AH1-452 Phase I Study Report

v1.00 released 2025-10-29 20:16

Clementine-Clementine Jct. 25 kV

8.35 MW Capacity / 19.9 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is IMG Solar LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Keystone Appalachian Transmission Company.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Keystone Appalachian Transmission Company zone — Armstrong County, Pennsylvania. The installed facilities will have a total capability of 19.9 MW with 8.35 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-452
Project Name:
Clementine-Clementine Jct. 25 kV
Project Developer Name:
IMG Solar LLC
State:
Pennsylvania
County:
Armstrong
Transmission Owner:
Keystone Appalachian Transmission Company
MFO:
19.9
MWE:
19.9
MWC:
8.35
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-452 will interconnect on the Keystone Appalachian Transmission Company distribution system on the Clementine Jct to Clementine 25 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-452 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-452Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-452

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-452 Project due at DP1
ABA - B
AH1-452$0$79,600$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AH1-452 did not contribute to any overloads on the FE transmission <100 kV system.  For any distribution impacts, please refer to the studies conducted as part of the FirstEnergy's state-level agreement process for non-FERC jurisdictional projects.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-452 was evaluated as a 19.9 MW (8.35 MW Capacity) injection in the APS area.

AH1-452 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 19.9 MW (19.9 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-3_WP-138-171A_SRT-A
BreakerAC150.5 %151.0B227.251.04
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-2_WP-138-054A_SRT-A
BusAC149.99 %151.0B226.480.98
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC142.46 %151.0B215.111.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC142.46 %151.0B215.111.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC138.88 %151.0B209.71.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC138.88 %151.0B209.71.0
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC121.3 %151.0B183.160.56
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.58 %151.0B157.921.68
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P2-2_WP-138-055_SRT-A
BusAC104.36 %151.0B157.581.47
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P2-3_WP-138-177_A_SRT-A
BreakerAC168.0 %151.0B253.680.85
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC143.83 %151.0B217.180.45
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC133.67 %151.0B201.840.49
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-18201_SRT-A
BreakerAC136.64 %192.0B262.360.93
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-182_SRT-A
BreakerAC136.64 %192.0B262.360.93
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-181T_SRT-A
BreakerAC136.64 %192.0B262.360.93
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-2_WP-138-0582-1_SRT-A
BusAC136.63 %192.0B262.320.93
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-050_SRT-A
TowerAC130.89 %192.0B251.30.82
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P2-3_WP-138-177_A_SRT-A
BreakerAC168.97 %151.0B255.150.85
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC144.37 %151.0B218.00.45
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC134.03 %151.0B202.390.49
GD2AP
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC128.11 %192.0B245.970.75
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-3_WP-138-171A_SRT-A
BreakerAC148.95 %151.0B224.921.04
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-2_WP-138-054A_SRT-A
BusAC148.43 %151.0B224.130.98
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC141.31 %151.0B213.371.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC141.31 %151.0B213.371.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
BreakerAC137.47 %151.0B207.581.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-3_SRT-A
BreakerAC137.47 %151.0B207.581.0
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC119.95 %151.0B181.130.56
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.78 %151.0B158.221.68
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P2-2_WP-138-055_SRT-A
BusAC102.82 %151.0B155.251.47
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-18201_SRT-A
BreakerAC141.35 %192.0B271.390.93
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-182_SRT-A
BreakerAC141.35 %192.0B271.390.93
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-181T_SRT-A
BreakerAC141.35 %192.0B271.380.93
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-2_WP-138-0582-1_SRT-A
BusAC141.33 %192.0B271.360.93
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC106.31 %1001.0B1064.170.95
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC106.31 %1001.0B1064.170.95
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC106.31 %1001.0B1064.160.95
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC104.94 %1001.0B1050.420.97
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0183-208_SRT-A
BreakerAC103.22 %1001.0B1033.260.86
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-230-001T_SRT-A
BusAC133.05 %827.0B1100.291.1
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC133.04 %827.0B1100.251.1
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-345-001T-DRT-001_SRT-A
BusAC131.95 %827.0B1091.21.1
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-2_PN-345-001T_SRT-A
BusAC131.95 %827.0B1091.21.1
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P2-3_PN-230-0183-207_SRT-A
BreakerAC129.11 %827.0B1067.771.1
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC128.09 %827.0B1059.331.12
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P2-2_WP-230-005T_SRT-A
BusAC115.4 %827.0B954.320.93
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Base Case
SingleAC113.83 %647.0A736.470.5
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC113.78 %827.0B940.961.14
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC112.55 %827.0B930.830.63
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC108.7 %827.0B898.940.76
GD2PENELEC
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
PN_P1-2_PN-345-003_SRT-A
SingleAC101.77 %827.0B841.630.62
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC132.2 %980.0B1295.550.85
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC131.02 %980.0B1284.020.86
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC131.02 %980.0B1284.020.86
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC131.01 %980.0B1283.850.86
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC121.6 %980.0B1191.640.78
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC121.6 %980.0B1191.640.78
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC108.9 %980.0B1067.20.78
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC105.44 %980.0B1033.270.49
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC105.43 %980.0B1033.250.49
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-050_SRT-A
TowerAC104.7 %980.0B1026.040.78
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-230-001T_SRT-A
BusAC132.97 %827.0B1099.71.1
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-230-0183-210_SRT-A
BreakerAC132.97 %827.0B1099.661.1
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-345-001T_SRT-A
BusAC131.9 %827.0B1090.831.1
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-2_PN-345-001T-DRT-001_SRT-A
BusAC131.9 %827.0B1090.831.1
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P2-3_PN-230-0183-207_SRT-A
BreakerAC129.01 %827.0B1066.941.1
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC128.09 %827.0B1059.311.12
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P2-2_WP-230-005T_SRT-A
BusAC115.44 %827.0B954.650.93
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Base Case
SingleAC113.82 %647.0A736.420.5
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P7-1_WPP-138-053A_SRT-A
TowerAC113.78 %827.0B940.951.14
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P1-3_DRT-230-003-DRT_SRT-SL
SingleAC112.51 %827.0B930.450.63
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
AP_P7-1_WPP-138-051A_SRT-A
TowerAC108.69 %827.0B898.890.76
GD2PENELEC
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
PN_P1-2_PN-345-003_SRT-A
SingleAC101.82 %827.0B842.020.62
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC133.95 %980.0B1312.711.13
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC133.46 %980.0B1307.881.14
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC133.46 %980.0B1307.881.14
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC133.4 %980.0B1307.341.14
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC122.69 %980.0B1202.41.05
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC122.69 %980.0B1202.41.05
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC108.43 %980.0B1062.610.87
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-036_SRT-A
BusAC108.01 %980.0B1058.480.94
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC107.82 %980.0B1056.61.03
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-083_SRT-A
TowerAC105.56 %980.0B1034.460.94
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC104.25 %980.0B1021.650.65
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC104.25 %980.0B1021.630.65

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-171A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-171A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.5 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:227.25
MW Contribution:1.04
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.101
971183AH1-050 GEN
Solar/Wind Harmer
3.056
970647AG2-420 GEN
Solar/Wind Harmer
0.169
20082826HNSMLK 1
Adder
4.017
20083026HNSMLK 3
Adder
4.017
203860AG1-193 C
Solar/Wind Harmer
0.198
971865AH1-452 GEN
Solar/Wind Harmer
1.037
970267AG2-176 GEN
Solar/Wind Harmer
8.051
970713AG2-456 GEN
Solar/Wind Harmer
3.839
971705AH1-358 GEN
Solar/Wind Harmer
1.116
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.882
238219AF1-167 C
Solar/Wind Harmer
1.621
971185AH1-051 GEN
Solar/Wind Harmer
1.833
971355AH1-158 GEN
Solar/Wind Harmer
2.132
203856AF2-165 C
Solar/Wind Harmer
0.88
970647AG2-420 GEN
Solar/Wind Harmer
1.45
20082926HNSMLK 2
Adder
4.017
20083126HNSMLK 4
Adder
4.017
945751AF1-240 GEN
Solar/Wind Harmer
1.058
959441AF2-235 GEN
Solar/Wind Harmer
0.2
957161AF2-010 GEN
Solar/Wind Harmer
3.921
203830AF1-094 GEN
Solar/Wind Harmer
0.304
971703AH1-357 GEN
Solar/Wind Harmer
0.96
971707AH1-359 GEN
Solar/Wind Harmer
0.96
20120126WRREN CT
Adder
2.873
962511AG1-100 GEN
Solar/Wind Harmer
0.267
20334926Z1-069 C
Solar/Wind Harmer
0.923
203962AF1-287 GEN
Solar/Wind Harmer
0.879
203854AF2-039 C
Solar/Wind Harmer
0.178
20060826PINEY #1
50/50
0.054
971055AG2-654 GEN
Solar/Wind Harmer
1.941
970663AG2-429 GEN
Solar/Wind Harmer
8.559
970663AG2-429 GEN
Solar/Wind Harmer
1.393
203846AF2-130 C
Solar/Wind Harmer
0.471
20083226HNSMLK 5
Adder
4.017
20083926HOMER C3
Adder
37.854
20083826HOMER C2
Adder
35.758
970677AG2-438 GEN
Solar/Wind Harmer
0.502
203804AE2-113_GEN
Solar/Wind Harmer
2.367
966771AG1-548 GEN
Solar/Wind Harmer
7.169
966771AG1-548 GEN
Solar/Wind Harmer
1.389
940863AE2-074 GEN
Solar/Wind Harmer
0.802
203855AF2-088 C
Solar/Wind Harmer
0.086
20083726HOMER C1
Adder
21.846
23513401AL&D6
50/50
0.042
946381AF1-302 GEN
Solar/Wind Harmer
2.052
203848AF2-166 C
Solar/Wind Harmer
1.647
238217AF1-153 C O1
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.182
971933AH1-491 GEN
Solar/Wind Harmer
1.003
203980AG1-197 GEN
Solar/Wind Harmer
0.222
972075AH1-587 GEN
Solar/Wind Harmer
9.775
972077AH1-588 GEN
Solar/Wind Harmer
11.517
972079AH1-589 GEN
Solar/Wind Harmer
9.486
970715AG2-457 GEN
Solar/Wind Harmer
3.839
970305AG2-200 GEN
Solar/Wind Harmer
0.909
971931AH1-490 GEN
Solar/Wind Harmer
0.884
971709AH1-360 GEN
Solar/Wind Harmer
1.116
961971AG1-040 GEN
Solar/Wind Harmer
0.29
203954AE2-126 C
Solar/Wind Harmer
0.286
20072226SHAWVL 2
Adder
6.145
203813AE2-344_GEN
Solar/Wind Harmer
5.097
20091326SHAW-D
Adder
0.286
972169AH1-667 GEN
Solar/Wind Harmer
0.783
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.635
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.139
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.905
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.896
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-054A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-054A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:149.99 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:226.48
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
23513401AL&D6
50/50
0.041
946381AF1-302 GEN
Solar/Wind Harmer
2.041
203848AF2-166 C
Solar/Wind Harmer
1.637
238217AF1-153 C O1
Solar/Wind Harmer
0.376
203979AG1-198 GEN
Solar/Wind Harmer
0.181
971933AH1-491 GEN
Solar/Wind Harmer
0.997
972075AH1-587 GEN
Solar/Wind Harmer
9.72
203980AG1-197 GEN
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
11.453
972079AH1-589 GEN
Solar/Wind Harmer
9.433
970715AG2-457 GEN
Solar/Wind Harmer
3.818
970305AG2-200 GEN
Solar/Wind Harmer
0.903
971931AH1-490 GEN
Solar/Wind Harmer
0.879
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
238219AF1-167 C
Solar/Wind Harmer
1.603
971185AH1-051 GEN
Solar/Wind Harmer
1.822
971355AH1-158 GEN
Solar/Wind Harmer
2.119
203856AF2-165 C
Solar/Wind Harmer
0.874
970647AG2-420 GEN
Solar/Wind Harmer
1.441
20082926HNSMLK 2
Adder
3.994
20083126HNSMLK 4
Adder
3.994
945751AF1-240 GEN
Solar/Wind Harmer
1.051
959441AF2-235 GEN
Solar/Wind Harmer
0.199
957161AF2-010 GEN
Solar/Wind Harmer
3.897
203830AF1-094 GEN
Solar/Wind Harmer
0.302
971703AH1-357 GEN
Solar/Wind Harmer
0.954
971707AH1-359 GEN
Solar/Wind Harmer
0.954
20120126WRREN CT
Adder
2.856
962511AG1-100 GEN
Solar/Wind Harmer
0.266
20334926Z1-069 C
Solar/Wind Harmer
0.918
203962AF1-287 GEN
Solar/Wind Harmer
0.874
203854AF2-039 C
Solar/Wind Harmer
0.177
20060826PINEY #1
50/50
0.054
970663AG2-429 GEN
Solar/Wind Harmer
8.508
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.468
20083226HNSMLK 5
Adder
3.994
20083926HOMER C3
Adder
37.649
20083826HOMER C2
Adder
35.564
970677AG2-438 GEN
Solar/Wind Harmer
0.499
203804AE2-113_GEN
Solar/Wind Harmer
2.354
966771AG1-548 GEN
Solar/Wind Harmer
7.125
966771AG1-548 GEN
Solar/Wind Harmer
1.381
940863AE2-074 GEN
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.085
20083726HOMER C1
Adder
21.733
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.078
971183AH1-050 GEN
Solar/Wind Harmer
3.037
970647AG2-420 GEN
Solar/Wind Harmer
0.168
20082826HNSMLK 1
Adder
3.994
20083026HNSMLK 3
Adder
3.994
203860AG1-193 C
Solar/Wind Harmer
0.197
971865AH1-452 GEN
Solar/Wind Harmer
0.981
970267AG2-176 GEN
Solar/Wind Harmer
8.003
970713AG2-456 GEN
Solar/Wind Harmer
3.818
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
961971AG1-040 GEN
Solar/Wind Harmer
0.288
203954AE2-126 C
Solar/Wind Harmer
0.284
20072226SHAWVL 2
Adder
6.11
203813AE2-344_GEN
Solar/Wind Harmer
5.067
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.779
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.904
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.853
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.46 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:215.11
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.053
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.436
20082926HNSMLK 2
Adder
4.152
20083126HNSMLK 4
Adder
4.152
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.152
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.338
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.152
20083026HNSMLK 3
Adder
4.152
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.97
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.346
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.447
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.167
971709AH1-360 GEN
Solar/Wind Harmer
1.167
203954AE2-126 C
Solar/Wind Harmer
0.277
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.753
20083826HOMER C2
Adder
32.828
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.403
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.047
972079AH1-589 GEN
Solar/Wind Harmer
9.923
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.881
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.818
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.18
G-007ALTFEXP_G-007A->PJM
CMTX
1.776
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.46 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:215.11
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.053
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.436
20082926HNSMLK 2
Adder
4.152
20083126HNSMLK 4
Adder
4.152
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.152
20083026HNSMLK 3
Adder
4.152
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.97
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.346
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.447
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.167
971709AH1-360 GEN
Solar/Wind Harmer
1.167
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.152
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.338
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.753
20083826HOMER C2
Adder
32.828
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.403
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.047
972079AH1-589 GEN
Solar/Wind Harmer
9.923
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.881
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.818
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.921
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.18
G-007ALTFEXP_G-007A->PJM
CMTX
1.776
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.556
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:209.7
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.546
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.073
971707AH1-359 GEN
Solar/Wind Harmer
1.073
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.599
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.873
944411AF1-106 GEN
Solar/Wind Harmer
0.098
238183AE2-316 GEN
Solar/Wind Harmer
3.309
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.577
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.294
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.558
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.908
970663AG2-429 GEN
Solar/Wind Harmer
6.703
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.743
20083826HOMER C2
Adder
48.877
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.645
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.91
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.882
972079AH1-589 GEN
Solar/Wind Harmer
10.61
970715AG2-457 GEN
Solar/Wind Harmer
4.294
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.315
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.924
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.625
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
G-007ALTFEXP_G-007A->PJM
CMTX
0.924
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.88 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:209.7
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.546
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.073
971707AH1-359 GEN
Solar/Wind Harmer
1.073
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.599
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.873
944411AF1-106 GEN
Solar/Wind Harmer
0.098
238183AE2-316 GEN
Solar/Wind Harmer
3.309
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.577
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.294
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.558
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.985
944411AF1-106 GEN
Solar/Wind Harmer
0.908
970663AG2-429 GEN
Solar/Wind Harmer
6.703
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.743
20083826HOMER C2
Adder
48.877
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.645
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.91
23513401AL&D6
50/50
0.038
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.882
972079AH1-589 GEN
Solar/Wind Harmer
10.61
970715AG2-457 GEN
Solar/Wind Harmer
4.294
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.315
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.924
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.625
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
G-007ALTFEXP_G-007A->PJM
CMTX
0.924
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.3 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:183.16
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.054
20066226SCRUB GR
50/50
0.379
20083226HNSMLK 5
50/50
4.238
970663AG2-429 GEN
Solar/Wind Harmer
6.337
970663AG2-429 GEN
Solar/Wind Harmer
1.385
20060826PINEY #1
50/50
0.061
20082826HNSMLK 1
50/50
4.238
20083026HNSMLK 3
50/50
4.238
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
0.168
203860AG1-193 C
Solar/Wind Harmer
0
971865AH1-452 GEN
Solar/Wind Harmer
0.564
970267AG2-176 GEN
Solar/Wind Harmer
5.584
970713AG2-456 GEN
Solar/Wind Harmer
3.096
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
203954AE2-126 C
Solar/Wind Harmer
0
20072226SHAWVL 2
Adder
6.11
203813AE2-344_GEN
Solar/Wind Harmer
3.535
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.543
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
20082926HNSMLK 2
50/50
4.238
20083126HNSMLK 4
50/50
4.238
238219AF1-167 C
Solar/Wind Harmer
1.117
971185AH1-051 GEN
Solar/Wind Harmer
1.57
971355AH1-158 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
1.005
945751AF1-240 GEN
Solar/Wind Harmer
0.854
957161AF2-010 GEN
Solar/Wind Harmer
2.707
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.666
971707AH1-359 GEN
Solar/Wind Harmer
0.666
20120126WRREN CT
Adder
2.856
20334926Z1-069 C
Solar/Wind Harmer
0.23
203962AF1-287 GEN
Solar/Wind Harmer
0.61
203854AF2-039 C
Solar/Wind Harmer
0
23513401AL&D6
50/50
0.041
203848AF2-166 C
Solar/Wind Harmer
1.142
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.696
972075AH1-587 GEN
Solar/Wind Harmer
6.782
203980AG1-197 GEN
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
7.99
972079AH1-589 GEN
Solar/Wind Harmer
9.433
970715AG2-457 GEN
Solar/Wind Harmer
3.096
970305AG2-200 GEN
Solar/Wind Harmer
0.63
971931AH1-490 GEN
Solar/Wind Harmer
0.613
971055AG2-654 GEN
Solar/Wind Harmer
1.082
20083926HOMER C3
Adder
37.649
20083826HOMER C2
Adder
35.564
970677AG2-438 GEN
Solar/Wind Harmer
0.388
203804AE2-113_GEN
Solar/Wind Harmer
0.003
966771AG1-548 GEN
Solar/Wind Harmer
1.134
966771AG1-548 GEN
Solar/Wind Harmer
1.418
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.733
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.904
G-007ALTFEXP_G-007A->PJM
CMTX
1.485
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.853
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:157.92
MW Contribution:1.68
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.018
238219AF1-167 C
Solar/Wind Harmer
1.452
203932AE1-123
Adder
1.503
971185AH1-051 GEN
Solar/Wind Harmer
1.549
971355AH1-158 GEN
Solar/Wind Harmer
1.801
203856AF2-165 C
Solar/Wind Harmer
0.743
970647AG2-420 GEN
Solar/Wind Harmer
1.224
945751AF1-240 GEN
Solar/Wind Harmer
0.922
20082926HNSMLK 2
Adder
3.365
20083126HNSMLK 4
Adder
3.365
959441AF2-235 GEN
Solar/Wind Harmer
0.169
971703AH1-357 GEN
Solar/Wind Harmer
0.821
971707AH1-359 GEN
Solar/Wind Harmer
0.821
23513401AL&D6
50/50
0.044
946381AF1-302 GEN
Solar/Wind Harmer
1.716
203848AF2-166 C
Solar/Wind Harmer
1.394
238217AF1-153 C O1
Solar/Wind Harmer
0.322
972075AH1-587 GEN
Solar/Wind Harmer
8.365
972077AH1-588 GEN
Solar/Wind Harmer
9.847
972079AH1-589 GEN
Solar/Wind Harmer
8.11
970715AG2-457 GEN
Solar/Wind Harmer
3.282
971055AG2-654 GEN
Solar/Wind Harmer
1.558
970663AG2-429 GEN
Solar/Wind Harmer
7.159
970663AG2-429 GEN
Solar/Wind Harmer
1.165
203846AF2-130 C
Solar/Wind Harmer
0.398
20083226HNSMLK 5
Adder
3.365
20083926HOMER C3
Adder
32.597
20083826HOMER C2
Adder
30.791
20083726HOMER C1
Adder
19.751
971865AH1-452 GEN
Solar/Wind Harmer
1.68
238183AE2-316 GEN
Solar/Wind Harmer
3.43
971183AH1-050 GEN
Solar/Wind Harmer
2.581
970647AG2-420 GEN
Solar/Wind Harmer
0.142
20082826HNSMLK 1
Adder
3.365
20083026HNSMLK 3
Adder
3.365
203860AG1-193 C
Solar/Wind Harmer
0.167
970267AG2-176 GEN
Solar/Wind Harmer
6.754
970713AG2-456 GEN
Solar/Wind Harmer
3.282
971705AH1-358 GEN
Solar/Wind Harmer
0.954
971709AH1-360 GEN
Solar/Wind Harmer
0.954
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.592
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.87
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.089
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.844
G-007ALTFEXP_G-007A->PJM
CMTX
1.392
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.658
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-055_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-055_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.36 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:157.58
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.314
203932AE1-123
Adder
1.455
971185AH1-051 GEN
Solar/Wind Harmer
1.499
971355AH1-158 GEN
Solar/Wind Harmer
1.743
203856AF2-165 C
Solar/Wind Harmer
0.719
970647AG2-420 GEN
Solar/Wind Harmer
1.184
945751AF1-240 GEN
Solar/Wind Harmer
0.9
20082926HNSMLK 2
Adder
3.264
20083126HNSMLK 4
Adder
3.264
959441AF2-235 GEN
Solar/Wind Harmer
0.164
971703AH1-357 GEN
Solar/Wind Harmer
0.805
971707AH1-359 GEN
Solar/Wind Harmer
0.805
971865AH1-452 GEN
Solar/Wind Harmer
1.465
238183AE2-316 GEN
Solar/Wind Harmer
3.328
971183AH1-050 GEN
Solar/Wind Harmer
2.498
970647AG2-420 GEN
Solar/Wind Harmer
0.138
20082826HNSMLK 1
Adder
3.264
20083026HNSMLK 3
Adder
3.264
203860AG1-193 C
Solar/Wind Harmer
0.162
970267AG2-176 GEN
Solar/Wind Harmer
6.529
970713AG2-456 GEN
Solar/Wind Harmer
3.219
971705AH1-358 GEN
Solar/Wind Harmer
0.936
971709AH1-360 GEN
Solar/Wind Harmer
0.936
23513401AL&D6
50/50
0.037
946381AF1-302 GEN
Solar/Wind Harmer
1.665
203848AF2-166 C
Solar/Wind Harmer
1.35
238217AF1-153 C O1
Solar/Wind Harmer
0.314
972075AH1-587 GEN
Solar/Wind Harmer
8.204
972077AH1-588 GEN
Solar/Wind Harmer
9.656
972079AH1-589 GEN
Solar/Wind Harmer
7.953
970715AG2-457 GEN
Solar/Wind Harmer
3.219
971055AG2-654 GEN
Solar/Wind Harmer
1.278
970663AG2-429 GEN
Solar/Wind Harmer
6.915
970663AG2-429 GEN
Solar/Wind Harmer
1.126
203846AF2-130 C
Solar/Wind Harmer
0.386
20083226HNSMLK 5
Adder
3.264
20083926HOMER C3
Adder
32.146
20083826HOMER C2
Adder
30.366
20083726HOMER C1
Adder
19.961
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.65
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.382
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.926
G-007ALTFEXP_G-007A->PJM
CMTX
1.582
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-177_A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-177_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.0 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:253.68
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.066
238183AE2-316 GEN
Solar/Wind Harmer
4.473
971183AH1-050 GEN
Solar/Wind Harmer
3.312
970647AG2-420 GEN
Solar/Wind Harmer
0.183
20082826HNSMLK 1
Adder
4.379
20083026HNSMLK 3
Adder
4.379
203860AG1-193 C
Solar/Wind Harmer
0.216
970267AG2-176 GEN
Solar/Wind Harmer
8.783
961971AG1-040 GEN
Solar/Wind Harmer
0.317
970713AG2-456 GEN
Solar/Wind Harmer
4.103
971705AH1-358 GEN
Solar/Wind Harmer
1.193
971709AH1-360 GEN
Solar/Wind Harmer
1.193
203954AE2-126 C
Solar/Wind Harmer
0.304
971865AH1-452 GEN
Solar/Wind Harmer
0.846
203813AE2-344_GEN
Solar/Wind Harmer
5.571
20072226SHAWVL 2
Adder
6.51
972169AH1-667 GEN
Solar/Wind Harmer
0.824
20091326SHAW-D
Adder
0.301
203835AF1-098 GEN
Solar/Wind Harmer
1.093
238206AE2-263_GEN
Solar/Wind Harmer
1.043
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.033
238219AF1-167 C
Solar/Wind Harmer
1.746
971185AH1-051 GEN
Solar/Wind Harmer
1.987
971355AH1-158 GEN
Solar/Wind Harmer
2.311
203856AF2-165 C
Solar/Wind Harmer
0.954
970647AG2-420 GEN
Solar/Wind Harmer
1.572
20082926HNSMLK 2
Adder
4.379
20083126HNSMLK 4
Adder
4.379
959441AF2-235 GEN
Solar/Wind Harmer
0.217
945751AF1-240 GEN
Solar/Wind Harmer
1.121
957161AF2-010 GEN
Solar/Wind Harmer
4.268
203830AF1-094 GEN
Solar/Wind Harmer
0.331
971703AH1-357 GEN
Solar/Wind Harmer
1.026
971707AH1-359 GEN
Solar/Wind Harmer
1.026
20120126WRREN CT
Adder
3.099
962511AG1-100 GEN
Solar/Wind Harmer
0.292
203962AF1-287 GEN
Solar/Wind Harmer
0.961
20334926Z1-069 C
Solar/Wind Harmer
0.981
203854AF2-039 C
Solar/Wind Harmer
0.187
238202AE2-262_GEN
Solar/Wind Harmer
1.12
971627AH1-313 GEN
Solar/Wind Harmer
4.389
203948AG1-140 C
Solar/Wind Harmer
0.114
20060826PINEY #1
50/50
0.059
970663AG2-429 GEN
Solar/Wind Harmer
9.339
970663AG2-429 GEN
Solar/Wind Harmer
1.52
971055AG2-654 GEN
Solar/Wind Harmer
1.148
203846AF2-130 C
Solar/Wind Harmer
0.509
20083226HNSMLK 5
Adder
4.379
20083926HOMER C3
Adder
40.151
20083826HOMER C2
Adder
37.927
970677AG2-438 GEN
Solar/Wind Harmer
0.546
966771AG1-548 GEN
Solar/Wind Harmer
7.806
966771AG1-548 GEN
Solar/Wind Harmer
1.513
203804AE2-113_GEN
Solar/Wind Harmer
2.528
940863AE2-074 GEN
Solar/Wind Harmer
0.855
203855AF2-088 C
Solar/Wind Harmer
0.09
20083726HOMER C1
Adder
22.048
23513401AL&D6
50/50
0.029
946381AF1-302 GEN
Solar/Wind Harmer
2.238
203848AF2-166 C
Solar/Wind Harmer
1.782
238217AF1-153 C O1
Solar/Wind Harmer
0.407
203979AG1-198 GEN
Solar/Wind Harmer
0.198
971933AH1-491 GEN
Solar/Wind Harmer
1.092
203980AG1-197 GEN
Solar/Wind Harmer
0.242
972075AH1-587 GEN
Solar/Wind Harmer
10.438
972077AH1-588 GEN
Solar/Wind Harmer
12.308
972079AH1-589 GEN
Solar/Wind Harmer
10.138
970715AG2-457 GEN
Solar/Wind Harmer
4.103
970305AG2-200 GEN
Solar/Wind Harmer
0.98
971931AH1-490 GEN
Solar/Wind Harmer
0.967
203963AG1-253 GEN
Solar/Wind Harmer
0.173
203947AF1-006 C
Solar/Wind Harmer
0.241
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.576
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.519
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.822
G-007ALTFEXP_G-007A->PJM
CMTX
1.254
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.83 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:217.18
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.029
20082926HNSMLK 2
50/50
4.644
20083126HNSMLK 4
50/50
4.644
238219AF1-167 C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
1.71
971355AH1-158 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
1.096
945751AF1-240 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
2.963
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.714
971707AH1-359 GEN
Solar/Wind Harmer
0.714
20120126WRREN CT
Adder
3.096
203962AF1-287 GEN
Solar/Wind Harmer
0.671
20334926Z1-069 C
Solar/Wind Harmer
0.245
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.054
203948AG1-140 C
Solar/Wind Harmer
0.086
23513401AL&D6
50/50
0.029
203848AF2-166 C
Solar/Wind Harmer
1.242
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.762
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.269
972077AH1-588 GEN
Solar/Wind Harmer
8.573
972079AH1-589 GEN
Solar/Wind Harmer
10.121
970715AG2-457 GEN
Solar/Wind Harmer
3.322
970305AG2-200 GEN
Solar/Wind Harmer
0.683
971931AH1-490 GEN
Solar/Wind Harmer
0.675
203963AG1-253 GEN
Solar/Wind Harmer
0.136
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.059
20066226SCRUB GR
50/50
0.413
20083226HNSMLK 5
50/50
4.644
970663AG2-429 GEN
Solar/Wind Harmer
6.947
970663AG2-429 GEN
Solar/Wind Harmer
1.518
971055AG2-654 GEN
Solar/Wind Harmer
0.933
20083926HOMER C3
Adder
40.066
20083826HOMER C2
Adder
37.847
970677AG2-438 GEN
Solar/Wind Harmer
0.425
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.553
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.944
20060826PINEY #1
50/50
0.066
20082826HNSMLK 1
50/50
4.644
20083026HNSMLK 3
50/50
4.644
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
0.183
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.126
970713AG2-456 GEN
Solar/Wind Harmer
3.322
971705AH1-358 GEN
Solar/Wind Harmer
1.191
971709AH1-360 GEN
Solar/Wind Harmer
1.191
203954AE2-126 C
Solar/Wind Harmer
0.001
203813AE2-344_GEN
Solar/Wind Harmer
3.887
20072226SHAWVL 2
Adder
6.494
971865AH1-452 GEN
Solar/Wind Harmer
0.451
20091326SHAW-D
Adder
0.3
972169AH1-667 GEN
Solar/Wind Harmer
0.574
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.146
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.79
G-007ALTFEXP_G-007A->PJM
CMTX
1.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.982
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.67 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:201.84
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.06
20066226SCRUB GR
50/50
0.421
20083226HNSMLK 5
50/50
4.728
970663AG2-429 GEN
Solar/Wind Harmer
7.068
970663AG2-429 GEN
Solar/Wind Harmer
1.545
971055AG2-654 GEN
Solar/Wind Harmer
0.966
20083926HOMER C3
Adder
40.966
20083826HOMER C2
Adder
38.697
970677AG2-438 GEN
Solar/Wind Harmer
0.433
966771AG1-548 GEN
Solar/Wind Harmer
1.265
966771AG1-548 GEN
Solar/Wind Harmer
1.581
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
22.622
20060826PINEY #1
50/50
0.068
20082826HNSMLK 1
50/50
4.728
20083026HNSMLK 3
50/50
4.728
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
0.186
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.236
970713AG2-456 GEN
Solar/Wind Harmer
3.392
971705AH1-358 GEN
Solar/Wind Harmer
1.216
971709AH1-360 GEN
Solar/Wind Harmer
1.216
203954AE2-126 C
Solar/Wind Harmer
0.001
971865AH1-452 GEN
Solar/Wind Harmer
0.487
203813AE2-344_GEN
Solar/Wind Harmer
3.956
20072226SHAWVL 2
Adder
6.64
20091326SHAW-D
Adder
0.308
972169AH1-667 GEN
Solar/Wind Harmer
0.587
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.077
23503001MHNG-T155
50/50
0.018
20060826PINEY #1
50/50
0.065
203932AE1-123
50/50
2.068
20082926HNSMLK 2
50/50
4.728
20083126HNSMLK 4
50/50
4.728
238219AF1-167 C
Solar/Wind Harmer
1.237
971185AH1-051 GEN
Solar/Wind Harmer
1.742
971355AH1-158 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
1.116
945751AF1-240 GEN
Solar/Wind Harmer
0.929
957161AF2-010 GEN
Solar/Wind Harmer
3.017
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.73
971707AH1-359 GEN
Solar/Wind Harmer
0.73
20120126WRREN CT
Adder
3.157
203962AF1-287 GEN
Solar/Wind Harmer
0.682
20334926Z1-069 C
Solar/Wind Harmer
0.251
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.124
203948AG1-140 C
Solar/Wind Harmer
0.087
20084926LAKVU GN
Adder
0.077
960051AF2-296 GEN
Solar/Wind Harmer
0.603
203848AF2-166 C
Solar/Wind Harmer
1.265
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.775
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.424
972077AH1-588 GEN
Solar/Wind Harmer
8.754
972079AH1-589 GEN
Solar/Wind Harmer
10.335
970715AG2-457 GEN
Solar/Wind Harmer
3.392
970305AG2-200 GEN
Solar/Wind Harmer
0.697
971931AH1-490 GEN
Solar/Wind Harmer
0.686
203963AG1-253 GEN
Solar/Wind Harmer
0.139
203947AF1-006 C
Solar/Wind Harmer
0.021
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.826
G-007ALTFEXP_G-007A->PJM
CMTX
1.282
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.258
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-18201_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-18201_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-182_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-182_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-181T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-181T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-0582-1_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-0582-1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.63 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.32
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-050_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-050_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.89 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:251.3
MW Contribution:0.82
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.023
20079426CONEMAGH
Adder
0.774
971541AH1-268 GEN
Solar/Wind Harmer
2.196
970899AG2-561 GEN
Solar/Wind Harmer
1.241
203818AF1-086 GEN
Solar/Wind Harmer
1.365
945751AF1-240 GEN
Solar/Wind Harmer
0.777
970125AG2-091 GEN
Solar/Wind Harmer
0.292
971879AH1-460 GEN
Solar/Wind Harmer
3.19
203841AF2-001_GEN
Solar/Wind Harmer
0.957
960051AF2-296 GEN
Solar/Wind Harmer
0.892
971419AH1-201 GEN
Solar/Wind Harmer
1.389
237043AE2-125 C
Solar/Wind Helper
0.286
971279AH1-102 GEN
Solar/Wind Harmer
5.159
20094526CT_V3-030
Solar/Wind Harmer
0.382
971865AH1-452 GEN
Solar/Wind Harmer
0.821
20088826HIGHLAND
Solar/Wind Harmer
0.79
203843AF2-002_GEN
Solar/Wind Harmer
0.479
970631AG2-411 GEN
Solar/Wind Harmer
2.985
964201AG1-281 GEN
Solar/Wind Harmer
0.265
971423AH1-203 GEN
Solar/Wind Harmer
3.02
237046AF1-021 C
Solar/Wind Helper
0.238
946071AF1-272 GEN
Solar/Wind Harmer
2.834
971441AH1-212 GEN
Solar/Wind Harmer
0.99
203857AF2-221 C
Solar/Wind Harmer
0.73
970123AG2-090 GEN
Solar/Wind Harmer
0.681
203839AF1-321 GEN
Solar/Wind Harmer
0.957
20084626FORWARD
Solar/Wind Harmer
0.374
203940AF1-140 C
Solar/Wind Harmer
0.232
203853AF1-134 C O1
Solar/Wind Harmer
0.27
20088926STNY CRK
Solar/Wind Harmer
0.535
971427AH1-205 GEN
Solar/Wind Harmer
0.646
972077AH1-588 GEN
Solar/Wind Harmer
6.901
972079AH1-589 GEN
Solar/Wind Harmer
5.684
23652301WDPWR_K20
Solar/Wind Helper
0.114
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
71.495
971321AH1-140 GEN
Solar/Wind Harmer
13.856
20092526R32
Solar/Wind Harmer
0.847
203850AG1-041 C
Solar/Wind Harmer
0.557
203844AF2-092 C
Solar/Wind Harmer
0.556
20091526CHSTN_FL
Solar/Wind Harmer
0.384
20083726HOMER C1
Adder
25.766
20083926HOMER C3
Adder
25.516
20083826HOMER C2
Adder
24.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.725
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.43
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.124
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.05
G-007ALTFEXP_G-007A->PJM
CMTX
1.602
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.211
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-177_A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-177_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.97 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:255.15
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.066
238183AE2-316 GEN
Solar/Wind Harmer
4.473
971183AH1-050 GEN
Solar/Wind Harmer
3.312
970647AG2-420 GEN
Solar/Wind Harmer
0.183
20082826HNSMLK 1
Adder
4.379
20083026HNSMLK 3
Adder
4.379
203860AG1-193 C
Solar/Wind Harmer
0.216
970267AG2-176 GEN
Solar/Wind Harmer
8.783
961971AG1-040 GEN
Solar/Wind Harmer
0.317
970713AG2-456 GEN
Solar/Wind Harmer
4.103
971705AH1-358 GEN
Solar/Wind Harmer
1.193
971709AH1-360 GEN
Solar/Wind Harmer
1.193
203954AE2-126 C
Solar/Wind Harmer
0.304
971865AH1-452 GEN
Solar/Wind Harmer
0.846
203813AE2-344_GEN
Solar/Wind Harmer
5.571
20072226SHAWVL 2
Adder
6.51
972169AH1-667 GEN
Solar/Wind Harmer
0.824
20091326SHAW-D
Adder
0.301
203835AF1-098 GEN
Solar/Wind Harmer
1.093
238206AE2-263_GEN
Solar/Wind Harmer
1.043
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.033
238219AF1-167 C
Solar/Wind Harmer
1.746
971185AH1-051 GEN
Solar/Wind Harmer
1.987
971355AH1-158 GEN
Solar/Wind Harmer
2.311
203856AF2-165 C
Solar/Wind Harmer
0.954
970647AG2-420 GEN
Solar/Wind Harmer
1.572
20082926HNSMLK 2
Adder
4.379
20083126HNSMLK 4
Adder
4.379
959441AF2-235 GEN
Solar/Wind Harmer
0.217
945751AF1-240 GEN
Solar/Wind Harmer
1.121
957161AF2-010 GEN
Solar/Wind Harmer
4.268
203830AF1-094 GEN
Solar/Wind Harmer
0.331
971703AH1-357 GEN
Solar/Wind Harmer
1.026
971707AH1-359 GEN
Solar/Wind Harmer
1.026
20120126WRREN CT
Adder
3.099
962511AG1-100 GEN
Solar/Wind Harmer
0.292
203962AF1-287 GEN
Solar/Wind Harmer
0.961
20334926Z1-069 C
Solar/Wind Harmer
0.981
203854AF2-039 C
Solar/Wind Harmer
0.187
238202AE2-262_GEN
Solar/Wind Harmer
1.12
971627AH1-313 GEN
Solar/Wind Harmer
4.389
203948AG1-140 C
Solar/Wind Harmer
0.114
20060826PINEY #1
50/50
0.059
970663AG2-429 GEN
Solar/Wind Harmer
9.339
970663AG2-429 GEN
Solar/Wind Harmer
1.52
971055AG2-654 GEN
Solar/Wind Harmer
1.148
203846AF2-130 C
Solar/Wind Harmer
0.509
20083226HNSMLK 5
Adder
4.379
20083926HOMER C3
Adder
40.151
20083826HOMER C2
Adder
37.927
970677AG2-438 GEN
Solar/Wind Harmer
0.546
966771AG1-548 GEN
Solar/Wind Harmer
7.806
966771AG1-548 GEN
Solar/Wind Harmer
1.513
203804AE2-113_GEN
Solar/Wind Harmer
2.528
940863AE2-074 GEN
Solar/Wind Harmer
0.855
203855AF2-088 C
Solar/Wind Harmer
0.09
20083726HOMER C1
Adder
22.048
23513401AL&D6
50/50
0.029
946381AF1-302 GEN
Solar/Wind Harmer
2.238
203848AF2-166 C
Solar/Wind Harmer
1.782
238217AF1-153 C O1
Solar/Wind Harmer
0.407
203979AG1-198 GEN
Solar/Wind Harmer
0.198
971933AH1-491 GEN
Solar/Wind Harmer
1.092
203980AG1-197 GEN
Solar/Wind Harmer
0.242
972075AH1-587 GEN
Solar/Wind Harmer
10.438
972077AH1-588 GEN
Solar/Wind Harmer
12.308
972079AH1-589 GEN
Solar/Wind Harmer
10.138
970715AG2-457 GEN
Solar/Wind Harmer
4.103
970305AG2-200 GEN
Solar/Wind Harmer
0.98
971931AH1-490 GEN
Solar/Wind Harmer
0.967
203963AG1-253 GEN
Solar/Wind Harmer
0.173
203947AF1-006 C
Solar/Wind Harmer
0.241
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.185
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.576
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.519
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.822
G-007ALTFEXP_G-007A->PJM
CMTX
1.254
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.055
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.37 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:218.0
MW Contribution:0.45
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.064
203932AE1-123
50/50
2.029
20082926HNSMLK 2
50/50
4.644
20083126HNSMLK 4
50/50
4.644
238219AF1-167 C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
1.71
971355AH1-158 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
1.096
945751AF1-240 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
2.963
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.714
971707AH1-359 GEN
Solar/Wind Harmer
0.714
20120126WRREN CT
Adder
3.096
203962AF1-287 GEN
Solar/Wind Harmer
0.671
20334926Z1-069 C
Solar/Wind Harmer
0.245
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.054
203948AG1-140 C
Solar/Wind Harmer
0.086
23513401AL&D6
50/50
0.029
203848AF2-166 C
Solar/Wind Harmer
1.242
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.762
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.269
972077AH1-588 GEN
Solar/Wind Harmer
8.573
972079AH1-589 GEN
Solar/Wind Harmer
10.121
970715AG2-457 GEN
Solar/Wind Harmer
3.322
970305AG2-200 GEN
Solar/Wind Harmer
0.683
971931AH1-490 GEN
Solar/Wind Harmer
0.675
203963AG1-253 GEN
Solar/Wind Harmer
0.136
203947AF1-006 C
Solar/Wind Harmer
0.021
20060826PINEY #1
50/50
0.059
20066226SCRUB GR
50/50
0.413
20083226HNSMLK 5
50/50
4.644
970663AG2-429 GEN
Solar/Wind Harmer
6.947
970663AG2-429 GEN
Solar/Wind Harmer
1.518
971055AG2-654 GEN
Solar/Wind Harmer
0.933
20083926HOMER C3
Adder
40.066
20083826HOMER C2
Adder
37.847
970677AG2-438 GEN
Solar/Wind Harmer
0.425
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.553
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.944
20060826PINEY #1
50/50
0.066
20082826HNSMLK 1
50/50
4.644
20083026HNSMLK 3
50/50
4.644
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.85
970647AG2-420 GEN
Solar/Wind Harmer
0.183
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.126
970713AG2-456 GEN
Solar/Wind Harmer
3.322
971705AH1-358 GEN
Solar/Wind Harmer
1.191
971709AH1-360 GEN
Solar/Wind Harmer
1.191
203954AE2-126 C
Solar/Wind Harmer
0.001
203813AE2-344_GEN
Solar/Wind Harmer
3.887
20072226SHAWVL 2
Adder
6.494
971865AH1-452 GEN
Solar/Wind Harmer
0.451
20091326SHAW-D
Adder
0.3
972169AH1-667 GEN
Solar/Wind Harmer
0.574
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.146
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.178
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.554
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.79
G-007ALTFEXP_G-007A->PJM
CMTX
1.215
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.982
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.03 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:202.39
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.018
20060826PINEY #1
50/50
0.065
203932AE1-123
50/50
2.068
203848AF2-166 C
Solar/Wind Harmer
1.265
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.775
203980AG1-197 GEN
Solar/Wind Harmer
0
972075AH1-587 GEN
Solar/Wind Harmer
7.424
20060826PINEY #1
50/50
0.06
20066226SCRUB GR
50/50
0.421
20083226HNSMLK 5
50/50
4.728
970663AG2-429 GEN
Solar/Wind Harmer
7.068
970663AG2-429 GEN
Solar/Wind Harmer
1.545
971055AG2-654 GEN
Solar/Wind Harmer
0.966
20083926HOMER C3
Adder
40.966
20083826HOMER C2
Adder
38.697
970677AG2-438 GEN
Solar/Wind Harmer
0.433
966771AG1-548 GEN
Solar/Wind Harmer
1.265
966771AG1-548 GEN
Solar/Wind Harmer
1.581
203804AE2-113_GEN
Solar/Wind Harmer
0.003
203855AF2-088 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.086
20083726HOMER C1
Adder
22.622
20060826PINEY #1
50/50
0.068
20082826HNSMLK 1
50/50
4.728
20083026HNSMLK 3
50/50
4.728
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
0.186
203860AG1-193 C
Solar/Wind Harmer
0
970267AG2-176 GEN
Solar/Wind Harmer
6.236
970713AG2-456 GEN
Solar/Wind Harmer
3.392
971705AH1-358 GEN
Solar/Wind Harmer
1.216
971709AH1-360 GEN
Solar/Wind Harmer
1.216
203954AE2-126 C
Solar/Wind Harmer
0.001
971865AH1-452 GEN
Solar/Wind Harmer
0.487
203813AE2-344_GEN
Solar/Wind Harmer
3.956
20072226SHAWVL 2
Adder
6.64
20091326SHAW-D
Adder
0.308
972169AH1-667 GEN
Solar/Wind Harmer
0.587
203835AF1-098 GEN
Solar/Wind Harmer
0.002
238206AE2-263_GEN
Solar/Wind Harmer
0.002
20084926LAKVU GN
Adder
0.077
20082926HNSMLK 2
50/50
4.728
20083126HNSMLK 4
50/50
4.728
238219AF1-167 C
Solar/Wind Harmer
1.237
971185AH1-051 GEN
Solar/Wind Harmer
1.742
971355AH1-158 GEN
Solar/Wind Harmer
2.903
970647AG2-420 GEN
Solar/Wind Harmer
1.116
945751AF1-240 GEN
Solar/Wind Harmer
0.929
957161AF2-010 GEN
Solar/Wind Harmer
3.017
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.73
971707AH1-359 GEN
Solar/Wind Harmer
0.73
20120126WRREN CT
Adder
3.157
203962AF1-287 GEN
Solar/Wind Harmer
0.682
20334926Z1-069 C
Solar/Wind Harmer
0.251
203854AF2-039 C
Solar/Wind Harmer
0
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.124
203948AG1-140 C
Solar/Wind Harmer
0.087
20084926LAKVU GN
Adder
0.077
960051AF2-296 GEN
Solar/Wind Harmer
0.603
972077AH1-588 GEN
Solar/Wind Harmer
8.754
972079AH1-589 GEN
Solar/Wind Harmer
10.335
970715AG2-457 GEN
Solar/Wind Harmer
3.392
970305AG2-200 GEN
Solar/Wind Harmer
0.697
971931AH1-490 GEN
Solar/Wind Harmer
0.686
203963AG1-253 GEN
Solar/Wind Harmer
0.139
203947AF1-006 C
Solar/Wind Harmer
0.021
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.187
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.58
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.599
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.826
G-007ALTFEXP_G-007A->PJM
CMTX
1.282
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.258
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KARNSC-01BUTLER 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KARNSC-01BUTLER 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.11 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:245.97
MW Contribution:0.75
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.015
20060826PINEY #1
50/50
0.096
203932AE1-123
50/50
3.054
238219AF1-167 C
Solar/Wind Harmer
2.467
971185AH1-051 GEN
Solar/Wind Harmer
2.737
971355AH1-158 GEN
Solar/Wind Harmer
3.182
203856AF2-165 C
Solar/Wind Harmer
1.308
945751AF1-240 GEN
Solar/Wind Harmer
1.69
970647AG2-420 GEN
Solar/Wind Harmer
2.12
959441AF2-235 GEN
Solar/Wind Harmer
0.292
20082926HNSMLK 2
Adder
4.424
20083126HNSMLK 4
Adder
4.424
957161AF2-010 GEN
Solar/Wind Harmer
5.269
203830AF1-094 GEN
Solar/Wind Harmer
0.406
970899AG2-561 GEN
Solar/Wind Harmer
1.157
203818AF1-086 GEN
Solar/Wind Harmer
1.427
960051AF2-296 GEN
Solar/Wind Harmer
1.105
971703AH1-357 GEN
Solar/Wind Harmer
1.104
971707AH1-359 GEN
Solar/Wind Harmer
1.104
203854AF2-039 C
Solar/Wind Harmer
0.223
20120126WRREN CT
Adder
3.436
962511AG1-100 GEN
Solar/Wind Harmer
0.326
203962AF1-287 GEN
Solar/Wind Harmer
1.074
238202AE2-262_GEN
Solar/Wind Harmer
1.299
971627AH1-313 GEN
Solar/Wind Harmer
5.092
20334926Z1-069 C
Solar/Wind Harmer
1.043
965131AG1-378 GEN
Solar/Wind Harmer
0.96
203948AG1-140 C
Solar/Wind Harmer
0.125
20084926LAKVU GN
Adder
0.083
20060826PINEY #1
50/50
0.1
971183AH1-050 GEN
Solar/Wind Harmer
4.561
238183AE2-316 GEN
Solar/Wind Harmer
4.499
970647AG2-420 GEN
Solar/Wind Harmer
0.247
203860AG1-193 C
Solar/Wind Harmer
0.268
20082826HNSMLK 1
Adder
4.424
20083026HNSMLK 3
Adder
4.424
970267AG2-176 GEN
Solar/Wind Harmer
9.922
961971AG1-040 GEN
Solar/Wind Harmer
0.356
203954AE2-126 C
Solar/Wind Harmer
0.353
20072226SHAWVL 2
Adder
7.607
970713AG2-456 GEN
Solar/Wind Harmer
4.417
971705AH1-358 GEN
Solar/Wind Harmer
1.284
971709AH1-360 GEN
Solar/Wind Harmer
1.284
20091326SHAW-D
Adder
0.358
972169AH1-667 GEN
Solar/Wind Harmer
0.981
203813AE2-344_GEN
Solar/Wind Harmer
6.223
238206AE2-263_GEN
Solar/Wind Harmer
1.211
203835AF1-098 GEN
Solar/Wind Harmer
1.215
20084926LAKVU GN
Adder
0.083
20094526CT_V3-030
Solar/Wind Harmer
0.318
971865AH1-452 GEN
Solar/Wind Harmer
0.749
238215AE2-248 C
Solar/Wind Harmer
0.694
20326126BLOSSBCT
Adder
0.986
203848AF2-166 C
Solar/Wind Harmer
2.585
946381AF1-302 GEN
Solar/Wind Harmer
2.251
238217AF1-153 C O1
Solar/Wind Harmer
0.495
203979AG1-198 GEN
Solar/Wind Harmer
0.244
971933AH1-491 GEN
Solar/Wind Harmer
1.34
203980AG1-197 GEN
Solar/Wind Harmer
0.272
972075AH1-587 GEN
Solar/Wind Harmer
11.458
203853AF1-134 C O1
Solar/Wind Harmer
0.334
972077AH1-588 GEN
Solar/Wind Harmer
13.25
972079AH1-589 GEN
Solar/Wind Harmer
10.913
970715AG2-457 GEN
Solar/Wind Harmer
4.417
970305AG2-200 GEN
Solar/Wind Harmer
1.087
20060826PINEY #1
50/50
0.088
20066226SCRUB GR
50/50
0.554
970663AG2-429 GEN
Solar/Wind Harmer
12.229
970663AG2-429 GEN
Solar/Wind Harmer
1.991
203846AF2-130 C
Solar/Wind Harmer
0.738
20083226HNSMLK 5
Adder
4.424
970677AG2-438 GEN
Solar/Wind Harmer
0.67
966771AG1-548 GEN
Solar/Wind Harmer
9.498
966771AG1-548 GEN
Solar/Wind Harmer
1.841
203804AE2-113_GEN
Solar/Wind Harmer
2.797
20083926HOMER C3
Adder
40.376
20083826HOMER C2
Adder
38.14
203855AF2-088 C
Solar/Wind Harmer
0.107
940863AE2-074 GEN
Solar/Wind Harmer
0.914
965121AG1-377 GEN
Solar/Wind Harmer
0.96
20084926LAKVU GN
Adder
0.093
971055AG2-654 GEN
Solar/Wind Harmer
0.56
20083726HOMER C1
Adder
23.686
971931AH1-490 GEN
Solar/Wind Harmer
1.079
203952AE2-129 C
Solar/Wind Harmer
0.291
203946AE2-131 C
Solar/Wind Harmer
0.29
962411AG1-090 GEN
Solar/Wind Harmer
4.559
203947AF1-006 C
Solar/Wind Harmer
0.267
203963AG1-253 GEN
Solar/Wind Harmer
0.191
216419AE2-001 C
Solar/Wind Harmer
0.889
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.149
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.184
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.571
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.016
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.096
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.815
G-007ALTFEXP_G-007A->PJM
CMTX
1.066
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.208
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-171A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-171A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.95 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:224.92
MW Contribution:1.04
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.017
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.882
238219AF1-167 C
Solar/Wind Harmer
1.621
971185AH1-051 GEN
Solar/Wind Harmer
1.834
971355AH1-158 GEN
Solar/Wind Harmer
2.132
203856AF2-165 C
Solar/Wind Harmer
0.88
970647AG2-420 GEN
Solar/Wind Harmer
1.45
20082926HNSMLK 2
Adder
4.017
20083126HNSMLK 4
Adder
4.017
945751AF1-240 GEN
Solar/Wind Harmer
1.058
959441AF2-235 GEN
Solar/Wind Harmer
0.2
957161AF2-010 GEN
Solar/Wind Harmer
3.922
203830AF1-094 GEN
Solar/Wind Harmer
0.304
971703AH1-357 GEN
Solar/Wind Harmer
0.96
971707AH1-359 GEN
Solar/Wind Harmer
0.96
20120126WRREN CT
Adder
2.873
962511AG1-100 GEN
Solar/Wind Harmer
0.267
20334926Z1-069 C
Solar/Wind Harmer
0.923
203962AF1-287 GEN
Solar/Wind Harmer
0.88
203854AF2-039 C
Solar/Wind Harmer
0.178
20060826PINEY #1
50/50
0.054
971055AG2-654 GEN
Solar/Wind Harmer
1.941
970663AG2-429 GEN
Solar/Wind Harmer
8.56
970663AG2-429 GEN
Solar/Wind Harmer
1.393
203846AF2-130 C
Solar/Wind Harmer
0.471
20083226HNSMLK 5
Adder
4.017
20083926HOMER C3
Adder
37.859
20083826HOMER C2
Adder
35.762
970677AG2-438 GEN
Solar/Wind Harmer
0.502
203804AE2-113_GEN
Solar/Wind Harmer
2.367
966771AG1-548 GEN
Solar/Wind Harmer
7.17
966771AG1-548 GEN
Solar/Wind Harmer
1.39
940863AE2-074 GEN
Solar/Wind Harmer
0.802
203855AF2-088 C
Solar/Wind Harmer
0.086
20083726HOMER C1
Adder
21.851
946381AF1-302 GEN
Solar/Wind Harmer
2.052
203848AF2-166 C
Solar/Wind Harmer
1.648
238217AF1-153 C O1
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.182
971933AH1-491 GEN
Solar/Wind Harmer
1.003
203980AG1-197 GEN
Solar/Wind Harmer
0.222
972075AH1-587 GEN
Solar/Wind Harmer
9.777
972077AH1-588 GEN
Solar/Wind Harmer
11.519
972079AH1-589 GEN
Solar/Wind Harmer
9.487
970715AG2-457 GEN
Solar/Wind Harmer
3.84
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.102
971183AH1-050 GEN
Solar/Wind Harmer
3.056
970647AG2-420 GEN
Solar/Wind Harmer
0.169
20082826HNSMLK 1
Adder
4.017
20083026HNSMLK 3
Adder
4.017
203860AG1-193 C
Solar/Wind Harmer
0.198
971865AH1-452 GEN
Solar/Wind Harmer
1.037
970267AG2-176 GEN
Solar/Wind Harmer
8.052
970713AG2-456 GEN
Solar/Wind Harmer
3.84
971705AH1-358 GEN
Solar/Wind Harmer
1.116
971709AH1-360 GEN
Solar/Wind Harmer
1.116
961971AG1-040 GEN
Solar/Wind Harmer
0.29
203954AE2-126 C
Solar/Wind Harmer
0.286
20072226SHAWVL 2
Adder
6.146
203813AE2-344_GEN
Solar/Wind Harmer
5.098
20091326SHAW-D
Adder
0.286
972169AH1-667 GEN
Solar/Wind Harmer
0.783
970305AG2-200 GEN
Solar/Wind Harmer
0.909
971931AH1-490 GEN
Solar/Wind Harmer
0.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.145
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.903
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.9
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-054A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-054A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:148.43 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:224.13
MW Contribution:0.98
Bus #Bus NameTypeMW Contribution
946381AF1-302 GEN
Solar/Wind Harmer
2.041
203848AF2-166 C
Solar/Wind Harmer
1.637
238217AF1-153 C O1
Solar/Wind Harmer
0.376
203979AG1-198 GEN
Solar/Wind Harmer
0.181
971933AH1-491 GEN
Solar/Wind Harmer
0.997
972075AH1-587 GEN
Solar/Wind Harmer
9.722
203980AG1-197 GEN
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
11.454
972079AH1-589 GEN
Solar/Wind Harmer
9.434
970715AG2-457 GEN
Solar/Wind Harmer
3.818
970305AG2-200 GEN
Solar/Wind Harmer
0.904
971931AH1-490 GEN
Solar/Wind Harmer
0.879
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
238219AF1-167 C
Solar/Wind Harmer
1.603
971185AH1-051 GEN
Solar/Wind Harmer
1.822
971355AH1-158 GEN
Solar/Wind Harmer
2.119
203856AF2-165 C
Solar/Wind Harmer
0.874
970647AG2-420 GEN
Solar/Wind Harmer
1.441
20082926HNSMLK 2
Adder
3.994
20083126HNSMLK 4
Adder
3.994
945751AF1-240 GEN
Solar/Wind Harmer
1.051
959441AF2-235 GEN
Solar/Wind Harmer
0.199
957161AF2-010 GEN
Solar/Wind Harmer
3.898
203830AF1-094 GEN
Solar/Wind Harmer
0.302
971703AH1-357 GEN
Solar/Wind Harmer
0.955
971707AH1-359 GEN
Solar/Wind Harmer
0.955
20120126WRREN CT
Adder
2.857
962511AG1-100 GEN
Solar/Wind Harmer
0.266
20334926Z1-069 C
Solar/Wind Harmer
0.918
203962AF1-287 GEN
Solar/Wind Harmer
0.874
203854AF2-039 C
Solar/Wind Harmer
0.177
20060826PINEY #1
50/50
0.054
970663AG2-429 GEN
Solar/Wind Harmer
8.508
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.468
20083226HNSMLK 5
Adder
3.994
20083926HOMER C3
Adder
37.654
20083826HOMER C2
Adder
35.569
970677AG2-438 GEN
Solar/Wind Harmer
0.499
203804AE2-113_GEN
Solar/Wind Harmer
2.354
966771AG1-548 GEN
Solar/Wind Harmer
7.126
20060826PINEY #1
50/50
0.061
238183AE2-316 GEN
Solar/Wind Harmer
4.079
971183AH1-050 GEN
Solar/Wind Harmer
3.037
970647AG2-420 GEN
Solar/Wind Harmer
0.168
20082826HNSMLK 1
Adder
3.994
20083026HNSMLK 3
Adder
3.994
203860AG1-193 C
Solar/Wind Harmer
0.197
971865AH1-452 GEN
Solar/Wind Harmer
0.981
970267AG2-176 GEN
Solar/Wind Harmer
8.004
970713AG2-456 GEN
Solar/Wind Harmer
3.818
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
961971AG1-040 GEN
Solar/Wind Harmer
0.288
203954AE2-126 C
Solar/Wind Harmer
0.284
20072226SHAWVL 2
Adder
6.111
203813AE2-344_GEN
Solar/Wind Harmer
5.068
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.779
966771AG1-548 GEN
Solar/Wind Harmer
1.381
940863AE2-074 GEN
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.085
20083726HOMER C1
Adder
21.738
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.633
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.31 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:213.37
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.437
20082926HNSMLK 2
Adder
4.153
20083126HNSMLK 4
Adder
4.153
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.944
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.153
20083026HNSMLK 3
Adder
4.153
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.971
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.347
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.448
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.168
971709AH1-360 GEN
Solar/Wind Harmer
1.168
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.153
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.339
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.758
20083826HOMER C2
Adder
32.833
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.408
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.049
972079AH1-589 GEN
Solar/Wind Harmer
9.924
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.883
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.817
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.926
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.178
G-007ALTFEXP_G-007A->PJM
CMTX
1.778
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.31 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:213.37
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.267
203932AE1-123
Adder
1.515
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
0.86
970647AG2-420 GEN
Solar/Wind Harmer
1.437
20082926HNSMLK 2
Adder
4.153
20083126HNSMLK 4
Adder
4.153
959441AF2-235 GEN
Solar/Wind Harmer
0.21
957161AF2-010 GEN
Solar/Wind Harmer
4.969
203830AF1-094 GEN
Solar/Wind Harmer
0.389
962511AG1-100 GEN
Solar/Wind Harmer
0.383
203962AF1-287 GEN
Solar/Wind Harmer
1.261
20084926LAKVU GN
Adder
0.106
945751AF1-240 GEN
Solar/Wind Harmer
0.941
203948AG1-140 C
Solar/Wind Harmer
0.156
20120126WRREN CT
Adder
3.485
971703AH1-357 GEN
Solar/Wind Harmer
1.004
971707AH1-359 GEN
Solar/Wind Harmer
1.004
20334926Z1-069 C
Solar/Wind Harmer
0.936
238183AE2-316 GEN
Solar/Wind Harmer
3.338
971183AH1-050 GEN
Solar/Wind Harmer
2.944
970647AG2-420 GEN
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
4.153
20083026HNSMLK 3
Adder
4.153
203860AG1-193 C
Solar/Wind Harmer
0.212
970267AG2-176 GEN
Solar/Wind Harmer
9.971
961971AG1-040 GEN
Solar/Wind Harmer
0.39
203813AE2-344_GEN
Solar/Wind Harmer
7.347
20084926LAKVU GN
Adder
0.106
203835AF1-098 GEN
Solar/Wind Harmer
1.448
971865AH1-452 GEN
Solar/Wind Harmer
1.001
970713AG2-456 GEN
Solar/Wind Harmer
4.016
971705AH1-358 GEN
Solar/Wind Harmer
1.168
971709AH1-360 GEN
Solar/Wind Harmer
1.168
203954AE2-126 C
Solar/Wind Harmer
0.277
970663AG2-429 GEN
Solar/Wind Harmer
6.686
970663AG2-429 GEN
Solar/Wind Harmer
1.088
971055AG2-654 GEN
Solar/Wind Harmer
0.968
203846AF2-130 C
Solar/Wind Harmer
0.426
20083226HNSMLK 5
Adder
4.153
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.339
966771AG1-548 GEN
Solar/Wind Harmer
1.81
20084926LAKVU GN
Adder
0.12
203804AE2-113_GEN
Solar/Wind Harmer
2.377
20083926HOMER C3
Adder
34.758
20083826HOMER C2
Adder
32.833
940863AE2-074 GEN
Solar/Wind Harmer
0.819
20083726HOMER C1
Adder
21.408
946381AF1-302 GEN
Solar/Wind Harmer
1.67
203848AF2-166 C
Solar/Wind Harmer
1.492
203980AG1-197 GEN
Solar/Wind Harmer
0.295
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
971931AH1-490 GEN
Solar/Wind Harmer
1.267
203947AF1-006 C
Solar/Wind Harmer
0.344
203963AG1-253 GEN
Solar/Wind Harmer
0.238
238217AF1-153 C O1
Solar/Wind Harmer
0.34
970305AG2-200 GEN
Solar/Wind Harmer
1.102
972077AH1-588 GEN
Solar/Wind Harmer
12.049
972079AH1-589 GEN
Solar/Wind Harmer
9.924
970715AG2-457 GEN
Solar/Wind Harmer
4.016
972075AH1-587 GEN
Solar/Wind Harmer
9.883
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.817
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.926
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.178
G-007ALTFEXP_G-007A->PJM
CMTX
1.778
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.56
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.47 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:207.58
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.547
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.074
971707AH1-359 GEN
Solar/Wind Harmer
1.074
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.6
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.874
944411AF1-106 GEN
Solar/Wind Harmer
0.098
238183AE2-316 GEN
Solar/Wind Harmer
3.31
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.578
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.295
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.559
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.986
944411AF1-106 GEN
Solar/Wind Harmer
0.908
970663AG2-429 GEN
Solar/Wind Harmer
6.704
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.748
20083826HOMER C2
Adder
48.882
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.646
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.915
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.884
972079AH1-589 GEN
Solar/Wind Harmer
10.611
970715AG2-457 GEN
Solar/Wind Harmer
4.295
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.317
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.925
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.11
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.126
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.393
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.631
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.558
G-007ALTFEXP_G-007A->PJM
CMTX
0.926
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-3_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.47 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:207.58
MW Contribution:1.0
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.012
238219AF1-167 C
Solar/Wind Harmer
1.255
203932AE1-123
Adder
1.415
20082926HNSMLK 2
Adder
3.849
20083126HNSMLK 4
Adder
3.849
971185AH1-051 GEN
Solar/Wind Harmer
1.547
971355AH1-158 GEN
Solar/Wind Harmer
1.798
203856AF2-165 C
Solar/Wind Harmer
0.745
970647AG2-420 GEN
Solar/Wind Harmer
1.238
959441AF2-235 GEN
Solar/Wind Harmer
0.173
971703AH1-357 GEN
Solar/Wind Harmer
1.074
971707AH1-359 GEN
Solar/Wind Harmer
1.074
945751AF1-240 GEN
Solar/Wind Harmer
0.82
20334926Z1-069 C
Solar/Wind Harmer
1.063
957161AF2-010 GEN
Solar/Wind Harmer
3.6
203830AF1-094 GEN
Solar/Wind Harmer
0.28
20120126WRREN CT
Adder
2.874
944411AF1-106 GEN
Solar/Wind Harmer
0.098
238183AE2-316 GEN
Solar/Wind Harmer
3.31
20082826HNSMLK 1
Adder
3.849
20083026HNSMLK 3
Adder
3.849
971183AH1-050 GEN
Solar/Wind Harmer
2.578
970647AG2-420 GEN
Solar/Wind Harmer
0.144
971865AH1-452 GEN
Solar/Wind Harmer
1.002
203860AG1-193 C
Solar/Wind Harmer
0.177
970713AG2-456 GEN
Solar/Wind Harmer
4.295
971705AH1-358 GEN
Solar/Wind Harmer
1.248
971709AH1-360 GEN
Solar/Wind Harmer
1.248
970267AG2-176 GEN
Solar/Wind Harmer
7.559
961971AG1-040 GEN
Solar/Wind Harmer
0.276
20326126BLOSSBCT
Adder
0.995
20335026MILZ1-092
Adder
0.986
944411AF1-106 GEN
Solar/Wind Harmer
0.908
970663AG2-429 GEN
Solar/Wind Harmer
6.704
970663AG2-429 GEN
Solar/Wind Harmer
1.091
971055AG2-654 GEN
Solar/Wind Harmer
0.967
20083926HOMER C3
Adder
51.748
20083826HOMER C2
Adder
48.882
203846AF2-130 C
Solar/Wind Harmer
0.385
20083226HNSMLK 5
Adder
3.849
940863AE2-074 GEN
Solar/Wind Harmer
0.912
203804AE2-113_GEN
Solar/Wind Harmer
2.434
970677AG2-438 GEN
Solar/Wind Harmer
0.462
966771AG1-548 GEN
Solar/Wind Harmer
6.646
966771AG1-548 GEN
Solar/Wind Harmer
1.288
20083726HOMER C1
Adder
3.915
946381AF1-302 GEN
Solar/Wind Harmer
1.656
203848AF2-166 C
Solar/Wind Harmer
1.347
972077AH1-588 GEN
Solar/Wind Harmer
12.884
972079AH1-589 GEN
Solar/Wind Harmer
10.611
970715AG2-457 GEN
Solar/Wind Harmer
4.295
238217AF1-153 C O1
Solar/Wind Harmer
0.32
972075AH1-587 GEN
Solar/Wind Harmer
10.317
203980AG1-197 GEN
Solar/Wind Harmer
0.211
203979AG1-198 GEN
Solar/Wind Harmer
0.168
971933AH1-491 GEN
Solar/Wind Harmer
0.925
970305AG2-200 GEN
Solar/Wind Harmer
0.909
20398826ARMNA MT
Solar/Wind Harmer
1.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.11
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.126
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.393
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.631
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.558
G-007ALTFEXP_G-007A->PJM
CMTX
0.926
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.95 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:181.13
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
20060826PINEY #1
50/50
0.061
20082826HNSMLK 1
50/50
4.239
20083026HNSMLK 3
50/50
4.239
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971183AH1-050 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
0.168
203860AG1-193 C
Solar/Wind Harmer
0
971865AH1-452 GEN
Solar/Wind Harmer
0.564
970267AG2-176 GEN
Solar/Wind Harmer
5.584
970713AG2-456 GEN
Solar/Wind Harmer
3.097
971705AH1-358 GEN
Solar/Wind Harmer
1.11
971709AH1-360 GEN
Solar/Wind Harmer
1.11
203954AE2-126 C
Solar/Wind Harmer
0
20072226SHAWVL 2
Adder
6.111
203813AE2-344_GEN
Solar/Wind Harmer
3.536
20091326SHAW-D
Adder
0.284
972169AH1-667 GEN
Solar/Wind Harmer
0.543
23503001MHNG-T155
50/50
0.016
20060826PINEY #1
50/50
0.059
203932AE1-123
50/50
1.87
20082926HNSMLK 2
50/50
4.239
20083126HNSMLK 4
50/50
4.239
238219AF1-167 C
Solar/Wind Harmer
1.117
971185AH1-051 GEN
Solar/Wind Harmer
1.57
971355AH1-158 GEN
Solar/Wind Harmer
2.617
970647AG2-420 GEN
Solar/Wind Harmer
1.005
945751AF1-240 GEN
Solar/Wind Harmer
0.854
957161AF2-010 GEN
Solar/Wind Harmer
2.708
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971703AH1-357 GEN
Solar/Wind Harmer
0.666
971707AH1-359 GEN
Solar/Wind Harmer
0.666
20120126WRREN CT
Adder
2.857
20334926Z1-069 C
Solar/Wind Harmer
0.23
203962AF1-287 GEN
Solar/Wind Harmer
0.61
203854AF2-039 C
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
1.142
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.696
972075AH1-587 GEN
Solar/Wind Harmer
6.783
203980AG1-197 GEN
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
7.991
972079AH1-589 GEN
Solar/Wind Harmer
9.434
970715AG2-457 GEN
Solar/Wind Harmer
3.097
970305AG2-200 GEN
Solar/Wind Harmer
0.63
971931AH1-490 GEN
Solar/Wind Harmer
0.613
20060826PINEY #1
50/50
0.054
20066226SCRUB GR
50/50
0.379
20083226HNSMLK 5
50/50
4.239
970663AG2-429 GEN
Solar/Wind Harmer
6.337
970663AG2-429 GEN
Solar/Wind Harmer
1.385
971055AG2-654 GEN
Solar/Wind Harmer
1.082
20083926HOMER C3
Adder
37.654
20083826HOMER C2
Adder
35.569
970677AG2-438 GEN
Solar/Wind Harmer
0.388
203804AE2-113_GEN
Solar/Wind Harmer
0.003
966771AG1-548 GEN
Solar/Wind Harmer
1.134
966771AG1-548 GEN
Solar/Wind Harmer
1.418
203855AF2-088 C
Solar/Wind Harmer
0
20083726HOMER C1
Adder
21.738
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.633
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.099
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
G-007ALTFEXP_G-007A->PJM
CMTX
1.487
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:158.22
MW Contribution:1.68
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.018
238219AF1-167 C
Solar/Wind Harmer
1.452
203932AE1-123
Adder
1.503
971185AH1-051 GEN
Solar/Wind Harmer
1.549
971355AH1-158 GEN
Solar/Wind Harmer
1.801
203856AF2-165 C
Solar/Wind Harmer
0.743
970647AG2-420 GEN
Solar/Wind Harmer
1.224
945751AF1-240 GEN
Solar/Wind Harmer
0.922
20082926HNSMLK 2
Adder
3.366
20083126HNSMLK 4
Adder
3.366
959441AF2-235 GEN
Solar/Wind Harmer
0.169
971703AH1-357 GEN
Solar/Wind Harmer
0.821
971865AH1-452 GEN
Solar/Wind Harmer
1.68
238183AE2-316 GEN
Solar/Wind Harmer
3.43
971183AH1-050 GEN
Solar/Wind Harmer
2.582
970647AG2-420 GEN
Solar/Wind Harmer
0.142
20082826HNSMLK 1
Adder
3.366
20083026HNSMLK 3
Adder
3.366
203860AG1-193 C
Solar/Wind Harmer
0.167
970267AG2-176 GEN
Solar/Wind Harmer
6.755
970713AG2-456 GEN
Solar/Wind Harmer
3.283
971705AH1-358 GEN
Solar/Wind Harmer
0.954
971709AH1-360 GEN
Solar/Wind Harmer
0.954
971707AH1-359 GEN
Solar/Wind Harmer
0.821
946381AF1-302 GEN
Solar/Wind Harmer
1.716
203848AF2-166 C
Solar/Wind Harmer
1.395
238217AF1-153 C O1
Solar/Wind Harmer
0.322
972075AH1-587 GEN
Solar/Wind Harmer
8.367
972077AH1-588 GEN
Solar/Wind Harmer
9.849
972079AH1-589 GEN
Solar/Wind Harmer
8.112
970715AG2-457 GEN
Solar/Wind Harmer
3.283
971055AG2-654 GEN
Solar/Wind Harmer
1.558
970663AG2-429 GEN
Solar/Wind Harmer
7.159
970663AG2-429 GEN
Solar/Wind Harmer
1.165
203846AF2-130 C
Solar/Wind Harmer
0.398
20083226HNSMLK 5
Adder
3.366
20083926HOMER C3
Adder
32.602
20083826HOMER C2
Adder
30.796
20083726HOMER C1
Adder
19.756
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.133
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.19
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.591
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.875
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.088
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.842
G-007ALTFEXP_G-007A->PJM
CMTX
1.394
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.662
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-055_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-055_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.82 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:155.25
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
23503001MHNG-T155
50/50
0.013
238219AF1-167 C
Solar/Wind Harmer
1.314
203932AE1-123
Adder
1.455
971185AH1-051 GEN
Solar/Wind Harmer
1.499
971355AH1-158 GEN
Solar/Wind Harmer
1.743
203856AF2-165 C
Solar/Wind Harmer
0.719
970647AG2-420 GEN
Solar/Wind Harmer
1.184
945751AF1-240 GEN
Solar/Wind Harmer
0.9
20082926HNSMLK 2
Adder
3.264
20083126HNSMLK 4
Adder
3.264
959441AF2-235 GEN
Solar/Wind Harmer
0.164
971703AH1-357 GEN
Solar/Wind Harmer
0.805
971707AH1-359 GEN
Solar/Wind Harmer
0.805
971865AH1-452 GEN
Solar/Wind Harmer
1.465
238183AE2-316 GEN
Solar/Wind Harmer
3.328
971183AH1-050 GEN
Solar/Wind Harmer
2.499
970647AG2-420 GEN
Solar/Wind Harmer
0.138
20082826HNSMLK 1
Adder
3.264
20083026HNSMLK 3
Adder
3.264
203860AG1-193 C
Solar/Wind Harmer
0.162
970267AG2-176 GEN
Solar/Wind Harmer
6.53
970713AG2-456 GEN
Solar/Wind Harmer
3.219
971705AH1-358 GEN
Solar/Wind Harmer
0.936
971709AH1-360 GEN
Solar/Wind Harmer
0.936
946381AF1-302 GEN
Solar/Wind Harmer
1.665
203848AF2-166 C
Solar/Wind Harmer
1.35
238217AF1-153 C O1
Solar/Wind Harmer
0.314
972075AH1-587 GEN
Solar/Wind Harmer
8.206
972077AH1-588 GEN
Solar/Wind Harmer
9.657
972079AH1-589 GEN
Solar/Wind Harmer
7.954
970715AG2-457 GEN
Solar/Wind Harmer
3.219
971055AG2-654 GEN
Solar/Wind Harmer
1.278
970663AG2-429 GEN
Solar/Wind Harmer
6.916
970663AG2-429 GEN
Solar/Wind Harmer
1.126
203846AF2-130 C
Solar/Wind Harmer
0.386
20083226HNSMLK 5
Adder
3.264
20083926HOMER C3
Adder
32.151
20083826HOMER C2
Adder
30.371
20083726HOMER C1
Adder
19.966
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.649
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.093
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.924
G-007ALTFEXP_G-007A->PJM
CMTX
1.584
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.832
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-18201_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-18201_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.39
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-182_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-182_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.39
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-181T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-181T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.38
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-0582-1_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-0582-1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:141.33 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.36
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
961581Q1080_CY23
External Queue
19.463396072387695
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
961581Q1080_CY23
External Queue
19.46338653564453
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-A_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.16
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
961581Q1080_CY23
External Queue
19.463396072387695
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1050.42
MW Contribution:0.97
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.647
203857AF2-221 C
Solar/Wind Harmer
4.193
970123AG2-090 GEN
Solar/Wind Harmer
3.913
203839AF1-321 GEN
Solar/Wind Harmer
5.431
20084626FORWARD
Solar/Wind Harmer
2.135
971441AH1-212 GEN
Solar/Wind Harmer
5.336
203940AF1-140 C
Solar/Wind Harmer
1.313
20088626ARWF_N39
Solar/Wind Harmer
4.901
20303426NA_O38_P22
Solar/Wind Harmer
3.968
20088926STNY CRK
Solar/Wind Harmer
3.084
971427AH1-205 GEN
Solar/Wind Harmer
3.723
20083426SW_E13_K22
Solar/Wind Harmer
0.724
946071AF1-272 GEN
Solar/Wind Harmer
7.688
944781AF1-143 GEN
Solar/Wind Harmer
6.199
203853AF1-134 C O1
Solar/Wind Harmer
1.085
203952AE2-129 C
Solar/Wind Harmer
1.043
203946AE2-131 C
Solar/Wind Harmer
1.041
962411AG1-090 GEN
Solar/Wind Harmer
16.36
203955AF1-039 C O1
Solar/Wind Harmer
0.717
972077AH1-588 GEN
Solar/Wind Harmer
37.067
972079AH1-589 GEN
Solar/Wind Harmer
30.53
970715AG2-457 GEN
Solar/Wind Harmer
12.356
972075AH1-587 GEN
Solar/Wind Harmer
29.887
203848AF2-166 C
Solar/Wind Harmer
2.585
238217AF1-153 C O1
Solar/Wind Harmer
0.765
946381AF1-302 GEN
Solar/Wind Harmer
2.644
20398826ARMNA MT
Solar/Wind Harmer
2.923
970305AG2-200 GEN
Solar/Wind Harmer
2.435
203859AF2-294 C
Solar/Wind Harmer
1.92
970313AG2-206 GEN
Solar/Wind Harmer
5.384
216419AE2-001 C
Solar/Wind Harmer
2.24
203979AG1-198 GEN
Solar/Wind Harmer
0.379
971933AH1-491 GEN
Solar/Wind Harmer
2.086
203980AG1-197 GEN
Solar/Wind Harmer
0.471
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.963
203947AF1-006 C
Solar/Wind Harmer
0.52
20083326SEWRDB34
50/50
11.883
20079426CONEMAGH
50/50
3.851
970125AG2-091 GEN
Solar/Wind Harmer
1.677
971879AH1-460 GEN
Solar/Wind Harmer
18.223
203841AF2-001_GEN
Solar/Wind Harmer
5.431
971541AH1-268 GEN
Solar/Wind Harmer
9.304
971419AH1-201 GEN
Solar/Wind Harmer
8.004
970899AG2-561 GEN
Solar/Wind Harmer
4.534
203818AF1-086 GEN
Solar/Wind Harmer
5.258
20089126CSLMN_L13
Solar/Wind Harmer
1.809
20089026BF_G21_K23
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
3.589
945751AF1-240 GEN
Solar/Wind Harmer
2.752
965131AG1-378 GEN
Solar/Wind Harmer
3.444
202652Y1-033 WT C
Solar/Wind Harmer
1.474
971703AH1-357 GEN
Solar/Wind Harmer
3.089
971707AH1-359 GEN
Solar/Wind Harmer
3.089
20334926Z1-069 C
Solar/Wind Harmer
3.079
203854AF2-039 C
Solar/Wind Harmer
0.59
203932AE1-123
Adder
2.648
20082926HNSMLK 2
Adder
7.863
20083126HNSMLK 4
Adder
7.863
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.475
970647AG2-420 GEN
Solar/Wind Harmer
2.464
944411AF1-106 GEN
Solar/Wind Harmer
0.277
20120126WRREN CT
Adder
7.7
238202AE2-262_GEN
Solar/Wind Harmer
3.02
971627AH1-313 GEN
Solar/Wind Harmer
11.841
959441AF2-235 GEN
Solar/Wind Harmer
0.355
238219AF1-167 C
Solar/Wind Harmer
1.567
970335AG2-220 GEN
Solar/Wind Harmer
3.494
971127AH1-005 GEN
Solar/Wind Harmer
2.254
957161AF2-010 GEN
Solar/Wind Harmer
8.077
203830AF1-094 GEN
Solar/Wind Harmer
0.632
20335126GROZ1-110
Adder
2.405
20335226CANZ2-011
Adder
2.338
203948AG1-140 C
Solar/Wind Harmer
0.261
203962AF1-287 GEN
Solar/Wind Harmer
1.968
962511AG1-100 GEN
Solar/Wind Harmer
0.593
20084926LAKVU GN
Adder
0.167
20328326MANOR_T86
Adder
0.129
941421AE2-139 GEN
Solar/Wind Harmer
2.625
972271AH1-720 GEN
Adder
5.537
200917MEHOOPANY_G
Solar/Wind Harmer
2.511
970643AG2-418 GEN
Solar/Wind Harmer
1.331
970679AG2-439 GEN
Solar/Wind Harmer
0.553
20050326C.SLOPE
50/50
0.894
20092526R32
Solar/Wind Harmer
4.874
20083726HOMER C1
Adder
189.504
203961AE2-224 GEN
Solar/Wind Harmer
8.378
203850AG1-041 C
Solar/Wind Harmer
3.171
203844AF2-092 C
Solar/Wind Harmer
3.165
20091526CHSTN_FL
Solar/Wind Harmer
2.127
20083926HOMER C3
Adder
158.653
20083826HOMER C2
Adder
149.866
20090526Q36
Solar/Wind Harmer
3.039
203993AD2-133_GEN1
Solar/Wind Harmer
3.039
941231AE2-117 GEN
Solar/Wind Harmer
1.097
965121AG1-377 GEN
Solar/Wind Harmer
3.444
940863AE2-074 GEN
Solar/Wind Harmer
2.641
203804AE2-113_GEN
Solar/Wind Harmer
7.05
203855AF2-088 C
Solar/Wind Harmer
0.284
20083226HNSMLK 5
Adder
7.863
203846AF2-130 C
Solar/Wind Harmer
0.738
970663AG2-429 GEN
Solar/Wind Harmer
8.343
970663AG2-429 GEN
Solar/Wind Harmer
1.358
970555AG2-356 GEN
Solar/Wind Harmer
2.341
970677AG2-438 GEN
Solar/Wind Harmer
1.043
966771AG1-548 GEN
Solar/Wind Harmer
15.105
966771AG1-548 GEN
Solar/Wind Harmer
2.927
20084926LAKVU GN
Adder
0.188
971321AH1-140 GEN
Solar/Wind Harmer
12.535
971321AH1-140 GEN
Solar/Wind Harmer
2.429
203926AA2-133 GEN
Adder
1.9
20334726NME_Y1-047
Adder
1.687
20390726Y2-042
Adder
1.324
971055AG2-654 GEN
Solar/Wind Harmer
0.609
20088826HIGHLAND
Solar/Wind Harmer
4.549
957561AF2-050 GEN
Solar/Wind Harmer
13.832
203843AF2-002_GEN
Solar/Wind Harmer
2.715
970631AG2-411 GEN
Solar/Wind Harmer
17.019
971279AH1-102 GEN
Solar/Wind Harmer
21.862
964201AG1-281 GEN
Solar/Wind Harmer
1.524
971423AH1-203 GEN
Solar/Wind Harmer
17.45
20094526CT_V3-030
Solar/Wind Harmer
1.725
20089226LOOKOUT
Solar/Wind Harmer
1.761
203987AE2-118 C
Solar/Wind Harmer
3.93
964391AG1-301 GEN
Solar/Wind Harmer
1.083
970713AG2-456 GEN
Solar/Wind Harmer
12.356
971705AH1-358 GEN
Solar/Wind Harmer
3.592
971709AH1-360 GEN
Solar/Wind Harmer
3.592
20091326SHAW-D
Adder
0.949
972169AH1-667 GEN
Solar/Wind Harmer
2.597
203954AE2-126 C
Solar/Wind Harmer
0.846
20082826HNSMLK 1
Adder
7.863
20083026HNSMLK 3
Adder
7.863
20072226SHAWVL 2
Adder
17.575
238183AE2-316 GEN
Solar/Wind Harmer
5.284
971183AH1-050 GEN
Solar/Wind Harmer
5.068
20326126BLOSSBCT
Adder
2.857
970647AG2-420 GEN
Solar/Wind Harmer
0.286
20335026MILZ1-092
Adder
2.802
944411AF1-106 GEN
Solar/Wind Harmer
2.581
203860AG1-193 C
Solar/Wind Harmer
0.362
238206AE2-263_GEN
Solar/Wind Harmer
2.815
959471AF2-238 GEN
Solar/Wind Harmer
0.708
970337AG2-221 GEN
Solar/Wind Harmer
2.341
970511AG2-327 GEN
Solar/Wind Harmer
1.122
238215AE2-248 C
Solar/Wind Harmer
1.775
970267AG2-176 GEN
Solar/Wind Harmer
16.374
961971AG1-040 GEN
Solar/Wind Harmer
0.62
203835AF1-098 GEN
Solar/Wind Harmer
2.467
203813AE2-344_GEN
Solar/Wind Harmer
11.413
20084926LAKVU GN
Adder
0.167
970643AG2-418 GEN
Solar/Wind Harmer
0.619
971865AH1-452 GEN
Solar/Wind Harmer
0.967
24035802GEN-Y1-012
Adder
0.202
961581Q1080_CY23
External Queue
18.953319549560547
LGEELTFEXP_LGEE->PJM
CLTF
0.266
WECLTFEXP_WEC->PJM
CLTF
0.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.029
TVALTFEXP_TVA->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.052
MECLTFEXP_MEC->PJM
CLTF
0.688
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.439

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0183-208_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0183-208_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.22 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1033.26
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.641
203857AF2-221 C
Solar/Wind Harmer
3.95
970123AG2-090 GEN
Solar/Wind Harmer
3.686
20088626ARWF_N39
Solar/Wind Harmer
4.759
20303426NA_O38_P22
Solar/Wind Harmer
3.853
203839AF1-321 GEN
Solar/Wind Harmer
5.082
20084626FORWARD
Solar/Wind Harmer
1.999
203940AF1-140 C
Solar/Wind Harmer
1.239
971441AH1-212 GEN
Solar/Wind Harmer
4.999
20088926STNY CRK
Solar/Wind Harmer
2.892
971427AH1-205 GEN
Solar/Wind Harmer
3.492
20083426SW_E13_K22
Solar/Wind Harmer
0.678
944781AF1-143 GEN
Solar/Wind Harmer
5.802
203952AE2-129 C
Solar/Wind Harmer
0.969
203946AE2-131 C
Solar/Wind Harmer
0.968
962411AG1-090 GEN
Solar/Wind Harmer
15.203
203853AF1-134 C O1
Solar/Wind Harmer
0.925
972077AH1-588 GEN
Solar/Wind Harmer
35.86
972079AH1-589 GEN
Solar/Wind Harmer
29.536
970715AG2-457 GEN
Solar/Wind Harmer
11.953
203955AF1-039 C O1
Solar/Wind Harmer
0.671
972075AH1-587 GEN
Solar/Wind Harmer
28.698
20398826ARMNA MT
Solar/Wind Harmer
2.842
238217AF1-153 C O1
Solar/Wind Harmer
0.716
946381AF1-302 GEN
Solar/Wind Harmer
2.487
970305AG2-200 GEN
Solar/Wind Harmer
2.329
203848AF2-166 C
Solar/Wind Harmer
2.325
946071AF1-272 GEN
Solar/Wind Harmer
3.833
203859AF2-294 C
Solar/Wind Harmer
1.868
970313AG2-206 GEN
Solar/Wind Harmer
5.227
216419AE2-001 C
Solar/Wind Harmer
2.105
203980AG1-197 GEN
Solar/Wind Harmer
0.448
203979AG1-198 GEN
Solar/Wind Harmer
0.356
971933AH1-491 GEN
Solar/Wind Harmer
1.961
203963AG1-253 GEN
Solar/Wind Harmer
0.382
971931AH1-490 GEN
Solar/Wind Harmer
1.87
203947AF1-006 C
Solar/Wind Harmer
0.497
20083326SEWRDB34
50/50
11.609
20079426CONEMAGH
50/50
3.593
970125AG2-091 GEN
Solar/Wind Harmer
1.58
971879AH1-460 GEN
Solar/Wind Harmer
17.118
203841AF2-001_GEN
Solar/Wind Harmer
5.082
971419AH1-201 GEN
Solar/Wind Harmer
7.507
971541AH1-268 GEN
Solar/Wind Harmer
8.155
20089126CSLMN_L13
Solar/Wind Harmer
1.693
20089026BF_G21_K23
Solar/Wind Harmer
1.34
970899AG2-561 GEN
Solar/Wind Harmer
3.549
203818AF1-086 GEN
Solar/Wind Harmer
4.301
965131AG1-378 GEN
Solar/Wind Harmer
3.201
960051AF2-296 GEN
Solar/Wind Harmer
3.058
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
202652Y1-033 WT C
Solar/Wind Harmer
1.378
945751AF1-240 GEN
Solar/Wind Harmer
2.28
20334926Z1-069 C
Solar/Wind Harmer
2.988
203854AF2-039 C
Solar/Wind Harmer
0.541
20082926HNSMLK 2
Adder
7.58
20083126HNSMLK 4
Adder
7.58
944411AF1-106 GEN
Solar/Wind Harmer
0.27
203932AE1-123
Adder
2.352
20120126WRREN CT
Adder
7.362
971185AH1-051 GEN
Solar/Wind Harmer
2.776
971355AH1-158 GEN
Solar/Wind Harmer
3.228
203856AF2-165 C
Solar/Wind Harmer
1.349
970647AG2-420 GEN
Solar/Wind Harmer
2.262
238202AE2-262_GEN
Solar/Wind Harmer
2.83
971627AH1-313 GEN
Solar/Wind Harmer
11.095
970335AG2-220 GEN
Solar/Wind Harmer
3.393
971127AH1-005 GEN
Solar/Wind Harmer
2.189
959441AF2-235 GEN
Solar/Wind Harmer
0.327
238219AF1-167 C
Solar/Wind Harmer
1.437
20335126GROZ1-110
Adder
2.316
20335226CANZ2-011
Adder
2.251
957161AF2-010 GEN
Solar/Wind Harmer
7.586
203830AF1-094 GEN
Solar/Wind Harmer
0.594
203948AG1-140 C
Solar/Wind Harmer
0.25
203962AF1-287 GEN
Solar/Wind Harmer
1.875
962511AG1-100 GEN
Solar/Wind Harmer
0.565
20084926LAKVU GN
Adder
0.16
20328326MANOR_T86
Adder
0.125
941421AE2-139 GEN
Solar/Wind Harmer
2.528
972271AH1-720 GEN
Adder
5.344
200917MEHOOPANY_G
Solar/Wind Harmer
2.433
970643AG2-418 GEN
Solar/Wind Harmer
1.273
970679AG2-439 GEN
Solar/Wind Harmer
0.536
20083726HOMER C1
Adder
187.733
203961AE2-224 GEN
Solar/Wind Harmer
8.147
20092526R32
Solar/Wind Harmer
4.61
203850AG1-041 C
Solar/Wind Harmer
2.985
203844AF2-092 C
Solar/Wind Harmer
2.977
20091526CHSTN_FL
Solar/Wind Harmer
2.007
20083926HOMER C3
Adder
156.059
20083826HOMER C2
Adder
147.416
20090526Q36
Solar/Wind Harmer
2.845
203993AD2-133_GEN1
Solar/Wind Harmer
2.845
941231AE2-117 GEN
Solar/Wind Harmer
1.048
965121AG1-377 GEN
Solar/Wind Harmer
3.201
940863AE2-074 GEN
Solar/Wind Harmer
2.56
203804AE2-113_GEN
Solar/Wind Harmer
6.747
203855AF2-088 C
Solar/Wind Harmer
0.261
20083226HNSMLK 5
Adder
7.58
203846AF2-130 C
Solar/Wind Harmer
0.664
970555AG2-356 GEN
Solar/Wind Harmer
2.272
970663AG2-429 GEN
Solar/Wind Harmer
7.716
970663AG2-429 GEN
Solar/Wind Harmer
1.256
970677AG2-438 GEN
Solar/Wind Harmer
0.98
966771AG1-548 GEN
Solar/Wind Harmer
14.226
966771AG1-548 GEN
Solar/Wind Harmer
2.757
20084926LAKVU GN
Adder
0.18
203926AA2-133 GEN
Adder
1.839
20334726NME_Y1-047
Adder
1.634
971321AH1-140 GEN
Solar/Wind Harmer
8.786
971321AH1-140 GEN
Solar/Wind Harmer
1.703
20390726Y2-042
Adder
1.283
971055AG2-654 GEN
Solar/Wind Harmer
0.555
957561AF2-050 GEN
Solar/Wind Harmer
13.449
20088826HIGHLAND
Solar/Wind Harmer
4.302
203843AF2-002_GEN
Solar/Wind Harmer
2.541
970631AG2-411 GEN
Solar/Wind Harmer
15.933
964201AG1-281 GEN
Solar/Wind Harmer
1.443
971279AH1-102 GEN
Solar/Wind Harmer
19.163
971423AH1-203 GEN
Solar/Wind Harmer
16.357
20094526CT_V3-030
Solar/Wind Harmer
1.513
20089226LOOKOUT
Solar/Wind Harmer
1.648
203987AE2-118 C
Solar/Wind Harmer
3.76
964391AG1-301 GEN
Solar/Wind Harmer
1.036
970713AG2-456 GEN
Solar/Wind Harmer
11.953
971705AH1-358 GEN
Solar/Wind Harmer
3.475
971709AH1-360 GEN
Solar/Wind Harmer
3.475
972169AH1-667 GEN
Solar/Wind Harmer
2.382
20091326SHAW-D
Adder
0.87
203954AE2-126 C
Solar/Wind Harmer
0.787
20082826HNSMLK 1
Adder
7.58
20083026HNSMLK 3
Adder
7.58
20326126BLOSSBCT
Adder
2.771
20335026MILZ1-092
Adder
2.724
944411AF1-106 GEN
Solar/Wind Harmer
2.51
20072226SHAWVL 2
Adder
16.351
238183AE2-316 GEN
Solar/Wind Harmer
4.969
971183AH1-050 GEN
Solar/Wind Harmer
4.627
959471AF2-238 GEN
Solar/Wind Harmer
0.687
970337AG2-221 GEN
Solar/Wind Harmer
2.272
970647AG2-420 GEN
Solar/Wind Harmer
0.263
203860AG1-193 C
Solar/Wind Harmer
0.338
238206AE2-263_GEN
Solar/Wind Harmer
2.637
970511AG2-327 GEN
Solar/Wind Harmer
1.089
238215AE2-248 C
Solar/Wind Harmer
1.668
970267AG2-176 GEN
Solar/Wind Harmer
15.562
961971AG1-040 GEN
Solar/Wind Harmer
0.591
203835AF1-098 GEN
Solar/Wind Harmer
2.356
203813AE2-344_GEN
Solar/Wind Harmer
10.878
20084926LAKVU GN
Adder
0.16
970643AG2-418 GEN
Solar/Wind Harmer
0.592
971865AH1-452 GEN
Solar/Wind Harmer
0.859
24035802GEN-Y1-012
Adder
0.193
961581Q1080_CY23
External Queue
19.001585006713867
LGEELTFEXP_LGEE->PJM
CLTF
0.253
WECLTFEXP_WEC->PJM
CLTF
0.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
0.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.031
TVALTFEXP_TVA->PJM
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.002
MECLTFEXP_MEC->PJM
CLTF
0.655
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.226

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.05 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1100.29
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.04 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1100.25
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-345-001T-DRT-001_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-345-001T-DRT-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.95 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1091.2
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-2_PN-345-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-2_PN-345-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.95 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1091.2
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P2-3_PN-230-0183-207_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P2-3_PN-230-0183-207_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.11 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1067.77
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.494
972079AH1-589 GEN
Solar/Wind Harmer
50.65
970715AG2-457 GEN
Solar/Wind Harmer
20.498
972075AH1-587 GEN
Solar/Wind Harmer
44.13
20398826ARMNA MT
Solar/Wind Harmer
5.104
203859AF2-294 C
Solar/Wind Harmer
3.385
970313AG2-206 GEN
Solar/Wind Harmer
9.157
970305AG2-200 GEN
Solar/Wind Harmer
3.532
203980AG1-197 GEN
Solar/Wind Harmer
0.742
203963AG1-253 GEN
Solar/Wind Harmer
0.636
971931AH1-490 GEN
Solar/Wind Harmer
3.095
203979AG1-198 GEN
Solar/Wind Harmer
0.542
971933AH1-491 GEN
Solar/Wind Harmer
2.984
946381AF1-302 GEN
Solar/Wind Harmer
3.122
203947AF1-006 C
Solar/Wind Harmer
0.819
203848AF2-166 C
Solar/Wind Harmer
2.689
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.022
20088626ARWF_N39
Solar/Wind Helper
1.462
20303426NA_O38_P22
Solar/Wind Helper
1.199
20084626FORWARD
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.407
20088926STNY CRK
Solar/Wind Helper
0.814
20083426SW_E13_K22
Solar/Wind Helper
0.054
944781AF1-143 GEN
Solar/Wind Helper
2.029
946071AF1-272 GEN
Solar/Wind Helper
2.016
203955AF1-039 C O1
Solar/Wind Helper
0.239
20082826HNSMLK 1
50/50
14.737
20083026HNSMLK 3
50/50
14.737
20335026MILZ1-092
50/50
5.207
20326126BLOSSBCT
50/50
5.086
970713AG2-456 GEN
Solar/Wind Harmer
20.498
971705AH1-358 GEN
Solar/Wind Harmer
5.959
971709AH1-360 GEN
Solar/Wind Harmer
5.959
944411AF1-106 GEN
Solar/Wind Harmer
4.52
959471AF2-238 GEN
Solar/Wind Harmer
1.194
970337AG2-221 GEN
Solar/Wind Harmer
3.948
970511AG2-327 GEN
Solar/Wind Harmer
1.908
970267AG2-176 GEN
Solar/Wind Harmer
25.838
203860AG1-193 C
Solar/Wind Harmer
0.515
961971AG1-040 GEN
Solar/Wind Harmer
0.978
203835AF1-098 GEN
Solar/Wind Harmer
3.788
203813AE2-344_GEN
Solar/Wind Harmer
17.961
970647AG2-420 GEN
Solar/Wind Harmer
0.355
20084926LAKVU GN
Adder
0.263
971183AH1-050 GEN
Solar/Wind Harmer
6.014
238183AE2-316 GEN
Solar/Wind Harmer
6.239
203954AE2-126 C
Solar/Wind Harmer
0.637
20072226SHAWVL 2
Adder
10.919
24035802GEN-Y1-012
Adder
0.325
238206AE2-263_GEN
Solar/Wind Harmer
1.703
20091326SHAW-D
Adder
0.431
972169AH1-667 GEN
Solar/Wind Harmer
1.178
971865AH1-452 GEN
Solar/Wind Harmer
1.096
238215AE2-248 C
Solar/Wind Harmer
0.763
20088826HIGHLAND
Solar/Wind Helper
1.026
964201AG1-281 GEN
Solar/Wind Helper
0.467
20089226LOOKOUT
Solar/Wind Helper
0.476
20094526CT_V3-030
Solar/Wind Helper
0.295
964391AG1-301 GEN
Solar/Wind Helper
0.262
20082926HNSMLK 2
50/50
14.737
20083126HNSMLK 4
50/50
14.737
971703AH1-357 GEN
Solar/Wind Harmer
5.125
971707AH1-359 GEN
Solar/Wind Harmer
5.125
20334926Z1-069 C
Solar/Wind Harmer
5.297
944411AF1-106 GEN
Solar/Wind Harmer
0.486
970335AG2-220 GEN
Solar/Wind Harmer
5.951
971127AH1-005 GEN
Solar/Wind Harmer
3.839
20120126WRREN CT
Adder
11.166
203948AG1-140 C
Solar/Wind Harmer
0.417
962511AG1-100 GEN
Solar/Wind Harmer
0.936
203962AF1-287 GEN
Solar/Wind Harmer
3.094
970647AG2-420 GEN
Solar/Wind Harmer
3.055
20335126GROZ1-110
Adder
3.563
20335226CANZ2-011
Adder
3.463
20084926LAKVU GN
Adder
0.263
203830AF1-094 GEN
Solar/Wind Harmer
0.904
957161AF2-010 GEN
Solar/Wind Harmer
11.478
971185AH1-051 GEN
Solar/Wind Harmer
3.608
971355AH1-158 GEN
Solar/Wind Harmer
4.196
203856AF2-165 C
Solar/Wind Harmer
1.767
959441AF2-235 GEN
Solar/Wind Harmer
0.444
20328326MANOR_T86
Adder
0.207
238219AF1-167 C
Solar/Wind Harmer
1.891
972271AH1-720 GEN
Adder
8.501
941421AE2-139 GEN
Solar/Wind Harmer
3.883
203932AE1-123
Adder
2.444
200917MEHOOPANY_G
Solar/Wind Harmer
4.114
970679AG2-439 GEN
Solar/Wind Harmer
0.912
238202AE2-262_GEN
Solar/Wind Harmer
1.827
971627AH1-313 GEN
Solar/Wind Harmer
7.164
203854AF2-039 C
Solar/Wind Harmer
0.268
945751AF1-240 GEN
Solar/Wind Harmer
0.867
20089126CSLMN_L13
Solar/Wind Helper
0.489
20089026BF_G21_K23
Solar/Wind Helper
0.387
202652Y1-033 WT C
Solar/Wind Helper
0.363
20083926HOMER C3
50/50
340.465
20083826HOMER C2
50/50
321.609
20083226HNSMLK 5
50/50
14.737
940863AE2-074 GEN
Solar/Wind Harmer
4.454
20083726HOMER C1
Adder
-144.162
203804AE2-113_GEN
Solar/Wind Harmer
9.857
970555AG2-356 GEN
Solar/Wind Harmer
3.948
970663AG2-429 GEN
Solar/Wind Harmer
10.921
970663AG2-429 GEN
Solar/Wind Harmer
1.778
20084926LAKVU GN
Adder
0.296
966771AG1-548 GEN
Solar/Wind Harmer
21.818
966771AG1-548 GEN
Solar/Wind Harmer
4.228
970677AG2-438 GEN
Solar/Wind Harmer
1.492
203846AF2-130 C
Solar/Wind Harmer
0.768
203926AA2-133 GEN
Adder
3.075
20334726NME_Y1-047
Adder
2.764
20390726Y2-042
Adder
2.182
203855AF2-088 C
Solar/Wind Harmer
0.129
971055AG2-654 GEN
Solar/Wind Harmer
0.793
203961AE2-224 GEN
Solar/Wind Helper
3.145
20092526R32
Solar/Wind Helper
1.329
20091526CHSTN_FL
Solar/Wind Helper
0.439
941231AE2-117 GEN
Solar/Wind Helper
0.253
961581Q1080_CY23
External Queue
46.2189826965332
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.25
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.137
TVALTFEXP_TVA->PJM
CLTF
0.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.535
MECLTFEXP_MEC->PJM
CLTF
0.999
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.463

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.09 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1059.33
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.011
972079AH1-589 GEN
Solar/Wind Harmer
50.252
970715AG2-457 GEN
Solar/Wind Harmer
20.337
203980AG1-197 GEN
Solar/Wind Harmer
1.017
203963AG1-253 GEN
Solar/Wind Harmer
0.892
971931AH1-490 GEN
Solar/Wind Harmer
4.439
972075AH1-587 GEN
Solar/Wind Harmer
44.277
203947AF1-006 C
Solar/Wind Harmer
1.229
970305AG2-200 GEN
Solar/Wind Harmer
4.224
20398826ARMNA MT
Solar/Wind Harmer
4.863
203979AG1-198 GEN
Solar/Wind Harmer
0.755
971933AH1-491 GEN
Solar/Wind Harmer
4.156
203859AF2-294 C
Solar/Wind Harmer
3.269
970313AG2-206 GEN
Solar/Wind Harmer
8.823
203848AF2-166 C
Solar/Wind Harmer
3.205
946381AF1-302 GEN
Solar/Wind Harmer
3.267
238217AF1-153 C O1
Solar/Wind Harmer
0.803
20082826HNSMLK 1
50/50
16.171
20083026HNSMLK 3
50/50
16.171
970713AG2-456 GEN
Solar/Wind Harmer
20.337
971705AH1-358 GEN
Solar/Wind Harmer
5.912
971709AH1-360 GEN
Solar/Wind Harmer
5.912
970267AG2-176 GEN
Solar/Wind Harmer
33.863
961971AG1-040 GEN
Solar/Wind Harmer
1.351
203813AE2-344_GEN
Solar/Wind Harmer
25.804
20084926LAKVU GN
Adder
0.386
203835AF1-098 GEN
Solar/Wind Harmer
5.278
203860AG1-193 C
Solar/Wind Harmer
0.636
20335026MILZ1-092
Adder
4.716
944411AF1-106 GEN
Solar/Wind Harmer
4.345
20326126BLOSSBCT
Adder
4.603
959471AF2-238 GEN
Solar/Wind Harmer
1.148
970337AG2-221 GEN
Solar/Wind Harmer
3.798
970647AG2-420 GEN
Solar/Wind Harmer
0.435
970511AG2-327 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
7.295
238183AE2-316 GEN
Solar/Wind Harmer
6.529
203954AE2-126 C
Solar/Wind Harmer
0.73
20072226SHAWVL 2
Adder
13.13
238206AE2-263_GEN
Solar/Wind Harmer
2.077
20091326SHAW-D
Adder
0.549
972169AH1-667 GEN
Solar/Wind Harmer
1.503
971865AH1-452 GEN
Solar/Wind Harmer
1.125
238215AE2-248 C
Solar/Wind Harmer
1.032
20088826HIGHLAND
Solar/Wind Helper
0.735
20089226LOOKOUT
Solar/Wind Helper
0.398
964201AG1-281 GEN
Solar/Wind Helper
0.309
216419AE2-001 C
Solar/Wind Harmer
1.355
203853AF1-134 C O1
Solar/Wind Harmer
0.282
203952AE2-129 C
Solar/Wind Harmer
0.273
203946AE2-131 C
Solar/Wind Harmer
0.272
962411AG1-090 GEN
Solar/Wind Harmer
4.281
20084626FORWARD
Solar/Wind Helper
0.323
20083426SW_E13_K22
Solar/Wind Helper
0.045
20088926STNY CRK
Solar/Wind Helper
0.657
20088626ARWF_N39
Solar/Wind Helper
0.915
20303426NA_O38_P22
Solar/Wind Helper
0.75
203940AF1-140 C
Solar/Wind Helper
0.284
944781AF1-143 GEN
Solar/Wind Helper
1.695
203955AF1-039 C O1
Solar/Wind Helper
0.199
20082926HNSMLK 2
50/50
16.171
20083126HNSMLK 4
50/50
16.171
971703AH1-357 GEN
Solar/Wind Harmer
5.084
971707AH1-359 GEN
Solar/Wind Harmer
5.084
20334926Z1-069 C
Solar/Wind Harmer
5.092
203948AG1-140 C
Solar/Wind Harmer
0.584
962511AG1-100 GEN
Solar/Wind Harmer
1.342
203962AF1-287 GEN
Solar/Wind Harmer
4.429
20084926LAKVU GN
Adder
0.386
20120126WRREN CT
Adder
13.354
203830AF1-094 GEN
Solar/Wind Harmer
1.259
944411AF1-106 GEN
Solar/Wind Harmer
0.467
957161AF2-010 GEN
Solar/Wind Harmer
15.93
959441AF2-235 GEN
Solar/Wind Harmer
0.57
970647AG2-420 GEN
Solar/Wind Harmer
3.743
970335AG2-220 GEN
Solar/Wind Harmer
5.73
971127AH1-005 GEN
Solar/Wind Harmer
3.697
203856AF2-165 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
4.377
971355AH1-158 GEN
Solar/Wind Harmer
5.09
20335126GROZ1-110
Adder
3.54
20335226CANZ2-011
Adder
3.441
238219AF1-167 C
Solar/Wind Harmer
1.987
20328326MANOR_T86
Adder
0.205
203932AE1-123
Adder
2.816
972271AH1-720 GEN
Adder
8.529
941421AE2-139 GEN
Solar/Wind Harmer
3.915
200917MEHOOPANY_G
Solar/Wind Harmer
4.134
970679AG2-439 GEN
Solar/Wind Harmer
0.936
238202AE2-262_GEN
Solar/Wind Harmer
2.229
971627AH1-313 GEN
Solar/Wind Harmer
8.739
203854AF2-039 C
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.249
960051AF2-296 GEN
Solar/Wind Harmer
0.933
965131AG1-378 GEN
Solar/Wind Harmer
0.901
20089126CSLMN_L13
Solar/Wind Helper
0.408
20089026BF_G21_K23
Solar/Wind Helper
0.323
202652Y1-033 WT C
Solar/Wind Helper
0.302
20083926HOMER C3
50/50
297.76
20083826HOMER C2
50/50
281.269
20083226HNSMLK 5
50/50
16.171
940863AE2-074 GEN
Solar/Wind Harmer
4.324
20084926LAKVU GN
Adder
0.434
966771AG1-548 GEN
Solar/Wind Harmer
30.55
966771AG1-548 GEN
Solar/Wind Harmer
5.921
203804AE2-113_GEN
Solar/Wind Harmer
10.01
970677AG2-438 GEN
Solar/Wind Harmer
2.078
970555AG2-356 GEN
Solar/Wind Harmer
3.798
970663AG2-429 GEN
Solar/Wind Harmer
11.217
970663AG2-429 GEN
Solar/Wind Harmer
1.826
203846AF2-130 C
Solar/Wind Harmer
0.916
20083726HOMER C1
Adder
-95.563
203926AA2-133 GEN
Adder
3.065
20334726NME_Y1-047
Adder
2.777
20390726Y2-042
Adder
2.24
203855AF2-088 C
Solar/Wind Harmer
0.164
971055AG2-654 GEN
Solar/Wind Harmer
0.819
965121AG1-377 GEN
Solar/Wind Harmer
0.901
203961AE2-224 GEN
Solar/Wind Helper
2.002
20092526R32
Solar/Wind Helper
0.952
961581Q1080_CY23
External Queue
34.45887756347656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.127
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.016
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:954.32
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
12.11
20083126HNSMLK 4
50/50
12.11
971703AH1-357 GEN
Solar/Wind Harmer
4.348
971707AH1-359 GEN
Solar/Wind Harmer
4.348
20334926Z1-069 C
Solar/Wind Harmer
4.463
944411AF1-106 GEN
Solar/Wind Harmer
0.409
970335AG2-220 GEN
Solar/Wind Harmer
5.061
971127AH1-005 GEN
Solar/Wind Harmer
3.265
20120126WRREN CT
Adder
9.788
20335126GROZ1-110
Adder
3.176
20335226CANZ2-011
Adder
3.087
203948AG1-140 C
Solar/Wind Harmer
0.352
203962AF1-287 GEN
Solar/Wind Harmer
2.601
962511AG1-100 GEN
Solar/Wind Harmer
0.786
970647AG2-420 GEN
Solar/Wind Harmer
2.57
20084926LAKVU GN
Adder
0.223
203830AF1-094 GEN
Solar/Wind Harmer
0.764
20328326MANOR_T86
Adder
0.18
957161AF2-010 GEN
Solar/Wind Harmer
9.707
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.49
959441AF2-235 GEN
Solar/Wind Harmer
0.375
238219AF1-167 C
Solar/Wind Harmer
1.615
941421AE2-139 GEN
Solar/Wind Harmer
3.471
972271AH1-720 GEN
Adder
7.506
203932AE1-123
Adder
2.09
238202AE2-262_GEN
Solar/Wind Harmer
2.629
971627AH1-313 GEN
Solar/Wind Harmer
10.307
200917MEHOOPANY_G
Solar/Wind Harmer
3.564
203854AF2-039 C
Solar/Wind Harmer
0.337
970679AG2-439 GEN
Solar/Wind Harmer
0.792
945751AF1-240 GEN
Solar/Wind Harmer
0.788
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.365
20082826HNSMLK 1
50/50
12.11
20083026HNSMLK 3
50/50
12.11
20335026MILZ1-092
50/50
4.385
20326126BLOSSBCT
50/50
4.34
970713AG2-456 GEN
Solar/Wind Harmer
17.393
971705AH1-358 GEN
Solar/Wind Harmer
5.056
971709AH1-360 GEN
Solar/Wind Harmer
5.056
944411AF1-106 GEN
Solar/Wind Harmer
3.807
959471AF2-238 GEN
Solar/Wind Harmer
1.018
970337AG2-221 GEN
Solar/Wind Harmer
3.367
970511AG2-327 GEN
Solar/Wind Harmer
1.623
970267AG2-176 GEN
Solar/Wind Harmer
21.537
203860AG1-193 C
Solar/Wind Harmer
0.429
238183AE2-316 GEN
Solar/Wind Harmer
5.79
961971AG1-040 GEN
Solar/Wind Harmer
0.819
203835AF1-098 GEN
Solar/Wind Harmer
3.232
203813AE2-344_GEN
Solar/Wind Harmer
15.097
970647AG2-420 GEN
Solar/Wind Harmer
0.299
20084926LAKVU GN
Adder
0.223
971183AH1-050 GEN
Solar/Wind Harmer
5.068
203954AE2-126 C
Solar/Wind Harmer
0.674
238206AE2-263_GEN
Solar/Wind Harmer
2.45
20072226SHAWVL 2
Adder
13.73
238215AE2-248 C
Solar/Wind Harmer
1.548
20091326SHAW-D
Adder
0.542
972169AH1-667 GEN
Solar/Wind Harmer
1.484
24035802GEN-Y1-012
Adder
0.274
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20088826HIGHLAND
Solar/Wind Helper
0.91
964201AG1-281 GEN
Solar/Wind Helper
0.414
20089226LOOKOUT
Solar/Wind Helper
0.481
964391AG1-301 GEN
Solar/Wind Helper
0.26
20094526CT_V3-030
Solar/Wind Helper
0.226
972077AH1-588 GEN
Solar/Wind Harmer
52.179
972079AH1-589 GEN
Solar/Wind Harmer
42.977
970715AG2-457 GEN
Solar/Wind Harmer
17.393
972075AH1-587 GEN
Solar/Wind Harmer
38.609
20398826ARMNA MT
Solar/Wind Harmer
4.304
203859AF2-294 C
Solar/Wind Harmer
2.847
970313AG2-206 GEN
Solar/Wind Harmer
7.793
970305AG2-200 GEN
Solar/Wind Harmer
3.096
946381AF1-302 GEN
Solar/Wind Harmer
2.897
203980AG1-197 GEN
Solar/Wind Harmer
0.621
203963AG1-253 GEN
Solar/Wind Harmer
0.538
971931AH1-490 GEN
Solar/Wind Harmer
2.598
203979AG1-198 GEN
Solar/Wind Harmer
0.459
971933AH1-491 GEN
Solar/Wind Harmer
2.523
203947AF1-006 C
Solar/Wind Harmer
0.691
238217AF1-153 C O1
Solar/Wind Harmer
0.737
203848AF2-166 C
Solar/Wind Harmer
2.285
216419AE2-001 C
Solar/Wind Harmer
1.962
20084626FORWARD
Solar/Wind Helper
0.391
20088626ARWF_N39
Solar/Wind Helper
1.229
20303426NA_O38_P22
Solar/Wind Helper
1.008
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.051
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.501
20083926HOMER C3
50/50
275.49
20083826HOMER C2
50/50
260.232
20083226HNSMLK 5
50/50
12.11
940863AE2-074 GEN
Solar/Wind Harmer
3.768
203804AE2-113_GEN
Solar/Wind Harmer
8.756
970555AG2-356 GEN
Solar/Wind Harmer
3.367
20083726HOMER C1
Adder
-110.032
970663AG2-429 GEN
Solar/Wind Harmer
9.226
970663AG2-429 GEN
Solar/Wind Harmer
1.502
20084926LAKVU GN
Adder
0.25
966771AG1-548 GEN
Solar/Wind Harmer
18.453
966771AG1-548 GEN
Solar/Wind Harmer
3.576
970677AG2-438 GEN
Solar/Wind Harmer
1.262
203846AF2-130 C
Solar/Wind Harmer
0.653
203926AA2-133 GEN
Adder
2.669
20334726NME_Y1-047
Adder
2.394
203855AF2-088 C
Solar/Wind Harmer
0.162
20390726Y2-042
Adder
1.895
971055AG2-654 GEN
Solar/Wind Harmer
0.672
203961AE2-224 GEN
Solar/Wind Helper
2.595
20092526R32
Solar/Wind Helper
1.18
20091526CHSTN_FL
Solar/Wind Helper
0.359
941231AE2-117 GEN
Solar/Wind Helper
0.246
961581Q1080_CY23
External Queue
35.905757904052734
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.22
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.702
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.117
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.063
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.353
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.687

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:736.47
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
11.769
20083026HNSMLK 3
50/50
11.769
20335026MILZ1-092
50/50
4.157
20326126BLOSSBCT
50/50
4.059
970713AG2-456 GEN
Solar/Wind Harmer
13.266
971705AH1-358 GEN
Solar/Wind Harmer
4.755
971709AH1-360 GEN
Solar/Wind Harmer
4.755
944411AF1-106 GEN
Solar/Wind Harmer
3.997
970337AG2-221 GEN
Solar/Wind Harmer
2.419
970511AG2-327 GEN
Solar/Wind Harmer
1.062
970267AG2-176 GEN
Solar/Wind Harmer
14.386
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
10
970647AG2-420 GEN
Solar/Wind Harmer
0.283
20084926LAKVU GN
Adder
0.21
971183AH1-050 GEN
Solar/Wind Harmer
4.125
238183AE2-316 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
8.587
24035802GEN-Y1-012
Adder
0.26
238206AE2-263_GEN
Solar/Wind Harmer
0.002
971865AH1-452 GEN
Solar/Wind Harmer
0.503
20091326SHAW-D
Adder
0.334
972169AH1-667 GEN
Solar/Wind Harmer
0.639
20088826HIGHLAND
Solar/Wind Helper
0.93
20089226LOOKOUT
Solar/Wind Helper
0.49
964201AG1-281 GEN
Solar/Wind Helper
0.416
20094526CT_V3-030
Solar/Wind Helper
0.257
20082926HNSMLK 2
50/50
11.769
20083126HNSMLK 4
50/50
11.769
971703AH1-357 GEN
Solar/Wind Harmer
2.853
971707AH1-359 GEN
Solar/Wind Harmer
2.853
20334926Z1-069 C
Solar/Wind Harmer
1.059
970335AG2-220 GEN
Solar/Wind Harmer
3.421
971127AH1-005 GEN
Solar/Wind Harmer
2.494
20120126WRREN CT
Adder
8.901
203948AG1-140 C
Solar/Wind Harmer
0.251
203962AF1-287 GEN
Solar/Wind Harmer
1.723
970647AG2-420 GEN
Solar/Wind Harmer
1.698
20335126GROZ1-110
Adder
2.841
20335226CANZ2-011
Adder
2.761
20084926LAKVU GN
Adder
0.21
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
6.358
971185AH1-051 GEN
Solar/Wind Harmer
2.475
971355AH1-158 GEN
Solar/Wind Harmer
4.125
20328326MANOR_T86
Adder
0.165
238219AF1-167 C
Solar/Wind Harmer
1.049
972271AH1-720 GEN
Adder
6.781
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.94
200917MEHOOPANY_G
Solar/Wind Harmer
0.33
970679AG2-439 GEN
Solar/Wind Harmer
0.458
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.936
203854AF2-039 C
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Helper
0.504
20089026BF_G21_K23
Solar/Wind Helper
0.399
202652Y1-033 WT C
Solar/Wind Helper
0.372
972077AH1-588 GEN
Solar/Wind Harmer
34.236
972079AH1-589 GEN
Solar/Wind Harmer
40.417
970715AG2-457 GEN
Solar/Wind Harmer
13.266
972075AH1-587 GEN
Solar/Wind Harmer
24.541
20398826ARMNA MT
Solar/Wind Harmer
0.069
203859AF2-294 C
Solar/Wind Harmer
1.886
970313AG2-206 GEN
Solar/Wind Harmer
5.1
970305AG2-200 GEN
Solar/Wind Harmer
1.964
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.723
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Harmer
0.056
203848AF2-166 C
Solar/Wind Harmer
1.492
20084626FORWARD
Solar/Wind Helper
0.399
20088926STNY CRK
Solar/Wind Helper
0.82
20083426SW_E13_K22
Solar/Wind Helper
0.056
20088626ARWF_N39
Solar/Wind Helper
1.176
20303426NA_O38_P22
Solar/Wind Helper
0.964
203940AF1-140 C
Solar/Wind Helper
0.372
944781AF1-143 GEN
Solar/Wind Helper
2.09
203955AF1-039 C O1
Solar/Wind Helper
0.245
946071AF1-272 GEN
Solar/Wind Helper
1.627
20083926HOMER C3
50/50
272.069
20083826HOMER C2
50/50
257.001
20083226HNSMLK 5
50/50
11.769
20083726HOMER C1
Adder
-111.627
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.199
970663AG2-429 GEN
Solar/Wind Harmer
6.483
970663AG2-429 GEN
Solar/Wind Harmer
1.417
20084926LAKVU GN
Adder
0.236
966771AG1-548 GEN
Solar/Wind Harmer
2.769
966771AG1-548 GEN
Solar/Wind Harmer
3.462
970677AG2-438 GEN
Solar/Wind Harmer
0.927
203926AA2-133 GEN
Adder
2.454
20334726NME_Y1-047
Adder
2.206
20390726Y2-042
Adder
1.742
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.52
203961AE2-224 GEN
Solar/Wind Helper
2.523
20092526R32
Solar/Wind Helper
1.205
20091526CHSTN_FL
Solar/Wind Helper
0.389
961581Q1080_CY23
External Queue
36.97114562988281
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.012
LAGNLTFEXP_LAGN->PJM
CLTF
0.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
TVALTFEXP_TVA->PJM
CLTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.231
MECLTFEXP_MEC->PJM
CLTF
0.801
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.369
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.185

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.78 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:940.96
MW Contribution:1.14
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
13.162
20083126HNSMLK 4
50/50
13.162
971703AH1-357 GEN
Solar/Wind Harmer
4.4
971707AH1-359 GEN
Solar/Wind Harmer
4.4
20334926Z1-069 C
Solar/Wind Harmer
4.526
944411AF1-106 GEN
Solar/Wind Harmer
0.415
970335AG2-220 GEN
Solar/Wind Harmer
5.101
971127AH1-005 GEN
Solar/Wind Harmer
3.291
20120126WRREN CT
Adder
9.836
238219AF1-167 C
Solar/Wind Harmer
2.025
970647AG2-420 GEN
Solar/Wind Harmer
2.905
971185AH1-051 GEN
Solar/Wind Harmer
3.469
971355AH1-158 GEN
Solar/Wind Harmer
4.034
203856AF2-165 C
Solar/Wind Harmer
1.693
203948AG1-140 C
Solar/Wind Harmer
0.367
959441AF2-235 GEN
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.834
203962AF1-287 GEN
Solar/Wind Harmer
2.757
957161AF2-010 GEN
Solar/Wind Harmer
10.433
203830AF1-094 GEN
Solar/Wind Harmer
0.82
20084926LAKVU GN
Adder
0.232
20335126GROZ1-110
Adder
3.099
20335226CANZ2-011
Adder
3.012
203932AE1-123
Adder
2.515
20328326MANOR_T86
Adder
0.179
972271AH1-720 GEN
Adder
7.405
941421AE2-139 GEN
Solar/Wind Harmer
3.392
200917MEHOOPANY_G
Solar/Wind Harmer
3.576
970679AG2-439 GEN
Solar/Wind Harmer
0.798
238202AE2-262_GEN
Solar/Wind Harmer
1.779
971627AH1-313 GEN
Solar/Wind Harmer
6.977
203854AF2-039 C
Solar/Wind Harmer
0.265
945751AF1-240 GEN
Solar/Wind Harmer
1.012
20089126CSLMN_L13
Solar/Wind Helper
0.471
20089026BF_G21_K23
Solar/Wind Helper
0.373
202652Y1-033 WT C
Solar/Wind Helper
0.351
20082826HNSMLK 1
50/50
13.162
20083026HNSMLK 3
50/50
13.162
20335026MILZ1-092
50/50
4.448
20326126BLOSSBCT
50/50
4.359
970713AG2-456 GEN
Solar/Wind Harmer
17.6
971705AH1-358 GEN
Solar/Wind Harmer
5.116
971709AH1-360 GEN
Solar/Wind Harmer
5.116
944411AF1-106 GEN
Solar/Wind Harmer
3.862
959471AF2-238 GEN
Solar/Wind Harmer
1.024
970337AG2-221 GEN
Solar/Wind Harmer
3.385
970511AG2-327 GEN
Solar/Wind Harmer
1.636
203860AG1-193 C
Solar/Wind Harmer
0.475
970267AG2-176 GEN
Solar/Wind Harmer
23.253
238183AE2-316 GEN
Solar/Wind Harmer
6.305
970647AG2-420 GEN
Solar/Wind Harmer
0.338
961971AG1-040 GEN
Solar/Wind Harmer
0.876
971183AH1-050 GEN
Solar/Wind Harmer
5.782
203835AF1-098 GEN
Solar/Wind Harmer
3.35
203813AE2-344_GEN
Solar/Wind Harmer
16.003
20084926LAKVU GN
Adder
0.232
203954AE2-126 C
Solar/Wind Harmer
0.595
20072226SHAWVL 2
Adder
10.566
238206AE2-263_GEN
Solar/Wind Harmer
1.658
24035802GEN-Y1-012
Adder
0.283
971865AH1-452 GEN
Solar/Wind Harmer
1.144
20091326SHAW-D
Adder
0.426
972169AH1-667 GEN
Solar/Wind Harmer
1.167
238215AE2-248 C
Solar/Wind Harmer
0.78
20088826HIGHLAND
Solar/Wind Helper
0.858
20089226LOOKOUT
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.375
20083926HOMER C3
50/50
285.029
20083826HOMER C2
50/50
269.243
20083226HNSMLK 5
50/50
13.162
940863AE2-074 GEN
Solar/Wind Harmer
3.814
203804AE2-113_GEN
Solar/Wind Harmer
8.618
970555AG2-356 GEN
Solar/Wind Harmer
3.385
970663AG2-429 GEN
Solar/Wind Harmer
11.496
970663AG2-429 GEN
Solar/Wind Harmer
1.871
20083726HOMER C1
Adder
-104.741
970677AG2-438 GEN
Solar/Wind Harmer
1.353
966771AG1-548 GEN
Solar/Wind Harmer
19.741
966771AG1-548 GEN
Solar/Wind Harmer
3.826
203846AF2-130 C
Solar/Wind Harmer
0.764
20084926LAKVU GN
Adder
0.261
203926AA2-133 GEN
Adder
2.667
20334726NME_Y1-047
Adder
2.402
20390726Y2-042
Adder
1.91
971055AG2-654 GEN
Solar/Wind Harmer
0.981
203855AF2-088 C
Solar/Wind Harmer
0.128
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.322
20091526CHSTN_FL
Solar/Wind Helper
0.335
972077AH1-588 GEN
Solar/Wind Harmer
52.799
972079AH1-589 GEN
Solar/Wind Harmer
43.488
970715AG2-457 GEN
Solar/Wind Harmer
17.6
972075AH1-587 GEN
Solar/Wind Harmer
38.338
20398826ARMNA MT
Solar/Wind Harmer
4.359
203859AF2-294 C
Solar/Wind Harmer
2.894
970313AG2-206 GEN
Solar/Wind Harmer
7.852
970305AG2-200 GEN
Solar/Wind Harmer
3.111
946381AF1-302 GEN
Solar/Wind Harmer
3.155
203980AG1-197 GEN
Solar/Wind Harmer
0.665
203963AG1-253 GEN
Solar/Wind Harmer
0.56
971931AH1-490 GEN
Solar/Wind Harmer
2.76
203979AG1-198 GEN
Solar/Wind Harmer
0.492
971933AH1-491 GEN
Solar/Wind Harmer
2.707
203848AF2-166 C
Solar/Wind Harmer
2.673
203947AF1-006 C
Solar/Wind Harmer
0.726
238217AF1-153 C O1
Solar/Wind Harmer
0.695
216419AE2-001 C
Solar/Wind Harmer
1.035
20084626FORWARD
Solar/Wind Helper
0.371
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.761
20088626ARWF_N39
Solar/Wind Helper
1.075
20303426NA_O38_P22
Solar/Wind Helper
0.881
203940AF1-140 C
Solar/Wind Helper
0.339
944781AF1-143 GEN
Solar/Wind Helper
1.956
203955AF1-039 C O1
Solar/Wind Helper
0.231
946071AF1-272 GEN
Solar/Wind Helper
1.436
961581Q1080_CY23
External Queue
37.79337692260742
LGEELTFEXP_LGEE->PJM
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.058
LAGNLTFEXP_LAGN->PJM
CLTF
0.47
TVALTFEXP_TVA->PJM
CLTF
0.217
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.907
MECLTFEXP_MEC->PJM
CLTF
0.656
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.028

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.55 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:930.83
MW Contribution:0.63
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
16.726
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
5.039
970337AG2-221 GEN
Solar/Wind Harmer
3.049
970511AG2-327 GEN
Solar/Wind Harmer
1.34
970267AG2-176 GEN
Solar/Wind Harmer
18.137
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.007
203813AE2-344_GEN
Solar/Wind Harmer
12.608
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
5.201
238183AE2-316 GEN
Solar/Wind Harmer
0.006
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
0.003
971865AH1-452 GEN
Solar/Wind Harmer
0.634
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
0.805
238215AE2-248 C
Solar/Wind Harmer
0.525
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
3.597
971707AH1-359 GEN
Solar/Wind Harmer
3.597
20334926Z1-069 C
Solar/Wind Harmer
1.335
970335AG2-220 GEN
Solar/Wind Harmer
4.313
971127AH1-005 GEN
Solar/Wind Harmer
3.145
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.316
203962AF1-287 GEN
Solar/Wind Harmer
2.172
970647AG2-420 GEN
Solar/Wind Harmer
2.14
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.002
957161AF2-010 GEN
Solar/Wind Harmer
8.016
971185AH1-051 GEN
Solar/Wind Harmer
3.121
971355AH1-158 GEN
Solar/Wind Harmer
5.201
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.323
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
0.416
970679AG2-439 GEN
Solar/Wind Harmer
0.577
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.962
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.687
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
972077AH1-588 GEN
Solar/Wind Harmer
43.163
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
16.726
972075AH1-587 GEN
Solar/Wind Harmer
30.94
20398826ARMNA MT
Solar/Wind Harmer
0.087
203859AF2-294 C
Solar/Wind Harmer
2.377
970313AG2-206 GEN
Solar/Wind Harmer
6.43
970305AG2-200 GEN
Solar/Wind Harmer
2.477
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.503
971931AH1-490 GEN
Solar/Wind Harmer
2.172
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
2.093
203947AF1-006 C
Solar/Wind Harmer
0.07
203848AF2-166 C
Solar/Wind Harmer
1.881
216419AE2-001 C
Solar/Wind Harmer
0.704
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
0.011
970555AG2-356 GEN
Solar/Wind Harmer
2.772
970663AG2-429 GEN
Solar/Wind Harmer
8.174
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
3.492
966771AG1-548 GEN
Solar/Wind Harmer
4.365
970677AG2-438 GEN
Solar/Wind Harmer
1.168
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.655
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:898.94
MW Contribution:0.76
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
12.408
20083126HNSMLK 4
50/50
12.408
971703AH1-357 GEN
Solar/Wind Harmer
4.225
971707AH1-359 GEN
Solar/Wind Harmer
4.225
20334926Z1-069 C
Solar/Wind Harmer
4.357
944411AF1-106 GEN
Solar/Wind Harmer
0.4
970335AG2-220 GEN
Solar/Wind Harmer
4.898
971127AH1-005 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
9.318
203948AG1-140 C
Solar/Wind Harmer
0.348
970647AG2-420 GEN
Solar/Wind Harmer
2.646
962511AG1-100 GEN
Solar/Wind Harmer
0.787
203962AF1-287 GEN
Solar/Wind Harmer
2.602
971185AH1-051 GEN
Solar/Wind Harmer
3.141
971355AH1-158 GEN
Solar/Wind Harmer
3.653
203856AF2-165 C
Solar/Wind Harmer
1.536
238219AF1-167 C
Solar/Wind Harmer
1.719
959441AF2-235 GEN
Solar/Wind Harmer
0.383
957161AF2-010 GEN
Solar/Wind Harmer
9.735
203830AF1-094 GEN
Solar/Wind Harmer
0.766
20335126GROZ1-110
Adder
2.949
20335226CANZ2-011
Adder
2.867
20084926LAKVU GN
Adder
0.22
20328326MANOR_T86
Adder
0.171
203932AE1-123
Adder
2.197
972271AH1-720 GEN
Adder
7.041
941421AE2-139 GEN
Solar/Wind Harmer
3.22
200917MEHOOPANY_G
Solar/Wind Harmer
3.404
970679AG2-439 GEN
Solar/Wind Harmer
0.756
238202AE2-262_GEN
Solar/Wind Harmer
1.583
971627AH1-313 GEN
Solar/Wind Harmer
6.208
203854AF2-039 C
Solar/Wind Harmer
0.232
945751AF1-240 GEN
Solar/Wind Harmer
0.814
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.366
20082826HNSMLK 1
50/50
12.408
20083026HNSMLK 3
50/50
12.408
20335026MILZ1-092
50/50
4.281
20326126BLOSSBCT
50/50
4.187
970713AG2-456 GEN
Solar/Wind Harmer
16.899
971705AH1-358 GEN
Solar/Wind Harmer
4.912
971709AH1-360 GEN
Solar/Wind Harmer
4.912
944411AF1-106 GEN
Solar/Wind Harmer
3.717
959471AF2-238 GEN
Solar/Wind Harmer
0.983
970337AG2-221 GEN
Solar/Wind Harmer
3.251
970511AG2-327 GEN
Solar/Wind Harmer
1.571
970267AG2-176 GEN
Solar/Wind Harmer
21.827
203860AG1-193 C
Solar/Wind Harmer
0.44
961971AG1-040 GEN
Solar/Wind Harmer
0.824
238183AE2-316 GEN
Solar/Wind Harmer
5.58
970647AG2-420 GEN
Solar/Wind Harmer
0.308
203835AF1-098 GEN
Solar/Wind Harmer
3.172
203813AE2-344_GEN
Solar/Wind Harmer
15.102
971183AH1-050 GEN
Solar/Wind Harmer
5.235
20084926LAKVU GN
Adder
0.22
203954AE2-126 C
Solar/Wind Harmer
0.542
20072226SHAWVL 2
Adder
9.429
24035802GEN-Y1-012
Adder
0.271
238206AE2-263_GEN
Solar/Wind Harmer
1.476
20091326SHAW-D
Adder
0.373
972169AH1-667 GEN
Solar/Wind Harmer
1.02
971865AH1-452 GEN
Solar/Wind Harmer
0.761
20088826HIGHLAND
Solar/Wind Helper
0.908
20089226LOOKOUT
Solar/Wind Helper
0.481
964201AG1-281 GEN
Solar/Wind Helper
0.403
20094526CT_V3-030
Solar/Wind Helper
0.241
972077AH1-588 GEN
Solar/Wind Harmer
50.696
972079AH1-589 GEN
Solar/Wind Harmer
41.756
970715AG2-457 GEN
Solar/Wind Harmer
16.899
972075AH1-587 GEN
Solar/Wind Harmer
36.551
20398826ARMNA MT
Solar/Wind Harmer
4.195
203859AF2-294 C
Solar/Wind Harmer
2.784
970313AG2-206 GEN
Solar/Wind Harmer
7.539
970305AG2-200 GEN
Solar/Wind Harmer
2.947
203980AG1-197 GEN
Solar/Wind Harmer
0.626
203963AG1-253 GEN
Solar/Wind Harmer
0.532
946381AF1-302 GEN
Solar/Wind Harmer
2.792
971931AH1-490 GEN
Solar/Wind Harmer
2.603
203979AG1-198 GEN
Solar/Wind Harmer
0.46
971933AH1-491 GEN
Solar/Wind Harmer
2.528
203947AF1-006 C
Solar/Wind Harmer
0.687
203848AF2-166 C
Solar/Wind Harmer
2.378
238217AF1-153 C O1
Solar/Wind Harmer
0.626
216419AE2-001 C
Solar/Wind Harmer
0.898
20084626FORWARD
Solar/Wind Helper
0.391
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
20088626ARWF_N39
Solar/Wind Helper
1.142
20303426NA_O38_P22
Solar/Wind Helper
0.936
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.052
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.602
20083926HOMER C3
50/50
277.61
20083826HOMER C2
50/50
262.235
20083226HNSMLK 5
50/50
12.408
940863AE2-074 GEN
Solar/Wind Harmer
3.667
203804AE2-113_GEN
Solar/Wind Harmer
8.186
970555AG2-356 GEN
Solar/Wind Harmer
3.251
20083726HOMER C1
Adder
-109.082
970663AG2-429 GEN
Solar/Wind Harmer
9.987
970663AG2-429 GEN
Solar/Wind Harmer
1.626
970677AG2-438 GEN
Solar/Wind Harmer
1.264
966771AG1-548 GEN
Solar/Wind Harmer
18.467
966771AG1-548 GEN
Solar/Wind Harmer
3.579
20084926LAKVU GN
Adder
0.248
203846AF2-130 C
Solar/Wind Harmer
0.679
203926AA2-133 GEN
Adder
2.542
20334726NME_Y1-047
Adder
2.287
20390726Y2-042
Adder
1.81
203855AF2-088 C
Solar/Wind Harmer
0.112
971055AG2-654 GEN
Solar/Wind Harmer
0.641
20092526R32
Solar/Wind Helper
1.178
203961AE2-224 GEN
Solar/Wind Helper
2.456
20091526CHSTN_FL
Solar/Wind Helper
0.371
961581Q1080_CY23
External Queue
37.30971908569336
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
0.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.036
TVALTFEXP_TVA->PJM
CLTF
0.277
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.138
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.867

Details for 26HOMER CT _-26HOMER CT 230.0 kV Ckt S line l/o PN_P1-2_PN-345-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT _-26HOMER CT 230.0 kV Ckt S line
Contingency Name:
PN_P1-2_PN-345-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.77 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:841.63
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
18.564
20083026HNSMLK 3
50/50
18.564
20335026MILZ1-092
50/50
4.382
20326126BLOSSBCT
50/50
4.303
970713AG2-456 GEN
Solar/Wind Harmer
13.579
971705AH1-358 GEN
Solar/Wind Harmer
4.867
971709AH1-360 GEN
Solar/Wind Harmer
4.867
944411AF1-106 GEN
Solar/Wind Harmer
4.214
970337AG2-221 GEN
Solar/Wind Harmer
2.569
970511AG2-327 GEN
Solar/Wind Harmer
1.129
238183AE2-316 GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.192
20084926LAKVU GN
Adder
0.141
203860AG1-193 C
Solar/Wind Harmer
0
203813AE2-344_GEN
Solar/Wind Harmer
5.955
970267AG2-176 GEN
Solar/Wind Harmer
7.41
20072226SHAWVL 2
Adder
9.384
971865AH1-452 GEN
Solar/Wind Harmer
0.62
238206AE2-263_GEN
Solar/Wind Harmer
0.003
20091326SHAW-D
Adder
0.376
972169AH1-667 GEN
Solar/Wind Harmer
0.717
238215AE2-248 C
Solar/Wind Harmer
0.484
20088826HIGHLAND
Solar/Wind Helper
0.802
20089226LOOKOUT
Solar/Wind Helper
0.425
964201AG1-281 GEN
Solar/Wind Helper
0.352
20082926HNSMLK 2
50/50
18.564
20083126HNSMLK 4
50/50
18.564
20334926Z1-069 C
Solar/Wind Harmer
1.108
971703AH1-357 GEN
Solar/Wind Harmer
2.92
971707AH1-359 GEN
Solar/Wind Harmer
2.92
970335AG2-220 GEN
Solar/Wind Harmer
3.635
971127AH1-005 GEN
Solar/Wind Harmer
2.651
20335126GROZ1-110
Adder
3.032
20335226CANZ2-011
Adder
2.947
20120126WRREN CT
Adder
7.924
20328326MANOR_T86
Adder
0.176
238219AF1-167 C
Solar/Wind Harmer
1.164
972271AH1-720 GEN
Adder
7.271
941421AE2-139 GEN
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.355
203932AE1-123
Adder
1.872
203948AG1-140 C
Solar/Wind Harmer
0.18
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
1.151
957161AF2-010 GEN
Solar/Wind Harmer
4.365
203830AF1-094 GEN
Solar/Wind Harmer
0.001
970679AG2-439 GEN
Solar/Wind Harmer
0.498
20084926LAKVU GN
Adder
0.141
203962AF1-287 GEN
Solar/Wind Harmer
1.029
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.345
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.566
20089126CSLMN_L13
Solar/Wind Helper
0.437
20089026BF_G21_K23
Solar/Wind Helper
0.346
202652Y1-033 WT C
Solar/Wind Helper
0.322
20083926HOMER C3
50/50
294.484
20083826HOMER C2
50/50
278.174
20083226HNSMLK 5
50/50
18.564
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.336
20083726HOMER C1
Adder
-98.732
970663AG2-429 GEN
Solar/Wind Harmer
7.36
970663AG2-429 GEN
Solar/Wind Harmer
1.608
203926AA2-133 GEN
Adder
2.63
20334726NME_Y1-047
Adder
2.373
970677AG2-438 GEN
Solar/Wind Harmer
0.635
966771AG1-548 GEN
Solar/Wind Harmer
1.891
966771AG1-548 GEN
Solar/Wind Harmer
2.364
20390726Y2-042
Adder
1.896
20084926LAKVU GN
Adder
0.158
971055AG2-654 GEN
Solar/Wind Harmer
0.641
203855AF2-088 C
Solar/Wind Harmer
0
203961AE2-224 GEN
Solar/Wind Helper
2.177
20092526R32
Solar/Wind Helper
1.04
20091526CHSTN_FL
Solar/Wind Helper
0.318
972077AH1-588 GEN
Solar/Wind Harmer
35.043
972079AH1-589 GEN
Solar/Wind Harmer
41.37
970715AG2-457 GEN
Solar/Wind Harmer
13.579
20398826ARMNA MT
Solar/Wind Harmer
0.073
972075AH1-587 GEN
Solar/Wind Harmer
25.36
203859AF2-294 C
Solar/Wind Harmer
1.99
970313AG2-206 GEN
Solar/Wind Harmer
5.42
970305AG2-200 GEN
Solar/Wind Harmer
1.749
203963AG1-253 GEN
Solar/Wind Harmer
0.286
203848AF2-166 C
Solar/Wind Harmer
1.259
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.137
203947AF1-006 C
Solar/Wind Harmer
0.035
971931AH1-490 GEN
Solar/Wind Harmer
1.006
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
0.643
20084626FORWARD
Solar/Wind Helper
0.347
20083426SW_E13_K22
Solar/Wind Helper
0.048
20088926STNY CRK
Solar/Wind Helper
0.71
20088626ARWF_N39
Solar/Wind Helper
1.008
20303426NA_O38_P22
Solar/Wind Helper
0.827
203940AF1-140 C
Solar/Wind Helper
0.318
944781AF1-143 GEN
Solar/Wind Helper
1.814
203955AF1-039 C O1
Solar/Wind Helper
0.213
946071AF1-272 GEN
Solar/Wind Helper
1.339
961581Q1080_CY23
External Queue
42.41039276123047
LGEELTFEXP_LGEE->PJM
CLTF
0.139
WECLTFEXP_WEC->PJM
CLTF
0.096
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
0.242
TVALTFEXP_TVA->PJM
CLTF
0.11
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.019
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.475
MECLTFEXP_MEC->PJM
CLTF
0.372
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.509
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.201

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.2 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1295.55
MW Contribution:0.85
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.921
203857AF2-221 C
Solar/Wind Harmer
4.203
970123AG2-090 GEN
Solar/Wind Harmer
3.923
203839AF1-321 GEN
Solar/Wind Harmer
5.589
20084626FORWARD
Solar/Wind Harmer
2.204
20088626ARWF_N39
Solar/Wind Harmer
5.112
20303426NA_O38_P22
Solar/Wind Harmer
4.138
203940AF1-140 C
Solar/Wind Harmer
1.284
20088926STNY CRK
Solar/Wind Harmer
3.117
971427AH1-205 GEN
Solar/Wind Harmer
3.764
971441AH1-212 GEN
Solar/Wind Harmer
4.958
20083426SW_E13_K22
Solar/Wind Harmer
0.738
944781AF1-143 GEN
Solar/Wind Harmer
6.285
972077AH1-588 GEN
Solar/Wind Harmer
48.014
972079AH1-589 GEN
Solar/Wind Harmer
39.546
970715AG2-457 GEN
Solar/Wind Harmer
16.005
972075AH1-587 GEN
Solar/Wind Harmer
37.507
203952AE2-129 C
Solar/Wind Harmer
1.045
203946AE2-131 C
Solar/Wind Harmer
1.043
962411AG1-090 GEN
Solar/Wind Harmer
16.386
20398826ARMNA MT
Solar/Wind Harmer
3.926
203955AF1-039 C O1
Solar/Wind Harmer
0.721
203859AF2-294 C
Solar/Wind Harmer
2.598
970313AG2-206 GEN
Solar/Wind Harmer
7.221
970305AG2-200 GEN
Solar/Wind Harmer
2.986
946381AF1-302 GEN
Solar/Wind Harmer
3.044
203853AF1-134 C O1
Solar/Wind Harmer
0.868
238217AF1-153 C O1
Solar/Wind Harmer
0.857
203848AF2-166 C
Solar/Wind Harmer
2.614
203980AG1-197 GEN
Solar/Wind Harmer
0.568
216419AE2-001 C
Solar/Wind Harmer
2.453
203963AG1-253 GEN
Solar/Wind Harmer
0.49
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.419
971931AH1-490 GEN
Solar/Wind Harmer
2.369
203947AF1-006 C
Solar/Wind Harmer
0.629
957561AF2-050 GEN
Solar/Wind Harmer
14.434
203843AF2-002_GEN
Solar/Wind Harmer
2.795
970631AG2-411 GEN
Solar/Wind Harmer
17.564
20088826HIGHLAND
Solar/Wind Harmer
4.455
971423AH1-203 GEN
Solar/Wind Harmer
17.686
964201AG1-281 GEN
Solar/Wind Harmer
1.503
20089226LOOKOUT
Solar/Wind Harmer
1.785
203987AE2-118 C
Solar/Wind Harmer
4.021
970713AG2-456 GEN
Solar/Wind Harmer
16.005
971705AH1-358 GEN
Solar/Wind Harmer
4.652
971709AH1-360 GEN
Solar/Wind Harmer
4.652
971279AH1-102 GEN
Solar/Wind Harmer
16.075
20094526CT_V3-030
Solar/Wind Harmer
1.376
964391AG1-301 GEN
Solar/Wind Harmer
1.116
20082826HNSMLK 1
Adder
10.051
20083026HNSMLK 3
Adder
10.051
20326126BLOSSBCT
Adder
3.791
20335026MILZ1-092
Adder
3.765
944411AF1-106 GEN
Solar/Wind Harmer
3.468
959471AF2-238 GEN
Solar/Wind Harmer
0.945
970337AG2-221 GEN
Solar/Wind Harmer
3.124
203954AE2-126 C
Solar/Wind Harmer
0.919
970511AG2-327 GEN
Solar/Wind Harmer
1.504
972169AH1-667 GEN
Solar/Wind Harmer
2.64
20091326SHAW-D
Adder
0.964
238183AE2-316 GEN
Solar/Wind Harmer
6.084
20072226SHAWVL 2
Adder
18.929
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.311
971183AH1-050 GEN
Solar/Wind Harmer
5.394
970267AG2-176 GEN
Solar/Wind Harmer
19.756
238206AE2-263_GEN
Solar/Wind Harmer
3.094
961971AG1-040 GEN
Solar/Wind Harmer
0.749
203835AF1-098 GEN
Solar/Wind Harmer
2.998
238215AE2-248 C
Solar/Wind Harmer
1.943
203813AE2-344_GEN
Solar/Wind Harmer
13.78
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.691
24035802GEN-Y1-012
Adder
0.229
971865AH1-452 GEN
Solar/Wind Harmer
0.847
20083326SEWRDB34
50/50
11.281
970125AG2-091 GEN
Solar/Wind Harmer
1.681
971879AH1-460 GEN
Solar/Wind Harmer
18.472
203841AF2-001_GEN
Solar/Wind Harmer
5.589
971419AH1-201 GEN
Solar/Wind Harmer
8.093
20079426CONEMAGH
Adder
3.005
20089126CSLMN_L13
Solar/Wind Harmer
1.834
20089026BF_G21_K23
Solar/Wind Harmer
1.452
971703AH1-357 GEN
Solar/Wind Harmer
4.001
971707AH1-359 GEN
Solar/Wind Harmer
4.001
971541AH1-268 GEN
Solar/Wind Harmer
6.841
20334926Z1-069 C
Solar/Wind Harmer
4.066
965131AG1-378 GEN
Solar/Wind Harmer
3.45
20082926HNSMLK 2
Adder
10.051
20083126HNSMLK 4
Adder
10.051
944411AF1-106 GEN
Solar/Wind Harmer
0.373
202652Y1-033 WT C
Solar/Wind Harmer
1.48
970335AG2-220 GEN
Solar/Wind Harmer
4.687
971127AH1-005 GEN
Solar/Wind Harmer
3.024
20120126WRREN CT
Adder
9.44
203854AF2-039 C
Solar/Wind Harmer
0.6
960051AF2-296 GEN
Solar/Wind Harmer
2.87
203818AF1-086 GEN
Solar/Wind Harmer
3.609
970647AG2-420 GEN
Solar/Wind Harmer
2.671
971185AH1-051 GEN
Solar/Wind Harmer
3.237
971355AH1-158 GEN
Solar/Wind Harmer
3.764
20335126GROZ1-110
Adder
3.122
20335226CANZ2-011
Adder
3.034
203856AF2-165 C
Solar/Wind Harmer
1.577
970899AG2-561 GEN
Solar/Wind Harmer
2.635
945751AF1-240 GEN
Solar/Wind Harmer
2.06
238202AE2-262_GEN
Solar/Wind Harmer
3.32
971627AH1-313 GEN
Solar/Wind Harmer
13.017
203932AE1-123
Adder
2.564
959441AF2-235 GEN
Solar/Wind Harmer
0.387
238219AF1-167 C
Solar/Wind Harmer
1.674
203948AG1-140 C
Solar/Wind Harmer
0.321
957161AF2-010 GEN
Solar/Wind Harmer
9.338
20328326MANOR_T86
Adder
0.172
203830AF1-094 GEN
Solar/Wind Harmer
0.733
203962AF1-287 GEN
Solar/Wind Harmer
2.376
962511AG1-100 GEN
Solar/Wind Harmer
0.716
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.451
972271AH1-720 GEN
Adder
7.368
200917MEHOOPANY_G
Solar/Wind Harmer
3.45
970679AG2-439 GEN
Solar/Wind Harmer
0.782
970643AG2-418 GEN
Solar/Wind Harmer
1.486
20083726HOMER C1
50/50
286.383
20083926HOMER C3
50/50
233.562
20083826HOMER C2
50/50
220.627
20050326C.SLOPE
50/50
0.843
203961AE2-224 GEN
Solar/Wind Harmer
8.743
20092526R32
Solar/Wind Harmer
4.774
203844AF2-092 C
Solar/Wind Harmer
3.155
203850AG1-041 C
Solar/Wind Harmer
3.148
20091526CHSTN_FL
Solar/Wind Harmer
2.073
940863AE2-074 GEN
Solar/Wind Harmer
3.456
20090526Q36
Solar/Wind Harmer
3.014
203993AD2-133_GEN1
Solar/Wind Harmer
3.014
941231AE2-117 GEN
Solar/Wind Harmer
1.126
203804AE2-113_GEN
Solar/Wind Harmer
8.719
965121AG1-377 GEN
Solar/Wind Harmer
3.45
20083226HNSMLK 5
Adder
10.051
970555AG2-356 GEN
Solar/Wind Harmer
3.124
203855AF2-088 C
Solar/Wind Harmer
0.289
970663AG2-429 GEN
Solar/Wind Harmer
9.219
970663AG2-429 GEN
Solar/Wind Harmer
1.501
203846AF2-130 C
Solar/Wind Harmer
0.747
970677AG2-438 GEN
Solar/Wind Harmer
1.209
966771AG1-548 GEN
Solar/Wind Harmer
17.6
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.229
203926AA2-133 GEN
Adder
2.573
20334726NME_Y1-047
Adder
2.318
20390726Y2-042
Adder
1.871
971055AG2-654 GEN
Solar/Wind Harmer
0.552
961581Q1080_CY23
External Queue
28.047279357910156
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.14
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.124
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.211
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.273
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1283.85
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.948
203839AF1-321 GEN
Solar/Wind Harmer
5.307
20084626FORWARD
Solar/Wind Harmer
2.09
203857AF2-221 C
Solar/Wind Harmer
3.907
970123AG2-090 GEN
Solar/Wind Harmer
3.647
20088926STNY CRK
Solar/Wind Harmer
2.928
971427AH1-205 GEN
Solar/Wind Harmer
3.536
20088626ARWF_N39
Solar/Wind Harmer
4.477
20303426NA_O38_P22
Solar/Wind Harmer
3.625
203940AF1-140 C
Solar/Wind Harmer
1.175
20083426SW_E13_K22
Solar/Wind Harmer
0.698
971441AH1-212 GEN
Solar/Wind Harmer
4.486
972077AH1-588 GEN
Solar/Wind Harmer
48.69
972079AH1-589 GEN
Solar/Wind Harmer
40.103
970715AG2-457 GEN
Solar/Wind Harmer
16.23
944781AF1-143 GEN
Solar/Wind Harmer
5.944
972075AH1-587 GEN
Solar/Wind Harmer
37.76
20398826ARMNA MT
Solar/Wind Harmer
3.987
203952AE2-129 C
Solar/Wind Harmer
0.978
203946AE2-131 C
Solar/Wind Harmer
0.976
962411AG1-090 GEN
Solar/Wind Harmer
15.339
203859AF2-294 C
Solar/Wind Harmer
2.639
970313AG2-206 GEN
Solar/Wind Harmer
7.317
970305AG2-200 GEN
Solar/Wind Harmer
3.008
203955AF1-039 C O1
Solar/Wind Harmer
0.681
946381AF1-302 GEN
Solar/Wind Harmer
3.033
238217AF1-153 C O1
Solar/Wind Harmer
0.842
203853AF1-134 C O1
Solar/Wind Harmer
0.816
203848AF2-166 C
Solar/Wind Harmer
2.611
203980AG1-197 GEN
Solar/Wind Harmer
0.577
203963AG1-253 GEN
Solar/Wind Harmer
0.498
203979AG1-198 GEN
Solar/Wind Harmer
0.445
971933AH1-491 GEN
Solar/Wind Harmer
2.447
971931AH1-490 GEN
Solar/Wind Harmer
2.408
216419AE2-001 C
Solar/Wind Harmer
2.331
203947AF1-006 C
Solar/Wind Harmer
0.639
203843AF2-002_GEN
Solar/Wind Harmer
2.653
970631AG2-411 GEN
Solar/Wind Harmer
16.66
957561AF2-050 GEN
Solar/Wind Harmer
12.617
20088826HIGHLAND
Solar/Wind Harmer
4.07
971423AH1-203 GEN
Solar/Wind Harmer
16.651
964201AG1-281 GEN
Solar/Wind Harmer
1.366
970713AG2-456 GEN
Solar/Wind Harmer
16.23
971705AH1-358 GEN
Solar/Wind Harmer
4.718
971709AH1-360 GEN
Solar/Wind Harmer
4.718
20089226LOOKOUT
Solar/Wind Harmer
1.689
203987AE2-118 C
Solar/Wind Harmer
3.598
971279AH1-102 GEN
Solar/Wind Harmer
14.659
20094526CT_V3-030
Solar/Wind Harmer
1.254
20082826HNSMLK 1
Adder
10.267
20083026HNSMLK 3
Adder
10.267
20335026MILZ1-092
Adder
3.824
944411AF1-106 GEN
Solar/Wind Harmer
3.523
20326126BLOSSBCT
Adder
3.84
964391AG1-301 GEN
Solar/Wind Harmer
1
959471AF2-238 GEN
Solar/Wind Harmer
0.957
970337AG2-221 GEN
Solar/Wind Harmer
3.165
970511AG2-327 GEN
Solar/Wind Harmer
1.524
203954AE2-126 C
Solar/Wind Harmer
0.895
238183AE2-316 GEN
Solar/Wind Harmer
6.061
972169AH1-667 GEN
Solar/Wind Harmer
2.525
20091326SHAW-D
Adder
0.922
203860AG1-193 C
Solar/Wind Harmer
0.421
970647AG2-420 GEN
Solar/Wind Harmer
0.312
970267AG2-176 GEN
Solar/Wind Harmer
20.083
971183AH1-050 GEN
Solar/Wind Harmer
5.417
20072226SHAWVL 2
Adder
18.247
961971AG1-040 GEN
Solar/Wind Harmer
0.761
203835AF1-098 GEN
Solar/Wind Harmer
3.037
238206AE2-263_GEN
Solar/Wind Harmer
2.973
203813AE2-344_GEN
Solar/Wind Harmer
14.003
20084926LAKVU GN
Adder
0.206
238215AE2-248 C
Solar/Wind Harmer
1.842
970643AG2-418 GEN
Solar/Wind Harmer
0.625
24035802GEN-Y1-012
Adder
0.234
971865AH1-452 GEN
Solar/Wind Harmer
0.861
20083326SEWRDB34
50/50
8.898
20079426CONEMAGH
50/50
2.901
203841AF2-001_GEN
Solar/Wind Harmer
5.307
971879AH1-460 GEN
Solar/Wind Harmer
17.329
970125AG2-091 GEN
Solar/Wind Harmer
1.563
971419AH1-201 GEN
Solar/Wind Harmer
7.603
971703AH1-357 GEN
Solar/Wind Harmer
4.058
971707AH1-359 GEN
Solar/Wind Harmer
4.058
20334926Z1-069 C
Solar/Wind Harmer
4.13
20089126CSLMN_L13
Solar/Wind Harmer
1.734
20089026BF_G21_K23
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
6.238
20082926HNSMLK 2
Adder
10.267
20083126HNSMLK 4
Adder
10.267
944411AF1-106 GEN
Solar/Wind Harmer
0.379
965131AG1-378 GEN
Solar/Wind Harmer
3.229
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.064
20120126WRREN CT
Adder
9.509
202652Y1-033 WT C
Solar/Wind Harmer
1.4
203854AF2-039 C
Solar/Wind Harmer
0.573
960051AF2-296 GEN
Solar/Wind Harmer
2.698
970647AG2-420 GEN
Solar/Wind Harmer
2.687
971185AH1-051 GEN
Solar/Wind Harmer
3.25
971355AH1-158 GEN
Solar/Wind Harmer
3.779
20335126GROZ1-110
Adder
3.135
20335226CANZ2-011
Adder
3.047
203856AF2-165 C
Solar/Wind Harmer
1.584
203818AF1-086 GEN
Solar/Wind Harmer
3.348
203932AE1-123
Adder
2.548
959441AF2-235 GEN
Solar/Wind Harmer
0.389
945751AF1-240 GEN
Solar/Wind Harmer
1.977
238202AE2-262_GEN
Solar/Wind Harmer
3.19
971627AH1-313 GEN
Solar/Wind Harmer
12.507
238219AF1-167 C
Solar/Wind Harmer
1.682
203948AG1-140 C
Solar/Wind Harmer
0.326
957161AF2-010 GEN
Solar/Wind Harmer
9.444
203830AF1-094 GEN
Solar/Wind Harmer
0.741
20328326MANOR_T86
Adder
0.174
970899AG2-561 GEN
Solar/Wind Harmer
2.417
203962AF1-287 GEN
Solar/Wind Harmer
2.414
962511AG1-100 GEN
Solar/Wind Harmer
0.728
20084926LAKVU GN
Adder
0.206
941421AE2-139 GEN
Solar/Wind Harmer
3.462
972271AH1-720 GEN
Adder
7.407
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.345
20083726HOMER C1
50/50
294.677
20083926HOMER C3
50/50
239.758
20083826HOMER C2
50/50
226.48
20050326C.SLOPE
50/50
0.759
203961AE2-224 GEN
Solar/Wind Harmer
7.642
20092526R32
Solar/Wind Harmer
4.361
203844AF2-092 C
Solar/Wind Harmer
2.929
203850AG1-041 C
Solar/Wind Harmer
2.914
20091526CHSTN_FL
Solar/Wind Harmer
1.885
940863AE2-074 GEN
Solar/Wind Harmer
3.506
203804AE2-113_GEN
Solar/Wind Harmer
8.75
20090526Q36
Solar/Wind Harmer
2.784
203993AD2-133_GEN1
Solar/Wind Harmer
2.784
20083226HNSMLK 5
Adder
10.267
941231AE2-117 GEN
Solar/Wind Harmer
1.012
965121AG1-377 GEN
Solar/Wind Harmer
3.229
970555AG2-356 GEN
Solar/Wind Harmer
3.165
203855AF2-088 C
Solar/Wind Harmer
0.276
970663AG2-429 GEN
Solar/Wind Harmer
9.296
970663AG2-429 GEN
Solar/Wind Harmer
1.513
203846AF2-130 C
Solar/Wind Harmer
0.746
970677AG2-438 GEN
Solar/Wind Harmer
1.223
966771AG1-548 GEN
Solar/Wind Harmer
17.81
966771AG1-548 GEN
Solar/Wind Harmer
3.452
20084926LAKVU GN
Adder
0.232
203926AA2-133 GEN
Adder
2.594
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.883
971055AG2-654 GEN
Solar/Wind Harmer
0.566
961581Q1080_CY23
External Queue
29.164003372192383
WECLTFEXP_WEC->PJM
CLTF
0.019
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.208
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
MECLTFEXP_MEC->PJM
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.884
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
971865AH1-452 GEN
Solar/Wind Harmer
0.778
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
961581Q1080_CY23
External Queue
20.78413963317871
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
971865AH1-452 GEN
Solar/Wind Harmer
0.778
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
961581Q1080_CY23
External Queue
20.78413963317871
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.9 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1067.2
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.225
20079426CONEMAGH
50/50
2.285
203841AF2-001_GEN
Solar/Wind Harmer
4.231
971879AH1-460 GEN
Solar/Wind Harmer
13.827
970125AG2-091 GEN
Solar/Wind Harmer
1.248
971419AH1-201 GEN
Solar/Wind Harmer
6.062
971703AH1-357 GEN
Solar/Wind Harmer
3.389
971707AH1-359 GEN
Solar/Wind Harmer
3.389
20334926Z1-069 C
Solar/Wind Harmer
3.451
20089126CSLMN_L13
Solar/Wind Harmer
1.376
20089026BF_G21_K23
Solar/Wind Harmer
1.089
20082926HNSMLK 2
Adder
8.888
20083126HNSMLK 4
Adder
8.888
944411AF1-106 GEN
Solar/Wind Harmer
0.318
971541AH1-268 GEN
Solar/Wind Harmer
4.764
965131AG1-378 GEN
Solar/Wind Harmer
2.667
970335AG2-220 GEN
Solar/Wind Harmer
4.008
971127AH1-005 GEN
Solar/Wind Harmer
2.586
20120126WRREN CT
Adder
8.023
238219AF1-167 C
Solar/Wind Harmer
1.644
971185AH1-051 GEN
Solar/Wind Harmer
2.873
971355AH1-158 GEN
Solar/Wind Harmer
3.341
970647AG2-420 GEN
Solar/Wind Harmer
2.365
202652Y1-033 WT C
Solar/Wind Harmer
1.103
203854AF2-039 C
Solar/Wind Harmer
0.481
203856AF2-165 C
Solar/Wind Harmer
1.398
203932AE1-123
Adder
2.301
20335126GROZ1-110
Adder
2.667
20335226CANZ2-011
Adder
2.592
959441AF2-235 GEN
Solar/Wind Harmer
0.34
238202AE2-262_GEN
Solar/Wind Harmer
2.732
971627AH1-313 GEN
Solar/Wind Harmer
10.713
960051AF2-296 GEN
Solar/Wind Harmer
2.134
957161AF2-010 GEN
Solar/Wind Harmer
8.095
203830AF1-094 GEN
Solar/Wind Harmer
0.635
203948AG1-140 C
Solar/Wind Harmer
0.274
20328326MANOR_T86
Adder
0.149
945751AF1-240 GEN
Solar/Wind Harmer
1.622
203962AF1-287 GEN
Solar/Wind Harmer
2.05
962511AG1-100 GEN
Solar/Wind Harmer
0.619
20084926LAKVU GN
Adder
0.174
203818AF1-086 GEN
Solar/Wind Harmer
2.522
941421AE2-139 GEN
Solar/Wind Harmer
2.971
972271AH1-720 GEN
Adder
6.359
200917MEHOOPANY_G
Solar/Wind Harmer
3.008
970899AG2-561 GEN
Solar/Wind Harmer
1.709
970679AG2-439 GEN
Solar/Wind Harmer
0.692
970643AG2-418 GEN
Solar/Wind Harmer
1.17
203843AF2-002_GEN
Solar/Wind Harmer
2.116
970631AG2-411 GEN
Solar/Wind Harmer
13.291
957561AF2-050 GEN
Solar/Wind Harmer
10.23
20088826HIGHLAND
Solar/Wind Harmer
3.255
971423AH1-203 GEN
Solar/Wind Harmer
13.269
964201AG1-281 GEN
Solar/Wind Harmer
1.098
970713AG2-456 GEN
Solar/Wind Harmer
13.555
971705AH1-358 GEN
Solar/Wind Harmer
3.94
971709AH1-360 GEN
Solar/Wind Harmer
3.94
20089226LOOKOUT
Solar/Wind Harmer
1.34
20082826HNSMLK 1
Adder
8.888
20083026HNSMLK 3
Adder
8.888
203987AE2-118 C
Solar/Wind Harmer
2.942
20326126BLOSSBCT
Adder
3.229
20335026MILZ1-092
Adder
3.213
944411AF1-106 GEN
Solar/Wind Harmer
2.96
971279AH1-102 GEN
Solar/Wind Harmer
11.195
20083726HOMER C1
50/50
236.905
20083926HOMER C3
50/50
197.325
20083826HOMER C2
50/50
186.396
20050326C.SLOPE
50/50
0.607
203961AE2-224 GEN
Solar/Wind Harmer
6.197
20092526R32
Solar/Wind Harmer
3.488
203844AF2-092 C
Solar/Wind Harmer
2.34
203850AG1-041 C
Solar/Wind Harmer
2.329
20091526CHSTN_FL
Solar/Wind Harmer
1.52
940863AE2-074 GEN
Solar/Wind Harmer
2.929
203804AE2-113_GEN
Solar/Wind Harmer
7.361
20083226HNSMLK 5
Adder
8.888
20090526Q36
Solar/Wind Harmer
2.277
203993AD2-133_GEN1
Solar/Wind Harmer
2.277
941231AE2-117 GEN
Solar/Wind Harmer
0.831
965121AG1-377 GEN
Solar/Wind Harmer
2.667
970555AG2-356 GEN
Solar/Wind Harmer
2.667
970663AG2-429 GEN
Solar/Wind Harmer
9.078
970663AG2-429 GEN
Solar/Wind Harmer
1.478
203855AF2-088 C
Solar/Wind Harmer
0.231
203846AF2-130 C
Solar/Wind Harmer
0.666
20094526CT_V3-030
Solar/Wind Harmer
0.97
964391AG1-301 GEN
Solar/Wind Harmer
0.822
238183AE2-316 GEN
Solar/Wind Harmer
5.648
959471AF2-238 GEN
Solar/Wind Harmer
0.806
970337AG2-221 GEN
Solar/Wind Harmer
2.667
970511AG2-327 GEN
Solar/Wind Harmer
1.287
203954AE2-126 C
Solar/Wind Harmer
0.756
203860AG1-193 C
Solar/Wind Harmer
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.788
970647AG2-420 GEN
Solar/Wind Harmer
0.275
972169AH1-667 GEN
Solar/Wind Harmer
2.116
20091326SHAW-D
Adder
0.773
970267AG2-176 GEN
Solar/Wind Harmer
17.249
20072226SHAWVL 2
Adder
15.552
961971AG1-040 GEN
Solar/Wind Harmer
0.65
238206AE2-263_GEN
Solar/Wind Harmer
2.547
203835AF1-098 GEN
Solar/Wind Harmer
2.563
203813AE2-344_GEN
Solar/Wind Harmer
11.887
20084926LAKVU GN
Adder
0.174
238215AE2-248 C
Solar/Wind Harmer
1.577
970643AG2-418 GEN
Solar/Wind Harmer
0.544
971865AH1-452 GEN
Solar/Wind Harmer
0.783
24035802GEN-Y1-012
Adder
0.187
20080926SITHE
50/50
0.762
203839AF1-321 GEN
Solar/Wind Harmer
4.231
20084626FORWARD
Solar/Wind Harmer
1.668
203857AF2-221 C
Solar/Wind Harmer
3.12
970123AG2-090 GEN
Solar/Wind Harmer
2.912
20088626ARWF_N39
Solar/Wind Harmer
3.636
20303426NA_O38_P22
Solar/Wind Harmer
2.943
20088926STNY CRK
Solar/Wind Harmer
2.334
971427AH1-205 GEN
Solar/Wind Harmer
2.819
203940AF1-140 C
Solar/Wind Harmer
0.941
20083426SW_E13_K22
Solar/Wind Harmer
0.556
971441AH1-212 GEN
Solar/Wind Harmer
3.578
972077AH1-588 GEN
Solar/Wind Harmer
40.664
972079AH1-589 GEN
Solar/Wind Harmer
33.493
970715AG2-457 GEN
Solar/Wind Harmer
13.555
972075AH1-587 GEN
Solar/Wind Harmer
31.692
944781AF1-143 GEN
Solar/Wind Harmer
4.717
20398826ARMNA MT
Solar/Wind Harmer
3.349
946381AF1-302 GEN
Solar/Wind Harmer
2.826
203952AE2-129 C
Solar/Wind Harmer
0.808
203946AE2-131 C
Solar/Wind Harmer
0.806
962411AG1-090 GEN
Solar/Wind Harmer
12.668
203859AF2-294 C
Solar/Wind Harmer
2.224
970313AG2-206 GEN
Solar/Wind Harmer
6.176
970305AG2-200 GEN
Solar/Wind Harmer
2.538
238217AF1-153 C O1
Solar/Wind Harmer
0.739
203955AF1-039 C O1
Solar/Wind Harmer
0.537
203848AF2-166 C
Solar/Wind Harmer
2.332
203980AG1-197 GEN
Solar/Wind Harmer
0.493
203853AF1-134 C O1
Solar/Wind Harmer
0.645
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.095
203963AG1-253 GEN
Solar/Wind Harmer
0.419
971931AH1-490 GEN
Solar/Wind Harmer
2.046
216419AE2-001 C
Solar/Wind Harmer
1.996
203947AF1-006 C
Solar/Wind Harmer
0.539
946071AF1-272 GEN
Solar/Wind Helper
1.397
970677AG2-438 GEN
Solar/Wind Harmer
1.048
966771AG1-548 GEN
Solar/Wind Harmer
15.227
966771AG1-548 GEN
Solar/Wind Harmer
2.951
20084926LAKVU GN
Adder
0.196
203926AA2-133 GEN
Adder
2.229
20334726NME_Y1-047
Adder
2.021
20390726Y2-042
Adder
1.655
971055AG2-654 GEN
Solar/Wind Harmer
0.64
961581Q1080_CY23
External Queue
23.464759826660156
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.644
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.168
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.93
G-007ALTFEXP_G-007A->PJM
CMTX
0.72
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.335
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.27
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.25
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
961581Q1080_CY23
External Queue
27.7316951751709
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-050_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-050_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.7 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1026.04
MW Contribution:0.78
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.094
970631AG2-411 GEN
Solar/Wind Harmer
13.15
957561AF2-050 GEN
Solar/Wind Harmer
10.099
20088826HIGHLAND
Solar/Wind Harmer
3.218
971423AH1-203 GEN
Solar/Wind Harmer
13.128
964201AG1-281 GEN
Solar/Wind Harmer
1.083
970713AG2-456 GEN
Solar/Wind Harmer
13.01
971705AH1-358 GEN
Solar/Wind Harmer
3.782
971709AH1-360 GEN
Solar/Wind Harmer
3.782
20089226LOOKOUT
Solar/Wind Harmer
1.327
203987AE2-118 C
Solar/Wind Harmer
2.887
20082826HNSMLK 1
Adder
8.283
20083026HNSMLK 3
Adder
8.283
20335026MILZ1-092
Adder
3.095
944411AF1-106 GEN
Solar/Wind Harmer
2.852
20326126BLOSSBCT
Adder
3.108
971279AH1-102 GEN
Solar/Wind Harmer
10.981
964391AG1-301 GEN
Solar/Wind Harmer
0.805
20094526CT_V3-030
Solar/Wind Harmer
0.947
959471AF2-238 GEN
Solar/Wind Harmer
0.776
970337AG2-221 GEN
Solar/Wind Harmer
2.568
970511AG2-327 GEN
Solar/Wind Harmer
1.239
238183AE2-316 GEN
Solar/Wind Harmer
5.03
203954AE2-126 C
Solar/Wind Harmer
0.716
972169AH1-667 GEN
Solar/Wind Harmer
2.01
20091326SHAW-D
Adder
0.734
203860AG1-193 C
Solar/Wind Harmer
0.337
970647AG2-420 GEN
Solar/Wind Harmer
0.25
20072226SHAWVL 2
Adder
14.703
971183AH1-050 GEN
Solar/Wind Harmer
4.335
970267AG2-176 GEN
Solar/Wind Harmer
16.035
238206AE2-263_GEN
Solar/Wind Harmer
2.411
961971AG1-040 GEN
Solar/Wind Harmer
0.606
203835AF1-098 GEN
Solar/Wind Harmer
2.413
20083326SEWRDB34
50/50
7.147
20079426CONEMAGH
50/50
2.267
203841AF2-001_GEN
Solar/Wind Harmer
4.187
971879AH1-460 GEN
Solar/Wind Harmer
13.683
970125AG2-091 GEN
Solar/Wind Harmer
1.235
971419AH1-201 GEN
Solar/Wind Harmer
5.996
971703AH1-357 GEN
Solar/Wind Harmer
3.253
971707AH1-359 GEN
Solar/Wind Harmer
3.253
20334926Z1-069 C
Solar/Wind Harmer
3.322
20089126CSLMN_L13
Solar/Wind Harmer
1.363
20089026BF_G21_K23
Solar/Wind Harmer
1.079
20082926HNSMLK 2
Adder
8.283
20083126HNSMLK 4
Adder
8.283
944411AF1-106 GEN
Solar/Wind Harmer
0.307
971541AH1-268 GEN
Solar/Wind Harmer
4.673
965131AG1-378 GEN
Solar/Wind Harmer
2.568
970335AG2-220 GEN
Solar/Wind Harmer
3.859
971127AH1-005 GEN
Solar/Wind Harmer
2.49
20120126WRREN CT
Adder
7.604
202652Y1-033 WT C
Solar/Wind Harmer
1.094
203854AF2-039 C
Solar/Wind Harmer
0.457
20335126GROZ1-110
Adder
2.557
20335226CANZ2-011
Adder
2.485
970647AG2-420 GEN
Solar/Wind Harmer
2.15
971185AH1-051 GEN
Solar/Wind Harmer
2.601
971355AH1-158 GEN
Solar/Wind Harmer
3.025
203856AF2-165 C
Solar/Wind Harmer
1.267
238219AF1-167 C
Solar/Wind Harmer
1.406
203932AE1-123
Adder
2.04
959441AF2-235 GEN
Solar/Wind Harmer
0.311
960051AF2-296 GEN
Solar/Wind Harmer
2.032
238202AE2-262_GEN
Solar/Wind Harmer
2.587
971627AH1-313 GEN
Solar/Wind Harmer
10.143
20328326MANOR_T86
Adder
0.143
203948AG1-140 C
Solar/Wind Harmer
0.259
957161AF2-010 GEN
Solar/Wind Harmer
7.507
203830AF1-094 GEN
Solar/Wind Harmer
0.589
203962AF1-287 GEN
Solar/Wind Harmer
1.916
962511AG1-100 GEN
Solar/Wind Harmer
0.578
203818AF1-086 GEN
Solar/Wind Harmer
2.406
945751AF1-240 GEN
Solar/Wind Harmer
1.476
941421AE2-139 GEN
Solar/Wind Harmer
2.847
20084926LAKVU GN
Adder
0.163
972271AH1-720 GEN
Adder
6.098
200917MEHOOPANY_G
Solar/Wind Harmer
2.887
970899AG2-561 GEN
Solar/Wind Harmer
1.627
970679AG2-439 GEN
Solar/Wind Harmer
0.663
970643AG2-418 GEN
Solar/Wind Harmer
1.132
20080926SITHE
50/50
0.753
203839AF1-321 GEN
Solar/Wind Harmer
4.187
20084626FORWARD
Solar/Wind Harmer
1.65
203857AF2-221 C
Solar/Wind Harmer
3.087
970123AG2-090 GEN
Solar/Wind Harmer
2.881
20088626ARWF_N39
Solar/Wind Harmer
3.587
20303426NA_O38_P22
Solar/Wind Harmer
2.903
20088926STNY CRK
Solar/Wind Harmer
2.309
971427AH1-205 GEN
Solar/Wind Harmer
2.789
203940AF1-140 C
Solar/Wind Harmer
0.929
20083426SW_E13_K22
Solar/Wind Harmer
0.55
971441AH1-212 GEN
Solar/Wind Harmer
3.528
972077AH1-588 GEN
Solar/Wind Harmer
39.03
972079AH1-589 GEN
Solar/Wind Harmer
32.147
970715AG2-457 GEN
Solar/Wind Harmer
13.01
944781AF1-143 GEN
Solar/Wind Harmer
4.671
972075AH1-587 GEN
Solar/Wind Harmer
30.308
20398826ARMNA MT
Solar/Wind Harmer
3.227
203952AE2-129 C
Solar/Wind Harmer
0.778
203946AE2-131 C
Solar/Wind Harmer
0.776
962411AG1-090 GEN
Solar/Wind Harmer
12.198
203859AF2-294 C
Solar/Wind Harmer
2.142
970313AG2-206 GEN
Solar/Wind Harmer
5.946
970305AG2-200 GEN
Solar/Wind Harmer
2.405
946381AF1-302 GEN
Solar/Wind Harmer
2.517
203955AF1-039 C O1
Solar/Wind Harmer
0.533
238217AF1-153 C O1
Solar/Wind Harmer
0.684
203848AF2-166 C
Solar/Wind Harmer
2.089
203853AF1-134 C O1
Solar/Wind Harmer
0.614
203980AG1-197 GEN
Solar/Wind Harmer
0.46
203963AG1-253 GEN
Solar/Wind Harmer
0.395
203979AG1-198 GEN
Solar/Wind Harmer
0.353
971933AH1-491 GEN
Solar/Wind Harmer
1.945
971931AH1-490 GEN
Solar/Wind Harmer
1.912
216419AE2-001 C
Solar/Wind Harmer
1.898
203947AF1-006 C
Solar/Wind Harmer
0.506
946071AF1-272 GEN
Solar/Wind Helper
1.424
20083726HOMER C1
50/50
234.187
20083926HOMER C3
50/50
191.764
20083826HOMER C2
50/50
181.144
20050326C.SLOPE
50/50
0.6
203961AE2-224 GEN
Solar/Wind Harmer
6.117
20092526R32
Solar/Wind Harmer
3.448
203844AF2-092 C
Solar/Wind Harmer
2.313
203850AG1-041 C
Solar/Wind Harmer
2.301
20091526CHSTN_FL
Solar/Wind Harmer
1.493
940863AE2-074 GEN
Solar/Wind Harmer
2.816
203804AE2-113_GEN
Solar/Wind Harmer
7.026
20090526Q36
Solar/Wind Harmer
2.212
203993AD2-133_GEN1
Solar/Wind Harmer
2.212
20083226HNSMLK 5
Adder
8.283
941231AE2-117 GEN
Solar/Wind Harmer
0.813
965121AG1-377 GEN
Solar/Wind Harmer
2.568
970555AG2-356 GEN
Solar/Wind Harmer
2.568
970663AG2-429 GEN
Solar/Wind Harmer
7.782
970663AG2-429 GEN
Solar/Wind Harmer
1.267
203855AF2-088 C
Solar/Wind Harmer
0.22
203846AF2-130 C
Solar/Wind Harmer
0.597
970677AG2-438 GEN
Solar/Wind Harmer
0.972
966771AG1-548 GEN
Solar/Wind Harmer
14.151
966771AG1-548 GEN
Solar/Wind Harmer
2.742
20084926LAKVU GN
Adder
0.184
203926AA2-133 GEN
Adder
2.14
20334726NME_Y1-047
Adder
1.94
20390726Y2-042
Adder
1.587
203813AE2-344_GEN
Solar/Wind Harmer
11.114
238215AE2-248 C
Solar/Wind Harmer
1.501
20084926LAKVU GN
Adder
0.163
970643AG2-418 GEN
Solar/Wind Harmer
0.526
971865AH1-452 GEN
Solar/Wind Harmer
0.776
961581Q1080_CY23
External Queue
23.127099990844727
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.595
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.048
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.859
G-007ALTFEXP_G-007A->PJM
CMTX
0.626
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.114
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-230-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:132.97 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1099.7
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-230-0183-210_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-230-0183-210_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.97 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1099.66
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.856
972079AH1-589 GEN
Solar/Wind Harmer
50.947
970715AG2-457 GEN
Solar/Wind Harmer
20.619
972075AH1-587 GEN
Solar/Wind Harmer
44.338
20398826ARMNA MT
Solar/Wind Harmer
5.136
203859AF2-294 C
Solar/Wind Harmer
3.407
970313AG2-206 GEN
Solar/Wind Harmer
9.214
970305AG2-200 GEN
Solar/Wind Harmer
3.549
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.113
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.131
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.695
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.009
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.035
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.483
20303426NA_O38_P22
Solar/Wind Helper
1.216
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.636
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.053
20082826HNSMLK 1
50/50
14.834
20083026HNSMLK 3
50/50
14.834
20335026MILZ1-092
50/50
5.24
20326126BLOSSBCT
50/50
5.117
970713AG2-456 GEN
Solar/Wind Harmer
20.619
971705AH1-358 GEN
Solar/Wind Harmer
5.994
971709AH1-360 GEN
Solar/Wind Harmer
5.994
944411AF1-106 GEN
Solar/Wind Harmer
4.549
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.972
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.989
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.809
203813AE2-344_GEN
Solar/Wind Harmer
18.065
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.034
238183AE2-316 GEN
Solar/Wind Harmer
6.257
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.82
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.69
971865AH1-452 GEN
Solar/Wind Harmer
1.102
20091326SHAW-D
Adder
0.421
972169AH1-667 GEN
Solar/Wind Harmer
1.153
238215AE2-248 C
Solar/Wind Harmer
0.752
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.834
20083126HNSMLK 4
50/50
14.834
971703AH1-357 GEN
Solar/Wind Harmer
5.155
971707AH1-359 GEN
Solar/Wind Harmer
5.155
20334926Z1-069 C
Solar/Wind Harmer
5.33
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.987
971127AH1-005 GEN
Solar/Wind Harmer
3.863
20120126WRREN CT
Adder
11.22
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.112
970647AG2-420 GEN
Solar/Wind Harmer
3.067
20335126GROZ1-110
Adder
3.58
20335226CANZ2-011
Adder
3.48
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.535
971185AH1-051 GEN
Solar/Wind Harmer
3.62
971355AH1-158 GEN
Solar/Wind Harmer
4.21
203856AF2-165 C
Solar/Wind Harmer
1.773
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.547
941421AE2-139 GEN
Solar/Wind Harmer
3.902
203932AE1-123
Adder
2.445
200917MEHOOPANY_G
Solar/Wind Harmer
4.138
970679AG2-439 GEN
Solar/Wind Harmer
0.917
238202AE2-262_GEN
Solar/Wind Harmer
1.813
971627AH1-313 GEN
Solar/Wind Harmer
7.108
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20083926HOMER C3
50/50
342.978
20083826HOMER C2
50/50
323.983
20083226HNSMLK 5
50/50
14.834
940863AE2-074 GEN
Solar/Wind Harmer
4.481
20083726HOMER C1
Adder
-140.768
203804AE2-113_GEN
Solar/Wind Harmer
9.898
970555AG2-356 GEN
Solar/Wind Harmer
3.972
970663AG2-429 GEN
Solar/Wind Harmer
10.97
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.929
966771AG1-548 GEN
Solar/Wind Harmer
4.25
970677AG2-438 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.093
20334726NME_Y1-047
Adder
2.78
20390726Y2-042
Adder
2.195
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.182
20092526R32
Solar/Wind Helper
1.52
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.27
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.381
WECLTFEXP_WEC->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.018
LAGNLTFEXP_LAGN->PJM
CLTF
0.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.534
MECLTFEXP_MEC->PJM
CLTF
1.002
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.565
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.472

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-345-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-345-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.9 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1090.83
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-2_PN-345-001T-DRT-001_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-2_PN-345-001T-DRT-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.9 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1090.83
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.867
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
20.622
972075AH1-587 GEN
Solar/Wind Harmer
44.348
20398826ARMNA MT
Solar/Wind Harmer
5.137
203859AF2-294 C
Solar/Wind Harmer
3.408
970313AG2-206 GEN
Solar/Wind Harmer
9.216
970305AG2-200 GEN
Solar/Wind Harmer
3.55
203980AG1-197 GEN
Solar/Wind Harmer
0.747
203963AG1-253 GEN
Solar/Wind Harmer
0.64
971931AH1-490 GEN
Solar/Wind Harmer
3.114
203979AG1-198 GEN
Solar/Wind Harmer
0.545
971933AH1-491 GEN
Solar/Wind Harmer
2.999
946381AF1-302 GEN
Solar/Wind Harmer
3.132
203947AF1-006 C
Solar/Wind Harmer
0.824
203848AF2-166 C
Solar/Wind Harmer
2.696
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.01
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
20.622
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
4.55
959471AF2-238 GEN
Solar/Wind Harmer
1.201
970337AG2-221 GEN
Solar/Wind Harmer
3.973
970511AG2-327 GEN
Solar/Wind Harmer
1.92
970267AG2-176 GEN
Solar/Wind Harmer
25.996
203860AG1-193 C
Solar/Wind Harmer
0.517
961971AG1-040 GEN
Solar/Wind Harmer
0.984
203835AF1-098 GEN
Solar/Wind Harmer
3.81
203813AE2-344_GEN
Solar/Wind Harmer
18.071
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
6.036
238183AE2-316 GEN
Solar/Wind Harmer
6.259
203954AE2-126 C
Solar/Wind Harmer
0.633
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
1.691
971865AH1-452 GEN
Solar/Wind Harmer
1.103
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
1.154
238215AE2-248 C
Solar/Wind Harmer
0.753
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
5.156
971707AH1-359 GEN
Solar/Wind Harmer
5.156
20334926Z1-069 C
Solar/Wind Harmer
5.331
944411AF1-106 GEN
Solar/Wind Harmer
0.489
970335AG2-220 GEN
Solar/Wind Harmer
5.989
971127AH1-005 GEN
Solar/Wind Harmer
3.864
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.941
203962AF1-287 GEN
Solar/Wind Harmer
3.113
970647AG2-420 GEN
Solar/Wind Harmer
3.068
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.908
957161AF2-010 GEN
Solar/Wind Harmer
11.539
971185AH1-051 GEN
Solar/Wind Harmer
3.622
971355AH1-158 GEN
Solar/Wind Harmer
4.211
203856AF2-165 C
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.446
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.898
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
3.904
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
4.14
970679AG2-439 GEN
Solar/Wind Harmer
0.918
238202AE2-262_GEN
Solar/Wind Harmer
1.814
971627AH1-313 GEN
Solar/Wind Harmer
7.113
203854AF2-039 C
Solar/Wind Harmer
0.262
945751AF1-240 GEN
Solar/Wind Harmer
0.845
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
940863AE2-074 GEN
Solar/Wind Harmer
4.482
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
9.9
970555AG2-356 GEN
Solar/Wind Harmer
3.973
970663AG2-429 GEN
Solar/Wind Harmer
10.974
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
21.936
966771AG1-548 GEN
Solar/Wind Harmer
4.251
970677AG2-438 GEN
Solar/Wind Harmer
1.5
203846AF2-130 C
Solar/Wind Harmer
0.77
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0.126
971055AG2-654 GEN
Solar/Wind Harmer
0.799
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P2-3_PN-230-0183-207_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P2-3_PN-230-0183-207_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.01 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1066.94
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
972077AH1-588 GEN
Solar/Wind Harmer
61.494
972079AH1-589 GEN
Solar/Wind Harmer
50.65
970715AG2-457 GEN
Solar/Wind Harmer
20.498
972075AH1-587 GEN
Solar/Wind Harmer
44.13
20398826ARMNA MT
Solar/Wind Harmer
5.104
203859AF2-294 C
Solar/Wind Harmer
3.385
970313AG2-206 GEN
Solar/Wind Harmer
9.157
970305AG2-200 GEN
Solar/Wind Harmer
3.532
203980AG1-197 GEN
Solar/Wind Harmer
0.742
203963AG1-253 GEN
Solar/Wind Harmer
0.636
971931AH1-490 GEN
Solar/Wind Harmer
3.095
203979AG1-198 GEN
Solar/Wind Harmer
0.542
971933AH1-491 GEN
Solar/Wind Harmer
2.984
946381AF1-302 GEN
Solar/Wind Harmer
3.122
203947AF1-006 C
Solar/Wind Harmer
0.819
203848AF2-166 C
Solar/Wind Harmer
2.689
238217AF1-153 C O1
Solar/Wind Harmer
0.721
216419AE2-001 C
Solar/Wind Harmer
1.022
20088626ARWF_N39
Solar/Wind Helper
1.462
20303426NA_O38_P22
Solar/Wind Helper
1.199
20084626FORWARD
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.407
20088926STNY CRK
Solar/Wind Helper
0.814
20083426SW_E13_K22
Solar/Wind Helper
0.054
944781AF1-143 GEN
Solar/Wind Helper
2.029
946071AF1-272 GEN
Solar/Wind Helper
2.016
203955AF1-039 C O1
Solar/Wind Helper
0.239
20082826HNSMLK 1
50/50
14.737
20083026HNSMLK 3
50/50
14.737
20335026MILZ1-092
50/50
5.207
20326126BLOSSBCT
50/50
5.086
970713AG2-456 GEN
Solar/Wind Harmer
20.498
971705AH1-358 GEN
Solar/Wind Harmer
5.959
971709AH1-360 GEN
Solar/Wind Harmer
5.959
944411AF1-106 GEN
Solar/Wind Harmer
4.52
959471AF2-238 GEN
Solar/Wind Harmer
1.194
970337AG2-221 GEN
Solar/Wind Harmer
3.948
970511AG2-327 GEN
Solar/Wind Harmer
1.908
970267AG2-176 GEN
Solar/Wind Harmer
25.838
203860AG1-193 C
Solar/Wind Harmer
0.515
961971AG1-040 GEN
Solar/Wind Harmer
0.978
203835AF1-098 GEN
Solar/Wind Harmer
3.788
203813AE2-344_GEN
Solar/Wind Harmer
17.961
970647AG2-420 GEN
Solar/Wind Harmer
0.355
20084926LAKVU GN
Adder
0.263
971183AH1-050 GEN
Solar/Wind Harmer
6.014
238183AE2-316 GEN
Solar/Wind Harmer
6.239
203954AE2-126 C
Solar/Wind Harmer
0.637
20072226SHAWVL 2
Adder
10.919
24035802GEN-Y1-012
Adder
0.325
238206AE2-263_GEN
Solar/Wind Harmer
1.703
20091326SHAW-D
Adder
0.431
972169AH1-667 GEN
Solar/Wind Harmer
1.178
971865AH1-452 GEN
Solar/Wind Harmer
1.096
238215AE2-248 C
Solar/Wind Harmer
0.763
20088826HIGHLAND
Solar/Wind Helper
1.026
964201AG1-281 GEN
Solar/Wind Helper
0.467
20089226LOOKOUT
Solar/Wind Helper
0.476
20094526CT_V3-030
Solar/Wind Helper
0.295
964391AG1-301 GEN
Solar/Wind Helper
0.262
20082926HNSMLK 2
50/50
14.737
20083126HNSMLK 4
50/50
14.737
971703AH1-357 GEN
Solar/Wind Harmer
5.125
971707AH1-359 GEN
Solar/Wind Harmer
5.125
20334926Z1-069 C
Solar/Wind Harmer
5.297
944411AF1-106 GEN
Solar/Wind Harmer
0.486
970335AG2-220 GEN
Solar/Wind Harmer
5.951
971127AH1-005 GEN
Solar/Wind Harmer
3.839
20120126WRREN CT
Adder
11.166
203948AG1-140 C
Solar/Wind Harmer
0.417
962511AG1-100 GEN
Solar/Wind Harmer
0.936
203962AF1-287 GEN
Solar/Wind Harmer
3.094
970647AG2-420 GEN
Solar/Wind Harmer
3.055
20335126GROZ1-110
Adder
3.563
20335226CANZ2-011
Adder
3.463
20084926LAKVU GN
Adder
0.263
203830AF1-094 GEN
Solar/Wind Harmer
0.904
957161AF2-010 GEN
Solar/Wind Harmer
11.478
971185AH1-051 GEN
Solar/Wind Harmer
3.608
971355AH1-158 GEN
Solar/Wind Harmer
4.196
203856AF2-165 C
Solar/Wind Harmer
1.767
959441AF2-235 GEN
Solar/Wind Harmer
0.444
20328326MANOR_T86
Adder
0.207
238219AF1-167 C
Solar/Wind Harmer
1.891
972271AH1-720 GEN
Adder
8.501
941421AE2-139 GEN
Solar/Wind Harmer
3.883
203932AE1-123
Adder
2.444
200917MEHOOPANY_G
Solar/Wind Harmer
4.114
970679AG2-439 GEN
Solar/Wind Harmer
0.912
238202AE2-262_GEN
Solar/Wind Harmer
1.827
971627AH1-313 GEN
Solar/Wind Harmer
7.164
203854AF2-039 C
Solar/Wind Harmer
0.268
945751AF1-240 GEN
Solar/Wind Harmer
0.867
20089126CSLMN_L13
Solar/Wind Helper
0.489
20089026BF_G21_K23
Solar/Wind Helper
0.387
202652Y1-033 WT C
Solar/Wind Helper
0.363
20083926HOMER C3
50/50
340.465
20083826HOMER C2
50/50
321.609
20083226HNSMLK 5
50/50
14.737
940863AE2-074 GEN
Solar/Wind Harmer
4.454
20083726HOMER C1
Adder
-144.162
203804AE2-113_GEN
Solar/Wind Harmer
9.857
970555AG2-356 GEN
Solar/Wind Harmer
3.948
970663AG2-429 GEN
Solar/Wind Harmer
10.921
970663AG2-429 GEN
Solar/Wind Harmer
1.778
20084926LAKVU GN
Adder
0.296
966771AG1-548 GEN
Solar/Wind Harmer
21.818
966771AG1-548 GEN
Solar/Wind Harmer
4.228
970677AG2-438 GEN
Solar/Wind Harmer
1.492
203846AF2-130 C
Solar/Wind Harmer
0.768
203926AA2-133 GEN
Adder
3.075
20334726NME_Y1-047
Adder
2.764
20390726Y2-042
Adder
2.182
203855AF2-088 C
Solar/Wind Harmer
0.129
971055AG2-654 GEN
Solar/Wind Harmer
0.793
203961AE2-224 GEN
Solar/Wind Helper
3.145
20092526R32
Solar/Wind Helper
1.329
20091526CHSTN_FL
Solar/Wind Helper
0.439
941231AE2-117 GEN
Solar/Wind Helper
0.253
961581Q1080_CY23
External Queue
46.2189826965332
LGEELTFEXP_LGEE->PJM
CLTF
0.38
WECLTFEXP_WEC->PJM
CLTF
0.25
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.137
TVALTFEXP_TVA->PJM
CLTF
0.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.527
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.535
MECLTFEXP_MEC->PJM
CLTF
0.999
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.463

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.09 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:1059.31
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
16.171
20083026HNSMLK 3
50/50
16.171
970713AG2-456 GEN
Solar/Wind Harmer
20.337
971705AH1-358 GEN
Solar/Wind Harmer
5.912
971709AH1-360 GEN
Solar/Wind Harmer
5.912
970267AG2-176 GEN
Solar/Wind Harmer
33.863
961971AG1-040 GEN
Solar/Wind Harmer
1.351
203813AE2-344_GEN
Solar/Wind Harmer
25.804
20084926LAKVU GN
Adder
0.386
203835AF1-098 GEN
Solar/Wind Harmer
5.278
203860AG1-193 C
Solar/Wind Harmer
0.636
20335026MILZ1-092
Adder
4.716
944411AF1-106 GEN
Solar/Wind Harmer
4.345
20326126BLOSSBCT
Adder
4.603
959471AF2-238 GEN
Solar/Wind Harmer
1.148
970337AG2-221 GEN
Solar/Wind Harmer
3.798
970647AG2-420 GEN
Solar/Wind Harmer
0.435
970511AG2-327 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
7.295
238183AE2-316 GEN
Solar/Wind Harmer
6.529
203954AE2-126 C
Solar/Wind Harmer
0.73
20072226SHAWVL 2
Adder
13.13
238206AE2-263_GEN
Solar/Wind Harmer
2.077
20091326SHAW-D
Adder
0.549
972169AH1-667 GEN
Solar/Wind Harmer
1.503
971865AH1-452 GEN
Solar/Wind Harmer
1.125
238215AE2-248 C
Solar/Wind Harmer
1.032
20088826HIGHLAND
Solar/Wind Helper
0.735
20089226LOOKOUT
Solar/Wind Helper
0.398
964201AG1-281 GEN
Solar/Wind Helper
0.309
972077AH1-588 GEN
Solar/Wind Harmer
61.011
972079AH1-589 GEN
Solar/Wind Harmer
50.252
970715AG2-457 GEN
Solar/Wind Harmer
20.337
203980AG1-197 GEN
Solar/Wind Harmer
1.017
203963AG1-253 GEN
Solar/Wind Harmer
0.892
971931AH1-490 GEN
Solar/Wind Harmer
4.439
972075AH1-587 GEN
Solar/Wind Harmer
44.277
203947AF1-006 C
Solar/Wind Harmer
1.229
970305AG2-200 GEN
Solar/Wind Harmer
4.224
20398826ARMNA MT
Solar/Wind Harmer
4.863
203979AG1-198 GEN
Solar/Wind Harmer
0.755
971933AH1-491 GEN
Solar/Wind Harmer
4.156
203859AF2-294 C
Solar/Wind Harmer
3.269
970313AG2-206 GEN
Solar/Wind Harmer
8.823
203848AF2-166 C
Solar/Wind Harmer
3.205
946381AF1-302 GEN
Solar/Wind Harmer
3.267
238217AF1-153 C O1
Solar/Wind Harmer
0.803
216419AE2-001 C
Solar/Wind Harmer
1.355
203853AF1-134 C O1
Solar/Wind Harmer
0.282
203952AE2-129 C
Solar/Wind Harmer
0.273
203946AE2-131 C
Solar/Wind Harmer
0.272
962411AG1-090 GEN
Solar/Wind Harmer
4.281
20084626FORWARD
Solar/Wind Helper
0.323
20083426SW_E13_K22
Solar/Wind Helper
0.045
20088926STNY CRK
Solar/Wind Helper
0.657
20088626ARWF_N39
Solar/Wind Helper
0.915
20303426NA_O38_P22
Solar/Wind Helper
0.75
203940AF1-140 C
Solar/Wind Helper
0.284
944781AF1-143 GEN
Solar/Wind Helper
1.695
203955AF1-039 C O1
Solar/Wind Helper
0.199
20082926HNSMLK 2
50/50
16.171
20083126HNSMLK 4
50/50
16.171
971703AH1-357 GEN
Solar/Wind Harmer
5.084
971707AH1-359 GEN
Solar/Wind Harmer
5.084
20334926Z1-069 C
Solar/Wind Harmer
5.092
203948AG1-140 C
Solar/Wind Harmer
0.584
962511AG1-100 GEN
Solar/Wind Harmer
1.342
203962AF1-287 GEN
Solar/Wind Harmer
4.429
20084926LAKVU GN
Adder
0.386
20120126WRREN CT
Adder
13.354
203830AF1-094 GEN
Solar/Wind Harmer
1.259
944411AF1-106 GEN
Solar/Wind Harmer
0.467
957161AF2-010 GEN
Solar/Wind Harmer
15.93
959441AF2-235 GEN
Solar/Wind Harmer
0.57
970647AG2-420 GEN
Solar/Wind Harmer
3.743
970335AG2-220 GEN
Solar/Wind Harmer
5.73
971127AH1-005 GEN
Solar/Wind Harmer
3.697
203856AF2-165 C
Solar/Wind Harmer
2.166
971185AH1-051 GEN
Solar/Wind Harmer
4.377
971355AH1-158 GEN
Solar/Wind Harmer
5.09
20335126GROZ1-110
Adder
3.54
20335226CANZ2-011
Adder
3.441
238219AF1-167 C
Solar/Wind Harmer
1.987
20328326MANOR_T86
Adder
0.205
203932AE1-123
Adder
2.816
972271AH1-720 GEN
Adder
8.529
941421AE2-139 GEN
Solar/Wind Harmer
3.915
200917MEHOOPANY_G
Solar/Wind Harmer
4.134
970679AG2-439 GEN
Solar/Wind Harmer
0.936
238202AE2-262_GEN
Solar/Wind Harmer
2.229
971627AH1-313 GEN
Solar/Wind Harmer
8.739
203854AF2-039 C
Solar/Wind Harmer
0.341
945751AF1-240 GEN
Solar/Wind Harmer
1.249
960051AF2-296 GEN
Solar/Wind Harmer
0.933
965131AG1-378 GEN
Solar/Wind Harmer
0.901
20089126CSLMN_L13
Solar/Wind Helper
0.408
20089026BF_G21_K23
Solar/Wind Helper
0.323
202652Y1-033 WT C
Solar/Wind Helper
0.302
20083926HOMER C3
50/50
297.76
20083826HOMER C2
50/50
281.269
20083226HNSMLK 5
50/50
16.171
940863AE2-074 GEN
Solar/Wind Harmer
4.324
20084926LAKVU GN
Adder
0.434
966771AG1-548 GEN
Solar/Wind Harmer
30.55
966771AG1-548 GEN
Solar/Wind Harmer
5.921
203804AE2-113_GEN
Solar/Wind Harmer
10.01
970677AG2-438 GEN
Solar/Wind Harmer
2.078
970555AG2-356 GEN
Solar/Wind Harmer
3.798
970663AG2-429 GEN
Solar/Wind Harmer
11.217
970663AG2-429 GEN
Solar/Wind Harmer
1.826
203846AF2-130 C
Solar/Wind Harmer
0.916
20083726HOMER C1
Adder
-95.563
203926AA2-133 GEN
Adder
3.065
20334726NME_Y1-047
Adder
2.777
20390726Y2-042
Adder
2.24
203855AF2-088 C
Solar/Wind Harmer
0.164
971055AG2-654 GEN
Solar/Wind Harmer
0.819
965121AG1-377 GEN
Solar/Wind Harmer
0.901
203961AE2-224 GEN
Solar/Wind Helper
2.002
20092526R32
Solar/Wind Helper
0.952
961581Q1080_CY23
External Queue
34.45887756347656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.04
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.127
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.016
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P2-2_WP-230-005T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P2-2_WP-230-005T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.44 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:954.65
MW Contribution:0.93
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
12.11
20083126HNSMLK 4
50/50
12.11
971703AH1-357 GEN
Solar/Wind Harmer
4.348
971707AH1-359 GEN
Solar/Wind Harmer
4.348
20334926Z1-069 C
Solar/Wind Harmer
4.463
944411AF1-106 GEN
Solar/Wind Harmer
0.409
970335AG2-220 GEN
Solar/Wind Harmer
5.061
971127AH1-005 GEN
Solar/Wind Harmer
3.265
20120126WRREN CT
Adder
9.788
20335126GROZ1-110
Adder
3.176
20335226CANZ2-011
Adder
3.087
203948AG1-140 C
Solar/Wind Harmer
0.352
203962AF1-287 GEN
Solar/Wind Harmer
2.601
962511AG1-100 GEN
Solar/Wind Harmer
0.786
970647AG2-420 GEN
Solar/Wind Harmer
2.57
20084926LAKVU GN
Adder
0.223
203830AF1-094 GEN
Solar/Wind Harmer
0.764
20328326MANOR_T86
Adder
0.18
957161AF2-010 GEN
Solar/Wind Harmer
9.707
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.49
959441AF2-235 GEN
Solar/Wind Harmer
0.375
238219AF1-167 C
Solar/Wind Harmer
1.615
941421AE2-139 GEN
Solar/Wind Harmer
3.471
972271AH1-720 GEN
Adder
7.506
203932AE1-123
Adder
2.09
238202AE2-262_GEN
Solar/Wind Harmer
2.629
971627AH1-313 GEN
Solar/Wind Harmer
10.307
200917MEHOOPANY_G
Solar/Wind Harmer
3.564
203854AF2-039 C
Solar/Wind Harmer
0.337
970679AG2-439 GEN
Solar/Wind Harmer
0.792
945751AF1-240 GEN
Solar/Wind Harmer
0.788
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.365
20082826HNSMLK 1
50/50
12.11
20083026HNSMLK 3
50/50
12.11
20335026MILZ1-092
50/50
4.385
20326126BLOSSBCT
50/50
4.34
970713AG2-456 GEN
Solar/Wind Harmer
17.393
971705AH1-358 GEN
Solar/Wind Harmer
5.056
971709AH1-360 GEN
Solar/Wind Harmer
5.056
944411AF1-106 GEN
Solar/Wind Harmer
3.807
959471AF2-238 GEN
Solar/Wind Harmer
1.018
970337AG2-221 GEN
Solar/Wind Harmer
3.367
970511AG2-327 GEN
Solar/Wind Harmer
1.623
970267AG2-176 GEN
Solar/Wind Harmer
21.537
203860AG1-193 C
Solar/Wind Harmer
0.429
238183AE2-316 GEN
Solar/Wind Harmer
5.79
961971AG1-040 GEN
Solar/Wind Harmer
0.819
203835AF1-098 GEN
Solar/Wind Harmer
3.232
203813AE2-344_GEN
Solar/Wind Harmer
15.097
970647AG2-420 GEN
Solar/Wind Harmer
0.299
20084926LAKVU GN
Adder
0.223
971183AH1-050 GEN
Solar/Wind Harmer
5.068
203954AE2-126 C
Solar/Wind Harmer
0.674
238206AE2-263_GEN
Solar/Wind Harmer
2.45
20072226SHAWVL 2
Adder
13.73
238215AE2-248 C
Solar/Wind Harmer
1.548
20091326SHAW-D
Adder
0.542
972169AH1-667 GEN
Solar/Wind Harmer
1.484
24035802GEN-Y1-012
Adder
0.274
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20088826HIGHLAND
Solar/Wind Helper
0.91
964201AG1-281 GEN
Solar/Wind Helper
0.414
20089226LOOKOUT
Solar/Wind Helper
0.481
964391AG1-301 GEN
Solar/Wind Helper
0.26
20094526CT_V3-030
Solar/Wind Helper
0.226
972077AH1-588 GEN
Solar/Wind Harmer
52.179
972079AH1-589 GEN
Solar/Wind Harmer
42.977
970715AG2-457 GEN
Solar/Wind Harmer
17.393
972075AH1-587 GEN
Solar/Wind Harmer
38.609
20398826ARMNA MT
Solar/Wind Harmer
4.304
203859AF2-294 C
Solar/Wind Harmer
2.847
970313AG2-206 GEN
Solar/Wind Harmer
7.793
970305AG2-200 GEN
Solar/Wind Harmer
3.096
946381AF1-302 GEN
Solar/Wind Harmer
2.897
203980AG1-197 GEN
Solar/Wind Harmer
0.621
203963AG1-253 GEN
Solar/Wind Harmer
0.538
971931AH1-490 GEN
Solar/Wind Harmer
2.598
203979AG1-198 GEN
Solar/Wind Harmer
0.459
971933AH1-491 GEN
Solar/Wind Harmer
2.523
203947AF1-006 C
Solar/Wind Harmer
0.691
238217AF1-153 C O1
Solar/Wind Harmer
0.737
203848AF2-166 C
Solar/Wind Harmer
2.285
216419AE2-001 C
Solar/Wind Harmer
1.962
20084626FORWARD
Solar/Wind Helper
0.391
20088626ARWF_N39
Solar/Wind Helper
1.229
20303426NA_O38_P22
Solar/Wind Helper
1.008
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.051
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.501
20083926HOMER C3
50/50
275.49
20083826HOMER C2
50/50
260.232
20083226HNSMLK 5
50/50
12.11
940863AE2-074 GEN
Solar/Wind Harmer
3.768
203804AE2-113_GEN
Solar/Wind Harmer
8.756
970555AG2-356 GEN
Solar/Wind Harmer
3.367
20083726HOMER C1
Adder
-110.032
970663AG2-429 GEN
Solar/Wind Harmer
9.226
970663AG2-429 GEN
Solar/Wind Harmer
1.502
20084926LAKVU GN
Adder
0.25
966771AG1-548 GEN
Solar/Wind Harmer
18.453
966771AG1-548 GEN
Solar/Wind Harmer
3.576
970677AG2-438 GEN
Solar/Wind Harmer
1.262
203846AF2-130 C
Solar/Wind Harmer
0.653
203926AA2-133 GEN
Adder
2.669
20334726NME_Y1-047
Adder
2.394
203855AF2-088 C
Solar/Wind Harmer
0.162
20390726Y2-042
Adder
1.895
971055AG2-654 GEN
Solar/Wind Harmer
0.672
203961AE2-224 GEN
Solar/Wind Helper
2.595
20092526R32
Solar/Wind Helper
1.18
20091526CHSTN_FL
Solar/Wind Helper
0.359
941231AE2-117 GEN
Solar/Wind Helper
0.246
961581Q1080_CY23
External Queue
35.905757904052734
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.22
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.702
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.117
TVALTFEXP_TVA->PJM
CLTF
0.332
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.063
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.353
MECLTFEXP_MEC->PJM
CLTF
0.878
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.687

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.82 %
Rating:647.0 MVA
Rating Type:A
MVA to Mitigate:736.42
MW Contribution:0.5
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
11.769
20083026HNSMLK 3
50/50
11.769
20335026MILZ1-092
50/50
4.157
20326126BLOSSBCT
50/50
4.059
970713AG2-456 GEN
Solar/Wind Harmer
13.266
971705AH1-358 GEN
Solar/Wind Harmer
4.755
971709AH1-360 GEN
Solar/Wind Harmer
4.755
944411AF1-106 GEN
Solar/Wind Harmer
3.997
970337AG2-221 GEN
Solar/Wind Harmer
2.419
970511AG2-327 GEN
Solar/Wind Harmer
1.062
970267AG2-176 GEN
Solar/Wind Harmer
14.386
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
10
970647AG2-420 GEN
Solar/Wind Harmer
0.283
20084926LAKVU GN
Adder
0.21
971183AH1-050 GEN
Solar/Wind Harmer
4.125
238183AE2-316 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
8.587
24035802GEN-Y1-012
Adder
0.26
238206AE2-263_GEN
Solar/Wind Harmer
0.002
971865AH1-452 GEN
Solar/Wind Harmer
0.503
20091326SHAW-D
Adder
0.334
972169AH1-667 GEN
Solar/Wind Harmer
0.639
20088826HIGHLAND
Solar/Wind Helper
0.93
20089226LOOKOUT
Solar/Wind Helper
0.49
964201AG1-281 GEN
Solar/Wind Helper
0.416
20094526CT_V3-030
Solar/Wind Helper
0.257
20082926HNSMLK 2
50/50
11.769
20083126HNSMLK 4
50/50
11.769
971703AH1-357 GEN
Solar/Wind Harmer
2.853
971707AH1-359 GEN
Solar/Wind Harmer
2.853
20334926Z1-069 C
Solar/Wind Harmer
1.059
970335AG2-220 GEN
Solar/Wind Harmer
3.421
971127AH1-005 GEN
Solar/Wind Harmer
2.494
20120126WRREN CT
Adder
8.901
203948AG1-140 C
Solar/Wind Harmer
0.251
203962AF1-287 GEN
Solar/Wind Harmer
1.723
970647AG2-420 GEN
Solar/Wind Harmer
1.698
20335126GROZ1-110
Adder
2.841
20335226CANZ2-011
Adder
2.761
20084926LAKVU GN
Adder
0.21
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
6.358
971185AH1-051 GEN
Solar/Wind Harmer
2.475
971355AH1-158 GEN
Solar/Wind Harmer
4.125
20328326MANOR_T86
Adder
0.165
238219AF1-167 C
Solar/Wind Harmer
1.049
972271AH1-720 GEN
Adder
6.781
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.94
200917MEHOOPANY_G
Solar/Wind Harmer
0.33
970679AG2-439 GEN
Solar/Wind Harmer
0.458
238202AE2-262_GEN
Solar/Wind Harmer
0.002
971627AH1-313 GEN
Solar/Wind Harmer
3.936
203854AF2-039 C
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Helper
0.504
20089026BF_G21_K23
Solar/Wind Helper
0.399
202652Y1-033 WT C
Solar/Wind Helper
0.372
972077AH1-588 GEN
Solar/Wind Harmer
34.236
972079AH1-589 GEN
Solar/Wind Harmer
40.417
970715AG2-457 GEN
Solar/Wind Harmer
13.266
972075AH1-587 GEN
Solar/Wind Harmer
24.541
20398826ARMNA MT
Solar/Wind Harmer
0.069
203859AF2-294 C
Solar/Wind Harmer
1.886
970313AG2-206 GEN
Solar/Wind Harmer
5.1
970305AG2-200 GEN
Solar/Wind Harmer
1.964
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.723
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Harmer
0.056
203848AF2-166 C
Solar/Wind Harmer
1.492
20084626FORWARD
Solar/Wind Helper
0.399
20088926STNY CRK
Solar/Wind Helper
0.82
20083426SW_E13_K22
Solar/Wind Helper
0.056
20088626ARWF_N39
Solar/Wind Helper
1.176
20303426NA_O38_P22
Solar/Wind Helper
0.964
203940AF1-140 C
Solar/Wind Helper
0.372
944781AF1-143 GEN
Solar/Wind Helper
2.09
203955AF1-039 C O1
Solar/Wind Helper
0.245
946071AF1-272 GEN
Solar/Wind Helper
1.627
20083926HOMER C3
50/50
272.069
20083826HOMER C2
50/50
257.001
20083226HNSMLK 5
50/50
11.769
20083726HOMER C1
Adder
-111.627
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.199
970663AG2-429 GEN
Solar/Wind Harmer
6.483
970663AG2-429 GEN
Solar/Wind Harmer
1.417
20084926LAKVU GN
Adder
0.236
966771AG1-548 GEN
Solar/Wind Harmer
2.769
966771AG1-548 GEN
Solar/Wind Harmer
3.462
970677AG2-438 GEN
Solar/Wind Harmer
0.927
203926AA2-133 GEN
Adder
2.454
20334726NME_Y1-047
Adder
2.206
20390726Y2-042
Adder
1.742
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.52
203961AE2-224 GEN
Solar/Wind Helper
2.523
20092526R32
Solar/Wind Helper
1.205
20091526CHSTN_FL
Solar/Wind Helper
0.389
961581Q1080_CY23
External Queue
36.97114562988281
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.012
LAGNLTFEXP_LAGN->PJM
CLTF
0.64
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.112
TVALTFEXP_TVA->PJM
CLTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.241
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.231
MECLTFEXP_MEC->PJM
CLTF
0.801
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM NorthLTFEXP_CBM-N->PJM
CBM
35.369
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.185

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.78 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:940.95
MW Contribution:1.14
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
13.162
20083126HNSMLK 4
50/50
13.162
971703AH1-357 GEN
Solar/Wind Harmer
4.4
971707AH1-359 GEN
Solar/Wind Harmer
4.4
20334926Z1-069 C
Solar/Wind Harmer
4.526
944411AF1-106 GEN
Solar/Wind Harmer
0.415
970335AG2-220 GEN
Solar/Wind Harmer
5.101
971127AH1-005 GEN
Solar/Wind Harmer
3.291
20120126WRREN CT
Adder
9.836
238219AF1-167 C
Solar/Wind Harmer
2.025
970647AG2-420 GEN
Solar/Wind Harmer
2.905
971185AH1-051 GEN
Solar/Wind Harmer
3.469
971355AH1-158 GEN
Solar/Wind Harmer
4.034
203856AF2-165 C
Solar/Wind Harmer
1.693
203948AG1-140 C
Solar/Wind Harmer
0.367
959441AF2-235 GEN
Solar/Wind Harmer
0.419
962511AG1-100 GEN
Solar/Wind Harmer
0.834
203962AF1-287 GEN
Solar/Wind Harmer
2.757
957161AF2-010 GEN
Solar/Wind Harmer
10.433
203830AF1-094 GEN
Solar/Wind Harmer
0.82
20084926LAKVU GN
Adder
0.232
20335126GROZ1-110
Adder
3.099
20335226CANZ2-011
Adder
3.012
203932AE1-123
Adder
2.515
20328326MANOR_T86
Adder
0.179
972271AH1-720 GEN
Adder
7.405
941421AE2-139 GEN
Solar/Wind Harmer
3.392
200917MEHOOPANY_G
Solar/Wind Harmer
3.576
970679AG2-439 GEN
Solar/Wind Harmer
0.798
238202AE2-262_GEN
Solar/Wind Harmer
1.779
971627AH1-313 GEN
Solar/Wind Harmer
6.977
203854AF2-039 C
Solar/Wind Harmer
0.265
945751AF1-240 GEN
Solar/Wind Harmer
1.012
20089126CSLMN_L13
Solar/Wind Helper
0.471
20089026BF_G21_K23
Solar/Wind Helper
0.373
202652Y1-033 WT C
Solar/Wind Helper
0.351
20082826HNSMLK 1
50/50
13.162
20083026HNSMLK 3
50/50
13.162
20335026MILZ1-092
50/50
4.448
20326126BLOSSBCT
50/50
4.359
970713AG2-456 GEN
Solar/Wind Harmer
17.6
971705AH1-358 GEN
Solar/Wind Harmer
5.116
971709AH1-360 GEN
Solar/Wind Harmer
5.116
944411AF1-106 GEN
Solar/Wind Harmer
3.862
959471AF2-238 GEN
Solar/Wind Harmer
1.024
970337AG2-221 GEN
Solar/Wind Harmer
3.385
970511AG2-327 GEN
Solar/Wind Harmer
1.636
203860AG1-193 C
Solar/Wind Harmer
0.475
970267AG2-176 GEN
Solar/Wind Harmer
23.253
238183AE2-316 GEN
Solar/Wind Harmer
6.305
970647AG2-420 GEN
Solar/Wind Harmer
0.338
961971AG1-040 GEN
Solar/Wind Harmer
0.876
971183AH1-050 GEN
Solar/Wind Harmer
5.782
203835AF1-098 GEN
Solar/Wind Harmer
3.35
203813AE2-344_GEN
Solar/Wind Harmer
16.003
20084926LAKVU GN
Adder
0.232
203954AE2-126 C
Solar/Wind Harmer
0.595
20072226SHAWVL 2
Adder
10.566
238206AE2-263_GEN
Solar/Wind Harmer
1.658
24035802GEN-Y1-012
Adder
0.283
971865AH1-452 GEN
Solar/Wind Harmer
1.144
20091326SHAW-D
Adder
0.426
972169AH1-667 GEN
Solar/Wind Harmer
1.167
238215AE2-248 C
Solar/Wind Harmer
0.78
20088826HIGHLAND
Solar/Wind Helper
0.858
20089226LOOKOUT
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.375
20083926HOMER C3
50/50
285.029
20083826HOMER C2
50/50
269.243
20083226HNSMLK 5
50/50
13.162
940863AE2-074 GEN
Solar/Wind Harmer
3.814
203804AE2-113_GEN
Solar/Wind Harmer
8.618
970555AG2-356 GEN
Solar/Wind Harmer
3.385
970663AG2-429 GEN
Solar/Wind Harmer
11.496
970663AG2-429 GEN
Solar/Wind Harmer
1.871
20083726HOMER C1
Adder
-104.741
970677AG2-438 GEN
Solar/Wind Harmer
1.353
966771AG1-548 GEN
Solar/Wind Harmer
19.741
966771AG1-548 GEN
Solar/Wind Harmer
3.826
203846AF2-130 C
Solar/Wind Harmer
0.764
20084926LAKVU GN
Adder
0.261
203926AA2-133 GEN
Adder
2.667
20334726NME_Y1-047
Adder
2.402
20390726Y2-042
Adder
1.91
971055AG2-654 GEN
Solar/Wind Harmer
0.981
203855AF2-088 C
Solar/Wind Harmer
0.128
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.322
20091526CHSTN_FL
Solar/Wind Helper
0.335
972077AH1-588 GEN
Solar/Wind Harmer
52.799
972079AH1-589 GEN
Solar/Wind Harmer
43.488
970715AG2-457 GEN
Solar/Wind Harmer
17.6
972075AH1-587 GEN
Solar/Wind Harmer
38.338
20398826ARMNA MT
Solar/Wind Harmer
4.359
203859AF2-294 C
Solar/Wind Harmer
2.894
970313AG2-206 GEN
Solar/Wind Harmer
7.852
970305AG2-200 GEN
Solar/Wind Harmer
3.111
946381AF1-302 GEN
Solar/Wind Harmer
3.155
203980AG1-197 GEN
Solar/Wind Harmer
0.665
203963AG1-253 GEN
Solar/Wind Harmer
0.56
971931AH1-490 GEN
Solar/Wind Harmer
2.76
203979AG1-198 GEN
Solar/Wind Harmer
0.492
971933AH1-491 GEN
Solar/Wind Harmer
2.707
203848AF2-166 C
Solar/Wind Harmer
2.673
203947AF1-006 C
Solar/Wind Harmer
0.726
238217AF1-153 C O1
Solar/Wind Harmer
0.695
216419AE2-001 C
Solar/Wind Harmer
1.035
20084626FORWARD
Solar/Wind Helper
0.371
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.761
20088626ARWF_N39
Solar/Wind Helper
1.075
20303426NA_O38_P22
Solar/Wind Helper
0.881
203940AF1-140 C
Solar/Wind Helper
0.339
944781AF1-143 GEN
Solar/Wind Helper
1.956
203955AF1-039 C O1
Solar/Wind Helper
0.231
946071AF1-272 GEN
Solar/Wind Helper
1.436
961581Q1080_CY23
External Queue
37.79337692260742
LGEELTFEXP_LGEE->PJM
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.167
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.058
LAGNLTFEXP_LAGN->PJM
CLTF
0.47
TVALTFEXP_TVA->PJM
CLTF
0.217
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.06
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.907
MECLTFEXP_MEC->PJM
CLTF
0.656
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.028

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P1-3_DRT-230-003-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P1-3_DRT-230-003-DRT_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.51 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:930.45
MW Contribution:0.63
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
14.837
20083126HNSMLK 4
50/50
14.837
971703AH1-357 GEN
Solar/Wind Harmer
3.597
971707AH1-359 GEN
Solar/Wind Harmer
3.597
20334926Z1-069 C
Solar/Wind Harmer
1.335
970335AG2-220 GEN
Solar/Wind Harmer
4.313
971127AH1-005 GEN
Solar/Wind Harmer
3.145
20120126WRREN CT
Adder
11.223
203948AG1-140 C
Solar/Wind Harmer
0.316
203962AF1-287 GEN
Solar/Wind Harmer
2.172
970647AG2-420 GEN
Solar/Wind Harmer
2.14
20335126GROZ1-110
Adder
3.581
20335226CANZ2-011
Adder
3.481
20084926LAKVU GN
Adder
0.265
203830AF1-094 GEN
Solar/Wind Harmer
0.002
957161AF2-010 GEN
Solar/Wind Harmer
8.016
971185AH1-051 GEN
Solar/Wind Harmer
3.121
971355AH1-158 GEN
Solar/Wind Harmer
5.201
20328326MANOR_T86
Adder
0.208
238219AF1-167 C
Solar/Wind Harmer
1.323
972271AH1-720 GEN
Adder
8.55
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
2.446
200917MEHOOPANY_G
Solar/Wind Harmer
0.416
970679AG2-439 GEN
Solar/Wind Harmer
0.577
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.962
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.687
20089126CSLMN_L13
Solar/Wind Helper
0.635
20089026BF_G21_K23
Solar/Wind Helper
0.503
202652Y1-033 WT C
Solar/Wind Helper
0.469
972077AH1-588 GEN
Solar/Wind Harmer
43.163
972079AH1-589 GEN
Solar/Wind Harmer
50.956
970715AG2-457 GEN
Solar/Wind Harmer
16.726
972075AH1-587 GEN
Solar/Wind Harmer
30.94
20398826ARMNA MT
Solar/Wind Harmer
0.087
203859AF2-294 C
Solar/Wind Harmer
2.377
970313AG2-206 GEN
Solar/Wind Harmer
6.43
970305AG2-200 GEN
Solar/Wind Harmer
2.477
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.503
971931AH1-490 GEN
Solar/Wind Harmer
2.172
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
2.093
203947AF1-006 C
Solar/Wind Harmer
0.07
203848AF2-166 C
Solar/Wind Harmer
1.881
216419AE2-001 C
Solar/Wind Harmer
0.704
20084626FORWARD
Solar/Wind Helper
0.503
20088926STNY CRK
Solar/Wind Helper
1.034
20083426SW_E13_K22
Solar/Wind Helper
0.07
20088626ARWF_N39
Solar/Wind Helper
1.482
20303426NA_O38_P22
Solar/Wind Helper
1.215
203940AF1-140 C
Solar/Wind Helper
0.469
944781AF1-143 GEN
Solar/Wind Helper
2.635
203955AF1-039 C O1
Solar/Wind Helper
0.309
946071AF1-272 GEN
Solar/Wind Helper
2.052
20083926HOMER C3
50/50
343.015
20083826HOMER C2
50/50
324.017
20083226HNSMLK 5
50/50
14.837
20083726HOMER C1
Adder
-140.736
203804AE2-113_GEN
Solar/Wind Harmer
0.011
970555AG2-356 GEN
Solar/Wind Harmer
2.772
970663AG2-429 GEN
Solar/Wind Harmer
8.174
970663AG2-429 GEN
Solar/Wind Harmer
1.786
20084926LAKVU GN
Adder
0.298
966771AG1-548 GEN
Solar/Wind Harmer
3.492
966771AG1-548 GEN
Solar/Wind Harmer
4.365
970677AG2-438 GEN
Solar/Wind Harmer
1.168
203926AA2-133 GEN
Adder
3.094
20334726NME_Y1-047
Adder
2.781
20390726Y2-042
Adder
2.196
203855AF2-088 C
Solar/Wind Harmer
0
971055AG2-654 GEN
Solar/Wind Harmer
0.655
203961AE2-224 GEN
Solar/Wind Helper
3.181
20092526R32
Solar/Wind Helper
1.519
20091526CHSTN_FL
Solar/Wind Helper
0.491
941231AE2-117 GEN
Solar/Wind Helper
0.269
20082826HNSMLK 1
50/50
14.837
20083026HNSMLK 3
50/50
14.837
20335026MILZ1-092
50/50
5.241
20326126BLOSSBCT
50/50
5.118
970713AG2-456 GEN
Solar/Wind Harmer
16.726
971705AH1-358 GEN
Solar/Wind Harmer
5.995
971709AH1-360 GEN
Solar/Wind Harmer
5.995
944411AF1-106 GEN
Solar/Wind Harmer
5.039
970337AG2-221 GEN
Solar/Wind Harmer
3.049
970511AG2-327 GEN
Solar/Wind Harmer
1.34
970267AG2-176 GEN
Solar/Wind Harmer
18.137
203860AG1-193 C
Solar/Wind Harmer
0.001
203835AF1-098 GEN
Solar/Wind Harmer
0.007
203813AE2-344_GEN
Solar/Wind Harmer
12.608
970647AG2-420 GEN
Solar/Wind Harmer
0.357
20084926LAKVU GN
Adder
0.265
971183AH1-050 GEN
Solar/Wind Harmer
5.201
238183AE2-316 GEN
Solar/Wind Harmer
0.006
203954AE2-126 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
10.826
24035802GEN-Y1-012
Adder
0.327
238206AE2-263_GEN
Solar/Wind Harmer
0.003
971865AH1-452 GEN
Solar/Wind Harmer
0.634
20091326SHAW-D
Adder
0.422
972169AH1-667 GEN
Solar/Wind Harmer
0.805
238215AE2-248 C
Solar/Wind Harmer
0.525
20088826HIGHLAND
Solar/Wind Helper
1.172
20089226LOOKOUT
Solar/Wind Helper
0.618
964201AG1-281 GEN
Solar/Wind Helper
0.524
20094526CT_V3-030
Solar/Wind Helper
0.325
964391AG1-301 GEN
Solar/Wind Helper
0.277
961581Q1080_CY23
External Queue
46.6118278503418
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.253
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.015
LAGNLTFEXP_LAGN->PJM
CLTF
0.807
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.141
TVALTFEXP_TVA->PJM
CLTF
0.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.552
MECLTFEXP_MEC->PJM
CLTF
1.01
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM NorthLTFEXP_CBM-N->PJM
CBM
44.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.537

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:898.89
MW Contribution:0.76
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
12.408
20083126HNSMLK 4
50/50
12.408
971703AH1-357 GEN
Solar/Wind Harmer
4.225
971707AH1-359 GEN
Solar/Wind Harmer
4.225
20334926Z1-069 C
Solar/Wind Harmer
4.357
944411AF1-106 GEN
Solar/Wind Harmer
0.4
970335AG2-220 GEN
Solar/Wind Harmer
4.898
971127AH1-005 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
9.318
203948AG1-140 C
Solar/Wind Harmer
0.348
970647AG2-420 GEN
Solar/Wind Harmer
2.646
962511AG1-100 GEN
Solar/Wind Harmer
0.787
203962AF1-287 GEN
Solar/Wind Harmer
2.602
971185AH1-051 GEN
Solar/Wind Harmer
3.141
971355AH1-158 GEN
Solar/Wind Harmer
3.653
203856AF2-165 C
Solar/Wind Harmer
1.536
238219AF1-167 C
Solar/Wind Harmer
1.719
959441AF2-235 GEN
Solar/Wind Harmer
0.383
957161AF2-010 GEN
Solar/Wind Harmer
9.735
203830AF1-094 GEN
Solar/Wind Harmer
0.766
20335126GROZ1-110
Adder
2.949
20335226CANZ2-011
Adder
2.867
20084926LAKVU GN
Adder
0.22
20328326MANOR_T86
Adder
0.171
203932AE1-123
Adder
2.197
972271AH1-720 GEN
Adder
7.041
941421AE2-139 GEN
Solar/Wind Harmer
3.22
200917MEHOOPANY_G
Solar/Wind Harmer
3.404
970679AG2-439 GEN
Solar/Wind Harmer
0.756
238202AE2-262_GEN
Solar/Wind Harmer
1.583
971627AH1-313 GEN
Solar/Wind Harmer
6.208
203854AF2-039 C
Solar/Wind Harmer
0.232
945751AF1-240 GEN
Solar/Wind Harmer
0.814
20089126CSLMN_L13
Solar/Wind Helper
0.494
20089026BF_G21_K23
Solar/Wind Helper
0.391
202652Y1-033 WT C
Solar/Wind Helper
0.366
20082826HNSMLK 1
50/50
12.408
20083026HNSMLK 3
50/50
12.408
20335026MILZ1-092
50/50
4.281
20326126BLOSSBCT
50/50
4.187
970713AG2-456 GEN
Solar/Wind Harmer
16.899
971705AH1-358 GEN
Solar/Wind Harmer
4.912
971709AH1-360 GEN
Solar/Wind Harmer
4.912
944411AF1-106 GEN
Solar/Wind Harmer
3.717
959471AF2-238 GEN
Solar/Wind Harmer
0.983
970337AG2-221 GEN
Solar/Wind Harmer
3.251
970511AG2-327 GEN
Solar/Wind Harmer
1.571
970267AG2-176 GEN
Solar/Wind Harmer
21.827
203860AG1-193 C
Solar/Wind Harmer
0.44
961971AG1-040 GEN
Solar/Wind Harmer
0.824
238183AE2-316 GEN
Solar/Wind Harmer
5.58
970647AG2-420 GEN
Solar/Wind Harmer
0.308
203835AF1-098 GEN
Solar/Wind Harmer
3.172
203813AE2-344_GEN
Solar/Wind Harmer
15.102
971183AH1-050 GEN
Solar/Wind Harmer
5.235
20084926LAKVU GN
Adder
0.22
203954AE2-126 C
Solar/Wind Harmer
0.542
20072226SHAWVL 2
Adder
9.429
24035802GEN-Y1-012
Adder
0.271
238206AE2-263_GEN
Solar/Wind Harmer
1.476
20091326SHAW-D
Adder
0.373
972169AH1-667 GEN
Solar/Wind Harmer
1.02
971865AH1-452 GEN
Solar/Wind Harmer
0.761
20088826HIGHLAND
Solar/Wind Helper
0.908
20089226LOOKOUT
Solar/Wind Helper
0.481
964201AG1-281 GEN
Solar/Wind Helper
0.403
20094526CT_V3-030
Solar/Wind Helper
0.241
972077AH1-588 GEN
Solar/Wind Harmer
50.696
972079AH1-589 GEN
Solar/Wind Harmer
41.756
970715AG2-457 GEN
Solar/Wind Harmer
16.899
972075AH1-587 GEN
Solar/Wind Harmer
36.551
20398826ARMNA MT
Solar/Wind Harmer
4.195
203859AF2-294 C
Solar/Wind Harmer
2.784
970313AG2-206 GEN
Solar/Wind Harmer
7.539
970305AG2-200 GEN
Solar/Wind Harmer
2.947
203980AG1-197 GEN
Solar/Wind Harmer
0.626
203963AG1-253 GEN
Solar/Wind Harmer
0.532
946381AF1-302 GEN
Solar/Wind Harmer
2.792
971931AH1-490 GEN
Solar/Wind Harmer
2.603
203979AG1-198 GEN
Solar/Wind Harmer
0.46
971933AH1-491 GEN
Solar/Wind Harmer
2.528
203947AF1-006 C
Solar/Wind Harmer
0.687
203848AF2-166 C
Solar/Wind Harmer
2.378
238217AF1-153 C O1
Solar/Wind Harmer
0.626
216419AE2-001 C
Solar/Wind Harmer
0.898
20084626FORWARD
Solar/Wind Helper
0.391
20083426SW_E13_K22
Solar/Wind Helper
0.055
20088926STNY CRK
Solar/Wind Helper
0.803
20088626ARWF_N39
Solar/Wind Helper
1.142
20303426NA_O38_P22
Solar/Wind Helper
0.936
203940AF1-140 C
Solar/Wind Helper
0.362
944781AF1-143 GEN
Solar/Wind Helper
2.052
203955AF1-039 C O1
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Helper
1.602
20083926HOMER C3
50/50
277.61
20083826HOMER C2
50/50
262.235
20083226HNSMLK 5
50/50
12.408
940863AE2-074 GEN
Solar/Wind Harmer
3.667
203804AE2-113_GEN
Solar/Wind Harmer
8.186
970555AG2-356 GEN
Solar/Wind Harmer
3.251
20083726HOMER C1
Adder
-109.082
970663AG2-429 GEN
Solar/Wind Harmer
9.987
970663AG2-429 GEN
Solar/Wind Harmer
1.626
970677AG2-438 GEN
Solar/Wind Harmer
1.264
966771AG1-548 GEN
Solar/Wind Harmer
18.467
966771AG1-548 GEN
Solar/Wind Harmer
3.579
20084926LAKVU GN
Adder
0.248
203846AF2-130 C
Solar/Wind Harmer
0.679
203926AA2-133 GEN
Adder
2.542
20334726NME_Y1-047
Adder
2.287
20390726Y2-042
Adder
1.81
203855AF2-088 C
Solar/Wind Harmer
0.112
971055AG2-654 GEN
Solar/Wind Harmer
0.641
20092526R32
Solar/Wind Helper
1.178
203961AE2-224 GEN
Solar/Wind Helper
2.456
20091526CHSTN_FL
Solar/Wind Helper
0.371
961581Q1080_CY23
External Queue
37.30971908569336
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
0.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.036
TVALTFEXP_TVA->PJM
CLTF
0.277
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.138
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.867

Details for 26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer l/o PN_P1-2_PN-345-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer
Contingency Name:
PN_P1-2_PN-345-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.82 %
Rating:827.0 MVA
Rating Type:B
MVA to Mitigate:842.02
MW Contribution:0.62
Bus #Bus NameTypeMW Contribution
20082826HNSMLK 1
50/50
18.564
20083026HNSMLK 3
50/50
18.564
20335026MILZ1-092
50/50
4.382
20326126BLOSSBCT
50/50
4.303
970713AG2-456 GEN
Solar/Wind Harmer
13.579
971705AH1-358 GEN
Solar/Wind Harmer
4.867
971709AH1-360 GEN
Solar/Wind Harmer
4.867
944411AF1-106 GEN
Solar/Wind Harmer
4.214
970337AG2-221 GEN
Solar/Wind Harmer
2.569
970511AG2-327 GEN
Solar/Wind Harmer
1.129
238183AE2-316 GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.004
203954AE2-126 C
Solar/Wind Harmer
0.001
971183AH1-050 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
0.192
20084926LAKVU GN
Adder
0.141
203860AG1-193 C
Solar/Wind Harmer
0
203813AE2-344_GEN
Solar/Wind Harmer
5.955
970267AG2-176 GEN
Solar/Wind Harmer
7.41
20072226SHAWVL 2
Adder
9.384
971865AH1-452 GEN
Solar/Wind Harmer
0.62
238206AE2-263_GEN
Solar/Wind Harmer
0.003
20091326SHAW-D
Adder
0.376
972169AH1-667 GEN
Solar/Wind Harmer
0.717
238215AE2-248 C
Solar/Wind Harmer
0.484
20088826HIGHLAND
Solar/Wind Helper
0.802
20089226LOOKOUT
Solar/Wind Helper
0.425
964201AG1-281 GEN
Solar/Wind Helper
0.352
20082926HNSMLK 2
50/50
18.564
20083126HNSMLK 4
50/50
18.564
20334926Z1-069 C
Solar/Wind Harmer
1.108
971703AH1-357 GEN
Solar/Wind Harmer
2.92
971707AH1-359 GEN
Solar/Wind Harmer
2.92
970335AG2-220 GEN
Solar/Wind Harmer
3.635
971127AH1-005 GEN
Solar/Wind Harmer
2.651
20335126GROZ1-110
Adder
3.032
20335226CANZ2-011
Adder
2.947
20120126WRREN CT
Adder
7.924
20328326MANOR_T86
Adder
0.176
238219AF1-167 C
Solar/Wind Harmer
1.164
972271AH1-720 GEN
Adder
7.271
941421AE2-139 GEN
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.355
203932AE1-123
Adder
1.872
203948AG1-140 C
Solar/Wind Harmer
0.18
971185AH1-051 GEN
Solar/Wind Harmer
1.766
971355AH1-158 GEN
Solar/Wind Harmer
2.943
970647AG2-420 GEN
Solar/Wind Harmer
1.151
957161AF2-010 GEN
Solar/Wind Harmer
4.365
203830AF1-094 GEN
Solar/Wind Harmer
0.001
970679AG2-439 GEN
Solar/Wind Harmer
0.498
20084926LAKVU GN
Adder
0.141
203962AF1-287 GEN
Solar/Wind Harmer
1.029
238202AE2-262_GEN
Solar/Wind Harmer
0.003
971627AH1-313 GEN
Solar/Wind Harmer
4.345
203854AF2-039 C
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.566
20089126CSLMN_L13
Solar/Wind Helper
0.437
20089026BF_G21_K23
Solar/Wind Helper
0.346
202652Y1-033 WT C
Solar/Wind Helper
0.322
20083926HOMER C3
50/50
294.484
20083826HOMER C2
50/50
278.174
20083226HNSMLK 5
50/50
18.564
203804AE2-113_GEN
Solar/Wind Harmer
0.009
970555AG2-356 GEN
Solar/Wind Harmer
2.336
20083726HOMER C1
Adder
-98.732
970663AG2-429 GEN
Solar/Wind Harmer
7.36
970663AG2-429 GEN
Solar/Wind Harmer
1.608
203926AA2-133 GEN
Adder
2.63
20334726NME_Y1-047
Adder
2.373
970677AG2-438 GEN
Solar/Wind Harmer
0.635
966771AG1-548 GEN
Solar/Wind Harmer
1.891
966771AG1-548 GEN
Solar/Wind Harmer
2.364
20390726Y2-042
Adder
1.896
20084926LAKVU GN
Adder
0.158
971055AG2-654 GEN
Solar/Wind Harmer
0.641
203855AF2-088 C
Solar/Wind Harmer
0
203961AE2-224 GEN
Solar/Wind Helper
2.177
20092526R32
Solar/Wind Helper
1.04
20091526CHSTN_FL
Solar/Wind Helper
0.318
972077AH1-588 GEN
Solar/Wind Harmer
35.043
972079AH1-589 GEN
Solar/Wind Harmer
41.37
970715AG2-457 GEN
Solar/Wind Harmer
13.579
20398826ARMNA MT
Solar/Wind Harmer
0.073
972075AH1-587 GEN
Solar/Wind Harmer
25.36
203859AF2-294 C
Solar/Wind Harmer
1.99
970313AG2-206 GEN
Solar/Wind Harmer
5.42
970305AG2-200 GEN
Solar/Wind Harmer
1.749
203963AG1-253 GEN
Solar/Wind Harmer
0.286
203848AF2-166 C
Solar/Wind Harmer
1.259
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.137
203947AF1-006 C
Solar/Wind Harmer
0.035
971931AH1-490 GEN
Solar/Wind Harmer
1.006
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
0.643
20084626FORWARD
Solar/Wind Helper
0.347
20083426SW_E13_K22
Solar/Wind Helper
0.048
20088926STNY CRK
Solar/Wind Helper
0.71
20088626ARWF_N39
Solar/Wind Helper
1.008
20303426NA_O38_P22
Solar/Wind Helper
0.827
203940AF1-140 C
Solar/Wind Helper
0.318
944781AF1-143 GEN
Solar/Wind Helper
1.814
203955AF1-039 C O1
Solar/Wind Helper
0.213
946071AF1-272 GEN
Solar/Wind Helper
1.339
961581Q1080_CY23
External Queue
42.41039276123047
LGEELTFEXP_LGEE->PJM
CLTF
0.139
WECLTFEXP_WEC->PJM
CLTF
0.096
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
0.242
TVALTFEXP_TVA->PJM
CLTF
0.11
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.019
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.475
MECLTFEXP_MEC->PJM
CLTF
0.372
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CBM NorthLTFEXP_CBM-N->PJM
CBM
38.509
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.201

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.95 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1312.71
MW Contribution:1.13
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.475
20216026CON.GEN2
50/50
0.034
970125AG2-091 GEN
Solar/Wind Harmer
1.837
971879AH1-460 GEN
Solar/Wind Harmer
20.153
20079426CONEMAGH
Adder
3.673
203841AF2-001_GEN
Solar/Wind Harmer
6.086
971541AH1-268 GEN
Solar/Wind Harmer
10.099
971419AH1-201 GEN
Solar/Wind Harmer
8.865
970899AG2-561 GEN
Solar/Wind Harmer
5.475
203818AF1-086 GEN
Solar/Wind Harmer
6.305
20089126CSLMN_L13
Solar/Wind Harmer
2.008
20089026BF_G21_K23
Solar/Wind Harmer
1.589
960051AF2-296 GEN
Solar/Wind Harmer
4.314
945751AF1-240 GEN
Solar/Wind Harmer
3.376
971703AH1-357 GEN
Solar/Wind Harmer
4.068
971707AH1-359 GEN
Solar/Wind Harmer
4.068
965131AG1-378 GEN
Solar/Wind Harmer
3.983
20334926Z1-069 C
Solar/Wind Harmer
4.096
20082926HNSMLK 2
Adder
10.319
20083126HNSMLK 4
Adder
10.319
203854AF2-039 C
Solar/Wind Harmer
0.712
202652Y1-033 WT C
Solar/Wind Harmer
1.626
203932AE1-123
Adder
3.315
944411AF1-106 GEN
Solar/Wind Harmer
0.373
971185AH1-051 GEN
Solar/Wind Harmer
3.853
971355AH1-158 GEN
Solar/Wind Harmer
4.48
203856AF2-165 C
Solar/Wind Harmer
1.87
20120126WRREN CT
Adder
9.907
970647AG2-420 GEN
Solar/Wind Harmer
3.129
970335AG2-220 GEN
Solar/Wind Harmer
4.71
971127AH1-005 GEN
Solar/Wind Harmer
3.038
959441AF2-235 GEN
Solar/Wind Harmer
0.45
238219AF1-167 C
Solar/Wind Harmer
1.972
238202AE2-262_GEN
Solar/Wind Harmer
3.699
971627AH1-313 GEN
Solar/Wind Harmer
14.502
20335126GROZ1-110
Adder
3.201
20335226CANZ2-011
Adder
3.111
957161AF2-010 GEN
Solar/Wind Harmer
10.289
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.336
203962AF1-287 GEN
Solar/Wind Harmer
2.519
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.532
972271AH1-720 GEN
Adder
7.499
200917MEHOOPANY_G
Solar/Wind Harmer
3.471
970679AG2-439 GEN
Solar/Wind Harmer
0.783
970643AG2-418 GEN
Solar/Wind Harmer
1.57
237043AE2-125 C
Solar/Wind Harmer
0.185
203843AF2-002_GEN
Solar/Wind Harmer
3.043
970631AG2-411 GEN
Solar/Wind Harmer
19.093
20088826HIGHLAND
Solar/Wind Harmer
4.899
957561AF2-050 GEN
Solar/Wind Harmer
14.764
971279AH1-102 GEN
Solar/Wind Harmer
23.731
971423AH1-203 GEN
Solar/Wind Harmer
19.36
20094526CT_V3-030
Solar/Wind Harmer
1.946
964201AG1-281 GEN
Solar/Wind Harmer
1.65
20089226LOOKOUT
Solar/Wind Harmer
1.955
203987AE2-118 C
Solar/Wind Harmer
4.298
970713AG2-456 GEN
Solar/Wind Harmer
16.27
971705AH1-358 GEN
Solar/Wind Harmer
4.73
971709AH1-360 GEN
Solar/Wind Harmer
4.73
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.319
20083026HNSMLK 3
Adder
10.319
20091326SHAW-D
Adder
1.146
972169AH1-667 GEN
Solar/Wind Harmer
3.136
203954AE2-126 C
Solar/Wind Harmer
1.044
20326126BLOSSBCT
Adder
3.822
20335026MILZ1-092
Adder
3.771
20083726HOMER C1
50/50
274.812
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.267
20083926HOMER C3
50/50
227.884
20083826HOMER C2
50/50
215.262
20092526R32
Solar/Wind Harmer
5.249
203961AE2-224 GEN
Solar/Wind Harmer
8.943
203844AF2-092 C
Solar/Wind Harmer
3.471
203850AG1-041 C
Solar/Wind Harmer
3.468
20091526CHSTN_FL
Solar/Wind Harmer
2.312
20090526Q36
Solar/Wind Harmer
3.421
203993AD2-133_GEN1
Solar/Wind Harmer
3.421
940863AE2-074 GEN
Solar/Wind Harmer
3.497
941231AE2-117 GEN
Solar/Wind Harmer
1.21
965121AG1-377 GEN
Solar/Wind Harmer
3.983
203804AE2-113_GEN
Solar/Wind Harmer
9.118
20083226HNSMLK 5
Adder
10.319
203855AF2-088 C
Solar/Wind Harmer
0.343
203846AF2-130 C
Solar/Wind Harmer
0.929
970555AG2-356 GEN
Solar/Wind Harmer
3.145
970663AG2-429 GEN
Solar/Wind Harmer
10.588
970663AG2-429 GEN
Solar/Wind Harmer
1.724
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.253
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.597
971321AH1-140 GEN
Solar/Wind Harmer
14.986
971321AH1-140 GEN
Solar/Wind Harmer
2.904
20334726NME_Y1-047
Adder
2.332
20390726Y2-042
Adder
1.874
971055AG2-654 GEN
Solar/Wind Harmer
0.689
20080926SITHE
50/50
0.884
946071AF1-272 GEN
Solar/Wind Harmer
11.274
203857AF2-221 C
Solar/Wind Harmer
4.592
970123AG2-090 GEN
Solar/Wind Harmer
4.286
203839AF1-321 GEN
Solar/Wind Harmer
6.086
20084626FORWARD
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
1.422
971441AH1-212 GEN
Solar/Wind Harmer
5.714
20088626ARWF_N39
Solar/Wind Harmer
5.246
20303426NA_O38_P22
Solar/Wind Harmer
4.247
20088926STNY CRK
Solar/Wind Harmer
3.415
971427AH1-205 GEN
Solar/Wind Harmer
4.123
20083426SW_E13_K22
Solar/Wind Harmer
0.807
944781AF1-143 GEN
Solar/Wind Harmer
6.882
203853AF1-134 C O1
Solar/Wind Harmer
1.304
972077AH1-588 GEN
Solar/Wind Harmer
48.81
972079AH1-589 GEN
Solar/Wind Harmer
40.202
970715AG2-457 GEN
Solar/Wind Harmer
16.27
203952AE2-129 C
Solar/Wind Harmer
1.206
203946AE2-131 C
Solar/Wind Harmer
1.204
962411AG1-090 GEN
Solar/Wind Harmer
18.919
972075AH1-587 GEN
Solar/Wind Harmer
38.875
203955AF1-039 C O1
Solar/Wind Harmer
0.791
20398826ARMNA MT
Solar/Wind Harmer
3.933
203848AF2-166 C
Solar/Wind Harmer
3.252
946381AF1-302 GEN
Solar/Wind Harmer
3.343
238217AF1-153 C O1
Solar/Wind Harmer
0.955
970305AG2-200 GEN
Solar/Wind Harmer
3.134
203859AF2-294 C
Solar/Wind Harmer
2.597
970313AG2-206 GEN
Solar/Wind Harmer
7.257
216419AE2-001 C
Solar/Wind Harmer
2.715
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.657
203963AG1-253 GEN
Solar/Wind Harmer
0.513
971931AH1-490 GEN
Solar/Wind Harmer
2.512
203947AF1-006 C
Solar/Wind Harmer
0.664
944411AF1-106 GEN
Solar/Wind Harmer
3.474
238183AE2-316 GEN
Solar/Wind Harmer
6.681
971183AH1-050 GEN
Solar/Wind Harmer
6.421
959471AF2-238 GEN
Solar/Wind Harmer
0.951
970337AG2-221 GEN
Solar/Wind Harmer
3.145
20072226SHAWVL 2
Adder
21.511
970647AG2-420 GEN
Solar/Wind Harmer
0.364
203860AG1-193 C
Solar/Wind Harmer
0.463
970511AG2-327 GEN
Solar/Wind Harmer
1.512
238206AE2-263_GEN
Solar/Wind Harmer
3.447
970267AG2-176 GEN
Solar/Wind Harmer
21.074
238215AE2-248 C
Solar/Wind Harmer
2.148
961971AG1-040 GEN
Solar/Wind Harmer
0.796
203835AF1-098 GEN
Solar/Wind Harmer
3.159
203813AE2-344_GEN
Solar/Wind Harmer
14.605
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.73
971865AH1-452 GEN
Solar/Wind Harmer
1.131
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.21918487548828
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.035
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.214
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.809
MECLTFEXP_MEC->PJM
CLTF
0.089
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.23
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:1.14
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:1.14
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.34
MW Contribution:1.14
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
10.123
20216026CON.GEN2
50/50
0.033
203841AF2-001_GEN
Solar/Wind Harmer
5.897
971879AH1-460 GEN
Solar/Wind Harmer
19.409
970125AG2-091 GEN
Solar/Wind Harmer
1.761
20079426CONEMAGH
Adder
3.479
971541AH1-268 GEN
Solar/Wind Harmer
9.67
971419AH1-201 GEN
Solar/Wind Harmer
8.545
970899AG2-561 GEN
Solar/Wind Harmer
5.321
203818AF1-086 GEN
Solar/Wind Harmer
6.126
20089126CSLMN_L13
Solar/Wind Harmer
1.942
20089026BF_G21_K23
Solar/Wind Harmer
1.537
945751AF1-240 GEN
Solar/Wind Harmer
3.316
960051AF2-296 GEN
Solar/Wind Harmer
4.2
971703AH1-357 GEN
Solar/Wind Harmer
4.103
971707AH1-359 GEN
Solar/Wind Harmer
4.103
20334926Z1-069 C
Solar/Wind Harmer
4.137
965131AG1-378 GEN
Solar/Wind Harmer
3.847
20082926HNSMLK 2
Adder
10.453
20083126HNSMLK 4
Adder
10.453
203854AF2-039 C
Solar/Wind Harmer
0.696
202652Y1-033 WT C
Solar/Wind Harmer
1.572
203932AE1-123
Adder
3.3
944411AF1-106 GEN
Solar/Wind Harmer
0.377
971185AH1-051 GEN
Solar/Wind Harmer
3.857
971355AH1-158 GEN
Solar/Wind Harmer
4.485
20120126WRREN CT
Adder
9.95
203856AF2-165 C
Solar/Wind Harmer
1.872
970647AG2-420 GEN
Solar/Wind Harmer
3.136
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.065
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.975
238202AE2-262_GEN
Solar/Wind Harmer
3.621
971627AH1-313 GEN
Solar/Wind Harmer
14.197
20335126GROZ1-110
Adder
3.21
20335226CANZ2-011
Adder
3.12
957161AF2-010 GEN
Solar/Wind Harmer
10.35
203830AF1-094 GEN
Solar/Wind Harmer
0.81
203948AG1-140 C
Solar/Wind Harmer
0.339
203962AF1-287 GEN
Solar/Wind Harmer
2.542
962511AG1-100 GEN
Solar/Wind Harmer
0.767
20328326MANOR_T86
Adder
0.175
20084926LAKVU GN
Adder
0.216
941421AE2-139 GEN
Solar/Wind Harmer
3.541
972271AH1-720 GEN
Adder
7.526
200917MEHOOPANY_G
Solar/Wind Harmer
3.49
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.488
237043AE2-125 C
Solar/Wind Harmer
0.181
20083726HOMER C1
50/50
280.069
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.263
20083926HOMER C3
50/50
231.8
20083826HOMER C2
50/50
218.961
20092526R32
Solar/Wind Harmer
4.991
203844AF2-092 C
Solar/Wind Harmer
3.326
203850AG1-041 C
Solar/Wind Harmer
3.319
20080926SITHE
50/50
0.901
946071AF1-272 GEN
Solar/Wind Harmer
11.144
203839AF1-321 GEN
Solar/Wind Harmer
5.897
20084626FORWARD
Solar/Wind Harmer
2.32
203857AF2-221 C
Solar/Wind Harmer
4.403
970123AG2-090 GEN
Solar/Wind Harmer
4.109
203940AF1-140 C
Solar/Wind Harmer
1.353
971441AH1-212 GEN
Solar/Wind Harmer
5.415
20088926STNY CRK
Solar/Wind Harmer
3.291
971427AH1-205 GEN
Solar/Wind Harmer
3.974
20083426SW_E13_K22
Solar/Wind Harmer
0.78
20088626ARWF_N39
Solar/Wind Harmer
4.882
20303426NA_O38_P22
Solar/Wind Harmer
3.952
944781AF1-143 GEN
Solar/Wind Harmer
6.655
203853AF1-134 C O1
Solar/Wind Harmer
1.27
972077AH1-588 GEN
Solar/Wind Harmer
49.242
972079AH1-589 GEN
Solar/Wind Harmer
40.557
970715AG2-457 GEN
Solar/Wind Harmer
16.414
972075AH1-587 GEN
Solar/Wind Harmer
39.041
203952AE2-129 C
Solar/Wind Harmer
1.165
203946AE2-131 C
Solar/Wind Harmer
1.163
962411AG1-090 GEN
Solar/Wind Harmer
18.273
20398826ARMNA MT
Solar/Wind Harmer
3.972
203955AF1-039 C O1
Solar/Wind Harmer
0.765
203848AF2-166 C
Solar/Wind Harmer
3.246
946381AF1-302 GEN
Solar/Wind Harmer
3.336
970305AG2-200 GEN
Solar/Wind Harmer
3.147
238217AF1-153 C O1
Solar/Wind Harmer
0.946
203859AF2-294 C
Solar/Wind Harmer
2.624
970313AG2-206 GEN
Solar/Wind Harmer
7.319
203980AG1-197 GEN
Solar/Wind Harmer
0.61
203979AG1-198 GEN
Solar/Wind Harmer
0.486
971933AH1-491 GEN
Solar/Wind Harmer
2.673
216419AE2-001 C
Solar/Wind Harmer
2.642
203963AG1-253 GEN
Solar/Wind Harmer
0.517
971931AH1-490 GEN
Solar/Wind Harmer
2.536
203947AF1-006 C
Solar/Wind Harmer
0.67
203843AF2-002_GEN
Solar/Wind Harmer
2.948
970631AG2-411 GEN
Solar/Wind Harmer
18.493
20088826HIGHLAND
Solar/Wind Harmer
4.657
971279AH1-102 GEN
Solar/Wind Harmer
22.722
957561AF2-050 GEN
Solar/Wind Harmer
13.724
971423AH1-203 GEN
Solar/Wind Harmer
18.68
20094526CT_V3-030
Solar/Wind Harmer
1.866
964201AG1-281 GEN
Solar/Wind Harmer
1.565
20089226LOOKOUT
Solar/Wind Harmer
1.89
970713AG2-456 GEN
Solar/Wind Harmer
16.414
971705AH1-358 GEN
Solar/Wind Harmer
4.771
971709AH1-360 GEN
Solar/Wind Harmer
4.771
203987AE2-118 C
Solar/Wind Harmer
4.049
964391AG1-301 GEN
Solar/Wind Harmer
1.125
20082826HNSMLK 1
Adder
10.453
20083026HNSMLK 3
Adder
10.453
20091326SHAW-D
Adder
1.119
972169AH1-667 GEN
Solar/Wind Harmer
3.064
203954AE2-126 C
Solar/Wind Harmer
1.029
20326126BLOSSBCT
Adder
3.854
20335026MILZ1-092
Adder
3.809
944411AF1-106 GEN
Solar/Wind Harmer
3.509
971183AH1-050 GEN
Solar/Wind Harmer
6.429
959471AF2-238 GEN
Solar/Wind Harmer
0.959
970337AG2-221 GEN
Solar/Wind Harmer
3.171
238183AE2-316 GEN
Solar/Wind Harmer
6.666
970647AG2-420 GEN
Solar/Wind Harmer
0.365
20072226SHAWVL 2
Adder
21.096
203860AG1-193 C
Solar/Wind Harmer
0.466
970511AG2-327 GEN
Solar/Wind Harmer
1.525
238206AE2-263_GEN
Solar/Wind Harmer
3.375
970267AG2-176 GEN
Solar/Wind Harmer
21.271
961971AG1-040 GEN
Solar/Wind Harmer
0.803
203835AF1-098 GEN
Solar/Wind Harmer
3.183
238215AE2-248 C
Solar/Wind Harmer
2.088
203813AE2-344_GEN
Solar/Wind Harmer
14.741
20084926LAKVU GN
Adder
0.216
970643AG2-418 GEN
Solar/Wind Harmer
0.692
971865AH1-452 GEN
Solar/Wind Harmer
1.138
24035802GEN-Y1-012
Adder
0.247
203961AE2-224 GEN
Solar/Wind Harmer
8.313
20091526CHSTN_FL
Solar/Wind Harmer
2.196
20090526Q36
Solar/Wind Harmer
3.279
203993AD2-133_GEN1
Solar/Wind Harmer
3.279
940863AE2-074 GEN
Solar/Wind Harmer
3.529
965121AG1-377 GEN
Solar/Wind Harmer
3.847
203804AE2-113_GEN
Solar/Wind Harmer
9.139
941231AE2-117 GEN
Solar/Wind Harmer
1.142
20083226HNSMLK 5
Adder
10.453
203855AF2-088 C
Solar/Wind Harmer
0.335
203846AF2-130 C
Solar/Wind Harmer
0.927
970555AG2-356 GEN
Solar/Wind Harmer
3.171
970663AG2-429 GEN
Solar/Wind Harmer
10.629
970663AG2-429 GEN
Solar/Wind Harmer
1.73
970677AG2-438 GEN
Solar/Wind Harmer
1.337
966771AG1-548 GEN
Solar/Wind Harmer
19.376
966771AG1-548 GEN
Solar/Wind Harmer
3.755
20084926LAKVU GN
Adder
0.243
203926AA2-133 GEN
Adder
2.612
971321AH1-140 GEN
Solar/Wind Harmer
14.65
971321AH1-140 GEN
Solar/Wind Harmer
2.839
20334726NME_Y1-047
Adder
2.345
20390726Y2-042
Adder
1.882
971055AG2-654 GEN
Solar/Wind Harmer
0.697
961581Q1080_CY23
External Queue
26.921693801879883
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.268
MECLTFEXP_MEC->PJM
CLTF
0.139
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.097
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:1.05
Bus #Bus NameTypeMW Contribution
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
961581Q1080_CY23
External Queue
18.789121627807617
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:1.05
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
961581Q1080_CY23
External Queue
18.789121627807617
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1062.61
MW Contribution:0.87
Bus #Bus NameTypeMW Contribution
20079426CONEMAGH
50/50
2.866
20083326SEWRDB34
50/50
7.468
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.929
971879AH1-460 GEN
Solar/Wind Harmer
16.011
20089126CSLMN_L13
Solar/Wind Harmer
2.122
20089026BF_G21_K23
Solar/Wind Harmer
1.68
970125AG2-091 GEN
Solar/Wind Harmer
1.438
202652Y1-033 WT C
Solar/Wind Harmer
2.225
971419AH1-201 GEN
Solar/Wind Harmer
7.565
971541AH1-268 GEN
Solar/Wind Harmer
7.677
970899AG2-561 GEN
Solar/Wind Harmer
4.351
203818AF1-086 GEN
Solar/Wind Harmer
4.985
945751AF1-240 GEN
Solar/Wind Harmer
2.685
960051AF2-296 GEN
Solar/Wind Harmer
3.403
971703AH1-357 GEN
Solar/Wind Harmer
3.277
971707AH1-359 GEN
Solar/Wind Harmer
3.277
20334926Z1-069 C
Solar/Wind Harmer
3.316
965131AG1-378 GEN
Solar/Wind Harmer
3.08
20082926HNSMLK 2
Adder
8.288
20083126HNSMLK 4
Adder
8.288
203854AF2-039 C
Solar/Wind Harmer
0.56
944411AF1-106 GEN
Solar/Wind Harmer
0.304
203932AE1-123
Adder
2.638
971185AH1-051 GEN
Solar/Wind Harmer
3.071
971355AH1-158 GEN
Solar/Wind Harmer
3.571
20120126WRREN CT
Adder
7.914
203856AF2-165 C
Solar/Wind Harmer
1.49
970647AG2-420 GEN
Solar/Wind Harmer
2.494
970335AG2-220 GEN
Solar/Wind Harmer
3.845
971127AH1-005 GEN
Solar/Wind Harmer
2.481
959441AF2-235 GEN
Solar/Wind Harmer
0.358
238219AF1-167 C
Solar/Wind Harmer
1.568
238202AE2-262_GEN
Solar/Wind Harmer
2.913
971627AH1-313 GEN
Solar/Wind Harmer
11.421
20335126GROZ1-110
Adder
2.606
20335226CANZ2-011
Adder
2.533
957161AF2-010 GEN
Solar/Wind Harmer
8.186
203830AF1-094 GEN
Solar/Wind Harmer
0.64
203948AG1-140 C
Solar/Wind Harmer
0.267
20328326MANOR_T86
Adder
0.143
20081326YOUGH
50/50
0.092
203843AF2-002_GEN
Solar/Wind Harmer
2.465
970631AG2-411 GEN
Solar/Wind Harmer
15.449
20080926SITHE
50/50
0.719
20084126DEEPCRK2
50/50
0.151
20084026DEEPCRK1
50/50
0.149
946071AF1-272 GEN
Solar/Wind Harmer
9.629
203839AF1-321 GEN
Solar/Wind Harmer
4.929
20084626FORWARD
Solar/Wind Harmer
1.938
20083426SW_E13_K22
Solar/Wind Harmer
0.722
944781AF1-143 GEN
Solar/Wind Harmer
7.273
203857AF2-221 C
Solar/Wind Harmer
3.595
970123AG2-090 GEN
Solar/Wind Harmer
3.356
203955AF1-039 C O1
Solar/Wind Harmer
1.083
971427AH1-205 GEN
Solar/Wind Harmer
3.518
20088926STNY CRK
Solar/Wind Harmer
2.909
203962AF1-287 GEN
Solar/Wind Harmer
2.003
962511AG1-100 GEN
Solar/Wind Harmer
0.604
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.897
972271AH1-720 GEN
Adder
6.165
200917MEHOOPANY_G
Solar/Wind Harmer
2.882
970679AG2-439 GEN
Solar/Wind Harmer
0.659
970643AG2-418 GEN
Solar/Wind Harmer
1.212
20089226LOOKOUT
Solar/Wind Harmer
2.066
971423AH1-203 GEN
Solar/Wind Harmer
16.774
20088826HIGHLAND
Solar/Wind Harmer
3.74
971279AH1-102 GEN
Solar/Wind Harmer
18.04
957561AF2-050 GEN
Solar/Wind Harmer
10.536
20094526CT_V3-030
Solar/Wind Harmer
1.499
964201AG1-281 GEN
Solar/Wind Harmer
1.255
970713AG2-456 GEN
Solar/Wind Harmer
13.107
971705AH1-358 GEN
Solar/Wind Harmer
3.81
971709AH1-360 GEN
Solar/Wind Harmer
3.81
203987AE2-118 C
Solar/Wind Harmer
3.189
964391AG1-301 GEN
Solar/Wind Harmer
0.888
20082826HNSMLK 1
Adder
8.288
20083026HNSMLK 3
Adder
8.288
20091326SHAW-D
Adder
0.9
972169AH1-667 GEN
Solar/Wind Harmer
2.463
203954AE2-126 C
Solar/Wind Harmer
0.826
20326126BLOSSBCT
Adder
3.108
20335026MILZ1-092
Adder
3.072
944411AF1-106 GEN
Solar/Wind Harmer
2.83
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.563
971183AH1-050 GEN
Solar/Wind Harmer
5.118
238183AE2-316 GEN
Solar/Wind Harmer
5.316
970647AG2-420 GEN
Solar/Wind Harmer
0.29
20072226SHAWVL 2
Adder
16.955
970511AG2-327 GEN
Solar/Wind Harmer
1.234
203860AG1-193 C
Solar/Wind Harmer
0.37
238206AE2-263_GEN
Solar/Wind Harmer
2.715
970267AG2-176 GEN
Solar/Wind Harmer
16.811
238215AE2-248 C
Solar/Wind Harmer
1.682
961971AG1-040 GEN
Solar/Wind Harmer
0.634
203835AF1-098 GEN
Solar/Wind Harmer
2.515
203813AE2-344_GEN
Solar/Wind Harmer
11.616
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.873
24035802GEN-Y1-012
Adder
0.187
203940AF1-140 C
Solar/Wind Harmer
1.095
971441AH1-212 GEN
Solar/Wind Harmer
4.287
20088626ARWF_N39
Solar/Wind Harmer
3.758
20303426NA_O38_P22
Solar/Wind Harmer
3.042
203853AF1-134 C O1
Solar/Wind Harmer
1.029
972077AH1-588 GEN
Solar/Wind Harmer
39.32
972079AH1-589 GEN
Solar/Wind Harmer
32.386
970715AG2-457 GEN
Solar/Wind Harmer
13.107
972075AH1-587 GEN
Solar/Wind Harmer
31.212
203952AE2-129 C
Solar/Wind Harmer
0.933
203946AE2-131 C
Solar/Wind Harmer
0.931
962411AG1-090 GEN
Solar/Wind Harmer
14.63
20398826ARMNA MT
Solar/Wind Harmer
3.204
203848AF2-166 C
Solar/Wind Harmer
2.59
946381AF1-302 GEN
Solar/Wind Harmer
2.66
238217AF1-153 C O1
Solar/Wind Harmer
0.758
970305AG2-200 GEN
Solar/Wind Harmer
2.503
203859AF2-294 C
Solar/Wind Harmer
2.123
970313AG2-206 GEN
Solar/Wind Harmer
5.926
216419AE2-001 C
Solar/Wind Harmer
2.128
203980AG1-197 GEN
Solar/Wind Harmer
0.481
203979AG1-198 GEN
Solar/Wind Harmer
0.384
971933AH1-491 GEN
Solar/Wind Harmer
2.114
203963AG1-253 GEN
Solar/Wind Harmer
0.408
971931AH1-490 GEN
Solar/Wind Harmer
1.998
203947AF1-006 C
Solar/Wind Harmer
0.527
20083726HOMER C1
50/50
223.712
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.225
20083926HOMER C3
50/50
185.007
20083826HOMER C2
50/50
174.761
20050326C.SLOPE
50/50
0.703
203844AF2-092 C
Solar/Wind Harmer
2.767
20092526R32
Solar/Wind Harmer
4.007
203850AG1-041 C
Solar/Wind Harmer
2.745
203961AE2-224 GEN
Solar/Wind Harmer
6.382
20091526CHSTN_FL
Solar/Wind Harmer
1.749
20090526Q36
Solar/Wind Harmer
2.618
203993AD2-133_GEN1
Solar/Wind Harmer
2.618
940863AE2-074 GEN
Solar/Wind Harmer
2.824
965121AG1-377 GEN
Solar/Wind Harmer
3.08
203804AE2-113_GEN
Solar/Wind Harmer
7.308
941231AE2-117 GEN
Solar/Wind Harmer
0.902
20083226HNSMLK 5
Adder
8.288
203855AF2-088 C
Solar/Wind Harmer
0.269
203846AF2-130 C
Solar/Wind Harmer
0.74
970555AG2-356 GEN
Solar/Wind Harmer
2.563
970663AG2-429 GEN
Solar/Wind Harmer
8.44
970663AG2-429 GEN
Solar/Wind Harmer
1.374
970677AG2-438 GEN
Solar/Wind Harmer
1.057
966771AG1-548 GEN
Solar/Wind Harmer
15.316
966771AG1-548 GEN
Solar/Wind Harmer
2.968
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.144
20334726NME_Y1-047
Adder
1.937
971321AH1-140 GEN
Solar/Wind Harmer
11.795
971321AH1-140 GEN
Solar/Wind Harmer
2.286
20390726Y2-042
Adder
1.578
961581Q1080_CY23
External Queue
21.336383819580078
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.238
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.164
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.693
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.865
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-036_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-036_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1058.48
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.925
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.355
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20092526R32
Solar/Wind Harmer
3.878
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
971321AH1-140 GEN
Solar/Wind Harmer
26.397
971321AH1-140 GEN
Solar/Wind Harmer
5.116
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
21.315889358520508
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.82 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1056.6
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.372
20079426CONEMAGH
50/50
2.786
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.544
971879AH1-460 GEN
Solar/Wind Harmer
14.908
970125AG2-091 GEN
Solar/Wind Harmer
1.349
970899AG2-561 GEN
Solar/Wind Harmer
4.363
971541AH1-268 GEN
Solar/Wind Harmer
7.566
971419AH1-201 GEN
Solar/Wind Harmer
6.568
203818AF1-086 GEN
Solar/Wind Harmer
5.016
945751AF1-240 GEN
Solar/Wind Harmer
2.826
960051AF2-296 GEN
Solar/Wind Harmer
3.452
971703AH1-357 GEN
Solar/Wind Harmer
3.396
971707AH1-359 GEN
Solar/Wind Harmer
3.396
20089126CSLMN_L13
Solar/Wind Harmer
1.489
20089026BF_G21_K23
Solar/Wind Harmer
1.178
20334926Z1-069 C
Solar/Wind Harmer
3.425
965131AG1-378 GEN
Solar/Wind Harmer
3.102
20082926HNSMLK 2
Adder
8.956
20083126HNSMLK 4
Adder
8.956
203932AE1-123
Adder
2.943
203854AF2-039 C
Solar/Wind Harmer
0.576
971185AH1-051 GEN
Solar/Wind Harmer
3.381
971355AH1-158 GEN
Solar/Wind Harmer
3.931
944411AF1-106 GEN
Solar/Wind Harmer
0.314
238219AF1-167 C
Solar/Wind Harmer
1.869
203856AF2-165 C
Solar/Wind Harmer
1.638
970647AG2-420 GEN
Solar/Wind Harmer
2.739
20120126WRREN CT
Adder
8.311
959441AF2-235 GEN
Solar/Wind Harmer
0.392
202652Y1-033 WT C
Solar/Wind Harmer
1.199
970335AG2-220 GEN
Solar/Wind Harmer
3.968
971127AH1-005 GEN
Solar/Wind Harmer
2.56
238202AE2-262_GEN
Solar/Wind Harmer
3.032
971627AH1-313 GEN
Solar/Wind Harmer
11.888
20335126GROZ1-110
Adder
2.697
20335226CANZ2-011
Adder
2.622
957161AF2-010 GEN
Solar/Wind Harmer
8.813
203830AF1-094 GEN
Solar/Wind Harmer
0.689
203948AG1-140 C
Solar/Wind Harmer
0.283
203962AF1-287 GEN
Solar/Wind Harmer
2.142
962511AG1-100 GEN
Solar/Wind Harmer
0.646
20328326MANOR_T86
Adder
0.148
20084926LAKVU GN
Adder
0.18
941421AE2-139 GEN
Solar/Wind Harmer
2.999
972271AH1-720 GEN
Adder
6.38
200917MEHOOPANY_G
Solar/Wind Harmer
2.981
970679AG2-439 GEN
Solar/Wind Harmer
0.682
970643AG2-418 GEN
Solar/Wind Harmer
1.229
20080526COLVER13
50/50
1.527
203843AF2-002_GEN
Solar/Wind Harmer
2.272
970631AG2-411 GEN
Solar/Wind Harmer
14.256
20088826HIGHLAND
Solar/Wind Harmer
3.558
971279AH1-102 GEN
Solar/Wind Harmer
17.777
957561AF2-050 GEN
Solar/Wind Harmer
10.408
20094526CT_V3-030
Solar/Wind Harmer
1.478
971423AH1-203 GEN
Solar/Wind Harmer
14.36
964201AG1-281 GEN
Solar/Wind Harmer
1.202
970713AG2-456 GEN
Solar/Wind Harmer
13.583
971705AH1-358 GEN
Solar/Wind Harmer
3.949
971709AH1-360 GEN
Solar/Wind Harmer
3.949
20089226LOOKOUT
Solar/Wind Harmer
1.449
203987AE2-118 C
Solar/Wind Harmer
3.141
20082826HNSMLK 1
Adder
8.956
20083026HNSMLK 3
Adder
8.956
964391AG1-301 GEN
Solar/Wind Harmer
0.878
238183AE2-316 GEN
Solar/Wind Harmer
6.048
203954AE2-126 C
Solar/Wind Harmer
0.858
20091326SHAW-D
Adder
0.927
972169AH1-667 GEN
Solar/Wind Harmer
2.536
20080926SITHE
50/50
0.719
946071AF1-272 GEN
Solar/Wind Harmer
9.57
203839AF1-321 GEN
Solar/Wind Harmer
4.544
20084626FORWARD
Solar/Wind Harmer
1.789
203857AF2-221 C
Solar/Wind Harmer
3.373
970123AG2-090 GEN
Solar/Wind Harmer
3.149
203940AF1-140 C
Solar/Wind Harmer
1.038
971441AH1-212 GEN
Solar/Wind Harmer
4.156
20088926STNY CRK
Solar/Wind Harmer
2.53
971427AH1-205 GEN
Solar/Wind Harmer
3.055
20083426SW_E13_K22
Solar/Wind Harmer
0.6
20088626ARWF_N39
Solar/Wind Harmer
3.713
20303426NA_O38_P22
Solar/Wind Harmer
3.005
203853AF1-134 C O1
Solar/Wind Harmer
1.044
972077AH1-588 GEN
Solar/Wind Harmer
40.749
972079AH1-589 GEN
Solar/Wind Harmer
33.563
970715AG2-457 GEN
Solar/Wind Harmer
13.583
944781AF1-143 GEN
Solar/Wind Harmer
5.102
972075AH1-587 GEN
Solar/Wind Harmer
32.43
203952AE2-129 C
Solar/Wind Harmer
0.939
203946AE2-131 C
Solar/Wind Harmer
0.938
962411AG1-090 GEN
Solar/Wind Harmer
14.732
946381AF1-302 GEN
Solar/Wind Harmer
3.026
203848AF2-166 C
Solar/Wind Harmer
2.871
20398826ARMNA MT
Solar/Wind Harmer
3.303
238217AF1-153 C O1
Solar/Wind Harmer
0.814
970305AG2-200 GEN
Solar/Wind Harmer
2.629
203859AF2-294 C
Solar/Wind Harmer
2.19
203955AF1-039 C O1
Solar/Wind Harmer
0.584
970313AG2-206 GEN
Solar/Wind Harmer
6.115
203980AG1-197 GEN
Solar/Wind Harmer
0.517
203979AG1-198 GEN
Solar/Wind Harmer
0.413
971933AH1-491 GEN
Solar/Wind Harmer
2.274
216419AE2-001 C
Solar/Wind Harmer
2.202
203963AG1-253 GEN
Solar/Wind Harmer
0.432
971931AH1-490 GEN
Solar/Wind Harmer
2.138
203947AF1-006 C
Solar/Wind Harmer
0.561
20326126BLOSSBCT
Adder
3.208
971183AH1-050 GEN
Solar/Wind Harmer
5.635
20335026MILZ1-092
Adder
3.169
944411AF1-106 GEN
Solar/Wind Harmer
2.919
970647AG2-420 GEN
Solar/Wind Harmer
0.318
203860AG1-193 C
Solar/Wind Harmer
0.403
959471AF2-238 GEN
Solar/Wind Harmer
0.8
970337AG2-221 GEN
Solar/Wind Harmer
2.645
20072226SHAWVL 2
Adder
17.649
970511AG2-327 GEN
Solar/Wind Harmer
1.274
970267AG2-176 GEN
Solar/Wind Harmer
18.122
238206AE2-263_GEN
Solar/Wind Harmer
2.826
961971AG1-040 GEN
Solar/Wind Harmer
0.68
203835AF1-098 GEN
Solar/Wind Harmer
2.664
238215AE2-248 C
Solar/Wind Harmer
1.738
203813AE2-344_GEN
Solar/Wind Harmer
12.418
20084926LAKVU GN
Adder
0.18
970643AG2-418 GEN
Solar/Wind Harmer
0.572
971865AH1-452 GEN
Solar/Wind Harmer
1.032
24035802GEN-Y1-012
Adder
0.198
20083726HOMER C1
50/50
223.475
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.224
20083926HOMER C3
50/50
189.284
20083826HOMER C2
50/50
178.8
20092526R32
Solar/Wind Harmer
3.812
203844AF2-092 C
Solar/Wind Harmer
2.555
203850AG1-041 C
Solar/Wind Harmer
2.548
203961AE2-224 GEN
Solar/Wind Harmer
6.304
20091526CHSTN_FL
Solar/Wind Harmer
1.696
940863AE2-074 GEN
Solar/Wind Harmer
2.921
20090526Q36
Solar/Wind Harmer
2.597
203993AD2-133_GEN1
Solar/Wind Harmer
2.597
203804AE2-113_GEN
Solar/Wind Harmer
7.605
965121AG1-377 GEN
Solar/Wind Harmer
3.102
20083226HNSMLK 5
Adder
8.956
941231AE2-117 GEN
Solar/Wind Harmer
0.892
970663AG2-429 GEN
Solar/Wind Harmer
10.063
970663AG2-429 GEN
Solar/Wind Harmer
1.638
203846AF2-130 C
Solar/Wind Harmer
0.82
203855AF2-088 C
Solar/Wind Harmer
0.277
970555AG2-356 GEN
Solar/Wind Harmer
2.645
970677AG2-438 GEN
Solar/Wind Harmer
1.137
966771AG1-548 GEN
Solar/Wind Harmer
16.455
966771AG1-548 GEN
Solar/Wind Harmer
3.189
20084926LAKVU GN
Adder
0.203
203926AA2-133 GEN
Adder
2.216
20334726NME_Y1-047
Adder
2.003
971321AH1-140 GEN
Solar/Wind Harmer
10.527
971321AH1-140 GEN
Solar/Wind Harmer
2.04
20390726Y2-042
Adder
1.633
971055AG2-654 GEN
Solar/Wind Harmer
0.739
961581Q1080_CY23
External Queue
21.48957061767578
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.476
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.154
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.691
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CBM NorthLTFEXP_CBM-N->PJM
CBM
29.854
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-083_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-083_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.56 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1034.46
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.926
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.356
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20092526R32
Solar/Wind Harmer
3.878
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
21.315900802612305
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.65
MW Contribution:0.65
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
203843AF2-002_GEN
Solar/Wind Harmer
2.147
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.63
MW Contribution:0.65
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
203843AF2-002_GEN
Solar/Wind Harmer
2.147
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'AP_P2-3_WP-138-171A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235153 TO BUS 235274 CKT 1   /*01CABOT      138.0 - 01WOODLD     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235274 TO BUS 235803 CKT 1   /*01WOODLD     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235274 TO BUS 236236 CKT 2   /*01WOODLD     138.0 - 01WOODLAND    25.0
END
CONTINGENCY 'AP_P2-2_WP-138-054A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041D_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238544 CKT 4   /*02S8-ATT     345.0 - 02ASH_3      138.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041E_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238542 CKT 9   /*02S8-ATT     345.0 - 02ASH_1      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3-DRTF-013_SRT-SL'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1                /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                                /*26HOMER CT   230.0
 SET POSTCONTRATING 1000 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
 SET PRECONTRATING 830 BRANCH FROM BUS 200912 TO BUS 200793 CKT 1 /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-3_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BUS 200767                                   /*26HOMER CT   230.0
END
CONTINGENCY 'AP_P1-3_WP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235282 TO BUS 235240 CKT 1   /*01GAR RN     138.0 - 01COLMBGPN   138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-051A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1   /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235137 CKT 1   /*01BRACKENRDG 138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235202 CKT 1   /*01BRACKENR J 138.0 - 01KISKIV     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235245 CKT 1   /*01BRACKENR J 138.0 - 01SHFCRN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1   /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1   /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'AP_P2-2_WP-138-055_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235137 CKT 1   /*01KISKIV     138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235262 CKT 1   /*01KISKIV     138.0 - 01VANDRG     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235278 CKT 1   /*01KISKIV     138.0 - 01N WASH     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 2   /*01KISKIV     138.0 - 01KISKI VA    25.0
END
CONTINGENCY 'AP_P2-3_WP-138-177_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235078 CKT ZB   /*01SPGDL-3    138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235603 CKT 1    /*01SPGDL-3    138.0 - 01PITTML     138.0
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235610 CKT 1    /*01SPGDL-3    138.0 - 01SPRGD1      13.8
 DISCONNECT BRANCH FROM BUS 235079 TO BUS 235611 CKT 1    /*01SPGDL-3    138.0 - 01SPRGD2      13.8
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 OPEN BUS 235132                                          /*01AL 4       138.0
 OPEN BUS 235138                                          /*01AL 4J      138.0
 OPEN BUS 235825                                          /*01ALL L4T    138.0
END
CONTINGENCY 'AP_P1-2_WP-138-087_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235825 CKT 1   /*01BRACKENRDG 138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1   /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1   /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1   /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235825 TO BUS 235132 CKT 1   /*01ALL L4T    138.0 - 01AL 4       138.0
END
CONTINGENCY 'AP_P1-2_WP-138-103_SRT-A'
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235134 CKT 1   /*01AL&D6T     138.0 - 01AL&D6      138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235139 CKT 1   /*01KITTAN     138.0 - 01AL&D6T     138.0
 DISCONNECT BUS 235134                                   /*01AL&D6      138.0
END
CONTINGENCY 'AP_P2-3_WP-138-18201_SRT-A'
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235256 CKT 1    /*01FEDLST     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235190 TO BUS 235256 CKT 1    /*01HARWCK     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235195 TO BUS 235256 CKT 1    /*01HUNTDN     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235078 CKT ZB   /*01SPGDL      138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1    /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1    /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1    /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1    /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1    /*01SPGDL      138.0 - 15CHESWK     138.0
 OPEN BUS 235613                                          /*01SPRGD4      16.5
 OPEN BUS 235614                                          /*01SPRGD5      16.5
END
CONTINGENCY 'AP_P2-3_WP-138-182_SRT-A'
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235256 CKT 1    /*01FEDLST     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235767 CKT 1    /*01FEDLST     138.0 - 01FEDERL S    25.0
 DISCONNECT BRANCH FROM BUS 235190 TO BUS 235256 CKT 1    /*01HARWCK     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235195 TO BUS 235256 CKT 1    /*01HUNTDN     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235078 CKT ZB   /*01SPGDL      138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1    /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1    /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1    /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1    /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1    /*01SPGDL      138.0 - 15CHESWK     138.0
END
CONTINGENCY 'AP_P2-3_WP-138-181T_SRT-A'
 OPEN BRANCH FROM BUS 235256 TO BUS 235181 CKT 1   /*01SPGDL      138.0 - 01FEDLST     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235190 CKT 1   /*01SPGDL      138.0 - 01HARWCK     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235195 CKT 1   /*01SPGDL      138.0 - 01HUNTDN     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235222 CKT 1   /*01SPGDL      138.0 - 01MURRYC     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 254042 CKT 1   /*01SPGDL      138.0 - 15PLUM       138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 254064 CKT 1   /*01SPGDL      138.0 - 15CHESWK     138.0
 OPEN BUS 235613                                   /*01SPRGD4      16.5
 OPEN BUS 235614                                   /*01SPRGD5      16.5
END
CONTINGENCY 'AP_P2-2_WP-138-0582-1_SRT-A'
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235181 CKT 1   /*01SPGDL      138.0 - 01FEDLST     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235190 CKT 1   /*01SPGDL      138.0 - 01HARWCK     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235195 CKT 1   /*01SPGDL      138.0 - 01HUNTDN     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1   /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1   /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1   /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1   /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1   /*01SPGDL      138.0 - 15CHESWK     138.0
 DISCONNECT BUS 235613                                   /*01SPRGD4      16.5
 DISCONNECT BUS 235614                                   /*01SPRGD5      16.5
END
CONTINGENCY 'AP_P7-1_WPP-138-050_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235137 CKT 1    /*01BRACKENRDG 138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235743 CKT 1    /*01BRACKENRDG 138.0 - 01BRACKENRID  25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235202 CKT 1    /*01BRACKENR J 138.0 - 01KISKIV     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235245 CKT 1    /*01BRACKENR J 138.0 - 01SHFCRN     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1    /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1    /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1    /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1    /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-C_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-B_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-A_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0201A-20_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200795 TO BUS 200810 CKT 1          /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-208_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200768 CKT 1   /*26HOMER CT   230.0 - 26QUEMAHON   230.0
 DISCONNECT BRANCH FROM BUS 200768 TO BUS 200796 CKT 1   /*26QUEMAHON   230.0 - 26HOOVRSVL   230.0
 OPEN BRANCH FROM BUS 200767 TO BUS 200795 CKT 1         /*26HOMER CT   230.0 - 26SHELOCTA   230.0
END
CONTINGENCY 'PN_P2-2_PN-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
 DISCONNECT BUS 200807                                   /*26PIERC230   230.0
 DISCONNECT BUS 200808                                   /*26PIERC138   138.0
 DISCONNECT BUS 200809                                   /*26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-210_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 DISCONNECT BRANCH FROM BUS 200807 TO BUS 200808 CKT 1   /*26PIERC230   230.0 - 26PIERC138   138.0
 DISCONNECT BRANCH FROM BUS 200808 TO BUS 200809 CKT 1   /*26PIERC138   138.0 - 26SITHE      138.0
 REMOVE MACHINE 1 FROM BUS 200809                        /*26SITHE      138.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T-DRT-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P2-2_PN-345-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N   /*26HOMER CY   345.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-207_SRT-A'
 OPEN BRANCH FROM BUS 200767 TO BUS 200769 CKT N   /*26HOMER CT   230.0 - 26HOMER CY   345.0
 OPEN BRANCH FROM BUS 200767 TO BUS 200807 CKT 1   /*26HOMER CT   230.0 - 26PIERC230   230.0
 OPEN BUS 200768                                   /*26QUEMAHON   230.0
END
CONTINGENCY 'AP_P2-2_WP-230-005T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 200513 CKT 1    /*01SHINGL     230.0 - 26LEWISTWN   230.0
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 235970 CKT 1    /*01SHINGL     230.0 - 01DALE       230.0
 DISCONNECT BRANCH FROM BUS 235248 TO BUS 236711 CKT 82   /*01SHINGL     230.0 - 01SHINGLTN    46.0
END
CONTINGENCY 'PN_P1-3_DRT-230-003-DRT_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 CKT N          /*26HOMER CY   345.0 - 26HOMER CT   230.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 961580 CKT 1 /*26HOMER CY   345.0 - Q1080 TAP    345.0
END
CONTINGENCY 'PN_P1-2_PN-345-003_SRT-A'
 DISCONNECT BRANCH FROM BUS 200826 TO BUS 200595 CKT 1   /*26HANDSMLK   345.0 - 26WAYNE      345.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-2_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200741 CKT 9   /*26SEWARD 2   230.0 - 26SEWARD     115.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-003JT_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-2_PN-500-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-A_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 200912 TO BUS 200793 CKT 1   /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P1-3_PN-500-003_SRT-A'
 OPEN BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'AP_P2-2_MP-138-100_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235469 CKT 1   /*01ALBRIG     138.0 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 235469 TO BUS 235470 CKT 1   /*01GARRET     138.0 - 01GARRET     115.0
 DISCONNECT BRANCH FROM BUS 237410 TO BUS 235469 CKT 1   /*01GARRETT     34.5 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 970994 TO BUS 235469 CKT 1   /*AG2-615 TP   138.0 - 01GARRET     138.0
END
CONTINGENCY 'AP_P2-2_WP-138-036_SRT-A'
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235173 CKT 1    /*01LOYALH3    138.0 - 01EDGEWT     138.0
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235617 CKT ZB   /*01LOYALH3    138.0 - 01LOYALH2    138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-083_SRT-A'
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235596 CKT 1   /*01EDGEWT     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235618 CKT 1   /*01EDGEWT     138.0 - 01LOYALH3    138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 236469 CKT 1   /*01EDGEWT     138.0 - 01EDGEWATR    25.0
 DISCONNECT BRANCH FROM BUS 235178 TO BUS 235264 CKT 1   /*01ETHEL      138.0 - 01VASC       138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235596 CKT 1   /*01VASC       138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235975 CKT 1   /*01VASC       138.0 - 01VASCO       25.0
 DISCONNECT BRANCH FROM BUS 235617 TO BUS 235213 CKT 1   /*01LOYALH2    138.0 - 01LUXOR      138.0
END
235139 to 235138 ckt 1
235240 to 235202 ckt 1
235173 to 235618 ckt 1
235282 to 235240 ckt 1
235197 to 235152 ckt 1
235204 to 235139 ckt 1
235596 to 235173 ckt 1
200912 to 200005 ckt 3
999266 to 200767 ckt S
200767 to 200795 ckt 1
200769 to 999266 ckt S
200795 to 200810 ckt 1

Winter Peak Analysis

The New Service Request AH1-452 was evaluated as a 19.9 MW (8.35 MW Capacity) injection in the APS area.

AH1-452 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 19.9 MW (19.9 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-452 was evaluated as a 19.9 MW injection

AH1-452 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 19.9 MW (19.9 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC114.75 %151.0B173.270.69
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC123.04 %151.0B185.790.55
GD2AP
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC122.49 %151.0B184.970.6
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-087_SRT-A
SingleAC124.67 %151.0B188.250.55
GD2AP
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
AP_P1-2_WP-138-103_SRT-A
SingleAC124.12 %151.0B187.430.6
GD2AP
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
AP_P1-3_WP-138-053A_SRT-A
SingleAC113.72 %151.0B171.710.69

Details for 01AL&D6T-01AL 4J 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01AL&D6T-01AL 4J 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.75 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:173.27
MW Contribution:0.69
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
33.153
20083926HOMER C3
50/50
39.656
20334926Z1-069 C
Solar/Wind Harmer
1.546
238219AF1-167 C
Solar/Wind Harmer
1.022
203848AF2-166 C
Solar/Wind Harmer
1.023
203962AF1-287 GEN
Solar/Wind Harmer
0.544
203813AE2-344_GEN
Solar/Wind Harmer
3.153
203804AE2-113_GEN
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.656
966771AG1-548 GEN
Solar/Wind Harmer
4.557
966771AG1-548 GEN
Solar/Wind Harmer
1.406
970267AG2-176 GEN
Solar/Wind Harmer
4.989
970305AG2-200 GEN
Solar/Wind Harmer
0.562
970647AG2-420 GEN
Solar/Wind Harmer
0.9
970647AG2-420 GEN
Solar/Wind Harmer
0.417
970663AG2-429 GEN
Solar/Wind Harmer
5.424
970663AG2-429 GEN
Solar/Wind Harmer
3.451
970677AG2-438 GEN
Solar/Wind Harmer
0.311
970713AG2-456 GEN
Solar/Wind Harmer
2.378
970715AG2-457 GEN
Solar/Wind Harmer
2.378
971055AG2-654 GEN
Solar/Wind Harmer
0.936
971183AH1-050 GEN
Solar/Wind Harmer
2.343
971185AH1-051 GEN
Solar/Wind Harmer
1.406
971355AH1-158 GEN
Solar/Wind Harmer
2.603
971703AH1-357 GEN
Solar/Wind Harmer
0.594
971705AH1-358 GEN
Solar/Wind Harmer
1.101
971707AH1-359 GEN
Solar/Wind Harmer
0.594
971709AH1-360 GEN
Solar/Wind Harmer
1.101
971865AH1-452 GEN
Solar/Wind Harmer
0.694
971931AH1-490 GEN
Solar/Wind Harmer
0.547
971933AH1-491 GEN
Solar/Wind Harmer
0.621
972075AH1-587 GEN
Solar/Wind Harmer
6.055
972077AH1-588 GEN
Solar/Wind Harmer
7.133
972079AH1-589 GEN
Solar/Wind Harmer
9.356
957161AF2-010 GEN
Solar/Wind Harmer
2.428
966451AG1-514 GEN
50/50
Charging
0.98
G-007ALTFEXP_G-007A->PJM
CMTX
1.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.021
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.713
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.642
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.845

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.04 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:185.79
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
35.268
20083926HOMER C3
50/50
42.186
20334926Z1-069 C
Solar/Wind Harmer
1.648
238219AF1-167 C
Solar/Wind Harmer
1.111
203848AF2-166 C
Solar/Wind Harmer
1.112
203962AF1-287 GEN
Solar/Wind Harmer
0.598
203813AE2-344_GEN
Solar/Wind Harmer
3.467
203804AE2-113_GEN
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.698
966771AG1-548 GEN
Solar/Wind Harmer
4.99
966771AG1-548 GEN
Solar/Wind Harmer
1.54
970267AG2-176 GEN
Solar/Wind Harmer
5.472
970305AG2-200 GEN
Solar/Wind Harmer
0.609
970647AG2-420 GEN
Solar/Wind Harmer
0.981
970647AG2-420 GEN
Solar/Wind Harmer
0.454
970663AG2-429 GEN
Solar/Wind Harmer
5.945
970663AG2-429 GEN
Solar/Wind Harmer
3.783
970677AG2-438 GEN
Solar/Wind Harmer
0.34
970713AG2-456 GEN
Solar/Wind Harmer
2.55
970715AG2-457 GEN
Solar/Wind Harmer
2.55
971055AG2-654 GEN
Solar/Wind Harmer
0.806
971183AH1-050 GEN
Solar/Wind Harmer
2.551
971185AH1-051 GEN
Solar/Wind Harmer
1.531
971355AH1-158 GEN
Solar/Wind Harmer
2.835
971703AH1-357 GEN
Solar/Wind Harmer
0.638
971705AH1-358 GEN
Solar/Wind Harmer
1.181
971707AH1-359 GEN
Solar/Wind Harmer
0.638
971709AH1-360 GEN
Solar/Wind Harmer
1.181
971865AH1-452 GEN
Solar/Wind Harmer
0.553
971931AH1-490 GEN
Solar/Wind Harmer
0.602
971933AH1-491 GEN
Solar/Wind Harmer
0.68
972075AH1-587 GEN
Solar/Wind Harmer
6.488
972077AH1-588 GEN
Solar/Wind Harmer
7.65
972079AH1-589 GEN
Solar/Wind Harmer
10.035
972169AH1-667 GEN
Solar/Wind Harmer
0.511
957161AF2-010 GEN
Solar/Wind Harmer
2.658
966451AG1-514 GEN
50/50
Charging
0.673
G-007ALTFEXP_G-007A->PJM
CMTX
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.206
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.747
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.089

Details for 01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01COLMBGPN-01KISKIV 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.49 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:184.97
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
36.064
20083926HOMER C3
50/50
43.138
20334926Z1-069 C
Solar/Wind Harmer
1.684
203948AG1-140 C
Solar/Wind Harmer
0.072
238219AF1-167 C
Solar/Wind Harmer
1.131
203848AF2-166 C
Solar/Wind Harmer
1.133
203962AF1-287 GEN
Solar/Wind Harmer
0.609
203813AE2-344_GEN
Solar/Wind Harmer
3.529
203804AE2-113_GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.11
945751AF1-240 GEN
Solar/Wind Harmer
0.714
966771AG1-548 GEN
Solar/Wind Harmer
5.08
966771AG1-548 GEN
Solar/Wind Harmer
1.568
970267AG2-176 GEN
Solar/Wind Harmer
5.571
970305AG2-200 GEN
Solar/Wind Harmer
0.621
970647AG2-420 GEN
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
0.462
970663AG2-429 GEN
Solar/Wind Harmer
6.049
970663AG2-429 GEN
Solar/Wind Harmer
3.85
970677AG2-438 GEN
Solar/Wind Harmer
0.346
970713AG2-456 GEN
Solar/Wind Harmer
2.604
970715AG2-457 GEN
Solar/Wind Harmer
2.604
971055AG2-654 GEN
Solar/Wind Harmer
0.836
971183AH1-050 GEN
Solar/Wind Harmer
2.599
971185AH1-051 GEN
Solar/Wind Harmer
1.559
971355AH1-158 GEN
Solar/Wind Harmer
2.887
971703AH1-357 GEN
Solar/Wind Harmer
0.651
971705AH1-358 GEN
Solar/Wind Harmer
1.206
971707AH1-359 GEN
Solar/Wind Harmer
0.651
971709AH1-360 GEN
Solar/Wind Harmer
1.206
971865AH1-452 GEN
Solar/Wind Harmer
0.599
971931AH1-490 GEN
Solar/Wind Harmer
0.612
971933AH1-491 GEN
Solar/Wind Harmer
0.692
972075AH1-587 GEN
Solar/Wind Harmer
6.626
972077AH1-588 GEN
Solar/Wind Harmer
7.813
972079AH1-589 GEN
Solar/Wind Harmer
10.248
972169AH1-667 GEN
Solar/Wind Harmer
0.524
957161AF2-010 GEN
Solar/Wind Harmer
2.706
966451AG1-514 GEN
50/50
Charging
0.725
G-007ALTFEXP_G-007A->PJM
CMTX
1.159
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.668
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.268

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-087_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-087_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.67 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:188.25
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
35.268
20083926HOMER C3
50/50
42.186
20334926Z1-069 C
Solar/Wind Harmer
1.648
238219AF1-167 C
Solar/Wind Harmer
1.111
203848AF2-166 C
Solar/Wind Harmer
1.112
203962AF1-287 GEN
Solar/Wind Harmer
0.598
203813AE2-344_GEN
Solar/Wind Harmer
3.467
203804AE2-113_GEN
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.698
966771AG1-548 GEN
Solar/Wind Harmer
4.99
966771AG1-548 GEN
Solar/Wind Harmer
1.54
970267AG2-176 GEN
Solar/Wind Harmer
5.472
970305AG2-200 GEN
Solar/Wind Harmer
0.609
970647AG2-420 GEN
Solar/Wind Harmer
0.981
970647AG2-420 GEN
Solar/Wind Harmer
0.454
970663AG2-429 GEN
Solar/Wind Harmer
5.945
970663AG2-429 GEN
Solar/Wind Harmer
3.783
970677AG2-438 GEN
Solar/Wind Harmer
0.34
970713AG2-456 GEN
Solar/Wind Harmer
2.55
970715AG2-457 GEN
Solar/Wind Harmer
2.55
971055AG2-654 GEN
Solar/Wind Harmer
0.806
971183AH1-050 GEN
Solar/Wind Harmer
2.551
971185AH1-051 GEN
Solar/Wind Harmer
1.531
971355AH1-158 GEN
Solar/Wind Harmer
2.835
971703AH1-357 GEN
Solar/Wind Harmer
0.638
971705AH1-358 GEN
Solar/Wind Harmer
1.181
971707AH1-359 GEN
Solar/Wind Harmer
0.638
971709AH1-360 GEN
Solar/Wind Harmer
1.181
971865AH1-452 GEN
Solar/Wind Harmer
0.553
971931AH1-490 GEN
Solar/Wind Harmer
0.602
971933AH1-491 GEN
Solar/Wind Harmer
0.68
972075AH1-587 GEN
Solar/Wind Harmer
6.488
972077AH1-588 GEN
Solar/Wind Harmer
7.65
972079AH1-589 GEN
Solar/Wind Harmer
10.035
972169AH1-667 GEN
Solar/Wind Harmer
0.511
957161AF2-010 GEN
Solar/Wind Harmer
2.658
966451AG1-514 GEN
50/50
Charging
0.673
G-007ALTFEXP_G-007A->PJM
CMTX
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.921
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.206
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.747
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.089

Details for 01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-103_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GAR RN-01COLMBGPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-103_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.12 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:187.43
MW Contribution:0.6
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
36.064
20083926HOMER C3
50/50
43.138
20334926Z1-069 C
Solar/Wind Harmer
1.684
203948AG1-140 C
Solar/Wind Harmer
0.072
238219AF1-167 C
Solar/Wind Harmer
1.131
203848AF2-166 C
Solar/Wind Harmer
1.133
203962AF1-287 GEN
Solar/Wind Harmer
0.609
203813AE2-344_GEN
Solar/Wind Harmer
3.529
203804AE2-113_GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.11
945751AF1-240 GEN
Solar/Wind Harmer
0.714
966771AG1-548 GEN
Solar/Wind Harmer
5.08
966771AG1-548 GEN
Solar/Wind Harmer
1.568
970267AG2-176 GEN
Solar/Wind Harmer
5.571
970305AG2-200 GEN
Solar/Wind Harmer
0.621
970647AG2-420 GEN
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
0.462
970663AG2-429 GEN
Solar/Wind Harmer
6.049
970663AG2-429 GEN
Solar/Wind Harmer
3.85
970677AG2-438 GEN
Solar/Wind Harmer
0.346
970713AG2-456 GEN
Solar/Wind Harmer
2.604
970715AG2-457 GEN
Solar/Wind Harmer
2.604
971055AG2-654 GEN
Solar/Wind Harmer
0.836
971183AH1-050 GEN
Solar/Wind Harmer
2.599
971185AH1-051 GEN
Solar/Wind Harmer
1.559
971355AH1-158 GEN
Solar/Wind Harmer
2.887
971703AH1-357 GEN
Solar/Wind Harmer
0.651
971705AH1-358 GEN
Solar/Wind Harmer
1.206
971707AH1-359 GEN
Solar/Wind Harmer
0.651
971709AH1-360 GEN
Solar/Wind Harmer
1.206
971865AH1-452 GEN
Solar/Wind Harmer
0.599
971931AH1-490 GEN
Solar/Wind Harmer
0.612
971933AH1-491 GEN
Solar/Wind Harmer
0.692
972075AH1-587 GEN
Solar/Wind Harmer
6.626
972077AH1-588 GEN
Solar/Wind Harmer
7.813
972079AH1-589 GEN
Solar/Wind Harmer
10.248
972169AH1-667 GEN
Solar/Wind Harmer
0.524
957161AF2-010 GEN
Solar/Wind Harmer
2.706
966451AG1-514 GEN
50/50
Charging
0.725
G-007ALTFEXP_G-007A->PJM
CMTX
1.159
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.668
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.02
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.268

Details for 01KITTAN-01AL&D6T 138.0 kV Ckt 1 line l/o AP_P1-3_WP-138-053A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KITTAN-01AL&D6T 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-138-053A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.72 %
Rating:151.0 MVA
Rating Type:B
MVA to Mitigate:171.71
MW Contribution:0.69
Bus #Bus NameTypeMW Contribution
20083826HOMER C2
50/50
33.162
20083926HOMER C3
50/50
39.667
20334926Z1-069 C
Solar/Wind Harmer
1.546
238219AF1-167 C
Solar/Wind Harmer
1.022
203848AF2-166 C
Solar/Wind Harmer
1.023
203962AF1-287 GEN
Solar/Wind Harmer
0.544
203813AE2-344_GEN
Solar/Wind Harmer
3.154
203804AE2-113_GEN
Solar/Wind Harmer
0
945751AF1-240 GEN
Solar/Wind Harmer
0.656
966771AG1-548 GEN
Solar/Wind Harmer
4.558
966771AG1-548 GEN
Solar/Wind Harmer
1.407
970267AG2-176 GEN
Solar/Wind Harmer
4.99
970305AG2-200 GEN
Solar/Wind Harmer
0.563
970647AG2-420 GEN
Solar/Wind Harmer
0.9
970647AG2-420 GEN
Solar/Wind Harmer
0.417
970663AG2-429 GEN
Solar/Wind Harmer
5.424
970663AG2-429 GEN
Solar/Wind Harmer
3.452
970677AG2-438 GEN
Solar/Wind Harmer
0.311
970713AG2-456 GEN
Solar/Wind Harmer
2.378
970715AG2-457 GEN
Solar/Wind Harmer
2.378
971055AG2-654 GEN
Solar/Wind Harmer
0.936
971183AH1-050 GEN
Solar/Wind Harmer
2.343
971185AH1-051 GEN
Solar/Wind Harmer
1.406
971355AH1-158 GEN
Solar/Wind Harmer
2.603
971703AH1-357 GEN
Solar/Wind Harmer
0.595
971705AH1-358 GEN
Solar/Wind Harmer
1.101
971707AH1-359 GEN
Solar/Wind Harmer
0.595
971709AH1-360 GEN
Solar/Wind Harmer
1.101
971865AH1-452 GEN
Solar/Wind Harmer
0.694
971931AH1-490 GEN
Solar/Wind Harmer
0.547
971933AH1-491 GEN
Solar/Wind Harmer
0.621
972075AH1-587 GEN
Solar/Wind Harmer
6.056
972077AH1-588 GEN
Solar/Wind Harmer
7.135
972079AH1-589 GEN
Solar/Wind Harmer
9.359
957161AF2-010 GEN
Solar/Wind Harmer
2.429
966451AG1-514 GEN
50/50
Charging
0.98
G-007ALTFEXP_G-007A->PJM
CMTX
1.38
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.114
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.71
CBM NorthLTFEXP_CBM-N->PJM
CBM
9.65
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
3.855
CONTINGENCY 'AP_P1-3_WP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235803 CKT 1   /*01KISKIV     138.0 - 01NRTHPT     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235834 CKT 1   /*01KISKIV     138.0 - 01KISKI VA    25.0
 DISCONNECT BRANCH FROM BUS 235282 TO BUS 235240 CKT 1   /*01GAR RN     138.0 - 01COLMBGPN   138.0
END
CONTINGENCY 'AP_P1-2_WP-138-087_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235825 CKT 1   /*01BRACKENRDG 138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1   /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1   /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1   /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235825 TO BUS 235132 CKT 1   /*01ALL L4T    138.0 - 01AL 4       138.0
END
CONTINGENCY 'AP_P1-2_WP-138-103_SRT-A'
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235134 CKT 1   /*01AL&D6T     138.0 - 01AL&D6      138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235139 CKT 1   /*01KITTAN     138.0 - 01AL&D6T     138.0
 DISCONNECT BUS 235134                                   /*01AL&D6      138.0
END
235139 to 235138 ckt 1
235240 to 235202 ckt 1
235282 to 235240 ckt 1
235204 to 235139 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA2-133Wyalusing 34.5kVIn Service
AD2-133Eagle Valley 115kVIn Service
AE1-123Emlenton 34.5 kVIn Service
AE2-001Nittany-Zion 46 kVSuspended
AE2-074Potter 46 kVUnder Construction
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-316Brookville-Squab Hollow 138 kVUnder Construction
AE2-344Edinboro South-Venango Junction 115 kVSuspended
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-106East Sayre 34.5 kVWithdrawn
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-167West Freedom-C&K Coal 25 kVSuspended
AF1-240Timblin 34.5 kVActive
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-287Edinboro South 34.5 kV IISuspended
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-321Hooversville 115 kV ISuspended
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-010Union City-Titusville 115 kVActive
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-050Bear Rock-Johnstown 230 kVActive
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-092Snake Spring-Bedford Area 23 kVSuspended
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-165Clark Summit-Emlenton 34.5 kVIn Service
AF2-166Emlenton 34.5 kVWithdrawn
AF2-221Scalp Level 22.9 kVSuspended
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVActive
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-041Osterburg-Bedford North 23 kVWithdrawn
AG1-090Philipsburg 115 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-140Union City 34.5 kVSuspended
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-253Erie East-Union City 34.5 kVSuspended
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-377Philipsburg 115 kVActive
AG1-378Philipsburg 115 kVActive
AG1-514Springdale CT III 138 kVWithdrawn
AG1-548Erie South-Union City 115 kVActive
AG2-090Scalp Level 23 kV IVActive
AG2-091Scalp Level 23 kV VActive
AG2-176Geneva 115 kVActive
AG2-200North Warren–Russell 34.5 kVActive
AG2-206Tennessee Gas-East Towanda 115 kVActive
AG2-220East Towanda-South Troy 115 kVActive
AG2-221South Troy - North Towanda 34.5 kVActive
AG2-327Tennessee Gas-East Towanda 115 kVActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-411Statler Hill 115 kVActive
AG2-418Blain 115 kVActive
AG2-420Eclipse #2 34.5 kVActive
AG2-429Burma - Armstrong 138 kVActive
AG2-438Union City 34.5 kVActive
AG2-439Oxbow 34.5 kVActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AG2-654Craigsville - Leards Crossing 12 kVActive
AH1-005East Towanda-South Troy 115 kV IIActive
AH1-050Eclipse-Piney 115 kVActive
AH1-051Eclipse-Piney 115 kV IIActive
AH1-102Seward-Glory 115 kVActive
AH1-140Vasco 138 kVActive
AH1-158Eclipse-Piney 115 kV IIIActive
AH1-201Allegheny-New Baltimore 115kVActive
AH1-203Allegheny-Somerset 115 kVActive
AH1-205Allegheny-New Baltimore 115kVActive
AH1-212Bethlehem - Lilly 46 kVActive
AH1-268Seward-Glory 115 kV IIActive
AH1-313Moshannon-Milesburg 230 kV VIIActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-460Hooversville - Scalp Level 115 kVActive
AH1-490Venango Junction 34.5 kVActive
AH1-491Union City 34.5 kVActive
AH1-587Farmers Valley – Ridgeway 115 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
AH1-720East Towanda 230 kVActive
AH1-746Madera - Westover South 115 kVActive
Y1-033Penn Mar-Rock Wood 115kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n7166.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7166.1
Title
Replace 4/0 CU line exit at All Dam 6 Tap.
Description
Replace 4/0 CU line exit at All Dam 6 Tap on the 01AL&D6T - 01AL 4J
Total Cost ($USD)
$922,908
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 may need this upgrade in-service to be deliverable to the PJM system. If AH1-452 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01AL 4J-01AL&D6T 138.0 kV Ckt 1 line(Any)

System Reinforcement: n7166.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7166.2
Title
Reconductor 7.6 miles of 4/0 CU from All Dam 6 Tap to structure 84 (66 spans)
Description
Total Cost ($USD)
$26,284,067
Allocated Cost ($USD)
$0
Time Estimate
23 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 may need this upgrade in-service to be deliverable to the PJM system. If AH1-452 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01AL 4J-01AL&D6T 138.0 kV Ckt 1 line(Any)

System Reinforcement: n7165.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7165.1
Title
Replace T-line drops at All Dam 6
Description
Replace (2) T-line drops at All Dam 6
Total Cost ($USD)
$427,516
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 may need this upgrade in-service to be deliverable to the PJM system. If AH1-452 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01AL&D6T-01KITTAN 138.0 kV Ckt 1 line(Any)

System Reinforcement: n7165.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7165.2
Title
Reconductor All Dam 6 - Kittanning 138kV line
Description
Reconductor (Possible Rebuild) ~6 miles of the All Dam 6 - Kittanning 138kV line
Total Cost ($USD)
$21,034,523
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 may need this upgrade in-service to be deliverable to the PJM system. If AH1-452 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01AL&D6T-01KITTAN 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-PH1-076
Title
Reconductor Butler - Karns City 138 kV line.
Description
Reconductor (Possible Rebuild) ~15.6 miles on the Butler - Karns City 138 kV line.
Total Cost ($USD)
$51,840,579
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
01BUTLER-01KARNSC 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6183
Type
Load Flow
TO
APS
RTEP ID / TO ID
n6183
Title
Rebuild 10.4 miles of 4/0 CU from Columbia Big Pine - Garretts Run Jct 138 kV (99 spans).
Description
Rebuild 10.4 miles of 4/0 CU from Columbia Big Pine - Garretts Run Jct 138 kV (99 spans) using 954 kcmil 45/7 STR ACSR.
Total Cost ($USD)
$36,946,687
Allocated Cost ($USD)
$0
Time Estimate
26 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
01COLMBGPN-01GAR RN 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-018
Title
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Description
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Total Cost ($USD)
$5,581,666
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / WP-AF2-F-0010
Title
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Description
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Total Cost ($USD)
$19,555,226
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
01EDGEWT-01VASC T 138.0 kV Ckt 1 line(Any)

System Reinforcement: n7171.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7171.1
Title
Rebuild approximately 4.0 miles of 4/0 CU on the Kiski Valley to Columbia Big Pine 138kV line.
Description
Rebuild approximately 4.0 miles of 4/0 CU on the Kiski Valley to Columbia Big Pine 138kV line using 954 KCMIL 45/7 STR ACSR.
Total Cost ($USD)
$15,258,720
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
01KISKIV-01COLMBGPN 138.0 kV Ckt 1 line(Any)

System Reinforcement: n9116.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9116.0 / TC1-PN-001.d
Title
Rebuild approximately 11 miles of the Homer City-Shelocta 230 kV line with double bundled 795 kcmil 26/7 ACSS conductor
Description
Rebuild the Homer City – Shelocta 230 kV Line, approximately 11 miles, with double bunded 795 kcmil 26/7 ACSS conductor. Terminate new conductor at Homer City substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$39,312,233
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9117.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9117.0 / TC1-PN-001.f
Title
Replace disconnect switches at Homer City Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$1,254,760
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9225.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9225.0 / TC1-PN-001.e
Title
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Description
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Total Cost ($USD)
$107,569
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9118.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9118.0 / TC1-PN-001.g
Title
Replace disconnect switches and leads at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-003.g (Keystone-Shelocta 230kV line terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$0
Time Estimate
26 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.a
Title
Replace Sub conductor at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$869,783
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.b
Title
Adjust Relays at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$52,848
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: s3335.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
s3335.1 / PN-2024-007
Title
Replace Homer City South 345/230-23kV Transformer (Projected ISD 6/1/2027)
Description
Replace the South 345/230-23kV Transformer and associated equipment with: - One(1) 345/230kV Transformer with three single-phase units - Replace 345 kV circuit switcher, disconnects, circuit breaker, and substation conductor Transformer Ratings: - Before Proposed Solution: 649/836/793/984 MVA (SN/SLTE/WN/WLTE) - After Proposed Solution: 913/1147/1201/1376 MVA (SN/SLTE/WN/WLTE)
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-452 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-452 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26HOMER CT-26HOMER CT _ 230.0 kV Ckt S line(Any)
26HOMER CY-26HOMER CT _ 345.0/230.0 kV Ckt S transformer(Any)

System Reinforcement: n9120.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9120.0 / TC1-PN-003.c
Title
Replace substation conductor at Keystone substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$187,749
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9121.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9121.0 / TC1-PN-003.d
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9124.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9124.0 / TC1-PN-003.e
Title
Replace bus conductor at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,104,686
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9125.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9125.0 / TC1-PN-003.f
Title
Replace disconnect switches at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,254,762
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9127.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9127.0 / TC1-PN-003.g
Title
Replace disconnect switches and leads at Shelocta Substation (Keystone-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-001.g (Homer City-Shelocta 230kV line) terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$0
Time Estimate
26 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9126.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9126.0 / TC1-PN-003.h
Title
Replace breaker leads at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$152,770
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9119.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9119.0 / TC1-PN-003.b
Title
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor
Description
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor. Terminate new conductor at Keystone substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$9,533,592
Allocated Cost ($USD)
$0
Time Estimate
23 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.a
Title
Adjust relay settings at Keystone and Shelocta
Description
Total Cost ($USD)
$103,523
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.b
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-011
Title
Replace 500/230 kV Conemaugh #3 Transformer
Description
Replace 500/230 kV Conemaugh #3 Transformer
Total Cost ($USD)
$28,558,871
Allocated Cost ($USD)
$0
Time Estimate
66 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-452 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-452 could receive cost allocation. Although AH1-452 may not presently have cost responsibility for this upgrade, AH1-452 is a potential Aggregate Pool Contributor.

FacilityContingency
CONEM-GH-26CONEMAGH 500.0/230.0 kV Ckt 3 transformer(Any)

Attachments

AH1-452 One Line Diagram

AH1-452 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.