AH1-570 Phase I Study Report

v1.00 released 2025-10-29 22:08

Headquarters - Millersburg Junction 69 kV

15.6 MW Capacity / 25.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is South Fork Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is East Kentucky Power Cooperative, Inc..

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the East Kentucky Power Cooperative, Inc. zone — Kentucky. The installed facilities will have a total capability of 25.0 MW with 15.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-570
Project Name:
Headquarters - Millersburg Junction 69 kV
Project Developer Name:
South Fork Solar, LLC
State:
Kentucky
County:
Undetermined
Transmission Owner:
East Kentucky Power Cooperative, Inc.
MFO:
25.0
MWE:
25.0
MWC:
15.6
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-570 will interconnect on the East Kentucky Power Cooperative, Inc. transmission system tapping the Headquarters - Millersburg Junction 69 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-570 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-570Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$377,500$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$3,702,500$3,702,500
Network Upgrades$1,065,000$1,065,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$5,145,000$4,767,500

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-570

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-570 Project due at DP1
ABA - B
AH1-570$476,750$100,000$376,750

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)One (1) 69 kV generator lead line to include, but not limited to, installation of one 69 kV breaker, a 69 kV line monopole dead-end structure and foundation, a 3-pole disconnect switch mounted to the monopole, line conductor from the dead-end structure to the bus position in the switchyard, two (2) 48-strand fiber optic cables, and 69 kV metering equipment.$755,000 $377,500 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)East Nicholas County 69 Switching Station: Construct a new 69 kV switching station along the Headquarters-Millersburg Junction 69 kV line.$7,405,000 $3,702,500 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Revise relay settings/relays at the existing Hunt substation.$65,000 $32,500 (See Note 1)
(Pending)Loop the existing Headquarters-Millersburg Junction 69 kV line into the new East Nicholas County interconnection switching station.$580,000 $290,000 (See Note 1)
(Pending)Revise relay settings/relays at the existing Headquarters substation.$65,000 $32,500 (See Note 1)
(Pending)Install new overhead optical ground wire (OPGW) on the existing Hunt-Sideview 69 kV line (16.45 miles).$2,130,000 $710,000 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 19 to 31 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. EKPC interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-570 was evaluated as a 25.0 MW (15.6 MW Capacity) injection in the EKPC area.

AH1-570 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 25.0 MW (25.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.961.67
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.631.67
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.611.63
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.911.63
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#8122_05BEATTY 345_302W_SRT-A
BreakerAC114.33 %1203.0B1375.441.53
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#18136_05CHENOWETH 345_CB1_SRT-A-1
BreakerAC111.87 %1203.0B1345.771.54
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#18138_05CHENOWETH 345_CB3_SRT-A
BreakerAC111.87 %1203.0B1345.761.54
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
DAY_GREENE_345KV_FB_GJ_EE_SRT-A
BreakerAC111.81 %1203.0B1345.131.57
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#18137_05CHENOWETH 345_CB2_SRT-A
BreakerAC110.91 %1203.0B1334.281.54
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
495_SRT-A
TowerAC107.81 %1203.0B1296.981.52
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P1-2_#18134_SRT-A-1
SingleAC105.34 %1203.0B1267.271.12
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P1-2_#18134_SRT-A-2
SingleAC104.03 %1203.0B1251.481.12
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
GREENE_345KV_E_SRT-A
BusAC103.68 %1203.0B1247.231.48
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
34524 34598_SRT-A
TowerAC102.91 %1203.0B1238.041.4
GD2AEP
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC101.19 %1203.0B1217.341.35
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#3195_05BEATTY 345_304E_SRT-A
BreakerAC111.35 %1203.0B1339.591.51
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A
BreakerAC100.06 %1203.0B1203.741.4
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A
BreakerAC100.06 %1203.0B1203.721.4
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC109.09 %1203.0B1312.321.44
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC108.01 %1203.0B1299.361.45
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC108.01 %1203.0B1299.331.45
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC108.01 %1203.0B1299.321.45
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC106.27 %1203.0B1278.41.1
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.8 %2320.0B2500.921.29
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.480.94
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.971.8
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.552.49
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.432.48
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.982.48
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.432.48
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC116.66 %5523.0B6443.113.6
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.322.61
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.532.74
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.12 %5523.0B6192.173.64
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.852.0
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.023.3
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.09 %5523.0B5914.322.97
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.342.39
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.473.03
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.143.06
GD2AEP
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line
34541 34553_SRT-A
TowerAC100.75 %257.0B258.941.71
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC156.15 %1540.0B2404.662.12
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC154.73 %1540.0B2382.872.09
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC153.9 %1540.0B2370.072.17
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC153.46 %1540.0B2363.362.17
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC153.34 %1540.0B2361.462.17
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC145.41 %1540.0B2239.271.52
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.341.58
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC135.59 %1540.0B2088.162.13
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC132.73 %1540.0B2044.012.12
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34524 34598_SRT-A
TowerAC132.58 %1540.0B2041.732.13
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.091.48
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC130.87 %1540.0B2015.352.04
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC112.42 %1540.0B1731.231.3
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC108.09 %1540.0B1664.561.31
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.36 %1540.0B1561.020.95
GD2DEO&K
08LONGBR-08MTZION 138.0 kV Ckt 1 line
34541 34553_SRT-A
TowerAC106.05 %284.0B301.172.37
GD2DEO&K/EKPC
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line
34541 34553_SRT-A
TowerAC115.17 %284.0B327.082.37
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC118.71 %1532.0B1818.597.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC118.58 %1532.0B1816.677.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC117.61 %1532.0B1801.715.59
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC116.62 %1532.0B1786.66.04
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC115.28 %1532.0B1766.126.1
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC115.23 %1532.0B1765.386.1
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC115.19 %1532.0B1764.776.1
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC115.16 %1532.0B1764.326.1
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC114.67 %1240.0A1421.954.16
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC114.33 %1532.0B1751.587.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
SingleAC105.32 %1532.0B1613.525.22
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
SingleAC103.95 %1532.0B1592.574.42
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC118.45 %1203.0B1424.981.43
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC116.03 %1203.0B1395.781.43
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC115.99 %1203.0B1395.311.43
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC115.99 %1203.0B1395.31.43
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC115.08 %1203.0B1384.411.08
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC103.58 %1203.0B1246.021.1
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P1-2_#762_8072_SRT-A
SingleAC102.19 %1203.0B1229.311.04
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-1
TowerAC102.16 %1203.0B1229.041.1

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:1.67
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:1.67
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:1.63
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:1.63
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#8122_05BEATTY 345_302W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8122_05BEATTY 345_302W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.33 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1375.44
MW Contribution:1.53
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.305
270161DARBY CT6
50/50
3.26
253317AC1-085 GEN4
Solar/Wind Harmer
8.481
253394AE2-221_GEN
Solar/Wind Harmer
4.048
253398AE2-221_GEN2
Solar/Wind Harmer
4.048
25183208HLCRTG
Solar/Wind Harmer
4.913
252509AD1-136 GEN
Solar/Wind Harmer
0.173
252519AF1-045_GEN
Solar/Wind Harmer
3.89
252516AE2-318_GEN
Solar/Wind Harmer
2.968
972043AH1-570 GEN
Solar/Wind Harmer
1.535
972045AH1-571 GEN
Solar/Wind Harmer
1.228
339221AD2-048_GEN
Solar/Wind Harmer
0.941
971125AH1-004 GEN
Solar/Wind Harmer
2.392
970107AG2-081 GEN
Solar/Wind Harmer
1.794
960161AF2-307 GEN
Solar/Wind Harmer
3.613
270518AE2-148 GEN
Solar/Wind Harmer
6.516
942891AE2-308 GEN
Solar/Wind Harmer
5.35
270186AC1-089 GEN
Solar/Wind Harmer
3.21
25194408D.CRK1
Adder
3.805
25194508D.CRK3
Adder
0.711
253370AE2-315 SEC1
Adder
1.001
962581AG1-107 GEN
Solar/Wind Harmer
2.428
961491AF2-440 GEN
Solar/Wind Harmer
1.009
25322209TAIT E
Adder
4.451
25322209TAIT E
Adder
4.351
25326109MON D
Adder
0.591
970235AG2-159 GEN
Solar/Wind Harmer
1.738
970235AG2-159 GEN
Solar/Wind Harmer
1.061
946101AF1-275 GEN
Solar/Wind Helper
0.601
270159DARBY CT4
50/50
60.679
253343AC1-166 GEN
Solar/Wind Harmer
5.417
253325AC1-069 GEN
Solar/Wind Harmer
5.224
253432AC1-085 GEN2
Solar/Wind Harmer
0.271
946171AF1-282 GEN
Solar/Wind Harmer
10.125
945681AF1-233 GEN
Solar/Wind Harmer
15.185
25196808ZIMRHP
Adder
51.482
252507AC2-088 GEN
Solar/Wind Harmer
1.21
339216AC1-074 GEN
Solar/Wind Harmer
1.047
943111AE2-339 GEN
Solar/Wind Harmer
0.527
3429421JKCT 10G
Adder
4.873
3429241JKCT 3G
Adder
6.638
25194608D.CRK4
Adder
0.827
253370AE2-315 SEC1
Adder
1.001
253371AE2-315 SEC2
Adder
0.947
25326309TAIT D
Adder
0.499
960071AF2-298 GEN
Solar/Wind Harmer
2.171
25196008MFTGT1
Adder
0.602
270156DARBY CT1
50/50
61.661
270157DARBY CT2
50/50
61.51
270158DARBY CT3
50/50
60.528
270340AC2-060 GEN
Solar/Wind Harmer
3.017
972163AH1-664 GEN
Solar/Wind Harmer
7.891
972165AH1-665 GEN
Solar/Wind Harmer
6.313
339243AC2-075 GEN1
Solar/Wind Harmer
0.284
3429211JKCT 2G
Adder
6.552
945631AF1-228 GEN
Solar/Wind Harmer
2.522
253372AE2-315 SEC3
Adder
0.947
253372AE2-315 SEC3
Adder
0.947
252524AE2-267 GEN
Solar/Wind Harmer
0.787
25196408WSDLE3
Adder
4.402
25196308WSDLE2
Adder
4.364
25196208WSDLE1
Adder
4.353
25196708WSDLE6
Adder
4.342
25196508WSDLE4
Adder
4.233
270367AC2-061_GEN
Solar/Wind Harmer
1.55
25306009OHH W.
Adder
1.314
25196108MFTGT2
Adder
0.664
25196108MFTGT2
Adder
0.616
270520AE2-214 GEN
Solar/Wind Helper
4.799
270054AF2-122 C O1
Solar/Wind Helper
0.645
253338AC1-165 GEN
Solar/Wind Harmer
5.417
253333AC1-068 GEN
Solar/Wind Harmer
5.224
253415AE1-040 GEN
Solar/Wind Harmer
1.48
253316AC1-085 GEN3
Solar/Wind Harmer
8.481
253433AC1-085 GEN1
Solar/Wind Harmer
5.384
946181AF1-283 GEN
Solar/Wind Harmer
13.162
958171AF2-111 GEN
Solar/Wind Harmer
22.314
253406AD2-031_GEN
Solar/Wind Harmer
1.04
972167AH1-666 GEN
Solar/Wind Harmer
6.479
3429391JKCT 9G
Adder
4.873
252510AF1-249 C
Solar/Wind Harmer
0.212
970093AG2-073 GEN
Solar/Wind Harmer
5.037
25194608D.CRK4
Adder
0.827
253303V4-073 C
Solar/Wind Harmer
0.058
253370AE2-315 SEC1
Adder
1.001
253371AE2-315 SEC2
Adder
0.947
25196608WSDLE5
Adder
4.277
966571AG1-526 GEN
Solar/Wind Harmer
9.958
25196008MFTGT1
Adder
0.583
241955AC1-078 GEN
Solar/Wind Helper
1.245
960801AF2-371 GEN
Solar/Wind Helper
0.548
964871AG1-351 GEN
Solar/Wind Helper
0.378
LAGNLTFEXP_LAGN->PJM
CLTF
2.836
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.767
TVALTFEXP_TVA->PJM
CLTF
1.555
NYPJM->LTFIMP_NY
CLTF
0.584
LGEELTFEXP_LGEE->PJM
CLTF
2.263
WECLTFEXP_WEC->PJM
CLTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.361
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.405
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.82
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.017
MECLTFEXP_MEC->PJM
CLTF
1.973
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#18136_05CHENOWETH 345_CB1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18136_05CHENOWETH 345_CB1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1345.77
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.32
270161DARBY CT6
50/50
3.275
253317AC1-085 GEN4
Solar/Wind Harmer
8.524
253394AE2-221_GEN
Solar/Wind Harmer
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.069
25183208HLCRTG
Solar/Wind Harmer
4.94
252509AD1-136 GEN
Solar/Wind Harmer
0.174
252519AF1-045_GEN
Solar/Wind Harmer
3.913
252516AE2-318_GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
1.545
972045AH1-571 GEN
Solar/Wind Harmer
1.236
339221AD2-048_GEN
Solar/Wind Harmer
0.947
971125AH1-004 GEN
Solar/Wind Harmer
2.408
970107AG2-081 GEN
Solar/Wind Harmer
1.806
960161AF2-307 GEN
Solar/Wind Harmer
3.637
942891AE2-308 GEN
Solar/Wind Harmer
5.387
270186AC1-089 GEN
Solar/Wind Harmer
3.228
25194408D.CRK1
Adder
3.829
25194508D.CRK3
Adder
0.716
253370AE2-315 SEC1
Adder
1.005
962581AG1-107 GEN
Solar/Wind Harmer
2.441
961491AF2-440 GEN
Solar/Wind Harmer
1.014
25322209TAIT E
Adder
4.469
25322209TAIT E
Adder
4.369
25326109MON D
Adder
0.593
970235AG2-159 GEN
Solar/Wind Harmer
1.751
970235AG2-159 GEN
Solar/Wind Harmer
1.069
946101AF1-275 GEN
Solar/Wind Helper
0.589
270159DARBY CT4
50/50
60.953
253343AC1-166 GEN
Solar/Wind Harmer
5.441
253325AC1-069 GEN
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
946171AF1-282 GEN
Solar/Wind Harmer
10.176
945681AF1-233 GEN
Solar/Wind Harmer
15.273
25196808ZIMRHP
Adder
51.789
252507AC2-088 GEN
Solar/Wind Harmer
1.218
339216AC1-074 GEN
Solar/Wind Harmer
1.054
943111AE2-339 GEN
Solar/Wind Harmer
0.53
3429421JKCT 10G
Adder
4.906
3429241JKCT 3G
Adder
6.683
25194608D.CRK4
Adder
0.832
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
25326309TAIT D
Adder
0.501
960071AF2-298 GEN
Solar/Wind Harmer
2.181
25196008MFTGT1
Adder
0.606
270156DARBY CT1
50/50
61.939
270157DARBY CT2
50/50
61.788
270158DARBY CT3
50/50
60.801
270340AC2-060 GEN
Solar/Wind Harmer
3.025
972163AH1-664 GEN
Solar/Wind Harmer
7.937
972165AH1-665 GEN
Solar/Wind Harmer
6.35
339243AC2-075 GEN1
Solar/Wind Harmer
0.285
3429211JKCT 2G
Adder
6.597
252524AE2-267 GEN
Solar/Wind Harmer
0.792
25196408WSDLE3
Adder
4.43
25196308WSDLE2
Adder
4.392
25196208WSDLE1
Adder
4.381
25196708WSDLE6
Adder
4.37
25196508WSDLE4
Adder
4.26
253372AE2-315 SEC3
Adder
0.951
253372AE2-315 SEC3
Adder
0.951
270367AC2-061_GEN
Solar/Wind Harmer
1.559
25306009OHH W.
Adder
1.321
25196108MFTGT2
Adder
0.668
25196108MFTGT2
Adder
0.621
945631AF1-228 GEN
Solar/Wind Helper
2.298
270520AE2-214 GEN
Solar/Wind Helper
4.704
270054AF2-122 C O1
Solar/Wind Helper
0.643
253338AC1-165 GEN
Solar/Wind Harmer
5.441
253333AC1-068 GEN
Solar/Wind Harmer
5.248
253415AE1-040 GEN
Solar/Wind Harmer
1.485
253316AC1-085 GEN3
Solar/Wind Harmer
8.524
253433AC1-085 GEN1
Solar/Wind Harmer
5.411
946181AF1-283 GEN
Solar/Wind Harmer
13.229
958171AF2-111 GEN
Solar/Wind Harmer
22.44
253406AD2-031_GEN
Solar/Wind Harmer
1.044
972167AH1-666 GEN
Solar/Wind Harmer
6.516
3429391JKCT 9G
Adder
4.906
252510AF1-249 C
Solar/Wind Harmer
0.214
970093AG2-073 GEN
Solar/Wind Harmer
5.074
25194608D.CRK4
Adder
0.832
25196608WSDLE5
Adder
4.304
253303V4-073 C
Solar/Wind Harmer
0.058
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
966571AG1-526 GEN
Solar/Wind Harmer
10.035
25196008MFTGT1
Adder
0.587
241955AC1-078 GEN
Solar/Wind Helper
1.357
960801AF2-371 GEN
Solar/Wind Helper
0.58
964871AG1-351 GEN
Solar/Wind Helper
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.887
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.838
TVALTFEXP_TVA->PJM
CLTF
1.581
NYPJM->LTFIMP_NY
CLTF
0.571
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
0.369
CPLELTFEXP_CPLE->PJM
CLTF
0.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.171
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.118
MECLTFEXP_MEC->PJM
CLTF
2.015
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#18138_05CHENOWETH 345_CB3_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18138_05CHENOWETH 345_CB3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1345.76
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.32
270161DARBY CT6
50/50
3.275
253317AC1-085 GEN4
Solar/Wind Harmer
8.524
253394AE2-221_GEN
Solar/Wind Harmer
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.069
25183208HLCRTG
Solar/Wind Harmer
4.94
252509AD1-136 GEN
Solar/Wind Harmer
0.174
252519AF1-045_GEN
Solar/Wind Harmer
3.913
252516AE2-318_GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
1.545
972045AH1-571 GEN
Solar/Wind Harmer
1.236
339221AD2-048_GEN
Solar/Wind Harmer
0.947
971125AH1-004 GEN
Solar/Wind Harmer
2.408
970107AG2-081 GEN
Solar/Wind Harmer
1.806
960161AF2-307 GEN
Solar/Wind Harmer
3.637
942891AE2-308 GEN
Solar/Wind Harmer
5.387
270186AC1-089 GEN
Solar/Wind Harmer
3.228
25194408D.CRK1
Adder
3.829
25194508D.CRK3
Adder
0.716
253370AE2-315 SEC1
Adder
1.005
962581AG1-107 GEN
Solar/Wind Harmer
2.441
961491AF2-440 GEN
Solar/Wind Harmer
1.014
25322209TAIT E
Adder
4.469
25322209TAIT E
Adder
4.369
25326109MON D
Adder
0.593
970235AG2-159 GEN
Solar/Wind Harmer
1.751
970235AG2-159 GEN
Solar/Wind Harmer
1.069
946101AF1-275 GEN
Solar/Wind Helper
0.589
270159DARBY CT4
50/50
60.953
253343AC1-166 GEN
Solar/Wind Harmer
5.441
253325AC1-069 GEN
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
946171AF1-282 GEN
Solar/Wind Harmer
10.176
945681AF1-233 GEN
Solar/Wind Harmer
15.273
25196808ZIMRHP
Adder
51.789
252507AC2-088 GEN
Solar/Wind Harmer
1.218
339216AC1-074 GEN
Solar/Wind Harmer
1.054
943111AE2-339 GEN
Solar/Wind Harmer
0.53
3429421JKCT 10G
Adder
4.906
3429241JKCT 3G
Adder
6.683
25194608D.CRK4
Adder
0.832
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
25326309TAIT D
Adder
0.501
960071AF2-298 GEN
Solar/Wind Harmer
2.181
25196008MFTGT1
Adder
0.606
270156DARBY CT1
50/50
61.939
270157DARBY CT2
50/50
61.788
270158DARBY CT3
50/50
60.801
270340AC2-060 GEN
Solar/Wind Harmer
3.025
972163AH1-664 GEN
Solar/Wind Harmer
7.937
972165AH1-665 GEN
Solar/Wind Harmer
6.35
339243AC2-075 GEN1
Solar/Wind Harmer
0.285
3429211JKCT 2G
Adder
6.597
252524AE2-267 GEN
Solar/Wind Harmer
0.792
25196408WSDLE3
Adder
4.43
25196308WSDLE2
Adder
4.392
25196208WSDLE1
Adder
4.381
25196708WSDLE6
Adder
4.37
25196508WSDLE4
Adder
4.26
253372AE2-315 SEC3
Adder
0.951
253372AE2-315 SEC3
Adder
0.951
270367AC2-061_GEN
Solar/Wind Harmer
1.559
25306009OHH W.
Adder
1.321
25196108MFTGT2
Adder
0.668
25196108MFTGT2
Adder
0.621
945631AF1-228 GEN
Solar/Wind Helper
2.298
270520AE2-214 GEN
Solar/Wind Helper
4.704
270054AF2-122 C O1
Solar/Wind Helper
0.643
253338AC1-165 GEN
Solar/Wind Harmer
5.441
253333AC1-068 GEN
Solar/Wind Harmer
5.248
253415AE1-040 GEN
Solar/Wind Harmer
1.485
253316AC1-085 GEN3
Solar/Wind Harmer
8.524
253433AC1-085 GEN1
Solar/Wind Harmer
5.411
946181AF1-283 GEN
Solar/Wind Harmer
13.229
958171AF2-111 GEN
Solar/Wind Harmer
22.44
253406AD2-031_GEN
Solar/Wind Harmer
1.044
972167AH1-666 GEN
Solar/Wind Harmer
6.516
3429391JKCT 9G
Adder
4.906
252510AF1-249 C
Solar/Wind Harmer
0.214
970093AG2-073 GEN
Solar/Wind Harmer
5.074
25194608D.CRK4
Adder
0.832
25196608WSDLE5
Adder
4.304
253303V4-073 C
Solar/Wind Harmer
0.058
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
966571AG1-526 GEN
Solar/Wind Harmer
10.035
25196008MFTGT1
Adder
0.587
241955AC1-078 GEN
Solar/Wind Helper
1.357
960801AF2-371 GEN
Solar/Wind Helper
0.58
964871AG1-351 GEN
Solar/Wind Helper
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.887
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.838
TVALTFEXP_TVA->PJM
CLTF
1.581
NYPJM->LTFIMP_NY
CLTF
0.571
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
0.369
CPLELTFEXP_CPLE->PJM
CLTF
0.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.171
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.118
MECLTFEXP_MEC->PJM
CLTF
2.015
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o DAY_GREENE_345KV_FB_GJ_EE_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
DAY_GREENE_345KV_FB_GJ_EE_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.81 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1345.13
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.324
270161DARBY CT6
50/50
3.279
253317AC1-085 GEN4
Solar/Wind Harmer
8.99
253394AE2-221_GEN
Solar/Wind Harmer
4.408
253398AE2-221_GEN2
Solar/Wind Harmer
4.408
25183208HLCRTG
Solar/Wind Harmer
5.024
252509AD1-136 GEN
Solar/Wind Harmer
0.177
252519AF1-045_GEN
Solar/Wind Harmer
3.972
252516AE2-318_GEN
Solar/Wind Harmer
3.03
972043AH1-570 GEN
Solar/Wind Harmer
1.575
972045AH1-571 GEN
Solar/Wind Harmer
1.26
339221AD2-048_GEN
Solar/Wind Harmer
0.965
971125AH1-004 GEN
Solar/Wind Harmer
2.453
970107AG2-081 GEN
Solar/Wind Harmer
1.84
960161AF2-307 GEN
Solar/Wind Harmer
3.711
942891AE2-308 GEN
Solar/Wind Harmer
5.49
270186AC1-089 GEN
Solar/Wind Harmer
3.335
253370AE2-315 SEC1
Adder
1.093
25194408D.CRK1
Adder
3.872
25194508D.CRK3
Adder
0.724
962581AG1-107 GEN
Solar/Wind Harmer
2.546
961491AF2-440 GEN
Solar/Wind Harmer
1.058
25322209TAIT E
Adder
4.734
25322209TAIT E
Adder
4.628
25326109MON D
Adder
0.622
970235AG2-159 GEN
Solar/Wind Harmer
1.777
970235AG2-159 GEN
Solar/Wind Harmer
1.085
270518AE2-148 GEN
Solar/Wind Helper
14.678
946101AF1-275 GEN
Solar/Wind Helper
0.587
270159DARBY CT4
50/50
61.028
253343AC1-166 GEN
Solar/Wind Harmer
5.458
253325AC1-069 GEN
Solar/Wind Harmer
5.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.732
945681AF1-233 GEN
Solar/Wind Harmer
15.573
25196808ZIMRHP
Adder
52.565
252507AC2-088 GEN
Solar/Wind Harmer
1.237
339216AC1-074 GEN
Solar/Wind Harmer
1.073
943111AE2-339 GEN
Solar/Wind Harmer
0.54
3429421JKCT 10G
Adder
4.999
3429241JKCT 3G
Adder
6.811
253370AE2-315 SEC1
Adder
1.093
253371AE2-315 SEC2
Adder
1.034
25194608D.CRK4
Adder
0.842
25326309TAIT D
Adder
0.531
960071AF2-298 GEN
Solar/Wind Harmer
2.268
25196008MFTGT1
Adder
0.611
270156DARBY CT1
50/50
62.016
270157DARBY CT2
50/50
61.864
270158DARBY CT3
50/50
60.876
270340AC2-060 GEN
Solar/Wind Harmer
3.1
972163AH1-664 GEN
Solar/Wind Harmer
8.093
972165AH1-665 GEN
Solar/Wind Harmer
6.475
339243AC2-075 GEN1
Solar/Wind Harmer
0.291
3429211JKCT 2G
Adder
6.723
253372AE2-315 SEC3
Adder
1.034
253372AE2-315 SEC3
Adder
1.034
270367AC2-061_GEN
Solar/Wind Harmer
1.613
252524AE2-267 GEN
Solar/Wind Harmer
0.799
25196408WSDLE3
Adder
4.472
25196308WSDLE2
Adder
4.433
25196208WSDLE1
Adder
4.422
25196708WSDLE6
Adder
4.411
25196508WSDLE4
Adder
4.299
25306009OHH W.
Adder
1.407
253349AC2-067 GEN
Solar/Wind Harmer
2.193
253400AC2-068 GEN
Solar/Wind Harmer
0.882
25196108MFTGT2
Adder
0.673
25196108MFTGT2
Adder
0.625
945631AF1-228 GEN
Solar/Wind Helper
2.288
270520AE2-214 GEN
Solar/Wind Helper
4.685
270054AF2-122 C O1
Solar/Wind Helper
0.639
253338AC1-165 GEN
Solar/Wind Harmer
5.458
253333AC1-068 GEN
Solar/Wind Harmer
5.264
253415AE1-040 GEN
Solar/Wind Harmer
1.515
253316AC1-085 GEN3
Solar/Wind Harmer
8.99
253433AC1-085 GEN1
Solar/Wind Harmer
5.706
946181AF1-283 GEN
Solar/Wind Harmer
13.952
958171AF2-111 GEN
Solar/Wind Harmer
22.871
253406AD2-031_GEN
Solar/Wind Harmer
1.122
972167AH1-666 GEN
Solar/Wind Harmer
6.644
3429391JKCT 9G
Adder
4.999
253303V4-073 C
Solar/Wind Harmer
0.063
253370AE2-315 SEC1
Adder
1.093
253371AE2-315 SEC2
Adder
1.034
252510AF1-249 C
Solar/Wind Harmer
0.216
970093AG2-073 GEN
Solar/Wind Harmer
5.17
25194608D.CRK4
Adder
0.842
25196608WSDLE5
Adder
4.344
966571AG1-526 GEN
Solar/Wind Harmer
10.222
25196008MFTGT1
Adder
0.591
241955AC1-078 GEN
Solar/Wind Helper
1.348
960801AF2-371 GEN
Solar/Wind Helper
0.575
964871AG1-351 GEN
Solar/Wind Helper
0.397
LAGNLTFEXP_LAGN->PJM
CLTF
2.957
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
1.62
NYPJM->LTFIMP_NY
CLTF
0.555
LGEELTFEXP_LGEE->PJM
CLTF
2.318
WECLTFEXP_WEC->PJM
CLTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
0.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.272
MECLTFEXP_MEC->PJM
CLTF
2.048
SIGELTFEXP_SIGE->PJM
CLTF
0.131

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#18137_05CHENOWETH 345_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18137_05CHENOWETH 345_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.91 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1334.28
MW Contribution:1.54
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.32
270161DARBY CT6
50/50
3.275
253317AC1-085 GEN4
Solar/Wind Harmer
8.524
253394AE2-221_GEN
Solar/Wind Harmer
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.069
25183208HLCRTG
Solar/Wind Harmer
4.94
252509AD1-136 GEN
Solar/Wind Harmer
0.174
252519AF1-045_GEN
Solar/Wind Harmer
3.913
252516AE2-318_GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
1.545
972045AH1-571 GEN
Solar/Wind Harmer
1.236
339221AD2-048_GEN
Solar/Wind Harmer
0.947
971125AH1-004 GEN
Solar/Wind Harmer
2.408
970107AG2-081 GEN
Solar/Wind Harmer
1.806
960161AF2-307 GEN
Solar/Wind Harmer
3.637
942891AE2-308 GEN
Solar/Wind Harmer
5.387
270186AC1-089 GEN
Solar/Wind Harmer
3.228
25194408D.CRK1
Adder
3.829
25194508D.CRK3
Adder
0.716
253370AE2-315 SEC1
Adder
1.005
962581AG1-107 GEN
Solar/Wind Harmer
2.441
961491AF2-440 GEN
Solar/Wind Harmer
1.014
25322209TAIT E
Adder
4.469
25322209TAIT E
Adder
4.369
25326109MON D
Adder
0.593
970235AG2-159 GEN
Solar/Wind Harmer
1.751
970235AG2-159 GEN
Solar/Wind Harmer
1.069
946101AF1-275 GEN
Solar/Wind Helper
0.589
270159DARBY CT4
50/50
60.952
253343AC1-166 GEN
Solar/Wind Harmer
5.441
253325AC1-069 GEN
Solar/Wind Harmer
5.248
253432AC1-085 GEN2
Solar/Wind Harmer
0.272
946171AF1-282 GEN
Solar/Wind Harmer
10.176
945681AF1-233 GEN
Solar/Wind Harmer
15.273
25196808ZIMRHP
Adder
51.788
252507AC2-088 GEN
Solar/Wind Harmer
1.218
339216AC1-074 GEN
Solar/Wind Harmer
1.054
943111AE2-339 GEN
Solar/Wind Harmer
0.53
3429421JKCT 10G
Adder
4.906
3429241JKCT 3G
Adder
6.683
25194608D.CRK4
Adder
0.832
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
25326309TAIT D
Adder
0.501
960071AF2-298 GEN
Solar/Wind Harmer
2.181
25196008MFTGT1
Adder
0.606
270156DARBY CT1
50/50
61.939
270157DARBY CT2
50/50
61.787
270158DARBY CT3
50/50
60.801
270340AC2-060 GEN
Solar/Wind Harmer
3.025
972163AH1-664 GEN
Solar/Wind Harmer
7.937
972165AH1-665 GEN
Solar/Wind Harmer
6.349
339243AC2-075 GEN1
Solar/Wind Harmer
0.285
3429211JKCT 2G
Adder
6.597
252524AE2-267 GEN
Solar/Wind Harmer
0.792
25196408WSDLE3
Adder
4.43
25196308WSDLE2
Adder
4.392
25196208WSDLE1
Adder
4.381
25196708WSDLE6
Adder
4.37
25196508WSDLE4
Adder
4.26
253372AE2-315 SEC3
Adder
0.951
253372AE2-315 SEC3
Adder
0.951
270367AC2-061_GEN
Solar/Wind Harmer
1.559
25306009OHH W.
Adder
1.321
25196108MFTGT2
Adder
0.668
25196108MFTGT2
Adder
0.621
945631AF1-228 GEN
Solar/Wind Helper
2.298
270520AE2-214 GEN
Solar/Wind Helper
4.704
270054AF2-122 C O1
Solar/Wind Helper
0.643
253338AC1-165 GEN
Solar/Wind Harmer
5.441
253333AC1-068 GEN
Solar/Wind Harmer
5.248
253415AE1-040 GEN
Solar/Wind Harmer
1.485
253316AC1-085 GEN3
Solar/Wind Harmer
8.524
253433AC1-085 GEN1
Solar/Wind Harmer
5.411
946181AF1-283 GEN
Solar/Wind Harmer
13.229
958171AF2-111 GEN
Solar/Wind Harmer
22.44
253406AD2-031_GEN
Solar/Wind Harmer
1.044
972167AH1-666 GEN
Solar/Wind Harmer
6.516
3429391JKCT 9G
Adder
4.906
252510AF1-249 C
Solar/Wind Harmer
0.214
970093AG2-073 GEN
Solar/Wind Harmer
5.073
25194608D.CRK4
Adder
0.832
25196608WSDLE5
Adder
4.304
253303V4-073 C
Solar/Wind Harmer
0.058
253370AE2-315 SEC1
Adder
1.005
253371AE2-315 SEC2
Adder
0.951
966571AG1-526 GEN
Solar/Wind Harmer
10.035
25196008MFTGT1
Adder
0.587
241955AC1-078 GEN
Solar/Wind Helper
1.357
960801AF2-371 GEN
Solar/Wind Helper
0.58
964871AG1-351 GEN
Solar/Wind Helper
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.887
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.838
TVALTFEXP_TVA->PJM
CLTF
1.581
NYPJM->LTFIMP_NY
CLTF
0.571
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
0.369
CPLELTFEXP_CPLE->PJM
CLTF
0.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.752
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.117
MECLTFEXP_MEC->PJM
CLTF
2.014
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o 495_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
495_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.81 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1296.98
MW Contribution:1.52
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
63.939
270157DARBY CT2
50/50
63.782
270158DARBY CT3
50/50
62.764
270340AC2-060 GEN
Solar/Wind Harmer
3.2
972163AH1-664 GEN
Solar/Wind Harmer
8.09
972165AH1-665 GEN
Solar/Wind Harmer
6.472
339243AC2-075 GEN1
Solar/Wind Harmer
0.281
3429211JKCT 2G
Adder
6.539
945631AF1-228 GEN
Solar/Wind Helper
1.52
270520AE2-214 GEN
Solar/Wind Helper
3.792
270159DARBY CT4
50/50
62.92
253343AC1-166 GEN
Solar/Wind Harmer
5.619
253325AC1-069 GEN
Solar/Wind Harmer
5.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
946171AF1-282 GEN
Solar/Wind Harmer
12.859
945681AF1-233 GEN
Solar/Wind Harmer
15.598
252507AC2-088 GEN
Solar/Wind Harmer
1.126
25196808ZIMRHP
Adder
47.5
339216AC1-074 GEN
Solar/Wind Harmer
1.037
943111AE2-339 GEN
Solar/Wind Harmer
0.526
3429421JKCT 10G
Adder
4.88
3429241JKCT 3G
Adder
6.625
253338AC1-165 GEN
Solar/Wind Harmer
5.619
253333AC1-068 GEN
Solar/Wind Harmer
5.419
253415AE1-040 GEN
Solar/Wind Harmer
1.551
253316AC1-085 GEN3
Solar/Wind Harmer
10.771
253433AC1-085 GEN1
Solar/Wind Harmer
6.837
946181AF1-283 GEN
Solar/Wind Harmer
16.716
253406AD2-031_GEN
Solar/Wind Harmer
1.315
958171AF2-111 GEN
Solar/Wind Harmer
23.108
972167AH1-666 GEN
Solar/Wind Harmer
6.657
3429391JKCT 9G
Adder
4.88
970093AG2-073 GEN
Solar/Wind Harmer
4.979
966571AG1-526 GEN
Solar/Wind Harmer
9.676
241955AC1-078 GEN
Solar/Wind Helper
1.22
270160DARBY CT5
50/50
3.427
270161DARBY CT6
50/50
3.38
253317AC1-085 GEN4
Solar/Wind Harmer
10.771
253394AE2-221_GEN
Solar/Wind Harmer
5.806
253398AE2-221_GEN2
Solar/Wind Harmer
5.806
25183208HLCRTG
Solar/Wind Harmer
4.659
252509AD1-136 GEN
Solar/Wind Harmer
0.161
972043AH1-570 GEN
Solar/Wind Harmer
1.525
972045AH1-571 GEN
Solar/Wind Harmer
1.22
339221AD2-048_GEN
Solar/Wind Harmer
0.93
971125AH1-004 GEN
Solar/Wind Harmer
2.38
970107AG2-081 GEN
Solar/Wind Harmer
1.785
960161AF2-307 GEN
Solar/Wind Harmer
3.648
252519AF1-045_GEN
Solar/Wind Harmer
3.365
252516AE2-318_GEN
Solar/Wind Harmer
2.567
942891AE2-308 GEN
Solar/Wind Harmer
5.308
270186AC1-089 GEN
Solar/Wind Harmer
2.893
946101AF1-275 GEN
Solar/Wind Helper
0.475
270518AE2-148 GEN
Solar/Wind Helper
7.445
LAGNLTFEXP_LAGN->PJM
CLTF
2.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.864
TVALTFEXP_TVA->PJM
CLTF
1.402
NYPJM->LTFIMP_NY
CLTF
0.462
LGEELTFEXP_LGEE->PJM
CLTF
1.977
WECLTFEXP_WEC->PJM
CLTF
0.246
CPLELTFEXP_CPLE->PJM
CLTF
0.434
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.263
MECLTFEXP_MEC->PJM
CLTF
1.495
SIGELTFEXP_SIGE->PJM
CLTF
0.106

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#18134_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#18134_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.34 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1267.27
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
61.918
270157DARBY CT2
50/50
61.767
270158DARBY CT3
50/50
60.78
270340AC2-060 GEN
Solar/Wind Harmer
0.008
972163AH1-664 GEN
Solar/Wind Harmer
6.148
972165AH1-665 GEN
Solar/Wind Harmer
4.924
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
6.571
945631AF1-228 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.411
25196308WSDLE2
Adder
4.373
25196208WSDLE1
Adder
4.362
25196708WSDLE6
Adder
4.351
25196508WSDLE4
Adder
4.241
253372AE2-315 SEC3
Adder
0.946
253372AE2-315 SEC3
Adder
0.946
270367AC2-061_GEN
Solar/Wind Harmer
0.003
25306009OHH W.
Adder
1.314
25196108MFTGT2
Adder
0.665
25196108MFTGT2
Adder
0.618
270520AE2-214 GEN
Solar/Wind Helper
4.716
270054AF2-122 C O1
Solar/Wind Helper
0.646
270160DARBY CT5
50/50
3.319
270161DARBY CT6
50/50
3.273
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
25183208HLCRTG
Solar/Wind Harmer
0.009
252509AD1-136 GEN
Solar/Wind Harmer
0.024
252519AF1-045_GEN
Solar/Wind Harmer
3.9
252516AE2-318_GEN
Solar/Wind Harmer
3.459
972043AH1-570 GEN
Solar/Wind Harmer
1.117
972045AH1-571 GEN
Solar/Wind Harmer
0.895
339221AD2-048_GEN
Solar/Wind Harmer
0.003
971125AH1-004 GEN
Solar/Wind Harmer
1.674
970107AG2-081 GEN
Solar/Wind Harmer
1.255
960161AF2-307 GEN
Solar/Wind Harmer
2.599
270518AE2-148 GEN
Solar/Wind Harmer
0.325
942891AE2-308 GEN
Solar/Wind Harmer
3.743
270186AC1-089 GEN
Solar/Wind Harmer
0.002
25194408D.CRK1
Adder
3.813
25194508D.CRK3
Adder
0.713
253370AE2-315 SEC1
Adder
1.001
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
4.448
25322209TAIT E
Adder
4.348
25326109MON D
Adder
0.59
970235AG2-159 GEN
Solar/Wind Harmer
1.854
970235AG2-159 GEN
Solar/Wind Harmer
1.064
946101AF1-275 GEN
Solar/Wind Helper
0.591
270159DARBY CT4
50/50
60.932
253343AC1-166 GEN
Solar/Wind Harmer
0.015
253325AC1-069 GEN
Solar/Wind Harmer
0.055
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.084
945681AF1-233 GEN
Solar/Wind Harmer
10.627
25196808ZIMRHP
Adder
51.62
252507AC2-088 GEN
Solar/Wind Harmer
0.215
339216AC1-074 GEN
Solar/Wind Harmer
0.119
3429421JKCT 10G
Adder
4.887
3429241JKCT 3G
Adder
6.657
25194608D.CRK4
Adder
0.829
253370AE2-315 SEC1
Adder
1.001
253371AE2-315 SEC2
Adder
0.946
25326309TAIT D
Adder
0.499
960071AF2-298 GEN
Solar/Wind Harmer
1.512
25196008MFTGT1
Adder
0.603
253338AC1-165 GEN
Solar/Wind Harmer
0.015
253333AC1-068 GEN
Solar/Wind Harmer
0.055
253415AE1-040 GEN
Solar/Wind Harmer
0.004
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.21
958171AF2-111 GEN
Solar/Wind Harmer
15.617
253406AD2-031_GEN
Solar/Wind Harmer
0.423
972167AH1-666 GEN
Solar/Wind Harmer
4.534
3429391JKCT 9G
Adder
4.887
252510AF1-249 C
Solar/Wind Harmer
0.027
970093AG2-073 GEN
Solar/Wind Harmer
3.524
25194608D.CRK4
Adder
0.829
25196608WSDLE5
Adder
4.285
253370AE2-315 SEC1
Adder
1.001
253371AE2-315 SEC2
Adder
0.946
966571AG1-526 GEN
Solar/Wind Harmer
6.967
25196008MFTGT1
Adder
0.584
241955AC1-078 GEN
Solar/Wind Helper
1.361
960801AF2-371 GEN
Solar/Wind Helper
0.582
964871AG1-351 GEN
Solar/Wind Helper
0.402
LAGNLTFEXP_LAGN->PJM
CLTF
2.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.77
TVALTFEXP_TVA->PJM
CLTF
1.559
NYPJM->LTFIMP_NY
CLTF
0.585
LGEELTFEXP_LGEE->PJM
CLTF
2.268
WECLTFEXP_WEC->PJM
CLTF
0.361
CPLELTFEXP_CPLE->PJM
CLTF
0.362
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.454
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.846
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.033
MECLTFEXP_MEC->PJM
CLTF
1.977
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#18134_SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#18134_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.03 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1251.48
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
3.319
270161DARBY CT6
50/50
3.274
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
25183208HLCRTG
Solar/Wind Harmer
0.009
252509AD1-136 GEN
Solar/Wind Harmer
0.024
252519AF1-045_GEN
Solar/Wind Harmer
3.905
252516AE2-318_GEN
Solar/Wind Harmer
3.464
972043AH1-570 GEN
Solar/Wind Harmer
1.119
972045AH1-571 GEN
Solar/Wind Harmer
0.896
339221AD2-048_GEN
Solar/Wind Harmer
0.003
971125AH1-004 GEN
Solar/Wind Harmer
1.676
970107AG2-081 GEN
Solar/Wind Harmer
1.257
960161AF2-307 GEN
Solar/Wind Harmer
2.603
270518AE2-148 GEN
Solar/Wind Harmer
0.325
942891AE2-308 GEN
Solar/Wind Harmer
3.75
270186AC1-089 GEN
Solar/Wind Harmer
0.002
25194408D.CRK1
Adder
3.82
25194508D.CRK3
Adder
0.714
253370AE2-315 SEC1
Adder
1.003
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
4.457
25322209TAIT E
Adder
4.357
25326109MON D
Adder
0.591
970235AG2-159 GEN
Solar/Wind Harmer
1.858
970235AG2-159 GEN
Solar/Wind Harmer
1.066
946101AF1-275 GEN
Solar/Wind Helper
0.59
270159DARBY CT4
50/50
60.941
253343AC1-166 GEN
Solar/Wind Harmer
0.015
253325AC1-069 GEN
Solar/Wind Harmer
0.055
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.091
945681AF1-233 GEN
Solar/Wind Harmer
10.639
25196808ZIMRHP
Adder
51.691
252507AC2-088 GEN
Solar/Wind Harmer
0.215
339216AC1-074 GEN
Solar/Wind Harmer
0.12
3429421JKCT 10G
Adder
4.895
3429241JKCT 3G
Adder
6.668
25194608D.CRK4
Adder
0.83
253370AE2-315 SEC1
Adder
1.003
253371AE2-315 SEC2
Adder
0.948
25326309TAIT D
Adder
0.5
960071AF2-298 GEN
Solar/Wind Harmer
1.515
25196008MFTGT1
Adder
0.605
253338AC1-165 GEN
Solar/Wind Harmer
0.015
253333AC1-068 GEN
Solar/Wind Harmer
0.055
253415AE1-040 GEN
Solar/Wind Harmer
0.004
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.218
958171AF2-111 GEN
Solar/Wind Harmer
15.634
253406AD2-031_GEN
Solar/Wind Harmer
0.424
972167AH1-666 GEN
Solar/Wind Harmer
4.539
3429391JKCT 9G
Adder
4.895
252510AF1-249 C
Solar/Wind Harmer
0.028
970093AG2-073 GEN
Solar/Wind Harmer
3.531
25194608D.CRK4
Adder
0.83
25196608WSDLE5
Adder
4.293
253370AE2-315 SEC1
Adder
1.003
253371AE2-315 SEC2
Adder
0.948
966571AG1-526 GEN
Solar/Wind Harmer
6.981
25196008MFTGT1
Adder
0.586
241955AC1-078 GEN
Solar/Wind Helper
1.359
960801AF2-371 GEN
Solar/Wind Helper
0.581
964871AG1-351 GEN
Solar/Wind Helper
0.401
270156DARBY CT1
50/50
61.927
270157DARBY CT2
50/50
61.775
270158DARBY CT3
50/50
60.789
270340AC2-060 GEN
Solar/Wind Harmer
0.008
972163AH1-664 GEN
Solar/Wind Harmer
6.155
972165AH1-665 GEN
Solar/Wind Harmer
4.93
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
6.582
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.419
25196308WSDLE2
Adder
4.381
25196208WSDLE1
Adder
4.37
25196708WSDLE6
Adder
4.359
25196508WSDLE4
Adder
4.249
253372AE2-315 SEC3
Adder
0.948
253372AE2-315 SEC3
Adder
0.948
270367AC2-061_GEN
Solar/Wind Harmer
0.003
25306009OHH W.
Adder
1.317
25196108MFTGT2
Adder
0.666
25196108MFTGT2
Adder
0.619
945631AF1-228 GEN
Solar/Wind Helper
2.3
270520AE2-214 GEN
Solar/Wind Helper
4.711
270054AF2-122 C O1
Solar/Wind Helper
0.645
LAGNLTFEXP_LAGN->PJM
CLTF
2.861
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.799
TVALTFEXP_TVA->PJM
CLTF
1.568
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
2.275
WECLTFEXP_WEC->PJM
CLTF
0.364
CPLELTFEXP_CPLE->PJM
CLTF
0.372
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.58
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.069
MECLTFEXP_MEC->PJM
CLTF
1.993
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o GREENE_345KV_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
GREENE_345KV_E_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1247.23
MW Contribution:1.48
Bus #Bus NameTypeMW Contribution
270159DARBY CT4
50/50
63.071
253343AC1-166 GEN
Solar/Wind Harmer
5.634
253325AC1-069 GEN
Solar/Wind Harmer
5.434
253432AC1-085 GEN2
Solar/Wind Harmer
0.339
946171AF1-282 GEN
Solar/Wind Harmer
12.65
945681AF1-233 GEN
Solar/Wind Harmer
15.207
339216AC1-074 GEN
Solar/Wind Harmer
1.004
252507AC2-088 GEN
Solar/Wind Harmer
1.067
25196808ZIMRHP
Adder
45.018
943111AE2-339 GEN
Solar/Wind Harmer
0.51
3429421JKCT 10G
Adder
4.735
3429241JKCT 3G
Adder
6.424
270160DARBY CT5
50/50
3.436
270161DARBY CT6
50/50
3.388
253317AC1-085 GEN4
Solar/Wind Harmer
10.596
253394AE2-221_GEN
Solar/Wind Harmer
5.714
253398AE2-221_GEN2
Solar/Wind Harmer
5.714
25183208HLCRTG
Solar/Wind Harmer
4.412
252509AD1-136 GEN
Solar/Wind Harmer
0.152
972043AH1-570 GEN
Solar/Wind Harmer
1.478
972045AH1-571 GEN
Solar/Wind Harmer
1.183
339221AD2-048_GEN
Solar/Wind Harmer
0.9
971125AH1-004 GEN
Solar/Wind Harmer
2.307
970107AG2-081 GEN
Solar/Wind Harmer
1.73
960161AF2-307 GEN
Solar/Wind Harmer
3.544
942891AE2-308 GEN
Solar/Wind Harmer
5.142
252519AF1-045_GEN
Solar/Wind Harmer
3.105
252516AE2-318_GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
2.837
946101AF1-275 GEN
Solar/Wind Helper
0.463
270518AE2-148 GEN
Solar/Wind Helper
6.817
253338AC1-165 GEN
Solar/Wind Harmer
5.634
253333AC1-068 GEN
Solar/Wind Harmer
5.434
253415AE1-040 GEN
Solar/Wind Harmer
1.566
253316AC1-085 GEN3
Solar/Wind Harmer
10.596
253433AC1-085 GEN1
Solar/Wind Harmer
6.726
946181AF1-283 GEN
Solar/Wind Harmer
16.445
253406AD2-031_GEN
Solar/Wind Harmer
1.329
958171AF2-111 GEN
Solar/Wind Harmer
22.553
972167AH1-666 GEN
Solar/Wind Harmer
6.49
3429391JKCT 9G
Adder
4.735
970093AG2-073 GEN
Solar/Wind Harmer
4.819
241955AC1-078 GEN
Solar/Wind Helper
1.164
270156DARBY CT1
50/50
64.093
270157DARBY CT2
50/50
63.935
270158DARBY CT3
50/50
62.914
270340AC2-060 GEN
Solar/Wind Harmer
3.229
972163AH1-664 GEN
Solar/Wind Harmer
7.886
972165AH1-665 GEN
Solar/Wind Harmer
6.309
339243AC2-075 GEN1
Solar/Wind Harmer
0.272
3429211JKCT 2G
Adder
6.341
945631AF1-228 GEN
Solar/Wind Helper
1.451
270520AE2-214 GEN
Solar/Wind Helper
3.694
LAGNLTFEXP_LAGN->PJM
CLTF
2.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.76
TVALTFEXP_TVA->PJM
CLTF
1.332
NYPJM->LTFIMP_NY
CLTF
0.447
LGEELTFEXP_LGEE->PJM
CLTF
1.871
WECLTFEXP_WEC->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.944
MECLTFEXP_MEC->PJM
CLTF
1.412
SIGELTFEXP_SIGE->PJM
CLTF
0.1

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o 34524 34598_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
34524 34598_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.91 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1238.04
MW Contribution:1.4
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
63.721
270157DARBY CT2
50/50
63.564
270158DARBY CT3
50/50
62.549
270340AC2-060 GEN
Solar/Wind Harmer
2.779
972163AH1-664 GEN
Solar/Wind Harmer
7.267
972165AH1-665 GEN
Solar/Wind Harmer
5.813
339243AC2-075 GEN1
Solar/Wind Harmer
0.259
3429211JKCT 2G
Adder
5.99
252524AE2-267 GEN
Solar/Wind Harmer
0.683
25196408WSDLE3
Adder
3.821
25196308WSDLE2
Adder
3.788
25196208WSDLE1
Adder
3.778
25196708WSDLE6
Adder
3.769
25196508WSDLE4
Adder
3.674
945631AF1-228 GEN
Solar/Wind Helper
1.477
270520AE2-214 GEN
Solar/Wind Helper
3.774
253338AC1-165 GEN
Solar/Wind Harmer
5.535
253333AC1-068 GEN
Solar/Wind Harmer
5.338
253415AE1-040 GEN
Solar/Wind Harmer
1.378
958171AF2-111 GEN
Solar/Wind Harmer
20.66
270160DARBY CT5
50/50
3.416
270161DARBY CT6
50/50
3.369
253317AC1-085 GEN4
Solar/Wind Harmer
6.675
25183208HLCRTG
Solar/Wind Harmer
4.509
252509AD1-136 GEN
Solar/Wind Harmer
0.157
253394AE2-221_GEN
Solar/Wind Harmer
2.684
253398AE2-221_GEN2
Solar/Wind Harmer
2.684
252519AF1-045_GEN
Solar/Wind Harmer
3.493
252516AE2-318_GEN
Solar/Wind Harmer
2.665
972043AH1-570 GEN
Solar/Wind Harmer
1.397
972045AH1-571 GEN
Solar/Wind Harmer
1.118
339221AD2-048_GEN
Solar/Wind Harmer
0.855
971125AH1-004 GEN
Solar/Wind Harmer
2.185
970107AG2-081 GEN
Solar/Wind Harmer
1.638
960161AF2-307 GEN
Solar/Wind Harmer
3.313
942891AE2-308 GEN
Solar/Wind Harmer
4.881
25194408D.CRK1
Adder
3.296
25194508D.CRK3
Adder
0.616
946101AF1-275 GEN
Solar/Wind Helper
0.473
270518AE2-148 GEN
Solar/Wind Helper
6.888
270159DARBY CT4
50/50
62.706
253343AC1-166 GEN
Solar/Wind Harmer
5.535
253325AC1-069 GEN
Solar/Wind Harmer
5.338
253432AC1-085 GEN2
Solar/Wind Harmer
0.213
946171AF1-282 GEN
Solar/Wind Harmer
7.969
945681AF1-233 GEN
Solar/Wind Harmer
13.997
25196808ZIMRHP
Adder
46.443
252507AC2-088 GEN
Solar/Wind Harmer
1.097
339216AC1-074 GEN
Solar/Wind Harmer
0.955
943111AE2-339 GEN
Solar/Wind Harmer
0.481
3429421JKCT 10G
Adder
4.461
3429241JKCT 3G
Adder
6.069
25194608D.CRK4
Adder
0.717
253316AC1-085 GEN3
Solar/Wind Harmer
6.675
253433AC1-085 GEN1
Solar/Wind Harmer
4.237
946181AF1-283 GEN
Solar/Wind Harmer
10.359
972167AH1-666 GEN
Solar/Wind Harmer
5.973
253406AD2-031_GEN
Solar/Wind Harmer
0.704
3429391JKCT 9G
Adder
4.461
970093AG2-073 GEN
Solar/Wind Harmer
4.59
252510AF1-249 C
Solar/Wind Harmer
0.184
25194608D.CRK4
Adder
0.717
25196608WSDLE5
Adder
3.712
241955AC1-078 GEN
Solar/Wind Helper
1.195
LAGNLTFEXP_LAGN->PJM
CLTF
2.486
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.749
TVALTFEXP_TVA->PJM
CLTF
1.381
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
1.98
WECLTFEXP_WEC->PJM
CLTF
0.278
CPLELTFEXP_CPLE->PJM
CLTF
0.395
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.202
MECLTFEXP_MEC->PJM
CLTF
1.604
SIGELTFEXP_SIGE->PJM
CLTF
0.109

Details for 05ADKINS-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ADKINS-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.19 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1217.34
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
270159DARBY CT4
50/50
62.85
253343AC1-166 GEN
Solar/Wind Harmer
5.559
253325AC1-069 GEN
Solar/Wind Harmer
5.361
253432AC1-085 GEN2
Solar/Wind Harmer
0.224
946171AF1-282 GEN
Solar/Wind Harmer
8.351
945681AF1-233 GEN
Solar/Wind Harmer
13.618
25196808ZIMRHP
Adder
42.456
270160DARBY CT5
50/50
3.423
270161DARBY CT6
50/50
3.377
253317AC1-085 GEN4
Solar/Wind Harmer
6.995
25183208HLCRTG
Solar/Wind Harmer
4.102
253394AE2-221_GEN
Solar/Wind Harmer
3.001
253398AE2-221_GEN2
Solar/Wind Harmer
3.001
252509AD1-136 GEN
Solar/Wind Harmer
0.143
972043AH1-570 GEN
Solar/Wind Harmer
1.349
972045AH1-571 GEN
Solar/Wind Harmer
1.079
339221AD2-048_GEN
Solar/Wind Harmer
0.823
971125AH1-004 GEN
Solar/Wind Harmer
2.109
970107AG2-081 GEN
Solar/Wind Harmer
1.582
960161AF2-307 GEN
Solar/Wind Harmer
3.217
252519AF1-045_GEN
Solar/Wind Harmer
3.028
252516AE2-318_GEN
Solar/Wind Harmer
2.31
942891AE2-308 GEN
Solar/Wind Harmer
4.719
946101AF1-275 GEN
Solar/Wind Helper
0.466
270518AE2-148 GEN
Solar/Wind Helper
5.937
253338AC1-165 GEN
Solar/Wind Harmer
5.559
253333AC1-068 GEN
Solar/Wind Harmer
5.361
253415AE1-040 GEN
Solar/Wind Harmer
1.417
253316AC1-085 GEN3
Solar/Wind Harmer
6.995
253433AC1-085 GEN1
Solar/Wind Harmer
4.441
946181AF1-283 GEN
Solar/Wind Harmer
10.857
958171AF2-111 GEN
Solar/Wind Harmer
20.127
972167AH1-666 GEN
Solar/Wind Harmer
5.811
253406AD2-031_GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
4.32
970093AG2-073 GEN
Solar/Wind Harmer
4.437
241955AC1-078 GEN
Solar/Wind Helper
1.137
270156DARBY CT1
50/50
63.867
270157DARBY CT2
50/50
63.711
270158DARBY CT3
50/50
62.693
270340AC2-060 GEN
Solar/Wind Harmer
2.864
972163AH1-664 GEN
Solar/Wind Harmer
7.068
972165AH1-665 GEN
Solar/Wind Harmer
5.654
339243AC2-075 GEN1
Solar/Wind Harmer
0.249
3429211JKCT 2G
Adder
5.799
270520AE2-214 GEN
Solar/Wind Helper
3.723
945631AF1-228 GEN
Solar/Wind Helper
1.387
252507AC2-088 GEN
Solar/Wind Harmer
1.002
339216AC1-074 GEN
Solar/Wind Harmer
0.918
943111AE2-339 GEN
Solar/Wind Harmer
0.465
3429421JKCT 10G
Adder
4.32
3429241JKCT 3G
Adder
5.875
LAGNLTFEXP_LAGN->PJM
CLTF
2.509
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.734
TVALTFEXP_TVA->PJM
CLTF
1.372
NYPJM->LTFIMP_NY
CLTF
0.495
LGEELTFEXP_LGEE->PJM
CLTF
1.865
WECLTFEXP_WEC->PJM
CLTF
0.337
CPLELTFEXP_CPLE->PJM
CLTF
0.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.433
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.088
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.06
MECLTFEXP_MEC->PJM
CLTF
1.776
SIGELTFEXP_SIGE->PJM
CLTF
0.105

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#3195_05BEATTY 345_304E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3195_05BEATTY 345_304E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1339.59
MW Contribution:1.51
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
1.706
270161DARBY CT6
50/50
1.683
25326109MON D
50/50
1.396
253370AE2-315 SEC1
50/50
2.118
270518AE2-148 GEN
Solar/Wind Harmer
33.1
253394AE2-221_GEN
Solar/Wind Harmer
5.184
253398AE2-221_GEN2
Solar/Wind Harmer
5.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.138
25322209TAIT E
Adder
9.353
25322209TAIT E
Adder
9.143
25183208HLCRTG
Solar/Wind Harmer
5.257
252519AF1-045_GEN
Solar/Wind Harmer
4.762
252516AE2-318_GEN
Solar/Wind Harmer
3.633
252509AD1-136 GEN
Solar/Wind Harmer
0.191
25194408D.CRK1
Adder
5.397
25194508D.CRK3
Adder
1.009
962581AG1-107 GEN
Solar/Wind Harmer
3.437
961491AF2-440 GEN
Solar/Wind Harmer
1.428
270186AC1-089 GEN
Solar/Wind Harmer
3.991
339221AD2-048_GEN
Solar/Wind Harmer
0.937
972043AH1-570 GEN
Solar/Wind Harmer
1.515
972045AH1-571 GEN
Solar/Wind Harmer
1.212
971125AH1-004 GEN
Solar/Wind Harmer
2.34
970107AG2-081 GEN
Solar/Wind Harmer
1.755
960161AF2-307 GEN
Solar/Wind Harmer
3.487
942891AE2-308 GEN
Solar/Wind Harmer
5.27
970235AG2-159 GEN
Solar/Wind Harmer
2.007
970235AG2-159 GEN
Solar/Wind Harmer
1.225
970077AG2-063 GEN
Solar/Wind Harmer
2.607
24728805RICHG1
Adder
1.761
24728905RICHG2
Adder
1.761
25326509SID D
Adder
0.568
946101AF1-275 GEN
Solar/Wind Helper
2.104
270471AD2-092_GEN
Solar/Wind Helper
0.832
270159DARBY CT4
50/50
31.323
253370AE2-315 SEC1
50/50
2.118
253371AE2-315 SEC2
50/50
2.003
25322209TAIT E
50/50
0.488
25322309TAIT W
50/50
0.487
253343AC1-166 GEN
Solar/Wind Harmer
2.95
253325AC1-069 GEN
Solar/Wind Harmer
2.845
253432AC1-085 GEN2
Solar/Wind Harmer
0.292
946171AF1-282 GEN
Solar/Wind Harmer
10.909
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.497
25196808ZIMRHP
Adder
56.989
252507AC2-088 GEN
Solar/Wind Harmer
1.339
945681AF1-233 GEN
Solar/Wind Harmer
14.039
25194608D.CRK4
Adder
1.173
339216AC1-074 GEN
Solar/Wind Harmer
1.035
25196008MFTGT1
Adder
0.812
943111AE2-339 GEN
Solar/Wind Harmer
0.512
3429421JKCT 10G
Adder
4.71
3429241JKCT 3G
Adder
6.464
970593AG2-378 GEN
Solar/Wind Harmer
0.966
270349AD2-093_GEN
Solar/Wind Helper
0.832
270156DARBY CT1
50/50
31.83
270157DARBY CT2
50/50
31.752
270158DARBY CT3
50/50
31.245
253372AE2-315 SEC3
50/50
2.003
253372AE2-315 SEC3
50/50
2.003
25322309TAIT W
50/50
0.493
945631AF1-228 GEN
Solar/Wind Harmer
15.366
270340AC2-060 GEN
Solar/Wind Harmer
2.773
25306009OHH W.
Adder
2.634
241972AD1-140 GEN
Solar/Wind Harmer
3.809
253349AC2-067 GEN
Solar/Wind Harmer
4.166
253400AC2-068 GEN
Solar/Wind Harmer
1.675
972163AH1-664 GEN
Solar/Wind Harmer
7.327
972165AH1-665 GEN
Solar/Wind Harmer
5.862
252524AE2-267 GEN
Solar/Wind Harmer
1.136
25196408WSDLE3
Adder
6.354
25196308WSDLE2
Adder
6.299
25196208WSDLE1
Adder
6.283
25196708WSDLE6
Adder
6.267
25196508WSDLE4
Adder
6.109
270367AC2-061_GEN
Solar/Wind Harmer
2.081
339243AC2-075 GEN1
Solar/Wind Harmer
0.28
25196108MFTGT2
Adder
0.896
25196108MFTGT2
Adder
0.832
944031AF1-071 GEN
Solar/Wind Harmer
0.556
3429211JKCT 2G
Adder
6.38
339211AE2-254 GEN
Solar/Wind Harmer
0.653
270520AE2-214 GEN
Solar/Wind Helper
16.8
270284AF1-227 GEN1
Solar/Wind Helper
1.077
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
253370AE2-315 SEC1
50/50
2.118
253371AE2-315 SEC2
50/50
2.003
25322209TAIT E
50/50
0.481
253338AC1-165 GEN
Solar/Wind Harmer
2.95
253333AC1-068 GEN
Solar/Wind Harmer
2.845
253316AC1-085 GEN3
Solar/Wind Harmer
9.138
253433AC1-085 GEN1
Solar/Wind Harmer
5.801
946181AF1-283 GEN
Solar/Wind Harmer
14.182
253415AE1-040 GEN
Solar/Wind Harmer
1.229
253406AD2-031_GEN
Solar/Wind Harmer
1.329
253303V4-073 C
Solar/Wind Harmer
0.115
958171AF2-111 GEN
Solar/Wind Harmer
20.161
972167AH1-666 GEN
Solar/Wind Harmer
5.985
241955AC1-078 GEN
Solar/Wind Harmer
5.548
25196608WSDLE5
Adder
6.172
252510AF1-249 C
Solar/Wind Harmer
0.299
25194608D.CRK4
Adder
1.173
25196008MFTGT1
Adder
0.787
3429391JKCT 9G
Adder
4.71
270222AC2-111 GEN
Solar/Wind Harmer
4.514
970093AG2-073 GEN
Solar/Wind Harmer
5
970605AG2-385 GEN
Solar/Wind Harmer
2.607
942051AE2-217 GEN
Solar/Wind Harmer
8.29
966571AG1-526 GEN
Solar/Wind Harmer
10.155
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.954
TVALTFEXP_TVA->PJM
CLTF
1.778
NYPJM->LTFIMP_NY
CLTF
0.709
LGEELTFEXP_LGEE->PJM
CLTF
2.67
WECLTFEXP_WEC->PJM
CLTF
0.422
CPLELTFEXP_CPLE->PJM
CLTF
0.384
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.528
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.847
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.106
MECLTFEXP_MEC->PJM
CLTF
2.33
SIGELTFEXP_SIGE->PJM
CLTF
0.154

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1203.74
MW Contribution:1.4
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.445
253338AC1-165 GEN
Solar/Wind Harmer
2.687
253333AC1-068 GEN
Solar/Wind Harmer
2.592
241955AC1-078 GEN
Solar/Wind Harmer
8.592
253415AE1-040 GEN
Solar/Wind Harmer
1.168
253316AC1-085 GEN3
Solar/Wind Harmer
8.408
253433AC1-085 GEN1
Solar/Wind Harmer
5.337
946181AF1-283 GEN
Solar/Wind Harmer
13.049
253406AD2-031_GEN
Solar/Wind Harmer
1.233
253303V4-073 C
Solar/Wind Harmer
0.107
958171AF2-111 GEN
Solar/Wind Harmer
18.592
972167AH1-666 GEN
Solar/Wind Harmer
5.527
270160DARBY CT5
50/50
1.55
270161DARBY CT6
50/50
1.529
25326109MON D
50/50
1.292
253370AE2-315 SEC1
50/50
1.955
270518AE2-148 GEN
Solar/Wind Harmer
30.115
253394AE2-221_GEN
Solar/Wind Harmer
4.767
253398AE2-221_GEN2
Solar/Wind Harmer
4.767
253317AC1-085 GEN4
Solar/Wind Harmer
8.408
25322209TAIT E
Adder
8.638
25322209TAIT E
Adder
8.444
25183208HLCRTG
Solar/Wind Harmer
4.848
252519AF1-045_GEN
Solar/Wind Harmer
4.396
252516AE2-318_GEN
Solar/Wind Harmer
3.353
252509AD1-136 GEN
Solar/Wind Harmer
0.177
25194408D.CRK1
Adder
4.981
25194508D.CRK3
Adder
0.931
962581AG1-107 GEN
Solar/Wind Harmer
3.226
961491AF2-440 GEN
Solar/Wind Harmer
1.341
270186AC1-089 GEN
Solar/Wind Harmer
3.745
339221AD2-048_GEN
Solar/Wind Harmer
0.866
970077AG2-063 GEN
Solar/Wind Harmer
3.037
972043AH1-570 GEN
Solar/Wind Harmer
1.4
972045AH1-571 GEN
Solar/Wind Harmer
1.12
971125AH1-004 GEN
Solar/Wind Harmer
2.161
970107AG2-081 GEN
Solar/Wind Harmer
1.621
960161AF2-307 GEN
Solar/Wind Harmer
3.228
942891AE2-308 GEN
Solar/Wind Harmer
4.87
970235AG2-159 GEN
Solar/Wind Harmer
1.855
970235AG2-159 GEN
Solar/Wind Harmer
1.133
946101AF1-275 GEN
Solar/Wind Helper
2.225
270471AD2-092_GEN
Solar/Wind Helper
0.83
270156DARBY CT1
50/50
28.923
270157DARBY CT2
50/50
28.852
270158DARBY CT3
50/50
28.391
253372AE2-315 SEC3
50/50
1.849
253372AE2-315 SEC3
50/50
1.849
25322309TAIT W
50/50
0.455
945631AF1-228 GEN
Solar/Wind Harmer
13.963
270340AC2-060 GEN
Solar/Wind Harmer
2.678
25306009OHH W.
Adder
2.431
241972AD1-140 GEN
Solar/Wind Harmer
3.722
253349AC2-067 GEN
Solar/Wind Harmer
3.843
253400AC2-068 GEN
Solar/Wind Harmer
1.545
972163AH1-664 GEN
Solar/Wind Harmer
6.768
972165AH1-665 GEN
Solar/Wind Harmer
5.414
252524AE2-267 GEN
Solar/Wind Harmer
1.048
25196408WSDLE3
Adder
5.862
25196308WSDLE2
Adder
5.811
25196208WSDLE1
Adder
5.796
25196708WSDLE6
Adder
5.782
25196508WSDLE4
Adder
5.636
270367AC2-061_GEN
Solar/Wind Harmer
1.956
270432AC2-029 GEN
Solar/Wind Harmer
4.062
339243AC2-075 GEN1
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
0.827
25196108MFTGT2
Adder
0.768
944031AF1-071 GEN
Solar/Wind Harmer
0.512
3429211JKCT 2G
Adder
5.894
270269AC2-059
Solar/Wind Harmer
4.061
270520AE2-214 GEN
Solar/Wind Helper
17.761
270284AF1-227 GEN1
Solar/Wind Helper
1.078
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
25196608WSDLE5
Adder
5.694
252510AF1-249 C
Solar/Wind Harmer
0.276
25194608D.CRK4
Adder
1.083
942051AE2-217 GEN
Solar/Wind Harmer
11.594
960801AF2-371 GEN
Solar/Wind Harmer
1.573
964871AG1-351 GEN
Solar/Wind Harmer
1.086
970605AG2-385 GEN
Solar/Wind Harmer
3.037
25196008MFTGT1
Adder
0.726
3429391JKCT 9G
Adder
4.349
270222AC2-111 GEN
Solar/Wind Harmer
4.153
970093AG2-073 GEN
Solar/Wind Harmer
4.621
270273AD2-016 GEN
Solar/Wind Harmer
1.161
270159DARBY CT4
50/50
28.462
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.45
25322309TAIT W
50/50
0.45
253343AC1-166 GEN
Solar/Wind Harmer
2.687
253325AC1-069 GEN
Solar/Wind Harmer
2.592
253432AC1-085 GEN2
Solar/Wind Harmer
0.269
946171AF1-282 GEN
Solar/Wind Harmer
10.038
25326309TAIT D
Adder
0.97
960071AF2-298 GEN
Solar/Wind Harmer
4.15
25196808ZIMRHP
Adder
52.581
252507AC2-088 GEN
Solar/Wind Harmer
1.237
945681AF1-233 GEN
Solar/Wind Harmer
12.965
25194608D.CRK4
Adder
1.083
339216AC1-074 GEN
Solar/Wind Harmer
0.956
970593AG2-378 GEN
Solar/Wind Harmer
1.125
25196008MFTGT1
Adder
0.75
943111AE2-339 GEN
Solar/Wind Harmer
0.473
3429421JKCT 10G
Adder
4.349
3429241JKCT 3G
Adder
5.971
270349AD2-093_GEN
Solar/Wind Helper
0.83
LAGNLTFEXP_LAGN->PJM
CLTF
3.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.868
TVALTFEXP_TVA->PJM
CLTF
1.647
NYPJM->LTFIMP_NY
CLTF
0.65
LGEELTFEXP_LGEE->PJM
CLTF
2.466
WECLTFEXP_WEC->PJM
CLTF
0.372
CPLELTFEXP_CPLE->PJM
CLTF
0.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.427
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.499
MECLTFEXP_MEC->PJM
CLTF
2.097
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1203.72
MW Contribution:1.4
Bus #Bus NameTypeMW Contribution
270160DARBY CT5
50/50
1.55
270161DARBY CT6
50/50
1.529
25326109MON D
50/50
1.291
253370AE2-315 SEC1
50/50
1.955
270518AE2-148 GEN
Solar/Wind Harmer
30.115
253394AE2-221_GEN
Solar/Wind Harmer
4.767
253398AE2-221_GEN2
Solar/Wind Harmer
4.767
253317AC1-085 GEN4
Solar/Wind Harmer
8.408
25322209TAIT E
Adder
8.638
25322209TAIT E
Adder
8.444
25183208HLCRTG
Solar/Wind Harmer
4.848
252519AF1-045_GEN
Solar/Wind Harmer
4.396
252516AE2-318_GEN
Solar/Wind Harmer
3.353
252509AD1-136 GEN
Solar/Wind Harmer
0.177
25194408D.CRK1
Adder
4.981
25194508D.CRK3
Adder
0.931
962581AG1-107 GEN
Solar/Wind Harmer
3.226
961491AF2-440 GEN
Solar/Wind Harmer
1.341
270186AC1-089 GEN
Solar/Wind Harmer
3.745
339221AD2-048_GEN
Solar/Wind Harmer
0.866
970077AG2-063 GEN
Solar/Wind Harmer
3.037
972043AH1-570 GEN
Solar/Wind Harmer
1.4
972045AH1-571 GEN
Solar/Wind Harmer
1.12
971125AH1-004 GEN
Solar/Wind Harmer
2.161
970107AG2-081 GEN
Solar/Wind Harmer
1.621
960161AF2-307 GEN
Solar/Wind Harmer
3.228
942891AE2-308 GEN
Solar/Wind Harmer
4.869
970235AG2-159 GEN
Solar/Wind Harmer
1.855
970235AG2-159 GEN
Solar/Wind Harmer
1.132
946101AF1-275 GEN
Solar/Wind Helper
2.225
270471AD2-092_GEN
Solar/Wind Helper
0.83
270156DARBY CT1
50/50
28.922
270157DARBY CT2
50/50
28.851
270158DARBY CT3
50/50
28.39
253372AE2-315 SEC3
50/50
1.849
253372AE2-315 SEC3
50/50
1.849
25322309TAIT W
50/50
0.455
945631AF1-228 GEN
Solar/Wind Harmer
13.963
270340AC2-060 GEN
Solar/Wind Harmer
2.678
25306009OHH W.
Adder
2.431
241972AD1-140 GEN
Solar/Wind Harmer
3.722
253349AC2-067 GEN
Solar/Wind Harmer
3.842
253400AC2-068 GEN
Solar/Wind Harmer
1.545
972163AH1-664 GEN
Solar/Wind Harmer
6.768
972165AH1-665 GEN
Solar/Wind Harmer
5.414
252524AE2-267 GEN
Solar/Wind Harmer
1.048
25196408WSDLE3
Adder
5.862
25196308WSDLE2
Adder
5.811
25196208WSDLE1
Adder
5.796
25196708WSDLE6
Adder
5.782
25196508WSDLE4
Adder
5.636
270367AC2-061_GEN
Solar/Wind Harmer
1.956
270432AC2-029 GEN
Solar/Wind Harmer
4.061
339243AC2-075 GEN1
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
0.827
25196108MFTGT2
Adder
0.768
944031AF1-071 GEN
Solar/Wind Harmer
0.512
3429211JKCT 2G
Adder
5.894
270269AC2-059
Solar/Wind Harmer
4.061
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.445
253338AC1-165 GEN
Solar/Wind Harmer
2.687
253333AC1-068 GEN
Solar/Wind Harmer
2.592
241955AC1-078 GEN
Solar/Wind Harmer
8.591
253415AE1-040 GEN
Solar/Wind Harmer
1.167
253316AC1-085 GEN3
Solar/Wind Harmer
8.408
253433AC1-085 GEN1
Solar/Wind Harmer
5.337
946181AF1-283 GEN
Solar/Wind Harmer
13.049
253406AD2-031_GEN
Solar/Wind Harmer
1.233
253303V4-073 C
Solar/Wind Harmer
0.107
958171AF2-111 GEN
Solar/Wind Harmer
18.591
972167AH1-666 GEN
Solar/Wind Harmer
5.527
25196608WSDLE5
Adder
5.694
252510AF1-249 C
Solar/Wind Harmer
0.276
25194608D.CRK4
Adder
1.083
942051AE2-217 GEN
Solar/Wind Harmer
11.593
960801AF2-371 GEN
Solar/Wind Harmer
1.573
964871AG1-351 GEN
Solar/Wind Harmer
1.086
970605AG2-385 GEN
Solar/Wind Harmer
3.037
25196008MFTGT1
Adder
0.726
3429391JKCT 9G
Adder
4.349
270222AC2-111 GEN
Solar/Wind Harmer
4.153
970093AG2-073 GEN
Solar/Wind Harmer
4.621
270273AD2-016 GEN
Solar/Wind Harmer
1.161
270520AE2-214 GEN
Solar/Wind Helper
17.762
270284AF1-227 GEN1
Solar/Wind Helper
1.078
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
270159DARBY CT4
50/50
28.461
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.45
25322309TAIT W
50/50
0.45
253343AC1-166 GEN
Solar/Wind Harmer
2.687
253325AC1-069 GEN
Solar/Wind Harmer
2.592
253432AC1-085 GEN2
Solar/Wind Harmer
0.269
946171AF1-282 GEN
Solar/Wind Harmer
10.038
25326309TAIT D
Adder
0.97
960071AF2-298 GEN
Solar/Wind Harmer
4.15
25196808ZIMRHP
Adder
52.579
252507AC2-088 GEN
Solar/Wind Harmer
1.237
945681AF1-233 GEN
Solar/Wind Harmer
12.964
25194608D.CRK4
Adder
1.083
339216AC1-074 GEN
Solar/Wind Harmer
0.956
970593AG2-378 GEN
Solar/Wind Harmer
1.125
25196008MFTGT1
Adder
0.75
943111AE2-339 GEN
Solar/Wind Harmer
0.473
3429421JKCT 10G
Adder
4.349
3429241JKCT 3G
Adder
5.971
270349AD2-093_GEN
Solar/Wind Helper
0.83
LAGNLTFEXP_LAGN->PJM
CLTF
3.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.868
TVALTFEXP_TVA->PJM
CLTF
1.647
NYPJM->LTFIMP_NY
CLTF
0.65
LGEELTFEXP_LGEE->PJM
CLTF
2.466
WECLTFEXP_WEC->PJM
CLTF
0.372
CPLELTFEXP_CPLE->PJM
CLTF
0.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.316
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.499
MECLTFEXP_MEC->PJM
CLTF
2.097
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.09 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1312.32
MW Contribution:1.44
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.072
253370AE2-315 SEC1
50/50
3.048
25322209TAIT E
50/50
14.544
25322209TAIT E
50/50
14.217
270518AE2-148 GEN
Solar/Wind Harmer
58.824
253394AE2-221_GEN
Solar/Wind Harmer
6.204
253398AE2-221_GEN2
Solar/Wind Harmer
6.204
253317AC1-085 GEN4
Solar/Wind Harmer
9.666
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.13
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.847
961491AF2-440 GEN
Solar/Wind Harmer
1.599
25326509SID D
Adder
0.983
270186AC1-089 GEN
Solar/Wind Harmer
4.107
253378AE2-206_GEN
Solar/Wind Harmer
2.352
276820AF1-078_GEN
Solar/Wind Harmer
1.045
24728805RICHG1
Adder
2.35
24728905RICHG2
Adder
2.35
339221AD2-048_GEN
Solar/Wind Harmer
0.897
972043AH1-570 GEN
Solar/Wind Harmer
1.438
972045AH1-571 GEN
Solar/Wind Harmer
1.15
971125AH1-004 GEN
Solar/Wind Harmer
2.22
970107AG2-081 GEN
Solar/Wind Harmer
1.665
970235AG2-159 GEN
Solar/Wind Harmer
2.18
970235AG2-159 GEN
Solar/Wind Harmer
1.331
970883AG2-550 GEN
Solar/Wind Harmer
5.173
970885AG2-551 GEN
Solar/Wind Harmer
1.203
942891AE2-308 GEN
Solar/Wind Harmer
5.018
960161AF2-307 GEN
Solar/Wind Harmer
3.198
270383AD1-128 GEN
Solar/Wind Harmer
2.932
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.854
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.714
25322209TAIT E
50/50
0.714
25326309TAIT D
50/50
1.634
960071AF2-298 GEN
Solar/Wind Harmer
6.591
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.54
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.941
253325AC1-069 GEN
Solar/Wind Harmer
0.907
270159DARBY CT4
Adder
7.309
25196808ZIMRHP
Adder
60.521
252507AC2-088 GEN
Solar/Wind Harmer
1.402
25196008MFTGT1
Adder
0.983
945681AF1-233 GEN
Solar/Wind Harmer
12.524
339216AC1-074 GEN
Solar/Wind Harmer
0.989
943111AE2-339 GEN
Solar/Wind Harmer
0.484
3429421JKCT 10G
Adder
4.419
3429241JKCT 3G
Adder
6.096
247536S-71 GEN
Solar/Wind Harmer
1.917
253372AE2-315 SEC3
50/50
2.883
253372AE2-315 SEC3
50/50
2.883
25322309TAIT W
50/50
0.723
963581AG1-207 GEN
50/50
13.107
25306009OHH W.
50/50
4.035
253349AC2-067 GEN
Solar/Wind Harmer
6.045
253400AC2-068 GEN
Solar/Wind Harmer
2.431
241972AD1-140 GEN
Solar/Wind Harmer
5.065
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.978
25196308WSDLE2
Adder
7.909
25196208WSDLE1
Adder
7.889
25196708WSDLE6
Adder
7.869
25196508WSDLE4
Adder
7.671
270156DARBY CT1
Adder
7.427
270157DARBY CT2
Adder
7.409
270158DARBY CT3
Adder
7.29
944031AF1-071 GEN
Solar/Wind Harmer
0.743
25196108MFTGT2
Adder
1.084
25196108MFTGT2
Adder
1.006
270367AC2-061_GEN
Solar/Wind Harmer
2.232
972163AH1-664 GEN
Solar/Wind Harmer
6.559
972165AH1-665 GEN
Solar/Wind Harmer
5.247
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
971673AH1-337 GEN
Solar/Wind Harmer
2.683
971029AG2-637 GEN
Solar/Wind Harmer
8.486
270543AE2-219 C
Solar/Wind Harmer
2.649
3429211JKCT 2G
Adder
6.017
270340AC2-060 GEN
Solar/Wind Harmer
1.553
945631AF1-228 GEN
Solar/Wind Helper
5.272
270520AE2-214 GEN
Solar/Wind Helper
6.82
270054AF2-122 C O1
Solar/Wind Helper
0.9
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.714
25322209TAIT E
50/50
0.706
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.506
253316AC1-085 GEN3
Solar/Wind Harmer
9.666
253433AC1-085 GEN1
Solar/Wind Harmer
6.136
946181AF1-283 GEN
Solar/Wind Harmer
15.002
25196608WSDLE5
Adder
7.75
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.941
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.028
958171AF2-111 GEN
Solar/Wind Harmer
17.743
25196008MFTGT1
Adder
0.952
972167AH1-666 GEN
Solar/Wind Harmer
5.337
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.419
970093AG2-073 GEN
Solar/Wind Harmer
4.788
270356AE2-297 GEN
Solar/Wind Harmer
2.179
966571AG1-526 GEN
Solar/Wind Harmer
9.998
960801AF2-371 GEN
Solar/Wind Helper
0.809
964871AG1-351 GEN
Solar/Wind Helper
0.558
241955AC1-078 GEN
Solar/Wind Helper
1.486
270273AD2-016 GEN
Solar/Wind Helper
1.381
LAGNLTFEXP_LAGN->PJM
CLTF
3.725
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.571
TVALTFEXP_TVA->PJM
CLTF
1.934
NYPJM->LTFIMP_NY
CLTF
0.843
LGEELTFEXP_LGEE->PJM
CLTF
2.977
WECLTFEXP_WEC->PJM
CLTF
0.663
CPLELTFEXP_CPLE->PJM
CLTF
0.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.887
MECLTFEXP_MEC->PJM
CLTF
3.237
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.36
MW Contribution:1.45
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
946101AF1-275 GEN
Solar/Wind Helper
0.84
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.33
MW Contribution:1.45
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
946101AF1-275 GEN
Solar/Wind Helper
0.84
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.32
MW Contribution:1.45
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
946101AF1-275 GEN
Solar/Wind Helper
0.84
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.27 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1278.4
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.884
253371AE2-315 SEC2
50/50
2.728
25322309TAIT W
50/50
0.68
25322209TAIT E
50/50
0.672
253303V4-073 C
Solar/Wind Harmer
0.157
253406AD2-031_GEN
Solar/Wind Harmer
1.258
253316AC1-085 GEN3
Solar/Wind Harmer
7.554
253433AC1-085 GEN1
Solar/Wind Harmer
4.795
946181AF1-283 GEN
Solar/Wind Harmer
11.724
25196608WSDLE5
Adder
7.024
25194608D.CRK4
Adder
1.313
252510AF1-249 C
Solar/Wind Harmer
0.33
270222AC2-111 GEN
Solar/Wind Harmer
5.802
25196008MFTGT1
Adder
0.866
270356AE2-297 GEN
Solar/Wind Harmer
2.238
958171AF2-111 GEN
Solar/Wind Harmer
12.086
972167AH1-666 GEN
Solar/Wind Harmer
3.72
270437AC2-090 C
Solar/Wind Harmer
2.57
962031AG1-047 GEN
Solar/Wind Harmer
1.383
957741AF2-068 GEN
Solar/Wind Harmer
6.862
946031AF1-268 GEN
Solar/Wind Harmer
3.685
960801AF2-371 GEN
Solar/Wind Helper
0.818
964871AG1-351 GEN
Solar/Wind Helper
0.565
241955AC1-078 GEN
Solar/Wind Helper
1.545
253338AC1-165 GEN
Solar/Wind Helper
0.732
253333AC1-068 GEN
Solar/Wind Helper
0.758
270273AD2-016 GEN
Solar/Wind Helper
1.443
25326109MON D
50/50
1.979
253370AE2-315 SEC1
50/50
2.884
25322209TAIT E
50/50
13.847
25322209TAIT E
50/50
13.536
270518AE2-148 GEN
Solar/Wind Harmer
59.988
253394AE2-221_GEN
Solar/Wind Harmer
5.279
253398AE2-221_GEN2
Solar/Wind Harmer
5.279
253317AC1-085 GEN4
Solar/Wind Harmer
7.554
25194408D.CRK1
Adder
6.039
25194508D.CRK3
Adder
1.129
252519AF1-045_GEN
Solar/Wind Harmer
4.592
252516AE2-318_GEN
Solar/Wind Harmer
3.503
25183208HLCRTG
Solar/Wind Harmer
4.277
25326509SID D
Adder
0.928
962581AG1-107 GEN
Solar/Wind Harmer
3.319
961491AF2-440 GEN
Solar/Wind Harmer
1.379
252509AD1-136 GEN
Solar/Wind Harmer
0.161
24728805RICHG1
Adder
2.319
24728905RICHG2
Adder
2.319
253378AE2-206_GEN
Solar/Wind Harmer
2.189
276820AF1-078_GEN
Solar/Wind Harmer
0.972
270186AC1-089 GEN
Solar/Wind Harmer
3.371
970883AG2-550 GEN
Solar/Wind Harmer
5.386
970885AG2-551 GEN
Solar/Wind Harmer
1.253
270383AD1-128 GEN
Solar/Wind Harmer
3.09
247621Y3-024
Adder
0.116
970235AG2-159 GEN
Solar/Wind Harmer
1.899
970235AG2-159 GEN
Solar/Wind Harmer
1.159
24379505HDWTR1G C
Solar/Wind Harmer
3.64
270209AC1-174_GEN
Solar/Wind Harmer
2.569
926881AC1-175 GEN
Solar/Wind Harmer
2.569
270201AC2-176 GEN
Solar/Wind Harmer
2.352
964611AG1-324 GEN
Solar/Wind Harmer
0.536
964611AG1-324 GEN
Solar/Wind Harmer
0.238
339221AD2-048_GEN
Solar/Wind Harmer
0.69
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.877
970825AG2-519 GEN
Solar/Wind Harmer
4.567
946101AF1-275 GEN
Solar/Wind Helper
0.779
270471AD2-092_GEN
Solar/Wind Helper
0.672
253372AE2-315 SEC3
50/50
2.728
253372AE2-315 SEC3
50/50
2.728
25322309TAIT W
50/50
0.688
963581AG1-207 GEN
50/50
12.502
25306009OHH W.
50/50
3.831
253349AC2-067 GEN
Solar/Wind Harmer
5.763
253400AC2-068 GEN
Solar/Wind Harmer
2.317
241972AD1-140 GEN
Solar/Wind Harmer
4.783
252524AE2-267 GEN
Solar/Wind Harmer
1.293
25196408WSDLE3
Adder
7.231
25196308WSDLE2
Adder
7.168
25196208WSDLE1
Adder
7.15
25196708WSDLE6
Adder
7.132
25196508WSDLE4
Adder
6.952
944031AF1-071 GEN
Solar/Wind Harmer
0.715
25196108MFTGT2
Adder
0.985
25196108MFTGT2
Adder
0.915
270367AC2-061_GEN
Solar/Wind Harmer
1.888
971673AH1-337 GEN
Solar/Wind Harmer
2.725
971029AG2-637 GEN
Solar/Wind Harmer
8.67
270543AE2-219 C
Solar/Wind Harmer
2.758
270240V3-007_GEN2
Solar/Wind Harmer
2.848
972163AH1-664 GEN
Solar/Wind Harmer
4.602
972165AH1-665 GEN
Solar/Wind Harmer
3.682
961761AG1-017 GEN
Solar/Wind Harmer
0.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
945631AF1-228 GEN
Solar/Wind Helper
4.964
270520AE2-214 GEN
Solar/Wind Helper
6.217
270054AF2-122 C O1
Solar/Wind Helper
0.923
253370AE2-315 SEC1
50/50
2.884
253371AE2-315 SEC2
50/50
2.728
25322309TAIT W
50/50
0.68
25322209TAIT E
50/50
0.68
25326309TAIT D
50/50
1.555
960071AF2-298 GEN
Solar/Wind Harmer
6.275
253432AC1-085 GEN2
Solar/Wind Harmer
0.241
946171AF1-282 GEN
Solar/Wind Harmer
9.018
25194608D.CRK4
Adder
1.313
25196808ZIMRHP
Adder
49.159
25196008MFTGT1
Adder
0.894
252507AC2-088 GEN
Solar/Wind Harmer
1.13
247536S-71 GEN
Solar/Wind Harmer
2.036
945681AF1-233 GEN
Solar/Wind Harmer
8.738
942081AE2-220 GEN
Solar/Wind Harmer
2.943
270239V3-007_GEN1
Solar/Wind Harmer
0.792
339216AC1-074 GEN
Solar/Wind Harmer
0.758
970825AG2-519 GEN
Solar/Wind Harmer
1.019
253343AC1-166 GEN
Solar/Wind Helper
0.732
253325AC1-069 GEN
Solar/Wind Helper
0.758
270349AD2-093_GEN
Solar/Wind Helper
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
4.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.506
TVALTFEXP_TVA->PJM
CLTF
2.012
NYPJM->LTFIMP_NY
CLTF
0.948
LGEELTFEXP_LGEE->PJM
CLTF
2.761
WECLTFEXP_WEC->PJM
CLTF
1.025
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.088
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.916
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.185

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2500.92
MW Contribution:1.29
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
Adder
4.909
24734705WLF1G3
Adder
4.898
24734805WLF1G4
Adder
4.898
24734905WLF1G5
Adder
4.898
966391AG1-508 GEN
Solar/Wind Harmer
2.785
971981AH1-535 GEN
Solar/Wind Harmer
7.897
971313AH1-133 GEN
Solar/Wind Harmer
7.717
970281AG2-184 GEN
Solar/Wind Harmer
14.619
972143AH1-644 GEN
Solar/Wind Harmer
6.961
962211AG1-066 GEN
Solar/Wind Harmer
1.642
270399AC1-101 GEN
Solar/Wind Harmer
2.775
270400AC1-102 GEN
Solar/Wind Harmer
2.775
957241AF2-018 GEN
Solar/Wind Harmer
2.86
965401AG1-405 GEN
Solar/Wind Harmer
3.385
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.854
970455AG2-298 GEN
Solar/Wind Harmer
3.268
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.233
972163AH1-664 GEN
Solar/Wind Harmer
4.977
972165AH1-665 GEN
Solar/Wind Harmer
3.982
944221AF1-090 GEN
Solar/Wind Harmer
5.331
276849AB2-070 GEN2
Solar/Wind Harmer
1.072
276848AB2-070 GEN3
Solar/Wind Harmer
1.072
276785W4-005 GEN1
Solar/Wind Harmer
1.442
276174W4-005 GEN2
Solar/Wind Harmer
1.442
946321AF1-296 GEN
Solar/Wind Harmer
4.942
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
3.031
961011AF2-392 GEN
Solar/Wind Harmer
5.096
957751AF2-069 GEN
Solar/Wind Harmer
0.215
276655WTG1_EQ
Solar/Wind Harmer
4.083
276656WTG2_EQ
Solar/Wind Harmer
0.541
959341AF2-225 GEN
Solar/Wind Harmer
7.015
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
7.003
270367AC2-061_GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.193
274823ROCKFORD ;21
Adder
9.057
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
970563AG2-360 GEN
50/50
26.913
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
9.063
960911AF2-382 GEN
Solar/Wind Harmer
5.848
971461AH1-227 GEN
Solar/Wind Harmer
3.853
972103AH1-617 GEN
Solar/Wind Harmer
13.923
270053AF1-130 C
Solar/Wind Harmer
2.393
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.326
339250AF1-203 GEN
Solar/Wind Harmer
0.353
971155AH1-034 GEN
Solar/Wind Harmer
5.827
962251AG1-071 GEN
Solar/Wind Harmer
3.186
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
2.839
966571AG1-526 GEN
Solar/Wind Harmer
12.469
970093AG2-073 GEN
Solar/Wind Harmer
5.535
270030AE2-140 GEN
Solar/Wind Harmer
10.994
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
3.962
958171AF2-111 GEN
Solar/Wind Harmer
12.227
970243AG2-164 GEN
Solar/Wind Harmer
12.56
970519AG2-331 GEN
Solar/Wind Harmer
8.438
970699AG2-449 GEN
Solar/Wind Harmer
5.582
942481AE2-261 GEN
Solar/Wind Harmer
14.457
276621W2-048 GEN
Solar/Wind Harmer
2.989
276838X2-022 GEN2
Solar/Wind Harmer
0.111
970193AG2-126 GEN
Solar/Wind Harmer
7.161
276668AB2-070 GEN1
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
1.442
971993AH1-541 GEN
Solar/Wind Harmer
4.403
965931AG1-462 GEN
Solar/Wind Harmer
12.103
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
3.387
965091AG1-374 GEN
Solar/Wind Harmer
14.098
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
1.583
276157O29GEN1
Solar/Wind Harmer
1.787
942111AE2-223 GEN
Solar/Wind Harmer
3.834
274858EASY ROAD;U2
Solar/Wind Harmer
2.241
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
274729ELWOOD EC;1P
Adder
7.487
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
24735205WLF2G2
Adder
4.909
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.747
971403AH1-188 GEN
Solar/Wind Harmer
9.188
971315AH1-136 GEN
Solar/Wind Harmer
1.275
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
1.013
962241AG1-070 GEN
Solar/Wind Harmer
2.607
964901AG1-354 GEN
Solar/Wind Harmer
8.682
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
5.664
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
1.077
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.669
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339216AC1-074 GEN
Solar/Wind Harmer
0.86
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
9.348
270445AC2-157 GEN2
Solar/Wind Harmer
2.736
970333AG2-219 GEN
Solar/Wind Harmer
15.351
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.939
963831AG1-236 GEN
Solar/Wind Harmer
4.696
274880W4-005 GEN4
Solar/Wind Harmer
1.442
972175AH1-670 GEN
Solar/Wind Harmer
6.469
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
3.316
274877BISHOP HL;1U
Solar/Wind Harmer
1.583
276158O29GEN2
Solar/Wind Harmer
2.349
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
3.699
939741AE1-205 GEN
Solar/Wind Harmer
9.353
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.314
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
3.284
971485AH1-239 GEN
Solar/Wind Harmer
4.843
339231AF1-038_GEN
Solar/Wind Harmer
1.082
339255AE2-071 GEN
Solar/Wind Harmer
0.618
964781AG1-341 GEN
Solar/Wind Harmer
6.173
339236AF1-050_GEN
Solar/Wind Harmer
1.045
971081AG2-670 GEN
Solar/Wind Harmer
4.298
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
2.668
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
3.502
942891AE2-308 GEN
Solar/Wind Harmer
5.447
964571AG1-320 GEN
Solar/Wind Harmer
4.432
971125AH1-004 GEN
Solar/Wind Harmer
2.1
970107AG2-081 GEN
Solar/Wind Harmer
1.575
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.035
339221AD2-048_GEN
Solar/Wind Harmer
0.789
970235AG2-159 GEN
Solar/Wind Harmer
2.014
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
2.736
970239AG2-162 GEN
Solar/Wind Harmer
5.35
276916AD2-100_GEN
Solar/Wind Harmer
10.174
276911AD2-131_GEN
Solar/Wind Harmer
2.056
957381AF2-032 GEN
Solar/Wind Harmer
0.202
276763AC1-053 GEN1
Solar/Wind Harmer
1.888
276764AC1-053 GEN2
Solar/Wind Harmer
1.888
945391AF1-204 GEN
Solar/Wind Harmer
6.653
270186AC1-089 GEN
Solar/Wind Harmer
2.887
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
1.871
276741O09 GEN1
Solar/Wind Harmer
1.678
276708O09 GEN2
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
1.333
274849CRESCENT ;1U
Solar/Wind Harmer
0.866
276645AC1-214 GEN1
Solar/Wind Harmer
0.627
276646AC1-214 GEN2
Solar/Wind Harmer
0.627
276603SUBLETTE C
Solar/Wind Harmer
0.491
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
11.684
938861AE1-114 GEN
Solar/Wind Harmer
3.828
274856ECOGROVE ;U1
Solar/Wind Harmer
1.572
276611AD2-172 GEN
Solar/Wind Harmer
1.193
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
7.487
274735ELWOOD EC;4P
Adder
2.023
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
274857EASY ROAD;U1
Solar/Wind Harmer
2.241
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
21.031
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
10.445
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
970819AG2-516 GEN
Solar/Wind Harmer
0.945
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
6.207
960911AF2-382 GEN
Solar/Wind Harmer
4.08
971461AH1-227 GEN
Solar/Wind Harmer
2.688
972103AH1-617 GEN
Solar/Wind Harmer
9.714
270053AF1-130 C
Solar/Wind Harmer
1.017
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.743
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
1.981
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
270030AE2-140 GEN
Solar/Wind Harmer
7.67
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
2.764
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970243AG2-164 GEN
Solar/Wind Harmer
1.988
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
970193AG2-126 GEN
Solar/Wind Harmer
4.996
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.536
965931AG1-462 GEN
Solar/Wind Harmer
8.444
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.836
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
970571AG2-364 GEN
Solar/Wind Harmer
6.485
959091AF2-200 GEN
Solar/Wind Harmer
6.478
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
276806AD2-047 C O1
Solar/Wind Harmer
1.793
970941AG2-585 GEN
Solar/Wind Harmer
3.954
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270437AC2-090 C
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
253406AD2-031_GEN
Solar/Wind Harmer
0.232
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
24735105WLF2G1
50/50
5.209
24734705WLF1G3
50/50
5.198
24734805WLF1G4
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
971313AH1-133 GEN
Solar/Wind Harmer
5.384
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
270400AC1-102 GEN
Solar/Wind Harmer
1.445
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
965401AG1-405 GEN
Solar/Wind Harmer
2.362
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
972165AH1-665 GEN
Solar/Wind Harmer
3.096
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.851
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
957751AF2-069 GEN
Solar/Wind Harmer
0.108
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.426
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
9.057
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.478
970169AG2-114 GEN
Solar/Wind Harmer
3.233
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
3.163
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
1.877
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971985AH1-537 GEN
Solar/Wind Harmer
0.937
270594AE1-207 GEN
Solar/Wind Harmer
3.524
958391AF2-133 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971609AH1-304 GEN
Solar/Wind Harmer
0.508
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
971029AG2-637 GEN
Solar/Wind Harmer
4.547
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
2.291
971485AH1-239 GEN
Solar/Wind Harmer
3.379
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
2.512
942891AE2-308 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
3.444
971125AH1-004 GEN
Solar/Wind Harmer
1.465
970107AG2-081 GEN
Solar/Wind Harmer
1.099
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
970239AG2-162 GEN
Solar/Wind Harmer
0.849
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276911AD2-131_GEN
Solar/Wind Harmer
0.468
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
3.539
270186AC1-089 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.117
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
971333AH1-146 GEN
Solar/Wind Harmer
6.465
971335AH1-147 GEN
Solar/Wind Harmer
6.465
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.647
958491AF2-143 GEN
Solar/Wind Harmer
4.817
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
25183208HLCRTG
Solar/Wind Harmer
0.005
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
1.51
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
270599AE1-208 GEN
Solar/Wind Harmer
2.851
270031AE2-169
Solar/Wind Harmer
1.71
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
24735205WLF2G2
50/50
5.209
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.41
971315AH1-136 GEN
Solar/Wind Harmer
0.889
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
0.002
962241AG1-070 GEN
Solar/Wind Harmer
2.203
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
3.952
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.098
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.731
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
7.717
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
970569AG2-363 GEN
Solar/Wind Harmer
9.728
252507AC2-088 GEN
Solar/Wind Harmer
0.147
957471AF2-041 GEN
Solar/Wind Harmer
9.717
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.69
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
0.568
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
274745AC1-111 GEN9
Adder
2.558
24791305MDL-5G
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.539
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.313
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
965031AG1-367 GEN
Solar/Wind Harmer
3.137
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:1.8
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:2.49
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:2.48
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:2.48
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:2.48
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.66 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6443.11
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
1.362
270329AC1-082 GEN1
Solar/Wind Harmer
0.802
957241AF2-018 GEN
Solar/Wind Harmer
7.728
270399AC1-101 GEN
Solar/Wind Harmer
7.31
270400AC1-102 GEN
Solar/Wind Harmer
7.31
962771AG1-126 GEN
Solar/Wind Harmer
54.777
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
32.861
972143AH1-644 GEN
Solar/Wind Harmer
15.648
971985AH1-537 GEN
Solar/Wind Harmer
27.909
941621AE2-160 GEN
Adder
5.057
962211AG1-066 GEN
Solar/Wind Harmer
3.665
971313AH1-133 GEN
Solar/Wind Harmer
14.875
270367AC2-061_GEN
Solar/Wind Harmer
4.719
970879AG2-548 GEN
Solar/Wind Harmer
6.295
972163AH1-664 GEN
Solar/Wind Harmer
14.604
972165AH1-665 GEN
Solar/Wind Harmer
11.684
339243AC2-075 GEN1
Solar/Wind Harmer
0.653
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
2.249
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
4.288
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
2.129
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
8.379
965401AG1-405 GEN
Solar/Wind Harmer
7.914
965411AG1-406 GEN
Solar/Wind Harmer
3.552
944031AF1-071 GEN
Solar/Wind Harmer
1.391
270269AC2-059
Solar/Wind Harmer
12.868
971061AG2-657 GEN
Solar/Wind Harmer
12.35
270240V3-007_GEN2
Solar/Wind Harmer
8.448
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
3.053
971227AH1-073 GEN
Solar/Wind Harmer
3.053
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
16.31
270186AC1-089 GEN
Solar/Wind Harmer
9.06
962581AG1-107 GEN
Solar/Wind Harmer
7.424
961491AF2-440 GEN
Solar/Wind Harmer
3.085
960161AF2-307 GEN
Solar/Wind Harmer
9.441
970879AG2-548 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
6.295
252509AD1-136 GEN
Solar/Wind Harmer
0.372
339221AD2-048_GEN
Solar/Wind Harmer
2.218
972043AH1-570 GEN
Solar/Wind Harmer
3.602
972045AH1-571 GEN
Solar/Wind Harmer
2.882
25183208HLCRTG
Solar/Wind Harmer
8.709
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
6.647
970235AG2-159 GEN
Solar/Wind Harmer
5.741
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
5.722
970107AG2-081 GEN
Solar/Wind Harmer
4.291
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
14.268
253317AC1-085 GEN4
Solar/Wind Harmer
11.89
270444AC2-157 GEN1
Solar/Wind Harmer
7.855
253394AE2-221_GEN
Solar/Wind Harmer
6.369
253398AE2-221_GEN2
Solar/Wind Harmer
6.369
964571AG1-320 GEN
Solar/Wind Harmer
11.394
970653AG2-424 GEN
Solar/Wind Harmer
6.671
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
10.253
945391AF1-204 GEN
Solar/Wind Harmer
19.047
24379505HDWTR1G C
Solar/Wind Harmer
10.797
270209AC1-174_GEN
Solar/Wind Harmer
7.62
926881AC1-175 GEN
Solar/Wind Harmer
7.62
253370AE2-315 SEC1
Adder
2.733
339231AF1-038_GEN
Solar/Wind Harmer
2.469
270383AD1-128 GEN
Solar/Wind Harmer
8.302
339236AF1-050_GEN
Solar/Wind Harmer
2.463
970241AG2-163 GEN
Solar/Wind Harmer
33.893
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
25326109MON D
Adder
1.763
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.804
970947AG2-589 GEN
Solar/Wind Harmer
3.539
960001AF2-291 GEN
Solar/Wind Harmer
5.242
971403AH1-188 GEN
Solar/Wind Harmer
24.059
962761AG1-125 GEN
Solar/Wind Harmer
54.777
970149AG2-104 GEN
Solar/Wind Harmer
67.649
970155AG2-107 GEN
Solar/Wind Harmer
23.885
971315AH1-136 GEN
Solar/Wind Harmer
3.199
927014AC1-188 GEN
Solar/Wind Harmer
2.494
971687AH1-348 GEN
Solar/Wind Harmer
1.529
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
46.803
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
27.516
252507AC2-088 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
2.413
25196008MFTGT1
Adder
1.989
943111AE2-339 GEN
Solar/Wind Harmer
1.263
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0.38
946171AF1-282 GEN
Solar/Wind Harmer
14.195
270263AC1-001 GEN
Solar/Wind Harmer
1.475
270445AC2-157 GEN2
Solar/Wind Harmer
7.855
971565AH1-281 GEN
Solar/Wind Harmer
2.807
971821AH1-427 GEN
Solar/Wind Harmer
14.027
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
339241AF1-083 GEN
Solar/Wind Harmer
2.279
942081AE2-220 GEN
Solar/Wind Harmer
8.729
270239V3-007_GEN1
Solar/Wind Harmer
2.35
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
13.573
963741AG1-226 GEN
Solar/Wind Harmer
61.007
970291AG2-192 GEN
Solar/Wind Harmer
1.76
270005AE1-210 C O1
Solar/Wind Harmer
7.396
965031AG1-367 GEN
Solar/Wind Harmer
13.534
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
20.265
960071AF2-298 GEN
Solar/Wind Harmer
6.737
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
274745AC1-111 GEN9
Adder
7.316
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
970825AG2-519 GEN
Solar/Wind Harmer
1.889
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
5.403
24699105WLD G1 C
Solar/Wind Harmer
5.339
253349AC2-067 GEN
Solar/Wind Harmer
6.756
253400AC2-068 GEN
Solar/Wind Harmer
2.717
965461AG1-414 GEN
Solar/Wind Harmer
3.069
970289AG2-191 GEN
Solar/Wind Harmer
2.572
270594AE1-207 GEN
Solar/Wind Harmer
19.886
963841AG1-237 GEN
Solar/Wind Harmer
14.783
24729505KEY G4
Adder
8.586
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.186
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
6.465
970153AG2-106 GEN
Solar/Wind Harmer
23.885
971191AH1-055 GEN
Solar/Wind Harmer
36.863
957541AF2-048 GEN
Solar/Wind Harmer
2.488
970913AG2-568 GEN
Solar/Wind Harmer
12.569
972103AH1-617 GEN
Solar/Wind Harmer
31.296
960911AF2-382 GEN
Solar/Wind Harmer
11.517
971461AH1-227 GEN
Solar/Wind Harmer
7.832
970243AG2-164 GEN
Solar/Wind Harmer
38.293
970519AG2-331 GEN
Solar/Wind Harmer
25.727
970699AG2-449 GEN
Solar/Wind Harmer
17.019
972167AH1-666 GEN
Solar/Wind Harmer
11.674
958171AF2-111 GEN
Solar/Wind Harmer
36.017
252510AF1-249 C
Solar/Wind Harmer
0.598
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
14.232
253316AC1-085 GEN3
Solar/Wind Harmer
11.89
253433AC1-085 GEN1
Solar/Wind Harmer
7.548
946181AF1-283 GEN
Solar/Wind Harmer
18.454
253406AD2-031_GEN
Solar/Wind Harmer
1.808
966571AG1-526 GEN
Solar/Wind Harmer
31.338
270291AC1-194 GEN
Solar/Wind Harmer
14.929
253415AE1-040 GEN
Solar/Wind Harmer
1.582
972173AH1-669 GEN
Solar/Wind Harmer
6.941
270222AC2-111 GEN
Solar/Wind Harmer
11.283
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
3.68
270356AE2-297 GEN
Solar/Wind Harmer
6.29
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
20.501
270437AC2-090 C
Solar/Wind Harmer
7.623
253303V4-073 C
Solar/Wind Harmer
0.158
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
12.267
970273AG2-179 GEN
Solar/Wind Harmer
5.305
960741AF2-365 GEN
Solar/Wind Harmer
6.78
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
18.947
270004AE1-209 GEN
Solar/Wind Harmer
7.396
274772LINCOLN ;3U
Adder
11.055
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.078
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
247621Y3-024
Adder
0.32
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.049
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
970825AG2-519 GEN
Solar/Wind Harmer
8.467
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:2.61
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:2.74
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
971277AH1-098 GEN
Solar/Wind Harmer
5.729
270583AD2-179 GEN
Solar/Wind Harmer
13.373
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971485AH1-239 GEN
Solar/Wind Harmer
9.113
970879AG2-548 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
339236AF1-050_GEN
Solar/Wind Harmer
2.029
339255AE2-071 GEN
Solar/Wind Harmer
1.185
964781AG1-341 GEN
Solar/Wind Harmer
11.836
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972043AH1-570 GEN
Solar/Wind Harmer
2.743
972045AH1-571 GEN
Solar/Wind Harmer
2.195
971125AH1-004 GEN
Solar/Wind Harmer
4.377
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
339221AD2-048_GEN
Solar/Wind Harmer
1.68
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
252509AD1-136 GEN
Solar/Wind Harmer
0.262
945391AF1-204 GEN
Solar/Wind Harmer
13.769
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
25183208HLCRTG
Solar/Wind Harmer
5.931
25194408D.CRK1
Adder
7.379
25194508D.CRK3
Adder
1.38
276916AD2-100_GEN
Solar/Wind Harmer
20.308
276911AD2-131_GEN
Solar/Wind Harmer
4.104
957381AF2-032 GEN
Solar/Wind Harmer
0.403
970241AG2-163 GEN
Solar/Wind Harmer
23.985
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
24728805RICHG1
Adder
3.448
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274765LEE CO EC;6U
Adder
8.446
274762LEE CO EC;3U
Adder
8.426
274763LEE CO EC;4U
Adder
8.346
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274696ROCKY RD ;4P
Adder
10.143
274695ROCKY RD ;2P
Adder
9.908
274693ROCKY RD ;1P
Adder
9.811
274697ROCKY RD ;3P
Adder
2.692
23652301WDPWR_K20
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.594
241967AE2-285_GEN
Solar/Wind Helper
0.583
241801AE1-079 GEN
Solar/Wind Helper
0.227
241985AE1-237 GEN
Solar/Wind Helper
0.227
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
944781AF1-143 GEN
Solar/Wind Helper
2.213
24289405MTG1
50/50
12.693
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
24318705GVG2
50/50
13.293
962761AG1-125 GEN
Solar/Wind Harmer
91.898
970149AG2-104 GEN
Solar/Wind Harmer
113.494
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
24686505CER G6
Adder
16.155
971403AH1-188 GEN
Solar/Wind Harmer
25.361
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
970947AG2-589 GEN
Solar/Wind Harmer
3.533
960001AF2-291 GEN
Solar/Wind Harmer
5.186
24728305BUCHG2
Adder
7.204
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
24735205WLF2G2
Adder
8.16
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
270336AE1-100 GEN
Solar/Wind Harmer
2.043
970091AG2-072 GEN
Adder
90.557
970333AG2-219 GEN
Solar/Wind Harmer
36.87
971367AH1-164 GEN
Solar/Wind Harmer
3.994
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
943111AE2-339 GEN
Solar/Wind Harmer
0.969
339216AC1-074 GEN
Solar/Wind Harmer
1.819
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
25194608D.CRK4
Adder
1.604
965911AG1-460 GEN
Solar/Wind Harmer
1.345
24728605AND G2
Adder
3.69
963741AG1-226 GEN
Solar/Wind Harmer
43.173
276615X2-022 GEN
Solar/Wind Harmer
1.868
274761LEE CO EC;2U
Adder
8.426
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
274822ROCKFORD ;11
Adder
17.664
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
20089226LOOKOUT
Solar/Wind Helper
0.519
963831AG1-236 GEN
Solar/Wind Harmer
2.691
24721605FLATG1
50/50
3.32
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
971313AH1-133 GEN
Solar/Wind Harmer
15.802
970281AG2-184 GEN
Solar/Wind Harmer
32.56
972143AH1-644 GEN
Solar/Wind Harmer
15.505
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
24734705WLF1G3
Adder
8.349
24734805WLF1G4
Adder
8.349
24734905WLF1G5
Adder
8.349
962211AG1-066 GEN
Solar/Wind Harmer
3.499
966391AG1-508 GEN
Solar/Wind Harmer
4.988
24735105WLF2G1
Adder
8.16
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
965411AG1-406 GEN
Solar/Wind Harmer
2.95
339211AE2-254 GEN
Solar/Wind Harmer
1.711
970879AG2-548 GEN
Solar/Wind Harmer
4.825
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
972165AH1-665 GEN
Solar/Wind Harmer
8.697
270367AC2-061_GEN
Solar/Wind Harmer
3.448
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
944221AF1-090 GEN
Solar/Wind Harmer
10.676
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274823ROCKFORD ;21
Adder
17.536
274746AC1-111 G10
Adder
4.954
274744AC1-111 GEN8
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241997AF1-093 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.203
24289405MTG1
50/50
12.693
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
24318705GVG2
50/50
13.293
970153AG2-106 GEN
Solar/Wind Harmer
40.072
24686205CER G4
Adder
16.091
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
971461AH1-227 GEN
Solar/Wind Harmer
7.917
971191AH1-055 GEN
Solar/Wind Harmer
33.8
270346AE1-212 GEN
Solar/Wind Harmer
13.484
943031AE2-326 GEN
Solar/Wind Harmer
5.284
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970243AG2-164 GEN
Solar/Wind Harmer
30.166
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
972273AH1-721 GEN
Adder
96.475
270030AE2-140 GEN
Solar/Wind Harmer
23.108
970273AG2-179 GEN
Solar/Wind Harmer
4.447
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
339250AF1-203 GEN
Solar/Wind Harmer
0.677
971155AH1-034 GEN
Solar/Wind Harmer
11.167
962251AG1-071 GEN
Solar/Wind Harmer
6.119
960741AF2-365 GEN
Solar/Wind Harmer
5.543
3429391JKCT 9G
Adder
9.194
972167AH1-666 GEN
Solar/Wind Harmer
8.642
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
25196008MFTGT1
Adder
1.363
970193AG2-126 GEN
Solar/Wind Harmer
14.82
252510AF1-249 C
Solar/Wind Harmer
0.411
270173AC1-122 GEN
Solar/Wind Harmer
1.562
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.312
942481AE2-261 GEN
Solar/Wind Harmer
28.829
24728705AND G3
Adder
7.718
24728505AND G1
Adder
3.69
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274760LEE CO EC;1U
Adder
8.426
274767LEE CO EC;8U
Adder
8.327
972236AH1-702 GEN2
Adder
1.974
274682WAUKEGAN ;7U
Adder
15.992
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
235058AG1-386 C
Solar/Wind Helper
0.421
237043AE2-125 C
Solar/Wind Helper
0.164
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089126CSLMN_L13
Solar/Wind Helper
0.533
20089026BF_G21_K23
Solar/Wind Helper
0.422
964991AG1-363 GEN
Solar/Wind Helper
3.317
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6192.17
MW Contribution:3.64
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.549
24723005RIVRG1
Adder
36.284
24723105RIVRG2
Adder
36.284
24685805CER G1
Adder
15.642
24685905CER G2
Adder
15.642
944971AF1-162 GEN
Solar/Wind Harmer
12.272
971225AH1-072 GEN
Solar/Wind Harmer
3.081
971227AH1-073 GEN
Solar/Wind Harmer
3.081
24728205BUCHG1
Adder
6.894
970239AG2-162 GEN
Solar/Wind Harmer
16.464
270186AC1-089 GEN
Solar/Wind Harmer
9.145
962581AG1-107 GEN
Solar/Wind Harmer
7.495
961491AF2-440 GEN
Solar/Wind Harmer
3.115
960161AF2-307 GEN
Solar/Wind Harmer
9.531
970879AG2-548 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
6.355
252509AD1-136 GEN
Solar/Wind Harmer
0.375
339221AD2-048_GEN
Solar/Wind Harmer
2.24
972043AH1-570 GEN
Solar/Wind Harmer
3.637
972045AH1-571 GEN
Solar/Wind Harmer
2.91
25183208HLCRTG
Solar/Wind Harmer
8.794
252519AF1-045_GEN
Solar/Wind Harmer
8.799
252516AE2-318_GEN
Solar/Wind Harmer
6.712
970235AG2-159 GEN
Solar/Wind Harmer
5.797
970235AG2-159 GEN
Solar/Wind Harmer
3.539
971125AH1-004 GEN
Solar/Wind Harmer
5.778
970107AG2-081 GEN
Solar/Wind Harmer
4.333
25194408D.CRK1
Adder
10.905
25194508D.CRK3
Adder
2.039
942891AE2-308 GEN
Solar/Wind Harmer
14.408
253317AC1-085 GEN4
Solar/Wind Harmer
12.008
270444AC2-157 GEN1
Solar/Wind Harmer
7.934
253394AE2-221_GEN
Solar/Wind Harmer
6.433
253398AE2-221_GEN2
Solar/Wind Harmer
6.433
964571AG1-320 GEN
Solar/Wind Harmer
11.509
970653AG2-424 GEN
Solar/Wind Harmer
6.739
970653AG2-424 GEN
Solar/Wind Harmer
2.436
24728805RICHG1
Adder
5.257
24728905RICHG2
Adder
5.257
971081AG2-670 GEN
Solar/Wind Harmer
10.358
945391AF1-204 GEN
Solar/Wind Harmer
19.242
24379505HDWTR1G C
Solar/Wind Harmer
10.908
270209AC1-174_GEN
Solar/Wind Harmer
7.698
926881AC1-175 GEN
Solar/Wind Harmer
7.698
253370AE2-315 SEC1
Adder
2.761
339231AF1-038_GEN
Solar/Wind Harmer
2.495
270383AD1-128 GEN
Solar/Wind Harmer
8.387
339236AF1-050_GEN
Solar/Wind Harmer
2.488
970241AG2-163 GEN
Solar/Wind Harmer
34.243
25322209TAIT E
Adder
13.324
25322209TAIT E
Adder
13.025
25326109MON D
Adder
1.782
247621Y3-024
Adder
0.324
274770LINCOLN ;1U
Adder
11.173
274771LINCOLN ;2U
Adder
11.173
972259AH1-714 GEN
Adder
25.243
972267AH1-718 GEN
Adder
5.508
274696ROCKY RD ;4P
Adder
15.074
274695ROCKY RD ;2P
Adder
14.726
274693ROCKY RD ;1P
Adder
14.581
274697ROCKY RD ;3P
Adder
4
274764LEE CO EC;5U
Adder
12.334
274765LEE CO EC;6U
Adder
12.334
274762LEE CO EC;3U
Adder
12.305
274763LEE CO EC;4U
Adder
12.189
23652301WDPWR_K20
Solar/Wind Helper
0.166
23585401KL_K28_T16
Solar/Wind Helper
1.512
203955AF1-039 C O1
Solar/Wind Helper
0.427
944781AF1-143 GEN
Solar/Wind Helper
2.801
238120AE2-309 GEN
Solar/Wind Helper
0.501
962101AG1-054 GEN
Solar/Wind Helper
0.706
20083426SW_E13_K22
Solar/Wind Helper
0.063
241985AE1-237 GEN
Solar/Wind Helper
0.267
241967AE2-285_GEN
Solar/Wind Helper
0.687
241801AE1-079 GEN
Solar/Wind Helper
0.267
20088926STNY CRK
Solar/Wind Helper
0.916
946071AF1-272 GEN
Solar/Wind Helper
3.012
20084626FORWARD
Solar/Wind Helper
0.397
203940AF1-140 C
Solar/Wind Helper
0.44
20088626ARWF_N39
Solar/Wind Helper
1.344
20303426NA_O38_P22
Solar/Wind Helper
1.102
203853AF1-134 C O1
Solar/Wind Helper
0.526
946381AF1-302 GEN
Solar/Wind Helper
0.243
203952AE2-129 C
Solar/Wind Helper
0.521
203946AE2-131 C
Solar/Wind Helper
0.522
238217AF1-153 C O1
Solar/Wind Helper
0.259
20398826ARMNA MT
Solar/Wind Helper
1.633
209137AF2-361 C
Solar/Wind Helper
1.509
946751AF1-339 GEN
Solar/Wind Helper
0.493
209054AE2-059 GEN
Solar/Wind Helper
0.089
961431AF2-434 GEN
Solar/Wind Helper
0.491
208972BECR K09
Solar/Wind Helper
0.367
209029WAYMART-WD
Solar/Wind Helper
0.923
203979AG1-198 GEN
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.165
211065PSPA IPP
Solar/Wind Helper
0.165
203980AG1-197 GEN
Solar/Wind Helper
0.363
966111AG1-480 GEN
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.087
20676228FRD_X1-012
Solar/Wind Helper
0.099
207471AF2-354 C
Solar/Wind Helper
0.181
20674928WA_W3-044
Solar/Wind Helper
0.106
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.028
207442AE1-156 GEN
Solar/Wind Helper
0.346
20676128MHD_W3-029
Solar/Wind Helper
0.102
20673828FLE_V3-070
Solar/Wind Helper
0.096
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20716928W4-060COL
Solar/Wind Helper
0.054
20720628TIN_W1-124
Solar/Wind Helper
0.2
20714928UPF_X1-085
Solar/Wind Helper
0.005
963391AG1-188 GEN
Solar/Wind Helper
0.086
963401AG1-189 GEN
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.351
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.053
203947AF1-006 C
Solar/Wind Helper
0.519
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.379
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233933AB2-153 GEN
Solar/Wind Helper
0.236
235063AE1-101 C2
Solar/Wind Helper
1.441
205916AD1-020 GEN
Solar/Wind Helper
1.685
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.382
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.191
238175AF1-290_GEN
Solar/Wind Helper
0.121
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.098
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
970825AG2-519 GEN
Solar/Wind Harmer
8.555
24289405MTG1
50/50
11.412
243186AF1-051 GEN
50/50
12.549
24318705GVG2
50/50
11.681
24721805FLATG3
50/50
2.772
24721705FLATG2
50/50
50.82
24723205RIVRG3
Adder
36.284
24686105CER G3
Adder
15.746
24686505CER G6
Adder
15.725
270331AC1-082 GEN3
Solar/Wind Harmer
0.811
970947AG2-589 GEN
Solar/Wind Harmer
3.567
960001AF2-291 GEN
Solar/Wind Harmer
5.284
971403AH1-188 GEN
Solar/Wind Harmer
24.255
962761AG1-125 GEN
Solar/Wind Harmer
55.23
970149AG2-104 GEN
Solar/Wind Harmer
68.21
970155AG2-107 GEN
Solar/Wind Harmer
24.083
971315AH1-136 GEN
Solar/Wind Harmer
3.227
927014AC1-188 GEN
Solar/Wind Harmer
2.517
971687AH1-348 GEN
Solar/Wind Harmer
1.543
24728305BUCHG2
Adder
6.894
970333AG2-219 GEN
Solar/Wind Harmer
47.244
970091AG2-072 GEN
Adder
114.655
945681AF1-233 GEN
Solar/Wind Harmer
27.78
252507AC2-088 GEN
Solar/Wind Harmer
2.628
25196808ZIMRHP
Adder
110.178
339216AC1-074 GEN
Solar/Wind Harmer
2.436
25196008MFTGT1
Adder
2.009
943111AE2-339 GEN
Solar/Wind Harmer
1.275
25194608D.CRK4
Adder
2.371
3429241JKCT 3G
Adder
17.06
3429421JKCT 10G
Adder
11.981
253432AC1-085 GEN2
Solar/Wind Harmer
0.384
946171AF1-282 GEN
Solar/Wind Harmer
14.335
270263AC1-001 GEN
Solar/Wind Harmer
1.49
270445AC2-157 GEN2
Solar/Wind Harmer
7.934
971565AH1-281 GEN
Solar/Wind Harmer
2.835
971821AH1-427 GEN
Solar/Wind Harmer
14.167
24735205WLF2G2
Adder
8.161
24728605AND G2
Adder
5.324
339241AF1-083 GEN
Solar/Wind Harmer
2.303
942081AE2-220 GEN
Solar/Wind Harmer
8.819
270239V3-007_GEN1
Solar/Wind Harmer
2.374
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
970273AG2-179 GEN
Solar/Wind Harmer
3.356
276903AD2-071 C
Solar/Wind Harmer
13.713
963741AG1-226 GEN
Solar/Wind Harmer
61.637
970291AG2-192 GEN
Solar/Wind Harmer
1.778
270005AE1-210 C O1
Solar/Wind Harmer
7.473
965031AG1-367 GEN
Solar/Wind Harmer
13.674
270032AE2-172
Solar/Wind Harmer
6.358
25326309TAIT D
Adder
1.497
964901AG1-354 GEN
Solar/Wind Harmer
20.475
960071AF2-298 GEN
Solar/Wind Harmer
6.807
274773LINCOLN ;4U
Adder
11.173
274774LINCOLN ;5U
Adder
11.173
274745AC1-111 GEN9
Adder
7.394
274761LEE CO EC;2U
Adder
12.305
274766LEE CO EC;7U
Adder
12.16
237046AF1-021 C
Solar/Wind Helper
0.57
238185AF2-356 C
Solar/Wind Helper
2.581
23751201ROTHROCK
Solar/Wind Helper
0.868
235054AD2-180 GEN
Solar/Wind Helper
2.007
23562501BACKB
Solar/Wind Helper
1.057
238117U2-030
Solar/Wind Helper
0.339
235531U2-073 GEN
Solar/Wind Helper
3.19
20089226LOOKOUT
Solar/Wind Helper
0.657
254303AC2-168 GEN
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.277
23751101LEADS_P59
Solar/Wind Helper
1.464
20088826HIGHLAND
Solar/Wind Helper
0.998
20094526CT_V3-030
Solar/Wind Helper
0.523
964201AG1-281 GEN
Solar/Wind Helper
0.537
238108AE1-109 GEN1
Solar/Wind Helper
0.101
964391AG1-301 GEN
Solar/Wind Helper
0.522
203954AE2-126 C
Solar/Wind Helper
0.514
238206AE2-263_GEN
Solar/Wind Helper
0.997
959471AF2-238 GEN
Solar/Wind Helper
0.51
203860AG1-193 C
Solar/Wind Helper
0.25
209067AE2-060 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.493
946741AF1-338 GEN
Solar/Wind Helper
0.493
961421AF2-433 GEN
Solar/Wind Helper
0.491
957921AF2-086 GEN
Solar/Wind Helper
0.486
961331AF2-424 GEN
Solar/Wind Helper
0.491
209027LOR2_Q27
Solar/Wind Helper
1.148
963071AG1-156 GEN
Solar/Wind Helper
1.601
963161AG1-165 GEN
Solar/Wind Helper
0.489
316095T157 G97
Solar/Wind Helper
1.137
23583801GRNGAP
Solar/Wind Helper
4.22
961971AG1-040 GEN
Solar/Wind Helper
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.929
20674628WNG_W3-110
Solar/Wind Helper
0.096
207510AF2-138 C
Solar/Wind Helper
0.087
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.078
219919AE1-041 FULL
Solar/Wind Helper
0.004
219612MATRIX C
Solar/Wind Helper
0.025
218438BLK ROCK C
Solar/Wind Helper
0.029
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.094
20720828JCB_W4-025
Solar/Wind Helper
0.066
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.06
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.119
219906AC1-017 C
Solar/Wind Helper
0.043
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.155
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.114
230415AB2-049 C
Solar/Wind Helper
0.031
230430AE1-229_GEN
Solar/Wind Helper
3.487
233971AC1-093 C
Solar/Wind Helper
0.364
233952AC2-187 GEN
Solar/Wind Helper
0.236
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233982AB2-133 GEN
Solar/Wind Helper
0.363
233918AB1-142 GEN
Solar/Wind Helper
0.51
235067AD1-061 GEN
Solar/Wind Helper
0.427
205917AD1-020 ES
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.232
237030AB1-096 C
Solar/Wind Helper
0.062
223402AF1-300 C
Solar/Wind Helper
0.332
970825AG2-519 GEN
Solar/Wind Harmer
1.909
24721605FLATG1
50/50
2.772
972203AH1-686 GEN
Adder
4.457
270330AC1-082 GEN2
Solar/Wind Harmer
1.373
270329AC1-082 GEN1
Solar/Wind Harmer
0.808
957241AF2-018 GEN
Solar/Wind Harmer
7.79
270399AC1-101 GEN
Solar/Wind Harmer
7.37
270400AC1-102 GEN
Solar/Wind Harmer
7.37
962771AG1-126 GEN
Solar/Wind Harmer
55.23
24477305BRIDGE
Adder
0.593
970281AG2-184 GEN
Solar/Wind Harmer
33.155
972143AH1-644 GEN
Solar/Wind Harmer
15.788
971985AH1-537 GEN
Solar/Wind Harmer
28.159
941621AE2-160 GEN
Adder
5.103
962211AG1-066 GEN
Solar/Wind Harmer
3.699
971313AH1-133 GEN
Solar/Wind Harmer
15.015
270367AC2-061_GEN
Solar/Wind Harmer
4.764
970879AG2-548 GEN
Solar/Wind Harmer
6.355
972163AH1-664 GEN
Solar/Wind Harmer
14.744
972165AH1-665 GEN
Solar/Wind Harmer
11.796
339243AC2-075 GEN1
Solar/Wind Harmer
0.66
25196108MFTGT2
Adder
2.214
25196108MFTGT2
Adder
2.056
3429211JKCT 2G
Adder
16.839
252524AE2-267 GEN
Solar/Wind Harmer
2.271
25196408WSDLE3
Adder
12.703
25196308WSDLE2
Adder
12.592
25196208WSDLE1
Adder
12.561
25196708WSDLE6
Adder
12.529
25196508WSDLE4
Adder
12.214
24734705WLF1G3
Adder
8.278
24734805WLF1G4
Adder
8.278
24734905WLF1G5
Adder
8.278
270340AC2-060 GEN
Solar/Wind Harmer
4.33
270132AB1-180 C
Adder
0.172
339211AE2-254 GEN
Solar/Wind Harmer
2.15
24735105WLF2G1
Adder
8.161
970455AG2-298 GEN
Solar/Wind Harmer
8.463
965401AG1-405 GEN
Solar/Wind Harmer
7.994
965411AG1-406 GEN
Solar/Wind Harmer
3.588
944031AF1-071 GEN
Solar/Wind Harmer
1.405
270269AC2-059
Solar/Wind Harmer
12.998
971061AG2-657 GEN
Solar/Wind Harmer
12.476
270240V3-007_GEN2
Solar/Wind Harmer
8.534
253372AE2-315 SEC3
Adder
2.611
253372AE2-315 SEC3
Adder
2.611
25306009OHH W.
Adder
3.967
24725505WLD G2 C
Solar/Wind Harmer
5.459
24699105WLD G1 C
Solar/Wind Harmer
5.394
253349AC2-067 GEN
Solar/Wind Harmer
6.826
253400AC2-068 GEN
Solar/Wind Harmer
2.745
965461AG1-414 GEN
Solar/Wind Harmer
3.101
970289AG2-191 GEN
Solar/Wind Harmer
2.598
270594AE1-207 GEN
Solar/Wind Harmer
20.092
963841AG1-237 GEN
Solar/Wind Harmer
14.936
24729505KEY G4
Adder
8.677
274775LINCOLN ;6U
Adder
11.173
274776LINCOLN ;7U
Adder
11.173
274777LINCOLN ;8U
Adder
11.173
274746AC1-111 G10
Adder
7.394
274744AC1-111 GEN8
Adder
7.394
274731ELWOOD EC;2P
Adder
21.74
274733ELWOOD EC;3P
Adder
13.586
23750501ELLIOTTS
Solar/Wind Helper
0.779
238126S14_GEN_1
Solar/Wind Helper
0.8
254304AE2-114 C
Solar/Wind Helper
0.235
241997AF1-093 GEN
Solar/Wind Helper
0.277
241982AE2-343 S C
Solar/Wind Helper
0.24
20092526R32
Solar/Wind Helper
1.294
203961AE2-224 GEN
Solar/Wind Helper
2.672
20091526CHSTN_FL
Solar/Wind Helper
0.646
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
20090526Q36
Solar/Wind Helper
1.152
203993AD2-133_GEN1
Solar/Wind Helper
1.152
941231AE2-117 GEN
Solar/Wind Helper
0.523
203846AF2-130 C
Solar/Wind Helper
0.491
203855AF2-088 C
Solar/Wind Helper
0.168
203804AE2-113_GEN
Solar/Wind Helper
1.898
959431AF2-234 GEN
Solar/Wind Helper
0.986
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.493
961261AF2-417 GEN
Solar/Wind Helper
0.488
209116AE2-175 GEN
Solar/Wind Helper
1.938
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.09
20675728RH_W2-091
Solar/Wind Helper
0.147
207484AF2-139 C O1
Solar/Wind Helper
0.09
203975AE1-071-GEN
Solar/Wind Helper
2.635
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.054
238208AF1-136 C
Solar/Wind Helper
0.189
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.071
966261AG1-495 GEN
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.17
218526CNTRALGAS2 C
Solar/Wind Helper
0.17
20675528CPH_W2-050
Solar/Wind Helper
0.092
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.304
20715728PEM_W1-119
Solar/Wind Helper
0.1
20715828PEM_W1-120
Solar/Wind Helper
0.1
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.359
219607WPEMNERT C
Solar/Wind Helper
0.083
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.119
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
0.988
234033AF1-007_GEN
Solar/Wind Helper
7.137
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
237085AD2-009_GEN
Solar/Wind Helper
1.427
205932AD2-116_GEN
Solar/Wind Helper
0.516
205956AE1-196_GEN
Solar/Wind Helper
0.516
205943AE1-185 GEN
Solar/Wind Helper
0.515
232436AB1-176 C
Solar/Wind Helper
0.045
233935AB2-179 C
Solar/Wind Helper
1.288
960921AF2-383 GEN
Solar/Wind Helper
0.183
24289405MTG1
50/50
11.412
24318705GVG2
50/50
11.681
24722005FLATG5
50/50
2.772
24721905FLATG4
50/50
50.82
24686205CER G4
Adder
15.663
24686405CER G5
Adder
15.601
270053AF1-130 C
Solar/Wind Harmer
6.517
970153AG2-106 GEN
Solar/Wind Harmer
24.083
971191AH1-055 GEN
Solar/Wind Harmer
37.171
957541AF2-048 GEN
Solar/Wind Harmer
2.51
970913AG2-568 GEN
Solar/Wind Harmer
12.681
972103AH1-617 GEN
Solar/Wind Harmer
31.576
960911AF2-382 GEN
Solar/Wind Harmer
11.622
971461AH1-227 GEN
Solar/Wind Harmer
7.904
970243AG2-164 GEN
Solar/Wind Harmer
38.654
970519AG2-331 GEN
Solar/Wind Harmer
25.969
970699AG2-449 GEN
Solar/Wind Harmer
17.18
972167AH1-666 GEN
Solar/Wind Harmer
11.786
958171AF2-111 GEN
Solar/Wind Harmer
36.367
252510AF1-249 C
Solar/Wind Harmer
0.604
25196008MFTGT1
Adder
1.945
25194608D.CRK4
Adder
2.371
25196608WSDLE5
Adder
12.34
3429391JKCT 9G
Adder
11.981
970093AG2-073 GEN
Solar/Wind Harmer
14.372
253316AC1-085 GEN3
Solar/Wind Harmer
12.008
253433AC1-085 GEN1
Solar/Wind Harmer
7.622
946181AF1-283 GEN
Solar/Wind Harmer
18.636
253406AD2-031_GEN
Solar/Wind Harmer
1.826
966571AG1-526 GEN
Solar/Wind Harmer
31.649
270291AC1-194 GEN
Solar/Wind Harmer
15.077
253415AE1-040 GEN
Solar/Wind Harmer
1.598
972173AH1-669 GEN
Solar/Wind Harmer
7.011
270222AC2-111 GEN
Solar/Wind Harmer
11.397
270273AD2-016 GEN
Solar/Wind Harmer
3.717
972273AH1-721 GEN
Adder
115.895
270356AE2-297 GEN
Solar/Wind Harmer
6.354
24728705AND G3
Adder
11.134
24728505AND G1
Adder
5.324
970193AG2-126 GEN
Solar/Wind Harmer
20.711
270437AC2-090 C
Solar/Wind Harmer
7.702
253303V4-073 C
Solar/Wind Harmer
0.16
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
270346AE1-212 GEN
Solar/Wind Harmer
12.393
970273AG2-179 GEN
Solar/Wind Harmer
5.36
960741AF2-365 GEN
Solar/Wind Harmer
6.85
247642Z2-115 C
Solar/Wind Harmer
0.088
970289AG2-191 GEN
Solar/Wind Harmer
1.05
970291AG2-192 GEN
Solar/Wind Harmer
0.954
958821AF2-173 GEN
Solar/Wind Harmer
19.143
270004AE1-209 GEN
Solar/Wind Harmer
7.473
274772LINCOLN ;3U
Adder
11.173
274760LEE CO EC;1U
Adder
12.305
274767LEE CO EC;8U
Adder
12.16
274729ELWOOD EC;1P
Adder
21.74
237048AF1-022 C
Solar/Wind Helper
0.225
237043AE2-125 C
Solar/Wind Helper
0.205
235058AG1-386 C
Solar/Wind Helper
0.508
964991AG1-363 GEN
Solar/Wind Helper
4.361
23750701CROSSCHOOL
Solar/Wind Helper
1.41
238118U2-030_1
Solar/Wind Helper
0.339
202652Y1-033 WT C
Solar/Wind Helper
0.647
20089126CSLMN_L13
Solar/Wind Helper
0.675
20089026BF_G21_K23
Solar/Wind Helper
0.534
238127S14_GEN_2
Solar/Wind Helper
0.8
254305AE2-115 C
Solar/Wind Helper
0.235
203818AF1-086 GEN
Solar/Wind Helper
1.862
203854AF2-039 C
Solar/Wind Helper
0.349
20334926Z1-069 C
Solar/Wind Helper
1.47
238202AE2-262_GEN
Solar/Wind Helper
1.048
941421AE2-139 GEN
Solar/Wind Helper
2.537
959441AF2-235 GEN
Solar/Wind Helper
0.252
200917MEHOOPANY_G
Solar/Wind Helper
2.394
209071AE2-133 GEN
Solar/Wind Helper
0.089
946731AF1-337 GEN
Solar/Wind Helper
0.493
212507AE2-042_GEN
Solar/Wind Helper
1.746
961341AF2-425 GEN
Solar/Wind Helper
0.491
212266LOR1
Solar/Wind Helper
0.053
961301AF2-421 GEN
Solar/Wind Helper
0.489
963151AG1-164 GEN
Solar/Wind Helper
0.489
316097T157 G90
Solar/Wind Helper
1.137
203830AF1-094 GEN
Solar/Wind Helper
0.488
20671928W4-073
Solar/Wind Helper
0.097
207518AF1-320_GEN
Solar/Wind Helper
1.692
207437AD2-070 GEN
Solar/Wind Helper
0.148
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.072
207528AF2-192 GEN
Solar/Wind Helper
0.081
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.481
217213AMBOY SO C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.524
20742028HF_AC1-207
Solar/Wind Helper
0.148
20715228NPK_W1-113
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.327
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.067
20714828MDF_W3-079
Solar/Wind Helper
0.137
207445AB1-138_GEN
Solar/Wind Helper
0.109
20720728JCB_W1-129
Solar/Wind Helper
0.06
219304NAMERICA C
Solar/Wind Helper
0.137
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219904AC1-010 C
Solar/Wind Helper
0.063
219258KINSLEYDEP C
Solar/Wind Helper
0.079
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.308
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
232434Z2-077 GEN
Solar/Wind Helper
0.129
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.116
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.51
966131AG1-482 GEN
Solar/Wind Helper
0.077
235062AE1-101 C1
Solar/Wind Helper
1.441
237038AE2-054 C
Solar/Wind Helper
0.234
237080AD1-060 GEN
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.165
223401AF1-299 GEN
Solar/Wind Helper
0.332
944201AF1-088_MTX
Adder
165.192
957141AF2-008_MTX
Adder
82.596
LAGNLTFEXP_LAGN->PJM
CLTF
25.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.665
TVALTFEXP_TVA->PJM
CLTF
12.772
NYPJM->LTFIMP_NY
CLTF
6.186
LGEELTFEXP_LGEE->PJM
CLTF
9.94
WECLTFEXP_WEC->PJM
CLTF
5.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.309
AH1-155LTFEXP_AH1-155->PJM
LTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
6.71
CBM West 2LTFEXP_CBM-W2->PJM
CBM
175.047
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
49.115
MECLTFEXP_MEC->PJM
CLTF
22.175
SIGELTFEXP_SIGE->PJM
CLTF
0.736

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:3.3
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
971277AH1-098 GEN
Solar/Wind Harmer
6.642
270583AD2-179 GEN
Solar/Wind Harmer
16.345
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
942891AE2-308 GEN
Solar/Wind Harmer
13.304
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972043AH1-570 GEN
Solar/Wind Harmer
3.299
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
971125AH1-004 GEN
Solar/Wind Harmer
5.257
970107AG2-081 GEN
Solar/Wind Harmer
3.942
971485AH1-239 GEN
Solar/Wind Harmer
10.499
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
971081AG2-670 GEN
Solar/Wind Harmer
9.778
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964781AG1-341 GEN
Solar/Wind Harmer
13.698
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
945391AF1-204 GEN
Solar/Wind Harmer
16.499
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
24.323
276911AD2-131_GEN
Solar/Wind Harmer
4.916
253370AE2-315 SEC1
Adder
2.238
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
26.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
970947AG2-589 GEN
Solar/Wind Harmer
3.612
960001AF2-291 GEN
Solar/Wind Harmer
5.329
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971329AH1-144 GEN
Solar/Wind Harmer
19.813
971315AH1-136 GEN
Solar/Wind Harmer
3.299
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
2.379
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
41.959
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
13.272
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
24.878
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339216AC1-074 GEN
Solar/Wind Harmer
2.198
339241AF1-083 GEN
Solar/Wind Harmer
2.171
971565AH1-281 GEN
Solar/Wind Harmer
2.604
964901AG1-354 GEN
Solar/Wind Harmer
19.445
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
270263AC1-001 GEN
Solar/Wind Harmer
1.245
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
38.198
970149AG2-104 GEN
Solar/Wind Harmer
47.174
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
963741AG1-226 GEN
Solar/Wind Harmer
22.669
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
971313AH1-133 GEN
Solar/Wind Harmer
17.224
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
5.763
970281AG2-184 GEN
Solar/Wind Harmer
34.934
972143AH1-644 GEN
Solar/Wind Harmer
16.635
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
962211AG1-066 GEN
Solar/Wind Harmer
3.823
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
14.056
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965401AG1-405 GEN
Solar/Wind Harmer
7.637
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972163AH1-664 GEN
Solar/Wind Harmer
13.228
972165AH1-665 GEN
Solar/Wind Harmer
10.582
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
1.95
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
962771AG1-126 GEN
Solar/Wind Harmer
38.198
944031AF1-071 GEN
Solar/Wind Harmer
1.178
944221AF1-090 GEN
Solar/Wind Harmer
12.754
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274823ROCKFORD ;21
Adder
21.377
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
8.54
972103AH1-617 GEN
Solar/Wind Harmer
33.271
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
36.143
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
26.875
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
966571AG1-526 GEN
Solar/Wind Harmer
29.484
270173AC1-122 GEN
Solar/Wind Harmer
2.108
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.144
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
339250AF1-203 GEN
Solar/Wind Harmer
0.784
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
962251AG1-071 GEN
Solar/Wind Harmer
7.087
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
253415AE1-040 GEN
Solar/Wind Harmer
1.318
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
972236AH1-702 GEN2
Adder
2.406
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5914.32
MW Contribution:2.97
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.329
243186AF1-051 GEN
50/50
12.367
24318705GVG2
50/50
11.512
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
24686505CER G6
Adder
14.768
971403AH1-188 GEN
Solar/Wind Harmer
23.029
270331AC1-082 GEN3
Solar/Wind Harmer
0.743
970947AG2-589 GEN
Solar/Wind Harmer
3.261
960001AF2-291 GEN
Solar/Wind Harmer
4.797
962761AG1-125 GEN
Solar/Wind Harmer
51.279
970149AG2-104 GEN
Solar/Wind Harmer
63.33
970155AG2-107 GEN
Solar/Wind Harmer
22.36
971315AH1-136 GEN
Solar/Wind Harmer
2.924
24728305BUCHG2
Adder
6.555
971687AH1-348 GEN
Solar/Wind Harmer
1.437
24735205WLF2G2
Adder
7.624
927014AC1-188 GEN
Solar/Wind Harmer
2.074
970333AG2-219 GEN
Solar/Wind Harmer
40.872
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
14.766
270445AC2-157 GEN2
Solar/Wind Harmer
6.775
971821AH1-427 GEN
Solar/Wind Harmer
11.992
971565AH1-281 GEN
Solar/Wind Harmer
2.394
3429241JKCT 3G
Adder
14.135
970273AG2-179 GEN
Solar/Wind Harmer
2.902
339241AF1-083 GEN
Solar/Wind Harmer
1.973
3429421JKCT 10G
Adder
9.882
943111AE2-339 GEN
Solar/Wind Harmer
1.047
339216AC1-074 GEN
Solar/Wind Harmer
1.982
945681AF1-233 GEN
Solar/Wind Harmer
22.212
964901AG1-354 GEN
Solar/Wind Harmer
17.673
962241AG1-070 GEN
Solar/Wind Harmer
5.277
963741AG1-226 GEN
Solar/Wind Harmer
52.124
25196008MFTGT1
Adder
1.607
24385905FR-11G C
Solar/Wind Harmer
9.582
24387305FR-4G C
Solar/Wind Harmer
5.858
252507AC2-088 GEN
Solar/Wind Harmer
2.064
24728605AND G2
Adder
4.411
970245AG2-165 GEN
Solar/Wind Harmer
20.527
965911AG1-460 GEN
Solar/Wind Harmer
1.601
25196808ZIMRHP
Adder
86.412
25194608D.CRK4
Adder
1.851
274761LEE CO EC;2U
Adder
10.448
274766LEE CO EC;7U
Adder
10.325
972235AH1-702 GEN1
Adder
2.828
274822ROCKFORD ;11
Adder
22.02
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
238185AF2-356 C
Solar/Wind Helper
2.169
23751201ROTHROCK
Solar/Wind Helper
0.732
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
254303AC2-168 GEN
Solar/Wind Helper
0.147
238117U2-030
Solar/Wind Helper
0.284
241966AE1-183 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.556
235531U2-073 GEN
Solar/Wind Helper
2.67
23751101LEADS_P59
Solar/Wind Helper
1.234
20088826HIGHLAND
Solar/Wind Helper
0.845
20094526CT_V3-030
Solar/Wind Helper
0.443
964201AG1-281 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.084
24791305MDL-5G
Solar/Wind Harmer
1.072
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971225AH1-072 GEN
Solar/Wind Harmer
2.872
971227AH1-073 GEN
Solar/Wind Harmer
2.872
970239AG2-162 GEN
Solar/Wind Harmer
14.243
270214AC2-123 GEN
Solar/Wind Harmer
2.998
971277AH1-098 GEN
Solar/Wind Harmer
5.115
960161AF2-307 GEN
Solar/Wind Harmer
7.971
270444AC2-157 GEN1
Solar/Wind Harmer
6.775
942891AE2-308 GEN
Solar/Wind Harmer
11.976
970235AG2-159 GEN
Solar/Wind Harmer
4.77
970235AG2-159 GEN
Solar/Wind Harmer
2.912
964571AG1-320 GEN
Solar/Wind Harmer
9.767
970653AG2-424 GEN
Solar/Wind Harmer
5.74
970653AG2-424 GEN
Solar/Wind Harmer
2.075
339231AF1-038_GEN
Solar/Wind Harmer
2.157
270186AC1-089 GEN
Solar/Wind Harmer
7.264
972043AH1-570 GEN
Solar/Wind Harmer
2.97
972045AH1-571 GEN
Solar/Wind Harmer
2.376
339221AD2-048_GEN
Solar/Wind Harmer
1.825
971081AG2-670 GEN
Solar/Wind Harmer
8.888
270583AD2-179 GEN
Solar/Wind Harmer
11.844
971125AH1-004 GEN
Solar/Wind Harmer
4.737
970107AG2-081 GEN
Solar/Wind Harmer
3.553
966021AG1-471 GEN
Solar/Wind Harmer
6.38
339236AF1-050_GEN
Solar/Wind Harmer
2.142
971485AH1-239 GEN
Solar/Wind Harmer
9.446
339255AE2-071 GEN
Solar/Wind Harmer
1.246
964781AG1-341 GEN
Solar/Wind Harmer
12.447
945391AF1-204 GEN
Solar/Wind Harmer
16.279
962581AG1-107 GEN
Solar/Wind Harmer
5.875
961491AF2-440 GEN
Solar/Wind Harmer
2.442
970241AG2-163 GEN
Solar/Wind Harmer
28.958
966841AG1-555 GEN
Solar/Wind Harmer
2.893
252509AD1-136 GEN
Solar/Wind Harmer
0.295
970321AG2-212 GEN
Solar/Wind Harmer
20.527
276916AD2-100_GEN
Solar/Wind Harmer
24.115
276911AD2-131_GEN
Solar/Wind Harmer
4.874
957381AF2-032 GEN
Solar/Wind Harmer
0.48
25194408D.CRK1
Adder
8.517
25194508D.CRK3
Adder
1.592
972267AH1-718 GEN
Adder
4.679
274764LEE CO EC;5U
Adder
10.473
274765LEE CO EC;6U
Adder
10.473
274762LEE CO EC;3U
Adder
10.448
274763LEE CO EC;4U
Adder
10.35
274696ROCKY RD ;4P
Adder
12.769
274695ROCKY RD ;2P
Adder
12.475
274693ROCKY RD ;1P
Adder
12.352
274697ROCKY RD ;3P
Adder
3.389
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
962101AG1-054 GEN
Solar/Wind Helper
0.609
241985AE1-237 GEN
Solar/Wind Helper
0.231
241967AE2-285_GEN
Solar/Wind Helper
0.593
241801AE1-079 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
238120AE2-309 GEN
Solar/Wind Helper
0.419
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20088926STNY CRK
Solar/Wind Helper
0.775
20084626FORWARD
Solar/Wind Helper
0.336
203940AF1-140 C
Solar/Wind Helper
0.373
20088626ARWF_N39
Solar/Wind Helper
1.136
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
946381AF1-302 GEN
Solar/Wind Helper
0.207
203952AE2-129 C
Solar/Wind Helper
0.442
203946AE2-131 C
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.329
24318705GVG2
50/50
11.512
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
24686205CER G4
Adder
14.71
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
6.152
970153AG2-106 GEN
Solar/Wind Harmer
22.36
970913AG2-568 GEN
Solar/Wind Harmer
12.168
971191AH1-055 GEN
Solar/Wind Harmer
32.44
960911AF2-382 GEN
Solar/Wind Harmer
11.01
972103AH1-617 GEN
Solar/Wind Harmer
29.136
971461AH1-227 GEN
Solar/Wind Harmer
7.367
270346AE1-212 GEN
Solar/Wind Harmer
11.966
957541AF2-048 GEN
Solar/Wind Harmer
2.069
970243AG2-164 GEN
Solar/Wind Harmer
33.441
970519AG2-331 GEN
Solar/Wind Harmer
22.466
970699AG2-449 GEN
Solar/Wind Harmer
14.862
943031AE2-326 GEN
Solar/Wind Harmer
4.718
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
12.017
966571AG1-526 GEN
Solar/Wind Harmer
26.615
970273AG2-179 GEN
Solar/Wind Harmer
4.636
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
5.368
960741AF2-365 GEN
Solar/Wind Harmer
5.892
972167AH1-666 GEN
Solar/Wind Harmer
9.416
339250AF1-203 GEN
Solar/Wind Harmer
0.712
971155AH1-034 GEN
Solar/Wind Harmer
11.743
962251AG1-071 GEN
Solar/Wind Harmer
6.45
970193AG2-126 GEN
Solar/Wind Harmer
17.522
25196008MFTGT1
Adder
1.556
24728705AND G3
Adder
9.226
24728505AND G1
Adder
4.411
970513AG2-328 GEN
Solar/Wind Harmer
20.527
970517AG2-330 GEN
Solar/Wind Harmer
18.618
942481AE2-261 GEN
Solar/Wind Harmer
34.305
25194608D.CRK4
Adder
1.851
274760LEE CO EC;1U
Adder
10.448
274767LEE CO EC;8U
Adder
10.325
25196608WSDLE5
Adder
9.621
972236AH1-702 GEN2
Adder
2.459
274682WAUKEGAN ;7U
Adder
20.129
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
235058AG1-386 C
Solar/Wind Helper
0.436
23750701CROSSCHOOL
Solar/Wind Helper
1.181
964991AG1-363 GEN
Solar/Wind Helper
3.632
202652Y1-033 WT C
Solar/Wind Helper
0.547
238118U2-030_1
Solar/Wind Helper
0.284
254305AE2-115 C
Solar/Wind Helper
0.203
20089126CSLMN_L13
Solar/Wind Helper
0.571
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
203818AF1-086 GEN
Solar/Wind Helper
1.58
24755605MDL-5G
Solar/Wind Harmer
1.072
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.188
957241AF2-018 GEN
Solar/Wind Harmer
7.355
270330AC1-082 GEN2
Solar/Wind Harmer
1.259
270329AC1-082 GEN1
Solar/Wind Harmer
0.741
270399AC1-101 GEN
Solar/Wind Harmer
6.952
270400AC1-102 GEN
Solar/Wind Harmer
6.952
24477305BRIDGE
Adder
0.568
962771AG1-126 GEN
Solar/Wind Harmer
51.279
941621AE2-160 GEN
Adder
4.884
970281AG2-184 GEN
Solar/Wind Harmer
30.593
972143AH1-644 GEN
Solar/Wind Harmer
14.568
971313AH1-133 GEN
Solar/Wind Harmer
14.325
962211AG1-066 GEN
Solar/Wind Harmer
3.356
270132AB1-180 C
Adder
0.166
24734705WLF1G3
Adder
7.759
24734805WLF1G4
Adder
7.759
24734905WLF1G5
Adder
7.759
971061AG2-657 GEN
Solar/Wind Harmer
12.002
971985AH1-537 GEN
Solar/Wind Harmer
23.775
24735105WLF2G1
Adder
7.624
966391AG1-508 GEN
Solar/Wind Harmer
4.457
971981AH1-535 GEN
Solar/Wind Harmer
12.146
965401AG1-405 GEN
Solar/Wind Harmer
6.855
965411AG1-406 GEN
Solar/Wind Harmer
3.076
339211AE2-254 GEN
Solar/Wind Harmer
1.816
970455AG2-298 GEN
Solar/Wind Harmer
7.163
3429211JKCT 2G
Adder
13.952
270367AC2-061_GEN
Solar/Wind Harmer
3.766
972163AH1-664 GEN
Solar/Wind Harmer
11.816
972165AH1-665 GEN
Solar/Wind Harmer
9.453
339243AC2-075 GEN1
Solar/Wind Harmer
0.537
963841AG1-237 GEN
Solar/Wind Harmer
12.629
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386205FR-12G C
Solar/Wind Harmer
4.941
24386405FR-21G C
Solar/Wind Harmer
4.958
24386605FR-22G C
Solar/Wind Harmer
4.958
24387005FR-3G C
Solar/Wind Harmer
4.561
944221AF1-090 GEN
Solar/Wind Harmer
12.589
24690905MDL-1G C
Solar/Wind Harmer
9.207
270180AB1-006 GEN1
Solar/Wind Harmer
8.248
946581AF1-322 GEN
Solar/Wind Harmer
11.733
24691005MDL-2G C
Solar/Wind Harmer
4.241
24697605MDL-3G C
Solar/Wind Harmer
4.228
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
25196508WSDLE4
Adder
9.523
274823ROCKFORD ;21
Adder
21.86
274746AC1-111 G10
Adder
6.26
274744AC1-111 GEN8
Adder
6.26
274775LINCOLN ;6U
Adder
9.447
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241997AF1-093 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.207
238126S14_GEN_1
Solar/Wind Helper
0.669
20092526R32
Solar/Wind Helper
1.095
203961AE2-224 GEN
Solar/Wind Helper
2.258
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
203846AF2-130 C
Solar/Wind Helper
0.42
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
941231AE2-117 GEN
Solar/Wind Helper
0.441
24697905MDL-4G C
Solar/Wind Harmer
1.02
944201AF1-088_MTX
Adder
141.066
957141AF2-008_MTX
Adder
70.533
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
TVALTFEXP_TVA->PJM
CLTF
11.394
NYPJM->LTFIMP_NY
CLTF
5.171
LGEELTFEXP_LGEE->PJM
CLTF
8.351
WECLTFEXP_WEC->PJM
CLTF
4.291
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
6.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.624

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:2.39
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:3.03
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.658
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
972203AH1-686 GEN
Adder
4.44
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270399AC1-101 GEN
Solar/Wind Harmer
7.483
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
970281AG2-184 GEN
Solar/Wind Harmer
32.43
972143AH1-644 GEN
Solar/Wind Harmer
15.443
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
971985AH1-537 GEN
Solar/Wind Harmer
26.909
962211AG1-066 GEN
Solar/Wind Harmer
3.527
24734705WLF1G3
Adder
8.169
24734805WLF1G4
Adder
8.169
24734905WLF1G5
Adder
8.169
24735105WLF2G1
Adder
7.999
966391AG1-508 GEN
Solar/Wind Harmer
4.787
970879AG2-548 GEN
Solar/Wind Harmer
5.647
971981AH1-535 GEN
Solar/Wind Harmer
12.632
270367AC2-061_GEN
Solar/Wind Harmer
3.956
972163AH1-664 GEN
Solar/Wind Harmer
12.214
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
965411AG1-406 GEN
Solar/Wind Harmer
3.11
3429211JKCT 2G
Adder
14.189
339211AE2-254 GEN
Solar/Wind Harmer
1.83
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
252524AE2-267 GEN
Solar/Wind Harmer
1.782
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
25196508WSDLE4
Adder
9.582
270069AE2-166 C O1
Solar/Wind Harmer
3.07
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944031AF1-071 GEN
Solar/Wind Harmer
1.053
944221AF1-090 GEN
Solar/Wind Harmer
11.289
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274823ROCKFORD ;21
Adder
18.572
274746AC1-111 G10
Adder
5.257
274744AC1-111 GEN8
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241997AF1-093 GEN
Solar/Wind Helper
0.245
241982AE2-343 S C
Solar/Wind Helper
0.214
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
203961AE2-224 GEN
Solar/Wind Helper
2.23
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
24289405MTG1
50/50
11.76
243186AF1-051 GEN
50/50
12.611
24318705GVG2
50/50
11.739
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
960001AF2-291 GEN
Solar/Wind Harmer
6.065
24723205RIVRG3
Adder
37.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24686505CER G6
Adder
16.242
971403AH1-188 GEN
Solar/Wind Harmer
24.803
24728305BUCHG2
Adder
6.985
971315AH1-136 GEN
Solar/Wind Harmer
3.105
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971687AH1-348 GEN
Solar/Wind Harmer
1.523
24735205WLF2G2
Adder
7.999
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
970333AG2-219 GEN
Solar/Wind Harmer
38.461
945681AF1-233 GEN
Solar/Wind Harmer
22.966
3429241JKCT 3G
Adder
14.375
971821AH1-427 GEN
Solar/Wind Harmer
12.078
3429421JKCT 10G
Adder
10.046
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339216AC1-074 GEN
Solar/Wind Harmer
2.018
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
339241AF1-083 GEN
Solar/Wind Harmer
1.967
252507AC2-088 GEN
Solar/Wind Harmer
2.122
964901AG1-354 GEN
Solar/Wind Harmer
17.575
962241AG1-070 GEN
Solar/Wind Harmer
5.234
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
270263AC1-001 GEN
Solar/Wind Harmer
1.114
24728605AND G2
Adder
4.036
963741AG1-226 GEN
Solar/Wind Harmer
46.021
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274761LEE CO EC;2U
Adder
8.918
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
274822ROCKFORD ;11
Adder
18.707
25326309TAIT D
Adder
1.04
274828WAUKEGAN ;BP
Adder
10.429
24289405MTG1
50/50
11.76
24318705GVG2
50/50
11.739
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
24686205CER G4
Adder
16.177
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970913AG2-568 GEN
Solar/Wind Harmer
13.469
960911AF2-382 GEN
Solar/Wind Harmer
11.728
957541AF2-048 GEN
Solar/Wind Harmer
2.449
972103AH1-617 GEN
Solar/Wind Harmer
30.886
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
4.651
958171AF2-111 GEN
Solar/Wind Harmer
29.515
339250AF1-203 GEN
Solar/Wind Harmer
0.708
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
962251AG1-071 GEN
Solar/Wind Harmer
6.397
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
25194608D.CRK4
Adder
1.865
25196608WSDLE5
Adder
9.681
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
946181AF1-283 GEN
Solar/Wind Harmer
14.239
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
24728505AND G1
Adder
4.036
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270222AC2-111 GEN
Solar/Wind Harmer
8.539
253415AE1-040 GEN
Solar/Wind Harmer
1.167
942481AE2-261 GEN
Solar/Wind Harmer
30.502
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274760LEE CO EC;1U
Adder
8.918
274767LEE CO EC;8U
Adder
8.813
972236AH1-702 GEN2
Adder
2.091
274682WAUKEGAN ;7U
Adder
16.961
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
235058AG1-386 C
Solar/Wind Helper
0.451
237043AE2-125 C
Solar/Wind Helper
0.173
254305AE2-115 C
Solar/Wind Helper
0.211
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089126CSLMN_L13
Solar/Wind Helper
0.56
20089026BF_G21_K23
Solar/Wind Helper
0.443
964991AG1-363 GEN
Solar/Wind Helper
3.463
238118U2-030_1
Solar/Wind Helper
0.272
203818AF1-086 GEN
Solar/Wind Helper
1.57
238127S14_GEN_2
Solar/Wind Helper
0.64
959441AF2-235 GEN
Solar/Wind Helper
0.22
243186AF1-051 GEN
50/50
12.611
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
971277AH1-098 GEN
Solar/Wind Harmer
5.494
970879AG2-548 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
270583AD2-179 GEN
Solar/Wind Harmer
12.914
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
971125AH1-004 GEN
Solar/Wind Harmer
4.815
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
971485AH1-239 GEN
Solar/Wind Harmer
9.472
252509AD1-136 GEN
Solar/Wind Harmer
0.303
971081AG2-670 GEN
Solar/Wind Harmer
8.855
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
339236AF1-050_GEN
Solar/Wind Harmer
2.132
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25183208HLCRTG
Solar/Wind Harmer
6.95
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
8.581
25194508D.CRK3
Adder
1.604
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
945391AF1-204 GEN
Solar/Wind Harmer
14.686
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
24728805RICHG1
Adder
3.931
24728905RICHG2
Adder
3.931
276916AD2-100_GEN
Solar/Wind Harmer
21.483
276911AD2-131_GEN
Solar/Wind Harmer
4.342
970241AG2-163 GEN
Solar/Wind Harmer
25.567
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274765LEE CO EC;6U
Adder
8.939
274762LEE CO EC;3U
Adder
8.918
274763LEE CO EC;4U
Adder
8.834
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274696ROCKY RD ;4P
Adder
10.757
274695ROCKY RD ;2P
Adder
10.508
274693ROCKY RD ;1P
Adder
10.405
274697ROCKY RD ;3P
Adder
2.855
23652301WDPWR_K20
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.626
241967AE2-285_GEN
Solar/Wind Helper
0.613
241801AE1-079 GEN
Solar/Wind Helper
0.238
241985AE1-237 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.323
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.764
20084626FORWARD
Solar/Wind Helper
0.332
203940AF1-140 C
Solar/Wind Helper
0.368
238120AE2-309 GEN
Solar/Wind Helper
0.4
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
20303426NA_O38_P22
Solar/Wind Helper
0.919
203853AF1-134 C O1
Solar/Wind Helper
0.443
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
23751201ROTHROCK
Solar/Wind Helper
0.699
235054AD2-180 GEN
Solar/Wind Helper
1.616
23562501BACKB
Solar/Wind Helper
0.85
20089226LOOKOUT
Solar/Wind Helper
0.545
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
964201AG1-281 GEN
Solar/Wind Helper
0.449
970149AG2-104 GEN
Solar/Wind Harmer
20.717
944201AF1-088_MTX
Adder
131.041
957141AF2-008_MTX
Adder
65.52
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
TVALTFEXP_TVA->PJM
CLTF
11.299
NYPJM->LTFIMP_NY
CLTF
5.029
LGEELTFEXP_LGEE->PJM
CLTF
8.22
WECLTFEXP_WEC->PJM
CLTF
3.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
7.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
MECLTFEXP_MEC->PJM
CLTF
16.832
SIGELTFEXP_SIGE->PJM
CLTF
0.595

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.672
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
972203AH1-686 GEN
Adder
4.469
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270399AC1-101 GEN
Solar/Wind Harmer
7.536
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
970281AG2-184 GEN
Solar/Wind Harmer
32.691
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
270214AC2-123 GEN
Solar/Wind Harmer
3.243
971277AH1-098 GEN
Solar/Wind Harmer
5.544
970879AG2-548 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
5.701
270583AD2-179 GEN
Solar/Wind Harmer
13.038
24289405MTG1
50/50
11.814
243186AF1-051 GEN
50/50
12.674
24318705GVG2
50/50
11.798
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
960001AF2-291 GEN
Solar/Wind Harmer
6.103
24723205RIVRG3
Adder
37.324
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24686505CER G6
Adder
16.345
971403AH1-188 GEN
Solar/Wind Harmer
24.977
24728305BUCHG2
Adder
7.041
971315AH1-136 GEN
Solar/Wind Harmer
3.129
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971687AH1-348 GEN
Solar/Wind Harmer
1.535
24735205WLF2G2
Adder
8.071
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
970333AG2-219 GEN
Solar/Wind Harmer
38.852
945681AF1-233 GEN
Solar/Wind Harmer
23.2
3429241JKCT 3G
Adder
14.522
971821AH1-427 GEN
Solar/Wind Harmer
12.202
3429421JKCT 10G
Adder
10.15
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339216AC1-074 GEN
Solar/Wind Harmer
2.039
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
339241AF1-083 GEN
Solar/Wind Harmer
1.988
252507AC2-088 GEN
Solar/Wind Harmer
2.144
964901AG1-354 GEN
Solar/Wind Harmer
17.761
962241AG1-070 GEN
Solar/Wind Harmer
5.29
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
270263AC1-001 GEN
Solar/Wind Harmer
1.127
24728605AND G2
Adder
4.084
963741AG1-226 GEN
Solar/Wind Harmer
46.579
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
972143AH1-644 GEN
Solar/Wind Harmer
15.567
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
971985AH1-537 GEN
Solar/Wind Harmer
27.131
962211AG1-066 GEN
Solar/Wind Harmer
3.557
24734705WLF1G3
Adder
8.24
24734805WLF1G4
Adder
8.24
24734905WLF1G5
Adder
8.24
24735105WLF2G1
Adder
8.071
966391AG1-508 GEN
Solar/Wind Harmer
4.83
970879AG2-548 GEN
Solar/Wind Harmer
5.701
971981AH1-535 GEN
Solar/Wind Harmer
12.756
270367AC2-061_GEN
Solar/Wind Harmer
3.995
972163AH1-664 GEN
Solar/Wind Harmer
12.338
972165AH1-665 GEN
Solar/Wind Harmer
9.871
965401AG1-405 GEN
Solar/Wind Harmer
7.001
965411AG1-406 GEN
Solar/Wind Harmer
3.142
3429211JKCT 2G
Adder
14.334
339211AE2-254 GEN
Solar/Wind Harmer
1.849
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
252524AE2-267 GEN
Solar/Wind Harmer
1.801
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
25196508WSDLE4
Adder
9.688
270069AE2-166 C O1
Solar/Wind Harmer
3.104
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944031AF1-071 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
11.424
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274823ROCKFORD ;21
Adder
18.813
274746AC1-111 G10
Adder
5.326
274744AC1-111 GEN8
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241997AF1-093 GEN
Solar/Wind Helper
0.242
241982AE2-343 S C
Solar/Wind Helper
0.211
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
238126S14_GEN_1
Solar/Wind Helper
0.631
203961AE2-224 GEN
Solar/Wind Helper
2.198
20091526CHSTN_FL
Solar/Wind Helper
0.532
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274761LEE CO EC;2U
Adder
9.033
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
274822ROCKFORD ;11
Adder
18.951
25326309TAIT D
Adder
1.054
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
23751201ROTHROCK
Solar/Wind Helper
0.69
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
20089226LOOKOUT
Solar/Wind Helper
0.537
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
235531U2-073 GEN
Solar/Wind Helper
2.519
20094526CT_V3-030
Solar/Wind Helper
0.433
964201AG1-281 GEN
Solar/Wind Helper
0.442
970149AG2-104 GEN
Solar/Wind Harmer
20.97
24289405MTG1
50/50
11.814
24318705GVG2
50/50
11.798
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
24686205CER G4
Adder
16.28
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970913AG2-568 GEN
Solar/Wind Harmer
13.568
960911AF2-382 GEN
Solar/Wind Harmer
11.821
957541AF2-048 GEN
Solar/Wind Harmer
2.468
972103AH1-617 GEN
Solar/Wind Harmer
31.134
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
4.7
958171AF2-111 GEN
Solar/Wind Harmer
29.825
339250AF1-203 GEN
Solar/Wind Harmer
0.715
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
962251AG1-071 GEN
Solar/Wind Harmer
6.465
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
25194608D.CRK4
Adder
1.886
25196608WSDLE5
Adder
9.788
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
24728505AND G1
Adder
4.084
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
253415AE1-040 GEN
Solar/Wind Harmer
1.181
942481AE2-261 GEN
Solar/Wind Harmer
30.873
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274760LEE CO EC;1U
Adder
9.033
274767LEE CO EC;8U
Adder
8.927
972236AH1-702 GEN2
Adder
2.118
274682WAUKEGAN ;7U
Adder
17.184
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
235058AG1-386 C
Solar/Wind Helper
0.446
237043AE2-125 C
Solar/Wind Helper
0.171
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089126CSLMN_L13
Solar/Wind Helper
0.552
20089026BF_G21_K23
Solar/Wind Helper
0.437
964991AG1-363 GEN
Solar/Wind Helper
3.415
238118U2-030_1
Solar/Wind Helper
0.268
203818AF1-086 GEN
Solar/Wind Helper
1.548
238127S14_GEN_2
Solar/Wind Helper
0.631
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
971125AH1-004 GEN
Solar/Wind Harmer
4.864
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
971485AH1-239 GEN
Solar/Wind Harmer
9.571
252509AD1-136 GEN
Solar/Wind Harmer
0.306
971081AG2-670 GEN
Solar/Wind Harmer
8.948
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970653AG2-424 GEN
Solar/Wind Harmer
2.076
339236AF1-050_GEN
Solar/Wind Harmer
2.155
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25183208HLCRTG
Solar/Wind Harmer
7.025
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
25194408D.CRK1
Adder
8.675
25194508D.CRK3
Adder
1.622
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
945391AF1-204 GEN
Solar/Wind Harmer
14.859
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
24728805RICHG1
Adder
3.978
24728905RICHG2
Adder
3.978
276916AD2-100_GEN
Solar/Wind Harmer
21.743
276911AD2-131_GEN
Solar/Wind Harmer
4.394
970241AG2-163 GEN
Solar/Wind Harmer
25.877
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274765LEE CO EC;6U
Adder
9.055
274762LEE CO EC;3U
Adder
9.033
274763LEE CO EC;4U
Adder
8.948
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
274696ROCKY RD ;4P
Adder
10.898
274695ROCKY RD ;2P
Adder
10.646
274693ROCKY RD ;1P
Adder
10.542
274697ROCKY RD ;3P
Adder
2.892
23652301WDPWR_K20
Solar/Wind Helper
0.138
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
241967AE2-285_GEN
Solar/Wind Helper
0.605
241801AE1-079 GEN
Solar/Wind Helper
0.235
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.291
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.754
20084626FORWARD
Solar/Wind Helper
0.327
203940AF1-140 C
Solar/Wind Helper
0.363
238120AE2-309 GEN
Solar/Wind Helper
0.394
944201AF1-088_MTX
Adder
132.484
957141AF2-008_MTX
Adder
66.242
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
TVALTFEXP_TVA->PJM
CLTF
11.425
NYPJM->LTFIMP_NY
CLTF
4.949
LGEELTFEXP_LGEE->PJM
CLTF
8.306
WECLTFEXP_WEC->PJM
CLTF
3.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CPLELTFEXP_CPLE->PJM
CLTF
7.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
MECLTFEXP_MEC->PJM
CLTF
17.041
SIGELTFEXP_SIGE->PJM
CLTF
0.602

Details for 05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o 34541 34553_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line
Contingency Name:
34541 34553_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.75 %
Rating:257.0 MVA
Rating Type:B
MVA to Mitigate:258.94
MW Contribution:1.71
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
7.682
972165AH1-665 GEN
Solar/Wind Harmer
6.145
339243AC2-075 GEN1
Solar/Wind Harmer
0.209
3429211JKCT 2G
Adder
4.521
270367AC2-061_GEN
Solar/Wind Helper
3.208
945681AF1-233 GEN
Solar/Wind Harmer
14.164
339216AC1-074 GEN
Solar/Wind Harmer
0.772
3429421JKCT 10G
Adder
3.262
3429241JKCT 3G
Adder
4.58
972167AH1-666 GEN
Solar/Wind Harmer
6.002
958171AF2-111 GEN
Solar/Wind Harmer
14.988
3429391JKCT 9G
Adder
3.262
972273AH1-721 GEN
Adder
15.922
270186AC1-089 GEN
Solar/Wind Harmer
36.77
972043AH1-570 GEN
Solar/Wind Harmer
1.707
972045AH1-571 GEN
Solar/Wind Harmer
1.365
339221AD2-048_GEN
Solar/Wind Harmer
1.015
960161AF2-307 GEN
Solar/Wind Harmer
3.397
962581AG1-107 GEN
Solar/Wind Helper
1.757
961491AF2-440 GEN
Solar/Wind Helper
0.072
950051AG9-018
External Queue
5.956659317016602
950041AG9-017
External Queue
14.810466766357422
LAGNLTFEXP_LAGN->PJM
CLTF
0.97
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.763
TVALTFEXP_TVA->PJM
CLTF
0.588
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.87
WECLTFEXP_WEC->PJM
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.667
MECLTFEXP_MEC->PJM
CLTF
0.437
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2404.66
MW Contribution:2.12
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.126
24802806KYGER 2HP
50/50
4.102
24802906KYGER 2LP
50/50
2.412
252509AD1-136 GEN
Solar/Wind Harmer
0.295
25183208HLCRTG
Solar/Wind Harmer
6.611
252519AF1-045_GEN
Solar/Wind Harmer
6.54
252516AE2-318_GEN
Solar/Wind Harmer
4.989
25194408D.CRK1
Adder
7.904
25194508D.CRK3
Adder
1.478
253317AC1-085 GEN4
Solar/Wind Harmer
8.546
253394AE2-221_GEN
Solar/Wind Harmer
4.374
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
270186AC1-089 GEN
Solar/Wind Harmer
5.453
970235AG2-159 GEN
Solar/Wind Harmer
3.57
970235AG2-159 GEN
Solar/Wind Harmer
2.18
962581AG1-107 GEN
Solar/Wind Harmer
4.438
961491AF2-440 GEN
Solar/Wind Harmer
1.844
339221AD2-048_GEN
Solar/Wind Harmer
1.337
972043AH1-570 GEN
Solar/Wind Harmer
2.119
972045AH1-571 GEN
Solar/Wind Harmer
1.695
971125AH1-004 GEN
Solar/Wind Harmer
3.302
970107AG2-081 GEN
Solar/Wind Harmer
2.476
253370AE2-315 SEC1
Adder
1.653
24728805RICHG1
Adder
3.025
24728905RICHG2
Adder
3.025
25322209TAIT E
Adder
7.801
25322209TAIT E
Adder
7.626
25326109MON D
Adder
1.023
24379505HDWTR1G C
Solar/Wind Harmer
5.961
270209AC1-174_GEN
Solar/Wind Harmer
4.207
926881AC1-175 GEN
Solar/Wind Harmer
4.207
942891AE2-308 GEN
Solar/Wind Harmer
7.431
270383AD1-128 GEN
Solar/Wind Harmer
4.52
970883AG2-550 GEN
Solar/Wind Harmer
7.178
970885AG2-551 GEN
Solar/Wind Harmer
1.669
970825AG2-519 GEN
Solar/Wind Harmer
7.36
960161AF2-307 GEN
Solar/Wind Harmer
4.47
960441AF2-335 GEN
Solar/Wind Harmer
6.942
247621Y3-024
Adder
0.165
964611AG1-324 GEN
Solar/Wind Harmer
0.799
964611AG1-324 GEN
Solar/Wind Harmer
0.355
270201AC2-176 GEN
Solar/Wind Harmer
3.455
270599AE1-208 GEN
Solar/Wind Harmer
5.434
270031AE2-169
Solar/Wind Harmer
5.434
964571AG1-320 GEN
Solar/Wind Harmer
5.336
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.078
970653AG2-424 GEN
Solar/Wind Harmer
3.01
970653AG2-424 GEN
Solar/Wind Harmer
1.088
942221AE2-234 GEN
Solar/Wind Harmer
0.447
270444AC2-157 GEN1
Solar/Wind Harmer
3.342
945391AF1-204 GEN
Solar/Wind Harmer
8.332
970239AG2-162 GEN
Solar/Wind Harmer
6.523
970241AG2-163 GEN
Solar/Wind Harmer
14.458
25326509SID D
Adder
0.758
971081AG2-670 GEN
Solar/Wind Harmer
4.267
966841AG1-555 GEN
Solar/Wind Harmer
1.422
274770LINCOLN ;1U
Adder
4.435
274771LINCOLN ;2U
Adder
4.435
972259AH1-714 GEN
Adder
10.005
274803UNIV PARK;6U
Adder
3.054
274674JOLIET 9 ;6U
Adder
8.062
274808UNIV PK N;4U
Adder
2.611
237033AB1-150 GEN
Solar/Wind Helper
0.408
270518AE2-148 GEN
Solar/Wind Harmer
6.451
24803406KYGER 5HP
50/50
4.08
24803206KYGER 4HP
50/50
4.077
252507AC2-088 GEN
Solar/Wind Harmer
2.066
25196808ZIMRHP
Adder
80.623
25194608D.CRK4
Adder
1.718
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
946171AF1-282 GEN
Solar/Wind Harmer
10.203
25196008MFTGT1
Adder
1.392
945681AF1-233 GEN
Solar/Wind Harmer
17.49
339216AC1-074 GEN
Solar/Wind Harmer
1.487
270263AC1-001 GEN
Solar/Wind Harmer
0.884
253370AE2-315 SEC1
Adder
1.653
253371AE2-315 SEC2
Adder
1.564
943111AE2-339 GEN
Solar/Wind Harmer
0.716
25326309TAIT D
Adder
0.876
960071AF2-298 GEN
Solar/Wind Harmer
3.959
3429421JKCT 10G
Adder
6.489
3429241JKCT 3G
Adder
8.962
942081AE2-220 GEN
Solar/Wind Harmer
4.82
270239V3-007_GEN1
Solar/Wind Harmer
1.297
270005AE1-210 C O1
Solar/Wind Harmer
3.865
965031AG1-367 GEN
Solar/Wind Harmer
7.071
24728605AND G2
Adder
2.691
247536S-71 GEN
Solar/Wind Harmer
2.823
970825AG2-519 GEN
Solar/Wind Harmer
1.642
971565AH1-281 GEN
Solar/Wind Harmer
1.372
945371AF1-202 GEN
Solar/Wind Harmer
4.682
276903AD2-071 C
Solar/Wind Harmer
6.687
270032AE2-172
Solar/Wind Harmer
3.071
958861AF2-177 GEN
Solar/Wind Harmer
7.167
971821AH1-427 GEN
Solar/Wind Harmer
6.495
965651AG1-433 GEN
Solar/Wind Harmer
3.539
970291AG2-192 GEN
Solar/Wind Harmer
0.841
253343AC1-166 GEN
Solar/Wind Harmer
0.666
253325AC1-069 GEN
Solar/Wind Harmer
0.642
970091AG2-072 GEN
Adder
46.366
270445AC2-157 GEN2
Solar/Wind Harmer
3.342
970333AG2-219 GEN
Solar/Wind Harmer
18.718
963741AG1-226 GEN
Solar/Wind Harmer
26.024
339241AF1-083 GEN
Solar/Wind Harmer
0.96
24385905FR-11G C
Solar/Wind Harmer
4.71
24387305FR-4G C
Solar/Wind Harmer
2.879
24791305MDL-5G
Solar/Wind Harmer
1.348
274773LINCOLN ;4U
Adder
4.435
274774LINCOLN ;5U
Adder
4.435
274732ELWOOD EC;7P
Adder
8.613
274801UNIV PARK;4U
Adder
3.055
274723RIVER EC ;12
Adder
9.381
274674JOLIET 9 ;6U
Adder
8.062
274812UNIV PK N;8U
Adder
2.622
274751CRETE EC ;1U
Adder
4.312
274754CRETE EC ;4U
Adder
4.312
960001AF2-291 GEN
Solar/Wind Helper
1.73
270331AC1-082 GEN3
Solar/Wind Helper
0.207
24802606KYGER 1HP
50/50
4.15
24802706KYGER 1LP
50/50
2.436
24803506KYGER 5LP
50/50
2.379
25016408BKJDB1
50/50
0.28
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
49.695
252524AE2-267 GEN
Solar/Wind Harmer
1.648
25196408WSDLE3
Adder
9.218
25196308WSDLE2
Adder
9.138
25196208WSDLE1
Adder
9.115
25196708WSDLE6
Adder
9.092
25196508WSDLE4
Adder
8.863
25196108MFTGT2
Adder
1.534
25196108MFTGT2
Adder
1.425
972163AH1-664 GEN
Solar/Wind Harmer
9.175
972165AH1-665 GEN
Solar/Wind Harmer
7.34
270367AC2-061_GEN
Solar/Wind Harmer
2.878
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270340AC2-060 GEN
Solar/Wind Harmer
2.625
944031AF1-071 GEN
Solar/Wind Harmer
0.86
270269AC2-059
Solar/Wind Harmer
7.894
253372AE2-315 SEC3
Adder
1.564
253372AE2-315 SEC3
Adder
1.564
25306009OHH W.
Adder
2.347
253349AC2-067 GEN
Solar/Wind Harmer
3.985
253400AC2-068 GEN
Solar/Wind Harmer
1.602
3429211JKCT 2G
Adder
8.846
270240V3-007_GEN2
Solar/Wind Harmer
4.664
971673AH1-337 GEN
Solar/Wind Harmer
3.435
971029AG2-637 GEN
Solar/Wind Harmer
11.093
970689AG2-444 GEN
Solar/Wind Harmer
12.048
270543AE2-219 C
Solar/Wind Harmer
3.676
970115AG2-085 GEN
Solar/Wind Harmer
2.777
24725505WLD G2 C
Solar/Wind Harmer
2.7
24699105WLD G1 C
Solar/Wind Harmer
2.668
961761AG1-017 GEN
Solar/Wind Harmer
0.288
945581AF1-223 GEN
Solar/Wind Harmer
3.044
241972AD1-140 GEN
Solar/Wind Harmer
2.991
970455AG2-298 GEN
Solar/Wind Harmer
3.991
270432AC2-029 GEN
Solar/Wind Harmer
4.641
339211AE2-254 GEN
Solar/Wind Harmer
1
270594AE1-207 GEN
Solar/Wind Harmer
9.705
965101AG1-375 GEN
Solar/Wind Harmer
6.557
958711AF2-162 GEN
Solar/Wind Harmer
0.655
965461AG1-414 GEN
Solar/Wind Harmer
1.467
970289AG2-191 GEN
Solar/Wind Harmer
1.229
270024AE2-089 GEN
Solar/Wind Harmer
2.954
24729505KEY G4
Adder
4.041
963841AG1-237 GEN
Solar/Wind Harmer
6.258
965401AG1-405 GEN
Solar/Wind Harmer
3.232
965411AG1-406 GEN
Solar/Wind Harmer
1.451
24386205FR-12G C
Solar/Wind Harmer
2.428
24386405FR-21G C
Solar/Wind Harmer
2.437
24386605FR-22G C
Solar/Wind Harmer
2.437
24387005FR-3G C
Solar/Wind Harmer
2.242
963791AG1-232 GEN
Solar/Wind Harmer
7.567
24690905MDL-1G C
Solar/Wind Harmer
4.488
270180AB1-006 GEN1
Solar/Wind Harmer
4.02
946581AF1-322 GEN
Solar/Wind Harmer
5.719
24691005MDL-2G C
Solar/Wind Harmer
2.067
24697605MDL-3G C
Solar/Wind Harmer
2.061
24697905MDL-4G C
Solar/Wind Harmer
1.283
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
274775LINCOLN ;6U
Adder
4.435
274776LINCOLN ;7U
Adder
4.435
274777LINCOLN ;8U
Adder
4.435
972227AH1-698 GEN1
Adder
1.369
274731ELWOOD EC;2P
Adder
8.613
274733ELWOOD EC;3P
Adder
8.613
274735ELWOOD EC;4P
Adder
8.613
274728ELWOOD EC;5P
Adder
8.613
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.063
274814UNIV PK N;0U
Adder
2.645
274807UNIV PK N;3U
Adder
2.64
274805UNIV PK N;1U
Adder
2.628
274811UNIV PK N;7U
Adder
2.622
274687WILL CNTY;4U
Adder
14.622
274687WILL CNTY;4U
Adder
14.622
274675JOLIET 29;7U
Adder
4.98
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.208
24803106KYGER 3LP
50/50
2.429
24803306KYGER 4LP
50/50
2.379
971191AH1-055 GEN
Solar/Wind Harmer
84.382
25194608D.CRK4
Adder
1.718
25196608WSDLE5
Adder
8.955
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.546
253433AC1-085 GEN1
Solar/Wind Harmer
5.425
946181AF1-283 GEN
Solar/Wind Harmer
13.263
25196008MFTGT1
Adder
1.348
958171AF2-111 GEN
Solar/Wind Harmer
24.756
972167AH1-666 GEN
Solar/Wind Harmer
7.453
253406AD2-031_GEN
Solar/Wind Harmer
1.157
972173AH1-669 GEN
Solar/Wind Harmer
4.43
270222AC2-111 GEN
Solar/Wind Harmer
6.98
270273AD2-016 GEN
Solar/Wind Harmer
2.257
253415AE1-040 GEN
Solar/Wind Harmer
0.952
253303V4-073 C
Solar/Wind Harmer
0.096
253370AE2-315 SEC1
Adder
1.653
253371AE2-315 SEC2
Adder
1.564
270356AE2-297 GEN
Solar/Wind Harmer
3.556
3429391JKCT 9G
Adder
6.489
270437AC2-090 C
Solar/Wind Harmer
4.209
970093AG2-073 GEN
Solar/Wind Harmer
7.103
958821AF2-173 GEN
Solar/Wind Harmer
9.9
270004AE1-209 GEN
Solar/Wind Harmer
3.865
24728705AND G3
Adder
5.629
24728505AND G1
Adder
2.691
946031AF1-268 GEN
Solar/Wind Harmer
5.792
966571AG1-526 GEN
Solar/Wind Harmer
15.251
962031AG1-047 GEN
Solar/Wind Harmer
2.032
957741AF2-068 GEN
Solar/Wind Harmer
10.082
970289AG2-191 GEN
Solar/Wind Harmer
0.497
970291AG2-192 GEN
Solar/Wind Harmer
0.451
247642Z2-115 C
Solar/Wind Harmer
0.041
971617AH1-308 GEN
Solar/Wind Harmer
3.659
944531AF1-118 GEN
Solar/Wind Harmer
21.491
253338AC1-165 GEN
Solar/Wind Harmer
0.666
253333AC1-068 GEN
Solar/Wind Harmer
0.642
970193AG2-126 GEN
Solar/Wind Harmer
8.968
970243AG2-164 GEN
Solar/Wind Harmer
15.315
970519AG2-331 GEN
Solar/Wind Harmer
10.289
970699AG2-449 GEN
Solar/Wind Harmer
6.806
24755605MDL-5G
Solar/Wind Harmer
1.348
970781AG2-491 GEN
Solar/Wind Harmer
5.589
972273AH1-721 GEN
Adder
43.969
274772LINCOLN ;3U
Adder
4.435
972228AH1-698 GEN2
Adder
1.944
274729ELWOOD EC;1P
Adder
8.613
274730ELWOOD EC;6P
Adder
8.613
274734ELWOOD EC;8P
Adder
8.613
274736ELWOOD EC;9P
Adder
8.613
274800UNIV PARK;3U
Adder
3.055
972038AH1-567 GEN2
Adder
0.191
274802UNIV PARK;5U
Adder
3.054
274826FISK ;BP
Adder
5.732
274724RIVER EC ;11
Adder
9.271
274752CRETE EC ;2U
Adder
4.312
274753CRETE EC ;3U
Adder
4.312
235780M24_1
Solar/Wind Helper
1.012
944201AF1-088_MTX
Adder
69.584
957141AF2-008_MTX
Adder
34.792
LAGNLTFEXP_LAGN->PJM
CLTF
6.68
TVALTFEXP_TVA->PJM
CLTF
3.156
NYPJM->LTFIMP_NY
CLTF
1.706
LGEELTFEXP_LGEE->PJM
CLTF
5.222
WECLTFEXP_WEC->PJM
CLTF
1.971
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.703
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.86
MECLTFEXP_MEC->PJM
CLTF
8.255
SIGELTFEXP_SIGE->PJM
CLTF
0.338

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.73 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2382.87
MW Contribution:2.09
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.129
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252509AD1-136 GEN
Solar/Wind Harmer
0.291
25183208HLCRTG
Solar/Wind Harmer
6.511
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
4.911
25194408D.CRK1
Adder
7.772
25194508D.CRK3
Adder
1.453
253317AC1-085 GEN4
Solar/Wind Harmer
8.395
253394AE2-221_GEN
Solar/Wind Harmer
4.283
253398AE2-221_GEN2
Solar/Wind Harmer
4.283
270186AC1-089 GEN
Solar/Wind Harmer
5.375
970235AG2-159 GEN
Solar/Wind Harmer
3.519
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
4.366
961491AF2-440 GEN
Solar/Wind Harmer
1.815
339221AD2-048_GEN
Solar/Wind Harmer
1.319
972043AH1-570 GEN
Solar/Wind Harmer
2.09
972045AH1-571 GEN
Solar/Wind Harmer
1.672
971125AH1-004 GEN
Solar/Wind Harmer
3.256
970107AG2-081 GEN
Solar/Wind Harmer
2.442
253370AE2-315 SEC1
Adder
1.603
24728805RICHG1
Adder
2.949
24728905RICHG2
Adder
2.949
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
5.802
270209AC1-174_GEN
Solar/Wind Harmer
4.094
926881AC1-175 GEN
Solar/Wind Harmer
4.094
942891AE2-308 GEN
Solar/Wind Harmer
7.33
270383AD1-128 GEN
Solar/Wind Harmer
4.391
970883AG2-550 GEN
Solar/Wind Harmer
6.941
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960161AF2-307 GEN
Solar/Wind Harmer
4.414
970825AG2-519 GEN
Solar/Wind Harmer
7.137
960441AF2-335 GEN
Solar/Wind Harmer
6.731
247621Y3-024
Adder
0.159
964611AG1-324 GEN
Solar/Wind Harmer
0.771
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
3.329
270599AE1-208 GEN
Solar/Wind Harmer
5.257
270031AE2-169
Solar/Wind Harmer
5.257
964571AG1-320 GEN
Solar/Wind Harmer
5.25
944541AF1-119 GEN
Solar/Wind Harmer
2.619
960971AF2-388 GEN
Solar/Wind Harmer
6.834
970653AG2-424 GEN
Solar/Wind Harmer
2.963
970653AG2-424 GEN
Solar/Wind Harmer
1.071
942221AE2-234 GEN
Solar/Wind Harmer
0.429
270444AC2-157 GEN1
Solar/Wind Harmer
3.266
945391AF1-204 GEN
Solar/Wind Harmer
8.111
970239AG2-162 GEN
Solar/Wind Harmer
6.391
970241AG2-163 GEN
Solar/Wind Harmer
14.036
971081AG2-670 GEN
Solar/Wind Harmer
4.204
966841AG1-555 GEN
Solar/Wind Harmer
1.378
339236AF1-050_GEN
Solar/Wind Harmer
0.978
945421AF1-207 GEN
Solar/Wind Harmer
7.543
25326509SID D
Adder
0.697
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
972259AH1-714 GEN
Adder
9.649
274674JOLIET 9 ;6U
Adder
7.776
274803UNIV PARK;6U
Adder
2.944
237033AB1-150 GEN
Solar/Wind Helper
0.4
957841AF2-078 GEN
Solar/Wind Harmer
2.252
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.08
252507AC2-088 GEN
Solar/Wind Harmer
2.039
25196808ZIMRHP
Adder
79.423
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
946171AF1-282 GEN
Solar/Wind Harmer
10.022
25196008MFTGT1
Adder
1.369
945681AF1-233 GEN
Solar/Wind Harmer
17.256
339216AC1-074 GEN
Solar/Wind Harmer
1.467
270263AC1-001 GEN
Solar/Wind Harmer
0.873
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
943111AE2-339 GEN
Solar/Wind Harmer
0.706
25326309TAIT D
Adder
0.846
3429421JKCT 10G
Adder
6.399
960071AF2-298 GEN
Solar/Wind Harmer
3.823
3429241JKCT 3G
Adder
8.84
942081AE2-220 GEN
Solar/Wind Harmer
4.691
270239V3-007_GEN1
Solar/Wind Harmer
1.263
270005AE1-210 C O1
Solar/Wind Harmer
3.751
965031AG1-367 GEN
Solar/Wind Harmer
6.864
24728605AND G2
Adder
2.624
970825AG2-519 GEN
Solar/Wind Harmer
1.592
971565AH1-281 GEN
Solar/Wind Harmer
1.351
247536S-71 GEN
Solar/Wind Harmer
2.726
945371AF1-202 GEN
Solar/Wind Harmer
4.531
276903AD2-071 C
Solar/Wind Harmer
6.489
971821AH1-427 GEN
Solar/Wind Harmer
6.405
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
6.924
970291AG2-192 GEN
Solar/Wind Harmer
0.815
965651AG1-433 GEN
Solar/Wind Harmer
3.417
970091AG2-072 GEN
Adder
45.505
253343AC1-166 GEN
Solar/Wind Harmer
0.642
253325AC1-069 GEN
Solar/Wind Harmer
0.619
270445AC2-157 GEN2
Solar/Wind Harmer
3.266
970333AG2-219 GEN
Solar/Wind Harmer
18.34
339241AF1-083 GEN
Solar/Wind Harmer
0.945
963741AG1-226 GEN
Solar/Wind Harmer
25.264
24385905FR-11G C
Solar/Wind Harmer
4.564
24387305FR-4G C
Solar/Wind Harmer
2.79
24791305MDL-5G
Solar/Wind Harmer
1.304
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
274801UNIV PARK;4U
Adder
2.945
274676JOLIET 29;8U
Adder
15.482
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.205
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
25016408BKJDB1
50/50
0.276
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
49.57
252524AE2-267 GEN
Solar/Wind Harmer
1.62
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196508WSDLE4
Adder
8.713
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
972163AH1-664 GEN
Solar/Wind Harmer
9.052
972165AH1-665 GEN
Solar/Wind Harmer
7.242
270367AC2-061_GEN
Solar/Wind Harmer
2.835
339243AC2-075 GEN1
Solar/Wind Harmer
0.397
270340AC2-060 GEN
Solar/Wind Harmer
2.578
944031AF1-071 GEN
Solar/Wind Harmer
0.84
270269AC2-059
Solar/Wind Harmer
7.774
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
253349AC2-067 GEN
Solar/Wind Harmer
3.854
253400AC2-068 GEN
Solar/Wind Harmer
1.55
3429211JKCT 2G
Adder
8.726
270240V3-007_GEN2
Solar/Wind Harmer
4.539
970689AG2-444 GEN
Solar/Wind Harmer
11.825
971673AH1-337 GEN
Solar/Wind Harmer
3.329
971029AG2-637 GEN
Solar/Wind Harmer
10.743
270543AE2-219 C
Solar/Wind Harmer
3.554
970115AG2-085 GEN
Solar/Wind Harmer
2.693
24725505WLD G2 C
Solar/Wind Harmer
2.621
24699105WLD G1 C
Solar/Wind Harmer
2.59
970455AG2-298 GEN
Solar/Wind Harmer
3.93
339211AE2-254 GEN
Solar/Wind Harmer
0.986
945581AF1-223 GEN
Solar/Wind Harmer
2.945
270432AC2-029 GEN
Solar/Wind Harmer
4.535
961761AG1-017 GEN
Solar/Wind Harmer
0.277
270594AE1-207 GEN
Solar/Wind Harmer
9.407
241972AD1-140 GEN
Solar/Wind Harmer
2.855
965101AG1-375 GEN
Solar/Wind Harmer
6.335
965461AG1-414 GEN
Solar/Wind Harmer
1.422
970289AG2-191 GEN
Solar/Wind Harmer
1.191
958711AF2-162 GEN
Solar/Wind Harmer
0.632
270024AE2-089 GEN
Solar/Wind Harmer
2.831
24729505KEY G4
Adder
3.892
965401AG1-405 GEN
Solar/Wind Harmer
3.19
965411AG1-406 GEN
Solar/Wind Harmer
1.432
963841AG1-237 GEN
Solar/Wind Harmer
6.07
24386205FR-12G C
Solar/Wind Harmer
2.353
24386405FR-21G C
Solar/Wind Harmer
2.362
24386605FR-22G C
Solar/Wind Harmer
2.362
24387005FR-3G C
Solar/Wind Harmer
2.172
24690905MDL-1G C
Solar/Wind Harmer
4.343
270180AB1-006 GEN1
Solar/Wind Harmer
3.891
946581AF1-322 GEN
Solar/Wind Harmer
5.534
24691005MDL-2G C
Solar/Wind Harmer
2.001
24697605MDL-3G C
Solar/Wind Harmer
1.994
24697905MDL-4G C
Solar/Wind Harmer
1.242
270181AB1-006 GEN2
Solar/Wind Harmer
0.387
274775LINCOLN ;6U
Adder
4.276
274776LINCOLN ;7U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
972227AH1-698 GEN1
Adder
1.32
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
274735ELWOOD EC;4P
Adder
8.308
274728ELWOOD EC;5P
Adder
8.308
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.916
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.206
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
84.399
25194608D.CRK4
Adder
1.69
25196608WSDLE5
Adder
8.803
252510AF1-249 C
Solar/Wind Harmer
0.429
253316AC1-085 GEN3
Solar/Wind Harmer
8.395
253433AC1-085 GEN1
Solar/Wind Harmer
5.329
946181AF1-283 GEN
Solar/Wind Harmer
13.029
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
24.417
972167AH1-666 GEN
Solar/Wind Harmer
7.353
253406AD2-031_GEN
Solar/Wind Harmer
1.133
972173AH1-669 GEN
Solar/Wind Harmer
4.368
270222AC2-111 GEN
Solar/Wind Harmer
6.813
270273AD2-016 GEN
Solar/Wind Harmer
2.223
253415AE1-040 GEN
Solar/Wind Harmer
0.933
253303V4-073 C
Solar/Wind Harmer
0.093
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
3429391JKCT 9G
Adder
6.399
270356AE2-297 GEN
Solar/Wind Harmer
3.47
270437AC2-090 C
Solar/Wind Harmer
4.096
970093AG2-073 GEN
Solar/Wind Harmer
7.006
958821AF2-173 GEN
Solar/Wind Harmer
9.609
270004AE1-209 GEN
Solar/Wind Harmer
3.751
24728705AND G3
Adder
5.489
24728505AND G1
Adder
2.624
966571AG1-526 GEN
Solar/Wind Harmer
15.039
946031AF1-268 GEN
Solar/Wind Harmer
5.61
962031AG1-047 GEN
Solar/Wind Harmer
1.957
957741AF2-068 GEN
Solar/Wind Harmer
9.713
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.039
971617AH1-308 GEN
Solar/Wind Harmer
3.507
944531AF1-118 GEN
Solar/Wind Harmer
20.676
253338AC1-165 GEN
Solar/Wind Harmer
0.642
253333AC1-068 GEN
Solar/Wind Harmer
0.619
970193AG2-126 GEN
Solar/Wind Harmer
8.731
970243AG2-164 GEN
Solar/Wind Harmer
15.006
970519AG2-331 GEN
Solar/Wind Harmer
10.081
970699AG2-449 GEN
Solar/Wind Harmer
6.669
960741AF2-365 GEN
Solar/Wind Harmer
2.727
24755605MDL-5G
Solar/Wind Harmer
1.304
970781AG2-491 GEN
Solar/Wind Harmer
5.408
972273AH1-721 GEN
Adder
43.396
274772LINCOLN ;3U
Adder
4.276
972228AH1-698 GEN2
Adder
1.875
274729ELWOOD EC;1P
Adder
8.308
274730ELWOOD EC;6P
Adder
8.308
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
274800UNIV PARK;3U
Adder
2.945
972038AH1-567 GEN2
Adder
0.184
274802UNIV PARK;5U
Adder
2.944
274826FISK ;BP
Adder
5.526
274676JOLIET 29;8U
Adder
14.929
235780M24_1
Solar/Wind Helper
0.99
944201AF1-088_MTX
Adder
67.999
957141AF2-008_MTX
Adder
33.999
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
TVALTFEXP_TVA->PJM
CLTF
3.109
NYPJM->LTFIMP_NY
CLTF
1.661
LGEELTFEXP_LGEE->PJM
CLTF
5.141
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
MECLTFEXP_MEC->PJM
CLTF
8.008
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2370.07
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.182
24802806KYGER 2HP
50/50
4.157
24802906KYGER 2LP
50/50
2.444
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.907
252519AF1-045_GEN
Solar/Wind Harmer
6.804
252516AE2-318_GEN
Solar/Wind Harmer
5.19
25194408D.CRK1
Adder
8.18
25194508D.CRK3
Adder
1.529
253317AC1-085 GEN4
Solar/Wind Harmer
8.99
253394AE2-221_GEN
Solar/Wind Harmer
4.598
253398AE2-221_GEN2
Solar/Wind Harmer
4.598
270186AC1-089 GEN
Solar/Wind Harmer
5.704
962581AG1-107 GEN
Solar/Wind Harmer
4.651
961491AF2-440 GEN
Solar/Wind Harmer
1.933
970235AG2-159 GEN
Solar/Wind Harmer
3.657
970235AG2-159 GEN
Solar/Wind Harmer
2.233
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.168
972045AH1-571 GEN
Solar/Wind Harmer
1.734
253370AE2-315 SEC1
Adder
1.72
971125AH1-004 GEN
Solar/Wind Harmer
3.367
970107AG2-081 GEN
Solar/Wind Harmer
2.525
25322209TAIT E
Adder
8.1
25322209TAIT E
Adder
7.918
25326109MON D
Adder
1.066
24728805RICHG1
Adder
2.989
24728905RICHG2
Adder
2.989
942891AE2-308 GEN
Solar/Wind Harmer
7.489
24379505HDWTR1G C
Solar/Wind Harmer
5.662
270209AC1-174_GEN
Solar/Wind Harmer
3.996
926881AC1-175 GEN
Solar/Wind Harmer
3.996
270383AD1-128 GEN
Solar/Wind Harmer
4.312
960161AF2-307 GEN
Solar/Wind Harmer
4.476
970883AG2-550 GEN
Solar/Wind Harmer
6.854
970885AG2-551 GEN
Solar/Wind Harmer
1.594
970825AG2-519 GEN
Solar/Wind Harmer
6.864
960441AF2-335 GEN
Solar/Wind Harmer
6.467
964571AG1-320 GEN
Solar/Wind Harmer
5.282
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.745
964611AG1-324 GEN
Solar/Wind Harmer
0.331
970239AG2-162 GEN
Solar/Wind Harmer
6.902
270201AC2-176 GEN
Solar/Wind Harmer
3.22
970653AG2-424 GEN
Solar/Wind Harmer
2.961
970653AG2-424 GEN
Solar/Wind Harmer
1.071
270518AE2-148 GEN
Solar/Wind Harmer
7.398
270599AE1-208 GEN
Solar/Wind Harmer
4.966
270031AE2-169
Solar/Wind Harmer
4.966
270444AC2-157 GEN1
Solar/Wind Harmer
3.313
25326509SID D
Adder
0.762
944541AF1-119 GEN
Solar/Wind Harmer
2.391
960971AF2-388 GEN
Solar/Wind Harmer
6.241
945391AF1-204 GEN
Solar/Wind Harmer
7.862
971081AG2-670 GEN
Solar/Wind Harmer
4.133
942221AE2-234 GEN
Solar/Wind Harmer
0.395
253378AE2-206_GEN
Solar/Wind Harmer
1.933
276820AF1-078_GEN
Solar/Wind Harmer
0.858
970241AG2-163 GEN
Solar/Wind Harmer
13.348
339236AF1-050_GEN
Solar/Wind Harmer
0.955
970077AG2-063 GEN
Solar/Wind Harmer
2.789
966841AG1-555 GEN
Solar/Wind Harmer
1.294
274674JOLIET 9 ;6U
Adder
6.759
972259AH1-714 GEN
Adder
8.367
274803UNIV PARK;6U
Adder
2.554
274696ROCKY RD ;4P
Adder
0.295
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.135
24803206KYGER 4HP
50/50
4.132
252507AC2-088 GEN
Solar/Wind Harmer
2.152
25196808ZIMRHP
Adder
83.726
25194608D.CRK4
Adder
1.778
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.732
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.088
270263AC1-001 GEN
Solar/Wind Harmer
0.979
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
25326309TAIT D
Adder
0.909
943111AE2-339 GEN
Solar/Wind Harmer
0.729
960071AF2-298 GEN
Solar/Wind Harmer
4.096
3429421JKCT 10G
Adder
6.576
3429241JKCT 3G
Adder
9.052
942081AE2-220 GEN
Solar/Wind Harmer
4.578
270239V3-007_GEN1
Solar/Wind Harmer
1.232
971565AH1-281 GEN
Solar/Wind Harmer
1.37
24728605AND G2
Adder
2.586
253343AC1-166 GEN
Solar/Wind Harmer
0.731
253325AC1-069 GEN
Solar/Wind Harmer
0.705
247536S-71 GEN
Solar/Wind Harmer
2.668
270005AE1-210 C O1
Solar/Wind Harmer
3.592
965031AG1-367 GEN
Solar/Wind Harmer
6.573
970825AG2-519 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
49.481
971821AH1-427 GEN
Solar/Wind Harmer
6.424
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.411
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.778
252524AE2-267 GEN
Solar/Wind Harmer
1.706
25196408WSDLE3
Adder
9.541
25196308WSDLE2
Adder
9.458
25196208WSDLE1
Adder
9.434
25196708WSDLE6
Adder
9.41
25196508WSDLE4
Adder
9.173
25196108MFTGT2
Adder
1.578
25196108MFTGT2
Adder
1.465
270367AC2-061_GEN
Solar/Wind Harmer
3.016
972163AH1-664 GEN
Solar/Wind Harmer
9.479
972165AH1-665 GEN
Solar/Wind Harmer
7.583
270269AC2-059
Solar/Wind Harmer
8.741
270340AC2-060 GEN
Solar/Wind Harmer
2.826
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.863
253372AE2-315 SEC3
Adder
1.627
253372AE2-315 SEC3
Adder
1.627
25306009OHH W.
Adder
2.431
970689AG2-444 GEN
Solar/Wind Harmer
13.51
253349AC2-067 GEN
Solar/Wind Harmer
4.095
253400AC2-068 GEN
Solar/Wind Harmer
1.647
3429211JKCT 2G
Adder
8.934
270432AC2-029 GEN
Solar/Wind Harmer
5.224
971673AH1-337 GEN
Solar/Wind Harmer
3.327
270240V3-007_GEN2
Solar/Wind Harmer
4.43
971029AG2-637 GEN
Solar/Wind Harmer
10.703
241972AD1-140 GEN
Solar/Wind Harmer
3.161
270543AE2-219 C
Solar/Wind Harmer
3.509
970455AG2-298 GEN
Solar/Wind Harmer
3.965
339211AE2-254 GEN
Solar/Wind Harmer
0.992
970115AG2-085 GEN
Solar/Wind Harmer
2.587
24725505WLD G2 C
Solar/Wind Harmer
2.527
24699105WLD G1 C
Solar/Wind Harmer
2.497
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.981
945581AF1-223 GEN
Solar/Wind Harmer
2.744
965461AG1-414 GEN
Solar/Wind Harmer
1.353
970289AG2-191 GEN
Solar/Wind Harmer
1.134
965101AG1-375 GEN
Solar/Wind Harmer
5.827
270024AE2-089 GEN
Solar/Wind Harmer
2.681
958711AF2-162 GEN
Solar/Wind Harmer
0.578
965401AG1-405 GEN
Solar/Wind Harmer
3.127
965411AG1-406 GEN
Solar/Wind Harmer
1.403
270156DARBY CT1
Adder
4.854
270157DARBY CT2
Adder
4.842
270158DARBY CT3
Adder
4.765
972203AH1-686 GEN
Adder
1.236
24729505KEY G4
Adder
3.472
963841AG1-237 GEN
Solar/Wind Harmer
5.739
945631AF1-228 GEN
Solar/Wind Harmer
2.433
24386205FR-12G C
Solar/Wind Harmer
2.21
24386405FR-21G C
Solar/Wind Harmer
2.218
24386605FR-22G C
Solar/Wind Harmer
2.218
24387005FR-3G C
Solar/Wind Harmer
2.04
24690905MDL-1G C
Solar/Wind Harmer
4.036
270180AB1-006 GEN1
Solar/Wind Harmer
3.615
274731ELWOOD EC;2P
Adder
7.226
274733ELWOOD EC;3P
Adder
7.226
274735ELWOOD EC;4P
Adder
7.226
274728ELWOOD EC;5P
Adder
7.225
972227AH1-698 GEN1
Adder
1.146
274675JOLIET 29;7U
Adder
13.447
274675JOLIET 29;7U
Adder
12.966
274687WILL CNTY;4U
Adder
12.245
274687WILL CNTY;4U
Adder
12.245
972037AH1-567 GEN1
Adder
0.08
274746AC1-111 G10
Adder
2.448
274744AC1-111 GEN8
Adder
2.448
274827FISK ;RP
Adder
3.396
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.964
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.411
971191AH1-055 GEN
Solar/Wind Harmer
86.587
25194608D.CRK4
Adder
1.778
25196608WSDLE5
Adder
9.268
252510AF1-249 C
Solar/Wind Harmer
0.452
253316AC1-085 GEN3
Solar/Wind Harmer
8.99
253433AC1-085 GEN1
Solar/Wind Harmer
5.707
946181AF1-283 GEN
Solar/Wind Harmer
13.952
958171AF2-111 GEN
Solar/Wind Harmer
25.736
25196008MFTGT1
Adder
1.386
972173AH1-669 GEN
Solar/Wind Harmer
4.892
972167AH1-666 GEN
Solar/Wind Harmer
7.71
253406AD2-031_GEN
Solar/Wind Harmer
1.22
270273AD2-016 GEN
Solar/Wind Harmer
2.5
253415AE1-040 GEN
Solar/Wind Harmer
1.023
270222AC2-111 GEN
Solar/Wind Harmer
7.003
253303V4-073 C
Solar/Wind Harmer
0.1
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
3429391JKCT 9G
Adder
6.576
270356AE2-297 GEN
Solar/Wind Harmer
3.463
270437AC2-090 C
Solar/Wind Harmer
3.998
970093AG2-073 GEN
Solar/Wind Harmer
7.116
966571AG1-526 GEN
Solar/Wind Harmer
15.203
24728705AND G3
Adder
5.409
24728505AND G1
Adder
2.586
253338AC1-165 GEN
Solar/Wind Harmer
0.731
253333AC1-068 GEN
Solar/Wind Harmer
0.705
958821AF2-173 GEN
Solar/Wind Harmer
9.202
270004AE1-209 GEN
Solar/Wind Harmer
3.592
946031AF1-268 GEN
Solar/Wind Harmer
5.411
970243AG2-164 GEN
Solar/Wind Harmer
16.205
970519AG2-331 GEN
Solar/Wind Harmer
10.887
970699AG2-449 GEN
Solar/Wind Harmer
7.202
962031AG1-047 GEN
Solar/Wind Harmer
1.893
957741AF2-068 GEN
Solar/Wind Harmer
9.396
970289AG2-191 GEN
Solar/Wind Harmer
0.458
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.321
970193AG2-126 GEN
Solar/Wind Harmer
8.463
960741AF2-365 GEN
Solar/Wind Harmer
2.669
944531AF1-118 GEN
Solar/Wind Harmer
18.282
970605AG2-385 GEN
Solar/Wind Harmer
2.789
972273AH1-721 GEN
Adder
41.984
274729ELWOOD EC;1P
Adder
7.226
274730ELWOOD EC;6P
Adder
7.225
274734ELWOOD EC;8P
Adder
7.225
274736ELWOOD EC;9P
Adder
7.225
972228AH1-698 GEN2
Adder
1.628
274800UNIV PARK;3U
Adder
2.555
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.966
274802UNIV PARK;5U
Adder
2.554
274826FISK ;BP
Adder
4.792
235780M24_1
Solar/Wind Helper
0.998
970333AG2-219 GEN
Solar/Wind Harmer
19.806
276903AD2-071 C
Solar/Wind Harmer
6.236
270032AE2-172
Solar/Wind Harmer
2.842
945371AF1-202 GEN
Solar/Wind Harmer
4.221
970291AG2-192 GEN
Solar/Wind Harmer
0.776
270445AC2-157 GEN2
Solar/Wind Harmer
3.313
958861AF2-177 GEN
Solar/Wind Harmer
6.369
965651AG1-433 GEN
Solar/Wind Harmer
3.12
339241AF1-083 GEN
Solar/Wind Harmer
0.932
270159DARBY CT4
Adder
4.776
963741AG1-226 GEN
Solar/Wind Harmer
24.026
970593AG2-378 GEN
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
4.286
24387305FR-4G C
Solar/Wind Harmer
2.62
964901AG1-354 GEN
Solar/Wind Harmer
7.622
274732ELWOOD EC;7P
Adder
7.225
274674JOLIET 9 ;6U
Adder
6.759
274801UNIV PARK;4U
Adder
2.555
274676JOLIET 29;8U
Adder
13.447
274745AC1-111 GEN9
Adder
2.448
960001AF2-291 GEN
Solar/Wind Helper
1.675
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
68.979
957141AF2-008_MTX
Adder
34.49
LAGNLTFEXP_LAGN->PJM
CLTF
5.577
TVALTFEXP_TVA->PJM
CLTF
2.613
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.304
WECLTFEXP_WEC->PJM
CLTF
1.665
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.668
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.558
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.83
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.269
MECLTFEXP_MEC->PJM
CLTF
7.133
SIGELTFEXP_SIGE->PJM
CLTF
0.33

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2363.36
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.901
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
5.186
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
8.982
253394AE2-221_GEN
Solar/Wind Harmer
4.593
253398AE2-221_GEN2
Solar/Wind Harmer
4.593
270186AC1-089 GEN
Solar/Wind Harmer
5.711
962581AG1-107 GEN
Solar/Wind Harmer
4.655
961491AF2-440 GEN
Solar/Wind Harmer
1.934
970235AG2-159 GEN
Solar/Wind Harmer
3.659
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
1.373
972043AH1-570 GEN
Solar/Wind Harmer
2.172
972045AH1-571 GEN
Solar/Wind Harmer
1.738
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
3.374
970107AG2-081 GEN
Solar/Wind Harmer
2.53
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
7.516
24379505HDWTR1G C
Solar/Wind Harmer
5.654
270209AC1-174_GEN
Solar/Wind Harmer
3.99
926881AC1-175 GEN
Solar/Wind Harmer
3.99
270383AD1-128 GEN
Solar/Wind Harmer
4.306
960161AF2-307 GEN
Solar/Wind Harmer
4.504
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.756
252524AE2-267 GEN
Solar/Wind Harmer
1.704
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
9.494
972165AH1-665 GEN
Solar/Wind Harmer
7.595
270367AC2-061_GEN
Solar/Wind Harmer
3.018
270269AC2-059
Solar/Wind Harmer
8.724
270340AC2-060 GEN
Solar/Wind Harmer
2.823
339243AC2-075 GEN1
Solar/Wind Harmer
0.414
944031AF1-071 GEN
Solar/Wind Harmer
0.862
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
13.474
253349AC2-067 GEN
Solar/Wind Harmer
4.09
253400AC2-068 GEN
Solar/Wind Harmer
1.644
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
86.549
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.702
946181AF1-283 GEN
Solar/Wind Harmer
13.94
958171AF2-111 GEN
Solar/Wind Harmer
25.744
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
4.883
972167AH1-666 GEN
Solar/Wind Harmer
7.721
253406AD2-031_GEN
Solar/Wind Harmer
1.219
270273AD2-016 GEN
Solar/Wind Harmer
2.495
253415AE1-040 GEN
Solar/Wind Harmer
1.022
270222AC2-111 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
3.459
270437AC2-090 C
Solar/Wind Harmer
3.992
970093AG2-073 GEN
Solar/Wind Harmer
7.147
966571AG1-526 GEN
Solar/Wind Harmer
15.27
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.729
253333AC1-068 GEN
Solar/Wind Harmer
0.703
958821AF2-173 GEN
Solar/Wind Harmer
9.186
270004AE1-209 GEN
Solar/Wind Harmer
3.586
946031AF1-268 GEN
Solar/Wind Harmer
5.401
970243AG2-164 GEN
Solar/Wind Harmer
16.159
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
5.21
971673AH1-337 GEN
Solar/Wind Harmer
3.321
270240V3-007_GEN2
Solar/Wind Harmer
4.424
971029AG2-637 GEN
Solar/Wind Harmer
10.686
241972AD1-140 GEN
Solar/Wind Harmer
3.154
270543AE2-219 C
Solar/Wind Harmer
3.503
970455AG2-298 GEN
Solar/Wind Harmer
3.979
339211AE2-254 GEN
Solar/Wind Harmer
0.997
970115AG2-085 GEN
Solar/Wind Harmer
2.582
24725505WLD G2 C
Solar/Wind Harmer
2.523
24699105WLD G1 C
Solar/Wind Harmer
2.493
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.964
945581AF1-223 GEN
Solar/Wind Harmer
2.738
965461AG1-414 GEN
Solar/Wind Harmer
1.35
970289AG2-191 GEN
Solar/Wind Harmer
1.132
965101AG1-375 GEN
Solar/Wind Harmer
5.814
270024AE2-089 GEN
Solar/Wind Harmer
2.674
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.152
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
5.728
945631AF1-228 GEN
Solar/Wind Harmer
2.424
24386205FR-12G C
Solar/Wind Harmer
2.206
24386405FR-21G C
Solar/Wind Harmer
2.213
24386605FR-22G C
Solar/Wind Harmer
2.213
24387005FR-3G C
Solar/Wind Harmer
2.036
24690905MDL-1G C
Solar/Wind Harmer
4.026
270180AB1-006 GEN1
Solar/Wind Harmer
3.607
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.959
970883AG2-550 GEN
Solar/Wind Harmer
6.842
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
6.852
964571AG1-320 GEN
Solar/Wind Harmer
5.299
960441AF2-335 GEN
Solar/Wind Harmer
6.456
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.744
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.882
270201AC2-176 GEN
Solar/Wind Harmer
3.214
970653AG2-424 GEN
Solar/Wind Harmer
2.974
970653AG2-424 GEN
Solar/Wind Harmer
1.075
270518AE2-148 GEN
Solar/Wind Harmer
7.376
270599AE1-208 GEN
Solar/Wind Harmer
4.957
270031AE2-169
Solar/Wind Harmer
4.957
270444AC2-157 GEN1
Solar/Wind Harmer
3.31
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
2.386
960971AF2-388 GEN
Solar/Wind Harmer
6.226
945391AF1-204 GEN
Solar/Wind Harmer
7.855
971081AG2-670 GEN
Solar/Wind Harmer
4.16
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.926
276820AF1-078_GEN
Solar/Wind Harmer
0.856
970241AG2-163 GEN
Solar/Wind Harmer
13.326
339236AF1-050_GEN
Solar/Wind Harmer
0.962
970077AG2-063 GEN
Solar/Wind Harmer
2.779
966841AG1-555 GEN
Solar/Wind Harmer
1.291
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
972267AH1-718 GEN
Adder
1.821
274803UNIV PARK;6U
Adder
2.549
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
2.151
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.723
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.114
270263AC1-001 GEN
Solar/Wind Harmer
0.977
339216AC1-074 GEN
Solar/Wind Harmer
1.528
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.09
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
942081AE2-220 GEN
Solar/Wind Harmer
4.571
270239V3-007_GEN1
Solar/Wind Harmer
1.23
971565AH1-281 GEN
Solar/Wind Harmer
1.374
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.729
253325AC1-069 GEN
Solar/Wind Harmer
0.703
247536S-71 GEN
Solar/Wind Harmer
2.663
270005AE1-210 C O1
Solar/Wind Harmer
3.586
965031AG1-367 GEN
Solar/Wind Harmer
6.561
970825AG2-519 GEN
Solar/Wind Harmer
1.529
971821AH1-427 GEN
Solar/Wind Harmer
6.457
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
19.749
276903AD2-071 C
Solar/Wind Harmer
6.224
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
4.213
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.31
958861AF2-177 GEN
Solar/Wind Harmer
6.354
965651AG1-433 GEN
Solar/Wind Harmer
3.113
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
23.987
970593AG2-378 GEN
Solar/Wind Harmer
1.029
24385905FR-11G C
Solar/Wind Harmer
4.277
24387305FR-4G C
Solar/Wind Harmer
2.615
964901AG1-354 GEN
Solar/Wind Harmer
7.68
274732ELWOOD EC;7P
Adder
7.212
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
970519AG2-331 GEN
Solar/Wind Harmer
10.856
970699AG2-449 GEN
Solar/Wind Harmer
7.182
962031AG1-047 GEN
Solar/Wind Harmer
1.89
957741AF2-068 GEN
Solar/Wind Harmer
9.378
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
8.454
960741AF2-365 GEN
Solar/Wind Harmer
2.685
944531AF1-118 GEN
Solar/Wind Harmer
18.231
970605AG2-385 GEN
Solar/Wind Harmer
2.779
972273AH1-721 GEN
Adder
42.389
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274802UNIV PARK;5U
Adder
2.549
235780M24_1
Solar/Wind Helper
0.999
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.34 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2361.46
MW Contribution:2.17
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.409
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.731
252524AE2-267 GEN
Solar/Wind Harmer
1.703
25196408WSDLE3
Adder
9.524
25196308WSDLE2
Adder
9.441
25196208WSDLE1
Adder
9.417
25196708WSDLE6
Adder
9.394
25196508WSDLE4
Adder
9.157
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.474
972165AH1-665 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.01
270269AC2-059
Solar/Wind Harmer
8.712
270340AC2-060 GEN
Solar/Wind Harmer
2.818
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.861
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
970689AG2-444 GEN
Solar/Wind Harmer
13.458
253349AC2-067 GEN
Solar/Wind Harmer
4.085
253400AC2-068 GEN
Solar/Wind Harmer
1.643
3429211JKCT 2G
Adder
8.952
270432AC2-029 GEN
Solar/Wind Harmer
5.202
971673AH1-337 GEN
Solar/Wind Harmer
3.318
270240V3-007_GEN2
Solar/Wind Harmer
4.42
971029AG2-637 GEN
Solar/Wind Harmer
10.676
241972AD1-140 GEN
Solar/Wind Harmer
3.15
270543AE2-219 C
Solar/Wind Harmer
3.5
970455AG2-298 GEN
Solar/Wind Harmer
3.975
339211AE2-254 GEN
Solar/Wind Harmer
0.995
970115AG2-085 GEN
Solar/Wind Harmer
2.58
24725505WLD G2 C
Solar/Wind Harmer
2.521
24699105WLD G1 C
Solar/Wind Harmer
2.491
961761AG1-017 GEN
Solar/Wind Harmer
0.267
270594AE1-207 GEN
Solar/Wind Harmer
8.956
945581AF1-223 GEN
Solar/Wind Harmer
2.736
965461AG1-414 GEN
Solar/Wind Harmer
1.349
970289AG2-191 GEN
Solar/Wind Harmer
1.131
965101AG1-375 GEN
Solar/Wind Harmer
5.809
270024AE2-089 GEN
Solar/Wind Harmer
2.672
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.149
965411AG1-406 GEN
Solar/Wind Harmer
1.413
270156DARBY CT1
Adder
4.829
270157DARBY CT2
Adder
4.817
270158DARBY CT3
Adder
4.74
24729505KEY G4
Adder
3.46
972203AH1-686 GEN
Adder
1.224
963841AG1-237 GEN
Solar/Wind Harmer
5.724
945631AF1-228 GEN
Solar/Wind Harmer
2.42
24386205FR-12G C
Solar/Wind Harmer
2.204
24386405FR-21G C
Solar/Wind Harmer
2.212
24386605FR-22G C
Solar/Wind Harmer
2.212
24387005FR-3G C
Solar/Wind Harmer
2.034
24690905MDL-1G C
Solar/Wind Harmer
4.023
270180AB1-006 GEN1
Solar/Wind Harmer
3.604
274731ELWOOD EC;2P
Adder
7.207
274733ELWOOD EC;3P
Adder
7.207
274735ELWOOD EC;4P
Adder
7.207
274728ELWOOD EC;5P
Adder
7.207
972227AH1-698 GEN1
Adder
1.143
274675JOLIET 29;7U
Adder
13.413
274675JOLIET 29;7U
Adder
12.934
274687WILL CNTY;4U
Adder
12.214
274687WILL CNTY;4U
Adder
12.214
274746AC1-111 G10
Adder
2.442
274744AC1-111 GEN8
Adder
2.442
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
946581AF1-322 GEN
Solar/Wind Harmer
1.958
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.154
24802906KYGER 2LP
50/50
2.442
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.895
252519AF1-045_GEN
Solar/Wind Harmer
6.792
252516AE2-318_GEN
Solar/Wind Harmer
5.181
25194408D.CRK1
Adder
8.166
25194508D.CRK3
Adder
1.527
253317AC1-085 GEN4
Solar/Wind Harmer
8.973
253394AE2-221_GEN
Solar/Wind Harmer
4.589
253398AE2-221_GEN2
Solar/Wind Harmer
4.589
270186AC1-089 GEN
Solar/Wind Harmer
5.695
962581AG1-107 GEN
Solar/Wind Harmer
4.642
961491AF2-440 GEN
Solar/Wind Harmer
1.929
970235AG2-159 GEN
Solar/Wind Harmer
3.656
970235AG2-159 GEN
Solar/Wind Harmer
2.232
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.169
972045AH1-571 GEN
Solar/Wind Harmer
1.735
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
3.37
970107AG2-081 GEN
Solar/Wind Harmer
2.527
25322209TAIT E
Adder
8.079
25322209TAIT E
Adder
7.897
25326109MON D
Adder
1.063
24728805RICHG1
Adder
2.983
24728905RICHG2
Adder
2.983
942891AE2-308 GEN
Solar/Wind Harmer
7.505
24379505HDWTR1G C
Solar/Wind Harmer
5.649
270209AC1-174_GEN
Solar/Wind Harmer
3.987
926881AC1-175 GEN
Solar/Wind Harmer
3.987
270383AD1-128 GEN
Solar/Wind Harmer
4.302
960161AF2-307 GEN
Solar/Wind Harmer
4.486
970883AG2-550 GEN
Solar/Wind Harmer
6.835
970885AG2-551 GEN
Solar/Wind Harmer
1.59
970825AG2-519 GEN
Solar/Wind Harmer
6.846
964571AG1-320 GEN
Solar/Wind Harmer
5.295
960441AF2-335 GEN
Solar/Wind Harmer
6.451
247621Y3-024
Adder
0.154
964611AG1-324 GEN
Solar/Wind Harmer
0.743
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.877
270201AC2-176 GEN
Solar/Wind Harmer
3.211
970653AG2-424 GEN
Solar/Wind Harmer
2.972
970653AG2-424 GEN
Solar/Wind Harmer
1.074
270518AE2-148 GEN
Solar/Wind Harmer
7.366
270599AE1-208 GEN
Solar/Wind Harmer
4.953
270031AE2-169
Solar/Wind Harmer
4.953
270444AC2-157 GEN1
Solar/Wind Harmer
3.307
25326509SID D
Adder
0.759
944541AF1-119 GEN
Solar/Wind Harmer
2.384
960971AF2-388 GEN
Solar/Wind Harmer
6.221
945391AF1-204 GEN
Solar/Wind Harmer
7.849
971081AG2-670 GEN
Solar/Wind Harmer
4.157
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.924
276820AF1-078_GEN
Solar/Wind Harmer
0.855
970241AG2-163 GEN
Solar/Wind Harmer
13.317
339236AF1-050_GEN
Solar/Wind Harmer
0.962
966841AG1-555 GEN
Solar/Wind Harmer
1.29
970077AG2-063 GEN
Solar/Wind Harmer
2.775
274674JOLIET 9 ;6U
Adder
6.742
972259AH1-714 GEN
Adder
8.345
972267AH1-718 GEN
Adder
1.82
274803UNIV PARK;6U
Adder
2.547
274764LEE CO EC;5U
Adder
4.073
274765LEE CO EC;6U
Adder
2.573
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.132
24803206KYGER 4HP
50/50
4.129
252507AC2-088 GEN
Solar/Wind Harmer
2.149
25196808ZIMRHP
Adder
83.601
25194608D.CRK4
Adder
1.775
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.712
25196008MFTGT1
Adder
1.429
945681AF1-233 GEN
Solar/Wind Harmer
18.078
270263AC1-001 GEN
Solar/Wind Harmer
0.975
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.907
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.085
3429421JKCT 10G
Adder
6.587
3429241JKCT 3G
Adder
9.07
942081AE2-220 GEN
Solar/Wind Harmer
4.567
270239V3-007_GEN1
Solar/Wind Harmer
1.229
971565AH1-281 GEN
Solar/Wind Harmer
1.373
24728605AND G2
Adder
2.582
253343AC1-166 GEN
Solar/Wind Harmer
0.728
253325AC1-069 GEN
Solar/Wind Harmer
0.702
247536S-71 GEN
Solar/Wind Harmer
2.66
270005AE1-210 C O1
Solar/Wind Harmer
3.583
965031AG1-367 GEN
Solar/Wind Harmer
6.556
970825AG2-519 GEN
Solar/Wind Harmer
1.528
971821AH1-427 GEN
Solar/Wind Harmer
6.451
970091AG2-072 GEN
Adder
49.343
970333AG2-219 GEN
Solar/Wind Harmer
19.734
276903AD2-071 C
Solar/Wind Harmer
6.219
270032AE2-172
Solar/Wind Harmer
2.834
945371AF1-202 GEN
Solar/Wind Harmer
4.209
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.307
958861AF2-177 GEN
Solar/Wind Harmer
6.349
965651AG1-433 GEN
Solar/Wind Harmer
3.11
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.752
963741AG1-226 GEN
Solar/Wind Harmer
23.97
24385905FR-11G C
Solar/Wind Harmer
4.274
24387305FR-4G C
Solar/Wind Harmer
2.613
970593AG2-378 GEN
Solar/Wind Harmer
1.028
964901AG1-354 GEN
Solar/Wind Harmer
7.677
274732ELWOOD EC;7P
Adder
7.207
274674JOLIET 9 ;6U
Adder
6.742
274676JOLIET 29;8U
Adder
13.413
274801UNIV PARK;4U
Adder
2.548
274745AC1-111 GEN9
Adder
2.442
960001AF2-291 GEN
Solar/Wind Helper
1.68
270331AC1-082 GEN3
Solar/Wind Helper
0.199
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.409
971191AH1-055 GEN
Solar/Wind Harmer
86.509
25194608D.CRK4
Adder
1.775
25196608WSDLE5
Adder
9.252
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.973
253433AC1-085 GEN1
Solar/Wind Harmer
5.696
946181AF1-283 GEN
Solar/Wind Harmer
13.926
958171AF2-111 GEN
Solar/Wind Harmer
25.716
25196008MFTGT1
Adder
1.384
972173AH1-669 GEN
Solar/Wind Harmer
4.876
972167AH1-666 GEN
Solar/Wind Harmer
7.706
253406AD2-031_GEN
Solar/Wind Harmer
1.218
270273AD2-016 GEN
Solar/Wind Harmer
2.491
253415AE1-040 GEN
Solar/Wind Harmer
1.02
270222AC2-111 GEN
Solar/Wind Harmer
6.988
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
3429391JKCT 9G
Adder
6.587
270356AE2-297 GEN
Solar/Wind Harmer
3.456
270437AC2-090 C
Solar/Wind Harmer
3.989
970093AG2-073 GEN
Solar/Wind Harmer
7.136
966571AG1-526 GEN
Solar/Wind Harmer
15.255
24728705AND G3
Adder
5.399
24728505AND G1
Adder
2.582
253338AC1-165 GEN
Solar/Wind Harmer
0.728
253333AC1-068 GEN
Solar/Wind Harmer
0.702
958821AF2-173 GEN
Solar/Wind Harmer
9.178
270004AE1-209 GEN
Solar/Wind Harmer
3.583
946031AF1-268 GEN
Solar/Wind Harmer
5.397
970243AG2-164 GEN
Solar/Wind Harmer
16.146
970519AG2-331 GEN
Solar/Wind Harmer
10.848
970699AG2-449 GEN
Solar/Wind Harmer
7.176
962031AG1-047 GEN
Solar/Wind Harmer
1.888
957741AF2-068 GEN
Solar/Wind Harmer
9.369
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.31
970193AG2-126 GEN
Solar/Wind Harmer
8.449
960741AF2-365 GEN
Solar/Wind Harmer
2.684
944531AF1-118 GEN
Solar/Wind Harmer
18.215
970605AG2-385 GEN
Solar/Wind Harmer
2.775
972273AH1-721 GEN
Adder
42.355
274729ELWOOD EC;1P
Adder
7.207
274730ELWOOD EC;6P
Adder
7.207
274734ELWOOD EC;8P
Adder
7.207
274736ELWOOD EC;9P
Adder
7.207
972228AH1-698 GEN2
Adder
1.623
274676JOLIET 29;8U
Adder
12.934
274800UNIV PARK;3U
Adder
2.548
972038AH1-567 GEN2
Adder
0.159
274802UNIV PARK;5U
Adder
2.547
235780M24_1
Solar/Wind Helper
0.999
944201AF1-088_MTX
Adder
68.864
957141AF2-008_MTX
Adder
34.432
LAGNLTFEXP_LAGN->PJM
CLTF
5.68
TVALTFEXP_TVA->PJM
CLTF
2.676
NYPJM->LTFIMP_NY
CLTF
1.589
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.663
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.615
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.948
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.72
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.465
MECLTFEXP_MEC->PJM
CLTF
7.143
SIGELTFEXP_SIGE->PJM
CLTF
0.33

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.41 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2239.27
MW Contribution:1.52
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.129
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
5.71
25194408D.CRK1
Adder
7.772
25194508D.CRK3
Adder
1.453
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
3.745
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.215
971125AH1-004 GEN
Solar/Wind Harmer
2.272
970107AG2-081 GEN
Solar/Wind Harmer
1.704
253370AE2-315 SEC1
Adder
1.603
24728805RICHG1
Adder
2.949
24728905RICHG2
Adder
2.949
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.114
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.843
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960161AF2-307 GEN
Solar/Wind Harmer
3.166
970825AG2-519 GEN
Solar/Wind Harmer
5.23
960441AF2-335 GEN
Solar/Wind Harmer
4.696
247621Y3-024
Adder
0.159
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
4.125
270031AE2-169
Solar/Wind Harmer
2.475
964571AG1-320 GEN
Solar/Wind Harmer
4.08
971613AH1-306 GEN
Solar/Wind Harmer
2.143
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.559
970653AG2-424 GEN
Solar/Wind Harmer
2.067
970653AG2-424 GEN
Solar/Wind Harmer
1.071
942221AE2-234 GEN
Solar/Wind Harmer
0.02
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.992
945391AF1-204 GEN
Solar/Wind Harmer
4.315
970239AG2-162 GEN
Solar/Wind Harmer
1.015
970241AG2-163 GEN
Solar/Wind Harmer
2.285
971081AG2-670 GEN
Solar/Wind Harmer
2.933
966841AG1-555 GEN
Solar/Wind Harmer
0.433
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.321
25326509SID D
Adder
0.697
276916AD2-100_GEN
Solar/Wind Harmer
7.697
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.581
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.207
274887GEN-1.85
Solar/Wind Harmer
0.093
276843GEN-1.7
Solar/Wind Harmer
0.114
958011AF2-095 GEN
Solar/Wind Harmer
5.082
972259AH1-714 GEN
Adder
9.649
274674JOLIET 9 ;6U
Adder
7.776
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.285
958491AF2-143 GEN
Solar/Wind Harmer
5.285
274803UNIV PARK;6U
Adder
2.944
274879MINONK ;1U
Solar/Wind Harmer
0.149
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.477
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.139
276646AC1-214 GEN2
Solar/Wind Harmer
0.139
276782AC1-033 GEN
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.654
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
962691AG1-118 GEN
Solar/Wind Harmer
10.504
970921AG2-575 GEN
Solar/Wind Harmer
3.5
970921AG2-575 GEN
Solar/Wind Harmer
1.167
964781AG1-341 GEN
Solar/Wind Harmer
3.707
942991AE2-321 GEN
Solar/Wind Harmer
3.901
971333AH1-146 GEN
Solar/Wind Harmer
6.981
971335AH1-147 GEN
Solar/Wind Harmer
6.981
971341AH1-150 GEN
Solar/Wind Harmer
6.979
971343AH1-151 GEN
Solar/Wind Harmer
6.979
237033AB1-150 GEN
Solar/Wind Helper
0.4
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.08
252507AC2-088 GEN
Solar/Wind Harmer
0.36
25196808ZIMRHP
Adder
79.423
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.992
25196008MFTGT1
Adder
1.369
945681AF1-233 GEN
Solar/Wind Harmer
12.039
339216AC1-074 GEN
Solar/Wind Harmer
0.167
270263AC1-001 GEN
Solar/Wind Harmer
0.584
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
25326309TAIT D
Adder
0.846
3429421JKCT 10G
Adder
6.399
960071AF2-298 GEN
Solar/Wind Harmer
2.664
970773AG2-487 GEN
Solar/Wind Harmer
0.938
3429241JKCT 3G
Adder
8.84
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.753
270005AE1-210 C O1
Solar/Wind Harmer
1.038
965031AG1-367 GEN
Solar/Wind Harmer
4.789
24728605AND G2
Adder
2.624
970825AG2-519 GEN
Solar/Wind Harmer
1.675
971565AH1-281 GEN
Solar/Wind Harmer
0.942
247536S-71 GEN
Solar/Wind Harmer
0.189
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.056
971821AH1-427 GEN
Solar/Wind Harmer
4.468
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
1.915
970291AG2-192 GEN
Solar/Wind Harmer
0.569
965651AG1-433 GEN
Solar/Wind Harmer
1.28
970091AG2-072 GEN
Adder
45.505
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.006
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.902
963741AG1-226 GEN
Solar/Wind Harmer
9.27
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.626
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.429
276615X2-022 GEN
Solar/Wind Harmer
0.038
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.754
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.476
972175AH1-670 GEN
Solar/Wind Harmer
3.016
970245AG2-165 GEN
Solar/Wind Harmer
1.581
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
5.072
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.519
939401AE1-172 GEN
Solar/Wind Harmer
2.671
970273AG2-179 GEN
Solar/Wind Harmer
1.245
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
276901AD2-066 C O1
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
1.852
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.368
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
274801UNIV PARK;4U
Adder
2.945
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.427
970569AG2-363 GEN
Solar/Wind Harmer
10.571
276164X3-005 C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.482
962241AG1-070 GEN
Solar/Wind Harmer
1.916
274877BISHOP HL;1U
Solar/Wind Harmer
0.118
962781AG1-127 GEN
Solar/Wind Harmer
3.331
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.063
957471AF2-041 GEN
Solar/Wind Harmer
10.469
959081AF2-199 GEN
Solar/Wind Harmer
3.49
971067AG2-660 GEN
Solar/Wind Harmer
1.163
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.205
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.697
25194608D.CRK4
Adder
1.69
25196608WSDLE5
Adder
8.803
252510AF1-249 C
Solar/Wind Harmer
0.055
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.09
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.035
972167AH1-666 GEN
Solar/Wind Harmer
5.13
253406AD2-031_GEN
Solar/Wind Harmer
0.461
972173AH1-669 GEN
Solar/Wind Harmer
3.047
270222AC2-111 GEN
Solar/Wind Harmer
2.955
270273AD2-016 GEN
Solar/Wind Harmer
0.603
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
970191AG2-125 GEN
Solar/Wind Harmer
1.388
3429391JKCT 9G
Adder
6.399
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.888
958821AF2-173 GEN
Solar/Wind Harmer
6.704
270004AE1-209 GEN
Solar/Wind Harmer
1.038
24728705AND G3
Adder
5.489
24728505AND G1
Adder
2.624
966571AG1-526 GEN
Solar/Wind Harmer
10.492
946031AF1-268 GEN
Solar/Wind Harmer
4.488
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.776
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.507
944531AF1-118 GEN
Solar/Wind Harmer
18.471
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.006
970193AG2-126 GEN
Solar/Wind Harmer
6.091
970243AG2-164 GEN
Solar/Wind Harmer
2.375
970519AG2-331 GEN
Solar/Wind Harmer
10.553
970699AG2-449 GEN
Solar/Wind Harmer
1.015
960741AF2-365 GEN
Solar/Wind Harmer
1.902
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
3.773
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.693
276668AB2-070 GEN1
Solar/Wind Harmer
0.134
276621W2-048 GEN
Solar/Wind Harmer
0.185
276838X2-022 GEN2
Solar/Wind Harmer
0.206
942481AE2-261 GEN
Solar/Wind Harmer
10.947
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.581
970517AG2-330 GEN
Solar/Wind Harmer
9.486
972273AH1-721 GEN
Adder
43.396
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.888
959611AF2-252 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.177
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
970273AG2-179 GEN
Solar/Wind Harmer
2.134
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.276
972228AH1-698 GEN2
Adder
1.875
276806AD2-047 C O1
Solar/Wind Harmer
2
970941AG2-585 GEN
Solar/Wind Harmer
4.411
274729ELWOOD EC;1P
Adder
8.308
276893AG1-478 C
Solar/Wind Harmer
0.14
274730ELWOOD EC;6P
Adder
8.308
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
970707AG2-453 GEN
Solar/Wind Harmer
11.517
274800UNIV PARK;3U
Adder
2.945
972038AH1-567 GEN2
Adder
0.184
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
7.047
274802UNIV PARK;5U
Adder
2.944
270043AE2-236 GEN
Solar/Wind Harmer
2.261
274826FISK ;BP
Adder
5.526
274676JOLIET 29;8U
Adder
14.929
962251AG1-071 GEN
Solar/Wind Harmer
2.197
274878BISHOP HL;2U
Solar/Wind Harmer
0.118
943121AE2-341 GEN
Solar/Wind Harmer
5.891
943591AF1-030 GEN
Solar/Wind Harmer
3.917
339250AF1-203 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.128
971155AH1-034 GEN
Solar/Wind Harmer
4.077
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
959091AF2-200 GEN
Solar/Wind Harmer
6.979
235780M24_1
Solar/Wind Helper
0.99
970349AG2-230 GEN
Solar/Wind Harmer
0.971
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
25016408BKJDB1
50/50
0.276
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.764
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196508WSDLE4
Adder
8.713
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
972163AH1-664 GEN
Solar/Wind Harmer
7.031
972165AH1-665 GEN
Solar/Wind Harmer
5.631
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
253349AC2-067 GEN
Solar/Wind Harmer
1.699
253400AC2-068 GEN
Solar/Wind Harmer
0.683
3429211JKCT 2G
Adder
8.726
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970689AG2-444 GEN
Solar/Wind Harmer
10.333
971673AH1-337 GEN
Solar/Wind Harmer
3.282
971029AG2-637 GEN
Solar/Wind Harmer
7.495
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.879
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.046
339211AE2-254 GEN
Solar/Wind Harmer
0.002
945581AF1-223 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.004
971609AH1-304 GEN
Solar/Wind Harmer
0.735
270594AE1-207 GEN
Solar/Wind Harmer
5.001
241972AD1-140 GEN
Solar/Wind Harmer
0.486
965101AG1-375 GEN
Solar/Wind Harmer
4.42
970289AG2-191 GEN
Solar/Wind Harmer
0.831
270024AE2-089 GEN
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
3.892
965401AG1-405 GEN
Solar/Wind Harmer
2.225
965411AG1-406 GEN
Solar/Wind Harmer
1.432
963841AG1-237 GEN
Solar/Wind Harmer
1.679
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.01
270071AF1-092 GEN
Solar/Wind Harmer
7.101
971611AH1-305 GEN
Solar/Wind Harmer
2.203
944221AF1-090 GEN
Solar/Wind Harmer
2.159
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.134
276848AB2-070 GEN3
Solar/Wind Harmer
0.133
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.804
941731AE2-173 GEN
Solar/Wind Harmer
3.019
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
970169AG2-114 GEN
Solar/Wind Harmer
3.59
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.276
274776LINCOLN ;7U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972227AH1-698 GEN1
Adder
1.32
970833AG2-524 GEN
Solar/Wind Harmer
3.883
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.529
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
274735ELWOOD EC;4P
Adder
8.308
274728ELWOOD EC;5P
Adder
8.308
972037AH1-567 GEN1
Adder
0.092
276868AE1-113 GEN
Solar/Wind Harmer
0.707
276882AE2-255 GEN
Solar/Wind Harmer
0.412
957751AF2-069 GEN
Solar/Wind Harmer
0.116
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
3.916
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971177AH1-047 GEN
Solar/Wind Harmer
2.154
971411AH1-196 GEN
Solar/Wind Harmer
5.236
971171AH1-044 GEN
Solar/Wind Harmer
6.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.206
971347AH1-153 GEN
Solar/Wind Harmer
0.971
944201AF1-088_MTX
Adder
67.999
957141AF2-008_MTX
Adder
33.999
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
TVALTFEXP_TVA->PJM
CLTF
3.109
NYPJM->LTFIMP_NY
CLTF
1.661
LGEELTFEXP_LGEE->PJM
CLTF
5.141
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
MECLTFEXP_MEC->PJM
CLTF
8.008
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:1.58
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.799
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
0.38
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
12.638
270263AC1-001 GEN
Solar/Wind Harmer
0.653
339216AC1-074 GEN
Solar/Wind Harmer
0.174
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
960071AF2-298 GEN
Solar/Wind Harmer
2.849
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
6.03
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.576
972045AH1-571 GEN
Solar/Wind Harmer
1.263
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
970107AG2-081 GEN
Solar/Wind Harmer
1.765
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970883AG2-550 GEN
Solar/Wind Harmer
4.773
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
5.021
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
1.093
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270599AE1-208 GEN
Solar/Wind Harmer
3.89
270031AE2-169
Solar/Wind Harmer
2.334
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.613
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
966841AG1-555 GEN
Solar/Wind Harmer
0.406
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276911AD2-131_GEN
Solar/Wind Harmer
0.471
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
964781AG1-341 GEN
Solar/Wind Harmer
3.601
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
2.586
960611AF2-352 GEN
Solar/Wind Harmer
1.093
970321AG2-212 GEN
Solar/Wind Harmer
1.366
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.13
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.821
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
274803UNIV PARK;6U
Adder
2.549
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
971573AH1-285 GEN
Solar/Wind Harmer
0.568
237033AB1-150 GEN
Solar/Wind Helper
0.403
971333AH1-146 GEN
Solar/Wind Harmer
3.002
971335AH1-147 GEN
Solar/Wind Harmer
3.002
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.657
971565AH1-281 GEN
Solar/Wind Harmer
0.959
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.185
270005AE1-210 C O1
Solar/Wind Harmer
0.992
965031AG1-367 GEN
Solar/Wind Harmer
4.578
970825AG2-519 GEN
Solar/Wind Harmer
1.608
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
3.125
276903AD2-071 C
Solar/Wind Harmer
4.849
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
958861AF2-177 GEN
Solar/Wind Harmer
1.758
965651AG1-433 GEN
Solar/Wind Harmer
1.166
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.358
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
963831AG1-236 GEN
Solar/Wind Harmer
1.313
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.279
958381AF2-132 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.562
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
6.619
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
970569AG2-363 GEN
Solar/Wind Harmer
9.313
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
276158O29GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.212
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.15
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.447
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
958171AF2-111 GEN
Solar/Wind Harmer
17.961
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
3.407
972167AH1-666 GEN
Solar/Wind Harmer
5.387
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
3.033
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
970191AG2-125 GEN
Solar/Wind Harmer
1.473
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970243AG2-164 GEN
Solar/Wind Harmer
2.557
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
5.898
960741AF2-365 GEN
Solar/Wind Harmer
1.874
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
972273AH1-721 GEN
Adder
42.389
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.498
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.156
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.555
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.838
959611AF2-252 GEN
Solar/Wind Harmer
1.093
942111AE2-223 GEN
Solar/Wind Harmer
1.059
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
970571AG2-364 GEN
Solar/Wind Harmer
6.209
942051AE2-217 GEN
Solar/Wind Harmer
5.584
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.1
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.902
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
7.374
972165AH1-665 GEN
Solar/Wind Harmer
5.906
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
253349AC2-067 GEN
Solar/Wind Harmer
1.803
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.455
241972AD1-140 GEN
Solar/Wind Harmer
0.537
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
3.084
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.766
971609AH1-304 GEN
Solar/Wind Harmer
0.693
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.789
965101AG1-375 GEN
Solar/Wind Harmer
4.056
270024AE2-089 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
2.199
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.422
941731AE2-173 GEN
Solar/Wind Harmer
2.716
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.133
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276868AE1-113 GEN
Solar/Wind Harmer
0.619
276882AE2-255 GEN
Solar/Wind Harmer
0.361
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
960591AF2-350 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
971681AH1-341 GEN
Solar/Wind Harmer
4.912
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2088.16
MW Contribution:2.13
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.209
24802806KYGER 2HP
50/50
4.185
24802906KYGER 2LP
50/50
2.46
252509AD1-136 GEN
Solar/Wind Harmer
0.297
25183208HLCRTG
Solar/Wind Harmer
6.65
252519AF1-045_GEN
Solar/Wind Harmer
6.541
252516AE2-318_GEN
Solar/Wind Harmer
4.99
25194408D.CRK1
Adder
7.828
25194508D.CRK3
Adder
1.464
253317AC1-085 GEN4
Solar/Wind Harmer
8.59
253394AE2-221_GEN
Solar/Wind Harmer
4.35
253398AE2-221_GEN2
Solar/Wind Harmer
4.35
270186AC1-089 GEN
Solar/Wind Harmer
5.71
962581AG1-107 GEN
Solar/Wind Harmer
4.635
961491AF2-440 GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
3.527
970235AG2-159 GEN
Solar/Wind Harmer
2.153
339221AD2-048_GEN
Solar/Wind Harmer
1.344
972043AH1-570 GEN
Solar/Wind Harmer
2.133
972045AH1-571 GEN
Solar/Wind Harmer
1.707
971125AH1-004 GEN
Solar/Wind Harmer
3.309
970107AG2-081 GEN
Solar/Wind Harmer
2.482
253370AE2-315 SEC1
Adder
1.591
25322209TAIT E
Adder
7.443
25322209TAIT E
Adder
7.276
942891AE2-308 GEN
Solar/Wind Harmer
7.449
25326109MON D
Adder
0.971
24728805RICHG1
Adder
2.784
24728905RICHG2
Adder
2.784
960161AF2-307 GEN
Solar/Wind Harmer
4.571
24379505HDWTR1G C
Solar/Wind Harmer
5.217
270209AC1-174_GEN
Solar/Wind Harmer
3.682
926881AC1-175 GEN
Solar/Wind Harmer
3.682
270383AD1-128 GEN
Solar/Wind Harmer
3.962
964571AG1-320 GEN
Solar/Wind Harmer
5.136
970883AG2-550 GEN
Solar/Wind Harmer
6.261
970885AG2-551 GEN
Solar/Wind Harmer
1.456
970653AG2-424 GEN
Solar/Wind Harmer
2.916
970653AG2-424 GEN
Solar/Wind Harmer
1.054
970825AG2-519 GEN
Solar/Wind Harmer
6.248
960441AF2-335 GEN
Solar/Wind Harmer
5.883
247621Y3-024
Adder
0.14
964611AG1-324 GEN
Solar/Wind Harmer
0.674
964611AG1-324 GEN
Solar/Wind Harmer
0.299
270201AC2-176 GEN
Solar/Wind Harmer
2.909
971081AG2-670 GEN
Solar/Wind Harmer
4.164
270599AE1-208 GEN
Solar/Wind Harmer
4.481
270031AE2-169
Solar/Wind Harmer
4.481
339236AF1-050_GEN
Solar/Wind Harmer
0.967
970239AG2-162 GEN
Solar/Wind Harmer
5.822
270444AC2-157 GEN1
Solar/Wind Harmer
2.94
339231AF1-038_GEN
Solar/Wind Harmer
0.928
944541AF1-119 GEN
Solar/Wind Harmer
2.14
960971AF2-388 GEN
Solar/Wind Harmer
5.586
25326509SID D
Adder
0.665
945391AF1-204 GEN
Solar/Wind Harmer
7.039
339255AE2-071 GEN
Solar/Wind Harmer
0.525
964781AG1-341 GEN
Solar/Wind Harmer
5.228
24803106KYGER 3LP
50/50
2.478
24803306KYGER 4LP
50/50
2.427
971191AH1-055 GEN
Solar/Wind Harmer
87.457
972173AH1-669 GEN
Solar/Wind Harmer
6.452
270273AD2-016 GEN
Solar/Wind Harmer
3.245
252510AF1-249 C
Solar/Wind Harmer
0.433
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.854
253316AC1-085 GEN3
Solar/Wind Harmer
8.59
253433AC1-085 GEN1
Solar/Wind Harmer
5.453
946181AF1-283 GEN
Solar/Wind Harmer
13.332
958171AF2-111 GEN
Solar/Wind Harmer
25.055
25196008MFTGT1
Adder
1.324
253415AE1-040 GEN
Solar/Wind Harmer
1.099
972167AH1-666 GEN
Solar/Wind Harmer
7.578
253406AD2-031_GEN
Solar/Wind Harmer
1.187
270222AC2-111 GEN
Solar/Wind Harmer
6.559
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429391JKCT 9G
Adder
6.507
970093AG2-073 GEN
Solar/Wind Harmer
7.118
270356AE2-297 GEN
Solar/Wind Harmer
3.213
966571AG1-526 GEN
Solar/Wind Harmer
15.167
270437AC2-090 C
Solar/Wind Harmer
3.683
24728705AND G3
Adder
4.972
24728505AND G1
Adder
2.377
958821AF2-173 GEN
Solar/Wind Harmer
8.396
270004AE1-209 GEN
Solar/Wind Harmer
3.277
946031AF1-268 GEN
Solar/Wind Harmer
4.924
962031AG1-047 GEN
Solar/Wind Harmer
1.711
957741AF2-068 GEN
Solar/Wind Harmer
8.489
253338AC1-165 GEN
Solar/Wind Harmer
0.608
253333AC1-068 GEN
Solar/Wind Harmer
0.586
960741AF2-365 GEN
Solar/Wind Harmer
2.673
970289AG2-191 GEN
Solar/Wind Harmer
0.409
970291AG2-192 GEN
Solar/Wind Harmer
0.372
970243AG2-164 GEN
Solar/Wind Harmer
13.668
970519AG2-331 GEN
Solar/Wind Harmer
9.183
970699AG2-449 GEN
Solar/Wind Harmer
6.075
972273AH1-721 GEN
Adder
43.806
247642Z2-115 C
Solar/Wind Harmer
0.033
970273AG2-179 GEN
Solar/Wind Harmer
1.986
971617AH1-308 GEN
Solar/Wind Harmer
2.961
970193AG2-126 GEN
Solar/Wind Harmer
7.576
339250AF1-203 GEN
Solar/Wind Harmer
0.3
962251AG1-071 GEN
Solar/Wind Harmer
2.72
971155AH1-034 GEN
Solar/Wind Harmer
4.929
944531AF1-118 GEN
Solar/Wind Harmer
16.137
24802606KYGER 1HP
50/50
4.234
24802706KYGER 1LP
50/50
2.485
24803506KYGER 5LP
50/50
2.427
25016408BKJDB1
50/50
0.281
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
50.621
270269AC2-059
Solar/Wind Harmer
11.349
252524AE2-267 GEN
Solar/Wind Harmer
1.629
25196408WSDLE3
Adder
9.115
25196308WSDLE2
Adder
9.036
25196208WSDLE1
Adder
9.013
25196708WSDLE6
Adder
8.99
25196508WSDLE4
Adder
8.764
270340AC2-060 GEN
Solar/Wind Harmer
3.131
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.4
270367AC2-061_GEN
Solar/Wind Harmer
3.017
972163AH1-664 GEN
Solar/Wind Harmer
9.331
972165AH1-665 GEN
Solar/Wind Harmer
7.465
339243AC2-075 GEN1
Solar/Wind Harmer
0.404
270432AC2-029 GEN
Solar/Wind Harmer
6.133
944031AF1-071 GEN
Solar/Wind Harmer
0.808
253372AE2-315 SEC3
Adder
1.505
253372AE2-315 SEC3
Adder
1.505
25306009OHH W.
Adder
2.25
3429211JKCT 2G
Adder
8.876
253349AC2-067 GEN
Solar/Wind Harmer
3.779
253400AC2-068 GEN
Solar/Wind Harmer
1.52
971673AH1-337 GEN
Solar/Wind Harmer
3.058
270240V3-007_GEN2
Solar/Wind Harmer
4.082
339211AE2-254 GEN
Solar/Wind Harmer
0.993
971029AG2-637 GEN
Solar/Wind Harmer
9.823
970455AG2-298 GEN
Solar/Wind Harmer
3.88
270543AE2-219 C
Solar/Wind Harmer
3.206
241972AD1-140 GEN
Solar/Wind Harmer
2.785
970115AG2-085 GEN
Solar/Wind Harmer
2.353
24725505WLD G2 C
Solar/Wind Harmer
2.288
24699105WLD G1 C
Solar/Wind Harmer
2.261
961761AG1-017 GEN
Solar/Wind Harmer
0.242
965401AG1-405 GEN
Solar/Wind Harmer
3.224
965411AG1-406 GEN
Solar/Wind Harmer
1.447
270594AE1-207 GEN
Solar/Wind Harmer
8.066
945581AF1-223 GEN
Solar/Wind Harmer
2.476
965461AG1-414 GEN
Solar/Wind Harmer
1.209
970289AG2-191 GEN
Solar/Wind Harmer
1.013
965101AG1-375 GEN
Solar/Wind Harmer
5.23
958711AF2-162 GEN
Solar/Wind Harmer
0.517
270024AE2-089 GEN
Solar/Wind Harmer
2.39
24729505KEY G4
Adder
3.077
963841AG1-237 GEN
Solar/Wind Harmer
5.029
24386205FR-12G C
Solar/Wind Harmer
1.926
24386405FR-21G C
Solar/Wind Harmer
1.932
24386605FR-22G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
270330AC1-082 GEN2
Solar/Wind Helper
0.039
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803406KYGER 5HP
50/50
4.162
24803206KYGER 4HP
50/50
4.159
270263AC1-001 GEN
Solar/Wind Harmer
1.225
252507AC2-088 GEN
Solar/Wind Harmer
2.082
25196808ZIMRHP
Adder
80.646
25194608D.CRK4
Adder
1.702
253432AC1-085 GEN2
Solar/Wind Harmer
0.275
946171AF1-282 GEN
Solar/Wind Harmer
10.256
25196008MFTGT1
Adder
1.367
945681AF1-233 GEN
Solar/Wind Harmer
17.786
339216AC1-074 GEN
Solar/Wind Harmer
1.493
943111AE2-339 GEN
Solar/Wind Harmer
0.717
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429421JKCT 10G
Adder
6.507
25326309TAIT D
Adder
0.835
3429241JKCT 3G
Adder
8.993
960071AF2-298 GEN
Solar/Wind Harmer
3.766
971565AH1-281 GEN
Solar/Wind Harmer
1.333
942081AE2-220 GEN
Solar/Wind Harmer
4.218
270239V3-007_GEN1
Solar/Wind Harmer
1.135
971821AH1-427 GEN
Solar/Wind Harmer
6.444
24728605AND G2
Adder
2.377
270005AE1-210 C O1
Solar/Wind Harmer
3.277
965031AG1-367 GEN
Solar/Wind Harmer
5.997
247536S-71 GEN
Solar/Wind Harmer
2.426
970825AG2-519 GEN
Solar/Wind Harmer
1.394
339241AF1-083 GEN
Solar/Wind Harmer
0.937
276903AD2-071 C
Solar/Wind Harmer
5.625
253343AC1-166 GEN
Solar/Wind Harmer
0.608
253325AC1-069 GEN
Solar/Wind Harmer
0.586
970091AG2-072 GEN
Adder
42.53
270032AE2-172
Solar/Wind Harmer
2.553
945371AF1-202 GEN
Solar/Wind Harmer
3.81
970291AG2-192 GEN
Solar/Wind Harmer
0.693
970333AG2-219 GEN
Solar/Wind Harmer
16.705
270445AC2-157 GEN2
Solar/Wind Harmer
2.94
958861AF2-177 GEN
Solar/Wind Harmer
5.717
964901AG1-354 GEN
Solar/Wind Harmer
7.741
965651AG1-433 GEN
Solar/Wind Harmer
2.793
970273AG2-179 GEN
Solar/Wind Harmer
1.244
962241AG1-070 GEN
Solar/Wind Harmer
2.225
963741AG1-226 GEN
Solar/Wind Harmer
21.164
24385905FR-11G C
Solar/Wind Harmer
3.734
24387305FR-4G C
Solar/Wind Harmer
2.283
960001AF2-291 GEN
Solar/Wind Helper
1.622
270331AC1-082 GEN3
Solar/Wind Helper
0.187
270518AE2-148 GEN
Solar/Wind Harmer
5.786
942221AE2-234 GEN
Solar/Wind Harmer
0.35
970241AG2-163 GEN
Solar/Wind Harmer
11.758
971485AH1-239 GEN
Solar/Wind Harmer
3.722
966021AG1-471 GEN
Solar/Wind Harmer
2.491
253378AE2-206_GEN
Solar/Wind Harmer
1.656
276820AF1-078_GEN
Solar/Wind Harmer
0.736
966841AG1-555 GEN
Solar/Wind Harmer
0.721
944201AF1-088_MTX
Adder
61.225
957141AF2-008_MTX
Adder
30.613
LAGNLTFEXP_LAGN->PJM
CLTF
6.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.548
TVALTFEXP_TVA->PJM
CLTF
2.997
NYPJM->LTFIMP_NY
CLTF
1.498
LGEELTFEXP_LGEE->PJM
CLTF
5.05
WECLTFEXP_WEC->PJM
CLTF
1.467
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1
AG2-052LTFEXP_AG2-052->PJM
LTF
0.095
AH1-155LTFEXP_AH1-155->PJM
LTF
0.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.203
MECLTFEXP_MEC->PJM
CLTF
6.527
SIGELTFEXP_SIGE->PJM
CLTF
0.311

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.73 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2044.01
MW Contribution:2.12
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
6.939
252516AE2-318_GEN
Solar/Wind Harmer
5.293
25194408D.CRK1
Adder
8.527
25194508D.CRK3
Adder
1.594
25183208HLCRTG
Solar/Wind Harmer
6.758
253317AC1-085 GEN4
Solar/Wind Harmer
7.888
970235AG2-159 GEN
Solar/Wind Harmer
3.588
970235AG2-159 GEN
Solar/Wind Harmer
2.19
270186AC1-089 GEN
Solar/Wind Harmer
5.394
339221AD2-048_GEN
Solar/Wind Harmer
1.338
962581AG1-107 GEN
Solar/Wind Harmer
4.27
961491AF2-440 GEN
Solar/Wind Harmer
1.775
972043AH1-570 GEN
Solar/Wind Harmer
2.119
972045AH1-571 GEN
Solar/Wind Harmer
1.695
253394AE2-221_GEN
Solar/Wind Harmer
3.836
253398AE2-221_GEN2
Solar/Wind Harmer
3.836
971125AH1-004 GEN
Solar/Wind Harmer
3.294
970107AG2-081 GEN
Solar/Wind Harmer
2.471
24728805RICHG1
Adder
2.798
24728905RICHG2
Adder
2.798
942891AE2-308 GEN
Solar/Wind Harmer
7.396
960161AF2-307 GEN
Solar/Wind Harmer
4.489
24379505HDWTR1G C
Solar/Wind Harmer
5.372
270209AC1-174_GEN
Solar/Wind Harmer
3.791
926881AC1-175 GEN
Solar/Wind Harmer
3.791
270383AD1-128 GEN
Solar/Wind Harmer
4.025
964571AG1-320 GEN
Solar/Wind Harmer
5.163
253370AE2-315 SEC1
Adder
1.257
970883AG2-550 GEN
Solar/Wind Harmer
6.253
970885AG2-551 GEN
Solar/Wind Harmer
1.454
25322209TAIT E
Adder
5.931
25322209TAIT E
Adder
5.798
970653AG2-424 GEN
Solar/Wind Harmer
2.924
970653AG2-424 GEN
Solar/Wind Harmer
1.057
970825AG2-519 GEN
Solar/Wind Harmer
6.385
960441AF2-335 GEN
Solar/Wind Harmer
6.012
247621Y3-024
Adder
0.141
25326109MON D
Adder
0.761
964611AG1-324 GEN
Solar/Wind Harmer
0.68
964611AG1-324 GEN
Solar/Wind Harmer
0.302
270201AC2-176 GEN
Solar/Wind Harmer
2.928
270599AE1-208 GEN
Solar/Wind Harmer
4.584
270031AE2-169
Solar/Wind Harmer
4.584
971081AG2-670 GEN
Solar/Wind Harmer
4.157
339236AF1-050_GEN
Solar/Wind Harmer
0.965
270444AC2-157 GEN1
Solar/Wind Harmer
2.967
970239AG2-162 GEN
Solar/Wind Harmer
5.82
944541AF1-119 GEN
Solar/Wind Harmer
2.201
960971AF2-388 GEN
Solar/Wind Harmer
5.745
945391AF1-204 GEN
Solar/Wind Harmer
7.147
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.213
942221AE2-234 GEN
Solar/Wind Harmer
0.356
970241AG2-163 GEN
Solar/Wind Harmer
11.947
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.146
25326509SID D
Adder
0.572
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.12
25196608WSDLE5
Adder
9.731
25194608D.CRK4
Adder
1.854
252510AF1-249 C
Solar/Wind Harmer
0.469
25196008MFTGT1
Adder
1.385
958171AF2-111 GEN
Solar/Wind Harmer
24.753
253316AC1-085 GEN3
Solar/Wind Harmer
7.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.007
946181AF1-283 GEN
Solar/Wind Harmer
12.242
972167AH1-666 GEN
Solar/Wind Harmer
7.471
972173AH1-669 GEN
Solar/Wind Harmer
4.449
270273AD2-016 GEN
Solar/Wind Harmer
2.265
270222AC2-111 GEN
Solar/Wind Harmer
6.583
253406AD2-031_GEN
Solar/Wind Harmer
1.022
253415AE1-040 GEN
Solar/Wind Harmer
0.887
3429391JKCT 9G
Adder
6.458
270356AE2-297 GEN
Solar/Wind Harmer
3.298
970093AG2-073 GEN
Solar/Wind Harmer
7.066
966571AG1-526 GEN
Solar/Wind Harmer
15.11
270437AC2-090 C
Solar/Wind Harmer
3.793
24728705AND G3
Adder
5.08
24728505AND G1
Adder
2.429
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
958821AF2-173 GEN
Solar/Wind Harmer
8.623
270004AE1-209 GEN
Solar/Wind Harmer
3.366
946031AF1-268 GEN
Solar/Wind Harmer
5.017
962031AG1-047 GEN
Solar/Wind Harmer
1.721
957741AF2-068 GEN
Solar/Wind Harmer
8.543
253338AC1-165 GEN
Solar/Wind Harmer
0.615
253333AC1-068 GEN
Solar/Wind Harmer
0.593
970289AG2-191 GEN
Solar/Wind Harmer
0.418
970291AG2-192 GEN
Solar/Wind Harmer
0.38
960741AF2-365 GEN
Solar/Wind Harmer
2.673
970243AG2-164 GEN
Solar/Wind Harmer
13.665
970519AG2-331 GEN
Solar/Wind Harmer
9.181
970699AG2-449 GEN
Solar/Wind Harmer
6.073
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.41
971617AH1-308 GEN
Solar/Wind Harmer
2.99
970193AG2-126 GEN
Solar/Wind Harmer
7.693
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.713
971155AH1-034 GEN
Solar/Wind Harmer
4.913
944531AF1-118 GEN
Solar/Wind Harmer
16.613
235780M24_1
Solar/Wind Helper
0.923
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.293
25250008NTE_CT
50/50
1.921
25250108NTE_ST
50/50
1.463
971985AH1-537 GEN
Solar/Wind Harmer
50.537
252524AE2-267 GEN
Solar/Wind Harmer
1.791
25196408WSDLE3
Adder
10.017
25196308WSDLE2
Adder
9.93
25196208WSDLE1
Adder
9.905
25196708WSDLE6
Adder
9.88
25196508WSDLE4
Adder
9.631
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.197
972165AH1-665 GEN
Solar/Wind Harmer
7.358
270367AC2-061_GEN
Solar/Wind Harmer
2.867
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270269AC2-059
Solar/Wind Harmer
7.919
270340AC2-060 GEN
Solar/Wind Harmer
2.488
944031AF1-071 GEN
Solar/Wind Harmer
0.811
3429211JKCT 2G
Adder
8.808
970689AG2-444 GEN
Solar/Wind Harmer
12.105
270240V3-007_GEN2
Solar/Wind Harmer
4.203
270432AC2-029 GEN
Solar/Wind Harmer
4.625
971673AH1-337 GEN
Solar/Wind Harmer
3.039
339211AE2-254 GEN
Solar/Wind Harmer
0.989
971029AG2-637 GEN
Solar/Wind Harmer
9.777
970455AG2-298 GEN
Solar/Wind Harmer
3.893
253349AC2-067 GEN
Solar/Wind Harmer
3.188
253400AC2-068 GEN
Solar/Wind Harmer
1.282
25306009OHH W.
Adder
1.837
253372AE2-315 SEC3
Adder
1.189
253372AE2-315 SEC3
Adder
1.189
270543AE2-219 C
Solar/Wind Harmer
3.202
970115AG2-085 GEN
Solar/Wind Harmer
2.405
24725505WLD G2 C
Solar/Wind Harmer
2.339
24699105WLD G1 C
Solar/Wind Harmer
2.311
961761AG1-017 GEN
Solar/Wind Harmer
0.244
945581AF1-223 GEN
Solar/Wind Harmer
2.545
965401AG1-405 GEN
Solar/Wind Harmer
3.196
965411AG1-406 GEN
Solar/Wind Harmer
1.435
270594AE1-207 GEN
Solar/Wind Harmer
8.234
965461AG1-414 GEN
Solar/Wind Harmer
1.234
970289AG2-191 GEN
Solar/Wind Harmer
1.034
965101AG1-375 GEN
Solar/Wind Harmer
5.378
958711AF2-162 GEN
Solar/Wind Harmer
0.532
270024AE2-089 GEN
Solar/Wind Harmer
2.414
241972AD1-140 GEN
Solar/Wind Harmer
2.212
24729505KEY G4
Adder
3.167
963841AG1-237 GEN
Solar/Wind Harmer
5.111
24386205FR-12G C
Solar/Wind Harmer
1.958
24386405FR-21G C
Solar/Wind Harmer
1.964
24386605FR-22G C
Solar/Wind Harmer
1.964
24387005FR-3G C
Solar/Wind Harmer
1.807
270156DARBY CT1
Adder
3.979
270157DARBY CT2
Adder
3.97
270158DARBY CT3
Adder
3.906
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.131
25194608D.CRK4
Adder
1.854
25196808ZIMRHP
Adder
83.848
25196008MFTGT1
Adder
1.43
253432AC1-085 GEN2
Solar/Wind Harmer
0.252
946171AF1-282 GEN
Solar/Wind Harmer
9.417
945681AF1-233 GEN
Solar/Wind Harmer
17.533
339216AC1-074 GEN
Solar/Wind Harmer
1.49
270263AC1-001 GEN
Solar/Wind Harmer
0.891
943111AE2-339 GEN
Solar/Wind Harmer
0.713
3429421JKCT 10G
Adder
6.458
3429241JKCT 3G
Adder
8.923
942081AE2-220 GEN
Solar/Wind Harmer
4.343
270239V3-007_GEN1
Solar/Wind Harmer
1.169
971565AH1-281 GEN
Solar/Wind Harmer
1.339
971821AH1-427 GEN
Solar/Wind Harmer
6.42
24728605AND G2
Adder
2.429
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
270005AE1-210 C O1
Solar/Wind Harmer
3.366
965031AG1-367 GEN
Solar/Wind Harmer
6.159
960071AF2-298 GEN
Solar/Wind Harmer
3.07
25326309TAIT D
Adder
0.666
970825AG2-519 GEN
Solar/Wind Harmer
1.425
247536S-71 GEN
Solar/Wind Harmer
2.43
276903AD2-071 C
Solar/Wind Harmer
5.746
253343AC1-166 GEN
Solar/Wind Harmer
0.615
253325AC1-069 GEN
Solar/Wind Harmer
0.593
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.916
270032AE2-172
Solar/Wind Harmer
2.606
970091AG2-072 GEN
Adder
42.548
970291AG2-192 GEN
Solar/Wind Harmer
0.707
958861AF2-177 GEN
Solar/Wind Harmer
5.878
270445AC2-157 GEN2
Solar/Wind Harmer
2.967
970333AG2-219 GEN
Solar/Wind Harmer
16.702
965651AG1-433 GEN
Solar/Wind Harmer
2.872
964901AG1-354 GEN
Solar/Wind Harmer
7.722
970273AG2-179 GEN
Solar/Wind Harmer
1.235
962241AG1-070 GEN
Solar/Wind Harmer
2.22
963741AG1-226 GEN
Solar/Wind Harmer
21.505
24385905FR-11G C
Solar/Wind Harmer
3.796
24387305FR-4G C
Solar/Wind Harmer
2.321
270159DARBY CT4
Adder
3.916
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
61.779
957141AF2-008_MTX
Adder
30.89
LAGNLTFEXP_LAGN->PJM
CLTF
5.99
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.148
TVALTFEXP_TVA->PJM
CLTF
2.938
NYPJM->LTFIMP_NY
CLTF
1.486
LGEELTFEXP_LGEE->PJM
CLTF
5.109
WECLTFEXP_WEC->PJM
CLTF
1.495
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.963
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.08
MECLTFEXP_MEC->PJM
CLTF
6.608
SIGELTFEXP_SIGE->PJM
CLTF
0.315

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34524 34598_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34524 34598_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2041.73
MW Contribution:2.13
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.306
25183208HLCRTG
Solar/Wind Harmer
6.991
252519AF1-045_GEN
Solar/Wind Harmer
6.973
252516AE2-318_GEN
Solar/Wind Harmer
5.319
25194408D.CRK1
Adder
8.448
25194508D.CRK3
Adder
1.579
253317AC1-085 GEN4
Solar/Wind Harmer
7.982
970235AG2-159 GEN
Solar/Wind Harmer
3.58
970235AG2-159 GEN
Solar/Wind Harmer
2.186
270186AC1-089 GEN
Solar/Wind Harmer
5.399
339221AD2-048_GEN
Solar/Wind Harmer
1.342
253394AE2-221_GEN
Solar/Wind Harmer
3.877
253398AE2-221_GEN2
Solar/Wind Harmer
3.877
972043AH1-570 GEN
Solar/Wind Harmer
2.126
972045AH1-571 GEN
Solar/Wind Harmer
1.701
962581AG1-107 GEN
Solar/Wind Harmer
4.271
961491AF2-440 GEN
Solar/Wind Harmer
1.775
971125AH1-004 GEN
Solar/Wind Harmer
3.306
970107AG2-081 GEN
Solar/Wind Harmer
2.48
942891AE2-308 GEN
Solar/Wind Harmer
7.422
24728805RICHG1
Adder
2.785
24728905RICHG2
Adder
2.785
960161AF2-307 GEN
Solar/Wind Harmer
4.511
24379505HDWTR1G C
Solar/Wind Harmer
5.345
270209AC1-174_GEN
Solar/Wind Harmer
3.772
926881AC1-175 GEN
Solar/Wind Harmer
3.772
270383AD1-128 GEN
Solar/Wind Harmer
4.006
253370AE2-315 SEC1
Adder
1.261
964571AG1-320 GEN
Solar/Wind Harmer
5.157
970883AG2-550 GEN
Solar/Wind Harmer
6.228
970885AG2-551 GEN
Solar/Wind Harmer
1.448
25322209TAIT E
Adder
5.949
25322209TAIT E
Adder
5.815
970653AG2-424 GEN
Solar/Wind Harmer
2.922
970653AG2-424 GEN
Solar/Wind Harmer
1.056
970825AG2-519 GEN
Solar/Wind Harmer
6.356
960441AF2-335 GEN
Solar/Wind Harmer
5.986
247621Y3-024
Adder
0.14
25326109MON D
Adder
0.764
964611AG1-324 GEN
Solar/Wind Harmer
0.677
964611AG1-324 GEN
Solar/Wind Harmer
0.301
270201AC2-176 GEN
Solar/Wind Harmer
2.916
270599AE1-208 GEN
Solar/Wind Harmer
4.564
270031AE2-169
Solar/Wind Harmer
4.564
971081AG2-670 GEN
Solar/Wind Harmer
4.155
339236AF1-050_GEN
Solar/Wind Harmer
0.964
270444AC2-157 GEN1
Solar/Wind Harmer
2.957
970239AG2-162 GEN
Solar/Wind Harmer
5.801
944541AF1-119 GEN
Solar/Wind Harmer
2.192
960971AF2-388 GEN
Solar/Wind Harmer
5.72
945391AF1-204 GEN
Solar/Wind Harmer
7.122
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.208
942221AE2-234 GEN
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
11.906
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.142
25326509SID D
Adder
0.573
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.136
25196608WSDLE5
Adder
9.63
25194608D.CRK4
Adder
1.836
252510AF1-249 C
Solar/Wind Harmer
0.465
25196008MFTGT1
Adder
1.376
958171AF2-111 GEN
Solar/Wind Harmer
24.947
253316AC1-085 GEN3
Solar/Wind Harmer
7.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.067
946181AF1-283 GEN
Solar/Wind Harmer
12.388
972167AH1-666 GEN
Solar/Wind Harmer
7.523
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.291
25183008BIOENL
50/50
0.032
25250008NTE_CT
50/50
1.9
25250108NTE_ST
50/50
1.447
971985AH1-537 GEN
Solar/Wind Harmer
50.462
252524AE2-267 GEN
Solar/Wind Harmer
1.772
25196408WSDLE3
Adder
9.913
25196308WSDLE2
Adder
9.827
25196208WSDLE1
Adder
9.802
25196708WSDLE6
Adder
9.777
25196508WSDLE4
Adder
9.531
25196108MFTGT2
Adder
1.567
25196108MFTGT2
Adder
1.455
972163AH1-664 GEN
Solar/Wind Harmer
9.259
972165AH1-665 GEN
Solar/Wind Harmer
7.407
270367AC2-061_GEN
Solar/Wind Harmer
2.864
339243AC2-075 GEN1
Solar/Wind Harmer
0.405
270269AC2-059
Solar/Wind Harmer
7.935
270340AC2-060 GEN
Solar/Wind Harmer
2.497
944031AF1-071 GEN
Solar/Wind Harmer
0.807
3429211JKCT 2G
Adder
8.843
970689AG2-444 GEN
Solar/Wind Harmer
12.133
270240V3-007_GEN2
Solar/Wind Harmer
4.182
270432AC2-029 GEN
Solar/Wind Harmer
4.637
971673AH1-337 GEN
Solar/Wind Harmer
3.026
339211AE2-254 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
9.737
970455AG2-298 GEN
Solar/Wind Harmer
3.891
253349AC2-067 GEN
Solar/Wind Harmer
3.191
253400AC2-068 GEN
Solar/Wind Harmer
1.283
25306009OHH W.
Adder
1.841
253372AE2-315 SEC3
Adder
1.193
253372AE2-315 SEC3
Adder
1.193
270543AE2-219 C
Solar/Wind Harmer
3.189
970115AG2-085 GEN
Solar/Wind Harmer
2.394
24725505WLD G2 C
Solar/Wind Harmer
2.329
24699105WLD G1 C
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.243
965401AG1-405 GEN
Solar/Wind Harmer
3.201
965411AG1-406 GEN
Solar/Wind Harmer
1.437
945581AF1-223 GEN
Solar/Wind Harmer
2.534
270594AE1-207 GEN
Solar/Wind Harmer
8.199
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
1.03
965101AG1-375 GEN
Solar/Wind Harmer
5.355
958711AF2-162 GEN
Solar/Wind Harmer
0.529
270024AE2-089 GEN
Solar/Wind Harmer
2.404
241972AD1-140 GEN
Solar/Wind Harmer
2.223
24729505KEY G4
Adder
3.154
963841AG1-237 GEN
Solar/Wind Harmer
5.094
24386205FR-12G C
Solar/Wind Harmer
1.951
24386405FR-21G C
Solar/Wind Harmer
1.958
24386605FR-22G C
Solar/Wind Harmer
1.958
24387005FR-3G C
Solar/Wind Harmer
1.801
270156DARBY CT1
Adder
4.019
270157DARBY CT2
Adder
4.009
270158DARBY CT3
Adder
3.945
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.144
25194608D.CRK4
Adder
1.836
25196808ZIMRHP
Adder
83.684
25196008MFTGT1
Adder
1.421
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.53
945681AF1-233 GEN
Solar/Wind Harmer
17.654
339216AC1-074 GEN
Solar/Wind Harmer
1.495
270263AC1-001 GEN
Solar/Wind Harmer
0.893
943111AE2-339 GEN
Solar/Wind Harmer
0.716
3429421JKCT 10G
Adder
6.486
3429241JKCT 3G
Adder
8.959
942081AE2-220 GEN
Solar/Wind Harmer
4.322
270239V3-007_GEN1
Solar/Wind Harmer
1.163
971565AH1-281 GEN
Solar/Wind Harmer
1.338
971821AH1-427 GEN
Solar/Wind Harmer
6.429
24728605AND G2
Adder
2.419
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
960071AF2-298 GEN
Solar/Wind Harmer
3.077
270005AE1-210 C O1
Solar/Wind Harmer
3.35
965031AG1-367 GEN
Solar/Wind Harmer
6.131
25326309TAIT D
Adder
0.668
970825AG2-519 GEN
Solar/Wind Harmer
1.418
247536S-71 GEN
Solar/Wind Harmer
2.42
276903AD2-071 C
Solar/Wind Harmer
5.722
253343AC1-166 GEN
Solar/Wind Harmer
0.621
253325AC1-069 GEN
Solar/Wind Harmer
0.599
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.898
270032AE2-172
Solar/Wind Harmer
2.595
970091AG2-072 GEN
Adder
42.403
970291AG2-192 GEN
Solar/Wind Harmer
0.704
958861AF2-177 GEN
Solar/Wind Harmer
5.853
270445AC2-157 GEN2
Solar/Wind Harmer
2.957
970333AG2-219 GEN
Solar/Wind Harmer
16.645
965651AG1-433 GEN
Solar/Wind Harmer
2.86
964901AG1-354 GEN
Solar/Wind Harmer
7.717
970273AG2-179 GEN
Solar/Wind Harmer
1.236
962241AG1-070 GEN
Solar/Wind Harmer
2.218
963741AG1-226 GEN
Solar/Wind Harmer
21.432
24385905FR-11G C
Solar/Wind Harmer
3.783
24387305FR-4G C
Solar/Wind Harmer
2.313
270159DARBY CT4
Adder
3.955
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.198
972173AH1-669 GEN
Solar/Wind Harmer
4.457
270273AD2-016 GEN
Solar/Wind Harmer
2.269
253406AD2-031_GEN
Solar/Wind Harmer
1.029
270222AC2-111 GEN
Solar/Wind Harmer
6.549
253415AE1-040 GEN
Solar/Wind Harmer
0.891
3429391JKCT 9G
Adder
6.486
270356AE2-297 GEN
Solar/Wind Harmer
3.281
970093AG2-073 GEN
Solar/Wind Harmer
7.088
966571AG1-526 GEN
Solar/Wind Harmer
15.14
270437AC2-090 C
Solar/Wind Harmer
3.774
24728705AND G3
Adder
5.059
24728505AND G1
Adder
2.419
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
958821AF2-173 GEN
Solar/Wind Harmer
8.583
270004AE1-209 GEN
Solar/Wind Harmer
3.35
946031AF1-268 GEN
Solar/Wind Harmer
4.995
253338AC1-165 GEN
Solar/Wind Harmer
0.621
253333AC1-068 GEN
Solar/Wind Harmer
0.599
962031AG1-047 GEN
Solar/Wind Harmer
1.715
957741AF2-068 GEN
Solar/Wind Harmer
8.509
970289AG2-191 GEN
Solar/Wind Harmer
0.416
970291AG2-192 GEN
Solar/Wind Harmer
0.378
960741AF2-365 GEN
Solar/Wind Harmer
2.671
970243AG2-164 GEN
Solar/Wind Harmer
13.619
970519AG2-331 GEN
Solar/Wind Harmer
9.15
970699AG2-449 GEN
Solar/Wind Harmer
6.053
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.453
971617AH1-308 GEN
Solar/Wind Harmer
2.978
970193AG2-126 GEN
Solar/Wind Harmer
7.666
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.711
971155AH1-034 GEN
Solar/Wind Harmer
4.909
944531AF1-118 GEN
Solar/Wind Harmer
16.546
235780M24_1
Solar/Wind Helper
0.922
944201AF1-088_MTX
Adder
61.569
957141AF2-008_MTX
Adder
30.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.15
TVALTFEXP_TVA->PJM
CLTF
2.933
NYPJM->LTFIMP_NY
CLTF
1.483
LGEELTFEXP_LGEE->PJM
CLTF
5.097
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.814
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.458
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.052
MECLTFEXP_MEC->PJM
CLTF
6.588
SIGELTFEXP_SIGE->PJM
CLTF
0.314

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:1.48
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
69.07
25194608D.CRK4
Adder
1.656
25196608WSDLE5
Adder
8.625
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
958171AF2-111 GEN
Solar/Wind Harmer
16.854
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
972173AH1-669 GEN
Solar/Wind Harmer
3.165
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
3429391JKCT 9G
Adder
6.235
270356AE2-297 GEN
Solar/Wind Harmer
0.006
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
270437AC2-090 C
Solar/Wind Harmer
0.002
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
24728505AND G1
Adder
2.32
958821AF2-173 GEN
Solar/Wind Harmer
5.771
270004AE1-209 GEN
Solar/Wind Harmer
0.893
946031AF1-268 GEN
Solar/Wind Harmer
3.889
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
2.961
960741AF2-365 GEN
Solar/Wind Harmer
1.775
970243AG2-164 GEN
Solar/Wind Harmer
2.07
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
972273AH1-721 GEN
Adder
41.409
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
970605AG2-385 GEN
Solar/Wind Harmer
1.988
971155AH1-034 GEN
Solar/Wind Harmer
3.802
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
25016408BKJDB1
50/50
0.272
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.759
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196508WSDLE4
Adder
8.537
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
972163AH1-664 GEN
Solar/Wind Harmer
6.955
972165AH1-665 GEN
Solar/Wind Harmer
5.57
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
253349AC2-067 GEN
Solar/Wind Harmer
1.665
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
971673AH1-337 GEN
Solar/Wind Harmer
2.979
241972AD1-140 GEN
Solar/Wind Harmer
0.495
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
270594AE1-207 GEN
Solar/Wind Harmer
4.227
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
965411AG1-406 GEN
Solar/Wind Harmer
1.371
970289AG2-191 GEN
Solar/Wind Harmer
0.697
965101AG1-375 GEN
Solar/Wind Harmer
3.623
270024AE2-089 GEN
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
270158DARBY CT3
Adder
4.334
24729505KEY G4
Adder
3.073
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
1.779
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803006KYGER 3HP
50/50
4.149
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
25194408D.CRK1
Adder
7.616
25194508D.CRK3
Adder
1.424
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.484
972045AH1-571 GEN
Solar/Wind Harmer
1.189
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
970107AG2-081 GEN
Solar/Wind Harmer
1.662
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
960161AF2-307 GEN
Solar/Wind Harmer
3.112
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.325
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
970825AG2-519 GEN
Solar/Wind Harmer
4.514
960441AF2-335 GEN
Solar/Wind Harmer
4.047
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270599AE1-208 GEN
Solar/Wind Harmer
3.479
270031AE2-169
Solar/Wind Harmer
2.087
971613AH1-306 GEN
Solar/Wind Harmer
1.811
971081AG2-670 GEN
Solar/Wind Harmer
2.763
25326509SID D
Adder
0.693
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
944541AF1-119 GEN
Solar/Wind Harmer
0.237
960971AF2-388 GEN
Solar/Wind Harmer
2.079
970239AG2-162 GEN
Solar/Wind Harmer
0.884
945391AF1-204 GEN
Solar/Wind Harmer
3.646
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.467
942221AE2-234 GEN
Solar/Wind Harmer
0.017
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
970077AG2-063 GEN
Solar/Wind Harmer
1.879
964781AG1-341 GEN
Solar/Wind Harmer
3.457
970241AG2-163 GEN
Solar/Wind Harmer
1.873
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
966021AG1-471 GEN
Solar/Wind Harmer
1.637
942861AE2-305 GEN
Solar/Wind Harmer
2.346
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.099
252507AC2-088 GEN
Solar/Wind Harmer
0.356
25196808ZIMRHP
Adder
78.156
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
25196008MFTGT1
Adder
1.327
945681AF1-233 GEN
Solar/Wind Harmer
11.914
270263AC1-001 GEN
Solar/Wind Harmer
0.606
339216AC1-074 GEN
Solar/Wind Harmer
0.163
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
25326309TAIT D
Adder
0.84
960071AF2-298 GEN
Solar/Wind Harmer
2.635
3429421JKCT 10G
Adder
6.235
3429241JKCT 3G
Adder
8.606
970773AG2-487 GEN
Solar/Wind Harmer
0.849
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.314
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
247536S-71 GEN
Solar/Wind Harmer
0.167
270005AE1-210 C O1
Solar/Wind Harmer
0.893
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970825AG2-519 GEN
Solar/Wind Harmer
1.446
276903AD2-071 C
Solar/Wind Harmer
4.31
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
40.612
970291AG2-192 GEN
Solar/Wind Harmer
0.477
958861AF2-177 GEN
Solar/Wind Harmer
1.57
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
970333AG2-219 GEN
Solar/Wind Harmer
2.53
270159DARBY CT4
Adder
4.344
964901AG1-354 GEN
Solar/Wind Harmer
5.126
970273AG2-179 GEN
Solar/Wind Harmer
1.177
962241AG1-070 GEN
Solar/Wind Harmer
1.783
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
59.081
957141AF2-008_MTX
Adder
29.541
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.447
LGEELTFEXP_LGEE->PJM
CLTF
4.851
WECLTFEXP_WEC->PJM
CLTF
1.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
MECLTFEXP_MEC->PJM
CLTF
6.369
SIGELTFEXP_SIGE->PJM
CLTF
0.3

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.87 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2015.35
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.391
971191AH1-055 GEN
Solar/Wind Harmer
84.832
25194608D.CRK4
Adder
1.654
25196608WSDLE5
Adder
8.615
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.382
253433AC1-085 GEN1
Solar/Wind Harmer
5.321
946181AF1-283 GEN
Solar/Wind Harmer
13.008
958171AF2-111 GEN
Solar/Wind Harmer
24.127
25196008MFTGT1
Adder
1.283
972167AH1-666 GEN
Solar/Wind Harmer
7.267
972173AH1-669 GEN
Solar/Wind Harmer
4.53
253406AD2-031_GEN
Solar/Wind Harmer
1.135
270273AD2-016 GEN
Solar/Wind Harmer
2.312
253415AE1-040 GEN
Solar/Wind Harmer
0.949
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
270222AC2-111 GEN
Solar/Wind Harmer
6.424
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.448
24803506KYGER 5LP
50/50
2.391
25016408BKJDB1
50/50
0.271
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
49.503
252524AE2-267 GEN
Solar/Wind Harmer
1.585
25196408WSDLE3
Adder
8.868
25196308WSDLE2
Adder
8.791
25196208WSDLE1
Adder
8.769
25196708WSDLE6
Adder
8.747
25196508WSDLE4
Adder
8.527
25196108MFTGT2
Adder
1.461
25196108MFTGT2
Adder
1.356
972163AH1-664 GEN
Solar/Wind Harmer
8.942
972165AH1-665 GEN
Solar/Wind Harmer
7.153
270367AC2-061_GEN
Solar/Wind Harmer
2.821
270269AC2-059
Solar/Wind Harmer
8.083
270340AC2-060 GEN
Solar/Wind Harmer
2.623
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253372AE2-315 SEC3
Adder
1.504
253372AE2-315 SEC3
Adder
1.504
944031AF1-071 GEN
Solar/Wind Harmer
0.792
25306009OHH W.
Adder
2.244
970689AG2-444 GEN
Solar/Wind Harmer
12.446
253349AC2-067 GEN
Solar/Wind Harmer
3.771
253400AC2-068 GEN
Solar/Wind Harmer
1.517
3429211JKCT 2G
Adder
8.48
270432AC2-029 GEN
Solar/Wind Harmer
4.791
971673AH1-337 GEN
Solar/Wind Harmer
3.016
241972AD1-140 GEN
Solar/Wind Harmer
2.901
270240V3-007_GEN2
Solar/Wind Harmer
4.001
971029AG2-637 GEN
Solar/Wind Harmer
9.695
339211AE2-254 GEN
Solar/Wind Harmer
0.945
270543AE2-219 C
Solar/Wind Harmer
3.168
970455AG2-298 GEN
Solar/Wind Harmer
3.705
970115AG2-085 GEN
Solar/Wind Harmer
2.315
24725505WLD G2 C
Solar/Wind Harmer
2.245
24699105WLD G1 C
Solar/Wind Harmer
2.218
961761AG1-017 GEN
Solar/Wind Harmer
0.24
270594AE1-207 GEN
Solar/Wind Harmer
7.932
945581AF1-223 GEN
Solar/Wind Harmer
2.447
965401AG1-405 GEN
Solar/Wind Harmer
3.049
965411AG1-406 GEN
Solar/Wind Harmer
1.368
965461AG1-414 GEN
Solar/Wind Harmer
1.189
970289AG2-191 GEN
Solar/Wind Harmer
0.996
965101AG1-375 GEN
Solar/Wind Harmer
5.181
270024AE2-089 GEN
Solar/Wind Harmer
2.385
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.098
252507AC2-088 GEN
Solar/Wind Harmer
2.011
25196808ZIMRHP
Adder
78.065
25194608D.CRK4
Adder
1.654
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
946171AF1-282 GEN
Solar/Wind Harmer
10.007
25196008MFTGT1
Adder
1.325
945681AF1-233 GEN
Solar/Wind Harmer
17.054
270263AC1-001 GEN
Solar/Wind Harmer
0.904
339216AC1-074 GEN
Solar/Wind Harmer
1.432
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
943111AE2-339 GEN
Solar/Wind Harmer
0.687
25326309TAIT D
Adder
0.839
960071AF2-298 GEN
Solar/Wind Harmer
3.776
3429421JKCT 10G
Adder
6.225
3429241JKCT 3G
Adder
8.591
942081AE2-220 GEN
Solar/Wind Harmer
4.134
270239V3-007_GEN1
Solar/Wind Harmer
1.113
971565AH1-281 GEN
Solar/Wind Harmer
1.274
253343AC1-166 GEN
Solar/Wind Harmer
0.67
253325AC1-069 GEN
Solar/Wind Harmer
0.647
971821AH1-427 GEN
Solar/Wind Harmer
6.132
24728605AND G2
Adder
2.316
247536S-71 GEN
Solar/Wind Harmer
2.401
270005AE1-210 C O1
Solar/Wind Harmer
3.222
965031AG1-367 GEN
Solar/Wind Harmer
5.896
970825AG2-519 GEN
Solar/Wind Harmer
1.372
276903AD2-071 C
Solar/Wind Harmer
5.52
270032AE2-172
Solar/Wind Harmer
2.51
945371AF1-202 GEN
Solar/Wind Harmer
3.764
339241AF1-083 GEN
Solar/Wind Harmer
0.89
970091AG2-072 GEN
Adder
40.521
970291AG2-192 GEN
Solar/Wind Harmer
0.682
958861AF2-177 GEN
Solar/Wind Harmer
5.663
270445AC2-157 GEN2
Solar/Wind Harmer
2.831
965651AG1-433 GEN
Solar/Wind Harmer
2.77
970333AG2-219 GEN
Solar/Wind Harmer
15.949
270159DARBY CT4
Adder
4.334
964901AG1-354 GEN
Solar/Wind Harmer
7.329
970273AG2-179 GEN
Solar/Wind Harmer
1.174
962241AG1-070 GEN
Solar/Wind Harmer
2.105
970593AG2-378 GEN
Solar/Wind Harmer
0.935
963741AG1-226 GEN
Solar/Wind Harmer
20.657
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.199
24385905FR-11G C
Solar/Wind Harmer
1.387
24387305FR-4G C
Solar/Wind Harmer
0.848
24803006KYGER 3HP
50/50
4.148
24802806KYGER 2HP
50/50
4.124
24802906KYGER 2LP
50/50
2.424
252509AD1-136 GEN
Solar/Wind Harmer
0.287
25183208HLCRTG
Solar/Wind Harmer
6.445
252519AF1-045_GEN
Solar/Wind Harmer
6.343
252516AE2-318_GEN
Solar/Wind Harmer
4.838
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253317AC1-085 GEN4
Solar/Wind Harmer
8.382
253394AE2-221_GEN
Solar/Wind Harmer
4.278
253398AE2-221_GEN2
Solar/Wind Harmer
4.278
270186AC1-089 GEN
Solar/Wind Harmer
5.345
962581AG1-107 GEN
Solar/Wind Harmer
4.348
961491AF2-440 GEN
Solar/Wind Harmer
1.807
970235AG2-159 GEN
Solar/Wind Harmer
3.391
970235AG2-159 GEN
Solar/Wind Harmer
2.07
339221AD2-048_GEN
Solar/Wind Harmer
1.288
972043AH1-570 GEN
Solar/Wind Harmer
2.042
972045AH1-571 GEN
Solar/Wind Harmer
1.634
253370AE2-315 SEC1
Adder
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.171
970107AG2-081 GEN
Solar/Wind Harmer
2.378
25322209TAIT E
Adder
7.474
25322209TAIT E
Adder
7.306
25326109MON D
Adder
0.983
24728805RICHG1
Adder
2.726
24728905RICHG2
Adder
2.726
942891AE2-308 GEN
Solar/Wind Harmer
7.111
960161AF2-307 GEN
Solar/Wind Harmer
4.331
24379505HDWTR1G C
Solar/Wind Harmer
5.113
270209AC1-174_GEN
Solar/Wind Harmer
3.609
926881AC1-175 GEN
Solar/Wind Harmer
3.609
270383AD1-128 GEN
Solar/Wind Harmer
3.893
970883AG2-550 GEN
Solar/Wind Harmer
6.188
970885AG2-551 GEN
Solar/Wind Harmer
1.439
964571AG1-320 GEN
Solar/Wind Harmer
4.907
970825AG2-519 GEN
Solar/Wind Harmer
6.148
960441AF2-335 GEN
Solar/Wind Harmer
5.788
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
2.78
970653AG2-424 GEN
Solar/Wind Harmer
1.005
964611AG1-324 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
0.296
270201AC2-176 GEN
Solar/Wind Harmer
2.885
270518AE2-148 GEN
Solar/Wind Harmer
6.747
270599AE1-208 GEN
Solar/Wind Harmer
4.424
270031AE2-169
Solar/Wind Harmer
4.424
971081AG2-670 GEN
Solar/Wind Harmer
3.951
25326509SID D
Adder
0.691
270444AC2-157 GEN1
Solar/Wind Harmer
2.831
944541AF1-119 GEN
Solar/Wind Harmer
2.123
960971AF2-388 GEN
Solar/Wind Harmer
5.54
970239AG2-162 GEN
Solar/Wind Harmer
5.558
339236AF1-050_GEN
Solar/Wind Harmer
0.916
945391AF1-204 GEN
Solar/Wind Harmer
6.838
253378AE2-206_GEN
Solar/Wind Harmer
1.747
276820AF1-078_GEN
Solar/Wind Harmer
0.776
339231AF1-038_GEN
Solar/Wind Harmer
0.875
942221AE2-234 GEN
Solar/Wind Harmer
0.349
339255AE2-071 GEN
Solar/Wind Harmer
0.496
970077AG2-063 GEN
Solar/Wind Harmer
2.523
964781AG1-341 GEN
Solar/Wind Harmer
4.942
970241AG2-163 GEN
Solar/Wind Harmer
11.476
237033AB1-150 GEN
Solar/Wind Helper
0.373
3429391JKCT 9G
Adder
6.225
270356AE2-297 GEN
Solar/Wind Harmer
3.136
970093AG2-073 GEN
Solar/Wind Harmer
6.785
966571AG1-526 GEN
Solar/Wind Harmer
14.46
270437AC2-090 C
Solar/Wind Harmer
3.61
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253333AC1-068 GEN
Solar/Wind Harmer
0.647
24728705AND G3
Adder
4.843
24728505AND G1
Adder
2.316
958821AF2-173 GEN
Solar/Wind Harmer
8.255
270004AE1-209 GEN
Solar/Wind Harmer
3.222
946031AF1-268 GEN
Solar/Wind Harmer
4.852
962031AG1-047 GEN
Solar/Wind Harmer
1.696
957741AF2-068 GEN
Solar/Wind Harmer
8.417
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.366
247642Z2-115 C
Solar/Wind Harmer
0.033
971617AH1-308 GEN
Solar/Wind Harmer
2.954
960741AF2-365 GEN
Solar/Wind Harmer
2.538
970243AG2-164 GEN
Solar/Wind Harmer
13.049
970519AG2-331 GEN
Solar/Wind Harmer
8.767
970699AG2-449 GEN
Solar/Wind Harmer
5.799
972273AH1-721 GEN
Adder
41.309
970193AG2-126 GEN
Solar/Wind Harmer
7.36
970273AG2-179 GEN
Solar/Wind Harmer
1.875
339250AF1-203 GEN
Solar/Wind Harmer
0.284
962251AG1-071 GEN
Solar/Wind Harmer
2.573
970605AG2-385 GEN
Solar/Wind Harmer
2.523
971155AH1-034 GEN
Solar/Wind Harmer
4.659
944531AF1-118 GEN
Solar/Wind Harmer
16.107
235780M24_1
Solar/Wind Helper
0.926
958711AF2-162 GEN
Solar/Wind Harmer
0.513
270156DARBY CT1
Adder
4.404
270157DARBY CT2
Adder
4.393
270158DARBY CT3
Adder
4.323
24729505KEY G4
Adder
3.066
945631AF1-228 GEN
Solar/Wind Harmer
2.201
963841AG1-237 GEN
Solar/Wind Harmer
4.916
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
24386205FR-12G C
Solar/Wind Harmer
0.715
24386405FR-21G C
Solar/Wind Harmer
0.718
24386605FR-22G C
Solar/Wind Harmer
0.718
24387005FR-3G C
Solar/Wind Harmer
0.66
944201AF1-088_MTX
Adder
58.943
957141AF2-008_MTX
Adder
29.471
LAGNLTFEXP_LAGN->PJM
CLTF
5.654
TVALTFEXP_TVA->PJM
CLTF
2.763
NYPJM->LTFIMP_NY
CLTF
1.454
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
1.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.093
AH1-155LTFEXP_AH1-155->PJM
LTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.298
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.278
MECLTFEXP_MEC->PJM
CLTF
6.349
SIGELTFEXP_SIGE->PJM
CLTF
0.299

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1731.23
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.445
25194508D.CRK3
Adder
1.392
252509AD1-136 GEN
Solar/Wind Harmer
0.247
252519AF1-045_GEN
Solar/Wind Harmer
5.249
252516AE2-318_GEN
Solar/Wind Harmer
4.004
970235AG2-159 GEN
Solar/Wind Harmer
3.379
970235AG2-159 GEN
Solar/Wind Harmer
2.062
24728805RICHG1
Adder
2.802
24728905RICHG2
Adder
2.802
970239AG2-162 GEN
Solar/Wind Harmer
7.946
24379505HDWTR1G C
Solar/Wind Harmer
5.682
270209AC1-174_GEN
Solar/Wind Harmer
4.01
926881AC1-175 GEN
Solar/Wind Harmer
4.01
25183208HLCRTG
Solar/Wind Harmer
4.17
270383AD1-128 GEN
Solar/Wind Harmer
4.168
970825AG2-519 GEN
Solar/Wind Harmer
6.785
970883AG2-550 GEN
Solar/Wind Harmer
6.422
970885AG2-551 GEN
Solar/Wind Harmer
1.494
960441AF2-335 GEN
Solar/Wind Harmer
6.4
270444AC2-157 GEN1
Solar/Wind Harmer
3.557
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.716
964611AG1-324 GEN
Solar/Wind Harmer
0.318
270599AE1-208 GEN
Solar/Wind Harmer
4.914
270031AE2-169
Solar/Wind Harmer
4.914
270201AC2-176 GEN
Solar/Wind Harmer
3.077
945391AF1-204 GEN
Solar/Wind Harmer
8.18
964571AG1-320 GEN
Solar/Wind Harmer
4.801
253370AE2-315 SEC1
Adder
1.168
25322209TAIT E
Adder
5.656
25322209TAIT E
Adder
5.529
944541AF1-119 GEN
Solar/Wind Harmer
2.371
960971AF2-388 GEN
Solar/Wind Harmer
6.188
25326109MON D
Adder
0.736
339221AD2-048_GEN
Solar/Wind Harmer
0.86
970241AG2-163 GEN
Solar/Wind Harmer
13.959
966841AG1-555 GEN
Solar/Wind Harmer
1.358
970653AG2-424 GEN
Solar/Wind Harmer
2.609
970653AG2-424 GEN
Solar/Wind Harmer
0.943
942221AE2-234 GEN
Solar/Wind Harmer
0.385
971125AH1-004 GEN
Solar/Wind Harmer
2.088
970107AG2-081 GEN
Solar/Wind Harmer
1.566
945421AF1-207 GEN
Solar/Wind Harmer
7.319
957841AF2-078 GEN
Solar/Wind Harmer
3.149
972043AH1-570 GEN
Solar/Wind Harmer
1.297
972045AH1-571 GEN
Solar/Wind Harmer
1.038
276916AD2-100_GEN
Solar/Wind Harmer
10.542
276911AD2-131_GEN
Solar/Wind Harmer
2.131
957381AF2-032 GEN
Solar/Wind Harmer
0.209
276763AC1-053 GEN1
Solar/Wind Harmer
1.963
276764AC1-053 GEN2
Solar/Wind Harmer
1.963
960611AF2-352 GEN
Solar/Wind Harmer
1.123
274674JOLIET 9 ;6U
Adder
6.909
972259AH1-714 GEN
Adder
8.555
274803UNIV PARK;6U
Adder
2.611
274808UNIV PK N;4U
Adder
2.229
274695ROCKY RD ;2P
Adder
4.974
274693ROCKY RD ;1P
Adder
4.925
274697ROCKY RD ;3P
Adder
1.351
274696ROCKY RD ;4P
Adder
5.092
274770LINCOLN ;1U
Adder
3.769
274771LINCOLN ;2U
Adder
3.769
25196008MFTGT1
Adder
1.408
25194608D.CRK4
Adder
1.618
252507AC2-088 GEN
Solar/Wind Harmer
1.731
25196808ZIMRHP
Adder
61.966
970091AG2-072 GEN
Adder
56.238
970333AG2-219 GEN
Solar/Wind Harmer
22.8
942081AE2-220 GEN
Solar/Wind Harmer
4.594
270239V3-007_GEN1
Solar/Wind Harmer
1.236
24728605AND G2
Adder
2.599
270005AE1-210 C O1
Solar/Wind Harmer
3.583
965031AG1-367 GEN
Solar/Wind Harmer
6.555
970825AG2-519 GEN
Solar/Wind Harmer
1.514
270445AC2-157 GEN2
Solar/Wind Harmer
3.557
276903AD2-071 C
Solar/Wind Harmer
6.281
247536S-71 GEN
Solar/Wind Harmer
2.52
270032AE2-172
Solar/Wind Harmer
2.857
970291AG2-192 GEN
Solar/Wind Harmer
0.784
971565AH1-281 GEN
Solar/Wind Harmer
1.205
945371AF1-202 GEN
Solar/Wind Harmer
4.196
339216AC1-074 GEN
Solar/Wind Harmer
0.989
960071AF2-298 GEN
Solar/Wind Harmer
2.911
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.105
25326309TAIT D
Adder
0.635
958861AF2-177 GEN
Solar/Wind Harmer
6.32
965651AG1-433 GEN
Solar/Wind Harmer
3.094
963741AG1-226 GEN
Solar/Wind Harmer
25.125
24385905FR-11G C
Solar/Wind Harmer
4.498
24387305FR-4G C
Solar/Wind Harmer
2.75
24791305MDL-5G
Solar/Wind Harmer
1.272
940581AE2-045 GEN
Solar/Wind Harmer
5.167
971605AH1-302 GEN
Solar/Wind Harmer
4.418
965911AG1-460 GEN
Solar/Wind Harmer
0.698
943111AE2-339 GEN
Solar/Wind Harmer
0.442
276615X2-022 GEN
Solar/Wind Harmer
0.974
274880W4-005 GEN4
Solar/Wind Harmer
1.501
963831AG1-236 GEN
Solar/Wind Harmer
4.882
964861AG1-349 GEN
Solar/Wind Harmer
3.873
971917AH1-482 GEN
Solar/Wind Harmer
4.469
958381AF2-132 GEN
Solar/Wind Harmer
4.46
972175AH1-670 GEN
Solar/Wind Harmer
6.696
274854TWINGROVE;U2
Solar/Wind Harmer
3.408
270055AF2-134 C O1
Solar/Wind Harmer
1.456
3429421JKCT 10G
Adder
3.867
3429241JKCT 3G
Adder
5.42
274732ELWOOD EC;7P
Adder
7.386
274674JOLIET 9 ;6U
Adder
6.909
274801UNIV PARK;4U
Adder
2.612
274676JOLIET 29;8U
Adder
13.743
274745AC1-111 GEN9
Adder
2.501
274812UNIV PK N;8U
Adder
2.239
274773LINCOLN ;4U
Adder
3.769
274774LINCOLN ;5U
Adder
3.769
927014AC1-188 GEN
Solar/Wind Helper
0.882
270263AC1-001 GEN
Solar/Wind Helper
0.627
270331AC1-082 GEN3
Solar/Wind Helper
0.1
960001AF2-291 GEN
Solar/Wind Helper
0.556
276726Z2-087_GEN
Solar/Wind Harmer
1.849
25016408BKJDB1
50/50
0.314
25196108MFTGT2
Adder
1.553
25196108MFTGT2
Adder
1.442
252524AE2-267 GEN
Solar/Wind Harmer
1.576
25196408WSDLE3
Adder
8.818
25196308WSDLE2
Adder
8.742
25196208WSDLE1
Adder
8.72
25196708WSDLE6
Adder
8.698
25196508WSDLE4
Adder
8.479
971985AH1-537 GEN
Solar/Wind Harmer
17.666
944031AF1-071 GEN
Solar/Wind Harmer
0.792
270240V3-007_GEN2
Solar/Wind Harmer
4.445
971673AH1-337 GEN
Solar/Wind Harmer
3.08
971029AG2-637 GEN
Solar/Wind Harmer
9.944
270543AE2-219 C
Solar/Wind Harmer
3.289
970115AG2-085 GEN
Solar/Wind Harmer
2.56
24725505WLD G2 C
Solar/Wind Harmer
2.539
24699105WLD G1 C
Solar/Wind Harmer
2.509
270594AE1-207 GEN
Solar/Wind Harmer
9.028
253349AC2-067 GEN
Solar/Wind Harmer
3.02
253400AC2-068 GEN
Solar/Wind Harmer
1.214
965461AG1-414 GEN
Solar/Wind Harmer
1.368
970289AG2-191 GEN
Solar/Wind Harmer
1.147
945581AF1-223 GEN
Solar/Wind Harmer
2.728
961761AG1-017 GEN
Solar/Wind Harmer
0.256
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
25306009OHH W.
Adder
1.694
253372AE2-315 SEC3
Adder
1.105
253372AE2-315 SEC3
Adder
1.105
965101AG1-375 GEN
Solar/Wind Harmer
5.783
970455AG2-298 GEN
Solar/Wind Harmer
3.424
958711AF2-162 GEN
Solar/Wind Harmer
0.573
963841AG1-237 GEN
Solar/Wind Harmer
6.011
270024AE2-089 GEN
Solar/Wind Harmer
2.562
24386205FR-12G C
Solar/Wind Harmer
2.319
24386405FR-21G C
Solar/Wind Harmer
2.327
24386605FR-22G C
Solar/Wind Harmer
2.327
24387005FR-3G C
Solar/Wind Harmer
2.141
24729505KEY G4
Adder
3.433
24690905MDL-1G C
Solar/Wind Harmer
4.237
270180AB1-006 GEN1
Solar/Wind Harmer
3.795
946581AF1-322 GEN
Solar/Wind Harmer
5.399
24691005MDL-2G C
Solar/Wind Harmer
1.952
24697605MDL-3G C
Solar/Wind Harmer
1.946
24697905MDL-4G C
Solar/Wind Harmer
1.211
270181AB1-006 GEN2
Solar/Wind Harmer
0.377
944221AF1-090 GEN
Solar/Wind Harmer
5.552
958391AF2-133 GEN
Solar/Wind Harmer
4.51
276785W4-005 GEN1
Solar/Wind Harmer
1.501
276174W4-005 GEN2
Solar/Wind Harmer
1.501
276849AB2-070 GEN2
Solar/Wind Harmer
1.115
276848AB2-070 GEN3
Solar/Wind Harmer
1.115
270536AF1-215 GEN2
Solar/Wind Harmer
2.185
276655WTG1_EQ
Solar/Wind Harmer
4.19
3429211JKCT 2G
Adder
5.349
274731ELWOOD EC;2P
Adder
7.387
274733ELWOOD EC;3P
Adder
7.387
274735ELWOOD EC;4P
Adder
7.387
274728ELWOOD EC;5P
Adder
7.386
972227AH1-698 GEN1
Adder
1.172
274675JOLIET 29;7U
Adder
13.743
274675JOLIET 29;7U
Adder
13.252
972037AH1-567 GEN1
Adder
0.082
274687WILL CNTY;4U
Adder
12.515
274687WILL CNTY;4U
Adder
12.515
274827FISK ;RP
Adder
3.472
274746AC1-111 G10
Adder
2.501
274744AC1-111 GEN8
Adder
2.501
274814UNIV PK N;0U
Adder
2.259
274807UNIV PK N;3U
Adder
2.254
274805UNIV PK N;1U
Adder
2.244
274811UNIV PK N;7U
Adder
2.239
274775LINCOLN ;6U
Adder
3.769
274776LINCOLN ;7U
Adder
3.769
274777LINCOLN ;8U
Adder
1.5
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.1
25196008MFTGT1
Adder
1.364
25196608WSDLE5
Adder
8.567
25194608D.CRK4
Adder
1.618
252510AF1-249 C
Solar/Wind Harmer
0.399
270222AC2-111 GEN
Solar/Wind Harmer
6.429
270356AE2-297 GEN
Solar/Wind Harmer
3.466
970243AG2-164 GEN
Solar/Wind Harmer
18.655
970519AG2-331 GEN
Solar/Wind Harmer
12.533
970699AG2-449 GEN
Solar/Wind Harmer
8.291
270437AC2-090 C
Solar/Wind Harmer
4.012
24728705AND G3
Adder
5.435
24728505AND G1
Adder
2.599
958821AF2-173 GEN
Solar/Wind Harmer
9.177
270004AE1-209 GEN
Solar/Wind Harmer
3.583
946031AF1-268 GEN
Solar/Wind Harmer
5.309
970289AG2-191 GEN
Solar/Wind Harmer
0.463
970291AG2-192 GEN
Solar/Wind Harmer
0.421
962031AG1-047 GEN
Solar/Wind Harmer
1.809
957741AF2-068 GEN
Solar/Wind Harmer
8.978
247642Z2-115 C
Solar/Wind Harmer
0.038
970193AG2-126 GEN
Solar/Wind Harmer
8.804
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.105
971617AH1-308 GEN
Solar/Wind Harmer
3.173
24755605MDL-5G
Solar/Wind Harmer
1.272
970781AG2-491 GEN
Solar/Wind Harmer
5.276
944531AF1-118 GEN
Solar/Wind Harmer
18.052
959141AF2-205 GEN
Solar/Wind Harmer
3.031
942481AE2-261 GEN
Solar/Wind Harmer
14.959
276621W2-048 GEN
Solar/Wind Harmer
3.102
276838X2-022 GEN2
Solar/Wind Harmer
0.116
276686W4-005 GEN3
Solar/Wind Harmer
1.501
971993AH1-541 GEN
Solar/Wind Harmer
4.586
276668AB2-070 GEN1
Solar/Wind Harmer
1.115
964401AG1-302 GEN
Solar/Wind Harmer
4.46
966571AG1-526 GEN
Solar/Wind Harmer
10.766
274853TWINGROVE;U1
Solar/Wind Harmer
3.481
965091AG1-374 GEN
Solar/Wind Harmer
14.491
959611AF2-252 GEN
Solar/Wind Harmer
1.123
270535AF1-215 GEN1
Solar/Wind Harmer
2.185
3429391JKCT 9G
Adder
3.867
274729ELWOOD EC;1P
Adder
7.387
274730ELWOOD EC;6P
Adder
7.386
274734ELWOOD EC;8P
Adder
7.386
274736ELWOOD EC;9P
Adder
7.386
972228AH1-698 GEN2
Adder
1.665
274800UNIV PARK;3U
Adder
2.612
972038AH1-567 GEN2
Adder
0.163
274676JOLIET 29;8U
Adder
13.252
274802UNIV PARK;5U
Adder
2.611
274826FISK ;BP
Adder
4.898
274772LINCOLN ;3U
Adder
3.769
957541AF2-048 GEN
Solar/Wind Helper
0.885
270273AD2-016 GEN
Solar/Wind Helper
1.46
944201AF1-088_MTX
Adder
74.065
957141AF2-008_MTX
Adder
37.033
LAGNLTFEXP_LAGN->PJM
CLTF
5.235
TVALTFEXP_TVA->PJM
CLTF
2.34
NYPJM->LTFIMP_NY
CLTF
1.1
LGEELTFEXP_LGEE->PJM
CLTF
5.188
WECLTFEXP_WEC->PJM
CLTF
1.697
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.679
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.731
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.315
MECLTFEXP_MEC->PJM
CLTF
7.201
SIGELTFEXP_SIGE->PJM
CLTF
0.328

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1664.56
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.248
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.023
970235AG2-159 GEN
Solar/Wind Harmer
3.396
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
7.992
24379505HDWTR1G C
Solar/Wind Harmer
5.715
270209AC1-174_GEN
Solar/Wind Harmer
4.034
926881AC1-175 GEN
Solar/Wind Harmer
4.034
25183208HLCRTG
Solar/Wind Harmer
4.196
270383AD1-128 GEN
Solar/Wind Harmer
4.194
970825AG2-519 GEN
Solar/Wind Harmer
6.83
970883AG2-550 GEN
Solar/Wind Harmer
6.465
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
6.443
270444AC2-157 GEN1
Solar/Wind Harmer
3.581
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.721
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
4.948
270031AE2-169
Solar/Wind Harmer
4.948
270201AC2-176 GEN
Solar/Wind Harmer
3.099
945391AF1-204 GEN
Solar/Wind Harmer
8.239
964571AG1-320 GEN
Solar/Wind Harmer
4.836
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
2.389
960971AF2-388 GEN
Solar/Wind Harmer
6.235
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.867
970241AG2-163 GEN
Solar/Wind Harmer
14.065
966841AG1-555 GEN
Solar/Wind Harmer
1.368
970653AG2-424 GEN
Solar/Wind Harmer
2.629
970653AG2-424 GEN
Solar/Wind Harmer
0.95
942221AE2-234 GEN
Solar/Wind Harmer
0.388
971125AH1-004 GEN
Solar/Wind Harmer
2.105
970107AG2-081 GEN
Solar/Wind Harmer
1.579
945421AF1-207 GEN
Solar/Wind Harmer
7.378
957841AF2-078 GEN
Solar/Wind Harmer
3.175
972043AH1-570 GEN
Solar/Wind Harmer
1.308
972045AH1-571 GEN
Solar/Wind Harmer
1.046
276916AD2-100_GEN
Solar/Wind Harmer
10.632
276911AD2-131_GEN
Solar/Wind Harmer
2.149
957381AF2-032 GEN
Solar/Wind Harmer
0.211
276763AC1-053 GEN1
Solar/Wind Harmer
1.979
276764AC1-053 GEN2
Solar/Wind Harmer
1.979
960611AF2-352 GEN
Solar/Wind Harmer
1.133
274674JOLIET 9 ;6U
Adder
6.975
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
274697ROCKY RD ;3P
Adder
1.364
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
25196008MFTGT1
Adder
1.414
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
1.738
25196808ZIMRHP
Adder
62.29
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
22.935
942081AE2-220 GEN
Solar/Wind Harmer
4.621
270239V3-007_GEN1
Solar/Wind Harmer
1.244
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
3.606
965031AG1-367 GEN
Solar/Wind Harmer
6.598
970825AG2-519 GEN
Solar/Wind Harmer
1.524
270445AC2-157 GEN2
Solar/Wind Harmer
3.581
276903AD2-071 C
Solar/Wind Harmer
6.323
247536S-71 GEN
Solar/Wind Harmer
2.537
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.79
971565AH1-281 GEN
Solar/Wind Harmer
1.214
945371AF1-202 GEN
Solar/Wind Harmer
4.226
339216AC1-074 GEN
Solar/Wind Harmer
0.996
960071AF2-298 GEN
Solar/Wind Harmer
2.932
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
6.367
965651AG1-433 GEN
Solar/Wind Harmer
3.117
963741AG1-226 GEN
Solar/Wind Harmer
25.317
24385905FR-11G C
Solar/Wind Harmer
4.533
24387305FR-4G C
Solar/Wind Harmer
2.771
24791305MDL-5G
Solar/Wind Harmer
1.283
940581AE2-045 GEN
Solar/Wind Harmer
5.21
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
943111AE2-339 GEN
Solar/Wind Harmer
0.446
276615X2-022 GEN
Solar/Wind Harmer
0.982
274880W4-005 GEN4
Solar/Wind Harmer
1.514
963831AG1-236 GEN
Solar/Wind Harmer
4.924
964861AG1-349 GEN
Solar/Wind Harmer
3.906
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
4.498
972175AH1-670 GEN
Solar/Wind Harmer
6.754
274854TWINGROVE;U2
Solar/Wind Harmer
3.439
270055AF2-134 C O1
Solar/Wind Harmer
1.469
3429421JKCT 10G
Adder
3.902
3429241JKCT 3G
Adder
5.47
274732ELWOOD EC;7P
Adder
7.457
274674JOLIET 9 ;6U
Adder
6.975
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
1.583
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
17.742
944031AF1-071 GEN
Solar/Wind Harmer
0.797
270240V3-007_GEN2
Solar/Wind Harmer
4.472
971673AH1-337 GEN
Solar/Wind Harmer
3.1
971029AG2-637 GEN
Solar/Wind Harmer
10.008
270543AE2-219 C
Solar/Wind Harmer
3.31
970115AG2-085 GEN
Solar/Wind Harmer
2.577
24725505WLD G2 C
Solar/Wind Harmer
2.556
24699105WLD G1 C
Solar/Wind Harmer
2.526
270594AE1-207 GEN
Solar/Wind Harmer
9.091
253349AC2-067 GEN
Solar/Wind Harmer
3.041
253400AC2-068 GEN
Solar/Wind Harmer
1.223
965461AG1-414 GEN
Solar/Wind Harmer
1.378
970289AG2-191 GEN
Solar/Wind Harmer
1.155
945581AF1-223 GEN
Solar/Wind Harmer
2.747
961761AG1-017 GEN
Solar/Wind Harmer
0.258
339243AC2-075 GEN1
Solar/Wind Harmer
0.27
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
5.825
970455AG2-298 GEN
Solar/Wind Harmer
3.45
958711AF2-162 GEN
Solar/Wind Harmer
0.577
963841AG1-237 GEN
Solar/Wind Harmer
6.058
270024AE2-089 GEN
Solar/Wind Harmer
2.582
24386205FR-12G C
Solar/Wind Harmer
2.337
24386405FR-21G C
Solar/Wind Harmer
2.346
24386605FR-22G C
Solar/Wind Harmer
2.346
24387005FR-3G C
Solar/Wind Harmer
2.158
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
4.271
270180AB1-006 GEN1
Solar/Wind Harmer
3.826
946581AF1-322 GEN
Solar/Wind Harmer
5.443
24691005MDL-2G C
Solar/Wind Harmer
1.967
24697605MDL-3G C
Solar/Wind Harmer
1.961
24697905MDL-4G C
Solar/Wind Harmer
1.221
270181AB1-006 GEN2
Solar/Wind Harmer
0.38
944221AF1-090 GEN
Solar/Wind Harmer
5.598
958391AF2-133 GEN
Solar/Wind Harmer
4.549
276785W4-005 GEN1
Solar/Wind Harmer
1.514
276174W4-005 GEN2
Solar/Wind Harmer
1.514
276849AB2-070 GEN2
Solar/Wind Harmer
1.125
276848AB2-070 GEN3
Solar/Wind Harmer
1.125
270536AF1-215 GEN2
Solar/Wind Harmer
2.204
276655WTG1_EQ
Solar/Wind Harmer
4.228
3429211JKCT 2G
Adder
5.399
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.4
270222AC2-111 GEN
Solar/Wind Harmer
6.463
270356AE2-297 GEN
Solar/Wind Harmer
3.485
970243AG2-164 GEN
Solar/Wind Harmer
18.765
970519AG2-331 GEN
Solar/Wind Harmer
12.607
970699AG2-449 GEN
Solar/Wind Harmer
8.34
270437AC2-090 C
Solar/Wind Harmer
4.035
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
9.237
270004AE1-209 GEN
Solar/Wind Harmer
3.606
946031AF1-268 GEN
Solar/Wind Harmer
5.344
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
1.822
957741AF2-068 GEN
Solar/Wind Harmer
9.042
247642Z2-115 C
Solar/Wind Harmer
0.038
970193AG2-126 GEN
Solar/Wind Harmer
8.868
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
1.283
970781AG2-491 GEN
Solar/Wind Harmer
5.319
944531AF1-118 GEN
Solar/Wind Harmer
18.201
959141AF2-205 GEN
Solar/Wind Harmer
3.057
942481AE2-261 GEN
Solar/Wind Harmer
15.086
276621W2-048 GEN
Solar/Wind Harmer
3.128
276838X2-022 GEN2
Solar/Wind Harmer
0.117
276686W4-005 GEN3
Solar/Wind Harmer
1.514
971993AH1-541 GEN
Solar/Wind Harmer
4.625
276668AB2-070 GEN1
Solar/Wind Harmer
1.125
964401AG1-302 GEN
Solar/Wind Harmer
4.498
966571AG1-526 GEN
Solar/Wind Harmer
10.861
274853TWINGROVE;U1
Solar/Wind Harmer
3.512
965091AG1-374 GEN
Solar/Wind Harmer
14.619
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
2.204
3429391JKCT 9G
Adder
3.902
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
274772LINCOLN ;3U
Adder
3.805
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
276726Z2-087_GEN
Solar/Wind Harmer
1.865
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1561.02
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.678
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
1.269
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.007
25196008MFTGT1
Adder
1.414
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
0.307
25196808ZIMRHP
Adder
62.29
970773AG2-487 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
3.629
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.005
970883AG2-550 GEN
Solar/Wind Harmer
4.51
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
4.495
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.281
971613AH1-306 GEN
Solar/Wind Harmer
2.071
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
3.883
270031AE2-169
Solar/Wind Harmer
2.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
4.382
964571AG1-320 GEN
Solar/Wind Harmer
3.758
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
0.267
960971AF2-388 GEN
Solar/Wind Harmer
2.335
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
0.43
970653AG2-424 GEN
Solar/Wind Harmer
1.834
970653AG2-424 GEN
Solar/Wind Harmer
0.95
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971125AH1-004 GEN
Solar/Wind Harmer
1.469
970107AG2-081 GEN
Solar/Wind Harmer
1.102
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972043AH1-570 GEN
Solar/Wind Harmer
0.949
972045AH1-571 GEN
Solar/Wind Harmer
0.76
276916AD2-100_GEN
Solar/Wind Harmer
7.418
276911AD2-131_GEN
Solar/Wind Harmer
0.489
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970321AG2-212 GEN
Solar/Wind Harmer
1.448
942891AE2-308 GEN
Solar/Wind Harmer
3.277
971081AG2-670 GEN
Solar/Wind Harmer
2.441
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.134
958491AF2-143 GEN
Solar/Wind Harmer
4.777
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.764
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.553
274674JOLIET 9 ;6U
Adder
6.975
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
274697ROCKY RD ;3P
Adder
1.364
962691AG1-118 GEN
Solar/Wind Harmer
9.438
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
970921AG2-575 GEN
Solar/Wind Harmer
3.145
970921AG2-575 GEN
Solar/Wind Harmer
1.048
276603SUBLETTE C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.288
971343AH1-151 GEN
Solar/Wind Harmer
6.288
942991AE2-321 GEN
Solar/Wind Harmer
3.508
971333AH1-146 GEN
Solar/Wind Harmer
6.283
971335AH1-147 GEN
Solar/Wind Harmer
6.283
938861AE1-114 GEN
Solar/Wind Harmer
1.78
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
3.864
965791AG1-447 GEN
Solar/Wind Harmer
2.834
24441505OLIV SLR
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.697
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
0.997
965031AG1-367 GEN
Solar/Wind Harmer
4.603
970825AG2-519 GEN
Solar/Wind Harmer
1.603
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
4.926
247536S-71 GEN
Solar/Wind Harmer
0.176
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.551
971565AH1-281 GEN
Solar/Wind Harmer
0.847
945371AF1-202 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.113
960071AF2-298 GEN
Solar/Wind Harmer
2.043
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
1.761
965651AG1-433 GEN
Solar/Wind Harmer
1.167
963741AG1-226 GEN
Solar/Wind Harmer
9.29
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
276615X2-022 GEN
Solar/Wind Harmer
0.037
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.362
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
2.851
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.729
970245AG2-165 GEN
Solar/Wind Harmer
1.448
971821AH1-427 GEN
Solar/Wind Harmer
3.331
970373AG2-245 GEN
Solar/Wind Harmer
6.927
3429421JKCT 10G
Adder
3.902
939401AE1-172 GEN
Solar/Wind Harmer
2.433
3429241JKCT 3G
Adder
5.47
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.614
971997AH1-543 GEN
Solar/Wind Harmer
1.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.457
276776AD2-060 GEN
Solar/Wind Harmer
0.33
274674JOLIET 9 ;6U
Adder
6.975
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.056
962781AG1-127 GEN
Solar/Wind Harmer
2.993
957471AF2-041 GEN
Solar/Wind Harmer
9.432
959081AF2-199 GEN
Solar/Wind Harmer
3.144
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
970819AG2-516 GEN
Solar/Wind Harmer
3.764
971475AH1-234 GEN
Solar/Wind Harmer
1.52
964901AG1-354 GEN
Solar/Wind Harmer
4.633
962241AG1-070 GEN
Solar/Wind Harmer
1.643
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
2.063
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.056
971029AG2-637 GEN
Solar/Wind Harmer
6.982
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.798
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.833
253349AC2-067 GEN
Solar/Wind Harmer
1.341
253400AC2-068 GEN
Solar/Wind Harmer
0.539
970289AG2-191 GEN
Solar/Wind Harmer
0.806
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
4.064
970455AG2-298 GEN
Solar/Wind Harmer
2.674
963841AG1-237 GEN
Solar/Wind Harmer
1.675
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.096
971611AH1-305 GEN
Solar/Wind Harmer
2.122
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.547
941731AE2-173 GEN
Solar/Wind Harmer
2.815
339211AE2-254 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
3.303
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
4.381
270071AF1-092 GEN
Solar/Wind Harmer
6.208
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.399
957751AF2-069 GEN
Solar/Wind Harmer
0.106
926823AC1-168 GEN
Solar/Wind Harmer
0.547
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.373
970833AG2-524 GEN
Solar/Wind Harmer
3.487
970833AG2-524 GEN
Solar/Wind Harmer
2.324
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
960591AF2-350 GEN
Solar/Wind Harmer
3.162
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
971675AH1-338 GEN
Solar/Wind Harmer
1.227
971171AH1-044 GEN
Solar/Wind Harmer
6.288
961011AF2-392 GEN
Solar/Wind Harmer
1.844
971681AH1-341 GEN
Solar/Wind Harmer
5.059
971177AH1-047 GEN
Solar/Wind Harmer
1.937
971411AH1-196 GEN
Solar/Wind Harmer
4.711
276612AE2-035 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.755
241972AD1-140 GEN
Solar/Wind Harmer
0.34
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
3.38
971347AH1-153 GEN
Solar/Wind Harmer
4.502
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.052
270222AC2-111 GEN
Solar/Wind Harmer
2.803
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970243AG2-164 GEN
Solar/Wind Harmer
2.969
970519AG2-331 GEN
Solar/Wind Harmer
13.197
970699AG2-449 GEN
Solar/Wind Harmer
1.269
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
6.444
270004AE1-209 GEN
Solar/Wind Harmer
0.997
946031AF1-268 GEN
Solar/Wind Harmer
4.275
970191AG2-125 GEN
Solar/Wind Harmer
1.095
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.308
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.187
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.711
944531AF1-118 GEN
Solar/Wind Harmer
16.26
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.525
276621W2-048 GEN
Solar/Wind Harmer
0.176
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.613
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
964401AG1-302 GEN
Solar/Wind Harmer
0.001
966571AG1-526 GEN
Solar/Wind Harmer
7.577
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.199
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
1.098
970513AG2-328 GEN
Solar/Wind Harmer
1.448
970517AG2-330 GEN
Solar/Wind Harmer
8.688
960741AF2-365 GEN
Solar/Wind Harmer
1.664
3429391JKCT 9G
Adder
3.902
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.41
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.181
276694AA1-018 GEN2
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.125
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
276806AD2-047 C O1
Solar/Wind Harmer
1.792
970941AG2-585 GEN
Solar/Wind Harmer
3.953
276157O29GEN1
Solar/Wind Harmer
0.511
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
970707AG2-453 GEN
Solar/Wind Harmer
10.286
943121AE2-341 GEN
Solar/Wind Harmer
5.278
943591AF1-030 GEN
Solar/Wind Harmer
3.51
274772LINCOLN ;3U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.115
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.056
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.335
959091AF2-200 GEN
Solar/Wind Harmer
6.288
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.987
962251AG1-071 GEN
Solar/Wind Harmer
1.885
958171AF2-111 GEN
Solar/Wind Harmer
7.532
970349AG2-230 GEN
Solar/Wind Harmer
4.502
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o 34541 34553_SRT-A


Base Case Flowgate

Area:DEO&K
Facility Description:
08LONGBR-08MTZION 138.0 kV Ckt 1 line
Contingency Name:
34541 34553_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.05 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:301.17
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
339243AC2-075 GEN1
Solar/Wind Harmer
0.63
972163AH1-664 GEN
Solar/Wind Harmer
9.177
972165AH1-665 GEN
Solar/Wind Harmer
7.342
3429211JKCT 2G
Adder
7.529
339211AE2-254 GEN
Solar/Wind Harmer
0.721
3429631SPURLK3G
50/50
1.634
972167AH1-666 GEN
Solar/Wind Harmer
7.474
958171AF2-111 GEN
Solar/Wind Harmer
22.601
3429391JKCT 9G
Adder
5.479
970093AG2-073 GEN
Solar/Wind Harmer
5.893
966571AG1-526 GEN
Solar/Wind Harmer
11.102
972273AH1-721 GEN
Adder
28.683
3429601SPURLK2G
50/50
3.115
970235AG2-159 GEN
Solar/Wind Harmer
5.178
970235AG2-159 GEN
Solar/Wind Harmer
3.161
339221AD2-048_GEN
Solar/Wind Harmer
1.67
972043AH1-570 GEN
Solar/Wind Harmer
2.368
972045AH1-571 GEN
Solar/Wind Harmer
1.894
971125AH1-004 GEN
Solar/Wind Harmer
3.657
970107AG2-081 GEN
Solar/Wind Harmer
2.742
960161AF2-307 GEN
Solar/Wind Harmer
4.146
942891AE2-308 GEN
Solar/Wind Harmer
6.382
3429571SPURLK1G
50/50
1.979
3429661SPURLK4G
50/50
1.634
339216AC1-074 GEN
Solar/Wind Harmer
2.326
945681AF1-233 GEN
Solar/Wind Harmer
17.52
943111AE2-339 GEN
Solar/Wind Harmer
0.696
3429421JKCT 10G
Adder
5.479
3429241JKCT 3G
Adder
7.628
971821AH1-427 GEN
Solar/Wind Harmer
4.617
950041AG9-017
External Queue
4.585630416870117
LAGNLTFEXP_LAGN->PJM
CLTF
1.662
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.496
TVALTFEXP_TVA->PJM
CLTF
1.035
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
1.885
WECLTFEXP_WEC->PJM
CLTF
0.056
CPLELTFEXP_CPLE->PJM
CLTF
0.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.735
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.23
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.044
MECLTFEXP_MEC->PJM
CLTF
0.588
SIGELTFEXP_SIGE->PJM
CLTF
0.062

Details for 4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o 34541 34553_SRT-A


Base Case Flowgate

Area:DEO&K/EKPC
Facility Description:
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line
Contingency Name:
34541 34553_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.17 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:327.08
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
339243AC2-075 GEN1
Solar/Wind Harmer
0.63
972163AH1-664 GEN
Solar/Wind Harmer
9.177
972165AH1-665 GEN
Solar/Wind Harmer
7.342
3429211JKCT 2G
Adder
7.529
339211AE2-254 GEN
Solar/Wind Harmer
0.721
3429571SPURLK1G
50/50
1.979
3429661SPURLK4G
50/50
1.634
339216AC1-074 GEN
Solar/Wind Harmer
2.326
945681AF1-233 GEN
Solar/Wind Harmer
17.52
943111AE2-339 GEN
Solar/Wind Harmer
0.696
3429421JKCT 10G
Adder
5.479
3429241JKCT 3G
Adder
7.628
971821AH1-427 GEN
Solar/Wind Harmer
4.617
3429631SPURLK3G
50/50
1.634
972167AH1-666 GEN
Solar/Wind Harmer
7.474
958171AF2-111 GEN
Solar/Wind Harmer
22.601
3429391JKCT 9G
Adder
5.479
970093AG2-073 GEN
Solar/Wind Harmer
5.893
966571AG1-526 GEN
Solar/Wind Harmer
11.102
972273AH1-721 GEN
Adder
28.683
3429601SPURLK2G
50/50
3.115
970235AG2-159 GEN
Solar/Wind Harmer
5.178
970235AG2-159 GEN
Solar/Wind Harmer
3.161
339221AD2-048_GEN
Solar/Wind Harmer
1.67
972043AH1-570 GEN
Solar/Wind Harmer
2.368
972045AH1-571 GEN
Solar/Wind Harmer
1.894
971125AH1-004 GEN
Solar/Wind Harmer
3.657
970107AG2-081 GEN
Solar/Wind Harmer
2.742
960161AF2-307 GEN
Solar/Wind Harmer
4.146
942891AE2-308 GEN
Solar/Wind Harmer
6.382
950041AG9-017
External Queue
4.585630416870117
LAGNLTFEXP_LAGN->PJM
CLTF
1.662
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.496
TVALTFEXP_TVA->PJM
CLTF
1.035
NYPJM->LTFIMP_NY
CLTF
0.077
LGEELTFEXP_LGEE->PJM
CLTF
1.885
WECLTFEXP_WEC->PJM
CLTF
0.056
CPLELTFEXP_CPLE->PJM
CLTF
0.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.735
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.23
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.044
MECLTFEXP_MEC->PJM
CLTF
0.588
SIGELTFEXP_SIGE->PJM
CLTF
0.062

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.71 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1818.59
MW Contribution:7.2
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.014
972165AH1-665 GEN
Solar/Wind Harmer
34.411
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.746
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.383
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.675
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.013
972143AH1-644 GEN
Solar/Wind Harmer
6.197
945631AF1-228 GEN
Solar/Wind Helper
0.922
241972AD1-140 GEN
Solar/Wind Helper
1.753
3429601SPURLK2G
50/50
18.627
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.442
970107AG2-081 GEN
Solar/Wind Harmer
8.582
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.296
942891AE2-308 GEN
Solar/Wind Harmer
25.136
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.243
970235AG2-159 GEN
Solar/Wind Harmer
2.59
971081AG2-670 GEN
Solar/Wind Harmer
7.638
970653AG2-424 GEN
Solar/Wind Harmer
4.629
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.673
966021AG1-471 GEN
Solar/Wind Harmer
4.84
270186AC1-089 GEN
Solar/Wind Harmer
5.47
971485AH1-239 GEN
Solar/Wind Harmer
7.086
964571AG1-320 GEN
Solar/Wind Harmer
7.225
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.106
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
253394AE2-221_GEN
Solar/Wind Helper
2.188
253398AE2-221_GEN2
Solar/Wind Helper
2.188
25183208HLCRTG
Solar/Wind Helper
2.422
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.114
3429661SPURLK4G
50/50
9.769
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.785
945681AF1-233 GEN
Solar/Wind Harmer
83.563
339216AC1-074 GEN
Solar/Wind Harmer
4.868
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.162
971821AH1-427 GEN
Solar/Wind Harmer
16.414
971565AH1-281 GEN
Solar/Wind Harmer
2.168
339241AF1-083 GEN
Solar/Wind Harmer
1.765
971315AH1-136 GEN
Solar/Wind Harmer
2.121
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.831
962241AG1-070 GEN
Solar/Wind Harmer
3.397
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.993
3429631SPURLK3G
50/50
9.769
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.708
972167AH1-666 GEN
Solar/Wind Harmer
35.712
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.159
966571AG1-526 GEN
Solar/Wind Harmer
42.232
972273AH1-721 GEN
Adder
104.488
970273AG2-179 GEN
Solar/Wind Harmer
4.096
960741AF2-365 GEN
Solar/Wind Harmer
4.057
339250AF1-203 GEN
Solar/Wind Harmer
0.484
971155AH1-034 GEN
Solar/Wind Harmer
7.829
962251AG1-071 GEN
Solar/Wind Harmer
4.152
972103AH1-617 GEN
Solar/Wind Harmer
12.393
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.684
253415AE1-040 GEN
Solar/Wind Helper
0.407
950051AG9-018
External Queue
23.242685317993164
950011AG9-010
External Queue
6.110060214996338
950041AG9-017
External Queue
23.325098037719727
LAGNLTFEXP_LAGN->PJM
CLTF
6.065
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.858
TVALTFEXP_TVA->PJM
CLTF
3.721
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.925
WECLTFEXP_WEC->PJM
CLTF
0.319
CPLELTFEXP_CPLE->PJM
CLTF
1.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.309
MECLTFEXP_MEC->PJM
CLTF
2.533
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.58 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1816.67
MW Contribution:7.2
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.016
972165AH1-665 GEN
Solar/Wind Harmer
34.413
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.381
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.673
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.012
972143AH1-644 GEN
Solar/Wind Harmer
6.196
945631AF1-228 GEN
Solar/Wind Helper
0.92
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.441
970107AG2-081 GEN
Solar/Wind Harmer
8.581
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.295
942891AE2-308 GEN
Solar/Wind Harmer
25.135
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.237
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
7.636
970653AG2-424 GEN
Solar/Wind Harmer
4.628
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.672
270186AC1-089 GEN
Solar/Wind Harmer
5.474
966021AG1-471 GEN
Solar/Wind Harmer
4.838
971485AH1-239 GEN
Solar/Wind Harmer
7.084
964571AG1-320 GEN
Solar/Wind Harmer
7.222
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.103
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
83.568
339216AC1-074 GEN
Solar/Wind Harmer
4.867
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
16.411
971565AH1-281 GEN
Solar/Wind Harmer
2.167
339241AF1-083 GEN
Solar/Wind Harmer
1.764
971315AH1-136 GEN
Solar/Wind Harmer
2.12
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.826
962241AG1-070 GEN
Solar/Wind Harmer
3.396
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
3429631SPURLK3G
50/50
9.77
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.718
972167AH1-666 GEN
Solar/Wind Harmer
35.714
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.157
966571AG1-526 GEN
Solar/Wind Harmer
42.226
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.095
960741AF2-365 GEN
Solar/Wind Harmer
4.056
339250AF1-203 GEN
Solar/Wind Harmer
0.483
971155AH1-034 GEN
Solar/Wind Harmer
7.826
962251AG1-071 GEN
Solar/Wind Harmer
4.151
972103AH1-617 GEN
Solar/Wind Harmer
12.392
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
950051AG9-018
External Queue
23.248964309692383
950011AG9-010
External Queue
6.113064289093018
950041AG9-017
External Queue
23.331375122070312
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.61 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1801.71
MW Contribution:5.59
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
13.435
972043AH1-570 GEN
Solar/Wind Harmer
5.591
972045AH1-571 GEN
Solar/Wind Harmer
4.473
971125AH1-004 GEN
Solar/Wind Harmer
8.9
970107AG2-081 GEN
Solar/Wind Harmer
6.675
339221AD2-048_GEN
Solar/Wind Harmer
3.382
960161AF2-307 GEN
Solar/Wind Harmer
13.557
942891AE2-308 GEN
Solar/Wind Harmer
19.615
970235AG2-159 GEN
Solar/Wind Harmer
4.694
970235AG2-159 GEN
Solar/Wind Harmer
2.866
339231AF1-038_GEN
Solar/Wind Harmer
1.69
971081AG2-670 GEN
Solar/Wind Harmer
6.943
970653AG2-424 GEN
Solar/Wind Harmer
4.401
970653AG2-424 GEN
Solar/Wind Harmer
1.591
964571AG1-320 GEN
Solar/Wind Harmer
7.156
339236AF1-050_GEN
Solar/Wind Harmer
1.548
966021AG1-471 GEN
Solar/Wind Harmer
4.332
971485AH1-239 GEN
Solar/Wind Harmer
6.379
339255AE2-071 GEN
Solar/Wind Harmer
0.801
964781AG1-341 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
4.24
25194408D.CRK1
Adder
5.107
25194508D.CRK3
Adder
0.955
25183208HLCRTG
Solar/Wind Helper
5.68
253394AE2-221_GEN
Solar/Wind Helper
3.647
253398AE2-221_GEN2
Solar/Wind Helper
3.647
270518AE2-148 GEN
Solar/Wind Helper
9.647
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
25197008MELDL1
50/50
0.565
972163AH1-664 GEN
Solar/Wind Harmer
31.627
972165AH1-665 GEN
Solar/Wind Harmer
25.302
339243AC2-075 GEN1
Solar/Wind Harmer
1.04
3429211JKCT 2G
Adder
24.5
339211AE2-254 GEN
Solar/Wind Harmer
2.124
965401AG1-405 GEN
Solar/Wind Harmer
6.938
965411AG1-406 GEN
Solar/Wind Harmer
3.114
970455AG2-298 GEN
Solar/Wind Harmer
6.185
25196108MFTGT2
Adder
1.16
25196108MFTGT2
Adder
1.077
962211AG1-066 GEN
Solar/Wind Harmer
1.705
252524AE2-267 GEN
Solar/Wind Harmer
1.086
25196408WSDLE3
Adder
6.077
25196308WSDLE2
Adder
6.024
25196208WSDLE1
Adder
6.009
25196708WSDLE6
Adder
5.994
25196508WSDLE4
Adder
5.843
970281AG2-184 GEN
Solar/Wind Harmer
9.902
972143AH1-644 GEN
Solar/Wind Harmer
4.715
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.723
270340AC2-060 GEN
Solar/Wind Helper
1.337
270520AE2-214 GEN
Solar/Wind Helper
2.981
241973AD2-163_GEN1
Solar/Wind Helper
0.936
253383AE2-342_GEN
Solar/Wind Helper
0.365
3429661SPURLK4G
50/50
7.046
3429571SPURLK1G
50/50
7.13
25197208MELDL3
50/50
0.569
945681AF1-233 GEN
Solar/Wind Harmer
61.301
339216AC1-074 GEN
Solar/Wind Harmer
3.841
943111AE2-339 GEN
Solar/Wind Harmer
1.977
3429421JKCT 10G
Adder
18.466
25196808ZIMRHP
Adder
160.301
3429241JKCT 3G
Adder
24.821
971821AH1-427 GEN
Solar/Wind Harmer
13.653
971565AH1-281 GEN
Solar/Wind Harmer
2.045
339241AF1-083 GEN
Solar/Wind Harmer
1.592
970273AG2-179 GEN
Solar/Wind Harmer
2.255
964901AG1-354 GEN
Solar/Wind Harmer
12.036
971315AH1-136 GEN
Solar/Wind Harmer
1.582
25196008MFTGT1
Adder
1.052
962241AG1-070 GEN
Solar/Wind Harmer
3.274
25194608D.CRK4
Adder
1.11
253343AC1-166 GEN
Solar/Wind Helper
1.288
253325AC1-069 GEN
Solar/Wind Helper
1.335
252507AC2-088 GEN
Solar/Wind Helper
0.98
270263AC1-001 GEN
Solar/Wind Helper
0.509
3429631SPURLK3G
50/50
7.046
25197108MELDL2
50/50
0.574
958171AF2-111 GEN
Solar/Wind Harmer
93.548
972167AH1-666 GEN
Solar/Wind Harmer
26.189
3429391JKCT 9G
Adder
18.466
970093AG2-073 GEN
Solar/Wind Harmer
18.208
966571AG1-526 GEN
Solar/Wind Harmer
34.399
972273AH1-721 GEN
Adder
88.436
970273AG2-179 GEN
Solar/Wind Harmer
3.601
960741AF2-365 GEN
Solar/Wind Harmer
3.916
25196008MFTGT1
Adder
1.019
339250AF1-203 GEN
Solar/Wind Harmer
0.458
971155AH1-034 GEN
Solar/Wind Harmer
7.447
962251AG1-071 GEN
Solar/Wind Harmer
4.002
25196608WSDLE5
Adder
5.903
25194608D.CRK4
Adder
1.11
252510AF1-249 C
Solar/Wind Harmer
0.263
972103AH1-617 GEN
Solar/Wind Harmer
9.431
253338AC1-165 GEN
Solar/Wind Helper
1.288
253333AC1-068 GEN
Solar/Wind Helper
1.335
253406AD2-031_GEN
Solar/Wind Helper
1.189
253415AE1-040 GEN
Solar/Wind Helper
0.677
241955AC1-078 GEN
Solar/Wind Helper
1.207
241974AD2-163_GEN2
Solar/Wind Helper
0.936
270273AD2-016 GEN
Solar/Wind Helper
1.38
960801AF2-371 GEN
Solar/Wind Helper
0.521
964871AG1-351 GEN
Solar/Wind Helper
0.36
950051AG9-018
External Queue
14.528197288513184
950041AG9-017
External Queue
14.816180229187012
LAGNLTFEXP_LAGN->PJM
CLTF
6.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.13
TVALTFEXP_TVA->PJM
CLTF
3.879
NYPJM->LTFIMP_NY
CLTF
0.784
LGEELTFEXP_LGEE->PJM
CLTF
5.678
WECLTFEXP_WEC->PJM
CLTF
0.782
CPLELTFEXP_CPLE->PJM
CLTF
0.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.602
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.536
MECLTFEXP_MEC->PJM
CLTF
4.374
SIGELTFEXP_SIGE->PJM
CLTF
0.293

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.62 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1786.6
MW Contribution:6.04
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.688
972163AH1-664 GEN
Solar/Wind Harmer
35.04
972165AH1-665 GEN
Solar/Wind Harmer
28.032
339243AC2-075 GEN1
Solar/Wind Harmer
1.117
3429211JKCT 2G
Adder
26.517
339211AE2-254 GEN
Solar/Wind Harmer
2.222
965401AG1-405 GEN
Solar/Wind Harmer
7.259
965411AG1-406 GEN
Solar/Wind Harmer
3.258
970455AG2-298 GEN
Solar/Wind Harmer
6.151
962211AG1-066 GEN
Solar/Wind Harmer
1.825
970281AG2-184 GEN
Solar/Wind Harmer
10.652
972143AH1-644 GEN
Solar/Wind Harmer
5.072
25196108MFTGT2
Adder
0.725
25196108MFTGT2
Adder
0.673
945631AF1-228 GEN
Solar/Wind Helper
1.079
270340AC2-060 GEN
Solar/Wind Helper
1.058
270520AE2-214 GEN
Solar/Wind Helper
2.349
241972AD1-140 GEN
Solar/Wind Helper
1.835
3429601SPURLK2G
50/50
15.032
972043AH1-570 GEN
Solar/Wind Harmer
6.036
972045AH1-571 GEN
Solar/Wind Harmer
4.829
971125AH1-004 GEN
Solar/Wind Harmer
9.607
970107AG2-081 GEN
Solar/Wind Harmer
7.205
339221AD2-048_GEN
Solar/Wind Harmer
3.631
960161AF2-307 GEN
Solar/Wind Harmer
14.82
942891AE2-308 GEN
Solar/Wind Harmer
21.118
970235AG2-159 GEN
Solar/Wind Harmer
4.418
970235AG2-159 GEN
Solar/Wind Harmer
2.697
339231AF1-038_GEN
Solar/Wind Harmer
1.721
971081AG2-670 GEN
Solar/Wind Harmer
6.96
970653AG2-424 GEN
Solar/Wind Harmer
4.326
970653AG2-424 GEN
Solar/Wind Harmer
1.564
339236AF1-050_GEN
Solar/Wind Harmer
1.539
964571AG1-320 GEN
Solar/Wind Harmer
6.913
966021AG1-471 GEN
Solar/Wind Harmer
4.369
971485AH1-239 GEN
Solar/Wind Harmer
6.417
339255AE2-071 GEN
Solar/Wind Harmer
0.788
964781AG1-341 GEN
Solar/Wind Harmer
7.607
270186AC1-089 GEN
Solar/Wind Harmer
4.26
253394AE2-221_GEN
Solar/Wind Helper
2.834
253398AE2-221_GEN2
Solar/Wind Helper
2.834
25183208HLCRTG
Solar/Wind Helper
2.94
270518AE2-148 GEN
Solar/Wind Helper
6.991
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
3429661SPURLK4G
50/50
7.884
3429571SPURLK1G
50/50
7.938
25197208MELDL3
50/50
0.692
25196808ZIMRHP
50/50
216.474
945681AF1-233 GEN
Solar/Wind Harmer
67.998
339216AC1-074 GEN
Solar/Wind Harmer
4.124
943111AE2-339 GEN
Solar/Wind Harmer
2.139
3429421JKCT 10G
Adder
20.047
3429241JKCT 3G
Adder
26.865
971821AH1-427 GEN
Solar/Wind Harmer
14.261
971565AH1-281 GEN
Solar/Wind Harmer
2.017
339241AF1-083 GEN
Solar/Wind Harmer
1.601
970273AG2-179 GEN
Solar/Wind Harmer
2.293
971315AH1-136 GEN
Solar/Wind Harmer
1.727
964901AG1-354 GEN
Solar/Wind Harmer
11.895
962241AG1-070 GEN
Solar/Wind Harmer
3.198
25196008MFTGT1
Adder
0.658
253343AC1-166 GEN
Solar/Wind Helper
1.021
253325AC1-069 GEN
Solar/Wind Helper
1.058
252507AC2-088 GEN
Solar/Wind Helper
0.737
3429631SPURLK3G
50/50
7.884
25197108MELDL2
50/50
0.698
958171AF2-111 GEN
Solar/Wind Harmer
104.27
972167AH1-666 GEN
Solar/Wind Harmer
29.055
3429391JKCT 9G
Adder
20.047
970093AG2-073 GEN
Solar/Wind Harmer
19.531
966571AG1-526 GEN
Solar/Wind Harmer
36.287
972273AH1-721 GEN
Adder
91.547
970273AG2-179 GEN
Solar/Wind Harmer
3.663
960741AF2-365 GEN
Solar/Wind Harmer
3.824
339250AF1-203 GEN
Solar/Wind Harmer
0.45
971155AH1-034 GEN
Solar/Wind Harmer
7.314
962251AG1-071 GEN
Solar/Wind Harmer
3.909
972103AH1-617 GEN
Solar/Wind Harmer
10.145
25196008MFTGT1
Adder
0.637
253338AC1-165 GEN
Solar/Wind Helper
1.021
253333AC1-068 GEN
Solar/Wind Helper
1.058
253406AD2-031_GEN
Solar/Wind Helper
0.902
253415AE1-040 GEN
Solar/Wind Helper
0.53
241955AC1-078 GEN
Solar/Wind Helper
0.928
950051AG9-018
External Queue
17.501935958862305
950041AG9-017
External Queue
17.643001556396484
LAGNLTFEXP_LAGN->PJM
CLTF
6.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.16
TVALTFEXP_TVA->PJM
CLTF
3.662
NYPJM->LTFIMP_NY
CLTF
0.663
LGEELTFEXP_LGEE->PJM
CLTF
5.148
WECLTFEXP_WEC->PJM
CLTF
0.587
CPLELTFEXP_CPLE->PJM
CLTF
0.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.428
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.346
MECLTFEXP_MEC->PJM
CLTF
3.54
SIGELTFEXP_SIGE->PJM
CLTF
0.254

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.28 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1766.12
MW Contribution:6.1
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.877
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.272
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.702
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.126
270518AE2-148 GEN
Solar/Wind Helper
5.923
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.684
945681AF1-233 GEN
Solar/Wind Harmer
69.569
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.88
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.44816780090332
950041AG9-017
External Queue
18.620590209960938
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.381
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.082
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1765.38
MW Contribution:6.1
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.876
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.924
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.666
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.878
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.448036193847656
950041AG9-017
External Queue
18.620628356933594
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.081
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.19 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.77
MW Contribution:6.1
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.433
972043AH1-570 GEN
Solar/Wind Harmer
6.099
972045AH1-571 GEN
Solar/Wind Harmer
4.879
971125AH1-004 GEN
Solar/Wind Harmer
9.702
970107AG2-081 GEN
Solar/Wind Harmer
7.276
339221AD2-048_GEN
Solar/Wind Harmer
3.656
960161AF2-307 GEN
Solar/Wind Harmer
15.079
942891AE2-308 GEN
Solar/Wind Harmer
21.337
970235AG2-159 GEN
Solar/Wind Harmer
4.079
970235AG2-159 GEN
Solar/Wind Harmer
2.49
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.828
970653AG2-424 GEN
Solar/Wind Harmer
4.209
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.505
964571AG1-320 GEN
Solar/Wind Harmer
6.674
966021AG1-471 GEN
Solar/Wind Harmer
4.297
971485AH1-239 GEN
Solar/Wind Harmer
6.305
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.838
972165AH1-665 GEN
Solar/Wind Harmer
28.67
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.853
339211AE2-254 GEN
Solar/Wind Harmer
2.218
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.254
970455AG2-298 GEN
Solar/Wind Harmer
6.013
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.719
945681AF1-233 GEN
Solar/Wind Harmer
69.574
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.165
3429421JKCT 10G
Adder
20.327
3429241JKCT 3G
Adder
27.206
971821AH1-427 GEN
Solar/Wind Harmer
14.227
971565AH1-281 GEN
Solar/Wind Harmer
1.966
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.264
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.598
962241AG1-070 GEN
Solar/Wind Harmer
3.102
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.886
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.883
972167AH1-666 GEN
Solar/Wind Harmer
29.73
3429391JKCT 9G
Adder
20.327
970093AG2-073 GEN
Solar/Wind Harmer
19.704
966571AG1-526 GEN
Solar/Wind Harmer
36.357
972273AH1-721 GEN
Adder
91.022
970273AG2-179 GEN
Solar/Wind Harmer
3.616
960741AF2-365 GEN
Solar/Wind Harmer
3.709
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.112
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
270186AC1-089 GEN
Solar/Wind Harmer
4.704
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.385
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.512
252509AD1-136 GEN
Solar/Wind Helper
0.127
270518AE2-148 GEN
Solar/Wind Helper
5.922
950051AG9-018
External Queue
18.447389602661133
950041AG9-017
External Queue
18.62034034729004
LAGNLTFEXP_LAGN->PJM
CLTF
5.885
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.49
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.829
WECLTFEXP_WEC->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.502
MECLTFEXP_MEC->PJM
CLTF
3.084
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.16 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.32
MW Contribution:6.1
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
14.225
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.596
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.701
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.078
970235AG2-159 GEN
Solar/Wind Harmer
2.489
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.827
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.673
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.304
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.384
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.873
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.702
966571AG1-526 GEN
Solar/Wind Harmer
36.352
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.708
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.111
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.274
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.834
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.012
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.787
972143AH1-644 GEN
Solar/Wind Harmer
5.137
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.446699142456055
950041AG9-017
External Queue
18.61962890625
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.67 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1421.95
MW Contribution:4.16
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.485
25197108MELDL2
50/50
0.555
958171AF2-111 GEN
Solar/Wind Harmer
69.07
972167AH1-666 GEN
Solar/Wind Harmer
19.252
3429391JKCT 9G
Adder
19.034
970093AG2-073 GEN
Solar/Wind Harmer
12.938
966571AG1-526 GEN
Solar/Wind Harmer
24.04
972273AH1-721 GEN
Adder
86.897
970273AG2-179 GEN
Solar/Wind Harmer
3.732
960741AF2-365 GEN
Solar/Wind Harmer
2.535
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.654
962251AG1-071 GEN
Solar/Wind Harmer
2.943
972103AH1-617 GEN
Solar/Wind Harmer
6.68
25196008MFTGT1
Adder
0.603
253338AC1-165 GEN
Solar/Wind Helper
1.014
253333AC1-068 GEN
Solar/Wind Helper
1.051
253406AD2-031_GEN
Solar/Wind Helper
0.849
253415AE1-040 GEN
Solar/Wind Helper
0.499
25197008MELDL1
50/50
0.547
972163AH1-664 GEN
Solar/Wind Harmer
25.851
972165AH1-665 GEN
Solar/Wind Harmer
20.704
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
25.178
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
4.808
965411AG1-406 GEN
Solar/Wind Harmer
3.093
970455AG2-298 GEN
Solar/Wind Harmer
4.531
970281AG2-184 GEN
Solar/Wind Harmer
7.014
972143AH1-644 GEN
Solar/Wind Harmer
3.618
25196108MFTGT2
Adder
0.686
25196108MFTGT2
Adder
0.637
945631AF1-228 GEN
Solar/Wind Helper
0.994
270340AC2-060 GEN
Solar/Wind Helper
0.992
270520AE2-214 GEN
Solar/Wind Helper
2.234
3429601SPURLK2G
50/50
14.272
972043AH1-570 GEN
Solar/Wind Harmer
4.16
972045AH1-571 GEN
Solar/Wind Harmer
3.333
971125AH1-004 GEN
Solar/Wind Harmer
6.363
970107AG2-081 GEN
Solar/Wind Harmer
4.772
339221AD2-048_GEN
Solar/Wind Harmer
0.009
960161AF2-307 GEN
Solar/Wind Harmer
10.094
942891AE2-308 GEN
Solar/Wind Harmer
13.99
970235AG2-159 GEN
Solar/Wind Harmer
4.442
970235AG2-159 GEN
Solar/Wind Harmer
2.549
971081AG2-670 GEN
Solar/Wind Harmer
4.612
970653AG2-424 GEN
Solar/Wind Harmer
2.868
970653AG2-424 GEN
Solar/Wind Harmer
1.486
964571AG1-320 GEN
Solar/Wind Harmer
5.107
966021AG1-471 GEN
Solar/Wind Harmer
2.893
971485AH1-239 GEN
Solar/Wind Harmer
4.249
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.081
964781AG1-341 GEN
Solar/Wind Harmer
5.04
253394AE2-221_GEN
Solar/Wind Helper
2.805
253398AE2-221_GEN2
Solar/Wind Helper
2.805
25183208HLCRTG
Solar/Wind Helper
2.661
270518AE2-148 GEN
Solar/Wind Helper
6.187
252509AD1-136 GEN
Solar/Wind Helper
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.28
3429661SPURLK4G
50/50
7.485
3429571SPURLK1G
50/50
7.538
25197208MELDL3
50/50
0.55
945681AF1-233 GEN
Solar/Wind Harmer
45.056
339216AC1-074 GEN
Solar/Wind Harmer
0.445
3429421JKCT 10G
Adder
19.034
3429241JKCT 3G
Adder
25.509
25196808ZIMRHP
Adder
146.521
971821AH1-427 GEN
Solar/Wind Harmer
9.447
971565AH1-281 GEN
Solar/Wind Harmer
1.338
970273AG2-179 GEN
Solar/Wind Harmer
2.177
971315AH1-136 GEN
Solar/Wind Harmer
1.141
964901AG1-354 GEN
Solar/Wind Harmer
7.882
962241AG1-070 GEN
Solar/Wind Harmer
2.566
25196008MFTGT1
Adder
0.622
253343AC1-166 GEN
Solar/Wind Helper
1.014
253325AC1-069 GEN
Solar/Wind Helper
1.051
252507AC2-088 GEN
Solar/Wind Helper
0.746
950051AG9-018
External Queue
16.609764099121094
950041AG9-017
External Queue
16.814743041992188
LAGNLTFEXP_LAGN->PJM
CLTF
5.94
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.879
TVALTFEXP_TVA->PJM
CLTF
3.468
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
4.904
WECLTFEXP_WEC->PJM
CLTF
0.565
CPLELTFEXP_CPLE->PJM
CLTF
0.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.508
MECLTFEXP_MEC->PJM
CLTF
3.38
SIGELTFEXP_SIGE->PJM
CLTF
0.241

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.33 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1751.58
MW Contribution:7.2
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
9.776
3429571SPURLK1G
50/50
9.792
945681AF1-233 GEN
Solar/Wind Harmer
83.633
339216AC1-074 GEN
Solar/Wind Harmer
4.873
943111AE2-339 GEN
Solar/Wind Harmer
2.561
3429421JKCT 10G
Adder
24.103
3429241JKCT 3G
Adder
32.202
971821AH1-427 GEN
Solar/Wind Harmer
16.445
971565AH1-281 GEN
Solar/Wind Harmer
2.174
339241AF1-083 GEN
Solar/Wind Harmer
1.77
971315AH1-136 GEN
Solar/Wind Harmer
2.127
970273AG2-179 GEN
Solar/Wind Harmer
2.572
964901AG1-354 GEN
Solar/Wind Harmer
12.878
962241AG1-070 GEN
Solar/Wind Harmer
3.411
971687AH1-348 GEN
Solar/Wind Harmer
0.46
253343AC1-166 GEN
Solar/Wind Helper
0.792
253325AC1-069 GEN
Solar/Wind Helper
0.821
252507AC2-088 GEN
Solar/Wind Helper
0.99
3429601SPURLK2G
50/50
18.64
972043AH1-570 GEN
Solar/Wind Harmer
7.203
972045AH1-571 GEN
Solar/Wind Harmer
5.763
971125AH1-004 GEN
Solar/Wind Harmer
11.455
970107AG2-081 GEN
Solar/Wind Harmer
8.591
960161AF2-307 GEN
Solar/Wind Harmer
17.988
339221AD2-048_GEN
Solar/Wind Harmer
4.301
942891AE2-308 GEN
Solar/Wind Harmer
25.169
339231AF1-038_GEN
Solar/Wind Harmer
1.932
970235AG2-159 GEN
Solar/Wind Harmer
4.251
970235AG2-159 GEN
Solar/Wind Harmer
2.595
971081AG2-670 GEN
Solar/Wind Harmer
7.662
970653AG2-424 GEN
Solar/Wind Harmer
4.644
970653AG2-424 GEN
Solar/Wind Harmer
1.679
339236AF1-050_GEN
Solar/Wind Harmer
1.678
270186AC1-089 GEN
Solar/Wind Harmer
5.494
966021AG1-471 GEN
Solar/Wind Harmer
4.857
971485AH1-239 GEN
Solar/Wind Harmer
7.111
964571AG1-320 GEN
Solar/Wind Harmer
7.25
339255AE2-071 GEN
Solar/Wind Harmer
0.849
964781AG1-341 GEN
Solar/Wind Harmer
8.139
971225AH1-072 GEN
Solar/Wind Harmer
0.888
971227AH1-073 GEN
Solar/Wind Harmer
0.888
253394AE2-221_GEN
Solar/Wind Helper
2.179
253398AE2-221_GEN2
Solar/Wind Helper
2.179
25183208HLCRTG
Solar/Wind Helper
2.409
252509AD1-136 GEN
Solar/Wind Helper
0.141
270518AE2-148 GEN
Solar/Wind Helper
6.059
3429631SPURLK3G
50/50
9.776
958171AF2-111 GEN
Solar/Wind Harmer
128.804
972167AH1-666 GEN
Solar/Wind Harmer
35.741
3429391JKCT 9G
Adder
24.103
970093AG2-073 GEN
Solar/Wind Harmer
23.192
966571AG1-526 GEN
Solar/Wind Harmer
42.302
972273AH1-721 GEN
Adder
104.752
970273AG2-179 GEN
Solar/Wind Harmer
4.108
960741AF2-365 GEN
Solar/Wind Harmer
4.073
339250AF1-203 GEN
Solar/Wind Harmer
0.485
971155AH1-034 GEN
Solar/Wind Harmer
7.86
962251AG1-071 GEN
Solar/Wind Harmer
4.17
972103AH1-617 GEN
Solar/Wind Harmer
12.461
971461AH1-227 GEN
Solar/Wind Harmer
2.276
253338AC1-165 GEN
Solar/Wind Helper
0.792
253333AC1-068 GEN
Solar/Wind Helper
0.821
253406AD2-031_GEN
Solar/Wind Helper
0.679
253415AE1-040 GEN
Solar/Wind Helper
0.403
972163AH1-664 GEN
Solar/Wind Harmer
43.05
972165AH1-665 GEN
Solar/Wind Harmer
34.44
339243AC2-075 GEN1
Solar/Wind Harmer
1.319
3429211JKCT 2G
Adder
31.785
339211AE2-254 GEN
Solar/Wind Harmer
2.566
965401AG1-405 GEN
Solar/Wind Harmer
8.401
965411AG1-406 GEN
Solar/Wind Harmer
3.77
970455AG2-298 GEN
Solar/Wind Harmer
6.693
962211AG1-066 GEN
Solar/Wind Harmer
2.199
970281AG2-184 GEN
Solar/Wind Harmer
13.084
972143AH1-644 GEN
Solar/Wind Harmer
6.23
945631AF1-228 GEN
Solar/Wind Helper
0.914
950051AG9-018
External Queue
23.248964309692383
950011AG9-010
External Queue
6.113064289093018
950041AG9-017
External Queue
23.331375122070312
LAGNLTFEXP_LAGN->PJM
CLTF
6.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.96
TVALTFEXP_TVA->PJM
CLTF
3.754
NYPJM->LTFIMP_NY
CLTF
0.539
LGEELTFEXP_LGEE->PJM
CLTF
4.945
WECLTFEXP_WEC->PJM
CLTF
0.331
CPLELTFEXP_CPLE->PJM
CLTF
1.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.92
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.429
MECLTFEXP_MEC->PJM
CLTF
2.587
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1613.52
MW Contribution:5.22
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
33.413
972165AH1-665 GEN
Solar/Wind Harmer
26.76
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
0.005
965401AG1-405 GEN
Solar/Wind Harmer
5.847
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
5.173
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
5.22
972045AH1-571 GEN
Solar/Wind Harmer
4.183
971125AH1-004 GEN
Solar/Wind Harmer
7.982
970107AG2-081 GEN
Solar/Wind Harmer
5.987
960161AF2-307 GEN
Solar/Wind Harmer
12.886
339221AD2-048_GEN
Solar/Wind Harmer
0.012
942891AE2-308 GEN
Solar/Wind Harmer
17.536
970235AG2-159 GEN
Solar/Wind Harmer
4.508
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
5.327
970653AG2-424 GEN
Solar/Wind Harmer
3.229
970653AG2-424 GEN
Solar/Wind Harmer
1.673
270186AC1-089 GEN
Solar/Wind Harmer
0.004
966021AG1-471 GEN
Solar/Wind Harmer
3.376
971485AH1-239 GEN
Solar/Wind Harmer
4.942
964571AG1-320 GEN
Solar/Wind Harmer
5.612
339255AE2-071 GEN
Solar/Wind Harmer
-0.091
964781AG1-341 GEN
Solar/Wind Harmer
5.653
971225AH1-072 GEN
Solar/Wind Harmer
0.614
971227AH1-073 GEN
Solar/Wind Harmer
0.614
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
58.303
339216AC1-074 GEN
Solar/Wind Harmer
0.553
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
11.449
971565AH1-281 GEN
Solar/Wind Harmer
1.512
971315AH1-136 GEN
Solar/Wind Harmer
1.479
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
8.949
962241AG1-070 GEN
Solar/Wind Harmer
2.87
971687AH1-348 GEN
Solar/Wind Harmer
0.319
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
3429631SPURLK3G
50/50
9.77
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
89.804
972167AH1-666 GEN
Solar/Wind Harmer
24.916
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
16.156
966571AG1-526 GEN
Solar/Wind Harmer
29.46
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.395
960741AF2-365 GEN
Solar/Wind Harmer
2.829
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
6.37
962251AG1-071 GEN
Solar/Wind Harmer
3.291
972103AH1-617 GEN
Solar/Wind Harmer
8.646
971461AH1-227 GEN
Solar/Wind Harmer
1.576
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
970281AG2-184 GEN
Solar/Wind Harmer
9.078
972143AH1-644 GEN
Solar/Wind Harmer
4.683
945631AF1-228 GEN
Solar/Wind Helper
0.92
950051AG9-018
External Queue
23.248964309692383
950011AG9-010
External Queue
6.113064289093018
950041AG9-017
External Queue
23.331375122070312
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1592.57
MW Contribution:4.42
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
4.425
972045AH1-571 GEN
Solar/Wind Harmer
3.545
971125AH1-004 GEN
Solar/Wind Harmer
6.768
970107AG2-081 GEN
Solar/Wind Harmer
5.076
339221AD2-048_GEN
Solar/Wind Harmer
0.01
960161AF2-307 GEN
Solar/Wind Harmer
10.815
942891AE2-308 GEN
Solar/Wind Harmer
14.884
970235AG2-159 GEN
Solar/Wind Harmer
4.339
970235AG2-159 GEN
Solar/Wind Harmer
2.489
971081AG2-670 GEN
Solar/Wind Harmer
4.763
970653AG2-424 GEN
Solar/Wind Harmer
2.936
970653AG2-424 GEN
Solar/Wind Harmer
1.521
964571AG1-320 GEN
Solar/Wind Harmer
5.185
966021AG1-471 GEN
Solar/Wind Harmer
2.997
971485AH1-239 GEN
Solar/Wind Harmer
4.398
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.083
964781AG1-341 GEN
Solar/Wind Harmer
5.152
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
48.536
339216AC1-074 GEN
Solar/Wind Harmer
0.471
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
9.925
971565AH1-281 GEN
Solar/Wind Harmer
1.371
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.227
964901AG1-354 GEN
Solar/Wind Harmer
8.09
962241AG1-070 GEN
Solar/Wind Harmer
2.621
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
74.563
972167AH1-666 GEN
Solar/Wind Harmer
20.74
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
13.746
966571AG1-526 GEN
Solar/Wind Harmer
25.362
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.88
960741AF2-365 GEN
Solar/Wind Harmer
2.587
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.788
962251AG1-071 GEN
Solar/Wind Harmer
3.005
972103AH1-617 GEN
Solar/Wind Harmer
7.168
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
27.834
972165AH1-665 GEN
Solar/Wind Harmer
22.292
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
5.057
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
4.66
970281AG2-184 GEN
Solar/Wind Harmer
7.526
972143AH1-644 GEN
Solar/Wind Harmer
3.883
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.446699142456055
950041AG9-017
External Queue
18.61962890625
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.45 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1424.98
MW Contribution:1.43
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.873
253372AE2-315 SEC3
50/50
2.873
25322309TAIT W
50/50
0.72
963581AG1-207 GEN
50/50
13.06
25306009OHH W.
50/50
4.021
945631AF1-228 GEN
Solar/Wind Harmer
27.818
253349AC2-067 GEN
Solar/Wind Harmer
6.021
253400AC2-068 GEN
Solar/Wind Harmer
2.421
241972AD1-140 GEN
Solar/Wind Harmer
5.044
252524AE2-267 GEN
Solar/Wind Harmer
1.419
25196408WSDLE3
Adder
7.936
25196308WSDLE2
Adder
7.867
25196208WSDLE1
Adder
7.848
25196708WSDLE6
Adder
7.828
25196508WSDLE4
Adder
7.631
270156DARBY CT1
Adder
7.385
270157DARBY CT2
Adder
7.367
270158DARBY CT3
Adder
7.249
944031AF1-071 GEN
Solar/Wind Harmer
0.738
25196108MFTGT2
Adder
1.077
25196108MFTGT2
Adder
1
270367AC2-061_GEN
Solar/Wind Harmer
2.217
972163AH1-664 GEN
Solar/Wind Harmer
6.512
972165AH1-665 GEN
Solar/Wind Harmer
5.209
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
971673AH1-337 GEN
Solar/Wind Harmer
2.661
971029AG2-637 GEN
Solar/Wind Harmer
8.415
270543AE2-219 C
Solar/Wind Harmer
2.625
3429211JKCT 2G
Adder
5.962
270340AC2-060 GEN
Solar/Wind Harmer
1.539
270520AE2-214 GEN
Solar/Wind Helper
6.845
270054AF2-122 C O1
Solar/Wind Helper
0.907
25326109MON D
50/50
2.066
253370AE2-315 SEC1
50/50
3.038
25322209TAIT E
50/50
14.495
25322209TAIT E
50/50
14.169
270518AE2-148 GEN
Solar/Wind Harmer
58.767
253394AE2-221_GEN
Solar/Wind Harmer
6.182
253398AE2-221_GEN2
Solar/Wind Harmer
6.182
253317AC1-085 GEN4
Solar/Wind Harmer
9.627
25183208HLCRTG
Solar/Wind Harmer
5.419
252519AF1-045_GEN
Solar/Wind Harmer
5.386
252516AE2-318_GEN
Solar/Wind Harmer
4.109
25194408D.CRK1
Adder
6.661
25194508D.CRK3
Adder
1.245
252509AD1-136 GEN
Solar/Wind Harmer
0.199
962581AG1-107 GEN
Solar/Wind Harmer
3.823
961491AF2-440 GEN
Solar/Wind Harmer
1.589
25326509SID D
Adder
0.977
270186AC1-089 GEN
Solar/Wind Harmer
4.078
253378AE2-206_GEN
Solar/Wind Harmer
2.335
276820AF1-078_GEN
Solar/Wind Harmer
1.037
24728805RICHG1
Adder
2.332
24728905RICHG2
Adder
2.332
339221AD2-048_GEN
Solar/Wind Harmer
0.89
972043AH1-570 GEN
Solar/Wind Harmer
1.426
972045AH1-571 GEN
Solar/Wind Harmer
1.141
971125AH1-004 GEN
Solar/Wind Harmer
2.201
970107AG2-081 GEN
Solar/Wind Harmer
1.651
970235AG2-159 GEN
Solar/Wind Harmer
2.161
970235AG2-159 GEN
Solar/Wind Harmer
1.319
970883AG2-550 GEN
Solar/Wind Harmer
5.126
970885AG2-551 GEN
Solar/Wind Harmer
1.192
942891AE2-308 GEN
Solar/Wind Harmer
4.971
960161AF2-307 GEN
Solar/Wind Harmer
3.167
270383AD1-128 GEN
Solar/Wind Harmer
2.903
247621Y3-024
Adder
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.857
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.712
25322209TAIT E
50/50
0.712
25326309TAIT D
50/50
1.628
960071AF2-298 GEN
Solar/Wind Harmer
6.567
253432AC1-085 GEN2
Solar/Wind Harmer
0.308
946171AF1-282 GEN
Solar/Wind Harmer
11.493
25194608D.CRK4
Adder
1.448
253343AC1-166 GEN
Solar/Wind Harmer
0.935
253325AC1-069 GEN
Solar/Wind Harmer
0.902
270159DARBY CT4
Adder
7.267
25196808ZIMRHP
Adder
60.162
252507AC2-088 GEN
Solar/Wind Harmer
1.394
25196008MFTGT1
Adder
0.977
945681AF1-233 GEN
Solar/Wind Harmer
12.435
339216AC1-074 GEN
Solar/Wind Harmer
0.981
943111AE2-339 GEN
Solar/Wind Harmer
0.48
3429421JKCT 10G
Adder
4.38
3429241JKCT 3G
Adder
6.04
247536S-71 GEN
Solar/Wind Harmer
1.898
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.712
25322209TAIT E
50/50
0.703
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.5
253316AC1-085 GEN3
Solar/Wind Harmer
9.627
253433AC1-085 GEN1
Solar/Wind Harmer
6.111
946181AF1-283 GEN
Solar/Wind Harmer
14.94
25196608WSDLE5
Adder
7.709
25194608D.CRK4
Adder
1.448
252510AF1-249 C
Solar/Wind Harmer
0.366
253338AC1-165 GEN
Solar/Wind Harmer
0.935
253333AC1-068 GEN
Solar/Wind Harmer
0.902
270222AC2-111 GEN
Solar/Wind Harmer
5.989
958171AF2-111 GEN
Solar/Wind Harmer
17.625
25196008MFTGT1
Adder
0.946
972167AH1-666 GEN
Solar/Wind Harmer
5.299
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.38
970093AG2-073 GEN
Solar/Wind Harmer
4.741
270356AE2-297 GEN
Solar/Wind Harmer
2.157
966571AG1-526 GEN
Solar/Wind Harmer
9.893
960801AF2-371 GEN
Solar/Wind Helper
0.814
964871AG1-351 GEN
Solar/Wind Helper
0.562
241955AC1-078 GEN
Solar/Wind Helper
1.496
270273AD2-016 GEN
Solar/Wind Helper
1.395
LAGNLTFEXP_LAGN->PJM
CLTF
3.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.427
TVALTFEXP_TVA->PJM
CLTF
1.886
NYPJM->LTFIMP_NY
CLTF
0.874
LGEELTFEXP_LGEE->PJM
CLTF
2.944
WECLTFEXP_WEC->PJM
CLTF
0.645
CPLELTFEXP_CPLE->PJM
CLTF
0.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.018
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.65
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.706
MECLTFEXP_MEC->PJM
CLTF
3.158
SIGELTFEXP_SIGE->PJM
CLTF
0.179

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.03 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.78
MW Contribution:1.43
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
270054AF2-122 C O1
Solar/Wind Helper
0.91
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.99 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.31
MW Contribution:1.43
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
270054AF2-122 C O1
Solar/Wind Helper
0.91
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.99 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.3
MW Contribution:1.43
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
270054AF2-122 C O1
Solar/Wind Helper
0.91
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.08 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1384.41
MW Contribution:1.08
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.874
253371AE2-315 SEC2
50/50
2.718
25322309TAIT W
50/50
0.677
25322209TAIT E
50/50
0.669
253303V4-073 C
Solar/Wind Harmer
0.157
253406AD2-031_GEN
Solar/Wind Harmer
1.252
253316AC1-085 GEN3
Solar/Wind Harmer
7.514
253433AC1-085 GEN1
Solar/Wind Harmer
4.77
946181AF1-283 GEN
Solar/Wind Harmer
11.662
25196608WSDLE5
Adder
6.984
25194608D.CRK4
Adder
1.305
252510AF1-249 C
Solar/Wind Harmer
0.328
270222AC2-111 GEN
Solar/Wind Harmer
5.764
25196008MFTGT1
Adder
0.859
270356AE2-297 GEN
Solar/Wind Harmer
2.217
25326109MON D
50/50
1.972
253370AE2-315 SEC1
50/50
2.874
25322209TAIT E
50/50
13.798
25322209TAIT E
50/50
13.488
270518AE2-148 GEN
Solar/Wind Harmer
59.931
253394AE2-221_GEN
Solar/Wind Harmer
5.257
253398AE2-221_GEN2
Solar/Wind Harmer
5.257
253317AC1-085 GEN4
Solar/Wind Harmer
7.514
25194408D.CRK1
Adder
6.003
25194508D.CRK3
Adder
1.122
252519AF1-045_GEN
Solar/Wind Harmer
4.563
252516AE2-318_GEN
Solar/Wind Harmer
3.481
25183208HLCRTG
Solar/Wind Harmer
4.249
25326509SID D
Adder
0.922
962581AG1-107 GEN
Solar/Wind Harmer
3.295
961491AF2-440 GEN
Solar/Wind Harmer
1.369
252509AD1-136 GEN
Solar/Wind Harmer
0.16
24728805RICHG1
Adder
2.301
24728905RICHG2
Adder
2.301
253378AE2-206_GEN
Solar/Wind Harmer
2.172
276820AF1-078_GEN
Solar/Wind Harmer
0.965
270186AC1-089 GEN
Solar/Wind Harmer
3.342
970883AG2-550 GEN
Solar/Wind Harmer
5.339
970885AG2-551 GEN
Solar/Wind Harmer
1.242
270383AD1-128 GEN
Solar/Wind Harmer
3.062
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.88
970235AG2-159 GEN
Solar/Wind Harmer
1.148
24379505HDWTR1G C
Solar/Wind Harmer
3.603
270209AC1-174_GEN
Solar/Wind Harmer
2.543
926881AC1-175 GEN
Solar/Wind Harmer
2.543
270201AC2-176 GEN
Solar/Wind Harmer
2.328
964611AG1-324 GEN
Solar/Wind Harmer
0.53
964611AG1-324 GEN
Solar/Wind Harmer
0.235
339221AD2-048_GEN
Solar/Wind Harmer
0.683
972043AH1-570 GEN
Solar/Wind Harmer
1.085
972045AH1-571 GEN
Solar/Wind Harmer
0.868
946101AF1-275 GEN
Solar/Wind Helper
0.782
270471AD2-092_GEN
Solar/Wind Helper
0.679
253370AE2-315 SEC1
50/50
2.874
253371AE2-315 SEC2
50/50
2.718
25322309TAIT W
50/50
0.677
25322209TAIT E
50/50
0.678
25326309TAIT D
50/50
1.55
960071AF2-298 GEN
Solar/Wind Harmer
6.251
253432AC1-085 GEN2
Solar/Wind Harmer
0.24
946171AF1-282 GEN
Solar/Wind Harmer
8.971
25194608D.CRK4
Adder
1.305
25196808ZIMRHP
Adder
48.8
25196008MFTGT1
Adder
0.887
252507AC2-088 GEN
Solar/Wind Harmer
1.122
247536S-71 GEN
Solar/Wind Harmer
2.017
945681AF1-233 GEN
Solar/Wind Harmer
8.649
942081AE2-220 GEN
Solar/Wind Harmer
2.913
270239V3-007_GEN1
Solar/Wind Harmer
0.784
339216AC1-074 GEN
Solar/Wind Harmer
0.75
253343AC1-166 GEN
Solar/Wind Helper
0.737
253325AC1-069 GEN
Solar/Wind Helper
0.763
270349AD2-093_GEN
Solar/Wind Helper
0.679
253372AE2-315 SEC3
50/50
2.718
253372AE2-315 SEC3
50/50
2.718
25322309TAIT W
50/50
0.686
963581AG1-207 GEN
50/50
12.455
25306009OHH W.
50/50
3.817
945631AF1-228 GEN
Solar/Wind Harmer
28.545
253349AC2-067 GEN
Solar/Wind Harmer
5.739
253400AC2-068 GEN
Solar/Wind Harmer
2.308
241972AD1-140 GEN
Solar/Wind Harmer
4.762
252524AE2-267 GEN
Solar/Wind Harmer
1.285
25196408WSDLE3
Adder
7.189
25196308WSDLE2
Adder
7.126
25196208WSDLE1
Adder
7.109
25196708WSDLE6
Adder
7.091
25196508WSDLE4
Adder
6.912
944031AF1-071 GEN
Solar/Wind Harmer
0.71
25196108MFTGT2
Adder
0.978
25196108MFTGT2
Adder
0.908
270367AC2-061_GEN
Solar/Wind Harmer
1.873
971673AH1-337 GEN
Solar/Wind Harmer
2.703
971029AG2-637 GEN
Solar/Wind Harmer
8.599
270543AE2-219 C
Solar/Wind Harmer
2.734
270240V3-007_GEN2
Solar/Wind Harmer
2.819
972163AH1-664 GEN
Solar/Wind Harmer
4.555
972165AH1-665 GEN
Solar/Wind Harmer
3.644
961761AG1-017 GEN
Solar/Wind Harmer
0.194
339243AC2-075 GEN1
Solar/Wind Harmer
0.203
270520AE2-214 GEN
Solar/Wind Helper
6.241
270054AF2-122 C O1
Solar/Wind Helper
0.929
958171AF2-111 GEN
Solar/Wind Harmer
11.967
972167AH1-666 GEN
Solar/Wind Harmer
3.682
270437AC2-090 C
Solar/Wind Harmer
2.544
962031AG1-047 GEN
Solar/Wind Harmer
1.368
957741AF2-068 GEN
Solar/Wind Harmer
6.791
946031AF1-268 GEN
Solar/Wind Harmer
3.646
960801AF2-371 GEN
Solar/Wind Helper
0.823
964871AG1-351 GEN
Solar/Wind Helper
0.569
241955AC1-078 GEN
Solar/Wind Helper
1.555
253338AC1-165 GEN
Solar/Wind Helper
0.737
253333AC1-068 GEN
Solar/Wind Helper
0.763
270273AD2-016 GEN
Solar/Wind Helper
1.456
LAGNLTFEXP_LAGN->PJM
CLTF
4.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.362
TVALTFEXP_TVA->PJM
CLTF
1.964
NYPJM->LTFIMP_NY
CLTF
0.978
LGEELTFEXP_LGEE->PJM
CLTF
2.729
WECLTFEXP_WEC->PJM
CLTF
1.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CPLELTFEXP_CPLE->PJM
CLTF
0.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.791
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.735
MECLTFEXP_MEC->PJM
CLTF
4.352
SIGELTFEXP_SIGE->PJM
CLTF
0.183

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.58 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1246.02
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.797
253372AE2-315 SEC3
50/50
2.797
25322309TAIT W
50/50
0.707
963581AG1-207 GEN
50/50
12.873
25306009OHH W.
50/50
3.93
945631AF1-228 GEN
Solar/Wind Harmer
28.95
253349AC2-067 GEN
Solar/Wind Harmer
5.914
253400AC2-068 GEN
Solar/Wind Harmer
2.378
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.318
25196408WSDLE3
Adder
7.373
25196308WSDLE2
Adder
7.309
25196208WSDLE1
Adder
7.291
25196708WSDLE6
Adder
7.272
25196508WSDLE4
Adder
7.089
944031AF1-071 GEN
Solar/Wind Harmer
0.733
25196108MFTGT2
Adder
0.996
25196108MFTGT2
Adder
0.924
270367AC2-061_GEN
Solar/Wind Harmer
1.945
971673AH1-337 GEN
Solar/Wind Harmer
2.763
971029AG2-637 GEN
Solar/Wind Harmer
8.781
270543AE2-219 C
Solar/Wind Harmer
2.777
270240V3-007_GEN2
Solar/Wind Harmer
3.159
24729505KEY G4
Adder
3.142
958711AF2-162 GEN
Solar/Wind Harmer
0.49
965101AG1-375 GEN
Solar/Wind Harmer
4.842
945581AF1-223 GEN
Solar/Wind Harmer
2.196
972163AH1-664 GEN
Solar/Wind Harmer
4.698
972165AH1-665 GEN
Solar/Wind Harmer
3.758
961761AG1-017 GEN
Solar/Wind Harmer
0.195
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
970115AG2-085 GEN
Solar/Wind Harmer
1.763
270520AE2-214 GEN
Solar/Wind Helper
5.68
270054AF2-122 C O1
Solar/Wind Helper
0.769
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.689
253303V4-073 C
Solar/Wind Harmer
0.161
253406AD2-031_GEN
Solar/Wind Harmer
1.299
253316AC1-085 GEN3
Solar/Wind Harmer
7.79
253433AC1-085 GEN1
Solar/Wind Harmer
4.945
946181AF1-283 GEN
Solar/Wind Harmer
12.09
25196608WSDLE5
Adder
7.162
25194608D.CRK4
Adder
1.339
252510AF1-249 C
Solar/Wind Harmer
0.337
270222AC2-111 GEN
Solar/Wind Harmer
5.95
25196008MFTGT1
Adder
0.875
270437AC2-090 C
Solar/Wind Harmer
2.85
270356AE2-297 GEN
Solar/Wind Harmer
2.265
958171AF2-111 GEN
Solar/Wind Harmer
12.391
944531AF1-118 GEN
Solar/Wind Harmer
16.954
958821AF2-173 GEN
Solar/Wind Harmer
6.775
270004AE1-209 GEN
Solar/Wind Harmer
2.645
972167AH1-666 GEN
Solar/Wind Harmer
3.803
946031AF1-268 GEN
Solar/Wind Harmer
3.894
962031AG1-047 GEN
Solar/Wind Harmer
1.375
957741AF2-068 GEN
Solar/Wind Harmer
6.824
960801AF2-371 GEN
Solar/Wind Helper
0.736
964871AG1-351 GEN
Solar/Wind Helper
0.508
241955AC1-078 GEN
Solar/Wind Helper
1.347
253338AC1-165 GEN
Solar/Wind Helper
0.659
253333AC1-068 GEN
Solar/Wind Helper
0.683
270273AD2-016 GEN
Solar/Wind Helper
1.278
25326109MON D
50/50
2.033
253370AE2-315 SEC1
50/50
2.957
25322209TAIT E
50/50
14.212
25322209TAIT E
50/50
13.892
270518AE2-148 GEN
Solar/Wind Harmer
60.837
253394AE2-221_GEN
Solar/Wind Harmer
5.421
253398AE2-221_GEN2
Solar/Wind Harmer
5.421
253317AC1-085 GEN4
Solar/Wind Harmer
7.79
25194408D.CRK1
Adder
6.158
25194508D.CRK3
Adder
1.151
252519AF1-045_GEN
Solar/Wind Harmer
4.698
252516AE2-318_GEN
Solar/Wind Harmer
3.584
25326509SID D
Adder
0.978
25183208HLCRTG
Solar/Wind Harmer
4.398
962581AG1-107 GEN
Solar/Wind Harmer
3.42
961491AF2-440 GEN
Solar/Wind Harmer
1.421
253378AE2-206_GEN
Solar/Wind Harmer
2.357
276820AF1-078_GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Harmer
0.165
24728805RICHG1
Adder
2.37
24728905RICHG2
Adder
2.37
270186AC1-089 GEN
Solar/Wind Harmer
3.469
970883AG2-550 GEN
Solar/Wind Harmer
5.423
970885AG2-551 GEN
Solar/Wind Harmer
1.261
270383AD1-128 GEN
Solar/Wind Harmer
3.26
24379505HDWTR1G C
Solar/Wind Harmer
4.037
270209AC1-174_GEN
Solar/Wind Harmer
2.849
926881AC1-175 GEN
Solar/Wind Harmer
2.849
944541AF1-119 GEN
Solar/Wind Harmer
2.028
960971AF2-388 GEN
Solar/Wind Harmer
5.293
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.869
970235AG2-159 GEN
Solar/Wind Harmer
1.141
964611AG1-324 GEN
Solar/Wind Harmer
0.54
964611AG1-324 GEN
Solar/Wind Harmer
0.24
270201AC2-176 GEN
Solar/Wind Harmer
2.339
970825AG2-519 GEN
Solar/Wind Harmer
4.771
339221AD2-048_GEN
Solar/Wind Harmer
0.691
960441AF2-335 GEN
Solar/Wind Harmer
4.409
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.878
946101AF1-275 GEN
Solar/Wind Helper
0.711
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.698
25326309TAIT D
50/50
1.596
960071AF2-298 GEN
Solar/Wind Harmer
6.443
253432AC1-085 GEN2
Solar/Wind Harmer
0.249
946171AF1-282 GEN
Solar/Wind Harmer
9.3
25194608D.CRK4
Adder
1.339
25196808ZIMRHP
Adder
50.253
25196008MFTGT1
Adder
0.903
252507AC2-088 GEN
Solar/Wind Harmer
1.156
942081AE2-220 GEN
Solar/Wind Harmer
3.264
270239V3-007_GEN1
Solar/Wind Harmer
0.878
247536S-71 GEN
Solar/Wind Harmer
2.035
958861AF2-177 GEN
Solar/Wind Harmer
5.292
965651AG1-433 GEN
Solar/Wind Harmer
2.646
945371AF1-202 GEN
Solar/Wind Harmer
3.378
270005AE1-210 C O1
Solar/Wind Harmer
2.645
965031AG1-367 GEN
Solar/Wind Harmer
4.839
945681AF1-233 GEN
Solar/Wind Harmer
8.93
970825AG2-519 GEN
Solar/Wind Harmer
1.065
339216AC1-074 GEN
Solar/Wind Harmer
0.759
253343AC1-166 GEN
Solar/Wind Helper
0.659
253325AC1-069 GEN
Solar/Wind Helper
0.683
LAGNLTFEXP_LAGN->PJM
CLTF
3.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.138
TVALTFEXP_TVA->PJM
CLTF
1.63
NYPJM->LTFIMP_NY
CLTF
0.756
LGEELTFEXP_LGEE->PJM
CLTF
2.605
WECLTFEXP_WEC->PJM
CLTF
0.534
CPLELTFEXP_CPLE->PJM
CLTF
0.102
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.934
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.583
MECLTFEXP_MEC->PJM
CLTF
2.702
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#762_8072_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#762_8072_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1229.31
MW Contribution:1.04
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.074
253370AE2-315 SEC1
50/50
3.051
25322209TAIT E
50/50
14.556
25322209TAIT E
50/50
14.229
270518AE2-148 GEN
Solar/Wind Harmer
2.944
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.411
252516AE2-318_GEN
Solar/Wind Harmer
4.799
25194408D.CRK1
Adder
6.692
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.028
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
0.981
270186AC1-089 GEN
Solar/Wind Harmer
0.003
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.963
24728805RICHG1
Adder
2.343
24728905RICHG2
Adder
2.343
339221AD2-048_GEN
Solar/Wind Harmer
0.002
972043AH1-570 GEN
Solar/Wind Harmer
1.039
972045AH1-571 GEN
Solar/Wind Harmer
0.833
971125AH1-004 GEN
Solar/Wind Harmer
1.542
970107AG2-081 GEN
Solar/Wind Harmer
1.157
970235AG2-159 GEN
Solar/Wind Harmer
2.31
970235AG2-159 GEN
Solar/Wind Harmer
1.325
970883AG2-550 GEN
Solar/Wind Harmer
3.593
970885AG2-551 GEN
Solar/Wind Harmer
1.198
942891AE2-308 GEN
Solar/Wind Harmer
3.483
960161AF2-307 GEN
Solar/Wind Harmer
2.281
270383AD1-128 GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.844
253370AE2-315 SEC1
50/50
3.051
253371AE2-315 SEC2
50/50
2.886
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.635
960071AF2-298 GEN
Solar/Wind Harmer
4.595
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.056
25194608D.CRK4
Adder
1.455
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.009
270159DARBY CT4
Adder
7.297
25196808ZIMRHP
Adder
60.434
252507AC2-088 GEN
Solar/Wind Harmer
0.247
25196008MFTGT1
Adder
0.981
945681AF1-233 GEN
Solar/Wind Harmer
8.713
339216AC1-074 GEN
Solar/Wind Harmer
0.112
3429421JKCT 10G
Adder
4.399
3429241JKCT 3G
Adder
6.066
970773AG2-487 GEN
Solar/Wind Harmer
0.586
247536S-71 GEN
Solar/Wind Harmer
0.132
253370AE2-315 SEC1
50/50
3.051
253372AE2-315 SEC3
50/50
2.886
253372AE2-315 SEC3
50/50
2.886
25322309TAIT W
50/50
0.723
963581AG1-207 GEN
50/50
13.114
25306009OHH W.
50/50
4.038
945631AF1-228 GEN
Solar/Wind Harmer
0
253349AC2-067 GEN
Solar/Wind Harmer
2.666
253400AC2-068 GEN
Solar/Wind Harmer
1.072
241972AD1-140 GEN
Solar/Wind Harmer
0.856
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
7.973
25196308WSDLE2
Adder
7.904
25196208WSDLE1
Adder
7.884
25196708WSDLE6
Adder
7.864
25196508WSDLE4
Adder
7.666
270156DARBY CT1
Adder
7.416
270157DARBY CT2
Adder
7.397
270158DARBY CT3
Adder
7.279
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
270367AC2-061_GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
5.08
972165AH1-665 GEN
Solar/Wind Harmer
4.068
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.635
971029AG2-637 GEN
Solar/Wind Harmer
5.898
270543AE2-219 C
Solar/Wind Harmer
0.002
3429211JKCT 2G
Adder
5.988
270340AC2-060 GEN
Solar/Wind Harmer
0.004
270520AE2-214 GEN
Solar/Wind Helper
6.734
270054AF2-122 C O1
Solar/Wind Helper
0.911
253371AE2-315 SEC2
50/50
2.886
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.706
970191AG2-125 GEN
Solar/Wind Harmer
2.178
253406AD2-031_GEN
Solar/Wind Harmer
0.612
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
10.473
25196608WSDLE5
Adder
7.745
25194608D.CRK4
Adder
1.455
252510AF1-249 C
Solar/Wind Harmer
0.047
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
2.609
958171AF2-111 GEN
Solar/Wind Harmer
12.35
25196008MFTGT1
Adder
0.95
972167AH1-666 GEN
Solar/Wind Harmer
3.713
253415AE1-040 GEN
Solar/Wind Harmer
0.002
3429391JKCT 9G
Adder
4.399
970093AG2-073 GEN
Solar/Wind Harmer
3.322
270356AE2-297 GEN
Solar/Wind Harmer
0.004
966571AG1-526 GEN
Solar/Wind Harmer
6.932
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.673
270273AD2-016 GEN
Solar/Wind Helper
1.465
LAGNLTFEXP_LAGN->PJM
CLTF
3.644
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.43
TVALTFEXP_TVA->PJM
CLTF
1.893
NYPJM->LTFIMP_NY
CLTF
0.877
LGEELTFEXP_LGEE->PJM
CLTF
2.957
WECLTFEXP_WEC->PJM
CLTF
0.648
CPLELTFEXP_CPLE->PJM
CLTF
0.155
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.743
MECLTFEXP_MEC->PJM
CLTF
3.173
SIGELTFEXP_SIGE->PJM
CLTF
0.18

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1229.04
MW Contribution:1.1
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.797
253372AE2-315 SEC3
50/50
2.797
25322309TAIT W
50/50
0.707
963581AG1-207 GEN
50/50
12.873
25306009OHH W.
50/50
3.93
945631AF1-228 GEN
Solar/Wind Harmer
28.95
253349AC2-067 GEN
Solar/Wind Harmer
5.914
253400AC2-068 GEN
Solar/Wind Harmer
2.378
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.318
25196408WSDLE3
Adder
7.373
25196308WSDLE2
Adder
7.309
25196208WSDLE1
Adder
7.291
25196708WSDLE6
Adder
7.272
25196508WSDLE4
Adder
7.089
944031AF1-071 GEN
Solar/Wind Harmer
0.733
25196108MFTGT2
Adder
0.996
25196108MFTGT2
Adder
0.924
270367AC2-061_GEN
Solar/Wind Harmer
1.945
971673AH1-337 GEN
Solar/Wind Harmer
2.763
971029AG2-637 GEN
Solar/Wind Harmer
8.781
270543AE2-219 C
Solar/Wind Harmer
2.777
270240V3-007_GEN2
Solar/Wind Harmer
3.159
24729505KEY G4
Adder
3.142
958711AF2-162 GEN
Solar/Wind Harmer
0.49
965101AG1-375 GEN
Solar/Wind Harmer
4.842
945581AF1-223 GEN
Solar/Wind Harmer
2.196
972163AH1-664 GEN
Solar/Wind Harmer
4.698
972165AH1-665 GEN
Solar/Wind Harmer
3.758
961761AG1-017 GEN
Solar/Wind Harmer
0.195
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
970115AG2-085 GEN
Solar/Wind Harmer
1.763
270520AE2-214 GEN
Solar/Wind Helper
5.68
270054AF2-122 C O1
Solar/Wind Helper
0.769
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.698
25326309TAIT D
50/50
1.596
960071AF2-298 GEN
Solar/Wind Harmer
6.443
253432AC1-085 GEN2
Solar/Wind Harmer
0.249
946171AF1-282 GEN
Solar/Wind Harmer
9.3
25194608D.CRK4
Adder
1.339
25196808ZIMRHP
Adder
50.253
25196008MFTGT1
Adder
0.903
252507AC2-088 GEN
Solar/Wind Harmer
1.156
942081AE2-220 GEN
Solar/Wind Harmer
3.264
270239V3-007_GEN1
Solar/Wind Harmer
0.878
247536S-71 GEN
Solar/Wind Harmer
2.035
958861AF2-177 GEN
Solar/Wind Harmer
5.292
965651AG1-433 GEN
Solar/Wind Harmer
2.646
945371AF1-202 GEN
Solar/Wind Harmer
3.378
270005AE1-210 C O1
Solar/Wind Harmer
2.645
965031AG1-367 GEN
Solar/Wind Harmer
4.839
945681AF1-233 GEN
Solar/Wind Harmer
8.93
970825AG2-519 GEN
Solar/Wind Harmer
1.065
339216AC1-074 GEN
Solar/Wind Harmer
0.759
253343AC1-166 GEN
Solar/Wind Helper
0.659
253325AC1-069 GEN
Solar/Wind Helper
0.683
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.689
253303V4-073 C
Solar/Wind Harmer
0.161
253406AD2-031_GEN
Solar/Wind Harmer
1.299
253316AC1-085 GEN3
Solar/Wind Harmer
7.79
253433AC1-085 GEN1
Solar/Wind Harmer
4.945
946181AF1-283 GEN
Solar/Wind Harmer
12.09
25196608WSDLE5
Adder
7.162
25194608D.CRK4
Adder
1.339
252510AF1-249 C
Solar/Wind Harmer
0.337
270222AC2-111 GEN
Solar/Wind Harmer
5.95
25196008MFTGT1
Adder
0.875
270437AC2-090 C
Solar/Wind Harmer
2.85
270356AE2-297 GEN
Solar/Wind Harmer
2.265
958171AF2-111 GEN
Solar/Wind Harmer
12.391
958821AF2-173 GEN
Solar/Wind Harmer
6.775
270004AE1-209 GEN
Solar/Wind Harmer
2.645
972167AH1-666 GEN
Solar/Wind Harmer
3.803
946031AF1-268 GEN
Solar/Wind Harmer
3.894
962031AG1-047 GEN
Solar/Wind Harmer
1.375
957741AF2-068 GEN
Solar/Wind Harmer
6.824
960801AF2-371 GEN
Solar/Wind Helper
0.736
964871AG1-351 GEN
Solar/Wind Helper
0.508
241955AC1-078 GEN
Solar/Wind Helper
1.347
253338AC1-165 GEN
Solar/Wind Helper
0.659
253333AC1-068 GEN
Solar/Wind Helper
0.683
270273AD2-016 GEN
Solar/Wind Helper
1.278
25326109MON D
50/50
2.033
253370AE2-315 SEC1
50/50
2.957
25322209TAIT E
50/50
14.212
25322209TAIT E
50/50
13.892
270518AE2-148 GEN
Solar/Wind Harmer
60.837
253394AE2-221_GEN
Solar/Wind Harmer
5.421
253398AE2-221_GEN2
Solar/Wind Harmer
5.421
253317AC1-085 GEN4
Solar/Wind Harmer
7.79
25194408D.CRK1
Adder
6.158
25194508D.CRK3
Adder
1.151
252519AF1-045_GEN
Solar/Wind Harmer
4.698
252516AE2-318_GEN
Solar/Wind Harmer
3.584
25326509SID D
Adder
0.978
25183208HLCRTG
Solar/Wind Harmer
4.398
962581AG1-107 GEN
Solar/Wind Harmer
3.42
961491AF2-440 GEN
Solar/Wind Harmer
1.421
253378AE2-206_GEN
Solar/Wind Harmer
2.357
276820AF1-078_GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Harmer
0.165
24728805RICHG1
Adder
2.37
24728905RICHG2
Adder
2.37
270186AC1-089 GEN
Solar/Wind Harmer
3.469
970883AG2-550 GEN
Solar/Wind Harmer
5.423
970885AG2-551 GEN
Solar/Wind Harmer
1.261
270383AD1-128 GEN
Solar/Wind Harmer
3.26
24379505HDWTR1G C
Solar/Wind Harmer
4.037
270209AC1-174_GEN
Solar/Wind Harmer
2.849
926881AC1-175 GEN
Solar/Wind Harmer
2.849
944541AF1-119 GEN
Solar/Wind Harmer
2.028
960971AF2-388 GEN
Solar/Wind Harmer
5.293
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.869
970235AG2-159 GEN
Solar/Wind Harmer
1.141
964611AG1-324 GEN
Solar/Wind Harmer
0.54
964611AG1-324 GEN
Solar/Wind Harmer
0.24
270201AC2-176 GEN
Solar/Wind Harmer
2.339
970825AG2-519 GEN
Solar/Wind Harmer
4.771
339221AD2-048_GEN
Solar/Wind Harmer
0.691
960441AF2-335 GEN
Solar/Wind Harmer
4.409
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.878
946101AF1-275 GEN
Solar/Wind Helper
0.711
LAGNLTFEXP_LAGN->PJM
CLTF
3.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.138
TVALTFEXP_TVA->PJM
CLTF
1.63
NYPJM->LTFIMP_NY
CLTF
0.756
LGEELTFEXP_LGEE->PJM
CLTF
2.605
WECLTFEXP_WEC->PJM
CLTF
0.534
CPLELTFEXP_CPLE->PJM
CLTF
0.102
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.934
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.583
MECLTFEXP_MEC->PJM
CLTF
2.702
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#8122_05BEATTY 345_302W_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 243469 CKT 3   /*05BEATTY     345.0 - 05BEATTY     138.0
 OPEN BRANCH FROM BUS 243453 TO BUS 945630 CKT 1   /*05BEATTY     345.0 - AF1-228 TP   345.0
END
CONTINGENCY 'AEP_P4_#18136_05CHENOWETH 345_CB1_SRT-A-1'
 OPEN BRANCH FROM BUS 253027 TO BUS 253248 CKT 1   /*09GREENE     345.0 - 09MADISN     345.0
 OPEN BRANCH FROM BUS 253248 TO BUS 288724 CKT 1   /*09MADISN     345.0 - 05CHENOWETH  345.0
 OPEN BRANCH FROM BUS 945630 TO BUS 288724 CKT 1   /*AF1-228 TP   345.0 - 05CHENOWETH  345.0
END
CONTINGENCY 'AEP_P4_#18138_05CHENOWETH 345_CB3_SRT-A'
 OPEN BRANCH FROM BUS 253027 TO BUS 253248 CKT 1   /*09GREENE     345.0 - 09MADISN     345.0
 OPEN BRANCH FROM BUS 253248 TO BUS 288724 CKT 1   /*09MADISN     345.0 - 05CHENOWETH  345.0
 OPEN BRANCH FROM BUS 288724 TO BUS 288725 CKT 1   /*05CHENOWETH  345.0 - 05CHENOWETSF 345.0
END
CONTINGENCY 'DAY_GREENE_345KV_FB_GJ_EE_SRT-A'
 OPEN BRANCH FROM BUS 253006 TO BUS 253027 CKT 1   /*09BATH       345.0 - 09GREENE     345.0
 OPEN BRANCH FROM BUS 253027 TO BUS 253248 CKT 1   /*09GREENE     345.0 - 09MADISN     345.0
END
CONTINGENCY 'AEP_P4_#18137_05CHENOWETH 345_CB2_SRT-A'
 OPEN BRANCH FROM BUS 288724 TO BUS 288725 CKT 1   /*05CHENOWETH  345.0 - 05CHENOWETSF 345.0
 OPEN BRANCH FROM BUS 945630 TO BUS 288724 CKT 1   /*AF1-228 TP   345.0 - 05CHENOWETH  345.0
END
CONTINGENCY '495_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 253014 TO BUS 253013 CKT 1   /*09CLINTO     345.0 - 09CLINTO      69.0
 OPEN BRANCH FROM BUS 253014 TO BUS 253027 CKT 1   /*09CLINTO     345.0 - 09GREENE     345.0
END
CONTINGENCY 'AEP_P1-2_#18134_SRT-A-1'
 OPEN BRANCH FROM BUS 243453 TO BUS 945630 CKT 1   /*05BEATTY     345.0 - AF1-228 TP   345.0
END
CONTINGENCY 'AEP_P1-2_#18134_SRT-A-2'
 OPEN BRANCH FROM BUS 945630 TO BUS 288724 CKT 1   /*AF1-228 TP   345.0 - 05CHENOWETH  345.0
END
CONTINGENCY 'GREENE_345KV_E_SRT-A'
 OPEN BRANCH FROM BUS 253014 TO BUS 253027 CKT 1   /*09CLINTO     345.0 - 09GREENE     345.0
END
CONTINGENCY '34524 34598_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#3195_05BEATTY 345_304E_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 243453 TO BUS 290098 CKT 4   /*05BEATTY     345.0 - 05BEATTY 4EQ   1.0
 OPEN BRANCH FROM BUS 243469 TO BUS 290098 CKT 4   /*05BEATTY     138.0 - 05BEATTY 4EQ   1.0
 OPEN BRANCH FROM BUS 290098 TO BUS 290099 CKT 4   /*05BEATTY 4EQ   1.0 - 05BEATTY T4   34.5
END
CONTINGENCY 'AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 288776 TO BUS 288781 CKT 2   /*05CYPRUS34   138.0 - 05CYPRUS2EQ    1.0
 OPEN BRANCH FROM BUS 288778 TO BUS 288781 CKT 2   /*05CYPRUS     345.0 - 05CYPRUS2EQ    1.0
 OPEN BRANCH FROM BUS 288781 TO BUS 288782 CKT 2   /*05CYPRUS2EQ    1.0 - 05CYPRUST2    34.5
END
CONTINGENCY 'AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 288778 TO BUS 288779 CKT 1   /*05CYPRUS     345.0 - 05CYPRUS1EQ    1.0
 OPEN BRANCH FROM BUS 288779 TO BUS 288780 CKT 1   /*05CYPRUS1EQ    1.0 - 05CYPRUST1    34.5
 OPEN BRANCH FROM BUS 288779 TO BUS 290230 CKT 1   /*05CYPRUS1EQ    1.0 - 05CYPRUS12   138.0
END
CONTINGENCY 'AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 243469 CKT 3   /*05BEATTY     345.0 - 05BEATTY     138.0
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
CONTINGENCY 'AEP_P4_#16620_05ADKINS 345_A_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1   /*05ADKINS     345.0 - 09ATLNTA     345.0
END
CONTINGENCY 'AEP_P4_#16621_05ADKINS 345_A1_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1                /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#16622_05ADKINS 345_B1_SRT-A'
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1                /*05ADKINS     345.0 - 09ATLNTA     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY '34541 34553_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1   /*09STUART     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 970688 TO BUS 246888 CKT 1   /*AG2-444 TP   345.0 - 05BIERSR     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A'
 OPEN BRANCH FROM BUS 249577 TO BUS 249581 CKT 1   /*08ZIMER      345.0 - 08MELDAL     345.0
END
CONTINGENCY 'DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P1-2_#762_8072_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-1'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 958860 TO BUS 944530 CKT 2   /*AF2-177 TP   345.0 - AF1-118 TP   345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
245769 to 243453 ckt 1
243453 to 244022 ckt 1
288724 to 945630 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
246946 to 243019 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
250054 to 250077 ckt 1
342559 to 250054 ckt 1
342838 to 253077 ckt 1
945630 to 243453 ckt 1

Winter Peak Analysis

The New Service Request AH1-570 was evaluated as a 25.0 MW (15.6 MW Capacity) injection in the EKPC area.

AH1-570 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 25.0 MW (25.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-570 was evaluated as a 25.0 MW injection

AH1-570 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 25.0 MW (25.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-207Vandalia 69 kVEngineering & Procurement
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Study Pending
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3877.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3877.2
Title
Upgrade 345 kV circuit breakers 'A' and 'A1' to 4000A 63 kA breakers at Adkins station
Description
Upgrade 345 kV circuit breakers 'A' and 'A1' to 4000A 63 kA breakers at Adkins station along with some station conductor that is currently limiting the 345 kV line to Beatty.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05BEATTY-05ADKINS 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2063.4
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2063.4 / AEPO0001a
Title
Upgrade/Replace 3-345kV 1600A switches at Beatty station
Description
Upgrade/Replace 3-345kV 1600A switches at Beatty station Scope of s2063 replaced the need for network upgrade: n6769.1
Cost Information
Time Estimate
Nov 15 2022

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-570 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05BEATTY-05COLE 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3877.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3877.1
Title
Replace station conductor and switches in the 345 kV yard at Beatty
Description
Replace station conductor and switches in the 345 kV yard at Beatty that are currently limiting the 345 kV lines to Adkins and Chenoweth.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05BEATTY-AF1-228 TP 345.0 kV Ckt 1 line(Any)
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line(Any)
05BEATTY-05ADKINS 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: n5857
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5857 / N5857
Title
Rebuild / reconductor 10 miles of ACSR ~ 477 ~ 26/7 ~ HAWK- Conductor Section 1.
Description
Rebuild / reconductor 10 miles of ACSR ~ 477 ~ 26/7 ~ HAWK- Conductor Section 1.
Total Cost ($USD)
$19,552,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
05HILLSB-05WLDCAT 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18819
Title
06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
Description
At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2213.9
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2213.9 / (Pending)
Title
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Description
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-570 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9186.0
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
n9186.0 / M240135
Title
Rebuild ~1.40 mile DEOK portion of Longbranch-Mt. Zion with new structures and 954ACSS/TW, 200C
Description
Rebuild the ~1.40 mile DEOK portion of the Longbranch-Mt. Zion line from the structure near 38.940740, -84.623478 with new structures, 954ACSS/TW, 1 conductor per phase, 200 degree C. Restore distribution underbuild.
Total Cost ($USD)
$4,803,522
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
08LONGBR-08MTZION 138.0 kV Ckt 1 line34541 34553_SRT-A

System Reinforcement: n6460.3
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6460.3
Title
Rebuild the EKPC portion of the Longbranch-Mt. Zion 138 kV line section using 954 MCM ACSS conductor (3.7 miles).
Description
Rebuild the EKPC portion of the Longbranch-Mt. Zion 138 kV line section using 954 MCM ACSS conductor (3.7 miles).
Total Cost ($USD)
$7,400,000
Allocated Cost ($USD)
$0
Time Estimate
14 to 24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
08LONGBR-08MTZION 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / DEOK_TC1_13706
Title
Line is 100% owned by EKPC. No DEOK upgrade required.
Description
Line is 100% owned by EKPC. No DEOK upgrade required.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6463.3
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6463.3 / EKPC-tc1-r0007a
Title
Replace the 954 MCM ACSR line conductor in the Boone County-Longbranch 138 kV line with 795 MCM ACSS conductor (2.3 miles)
Description
Replace the 954 MCM ACSR line conductor in the Boone County-Longbranch 138 kV line with 795 MCM ACSS conductor (2.3 miles)
Total Cost ($USD)
$5,400,000
Allocated Cost ($USD)
$0
Time Estimate
11 to 19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6463.2
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n6463.2 / EKPC-tc1-r0007b
Title
Upgrade jumpers associated with Boone 138 kV bus using 2-500 MCM 37 CU conductor or equivalent
Description
Upgrade 795 MCM AA jumpers associated with Boone 138 kV bus (Boone-Longbranch 69 kV line) using 2-500 MCM 37 CU conductor or equivalent
Total Cost ($USD)
$330,000
Allocated Cost ($USD)
$0
Time Estimate
Jun 01 2022

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AH1-570 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
08LONGBR-4BOONE CO 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18817
Title
Replace Stuart Switches to 4000 A
Description
Replace Stuart Switches to 4000 A
Total Cost ($USD)
$1,200,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18818
Title
Replace Wavetrap to 4000 A
Description
Replace Wavetrap to 4000 A
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9670.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9670.0 / DAYr190039
Title
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Description
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Total Cost ($USD)
$50,000,000
Allocated Cost ($USD)
$0
Time Estimate
60 to 72 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9671.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9671.0 / DAYr190040
Title
Replace Stuart substation bus and conductor
Description
Replace Stuart substation bus and conductor
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9672.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9672.0 / DAYr190041
Title
Replace Stuart substation breakers to 4000 A breakers
Description
Replace Stuart substation breakers to 4000 A breakers
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9673.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9673.0 / EKPC-tc1-r0020b
Title
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Description
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Total Cost ($USD)
$1,295,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-570 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-570 could receive cost allocation. Although AH1-570 may not presently have cost responsibility for this upgrade, AH1-570 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0020a
Title
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Description
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-570 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-570 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-570 One Line Diagram

AH1-570 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.