AH1-673 Phase I Study Report

v1.00 released 2025-10-29 20:58

State Line - River Energy Center 138 kV

85.0 MW Capacity / 85.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Big Shoulders Storage LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Commonwealth Edison Company zone — Cook County, Illinois. The installed facilities will have a total capability of 85.0 MW with 85.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-673
Project Name:
State Line - River Energy Center 138 kV
Project Developer Name:
Big Shoulders Storage LLC
State:
Illinois
County:
Cook
Transmission Owner:
Commonwealth Edison Company
MFO:
85.0
MWE:
85.0
MWC:
85.0
Battery Storage Specification:
850.0 MWh, 10.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-673 will interconnect on the Commonwealth Edison Company  transmission system by tapping the River Energy Center - State Line 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-673 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-673Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$1,800,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$30,000,000$30,000,000
Network Upgrades$5,000,000$5,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$36,800,000$35,000,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-673

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-673 Project due at DP1
ABA - B
AH1-673$3,500,000$340,000$3,160,000

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

If your project relies on Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and/or Network Upgrades that will be constructed by another New Service Request and the other New Service Request withdraws, the scope and costs will be allocated to your project, unless the Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and/or applicable Network Upgrades have been securitized in an ISA/GIA. 

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Transmission Owner Interconnection Facilities to interconnect developer project to ComEd facility.$1,800,000 $1,800,000
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)New interconnection substation built to ComEd Standard breaker and a half configuration$30,000,000 $30,000,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Transmission line work required to cut into new interconnection substation. Remote terminal work required, relaying and communication upgrades.$5,000,000 $5,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 60 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Notes on Cost Estimate:

  1. These estimates are order-of-magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

 

 

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-673 was evaluated as a 85.0 MW (85.0 MW Capacity) injection in the ComEd area.

AH1-673 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 85.0 MW (85.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC148.76 %1841.0B2738.5816.45
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC148.75 %1841.0B2738.5716.45
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC147.24 %1841.0B2710.6215.92
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC143.24 %1841.0B2637.1115.91
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC124.81 %1841.0B2297.7316.45
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC124.8 %1841.0B2297.6116.45
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-1
TowerAC118.06 %1841.0B2173.4714.85
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-2
TowerAC116.53 %1841.0B2145.414.86
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC109.12 %1841.0B2008.8712.84
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC107.24 %1841.0B1974.312.79
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC106.35 %1385.0A1472.9612.19
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
BusAC101.5 %1841.0B1868.712.85
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC121.82 %1591.0B1938.1914.18
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC119.96 %1591.0B1908.5614.18
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC112.09 %1591.0B1783.315.34
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC112.08 %1591.0B1783.2315.34

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2738.58
MW Contribution:16.45
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
14.088
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
8.543
274777LINCOLN ;8U
Adder
8.543
274675JOLIET 29;7U
Adder
41.035
274675JOLIET 29;7U
Adder
39.569
970833AG2-524 GEN
Solar/Wind Harmer
11.298
970833AG2-524 GEN
Solar/Wind Harmer
5.255
276868AE1-113 GEN
Solar/Wind Harmer
12.378
971411AH1-196 GEN
Solar/Wind Harmer
18.219
971675AH1-338 GEN
Solar/Wind Harmer
21.746
971171AH1-044 GEN
Solar/Wind Harmer
23.909
274823ROCKFORD ;21
Adder
23.224
946321AF1-296 GEN
Solar/Wind Harmer
11.128
276656WTG2_EQ
Solar/Wind Harmer
1.138
941731AE2-173 GEN
Solar/Wind Harmer
4.097
274724RIVER EC ;11
50/50
31.815
957371AF2-031 GEN
50/50
1.575
274800UNIV PARK;3U
Adder
8.394
970941AG2-585 GEN
Solar/Wind Harmer
17.61
274802UNIV PARK;5U
Adder
8.077
274772LINCOLN ;3U
Adder
8.543
276893AG1-478 C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
21.766
276897AD1-100 C
Solar/Wind Harmer
38.391
276805AD2-038 GEN
Solar/Wind Harmer
6.386
276799AD1-013 GEN
Solar/Wind Harmer
2.673
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274850MENDOTA H;RU
Solar/Wind Harmer
3.101
276602WESTBROOK C
Solar/Wind Harmer
2.567
276863AD2-134 GEN
Solar/Wind Harmer
2.157
276889AE2-281 GEN
Solar/Wind Harmer
2.291
970571AG2-364 GEN
Solar/Wind Harmer
23.178
274858EASY ROAD;U2
Solar/Wind Harmer
5.518
276157O29GEN1
Solar/Wind Harmer
4.251
274888KELLY CRK;1U
Solar/Wind Harmer
8.317
274770LINCOLN ;1U
Adder
8.543
274771LINCOLN ;2U
Adder
8.543
972259AH1-714 GEN
Adder
25.2
274808UNIV PK N;4U
Adder
6.518
274697ROCKY RD ;3P
Adder
3.815
274696ROCKY RD ;4P
Adder
14.376
962691AG1-118 GEN
Solar/Wind Harmer
37.207
274856ECOGROVE ;U1
Solar/Wind Harmer
3.964
276611AD2-172 GEN
Solar/Wind Harmer
3.007
938861AE1-114 GEN
Solar/Wind Harmer
9.505
274762LEE CO EC;3U
Adder
10.713
276603SUBLETTE C
Solar/Wind Harmer
1.202
276645AC1-214 GEN1
Solar/Wind Harmer
1.461
274887GEN-1.85
Solar/Wind Harmer
7.509
274803UNIV PARK;6U
Adder
8.077
274674JOLIET 9 ;6U
Adder
20.703
958481AF2-142 GEN
Solar/Wind Harmer
19.223
274862TOP CROP ;2U
Solar/Wind Harmer
6.462
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.443
274693ROCKY RD ;1P
Adder
13.907
970921AG2-575 GEN
Solar/Wind Harmer
12.347
970921AG2-575 GEN
Solar/Wind Harmer
2.871
274879MINONK ;1U
Solar/Wind Harmer
8.253
971335AH1-147 GEN
Solar/Wind Harmer
24.221
274764LEE CO EC;5U
Adder
10.738
972267AH1-718 GEN
Adder
4.7
276708O09 GEN2
Solar/Wind Harmer
3.992
276782AC1-033 GEN
Solar/Wind Harmer
4.314
276843GEN-1.7
Solar/Wind Harmer
0.808
958011AF2-095 GEN
Solar/Wind Harmer
20.287
274861TOP CROP ;1U
Solar/Wind Harmer
7.739
971573AH1-285 GEN
Solar/Wind Harmer
10.912
274695ROCKY RD ;2P
Adder
14.045
958491AF2-143 GEN
Solar/Wind Harmer
18.672
942991AE2-321 GEN
Solar/Wind Harmer
12.244
971333AH1-146 GEN
Solar/Wind Harmer
24.221
276872AE1-163_GEN1
Solar/Wind Harmer
8.019
274765LEE CO EC;6U
Adder
10.738
274763LEE CO EC;4U
Adder
10.612
274851PROVIDENC;RU
Solar/Wind Harmer
3.106
276646AC1-214 GEN2
Solar/Wind Harmer
1.461
274826FISK ;BP
50/50
16.789
276772AC2-154 GEN
Solar/Wind Harmer
3.929
972228AH1-698 GEN2
Adder
4.963
274730ELWOOD EC;6P
Adder
21.769
939351AE1-166 GEN
Solar/Wind Harmer
7.844
970707AG2-453 GEN
Solar/Wind Harmer
36.666
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
972231SS25-0005
Solar/Wind Harmer
11.874
274752CRETE EC ;2U
Adder
6.116
274855GSG-6 ;RU
Solar/Wind Harmer
4.459
274776LINCOLN ;7U
Adder
8.543
274687WILL CNTY;4U
Adder
37.907
274687WILL CNTY;4U
Adder
37.907
274731ELWOOD EC;2P
Adder
21.766
274733ELWOOD EC;3P
Adder
21.766
274814UNIV PK N;0U
Adder
6.604
274807UNIV PK N;3U
Adder
6.59
274805UNIV PK N;1U
Adder
6.561
274746AC1-111 G10
Adder
7.173
276882AE2-255 GEN
Solar/Wind Harmer
4.126
926823AC1-168 GEN
Solar/Wind Harmer
4.911
276655WTG1_EQ
Solar/Wind Harmer
8.592
276806AD2-047 C O1
Solar/Wind Harmer
15.071
274676JOLIET 29;8U
Adder
39.569
274734ELWOOD EC;8P
Adder
21.769
274736ELWOOD EC;9P
Adder
21.769
943121AE2-341 GEN
Solar/Wind Harmer
19.202
943591AF1-030 GEN
Solar/Wind Harmer
12.801
274682WAUKEGAN ;7U
Adder
22.761
972181SS23-001
Solar/Wind Harmer
7.421
959091AF2-200 GEN
Solar/Wind Harmer
23.909
274767LEE CO EC;8U
Adder
10.587
961501AF2-441 GEN
50/50
15.121
274827FISK ;RP
50/50
11.898
972227AH1-698 GEN1
Adder
3.494
274735ELWOOD EC;4P
Adder
21.766
274811UNIV PK N;7U
Adder
6.547
274744AC1-111 GEN8
Adder
7.173
961011AF2-392 GEN
Solar/Wind Harmer
12.329
970169AG2-114 GEN
Solar/Wind Harmer
10.984
274848CAMPGROVE;RU
Solar/Wind Harmer
6.902
941551AE2-152 GEN
Solar/Wind Harmer
6
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
10.097
959081AF2-199 GEN
Solar/Wind Harmer
11.955
971067AG2-660 GEN
Solar/Wind Harmer
2.78
274822ROCKFORD ;11
Adder
23.394
970819AG2-516 GEN
Solar/Wind Harmer
14.154
971475AH1-234 GEN
Solar/Wind Harmer
26.315
276726Z2-087_GEN
Solar/Wind Harmer
7.783
274723RIVER EC ;12
50/50
31.785
274801UNIV PARK;4U
Adder
8.394
274773LINCOLN ;4U
Adder
8.543
274774LINCOLN ;5U
Adder
8.543
274751CRETE EC ;1U
Adder
6.116
276861AD2-134 GEN
Solar/Wind Harmer
2.157
971997AH1-543 GEN
Solar/Wind Harmer
18.889
970569AG2-363 GEN
Solar/Wind Harmer
34.768
274761LEE CO EC;2U
Adder
10.713
276158O29GEN2
Solar/Wind Harmer
5.589
939741AE1-205 GEN
Solar/Wind Harmer
14.093
972179AH1-673 GEN
50/50
16.453
276164X3-005 C
Solar/Wind Harmer
1.103
276776AD2-060 GEN
Solar/Wind Harmer
0.596
972207SS24-0001
Solar/Wind Harmer
30.372
274676JOLIET 29;8U
Adder
41.034
274812UNIV PK N;8U
Adder
6.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.918
274745AC1-111 GEN9
Adder
7.173
274682WAUKEGAN ;7U
Adder
22.761
274828WAUKEGAN ;BP
Adder
13.956
960751AF2-366 GEN
Solar/Wind Harmer
3.543
274674JOLIET 9 ;6U
Adder
20.703
274732ELWOOD EC;7P
Adder
21.769
274754CRETE EC ;4U
Adder
6.116
962781AG1-127 GEN
Solar/Wind Harmer
11.742
939401AE1-172 GEN
Solar/Wind Harmer
16.677
276876AE1-163_GEN2
Solar/Wind Harmer
8.019
972235AH1-702 GEN1
Adder
2.99
274857EASY ROAD;U1
Solar/Wind Harmer
5.518
274766LEE CO EC;7U
Adder
10.587
274728ELWOOD EC;5P
Adder
21.769
971177AH1-047 GEN
Solar/Wind Harmer
7.169
276612AE2-035 GEN
Solar/Wind Harmer
3.007
971681AH1-341 GEN
Solar/Wind Harmer
17.392
274863CRW1-WTG
Solar/Wind Harmer
6.413
274864CRW2-WTG
Solar/Wind Harmer
6.413
957751AF2-069 GEN
Solar/Wind Harmer
0.501
276901AD2-066 C O1
Solar/Wind Harmer
4.301
957471AF2-041 GEN
Solar/Wind Harmer
35.864
274877BISHOP HL;1U
Solar/Wind Harmer
3.65
274847GR RIDGE ;BU
Solar/Wind Harmer
6.524
971341AH1-150 GEN
Solar/Wind Harmer
23.909
971343AH1-151 GEN
Solar/Wind Harmer
23.909
276741O09 GEN1
Solar/Wind Harmer
3.992
274849CRESCENT ;1U
Solar/Wind Harmer
2.016
972038AH1-567 GEN2
Adder
0.525
274753CRETE EC ;3U
Adder
6.116
274872LEEDK;1U
Solar/Wind Harmer
0.314
972236AH1-702 GEN2
Adder
2.6
274760LEE CO EC;1U
Adder
10.713
274878BISHOP HL;2U
Solar/Wind Harmer
3.65
965931AG1-462 GEN
Solar/Wind Harmer
26.907
990582J1340
External Queue
21.826017379760742
990662J1358
External Queue
15.149626731872559
990512J1326
External Queue
5.457309722900391
991092J1477
External Queue
2.8719847202301025
990577J1339
External Queue
21.826017379760742
990647J1355
External Queue
42.77540969848633
991247J1684 G
External Queue
28.069046020507812
990547J1333 G
External Queue
34.17172622680664
990552J1334 G
External Queue
34.17172622680664
990557J1335 G
External Queue
34.17172622680664
990562J1336 G
External Queue
34.17172622680664
990762J1386
External Queue
10.366711616516113
991332J1785
External Queue
12.019579887390137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.854
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.032
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
NYPJM->LTFIMP_NY
CLTF
1.15
TVALTFEXP_TVA->PJM
CLTF
1.346
LAGNLTFEXP_LAGN->PJM
CLTF
4.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.551
WECLTFEXP_WEC->PJM
CLTF
4.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.385
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.199
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
MECLTFEXP_MEC->PJM
CLTF
14.34
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.75 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2738.57
MW Contribution:16.45
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
14.088
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
8.544
274777LINCOLN ;8U
Adder
8.544
274675JOLIET 29;7U
Adder
41.035
274675JOLIET 29;7U
Adder
39.569
970833AG2-524 GEN
Solar/Wind Harmer
11.298
970833AG2-524 GEN
Solar/Wind Harmer
5.255
276868AE1-113 GEN
Solar/Wind Harmer
12.378
971411AH1-196 GEN
Solar/Wind Harmer
18.219
971675AH1-338 GEN
Solar/Wind Harmer
21.745
971171AH1-044 GEN
Solar/Wind Harmer
23.909
274823ROCKFORD ;21
Adder
23.224
946321AF1-296 GEN
Solar/Wind Harmer
11.128
276656WTG2_EQ
Solar/Wind Harmer
1.138
941731AE2-173 GEN
Solar/Wind Harmer
4.097
274724RIVER EC ;11
50/50
31.816
957371AF2-031 GEN
50/50
1.575
274800UNIV PARK;3U
Adder
8.394
970941AG2-585 GEN
Solar/Wind Harmer
17.61
274802UNIV PARK;5U
Adder
8.077
274772LINCOLN ;3U
Adder
8.544
276893AG1-478 C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
21.766
276897AD1-100 C
Solar/Wind Harmer
38.391
276805AD2-038 GEN
Solar/Wind Harmer
6.386
276799AD1-013 GEN
Solar/Wind Harmer
2.673
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274850MENDOTA H;RU
Solar/Wind Harmer
3.101
276602WESTBROOK C
Solar/Wind Harmer
2.567
276863AD2-134 GEN
Solar/Wind Harmer
2.157
276889AE2-281 GEN
Solar/Wind Harmer
2.291
970571AG2-364 GEN
Solar/Wind Harmer
23.178
274858EASY ROAD;U2
Solar/Wind Harmer
5.518
276157O29GEN1
Solar/Wind Harmer
4.251
274888KELLY CRK;1U
Solar/Wind Harmer
8.317
274770LINCOLN ;1U
Adder
8.544
274771LINCOLN ;2U
Adder
8.544
972259AH1-714 GEN
Adder
25.2
274808UNIV PK N;4U
Adder
6.518
274697ROCKY RD ;3P
Adder
3.815
274696ROCKY RD ;4P
Adder
14.376
962691AG1-118 GEN
Solar/Wind Harmer
37.207
274856ECOGROVE ;U1
Solar/Wind Harmer
3.964
276611AD2-172 GEN
Solar/Wind Harmer
3.007
938861AE1-114 GEN
Solar/Wind Harmer
9.504
274762LEE CO EC;3U
Adder
10.713
276603SUBLETTE C
Solar/Wind Harmer
1.202
276645AC1-214 GEN1
Solar/Wind Harmer
1.461
274887GEN-1.85
Solar/Wind Harmer
7.509
274803UNIV PARK;6U
Adder
8.077
274674JOLIET 9 ;6U
Adder
20.703
958481AF2-142 GEN
Solar/Wind Harmer
19.223
274862TOP CROP ;2U
Solar/Wind Harmer
6.462
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.443
274693ROCKY RD ;1P
Adder
13.907
970921AG2-575 GEN
Solar/Wind Harmer
12.347
970921AG2-575 GEN
Solar/Wind Harmer
2.871
274879MINONK ;1U
Solar/Wind Harmer
8.253
276843GEN-1.7
Solar/Wind Harmer
0.808
958011AF2-095 GEN
Solar/Wind Harmer
20.287
274861TOP CROP ;1U
Solar/Wind Harmer
7.739
971573AH1-285 GEN
Solar/Wind Harmer
10.912
274695ROCKY RD ;2P
Adder
14.045
958491AF2-143 GEN
Solar/Wind Harmer
18.672
942991AE2-321 GEN
Solar/Wind Harmer
12.244
971333AH1-146 GEN
Solar/Wind Harmer
24.22
276872AE1-163_GEN1
Solar/Wind Harmer
8.019
274765LEE CO EC;6U
Adder
10.738
274763LEE CO EC;4U
Adder
10.612
274851PROVIDENC;RU
Solar/Wind Harmer
3.106
276646AC1-214 GEN2
Solar/Wind Harmer
1.461
971335AH1-147 GEN
Solar/Wind Harmer
24.22
274764LEE CO EC;5U
Adder
10.738
972267AH1-718 GEN
Adder
4.7
276708O09 GEN2
Solar/Wind Harmer
3.992
276782AC1-033 GEN
Solar/Wind Harmer
4.314
274826FISK ;BP
50/50
16.789
276772AC2-154 GEN
Solar/Wind Harmer
3.929
972228AH1-698 GEN2
Adder
4.963
274730ELWOOD EC;6P
Adder
21.769
939351AE1-166 GEN
Solar/Wind Harmer
7.844
970707AG2-453 GEN
Solar/Wind Harmer
36.665
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
972231SS25-0005
Solar/Wind Harmer
11.874
274776LINCOLN ;7U
Adder
8.544
274687WILL CNTY;4U
Adder
37.907
274687WILL CNTY;4U
Adder
37.907
274731ELWOOD EC;2P
Adder
21.766
274733ELWOOD EC;3P
Adder
21.766
274814UNIV PK N;0U
Adder
6.604
274807UNIV PK N;3U
Adder
6.59
274805UNIV PK N;1U
Adder
6.561
274746AC1-111 G10
Adder
7.173
276882AE2-255 GEN
Solar/Wind Harmer
4.126
926823AC1-168 GEN
Solar/Wind Harmer
4.911
276655WTG1_EQ
Solar/Wind Harmer
8.591
276806AD2-047 C O1
Solar/Wind Harmer
15.071
274676JOLIET 29;8U
Adder
39.568
274734ELWOOD EC;8P
Adder
21.769
274736ELWOOD EC;9P
Adder
21.769
943121AE2-341 GEN
Solar/Wind Harmer
19.201
943591AF1-030 GEN
Solar/Wind Harmer
12.801
274682WAUKEGAN ;7U
Adder
22.761
972181SS23-001
Solar/Wind Harmer
7.421
959091AF2-200 GEN
Solar/Wind Harmer
23.909
274767LEE CO EC;8U
Adder
10.586
961501AF2-441 GEN
50/50
15.121
274827FISK ;RP
50/50
11.898
972227AH1-698 GEN1
Adder
3.493
274735ELWOOD EC;4P
Adder
21.766
274811UNIV PK N;7U
Adder
6.547
274744AC1-111 GEN8
Adder
7.173
961011AF2-392 GEN
Solar/Wind Harmer
12.329
970169AG2-114 GEN
Solar/Wind Harmer
10.984
274848CAMPGROVE;RU
Solar/Wind Harmer
6.902
941551AE2-152 GEN
Solar/Wind Harmer
6
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
10.096
959081AF2-199 GEN
Solar/Wind Harmer
11.955
971067AG2-660 GEN
Solar/Wind Harmer
2.78
274822ROCKFORD ;11
Adder
23.393
970819AG2-516 GEN
Solar/Wind Harmer
14.154
274723RIVER EC ;12
50/50
31.785
274801UNIV PARK;4U
Adder
8.394
274773LINCOLN ;4U
Adder
8.544
274774LINCOLN ;5U
Adder
8.544
274751CRETE EC ;1U
Adder
6.116
276861AD2-134 GEN
Solar/Wind Harmer
2.157
971997AH1-543 GEN
Solar/Wind Harmer
18.888
970569AG2-363 GEN
Solar/Wind Harmer
34.767
274761LEE CO EC;2U
Adder
10.713
276158O29GEN2
Solar/Wind Harmer
5.589
939741AE1-205 GEN
Solar/Wind Harmer
14.093
274752CRETE EC ;2U
Adder
6.116
274855GSG-6 ;RU
Solar/Wind Harmer
4.459
274674JOLIET 9 ;6U
Adder
20.703
274732ELWOOD EC;7P
Adder
21.769
274754CRETE EC ;4U
Adder
6.116
962781AG1-127 GEN
Solar/Wind Harmer
11.742
939401AE1-172 GEN
Solar/Wind Harmer
16.677
276876AE1-163_GEN2
Solar/Wind Harmer
8.019
972235AH1-702 GEN1
Adder
2.99
274857EASY ROAD;U1
Solar/Wind Harmer
5.518
274766LEE CO EC;7U
Adder
10.586
274728ELWOOD EC;5P
Adder
21.769
971177AH1-047 GEN
Solar/Wind Harmer
7.169
276612AE2-035 GEN
Solar/Wind Harmer
3.007
971681AH1-341 GEN
Solar/Wind Harmer
17.392
274863CRW1-WTG
Solar/Wind Harmer
6.412
274864CRW2-WTG
Solar/Wind Harmer
6.412
957751AF2-069 GEN
Solar/Wind Harmer
0.501
971475AH1-234 GEN
Solar/Wind Harmer
26.315
276726Z2-087_GEN
Solar/Wind Harmer
7.783
972179AH1-673 GEN
50/50
16.453
276164X3-005 C
Solar/Wind Harmer
1.103
276776AD2-060 GEN
Solar/Wind Harmer
0.596
972207SS24-0001
Solar/Wind Harmer
30.377
274676JOLIET 29;8U
Adder
41.034
274812UNIV PK N;8U
Adder
6.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.918
274745AC1-111 GEN9
Adder
7.173
274682WAUKEGAN ;7U
Adder
22.761
274828WAUKEGAN ;BP
Adder
13.956
960751AF2-366 GEN
Solar/Wind Harmer
3.542
276901AD2-066 C O1
Solar/Wind Harmer
4.301
957471AF2-041 GEN
Solar/Wind Harmer
35.864
274877BISHOP HL;1U
Solar/Wind Harmer
3.65
274847GR RIDGE ;BU
Solar/Wind Harmer
6.524
971341AH1-150 GEN
Solar/Wind Harmer
23.909
971343AH1-151 GEN
Solar/Wind Harmer
23.909
276741O09 GEN1
Solar/Wind Harmer
3.992
274849CRESCENT ;1U
Solar/Wind Harmer
2.016
972038AH1-567 GEN2
Adder
0.525
274753CRETE EC ;3U
Adder
6.116
274872LEEDK;1U
Solar/Wind Harmer
0.314
972236AH1-702 GEN2
Adder
2.6
274760LEE CO EC;1U
Adder
10.713
274878BISHOP HL;2U
Solar/Wind Harmer
3.65
965931AG1-462 GEN
Solar/Wind Harmer
26.907
990582J1340
External Queue
21.826255798339844
990662J1358
External Queue
15.149800300598145
990512J1326
External Queue
5.457244396209717
991092J1477
External Queue
2.871951103210449
990577J1339
External Queue
21.826255798339844
990647J1355
External Queue
42.775543212890625
991247J1684 G
External Queue
28.06928825378418
990547J1333 G
External Queue
34.1719856262207
990552J1334 G
External Queue
34.1719856262207
990557J1335 G
External Queue
34.1719856262207
990562J1336 G
External Queue
34.1719856262207
990762J1386
External Queue
10.366846084594727
991332J1785
External Queue
12.01968002319336
NYPJM->LTFIMP_NY
CLTF
1.15
TVALTFEXP_TVA->PJM
CLTF
1.346
LAGNLTFEXP_LAGN->PJM
CLTF
4.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.551
WECLTFEXP_WEC->PJM
CLTF
4.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.385
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.199
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
MECLTFEXP_MEC->PJM
CLTF
14.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.854
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.032
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2710.62
MW Contribution:15.92
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
13.662
972037AH1-567 GEN1
Adder
0.245
274775LINCOLN ;6U
Adder
8.27
274777LINCOLN ;8U
Adder
8.27
274675JOLIET 29;7U
Adder
39.845
274675JOLIET 29;7U
Adder
38.422
970833AG2-524 GEN
Solar/Wind Harmer
10.999
970833AG2-524 GEN
Solar/Wind Harmer
5.116
276868AE1-113 GEN
Solar/Wind Harmer
12.091
971411AH1-196 GEN
Solar/Wind Harmer
17.804
971675AH1-338 GEN
Solar/Wind Harmer
21.263
971171AH1-044 GEN
Solar/Wind Harmer
23.391
274823ROCKFORD ;21
Adder
22.721
946321AF1-296 GEN
Solar/Wind Harmer
10.965
276656WTG2_EQ
Solar/Wind Harmer
1.133
274724RIVER EC ;11
50/50
30.79
957371AF2-031 GEN
50/50
1.524
274800UNIV PARK;3U
Adder
8.139
970941AG2-585 GEN
Solar/Wind Harmer
17.077
274802UNIV PARK;5U
Adder
7.816
274772LINCOLN ;3U
Adder
8.27
276893AG1-478 C
Solar/Wind Harmer
0.546
274729ELWOOD EC;1P
Adder
21.149
276897AD1-100 C
Solar/Wind Harmer
37.296
276805AD2-038 GEN
Solar/Wind Harmer
6.229
276799AD1-013 GEN
Solar/Wind Harmer
2.613
946671AF1-331 GEN
Solar/Wind Harmer
0.495
274850MENDOTA H;RU
Solar/Wind Harmer
3.032
276602WESTBROOK C
Solar/Wind Harmer
2.51
276863AD2-134 GEN
Solar/Wind Harmer
2.109
276889AE2-281 GEN
Solar/Wind Harmer
2.242
970571AG2-364 GEN
Solar/Wind Harmer
22.727
274858EASY ROAD;U2
Solar/Wind Harmer
5.41
276157O29GEN1
Solar/Wind Harmer
4.178
942111AE2-223 GEN
Solar/Wind Harmer
8.037
24441205WTRV SLR C
Solar/Wind Helper
0.04
274888KELLY CRK;1U
Solar/Wind Harmer
8.066
274770LINCOLN ;1U
Adder
8.27
274771LINCOLN ;2U
Adder
8.27
972259AH1-714 GEN
Adder
24.494
274808UNIV PK N;4U
Adder
6.273
274697ROCKY RD ;3P
Adder
3.721
274696ROCKY RD ;4P
Adder
14.019
962691AG1-118 GEN
Solar/Wind Harmer
36.326
274856ECOGROVE ;U1
Solar/Wind Harmer
3.881
276611AD2-172 GEN
Solar/Wind Harmer
2.945
938861AE1-114 GEN
Solar/Wind Harmer
9.315
958011AF2-095 GEN
Solar/Wind Harmer
19.673
276843GEN-1.7
Solar/Wind Harmer
0.783
274861TOP CROP ;1U
Solar/Wind Harmer
7.533
971573AH1-285 GEN
Solar/Wind Harmer
10.642
274695ROCKY RD ;2P
Adder
13.696
958491AF2-143 GEN
Solar/Wind Harmer
18.213
942991AE2-321 GEN
Solar/Wind Harmer
11.96
971333AH1-146 GEN
Solar/Wind Harmer
23.675
276872AE1-163_GEN1
Solar/Wind Harmer
7.846
274765LEE CO EC;6U
Adder
10.528
274763LEE CO EC;4U
Adder
10.405
274851PROVIDENC;RU
Solar/Wind Harmer
3.06
276646AC1-214 GEN2
Solar/Wind Harmer
1.439
960981AF2-389 GEN
Solar/Wind Helper
0.286
274887GEN-1.85
Solar/Wind Harmer
7.282
274803UNIV PARK;6U
Adder
7.816
274674JOLIET 9 ;6U
Adder
20.123
958481AF2-142 GEN
Solar/Wind Harmer
18.712
274862TOP CROP ;2U
Solar/Wind Harmer
6.29
274683WAUKEGAN ;8U
Adder
25.952
274683WAUKEGAN ;8U
Adder
21.876
274693ROCKY RD ;1P
Adder
13.562
970921AG2-575 GEN
Solar/Wind Harmer
12.058
970921AG2-575 GEN
Solar/Wind Harmer
2.804
274879MINONK ;1U
Solar/Wind Harmer
8.062
971335AH1-147 GEN
Solar/Wind Harmer
23.675
274764LEE CO EC;5U
Adder
10.528
972267AH1-718 GEN
Adder
4.614
276708O09 GEN2
Solar/Wind Harmer
3.923
276782AC1-033 GEN
Solar/Wind Harmer
4.252
270216AD2-079_GEN
Solar/Wind Helper
0.122
274776LINCOLN ;7U
Adder
8.27
274687WILL CNTY;4U
Adder
36.789
274687WILL CNTY;4U
Adder
36.789
274731ELWOOD EC;2P
Adder
21.149
274733ELWOOD EC;3P
Adder
21.149
274814UNIV PK N;0U
Adder
6.356
274807UNIV PK N;3U
Adder
6.342
274805UNIV PK N;1U
Adder
6.315
274746AC1-111 G10
Adder
6.989
276882AE2-255 GEN
Solar/Wind Harmer
4.031
926823AC1-168 GEN
Solar/Wind Harmer
4.823
276655WTG1_EQ
Solar/Wind Harmer
8.559
276806AD2-047 C O1
Solar/Wind Harmer
14.615
274676JOLIET 29;8U
Adder
38.421
274734ELWOOD EC;8P
Adder
21.152
274736ELWOOD EC;9P
Adder
21.152
943121AE2-341 GEN
Solar/Wind Harmer
18.718
943591AF1-030 GEN
Solar/Wind Harmer
12.479
274682WAUKEGAN ;7U
Adder
22.183
972181SS23-001
Solar/Wind Harmer
7.098
959091AF2-200 GEN
Solar/Wind Harmer
23.391
274767LEE CO EC;8U
Adder
10.38
247643Z2-116 C
Solar/Wind Helper
0.028
961501AF2-441 GEN
50/50
14.64
274827FISK ;RP
50/50
11.53
972227AH1-698 GEN1
Adder
3.388
274735ELWOOD EC;4P
Adder
21.149
274811UNIV PK N;7U
Adder
6.301
274744AC1-111 GEN8
Adder
6.989
961011AF2-392 GEN
Solar/Wind Harmer
12.101
970169AG2-114 GEN
Solar/Wind Harmer
10.835
274848CAMPGROVE;RU
Solar/Wind Harmer
6.811
944161AF1-084 GEN
Solar/Wind Helper
0.656
959341AF2-225 GEN
Solar/Wind Harmer
0.282
274762LEE CO EC;3U
Adder
10.504
276603SUBLETTE C
Solar/Wind Harmer
1.179
276645AC1-214 GEN1
Solar/Wind Harmer
1.439
957891AF2-083 GEN
Solar/Wind Helper
1.378
274723RIVER EC ;12
50/50
30.754
274801UNIV PARK;4U
Adder
8.139
274773LINCOLN ;4U
Adder
8.27
274774LINCOLN ;5U
Adder
8.27
274751CRETE EC ;1U
Adder
5.849
276861AD2-134 GEN
Solar/Wind Harmer
2.109
971997AH1-543 GEN
Solar/Wind Harmer
18.488
970569AG2-363 GEN
Solar/Wind Harmer
34.09
274761LEE CO EC;2U
Adder
10.504
276158O29GEN2
Solar/Wind Harmer
5.493
939741AE1-205 GEN
Solar/Wind Harmer
19.607
274826FISK ;BP
50/50
16.268
276772AC2-154 GEN
Solar/Wind Harmer
3.81
972228AH1-698 GEN2
Adder
4.813
274730ELWOOD EC;6P
Adder
21.152
939351AE1-166 GEN
Solar/Wind Harmer
7.62
970707AG2-453 GEN
Solar/Wind Harmer
35.702
276694AA1-018 GEN2
Solar/Wind Harmer
7.872
972231SS25-0005
Solar/Wind Harmer
11.357
274752CRETE EC ;2U
Adder
5.849
274855GSG-6 ;RU
Solar/Wind Harmer
4.361
274674JOLIET 9 ;6U
Adder
20.123
274732ELWOOD EC;7P
Adder
21.152
962781AG1-127 GEN
Solar/Wind Harmer
11.467
274754CRETE EC ;4U
Adder
5.849
939401AE1-172 GEN
Solar/Wind Harmer
16.327
276876AE1-163_GEN2
Solar/Wind Harmer
7.846
972235AH1-702 GEN1
Adder
2.926
274857EASY ROAD;U1
Solar/Wind Harmer
5.41
274766LEE CO EC;7U
Adder
10.38
274728ELWOOD EC;5P
Adder
21.152
971177AH1-047 GEN
Solar/Wind Harmer
7.003
276612AE2-035 GEN
Solar/Wind Harmer
2.945
971681AH1-341 GEN
Solar/Wind Harmer
17.046
274863CRW1-WTG
Solar/Wind Harmer
6.3
274864CRW2-WTG
Solar/Wind Harmer
6.3
957751AF2-069 GEN
Solar/Wind Harmer
0.493
941551AE2-152 GEN
Solar/Wind Harmer
5.829
276691AA1-018 GEN1
Solar/Wind Harmer
0.581
274872LEEDK;1U
Solar/Wind Harmer
9.863
959081AF2-199 GEN
Solar/Wind Harmer
11.696
971067AG2-660 GEN
Solar/Wind Harmer
2.72
274822ROCKFORD ;11
Adder
22.887
970819AG2-516 GEN
Solar/Wind Harmer
13.856
971475AH1-234 GEN
Solar/Wind Harmer
25.766
276726Z2-087_GEN
Solar/Wind Harmer
7.754
972179AH1-673 GEN
50/50
15.92
276164X3-005 C
Solar/Wind Harmer
1.068
276776AD2-060 GEN
Solar/Wind Harmer
0.578
972207SS24-0001
Solar/Wind Harmer
29.403
274676JOLIET 29;8U
Adder
39.844
274812UNIV PK N;8U
Adder
6.301
274871GR RIDGE ;2U
Solar/Wind Harmer
9.656
274745AC1-111 GEN9
Adder
6.989
274682WAUKEGAN ;7U
Adder
22.183
274828WAUKEGAN ;BP
Adder
13.603
960751AF2-366 GEN
Solar/Wind Harmer
3.46
276901AD2-066 C O1
Solar/Wind Harmer
4.203
957471AF2-041 GEN
Solar/Wind Harmer
35.087
274877BISHOP HL;1U
Solar/Wind Harmer
3.598
270449AD2-020 GEN
Solar/Wind Helper
0.694
274847GR RIDGE ;BU
Solar/Wind Harmer
6.352
971341AH1-150 GEN
Solar/Wind Harmer
23.391
971343AH1-151 GEN
Solar/Wind Harmer
23.391
276741O09 GEN1
Solar/Wind Harmer
3.923
274849CRESCENT ;1U
Solar/Wind Harmer
1.987
972038AH1-567 GEN2
Adder
0.509
274872LEEDK;1U
Solar/Wind Harmer
0.307
274753CRETE EC ;3U
Adder
5.849
972236AH1-702 GEN2
Adder
2.544
274760LEE CO EC;1U
Adder
10.504
274878BISHOP HL;2U
Solar/Wind Harmer
3.598
965931AG1-462 GEN
Solar/Wind Harmer
26.532
990582J1340
External Queue
20.82658576965332
990662J1358
External Queue
14.046708106994629
990512J1326
External Queue
5.329690456390381
991092J1477
External Queue
2.8509562015533447
990577J1339
External Queue
20.82658576965332
990647J1355
External Queue
41.498023986816406
991247J1684 G
External Queue
26.93834686279297
990547J1333 G
External Queue
32.91541290283203
990552J1334 G
External Queue
32.91541290283203
990557J1335 G
External Queue
32.91541290283203
990562J1336 G
External Queue
32.91541290283203
991332J1785
External Queue
11.147284507751465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.645
LGEELTFEXP_LGEE->PJM
CLTF
0.185
TVALTFEXP_TVA->PJM
CLTF
1.715
AG2-052LTFEXP_AG2-052->PJM
LTF
0.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.605
WECLTFEXP_WEC->PJM
CLTF
4.445
MECLTFEXP_MEC->PJM
CLTF
14.337
AH1-155LTFEXP_AH1-155->PJM
LTF
0.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.461
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.278
LAGNLTFEXP_LAGN->PJM
CLTF
5.611
NYPJM->LTFIMP_NY
CLTF
1.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.104
SIGELTFEXP_SIGE->PJM
CLTF
0.07

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2637.11
MW Contribution:15.91
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
13.59
972037AH1-567 GEN1
Adder
0.244
274775LINCOLN ;6U
Adder
8.216
274777LINCOLN ;8U
Adder
8.216
274675JOLIET 29;7U
Adder
39.582
274675JOLIET 29;7U
Adder
38.168
970833AG2-524 GEN
Solar/Wind Harmer
10.903
970833AG2-524 GEN
Solar/Wind Harmer
5.071
276868AE1-113 GEN
Solar/Wind Harmer
11.941
971411AH1-196 GEN
Solar/Wind Harmer
17.589
971675AH1-338 GEN
Solar/Wind Harmer
20.997
971171AH1-044 GEN
Solar/Wind Harmer
23.085
274724RIVER EC ;11
50/50
30.779
957371AF2-031 GEN
50/50
1.524
274800UNIV PARK;3U
Adder
8.103
970941AG2-585 GEN
Solar/Wind Harmer
16.988
274823ROCKFORD ;21
Adder
22.421
946321AF1-296 GEN
Solar/Wind Harmer
10.744
276656WTG2_EQ
Solar/Wind Harmer
1.097
941731AE2-173 GEN
Solar/Wind Harmer
3.951
958011AF2-095 GEN
Solar/Wind Harmer
19.57
276843GEN-1.7
Solar/Wind Harmer
0.779
274861TOP CROP ;1U
Solar/Wind Harmer
7.462
971573AH1-285 GEN
Solar/Wind Harmer
10.539
274695ROCKY RD ;2P
Adder
13.56
958491AF2-143 GEN
Solar/Wind Harmer
18.008
942991AE2-321 GEN
Solar/Wind Harmer
11.821
971333AH1-146 GEN
Solar/Wind Harmer
23.384
276872AE1-163_GEN1
Solar/Wind Harmer
7.736
274765LEE CO EC;6U
Adder
10.367
274763LEE CO EC;4U
Adder
10.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.997
276646AC1-214 GEN2
Solar/Wind Harmer
1.41
274887GEN-1.85
Solar/Wind Harmer
7.244
274803UNIV PARK;6U
Adder
7.784
274674JOLIET 9 ;6U
Adder
19.981
958481AF2-142 GEN
Solar/Wind Harmer
18.537
274862TOP CROP ;2U
Solar/Wind Harmer
6.231
274683WAUKEGAN ;8U
Adder
25.698
274683WAUKEGAN ;8U
Adder
21.662
274693ROCKY RD ;1P
Adder
13.426
970921AG2-575 GEN
Solar/Wind Harmer
11.923
970921AG2-575 GEN
Solar/Wind Harmer
2.773
274879MINONK ;1U
Solar/Wind Harmer
7.962
971335AH1-147 GEN
Solar/Wind Harmer
23.384
274764LEE CO EC;5U
Adder
10.367
972267AH1-718 GEN
Adder
4.538
276708O09 GEN2
Solar/Wind Harmer
3.854
276782AC1-033 GEN
Solar/Wind Harmer
4.163
274776LINCOLN ;7U
Adder
8.216
274687WILL CNTY;4U
Adder
36.565
274687WILL CNTY;4U
Adder
36.565
274731ELWOOD EC;2P
Adder
20.994
274733ELWOOD EC;3P
Adder
20.994
274814UNIV PK N;0U
Adder
6.344
274807UNIV PK N;3U
Adder
6.33
274805UNIV PK N;1U
Adder
6.302
274746AC1-111 G10
Adder
6.926
276882AE2-255 GEN
Solar/Wind Harmer
3.981
276806AD2-047 C O1
Solar/Wind Harmer
14.538
274676JOLIET 29;8U
Adder
38.167
274734ELWOOD EC;8P
Adder
20.997
274736ELWOOD EC;9P
Adder
20.997
943121AE2-341 GEN
Solar/Wind Harmer
18.546
943591AF1-030 GEN
Solar/Wind Harmer
12.364
274682WAUKEGAN ;7U
Adder
21.969
972181SS23-001
Solar/Wind Harmer
7.104
959091AF2-200 GEN
Solar/Wind Harmer
23.085
274767LEE CO EC;8U
Adder
10.221
961501AF2-441 GEN
50/50
14.62
274827FISK ;RP
50/50
11.483
972227AH1-698 GEN1
Adder
3.367
274735ELWOOD EC;4P
Adder
20.994
274811UNIV PK N;7U
Adder
6.289
274744AC1-111 GEN8
Adder
6.926
961011AF2-392 GEN
Solar/Wind Harmer
11.903
970169AG2-114 GEN
Solar/Wind Harmer
10.595
274848CAMPGROVE;RU
Solar/Wind Harmer
6.662
926823AC1-168 GEN
Solar/Wind Harmer
4.739
276655WTG1_EQ
Solar/Wind Harmer
8.286
274888KELLY CRK;1U
Solar/Wind Harmer
8.024
274770LINCOLN ;1U
Adder
8.216
274771LINCOLN ;2U
Adder
8.216
972259AH1-714 GEN
Adder
24.316
274808UNIV PK N;4U
Adder
6.261
274697ROCKY RD ;3P
Adder
3.684
274696ROCKY RD ;4P
Adder
13.879
962691AG1-118 GEN
Solar/Wind Harmer
35.927
274856ECOGROVE ;U1
Solar/Wind Harmer
3.827
276611AD2-172 GEN
Solar/Wind Harmer
2.904
938861AE1-114 GEN
Solar/Wind Harmer
9.176
274762LEE CO EC;3U
Adder
10.343
276603SUBLETTE C
Solar/Wind Harmer
1.161
276645AC1-214 GEN1
Solar/Wind Harmer
1.41
274802UNIV PARK;5U
Adder
7.784
274772LINCOLN ;3U
Adder
8.216
276893AG1-478 C
Solar/Wind Harmer
0.542
274729ELWOOD EC;1P
Adder
20.994
276897AD1-100 C
Solar/Wind Harmer
36.988
276805AD2-038 GEN
Solar/Wind Harmer
6.159
276799AD1-013 GEN
Solar/Wind Harmer
2.581
946671AF1-331 GEN
Solar/Wind Harmer
0.489
274850MENDOTA H;RU
Solar/Wind Harmer
2.994
276602WESTBROOK C
Solar/Wind Harmer
2.479
276863AD2-134 GEN
Solar/Wind Harmer
2.082
276889AE2-281 GEN
Solar/Wind Harmer
2.21
970571AG2-364 GEN
Solar/Wind Harmer
22.362
274858EASY ROAD;U2
Solar/Wind Harmer
5.327
276157O29GEN1
Solar/Wind Harmer
4.104
274723RIVER EC ;12
50/50
30.74
274801UNIV PARK;4U
Adder
8.103
274773LINCOLN ;4U
Adder
8.216
274774LINCOLN ;5U
Adder
8.216
274751CRETE EC ;1U
Adder
5.854
276861AD2-134 GEN
Solar/Wind Harmer
2.082
971997AH1-543 GEN
Solar/Wind Harmer
18.231
970569AG2-363 GEN
Solar/Wind Harmer
33.543
274761LEE CO EC;2U
Adder
10.343
276158O29GEN2
Solar/Wind Harmer
5.395
939741AE1-205 GEN
Solar/Wind Harmer
13.592
274826FISK ;BP
50/50
16.202
276772AC2-154 GEN
Solar/Wind Harmer
3.79
972228AH1-698 GEN2
Adder
4.783
274730ELWOOD EC;6P
Adder
20.997
939351AE1-166 GEN
Solar/Wind Harmer
7.558
970707AG2-453 GEN
Solar/Wind Harmer
35.422
276694AA1-018 GEN2
Solar/Wind Harmer
7.799
972231SS25-0005
Solar/Wind Harmer
11.367
274752CRETE EC ;2U
Adder
5.854
274855GSG-6 ;RU
Solar/Wind Harmer
4.306
274674JOLIET 9 ;6U
Adder
19.981
274732ELWOOD EC;7P
Adder
20.997
274754CRETE EC ;4U
Adder
5.854
962781AG1-127 GEN
Solar/Wind Harmer
11.338
939401AE1-172 GEN
Solar/Wind Harmer
16.071
276876AE1-163_GEN2
Solar/Wind Harmer
7.736
972235AH1-702 GEN1
Adder
2.886
274857EASY ROAD;U1
Solar/Wind Harmer
5.327
274766LEE CO EC;7U
Adder
10.221
274728ELWOOD EC;5P
Adder
20.997
971177AH1-047 GEN
Solar/Wind Harmer
6.921
276612AE2-035 GEN
Solar/Wind Harmer
2.904
971681AH1-341 GEN
Solar/Wind Harmer
16.791
274863CRW1-WTG
Solar/Wind Harmer
6.181
274864CRW2-WTG
Solar/Wind Harmer
6.181
957751AF2-069 GEN
Solar/Wind Harmer
0.483
941551AE2-152 GEN
Solar/Wind Harmer
5.78
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274872LEEDK;1U
Solar/Wind Harmer
9.749
959081AF2-199 GEN
Solar/Wind Harmer
11.542
971067AG2-660 GEN
Solar/Wind Harmer
2.684
274822ROCKFORD ;11
Adder
22.585
970819AG2-516 GEN
Solar/Wind Harmer
13.665
971475AH1-234 GEN
Solar/Wind Harmer
25.406
276726Z2-087_GEN
Solar/Wind Harmer
7.506
972179AH1-673 GEN
50/50
15.911
276164X3-005 C
Solar/Wind Harmer
1.066
276776AD2-060 GEN
Solar/Wind Harmer
0.575
972207SS24-0001
Solar/Wind Harmer
29.211
274676JOLIET 29;8U
Adder
39.581
274812UNIV PK N;8U
Adder
6.289
274871GR RIDGE ;2U
Solar/Wind Harmer
9.57
274745AC1-111 GEN9
Adder
6.926
274682WAUKEGAN ;7U
Adder
21.969
274828WAUKEGAN ;BP
Adder
13.47
960751AF2-366 GEN
Solar/Wind Harmer
3.421
276901AD2-066 C O1
Solar/Wind Harmer
4.15
957471AF2-041 GEN
Solar/Wind Harmer
34.627
274877BISHOP HL;1U
Solar/Wind Harmer
3.523
274847GR RIDGE ;BU
Solar/Wind Harmer
6.295
971341AH1-150 GEN
Solar/Wind Harmer
23.085
971343AH1-151 GEN
Solar/Wind Harmer
23.085
276741O09 GEN1
Solar/Wind Harmer
3.854
274849CRESCENT ;1U
Solar/Wind Harmer
1.946
972038AH1-567 GEN2
Adder
0.507
274753CRETE EC ;3U
Adder
5.854
274872LEEDK;1U
Solar/Wind Harmer
0.304
972236AH1-702 GEN2
Adder
2.51
274760LEE CO EC;1U
Adder
10.343
274878BISHOP HL;2U
Solar/Wind Harmer
3.523
965931AG1-462 GEN
Solar/Wind Harmer
25.979
990582J1340
External Queue
21.181657791137695
990662J1358
External Queue
14.583775520324707
990512J1326
External Queue
5.3167853355407715
991092J1477
External Queue
2.8052659034729004
990577J1339
External Queue
21.181657791137695
990647J1355
External Queue
42.006256103515625
991247J1684 G
External Queue
27.351411819458008
990547J1333 G
External Queue
33.3844108581543
990552J1334 G
External Queue
33.3844108581543
990557J1335 G
External Queue
33.3844108581543
990562J1336 G
External Queue
33.3844108581543
990762J1386
External Queue
10.017333030700684
991332J1785
External Queue
11.59352970123291
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.814
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.921
AH1-155LTFEXP_AH1-155->PJM
LTF
0.815
NYPJM->LTFIMP_NY
CLTF
1.102
TVALTFEXP_TVA->PJM
CLTF
1.322
LAGNLTFEXP_LAGN->PJM
CLTF
4.851
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.324
WECLTFEXP_WEC->PJM
CLTF
4.387
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.396
MECLTFEXP_MEC->PJM
CLTF
13.851
AG2-052LTFEXP_AG2-052->PJM
LTF
0.543

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.81 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2297.73
MW Contribution:16.45
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
9.826
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
11.59
274777LINCOLN ;8U
Adder
11.59
274675JOLIET 29;7U
Adder
41.051
274675JOLIET 29;7U
Adder
39.585
970833AG2-524 GEN
Solar/Wind Harmer
9.94
970833AG2-524 GEN
Solar/Wind Harmer
6.627
276868AE1-113 GEN
Solar/Wind Harmer
1.713
971411AH1-196 GEN
Solar/Wind Harmer
12.725
971675AH1-338 GEN
Solar/Wind Harmer
3.291
971171AH1-044 GEN
Solar/Wind Harmer
16.7
274823ROCKFORD ;21
Adder
23.249
946321AF1-296 GEN
Solar/Wind Harmer
4.171
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.72
274724RIVER EC ;11
50/50
31.802
957371AF2-031 GEN
50/50
1.574
274800UNIV PARK;3U
Adder
8.394
970941AG2-585 GEN
Solar/Wind Harmer
12.282
274802UNIV PARK;5U
Adder
8.076
274772LINCOLN ;3U
Adder
11.59
276893AG1-478 C
Solar/Wind Harmer
0.372
274729ELWOOD EC;1P
Adder
21.774
276897AD1-100 C
Solar/Wind Harmer
0.012
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.901
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.151
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
16.178
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.26
942111AE2-223 GEN
Solar/Wind Harmer
2.231
971993AH1-541 GEN
Solar/Wind Harmer
2.515
276621W2-048 GEN
Solar/Wind Harmer
0.262
276838X2-022 GEN2
Solar/Wind Harmer
0.293
942481AE2-261 GEN
Solar/Wind Harmer
14.075
274888KELLY CRK;1U
Solar/Wind Harmer
0.577
274770LINCOLN ;1U
Adder
11.59
274771LINCOLN ;2U
Adder
11.59
972259AH1-714 GEN
Adder
25.222
274808UNIV PK N;4U
Adder
6.517
274696ROCKY RD ;4P
Adder
14.393
274697ROCKY RD ;3P
Adder
3.82
962691AG1-118 GEN
Solar/Wind Harmer
25.992
274856ECOGROVE ;U1
Solar/Wind Harmer
0.194
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.589
274762LEE CO EC;3U
Adder
10.724
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.259
274803UNIV PARK;6U
Adder
8.076
274674JOLIET 9 ;6U
Adder
20.714
958481AF2-142 GEN
Solar/Wind Harmer
13.413
274862TOP CROP ;2U
Solar/Wind Harmer
1.206
274683WAUKEGAN ;8U
Adder
26.649
274683WAUKEGAN ;8U
Adder
22.464
274693ROCKY RD ;1P
Adder
13.923
970921AG2-575 GEN
Solar/Wind Harmer
8.625
970921AG2-575 GEN
Solar/Wind Harmer
2.875
274879MINONK ;1U
Solar/Wind Harmer
0.36
971335AH1-147 GEN
Solar/Wind Harmer
16.917
274764LEE CO EC;5U
Adder
10.749
972267AH1-718 GEN
Adder
4.705
276708O09 GEN2
Solar/Wind Harmer
0.278
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.185
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
14.149
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.652
274695ROCKY RD ;2P
Adder
14.061
958491AF2-143 GEN
Solar/Wind Harmer
13.029
942991AE2-321 GEN
Solar/Wind Harmer
9.55
971333AH1-146 GEN
Solar/Wind Harmer
16.917
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274765LEE CO EC;6U
Adder
10.749
274763LEE CO EC;4U
Adder
10.623
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.299
276911AD2-131_GEN
Solar/Wind Harmer
0.632
274826FISK ;BP
50/50
16.786
972228AH1-698 GEN2
Adder
4.962
274730ELWOOD EC;6P
Adder
21.778
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.902
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
10.307
274855GSG-6 ;RU
Solar/Wind Harmer
0.309
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.185
274776LINCOLN ;7U
Adder
11.59
274687WILL CNTY;4U
Adder
37.915
274687WILL CNTY;4U
Adder
37.915
274731ELWOOD EC;2P
Adder
21.774
274733ELWOOD EC;3P
Adder
21.774
274814UNIV PK N;0U
Adder
6.603
274807UNIV PK N;3U
Adder
6.589
274805UNIV PK N;1U
Adder
6.56
274746AC1-111 G10
Adder
7.182
276882AE2-255 GEN
Solar/Wind Harmer
0.998
926823AC1-168 GEN
Solar/Wind Harmer
1.354
276655WTG1_EQ
Solar/Wind Harmer
0.003
944221AF1-090 GEN
Solar/Wind Harmer
2.406
276806AD2-047 C O1
Solar/Wind Harmer
5.568
274676JOLIET 29;8U
Adder
39.585
274734ELWOOD EC;8P
Adder
21.778
274736ELWOOD EC;9P
Adder
21.778
943121AE2-341 GEN
Solar/Wind Harmer
14.998
943591AF1-030 GEN
Solar/Wind Harmer
9.974
274682WAUKEGAN ;7U
Adder
22.781
959091AF2-200 GEN
Solar/Wind Harmer
16.7
274767LEE CO EC;8U
Adder
10.598
276668AB2-070 GEN1
Solar/Wind Harmer
0.198
961501AF2-441 GEN
50/50
15.114
274827FISK ;RP
50/50
11.896
972227AH1-698 GEN1
Adder
3.493
274735ELWOOD EC;4P
Adder
21.774
274811UNIV PK N;7U
Adder
6.546
274744AC1-111 GEN8
Adder
7.182
961011AF2-392 GEN
Solar/Wind Harmer
4.645
970169AG2-114 GEN
Solar/Wind Harmer
7.664
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
7.208
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.198
276848AB2-070 GEN3
Solar/Wind Harmer
0.197
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.083
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
8.35
971067AG2-660 GEN
Solar/Wind Harmer
2.783
274822ROCKFORD ;11
Adder
23.418
970819AG2-516 GEN
Solar/Wind Harmer
9.885
971475AH1-234 GEN
Solar/Wind Harmer
3.982
276726Z2-087_GEN
Solar/Wind Harmer
0.002
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
274723RIVER EC ;12
50/50
31.772
274801UNIV PARK;4U
Adder
8.394
274773LINCOLN ;4U
Adder
11.59
274774LINCOLN ;5U
Adder
11.59
274751CRETE EC ;1U
Adder
10.307
276861AD2-134 GEN
Solar/Wind Harmer
0.151
971997AH1-543 GEN
Solar/Wind Harmer
4.397
970569AG2-363 GEN
Solar/Wind Harmer
24.267
274761LEE CO EC;2U
Adder
10.724
276158O29GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.61
972175AH1-670 GEN
Solar/Wind Harmer
4.931
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972179AH1-673 GEN
50/50
16.446
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274676JOLIET 29;8U
Adder
41.051
274812UNIV PK N;8U
Adder
6.546
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.182
274682WAUKEGAN ;7U
Adder
22.781
274828WAUKEGAN ;BP
Adder
13.969
276901AD2-066 C O1
Solar/Wind Harmer
0.008
957471AF2-041 GEN
Solar/Wind Harmer
25.05
274877BISHOP HL;1U
Solar/Wind Harmer
0.254
274674JOLIET 9 ;6U
Adder
20.714
274732ELWOOD EC;7P
Adder
21.778
274754CRETE EC ;4U
Adder
10.307
962781AG1-127 GEN
Solar/Wind Harmer
8.208
939401AE1-172 GEN
Solar/Wind Harmer
6.239
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.993
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
10.598
963831AG1-236 GEN
Solar/Wind Harmer
2.091
276615X2-022 GEN
Solar/Wind Harmer
0.055
965911AG1-460 GEN
Solar/Wind Harmer
0.941
274728ELWOOD EC;5P
Adder
21.778
971177AH1-047 GEN
Solar/Wind Harmer
5.269
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
13.037
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.251
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
16.7
971343AH1-151 GEN
Solar/Wind Harmer
16.7
276741O09 GEN1
Solar/Wind Harmer
0.278
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
9.598
972038AH1-567 GEN2
Adder
0.525
274753CRETE EC ;3U
Adder
10.307
274872LEEDK;1U
Solar/Wind Harmer
0.315
972236AH1-702 GEN2
Adder
2.603
274760LEE CO EC;1U
Adder
10.724
274878BISHOP HL;2U
Solar/Wind Harmer
0.254
965931AG1-462 GEN
Solar/Wind Harmer
18.79
965091AG1-374 GEN
Solar/Wind Harmer
19.661
276686W4-005 GEN3
Solar/Wind Harmer
0.001
990407J1304
External Queue
4.24149227142334
991303J1755 G
External Queue
4.699468612670898
990582J1340
External Queue
21.8123722076416
990662J1358
External Queue
15.139077186584473
990512J1326
External Queue
5.464118957519531
991092J1477
External Queue
2.8750312328338623
990577J1339
External Queue
21.8123722076416
990647J1355
External Queue
42.76608657836914
991247J1684 G
External Queue
28.054828643798828
990547J1333 G
External Queue
34.15701675415039
990552J1334 G
External Queue
34.15701675415039
990557J1335 G
External Queue
34.15701675415039
990562J1336 G
External Queue
34.15701675415039
990762J1386
External Queue
10.359478950500488
991777J1629 G
External Queue
12.388229370117188
991332J1785
External Queue
12.013145446777344
991337J1802
External Queue
7.676261901855469
990117J1214
External Queue
18.796567916870117
990727J1377 G
External Queue
6.363696098327637
NYPJM->LTFIMP_NY
CLTF
1.15
TVALTFEXP_TVA->PJM
CLTF
1.346
LAGNLTFEXP_LAGN->PJM
CLTF
4.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.618
WECLTFEXP_WEC->PJM
CLTF
4.549
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.386
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.212
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
MECLTFEXP_MEC->PJM
CLTF
14.351
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.034
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.8 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2297.61
MW Contribution:16.45
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
9.826
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
11.59
274777LINCOLN ;8U
Adder
11.59
274675JOLIET 29;7U
Adder
41.051
274675JOLIET 29;7U
Adder
39.585
970833AG2-524 GEN
Solar/Wind Harmer
9.94
970833AG2-524 GEN
Solar/Wind Harmer
6.627
276868AE1-113 GEN
Solar/Wind Harmer
1.713
971411AH1-196 GEN
Solar/Wind Harmer
12.725
971675AH1-338 GEN
Solar/Wind Harmer
3.291
971171AH1-044 GEN
Solar/Wind Harmer
16.7
274823ROCKFORD ;21
Adder
23.249
946321AF1-296 GEN
Solar/Wind Harmer
4.171
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
5.72
274724RIVER EC ;11
50/50
31.802
957371AF2-031 GEN
50/50
1.574
274800UNIV PARK;3U
Adder
8.394
970941AG2-585 GEN
Solar/Wind Harmer
12.282
274802UNIV PARK;5U
Adder
8.076
274772LINCOLN ;3U
Adder
11.59
276893AG1-478 C
Solar/Wind Harmer
0.372
274729ELWOOD EC;1P
Adder
21.774
276897AD1-100 C
Solar/Wind Harmer
0.012
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.901
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.151
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
16.178
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.26
942111AE2-223 GEN
Solar/Wind Harmer
2.231
971993AH1-541 GEN
Solar/Wind Harmer
2.515
276621W2-048 GEN
Solar/Wind Harmer
0.262
276838X2-022 GEN2
Solar/Wind Harmer
0.293
942481AE2-261 GEN
Solar/Wind Harmer
14.075
274888KELLY CRK;1U
Solar/Wind Harmer
0.577
274770LINCOLN ;1U
Adder
11.59
274771LINCOLN ;2U
Adder
11.59
972259AH1-714 GEN
Adder
25.222
274808UNIV PK N;4U
Adder
6.517
274696ROCKY RD ;4P
Adder
14.393
274697ROCKY RD ;3P
Adder
3.82
962691AG1-118 GEN
Solar/Wind Harmer
25.992
274856ECOGROVE ;U1
Solar/Wind Harmer
0.194
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.589
274762LEE CO EC;3U
Adder
10.724
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.259
274803UNIV PARK;6U
Adder
8.076
274674JOLIET 9 ;6U
Adder
20.714
958481AF2-142 GEN
Solar/Wind Harmer
13.413
274862TOP CROP ;2U
Solar/Wind Harmer
1.206
274683WAUKEGAN ;8U
Adder
26.649
274683WAUKEGAN ;8U
Adder
22.464
274693ROCKY RD ;1P
Adder
13.923
970921AG2-575 GEN
Solar/Wind Harmer
8.625
970921AG2-575 GEN
Solar/Wind Harmer
2.875
274879MINONK ;1U
Solar/Wind Harmer
0.36
971335AH1-147 GEN
Solar/Wind Harmer
16.917
274764LEE CO EC;5U
Adder
10.749
972267AH1-718 GEN
Adder
4.705
276708O09 GEN2
Solar/Wind Harmer
0.278
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.185
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
14.149
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.652
274695ROCKY RD ;2P
Adder
14.061
958491AF2-143 GEN
Solar/Wind Harmer
13.029
942991AE2-321 GEN
Solar/Wind Harmer
9.55
971333AH1-146 GEN
Solar/Wind Harmer
16.917
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274765LEE CO EC;6U
Adder
10.749
274763LEE CO EC;4U
Adder
10.623
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.299
276911AD2-131_GEN
Solar/Wind Harmer
0.632
274826FISK ;BP
50/50
16.786
972228AH1-698 GEN2
Adder
4.962
274730ELWOOD EC;6P
Adder
21.778
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.902
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
10.307
274855GSG-6 ;RU
Solar/Wind Harmer
0.309
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
959611AF2-252 GEN
Solar/Wind Harmer
2.185
274776LINCOLN ;7U
Adder
11.59
274687WILL CNTY;4U
Adder
37.915
274687WILL CNTY;4U
Adder
37.915
274731ELWOOD EC;2P
Adder
21.774
274733ELWOOD EC;3P
Adder
21.774
274814UNIV PK N;0U
Adder
6.603
274807UNIV PK N;3U
Adder
6.589
274805UNIV PK N;1U
Adder
6.56
274746AC1-111 G10
Adder
7.182
276882AE2-255 GEN
Solar/Wind Harmer
0.998
926823AC1-168 GEN
Solar/Wind Harmer
1.354
276655WTG1_EQ
Solar/Wind Harmer
0.003
944221AF1-090 GEN
Solar/Wind Harmer
2.406
276806AD2-047 C O1
Solar/Wind Harmer
5.568
274676JOLIET 29;8U
Adder
39.585
274734ELWOOD EC;8P
Adder
21.778
274736ELWOOD EC;9P
Adder
21.778
943121AE2-341 GEN
Solar/Wind Harmer
14.998
943591AF1-030 GEN
Solar/Wind Harmer
9.974
274682WAUKEGAN ;7U
Adder
22.781
959091AF2-200 GEN
Solar/Wind Harmer
16.7
274767LEE CO EC;8U
Adder
10.598
276668AB2-070 GEN1
Solar/Wind Harmer
0.198
961501AF2-441 GEN
50/50
15.114
274827FISK ;RP
50/50
11.896
972227AH1-698 GEN1
Adder
3.493
274735ELWOOD EC;4P
Adder
21.774
274811UNIV PK N;7U
Adder
6.546
274744AC1-111 GEN8
Adder
7.182
961011AF2-392 GEN
Solar/Wind Harmer
4.645
970169AG2-114 GEN
Solar/Wind Harmer
7.664
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
7.208
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.198
276848AB2-070 GEN3
Solar/Wind Harmer
0.197
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.083
274872LEEDK;1U
Solar/Wind Harmer
0.005
959081AF2-199 GEN
Solar/Wind Harmer
8.35
971067AG2-660 GEN
Solar/Wind Harmer
2.783
274822ROCKFORD ;11
Adder
23.418
970819AG2-516 GEN
Solar/Wind Harmer
9.885
971475AH1-234 GEN
Solar/Wind Harmer
3.982
276726Z2-087_GEN
Solar/Wind Harmer
0.002
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
274723RIVER EC ;12
50/50
31.772
274801UNIV PARK;4U
Adder
8.394
274773LINCOLN ;4U
Adder
11.59
274774LINCOLN ;5U
Adder
11.59
274751CRETE EC ;1U
Adder
10.307
276861AD2-134 GEN
Solar/Wind Harmer
0.151
971997AH1-543 GEN
Solar/Wind Harmer
4.397
970569AG2-363 GEN
Solar/Wind Harmer
24.267
274761LEE CO EC;2U
Adder
10.724
276158O29GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.61
972175AH1-670 GEN
Solar/Wind Harmer
4.931
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972179AH1-673 GEN
50/50
16.446
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274676JOLIET 29;8U
Adder
41.051
274812UNIV PK N;8U
Adder
6.546
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.182
274682WAUKEGAN ;7U
Adder
22.781
274828WAUKEGAN ;BP
Adder
13.969
276901AD2-066 C O1
Solar/Wind Harmer
0.008
957471AF2-041 GEN
Solar/Wind Harmer
25.05
274877BISHOP HL;1U
Solar/Wind Harmer
0.254
274674JOLIET 9 ;6U
Adder
20.714
274732ELWOOD EC;7P
Adder
21.778
274754CRETE EC ;4U
Adder
10.307
962781AG1-127 GEN
Solar/Wind Harmer
8.208
939401AE1-172 GEN
Solar/Wind Harmer
6.239
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.993
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274766LEE CO EC;7U
Adder
10.598
963831AG1-236 GEN
Solar/Wind Harmer
2.091
276615X2-022 GEN
Solar/Wind Harmer
0.055
965911AG1-460 GEN
Solar/Wind Harmer
0.941
274728ELWOOD EC;5P
Adder
21.778
971177AH1-047 GEN
Solar/Wind Harmer
5.269
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
13.037
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.251
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971341AH1-150 GEN
Solar/Wind Harmer
16.7
971343AH1-151 GEN
Solar/Wind Harmer
16.7
276741O09 GEN1
Solar/Wind Harmer
0.278
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
9.598
972038AH1-567 GEN2
Adder
0.525
274753CRETE EC ;3U
Adder
10.307
274872LEEDK;1U
Solar/Wind Harmer
0.315
972236AH1-702 GEN2
Adder
2.603
274760LEE CO EC;1U
Adder
10.724
274878BISHOP HL;2U
Solar/Wind Harmer
0.254
965931AG1-462 GEN
Solar/Wind Harmer
18.79
965091AG1-374 GEN
Solar/Wind Harmer
19.661
276686W4-005 GEN3
Solar/Wind Harmer
0.001
990407J1304
External Queue
4.24149227142334
991303J1755 G
External Queue
4.699468612670898
990582J1340
External Queue
21.8123722076416
990662J1358
External Queue
15.139077186584473
990512J1326
External Queue
5.464118957519531
991092J1477
External Queue
2.8750312328338623
990577J1339
External Queue
21.8123722076416
990647J1355
External Queue
42.76608657836914
991247J1684 G
External Queue
28.054828643798828
990547J1333 G
External Queue
34.15701675415039
990552J1334 G
External Queue
34.15701675415039
990557J1335 G
External Queue
34.15701675415039
990562J1336 G
External Queue
34.15701675415039
990762J1386
External Queue
10.359478950500488
991777J1629 G
External Queue
12.388229370117188
991332J1785
External Queue
12.013145446777344
991337J1802
External Queue
7.676261901855469
990117J1214
External Queue
18.796567916870117
990727J1377 G
External Queue
6.363696098327637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.618
WECLTFEXP_WEC->PJM
CLTF
4.549
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.386
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.212
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
MECLTFEXP_MEC->PJM
CLTF
14.351
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.034
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
NYPJM->LTFIMP_NY
CLTF
1.15
TVALTFEXP_TVA->PJM
CLTF
1.346
LAGNLTFEXP_LAGN->PJM
CLTF
4.987

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-1


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.06 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2173.47
MW Contribution:14.85
Bus #Bus NameTypeMW Contribution
274754CRETE EC ;4U
50/50
6.972
274674JOLIET 9 ;6U
Adder
16.382
274732ELWOOD EC;7P
Adder
17.371
276876AE1-163_GEN2
Solar/Wind Harmer
6.384
962781AG1-127 GEN
Solar/Wind Harmer
8.671
972235AH1-702 GEN1
Adder
2.245
939401AE1-172 GEN
Solar/Wind Harmer
12.327
972037AH1-567 GEN1
Adder
0.22
960591AF2-350 GEN
Solar/Wind Harmer
11.589
274675JOLIET 29;7U
Adder
32.84
274675JOLIET 29;7U
Adder
31.667
970833AG2-524 GEN
Solar/Wind Harmer
8.503
970833AG2-524 GEN
Solar/Wind Harmer
3.955
276868AE1-113 GEN
Solar/Wind Harmer
9.754
971411AH1-196 GEN
Solar/Wind Harmer
13.697
971675AH1-338 GEN
Solar/Wind Harmer
16.12
274728ELWOOD EC;5P
Adder
17.371
971177AH1-047 GEN
Solar/Wind Harmer
5.384
276612AE2-035 GEN
Solar/Wind Harmer
2.26
971681AH1-341 GEN
Solar/Wind Harmer
13.054
274863CRW1-WTG
Solar/Wind Harmer
4.746
274864CRW2-WTG
Solar/Wind Harmer
4.746
957751AF2-069 GEN
Solar/Wind Harmer
0.383
274723RIVER EC ;12
50/50
28.753
274751CRETE EC ;1U
50/50
6.972
274809UNIV PK N;5U
50/50
0.365
966431AG1-512 GEN
50/50
2.343
274801UNIV PARK;4U
Adder
7.042
970569AG2-363 GEN
Solar/Wind Harmer
27.387
971997AH1-543 GEN
Solar/Wind Harmer
14.261
276861AD2-134 GEN
Solar/Wind Harmer
1.599
274773LINCOLN ;4U
Adder
5.515
274774LINCOLN ;5U
Adder
5.515
274761LEE CO EC;2U
Adder
8.049
276158O29GEN2
Solar/Wind Harmer
4.219
274814UNIV PK N;0U
50/50
6.75
274807UNIV PK N;3U
50/50
6.736
274805UNIV PK N;1U
50/50
6.706
960681AF2-359 GEN
Solar/Wind Harmer
5.525
274687WILL CNTY;4U
Adder
30.801
274687WILL CNTY;4U
Adder
30.801
274731ELWOOD EC;2P
Adder
17.362
274733ELWOOD EC;3P
Adder
17.362
276882AE2-255 GEN
Solar/Wind Harmer
3.252
274746AC1-111 G10
Adder
5.294
274776LINCOLN ;7U
Adder
5.515
926823AC1-168 GEN
Solar/Wind Harmer
3.743
276655WTG1_EQ
Solar/Wind Harmer
6.393
276691AA1-018 GEN1
Solar/Wind Harmer
0.486
941551AE2-152 GEN
Solar/Wind Harmer
4.547
274872LEEDK;1U
Solar/Wind Harmer
7.455
274822ROCKFORD ;11
Adder
17.573
959081AF2-199 GEN
Solar/Wind Harmer
8.922
971067AG2-660 GEN
Solar/Wind Harmer
2.075
970819AG2-516 GEN
Solar/Wind Harmer
10.64
971475AH1-234 GEN
Solar/Wind Harmer
19.807
276726Z2-087_GEN
Solar/Wind Harmer
3.571
961501AF2-441 GEN
50/50
13.333
274811UNIV PK N;7U
50/50
6.692
274827FISK ;RP
50/50
10.094
972227AH1-698 GEN1
Adder
2.791
274735ELWOOD EC;4P
Adder
17.362
274744AC1-111 GEN8
Adder
5.294
961011AF2-392 GEN
Solar/Wind Harmer
9.267
274848CAMPGROVE;RU
Solar/Wind Harmer
5.28
970169AG2-114 GEN
Solar/Wind Harmer
8.142
972179AH1-673 GEN
50/50
14.849
274813UNIV PK N;9U
50/50
0.367
274812UNIV PK N;8U
50/50
6.692
276164X3-005 C
Solar/Wind Harmer
0.958
276776AD2-060 GEN
Solar/Wind Harmer
0.49
274676JOLIET 29;8U
Adder
32.842
274682WAUKEGAN ;7U
Adder
17.388
274871GR RIDGE ;2U
Solar/Wind Harmer
7.436
274828WAUKEGAN ;BP
Adder
10.66
276901AD2-066 C O1
Solar/Wind Harmer
3.358
274745AC1-111 GEN9
Adder
5.294
960751AF2-366 GEN
Solar/Wind Harmer
2.616
957471AF2-041 GEN
Solar/Wind Harmer
26.767
972207SS24-0001
Solar/Wind Harmer
19.609
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
965681AG1-436 GEN
Solar/Wind Harmer
18.282
274847GR RIDGE ;BU
Solar/Wind Harmer
4.892
971341AH1-150 GEN
Solar/Wind Harmer
17.845
971343AH1-151 GEN
Solar/Wind Harmer
17.845
276741O09 GEN1
Solar/Wind Harmer
3.013
274849CRESCENT ;1U
Solar/Wind Harmer
1.542
274810UNIV PK N;6U
50/50
0.366
972181SS23-001
Solar/Wind Harmer
7.973
276806AD2-047 C O1
Solar/Wind Harmer
12.398
274676JOLIET 29;8U
Adder
31.669
274734ELWOOD EC;8P
Adder
17.371
274736ELWOOD EC;9P
Adder
17.371
274682WAUKEGAN ;7U
Adder
17.388
943121AE2-341 GEN
Solar/Wind Harmer
13.826
943591AF1-030 GEN
Solar/Wind Harmer
9.217
959091AF2-200 GEN
Solar/Wind Harmer
17.845
274767LEE CO EC;8U
Adder
7.954
274808UNIV PK N;4U
50/50
6.662
274888KELLY CRK;1U
Solar/Wind Harmer
6.842
972259AH1-714 GEN
Adder
18.776
274696ROCKY RD ;4P
Adder
10.753
274697ROCKY RD ;3P
Adder
2.854
962691AG1-118 GEN
Solar/Wind Harmer
27.46
274770LINCOLN ;1U
Adder
5.515
274771LINCOLN ;2U
Adder
5.515
274856ECOGROVE ;U1
Solar/Wind Harmer
2.978
276611AD2-172 GEN
Solar/Wind Harmer
2.26
938861AE1-114 GEN
Solar/Wind Harmer
7.139
274762LEE CO EC;3U
Adder
8.049
276603SUBLETTE C
Solar/Wind Harmer
0.903
276645AC1-214 GEN1
Solar/Wind Harmer
1.117
274724RIVER EC ;11
50/50
28.7
957371AF2-031 GEN
50/50
1.421
274800UNIV PARK;3U
Adder
7.042
274802UNIV PARK;5U
Adder
7.024
970941AG2-585 GEN
Solar/Wind Harmer
14.487
276893AG1-478 C
Solar/Wind Harmer
0.451
274729ELWOOD EC;1P
Adder
17.362
276805AD2-038 GEN
Solar/Wind Harmer
5.156
276897AD1-100 C
Solar/Wind Harmer
29.097
276889AE2-281 GEN
Solar/Wind Harmer
1.824
970571AG2-364 GEN
Solar/Wind Harmer
18.258
276799AD1-013 GEN
Solar/Wind Harmer
1.981
946671AF1-331 GEN
Solar/Wind Harmer
0.375
274850MENDOTA H;RU
Solar/Wind Harmer
2.299
276602WESTBROOK C
Solar/Wind Harmer
1.903
276863AD2-134 GEN
Solar/Wind Harmer
1.599
274772LINCOLN ;3U
Adder
5.515
274858EASY ROAD;U2
Solar/Wind Harmer
4.146
276157O29GEN1
Solar/Wind Harmer
3.209
274823ROCKFORD ;21
Adder
17.445
971171AH1-044 GEN
Solar/Wind Harmer
17.845
274775LINCOLN ;6U
Adder
5.515
274777LINCOLN ;8U
Adder
5.515
946321AF1-296 GEN
Solar/Wind Harmer
8.404
274857EASY ROAD;U1
Solar/Wind Harmer
4.146
274766LEE CO EC;7U
Adder
7.954
274803UNIV PARK;6U
Adder
7.024
274887GEN-1.85
Solar/Wind Harmer
6.177
274674JOLIET 9 ;6U
Adder
16.382
274862TOP CROP ;2U
Solar/Wind Harmer
5.287
958481AF2-142 GEN
Solar/Wind Harmer
15.669
274683WAUKEGAN ;8U
Adder
20.336
274683WAUKEGAN ;8U
Adder
17.142
274879MINONK ;1U
Solar/Wind Harmer
6.503
274693ROCKY RD ;1P
Adder
10.402
970921AG2-575 GEN
Solar/Wind Harmer
9.117
970921AG2-575 GEN
Solar/Wind Harmer
2.12
971335AH1-147 GEN
Solar/Wind Harmer
18.129
274764LEE CO EC;5U
Adder
8.068
972267AH1-718 GEN
Adder
3.533
276708O09 GEN2
Solar/Wind Harmer
3.013
276782AC1-033 GEN
Solar/Wind Harmer
3.295
274752CRETE EC ;2U
50/50
6.972
274806UNIV PK N;2U
50/50
0.374
274815UNIV PK N;XU
50/50
0.368
274826FISK ;BP
50/50
14.243
972231SS25-0005
Solar/Wind Harmer
12.757
276772AC2-154 GEN
Solar/Wind Harmer
3.232
972228AH1-698 GEN2
Adder
3.966
274730ELWOOD EC;6P
Adder
17.371
276694AA1-018 GEN2
Solar/Wind Harmer
6.592
939351AE1-166 GEN
Solar/Wind Harmer
5.945
970707AG2-453 GEN
Solar/Wind Harmer
25.251
274855GSG-6 ;RU
Solar/Wind Harmer
3.306
965791AG1-447 GEN
Solar/Wind Harmer
9.353
958011AF2-095 GEN
Solar/Wind Harmer
16.689
276843GEN-1.7
Solar/Wind Harmer
0.665
274861TOP CROP ;1U
Solar/Wind Harmer
6.332
958491AF2-143 GEN
Solar/Wind Harmer
15.077
276872AE1-163_GEN1
Solar/Wind Harmer
6.384
274695ROCKY RD ;2P
Adder
10.505
942991AE2-321 GEN
Solar/Wind Harmer
9.2
971573AH1-285 GEN
Solar/Wind Harmer
7.905
971333AH1-146 GEN
Solar/Wind Harmer
18.129
274765LEE CO EC;6U
Adder
8.068
274763LEE CO EC;4U
Adder
7.973
274851PROVIDENC;RU
Solar/Wind Harmer
2.375
276646AC1-214 GEN2
Solar/Wind Harmer
1.117
274753CRETE EC ;3U
50/50
6.972
274816UNIV PK N;YU
50/50
0.367
972038AH1-567 GEN2
Adder
0.441
274872LEEDK;1U
Solar/Wind Harmer
0.232
972236AH1-702 GEN2
Adder
1.952
274760LEE CO EC;1U
Adder
8.049
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.332
990582J1340
External Queue
26.695417404174805
990662J1358
External Queue
16.238128662109375
990512J1326
External Queue
4.073311805725098
990577J1339
External Queue
26.695417404174805
990647J1355
External Queue
44.529808044433594
991247J1684 G
External Queue
32.260398864746094
990547J1333 G
External Queue
37.6640739440918
990552J1334 G
External Queue
37.6640739440918
990557J1335 G
External Queue
37.6640739440918
990562J1336 G
External Queue
37.6640739440918
990762J1386
External Queue
13.060995101928711
991332J1785
External Queue
12.545342445373535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.084
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.138
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.654
AH1-155LTFEXP_AH1-155->PJM
LTF
0.832
NYPJM->LTFIMP_NY
CLTF
0.863
TVALTFEXP_TVA->PJM
CLTF
1.06
LAGNLTFEXP_LAGN->PJM
CLTF
3.848
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.38
WECLTFEXP_WEC->PJM
CLTF
3.459
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.249
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.639
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.298
MECLTFEXP_MEC->PJM
CLTF
10.891
AG2-052LTFEXP_AG2-052->PJM
LTF
0.555

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-2


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2145.4
MW Contribution:14.86
Bus #Bus NameTypeMW Contribution
274728ELWOOD EC;5P
Adder
17.386
971177AH1-047 GEN
Solar/Wind Harmer
5.389
276612AE2-035 GEN
Solar/Wind Harmer
2.262
971681AH1-341 GEN
Solar/Wind Harmer
13.067
274863CRW1-WTG
Solar/Wind Harmer
4.751
274864CRW2-WTG
Solar/Wind Harmer
4.751
957751AF2-069 GEN
Solar/Wind Harmer
0.383
274723RIVER EC ;12
50/50
28.77
274751CRETE EC ;1U
50/50
6.976
274809UNIV PK N;5U
50/50
0.365
966431AG1-512 GEN
50/50
2.344
274801UNIV PARK;4U
Adder
7.047
970569AG2-363 GEN
Solar/Wind Harmer
27.413
971997AH1-543 GEN
Solar/Wind Harmer
14.275
276861AD2-134 GEN
Solar/Wind Harmer
1.601
274773LINCOLN ;4U
Adder
5.521
274774LINCOLN ;5U
Adder
5.521
274761LEE CO EC;2U
Adder
8.057
276158O29GEN2
Solar/Wind Harmer
4.223
939741AE1-205 GEN
Solar/Wind Harmer
10.499
274814UNIV PK N;0U
50/50
6.755
274807UNIV PK N;3U
50/50
6.74
274805UNIV PK N;1U
50/50
6.711
274687WILL CNTY;4U
Adder
30.826
274687WILL CNTY;4U
Adder
30.826
274731ELWOOD EC;2P
Adder
17.376
274733ELWOOD EC;3P
Adder
17.376
276882AE2-255 GEN
Solar/Wind Harmer
3.255
274746AC1-111 G10
Adder
5.299
274776LINCOLN ;7U
Adder
5.521
926823AC1-168 GEN
Solar/Wind Harmer
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.4
960681AF2-359 GEN
Solar/Wind Helper
0.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.487
941551AE2-152 GEN
Solar/Wind Harmer
4.551
274872LEEDK;1U
Solar/Wind Harmer
7.462
274822ROCKFORD ;11
Adder
17.59
959081AF2-199 GEN
Solar/Wind Harmer
8.931
971067AG2-660 GEN
Solar/Wind Harmer
2.077
970819AG2-516 GEN
Solar/Wind Harmer
10.65
971475AH1-234 GEN
Solar/Wind Harmer
19.826
276726Z2-087_GEN
Solar/Wind Harmer
5.798
961501AF2-441 GEN
50/50
13.341
274811UNIV PK N;7U
50/50
6.696
274827FISK ;RP
50/50
10.102
972227AH1-698 GEN1
Adder
2.793
274735ELWOOD EC;4P
Adder
17.376
274744AC1-111 GEN8
Adder
5.299
961011AF2-392 GEN
Solar/Wind Harmer
9.277
274848CAMPGROVE;RU
Solar/Wind Harmer
5.286
970169AG2-114 GEN
Solar/Wind Harmer
8.151
972179AH1-673 GEN
50/50
14.858
274813UNIV PK N;9U
50/50
0.367
274812UNIV PK N;8U
50/50
6.696
276164X3-005 C
Solar/Wind Harmer
0.959
276776AD2-060 GEN
Solar/Wind Harmer
0.49
274676JOLIET 29;8U
Adder
32.869
274682WAUKEGAN ;7U
Adder
17.404
274871GR RIDGE ;2U
Solar/Wind Harmer
7.443
274828WAUKEGAN ;BP
Adder
10.669
276901AD2-066 C O1
Solar/Wind Harmer
3.361
274745AC1-111 GEN9
Adder
5.299
960751AF2-366 GEN
Solar/Wind Harmer
2.618
957471AF2-041 GEN
Solar/Wind Harmer
26.794
972207SS24-0001
Solar/Wind Harmer
19.628
274877BISHOP HL;1U
Solar/Wind Harmer
2.791
274847GR RIDGE ;BU
Solar/Wind Harmer
4.896
971341AH1-150 GEN
Solar/Wind Harmer
17.862
971343AH1-151 GEN
Solar/Wind Harmer
17.862
276741O09 GEN1
Solar/Wind Harmer
3.017
274849CRESCENT ;1U
Solar/Wind Harmer
1.543
274810UNIV PK N;6U
50/50
0.366
972181SS23-001
Solar/Wind Harmer
7.978
276806AD2-047 C O1
Solar/Wind Harmer
12.407
274676JOLIET 29;8U
Adder
31.695
274734ELWOOD EC;8P
Adder
17.386
274736ELWOOD EC;9P
Adder
17.386
274682WAUKEGAN ;7U
Adder
17.404
943121AE2-341 GEN
Solar/Wind Harmer
13.839
943591AF1-030 GEN
Solar/Wind Harmer
9.226
959091AF2-200 GEN
Solar/Wind Harmer
17.862
274767LEE CO EC;8U
Adder
7.962
274808UNIV PK N;4U
50/50
6.667
274888KELLY CRK;1U
Solar/Wind Harmer
6.847
972259AH1-714 GEN
Adder
18.793
274696ROCKY RD ;4P
Adder
10.763
274697ROCKY RD ;3P
Adder
2.856
962691AG1-118 GEN
Solar/Wind Harmer
27.486
274770LINCOLN ;1U
Adder
5.521
274771LINCOLN ;2U
Adder
5.521
274856ECOGROVE ;U1
Solar/Wind Harmer
2.981
276611AD2-172 GEN
Solar/Wind Harmer
2.262
938861AE1-114 GEN
Solar/Wind Harmer
7.146
274762LEE CO EC;3U
Adder
8.057
276603SUBLETTE C
Solar/Wind Harmer
0.903
276645AC1-214 GEN1
Solar/Wind Harmer
1.118
274724RIVER EC ;11
50/50
28.716
957371AF2-031 GEN
50/50
1.422
274800UNIV PARK;3U
Adder
7.047
274802UNIV PARK;5U
Adder
7.029
970941AG2-585 GEN
Solar/Wind Harmer
14.498
276893AG1-478 C
Solar/Wind Harmer
0.452
274729ELWOOD EC;1P
Adder
17.376
276805AD2-038 GEN
Solar/Wind Harmer
5.161
276897AD1-100 C
Solar/Wind Harmer
29.122
276889AE2-281 GEN
Solar/Wind Harmer
1.826
970571AG2-364 GEN
Solar/Wind Harmer
18.275
276799AD1-013 GEN
Solar/Wind Harmer
1.983
946671AF1-331 GEN
Solar/Wind Harmer
0.375
274850MENDOTA H;RU
Solar/Wind Harmer
2.301
276602WESTBROOK C
Solar/Wind Harmer
1.905
276863AD2-134 GEN
Solar/Wind Harmer
1.601
274772LINCOLN ;3U
Adder
5.521
274858EASY ROAD;U2
Solar/Wind Harmer
4.15
276157O29GEN1
Solar/Wind Harmer
3.212
972037AH1-567 GEN1
Adder
0.221
960591AF2-350 GEN
Solar/Wind Harmer
11.598
274675JOLIET 29;7U
Adder
32.867
274675JOLIET 29;7U
Adder
31.693
970833AG2-524 GEN
Solar/Wind Harmer
8.511
970833AG2-524 GEN
Solar/Wind Harmer
3.958
276868AE1-113 GEN
Solar/Wind Harmer
9.763
971411AH1-196 GEN
Solar/Wind Harmer
13.71
971675AH1-338 GEN
Solar/Wind Harmer
16.136
274823ROCKFORD ;21
Adder
17.462
971171AH1-044 GEN
Solar/Wind Harmer
17.862
274775LINCOLN ;6U
Adder
5.521
274777LINCOLN ;8U
Adder
5.521
946321AF1-296 GEN
Solar/Wind Harmer
8.413
276656WTG2_EQ
Solar/Wind Harmer
0.847
941731AE2-173 GEN
Solar/Wind Harmer
3.052
274754CRETE EC ;4U
50/50
6.976
274674JOLIET 9 ;6U
Adder
16.396
274732ELWOOD EC;7P
Adder
17.386
276876AE1-163_GEN2
Solar/Wind Harmer
6.39
962781AG1-127 GEN
Solar/Wind Harmer
8.679
972235AH1-702 GEN1
Adder
2.247
939401AE1-172 GEN
Solar/Wind Harmer
12.339
274857EASY ROAD;U1
Solar/Wind Harmer
4.15
274766LEE CO EC;7U
Adder
7.962
274803UNIV PARK;6U
Adder
7.029
274887GEN-1.85
Solar/Wind Harmer
6.182
274674JOLIET 9 ;6U
Adder
16.396
274862TOP CROP ;2U
Solar/Wind Harmer
5.291
958481AF2-142 GEN
Solar/Wind Harmer
15.682
274683WAUKEGAN ;8U
Adder
20.354
274683WAUKEGAN ;8U
Adder
17.158
274879MINONK ;1U
Solar/Wind Harmer
6.509
274693ROCKY RD ;1P
Adder
10.411
970921AG2-575 GEN
Solar/Wind Harmer
9.126
970921AG2-575 GEN
Solar/Wind Harmer
2.122
971335AH1-147 GEN
Solar/Wind Harmer
18.147
274764LEE CO EC;5U
Adder
8.076
972267AH1-718 GEN
Adder
3.537
276708O09 GEN2
Solar/Wind Harmer
3.017
276782AC1-033 GEN
Solar/Wind Harmer
3.298
274752CRETE EC ;2U
50/50
6.976
274806UNIV PK N;2U
50/50
0.374
274815UNIV PK N;XU
50/50
0.368
274826FISK ;BP
50/50
14.253
972231SS25-0005
Solar/Wind Harmer
12.765
276772AC2-154 GEN
Solar/Wind Harmer
3.234
972228AH1-698 GEN2
Adder
3.969
274730ELWOOD EC;6P
Adder
17.386
276694AA1-018 GEN2
Solar/Wind Harmer
6.598
939351AE1-166 GEN
Solar/Wind Harmer
5.95
970707AG2-453 GEN
Solar/Wind Harmer
25.276
274855GSG-6 ;RU
Solar/Wind Harmer
3.31
276843GEN-1.7
Solar/Wind Harmer
0.665
958011AF2-095 GEN
Solar/Wind Harmer
16.701
274861TOP CROP ;1U
Solar/Wind Harmer
6.337
958491AF2-143 GEN
Solar/Wind Harmer
15.09
276872AE1-163_GEN1
Solar/Wind Harmer
6.39
274695ROCKY RD ;2P
Adder
10.515
942991AE2-321 GEN
Solar/Wind Harmer
9.209
971573AH1-285 GEN
Solar/Wind Harmer
7.912
971333AH1-146 GEN
Solar/Wind Harmer
18.147
274765LEE CO EC;6U
Adder
8.076
274763LEE CO EC;4U
Adder
7.981
274851PROVIDENC;RU
Solar/Wind Harmer
2.377
276646AC1-214 GEN2
Solar/Wind Harmer
1.118
274753CRETE EC ;3U
50/50
6.976
274816UNIV PK N;YU
50/50
0.367
972038AH1-567 GEN2
Adder
0.441
274872LEEDK;1U
Solar/Wind Harmer
0.232
972236AH1-702 GEN2
Adder
1.954
274760LEE CO EC;1U
Adder
8.057
274878BISHOP HL;2U
Solar/Wind Harmer
2.791
965931AG1-462 GEN
Solar/Wind Harmer
20.355
990582J1340
External Queue
26.695417404174805
990662J1358
External Queue
16.238128662109375
990512J1326
External Queue
4.073311805725098
990577J1339
External Queue
26.695417404174805
990647J1355
External Queue
44.529808044433594
991247J1684 G
External Queue
32.260398864746094
990547J1333 G
External Queue
37.6640739440918
990552J1334 G
External Queue
37.6640739440918
990557J1335 G
External Queue
37.6640739440918
990562J1336 G
External Queue
37.6640739440918
990762J1386
External Queue
13.060995101928711
991332J1785
External Queue
12.545342445373535
NYPJM->LTFIMP_NY
CLTF
0.857
TVALTFEXP_TVA->PJM
CLTF
1.069
LAGNLTFEXP_LAGN->PJM
CLTF
3.866
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.508
WECLTFEXP_WEC->PJM
CLTF
3.463
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.244
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.757
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.292
MECLTFEXP_MEC->PJM
CLTF
10.905
AG2-052LTFEXP_AG2-052->PJM
LTF
0.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.118
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.636
AH1-155LTFEXP_AH1-155->PJM
LTF
0.832

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.12 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2008.87
MW Contribution:12.84
Bus #Bus NameTypeMW Contribution
276843GEN-1.7
Solar/Wind Harmer
0.563
958011AF2-095 GEN
Solar/Wind Harmer
14.146
274861TOP CROP ;1U
Solar/Wind Harmer
5.388
971573AH1-285 GEN
Solar/Wind Harmer
7.528
274695ROCKY RD ;2P
Adder
9.715
958491AF2-143 GEN
Solar/Wind Harmer
12.974
942991AE2-321 GEN
Solar/Wind Harmer
8.47
971333AH1-146 GEN
Solar/Wind Harmer
16.744
276872AE1-163_GEN1
Solar/Wind Harmer
5.557
274765LEE CO EC;6U
Adder
7.419
274763LEE CO EC;4U
Adder
7.332
274851PROVIDENC;RU
Solar/Wind Harmer
2.133
276646AC1-214 GEN2
Solar/Wind Harmer
1.003
276806AD2-047 C O1
Solar/Wind Harmer
10.508
972181SS23-001
Solar/Wind Harmer
5.625
274676JOLIET 29;8U
Adder
27.588
274734ELWOOD EC;8P
Adder
15.12
274736ELWOOD EC;9P
Adder
15.12
943121AE2-341 GEN
Solar/Wind Harmer
13.243
943591AF1-030 GEN
Solar/Wind Harmer
8.829
274682WAUKEGAN ;7U
Adder
15.783
959091AF2-200 GEN
Solar/Wind Harmer
16.52
274767LEE CO EC;8U
Adder
7.315
274814UNIV PK N;0U
Adder
4.832
274807UNIV PK N;3U
Adder
4.821
274805UNIV PK N;1U
Adder
4.8
274687WILL CNTY;4U
Adder
26.582
274687WILL CNTY;4U
Adder
26.582
274731ELWOOD EC;2P
Adder
15.116
274733ELWOOD EC;3P
Adder
15.116
274746AC1-111 G10
Adder
4.955
276882AE2-255 GEN
Solar/Wind Harmer
2.859
926823AC1-168 GEN
Solar/Wind Harmer
3.364
274776LINCOLN ;7U
Adder
4.097
276655WTG1_EQ
Solar/Wind Harmer
5.587
274888KELLY CRK;1U
Solar/Wind Harmer
5.8
274808UNIV PK N;4U
Adder
4.769
972259AH1-714 GEN
Adder
17.081
274697ROCKY RD ;3P
Adder
2.639
274696ROCKY RD ;4P
Adder
9.944
962691AG1-118 GEN
Solar/Wind Harmer
25.701
274856ECOGROVE ;U1
Solar/Wind Harmer
2.74
276611AD2-172 GEN
Solar/Wind Harmer
2.079
938861AE1-114 GEN
Solar/Wind Harmer
6.567
274762LEE CO EC;3U
Adder
7.402
276603SUBLETTE C
Solar/Wind Harmer
0.83
276645AC1-214 GEN1
Solar/Wind Harmer
1.003
274770LINCOLN ;1U
Adder
4.097
274724RIVER EC ;11
50/50
24.978
957371AF2-031 GEN
50/50
1.237
274800UNIV PARK;3U
Adder
6.047
274802UNIV PARK;5U
Adder
5.796
970941AG2-585 GEN
Solar/Wind Harmer
12.279
276893AG1-478 C
Solar/Wind Harmer
0.391
274729ELWOOD EC;1P
Adder
15.116
276805AD2-038 GEN
Solar/Wind Harmer
4.437
276799AD1-013 GEN
Solar/Wind Harmer
1.846
946671AF1-331 GEN
Solar/Wind Harmer
0.35
274850MENDOTA H;RU
Solar/Wind Harmer
2.142
276602WESTBROOK C
Solar/Wind Harmer
1.773
276863AD2-134 GEN
Solar/Wind Harmer
1.489
276897AD1-100 C
Solar/Wind Harmer
24.008
276889AE2-281 GEN
Solar/Wind Harmer
1.588
970571AG2-364 GEN
Solar/Wind Harmer
16.028
274858EASY ROAD;U2
Solar/Wind Harmer
3.813
276157O29GEN1
Solar/Wind Harmer
2.932
274772LINCOLN ;3U
Adder
4.097
274723RIVER EC ;12
50/50
24.885
274801UNIV PARK;4U
Adder
6.047
274751CRETE EC ;1U
Adder
4.635
276861AD2-134 GEN
Solar/Wind Harmer
1.489
971997AH1-543 GEN
Solar/Wind Harmer
12.986
970569AG2-363 GEN
Solar/Wind Harmer
24.043
274761LEE CO EC;2U
Adder
7.402
276158O29GEN2
Solar/Wind Harmer
3.855
274773LINCOLN ;4U
Adder
4.097
274774LINCOLN ;5U
Adder
4.097
939741AE1-205 GEN
Solar/Wind Harmer
1.728
961501AF2-441 GEN
50/50
11.515
274827FISK ;RP
50/50
8.583
274811UNIV PK N;7U
Adder
4.79
274735ELWOOD EC;4P
Adder
15.116
972227AH1-698 GEN1
Adder
2.352
274744AC1-111 GEN8
Adder
4.955
961011AF2-392 GEN
Solar/Wind Harmer
8.514
274848CAMPGROVE;RU
Solar/Wind Harmer
4.743
970169AG2-114 GEN
Solar/Wind Harmer
7.185
274826FISK ;BP
50/50
12.111
276772AC2-154 GEN
Solar/Wind Harmer
2.739
972231SS25-0005
Solar/Wind Harmer
9
274752CRETE EC ;2U
Adder
4.635
274730ELWOOD EC;6P
Adder
15.12
972228AH1-698 GEN2
Adder
3.343
970707AG2-453 GEN
Solar/Wind Harmer
24.989
276694AA1-018 GEN2
Solar/Wind Harmer
5.63
274855GSG-6 ;RU
Solar/Wind Harmer
3.08
939351AE1-166 GEN
Solar/Wind Harmer
4.905
274754CRETE EC ;4U
Adder
4.635
274674JOLIET 9 ;6U
Adder
14.509
274732ELWOOD EC;7P
Adder
15.12
962781AG1-127 GEN
Solar/Wind Harmer
8.111
276876AE1-163_GEN2
Solar/Wind Harmer
5.557
972235AH1-702 GEN1
Adder
2.067
274857EASY ROAD;U1
Solar/Wind Harmer
3.813
274766LEE CO EC;7U
Adder
7.315
939401AE1-172 GEN
Solar/Wind Harmer
10.332
972037AH1-567 GEN1
Adder
0.182
960591AF2-350 GEN
Solar/Wind Harmer
9.823
274675JOLIET 29;7U
Adder
28.61
274675JOLIET 29;7U
Adder
27.588
970833AG2-524 GEN
Solar/Wind Harmer
7.714
970833AG2-524 GEN
Solar/Wind Harmer
3.588
276868AE1-113 GEN
Solar/Wind Harmer
8.577
971411AH1-196 GEN
Solar/Wind Harmer
12.602
971675AH1-338 GEN
Solar/Wind Harmer
15.019
971171AH1-044 GEN
Solar/Wind Harmer
16.52
274823ROCKFORD ;21
Adder
16.058
946321AF1-296 GEN
Solar/Wind Harmer
7.682
274775LINCOLN ;6U
Adder
4.097
274777LINCOLN ;8U
Adder
4.097
276656WTG2_EQ
Solar/Wind Harmer
0.74
941731AE2-173 GEN
Solar/Wind Harmer
0.502
274728ELWOOD EC;5P
Adder
15.12
971177AH1-047 GEN
Solar/Wind Harmer
4.959
276612AE2-035 GEN
Solar/Wind Harmer
2.079
971681AH1-341 GEN
Solar/Wind Harmer
12.015
957751AF2-069 GEN
Solar/Wind Harmer
0.344
274863CRW1-WTG
Solar/Wind Harmer
4.029
274864CRW2-WTG
Solar/Wind Harmer
4.029
276691AA1-018 GEN1
Solar/Wind Harmer
0.415
274872LEEDK;1U
Solar/Wind Harmer
6.973
941551AE2-152 GEN
Solar/Wind Harmer
3.752
959081AF2-199 GEN
Solar/Wind Harmer
8.26
971067AG2-660 GEN
Solar/Wind Harmer
1.921
274822ROCKFORD ;11
Adder
16.175
970819AG2-516 GEN
Solar/Wind Harmer
9.785
971475AH1-234 GEN
Solar/Wind Harmer
18.197
276726Z2-087_GEN
Solar/Wind Harmer
5.061
274771LINCOLN ;2U
Adder
4.097
972179AH1-673 GEN
50/50
12.84
276164X3-005 C
Solar/Wind Harmer
0.819
276776AD2-060 GEN
Solar/Wind Harmer
0.415
274812UNIV PK N;8U
Adder
4.79
274676JOLIET 29;8U
Adder
28.61
274745AC1-111 GEN9
Adder
4.955
274682WAUKEGAN ;7U
Adder
15.783
274871GR RIDGE ;2U
Solar/Wind Harmer
6.749
274828WAUKEGAN ;BP
Adder
9.677
960751AF2-366 GEN
Solar/Wind Harmer
2.447
276901AD2-066 C O1
Solar/Wind Harmer
2.973
957471AF2-041 GEN
Solar/Wind Harmer
24.78
274877BISHOP HL;1U
Solar/Wind Harmer
2.51
972207SS24-0001
Solar/Wind Harmer
14.568
274847GR RIDGE ;BU
Solar/Wind Harmer
4.439
971341AH1-150 GEN
Solar/Wind Harmer
16.52
971343AH1-151 GEN
Solar/Wind Harmer
16.52
276741O09 GEN1
Solar/Wind Harmer
2.754
274849CRESCENT ;1U
Solar/Wind Harmer
1.385
274803UNIV PARK;6U
Adder
5.796
274887GEN-1.85
Solar/Wind Harmer
5.236
274674JOLIET 9 ;6U
Adder
14.509
958481AF2-142 GEN
Solar/Wind Harmer
13.381
274862TOP CROP ;2U
Solar/Wind Harmer
4.499
274683WAUKEGAN ;8U
Adder
18.461
274683WAUKEGAN ;8U
Adder
15.562
274693ROCKY RD ;1P
Adder
9.619
970921AG2-575 GEN
Solar/Wind Harmer
8.529
970921AG2-575 GEN
Solar/Wind Harmer
1.983
274879MINONK ;1U
Solar/Wind Harmer
5.719
971335AH1-147 GEN
Solar/Wind Harmer
16.744
274764LEE CO EC;5U
Adder
7.419
972267AH1-718 GEN
Adder
3.246
276708O09 GEN2
Solar/Wind Harmer
2.754
276782AC1-033 GEN
Solar/Wind Harmer
2.966
972038AH1-567 GEN2
Adder
0.379
274753CRETE EC ;3U
Adder
4.635
274872LEEDK;1U
Solar/Wind Harmer
0.217
972236AH1-702 GEN2
Adder
1.797
274760LEE CO EC;1U
Adder
7.402
274878BISHOP HL;2U
Solar/Wind Harmer
2.51
965931AG1-462 GEN
Solar/Wind Harmer
18.575
990582J1340
External Queue
21.04810905456543
990662J1358
External Queue
15.27561092376709
990577J1339
External Queue
21.04810905456543
990647J1355
External Queue
44.93280029296875
991247J1684 G
External Queue
27.28211784362793
990547J1333 G
External Queue
33.37971496582031
990552J1334 G
External Queue
33.37971496582031
990557J1335 G
External Queue
33.37971496582031
990562J1336 G
External Queue
33.37971496582031
990762J1386
External Queue
9.419135093688965
991332J1785
External Queue
13.058797836303711
991337J1802
External Queue
9.793804168701172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.279
MECLTFEXP_MEC->PJM
CLTF
9.903
AG2-052LTFEXP_AG2-052->PJM
LTF
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.795
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
AH1-155LTFEXP_AH1-155->PJM
LTF
0.801
NYPJM->LTFIMP_NY
CLTF
0.789
TVALTFEXP_TVA->PJM
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.486
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.624
WECLTFEXP_WEC->PJM
CLTF
3.148
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.222
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1974.3
MW Contribution:12.79
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
5.971
276806AD2-047 C O1
Solar/Wind Harmer
10.136
274676JOLIET 29;8U
Adder
25.45
274734ELWOOD EC;8P
Adder
13.956
274736ELWOOD EC;9P
Adder
13.956
274682WAUKEGAN ;7U
Adder
13.945
943121AE2-341 GEN
Solar/Wind Harmer
11.02
943591AF1-030 GEN
Solar/Wind Harmer
7.347
959091AF2-200 GEN
Solar/Wind Harmer
14.313
274767LEE CO EC;8U
Adder
6.394
274814UNIV PK N;0U
Adder
4.904
274807UNIV PK N;3U
Adder
4.894
274805UNIV PK N;1U
Adder
4.872
274687WILL CNTY;4U
Adder
24.874
274687WILL CNTY;4U
Adder
24.874
274731ELWOOD EC;2P
Adder
13.948
274733ELWOOD EC;3P
Adder
13.948
276882AE2-255 GEN
Solar/Wind Harmer
2.621
274746AC1-111 G10
Adder
4.23
274776LINCOLN ;7U
Adder
4.396
926823AC1-168 GEN
Solar/Wind Harmer
3.02
276655WTG1_EQ
Solar/Wind Harmer
5.245
274724RIVER EC ;11
50/50
24.848
957371AF2-031 GEN
50/50
1.23
274800UNIV PARK;3U
Adder
5.803
274802UNIV PARK;5U
Adder
5.65
970941AG2-585 GEN
Solar/Wind Harmer
11.843
276893AG1-478 C
Solar/Wind Harmer
0.366
274729ELWOOD EC;1P
Adder
13.948
276805AD2-038 GEN
Solar/Wind Harmer
4.161
276897AD1-100 C
Solar/Wind Harmer
23.39
276889AE2-281 GEN
Solar/Wind Harmer
1.473
970571AG2-364 GEN
Solar/Wind Harmer
14.756
276799AD1-013 GEN
Solar/Wind Harmer
1.587
946671AF1-331 GEN
Solar/Wind Harmer
0.301
274850MENDOTA H;RU
Solar/Wind Harmer
1.842
276602WESTBROOK C
Solar/Wind Harmer
1.525
276863AD2-134 GEN
Solar/Wind Harmer
1.281
274772LINCOLN ;3U
Adder
4.396
274858EASY ROAD;U2
Solar/Wind Harmer
3.333
276157O29GEN1
Solar/Wind Harmer
2.586
274723RIVER EC ;12
50/50
24.793
274751CRETE EC ;1U
50/50
5.221
274801UNIV PARK;4U
Adder
5.803
970569AG2-363 GEN
Solar/Wind Harmer
22.135
971997AH1-543 GEN
Solar/Wind Harmer
11.469
276861AD2-134 GEN
Solar/Wind Harmer
1.281
274773LINCOLN ;4U
Adder
4.396
274774LINCOLN ;5U
Adder
4.396
274761LEE CO EC;2U
Adder
6.471
276158O29GEN2
Solar/Wind Harmer
3.4
939741AE1-205 GEN
Solar/Wind Harmer
1.622
961501AF2-441 GEN
50/50
11.401
274827FISK ;RP
50/50
8.305
274811UNIV PK N;7U
Adder
4.862
972227AH1-698 GEN1
Adder
2.231
274735ELWOOD EC;4P
Adder
13.948
274744AC1-111 GEN8
Adder
4.23
961011AF2-392 GEN
Solar/Wind Harmer
7.457
274848CAMPGROVE;RU
Solar/Wind Harmer
4.279
970169AG2-114 GEN
Solar/Wind Harmer
6.61
274826FISK ;BP
50/50
11.719
274752CRETE EC ;2U
50/50
5.221
972231SS25-0005
Solar/Wind Harmer
9.553
276772AC2-154 GEN
Solar/Wind Harmer
2.642
972228AH1-698 GEN2
Adder
3.17
274730ELWOOD EC;6P
Adder
13.956
276694AA1-018 GEN2
Solar/Wind Harmer
5.317
939351AE1-166 GEN
Solar/Wind Harmer
4.779
274855GSG-6 ;RU
Solar/Wind Harmer
2.649
970707AG2-453 GEN
Solar/Wind Harmer
19.957
274754CRETE EC ;4U
50/50
5.221
274674JOLIET 9 ;6U
Adder
13.259
274732ELWOOD EC;7P
Adder
13.956
276876AE1-163_GEN2
Solar/Wind Harmer
5.157
962781AG1-127 GEN
Solar/Wind Harmer
6.939
972235AH1-702 GEN1
Adder
1.802
939401AE1-172 GEN
Solar/Wind Harmer
9.961
274857EASY ROAD;U1
Solar/Wind Harmer
3.333
274766LEE CO EC;7U
Adder
6.394
972037AH1-567 GEN1
Adder
0.177
960591AF2-350 GEN
Solar/Wind Harmer
9.475
274675JOLIET 29;7U
Adder
26.39
274675JOLIET 29;7U
Adder
25.448
970833AG2-524 GEN
Solar/Wind Harmer
6.795
970833AG2-524 GEN
Solar/Wind Harmer
3.16
276868AE1-113 GEN
Solar/Wind Harmer
7.862
971411AH1-196 GEN
Solar/Wind Harmer
10.985
274823ROCKFORD ;21
Adder
14.001
971675AH1-338 GEN
Solar/Wind Harmer
12.917
971171AH1-044 GEN
Solar/Wind Harmer
14.313
274775LINCOLN ;6U
Adder
4.396
274777LINCOLN ;8U
Adder
4.396
946321AF1-296 GEN
Solar/Wind Harmer
6.782
276656WTG2_EQ
Solar/Wind Harmer
0.694
941731AE2-173 GEN
Solar/Wind Harmer
0.471
274728ELWOOD EC;5P
Adder
13.956
971177AH1-047 GEN
Solar/Wind Harmer
4.317
276612AE2-035 GEN
Solar/Wind Harmer
1.815
971681AH1-341 GEN
Solar/Wind Harmer
10.49
274863CRW1-WTG
Solar/Wind Harmer
3.846
274864CRW2-WTG
Solar/Wind Harmer
3.846
957751AF2-069 GEN
Solar/Wind Harmer
0.31
276691AA1-018 GEN1
Solar/Wind Harmer
0.392
941551AE2-152 GEN
Solar/Wind Harmer
3.655
274872LEEDK;1U
Solar/Wind Harmer
5.967
274822ROCKFORD ;11
Adder
14.104
959081AF2-199 GEN
Solar/Wind Harmer
7.157
971067AG2-660 GEN
Solar/Wind Harmer
1.664
970819AG2-516 GEN
Solar/Wind Harmer
8.544
971475AH1-234 GEN
Solar/Wind Harmer
15.907
276726Z2-087_GEN
Solar/Wind Harmer
4.751
274808UNIV PK N;4U
Adder
4.841
274888KELLY CRK;1U
Solar/Wind Harmer
5.594
972259AH1-714 GEN
Adder
14.938
274696ROCKY RD ;4P
Adder
8.608
274697ROCKY RD ;3P
Adder
2.284
962691AG1-118 GEN
Solar/Wind Harmer
21.97
274770LINCOLN ;1U
Adder
4.396
274771LINCOLN ;2U
Adder
4.396
274856ECOGROVE ;U1
Solar/Wind Harmer
2.392
276611AD2-172 GEN
Solar/Wind Harmer
1.815
938861AE1-114 GEN
Solar/Wind Harmer
5.738
274762LEE CO EC;3U
Adder
6.471
276603SUBLETTE C
Solar/Wind Harmer
0.726
276645AC1-214 GEN1
Solar/Wind Harmer
0.904
276843GEN-1.7
Solar/Wind Harmer
0.543
958011AF2-095 GEN
Solar/Wind Harmer
13.644
274861TOP CROP ;1U
Solar/Wind Harmer
5.1
958491AF2-143 GEN
Solar/Wind Harmer
12.168
276872AE1-163_GEN1
Solar/Wind Harmer
5.157
274695ROCKY RD ;2P
Adder
8.409
942991AE2-321 GEN
Solar/Wind Harmer
7.376
971573AH1-285 GEN
Solar/Wind Harmer
6.307
971333AH1-146 GEN
Solar/Wind Harmer
14.536
274765LEE CO EC;6U
Adder
6.486
274763LEE CO EC;4U
Adder
6.41
274851PROVIDENC;RU
Solar/Wind Harmer
1.923
276646AC1-214 GEN2
Solar/Wind Harmer
0.904
972179AH1-673 GEN
50/50
12.786
276164X3-005 C
Solar/Wind Harmer
0.81
274812UNIV PK N;8U
Adder
4.862
276776AD2-060 GEN
Solar/Wind Harmer
0.401
274676JOLIET 29;8U
Adder
26.392
274682WAUKEGAN ;7U
Adder
13.945
274828WAUKEGAN ;BP
Adder
8.549
274871GR RIDGE ;2U
Solar/Wind Harmer
5.935
276901AD2-066 C O1
Solar/Wind Harmer
2.709
274745AC1-111 GEN9
Adder
4.23
960751AF2-366 GEN
Solar/Wind Harmer
2.093
957471AF2-041 GEN
Solar/Wind Harmer
21.47
972207SS24-0001
Solar/Wind Harmer
15.629
274877BISHOP HL;1U
Solar/Wind Harmer
2.257
274847GR RIDGE ;BU
Solar/Wind Harmer
3.904
971341AH1-150 GEN
Solar/Wind Harmer
14.313
971343AH1-151 GEN
Solar/Wind Harmer
14.313
276741O09 GEN1
Solar/Wind Harmer
2.429
274849CRESCENT ;1U
Solar/Wind Harmer
1.248
274803UNIV PARK;6U
Adder
5.65
274887GEN-1.85
Solar/Wind Harmer
5.05
274674JOLIET 9 ;6U
Adder
13.259
958481AF2-142 GEN
Solar/Wind Harmer
12.638
274862TOP CROP ;2U
Solar/Wind Harmer
4.259
274879MINONK ;1U
Solar/Wind Harmer
5.242
274683WAUKEGAN ;8U
Adder
16.31
274683WAUKEGAN ;8U
Adder
13.748
274693ROCKY RD ;1P
Adder
8.326
970921AG2-575 GEN
Solar/Wind Harmer
7.296
970921AG2-575 GEN
Solar/Wind Harmer
1.697
971335AH1-147 GEN
Solar/Wind Harmer
14.536
274764LEE CO EC;5U
Adder
6.486
972267AH1-718 GEN
Adder
2.843
276708O09 GEN2
Solar/Wind Harmer
2.429
276782AC1-033 GEN
Solar/Wind Harmer
2.667
274753CRETE EC ;3U
50/50
5.221
972038AH1-567 GEN2
Adder
0.363
274872LEEDK;1U
Solar/Wind Harmer
0.186
972236AH1-702 GEN2
Adder
1.567
274760LEE CO EC;1U
Adder
6.471
274878BISHOP HL;2U
Solar/Wind Harmer
2.257
965931AG1-462 GEN
Solar/Wind Harmer
16.418
990582J1340
External Queue
22.734060287475586
990662J1358
External Queue
17.02812957763672
990577J1339
External Queue
22.734060287475586
990647J1355
External Queue
44.96678161621094
991247J1684 G
External Queue
28.594083786010742
990547J1333 G
External Queue
34.311134338378906
990552J1334 G
External Queue
34.311134338378906
990557J1335 G
External Queue
34.311134338378906
990562J1336 G
External Queue
34.311134338378906
990762J1386
External Queue
10.402356147766113
991332J1785
External Queue
14.410825729370117
991337J1802
External Queue
10.868054389953613
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.731
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
AH1-155LTFEXP_AH1-155->PJM
LTF
0.799
NYPJM->LTFIMP_NY
CLTF
0.758
TVALTFEXP_TVA->PJM
CLTF
0.917
LAGNLTFEXP_LAGN->PJM
CLTF
3.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.616
WECLTFEXP_WEC->PJM
CLTF
2.779
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.007
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
MECLTFEXP_MEC->PJM
CLTF
8.864
AG2-052LTFEXP_AG2-052->PJM
LTF
0.533

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.35 %
Rating:1385.0 MVA
Rating Type:A
MVA to Mitigate:1472.96
MW Contribution:12.19
Bus #Bus NameTypeMW Contribution
972037AH1-567 GEN1
Adder
0.164
960591AF2-350 GEN
Solar/Wind Harmer
6.198
274675JOLIET 29;7U
Adder
24.583
274675JOLIET 29;7U
Adder
23.705
970833AG2-524 GEN
Solar/Wind Harmer
5.575
970833AG2-524 GEN
Solar/Wind Harmer
3.717
276868AE1-113 GEN
Solar/Wind Harmer
1.012
971411AH1-196 GEN
Solar/Wind Harmer
7.155
274775LINCOLN ;6U
Adder
5.693
274777LINCOLN ;8U
Adder
5.693
274823ROCKFORD ;21
Adder
13.066
971675AH1-338 GEN
Solar/Wind Harmer
1.824
971171AH1-044 GEN
Solar/Wind Harmer
9.322
946321AF1-296 GEN
Solar/Wind Harmer
2.364
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
3.23
274724RIVER EC ;11
50/50
23.754
957371AF2-031 GEN
50/50
1.176
274800UNIV PARK;3U
Adder
5.454
274802UNIV PARK;5U
Adder
5.231
970941AG2-585 GEN
Solar/Wind Harmer
7.747
276893AG1-478 C
Solar/Wind Harmer
0.226
274729ELWOOD EC;1P
Adder
12.987
276897AD1-100 C
Solar/Wind Harmer
0.007
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
9.561
274772LINCOLN ;3U
Adder
5.693
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.499
274850MENDOTA H;RU
Solar/Wind Harmer
0.055
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.084
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.713
942111AE2-223 GEN
Solar/Wind Harmer
1.26
971993AH1-541 GEN
Solar/Wind Harmer
1.446
276621W2-048 GEN
Solar/Wind Harmer
0.152
276838X2-022 GEN2
Solar/Wind Harmer
0.169
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274808UNIV PK N;4U
Adder
4.345
972259AH1-714 GEN
Adder
13.947
274696ROCKY RD ;4P
Adder
8.044
274697ROCKY RD ;3P
Adder
2.135
962691AG1-118 GEN
Solar/Wind Harmer
14.331
274770LINCOLN ;1U
Adder
5.693
274771LINCOLN ;2U
Adder
5.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.109
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.58
274762LEE CO EC;3U
Adder
6.033
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.172
274803UNIV PARK;6U
Adder
5.231
274887GEN-1.85
Solar/Wind Harmer
0.163
274674JOLIET 9 ;6U
Adder
12.404
958481AF2-142 GEN
Solar/Wind Harmer
8.196
274862TOP CROP ;2U
Solar/Wind Harmer
0.738
274879MINONK ;1U
Solar/Wind Harmer
0.213
274683WAUKEGAN ;8U
Adder
15.223
274683WAUKEGAN ;8U
Adder
12.832
274693ROCKY RD ;1P
Adder
7.781
970921AG2-575 GEN
Solar/Wind Harmer
4.759
970921AG2-575 GEN
Solar/Wind Harmer
1.586
971335AH1-147 GEN
Solar/Wind Harmer
9.469
274764LEE CO EC;5U
Adder
6.048
972267AH1-718 GEN
Adder
2.65
276708O09 GEN2
Solar/Wind Harmer
0.157
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.237
958011AF2-095 GEN
Solar/Wind Harmer
8.925
276843GEN-1.7
Solar/Wind Harmer
0.201
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
958491AF2-143 GEN
Solar/Wind Harmer
7.889
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
7.858
942991AE2-321 GEN
Solar/Wind Harmer
5.365
971573AH1-285 GEN
Solar/Wind Harmer
0.893
971333AH1-146 GEN
Solar/Wind Harmer
9.469
274765LEE CO EC;6U
Adder
6.048
274763LEE CO EC;4U
Adder
5.977
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
276646AC1-214 GEN2
Solar/Wind Harmer
0.172
274826FISK ;BP
50/50
10.998
274752CRETE EC ;2U
Adder
7.24
972228AH1-698 GEN2
Adder
2.946
274730ELWOOD EC;6P
Adder
12.994
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
939351AE1-166 GEN
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.172
970707AG2-453 GEN
Solar/Wind Harmer
15.258
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.237
274814UNIV PK N;0U
Adder
4.402
274807UNIV PK N;3U
Adder
4.392
274805UNIV PK N;1U
Adder
4.373
274687WILL CNTY;4U
Adder
23.197
274687WILL CNTY;4U
Adder
23.197
274731ELWOOD EC;2P
Adder
12.987
274733ELWOOD EC;3P
Adder
12.987
276882AE2-255 GEN
Solar/Wind Harmer
0.589
274746AC1-111 G10
Adder
3.958
274776LINCOLN ;7U
Adder
5.693
926823AC1-168 GEN
Solar/Wind Harmer
0.774
276655WTG1_EQ
Solar/Wind Harmer
0.002
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274676JOLIET 29;8U
Adder
23.706
274734ELWOOD EC;8P
Adder
12.994
274736ELWOOD EC;9P
Adder
12.994
274682WAUKEGAN ;7U
Adder
13.016
943121AE2-341 GEN
Solar/Wind Harmer
8.053
943591AF1-030 GEN
Solar/Wind Harmer
5.355
959091AF2-200 GEN
Solar/Wind Harmer
9.322
274767LEE CO EC;8U
Adder
5.962
276668AB2-070 GEN1
Solar/Wind Harmer
0.114
961501AF2-441 GEN
50/50
10.865
274827FISK ;RP
50/50
7.795
274811UNIV PK N;7U
Adder
4.364
972227AH1-698 GEN1
Adder
2.073
274735ELWOOD EC;4P
Adder
12.987
274744AC1-111 GEN8
Adder
3.958
961011AF2-392 GEN
Solar/Wind Harmer
2.615
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
4.287
959341AF2-225 GEN
Solar/Wind Harmer
4.07
276785W4-005 GEN1
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.114
276848AB2-070 GEN3
Solar/Wind Harmer
0.114
276691AA1-018 GEN1
Solar/Wind Harmer
0.662
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
13.162
959081AF2-199 GEN
Solar/Wind Harmer
4.661
971067AG2-660 GEN
Solar/Wind Harmer
1.554
970819AG2-516 GEN
Solar/Wind Harmer
5.561
971475AH1-234 GEN
Solar/Wind Harmer
2.243
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
274723RIVER EC ;12
50/50
23.648
274801UNIV PARK;4U
Adder
5.454
274751CRETE EC ;1U
Adder
7.24
970569AG2-363 GEN
Solar/Wind Harmer
14.342
971997AH1-543 GEN
Solar/Wind Harmer
2.486
274773LINCOLN ;4U
Adder
5.693
274774LINCOLN ;5U
Adder
5.693
276861AD2-134 GEN
Solar/Wind Harmer
0.084
274761LEE CO EC;2U
Adder
6.033
276158O29GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
5.426
972175AH1-670 GEN
Solar/Wind Harmer
2.813
274880W4-005 GEN4
Solar/Wind Harmer
0
972179AH1-673 GEN
50/50
12.191
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.647
274812UNIV PK N;8U
Adder
4.364
274676JOLIET 29;8U
Adder
24.584
274682WAUKEGAN ;7U
Adder
13.016
274828WAUKEGAN ;BP
Adder
7.98
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.005
274745AC1-111 GEN9
Adder
3.958
957471AF2-041 GEN
Solar/Wind Harmer
13.983
274877BISHOP HL;1U
Solar/Wind Harmer
0.146
274754CRETE EC ;4U
Adder
7.24
274674JOLIET 9 ;6U
Adder
12.404
274732ELWOOD EC;7P
Adder
12.994
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
4.529
939401AE1-172 GEN
Solar/Wind Harmer
3.483
972235AH1-702 GEN1
Adder
1.681
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
5.962
963831AG1-236 GEN
Solar/Wind Harmer
1.205
276615X2-022 GEN
Solar/Wind Harmer
0.032
274728ELWOOD EC;5P
Adder
12.994
971177AH1-047 GEN
Solar/Wind Harmer
2.959
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
7.326
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.144
276174W4-005 GEN2
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
9.322
971343AH1-151 GEN
Solar/Wind Harmer
9.322
276741O09 GEN1
Solar/Wind Harmer
0.157
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.341
274753CRETE EC ;3U
Adder
7.24
274872LEEDK;1U
Solar/Wind Harmer
0.174
972236AH1-702 GEN2
Adder
1.462
274760LEE CO EC;1U
Adder
6.033
274878BISHOP HL;2U
Solar/Wind Harmer
0.146
965931AG1-462 GEN
Solar/Wind Harmer
10.656
965091AG1-374 GEN
Solar/Wind Harmer
11.132
276686W4-005 GEN3
Solar/Wind Harmer
0
990582J1340
External Queue
21.449987411499023
990662J1358
External Queue
15.778422355651855
990577J1339
External Queue
21.449987411499023
990647J1355
External Queue
45.918251037597656
991247J1684 G
External Queue
27.706777572631836
990547J1333 G
External Queue
33.825042724609375
990552J1334 G
External Queue
33.825042724609375
990557J1335 G
External Queue
33.825042724609375
990562J1336 G
External Queue
33.825042724609375
990762J1386
External Queue
9.490592002868652
991332J1785
External Queue
13.620012283325195
991337J1802
External Queue
10.729607582092285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.496
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.223
MECLTFEXP_MEC->PJM
CLTF
8.217
AG2-052LTFEXP_AG2-052->PJM
LTF
0.532
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.481
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.383
AH1-155LTFEXP_AH1-155->PJM
LTF
0.798
NYPJM->LTFIMP_NY
CLTF
0.662
TVALTFEXP_TVA->PJM
CLTF
0.838
LAGNLTFEXP_LAGN->PJM
CLTF
2.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.34
WECLTFEXP_WEC->PJM
CLTF
2.592
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.154
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1868.7
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
6.006
276806AD2-047 C O1
Solar/Wind Harmer
10.199
274676JOLIET 29;8U
Adder
25.626
274734ELWOOD EC;8P
Adder
14.054
274736ELWOOD EC;9P
Adder
14.054
274682WAUKEGAN ;7U
Adder
14.052
943121AE2-341 GEN
Solar/Wind Harmer
11.109
943591AF1-030 GEN
Solar/Wind Harmer
7.406
959091AF2-200 GEN
Solar/Wind Harmer
14.432
274767LEE CO EC;8U
Adder
6.449
274814UNIV PK N;0U
Adder
4.934
274807UNIV PK N;3U
Adder
4.924
274805UNIV PK N;1U
Adder
4.902
274687WILL CNTY;4U
Adder
25.041
274687WILL CNTY;4U
Adder
25.041
274731ELWOOD EC;2P
Adder
14.046
274733ELWOOD EC;3P
Adder
14.046
276882AE2-255 GEN
Solar/Wind Harmer
2.641
274746AC1-111 G10
Adder
4.264
274776LINCOLN ;7U
Adder
4.433
926823AC1-168 GEN
Solar/Wind Harmer
3.046
276655WTG1_EQ
Solar/Wind Harmer
5.297
274724RIVER EC ;11
50/50
24.96
957371AF2-031 GEN
50/50
1.236
274800UNIV PARK;3U
Adder
5.838
274802UNIV PARK;5U
Adder
5.685
970941AG2-585 GEN
Solar/Wind Harmer
11.918
276893AG1-478 C
Solar/Wind Harmer
0.368
274729ELWOOD EC;1P
Adder
14.046
276805AD2-038 GEN
Solar/Wind Harmer
4.192
276897AD1-100 C
Solar/Wind Harmer
23.563
276889AE2-281 GEN
Solar/Wind Harmer
1.485
970571AG2-364 GEN
Solar/Wind Harmer
14.876
276799AD1-013 GEN
Solar/Wind Harmer
1.601
946671AF1-331 GEN
Solar/Wind Harmer
0.303
274850MENDOTA H;RU
Solar/Wind Harmer
1.858
276602WESTBROOK C
Solar/Wind Harmer
1.538
276863AD2-134 GEN
Solar/Wind Harmer
1.292
274772LINCOLN ;3U
Adder
4.433
274858EASY ROAD;U2
Solar/Wind Harmer
3.361
276157O29GEN1
Solar/Wind Harmer
2.609
274723RIVER EC ;12
50/50
24.906
274751CRETE EC ;1U
50/50
5.252
274801UNIV PARK;4U
Adder
5.838
970569AG2-363 GEN
Solar/Wind Harmer
22.313
961501AF2-441 GEN
50/50
11.457
274827FISK ;RP
50/50
8.354
274811UNIV PK N;7U
Adder
4.892
972227AH1-698 GEN1
Adder
2.246
274735ELWOOD EC;4P
Adder
14.046
274744AC1-111 GEN8
Adder
4.264
961011AF2-392 GEN
Solar/Wind Harmer
7.521
274848CAMPGROVE;RU
Solar/Wind Harmer
4.318
970169AG2-114 GEN
Solar/Wind Harmer
6.669
274826FISK ;BP
50/50
11.788
274752CRETE EC ;2U
50/50
5.252
972231SS25-0005
Solar/Wind Harmer
9.61
276772AC2-154 GEN
Solar/Wind Harmer
2.659
972228AH1-698 GEN2
Adder
3.192
274730ELWOOD EC;6P
Adder
14.054
276694AA1-018 GEN2
Solar/Wind Harmer
5.355
939351AE1-166 GEN
Solar/Wind Harmer
4.814
274855GSG-6 ;RU
Solar/Wind Harmer
2.671
970707AG2-453 GEN
Solar/Wind Harmer
20.124
274754CRETE EC ;4U
50/50
5.252
274674JOLIET 9 ;6U
Adder
13.35
274732ELWOOD EC;7P
Adder
14.054
276876AE1-163_GEN2
Solar/Wind Harmer
5.197
962781AG1-127 GEN
Solar/Wind Harmer
6.995
972235AH1-702 GEN1
Adder
1.817
939401AE1-172 GEN
Solar/Wind Harmer
10.044
274857EASY ROAD;U1
Solar/Wind Harmer
3.361
274766LEE CO EC;7U
Adder
6.449
972037AH1-567 GEN1
Adder
0.178
960591AF2-350 GEN
Solar/Wind Harmer
9.534
274675JOLIET 29;7U
Adder
26.573
274675JOLIET 29;7U
Adder
25.624
970833AG2-524 GEN
Solar/Wind Harmer
6.847
970833AG2-524 GEN
Solar/Wind Harmer
3.184
276868AE1-113 GEN
Solar/Wind Harmer
7.922
971411AH1-196 GEN
Solar/Wind Harmer
11.075
274823ROCKFORD ;21
Adder
14.117
971675AH1-338 GEN
Solar/Wind Harmer
13.024
971171AH1-044 GEN
Solar/Wind Harmer
14.432
274775LINCOLN ;6U
Adder
4.433
274777LINCOLN ;8U
Adder
4.433
946321AF1-296 GEN
Solar/Wind Harmer
6.845
276656WTG2_EQ
Solar/Wind Harmer
0.701
941731AE2-173 GEN
Solar/Wind Harmer
0.476
971997AH1-543 GEN
Solar/Wind Harmer
11.562
276861AD2-134 GEN
Solar/Wind Harmer
1.292
274773LINCOLN ;4U
Adder
4.433
274774LINCOLN ;5U
Adder
4.433
274761LEE CO EC;2U
Adder
6.526
276158O29GEN2
Solar/Wind Harmer
3.43
939741AE1-205 GEN
Solar/Wind Harmer
1.638
274728ELWOOD EC;5P
Adder
14.054
971177AH1-047 GEN
Solar/Wind Harmer
4.352
276612AE2-035 GEN
Solar/Wind Harmer
1.83
971681AH1-341 GEN
Solar/Wind Harmer
10.58
274863CRW1-WTG
Solar/Wind Harmer
3.879
274864CRW2-WTG
Solar/Wind Harmer
3.879
957751AF2-069 GEN
Solar/Wind Harmer
0.313
276691AA1-018 GEN1
Solar/Wind Harmer
0.395
941551AE2-152 GEN
Solar/Wind Harmer
3.682
274872LEEDK;1U
Solar/Wind Harmer
6.016
274822ROCKFORD ;11
Adder
14.221
959081AF2-199 GEN
Solar/Wind Harmer
7.216
971067AG2-660 GEN
Solar/Wind Harmer
1.678
970819AG2-516 GEN
Solar/Wind Harmer
8.615
971475AH1-234 GEN
Solar/Wind Harmer
16.041
276726Z2-087_GEN
Solar/Wind Harmer
4.798
274808UNIV PK N;4U
Adder
4.87
274888KELLY CRK;1U
Solar/Wind Harmer
5.629
972259AH1-714 GEN
Adder
15.051
274696ROCKY RD ;4P
Adder
8.676
274697ROCKY RD ;3P
Adder
2.302
962691AG1-118 GEN
Solar/Wind Harmer
22.149
274770LINCOLN ;1U
Adder
4.433
274771LINCOLN ;2U
Adder
4.433
274856ECOGROVE ;U1
Solar/Wind Harmer
2.412
276611AD2-172 GEN
Solar/Wind Harmer
1.83
938861AE1-114 GEN
Solar/Wind Harmer
5.786
274762LEE CO EC;3U
Adder
6.526
276603SUBLETTE C
Solar/Wind Harmer
0.732
276645AC1-214 GEN1
Solar/Wind Harmer
0.912
276843GEN-1.7
Solar/Wind Harmer
0.547
958011AF2-095 GEN
Solar/Wind Harmer
13.73
274861TOP CROP ;1U
Solar/Wind Harmer
5.137
958491AF2-143 GEN
Solar/Wind Harmer
12.257
276872AE1-163_GEN1
Solar/Wind Harmer
5.197
274695ROCKY RD ;2P
Adder
8.475
942991AE2-321 GEN
Solar/Wind Harmer
7.435
971573AH1-285 GEN
Solar/Wind Harmer
6.358
971333AH1-146 GEN
Solar/Wind Harmer
14.655
274765LEE CO EC;6U
Adder
6.541
274763LEE CO EC;4U
Adder
6.465
274851PROVIDENC;RU
Solar/Wind Harmer
1.94
276646AC1-214 GEN2
Solar/Wind Harmer
0.912
972179AH1-673 GEN
50/50
12.845
276164X3-005 C
Solar/Wind Harmer
0.814
274812UNIV PK N;8U
Adder
4.892
276776AD2-060 GEN
Solar/Wind Harmer
0.403
274676JOLIET 29;8U
Adder
26.575
274682WAUKEGAN ;7U
Adder
14.052
274828WAUKEGAN ;BP
Adder
8.615
274871GR RIDGE ;2U
Solar/Wind Harmer
5.981
276901AD2-066 C O1
Solar/Wind Harmer
2.73
274745AC1-111 GEN9
Adder
4.264
960751AF2-366 GEN
Solar/Wind Harmer
2.11
957471AF2-041 GEN
Solar/Wind Harmer
21.648
972207SS24-0001
Solar/Wind Harmer
15.761
274877BISHOP HL;1U
Solar/Wind Harmer
2.277
274847GR RIDGE ;BU
Solar/Wind Harmer
3.934
971341AH1-150 GEN
Solar/Wind Harmer
14.432
971343AH1-151 GEN
Solar/Wind Harmer
14.432
276741O09 GEN1
Solar/Wind Harmer
2.45
274849CRESCENT ;1U
Solar/Wind Harmer
1.259
274803UNIV PARK;6U
Adder
5.685
274887GEN-1.85
Solar/Wind Harmer
5.082
274674JOLIET 9 ;6U
Adder
13.35
958481AF2-142 GEN
Solar/Wind Harmer
12.728
274862TOP CROP ;2U
Solar/Wind Harmer
4.289
274879MINONK ;1U
Solar/Wind Harmer
5.282
274683WAUKEGAN ;8U
Adder
16.435
274683WAUKEGAN ;8U
Adder
13.854
274693ROCKY RD ;1P
Adder
8.392
970921AG2-575 GEN
Solar/Wind Harmer
7.356
970921AG2-575 GEN
Solar/Wind Harmer
1.711
971335AH1-147 GEN
Solar/Wind Harmer
14.655
274764LEE CO EC;5U
Adder
6.541
972267AH1-718 GEN
Adder
2.868
276708O09 GEN2
Solar/Wind Harmer
2.45
276782AC1-033 GEN
Solar/Wind Harmer
2.691
274753CRETE EC ;3U
50/50
5.252
972038AH1-567 GEN2
Adder
0.365
274872LEEDK;1U
Solar/Wind Harmer
0.187
972236AH1-702 GEN2
Adder
1.58
274760LEE CO EC;1U
Adder
6.526
274878BISHOP HL;2U
Solar/Wind Harmer
2.277
965931AG1-462 GEN
Solar/Wind Harmer
16.57
990582J1340
External Queue
22.734060287475586
990662J1358
External Queue
17.02812957763672
990577J1339
External Queue
22.734060287475586
990647J1355
External Queue
44.96678161621094
991247J1684 G
External Queue
28.594083786010742
990547J1333 G
External Queue
34.311134338378906
990552J1334 G
External Queue
34.311134338378906
990557J1335 G
External Queue
34.311134338378906
990562J1336 G
External Queue
34.311134338378906
990762J1386
External Queue
10.402356147766113
991332J1785
External Queue
14.410825729370117
991337J1802
External Queue
10.868054389953613
NYPJM->LTFIMP_NY
CLTF
0.719
TVALTFEXP_TVA->PJM
CLTF
0.977
LAGNLTFEXP_LAGN->PJM
CLTF
3.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.488
WECLTFEXP_WEC->PJM
CLTF
2.802
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.812
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.229
MECLTFEXP_MEC->PJM
CLTF
8.964
AG2-052LTFEXP_AG2-052->PJM
LTF
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.958
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.245
AH1-155LTFEXP_AH1-155->PJM
LTF
0.801

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.82 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1938.19
MW Contribution:14.18
Bus #Bus NameTypeMW Contribution
274810UNIV PK N;6U
50/50
0.35
276806AD2-047 C O1
Solar/Wind Harmer
13.361
274676JOLIET 29;8U
Adder
32.778
972181SS23-001
Solar/Wind Harmer
6.499
274734ELWOOD EC;8P
Adder
17.945
274736ELWOOD EC;9P
Adder
17.945
274682WAUKEGAN ;7U
Adder
18.079
943121AE2-341 GEN
Solar/Wind Harmer
14.588
943591AF1-030 GEN
Solar/Wind Harmer
9.726
959091AF2-200 GEN
Solar/Wind Harmer
18.579
274767LEE CO EC;8U
Adder
8.245
274814UNIV PK N;0U
50/50
6.449
274802UNIV PARK;5U
50/50
7.353
274799UNIV PARK;2U
50/50
0.324
274800UNIV PARK;3U
50/50
7.213
970941AG2-585 GEN
Solar/Wind Harmer
15.612
276893AG1-478 C
Solar/Wind Harmer
0.474
274729ELWOOD EC;1P
Adder
17.949
276897AD1-100 C
Solar/Wind Harmer
31.017
276805AD2-038 GEN
Solar/Wind Harmer
5.442
274772LINCOLN ;3U
Adder
6.2
276889AE2-281 GEN
Solar/Wind Harmer
1.892
276799AD1-013 GEN
Solar/Wind Harmer
2.068
946671AF1-331 GEN
Solar/Wind Harmer
0.391
970571AG2-364 GEN
Solar/Wind Harmer
18.686
274850MENDOTA H;RU
Solar/Wind Harmer
2.399
276602WESTBROOK C
Solar/Wind Harmer
1.986
276863AD2-134 GEN
Solar/Wind Harmer
1.668
274858EASY ROAD;U2
Solar/Wind Harmer
4.298
276157O29GEN1
Solar/Wind Harmer
3.312
942111AE2-223 GEN
Solar/Wind Harmer
6.109
274724RIVER EC ;11
Adder
9.565
274827FISK ;RP
50/50
10.684
274811UNIV PK N;7U
50/50
6.393
972227AH1-698 GEN1
Adder
2.906
274735ELWOOD EC;4P
Adder
17.949
274744AC1-111 GEN8
Adder
5.555
961011AF2-392 GEN
Solar/Wind Harmer
9.592
970169AG2-114 GEN
Solar/Wind Harmer
8.429
274848CAMPGROVE;RU
Solar/Wind Harmer
5.398
959341AF2-225 GEN
Solar/Wind Harmer
11.178
276785W4-005 GEN1
Solar/Wind Harmer
0.034
274826FISK ;BP
50/50
15.075
274806UNIV PK N;2U
50/50
0.357
274815UNIV PK N;XU
50/50
0.351
276772AC2-154 GEN
Solar/Wind Harmer
3.483
276694AA1-018 GEN2
Solar/Wind Harmer
7.037
972228AH1-698 GEN2
Adder
4.13
972231SS25-0005
Solar/Wind Harmer
10.398
274752CRETE EC ;2U
Adder
5.356
274730ELWOOD EC;6P
Adder
17.945
939351AE1-166 GEN
Solar/Wind Harmer
6.338
970707AG2-453 GEN
Solar/Wind Harmer
26.994
274855GSG-6 ;RU
Solar/Wind Harmer
3.45
274853TWINGROVE;U1
Solar/Wind Harmer
5.103
959611AF2-252 GEN
Solar/Wind Harmer
1.646
274754CRETE EC ;4U
Adder
5.356
274732ELWOOD EC;7P
Adder
17.945
274674JOLIET 9 ;6U
Adder
16.709
276876AE1-163_GEN2
Solar/Wind Harmer
6.622
962781AG1-127 GEN
Solar/Wind Harmer
9.072
939401AE1-172 GEN
Solar/Wind Harmer
13.014
972235AH1-702 GEN1
Adder
2.333
274857EASY ROAD;U1
Solar/Wind Harmer
4.298
274766LEE CO EC;7U
Adder
8.245
972037AH1-567 GEN1
50/50
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.489
274675JOLIET 29;7U
Adder
33.999
274675JOLIET 29;7U
Adder
32.784
970833AG2-524 GEN
Solar/Wind Harmer
8.898
970833AG2-524 GEN
Solar/Wind Harmer
4.139
274775LINCOLN ;6U
Adder
6.2
274777LINCOLN ;8U
Adder
6.2
276868AE1-113 GEN
Solar/Wind Harmer
10.017
971411AH1-196 GEN
Solar/Wind Harmer
14.253
971675AH1-338 GEN
Solar/Wind Harmer
16.822
274823ROCKFORD ;21
Adder
18.134
971171AH1-044 GEN
Solar/Wind Harmer
18.579
946321AF1-296 GEN
Solar/Wind Harmer
8.648
276656WTG2_EQ
Solar/Wind Harmer
0.861
941731AE2-173 GEN
Solar/Wind Harmer
4.332
274728ELWOOD EC;5P
Adder
17.945
971177AH1-047 GEN
Solar/Wind Harmer
5.607
276612AE2-035 GEN
Solar/Wind Harmer
2.346
971681AH1-341 GEN
Solar/Wind Harmer
13.54
274863CRW1-WTG
Solar/Wind Harmer
4.973
274864CRW2-WTG
Solar/Wind Harmer
4.973
957751AF2-069 GEN
Solar/Wind Harmer
0.392
276174W4-005 GEN2
Solar/Wind Harmer
0.034
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
941551AE2-152 GEN
Solar/Wind Harmer
4.847
274872LEEDK;1U
Solar/Wind Harmer
7.797
274822ROCKFORD ;11
Adder
18.266
959081AF2-199 GEN
Solar/Wind Harmer
9.289
971067AG2-660 GEN
Solar/Wind Harmer
2.16
970819AG2-516 GEN
Solar/Wind Harmer
11.049
971475AH1-234 GEN
Solar/Wind Harmer
20.56
276726Z2-087_GEN
Solar/Wind Harmer
5.894
274854TWINGROVE;U2
Solar/Wind Harmer
4.996
274807UNIV PK N;3U
50/50
6.435
274805UNIV PK N;1U
50/50
6.407
274687WILL CNTY;4U
Adder
31.015
274687WILL CNTY;4U
Adder
31.015
274731ELWOOD EC;2P
Adder
17.949
274733ELWOOD EC;3P
Adder
17.949
274776LINCOLN ;7U
Adder
6.2
274746AC1-111 G10
Adder
5.555
276882AE2-255 GEN
Solar/Wind Harmer
3.339
926823AC1-168 GEN
Solar/Wind Harmer
3.856
276655WTG1_EQ
Solar/Wind Harmer
6.506
960681AF2-359 GEN
Solar/Wind Helper
1.016
274723RIVER EC ;12
50/50
26.242
274809UNIV PK N;5U
50/50
0.349
966431AG1-512 GEN
50/50
2.238
274801UNIV PARK;4U
50/50
7.213
274751CRETE EC ;1U
Adder
5.356
274773LINCOLN ;4U
Adder
6.2
274774LINCOLN ;5U
Adder
6.2
971997AH1-543 GEN
Solar/Wind Harmer
14.798
970569AG2-363 GEN
Solar/Wind Harmer
28.029
276861AD2-134 GEN
Solar/Wind Harmer
1.668
274761LEE CO EC;2U
Adder
8.344
276158O29GEN2
Solar/Wind Harmer
4.354
939741AE1-205 GEN
Solar/Wind Harmer
14.903
972175AH1-670 GEN
Solar/Wind Harmer
8.682
274880W4-005 GEN4
Solar/Wind Harmer
0.034
274808UNIV PK N;4U
50/50
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
7.374
972259AH1-714 GEN
Adder
19.777
274770LINCOLN ;1U
Adder
6.2
274771LINCOLN ;2U
Adder
6.2
274798UNIV PARK;1U
50/50
0.314
276843GEN-1.7
Solar/Wind Harmer
0.716
958011AF2-095 GEN
Solar/Wind Harmer
17.985
958491AF2-143 GEN
Solar/Wind Harmer
15.914
274861TOP CROP ;1U
Solar/Wind Harmer
6.234
276872AE1-163_GEN1
Solar/Wind Harmer
6.622
274695ROCKY RD ;2P
Adder
10.974
971573AH1-285 GEN
Solar/Wind Harmer
8.323
942991AE2-321 GEN
Solar/Wind Harmer
9.58
971333AH1-146 GEN
Solar/Wind Harmer
18.881
274765LEE CO EC;6U
Adder
8.363
274763LEE CO EC;4U
Adder
8.265
274851PROVIDENC;RU
Solar/Wind Harmer
2.433
276646AC1-214 GEN2
Solar/Wind Harmer
1.144
24441505OLIV SLR
Solar/Wind Helper
0.062
270526AF1-158 GEN
Solar/Wind Helper
1.044
972179AH1-673 GEN
50/50
14.177
274813UNIV PK N;9U
50/50
0.35
274812UNIV PK N;8U
50/50
6.393
276164X3-005 C
Solar/Wind Harmer
0.937
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274676JOLIET 29;8U
Adder
33.992
274871GR RIDGE ;2U
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
18.079
274828WAUKEGAN ;BP
Adder
11.082
972207SS24-0001
Solar/Wind Harmer
22.042
274745AC1-111 GEN9
Adder
5.555
276901AD2-066 C O1
Solar/Wind Harmer
3.464
960751AF2-366 GEN
Solar/Wind Harmer
2.737
957471AF2-041 GEN
Solar/Wind Harmer
27.868
274877BISHOP HL;1U
Solar/Wind Harmer
2.856
274847GR RIDGE ;BU
Solar/Wind Harmer
5.127
971341AH1-150 GEN
Solar/Wind Harmer
18.579
971343AH1-151 GEN
Solar/Wind Harmer
18.579
276741O09 GEN1
Solar/Wind Harmer
3.11
274849CRESCENT ;1U
Solar/Wind Harmer
1.58
274696ROCKY RD ;4P
Adder
11.233
274697ROCKY RD ;3P
Adder
2.981
962691AG1-118 GEN
Solar/Wind Harmer
28.743
274856ECOGROVE ;U1
Solar/Wind Harmer
3.092
276611AD2-172 GEN
Solar/Wind Harmer
2.346
938861AE1-114 GEN
Solar/Wind Harmer
7.404
274762LEE CO EC;3U
Adder
8.344
276603SUBLETTE C
Solar/Wind Harmer
0.935
276645AC1-214 GEN1
Solar/Wind Harmer
1.144
274803UNIV PARK;6U
50/50
7.353
274887GEN-1.85
Solar/Wind Harmer
6.657
958481AF2-142 GEN
Solar/Wind Harmer
16.726
274674JOLIET 9 ;6U
Adder
16.709
274862TOP CROP ;2U
Solar/Wind Harmer
5.206
274683WAUKEGAN ;8U
Adder
21.142
274683WAUKEGAN ;8U
Adder
17.822
274879MINONK ;1U
Solar/Wind Harmer
6.679
274693ROCKY RD ;1P
Adder
10.866
970921AG2-575 GEN
Solar/Wind Harmer
9.539
970921AG2-575 GEN
Solar/Wind Harmer
2.218
971335AH1-147 GEN
Solar/Wind Harmer
18.881
274764LEE CO EC;5U
Adder
8.363
972267AH1-718 GEN
Adder
3.656
276708O09 GEN2
Solar/Wind Harmer
3.11
276782AC1-033 GEN
Solar/Wind Harmer
3.375
960611AF2-352 GEN
Solar/Wind Harmer
1.646
274816UNIV PK N;YU
50/50
0.35
972038AH1-567 GEN2
50/50
0.451
274753CRETE EC ;3U
Adder
5.356
274872LEEDK;1U
Solar/Wind Harmer
0.243
972236AH1-702 GEN2
Adder
2.028
274760LEE CO EC;1U
Adder
8.344
274878BISHOP HL;2U
Solar/Wind Harmer
2.856
965931AG1-462 GEN
Solar/Wind Harmer
20.903
965091AG1-374 GEN
Solar/Wind Harmer
21.239
276686W4-005 GEN3
Solar/Wind Harmer
0.034
990407J1304
External Queue
3.9451146125793457
990512J1326
External Queue
5.108882904052734
991092J1477
External Queue
2.769141674041748
991777J1629 G
External Queue
11.657174110412598
990117J1214
External Queue
17.574556350708008
990727J1377 G
External Queue
5.916489124298096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.64
WECLTFEXP_WEC->PJM
CLTF
3.585
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.273
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
MECLTFEXP_MEC->PJM
CLTF
11.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.18
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.35
NYPJM->LTFIMP_NY
CLTF
0.854
TVALTFEXP_TVA->PJM
CLTF
0.842
LAGNLTFEXP_LAGN->PJM
CLTF
3.477

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.96 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1908.56
MW Contribution:14.18
Bus #Bus NameTypeMW Contribution
274810UNIV PK N;6U
50/50
0.35
276806AD2-047 C O1
Solar/Wind Harmer
13.361
274676JOLIET 29;8U
Adder
32.778
274734ELWOOD EC;8P
Adder
17.945
274736ELWOOD EC;9P
Adder
17.945
274682WAUKEGAN ;7U
Adder
18.079
943121AE2-341 GEN
Solar/Wind Harmer
14.588
943591AF1-030 GEN
Solar/Wind Harmer
9.726
274802UNIV PARK;5U
50/50
7.353
274799UNIV PARK;2U
50/50
0.324
274827FISK ;RP
50/50
10.684
274811UNIV PK N;7U
50/50
6.393
972227AH1-698 GEN1
Adder
2.906
274735ELWOOD EC;4P
Adder
17.949
274826FISK ;BP
50/50
15.075
274806UNIV PK N;2U
50/50
0.357
274815UNIV PK N;XU
50/50
0.351
274732ELWOOD EC;7P
Adder
17.945
274674JOLIET 9 ;6U
Adder
16.709
276876AE1-163_GEN2
Solar/Wind Harmer
6.622
962781AG1-127 GEN
Solar/Wind Harmer
9.072
939401AE1-172 GEN
Solar/Wind Harmer
13.014
972235AH1-702 GEN1
Adder
2.333
274857EASY ROAD;U1
Solar/Wind Harmer
4.298
274766LEE CO EC;7U
Adder
8.245
972037AH1-567 GEN1
50/50
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.489
274675JOLIET 29;7U
Adder
33.999
274675JOLIET 29;7U
Adder
32.784
970833AG2-524 GEN
Solar/Wind Harmer
8.898
970833AG2-524 GEN
Solar/Wind Harmer
4.139
274775LINCOLN ;6U
Adder
6.2
274777LINCOLN ;8U
Adder
6.2
276868AE1-113 GEN
Solar/Wind Harmer
10.017
971411AH1-196 GEN
Solar/Wind Harmer
14.253
971675AH1-338 GEN
Solar/Wind Harmer
16.822
274823ROCKFORD ;21
Adder
18.134
971171AH1-044 GEN
Solar/Wind Harmer
18.579
946321AF1-296 GEN
Solar/Wind Harmer
8.648
276656WTG2_EQ
Solar/Wind Harmer
0.861
941731AE2-173 GEN
Solar/Wind Harmer
4.332
274728ELWOOD EC;5P
Adder
17.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
941551AE2-152 GEN
Solar/Wind Harmer
4.847
274872LEEDK;1U
Solar/Wind Harmer
7.797
274822ROCKFORD ;11
Adder
18.266
959081AF2-199 GEN
Solar/Wind Harmer
9.289
971067AG2-660 GEN
Solar/Wind Harmer
2.16
970819AG2-516 GEN
Solar/Wind Harmer
11.049
274814UNIV PK N;0U
50/50
6.449
274807UNIV PK N;3U
50/50
6.435
274805UNIV PK N;1U
50/50
6.407
274687WILL CNTY;4U
Adder
31.015
274687WILL CNTY;4U
Adder
31.015
274731ELWOOD EC;2P
Adder
17.949
274733ELWOOD EC;3P
Adder
17.949
274776LINCOLN ;7U
Adder
6.2
274746AC1-111 G10
Adder
5.555
276882AE2-255 GEN
Solar/Wind Harmer
3.339
971177AH1-047 GEN
Solar/Wind Harmer
5.607
276612AE2-035 GEN
Solar/Wind Harmer
2.346
971681AH1-341 GEN
Solar/Wind Harmer
13.54
274863CRW1-WTG
Solar/Wind Harmer
4.973
274864CRW2-WTG
Solar/Wind Harmer
4.973
957751AF2-069 GEN
Solar/Wind Harmer
0.392
276174W4-005 GEN2
Solar/Wind Harmer
1.728
274723RIVER EC ;12
50/50
26.242
274809UNIV PK N;5U
50/50
0.349
966431AG1-512 GEN
50/50
2.238
274801UNIV PARK;4U
50/50
7.213
274773LINCOLN ;4U
Adder
6.2
274774LINCOLN ;5U
Adder
6.2
971997AH1-543 GEN
Solar/Wind Harmer
14.798
970569AG2-363 GEN
Solar/Wind Harmer
28.029
276861AD2-134 GEN
Solar/Wind Harmer
1.668
274761LEE CO EC;2U
Adder
8.344
276158O29GEN2
Solar/Wind Harmer
4.354
939741AE1-205 GEN
Solar/Wind Harmer
14.903
972175AH1-670 GEN
Solar/Wind Harmer
8.682
274880W4-005 GEN4
Solar/Wind Harmer
1.728
926823AC1-168 GEN
Solar/Wind Harmer
3.856
276655WTG1_EQ
Solar/Wind Harmer
6.506
960681AF2-359 GEN
Solar/Wind Helper
1.016
971475AH1-234 GEN
Solar/Wind Harmer
20.56
276726Z2-087_GEN
Solar/Wind Harmer
5.894
274854TWINGROVE;U2
Solar/Wind Harmer
4.996
274798UNIV PARK;1U
50/50
0.314
276843GEN-1.7
Solar/Wind Harmer
0.716
958011AF2-095 GEN
Solar/Wind Harmer
17.985
958491AF2-143 GEN
Solar/Wind Harmer
15.914
274861TOP CROP ;1U
Solar/Wind Harmer
6.234
276872AE1-163_GEN1
Solar/Wind Harmer
6.622
274695ROCKY RD ;2P
Adder
10.974
971573AH1-285 GEN
Solar/Wind Harmer
8.323
942991AE2-321 GEN
Solar/Wind Harmer
9.58
971333AH1-146 GEN
Solar/Wind Harmer
18.881
274765LEE CO EC;6U
Adder
8.363
274763LEE CO EC;4U
Adder
8.265
274851PROVIDENC;RU
Solar/Wind Harmer
2.433
276646AC1-214 GEN2
Solar/Wind Harmer
1.144
24441505OLIV SLR
Solar/Wind Helper
0.062
274744AC1-111 GEN8
Adder
5.555
961011AF2-392 GEN
Solar/Wind Harmer
9.592
970169AG2-114 GEN
Solar/Wind Harmer
8.429
274848CAMPGROVE;RU
Solar/Wind Harmer
5.398
959341AF2-225 GEN
Solar/Wind Harmer
11.178
276785W4-005 GEN1
Solar/Wind Harmer
1.728
972179AH1-673 GEN
50/50
14.177
274813UNIV PK N;9U
50/50
0.35
274812UNIV PK N;8U
50/50
6.393
276164X3-005 C
Solar/Wind Harmer
0.937
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274676JOLIET 29;8U
Adder
33.992
274871GR RIDGE ;2U
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
18.079
274828WAUKEGAN ;BP
Adder
11.082
972207SS24-0001
Solar/Wind Harmer
22.042
274745AC1-111 GEN9
Adder
5.555
276901AD2-066 C O1
Solar/Wind Harmer
3.464
960751AF2-366 GEN
Solar/Wind Harmer
2.737
957471AF2-041 GEN
Solar/Wind Harmer
27.868
274877BISHOP HL;1U
Solar/Wind Harmer
2.856
274847GR RIDGE ;BU
Solar/Wind Harmer
5.127
971341AH1-150 GEN
Solar/Wind Harmer
18.579
971343AH1-151 GEN
Solar/Wind Harmer
18.579
276741O09 GEN1
Solar/Wind Harmer
3.11
274849CRESCENT ;1U
Solar/Wind Harmer
1.58
959091AF2-200 GEN
Solar/Wind Harmer
18.579
274767LEE CO EC;8U
Adder
8.245
274808UNIV PK N;4U
50/50
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
7.374
972259AH1-714 GEN
Adder
19.777
274770LINCOLN ;1U
Adder
6.2
274771LINCOLN ;2U
Adder
6.2
274696ROCKY RD ;4P
Adder
11.233
274697ROCKY RD ;3P
Adder
2.981
962691AG1-118 GEN
Solar/Wind Harmer
28.743
274856ECOGROVE ;U1
Solar/Wind Harmer
3.092
276611AD2-172 GEN
Solar/Wind Harmer
2.346
938861AE1-114 GEN
Solar/Wind Harmer
7.404
274762LEE CO EC;3U
Adder
8.344
276603SUBLETTE C
Solar/Wind Harmer
0.935
276645AC1-214 GEN1
Solar/Wind Harmer
1.144
274800UNIV PARK;3U
50/50
7.213
970941AG2-585 GEN
Solar/Wind Harmer
15.612
276893AG1-478 C
Solar/Wind Harmer
0.474
274729ELWOOD EC;1P
Adder
17.949
276897AD1-100 C
Solar/Wind Harmer
31.017
276805AD2-038 GEN
Solar/Wind Harmer
5.442
274772LINCOLN ;3U
Adder
6.2
276889AE2-281 GEN
Solar/Wind Harmer
1.892
276799AD1-013 GEN
Solar/Wind Harmer
2.068
946671AF1-331 GEN
Solar/Wind Harmer
0.391
970571AG2-364 GEN
Solar/Wind Harmer
18.686
274850MENDOTA H;RU
Solar/Wind Harmer
2.399
276602WESTBROOK C
Solar/Wind Harmer
1.986
276863AD2-134 GEN
Solar/Wind Harmer
1.668
274858EASY ROAD;U2
Solar/Wind Harmer
4.298
276157O29GEN1
Solar/Wind Harmer
3.312
942111AE2-223 GEN
Solar/Wind Harmer
6.109
274724RIVER EC ;11
Adder
9.565
971993AH1-541 GEN
Solar/Wind Harmer
2.036
274803UNIV PARK;6U
50/50
7.353
274887GEN-1.85
Solar/Wind Harmer
6.657
958481AF2-142 GEN
Solar/Wind Harmer
16.726
274674JOLIET 9 ;6U
Adder
16.709
274862TOP CROP ;2U
Solar/Wind Harmer
5.206
274683WAUKEGAN ;8U
Adder
21.142
274683WAUKEGAN ;8U
Adder
17.822
274879MINONK ;1U
Solar/Wind Harmer
6.679
274693ROCKY RD ;1P
Adder
10.866
970921AG2-575 GEN
Solar/Wind Harmer
9.539
970921AG2-575 GEN
Solar/Wind Harmer
2.218
971335AH1-147 GEN
Solar/Wind Harmer
18.881
274764LEE CO EC;5U
Adder
8.363
972267AH1-718 GEN
Adder
3.656
276708O09 GEN2
Solar/Wind Harmer
3.11
276782AC1-033 GEN
Solar/Wind Harmer
3.375
960611AF2-352 GEN
Solar/Wind Harmer
1.646
276772AC2-154 GEN
Solar/Wind Harmer
3.483
276694AA1-018 GEN2
Solar/Wind Harmer
7.037
972228AH1-698 GEN2
Adder
4.13
274730ELWOOD EC;6P
Adder
17.945
939351AE1-166 GEN
Solar/Wind Harmer
6.338
970707AG2-453 GEN
Solar/Wind Harmer
26.994
274855GSG-6 ;RU
Solar/Wind Harmer
3.45
274853TWINGROVE;U1
Solar/Wind Harmer
5.103
959611AF2-252 GEN
Solar/Wind Harmer
1.646
270526AF1-158 GEN
Solar/Wind Helper
1.044
274816UNIV PK N;YU
50/50
0.35
972038AH1-567 GEN2
50/50
0.451
274872LEEDK;1U
Solar/Wind Harmer
0.243
972236AH1-702 GEN2
Adder
2.028
274760LEE CO EC;1U
Adder
8.344
274878BISHOP HL;2U
Solar/Wind Harmer
2.856
965931AG1-462 GEN
Solar/Wind Harmer
20.903
965091AG1-374 GEN
Solar/Wind Harmer
21.239
276686W4-005 GEN3
Solar/Wind Harmer
1.728
990407J1304
External Queue
3.9451146125793457
990512J1326
External Queue
5.108882904052734
991092J1477
External Queue
2.769141674041748
991777J1629 G
External Queue
11.657174110412598
990117J1214
External Queue
17.574556350708008
990727J1377 G
External Queue
5.916489124298096
NYPJM->LTFIMP_NY
CLTF
0.854
TVALTFEXP_TVA->PJM
CLTF
0.842
LAGNLTFEXP_LAGN->PJM
CLTF
3.477
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.64
WECLTFEXP_WEC->PJM
CLTF
3.585
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.273
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
MECLTFEXP_MEC->PJM
CLTF
11.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.18
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.35

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1783.3
MW Contribution:15.34
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
12.073
274775LINCOLN ;6U
Adder
7.259
274777LINCOLN ;8U
Adder
7.259
274675JOLIET 29;7U
Adder
31.65
274675JOLIET 29;7U
Adder
30.52
972037AH1-567 GEN1
Adder
0.183
970833AG2-524 GEN
Solar/Wind Harmer
8.703
970833AG2-524 GEN
Solar/Wind Harmer
4.048
971411AH1-196 GEN
Solar/Wind Harmer
14.053
276868AE1-113 GEN
Solar/Wind Harmer
9.466
971675AH1-338 GEN
Solar/Wind Harmer
16.796
971171AH1-044 GEN
Solar/Wind Harmer
18.438
274823ROCKFORD ;21
Adder
17.9
946321AF1-296 GEN
Solar/Wind Harmer
8.521
276656WTG2_EQ
Solar/Wind Harmer
0.875
941731AE2-173 GEN
Solar/Wind Harmer
4.403
958011AF2-095 GEN
Solar/Wind Harmer
17.386
276843GEN-1.7
Solar/Wind Harmer
0.692
971573AH1-285 GEN
Solar/Wind Harmer
8.467
958491AF2-143 GEN
Solar/Wind Harmer
14.766
274695ROCKY RD ;2P
Adder
10.859
942991AE2-321 GEN
Solar/Wind Harmer
9.449
971333AH1-146 GEN
Solar/Wind Harmer
18.687
274861TOP CROP ;1U
Solar/Wind Harmer
5.622
276872AE1-163_GEN1
Solar/Wind Harmer
6.213
274765LEE CO EC;6U
Adder
8.261
274763LEE CO EC;4U
Adder
8.163
274887GEN-1.85
Solar/Wind Harmer
6.435
274674JOLIET 9 ;6U
Adder
16.145
958481AF2-142 GEN
Solar/Wind Harmer
15.409
274803UNIV PARK;6U
Adder
5.821
274693ROCKY RD ;1P
Adder
10.752
274683WAUKEGAN ;8U
Adder
20.545
274683WAUKEGAN ;8U
Adder
17.319
970921AG2-575 GEN
Solar/Wind Harmer
9.552
970921AG2-575 GEN
Solar/Wind Harmer
2.221
274879MINONK ;1U
Solar/Wind Harmer
6.311
971335AH1-147 GEN
Solar/Wind Harmer
18.687
274862TOP CROP ;2U
Solar/Wind Harmer
4.695
274764LEE CO EC;5U
Adder
8.261
972267AH1-718 GEN
Adder
3.611
276708O09 GEN2
Solar/Wind Harmer
3.063
276782AC1-033 GEN
Solar/Wind Harmer
3.295
960611AF2-352 GEN
Solar/Wind Harmer
1.674
274851PROVIDENC;RU
Solar/Wind Harmer
2.373
276646AC1-214 GEN2
Solar/Wind Harmer
1.116
276806AD2-047 C O1
Solar/Wind Harmer
12.916
274676JOLIET 29;8U
Adder
30.511
274734ELWOOD EC;8P
Adder
16.713
274736ELWOOD EC;9P
Adder
16.713
943121AE2-341 GEN
Solar/Wind Harmer
14.914
943591AF1-030 GEN
Solar/Wind Harmer
9.943
274682WAUKEGAN ;7U
Adder
17.565
959091AF2-200 GEN
Solar/Wind Harmer
18.438
274767LEE CO EC;8U
Adder
8.144
276668AB2-070 GEN1
Solar/Wind Harmer
1.303
274827FISK ;RP
50/50
10.217
972227AH1-698 GEN1
Adder
2.662
274776LINCOLN ;7U
Adder
7.259
274687WILL CNTY;4U
Adder
28.813
274687WILL CNTY;4U
Adder
28.813
274731ELWOOD EC;2P
Adder
16.726
274733ELWOOD EC;3P
Adder
16.726
274746AC1-111 G10
Adder
5.561
276882AE2-255 GEN
Solar/Wind Harmer
3.155
926823AC1-168 GEN
Solar/Wind Harmer
3.758
276655WTG1_EQ
Solar/Wind Harmer
6.612
274814UNIV PK N;0U
Adder
3.46
274807UNIV PK N;3U
Adder
3.452
274805UNIV PK N;1U
Adder
3.437
274888KELLY CRK;1U
Solar/Wind Harmer
7.128
274770LINCOLN ;1U
Adder
7.259
274771LINCOLN ;2U
Adder
7.259
972259AH1-714 GEN
Adder
19.364
274697ROCKY RD ;3P
Adder
2.95
274696ROCKY RD ;4P
Adder
11.115
962691AG1-118 GEN
Solar/Wind Harmer
28.792
274856ECOGROVE ;U1
Solar/Wind Harmer
3.052
276611AD2-172 GEN
Solar/Wind Harmer
2.316
938861AE1-114 GEN
Solar/Wind Harmer
7.314
274762LEE CO EC;3U
Adder
8.241
276603SUBLETTE C
Solar/Wind Harmer
0.925
276645AC1-214 GEN1
Solar/Wind Harmer
1.116
274808UNIV PK N;4U
Adder
3.415
970941AG2-585 GEN
Solar/Wind Harmer
15.092
274772LINCOLN ;3U
Adder
7.259
274800UNIV PARK;3U
Adder
6.572
276893AG1-478 C
Solar/Wind Harmer
0.452
276897AD1-100 C
Solar/Wind Harmer
30.836
274729ELWOOD EC;1P
Adder
16.726
274802UNIV PARK;5U
Adder
5.821
276805AD2-038 GEN
Solar/Wind Harmer
5.05
276799AD1-013 GEN
Solar/Wind Harmer
2.065
946671AF1-331 GEN
Solar/Wind Harmer
0.391
274850MENDOTA H;RU
Solar/Wind Harmer
2.395
276602WESTBROOK C
Solar/Wind Harmer
1.982
276863AD2-134 GEN
Solar/Wind Harmer
1.666
276889AE2-281 GEN
Solar/Wind Harmer
1.775
274858EASY ROAD;U2
Solar/Wind Harmer
4.245
970571AG2-364 GEN
Solar/Wind Harmer
17.683
276157O29GEN1
Solar/Wind Harmer
3.261
942111AE2-223 GEN
Solar/Wind Harmer
6.208
274724RIVER EC ;11
Adder
11.404
971993AH1-541 GEN
Solar/Wind Harmer
5.375
274723RIVER EC ;12
50/50
28.573
274773LINCOLN ;4U
Adder
7.259
274774LINCOLN ;5U
Adder
7.259
274801UNIV PARK;4U
Adder
6.572
276861AD2-134 GEN
Solar/Wind Harmer
1.666
971997AH1-543 GEN
Solar/Wind Harmer
14.549
274761LEE CO EC;2U
Adder
8.241
970569AG2-363 GEN
Solar/Wind Harmer
26.525
276158O29GEN2
Solar/Wind Harmer
4.288
939741AE1-205 GEN
Solar/Wind Harmer
15.147
972175AH1-670 GEN
Solar/Wind Harmer
8.832
274880W4-005 GEN4
Solar/Wind Harmer
1.759
274735ELWOOD EC;4P
Adder
16.726
274744AC1-111 GEN8
Adder
5.561
961011AF2-392 GEN
Solar/Wind Harmer
9.475
970169AG2-114 GEN
Solar/Wind Harmer
8.538
274848CAMPGROVE;RU
Solar/Wind Harmer
5.265
959341AF2-225 GEN
Solar/Wind Harmer
11.36
274811UNIV PK N;7U
Adder
3.43
276785W4-005 GEN1
Solar/Wind Harmer
1.759
276849AB2-070 GEN2
Solar/Wind Harmer
1.303
276848AB2-070 GEN3
Solar/Wind Harmer
1.303
274826FISK ;BP
50/50
14.417
276772AC2-154 GEN
Solar/Wind Harmer
3.367
939351AE1-166 GEN
Solar/Wind Harmer
6.301
276694AA1-018 GEN2
Solar/Wind Harmer
6.483
972228AH1-698 GEN2
Adder
3.782
274730ELWOOD EC;6P
Adder
16.713
970707AG2-453 GEN
Solar/Wind Harmer
28.408
274855GSG-6 ;RU
Solar/Wind Harmer
3.444
274853TWINGROVE;U1
Solar/Wind Harmer
5.187
959611AF2-252 GEN
Solar/Wind Harmer
1.674
274674JOLIET 9 ;6U
Adder
16.145
274732ELWOOD EC;7P
Adder
16.713
962781AG1-127 GEN
Solar/Wind Harmer
9.084
939401AE1-172 GEN
Solar/Wind Harmer
13.283
276876AE1-163_GEN2
Solar/Wind Harmer
6.213
972235AH1-702 GEN1
Adder
2.304
274857EASY ROAD;U1
Solar/Wind Harmer
4.245
274766LEE CO EC;7U
Adder
8.144
963831AG1-236 GEN
Solar/Wind Harmer
5.613
274728ELWOOD EC;5P
Adder
16.713
971177AH1-047 GEN
Solar/Wind Harmer
5.532
274863CRW1-WTG
Solar/Wind Harmer
5.068
274864CRW2-WTG
Solar/Wind Harmer
5.068
276612AE2-035 GEN
Solar/Wind Harmer
2.316
971681AH1-341 GEN
Solar/Wind Harmer
13.385
957751AF2-069 GEN
Solar/Wind Harmer
0.383
276174W4-005 GEN2
Solar/Wind Harmer
1.759
941551AE2-152 GEN
Solar/Wind Harmer
4.819
276691AA1-018 GEN1
Solar/Wind Harmer
0.478
274872LEEDK;1U
Solar/Wind Harmer
7.809
959081AF2-199 GEN
Solar/Wind Harmer
9.219
971067AG2-660 GEN
Solar/Wind Harmer
2.144
274822ROCKFORD ;11
Adder
18.03
970819AG2-516 GEN
Solar/Wind Harmer
10.902
971475AH1-234 GEN
Solar/Wind Harmer
20.266
276726Z2-087_GEN
Solar/Wind Harmer
5.99
274854TWINGROVE;U2
Solar/Wind Harmer
5.078
972179AH1-673 GEN
50/50
15.342
276164X3-005 C
Solar/Wind Harmer
0.97
276776AD2-060 GEN
Solar/Wind Harmer
0.51
972207SS24-0001
Solar/Wind Harmer
25.81
274676JOLIET 29;8U
Adder
31.641
274745AC1-111 GEN9
Adder
5.561
274871GR RIDGE ;2U
Solar/Wind Harmer
7.625
274682WAUKEGAN ;7U
Adder
17.565
274828WAUKEGAN ;BP
Adder
10.769
960751AF2-366 GEN
Solar/Wind Harmer
2.74
276901AD2-066 C O1
Solar/Wind Harmer
3.317
957471AF2-041 GEN
Solar/Wind Harmer
27.658
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
274812UNIV PK N;8U
Adder
3.43
274847GR RIDGE ;BU
Solar/Wind Harmer
5.016
971341AH1-150 GEN
Solar/Wind Harmer
18.438
971343AH1-151 GEN
Solar/Wind Harmer
18.438
276741O09 GEN1
Solar/Wind Harmer
3.063
274849CRESCENT ;1U
Solar/Wind Harmer
1.54
276763AC1-053 GEN1
Solar/Wind Harmer
2.256
276764AC1-053 GEN2
Solar/Wind Harmer
2.256
972038AH1-567 GEN2
Adder
0.411
274872LEEDK;1U
Solar/Wind Harmer
0.243
972236AH1-702 GEN2
Adder
2.003
274760LEE CO EC;1U
Adder
8.241
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.591
965091AG1-374 GEN
Solar/Wind Harmer
21.591
276686W4-005 GEN3
Solar/Wind Harmer
1.759
990407J1304
External Queue
3.7535388469696045
990512J1326
External Queue
4.853736400604248
991092J1477
External Queue
2.612919330596924
990117J1214
External Queue
11.036625862121582
990727J1377 G
External Queue
5.637885093688965
NYPJM->LTFIMP_NY
CLTF
0.848
TVALTFEXP_TVA->PJM
CLTF
0.873
LAGNLTFEXP_LAGN->PJM
CLTF
3.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.973
WECLTFEXP_WEC->PJM
CLTF
3.499
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.431
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346
MECLTFEXP_MEC->PJM
CLTF
10.858
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.319
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.23

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.08 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1783.23
MW Contribution:15.34
Bus #Bus NameTypeMW Contribution
960591AF2-350 GEN
Solar/Wind Harmer
12.074
274775LINCOLN ;6U
Adder
7.264
274777LINCOLN ;8U
Adder
7.264
274675JOLIET 29;7U
Adder
31.649
274675JOLIET 29;7U
Adder
30.519
972037AH1-567 GEN1
Adder
0.183
970833AG2-524 GEN
Solar/Wind Harmer
8.702
970833AG2-524 GEN
Solar/Wind Harmer
4.047
971411AH1-196 GEN
Solar/Wind Harmer
14.052
276868AE1-113 GEN
Solar/Wind Harmer
9.465
274887GEN-1.85
Solar/Wind Harmer
6.436
274674JOLIET 9 ;6U
Adder
16.144
958481AF2-142 GEN
Solar/Wind Harmer
15.409
274803UNIV PARK;6U
Adder
5.821
274693ROCKY RD ;1P
Adder
10.751
276843GEN-1.7
Solar/Wind Harmer
0.692
958011AF2-095 GEN
Solar/Wind Harmer
17.386
958491AF2-143 GEN
Solar/Wind Harmer
14.766
971573AH1-285 GEN
Solar/Wind Harmer
8.466
274695ROCKY RD ;2P
Adder
10.857
942991AE2-321 GEN
Solar/Wind Harmer
9.448
971333AH1-146 GEN
Solar/Wind Harmer
18.684
274861TOP CROP ;1U
Solar/Wind Harmer
5.622
276872AE1-163_GEN1
Solar/Wind Harmer
6.213
274765LEE CO EC;6U
Adder
8.26
274763LEE CO EC;4U
Adder
8.162
274851PROVIDENC;RU
Solar/Wind Harmer
2.372
276646AC1-214 GEN2
Solar/Wind Harmer
1.116
276806AD2-047 C O1
Solar/Wind Harmer
12.916
274676JOLIET 29;8U
Adder
30.51
274734ELWOOD EC;8P
Adder
16.713
274736ELWOOD EC;9P
Adder
16.713
943121AE2-341 GEN
Solar/Wind Harmer
14.912
943591AF1-030 GEN
Solar/Wind Harmer
9.941
274682WAUKEGAN ;7U
Adder
17.564
959091AF2-200 GEN
Solar/Wind Harmer
18.436
274767LEE CO EC;8U
Adder
8.143
276668AB2-070 GEN1
Solar/Wind Harmer
1.303
274776LINCOLN ;7U
Adder
7.264
274687WILL CNTY;4U
Adder
28.812
274687WILL CNTY;4U
Adder
28.812
274731ELWOOD EC;2P
Adder
16.725
274733ELWOOD EC;3P
Adder
16.725
274746AC1-111 G10
Adder
5.561
276882AE2-255 GEN
Solar/Wind Harmer
3.155
926823AC1-168 GEN
Solar/Wind Harmer
3.758
276655WTG1_EQ
Solar/Wind Harmer
6.612
274814UNIV PK N;0U
Adder
3.46
274807UNIV PK N;3U
Adder
3.452
274805UNIV PK N;1U
Adder
3.437
274888KELLY CRK;1U
Solar/Wind Harmer
7.128
274770LINCOLN ;1U
Adder
7.264
274771LINCOLN ;2U
Adder
7.264
972259AH1-714 GEN
Adder
19.362
274697ROCKY RD ;3P
Adder
2.949
274696ROCKY RD ;4P
Adder
11.113
962691AG1-118 GEN
Solar/Wind Harmer
28.788
274856ECOGROVE ;U1
Solar/Wind Harmer
3.052
276611AD2-172 GEN
Solar/Wind Harmer
2.316
938861AE1-114 GEN
Solar/Wind Harmer
7.314
274762LEE CO EC;3U
Adder
8.24
276603SUBLETTE C
Solar/Wind Harmer
0.925
276645AC1-214 GEN1
Solar/Wind Harmer
1.116
274808UNIV PK N;4U
Adder
3.415
970941AG2-585 GEN
Solar/Wind Harmer
15.092
274772LINCOLN ;3U
Adder
7.264
274800UNIV PARK;3U
Adder
6.572
276893AG1-478 C
Solar/Wind Harmer
0.452
276897AD1-100 C
Solar/Wind Harmer
30.838
274729ELWOOD EC;1P
Adder
16.725
274802UNIV PARK;5U
Adder
5.821
276805AD2-038 GEN
Solar/Wind Harmer
5.05
276799AD1-013 GEN
Solar/Wind Harmer
2.064
946671AF1-331 GEN
Solar/Wind Harmer
0.391
274850MENDOTA H;RU
Solar/Wind Harmer
2.394
276602WESTBROOK C
Solar/Wind Harmer
1.982
276863AD2-134 GEN
Solar/Wind Harmer
1.665
276889AE2-281 GEN
Solar/Wind Harmer
1.775
274858EASY ROAD;U2
Solar/Wind Harmer
4.244
970571AG2-364 GEN
Solar/Wind Harmer
17.682
276157O29GEN1
Solar/Wind Harmer
3.261
942111AE2-223 GEN
Solar/Wind Harmer
6.208
274724RIVER EC ;11
Adder
11.405
971993AH1-541 GEN
Solar/Wind Harmer
5.374
274723RIVER EC ;12
50/50
28.574
274773LINCOLN ;4U
Adder
7.264
274774LINCOLN ;5U
Adder
7.264
274801UNIV PARK;4U
Adder
6.572
276861AD2-134 GEN
Solar/Wind Harmer
1.665
971997AH1-543 GEN
Solar/Wind Harmer
14.547
274761LEE CO EC;2U
Adder
8.24
970569AG2-363 GEN
Solar/Wind Harmer
26.523
276158O29GEN2
Solar/Wind Harmer
4.287
939741AE1-205 GEN
Solar/Wind Harmer
15.146
972175AH1-670 GEN
Solar/Wind Harmer
8.832
274880W4-005 GEN4
Solar/Wind Harmer
1.759
274827FISK ;RP
50/50
10.217
972227AH1-698 GEN1
Adder
2.662
274735ELWOOD EC;4P
Adder
16.725
274744AC1-111 GEN8
Adder
5.561
961011AF2-392 GEN
Solar/Wind Harmer
9.474
970169AG2-114 GEN
Solar/Wind Harmer
8.537
274848CAMPGROVE;RU
Solar/Wind Harmer
5.265
959341AF2-225 GEN
Solar/Wind Harmer
11.36
274811UNIV PK N;7U
Adder
3.43
276785W4-005 GEN1
Solar/Wind Harmer
1.759
276849AB2-070 GEN2
Solar/Wind Harmer
1.303
276848AB2-070 GEN3
Solar/Wind Harmer
1.303
274826FISK ;BP
50/50
14.417
276772AC2-154 GEN
Solar/Wind Harmer
3.367
939351AE1-166 GEN
Solar/Wind Harmer
6.301
276694AA1-018 GEN2
Solar/Wind Harmer
6.483
972228AH1-698 GEN2
Adder
3.782
274730ELWOOD EC;6P
Adder
16.713
970707AG2-453 GEN
Solar/Wind Harmer
28.402
274855GSG-6 ;RU
Solar/Wind Harmer
3.444
274853TWINGROVE;U1
Solar/Wind Harmer
5.187
959611AF2-252 GEN
Solar/Wind Harmer
1.674
274674JOLIET 9 ;6U
Adder
16.144
274732ELWOOD EC;7P
Adder
16.713
962781AG1-127 GEN
Solar/Wind Harmer
9.082
939401AE1-172 GEN
Solar/Wind Harmer
13.283
276876AE1-163_GEN2
Solar/Wind Harmer
6.213
972235AH1-702 GEN1
Adder
2.304
274857EASY ROAD;U1
Solar/Wind Harmer
4.244
274766LEE CO EC;7U
Adder
8.143
963831AG1-236 GEN
Solar/Wind Harmer
5.613
971675AH1-338 GEN
Solar/Wind Harmer
16.793
971171AH1-044 GEN
Solar/Wind Harmer
18.436
274823ROCKFORD ;21
Adder
17.897
946321AF1-296 GEN
Solar/Wind Harmer
8.52
276656WTG2_EQ
Solar/Wind Harmer
0.875
941731AE2-173 GEN
Solar/Wind Harmer
4.403
274728ELWOOD EC;5P
Adder
16.713
971177AH1-047 GEN
Solar/Wind Harmer
5.531
274863CRW1-WTG
Solar/Wind Harmer
5.068
274864CRW2-WTG
Solar/Wind Harmer
5.068
276612AE2-035 GEN
Solar/Wind Harmer
2.316
971681AH1-341 GEN
Solar/Wind Harmer
13.383
957751AF2-069 GEN
Solar/Wind Harmer
0.382
276174W4-005 GEN2
Solar/Wind Harmer
1.759
941551AE2-152 GEN
Solar/Wind Harmer
4.819
276691AA1-018 GEN1
Solar/Wind Harmer
0.478
274872LEEDK;1U
Solar/Wind Harmer
7.808
959081AF2-199 GEN
Solar/Wind Harmer
9.218
971067AG2-660 GEN
Solar/Wind Harmer
2.144
274822ROCKFORD ;11
Adder
18.028
970819AG2-516 GEN
Solar/Wind Harmer
10.901
971475AH1-234 GEN
Solar/Wind Harmer
20.263
276726Z2-087_GEN
Solar/Wind Harmer
5.99
274854TWINGROVE;U2
Solar/Wind Harmer
5.078
972179AH1-673 GEN
50/50
15.343
276164X3-005 C
Solar/Wind Harmer
0.97
276776AD2-060 GEN
Solar/Wind Harmer
0.51
972207SS24-0001
Solar/Wind Harmer
25.827
274676JOLIET 29;8U
Adder
31.64
274745AC1-111 GEN9
Adder
5.561
274871GR RIDGE ;2U
Solar/Wind Harmer
7.624
274682WAUKEGAN ;7U
Adder
17.564
274828WAUKEGAN ;BP
Adder
10.768
960751AF2-366 GEN
Solar/Wind Harmer
2.74
276901AD2-066 C O1
Solar/Wind Harmer
3.317
957471AF2-041 GEN
Solar/Wind Harmer
27.654
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
274812UNIV PK N;8U
Adder
3.43
274847GR RIDGE ;BU
Solar/Wind Harmer
5.015
971341AH1-150 GEN
Solar/Wind Harmer
18.436
971343AH1-151 GEN
Solar/Wind Harmer
18.436
276741O09 GEN1
Solar/Wind Harmer
3.062
274849CRESCENT ;1U
Solar/Wind Harmer
1.54
276763AC1-053 GEN1
Solar/Wind Harmer
2.256
276764AC1-053 GEN2
Solar/Wind Harmer
2.256
274683WAUKEGAN ;8U
Adder
20.543
274683WAUKEGAN ;8U
Adder
17.317
970921AG2-575 GEN
Solar/Wind Harmer
9.55
970921AG2-575 GEN
Solar/Wind Harmer
2.221
274879MINONK ;1U
Solar/Wind Harmer
6.311
971335AH1-147 GEN
Solar/Wind Harmer
18.684
274862TOP CROP ;2U
Solar/Wind Harmer
4.695
274764LEE CO EC;5U
Adder
8.26
972267AH1-718 GEN
Adder
3.611
276708O09 GEN2
Solar/Wind Harmer
3.062
276782AC1-033 GEN
Solar/Wind Harmer
3.294
960611AF2-352 GEN
Solar/Wind Harmer
1.674
972038AH1-567 GEN2
Adder
0.411
274872LEEDK;1U
Solar/Wind Harmer
0.243
972236AH1-702 GEN2
Adder
2.003
274760LEE CO EC;1U
Adder
8.24
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.589
965091AG1-374 GEN
Solar/Wind Harmer
21.59
276686W4-005 GEN3
Solar/Wind Harmer
1.759
990407J1304
External Queue
3.753084421157837
990512J1326
External Queue
4.853159427642822
991092J1477
External Queue
2.612651824951172
990117J1214
External Queue
11.035313606262207
990727J1377 G
External Queue
5.6371893882751465
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.319
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.229
NYPJM->LTFIMP_NY
CLTF
0.848
TVALTFEXP_TVA->PJM
CLTF
0.873
LAGNLTFEXP_LAGN->PJM
CLTF
3.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.968
WECLTFEXP_WEC->PJM
CLTF
3.498
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.431
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346
MECLTFEXP_MEC->PJM
CLTF
10.857
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 970244 TO BUS 290597 CKT 1    /*AG2-165 TP   765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P4_#1750_05DUMONT 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243219 CKT 3    /*05DUMONT     765.0 - 05DUMONT     345.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-1'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 243229 TO BUS 960680 CKT 1   /*05OLIVE      345.0 - AF2-359 TP   345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-2'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 960680 TO BUS 255112 CKT 1   /*AF2-359 TP   345.0 - 17STJOHN     345.0
END
CONTINGENCY 'COMED_P4_023-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 243918 CKT 1   /*05DUMONT     345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243229 TO BUS 243918 CKT 1   /*05OLIVE      345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 274750 TO BUS 255112 CKT 1   /*CRETE EC ;BP 345.0 - 17STJOHN     345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
CONTINGENCY 'COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1   /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
255113 to 243219 ckt 1
270677 to 255109 ckt 1

Winter Peak Analysis

The New Service Request AH1-673 was evaluated as a 85.0 MW (85.0 MW Capacity) injection in the ComEd area.

AH1-673 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 85.0 MW (85.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-673 was evaluated as a 85.0 MW injection and 85.0 MW withdrawal in the ComEd area.

AH1-673 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 85.0 MW (85.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AC1-033Kewanee 138 kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-111Aurora 138kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD2-020Valley 138 kVEngineering & Procurement
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-079Capitol Ave 34.5kVIn Service
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-205McLean 345 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-173McLean 345 kVActive
AE2-223McLean 345 kVActive
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-321Belvidere-Marengo 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AF1-030Sandwich-Plano 138 kVActive
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-331Twombley RoadEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-225McLean 345 kVActive
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-441Burnham 138kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-127Crego Rd 138 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-512University Park North 345 kVWithdrawn
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_18494
Title
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Description
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-673 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-673 could receive cost allocation. Although AH1-673 may not presently have cost responsibility for this upgrade, AH1-673 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9133.0
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
n9133.0 / NIPS_TC1_15152
Title
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Description
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Total Cost ($USD)
$1,800,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-673 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-673 could receive cost allocation. Although AH1-673 may not presently have cost responsibility for this upgrade, AH1-673 is a potential Aggregate Pool Contributor.

FacilityContingency
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18670
Title
17STILLWELL 345.0 kV to 05DUMONT 345.0 kV ckt 1 - Reconductor and Replace Equipment
Description
Rebuild ~8.62 miles of AEP owned 345kV line from Dumont to Stillwell utilizing 3-954 CARDINAL ACSR 54/7. At Dumont, replace the 2-1700 KCM AAC 61 str station conductor, the wavetrap facing Stillwell, the switches for CBs F and F1, and increase the CT thermal limit above 2739.336 MVA. NIPSCO will have to address their elements below 2739.336 SE MVA.
Total Cost ($USD)
$26,060,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-673 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-673 could receive cost allocation. Although AH1-673 may not presently have cost responsibility for this upgrade, AH1-673 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)

System Reinforcement: n8379
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n8379 / CE_NUN_L11212_NEW TR
Title
Wilton Center - Install 3rd Transformer
Description
Install 3rd Transforner 1120 MVA at TSS 112 Wilton Center. New breaker installations and bus work at 765kV and 345kV. New relay scheme, foundation work and TSS 112 control building upgrades. A preliminary estimate of $38 M with a preliminary construction timelline of 48 months. This is a resolution to the contingency thererfore the ratings will not change.
Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-673 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-673 could receive cost allocation. Although AH1-673 may not presently have cost responsibility for this upgrade, AH1-673 is a potential Aggregate Pool Contributor.

FacilityContingency
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 lineCOMED_P4_112-65-BT3-4___SRT-A
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 lineCOMED_P4_112-65-BT4-5___SRT-A

Attachments

AH1-673 One Line Diagram

AH1-673 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.