind Harmer
2.561
971707AH1-359 GEN
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
6.903
970335AG2-220 GEN
Solar/Wind Harmer
2.972
970647AG2-420 GEN
Solar/Wind Harmer
1.521
20084626FORWARD
Solar/Wind Helper
0.774
20088826HIGHLAND
Solar/Wind Helper
1.576
20089026BF_G21_K23
Solar/Wind Helper
0.602
970715AG2-457 GEN
Solar/Wind Harmer
10.244
203963AG1-253 GEN
Solar/Wind Harmer
0.318
203962AF1-287 GEN
Solar/Wind Harmer
1.544
20083426SW_E13_K22
Solar/Wind Helper
0.212
202652Y1-033 WT C
Solar/Wind Helper
0.604
203955AF1-039 C O1
Solar/Wind Helper
0.349
203948AG1-140 C
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.487
20091526CHSTN_FL
Solar/Wind Helper
0.589
971185AH1-051 GEN
Solar/Wind Harmer
1.57
20083926HOMER C3
50/50
271.671
203813AE2-344_GEN
Solar/Wind Harmer
8.962
203940AF1-140 C
Solar/Wind Helper
0.528
944781AF1-143 GEN
Solar/Wind Helper
2.963
971709AH1-360 GEN
Solar/Wind Harmer
4.743
20334926Z1-069 C
Solar/Wind Harmer
7.165
20088626ARWF_N39
Solar/Wind Helper
1.791
20094526CT_V3-030
Solar/Wind Helper
0.39
971355AH1-158 GEN
Solar/Wind Harmer
2.908
971705AH1-358 GEN
Solar/Wind Harmer
4.743
970337AG2-221 GEN
Solar/Wind Harmer
1.972
970511AG2-327 GEN
Solar/Wind Harmer
0.953
970663AG2-429 GEN
Solar/Wind Harmer
3.528
20088926STNY CRK
Solar/Wind Helper
1.238
966771AG1-548 GEN
Solar/Wind Harmer
11.167
957161AF2-010 GEN
Solar/Wind Harmer
5.721
964201AG1-281 GEN
Solar/Wind Helper
0.59
971183AH1-050 GEN
Solar/Wind Harmer
2.617
20083826HOMER C2
50/50
222.941
972077AH1-588 GEN
Solar/Wind Harmer
30.733
970313AG2-206 GEN
Solar/Wind Harmer
4.574
20089226LOOKOUT
Solar/Wind Helper
0.741
972075AH1-587 GEN
Solar/Wind Harmer
22.021
203859AF2-294 C
Solar/Wind Harmer
1.691
971127AH1-005 GEN
Solar/Wind Harmer
1.918
970663AG2-429 GEN
Solar/Wind Harmer
5.543
971931AH1-490 GEN
Solar/Wind Harmer
1.544
20089126CSLMN_L13
Solar/Wind Helper
0.761
946071AF1-272 GEN
Solar/Wind Helper
2.314
970713AG2-456 GEN
Solar/Wind Harmer
10.244
203961AE2-224 GEN
Solar/Wind Helper
3.582
970647AG2-420 GEN
Solar/Wind Harmer
0.704
20092526R32
Solar/Wind Helper
1.819
964391AG1-301 GEN
Solar/Wind Helper
0.314
970305AG2-200 GEN
Solar/Wind Harmer
1.761
970267AG2-176 GEN
Solar/Wind Harmer
12.898
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.008
MECLTFEXP_MEC->PJM
CLTF
0.709
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
0.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.012
TVALTFEXP_TVA->PJM
CLTF
0.241
LGEELTFEXP_LGEE->PJM
CLTF
0.271
WECLTFEXP_WEC->PJM
CLTF
0.18
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.047

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-345-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-345-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.35 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1041.16
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.875
20091526CHSTN_FL
Solar/Wind Helper
0.743
971185AH1-051 GEN
Solar/Wind Harmer
1.268
20083826HOMER C2
50/50
281.093
972077AH1-588 GEN
Solar/Wind Harmer
38.749
970313AG2-206 GEN
Solar/Wind Harmer
5.767
20089226LOOKOUT
Solar/Wind Helper
0.934
966771AG1-548 GEN
Solar/Wind Harmer
14.08
957161AF2-010 GEN
Solar/Wind Harmer
7.214
964201AG1-281 GEN
Solar/Wind Helper
0.743
971183AH1-050 GEN
Solar/Wind Harmer
2.113
944411AF1-106 GEN
Solar/Wind Harmer
4.706
970663AG2-429 GEN
Solar/Wind Harmer
6.989
971931AH1-490 GEN
Solar/Wind Harmer
1.947
20089126CSLMN_L13
Solar/Wind Helper
0.959
970715AG2-457 GEN
Solar/Wind Harmer
12.916
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.946
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.761
203955AF1-039 C O1
Solar/Wind Helper
0.44
946071AF1-272 GEN
Solar/Wind Helper
2.918
972079AH1-589 GEN
Solar/Wind Harmer
50.828
971703AH1-357 GEN
Solar/Wind Harmer
3.229
971707AH1-359 GEN
Solar/Wind Harmer
3.229
20398826ARMNA MT
Solar/Wind Harmer
8.703
970335AG2-220 GEN
Solar/Wind Harmer
3.748
970647AG2-420 GEN
Solar/Wind Harmer
1.918
20084626FORWARD
Solar/Wind Helper
0.975
20088826HIGHLAND
Solar/Wind Helper
1.987
20089026BF_G21_K23
Solar/Wind Helper
0.759
971709AH1-360 GEN
Solar/Wind Harmer
5.98
20334926Z1-069 C
Solar/Wind Harmer
9.034
20088626ARWF_N39
Solar/Wind Helper
2.258
20094526CT_V3-030
Solar/Wind Helper
0.492
971355AH1-158 GEN
Solar/Wind Harmer
2.347
203859AF2-294 C
Solar/Wind Harmer
2.133
971127AH1-005 GEN
Solar/Wind Harmer
2.418
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.487
966771AG1-548 GEN
Solar/Wind Harmer
4.346
970677AG2-438 GEN
Solar/Wind Harmer
0.938
20303426NA_O38_P22
Solar/Wind Helper
1.838
970647AG2-420 GEN
Solar/Wind Harmer
0.888
20092526R32
Solar/Wind Helper
2.293
964391AG1-301 GEN
Solar/Wind Helper
0.395
972075AH1-587 GEN
Solar/Wind Harmer
27.765
941231AE2-117 GEN
Solar/Wind Helper
0.384
20083926HOMER C3
50/50
342.533
203813AE2-344_GEN
Solar/Wind Harmer
11.299
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.736
970305AG2-200 GEN
Solar/Wind Harmer
2.221
970267AG2-176 GEN
Solar/Wind Harmer
16.262
970713AG2-456 GEN
Solar/Wind Harmer
12.916
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.516
971705AH1-358 GEN
Solar/Wind Harmer
5.98
970337AG2-221 GEN
Solar/Wind Harmer
2.487
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.448
20088926STNY CRK
Solar/Wind Helper
1.561
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.894
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.015
TVALTFEXP_TVA->PJM
CLTF
0.304
LGEELTFEXP_LGEE->PJM
CLTF
0.342
WECLTFEXP_WEC->PJM
CLTF
0.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.18 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1039.69
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.487
966771AG1-548 GEN
Solar/Wind Harmer
4.346
970677AG2-438 GEN
Solar/Wind Harmer
0.938
20303426NA_O38_P22
Solar/Wind Helper
1.838
972079AH1-589 GEN
Solar/Wind Harmer
50.828
971703AH1-357 GEN
Solar/Wind Harmer
3.229
971707AH1-359 GEN
Solar/Wind Harmer
3.229
20398826ARMNA MT
Solar/Wind Harmer
8.703
970335AG2-220 GEN
Solar/Wind Harmer
3.748
970647AG2-420 GEN
Solar/Wind Harmer
1.918
20084626FORWARD
Solar/Wind Helper
0.975
20088826HIGHLAND
Solar/Wind Helper
1.987
20089026BF_G21_K23
Solar/Wind Helper
0.759
970715AG2-457 GEN
Solar/Wind Harmer
12.916
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.946
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.761
203955AF1-039 C O1
Solar/Wind Helper
0.44
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.875
20091526CHSTN_FL
Solar/Wind Helper
0.743
971185AH1-051 GEN
Solar/Wind Harmer
1.98
20083926HOMER C3
50/50
342.533
203813AE2-344_GEN
Solar/Wind Harmer
11.299
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.736
971709AH1-360 GEN
Solar/Wind Harmer
5.98
20334926Z1-069 C
Solar/Wind Harmer
9.034
20088626ARWF_N39
Solar/Wind Helper
2.258
20094526CT_V3-030
Solar/Wind Helper
0.492
971355AH1-158 GEN
Solar/Wind Harmer
3.667
971705AH1-358 GEN
Solar/Wind Harmer
5.98
970337AG2-221 GEN
Solar/Wind Harmer
2.487
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.448
20088926STNY CRK
Solar/Wind Helper
1.561
966771AG1-548 GEN
Solar/Wind Harmer
14.08
957161AF2-010 GEN
Solar/Wind Harmer
7.214
964201AG1-281 GEN
Solar/Wind Helper
0.743
971183AH1-050 GEN
Solar/Wind Harmer
3.3
20083826HOMER C2
50/50
281.093
972077AH1-588 GEN
Solar/Wind Harmer
38.749
970313AG2-206 GEN
Solar/Wind Harmer
5.767
20089226LOOKOUT
Solar/Wind Helper
0.934
972075AH1-587 GEN
Solar/Wind Harmer
27.765
941231AE2-117 GEN
Solar/Wind Helper
0.384
203859AF2-294 C
Solar/Wind Harmer
2.133
971127AH1-005 GEN
Solar/Wind Harmer
2.418
970663AG2-429 GEN
Solar/Wind Harmer
6.989
971931AH1-490 GEN
Solar/Wind Harmer
1.947
20089126CSLMN_L13
Solar/Wind Helper
0.959
946071AF1-272 GEN
Solar/Wind Helper
2.918
970713AG2-456 GEN
Solar/Wind Harmer
12.916
203961AE2-224 GEN
Solar/Wind Helper
4.516
970647AG2-420 GEN
Solar/Wind Harmer
0.888
20092526R32
Solar/Wind Helper
2.293
964391AG1-301 GEN
Solar/Wind Helper
0.395
970305AG2-200 GEN
Solar/Wind Harmer
2.221
970267AG2-176 GEN
Solar/Wind Harmer
16.262
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.894
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.015
TVALTFEXP_TVA->PJM
CLTF
0.304
LGEELTFEXP_LGEE->PJM
CLTF
0.342
WECLTFEXP_WEC->PJM
CLTF
0.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-307-DRT-010_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-307-DRT-010_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.02 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1038.38
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
50/50
363.358
971709AH1-360 GEN
Solar/Wind Harmer
5.534
20334926Z1-069 C
Solar/Wind Harmer
6.269
971355AH1-158 GEN
Solar/Wind Harmer
5.376
20088626ARWF_N39
Solar/Wind Helper
2.112
20094526CT_V3-030
Solar/Wind Helper
0.447
970715AG2-457 GEN
Solar/Wind Harmer
11.954
203962AF1-287 GEN
Solar/Wind Harmer
1.938
203963AG1-253 GEN
Solar/Wind Harmer
0.376
20083426SW_E13_K22
Solar/Wind Helper
0.248
971185AH1-051 GEN
Solar/Wind Harmer
2.903
203948AG1-140 C
Solar/Wind Harmer
0.246
971933AH1-491 GEN
Solar/Wind Harmer
1.859
20091526CHSTN_FL
Solar/Wind Helper
0.696
203813AE2-344_GEN
Solar/Wind Harmer
11.256
238219AF1-167 C
Solar/Wind Harmer
1.268
203848AF2-166 C
Solar/Wind Harmer
1.756
203940AF1-140 C
Solar/Wind Helper
0.619
944781AF1-143 GEN
Solar/Wind Helper
3.452
20083826HOMER C2
50/50
298.182
972077AH1-588 GEN
Solar/Wind Harmer
35.862
20089226LOOKOUT
Solar/Wind Helper
0.863
972075AH1-587 GEN
Solar/Wind Harmer
25.287
941231AE2-117 GEN
Solar/Wind Helper
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.839
957161AF2-010 GEN
Solar/Wind Harmer
7.161
966771AG1-548 GEN
Solar/Wind Harmer
13.931
964201AG1-281 GEN
Solar/Wind Helper
0.693
971705AH1-358 GEN
Solar/Wind Harmer
5.534
970663AG2-429 GEN
Solar/Wind Harmer
4.676
970337AG2-221 GEN
Solar/Wind Harmer
1.279
20088926STNY CRK
Solar/Wind Helper
1.448
970663AG2-429 GEN
Solar/Wind Harmer
7.348
971931AH1-490 GEN
Solar/Wind Harmer
1.946
944411AF1-106 GEN
Solar/Wind Harmer
2.544
20089126CSLMN_L13
Solar/Wind Helper
0.886
972079AH1-589 GEN
Solar/Wind Harmer
47.041
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
970647AG2-420 GEN
Solar/Wind Harmer
1.986
20398826ARMNA MT
Solar/Wind Harmer
4.38
20084626FORWARD
Solar/Wind Helper
0.905
20088826HIGHLAND
Solar/Wind Helper
1.846
20089026BF_G21_K23
Solar/Wind Helper
0.702
970335AG2-220 GEN
Solar/Wind Harmer
0.043
202652Y1-033 WT C
Solar/Wind Helper
0.7
203955AF1-039 C O1
Solar/Wind Helper
0.405
946071AF1-272 GEN
Solar/Wind Helper
2.614
970713AG2-456 GEN
Solar/Wind Harmer
11.954
944411AF1-106 GEN
Solar/Wind Harmer
-0.012
203961AE2-224 GEN
Solar/Wind Helper
4.217
203859AF2-294 C
Solar/Wind Harmer
1.158
971127AH1-005 GEN
Solar/Wind Harmer
0.028
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.929
966771AG1-548 GEN
Solar/Wind Harmer
4.3
970555AG2-356 GEN
Solar/Wind Harmer
1.279
20303426NA_O38_P22
Solar/Wind Helper
1.719
970647AG2-420 GEN
Solar/Wind Harmer
0.919
20092526R32
Solar/Wind Helper
2.13
964391AG1-301 GEN
Solar/Wind Helper
0.378
970267AG2-176 GEN
Solar/Wind Harmer
16.604
970305AG2-200 GEN
Solar/Wind Harmer
2.093
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
23.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.074
MECLTFEXP_MEC->PJM
CLTF
1.264
SIGELTFEXP_SIGE->PJM
CLTF
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
1.098
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.517
LGEELTFEXP_LGEE->PJM
CLTF
0.495
WECLTFEXP_WEC->PJM
CLTF
0.312

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-345-0183-308_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-345-0183-308_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.02 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1038.38
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
971709AH1-360 GEN
Solar/Wind Harmer
5.534
971185AH1-051 GEN
Solar/Wind Harmer
2.903
203948AG1-140 C
Solar/Wind Harmer
0.246
971933AH1-491 GEN
Solar/Wind Harmer
1.859
20091526CHSTN_FL
Solar/Wind Helper
0.696
20083926HOMER C3
50/50
363.358
203813AE2-344_GEN
Solar/Wind Harmer
11.256
238219AF1-167 C
Solar/Wind Harmer
1.268
203848AF2-166 C
Solar/Wind Harmer
1.756
203940AF1-140 C
Solar/Wind Helper
0.619
944781AF1-143 GEN
Solar/Wind Helper
3.452
20083826HOMER C2
50/50
298.182
972077AH1-588 GEN
Solar/Wind Harmer
35.862
20089226LOOKOUT
Solar/Wind Helper
0.863
972075AH1-587 GEN
Solar/Wind Harmer
25.287
941231AE2-117 GEN
Solar/Wind Helper
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.839
957161AF2-010 GEN
Solar/Wind Harmer
7.161
966771AG1-548 GEN
Solar/Wind Harmer
13.931
964201AG1-281 GEN
Solar/Wind Helper
0.693
971705AH1-358 GEN
Solar/Wind Harmer
5.534
970663AG2-429 GEN
Solar/Wind Harmer
4.676
970337AG2-221 GEN
Solar/Wind Harmer
1.279
20088926STNY CRK
Solar/Wind Helper
1.448
970663AG2-429 GEN
Solar/Wind Harmer
7.348
971931AH1-490 GEN
Solar/Wind Harmer
1.946
944411AF1-106 GEN
Solar/Wind Harmer
2.544
20089126CSLMN_L13
Solar/Wind Helper
0.886
20334926Z1-069 C
Solar/Wind Harmer
6.269
971355AH1-158 GEN
Solar/Wind Harmer
5.376
20088626ARWF_N39
Solar/Wind Helper
2.112
20094526CT_V3-030
Solar/Wind Helper
0.447
972079AH1-589 GEN
Solar/Wind Harmer
47.041
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
970647AG2-420 GEN
Solar/Wind Harmer
1.986
20398826ARMNA MT
Solar/Wind Harmer
4.38
20084626FORWARD
Solar/Wind Helper
0.905
20088826HIGHLAND
Solar/Wind Helper
1.846
20089026BF_G21_K23
Solar/Wind Helper
0.702
970335AG2-220 GEN
Solar/Wind Harmer
0.043
970715AG2-457 GEN
Solar/Wind Harmer
11.954
203962AF1-287 GEN
Solar/Wind Harmer
1.938
203963AG1-253 GEN
Solar/Wind Harmer
0.376
20083426SW_E13_K22
Solar/Wind Helper
0.248
202652Y1-033 WT C
Solar/Wind Helper
0.7
203955AF1-039 C O1
Solar/Wind Helper
0.405
946071AF1-272 GEN
Solar/Wind Helper
2.614
203859AF2-294 C
Solar/Wind Harmer
1.158
971127AH1-005 GEN
Solar/Wind Harmer
0.028
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.929
966771AG1-548 GEN
Solar/Wind Harmer
4.3
970555AG2-356 GEN
Solar/Wind Harmer
1.279
20303426NA_O38_P22
Solar/Wind Helper
1.719
970647AG2-420 GEN
Solar/Wind Harmer
0.919
20092526R32
Solar/Wind Helper
2.13
964391AG1-301 GEN
Solar/Wind Helper
0.378
970267AG2-176 GEN
Solar/Wind Harmer
16.604
970305AG2-200 GEN
Solar/Wind Harmer
2.093
970713AG2-456 GEN
Solar/Wind Harmer
11.954
944411AF1-106 GEN
Solar/Wind Harmer
-0.012
203961AE2-224 GEN
Solar/Wind Helper
4.217
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
23.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.074
MECLTFEXP_MEC->PJM
CLTF
1.264
SIGELTFEXP_SIGE->PJM
CLTF
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
1.098
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.517
LGEELTFEXP_LGEE->PJM
CLTF
0.495
WECLTFEXP_WEC->PJM
CLTF
0.312

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.29 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:875.84
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.206
971185AH1-051 GEN
Solar/Wind Harmer
2.197
971933AH1-491 GEN
Solar/Wind Harmer
1.462
20091526CHSTN_FL
Solar/Wind Helper
0.606
20083826HOMER C2
50/50
226.144
972077AH1-588 GEN
Solar/Wind Harmer
36.661
970313AG2-206 GEN
Solar/Wind Harmer
4.744
20089226LOOKOUT
Solar/Wind Helper
0.733
971183AH1-050 GEN
Solar/Wind Harmer
3.661
966771AG1-548 GEN
Solar/Wind Harmer
10.973
964201AG1-281 GEN
Solar/Wind Helper
0.593
957161AF2-010 GEN
Solar/Wind Harmer
0.212
944411AF1-106 GEN
Solar/Wind Harmer
3.893
970663AG2-429 GEN
Solar/Wind Harmer
5.484
971931AH1-490 GEN
Solar/Wind Harmer
1.525
20089126CSLMN_L13
Solar/Wind Helper
0.753
970715AG2-457 GEN
Solar/Wind Harmer
12.22
203963AG1-253 GEN
Solar/Wind Harmer
0.315
203962AF1-287 GEN
Solar/Wind Harmer
1.523
20083426SW_E13_K22
Solar/Wind Helper
0.21
202652Y1-033 WT C
Solar/Wind Helper
0.598
203955AF1-039 C O1
Solar/Wind Helper
0.346
946071AF1-272 GEN
Solar/Wind Helper
2.311
971709AH1-360 GEN
Solar/Wind Harmer
5.658
20334926Z1-069 C
Solar/Wind Harmer
7.808
971355AH1-158 GEN
Solar/Wind Harmer
4.068
20088626ARWF_N39
Solar/Wind Helper
1.789
20094526CT_V3-030
Solar/Wind Helper
0.4
203859AF2-294 C
Solar/Wind Harmer
1.766
971127AH1-005 GEN
Solar/Wind Harmer
1.989
972079AH1-589 GEN
Solar/Wind Harmer
48.089
971703AH1-357 GEN
Solar/Wind Harmer
3.055
971707AH1-359 GEN
Solar/Wind Harmer
3.055
20398826ARMNA MT
Solar/Wind Harmer
7.191
970335AG2-220 GEN
Solar/Wind Harmer
3.084
970647AG2-420 GEN
Solar/Wind Harmer
1.508
20084626FORWARD
Solar/Wind Helper
0.766
20088826HIGHLAND
Solar/Wind Helper
1.567
20089026BF_G21_K23
Solar/Wind Helper
0.596
970647AG2-420 GEN
Solar/Wind Harmer
0.698
20092526R32
Solar/Wind Helper
1.808
964391AG1-301 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.044
966771AG1-548 GEN
Solar/Wind Harmer
3.387
970677AG2-438 GEN
Solar/Wind Harmer
0.731
20303426NA_O38_P22
Solar/Wind Helper
1.456
972075AH1-587 GEN
Solar/Wind Harmer
23.838
941231AE2-117 GEN
Solar/Wind Helper
0.323
20083926HOMER C3
50/50
275.574
203813AE2-344_GEN
Solar/Wind Harmer
8.844
203940AF1-140 C
Solar/Wind Helper
0.528
944781AF1-143 GEN
Solar/Wind Helper
2.934
970267AG2-176 GEN
Solar/Wind Harmer
12.824
970305AG2-200 GEN
Solar/Wind Harmer
1.621
970713AG2-456 GEN
Solar/Wind Harmer
12.22
944411AF1-106 GEN
Solar/Wind Harmer
-0.018
203961AE2-224 GEN
Solar/Wind Helper
3.565
971705AH1-358 GEN
Solar/Wind Harmer
5.658
970337AG2-221 GEN
Solar/Wind Harmer
2.044
970511AG2-327 GEN
Solar/Wind Harmer
0.988
970663AG2-429 GEN
Solar/Wind Harmer
3.49
20088926STNY CRK
Solar/Wind Helper
1.228
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.423
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.002
MECLTFEXP_MEC->PJM
CLTF
0.705
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
0.53
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.01
TVALTFEXP_TVA->PJM
CLTF
0.24
LGEELTFEXP_LGEE->PJM
CLTF
0.27
WECLTFEXP_WEC->PJM
CLTF
0.179
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.048

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.03 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:873.67
MW Contribution:2.75
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
233.509
972077AH1-588 GEN
Solar/Wind Harmer
33.057
970313AG2-206 GEN
Solar/Wind Harmer
4.911
971183AH1-050 GEN
Solar/Wind Harmer
4.464
957161AF2-010 GEN
Solar/Wind Harmer
6.52
971185AH1-051 GEN
Solar/Wind Harmer
2.678
203948AG1-140 C
Solar/Wind Harmer
0.229
971933AH1-491 GEN
Solar/Wind Harmer
1.692
20091526CHSTN_FL
Solar/Wind Helper
0.509
944411AF1-106 GEN
Solar/Wind Harmer
3.992
970663AG2-429 GEN
Solar/Wind Harmer
7.325
971931AH1-490 GEN
Solar/Wind Harmer
1.725
20089126CSLMN_L13
Solar/Wind Helper
0.713
970715AG2-457 GEN
Solar/Wind Harmer
11.019
203963AG1-253 GEN
Solar/Wind Harmer
0.35
203962AF1-287 GEN
Solar/Wind Harmer
1.723
20083426SW_E13_K22
Solar/Wind Helper
0.198
202652Y1-033 WT C
Solar/Wind Helper
0.571
203955AF1-039 C O1
Solar/Wind Helper
0.33
946071AF1-272 GEN
Solar/Wind Helper
2.049
971709AH1-360 GEN
Solar/Wind Harmer
5.101
20334926Z1-069 C
Solar/Wind Harmer
7.667
971355AH1-158 GEN
Solar/Wind Harmer
4.96
20088626ARWF_N39
Solar/Wind Helper
1.641
203859AF2-294 C
Solar/Wind Harmer
1.811
971127AH1-005 GEN
Solar/Wind Harmer
2.058
964201AG1-281 GEN
Solar/Wind Helper
0.534
966771AG1-548 GEN
Solar/Wind Harmer
6.996
972079AH1-589 GEN
Solar/Wind Harmer
43.362
971703AH1-357 GEN
Solar/Wind Harmer
2.755
971707AH1-359 GEN
Solar/Wind Harmer
2.755
20398826ARMNA MT
Solar/Wind Harmer
7.381
970335AG2-220 GEN
Solar/Wind Harmer
3.191
970647AG2-420 GEN
Solar/Wind Harmer
1.816
20084626FORWARD
Solar/Wind Helper
0.721
20088826HIGHLAND
Solar/Wind Helper
1.457
20089026BF_G21_K23
Solar/Wind Helper
0.565
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.118
970677AG2-438 GEN
Solar/Wind Harmer
0.846
20303426NA_O38_P22
Solar/Wind Helper
1.336
966771AG1-548 GEN
Solar/Wind Harmer
2.159
970647AG2-420 GEN
Solar/Wind Harmer
0.841
20092526R32
Solar/Wind Helper
1.681
972075AH1-587 GEN
Solar/Wind Harmer
23.992
20083926HOMER C3
50/50
284.548
238219AF1-167 C
Solar/Wind Harmer
1.29
203813AE2-344_GEN
Solar/Wind Harmer
10.002
203940AF1-140 C
Solar/Wind Helper
0.483
944781AF1-143 GEN
Solar/Wind Helper
2.779
970305AG2-200 GEN
Solar/Wind Harmer
1.946
970267AG2-176 GEN
Solar/Wind Harmer
14.541
20089226LOOKOUT
Solar/Wind Helper
0.695
970713AG2-456 GEN
Solar/Wind Harmer
11.019
944411AF1-106 GEN
Solar/Wind Harmer
-0.018
203961AE2-224 GEN
Solar/Wind Helper
3.303
971705AH1-358 GEN
Solar/Wind Harmer
5.101
970337AG2-221 GEN
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
4.661
970511AG2-327 GEN
Solar/Wind Harmer
1.023
20088926STNY CRK
Solar/Wind Helper
1.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.113
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.541
SIGELTFEXP_SIGE->PJM
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.336
TVALTFEXP_TVA->PJM
CLTF
0.143
LGEELTFEXP_LGEE->PJM
CLTF
0.2
WECLTFEXP_WEC->PJM
CLTF
0.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.102

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.37 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1066.04
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
20083426SW_E13_K22
Solar/Wind Helper
0.119
203962AF1-287 GEN
Solar/Wind Harmer
0.243
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
944411AF1-106 GEN
Solar/Wind Harmer
4.739
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
944411AF1-106 GEN
Solar/Wind Harmer
-0.022
203961AE2-224 GEN
Solar/Wind Helper
1.92
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-301_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-301_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.37 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1066.04
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
20083426SW_E13_K22
Solar/Wind Helper
0.119
203962AF1-287 GEN
Solar/Wind Harmer
0.243
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
944411AF1-106 GEN
Solar/Wind Harmer
4.739
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
944411AF1-106 GEN
Solar/Wind Harmer
-0.022
203961AE2-224 GEN
Solar/Wind Helper
1.92
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P1-2_WP-345-311T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P1-2_WP-345-311T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.96 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1062.63
MW Contribution:3.05
Bus #Bus NameTypeMW Contribution
970555AG2-356 GEN
Solar/Wind Harmer
2.517
203804AE2-113_GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
1.825
970677AG2-438 GEN
Solar/Wind Harmer
0.387
20303426NA_O38_P22
Solar/Wind Helper
0.767
972079AH1-589 GEN
Solar/Wind Harmer
48.024
971703AH1-357 GEN
Solar/Wind Harmer
3.051
971707AH1-359 GEN
Solar/Wind Harmer
3.051
20398826ARMNA MT
Solar/Wind Harmer
8.832
970335AG2-220 GEN
Solar/Wind Harmer
3.803
20084626FORWARD
Solar/Wind Helper
0.432
20088826HIGHLAND
Solar/Wind Helper
0.865
20089026BF_G21_K23
Solar/Wind Helper
0.342
970715AG2-457 GEN
Solar/Wind Harmer
12.204
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.22
203962AF1-287 GEN
Solar/Wind Harmer
0.762
20083426SW_E13_K22
Solar/Wind Helper
0.119
203948AG1-140 C
Solar/Wind Harmer
0.144
971933AH1-491 GEN
Solar/Wind Harmer
0.775
20083926HOMER C3
50/50
364.763
203940AF1-140 C
Solar/Wind Helper
0.282
944781AF1-143 GEN
Solar/Wind Helper
1.684
203813AE2-344_GEN
Solar/Wind Harmer
0.79
20334926Z1-069 C
Solar/Wind Harmer
8.921
971709AH1-360 GEN
Solar/Wind Harmer
5.65
970679AG2-439 GEN
Solar/Wind Harmer
0.604
20088626ARWF_N39
Solar/Wind Helper
0.942
971705AH1-358 GEN
Solar/Wind Harmer
5.65
970337AG2-221 GEN
Solar/Wind Harmer
2.517
970511AG2-327 GEN
Solar/Wind Harmer
1.219
20088926STNY CRK
Solar/Wind Helper
0.688
200917MEHOOPANY_G
Solar/Wind Harmer
7.226
966771AG1-548 GEN
Solar/Wind Harmer
5.913
957161AF2-010 GEN
Solar/Wind Harmer
2.945
20083826HOMER C2
50/50
299.336
972077AH1-588 GEN
Solar/Wind Harmer
36.611
970313AG2-206 GEN
Solar/Wind Harmer
5.852
20089226LOOKOUT
Solar/Wind Helper
0.421
972075AH1-587 GEN
Solar/Wind Harmer
25.831
203859AF2-294 C
Solar/Wind Harmer
2.155
971127AH1-005 GEN
Solar/Wind Harmer
2.453
20089126CSLMN_L13
Solar/Wind Helper
0.432
970713AG2-456 GEN
Solar/Wind Harmer
12.204
203961AE2-224 GEN
Solar/Wind Helper
1.92
20092526R32
Solar/Wind Helper
0.998
970305AG2-200 GEN
Solar/Wind Harmer
1.634
961581Q1080_CY23
External Queue
34.47880172729492
G-007ALTFEXP_G-007A->PJM
CMTX
0.362
CBM NorthLTFEXP_CBM-N->PJM
CBM
48.277
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
VFTLTFEXP_VFT->PJM
CMTX
1.499

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.59 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:825.5
MW Contribution:2.56
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
1.972
966771AG1-548 GEN
Solar/Wind Harmer
3.447
970677AG2-438 GEN
Solar/Wind Harmer
0.744
20303426NA_O38_P22
Solar/Wind Helper
1.457
972079AH1-589 GEN
Solar/Wind Harmer
40.313
971703AH1-357 GEN
Solar/Wind Harmer
2.561
971707AH1-359 GEN
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
6.903
970335AG2-220 GEN
Solar/Wind Harmer
2.972
970647AG2-420 GEN
Solar/Wind Harmer
1.521
20084626FORWARD
Solar/Wind Helper
0.774
20088826HIGHLAND
Solar/Wind Helper
1.576
20089026BF_G21_K23
Solar/Wind Helper
0.602
970715AG2-457 GEN
Solar/Wind Harmer
10.244
203963AG1-253 GEN
Solar/Wind Harmer
0.318
203962AF1-287 GEN
Solar/Wind Harmer
1.544
20083426SW_E13_K22
Solar/Wind Helper
0.212
202652Y1-033 WT C
Solar/Wind Helper
0.604
203955AF1-039 C O1
Solar/Wind Helper
0.349
203948AG1-140 C
Solar/Wind Harmer
0.208
971933AH1-491 GEN
Solar/Wind Harmer
1.487
20091526CHSTN_FL
Solar/Wind Helper
0.589
971185AH1-051 GEN
Solar/Wind Harmer
1.57
20083926HOMER C3
50/50
271.671
203813AE2-344_GEN
Solar/Wind Harmer
8.962
203940AF1-140 C
Solar/Wind Helper
0.528
944781AF1-143 GEN
Solar/Wind Helper
2.963
971709AH1-360 GEN
Solar/Wind Harmer
4.743
20334926Z1-069 C
Solar/Wind Harmer
7.165
20088626ARWF_N39
Solar/Wind Helper
1.791
20094526CT_V3-030
Solar/Wind Helper
0.39
971355AH1-158 GEN
Solar/Wind Harmer
2.908
971705AH1-358 GEN
Solar/Wind Harmer
4.743
970337AG2-221 GEN
Solar/Wind Harmer
1.972
970511AG2-327 GEN
Solar/Wind Harmer
0.953
970663AG2-429 GEN
Solar/Wind Harmer
3.528
20088926STNY CRK
Solar/Wind Helper
1.238
966771AG1-548 GEN
Solar/Wind Harmer
11.167
957161AF2-010 GEN
Solar/Wind Harmer
5.721
964201AG1-281 GEN
Solar/Wind Helper
0.59
971183AH1-050 GEN
Solar/Wind Harmer
2.617
20083826HOMER C2
50/50
222.941
972077AH1-588 GEN
Solar/Wind Harmer
30.733
970313AG2-206 GEN
Solar/Wind Harmer
4.574
20089226LOOKOUT
Solar/Wind Helper
0.741
972075AH1-587 GEN
Solar/Wind Harmer
22.021
203859AF2-294 C
Solar/Wind Harmer
1.691
971127AH1-005 GEN
Solar/Wind Harmer
1.918
970663AG2-429 GEN
Solar/Wind Harmer
5.543
971931AH1-490 GEN
Solar/Wind Harmer
1.544
20089126CSLMN_L13
Solar/Wind Helper
0.761
946071AF1-272 GEN
Solar/Wind Helper
2.314
970713AG2-456 GEN
Solar/Wind Harmer
10.244
203961AE2-224 GEN
Solar/Wind Helper
3.582
970647AG2-420 GEN
Solar/Wind Harmer
0.704
20092526R32
Solar/Wind Helper
1.819
964391AG1-301 GEN
Solar/Wind Helper
0.314
970305AG2-200 GEN
Solar/Wind Harmer
1.761
970267AG2-176 GEN
Solar/Wind Harmer
12.898
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.008
MECLTFEXP_MEC->PJM
CLTF
0.709
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
0.533
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.012
TVALTFEXP_TVA->PJM
CLTF
0.241
LGEELTFEXP_LGEE->PJM
CLTF
0.271
WECLTFEXP_WEC->PJM
CLTF
0.18
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.047

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1050.96
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.486
966771AG1-548 GEN
Solar/Wind Harmer
4.343
970677AG2-438 GEN
Solar/Wind Harmer
0.937
20303426NA_O38_P22
Solar/Wind Helper
1.839
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.874
20091526CHSTN_FL
Solar/Wind Helper
0.744
971185AH1-051 GEN
Solar/Wind Harmer
1.267
20083926HOMER C3
50/50
342.464
203813AE2-344_GEN
Solar/Wind Harmer
11.292
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.739
971709AH1-360 GEN
Solar/Wind Harmer
5.978
20334926Z1-069 C
Solar/Wind Harmer
9.031
20088626ARWF_N39
Solar/Wind Helper
2.26
20094526CT_V3-030
Solar/Wind Helper
0.493
971355AH1-158 GEN
Solar/Wind Harmer
2.346
970715AG2-457 GEN
Solar/Wind Harmer
12.912
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.945
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.762
203955AF1-039 C O1
Solar/Wind Helper
0.441
972079AH1-589 GEN
Solar/Wind Harmer
50.81
971703AH1-357 GEN
Solar/Wind Harmer
3.228
971707AH1-359 GEN
Solar/Wind Harmer
3.228
20398826ARMNA MT
Solar/Wind Harmer
8.7
970335AG2-220 GEN
Solar/Wind Harmer
3.746
970647AG2-420 GEN
Solar/Wind Harmer
1.917
20084626FORWARD
Solar/Wind Helper
0.976
20088826HIGHLAND
Solar/Wind Helper
1.989
20089026BF_G21_K23
Solar/Wind Helper
0.76
20083826HOMER C2
50/50
281.036
972077AH1-588 GEN
Solar/Wind Harmer
38.735
970313AG2-206 GEN
Solar/Wind Harmer
5.764
20089226LOOKOUT
Solar/Wind Helper
0.935
972075AH1-587 GEN
Solar/Wind Harmer
27.753
941231AE2-117 GEN
Solar/Wind Helper
0.385
966771AG1-548 GEN
Solar/Wind Harmer
14.071
957161AF2-010 GEN
Solar/Wind Harmer
7.209
964201AG1-281 GEN
Solar/Wind Helper
0.744
971183AH1-050 GEN
Solar/Wind Harmer
2.111
971705AH1-358 GEN
Solar/Wind Harmer
5.978
970337AG2-221 GEN
Solar/Wind Harmer
2.486
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.445
20088926STNY CRK
Solar/Wind Helper
1.562
944411AF1-106 GEN
Solar/Wind Harmer
4.704
970663AG2-429 GEN
Solar/Wind Harmer
6.985
971931AH1-490 GEN
Solar/Wind Harmer
1.946
20089126CSLMN_L13
Solar/Wind Helper
0.96
946071AF1-272 GEN
Solar/Wind Helper
2.922
970713AG2-456 GEN
Solar/Wind Harmer
12.912
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.519
203859AF2-294 C
Solar/Wind Harmer
2.132
971127AH1-005 GEN
Solar/Wind Harmer
2.417
970647AG2-420 GEN
Solar/Wind Harmer
0.887
20092526R32
Solar/Wind Helper
2.295
964391AG1-301 GEN
Solar/Wind Helper
0.396
970305AG2-200 GEN
Solar/Wind Harmer
2.22
970267AG2-176 GEN
Solar/Wind Harmer
16.253
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.482
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.235
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.653
TVALTFEXP_TVA->PJM
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.54 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1050.96
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.874
20091526CHSTN_FL
Solar/Wind Helper
0.744
971185AH1-051 GEN
Solar/Wind Harmer
1.267
20083926HOMER C3
50/50
342.464
203813AE2-344_GEN
Solar/Wind Harmer
11.292
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.739
20083826HOMER C2
50/50
281.036
972077AH1-588 GEN
Solar/Wind Harmer
38.735
970313AG2-206 GEN
Solar/Wind Harmer
5.764
20089226LOOKOUT
Solar/Wind Helper
0.935
966771AG1-548 GEN
Solar/Wind Harmer
14.071
957161AF2-010 GEN
Solar/Wind Harmer
7.209
964201AG1-281 GEN
Solar/Wind Helper
0.744
971183AH1-050 GEN
Solar/Wind Harmer
2.111
944411AF1-106 GEN
Solar/Wind Harmer
4.704
970663AG2-429 GEN
Solar/Wind Harmer
6.985
971931AH1-490 GEN
Solar/Wind Harmer
1.946
20089126CSLMN_L13
Solar/Wind Helper
0.96
971709AH1-360 GEN
Solar/Wind Harmer
5.978
20334926Z1-069 C
Solar/Wind Harmer
9.031
20088626ARWF_N39
Solar/Wind Helper
2.26
20094526CT_V3-030
Solar/Wind Helper
0.493
971355AH1-158 GEN
Solar/Wind Harmer
2.346
972079AH1-589 GEN
Solar/Wind Harmer
50.81
971703AH1-357 GEN
Solar/Wind Harmer
3.228
971707AH1-359 GEN
Solar/Wind Harmer
3.228
20398826ARMNA MT
Solar/Wind Harmer
8.7
970335AG2-220 GEN
Solar/Wind Harmer
3.746
970647AG2-420 GEN
Solar/Wind Harmer
1.917
20084626FORWARD
Solar/Wind Helper
0.976
20088826HIGHLAND
Solar/Wind Helper
1.989
20089026BF_G21_K23
Solar/Wind Helper
0.76
970715AG2-457 GEN
Solar/Wind Harmer
12.912
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.945
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.762
203955AF1-039 C O1
Solar/Wind Helper
0.441
946071AF1-272 GEN
Solar/Wind Helper
2.922
203859AF2-294 C
Solar/Wind Harmer
2.132
971127AH1-005 GEN
Solar/Wind Harmer
2.417
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.486
966771AG1-548 GEN
Solar/Wind Harmer
4.343
970677AG2-438 GEN
Solar/Wind Harmer
0.937
20303426NA_O38_P22
Solar/Wind Helper
1.839
970647AG2-420 GEN
Solar/Wind Harmer
0.887
20092526R32
Solar/Wind Helper
2.295
964391AG1-301 GEN
Solar/Wind Helper
0.396
972075AH1-587 GEN
Solar/Wind Harmer
27.753
941231AE2-117 GEN
Solar/Wind Helper
0.385
970305AG2-200 GEN
Solar/Wind Harmer
2.22
970267AG2-176 GEN
Solar/Wind Harmer
16.253
970713AG2-456 GEN
Solar/Wind Harmer
12.912
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.519
971705AH1-358 GEN
Solar/Wind Harmer
5.978
970337AG2-221 GEN
Solar/Wind Harmer
2.486
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.445
20088926STNY CRK
Solar/Wind Helper
1.562
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.482
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.588
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.235
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.653
TVALTFEXP_TVA->PJM
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-345-001T-DRT-001_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-345-001T-DRT-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.48 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1042.23
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.875
20091526CHSTN_FL
Solar/Wind Helper
0.743
971185AH1-051 GEN
Solar/Wind Harmer
1.268
20083826HOMER C2
50/50
281.093
972077AH1-588 GEN
Solar/Wind Harmer
38.749
970313AG2-206 GEN
Solar/Wind Harmer
5.767
20089226LOOKOUT
Solar/Wind Helper
0.934
966771AG1-548 GEN
Solar/Wind Harmer
14.08
957161AF2-010 GEN
Solar/Wind Harmer
7.214
964201AG1-281 GEN
Solar/Wind Helper
0.743
971183AH1-050 GEN
Solar/Wind Harmer
2.113
944411AF1-106 GEN
Solar/Wind Harmer
4.706
970663AG2-429 GEN
Solar/Wind Harmer
6.989
971931AH1-490 GEN
Solar/Wind Harmer
1.947
20089126CSLMN_L13
Solar/Wind Helper
0.959
971709AH1-360 GEN
Solar/Wind Harmer
5.98
20334926Z1-069 C
Solar/Wind Harmer
9.034
20088626ARWF_N39
Solar/Wind Helper
2.258
970715AG2-457 GEN
Solar/Wind Harmer
12.916
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.946
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.761
203955AF1-039 C O1
Solar/Wind Helper
0.44
946071AF1-272 GEN
Solar/Wind Helper
2.918
972079AH1-589 GEN
Solar/Wind Harmer
50.828
971703AH1-357 GEN
Solar/Wind Harmer
3.229
971707AH1-359 GEN
Solar/Wind Harmer
3.229
20398826ARMNA MT
Solar/Wind Harmer
8.703
970335AG2-220 GEN
Solar/Wind Harmer
3.748
970647AG2-420 GEN
Solar/Wind Harmer
1.918
20084626FORWARD
Solar/Wind Helper
0.975
20088826HIGHLAND
Solar/Wind Helper
1.987
20089026BF_G21_K23
Solar/Wind Helper
0.759
20094526CT_V3-030
Solar/Wind Helper
0.492
971355AH1-158 GEN
Solar/Wind Harmer
2.347
203859AF2-294 C
Solar/Wind Harmer
2.133
971127AH1-005 GEN
Solar/Wind Harmer
2.418
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.487
966771AG1-548 GEN
Solar/Wind Harmer
4.346
970677AG2-438 GEN
Solar/Wind Harmer
0.938
20303426NA_O38_P22
Solar/Wind Helper
1.838
970647AG2-420 GEN
Solar/Wind Harmer
0.888
20092526R32
Solar/Wind Helper
2.293
964391AG1-301 GEN
Solar/Wind Helper
0.395
972075AH1-587 GEN
Solar/Wind Harmer
27.765
941231AE2-117 GEN
Solar/Wind Helper
0.384
20083926HOMER C3
50/50
342.533
203813AE2-344_GEN
Solar/Wind Harmer
11.299
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.736
970305AG2-200 GEN
Solar/Wind Harmer
2.221
970267AG2-176 GEN
Solar/Wind Harmer
16.262
970713AG2-456 GEN
Solar/Wind Harmer
12.916
944411AF1-106 GEN
Solar/Wind Harmer
-0.021
203961AE2-224 GEN
Solar/Wind Helper
4.516
971705AH1-358 GEN
Solar/Wind Harmer
5.98
970337AG2-221 GEN
Solar/Wind Harmer
2.487
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.448
20088926STNY CRK
Solar/Wind Helper
1.561
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.894
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.015
TVALTFEXP_TVA->PJM
CLTF
0.304
LGEELTFEXP_LGEE->PJM
CLTF
0.342
WECLTFEXP_WEC->PJM
CLTF
0.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.3 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1040.75
MW Contribution:3.23
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.487
966771AG1-548 GEN
Solar/Wind Harmer
4.346
970677AG2-438 GEN
Solar/Wind Harmer
0.938
20303426NA_O38_P22
Solar/Wind Helper
1.838
972079AH1-589 GEN
Solar/Wind Harmer
50.828
971703AH1-357 GEN
Solar/Wind Harmer
3.229
971707AH1-359 GEN
Solar/Wind Harmer
3.229
20398826ARMNA MT
Solar/Wind Harmer
8.703
970335AG2-220 GEN
Solar/Wind Harmer
3.748
970647AG2-420 GEN
Solar/Wind Harmer
1.918
20084626FORWARD
Solar/Wind Helper
0.975
20088826HIGHLAND
Solar/Wind Helper
1.987
20089026BF_G21_K23
Solar/Wind Helper
0.759
970715AG2-457 GEN
Solar/Wind Harmer
12.916
203963AG1-253 GEN
Solar/Wind Harmer
0.4
203962AF1-287 GEN
Solar/Wind Harmer
1.946
20083426SW_E13_K22
Solar/Wind Helper
0.267
202652Y1-033 WT C
Solar/Wind Helper
0.761
203955AF1-039 C O1
Solar/Wind Helper
0.44
203948AG1-140 C
Solar/Wind Harmer
0.262
971933AH1-491 GEN
Solar/Wind Harmer
1.875
20091526CHSTN_FL
Solar/Wind Helper
0.743
971185AH1-051 GEN
Solar/Wind Harmer
1.98
20083926HOMER C3
50/50
342.533
203813AE2-344_GEN
Solar/Wind Harmer
11.299
203940AF1-140 C
Solar/Wind Helper
0.666
944781AF1-143 GEN
Solar/Wind Helper
3.736
971709AH1-360 GEN
Solar/Wind Harmer
5.98
20334926Z1-069 C
Solar/Wind Harmer
9.034
20088626ARWF_N39
Solar/Wind Helper
2.258
20094526CT_V3-030
Solar/Wind Helper
0.492
971355AH1-158 GEN
Solar/Wind Harmer
3.667
971705AH1-358 GEN
Solar/Wind Harmer
5.98
970337AG2-221 GEN
Solar/Wind Harmer
2.487
970511AG2-327 GEN
Solar/Wind Harmer
1.201
970663AG2-429 GEN
Solar/Wind Harmer
4.448
20088926STNY CRK
Solar/Wind Helper
1.561
966771AG1-548 GEN
Solar/Wind Harmer
14.08
957161AF2-010 GEN
Solar/Wind Harmer
7.214
964201AG1-281 GEN
Solar/Wind Helper
0.743
971183AH1-050 GEN
Solar/Wind Harmer
3.3
20083826HOMER C2
50/50
281.093
972077AH1-588 GEN
Solar/Wind Harmer
38.749
970313AG2-206 GEN
Solar/Wind Harmer
5.767
20089226LOOKOUT
Solar/Wind Helper
0.934
972075AH1-587 GEN
Solar/Wind Harmer
27.765
941231AE2-117 GEN
Solar/Wind Helper
0.384
203859AF2-294 C
Solar/Wind Harmer
2.133
971127AH1-005 GEN
Solar/Wind Harmer
2.418
970663AG2-429 GEN
Solar/Wind Harmer
6.989
971931AH1-490 GEN
Solar/Wind Harmer
1.947
20089126CSLMN_L13
Solar/Wind Helper
0.959
946071AF1-272 GEN
Solar/Wind Helper
2.918
970713AG2-456 GEN
Solar/Wind Harmer
12.916
203961AE2-224 GEN
Solar/Wind Helper
4.516
970647AG2-420 GEN
Solar/Wind Harmer
0.888
20092526R32
Solar/Wind Helper
2.293
964391AG1-301 GEN
Solar/Wind Helper
0.395
970305AG2-200 GEN
Solar/Wind Harmer
2.221
970267AG2-176 GEN
Solar/Wind Harmer
16.262
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.723
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.894
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
0.672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.015
TVALTFEXP_TVA->PJM
CLTF
0.304
LGEELTFEXP_LGEE->PJM
CLTF
0.342
WECLTFEXP_WEC->PJM
CLTF
0.227
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-308_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-308_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.18 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1039.72
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.929
966771AG1-548 GEN
Solar/Wind Harmer
4.3
970555AG2-356 GEN
Solar/Wind Harmer
1.279
20303426NA_O38_P22
Solar/Wind Helper
1.719
971185AH1-051 GEN
Solar/Wind Harmer
2.903
203948AG1-140 C
Solar/Wind Harmer
0.246
20083926HOMER C3
50/50
363.358
203813AE2-344_GEN
Solar/Wind Harmer
11.256
238219AF1-167 C
Solar/Wind Harmer
1.268
203848AF2-166 C
Solar/Wind Harmer
1.756
203940AF1-140 C
Solar/Wind Helper
0.619
944781AF1-143 GEN
Solar/Wind Helper
3.452
971709AH1-360 GEN
Solar/Wind Harmer
5.534
20334926Z1-069 C
Solar/Wind Harmer
6.269
971355AH1-158 GEN
Solar/Wind Harmer
5.376
20088626ARWF_N39
Solar/Wind Helper
2.112
20094526CT_V3-030
Solar/Wind Helper
0.447
970715AG2-457 GEN
Solar/Wind Harmer
11.954
203962AF1-287 GEN
Solar/Wind Harmer
1.938
203963AG1-253 GEN
Solar/Wind Harmer
0.376
20083426SW_E13_K22
Solar/Wind Helper
0.248
202652Y1-033 WT C
Solar/Wind Helper
0.7
203955AF1-039 C O1
Solar/Wind Helper
0.405
971933AH1-491 GEN
Solar/Wind Harmer
1.859
20091526CHSTN_FL
Solar/Wind Helper
0.696
20083826HOMER C2
50/50
298.182
972077AH1-588 GEN
Solar/Wind Harmer
35.862
20089226LOOKOUT
Solar/Wind Helper
0.863
972075AH1-587 GEN
Solar/Wind Harmer
25.287
941231AE2-117 GEN
Solar/Wind Helper
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.839
957161AF2-010 GEN
Solar/Wind Harmer
7.161
966771AG1-548 GEN
Solar/Wind Harmer
13.931
964201AG1-281 GEN
Solar/Wind Helper
0.693
971705AH1-358 GEN
Solar/Wind Harmer
5.534
970663AG2-429 GEN
Solar/Wind Harmer
4.676
970337AG2-221 GEN
Solar/Wind Harmer
1.279
20088926STNY CRK
Solar/Wind Helper
1.448
970663AG2-429 GEN
Solar/Wind Harmer
7.348
971931AH1-490 GEN
Solar/Wind Harmer
1.946
944411AF1-106 GEN
Solar/Wind Harmer
2.544
20089126CSLMN_L13
Solar/Wind Helper
0.886
972079AH1-589 GEN
Solar/Wind Harmer
47.041
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
970647AG2-420 GEN
Solar/Wind Harmer
1.986
20398826ARMNA MT
Solar/Wind Harmer
4.38
20084626FORWARD
Solar/Wind Helper
0.905
20088826HIGHLAND
Solar/Wind Helper
1.846
20089026BF_G21_K23
Solar/Wind Helper
0.702
970335AG2-220 GEN
Solar/Wind Harmer
0.043
946071AF1-272 GEN
Solar/Wind Helper
2.614
970713AG2-456 GEN
Solar/Wind Harmer
11.954
944411AF1-106 GEN
Solar/Wind Harmer
-0.012
203961AE2-224 GEN
Solar/Wind Helper
4.217
203859AF2-294 C
Solar/Wind Harmer
1.158
971127AH1-005 GEN
Solar/Wind Harmer
0.028
970647AG2-420 GEN
Solar/Wind Harmer
0.919
20092526R32
Solar/Wind Helper
2.13
964391AG1-301 GEN
Solar/Wind Helper
0.378
970267AG2-176 GEN
Solar/Wind Harmer
16.604
970305AG2-200 GEN
Solar/Wind Harmer
2.093
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
23.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.074
MECLTFEXP_MEC->PJM
CLTF
1.264
SIGELTFEXP_SIGE->PJM
CLTF
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
1.098
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.517
LGEELTFEXP_LGEE->PJM
CLTF
0.495
WECLTFEXP_WEC->PJM
CLTF
0.312

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-345-0183-307-DRT-010_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-345-0183-307-DRT-010_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.18 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:1039.72
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
970677AG2-438 GEN
Solar/Wind Harmer
0.929
966771AG1-548 GEN
Solar/Wind Harmer
4.3
970555AG2-356 GEN
Solar/Wind Harmer
1.279
20083926HOMER C3
50/50
363.358
203813AE2-344_GEN
Solar/Wind Harmer
11.256
238219AF1-167 C
Solar/Wind Harmer
1.268
203848AF2-166 C
Solar/Wind Harmer
1.756
203940AF1-140 C
Solar/Wind Helper
0.619
944781AF1-143 GEN
Solar/Wind Helper
3.452
971709AH1-360 GEN
Solar/Wind Harmer
5.534
20334926Z1-069 C
Solar/Wind Harmer
6.269
971355AH1-158 GEN
Solar/Wind Harmer
5.376
20088626ARWF_N39
Solar/Wind Helper
2.112
20094526CT_V3-030
Solar/Wind Helper
0.447
970715AG2-457 GEN
Solar/Wind Harmer
11.954
203962AF1-287 GEN
Solar/Wind Harmer
1.938
203963AG1-253 GEN
Solar/Wind Harmer
0.376
20083426SW_E13_K22
Solar/Wind Helper
0.248
202652Y1-033 WT C
Solar/Wind Helper
0.7
203955AF1-039 C O1
Solar/Wind Helper
0.405
971185AH1-051 GEN
Solar/Wind Harmer
2.903
203948AG1-140 C
Solar/Wind Harmer
0.246
971933AH1-491 GEN
Solar/Wind Harmer
1.859
20091526CHSTN_FL
Solar/Wind Helper
0.696
20083826HOMER C2
50/50
298.182
972077AH1-588 GEN
Solar/Wind Harmer
35.862
20089226LOOKOUT
Solar/Wind Helper
0.863
972075AH1-587 GEN
Solar/Wind Harmer
25.287
941231AE2-117 GEN
Solar/Wind Helper
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.839
957161AF2-010 GEN
Solar/Wind Harmer
7.161
966771AG1-548 GEN
Solar/Wind Harmer
13.931
964201AG1-281 GEN
Solar/Wind Helper
0.693
971705AH1-358 GEN
Solar/Wind Harmer
5.534
970663AG2-429 GEN
Solar/Wind Harmer
4.676
970337AG2-221 GEN
Solar/Wind Harmer
1.279
20088926STNY CRK
Solar/Wind Helper
1.448
970663AG2-429 GEN
Solar/Wind Harmer
7.348
971931AH1-490 GEN
Solar/Wind Harmer
1.946
944411AF1-106 GEN
Solar/Wind Harmer
2.544
20089126CSLMN_L13
Solar/Wind Helper
0.886
972079AH1-589 GEN
Solar/Wind Harmer
47.041
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
970647AG2-420 GEN
Solar/Wind Harmer
1.986
20398826ARMNA MT
Solar/Wind Harmer
4.38
20084626FORWARD
Solar/Wind Helper
0.905
20088826HIGHLAND
Solar/Wind Helper
1.846
20089026BF_G21_K23
Solar/Wind Helper
0.702
970335AG2-220 GEN
Solar/Wind Harmer
0.043
946071AF1-272 GEN
Solar/Wind Helper
2.614
970713AG2-456 GEN
Solar/Wind Harmer
11.954
944411AF1-106 GEN
Solar/Wind Harmer
-0.012
203961AE2-224 GEN
Solar/Wind Helper
4.217
203859AF2-294 C
Solar/Wind Harmer
1.158
971127AH1-005 GEN
Solar/Wind Harmer
0.028
20303426NA_O38_P22
Solar/Wind Helper
1.719
970647AG2-420 GEN
Solar/Wind Harmer
0.919
20092526R32
Solar/Wind Helper
2.13
964391AG1-301 GEN
Solar/Wind Helper
0.378
970267AG2-176 GEN
Solar/Wind Harmer
16.604
970305AG2-200 GEN
Solar/Wind Harmer
2.093
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM NorthLTFEXP_CBM-N->PJM
CBM
23.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.074
MECLTFEXP_MEC->PJM
CLTF
1.264
SIGELTFEXP_SIGE->PJM
CLTF
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
1.098
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.587
TVALTFEXP_TVA->PJM
CLTF
0.517
LGEELTFEXP_LGEE->PJM
CLTF
0.495
WECLTFEXP_WEC->PJM
CLTF
0.312

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:877.19
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
203948AG1-140 C
Solar/Wind Harmer
0.206
971185AH1-051 GEN
Solar/Wind Harmer
2.197
971933AH1-491 GEN
Solar/Wind Harmer
1.462
20091526CHSTN_FL
Solar/Wind Helper
0.606
20083826HOMER C2
50/50
226.144
972077AH1-588 GEN
Solar/Wind Harmer
36.661
970313AG2-206 GEN
Solar/Wind Harmer
4.744
20089226LOOKOUT
Solar/Wind Helper
0.733
971183AH1-050 GEN
Solar/Wind Harmer
3.661
966771AG1-548 GEN
Solar/Wind Harmer
10.973
964201AG1-281 GEN
Solar/Wind Helper
0.593
957161AF2-010 GEN
Solar/Wind Harmer
0.212
944411AF1-106 GEN
Solar/Wind Harmer
3.893
970663AG2-429 GEN
Solar/Wind Harmer
5.484
971931AH1-490 GEN
Solar/Wind Harmer
1.525
20089126CSLMN_L13
Solar/Wind Helper
0.753
970715AG2-457 GEN
Solar/Wind Harmer
12.22
203963AG1-253 GEN
Solar/Wind Harmer
0.315
203962AF1-287 GEN
Solar/Wind Harmer
1.523
20083426SW_E13_K22
Solar/Wind Helper
0.21
202652Y1-033 WT C
Solar/Wind Helper
0.598
203955AF1-039 C O1
Solar/Wind Helper
0.346
946071AF1-272 GEN
Solar/Wind Helper
2.311
972079AH1-589 GEN
Solar/Wind Harmer
48.089
971703AH1-357 GEN
Solar/Wind Harmer
3.055
971707AH1-359 GEN
Solar/Wind Harmer
3.055
971709AH1-360 GEN
Solar/Wind Harmer
5.658
20334926Z1-069 C
Solar/Wind Harmer
7.808
971355AH1-158 GEN
Solar/Wind Harmer
4.068
20088626ARWF_N39
Solar/Wind Helper
1.789
20094526CT_V3-030
Solar/Wind Helper
0.4
203859AF2-294 C
Solar/Wind Harmer
1.766
971127AH1-005 GEN
Solar/Wind Harmer
1.989
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.044
966771AG1-548 GEN
Solar/Wind Harmer
3.387
20398826ARMNA MT
Solar/Wind Harmer
7.191
970335AG2-220 GEN
Solar/Wind Harmer
3.084
970647AG2-420 GEN
Solar/Wind Harmer
1.508
20084626FORWARD
Solar/Wind Helper
0.766
20088826HIGHLAND
Solar/Wind Helper
1.567
20089026BF_G21_K23
Solar/Wind Helper
0.596
970647AG2-420 GEN
Solar/Wind Harmer
0.698
20092526R32
Solar/Wind Helper
1.808
964391AG1-301 GEN
Solar/Wind Helper
0.331
970677AG2-438 GEN
Solar/Wind Harmer
0.731
20303426NA_O38_P22
Solar/Wind Helper
1.456
972075AH1-587 GEN
Solar/Wind Harmer
23.838
941231AE2-117 GEN
Solar/Wind Helper
0.323
20083926HOMER C3
50/50
275.574
203813AE2-344_GEN
Solar/Wind Harmer
8.844
203940AF1-140 C
Solar/Wind Helper
0.528
944781AF1-143 GEN
Solar/Wind Helper
2.934
970267AG2-176 GEN
Solar/Wind Harmer
12.824
970305AG2-200 GEN
Solar/Wind Harmer
1.621
970713AG2-456 GEN
Solar/Wind Harmer
12.22
944411AF1-106 GEN
Solar/Wind Harmer
-0.018
203961AE2-224 GEN
Solar/Wind Helper
3.565
971705AH1-358 GEN
Solar/Wind Harmer
5.658
970337AG2-221 GEN
Solar/Wind Harmer
2.044
970511AG2-327 GEN
Solar/Wind Harmer
0.988
970663AG2-429 GEN
Solar/Wind Harmer
3.49
20088926STNY CRK
Solar/Wind Helper
1.228
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.423
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.002
MECLTFEXP_MEC->PJM
CLTF
0.705
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
0.53
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.01
TVALTFEXP_TVA->PJM
CLTF
0.24
LGEELTFEXP_LGEE->PJM
CLTF
0.27
WECLTFEXP_WEC->PJM
CLTF
0.179
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.048

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.2 %
Rating:824.0 MVA
Rating Type:B
MVA to Mitigate:875.06
MW Contribution:2.75
Bus #Bus NameTypeMW Contribution
971185AH1-051 GEN
Solar/Wind Harmer
2.678
203948AG1-140 C
Solar/Wind Harmer
0.229
971933AH1-491 GEN
Solar/Wind Harmer
1.692
20091526CHSTN_FL
Solar/Wind Helper
0.509
20083826HOMER C2
50/50
233.509
972077AH1-588 GEN
Solar/Wind Harmer
33.057
970313AG2-206 GEN
Solar/Wind Harmer
4.911
20089226LOOKOUT
Solar/Wind Helper
0.695
971183AH1-050 GEN
Solar/Wind Harmer
4.464
957161AF2-010 GEN
Solar/Wind Harmer
6.52
964201AG1-281 GEN
Solar/Wind Helper
0.534
966771AG1-548 GEN
Solar/Wind Harmer
6.996
944411AF1-106 GEN
Solar/Wind Harmer
3.992
970663AG2-429 GEN
Solar/Wind Harmer
7.325
971931AH1-490 GEN
Solar/Wind Harmer
1.725
20089126CSLMN_L13
Solar/Wind Helper
0.713
970715AG2-457 GEN
Solar/Wind Harmer
11.019
203963AG1-253 GEN
Solar/Wind Harmer
0.35
203962AF1-287 GEN
Solar/Wind Harmer
1.723
20083426SW_E13_K22
Solar/Wind Helper
0.198
202652Y1-033 WT C
Solar/Wind Helper
0.571
203955AF1-039 C O1
Solar/Wind Helper
0.33
946071AF1-272 GEN
Solar/Wind Helper
2.049
971709AH1-360 GEN
Solar/Wind Harmer
5.101
20334926Z1-069 C
Solar/Wind Harmer
7.667
971355AH1-158 GEN
Solar/Wind Harmer
4.96
20088626ARWF_N39
Solar/Wind Helper
1.641
203859AF2-294 C
Solar/Wind Harmer
1.811
971127AH1-005 GEN
Solar/Wind Harmer
2.058
972079AH1-589 GEN
Solar/Wind Harmer
43.362
971703AH1-357 GEN
Solar/Wind Harmer
2.755
971707AH1-359 GEN
Solar/Wind Harmer
2.755
20398826ARMNA MT
Solar/Wind Harmer
7.381
970335AG2-220 GEN
Solar/Wind Harmer
3.191
970647AG2-420 GEN
Solar/Wind Harmer
1.816
20084626FORWARD
Solar/Wind Helper
0.721
20088826HIGHLAND
Solar/Wind Helper
1.457
20089026BF_G21_K23
Solar/Wind Helper
0.565
970647AG2-420 GEN
Solar/Wind Harmer
0.841
20092526R32
Solar/Wind Helper
1.681
203804AE2-113_GEN
Solar/Wind Harmer
0
970555AG2-356 GEN
Solar/Wind Harmer
2.118
970677AG2-438 GEN
Solar/Wind Harmer
0.846
20303426NA_O38_P22
Solar/Wind Helper
1.336
966771AG1-548 GEN
Solar/Wind Harmer
2.159
972075AH1-587 GEN
Solar/Wind Harmer
23.992
20083926HOMER C3
50/50
284.548
238219AF1-167 C
Solar/Wind Harmer
1.29
203813AE2-344_GEN
Solar/Wind Harmer
10.002
203940AF1-140 C
Solar/Wind Helper
0.483
944781AF1-143 GEN
Solar/Wind Helper
2.779
970305AG2-200 GEN
Solar/Wind Harmer
1.946
970267AG2-176 GEN
Solar/Wind Harmer
14.541
970713AG2-456 GEN
Solar/Wind Harmer
11.019
944411AF1-106 GEN
Solar/Wind Harmer
-0.018
203961AE2-224 GEN
Solar/Wind Helper
3.303
971705AH1-358 GEN
Solar/Wind Harmer
5.101
970337AG2-221 GEN
Solar/Wind Harmer
2.118
970663AG2-429 GEN
Solar/Wind Harmer
4.661
970511AG2-327 GEN
Solar/Wind Harmer
1.023
20088926STNY CRK
Solar/Wind Helper
1.151
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.113
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.541
SIGELTFEXP_SIGE->PJM
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.336
TVALTFEXP_TVA->PJM
CLTF
0.143
LGEELTFEXP_LGEE->PJM
CLTF
0.2
WECLTFEXP_WEC->PJM
CLTF
0.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.102

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-028_SRT-A-1


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-028_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:148.81 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:238.1
MW Contribution:1.65
Bus #Bus NameTypeMW Contribution
971627AH1-313 GEN
50/50
Charging
2.796
203804AE2-113_GEN
Solar/Wind Harmer
0
203952AE2-129 C
Solar/Wind Helper
0.315
972079AH1-589 GEN
Solar/Wind Harmer
25.951
971703AH1-357 GEN
Solar/Wind Harmer
1.649
971707AH1-359 GEN
Solar/Wind Harmer
1.649
970715AG2-457 GEN
Solar/Wind Harmer
6.595
238202AE2-262_GEN
Solar/Wind Helper
1.262
238206AE2-263_GEN
Solar/Wind Helper
1.183
962411AG1-090 GEN
50/50
Charging
2.54
971709AH1-360 GEN
Solar/Wind Harmer
3.053
20334926Z1-069 C
Solar/Wind Harmer
3.747
203854AF2-039 C
Solar/Wind Helper
0.286
971705AH1-358 GEN
Solar/Wind Harmer
3.053
238217AF1-153 C O1
Solar/Wind Helper
0.38
203946AE2-131 C
Solar/Wind Helper
0.315
972077AH1-588 GEN
Solar/Wind Harmer
19.784
972075AH1-587 GEN
Solar/Wind Harmer
42.844
203855AF2-088 C
Solar/Wind Helper
0.138
970713AG2-456 GEN
Solar/Wind Harmer
6.595
203954AE2-126 C
Solar/Wind Helper
0.835
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.769
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.073
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.047
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-008_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.64 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:234.62
MW Contribution:1.65
Bus #Bus NameTypeMW Contribution
971627AH1-313 GEN
50/50
Charging
2.796
203804AE2-113_GEN
Solar/Wind Harmer
0
203952AE2-129 C
Solar/Wind Helper
0.315
972079AH1-589 GEN
Solar/Wind Harmer
25.951
971703AH1-357 GEN
Solar/Wind Harmer
1.649
971707AH1-359 GEN
Solar/Wind Harmer
1.649
970715AG2-457 GEN
Solar/Wind Harmer
6.595
238202AE2-262_GEN
Solar/Wind Helper
1.262
238206AE2-263_GEN
Solar/Wind Helper
1.183
962411AG1-090 GEN
50/50
Charging
2.54
971709AH1-360 GEN
Solar/Wind Harmer
3.053
20334926Z1-069 C
Solar/Wind Harmer
3.747
203854AF2-039 C
Solar/Wind Helper
0.286
971705AH1-358 GEN
Solar/Wind Harmer
3.053
238217AF1-153 C O1
Solar/Wind Helper
0.38
203946AE2-131 C
Solar/Wind Helper
0.315
972077AH1-588 GEN
Solar/Wind Harmer
19.784
972075AH1-587 GEN
Solar/Wind Harmer
42.844
203855AF2-088 C
Solar/Wind Helper
0.138
970713AG2-456 GEN
Solar/Wind Harmer
6.595
203954AE2-126 C
Solar/Wind Helper
0.835
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.769
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.073
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.047
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-39C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-39C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.42 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:232.67
MW Contribution:1.65
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
203952AE2-129 C
Solar/Wind Helper
0.315
972079AH1-589 GEN
Solar/Wind Harmer
25.951
971703AH1-357 GEN
Solar/Wind Harmer
1.649
970715AG2-457 GEN
Solar/Wind Harmer
6.595
238206AE2-263_GEN
Solar/Wind Helper
1.183
971709AH1-360 GEN
Solar/Wind Harmer
3.053
20334926Z1-069 C
Solar/Wind Harmer
3.747
203854AF2-039 C
Solar/Wind Helper
0.286
971705AH1-358 GEN
Solar/Wind Harmer
3.053
238217AF1-153 C O1
Solar/Wind Helper
0.38
203946AE2-131 C
Solar/Wind Helper
0.315
238202AE2-262_GEN
Solar/Wind Helper
1.262
971707AH1-359 GEN
Solar/Wind Harmer
1.649
972077AH1-588 GEN
Solar/Wind Harmer
19.784
972075AH1-587 GEN
Solar/Wind Harmer
42.844
203855AF2-088 C
Solar/Wind Helper
0.138
970713AG2-456 GEN
Solar/Wind Harmer
6.595
203954AE2-126 C
Solar/Wind Helper
0.835
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.769
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.073
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.047
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-39B_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-39B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.96 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:231.94
MW Contribution:1.65
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
203952AE2-129 C
Solar/Wind Helper
0.315
238206AE2-263_GEN
Solar/Wind Helper
1.183
971709AH1-360 GEN
Solar/Wind Harmer
3.053
20334926Z1-069 C
Solar/Wind Harmer
3.747
203854AF2-039 C
Solar/Wind Helper
0.286
971705AH1-358 GEN
Solar/Wind Harmer
3.053
238217AF1-153 C O1
Solar/Wind Helper
0.38
203946AE2-131 C
Solar/Wind Helper
0.315
970715AG2-457 GEN
Solar/Wind Harmer
6.595
238202AE2-262_GEN
Solar/Wind Helper
1.262
972079AH1-589 GEN
Solar/Wind Harmer
25.951
971703AH1-357 GEN
Solar/Wind Harmer
1.649
971707AH1-359 GEN
Solar/Wind Harmer
1.649
972077AH1-588 GEN
Solar/Wind Harmer
19.784
972075AH1-587 GEN
Solar/Wind Harmer
42.844
203855AF2-088 C
Solar/Wind Helper
0.138
970713AG2-456 GEN
Solar/Wind Harmer
6.595
203954AE2-126 C
Solar/Wind Helper
0.835
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.769
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.073
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.047
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.98 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:199.97
MW Contribution:1.59
Bus #Bus NameTypeMW Contribution
238206AE2-263_GEN
Solar/Wind Helper
1.626
972077AH1-588 GEN
Solar/Wind Harmer
19.055
970715AG2-457 GEN
Solar/Wind Harmer
6.352
238202AE2-262_GEN
Solar/Wind Helper
1.735
203855AF2-088 C
Solar/Wind Helper
0.18
972079AH1-589 GEN
Solar/Wind Harmer
24.995
971703AH1-357 GEN
Solar/Wind Harmer
1.588
971707AH1-359 GEN
Solar/Wind Harmer
1.588
971709AH1-360 GEN
Solar/Wind Harmer
2.941
20334926Z1-069 C
Solar/Wind Harmer
3.571
203854AF2-039 C
Solar/Wind Helper
0.374
203853AF1-134 C O1
Solar/Wind Helper
0.358
203804AE2-113_GEN
Solar/Wind Harmer
0
203952AE2-129 C
Solar/Wind Helper
0.419
972075AH1-587 GEN
Solar/Wind Harmer
41.157
238183AE2-316 GEN
Solar/Wind Helper
1.582
970713AG2-456 GEN
Solar/Wind Harmer
6.352
203954AE2-126 C
Solar/Wind Helper
1.001
971705AH1-358 GEN
Solar/Wind Harmer
2.941
238217AF1-153 C O1
Solar/Wind Helper
0.523
203946AE2-131 C
Solar/Wind Helper
0.419
946381AF1-302 GEN
Solar/Wind Helper
0.848
CPLELTFEXP_CPLE->PJM
CLTF
0.019
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.263
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.221
MECLTFEXP_MEC->PJM
CLTF
0.123
SIGELTFEXP_SIGE->PJM
CLTF
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
0.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.088
TVALTFEXP_TVA->PJM
CLTF
0.056
LGEELTFEXP_LGEE->PJM
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.03

Details for AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
AE2-113_TAP-26RIDGWAY 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.8 %
Rating:133.0 MVA
Rating Type:A
MVA to Mitigate:140.71
MW Contribution:0.84
Bus #Bus NameTypeMW Contribution
203804AE2-113_GEN
Solar/Wind Harmer
0
972079AH1-589 GEN
Solar/Wind Harmer
13.186
971703AH1-357 GEN
Solar/Wind Harmer
0.838
971707AH1-359 GEN
Solar/Wind Harmer
0.838
970715AG2-457 GEN
Solar/Wind Harmer
3.351
20334926Z1-069 C
Solar/Wind Harmer
2.647
971709AH1-360 GEN
Solar/Wind Harmer
1.551
203854AF2-039 C
Solar/Wind Helper
0.244
971705AH1-358 GEN
Solar/Wind Harmer
1.551
238217AF1-153 C O1
Solar/Wind Helper
0.298
972077AH1-588 GEN
Solar/Wind Harmer
10.053
972075AH1-587 GEN
Solar/Wind Harmer
39.171
203855AF2-088 C
Solar/Wind Helper
0.118
970713AG2-456 GEN
Solar/Wind Harmer
3.351
203954AE2-126 C
Solar/Wind Helper
0.77
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.461
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.065
MECLTFEXP_MEC->PJM
CLTF
0.042
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.034
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.016
LGEELTFEXP_LGEE->PJM
CLTF
0.017
WECLTFEXP_WEC->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.002

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-028_SRT-A-1


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-028_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.0 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:196.81
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
971627AH1-313 GEN
50/50
Charging
2.759
203804AE2-113_GEN
Solar/Wind Helper
19.397
203952AE2-129 C
Solar/Wind Helper
0.31
972079AH1-589 GEN
Solar/Wind Harmer
26.076
971703AH1-357 GEN
Solar/Wind Harmer
1.657
971707AH1-359 GEN
Solar/Wind Harmer
1.657
970715AG2-457 GEN
Solar/Wind Harmer
6.626
238202AE2-262_GEN
Solar/Wind Helper
1.246
238206AE2-263_GEN
Solar/Wind Helper
1.168
962411AG1-090 GEN
50/50
Charging
2.504
971709AH1-360 GEN
Solar/Wind Harmer
3.068
20334926Z1-069 C
Solar/Wind Harmer
3.77
203854AF2-039 C
Solar/Wind Helper
0.283
971705AH1-358 GEN
Solar/Wind Harmer
3.068
238217AF1-153 C O1
Solar/Wind Helper
0.376
203946AE2-131 C
Solar/Wind Helper
0.31
972077AH1-588 GEN
Solar/Wind Harmer
19.879
972075AH1-587 GEN
Solar/Wind Harmer
42.923
203855AF2-088 C
Solar/Wind Helper
0.136
970713AG2-456 GEN
Solar/Wind Harmer
6.626
203954AE2-126 C
Solar/Wind Helper
0.83
G-007ALTFEXP_G-007A->PJM
CMTX
0.11
CPLELTFEXP_CPLE->PJM
CLTF
0.042
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.128
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.15
MECLTFEXP_MEC->PJM
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.079
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.118
TVALTFEXP_TVA->PJM
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.014
VFTLTFEXP_VFT->PJM
CMTX
0.331
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P1-2_PN-230-008_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.85 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:193.36
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
971627AH1-313 GEN
50/50
Charging
2.759
203804AE2-113_GEN
Solar/Wind Helper
19.397
203952AE2-129 C
Solar/Wind Helper
0.31
972079AH1-589 GEN
Solar/Wind Harmer
26.076
971703AH1-357 GEN
Solar/Wind Harmer
1.657
971707AH1-359 GEN
Solar/Wind Harmer
1.657
970715AG2-457 GEN
Solar/Wind Harmer
6.626
238202AE2-262_GEN
Solar/Wind Helper
1.246
238206AE2-263_GEN
Solar/Wind Helper
1.168
962411AG1-090 GEN
50/50
Charging
2.504
971709AH1-360 GEN
Solar/Wind Harmer
3.068
20334926Z1-069 C
Solar/Wind Harmer
3.77
203854AF2-039 C
Solar/Wind Helper
0.283
971705AH1-358 GEN
Solar/Wind Harmer
3.068
238217AF1-153 C O1
Solar/Wind Helper
0.376
203946AE2-131 C
Solar/Wind Helper
0.31
972077AH1-588 GEN
Solar/Wind Harmer
19.879
972075AH1-587 GEN
Solar/Wind Harmer
42.923
203855AF2-088 C
Solar/Wind Helper
0.136
970713AG2-456 GEN
Solar/Wind Harmer
6.626
203954AE2-126 C
Solar/Wind Helper
0.83
G-007ALTFEXP_G-007A->PJM
CMTX
0.11
CPLELTFEXP_CPLE->PJM
CLTF
0.042
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.128
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.15
MECLTFEXP_MEC->PJM
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.079
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.118
TVALTFEXP_TVA->PJM
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.014
VFTLTFEXP_VFT->PJM
CMTX
0.331
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-39C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-39C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.66 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:191.46
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
238206AE2-263_GEN
Solar/Wind Helper
1.168
972077AH1-588 GEN
Solar/Wind Harmer
19.879
972075AH1-587 GEN
Solar/Wind Harmer
42.923
971705AH1-358 GEN
Solar/Wind Harmer
3.068
238217AF1-153 C O1
Solar/Wind Helper
0.376
203946AE2-131 C
Solar/Wind Helper
0.31
971709AH1-360 GEN
Solar/Wind Harmer
3.068
20334926Z1-069 C
Solar/Wind Harmer
3.77
203854AF2-039 C
Solar/Wind Helper
0.283
972079AH1-589 GEN
Solar/Wind Harmer
26.076
971703AH1-357 GEN
Solar/Wind Harmer
1.657
971707AH1-359 GEN
Solar/Wind Harmer
1.657
970715AG2-457 GEN
Solar/Wind Harmer
6.626
238202AE2-262_GEN
Solar/Wind Helper
1.246
203855AF2-088 C
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
19.397
203952AE2-129 C
Solar/Wind Helper
0.31
970713AG2-456 GEN
Solar/Wind Harmer
6.626
203954AE2-126 C
Solar/Wind Helper
0.83
G-007ALTFEXP_G-007A->PJM
CMTX
0.11
CPLELTFEXP_CPLE->PJM
CLTF
0.042
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.128
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.15
MECLTFEXP_MEC->PJM
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.079
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.118
TVALTFEXP_TVA->PJM
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.014
VFTLTFEXP_VFT->PJM
CMTX
0.331
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-39B_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-39B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.22 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:190.76
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
238206AE2-263_GEN
Solar/Wind Helper
1.168
972077AH1-588 GEN
Solar/Wind Harmer
19.879
972075AH1-587 GEN
Solar/Wind Harmer
42.923
971705AH1-358 GEN
Solar/Wind Harmer
3.068
238217AF1-153 C O1
Solar/Wind Helper
0.376
203946AE2-131 C
Solar/Wind Helper
0.31
971709AH1-360 GEN
Solar/Wind Harmer
3.068
20334926Z1-069 C
Solar/Wind Harmer
3.77
203854AF2-039 C
Solar/Wind Helper
0.283
972079AH1-589 GEN
Solar/Wind Harmer
26.076
971703AH1-357 GEN
Solar/Wind Harmer
1.657
971707AH1-359 GEN
Solar/Wind Harmer
1.657
970715AG2-457 GEN
Solar/Wind Harmer
6.626
238202AE2-262_GEN
Solar/Wind Helper
1.246
203855AF2-088 C
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
19.397
203952AE2-129 C
Solar/Wind Helper
0.31
970713AG2-456 GEN
Solar/Wind Harmer
6.626
203954AE2-126 C
Solar/Wind Helper
0.83
G-007ALTFEXP_G-007A->PJM
CMTX
0.11
CPLELTFEXP_CPLE->PJM
CLTF
0.042
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.128
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.15
MECLTFEXP_MEC->PJM
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.079
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.118
TVALTFEXP_TVA->PJM
CLTF
0.04
LGEELTFEXP_LGEE->PJM
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.014
VFTLTFEXP_VFT->PJM
CMTX
0.331
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.148

Details for AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line l/o PN_P7-1_PN-230-002A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
AH1-587 TP-AE2-113_TAP 115.0 kV Ckt 1 line
Contingency Name:
PN_P7-1_PN-230-002A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.41 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:163.86
MW Contribution:1.6
Bus #Bus NameTypeMW Contribution
238206AE2-263_GEN
Solar/Wind Helper
1.611
970715AG2-457 GEN
Solar/Wind Harmer
6.383
238202AE2-262_GEN
Solar/Wind Helper
1.718
203855AF2-088 C
Solar/Wind Helper
0.179
971709AH1-360 GEN
Solar/Wind Harmer
2.955
20334926Z1-069 C
Solar/Wind Harmer
3.594
203854AF2-039 C
Solar/Wind Helper
0.371
203853AF1-134 C O1
Solar/Wind Helper
0.354
972079AH1-589 GEN
Solar/Wind Harmer
25.119
971703AH1-357 GEN
Solar/Wind Harmer
1.596
971707AH1-359 GEN
Solar/Wind Harmer
1.596
203804AE2-113_GEN
Solar/Wind Helper
20.101
203952AE2-129 C
Solar/Wind Helper
0.414
972075AH1-587 GEN
Solar/Wind Harmer
41.236
238183AE2-316 GEN
Solar/Wind Helper
1.564
972077AH1-588 GEN
Solar/Wind Harmer
19.15
970713AG2-456 GEN
Solar/Wind Harmer
6.383
203954AE2-126 C
Solar/Wind Helper
0.996
971705AH1-358 GEN
Solar/Wind Harmer
2.955
238217AF1-153 C O1
Solar/Wind Helper
0.519
203946AE2-131 C
Solar/Wind Helper
0.414
946381AF1-302 GEN
Solar/Wind Helper
0.838
CPLELTFEXP_CPLE->PJM
CLTF
0.088
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.719
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.461
MECLTFEXP_MEC->PJM
CLTF
0.229
SIGELTFEXP_SIGE->PJM
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.28
TVALTFEXP_TVA->PJM
CLTF
0.12
LGEELTFEXP_LGEE->PJM
CLTF
0.093
WECLTFEXP_WEC->PJM
CLTF
0.054
CONTINGENCY 'AP_P1-3_WP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235282 TO BUS 235240 CKT 1   /*01GAR RN     138.0 - 01COLMBGPN   138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                   /*26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1                /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                                /*26HOMER CT   230.0
 SET POSTCONTRATING 1000 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
 SET PRECONTRATING 830 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-4_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200758 CKT 1   /*26SEWARD 2   230.0 - 26JOHNSTWN   230.0
 OPEN BUS 200767                                   /*26HOMER CT   230.0
END
CONTINGENCY 'AP_P1-2_WP-138-087_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235825 CKT 1   /*01BRACKENRDG 138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1   /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1   /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1   /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235825 TO BUS 235132 CKT 1   /*01ALL L4T    138.0 - 01AL 4       138.0
END
CONTINGENCY 'AP_P1-2_WP-138-103_SRT-A'
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235134 CKT 1   /*01AL&D6T     138.0 - 01AL&D6      138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235139 CKT 1   /*01KITTAN     138.0 - 01AL&D6T     138.0
 DISCONNECT BUS 235134                                   /*01AL&D6      138.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1          /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1   /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
END
CONTINGENCY 'AP_P1-2_WP-345-311T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235129 TO BUS 200769 CKT 1   /*01ARMSTRONG  345.0 - 26HOMER CY   345.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-210_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200807 TO BUS 200808 CKT 1   /*26PIERC230   230.0 - 26PIERC138   138.0
 DISCONNECT BRANCH FROM BUS 200808 TO BUS 200809 CKT 1   /*26PIERC138   138.0 - 26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-2_PN-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
 DISCONNECT BUS 200807                                   /*26PIERC230   230.0
 DISCONNECT BUS 200808                                   /*26PIERC138   138.0
 DISCONNECT BUS 200809                                   /*26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P1-3_DRT-230-003-DRT_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-307-DRT-010_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 961580 CKT 1          /*26HOMER CY   345.0 - Q1080 TAP    345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-308_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 961580 CKT 1   /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P7-1_PN-230-002A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200581 CKT 1   /*26GLADE      230.0 - 26FOREST     230.0
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1   /*26GLADE      230.0 - 26LEWIS RN   230.0
END
CONTINGENCY 'AP_P7-1_WPP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1    /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1    /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1    /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1    /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T-DRT-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P1-2_PN-230-028_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 970712 CKT 1   /*26LEWIS RN   230.0 - AG2-456 TP   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-008_SRT-A'
 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1   /*26GLADE      230.0 - 26LEWIS RN   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-39C_SRT-A'
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 200705 CKT 2   /*26LEWIS RN   230.0 - 26LEWS RN2    34.5
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 970712 CKT 1   /*26LEWIS RN   230.0 - AG2-456 TP   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-39B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 200697 CKT 6   /*26LEWIS RN   230.0 - 26LEWS RN3    34.5
 DISCONNECT BRANCH FROM BUS 200704 TO BUS 970712 CKT 1   /*26LEWIS RN   230.0 - AG2-456 TP   230.0
END
235139 to 235138 ckt 1
235129 to 235121 ckt 2
235240 to 235202 ckt 1
235282 to 235240 ckt 1
235204 to 235139 ckt 1
999266 to 200767 ckt S
200769 to 999266 ckt S
203800 to 200582 ckt 1
972074 to 203800 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-076Hunterstown-Conemaugh 500kVIn Service
AA1-082E. Towanda 230kVIn Service
AA2-133Wyalusing 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-032Church-Wye Mills 138 kVIn Service
AB2-036Church - Oil City 138kVSuspended
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-057Brunswick 26kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-172Todd 69kVIn Service
AB2-179Townsend 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-190East New Market 69kVSuspended
AC2-009Pennington 13 kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-185Cedar Creek 138kV IIEngineering & Procurement
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-042Camden Switch 26 kV IIIn Service
AD2-062Roxbury-Greene 138 kVSuspended
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-076Carville 138 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-133Eagle Valley 115kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-104BL England 138 kVSuspended
AE1-123Emlenton 34.5 kVIn Service
AE1-129Zion View - Middletown 115 kVSuspended
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-226Face Rock-Kinzer #13 69 kVWithdrawn
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE2-001Nittany-Zion 46 kVSuspended
AE2-042Milton 69 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-084Derry Tap-Derry Bus 69 kVEngineering & Procurement
AE2-110Columbia-West Bloomsburg 69 kVSuspended
AE2-112Carville 138 kV IISuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-211Jackson-Three Mile Island 230 kVSuspended
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-241Bloomsburg-Columbia 69 kVSuspended
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-271Montour 230 kVWithdrawn
AE2-316Brookville-Squab Hollow 138 kVUnder Construction
AE2-344Edinboro South-Venango Junction 115 kVSuspended
AE2-345Hunterstown-Texas Eastern Tap 115 kVSuspended
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-036Carville 138 kV IIISuspended
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-106East Sayre 34.5 kVWithdrawn
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-167West Freedom-C&K Coal 25 kVSuspended
AF1-208Laurel-Roadstown 69 kVWithdrawn
AF1-226Bowmans Mill-Scott 69 kVSuspended
AF1-240Timblin 34.5 kVActive
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-271AGratz 69 kVSuspended
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-287Edinboro South 34.5 kV IISuspended
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-321Hooversville 115 kV ISuspended
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-010Union City-Titusville 115 kVActive
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-050Bear Rock-Johnstown 230 kVActive
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-092Snake Spring-Bedford Area 23 kVSuspended
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-165Clark Summit-Emlenton 34.5 kVIn Service
AF2-166Emlenton 34.5 kVWithdrawn
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-221Scalp Level 22.9 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-254Cookstown-New Lisbon 34.5 kVSuspended
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-358Airey-Vienna 69 kVActive
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-445AFishbach-Port Carbon 69 kVSuspended
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-041Osterburg-Bedford North 23 kVWithdrawn
AG1-090Philipsburg 115 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-140Union City 34.5 kVSuspended
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-253Erie East-Union City 34.5 kVSuspended
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-362Wernersville 12.47 kVSuspended
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-377Philipsburg 115 kVActive
AG1-378Philipsburg 115 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-450Airey-Vienna 69 kV IIActive
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-487Gilbert 230 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-511Kittatinny 230 kVEngineering & Procurement
AG1-514Springdale CT III 138 kVWithdrawn
AG1-548Erie South-Union City 115 kVActive
AG2-016Oyster Creek-Whitings 34.5 kVActive
AG2-055Deans 500 kVWithdrawn
AG2-074Meckesville Tap 69kVActive
AG2-090Scalp Level 23 kV IVActive
AG2-091Scalp Level 23 kV VActive
AG2-161Wheelabrator Frackville-Gilberton 69 kVActive
AG2-176Geneva 115 kVActive
AG2-181Airey - Golden Hill 69 kVActive
AG2-200North Warren–Russell 34.5 kVActive
AG2-206Tennessee Gas-East Towanda 115 kVActive
AG2-220East Towanda-South Troy 115 kVActive
AG2-221South Troy - North Towanda 34.5 kVActive
AG2-297Cumberland 230 kVActive
AG2-327Tennessee Gas-East Towanda 115 kVActive
AG2-347Indian River 230 kV IIActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-380Carville 138 kV IVActive
AG2-411Statler Hill 115 kVActive
AG2-418Blain 115 kVActive
AG2-420Eclipse #2 34.5 kVActive
AG2-429Burma - Armstrong 138 kVActive
AG2-430Sunbury-Dalmatia 69 kV IIActive
AG2-438Union City 34.5 kVActive
AG2-439Oxbow 34.5 kVActive
AG2-447Cedar Creek 138 kV VIIActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AG2-582Flint Run 500 kVActive
AG2-616Churchtown - Upper Pittsgrove 138 kVActive
AG2-625Pequest River-Furnace Brook Tap 34.5 kV IIActive
AG2-626Pequest River-Furnace Brook Tap 34.5 kV IIIActive
AG2-627Woodstown-High Street 69 kVActive
AG2-654Craigsville - Leards Crossing 12 kVActive
AH1-005East Towanda-South Troy 115 kV IIActive
AH1-027Cartanza 230 kVActive
AH1-050Eclipse-Piney 115 kVActive
AH1-051Eclipse-Piney 115 kV IIActive
AH1-054Upton-Whitings 34.5 kVActive
AH1-057Edgewood 12.47 kVActive
AH1-102Seward-Glory 115 kVActive
AH1-140Vasco 138 kVActive
AH1-158Eclipse-Piney 115 kV IIIActive
AH1-201Allegheny-New Baltimore 115kVActive
AH1-203Allegheny-Somerset 115 kVActive
AH1-205Allegheny-New Baltimore 115kVActive
AH1-212Bethlehem - Lilly 46 kVActive
AH1-257Broadway - Washington 34.5 kVActive
AH1-258Belford - Keansburg 34.5 kVActive
AH1-265Winslow - Monroe 69kVActive
AH1-268Seward-Glory 115 kV IIActive
AH1-274Butler 69 kVActive
AH1-313Moshannon-Milesburg 230 kV VIIActive
AH1-334Lakehurst - Whitings 34.5 kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-380Mt Olive - Kenny 69kVActive
AH1-452Clementine-Clementine Jct. 25 kVActive
AH1-460Hooversville - Scalp Level 115 kVActive
AH1-490Venango Junction 34.5 kVActive
AH1-491Union City 34.5 kVActive
AH1-536Church-Oil City 138kVActive
AH1-584Nelson-Indian River 138kVActive
AH1-585Nelson-Indian River 138kVActive
AH1-586Nelson-Indian River 138kVActive
AH1-587Farmers Valley – Ridgeway 115 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-634Indian River 230kV IActive
AH1-641Churchtown - Upper Pittsgrove 138kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
AH1-672Farmview 138 kVActive
AH1-680Sammis - South Canton 345 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-695Three Mile Island 230 kVActive
AH1-701Valero 69 kVActive
AH1-703Bergen 230kVActive
AH1-705Sunbury #1 500kVActive
AH1-707Saegers 230 kVActive
AH1-710Salem 500kVActive
AH1-715Linden 230kVActive
AH1-720East Towanda 230 kVActive
AH1-722Linden 230kVActive
AH1-746Madera - Westover South 115 kVActive
V1-021Cape May County 12kVIn Service
V2-041Clayville 12kVIn Service
V2-046Pilesgrove Township 12kVIn Service
V4-054Fairfield Township 12kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-062Clayton 138kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
X2-083Newark 12kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYISO_CY17_13387
Title
East Sayre-North Waverly 115kV line upgrade - NYSEG (NYISO CY17 driven upgrade)
Description
North Waverly terminal equipment upgrades and a line reconductor of the NYSEG portion of the East Sayre – North Waverly 115kV line. (Install approximately twenty-six (26) new steel pole structures, one (1) 795 kcmil (26/7) ACSR conductor, and 36 Fiber OPGW). Final expected SUM ratings with both NYSEG & Penelec work complete = 218/251 MVA SN/SE. NYSEG uses LTE for Rate B, not STE like FirstEnergy. The earliest projected in-service date for this project is in 2026, but that timeframe may shift to complete the terminal equipment work at North Waverly. The final trip setting for the line will be updated during engineering and construction, but it must meet at least 176 MVA. Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal needs to be upgraded since it is limiting. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$10,525,000
Allocated Cost ($USD)
$0
Time Estimate
32 Months

Info

Note: AH1-357 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYSEG
Title
NYSEG Equipment Upgrades Required (Oakdale - Laurel Lake 115kV)
Description
NYSEG equipment upgrades are required on their portion of the line section from Oakdale (NYSEG) to Laurel Lake (FirstEnergy) in order to achieve the higher line ratings once the FirstEnergy upgrades are complete on their section of line. A full line reconductor is expected. The scope, cost, and time estimate will be covered under the Affected System Study process with NYISO.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYSEG
Title
NYSEG line ratings (NYSEG end Only)
Description
NYSEG records for this line indicate the ratings below, which should be consistent with the most recent NYISO FERC 715 cases. - Summer: 108/128/143 MVA (Normal/LTE/STE) - Winter: 133/149/162 MVA (Normal/LTE/STE) This line is limited by bus work at Goudey. However, the conductor (336.4 KCM 30/7 ACSR) appears to be limiting below the required 136 MVA. Below are the ratings on record for the main conductor: - Summer: 111/131/145 MVA (Normal/LTE/STE) - Winter: 143/157/167 MVA (Normal/LTE/STE)
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line(Any)
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Study Pending
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-357 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
PENELEC(Pending) / TC2-PN-001.bReconductor (Possible Rebuild) ~21.2 miles of Shawville-Shingletown 230kV transmission line. [PN side]$1,757,333
APS(Pending) / TC2-APS-020.bReconductor (Possible Rebuild) ~19.4 miles of Shawville-Shingletown 230kV transmission line. [WPP side]$1,642,873
PENELECn6855.2Rebuild 11.53 miles of transmission line between Warren and Glade.$1,483,232
PENELECn6817.1Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line$1,435,640
APS(Pending) / TC2-APS-034.cReconductor Shingletown - Lewistown 230kV line including T-line drop at Shingletown$1,050,141
APS(Pending) / TC2-PN-002.aReconductor Shingletown - Lewistown 230kV line [PN Side]$842,626
APS(Pending) / TC1-PH1-076Reconductor Butler - Karns City 138 kV line.$633,235
APS(Pending) / TC1-APS-002.dRebuild 11.6 miles of 556.5 ACSR of the Armstrong - Kittanning 138 kV line$587,195
APSn6183Rebuild 10.4 miles of 4/0 CU from Columbia Big Pine - Garretts Run Jct 138 kV (99 spans).$577,285
PENELECn8229Reconductor 18.7 miles the AE2-113 (Farmers Valley) - Ridgway 115 kV Line$546,741
PENELEC(Pending) / TC2-PN-010Reconductor FE owned 4.3 miles of Laurel Lake - Goudey (Oakdale) 115 kV Line$472,938
APS(Pending) / TC2-APS-017Reconductor (Possible Rebuild) ~5.9 miles of Elko - Carbon Center Jct 138 kV transmission line including (2) T-Line Drops at Elko$442,274
APSn7166.2Reconductor 7.6 miles of 4/0 CU from All Dam 6 Tap to structure 84 (66 spans)$370,503
PENELECn8281Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker$359,401
APSn7164.1Reconductor (Possible Rebuild) ~7.5 miles of the Karns City to Kissinger Jct 138kV line$321,067
PENELEC(Pending) / TC2-PN-011Replace 500/230 kV Conemaugh #3 Transformer$312,274
APSn7165.2Reconductor All Dam 6 - Kittanning 138kV line$296,465
APS(Pending) / TC2-APS-036.bUpgrade 345/138 kV #2 Transformer at Armstrong$244,210
APSn7171.1Rebuild approximately 4.0 miles of 4/0 CU on the Kiski Valley to Columbia Big Pine 138kV line.$238,415
APS(Pending) / TC1-PH1-066Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.$226,012
PENELEC(Pending) / TC2-PN-009Reconductor 6.2 miles of 115 kV Line between AH1-587 and AE2-113$191,085
PPLn6818Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.$42,136
APS(Pending) / TC2-APS-034.iReplace Circuit Breaker at Shingletown$23,194
PENELECn9118.0 / TC1-PN-001.gReplace disconnect switches and leads at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$22,384
APS(Pending) / TC2-APS-034.eReplace Current Transformers at Shingletown$22,361
PENELECn8096Install an additional 230kV circuit breaker between the East Towanda 230kV line terminal and the North Meshoppen 230/115kV #4 transformer.$20,920
PENELECn6855.1Replace substation conductor at Warren substation$20,225
PENELECn9127.0 / TC1-PN-003.gReplace disconnect switches and leads at Shelocta Substation (Keystone-Shelocta 230kV line terminal)$19,932
APS(Pending) / TC2-APS-036.aUpgrade/Replace (6) 138kV Substation Conductors [(2) ACSR 954 45/7 & (4) AAC 1000 37]$19,881
APS(Pending) / TC2-APS-026.aReplace (4) 10 Amp Meters & (3) 10 Amp Relays at Kittanning$19,433
PENELEC(Pending) / TC2-PN-003.cReplace substation conductor at Glade substation$19,098
PENELECn9117.0 / TC1-PN-001.fReplace disconnect switches at Homer City Substation (Homer City-Shelocta 230kV line terminal)$15,749
PENELECn9125.0 / TC1-PN-003.fReplace disconnect switches at Keystone Substation (Keystone-Shelocta 230kV line terminal)$14,024
APSn7166.1Replace 4/0 CU line exit at All Dam 6 Tap.$13,009
PENELECn9124.0 / TC1-PN-003.eReplace bus conductor at Keystone Substation (Keystone-Shelocta 230kV line terminal)$12,346
PENELEC(Pending) / TC2-PN-001.aReplace 230 kV bus conductor at Shawville$11,410
PENELEC(Pending) / TC2-PN-005.aReplace Sub conductor at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$10,917
APS(Pending) / TC2-APS-034.dReplace Disc Switches at Shingletown$10,178
APS(Pending) / TC2-APS-020.aReplace Bus Risers at Shingletown substation$9,690
APS(Pending) / TC2-APS-036.cUpdate/Replace 138 kV SEL-311B Relay$9,344
APS(Pending) / TC1-APS-002.cReplace/Upgrade (3) 138 kV T-Line Drops at Armstrong$9,165
APSn9241.0 / TC1-APS-002.bReplace 8 Amp ITH(50FD) relay at Kittanning$7,895
APS(Pending) / TC2-APS-034.hReplace/Update SEL-421 Relay at Shingletown$7,293
APS(Pending) / TC2-APS-034.gReplace/Update SEL-421 Relay at Shingletown$7,293
PENELECn7652Replace line trap at Shawville on the Shawville-Rockton Mountain 115kV line.$7,085
APS(Pending) / TC2-APS-031.bReplace 138 kV T-line drops at Karns City$7,083
APS(Pending) / TC2-APS-034.aReplace Bus Riser and Bus Side Disc Leads at Shingletown$6,115
APSn7165.1Replace T-line drops at All Dam 6$6,026
PENELECn6855.3Replace line trap at Glade$5,839
APSn9240.0 / TC1-APS-002.aReplace GE 800 Amp Wave Trap at Kittanning$5,645
APS(Pending) / TC2-APS-026.bReplace WHSE 1200 Amp Wave Trap at Armstrong$5,645
APS(Pending) / TC1-PH1-014Replace WT at Shingletown substation.$4,448
APS(Pending) / TC2-APS-034.bReplace Bus Riser at Shingletown$3,764
APS(Pending) / TC2-APS-036.dUpgrade/Replace (4) 138 kV SPS AL 3.00 PIPE Substation Conductors$3,542
APS(Pending) / TC2-APS-034.fReplace Breaker Leads at Shingletown$3,070
PENELEC(Pending) / TC2-PN-007.bReplace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)$2,941
PENELECn9121.0 / TC1-PN-003.dReplace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)$2,881
APS(Pending) / TC2-PN-002.bReplace/Update SEL-421 Relays at Lewistown$2,531
APS(Pending) / TC2-APS-031.aUpgrade (2) 138 kV Breaker Leads at Karns City$2,243
PENELECn9120.0 / TC1-PN-003.cReplace substation conductor at Keystone substation (Keystone-Shelocta 230kV line terminal)$2,098
PENELECn9126.0 / TC1-PN-003.hReplace breaker leads at Keystone Substation (Keystone-Shelocta 230kV line terminal)$1,707
PENELEC(Pending) / TC2-PN-007.aAdjust relay settings at Keystone and Shelocta$1,157
PENELEC(Pending) / TC2-PN-005.bAdjust Relays at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$663
PENELEC(Pending)Single Element Derate - Eliminated by end of 2025$0
PENELEC(Pending)FirstEnergy line ratings (FE end Only)$0
Grand Total:$14,473,305

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-001.b
Title
Reconductor (Possible Rebuild) ~21.2 miles of Shawville-Shingletown 230kV transmission line. [PN side]
Description
Reconductor (Possible Rebuild) ~21.2 miles of Shawville-Shingletown 230kV transmission line. [PN side] using one (1) 954 45/7 "Rail" ACSS. Requires reconductor of APS side of line to achieve higher line ratings.
Total Cost ($USD)
$107,340,814
Allocated Cost ($USD)
$1,757,333
Time Estimate
73 Months

Contributor

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
6.2 MW6.5%$7,030,471
AG2-457
6.2 MW6.5%$7,030,471
AH1-313
20.9 MW22.1%$23,757,593
AH1-357
1.5 MW1.6%$1,757,333
AH1-358
1.8 MW1.9%$2,044,337
AH1-359
1.5 MW1.6%$1,757,333
AH1-360
1.8 MW1.9%$2,044,337
AH1-587
20.6 MW21.8%$23,453,505
AH1-588
18.5 MW19.7%$21,092,551
AH1-589
15.3 MW16.2%$17,372,882

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-020.b
Title
Reconductor (Possible Rebuild) ~19.4 miles of Shawville-Shingletown 230kV transmission line. [WPP side]
Description
Reconductor (Possible Rebuild) ~19.4 miles of Shawville-Shingletown 230kV transmission line. [WPP side] using one (1) 954 45/7 "Rail" ACSS This project has a pre-req of TC2-PN-001.b (FE East project)
Total Cost ($USD)
$100,349,391
Allocated Cost ($USD)
$1,642,873
Time Estimate
69 Months

Contributor

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
6.2 MW6.5%$6,572,556
AG2-457
6.2 MW6.5%$6,572,556
AH1-313
20.9 MW22.1%$22,210,191
AH1-357
1.5 MW1.6%$1,642,873
AH1-358
1.8 MW1.9%$1,911,184
AH1-359
1.5 MW1.6%$1,642,873
AH1-360
1.8 MW1.9%$1,911,184
AH1-587
20.6 MW21.8%$21,925,909
AH1-588
18.5 MW19.7%$19,718,731
AH1-589
15.3 MW16.2%$16,241,335

System Reinforcement: n6855.2
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6855.2
Title
Rebuild 11.53 miles of transmission line between Warren and Glade.
Description
Total Cost ($USD)
$58,429,217
Allocated Cost ($USD)
$1,483,232
Time Estimate
49 Months

Contributor

FacilityContingency
26GLADE-26WARREN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
34.8 MW10.2%$5,933,100
AG2-457
34.8 MW10.2%$5,933,100
AH1-313
12.2 MW3.6%$2,074,750
AH1-357
8.7 MW2.5%$1,483,232
AH1-358
10.1 MW3.0%$1,724,721
AH1-359
8.7 MW2.5%$1,483,232
AH1-360
10.1 MW3.0%$1,724,721
AH1-587
32.9 MW9.6%$5,612,766
AH1-588
104.3 MW30.5%$17,799,300
AH1-589
85.9 MW25.1%$14,660,295

System Reinforcement: n6817.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6817.1
Title
Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line
Description
Total Cost ($USD)
$122,656,404
Allocated Cost ($USD)
$1,435,640
Time Estimate
81 Months

Contributor

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.7 MW5.1%$6,270,835
AG2-418
14.0 MW8.2%$10,085,515
AG2-456
8.0 MW4.7%$5,741,839
AG2-457
8.0 MW4.7%$5,741,839
AH1-050
2.8 MW1.6%$2,002,833
AH1-051
1.7 MW1.0%$1,202,132
AH1-102
6.9 MW4.0%$4,938,255
AH1-158
1.9 MW1.1%$1,397,443
AH1-203
6.5 MW3.8%$4,704,748
AH1-268
2.9 MW1.7%$2,101,569
AH1-313
26.0 MW15.3%$18,769,262
AH1-357
2.0 MW1.2%$1,435,640
AH1-358
2.3 MW1.4%$1,669,148
AH1-359
2.0 MW1.2%$1,435,640
AH1-360
2.3 MW1.4%$1,669,148
AH1-460
6.4 MW3.8%$4,608,894
AH1-587
24.2 MW14.2%$17,466,952
AH1-588
23.9 MW14.0%$17,226,238
AH1-589
19.7 MW11.6%$14,188,475

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.c
Title
Reconductor Shingletown - Lewistown 230kV line including T-line drop at Shingletown
Description
Reconductor (Possible Rebuild) ~14.4 miles of Shingletown - Lewistown 230kV line [APS Side] including T-line drop at Shingletown This project has a pre-req of TC2-APS-034.b
Total Cost ($USD)
$73,419,183
Allocated Cost ($USD)
$1,050,141
Time Estimate
55 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$3,986,293
AG2-456
7.9 MW5.7%$4,200,034
AG2-457
7.9 MW5.7%$4,200,034
AH1-313
32.3 MW23.3%$17,115,709
AH1-357
2.0 MW1.4%$1,050,141
AH1-358
2.3 MW1.7%$1,220,922
AH1-359
2.0 MW1.4%$1,050,141
AH1-360
2.3 MW1.7%$1,220,922
AH1-587
25.6 MW18.5%$13,561,671
AH1-588
23.8 MW17.2%$12,600,102
AH1-589
19.6 MW14.1%$10,378,364
AH1-720
5.3 MW3.9%$2,834,851

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-PN-002.a
Title
Reconductor Shingletown - Lewistown 230kV line [PN Side]
Description
Reconductor (Possible Rebuild) ~11.7 miles of Shingletown - Lewistown 230kV line [PN Side]
Total Cost ($USD)
$58,911,069
Allocated Cost ($USD)
$842,626
Time Estimate
49 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$3,198,575
AG2-456
7.9 MW5.7%$3,370,080
AG2-457
7.9 MW5.7%$3,370,080
AH1-313
32.3 MW23.3%$13,733,532
AH1-357
2.0 MW1.4%$842,626
AH1-358
2.3 MW1.7%$979,659
AH1-359
2.0 MW1.4%$842,626
AH1-360
2.3 MW1.7%$979,659
AH1-587
25.6 MW18.5%$10,881,795
AH1-588
23.8 MW17.2%$10,110,239
AH1-589
19.6 MW14.1%$8,327,531
AH1-720
5.3 MW3.9%$2,274,665

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-PH1-076
Title
Reconductor Butler - Karns City 138 kV line.
Description
Reconductor (Possible Rebuild) ~15.6 miles on the Butler - Karns City 138 kV line.
Total Cost ($USD)
$51,840,579
Allocated Cost ($USD)
$633,235
Time Estimate
30 Months

Contributor

FacilityContingency
01BUTLER-01KARNSC 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
13.1 MW12.9%$6,681,371
AG2-429
12.5 MW12.3%$6,391,032
AG2-456
5.0 MW4.9%$2,532,941
AG2-457
5.0 MW4.9%$2,532,941
AH1-050
4.7 MW4.6%$2,406,396
AH1-051
2.8 MW2.8%$1,444,041
AH1-102
3.6 MW3.5%$1,818,574
AH1-158
3.3 MW3.2%$1,678,762
AH1-268
1.5 MW1.5%$774,067
AH1-313
5.2 MW5.1%$2,646,729
AH1-357
1.2 MW1.2%$633,235
AH1-358
1.4 MW1.4%$736,308
AH1-359
1.2 MW1.2%$633,235
AH1-360
1.4 MW1.4%$736,308
AH1-587
12.4 MW12.2%$6,337,964
AH1-588
14.9 MW14.7%$7,598,312
AH1-589
12.3 MW12.1%$6,258,364

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-APS-002.d
Title
Rebuild 11.6 miles of 556.5 ACSR of the Armstrong - Kittanning 138 kV line
Description
Rebuild 11.6 miles of 556.5 ACSR of the Armstrong - Kittanning 138 kV line using 795.0 KCMIL 26/7 STR ACSR. This upgrade is scoped and estimated as a line rebuild. During the network upgrade facility study process, FirstEnergy will make a final determination on whether a full rebuild is required or if only a reconductor is required.
Total Cost ($USD)
$37,921,495
Allocated Cost ($USD)
$587,195
Time Estimate
28 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$4,768,689
AG2-429
7.4 MW9.8%$3,716,379
AG2-456
4.7 MW6.2%$2,347,771
AG2-457
4.7 MW6.2%$2,347,771
AH1-050
3.0 MW4.0%$1,506,831
AH1-051
1.8 MW2.4%$903,998
AH1-158
2.1 MW2.8%$1,051,301
AH1-357
1.2 MW1.5%$587,195
AH1-358
1.4 MW1.8%$682,538
AH1-359
1.2 MW1.5%$587,195
AH1-360
1.4 MW1.8%$682,538
AH1-587
11.7 MW15.5%$5,893,642
AH1-588
14.0 MW18.6%$7,043,817
AH1-589
11.5 MW15.3%$5,801,829

System Reinforcement: n6183
Type
Load Flow
TO
APS
RTEP ID / TO ID
n6183
Title
Rebuild 10.4 miles of 4/0 CU from Columbia Big Pine - Garretts Run Jct 138 kV (99 spans).
Description
Rebuild 10.4 miles of 4/0 CU from Columbia Big Pine - Garretts Run Jct 138 kV (99 spans) using 954 kcmil 45/7 STR ACSR.
Total Cost ($USD)
$36,946,687
Allocated Cost ($USD)
$577,285
Time Estimate
26 Months

Contributor

FacilityContingency
01COLMBGPN-01GAR RN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.1 MW11.2%$4,121,135
AG2-429
9.3 MW11.4%$4,194,031
AG2-456
5.1 MW6.2%$2,308,687
AG2-457
5.1 MW6.2%$2,308,687
AH1-050
3.0 MW3.7%$1,375,976
AH1-051
1.8 MW2.2%$825,404
AH1-158
2.6 MW3.2%$1,178,114
AH1-357
1.3 MW1.6%$577,285
AH1-358
1.5 MW1.8%$671,009
AH1-359
1.3 MW1.6%$577,285
AH1-360
1.5 MW1.8%$671,009
AH1-587
12.2 MW14.9%$5,506,619
AH1-588
15.3 MW18.7%$6,926,513
AH1-589
12.6 MW15.4%$5,704,933

System Reinforcement: n8229
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8229
Title
Reconductor 18.7 miles the AE2-113 (Farmers Valley) - Ridgway 115 kV Line
Description
Total Cost ($USD)
$62,172,697
Allocated Cost ($USD)
$546,741
Time Estimate
32 Months

Contributor

FacilityContingency
26RIDGWAY-AE2-113_TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
10.1 MW3.5%$2,186,533
AG2-457
10.1 MW3.5%$2,186,533
AH1-357
2.5 MW0.9%$546,741
AH1-358
3.1 MW1.1%$659,763
AH1-359
2.5 MW0.9%$546,741
AH1-360
3.1 MW1.1%$659,763
AH1-587
200.0 MW69.5%$43,218,927
AH1-588
30.4 MW10.6%$6,559,599
AH1-589
26.0 MW9.0%$5,608,096

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-010
Title
Reconductor FE owned 4.3 miles of Laurel Lake - Goudey (Oakdale) 115 kV Line
Description
Reconductor FE owned part of line with 1272 ACSR 45/7. NYSEG will need to upgrade their portion of the line to achieve the higher line ratings, which will be confirmed once the NYSEG upgrades are confirm. The new FirstEnergy ratings for their section of line are: Summer: 274/344/396 MVA SN/SE/SLD Winter: 360/413/452 MVA WN/WE/WLD
Total Cost ($USD)
$16,174,322
Allocated Cost ($USD)
$472,938
Time Estimate
20 Months

Contributor

FacilityContingency
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
2.3 MW11.7%$1,890,925
AG2-457
2.3 MW11.7%$1,890,925
AH1-357
0.6 MW2.9%$472,938
AH1-358
0.7 MW3.4%$549,967
AH1-359
0.6 MW2.9%$472,938
AH1-360
0.7 MW3.4%$549,967
AH1-588
6.8 MW35.1%$5,673,602
AH1-589
5.6 MW28.9%$4,673,060

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-017
Title
Reconductor (Possible Rebuild) ~5.9 miles of Elko - Carbon Center Jct 138 kV transmission line including (2) T-Line Drops at Elko
Description
Reconductor (Possible Rebuild) ~5.9 miles of Elko - Carbon Center Jct 138 kV transmission line including (2) T-Line Drops at Elko
Total Cost ($USD)
$20,614,554
Allocated Cost ($USD)
$442,274
Time Estimate
21 Months

Contributor

FacilityContingency
01CARB J-01ELKO 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
4.1 MW8.6%$1,768,665
AG2-457
4.1 MW8.6%$1,768,665
AH1-357
1.0 MW2.1%$442,274
AH1-358
1.2 MW2.5%$513,971
AH1-359
1.0 MW2.1%$442,274
AH1-360
1.2 MW2.5%$513,971
AH1-587
12.7 MW26.6%$5,488,260
AH1-588
12.3 MW25.7%$5,305,994
AH1-589
10.1 MW21.2%$4,370,481

System Reinforcement: n7166.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7166.2
Title
Reconductor 7.6 miles of 4/0 CU from All Dam 6 Tap to structure 84 (66 spans)
Description
Total Cost ($USD)
$26,284,067
Allocated Cost ($USD)
$370,503
Time Estimate
23 Months

Contributor

FacilityContingency
01AL 4J-01AL&D6T 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.1 MW11.8%$3,107,204
AG2-429
10.0 MW14.6%$3,841,262
AG2-456
3.8 MW5.6%$1,481,624
AG2-457
3.8 MW5.6%$1,481,624
AH1-050
3.1 MW4.5%$1,179,433
AH1-051
1.8 MW2.7%$707,428
AH1-158
2.6 MW3.8%$1,004,602
AH1-357
1.0 MW1.4%$370,503
AH1-358
1.1 MW1.6%$430,709
AH1-359
1.0 MW1.4%$370,503
AH1-360
1.1 MW1.6%$430,709
AH1-587
9.8 MW14.4%$3,772,565
AH1-588
11.5 MW16.9%$4,444,873
AH1-589
9.5 MW13.9%$3,661,028

System Reinforcement: n8281
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8281
Title
Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker
Description
Replace the #4 500/230 kV transformer with a larger unit and install a high side breaker. Install a 230-20 kV transformer and high side breaker to serve load currently fed from existing transformer tertiary. Estimated Summer Ratings: 910/1086/1141 MVA
Total Cost ($USD)
$31,322,503
Allocated Cost ($USD)
$359,401
Time Estimate
67 Months

Contributor

FacilityContingency
KEYSTONE-KEYSTONE _3 500.0/230.0 kV Ckt 4 transformer(Any)
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
24.1 MW5.9%$1,841,952
AG2-411
20.6 MW5.0%$1,572,439
AG2-429
14.0 MW3.4%$1,071,784
AG2-456
18.8 MW4.6%$1,437,300
AG2-457
18.8 MW4.6%$1,437,300
AH1-050
7.3 MW1.8%$559,511
AH1-051
4.4 MW1.1%$335,706
AH1-102
25.5 MW6.2%$1,948,656
AH1-140
20.1 MW4.9%$1,537,125
AH1-158
5.1 MW1.2%$390,434
AH1-201
9.5 MW2.3%$724,153
AH1-203
20.7 MW5.1%$1,583,446
AH1-205
4.4 MW1.1%$336,776
AH1-268
10.8 MW2.6%$829,329
AH1-313
16.2 MW4.0%$1,237,650
AH1-357
4.7 MW1.1%$359,401
AH1-358
5.5 MW1.3%$417,798
AH1-359
4.7 MW1.1%$359,401
AH1-360
5.5 MW1.3%$417,798
AH1-460
21.5 MW5.3%$1,644,441
AH1-587
44.7 MW10.9%$3,416,378
AH1-588
56.4 MW13.8%$4,312,053
AH1-589
46.5 MW11.3%$3,551,669

System Reinforcement: n7164.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7164.1
Title
Reconductor (Possible Rebuild) ~7.5 miles of the Karns City to Kissinger Jct 138kV line
Description
Reconductor (Possible Rebuild) ~7.5 miles of the Karns City to Kissinger Jct 138kV line This project is a pre-req for TC2-APS-031.a.
Total Cost ($USD)
$26,275,973
Allocated Cost ($USD)
$321,067
Time Estimate
23 Months

Contributor

FacilityContingency
01KARNSC-01KISSNG 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
13.8 MW12.9%$3,384,815
AG2-429
13.2 MW12.3%$3,236,913
AG2-456
5.2 MW4.9%$1,284,022
AG2-457
5.2 MW4.9%$1,284,022
AH1-050
5.0 MW4.6%$1,219,269
AH1-051
3.0 MW2.8%$731,414
AH1-102
3.8 MW3.5%$923,466
AH1-158
3.5 MW3.2%$850,619
AH1-268
1.6 MW1.5%$392,933
AH1-313
5.5 MW5.1%$1,342,153
AH1-357
1.3 MW1.2%$321,067
AH1-358
1.5 MW1.4%$373,311
AH1-359
1.3 MW1.2%$321,067
AH1-360
1.5 MW1.4%$373,311
AH1-587
13.1 MW12.2%$3,212,631
AH1-588
15.7 MW14.7%$3,852,066
AH1-589
12.9 MW12.1%$3,172,896

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-011
Title
Replace 500/230 kV Conemaugh #3 Transformer
Description
Replace 500/230 kV Conemaugh #3 Transformer
Total Cost ($USD)
$28,558,871
Allocated Cost ($USD)
$312,274
Time Estimate
66 Months

Contributor

FacilityContingency
CONEM-GH-26CONEMAGH 500.0/230.0 kV Ckt 3 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
16.5 MW5.8%$1,644,796
AG2-411
17.1 MW6.0%$1,706,593
AG2-456
12.5 MW4.4%$1,248,996
AG2-457
12.5 MW4.4%$1,248,996
AH1-050
5.0 MW1.8%$502,748
AH1-051
3.0 MW1.1%$301,709
AH1-102
21.4 MW7.5%$2,135,683
AH1-140
13.8 MW4.8%$1,379,567
AH1-158
3.5 MW1.2%$350,748
AH1-201
8.0 MW2.8%$801,866
AH1-203
17.5 MW6.1%$1,748,356
AH1-205
3.7 MW1.3%$372,975
AH1-268
9.1 MW3.2%$908,914
AH1-313
11.9 MW4.1%$1,183,213
AH1-357
3.1 MW1.1%$312,274
AH1-358
3.6 MW1.3%$363,107
AH1-359
3.1 MW1.1%$312,274
AH1-360
3.6 MW1.3%$363,107
AH1-460
18.3 MW6.4%$1,826,300
AH1-587
30.2 MW10.6%$3,013,300
AH1-588
37.6 MW13.1%$3,747,089
AH1-589
31.0 MW10.8%$3,086,260

System Reinforcement: n7165.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7165.2
Title
Reconductor All Dam 6 - Kittanning 138kV line
Description
Reconductor (Possible Rebuild) ~6 miles of the All Dam 6 - Kittanning 138kV line
Total Cost ($USD)
$21,034,523
Allocated Cost ($USD)
$296,465
Time Estimate
22 Months

Contributor

FacilityContingency
01AL&D6T-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.1 MW11.8%$2,486,603
AG2-429
10.0 MW14.6%$3,073,666
AG2-456
3.8 MW5.6%$1,185,861
AG2-457
3.8 MW5.6%$1,185,861
AH1-050
3.1 MW4.5%$943,748
AH1-051
1.8 MW2.7%$566,372
AH1-158
2.6 MW3.8%$803,853
AH1-357
1.0 MW1.4%$296,465
AH1-358
1.1 MW1.6%$344,641
AH1-359
1.0 MW1.4%$296,465
AH1-360
1.1 MW1.6%$344,641
AH1-587
9.8 MW14.4%$3,019,314
AH1-588
11.5 MW16.9%$3,557,275
AH1-589
9.5 MW13.9%$2,929,757

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.b
Title
Upgrade 345/138 kV #2 Transformer at Armstrong
Description
Upgrade 345/138 kV #2 Transformer at Armstrong
Total Cost ($USD)
$13,326,308
Allocated Cost ($USD)
$244,210
Time Estimate
65 Months

Contributor

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
20.8 MW12.4%$1,651,452
AG2-206
5.7 MW3.4%$453,783
AG2-220
3.7 MW2.2%$295,018
AG2-221
2.5 MW1.5%$194,512
AG2-327
1.2 MW0.7%$94,561
AG2-356
2.5 MW1.5%$194,512
AG2-456
12.3 MW7.3%$976,683
AG2-457
12.3 MW7.3%$976,683
AH1-005
2.4 MW1.4%$190,311
AH1-357
3.1 MW1.8%$244,210
AH1-358
3.6 MW2.1%$283,921
AH1-359
3.1 MW1.8%$244,210
AH1-360
3.6 MW2.1%$283,921
AH1-587
24.0 MW14.2%$1,898,991
AH1-588
37.0 MW22.0%$2,930,128
AH1-589
30.4 MW18.1%$2,413,410

System Reinforcement: n7171.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7171.1
Title
Rebuild approximately 4.0 miles of 4/0 CU on the Kiski Valley to Columbia Big Pine 138kV line.
Description
Rebuild approximately 4.0 miles of 4/0 CU on the Kiski Valley to Columbia Big Pine 138kV line using 954 KCMIL 45/7 STR ACSR.
Total Cost ($USD)
$15,258,720
Allocated Cost ($USD)
$238,415
Time Estimate
20 Months

Contributor

FacilityContingency
01KISKIV-01COLMBGPN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.1 MW11.2%$1,702,000
AG2-429
9.3 MW11.4%$1,732,105
AG2-456
5.1 MW6.2%$953,471
AG2-457
5.1 MW6.2%$953,471
AH1-050
3.0 MW3.7%$568,268
AH1-051
1.8 MW2.2%$340,886
AH1-158
2.6 MW3.2%$486,553
AH1-357
1.3 MW1.6%$238,415
AH1-358
1.5 MW1.8%$277,122
AH1-359
1.3 MW1.6%$238,415
AH1-360
1.5 MW1.8%$277,122
AH1-587
12.2 MW14.9%$2,274,195
AH1-588
15.3 MW18.7%$2,860,601
AH1-589
12.6 MW15.4%$2,356,097

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-PH1-066
Title
Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.
Description
Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.
Total Cost ($USD)
$18,224,602
Allocated Cost ($USD)
$226,012
Time Estimate
20 Months

Contributor

FacilityContingency
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
5.9 MW8.4%$1,534,022
AG2-456
3.5 MW5.0%$904,307
AG2-457
3.5 MW5.0%$904,307
AH1-102
9.5 MW13.5%$2,468,724
AH1-203
6.0 MW8.6%$1,561,819
AH1-268
4.0 MW5.8%$1,050,565
AH1-357
0.9 MW1.2%$226,012
AH1-358
1.0 MW1.4%$262,901
AH1-359
0.9 MW1.2%$226,012
AH1-360
1.0 MW1.4%$262,901
AH1-460
6.3 MW9.0%$1,632,480
AH1-587
8.6 MW12.3%$2,243,751
AH1-588
10.4 MW14.9%$2,712,661
AH1-589
8.6 MW12.3%$2,234,139

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-009
Title
Reconductor 6.2 miles of 115 kV Line between AH1-587 and AE2-113
Description
Total Cost ($USD)
$21,700,478
Allocated Cost ($USD)
$191,085
Time Estimate
22 Months

Contributor

FacilityContingency
AE2-113_TAP-AH1-587 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
10.1 MW3.5%$764,264
AG2-457
10.1 MW3.5%$764,264
AH1-357
2.5 MW0.9%$191,085
AH1-358
3.1 MW1.1%$231,170
AH1-359
2.5 MW0.9%$191,085
AH1-360
3.1 MW1.1%$231,170
AH1-587
200.0 MW69.4%$15,069,776
AH1-588
30.4 MW10.6%$2,292,866
AH1-589
26.1 MW9.1%$1,964,797

System Reinforcement: n6818
Type
Load Flow
TO
PPL
RTEP ID / TO ID
n6818
Title
Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.
Description
The FE portion of the line is rated at 546/666 MVA SN/SE. The PPL portion is limiting, which requires n6818. Reinforcement scope no longer includes any substation scope as Juniata 230kV substation is being rebuilt under S0945.1. Actual PPL facility ratings after upgrade: 1245/1431 MVA SN/SE (FE facilities are more limiting)
Total Cost ($USD)
$3,600,000
Allocated Cost ($USD)
$42,136
Time Estimate
24 Months

Contributor

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.7 MW5.1%$184,051
AG2-418
14.0 MW8.2%$296,013
AG2-456
8.0 MW4.7%$168,525
AG2-457
8.0 MW4.7%$168,525
AH1-050
2.8 MW1.6%$58,784
AH1-051
1.7 MW1.0%$35,283
AH1-102
6.9 MW4.0%$144,939
AH1-158
1.9 MW1.1%$41,015
AH1-203
6.5 MW3.8%$138,086
AH1-268
2.9 MW1.7%$61,682
AH1-313
26.0 MW15.3%$550,883
AH1-357
2.0 MW1.2%$42,136
AH1-358
2.3 MW1.4%$48,990
AH1-359
2.0 MW1.2%$42,136
AH1-360
2.3 MW1.4%$48,990
AH1-460
6.4 MW3.8%$135,272
AH1-587
24.2 MW14.2%$512,660
AH1-588
23.9 MW14.0%$505,595
AH1-589
19.7 MW11.6%$416,436

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.i
Title
Replace Circuit Breaker at Shingletown
Description
Replace (1) 230 kV Circuit Breaker at Shingletown This project has a pre-req of TC2-APS-034.h
Total Cost ($USD)
$1,621,562
Allocated Cost ($USD)
$23,194
Time Estimate
45 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$88,043
AG2-456
7.9 MW5.7%$92,763
AG2-457
7.9 MW5.7%$92,763
AH1-313
32.3 MW23.3%$378,024
AH1-357
2.0 MW1.4%$23,194
AH1-358
2.3 MW1.7%$26,966
AH1-359
2.0 MW1.4%$23,194
AH1-360
2.3 MW1.7%$26,966
AH1-587
25.6 MW18.5%$299,528
AH1-588
23.8 MW17.2%$278,290
AH1-589
19.6 MW14.1%$229,220
AH1-720
5.3 MW3.9%$62,612

System Reinforcement: n9118.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9118.0 / TC1-PN-001.g
Title
Replace disconnect switches and leads at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-003.g (Keystone-Shelocta 230kV line terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$22,384
Time Estimate
26 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$110,525
AG2-411
17.6 MW5.5%$98,262
AG2-429
10.7 MW3.4%$59,973
AG2-456
16.0 MW5.0%$89,540
AG2-457
16.0 MW5.0%$89,540
AH1-050
5.4 MW1.7%$30,177
AH1-051
3.2 MW1.0%$18,109
AH1-102
16.1 MW5.0%$89,932
AH1-158
3.8 MW1.2%$21,058
AH1-201
8.1 MW2.5%$45,277
AH1-203
17.7 MW5.5%$98,945
AH1-205
3.8 MW1.2%$21,058
AH1-268
6.8 MW2.1%$38,272
AH1-313
13.0 MW4.1%$72,824
AH1-357
4.0 MW1.3%$22,384
AH1-358
4.7 MW1.5%$26,026
AH1-359
4.0 MW1.3%$22,384
AH1-360
4.7 MW1.5%$26,026
AH1-460
18.5 MW5.8%$103,342
AH1-587
37.5 MW11.8%$209,834
AH1-588
48.0 MW15.1%$268,616
AH1-589
39.5 MW12.4%$221,241

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.e
Title
Replace Current Transformers at Shingletown
Description
Replace (3) 1200 Amp 230 kV Current Transformers at Shingletown This project has a pre-req of TC2-APS-034.d
Total Cost ($USD)
$1,563,362
Allocated Cost ($USD)
$22,361
Time Estimate
22 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$84,883
AG2-456
7.9 MW5.7%$89,434
AG2-457
7.9 MW5.7%$89,434
AH1-313
32.3 MW23.3%$364,456
AH1-357
2.0 MW1.4%$22,361
AH1-358
2.3 MW1.7%$25,998
AH1-359
2.0 MW1.4%$22,361
AH1-360
2.3 MW1.7%$25,998
AH1-587
25.6 MW18.5%$288,777
AH1-588
23.8 MW17.2%$268,302
AH1-589
19.6 MW14.1%$220,993
AH1-720
5.3 MW3.9%$60,364

System Reinforcement: n8096
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8096
Title
Install an additional 230kV circuit breaker between the East Towanda 230kV line terminal and the North Meshoppen 230/115kV #4 transformer.
Description
None
Total Cost ($USD)
$1,621,562
Allocated Cost ($USD)
$20,920
Time Estimate
45 Months

Contributor

FacilityContingency
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN-P2-3-PN-230-17B25
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN-P2_1-PN-230-997-DRT-067
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN-P2_1-PN-230-997-DRT-067
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN-P2_1-PN-230-997-DRT-067
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN_P2-3_PN-230-17B25_SRT-A
26NO MESHO-26N.MESHPN 115.0/230.0 kV Ckt 3 transformerPN_P2-3_PN-230-997-DRT-067_SRT-SL
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-206
9.2 MW9.4%$152,449
AG2-220
5.9 MW6.0%$97,969
AG2-221
3.5 MW3.6%$58,378
AG2-327
1.9 MW2.0%$31,762
AG2-356
3.5 MW3.6%$58,378
AG2-456
5.0 MW5.2%$83,645
AG2-457
5.0 MW5.2%$83,645
AH1-005
3.8 MW3.9%$63,208
AH1-357
1.3 MW1.3%$20,920
AH1-358
1.5 MW1.5%$24,317
AH1-359
1.3 MW1.3%$20,920
AH1-360
1.5 MW1.5%$24,317
AH1-587
12.4 MW12.8%$207,280
AH1-588
15.1 MW15.5%$250,951
AH1-589
12.4 MW12.7%$206,697
AH1-720
14.2 MW14.6%$236,727

System Reinforcement: n6855.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6855.1
Title
Replace substation conductor at Warren substation
Description
Still required to support the line reconductor for the higher facility rating above 546/666/753 MVA SN/SE/SLD.
Total Cost ($USD)
$796,717
Allocated Cost ($USD)
$20,225
Time Estimate
22 Months

Contributor

FacilityContingency
26GLADE-26WARREN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
34.8 MW10.2%$80,901
AG2-457
34.8 MW10.2%$80,901
AH1-313
12.2 MW3.6%$28,290
AH1-357
8.7 MW2.5%$20,225
AH1-358
10.1 MW3.0%$23,518
AH1-359
8.7 MW2.5%$20,225
AH1-360
10.1 MW3.0%$23,518
AH1-587
32.9 MW9.6%$76,533
AH1-588
104.3 MW30.5%$242,704
AH1-589
85.9 MW25.1%$199,902

System Reinforcement: n9127.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9127.0 / TC1-PN-003.g
Title
Replace disconnect switches and leads at Shelocta Substation (Keystone-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-001.g (Homer City-Shelocta 230kV line) terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$19,932
Time Estimate
26 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$103,254
AG2-411
19.1 MW5.2%$93,548
AG2-429
12.3 MW3.4%$60,324
AG2-456
16.3 MW4.5%$79,716
AG2-457
16.3 MW4.5%$79,716
AH1-050
6.4 MW1.8%$31,460
AH1-051
3.9 MW1.1%$18,878
AH1-102
23.7 MW6.5%$116,272
AH1-140
17.9 MW4.9%$87,654
AH1-158
4.5 MW1.2%$21,950
AH1-201
8.9 MW2.4%$43,435
AH1-203
19.4 MW5.3%$94,856
AH1-205
4.1 MW1.1%$20,201
AH1-268
10.1 MW2.8%$49,481
AH1-313
14.5 MW4.0%$71,054
AH1-357
4.1 MW1.1%$19,932
AH1-358
4.7 MW1.3%$23,175
AH1-359
4.1 MW1.1%$19,932
AH1-360
4.7 MW1.3%$23,175
AH1-460
20.2 MW5.5%$98,741
AH1-587
38.9 MW10.7%$190,471
AH1-588
48.8 MW13.4%$239,149
AH1-589
40.2 MW11.0%$196,973

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.a
Title
Upgrade/Replace (6) 138kV Substation Conductors [(2) ACSR 954 45/7 & (4) AAC 1000 37]
Description
Upgrade/Replace (6) 138kV Substation Conductors [(2) ACSR 954 45/7 & (4) AAC 1000 37]
Total Cost ($USD)
$1,084,903
Allocated Cost ($USD)
$19,881
Time Estimate
15 Months

Contributor

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
20.8 MW12.4%$134,446
AG2-206
5.7 MW3.4%$36,943
AG2-220
3.7 MW2.2%$24,018
AG2-221
2.5 MW1.5%$15,835
AG2-327
1.2 MW0.7%$7,698
AG2-356
2.5 MW1.5%$15,835
AG2-456
12.3 MW7.3%$79,512
AG2-457
12.3 MW7.3%$79,512
AH1-005
2.4 MW1.4%$15,493
AH1-357
3.1 MW1.8%$19,881
AH1-358
3.6 MW2.1%$23,114
AH1-359
3.1 MW1.8%$19,881
AH1-360
3.6 MW2.1%$23,114
AH1-587
24.0 MW14.2%$154,598
AH1-588
37.0 MW22.0%$238,544
AH1-589
30.4 MW18.1%$196,477

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-026.a
Title
Replace (4) 10 Amp Meters & (3) 10 Amp Relays at Kittanning
Description
Replace (4) 10 Amp Meters & (3) 10 Amp Relays at Kittanning
Total Cost ($USD)
$1,254,982
Allocated Cost ($USD)
$19,433
Time Estimate
20 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$157,816
AG2-429
7.4 MW9.8%$122,991
AG2-456
4.7 MW6.2%$77,698
AG2-457
4.7 MW6.2%$77,698
AH1-050
3.0 MW4.0%$49,867
AH1-051
1.8 MW2.4%$29,917
AH1-158
2.1 MW2.8%$34,792
AH1-357
1.2 MW1.5%$19,433
AH1-358
1.4 MW1.8%$22,588
AH1-359
1.2 MW1.5%$19,433
AH1-360
1.4 MW1.8%$22,588
AH1-587
11.7 MW15.5%$195,045
AH1-588
14.0 MW18.6%$233,110
AH1-589
11.5 MW15.3%$192,007

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-003.c
Title
Replace substation conductor at Glade substation
Description
Total Cost ($USD)
$752,332
Allocated Cost ($USD)
$19,098
Time Estimate
13 Months

Contributor

FacilityContingency
26GLADE-26WARREN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
34.8 MW10.2%$76,394
AG2-457
34.8 MW10.2%$76,394
AH1-313
12.2 MW3.6%$26,714
AH1-357
8.7 MW2.5%$19,098
AH1-358
10.1 MW3.0%$22,207
AH1-359
8.7 MW2.5%$19,098
AH1-360
10.1 MW3.0%$22,207
AH1-587
32.9 MW9.6%$72,270
AH1-588
104.3 MW30.5%$229,183
AH1-589
85.9 MW25.1%$188,765

System Reinforcement: n9117.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9117.0 / TC1-PN-001.f
Title
Replace disconnect switches at Homer City Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$1,254,760
Allocated Cost ($USD)
$15,749
Time Estimate
24 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$77,766
AG2-411
17.6 MW5.5%$69,137
AG2-429
10.7 MW3.4%$42,197
AG2-456
16.0 MW5.0%$63,001
AG2-457
16.0 MW5.0%$63,001
AH1-050
5.4 MW1.7%$21,232
AH1-051
3.2 MW1.0%$12,742
AH1-102
16.1 MW5.0%$63,276
AH1-158
3.8 MW1.2%$14,816
AH1-201
8.1 MW2.5%$31,857
AH1-203
17.7 MW5.5%$69,617
AH1-205
3.8 MW1.2%$14,816
AH1-268
6.8 MW2.1%$26,928
AH1-313
13.0 MW4.1%$51,239
AH1-357
4.0 MW1.3%$15,749
AH1-358
4.7 MW1.5%$18,312
AH1-359
4.0 MW1.3%$15,749
AH1-360
4.7 MW1.5%$18,312
AH1-460
18.5 MW5.8%$72,711
AH1-587
37.5 MW11.8%$147,639
AH1-588
48.0 MW15.1%$188,998
AH1-589
39.5 MW12.4%$155,665

System Reinforcement: n9125.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9125.0 / TC1-PN-003.f
Title
Replace disconnect switches at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,254,762
Allocated Cost ($USD)
$14,024
Time Estimate
24 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$72,649
AG2-411
19.1 MW5.2%$65,820
AG2-429
12.3 MW3.4%$42,444
AG2-456
16.3 MW4.5%$56,088
AG2-457
16.3 MW4.5%$56,088
AH1-050
6.4 MW1.8%$22,135
AH1-051
3.9 MW1.1%$13,283
AH1-102
23.7 MW6.5%$81,809
AH1-140
17.9 MW4.9%$61,673
AH1-158
4.5 MW1.2%$15,444
AH1-201
8.9 MW2.4%$30,561
AH1-203
19.4 MW5.3%$66,741
AH1-205
4.1 MW1.1%$14,213
AH1-268
10.1 MW2.8%$34,815
AH1-313
14.5 MW4.0%$49,993
AH1-357
4.1 MW1.1%$14,024
AH1-358
4.7 MW1.3%$16,306
AH1-359
4.1 MW1.1%$14,024
AH1-360
4.7 MW1.3%$16,306
AH1-460
20.2 MW5.5%$69,474
AH1-587
38.9 MW10.7%$134,016
AH1-588
48.8 MW13.4%$168,265
AH1-589
40.2 MW11.0%$138,590

System Reinforcement: n7166.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7166.1
Title
Replace 4/0 CU line exit at All Dam 6 Tap.
Description
Replace 4/0 CU line exit at All Dam 6 Tap on the 01AL&D6T - 01AL 4J
Total Cost ($USD)
$922,908
Allocated Cost ($USD)
$13,009
Time Estimate
18 Months

Contributor

FacilityContingency
01AL 4J-01AL&D6T 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.1 MW11.8%$109,103
AG2-429
10.0 MW14.6%$134,878
AG2-456
3.8 MW5.6%$52,024
AG2-457
3.8 MW5.6%$52,024
AH1-050
3.1 MW4.5%$41,413
AH1-051
1.8 MW2.7%$24,840
AH1-158
2.6 MW3.8%$35,274
AH1-357
1.0 MW1.4%$13,009
AH1-358
1.1 MW1.6%$15,123
AH1-359
1.0 MW1.4%$13,009
AH1-360
1.1 MW1.6%$15,123
AH1-587
9.8 MW14.4%$132,465
AH1-588
11.5 MW16.9%$156,072
AH1-589
9.5 MW13.9%$128,549

System Reinforcement: n9124.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9124.0 / TC1-PN-003.e
Title
Replace bus conductor at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,104,686
Allocated Cost ($USD)
$12,346
Time Estimate
13 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$63,960
AG2-411
19.1 MW5.2%$57,948
AG2-429
12.3 MW3.4%$37,367
AG2-456
16.3 MW4.5%$49,380
AG2-457
16.3 MW4.5%$49,380
AH1-050
6.4 MW1.8%$19,488
AH1-051
3.9 MW1.1%$11,694
AH1-102
23.7 MW6.5%$72,024
AH1-140
17.9 MW4.9%$54,297
AH1-158
4.5 MW1.2%$13,597
AH1-201
8.9 MW2.4%$26,906
AH1-203
19.4 MW5.3%$58,758
AH1-205
4.1 MW1.1%$12,513
AH1-268
10.1 MW2.8%$30,651
AH1-313
14.5 MW4.0%$44,014
AH1-357
4.1 MW1.1%$12,346
AH1-358
4.7 MW1.3%$14,356
AH1-359
4.1 MW1.1%$12,346
AH1-360
4.7 MW1.3%$14,356
AH1-460
20.2 MW5.5%$61,165
AH1-587
38.9 MW10.7%$117,987
AH1-588
48.8 MW13.4%$148,140
AH1-589
40.2 MW11.0%$122,014

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-001.a
Title
Replace 230 kV bus conductor at Shawville
Description
Replace 230 kV bus conductor at Shawville
Total Cost ($USD)
$696,930
Allocated Cost ($USD)
$11,410
Time Estimate
13 Months

Contributor

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
6.2 MW6.5%$45,647
AG2-457
6.2 MW6.5%$45,647
AH1-313
20.9 MW22.1%$154,251
AH1-357
1.5 MW1.6%$11,410
AH1-358
1.8 MW1.9%$13,273
AH1-359
1.5 MW1.6%$11,410
AH1-360
1.8 MW1.9%$13,273
AH1-587
20.6 MW21.8%$152,276
AH1-588
18.5 MW19.7%$136,947
AH1-589
15.3 MW16.2%$112,797

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.a
Title
Replace Sub conductor at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$869,783
Allocated Cost ($USD)
$10,917
Time Estimate
13 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$53,906
AG2-411
17.6 MW5.5%$47,925
AG2-429
10.7 MW3.4%$29,251
AG2-456
16.0 MW5.0%$43,671
AG2-457
16.0 MW5.0%$43,671
AH1-050
5.4 MW1.7%$14,718
AH1-051
3.2 MW1.0%$8,832
AH1-102
16.1 MW5.0%$43,862
AH1-158
3.8 MW1.2%$10,270
AH1-201
8.1 MW2.5%$22,083
AH1-203
17.7 MW5.5%$48,258
AH1-205
3.8 MW1.2%$10,270
AH1-268
6.8 MW2.1%$18,666
AH1-313
13.0 MW4.1%$35,518
AH1-357
4.0 MW1.3%$10,917
AH1-358
4.7 MW1.5%$12,693
AH1-359
4.0 MW1.3%$10,917
AH1-360
4.7 MW1.5%$12,693
AH1-460
18.5 MW5.8%$50,403
AH1-587
37.5 MW11.8%$102,341
AH1-588
48.0 MW15.1%$131,011
AH1-589
39.5 MW12.4%$107,905

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.d
Title
Replace Disc Switches at Shingletown
Description
Replace (2) 1200 Amp 230 kV Disc Switches (LWT_BUS & LWT_LINE) at Shingletown This project has a pre-req of TC2-APS-034.c
Total Cost ($USD)
$711,556
Allocated Cost ($USD)
$10,178
Time Estimate
22 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$38,634
AG2-456
7.9 MW5.7%$40,705
AG2-457
7.9 MW5.7%$40,705
AH1-313
32.3 MW23.3%$165,880
AH1-357
2.0 MW1.4%$10,178
AH1-358
2.3 MW1.7%$11,833
AH1-359
2.0 MW1.4%$10,178
AH1-360
2.3 MW1.7%$11,833
AH1-587
25.6 MW18.5%$131,436
AH1-588
23.8 MW17.2%$122,116
AH1-589
19.6 MW14.1%$100,584
AH1-720
5.3 MW3.9%$27,474

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-020.a
Title
Replace Bus Risers at Shingletown substation
Description
Replace (2) Bus Risers at Shingletown substation There is a pre-req for this project TC2-PN-001.a (FE-East Penelec project)
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$9,690
Time Estimate
13 Months

Contributor

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
6.2 MW6.5%$38,765
AG2-457
6.2 MW6.5%$38,765
AH1-313
20.9 MW22.1%$130,996
AH1-357
1.5 MW1.6%$9,690
AH1-358
1.8 MW1.9%$11,272
AH1-359
1.5 MW1.6%$9,690
AH1-360
1.8 MW1.9%$11,272
AH1-587
20.6 MW21.8%$129,320
AH1-588
18.5 MW19.7%$116,302
AH1-589
15.3 MW16.2%$95,792

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.c
Title
Update/Replace 138 kV SEL-311B Relay
Description
Update/Replace 138 kV SEL-311B Relay
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$9,344
Time Estimate
18 Months

Contributor

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
20.8 MW12.4%$63,188
AG2-206
5.7 MW3.4%$17,363
AG2-220
3.7 MW2.2%$11,288
AG2-221
2.5 MW1.5%$7,442
AG2-327
1.2 MW0.7%$3,618
AG2-356
2.5 MW1.5%$7,442
AG2-456
12.3 MW7.3%$37,370
AG2-457
12.3 MW7.3%$37,370
AH1-005
2.4 MW1.4%$7,282
AH1-357
3.1 MW1.8%$9,344
AH1-358
3.6 MW2.1%$10,863
AH1-359
3.1 MW1.8%$9,344
AH1-360
3.6 MW2.1%$10,863
AH1-587
24.0 MW14.2%$72,660
AH1-588
37.0 MW22.0%$112,113
AH1-589
30.4 MW18.1%$92,343

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-APS-002.c
Title
Replace/Upgrade (3) 138 kV T-Line Drops at Armstrong
Description
Upgrade Line drops at Armstrong using 795.0 KCMIL 26/7 STR ACSR
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$9,165
Time Estimate
13 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$74,428
AG2-429
7.4 MW9.8%$58,004
AG2-456
4.7 MW6.2%$36,643
AG2-457
4.7 MW6.2%$36,643
AH1-050
3.0 MW4.0%$23,518
AH1-051
1.8 MW2.4%$14,109
AH1-158
2.1 MW2.8%$16,408
AH1-357
1.2 MW1.5%$9,165
AH1-358
1.4 MW1.8%$10,653
AH1-359
1.2 MW1.5%$9,165
AH1-360
1.4 MW1.8%$10,653
AH1-587
11.7 MW15.5%$91,986
AH1-588
14.0 MW18.6%$109,937
AH1-589
11.5 MW15.3%$90,553

System Reinforcement: n9241.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9241.0 / TC1-APS-002.b
Title
Replace 8 Amp ITH(50FD) relay at Kittanning
Description
Replace 8 Amp ITH(50FD) relay at Kittanning
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$7,895
Time Estimate
18 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$64,120
AG2-429
7.4 MW9.8%$49,971
AG2-456
4.7 MW6.2%$31,568
AG2-457
4.7 MW6.2%$31,568
AH1-050
3.0 MW4.0%$20,261
AH1-051
1.8 MW2.4%$12,155
AH1-158
2.1 MW2.8%$14,136
AH1-357
1.2 MW1.5%$7,895
AH1-358
1.4 MW1.8%$9,177
AH1-359
1.2 MW1.5%$7,895
AH1-360
1.4 MW1.8%$9,177
AH1-587
11.7 MW15.5%$79,246
AH1-588
14.0 MW18.6%$94,712
AH1-589
11.5 MW15.3%$78,012

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.h
Title
Replace/Update SEL-421 Relay at Shingletown
Description
Replace/Update (1) SEL-421 Relay at Shingletown This project has a pre-req of TC2-APS-034.g
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$7,293
Time Estimate
18 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$27,685
AG2-456
7.9 MW5.7%$29,169
AG2-457
7.9 MW5.7%$29,169
AH1-313
32.3 MW23.3%$118,868
AH1-357
2.0 MW1.4%$7,293
AH1-358
2.3 MW1.7%$8,479
AH1-359
2.0 MW1.4%$7,293
AH1-360
2.3 MW1.7%$8,479
AH1-587
25.6 MW18.5%$94,186
AH1-588
23.8 MW17.2%$87,507
AH1-589
19.6 MW14.1%$72,078
AH1-720
5.3 MW3.9%$19,688

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.g
Title
Replace/Update SEL-421 Relay at Shingletown
Description
Replace/Update (1) SEL-421 Relay at Shingletown This project has a pre-req of TC2-APS-034.f
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$7,293
Time Estimate
18 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$27,685
AG2-456
7.9 MW5.7%$29,169
AG2-457
7.9 MW5.7%$29,169
AH1-313
32.3 MW23.3%$118,868
AH1-357
2.0 MW1.4%$7,293
AH1-358
2.3 MW1.7%$8,479
AH1-359
2.0 MW1.4%$7,293
AH1-360
2.3 MW1.7%$8,479
AH1-587
25.6 MW18.5%$94,186
AH1-588
23.8 MW17.2%$87,507
AH1-589
19.6 MW14.1%$72,078
AH1-720
5.3 MW3.9%$19,688

System Reinforcement: n7652
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n7652
Title
Replace line trap at Shawville on the Shawville-Rockton Mountain 115kV line.
Description
Replace line trap at Shawville on the Shawville-Rockton Mountain 115kV line.
Total Cost ($USD)
$364,562
Allocated Cost ($USD)
$7,085
Time Estimate
19 Months

Contributor

FacilityContingency
26ROCKTON-26SHAWVL 1 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
6.2 MW7.8%$28,339
AG2-457
6.2 MW7.8%$28,339
AH1-357
1.6 MW1.9%$7,085
AH1-358
1.8 MW2.3%$8,238
AH1-359
1.6 MW1.9%$7,085
AH1-360
1.8 MW2.3%$8,238
AH1-587
26.8 MW33.5%$122,206
AH1-588
18.6 MW23.3%$85,013
AH1-589
15.4 MW19.2%$70,018

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-031.b
Title
Replace 138 kV T-line drops at Karns City
Description
Replace (3) 138 kV T-line drops at Karns City
Total Cost ($USD)
$579,701
Allocated Cost ($USD)
$7,083
Time Estimate
13 Months

Contributor

FacilityContingency
01KARNSC-01KISSNG 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
13.8 MW12.9%$74,676
AG2-429
13.2 MW12.3%$71,413
AG2-456
5.2 MW4.9%$28,328
AG2-457
5.2 MW4.9%$28,328
AH1-050
5.0 MW4.6%$26,900
AH1-051
3.0 MW2.8%$16,136
AH1-102
3.8 MW3.5%$20,374
AH1-158
3.5 MW3.2%$18,766
AH1-268
1.6 MW1.5%$8,669
AH1-313
5.5 MW5.1%$29,611
AH1-357
1.3 MW1.2%$7,083
AH1-358
1.5 MW1.4%$8,236
AH1-359
1.3 MW1.2%$7,083
AH1-360
1.5 MW1.4%$8,236
AH1-587
13.1 MW12.2%$70,877
AH1-588
15.7 MW14.7%$84,984
AH1-589
12.9 MW12.1%$70,000

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.a
Title
Replace Bus Riser and Bus Side Disc Leads at Shingletown
Description
Replace (1) 230 kV Bus Riser and (1) 230 kV Bus Side Disc Leads at Shingletown
Total Cost ($USD)
$427,516
Allocated Cost ($USD)
$6,115
Time Estimate
13 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$23,212
AG2-456
7.9 MW5.7%$24,457
AG2-457
7.9 MW5.7%$24,457
AH1-313
32.3 MW23.3%$99,664
AH1-357
2.0 MW1.4%$6,115
AH1-358
2.3 MW1.7%$7,109
AH1-359
2.0 MW1.4%$6,115
AH1-360
2.3 MW1.7%$7,109
AH1-587
25.6 MW18.5%$78,969
AH1-588
23.8 MW17.2%$73,370
AH1-589
19.6 MW14.1%$60,433
AH1-720
5.3 MW3.9%$16,507

System Reinforcement: n7165.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7165.1
Title
Replace T-line drops at All Dam 6
Description
Replace (2) T-line drops at All Dam 6
Total Cost ($USD)
$427,516
Allocated Cost ($USD)
$6,026
Time Estimate
12 Months

Contributor

FacilityContingency
01AL&D6T-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
8.1 MW11.8%$50,539
AG2-429
10.0 MW14.6%$62,471
AG2-456
3.8 MW5.6%$24,102
AG2-457
3.8 MW5.6%$24,102
AH1-050
3.1 MW4.5%$19,181
AH1-051
1.8 MW2.7%$11,511
AH1-158
2.6 MW3.8%$16,338
AH1-357
1.0 MW1.4%$6,026
AH1-358
1.1 MW1.6%$7,005
AH1-359
1.0 MW1.4%$6,026
AH1-360
1.1 MW1.6%$7,005
AH1-587
9.8 MW14.4%$61,366
AH1-588
11.5 MW16.9%$72,300
AH1-589
9.5 MW13.9%$59,546

System Reinforcement: n6855.3
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6855.3
Title
Replace line trap at Glade
Description
Replace line trap at Glade on the Glade-Warren 230kV line.
Total Cost ($USD)
$230,000
Allocated Cost ($USD)
$5,839
Time Estimate
12 Months

Contributor

FacilityContingency
26GLADE-26WARREN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
34.8 MW10.2%$23,355
AG2-457
34.8 MW10.2%$23,355
AH1-313
12.2 MW3.6%$8,167
AH1-357
8.7 MW2.5%$5,839
AH1-358
10.1 MW3.0%$6,789
AH1-359
8.7 MW2.5%$5,839
AH1-360
10.1 MW3.0%$6,789
AH1-587
32.9 MW9.6%$22,094
AH1-588
104.3 MW30.5%$70,065
AH1-589
85.9 MW25.1%$57,709

System Reinforcement: n9240.0
Type
Load Flow
TO
APS
RTEP ID / TO ID
n9240.0 / TC1-APS-002.a
Title
Replace GE 800 Amp Wave Trap at Kittanning
Description
Replace GE 800 Amp Wave Trap at Kittanning
Total Cost ($USD)
$364,562
Allocated Cost ($USD)
$5,645
Time Estimate
17 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$45,844
AG2-429
7.4 MW9.8%$35,728
AG2-456
4.7 MW6.2%$22,571
AG2-457
4.7 MW6.2%$22,571
AH1-050
3.0 MW4.0%$14,486
AH1-051
1.8 MW2.4%$8,691
AH1-158
2.1 MW2.8%$10,107
AH1-357
1.2 MW1.5%$5,645
AH1-358
1.4 MW1.8%$6,562
AH1-359
1.2 MW1.5%$5,645
AH1-360
1.4 MW1.8%$6,562
AH1-587
11.7 MW15.5%$56,659
AH1-588
14.0 MW18.6%$67,716
AH1-589
11.5 MW15.3%$55,776

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-026.b
Title
Replace WHSE 1200 Amp Wave Trap at Armstrong
Description
Replace WHSE 1200 Amp Wave Trap at Armstrong
Total Cost ($USD)
$364,562
Allocated Cost ($USD)
$5,645
Time Estimate
18 Months

Contributor

FacilityContingency
01ARMSTR-01KITTAN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
9.5 MW12.6%$45,844
AG2-429
7.4 MW9.8%$35,728
AG2-456
4.7 MW6.2%$22,571
AG2-457
4.7 MW6.2%$22,571
AH1-050
3.0 MW4.0%$14,486
AH1-051
1.8 MW2.4%$8,691
AH1-158
2.1 MW2.8%$10,107
AH1-357
1.2 MW1.5%$5,645
AH1-358
1.4 MW1.8%$6,562
AH1-359
1.2 MW1.5%$5,645
AH1-360
1.4 MW1.8%$6,562
AH1-587
11.7 MW15.5%$56,659
AH1-588
14.0 MW18.6%$67,716
AH1-589
11.5 MW15.3%$55,776

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-PH1-014
Title
Replace WT at Shingletown substation.
Description
Replace WT at Shingletown substation.
Total Cost ($USD)
$308,526
Allocated Cost ($USD)
$4,448
Time Estimate
17 Months

Contributor

FacilityContingency
01SHINGL-01DALE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-456
5.8 MW5.8%$17,795
AG2-457
5.8 MW5.8%$17,795
AH1-313
31.9 MW31.7%$97,708
AH1-357
1.5 MW1.4%$4,448
AH1-358
1.7 MW1.7%$5,171
AH1-359
1.5 MW1.4%$4,448
AH1-360
1.7 MW1.7%$5,171
AH1-587
19.1 MW19.0%$58,633
AH1-588
17.4 MW17.3%$53,385
AH1-589
14.3 MW14.3%$43,971

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.b
Title
Replace Bus Riser at Shingletown
Description
Replace (1) 230 kV Bus Riser at Shingletown This project has pre-req TC2-APS-034.a
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$3,764
Time Estimate
12 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$14,289
AG2-456
7.9 MW5.7%$15,055
AG2-457
7.9 MW5.7%$15,055
AH1-313
32.3 MW23.3%$61,351
AH1-357
2.0 MW1.4%$3,764
AH1-358
2.3 MW1.7%$4,376
AH1-359
2.0 MW1.4%$3,764
AH1-360
2.3 MW1.7%$4,376
AH1-587
25.6 MW18.5%$48,611
AH1-588
23.8 MW17.2%$45,165
AH1-589
19.6 MW14.1%$37,201
AH1-720
5.3 MW3.9%$10,161

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.d
Title
Upgrade/Replace (4) 138 kV SPS AL 3.00 PIPE Substation Conductors
Description
Upgrade/Replace (4) 138 kV SPS AL 3.00 PIPE Substation Conductors
Total Cost ($USD)
$193,266
Allocated Cost ($USD)
$3,542
Time Estimate
14 Months

Contributor

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
20.8 MW12.4%$23,950
AG2-206
5.7 MW3.4%$6,581
AG2-220
3.7 MW2.2%$4,279
AG2-221
2.5 MW1.5%$2,821
AG2-327
1.2 MW0.7%$1,371
AG2-356
2.5 MW1.5%$2,821
AG2-456
12.3 MW7.3%$14,164
AG2-457
12.3 MW7.3%$14,164
AH1-005
2.4 MW1.4%$2,760
AH1-357
3.1 MW1.8%$3,542
AH1-358
3.6 MW2.1%$4,118
AH1-359
3.1 MW1.8%$3,542
AH1-360
3.6 MW2.1%$4,118
AH1-587
24.0 MW14.2%$27,540
AH1-588
37.0 MW22.0%$42,494
AH1-589
30.4 MW18.1%$35,001

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.f
Title
Replace Breaker Leads at Shingletown
Description
Replace (2) 230 kV Breaker Leads (Bus side and Line side) at Shingletown This project has a pre-req of TC2-APS-034.e
Total Cost ($USD)
$214,619
Allocated Cost ($USD)
$3,070
Time Estimate
12 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$11,653
AG2-456
7.9 MW5.7%$12,278
AG2-457
7.9 MW5.7%$12,278
AH1-313
32.3 MW23.3%$50,033
AH1-357
2.0 MW1.4%$3,070
AH1-358
2.3 MW1.7%$3,569
AH1-359
2.0 MW1.4%$3,070
AH1-360
2.3 MW1.7%$3,569
AH1-587
25.6 MW18.5%$39,643
AH1-588
23.8 MW17.2%$36,833
AH1-589
19.6 MW14.1%$30,338
AH1-720
5.3 MW3.9%$8,287

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.b
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$2,941
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$15,237
AG2-411
19.1 MW5.2%$13,805
AG2-429
12.3 MW3.4%$8,902
AG2-456
16.3 MW4.5%$11,764
AG2-457
16.3 MW4.5%$11,764
AH1-050
6.4 MW1.8%$4,643
AH1-051
3.9 MW1.1%$2,786
AH1-102
23.7 MW6.5%$17,158
AH1-140
17.9 MW4.9%$12,935
AH1-158
4.5 MW1.2%$3,239
AH1-201
8.9 MW2.4%$6,410
AH1-203
19.4 MW5.3%$13,998
AH1-205
4.1 MW1.1%$2,981
AH1-268
10.1 MW2.8%$7,302
AH1-313
14.5 MW4.0%$10,485
AH1-357
4.1 MW1.1%$2,941
AH1-358
4.7 MW1.3%$3,420
AH1-359
4.1 MW1.1%$2,941
AH1-360
4.7 MW1.3%$3,420
AH1-460
20.2 MW5.5%$14,571
AH1-587
38.9 MW10.7%$28,108
AH1-588
48.8 MW13.4%$35,291
AH1-589
40.2 MW11.0%$29,067

System Reinforcement: n9121.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9121.0 / TC1-PN-003.d
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$2,881
Time Estimate
11 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$14,924
AG2-411
19.1 MW5.2%$13,521
AG2-429
12.3 MW3.4%$8,719
AG2-456
16.3 MW4.5%$11,522
AG2-457
16.3 MW4.5%$11,522
AH1-050
6.4 MW1.8%$4,547
AH1-051
3.9 MW1.1%$2,729
AH1-102
23.7 MW6.5%$16,806
AH1-140
17.9 MW4.9%$12,669
AH1-158
4.5 MW1.2%$3,173
AH1-201
8.9 MW2.4%$6,278
AH1-203
19.4 MW5.3%$13,710
AH1-205
4.1 MW1.1%$2,920
AH1-268
10.1 MW2.8%$7,152
AH1-313
14.5 MW4.0%$10,270
AH1-357
4.1 MW1.1%$2,881
AH1-358
4.7 MW1.3%$3,350
AH1-359
4.1 MW1.1%$2,881
AH1-360
4.7 MW1.3%$3,350
AH1-460
20.2 MW5.5%$14,272
AH1-587
38.9 MW10.7%$27,530
AH1-588
48.8 MW13.4%$34,566
AH1-589
40.2 MW11.0%$28,470

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-PN-002.b
Title
Replace/Update SEL-421 Relays at Lewistown
Description
Replace/Update (2) SEL-421 Relays at Lewistown
Total Cost ($USD)
$176,953
Allocated Cost ($USD)
$2,531
Time Estimate
12 Months

Contributor

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
7.5 MW5.4%$9,608
AG2-456
7.9 MW5.7%$10,123
AG2-457
7.9 MW5.7%$10,123
AH1-313
32.3 MW23.3%$41,252
AH1-357
2.0 MW1.4%$2,531
AH1-358
2.3 MW1.7%$2,943
AH1-359
2.0 MW1.4%$2,531
AH1-360
2.3 MW1.7%$2,943
AH1-587
25.6 MW18.5%$32,686
AH1-588
23.8 MW17.2%$30,368
AH1-589
19.6 MW14.1%$25,014
AH1-720
5.3 MW3.9%$6,832

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-031.a
Title
Upgrade (2) 138 kV Breaker Leads at Karns City
Description
Upgrade (2) 138 kV Breaker Leads at Karns City This project has a pre-req of n7164.1.
Total Cost ($USD)
$183,598
Allocated Cost ($USD)
$2,243
Time Estimate
13 Months

Contributor

FacilityContingency
01KARNSC-01KISSNG 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
13.8 MW12.9%$23,651
AG2-429
13.2 MW12.3%$22,617
AG2-456
5.2 MW4.9%$8,972
AG2-457
5.2 MW4.9%$8,972
AH1-050
5.0 MW4.6%$8,519
AH1-051
3.0 MW2.8%$5,111
AH1-102
3.8 MW3.5%$6,453
AH1-158
3.5 MW3.2%$5,944
AH1-268
1.6 MW1.5%$2,746
AH1-313
5.5 MW5.1%$9,378
AH1-357
1.3 MW1.2%$2,243
AH1-358
1.5 MW1.4%$2,608
AH1-359
1.3 MW1.2%$2,243
AH1-360
1.5 MW1.4%$2,608
AH1-587
13.1 MW12.2%$22,448
AH1-588
15.7 MW14.7%$26,916
AH1-589
12.9 MW12.1%$22,170

System Reinforcement: n9120.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9120.0 / TC1-PN-003.c
Title
Replace substation conductor at Keystone substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$187,749
Allocated Cost ($USD)
$2,098
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$10,870
AG2-411
19.1 MW5.2%$9,849
AG2-429
12.3 MW3.4%$6,351
AG2-456
16.3 MW4.5%$8,392
AG2-457
16.3 MW4.5%$8,392
AH1-050
6.4 MW1.8%$3,312
AH1-051
3.9 MW1.1%$1,987
AH1-102
23.7 MW6.5%$12,241
AH1-140
17.9 MW4.9%$9,228
AH1-158
4.5 MW1.2%$2,311
AH1-201
8.9 MW2.4%$4,573
AH1-203
19.4 MW5.3%$9,986
AH1-205
4.1 MW1.1%$2,127
AH1-268
10.1 MW2.8%$5,209
AH1-313
14.5 MW4.0%$7,480
AH1-357
4.1 MW1.1%$2,098
AH1-358
4.7 MW1.3%$2,440
AH1-359
4.1 MW1.1%$2,098
AH1-360
4.7 MW1.3%$2,440
AH1-460
20.2 MW5.5%$10,395
AH1-587
38.9 MW10.7%$20,053
AH1-588
48.8 MW13.4%$25,177
AH1-589
40.2 MW11.0%$20,737

System Reinforcement: n9126.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9126.0 / TC1-PN-003.h
Title
Replace breaker leads at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$152,770
Allocated Cost ($USD)
$1,707
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$8,845
AG2-411
19.1 MW5.2%$8,014
AG2-429
12.3 MW3.4%$5,168
AG2-456
16.3 MW4.5%$6,829
AG2-457
16.3 MW4.5%$6,829
AH1-050
6.4 MW1.8%$2,695
AH1-051
3.9 MW1.1%$1,617
AH1-102
23.7 MW6.5%$9,960
AH1-140
17.9 MW4.9%$7,509
AH1-158
4.5 MW1.2%$1,880
AH1-201
8.9 MW2.4%$3,721
AH1-203
19.4 MW5.3%$8,126
AH1-205
4.1 MW1.1%$1,731
AH1-268
10.1 MW2.8%$4,239
AH1-313
14.5 MW4.0%$6,087
AH1-357
4.1 MW1.1%$1,707
AH1-358
4.7 MW1.3%$1,985
AH1-359
4.1 MW1.1%$1,707
AH1-360
4.7 MW1.3%$1,985
AH1-460
20.2 MW5.5%$8,459
AH1-587
38.9 MW10.7%$16,317
AH1-588
48.8 MW13.4%$20,487
AH1-589
40.2 MW11.0%$16,874

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.a
Title
Adjust relay settings at Keystone and Shelocta
Description
Total Cost ($USD)
$103,523
Allocated Cost ($USD)
$1,157
Time Estimate
11 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$5,994
AG2-411
19.1 MW5.2%$5,430
AG2-429
12.3 MW3.4%$3,502
AG2-456
16.3 MW4.5%$4,628
AG2-457
16.3 MW4.5%$4,628
AH1-050
6.4 MW1.8%$1,826
AH1-051
3.9 MW1.1%$1,096
AH1-102
23.7 MW6.5%$6,750
AH1-140
17.9 MW4.9%$5,088
AH1-158
4.5 MW1.2%$1,274
AH1-201
8.9 MW2.4%$2,521
AH1-203
19.4 MW5.3%$5,506
AH1-205
4.1 MW1.1%$1,173
AH1-268
10.1 MW2.8%$2,872
AH1-313
14.5 MW4.0%$4,125
AH1-357
4.1 MW1.1%$1,157
AH1-358
4.7 MW1.3%$1,345
AH1-359
4.1 MW1.1%$1,157
AH1-360
4.7 MW1.3%$1,345
AH1-460
20.2 MW5.5%$5,732
AH1-587
38.9 MW10.7%$11,057
AH1-588
48.8 MW13.4%$13,883
AH1-589
40.2 MW11.0%$11,434

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.b
Title
Adjust Relays at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$52,848
Allocated Cost ($USD)
$663
Time Estimate
12 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$3,275
AG2-411
17.6 MW5.5%$2,912
AG2-429
10.7 MW3.4%$1,777
AG2-456
16.0 MW5.0%$2,653
AG2-457
16.0 MW5.0%$2,653
AH1-050
5.4 MW1.7%$894
AH1-051
3.2 MW1.0%$537
AH1-102
16.1 MW5.0%$2,665
AH1-158
3.8 MW1.2%$624
AH1-201
8.1 MW2.5%$1,342
AH1-203
17.7 MW5.5%$2,932
AH1-205
3.8 MW1.2%$624
AH1-268
6.8 MW2.1%$1,134
AH1-313
13.0 MW4.1%$2,158
AH1-357
4.0 MW1.3%$663
AH1-358
4.7 MW1.5%$771
AH1-359
4.0 MW1.3%$663
AH1-360
4.7 MW1.5%$771
AH1-460
18.5 MW5.8%$3,062
AH1-587
37.5 MW11.8%$6,218
AH1-588
48.0 MW15.1%$7,960
AH1-589
39.5 MW12.4%$6,556

System Reinforcement: s3483.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
s3483.1 / APS-2023-021
Title
Convert Milesburg Substation into a four-breaker 230 kV ring bus (Projected ISD 12/17/2027)
Description
Milesburg – Moshannon 230 kV Line: - Before proposed solution: 548 / 688 / 699 / 804 MVA (SN / SE / WN / WE) - After proposed solution: 617 / 754 / 699 / 894 MVA (SN / SE / WN / WE) Milesburg – Dale Summit 230 kV Line: - Before proposed solution: 548 / 688 / 699 / 804 MVA (SN / SE / WN / WE) - After proposed solution: 617 / 754 / 699 / 894 MVA (SN / SE / WN / WE)
Cost Information
Time Estimate
Dec 17 2027

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-357 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01MILESB-AE2-262_TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.50
Title
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta
Description
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta by constructing a new Peach Bottom-North Delta 500 kV (0.3 miles) cut-in and cut-out lines.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 15 2027

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: s3335.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
s3335.1 / PN-2024-007
Title
Replace Homer City South 345/230-23kV Transformer (Projected ISD 6/1/2027)
Description
Replace the South 345/230-23kV Transformer and associated equipment with: - One(1) 345/230kV Transformer with three single-phase units - Replace 345 kV circuit switcher, disconnects, circuit breaker, and substation conductor Transformer Ratings: - Before Proposed Solution: 649/836/793/984 MVA (SN/SLTE/WN/WLTE) - After Proposed Solution: 913/1147/1201/1376 MVA (SN/SLTE/WN/WLTE)
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-357 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer(Any)
26HOMER CT-26HOMER CT _ 230.0 kV Ckt S line(Any)

System Reinforcement: n9116.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9116.0 / TC1-PN-001.d
Title
Rebuild approximately 11 miles of the Homer City-Shelocta 230 kV line with double bundled 795 kcmil 26/7 ACSS conductor
Description
Rebuild the Homer City – Shelocta 230 kV Line, approximately 11 miles, with double bunded 795 kcmil 26/7 ACSS conductor. Terminate new conductor at Homer City substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$39,312,233
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-357 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-357 could receive cost allocation. Although AH1-357 may not presently have cost responsibility for this upgrade, AH1-357 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9225.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9225.0 / TC1-PN-001.e
Title
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Description
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Total Cost ($USD)
$107,569
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-357 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-357 could receive cost allocation. Although AH1-357 may not presently have cost responsibility for this upgrade, AH1-357 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: s0945.1
Type
Load Flow
TO
PPL
RTEP ID / TO ID
s0945.1
Title
Rebuild the Juniata 230/69 kV Substation
Description
None
Cost Information
Time Estimate
Dec 31 2025

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-357 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9115.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9115.0 / PN-AF1-F-0022
Title
Replace substation conductor at the 115 kV tie at Shawville Substation
Description
Replace substation conductor at the 115 kV tie at Shawville. Upon completion of the Network Upgrade above, the expected final ratings are expected to be 188/239/263 MVA (SN/SLTE/SLD)
Total Cost ($USD)
$509,322
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-357 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-357 could receive cost allocation. Although AH1-357 may not presently have cost responsibility for this upgrade, AH1-357 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHAWVL 1-26SHAW. 2 115.0 kV Ckt ZB line(Any)

System Reinforcement: n9119.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9119.0 / TC1-PN-003.b
Title
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor
Description
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor. Terminate new conductor at Keystone substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$9,533,592
Allocated Cost ($USD)
$0
Time Estimate
23 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-357 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-357 could receive cost allocation. Although AH1-357 may not presently have cost responsibility for this upgrade, AH1-357 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AH1-357 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-357 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line(Any)
26N.MESHPN-26CANYON 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending)
Title
Single Element Derate - Eliminated by end of 2025
Description
FirstEnergy has an active internal project that will address the single element derate on the Keystone-South Bend 500kV line. This impacts the following contignencies: PN_P2-3_PN-500-DRT32_SRT-A [Breaker] and PN_P2-3_PN-500-004-DRT-002_SRT-SL [Breaker]
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line(Any)

System Reinforcement: n8471
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8471
Title
East Sayre-North Waverly 115kV line upgrade - FirstEnergy (NYISO CY17 driven upgrade)
Description
East Sayre Substation: Replace one (1) 115 kV circuit breaker on North Waverly (NYSEG) terminal at East Sayre. Revise wiring for the North Waverly 115kV PR and BU line protection relays to utilize the redundant CT’s and trip coils on the new breaker. East Sayre – North Waverly 115kV line: Replace 3 pole wood Structure 141 due to NYSEG reconductor of East Sayre-North Waverly 115kV line. Enable load encroachment such that all protection elements will achieve the required loadability of 221/263/263/301 MVA (SN/SE/WN/WE) Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal is still limiting. Once the scope of work and ratings at East Sayre are finalized, the expected line ratings will be updated. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$1,417,388
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2027

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-357 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-357 could receive cost allocation. Although AH1-357 may not presently have cost responsibility for this upgrade, AH1-357 is a potential Aggregate Pool Contributor.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending)
Title
FirstEnergy line ratings (FE end Only)
Description
On the FE side, The Laurel Lake – Goudey/Westover 115 kV (future Oakdale) Line Section is limited by the conductor: - 134/162/182 MVA SN/SE/SLD - 151/191/206 MVA WN/WE/WLD Note: To bring the existing line ratings to the conductor ratings, the limiting equipment on the NYSEG portion will need to be upgraded.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
OAKDL115-26LAUREL L 115.0 kV Ckt 1 line(Any)

          New AG2-456 230kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-456, AG2-457, AH1-357, AH1-358, AH1-359, AH1-360, AH1-588, AH1-589
        
          New AH1-050 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-050, AH1-051, AH1-158
        
          New AH1-102 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-102, AH1-268
        
          New Baltimore 115kV sub - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-201, AH1-205
        
          New AG2-206 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-206, AG2-327
        
          New AG2-220 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-220, AH1-005
        
          South Troy 34.5kV - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-221, AG2-356
        

Attachments

AH1-357 One Line Diagram

AH1-357 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.