AH1-644 Phase I Study Report

v1.00 released 2025-10-29 21:34

Spicewood Metering 138 kV

65.0 MW Capacity / 100.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Kentucky Power Company, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Kentucky. The installed facilities will have a total capability of 100.0 MW with 65.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-644
Project Name:
Spicewood Metering 138 kV
Project Developer Name:
Kentucky Power Company
State:
Kentucky
County:
Undetermined
Transmission Owner:
American Electric Power
MFO:
100.0
MWE:
100.0
MWC:
65.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-644 will interconnect on the American Electric Power transmission system at the Spicewood 138 kV Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-644 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-644Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$18,115,000$18,115,000
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$3,582,473$3,582,473
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$115,688$115,688
Distribution$7,425$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$21,820,586$21,813,161

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-644

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-644 Project due at DP1
ABA - B
AH1-644$2,181,316$400,000$1,781,316

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new ring bus station, initially populated with 3 breakers.$18,115,000 $18,115,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

The Transmission Owner identified network impacts to Distribution facilities as follows:

Transmission Owner Identified Network Impacts to Distribution Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
244480 05CHAUNCEY 46.0 - 244511 05RICH CRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0115.52 %1.56
244511 05RICH CRK 46.0 - 244498 05HUFFCRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0114.72 %1.56
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
18.0118.77 %0.96
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P7-1_#10809___SRT-A
CONTINGENCY 'AEP_P7-1_#10809___SRT-A'  

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 290391 TO BUS 290518 CKT 1                  / 290391 05TIN BRANCH 138 290518 05HOLDEN 138 1

  OPEN BRANCH FROM BUS 242761 TO BUS 290518 CKT 1                  / 242761 05RAGLDZ 138 290518 05HOLDEN 138 1

END
18.0111.71 %1.82

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
243709 05BLUEGRAS 69.0 - 243730 05HAZARD 2 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0124.24 %18.71
243709 05BLUEGRAS 69.0 - 243730 05HAZARD 2 69.0 CKT 1 AEP_P4_#13977_05BECKHA 138_K_SRT-A
CONTINGENCY 'AEP_P4_#13977_05BECKHA 138_K_SRT-A'  

  OPEN BRANCH FROM BUS 243672 TO BUS 243703 CKT 1                  / 243672 05BECKHA 138 243703 05TOPMOS 138 1

  OPEN BRANCH FROM BUS 243672 TO BUS 243704 CKT 1                  / 243672 05BECKHA 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 243704 CKT 1                  / 243692 05HAZRD1 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 290466 CKT 1                  / 243692 05HAZRD1 138 290466 05HAZARD1EQ 1.00 1

  REMOVE LOAD D1 FROM BUS 243672                                   / 243672 05BECKHA 138 D1

  REMOVE SWSHUNT FROM BUS 243672                                   / 243672 05BECKHA 138

  OPEN BRANCH FROM BUS 243711 TO BUS 243729 CKT 1                  / 243711 05BULAN 69.0 243729 05HAZARD1- 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243738 CKT 1                  / 243729 05HAZARD1- 69.0 243738 05LESLIE 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 290466 CKT 1                  / 243729 05HAZARD1- 69.0 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 290466 TO BUS 290467 CKT 1                  / 290466 05HAZARD1EQ 1.00 290467 05HAZARD T1 13.0 1

END

75.0104.28 %12.04
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0143.84 %18.71
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#13977_05BECKHA 138_K_SRT-A
CONTINGENCY 'AEP_P4_#13977_05BECKHA 138_K_SRT-A'  

  OPEN BRANCH FROM BUS 243672 TO BUS 243703 CKT 1                  / 243672 05BECKHA 138 243703 05TOPMOS 138 1

  OPEN BRANCH FROM BUS 243672 TO BUS 243704 CKT 1                  / 243672 05BECKHA 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 243704 CKT 1                  / 243692 05HAZRD1 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 290466 CKT 1                  / 243692 05HAZRD1 138 290466 05HAZARD1EQ 1.00 1

  REMOVE LOAD D1 FROM BUS 243672                                   / 243672 05BECKHA 138 D1

  REMOVE SWSHUNT FROM BUS 243672                                   / 243672 05BECKHA 138

  OPEN BRANCH FROM BUS 243711 TO BUS 243729 CKT 1                  / 243711 05BULAN 69.0 243729 05HAZARD1- 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243738 CKT 1                  / 243729 05HAZARD1- 69.0 243738 05LESLIE 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 290466 CKT 1                  / 243729 05HAZARD1- 69.0 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 290466 TO BUS 290467 CKT 1                  / 290466 05HAZARD1EQ 1.00 290467 05HAZARD T1 13.0 1

END

75.0123.29 %12.04
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#9504_05BEAVER CR1 138_M_SRT-A
CONTINGENCY 'AEP_P4_#9504_05BEAVER CR1 138_M_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0113.1 %13.26
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P2-2_#9501_05BEAVER CR1 138_1_SRT-A
CONTINGENCY 'AEP_P2-2_#9501_05BEAVER CR1 138_1_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0113.1 %13.26
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#9505_05BEAVER CR1 138_N_SRT-A
CONTINGENCY 'AEP_P4_#9505_05BEAVER CR1 138_N_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243682 TO BUS 243683 CKT 1                  / 243682 05CONSOL 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243683 TO BUS 243875 CKT 1                  / 243683 05CONSTP 138 243875 05SOFTSH 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0113.07 %13.26
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#13068_05HAZARD1- 69.0_F_SRT-A
CONTINGENCY 'AEP_P4_#13068_05HAZARD1- 69.0_F_SRT-A'  

  OPEN BRANCH FROM BUS 243692 TO BUS 290466 CKT 1                  / 243692 05HAZRD1 138 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243730 CKT Z1                 / 243729 05HAZARD1- 69.0 243730 05HAZARD 2 69.0 Z1

  OPEN BRANCH FROM BUS 243710 TO BUS 243745 CKT 1                  / 243710 05BONNYMAN 69.0 243745 05SHAMROCK 69.0 1

  OPEN BRANCH FROM BUS 243711 TO BUS 243729 CKT 1                  / 243711 05BULAN 69.0 243729 05HAZARD1- 69.0 1

  OPEN BRANCH FROM BUS 243711 TO BUS 243745 CKT 1                  / 243711 05BULAN 69.0 243745 05SHAMROCK 69.0 1

  OPEN BRANCH FROM BUS 243720 TO BUS 243745 CKT 1                  / 243720 05ENGLE 69.0 243745 05SHAMROCK 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243738 CKT 1                  / 243729 05HAZARD1- 69.0 243738 05LESLIE 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 290466 CKT 1                  / 243729 05HAZARD1- 69.0 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 290466 TO BUS 290467 CKT 1                  / 290466 05HAZARD1EQ 1.00 290467 05HAZARD T1 13.0 1

END
75.0105.83 %9.73
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P2-2_#9502_05BEAVER CR2 138_2_SRT-A
CONTINGENCY 'AEP_P2-2_#9502_05BEAVER CR2 138_2_SRT-A'  

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

END
75.0101.34 %10.36
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P2-2_#13393_05BEAVERCR 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#13393_05BEAVERCR 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243708 TO BUS 245919 CKT 1                  / 243708 05BEAVERCR 69.0 245919 05OSBORNE 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

END
75.0101.34 %10.36
243710 05BONNYMAN 69.0 - 243745 05SHAMROCK 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0106.73 %12.77
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0127.09 %18.71
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P4_#13977_05BECKHA 138_K_SRT-A
CONTINGENCY 'AEP_P4_#13977_05BECKHA 138_K_SRT-A'  

  OPEN BRANCH FROM BUS 243672 TO BUS 243703 CKT 1                  / 243672 05BECKHA 138 243703 05TOPMOS 138 1

  OPEN BRANCH FROM BUS 243672 TO BUS 243704 CKT 1                  / 243672 05BECKHA 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 243704 CKT 1                  / 243692 05HAZRD1 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 290466 CKT 1                  / 243692 05HAZRD1 138 290466 05HAZARD1EQ 1.00 1

  REMOVE LOAD D1 FROM BUS 243672                                   / 243672 05BECKHA 138 D1

  REMOVE SWSHUNT FROM BUS 243672                                   / 243672 05BECKHA 138

  OPEN BRANCH FROM BUS 243711 TO BUS 243729 CKT 1                  / 243711 05BULAN 69.0 243729 05HAZARD1- 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243738 CKT 1                  / 243729 05HAZARD1- 69.0 243738 05LESLIE 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 290466 CKT 1                  / 243729 05HAZARD1- 69.0 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 290466 TO BUS 290467 CKT 1                  / 290466 05HAZARD1EQ 1.00 290467 05HAZARD T1 13.0 1

END

75.0110.21 %12.04
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P4_#9505_05BEAVER CR1 138_N_SRT-A
CONTINGENCY 'AEP_P4_#9505_05BEAVER CR1 138_N_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243682 TO BUS 243683 CKT 1                  / 243682 05CONSOL 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243683 TO BUS 243875 CKT 1                  / 243683 05CONSTP 138 243875 05SOFTSH 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0106.67 %13.26
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P2-2_#9501_05BEAVER CR1 138_1_SRT-A
CONTINGENCY 'AEP_P2-2_#9501_05BEAVER CR1 138_1_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0106.63 %13.26
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P4_#9504_05BEAVER CR1 138_M_SRT-A
CONTINGENCY 'AEP_P4_#9504_05BEAVER CR1 138_M_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

END
75.0106.63 %13.26
Transmission Owner Identified System Reinforcements
AH1-644 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEP(Pending) / TC2-AEP-162SubRegionalBluegrass - Hazard: Sag study ~0.5 miles of 69kV line, replace the 69kV switches at Bluegrass and Hazard18.7 MW19.6%$39,216
AEP(Pending) / TC2-AEP-167SubRegionalBonnyman - Combs: Sag study ~3 miles of 69kV line, replace the 69kV switch at Combs18.7 MW19.6%$25,490
AEP(Pending) / TC2-AEP-173SubRegionalBonnyman - Shamrock: Sag study ~3 miles of 69kV line12.8 MW19.6%$5,883
AEP(Pending) / TC2-AEP-180SubRegionalBluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass18.7 MW19.6%$45,099
AEP(Pending) / TC2-AEP-185DistributionChauncey - Rich Creek: Sag study ~3.5 miles of 46kV line1.6 MW7.4%$2,970
AEP(Pending) / TC1-AEP-186DistributionRich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line1.6 MW7.4%$4,455
Grand Total:$123,113

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-162
Category
SubRegional
Title
Bluegrass - Hazard: Sag study ~0.5 miles of 69kV line, replace the 69kV switches at Bluegrass and Hazard
Description
Bluegrass - Hazard: Sag study ~0.5 miles of 69kV line, replace the 69kV switches at Bluegrass and Hazard
Total Cost
$200,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18439.3 MW41.2%$82,352
AH1-61737.4 MW39.2%$78,432
AH1-64418.7 MW19.6%$39,216

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-167
Category
SubRegional
Title
Bonnyman - Combs: Sag study ~3 miles of 69kV line, replace the 69kV switch at Combs
Description
Bonnyman - Combs: Sag study ~3 miles of 69kV line, replace the 69kV switch at Combs
Total Cost
$130,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18439.3 MW41.2%$53,529
AH1-61737.4 MW39.2%$50,981
AH1-64418.7 MW19.6%$25,490

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-173
Category
SubRegional
Title
Bonnyman - Shamrock: Sag study ~3 miles of 69kV line
Description
Bonnyman - Shamrock: Sag study ~3 miles of 69kV line
Total Cost
$30,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18426.8 MW41.2%$12,351
AH1-61725.5 MW39.2%$11,766
AH1-64412.8 MW19.6%$5,883

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-180
Category
SubRegional
Title
Bluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass
Description
Bluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass
Total Cost
$230,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18439.3 MW41.2%$94,704
AH1-61737.4 MW39.2%$90,197
AH1-64418.7 MW19.6%$45,099

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-185
Category
Distribution
Title
Chauncey - Rich Creek: Sag study ~3.5 miles of 46kV line
Description
Chauncey - Rich Creek: Sag study ~3.5 miles of 46kV line
Total Cost
$40,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1843.3 MW15.6%$6,245
AH1-18813.0 MW62.1%$24,826
AH1-6173.1 MW14.9%$5,959
AH1-6441.6 MW7.4%$2,970

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC1-AEP-186
Category
Distribution
Title
Rich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line
Description
Rich Creek - Huff Creek: Sag study ~5.25 miles of 46kV line
Total Cost
$60,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1843.3 MW15.6%$9,367
AH1-18813.0 MW62.1%$37,239
AH1-6173.1 MW14.9%$8,939
AH1-6441.6 MW7.4%$4,455

System Reinforcement: s3147.30
TO
AEP
RTEP ID / TO ID
s3147.30
Category
Distribution
Title
Grapevine Station - Removal of the Distribution station and equipment.
Description
Grapevine Station - Removal of the Distribution station and equipment.
Total Cost
$0
Contingent

Note: Although Queue Project AH1-644 may not have cost responsibility for this upgrade, Queue Project AH1-644 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-644 comes into service prior to completion of the upgrade, Queue Project AH1-644 will need an interim study.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-644 was evaluated as a 100.0 MW (65.0 MW Capacity) injection in the AEP area.

AH1-644 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#10335_05SALTV2 138_U_SRT-SL
BreakerAC107.34 %223.0B239.367.31
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#6173_05CLNCHR 138_E2_SRT-A
BreakerAC102.64 %223.0B228.886.59
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#10332_05SALTV1 138_A_SRT-SL
BreakerAC102.21 %223.0B227.926.61
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P7-1_#16933___SRT-A
TowerAC101.03 %223.0B225.36.5
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#10330_05SALTV1 138_C_SRT-SL
BreakerAC100.06 %223.0B223.136.61
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P2-2_#10330_05SALTV1 138_1_SRT-SL
BusAC100.05 %223.0B223.116.61
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC102.26 %392.0B400.858.39
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
AEP_P7-1_#10868___SRT-SL
TowerAC102.25 %392.0B400.819.85
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.8 %2320.0B2500.926.96
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.485.26
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.979.76
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.5512.97
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.4312.93
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.9812.92
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.4312.92
GD2AEP
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
AEP_P4_#16061_05GARRETT 138_CB2_SRT-A
BreakerAC106.65 %309.0B329.5465.35
GD2AEP
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
AEP_P4_#16060_05GARRETT 138_CB1_SRT-A
BreakerAC106.65 %309.0B329.5465.35
GD2AEP
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
AEP_P4_#16062_05GARRETT 138_CB3_SRT-A
BreakerAC105.73 %309.0B326.7165.35
GD2AEP
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A
BusAC104.11 %309.0B321.7165.35
GD2AEP
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A
BreakerAC104.11 %309.0B321.765.35
GD2AEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC168.34 %184.0A309.7565.0
GD2AEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
SingleAC103.12 %184.0B189.7565.0
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P7-1_#10868___SRT-SL
TowerAC108.56 %361.0B391.919.85
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC108.54 %361.0B391.838.39
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#1375_05BROADF 765_P2_SRT-A
BreakerAC101.45 %361.0B366.228.5
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC118.92 %5523.0B6567.8214.94
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC116.66 %5523.0B6443.1115.65
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.3211.83
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.5315.51
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.12 %5523.0B6192.1715.79
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.8510.39
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.0216.64
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.09 %5523.0B5914.3214.57
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.3412.57
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.16 %5523.0B5863.4715.44
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC102.19 %5523.0B5644.1415.57
GD2AEP
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
AEP_P4_#16060_05GARRETT 138_CB1_SRT-A
BreakerAC106.65 %309.0B329.5665.35
GD2AEP
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
AEP_P4_#16061_05GARRETT 138_CB2_SRT-A
BreakerAC106.65 %309.0B329.5665.35
GD2AEP
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
AEP_P4_#16062_05GARRETT 138_CB3_SRT-A
BreakerAC105.72 %309.0B326.6865.35
GD2AEP
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A
BusAC104.09 %309.0B321.6265.35
GD2AEP
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A
BreakerAC104.08 %309.0B321.6165.35
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC118.71 %1532.0B1818.596.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC118.58 %1532.0B1816.676.2
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC117.61 %1532.0B1801.714.71
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC116.62 %1532.0B1786.65.07
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC115.28 %1532.0B1766.125.14
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC115.23 %1532.0B1765.385.14
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC115.19 %1532.0B1764.775.14
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC115.16 %1532.0B1764.325.14
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC114.67 %1240.0A1421.953.62
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC114.33 %1532.0B1751.586.23
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
SingleAC105.32 %1532.0B1613.524.68
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
SingleAC103.95 %1532.0B1592.573.88
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#10180_05BROADF 138_H_SRT-A
BreakerAC104.41 %296.0B309.074.7

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#10335_05SALTV2 138_U_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10335_05SALTV2 138_U_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.34 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:239.36
MW Contribution:7.31
Bus #Bus NameTypeMW Contribution
24289905CRG1H
50/50
1.476
971225AH1-072 GEN
Solar/Wind Harmer
2.356
971227AH1-073 GEN
Solar/Wind Harmer
2.356
24290005CRG1L
50/50
1.239
971687AH1-348 GEN
Solar/Wind Harmer
1.143
971315AH1-136 GEN
Solar/Wind Harmer
0.886
24290205CRG2L
50/50
1.271
970281AG2-184 GEN
Solar/Wind Harmer
15.346
972143AH1-644 GEN
Solar/Wind Harmer
7.308
962211AG1-066 GEN
Solar/Wind Harmer
1.356
24689505VACITY
50/50
7.367
24290105CRG2H
50/50
1.515
971461AH1-227 GEN
Solar/Wind Harmer
6.044
972103AH1-617 GEN
Solar/Wind Harmer
14.616
960911AF2-382 GEN
Solar/Wind Harmer
5.247
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103
LGEELTFEXP_LGEE->PJM
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.262
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#6173_05CLNCHR 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6173_05CLNCHR 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.64 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:228.88
MW Contribution:6.59
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.149
970281AG2-184 GEN
Solar/Wind Harmer
13.837
972143AH1-644 GEN
Solar/Wind Harmer
6.589
962211AG1-066 GEN
Solar/Wind Harmer
1.215
24289905CRG1H
50/50
1.335
971225AH1-072 GEN
Solar/Wind Harmer
2.132
971227AH1-073 GEN
Solar/Wind Harmer
2.132
24689505VACITY
50/50
6.663
24290105CRG2H
50/50
1.37
971461AH1-227 GEN
Solar/Wind Harmer
5.468
972103AH1-617 GEN
Solar/Wind Harmer
13.178
960911AF2-382 GEN
Solar/Wind Harmer
4.87
24290005CRG1L
50/50
1.121
971687AH1-348 GEN
Solar/Wind Harmer
1.034
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.239
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.398

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#10332_05SALTV1 138_A_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10332_05SALTV1 138_A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.21 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:227.92
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.151
970281AG2-184 GEN
Solar/Wind Harmer
13.871
972143AH1-644 GEN
Solar/Wind Harmer
6.605
962211AG1-066 GEN
Solar/Wind Harmer
1.218
24289905CRG1H
50/50
1.337
971225AH1-072 GEN
Solar/Wind Harmer
2.136
971227AH1-073 GEN
Solar/Wind Harmer
2.136
24689505VACITY
50/50
6.672
24290105CRG2H
50/50
1.372
971461AH1-227 GEN
Solar/Wind Harmer
5.478
972103AH1-617 GEN
Solar/Wind Harmer
13.21
960911AF2-382 GEN
Solar/Wind Harmer
4.871
24290005CRG1L
50/50
1.122
971687AH1-348 GEN
Solar/Wind Harmer
1.036
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.413

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P7-1_#16933___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#16933___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.03 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:225.3
MW Contribution:6.5
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.144
970281AG2-184 GEN
Solar/Wind Harmer
13.646
972143AH1-644 GEN
Solar/Wind Harmer
6.498
962211AG1-066 GEN
Solar/Wind Harmer
1.154
24289905CRG1H
50/50
1.329
971225AH1-072 GEN
Solar/Wind Harmer
2.132
971227AH1-073 GEN
Solar/Wind Harmer
2.132
24728205BUCHG1
Adder
2.336
24689505VACITY
50/50
6.635
24290105CRG2H
50/50
1.364
971461AH1-227 GEN
Solar/Wind Harmer
5.469
960911AF2-382 GEN
Solar/Wind Harmer
5.458
972103AH1-617 GEN
Solar/Wind Harmer
12.996
24290005CRG1L
50/50
1.116
971687AH1-348 GEN
Solar/Wind Harmer
1.033
24728305BUCHG2
Adder
2.336
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.363
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.387
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.277
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.402

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#10330_05SALTV1 138_C_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10330_05SALTV1 138_C_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:223.13
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.151
970281AG2-184 GEN
Solar/Wind Harmer
13.871
972143AH1-644 GEN
Solar/Wind Harmer
6.605
962211AG1-066 GEN
Solar/Wind Harmer
1.218
24289905CRG1H
50/50
1.337
971225AH1-072 GEN
Solar/Wind Harmer
2.136
971227AH1-073 GEN
Solar/Wind Harmer
2.136
24689505VACITY
50/50
6.672
24290105CRG2H
50/50
1.372
971461AH1-227 GEN
Solar/Wind Harmer
5.478
972103AH1-617 GEN
Solar/Wind Harmer
13.21
960911AF2-382 GEN
Solar/Wind Harmer
4.871
24290005CRG1L
50/50
1.122
971687AH1-348 GEN
Solar/Wind Harmer
1.036
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.413

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P2-2_#10330_05SALTV1 138_1_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10330_05SALTV1 138_1_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.05 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:223.11
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
24289905CRG1H
50/50
1.337
971225AH1-072 GEN
Solar/Wind Harmer
2.136
971227AH1-073 GEN
Solar/Wind Harmer
2.136
24689505VACITY
50/50
6.672
24290105CRG2H
50/50
1.372
971461AH1-227 GEN
Solar/Wind Harmer
5.478
972103AH1-617 GEN
Solar/Wind Harmer
13.21
960911AF2-382 GEN
Solar/Wind Harmer
4.871
24290005CRG1L
50/50
1.122
971687AH1-348 GEN
Solar/Wind Harmer
1.036
24290205CRG2L
50/50
1.151
970281AG2-184 GEN
Solar/Wind Harmer
13.871
972143AH1-644 GEN
Solar/Wind Harmer
6.605
962211AG1-066 GEN
Solar/Wind Harmer
1.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.413

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.26 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:400.85
MW Contribution:8.39
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.396
970281AG2-184 GEN
Solar/Wind Harmer
17.617
972143AH1-644 GEN
Solar/Wind Harmer
8.389
962211AG1-066 GEN
Solar/Wind Harmer
1.712
24734705WLF1G3
Adder
3.816
24734805WLF1G4
Adder
3.816
24734905WLF1G5
Adder
3.816
24735105WLF2G1
Adder
3.464
24289905CRG1H
50/50
1.621
971225AH1-072 GEN
Solar/Wind Harmer
2.59
971227AH1-073 GEN
Solar/Wind Harmer
2.59
24689505VACITY
50/50
8.092
24290105CRG2H
50/50
1.664
971461AH1-227 GEN
Solar/Wind Harmer
6.643
972103AH1-617 GEN
Solar/Wind Harmer
16.778
960911AF2-382 GEN
Solar/Wind Harmer
4.453
972273AH1-721 GEN
Adder
21.36
24290005CRG1L
50/50
1.361
971687AH1-348 GEN
Solar/Wind Harmer
1.26
24735205WLF2G2
Adder
3.464
971315AH1-136 GEN
Solar/Wind Harmer
1.038
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.334
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.848
TVALTFEXP_TVA->PJM
CLTF
2.037
NYPJM->LTFIMP_NY
CLTF
0.25
LGEELTFEXP_LGEE->PJM
CLTF
0.762
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.023
MECLTFEXP_MEC->PJM
CLTF
1.516
SIGELTFEXP_SIGE->PJM
CLTF
0.056

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o AEP_P7-1_#10868___SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.25 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:400.81
MW Contribution:9.85
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
9.789
24290105CRG2H
50/50
2.013
971461AH1-227 GEN
Solar/Wind Harmer
7.956
972103AH1-617 GEN
Solar/Wind Harmer
19.691
960911AF2-382 GEN
Solar/Wind Harmer
5.334
24289905CRG1H
50/50
1.961
971225AH1-072 GEN
Solar/Wind Harmer
3.102
971227AH1-073 GEN
Solar/Wind Harmer
3.102
24290205CRG2L
50/50
1.689
24734705WLF1G3
50/50
8.262
24734805WLF1G4
50/50
8.262
24734905WLF1G5
50/50
8.262
24735105WLF2G1
50/50
5.963
970281AG2-184 GEN
Solar/Wind Harmer
20.676
972143AH1-644 GEN
Solar/Wind Harmer
9.846
962211AG1-066 GEN
Solar/Wind Harmer
1.946
24290005CRG1L
50/50
1.646
24735205WLF2G2
50/50
5.963
971687AH1-348 GEN
Solar/Wind Harmer
1.507
971315AH1-136 GEN
Solar/Wind Harmer
1.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.483
LAGNLTFEXP_LAGN->PJM
CLTF
2.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.929
TVALTFEXP_TVA->PJM
CLTF
1.512
NYPJM->LTFIMP_NY
CLTF
0.219
LGEELTFEXP_LGEE->PJM
CLTF
0.565
WECLTFEXP_WEC->PJM
CLTF
0.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.211
MECLTFEXP_MEC->PJM
CLTF
1.019
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2500.92
MW Contribution:6.96
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
26.913
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
9.063
960911AF2-382 GEN
Solar/Wind Harmer
5.848
971461AH1-227 GEN
Solar/Wind Harmer
3.853
972103AH1-617 GEN
Solar/Wind Harmer
13.923
270053AF1-130 C
Solar/Wind Harmer
2.393
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.326
339250AF1-203 GEN
Solar/Wind Harmer
0.353
971155AH1-034 GEN
Solar/Wind Harmer
5.827
962251AG1-071 GEN
Solar/Wind Harmer
3.186
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
2.839
966571AG1-526 GEN
Solar/Wind Harmer
12.469
970093AG2-073 GEN
Solar/Wind Harmer
5.535
270030AE2-140 GEN
Solar/Wind Harmer
10.994
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
3.962
958171AF2-111 GEN
Solar/Wind Harmer
12.227
970243AG2-164 GEN
Solar/Wind Harmer
12.56
970519AG2-331 GEN
Solar/Wind Harmer
8.438
970699AG2-449 GEN
Solar/Wind Harmer
5.582
942481AE2-261 GEN
Solar/Wind Harmer
14.457
276621W2-048 GEN
Solar/Wind Harmer
2.989
276838X2-022 GEN2
Solar/Wind Harmer
0.111
970193AG2-126 GEN
Solar/Wind Harmer
7.161
276668AB2-070 GEN1
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
1.442
971993AH1-541 GEN
Solar/Wind Harmer
4.403
965931AG1-462 GEN
Solar/Wind Harmer
12.103
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
3.387
965091AG1-374 GEN
Solar/Wind Harmer
14.098
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
1.583
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.314
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
3.284
971485AH1-239 GEN
Solar/Wind Harmer
4.843
339231AF1-038_GEN
Solar/Wind Harmer
1.082
339255AE2-071 GEN
Solar/Wind Harmer
0.618
24735205WLF2G2
Adder
4.909
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.747
971403AH1-188 GEN
Solar/Wind Harmer
9.188
971315AH1-136 GEN
Solar/Wind Harmer
1.275
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
1.013
962241AG1-070 GEN
Solar/Wind Harmer
2.607
964901AG1-354 GEN
Solar/Wind Harmer
8.682
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
5.664
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
1.077
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.669
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339216AC1-074 GEN
Solar/Wind Harmer
0.86
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
9.348
270445AC2-157 GEN2
Solar/Wind Harmer
2.736
970333AG2-219 GEN
Solar/Wind Harmer
15.351
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.939
963831AG1-236 GEN
Solar/Wind Harmer
4.696
274880W4-005 GEN4
Solar/Wind Harmer
1.442
972175AH1-670 GEN
Solar/Wind Harmer
6.469
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
3.316
274877BISHOP HL;1U
Solar/Wind Harmer
1.583
276158O29GEN2
Solar/Wind Harmer
2.349
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
3.699
939741AE1-205 GEN
Solar/Wind Harmer
9.353
274857EASY ROAD;U1
Solar/Wind Harmer
2.241
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
21.031
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
10.445
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
315616AA1-038_C
Solar/Wind Helper
1.807
24735105WLF2G1
Adder
4.909
24734705WLF1G3
Adder
4.898
24734805WLF1G4
Adder
4.898
24734905WLF1G5
Adder
4.898
966391AG1-508 GEN
Solar/Wind Harmer
2.785
971981AH1-535 GEN
Solar/Wind Harmer
7.897
971313AH1-133 GEN
Solar/Wind Harmer
7.717
970281AG2-184 GEN
Solar/Wind Harmer
14.619
972143AH1-644 GEN
Solar/Wind Harmer
6.961
962211AG1-066 GEN
Solar/Wind Harmer
1.642
270399AC1-101 GEN
Solar/Wind Harmer
2.775
270400AC1-102 GEN
Solar/Wind Harmer
2.775
957241AF2-018 GEN
Solar/Wind Harmer
2.86
965401AG1-405 GEN
Solar/Wind Harmer
3.385
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.854
970455AG2-298 GEN
Solar/Wind Harmer
3.268
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.233
972163AH1-664 GEN
Solar/Wind Harmer
4.977
964781AG1-341 GEN
Solar/Wind Harmer
6.173
339236AF1-050_GEN
Solar/Wind Harmer
1.045
971081AG2-670 GEN
Solar/Wind Harmer
4.298
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
2.668
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
3.502
942891AE2-308 GEN
Solar/Wind Harmer
5.447
964571AG1-320 GEN
Solar/Wind Harmer
4.432
971125AH1-004 GEN
Solar/Wind Harmer
2.1
970107AG2-081 GEN
Solar/Wind Harmer
1.575
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.035
339221AD2-048_GEN
Solar/Wind Harmer
0.789
970235AG2-159 GEN
Solar/Wind Harmer
2.014
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
2.736
970239AG2-162 GEN
Solar/Wind Harmer
5.35
276916AD2-100_GEN
Solar/Wind Harmer
10.174
276911AD2-131_GEN
Solar/Wind Harmer
2.056
957381AF2-032 GEN
Solar/Wind Harmer
0.202
276763AC1-053 GEN1
Solar/Wind Harmer
1.888
276764AC1-053 GEN2
Solar/Wind Harmer
1.888
945391AF1-204 GEN
Solar/Wind Harmer
6.653
270186AC1-089 GEN
Solar/Wind Harmer
2.887
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
1.871
276741O09 GEN1
Solar/Wind Harmer
1.678
276708O09 GEN2
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
1.333
274849CRESCENT ;1U
Solar/Wind Harmer
0.866
276645AC1-214 GEN1
Solar/Wind Harmer
0.627
276646AC1-214 GEN2
Solar/Wind Harmer
0.627
276603SUBLETTE C
Solar/Wind Harmer
0.491
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
11.684
938861AE1-114 GEN
Solar/Wind Harmer
3.828
274856ECOGROVE ;U1
Solar/Wind Harmer
1.572
276611AD2-172 GEN
Solar/Wind Harmer
1.193
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
970819AG2-516 GEN
Solar/Wind Harmer
0.945
972165AH1-665 GEN
Solar/Wind Harmer
3.982
944221AF1-090 GEN
Solar/Wind Harmer
5.331
276849AB2-070 GEN2
Solar/Wind Harmer
1.072
276848AB2-070 GEN3
Solar/Wind Harmer
1.072
276785W4-005 GEN1
Solar/Wind Harmer
1.442
276174W4-005 GEN2
Solar/Wind Harmer
1.442
946321AF1-296 GEN
Solar/Wind Harmer
4.942
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
3.031
961011AF2-392 GEN
Solar/Wind Harmer
5.096
957751AF2-069 GEN
Solar/Wind Harmer
0.215
276655WTG1_EQ
Solar/Wind Harmer
4.083
276656WTG2_EQ
Solar/Wind Harmer
0.541
959341AF2-225 GEN
Solar/Wind Harmer
7.015
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
7.003
270367AC2-061_GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.193
274823ROCKFORD ;21
Adder
9.057
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
7.487
274735ELWOOD EC;4P
Adder
2.023
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
276157O29GEN1
Solar/Wind Harmer
1.787
942111AE2-223 GEN
Solar/Wind Harmer
3.834
274858EASY ROAD;U2
Solar/Wind Harmer
2.241
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
274729ELWOOD EC;1P
Adder
7.487
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:5.26
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
50/50
5.209
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.41
971315AH1-136 GEN
Solar/Wind Harmer
0.889
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
0.002
962241AG1-070 GEN
Solar/Wind Harmer
2.203
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
3.952
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.098
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
274880W4-005 GEN4
Solar/Wind Harmer
0
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
6.207
960911AF2-382 GEN
Solar/Wind Harmer
4.08
971461AH1-227 GEN
Solar/Wind Harmer
2.688
972103AH1-617 GEN
Solar/Wind Harmer
9.714
270053AF1-130 C
Solar/Wind Harmer
1.017
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.743
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
1.981
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
270030AE2-140 GEN
Solar/Wind Harmer
7.67
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
2.764
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970243AG2-164 GEN
Solar/Wind Harmer
1.988
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
970193AG2-126 GEN
Solar/Wind Harmer
4.996
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.536
965931AG1-462 GEN
Solar/Wind Harmer
8.444
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.836
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
970571AG2-364 GEN
Solar/Wind Harmer
6.485
959091AF2-200 GEN
Solar/Wind Harmer
6.478
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
276806AD2-047 C O1
Solar/Wind Harmer
1.793
970941AG2-585 GEN
Solar/Wind Harmer
3.954
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270437AC2-090 C
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
253406AD2-031_GEN
Solar/Wind Harmer
0.232
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
2.291
971485AH1-239 GEN
Solar/Wind Harmer
3.379
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
2.512
942891AE2-308 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
3.444
971125AH1-004 GEN
Solar/Wind Harmer
1.465
970107AG2-081 GEN
Solar/Wind Harmer
1.099
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
970239AG2-162 GEN
Solar/Wind Harmer
0.849
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276911AD2-131_GEN
Solar/Wind Harmer
0.468
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
3.539
270186AC1-089 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.117
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
971333AH1-146 GEN
Solar/Wind Harmer
6.465
971335AH1-147 GEN
Solar/Wind Harmer
6.465
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.647
958491AF2-143 GEN
Solar/Wind Harmer
4.817
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
25183208HLCRTG
Solar/Wind Harmer
0.005
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
1.51
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
270599AE1-208 GEN
Solar/Wind Harmer
2.851
270031AE2-169
Solar/Wind Harmer
1.71
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
24735105WLF2G1
50/50
5.209
24734705WLF1G3
50/50
5.198
24734805WLF1G4
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
971313AH1-133 GEN
Solar/Wind Harmer
5.384
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
270400AC1-102 GEN
Solar/Wind Harmer
1.445
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
965401AG1-405 GEN
Solar/Wind Harmer
2.362
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
972165AH1-665 GEN
Solar/Wind Harmer
3.096
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.851
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
957751AF2-069 GEN
Solar/Wind Harmer
0.108
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.426
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
9.057
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.478
970169AG2-114 GEN
Solar/Wind Harmer
3.233
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
3.163
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
1.877
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971985AH1-537 GEN
Solar/Wind Harmer
0.937
270594AE1-207 GEN
Solar/Wind Harmer
3.524
958391AF2-133 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971609AH1-304 GEN
Solar/Wind Harmer
0.508
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
971029AG2-637 GEN
Solar/Wind Harmer
4.547
972175AH1-670 GEN
Solar/Wind Harmer
2.731
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
7.717
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
970569AG2-363 GEN
Solar/Wind Harmer
9.728
252507AC2-088 GEN
Solar/Wind Harmer
0.147
957471AF2-041 GEN
Solar/Wind Harmer
9.717
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.69
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
0.568
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
274745AC1-111 GEN9
Adder
2.558
24791305MDL-5G
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.539
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.313
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
965031AG1-367 GEN
Solar/Wind Harmer
3.137
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:9.76
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:12.97
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:12.93
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:12.92
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:12.92
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line l/o AEP_P4_#16061_05GARRETT 138_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16061_05GARRETT 138_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:329.54
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line l/o AEP_P4_#16060_05GARRETT 138_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16060_05GARRETT 138_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:329.54
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line l/o AEP_P4_#16062_05GARRETT 138_CB3_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16062_05GARRETT 138_CB3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.73 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:326.71
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line l/o AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:321.71
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
972103AH1-617 GEN
Solar/Wind Harmer
130.705
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line l/o AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CONSTP-05BEAVER CR1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:321.7
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:168.34 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:309.75
MW Contribution:65.0
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
126
972143AH1-644 GEN
Solar/Wind Harmer
65
972103AH1-617 GEN
Solar/Wind Harmer
120

Details for 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.12 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:189.75
MW Contribution:65.0
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
126
972143AH1-644 GEN
Solar/Wind Harmer
65

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P7-1_#10868___SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.56 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:391.91
MW Contribution:9.85
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
9.789
24290105CRG2H
50/50
2.013
971461AH1-227 GEN
Solar/Wind Harmer
7.956
972103AH1-617 GEN
Solar/Wind Harmer
19.691
960911AF2-382 GEN
Solar/Wind Harmer
5.334
24290005CRG1L
50/50
1.646
24735205WLF2G2
50/50
5.963
971687AH1-348 GEN
Solar/Wind Harmer
1.507
971315AH1-136 GEN
Solar/Wind Harmer
1.196
24290205CRG2L
50/50
1.689
24734705WLF1G3
50/50
8.262
24734805WLF1G4
50/50
8.262
24734905WLF1G5
50/50
8.262
24735105WLF2G1
50/50
5.963
970281AG2-184 GEN
Solar/Wind Harmer
20.676
972143AH1-644 GEN
Solar/Wind Harmer
9.846
962211AG1-066 GEN
Solar/Wind Harmer
1.946
24289905CRG1H
50/50
1.961
971225AH1-072 GEN
Solar/Wind Harmer
3.102
971227AH1-073 GEN
Solar/Wind Harmer
3.102
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.483
LAGNLTFEXP_LAGN->PJM
CLTF
2.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.929
TVALTFEXP_TVA->PJM
CLTF
1.512
NYPJM->LTFIMP_NY
CLTF
0.219
LGEELTFEXP_LGEE->PJM
CLTF
0.565
WECLTFEXP_WEC->PJM
CLTF
0.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.211
MECLTFEXP_MEC->PJM
CLTF
1.019
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.54 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:391.83
MW Contribution:8.39
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
8.092
24290105CRG2H
50/50
1.664
971461AH1-227 GEN
Solar/Wind Harmer
6.643
972103AH1-617 GEN
Solar/Wind Harmer
16.778
960911AF2-382 GEN
Solar/Wind Harmer
4.453
972273AH1-721 GEN
Adder
21.36
24290005CRG1L
50/50
1.361
971687AH1-348 GEN
Solar/Wind Harmer
1.26
24735205WLF2G2
Adder
3.464
971315AH1-136 GEN
Solar/Wind Harmer
1.038
24289905CRG1H
50/50
1.621
971225AH1-072 GEN
Solar/Wind Harmer
2.59
971227AH1-073 GEN
Solar/Wind Harmer
2.59
24290205CRG2L
50/50
1.396
970281AG2-184 GEN
Solar/Wind Harmer
17.617
972143AH1-644 GEN
Solar/Wind Harmer
8.389
962211AG1-066 GEN
Solar/Wind Harmer
1.712
24734705WLF1G3
Adder
3.816
24734805WLF1G4
Adder
3.816
24734905WLF1G5
Adder
3.816
24735105WLF2G1
Adder
3.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.334
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.848
TVALTFEXP_TVA->PJM
CLTF
2.037
NYPJM->LTFIMP_NY
CLTF
0.25
LGEELTFEXP_LGEE->PJM
CLTF
0.762
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.023
MECLTFEXP_MEC->PJM
CLTF
1.516
SIGELTFEXP_SIGE->PJM
CLTF
0.056

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#1375_05BROADF 765_P2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1375_05BROADF 765_P2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.45 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:366.22
MW Contribution:8.5
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.423
970281AG2-184 GEN
Solar/Wind Harmer
17.842
972143AH1-644 GEN
Solar/Wind Harmer
8.496
962211AG1-066 GEN
Solar/Wind Harmer
1.733
24734705WLF1G3
Adder
4.046
24734805WLF1G4
Adder
4.046
24734905WLF1G5
Adder
4.046
24735105WLF2G1
Adder
3.65
971981AH1-535 GEN
Solar/Wind Harmer
4.458
24289905CRG1H
50/50
1.652
971225AH1-072 GEN
Solar/Wind Harmer
2.639
971227AH1-073 GEN
Solar/Wind Harmer
2.639
24689505VACITY
50/50
8.247
24290105CRG2H
50/50
1.696
971461AH1-227 GEN
Solar/Wind Harmer
6.769
972103AH1-617 GEN
Solar/Wind Harmer
16.992
960911AF2-382 GEN
Solar/Wind Harmer
4.731
972273AH1-721 GEN
Adder
21.458
24290005CRG1L
50/50
1.387
971687AH1-348 GEN
Solar/Wind Harmer
1.284
24735205WLF2G2
Adder
3.65
971315AH1-136 GEN
Solar/Wind Harmer
1.036
CPLELTFEXP_CPLE->PJM
CLTF
0.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.396
LAGNLTFEXP_LAGN->PJM
CLTF
3.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.759
TVALTFEXP_TVA->PJM
CLTF
2.133
NYPJM->LTFIMP_NY
CLTF
0.222
LGEELTFEXP_LGEE->PJM
CLTF
0.695
WECLTFEXP_WEC->PJM
CLTF
0.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.251
MECLTFEXP_MEC->PJM
CLTF
1.411
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.92 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6567.82
MW Contribution:14.94
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
13.011
24723005RIVRG1
Adder
35.494
24723105RIVRG2
Adder
35.494
24685805CER G1
Adder
15.083
24685905CER G2
Adder
15.083
944971AF1-162 GEN
Solar/Wind Harmer
11.935
24728205BUCHG1
Adder
6.779
971225AH1-072 GEN
Solar/Wind Harmer
2.955
971227AH1-073 GEN
Solar/Wind Harmer
2.955
970239AG2-162 GEN
Solar/Wind Harmer
14.933
270214AC2-123 GEN
Solar/Wind Harmer
3.11
971277AH1-098 GEN
Solar/Wind Harmer
5.306
270444AC2-157 GEN1
Solar/Wind Harmer
7.082
970321AG2-212 GEN
Solar/Wind Harmer
22.591
966841AG1-555 GEN
Solar/Wind Harmer
3.087
970241AG2-163 GEN
Solar/Wind Harmer
30.74
945391AF1-204 GEN
Solar/Wind Harmer
17.134
270583AD2-179 GEN
Solar/Wind Harmer
12.284
945421AF1-207 GEN
Solar/Wind Harmer
17.235
957841AF2-078 GEN
Solar/Wind Harmer
7.417
960161AF2-307 GEN
Solar/Wind Harmer
7.874
274770LINCOLN ;1U
Adder
7.573
274771LINCOLN ;2U
Adder
7.573
276763AC1-053 GEN1
Solar/Wind Harmer
4.827
276764AC1-053 GEN2
Solar/Wind Harmer
4.827
276916AD2-100_GEN
Solar/Wind Harmer
25.634
276911AD2-131_GEN
Solar/Wind Harmer
5.181
957381AF2-032 GEN
Solar/Wind Harmer
0.511
960611AF2-352 GEN
Solar/Wind Harmer
2.837
972259AH1-714 GEN
Adder
23.231
274696ROCKY RD ;4P
Adder
13.859
274695ROCKY RD ;2P
Adder
13.539
274693ROCKY RD ;1P
Adder
13.406
274697ROCKY RD ;3P
Adder
3.678
274674JOLIET 9 ;6U
Adder
18.717
274683WAUKEGAN ;8U
Adder
25.61
274683WAUKEGAN ;8U
Adder
21.588
23652301WDPWR_K20
Solar/Wind Helper
0.145
23585401KL_K28_T16
Solar/Wind Helper
1.297
962101AG1-054 GEN
Solar/Wind Helper
0.64
241985AE1-237 GEN
Solar/Wind Helper
0.244
241967AE2-285_GEN
Solar/Wind Helper
0.626
241801AE1-079 GEN
Solar/Wind Helper
0.243
203955AF1-039 C O1
Solar/Wind Helper
0.37
944781AF1-143 GEN
Solar/Wind Helper
2.439
20083426SW_E13_K22
Solar/Wind Helper
0.055
946071AF1-272 GEN
Solar/Wind Helper
2.647
20088926STNY CRK
Solar/Wind Helper
0.8
20084626FORWARD
Solar/Wind Helper
0.347
238120AE2-309 GEN
Solar/Wind Helper
0.426
203940AF1-140 C
Solar/Wind Helper
0.385
20088626ARWF_N39
Solar/Wind Helper
1.174
20303426NA_O38_P22
Solar/Wind Helper
0.963
946381AF1-302 GEN
Solar/Wind Helper
0.215
203853AF1-134 C O1
Solar/Wind Helper
0.463
203952AE2-129 C
Solar/Wind Helper
0.458
203946AE2-131 C
Solar/Wind Helper
0.459
24721605FLATG1
50/50
2.932
962771AG1-126 GEN
Solar/Wind Harmer
67.471
972203AH1-686 GEN
Adder
4.314
957241AF2-018 GEN
Solar/Wind Harmer
7.577
270399AC1-101 GEN
Solar/Wind Harmer
7.162
270400AC1-102 GEN
Solar/Wind Harmer
7.162
24477305BRIDGE
Adder
0.586
270330AC1-082 GEN2
Solar/Wind Harmer
1.275
270329AC1-082 GEN1
Solar/Wind Harmer
0.751
941621AE2-160 GEN
Adder
5.032
970281AG2-184 GEN
Solar/Wind Harmer
31.364
972143AH1-644 GEN
Solar/Wind Harmer
14.935
971313AH1-133 GEN
Solar/Wind Harmer
14.825
270132AB1-180 C
Adder
0.172
962211AG1-066 GEN
Solar/Wind Harmer
3.426
24734705WLF1G3
Adder
8.014
24734805WLF1G4
Adder
8.014
24734905WLF1G5
Adder
8.014
971061AG2-657 GEN
Solar/Wind Harmer
12.379
24735105WLF2G1
Adder
7.873
966391AG1-508 GEN
Solar/Wind Harmer
4.623
971985AH1-537 GEN
Solar/Wind Harmer
23.443
971981AH1-535 GEN
Solar/Wind Harmer
12.541
24386205FR-12G C
Solar/Wind Harmer
5.273
24386405FR-21G C
Solar/Wind Harmer
5.292
24386605FR-22G C
Solar/Wind Harmer
5.292
24387005FR-3G C
Solar/Wind Harmer
4.867
963841AG1-237 GEN
Solar/Wind Harmer
13.441
24690905MDL-1G C
Solar/Wind Harmer
9.861
270180AB1-006 GEN1
Solar/Wind Harmer
8.834
946581AF1-322 GEN
Solar/Wind Harmer
12.566
24691005MDL-2G C
Solar/Wind Harmer
4.542
24697605MDL-3G C
Solar/Wind Harmer
4.528
24697905MDL-4G C
Solar/Wind Harmer
2.819
270181AB1-006 GEN2
Solar/Wind Harmer
0.878
274775LINCOLN ;6U
Adder
7.573
274776LINCOLN ;7U
Adder
7.573
274777LINCOLN ;8U
Adder
7.573
944221AF1-090 GEN
Solar/Wind Harmer
13.349
276785W4-005 GEN1
Solar/Wind Harmer
3.693
276174W4-005 GEN2
Solar/Wind Harmer
3.693
276849AB2-070 GEN2
Solar/Wind Harmer
2.746
276848AB2-070 GEN3
Solar/Wind Harmer
2.746
276655WTG1_EQ
Solar/Wind Harmer
10.651
276656WTG2_EQ
Solar/Wind Harmer
1.41
959341AF2-225 GEN
Solar/Wind Harmer
18.299
274746AC1-111 G10
Adder
6.801
274744AC1-111 GEN8
Adder
6.801
972227AH1-698 GEN1
Adder
3.171
274731ELWOOD EC;2P
Adder
19.981
274733ELWOOD EC;3P
Adder
19.981
274735ELWOOD EC;4P
Adder
19.981
274728ELWOOD EC;5P
Adder
19.981
274675JOLIET 29;7U
Adder
37.288
274675JOLIET 29;7U
Adder
35.957
274687WILL CNTY;4U
Adder
2.145
23750501ELLIOTTS
Solar/Wind Helper
0.675
254304AE2-114 C
Solar/Wind Helper
0.214
241997AF1-093 GEN
Solar/Wind Helper
0.251
241982AE2-343 S C
Solar/Wind Helper
0.219
238126S14_GEN_1
Solar/Wind Helper
0.681
20092526R32
Solar/Wind Helper
1.133
203961AE2-224 GEN
Solar/Wind Helper
2.335
20091526CHSTN_FL
Solar/Wind Helper
0.565
203846AF2-130 C
Solar/Wind Helper
0.44
20090526Q36
Solar/Wind Helper
1.009
203993AD2-133_GEN1
Solar/Wind Helper
1.009
203804AE2-113_GEN
Solar/Wind Helper
1.683
941231AE2-117 GEN
Solar/Wind Helper
0.455
203855AF2-088 C
Solar/Wind Helper
0.148
238109AE1-109 GEN2
Solar/Wind Helper
0.085
238110AE1-109 GEN3
Solar/Wind Helper
0.085
941731AE2-173 GEN
Solar/Wind Harmer
5.878
24289405MTG1
50/50
11.755
24318705GVG2
50/50
12.111
24722005FLATG5
50/50
2.932
24721905FLATG4
50/50
53.759
970153AG2-106 GEN
Solar/Wind Harmer
29.42
24686205CER G4
Adder
15.103
24686405CER G5
Adder
15.043
270053AF1-130 C
Solar/Wind Harmer
6.338
970913AG2-568 GEN
Solar/Wind Harmer
12.572
960911AF2-382 GEN
Solar/Wind Harmer
11.374
972103AH1-617 GEN
Solar/Wind Harmer
29.871
971461AH1-227 GEN
Solar/Wind Harmer
7.579
971191AH1-055 GEN
Solar/Wind Harmer
32.25
270346AE1-212 GEN
Solar/Wind Harmer
12.382
970243AG2-164 GEN
Solar/Wind Harmer
35.061
970519AG2-331 GEN
Solar/Wind Harmer
23.555
970699AG2-449 GEN
Solar/Wind Harmer
15.583
943031AE2-326 GEN
Solar/Wind Harmer
4.895
971331AH1-145 GEN
Solar/Wind Harmer
11.867
957541AF2-048 GEN
Solar/Wind Harmer
2.003
970513AG2-328 GEN
Solar/Wind Harmer
22.591
970517AG2-330 GEN
Solar/Wind Harmer
20.49
247619Y1-049
Adder
0.54
970193AG2-126 GEN
Solar/Wind Harmer
18.442
24755605MDL-5G
Solar/Wind Harmer
2.962
970781AG2-491 GEN
Solar/Wind Harmer
12.28
958121AF2-106 GEN
Solar/Wind Harmer
5.567
274772LINCOLN ;3U
Adder
7.573
276686W4-005 GEN3
Solar/Wind Harmer
3.693
971993AH1-541 GEN
Solar/Wind Harmer
11.28
276668AB2-070 GEN1
Solar/Wind Harmer
2.746
276621W2-048 GEN
Solar/Wind Harmer
7.618
276838X2-022 GEN2
Solar/Wind Harmer
0.284
942481AE2-261 GEN
Solar/Wind Harmer
36.492
274853TWINGROVE;U1
Solar/Wind Harmer
8.794
965091AG1-374 GEN
Solar/Wind Harmer
36.602
959611AF2-252 GEN
Solar/Wind Harmer
2.837
942111AE2-223 GEN
Solar/Wind Harmer
10.001
972273AH1-721 GEN
Adder
101.345
972228AH1-698 GEN2
Adder
4.504
274729ELWOOD EC;1P
Adder
19.981
274730ELWOOD EC;6P
Adder
19.981
274734ELWOOD EC;8P
Adder
19.981
274736ELWOOD EC;9P
Adder
19.981
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
35.957
237048AF1-022 C
Solar/Wind Helper
0.196
235058AG1-386 C
Solar/Wind Helper
0.457
237043AE2-125 C
Solar/Wind Helper
0.18
254305AE2-115 C
Solar/Wind Helper
0.214
23750701CROSSCHOOL
Solar/Wind Helper
1.202
202652Y1-033 WT C
Solar/Wind Helper
0.561
964991AG1-363 GEN
Solar/Wind Helper
3.697
238118U2-030_1
Solar/Wind Helper
0.289
20089126CSLMN_L13
Solar/Wind Helper
0.588
20089026BF_G21_K23
Solar/Wind Helper
0.465
238127S14_GEN_2
Solar/Wind Helper
0.681
203818AF1-086 GEN
Solar/Wind Helper
1.639
959441AF2-235 GEN
Solar/Wind Helper
0.228
203854AF2-039 C
Solar/Wind Helper
0.307
20334926Z1-069 C
Solar/Wind Helper
1.299
238202AE2-262_GEN
Solar/Wind Helper
0.919
203830AF1-094 GEN
Solar/Wind Helper
0.445
962511AG1-100 GEN
Solar/Wind Helper
0.442
24289405MTG1
50/50
11.755
243186AF1-051 GEN
50/50
13.011
24318705GVG2
50/50
12.111
24721805FLATG3
50/50
2.932
24721705FLATG2
50/50
53.759
962761AG1-125 GEN
Solar/Wind Harmer
67.471
970149AG2-104 GEN
Solar/Wind Harmer
83.326
970155AG2-107 GEN
Solar/Wind Harmer
29.42
24723205RIVRG3
Adder
35.494
24686105CER G3
Adder
15.183
24686505CER G6
Adder
15.163
971403AH1-188 GEN
Solar/Wind Harmer
23.764
270331AC1-082 GEN3
Solar/Wind Harmer
0.753
970947AG2-589 GEN
Solar/Wind Harmer
3.299
960001AF2-291 GEN
Solar/Wind Harmer
4.831
24728305BUCHG2
Adder
6.779
971315AH1-136 GEN
Solar/Wind Harmer
2.975
971687AH1-348 GEN
Solar/Wind Harmer
1.478
24735205WLF2G2
Adder
7.873
970333AG2-219 GEN
Solar/Wind Harmer
42.852
970091AG2-072 GEN
Adder
103.022
971329AH1-144 GEN
Solar/Wind Harmer
15.308
270445AC2-157 GEN2
Solar/Wind Harmer
7.082
927014AC1-188 GEN
Solar/Wind Harmer
2.008
970245AG2-165 GEN
Solar/Wind Harmer
22.591
24385905FR-11G C
Solar/Wind Harmer
10.226
24387305FR-4G C
Solar/Wind Harmer
6.252
963741AG1-226 GEN
Solar/Wind Harmer
55.333
24791305MDL-5G
Solar/Wind Harmer
2.962
972207SS24-0001
Solar/Wind Harmer
26.925
274773LINCOLN ;4U
Adder
7.573
274774LINCOLN ;5U
Adder
7.573
274880W4-005 GEN4
Solar/Wind Harmer
3.693
963831AG1-236 GEN
Solar/Wind Harmer
12.008
276615X2-022 GEN
Solar/Wind Harmer
2.392
972175AH1-670 GEN
Solar/Wind Harmer
16.675
965911AG1-460 GEN
Solar/Wind Harmer
1.703
940581AE2-045 GEN
Solar/Wind Harmer
12.446
971605AH1-302 GEN
Solar/Wind Harmer
10.643
274854TWINGROVE;U2
Solar/Wind Harmer
8.609
276726Z2-087_GEN
Solar/Wind Harmer
9.649
274745AC1-111 GEN9
Adder
6.801
274674JOLIET 9 ;6U
Adder
18.717
274732ELWOOD EC;7P
Adder
19.981
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
37.288
274828WAUKEGAN ;BP
Adder
13.424
237046AF1-021 C
Solar/Wind Helper
0.497
238185AF2-356 C
Solar/Wind Helper
2.208
254303AC2-168 GEN
Solar/Wind Helper
0.155
23751201ROTHROCK
Solar/Wind Helper
0.744
241966AE1-183 GEN
Solar/Wind Helper
0.251
235054AD2-180 GEN
Solar/Wind Helper
1.717
23562501BACKB
Solar/Wind Helper
0.906
238117U2-030
Solar/Wind Helper
0.289
20089226LOOKOUT
Solar/Wind Helper
0.572
235531U2-073 GEN
Solar/Wind Helper
2.719
20088826HIGHLAND
Solar/Wind Helper
0.874
20094526CT_V3-030
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.47
23751101LEADS_P59
Solar/Wind Helper
1.247
203860AG1-193 C
Solar/Wind Helper
0.227
203954AE2-126 C
Solar/Wind Helper
0.454
964391AG1-301 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.085
238206AE2-263_GEN
Solar/Wind Helper
0.874
959471AF2-238 GEN
Solar/Wind Helper
0.447
961971AG1-040 GEN
Solar/Wind Helper
0.444
203835AF1-098 GEN
Solar/Wind Helper
1.765
939741AE1-205 GEN
Solar/Wind Harmer
20.221
238217AF1-153 C O1
Solar/Wind Helper
0.229
20398826ARMNA MT
Solar/Wind Helper
1.433
203979AG1-198 GEN
Solar/Wind Helper
0.267
203980AG1-197 GEN
Solar/Wind Helper
0.333
944201AF1-088_MTX
Adder
147.459
957141AF2-008_MTX
Adder
73.729
CPLELTFEXP_CPLE->PJM
CLTF
6.999
CBM West 2LTFEXP_CBM-W2->PJM
CBM
159.017
LAGNLTFEXP_LAGN->PJM
CLTF
23.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.656
TVALTFEXP_TVA->PJM
CLTF
11.825
NYPJM->LTFIMP_NY
CLTF
5.324
LGEELTFEXP_LGEE->PJM
CLTF
8.439
WECLTFEXP_WEC->PJM
CLTF
4.643
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.422
CBM West 1LTFEXP_CBM-W1->PJM
CBM
150.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.72
MECLTFEXP_MEC->PJM
CLTF
20.29
SIGELTFEXP_SIGE->PJM
CLTF
0.642

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.66 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6443.11
MW Contribution:15.65
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
6.465
970153AG2-106 GEN
Solar/Wind Harmer
23.885
971191AH1-055 GEN
Solar/Wind Harmer
36.863
957541AF2-048 GEN
Solar/Wind Harmer
2.488
970913AG2-568 GEN
Solar/Wind Harmer
12.569
972103AH1-617 GEN
Solar/Wind Harmer
31.296
960911AF2-382 GEN
Solar/Wind Harmer
11.517
971461AH1-227 GEN
Solar/Wind Harmer
7.832
970243AG2-164 GEN
Solar/Wind Harmer
38.293
970519AG2-331 GEN
Solar/Wind Harmer
25.727
970699AG2-449 GEN
Solar/Wind Harmer
17.019
972167AH1-666 GEN
Solar/Wind Harmer
11.674
958171AF2-111 GEN
Solar/Wind Harmer
36.017
252510AF1-249 C
Solar/Wind Harmer
0.598
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
14.232
253316AC1-085 GEN3
Solar/Wind Harmer
11.89
253433AC1-085 GEN1
Solar/Wind Harmer
7.548
946181AF1-283 GEN
Solar/Wind Harmer
18.454
253406AD2-031_GEN
Solar/Wind Harmer
1.808
966571AG1-526 GEN
Solar/Wind Harmer
31.338
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
3.053
971227AH1-073 GEN
Solar/Wind Harmer
3.053
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
16.31
270186AC1-089 GEN
Solar/Wind Harmer
9.06
962581AG1-107 GEN
Solar/Wind Harmer
7.424
961491AF2-440 GEN
Solar/Wind Harmer
3.085
960161AF2-307 GEN
Solar/Wind Harmer
9.441
970879AG2-548 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
6.295
252509AD1-136 GEN
Solar/Wind Harmer
0.372
339221AD2-048_GEN
Solar/Wind Harmer
2.218
972043AH1-570 GEN
Solar/Wind Harmer
3.602
972045AH1-571 GEN
Solar/Wind Harmer
2.882
25183208HLCRTG
Solar/Wind Harmer
8.709
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
6.647
970235AG2-159 GEN
Solar/Wind Harmer
5.741
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
5.722
970107AG2-081 GEN
Solar/Wind Harmer
4.291
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
14.268
253317AC1-085 GEN4
Solar/Wind Harmer
11.89
270444AC2-157 GEN1
Solar/Wind Harmer
7.855
253394AE2-221_GEN
Solar/Wind Harmer
6.369
253398AE2-221_GEN2
Solar/Wind Harmer
6.369
964571AG1-320 GEN
Solar/Wind Harmer
11.394
970653AG2-424 GEN
Solar/Wind Harmer
6.671
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
10.253
945391AF1-204 GEN
Solar/Wind Harmer
19.047
24379505HDWTR1G C
Solar/Wind Harmer
10.797
270209AC1-174_GEN
Solar/Wind Harmer
7.62
926881AC1-175 GEN
Solar/Wind Harmer
7.62
253370AE2-315 SEC1
Adder
2.733
339231AF1-038_GEN
Solar/Wind Harmer
2.469
270383AD1-128 GEN
Solar/Wind Harmer
8.302
339236AF1-050_GEN
Solar/Wind Harmer
2.463
970241AG2-163 GEN
Solar/Wind Harmer
33.893
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
25326109MON D
Adder
1.763
247621Y3-024
Adder
0.32
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.049
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
970825AG2-519 GEN
Solar/Wind Harmer
8.467
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
1.362
270329AC1-082 GEN1
Solar/Wind Harmer
0.802
957241AF2-018 GEN
Solar/Wind Harmer
7.728
270399AC1-101 GEN
Solar/Wind Harmer
7.31
270400AC1-102 GEN
Solar/Wind Harmer
7.31
962771AG1-126 GEN
Solar/Wind Harmer
54.777
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
32.861
972143AH1-644 GEN
Solar/Wind Harmer
15.648
971985AH1-537 GEN
Solar/Wind Harmer
27.909
941621AE2-160 GEN
Adder
5.057
962211AG1-066 GEN
Solar/Wind Harmer
3.665
971313AH1-133 GEN
Solar/Wind Harmer
14.875
270367AC2-061_GEN
Solar/Wind Harmer
4.719
970879AG2-548 GEN
Solar/Wind Harmer
6.295
972163AH1-664 GEN
Solar/Wind Harmer
14.604
972165AH1-665 GEN
Solar/Wind Harmer
11.684
339243AC2-075 GEN1
Solar/Wind Harmer
0.653
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
2.249
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
4.288
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
2.129
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
8.379
965401AG1-405 GEN
Solar/Wind Harmer
7.914
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270291AC1-194 GEN
Solar/Wind Harmer
14.929
253415AE1-040 GEN
Solar/Wind Harmer
1.582
972173AH1-669 GEN
Solar/Wind Harmer
6.941
270222AC2-111 GEN
Solar/Wind Harmer
11.283
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
3.68
270356AE2-297 GEN
Solar/Wind Harmer
6.29
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
20.501
270437AC2-090 C
Solar/Wind Harmer
7.623
253303V4-073 C
Solar/Wind Harmer
0.158
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
12.267
970273AG2-179 GEN
Solar/Wind Harmer
5.305
960741AF2-365 GEN
Solar/Wind Harmer
6.78
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
18.947
270004AE1-209 GEN
Solar/Wind Harmer
7.396
274772LINCOLN ;3U
Adder
11.055
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.078
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.804
970947AG2-589 GEN
Solar/Wind Harmer
3.539
960001AF2-291 GEN
Solar/Wind Harmer
5.242
971403AH1-188 GEN
Solar/Wind Harmer
24.059
962761AG1-125 GEN
Solar/Wind Harmer
54.777
970149AG2-104 GEN
Solar/Wind Harmer
67.649
970155AG2-107 GEN
Solar/Wind Harmer
23.885
971315AH1-136 GEN
Solar/Wind Harmer
3.199
927014AC1-188 GEN
Solar/Wind Harmer
2.494
971687AH1-348 GEN
Solar/Wind Harmer
1.529
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
46.803
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
27.516
252507AC2-088 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
2.413
25196008MFTGT1
Adder
1.989
943111AE2-339 GEN
Solar/Wind Harmer
1.263
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0.38
946171AF1-282 GEN
Solar/Wind Harmer
14.195
270263AC1-001 GEN
Solar/Wind Harmer
1.475
270445AC2-157 GEN2
Solar/Wind Harmer
7.855
971565AH1-281 GEN
Solar/Wind Harmer
2.807
971821AH1-427 GEN
Solar/Wind Harmer
14.027
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
339241AF1-083 GEN
Solar/Wind Harmer
2.279
942081AE2-220 GEN
Solar/Wind Harmer
8.729
270239V3-007_GEN1
Solar/Wind Harmer
2.35
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
13.573
963741AG1-226 GEN
Solar/Wind Harmer
61.007
970291AG2-192 GEN
Solar/Wind Harmer
1.76
270005AE1-210 C O1
Solar/Wind Harmer
7.396
965031AG1-367 GEN
Solar/Wind Harmer
13.534
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
20.265
960071AF2-298 GEN
Solar/Wind Harmer
6.737
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
274745AC1-111 GEN9
Adder
7.316
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
970825AG2-519 GEN
Solar/Wind Harmer
1.889
944031AF1-071 GEN
Solar/Wind Harmer
1.391
270269AC2-059
Solar/Wind Harmer
12.868
971061AG2-657 GEN
Solar/Wind Harmer
12.35
270240V3-007_GEN2
Solar/Wind Harmer
8.448
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
5.403
24699105WLD G1 C
Solar/Wind Harmer
5.339
253349AC2-067 GEN
Solar/Wind Harmer
6.756
253400AC2-068 GEN
Solar/Wind Harmer
2.717
965461AG1-414 GEN
Solar/Wind Harmer
3.069
970289AG2-191 GEN
Solar/Wind Harmer
2.572
270594AE1-207 GEN
Solar/Wind Harmer
19.886
963841AG1-237 GEN
Solar/Wind Harmer
14.783
24729505KEY G4
Adder
8.586
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.186
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:11.83
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:15.51
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24289405MTG1
50/50
12.693
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
24289405MTG1
50/50
12.693
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
24318705GVG2
50/50
13.293
970153AG2-106 GEN
Solar/Wind Harmer
40.072
24686205CER G4
Adder
16.091
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
971461AH1-227 GEN
Solar/Wind Harmer
7.917
971191AH1-055 GEN
Solar/Wind Harmer
33.8
270346AE1-212 GEN
Solar/Wind Harmer
13.484
943031AE2-326 GEN
Solar/Wind Harmer
5.284
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970243AG2-164 GEN
Solar/Wind Harmer
30.166
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
972273AH1-721 GEN
Adder
96.475
270030AE2-140 GEN
Solar/Wind Harmer
23.108
970273AG2-179 GEN
Solar/Wind Harmer
4.447
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
339250AF1-203 GEN
Solar/Wind Harmer
0.677
971155AH1-034 GEN
Solar/Wind Harmer
11.167
962251AG1-071 GEN
Solar/Wind Harmer
6.119
960741AF2-365 GEN
Solar/Wind Harmer
5.543
3429391JKCT 9G
Adder
9.194
972167AH1-666 GEN
Solar/Wind Harmer
8.642
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
25196008MFTGT1
Adder
1.363
970193AG2-126 GEN
Solar/Wind Harmer
14.82
252510AF1-249 C
Solar/Wind Harmer
0.411
270173AC1-122 GEN
Solar/Wind Harmer
1.562
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.312
942481AE2-261 GEN
Solar/Wind Harmer
28.829
24728705AND G3
Adder
7.718
24728505AND G1
Adder
3.69
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274760LEE CO EC;1U
Adder
8.426
274767LEE CO EC;8U
Adder
8.327
972236AH1-702 GEN2
Adder
1.974
274682WAUKEGAN ;7U
Adder
15.992
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
235058AG1-386 C
Solar/Wind Helper
0.421
237043AE2-125 C
Solar/Wind Helper
0.164
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089126CSLMN_L13
Solar/Wind Helper
0.533
20089026BF_G21_K23
Solar/Wind Helper
0.422
964991AG1-363 GEN
Solar/Wind Helper
3.317
24721605FLATG1
50/50
3.32
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
971313AH1-133 GEN
Solar/Wind Harmer
15.802
970281AG2-184 GEN
Solar/Wind Harmer
32.56
972143AH1-644 GEN
Solar/Wind Harmer
15.505
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
24734705WLF1G3
Adder
8.349
24734805WLF1G4
Adder
8.349
24734905WLF1G5
Adder
8.349
962211AG1-066 GEN
Solar/Wind Harmer
3.499
966391AG1-508 GEN
Solar/Wind Harmer
4.988
24735105WLF2G1
Adder
8.16
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
965411AG1-406 GEN
Solar/Wind Harmer
2.95
339211AE2-254 GEN
Solar/Wind Harmer
1.711
970879AG2-548 GEN
Solar/Wind Harmer
4.825
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
972165AH1-665 GEN
Solar/Wind Harmer
8.697
270367AC2-061_GEN
Solar/Wind Harmer
3.448
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
944221AF1-090 GEN
Solar/Wind Harmer
10.676
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
24728205BUCHG1
Adder
7.204
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
971277AH1-098 GEN
Solar/Wind Harmer
5.729
270583AD2-179 GEN
Solar/Wind Harmer
13.373
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971485AH1-239 GEN
Solar/Wind Harmer
9.113
970879AG2-548 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
339236AF1-050_GEN
Solar/Wind Harmer
2.029
339255AE2-071 GEN
Solar/Wind Harmer
1.185
964781AG1-341 GEN
Solar/Wind Harmer
11.836
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972043AH1-570 GEN
Solar/Wind Harmer
2.743
972045AH1-571 GEN
Solar/Wind Harmer
2.195
971125AH1-004 GEN
Solar/Wind Harmer
4.377
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
339221AD2-048_GEN
Solar/Wind Harmer
1.68
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
252509AD1-136 GEN
Solar/Wind Harmer
0.262
945391AF1-204 GEN
Solar/Wind Harmer
13.769
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
25183208HLCRTG
Solar/Wind Harmer
5.931
25194408D.CRK1
Adder
7.379
25194508D.CRK3
Adder
1.38
276916AD2-100_GEN
Solar/Wind Harmer
20.308
276911AD2-131_GEN
Solar/Wind Harmer
4.104
957381AF2-032 GEN
Solar/Wind Harmer
0.403
970241AG2-163 GEN
Solar/Wind Harmer
23.985
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
24728805RICHG1
Adder
3.448
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274765LEE CO EC;6U
Adder
8.446
274762LEE CO EC;3U
Adder
8.426
274763LEE CO EC;4U
Adder
8.346
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274696ROCKY RD ;4P
Adder
10.143
274695ROCKY RD ;2P
Adder
9.908
274693ROCKY RD ;1P
Adder
9.811
274697ROCKY RD ;3P
Adder
2.692
23652301WDPWR_K20
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.594
241967AE2-285_GEN
Solar/Wind Helper
0.583
241801AE1-079 GEN
Solar/Wind Helper
0.227
241985AE1-237 GEN
Solar/Wind Helper
0.227
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
944781AF1-143 GEN
Solar/Wind Helper
2.213
243186AF1-051 GEN
50/50
14.281
24318705GVG2
50/50
13.293
962761AG1-125 GEN
Solar/Wind Harmer
91.898
970149AG2-104 GEN
Solar/Wind Harmer
113.494
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
24686505CER G6
Adder
16.155
971403AH1-188 GEN
Solar/Wind Harmer
25.361
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
970947AG2-589 GEN
Solar/Wind Harmer
3.533
960001AF2-291 GEN
Solar/Wind Harmer
5.186
24728305BUCHG2
Adder
7.204
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
24735205WLF2G2
Adder
8.16
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
270336AE1-100 GEN
Solar/Wind Harmer
2.043
970091AG2-072 GEN
Adder
90.557
970333AG2-219 GEN
Solar/Wind Harmer
36.87
971367AH1-164 GEN
Solar/Wind Harmer
3.994
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
943111AE2-339 GEN
Solar/Wind Harmer
0.969
339216AC1-074 GEN
Solar/Wind Harmer
1.819
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
25194608D.CRK4
Adder
1.604
965911AG1-460 GEN
Solar/Wind Harmer
1.345
24728605AND G2
Adder
3.69
963741AG1-226 GEN
Solar/Wind Harmer
43.173
276615X2-022 GEN
Solar/Wind Harmer
1.868
274761LEE CO EC;2U
Adder
8.426
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
274822ROCKFORD ;11
Adder
17.664
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
20089226LOOKOUT
Solar/Wind Helper
0.519
963831AG1-236 GEN
Solar/Wind Harmer
2.691
274823ROCKFORD ;21
Adder
17.536
274746AC1-111 G10
Adder
4.954
274744AC1-111 GEN8
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241997AF1-093 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.203
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6192.17
MW Contribution:15.79
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.412
24318705GVG2
50/50
11.681
24722005FLATG5
50/50
2.772
24721905FLATG4
50/50
50.82
24686205CER G4
Adder
15.663
24686405CER G5
Adder
15.601
270053AF1-130 C
Solar/Wind Harmer
6.517
970153AG2-106 GEN
Solar/Wind Harmer
24.083
971191AH1-055 GEN
Solar/Wind Harmer
37.171
957541AF2-048 GEN
Solar/Wind Harmer
2.51
970913AG2-568 GEN
Solar/Wind Harmer
12.681
972103AH1-617 GEN
Solar/Wind Harmer
31.576
960911AF2-382 GEN
Solar/Wind Harmer
11.622
971461AH1-227 GEN
Solar/Wind Harmer
7.904
970243AG2-164 GEN
Solar/Wind Harmer
38.654
970519AG2-331 GEN
Solar/Wind Harmer
25.969
970699AG2-449 GEN
Solar/Wind Harmer
17.18
972167AH1-666 GEN
Solar/Wind Harmer
11.786
958171AF2-111 GEN
Solar/Wind Harmer
36.367
252510AF1-249 C
Solar/Wind Harmer
0.604
25196008MFTGT1
Adder
1.945
25194608D.CRK4
Adder
2.371
25196608WSDLE5
Adder
12.34
3429391JKCT 9G
Adder
11.981
970093AG2-073 GEN
Solar/Wind Harmer
14.372
253316AC1-085 GEN3
Solar/Wind Harmer
12.008
253433AC1-085 GEN1
Solar/Wind Harmer
7.622
946181AF1-283 GEN
Solar/Wind Harmer
18.636
253406AD2-031_GEN
Solar/Wind Harmer
1.826
966571AG1-526 GEN
Solar/Wind Harmer
31.649
270291AC1-194 GEN
Solar/Wind Harmer
15.077
253415AE1-040 GEN
Solar/Wind Harmer
1.598
972173AH1-669 GEN
Solar/Wind Harmer
7.011
270222AC2-111 GEN
Solar/Wind Harmer
11.397
270273AD2-016 GEN
Solar/Wind Harmer
3.717
972273AH1-721 GEN
Adder
115.895
270356AE2-297 GEN
Solar/Wind Harmer
6.354
24728705AND G3
Adder
11.134
24728505AND G1
Adder
5.324
970193AG2-126 GEN
Solar/Wind Harmer
20.711
243186AF1-051 GEN
50/50
12.549
24723005RIVRG1
Adder
36.284
24723105RIVRG2
Adder
36.284
24685805CER G1
Adder
15.642
24685905CER G2
Adder
15.642
944971AF1-162 GEN
Solar/Wind Harmer
12.272
971225AH1-072 GEN
Solar/Wind Harmer
3.081
971227AH1-073 GEN
Solar/Wind Harmer
3.081
24728205BUCHG1
Adder
6.894
970239AG2-162 GEN
Solar/Wind Harmer
16.464
270186AC1-089 GEN
Solar/Wind Harmer
9.145
962581AG1-107 GEN
Solar/Wind Harmer
7.495
961491AF2-440 GEN
Solar/Wind Harmer
3.115
960161AF2-307 GEN
Solar/Wind Harmer
9.531
970879AG2-548 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
6.355
252509AD1-136 GEN
Solar/Wind Harmer
0.375
339221AD2-048_GEN
Solar/Wind Harmer
2.24
972043AH1-570 GEN
Solar/Wind Harmer
3.637
972045AH1-571 GEN
Solar/Wind Harmer
2.91
25183208HLCRTG
Solar/Wind Harmer
8.794
252519AF1-045_GEN
Solar/Wind Harmer
8.799
252516AE2-318_GEN
Solar/Wind Harmer
6.712
970235AG2-159 GEN
Solar/Wind Harmer
5.797
970235AG2-159 GEN
Solar/Wind Harmer
3.539
971125AH1-004 GEN
Solar/Wind Harmer
5.778
970107AG2-081 GEN
Solar/Wind Harmer
4.333
25194408D.CRK1
Adder
10.905
25194508D.CRK3
Adder
2.039
942891AE2-308 GEN
Solar/Wind Harmer
14.408
253317AC1-085 GEN4
Solar/Wind Harmer
12.008
270444AC2-157 GEN1
Solar/Wind Harmer
7.934
253394AE2-221_GEN
Solar/Wind Harmer
6.433
253398AE2-221_GEN2
Solar/Wind Harmer
6.433
964571AG1-320 GEN
Solar/Wind Harmer
11.509
970653AG2-424 GEN
Solar/Wind Harmer
6.739
970653AG2-424 GEN
Solar/Wind Harmer
2.436
24289405MTG1
50/50
11.412
243186AF1-051 GEN
50/50
12.549
24318705GVG2
50/50
11.681
24721805FLATG3
50/50
2.772
24721705FLATG2
50/50
50.82
24723205RIVRG3
Adder
36.284
24686105CER G3
Adder
15.746
24686505CER G6
Adder
15.725
270331AC1-082 GEN3
Solar/Wind Harmer
0.811
970947AG2-589 GEN
Solar/Wind Harmer
3.567
960001AF2-291 GEN
Solar/Wind Harmer
5.284
971403AH1-188 GEN
Solar/Wind Harmer
24.255
962761AG1-125 GEN
Solar/Wind Harmer
55.23
970149AG2-104 GEN
Solar/Wind Harmer
68.21
970155AG2-107 GEN
Solar/Wind Harmer
24.083
971315AH1-136 GEN
Solar/Wind Harmer
3.227
927014AC1-188 GEN
Solar/Wind Harmer
2.517
971687AH1-348 GEN
Solar/Wind Harmer
1.543
24728305BUCHG2
Adder
6.894
970333AG2-219 GEN
Solar/Wind Harmer
47.244
970091AG2-072 GEN
Adder
114.655
945681AF1-233 GEN
Solar/Wind Harmer
27.78
252507AC2-088 GEN
Solar/Wind Harmer
2.628
25196808ZIMRHP
Adder
110.178
339216AC1-074 GEN
Solar/Wind Harmer
2.436
25196008MFTGT1
Adder
2.009
943111AE2-339 GEN
Solar/Wind Harmer
1.275
25194608D.CRK4
Adder
2.371
3429241JKCT 3G
Adder
17.06
3429421JKCT 10G
Adder
11.981
253432AC1-085 GEN2
Solar/Wind Harmer
0.384
946171AF1-282 GEN
Solar/Wind Harmer
14.335
270263AC1-001 GEN
Solar/Wind Harmer
1.49
270445AC2-157 GEN2
Solar/Wind Harmer
7.934
971565AH1-281 GEN
Solar/Wind Harmer
2.835
971821AH1-427 GEN
Solar/Wind Harmer
14.167
24735205WLF2G2
Adder
8.161
24728605AND G2
Adder
5.324
339241AF1-083 GEN
Solar/Wind Harmer
2.303
942081AE2-220 GEN
Solar/Wind Harmer
8.819
270239V3-007_GEN1
Solar/Wind Harmer
2.374
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
970273AG2-179 GEN
Solar/Wind Harmer
3.356
276903AD2-071 C
Solar/Wind Harmer
13.713
963741AG1-226 GEN
Solar/Wind Harmer
61.637
970291AG2-192 GEN
Solar/Wind Harmer
1.778
270005AE1-210 C O1
Solar/Wind Harmer
7.473
965031AG1-367 GEN
Solar/Wind Harmer
13.674
24721605FLATG1
50/50
2.772
972203AH1-686 GEN
Adder
4.457
270330AC1-082 GEN2
Solar/Wind Harmer
1.373
270329AC1-082 GEN1
Solar/Wind Harmer
0.808
957241AF2-018 GEN
Solar/Wind Harmer
7.79
270399AC1-101 GEN
Solar/Wind Harmer
7.37
270400AC1-102 GEN
Solar/Wind Harmer
7.37
962771AG1-126 GEN
Solar/Wind Harmer
55.23
24477305BRIDGE
Adder
0.593
970281AG2-184 GEN
Solar/Wind Harmer
33.155
972143AH1-644 GEN
Solar/Wind Harmer
15.788
971985AH1-537 GEN
Solar/Wind Harmer
28.159
941621AE2-160 GEN
Adder
5.103
962211AG1-066 GEN
Solar/Wind Harmer
3.699
971313AH1-133 GEN
Solar/Wind Harmer
15.015
270367AC2-061_GEN
Solar/Wind Harmer
4.764
970879AG2-548 GEN
Solar/Wind Harmer
6.355
972163AH1-664 GEN
Solar/Wind Harmer
14.744
972165AH1-665 GEN
Solar/Wind Harmer
11.796
339243AC2-075 GEN1
Solar/Wind Harmer
0.66
25196108MFTGT2
Adder
2.214
25196108MFTGT2
Adder
2.056
3429211JKCT 2G
Adder
16.839
252524AE2-267 GEN
Solar/Wind Harmer
2.271
25196408WSDLE3
Adder
12.703
25196308WSDLE2
Adder
12.592
25196208WSDLE1
Adder
12.561
25196708WSDLE6
Adder
12.529
25196508WSDLE4
Adder
12.214
24734705WLF1G3
Adder
8.278
24734805WLF1G4
Adder
8.278
24734905WLF1G5
Adder
8.278
270340AC2-060 GEN
Solar/Wind Harmer
4.33
270132AB1-180 C
Adder
0.172
339211AE2-254 GEN
Solar/Wind Harmer
2.15
24735105WLF2G1
Adder
8.161
970455AG2-298 GEN
Solar/Wind Harmer
8.463
965401AG1-405 GEN
Solar/Wind Harmer
7.994
965411AG1-406 GEN
Solar/Wind Harmer
3.588
944031AF1-071 GEN
Solar/Wind Harmer
1.405
270269AC2-059
Solar/Wind Harmer
12.998
971061AG2-657 GEN
Solar/Wind Harmer
12.476
270240V3-007_GEN2
Solar/Wind Harmer
8.534
253372AE2-315 SEC3
Adder
2.611
253372AE2-315 SEC3
Adder
2.611
25306009OHH W.
Adder
3.967
24725505WLD G2 C
Solar/Wind Harmer
5.459
24699105WLD G1 C
Solar/Wind Harmer
5.394
253349AC2-067 GEN
Solar/Wind Harmer
6.826
253400AC2-068 GEN
Solar/Wind Harmer
2.745
965461AG1-414 GEN
Solar/Wind Harmer
3.101
970289AG2-191 GEN
Solar/Wind Harmer
2.598
270594AE1-207 GEN
Solar/Wind Harmer
20.092
963841AG1-237 GEN
Solar/Wind Harmer
14.936
24729505KEY G4
Adder
8.677
274775LINCOLN ;6U
Adder
11.173
274776LINCOLN ;7U
Adder
11.173
274777LINCOLN ;8U
Adder
11.173
274746AC1-111 G10
Adder
7.394
274744AC1-111 GEN8
Adder
7.394
274731ELWOOD EC;2P
Adder
21.74
274733ELWOOD EC;3P
Adder
13.586
23750501ELLIOTTS
Solar/Wind Helper
0.779
238126S14_GEN_1
Solar/Wind Helper
0.8
254304AE2-114 C
Solar/Wind Helper
0.235
241997AF1-093 GEN
Solar/Wind Helper
0.277
241982AE2-343 S C
Solar/Wind Helper
0.24
20092526R32
Solar/Wind Helper
1.294
203961AE2-224 GEN
Solar/Wind Helper
2.672
20091526CHSTN_FL
Solar/Wind Helper
0.646
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
20090526Q36
Solar/Wind Helper
1.152
203993AD2-133_GEN1
Solar/Wind Helper
1.152
941231AE2-117 GEN
Solar/Wind Helper
0.523
203846AF2-130 C
Solar/Wind Helper
0.491
203855AF2-088 C
Solar/Wind Helper
0.168
203804AE2-113_GEN
Solar/Wind Helper
1.898
959431AF2-234 GEN
Solar/Wind Helper
0.986
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.493
961261AF2-417 GEN
Solar/Wind Helper
0.488
209116AE2-175 GEN
Solar/Wind Helper
1.938
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.09
20675728RH_W2-091
Solar/Wind Helper
0.147
207484AF2-139 C O1
Solar/Wind Helper
0.09
203975AE1-071-GEN
Solar/Wind Helper
2.635
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.054
238208AF1-136 C
Solar/Wind Helper
0.189
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.071
966261AG1-495 GEN
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.17
218526CNTRALGAS2 C
Solar/Wind Helper
0.17
20675528CPH_W2-050
Solar/Wind Helper
0.092
219620RIDERU C
Solar/Wind Helper
0.001
270437AC2-090 C
Solar/Wind Harmer
7.702
253303V4-073 C
Solar/Wind Harmer
0.16
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
270346AE1-212 GEN
Solar/Wind Harmer
12.393
970273AG2-179 GEN
Solar/Wind Harmer
5.36
960741AF2-365 GEN
Solar/Wind Harmer
6.85
247642Z2-115 C
Solar/Wind Harmer
0.088
970289AG2-191 GEN
Solar/Wind Harmer
1.05
970291AG2-192 GEN
Solar/Wind Harmer
0.954
958821AF2-173 GEN
Solar/Wind Harmer
19.143
270004AE1-209 GEN
Solar/Wind Harmer
7.473
274772LINCOLN ;3U
Adder
11.173
274760LEE CO EC;1U
Adder
12.305
274767LEE CO EC;8U
Adder
12.16
274729ELWOOD EC;1P
Adder
21.74
237048AF1-022 C
Solar/Wind Helper
0.225
237043AE2-125 C
Solar/Wind Helper
0.205
235058AG1-386 C
Solar/Wind Helper
0.508
964991AG1-363 GEN
Solar/Wind Helper
4.361
23750701CROSSCHOOL
Solar/Wind Helper
1.41
238118U2-030_1
Solar/Wind Helper
0.339
202652Y1-033 WT C
Solar/Wind Helper
0.647
20089126CSLMN_L13
Solar/Wind Helper
0.675
20089026BF_G21_K23
Solar/Wind Helper
0.534
238127S14_GEN_2
Solar/Wind Helper
0.8
254305AE2-115 C
Solar/Wind Helper
0.235
203818AF1-086 GEN
Solar/Wind Helper
1.862
203854AF2-039 C
Solar/Wind Helper
0.349
20334926Z1-069 C
Solar/Wind Helper
1.47
238202AE2-262_GEN
Solar/Wind Helper
1.048
941421AE2-139 GEN
Solar/Wind Helper
2.537
959441AF2-235 GEN
Solar/Wind Helper
0.252
200917MEHOOPANY_G
Solar/Wind Helper
2.394
209071AE2-133 GEN
Solar/Wind Helper
0.089
946731AF1-337 GEN
Solar/Wind Helper
0.493
212507AE2-042_GEN
Solar/Wind Helper
1.746
961341AF2-425 GEN
Solar/Wind Helper
0.491
212266LOR1
Solar/Wind Helper
0.053
961301AF2-421 GEN
Solar/Wind Helper
0.489
963151AG1-164 GEN
Solar/Wind Helper
0.489
316097T157 G90
Solar/Wind Helper
1.137
203830AF1-094 GEN
Solar/Wind Helper
0.488
20671928W4-073
Solar/Wind Helper
0.097
207518AF1-320_GEN
Solar/Wind Helper
1.692
207437AD2-070 GEN
Solar/Wind Helper
0.148
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.072
207528AF2-192 GEN
Solar/Wind Helper
0.081
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.481
217213AMBOY SO C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.524
20742028HF_AC1-207
Solar/Wind Helper
0.148
20715228NPK_W1-113
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.327
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.067
20714828MDF_W3-079
Solar/Wind Helper
0.137
207445AB1-138_GEN
Solar/Wind Helper
0.109
20720728JCB_W1-129
Solar/Wind Helper
0.06
219304NAMERICA C
Solar/Wind Helper
0.137
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219904AC1-010 C
Solar/Wind Helper
0.063
219258KINSLEYDEP C
Solar/Wind Helper
0.079
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.308
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
232434Z2-077 GEN
Solar/Wind Helper
0.129
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.116
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.51
966131AG1-482 GEN
Solar/Wind Helper
0.077
235062AE1-101 C1
Solar/Wind Helper
1.441
237038AE2-054 C
Solar/Wind Helper
0.234
237080AD1-060 GEN
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.165
223401AF1-299 GEN
Solar/Wind Helper
0.332
270032AE2-172
Solar/Wind Harmer
6.358
25326309TAIT D
Adder
1.497
964901AG1-354 GEN
Solar/Wind Harmer
20.475
960071AF2-298 GEN
Solar/Wind Harmer
6.807
274773LINCOLN ;4U
Adder
11.173
274774LINCOLN ;5U
Adder
11.173
274745AC1-111 GEN9
Adder
7.394
274761LEE CO EC;2U
Adder
12.305
274766LEE CO EC;7U
Adder
12.16
237046AF1-021 C
Solar/Wind Helper
0.57
238185AF2-356 C
Solar/Wind Helper
2.581
23751201ROTHROCK
Solar/Wind Helper
0.868
235054AD2-180 GEN
Solar/Wind Helper
2.007
23562501BACKB
Solar/Wind Helper
1.057
238117U2-030
Solar/Wind Helper
0.339
235531U2-073 GEN
Solar/Wind Helper
3.19
20089226LOOKOUT
Solar/Wind Helper
0.657
254303AC2-168 GEN
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.277
23751101LEADS_P59
Solar/Wind Helper
1.464
20088826HIGHLAND
Solar/Wind Helper
0.998
20094526CT_V3-030
Solar/Wind Helper
0.523
964201AG1-281 GEN
Solar/Wind Helper
0.537
238108AE1-109 GEN1
Solar/Wind Helper
0.101
964391AG1-301 GEN
Solar/Wind Helper
0.522
203954AE2-126 C
Solar/Wind Helper
0.514
238206AE2-263_GEN
Solar/Wind Helper
0.997
959471AF2-238 GEN
Solar/Wind Helper
0.51
203860AG1-193 C
Solar/Wind Helper
0.25
209067AE2-060 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.493
946741AF1-338 GEN
Solar/Wind Helper
0.493
961421AF2-433 GEN
Solar/Wind Helper
0.491
957921AF2-086 GEN
Solar/Wind Helper
0.486
961331AF2-424 GEN
Solar/Wind Helper
0.491
209027LOR2_Q27
Solar/Wind Helper
1.148
963071AG1-156 GEN
Solar/Wind Helper
1.601
963161AG1-165 GEN
Solar/Wind Helper
0.489
316095T157 G97
Solar/Wind Helper
1.137
23583801GRNGAP
Solar/Wind Helper
4.22
961971AG1-040 GEN
Solar/Wind Helper
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.929
20674628WNG_W3-110
Solar/Wind Helper
0.096
207510AF2-138 C
Solar/Wind Helper
0.087
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.078
219919AE1-041 FULL
Solar/Wind Helper
0.004
219612MATRIX C
Solar/Wind Helper
0.025
218438BLK ROCK C
Solar/Wind Helper
0.029
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.094
20720828JCB_W4-025
Solar/Wind Helper
0.066
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.06
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.119
219906AC1-017 C
Solar/Wind Helper
0.043
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.155
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.114
230415AB2-049 C
Solar/Wind Helper
0.031
230430AE1-229_GEN
Solar/Wind Helper
3.487
233971AC1-093 C
Solar/Wind Helper
0.364
233952AC2-187 GEN
Solar/Wind Helper
0.236
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233982AB2-133 GEN
Solar/Wind Helper
0.363
233918AB1-142 GEN
Solar/Wind Helper
0.51
235067AD1-061 GEN
Solar/Wind Helper
0.427
205917AD1-020 ES
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.232
237030AB1-096 C
Solar/Wind Helper
0.062
223402AF1-300 C
Solar/Wind Helper
0.332
970825AG2-519 GEN
Solar/Wind Harmer
1.909
24728805RICHG1
Adder
5.257
24728905RICHG2
Adder
5.257
971081AG2-670 GEN
Solar/Wind Harmer
10.358
945391AF1-204 GEN
Solar/Wind Harmer
19.242
24379505HDWTR1G C
Solar/Wind Harmer
10.908
270209AC1-174_GEN
Solar/Wind Harmer
7.698
926881AC1-175 GEN
Solar/Wind Harmer
7.698
253370AE2-315 SEC1
Adder
2.761
339231AF1-038_GEN
Solar/Wind Harmer
2.495
270383AD1-128 GEN
Solar/Wind Harmer
8.387
339236AF1-050_GEN
Solar/Wind Harmer
2.488
970241AG2-163 GEN
Solar/Wind Harmer
34.243
25322209TAIT E
Adder
13.324
25322209TAIT E
Adder
13.025
25326109MON D
Adder
1.782
247621Y3-024
Adder
0.324
274770LINCOLN ;1U
Adder
11.173
274771LINCOLN ;2U
Adder
11.173
972259AH1-714 GEN
Adder
25.243
972267AH1-718 GEN
Adder
5.508
274696ROCKY RD ;4P
Adder
15.074
274695ROCKY RD ;2P
Adder
14.726
274693ROCKY RD ;1P
Adder
14.581
274697ROCKY RD ;3P
Adder
4
274764LEE CO EC;5U
Adder
12.334
274765LEE CO EC;6U
Adder
12.334
274762LEE CO EC;3U
Adder
12.305
274763LEE CO EC;4U
Adder
12.189
23652301WDPWR_K20
Solar/Wind Helper
0.166
23585401KL_K28_T16
Solar/Wind Helper
1.512
203955AF1-039 C O1
Solar/Wind Helper
0.427
944781AF1-143 GEN
Solar/Wind Helper
2.801
238120AE2-309 GEN
Solar/Wind Helper
0.501
962101AG1-054 GEN
Solar/Wind Helper
0.706
20083426SW_E13_K22
Solar/Wind Helper
0.063
241985AE1-237 GEN
Solar/Wind Helper
0.267
241967AE2-285_GEN
Solar/Wind Helper
0.687
241801AE1-079 GEN
Solar/Wind Helper
0.267
20088926STNY CRK
Solar/Wind Helper
0.916
946071AF1-272 GEN
Solar/Wind Helper
3.012
20084626FORWARD
Solar/Wind Helper
0.397
203940AF1-140 C
Solar/Wind Helper
0.44
20088626ARWF_N39
Solar/Wind Helper
1.344
20303426NA_O38_P22
Solar/Wind Helper
1.102
203853AF1-134 C O1
Solar/Wind Helper
0.526
946381AF1-302 GEN
Solar/Wind Helper
0.243
203952AE2-129 C
Solar/Wind Helper
0.521
203946AE2-131 C
Solar/Wind Helper
0.522
238217AF1-153 C O1
Solar/Wind Helper
0.259
20398826ARMNA MT
Solar/Wind Helper
1.633
209137AF2-361 C
Solar/Wind Helper
1.509
946751AF1-339 GEN
Solar/Wind Helper
0.493
209054AE2-059 GEN
Solar/Wind Helper
0.089
961431AF2-434 GEN
Solar/Wind Helper
0.491
208972BECR K09
Solar/Wind Helper
0.367
209029WAYMART-WD
Solar/Wind Helper
0.923
203979AG1-198 GEN
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.165
211065PSPA IPP
Solar/Wind Helper
0.165
203980AG1-197 GEN
Solar/Wind Helper
0.363
966111AG1-480 GEN
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.087
20676228FRD_X1-012
Solar/Wind Helper
0.099
207471AF2-354 C
Solar/Wind Helper
0.181
20674928WA_W3-044
Solar/Wind Helper
0.106
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.028
207442AE1-156 GEN
Solar/Wind Helper
0.346
20676128MHD_W3-029
Solar/Wind Helper
0.102
20673828FLE_V3-070
Solar/Wind Helper
0.096
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20716928W4-060COL
Solar/Wind Helper
0.054
20720628TIN_W1-124
Solar/Wind Helper
0.2
20714928UPF_X1-085
Solar/Wind Helper
0.005
963391AG1-188 GEN
Solar/Wind Helper
0.086
963401AG1-189 GEN
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.351
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.053
203947AF1-006 C
Solar/Wind Helper
0.519
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.379
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233933AB2-153 GEN
Solar/Wind Helper
0.236
235063AE1-101 C2
Solar/Wind Helper
1.441
205916AD1-020 GEN
Solar/Wind Helper
1.685
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.382
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.191
238175AF1-290_GEN
Solar/Wind Helper
0.121
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.098
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
970825AG2-519 GEN
Solar/Wind Harmer
8.555
207459AE1-142 C O1
Solar/Wind Helper
0.304
20715728PEM_W1-119
Solar/Wind Helper
0.1
20715828PEM_W1-120
Solar/Wind Helper
0.1
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.359
219607WPEMNERT C
Solar/Wind Helper
0.083
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.119
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
0.988
234033AF1-007_GEN
Solar/Wind Helper
7.137
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
237085AD2-009_GEN
Solar/Wind Helper
1.427
205932AD2-116_GEN
Solar/Wind Helper
0.516
205956AE1-196_GEN
Solar/Wind Helper
0.516
205943AE1-185 GEN
Solar/Wind Helper
0.515
232436AB1-176 C
Solar/Wind Helper
0.045
233935AB2-179 C
Solar/Wind Helper
1.288
960921AF2-383 GEN
Solar/Wind Helper
0.183
944201AF1-088_MTX
Adder
165.192
957141AF2-008_MTX
Adder
82.596
CPLELTFEXP_CPLE->PJM
CLTF
6.71
CBM West 2LTFEXP_CBM-W2->PJM
CBM
175.047
LAGNLTFEXP_LAGN->PJM
CLTF
25.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.665
TVALTFEXP_TVA->PJM
CLTF
12.772
NYPJM->LTFIMP_NY
CLTF
6.186
LGEELTFEXP_LGEE->PJM
CLTF
9.94
WECLTFEXP_WEC->PJM
CLTF
5.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.309
AH1-155LTFEXP_AH1-155->PJM
LTF
0.464
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
49.115
MECLTFEXP_MEC->PJM
CLTF
22.175
SIGELTFEXP_SIGE->PJM
CLTF
0.736

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:10.39
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:16.64
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
8.54
972103AH1-617 GEN
Solar/Wind Harmer
33.271
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
36.143
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
26.875
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
966571AG1-526 GEN
Solar/Wind Harmer
29.484
270173AC1-122 GEN
Solar/Wind Harmer
2.108
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.144
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
339250AF1-203 GEN
Solar/Wind Harmer
0.784
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
962251AG1-071 GEN
Solar/Wind Harmer
7.087
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
253415AE1-040 GEN
Solar/Wind Harmer
1.318
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
972236AH1-702 GEN2
Adder
2.406
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
26.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
970947AG2-589 GEN
Solar/Wind Harmer
3.612
960001AF2-291 GEN
Solar/Wind Harmer
5.329
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971329AH1-144 GEN
Solar/Wind Harmer
19.813
971315AH1-136 GEN
Solar/Wind Harmer
3.299
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
971277AH1-098 GEN
Solar/Wind Harmer
6.642
270583AD2-179 GEN
Solar/Wind Harmer
16.345
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
942891AE2-308 GEN
Solar/Wind Harmer
13.304
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972043AH1-570 GEN
Solar/Wind Harmer
3.299
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
971125AH1-004 GEN
Solar/Wind Harmer
5.257
970107AG2-081 GEN
Solar/Wind Harmer
3.942
971485AH1-239 GEN
Solar/Wind Harmer
10.499
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
971081AG2-670 GEN
Solar/Wind Harmer
9.778
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964781AG1-341 GEN
Solar/Wind Harmer
13.698
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
945391AF1-204 GEN
Solar/Wind Harmer
16.499
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
24.323
276911AD2-131_GEN
Solar/Wind Harmer
4.916
253370AE2-315 SEC1
Adder
2.238
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
2.379
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
41.959
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
13.272
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
24.878
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339216AC1-074 GEN
Solar/Wind Harmer
2.198
339241AF1-083 GEN
Solar/Wind Harmer
2.171
971565AH1-281 GEN
Solar/Wind Harmer
2.604
964901AG1-354 GEN
Solar/Wind Harmer
19.445
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
270263AC1-001 GEN
Solar/Wind Harmer
1.245
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
38.198
970149AG2-104 GEN
Solar/Wind Harmer
47.174
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
963741AG1-226 GEN
Solar/Wind Harmer
22.669
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
971313AH1-133 GEN
Solar/Wind Harmer
17.224
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
5.763
970281AG2-184 GEN
Solar/Wind Harmer
34.934
972143AH1-644 GEN
Solar/Wind Harmer
16.635
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
962211AG1-066 GEN
Solar/Wind Harmer
3.823
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
14.056
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965401AG1-405 GEN
Solar/Wind Harmer
7.637
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972163AH1-664 GEN
Solar/Wind Harmer
13.228
972165AH1-665 GEN
Solar/Wind Harmer
10.582
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
1.95
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
962771AG1-126 GEN
Solar/Wind Harmer
38.198
944031AF1-071 GEN
Solar/Wind Harmer
1.178
944221AF1-090 GEN
Solar/Wind Harmer
12.754
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
274823ROCKFORD ;21
Adder
21.377
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5914.32
MW Contribution:14.57
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.188
957241AF2-018 GEN
Solar/Wind Harmer
7.355
270330AC1-082 GEN2
Solar/Wind Harmer
1.259
270329AC1-082 GEN1
Solar/Wind Harmer
0.741
270399AC1-101 GEN
Solar/Wind Harmer
6.952
270400AC1-102 GEN
Solar/Wind Harmer
6.952
24477305BRIDGE
Adder
0.568
962771AG1-126 GEN
Solar/Wind Harmer
51.279
941621AE2-160 GEN
Adder
4.884
970281AG2-184 GEN
Solar/Wind Harmer
30.593
972143AH1-644 GEN
Solar/Wind Harmer
14.568
971313AH1-133 GEN
Solar/Wind Harmer
14.325
962211AG1-066 GEN
Solar/Wind Harmer
3.356
270132AB1-180 C
Adder
0.166
24734705WLF1G3
Adder
7.759
24734805WLF1G4
Adder
7.759
24734905WLF1G5
Adder
7.759
971061AG2-657 GEN
Solar/Wind Harmer
12.002
971985AH1-537 GEN
Solar/Wind Harmer
23.775
24735105WLF2G1
Adder
7.624
966391AG1-508 GEN
Solar/Wind Harmer
4.457
971981AH1-535 GEN
Solar/Wind Harmer
12.146
965401AG1-405 GEN
Solar/Wind Harmer
6.855
965411AG1-406 GEN
Solar/Wind Harmer
3.076
339211AE2-254 GEN
Solar/Wind Harmer
1.816
970455AG2-298 GEN
Solar/Wind Harmer
7.163
3429211JKCT 2G
Adder
13.952
270367AC2-061_GEN
Solar/Wind Harmer
3.766
972163AH1-664 GEN
Solar/Wind Harmer
11.816
972165AH1-665 GEN
Solar/Wind Harmer
9.453
339243AC2-075 GEN1
Solar/Wind Harmer
0.537
963841AG1-237 GEN
Solar/Wind Harmer
12.629
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386205FR-12G C
Solar/Wind Harmer
4.941
24386405FR-21G C
Solar/Wind Harmer
4.958
24386605FR-22G C
Solar/Wind Harmer
4.958
24387005FR-3G C
Solar/Wind Harmer
4.561
944221AF1-090 GEN
Solar/Wind Harmer
12.589
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971225AH1-072 GEN
Solar/Wind Harmer
2.872
971227AH1-073 GEN
Solar/Wind Harmer
2.872
970239AG2-162 GEN
Solar/Wind Harmer
14.243
270214AC2-123 GEN
Solar/Wind Harmer
2.998
971277AH1-098 GEN
Solar/Wind Harmer
5.115
960161AF2-307 GEN
Solar/Wind Harmer
7.971
270444AC2-157 GEN1
Solar/Wind Harmer
6.775
942891AE2-308 GEN
Solar/Wind Harmer
11.976
970235AG2-159 GEN
Solar/Wind Harmer
4.77
970235AG2-159 GEN
Solar/Wind Harmer
2.912
964571AG1-320 GEN
Solar/Wind Harmer
9.767
970653AG2-424 GEN
Solar/Wind Harmer
5.74
970653AG2-424 GEN
Solar/Wind Harmer
2.075
339231AF1-038_GEN
Solar/Wind Harmer
2.157
270186AC1-089 GEN
Solar/Wind Harmer
7.264
972043AH1-570 GEN
Solar/Wind Harmer
2.97
972045AH1-571 GEN
Solar/Wind Harmer
2.376
339221AD2-048_GEN
Solar/Wind Harmer
1.825
971081AG2-670 GEN
Solar/Wind Harmer
8.888
270583AD2-179 GEN
Solar/Wind Harmer
11.844
971125AH1-004 GEN
Solar/Wind Harmer
4.737
970107AG2-081 GEN
Solar/Wind Harmer
3.553
966021AG1-471 GEN
Solar/Wind Harmer
6.38
339236AF1-050_GEN
Solar/Wind Harmer
2.142
971485AH1-239 GEN
Solar/Wind Harmer
9.446
24289405MTG1
50/50
11.329
24318705GVG2
50/50
11.512
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
24686205CER G4
Adder
14.71
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
6.152
970153AG2-106 GEN
Solar/Wind Harmer
22.36
970913AG2-568 GEN
Solar/Wind Harmer
12.168
971191AH1-055 GEN
Solar/Wind Harmer
32.44
960911AF2-382 GEN
Solar/Wind Harmer
11.01
972103AH1-617 GEN
Solar/Wind Harmer
29.136
971461AH1-227 GEN
Solar/Wind Harmer
7.367
270346AE1-212 GEN
Solar/Wind Harmer
11.966
957541AF2-048 GEN
Solar/Wind Harmer
2.069
970243AG2-164 GEN
Solar/Wind Harmer
33.441
970519AG2-331 GEN
Solar/Wind Harmer
22.466
970699AG2-449 GEN
Solar/Wind Harmer
14.862
943031AE2-326 GEN
Solar/Wind Harmer
4.718
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
12.017
966571AG1-526 GEN
Solar/Wind Harmer
26.615
970273AG2-179 GEN
Solar/Wind Harmer
4.636
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
5.368
960741AF2-365 GEN
Solar/Wind Harmer
5.892
972167AH1-666 GEN
Solar/Wind Harmer
9.416
339250AF1-203 GEN
Solar/Wind Harmer
0.712
971155AH1-034 GEN
Solar/Wind Harmer
11.743
962251AG1-071 GEN
Solar/Wind Harmer
6.45
970193AG2-126 GEN
Solar/Wind Harmer
17.522
25196008MFTGT1
Adder
1.556
24728705AND G3
Adder
9.226
24728505AND G1
Adder
4.411
970513AG2-328 GEN
Solar/Wind Harmer
20.527
970517AG2-330 GEN
Solar/Wind Harmer
18.618
24289405MTG1
50/50
11.329
243186AF1-051 GEN
50/50
12.367
24318705GVG2
50/50
11.512
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
24686505CER G6
Adder
14.768
971403AH1-188 GEN
Solar/Wind Harmer
23.029
270331AC1-082 GEN3
Solar/Wind Harmer
0.743
970947AG2-589 GEN
Solar/Wind Harmer
3.261
960001AF2-291 GEN
Solar/Wind Harmer
4.797
962761AG1-125 GEN
Solar/Wind Harmer
51.279
970149AG2-104 GEN
Solar/Wind Harmer
63.33
970155AG2-107 GEN
Solar/Wind Harmer
22.36
971315AH1-136 GEN
Solar/Wind Harmer
2.924
24728305BUCHG2
Adder
6.555
971687AH1-348 GEN
Solar/Wind Harmer
1.437
24735205WLF2G2
Adder
7.624
927014AC1-188 GEN
Solar/Wind Harmer
2.074
970333AG2-219 GEN
Solar/Wind Harmer
40.872
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
14.766
270445AC2-157 GEN2
Solar/Wind Harmer
6.775
971821AH1-427 GEN
Solar/Wind Harmer
11.992
971565AH1-281 GEN
Solar/Wind Harmer
2.394
3429241JKCT 3G
Adder
14.135
970273AG2-179 GEN
Solar/Wind Harmer
2.902
339241AF1-083 GEN
Solar/Wind Harmer
1.973
3429421JKCT 10G
Adder
9.882
943111AE2-339 GEN
Solar/Wind Harmer
1.047
339216AC1-074 GEN
Solar/Wind Harmer
1.982
945681AF1-233 GEN
Solar/Wind Harmer
22.212
964901AG1-354 GEN
Solar/Wind Harmer
17.673
962241AG1-070 GEN
Solar/Wind Harmer
5.277
963741AG1-226 GEN
Solar/Wind Harmer
52.124
25196008MFTGT1
Adder
1.607
24385905FR-11G C
Solar/Wind Harmer
9.582
24387305FR-4G C
Solar/Wind Harmer
5.858
252507AC2-088 GEN
Solar/Wind Harmer
2.064
24728605AND G2
Adder
4.411
970245AG2-165 GEN
Solar/Wind Harmer
20.527
965911AG1-460 GEN
Solar/Wind Harmer
1.601
25196808ZIMRHP
Adder
86.412
25194608D.CRK4
Adder
1.851
274761LEE CO EC;2U
Adder
10.448
274766LEE CO EC;7U
Adder
10.325
972235AH1-702 GEN1
Adder
2.828
274822ROCKFORD ;11
Adder
22.02
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
238185AF2-356 C
Solar/Wind Helper
2.169
339255AE2-071 GEN
Solar/Wind Harmer
1.246
964781AG1-341 GEN
Solar/Wind Harmer
12.447
945391AF1-204 GEN
Solar/Wind Harmer
16.279
962581AG1-107 GEN
Solar/Wind Harmer
5.875
961491AF2-440 GEN
Solar/Wind Harmer
2.442
970241AG2-163 GEN
Solar/Wind Harmer
28.958
966841AG1-555 GEN
Solar/Wind Harmer
2.893
252509AD1-136 GEN
Solar/Wind Harmer
0.295
970321AG2-212 GEN
Solar/Wind Harmer
20.527
276916AD2-100_GEN
Solar/Wind Harmer
24.115
276911AD2-131_GEN
Solar/Wind Harmer
4.874
957381AF2-032 GEN
Solar/Wind Harmer
0.48
25194408D.CRK1
Adder
8.517
25194508D.CRK3
Adder
1.592
972267AH1-718 GEN
Adder
4.679
274764LEE CO EC;5U
Adder
10.473
274765LEE CO EC;6U
Adder
10.473
274762LEE CO EC;3U
Adder
10.448
274763LEE CO EC;4U
Adder
10.35
274696ROCKY RD ;4P
Adder
12.769
274695ROCKY RD ;2P
Adder
12.475
274693ROCKY RD ;1P
Adder
12.352
274697ROCKY RD ;3P
Adder
3.389
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
962101AG1-054 GEN
Solar/Wind Helper
0.609
241985AE1-237 GEN
Solar/Wind Helper
0.231
241967AE2-285_GEN
Solar/Wind Helper
0.593
241801AE1-079 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
238120AE2-309 GEN
Solar/Wind Helper
0.419
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20088926STNY CRK
Solar/Wind Helper
0.775
20084626FORWARD
Solar/Wind Helper
0.336
203940AF1-140 C
Solar/Wind Helper
0.373
20088626ARWF_N39
Solar/Wind Helper
1.136
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
946381AF1-302 GEN
Solar/Wind Helper
0.207
203952AE2-129 C
Solar/Wind Helper
0.442
203946AE2-131 C
Solar/Wind Helper
0.442
942481AE2-261 GEN
Solar/Wind Harmer
34.305
25194608D.CRK4
Adder
1.851
274760LEE CO EC;1U
Adder
10.448
274767LEE CO EC;8U
Adder
10.325
25196608WSDLE5
Adder
9.621
972236AH1-702 GEN2
Adder
2.459
274682WAUKEGAN ;7U
Adder
20.129
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
235058AG1-386 C
Solar/Wind Helper
0.436
23750701CROSSCHOOL
Solar/Wind Helper
1.181
964991AG1-363 GEN
Solar/Wind Helper
3.632
202652Y1-033 WT C
Solar/Wind Helper
0.547
238118U2-030_1
Solar/Wind Helper
0.284
254305AE2-115 C
Solar/Wind Helper
0.203
20089126CSLMN_L13
Solar/Wind Helper
0.571
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
203818AF1-086 GEN
Solar/Wind Helper
1.58
24755605MDL-5G
Solar/Wind Harmer
1.072
23751201ROTHROCK
Solar/Wind Helper
0.732
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
254303AC2-168 GEN
Solar/Wind Helper
0.147
238117U2-030
Solar/Wind Helper
0.284
241966AE1-183 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.556
235531U2-073 GEN
Solar/Wind Helper
2.67
23751101LEADS_P59
Solar/Wind Helper
1.234
20088826HIGHLAND
Solar/Wind Helper
0.845
20094526CT_V3-030
Solar/Wind Helper
0.443
964201AG1-281 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.084
24791305MDL-5G
Solar/Wind Harmer
1.072
24690905MDL-1G C
Solar/Wind Harmer
9.207
270180AB1-006 GEN1
Solar/Wind Harmer
8.248
946581AF1-322 GEN
Solar/Wind Harmer
11.733
24691005MDL-2G C
Solar/Wind Harmer
4.241
24697605MDL-3G C
Solar/Wind Harmer
4.228
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
25196508WSDLE4
Adder
9.523
274823ROCKFORD ;21
Adder
21.86
274746AC1-111 G10
Adder
6.26
274744AC1-111 GEN8
Adder
6.26
274775LINCOLN ;6U
Adder
9.447
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241997AF1-093 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.207
238126S14_GEN_1
Solar/Wind Helper
0.669
20092526R32
Solar/Wind Helper
1.095
203961AE2-224 GEN
Solar/Wind Helper
2.258
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
203846AF2-130 C
Solar/Wind Helper
0.42
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
941231AE2-117 GEN
Solar/Wind Helper
0.441
24697905MDL-4G C
Solar/Wind Harmer
1.02
944201AF1-088_MTX
Adder
141.066
957141AF2-008_MTX
Adder
70.533
CPLELTFEXP_CPLE->PJM
CLTF
6.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
TVALTFEXP_TVA->PJM
CLTF
11.394
NYPJM->LTFIMP_NY
CLTF
5.171
LGEELTFEXP_LGEE->PJM
CLTF
8.351
WECLTFEXP_WEC->PJM
CLTF
4.291
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.624

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:12.57
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5863.47
MW Contribution:15.44
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.76
24318705GVG2
50/50
11.739
24722005FLATG5
50/50
2.658
24721905FLATG4
50/50
48.723
24686205CER G4
Adder
16.177
24686405CER G5
Adder
16.113
270053AF1-130 C
Solar/Wind Harmer
6.632
971191AH1-055 GEN
Solar/Wind Harmer
39.064
970913AG2-568 GEN
Solar/Wind Harmer
13.469
960911AF2-382 GEN
Solar/Wind Harmer
11.728
957541AF2-048 GEN
Solar/Wind Harmer
2.449
972103AH1-617 GEN
Solar/Wind Harmer
30.886
971461AH1-227 GEN
Solar/Wind Harmer
7.809
270346AE1-212 GEN
Solar/Wind Harmer
13.257
943031AE2-326 GEN
Solar/Wind Harmer
5.058
971331AH1-145 GEN
Solar/Wind Harmer
12.477
247619Y1-049
Adder
0.564
958121AF2-106 GEN
Solar/Wind Harmer
5.853
970093AG2-073 GEN
Solar/Wind Harmer
12.205
970243AG2-164 GEN
Solar/Wind Harmer
31.468
970519AG2-331 GEN
Solar/Wind Harmer
21.141
970699AG2-449 GEN
Solar/Wind Harmer
13.986
972167AH1-666 GEN
Solar/Wind Harmer
9.735
972273AH1-721 GEN
Adder
101.075
966571AG1-526 GEN
Solar/Wind Harmer
26.852
270291AC1-194 GEN
Solar/Wind Harmer
12.828
3429391JKCT 9G
Adder
10.046
970273AG2-179 GEN
Solar/Wind Harmer
4.651
958171AF2-111 GEN
Solar/Wind Harmer
29.515
24289405MTG1
50/50
11.76
243186AF1-051 GEN
50/50
12.611
24318705GVG2
50/50
11.739
24721805FLATG3
50/50
2.658
24721705FLATG2
50/50
48.723
960001AF2-291 GEN
Solar/Wind Harmer
6.065
24723205RIVRG3
Adder
37.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.892
970947AG2-589 GEN
Solar/Wind Harmer
3.922
24686105CER G3
Adder
16.263
24686505CER G6
Adder
16.242
971403AH1-188 GEN
Solar/Wind Harmer
24.803
24728305BUCHG2
Adder
6.985
971315AH1-136 GEN
Solar/Wind Harmer
3.105
927014AC1-188 GEN
Solar/Wind Harmer
2.455
971687AH1-348 GEN
Solar/Wind Harmer
1.523
24735205WLF2G2
Adder
7.999
971329AH1-144 GEN
Solar/Wind Harmer
16.096
970091AG2-072 GEN
Adder
94.679
970333AG2-219 GEN
Solar/Wind Harmer
38.461
945681AF1-233 GEN
Solar/Wind Harmer
22.966
3429241JKCT 3G
Adder
14.375
971821AH1-427 GEN
Solar/Wind Harmer
12.078
3429421JKCT 10G
Adder
10.046
943111AE2-339 GEN
Solar/Wind Harmer
1.064
339216AC1-074 GEN
Solar/Wind Harmer
2.018
970273AG2-179 GEN
Solar/Wind Harmer
2.912
971565AH1-281 GEN
Solar/Wind Harmer
2.371
339241AF1-083 GEN
Solar/Wind Harmer
1.967
252507AC2-088 GEN
Solar/Wind Harmer
2.122
964901AG1-354 GEN
Solar/Wind Harmer
17.575
962241AG1-070 GEN
Solar/Wind Harmer
5.234
25196808ZIMRHP
Adder
88.001
25196008MFTGT1
Adder
1.601
25194608D.CRK4
Adder
1.865
270336AE1-100 GEN
Solar/Wind Harmer
1.949
270445AC2-157 GEN2
Solar/Wind Harmer
6.293
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
946171AF1-282 GEN
Solar/Wind Harmer
10.953
971367AH1-164 GEN
Solar/Wind Harmer
3.823
943811AF1-049 GEN
Solar/Wind Harmer
4.073
270263AC1-001 GEN
Solar/Wind Harmer
1.114
24728605AND G2
Adder
4.036
963741AG1-226 GEN
Solar/Wind Harmer
46.021
965911AG1-460 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
40.758
253370AE2-315 SEC1
Adder
1.951
24721605FLATG1
50/50
2.658
270330AC1-082 GEN2
Solar/Wind Harmer
1.51
270329AC1-082 GEN1
Solar/Wind Harmer
0.889
972203AH1-686 GEN
Adder
4.44
24477305BRIDGE
Adder
0.635
957241AF2-018 GEN
Solar/Wind Harmer
7.929
270399AC1-101 GEN
Solar/Wind Harmer
7.483
270400AC1-102 GEN
Solar/Wind Harmer
7.483
941621AE2-160 GEN
Adder
5.566
970281AG2-184 GEN
Solar/Wind Harmer
32.43
972143AH1-644 GEN
Solar/Wind Harmer
15.443
270132AB1-180 C
Adder
0.184
971313AH1-133 GEN
Solar/Wind Harmer
15.282
971061AG2-657 GEN
Solar/Wind Harmer
13.752
971985AH1-537 GEN
Solar/Wind Harmer
26.909
962211AG1-066 GEN
Solar/Wind Harmer
3.527
24734705WLF1G3
Adder
8.169
24734805WLF1G4
Adder
8.169
24734905WLF1G5
Adder
8.169
24735105WLF2G1
Adder
7.999
966391AG1-508 GEN
Solar/Wind Harmer
4.787
339250AF1-203 GEN
Solar/Wind Harmer
0.708
971155AH1-034 GEN
Solar/Wind Harmer
11.668
960741AF2-365 GEN
Solar/Wind Harmer
5.83
962251AG1-071 GEN
Solar/Wind Harmer
6.397
25196008MFTGT1
Adder
1.55
252510AF1-249 C
Solar/Wind Harmer
0.477
25194608D.CRK4
Adder
1.865
25196608WSDLE5
Adder
9.681
270030AE2-140 GEN
Solar/Wind Harmer
22.032
253316AC1-085 GEN3
Solar/Wind Harmer
9.175
253433AC1-085 GEN1
Solar/Wind Harmer
5.824
946181AF1-283 GEN
Solar/Wind Harmer
14.239
253406AD2-031_GEN
Solar/Wind Harmer
1.378
970193AG2-126 GEN
Solar/Wind Harmer
15.807
24728705AND G3
Adder
8.441
24728505AND G1
Adder
4.036
270356AE2-297 GEN
Solar/Wind Harmer
4.782
270222AC2-111 GEN
Solar/Wind Harmer
8.539
253415AE1-040 GEN
Solar/Wind Harmer
1.167
942481AE2-261 GEN
Solar/Wind Harmer
30.502
253370AE2-315 SEC1
Adder
1.951
253371AE2-315 SEC2
Adder
1.845
274760LEE CO EC;1U
Adder
8.918
274767LEE CO EC;8U
Adder
8.813
972236AH1-702 GEN2
Adder
2.091
274682WAUKEGAN ;7U
Adder
16.961
274729ELWOOD EC;1P
Adder
6.986
237048AF1-022 C
Solar/Wind Helper
0.187
235058AG1-386 C
Solar/Wind Helper
0.451
237043AE2-125 C
Solar/Wind Helper
0.173
254305AE2-115 C
Solar/Wind Helper
0.211
202652Y1-033 WT C
Solar/Wind Helper
0.534
23750701CROSSCHOOL
Solar/Wind Helper
1.129
20089126CSLMN_L13
Solar/Wind Helper
0.56
20089026BF_G21_K23
Solar/Wind Helper
0.443
964991AG1-363 GEN
Solar/Wind Helper
3.463
238118U2-030_1
Solar/Wind Helper
0.272
203818AF1-086 GEN
Solar/Wind Helper
1.57
238127S14_GEN_2
Solar/Wind Helper
0.64
959441AF2-235 GEN
Solar/Wind Helper
0.22
243186AF1-051 GEN
50/50
12.611
24723005RIVRG1
Adder
37.09
24723105RIVRG2
Adder
37.09
24685805CER G1
Adder
16.156
24685905CER G2
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.489
24728205BUCHG1
Adder
6.985
971225AH1-072 GEN
Solar/Wind Harmer
3.044
971227AH1-073 GEN
Solar/Wind Harmer
3.044
270214AC2-123 GEN
Solar/Wind Harmer
3.214
971277AH1-098 GEN
Solar/Wind Harmer
5.494
970879AG2-548 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
8.094
971073AG2-665 GEN
Solar/Wind Harmer
5.647
270583AD2-179 GEN
Solar/Wind Harmer
12.914
960161AF2-307 GEN
Solar/Wind Harmer
8.235
270186AC1-089 GEN
Solar/Wind Harmer
7.622
962581AG1-107 GEN
Solar/Wind Harmer
6.151
961491AF2-440 GEN
Solar/Wind Harmer
2.556
970239AG2-162 GEN
Solar/Wind Harmer
13.403
942891AE2-308 GEN
Solar/Wind Harmer
12.168
972043AH1-570 GEN
Solar/Wind Harmer
3.032
972045AH1-571 GEN
Solar/Wind Harmer
2.426
339221AD2-048_GEN
Solar/Wind Harmer
1.861
971125AH1-004 GEN
Solar/Wind Harmer
4.815
970107AG2-081 GEN
Solar/Wind Harmer
3.611
970235AG2-159 GEN
Solar/Wind Harmer
4.78
970235AG2-159 GEN
Solar/Wind Harmer
2.918
339231AF1-038_GEN
Solar/Wind Harmer
2.165
966021AG1-471 GEN
Solar/Wind Harmer
6.404
971485AH1-239 GEN
Solar/Wind Harmer
9.472
252509AD1-136 GEN
Solar/Wind Harmer
0.303
971081AG2-670 GEN
Solar/Wind Harmer
8.855
970653AG2-424 GEN
Solar/Wind Harmer
5.682
970653AG2-424 GEN
Solar/Wind Harmer
2.054
339236AF1-050_GEN
Solar/Wind Harmer
2.132
964571AG1-320 GEN
Solar/Wind Harmer
9.614
339255AE2-071 GEN
Solar/Wind Harmer
1.239
964781AG1-341 GEN
Solar/Wind Harmer
12.366
25183208HLCRTG
Solar/Wind Harmer
6.95
252519AF1-045_GEN
Solar/Wind Harmer
6.963
252516AE2-318_GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
8.581
25194508D.CRK3
Adder
1.604
270444AC2-157 GEN1
Solar/Wind Harmer
6.293
253317AC1-085 GEN4
Solar/Wind Harmer
9.175
945391AF1-204 GEN
Solar/Wind Harmer
14.686
253394AE2-221_GEN
Solar/Wind Harmer
4.786
253398AE2-221_GEN2
Solar/Wind Harmer
4.786
24728805RICHG1
Adder
3.931
24728905RICHG2
Adder
3.931
276916AD2-100_GEN
Solar/Wind Harmer
21.483
276911AD2-131_GEN
Solar/Wind Harmer
4.342
970241AG2-163 GEN
Solar/Wind Harmer
25.567
957381AF2-032 GEN
Solar/Wind Harmer
0.427
253370AE2-315 SEC1
Adder
1.951
972267AH1-718 GEN
Adder
4.004
274764LEE CO EC;5U
Adder
8.939
274765LEE CO EC;6U
Adder
8.939
274762LEE CO EC;3U
Adder
8.918
274763LEE CO EC;4U
Adder
8.834
25322209TAIT E
Adder
9.264
25322209TAIT E
Adder
9.056
247621Y3-024
Adder
0.228
274683WAUKEGAN ;8U
Adder
19.896
274683WAUKEGAN ;8U
Adder
16.771
274696ROCKY RD ;4P
Adder
10.757
274695ROCKY RD ;2P
Adder
10.508
274693ROCKY RD ;1P
Adder
10.405
274697ROCKY RD ;3P
Adder
2.855
23652301WDPWR_K20
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.626
241967AE2-285_GEN
Solar/Wind Helper
0.613
241801AE1-079 GEN
Solar/Wind Helper
0.238
241985AE1-237 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.223
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.323
946071AF1-272 GEN
Solar/Wind Helper
2.537
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.764
20084626FORWARD
Solar/Wind Helper
0.332
203940AF1-140 C
Solar/Wind Helper
0.368
238120AE2-309 GEN
Solar/Wind Helper
0.4
946381AF1-302 GEN
Solar/Wind Helper
0.207
20088626ARWF_N39
Solar/Wind Helper
1.121
20303426NA_O38_P22
Solar/Wind Helper
0.919
203853AF1-134 C O1
Solar/Wind Helper
0.443
970879AG2-548 GEN
Solar/Wind Harmer
5.647
971981AH1-535 GEN
Solar/Wind Harmer
12.632
270367AC2-061_GEN
Solar/Wind Harmer
3.956
972163AH1-664 GEN
Solar/Wind Harmer
12.214
972165AH1-665 GEN
Solar/Wind Harmer
9.771
965401AG1-405 GEN
Solar/Wind Harmer
6.93
965411AG1-406 GEN
Solar/Wind Harmer
3.11
3429211JKCT 2G
Adder
14.189
339211AE2-254 GEN
Solar/Wind Harmer
1.83
339243AC2-075 GEN1
Solar/Wind Harmer
0.546
970455AG2-298 GEN
Solar/Wind Harmer
7.102
25196108MFTGT2
Adder
1.765
25196108MFTGT2
Adder
1.639
252524AE2-267 GEN
Solar/Wind Harmer
1.782
25196408WSDLE3
Adder
9.966
25196308WSDLE2
Adder
9.88
25196208WSDLE1
Adder
9.855
25196708WSDLE6
Adder
9.83
25196508WSDLE4
Adder
9.582
270069AE2-166 C O1
Solar/Wind Harmer
3.07
270340AC2-060 GEN
Solar/Wind Harmer
3.233
944031AF1-071 GEN
Solar/Wind Harmer
1.053
944221AF1-090 GEN
Solar/Wind Harmer
11.289
962771AG1-126 GEN
Solar/Wind Harmer
40.758
25306009OHH W.
Adder
2.813
253372AE2-315 SEC3
Adder
1.845
253372AE2-315 SEC3
Adder
1.845
274823ROCKFORD ;21
Adder
18.572
274746AC1-111 G10
Adder
5.257
274744AC1-111 GEN8
Adder
5.257
23750501ELLIOTTS
Solar/Wind Helper
0.642
254304AE2-114 C
Solar/Wind Helper
0.211
241997AF1-093 GEN
Solar/Wind Helper
0.245
241982AE2-343 S C
Solar/Wind Helper
0.214
20092526R32
Solar/Wind Helper
1.083
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
203961AE2-224 GEN
Solar/Wind Helper
2.23
20091526CHSTN_FL
Solar/Wind Helper
0.54
20090526Q36
Solar/Wind Helper
0.964
203993AD2-133_GEN1
Solar/Wind Helper
0.964
253371AE2-315 SEC2
Adder
1.845
274761LEE CO EC;2U
Adder
8.918
274766LEE CO EC;7U
Adder
8.813
972235AH1-702 GEN1
Adder
2.404
274822ROCKFORD ;11
Adder
18.707
25326309TAIT D
Adder
1.04
274828WAUKEGAN ;BP
Adder
10.429
274682WAUKEGAN ;7U
Adder
16.961
274745AC1-111 GEN9
Adder
5.257
237046AF1-021 C
Solar/Wind Helper
0.476
254303AC2-168 GEN
Solar/Wind Helper
0.153
241966AE1-183 GEN
Solar/Wind Helper
0.245
238185AF2-356 C
Solar/Wind Helper
2.079
23751201ROTHROCK
Solar/Wind Helper
0.699
235054AD2-180 GEN
Solar/Wind Helper
1.616
23562501BACKB
Solar/Wind Helper
0.85
20089226LOOKOUT
Solar/Wind Helper
0.545
238117U2-030
Solar/Wind Helper
0.272
20088826HIGHLAND
Solar/Wind Helper
0.835
235531U2-073 GEN
Solar/Wind Helper
2.555
20094526CT_V3-030
Solar/Wind Helper
0.44
964201AG1-281 GEN
Solar/Wind Helper
0.449
970149AG2-104 GEN
Solar/Wind Harmer
20.717
944201AF1-088_MTX
Adder
131.041
957141AF2-008_MTX
Adder
65.52
CPLELTFEXP_CPLE->PJM
CLTF
7.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
144.471
LAGNLTFEXP_LAGN->PJM
CLTF
21.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.108
TVALTFEXP_TVA->PJM
CLTF
11.299
NYPJM->LTFIMP_NY
CLTF
5.029
LGEELTFEXP_LGEE->PJM
CLTF
8.22
WECLTFEXP_WEC->PJM
CLTF
3.65
AG2-052LTFEXP_AG2-052->PJM
LTF
0.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.329
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.883
MECLTFEXP_MEC->PJM
CLTF
16.832
SIGELTFEXP_SIGE->PJM
CLTF
0.595

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5644.14
MW Contribution:15.57
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.814
24318705GVG2
50/50
11.798
24722005FLATG5
50/50
2.672
24721905FLATG4
50/50
48.99
24686205CER G4
Adder
16.28
24686405CER G5
Adder
16.216
270053AF1-130 C
Solar/Wind Harmer
6.678
971191AH1-055 GEN
Solar/Wind Harmer
39.337
970913AG2-568 GEN
Solar/Wind Harmer
13.568
960911AF2-382 GEN
Solar/Wind Harmer
11.821
957541AF2-048 GEN
Solar/Wind Harmer
2.468
972103AH1-617 GEN
Solar/Wind Harmer
31.134
971461AH1-227 GEN
Solar/Wind Harmer
7.872
270346AE1-212 GEN
Solar/Wind Harmer
13.369
943031AE2-326 GEN
Solar/Wind Harmer
5.103
971331AH1-145 GEN
Solar/Wind Harmer
12.593
247619Y1-049
Adder
0.569
958121AF2-106 GEN
Solar/Wind Harmer
5.909
970093AG2-073 GEN
Solar/Wind Harmer
12.329
970243AG2-164 GEN
Solar/Wind Harmer
31.788
970519AG2-331 GEN
Solar/Wind Harmer
21.356
970699AG2-449 GEN
Solar/Wind Harmer
14.128
972167AH1-666 GEN
Solar/Wind Harmer
9.834
972273AH1-721 GEN
Adder
102.108
966571AG1-526 GEN
Solar/Wind Harmer
27.128
270291AC1-194 GEN
Solar/Wind Harmer
12.959
3429391JKCT 9G
Adder
10.15
970273AG2-179 GEN
Solar/Wind Harmer
4.7
958171AF2-111 GEN
Solar/Wind Harmer
29.825
339250AF1-203 GEN
Solar/Wind Harmer
0.715
971155AH1-034 GEN
Solar/Wind Harmer
11.792
960741AF2-365 GEN
Solar/Wind Harmer
5.892
962251AG1-071 GEN
Solar/Wind Harmer
6.465
25196008MFTGT1
Adder
1.567
252510AF1-249 C
Solar/Wind Harmer
0.482
25194608D.CRK4
Adder
1.886
25196608WSDLE5
Adder
9.788
270030AE2-140 GEN
Solar/Wind Harmer
22.282
253316AC1-085 GEN3
Solar/Wind Harmer
9.279
253433AC1-085 GEN1
Solar/Wind Harmer
5.89
946181AF1-283 GEN
Solar/Wind Harmer
14.4
253406AD2-031_GEN
Solar/Wind Harmer
1.394
970193AG2-126 GEN
Solar/Wind Harmer
15.993
24728705AND G3
Adder
8.541
24728505AND G1
Adder
4.084
270356AE2-297 GEN
Solar/Wind Harmer
4.839
270222AC2-111 GEN
Solar/Wind Harmer
8.641
253415AE1-040 GEN
Solar/Wind Harmer
1.181
942481AE2-261 GEN
Solar/Wind Harmer
30.873
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274760LEE CO EC;1U
Adder
9.033
274767LEE CO EC;8U
Adder
8.927
972236AH1-702 GEN2
Adder
2.118
274682WAUKEGAN ;7U
Adder
17.184
274729ELWOOD EC;1P
Adder
7.078
237048AF1-022 C
Solar/Wind Helper
0.185
235058AG1-386 C
Solar/Wind Helper
0.446
237043AE2-125 C
Solar/Wind Helper
0.171
254305AE2-115 C
Solar/Wind Helper
0.208
202652Y1-033 WT C
Solar/Wind Helper
0.526
23750701CROSSCHOOL
Solar/Wind Helper
1.114
20089126CSLMN_L13
Solar/Wind Helper
0.552
243186AF1-051 GEN
50/50
12.674
24723005RIVRG1
Adder
37.324
24723105RIVRG2
Adder
37.324
24685805CER G1
Adder
16.259
24685905CER G2
Adder
16.259
944971AF1-162 GEN
Solar/Wind Harmer
12.576
24728205BUCHG1
Adder
7.041
971225AH1-072 GEN
Solar/Wind Harmer
3.069
971227AH1-073 GEN
Solar/Wind Harmer
3.069
270214AC2-123 GEN
Solar/Wind Harmer
3.243
971277AH1-098 GEN
Solar/Wind Harmer
5.544
970879AG2-548 GEN
Solar/Wind Harmer
8.171
971073AG2-665 GEN
Solar/Wind Harmer
8.171
24721605FLATG1
50/50
2.672
270330AC1-082 GEN2
Solar/Wind Harmer
1.52
270329AC1-082 GEN1
Solar/Wind Harmer
0.895
972203AH1-686 GEN
Adder
4.469
24477305BRIDGE
Adder
0.639
957241AF2-018 GEN
Solar/Wind Harmer
7.983
270399AC1-101 GEN
Solar/Wind Harmer
7.536
270400AC1-102 GEN
Solar/Wind Harmer
7.536
941621AE2-160 GEN
Adder
5.607
970281AG2-184 GEN
Solar/Wind Harmer
32.691
972143AH1-644 GEN
Solar/Wind Harmer
15.567
270132AB1-180 C
Adder
0.186
971313AH1-133 GEN
Solar/Wind Harmer
15.406
971061AG2-657 GEN
Solar/Wind Harmer
13.864
971985AH1-537 GEN
Solar/Wind Harmer
27.131
962211AG1-066 GEN
Solar/Wind Harmer
3.557
24734705WLF1G3
Adder
8.24
24734805WLF1G4
Adder
8.24
24734905WLF1G5
Adder
8.24
24735105WLF2G1
Adder
8.071
966391AG1-508 GEN
Solar/Wind Harmer
4.83
970879AG2-548 GEN
Solar/Wind Harmer
5.701
971981AH1-535 GEN
Solar/Wind Harmer
12.756
270367AC2-061_GEN
Solar/Wind Harmer
3.995
972163AH1-664 GEN
Solar/Wind Harmer
12.338
972165AH1-665 GEN
Solar/Wind Harmer
9.871
965401AG1-405 GEN
Solar/Wind Harmer
7.001
965411AG1-406 GEN
Solar/Wind Harmer
3.142
3429211JKCT 2G
Adder
14.334
339211AE2-254 GEN
Solar/Wind Harmer
1.849
339243AC2-075 GEN1
Solar/Wind Harmer
0.552
970455AG2-298 GEN
Solar/Wind Harmer
7.176
25196108MFTGT2
Adder
1.784
25196108MFTGT2
Adder
1.656
252524AE2-267 GEN
Solar/Wind Harmer
1.801
25196408WSDLE3
Adder
10.076
25196308WSDLE2
Adder
9.988
25196208WSDLE1
Adder
9.963
25196708WSDLE6
Adder
9.938
25196508WSDLE4
Adder
9.688
270069AE2-166 C O1
Solar/Wind Harmer
3.104
270340AC2-060 GEN
Solar/Wind Harmer
3.271
944031AF1-071 GEN
Solar/Wind Harmer
1.065
944221AF1-090 GEN
Solar/Wind Harmer
11.424
962771AG1-126 GEN
Solar/Wind Harmer
41.255
25306009OHH W.
Adder
2.849
253372AE2-315 SEC3
Adder
1.869
253372AE2-315 SEC3
Adder
1.869
274823ROCKFORD ;21
Adder
18.813
274746AC1-111 G10
Adder
5.326
274744AC1-111 GEN8
Adder
5.326
23750501ELLIOTTS
Solar/Wind Helper
0.635
254304AE2-114 C
Solar/Wind Helper
0.208
241997AF1-093 GEN
Solar/Wind Helper
0.242
241982AE2-343 S C
Solar/Wind Helper
0.211
20092526R32
Solar/Wind Helper
1.068
203846AF2-130 C
Solar/Wind Helper
0.419
238126S14_GEN_1
Solar/Wind Helper
0.631
203961AE2-224 GEN
Solar/Wind Helper
2.198
20091526CHSTN_FL
Solar/Wind Helper
0.532
971073AG2-665 GEN
Solar/Wind Harmer
5.701
270583AD2-179 GEN
Solar/Wind Harmer
13.038
960161AF2-307 GEN
Solar/Wind Harmer
8.314
270186AC1-089 GEN
Solar/Wind Harmer
7.697
962581AG1-107 GEN
Solar/Wind Harmer
6.214
961491AF2-440 GEN
Solar/Wind Harmer
2.582
970239AG2-162 GEN
Solar/Wind Harmer
13.539
942891AE2-308 GEN
Solar/Wind Harmer
12.292
972043AH1-570 GEN
Solar/Wind Harmer
3.063
972045AH1-571 GEN
Solar/Wind Harmer
2.45
339221AD2-048_GEN
Solar/Wind Harmer
1.88
971125AH1-004 GEN
Solar/Wind Harmer
4.864
970107AG2-081 GEN
Solar/Wind Harmer
3.648
970235AG2-159 GEN
Solar/Wind Harmer
4.83
970235AG2-159 GEN
Solar/Wind Harmer
2.948
339231AF1-038_GEN
Solar/Wind Harmer
2.187
966021AG1-471 GEN
Solar/Wind Harmer
6.471
971485AH1-239 GEN
Solar/Wind Harmer
9.571
252509AD1-136 GEN
Solar/Wind Harmer
0.306
971081AG2-670 GEN
Solar/Wind Harmer
8.948
970653AG2-424 GEN
Solar/Wind Harmer
5.742
970653AG2-424 GEN
Solar/Wind Harmer
2.076
339236AF1-050_GEN
Solar/Wind Harmer
2.155
964571AG1-320 GEN
Solar/Wind Harmer
9.715
339255AE2-071 GEN
Solar/Wind Harmer
1.252
964781AG1-341 GEN
Solar/Wind Harmer
12.498
25183208HLCRTG
Solar/Wind Harmer
7.025
252519AF1-045_GEN
Solar/Wind Harmer
7.038
252516AE2-318_GEN
Solar/Wind Harmer
5.369
25194408D.CRK1
Adder
8.675
25194508D.CRK3
Adder
1.622
270444AC2-157 GEN1
Solar/Wind Harmer
6.363
253317AC1-085 GEN4
Solar/Wind Harmer
9.279
945391AF1-204 GEN
Solar/Wind Harmer
14.859
253394AE2-221_GEN
Solar/Wind Harmer
4.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.843
24728805RICHG1
Adder
3.978
24728905RICHG2
Adder
3.978
276916AD2-100_GEN
Solar/Wind Harmer
21.743
276911AD2-131_GEN
Solar/Wind Harmer
4.394
970241AG2-163 GEN
Solar/Wind Harmer
25.877
957381AF2-032 GEN
Solar/Wind Harmer
0.432
253370AE2-315 SEC1
Adder
1.976
972267AH1-718 GEN
Adder
4.056
274764LEE CO EC;5U
Adder
9.055
274765LEE CO EC;6U
Adder
9.055
274762LEE CO EC;3U
Adder
9.033
274763LEE CO EC;4U
Adder
8.948
25322209TAIT E
Adder
9.385
25322209TAIT E
Adder
9.175
247621Y3-024
Adder
0.231
274683WAUKEGAN ;8U
Adder
20.157
274683WAUKEGAN ;8U
Adder
16.992
274696ROCKY RD ;4P
Adder
10.898
274695ROCKY RD ;2P
Adder
10.646
274693ROCKY RD ;1P
Adder
10.542
274697ROCKY RD ;3P
Adder
2.892
23652301WDPWR_K20
Solar/Wind Helper
0.138
962101AG1-054 GEN
Solar/Wind Helper
0.618
241985AE1-237 GEN
Solar/Wind Helper
0.235
241967AE2-285_GEN
Solar/Wind Helper
0.605
241801AE1-079 GEN
Solar/Wind Helper
0.235
23585401KL_K28_T16
Solar/Wind Helper
1.207
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.291
946071AF1-272 GEN
Solar/Wind Helper
2.502
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088926STNY CRK
Solar/Wind Helper
0.754
20084626FORWARD
Solar/Wind Helper
0.327
203940AF1-140 C
Solar/Wind Helper
0.363
238120AE2-309 GEN
Solar/Wind Helper
0.394
20089026BF_G21_K23
Solar/Wind Helper
0.437
964991AG1-363 GEN
Solar/Wind Helper
3.415
238118U2-030_1
Solar/Wind Helper
0.268
203818AF1-086 GEN
Solar/Wind Helper
1.548
238127S14_GEN_2
Solar/Wind Helper
0.631
24289405MTG1
50/50
11.814
243186AF1-051 GEN
50/50
12.674
24318705GVG2
50/50
11.798
24721805FLATG3
50/50
2.672
24721705FLATG2
50/50
48.99
960001AF2-291 GEN
Solar/Wind Harmer
6.103
24723205RIVRG3
Adder
37.324
270331AC1-082 GEN3
Solar/Wind Harmer
0.897
970947AG2-589 GEN
Solar/Wind Harmer
3.947
24686105CER G3
Adder
16.366
24686505CER G6
Adder
16.345
971403AH1-188 GEN
Solar/Wind Harmer
24.977
24728305BUCHG2
Adder
7.041
971315AH1-136 GEN
Solar/Wind Harmer
3.129
927014AC1-188 GEN
Solar/Wind Harmer
2.475
971687AH1-348 GEN
Solar/Wind Harmer
1.535
24735205WLF2G2
Adder
8.071
971329AH1-144 GEN
Solar/Wind Harmer
16.245
970091AG2-072 GEN
Adder
95.631
970333AG2-219 GEN
Solar/Wind Harmer
38.852
945681AF1-233 GEN
Solar/Wind Harmer
23.2
3429241JKCT 3G
Adder
14.522
971821AH1-427 GEN
Solar/Wind Harmer
12.202
3429421JKCT 10G
Adder
10.15
943111AE2-339 GEN
Solar/Wind Harmer
1.075
339216AC1-074 GEN
Solar/Wind Harmer
2.039
970273AG2-179 GEN
Solar/Wind Harmer
2.943
971565AH1-281 GEN
Solar/Wind Harmer
2.396
339241AF1-083 GEN
Solar/Wind Harmer
1.988
252507AC2-088 GEN
Solar/Wind Harmer
2.144
964901AG1-354 GEN
Solar/Wind Harmer
17.761
962241AG1-070 GEN
Solar/Wind Harmer
5.29
25196808ZIMRHP
Adder
88.943
25196008MFTGT1
Adder
1.618
25194608D.CRK4
Adder
1.886
270336AE1-100 GEN
Solar/Wind Harmer
1.97
270445AC2-157 GEN2
Solar/Wind Harmer
6.363
253432AC1-085 GEN2
Solar/Wind Harmer
0.297
946171AF1-282 GEN
Solar/Wind Harmer
11.077
971367AH1-164 GEN
Solar/Wind Harmer
3.867
943811AF1-049 GEN
Solar/Wind Harmer
4.12
270263AC1-001 GEN
Solar/Wind Harmer
1.127
24728605AND G2
Adder
4.084
963741AG1-226 GEN
Solar/Wind Harmer
46.579
965911AG1-460 GEN
Solar/Wind Harmer
1.441
962761AG1-125 GEN
Solar/Wind Harmer
41.255
253370AE2-315 SEC1
Adder
1.976
253371AE2-315 SEC2
Adder
1.869
274761LEE CO EC;2U
Adder
9.033
274766LEE CO EC;7U
Adder
8.927
972235AH1-702 GEN1
Adder
2.436
274822ROCKFORD ;11
Adder
18.951
25326309TAIT D
Adder
1.054
274828WAUKEGAN ;BP
Adder
10.566
274682WAUKEGAN ;7U
Adder
17.184
274745AC1-111 GEN9
Adder
5.326
237046AF1-021 C
Solar/Wind Helper
0.471
254303AC2-168 GEN
Solar/Wind Helper
0.151
241966AE1-183 GEN
Solar/Wind Helper
0.242
238185AF2-356 C
Solar/Wind Helper
2.051
23751201ROTHROCK
Solar/Wind Helper
0.69
235054AD2-180 GEN
Solar/Wind Helper
1.594
23562501BACKB
Solar/Wind Helper
0.838
20089226LOOKOUT
Solar/Wind Helper
0.537
238117U2-030
Solar/Wind Helper
0.268
20088826HIGHLAND
Solar/Wind Helper
0.824
235531U2-073 GEN
Solar/Wind Helper
2.519
20094526CT_V3-030
Solar/Wind Helper
0.433
964201AG1-281 GEN
Solar/Wind Helper
0.442
970149AG2-104 GEN
Solar/Wind Harmer
20.97
944201AF1-088_MTX
Adder
132.484
957141AF2-008_MTX
Adder
66.242
CPLELTFEXP_CPLE->PJM
CLTF
7.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
146.148
LAGNLTFEXP_LAGN->PJM
CLTF
21.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.485
TVALTFEXP_TVA->PJM
CLTF
11.425
NYPJM->LTFIMP_NY
CLTF
4.949
LGEELTFEXP_LGEE->PJM
CLTF
8.306
WECLTFEXP_WEC->PJM
CLTF
3.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.222
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.356
MECLTFEXP_MEC->PJM
CLTF
17.041
SIGELTFEXP_SIGE->PJM
CLTF
0.602

Details for 05SOFTSH-05CONSTP 138.0 kV Ckt 1 line l/o AEP_P4_#16060_05GARRETT 138_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16060_05GARRETT 138_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:329.56
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05SOFTSH-05CONSTP 138.0 kV Ckt 1 line l/o AEP_P4_#16061_05GARRETT 138_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16061_05GARRETT 138_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:329.56
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05SOFTSH-05CONSTP 138.0 kV Ckt 1 line l/o AEP_P4_#16062_05GARRETT 138_CB3_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16062_05GARRETT 138_CB3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.72 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:326.68
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05SOFTSH-05CONSTP 138.0 kV Ckt 1 line l/o AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.09 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:321.62
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
972103AH1-617 GEN
Solar/Wind Harmer
130.705
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 05SOFTSH-05CONSTP 138.0 kV Ckt 1 line l/o AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOFTSH-05CONSTP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.08 %
Rating:309.0 MVA
Rating Type:B
MVA to Mitigate:321.61
MW Contribution:65.35
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
137.241
972143AH1-644 GEN
Solar/Wind Harmer
65.353
962211AG1-066 GEN
Solar/Wind Harmer
6.438
972103AH1-617 GEN
Solar/Wind Harmer
130.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.16
LAGNLTFEXP_LAGN->PJM
CLTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.054
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.024
LGEELTFEXP_LGEE->PJM
CLTF
0.21
WECLTFEXP_WEC->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.788
MECLTFEXP_MEC->PJM
CLTF
0.213
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.71 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1818.59
MW Contribution:6.2
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.014
972165AH1-665 GEN
Solar/Wind Harmer
34.411
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.746
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.383
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.675
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.013
972143AH1-644 GEN
Solar/Wind Harmer
6.197
945631AF1-228 GEN
Solar/Wind Helper
0.922
241972AD1-140 GEN
Solar/Wind Helper
1.753
3429631SPURLK3G
50/50
9.769
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.708
972167AH1-666 GEN
Solar/Wind Harmer
35.712
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.159
966571AG1-526 GEN
Solar/Wind Harmer
42.232
972273AH1-721 GEN
Adder
104.488
970273AG2-179 GEN
Solar/Wind Harmer
4.096
960741AF2-365 GEN
Solar/Wind Harmer
4.057
339250AF1-203 GEN
Solar/Wind Harmer
0.484
971155AH1-034 GEN
Solar/Wind Harmer
7.829
962251AG1-071 GEN
Solar/Wind Harmer
4.152
972103AH1-617 GEN
Solar/Wind Harmer
12.393
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.684
253415AE1-040 GEN
Solar/Wind Helper
0.407
3429661SPURLK4G
50/50
9.769
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.785
945681AF1-233 GEN
Solar/Wind Harmer
83.563
339216AC1-074 GEN
Solar/Wind Harmer
4.868
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.162
971821AH1-427 GEN
Solar/Wind Harmer
16.414
971565AH1-281 GEN
Solar/Wind Harmer
2.168
339241AF1-083 GEN
Solar/Wind Harmer
1.765
971315AH1-136 GEN
Solar/Wind Harmer
2.121
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.831
962241AG1-070 GEN
Solar/Wind Harmer
3.397
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.993
3429601SPURLK2G
50/50
18.627
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.442
970107AG2-081 GEN
Solar/Wind Harmer
8.582
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.296
942891AE2-308 GEN
Solar/Wind Harmer
25.136
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.243
970235AG2-159 GEN
Solar/Wind Harmer
2.59
971081AG2-670 GEN
Solar/Wind Harmer
7.638
970653AG2-424 GEN
Solar/Wind Harmer
4.629
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.673
966021AG1-471 GEN
Solar/Wind Harmer
4.84
270186AC1-089 GEN
Solar/Wind Harmer
5.47
971485AH1-239 GEN
Solar/Wind Harmer
7.086
964571AG1-320 GEN
Solar/Wind Harmer
7.225
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.106
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
253394AE2-221_GEN
Solar/Wind Helper
2.188
253398AE2-221_GEN2
Solar/Wind Helper
2.188
25183208HLCRTG
Solar/Wind Helper
2.422
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.114
950011AG9-010
External Queue
6.110060214996338
950051AG9-018
External Queue
23.242685317993164
950041AG9-017
External Queue
23.325098037719727
CPLELTFEXP_CPLE->PJM
CLTF
1.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.494
LAGNLTFEXP_LAGN->PJM
CLTF
6.065
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.858
TVALTFEXP_TVA->PJM
CLTF
3.721
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.925
WECLTFEXP_WEC->PJM
CLTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.309
MECLTFEXP_MEC->PJM
CLTF
2.533
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.58 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1816.67
MW Contribution:6.2
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
43.016
972165AH1-665 GEN
Solar/Wind Harmer
34.413
339243AC2-075 GEN1
Solar/Wind Harmer
1.318
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
2.561
965401AG1-405 GEN
Solar/Wind Harmer
8.381
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
6.673
962211AG1-066 GEN
Solar/Wind Harmer
2.191
970281AG2-184 GEN
Solar/Wind Harmer
13.012
972143AH1-644 GEN
Solar/Wind Harmer
6.196
945631AF1-228 GEN
Solar/Wind Helper
0.92
3429631SPURLK3G
50/50
9.77
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
128.718
972167AH1-666 GEN
Solar/Wind Harmer
35.714
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
23.157
966571AG1-526 GEN
Solar/Wind Harmer
42.226
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.095
960741AF2-365 GEN
Solar/Wind Harmer
4.056
339250AF1-203 GEN
Solar/Wind Harmer
0.483
971155AH1-034 GEN
Solar/Wind Harmer
7.826
962251AG1-071 GEN
Solar/Wind Harmer
4.151
972103AH1-617 GEN
Solar/Wind Harmer
12.392
971461AH1-227 GEN
Solar/Wind Harmer
2.259
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
83.568
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
7.195
972045AH1-571 GEN
Solar/Wind Harmer
5.756
971125AH1-004 GEN
Solar/Wind Harmer
11.441
970107AG2-081 GEN
Solar/Wind Harmer
8.581
960161AF2-307 GEN
Solar/Wind Harmer
17.966
339221AD2-048_GEN
Solar/Wind Harmer
4.295
942891AE2-308 GEN
Solar/Wind Harmer
25.135
339231AF1-038_GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
4.237
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
7.636
970653AG2-424 GEN
Solar/Wind Harmer
4.628
970653AG2-424 GEN
Solar/Wind Harmer
1.673
339236AF1-050_GEN
Solar/Wind Harmer
1.672
270186AC1-089 GEN
Solar/Wind Harmer
5.474
966021AG1-471 GEN
Solar/Wind Harmer
4.838
971485AH1-239 GEN
Solar/Wind Harmer
7.084
964571AG1-320 GEN
Solar/Wind Harmer
7.222
339255AE2-071 GEN
Solar/Wind Harmer
0.846
964781AG1-341 GEN
Solar/Wind Harmer
8.103
971225AH1-072 GEN
Solar/Wind Harmer
0.881
971227AH1-073 GEN
Solar/Wind Harmer
0.881
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
339216AC1-074 GEN
Solar/Wind Harmer
4.867
943111AE2-339 GEN
Solar/Wind Harmer
2.558
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
16.411
971565AH1-281 GEN
Solar/Wind Harmer
2.167
339241AF1-083 GEN
Solar/Wind Harmer
1.764
971315AH1-136 GEN
Solar/Wind Harmer
2.12
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
12.826
962241AG1-070 GEN
Solar/Wind Harmer
3.396
971687AH1-348 GEN
Solar/Wind Harmer
0.457
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
950041AG9-017
External Queue
23.331375122070312
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.61 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1801.71
MW Contribution:4.71
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
13.435
972043AH1-570 GEN
Solar/Wind Harmer
5.591
972045AH1-571 GEN
Solar/Wind Harmer
4.473
971125AH1-004 GEN
Solar/Wind Harmer
8.9
970107AG2-081 GEN
Solar/Wind Harmer
6.675
339221AD2-048_GEN
Solar/Wind Harmer
3.382
960161AF2-307 GEN
Solar/Wind Harmer
13.557
942891AE2-308 GEN
Solar/Wind Harmer
19.615
970235AG2-159 GEN
Solar/Wind Harmer
4.694
970235AG2-159 GEN
Solar/Wind Harmer
2.866
339231AF1-038_GEN
Solar/Wind Harmer
1.69
971081AG2-670 GEN
Solar/Wind Harmer
6.943
970653AG2-424 GEN
Solar/Wind Harmer
4.401
970653AG2-424 GEN
Solar/Wind Harmer
1.591
964571AG1-320 GEN
Solar/Wind Harmer
7.156
339236AF1-050_GEN
Solar/Wind Harmer
1.548
966021AG1-471 GEN
Solar/Wind Harmer
4.332
971485AH1-239 GEN
Solar/Wind Harmer
6.379
339255AE2-071 GEN
Solar/Wind Harmer
0.801
964781AG1-341 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
4.24
25194408D.CRK1
Adder
5.107
25194508D.CRK3
Adder
0.955
25183208HLCRTG
Solar/Wind Helper
5.68
253394AE2-221_GEN
Solar/Wind Helper
3.647
253398AE2-221_GEN2
Solar/Wind Helper
3.647
270518AE2-148 GEN
Solar/Wind Helper
9.647
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
3429631SPURLK3G
50/50
7.046
25197108MELDL2
50/50
0.574
958171AF2-111 GEN
Solar/Wind Harmer
93.548
972167AH1-666 GEN
Solar/Wind Harmer
26.189
3429391JKCT 9G
Adder
18.466
970093AG2-073 GEN
Solar/Wind Harmer
18.208
966571AG1-526 GEN
Solar/Wind Harmer
34.399
972273AH1-721 GEN
Adder
88.436
970273AG2-179 GEN
Solar/Wind Harmer
3.601
960741AF2-365 GEN
Solar/Wind Harmer
3.916
25196008MFTGT1
Adder
1.019
339250AF1-203 GEN
Solar/Wind Harmer
0.458
971155AH1-034 GEN
Solar/Wind Harmer
7.447
962251AG1-071 GEN
Solar/Wind Harmer
4.002
25196608WSDLE5
Adder
5.903
25194608D.CRK4
Adder
1.11
252510AF1-249 C
Solar/Wind Harmer
0.263
972103AH1-617 GEN
Solar/Wind Harmer
9.431
253338AC1-165 GEN
Solar/Wind Helper
1.288
253333AC1-068 GEN
Solar/Wind Helper
1.335
253406AD2-031_GEN
Solar/Wind Helper
1.189
253415AE1-040 GEN
Solar/Wind Helper
0.677
241955AC1-078 GEN
Solar/Wind Helper
1.207
241974AD2-163_GEN2
Solar/Wind Helper
0.936
270273AD2-016 GEN
Solar/Wind Helper
1.38
960801AF2-371 GEN
Solar/Wind Helper
0.521
964871AG1-351 GEN
Solar/Wind Helper
0.36
3429661SPURLK4G
50/50
7.046
3429571SPURLK1G
50/50
7.13
25197208MELDL3
50/50
0.569
945681AF1-233 GEN
Solar/Wind Harmer
61.301
339216AC1-074 GEN
Solar/Wind Harmer
3.841
943111AE2-339 GEN
Solar/Wind Harmer
1.977
3429421JKCT 10G
Adder
18.466
25196808ZIMRHP
Adder
160.301
3429241JKCT 3G
Adder
24.821
971821AH1-427 GEN
Solar/Wind Harmer
13.653
971565AH1-281 GEN
Solar/Wind Harmer
2.045
339241AF1-083 GEN
Solar/Wind Harmer
1.592
970273AG2-179 GEN
Solar/Wind Harmer
2.255
964901AG1-354 GEN
Solar/Wind Harmer
12.036
971315AH1-136 GEN
Solar/Wind Harmer
1.582
25196008MFTGT1
Adder
1.052
962241AG1-070 GEN
Solar/Wind Harmer
3.274
25194608D.CRK4
Adder
1.11
253343AC1-166 GEN
Solar/Wind Helper
1.288
253325AC1-069 GEN
Solar/Wind Helper
1.335
252507AC2-088 GEN
Solar/Wind Helper
0.98
270263AC1-001 GEN
Solar/Wind Helper
0.509
25197008MELDL1
50/50
0.565
972163AH1-664 GEN
Solar/Wind Harmer
31.627
972165AH1-665 GEN
Solar/Wind Harmer
25.302
339243AC2-075 GEN1
Solar/Wind Harmer
1.04
3429211JKCT 2G
Adder
24.5
339211AE2-254 GEN
Solar/Wind Harmer
2.124
965401AG1-405 GEN
Solar/Wind Harmer
6.938
965411AG1-406 GEN
Solar/Wind Harmer
3.114
970455AG2-298 GEN
Solar/Wind Harmer
6.185
25196108MFTGT2
Adder
1.16
25196108MFTGT2
Adder
1.077
962211AG1-066 GEN
Solar/Wind Harmer
1.705
252524AE2-267 GEN
Solar/Wind Harmer
1.086
25196408WSDLE3
Adder
6.077
25196308WSDLE2
Adder
6.024
25196208WSDLE1
Adder
6.009
25196708WSDLE6
Adder
5.994
25196508WSDLE4
Adder
5.843
970281AG2-184 GEN
Solar/Wind Harmer
9.902
972143AH1-644 GEN
Solar/Wind Harmer
4.715
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.723
270340AC2-060 GEN
Solar/Wind Helper
1.337
270520AE2-214 GEN
Solar/Wind Helper
2.981
241973AD2-163_GEN1
Solar/Wind Helper
0.936
253383AE2-342_GEN
Solar/Wind Helper
0.365
950051AG9-018
External Queue
14.528197288513184
950041AG9-017
External Queue
14.816180229187012
CPLELTFEXP_CPLE->PJM
CLTF
0.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.602
LAGNLTFEXP_LAGN->PJM
CLTF
6.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.13
TVALTFEXP_TVA->PJM
CLTF
3.879
NYPJM->LTFIMP_NY
CLTF
0.784
LGEELTFEXP_LGEE->PJM
CLTF
5.678
WECLTFEXP_WEC->PJM
CLTF
0.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.26
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.536
MECLTFEXP_MEC->PJM
CLTF
4.374
SIGELTFEXP_SIGE->PJM
CLTF
0.293

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.62 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1786.6
MW Contribution:5.07
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.884
25197108MELDL2
50/50
0.698
958171AF2-111 GEN
Solar/Wind Harmer
104.27
972167AH1-666 GEN
Solar/Wind Harmer
29.055
3429391JKCT 9G
Adder
20.047
970093AG2-073 GEN
Solar/Wind Harmer
19.531
966571AG1-526 GEN
Solar/Wind Harmer
36.287
972273AH1-721 GEN
Adder
91.547
970273AG2-179 GEN
Solar/Wind Harmer
3.663
960741AF2-365 GEN
Solar/Wind Harmer
3.824
339250AF1-203 GEN
Solar/Wind Harmer
0.45
971155AH1-034 GEN
Solar/Wind Harmer
7.314
962251AG1-071 GEN
Solar/Wind Harmer
3.909
972103AH1-617 GEN
Solar/Wind Harmer
10.145
25196008MFTGT1
Adder
0.637
253338AC1-165 GEN
Solar/Wind Helper
1.021
253333AC1-068 GEN
Solar/Wind Helper
1.058
253406AD2-031_GEN
Solar/Wind Helper
0.902
253415AE1-040 GEN
Solar/Wind Helper
0.53
241955AC1-078 GEN
Solar/Wind Helper
0.928
3429601SPURLK2G
50/50
15.032
972043AH1-570 GEN
Solar/Wind Harmer
6.036
972045AH1-571 GEN
Solar/Wind Harmer
4.829
971125AH1-004 GEN
Solar/Wind Harmer
9.607
970107AG2-081 GEN
Solar/Wind Harmer
7.205
339221AD2-048_GEN
Solar/Wind Harmer
3.631
960161AF2-307 GEN
Solar/Wind Harmer
14.82
942891AE2-308 GEN
Solar/Wind Harmer
21.118
970235AG2-159 GEN
Solar/Wind Harmer
4.418
970235AG2-159 GEN
Solar/Wind Harmer
2.697
339231AF1-038_GEN
Solar/Wind Harmer
1.721
971081AG2-670 GEN
Solar/Wind Harmer
6.96
970653AG2-424 GEN
Solar/Wind Harmer
4.326
970653AG2-424 GEN
Solar/Wind Harmer
1.564
339236AF1-050_GEN
Solar/Wind Harmer
1.539
964571AG1-320 GEN
Solar/Wind Harmer
6.913
966021AG1-471 GEN
Solar/Wind Harmer
4.369
971485AH1-239 GEN
Solar/Wind Harmer
6.417
339255AE2-071 GEN
Solar/Wind Harmer
0.788
964781AG1-341 GEN
Solar/Wind Harmer
7.607
270186AC1-089 GEN
Solar/Wind Harmer
4.26
253394AE2-221_GEN
Solar/Wind Helper
2.834
253398AE2-221_GEN2
Solar/Wind Helper
2.834
25183208HLCRTG
Solar/Wind Helper
2.94
270518AE2-148 GEN
Solar/Wind Helper
6.991
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
25197008MELDL1
50/50
0.688
972163AH1-664 GEN
Solar/Wind Harmer
35.04
972165AH1-665 GEN
Solar/Wind Harmer
28.032
339243AC2-075 GEN1
Solar/Wind Harmer
1.117
3429211JKCT 2G
Adder
26.517
339211AE2-254 GEN
Solar/Wind Harmer
2.222
965401AG1-405 GEN
Solar/Wind Harmer
7.259
965411AG1-406 GEN
Solar/Wind Harmer
3.258
970455AG2-298 GEN
Solar/Wind Harmer
6.151
962211AG1-066 GEN
Solar/Wind Harmer
1.825
970281AG2-184 GEN
Solar/Wind Harmer
10.652
972143AH1-644 GEN
Solar/Wind Harmer
5.072
25196108MFTGT2
Adder
0.725
25196108MFTGT2
Adder
0.673
945631AF1-228 GEN
Solar/Wind Helper
1.079
270340AC2-060 GEN
Solar/Wind Helper
1.058
270520AE2-214 GEN
Solar/Wind Helper
2.349
241972AD1-140 GEN
Solar/Wind Helper
1.835
3429661SPURLK4G
50/50
7.884
3429571SPURLK1G
50/50
7.938
25197208MELDL3
50/50
0.692
25196808ZIMRHP
50/50
216.474
945681AF1-233 GEN
Solar/Wind Harmer
67.998
339216AC1-074 GEN
Solar/Wind Harmer
4.124
943111AE2-339 GEN
Solar/Wind Harmer
2.139
3429421JKCT 10G
Adder
20.047
3429241JKCT 3G
Adder
26.865
971821AH1-427 GEN
Solar/Wind Harmer
14.261
971565AH1-281 GEN
Solar/Wind Harmer
2.017
339241AF1-083 GEN
Solar/Wind Harmer
1.601
970273AG2-179 GEN
Solar/Wind Harmer
2.293
971315AH1-136 GEN
Solar/Wind Harmer
1.727
964901AG1-354 GEN
Solar/Wind Harmer
11.895
962241AG1-070 GEN
Solar/Wind Harmer
3.198
25196008MFTGT1
Adder
0.658
253343AC1-166 GEN
Solar/Wind Helper
1.021
253325AC1-069 GEN
Solar/Wind Helper
1.058
252507AC2-088 GEN
Solar/Wind Helper
0.737
950051AG9-018
External Queue
17.501935958862305
950041AG9-017
External Queue
17.643001556396484
CPLELTFEXP_CPLE->PJM
CLTF
0.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.16
TVALTFEXP_TVA->PJM
CLTF
3.662
NYPJM->LTFIMP_NY
CLTF
0.663
LGEELTFEXP_LGEE->PJM
CLTF
5.148
WECLTFEXP_WEC->PJM
CLTF
0.587
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.428
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.346
MECLTFEXP_MEC->PJM
CLTF
3.54
SIGELTFEXP_SIGE->PJM
CLTF
0.254

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.28 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1766.12
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.702
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.126
270518AE2-148 GEN
Solar/Wind Helper
5.923
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.877
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.272
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.684
945681AF1-233 GEN
Solar/Wind Harmer
69.569
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.88
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.44816780090332
950041AG9-017
External Queue
18.620590209960938
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.381
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.082
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1765.38
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.7
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.075
970235AG2-159 GEN
Solar/Wind Harmer
2.488
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.826
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.672
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.303
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.383
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.924
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.876
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.701
966571AG1-526 GEN
Solar/Wind Harmer
36.35
972273AH1-721 GEN
Adder
91.003
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.707
339250AF1-203 GEN
Solar/Wind Harmer
0.438
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.666
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.143
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.202
971821AH1-427 GEN
Solar/Wind Harmer
14.224
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.595
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.878
971155AH1-034 GEN
Solar/Wind Harmer
7.11
962251AG1-071 GEN
Solar/Wind Harmer
3.79
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.835
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.248
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.011
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.448036193847656
950041AG9-017
External Queue
18.620628356933594
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.378
LAGNLTFEXP_LAGN->PJM
CLTF
5.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.081
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.827
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.496
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.19 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.77
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3429601SPURLK2G
50/50
15.433
972043AH1-570 GEN
Solar/Wind Harmer
6.099
972045AH1-571 GEN
Solar/Wind Harmer
4.879
971125AH1-004 GEN
Solar/Wind Harmer
9.702
970107AG2-081 GEN
Solar/Wind Harmer
7.276
339221AD2-048_GEN
Solar/Wind Harmer
3.656
960161AF2-307 GEN
Solar/Wind Harmer
15.079
942891AE2-308 GEN
Solar/Wind Harmer
21.337
970235AG2-159 GEN
Solar/Wind Harmer
4.079
970235AG2-159 GEN
Solar/Wind Harmer
2.49
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.828
970653AG2-424 GEN
Solar/Wind Harmer
4.209
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.505
964571AG1-320 GEN
Solar/Wind Harmer
6.674
966021AG1-471 GEN
Solar/Wind Harmer
4.297
971485AH1-239 GEN
Solar/Wind Harmer
6.305
270186AC1-089 GEN
Solar/Wind Harmer
4.704
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.385
253394AE2-221_GEN
Solar/Wind Helper
2.6
253398AE2-221_GEN2
Solar/Wind Helper
2.6
25183208HLCRTG
Solar/Wind Helper
2.512
252509AD1-136 GEN
Solar/Wind Helper
0.127
270518AE2-148 GEN
Solar/Wind Helper
5.922
3429631SPURLK3G
50/50
8.094
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.883
972167AH1-666 GEN
Solar/Wind Harmer
29.73
3429391JKCT 9G
Adder
20.327
970093AG2-073 GEN
Solar/Wind Harmer
19.704
966571AG1-526 GEN
Solar/Wind Harmer
36.357
972273AH1-721 GEN
Adder
91.022
970273AG2-179 GEN
Solar/Wind Harmer
3.616
960741AF2-365 GEN
Solar/Wind Harmer
3.709
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.112
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.273
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429661SPURLK4G
50/50
8.094
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.74
25196808ZIMRHP
50/50
235.719
945681AF1-233 GEN
Solar/Wind Harmer
69.574
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.165
3429421JKCT 10G
Adder
20.327
3429241JKCT 3G
Adder
27.206
971821AH1-427 GEN
Solar/Wind Harmer
14.227
971565AH1-281 GEN
Solar/Wind Harmer
1.966
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.264
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.598
962241AG1-070 GEN
Solar/Wind Harmer
3.102
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.886
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.838
972165AH1-665 GEN
Solar/Wind Harmer
28.67
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.853
339211AE2-254 GEN
Solar/Wind Harmer
2.218
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.254
970455AG2-298 GEN
Solar/Wind Harmer
6.013
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.786
972143AH1-644 GEN
Solar/Wind Harmer
5.136
945631AF1-228 GEN
Solar/Wind Helper
0.946
950051AG9-018
External Queue
18.447389602661133
950041AG9-017
External Queue
18.62034034729004
CPLELTFEXP_CPLE->PJM
CLTF
0.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.402
LAGNLTFEXP_LAGN->PJM
CLTF
5.885
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.08
TVALTFEXP_TVA->PJM
CLTF
3.49
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.829
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.502
MECLTFEXP_MEC->PJM
CLTF
3.084
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.16 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1764.32
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
35.834
972165AH1-665 GEN
Solar/Wind Harmer
28.668
339243AC2-075 GEN1
Solar/Wind Harmer
1.122
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
2.217
965401AG1-405 GEN
Solar/Wind Harmer
7.249
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
6.012
962211AG1-066 GEN
Solar/Wind Harmer
1.843
970281AG2-184 GEN
Solar/Wind Harmer
10.787
972143AH1-644 GEN
Solar/Wind Harmer
5.137
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
6.098
972045AH1-571 GEN
Solar/Wind Harmer
4.878
971125AH1-004 GEN
Solar/Wind Harmer
9.701
970107AG2-081 GEN
Solar/Wind Harmer
7.275
339221AD2-048_GEN
Solar/Wind Harmer
3.655
960161AF2-307 GEN
Solar/Wind Harmer
15.078
942891AE2-308 GEN
Solar/Wind Harmer
21.334
970235AG2-159 GEN
Solar/Wind Harmer
4.078
970235AG2-159 GEN
Solar/Wind Harmer
2.489
339231AF1-038_GEN
Solar/Wind Harmer
1.699
971081AG2-670 GEN
Solar/Wind Harmer
6.827
970653AG2-424 GEN
Solar/Wind Harmer
4.208
970653AG2-424 GEN
Solar/Wind Harmer
1.521
339236AF1-050_GEN
Solar/Wind Harmer
1.504
964571AG1-320 GEN
Solar/Wind Harmer
6.673
966021AG1-471 GEN
Solar/Wind Harmer
4.296
971485AH1-239 GEN
Solar/Wind Harmer
6.304
270186AC1-089 GEN
Solar/Wind Harmer
4.703
339255AE2-071 GEN
Solar/Wind Harmer
0.767
964781AG1-341 GEN
Solar/Wind Harmer
7.384
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
106.873
972167AH1-666 GEN
Solar/Wind Harmer
29.728
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
19.702
966571AG1-526 GEN
Solar/Wind Harmer
36.352
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.615
960741AF2-365 GEN
Solar/Wind Harmer
3.708
339250AF1-203 GEN
Solar/Wind Harmer
0.438
971155AH1-034 GEN
Solar/Wind Harmer
7.111
962251AG1-071 GEN
Solar/Wind Harmer
3.791
972103AH1-617 GEN
Solar/Wind Harmer
10.274
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
69.568
339216AC1-074 GEN
Solar/Wind Harmer
4.144
943111AE2-339 GEN
Solar/Wind Harmer
2.164
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
14.225
971565AH1-281 GEN
Solar/Wind Harmer
1.965
339241AF1-083 GEN
Solar/Wind Harmer
1.573
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.759
964901AG1-354 GEN
Solar/Wind Harmer
11.596
962241AG1-070 GEN
Solar/Wind Harmer
3.101
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
950051AG9-018
External Queue
18.446699142456055
950041AG9-017
External Queue
18.61962890625
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.67 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1421.95
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.485
25197108MELDL2
50/50
0.555
958171AF2-111 GEN
Solar/Wind Harmer
69.07
972167AH1-666 GEN
Solar/Wind Harmer
19.252
3429391JKCT 9G
Adder
19.034
970093AG2-073 GEN
Solar/Wind Harmer
12.938
966571AG1-526 GEN
Solar/Wind Harmer
24.04
972273AH1-721 GEN
Adder
86.897
970273AG2-179 GEN
Solar/Wind Harmer
3.732
960741AF2-365 GEN
Solar/Wind Harmer
2.535
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.654
962251AG1-071 GEN
Solar/Wind Harmer
2.943
972103AH1-617 GEN
Solar/Wind Harmer
6.68
25196008MFTGT1
Adder
0.603
3429601SPURLK2G
50/50
14.272
972043AH1-570 GEN
Solar/Wind Harmer
4.16
972045AH1-571 GEN
Solar/Wind Harmer
3.333
971125AH1-004 GEN
Solar/Wind Harmer
6.363
970107AG2-081 GEN
Solar/Wind Harmer
4.772
339221AD2-048_GEN
Solar/Wind Harmer
0.009
960161AF2-307 GEN
Solar/Wind Harmer
10.094
942891AE2-308 GEN
Solar/Wind Harmer
13.99
970235AG2-159 GEN
Solar/Wind Harmer
4.442
970235AG2-159 GEN
Solar/Wind Harmer
2.549
971081AG2-670 GEN
Solar/Wind Harmer
4.612
970653AG2-424 GEN
Solar/Wind Harmer
2.868
970653AG2-424 GEN
Solar/Wind Harmer
1.486
964571AG1-320 GEN
Solar/Wind Harmer
5.107
966021AG1-471 GEN
Solar/Wind Harmer
2.893
971485AH1-239 GEN
Solar/Wind Harmer
4.249
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.081
964781AG1-341 GEN
Solar/Wind Harmer
5.04
253394AE2-221_GEN
Solar/Wind Helper
2.805
253398AE2-221_GEN2
Solar/Wind Helper
2.805
25183208HLCRTG
Solar/Wind Helper
2.661
270518AE2-148 GEN
Solar/Wind Helper
6.187
252509AD1-136 GEN
Solar/Wind Helper
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.28
3429661SPURLK4G
50/50
7.485
3429571SPURLK1G
50/50
7.538
25197208MELDL3
50/50
0.55
945681AF1-233 GEN
Solar/Wind Harmer
45.056
339216AC1-074 GEN
Solar/Wind Harmer
0.445
3429421JKCT 10G
Adder
19.034
3429241JKCT 3G
Adder
25.509
25196808ZIMRHP
Adder
146.521
971821AH1-427 GEN
Solar/Wind Harmer
9.447
971565AH1-281 GEN
Solar/Wind Harmer
1.338
970273AG2-179 GEN
Solar/Wind Harmer
2.177
971315AH1-136 GEN
Solar/Wind Harmer
1.141
964901AG1-354 GEN
Solar/Wind Harmer
7.882
962241AG1-070 GEN
Solar/Wind Harmer
2.566
25196008MFTGT1
Adder
0.622
253343AC1-166 GEN
Solar/Wind Helper
1.014
253325AC1-069 GEN
Solar/Wind Helper
1.051
252507AC2-088 GEN
Solar/Wind Helper
0.746
253338AC1-165 GEN
Solar/Wind Helper
1.014
253333AC1-068 GEN
Solar/Wind Helper
1.051
253406AD2-031_GEN
Solar/Wind Helper
0.849
253415AE1-040 GEN
Solar/Wind Helper
0.499
25197008MELDL1
50/50
0.547
972163AH1-664 GEN
Solar/Wind Harmer
25.851
972165AH1-665 GEN
Solar/Wind Harmer
20.704
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
25.178
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
4.808
965411AG1-406 GEN
Solar/Wind Harmer
3.093
970455AG2-298 GEN
Solar/Wind Harmer
4.531
970281AG2-184 GEN
Solar/Wind Harmer
7.014
972143AH1-644 GEN
Solar/Wind Harmer
3.618
25196108MFTGT2
Adder
0.686
25196108MFTGT2
Adder
0.637
945631AF1-228 GEN
Solar/Wind Helper
0.994
270340AC2-060 GEN
Solar/Wind Helper
0.992
270520AE2-214 GEN
Solar/Wind Helper
2.234
950051AG9-018
External Queue
16.609764099121094
950041AG9-017
External Queue
16.814743041992188
CPLELTFEXP_CPLE->PJM
CLTF
0.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.046
LAGNLTFEXP_LAGN->PJM
CLTF
5.94
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.879
TVALTFEXP_TVA->PJM
CLTF
3.468
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
4.904
WECLTFEXP_WEC->PJM
CLTF
0.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.508
MECLTFEXP_MEC->PJM
CLTF
3.38
SIGELTFEXP_SIGE->PJM
CLTF
0.241

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.33 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1751.58
MW Contribution:6.23
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
43.05
972165AH1-665 GEN
Solar/Wind Harmer
34.44
339243AC2-075 GEN1
Solar/Wind Harmer
1.319
3429211JKCT 2G
Adder
31.785
339211AE2-254 GEN
Solar/Wind Harmer
2.566
965401AG1-405 GEN
Solar/Wind Harmer
8.401
965411AG1-406 GEN
Solar/Wind Harmer
3.77
970455AG2-298 GEN
Solar/Wind Harmer
6.693
962211AG1-066 GEN
Solar/Wind Harmer
2.199
970281AG2-184 GEN
Solar/Wind Harmer
13.084
972143AH1-644 GEN
Solar/Wind Harmer
6.23
945631AF1-228 GEN
Solar/Wind Helper
0.914
3429601SPURLK2G
50/50
18.64
972043AH1-570 GEN
Solar/Wind Harmer
7.203
972045AH1-571 GEN
Solar/Wind Harmer
5.763
971125AH1-004 GEN
Solar/Wind Harmer
11.455
970107AG2-081 GEN
Solar/Wind Harmer
8.591
960161AF2-307 GEN
Solar/Wind Harmer
17.988
339221AD2-048_GEN
Solar/Wind Harmer
4.301
942891AE2-308 GEN
Solar/Wind Harmer
25.169
339231AF1-038_GEN
Solar/Wind Harmer
1.932
970235AG2-159 GEN
Solar/Wind Harmer
4.251
970235AG2-159 GEN
Solar/Wind Harmer
2.595
971081AG2-670 GEN
Solar/Wind Harmer
7.662
970653AG2-424 GEN
Solar/Wind Harmer
4.644
970653AG2-424 GEN
Solar/Wind Harmer
1.679
339236AF1-050_GEN
Solar/Wind Harmer
1.678
270186AC1-089 GEN
Solar/Wind Harmer
5.494
966021AG1-471 GEN
Solar/Wind Harmer
4.857
971485AH1-239 GEN
Solar/Wind Harmer
7.111
964571AG1-320 GEN
Solar/Wind Harmer
7.25
339255AE2-071 GEN
Solar/Wind Harmer
0.849
964781AG1-341 GEN
Solar/Wind Harmer
8.139
971225AH1-072 GEN
Solar/Wind Harmer
0.888
971227AH1-073 GEN
Solar/Wind Harmer
0.888
253394AE2-221_GEN
Solar/Wind Helper
2.179
253398AE2-221_GEN2
Solar/Wind Helper
2.179
25183208HLCRTG
Solar/Wind Helper
2.409
252509AD1-136 GEN
Solar/Wind Helper
0.141
270518AE2-148 GEN
Solar/Wind Helper
6.059
3429631SPURLK3G
50/50
9.776
958171AF2-111 GEN
Solar/Wind Harmer
128.804
972167AH1-666 GEN
Solar/Wind Harmer
35.741
3429391JKCT 9G
Adder
24.103
970093AG2-073 GEN
Solar/Wind Harmer
23.192
966571AG1-526 GEN
Solar/Wind Harmer
42.302
972273AH1-721 GEN
Adder
104.752
970273AG2-179 GEN
Solar/Wind Harmer
4.108
960741AF2-365 GEN
Solar/Wind Harmer
4.073
339250AF1-203 GEN
Solar/Wind Harmer
0.485
971155AH1-034 GEN
Solar/Wind Harmer
7.86
962251AG1-071 GEN
Solar/Wind Harmer
4.17
972103AH1-617 GEN
Solar/Wind Harmer
12.461
971461AH1-227 GEN
Solar/Wind Harmer
2.276
253338AC1-165 GEN
Solar/Wind Helper
0.792
253333AC1-068 GEN
Solar/Wind Helper
0.821
253406AD2-031_GEN
Solar/Wind Helper
0.679
253415AE1-040 GEN
Solar/Wind Helper
0.403
3429661SPURLK4G
50/50
9.776
3429571SPURLK1G
50/50
9.792
945681AF1-233 GEN
Solar/Wind Harmer
83.633
339216AC1-074 GEN
Solar/Wind Harmer
4.873
943111AE2-339 GEN
Solar/Wind Harmer
2.561
3429421JKCT 10G
Adder
24.103
3429241JKCT 3G
Adder
32.202
971821AH1-427 GEN
Solar/Wind Harmer
16.445
971565AH1-281 GEN
Solar/Wind Harmer
2.174
339241AF1-083 GEN
Solar/Wind Harmer
1.77
971315AH1-136 GEN
Solar/Wind Harmer
2.127
970273AG2-179 GEN
Solar/Wind Harmer
2.572
964901AG1-354 GEN
Solar/Wind Harmer
12.878
962241AG1-070 GEN
Solar/Wind Harmer
3.411
971687AH1-348 GEN
Solar/Wind Harmer
0.46
253343AC1-166 GEN
Solar/Wind Helper
0.792
253325AC1-069 GEN
Solar/Wind Helper
0.821
252507AC2-088 GEN
Solar/Wind Helper
0.99
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
950041AG9-017
External Queue
23.331375122070312
CPLELTFEXP_CPLE->PJM
CLTF
1.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.92
LAGNLTFEXP_LAGN->PJM
CLTF
6.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.96
TVALTFEXP_TVA->PJM
CLTF
3.754
NYPJM->LTFIMP_NY
CLTF
0.539
LGEELTFEXP_LGEE->PJM
CLTF
4.945
WECLTFEXP_WEC->PJM
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.097
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.429
MECLTFEXP_MEC->PJM
CLTF
2.587
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1613.52
MW Contribution:4.68
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
9.77
3429661SPURLK4G
50/50
9.77
25197208MELDL3
50/50
1.274
3429571SPURLK1G
50/50
9.786
945681AF1-233 GEN
Solar/Wind Harmer
58.303
339216AC1-074 GEN
Solar/Wind Harmer
0.553
3429421JKCT 10G
Adder
24.075
3429241JKCT 3G
Adder
32.161
971821AH1-427 GEN
Solar/Wind Harmer
11.449
971565AH1-281 GEN
Solar/Wind Harmer
1.512
971315AH1-136 GEN
Solar/Wind Harmer
1.479
970273AG2-179 GEN
Solar/Wind Harmer
2.564
964901AG1-354 GEN
Solar/Wind Harmer
8.949
962241AG1-070 GEN
Solar/Wind Harmer
2.87
971687AH1-348 GEN
Solar/Wind Harmer
0.319
253343AC1-166 GEN
Solar/Wind Helper
0.796
253325AC1-069 GEN
Solar/Wind Helper
0.825
252507AC2-088 GEN
Solar/Wind Helper
0.996
3429601SPURLK2G
50/50
18.629
972043AH1-570 GEN
Solar/Wind Harmer
5.22
972045AH1-571 GEN
Solar/Wind Harmer
4.183
971125AH1-004 GEN
Solar/Wind Harmer
7.982
970107AG2-081 GEN
Solar/Wind Harmer
5.987
960161AF2-307 GEN
Solar/Wind Harmer
12.886
339221AD2-048_GEN
Solar/Wind Harmer
0.012
942891AE2-308 GEN
Solar/Wind Harmer
17.536
970235AG2-159 GEN
Solar/Wind Harmer
4.508
970235AG2-159 GEN
Solar/Wind Harmer
2.587
971081AG2-670 GEN
Solar/Wind Harmer
5.327
970653AG2-424 GEN
Solar/Wind Harmer
3.229
970653AG2-424 GEN
Solar/Wind Harmer
1.673
270186AC1-089 GEN
Solar/Wind Harmer
0.004
966021AG1-471 GEN
Solar/Wind Harmer
3.376
971485AH1-239 GEN
Solar/Wind Harmer
4.942
964571AG1-320 GEN
Solar/Wind Harmer
5.612
339255AE2-071 GEN
Solar/Wind Harmer
-0.091
964781AG1-341 GEN
Solar/Wind Harmer
5.653
971225AH1-072 GEN
Solar/Wind Harmer
0.614
971227AH1-073 GEN
Solar/Wind Harmer
0.614
253394AE2-221_GEN
Solar/Wind Helper
2.185
253398AE2-221_GEN2
Solar/Wind Helper
2.185
25183208HLCRTG
Solar/Wind Helper
2.418
252509AD1-136 GEN
Solar/Wind Helper
0.142
270518AE2-148 GEN
Solar/Wind Helper
6.102
25197008MELDL1
50/50
1.267
972163AH1-664 GEN
Solar/Wind Harmer
33.413
972165AH1-665 GEN
Solar/Wind Harmer
26.76
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
31.745
339211AE2-254 GEN
Solar/Wind Harmer
0.005
965401AG1-405 GEN
Solar/Wind Harmer
5.847
965411AG1-406 GEN
Solar/Wind Harmer
3.762
970455AG2-298 GEN
Solar/Wind Harmer
5.173
970281AG2-184 GEN
Solar/Wind Harmer
9.078
972143AH1-644 GEN
Solar/Wind Harmer
4.683
945631AF1-228 GEN
Solar/Wind Helper
0.92
25197108MELDL2
50/50
1.285
958171AF2-111 GEN
Solar/Wind Harmer
89.804
972167AH1-666 GEN
Solar/Wind Harmer
24.916
3429391JKCT 9G
Adder
24.075
970093AG2-073 GEN
Solar/Wind Harmer
16.156
966571AG1-526 GEN
Solar/Wind Harmer
29.46
972273AH1-721 GEN
Adder
104.468
970273AG2-179 GEN
Solar/Wind Harmer
4.395
960741AF2-365 GEN
Solar/Wind Harmer
2.829
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
6.37
962251AG1-071 GEN
Solar/Wind Harmer
3.291
972103AH1-617 GEN
Solar/Wind Harmer
8.646
971461AH1-227 GEN
Solar/Wind Harmer
1.576
253338AC1-165 GEN
Solar/Wind Helper
0.796
253333AC1-068 GEN
Solar/Wind Helper
0.825
253406AD2-031_GEN
Solar/Wind Helper
0.683
253415AE1-040 GEN
Solar/Wind Helper
0.407
950011AG9-010
External Queue
6.113064289093018
950051AG9-018
External Queue
23.248964309692383
950041AG9-017
External Queue
23.331375122070312
CPLELTFEXP_CPLE->PJM
CLTF
1.169
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.457
LAGNLTFEXP_LAGN->PJM
CLTF
6.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.856
TVALTFEXP_TVA->PJM
CLTF
3.719
NYPJM->LTFIMP_NY
CLTF
0.561
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.318
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.299
MECLTFEXP_MEC->PJM
CLTF
2.529
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A


Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1592.57
MW Contribution:3.88
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
8.093
3429571SPURLK1G
50/50
8.131
3429601SPURLK2G
50/50
15.432
972043AH1-570 GEN
Solar/Wind Harmer
4.425
972045AH1-571 GEN
Solar/Wind Harmer
3.545
971125AH1-004 GEN
Solar/Wind Harmer
6.768
970107AG2-081 GEN
Solar/Wind Harmer
5.076
339221AD2-048_GEN
Solar/Wind Harmer
0.01
960161AF2-307 GEN
Solar/Wind Harmer
10.815
942891AE2-308 GEN
Solar/Wind Harmer
14.884
970235AG2-159 GEN
Solar/Wind Harmer
4.339
970235AG2-159 GEN
Solar/Wind Harmer
2.489
971081AG2-670 GEN
Solar/Wind Harmer
4.763
970653AG2-424 GEN
Solar/Wind Harmer
2.936
970653AG2-424 GEN
Solar/Wind Harmer
1.521
964571AG1-320 GEN
Solar/Wind Harmer
5.185
966021AG1-471 GEN
Solar/Wind Harmer
2.997
971485AH1-239 GEN
Solar/Wind Harmer
4.398
270186AC1-089 GEN
Solar/Wind Harmer
0.003
339255AE2-071 GEN
Solar/Wind Harmer
-0.083
964781AG1-341 GEN
Solar/Wind Harmer
5.152
253394AE2-221_GEN
Solar/Wind Helper
2.601
253398AE2-221_GEN2
Solar/Wind Helper
2.601
25183208HLCRTG
Solar/Wind Helper
2.511
252509AD1-136 GEN
Solar/Wind Helper
0.125
270518AE2-148 GEN
Solar/Wind Helper
5.925
25197008MELDL1
50/50
0.735
972163AH1-664 GEN
Solar/Wind Harmer
27.834
972165AH1-665 GEN
Solar/Wind Harmer
22.292
339243AC2-075 GEN1
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
26.85
339211AE2-254 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
5.057
965411AG1-406 GEN
Solar/Wind Harmer
3.253
970455AG2-298 GEN
Solar/Wind Harmer
4.66
970281AG2-184 GEN
Solar/Wind Harmer
7.526
972143AH1-644 GEN
Solar/Wind Harmer
3.883
945631AF1-228 GEN
Solar/Wind Helper
0.946
3429631SPURLK3G
50/50
8.093
25197108MELDL2
50/50
0.746
958171AF2-111 GEN
Solar/Wind Harmer
74.563
972167AH1-666 GEN
Solar/Wind Harmer
20.74
3429391JKCT 9G
Adder
20.324
970093AG2-073 GEN
Solar/Wind Harmer
13.746
966571AG1-526 GEN
Solar/Wind Harmer
25.362
972273AH1-721 GEN
Adder
91.009
970273AG2-179 GEN
Solar/Wind Harmer
3.88
960741AF2-365 GEN
Solar/Wind Harmer
2.587
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
5.788
962251AG1-071 GEN
Solar/Wind Harmer
3.005
972103AH1-617 GEN
Solar/Wind Harmer
7.168
253338AC1-165 GEN
Solar/Wind Helper
0.943
253333AC1-068 GEN
Solar/Wind Helper
0.977
253406AD2-031_GEN
Solar/Wind Helper
0.781
253415AE1-040 GEN
Solar/Wind Helper
0.462
25197208MELDL3
50/50
0.739
25196808ZIMRHP
50/50
235.624
945681AF1-233 GEN
Solar/Wind Harmer
48.536
339216AC1-074 GEN
Solar/Wind Harmer
0.471
3429421JKCT 10G
Adder
20.324
3429241JKCT 3G
Adder
27.203
971821AH1-427 GEN
Solar/Wind Harmer
9.925
971565AH1-281 GEN
Solar/Wind Harmer
1.371
970273AG2-179 GEN
Solar/Wind Harmer
2.263
971315AH1-136 GEN
Solar/Wind Harmer
1.227
964901AG1-354 GEN
Solar/Wind Harmer
8.09
962241AG1-070 GEN
Solar/Wind Harmer
2.621
253343AC1-166 GEN
Solar/Wind Helper
0.943
253325AC1-069 GEN
Solar/Wind Helper
0.977
252507AC2-088 GEN
Solar/Wind Helper
0.876
950051AG9-018
External Queue
18.446699142456055
950041AG9-017
External Queue
18.61962890625
CPLELTFEXP_CPLE->PJM
CLTF
0.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.382
LAGNLTFEXP_LAGN->PJM
CLTF
5.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.082
TVALTFEXP_TVA->PJM
CLTF
3.489
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
4.828
WECLTFEXP_WEC->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.499
MECLTFEXP_MEC->PJM
CLTF
3.081
SIGELTFEXP_SIGE->PJM
CLTF
0.231

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#10180_05BROADF 138_H_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10180_05BROADF 138_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.41 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:309.07
MW Contribution:4.7
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.855
971313AH1-133 GEN
Solar/Wind Harmer
41.811
24734705WLF1G3
Adder
6.633
24734805WLF1G4
Adder
6.633
24734905WLF1G5
Adder
6.633
24735105WLF2G1
Adder
4.797
970281AG2-184 GEN
Solar/Wind Harmer
9.876
972143AH1-644 GEN
Solar/Wind Harmer
4.703
24289905CRG1H
50/50
0.993
971225AH1-072 GEN
Solar/Wind Harmer
1.518
971227AH1-073 GEN
Solar/Wind Harmer
1.518
970563AG2-360 GEN
50/50
67.236
24689505VACITY
50/50
4.956
24290105CRG2H
50/50
1.019
971461AH1-227 GEN
Solar/Wind Harmer
3.894
972103AH1-617 GEN
Solar/Wind Harmer
9.406
24290005CRG1L
50/50
0.834
24735205WLF2G2
Adder
4.797
971687AH1-348 GEN
Solar/Wind Harmer
0.737
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.705
TVALTFEXP_TVA->PJM
CLTF
1.237
NYPJM->LTFIMP_NY
CLTF
0.119
LGEELTFEXP_LGEE->PJM
CLTF
0.364
WECLTFEXP_WEC->PJM
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.168
MECLTFEXP_MEC->PJM
CLTF
0.758
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CONTINGENCY 'AEP_P4_#10335_05SALTV2 138_U_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242789 CKT 1    /*05BROADF     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 242789 CKT 1    /*05MEADWV     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
 OPEN BRANCH FROM BUS 242789 TO BUS 243269 CKT 1    /*05SALTV2     138.0 - 05SALTVL 1EQ   1.0
 OPEN BRANCH FROM BUS 242885 TO BUS 243269 CKT 1    /*05SALTVILL    69.0 - 05SALTVL 1EQ   1.0
 OPEN BRANCH FROM BUS 243269 TO BUS 243503 CKT 1    /*05SALTVL 1EQ   1.0 - 05SALTVL T1   34.5
END
CONTINGENCY 'AEP_P4_#6173_05CLNCHR 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 242605 TO BUS 242700 CKT 1   /*05CLNCHR     138.0 - 05LEBANO     138.0
 OPEN BRANCH FROM BUS 242635 TO BUS 246766 CKT 1   /*05ELKGARDN   138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242700 TO BUS 244243 CKT 1   /*05LEBANO     138.0 - 05LEBANON     12.0
 OPEN BRANCH FROM BUS 242700 TO BUS 246766 CKT 1   /*05LEBANO     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1   /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
END
CONTINGENCY 'AEP_P4_#10332_05SALTV1 138_A_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242700 CKT 1    /*05CLNCHR     138.0 - 05LEBANO     138.0
 OPEN BRANCH FROM BUS 242635 TO BUS 246766 CKT 1    /*05ELKGARDN   138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242700 TO BUS 244243 CKT 1    /*05LEBANO     138.0 - 05LEBANON     12.0
 OPEN BRANCH FROM BUS 242700 TO BUS 246766 CKT 1    /*05LEBANO     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
END
CONTINGENCY 'AEP_P7-1_#16933___SRT-A'
 OPEN BRANCH FROM BUS 242605 TO BUS 242615 CKT 1   /*05CLNCHR     138.0 - 05COPPER     138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242793 CKT 1   /*05CLNCHR     138.0 - 05SEXTON     138.0
 OPEN BRANCH FROM BUS 242615 TO BUS 242667 CKT 1   /*05COPPER     138.0 - 05HILL       138.0
 OPEN BRANCH FROM BUS 242624 TO BUS 242793 CKT 1   /*05DICKEN     138.0 - 05SEXTON     138.0
 OPEN BRANCH FROM BUS 242793 TO BUS 245220 CKT 1   /*05SEXTON     138.0 - 05W.KINGSPT2 138.0
END
CONTINGENCY 'AEP_P4_#10330_05SALTV1 138_C_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
END
CONTINGENCY 'AEP_P2-2_#10330_05SALTV1 138_1_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
END
CONTINGENCY 'AEP_P4_#9173_05BROADF 765_P_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 290612 CKT Z1   /*05BAKER      765.0 - 05BAKER_RB   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6    /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290613 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RB 765.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6    /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1    /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6    /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
 OPEN BRANCH FROM BUS 290612 TO BUS 290613 CKT 1    /*05BAKER_RB   765.0 - 05BROADFR_RB 765.0
END
CONTINGENCY 'AEP_P7-1_#10868___SRT-SL'
 OPEN BRANCH FROM BUS 242533 TO BUS 242693 CKT 1   /*05ABINGD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 290135 CKT 1   /*05BROADF     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242665 CKT 1   /*05CLNCHR     138.0 - 05HANSON     138.0
 OPEN BRANCH FROM BUS 242665 TO BUS 242714 CKT 1   /*05HANSON     138.0 - 05MEADWV     138.0
 OPEN BRANCH FROM BUS 242692 TO BUS 242693 CKT 1   /*05KEYWOD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242693 TO BUS 290135 CKT 1   /*05KEYWSS     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 242789 CKT 1   /*05MEADWV     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 290185 CKT 2   /*05MEADWV     138.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244241 CKT 1   /*05MEADWVW     69.0 - 05HILLMAN     69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244268 CKT 1   /*05MEADWVW     69.0 - 05MEDALLIN    69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 290185 CKT 2   /*05MEADWVW     69.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 290184 TO BUS 290185 CKT 2   /*05MEADWVW T2  13.1 - 05MEADWVW2EQ 999.0
END
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#16061_05GARRETT 138_CB2_SRT-A'
 OPEN BRANCH FROM BUS 243875 TO BUS 247897 CKT 1    /*05SOFTSH     138.0 - 05SNAG FK SS 138.0
 OPEN BRANCH FROM BUS 246557 TO BUS 247897 CKT 1    /*05GARRETT    138.0 - 05SNAG FK SS 138.0
 OPEN BRANCH FROM BUS 246557 TO BUS 247921 CKT 1    /*05GARRETT    138.0 - 05EASTERN    138.0
 OPEN BRANCH FROM BUS 247897 TO BUS 342218 CKT Z1   /*05SNAG FK SS 138.0 - 4SALT LICK   138.0
END
CONTINGENCY 'AEP_P4_#16060_05GARRETT 138_CB1_SRT-A'
 OPEN BRANCH FROM BUS 243875 TO BUS 247897 CKT 1    /*05SOFTSH     138.0 - 05SNAG FK SS 138.0
 OPEN BRANCH FROM BUS 246557 TO BUS 247897 CKT 1    /*05GARRETT    138.0 - 05SNAG FK SS 138.0
 OPEN BRANCH FROM BUS 247897 TO BUS 342218 CKT Z1   /*05SNAG FK SS 138.0 - 4SALT LICK   138.0
 REMOVE LOAD D1 FROM BUS 246557                     /*05GARRETT    138.0
END
CONTINGENCY 'AEP_P4_#16062_05GARRETT 138_CB3_SRT-A'
 OPEN BRANCH FROM BUS 246557 TO BUS 247921 CKT 1   /*05GARRETT    138.0 - 05EASTERN    138.0
 REMOVE LOAD D1 FROM BUS 246557                    /*05GARRETT    138.0
END
CONTINGENCY 'AEP_P2-2_#16057_Q5EASTERN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 243691 TO BUS 247921 CKT 1   /*05HAYSBR     138.0 - 05EASTERN    138.0
 OPEN BRANCH FROM BUS 243698 TO BUS 247921 CKT 1   /*05MORGFK     138.0 - 05EASTERN    138.0
 OPEN BRANCH FROM BUS 246557 TO BUS 247921 CKT 1   /*05GARRETT    138.0 - 05EASTERN    138.0
END
CONTINGENCY 'AEP_P4_#16063_Q5EASTERN 138_CB1_SRT-A'
 OPEN BRANCH FROM BUS 243691 TO BUS 247921 CKT 1   /*05HAYSBR     138.0 - 05EASTERN    138.0
 OPEN BRANCH FROM BUS 243698 TO BUS 247921 CKT 1   /*05MORGFK     138.0 - 05EASTERN    138.0
 OPEN BRANCH FROM BUS 246557 TO BUS 247921 CKT 1   /*05GARRETT    138.0 - 05EASTERN    138.0
END
CONTINGENCY 'AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A'
 DISCONNECT BRANCH FROM BUS 972103 TO BUS 243689 CKT Z1   /*AH1-617 GEN  138.0 - 05HARBER     138.0
END
CONTINGENCY 'AEP_P4_#1375_05BROADF 765_P2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6   /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6   /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1   /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6   /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
CONTINGENCY 'DEOK_P1_ZIMMER-MELDAHL 34576_SRT-A'
 OPEN BRANCH FROM BUS 249577 TO BUS 249581 CKT 1   /*08ZIMER      345.0 - 08MELDAL     345.0
END
CONTINGENCY 'DEOK_P1_RED BANK-SILVER GROVE-ZIMMER 4545_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'AEP_P4_#10180_05BROADF 138_H_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290420 CKT 5   /*05BROADF     765.0 - 05BROADFD5EQ   1.0
 OPEN BRANCH FROM BUS 242566 TO BUS 290151 CKT 1   /*05BROADF     138.0 - 05SALMON     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 290420 CKT 5   /*05BROADF     138.0 - 05BROADFD5EQ   1.0
 OPEN BRANCH FROM BUS 290420 TO BUS 290421 CKT 5   /*05BROADFD5EQ   1.0 - 05BROADFD T5  13.8
END
242605 to 242533 ckt 1
242605 to 242700 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243683 to 243671 ckt 1
243689 to 243875 ckt 1
242700 to 246766 ckt 1
242516 to 242920 ckt 1
243875 to 243683 ckt 1
342838 to 253077 ckt 1
971312 to 242827 ckt 1

Winter Peak Analysis

The New Service Request AH1-644 was evaluated as a 100.0 MW (65.0 MW Capacity) injection in the AEP area.

AH1-644 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-644 was evaluated as a 100.0 MW injection

AH1-644 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC151.72 %184.0A279.1755.0

Details for 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.72 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:279.17
MW Contribution:55.0
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
115.5
972103AH1-617 GEN
Solar/Wind Harmer
110
972143AH1-644 GEN
Solar/Wind Harmer
55
243689 to 243875 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-214Cole 345 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Study Pending
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-644 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1870305HARBER 138.0 kV to 05SOFTSH 138.0 kV ckt 1 - Rebuild$3,147,368
AEP(Pending) / AEP-TC2-1871105CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Reconductor$189,617
AEP(Pending) / AEP-TC2-1870805LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Replace Equipment$185,706
AEP(Pending) / AEP-TC2-1868305CLNCHR 138.0 kV to 05ABINGD 138.0 kV ckt 1 - Sag Study$30,370
AEP(Pending) / AEP-TC2-1869505CONSTP 138.0 kV to 05BEAVER CR1 138.0 kV ckt 1 - Sag study$19,608
AEP(Pending) / AEP-TC2-1871205SOFTSH 138.0 kV to 05CONSTP 138.0 kV ckt 1 - Sag study$9,804
Grand Total:$3,582,473

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18703
Title
05HARBER 138.0 kV to 05SOFTSH 138.0 kV ckt 1 - Rebuild
Description
o Rebuild the line section between Harbert Metering and Softshell station at 5.5 miles with 1272 ACSR. Replaces the relays at Softshell station. Replace the station conductor at Harbert Metering. Replace the station conductor at Softshell station.
Total Cost ($USD)
$23,000,000
Allocated Cost ($USD)
$3,147,368
Time Estimate
48 to 72 Months

Contributor

FacilityContingency
05HARBER-05SOFTSH 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
210.0 MW44.2%$10,168,421
AH1-617
200.0 MW42.1%$9,684,211
AH1-644
65.0 MW13.7%$3,147,368

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18711
Title
05CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Reconductor
Description
Reconductor Clinch River - Str. 74-1 with 1033 ACSS Reconductor Str. 74-33 - Lebanon with 1033 ACSS Replace 1590 KCM AAC, 61-Str at Clinch River Station Replace 1590 KCM AAC, 61-Str at Lebanon
Total Cost ($USD)
$1,600,000
Allocated Cost ($USD)
$189,617
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
17.6 MW24.9%$398,197
AH1-227
6.6 MW9.4%$150,152
AH1-617
16.8 MW23.7%$379,233
AH1-644
8.4 MW11.9%$189,617
AH1-721
21.4 MW30.2%$482,801

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18708
Title
05LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Replace Equipment
Description
Replace 1590 KCM AAC, 61-Str at Lebanon Replace 1200 A switch at Elk Garden with a 2000 A switch
Total Cost ($USD)
$1,500,000
Allocated Cost ($USD)
$185,706
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
20.7 MW26.0%$389,971
AH1-227
8.0 MW10.0%$150,058
AH1-617
19.7 MW24.8%$371,393
AH1-644
9.8 MW12.4%$185,706
AH1-721
21.4 MW26.9%$402,872

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18683
Title
05CLNCHR 138.0 kV to 05ABINGD 138.0 kV ckt 1 - Sag Study
Description
Sag Study ~18 miles of line on Clinch River - Abingdon 138 kV
Total Cost ($USD)
$180,000
Allocated Cost ($USD)
$30,370
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05ABINGD-05CLNCHR 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
15.3 MW35.4%$63,773
AH1-227
6.0 MW14.0%$25,117
AH1-617
14.6 MW33.7%$60,740
AH1-644
7.3 MW16.9%$30,370

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18695
Title
05CONSTP 138.0 kV to 05BEAVER CR1 138.0 kV ckt 1 - Sag study
Description
Sag study the 795 ACSR conductor to get it to MOT at ~10 miles
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$19,608
Time Estimate
12 to 24 Months

Contributor

FacilityContingency
05BEAVER CR1-05CONSTP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
137.2 MW41.2%$41,177
AH1-617
130.7 MW39.2%$39,216
AH1-644
65.4 MW19.6%$19,608

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18712
Title
05SOFTSH 138.0 kV to 05CONSTP 138.0 kV ckt 1 - Sag study
Description
Sag study the 795 ACSR conductor to get it to MOT at ~5.25 miles
Total Cost ($USD)
$50,000
Allocated Cost ($USD)
$9,804
Time Estimate
6 to 12 Months

Contributor

FacilityContingency
05CONSTP-05SOFTSH 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184
137.2 MW41.2%$20,588
AH1-617
130.7 MW39.2%$19,608
AH1-644
65.4 MW19.6%$9,804

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18624
Title
AH1-133 TP 138.0 kV to 05TAZEWE 138.0 kV ckt 1 - Sag Study
Description
Sag Study ~0.1 mile of line on Saltville - Tazewell 138 kV from Tazewell to Str. 82-79D
Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$0
Time Estimate
6 to 12 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 may need this upgrade in-service to be deliverable to the PJM system. If AH1-644 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05TAZEWE-AH1-133 TP 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18627
Title
AH1-133 TP 138.0 kV to 05TAZEWE 138.0 kV ckt 1 - Sag study
Description
Sag study 11 miles of 138kV line between AH1-133 TP and Tazewell station.
Total Cost ($USD)
$110,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 may need this upgrade in-service to be deliverable to the PJM system. If AH1-644 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05TAZEWE-AH1-133 TP 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18817
Title
Replace Stuart Switches to 4000 A
Description
Replace Stuart Switches to 4000 A
Total Cost ($USD)
$1,200,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
(Pending) / Dayton-TC2-18818
Title
Replace Wavetrap to 4000 A
Description
Replace Wavetrap to 4000 A
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9670.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9670.0 / DAYr190039
Title
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Description
Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor.
Total Cost ($USD)
$50,000,000
Allocated Cost ($USD)
$0
Time Estimate
60 to 72 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9671.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9671.0 / DAYr190040
Title
Replace Stuart substation bus and conductor
Description
Replace Stuart substation bus and conductor
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9672.0
Type
Load Flow
TO
Dayton
RTEP ID / TO ID
n9672.0 / DAYr190041
Title
Replace Stuart substation breakers to 4000 A breakers
Description
Replace Stuart substation breakers to 4000 A breakers
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9673.0
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
n9673.0 / EKPC-tc1-r0020b
Title
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Description
Replace the 1500A interconnection metering CTs at Spurlock Station with 2000A equipment.
Total Cost ($USD)
$1,295,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-644 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-644 could receive cost allocation. Although AH1-644 may not presently have cost responsibility for this upgrade, AH1-644 is a potential Aggregate Pool Contributor.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
EKPC
RTEP ID / TO ID
(Pending) / EKPC-tc1-r0020a
Title
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Description
Dayton Power & Light addresses its limiting elements (EKPC limits are 1777/1792/1792 for Rate A/B/C).
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-644 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-644 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

Attachments

AH1-644 One Line Diagram

AH1-644 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.