AH1-690 Phase I Study Report

v1.00 released 2025-10-29 21:50

Bay Shore - Lallendorf 345 kV

1440.0 MW Capacity / 1475.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is CPV Oregon, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Transmission Systems, Incorporated.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Natural Gas generating facility located in the American Transmission Systems, Incorporated zone — Lucas County, Ohio. The installed facilities will have a total capability of 1475.0 MW with 1440.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-690
Project Name:
Bay Shore - Lallendorf 345 kV
Project Developer Name:
CPV Oregon, LLC
State:
Ohio
County:
Lucas
Transmission Owner:
American Transmission Systems, Incorporated
MFO:
1475.0
MWE:
1475.0
MWC:
1440.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-690 will interconnect on the American Transmission Systems, Incorporated transmission system by tapping the BayShore - Lallendorf 345 kV 1 and 2 lines.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-690 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-690Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$843,231$0
Other Scope$60,800$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$32,872,665$32,872,665
Network Upgrades$7,999,870$7,999,870
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$1,232,419,113$1,232,419,113
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$17,528,776$17,528,776
Distribution$3,936,000$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$1,295,660,455$1,290,820,424

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-690

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-690 Project due at DP1
ABA - B
AH1-690$129,082,042$5,900,000$123,182,042

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Integrate Interconnection Facilities protection and controls to the Transmission Owner system.$63,840 $63,840
(Pending)Construction of (1) span of conductor between the new Interconnection substation takeoff structure and Developer owned dead end structure.$779,391 $779,391
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construct a new 345 kV 5-breaker ring bus Interconnection substation.$32,796,665 $32,796,665
(Pending)ADSS fiber to new interconnection substation.$76,000 $76,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Cut the existing Bayshore-Lallendorf No.1 345kV line and Loop in the new Interconnection substation.$3,946,735 $3,946,735
(Pending)Revise relay settings at Bayshore substation as required.$53,200 $53,200
(Pending)Revise relay settings at Lallendorf substation as required.$53,200 $53,200
(Pending)Cut the existing Bayshore-Lallendorf No.1 345kV line and loop in the new interconnection substation.$3,946,735 $3,946,735
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install 345 kV revenue metering within new Interconnection substation.$60,800 $60,800

Based on the scope of work for the Interconnection Facilities, it is expected to take 55 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

The Transmission Owner identified network impacts to Distribution facilities as follows:

Transmission Owner Identified Network Impacts to Distribution Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
245749 05FNDCTREQ 1.0 - 245747 05FINDLAY C 34.5 CKT 1 AEP_P7-1_#17590___SRT-A
CONTINGENCY 'AEP_P7-1_#17590___SRT-A'  

  OPEN BRANCH FROM BUS 288663 TO BUS 288672 CKT 1                  / 288663 05FIN DATAZ 138 288672 05N.FINDLAY2 138 1

  OPEN BRANCH FROM BUS 288663 TO BUS 288664 CKT Z                  / 288663 05FIN DATAZ 138 288664 05FIN DATA 138 Z

  OPEN BRANCH FROM BUS 247172 TO BUS 288663 CKT 1                  / 247172 05EBERSO 138 288663 05FIN DATAZ 138 1

  OPEN BRANCH FROM BUS 247172 TO BUS 247893 CKT 1                  / 247172 05EBERSO 138 247893 05FLAG CITY 138 1

  OPEN BRANCH FROM BUS 243057 TO BUS 247893 CKT 1                  / 243057 05NEW LIBR1 138 247893 05FLAG CITY 138 1

END
45.0111.45 %7.02

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
239713 02NOVA 69.0 - 239167 02WELLNG 69.0 CKT 1 ATSI_P1-2_OEC-345-809_SRT-A 33.0159.11 %7.44
240865 02GRNSPR 69.0 - 240851 02CLYDE 69.0 CKT 0 ATSI_P1-2_OEC-345-810_SRT-A 58.0101.57 %5.99
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 ATSI_P7-1_TE-345-027A_SRT-A
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'  /* DB - AD1-103 & DB - HAYES 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1            /* 02DAV-BE 345 AD1-103 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1            /* 02DAV-BE 345 02HAYES 345

END
31.0120.02 %2.31
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  REMOVE LOAD D1 FROM BUS 243011                                   / 243011 05FULTON 138 D1

  REMOVE LOAD T1 FROM BUS 245540                                   / 245540 05BLOOMFLD8 138 T1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  REMOVE LOAD T1 FROM BUS 243148                                   / 243148 05WINDFL 138 T1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  REMOVE LOAD D1 FROM BUS 245716                                   / 245716 05WALDO 69.0 D1

  REMOVE SWSHUNT FROM BUS 245716                                   / 245716 05WALDO 69.0

  OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1                  / 245716 05WALDO 69.0 247032 05UNCAPHSS 69.0 1

  REMOVE LOAD D1 FROM BUS 247032                                   / 247032 05UNCAPHSS 69.0 D1

  OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1                  / 245711 05S MORRAL 69.0 247032 05UNCAPHSS 69.0 1

/*  OPEN BRANCH FROM BUS 972046 TO BUS 247032 CKT 1                  / 972046 AH1-572 TP 69.0 247032 05UNCAPHSS 69.0 1 /* Withdrawn

  REMOVE LOAD D1 FROM BUS 245711                                   / 245711 05S MORRAL 69.0 D1

  OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1                  / 245710 05RIDGEDALEZ69.0 245711 05S MORRAL 69.0 1

  OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1                 / 245710 05RIDGEDALEZ69.0 290079 05GOODNOW SS69.0 Z1

  OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1                  / 245391 05RIDGEDALE869.0 245710 05RIDGEDALEZ69.0 1

  OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1                  / 245699 05HARPSTER P69.0 290079 05GOODNOW SS69.0 1

  REMOVE LOAD T1 FROM BUS 245391                                   / 245391 05RIDGEDALE869.0 T1

  REMOVE LOAD C1 FROM BUS 245699                                   / 245699 05HARPSTER P69.0 C1

  OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1                  / 245699 05HARPSTER P69.0 245701 05HARPSTER 69.0 1

END
31.0119.56 %1.84
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
31.0114.3 %1.84
245715 05U SANDSK 69.0 - 247379 05NEVADA SS 69.0 CKT 1 AEP_P2-2_#17157_05E.TIFFIN 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#17157_05E.TIFFIN 69.0_1_SRT-A'  

  OPEN BRANCH FROM BUS 243032 TO BUS 245630 CKT 1                  / 243032 05E.TIFFIN 69.0 245630 05S TIFFIN 69.0 1

  OPEN BRANCH FROM BUS 243032 TO BUS 290149 CKT 1                  / 243032 05E.TIFFIN 69.0 290149 05MOUSEY SS 69.0 1

  REMOVE LOAD D1 FROM BUS 243032                                   / 243032 05E.TIFFIN 69.0 D1

END
31.0109.62 %1.56
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 ATSI_P7-1_TE-345-027A_SRT-A
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'  /* DB - AD1-103 & DB - HAYES 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1            /* 02DAV-BE 345 AD1-103 345

  DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1            /* 02DAV-BE 345 02HAYES 345

END
31.0115.85 %2.31
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P4_#13372_05N WALDO 69.0_A_SRT-A
CONTINGENCY 'AEP_P4_#13372_05N WALDO 69.0_A_SRT-A'  

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  REMOVE LOAD D1 FROM BUS 243011                                   / 243011 05FULTON 138 D1

  REMOVE LOAD T1 FROM BUS 245540                                   / 245540 05BLOOMFLD8 138 T1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  REMOVE LOAD T1 FROM BUS 243148                                   / 243148 05WINDFL 138 T1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  REMOVE LOAD D1 FROM BUS 245716                                   / 245716 05WALDO 69.0 D1

  REMOVE SWSHUNT FROM BUS 245716                                   / 245716 05WALDO 69.0

  OPEN BRANCH FROM BUS 245716 TO BUS 247032 CKT 1                  / 245716 05WALDO 69.0 247032 05UNCAPHSS 69.0 1

  REMOVE LOAD D1 FROM BUS 247032                                   / 247032 05UNCAPHSS 69.0 D1

  OPEN BRANCH FROM BUS 245711 TO BUS 247032 CKT 1                  / 245711 05S MORRAL 69.0 247032 05UNCAPHSS 69.0 1

/*  OPEN BRANCH FROM BUS 972046 TO BUS 247032 CKT 1                  / 972046 AH1-572 TP 69.0 247032 05UNCAPHSS 69.0 1 /* Withdrawn

  REMOVE LOAD D1 FROM BUS 245711                                   / 245711 05S MORRAL 69.0 D1

  OPEN BRANCH FROM BUS 245710 TO BUS 245711 CKT 1                  / 245710 05RIDGEDALEZ69.0 245711 05S MORRAL 69.0 1

  OPEN BRANCH FROM BUS 245710 TO BUS 290079 CKT Z1                 / 245710 05RIDGEDALEZ69.0 290079 05GOODNOW SS69.0 Z1

  OPEN BRANCH FROM BUS 245391 TO BUS 245710 CKT 1                  / 245391 05RIDGEDALE869.0 245710 05RIDGEDALEZ69.0 1

  OPEN BRANCH FROM BUS 245699 TO BUS 290079 CKT 1                  / 245699 05HARPSTER P69.0 290079 05GOODNOW SS69.0 1

  REMOVE LOAD T1 FROM BUS 245391                                   / 245391 05RIDGEDALE869.0 T1

  REMOVE LOAD C1 FROM BUS 245699                                   / 245699 05HARPSTER P69.0 C1

  OPEN BRANCH FROM BUS 245699 TO BUS 245701 CKT 1                  / 245699 05HARPSTER P69.0 245701 05HARPSTER 69.0 1

END
31.0115.59 %1.84
247379 05NEVADA SS 69.0 - 245687 05BROK SWR 69.0 CKT 1 AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A
CONTINGENCY 'AEP_P2-2_#14773_05N WALDO 69.0_1_SRT-A'                                                   /Waldo - La Rue line tapped by AD1-106 & AG2-595

  OPEN BRANCH FROM BUS 243048 TO BUS 245708 CKT 1                  / 243048 05N WALD 138 245708 05N WALDO 69.0 1

  OPEN BRANCH FROM BUS 245708 TO BUS 245716 CKT 1                  / 245708 05N WALDO 69.0 245716 05WALDO 69.0 1

  OPEN BRANCH FROM BUS 243048 TO BUS 270372 CKT 1                  / 243048 05N WALD 138 270372 AD1-106 TAP 138 1

  OPEN BRANCH FROM BUS 243048 TO BUS 243148 CKT 1                  / 243048 05N WALD 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 243011 TO BUS 243148 CKT 1                  / 243011 05FULTON 138 243148 05WINDFL 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243011 CKT 1                  / 242963 05HEDDSS 138 243011 05FULTON 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 245540 CKT 1                  / 242963 05HEDDSS 138 245540 05BLOOMFLD8 138 1

  OPEN BRANCH FROM BUS 242963 TO BUS 243153 CKT 1                  / 242963 05HEDDSS 138 243153 05WMTVER 138 1

  REMOVE LOAD D2 FROM BUS 245708                                   / 245708 05N WALDO 69.0 D2

END
31.0110.49 %1.84
Transmission Owner Identified System Reinforcements
AH1-690 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
ATSI(Pending) / TC2-ATSI-L06SubRegionalReconductor/rebuild 4.8 miles between Greensprings Tap and Clyde Tap6.0 MW100.0%$17,380,145
AEP(Pending) / TC2-AEP-149DistributionAt Findlay Center TR#1 138/34.5kV 45MVA needs to be replaced with a 138/34.5kV 90MVA bank7.0 MW100.0%$3,936,000
ATSI(Pending) / TC2-ATSI-L02SubRegionalUpgrade (1) 4A overcurrent relay for breaker B41 at Wellington7.4 MW29.1%$148,631
Grand Total:$21,464,776

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L06
Category
SubRegional
Title
Reconductor/rebuild 4.8 miles between Greensprings Tap and Clyde Tap
Description
Reconductor (possible rebuild) 4.8 miles of 4/0 CU 19 transmission line between Greensprings Tap and Clyde Tap on the Bellevue - West Fremont 69kV line using one (1) 795 26/7 "Drake ACSS New ratings to be 164/206/237 MVA
Total Cost
$17,380,145
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-6906.0 MW100.0%$17,380,145

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-190
Category
SubRegional
Title
Nevada - Sands: ~11.2 miles of 69kV single circuit needs rebuilt.
Description
Nevada - Sands: ~11.2 miles of 69kV single circuit needs rebuilt. Existing conductor 1-4/0 COPPER 19 75/75 °C
Total Cost
$35,840,000
Note: Based on PJM cost allocation criteria, AH1-690 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-690 could receive cost allocation. Although Queue Project AH1-690 may not presently have cost responsibility for this upgrade, Queue Project AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-690 comes into service prior to completion of the upgrade, Queue Project AH1-690 will need an interim study.

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-149
Category
Distribution
Title
At Findlay Center TR#1 138/34.5kV 45MVA needs to be replaced with a 138/34.5kV 90MVA bank
Description
At Findlay Center TR#1 138/34.5kV 45MVA needs to be replaced with a 138/34.5kV 90MVA bank
Total Cost
$3,936,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-6907.0 MW100.0%$3,936,000

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-193
Category
SubRegional
Title
Nevada - Brok: ~3 miles of 69kV single circuit needs rebuilt.
Description
Nevada - Brok: ~3 miles of 69kV single circuit needs rebuilt.
Total Cost
$9,600,000
Note: Based on PJM cost allocation criteria, AH1-690 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AH1-690 could receive cost allocation. Although Queue Project AH1-690 may not presently have cost responsibility for this upgrade, Queue Project AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AH1-690 comes into service prior to completion of the upgrade, Queue Project AH1-690 will need an interim study.

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L02
Category
SubRegional
Title
Upgrade (1) 4A overcurrent relay for breaker B41 at Wellington
Description
Upgrade (1) 4A overcurrent relay for breaker B41 at Wellington New ratings to be 55/69/80 MVA
Total Cost
$509,895
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-10918.1 MW70.9%$361,264
AH1-6907.4 MW29.1%$148,631

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-690 was evaluated as a 1475.0 MW (1440.0 MW Capacity) injection in the ATSI area.

AH1-690 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1475.0 MW (1475.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2ATSI
02ASQ-11-02AVQ1 138.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-001_SRT-A
TowerAC102.13 %332.0B339.0745.19
GD2ATSI
02AVERY-02SHNROK 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC135.2 %282.0B381.2758.35
GD2ATSI
02AVERY-02SHNROK 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC132.18 %282.0B372.7458.38
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-008B_SRT-SL
BreakerAC168.3 %1683.0B2832.52441.81
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-013_SRT-SL
BreakerAC146.58 %1683.0B2466.99445.14
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-014_SRT-A
BreakerAC146.58 %1683.0B2466.97445.15
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-009_SRT-A
BreakerAC146.4 %1683.0B2463.99445.37
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.59445.37
GD2ATSI
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC109.31 %1745.0B1907.45238.13
GD2ATSI
02BEAVER-02JONSON 138.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC122.44 %282.0B345.2941.55
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-901_SRT-SL
BreakerAC113.76 %1720.0B1956.7209.15
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-007A_SRT-SL
BreakerAC104.78 %1878.0B1967.82212.09
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-031_SRT-A
BreakerAC100.84 %1878.0B1893.72206.56
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC174.17 %1878.0B3270.93297.55
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-003_SRT-SL
BreakerAC104.76 %1878.0B1967.48210.31
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-028_SRT-A
BreakerAC101.37 %1878.0B1903.65207.62
GD2ATSI
02BRWELL-02FORD 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC170.25 %230.0B391.5660.94
GD2ATSI
02BRWELL-02FORD 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC166.37 %230.0B382.6560.97
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC149.08 %1892.0B2820.59306.57
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC146.41 %1892.0B2770.12307.32
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC144.5 %1892.0B2733.88307.27
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.86 %1892.0B2589.31307.1
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC136.39 %1892.0B2580.58307.27
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC155.03 %1646.0B2551.84290.29
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC155.03 %1646.0B2551.84290.29
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B2_SRT-SL
BreakerAC153.46 %1646.0B2525.94287.75
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC153.46 %1646.0B2525.94287.75
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC151.55 %1646.0B2494.57280.32
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC136.64 %1646.0B2249.01287.75
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.34275.12
GD2ATSI
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
AEP_P4_#8396_05OHIOCT 345_M_SRT-A
BreakerAC108.55 %209.0B226.8823.04
GD2ATSI
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
AEP_P4_#16815_05OHIOCT 345_M2_SRT-A
BreakerAC108.52 %209.0B226.8123.04
GD2ATSI
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
ATSI_P2-3_OES-138-020_SRT-SL
BreakerAC105.07 %209.0B219.5920.84
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-025_BDR_A_SRT-SL
BreakerAC113.1 %132.0B149.2928.95
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P7-1_CEI-345-010_SRT-A
TowerAC109.05 %132.0B143.9529.47
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P1-2_CEI-345-701_SRT-A
SingleAC106.07 %132.0B140.0130.05
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-002H_SRT-SL
BreakerAC106.07 %132.0B140.0130.05
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-018_BDR_A_SRT-SL
BreakerAC105.53 %132.0B139.330.09
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P7-1_CEI-345-002_SRT-A
TowerAC104.56 %132.0B138.0229.83
GD2ATSI
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-002I_SRT-A
BreakerAC104.53 %132.0B137.9829.83
GD2ATSI
02GALION-02GALION 345.0/138.0 kV Ckt 3 transformer
ATSI_P2-3_OES-138-021_SRT-SL
BreakerAC103.25 %417.0B430.5440.09
GD2ATSI
02GALION-02GALION 345.0/138.0 kV Ckt 4 transformer
ATSI_P2-3_OES-138-018_SRT-SL
BreakerAC104.79 %411.0B430.6940.11
GD2ATSI
02GRNFLD-02N DEPT 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC157.88 %242.0B382.0760.94
GD2ATSI
02GRNFLD-02N DEPT 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC154.19 %242.0B373.1560.97
GD2ATSI
02GRNFLD-02NASA 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC179.06 %192.0B343.854.56
GD2ATSI
02GRNFLD-02NASA 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC177.37 %192.0B340.5554.59
GD2ATSI
02HAYES-02AVERY 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC123.09 %339.0B417.2760.6
GD2ATSI
02HAYES-02AVERY 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC120.42 %339.0B408.2160.63
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC146.75 %1878.0B2755.89288.19
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC144.08 %1878.0B2705.74289.62
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC142.21 %1878.0B2670.76288.97
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.95288.81
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.09288.97
GD2ATSI
02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC175.39 %352.0B617.3789.7
IPDATSI
02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC126.45 %352.0B445.0995.19
GD2AEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC124.85 %1409.0B1759.15788.05
IPDAEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC110.58 %1409.0B1558.11788.05
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-007_SRT-SL
BreakerAC137.87 %1878.0B2589.19230.61
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-004_SRT-A
BreakerAC118.2 %1878.0B2219.8234.32
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-005_SRT-SL
BreakerAC118.2 %1878.0B2219.73234.28
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-006_SRT-SL
BreakerAC118.2 %1878.0B2219.73234.28
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.73234.28
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC109.02 %1878.0B2047.43211.68
GD2ATSI
02N DEPT-02BRWELL 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC171.21 %230.0B393.7960.94
GD2ATSI
02N DEPT-02BRWELL 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC167.34 %230.0B384.8860.97
GD2ATSI
02NASA-02BEAVER 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC178.12 %192.0B341.9954.56
GD2ATSI
02NASA-02BEAVER 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC176.43 %192.0B338.7454.59
GD2ATSI
02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC108.86 %314.0B341.8266.07
GD2ATSI
02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC106.41 %314.0B334.1266.1
GD2ATSI
02OTTAWA-02LAKVEW 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC115.82 %516.0B597.6389.7
GD2AEP/ATSI
02W.FREM-05FRMNT 138.0 kV Ckt 1 line
AEP_P4_#17249_05FOSTOR 345_A1_SRT-A
BreakerAC108.84 %380.0B413.5897.56
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC117.99 %1302.0B1536.2387.56
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC110.86 %1302.0B1443.4594.17
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC104.12 %1302.0B1355.5874.51
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC103.45 %1302.0B1346.9281.32
GD2AEP
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC158.21 %167.0B264.219.05
GD2AEP
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC156.66 %167.0B261.629.06
GD2AEP
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC156.47 %167.0B261.319.06
GD2AEP
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC144.17 %167.0B240.779.06
GD2AEP
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC161.25 %167.0B269.299.05
GD2AEP
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC159.7 %167.0B266.79.06
GD2AEP
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC159.52 %167.0B266.49.06
GD2AEP
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC145.35 %167.0B242.739.06
GD2AEP
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC159.14 %167.0B265.769.05
GD2AEP
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC157.59 %167.0B263.189.06
GD2AEP
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC157.41 %167.0B262.879.06
GD2AEP
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC143.23 %167.0B239.29.06
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
BreakerAC112.9 %971.0B1096.25115.56
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
BreakerAC105.18 %971.0B1021.28115.99
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
BreakerAC104.18 %971.0B1011.61116.09
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC104.17 %971.0B1011.54116.09
GD2AEP
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC101.83 %1301.0B1324.8189.12
GD2AEP
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC156.86 %167.0B261.969.05
GD2AEP
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC155.32 %167.0B259.389.06
GD2AEP
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC155.13 %167.0B259.079.06
GD2AEP
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC140.96 %167.0B235.419.06
GD2AEP
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC150.94 %167.0B252.079.05
GD2AEP
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC149.39 %167.0B249.499.06
GD2AEP
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC149.21 %167.0B249.189.06
GD2AEP
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC135.04 %167.0B225.529.06
GD2AEP
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC154.46 %167.0B257.959.05
GD2AEP
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC152.91 %167.0B255.379.06
GD2AEP
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC152.74 %167.0B255.079.06
GD2AEP
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC138.56 %167.0B231.49.06
GD2AEP
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC103.4 %255.0B263.6715.52
GD2AEP
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC102.5 %255.0B261.3615.53
GD2AEP
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC102.45 %255.0B261.2514.96
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC182.88 %508.54B930.0328.67
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC178.67 %508.54B908.5928.67
GD2AEP
AC2-015 TAP-05HOWARD1 138.0 kV Ckt 1 line
AEP_P4_#7105_05MELMOR 138_B2_SRT-A
BreakerAC102.18 %183.0B186.9926.1
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC165.39 %1499.0B2479.15275.94
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-F1_SRT-A
BreakerAC145.45 %1798.0B2615.26289.96
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-12_SRT-A
BreakerAC145.45 %1798.0B2615.26289.96
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC142.16 %1798.0B2556.01279.99
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010B1_SRT-SL
BreakerAC141.11 %1798.0B2537.18287.42
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC123.08 %1798.0B2212.91287.42
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.36274.79
GD2AEP/DVP
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC195.0 %167.0B325.658.44
GD2AEP/DVP
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC193.53 %167.0B323.28.45
GD2AEP/DVP
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC193.36 %167.0B322.918.45
GD2AEP/DVP
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC192.44 %156.98B302.18.45
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
AEP_P4_#17249_05FOSTOR 345_A1_SRT-A
BreakerAC116.88 %223.0B260.6430.96
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
AEP_P4_#10098_05LCKWRD 138_A_SRT-A
BreakerAC109.73 %223.0B244.719.24
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
AEP_P2-2_#5123_05LCKWRD 138_1_SRT-A
BusAC109.65 %223.0B244.5319.27
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
AEP_P4_#5123_05LCKWRD 138_B_SRT-A
BreakerAC109.65 %223.0B244.5119.27
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC105.2 %223.0B234.613.4
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC103.28 %223.0B230.3112.53
GD2AEP
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
AEP_P2-2_#744_05FOSTOR 345_2_SRT-A
BusAC100.96 %223.0B225.1412.11
GD2AEP/ATSI
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC106.19 %1308.0B1388.99228.6
GD2AEP/ATSI
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC105.3 %1308.0B1377.33222.24
GD2ATSI
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
ATSI_P1-2_TE-345-606_SRT-A-1
SingleAC102.39 %1774.0B1816.36717.96
GD2ATSI
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
ATSI_P2-3_TE-345-002_SRT-SL
BreakerAC101.27 %1720.0B1741.77686.08
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-018_SRT-A
SingleAC139.93 %128.0B179.127.01
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-017_SRT-A
SingleAC139.93 %128.0B179.127.01
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1154-W_SRT-A
BusAC124.81 %128.0B159.767.85
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Base Case
SingleAC116.38 %114.0A132.687.01
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
AP_P2-2_WP-230-001T_SRT-A
BusAC113.06 %128.0B144.717.6

Details for 02ASQ-11-02AVQ1 138.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-001_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02ASQ-11-02AVQ1 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-001_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.13 %
Rating:332.0 MVA
Rating Type:B
MVA to Mitigate:339.07
MW Contribution:45.19
Bus #Bus NameTypeMW Contribution
241886AC2-103 GEN2
Solar/Wind Harmer
2.539
972211AH1-690 GEN
Adder
45.194
23857102WLORG-A
Adder
3.599
957071AF2-004 GEN
Adder
1.895
966321AG1-501 GEN
Adder
0.726
957111AF2-005 GEN
Adder
0.58
241885AC2-103 GEN1
Solar/Wind Harmer
2.539
23857202WLORG-B
Adder
3.708
966311AG1-500 GEN
Adder
22.138
LAGNLTFEXP_LAGN->PJM
CLTF
1.035
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.536
TVALTFEXP_TVA->PJM
CLTF
0.477
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.327
CPLELTFEXP_CPLE->PJM
CLTF
0.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.401
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.89
MECLTFEXP_MEC->PJM
CLTF
1.29
SIGELTFEXP_SIGE->PJM
CLTF
0.035

Details for 02AVERY-02SHNROK 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02AVERY-02SHNROK 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.2 %
Rating:282.0 MVA
Rating Type:B
MVA to Mitigate:381.27
MW Contribution:58.35
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
2.955
241885AC2-103 GEN1
Solar/Wind Harmer
2.567
274732ELWOOD EC;7P
Adder
1.685
274729ELWOOD EC;1P
Adder
1.685
274730ELWOOD EC;6P
Adder
1.685
274734ELWOOD EC;8P
Adder
1.685
274736ELWOOD EC;9P
Adder
1.685
24191202EL_AA1-006
50/50
0.309
241886AC2-103 GEN2
Solar/Wind Harmer
2.567
972211AH1-690 GEN
Adder
58.352
274731ELWOOD EC;2P
Adder
1.685
274733ELWOOD EC;3P
Adder
1.685
274735ELWOOD EC;4P
Adder
1.685
274728ELWOOD EC;5P
Adder
1.685
LAGNLTFEXP_LAGN->PJM
CLTF
1.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.476
TVALTFEXP_TVA->PJM
CLTF
0.507
NYPJM->LTFIMP_NY
CLTF
0.482
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.376
CPLELTFEXP_CPLE->PJM
CLTF
0.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.012
MECLTFEXP_MEC->PJM
CLTF
1.464
SIGELTFEXP_SIGE->PJM
CLTF
0.038

Details for 02AVERY-02SHNROK 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02AVERY-02SHNROK 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.18 %
Rating:282.0 MVA
Rating Type:B
MVA to Mitigate:372.74
MW Contribution:58.38
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
2.956
274732ELWOOD EC;7P
Adder
1.688
24191202EL_AA1-006
50/50
0.309
972211AH1-690 GEN
Adder
58.38
274731ELWOOD EC;2P
Adder
1.688
274733ELWOOD EC;3P
Adder
1.688
274735ELWOOD EC;4P
Adder
1.688
274728ELWOOD EC;5P
Adder
1.688
274729ELWOOD EC;1P
Adder
1.688
274730ELWOOD EC;6P
Adder
1.688
274734ELWOOD EC;8P
Adder
1.688
274736ELWOOD EC;9P
Adder
1.688
LAGNLTFEXP_LAGN->PJM
CLTF
1.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.482
TVALTFEXP_TVA->PJM
CLTF
0.509
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.46
WECLTFEXP_WEC->PJM
CLTF
0.376
CPLELTFEXP_CPLE->PJM
CLTF
0.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.982
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.019
MECLTFEXP_MEC->PJM
CLTF
1.467
SIGELTFEXP_SIGE->PJM
CLTF
0.038

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-008B_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-008B_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.3 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2832.52
MW Contribution:441.81
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.743
241832AE2-181_GEN
Solar/Wind Harmer
1.964
958321AF2-126 GEN
Solar/Wind Harmer
1.44
23906502RICHG2&3
Adder
1.317
270541AE2-072 C
Solar/Wind Harmer
4.336
270575GUS2 35KV
Solar/Wind Harmer
9.524
970217AG2-149 GEN
Solar/Wind Harmer
24.156
247604X1-042
Adder
0.294
270044AE2-322 C
Solar/Wind Harmer
0.914
270404AC1-167 GEN
Solar/Wind Harmer
0.761
24441205WTRV SLR C
Solar/Wind Harmer
0.093
270258AD1-119 GEN
Solar/Wind Harmer
1.873
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
3.628
958091AF2-103 GEN
Solar/Wind Harmer
0.103
270588AE1-091_GEN
Solar/Wind Harmer
7.012
24642205MAYFLWER
Adder
0.396
247643Z2-116 C
Solar/Wind Harmer
0.043
970031AG2-029 GEN
Solar/Wind Harmer
18.318
270191TR4_S_V150
Solar/Wind Harmer
1.803
270247TR4_N_V136
Solar/Wind Harmer
0.511
959331AF2-224 GEN
Solar/Wind Harmer
5.881
965021AG1-366 GEN
Solar/Wind Harmer
1.368
270485AE1-090_GEN
Solar/Wind Harmer
0.345
970349AG2-230 GEN
Solar/Wind Harmer
8.492
270043AE2-236 GEN
Solar/Wind Harmer
3.088
270535AF1-215 GEN1
Solar/Wind Harmer
2.437
942871AE2-306 GEN
Solar/Wind Harmer
0.48
270391AF1-285 GEN3
Solar/Wind Harmer
0.246
972231SS25-0005
Solar/Wind Harmer
5.018
972181SS23-001
Solar/Wind Harmer
3.136
274752CRETE EC ;2U
Adder
2.584
274753CRETE EC ;3U
Adder
2.584
964401AG1-302 GEN
Solar/Wind Harmer
4.779
274724RIVER EC ;11
Adder
9.288
959141AF2-205 GEN
Solar/Wind Harmer
3.132
274802UNIV PARK;5U
Adder
3.011
274826FISK ;BP
Adder
5.644
274800UNIV PARK;3U
Adder
3.001
972038AH1-567 GEN2
Adder
0.188
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.498
970941AG2-585 GEN
Solar/Wind Harmer
6.424
274772LINCOLN ;3U
Adder
3.184
972228AH1-698 GEN2
Adder
1.898
274676JOLIET 29;8U
Adder
15.079
276897AD1-100 C
Solar/Wind Harmer
14.775
939351AE1-166 GEN
Solar/Wind Harmer
3.019
276893AG1-478 C
Solar/Wind Harmer
0.213
274729ELWOOD EC;1P
Adder
8.363
274730ELWOOD EC;6P
Adder
8.363
274734ELWOOD EC;8P
Adder
8.363
274736ELWOOD EC;9P
Adder
8.363
970707AG2-453 GEN
Solar/Wind Harmer
14.243
970513AG2-328 GEN
Solar/Wind Harmer
9.047
970517AG2-330 GEN
Solar/Wind Harmer
8.206
943121AE2-341 GEN
Solar/Wind Harmer
7.543
943591AF1-030 GEN
Solar/Wind Harmer
5.029
276694AA1-018 GEN2
Solar/Wind Harmer
3.173
274682WAUKEGAN ;7U
Adder
8.98
972236AH1-702 GEN2
Adder
1.07
274760LEE CO EC;1U
Adder
4.495
274767LEE CO EC;8U
Adder
4.442
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.342
959441AF2-235 GEN
Solar/Wind Helper
0.155
254305AE2-115 C
Solar/Wind Helper
0.119
20334926Z1-069 C
Solar/Wind Helper
0.677
972211AH1-690 GEN
50/50
441.807
23888502TROY G1
50/50
1.502
23888602TROY G2
50/50
1.502
970817AG2-515 GEN
Solar/Wind Harmer
14.047
945411AF1-206 GEN
Solar/Wind Harmer
8.225
945641AF1-229 GEN
Solar/Wind Harmer
3.751
270499AE1-146 GEN
Solar/Wind Harmer
2.271
971549AH1-272 GEN
Solar/Wind Harmer
14.989
270297AD1-101 GEN
Solar/Wind Harmer
1.998
944161AF1-084 GEN
Solar/Wind Harmer
1.473
957201AF2-014 GEN
Solar/Wind Harmer
2.92
270435AC2-044 GEN
Solar/Wind Harmer
1.288
247607V1-011 GEN
Solar/Wind Harmer
2.525
971771AH1-392 GEN
Solar/Wind Harmer
5.464
965041AG1-368 GEN
Solar/Wind Harmer
6.053
965051AG1-369 GEN
Solar/Wind Harmer
3.001
966831AG1-554 GEN
Solar/Wind Harmer
0.715
971989AH1-539 GEN
Solar/Wind Harmer
7.733
971769AH1-391 GEN
Solar/Wind Harmer
5.922
270302AB2-170 GEN
Solar/Wind Harmer
4.775
270317AD1-130_GEN
Solar/Wind Harmer
1.83
960681AF2-359 GEN
Solar/Wind Harmer
2.151
971347AH1-153 GEN
Solar/Wind Harmer
8.492
963791AG1-232 GEN
Solar/Wind Harmer
7.348
971567AH1-282 GEN
Solar/Wind Harmer
8.122
270536AF1-215 GEN2
Solar/Wind Harmer
2.437
270578AF1-285 GEN2
Solar/Wind Harmer
0.246
274814UNIV PK N;0U
Adder
2.638
274807UNIV PK N;3U
Adder
2.632
274805UNIV PK N;1U
Adder
2.621
274811UNIV PK N;7U
Adder
2.615
270071AF1-092 GEN
Solar/Wind Harmer
7.832
958391AF2-133 GEN
Solar/Wind Harmer
4.734
972037AH1-567 GEN1
Adder
0.095
274827FISK ;RP
Adder
4
960591AF2-350 GEN
Solar/Wind Harmer
5.139
274775LINCOLN ;6U
Adder
3.184
274776LINCOLN ;7U
Adder
3.184
274777LINCOLN ;8U
Adder
3.184
972227AH1-698 GEN1
Adder
1.336
274687WILL CNTY;4U
Adder
14.272
274687WILL CNTY;4U
Adder
14.272
274675JOLIET 29;7U
Adder
15.638
274675JOLIET 29;7U
Adder
15.08
274731ELWOOD EC;2P
Adder
8.363
274733ELWOOD EC;3P
Adder
8.363
274735ELWOOD EC;4P
Adder
8.363
274728ELWOOD EC;5P
Adder
8.363
970833AG2-524 GEN
Solar/Wind Harmer
4.42
970833AG2-524 GEN
Solar/Wind Harmer
2.056
274746AC1-111 G10
Adder
2.812
274744AC1-111 GEN8
Adder
2.812
274823ROCKFORD ;21
Adder
9.526
24729505KEY G4
Adder
3.155
241886AC2-103 GEN2
Solar/Wind Helper
6.897
241982AE2-343 S C
Solar/Wind Helper
0.125
254304AE2-114 C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.261
241997AF1-093 GEN
Solar/Wind Helper
0.138
203804AE2-113_GEN
Solar/Wind Helper
0.91
24190002OREGON_ST1
50/50
5.505
24189802OREGON_CT1
50/50
4.176
23888802TROY G4
50/50
1.502
241996AE2-282_GEN
Solar/Wind Harmer
2.202
971677AH1-339 GEN
Solar/Wind Harmer
6.538
961051AF2-396 GEN
Solar/Wind Harmer
10.337
961051AF2-396 GEN
Solar/Wind Harmer
4.808
246938BC-WTG3
Solar/Wind Harmer
2.563
246937BC-WTG2
Solar/Wind Harmer
2.519
960981AF2-389 GEN
Solar/Wind Harmer
0.966
957891AF2-083 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
3.789
942801AE2-298 GEN
Solar/Wind Harmer
0.957
247620Y3-023
Adder
0.286
270216AD2-079_GEN
Solar/Wind Harmer
0.373
270526AF1-158 GEN
Solar/Wind Harmer
2.704
24441505OLIV SLR
Solar/Wind Harmer
0.079
970611AG2-400 GEN
Solar/Wind Harmer
5.881
965681AG1-436 GEN
Solar/Wind Harmer
7.117
965791AG1-447 GEN
Solar/Wind Harmer
3.641
270224U2-072_GEN2
Solar/Wind Harmer
1.047
270227U2-072_GEN3
Solar/Wind Harmer
1.047
270228U2-072_GEN4
Solar/Wind Harmer
1.047
270231U2-072_GEN5
Solar/Wind Harmer
1.047
274808UNIV PK N;4U
Adder
2.604
274803UNIV PARK;6U
Adder
3.011
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.401
274770LINCOLN ;1U
Adder
3.184
274771LINCOLN ;2U
Adder
3.184
972259AH1-714 GEN
Adder
9.731
274674JOLIET 9 ;6U
Adder
7.833
970321AG2-212 GEN
Solar/Wind Harmer
9.047
274847GR RIDGE ;BU
Solar/Wind Harmer
2.559
958481AF2-142 GEN
Solar/Wind Harmer
7.542
274861TOP CROP ;1U
Solar/Wind Harmer
3.046
274862TOP CROP ;2U
Solar/Wind Harmer
2.544
942221AE2-234 GEN
Solar/Wind Harmer
0.367
274696ROCKY RD ;4P
Adder
5.693
274695ROCKY RD ;2P
Adder
5.562
274693ROCKY RD ;1P
Adder
5.507
274697ROCKY RD ;3P
Adder
1.511
274683WAUKEGAN ;8U
Adder
10.52
274683WAUKEGAN ;8U
Adder
8.868
274764LEE CO EC;5U
Adder
4.506
274765LEE CO EC;6U
Adder
4.506
274762LEE CO EC;3U
Adder
4.495
274763LEE CO EC;4U
Adder
4.453
972267AH1-718 GEN
Adder
1.998
247621Y3-024
Adder
0.11
25326509SID D
Adder
0.587
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.263
203979AG1-198 GEN
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.358
241801AE1-079 GEN
Solar/Wind Helper
0.139
241985AE1-237 GEN
Solar/Wind Helper
0.139
962101AG1-054 GEN
Solar/Wind Helper
0.345
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
971573AH1-285 GEN
Solar/Wind Harmer
0.202
24189902OREGON_CT2
50/50
4.092
23856402BAYSG1
50/50
1.558
23888702TROY G3
50/50
1.502
972253AH1-711 GEN
50/50
45.886
23920202STRYCT
50/50
1.896
241808AF1-120 C
Solar/Wind Harmer
1.228
241858AF1-205_GEN
Solar/Wind Harmer
5.333
241840AF1-064_GEN
Solar/Wind Harmer
1.343
972301AH1-735 GEN
Adder
6.599
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.317
270361_3
Solar/Wind Harmer
8.085
960841AF2-375 GEN
Solar/Wind Harmer
3.588
970515AG2-329 GEN
Solar/Wind Harmer
10.955
944231AF1-091 GEN
Solar/Wind Harmer
2.656
247522W1-056 GEN
Solar/Wind Harmer
1.562
270449AD2-020 GEN
Solar/Wind Harmer
1.841
943021AE2-325 GEN
Solar/Wind Harmer
2.392
246936BC-WTG1
Solar/Wind Harmer
2.519
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
945111AF1-176 GEN
Solar/Wind Harmer
11.446
270505AE1-170 C O1
Solar/Wind Harmer
9.623
965421AG1-410 GEN
Solar/Wind Harmer
19.155
24639705ELKHART HY
Adder
0.095
24695305TIMB G C
Solar/Wind Harmer
3.406
270063AE2-323 C
Solar/Wind Harmer
1.345
247521TR3_G114
Solar/Wind Harmer
2.021
270246TR4_N_V150
Solar/Wind Harmer
0.511
965011AG1-365 GEN
Solar/Wind Harmer
5.881
270462AD2-086
Solar/Wind Harmer
3.972
970373AG2-245 GEN
Solar/Wind Harmer
11.492
270055AF2-134 C O1
Solar/Wind Harmer
1.624
270223U2-072_GEN1
Solar/Wind Harmer
1.047
270578AF1-285 GEN2
Solar/Wind Harmer
0.64
270391AF1-285 GEN3
Solar/Wind Harmer
0.64
274751CRETE EC ;1U
Adder
2.584
274754CRETE EC ;4U
Adder
2.584
958381AF2-132 GEN
Solar/Wind Harmer
4.779
964861AG1-349 GEN
Solar/Wind Harmer
4.133
971917AH1-482 GEN
Solar/Wind Harmer
4.769
274723RIVER EC ;12
Adder
9.4
274812UNIV PK N;8U
Adder
2.615
276164X3-005 C
Solar/Wind Harmer
0.365
274801UNIV PARK;4U
Adder
3.001
276776AD2-060 GEN
Solar/Wind Harmer
0.217
972207SS24-0001
Solar/Wind Harmer
11.322
274773LINCOLN ;4U
Adder
3.184
274774LINCOLN ;5U
Adder
3.184
940581AE2-045 GEN
Solar/Wind Harmer
5.238
971605AH1-302 GEN
Solar/Wind Harmer
4.479
274676JOLIET 29;8U
Adder
15.638
941551AE2-152 GEN
Solar/Wind Harmer
2.309
274732ELWOOD EC;7P
Adder
8.363
274674JOLIET 9 ;6U
Adder
7.833
970245AG2-165 GEN
Solar/Wind Harmer
9.047
274871GR RIDGE ;2U
Solar/Wind Harmer
3.89
274745AC1-111 GEN9
Adder
2.812
276691AA1-018 GEN1
Solar/Wind Harmer
0.234
274682WAUKEGAN ;7U
Adder
8.98
274828WAUKEGAN ;BP
Adder
5.514
274822ROCKFORD ;11
Adder
9.595
972235AH1-702 GEN1
Adder
1.23
274761LEE CO EC;2U
Adder
4.495
274766LEE CO EC;7U
Adder
4.442
241885AC2-103 GEN1
Solar/Wind Helper
6.897
241807AE2-176_GEN
Solar/Wind Helper
1.674
961971AG1-040 GEN
Solar/Wind Helper
0.353
203835AF1-098 GEN
Solar/Wind Helper
1.392
203860AG1-193 C
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.138
254303AC2-168 GEN
Solar/Wind Helper
0.08
203954AE2-126 C
Solar/Wind Helper
0.229
991182J1586 G
External Queue
28.11846351623535
991177J1571 G
External Queue
15.792752265930176
990142J1224
External Queue
14.791350364685059
990527J1329
External Queue
2.0234405994415283
LAGNLTFEXP_LAGN->PJM
CLTF
5.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.753
TVALTFEXP_TVA->PJM
CLTF
2.558
NYPJM->LTFIMP_NY
CLTF
2.102
LGEELTFEXP_LGEE->PJM
CLTF
2.253
WECLTFEXP_WEC->PJM
CLTF
1.864
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.66
CBM West 1LTFEXP_CBM-W1->PJM
CBM
109.741
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.094
MECLTFEXP_MEC->PJM
CLTF
7.274
SIGELTFEXP_SIGE->PJM
CLTF
0.188

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-013_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-013_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.99
MW Contribution:445.14
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.688
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
972211AH1-690 GEN
50/50
445.145
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.021
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.953
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.729
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.925
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
991182J1586 G
External Queue
28.164417266845703
991177J1571 G
External Queue
15.818673133850098
990142J1224
External Queue
14.81525993347168
990527J1329
External Queue
2.0267114639282227
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.921
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-014_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.58 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2466.97
MW Contribution:445.15
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
445.147
23888502TROY G1
50/50
1.536
23888602TROY G2
50/50
1.536
970817AG2-515 GEN
Solar/Wind Harmer
14.306
945411AF1-206 GEN
Solar/Wind Harmer
8.348
945641AF1-229 GEN
Solar/Wind Harmer
3.836
270499AE1-146 GEN
Solar/Wind Harmer
2.323
971549AH1-272 GEN
Solar/Wind Harmer
15.402
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.521
957201AF2-014 GEN
Solar/Wind Harmer
3.02
270435AC2-044 GEN
Solar/Wind Harmer
1.332
247607V1-011 GEN
Solar/Wind Harmer
2.612
971771AH1-392 GEN
Solar/Wind Harmer
5.663
965041AG1-368 GEN
Solar/Wind Harmer
6.272
965051AG1-369 GEN
Solar/Wind Harmer
3.11
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.012
971769AH1-391 GEN
Solar/Wind Harmer
6.143
270302AB2-170 GEN
Solar/Wind Harmer
4.96
270317AD1-130_GEN
Solar/Wind Harmer
1.901
960681AF2-359 GEN
Solar/Wind Harmer
2.234
971347AH1-153 GEN
Solar/Wind Harmer
8.822
963791AG1-232 GEN
Solar/Wind Harmer
7.644
971567AH1-282 GEN
Solar/Wind Harmer
8.457
270536AF1-215 GEN2
Solar/Wind Harmer
2.537
270578AF1-285 GEN2
Solar/Wind Harmer
0.257
274814UNIV PK N;0U
Adder
2.749
274807UNIV PK N;3U
Adder
2.743
274805UNIV PK N;1U
Adder
2.731
24190002OREGON_ST1
50/50
5.547
24189802OREGON_CT1
50/50
4.208
23888802TROY G4
50/50
1.536
241996AE2-282_GEN
Solar/Wind Harmer
2.235
971677AH1-339 GEN
Solar/Wind Harmer
6.71
961051AF2-396 GEN
Solar/Wind Harmer
10.687
961051AF2-396 GEN
Solar/Wind Harmer
4.971
246938BC-WTG3
Solar/Wind Harmer
2.651
246937BC-WTG2
Solar/Wind Harmer
2.606
960981AF2-389 GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
2.231
270007AE1-245 C
Solar/Wind Harmer
3.918
942801AE2-298 GEN
Solar/Wind Harmer
0.99
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.804
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.101
965681AG1-436 GEN
Solar/Wind Harmer
7.392
965791AG1-447 GEN
Solar/Wind Harmer
3.782
270224U2-072_GEN2
Solar/Wind Harmer
1.091
270227U2-072_GEN3
Solar/Wind Harmer
1.091
270228U2-072_GEN4
Solar/Wind Harmer
1.091
270231U2-072_GEN5
Solar/Wind Harmer
1.091
274808UNIV PK N;4U
Adder
2.713
274803UNIV PARK;6U
Adder
3.139
274888KELLY CRK;1U
Solar/Wind Harmer
3.164
274887GEN-1.85
Solar/Wind Harmer
2.856
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.717
274770LINCOLN ;1U
Adder
3.32
274771LINCOLN ;2U
Adder
3.32
972259AH1-714 GEN
Adder
10.15
274674JOLIET 9 ;6U
Adder
8.171
970321AG2-212 GEN
Solar/Wind Harmer
9.439
274847GR RIDGE ;BU
Solar/Wind Harmer
2.67
958481AF2-142 GEN
Solar/Wind Harmer
7.871
274861TOP CROP ;1U
Solar/Wind Harmer
3.179
274862TOP CROP ;2U
Solar/Wind Harmer
2.655
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.943
274695ROCKY RD ;2P
Adder
5.806
274693ROCKY RD ;1P
Adder
5.749
274697ROCKY RD ;3P
Adder
1.577
274683WAUKEGAN ;8U
Adder
10.982
274683WAUKEGAN ;8U
Adder
9.257
274764LEE CO EC;5U
Adder
4.71
274765LEE CO EC;6U
Adder
4.71
274762LEE CO EC;3U
Adder
4.699
274763LEE CO EC;4U
Adder
4.655
972267AH1-718 GEN
Adder
2.09
247621Y3-024
Adder
0.116
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.199
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.134
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
971573AH1-285 GEN
Solar/Wind Harmer
0.21
23929302BS-PKR
50/50
2.766
241832AE2-181_GEN
Solar/Wind Harmer
1.995
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.342
270541AE2-072 C
Solar/Wind Harmer
4.431
270575GUS2 35KV
Solar/Wind Harmer
9.732
970217AG2-149 GEN
Solar/Wind Harmer
24.885
247604X1-042
Adder
0.304
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.785
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.934
274811UNIV PK N;7U
Adder
2.725
270071AF1-092 GEN
Solar/Wind Harmer
8.161
958391AF2-133 GEN
Solar/Wind Harmer
4.933
972037AH1-567 GEN1
Adder
0.099
274827FISK ;RP
Adder
4.17
960591AF2-350 GEN
Solar/Wind Harmer
5.359
274775LINCOLN ;6U
Adder
3.32
274776LINCOLN ;7U
Adder
3.32
274777LINCOLN ;8U
Adder
3.32
972227AH1-698 GEN1
Adder
1.394
274687WILL CNTY;4U
Adder
14.885
274687WILL CNTY;4U
Adder
14.885
274675JOLIET 29;7U
Adder
16.311
274675JOLIET 29;7U
Adder
15.729
274731ELWOOD EC;2P
Adder
8.724
274733ELWOOD EC;3P
Adder
8.724
274735ELWOOD EC;4P
Adder
8.724
274728ELWOOD EC;5P
Adder
8.724
970833AG2-524 GEN
Solar/Wind Harmer
4.611
970833AG2-524 GEN
Solar/Wind Harmer
2.145
274746AC1-111 G10
Adder
2.935
274744AC1-111 GEN8
Adder
2.935
274823ROCKFORD ;21
Adder
9.952
24729505KEY G4
Adder
3.297
241886AC2-103 GEN2
Solar/Wind Helper
6.853
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.87
270491AE1-102 GEN2
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
3.753
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.25
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.979
270191TR4_S_V150
Solar/Wind Harmer
1.869
270247TR4_N_V136
Solar/Wind Harmer
0.53
959331AF2-224 GEN
Solar/Wind Harmer
6.101
965021AG1-366 GEN
Solar/Wind Harmer
1.419
270485AE1-090_GEN
Solar/Wind Harmer
0.359
970349AG2-230 GEN
Solar/Wind Harmer
8.822
270043AE2-236 GEN
Solar/Wind Harmer
3.209
270535AF1-215 GEN1
Solar/Wind Harmer
2.537
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.257
972231SS25-0005
Solar/Wind Harmer
5.226
972181SS23-001
Solar/Wind Harmer
3.267
274752CRETE EC ;2U
Adder
2.692
274753CRETE EC ;3U
Adder
2.692
964401AG1-302 GEN
Solar/Wind Harmer
4.978
274724RIVER EC ;11
Adder
9.677
959141AF2-205 GEN
Solar/Wind Harmer
3.265
274802UNIV PARK;5U
Adder
3.139
274826FISK ;BP
Adder
5.884
274800UNIV PARK;3U
Adder
3.129
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.494
276806AD2-047 C O1
Solar/Wind Harmer
5.733
970941AG2-585 GEN
Solar/Wind Harmer
6.698
274772LINCOLN ;3U
Adder
3.32
972228AH1-698 GEN2
Adder
1.979
274676JOLIET 29;8U
Adder
15.728
276897AD1-100 C
Solar/Wind Harmer
15.411
939351AE1-166 GEN
Solar/Wind Harmer
3.149
276893AG1-478 C
Solar/Wind Harmer
0.222
274729ELWOOD EC;1P
Adder
8.724
274730ELWOOD EC;6P
Adder
8.724
274734ELWOOD EC;8P
Adder
8.724
274736ELWOOD EC;9P
Adder
8.724
970707AG2-453 GEN
Solar/Wind Harmer
14.858
970513AG2-328 GEN
Solar/Wind Harmer
9.439
970517AG2-330 GEN
Solar/Wind Harmer
8.561
943121AE2-341 GEN
Solar/Wind Harmer
7.872
943591AF1-030 GEN
Solar/Wind Harmer
5.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.311
274682WAUKEGAN ;7U
Adder
9.374
972236AH1-702 GEN2
Adder
1.118
274760LEE CO EC;1U
Adder
4.699
274767LEE CO EC;8U
Adder
4.644
24728705AND G3
Adder
3.481
24728505AND G1
Adder
1.664
962511AG1-100 GEN
Solar/Wind Helper
0.351
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
24189902OREGON_CT2
50/50
4.123
23856402BAYSG1
50/50
1.571
23888702TROY G3
50/50
1.536
972253AH1-711 GEN
50/50
46.923
23920202STRYCT
50/50
1.926
241808AF1-120 C
Solar/Wind Harmer
1.246
241858AF1-205_GEN
Solar/Wind Harmer
5.409
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.723
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.342
270361_3
Solar/Wind Harmer
8.261
960841AF2-375 GEN
Solar/Wind Harmer
3.668
970515AG2-329 GEN
Solar/Wind Harmer
11.285
944231AF1-091 GEN
Solar/Wind Harmer
2.737
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.903
943021AE2-325 GEN
Solar/Wind Harmer
2.473
246936BC-WTG1
Solar/Wind Harmer
2.606
270489AE1-102 GEN1
Solar/Wind Harmer
0.866
945111AF1-176 GEN
Solar/Wind Harmer
11.84
270505AE1-170 C O1
Solar/Wind Harmer
9.954
965421AG1-410 GEN
Solar/Wind Harmer
19.819
24639705ELKHART HY
Adder
0.099
24695305TIMB G C
Solar/Wind Harmer
3.527
270063AE2-323 C
Solar/Wind Harmer
1.394
247521TR3_G114
Solar/Wind Harmer
2.094
270246TR4_N_V150
Solar/Wind Harmer
0.53
965011AG1-365 GEN
Solar/Wind Harmer
6.101
270462AD2-086
Solar/Wind Harmer
4.126
970373AG2-245 GEN
Solar/Wind Harmer
11.954
270055AF2-134 C O1
Solar/Wind Harmer
1.691
270223U2-072_GEN1
Solar/Wind Harmer
1.091
270578AF1-285 GEN2
Solar/Wind Harmer
0.667
270391AF1-285 GEN3
Solar/Wind Harmer
0.667
274751CRETE EC ;1U
Adder
2.692
274754CRETE EC ;4U
Adder
2.692
958381AF2-132 GEN
Solar/Wind Harmer
4.978
964861AG1-349 GEN
Solar/Wind Harmer
4.305
971917AH1-482 GEN
Solar/Wind Harmer
4.968
274723RIVER EC ;12
Adder
9.794
274812UNIV PK N;8U
Adder
2.725
276164X3-005 C
Solar/Wind Harmer
0.381
274801UNIV PARK;4U
Adder
3.129
276776AD2-060 GEN
Solar/Wind Harmer
0.227
972207SS24-0001
Solar/Wind Harmer
11.806
274773LINCOLN ;4U
Adder
3.32
274774LINCOLN ;5U
Adder
3.32
940581AE2-045 GEN
Solar/Wind Harmer
5.461
971605AH1-302 GEN
Solar/Wind Harmer
4.67
274676JOLIET 29;8U
Adder
16.311
941551AE2-152 GEN
Solar/Wind Harmer
2.408
274732ELWOOD EC;7P
Adder
8.724
274674JOLIET 9 ;6U
Adder
8.171
970245AG2-165 GEN
Solar/Wind Harmer
9.439
274871GR RIDGE ;2U
Solar/Wind Harmer
4.059
274745AC1-111 GEN9
Adder
2.935
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.374
274828WAUKEGAN ;BP
Adder
5.756
274822ROCKFORD ;11
Adder
10.025
972235AH1-702 GEN1
Adder
1.285
274761LEE CO EC;2U
Adder
4.699
274766LEE CO EC;7U
Adder
4.644
24728605AND G2
Adder
1.664
241885AC2-103 GEN1
Solar/Wind Helper
6.853
241807AE2-176_GEN
Solar/Wind Helper
1.649
961971AG1-040 GEN
Solar/Wind Helper
0.343
203835AF1-098 GEN
Solar/Wind Helper
1.35
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
991182J1586 G
External Queue
28.164098739624023
991177J1571 G
External Queue
15.818490982055664
990142J1224
External Queue
14.815095901489258
990527J1329
External Queue
2.026688814163208
LAGNLTFEXP_LAGN->PJM
CLTF
6.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.404
TVALTFEXP_TVA->PJM
CLTF
2.778
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
2.403
WECLTFEXP_WEC->PJM
CLTF
1.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
0.732
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.92
MECLTFEXP_MEC->PJM
CLTF
7.642
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-009_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2463.99
MW Contribution:445.37
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
1.996
958321AF2-126 GEN
Solar/Wind Harmer
1.466
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
4.433
270575GUS2 35KV
Solar/Wind Harmer
9.743
970217AG2-149 GEN
Solar/Wind Harmer
24.838
247604X1-042
Adder
0.303
270044AE2-322 C
Solar/Wind Harmer
0.942
270404AC1-167 GEN
Solar/Wind Harmer
0.784
24441205WTRV SLR C
Solar/Wind Harmer
0.096
270258AD1-119 GEN
Solar/Wind Harmer
1.933
270491AE1-102 GEN2
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
3.748
958091AF2-103 GEN
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
7.246
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0.044
970031AG2-029 GEN
Solar/Wind Harmer
18.957
270191TR4_S_V150
Solar/Wind Harmer
1.867
270247TR4_N_V136
Solar/Wind Harmer
0.529
959331AF2-224 GEN
Solar/Wind Harmer
6.095
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.358
970349AG2-230 GEN
Solar/Wind Harmer
8.811
270043AE2-236 GEN
Solar/Wind Harmer
3.205
270535AF1-215 GEN1
Solar/Wind Harmer
2.534
942871AE2-306 GEN
Solar/Wind Harmer
0.5
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
972231SS25-0005
Solar/Wind Harmer
5.22
972181SS23-001
Solar/Wind Harmer
3.263
274752CRETE EC ;2U
Adder
2.689
274753CRETE EC ;3U
Adder
2.689
964401AG1-302 GEN
Solar/Wind Harmer
4.972
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
3.261
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276772AC2-154 GEN
Solar/Wind Harmer
1.493
276806AD2-047 C O1
Solar/Wind Harmer
5.726
970941AG2-585 GEN
Solar/Wind Harmer
6.69
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
2.237
971677AH1-339 GEN
Solar/Wind Harmer
6.708
961051AF2-396 GEN
Solar/Wind Harmer
10.675
961051AF2-396 GEN
Solar/Wind Harmer
4.965
246938BC-WTG3
Solar/Wind Harmer
2.648
246937BC-WTG2
Solar/Wind Harmer
2.603
960981AF2-389 GEN
Solar/Wind Harmer
0.999
957891AF2-083 GEN
Solar/Wind Harmer
2.228
270007AE1-245 C
Solar/Wind Harmer
3.915
942801AE2-298 GEN
Solar/Wind Harmer
0.989
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.386
270526AF1-158 GEN
Solar/Wind Harmer
2.801
24441505OLIV SLR
Solar/Wind Harmer
0.082
970611AG2-400 GEN
Solar/Wind Harmer
6.095
965681AG1-436 GEN
Solar/Wind Harmer
7.384
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
1.089
270227U2-072_GEN3
Solar/Wind Harmer
1.089
270228U2-072_GEN4
Solar/Wind Harmer
1.089
270231U2-072_GEN5
Solar/Wind Harmer
1.089
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
3.16
274887GEN-1.85
Solar/Wind Harmer
2.853
276843GEN-1.7
Solar/Wind Harmer
0.307
958011AF2-095 GEN
Solar/Wind Harmer
7.707
274770LINCOLN ;1U
Adder
3.317
274771LINCOLN ;2U
Adder
3.317
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
9.428
274847GR RIDGE ;BU
Solar/Wind Harmer
2.667
958481AF2-142 GEN
Solar/Wind Harmer
7.862
274861TOP CROP ;1U
Solar/Wind Harmer
3.176
274862TOP CROP ;2U
Solar/Wind Harmer
2.652
942221AE2-234 GEN
Solar/Wind Harmer
0.383
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
972267AH1-718 GEN
Adder
2.087
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.615
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
971573AH1-285 GEN
Solar/Wind Harmer
0.21
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
1.247
241858AF1-205_GEN
Solar/Wind Harmer
5.419
241840AF1-064_GEN
Solar/Wind Harmer
1.367
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
8.271
960841AF2-375 GEN
Solar/Wind Harmer
3.672
970515AG2-329 GEN
Solar/Wind Harmer
11.264
944231AF1-091 GEN
Solar/Wind Harmer
2.736
247522W1-056 GEN
Solar/Wind Harmer
1.61
270449AD2-020 GEN
Solar/Wind Harmer
1.901
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
2.603
270489AE1-102 GEN1
Solar/Wind Harmer
0.865
945111AF1-176 GEN
Solar/Wind Harmer
11.826
270505AE1-170 C O1
Solar/Wind Harmer
9.942
965421AG1-410 GEN
Solar/Wind Harmer
19.794
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
3.523
270063AE2-323 C
Solar/Wind Harmer
1.392
247521TR3_G114
Solar/Wind Harmer
2.092
270246TR4_N_V150
Solar/Wind Harmer
0.529
965011AG1-365 GEN
Solar/Wind Harmer
6.095
270462AD2-086
Solar/Wind Harmer
4.12
970373AG2-245 GEN
Solar/Wind Harmer
11.94
270055AF2-134 C O1
Solar/Wind Harmer
1.689
270223U2-072_GEN1
Solar/Wind Harmer
1.089
270578AF1-285 GEN2
Solar/Wind Harmer
0.666
270391AF1-285 GEN3
Solar/Wind Harmer
0.666
274751CRETE EC ;1U
Adder
2.689
274754CRETE EC ;4U
Adder
2.689
958381AF2-132 GEN
Solar/Wind Harmer
4.972
964861AG1-349 GEN
Solar/Wind Harmer
4.3
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0.38
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.226
972207SS24-0001
Solar/Wind Harmer
11.792
274773LINCOLN ;4U
Adder
3.317
274774LINCOLN ;5U
Adder
3.317
940581AE2-045 GEN
Solar/Wind Harmer
5.455
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
2.406
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
9.428
274871GR RIDGE ;2U
Solar/Wind Harmer
4.054
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24728605AND G2
Adder
1.662
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
14.26
945411AF1-206 GEN
Solar/Wind Harmer
8.353
945641AF1-229 GEN
Solar/Wind Harmer
3.828
270499AE1-146 GEN
Solar/Wind Harmer
2.325
971549AH1-272 GEN
Solar/Wind Harmer
15.383
270297AD1-101 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
1.52
957201AF2-014 GEN
Solar/Wind Harmer
3.017
270435AC2-044 GEN
Solar/Wind Harmer
1.33
247607V1-011 GEN
Solar/Wind Harmer
2.61
971771AH1-392 GEN
Solar/Wind Harmer
5.656
965041AG1-368 GEN
Solar/Wind Harmer
6.266
965051AG1-369 GEN
Solar/Wind Harmer
3.107
966831AG1-554 GEN
Solar/Wind Harmer
0.741
971989AH1-539 GEN
Solar/Wind Harmer
8.008
971769AH1-391 GEN
Solar/Wind Harmer
6.135
270302AB2-170 GEN
Solar/Wind Harmer
4.953
270317AD1-130_GEN
Solar/Wind Harmer
1.899
960681AF2-359 GEN
Solar/Wind Harmer
2.232
971347AH1-153 GEN
Solar/Wind Harmer
8.811
963791AG1-232 GEN
Solar/Wind Harmer
7.636
971567AH1-282 GEN
Solar/Wind Harmer
8.442
270536AF1-215 GEN2
Solar/Wind Harmer
2.534
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
8.152
958391AF2-133 GEN
Solar/Wind Harmer
4.927
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
5.352
274775LINCOLN ;6U
Adder
3.317
274776LINCOLN ;7U
Adder
3.317
274777LINCOLN ;8U
Adder
3.317
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.606
970833AG2-524 GEN
Solar/Wind Harmer
2.142
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
274823ROCKFORD ;21
Adder
9.941
24729505KEY G4
Adder
3.294
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
274772LINCOLN ;3U
Adder
3.317
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
15.393
939351AE1-166 GEN
Solar/Wind Harmer
3.145
276893AG1-478 C
Solar/Wind Harmer
0.221
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
14.84
970513AG2-328 GEN
Solar/Wind Harmer
9.428
970517AG2-330 GEN
Solar/Wind Harmer
8.551
943121AE2-341 GEN
Solar/Wind Harmer
7.863
943591AF1-030 GEN
Solar/Wind Harmer
5.242
276694AA1-018 GEN2
Solar/Wind Harmer
3.307
274682WAUKEGAN ;7U
Adder
9.363
972236AH1-702 GEN2
Adder
1.116
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24728705AND G3
Adder
3.477
24728505AND G1
Adder
1.662
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
991182J1586 G
External Queue
28.11846351623535
991177J1571 G
External Queue
15.792752265930176
990142J1224
External Queue
14.791350364685059
990527J1329
External Queue
2.0234405994415283
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:445.37
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
270223U2-072_GEN1
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
991182J1586 G
External Queue
28.11846351623535
991177J1571 G
External Queue
15.792752265930176
990142J1224
External Queue
14.791350364685059
990527J1329
External Queue
2.0234405994415283
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 02BEAVER-02CARLIL 345.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.31 %
Rating:1745.0 MVA
Rating Type:B
MVA to Mitigate:1907.45
MW Contribution:238.13
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
10.407
972211AH1-690 GEN
50/50
238.133
241886AC2-103 GEN2
Solar/Wind Harmer
14.419
24191202EL_AA1-006
Adder
0.297
970817AG2-515 GEN
Solar/Wind Harmer
13.044
945411AF1-206 GEN
Solar/Wind Harmer
7.213
270499AE1-146 GEN
Solar/Wind Harmer
2.343
945641AF1-229 GEN
Solar/Wind Harmer
3.229
970159AG2-109 GEN
Solar/Wind Harmer
3.418
270297AD1-101 GEN
Solar/Wind Harmer
1.75
971549AH1-272 GEN
Solar/Wind Harmer
11.155
966831AG1-554 GEN
Solar/Wind Harmer
0.704
971989AH1-539 GEN
Solar/Wind Harmer
7.613
971567AH1-282 GEN
Solar/Wind Harmer
8.024
247607V1-011 GEN
Solar/Wind Harmer
2.098
957201AF2-014 GEN
Solar/Wind Harmer
2.368
270435AC2-044 GEN
Solar/Wind Harmer
1.044
944161AF1-084 GEN
Solar/Wind Harmer
1.106
965041AG1-368 GEN
Solar/Wind Harmer
4.881
965051AG1-369 GEN
Solar/Wind Harmer
2.43
270302AB2-170 GEN
Solar/Wind Harmer
3.966
270317AD1-130_GEN
Solar/Wind Harmer
1.52
971219AH1-069 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
4.129
971769AH1-391 GEN
Solar/Wind Harmer
4.471
270578AF1-285 GEN2
Solar/Wind Harmer
0.204
970179AG2-119 GEN
Solar/Wind Harmer
3.495
963791AG1-232 GEN
Solar/Wind Harmer
5.807
960681AF2-359 GEN
Solar/Wind Harmer
1.625
241982AE2-343 S C
Solar/Wind Helper
0.109
254304AE2-114 C
Solar/Wind Helper
0.104
241997AF1-093 GEN
Solar/Wind Helper
0.121
23917202WLORG-3
50/50
1.553
23917302WLORG-4
50/50
1.519
966311AG1-500 GEN
50/50
141.29
23857202WLORG-B
50/50
9.372
24190002OREGON_ST1
50/50
2.971
24189802OREGON_CT1
50/50
2.254
241996AE2-282_GEN
Solar/Wind Harmer
1.931
971677AH1-339 GEN
Solar/Wind Harmer
6.773
270007AE1-245 C
Solar/Wind Harmer
3.147
942801AE2-298 GEN
Solar/Wind Harmer
0.797
246938BC-WTG3
Solar/Wind Harmer
2.078
246937BC-WTG2
Solar/Wind Harmer
2.043
971231AH1-075 GEN
Solar/Wind Harmer
0.399
961051AF2-396 GEN
Solar/Wind Harmer
7.783
961051AF2-396 GEN
Solar/Wind Harmer
3.62
960981AF2-389 GEN
Solar/Wind Harmer
0.728
957891AF2-083 GEN
Solar/Wind Harmer
1.625
247620Y3-023
Adder
0.218
270216AD2-079_GEN
Solar/Wind Harmer
0.283
970611AG2-400 GEN
Solar/Wind Harmer
4.645
971201AH1-060 GEN
Solar/Wind Harmer
0.917
270526AF1-158 GEN
Solar/Wind Harmer
2.042
24441505OLIV SLR
Solar/Wind Harmer
0.06
270224U2-072_GEN2
Solar/Wind Harmer
0.868
270227U2-072_GEN3
Solar/Wind Harmer
0.868
270228U2-072_GEN4
Solar/Wind Harmer
0.868
270231U2-072_GEN5
Solar/Wind Harmer
0.868
241960AC2-195 GEN
Solar/Wind Harmer
1.215
965681AG1-436 GEN
Solar/Wind Harmer
5.376
965791AG1-447 GEN
Solar/Wind Harmer
2.75
203947AF1-006 C
Solar/Wind Helper
0.283
241967AE2-285_GEN
Solar/Wind Helper
0.314
241801AE1-079 GEN
Solar/Wind Helper
0.122
203980AG1-197 GEN
Solar/Wind Helper
0.188
241985AE1-237 GEN
Solar/Wind Helper
0.122
203979AG1-198 GEN
Solar/Wind Helper
0.147
962101AG1-054 GEN
Solar/Wind Helper
0.304
957071AF2-004 GEN
50/50
12.095
23917502WLORG-6
50/50
0.764
23857102WLORG-A
50/50
9.096
23917402WLORG-5
50/50
1.527
23917102WLORG-2
50/50
1.505
23929302BS-PKR
50/50
2.106
241832AE2-181_GEN
Solar/Wind Harmer
1.75
958321AF2-126 GEN
Solar/Wind Harmer
1.366
23906502RICHG2&3
Adder
1.187
270575GUS2 35KV
Solar/Wind Harmer
10.039
270541AE2-072 C
Solar/Wind Harmer
3.99
970217AG2-149 GEN
Solar/Wind Harmer
22.552
270588AE1-091_GEN
Solar/Wind Harmer
6.591
270044AE2-322 C
Solar/Wind Harmer
0.769
270404AC1-167 GEN
Solar/Wind Harmer
0.641
270258AD1-119 GEN
Solar/Wind Harmer
1.565
961961AG1-039 GEN
Solar/Wind Harmer
1.583
958091AF2-103 GEN
Solar/Wind Harmer
0.086
247604X1-042
Adder
0.22
270491AE1-102 GEN2
Solar/Wind Harmer
0.679
24441205WTRV SLR C
Solar/Wind Harmer
0.07
270377AD1-106 GEN
Solar/Wind Harmer
3.082
270191TR4_S_V150
Solar/Wind Harmer
1.46
270247TR4_N_V136
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
2.737
270485AE1-090_GEN
Solar/Wind Harmer
0.287
24642205MAYFLWER
Adder
0.299
970031AG2-029 GEN
Solar/Wind Harmer
14.083
247643Z2-116 C
Solar/Wind Harmer
0.032
959331AF2-224 GEN
Solar/Wind Harmer
4.645
965021AG1-366 GEN
Solar/Wind Harmer
1.08
970065AG2-057 GEN
Solar/Wind Harmer
0.459
942871AE2-306 GEN
Solar/Wind Harmer
0.398
270391AF1-285 GEN3
Solar/Wind Harmer
0.204
270043AE2-236 GEN
Solar/Wind Harmer
2.394
962511AG1-100 GEN
Solar/Wind Helper
0.255
203830AF1-094 GEN
Solar/Wind Helper
0.245
254305AE2-115 C
Solar/Wind Helper
0.104
959441AF2-235 GEN
Solar/Wind Helper
0.115
966321AG1-501 GEN
50/50
1.834
957111AF2-005 GEN
50/50
1.467
24189902OREGON_CT2
50/50
2.208
23856402BAYSG1
50/50
1.196
241885AC2-103 GEN1
Solar/Wind Harmer
14.419
241807AE2-176_GEN
Solar/Wind Harmer
6.057
972253AH1-711 GEN
Adder
43.699
241858AF1-205_GEN
Solar/Wind Harmer
4.928
241808AF1-120 C
Solar/Wind Harmer
1.077
23920202STRYCT
Adder
1.608
241840AF1-064_GEN
Solar/Wind Harmer
1.274
972301AH1-735 GEN
Adder
5.944
23906402RICHG1
Adder
1.189
23906502RICHG2&3
Adder
1.187
270361_3
Solar/Wind Harmer
8.521
960841AF2-375 GEN
Solar/Wind Harmer
3.749
270428AC2-015 C
Solar/Wind Harmer
4.415
247522W1-056 GEN
Solar/Wind Harmer
1.589
970515AG2-329 GEN
Solar/Wind Harmer
10.227
970905AG2-564 GEN
Solar/Wind Harmer
3.497
944231AF1-091 GEN
Solar/Wind Harmer
2.19
241847AF2-150_GEN
Solar/Wind Harmer
2.294
246936BC-WTG1
Solar/Wind Harmer
2.043
270489AE1-102 GEN1
Solar/Wind Harmer
0.679
965421AG1-410 GEN
Solar/Wind Harmer
15.499
24695305TIMB G C
Solar/Wind Harmer
2.781
270449AD2-020 GEN
Solar/Wind Harmer
1.385
943021AE2-325 GEN
Solar/Wind Harmer
1.799
247521TR3_G114
Solar/Wind Harmer
1.636
270246TR4_N_V150
Solar/Wind Harmer
0.414
945111AF1-176 GEN
Solar/Wind Harmer
8.634
270505AE1-170 C O1
Solar/Wind Harmer
7.249
270462AD2-086
Solar/Wind Harmer
3.299
24639705ELKHART HY
Adder
0.072
270063AE2-323 C
Solar/Wind Harmer
1.038
971221AH1-070 GEN
Solar/Wind Harmer
0.796
965011AG1-365 GEN
Solar/Wind Harmer
4.645
241813AF1-122_GEN
Solar/Wind Harmer
2.935
270223U2-072_GEN1
Solar/Wind Harmer
0.868
270578AF1-285 GEN2
Solar/Wind Harmer
0.531
270391AF1-285 GEN3
Solar/Wind Harmer
0.531
961971AG1-040 GEN
Solar/Wind Helper
0.251
203835AF1-098 GEN
Solar/Wind Helper
0.992
241966AE1-183 GEN
Solar/Wind Helper
0.121
203860AG1-193 C
Solar/Wind Helper
0.116
254303AC2-168 GEN
Solar/Wind Helper
0.071
991177J1571 G
External Queue
13.065269470214844
990142J1224
External Queue
11.235392570495605
990527J1329
External Queue
1.536989450454712
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.536
TVALTFEXP_TVA->PJM
CLTF
1.857
NYPJM->LTFIMP_NY
CLTF
1.797
LGEELTFEXP_LGEE->PJM
CLTF
1.709
WECLTFEXP_WEC->PJM
CLTF
1.408
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136
CPLELTFEXP_CPLE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.236
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.4
MECLTFEXP_MEC->PJM
CLTF
5.472
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 02BEAVER-02JONSON 138.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02JONSON 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.44 %
Rating:282.0 MVA
Rating Type:B
MVA to Mitigate:345.29
MW Contribution:41.55
Bus #Bus NameTypeMW Contribution
966321AG1-501 GEN
50/50
1.316
957111AF2-005 GEN
50/50
1.052
23917502WLORG-6
50/50
0.548
23857102WLORG-A
50/50
6.525
957071AF2-004 GEN
Adder
1.611
972211AH1-690 GEN
Adder
41.548
23857202WLORG-B
50/50
6.723
966311AG1-500 GEN
Adder
18.821
LAGNLTFEXP_LAGN->PJM
CLTF
0.965
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.445
NYPJM->LTFIMP_NY
CLTF
0.459
LGEELTFEXP_LGEE->PJM
CLTF
0.4
WECLTFEXP_WEC->PJM
CLTF
0.305
CPLELTFEXP_CPLE->PJM
CLTF
0.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.61
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.158
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.765
MECLTFEXP_MEC->PJM
CLTF
1.204
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-901_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-901_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1956.7
MW Contribution:209.15
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.356
23917102WLORG-2
50/50
1.337
24189902OREGON_CT2
50/50
1.94
23856402BAYSG1
50/50
1.043
241885AC2-103 GEN1
Solar/Wind Harmer
12.757
241807AE2-176_GEN
Solar/Wind Harmer
5.062
23917202WLORG-3
50/50
1.38
23917302WLORG-4
50/50
1.349
966311AG1-500 GEN
50/50
125.486
24190002OREGON_ST1
50/50
2.61
24189802OREGON_CT1
50/50
1.98
241996AE2-282_GEN
Solar/Wind Harmer
1.697
23857202WLORG-B
Adder
4.429
971677AH1-339 GEN
Solar/Wind Harmer
5.947
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.905
246937BC-WTG2
Solar/Wind Harmer
1.873
961051AF2-396 GEN
Solar/Wind Harmer
7.181
961051AF2-396 GEN
Solar/Wind Harmer
3.34
971231AH1-075 GEN
Solar/Wind Harmer
0.362
960981AF2-389 GEN
Solar/Wind Harmer
0.673
957891AF2-083 GEN
Solar/Wind Harmer
1.501
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.262
970611AG2-400 GEN
Solar/Wind Harmer
4.301
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.296
203979AG1-198 GEN
Solar/Wind Helper
0.229
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.295
23867002DVBSG1
50/50
9.149
972211AH1-690 GEN
50/50
209.151
241886AC2-103 GEN2
Solar/Wind Harmer
12.757
970817AG2-515 GEN
Solar/Wind Harmer
11.458
24191202EL_AA1-006
Adder
0.247
945411AF1-206 GEN
Solar/Wind Harmer
6.338
270499AE1-146 GEN
Solar/Wind Harmer
2.056
945641AF1-229 GEN
Solar/Wind Harmer
2.848
970159AG2-109 GEN
Solar/Wind Harmer
2.554
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.147
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.852
247607V1-011 GEN
Solar/Wind Harmer
1.919
971567AH1-282 GEN
Solar/Wind Harmer
7.189
957201AF2-014 GEN
Solar/Wind Harmer
2.171
270435AC2-044 GEN
Solar/Wind Harmer
0.957
944161AF1-084 GEN
Solar/Wind Harmer
1.019
965041AG1-368 GEN
Solar/Wind Harmer
4.498
957071AF2-004 GEN
50/50
10.742
23929302BS-PKR
50/50
1.836
241832AE2-181_GEN
Solar/Wind Harmer
1.539
958321AF2-126 GEN
Solar/Wind Harmer
1.2
23906502RICHG2&3
Adder
1.05
270575GUS2 35KV
Solar/Wind Harmer
8.781
23857102WLORG-A
Adder
4.299
270541AE2-072 C
Solar/Wind Harmer
3.537
970217AG2-149 GEN
Solar/Wind Harmer
19.929
270588AE1-091_GEN
Solar/Wind Harmer
5.941
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.426
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.202
961961AG1-039 GEN
Solar/Wind Harmer
1.372
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.793
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.527
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.277
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.301
965021AG1-366 GEN
Solar/Wind Harmer
1
962511AG1-100 GEN
Solar/Wind Helper
0.409
203830AF1-094 GEN
Solar/Wind Helper
0.382
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.688
254305AE2-115 C
Solar/Wind Helper
0.102
972253AH1-711 GEN
Adder
38.383
241858AF1-205_GEN
Solar/Wind Harmer
4.326
241808AF1-120 C
Solar/Wind Harmer
0.946
23920202STRYCT
Adder
1.415
241840AF1-064_GEN
Solar/Wind Harmer
1.119
972301AH1-735 GEN
Adder
5.258
23906402RICHG1
Adder
1.052
23906502RICHG2&3
Adder
1.05
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.283
966321AG1-501 GEN
Adder
0.867
957111AF2-005 GEN
Adder
0.693
270428AC2-015 C
Solar/Wind Harmer
3.75
247522W1-056 GEN
Solar/Wind Harmer
1.41
970515AG2-329 GEN
Solar/Wind Harmer
9.037
970905AG2-564 GEN
Solar/Wind Harmer
2.954
944231AF1-091 GEN
Solar/Wind Harmer
1.993
241847AF2-150_GEN
Solar/Wind Harmer
1.989
246936BC-WTG1
Solar/Wind Harmer
1.873
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.219
24695305TIMB G C
Solar/Wind Harmer
2.555
270449AD2-020 GEN
Solar/Wind Harmer
1.277
943021AE2-325 GEN
Solar/Wind Harmer
1.659
247521TR3_G114
Solar/Wind Harmer
1.508
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.974
270505AE1-170 C O1
Solar/Wind Harmer
6.696
270462AD2-086
Solar/Wind Harmer
3.05
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
965011AG1-365 GEN
Solar/Wind Harmer
4.301
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.566
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.23
254303AC2-168 GEN
Solar/Wind Helper
0.068
965051AG1-369 GEN
Solar/Wind Harmer
2.239
270302AB2-170 GEN
Solar/Wind Harmer
3.666
270317AD1-130_GEN
Solar/Wind Harmer
1.405
203846AF2-130 C
Solar/Wind Helper
0.272
203804AE2-113_GEN
Solar/Wind Helper
0.933
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
991177J1571 G
External Queue
11.149422645568848
990142J1224
External Queue
9.595755577087402
990527J1329
External Queue
1.3126888275146484
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.004
TVALTFEXP_TVA->PJM
CLTF
1.884
NYPJM->LTFIMP_NY
CLTF
1.974
LGEELTFEXP_LGEE->PJM
CLTF
1.688
WECLTFEXP_WEC->PJM
CLTF
1.329
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.464
MECLTFEXP_MEC->PJM
CLTF
5.219
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-007A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-007A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.82
MW Contribution:212.09
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.431
23917102WLORG-2
50/50
1.41
24189902OREGON_CT2
50/50
1.967
241885AC2-103 GEN1
Solar/Wind Harmer
13.312
23867002DVBSG1
50/50
9.378
972211AH1-690 GEN
50/50
212.091
241886AC2-103 GEN2
Solar/Wind Harmer
13.312
970817AG2-515 GEN
Solar/Wind Harmer
11.575
945411AF1-206 GEN
Solar/Wind Harmer
6.379
957071AF2-004 GEN
50/50
11.332
23929302BS-PKR
Adder
1.735
241832AE2-181_GEN
Solar/Wind Harmer
1.549
958321AF2-126 GEN
Solar/Wind Harmer
1.204
23906502RICHG2&3
Adder
1.054
270575GUS2 35KV
Solar/Wind Harmer
8.659
270541AE2-072 C
Solar/Wind Harmer
3.532
970217AG2-149 GEN
Solar/Wind Harmer
19.363
270588AE1-091_GEN
Solar/Wind Harmer
5.847
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.581
270258AD1-119 GEN
Solar/Wind Harmer
1.423
247604X1-042
Adder
0.202
958091AF2-103 GEN
Solar/Wind Harmer
0.078
270491AE1-102 GEN2
Solar/Wind Harmer
0.62
24441205WTRV SLR C
Solar/Wind Harmer
0.064
24191202EL_AA1-006
Adder
0.223
270499AE1-146 GEN
Solar/Wind Harmer
2.029
945641AF1-229 GEN
Solar/Wind Harmer
2.819
270297AD1-101 GEN
Solar/Wind Harmer
1.573
971549AH1-272 GEN
Solar/Wind Harmer
10.193
966831AG1-554 GEN
Solar/Wind Harmer
0.62
971989AH1-539 GEN
Solar/Wind Harmer
6.706
247607V1-011 GEN
Solar/Wind Harmer
1.912
957201AF2-014 GEN
Solar/Wind Harmer
2.164
270435AC2-044 GEN
Solar/Wind Harmer
0.954
944161AF1-084 GEN
Solar/Wind Harmer
1.021
971567AH1-282 GEN
Solar/Wind Harmer
6.891
970159AG2-109 GEN
Solar/Wind Harmer
1.835
965041AG1-368 GEN
Solar/Wind Harmer
4.486
965051AG1-369 GEN
Solar/Wind Harmer
2.232
270302AB2-170 GEN
Solar/Wind Harmer
3.641
270317AD1-130_GEN
Solar/Wind Harmer
1.396
203846AF2-130 C
Solar/Wind Helper
0.27
203804AE2-113_GEN
Solar/Wind Helper
0.928
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
241997AF1-093 GEN
Solar/Wind Helper
0.117
241807AE2-176_GEN
Solar/Wind Harmer
4.79
972253AH1-711 GEN
Adder
38.846
241858AF1-205_GEN
Solar/Wind Harmer
4.354
241808AF1-120 C
Solar/Wind Harmer
0.952
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.123
972301AH1-735 GEN
Adder
5.278
23906402RICHG1
Adder
1.056
23906502RICHG2&3
Adder
1.054
270361_3
Solar/Wind Harmer
7.35
960841AF2-375 GEN
Solar/Wind Harmer
3.239
270428AC2-015 C
Solar/Wind Harmer
3.47
247522W1-056 GEN
Solar/Wind Harmer
1.38
970515AG2-329 GEN
Solar/Wind Harmer
8.781
970905AG2-564 GEN
Solar/Wind Harmer
2.663
944231AF1-091 GEN
Solar/Wind Harmer
1.994
246936BC-WTG1
Solar/Wind Harmer
1.867
270489AE1-102 GEN1
Solar/Wind Harmer
0.62
965421AG1-410 GEN
Solar/Wind Harmer
14.177
24695305TIMB G C
Solar/Wind Harmer
2.547
270449AD2-020 GEN
Solar/Wind Harmer
1.279
943021AE2-325 GEN
Solar/Wind Harmer
1.662
945111AF1-176 GEN
Solar/Wind Harmer
7.986
247521TR3_G114
Solar/Wind Harmer
1.503
270246TR4_N_V150
Solar/Wind Harmer
0.38
270505AE1-170 C O1
Solar/Wind Harmer
6.706
241847AF2-150_GEN
Solar/Wind Harmer
1.823
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.96
270462AD2-086
Solar/Wind Harmer
3.029
961971AG1-040 GEN
Solar/Wind Helper
0.395
203835AF1-098 GEN
Solar/Wind Helper
1.556
203860AG1-193 C
Solar/Wind Helper
0.17
241966AE1-183 GEN
Solar/Wind Helper
0.117
203954AE2-126 C
Solar/Wind Helper
0.228
254303AC2-168 GEN
Solar/Wind Helper
0.067
23917202WLORG-3
50/50
1.455
23917302WLORG-4
50/50
1.423
966311AG1-500 GEN
50/50
132.376
24190002OREGON_ST1
50/50
2.646
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.708
971677AH1-339 GEN
Solar/Wind Harmer
5.827
270007AE1-245 C
Solar/Wind Harmer
2.868
942801AE2-298 GEN
Solar/Wind Harmer
0.727
246938BC-WTG3
Solar/Wind Harmer
1.899
246937BC-WTG2
Solar/Wind Harmer
1.867
961051AF2-396 GEN
Solar/Wind Harmer
7.193
961051AF2-396 GEN
Solar/Wind Harmer
3.346
960981AF2-389 GEN
Solar/Wind Harmer
0.674
957891AF2-083 GEN
Solar/Wind Harmer
1.504
247620Y3-023
Adder
0.202
971231AH1-075 GEN
Solar/Wind Harmer
0.349
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.455
203980AG1-197 GEN
Solar/Wind Helper
0.294
203979AG1-198 GEN
Solar/Wind Helper
0.227
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.305
241985AE1-237 GEN
Solar/Wind Helper
0.118
946381AF1-302 GEN
Solar/Wind Helper
0.109
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.293
945111AF1-176 GEN
Solar/Wind Harmer
2.531
270191TR4_S_V150
Solar/Wind Harmer
1.341
270247TR4_N_V136
Solar/Wind Harmer
0.38
961961AG1-039 GEN
Solar/Wind Harmer
1.258
24642205MAYFLWER
Adder
0.277
270377AD1-106 GEN
Solar/Wind Harmer
2.69
270485AE1-090_GEN
Solar/Wind Harmer
0.263
970031AG2-029 GEN
Solar/Wind Harmer
13.034
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.406
203830AF1-094 GEN
Solar/Wind Helper
0.379
959441AF2-235 GEN
Solar/Wind Helper
0.167
20334926Z1-069 C
Solar/Wind Helper
0.684
254305AE2-115 C
Solar/Wind Helper
0.101
991177J1571 G
External Queue
11.313738822937012
990142J1224
External Queue
9.748601913452148
990527J1329
External Queue
1.333598017692566
LAGNLTFEXP_LAGN->PJM
CLTF
4.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.967
TVALTFEXP_TVA->PJM
CLTF
1.87
NYPJM->LTFIMP_NY
CLTF
1.964
LGEELTFEXP_LGEE->PJM
CLTF
1.675
WECLTFEXP_WEC->PJM
CLTF
1.327
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.394
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.887
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.407
MECLTFEXP_MEC->PJM
CLTF
5.205
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-031_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1893.72
MW Contribution:206.56
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.318
23917102WLORG-2
50/50
1.299
24189902OREGON_CT2
50/50
1.916
23856402BAYSG1
50/50
1.035
241885AC2-103 GEN1
Solar/Wind Harmer
12.452
241807AE2-176_GEN
Solar/Wind Harmer
5.144
972253AH1-711 GEN
Adder
37.939
241858AF1-205_GEN
Solar/Wind Harmer
4.286
241808AF1-120 C
Solar/Wind Harmer
0.937
23920202STRYCT
Adder
1.402
241840AF1-064_GEN
Solar/Wind Harmer
1.11
966321AG1-501 GEN
Adder
1.036
957111AF2-005 GEN
Adder
0.829
972301AH1-735 GEN
Adder
5.214
23906402RICHG1
Adder
1.043
23906502RICHG2&3
Adder
1.042
270361_3
Solar/Wind Harmer
7.442
960841AF2-375 GEN
Solar/Wind Harmer
3.277
270428AC2-015 C
Solar/Wind Harmer
3.83
247522W1-056 GEN
Solar/Wind Harmer
1.411
970515AG2-329 GEN
Solar/Wind Harmer
9.065
970905AG2-564 GEN
Solar/Wind Harmer
3.041
944231AF1-091 GEN
Solar/Wind Harmer
1.98
241847AF2-150_GEN
Solar/Wind Harmer
2.034
246936BC-WTG1
Solar/Wind Harmer
1.863
270489AE1-102 GEN1
Solar/Wind Harmer
0.619
965421AG1-410 GEN
Solar/Wind Harmer
14.14
24695305TIMB G C
Solar/Wind Harmer
2.541
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.647
247521TR3_G114
Solar/Wind Harmer
1.5
270246TR4_N_V150
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
7.917
270505AE1-170 C O1
Solar/Wind Harmer
6.647
270462AD2-086
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.066
270063AE2-323 C
Solar/Wind Harmer
0.954
961971AG1-040 GEN
Solar/Wind Helper
0.397
203835AF1-098 GEN
Solar/Wind Helper
1.564
203860AG1-193 C
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.229
254303AC2-168 GEN
Solar/Wind Helper
0.068
23867002DVBSG1
50/50
8.998
972211AH1-690 GEN
50/50
206.563
24191202EL_AA1-006
50/50
0.275
241886AC2-103 GEN2
Solar/Wind Harmer
12.452
970817AG2-515 GEN
Solar/Wind Harmer
11.334
945411AF1-206 GEN
Solar/Wind Harmer
6.279
270499AE1-146 GEN
Solar/Wind Harmer
2.052
945641AF1-229 GEN
Solar/Wind Harmer
2.838
970159AG2-109 GEN
Solar/Wind Harmer
2.868
270297AD1-101 GEN
Solar/Wind Harmer
1.572
971549AH1-272 GEN
Solar/Wind Harmer
10.061
966831AG1-554 GEN
Solar/Wind Harmer
0.634
971989AH1-539 GEN
Solar/Wind Harmer
6.861
971567AH1-282 GEN
Solar/Wind Harmer
7.246
247607V1-011 GEN
Solar/Wind Harmer
1.909
957201AF2-014 GEN
Solar/Wind Harmer
2.159
270435AC2-044 GEN
Solar/Wind Harmer
0.952
944161AF1-084 GEN
Solar/Wind Harmer
1.011
965041AG1-368 GEN
Solar/Wind Harmer
4.473
965051AG1-369 GEN
Solar/Wind Harmer
2.227
270302AB2-170 GEN
Solar/Wind Harmer
3.651
270317AD1-130_GEN
Solar/Wind Harmer
1.4
203846AF2-130 C
Solar/Wind Helper
0.271
203804AE2-113_GEN
Solar/Wind Helper
0.931
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.34
23917302WLORG-4
50/50
1.311
966311AG1-500 GEN
50/50
121.92
24190002OREGON_ST1
50/50
2.577
24189802OREGON_CT1
50/50
1.955
241996AE2-282_GEN
Solar/Wind Harmer
1.681
23857202WLORG-B
Adder
5.296
971677AH1-339 GEN
Solar/Wind Harmer
5.951
270007AE1-245 C
Solar/Wind Harmer
2.864
942801AE2-298 GEN
Solar/Wind Harmer
0.726
246938BC-WTG3
Solar/Wind Harmer
1.895
246937BC-WTG2
Solar/Wind Harmer
1.863
971231AH1-075 GEN
Solar/Wind Harmer
0.364
961051AF2-396 GEN
Solar/Wind Harmer
7.128
961051AF2-396 GEN
Solar/Wind Harmer
3.316
960981AF2-389 GEN
Solar/Wind Harmer
0.668
957891AF2-083 GEN
Solar/Wind Harmer
1.491
247620Y3-023
Adder
0.2
203947AF1-006 C
Solar/Wind Helper
0.458
203980AG1-197 GEN
Solar/Wind Helper
0.295
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.119
241967AE2-285_GEN
Solar/Wind Helper
0.307
241985AE1-237 GEN
Solar/Wind Helper
0.119
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
962101AG1-054 GEN
Solar/Wind Helper
0.294
957071AF2-004 GEN
50/50
10.437
23929302BS-PKR
50/50
1.821
241832AE2-181_GEN
Solar/Wind Harmer
1.524
958321AF2-126 GEN
Solar/Wind Harmer
1.19
23857102WLORG-A
Adder
5.14
23906502RICHG2&3
Adder
1.042
270575GUS2 35KV
Solar/Wind Harmer
8.767
270541AE2-072 C
Solar/Wind Harmer
3.515
970217AG2-149 GEN
Solar/Wind Harmer
19.989
270588AE1-091_GEN
Solar/Wind Harmer
5.936
270044AE2-322 C
Solar/Wind Harmer
0.695
270404AC1-167 GEN
Solar/Wind Harmer
0.579
270258AD1-119 GEN
Solar/Wind Harmer
1.418
961961AG1-039 GEN
Solar/Wind Harmer
1.403
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.2
270491AE1-102 GEN2
Solar/Wind Harmer
0.619
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.813
270191TR4_S_V150
Solar/Wind Harmer
1.338
270247TR4_N_V136
Solar/Wind Harmer
0.379
945111AF1-176 GEN
Solar/Wind Harmer
2.509
270485AE1-090_GEN
Solar/Wind Harmer
0.264
24642205MAYFLWER
Adder
0.275
970031AG2-029 GEN
Solar/Wind Harmer
12.948
962511AG1-100 GEN
Solar/Wind Helper
0.408
203830AF1-094 GEN
Solar/Wind Helper
0.381
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.686
254305AE2-115 C
Solar/Wind Helper
0.102
991177J1571 G
External Queue
11.006390571594238
990142J1224
External Queue
9.468253135681152
990527J1329
External Queue
1.2952468395233154
LAGNLTFEXP_LAGN->PJM
CLTF
4.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
TVALTFEXP_TVA->PJM
CLTF
1.879
NYPJM->LTFIMP_NY
CLTF
1.967
LGEELTFEXP_LGEE->PJM
CLTF
1.683
WECLTFEXP_WEC->PJM
CLTF
1.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.443
MECLTFEXP_MEC->PJM
CLTF
5.19
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.17 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:3270.93
MW Contribution:297.55
Bus #Bus NameTypeMW Contribution
23917202WLORG-3
50/50
1.953
23917302WLORG-4
50/50
1.91
966311AG1-500 GEN
50/50
177.624
24190002OREGON_ST1
50/50
3.713
24189802OREGON_CT1
50/50
2.816
23857202WLORG-B
Adder
8.455
241996AE2-282_GEN
Solar/Wind Harmer
2.414
971677AH1-339 GEN
Solar/Wind Harmer
8.462
270007AE1-245 C
Solar/Wind Harmer
4.022
942801AE2-298 GEN
Solar/Wind Harmer
1.019
246938BC-WTG3
Solar/Wind Harmer
2.659
246937BC-WTG2
Solar/Wind Harmer
2.614
971231AH1-075 GEN
Solar/Wind Harmer
0.508
961051AF2-396 GEN
Solar/Wind Harmer
9.992
961051AF2-396 GEN
Solar/Wind Harmer
4.648
960981AF2-389 GEN
Solar/Wind Harmer
0.936
957891AF2-083 GEN
Solar/Wind Harmer
2.088
247620Y3-023
Adder
0.281
270216AD2-079_GEN
Solar/Wind Harmer
0.363
970611AG2-400 GEN
Solar/Wind Harmer
5.975
270526AF1-158 GEN
Solar/Wind Harmer
2.631
24441505OLIV SLR
Solar/Wind Harmer
0.077
971201AH1-060 GEN
Solar/Wind Harmer
1.151
270224U2-072_GEN2
Solar/Wind Harmer
1.12
270227U2-072_GEN3
Solar/Wind Harmer
1.12
270228U2-072_GEN4
Solar/Wind Harmer
1.12
270231U2-072_GEN5
Solar/Wind Harmer
1.12
965681AG1-436 GEN
Solar/Wind Harmer
6.942
965791AG1-447 GEN
Solar/Wind Harmer
3.552
241960AC2-195 GEN
Solar/Wind Harmer
1.533
274808UNIV PK N;4U
Adder
2.553
942221AE2-234 GEN
Solar/Wind Harmer
0.373
274803UNIV PARK;6U
Adder
2.953
274888KELLY CRK;1U
Solar/Wind Harmer
2.977
274887GEN-1.85
Solar/Wind Harmer
2.688
957071AF2-004 GEN
50/50
15.205
23929302BS-PKR
50/50
2.62
23857102WLORG-A
Adder
8.207
241832AE2-181_GEN
Solar/Wind Harmer
2.188
958321AF2-126 GEN
Solar/Wind Harmer
1.707
23906502RICHG2&3
Adder
1.489
270575GUS2 35KV
Solar/Wind Harmer
12.516
270541AE2-072 C
Solar/Wind Harmer
5.011
970217AG2-149 GEN
Solar/Wind Harmer
28.273
270588AE1-091_GEN
Solar/Wind Harmer
8.353
270044AE2-322 C
Solar/Wind Harmer
0.979
270404AC1-167 GEN
Solar/Wind Harmer
0.816
270258AD1-119 GEN
Solar/Wind Harmer
1.996
961961AG1-039 GEN
Solar/Wind Harmer
1.964
958091AF2-103 GEN
Solar/Wind Harmer
0.109
247604X1-042
Adder
0.282
270491AE1-102 GEN2
Solar/Wind Harmer
0.868
24441205WTRV SLR C
Solar/Wind Harmer
0.089
270377AD1-106 GEN
Solar/Wind Harmer
3.918
270191TR4_S_V150
Solar/Wind Harmer
1.873
270247TR4_N_V136
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
3.515
270485AE1-090_GEN
Solar/Wind Harmer
0.369
24642205MAYFLWER
Adder
0.384
970031AG2-029 GEN
Solar/Wind Harmer
18.113
247643Z2-116 C
Solar/Wind Harmer
0.042
959331AF2-224 GEN
Solar/Wind Harmer
5.975
965021AG1-366 GEN
Solar/Wind Harmer
1.39
970065AG2-057 GEN
Solar/Wind Harmer
0.575
942871AE2-306 GEN
Solar/Wind Harmer
0.514
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270043AE2-236 GEN
Solar/Wind Harmer
3.089
970349AG2-230 GEN
Solar/Wind Harmer
8.3
270535AF1-215 GEN1
Solar/Wind Harmer
2.387
972231SS25-0005
Solar/Wind Harmer
4.917
972181SS23-001
Solar/Wind Harmer
3.073
274752CRETE EC ;2U
Adder
2.532
274753CRETE EC ;3U
Adder
2.532
964401AG1-302 GEN
Solar/Wind Harmer
4.687
274724RIVER EC ;11
Adder
9.105
959141AF2-205 GEN
Solar/Wind Harmer
3.076
274802UNIV PARK;5U
Adder
2.953
274826FISK ;BP
Adder
5.536
274800UNIV PARK;3U
Adder
2.944
972038AH1-567 GEN2
Adder
0.184
276772AC2-154 GEN
Solar/Wind Harmer
1.406
276806AD2-047 C O1
Solar/Wind Harmer
5.394
970941AG2-585 GEN
Solar/Wind Harmer
6.303
274772LINCOLN ;3U
Adder
3.125
971617AH1-308 GEN
Solar/Wind Harmer
2.93
972228AH1-698 GEN2
Adder
1.862
274676JOLIET 29;8U
Adder
14.797
276897AD1-100 C
Solar/Wind Harmer
14.503
939351AE1-166 GEN
Solar/Wind Harmer
2.963
276893AG1-478 C
Solar/Wind Harmer
0.209
970707AG2-453 GEN
Solar/Wind Harmer
13.981
274729ELWOOD EC;1P
Adder
8.208
274730ELWOOD EC;6P
Adder
8.208
274734ELWOOD EC;8P
Adder
8.208
274736ELWOOD EC;9P
Adder
8.208
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.078
274682WAUKEGAN ;7U
Adder
8.816
972236AH1-702 GEN2
Adder
1.051
274760LEE CO EC;1U
Adder
4.416
962511AG1-100 GEN
Solar/Wind Helper
0.462
203830AF1-094 GEN
Solar/Wind Helper
0.435
959441AF2-235 GEN
Solar/Wind Helper
0.196
254305AE2-115 C
Solar/Wind Helper
0.138
20334926Z1-069 C
Solar/Wind Helper
0.837
203854AF2-039 C
Solar/Wind Helper
0.18
203818AF1-086 GEN
Solar/Wind Helper
0.912
238202AE2-262_GEN
Solar/Wind Helper
0.528
941421AE2-139 GEN
Solar/Wind Helper
1.203
235058AG1-386 C
Solar/Wind Helper
0.205
200917MEHOOPANY_G
Solar/Wind Helper
1.091
23867002DVBSG1
50/50
13.011
972211AH1-690 GEN
50/50
297.552
241886AC2-103 GEN2
Solar/Wind Harmer
18.089
24191202EL_AA1-006
Adder
0.36
970817AG2-515 GEN
Solar/Wind Harmer
16.3
945411AF1-206 GEN
Solar/Wind Harmer
9.015
270499AE1-146 GEN
Solar/Wind Harmer
2.926
945641AF1-229 GEN
Solar/Wind Harmer
4.044
970159AG2-109 GEN
Solar/Wind Harmer
3.924
270297AD1-101 GEN
Solar/Wind Harmer
2.22
971549AH1-272 GEN
Solar/Wind Harmer
14.209
966831AG1-554 GEN
Solar/Wind Harmer
0.892
971989AH1-539 GEN
Solar/Wind Harmer
9.641
247607V1-011 GEN
Solar/Wind Harmer
2.681
971567AH1-282 GEN
Solar/Wind Harmer
10.136
957201AF2-014 GEN
Solar/Wind Harmer
3.029
270435AC2-044 GEN
Solar/Wind Harmer
1.336
944161AF1-084 GEN
Solar/Wind Harmer
1.419
965041AG1-368 GEN
Solar/Wind Harmer
6.263
965051AG1-369 GEN
Solar/Wind Harmer
3.117
270302AB2-170 GEN
Solar/Wind Harmer
5.097
270317AD1-130_GEN
Solar/Wind Harmer
1.954
971771AH1-392 GEN
Solar/Wind Harmer
5.317
971769AH1-391 GEN
Solar/Wind Harmer
5.763
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
960681AF2-359 GEN
Solar/Wind Harmer
2.098
963791AG1-232 GEN
Solar/Wind Harmer
7.497
971347AH1-153 GEN
Solar/Wind Harmer
8.3
970179AG2-119 GEN
Solar/Wind Harmer
4.411
971219AH1-069 GEN
Solar/Wind Harmer
0.907
270536AF1-215 GEN2
Solar/Wind Harmer
2.387
270071AF1-092 GEN
Solar/Wind Harmer
7.858
958391AF2-133 GEN
Solar/Wind Harmer
4.646
274814UNIV PK N;0U
Adder
2.586
274807UNIV PK N;3U
Adder
2.581
274805UNIV PK N;1U
Adder
2.569
274811UNIV PK N;7U
Adder
2.564
972037AH1-567 GEN1
Adder
0.093
274827FISK ;RP
Adder
3.924
960591AF2-350 GEN
Solar/Wind Harmer
5.042
274775LINCOLN ;6U
Adder
3.125
274776LINCOLN ;7U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
270024AE2-089 GEN
Solar/Wind Harmer
2.366
972227AH1-698 GEN1
Adder
1.311
274687WILL CNTY;4U
Adder
14.004
274687WILL CNTY;4U
Adder
14.004
274675JOLIET 29;7U
Adder
15.345
274675JOLIET 29;7U
Adder
14.797
274731ELWOOD EC;2P
Adder
8.208
274733ELWOOD EC;3P
Adder
8.208
274735ELWOOD EC;4P
Adder
8.208
274728ELWOOD EC;5P
Adder
8.208
274746AC1-111 G10
Adder
2.761
274744AC1-111 GEN8
Adder
2.761
24729505KEY G4
Adder
3.179
274823ROCKFORD ;21
Adder
9.356
203846AF2-130 C
Solar/Wind Helper
0.325
241982AE2-343 S C
Solar/Wind Helper
0.145
254304AE2-114 C
Solar/Wind Helper
0.138
241997AF1-093 GEN
Solar/Wind Helper
0.16
203804AE2-113_GEN
Solar/Wind Helper
1.128
203855AF2-088 C
Solar/Wind Helper
0.087
20090526Q36
Solar/Wind Helper
0.548
203993AD2-133_GEN1
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.29
20092526R32
Solar/Wind Helper
0.563
203961AE2-224 GEN
Solar/Wind Helper
1.164
941231AE2-117 GEN
Solar/Wind Helper
0.227
970833AG2-524 GEN
Solar/Wind Harmer
1.943
970833AG2-524 GEN
Solar/Wind Harmer
0.904
276843GEN-1.7
Solar/Wind Harmer
0.289
958011AF2-095 GEN
Solar/Wind Harmer
7.261
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
972259AH1-714 GEN
Adder
9.55
274674JOLIET 9 ;6U
Adder
7.687
970321AG2-212 GEN
Solar/Wind Harmer
8.906
274696ROCKY RD ;4P
Adder
5.589
274695ROCKY RD ;2P
Adder
5.46
274693ROCKY RD ;1P
Adder
5.407
274697ROCKY RD ;3P
Adder
1.483
274683WAUKEGAN ;8U
Adder
10.328
274683WAUKEGAN ;8U
Adder
8.706
25326509SID D
Adder
0.633
274764LEE CO EC;5U
Adder
4.426
274765LEE CO EC;6U
Adder
4.426
203947AF1-006 C
Solar/Wind Helper
0.516
203980AG1-197 GEN
Solar/Wind Helper
0.336
203979AG1-198 GEN
Solar/Wind Helper
0.261
241967AE2-285_GEN
Solar/Wind Helper
0.417
241801AE1-079 GEN
Solar/Wind Helper
0.162
241985AE1-237 GEN
Solar/Wind Helper
0.162
962101AG1-054 GEN
Solar/Wind Helper
0.402
946381AF1-302 GEN
Solar/Wind Helper
0.136
238217AF1-153 C O1
Solar/Wind Helper
0.144
20398826ARMNA MT
Solar/Wind Helper
0.849
203853AF1-134 C O1
Solar/Wind Helper
0.264
203952AE2-129 C
Solar/Wind Helper
0.257
203946AE2-131 C
Solar/Wind Helper
0.258
946071AF1-272 GEN
Solar/Wind Helper
1.356
203940AF1-140 C
Solar/Wind Helper
0.192
20084626FORWARD
Solar/Wind Helper
0.17
20088626ARWF_N39
Solar/Wind Helper
0.584
20303426NA_O38_P22
Solar/Wind Helper
0.479
20088926STNY CRK
Solar/Wind Helper
0.38
20083426SW_E13_K22
Solar/Wind Helper
0.025
23917402WLORG-5
50/50
1.92
23917102WLORG-2
50/50
1.892
24189902OREGON_CT2
50/50
2.76
23856402BAYSG1
50/50
1.489
241885AC2-103 GEN1
Solar/Wind Harmer
18.089
241807AE2-176_GEN
Solar/Wind Harmer
7.368
972253AH1-711 GEN
Adder
54.605
241858AF1-205_GEN
Solar/Wind Harmer
6.156
966321AG1-501 GEN
Adder
1.655
957111AF2-005 GEN
Adder
1.324
241808AF1-120 C
Solar/Wind Harmer
1.346
23920202STRYCT
Adder
2.011
241840AF1-064_GEN
Solar/Wind Harmer
1.592
972301AH1-735 GEN
Adder
7.456
23906402RICHG1
Adder
1.491
23906502RICHG2&3
Adder
1.489
270361_3
Solar/Wind Harmer
10.624
960841AF2-375 GEN
Solar/Wind Harmer
4.677
270428AC2-015 C
Solar/Wind Harmer
5.418
247522W1-056 GEN
Solar/Wind Harmer
1.996
970515AG2-329 GEN
Solar/Wind Harmer
12.822
970905AG2-564 GEN
Solar/Wind Harmer
4.278
944231AF1-091 GEN
Solar/Wind Harmer
2.791
241847AF2-150_GEN
Solar/Wind Harmer
2.847
246936BC-WTG1
Solar/Wind Harmer
2.614
270489AE1-102 GEN1
Solar/Wind Harmer
0.868
965421AG1-410 GEN
Solar/Wind Harmer
19.836
24695305TIMB G C
Solar/Wind Harmer
3.562
270449AD2-020 GEN
Solar/Wind Harmer
1.777
943021AE2-325 GEN
Solar/Wind Harmer
2.309
247521TR3_G114
Solar/Wind Harmer
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.531
945111AF1-176 GEN
Solar/Wind Harmer
11.092
270505AE1-170 C O1
Solar/Wind Harmer
9.313
270462AD2-086
Solar/Wind Harmer
4.24
24639705ELKHART HY
Adder
0.093
270063AE2-323 C
Solar/Wind Harmer
1.334
965011AG1-365 GEN
Solar/Wind Harmer
5.975
241813AF1-122_GEN
Solar/Wind Harmer
3.682
270223U2-072_GEN1
Solar/Wind Harmer
1.12
270578AF1-285 GEN2
Solar/Wind Harmer
0.685
270391AF1-285 GEN3
Solar/Wind Harmer
0.685
970373AG2-245 GEN
Solar/Wind Harmer
11.24
971221AH1-070 GEN
Solar/Wind Harmer
0.907
270055AF2-134 C O1
Solar/Wind Harmer
1.591
274751CRETE EC ;1U
Adder
2.532
274754CRETE EC ;4U
Adder
2.532
958381AF2-132 GEN
Solar/Wind Harmer
4.687
964861AG1-349 GEN
Solar/Wind Harmer
4.054
971917AH1-482 GEN
Solar/Wind Harmer
4.678
274723RIVER EC ;12
Adder
9.215
274812UNIV PK N;8U
Adder
2.564
276164X3-005 C
Solar/Wind Harmer
0.358
274801UNIV PARK;4U
Adder
2.944
940581AE2-045 GEN
Solar/Wind Harmer
5.147
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276776AD2-060 GEN
Solar/Wind Harmer
0.213
972207SS24-0001
Solar/Wind Harmer
11.112
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274676JOLIET 29;8U
Adder
15.345
941551AE2-152 GEN
Solar/Wind Harmer
2.266
274732ELWOOD EC;7P
Adder
8.208
274674JOLIET 9 ;6U
Adder
7.687
970245AG2-165 GEN
Solar/Wind Harmer
8.906
274745AC1-111 GEN9
Adder
2.761
274682WAUKEGAN ;7U
Adder
8.816
274828WAUKEGAN ;BP
Adder
5.414
274822ROCKFORD ;11
Adder
9.424
972235AH1-702 GEN1
Adder
1.208
274761LEE CO EC;2U
Adder
2.885
961971AG1-040 GEN
Solar/Wind Helper
0.451
203835AF1-098 GEN
Solar/Wind Helper
1.778
203860AG1-193 C
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.16
254303AC2-168 GEN
Solar/Wind Helper
0.093
203954AE2-126 C
Solar/Wind Helper
0.282
959471AF2-238 GEN
Solar/Wind Helper
0.26
238206AE2-263_GEN
Solar/Wind Helper
0.502
20094526CT_V3-030
Solar/Wind Helper
0.243
20088826HIGHLAND
Solar/Wind Helper
0.435
964201AG1-281 GEN
Solar/Wind Helper
0.234
964391AG1-301 GEN
Solar/Wind Helper
0.226
991182J1586 G
External Queue
25.886547088623047
991177J1571 G
External Queue
16.072763442993164
990142J1224
External Queue
13.827776908874512
990527J1329
External Queue
1.891624927520752
LAGNLTFEXP_LAGN->PJM
CLTF
5.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.427
TVALTFEXP_TVA->PJM
CLTF
2.517
NYPJM->LTFIMP_NY
CLTF
2.552
LGEELTFEXP_LGEE->PJM
CLTF
2.281
WECLTFEXP_WEC->PJM
CLTF
1.831
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177
CPLELTFEXP_CPLE->PJM
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.995
MECLTFEXP_MEC->PJM
CLTF
7.157
SIGELTFEXP_SIGE->PJM
CLTF
0.189

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-003_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.48
MW Contribution:210.31
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.364
23917102WLORG-2
50/50
1.344
24189902OREGON_CT2
50/50
1.95
23856402BAYSG1
50/50
1.049
241885AC2-103 GEN1
Solar/Wind Harmer
12.828
241807AE2-176_GEN
Solar/Wind Harmer
5.09
972253AH1-711 GEN
Adder
38.596
241858AF1-205_GEN
Solar/Wind Harmer
4.35
241808AF1-120 C
Solar/Wind Harmer
0.951
23920202STRYCT
Adder
1.423
241840AF1-064_GEN
Solar/Wind Harmer
1.126
972301AH1-735 GEN
Adder
5.287
23906402RICHG1
Adder
1.057
23906502RICHG2&3
Adder
1.056
270361_3
Solar/Wind Harmer
7.495
960841AF2-375 GEN
Solar/Wind Harmer
3.301
966321AG1-501 GEN
Adder
0.871
957111AF2-005 GEN
Adder
0.697
270428AC2-015 C
Solar/Wind Harmer
3.771
247522W1-056 GEN
Solar/Wind Harmer
1.418
970515AG2-329 GEN
Solar/Wind Harmer
9.087
970905AG2-564 GEN
Solar/Wind Harmer
2.97
944231AF1-091 GEN
Solar/Wind Harmer
2.004
241847AF2-150_GEN
Solar/Wind Harmer
2
246936BC-WTG1
Solar/Wind Harmer
1.883
270489AE1-102 GEN1
Solar/Wind Harmer
0.626
965421AG1-410 GEN
Solar/Wind Harmer
14.298
24695305TIMB G C
Solar/Wind Harmer
2.569
270449AD2-020 GEN
Solar/Wind Harmer
1.284
943021AE2-325 GEN
Solar/Wind Harmer
1.668
247521TR3_G114
Solar/Wind Harmer
1.516
270246TR4_N_V150
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
8.018
270505AE1-170 C O1
Solar/Wind Harmer
6.733
270462AD2-086
Solar/Wind Harmer
3.066
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.965
965011AG1-365 GEN
Solar/Wind Harmer
4.324
961971AG1-040 GEN
Solar/Wind Helper
0.4
203835AF1-098 GEN
Solar/Wind Helper
1.575
203860AG1-193 C
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.119
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
957071AF2-004 GEN
50/50
10.802
23929302BS-PKR
50/50
1.846
241832AE2-181_GEN
Solar/Wind Harmer
1.547
958321AF2-126 GEN
Solar/Wind Harmer
1.207
23906502RICHG2&3
Adder
1.056
270575GUS2 35KV
Solar/Wind Harmer
8.83
23857102WLORG-A
Adder
4.322
270541AE2-072 C
Solar/Wind Harmer
3.557
970217AG2-149 GEN
Solar/Wind Harmer
20.039
270588AE1-091_GEN
Solar/Wind Harmer
5.974
270044AE2-322 C
Solar/Wind Harmer
0.703
270404AC1-167 GEN
Solar/Wind Harmer
0.585
270258AD1-119 GEN
Solar/Wind Harmer
1.434
958091AF2-103 GEN
Solar/Wind Harmer
0.079
247604X1-042
Adder
0.203
961961AG1-039 GEN
Solar/Wind Harmer
1.38
270491AE1-102 GEN2
Solar/Wind Harmer
0.626
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.809
270191TR4_S_V150
Solar/Wind Harmer
1.353
270247TR4_N_V136
Solar/Wind Harmer
0.384
945111AF1-176 GEN
Solar/Wind Harmer
2.541
270485AE1-090_GEN
Solar/Wind Harmer
0.267
24642205MAYFLWER
Adder
0.278
970031AG2-029 GEN
Solar/Wind Harmer
13.106
247643Z2-116 C
Solar/Wind Harmer
0.03
959331AF2-224 GEN
Solar/Wind Harmer
4.324
965021AG1-366 GEN
Solar/Wind Harmer
1.006
962511AG1-100 GEN
Solar/Wind Helper
0.411
203830AF1-094 GEN
Solar/Wind Helper
0.384
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.692
254305AE2-115 C
Solar/Wind Helper
0.103
23867002DVBSG1
50/50
9.2
972211AH1-690 GEN
50/50
210.311
241886AC2-103 GEN2
Solar/Wind Harmer
12.828
970817AG2-515 GEN
Solar/Wind Harmer
11.522
24191202EL_AA1-006
Adder
0.249
945411AF1-206 GEN
Solar/Wind Harmer
6.374
270499AE1-146 GEN
Solar/Wind Harmer
2.067
945641AF1-229 GEN
Solar/Wind Harmer
2.863
970159AG2-109 GEN
Solar/Wind Harmer
2.569
270297AD1-101 GEN
Solar/Wind Harmer
1.589
971549AH1-272 GEN
Solar/Wind Harmer
10.203
966831AG1-554 GEN
Solar/Wind Harmer
0.637
971989AH1-539 GEN
Solar/Wind Harmer
6.89
247607V1-011 GEN
Solar/Wind Harmer
1.93
971567AH1-282 GEN
Solar/Wind Harmer
7.229
957201AF2-014 GEN
Solar/Wind Harmer
2.183
270435AC2-044 GEN
Solar/Wind Harmer
0.963
944161AF1-084 GEN
Solar/Wind Harmer
1.025
965041AG1-368 GEN
Solar/Wind Harmer
4.523
965051AG1-369 GEN
Solar/Wind Harmer
2.252
270302AB2-170 GEN
Solar/Wind Harmer
3.686
270317AD1-130_GEN
Solar/Wind Harmer
1.413
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.939
241982AE2-343 S C
Solar/Wind Helper
0.108
254304AE2-114 C
Solar/Wind Helper
0.103
241997AF1-093 GEN
Solar/Wind Helper
0.119
23917202WLORG-3
50/50
1.387
23917302WLORG-4
50/50
1.357
966311AG1-500 GEN
50/50
126.182
24190002OREGON_ST1
50/50
2.624
24189802OREGON_CT1
50/50
1.991
241996AE2-282_GEN
Solar/Wind Harmer
1.706
23857202WLORG-B
Adder
4.453
971677AH1-339 GEN
Solar/Wind Harmer
5.98
270007AE1-245 C
Solar/Wind Harmer
2.895
942801AE2-298 GEN
Solar/Wind Harmer
0.734
246938BC-WTG3
Solar/Wind Harmer
1.916
246937BC-WTG2
Solar/Wind Harmer
1.883
961051AF2-396 GEN
Solar/Wind Harmer
7.22
961051AF2-396 GEN
Solar/Wind Harmer
3.358
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.51
247620Y3-023
Adder
0.203
270216AD2-079_GEN
Solar/Wind Harmer
0.263
970611AG2-400 GEN
Solar/Wind Harmer
4.324
203947AF1-006 C
Solar/Wind Helper
0.461
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.309
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.111
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.297
991177J1571 G
External Queue
11.211230278015137
990142J1224
External Queue
9.648950576782227
990527J1329
External Queue
1.3199658393859863
LAGNLTFEXP_LAGN->PJM
CLTF
4.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.016
TVALTFEXP_TVA->PJM
CLTF
1.895
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.697
WECLTFEXP_WEC->PJM
CLTF
1.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.086
AH1-155LTFEXP_AH1-155->PJM
LTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.744
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.978
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.506
MECLTFEXP_MEC->PJM
CLTF
5.248
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-028_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1903.65
MW Contribution:207.62
Bus #Bus NameTypeMW Contribution
23917402WLORG-5
50/50
1.325
23917102WLORG-2
50/50
1.305
24189902OREGON_CT2
50/50
1.926
957071AF2-004 GEN
50/50
10.49
23929302BS-PKR
50/50
1.83
241832AE2-181_GEN
Solar/Wind Harmer
1.532
958321AF2-126 GEN
Solar/Wind Harmer
1.196
23857102WLORG-A
Adder
5.166
23906502RICHG2&3
Adder
1.047
270575GUS2 35KV
Solar/Wind Harmer
8.812
270541AE2-072 C
Solar/Wind Harmer
3.533
970217AG2-149 GEN
Solar/Wind Harmer
20.092
270588AE1-091_GEN
Solar/Wind Harmer
5.966
270044AE2-322 C
Solar/Wind Harmer
0.698
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270258AD1-119 GEN
Solar/Wind Harmer
1.425
961961AG1-039 GEN
Solar/Wind Harmer
1.41
23867002DVBSG1
50/50
9.044
972211AH1-690 GEN
50/50
207.621
24191202EL_AA1-006
50/50
0.277
241886AC2-103 GEN2
Solar/Wind Harmer
12.516
970817AG2-515 GEN
Solar/Wind Harmer
11.392
945411AF1-206 GEN
Solar/Wind Harmer
6.311
270499AE1-146 GEN
Solar/Wind Harmer
2.062
945641AF1-229 GEN
Solar/Wind Harmer
2.852
970159AG2-109 GEN
Solar/Wind Harmer
2.883
270297AD1-101 GEN
Solar/Wind Harmer
1.58
971549AH1-272 GEN
Solar/Wind Harmer
10.113
966831AG1-554 GEN
Solar/Wind Harmer
0.638
971989AH1-539 GEN
Solar/Wind Harmer
6.896
971567AH1-282 GEN
Solar/Wind Harmer
7.283
247607V1-011 GEN
Solar/Wind Harmer
1.919
957201AF2-014 GEN
Solar/Wind Harmer
2.17
270435AC2-044 GEN
Solar/Wind Harmer
0.957
23856402BAYSG1
50/50
1.04
241885AC2-103 GEN1
Solar/Wind Harmer
12.516
241807AE2-176_GEN
Solar/Wind Harmer
5.17
972253AH1-711 GEN
Adder
38.133
241858AF1-205_GEN
Solar/Wind Harmer
4.307
241808AF1-120 C
Solar/Wind Harmer
0.942
23920202STRYCT
Adder
1.409
241840AF1-064_GEN
Solar/Wind Harmer
1.116
966321AG1-501 GEN
Adder
1.042
957111AF2-005 GEN
Adder
0.833
972301AH1-735 GEN
Adder
5.24
23906402RICHG1
Adder
1.048
23906502RICHG2&3
Adder
1.047
270361_3
Solar/Wind Harmer
7.48
960841AF2-375 GEN
Solar/Wind Harmer
3.294
270428AC2-015 C
Solar/Wind Harmer
3.85
247522W1-056 GEN
Solar/Wind Harmer
1.419
970515AG2-329 GEN
Solar/Wind Harmer
9.111
970905AG2-564 GEN
Solar/Wind Harmer
3.056
944231AF1-091 GEN
Solar/Wind Harmer
1.99
241847AF2-150_GEN
Solar/Wind Harmer
2.044
246936BC-WTG1
Solar/Wind Harmer
1.872
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
965421AG1-410 GEN
Solar/Wind Harmer
14.212
24695305TIMB G C
Solar/Wind Harmer
2.554
270449AD2-020 GEN
Solar/Wind Harmer
1.274
943021AE2-325 GEN
Solar/Wind Harmer
1.655
247521TR3_G114
Solar/Wind Harmer
1.507
270246TR4_N_V150
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
7.958
270505AE1-170 C O1
Solar/Wind Harmer
6.681
270462AD2-086
Solar/Wind Harmer
3.053
24639705ELKHART HY
Adder
0.067
270063AE2-323 C
Solar/Wind Harmer
0.958
961971AG1-040 GEN
Solar/Wind Helper
0.399
203835AF1-098 GEN
Solar/Wind Helper
1.572
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
203954AE2-126 C
Solar/Wind Helper
0.231
254303AC2-168 GEN
Solar/Wind Helper
0.068
944161AF1-084 GEN
Solar/Wind Harmer
1.017
965041AG1-368 GEN
Solar/Wind Harmer
4.496
965051AG1-369 GEN
Solar/Wind Harmer
2.238
270302AB2-170 GEN
Solar/Wind Harmer
3.67
270317AD1-130_GEN
Solar/Wind Harmer
1.407
203846AF2-130 C
Solar/Wind Helper
0.273
203804AE2-113_GEN
Solar/Wind Helper
0.936
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
241997AF1-093 GEN
Solar/Wind Helper
0.118
23917202WLORG-3
50/50
1.347
23917302WLORG-4
50/50
1.318
966311AG1-500 GEN
50/50
122.544
24190002OREGON_ST1
50/50
2.591
24189802OREGON_CT1
50/50
1.965
241996AE2-282_GEN
Solar/Wind Harmer
1.69
23857202WLORG-B
Adder
5.323
971677AH1-339 GEN
Solar/Wind Harmer
5.982
270007AE1-245 C
Solar/Wind Harmer
2.879
942801AE2-298 GEN
Solar/Wind Harmer
0.729
246938BC-WTG3
Solar/Wind Harmer
1.904
246937BC-WTG2
Solar/Wind Harmer
1.872
971231AH1-075 GEN
Solar/Wind Harmer
0.366
961051AF2-396 GEN
Solar/Wind Harmer
7.165
961051AF2-396 GEN
Solar/Wind Harmer
3.333
960981AF2-389 GEN
Solar/Wind Harmer
0.672
957891AF2-083 GEN
Solar/Wind Harmer
1.498
247620Y3-023
Adder
0.202
270216AD2-079_GEN
Solar/Wind Harmer
0.261
203947AF1-006 C
Solar/Wind Helper
0.46
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241967AE2-285_GEN
Solar/Wind Helper
0.308
241801AE1-079 GEN
Solar/Wind Helper
0.12
241985AE1-237 GEN
Solar/Wind Helper
0.12
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.296
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.201
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
24441205WTRV SLR C
Solar/Wind Harmer
0.064
270377AD1-106 GEN
Solar/Wind Harmer
2.828
270191TR4_S_V150
Solar/Wind Harmer
1.345
270247TR4_N_V136
Solar/Wind Harmer
0.381
945111AF1-176 GEN
Solar/Wind Harmer
2.522
270485AE1-090_GEN
Solar/Wind Harmer
0.265
24642205MAYFLWER
Adder
0.276
970031AG2-029 GEN
Solar/Wind Harmer
13.014
247643Z2-116 C
Solar/Wind Harmer
0.03
962511AG1-100 GEN
Solar/Wind Helper
0.41
203830AF1-094 GEN
Solar/Wind Helper
0.383
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.69
254305AE2-115 C
Solar/Wind Helper
0.102
991177J1571 G
External Queue
11.062751770019531
990142J1224
External Queue
9.516737937927246
990527J1329
External Queue
1.3018794059753418
LAGNLTFEXP_LAGN->PJM
CLTF
4.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
1.889
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.691
WECLTFEXP_WEC->PJM
CLTF
1.328
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.594
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.481
MECLTFEXP_MEC->PJM
CLTF
5.217
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 02BRWELL-02FORD 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BRWELL-02FORD 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:170.25 %
Rating:230.0 MVA
Rating Type:B
MVA to Mitigate:391.56
MW Contribution:60.94
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.094
241885AC2-103 GEN1
Solar/Wind Harmer
2.6
972253AH1-711 GEN
Adder
11.964
274676JOLIET 29;8U
Adder
3.3
274732ELWOOD EC;7P
Adder
1.765
957471AF2-041 GEN
Solar/Wind Harmer
3.101
959081AF2-199 GEN
Solar/Wind Harmer
1.034
971067AG2-660 GEN
Solar/Wind Harmer
0.24
24191202EL_AA1-006
Adder
0.153
241886AC2-103 GEN2
Solar/Wind Harmer
2.6
972211AH1-690 GEN
Adder
60.94
274675JOLIET 29;7U
Adder
3.3
274675JOLIET 29;7U
Adder
3.182
274731ELWOOD EC;2P
Adder
1.765
274733ELWOOD EC;3P
Adder
1.765
274735ELWOOD EC;4P
Adder
1.765
274728ELWOOD EC;5P
Adder
1.765
971171AH1-044 GEN
Solar/Wind Harmer
2.067
971341AH1-150 GEN
Solar/Wind Harmer
2.067
971343AH1-151 GEN
Solar/Wind Harmer
2.067
274676JOLIET 29;8U
Adder
3.182
274729ELWOOD EC;1P
Adder
1.765
274730ELWOOD EC;6P
Adder
1.765
274734ELWOOD EC;8P
Adder
1.765
274736ELWOOD EC;9P
Adder
1.765
959091AF2-200 GEN
Solar/Wind Harmer
2.067
LAGNLTFEXP_LAGN->PJM
CLTF
1.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.499
TVALTFEXP_TVA->PJM
CLTF
0.53
NYPJM->LTFIMP_NY
CLTF
0.503
LGEELTFEXP_LGEE->PJM
CLTF
0.479
WECLTFEXP_WEC->PJM
CLTF
0.393
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.104
MECLTFEXP_MEC->PJM
CLTF
1.533
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02BRWELL-02FORD 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BRWELL-02FORD 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:166.37 %
Rating:230.0 MVA
Rating Type:B
MVA to Mitigate:382.65
MW Contribution:60.97
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.094
972253AH1-711 GEN
Adder
11.97
274676JOLIET 29;8U
Adder
3.306
274732ELWOOD EC;7P
Adder
1.768
957471AF2-041 GEN
Solar/Wind Harmer
3.107
959081AF2-199 GEN
Solar/Wind Harmer
1.036
971067AG2-660 GEN
Solar/Wind Harmer
0.241
24191202EL_AA1-006
Adder
0.153
972211AH1-690 GEN
Adder
60.971
274675JOLIET 29;7U
Adder
3.306
274675JOLIET 29;7U
Adder
3.188
274731ELWOOD EC;2P
Adder
1.768
274733ELWOOD EC;3P
Adder
1.768
274735ELWOOD EC;4P
Adder
1.768
274728ELWOOD EC;5P
Adder
1.768
971171AH1-044 GEN
Solar/Wind Harmer
2.071
971341AH1-150 GEN
Solar/Wind Harmer
2.071
971343AH1-151 GEN
Solar/Wind Harmer
2.071
274676JOLIET 29;8U
Adder
3.188
274729ELWOOD EC;1P
Adder
1.768
274730ELWOOD EC;6P
Adder
1.768
274734ELWOOD EC;8P
Adder
1.768
274736ELWOOD EC;9P
Adder
1.768
959091AF2-200 GEN
Solar/Wind Harmer
2.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.505
TVALTFEXP_TVA->PJM
CLTF
0.532
NYPJM->LTFIMP_NY
CLTF
0.502
LGEELTFEXP_LGEE->PJM
CLTF
0.48
WECLTFEXP_WEC->PJM
CLTF
0.394
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.111
MECLTFEXP_MEC->PJM
CLTF
1.536
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.08 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2820.59
MW Contribution:306.57
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.123
241832AE2-181_GEN
Solar/Wind Harmer
1.981
958321AF2-126 GEN
Solar/Wind Harmer
1.453
23906502RICHG2&3
Adder
1.324
270541AE2-072 C
Solar/Wind Harmer
4.225
270575GUS2 35KV
Solar/Wind Harmer
8.717
970217AG2-149 GEN
Solar/Wind Harmer
22.392
270044AE2-322 C
Solar/Wind Harmer
0.856
270404AC1-167 GEN
Solar/Wind Harmer
0.713
247604X1-042
Adder
0.263
270258AD1-119 GEN
Solar/Wind Harmer
1.747
24441205WTRV SLR C
Solar/Wind Harmer
0.083
270491AE1-102 GEN2
Solar/Wind Harmer
0.767
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270588AE1-091_GEN
Solar/Wind Harmer
6.43
945111AF1-176 GEN
Solar/Wind Harmer
3.248
24642205MAYFLWER
Adder
0.355
247643Z2-116 C
Solar/Wind Harmer
0.038
970031AG2-029 GEN
Solar/Wind Harmer
16.505
270191TR4_S_V150
Solar/Wind Harmer
1.647
270247TR4_N_V136
Solar/Wind Harmer
0.467
959331AF2-224 GEN
Solar/Wind Harmer
5.341
965021AG1-366 GEN
Solar/Wind Harmer
1.242
270485AE1-090_GEN
Solar/Wind Harmer
0.317
270043AE2-236 GEN
Solar/Wind Harmer
2.786
970349AG2-230 GEN
Solar/Wind Harmer
7.592
942871AE2-306 GEN
Solar/Wind Harmer
0.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270535AF1-215 GEN1
Solar/Wind Harmer
2.176
972231SS25-0005
Solar/Wind Harmer
4.48
972181SS23-001
Solar/Wind Harmer
2.8
274752CRETE EC ;2U
Adder
2.308
274753CRETE EC ;3U
Adder
2.308
964401AG1-302 GEN
Solar/Wind Harmer
4.267
274724RIVER EC ;11
Adder
8.292
959141AF2-205 GEN
Solar/Wind Harmer
2.796
274802UNIV PARK;5U
Adder
2.687
274826FISK ;BP
Adder
5.037
274800UNIV PARK;3U
Adder
2.678
972038AH1-567 GEN2
Adder
0.168
276772AC2-154 GEN
Solar/Wind Harmer
1.279
276806AD2-047 C O1
Solar/Wind Harmer
4.906
970941AG2-585 GEN
Solar/Wind Harmer
5.733
274772LINCOLN ;3U
Adder
2.842
972228AH1-698 GEN2
Adder
1.694
274676JOLIET 29;8U
Adder
13.453
276897AD1-100 C
Solar/Wind Harmer
13.182
939351AE1-166 GEN
Solar/Wind Harmer
2.693
276893AG1-478 C
Solar/Wind Harmer
0.19
274729ELWOOD EC;1P
Adder
7.461
274730ELWOOD EC;6P
Adder
7.461
274734ELWOOD EC;8P
Adder
7.461
274736ELWOOD EC;9P
Adder
7.461
970707AG2-453 GEN
Solar/Wind Harmer
12.707
970513AG2-328 GEN
Solar/Wind Harmer
8.074
970517AG2-330 GEN
Solar/Wind Harmer
7.323
943121AE2-341 GEN
Solar/Wind Harmer
6.728
943591AF1-030 GEN
Solar/Wind Harmer
4.485
276694AA1-018 GEN2
Solar/Wind Harmer
2.83
274682WAUKEGAN ;7U
Adder
8.008
972236AH1-702 GEN2
Adder
0.953
274760LEE CO EC;1U
Adder
4.005
274767LEE CO EC;8U
Adder
3.958
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.651
23867002DVBSG1
50/50
15.541
972211AH1-690 GEN
50/50
306.568
23888502TROY G1
50/50
1.9
23888602TROY G2
50/50
1.9
241886AC2-103 GEN2
Solar/Wind Harmer
15.652
970817AG2-515 GEN
Solar/Wind Harmer
15.768
945411AF1-206 GEN
Solar/Wind Harmer
8.154
945641AF1-229 GEN
Solar/Wind Harmer
3.506
270499AE1-146 GEN
Solar/Wind Harmer
2.087
971549AH1-272 GEN
Solar/Wind Harmer
13.415
270297AD1-101 GEN
Solar/Wind Harmer
1.871
944161AF1-084 GEN
Solar/Wind Harmer
1.317
957201AF2-014 GEN
Solar/Wind Harmer
2.676
270435AC2-044 GEN
Solar/Wind Harmer
1.18
247607V1-011 GEN
Solar/Wind Harmer
2.325
965041AG1-368 GEN
Solar/Wind Harmer
5.531
965051AG1-369 GEN
Solar/Wind Harmer
2.742
966831AG1-554 GEN
Solar/Wind Harmer
0.652
971989AH1-539 GEN
Solar/Wind Harmer
7.048
971771AH1-392 GEN
Solar/Wind Harmer
4.891
971769AH1-391 GEN
Solar/Wind Harmer
5.295
270302AB2-170 GEN
Solar/Wind Harmer
4.384
270317AD1-130_GEN
Solar/Wind Harmer
1.681
960681AF2-359 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
7.592
971567AH1-282 GEN
Solar/Wind Harmer
7.444
963791AG1-232 GEN
Solar/Wind Harmer
6.663
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
7.051
274814UNIV PK N;0U
Adder
2.355
274807UNIV PK N;3U
Adder
2.35
274805UNIV PK N;1U
Adder
2.34
24190002OREGON_ST1
50/50
3.824
24189802OREGON_CT1
50/50
2.901
23888802TROY G4
50/50
1.9
241996AE2-282_GEN
Solar/Wind Harmer
2.183
971677AH1-339 GEN
Solar/Wind Harmer
5.955
246938BC-WTG3
Solar/Wind Harmer
2.348
246937BC-WTG2
Solar/Wind Harmer
2.308
270007AE1-245 C
Solar/Wind Harmer
3.488
942801AE2-298 GEN
Solar/Wind Harmer
0.883
961051AF2-396 GEN
Solar/Wind Harmer
9.249
961051AF2-396 GEN
Solar/Wind Harmer
4.302
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.929
247620Y3-023
Adder
0.257
270216AD2-079_GEN
Solar/Wind Harmer
0.334
970611AG2-400 GEN
Solar/Wind Harmer
5.341
270526AF1-158 GEN
Solar/Wind Harmer
2.418
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.36
965791AG1-447 GEN
Solar/Wind Harmer
3.254
270224U2-072_GEN2
Solar/Wind Harmer
0.959
270227U2-072_GEN3
Solar/Wind Harmer
0.959
270228U2-072_GEN4
Solar/Wind Harmer
0.959
270231U2-072_GEN5
Solar/Wind Harmer
0.959
274808UNIV PK N;4U
Adder
2.324
274803UNIV PARK;6U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
2.708
274887GEN-1.85
Solar/Wind Harmer
2.444
276843GEN-1.7
Solar/Wind Harmer
0.263
958011AF2-095 GEN
Solar/Wind Harmer
6.604
274770LINCOLN ;1U
Adder
2.842
274771LINCOLN ;2U
Adder
2.842
972259AH1-714 GEN
Adder
8.682
274674JOLIET 9 ;6U
Adder
6.988
942221AE2-234 GEN
Solar/Wind Harmer
0.331
970321AG2-212 GEN
Solar/Wind Harmer
8.074
274847GR RIDGE ;BU
Solar/Wind Harmer
2.283
274696ROCKY RD ;4P
Adder
5.076
274695ROCKY RD ;2P
Adder
4.959
274693ROCKY RD ;1P
Adder
4.91
274697ROCKY RD ;3P
Adder
1.347
274683WAUKEGAN ;8U
Adder
9.38
274683WAUKEGAN ;8U
Adder
7.907
274764LEE CO EC;5U
Adder
4.014
274765LEE CO EC;6U
Adder
4.014
274762LEE CO EC;3U
Adder
4.005
274763LEE CO EC;4U
Adder
3.967
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.343
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.331
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.113
958481AF2-142 GEN
Solar/Wind Harmer
6.617
274811UNIV PK N;7U
Adder
2.335
958391AF2-133 GEN
Solar/Wind Harmer
4.226
972037AH1-567 GEN1
Adder
0.084
274827FISK ;RP
Adder
3.57
960591AF2-350 GEN
Solar/Wind Harmer
4.586
274775LINCOLN ;6U
Adder
2.842
274776LINCOLN ;7U
Adder
2.842
274777LINCOLN ;8U
Adder
2.842
972227AH1-698 GEN1
Adder
1.192
274687WILL CNTY;4U
Adder
12.733
274687WILL CNTY;4U
Adder
12.733
274675JOLIET 29;7U
Adder
13.952
274675JOLIET 29;7U
Adder
13.453
274731ELWOOD EC;2P
Adder
7.461
274733ELWOOD EC;3P
Adder
7.461
274735ELWOOD EC;4P
Adder
7.461
274728ELWOOD EC;5P
Adder
7.461
970833AG2-524 GEN
Solar/Wind Harmer
3.942
970833AG2-524 GEN
Solar/Wind Harmer
1.834
274746AC1-111 G10
Adder
2.508
274744AC1-111 GEN8
Adder
2.508
24729505KEY G4
Adder
2.834
274823ROCKFORD ;21
Adder
8.489
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.25
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.874
24189902OREGON_CT2
50/50
2.842
23888702TROY G3
50/50
1.9
972253AH1-711 GEN
50/50
58.047
23856402BAYSG1
50/50
1.206
23920202STRYCT
50/50
1.925
241885AC2-103 GEN1
Solar/Wind Harmer
15.652
241858AF1-205_GEN
Solar/Wind Harmer
5.546
241808AF1-120 C
Solar/Wind Harmer
1.217
241840AF1-064_GEN
Solar/Wind Harmer
1.355
972301AH1-735 GEN
Adder
6.637
23906402RICHG1
Adder
1.327
23906502RICHG2&3
Adder
1.324
270361_3
Solar/Wind Harmer
7.399
960841AF2-375 GEN
Solar/Wind Harmer
3.289
970515AG2-329 GEN
Solar/Wind Harmer
10.155
944231AF1-091 GEN
Solar/Wind Harmer
2.497
247522W1-056 GEN
Solar/Wind Harmer
1.426
246936BC-WTG1
Solar/Wind Harmer
2.308
270489AE1-102 GEN1
Solar/Wind Harmer
0.767
270449AD2-020 GEN
Solar/Wind Harmer
1.647
943021AE2-325 GEN
Solar/Wind Harmer
2.14
965421AG1-410 GEN
Solar/Wind Harmer
17.537
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.61
24695305TIMB G C
Solar/Wind Harmer
3.122
24639705ELKHART HY
Adder
0.085
270063AE2-323 C
Solar/Wind Harmer
1.215
247521TR3_G114
Solar/Wind Harmer
1.846
270246TR4_N_V150
Solar/Wind Harmer
0.467
965011AG1-365 GEN
Solar/Wind Harmer
5.341
270462AD2-086
Solar/Wind Harmer
3.647
970373AG2-245 GEN
Solar/Wind Harmer
10.266
270223U2-072_GEN1
Solar/Wind Harmer
0.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
270055AF2-134 C O1
Solar/Wind Harmer
1.451
274751CRETE EC ;1U
Adder
2.308
274754CRETE EC ;4U
Adder
2.308
958381AF2-132 GEN
Solar/Wind Harmer
4.267
964861AG1-349 GEN
Solar/Wind Harmer
3.69
971917AH1-482 GEN
Solar/Wind Harmer
4.258
274723RIVER EC ;12
Adder
8.392
274812UNIV PK N;8U
Adder
2.335
276164X3-005 C
Solar/Wind Harmer
0.326
274801UNIV PARK;4U
Adder
2.678
276776AD2-060 GEN
Solar/Wind Harmer
0.194
940581AE2-045 GEN
Solar/Wind Harmer
4.675
972207SS24-0001
Solar/Wind Harmer
10.104
274773LINCOLN ;4U
Adder
2.842
274774LINCOLN ;5U
Adder
2.842
971605AH1-302 GEN
Solar/Wind Harmer
3.998
274676JOLIET 29;8U
Adder
13.952
941551AE2-152 GEN
Solar/Wind Harmer
2.06
274732ELWOOD EC;7P
Adder
7.461
274674JOLIET 9 ;6U
Adder
6.988
970245AG2-165 GEN
Solar/Wind Harmer
8.074
274871GR RIDGE ;2U
Solar/Wind Harmer
3.47
274745AC1-111 GEN9
Adder
2.508
276691AA1-018 GEN1
Solar/Wind Harmer
0.209
274682WAUKEGAN ;7U
Adder
8.008
274828WAUKEGAN ;BP
Adder
4.917
274822ROCKFORD ;11
Adder
8.551
972235AH1-702 GEN1
Adder
1.096
274761LEE CO EC;2U
Adder
4.005
274766LEE CO EC;7U
Adder
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.243
961971AG1-040 GEN
Solar/Wind Helper
0.336
203835AF1-098 GEN
Solar/Wind Helper
1.324
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
203954AE2-126 C
Solar/Wind Helper
0.22
991182J1586 G
External Queue
26.137367248535156
991177J1571 G
External Queue
15.847536087036133
990142J1224
External Queue
13.940826416015625
990527J1329
External Queue
1.9070898294448853
LAGNLTFEXP_LAGN->PJM
CLTF
4.896
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.089
TVALTFEXP_TVA->PJM
CLTF
2.214
NYPJM->LTFIMP_NY
CLTF
2.051
LGEELTFEXP_LGEE->PJM
CLTF
1.986
WECLTFEXP_WEC->PJM
CLTF
1.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.867
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
6.458
SIGELTFEXP_SIGE->PJM
CLTF
0.166

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.41 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2770.12
MW Contribution:307.32
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.908
23888802TROY G4
50/50
1.906
241996AE2-282_GEN
Solar/Wind Harmer
2.191
971677AH1-339 GEN
Solar/Wind Harmer
6.006
23929302BS-PKR
50/50
2.132
241832AE2-181_GEN
Solar/Wind Harmer
1.988
958321AF2-126 GEN
Solar/Wind Harmer
1.459
23906502RICHG2&3
Adder
1.33
270541AE2-072 C
Solar/Wind Harmer
4.248
270575GUS2 35KV
Solar/Wind Harmer
8.782
970217AG2-149 GEN
Solar/Wind Harmer
22.6
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.76
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.773
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.489
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.384
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.655
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.519
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.304
274724RIVER EC ;11
Adder
8.365
959141AF2-205 GEN
Solar/Wind Harmer
2.821
274802UNIV PARK;5U
Adder
2.711
274826FISK ;BP
Adder
5.082
274800UNIV PARK;3U
Adder
2.702
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.29
276806AD2-047 C O1
Solar/Wind Harmer
4.95
970941AG2-585 GEN
Solar/Wind Harmer
5.784
274772LINCOLN ;3U
Adder
2.867
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.575
276897AD1-100 C
Solar/Wind Harmer
13.3
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.528
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
12.822
970513AG2-328 GEN
Solar/Wind Harmer
8.148
970517AG2-330 GEN
Solar/Wind Harmer
7.39
943121AE2-341 GEN
Solar/Wind Harmer
6.789
943591AF1-030 GEN
Solar/Wind Harmer
4.526
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.081
972236AH1-702 GEN2
Adder
0.962
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.995
962511AG1-100 GEN
Solar/Wind Helper
0.343
203830AF1-094 GEN
Solar/Wind Helper
0.325
959441AF2-235 GEN
Solar/Wind Helper
0.148
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.648
246938BC-WTG3
Solar/Wind Harmer
2.366
246937BC-WTG2
Solar/Wind Harmer
2.326
270007AE1-245 C
Solar/Wind Harmer
3.514
942801AE2-298 GEN
Solar/Wind Harmer
0.89
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
970611AG2-400 GEN
Solar/Wind Harmer
5.384
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.412
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.711
274888KELLY CRK;1U
Solar/Wind Harmer
2.732
274887GEN-1.85
Solar/Wind Harmer
2.466
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.663
274770LINCOLN ;1U
Adder
2.867
274771LINCOLN ;2U
Adder
2.867
972259AH1-714 GEN
Adder
8.76
274674JOLIET 9 ;6U
Adder
7.051
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.148
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274696ROCKY RD ;4P
Adder
5.123
274683WAUKEGAN ;8U
Adder
9.466
274683WAUKEGAN ;8U
Adder
7.98
274764LEE CO EC;5U
Adder
4.052
274765LEE CO EC;6U
Adder
4.052
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.004
972267AH1-718 GEN
Adder
1.797
203947AF1-006 C
Solar/Wind Helper
0.382
203980AG1-197 GEN
Solar/Wind Helper
0.25
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.906
972253AH1-711 GEN
50/50
58.205
23856402BAYSG1
50/50
1.211
23920202STRYCT
50/50
1.932
241885AC2-103 GEN1
Solar/Wind Harmer
15.671
241858AF1-205_GEN
Solar/Wind Harmer
5.566
241808AF1-120 C
Solar/Wind Harmer
1.222
241840AF1-064_GEN
Solar/Wind Harmer
1.361
972301AH1-735 GEN
Adder
6.666
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.33
270361_3
Solar/Wind Harmer
7.454
960841AF2-375 GEN
Solar/Wind Harmer
3.314
970515AG2-329 GEN
Solar/Wind Harmer
10.249
944231AF1-091 GEN
Solar/Wind Harmer
2.514
247522W1-056 GEN
Solar/Wind Harmer
1.44
246936BC-WTG1
Solar/Wind Harmer
2.326
270489AE1-102 GEN1
Solar/Wind Harmer
0.773
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.671
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.146
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.861
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.384
270462AD2-086
Solar/Wind Harmer
3.678
970373AG2-245 GEN
Solar/Wind Harmer
10.352
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.592
270391AF1-285 GEN3
Solar/Wind Harmer
0.592
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.304
964861AG1-349 GEN
Solar/Wind Harmer
3.722
971917AH1-482 GEN
Solar/Wind Harmer
4.295
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.702
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.717
972207SS24-0001
Solar/Wind Harmer
10.194
274773LINCOLN ;4U
Adder
2.867
274774LINCOLN ;5U
Adder
2.867
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.077
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.051
970245AG2-165 GEN
Solar/Wind Harmer
8.148
274871GR RIDGE ;2U
Solar/Wind Harmer
3.502
274745AC1-111 GEN9
Adder
2.531
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.081
274828WAUKEGAN ;BP
Adder
4.962
274822ROCKFORD ;11
Adder
8.631
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.995
241807AE2-176_GEN
Solar/Wind Helper
2.224
961971AG1-040 GEN
Solar/Wind Helper
0.335
203835AF1-098 GEN
Solar/Wind Helper
1.322
203860AG1-193 C
Solar/Wind Helper
0.15
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
203979AG1-198 GEN
Solar/Wind Helper
0.195
241967AE2-285_GEN
Solar/Wind Helper
0.342
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.33
946381AF1-302 GEN
Solar/Wind Helper
0.106
238217AF1-153 C O1
Solar/Wind Helper
0.112
958481AF2-142 GEN
Solar/Wind Harmer
6.677
23867002DVBSG1
50/50
15.56
972211AH1-690 GEN
50/50
307.318
23888502TROY G1
50/50
1.906
23888602TROY G2
50/50
1.906
241886AC2-103 GEN2
Solar/Wind Harmer
15.671
970817AG2-515 GEN
Solar/Wind Harmer
15.816
945411AF1-206 GEN
Solar/Wind Harmer
8.184
945641AF1-229 GEN
Solar/Wind Harmer
3.527
270499AE1-146 GEN
Solar/Wind Harmer
2.102
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.884
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.696
270435AC2-044 GEN
Solar/Wind Harmer
1.189
247607V1-011 GEN
Solar/Wind Harmer
2.343
965041AG1-368 GEN
Solar/Wind Harmer
5.574
965051AG1-369 GEN
Solar/Wind Harmer
2.764
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.12
971771AH1-392 GEN
Solar/Wind Harmer
4.928
971769AH1-391 GEN
Solar/Wind Harmer
5.337
270302AB2-170 GEN
Solar/Wind Harmer
4.422
270317AD1-130_GEN
Solar/Wind Harmer
1.695
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.655
971567AH1-282 GEN
Solar/Wind Harmer
7.54
963791AG1-232 GEN
Solar/Wind Harmer
6.721
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.114
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.36
274811UNIV PK N;7U
Adder
2.355
958391AF2-133 GEN
Solar/Wind Harmer
4.264
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.627
274775LINCOLN ;6U
Adder
2.867
274776LINCOLN ;7U
Adder
2.867
274777LINCOLN ;8U
Adder
2.867
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.848
274687WILL CNTY;4U
Adder
12.848
274675JOLIET 29;7U
Adder
14.077
274675JOLIET 29;7U
Adder
13.575
274731ELWOOD EC;2P
Adder
7.528
274733ELWOOD EC;3P
Adder
7.528
274735ELWOOD EC;4P
Adder
7.528
274728ELWOOD EC;5P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.978
970833AG2-524 GEN
Solar/Wind Harmer
1.85
274746AC1-111 G10
Adder
2.531
274744AC1-111 GEN8
Adder
2.531
24729505KEY G4
Adder
2.861
274823ROCKFORD ;21
Adder
8.568
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.249
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.87
991182J1586 G
External Queue
26.15285873413086
991177J1571 G
External Queue
15.857954978942871
990142J1224
External Queue
13.94876766204834
990527J1329
External Queue
1.9081761837005615
LAGNLTFEXP_LAGN->PJM
CLTF
4.973
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.195
TVALTFEXP_TVA->PJM
CLTF
2.252
NYPJM->LTFIMP_NY
CLTF
2.036
LGEELTFEXP_LGEE->PJM
CLTF
2.013
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.785
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.917
MECLTFEXP_MEC->PJM
CLTF
6.526
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.5 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2733.88
MW Contribution:307.27
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
2.19
971677AH1-339 GEN
Solar/Wind Harmer
5.988
246938BC-WTG3
Solar/Wind Harmer
2.365
246937BC-WTG2
Solar/Wind Harmer
2.325
270007AE1-245 C
Solar/Wind Harmer
3.513
942801AE2-298 GEN
Solar/Wind Harmer
0.889
961051AF2-396 GEN
Solar/Wind Harmer
9.316
961051AF2-396 GEN
Solar/Wind Harmer
4.333
960981AF2-389 GEN
Solar/Wind Harmer
0.871
957891AF2-083 GEN
Solar/Wind Harmer
1.944
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.337
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
15.811
945411AF1-206 GEN
Solar/Wind Harmer
8.18
945641AF1-229 GEN
Solar/Wind Harmer
3.521
270499AE1-146 GEN
Solar/Wind Harmer
2.097
971549AH1-272 GEN
Solar/Wind Harmer
13.494
270297AD1-101 GEN
Solar/Wind Harmer
1.883
944161AF1-084 GEN
Solar/Wind Harmer
1.326
957201AF2-014 GEN
Solar/Wind Harmer
2.695
270435AC2-044 GEN
Solar/Wind Harmer
1.188
247607V1-011 GEN
Solar/Wind Harmer
2.341
965041AG1-368 GEN
Solar/Wind Harmer
5.573
965051AG1-369 GEN
Solar/Wind Harmer
2.763
966831AG1-554 GEN
Solar/Wind Harmer
0.657
971989AH1-539 GEN
Solar/Wind Harmer
7.103
971771AH1-392 GEN
Solar/Wind Harmer
4.929
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270302AB2-170 GEN
Solar/Wind Harmer
4.419
270317AD1-130_GEN
Solar/Wind Harmer
1.694
960681AF2-359 GEN
Solar/Wind Harmer
1.938
971347AH1-153 GEN
Solar/Wind Harmer
7.656
971567AH1-282 GEN
Solar/Wind Harmer
7.507
963791AG1-232 GEN
Solar/Wind Harmer
6.72
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
2.195
270071AF1-092 GEN
Solar/Wind Harmer
7.115
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
4.265
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
4.628
274775LINCOLN ;6U
Adder
2.868
274776LINCOLN ;7U
Adder
2.868
274777LINCOLN ;8U
Adder
2.868
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.979
970833AG2-524 GEN
Solar/Wind Harmer
1.851
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
24729505KEY G4
Adder
2.862
274823ROCKFORD ;21
Adder
8.571
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
1.987
958321AF2-126 GEN
Solar/Wind Harmer
1.458
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
4.244
270575GUS2 35KV
Solar/Wind Harmer
8.76
970217AG2-149 GEN
Solar/Wind Harmer
22.527
270044AE2-322 C
Solar/Wind Harmer
0.862
270404AC1-167 GEN
Solar/Wind Harmer
0.718
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
1.759
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.096
270588AE1-091_GEN
Solar/Wind Harmer
6.477
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0.039
970031AG2-029 GEN
Solar/Wind Harmer
16.631
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
959331AF2-224 GEN
Solar/Wind Harmer
5.383
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.32
270043AE2-236 GEN
Solar/Wind Harmer
2.809
970349AG2-230 GEN
Solar/Wind Harmer
7.656
942871AE2-306 GEN
Solar/Wind Harmer
0.444
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
2.195
972231SS25-0005
Solar/Wind Harmer
4.52
972181SS23-001
Solar/Wind Harmer
2.825
274752CRETE EC ;2U
Adder
2.328
274753CRETE EC ;3U
Adder
2.328
964401AG1-302 GEN
Solar/Wind Harmer
4.305
274724RIVER EC ;11
Adder
8.367
970611AG2-400 GEN
Solar/Wind Harmer
5.383
270526AF1-158 GEN
Solar/Wind Harmer
2.438
24441505OLIV SLR
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
6.413
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0.967
270227U2-072_GEN3
Solar/Wind Harmer
0.967
270228U2-072_GEN4
Solar/Wind Harmer
0.967
270231U2-072_GEN5
Solar/Wind Harmer
0.967
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
2.733
274887GEN-1.85
Solar/Wind Harmer
2.467
276843GEN-1.7
Solar/Wind Harmer
0.265
958011AF2-095 GEN
Solar/Wind Harmer
6.665
274770LINCOLN ;1U
Adder
2.868
274771LINCOLN ;2U
Adder
2.868
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.334
970321AG2-212 GEN
Solar/Wind Harmer
8.15
274847GR RIDGE ;BU
Solar/Wind Harmer
2.304
958481AF2-142 GEN
Solar/Wind Harmer
6.79
274861TOP CROP ;1U
Solar/Wind Harmer
2.743
274862TOP CROP ;2U
Solar/Wind Harmer
2.29
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
972267AH1-718 GEN
Adder
1.798
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
945421AF1-207 GEN
Solar/Wind Harmer
0.181
959141AF2-205 GEN
Solar/Wind Harmer
2.822
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276772AC2-154 GEN
Solar/Wind Harmer
1.291
276806AD2-047 C O1
Solar/Wind Harmer
4.951
970941AG2-585 GEN
Solar/Wind Harmer
5.785
274772LINCOLN ;3U
Adder
2.868
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
13.304
939351AE1-166 GEN
Solar/Wind Harmer
2.718
276893AG1-478 C
Solar/Wind Harmer
0.191
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
12.825
970513AG2-328 GEN
Solar/Wind Harmer
8.15
970517AG2-330 GEN
Solar/Wind Harmer
7.392
943121AE2-341 GEN
Solar/Wind Harmer
6.791
943591AF1-030 GEN
Solar/Wind Harmer
4.527
276694AA1-018 GEN2
Solar/Wind Harmer
2.856
274682WAUKEGAN ;7U
Adder
8.083
972236AH1-702 GEN2
Adder
0.963
274760LEE CO EC;1U
Adder
4.044
274767LEE CO EC;8U
Adder
3.996
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
5.563
241808AF1-120 C
Solar/Wind Harmer
1.221
241840AF1-064_GEN
Solar/Wind Harmer
1.36
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
7.436
960841AF2-375 GEN
Solar/Wind Harmer
3.306
970515AG2-329 GEN
Solar/Wind Harmer
10.216
944231AF1-091 GEN
Solar/Wind Harmer
2.513
247522W1-056 GEN
Solar/Wind Harmer
1.436
246936BC-WTG1
Solar/Wind Harmer
2.325
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
270449AD2-020 GEN
Solar/Wind Harmer
1.659
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
17.664
945111AF1-176 GEN
Solar/Wind Harmer
10.323
270505AE1-170 C O1
Solar/Wind Harmer
8.673
24695305TIMB G C
Solar/Wind Harmer
3.145
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.224
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
965011AG1-365 GEN
Solar/Wind Harmer
5.383
270462AD2-086
Solar/Wind Harmer
3.676
970373AG2-245 GEN
Solar/Wind Harmer
10.354
270223U2-072_GEN1
Solar/Wind Harmer
0.967
270578AF1-285 GEN2
Solar/Wind Harmer
0.591
270391AF1-285 GEN3
Solar/Wind Harmer
0.591
270055AF2-134 C O1
Solar/Wind Harmer
1.463
274751CRETE EC ;1U
Adder
2.328
274754CRETE EC ;4U
Adder
2.328
958381AF2-132 GEN
Solar/Wind Harmer
4.305
964861AG1-349 GEN
Solar/Wind Harmer
3.723
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0.329
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.196
940581AE2-045 GEN
Solar/Wind Harmer
4.718
972207SS24-0001
Solar/Wind Harmer
10.197
274773LINCOLN ;4U
Adder
2.868
274774LINCOLN ;5U
Adder
2.868
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
2.079
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
8.15
274871GR RIDGE ;2U
Solar/Wind Harmer
3.503
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.211
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
274822ROCKFORD ;11
Adder
8.634
972235AH1-702 GEN1
Adder
1.107
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
3.996
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
991182J1586 G
External Queue
26.137367248535156
991177J1571 G
External Queue
15.847536087036133
990142J1224
External Queue
13.940826416015625
990527J1329
External Queue
1.9070898294448853
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.86 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2589.31
MW Contribution:307.1
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.06
970217AG2-149 GEN
Solar/Wind Harmer
4.25
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.264
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.207
945111AF1-176 GEN
Solar/Wind Harmer
3.266
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.509
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.624
965021AG1-366 GEN
Solar/Wind Harmer
1.25
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.282
970349AG2-230 GEN
Solar/Wind Harmer
5.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.349
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.706
274826FISK ;BP
Adder
5.072
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.156
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.878
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.656
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270361_3
Solar/Wind Harmer
4.06
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.751
944231AF1-091 GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.152
965421AG1-410 GEN
Solar/Wind Harmer
12.302
945111AF1-176 GEN
Solar/Wind Harmer
7.189
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.14
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.749
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.209
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
24190002OREGON_ST1
50/50
3.831
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.804
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.176
961051AF2-396 GEN
Solar/Wind Harmer
5.45
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.749
970627AG2-408 GEN
Solar/Wind Harmer
1.125
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.275
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.34
274803UNIV PARK;6U
Adder
2.706
274888KELLY CRK;1U
Solar/Wind Harmer
0.189
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.104
958011AF2-095 GEN
Solar/Wind Harmer
4.64
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
972259AH1-714 GEN
Adder
8.743
274674JOLIET 9 ;6U
Adder
7.038
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.377
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.585
274696ROCKY RD ;4P
Adder
5.113
274695ROCKY RD ;2P
Adder
4.995
274693ROCKY RD ;1P
Adder
4.946
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.448
274683WAUKEGAN ;8U
Adder
7.964
958491AF2-143 GEN
Solar/Wind Harmer
4.684
962691AG1-118 GEN
Solar/Wind Harmer
9.334
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.106
970921AG2-575 GEN
Solar/Wind Harmer
1.035
942991AE2-321 GEN
Solar/Wind Harmer
3.454
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.163
971335AH1-147 GEN
Solar/Wind Harmer
6.163
971341AH1-150 GEN
Solar/Wind Harmer
6.137
971343AH1-151 GEN
Solar/Wind Harmer
6.137
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.044
274765LEE CO EC;6U
Adder
4.044
274762LEE CO EC;3U
Adder
4.035
274763LEE CO EC;4U
Adder
3.996
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
203947AF1-006 C
Solar/Wind Helper
0.381
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.329
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
23867002DVBSG1
50/50
15.559
972211AH1-690 GEN
50/50
307.104
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
11.024
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.494
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.812
965041AG1-368 GEN
Solar/Wind Harmer
3.881
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971989AH1-539 GEN
Solar/Wind Harmer
1.649
971771AH1-392 GEN
Solar/Wind Harmer
3.814
971769AH1-391 GEN
Solar/Wind Harmer
4.151
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.331
971567AH1-282 GEN
Solar/Wind Harmer
5.227
963791AG1-232 GEN
Solar/Wind Harmer
4.679
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.329
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274805UNIV PK N;1U
Adder
2.356
274811UNIV PK N;7U
Adder
2.351
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.595
960591AF2-350 GEN
Solar/Wind Harmer
3.222
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.823
274687WILL CNTY;4U
Adder
12.823
274675JOLIET 29;7U
Adder
14.05
274675JOLIET 29;7U
Adder
13.548
274731ELWOOD EC;2P
Adder
7.514
274733ELWOOD EC;3P
Adder
7.514
274735ELWOOD EC;4P
Adder
7.514
274728ELWOOD EC;5P
Adder
7.514
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.327
274746AC1-111 G10
Adder
2.526
274744AC1-111 GEN8
Adder
2.526
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.623
276882AE2-255 GEN
Solar/Wind Harmer
0.363
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.907
971411AH1-196 GEN
Solar/Wind Harmer
4.626
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
2.855
971171AH1-044 GEN
Solar/Wind Harmer
6.137
274823ROCKFORD ;21
Adder
8.551
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.05
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.885
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.766
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.868
274800UNIV PARK;3U
Adder
2.697
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.826
970941AG2-585 GEN
Solar/Wind Harmer
4.027
274772LINCOLN ;3U
Adder
3.895
972228AH1-698 GEN2
Adder
1.705
274676JOLIET 29;8U
Adder
13.548
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.514
274730ELWOOD EC;6P
Adder
7.514
274734ELWOOD EC;8P
Adder
7.514
274736ELWOOD EC;9P
Adder
7.514
970707AG2-453 GEN
Solar/Wind Harmer
10.416
970513AG2-328 GEN
Solar/Wind Harmer
1.377
970517AG2-330 GEN
Solar/Wind Harmer
8.26
943121AE2-341 GEN
Solar/Wind Harmer
5.284
943591AF1-030 GEN
Solar/Wind Harmer
3.514
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.61
274682WAUKEGAN ;7U
Adder
8.065
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.898
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.137
972236AH1-702 GEN2
Adder
0.96
970571AG2-364 GEN
Solar/Wind Harmer
6.113
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.035
276157O29GEN1
Solar/Wind Harmer
0.485
962511AG1-100 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.324
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.646
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.287
274723RIVER EC ;12
Adder
8.45
274812UNIV PK N;8U
Adder
2.351
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.697
276776AD2-060 GEN
Solar/Wind Harmer
0.336
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.026
274676JOLIET 29;8U
Adder
14.05
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.514
274674JOLIET 9 ;6U
Adder
7.038
970245AG2-165 GEN
Solar/Wind Harmer
1.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276691AA1-018 GEN1
Solar/Wind Harmer
0.382
274682WAUKEGAN ;7U
Adder
8.065
274828WAUKEGAN ;BP
Adder
4.952
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.328
962781AG1-127 GEN
Solar/Wind Harmer
2.956
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.206
959081AF2-199 GEN
Solar/Wind Harmer
3.069
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.614
972235AH1-702 GEN1
Adder
1.104
970569AG2-363 GEN
Solar/Wind Harmer
9.17
970819AG2-516 GEN
Solar/Wind Harmer
3.66
971475AH1-234 GEN
Solar/Wind Harmer
1.477
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.035
274766LEE CO EC;7U
Adder
2.419
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Helper
2.238
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.318
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
991182J1586 G
External Queue
26.137367248535156
991177J1571 G
External Queue
15.847536087036133
990142J1224
External Queue
13.940826416015625
990527J1329
External Queue
1.9070898294448853
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.186
TVALTFEXP_TVA->PJM
CLTF
2.246
NYPJM->LTFIMP_NY
CLTF
2.031
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.692
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.893
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.168

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2580.58
MW Contribution:307.27
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.881
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.806
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.19
961051AF2-396 GEN
Solar/Wind Harmer
5.46
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.756
970627AG2-408 GEN
Solar/Wind Harmer
1.127
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
11.031
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.815
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
0.19
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.105
958011AF2-095 GEN
Solar/Wind Harmer
4.65
274770LINCOLN ;1U
Adder
3.904
274771LINCOLN ;2U
Adder
3.904
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.38
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.737
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.427
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
958491AF2-143 GEN
Solar/Wind Harmer
4.695
962691AG1-118 GEN
Solar/Wind Harmer
9.356
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.113
970921AG2-575 GEN
Solar/Wind Harmer
1.038
942991AE2-321 GEN
Solar/Wind Harmer
3.462
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.177
971335AH1-147 GEN
Solar/Wind Harmer
6.177
971341AH1-150 GEN
Solar/Wind Harmer
6.151
971343AH1-151 GEN
Solar/Wind Harmer
6.151
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
276782AC1-033 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.064
970217AG2-149 GEN
Solar/Wind Harmer
4.257
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.213
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.514
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.629
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.287
970349AG2-230 GEN
Solar/Wind Harmer
5.341
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.925
274753CRETE EC ;3U
Adder
3.925
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.83
970941AG2-585 GEN
Solar/Wind Harmer
4.036
274772LINCOLN ;3U
Adder
3.904
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.127
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
10.439
970513AG2-328 GEN
Solar/Wind Harmer
1.38
970517AG2-330 GEN
Solar/Wind Harmer
8.279
943121AE2-341 GEN
Solar/Wind Harmer
5.296
943591AF1-030 GEN
Solar/Wind Harmer
3.522
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.616
274682WAUKEGAN ;7U
Adder
8.083
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.93
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.151
970571AG2-364 GEN
Solar/Wind Harmer
6.128
972236AH1-702 GEN2
Adder
0.963
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.044
276157O29GEN1
Solar/Wind Harmer
0.487
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
965041AG1-368 GEN
Solar/Wind Harmer
3.888
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971989AH1-539 GEN
Solar/Wind Harmer
1.652
971771AH1-392 GEN
Solar/Wind Harmer
3.821
971769AH1-391 GEN
Solar/Wind Harmer
4.158
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.341
971567AH1-282 GEN
Solar/Wind Harmer
5.238
963791AG1-232 GEN
Solar/Wind Harmer
4.689
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.342
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
3.229
274775LINCOLN ;6U
Adder
3.904
274776LINCOLN ;7U
Adder
3.904
274777LINCOLN ;8U
Adder
3.904
971611AH1-305 GEN
Solar/Wind Harmer
1.922
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.498
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.625
276882AE2-255 GEN
Solar/Wind Harmer
0.364
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.911
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.204
24729505KEY G4
Adder
2.862
971171AH1-044 GEN
Solar/Wind Harmer
6.151
274823ROCKFORD ;21
Adder
8.571
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.897
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.771
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
4.064
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.77
944231AF1-091 GEN
Solar/Wind Harmer
1.241
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.324
945111AF1-176 GEN
Solar/Wind Harmer
7.202
270505AE1-170 C O1
Solar/Wind Harmer
4.236
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.141
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.756
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.224
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.925
274754CRETE EC ;4U
Adder
3.925
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.337
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
3.904
274774LINCOLN ;5U
Adder
3.904
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
1.38
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.383
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.333
962781AG1-127 GEN
Solar/Wind Harmer
2.963
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.227
959081AF2-199 GEN
Solar/Wind Harmer
3.076
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.634
970569AG2-363 GEN
Solar/Wind Harmer
9.191
972235AH1-702 GEN1
Adder
1.107
970819AG2-516 GEN
Solar/Wind Harmer
3.668
971475AH1-234 GEN
Solar/Wind Harmer
1.481
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
2.424
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
991182J1586 G
External Queue
26.137367248535156
991177J1571 G
External Queue
15.847536087036133
990142J1224
External Queue
13.940826416015625
990527J1329
External Queue
1.9070898294448853
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:290.29
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
24.90056610107422
991177J1571 G
External Queue
15.212156295776367
990142J1224
External Queue
13.294119834899902
990527J1329
External Queue
1.8186211585998535
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.03 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2551.84
MW Contribution:290.29
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.157
972211AH1-690 GEN
50/50
290.294
23888502TROY G1
50/50
1.813
23888602TROY G2
50/50
1.813
970817AG2-515 GEN
Solar/Wind Harmer
15.206
945411AF1-206 GEN
Solar/Wind Harmer
8.026
945641AF1-229 GEN
Solar/Wind Harmer
3.439
270499AE1-146 GEN
Solar/Wind Harmer
2.201
971549AH1-272 GEN
Solar/Wind Harmer
13.004
270297AD1-101 GEN
Solar/Wind Harmer
1.871
247607V1-011 GEN
Solar/Wind Harmer
2.303
957201AF2-014 GEN
Solar/Wind Harmer
2.636
270435AC2-044 GEN
Solar/Wind Harmer
1.162
944161AF1-084 GEN
Solar/Wind Harmer
1.282
966831AG1-554 GEN
Solar/Wind Harmer
0.674
971989AH1-539 GEN
Solar/Wind Harmer
7.284
965041AG1-368 GEN
Solar/Wind Harmer
5.453
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.773
270302AB2-170 GEN
Solar/Wind Harmer
4.342
270317AD1-130_GEN
Solar/Wind Harmer
1.665
971769AH1-391 GEN
Solar/Wind Harmer
5.17
971567AH1-282 GEN
Solar/Wind Harmer
7.463
960681AF2-359 GEN
Solar/Wind Harmer
1.878
971347AH1-153 GEN
Solar/Wind Harmer
7.421
963791AG1-232 GEN
Solar/Wind Harmer
6.559
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.129
270071AF1-092 GEN
Solar/Wind Harmer
6.925
274814UNIV PK N;0U
Adder
2.305
274807UNIV PK N;3U
Adder
2.3
274805UNIV PK N;1U
Adder
2.29
274811UNIV PK N;7U
Adder
2.285
958391AF2-133 GEN
Solar/Wind Harmer
4.138
24190002OREGON_ST1
50/50
3.621
24189802OREGON_CT1
50/50
2.747
23888802TROY G4
50/50
1.813
241996AE2-282_GEN
Solar/Wind Harmer
2.149
971677AH1-339 GEN
Solar/Wind Harmer
6.251
270007AE1-245 C
Solar/Wind Harmer
3.456
246938BC-WTG3
Solar/Wind Harmer
2.313
246937BC-WTG2
Solar/Wind Harmer
2.274
942801AE2-298 GEN
Solar/Wind Harmer
0.875
961051AF2-396 GEN
Solar/Wind Harmer
9.012
961051AF2-396 GEN
Solar/Wind Harmer
4.192
960981AF2-389 GEN
Solar/Wind Harmer
0.843
957891AF2-083 GEN
Solar/Wind Harmer
1.881
247620Y3-023
Adder
0.251
270216AD2-079_GEN
Solar/Wind Harmer
0.326
970611AG2-400 GEN
Solar/Wind Harmer
5.249
270526AF1-158 GEN
Solar/Wind Harmer
2.361
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.214
965791AG1-447 GEN
Solar/Wind Harmer
3.179
270224U2-072_GEN2
Solar/Wind Harmer
0.951
270227U2-072_GEN3
Solar/Wind Harmer
0.951
270228U2-072_GEN4
Solar/Wind Harmer
0.951
270231U2-072_GEN5
Solar/Wind Harmer
0.951
274808UNIV PK N;4U
Adder
2.275
274803UNIV PARK;6U
Adder
2.631
274888KELLY CRK;1U
Solar/Wind Harmer
2.651
274887GEN-1.85
Solar/Wind Harmer
2.393
276843GEN-1.7
Solar/Wind Harmer
0.258
958011AF2-095 GEN
Solar/Wind Harmer
6.466
274770LINCOLN ;1U
Adder
2.783
274771LINCOLN ;2U
Adder
2.783
972259AH1-714 GEN
Adder
8.502
942221AE2-234 GEN
Solar/Wind Harmer
0.326
274674JOLIET 9 ;6U
Adder
6.844
970321AG2-212 GEN
Solar/Wind Harmer
7.911
274847GR RIDGE ;BU
Solar/Wind Harmer
2.236
958481AF2-142 GEN
Solar/Wind Harmer
6.589
274696ROCKY RD ;4P
Adder
4.973
274695ROCKY RD ;2P
Adder
4.858
274693ROCKY RD ;1P
Adder
4.81
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.189
274683WAUKEGAN ;8U
Adder
7.746
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
241967AE2-285_GEN
Solar/Wind Helper
0.334
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
274861TOP CROP ;1U
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
0.203
23929302BS-PKR
50/50
2.169
241832AE2-181_GEN
Solar/Wind Harmer
1.949
958321AF2-126 GEN
Solar/Wind Harmer
1.457
23906502RICHG2&3
Adder
1.308
270541AE2-072 C
Solar/Wind Harmer
4.233
270575GUS2 35KV
Solar/Wind Harmer
9.271
970217AG2-149 GEN
Solar/Wind Harmer
22.195
270044AE2-322 C
Solar/Wind Harmer
0.848
270404AC1-167 GEN
Solar/Wind Harmer
0.706
270258AD1-119 GEN
Solar/Wind Harmer
1.728
247604X1-042
Adder
0.256
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.56
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.166
24642205MAYFLWER
Adder
0.346
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
16.144
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.249
965021AG1-366 GEN
Solar/Wind Harmer
1.221
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.733
970349AG2-230 GEN
Solar/Wind Harmer
7.421
942871AE2-306 GEN
Solar/Wind Harmer
0.436
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270535AF1-215 GEN1
Solar/Wind Harmer
2.129
972231SS25-0005
Solar/Wind Harmer
4.384
972181SS23-001
Solar/Wind Harmer
2.74
274752CRETE EC ;2U
Adder
2.258
274753CRETE EC ;3U
Adder
2.258
964401AG1-302 GEN
Solar/Wind Harmer
4.176
274724RIVER EC ;11
Adder
8.116
959141AF2-205 GEN
Solar/Wind Harmer
2.738
274802UNIV PARK;5U
Adder
2.631
274826FISK ;BP
Adder
4.931
274800UNIV PARK;3U
Adder
2.622
972038AH1-567 GEN2
Adder
0.164
276772AC2-154 GEN
Solar/Wind Harmer
1.252
276806AD2-047 C O1
Solar/Wind Harmer
4.804
970941AG2-585 GEN
Solar/Wind Harmer
5.613
274772LINCOLN ;3U
Adder
2.783
972228AH1-698 GEN2
Adder
1.658
274676JOLIET 29;8U
Adder
13.174
276897AD1-100 C
Solar/Wind Harmer
12.909
939351AE1-166 GEN
Solar/Wind Harmer
2.638
276893AG1-478 C
Solar/Wind Harmer
0.186
274730ELWOOD EC;6P
Adder
7.307
274734ELWOOD EC;8P
Adder
7.307
274736ELWOOD EC;9P
Adder
7.307
970707AG2-453 GEN
Solar/Wind Harmer
12.445
274729ELWOOD EC;1P
Adder
7.307
970513AG2-328 GEN
Solar/Wind Harmer
7.911
970517AG2-330 GEN
Solar/Wind Harmer
7.175
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.59
943591AF1-030 GEN
Solar/Wind Harmer
4.393
276694AA1-018 GEN2
Solar/Wind Harmer
2.772
274682WAUKEGAN ;7U
Adder
7.844
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.633
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.495
960591AF2-350 GEN
Solar/Wind Harmer
4.49
274775LINCOLN ;6U
Adder
2.783
274776LINCOLN ;7U
Adder
2.783
274777LINCOLN ;8U
Adder
2.783
972227AH1-698 GEN1
Adder
1.168
274687WILL CNTY;4U
Adder
12.469
274687WILL CNTY;4U
Adder
12.469
274675JOLIET 29;7U
Adder
13.662
274675JOLIET 29;7U
Adder
13.175
274728ELWOOD EC;5P
Adder
7.307
274731ELWOOD EC;2P
Adder
7.307
274733ELWOOD EC;3P
Adder
7.307
274735ELWOOD EC;4P
Adder
7.307
970833AG2-524 GEN
Solar/Wind Harmer
3.861
970833AG2-524 GEN
Solar/Wind Harmer
1.796
274746AC1-111 G10
Adder
2.457
274744AC1-111 GEN8
Adder
2.457
270024AE2-089 GEN
Solar/Wind Harmer
2.062
241886AC2-103 GEN2
Solar/Wind Helper
9.152
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.851
24189902OREGON_CT2
50/50
2.691
23888702TROY G3
50/50
1.813
972253AH1-711 GEN
50/50
55.392
23856402BAYSG1
50/50
1.233
23920202STRYCT
50/50
1.896
241858AF1-205_GEN
Solar/Wind Harmer
5.467
241808AF1-120 C
Solar/Wind Harmer
1.198
241840AF1-064_GEN
Solar/Wind Harmer
1.359
972301AH1-735 GEN
Adder
6.555
23906402RICHG1
Adder
1.311
23906502RICHG2&3
Adder
1.308
270361_3
Solar/Wind Harmer
7.869
960841AF2-375 GEN
Solar/Wind Harmer
3.486
970515AG2-329 GEN
Solar/Wind Harmer
10.065
247522W1-056 GEN
Solar/Wind Harmer
1.487
944231AF1-091 GEN
Solar/Wind Harmer
2.457
246936BC-WTG1
Solar/Wind Harmer
2.274
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.272
270449AD2-020 GEN
Solar/Wind Harmer
1.604
943021AE2-325 GEN
Solar/Wind Harmer
2.085
24695305TIMB G C
Solar/Wind Harmer
3.084
945111AF1-176 GEN
Solar/Wind Harmer
9.989
270505AE1-170 C O1
Solar/Wind Harmer
8.391
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
270063AE2-323 C
Solar/Wind Harmer
1.189
965011AG1-365 GEN
Solar/Wind Harmer
5.249
270462AD2-086
Solar/Wind Harmer
3.612
270223U2-072_GEN1
Solar/Wind Harmer
0.951
270578AF1-285 GEN2
Solar/Wind Harmer
0.581
270391AF1-285 GEN3
Solar/Wind Harmer
0.581
970373AG2-245 GEN
Solar/Wind Harmer
10.039
270055AF2-134 C O1
Solar/Wind Harmer
1.419
274751CRETE EC ;1U
Adder
2.258
274754CRETE EC ;4U
Adder
2.258
958381AF2-132 GEN
Solar/Wind Harmer
4.176
964861AG1-349 GEN
Solar/Wind Harmer
3.612
971917AH1-482 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
8.214
274812UNIV PK N;8U
Adder
2.285
276164X3-005 C
Solar/Wind Harmer
0.319
274801UNIV PARK;4U
Adder
2.622
276776AD2-060 GEN
Solar/Wind Harmer
0.19
940581AE2-045 GEN
Solar/Wind Harmer
4.579
971605AH1-302 GEN
Solar/Wind Harmer
3.915
972207SS24-0001
Solar/Wind Harmer
9.894
274773LINCOLN ;4U
Adder
2.783
274774LINCOLN ;5U
Adder
2.783
274676JOLIET 29;8U
Adder
13.662
941551AE2-152 GEN
Solar/Wind Harmer
2.017
274732ELWOOD EC;7P
Adder
7.307
274674JOLIET 9 ;6U
Adder
6.844
970245AG2-165 GEN
Solar/Wind Harmer
7.911
274871GR RIDGE ;2U
Solar/Wind Harmer
3.399
274745AC1-111 GEN9
Adder
2.457
276691AA1-018 GEN1
Solar/Wind Harmer
0.205
274682WAUKEGAN ;7U
Adder
7.844
274828WAUKEGAN ;BP
Adder
4.817
241885AC2-103 GEN1
Solar/Wind Helper
9.152
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.294
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
24.90056610107422
991177J1571 G
External Queue
15.212156295776367
990142J1224
External Queue
13.294119834899902
990527J1329
External Queue
1.8186211585998535
LAGNLTFEXP_LAGN->PJM
CLTF
4.854
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.172
TVALTFEXP_TVA->PJM
CLTF
2.201
NYPJM->LTFIMP_NY
CLTF
1.985
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.716
MECLTFEXP_MEC->PJM
CLTF
6.343
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B2_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B2_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:287.75
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
991182J1586 G
External Queue
24.65229034423828
991177J1571 G
External Queue
15.044508934020996
990142J1224
External Queue
13.159761428833008
990527J1329
External Queue
1.8002409934997559
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2525.94
MW Contribution:287.75
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
1.922
958321AF2-126 GEN
Solar/Wind Harmer
1.433
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
4.165
270575GUS2 35KV
Solar/Wind Harmer
9.05
970217AG2-149 GEN
Solar/Wind Harmer
21.874
270044AE2-322 C
Solar/Wind Harmer
0.836
270404AC1-167 GEN
Solar/Wind Harmer
0.696
270258AD1-119 GEN
Solar/Wind Harmer
1.704
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.441
958091AF2-103 GEN
Solar/Wind Harmer
0.093
270491AE1-102 GEN2
Solar/Wind Harmer
0.745
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
1.604
270247TR4_N_V136
Solar/Wind Harmer
0.455
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.944
959331AF2-224 GEN
Solar/Wind Harmer
5.181
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.31
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.33
942871AE2-306 GEN
Solar/Wind Harmer
0.43
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.103
972231SS25-0005
Solar/Wind Harmer
4.331
972181SS23-001
Solar/Wind Harmer
2.707
274752CRETE EC ;2U
Adder
2.23
274753CRETE EC ;3U
Adder
2.23
964401AG1-302 GEN
Solar/Wind Harmer
4.125
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
2.704
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.237
276806AD2-047 C O1
Solar/Wind Harmer
4.745
970941AG2-585 GEN
Solar/Wind Harmer
5.544
274772LINCOLN ;3U
Adder
2.748
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
12.75
939351AE1-166 GEN
Solar/Wind Harmer
2.605
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
12.291
970513AG2-328 GEN
Solar/Wind Harmer
7.813
970517AG2-330 GEN
Solar/Wind Harmer
7.086
943121AE2-341 GEN
Solar/Wind Harmer
6.509
943591AF1-030 GEN
Solar/Wind Harmer
4.339
276694AA1-018 GEN2
Solar/Wind Harmer
2.738
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
971617AH1-308 GEN
Solar/Wind Harmer
0.096
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
15.035
945411AF1-206 GEN
Solar/Wind Harmer
7.914
945641AF1-229 GEN
Solar/Wind Harmer
3.393
270499AE1-146 GEN
Solar/Wind Harmer
2.151
971549AH1-272 GEN
Solar/Wind Harmer
12.855
270297AD1-101 GEN
Solar/Wind Harmer
1.842
247607V1-011 GEN
Solar/Wind Harmer
2.271
944161AF1-084 GEN
Solar/Wind Harmer
1.267
957201AF2-014 GEN
Solar/Wind Harmer
2.6
270435AC2-044 GEN
Solar/Wind Harmer
1.147
966831AG1-554 GEN
Solar/Wind Harmer
0.66
971989AH1-539 GEN
Solar/Wind Harmer
7.141
965041AG1-368 GEN
Solar/Wind Harmer
5.38
965051AG1-369 GEN
Solar/Wind Harmer
2.669
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.281
270317AD1-130_GEN
Solar/Wind Harmer
1.641
971769AH1-391 GEN
Solar/Wind Harmer
5.107
960681AF2-359 GEN
Solar/Wind Harmer
1.855
971567AH1-282 GEN
Solar/Wind Harmer
7.347
971347AH1-153 GEN
Solar/Wind Harmer
7.33
963791AG1-232 GEN
Solar/Wind Harmer
6.473
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.103
270071AF1-092 GEN
Solar/Wind Harmer
6.837
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
4.087
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
4.435
274775LINCOLN ;6U
Adder
2.748
274776LINCOLN ;7U
Adder
2.748
274777LINCOLN ;8U
Adder
2.748
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.814
970833AG2-524 GEN
Solar/Wind Harmer
1.774
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
270024AE2-089 GEN
Solar/Wind Harmer
0.078
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
2.119
971677AH1-339 GEN
Solar/Wind Harmer
6.113
270007AE1-245 C
Solar/Wind Harmer
3.406
246938BC-WTG3
Solar/Wind Harmer
2.282
246937BC-WTG2
Solar/Wind Harmer
2.243
942801AE2-298 GEN
Solar/Wind Harmer
0.863
961051AF2-396 GEN
Solar/Wind Harmer
8.904
961051AF2-396 GEN
Solar/Wind Harmer
4.142
960981AF2-389 GEN
Solar/Wind Harmer
0.833
957891AF2-083 GEN
Solar/Wind Harmer
1.858
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.181
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.139
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0.937
270227U2-072_GEN3
Solar/Wind Harmer
0.937
270228U2-072_GEN4
Solar/Wind Harmer
0.937
270231U2-072_GEN5
Solar/Wind Harmer
0.937
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
2.618
274887GEN-1.85
Solar/Wind Harmer
2.364
276843GEN-1.7
Solar/Wind Harmer
0.254
958011AF2-095 GEN
Solar/Wind Harmer
6.387
274770LINCOLN ;1U
Adder
2.748
274771LINCOLN ;2U
Adder
2.748
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.322
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
7.813
274847GR RIDGE ;BU
Solar/Wind Harmer
2.208
958481AF2-142 GEN
Solar/Wind Harmer
6.507
274861TOP CROP ;1U
Solar/Wind Harmer
2.629
274862TOP CROP ;2U
Solar/Wind Harmer
2.195
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
5.389
241808AF1-120 C
Solar/Wind Harmer
1.181
241840AF1-064_GEN
Solar/Wind Harmer
1.337
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
7.682
960841AF2-375 GEN
Solar/Wind Harmer
3.405
970515AG2-329 GEN
Solar/Wind Harmer
9.92
247522W1-056 GEN
Solar/Wind Harmer
1.456
944231AF1-091 GEN
Solar/Wind Harmer
2.424
246936BC-WTG1
Solar/Wind Harmer
2.243
270489AE1-102 GEN1
Solar/Wind Harmer
0.745
965421AG1-410 GEN
Solar/Wind Harmer
17.04
270449AD2-020 GEN
Solar/Wind Harmer
1.585
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
9.87
270505AE1-170 C O1
Solar/Wind Harmer
8.291
24695305TIMB G C
Solar/Wind Harmer
3.042
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.797
270246TR4_N_V150
Solar/Wind Harmer
0.455
270063AE2-323 C
Solar/Wind Harmer
1.174
965011AG1-365 GEN
Solar/Wind Harmer
5.181
270462AD2-086
Solar/Wind Harmer
3.561
270223U2-072_GEN1
Solar/Wind Harmer
0.937
270578AF1-285 GEN2
Solar/Wind Harmer
0.573
270391AF1-285 GEN3
Solar/Wind Harmer
0.573
970373AG2-245 GEN
Solar/Wind Harmer
9.916
270055AF2-134 C O1
Solar/Wind Harmer
1.402
274751CRETE EC ;1U
Adder
2.23
274754CRETE EC ;4U
Adder
2.23
958381AF2-132 GEN
Solar/Wind Harmer
4.125
964861AG1-349 GEN
Solar/Wind Harmer
3.567
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0.315
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.188
940581AE2-045 GEN
Solar/Wind Harmer
4.522
971605AH1-302 GEN
Solar/Wind Harmer
3.867
972207SS24-0001
Solar/Wind Harmer
9.772
274773LINCOLN ;4U
Adder
2.748
274774LINCOLN ;5U
Adder
2.748
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
1.993
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
7.813
274871GR RIDGE ;2U
Solar/Wind Harmer
3.357
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.202
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
991182J1586 G
External Queue
24.65229034423828
991177J1571 G
External Queue
15.044508934020996
990142J1224
External Queue
13.159761428833008
990527J1329
External Queue
1.8002409934997559
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.55 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2494.57
MW Contribution:280.32
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.267
241832AE2-181_GEN
Solar/Wind Harmer
1.96
958321AF2-126 GEN
Solar/Wind Harmer
1.494
23906502RICHG2&3
Adder
1.32
270575GUS2 35KV
Solar/Wind Harmer
10.036
270541AE2-072 C
Solar/Wind Harmer
4.33
970217AG2-149 GEN
Solar/Wind Harmer
22.419
270044AE2-322 C
Solar/Wind Harmer
0.854
270404AC1-167 GEN
Solar/Wind Harmer
0.711
270258AD1-119 GEN
Solar/Wind Harmer
1.74
270588AE1-091_GEN
Solar/Wind Harmer
6.813
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
945111AF1-176 GEN
Solar/Wind Harmer
3.137
270191TR4_S_V150
Solar/Wind Harmer
1.632
270247TR4_N_V136
Solar/Wind Harmer
0.463
24642205MAYFLWER
Adder
0.343
970031AG2-029 GEN
Solar/Wind Harmer
16.05
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.243
965021AG1-366 GEN
Solar/Wind Harmer
1.219
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270043AE2-236 GEN
Solar/Wind Harmer
2.723
970349AG2-230 GEN
Solar/Wind Harmer
7.365
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270377AD1-106 GEN
Solar/Wind Harmer
2.883
270535AF1-215 GEN1
Solar/Wind Harmer
2.114
972231SS25-0005
Solar/Wind Harmer
4.354
972181SS23-001
Solar/Wind Harmer
2.721
274752CRETE EC ;2U
Adder
2.243
274753CRETE EC ;3U
Adder
2.243
964401AG1-302 GEN
Solar/Wind Harmer
4.148
274724RIVER EC ;11
Adder
8.061
959141AF2-205 GEN
Solar/Wind Harmer
2.72
274802UNIV PARK;5U
Adder
2.613
274826FISK ;BP
Adder
4.899
274800UNIV PARK;3U
Adder
2.605
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.244
276806AD2-047 C O1
Solar/Wind Harmer
4.772
970941AG2-585 GEN
Solar/Wind Harmer
5.576
274772LINCOLN ;3U
Adder
2.764
972228AH1-698 GEN2
Adder
1.647
274676JOLIET 29;8U
Adder
13.089
276897AD1-100 C
Solar/Wind Harmer
12.825
939351AE1-166 GEN
Solar/Wind Harmer
2.621
276893AG1-478 C
Solar/Wind Harmer
0.185
274729ELWOOD EC;1P
Adder
7.259
274730ELWOOD EC;6P
Adder
7.259
274734ELWOOD EC;8P
Adder
7.259
274736ELWOOD EC;9P
Adder
7.259
970707AG2-453 GEN
Solar/Wind Harmer
12.364
970513AG2-328 GEN
Solar/Wind Harmer
7.863
970517AG2-330 GEN
Solar/Wind Harmer
7.132
971617AH1-308 GEN
Solar/Wind Harmer
2.555
943121AE2-341 GEN
Solar/Wind Harmer
6.548
943591AF1-030 GEN
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
7.794
962511AG1-100 GEN
Solar/Wind Helper
0.339
203830AF1-094 GEN
Solar/Wind Helper
0.321
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.639
276694AA1-018 GEN2
Solar/Wind Harmer
0.632
23867002DVBSG1
50/50
13.074
972211AH1-690 GEN
50/50
280.319
23888502TROY G1
50/50
1.766
23888602TROY G2
50/50
1.766
970817AG2-515 GEN
Solar/Wind Harmer
14.976
945411AF1-206 GEN
Solar/Wind Harmer
8.075
945641AF1-229 GEN
Solar/Wind Harmer
3.442
270499AE1-146 GEN
Solar/Wind Harmer
2.365
971549AH1-272 GEN
Solar/Wind Harmer
12.831
270297AD1-101 GEN
Solar/Wind Harmer
1.906
966831AG1-554 GEN
Solar/Wind Harmer
0.708
971989AH1-539 GEN
Solar/Wind Harmer
7.656
247607V1-011 GEN
Solar/Wind Harmer
2.323
957201AF2-014 GEN
Solar/Wind Harmer
2.642
270435AC2-044 GEN
Solar/Wind Harmer
1.165
944161AF1-084 GEN
Solar/Wind Harmer
1.269
24190002OREGON_ST1
50/50
3.497
24189802OREGON_CT1
50/50
2.653
23888802TROY G4
50/50
1.766
241996AE2-282_GEN
Solar/Wind Harmer
2.162
971677AH1-339 GEN
Solar/Wind Harmer
6.682
270007AE1-245 C
Solar/Wind Harmer
3.485
942801AE2-298 GEN
Solar/Wind Harmer
0.882
246938BC-WTG3
Solar/Wind Harmer
2.318
246937BC-WTG2
Solar/Wind Harmer
2.279
961051AF2-396 GEN
Solar/Wind Harmer
8.926
961051AF2-396 GEN
Solar/Wind Harmer
4.152
960981AF2-389 GEN
Solar/Wind Harmer
0.835
957891AF2-083 GEN
Solar/Wind Harmer
1.863
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.324
970611AG2-400 GEN
Solar/Wind Harmer
5.243
270526AF1-158 GEN
Solar/Wind Harmer
2.341
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.166
965791AG1-447 GEN
Solar/Wind Harmer
3.155
270224U2-072_GEN2
Solar/Wind Harmer
0.958
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.26
274803UNIV PARK;6U
Adder
2.613
274888KELLY CRK;1U
Solar/Wind Harmer
2.634
274887GEN-1.85
Solar/Wind Harmer
2.378
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.424
274770LINCOLN ;1U
Adder
2.764
274771LINCOLN ;2U
Adder
2.764
942221AE2-234 GEN
Solar/Wind Harmer
0.326
972259AH1-714 GEN
Adder
8.447
274674JOLIET 9 ;6U
Adder
6.799
970321AG2-212 GEN
Solar/Wind Harmer
7.863
274847GR RIDGE ;BU
Solar/Wind Harmer
2.221
274696ROCKY RD ;4P
Adder
4.941
274695ROCKY RD ;2P
Adder
4.827
274693ROCKY RD ;1P
Adder
4.78
274697ROCKY RD ;3P
Adder
1.311
274683WAUKEGAN ;8U
Adder
9.13
274683WAUKEGAN ;8U
Adder
7.697
203947AF1-006 C
Solar/Wind Helper
0.378
203980AG1-197 GEN
Solar/Wind Helper
0.247
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.336
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.324
946381AF1-302 GEN
Solar/Wind Helper
0.104
238217AF1-153 C O1
Solar/Wind Helper
0.11
24189902OREGON_CT2
50/50
2.599
23888702TROY G3
50/50
1.766
972253AH1-711 GEN
50/50
53.942
23856402BAYSG1
50/50
1.288
23920202STRYCT
50/50
1.908
241858AF1-205_GEN
Solar/Wind Harmer
5.509
241808AF1-120 C
Solar/Wind Harmer
1.205
241840AF1-064_GEN
Solar/Wind Harmer
1.394
972301AH1-735 GEN
Adder
6.613
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
270361_3
Solar/Wind Harmer
8.519
960841AF2-375 GEN
Solar/Wind Harmer
3.762
241807AE2-176_GEN
Solar/Wind Harmer
2.793
247522W1-056 GEN
Solar/Wind Harmer
1.578
970515AG2-329 GEN
Solar/Wind Harmer
10.167
944231AF1-091 GEN
Solar/Wind Harmer
2.462
246936BC-WTG1
Solar/Wind Harmer
2.279
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
965421AG1-410 GEN
Solar/Wind Harmer
17.306
270449AD2-020 GEN
Solar/Wind Harmer
1.589
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270428AC2-015 C
Solar/Wind Harmer
3.1
24695305TIMB G C
Solar/Wind Harmer
3.1
945111AF1-176 GEN
Solar/Wind Harmer
9.898
270505AE1-170 C O1
Solar/Wind Harmer
8.313
247521TR3_G114
Solar/Wind Harmer
1.829
270246TR4_N_V150
Solar/Wind Harmer
0.463
24639705ELKHART HY
Adder
0.083
270063AE2-323 C
Solar/Wind Harmer
1.182
965011AG1-365 GEN
Solar/Wind Harmer
5.243
270462AD2-086
Solar/Wind Harmer
3.638
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.966
270055AF2-134 C O1
Solar/Wind Harmer
1.409
274751CRETE EC ;1U
Adder
2.243
274754CRETE EC ;4U
Adder
2.243
958381AF2-132 GEN
Solar/Wind Harmer
4.148
964861AG1-349 GEN
Solar/Wind Harmer
3.588
971917AH1-482 GEN
Solar/Wind Harmer
4.14
274723RIVER EC ;12
Adder
8.158
274812UNIV PK N;8U
Adder
2.27
276164X3-005 C
Solar/Wind Harmer
0.317
274801UNIV PARK;4U
Adder
2.605
940581AE2-045 GEN
Solar/Wind Harmer
4.55
276776AD2-060 GEN
Solar/Wind Harmer
0.189
971605AH1-302 GEN
Solar/Wind Harmer
3.891
972207SS24-0001
Solar/Wind Harmer
9.829
274773LINCOLN ;4U
Adder
2.764
274774LINCOLN ;5U
Adder
2.764
274676JOLIET 29;8U
Adder
13.573
941551AE2-152 GEN
Solar/Wind Harmer
2.004
274732ELWOOD EC;7P
Adder
7.259
274674JOLIET 9 ;6U
Adder
6.799
970245AG2-165 GEN
Solar/Wind Harmer
7.863
274871GR RIDGE ;2U
Solar/Wind Harmer
3.377
970905AG2-564 GEN
Solar/Wind Harmer
2.194
274745AC1-111 GEN9
Adder
2.441
274682WAUKEGAN ;7U
Adder
7.794
274828WAUKEGAN ;BP
Adder
4.786
241885AC2-103 GEN1
Solar/Wind Helper
9.447
961971AG1-040 GEN
Solar/Wind Helper
0.332
203835AF1-098 GEN
Solar/Wind Helper
1.307
203860AG1-193 C
Solar/Wind Helper
0.148
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
276691AA1-018 GEN1
Solar/Wind Harmer
0.047
965041AG1-368 GEN
Solar/Wind Harmer
5.468
965051AG1-369 GEN
Solar/Wind Harmer
2.716
971771AH1-392 GEN
Solar/Wind Harmer
4.733
270302AB2-170 GEN
Solar/Wind Harmer
4.373
270317AD1-130_GEN
Solar/Wind Harmer
1.676
971769AH1-391 GEN
Solar/Wind Harmer
5.127
971567AH1-282 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
1.863
971347AH1-153 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
6.558
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
270536AF1-215 GEN2
Solar/Wind Harmer
2.114
270071AF1-092 GEN
Solar/Wind Harmer
6.904
958391AF2-133 GEN
Solar/Wind Harmer
4.11
274814UNIV PK N;0U
Adder
2.289
274807UNIV PK N;3U
Adder
2.285
274805UNIV PK N;1U
Adder
2.275
274811UNIV PK N;7U
Adder
2.27
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.472
960591AF2-350 GEN
Solar/Wind Harmer
4.461
274775LINCOLN ;6U
Adder
2.764
274776LINCOLN ;7U
Adder
2.764
274777LINCOLN ;8U
Adder
2.764
972227AH1-698 GEN1
Adder
1.16
274687WILL CNTY;4U
Adder
12.387
274687WILL CNTY;4U
Adder
12.387
274675JOLIET 29;7U
Adder
13.573
274675JOLIET 29;7U
Adder
13.089
274731ELWOOD EC;2P
Adder
7.259
274733ELWOOD EC;3P
Adder
7.259
274735ELWOOD EC;4P
Adder
7.259
274728ELWOOD EC;5P
Adder
7.259
270024AE2-089 GEN
Solar/Wind Harmer
2.063
970833AG2-524 GEN
Solar/Wind Harmer
3.836
970833AG2-524 GEN
Solar/Wind Harmer
1.784
274746AC1-111 G10
Adder
2.441
274744AC1-111 GEN8
Adder
2.441
241886AC2-103 GEN2
Solar/Wind Helper
9.447
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.858
991182J1586 G
External Queue
24.279396057128906
991177J1571 G
External Queue
14.956707954406738
990142J1224
External Queue
12.976524353027344
990527J1329
External Queue
1.7751743793487549
LAGNLTFEXP_LAGN->PJM
CLTF
4.838
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.167
TVALTFEXP_TVA->PJM
CLTF
2.196
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CPLELTFEXP_CPLE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.653
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.607
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.701
MECLTFEXP_MEC->PJM
CLTF
6.308
SIGELTFEXP_SIGE->PJM
CLTF
0.164

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2249.01
MW Contribution:287.75
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
14.11
972211AH1-690 GEN
50/50
287.754
23888502TROY G1
50/50
1.796
23888602TROY G2
50/50
1.796
970817AG2-515 GEN
Solar/Wind Harmer
10.489
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
10.011
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.735
971989AH1-539 GEN
Solar/Wind Harmer
1.661
965041AG1-368 GEN
Solar/Wind Harmer
3.753
965051AG1-369 GEN
Solar/Wind Harmer
1.862
971771AH1-392 GEN
Solar/Wind Harmer
3.655
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.502
971769AH1-391 GEN
Solar/Wind Harmer
3.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.126
971347AH1-153 GEN
Solar/Wind Harmer
5.114
963791AG1-232 GEN
Solar/Wind Harmer
4.516
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.095
274814UNIV PK N;0U
Adder
2.277
274807UNIV PK N;3U
Adder
2.272
274805UNIV PK N;1U
Adder
2.262
274811UNIV PK N;7U
Adder
2.257
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.452
960591AF2-350 GEN
Solar/Wind Harmer
3.094
971611AH1-305 GEN
Solar/Wind Harmer
1.842
274775LINCOLN ;6U
Adder
3.741
274776LINCOLN ;7U
Adder
3.741
274777LINCOLN ;8U
Adder
3.741
972227AH1-698 GEN1
Adder
1.153
274687WILL CNTY;4U
Adder
12.315
274687WILL CNTY;4U
Adder
12.315
274675JOLIET 29;7U
Adder
13.494
274675JOLIET 29;7U
Adder
13.012
274731ELWOOD EC;2P
Adder
7.217
274733ELWOOD EC;3P
Adder
7.217
24190002OREGON_ST1
50/50
3.59
24189802OREGON_CT1
50/50
2.723
23888802TROY G4
50/50
1.796
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.601
970621AG2-405 GEN
Solar/Wind Harmer
0.845
970623AG2-406 GEN
Solar/Wind Harmer
0.78
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.827
961051AF2-396 GEN
Solar/Wind Harmer
5.218
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.248
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.614
970627AG2-408 GEN
Solar/Wind Harmer
1.084
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.283
965791AG1-447 GEN
Solar/Wind Harmer
3.141
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.247
274803UNIV PARK;6U
Adder
2.599
274888KELLY CRK;1U
Solar/Wind Harmer
0.182
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.456
274770LINCOLN ;1U
Adder
3.741
274771LINCOLN ;2U
Adder
3.741
972259AH1-714 GEN
Adder
8.397
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.759
970321AG2-212 GEN
Solar/Wind Harmer
1.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.54
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.409
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.562
274696ROCKY RD ;4P
Adder
4.912
274695ROCKY RD ;2P
Adder
4.798
274693ROCKY RD ;1P
Adder
4.751
274697ROCKY RD ;3P
Adder
1.303
274683WAUKEGAN ;8U
Adder
9.076
274683WAUKEGAN ;8U
Adder
7.65
203947AF1-006 C
Solar/Wind Helper
0.369
203980AG1-197 GEN
Solar/Wind Helper
0.241
203979AG1-198 GEN
Solar/Wind Helper
0.188
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.111
23906502RICHG2&3
Adder
1.289
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.199
970217AG2-149 GEN
Solar/Wind Harmer
4.133
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.253
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.195
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.128
24642205MAYFLWER
Adder
0.342
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.41
959331AF2-224 GEN
Solar/Wind Harmer
2.53
965021AG1-366 GEN
Solar/Wind Harmer
1.205
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.196
970349AG2-230 GEN
Solar/Wind Harmer
5.114
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.76
274753CRETE EC ;3U
Adder
3.76
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.016
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.599
274826FISK ;BP
Adder
4.871
274800UNIV PARK;3U
Adder
2.59
24189902OREGON_CT2
50/50
2.668
23888702TROY G3
50/50
1.796
972253AH1-711 GEN
50/50
54.848
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.869
241858AF1-205_GEN
Solar/Wind Harmer
3.76
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.461
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.289
270361_3
Solar/Wind Harmer
4.199
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.4
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.197
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.06
945111AF1-176 GEN
Solar/Wind Harmer
6.886
270505AE1-170 C O1
Solar/Wind Harmer
4.049
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.614
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.918
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.76
274754CRETE EC ;4U
Adder
3.76
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.117
274723RIVER EC ;12
Adder
8.113
274812UNIV PK N;8U
Adder
2.257
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.59
276776AD2-060 GEN
Solar/Wind Harmer
0.323
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.867
274773LINCOLN ;4U
Adder
3.741
274774LINCOLN ;5U
Adder
3.741
274676JOLIET 29;8U
Adder
13.494
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.217
274674JOLIET 9 ;6U
Adder
6.759
970245AG2-165 GEN
Solar/Wind Harmer
1.323
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
276691AA1-018 GEN1
Solar/Wind Harmer
0.367
274682WAUKEGAN ;7U
Adder
7.748
274828WAUKEGAN ;BP
Adder
4.757
241885AC2-103 GEN1
Solar/Wind Helper
9.126
961971AG1-040 GEN
Solar/Wind Helper
0.324
203835AF1-098 GEN
Solar/Wind Helper
1.276
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.764
254303AC2-168 GEN
Solar/Wind Helper
0.074
972038AH1-567 GEN2
Adder
0.162
276806AD2-047 C O1
Solar/Wind Harmer
1.753
970941AG2-585 GEN
Solar/Wind Harmer
3.868
274772LINCOLN ;3U
Adder
3.741
972228AH1-698 GEN2
Adder
1.638
274676JOLIET 29;8U
Adder
13.012
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.217
274730ELWOOD EC;6P
Adder
7.217
274734ELWOOD EC;8P
Adder
7.217
274736ELWOOD EC;9P
Adder
7.217
970707AG2-453 GEN
Solar/Wind Harmer
10.005
970513AG2-328 GEN
Solar/Wind Harmer
1.323
970517AG2-330 GEN
Solar/Wind Harmer
7.937
943121AE2-341 GEN
Solar/Wind Harmer
5.076
943591AF1-030 GEN
Solar/Wind Harmer
3.375
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.521
274682WAUKEGAN ;7U
Adder
7.748
962511AG1-100 GEN
Solar/Wind Helper
0.331
203830AF1-094 GEN
Solar/Wind Helper
0.313
959441AF2-235 GEN
Solar/Wind Helper
0.142
254305AE2-115 C
Solar/Wind Helper
0.109
241801AE1-079 GEN
Solar/Wind Helper
0.128
241967AE2-285_GEN
Solar/Wind Helper
0.329
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.317
274735ELWOOD EC;4P
Adder
7.217
274728ELWOOD EC;5P
Adder
7.217
970833AG2-524 GEN
Solar/Wind Harmer
3.353
970833AG2-524 GEN
Solar/Wind Harmer
2.235
274746AC1-111 G10
Adder
2.426
274744AC1-111 GEN8
Adder
2.426
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241886AC2-103 GEN2
Solar/Wind Helper
9.126
241982AE2-343 S C
Solar/Wind Helper
0.114
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.24
241997AF1-093 GEN
Solar/Wind Helper
0.126
203804AE2-113_GEN
Solar/Wind Helper
0.838
991182J1586 G
External Queue
24.65229034423828
991177J1571 G
External Queue
15.044508934020996
990142J1224
External Queue
13.159761428833008
990527J1329
External Queue
1.8002409934997559
LAGNLTFEXP_LAGN->PJM
CLTF
4.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
TVALTFEXP_TVA->PJM
CLTF
2.173
NYPJM->LTFIMP_NY
CLTF
1.957
LGEELTFEXP_LGEE->PJM
CLTF
1.943
WECLTFEXP_WEC->PJM
CLTF
1.608
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.603
MECLTFEXP_MEC->PJM
CLTF
6.264
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:275.12
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.432
24189802OREGON_CT1
50/50
2.603
23888802TROY G4
50/50
1.736
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.655
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.246
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.242
965791AG1-447 GEN
Solar/Wind Harmer
3.111
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.374
274808UNIV PK N;4U
Adder
2.229
274803UNIV PARK;6U
Adder
2.577
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
23867002DVBSG1
50/50
12.729
972211AH1-690 GEN
50/50
275.118
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.844
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.772
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965041AG1-368 GEN
Solar/Wind Harmer
3.769
965051AG1-369 GEN
Solar/Wind Harmer
1.872
971771AH1-392 GEN
Solar/Wind Harmer
3.617
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
23929302BS-PKR
50/50
2.254
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.306
270575GUS2 35KV
Solar/Wind Harmer
4.656
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247604X1-042
Adder
0.249
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
3.093
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.338
970031AG2-029 GEN
Solar/Wind Harmer
2.393
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.528
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
24189902OREGON_CT2
50/50
2.551
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
23856402BAYSG1
50/50
1.281
23920202STRYCT
50/50
1.886
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.539
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
4.656
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.569
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
965421AG1-410 GEN
Solar/Wind Harmer
11.925
971653AH1-327 GEN
Solar/Wind Harmer
0.506
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.067
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.424
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274776LINCOLN ;7U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
972227AH1-698 GEN1
Adder
1.144
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274735ELWOOD EC;4P
Adder
7.16
274728ELWOOD EC;5P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
274746AC1-111 G10
Adder
2.408
274744AC1-111 GEN8
Adder
2.408
241886AC2-103 GEN2
Solar/Wind Helper
9.503
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
203846AF2-130 C
Solar/Wind Helper
0.243
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.728
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.95
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.577
274826FISK ;BP
Adder
4.831
274800UNIV PARK;3U
Adder
2.569
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.739
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
972228AH1-698 GEN2
Adder
1.625
274676JOLIET 29;8U
Adder
12.909
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274729ELWOOD EC;1P
Adder
7.16
274730ELWOOD EC;6P
Adder
7.16
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
971617AH1-308 GEN
Solar/Wind Harmer
2.523
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
276694AA1-018 GEN2
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.335
203830AF1-094 GEN
Solar/Wind Helper
0.317
959441AF2-235 GEN
Solar/Wind Helper
0.144
254305AE2-115 C
Solar/Wind Helper
0.11
20334926Z1-069 C
Solar/Wind Helper
0.632
972259AH1-714 GEN
Adder
8.331
274674JOLIET 9 ;6U
Adder
6.706
970321AG2-212 GEN
Solar/Wind Harmer
1.313
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241967AE2-285_GEN
Solar/Wind Helper
0.332
241801AE1-079 GEN
Solar/Wind Helper
0.129
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
946381AF1-302 GEN
Solar/Wind Helper
0.103
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.035
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.611
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.083
274723RIVER EC ;12
Adder
8.046
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
274676JOLIET 29;8U
Adder
13.387
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.074
991182J1586 G
External Queue
23.868927001953125
991177J1571 G
External Queue
14.724894523620605
990142J1224
External Queue
12.759525299072266
990527J1329
External Queue
1.745489239692688
LAGNLTFEXP_LAGN->PJM
CLTF
4.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
TVALTFEXP_TVA->PJM
CLTF
2.168
NYPJM->LTFIMP_NY
CLTF
1.977
LGEELTFEXP_LGEE->PJM
CLTF
1.944
WECLTFEXP_WEC->PJM
CLTF
1.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
MECLTFEXP_MEC->PJM
CLTF
6.223
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 02DUALR+-02ROBERT 138.0 kV Ckt 1 line l/o AEP_P4_#8396_05OHIOCT 345_M_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8396_05OHIOCT 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:226.88
MW Contribution:23.04
Bus #Bus NameTypeMW Contribution
241847AF2-150_GEN
Solar/Wind Harmer
3.592
970515AG2-329 GEN
Solar/Wind Harmer
7.958
241813AF1-122_GEN
Solar/Wind Harmer
2.825
961961AG1-039 GEN
Solar/Wind Harmer
2.478
970217AG2-149 GEN
Solar/Wind Harmer
17.549
970065AG2-057 GEN
Solar/Wind Harmer
0.441
970179AG2-119 GEN
Solar/Wind Harmer
48.028
971567AH1-282 GEN
Solar/Wind Harmer
9.572
972211AH1-690 GEN
Adder
23.037
241960AC2-195 GEN
Solar/Wind Harmer
16.693
971201AH1-060 GEN
Solar/Wind Harmer
0.883
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.169
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.52
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.118
G-007ALTFEXP_G-007A->PJM
CMTX
0.056
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.399
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.159
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.937

Details for 02DUALR+-02ROBERT 138.0 kV Ckt 1 line l/o AEP_P4_#16815_05OHIOCT 345_M2_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16815_05OHIOCT 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.52 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:226.81
MW Contribution:23.04
Bus #Bus NameTypeMW Contribution
241847AF2-150_GEN
Solar/Wind Harmer
3.592
970515AG2-329 GEN
Solar/Wind Harmer
7.958
241813AF1-122_GEN
Solar/Wind Harmer
2.825
970179AG2-119 GEN
Solar/Wind Harmer
48.028
971567AH1-282 GEN
Solar/Wind Harmer
9.572
972211AH1-690 GEN
Adder
23.037
961961AG1-039 GEN
Solar/Wind Harmer
2.478
970217AG2-149 GEN
Solar/Wind Harmer
17.549
970065AG2-057 GEN
Solar/Wind Harmer
0.441
241960AC2-195 GEN
Solar/Wind Harmer
16.693
971201AH1-060 GEN
Solar/Wind Harmer
0.883
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.169
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.52
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.118
G-007ALTFEXP_G-007A->PJM
CMTX
0.056
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.399
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.159
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.937

Details for 02DUALR+-02ROBERT 138.0 kV Ckt 1 line l/o ATSI_P2-3_OES-138-020_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02DUALR+-02ROBERT 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OES-138-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.07 %
Rating:209.0 MVA
Rating Type:B
MVA to Mitigate:219.59
MW Contribution:20.84
Bus #Bus NameTypeMW Contribution
241847AF2-150_GEN
Solar/Wind Harmer
4.134
970515AG2-329 GEN
Solar/Wind Harmer
7.202
241813AF1-122_GEN
Solar/Wind Harmer
2.851
961961AG1-039 GEN
Solar/Wind Harmer
2.852
970217AG2-149 GEN
Solar/Wind Harmer
15.88
970065AG2-057 GEN
Solar/Wind Harmer
0.446
970179AG2-119 GEN
Solar/Wind Harmer
39.36
971567AH1-282 GEN
Solar/Wind Harmer
7.146
972211AH1-690 GEN
Adder
20.839
241960AC2-195 GEN
Solar/Wind Harmer
13.681
971201AH1-060 GEN
Solar/Wind Harmer
0.891
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.224
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.119
G-007ALTFEXP_G-007A->PJM
CMTX
0.202
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.719
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.555
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.081
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.712
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.375

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-025_BDR_A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-025_BDR_A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.1 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:149.29
MW Contribution:28.95
Bus #Bus NameTypeMW Contribution
966311AG1-500 GEN
Adder
14.234
957071AF2-004 GEN
Adder
1.219
274676JOLIET 29;8U
Adder
1.721
274729ELWOOD EC;1P
Adder
0.955
274730ELWOOD EC;6P
Adder
0.955
274734ELWOOD EC;8P
Adder
0.955
274736ELWOOD EC;9P
Adder
0.955
274676JOLIET 29;8U
Adder
1.785
274732ELWOOD EC;7P
Adder
0.955
972211AH1-690 GEN
Adder
28.946
274675JOLIET 29;7U
Adder
1.785
274675JOLIET 29;7U
Adder
1.721
274731ELWOOD EC;2P
Adder
0.955
274733ELWOOD EC;3P
Adder
0.955
274735ELWOOD EC;4P
Adder
0.955
274728ELWOOD EC;5P
Adder
0.955
LAGNLTFEXP_LAGN->PJM
CLTF
0.688
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.378
TVALTFEXP_TVA->PJM
CLTF
0.318
NYPJM->LTFIMP_NY
CLTF
0.356
LGEELTFEXP_LGEE->PJM
CLTF
0.283
WECLTFEXP_WEC->PJM
CLTF
0.214
CPLELTFEXP_CPLE->PJM
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.259
MECLTFEXP_MEC->PJM
CLTF
0.846
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P7-1_CEI-345-010_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_CEI-345-010_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:143.95
MW Contribution:29.47
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
Adder
29.47
274675JOLIET 29;7U
Adder
1.813
274675JOLIET 29;7U
Adder
1.748
274731ELWOOD EC;2P
Adder
0.97
274733ELWOOD EC;3P
Adder
0.97
274735ELWOOD EC;4P
Adder
0.97
274728ELWOOD EC;5P
Adder
0.97
966311AG1-500 GEN
Adder
14.502
957071AF2-004 GEN
Adder
1.241
274676JOLIET 29;8U
Adder
1.748
274729ELWOOD EC;1P
Adder
0.97
274730ELWOOD EC;6P
Adder
0.97
274734ELWOOD EC;8P
Adder
0.97
274736ELWOOD EC;9P
Adder
0.97
274676JOLIET 29;8U
Adder
1.813
274732ELWOOD EC;7P
Adder
0.97
LAGNLTFEXP_LAGN->PJM
CLTF
0.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.381
TVALTFEXP_TVA->PJM
CLTF
0.323
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.287
WECLTFEXP_WEC->PJM
CLTF
0.217
CPLELTFEXP_CPLE->PJM
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.463
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.276
MECLTFEXP_MEC->PJM
CLTF
0.859
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P1-2_CEI-345-701_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_CEI-345-701_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.07 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:140.01
MW Contribution:30.05
Bus #Bus NameTypeMW Contribution
966311AG1-500 GEN
Adder
14.826
957071AF2-004 GEN
Adder
1.269
274676JOLIET 29;8U
Adder
1.766
274729ELWOOD EC;1P
Adder
0.979
274730ELWOOD EC;6P
Adder
0.979
274734ELWOOD EC;8P
Adder
0.979
274736ELWOOD EC;9P
Adder
0.979
972211AH1-690 GEN
Adder
30.051
274675JOLIET 29;7U
Adder
1.831
274675JOLIET 29;7U
Adder
1.766
274731ELWOOD EC;2P
Adder
0.979
274733ELWOOD EC;3P
Adder
0.979
274735ELWOOD EC;4P
Adder
0.979
274728ELWOOD EC;5P
Adder
0.979
274676JOLIET 29;8U
Adder
1.831
274732ELWOOD EC;7P
Adder
0.979
LAGNLTFEXP_LAGN->PJM
CLTF
0.699
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.373
TVALTFEXP_TVA->PJM
CLTF
0.323
NYPJM->LTFIMP_NY
CLTF
0.345
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.493
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.629
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.866
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-002H_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-002H_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.07 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:140.01
MW Contribution:30.05
Bus #Bus NameTypeMW Contribution
966311AG1-500 GEN
Adder
14.826
274676JOLIET 29;8U
Adder
1.831
274732ELWOOD EC;7P
Adder
0.979
972211AH1-690 GEN
Adder
30.051
274675JOLIET 29;7U
Adder
1.831
274675JOLIET 29;7U
Adder
1.766
274731ELWOOD EC;2P
Adder
0.979
274733ELWOOD EC;3P
Adder
0.979
274735ELWOOD EC;4P
Adder
0.979
274728ELWOOD EC;5P
Adder
0.979
957071AF2-004 GEN
Adder
1.269
274676JOLIET 29;8U
Adder
1.766
274729ELWOOD EC;1P
Adder
0.979
274730ELWOOD EC;6P
Adder
0.979
274734ELWOOD EC;8P
Adder
0.979
274736ELWOOD EC;9P
Adder
0.979
LAGNLTFEXP_LAGN->PJM
CLTF
0.699
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.373
TVALTFEXP_TVA->PJM
CLTF
0.323
NYPJM->LTFIMP_NY
CLTF
0.345
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.493
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.629
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.866
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-018_BDR_A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-018_BDR_A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:139.3
MW Contribution:30.09
Bus #Bus NameTypeMW Contribution
274676JOLIET 29;8U
Adder
1.832
274732ELWOOD EC;7P
Adder
0.98
957071AF2-004 GEN
Adder
1.271
274676JOLIET 29;8U
Adder
1.766
274729ELWOOD EC;1P
Adder
0.98
274730ELWOOD EC;6P
Adder
0.98
274734ELWOOD EC;8P
Adder
0.98
274736ELWOOD EC;9P
Adder
0.98
972211AH1-690 GEN
Adder
30.089
274675JOLIET 29;7U
Adder
1.832
274675JOLIET 29;7U
Adder
1.766
274731ELWOOD EC;2P
Adder
0.98
274733ELWOOD EC;3P
Adder
0.98
274735ELWOOD EC;4P
Adder
0.98
274728ELWOOD EC;5P
Adder
0.98
966311AG1-500 GEN
Adder
14.848
LAGNLTFEXP_LAGN->PJM
CLTF
0.699
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.373
TVALTFEXP_TVA->PJM
CLTF
0.323
NYPJM->LTFIMP_NY
CLTF
0.344
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.219
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.493
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.278
MECLTFEXP_MEC->PJM
CLTF
0.867
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P7-1_CEI-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_CEI-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:138.02
MW Contribution:29.83
Bus #Bus NameTypeMW Contribution
966311AG1-500 GEN
Adder
14.704
957071AF2-004 GEN
Adder
1.259
274676JOLIET 29;8U
Adder
1.753
274729ELWOOD EC;1P
Adder
0.973
274730ELWOOD EC;6P
Adder
0.973
274734ELWOOD EC;8P
Adder
0.973
274736ELWOOD EC;9P
Adder
0.973
972211AH1-690 GEN
Adder
29.833
274675JOLIET 29;7U
Adder
1.818
274675JOLIET 29;7U
Adder
1.753
274731ELWOOD EC;2P
Adder
0.973
274733ELWOOD EC;3P
Adder
0.973
274735ELWOOD EC;4P
Adder
0.973
274728ELWOOD EC;5P
Adder
0.973
274676JOLIET 29;8U
Adder
1.818
274732ELWOOD EC;7P
Adder
0.973
LAGNLTFEXP_LAGN->PJM
CLTF
0.695
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.371
TVALTFEXP_TVA->PJM
CLTF
0.321
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.286
WECLTFEXP_WEC->PJM
CLTF
0.218
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.456
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.86
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-002I_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-002I_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.53 %
Rating:132.0 MVA
Rating Type:B
MVA to Mitigate:137.98
MW Contribution:29.83
Bus #Bus NameTypeMW Contribution
966311AG1-500 GEN
Adder
14.704
274676JOLIET 29;8U
Adder
1.818
274732ELWOOD EC;7P
Adder
0.973
972211AH1-690 GEN
Adder
29.833
274675JOLIET 29;7U
Adder
1.818
274675JOLIET 29;7U
Adder
1.753
274731ELWOOD EC;2P
Adder
0.973
274733ELWOOD EC;3P
Adder
0.973
274735ELWOOD EC;4P
Adder
0.973
274728ELWOOD EC;5P
Adder
0.973
957071AF2-004 GEN
Adder
1.259
274676JOLIET 29;8U
Adder
1.753
274729ELWOOD EC;1P
Adder
0.973
274730ELWOOD EC;6P
Adder
0.973
274734ELWOOD EC;8P
Adder
0.973
274736ELWOOD EC;9P
Adder
0.973
LAGNLTFEXP_LAGN->PJM
CLTF
0.695
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.371
TVALTFEXP_TVA->PJM
CLTF
0.321
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.286
WECLTFEXP_WEC->PJM
CLTF
0.218
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.456
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.27
MECLTFEXP_MEC->PJM
CLTF
0.86
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02GALION-02GALION 345.0/138.0 kV Ckt 3 transformer l/o ATSI_P2-3_OES-138-021_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02GALION-02GALION 345.0/138.0 kV Ckt 3 transformer
Contingency Name:
ATSI_P2-3_OES-138-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.25 %
Rating:417.0 MVA
Rating Type:B
MVA to Mitigate:430.54
MW Contribution:40.09
Bus #Bus NameTypeMW Contribution
971567AH1-282 GEN
Solar/Wind Harmer
21.359
945641AF1-229 GEN
Solar/Wind Harmer
3.307
972211AH1-690 GEN
Adder
40.094
241960AC2-195 GEN
Solar/Wind Helper
4.36
970217AG2-149 GEN
Solar/Wind Harmer
46.106
970515AG2-329 GEN
Solar/Wind Harmer
20.909
958961AF2-187 GEN
Solar/Wind Helper
2.2
LAGNLTFEXP_LAGN->PJM
CLTF
0.692
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.317
TVALTFEXP_TVA->PJM
CLTF
0.31
NYPJM->LTFIMP_NY
CLTF
0.231
LGEELTFEXP_LGEE->PJM
CLTF
0.258
WECLTFEXP_WEC->PJM
CLTF
0.24
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.136
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.209
MECLTFEXP_MEC->PJM
CLTF
0.927
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02GALION-02GALION 345.0/138.0 kV Ckt 4 transformer l/o ATSI_P2-3_OES-138-018_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02GALION-02GALION 345.0/138.0 kV Ckt 4 transformer
Contingency Name:
ATSI_P2-3_OES-138-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.79 %
Rating:411.0 MVA
Rating Type:B
MVA to Mitigate:430.69
MW Contribution:40.11
Bus #Bus NameTypeMW Contribution
241960AC2-195 GEN
Solar/Wind Helper
4.362
971567AH1-282 GEN
Solar/Wind Harmer
21.366
945641AF1-229 GEN
Solar/Wind Harmer
3.308
972211AH1-690 GEN
Adder
40.107
970217AG2-149 GEN
Solar/Wind Harmer
46.122
970515AG2-329 GEN
Solar/Wind Harmer
20.916
958961AF2-187 GEN
Solar/Wind Helper
2.201
LAGNLTFEXP_LAGN->PJM
CLTF
0.692
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.317
TVALTFEXP_TVA->PJM
CLTF
0.31
NYPJM->LTFIMP_NY
CLTF
0.231
LGEELTFEXP_LGEE->PJM
CLTF
0.258
WECLTFEXP_WEC->PJM
CLTF
0.24
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.524
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.209
MECLTFEXP_MEC->PJM
CLTF
0.928
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 02GRNFLD-02N DEPT 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02GRNFLD-02N DEPT 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:157.88 %
Rating:242.0 MVA
Rating Type:B
MVA to Mitigate:382.07
MW Contribution:60.94
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
2.067
971343AH1-151 GEN
Solar/Wind Harmer
2.067
24191202EL_AA1-006
Adder
0.153
241886AC2-103 GEN2
Solar/Wind Harmer
2.6
972211AH1-690 GEN
Adder
60.94
274675JOLIET 29;7U
Adder
3.3
274675JOLIET 29;7U
Adder
3.182
274731ELWOOD EC;2P
Adder
1.765
274733ELWOOD EC;3P
Adder
1.765
274735ELWOOD EC;4P
Adder
1.765
274728ELWOOD EC;5P
Adder
1.765
971171AH1-044 GEN
Solar/Wind Harmer
2.067
274676JOLIET 29;8U
Adder
3.182
274729ELWOOD EC;1P
Adder
1.765
274730ELWOOD EC;6P
Adder
1.765
274734ELWOOD EC;8P
Adder
1.765
274736ELWOOD EC;9P
Adder
1.765
959091AF2-200 GEN
Solar/Wind Harmer
2.067
241807AE2-176_GEN
Solar/Wind Harmer
3.094
241885AC2-103 GEN1
Solar/Wind Harmer
2.6
274676JOLIET 29;8U
Adder
3.3
274732ELWOOD EC;7P
Adder
1.765
957471AF2-041 GEN
Solar/Wind Harmer
3.101
959081AF2-199 GEN
Solar/Wind Harmer
1.034
971067AG2-660 GEN
Solar/Wind Harmer
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
1.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.499
TVALTFEXP_TVA->PJM
CLTF
0.53
NYPJM->LTFIMP_NY
CLTF
0.503
LGEELTFEXP_LGEE->PJM
CLTF
0.479
WECLTFEXP_WEC->PJM
CLTF
0.393
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.104
MECLTFEXP_MEC->PJM
CLTF
1.533
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02GRNFLD-02N DEPT 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02GRNFLD-02N DEPT 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:154.19 %
Rating:242.0 MVA
Rating Type:B
MVA to Mitigate:373.15
MW Contribution:60.97
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.094
274676JOLIET 29;8U
Adder
3.306
274732ELWOOD EC;7P
Adder
1.768
957471AF2-041 GEN
Solar/Wind Harmer
3.107
959081AF2-199 GEN
Solar/Wind Harmer
1.036
971067AG2-660 GEN
Solar/Wind Harmer
0.241
24191202EL_AA1-006
Adder
0.153
972211AH1-690 GEN
Adder
60.971
274675JOLIET 29;7U
Adder
3.306
274675JOLIET 29;7U
Adder
3.188
274731ELWOOD EC;2P
Adder
1.768
274733ELWOOD EC;3P
Adder
1.768
274735ELWOOD EC;4P
Adder
1.768
274728ELWOOD EC;5P
Adder
1.768
971171AH1-044 GEN
Solar/Wind Harmer
2.071
971341AH1-150 GEN
Solar/Wind Harmer
2.071
971343AH1-151 GEN
Solar/Wind Harmer
2.071
274676JOLIET 29;8U
Adder
3.188
274729ELWOOD EC;1P
Adder
1.768
274730ELWOOD EC;6P
Adder
1.768
274734ELWOOD EC;8P
Adder
1.768
274736ELWOOD EC;9P
Adder
1.768
959091AF2-200 GEN
Solar/Wind Harmer
2.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.505
TVALTFEXP_TVA->PJM
CLTF
0.532
NYPJM->LTFIMP_NY
CLTF
0.502
LGEELTFEXP_LGEE->PJM
CLTF
0.48
WECLTFEXP_WEC->PJM
CLTF
0.394
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.111
MECLTFEXP_MEC->PJM
CLTF
1.536
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02GRNFLD-02NASA 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02GRNFLD-02NASA 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:179.06 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:343.8
MW Contribution:54.56
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
2.77
972253AH1-711 GEN
Adder
10.711
274676JOLIET 29;8U
Adder
2.954
274732ELWOOD EC;7P
Adder
1.58
957471AF2-041 GEN
Solar/Wind Harmer
2.776
959081AF2-199 GEN
Solar/Wind Harmer
0.925
971067AG2-660 GEN
Solar/Wind Harmer
0.215
274676JOLIET 29;8U
Adder
2.849
274729ELWOOD EC;1P
Adder
1.58
274730ELWOOD EC;6P
Adder
1.58
274734ELWOOD EC;8P
Adder
1.58
274736ELWOOD EC;9P
Adder
1.58
959091AF2-200 GEN
Solar/Wind Harmer
1.851
24191202EL_AA1-006
Adder
0.138
972211AH1-690 GEN
Adder
54.557
274675JOLIET 29;7U
Adder
2.954
274675JOLIET 29;7U
Adder
2.849
274731ELWOOD EC;2P
Adder
1.58
274733ELWOOD EC;3P
Adder
1.58
274735ELWOOD EC;4P
Adder
1.58
274728ELWOOD EC;5P
Adder
1.58
971171AH1-044 GEN
Solar/Wind Harmer
1.851
971341AH1-150 GEN
Solar/Wind Harmer
1.851
971343AH1-151 GEN
Solar/Wind Harmer
1.851
LAGNLTFEXP_LAGN->PJM
CLTF
1.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.447
TVALTFEXP_TVA->PJM
CLTF
0.474
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.429
WECLTFEXP_WEC->PJM
CLTF
0.352
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.39
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.883
MECLTFEXP_MEC->PJM
CLTF
1.372
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 02GRNFLD-02NASA 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02GRNFLD-02NASA 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:177.37 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:340.55
MW Contribution:54.59
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
1.854
971343AH1-151 GEN
Solar/Wind Harmer
1.854
24191202EL_AA1-006
Adder
0.138
972211AH1-690 GEN
Adder
54.585
274675JOLIET 29;7U
Adder
2.96
274675JOLIET 29;7U
Adder
2.854
274731ELWOOD EC;2P
Adder
1.583
274733ELWOOD EC;3P
Adder
1.583
274735ELWOOD EC;4P
Adder
1.583
274728ELWOOD EC;5P
Adder
1.583
971171AH1-044 GEN
Solar/Wind Harmer
1.854
274676JOLIET 29;8U
Adder
2.854
274729ELWOOD EC;1P
Adder
1.583
274730ELWOOD EC;6P
Adder
1.583
274734ELWOOD EC;8P
Adder
1.583
274736ELWOOD EC;9P
Adder
1.583
959091AF2-200 GEN
Solar/Wind Harmer
1.854
241807AE2-176_GEN
Solar/Wind Harmer
2.771
972253AH1-711 GEN
Adder
10.717
274676JOLIET 29;8U
Adder
2.96
274732ELWOOD EC;7P
Adder
1.583
957471AF2-041 GEN
Solar/Wind Harmer
2.781
959081AF2-199 GEN
Solar/Wind Harmer
0.927
971067AG2-660 GEN
Solar/Wind Harmer
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
1.05
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.476
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.43
WECLTFEXP_WEC->PJM
CLTF
0.353
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.78
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.89
MECLTFEXP_MEC->PJM
CLTF
1.375
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 02HAYES-02AVERY 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02AVERY 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.09 %
Rating:339.0 MVA
Rating Type:B
MVA to Mitigate:417.27
MW Contribution:60.6
Bus #Bus NameTypeMW Contribution
241886AC2-103 GEN2
Solar/Wind Harmer
2.739
972211AH1-690 GEN
Adder
60.6
241807AE2-176_GEN
Solar/Wind Harmer
2.688
241885AC2-103 GEN1
Solar/Wind Harmer
2.739
LAGNLTFEXP_LAGN->PJM
CLTF
1.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.465
TVALTFEXP_TVA->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.457
WECLTFEXP_WEC->PJM
CLTF
0.379
CPLELTFEXP_CPLE->PJM
CLTF
0.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.461
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.007
MECLTFEXP_MEC->PJM
CLTF
1.474
SIGELTFEXP_SIGE->PJM
CLTF
0.038

Details for 02HAYES-02AVERY 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02AVERY 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.42 %
Rating:339.0 MVA
Rating Type:B
MVA to Mitigate:408.21
MW Contribution:60.63
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
Adder
60.629
241807AE2-176_GEN
Solar/Wind Harmer
2.689
LAGNLTFEXP_LAGN->PJM
CLTF
1.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.47
TVALTFEXP_TVA->PJM
CLTF
0.507
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.458
WECLTFEXP_WEC->PJM
CLTF
0.379
CPLELTFEXP_CPLE->PJM
CLTF
0.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.014
MECLTFEXP_MEC->PJM
CLTF
1.477
SIGELTFEXP_SIGE->PJM
CLTF
0.038

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.75 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2755.89
MW Contribution:288.19
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.596
24189802OREGON_CT1
50/50
2.727
23888802TROY G4
50/50
1.831
241996AE2-282_GEN
Solar/Wind Harmer
2.316
971677AH1-339 GEN
Solar/Wind Harmer
7.553
270007AE1-245 C
Solar/Wind Harmer
3.723
942801AE2-298 GEN
Solar/Wind Harmer
0.943
246938BC-WTG3
Solar/Wind Harmer
2.462
246937BC-WTG2
Solar/Wind Harmer
2.42
961051AF2-396 GEN
Solar/Wind Harmer
9.365
961051AF2-396 GEN
Solar/Wind Harmer
4.356
960981AF2-389 GEN
Solar/Wind Harmer
0.877
957891AF2-083 GEN
Solar/Wind Harmer
1.955
247620Y3-023
Adder
0.262
270216AD2-079_GEN
Solar/Wind Harmer
0.34
970611AG2-400 GEN
Solar/Wind Harmer
5.544
270526AF1-158 GEN
Solar/Wind Harmer
2.458
24441505OLIV SLR
Solar/Wind Harmer
0.072
971231AH1-075 GEN
Solar/Wind Harmer
0.425
965681AG1-436 GEN
Solar/Wind Harmer
6.472
965791AG1-447 GEN
Solar/Wind Harmer
3.311
270224U2-072_GEN2
Solar/Wind Harmer
1.021
23929302BS-PKR
50/50
2.517
241832AE2-181_GEN
Solar/Wind Harmer
2.098
958321AF2-126 GEN
Solar/Wind Harmer
1.63
23906502RICHG2&3
Adder
1.417
270575GUS2 35KV
Solar/Wind Harmer
11.477
270541AE2-072 C
Solar/Wind Harmer
4.706
970217AG2-149 GEN
Solar/Wind Harmer
24.027
270044AE2-322 C
Solar/Wind Harmer
0.913
270404AC1-167 GEN
Solar/Wind Harmer
0.76
270588AE1-091_GEN
Solar/Wind Harmer
7.489
270258AD1-119 GEN
Solar/Wind Harmer
1.858
247604X1-042
Adder
0.265
958091AF2-103 GEN
Solar/Wind Harmer
0.101
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
945111AF1-176 GEN
Solar/Wind Harmer
3.292
270191TR4_S_V150
Solar/Wind Harmer
1.734
270247TR4_N_V136
Solar/Wind Harmer
0.492
24642205MAYFLWER
Adder
0.36
970031AG2-029 GEN
Solar/Wind Harmer
16.895
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.337
959331AF2-224 GEN
Solar/Wind Harmer
5.544
965021AG1-366 GEN
Solar/Wind Harmer
1.289
270377AD1-106 GEN
Solar/Wind Harmer
3.284
270043AE2-236 GEN
Solar/Wind Harmer
2.87
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
970349AG2-230 GEN
Solar/Wind Harmer
7.734
270535AF1-215 GEN1
Solar/Wind Harmer
2.22
972231SS25-0005
Solar/Wind Harmer
4.572
972181SS23-001
Solar/Wind Harmer
2.857
274752CRETE EC ;2U
Adder
2.355
274753CRETE EC ;3U
Adder
2.355
964401AG1-302 GEN
Solar/Wind Harmer
4.356
274724RIVER EC ;11
Adder
8.463
959141AF2-205 GEN
Solar/Wind Harmer
2.857
274802UNIV PARK;5U
Adder
2.744
961961AG1-039 GEN
Solar/Wind Harmer
1.348
274826FISK ;BP
Adder
5.143
274800UNIV PARK;3U
Adder
2.735
972038AH1-567 GEN2
Adder
0.171
276772AC2-154 GEN
Solar/Wind Harmer
1.306
276806AD2-047 C O1
Solar/Wind Harmer
5.01
970941AG2-585 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
2.903
972228AH1-698 GEN2
Adder
1.73
274676JOLIET 29;8U
Adder
13.741
971617AH1-308 GEN
Solar/Wind Harmer
2.7
276897AD1-100 C
Solar/Wind Harmer
13.466
939351AE1-166 GEN
Solar/Wind Harmer
2.751
276893AG1-478 C
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.621
274730ELWOOD EC;6P
Adder
7.621
274734ELWOOD EC;8P
Adder
7.621
274736ELWOOD EC;9P
Adder
7.621
970707AG2-453 GEN
Solar/Wind Harmer
12.981
970513AG2-328 GEN
Solar/Wind Harmer
8.259
970517AG2-330 GEN
Solar/Wind Harmer
7.49
274682WAUKEGAN ;7U
Adder
8.182
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.095
274767LEE CO EC;8U
Adder
4.047
962511AG1-100 GEN
Solar/Wind Helper
0.369
203830AF1-094 GEN
Solar/Wind Helper
0.349
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.696
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.772
943121AE2-341 GEN
Solar/Wind Harmer
2.136
943591AF1-030 GEN
Solar/Wind Harmer
1.424
270227U2-072_GEN3
Solar/Wind Harmer
1.021
270228U2-072_GEN4
Solar/Wind Harmer
1.021
270231U2-072_GEN5
Solar/Wind Harmer
1.021
274808UNIV PK N;4U
Adder
2.372
274803UNIV PARK;6U
Adder
2.744
942221AE2-234 GEN
Solar/Wind Harmer
0.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.765
274887GEN-1.85
Solar/Wind Harmer
2.496
276843GEN-1.7
Solar/Wind Harmer
0.269
958011AF2-095 GEN
Solar/Wind Harmer
6.744
274770LINCOLN ;1U
Adder
2.903
274771LINCOLN ;2U
Adder
2.903
972259AH1-714 GEN
Adder
8.868
274674JOLIET 9 ;6U
Adder
7.138
970321AG2-212 GEN
Solar/Wind Harmer
8.259
274847GR RIDGE ;BU
Solar/Wind Harmer
2.332
274696ROCKY RD ;4P
Adder
5.187
274695ROCKY RD ;2P
Adder
5.068
274693ROCKY RD ;1P
Adder
5.018
274697ROCKY RD ;3P
Adder
1.377
274683WAUKEGAN ;8U
Adder
9.585
274683WAUKEGAN ;8U
Adder
8.08
274764LEE CO EC;5U
Adder
4.104
274765LEE CO EC;6U
Adder
4.104
274762LEE CO EC;3U
Adder
4.095
274763LEE CO EC;4U
Adder
4.056
972267AH1-718 GEN
Adder
1.82
25326509SID D
Adder
0.57
203947AF1-006 C
Solar/Wind Helper
0.411
203980AG1-197 GEN
Solar/Wind Helper
0.269
203979AG1-198 GEN
Solar/Wind Helper
0.209
241967AE2-285_GEN
Solar/Wind Helper
0.365
241801AE1-079 GEN
Solar/Wind Helper
0.142
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.353
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.712
203853AF1-134 C O1
Solar/Wind Helper
0.222
24189902OREGON_CT2
50/50
2.672
23856402BAYSG1
50/50
1.43
23888702TROY G3
50/50
1.831
972253AH1-711 GEN
50/50
55.942
23860302FRMENG 3
50/50
3.53
23920202STRYCT
50/50
2.045
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
241807AE2-176_GEN
Solar/Wind Harmer
7.277
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241808AF1-120 C
Solar/Wind Harmer
1.291
241840AF1-064_GEN
Solar/Wind Harmer
1.52
972301AH1-735 GEN
Adder
7.097
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270361_3
Solar/Wind Harmer
9.742
960841AF2-375 GEN
Solar/Wind Harmer
4.291
247522W1-056 GEN
Solar/Wind Harmer
1.77
270428AC2-015 C
Solar/Wind Harmer
4.143
970515AG2-329 GEN
Solar/Wind Harmer
10.896
944231AF1-091 GEN
Solar/Wind Harmer
2.617
246936BC-WTG1
Solar/Wind Harmer
2.42
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
965421AG1-410 GEN
Solar/Wind Harmer
18.372
24695305TIMB G C
Solar/Wind Harmer
3.301
270449AD2-020 GEN
Solar/Wind Harmer
1.666
943021AE2-325 GEN
Solar/Wind Harmer
2.165
970905AG2-564 GEN
Solar/Wind Harmer
2.943
945111AF1-176 GEN
Solar/Wind Harmer
10.388
270505AE1-170 C O1
Solar/Wind Harmer
8.723
247521TR3_G114
Solar/Wind Harmer
1.944
270246TR4_N_V150
Solar/Wind Harmer
0.492
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
1.245
270462AD2-086
Solar/Wind Harmer
3.878
965011AG1-365 GEN
Solar/Wind Harmer
5.544
270223U2-072_GEN1
Solar/Wind Harmer
1.021
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
970373AG2-245 GEN
Solar/Wind Harmer
10.463
270055AF2-134 C O1
Solar/Wind Harmer
1.48
274751CRETE EC ;1U
Adder
2.355
274754CRETE EC ;4U
Adder
2.355
958381AF2-132 GEN
Solar/Wind Harmer
4.356
964861AG1-349 GEN
Solar/Wind Harmer
3.767
971917AH1-482 GEN
Solar/Wind Harmer
4.347
274723RIVER EC ;12
Adder
8.566
274812UNIV PK N;8U
Adder
2.383
276164X3-005 C
Solar/Wind Harmer
0.333
241847AF2-150_GEN
Solar/Wind Harmer
1.954
274801UNIV PARK;4U
Adder
2.735
940581AE2-045 GEN
Solar/Wind Harmer
4.778
971605AH1-302 GEN
Solar/Wind Harmer
4.086
276776AD2-060 GEN
Solar/Wind Harmer
0.198
972207SS24-0001
Solar/Wind Harmer
10.32
274773LINCOLN ;4U
Adder
2.903
274774LINCOLN ;5U
Adder
2.903
274676JOLIET 29;8U
Adder
14.25
941551AE2-152 GEN
Solar/Wind Harmer
2.104
274732ELWOOD EC;7P
Adder
7.621
274674JOLIET 9 ;6U
Adder
7.138
970245AG2-165 GEN
Solar/Wind Harmer
8.259
274871GR RIDGE ;2U
Solar/Wind Harmer
3.545
274745AC1-111 GEN9
Adder
2.563
274682WAUKEGAN ;7U
Adder
8.182
274828WAUKEGAN ;BP
Adder
5.024
274822ROCKFORD ;11
Adder
8.741
972235AH1-702 GEN1
Adder
1.121
274761LEE CO EC;2U
Adder
4.095
274766LEE CO EC;7U
Adder
4.047
961971AG1-040 GEN
Solar/Wind Helper
0.361
203835AF1-098 GEN
Solar/Wind Helper
1.422
203860AG1-193 C
Solar/Wind Helper
0.161
241966AE1-183 GEN
Solar/Wind Helper
0.14
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.235
23867002DVBSG1
50/50
12.801
972211AH1-690 GEN
50/50
288.187
23888502TROY G1
50/50
1.831
23888602TROY G2
50/50
1.831
23860102FRMENG 1
50/50
1.729
23860202FRMENG 2
50/50
1.729
24191202EL_AA1-006
50/50
0.333
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
970817AG2-515 GEN
Solar/Wind Harmer
15.71
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270499AE1-146 GEN
Solar/Wind Harmer
2.686
945641AF1-229 GEN
Solar/Wind Harmer
3.662
270297AD1-101 GEN
Solar/Wind Harmer
2.06
971549AH1-272 GEN
Solar/Wind Harmer
13.433
966831AG1-554 GEN
Solar/Wind Harmer
0.787
971989AH1-539 GEN
Solar/Wind Harmer
8.505
247607V1-011 GEN
Solar/Wind Harmer
2.482
957201AF2-014 GEN
Solar/Wind Harmer
2.805
270435AC2-044 GEN
Solar/Wind Harmer
1.237
944161AF1-084 GEN
Solar/Wind Harmer
1.331
965041AG1-368 GEN
Solar/Wind Harmer
5.807
965051AG1-369 GEN
Solar/Wind Harmer
2.887
270302AB2-170 GEN
Solar/Wind Harmer
4.661
270317AD1-130_GEN
Solar/Wind Harmer
1.787
971771AH1-392 GEN
Solar/Wind Harmer
4.969
971567AH1-282 GEN
Solar/Wind Harmer
8.2
971769AH1-391 GEN
Solar/Wind Harmer
5.381
960681AF2-359 GEN
Solar/Wind Harmer
1.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
971347AH1-153 GEN
Solar/Wind Harmer
7.734
963791AG1-232 GEN
Solar/Wind Harmer
6.936
270536AF1-215 GEN2
Solar/Wind Harmer
2.22
270071AF1-092 GEN
Solar/Wind Harmer
7.277
958391AF2-133 GEN
Solar/Wind Harmer
4.316
274814UNIV PK N;0U
Adder
2.404
274807UNIV PK N;3U
Adder
2.399
274805UNIV PK N;1U
Adder
2.388
274811UNIV PK N;7U
Adder
2.383
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.645
960591AF2-350 GEN
Solar/Wind Harmer
4.683
274775LINCOLN ;6U
Adder
2.903
274776LINCOLN ;7U
Adder
2.903
274777LINCOLN ;8U
Adder
2.903
972227AH1-698 GEN1
Adder
1.218
274687WILL CNTY;4U
Adder
13.005
274687WILL CNTY;4U
Adder
13.005
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274675JOLIET 29;7U
Adder
14.25
274675JOLIET 29;7U
Adder
13.741
274731ELWOOD EC;2P
Adder
7.621
274733ELWOOD EC;3P
Adder
7.621
274735ELWOOD EC;4P
Adder
7.621
274728ELWOOD EC;5P
Adder
7.621
970833AG2-524 GEN
Solar/Wind Harmer
4.028
970833AG2-524 GEN
Solar/Wind Harmer
1.873
274746AC1-111 G10
Adder
2.563
274744AC1-111 GEN8
Adder
2.563
24729505KEY G4
Adder
2.933
274823ROCKFORD ;21
Adder
8.678
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.267
241997AF1-093 GEN
Solar/Wind Helper
0.14
203804AE2-113_GEN
Solar/Wind Helper
0.935
203855AF2-088 C
Solar/Wind Helper
0.073
991182J1586 G
External Queue
25.292837142944336
991177J1571 G
External Queue
15.714932441711426
990142J1224
External Queue
13.53333568572998
990527J1329
External Queue
1.8513455390930176
LAGNLTFEXP_LAGN->PJM
CLTF
5.047
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
TVALTFEXP_TVA->PJM
CLTF
2.288
NYPJM->LTFIMP_NY
CLTF
2.188
LGEELTFEXP_LGEE->PJM
CLTF
2.068
WECLTFEXP_WEC->PJM
CLTF
1.698
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CPLELTFEXP_CPLE->PJM
CLTF
0.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.083
MECLTFEXP_MEC->PJM
CLTF
6.617
SIGELTFEXP_SIGE->PJM
CLTF
0.172

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.08 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2705.74
MW Contribution:289.62
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.686
23856402BAYSG1
50/50
1.441
23888702TROY G3
50/50
1.842
972253AH1-711 GEN
50/50
56.254
23860302FRMENG 3
50/50
3.59
23920202STRYCT
50/50
2.06
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
241807AE2-176_GEN
Solar/Wind Harmer
7.419
241858AF1-205_GEN
Solar/Wind Harmer
5.953
241808AF1-120 C
Solar/Wind Harmer
1.301
241840AF1-064_GEN
Solar/Wind Harmer
1.533
972301AH1-735 GEN
Adder
7.158
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270361_3
Solar/Wind Harmer
9.878
960841AF2-375 GEN
Solar/Wind Harmer
4.35
247522W1-056 GEN
Solar/Wind Harmer
1.802
270428AC2-015 C
Solar/Wind Harmer
4.301
970515AG2-329 GEN
Solar/Wind Harmer
11.13
944231AF1-091 GEN
Solar/Wind Harmer
2.648
246936BC-WTG1
Solar/Wind Harmer
2.454
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
965421AG1-410 GEN
Solar/Wind Harmer
18.626
970905AG2-564 GEN
Solar/Wind Harmer
3.098
24695305TIMB G C
Solar/Wind Harmer
3.347
270449AD2-020 GEN
Solar/Wind Harmer
1.687
943021AE2-325 GEN
Solar/Wind Harmer
2.193
945111AF1-176 GEN
Solar/Wind Harmer
10.521
270505AE1-170 C O1
Solar/Wind Harmer
8.835
247521TR3_G114
Solar/Wind Harmer
1.972
270246TR4_N_V150
Solar/Wind Harmer
0.499
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.262
270462AD2-086
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
5.623
270223U2-072_GEN1
Solar/Wind Harmer
1.038
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.614
270055AF2-134 C O1
Solar/Wind Harmer
1.502
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274751CRETE EC ;1U
Adder
2.389
274754CRETE EC ;4U
Adder
2.389
958381AF2-132 GEN
Solar/Wind Harmer
4.421
964861AG1-349 GEN
Solar/Wind Harmer
3.823
971917AH1-482 GEN
Solar/Wind Harmer
4.412
274723RIVER EC ;12
Adder
8.693
274812UNIV PK N;8U
Adder
2.419
276164X3-005 C
Solar/Wind Harmer
0.338
274801UNIV PARK;4U
Adder
2.776
940581AE2-045 GEN
Solar/Wind Harmer
4.851
971605AH1-302 GEN
Solar/Wind Harmer
4.148
276776AD2-060 GEN
Solar/Wind Harmer
0.201
972207SS24-0001
Solar/Wind Harmer
10.477
274773LINCOLN ;4U
Adder
2.947
274774LINCOLN ;5U
Adder
2.947
274676JOLIET 29;8U
Adder
14.467
941551AE2-152 GEN
Solar/Wind Harmer
2.137
274732ELWOOD EC;7P
Adder
7.738
274674JOLIET 9 ;6U
Adder
7.247
970245AG2-165 GEN
Solar/Wind Harmer
8.386
274871GR RIDGE ;2U
Solar/Wind Harmer
3.6
274745AC1-111 GEN9
Adder
2.602
274682WAUKEGAN ;7U
Adder
8.309
274828WAUKEGAN ;BP
Adder
5.102
274822ROCKFORD ;11
Adder
8.879
972235AH1-702 GEN1
Adder
1.138
274761LEE CO EC;2U
Adder
4.16
274766LEE CO EC;7U
Adder
4.111
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.429
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.236
23929302BS-PKR
50/50
2.537
241832AE2-181_GEN
Solar/Wind Harmer
2.114
958321AF2-126 GEN
Solar/Wind Harmer
1.643
23906502RICHG2&3
Adder
1.43
270575GUS2 35KV
Solar/Wind Harmer
11.637
270541AE2-072 C
Solar/Wind Harmer
4.757
970217AG2-149 GEN
Solar/Wind Harmer
24.543
270044AE2-322 C
Solar/Wind Harmer
0.925
270404AC1-167 GEN
Solar/Wind Harmer
0.77
270588AE1-091_GEN
Solar/Wind Harmer
7.618
270258AD1-119 GEN
Solar/Wind Harmer
1.882
247604X1-042
Adder
0.268
958091AF2-103 GEN
Solar/Wind Harmer
0.103
24441205WTRV SLR C
Solar/Wind Harmer
0.085
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
945111AF1-176 GEN
Solar/Wind Harmer
3.334
270191TR4_S_V150
Solar/Wind Harmer
1.759
270247TR4_N_V136
Solar/Wind Harmer
0.499
24642205MAYFLWER
Adder
0.364
970031AG2-029 GEN
Solar/Wind Harmer
17.123
247643Z2-116 C
Solar/Wind Harmer
0.04
270485AE1-090_GEN
Solar/Wind Harmer
0.342
959331AF2-224 GEN
Solar/Wind Harmer
5.623
965021AG1-366 GEN
Solar/Wind Harmer
1.308
270377AD1-106 GEN
Solar/Wind Harmer
3.371
270043AE2-236 GEN
Solar/Wind Harmer
2.911
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
970349AG2-230 GEN
Solar/Wind Harmer
7.843
270535AF1-215 GEN1
Solar/Wind Harmer
2.253
961961AG1-039 GEN
Solar/Wind Harmer
1.415
972231SS25-0005
Solar/Wind Harmer
4.639
972181SS23-001
Solar/Wind Harmer
2.9
274752CRETE EC ;2U
Adder
2.389
274753CRETE EC ;3U
Adder
2.389
964401AG1-302 GEN
Solar/Wind Harmer
4.421
274724RIVER EC ;11
Adder
8.59
959141AF2-205 GEN
Solar/Wind Harmer
2.9
274802UNIV PARK;5U
Adder
2.785
274826FISK ;BP
Adder
5.221
274800UNIV PARK;3U
Adder
2.776
972038AH1-567 GEN2
Adder
0.174
276772AC2-154 GEN
Solar/Wind Harmer
1.326
276806AD2-047 C O1
Solar/Wind Harmer
5.086
970941AG2-585 GEN
Solar/Wind Harmer
5.943
274772LINCOLN ;3U
Adder
2.947
972228AH1-698 GEN2
Adder
1.756
971617AH1-308 GEN
Solar/Wind Harmer
2.744
274676JOLIET 29;8U
Adder
13.951
276897AD1-100 C
Solar/Wind Harmer
13.671
939351AE1-166 GEN
Solar/Wind Harmer
2.793
276893AG1-478 C
Solar/Wind Harmer
0.197
970707AG2-453 GEN
Solar/Wind Harmer
13.179
24190002OREGON_ST1
50/50
3.613
24189802OREGON_CT1
50/50
2.741
23888802TROY G4
50/50
1.842
241996AE2-282_GEN
Solar/Wind Harmer
2.333
971677AH1-339 GEN
Solar/Wind Harmer
7.68
270007AE1-245 C
Solar/Wind Harmer
3.775
942801AE2-298 GEN
Solar/Wind Harmer
0.956
246938BC-WTG3
Solar/Wind Harmer
2.496
246937BC-WTG2
Solar/Wind Harmer
2.454
961051AF2-396 GEN
Solar/Wind Harmer
9.484
961051AF2-396 GEN
Solar/Wind Harmer
4.411
960981AF2-389 GEN
Solar/Wind Harmer
0.888
957891AF2-083 GEN
Solar/Wind Harmer
1.981
247620Y3-023
Adder
0.266
270216AD2-079_GEN
Solar/Wind Harmer
0.344
970611AG2-400 GEN
Solar/Wind Harmer
5.623
270526AF1-158 GEN
Solar/Wind Harmer
2.491
971231AH1-075 GEN
Solar/Wind Harmer
0.437
24441505OLIV SLR
Solar/Wind Harmer
0.073
965681AG1-436 GEN
Solar/Wind Harmer
6.563
965791AG1-447 GEN
Solar/Wind Harmer
3.358
270224U2-072_GEN2
Solar/Wind Harmer
1.038
270227U2-072_GEN3
Solar/Wind Harmer
1.038
270228U2-072_GEN4
Solar/Wind Harmer
1.038
270231U2-072_GEN5
Solar/Wind Harmer
1.038
274808UNIV PK N;4U
Adder
2.408
274803UNIV PARK;6U
Adder
2.785
942221AE2-234 GEN
Solar/Wind Harmer
0.349
274888KELLY CRK;1U
Solar/Wind Harmer
2.807
274887GEN-1.85
Solar/Wind Harmer
2.534
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.846
274770LINCOLN ;1U
Adder
2.947
274771LINCOLN ;2U
Adder
2.947
972259AH1-714 GEN
Adder
9.004
274674JOLIET 9 ;6U
Adder
7.247
970321AG2-212 GEN
Solar/Wind Harmer
8.386
274847GR RIDGE ;BU
Solar/Wind Harmer
2.368
274696ROCKY RD ;4P
Adder
5.267
274695ROCKY RD ;2P
Adder
5.146
274693ROCKY RD ;1P
Adder
5.095
274697ROCKY RD ;3P
Adder
1.398
274683WAUKEGAN ;8U
Adder
9.733
274683WAUKEGAN ;8U
Adder
8.205
274764LEE CO EC;5U
Adder
4.169
274765LEE CO EC;6U
Adder
4.169
274762LEE CO EC;3U
Adder
4.16
274763LEE CO EC;4U
Adder
4.12
972267AH1-718 GEN
Adder
1.849
25326509SID D
Adder
0.581
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.413
203980AG1-197 GEN
Solar/Wind Helper
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.21
241967AE2-285_GEN
Solar/Wind Helper
0.366
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.114
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.713
203853AF1-134 C O1
Solar/Wind Helper
0.223
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
289.616
23888502TROY G1
50/50
1.842
23888602TROY G2
50/50
1.842
23860102FRMENG 1
50/50
1.758
23860202FRMENG 2
50/50
1.758
24191202EL_AA1-006
50/50
0.345
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
970817AG2-515 GEN
Solar/Wind Harmer
15.806
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270499AE1-146 GEN
Solar/Wind Harmer
2.723
945641AF1-229 GEN
Solar/Wind Harmer
3.712
270297AD1-101 GEN
Solar/Wind Harmer
2.086
971549AH1-272 GEN
Solar/Wind Harmer
13.576
966831AG1-554 GEN
Solar/Wind Harmer
0.802
971989AH1-539 GEN
Solar/Wind Harmer
8.669
247607V1-011 GEN
Solar/Wind Harmer
2.516
957201AF2-014 GEN
Solar/Wind Harmer
2.844
270435AC2-044 GEN
Solar/Wind Harmer
1.254
944161AF1-084 GEN
Solar/Wind Harmer
1.348
965041AG1-368 GEN
Solar/Wind Harmer
5.889
965051AG1-369 GEN
Solar/Wind Harmer
2.928
270302AB2-170 GEN
Solar/Wind Harmer
4.734
270317AD1-130_GEN
Solar/Wind Harmer
1.815
971567AH1-282 GEN
Solar/Wind Harmer
8.435
971771AH1-392 GEN
Solar/Wind Harmer
5.035
971769AH1-391 GEN
Solar/Wind Harmer
5.455
960681AF2-359 GEN
Solar/Wind Harmer
1.984
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
971347AH1-153 GEN
Solar/Wind Harmer
7.843
963791AG1-232 GEN
Solar/Wind Harmer
7.04
270536AF1-215 GEN2
Solar/Wind Harmer
2.253
270071AF1-092 GEN
Solar/Wind Harmer
7.388
958391AF2-133 GEN
Solar/Wind Harmer
4.381
274814UNIV PK N;0U
Adder
2.44
274807UNIV PK N;3U
Adder
2.434
274805UNIV PK N;1U
Adder
2.424
274811UNIV PK N;7U
Adder
2.419
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.7
960591AF2-350 GEN
Solar/Wind Harmer
4.754
274775LINCOLN ;6U
Adder
2.947
274776LINCOLN ;7U
Adder
2.947
274777LINCOLN ;8U
Adder
2.947
972227AH1-698 GEN1
Adder
1.236
274687WILL CNTY;4U
Adder
13.203
274687WILL CNTY;4U
Adder
13.203
270024AE2-089 GEN
Solar/Wind Harmer
2.215
274675JOLIET 29;7U
Adder
14.468
274675JOLIET 29;7U
Adder
13.951
274731ELWOOD EC;2P
Adder
7.738
274733ELWOOD EC;3P
Adder
7.738
274735ELWOOD EC;4P
Adder
7.738
274728ELWOOD EC;5P
Adder
7.738
970833AG2-524 GEN
Solar/Wind Harmer
4.089
970833AG2-524 GEN
Solar/Wind Harmer
1.902
274746AC1-111 G10
Adder
2.602
274744AC1-111 GEN8
Adder
2.602
24729505KEY G4
Adder
2.98
274823ROCKFORD ;21
Adder
8.814
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.937
203855AF2-088 C
Solar/Wind Helper
0.073
274729ELWOOD EC;1P
Adder
7.738
274730ELWOOD EC;6P
Adder
7.738
274734ELWOOD EC;8P
Adder
7.738
274736ELWOOD EC;9P
Adder
7.738
970513AG2-328 GEN
Solar/Wind Harmer
8.386
970517AG2-330 GEN
Solar/Wind Harmer
7.606
274682WAUKEGAN ;7U
Adder
8.309
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.16
274767LEE CO EC;8U
Adder
4.111
962511AG1-100 GEN
Solar/Wind Helper
0.371
203830AF1-094 GEN
Solar/Wind Helper
0.351
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.121
20334926Z1-069 C
Solar/Wind Helper
0.698
203854AF2-039 C
Solar/Wind Helper
0.151
203818AF1-086 GEN
Solar/Wind Helper
0.773
943121AE2-341 GEN
Solar/Wind Harmer
2.169
943591AF1-030 GEN
Solar/Wind Harmer
1.446
991182J1586 G
External Queue
25.351587295532227
991177J1571 G
External Queue
15.754436492919922
990142J1224
External Queue
13.56344223022461
990527J1329
External Queue
1.8554641008377075
LAGNLTFEXP_LAGN->PJM
CLTF
5.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.294
TVALTFEXP_TVA->PJM
CLTF
2.348
NYPJM->LTFIMP_NY
CLTF
2.183
LGEELTFEXP_LGEE->PJM
CLTF
2.114
WECLTFEXP_WEC->PJM
CLTF
1.725
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.312
MECLTFEXP_MEC->PJM
CLTF
6.73
SIGELTFEXP_SIGE->PJM
CLTF
0.176

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.21 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2670.76
MW Contribution:288.97
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
15.756
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270499AE1-146 GEN
Solar/Wind Harmer
2.698
945641AF1-229 GEN
Solar/Wind Harmer
3.679
270297AD1-101 GEN
Solar/Wind Harmer
2.073
971549AH1-272 GEN
Solar/Wind Harmer
13.52
966831AG1-554 GEN
Solar/Wind Harmer
0.792
971989AH1-539 GEN
Solar/Wind Harmer
8.566
247607V1-011 GEN
Solar/Wind Harmer
2.5
957201AF2-014 GEN
Solar/Wind Harmer
2.826
270435AC2-044 GEN
Solar/Wind Harmer
1.246
944161AF1-084 GEN
Solar/Wind Harmer
1.342
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
2.323
971677AH1-339 GEN
Solar/Wind Harmer
7.59
270007AE1-245 C
Solar/Wind Harmer
3.751
942801AE2-298 GEN
Solar/Wind Harmer
0.95
246938BC-WTG3
Solar/Wind Harmer
2.481
246937BC-WTG2
Solar/Wind Harmer
2.439
961051AF2-396 GEN
Solar/Wind Harmer
9.439
961051AF2-396 GEN
Solar/Wind Harmer
4.39
960981AF2-389 GEN
Solar/Wind Harmer
0.884
957891AF2-083 GEN
Solar/Wind Harmer
1.971
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.343
970611AG2-400 GEN
Solar/Wind Harmer
5.591
270526AF1-158 GEN
Solar/Wind Harmer
2.479
24441505OLIV SLR
Solar/Wind Harmer
0.073
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
6.531
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
1.03
270227U2-072_GEN3
Solar/Wind Harmer
1.03
270228U2-072_GEN4
Solar/Wind Harmer
1.03
270231U2-072_GEN5
Solar/Wind Harmer
1.03
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.347
274888KELLY CRK;1U
Solar/Wind Harmer
2.793
274887GEN-1.85
Solar/Wind Harmer
2.521
276843GEN-1.7
Solar/Wind Harmer
0.271
958011AF2-095 GEN
Solar/Wind Harmer
6.812
274770LINCOLN ;1U
Adder
2.932
274771LINCOLN ;2U
Adder
2.932
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
8.342
274847GR RIDGE ;BU
Solar/Wind Harmer
2.356
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
972267AH1-718 GEN
Adder
1.84
25326509SID D
Adder
0.576
247621Y3-024
Adder
0.105
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
2.105
958321AF2-126 GEN
Solar/Wind Harmer
1.635
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
11.525
270541AE2-072 C
Solar/Wind Harmer
4.728
970217AG2-149 GEN
Solar/Wind Harmer
24.176
270044AE2-322 C
Solar/Wind Harmer
0.919
270404AC1-167 GEN
Solar/Wind Harmer
0.766
270588AE1-091_GEN
Solar/Wind Harmer
7.54
270258AD1-119 GEN
Solar/Wind Harmer
1.871
247604X1-042
Adder
0.267
958091AF2-103 GEN
Solar/Wind Harmer
0.102
24441205WTRV SLR C
Solar/Wind Harmer
0.084
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
1.748
270247TR4_N_V136
Solar/Wind Harmer
0.496
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
17.036
247643Z2-116 C
Solar/Wind Harmer
0.039
270485AE1-090_GEN
Solar/Wind Harmer
0.34
959331AF2-224 GEN
Solar/Wind Harmer
5.591
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
3.313
270043AE2-236 GEN
Solar/Wind Harmer
2.896
942871AE2-306 GEN
Solar/Wind Harmer
0.472
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
7.804
270535AF1-215 GEN1
Solar/Wind Harmer
2.241
972231SS25-0005
Solar/Wind Harmer
4.616
972181SS23-001
Solar/Wind Harmer
2.885
274752CRETE EC ;2U
Adder
2.377
274753CRETE EC ;3U
Adder
2.377
964401AG1-302 GEN
Solar/Wind Harmer
4.398
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
2.885
274802UNIV PARK;5U
Adder
2.771
961961AG1-039 GEN
Solar/Wind Harmer
1.361
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276772AC2-154 GEN
Solar/Wind Harmer
1.319
276806AD2-047 C O1
Solar/Wind Harmer
5.06
970941AG2-585 GEN
Solar/Wind Harmer
5.913
274772LINCOLN ;3U
Adder
2.932
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
13.601
939351AE1-166 GEN
Solar/Wind Harmer
2.779
276893AG1-478 C
Solar/Wind Harmer
0.196
970707AG2-453 GEN
Solar/Wind Harmer
13.112
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
8.342
970517AG2-330 GEN
Solar/Wind Harmer
7.566
274682WAUKEGAN ;7U
Adder
8.266
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274767LEE CO EC;8U
Adder
4.089
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
943121AE2-341 GEN
Solar/Wind Harmer
5.427
943591AF1-030 GEN
Solar/Wind Harmer
3.618
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
7.294
241858AF1-205_GEN
Solar/Wind Harmer
5.929
241808AF1-120 C
Solar/Wind Harmer
1.295
241840AF1-064_GEN
Solar/Wind Harmer
1.525
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
9.783
960841AF2-375 GEN
Solar/Wind Harmer
4.309
247522W1-056 GEN
Solar/Wind Harmer
1.78
270428AC2-015 C
Solar/Wind Harmer
4.168
970515AG2-329 GEN
Solar/Wind Harmer
10.964
944231AF1-091 GEN
Solar/Wind Harmer
2.634
246936BC-WTG1
Solar/Wind Harmer
2.439
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.512
24695305TIMB G C
Solar/Wind Harmer
3.326
270449AD2-020 GEN
Solar/Wind Harmer
1.68
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.966
945111AF1-176 GEN
Solar/Wind Harmer
10.472
270505AE1-170 C O1
Solar/Wind Harmer
8.793
247521TR3_G114
Solar/Wind Harmer
1.96
270246TR4_N_V150
Solar/Wind Harmer
0.496
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
1.255
270462AD2-086
Solar/Wind Harmer
3.91
965011AG1-365 GEN
Solar/Wind Harmer
5.591
270223U2-072_GEN1
Solar/Wind Harmer
1.03
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.561
270055AF2-134 C O1
Solar/Wind Harmer
1.494
274751CRETE EC ;1U
Adder
2.377
274754CRETE EC ;4U
Adder
2.377
958381AF2-132 GEN
Solar/Wind Harmer
4.398
964861AG1-349 GEN
Solar/Wind Harmer
3.804
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0.336
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
4.826
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.2
972207SS24-0001
Solar/Wind Harmer
10.423
274773LINCOLN ;4U
Adder
2.932
274774LINCOLN ;5U
Adder
2.932
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
2.126
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
8.342
274871GR RIDGE ;2U
Solar/Wind Harmer
3.581
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
274822ROCKFORD ;11
Adder
8.833
972235AH1-702 GEN1
Adder
1.133
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
4.089
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
965041AG1-368 GEN
Solar/Wind Harmer
5.854
965051AG1-369 GEN
Solar/Wind Harmer
2.91
270302AB2-170 GEN
Solar/Wind Harmer
4.7
270317AD1-130_GEN
Solar/Wind Harmer
1.802
971771AH1-392 GEN
Solar/Wind Harmer
5.011
971567AH1-282 GEN
Solar/Wind Harmer
8.27
971769AH1-391 GEN
Solar/Wind Harmer
5.428
960681AF2-359 GEN
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
7.804
963791AG1-232 GEN
Solar/Wind Harmer
7
270536AF1-215 GEN2
Solar/Wind Harmer
2.241
270071AF1-092 GEN
Solar/Wind Harmer
7.347
958391AF2-133 GEN
Solar/Wind Harmer
4.359
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
960591AF2-350 GEN
Solar/Wind Harmer
4.73
274775LINCOLN ;6U
Adder
2.932
274776LINCOLN ;7U
Adder
2.932
274777LINCOLN ;8U
Adder
2.932
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
2.202
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
4.069
970833AG2-524 GEN
Solar/Wind Harmer
1.892
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
274823ROCKFORD ;21
Adder
8.769
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
991182J1586 G
External Queue
25.292837142944336
991177J1571 G
External Queue
15.714932441711426
990142J1224
External Queue
13.53333568572998
990527J1329
External Queue
1.8513455390930176
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:288.81
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.836
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.745
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
288.807
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
971989AH1-539 GEN
Solar/Wind Harmer
1.989
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965041AG1-368 GEN
Solar/Wind Harmer
4.077
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.434
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274811UNIV PK N;7U
Adder
2.401
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.674
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274776LINCOLN ;7U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
972227AH1-698 GEN1
Adder
1.228
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274735ELWOOD EC;4P
Adder
7.682
274728ELWOOD EC;5P
Adder
7.682
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
274746AC1-111 G10
Adder
2.583
274744AC1-111 GEN8
Adder
2.583
24729505KEY G4
Adder
2.957
276868AE1-113 GEN
Solar/Wind Harmer
0.638
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.951
971411AH1-196 GEN
Solar/Wind Harmer
4.733
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
970169AG2-114 GEN
Solar/Wind Harmer
3.123
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.808
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.066
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.207
941731AE2-173 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.266
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
50/50
2.523
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906502RICHG2&3
Adder
1.422
270575GUS2 35KV
Solar/Wind Harmer
5.343
270541AE2-072 C
Solar/Wind Harmer
0.009
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.433
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.119
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270361_3
Solar/Wind Harmer
5.343
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.735
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.266
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.362
970031AG2-029 GEN
Solar/Wind Harmer
2.571
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.726
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270043AE2-236 GEN
Solar/Wind Harmer
2.353
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.529
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.765
274826FISK ;BP
Adder
5.184
274800UNIV PARK;3U
Adder
2.756
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.866
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
972228AH1-698 GEN2
Adder
1.743
274676JOLIET 29;8U
Adder
13.851
971617AH1-308 GEN
Solar/Wind Harmer
2.722
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
274730ELWOOD EC;6P
Adder
7.682
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
274682WAUKEGAN ;7U
Adder
8.249
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274872LEEDK;1U
Solar/Wind Harmer
0.116
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.279
970571AG2-364 GEN
Solar/Wind Harmer
6.257
972236AH1-702 GEN2
Adder
0.983
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.129
276157O29GEN1
Solar/Wind Harmer
0.497
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.061
959611AF2-252 GEN
Solar/Wind Harmer
1.007
965931AG1-462 GEN
Solar/Wind Harmer
7.661
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.367
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.158
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965681AG1-436 GEN
Solar/Wind Harmer
4.548
965791AG1-447 GEN
Solar/Wind Harmer
3.335
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.391
274803UNIV PARK;6U
Adder
2.765
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
274674JOLIET 9 ;6U
Adder
7.195
970321AG2-212 GEN
Solar/Wind Harmer
1.409
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
274693ROCKY RD ;1P
Adder
5.059
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
958491AF2-143 GEN
Solar/Wind Harmer
4.791
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
971335AH1-147 GEN
Solar/Wind Harmer
6.305
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274764LEE CO EC;5U
Adder
4.139
274765LEE CO EC;6U
Adder
4.139
274762LEE CO EC;3U
Adder
4.129
274763LEE CO EC;4U
Adder
4.09
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.207
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.815
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.305
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
270031AE2-169
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Helper
0.409
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.706
203853AF1-134 C O1
Solar/Wind Helper
0.221
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.687
944231AF1-091 GEN
Solar/Wind Harmer
1.299
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.179
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.894
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.381
274723RIVER EC ;12
Adder
8.632
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
274676JOLIET 29;8U
Adder
14.364
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.419
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970569AG2-363 GEN
Solar/Wind Harmer
9.385
972235AH1-702 GEN1
Adder
1.13
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.129
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.276
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.234
991182J1586 G
External Queue
25.292837142944336
991177J1571 G
External Queue
15.714932441711426
990142J1224
External Queue
13.53333568572998
990527J1329
External Queue
1.8513455390930176
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:288.97
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.529
971989AH1-539 GEN
Solar/Wind Harmer
1.992
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
5.347
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.741
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.267
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
2.575
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.73
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
1.422
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.746
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
4.556
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
2.357
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4.008
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.771
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.87
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.13
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
274682WAUKEGAN ;7U
Adder
8.266
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274872LEEDK;1U
Solar/Wind Harmer
0.117
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.293
970571AG2-364 GEN
Solar/Wind Harmer
6.27
972236AH1-702 GEN2
Adder
0.985
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.138
276157O29GEN1
Solar/Wind Harmer
0.498
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.081
959611AF2-252 GEN
Solar/Wind Harmer
1.009
965931AG1-462 GEN
Solar/Wind Harmer
7.678
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965041AG1-368 GEN
Solar/Wind Harmer
4.084
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.444
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274776LINCOLN ;7U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.955
971411AH1-196 GEN
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
970169AG2-114 GEN
Solar/Wind Harmer
3.129
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.812
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.072
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.214
941731AE2-173 GEN
Solar/Wind Harmer
2.551
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
1.412
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
958491AF2-143 GEN
Solar/Wind Harmer
4.801
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
971335AH1-147 GEN
Solar/Wind Harmer
6.319
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.208
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.819
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.11
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
270031AE2-169
Solar/Wind Harmer
1.663
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
5.347
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.704
944231AF1-091 GEN
Solar/Wind Harmer
1.301
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.901
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.44
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970569AG2-363 GEN
Solar/Wind Harmer
9.405
972235AH1-702 GEN1
Adder
1.133
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.909
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.286
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
991182J1586 G
External Queue
25.292837142944336
991177J1571 G
External Queue
15.714932441711426
990142J1224
External Queue
13.53333568572998
990527J1329
External Queue
1.8513455390930176
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175

Details for 02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:175.39 %
Rating:352.0 MVA
Rating Type:B
MVA to Mitigate:617.37
MW Contribution:89.7
Bus #Bus NameTypeMW Contribution
23860102FRMENG 1
50/50
0.973
23860202FRMENG 2
50/50
0.973
972211AH1-690 GEN
Adder
89.703
945411AF1-206 GEN
Solar/Wind Harmer
3.313
970817AG2-515 GEN
Solar/Wind Harmer
5.423
274675JOLIET 29;7U
Adder
4.927
274675JOLIET 29;7U
Adder
4.751
274731ELWOOD EC;2P
Adder
2.635
274733ELWOOD EC;3P
Adder
2.635
274735ELWOOD EC;4P
Adder
2.635
274728ELWOOD EC;5P
Adder
2.635
971171AH1-044 GEN
Solar/Wind Harmer
3.087
241886AC2-103 GEN2
Solar/Wind Helper
1.373
241996AE2-282_GEN
Solar/Wind Harmer
0.887
971341AH1-150 GEN
Solar/Wind Harmer
3.087
971343AH1-151 GEN
Solar/Wind Harmer
3.087
23929302BS-PKR
Adder
1.153
241832AE2-181_GEN
Solar/Wind Harmer
0.794
958321AF2-126 GEN
Solar/Wind Harmer
0.635
23906502RICHG2&3
Adder
0.526
274676JOLIET 29;8U
Adder
4.751
274729ELWOOD EC;1P
Adder
2.635
274730ELWOOD EC;6P
Adder
2.635
274734ELWOOD EC;8P
Adder
2.635
274736ELWOOD EC;9P
Adder
2.635
959091AF2-200 GEN
Solar/Wind Harmer
3.087
23860302FRMENG 3
50/50
1.987
241858AF1-205_GEN
Solar/Wind Harmer
2.226
241808AF1-120 C
Solar/Wind Harmer
0.495
972253AH1-711 GEN
Adder
17.007
241840AF1-064_GEN
Solar/Wind Harmer
0.592
23920202STRYCT
Adder
0.726
972301AH1-735 GEN
Adder
2.634
23906402RICHG1
Adder
0.527
23906502RICHG2&3
Adder
0.526
274676JOLIET 29;8U
Adder
4.927
274732ELWOOD EC;7P
Adder
2.635
957471AF2-041 GEN
Solar/Wind Harmer
4.631
959081AF2-199 GEN
Solar/Wind Harmer
1.544
971067AG2-660 GEN
Solar/Wind Harmer
0.359
241807AE2-176_GEN
Solar/Wind Helper
1.132
241885AC2-103 GEN1
Solar/Wind Helper
1.373
LAGNLTFEXP_LAGN->PJM
CLTF
1.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.776
TVALTFEXP_TVA->PJM
CLTF
0.797
NYPJM->LTFIMP_NY
CLTF
0.733
LGEELTFEXP_LGEE->PJM
CLTF
0.717
WECLTFEXP_WEC->PJM
CLTF
0.587
CPLELTFEXP_CPLE->PJM
CLTF
0.115
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.928
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.159
MECLTFEXP_MEC->PJM
CLTF
2.29
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for [AH1-690] 02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LAKVEW-02GRNFLD 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.45 %
Rating:352.0 MVA
Rating Type:B
MVA to Mitigate:445.09
MW Contribution:95.19
IPD Plant:AH1-690
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
PJM_IPD
95.186

Details for 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.85 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1759.15
MW Contribution:788.05
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
788.046
971549AH1-272 GEN
Solar/Wind Harmer
9.679
945641AF1-229 GEN
Solar/Wind Helper
1.292
270499AE1-146 GEN
Solar/Wind Helper
1.518
24190002OREGON_ST1
50/50
9.847
24189802OREGON_CT1
50/50
7.469
24189902OREGON_CT2
50/50
7.319
960841AF2-375 GEN
Solar/Wind Helper
1.005
247522W1-056 GEN
Solar/Wind Helper
0.609
991182J1586 G
External Queue
29.999971389770508
991177J1571 G
External Queue
11.570172309875488
990142J1224
External Queue
15.328842163085938
990527J1329
External Queue
2.09696888923645
LAGNLTFEXP_LAGN->PJM
CLTF
0.887
TVALTFEXP_TVA->PJM
CLTF
0.274
NYPJM->LTFIMP_NY
CLTF
0.462
LGEELTFEXP_LGEE->PJM
CLTF
0.155
WECLTFEXP_WEC->PJM
CLTF
0.632
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.544
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.997
MECLTFEXP_MEC->PJM
CLTF
2.173
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for [AH1-690] 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.58 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1558.11
MW Contribution:788.05
IPD Plant:AH1-690
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
PJM_IPD
788.046

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-007_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-007_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.87 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2589.19
MW Contribution:230.61
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.619
972253AH1-711 GEN
50/50
79.996
23920202STRYCT
50/50
2.358
24189902OREGON_CT2
50/50
2.142
972301AH1-735 GEN
50/50
8.615
23906402RICHG1
50/50
1.723
23906502RICHG2&3
50/50
1.719
241858AF1-205_GEN
Solar/Wind Harmer
6.914
241808AF1-120 C
Solar/Wind Harmer
1.462
241840AF1-064_GEN
Solar/Wind Harmer
1.676
270361_3
Solar/Wind Harmer
8.902
960841AF2-375 GEN
Solar/Wind Harmer
3.954
970515AG2-329 GEN
Solar/Wind Harmer
11.808
944231AF1-091 GEN
Solar/Wind Harmer
2.931
247522W1-056 GEN
Solar/Wind Harmer
1.705
246936BC-WTG1
Solar/Wind Harmer
2.664
270489AE1-102 GEN1
Solar/Wind Harmer
0.885
965421AG1-410 GEN
Solar/Wind Harmer
20.233
270449AD2-020 GEN
Solar/Wind Harmer
1.844
943021AE2-325 GEN
Solar/Wind Harmer
2.397
24695305TIMB G C
Solar/Wind Harmer
3.619
945111AF1-176 GEN
Solar/Wind Harmer
11.504
270505AE1-170 C O1
Solar/Wind Harmer
9.66
247521TR3_G114
Solar/Wind Harmer
2.136
270246TR4_N_V150
Solar/Wind Harmer
0.54
24639705ELKHART HY
Adder
0.096
270063AE2-323 C
Solar/Wind Harmer
1.381
965011AG1-365 GEN
Solar/Wind Harmer
6.135
270462AD2-086
Solar/Wind Harmer
4.259
270223U2-072_GEN1
Solar/Wind Harmer
1.122
270578AF1-285 GEN2
Solar/Wind Harmer
0.686
270391AF1-285 GEN3
Solar/Wind Harmer
0.686
970373AG2-245 GEN
Solar/Wind Harmer
11.628
270055AF2-134 C O1
Solar/Wind Harmer
1.645
274751CRETE EC ;1U
Adder
2.62
274754CRETE EC ;4U
Adder
2.62
958381AF2-132 GEN
Solar/Wind Harmer
4.846
964861AG1-349 GEN
Solar/Wind Harmer
4.191
971917AH1-482 GEN
Solar/Wind Harmer
4.836
274723RIVER EC ;12
Adder
9.531
274812UNIV PK N;8U
Adder
2.652
276164X3-005 C
Solar/Wind Harmer
0.371
274801UNIV PARK;4U
Adder
3.045
940581AE2-045 GEN
Solar/Wind Harmer
5.319
971605AH1-302 GEN
Solar/Wind Harmer
4.548
23906502RICHG2&3
50/50
1.719
241832AE2-181_GEN
Solar/Wind Harmer
2.411
958321AF2-126 GEN
Solar/Wind Harmer
1.797
23888802TROY G4
50/50
2.619
24190002OREGON_ST1
50/50
2.882
24189802OREGON_CT1
50/50
2.186
241996AE2-282_GEN
Solar/Wind Harmer
2.622
971677AH1-339 GEN
Solar/Wind Harmer
7.096
270007AE1-245 C
Solar/Wind Harmer
4.06
942801AE2-298 GEN
Solar/Wind Harmer
1.031
246938BC-WTG3
Solar/Wind Harmer
2.71
246937BC-WTG2
Solar/Wind Harmer
2.664
961051AF2-396 GEN
Solar/Wind Harmer
10.367
961051AF2-396 GEN
Solar/Wind Harmer
4.822
960981AF2-389 GEN
Solar/Wind Harmer
0.971
957891AF2-083 GEN
Solar/Wind Harmer
2.166
247620Y3-023
Adder
0.291
270216AD2-079_GEN
Solar/Wind Harmer
0.377
970611AG2-400 GEN
Solar/Wind Harmer
6.135
270526AF1-158 GEN
Solar/Wind Harmer
2.726
24441505OLIV SLR
Solar/Wind Harmer
0.08
965681AG1-436 GEN
Solar/Wind Harmer
7.186
965791AG1-447 GEN
Solar/Wind Harmer
3.677
270224U2-072_GEN2
Solar/Wind Harmer
1.122
270227U2-072_GEN3
Solar/Wind Harmer
1.122
270228U2-072_GEN4
Solar/Wind Harmer
1.122
270231U2-072_GEN5
Solar/Wind Harmer
1.122
274808UNIV PK N;4U
Adder
2.64
274803UNIV PARK;6U
Adder
3.055
942221AE2-234 GEN
Solar/Wind Harmer
0.382
274888KELLY CRK;1U
Solar/Wind Harmer
3.079
274887GEN-1.85
Solar/Wind Harmer
2.779
276843GEN-1.7
Solar/Wind Harmer
0.299
958011AF2-095 GEN
Solar/Wind Harmer
7.509
274770LINCOLN ;1U
Adder
3.232
274771LINCOLN ;2U
Adder
3.232
972259AH1-714 GEN
Adder
9.876
274674JOLIET 9 ;6U
Adder
7.95
970321AG2-212 GEN
Solar/Wind Harmer
9.194
274847GR RIDGE ;BU
Solar/Wind Harmer
2.598
958481AF2-142 GEN
Solar/Wind Harmer
7.657
274696ROCKY RD ;4P
Adder
5.781
274695ROCKY RD ;2P
Adder
5.647
274693ROCKY RD ;1P
Adder
5.592
274697ROCKY RD ;3P
Adder
1.534
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.004
274764LEE CO EC;5U
Adder
4.579
274765LEE CO EC;6U
Adder
4.579
274762LEE CO EC;3U
Adder
4.569
274763LEE CO EC;4U
Adder
4.525
972267AH1-718 GEN
Adder
2.031
247621Y3-024
Adder
0.115
25326509SID D
Adder
0.626
203947AF1-006 C
Solar/Wind Helper
0.414
203980AG1-197 GEN
Solar/Wind Helper
0.271
203979AG1-198 GEN
Solar/Wind Helper
0.211
241967AE2-285_GEN
Solar/Wind Helper
0.368
241801AE1-079 GEN
Solar/Wind Helper
0.143
241985AE1-237 GEN
Solar/Wind Helper
0.143
962101AG1-054 GEN
Solar/Wind Helper
0.354
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
20398826ARMNA MT
Solar/Wind Helper
0.707
203853AF1-134 C O1
Solar/Wind Helper
0.221
274861TOP CROP ;1U
Solar/Wind Harmer
0.282
274862TOP CROP ;2U
Solar/Wind Harmer
0.236
276776AD2-060 GEN
Solar/Wind Harmer
0.22
972207SS24-0001
Solar/Wind Harmer
11.49
274773LINCOLN ;4U
Adder
3.232
274774LINCOLN ;5U
Adder
3.232
274676JOLIET 29;8U
Adder
15.87
941551AE2-152 GEN
Solar/Wind Harmer
2.344
274732ELWOOD EC;7P
Adder
8.488
274674JOLIET 9 ;6U
Adder
7.95
970245AG2-165 GEN
Solar/Wind Harmer
9.194
274871GR RIDGE ;2U
Solar/Wind Harmer
3.949
274745AC1-111 GEN9
Adder
2.855
276691AA1-018 GEN1
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
9.118
274828WAUKEGAN ;BP
Adder
5.599
274822ROCKFORD ;11
Adder
9.749
972235AH1-702 GEN1
Adder
1.25
274761LEE CO EC;2U
Adder
4.569
274766LEE CO EC;7U
Adder
4.515
241885AC2-103 GEN1
Solar/Wind Helper
7.132
241807AE2-176_GEN
Solar/Wind Helper
1.736
961971AG1-040 GEN
Solar/Wind Helper
0.363
203835AF1-098 GEN
Solar/Wind Helper
1.432
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
254303AC2-168 GEN
Solar/Wind Helper
0.082
203954AE2-126 C
Solar/Wind Helper
0.234
23888502TROY G1
50/50
2.619
23888602TROY G2
50/50
2.619
972211AH1-690 GEN
50/50
230.612
23906902RICHG6
50/50
1.023
23906702RICHG4
50/50
1.02
23906802RICHG5
50/50
0.745
970817AG2-515 GEN
Solar/Wind Harmer
20.387
945411AF1-206 GEN
Solar/Wind Harmer
9.795
945641AF1-229 GEN
Solar/Wind Harmer
4.031
270499AE1-146 GEN
Solar/Wind Harmer
2.505
971549AH1-272 GEN
Solar/Wind Harmer
14.838
270297AD1-101 GEN
Solar/Wind Harmer
2.213
247607V1-011 GEN
Solar/Wind Harmer
2.706
957201AF2-014 GEN
Solar/Wind Harmer
3.088
270435AC2-044 GEN
Solar/Wind Harmer
1.362
944161AF1-084 GEN
Solar/Wind Harmer
1.473
966831AG1-554 GEN
Solar/Wind Harmer
0.779
971989AH1-539 GEN
Solar/Wind Harmer
8.419
965041AG1-368 GEN
Solar/Wind Harmer
6.392
965051AG1-369 GEN
Solar/Wind Harmer
3.172
971771AH1-392 GEN
Solar/Wind Harmer
5.509
270302AB2-170 GEN
Solar/Wind Harmer
5.12
270317AD1-130_GEN
Solar/Wind Harmer
1.963
971769AH1-391 GEN
Solar/Wind Harmer
5.97
971567AH1-282 GEN
Solar/Wind Harmer
8.782
960681AF2-359 GEN
Solar/Wind Harmer
2.172
971347AH1-153 GEN
Solar/Wind Harmer
8.587
963791AG1-232 GEN
Solar/Wind Harmer
7.686
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
270536AF1-215 GEN2
Solar/Wind Harmer
2.468
270071AF1-092 GEN
Solar/Wind Harmer
8.09
274814UNIV PK N;0U
Adder
2.675
274807UNIV PK N;3U
Adder
2.669
274805UNIV PK N;1U
Adder
2.658
274811UNIV PK N;7U
Adder
2.652
958391AF2-133 GEN
Solar/Wind Harmer
4.803
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.058
960591AF2-350 GEN
Solar/Wind Harmer
5.215
274775LINCOLN ;6U
Adder
3.232
274776LINCOLN ;7U
Adder
3.232
274777LINCOLN ;8U
Adder
3.232
972227AH1-698 GEN1
Adder
1.356
274687WILL CNTY;4U
Adder
14.483
274687WILL CNTY;4U
Adder
14.483
274675JOLIET 29;7U
Adder
15.87
274675JOLIET 29;7U
Adder
15.304
274731ELWOOD EC;2P
Adder
8.488
274733ELWOOD EC;3P
Adder
8.488
274735ELWOOD EC;4P
Adder
8.488
274728ELWOOD EC;5P
Adder
8.488
270024AE2-089 GEN
Solar/Wind Harmer
2.42
970833AG2-524 GEN
Solar/Wind Harmer
4.486
970833AG2-524 GEN
Solar/Wind Harmer
2.087
274746AC1-111 G10
Adder
2.855
274744AC1-111 GEN8
Adder
2.855
24729505KEY G4
Adder
3.263
274823ROCKFORD ;21
Adder
9.678
241886AC2-103 GEN2
Solar/Wind Helper
7.132
241982AE2-343 S C
Solar/Wind Helper
0.128
254304AE2-114 C
Solar/Wind Helper
0.122
203846AF2-130 C
Solar/Wind Helper
0.268
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.933
203855AF2-088 C
Solar/Wind Helper
0.072
23929302BS-PKR
Adder
1.928
270541AE2-072 C
Solar/Wind Harmer
5.113
270575GUS2 35KV
Solar/Wind Harmer
10.488
970217AG2-149 GEN
Solar/Wind Harmer
26.038
270044AE2-322 C
Solar/Wind Harmer
1.007
270404AC1-167 GEN
Solar/Wind Harmer
0.839
270258AD1-119 GEN
Solar/Wind Harmer
2.048
247604X1-042
Adder
0.293
270588AE1-091_GEN
Solar/Wind Harmer
7.623
24441205WTRV SLR C
Solar/Wind Harmer
0.093
958091AF2-103 GEN
Solar/Wind Harmer
0.111
270491AE1-102 GEN2
Solar/Wind Harmer
0.885
945111AF1-176 GEN
Solar/Wind Harmer
3.646
270191TR4_S_V150
Solar/Wind Harmer
1.906
270247TR4_N_V136
Solar/Wind Harmer
0.54
24642205MAYFLWER
Adder
0.399
970031AG2-029 GEN
Solar/Wind Harmer
18.728
247643Z2-116 C
Solar/Wind Harmer
0.043
959331AF2-224 GEN
Solar/Wind Harmer
6.135
965021AG1-366 GEN
Solar/Wind Harmer
1.427
270485AE1-090_GEN
Solar/Wind Harmer
0.37
270043AE2-236 GEN
Solar/Wind Harmer
3.186
970349AG2-230 GEN
Solar/Wind Harmer
8.587
942871AE2-306 GEN
Solar/Wind Harmer
0.515
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
270535AF1-215 GEN1
Solar/Wind Harmer
2.468
972231SS25-0005
Solar/Wind Harmer
5.086
972181SS23-001
Solar/Wind Harmer
3.179
274752CRETE EC ;2U
Adder
2.62
274753CRETE EC ;3U
Adder
2.62
964401AG1-302 GEN
Solar/Wind Harmer
4.846
274724RIVER EC ;11
Adder
9.418
959141AF2-205 GEN
Solar/Wind Harmer
3.179
274802UNIV PARK;5U
Adder
3.055
274826FISK ;BP
Adder
5.726
274800UNIV PARK;3U
Adder
3.045
972038AH1-567 GEN2
Adder
0.191
276772AC2-154 GEN
Solar/Wind Harmer
1.454
276806AD2-047 C O1
Solar/Wind Harmer
5.578
970941AG2-585 GEN
Solar/Wind Harmer
6.518
274772LINCOLN ;3U
Adder
3.232
972228AH1-698 GEN2
Adder
1.926
274676JOLIET 29;8U
Adder
15.304
276897AD1-100 C
Solar/Wind Harmer
14.996
939351AE1-166 GEN
Solar/Wind Harmer
3.064
276893AG1-478 C
Solar/Wind Harmer
0.216
274729ELWOOD EC;1P
Adder
8.488
274730ELWOOD EC;6P
Adder
8.488
274734ELWOOD EC;8P
Adder
8.488
274736ELWOOD EC;9P
Adder
8.488
970707AG2-453 GEN
Solar/Wind Harmer
14.457
971617AH1-308 GEN
Solar/Wind Harmer
2.998
970513AG2-328 GEN
Solar/Wind Harmer
9.194
970517AG2-330 GEN
Solar/Wind Harmer
8.339
943121AE2-341 GEN
Solar/Wind Harmer
7.659
943591AF1-030 GEN
Solar/Wind Harmer
5.106
276694AA1-018 GEN2
Solar/Wind Harmer
3.221
274682WAUKEGAN ;7U
Adder
9.118
972236AH1-702 GEN2
Adder
1.087
274760LEE CO EC;1U
Adder
4.569
274767LEE CO EC;8U
Adder
4.515
962511AG1-100 GEN
Solar/Wind Helper
0.372
203830AF1-094 GEN
Solar/Wind Helper
0.352
959441AF2-235 GEN
Solar/Wind Helper
0.159
254305AE2-115 C
Solar/Wind Helper
0.122
20334926Z1-069 C
Solar/Wind Helper
0.694
203854AF2-039 C
Solar/Wind Helper
0.15
991182J1586 G
External Queue
28.404245376586914
991177J1571 G
External Queue
18.513126373291016
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
LAGNLTFEXP_LAGN->PJM
CLTF
5.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.925
TVALTFEXP_TVA->PJM
CLTF
2.645
NYPJM->LTFIMP_NY
CLTF
2.147
LGEELTFEXP_LGEE->PJM
CLTF
2.336
WECLTFEXP_WEC->PJM
CLTF
1.894
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
45.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
103.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.444
MECLTFEXP_MEC->PJM
CLTF
7.414
SIGELTFEXP_SIGE->PJM
CLTF
0.194

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-004_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-004_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.8
MW Contribution:234.32
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.272
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274696ROCKY RD ;4P
Adder
6.031
274695ROCKY RD ;2P
Adder
5.892
274693ROCKY RD ;1P
Adder
5.834
274697ROCKY RD ;3P
Adder
1.6
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.74
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.177
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.001
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.127
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.989
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.089
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.045
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.842
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.773
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.702
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.773
274763LEE CO EC;4U
Adder
4.728
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241801AE1-079 GEN
Solar/Wind Helper
0.138
241967AE2-285_GEN
Solar/Wind Helper
0.354
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.319
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.605
945411AF1-206 GEN
Solar/Wind Harmer
9.926
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.244
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.707
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.096
274687WILL CNTY;4U
Adder
15.096
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.849
274733ELWOOD EC;3P
Adder
8.849
274735ELWOOD EC;4P
Adder
8.849
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.443
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.741
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.045
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.633
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.849
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.773
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.40474510192871
991177J1571 G
External Queue
18.512771606445312
990142J1224
External Queue
15.356985092163086
990527J1329
External Queue
2.100818634033203
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.488
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.861
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-005_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-005_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:234.28
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.404245376586914
991177J1571 G
External Queue
18.513126373291016
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.2 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2219.73
MW Contribution:234.28
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
7.002
241808AF1-120 C
Solar/Wind Harmer
1.482
241840AF1-064_GEN
Solar/Wind Harmer
1.7
270361_3
Solar/Wind Harmer
9.093
960841AF2-375 GEN
Solar/Wind Harmer
4.04
970515AG2-329 GEN
Solar/Wind Harmer
12.126
944231AF1-091 GEN
Solar/Wind Harmer
3.014
247522W1-056 GEN
Solar/Wind Harmer
1.754
246936BC-WTG1
Solar/Wind Harmer
2.75
270489AE1-102 GEN1
Solar/Wind Harmer
0.914
965421AG1-410 GEN
Solar/Wind Harmer
20.891
270449AD2-020 GEN
Solar/Wind Harmer
1.906
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
3.74
945111AF1-176 GEN
Solar/Wind Harmer
11.896
270505AE1-170 C O1
Solar/Wind Harmer
9.988
247521TR3_G114
Solar/Wind Harmer
2.21
270246TR4_N_V150
Solar/Wind Harmer
0.559
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
1.43
965011AG1-365 GEN
Solar/Wind Harmer
6.354
270462AD2-086
Solar/Wind Harmer
4.412
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.658
971677AH1-339 GEN
Solar/Wind Harmer
7.271
270007AE1-245 C
Solar/Wind Harmer
4.19
942801AE2-298 GEN
Solar/Wind Harmer
1.064
246938BC-WTG3
Solar/Wind Harmer
2.798
246937BC-WTG2
Solar/Wind Harmer
2.75
961051AF2-396 GEN
Solar/Wind Harmer
10.715
961051AF2-396 GEN
Solar/Wind Harmer
4.984
960981AF2-389 GEN
Solar/Wind Harmer
1.004
957891AF2-083 GEN
Solar/Wind Harmer
2.24
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.39
970611AG2-400 GEN
Solar/Wind Harmer
6.354
270526AF1-158 GEN
Solar/Wind Harmer
2.826
24441505OLIV SLR
Solar/Wind Harmer
0.083
965681AG1-436 GEN
Solar/Wind Harmer
7.46
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
1.166
270227U2-072_GEN3
Solar/Wind Harmer
1.166
270228U2-072_GEN4
Solar/Wind Harmer
1.166
270231U2-072_GEN5
Solar/Wind Harmer
1.166
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.398
274888KELLY CRK;1U
Solar/Wind Harmer
3.208
270223U2-072_GEN1
Solar/Wind Harmer
1.166
270578AF1-285 GEN2
Solar/Wind Harmer
0.713
270391AF1-285 GEN3
Solar/Wind Harmer
0.713
970373AG2-245 GEN
Solar/Wind Harmer
12.088
270055AF2-134 C O1
Solar/Wind Harmer
1.712
274751CRETE EC ;1U
Adder
2.727
274754CRETE EC ;4U
Adder
2.727
958381AF2-132 GEN
Solar/Wind Harmer
5.044
964861AG1-349 GEN
Solar/Wind Harmer
4.363
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0.386
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
5.542
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.23
972207SS24-0001
Solar/Wind Harmer
11.973
274773LINCOLN ;4U
Adder
3.367
274774LINCOLN ;5U
Adder
3.367
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
2.443
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
9.586
274871GR RIDGE ;2U
Solar/Wind Harmer
4.118
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.248
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
274822ROCKFORD ;11
Adder
10.179
972235AH1-702 GEN1
Adder
1.305
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24728605AND G2
Adder
1.715
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
274887GEN-1.85
Solar/Wind Harmer
2.896
276843GEN-1.7
Solar/Wind Harmer
0.312
958011AF2-095 GEN
Solar/Wind Harmer
7.825
274770LINCOLN ;1U
Adder
3.367
274771LINCOLN ;2U
Adder
3.367
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
9.586
274847GR RIDGE ;BU
Solar/Wind Harmer
2.709
958481AF2-142 GEN
Solar/Wind Harmer
7.986
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
972267AH1-718 GEN
Adder
2.123
247621Y3-024
Adder
0.12
25326509SID D
Adder
0.655
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
274861TOP CROP ;1U
Solar/Wind Harmer
0.294
274862TOP CROP ;2U
Solar/Wind Harmer
0.246
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
20.606
945411AF1-206 GEN
Solar/Wind Harmer
9.927
945641AF1-229 GEN
Solar/Wind Harmer
4.111
270499AE1-146 GEN
Solar/Wind Harmer
2.56
971549AH1-272 GEN
Solar/Wind Harmer
15.243
270297AD1-101 GEN
Solar/Wind Harmer
2.274
247607V1-011 GEN
Solar/Wind Harmer
2.793
957201AF2-014 GEN
Solar/Wind Harmer
3.188
270435AC2-044 GEN
Solar/Wind Harmer
1.406
944161AF1-084 GEN
Solar/Wind Harmer
1.521
966831AG1-554 GEN
Solar/Wind Harmer
0.805
971989AH1-539 GEN
Solar/Wind Harmer
8.703
965041AG1-368 GEN
Solar/Wind Harmer
6.611
965051AG1-369 GEN
Solar/Wind Harmer
3.281
971771AH1-392 GEN
Solar/Wind Harmer
5.706
270302AB2-170 GEN
Solar/Wind Harmer
5.304
270317AD1-130_GEN
Solar/Wind Harmer
2.033
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
2.444
958321AF2-126 GEN
Solar/Wind Harmer
1.823
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
5.213
270575GUS2 35KV
Solar/Wind Harmer
10.713
970217AG2-149 GEN
Solar/Wind Harmer
26.74
270044AE2-322 C
Solar/Wind Harmer
1.036
270404AC1-167 GEN
Solar/Wind Harmer
0.862
270258AD1-119 GEN
Solar/Wind Harmer
2.11
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
7.864
24441205WTRV SLR C
Solar/Wind Harmer
0.096
958091AF2-103 GEN
Solar/Wind Harmer
0.114
270491AE1-102 GEN2
Solar/Wind Harmer
0.914
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
1.971
270247TR4_N_V136
Solar/Wind Harmer
0.559
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
19.386
247643Z2-116 C
Solar/Wind Harmer
0.045
959331AF2-224 GEN
Solar/Wind Harmer
6.354
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.384
270043AE2-236 GEN
Solar/Wind Harmer
3.307
970349AG2-230 GEN
Solar/Wind Harmer
8.916
942871AE2-306 GEN
Solar/Wind Harmer
0.535
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
2.568
972231SS25-0005
Solar/Wind Harmer
5.294
972181SS23-001
Solar/Wind Harmer
3.309
274752CRETE EC ;2U
Adder
2.727
274753CRETE EC ;3U
Adder
2.727
964401AG1-302 GEN
Solar/Wind Harmer
5.044
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
3.312
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276772AC2-154 GEN
Solar/Wind Harmer
1.515
276806AD2-047 C O1
Solar/Wind Harmer
5.813
970941AG2-585 GEN
Solar/Wind Harmer
6.792
274772LINCOLN ;3U
Adder
3.367
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
15.632
939351AE1-166 GEN
Solar/Wind Harmer
3.194
276893AG1-478 C
Solar/Wind Harmer
0.225
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
15.071
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
9.586
970517AG2-330 GEN
Solar/Wind Harmer
8.694
943121AE2-341 GEN
Solar/Wind Harmer
7.988
943591AF1-030 GEN
Solar/Wind Harmer
5.325
276694AA1-018 GEN2
Solar/Wind Harmer
3.36
274682WAUKEGAN ;7U
Adder
9.512
972236AH1-702 GEN2
Adder
1.135
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
4.716
24728705AND G3
Adder
3.588
24728505AND G1
Adder
1.715
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
971769AH1-391 GEN
Solar/Wind Harmer
6.189
971567AH1-282 GEN
Solar/Wind Harmer
9.111
960681AF2-359 GEN
Solar/Wind Harmer
2.255
971347AH1-153 GEN
Solar/Wind Harmer
8.916
963791AG1-232 GEN
Solar/Wind Harmer
7.982
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
2.568
270071AF1-092 GEN
Solar/Wind Harmer
8.419
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
5.002
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
960591AF2-350 GEN
Solar/Wind Harmer
5.434
274775LINCOLN ;6U
Adder
3.367
274776LINCOLN ;7U
Adder
3.367
274777LINCOLN ;8U
Adder
3.367
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
2.523
970833AG2-524 GEN
Solar/Wind Harmer
4.678
970833AG2-524 GEN
Solar/Wind Harmer
2.176
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
24729505KEY G4
Adder
3.405
274823ROCKFORD ;21
Adder
10.105
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
944201AF1-088_MTX
Adder
0.5
991182J1586 G
External Queue
28.404245376586914
991177J1571 G
External Queue
18.513126373291016
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:234.28
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
991182J1586 G
External Queue
28.404245376586914
991177J1571 G
External Queue
18.513126373291016
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.02 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2047.43
MW Contribution:211.68
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.569
23888602TROY G2
50/50
2.569
972211AH1-690 GEN
50/50
211.679
23906902RICHG6
50/50
0.775
23906702RICHG4
50/50
0.773
23906802RICHG5
50/50
0.564
970817AG2-515 GEN
Solar/Wind Harmer
17.825
945411AF1-206 GEN
Solar/Wind Harmer
6.384
945641AF1-229 GEN
Solar/Wind Harmer
3.799
270499AE1-146 GEN
Solar/Wind Harmer
2.114
971549AH1-272 GEN
Solar/Wind Harmer
13.108
270297AD1-101 GEN
Solar/Wind Harmer
1.882
957201AF2-014 GEN
Solar/Wind Harmer
2.802
270435AC2-044 GEN
Solar/Wind Harmer
1.235
247607V1-011 GEN
Solar/Wind Harmer
2.395
944161AF1-084 GEN
Solar/Wind Harmer
1.31
966831AG1-554 GEN
Solar/Wind Harmer
0.689
23888802TROY G4
50/50
2.569
24190002OREGON_ST1
50/50
2.645
24189802OREGON_CT1
50/50
2.007
241996AE2-282_GEN
Solar/Wind Harmer
1.709
971677AH1-339 GEN
Solar/Wind Harmer
6.229
246938BC-WTG3
Solar/Wind Harmer
2.459
246937BC-WTG2
Solar/Wind Harmer
2.417
270007AE1-245 C
Solar/Wind Harmer
3.593
942801AE2-298 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
9.231
961051AF2-396 GEN
Solar/Wind Harmer
4.293
960981AF2-389 GEN
Solar/Wind Harmer
0.865
957891AF2-083 GEN
Solar/Wind Harmer
1.93
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.336
970611AG2-400 GEN
Solar/Wind Harmer
5.502
270526AF1-158 GEN
Solar/Wind Harmer
2.437
24441505OLIV SLR
Solar/Wind Harmer
0.072
270224U2-072_GEN2
Solar/Wind Harmer
1.039
270227U2-072_GEN3
Solar/Wind Harmer
1.039
270228U2-072_GEN4
Solar/Wind Harmer
1.039
270231U2-072_GEN5
Solar/Wind Harmer
1.039
965681AG1-436 GEN
Solar/Wind Harmer
6.439
965791AG1-447 GEN
Solar/Wind Harmer
3.294
274808UNIV PK N;4U
Adder
2.376
971989AH1-539 GEN
Solar/Wind Harmer
7.445
965041AG1-368 GEN
Solar/Wind Harmer
5.685
965051AG1-369 GEN
Solar/Wind Harmer
2.828
270302AB2-170 GEN
Solar/Wind Harmer
4.729
270317AD1-130_GEN
Solar/Wind Harmer
1.813
971567AH1-282 GEN
Solar/Wind Harmer
8.37
971771AH1-392 GEN
Solar/Wind Harmer
4.919
971769AH1-391 GEN
Solar/Wind Harmer
5.338
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
960681AF2-359 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
7.697
963791AG1-232 GEN
Solar/Wind Harmer
6.886
270536AF1-215 GEN2
Solar/Wind Harmer
2.218
270071AF1-092 GEN
Solar/Wind Harmer
7.266
274803UNIV PARK;6U
Adder
2.75
274888KELLY CRK;1U
Solar/Wind Harmer
2.773
274887GEN-1.85
Solar/Wind Harmer
2.503
276843GEN-1.7
Solar/Wind Harmer
0.269
942221AE2-234 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
6.763
274770LINCOLN ;1U
Adder
2.911
274771LINCOLN ;2U
Adder
2.911
972259AH1-714 GEN
Adder
8.899
274674JOLIET 9 ;6U
Adder
7.164
970321AG2-212 GEN
Solar/Wind Harmer
8.289
274847GR RIDGE ;BU
Solar/Wind Harmer
2.342
958481AF2-142 GEN
Solar/Wind Harmer
6.904
274696ROCKY RD ;4P
Adder
5.214
274814UNIV PK N;0U
Adder
2.407
274807UNIV PK N;3U
Adder
2.402
274805UNIV PK N;1U
Adder
2.392
274811UNIV PK N;7U
Adder
2.386
958391AF2-133 GEN
Solar/Wind Harmer
4.322
972037AH1-567 GEN1
Adder
0.086
274827FISK ;RP
Adder
3.654
960591AF2-350 GEN
Solar/Wind Harmer
4.697
274775LINCOLN ;6U
Adder
2.911
274776LINCOLN ;7U
Adder
2.911
274777LINCOLN ;8U
Adder
2.911
972227AH1-698 GEN1
Adder
1.222
274687WILL CNTY;4U
Adder
13.048
274687WILL CNTY;4U
Adder
13.048
274675JOLIET 29;7U
Adder
14.3
274675JOLIET 29;7U
Adder
13.789
274728ELWOOD EC;5P
Adder
7.649
274731ELWOOD EC;2P
Adder
7.649
274733ELWOOD EC;3P
Adder
7.649
274735ELWOOD EC;4P
Adder
7.649
270024AE2-089 GEN
Solar/Wind Harmer
2.183
970833AG2-524 GEN
Solar/Wind Harmer
4.044
970833AG2-524 GEN
Solar/Wind Harmer
1.881
274746AC1-111 G10
Adder
2.574
274744AC1-111 GEN8
Adder
2.574
24729505KEY G4
Adder
2.948
274823ROCKFORD ;21
Adder
8.739
241886AC2-103 GEN2
Solar/Wind Helper
5.94
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
203846AF2-130 C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.117
23906502RICHG2&3
50/50
1.301
241832AE2-181_GEN
Solar/Wind Harmer
1.668
958321AF2-126 GEN
Solar/Wind Harmer
1.231
270541AE2-072 C
Solar/Wind Harmer
4.058
270575GUS2 35KV
Solar/Wind Harmer
8.824
970217AG2-149 GEN
Solar/Wind Harmer
24.659
270044AE2-322 C
Solar/Wind Harmer
0.857
270404AC1-167 GEN
Solar/Wind Harmer
0.713
270258AD1-119 GEN
Solar/Wind Harmer
1.762
247604X1-042
Adder
0.26
270491AE1-102 GEN2
Solar/Wind Harmer
0.803
270588AE1-091_GEN
Solar/Wind Harmer
6.773
24441205WTRV SLR C
Solar/Wind Harmer
0.082
958091AF2-103 GEN
Solar/Wind Harmer
0.098
945111AF1-176 GEN
Solar/Wind Harmer
3.248
270191TR4_S_V150
Solar/Wind Harmer
1.699
270247TR4_N_V136
Solar/Wind Harmer
0.482
270485AE1-090_GEN
Solar/Wind Harmer
0.342
24642205MAYFLWER
Adder
0.356
970031AG2-029 GEN
Solar/Wind Harmer
16.707
247643Z2-116 C
Solar/Wind Harmer
0.039
959331AF2-224 GEN
Solar/Wind Harmer
5.502
965021AG1-366 GEN
Solar/Wind Harmer
1.28
942871AE2-306 GEN
Solar/Wind Harmer
0.477
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
270043AE2-236 GEN
Solar/Wind Harmer
2.848
970349AG2-230 GEN
Solar/Wind Harmer
7.697
270535AF1-215 GEN1
Solar/Wind Harmer
2.218
972231SS25-0005
Solar/Wind Harmer
4.574
972181SS23-001
Solar/Wind Harmer
2.859
274752CRETE EC ;2U
Adder
2.356
274753CRETE EC ;3U
Adder
2.356
964401AG1-302 GEN
Solar/Wind Harmer
4.359
274724RIVER EC ;11
Adder
8.473
959141AF2-205 GEN
Solar/Wind Harmer
2.862
274802UNIV PARK;5U
Adder
2.75
274826FISK ;BP
Adder
5.156
274800UNIV PARK;3U
Adder
2.742
972038AH1-567 GEN2
Adder
0.172
276772AC2-154 GEN
Solar/Wind Harmer
1.31
276806AD2-047 C O1
Solar/Wind Harmer
5.024
970941AG2-585 GEN
Solar/Wind Harmer
5.871
274772LINCOLN ;3U
Adder
2.911
972228AH1-698 GEN2
Adder
1.735
274676JOLIET 29;8U
Adder
13.789
276897AD1-100 C
Solar/Wind Harmer
13.513
939351AE1-166 GEN
Solar/Wind Harmer
2.761
276893AG1-478 C
Solar/Wind Harmer
0.194
274730ELWOOD EC;6P
Adder
7.649
274734ELWOOD EC;8P
Adder
7.649
274736ELWOOD EC;9P
Adder
7.649
970707AG2-453 GEN
Solar/Wind Harmer
13.028
274729ELWOOD EC;1P
Adder
7.649
971617AH1-308 GEN
Solar/Wind Harmer
2.704
970513AG2-328 GEN
Solar/Wind Harmer
8.289
970517AG2-330 GEN
Solar/Wind Harmer
7.518
943121AE2-341 GEN
Solar/Wind Harmer
6.906
943591AF1-030 GEN
Solar/Wind Harmer
4.604
276694AA1-018 GEN2
Solar/Wind Harmer
2.905
274682WAUKEGAN ;7U
Adder
8.225
972236AH1-702 GEN2
Adder
0.982
274760LEE CO EC;1U
Adder
4.128
274767LEE CO EC;8U
Adder
4.079
962511AG1-100 GEN
Solar/Wind Helper
0.311
203830AF1-094 GEN
Solar/Wind Helper
0.294
959441AF2-235 GEN
Solar/Wind Helper
0.133
254305AE2-115 C
Solar/Wind Helper
0.101
274695ROCKY RD ;2P
Adder
5.094
274693ROCKY RD ;1P
Adder
5.044
274697ROCKY RD ;3P
Adder
1.384
274683WAUKEGAN ;8U
Adder
9.635
274683WAUKEGAN ;8U
Adder
8.122
274764LEE CO EC;5U
Adder
4.138
274765LEE CO EC;6U
Adder
4.138
274762LEE CO EC;3U
Adder
4.128
274763LEE CO EC;4U
Adder
4.089
972267AH1-718 GEN
Adder
1.836
25326509SID D
Adder
0.577
247621Y3-024
Adder
0.104
203947AF1-006 C
Solar/Wind Helper
0.347
203980AG1-197 GEN
Solar/Wind Helper
0.226
203979AG1-198 GEN
Solar/Wind Helper
0.176
241967AE2-285_GEN
Solar/Wind Helper
0.305
241801AE1-079 GEN
Solar/Wind Helper
0.119
241985AE1-237 GEN
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.293
274861TOP CROP ;1U
Solar/Wind Harmer
0.254
274862TOP CROP ;2U
Solar/Wind Harmer
0.213
23888702TROY G3
50/50
2.569
972253AH1-711 GEN
50/50
78.462
24189902OREGON_CT2
50/50
1.966
23920202STRYCT
50/50
1.673
972301AH1-735 GEN
50/50
6.522
23906402RICHG1
50/50
1.304
23906502RICHG2&3
50/50
1.301
241858AF1-205_GEN
Solar/Wind Harmer
5.012
241808AF1-120 C
Solar/Wind Harmer
0.953
241840AF1-064_GEN
Solar/Wind Harmer
1.148
270361_3
Solar/Wind Harmer
7.49
960841AF2-375 GEN
Solar/Wind Harmer
3.331
970515AG2-329 GEN
Solar/Wind Harmer
11.182
247522W1-056 GEN
Solar/Wind Harmer
1.488
944231AF1-091 GEN
Solar/Wind Harmer
2.464
246936BC-WTG1
Solar/Wind Harmer
2.417
270489AE1-102 GEN1
Solar/Wind Harmer
0.803
965421AG1-410 GEN
Solar/Wind Harmer
18.338
270449AD2-020 GEN
Solar/Wind Harmer
1.642
943021AE2-325 GEN
Solar/Wind Harmer
2.133
24695305TIMB G C
Solar/Wind Harmer
3.212
945111AF1-176 GEN
Solar/Wind Harmer
10.248
270505AE1-170 C O1
Solar/Wind Harmer
8.607
247521TR3_G114
Solar/Wind Harmer
1.904
270246TR4_N_V150
Solar/Wind Harmer
0.482
270462AD2-086
Solar/Wind Harmer
3.934
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
1.226
965011AG1-365 GEN
Solar/Wind Harmer
5.502
270223U2-072_GEN1
Solar/Wind Harmer
1.039
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.44
270055AF2-134 C O1
Solar/Wind Harmer
1.479
274751CRETE EC ;1U
Adder
2.356
274754CRETE EC ;4U
Adder
2.356
958381AF2-132 GEN
Solar/Wind Harmer
4.359
964861AG1-349 GEN
Solar/Wind Harmer
3.77
971917AH1-482 GEN
Solar/Wind Harmer
4.351
274723RIVER EC ;12
Adder
8.575
274812UNIV PK N;8U
Adder
2.386
276164X3-005 C
Solar/Wind Harmer
0.334
274801UNIV PARK;4U
Adder
2.742
940581AE2-045 GEN
Solar/Wind Harmer
4.791
971605AH1-302 GEN
Solar/Wind Harmer
4.097
276776AD2-060 GEN
Solar/Wind Harmer
0.199
972207SS24-0001
Solar/Wind Harmer
10.349
274773LINCOLN ;4U
Adder
2.911
274774LINCOLN ;5U
Adder
2.911
274676JOLIET 29;8U
Adder
14.3
941551AE2-152 GEN
Solar/Wind Harmer
2.112
274732ELWOOD EC;7P
Adder
7.649
274674JOLIET 9 ;6U
Adder
7.164
970245AG2-165 GEN
Solar/Wind Harmer
8.289
274871GR RIDGE ;2U
Solar/Wind Harmer
3.56
274745AC1-111 GEN9
Adder
2.574
276691AA1-018 GEN1
Solar/Wind Harmer
0.214
274682WAUKEGAN ;7U
Adder
8.225
274828WAUKEGAN ;BP
Adder
5.051
274822ROCKFORD ;11
Adder
8.803
972235AH1-702 GEN1
Adder
1.129
274761LEE CO EC;2U
Adder
4.128
274766LEE CO EC;7U
Adder
4.079
241885AC2-103 GEN1
Solar/Wind Helper
5.94
241807AE2-176_GEN
Solar/Wind Helper
1.896
961971AG1-040 GEN
Solar/Wind Helper
0.304
203835AF1-098 GEN
Solar/Wind Helper
1.197
203860AG1-193 C
Solar/Wind Helper
0.135
241966AE1-183 GEN
Solar/Wind Helper
0.117
254303AC2-168 GEN
Solar/Wind Helper
0.068
991182J1586 G
External Queue
24.285308837890625
991177J1571 G
External Queue
14.387535095214844
990142J1224
External Queue
12.804616928100586
990527J1329
External Queue
1.7516577243804932
LAGNLTFEXP_LAGN->PJM
CLTF
5.44
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.193
TVALTFEXP_TVA->PJM
CLTF
2.504
NYPJM->LTFIMP_NY
CLTF
1.719
LGEELTFEXP_LGEE->PJM
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
1.711
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CPLELTFEXP_CPLE->PJM
CLTF
0.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.488
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.846
MECLTFEXP_MEC->PJM
CLTF
6.742
SIGELTFEXP_SIGE->PJM
CLTF
0.179

Details for 02N DEPT-02BRWELL 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02N DEPT-02BRWELL 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:171.21 %
Rating:230.0 MVA
Rating Type:B
MVA to Mitigate:393.79
MW Contribution:60.94
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.094
241885AC2-103 GEN1
Solar/Wind Harmer
2.6
972253AH1-711 GEN
Adder
11.964
274676JOLIET 29;8U
Adder
3.3
274732ELWOOD EC;7P
Adder
1.765
957471AF2-041 GEN
Solar/Wind Harmer
3.101
959081AF2-199 GEN
Solar/Wind Harmer
1.034
971067AG2-660 GEN
Solar/Wind Harmer
0.24
24191202EL_AA1-006
Adder
0.153
241886AC2-103 GEN2
Solar/Wind Harmer
2.6
972211AH1-690 GEN
Adder
60.94
274675JOLIET 29;7U
Adder
3.3
274675JOLIET 29;7U
Adder
3.182
274731ELWOOD EC;2P
Adder
1.765
274733ELWOOD EC;3P
Adder
1.765
274735ELWOOD EC;4P
Adder
1.765
274728ELWOOD EC;5P
Adder
1.765
971171AH1-044 GEN
Solar/Wind Harmer
2.067
971341AH1-150 GEN
Solar/Wind Harmer
2.067
971343AH1-151 GEN
Solar/Wind Harmer
2.067
274676JOLIET 29;8U
Adder
3.182
274729ELWOOD EC;1P
Adder
1.765
274730ELWOOD EC;6P
Adder
1.765
274734ELWOOD EC;8P
Adder
1.765
274736ELWOOD EC;9P
Adder
1.765
959091AF2-200 GEN
Solar/Wind Harmer
2.067
LAGNLTFEXP_LAGN->PJM
CLTF
1.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.499
TVALTFEXP_TVA->PJM
CLTF
0.53
NYPJM->LTFIMP_NY
CLTF
0.503
LGEELTFEXP_LGEE->PJM
CLTF
0.479
WECLTFEXP_WEC->PJM
CLTF
0.393
CPLELTFEXP_CPLE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.104
MECLTFEXP_MEC->PJM
CLTF
1.533
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02N DEPT-02BRWELL 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02N DEPT-02BRWELL 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:167.34 %
Rating:230.0 MVA
Rating Type:B
MVA to Mitigate:384.88
MW Contribution:60.97
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.094
972253AH1-711 GEN
Adder
11.97
274676JOLIET 29;8U
Adder
3.306
274732ELWOOD EC;7P
Adder
1.768
957471AF2-041 GEN
Solar/Wind Harmer
3.107
959081AF2-199 GEN
Solar/Wind Harmer
1.036
971067AG2-660 GEN
Solar/Wind Harmer
0.241
24191202EL_AA1-006
Adder
0.153
972211AH1-690 GEN
Adder
60.971
274675JOLIET 29;7U
Adder
3.306
274675JOLIET 29;7U
Adder
3.188
274731ELWOOD EC;2P
Adder
1.768
274733ELWOOD EC;3P
Adder
1.768
274735ELWOOD EC;4P
Adder
1.768
274728ELWOOD EC;5P
Adder
1.768
971171AH1-044 GEN
Solar/Wind Harmer
2.071
971341AH1-150 GEN
Solar/Wind Harmer
2.071
971343AH1-151 GEN
Solar/Wind Harmer
2.071
274676JOLIET 29;8U
Adder
3.188
274729ELWOOD EC;1P
Adder
1.768
274730ELWOOD EC;6P
Adder
1.768
274734ELWOOD EC;8P
Adder
1.768
274736ELWOOD EC;9P
Adder
1.768
959091AF2-200 GEN
Solar/Wind Harmer
2.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.505
TVALTFEXP_TVA->PJM
CLTF
0.532
NYPJM->LTFIMP_NY
CLTF
0.502
LGEELTFEXP_LGEE->PJM
CLTF
0.48
WECLTFEXP_WEC->PJM
CLTF
0.394
CPLELTFEXP_CPLE->PJM
CLTF
0.071
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.111
MECLTFEXP_MEC->PJM
CLTF
1.536
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 02NASA-02BEAVER 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02NASA-02BEAVER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:178.12 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:341.99
MW Contribution:54.56
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
1.851
971343AH1-151 GEN
Solar/Wind Harmer
1.851
24191202EL_AA1-006
Adder
0.138
972211AH1-690 GEN
Adder
54.557
274675JOLIET 29;7U
Adder
2.954
274675JOLIET 29;7U
Adder
2.849
274731ELWOOD EC;2P
Adder
1.58
274733ELWOOD EC;3P
Adder
1.58
274735ELWOOD EC;4P
Adder
1.58
274728ELWOOD EC;5P
Adder
1.58
971171AH1-044 GEN
Solar/Wind Harmer
1.851
274676JOLIET 29;8U
Adder
2.849
274729ELWOOD EC;1P
Adder
1.58
274730ELWOOD EC;6P
Adder
1.58
274734ELWOOD EC;8P
Adder
1.58
274736ELWOOD EC;9P
Adder
1.58
959091AF2-200 GEN
Solar/Wind Harmer
1.851
241807AE2-176_GEN
Solar/Wind Harmer
2.77
972253AH1-711 GEN
Adder
10.711
274676JOLIET 29;8U
Adder
2.954
274732ELWOOD EC;7P
Adder
1.58
957471AF2-041 GEN
Solar/Wind Harmer
2.776
959081AF2-199 GEN
Solar/Wind Harmer
0.925
971067AG2-660 GEN
Solar/Wind Harmer
0.215
LAGNLTFEXP_LAGN->PJM
CLTF
1.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.447
TVALTFEXP_TVA->PJM
CLTF
0.474
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.429
WECLTFEXP_WEC->PJM
CLTF
0.352
CPLELTFEXP_CPLE->PJM
CLTF
0.061
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.39
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.883
MECLTFEXP_MEC->PJM
CLTF
1.372
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 02NASA-02BEAVER 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02NASA-02BEAVER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:176.43 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:338.74
MW Contribution:54.59
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
1.854
971343AH1-151 GEN
Solar/Wind Harmer
1.854
24191202EL_AA1-006
Adder
0.138
972211AH1-690 GEN
Adder
54.585
274675JOLIET 29;7U
Adder
2.96
274675JOLIET 29;7U
Adder
2.854
274731ELWOOD EC;2P
Adder
1.583
274733ELWOOD EC;3P
Adder
1.583
274735ELWOOD EC;4P
Adder
1.583
274728ELWOOD EC;5P
Adder
1.583
971171AH1-044 GEN
Solar/Wind Harmer
1.854
274676JOLIET 29;8U
Adder
2.854
274729ELWOOD EC;1P
Adder
1.583
274730ELWOOD EC;6P
Adder
1.583
274734ELWOOD EC;8P
Adder
1.583
274736ELWOOD EC;9P
Adder
1.583
959091AF2-200 GEN
Solar/Wind Harmer
1.854
241807AE2-176_GEN
Solar/Wind Harmer
2.771
972253AH1-711 GEN
Adder
10.717
274676JOLIET 29;8U
Adder
2.96
274732ELWOOD EC;7P
Adder
1.583
957471AF2-041 GEN
Solar/Wind Harmer
2.781
959081AF2-199 GEN
Solar/Wind Harmer
0.927
971067AG2-660 GEN
Solar/Wind Harmer
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
1.05
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.476
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.43
WECLTFEXP_WEC->PJM
CLTF
0.353
CPLELTFEXP_CPLE->PJM
CLTF
0.063
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.78
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.89
MECLTFEXP_MEC->PJM
CLTF
1.375
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:314.0 MVA
Rating Type:B
MVA to Mitigate:341.82
MW Contribution:66.07
Bus #Bus NameTypeMW Contribution
241807AE2-176_GEN
Solar/Wind Harmer
3.455
241885AC2-103 GEN1
Solar/Wind Harmer
2.831
274732ELWOOD EC;7P
Adder
1.894
23929302BS-PKR
Adder
0.667
274729ELWOOD EC;1P
Adder
1.893
24191202EL_AA1-006
50/50
0.219
241886AC2-103 GEN2
Solar/Wind Harmer
2.831
972211AH1-690 GEN
Adder
66.067
274731ELWOOD EC;2P
Adder
1.893
274733ELWOOD EC;3P
Adder
1.893
274735ELWOOD EC;4P
Adder
1.893
274728ELWOOD EC;5P
Adder
1.894
274730ELWOOD EC;6P
Adder
1.894
274734ELWOOD EC;8P
Adder
1.894
274736ELWOOD EC;9P
Adder
1.894
LAGNLTFEXP_LAGN->PJM
CLTF
1.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.525
TVALTFEXP_TVA->PJM
CLTF
0.565
NYPJM->LTFIMP_NY
CLTF
0.533
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.422
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
23.776
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.242
MECLTFEXP_MEC->PJM
CLTF
1.642
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02OAKPOINT-02BEAVER 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.41 %
Rating:314.0 MVA
Rating Type:B
MVA to Mitigate:334.12
MW Contribution:66.1
Bus #Bus NameTypeMW Contribution
24191202EL_AA1-006
50/50
0.219
972211AH1-690 GEN
Adder
66.102
274731ELWOOD EC;2P
Adder
1.897
274733ELWOOD EC;3P
Adder
1.897
274735ELWOOD EC;4P
Adder
1.897
274728ELWOOD EC;5P
Adder
1.897
241886AC2-103 GEN2
Solar/Wind Helper
1.12
23929302BS-PKR
Adder
0.667
274729ELWOOD EC;1P
Adder
1.897
274730ELWOOD EC;6P
Adder
1.897
274734ELWOOD EC;8P
Adder
1.897
274736ELWOOD EC;9P
Adder
1.897
241807AE2-176_GEN
Solar/Wind Harmer
3.455
274732ELWOOD EC;7P
Adder
1.897
241885AC2-103 GEN1
Solar/Wind Helper
1.12
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.532
TVALTFEXP_TVA->PJM
CLTF
0.567
NYPJM->LTFIMP_NY
CLTF
0.532
LGEELTFEXP_LGEE->PJM
CLTF
0.512
WECLTFEXP_WEC->PJM
CLTF
0.423
CPLELTFEXP_CPLE->PJM
CLTF
0.073
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
23.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.25
MECLTFEXP_MEC->PJM
CLTF
1.646
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 02OTTAWA-02LAKVEW 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02OTTAWA-02LAKVEW 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:516.0 MVA
Rating Type:B
MVA to Mitigate:597.63
MW Contribution:89.7
Bus #Bus NameTypeMW Contribution
23860302FRMENG 3
50/50
1.987
241858AF1-205_GEN
Solar/Wind Harmer
2.226
241808AF1-120 C
Solar/Wind Harmer
0.495
972253AH1-711 GEN
Adder
17.007
241840AF1-064_GEN
Solar/Wind Harmer
0.592
23920202STRYCT
Adder
0.726
972301AH1-735 GEN
Adder
2.634
23906402RICHG1
Adder
0.527
23906502RICHG2&3
Adder
0.526
241807AE2-176_GEN
Solar/Wind Helper
1.132
241885AC2-103 GEN1
Solar/Wind Helper
1.373
23929302BS-PKR
Adder
1.153
241832AE2-181_GEN
Solar/Wind Harmer
0.794
958321AF2-126 GEN
Solar/Wind Harmer
0.635
23906502RICHG2&3
Adder
0.526
23860102FRMENG 1
50/50
0.973
23860202FRMENG 2
50/50
0.973
972211AH1-690 GEN
Adder
89.703
945411AF1-206 GEN
Solar/Wind Harmer
3.313
970817AG2-515 GEN
Solar/Wind Harmer
5.423
241886AC2-103 GEN2
Solar/Wind Helper
1.373
241996AE2-282_GEN
Solar/Wind Harmer
0.887
LAGNLTFEXP_LAGN->PJM
CLTF
1.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.776
TVALTFEXP_TVA->PJM
CLTF
0.797
NYPJM->LTFIMP_NY
CLTF
0.733
LGEELTFEXP_LGEE->PJM
CLTF
0.717
WECLTFEXP_WEC->PJM
CLTF
0.587
CPLELTFEXP_CPLE->PJM
CLTF
0.115
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.928
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.159
MECLTFEXP_MEC->PJM
CLTF
2.29
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 02W.FREM-05FRMNT 138.0 kV Ckt 1 line l/o AEP_P4_#17249_05FOSTOR 345_A1_SRT-A


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02W.FREM-05FRMNT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17249_05FOSTOR 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:380.0 MVA
Rating Type:B
MVA to Mitigate:413.58
MW Contribution:97.56
Bus #Bus NameTypeMW Contribution
23860302FRMENG 3
50/50
4.356
241807AE2-176_GEN
Solar/Wind Harmer
4.424
972253AH1-711 GEN
Adder
19.986
241858AF1-205_GEN
Solar/Wind Harmer
2.178
241885AC2-103 GEN1
Solar/Wind Harmer
2.972
241808AF1-120 C
Solar/Wind Harmer
0.45
23920202STRYCT
Adder
0.614
960841AF2-375 GEN
Solar/Wind Helper
1.757
247522W1-056 GEN
Solar/Wind Helper
0.969
23860102FRMENG 1
50/50
2.133
23929302BS-PKR
Adder
1.119
241832AE2-181_GEN
Solar/Wind Harmer
0.701
23860202FRMENG 2
50/50
2.133
24191202EL_AA1-006
Adder
0.178
972211AH1-690 GEN
Adder
97.565
970817AG2-515 GEN
Solar/Wind Harmer
5.972
241886AC2-103 GEN2
Solar/Wind Harmer
2.972
945411AF1-206 GEN
Solar/Wind Harmer
3.016
270499AE1-146 GEN
Solar/Wind Helper
2.604
945641AF1-229 GEN
Solar/Wind Helper
0.865
966831AG1-554 GEN
Solar/Wind Helper
0.496
241996AE2-282_GEN
Solar/Wind Harmer
0.807
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.439
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.353
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
G-007ALTFEXP_G-007A->PJM
CMTX
0.175
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.21
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.498
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.186
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.721

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.99 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1536.23
MW Contribution:87.56
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
0.947
270223U2-072_GEN1
Solar/Wind Harmer
8.675
270578AF1-285 GEN2
Solar/Wind Harmer
5.305
270391AF1-285 GEN3
Solar/Wind Harmer
5.305
270462AD2-086
Solar/Wind Harmer
26.506
246936BC-WTG1
Solar/Wind Harmer
4.395
270489AE1-102 GEN1
Solar/Wind Harmer
1.46
965421AG1-410 GEN
Solar/Wind Harmer
32.457
247522W1-056 GEN
Solar/Wind Harmer
1.843
960841AF2-375 GEN
Solar/Wind Harmer
3.015
24695305TIMB G C
Solar/Wind Harmer
4.219
270361_3
Solar/Wind Harmer
6.463
247521TR3_G114
Solar/Wind Harmer
2.408
270246TR4_N_V150
Solar/Wind Harmer
0.609
965011AG1-365 GEN
Solar/Wind Harmer
6.922
23906502RICHG2&3
Adder
0.822
972301AH1-735 GEN
Adder
4.089
23906402RICHG1
Adder
0.818
241840AF1-064_GEN
Solar/Wind Harmer
0.752
23920202STRYCT
Adder
0.86
944231AF1-091 GEN
Solar/Wind Harmer
2.303
241808AF1-120 C
Solar/Wind Harmer
0.537
241858AF1-205_GEN
Solar/Wind Harmer
2.383
972253AH1-711 GEN
Adder
18.549
270063AE2-323 C
Solar/Wind Harmer
1.091
24639705ELKHART HY
Adder
0.068
945111AF1-176 GEN
Solar/Wind Harmer
7.706
270349AD2-093_GEN
Solar/Wind Helper
1.798
270466AD2-091
50/50
22.116
270224U2-072_GEN2
Solar/Wind Harmer
8.675
270227U2-072_GEN3
Solar/Wind Harmer
8.675
270228U2-072_GEN4
Solar/Wind Harmer
8.675
270231U2-072_GEN5
Solar/Wind Harmer
8.675
246938BC-WTG3
Solar/Wind Harmer
4.471
965431AG1-411 GEN
50/50
12.58
24727105RPMNG2
50/50
0.95
942871AE2-306 GEN
Solar/Wind Harmer
3.979
270391AF1-285 GEN3
Solar/Wind Harmer
2.041
270485AE1-090_GEN
Solar/Wind Harmer
2.304
270491AE1-102 GEN2
Solar/Wind Harmer
1.46
270588AE1-091_GEN
Solar/Wind Harmer
10.946
270541AE2-072 C
Solar/Wind Harmer
3.904
958091AF2-103 GEN
Solar/Wind Harmer
0.136
270575GUS2 35KV
Solar/Wind Harmer
7.614
270258AD1-119 GEN
Solar/Wind Harmer
2.055
270044AE2-322 C
Solar/Wind Harmer
0.958
270404AC1-167 GEN
Solar/Wind Harmer
0.797
270191TR4_S_V150
Solar/Wind Harmer
2.148
270036AE2-216 BAT
50/50
24.327
24727205RPMNG3
50/50
0.942
270284AF1-227 GEN1
Solar/Wind Harmer
35.4
270286AF1-227 GEN2
Solar/Wind Harmer
13.096
270287AF1-227 GEN3
Solar/Wind Harmer
13.096
270578AF1-285 GEN2
Solar/Wind Harmer
2.041
270302AB2-170 GEN
Solar/Wind Harmer
31.863
270317AD1-130_GEN
Solar/Wind Harmer
12.215
957201AF2-014 GEN
Solar/Wind Harmer
5.094
270435AC2-044 GEN
Solar/Wind Harmer
2.246
270297AD1-101 GEN
Solar/Wind Harmer
2.352
247607V1-011 GEN
Solar/Wind Harmer
3.327
966831AG1-554 GEN
Solar/Wind Harmer
0.997
971989AH1-539 GEN
Solar/Wind Harmer
10.779
270499AE1-146 GEN
Solar/Wind Harmer
2.04
965051AG1-369 GEN
Solar/Wind Harmer
3.576
965041AG1-368 GEN
Solar/Wind Harmer
7.155
945411AF1-206 GEN
Solar/Wind Harmer
3.599
970817AG2-515 GEN
Solar/Wind Harmer
5.709
972211AH1-690 GEN
Adder
87.557
963791AG1-232 GEN
Solar/Wind Harmer
7.374
945641AF1-229 GEN
Solar/Wind Harmer
1.909
270071AF1-092 GEN
Solar/Wind Harmer
6.82
971549AH1-272 GEN
Solar/Wind Harmer
8.28
270024AE2-089 GEN
Solar/Wind Harmer
2.024
270520AE2-214 GEN
Solar/Wind Helper
2.538
270054AF2-122 C O1
Solar/Wind Helper
0.659
270247TR4_N_V136
Solar/Wind Harmer
0.609
959331AF2-224 GEN
Solar/Wind Harmer
6.922
965021AG1-366 GEN
Solar/Wind Harmer
1.61
23906502RICHG2&3
Adder
0.822
958321AF2-126 GEN
Solar/Wind Harmer
0.806
241832AE2-181_GEN
Solar/Wind Harmer
0.902
23929302BS-PKR
Adder
0.782
970031AG2-029 GEN
Solar/Wind Harmer
15.427
270043AE2-236 GEN
Solar/Wind Harmer
2.738
270377AD1-106 GEN
Solar/Wind Harmer
2.718
945111AF1-176 GEN
Solar/Wind Harmer
2.442
247643Z2-116 C
Solar/Wind Harmer
0.03
971617AH1-308 GEN
Solar/Wind Harmer
2.507
246937BC-WTG2
Solar/Wind Harmer
4.395
270007AE1-245 C
Solar/Wind Harmer
4.993
942801AE2-298 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.922
971677AH1-339 GEN
Solar/Wind Harmer
5.222
241996AE2-282_GEN
Solar/Wind Harmer
0.963
247620Y3-023
Adder
0.211
971231AH1-075 GEN
Solar/Wind Harmer
0.352
942221AE2-234 GEN
Solar/Wind Harmer
0.32
270216AD2-079_GEN
Solar/Wind Harmer
0.262
270471AD2-092_GEN
Solar/Wind Helper
1.798
946101AF1-275 GEN
Solar/Wind Helper
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
2.114
TVALTFEXP_TVA->PJM
CLTF
0.753
NYPJM->LTFIMP_NY
CLTF
0.798
LGEELTFEXP_LGEE->PJM
CLTF
0.744
WECLTFEXP_WEC->PJM
CLTF
1.222
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.369
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.723
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.052
MECLTFEXP_MEC->PJM
CLTF
4.384
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1443.45
MW Contribution:94.17
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
22.679
270224U2-072_GEN2
Solar/Wind Harmer
8.881
270227U2-072_GEN3
Solar/Wind Harmer
8.881
270228U2-072_GEN4
Solar/Wind Harmer
8.881
270231U2-072_GEN5
Solar/Wind Harmer
8.881
246938BC-WTG3
Solar/Wind Harmer
4.658
246937BC-WTG2
Solar/Wind Harmer
4.579
270007AE1-245 C
Solar/Wind Harmer
5.246
942801AE2-298 GEN
Solar/Wind Harmer
1.244
970611AG2-400 GEN
Solar/Wind Harmer
7.215
971677AH1-339 GEN
Solar/Wind Harmer
5.666
241996AE2-282_GEN
Solar/Wind Harmer
1.03
971231AH1-075 GEN
Solar/Wind Harmer
0.402
247620Y3-023
Adder
0.219
942221AE2-234 GEN
Solar/Wind Harmer
0.335
270216AD2-079_GEN
Solar/Wind Harmer
0.272
961051AF2-396 GEN
Solar/Wind Harmer
7.083
961051AF2-396 GEN
Solar/Wind Harmer
3.295
960981AF2-389 GEN
Solar/Wind Harmer
0.67
957891AF2-083 GEN
Solar/Wind Harmer
1.495
270471AD2-092_GEN
Solar/Wind Helper
1.579
965431AG1-411 GEN
50/50
13.106
24727105RPMNG2
50/50
0.99
942871AE2-306 GEN
Solar/Wind Harmer
4.074
270391AF1-285 GEN3
Solar/Wind Harmer
2.089
270485AE1-090_GEN
Solar/Wind Harmer
2.363
270491AE1-102 GEN2
Solar/Wind Harmer
1.521
270588AE1-091_GEN
Solar/Wind Harmer
11.649
270541AE2-072 C
Solar/Wind Harmer
4.133
958091AF2-103 GEN
Solar/Wind Harmer
0.143
270575GUS2 35KV
Solar/Wind Harmer
8.155
270258AD1-119 GEN
Solar/Wind Harmer
2.165
270044AE2-322 C
Solar/Wind Harmer
1.008
270404AC1-167 GEN
Solar/Wind Harmer
0.84
270191TR4_S_V150
Solar/Wind Harmer
2.259
270247TR4_N_V136
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
959331AF2-224 GEN
Solar/Wind Harmer
7.215
965021AG1-366 GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
0.86
24727005RPMNG1
50/50
0.986
270223U2-072_GEN1
Solar/Wind Harmer
8.881
270578AF1-285 GEN2
Solar/Wind Harmer
5.431
270391AF1-285 GEN3
Solar/Wind Harmer
5.431
270462AD2-086
Solar/Wind Harmer
27.18
246936BC-WTG1
Solar/Wind Harmer
4.579
270489AE1-102 GEN1
Solar/Wind Harmer
1.521
965421AG1-410 GEN
Solar/Wind Harmer
33.814
247522W1-056 GEN
Solar/Wind Harmer
1.977
960841AF2-375 GEN
Solar/Wind Harmer
3.224
24695305TIMB G C
Solar/Wind Harmer
4.424
270361_3
Solar/Wind Harmer
6.922
247521TR3_G114
Solar/Wind Harmer
2.532
270246TR4_N_V150
Solar/Wind Harmer
0.641
23906502RICHG2&3
Adder
0.873
965011AG1-365 GEN
Solar/Wind Harmer
7.215
972301AH1-735 GEN
Adder
4.34
23906402RICHG1
Adder
0.868
241840AF1-064_GEN
Solar/Wind Harmer
0.802
23920202STRYCT
Adder
0.918
944231AF1-091 GEN
Solar/Wind Harmer
2.414
241808AF1-120 C
Solar/Wind Harmer
0.574
241858AF1-205_GEN
Solar/Wind Harmer
2.55
270036AE2-216 BAT
50/50
24.946
24727205RPMNG3
50/50
0.982
270284AF1-227 GEN1
Solar/Wind Harmer
36.123
270286AF1-227 GEN2
Solar/Wind Harmer
13.364
270287AF1-227 GEN3
Solar/Wind Harmer
13.364
270578AF1-285 GEN2
Solar/Wind Harmer
2.089
270302AB2-170 GEN
Solar/Wind Harmer
32.674
270317AD1-130_GEN
Solar/Wind Harmer
12.526
957201AF2-014 GEN
Solar/Wind Harmer
5.307
270435AC2-044 GEN
Solar/Wind Harmer
2.34
966831AG1-554 GEN
Solar/Wind Harmer
1.072
971989AH1-539 GEN
Solar/Wind Harmer
11.594
270297AD1-101 GEN
Solar/Wind Harmer
2.489
247607V1-011 GEN
Solar/Wind Harmer
3.496
270499AE1-146 GEN
Solar/Wind Harmer
2.176
965051AG1-369 GEN
Solar/Wind Harmer
3.76
965041AG1-368 GEN
Solar/Wind Harmer
7.49
945411AF1-206 GEN
Solar/Wind Harmer
3.846
970817AG2-515 GEN
Solar/Wind Harmer
6.123
972211AH1-690 GEN
Adder
94.166
945641AF1-229 GEN
Solar/Wind Harmer
2.109
963791AG1-232 GEN
Solar/Wind Harmer
7.721
270071AF1-092 GEN
Solar/Wind Harmer
7.086
971549AH1-272 GEN
Solar/Wind Harmer
8.654
270024AE2-089 GEN
Solar/Wind Harmer
2.13
944161AF1-084 GEN
Solar/Wind Harmer
0.983
971771AH1-392 GEN
Solar/Wind Harmer
3.88
241832AE2-181_GEN
Solar/Wind Harmer
0.964
23929302BS-PKR
Adder
0.842
970031AG2-029 GEN
Solar/Wind Harmer
16.057
270043AE2-236 GEN
Solar/Wind Harmer
2.85
270377AD1-106 GEN
Solar/Wind Harmer
3.103
971617AH1-308 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
2.538
247643Z2-116 C
Solar/Wind Harmer
0.031
247604X1-042
Adder
0.185
24441205WTRV SLR C
Solar/Wind Harmer
0.06
944531AF1-118 GEN
Solar/Wind Harmer
15.258
24642205MAYFLWER
Adder
0.276
972253AH1-711 GEN
Adder
19.928
270063AE2-323 C
Solar/Wind Harmer
1.135
24639705ELKHART HY
Adder
0.071
945111AF1-176 GEN
Solar/Wind Harmer
8.008
270449AD2-020 GEN
Solar/Wind Harmer
1.247
943021AE2-325 GEN
Solar/Wind Harmer
1.62
270505AE1-170 C O1
Solar/Wind Harmer
6.636
270428AC2-015 C
Solar/Wind Harmer
2.363
270349AD2-093_GEN
Solar/Wind Helper
1.579
LAGNLTFEXP_LAGN->PJM
CLTF
1.858
TVALTFEXP_TVA->PJM
CLTF
0.593
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
0.737
WECLTFEXP_WEC->PJM
CLTF
1.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.545
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.885
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.552
MECLTFEXP_MEC->PJM
CLTF
4.428
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1355.58
MW Contribution:74.51
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
22.925
270284AF1-227 GEN1
Solar/Wind Harmer
33.804
270286AF1-227 GEN2
Solar/Wind Harmer
12.506
270287AF1-227 GEN3
Solar/Wind Harmer
12.506
270578AF1-285 GEN2
Solar/Wind Harmer
1.932
270302AB2-170 GEN
Solar/Wind Harmer
30.026
270317AD1-130_GEN
Solar/Wind Harmer
11.511
957201AF2-014 GEN
Solar/Wind Harmer
4.391
270435AC2-044 GEN
Solar/Wind Harmer
1.937
966831AG1-554 GEN
Solar/Wind Harmer
0.866
971989AH1-539 GEN
Solar/Wind Harmer
9.369
270297AD1-101 GEN
Solar/Wind Harmer
1.968
270499AE1-146 GEN
Solar/Wind Harmer
1.774
247607V1-011 GEN
Solar/Wind Harmer
2.755
965041AG1-368 GEN
Solar/Wind Harmer
5.71
965051AG1-369 GEN
Solar/Wind Harmer
2.846
945411AF1-206 GEN
Solar/Wind Harmer
3.028
970817AG2-515 GEN
Solar/Wind Harmer
4.828
972211AH1-690 GEN
Adder
74.506
945641AF1-229 GEN
Solar/Wind Harmer
1.612
270520AE2-214 GEN
Solar/Wind Helper
2.757
241973AD2-163_GEN1
Solar/Wind Helper
0.894
270054AF2-122 C O1
Solar/Wind Helper
0.641
253383AE2-342_GEN
Solar/Wind Helper
0.362
270466AD2-091
50/50
20.841
270224U2-072_GEN2
Solar/Wind Harmer
8.212
270227U2-072_GEN3
Solar/Wind Harmer
8.212
270228U2-072_GEN4
Solar/Wind Harmer
8.212
270231U2-072_GEN5
Solar/Wind Harmer
8.212
246938BC-WTG3
Solar/Wind Harmer
3.854
246937BC-WTG2
Solar/Wind Harmer
3.789
270007AE1-245 C
Solar/Wind Harmer
4.135
942801AE2-298 GEN
Solar/Wind Harmer
0.965
971677AH1-339 GEN
Solar/Wind Harmer
4.494
970611AG2-400 GEN
Solar/Wind Harmer
5.449
241996AE2-282_GEN
Solar/Wind Harmer
0.811
270471AD2-092_GEN
Solar/Wind Helper
2.275
946101AF1-275 GEN
Solar/Wind Helper
0.345
965431AG1-411 GEN
50/50
10.787
942871AE2-306 GEN
Solar/Wind Harmer
3.767
270391AF1-285 GEN3
Solar/Wind Harmer
1.932
270485AE1-090_GEN
Solar/Wind Harmer
2.171
270491AE1-102 GEN2
Solar/Wind Harmer
1.259
270588AE1-091_GEN
Solar/Wind Harmer
9.577
270541AE2-072 C
Solar/Wind Harmer
3.358
958091AF2-103 GEN
Solar/Wind Harmer
0.113
270575GUS2 35KV
Solar/Wind Harmer
6.607
270258AD1-119 GEN
Solar/Wind Harmer
1.667
270044AE2-322 C
Solar/Wind Harmer
0.777
270404AC1-167 GEN
Solar/Wind Harmer
0.647
23906502RICHG2&3
Adder
0.689
958321AF2-126 GEN
Solar/Wind Harmer
0.686
270191TR4_S_V150
Solar/Wind Harmer
1.71
270247TR4_N_V136
Solar/Wind Harmer
0.485
959331AF2-224 GEN
Solar/Wind Harmer
5.449
965021AG1-366 GEN
Solar/Wind Harmer
1.267
241832AE2-181_GEN
Solar/Wind Harmer
0.759
23929302BS-PKR
Adder
0.665
241974AD2-163_GEN2
Solar/Wind Helper
0.894
241955AC1-078 GEN
Solar/Wind Helper
0.968
270223U2-072_GEN1
Solar/Wind Harmer
8.212
270578AF1-285 GEN2
Solar/Wind Harmer
5.022
270391AF1-285 GEN3
Solar/Wind Harmer
5.022
270462AD2-086
Solar/Wind Harmer
24.978
246936BC-WTG1
Solar/Wind Harmer
3.789
270489AE1-102 GEN1
Solar/Wind Harmer
1.259
965421AG1-410 GEN
Solar/Wind Harmer
27.831
247522W1-056 GEN
Solar/Wind Harmer
1.6
960841AF2-375 GEN
Solar/Wind Harmer
2.619
270361_3
Solar/Wind Harmer
5.608
24695305TIMB G C
Solar/Wind Harmer
3.424
23906502RICHG2&3
Adder
0.689
241840AF1-064_GEN
Solar/Wind Harmer
0.64
247521TR3_G114
Solar/Wind Harmer
1.917
270246TR4_N_V150
Solar/Wind Harmer
0.485
972301AH1-735 GEN
Adder
3.425
23906402RICHG1
Adder
0.685
965011AG1-365 GEN
Solar/Wind Harmer
5.449
23920202STRYCT
Adder
0.724
241808AF1-120 C
Solar/Wind Harmer
0.452
241858AF1-205_GEN
Solar/Wind Harmer
2.013
972253AH1-711 GEN
Adder
15.822
944231AF1-091 GEN
Solar/Wind Harmer
1.794
270349AD2-093_GEN
Solar/Wind Helper
2.275
LAGNLTFEXP_LAGN->PJM
CLTF
1.249
TVALTFEXP_TVA->PJM
CLTF
0.415
NYPJM->LTFIMP_NY
CLTF
0.554
LGEELTFEXP_LGEE->PJM
CLTF
0.36
WECLTFEXP_WEC->PJM
CLTF
0.796
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.659
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.447
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.633
MECLTFEXP_MEC->PJM
CLTF
2.816
SIGELTFEXP_SIGE->PJM
CLTF
0.05

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:1302.0 MVA
Rating Type:B
MVA to Mitigate:1346.92
MW Contribution:81.32
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
23.248
24727205RPMNG3
50/50
0.868
270284AF1-227 GEN1
Solar/Wind Harmer
34.078
270286AF1-227 GEN2
Solar/Wind Harmer
12.607
270287AF1-227 GEN3
Solar/Wind Harmer
12.607
270578AF1-285 GEN2
Solar/Wind Harmer
1.955
270302AB2-170 GEN
Solar/Wind Harmer
30.45
270317AD1-130_GEN
Solar/Wind Harmer
11.673
957201AF2-014 GEN
Solar/Wind Harmer
4.709
270435AC2-044 GEN
Solar/Wind Harmer
2.077
966831AG1-554 GEN
Solar/Wind Harmer
0.919
971989AH1-539 GEN
Solar/Wind Harmer
9.938
270297AD1-101 GEN
Solar/Wind Harmer
2.134
247607V1-011 GEN
Solar/Wind Harmer
3.026
270499AE1-146 GEN
Solar/Wind Harmer
1.886
965041AG1-368 GEN
Solar/Wind Harmer
6.484
965051AG1-369 GEN
Solar/Wind Harmer
3.22
945411AF1-206 GEN
Solar/Wind Harmer
3.324
970817AG2-515 GEN
Solar/Wind Harmer
5.288
972211AH1-690 GEN
Adder
81.324
963791AG1-232 GEN
Solar/Wind Harmer
6.585
945641AF1-229 GEN
Solar/Wind Harmer
1.758
270520AE2-214 GEN
Solar/Wind Helper
2.563
241973AD2-163_GEN1
Solar/Wind Helper
0.822
270466AD2-091
50/50
21.135
270224U2-072_GEN2
Solar/Wind Harmer
8.311
270227U2-072_GEN3
Solar/Wind Harmer
8.311
270228U2-072_GEN4
Solar/Wind Harmer
8.311
270231U2-072_GEN5
Solar/Wind Harmer
8.311
246938BC-WTG3
Solar/Wind Harmer
4.133
246937BC-WTG2
Solar/Wind Harmer
4.063
270007AE1-245 C
Solar/Wind Harmer
4.541
942801AE2-298 GEN
Solar/Wind Harmer
1.064
970611AG2-400 GEN
Solar/Wind Harmer
6.286
971677AH1-339 GEN
Solar/Wind Harmer
4.825
241996AE2-282_GEN
Solar/Wind Harmer
0.89
270471AD2-092_GEN
Solar/Wind Helper
2.202
946101AF1-275 GEN
Solar/Wind Helper
0.321
965431AG1-411 GEN
50/50
11.618
24727105RPMNG2
50/50
0.875
942871AE2-306 GEN
Solar/Wind Harmer
3.812
270391AF1-285 GEN3
Solar/Wind Harmer
1.955
270485AE1-090_GEN
Solar/Wind Harmer
2.202
270491AE1-102 GEN2
Solar/Wind Harmer
1.35
270588AE1-091_GEN
Solar/Wind Harmer
10.088
270541AE2-072 C
Solar/Wind Harmer
3.595
958091AF2-103 GEN
Solar/Wind Harmer
0.124
270575GUS2 35KV
Solar/Wind Harmer
7.051
270258AD1-119 GEN
Solar/Wind Harmer
1.859
270044AE2-322 C
Solar/Wind Harmer
0.868
270404AC1-167 GEN
Solar/Wind Harmer
0.723
270191TR4_S_V150
Solar/Wind Harmer
1.934
270247TR4_N_V136
Solar/Wind Harmer
0.549
959331AF2-224 GEN
Solar/Wind Harmer
6.286
965021AG1-366 GEN
Solar/Wind Harmer
1.462
23906502RICHG2&3
Adder
0.756
958321AF2-126 GEN
Solar/Wind Harmer
0.744
241832AE2-181_GEN
Solar/Wind Harmer
0.833
23929302BS-PKR
Adder
0.727
970031AG2-029 GEN
Solar/Wind Harmer
13.816
270043AE2-236 GEN
Solar/Wind Harmer
2.443
241974AD2-163_GEN2
Solar/Wind Helper
0.822
24727005RPMNG1
50/50
0.872
270223U2-072_GEN1
Solar/Wind Harmer
8.311
270578AF1-285 GEN2
Solar/Wind Harmer
5.083
270391AF1-285 GEN3
Solar/Wind Harmer
5.083
270462AD2-086
Solar/Wind Harmer
25.33
246936BC-WTG1
Solar/Wind Harmer
4.063
270489AE1-102 GEN1
Solar/Wind Harmer
1.35
965421AG1-410 GEN
Solar/Wind Harmer
29.973
247522W1-056 GEN
Solar/Wind Harmer
1.7
960841AF2-375 GEN
Solar/Wind Harmer
2.791
24695305TIMB G C
Solar/Wind Harmer
3.83
270361_3
Solar/Wind Harmer
5.985
247521TR3_G114
Solar/Wind Harmer
2.168
270246TR4_N_V150
Solar/Wind Harmer
0.549
965011AG1-365 GEN
Solar/Wind Harmer
6.286
23906502RICHG2&3
Adder
0.756
972301AH1-735 GEN
Adder
3.758
23906402RICHG1
Adder
0.752
241840AF1-064_GEN
Solar/Wind Harmer
0.694
23920202STRYCT
Adder
0.794
944231AF1-091 GEN
Solar/Wind Harmer
2.084
241808AF1-120 C
Solar/Wind Harmer
0.496
241858AF1-205_GEN
Solar/Wind Harmer
2.204
972253AH1-711 GEN
Adder
17.22
270063AE2-323 C
Solar/Wind Harmer
0.974
270349AD2-093_GEN
Solar/Wind Helper
2.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.493
TVALTFEXP_TVA->PJM
CLTF
0.456
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.642
LGEELTFEXP_LGEE->PJM
CLTF
0.496
WECLTFEXP_WEC->PJM
CLTF
1.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.069
AH1-155LTFEXP_AH1-155->PJM
LTF
0.104
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.042
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.891
MECLTFEXP_MEC->PJM
CLTF
3.699
SIGELTFEXP_SIGE->PJM
CLTF
0.065

Details for 05BOXWD-05CLIFFR 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.21 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:264.21
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05BOXWD-05CLIFFR 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.66 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:261.62
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
966251AG1-494 GEN
50/50
3.437
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05BOXWD-05CLIFFR 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.47 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:261.31
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05BOXWD-05CLIFFR 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.17 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:240.77
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.25 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:269.29
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
958131AF2-107 GEN
Solar/Wind Harmer
12.516
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.7 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:266.7
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.52 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:266.4
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.35 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:242.73
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.403
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.14 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:265.76
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
958131AF2-107 GEN
Solar/Wind Harmer
12.516
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.59 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:263.18
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:157.41 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:262.87
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.23 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:239.2
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.403
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#6497_05MARYSV 345_J2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.9 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1096.25
MW Contribution:115.56
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
15.511
24727205RPMNG3
50/50
1.104
270302AB2-170 GEN
Solar/Wind Harmer
20.316
270317AD1-130_GEN
Solar/Wind Harmer
7.788
270578AF1-285 GEN2
Solar/Wind Harmer
1.128
270284AF1-227 GEN1
Solar/Wind Harmer
13.691
270286AF1-227 GEN2
Solar/Wind Harmer
5.065
270287AF1-227 GEN3
Solar/Wind Harmer
5.065
957201AF2-014 GEN
Solar/Wind Harmer
6.341
270435AC2-044 GEN
Solar/Wind Harmer
2.796
270499AE1-146 GEN
Solar/Wind Harmer
2.321
270466AD2-091
50/50
14.101
270224U2-072_GEN2
Solar/Wind Harmer
4.793
270227U2-072_GEN3
Solar/Wind Harmer
4.793
270228U2-072_GEN4
Solar/Wind Harmer
4.793
270231U2-072_GEN5
Solar/Wind Harmer
4.793
246938BC-WTG3
Solar/Wind Harmer
5.566
246937BC-WTG2
Solar/Wind Harmer
5.471
971677AH1-339 GEN
Solar/Wind Harmer
6.461
241996AE2-282_GEN
Solar/Wind Harmer
1.131
970611AG2-400 GEN
Solar/Wind Harmer
6.123
270007AE1-245 C
Solar/Wind Harmer
3.331
971231AH1-075 GEN
Solar/Wind Harmer
0.415
253378AE2-206_GEN
Solar/Wind Helper
1.724
276820AF1-078_GEN
Solar/Wind Helper
0.805
270471AD2-092_GEN
Solar/Wind Helper
0.767
24727005RPMNG1
50/50
1.109
270462AD2-086
Solar/Wind Harmer
16.9
270223U2-072_GEN1
Solar/Wind Harmer
4.793
270578AF1-285 GEN2
Solar/Wind Harmer
2.932
270391AF1-285 GEN3
Solar/Wind Harmer
2.932
246936BC-WTG1
Solar/Wind Harmer
5.471
270489AE1-102 GEN1
Solar/Wind Harmer
1.818
965421AG1-410 GEN
Solar/Wind Harmer
39.687
960841AF2-375 GEN
Solar/Wind Harmer
3.561
270361_3
Solar/Wind Harmer
7.855
247522W1-056 GEN
Solar/Wind Harmer
1.881
972253AH1-711 GEN
Adder
24.425
241840AF1-064_GEN
Solar/Wind Harmer
0.826
241858AF1-205_GEN
Solar/Wind Harmer
2.862
23920202STRYCT
Adder
0.981
241808AF1-120 C
Solar/Wind Harmer
0.631
23906502RICHG2&3
Adder
0.842
972301AH1-735 GEN
Adder
4.188
23906402RICHG1
Adder
0.838
965011AG1-365 GEN
Solar/Wind Harmer
6.123
270428AC2-015 C
Solar/Wind Harmer
3.044
241807AE2-176_GEN
Solar/Wind Harmer
2.084
970515AG2-329 GEN
Solar/Wind Harmer
7.906
24695305TIMB G C
Solar/Wind Harmer
2.935
241885AC2-103 GEN1
Solar/Wind Harmer
3.01
970905AG2-564 GEN
Solar/Wind Harmer
2.385
944231AF1-091 GEN
Solar/Wind Harmer
1.77
270349AD2-093_GEN
Solar/Wind Helper
0.767
966831AG1-554 GEN
Solar/Wind Harmer
0.972
971989AH1-539 GEN
Solar/Wind Harmer
10.515
945641AF1-229 GEN
Solar/Wind Harmer
2.888
972211AH1-690 GEN
Adder
115.56
970817AG2-515 GEN
Solar/Wind Harmer
7.248
945411AF1-206 GEN
Solar/Wind Harmer
4.225
247607V1-011 GEN
Solar/Wind Harmer
2.22
965041AG1-368 GEN
Solar/Wind Harmer
5.14
241886AC2-103 GEN2
Solar/Wind Harmer
3.01
24191202EL_AA1-006
Adder
0.108
253383AE2-342_GEN
Solar/Wind Helper
0.488
241972AD1-140 GEN
Solar/Wind Helper
2.205
965431AG1-411 GEN
50/50
15.383
24727105RPMNG2
50/50
1.113
270485AE1-090_GEN
Solar/Wind Harmer
1.469
942871AE2-306 GEN
Solar/Wind Harmer
2.199
270391AF1-285 GEN3
Solar/Wind Harmer
1.128
270491AE1-102 GEN2
Solar/Wind Harmer
1.818
270588AE1-091_GEN
Solar/Wind Harmer
10.17
270575GUS2 35KV
Solar/Wind Harmer
9.254
270541AE2-072 C
Solar/Wind Harmer
3.796
958321AF2-126 GEN
Solar/Wind Harmer
0.886
23929302BS-PKR
Adder
1.019
241832AE2-181_GEN
Solar/Wind Harmer
1.046
23906502RICHG2&3
Adder
0.842
959331AF2-224 GEN
Solar/Wind Harmer
6.123
965021AG1-366 GEN
Solar/Wind Harmer
1.424
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.433
270377AD1-106 GEN
Solar/Wind Harmer
3.205
270044AE2-322 C
Solar/Wind Harmer
0.58
270404AC1-167 GEN
Solar/Wind Harmer
0.483
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
990527J1329
External Queue
1.068130612373352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.855
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.588
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.093
WECLTFEXP_WEC->PJM
CLTF
0.42
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.562
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.355
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.659
MECLTFEXP_MEC->PJM
CLTF
1.044

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1021.28
MW Contribution:115.99
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.919
270223U2-072_GEN1
Solar/Wind Harmer
4.799
270578AF1-285 GEN2
Solar/Wind Harmer
2.935
270391AF1-285 GEN3
Solar/Wind Harmer
2.935
246936BC-WTG1
Solar/Wind Harmer
5.482
270489AE1-102 GEN1
Solar/Wind Harmer
1.821
965421AG1-410 GEN
Solar/Wind Harmer
39.77
960841AF2-375 GEN
Solar/Wind Harmer
3.572
270361_3
Solar/Wind Harmer
7.879
247522W1-056 GEN
Solar/Wind Harmer
1.887
972253AH1-711 GEN
Adder
24.514
241840AF1-064_GEN
Solar/Wind Harmer
0.829
241858AF1-205_GEN
Solar/Wind Harmer
2.873
23920202STRYCT
Adder
0.985
241808AF1-120 C
Solar/Wind Harmer
0.633
23906502RICHG2&3
Adder
0.845
972301AH1-735 GEN
Adder
4.205
23906402RICHG1
Adder
0.841
965011AG1-365 GEN
Solar/Wind Harmer
6.15
270428AC2-015 C
Solar/Wind Harmer
3.059
241807AE2-176_GEN
Solar/Wind Harmer
2.095
970515AG2-329 GEN
Solar/Wind Harmer
7.946
24695305TIMB G C
Solar/Wind Harmer
2.95
241885AC2-103 GEN1
Solar/Wind Harmer
3.026
970905AG2-564 GEN
Solar/Wind Harmer
2.399
944231AF1-091 GEN
Solar/Wind Harmer
1.78
270349AD2-093_GEN
Solar/Wind Helper
0.763
270036AE2-216 BAT
50/50
15.529
24727205RPMNG3
50/50
1.106
270302AB2-170 GEN
Solar/Wind Harmer
20.339
270317AD1-130_GEN
Solar/Wind Harmer
7.797
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.354
270435AC2-044 GEN
Solar/Wind Harmer
2.802
270499AE1-146 GEN
Solar/Wind Harmer
2.328
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.55
945641AF1-229 GEN
Solar/Wind Harmer
2.898
972211AH1-690 GEN
Adder
115.994
970817AG2-515 GEN
Solar/Wind Harmer
7.276
945411AF1-206 GEN
Solar/Wind Harmer
4.242
247607V1-011 GEN
Solar/Wind Harmer
2.231
965041AG1-368 GEN
Solar/Wind Harmer
5.168
241886AC2-103 GEN2
Solar/Wind Harmer
3.026
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.486
241972AD1-140 GEN
Solar/Wind Helper
2.193
965431AG1-411 GEN
50/50
15.415
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
942871AE2-306 GEN
Solar/Wind Harmer
2.201
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.821
270588AE1-091_GEN
Solar/Wind Harmer
10.201
270575GUS2 35KV
Solar/Wind Harmer
9.282
270541AE2-072 C
Solar/Wind Harmer
3.809
958321AF2-126 GEN
Solar/Wind Harmer
0.889
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.05
23906502RICHG2&3
Adder
0.845
959331AF2-224 GEN
Solar/Wind Harmer
6.15
965021AG1-366 GEN
Solar/Wind Harmer
1.43
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.522
270377AD1-106 GEN
Solar/Wind Harmer
3.222
270044AE2-322 C
Solar/Wind Harmer
0.583
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270466AD2-091
50/50
14.117
270224U2-072_GEN2
Solar/Wind Harmer
4.799
270227U2-072_GEN3
Solar/Wind Harmer
4.799
270228U2-072_GEN4
Solar/Wind Harmer
4.799
270231U2-072_GEN5
Solar/Wind Harmer
4.799
246938BC-WTG3
Solar/Wind Harmer
5.577
246937BC-WTG2
Solar/Wind Harmer
5.482
971677AH1-339 GEN
Solar/Wind Harmer
6.484
241996AE2-282_GEN
Solar/Wind Harmer
1.136
970611AG2-400 GEN
Solar/Wind Harmer
6.15
270007AE1-245 C
Solar/Wind Harmer
3.347
971231AH1-075 GEN
Solar/Wind Harmer
0.417
253378AE2-206_GEN
Solar/Wind Helper
1.721
276820AF1-078_GEN
Solar/Wind Helper
0.804
270471AD2-092_GEN
Solar/Wind Helper
0.763
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
990527J1329
External Queue
1.068130612373352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.837
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.533
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.075
WECLTFEXP_WEC->PJM
CLTF
0.43
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.544
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.062
MECLTFEXP_MEC->PJM
CLTF
1.09

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.61
MW Contribution:116.09
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270036AE2-216 BAT
50/50
15.533
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
270317AD1-130_GEN
Solar/Wind Harmer
7.799
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.357
270435AC2-044 GEN
Solar/Wind Harmer
2.803
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.558
945641AF1-229 GEN
Solar/Wind Harmer
2.9
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
247607V1-011 GEN
Solar/Wind Harmer
2.233
965041AG1-368 GEN
Solar/Wind Harmer
5.174
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.485
241972AD1-140 GEN
Solar/Wind Helper
2.191
270284AF1-227 GEN1
Solar/Wind Helper
1.184
270286AF1-227 GEN2
Solar/Wind Helper
0.434
270287AF1-227 GEN3
Solar/Wind Helper
0.434
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
246938BC-WTG3
Solar/Wind Harmer
5.579
246937BC-WTG2
Solar/Wind Harmer
5.484
971677AH1-339 GEN
Solar/Wind Harmer
6.488
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
971231AH1-075 GEN
Solar/Wind Harmer
0.418
253378AE2-206_GEN
Solar/Wind Helper
1.72
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270588AE1-091_GEN
Solar/Wind Harmer
10.207
270575GUS2 35KV
Solar/Wind Harmer
9.288
270541AE2-072 C
Solar/Wind Harmer
3.811
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.051
23906502RICHG2&3
Adder
0.846
959331AF2-224 GEN
Solar/Wind Harmer
6.157
965021AG1-366 GEN
Solar/Wind Harmer
1.432
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.541
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270044AE2-322 C
Solar/Wind Harmer
0.584
270404AC1-167 GEN
Solar/Wind Harmer
0.486
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.924
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
965421AG1-410 GEN
Solar/Wind Harmer
39.788
960841AF2-375 GEN
Solar/Wind Harmer
3.575
270361_3
Solar/Wind Harmer
7.884
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
241840AF1-064_GEN
Solar/Wind Harmer
0.83
241858AF1-205_GEN
Solar/Wind Harmer
2.875
23920202STRYCT
Adder
0.986
241808AF1-120 C
Solar/Wind Harmer
0.634
23906502RICHG2&3
Adder
0.846
972301AH1-735 GEN
Adder
4.209
23906402RICHG1
Adder
0.842
965011AG1-365 GEN
Solar/Wind Harmer
6.157
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
970515AG2-329 GEN
Solar/Wind Harmer
7.955
24695305TIMB G C
Solar/Wind Harmer
2.953
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270349AD2-093_GEN
Solar/Wind Helper
0.762
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
990527J1329
External Queue
1.068130612373352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.071
WECLTFEXP_WEC->PJM
CLTF
0.433
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
MECLTFEXP_MEC->PJM
CLTF
1.1

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.54
MW Contribution:116.09
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
1.112
270462AD2-086
Solar/Wind Harmer
16.924
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
965421AG1-410 GEN
Solar/Wind Harmer
39.788
960841AF2-375 GEN
Solar/Wind Harmer
3.575
270361_3
Solar/Wind Harmer
7.884
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
241840AF1-064_GEN
Solar/Wind Harmer
0.83
241858AF1-205_GEN
Solar/Wind Harmer
2.875
23920202STRYCT
Adder
0.986
241808AF1-120 C
Solar/Wind Harmer
0.634
23906502RICHG2&3
Adder
0.846
972301AH1-735 GEN
Adder
4.209
23906402RICHG1
Adder
0.842
965011AG1-365 GEN
Solar/Wind Harmer
6.157
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
970515AG2-329 GEN
Solar/Wind Harmer
7.955
24695305TIMB G C
Solar/Wind Harmer
2.953
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270349AD2-093_GEN
Solar/Wind Helper
0.762
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270485AE1-090_GEN
Solar/Wind Harmer
1.471
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270588AE1-091_GEN
Solar/Wind Harmer
10.207
270575GUS2 35KV
Solar/Wind Harmer
9.288
270541AE2-072 C
Solar/Wind Harmer
3.811
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
241832AE2-181_GEN
Solar/Wind Harmer
1.051
23906502RICHG2&3
Adder
0.846
959331AF2-224 GEN
Solar/Wind Harmer
6.157
965021AG1-366 GEN
Solar/Wind Harmer
1.432
958091AF2-103 GEN
Solar/Wind Harmer
0.091
970217AG2-149 GEN
Solar/Wind Harmer
17.541
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270044AE2-322 C
Solar/Wind Harmer
0.584
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270036AE2-216 BAT
50/50
15.533
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
270317AD1-130_GEN
Solar/Wind Harmer
7.799
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
957201AF2-014 GEN
Solar/Wind Harmer
6.357
270435AC2-044 GEN
Solar/Wind Harmer
2.803
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
971989AH1-539 GEN
Solar/Wind Harmer
10.558
945641AF1-229 GEN
Solar/Wind Harmer
2.9
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
247607V1-011 GEN
Solar/Wind Harmer
2.233
965041AG1-368 GEN
Solar/Wind Harmer
5.174
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
24191202EL_AA1-006
Adder
0.109
253383AE2-342_GEN
Solar/Wind Helper
0.485
241972AD1-140 GEN
Solar/Wind Helper
2.191
270284AF1-227 GEN1
Solar/Wind Helper
1.184
270286AF1-227 GEN2
Solar/Wind Helper
0.434
270287AF1-227 GEN3
Solar/Wind Helper
0.434
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
246938BC-WTG3
Solar/Wind Harmer
5.579
246937BC-WTG2
Solar/Wind Harmer
5.484
971677AH1-339 GEN
Solar/Wind Harmer
6.488
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
971231AH1-075 GEN
Solar/Wind Harmer
0.418
253378AE2-206_GEN
Solar/Wind Helper
1.72
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
990527J1329
External Queue
1.068130612373352
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.071
WECLTFEXP_WEC->PJM
CLTF
0.433
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
MECLTFEXP_MEC->PJM
CLTF
1.1

Details for 05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.83 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1324.81
MW Contribution:89.12
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
24.391
24727205RPMNG3
50/50
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
2.045
270302AB2-170 GEN
Solar/Wind Harmer
31.946
270317AD1-130_GEN
Solar/Wind Harmer
12.246
957201AF2-014 GEN
Solar/Wind Harmer
5.139
270435AC2-044 GEN
Solar/Wind Harmer
2.266
270297AD1-101 GEN
Solar/Wind Harmer
2.38
247607V1-011 GEN
Solar/Wind Harmer
3.367
966831AG1-554 GEN
Solar/Wind Harmer
1.009
971989AH1-539 GEN
Solar/Wind Harmer
10.907
270499AE1-146 GEN
Solar/Wind Harmer
2.064
965051AG1-369 GEN
Solar/Wind Harmer
3.625
24727005RPMNG1
50/50
0.956
270223U2-072_GEN1
Solar/Wind Harmer
8.695
270578AF1-285 GEN2
Solar/Wind Harmer
5.317
270391AF1-285 GEN3
Solar/Wind Harmer
5.317
270462AD2-086
Solar/Wind Harmer
26.575
246936BC-WTG1
Solar/Wind Harmer
4.434
270489AE1-102 GEN1
Solar/Wind Harmer
1.473
965421AG1-410 GEN
Solar/Wind Harmer
32.755
247522W1-056 GEN
Solar/Wind Harmer
1.866
960841AF2-375 GEN
Solar/Wind Harmer
3.054
24695305TIMB G C
Solar/Wind Harmer
4.274
270361_3
Solar/Wind Harmer
6.549
247521TR3_G114
Solar/Wind Harmer
2.441
270246TR4_N_V150
Solar/Wind Harmer
0.618
965011AG1-365 GEN
Solar/Wind Harmer
7.021
23906502RICHG2&3
Adder
0.834
972301AH1-735 GEN
Adder
4.148
23906402RICHG1
Adder
0.83
241840AF1-064_GEN
Solar/Wind Harmer
0.763
23920202STRYCT
Adder
0.874
944231AF1-091 GEN
Solar/Wind Harmer
2.34
241808AF1-120 C
Solar/Wind Harmer
0.546
241858AF1-205_GEN
Solar/Wind Harmer
2.423
972253AH1-711 GEN
Adder
18.867
270063AE2-323 C
Solar/Wind Harmer
1.113
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
7.883
270449AD2-020 GEN
Solar/Wind Harmer
1.227
943021AE2-325 GEN
Solar/Wind Harmer
1.594
270505AE1-170 C O1
Solar/Wind Harmer
6.536
270349AD2-093_GEN
Solar/Wind Helper
1.782
270466AD2-091
50/50
22.173
270224U2-072_GEN2
Solar/Wind Harmer
8.695
270227U2-072_GEN3
Solar/Wind Harmer
8.695
270228U2-072_GEN4
Solar/Wind Harmer
8.695
270231U2-072_GEN5
Solar/Wind Harmer
8.695
246938BC-WTG3
Solar/Wind Harmer
4.511
965431AG1-411 GEN
50/50
12.696
24727105RPMNG2
50/50
0.96
942871AE2-306 GEN
Solar/Wind Harmer
3.988
270391AF1-285 GEN3
Solar/Wind Harmer
2.045
270485AE1-090_GEN
Solar/Wind Harmer
2.31
270491AE1-102 GEN2
Solar/Wind Harmer
1.473
270588AE1-091_GEN
Solar/Wind Harmer
11.055
270541AE2-072 C
Solar/Wind Harmer
3.949
958091AF2-103 GEN
Solar/Wind Harmer
0.137
270575GUS2 35KV
Solar/Wind Harmer
7.716
270258AD1-119 GEN
Solar/Wind Harmer
2.083
270044AE2-322 C
Solar/Wind Harmer
0.971
270404AC1-167 GEN
Solar/Wind Harmer
0.808
270191TR4_S_V150
Solar/Wind Harmer
2.178
270247TR4_N_V136
Solar/Wind Harmer
0.618
959331AF2-224 GEN
Solar/Wind Harmer
7.021
965021AG1-366 GEN
Solar/Wind Harmer
1.633
23906502RICHG2&3
Adder
0.834
958321AF2-126 GEN
Solar/Wind Harmer
0.818
241832AE2-181_GEN
Solar/Wind Harmer
0.917
23929302BS-PKR
Adder
0.797
970031AG2-029 GEN
Solar/Wind Harmer
15.724
270043AE2-236 GEN
Solar/Wind Harmer
2.792
270377AD1-106 GEN
Solar/Wind Harmer
2.779
945111AF1-176 GEN
Solar/Wind Harmer
2.498
247643Z2-116 C
Solar/Wind Harmer
0.031
971617AH1-308 GEN
Solar/Wind Harmer
2.565
247604X1-042
Adder
0.182
24441205WTRV SLR C
Solar/Wind Harmer
0.059
965041AG1-368 GEN
Solar/Wind Harmer
7.254
945411AF1-206 GEN
Solar/Wind Harmer
3.658
970817AG2-515 GEN
Solar/Wind Harmer
5.808
972211AH1-690 GEN
Adder
89.121
963791AG1-232 GEN
Solar/Wind Harmer
7.507
945641AF1-229 GEN
Solar/Wind Harmer
1.945
270071AF1-092 GEN
Solar/Wind Harmer
6.969
971549AH1-272 GEN
Solar/Wind Harmer
8.464
270024AE2-089 GEN
Solar/Wind Harmer
2.07
944161AF1-084 GEN
Solar/Wind Harmer
0.967
270284AF1-227 GEN1
Solar/Wind Helper
5.57
270286AF1-227 GEN2
Solar/Wind Helper
2.043
270287AF1-227 GEN3
Solar/Wind Helper
2.043
270520AE2-214 GEN
Solar/Wind Helper
2.488
270054AF2-122 C O1
Solar/Wind Helper
0.645
246937BC-WTG2
Solar/Wind Harmer
4.434
270007AE1-245 C
Solar/Wind Harmer
5.052
942801AE2-298 GEN
Solar/Wind Harmer
1.194
970611AG2-400 GEN
Solar/Wind Harmer
7.021
971677AH1-339 GEN
Solar/Wind Harmer
5.301
241996AE2-282_GEN
Solar/Wind Harmer
0.979
247620Y3-023
Adder
0.215
971231AH1-075 GEN
Solar/Wind Harmer
0.36
942221AE2-234 GEN
Solar/Wind Harmer
0.327
270216AD2-079_GEN
Solar/Wind Harmer
0.268
961051AF2-396 GEN
Solar/Wind Harmer
6.972
961051AF2-396 GEN
Solar/Wind Harmer
3.243
960981AF2-389 GEN
Solar/Wind Harmer
0.66
957891AF2-083 GEN
Solar/Wind Harmer
1.473
270471AD2-092_GEN
Solar/Wind Helper
1.782
946101AF1-275 GEN
Solar/Wind Helper
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
2.316
TVALTFEXP_TVA->PJM
CLTF
0.854
NYPJM->LTFIMP_NY
CLTF
0.734
LGEELTFEXP_LGEE->PJM
CLTF
0.812
WECLTFEXP_WEC->PJM
CLTF
1.26
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.063
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.43
MECLTFEXP_MEC->PJM
CLTF
4.551
SIGELTFEXP_SIGE->PJM
CLTF
0.09

Details for 05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.86 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:261.96
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
958131AF2-107 GEN
Solar/Wind Harmer
12.516
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.32 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:259.38
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.13 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:259.07
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.96 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:235.41
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.403
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.94 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:252.07
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
958131AF2-107 GEN
Solar/Wind Harmer
12.516
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.39 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:249.49
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.21 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:249.18
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.04 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:225.52
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.403
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP
Facility Description:
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.46 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:257.95
MW Contribution:9.05
Bus #Bus NameTypeMW Contribution
274675JOLIET 29;7U
Adder
2.478
274675JOLIET 29;7U
Adder
2.39
274731ELWOOD EC;2P
Adder
1.328
274733ELWOOD EC;3P
Adder
1.328
274735ELWOOD EC;4P
Adder
1.328
274728ELWOOD EC;5P
Adder
1.328
972211AH1-690 GEN
Adder
9.055
270494AE1-108_GEN
Solar/Wind Helper
8.751
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.788
942671AE2-283 GEN
Solar/Wind Harmer
2.122
970239AG2-162 GEN
Solar/Wind Harmer
0.957
315821AE2-092 GEN
Solar/Wind Helper
1.498
966251AG1-494 GEN
50/50
3.436
958131AF2-107 GEN
Solar/Wind Harmer
12.516
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.402
970333AG2-219 GEN
Solar/Wind Harmer
2.747
274676JOLIET 29;8U
Adder
2.478
274732ELWOOD EC;7P
Adder
1.328
962751AG1-124 GEN
Solar/Wind Harmer
9.551
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.402
970243AG2-164 GEN
Solar/Wind Harmer
2.247
970519AG2-331 GEN
Solar/Wind Harmer
1.51
970699AG2-449 GEN
Solar/Wind Harmer
0.999
274676JOLIET 29;8U
Adder
2.39
274729ELWOOD EC;1P
Adder
1.328
274730ELWOOD EC;6P
Adder
1.328
274734ELWOOD EC;8P
Adder
1.328
274736ELWOOD EC;9P
Adder
1.328
944201AF1-088_MTX
Adder
10.008
957141AF2-008_MTX
Adder
5.004
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.025
TVALTFEXP_TVA->PJM
CLTF
0.954
NYPJM->LTFIMP_NY
CLTF
0.261
LGEELTFEXP_LGEE->PJM
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.873
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.546
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.91 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:255.37
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.062
270494AE1-108_GEN
Solar/Wind Helper
8.75
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.496
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.249
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
944201AF1-088_MTX
Adder
10.018
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.032
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.74 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:255.07
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.553
270173AC1-122 GEN
Solar/Wind Harmer
0.718
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.403
970243AG2-164 GEN
Solar/Wind Harmer
2.25
970519AG2-331 GEN
Solar/Wind Harmer
1.511
970699AG2-449 GEN
Solar/Wind Harmer
1
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
316217AC1-145 GEN
Solar/Wind Harmer
1.04
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.123
970239AG2-162 GEN
Solar/Wind Harmer
0.958
315821AE2-092 GEN
Solar/Wind Helper
1.495
966251AG1-494 GEN
50/50
3.437
958131AF2-107 GEN
Solar/Wind Harmer
12.518
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.403
970333AG2-219 GEN
Solar/Wind Harmer
2.749
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
957141AF2-008_MTX
Adder
5.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SOAPSTONE-05SCOTSV 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.56 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:231.4
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.42
315821AE2-092 GEN
Solar/Wind Helper
1.495
274675JOLIET 29;7U
Adder
2.481
274675JOLIET 29;7U
Adder
2.392
274731ELWOOD EC;2P
Adder
1.33
274733ELWOOD EC;3P
Adder
1.33
274735ELWOOD EC;4P
Adder
1.33
274728ELWOOD EC;5P
Adder
1.33
972211AH1-690 GEN
Adder
9.063
270494AE1-108_GEN
Solar/Wind Helper
8.749
962751AG1-124 GEN
Solar/Wind Harmer
6.543
270173AC1-122 GEN
Solar/Wind Harmer
0.148
3147312GRETNA
Solar/Wind Harmer
0.046
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.392
274729ELWOOD EC;1P
Adder
1.33
274730ELWOOD EC;6P
Adder
1.33
274734ELWOOD EC;8P
Adder
1.33
274736ELWOOD EC;9P
Adder
1.33
966251AG1-494 GEN
50/50
3.437
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.403
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
2.481
274732ELWOOD EC;7P
Adder
1.33
944201AF1-088_MTX
Adder
10.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.033
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.62
WECLTFEXP_WEC->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.416
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.551
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.4 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:263.67
MW Contribution:15.52
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
2.279
971343AH1-151 GEN
Solar/Wind Harmer
2.279
274676JOLIET 29;8U
Adder
3.535
274732ELWOOD EC;7P
Adder
1.894
957471AF2-041 GEN
Solar/Wind Harmer
3.418
959081AF2-199 GEN
Solar/Wind Harmer
1.139
971067AG2-660 GEN
Solar/Wind Harmer
0.265
274675JOLIET 29;7U
Adder
3.535
274675JOLIET 29;7U
Adder
3.409
274731ELWOOD EC;2P
Adder
1.894
274733ELWOOD EC;3P
Adder
1.894
274735ELWOOD EC;4P
Adder
1.894
274728ELWOOD EC;5P
Adder
1.894
971171AH1-044 GEN
Solar/Wind Harmer
2.279
972211AH1-690 GEN
Adder
15.515
274676JOLIET 29;8U
Adder
3.409
274729ELWOOD EC;1P
Adder
1.894
274730ELWOOD EC;6P
Adder
1.894
274734ELWOOD EC;8P
Adder
1.894
274736ELWOOD EC;9P
Adder
1.894
959091AF2-200 GEN
Solar/Wind Harmer
2.279
944201AF1-088_MTX
Adder
13.588
957141AF2-008_MTX
Adder
6.794
LAGNLTFEXP_LAGN->PJM
CLTF
1.815
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.257
TVALTFEXP_TVA->PJM
CLTF
0.899
NYPJM->LTFIMP_NY
CLTF
0.458
LGEELTFEXP_LGEE->PJM
CLTF
0.821
WECLTFEXP_WEC->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
0.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.231
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.577
MECLTFEXP_MEC->PJM
CLTF
1.837
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:261.36
MW Contribution:15.53
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
2.281
971343AH1-151 GEN
Solar/Wind Harmer
2.281
274732ELWOOD EC;7P
Adder
1.896
274676JOLIET 29;8U
Adder
3.538
274731ELWOOD EC;2P
Adder
1.896
274733ELWOOD EC;3P
Adder
1.896
274735ELWOOD EC;4P
Adder
1.896
274728ELWOOD EC;5P
Adder
1.896
274675JOLIET 29;7U
Adder
3.538
274675JOLIET 29;7U
Adder
3.412
971171AH1-044 GEN
Solar/Wind Harmer
2.281
972211AH1-690 GEN
Adder
15.532
274729ELWOOD EC;1P
Adder
1.896
274730ELWOOD EC;6P
Adder
1.896
274734ELWOOD EC;8P
Adder
1.896
274736ELWOOD EC;9P
Adder
1.896
274676JOLIET 29;8U
Adder
3.412
959091AF2-200 GEN
Solar/Wind Harmer
2.281
957471AF2-041 GEN
Solar/Wind Harmer
3.421
959081AF2-199 GEN
Solar/Wind Harmer
1.14
971067AG2-660 GEN
Solar/Wind Harmer
0.265
944201AF1-088_MTX
Adder
13.6
957141AF2-008_MTX
Adder
6.8
LAGNLTFEXP_LAGN->PJM
CLTF
1.817
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.26
TVALTFEXP_TVA->PJM
CLTF
0.9
NYPJM->LTFIMP_NY
CLTF
0.458
LGEELTFEXP_LGEE->PJM
CLTF
0.821
WECLTFEXP_WEC->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
0.236
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.533
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.247
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.581
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.45 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:261.25
MW Contribution:14.96
Bus #Bus NameTypeMW Contribution
971341AH1-150 GEN
Solar/Wind Harmer
2.197
971343AH1-151 GEN
Solar/Wind Harmer
2.197
274731ELWOOD EC;2P
Adder
1.826
274733ELWOOD EC;3P
Adder
1.826
274735ELWOOD EC;4P
Adder
1.826
274728ELWOOD EC;5P
Adder
1.826
274675JOLIET 29;7U
Adder
3.409
274675JOLIET 29;7U
Adder
3.287
971171AH1-044 GEN
Solar/Wind Harmer
2.197
972211AH1-690 GEN
Adder
14.961
274729ELWOOD EC;1P
Adder
1.826
274730ELWOOD EC;6P
Adder
1.826
274734ELWOOD EC;8P
Adder
1.826
274736ELWOOD EC;9P
Adder
1.826
274676JOLIET 29;8U
Adder
3.287
959091AF2-200 GEN
Solar/Wind Harmer
2.197
274732ELWOOD EC;7P
Adder
1.826
274676JOLIET 29;8U
Adder
3.409
957471AF2-041 GEN
Solar/Wind Harmer
3.296
959081AF2-199 GEN
Solar/Wind Harmer
1.099
971067AG2-660 GEN
Solar/Wind Harmer
0.255
944201AF1-088_MTX
Adder
13.101
957141AF2-008_MTX
Adder
6.55
LAGNLTFEXP_LAGN->PJM
CLTF
1.749
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.211
TVALTFEXP_TVA->PJM
CLTF
0.866
NYPJM->LTFIMP_NY
CLTF
0.441
LGEELTFEXP_LGEE->PJM
CLTF
0.791
WECLTFEXP_WEC->PJM
CLTF
0.419
CPLELTFEXP_CPLE->PJM
CLTF
0.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.447
MECLTFEXP_MEC->PJM
CLTF
1.771
SIGELTFEXP_SIGE->PJM
CLTF
0.058

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:182.88 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:930.03
MW Contribution:28.67
Bus #Bus NameTypeMW Contribution
970917AG2-570 GEN
Solar/Wind Harmer
15.316
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970919AG2-571 GEN
Solar/Wind Harmer
6.126
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.67 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:908.59
MW Contribution:28.67
Bus #Bus NameTypeMW Contribution
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for AC2-015 TAP-05HOWARD1 138.0 kV Ckt 1 line l/o AEP_P4_#7105_05MELMOR 138_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AC2-015 TAP-05HOWARD1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7105_05MELMOR 138_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.18 %
Rating:183.0 MVA
Rating Type:B
MVA to Mitigate:186.99
MW Contribution:26.1
Bus #Bus NameTypeMW Contribution
270499AE1-146 GEN
Solar/Wind Harmer
1.151
972211AH1-690 GEN
Adder
26.1
270428AC2-015 C
Solar/Wind Harmer
22.054
270361_3
Solar/Wind Harmer
4.517
960841AF2-375 GEN
Solar/Wind Harmer
1.927
270575GUS2 35KV
Solar/Wind Harmer
5.321
LAGNLTFEXP_LAGN->PJM
CLTF
0.171
TVALTFEXP_TVA->PJM
CLTF
0.056
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.106
LGEELTFEXP_LGEE->PJM
CLTF
0.064
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.98
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.234
MECLTFEXP_MEC->PJM
CLTF
0.404
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2479.15
MW Contribution:275.94
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.268
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.49
23906502RICHG2&3
Adder
1.312
270575GUS2 35KV
Solar/Wind Harmer
10.14
270541AE2-072 C
Solar/Wind Harmer
4.319
970217AG2-149 GEN
Solar/Wind Harmer
22.462
270044AE2-322 C
Solar/Wind Harmer
0.849
270404AC1-167 GEN
Solar/Wind Harmer
0.707
270588AE1-091_GEN
Solar/Wind Harmer
6.832
270258AD1-119 GEN
Solar/Wind Harmer
1.729
247604X1-042
Adder
0.25
24441205WTRV SLR C
Solar/Wind Harmer
0.079
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
945111AF1-176 GEN
Solar/Wind Harmer
3.104
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
24642205MAYFLWER
Adder
0.339
970031AG2-029 GEN
Solar/Wind Harmer
15.896
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.199
965021AG1-366 GEN
Solar/Wind Harmer
1.209
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
7.29
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.928
270535AF1-215 GEN1
Solar/Wind Harmer
2.093
972231SS25-0005
Solar/Wind Harmer
4.31
972181SS23-001
Solar/Wind Harmer
2.694
274752CRETE EC ;2U
Adder
2.22
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
274724RIVER EC ;11
Adder
7.979
959141AF2-205 GEN
Solar/Wind Harmer
2.693
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.723
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
961961AG1-039 GEN
Solar/Wind Harmer
1.256
274676JOLIET 29;8U
Adder
12.955
276897AD1-100 C
Solar/Wind Harmer
12.695
939351AE1-166 GEN
Solar/Wind Harmer
2.594
276893AG1-478 C
Solar/Wind Harmer
0.183
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.238
274729ELWOOD EC;1P
Adder
7.185
970513AG2-328 GEN
Solar/Wind Harmer
7.784
970517AG2-330 GEN
Solar/Wind Harmer
7.06
971617AH1-308 GEN
Solar/Wind Harmer
2.534
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.641
943121AE2-341 GEN
Solar/Wind Harmer
2.014
943591AF1-030 GEN
Solar/Wind Harmer
1.343
23867002DVBSG1
50/50
12.736
972211AH1-690 GEN
50/50
275.935
23888502TROY G1
50/50
1.742
23888602TROY G2
50/50
1.742
23860102FRMENG 1
50/50
1.188
23860202FRMENG 2
50/50
1.188
241886AC2-103 GEN2
Solar/Wind Harmer
25.595
970817AG2-515 GEN
Solar/Wind Harmer
14.806
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270499AE1-146 GEN
Solar/Wind Harmer
2.385
945641AF1-229 GEN
Solar/Wind Harmer
3.427
971549AH1-272 GEN
Solar/Wind Harmer
12.688
270297AD1-101 GEN
Solar/Wind Harmer
1.9
966831AG1-554 GEN
Solar/Wind Harmer
0.712
971989AH1-539 GEN
Solar/Wind Harmer
7.704
247607V1-011 GEN
Solar/Wind Harmer
2.309
957201AF2-014 GEN
Solar/Wind Harmer
2.623
270435AC2-044 GEN
Solar/Wind Harmer
1.157
944161AF1-084 GEN
Solar/Wind Harmer
1.256
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
965051AG1-369 GEN
Solar/Wind Harmer
2.697
971771AH1-392 GEN
Solar/Wind Harmer
4.684
270302AB2-170 GEN
Solar/Wind Harmer
4.348
270317AD1-130_GEN
Solar/Wind Harmer
1.667
971567AH1-282 GEN
Solar/Wind Harmer
7.657
971769AH1-391 GEN
Solar/Wind Harmer
5.074
960681AF2-359 GEN
Solar/Wind Harmer
1.844
971347AH1-153 GEN
Solar/Wind Harmer
7.29
963791AG1-232 GEN
Solar/Wind Harmer
6.504
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.093
270071AF1-092 GEN
Solar/Wind Harmer
6.841
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274805UNIV PK N;1U
Adder
2.251
274811UNIV PK N;7U
Adder
2.246
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.436
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.261
274687WILL CNTY;4U
Adder
12.261
274675JOLIET 29;7U
Adder
13.435
274675JOLIET 29;7U
Adder
12.955
274728ELWOOD EC;5P
Adder
7.185
274731ELWOOD EC;2P
Adder
7.185
274733ELWOOD EC;3P
Adder
7.185
274735ELWOOD EC;4P
Adder
7.185
270024AE2-089 GEN
Solar/Wind Harmer
2.045
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.416
274744AC1-111 GEN8
Adder
2.416
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.246
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.861
24190002OREGON_ST1
50/50
3.442
24189802OREGON_CT1
50/50
2.611
23888802TROY G4
50/50
1.742
241996AE2-282_GEN
Solar/Wind Harmer
2.147
971677AH1-339 GEN
Solar/Wind Harmer
6.747
270007AE1-245 C
Solar/Wind Harmer
3.464
942801AE2-298 GEN
Solar/Wind Harmer
0.877
246938BC-WTG3
Solar/Wind Harmer
2.302
246937BC-WTG2
Solar/Wind Harmer
2.263
961051AF2-396 GEN
Solar/Wind Harmer
8.832
961051AF2-396 GEN
Solar/Wind Harmer
4.108
960981AF2-389 GEN
Solar/Wind Harmer
0.827
957891AF2-083 GEN
Solar/Wind Harmer
1.844
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.32
970611AG2-400 GEN
Solar/Wind Harmer
5.199
270526AF1-158 GEN
Solar/Wind Harmer
2.317
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.102
965791AG1-447 GEN
Solar/Wind Harmer
3.122
270224U2-072_GEN2
Solar/Wind Harmer
0.952
270227U2-072_GEN3
Solar/Wind Harmer
0.952
270228U2-072_GEN4
Solar/Wind Harmer
0.952
270231U2-072_GEN5
Solar/Wind Harmer
0.952
971231AH1-075 GEN
Solar/Wind Harmer
0.379
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
942221AE2-234 GEN
Solar/Wind Harmer
0.323
972259AH1-714 GEN
Adder
8.361
274674JOLIET 9 ;6U
Adder
6.73
970321AG2-212 GEN
Solar/Wind Harmer
7.784
274847GR RIDGE ;BU
Solar/Wind Harmer
2.199
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.325
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
24189902OREGON_CT2
50/50
2.559
23888702TROY G3
50/50
1.742
972253AH1-711 GEN
50/50
53.201
23856402BAYSG1
50/50
1.289
23920202STRYCT
50/50
1.895
23860302FRMENG 3
50/50
2.426
241885AC2-103 GEN1
Solar/Wind Harmer
25.595
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241808AF1-120 C
Solar/Wind Harmer
1.197
241840AF1-064_GEN
Solar/Wind Harmer
1.39
972301AH1-735 GEN
Adder
6.573
23906402RICHG1
Adder
1.315
23906502RICHG2&3
Adder
1.312
270361_3
Solar/Wind Harmer
8.607
960841AF2-375 GEN
Solar/Wind Harmer
3.799
241807AE2-176_GEN
Solar/Wind Harmer
3.58
247522W1-056 GEN
Solar/Wind Harmer
1.591
970515AG2-329 GEN
Solar/Wind Harmer
10.186
944231AF1-091 GEN
Solar/Wind Harmer
2.443
270428AC2-015 C
Solar/Wind Harmer
3.305
246936BC-WTG1
Solar/Wind Harmer
2.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
965421AG1-410 GEN
Solar/Wind Harmer
17.181
270449AD2-020 GEN
Solar/Wind Harmer
1.572
943021AE2-325 GEN
Solar/Wind Harmer
2.042
24695305TIMB G C
Solar/Wind Harmer
3.08
945111AF1-176 GEN
Solar/Wind Harmer
9.795
270505AE1-170 C O1
Solar/Wind Harmer
8.226
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.171
965011AG1-365 GEN
Solar/Wind Harmer
5.199
270462AD2-086
Solar/Wind Harmer
3.617
270223U2-072_GEN1
Solar/Wind Harmer
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
970905AG2-564 GEN
Solar/Wind Harmer
2.368
970373AG2-245 GEN
Solar/Wind Harmer
9.864
270055AF2-134 C O1
Solar/Wind Harmer
1.395
274751CRETE EC ;1U
Adder
2.22
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
964861AG1-349 GEN
Solar/Wind Harmer
3.551
971917AH1-482 GEN
Solar/Wind Harmer
4.098
274723RIVER EC ;12
Adder
8.075
274812UNIV PK N;8U
Adder
2.246
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
4.504
276776AD2-060 GEN
Solar/Wind Harmer
0.187
971605AH1-302 GEN
Solar/Wind Harmer
3.851
972207SS24-0001
Solar/Wind Harmer
9.729
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
241847AF2-150_GEN
Solar/Wind Harmer
1.821
274676JOLIET 29;8U
Adder
13.435
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.73
970245AG2-165 GEN
Solar/Wind Harmer
7.784
274871GR RIDGE ;2U
Solar/Wind Harmer
3.343
274745AC1-111 GEN9
Adder
2.416
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
23.962841033935547
991177J1571 G
External Queue
14.786787033081055
990142J1224
External Queue
12.808939933776855
990527J1329
External Queue
1.7522491216659546
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.169
NYPJM->LTFIMP_NY
CLTF
2.01
LGEELTFEXP_LGEE->PJM
CLTF
1.95
WECLTFEXP_WEC->PJM
CLTF
1.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.6
MECLTFEXP_MEC->PJM
CLTF
6.243
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-F1_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:289.96
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
991182J1586 G
External Queue
24.90056610107422
991177J1571 G
External Queue
15.212156295776367
990142J1224
External Queue
13.294119834899902
990527J1329
External Queue
1.8186211585998535
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-12_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-12_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.45 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2615.26
MW Contribution:289.96
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.166
241832AE2-181_GEN
Solar/Wind Harmer
1.946
958321AF2-126 GEN
Solar/Wind Harmer
1.455
23906502RICHG2&3
Adder
1.306
270541AE2-072 C
Solar/Wind Harmer
4.224
270575GUS2 35KV
Solar/Wind Harmer
9.25
970217AG2-149 GEN
Solar/Wind Harmer
22.132
270044AE2-322 C
Solar/Wind Harmer
0.845
270404AC1-167 GEN
Solar/Wind Harmer
0.704
270258AD1-119 GEN
Solar/Wind Harmer
1.722
247604X1-042
Adder
0.255
24441205WTRV SLR C
Solar/Wind Harmer
0.081
270588AE1-091_GEN
Solar/Wind Harmer
6.538
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270491AE1-102 GEN2
Solar/Wind Harmer
0.753
945111AF1-176 GEN
Solar/Wind Harmer
3.155
24642205MAYFLWER
Adder
0.345
270191TR4_S_V150
Solar/Wind Harmer
1.62
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
16.085
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.229
965021AG1-366 GEN
Solar/Wind Harmer
1.216
270485AE1-090_GEN
Solar/Wind Harmer
0.313
270043AE2-236 GEN
Solar/Wind Harmer
2.722
970349AG2-230 GEN
Solar/Wind Harmer
7.391
942871AE2-306 GEN
Solar/Wind Harmer
0.434
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270535AF1-215 GEN1
Solar/Wind Harmer
2.12
972231SS25-0005
Solar/Wind Harmer
4.366
972181SS23-001
Solar/Wind Harmer
2.729
274752CRETE EC ;2U
Adder
2.249
274753CRETE EC ;3U
Adder
2.249
964401AG1-302 GEN
Solar/Wind Harmer
4.158
274724RIVER EC ;11
Adder
8.081
959141AF2-205 GEN
Solar/Wind Harmer
2.726
274802UNIV PARK;5U
Adder
2.619
274826FISK ;BP
Adder
4.91
274800UNIV PARK;3U
Adder
2.611
972038AH1-567 GEN2
Adder
0.163
276772AC2-154 GEN
Solar/Wind Harmer
1.247
276806AD2-047 C O1
Solar/Wind Harmer
4.783
970941AG2-585 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
2.77
972228AH1-698 GEN2
Adder
1.651
274676JOLIET 29;8U
Adder
13.116
276897AD1-100 C
Solar/Wind Harmer
12.852
939351AE1-166 GEN
Solar/Wind Harmer
2.626
276893AG1-478 C
Solar/Wind Harmer
0.185
274730ELWOOD EC;6P
Adder
7.275
24189902OREGON_CT2
50/50
2.688
23888702TROY G3
50/50
1.811
972253AH1-711 GEN
50/50
55.325
23856402BAYSG1
50/50
1.231
23920202STRYCT
50/50
1.893
241885AC2-103 GEN1
Solar/Wind Harmer
26.657
241858AF1-205_GEN
Solar/Wind Harmer
5.459
241808AF1-120 C
Solar/Wind Harmer
1.196
241840AF1-064_GEN
Solar/Wind Harmer
1.357
972301AH1-735 GEN
Adder
6.543
23906402RICHG1
Adder
1.309
23906502RICHG2&3
Adder
1.306
270361_3
Solar/Wind Harmer
7.852
960841AF2-375 GEN
Solar/Wind Harmer
3.479
970515AG2-329 GEN
Solar/Wind Harmer
10.037
247522W1-056 GEN
Solar/Wind Harmer
1.482
944231AF1-091 GEN
Solar/Wind Harmer
2.45
246936BC-WTG1
Solar/Wind Harmer
2.266
270489AE1-102 GEN1
Solar/Wind Harmer
0.753
965421AG1-410 GEN
Solar/Wind Harmer
17.213
270449AD2-020 GEN
Solar/Wind Harmer
1.599
943021AE2-325 GEN
Solar/Wind Harmer
2.077
24695305TIMB G C
Solar/Wind Harmer
3.074
945111AF1-176 GEN
Solar/Wind Harmer
9.954
270505AE1-170 C O1
Solar/Wind Harmer
8.362
24639705ELKHART HY
Adder
0.083
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
270063AE2-323 C
Solar/Wind Harmer
1.184
965011AG1-365 GEN
Solar/Wind Harmer
5.229
270462AD2-086
Solar/Wind Harmer
3.599
270223U2-072_GEN1
Solar/Wind Harmer
0.947
270578AF1-285 GEN2
Solar/Wind Harmer
0.579
270391AF1-285 GEN3
Solar/Wind Harmer
0.579
970373AG2-245 GEN
Solar/Wind Harmer
9.997
270055AF2-134 C O1
Solar/Wind Harmer
1.413
274751CRETE EC ;1U
Adder
2.249
274754CRETE EC ;4U
Adder
2.249
958381AF2-132 GEN
Solar/Wind Harmer
4.158
964861AG1-349 GEN
Solar/Wind Harmer
3.596
971917AH1-482 GEN
Solar/Wind Harmer
4.15
274723RIVER EC ;12
Adder
8.179
274812UNIV PK N;8U
Adder
2.275
276164X3-005 C
Solar/Wind Harmer
0.318
274801UNIV PARK;4U
Adder
2.611
276776AD2-060 GEN
Solar/Wind Harmer
0.189
940581AE2-045 GEN
Solar/Wind Harmer
4.559
972207SS24-0001
Solar/Wind Harmer
9.85
274773LINCOLN ;4U
Adder
2.77
274774LINCOLN ;5U
Adder
2.77
971605AH1-302 GEN
Solar/Wind Harmer
3.898
274676JOLIET 29;8U
Adder
13.602
941551AE2-152 GEN
Solar/Wind Harmer
2.009
274732ELWOOD EC;7P
Adder
7.275
274674JOLIET 9 ;6U
Adder
6.813
970245AG2-165 GEN
Solar/Wind Harmer
7.876
274871GR RIDGE ;2U
Solar/Wind Harmer
3.384
274745AC1-111 GEN9
Adder
2.446
276691AA1-018 GEN1
Solar/Wind Harmer
0.204
274682WAUKEGAN ;7U
Adder
7.809
274828WAUKEGAN ;BP
Adder
4.795
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.298
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.129
254303AC2-168 GEN
Solar/Wind Helper
0.075
274734ELWOOD EC;8P
Adder
7.275
274736ELWOOD EC;9P
Adder
7.275
970707AG2-453 GEN
Solar/Wind Harmer
12.39
274729ELWOOD EC;1P
Adder
7.274
970513AG2-328 GEN
Solar/Wind Harmer
7.876
970517AG2-330 GEN
Solar/Wind Harmer
7.143
971617AH1-308 GEN
Solar/Wind Harmer
2.543
943121AE2-341 GEN
Solar/Wind Harmer
6.56
943591AF1-030 GEN
Solar/Wind Harmer
4.374
276694AA1-018 GEN2
Solar/Wind Harmer
2.759
274682WAUKEGAN ;7U
Adder
7.809
962511AG1-100 GEN
Solar/Wind Helper
0.337
203830AF1-094 GEN
Solar/Wind Helper
0.319
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.636
24190002OREGON_ST1
50/50
3.617
24189802OREGON_CT1
50/50
2.744
23888802TROY G4
50/50
1.811
241996AE2-282_GEN
Solar/Wind Harmer
2.146
971677AH1-339 GEN
Solar/Wind Harmer
6.235
270007AE1-245 C
Solar/Wind Harmer
3.444
246938BC-WTG3
Solar/Wind Harmer
2.305
246937BC-WTG2
Solar/Wind Harmer
2.266
942801AE2-298 GEN
Solar/Wind Harmer
0.872
961051AF2-396 GEN
Solar/Wind Harmer
8.981
961051AF2-396 GEN
Solar/Wind Harmer
4.177
960981AF2-389 GEN
Solar/Wind Harmer
0.84
957891AF2-083 GEN
Solar/Wind Harmer
1.874
247620Y3-023
Adder
0.25
270216AD2-079_GEN
Solar/Wind Harmer
0.325
970611AG2-400 GEN
Solar/Wind Harmer
5.229
270526AF1-158 GEN
Solar/Wind Harmer
2.352
24441505OLIV SLR
Solar/Wind Harmer
0.069
965681AG1-436 GEN
Solar/Wind Harmer
6.19
965791AG1-447 GEN
Solar/Wind Harmer
3.167
270224U2-072_GEN2
Solar/Wind Harmer
0.947
270227U2-072_GEN3
Solar/Wind Harmer
0.947
270228U2-072_GEN4
Solar/Wind Harmer
0.947
270231U2-072_GEN5
Solar/Wind Harmer
0.947
274808UNIV PK N;4U
Adder
2.265
274803UNIV PARK;6U
Adder
2.619
274888KELLY CRK;1U
Solar/Wind Harmer
2.639
274887GEN-1.85
Solar/Wind Harmer
2.383
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.438
274770LINCOLN ;1U
Adder
2.77
274771LINCOLN ;2U
Adder
2.77
972259AH1-714 GEN
Adder
8.465
942221AE2-234 GEN
Solar/Wind Harmer
0.325
274674JOLIET 9 ;6U
Adder
6.813
970321AG2-212 GEN
Solar/Wind Harmer
7.876
274847GR RIDGE ;BU
Solar/Wind Harmer
2.226
274695ROCKY RD ;2P
Adder
4.836
274693ROCKY RD ;1P
Adder
4.789
274697ROCKY RD ;3P
Adder
1.314
274696ROCKY RD ;4P
Adder
4.95
274683WAUKEGAN ;8U
Adder
9.148
274683WAUKEGAN ;8U
Adder
7.711
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.335
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.323
946381AF1-302 GEN
Solar/Wind Helper
0.104
958481AF2-142 GEN
Solar/Wind Harmer
1.857
23867002DVBSG1
50/50
14.146
972211AH1-690 GEN
50/50
289.964
23888502TROY G1
50/50
1.811
23888602TROY G2
50/50
1.811
241886AC2-103 GEN2
Solar/Wind Harmer
26.657
970817AG2-515 GEN
Solar/Wind Harmer
15.186
945411AF1-206 GEN
Solar/Wind Harmer
8.014
945641AF1-229 GEN
Solar/Wind Harmer
3.431
270499AE1-146 GEN
Solar/Wind Harmer
2.196
971549AH1-272 GEN
Solar/Wind Harmer
12.968
270297AD1-101 GEN
Solar/Wind Harmer
1.865
247607V1-011 GEN
Solar/Wind Harmer
2.296
957201AF2-014 GEN
Solar/Wind Harmer
2.627
270435AC2-044 GEN
Solar/Wind Harmer
1.158
944161AF1-084 GEN
Solar/Wind Harmer
1.278
966831AG1-554 GEN
Solar/Wind Harmer
0.671
971989AH1-539 GEN
Solar/Wind Harmer
7.259
965041AG1-368 GEN
Solar/Wind Harmer
5.434
965051AG1-369 GEN
Solar/Wind Harmer
2.696
971771AH1-392 GEN
Solar/Wind Harmer
4.755
270302AB2-170 GEN
Solar/Wind Harmer
4.326
270317AD1-130_GEN
Solar/Wind Harmer
1.658
971769AH1-391 GEN
Solar/Wind Harmer
5.15
971567AH1-282 GEN
Solar/Wind Harmer
7.434
960681AF2-359 GEN
Solar/Wind Harmer
1.871
971347AH1-153 GEN
Solar/Wind Harmer
7.391
963791AG1-232 GEN
Solar/Wind Harmer
6.533
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
270536AF1-215 GEN2
Solar/Wind Harmer
2.12
270071AF1-092 GEN
Solar/Wind Harmer
6.896
274814UNIV PK N;0U
Adder
2.295
274807UNIV PK N;3U
Adder
2.29
274805UNIV PK N;1U
Adder
2.28
274811UNIV PK N;7U
Adder
2.275
958391AF2-133 GEN
Solar/Wind Harmer
4.12
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.48
960591AF2-350 GEN
Solar/Wind Harmer
4.471
274775LINCOLN ;6U
Adder
2.77
274776LINCOLN ;7U
Adder
2.77
274777LINCOLN ;8U
Adder
2.77
972227AH1-698 GEN1
Adder
1.163
274687WILL CNTY;4U
Adder
12.414
274687WILL CNTY;4U
Adder
12.414
274675JOLIET 29;7U
Adder
13.602
274675JOLIET 29;7U
Adder
13.116
274728ELWOOD EC;5P
Adder
7.275
274731ELWOOD EC;2P
Adder
7.274
274733ELWOOD EC;3P
Adder
7.274
274735ELWOOD EC;4P
Adder
7.274
970833AG2-524 GEN
Solar/Wind Harmer
3.844
970833AG2-524 GEN
Solar/Wind Harmer
1.788
274746AC1-111 G10
Adder
2.446
274744AC1-111 GEN8
Adder
2.446
270024AE2-089 GEN
Solar/Wind Harmer
2.053
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.854
991182J1586 G
External Queue
24.90056610107422
991177J1571 G
External Queue
15.212156295776367
990142J1224
External Queue
13.294119834899902
990527J1329
External Queue
1.8186211585998535
LAGNLTFEXP_LAGN->PJM
CLTF
4.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.113
TVALTFEXP_TVA->PJM
CLTF
2.181
NYPJM->LTFIMP_NY
CLTF
1.998
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CPLELTFEXP_CPLE->PJM
CLTF
0.312
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
92.632
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.641
MECLTFEXP_MEC->PJM
CLTF
6.31
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.16 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2556.01
MW Contribution:279.99
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.493
23929302BS-PKR
50/50
2.264
241832AE2-181_GEN
Solar/Wind Harmer
1.957
958321AF2-126 GEN
Solar/Wind Harmer
1.492
23906502RICHG2&3
Adder
1.318
270575GUS2 35KV
Solar/Wind Harmer
10.016
270541AE2-072 C
Solar/Wind Harmer
4.321
970217AG2-149 GEN
Solar/Wind Harmer
22.356
270044AE2-322 C
Solar/Wind Harmer
0.852
270404AC1-167 GEN
Solar/Wind Harmer
0.709
270258AD1-119 GEN
Solar/Wind Harmer
1.735
270588AE1-091_GEN
Solar/Wind Harmer
6.791
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
3.126
270191TR4_S_V150
Solar/Wind Harmer
1.626
270247TR4_N_V136
Solar/Wind Harmer
0.461
24642205MAYFLWER
Adder
0.342
970031AG2-029 GEN
Solar/Wind Harmer
15.991
247643Z2-116 C
Solar/Wind Harmer
0.037
959331AF2-224 GEN
Solar/Wind Harmer
5.223
965021AG1-366 GEN
Solar/Wind Harmer
1.215
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270043AE2-236 GEN
Solar/Wind Harmer
2.712
970349AG2-230 GEN
Solar/Wind Harmer
7.336
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.871
270535AF1-215 GEN1
Solar/Wind Harmer
2.105
972231SS25-0005
Solar/Wind Harmer
4.336
24189802OREGON_CT1
50/50
2.65
23888802TROY G4
50/50
1.764
241996AE2-282_GEN
Solar/Wind Harmer
2.159
971677AH1-339 GEN
Solar/Wind Harmer
6.666
270007AE1-245 C
Solar/Wind Harmer
3.473
942801AE2-298 GEN
Solar/Wind Harmer
0.88
246938BC-WTG3
Solar/Wind Harmer
2.311
246937BC-WTG2
Solar/Wind Harmer
2.271
961051AF2-396 GEN
Solar/Wind Harmer
8.895
961051AF2-396 GEN
Solar/Wind Harmer
4.137
960981AF2-389 GEN
Solar/Wind Harmer
0.832
957891AF2-083 GEN
Solar/Wind Harmer
1.857
247620Y3-023
Adder
0.249
270216AD2-079_GEN
Solar/Wind Harmer
0.322
970611AG2-400 GEN
Solar/Wind Harmer
5.223
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.141
965791AG1-447 GEN
Solar/Wind Harmer
3.142
270224U2-072_GEN2
Solar/Wind Harmer
0.954
270227U2-072_GEN3
Solar/Wind Harmer
0.954
270228U2-072_GEN4
Solar/Wind Harmer
0.954
270231U2-072_GEN5
Solar/Wind Harmer
0.954
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.25
274803UNIV PARK;6U
Adder
2.602
274888KELLY CRK;1U
Solar/Wind Harmer
2.622
274887GEN-1.85
Solar/Wind Harmer
2.367
276843GEN-1.7
Solar/Wind Harmer
0.255
958011AF2-095 GEN
Solar/Wind Harmer
6.395
274770LINCOLN ;1U
Adder
2.752
274771LINCOLN ;2U
Adder
2.752
942221AE2-234 GEN
Solar/Wind Harmer
0.324
972259AH1-714 GEN
Adder
8.409
274674JOLIET 9 ;6U
Adder
6.769
24189902OREGON_CT2
50/50
2.596
23888702TROY G3
50/50
1.764
972253AH1-711 GEN
50/50
53.875
23856402BAYSG1
50/50
1.286
23920202STRYCT
50/50
1.905
241885AC2-103 GEN1
Solar/Wind Harmer
25.888
241858AF1-205_GEN
Solar/Wind Harmer
5.501
241808AF1-120 C
Solar/Wind Harmer
1.204
241840AF1-064_GEN
Solar/Wind Harmer
1.392
972301AH1-735 GEN
Adder
6.601
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
270361_3
Solar/Wind Harmer
8.502
960841AF2-375 GEN
Solar/Wind Harmer
3.755
241807AE2-176_GEN
Solar/Wind Harmer
2.785
247522W1-056 GEN
Solar/Wind Harmer
1.573
970515AG2-329 GEN
Solar/Wind Harmer
10.138
944231AF1-091 GEN
Solar/Wind Harmer
2.455
246936BC-WTG1
Solar/Wind Harmer
2.271
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
965421AG1-410 GEN
Solar/Wind Harmer
17.247
270449AD2-020 GEN
Solar/Wind Harmer
1.583
943021AE2-325 GEN
Solar/Wind Harmer
2.057
270428AC2-015 C
Solar/Wind Harmer
3.089
24695305TIMB G C
Solar/Wind Harmer
3.089
945111AF1-176 GEN
Solar/Wind Harmer
9.863
270505AE1-170 C O1
Solar/Wind Harmer
8.284
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
24639705ELKHART HY
Adder
0.082
270063AE2-323 C
Solar/Wind Harmer
1.178
965011AG1-365 GEN
Solar/Wind Harmer
5.223
270462AD2-086
Solar/Wind Harmer
3.624
270223U2-072_GEN1
Solar/Wind Harmer
0.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.924
270055AF2-134 C O1
Solar/Wind Harmer
1.403
274751CRETE EC ;1U
Adder
2.233
274754CRETE EC ;4U
Adder
2.233
958381AF2-132 GEN
Solar/Wind Harmer
4.13
964861AG1-349 GEN
Solar/Wind Harmer
3.572
971917AH1-482 GEN
Solar/Wind Harmer
4.122
274723RIVER EC ;12
Adder
8.123
274812UNIV PK N;8U
Adder
2.26
276164X3-005 C
Solar/Wind Harmer
0.316
274801UNIV PARK;4U
Adder
2.593
940581AE2-045 GEN
Solar/Wind Harmer
4.53
276776AD2-060 GEN
Solar/Wind Harmer
0.188
971605AH1-302 GEN
Solar/Wind Harmer
3.873
972207SS24-0001
Solar/Wind Harmer
9.786
274773LINCOLN ;4U
Adder
2.752
274774LINCOLN ;5U
Adder
2.752
274676JOLIET 29;8U
Adder
13.513
941551AE2-152 GEN
Solar/Wind Harmer
1.995
274732ELWOOD EC;7P
Adder
7.227
274674JOLIET 9 ;6U
Adder
6.769
970245AG2-165 GEN
Solar/Wind Harmer
7.828
274871GR RIDGE ;2U
Solar/Wind Harmer
3.362
970905AG2-564 GEN
Solar/Wind Harmer
2.184
274745AC1-111 GEN9
Adder
2.43
274682WAUKEGAN ;7U
Adder
7.759
274828WAUKEGAN ;BP
Adder
4.764
961971AG1-040 GEN
Solar/Wind Helper
0.333
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.13
254303AC2-168 GEN
Solar/Wind Helper
0.075
972181SS23-001
Solar/Wind Harmer
2.71
274752CRETE EC ;2U
Adder
2.233
274753CRETE EC ;3U
Adder
2.233
964401AG1-302 GEN
Solar/Wind Harmer
4.13
274724RIVER EC ;11
Adder
8.026
959141AF2-205 GEN
Solar/Wind Harmer
2.708
274802UNIV PARK;5U
Adder
2.602
274826FISK ;BP
Adder
4.877
274800UNIV PARK;3U
Adder
2.593
972038AH1-567 GEN2
Adder
0.162
276772AC2-154 GEN
Solar/Wind Harmer
1.239
276806AD2-047 C O1
Solar/Wind Harmer
4.751
970941AG2-585 GEN
Solar/Wind Harmer
5.551
274772LINCOLN ;3U
Adder
2.752
972228AH1-698 GEN2
Adder
1.64
274676JOLIET 29;8U
Adder
13.03
276897AD1-100 C
Solar/Wind Harmer
12.768
939351AE1-166 GEN
Solar/Wind Harmer
2.609
276893AG1-478 C
Solar/Wind Harmer
0.184
274729ELWOOD EC;1P
Adder
7.227
274730ELWOOD EC;6P
Adder
7.227
274734ELWOOD EC;8P
Adder
7.227
274736ELWOOD EC;9P
Adder
7.227
970707AG2-453 GEN
Solar/Wind Harmer
12.309
970513AG2-328 GEN
Solar/Wind Harmer
7.828
970517AG2-330 GEN
Solar/Wind Harmer
7.1
971617AH1-308 GEN
Solar/Wind Harmer
2.543
274682WAUKEGAN ;7U
Adder
7.759
962511AG1-100 GEN
Solar/Wind Helper
0.34
203830AF1-094 GEN
Solar/Wind Helper
0.322
959441AF2-235 GEN
Solar/Wind Helper
0.146
254305AE2-115 C
Solar/Wind Helper
0.112
20334926Z1-069 C
Solar/Wind Helper
0.642
943121AE2-341 GEN
Solar/Wind Harmer
3.856
943591AF1-030 GEN
Solar/Wind Harmer
2.571
970321AG2-212 GEN
Solar/Wind Harmer
7.828
274847GR RIDGE ;BU
Solar/Wind Harmer
2.211
274696ROCKY RD ;4P
Adder
4.919
274695ROCKY RD ;2P
Adder
4.805
274693ROCKY RD ;1P
Adder
4.758
274697ROCKY RD ;3P
Adder
1.305
274683WAUKEGAN ;8U
Adder
9.089
274683WAUKEGAN ;8U
Adder
7.662
203947AF1-006 C
Solar/Wind Helper
0.379
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241967AE2-285_GEN
Solar/Wind Helper
0.337
241801AE1-079 GEN
Solar/Wind Helper
0.131
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.326
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23867002DVBSG1
50/50
13.062
972211AH1-690 GEN
50/50
279.989
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
241886AC2-103 GEN2
Solar/Wind Harmer
25.888
970817AG2-515 GEN
Solar/Wind Harmer
14.956
945411AF1-206 GEN
Solar/Wind Harmer
8.063
945641AF1-229 GEN
Solar/Wind Harmer
3.434
270499AE1-146 GEN
Solar/Wind Harmer
2.36
971549AH1-272 GEN
Solar/Wind Harmer
12.795
270297AD1-101 GEN
Solar/Wind Harmer
1.901
966831AG1-554 GEN
Solar/Wind Harmer
0.706
971989AH1-539 GEN
Solar/Wind Harmer
7.631
247607V1-011 GEN
Solar/Wind Harmer
2.315
957201AF2-014 GEN
Solar/Wind Harmer
2.633
270435AC2-044 GEN
Solar/Wind Harmer
1.161
944161AF1-084 GEN
Solar/Wind Harmer
1.265
965041AG1-368 GEN
Solar/Wind Harmer
5.449
965051AG1-369 GEN
Solar/Wind Harmer
2.706
971771AH1-392 GEN
Solar/Wind Harmer
4.715
270302AB2-170 GEN
Solar/Wind Harmer
4.356
270317AD1-130_GEN
Solar/Wind Harmer
1.67
971769AH1-391 GEN
Solar/Wind Harmer
5.107
971567AH1-282 GEN
Solar/Wind Harmer
7.577
960681AF2-359 GEN
Solar/Wind Harmer
1.856
971347AH1-153 GEN
Solar/Wind Harmer
7.336
963791AG1-232 GEN
Solar/Wind Harmer
6.532
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
270536AF1-215 GEN2
Solar/Wind Harmer
2.105
270071AF1-092 GEN
Solar/Wind Harmer
6.875
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.26
958391AF2-133 GEN
Solar/Wind Harmer
4.092
972037AH1-567 GEN1
Adder
0.082
274827FISK ;RP
Adder
3.457
960591AF2-350 GEN
Solar/Wind Harmer
4.441
274775LINCOLN ;6U
Adder
2.752
274776LINCOLN ;7U
Adder
2.752
274777LINCOLN ;8U
Adder
2.752
972227AH1-698 GEN1
Adder
1.155
274687WILL CNTY;4U
Adder
12.332
274687WILL CNTY;4U
Adder
12.332
274675JOLIET 29;7U
Adder
13.513
274675JOLIET 29;7U
Adder
13.03
274731ELWOOD EC;2P
Adder
7.227
274733ELWOOD EC;3P
Adder
7.227
274735ELWOOD EC;4P
Adder
7.227
274728ELWOOD EC;5P
Adder
7.227
270024AE2-089 GEN
Solar/Wind Harmer
2.053
970833AG2-524 GEN
Solar/Wind Harmer
3.819
970833AG2-524 GEN
Solar/Wind Harmer
1.776
274746AC1-111 G10
Adder
2.43
274744AC1-111 GEN8
Adder
2.43
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
203846AF2-130 C
Solar/Wind Helper
0.247
241997AF1-093 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.862
991182J1586 G
External Queue
24.279396057128906
991177J1571 G
External Queue
14.956707954406738
990142J1224
External Queue
12.976524353027344
990527J1329
External Queue
1.7751743793487549
LAGNLTFEXP_LAGN->PJM
CLTF
4.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
TVALTFEXP_TVA->PJM
CLTF
2.176
NYPJM->LTFIMP_NY
CLTF
2.013
LGEELTFEXP_LGEE->PJM
CLTF
1.955
WECLTFEXP_WEC->PJM
CLTF
1.61
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CPLELTFEXP_CPLE->PJM
CLTF
0.309
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.626
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010B1_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010B1_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2537.18
MW Contribution:287.42
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
26.725
241858AF1-205_GEN
Solar/Wind Harmer
5.381
241808AF1-120 C
Solar/Wind Harmer
1.18
241840AF1-064_GEN
Solar/Wind Harmer
1.335
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270361_3
Solar/Wind Harmer
7.665
960841AF2-375 GEN
Solar/Wind Harmer
3.397
970515AG2-329 GEN
Solar/Wind Harmer
9.891
247522W1-056 GEN
Solar/Wind Harmer
1.451
944231AF1-091 GEN
Solar/Wind Harmer
2.417
246936BC-WTG1
Solar/Wind Harmer
2.236
270489AE1-102 GEN1
Solar/Wind Harmer
0.743
965421AG1-410 GEN
Solar/Wind Harmer
16.981
270449AD2-020 GEN
Solar/Wind Harmer
1.58
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
9.834
270505AE1-170 C O1
Solar/Wind Harmer
8.262
24695305TIMB G C
Solar/Wind Harmer
3.031
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
1.791
270246TR4_N_V150
Solar/Wind Harmer
0.453
270063AE2-323 C
Solar/Wind Harmer
1.169
965011AG1-365 GEN
Solar/Wind Harmer
5.161
270462AD2-086
Solar/Wind Harmer
3.548
270223U2-072_GEN1
Solar/Wind Harmer
0.933
270578AF1-285 GEN2
Solar/Wind Harmer
0.571
270391AF1-285 GEN3
Solar/Wind Harmer
0.571
970373AG2-245 GEN
Solar/Wind Harmer
9.875
270055AF2-134 C O1
Solar/Wind Harmer
1.396
274751CRETE EC ;1U
Adder
2.221
274754CRETE EC ;4U
Adder
2.221
958381AF2-132 GEN
Solar/Wind Harmer
4.107
964861AG1-349 GEN
Solar/Wind Harmer
3.552
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0.314
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.187
940581AE2-045 GEN
Solar/Wind Harmer
4.502
971605AH1-302 GEN
Solar/Wind Harmer
3.85
972207SS24-0001
Solar/Wind Harmer
9.728
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
1.984
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
7.778
274871GR RIDGE ;2U
Solar/Wind Harmer
3.342
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.201
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
2.116
971677AH1-339 GEN
Solar/Wind Harmer
6.097
270007AE1-245 C
Solar/Wind Harmer
3.395
246938BC-WTG3
Solar/Wind Harmer
2.274
246937BC-WTG2
Solar/Wind Harmer
2.236
942801AE2-298 GEN
Solar/Wind Harmer
0.86
961051AF2-396 GEN
Solar/Wind Harmer
8.873
961051AF2-396 GEN
Solar/Wind Harmer
4.127
960981AF2-389 GEN
Solar/Wind Harmer
0.83
957891AF2-083 GEN
Solar/Wind Harmer
1.852
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.321
970611AG2-400 GEN
Solar/Wind Harmer
5.161
270526AF1-158 GEN
Solar/Wind Harmer
2.323
24441505OLIV SLR
Solar/Wind Harmer
0.068
965681AG1-436 GEN
Solar/Wind Harmer
6.114
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0.933
270227U2-072_GEN3
Solar/Wind Harmer
0.933
270228U2-072_GEN4
Solar/Wind Harmer
0.933
270231U2-072_GEN5
Solar/Wind Harmer
0.933
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274887GEN-1.85
Solar/Wind Harmer
2.354
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.32
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
7.778
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
26.725
970817AG2-515 GEN
Solar/Wind Harmer
15.015
945411AF1-206 GEN
Solar/Wind Harmer
7.902
945641AF1-229 GEN
Solar/Wind Harmer
3.386
270499AE1-146 GEN
Solar/Wind Harmer
2.146
971549AH1-272 GEN
Solar/Wind Harmer
12.819
270297AD1-101 GEN
Solar/Wind Harmer
1.836
247607V1-011 GEN
Solar/Wind Harmer
2.263
944161AF1-084 GEN
Solar/Wind Harmer
1.263
957201AF2-014 GEN
Solar/Wind Harmer
2.591
270435AC2-044 GEN
Solar/Wind Harmer
1.143
966831AG1-554 GEN
Solar/Wind Harmer
0.658
971989AH1-539 GEN
Solar/Wind Harmer
7.115
965041AG1-368 GEN
Solar/Wind Harmer
5.36
965051AG1-369 GEN
Solar/Wind Harmer
2.659
971771AH1-392 GEN
Solar/Wind Harmer
4.698
270302AB2-170 GEN
Solar/Wind Harmer
4.265
270317AD1-130_GEN
Solar/Wind Harmer
1.635
971769AH1-391 GEN
Solar/Wind Harmer
5.087
960681AF2-359 GEN
Solar/Wind Harmer
1.848
971567AH1-282 GEN
Solar/Wind Harmer
7.317
971347AH1-153 GEN
Solar/Wind Harmer
7.301
963791AG1-232 GEN
Solar/Wind Harmer
6.446
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
2.094
270071AF1-092 GEN
Solar/Wind Harmer
6.808
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
4.069
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
274847GR RIDGE ;BU
Solar/Wind Harmer
2.198
203947AF1-006 C
Solar/Wind Helper
0.37
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
958481AF2-142 GEN
Solar/Wind Harmer
6.372
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
1.919
958321AF2-126 GEN
Solar/Wind Harmer
1.431
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
4.156
270575GUS2 35KV
Solar/Wind Harmer
9.03
970217AG2-149 GEN
Solar/Wind Harmer
21.811
270044AE2-322 C
Solar/Wind Harmer
0.833
270404AC1-167 GEN
Solar/Wind Harmer
0.694
270258AD1-119 GEN
Solar/Wind Harmer
1.698
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0.08
270588AE1-091_GEN
Solar/Wind Harmer
6.42
958091AF2-103 GEN
Solar/Wind Harmer
0.092
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274776LINCOLN ;7U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
270491AE1-102 GEN2
Solar/Wind Harmer
0.743
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
1.598
270247TR4_N_V136
Solar/Wind Harmer
0.453
247643Z2-116 C
Solar/Wind Harmer
0.037
970031AG2-029 GEN
Solar/Wind Harmer
15.885
959331AF2-224 GEN
Solar/Wind Harmer
5.161
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.308
270043AE2-236 GEN
Solar/Wind Harmer
2.687
970349AG2-230 GEN
Solar/Wind Harmer
7.301
942871AE2-306 GEN
Solar/Wind Harmer
0.428
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
2.094
972231SS25-0005
Solar/Wind Harmer
4.312
972181SS23-001
Solar/Wind Harmer
2.695
274752CRETE EC ;2U
Adder
2.221
274753CRETE EC ;3U
Adder
2.221
964401AG1-302 GEN
Solar/Wind Harmer
4.107
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
2.692
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276772AC2-154 GEN
Solar/Wind Harmer
1.231
276806AD2-047 C O1
Solar/Wind Harmer
4.724
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
12.693
939351AE1-166 GEN
Solar/Wind Harmer
2.593
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.236
970513AG2-328 GEN
Solar/Wind Harmer
7.778
970517AG2-330 GEN
Solar/Wind Harmer
7.054
943121AE2-341 GEN
Solar/Wind Harmer
6.479
943591AF1-030 GEN
Solar/Wind Harmer
4.319
276694AA1-018 GEN2
Solar/Wind Harmer
2.725
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
991182J1586 G
External Queue
24.65229034423828
991177J1571 G
External Queue
15.044508934020996
990142J1224
External Queue
13.159761428833008
990527J1329
External Queue
1.8002409934997559
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.08 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2212.91
MW Contribution:287.42
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.125
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.109
23906502RICHG2&3
Adder
1.287
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.19
970217AG2-149 GEN
Solar/Wind Harmer
4.121
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.252
24441205WTRV SLR C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.185
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
3.117
24642205MAYFLWER
Adder
0.34
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.401
959331AF2-224 GEN
Solar/Wind Harmer
2.52
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
970349AG2-230 GEN
Solar/Wind Harmer
5.093
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.744
274753CRETE EC ;3U
Adder
3.744
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.981
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.587
274826FISK ;BP
Adder
4.849
274800UNIV PARK;3U
Adder
2.578
972038AH1-567 GEN2
Adder
0.161
276806AD2-047 C O1
Solar/Wind Harmer
1.746
970941AG2-585 GEN
Solar/Wind Harmer
3.851
274772LINCOLN ;3U
Adder
3.725
972228AH1-698 GEN2
Adder
1.631
274676JOLIET 29;8U
Adder
12.954
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.184
274730ELWOOD EC;6P
Adder
7.185
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
9.96
970513AG2-328 GEN
Solar/Wind Harmer
1.317
970517AG2-330 GEN
Solar/Wind Harmer
7.901
943121AE2-341 GEN
Solar/Wind Harmer
5.053
943591AF1-030 GEN
Solar/Wind Harmer
3.36
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.509
962511AG1-100 GEN
Solar/Wind Helper
0.332
203830AF1-094 GEN
Solar/Wind Helper
0.314
959441AF2-235 GEN
Solar/Wind Helper
0.143
254305AE2-115 C
Solar/Wind Helper
0.109
23867002DVBSG1
50/50
14.099
972211AH1-690 GEN
50/50
287.424
23888502TROY G1
50/50
1.793
23888602TROY G2
50/50
1.793
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.476
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.027
971549AH1-272 GEN
Solar/Wind Harmer
9.983
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.505
971619AH1-309 GEN
Solar/Wind Harmer
1.729
971989AH1-539 GEN
Solar/Wind Harmer
1.655
965041AG1-368 GEN
Solar/Wind Harmer
3.74
965051AG1-369 GEN
Solar/Wind Harmer
1.855
971771AH1-392 GEN
Solar/Wind Harmer
3.641
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.5
971769AH1-391 GEN
Solar/Wind Harmer
3.963
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971567AH1-282 GEN
Solar/Wind Harmer
5.105
971347AH1-153 GEN
Solar/Wind Harmer
5.093
963791AG1-232 GEN
Solar/Wind Harmer
4.498
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.069
274814UNIV PK N;0U
Adder
2.267
274807UNIV PK N;3U
Adder
2.262
274805UNIV PK N;1U
Adder
2.252
274811UNIV PK N;7U
Adder
2.247
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.437
960591AF2-350 GEN
Solar/Wind Harmer
3.081
971611AH1-305 GEN
Solar/Wind Harmer
1.834
274775LINCOLN ;6U
Adder
3.725
274776LINCOLN ;7U
Adder
3.725
274777LINCOLN ;8U
Adder
3.725
972227AH1-698 GEN1
Adder
1.148
274687WILL CNTY;4U
Adder
12.26
274687WILL CNTY;4U
Adder
12.26
274675JOLIET 29;7U
Adder
13.434
274675JOLIET 29;7U
Adder
12.954
274731ELWOOD EC;2P
Adder
7.184
274733ELWOOD EC;3P
Adder
7.184
274735ELWOOD EC;4P
Adder
7.184
274728ELWOOD EC;5P
Adder
7.185
970833AG2-524 GEN
Solar/Wind Harmer
3.337
970833AG2-524 GEN
Solar/Wind Harmer
2.225
274746AC1-111 G10
Adder
2.415
274744AC1-111 GEN8
Adder
2.415
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241982AE2-343 S C
Solar/Wind Helper
0.115
254304AE2-114 C
Solar/Wind Helper
0.109
203846AF2-130 C
Solar/Wind Helper
0.241
241997AF1-093 GEN
Solar/Wind Helper
0.127
203804AE2-113_GEN
Solar/Wind Helper
0.842
24190002OREGON_ST1
50/50
3.585
24189802OREGON_CT1
50/50
2.72
23888802TROY G4
50/50
1.793
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.599
970621AG2-405 GEN
Solar/Wind Harmer
0.843
970623AG2-406 GEN
Solar/Wind Harmer
0.778
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.144
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.8
961051AF2-396 GEN
Solar/Wind Harmer
5.2
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.247
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.601
970627AG2-408 GEN
Solar/Wind Harmer
1.08
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.266
965791AG1-447 GEN
Solar/Wind Harmer
3.128
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.237
274803UNIV PARK;6U
Adder
2.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.181
24189902OREGON_CT2
50/50
2.665
23888702TROY G3
50/50
1.793
972253AH1-711 GEN
50/50
54.781
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.866
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.754
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.449
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270361_3
Solar/Wind Harmer
4.19
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.364
247522W1-056 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.193
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
965421AG1-410 GEN
Solar/Wind Harmer
11.847
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.053
945111AF1-176 GEN
Solar/Wind Harmer
6.861
270505AE1-170 C O1
Solar/Wind Harmer
4.035
24695305TIMB G C
Solar/Wind Harmer
0.001
274887GEN-1.85
Solar/Wind Harmer
0.081
276843GEN-1.7
Solar/Wind Harmer
0.1
958011AF2-095 GEN
Solar/Wind Harmer
4.436
274770LINCOLN ;1U
Adder
3.725
274771LINCOLN ;2U
Adder
3.725
972259AH1-714 GEN
Adder
8.36
942221AE2-234 GEN
Solar/Wind Harmer
0.015
274674JOLIET 9 ;6U
Adder
6.729
970321AG2-212 GEN
Solar/Wind Harmer
1.317
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.519
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.56
203947AF1-006 C
Solar/Wind Helper
0.37
203980AG1-197 GEN
Solar/Wind Helper
0.242
203979AG1-198 GEN
Solar/Wind Helper
0.188
241967AE2-285_GEN
Solar/Wind Helper
0.33
241801AE1-079 GEN
Solar/Wind Helper
0.128
241985AE1-237 GEN
Solar/Wind Helper
0.128
962101AG1-054 GEN
Solar/Wind Helper
0.319
946381AF1-302 GEN
Solar/Wind Helper
0.102
24639705ELKHART HY
Adder
0.082
247521TR3_G114
Solar/Wind Harmer
0.135
270246TR4_N_V150
Solar/Wind Harmer
0.024
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.601
270462AD2-086
Solar/Wind Harmer
0.007
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.889
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274751CRETE EC ;1U
Adder
3.744
274754CRETE EC ;4U
Adder
3.744
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.099
274723RIVER EC ;12
Adder
8.078
274812UNIV PK N;8U
Adder
2.247
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.578
276776AD2-060 GEN
Solar/Wind Harmer
0.322
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.85
274773LINCOLN ;4U
Adder
3.725
274774LINCOLN ;5U
Adder
3.725
274676JOLIET 29;8U
Adder
13.434
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.729
970245AG2-165 GEN
Solar/Wind Harmer
1.317
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.365
961971AG1-040 GEN
Solar/Wind Helper
0.325
203835AF1-098 GEN
Solar/Wind Helper
1.28
203860AG1-193 C
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.767
254303AC2-168 GEN
Solar/Wind Helper
0.074
991182J1586 G
External Queue
24.65229034423828
991177J1571 G
External Queue
15.044508934020996
990142J1224
External Queue
13.159761428833008
990527J1329
External Queue
1.8002409934997559
LAGNLTFEXP_LAGN->PJM
CLTF
4.752
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
TVALTFEXP_TVA->PJM
CLTF
2.153
NYPJM->LTFIMP_NY
CLTF
1.97
LGEELTFEXP_LGEE->PJM
CLTF
1.929
WECLTFEXP_WEC->PJM
CLTF
1.6
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.578
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.528
MECLTFEXP_MEC->PJM
CLTF
6.231
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:274.79
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.251
241832AE2-181_GEN
Solar/Wind Harmer
0.003
958321AF2-126 GEN
Solar/Wind Harmer
1.147
23906502RICHG2&3
Adder
1.303
270575GUS2 35KV
Solar/Wind Harmer
4.647
270541AE2-072 C
Solar/Wind Harmer
0.008
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247604X1-042
Adder
0.248
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
3.081
270191TR4_S_V150
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.024
24642205MAYFLWER
Adder
0.337
970031AG2-029 GEN
Solar/Wind Harmer
2.384
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.518
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.712
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
7.915
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.566
274826FISK ;BP
Adder
4.81
274800UNIV PARK;3U
Adder
2.557
972038AH1-567 GEN2
Adder
0.16
276806AD2-047 C O1
Solar/Wind Harmer
1.732
23867002DVBSG1
50/50
12.718
972211AH1-690 GEN
50/50
274.788
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
1.766
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965041AG1-368 GEN
Solar/Wind Harmer
3.755
965051AG1-369 GEN
Solar/Wind Harmer
1.865
971771AH1-392 GEN
Solar/Wind Harmer
3.604
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.505
24191202EL_AA1-006
Adder
0.112
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.047
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.048
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
274827FISK ;RP
Adder
3.409
971611AH1-305 GEN
Solar/Wind Harmer
1.819
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274776LINCOLN ;7U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
972227AH1-698 GEN1
Adder
1.139
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274675JOLIET 29;7U
Adder
13.327
274675JOLIET 29;7U
Adder
12.851
274728ELWOOD EC;5P
Adder
7.127
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
24190002OREGON_ST1
50/50
3.428
24189802OREGON_CT1
50/50
2.6
23888802TROY G4
50/50
1.734
241996AE2-282_GEN
Solar/Wind Harmer
0.005
971677AH1-339 GEN
Solar/Wind Harmer
0.654
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.245
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.224
965791AG1-447 GEN
Solar/Wind Harmer
3.098
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.372
274808UNIV PK N;4U
Adder
2.219
274803UNIV PARK;6U
Adder
2.566
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
274674JOLIET 9 ;6U
Adder
6.676
970321AG2-212 GEN
Solar/Wind Harmer
1.307
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203947AF1-006 C
Solar/Wind Helper
0.375
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241967AE2-285_GEN
Solar/Wind Helper
0.334
241801AE1-079 GEN
Solar/Wind Helper
0.13
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
946381AF1-302 GEN
Solar/Wind Helper
0.103
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
972228AH1-698 GEN2
Adder
1.618
274676JOLIET 29;8U
Adder
12.851
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.12
274730ELWOOD EC;6P
Adder
7.127
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
274729ELWOOD EC;1P
Adder
7.127
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
203830AF1-094 GEN
Solar/Wind Helper
0.318
959441AF2-235 GEN
Solar/Wind Helper
0.145
254305AE2-115 C
Solar/Wind Helper
0.111
20334926Z1-069 C
Solar/Wind Helper
0.635
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
203846AF2-130 C
Solar/Wind Helper
0.244
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
24189902OREGON_CT2
50/50
2.548
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
23856402BAYSG1
50/50
1.279
23920202STRYCT
50/50
1.883
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.527
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
270361_3
Solar/Wind Harmer
4.647
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
241807AE2-176_GEN
Solar/Wind Harmer
0.004
247522W1-056 GEN
Solar/Wind Harmer
0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.533
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270428AC2-015 C
Solar/Wind Harmer
0.002
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.028
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270063AE2-323 C
Solar/Wind Harmer
0.003
965011AG1-365 GEN
Solar/Wind Harmer
3.597
270462AD2-086
Solar/Wind Harmer
0.008
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.065
274723RIVER EC ;12
Adder
8.011
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
274676JOLIET 29;8U
Adder
13.326
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
274871GR RIDGE ;2U
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
254303AC2-168 GEN
Solar/Wind Helper
0.075
991182J1586 G
External Queue
23.868927001953125
991177J1571 G
External Queue
14.724894523620605
990142J1224
External Queue
12.759525299072266
990527J1329
External Queue
1.745489239692688
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
TVALTFEXP_TVA->PJM
CLTF
2.148
NYPJM->LTFIMP_NY
CLTF
1.99
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CPLELTFEXP_CPLE->PJM
CLTF
0.305
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
MECLTFEXP_MEC->PJM
CLTF
6.19
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for AE1-108 POI-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:195.0 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:325.65
MW Contribution:8.44
Bus #Bus NameTypeMW Contribution
316217AC1-145 GEN
Solar/Wind Harmer
1.03
316197AC1-042 GEN
Solar/Wind Harmer
0.781
942671AE2-283 GEN
Solar/Wind Harmer
2.103
315821AE2-092 GEN
Solar/Wind Helper
1.507
962751AG1-124 GEN
Solar/Wind Harmer
9.516
270173AC1-122 GEN
Solar/Wind Harmer
0.712
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.381
274676JOLIET 29;8U
Adder
2.275
274729ELWOOD EC;1P
Adder
1.265
274730ELWOOD EC;6P
Adder
1.265
274734ELWOOD EC;8P
Adder
1.265
274736ELWOOD EC;9P
Adder
1.265
270494AE1-108_GEN
Solar/Wind Harmer
23.273
274675JOLIET 29;7U
Adder
2.36
274675JOLIET 29;7U
Adder
2.275
274731ELWOOD EC;2P
Adder
1.265
274733ELWOOD EC;3P
Adder
1.265
274735ELWOOD EC;4P
Adder
1.265
274728ELWOOD EC;5P
Adder
1.265
972211AH1-690 GEN
Adder
8.443
966251AG1-494 GEN
50/50
3.427
958131AF2-107 GEN
Solar/Wind Harmer
12.497
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.381
274676JOLIET 29;8U
Adder
2.36
274732ELWOOD EC;7P
Adder
1.265
944201AF1-088_MTX
Adder
9.558
957141AF2-008_MTX
Adder
4.779
LAGNLTFEXP_LAGN->PJM
CLTF
1.736
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.907
TVALTFEXP_TVA->PJM
CLTF
0.914
NYPJM->LTFIMP_NY
CLTF
0.286
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.349
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.398
MECLTFEXP_MEC->PJM
CLTF
1.352
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for AE1-108 POI-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:193.53 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:323.2
MW Contribution:8.45
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.518
270173AC1-122 GEN
Solar/Wind Harmer
0.712
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.382
274676JOLIET 29;8U
Adder
2.277
274729ELWOOD EC;1P
Adder
1.266
274730ELWOOD EC;6P
Adder
1.266
274734ELWOOD EC;8P
Adder
1.266
274736ELWOOD EC;9P
Adder
1.266
270494AE1-108_GEN
Solar/Wind Harmer
23.275
274675JOLIET 29;7U
Adder
2.362
274675JOLIET 29;7U
Adder
2.277
274731ELWOOD EC;2P
Adder
1.266
274733ELWOOD EC;3P
Adder
1.266
274735ELWOOD EC;4P
Adder
1.266
274728ELWOOD EC;5P
Adder
1.266
972211AH1-690 GEN
Adder
8.451
316217AC1-145 GEN
Solar/Wind Harmer
1.031
316197AC1-042 GEN
Solar/Wind Harmer
0.781
942671AE2-283 GEN
Solar/Wind Harmer
2.104
315821AE2-092 GEN
Solar/Wind Helper
1.505
966251AG1-494 GEN
50/50
3.428
958131AF2-107 GEN
Solar/Wind Harmer
12.498
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.382
274676JOLIET 29;8U
Adder
2.362
274732ELWOOD EC;7P
Adder
1.266
944201AF1-088_MTX
Adder
9.567
957141AF2-008_MTX
Adder
4.783
LAGNLTFEXP_LAGN->PJM
CLTF
1.739
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.915
NYPJM->LTFIMP_NY
CLTF
0.285
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.848
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
1.353
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for AE1-108 POI-4BREMO 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:193.36 %
Rating:167.0 MVA
Rating Type:B
MVA to Mitigate:322.91
MW Contribution:8.45
Bus #Bus NameTypeMW Contribution
962751AG1-124 GEN
Solar/Wind Harmer
9.518
270173AC1-122 GEN
Solar/Wind Harmer
0.712
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.382
274676JOLIET 29;8U
Adder
2.278
274729ELWOOD EC;1P
Adder
1.266
274730ELWOOD EC;6P
Adder
1.266
274734ELWOOD EC;8P
Adder
1.266
274736ELWOOD EC;9P
Adder
1.266
270494AE1-108_GEN
Solar/Wind Harmer
23.275
274675JOLIET 29;7U
Adder
2.362
274675JOLIET 29;7U
Adder
2.278
274731ELWOOD EC;2P
Adder
1.266
274733ELWOOD EC;3P
Adder
1.266
274735ELWOOD EC;4P
Adder
1.266
274728ELWOOD EC;5P
Adder
1.266
972211AH1-690 GEN
Adder
8.451
316217AC1-145 GEN
Solar/Wind Harmer
1.031
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.104
315821AE2-092 GEN
Solar/Wind Helper
1.505
966251AG1-494 GEN
50/50
3.428
958131AF2-107 GEN
Solar/Wind Harmer
12.499
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.382
274676JOLIET 29;8U
Adder
2.362
274732ELWOOD EC;7P
Adder
1.266
944201AF1-088_MTX
Adder
9.568
957141AF2-008_MTX
Adder
4.784
LAGNLTFEXP_LAGN->PJM
CLTF
1.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.915
TVALTFEXP_TVA->PJM
CLTF
0.916
NYPJM->LTFIMP_NY
CLTF
0.285
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.366
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.849
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
1.354
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for AE1-108 POI-4BREMO 138.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
AE1-108 POI-4BREMO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:192.44 %
Rating:156.98 MVA
Rating Type:B
MVA to Mitigate:302.1
MW Contribution:8.45
Bus #Bus NameTypeMW Contribution
270494AE1-108_GEN
Solar/Wind Harmer
9.548
274675JOLIET 29;7U
Adder
2.362
274675JOLIET 29;7U
Adder
2.278
274731ELWOOD EC;2P
Adder
1.266
274733ELWOOD EC;3P
Adder
1.266
274735ELWOOD EC;4P
Adder
1.266
274728ELWOOD EC;5P
Adder
1.266
972211AH1-690 GEN
Adder
8.451
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.407
315821AE2-092 GEN
Solar/Wind Helper
1.505
962751AG1-124 GEN
Solar/Wind Harmer
6.519
270173AC1-122 GEN
Solar/Wind Harmer
0.147
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.809
972273AH1-721 GEN
Adder
7.869
274676JOLIET 29;8U
Adder
2.278
274729ELWOOD EC;1P
Adder
1.266
274730ELWOOD EC;6P
Adder
1.266
274734ELWOOD EC;8P
Adder
1.266
274736ELWOOD EC;9P
Adder
1.266
966251AG1-494 GEN
50/50
3.428
24288905REUSENS
50/50
0.018
958131AF2-107 GEN
Solar/Wind Harmer
9.389
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.809
274676JOLIET 29;8U
Adder
2.362
274732ELWOOD EC;7P
Adder
1.266
944201AF1-088_MTX
Adder
9.568
LAGNLTFEXP_LAGN->PJM
CLTF
1.74
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.915
TVALTFEXP_TVA->PJM
CLTF
0.916
NYPJM->LTFIMP_NY
CLTF
0.285
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.366
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.849
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
1.354
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o AEP_P4_#17249_05FOSTOR 345_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17249_05FOSTOR 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.88 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:260.64
MW Contribution:30.96
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
2.343
972301AH1-735 GEN
50/50
11.302
23906402RICHG1
50/50
2.26
23920202STRYCT
50/50
1.417
241808AF1-120 C
Solar/Wind Harmer
0.66
241858AF1-205_GEN
Solar/Wind Harmer
2.467
23906902RICHG6
50/50
1.343
23906702RICHG4
50/50
1.339
23906802RICHG5
50/50
0.978
945411AF1-206 GEN
Solar/Wind Harmer
4.421
972211AH1-690 GEN
Adder
30.956
23906502RICHG2&3
50/50
2.343
270541AE2-072 C
Solar/Wind Harmer
22.61
241832AE2-181_GEN
Solar/Wind Harmer
1.246
241996AE2-282_GEN
Solar/Wind Harmer
1.184
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.389
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.121
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.82
MECLTFEXP_MEC->PJM
CLTF
0.072

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o AEP_P4_#10098_05LCKWRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10098_05LCKWRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.73 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:244.7
MW Contribution:19.24
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
1.437
23906902RICHG6
50/50
1.781
23906702RICHG4
50/50
1.776
23906802RICHG5
50/50
1.297
945411AF1-206 GEN
Solar/Wind Harmer
5.368
972211AH1-690 GEN
Adder
19.244
23906502RICHG2&3
50/50
3.071
270541AE2-072 C
Solar/Wind Harmer
24.169
241832AE2-181_GEN
Solar/Wind Harmer
1.542
23906502RICHG2&3
50/50
3.071
972301AH1-735 GEN
50/50
14.994
23906402RICHG1
50/50
2.999
23920202STRYCT
50/50
1.785
241808AF1-120 C
Solar/Wind Harmer
0.801
241858AF1-205_GEN
Solar/Wind Harmer
2.914
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.165
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.509
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.071
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.557
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.516

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o AEP_P2-2_#5123_05LCKWRD 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5123_05LCKWRD 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.65 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:244.53
MW Contribution:19.27
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
3.072
972301AH1-735 GEN
50/50
14.996
23906402RICHG1
50/50
2.999
23920202STRYCT
50/50
1.785
241808AF1-120 C
Solar/Wind Harmer
0.802
241858AF1-205_GEN
Solar/Wind Harmer
2.915
23906902RICHG6
50/50
1.781
23906702RICHG4
50/50
1.776
23906802RICHG5
50/50
1.298
945411AF1-206 GEN
Solar/Wind Harmer
5.369
972211AH1-690 GEN
Adder
19.265
241996AE2-282_GEN
Solar/Wind Harmer
1.438
23906502RICHG2&3
50/50
3.072
270541AE2-072 C
Solar/Wind Harmer
24.172
241832AE2-181_GEN
Solar/Wind Harmer
1.542
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.165
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.51
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.071
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.499

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o AEP_P4_#5123_05LCKWRD 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#5123_05LCKWRD 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.65 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:244.51
MW Contribution:19.27
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
1.438
23906502RICHG2&3
50/50
3.072
972301AH1-735 GEN
50/50
14.996
23906402RICHG1
50/50
2.999
23920202STRYCT
50/50
1.785
241808AF1-120 C
Solar/Wind Harmer
0.802
241858AF1-205_GEN
Solar/Wind Harmer
2.915
23906902RICHG6
50/50
1.781
23906702RICHG4
50/50
1.776
23906802RICHG5
50/50
1.298
945411AF1-206 GEN
Solar/Wind Harmer
5.369
972211AH1-690 GEN
Adder
19.265
23906502RICHG2&3
50/50
3.072
270541AE2-072 C
Solar/Wind Harmer
24.172
241832AE2-181_GEN
Solar/Wind Harmer
1.542
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.165
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.51
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.111
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.071
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.499

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.2 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:234.6
MW Contribution:13.4
Bus #Bus NameTypeMW Contribution
23906902RICHG6
50/50
1.313
23906702RICHG4
50/50
1.309
23906802RICHG5
50/50
0.956
945411AF1-206 GEN
Solar/Wind Harmer
3.918
972211AH1-690 GEN
Adder
13.401
23906502RICHG2&3
50/50
2.295
270541AE2-072 C
Solar/Wind Harmer
22.678
241832AE2-181_GEN
Solar/Wind Harmer
1.127
241996AE2-282_GEN
Solar/Wind Harmer
1.049
23906502RICHG2&3
50/50
2.295
972301AH1-735 GEN
50/50
11.053
23906402RICHG1
50/50
2.211
23920202STRYCT
50/50
1.307
241808AF1-120 C
Solar/Wind Harmer
0.585
241858AF1-205_GEN
Solar/Wind Harmer
2.105
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.104
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.09
WECLTFEXP_WEC->PJM
CLTF
0.066
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.073
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.274
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.567
MECLTFEXP_MEC->PJM
CLTF
0.199

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.28 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:230.31
MW Contribution:12.53
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
2.292
972301AH1-735 GEN
50/50
11.039
23906402RICHG1
50/50
2.208
23920202STRYCT
50/50
1.303
241808AF1-120 C
Solar/Wind Harmer
0.582
241858AF1-205_GEN
Solar/Wind Harmer
2.094
23906902RICHG6
50/50
1.311
23906702RICHG4
50/50
1.308
23906802RICHG5
50/50
0.955
945411AF1-206 GEN
Solar/Wind Harmer
3.901
972211AH1-690 GEN
Adder
12.533
23906502RICHG2&3
50/50
2.292
270541AE2-072 C
Solar/Wind Harmer
22.671
241832AE2-181_GEN
Solar/Wind Harmer
1.123
241996AE2-282_GEN
Solar/Wind Harmer
1.044
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.117
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.086
WECLTFEXP_WEC->PJM
CLTF
0.062
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.073
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.321
MECLTFEXP_MEC->PJM
CLTF
0.183

Details for AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line l/o AEP_P2-2_#744_05FOSTOR 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-072 TAP-05E.LEIPSIC2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#744_05FOSTOR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.96 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:225.14
MW Contribution:12.11
Bus #Bus NameTypeMW Contribution
23906902RICHG6
50/50
1.292
23906702RICHG4
50/50
1.288
23906802RICHG5
50/50
0.941
945411AF1-206 GEN
Solar/Wind Harmer
3.818
972211AH1-690 GEN
Adder
12.111
270499AE1-146 GEN
Solar/Wind Helper
1.394
241996AE2-282_GEN
Solar/Wind Harmer
1.022
23906502RICHG2&3
50/50
2.258
270541AE2-072 C
Solar/Wind Harmer
22.405
241832AE2-181_GEN
Solar/Wind Harmer
1.101
23906502RICHG2&3
50/50
2.258
972301AH1-735 GEN
50/50
10.873
23906402RICHG1
50/50
2.175
23920202STRYCT
50/50
1.278
241808AF1-120 C
Solar/Wind Harmer
0.57
241858AF1-205_GEN
Solar/Wind Harmer
2.04
960841AF2-375 GEN
Solar/Wind Helper
0.79
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.189
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
WECLTFEXP_WEC->PJM
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.077
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.709
MECLTFEXP_MEC->PJM
CLTF
0.118

Details for AG2-148 TP-02GALION 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:1308.0 MVA
Rating Type:B
MVA to Mitigate:1388.99
MW Contribution:228.6
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.547
972253AH1-711 GEN
50/50
47.255
24189902OREGON_CT2
50/50
2.124
23856402BAYSG1
50/50
1.067
23920202STRYCT
50/50
1.652
970515AG2-329 GEN
Solar/Wind Harmer
65.578
270361_3
Solar/Wind Harmer
11.019
960841AF2-375 GEN
Solar/Wind Harmer
4.812
241858AF1-205_GEN
Solar/Wind Harmer
4.763
241808AF1-120 C
Solar/Wind Harmer
1.035
241840AF1-064_GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
2.175
23906502RICHG2&3
Adder
1.164
972301AH1-735 GEN
Adder
5.82
23906402RICHG1
Adder
1.164
246936BC-WTG1
Solar/Wind Harmer
2.02
270489AE1-102 GEN1
Solar/Wind Harmer
0.671
965421AG1-410 GEN
Solar/Wind Harmer
15.09
944231AF1-091 GEN
Solar/Wind Harmer
1.879
270428AC2-015 C
Solar/Wind Harmer
2.682
241807AE2-176_GEN
Solar/Wind Harmer
1.803
24695305TIMB G C
Solar/Wind Harmer
2.462
270462AD2-086
Solar/Wind Harmer
3.011
958961AF2-187 GEN
Solar/Wind Helper
1.304
23888502TROY G1
50/50
1.547
23888602TROY G2
50/50
1.547
972211AH1-690 GEN
50/50
228.604
23867002DVBSG1
50/50
7.841
945641AF1-229 GEN
Solar/Wind Harmer
11.095
970817AG2-515 GEN
Solar/Wind Harmer
12.936
270499AE1-146 GEN
Solar/Wind Harmer
2.975
945411AF1-206 GEN
Solar/Wind Harmer
6.936
270297AD1-101 GEN
Solar/Wind Harmer
1.752
966831AG1-554 GEN
Solar/Wind Harmer
0.725
971989AH1-539 GEN
Solar/Wind Harmer
7.841
957201AF2-014 GEN
Solar/Wind Harmer
2.341
270435AC2-044 GEN
Solar/Wind Harmer
1.032
247607V1-011 GEN
Solar/Wind Harmer
1.952
971549AH1-272 GEN
Solar/Wind Harmer
9.056
270302AB2-170 GEN
Solar/Wind Harmer
3.619
270317AD1-130_GEN
Solar/Wind Harmer
1.387
23888802TROY G4
50/50
1.547
24190002OREGON_ST1
50/50
2.858
24189802OREGON_CT1
50/50
2.168
971677AH1-339 GEN
Solar/Wind Harmer
12.459
241996AE2-282_GEN
Solar/Wind Harmer
1.857
246938BC-WTG3
Solar/Wind Harmer
2.055
246937BC-WTG2
Solar/Wind Harmer
2.02
270007AE1-245 C
Solar/Wind Harmer
2.929
942801AE2-298 GEN
Solar/Wind Harmer
0.723
241960AC2-195 GEN
Solar/Wind Helper
2.638
23929302BS-PKR
50/50
1.879
970217AG2-149 GEN
Solar/Wind Harmer
144.609
270575GUS2 35KV
Solar/Wind Harmer
12.982
241832AE2-181_GEN
Solar/Wind Harmer
1.691
958321AF2-126 GEN
Solar/Wind Harmer
1.328
23906502RICHG2&3
Adder
1.164
270541AE2-072 C
Solar/Wind Harmer
4.235
270588AE1-091_GEN
Solar/Wind Harmer
7.004
270044AE2-322 C
Solar/Wind Harmer
0.704
270404AC1-167 GEN
Solar/Wind Harmer
0.586
270491AE1-102 GEN2
Solar/Wind Harmer
0.671
270258AD1-119 GEN
Solar/Wind Harmer
1.414
958091AF2-103 GEN
Solar/Wind Harmer
0.08
270485AE1-090_GEN
Solar/Wind Harmer
0.262
991182J1586 G
External Queue
23.483379364013672
991177J1571 G
External Queue
14.578453063964844
990142J1224
External Queue
12.53613567352295
990527J1329
External Queue
1.7149295806884766
LAGNLTFEXP_LAGN->PJM
CLTF
1.487
TVALTFEXP_TVA->PJM
CLTF
0.529
NYPJM->LTFIMP_NY
CLTF
0.701
LGEELTFEXP_LGEE->PJM
CLTF
0.514
WECLTFEXP_WEC->PJM
CLTF
0.87
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.438
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.62
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
3.106
SIGELTFEXP_SIGE->PJM
CLTF
0.058

Details for AG2-148 TP-02GALION 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-030_SRT-A


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
AG2-148 TP-02GALION 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.3 %
Rating:1308.0 MVA
Rating Type:B
MVA to Mitigate:1377.33
MW Contribution:222.24
Bus #Bus NameTypeMW Contribution
23888802TROY G4
50/50
1.513
24190002OREGON_ST1
50/50
2.778
24189802OREGON_CT1
50/50
2.107
971677AH1-339 GEN
Solar/Wind Harmer
12.57
241996AE2-282_GEN
Solar/Wind Harmer
1.843
23888502TROY G1
50/50
1.513
23888602TROY G2
50/50
1.513
246938BC-WTG3
Solar/Wind Harmer
2.036
246937BC-WTG2
Solar/Wind Harmer
2.001
270007AE1-245 C
Solar/Wind Harmer
2.91
942801AE2-298 GEN
Solar/Wind Harmer
0.718
241960AC2-195 GEN
Solar/Wind Helper
2.635
23929302BS-PKR
50/50
1.897
970217AG2-149 GEN
Solar/Wind Harmer
144.498
270575GUS2 35KV
Solar/Wind Harmer
13.195
241832AE2-181_GEN
Solar/Wind Harmer
1.678
958321AF2-126 GEN
Solar/Wind Harmer
1.33
23906502RICHG2&3
Adder
1.158
270541AE2-072 C
Solar/Wind Harmer
4.235
270588AE1-091_GEN
Solar/Wind Harmer
7.042
270044AE2-322 C
Solar/Wind Harmer
0.699
270404AC1-167 GEN
Solar/Wind Harmer
0.582
270491AE1-102 GEN2
Solar/Wind Harmer
0.665
270258AD1-119 GEN
Solar/Wind Harmer
1.404
958091AF2-103 GEN
Solar/Wind Harmer
0.079
972211AH1-690 GEN
50/50
222.237
23867002DVBSG1
50/50
7.301
23860102FRMENG 1
50/50
1.131
23860202FRMENG 2
50/50
1.131
945641AF1-229 GEN
Solar/Wind Harmer
11.066
970817AG2-515 GEN
Solar/Wind Harmer
12.715
241886AC2-103 GEN2
Solar/Wind Harmer
7.319
270499AE1-146 GEN
Solar/Wind Harmer
3.019
945411AF1-206 GEN
Solar/Wind Harmer
6.885
24191202EL_AA1-006
Adder
0.154
270297AD1-101 GEN
Solar/Wind Harmer
1.749
966831AG1-554 GEN
Solar/Wind Harmer
0.732
971989AH1-539 GEN
Solar/Wind Harmer
7.919
957201AF2-014 GEN
Solar/Wind Harmer
2.32
270435AC2-044 GEN
Solar/Wind Harmer
1.023
247607V1-011 GEN
Solar/Wind Harmer
1.939
971549AH1-272 GEN
Solar/Wind Harmer
8.874
23888702TROY G3
50/50
1.513
972253AH1-711 GEN
50/50
46.215
24189902OREGON_CT2
50/50
2.065
23856402BAYSG1
50/50
1.078
23920202STRYCT
50/50
1.641
23860302FRMENG 3
50/50
2.311
970515AG2-329 GEN
Solar/Wind Harmer
65.528
270361_3
Solar/Wind Harmer
11.201
960841AF2-375 GEN
Solar/Wind Harmer
4.888
241885AC2-103 GEN1
Solar/Wind Harmer
7.319
241858AF1-205_GEN
Solar/Wind Harmer
4.732
241808AF1-120 C
Solar/Wind Harmer
1.028
241840AF1-064_GEN
Solar/Wind Harmer
1.24
247522W1-056 GEN
Solar/Wind Harmer
2.197
23906502RICHG2&3
Adder
1.158
972301AH1-735 GEN
Adder
5.785
23906402RICHG1
Adder
1.157
241807AE2-176_GEN
Solar/Wind Harmer
3.394
270428AC2-015 C
Solar/Wind Harmer
2.976
246936BC-WTG1
Solar/Wind Harmer
2.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.665
965421AG1-410 GEN
Solar/Wind Harmer
14.948
944231AF1-091 GEN
Solar/Wind Harmer
1.859
24695305TIMB G C
Solar/Wind Harmer
2.44
958961AF2-187 GEN
Solar/Wind Helper
1.26
991182J1586 G
External Queue
23.031686782836914
991177J1571 G
External Queue
14.350388526916504
990142J1224
External Queue
12.300400733947754
990527J1329
External Queue
1.6826814413070679
LAGNLTFEXP_LAGN->PJM
CLTF
1.435
TVALTFEXP_TVA->PJM
CLTF
0.506
NYPJM->LTFIMP_NY
CLTF
0.692
LGEELTFEXP_LGEE->PJM
CLTF
0.496
WECLTFEXP_WEC->PJM
CLTF
0.851
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.02
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
60.282
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.046
MECLTFEXP_MEC->PJM
CLTF
3.034
SIGELTFEXP_SIGE->PJM
CLTF
0.057

Details for AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line l/o ATSI_P1-2_TE-345-606_SRT-A-1


Base Case Flowgate

Area:ATSI
Facility Description:
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P1-2_TE-345-606_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.39 %
Rating:1774.0 MVA
Rating Type:B
MVA to Mitigate:1816.36
MW Contribution:717.96
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
8.93
24189802OREGON_CT1
50/50
6.774
241996AE2-282_GEN
Solar/Wind Helper
0.654
247604X1-042
50/50
0.205
970217AG2-149 GEN
Solar/Wind Harmer
2.97
24441205WTRV SLR C
Solar/Wind Harmer
0
241832AE2-181_GEN
Solar/Wind Helper
0.274
972211AH1-690 GEN
50/50
717.964
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
7.71
241886AC2-103 GEN2
Solar/Wind Helper
3.47
945411AF1-206 GEN
Solar/Wind Helper
1.24
24189902OREGON_CT2
50/50
6.637
970515AG2-329 GEN
Solar/Wind Harmer
8.909
241885AC2-103 GEN1
Solar/Wind Helper
3.47
241807AE2-176_GEN
Solar/Wind Helper
1.924
241808AF1-120 C
Solar/Wind Helper
0.366
241840AF1-064_GEN
Solar/Wind Helper
0.496
LAGNLTFEXP_LAGN->PJM
CLTF
3.603
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.003
TVALTFEXP_TVA->PJM
CLTF
1.642
NYPJM->LTFIMP_NY
CLTF
1.135
LGEELTFEXP_LGEE->PJM
CLTF
1.403
WECLTFEXP_WEC->PJM
CLTF
1.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CPLELTFEXP_CPLE->PJM
CLTF
0.432
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.793
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.436
MECLTFEXP_MEC->PJM
CLTF
4.596
SIGELTFEXP_SIGE->PJM
CLTF
0.118

Details for AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line l/o ATSI_P2-3_TE-345-002_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AH1-690 TP-02BAY SH 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_TE-345-002_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1741.77
MW Contribution:686.08
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
686.076
945641AF1-229 GEN
Solar/Wind Harmer
2.405
971549AH1-272 GEN
Solar/Wind Harmer
9.865
944161AF1-084 GEN
Solar/Wind Harmer
0.95
241886AC2-103 GEN2
Solar/Wind Helper
3.545
24190002OREGON_ST1
50/50
8.534
24189802OREGON_CT1
50/50
6.473
970217AG2-149 GEN
Solar/Wind Harmer
15.369
247604X1-042
Adder
0.193
24441205WTRV SLR C
Solar/Wind Harmer
0.061
24189902OREGON_CT2
50/50
6.343
970515AG2-329 GEN
Solar/Wind Harmer
6.97
241885AC2-103 GEN1
Solar/Wind Helper
3.545
241807AE2-176_GEN
Solar/Wind Helper
1.782
990142J1224
External Queue
7.395538330078125
990527J1329
External Queue
1.0117015838623047
LAGNLTFEXP_LAGN->PJM
CLTF
3.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.988
TVALTFEXP_TVA->PJM
CLTF
1.638
NYPJM->LTFIMP_NY
CLTF
1.14
LGEELTFEXP_LGEE->PJM
CLTF
1.401
WECLTFEXP_WEC->PJM
CLTF
1.176
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CPLELTFEXP_CPLE->PJM
CLTF
0.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.219
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.917
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.423
MECLTFEXP_MEC->PJM
CLTF
4.59
SIGELTFEXP_SIGE->PJM
CLTF
0.117

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-018_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-018_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:179.12
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-017_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-017_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:179.12
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1154-W_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1154-W_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.81 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:159.76
MW Contribution:7.85
Bus #Bus NameTypeMW Contribution
970713AG2-456 GEN
Solar/Wind Harmer
2.477
971705AH1-358 GEN
Solar/Wind Harmer
0.72
971709AH1-360 GEN
Solar/Wind Harmer
0.72
959471AF2-238 GEN
Solar/Wind Helper
0.551
971703AH1-357 GEN
Solar/Wind Harmer
0.619
971707AH1-359 GEN
Solar/Wind Harmer
0.619
972191AH1-680 GEN
Adder
7.47
941421AE2-139 GEN
Solar/Wind Helper
3.345
200917MEHOOPANY_G
Solar/Wind Helper
2.227
20083926HOMER C3
Adder
18.011
20083826HOMER C2
Adder
17.014
20083726HOMER C1
Adder
10.622
972211AH1-690 GEN
Adder
7.849
203859AF2-294 C
Solar/Wind Harmer
0.816
972077AH1-588 GEN
Solar/Wind Harmer
7.43
972079AH1-589 GEN
Solar/Wind Harmer
6.12
970715AG2-457 GEN
Solar/Wind Harmer
2.477
970935AG2-582 GEN
Adder
7.698
20398826ARMNA MT
Solar/Wind Helper
1.623
LAGNLTFEXP_LAGN->PJM
CLTF
0.704
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.823
TVALTFEXP_TVA->PJM
CLTF
0.349
LGEELTFEXP_LGEE->PJM
CLTF
0.264
WECLTFEXP_WEC->PJM
CLTF
0.151
CPLELTFEXP_CPLE->PJM
CLTF
0.265
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.942
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.333
MECLTFEXP_MEC->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.38 %
Rating:114.0 MVA
Rating Type:A
MVA to Mitigate:132.68
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o AP_P2-2_WP-230-001T_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:144.71
MW Contribution:7.6
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
16.064
20083826HOMER C2
Adder
15.174
20083726HOMER C1
Adder
9.328
972211AH1-690 GEN
Adder
7.602
203859AF2-294 C
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
8.696
972079AH1-589 GEN
Solar/Wind Harmer
7.162
970715AG2-457 GEN
Solar/Wind Harmer
2.899
970935AG2-582 GEN
Adder
7.181
971703AH1-357 GEN
Solar/Wind Harmer
0.725
971707AH1-359 GEN
Solar/Wind Harmer
0.725
972191AH1-680 GEN
Adder
7.211
941421AE2-139 GEN
Solar/Wind Helper
3.037
200917MEHOOPANY_G
Solar/Wind Helper
2.024
970713AG2-456 GEN
Solar/Wind Harmer
2.899
971705AH1-358 GEN
Solar/Wind Harmer
0.843
971709AH1-360 GEN
Solar/Wind Harmer
0.843
959471AF2-238 GEN
Solar/Wind Helper
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
0.665
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.766
TVALTFEXP_TVA->PJM
CLTF
0.329
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.144
CPLELTFEXP_CPLE->PJM
CLTF
0.244
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.261
MECLTFEXP_MEC->PJM
CLTF
0.616
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CONTINGENCY 'ATSI_P7-1_OEC-345-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 239725 CKT 1   /*02AVON       345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 239725 CKT 2   /*02AVON       345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-008B_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1          /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-013_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1          /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 2          /*02LEMOYN     345.0 - 02LEMOYN     138.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238889 TO BUS 238961 CKT 1 /*02LEMOYN     345.0 - 02MIDWAY     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238654 CKT 1   /*02LEMOYN     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 238890 CKT 1   /*02LEMOYN     345.0 - 02LEMOYN     138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P7-1_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-901_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-007A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 2   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 1   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-F1_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 2   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-12_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B2_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010B1_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1          /*02DAV-BE     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P4_#8396_05OHIOCT 345_M_SRT-A'
 OPEN BRANCH FROM BUS 971566 TO BUS 242941 CKT 1   /*AH1-282 TP   345.0 - 05OHIOCT     345.0
 REMOVE SWSHUNT FROM BUS 242941                    /*05OHIOCT     345.0
END
CONTINGENCY 'AEP_P4_#16815_05OHIOCT 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 242941 TO BUS 244319 CKT Z1   /*05OHIOCT     345.0 - 05OHIOCT_REA 345.0
 OPEN BRANCH FROM BUS 971566 TO BUS 242941 CKT 1    /*AH1-282 TP   345.0 - 05OHIOCT     345.0
END
CONTINGENCY 'ATSI_P2-3_OES-138-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238746 TO BUS 238747 CKT 1          /*02GALION     138.0 - 02GALION      69.0
 DISCONNECT BRANCH FROM BUS 238746 TO BUS 239308 CKT 1          /*02GALION     138.0 - 02MR-ETH     138.0
 DISCONNECT BRANCH FROM BUS 239073 TO BUS 239308 CKT 1          /*02ROBERT     138.0 - 02MR-ETH     138.0
 DISCONNECT BUS 239308                                          /*02MR-ETH     138.0
 REDUCE BUS 238746 SHUNT BY 100 PERCENT                         /*02GALION     138.0
 REMOVE LOAD C FROM BUS 239308                                  /*02MR-ETH     138.0
 SET POSTCONTRATING 413 BRANCH FROM BUS 238745 TO BUS 238746 CKT 4 /*02GALION     345.0 - 02GALION     138.0
 SET POSTCONTRATING 417 BRANCH FROM BUS 238745 TO BUS 238746 CKT 3 /*02GALION     345.0 - 02GALION     138.0
 SET PRECONTRATING 328 BRANCH FROM BUS 238745 TO BUS 238746 CKT 3 /*02GALION     345.0 - 02GALION     138.0
 SET PRECONTRATING 329 BRANCH FROM BUS 238745 TO BUS 238746 CKT 4 /*02GALION     345.0 - 02GALION     138.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-025_BDR_A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1          /*02AVON       345.0 - 02JUNIPE     345.0
 DISCONNECT BRANCH FROM BUS 238781 TO BUS 238850 CKT 1          /*02HANNA      345.0 - 02JUNIPE     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238783 TO BUS 238850 CKT 1 /*02HARDIN     345.0 - 02JUNIPE     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238783 TO BUS 238850 CKT 1 /*02HARDIN     345.0 - 02JUNIPE     345.0
END
CONTINGENCY 'ATSI_P7-1_CEI-345-010_SRT-A'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1   /*02AVON       345.0 - 02JUNIPE     345.0
 DISCONNECT BRANCH FROM BUS 238783 TO BUS 238615 CKT 1   /*02HARDIN     345.0 - 02CHAMBR     345.0
END
CONTINGENCY 'ATSI_P1-2_CEI-345-701_SRT-A'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1   /*02AVON       345.0 - 02JUNIPE     345.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-002H_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1          /*02AVON       345.0 - 02JUNIPE     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238551 TO BUS 239725 CKT 1 /*02AVON       345.0 - 02LAKEAVE    345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238551 TO BUS 239725 CKT 1 /*02AVON       345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-018_BDR_A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1          /*02AVON       345.0 - 02JUNIPE     345.0
 DISCONNECT BRANCH FROM BUS 238783 TO BUS 238850 CKT 1          /*02HARDIN     345.0 - 02JUNIPE     345.0
 SET POSTCONTRATING 1289 BRANCH FROM BUS 238850 TO BUS 239122 CKT 1 /*02JUNIPE     345.0 - 02STAR       345.0
 SET POSTCONTRATING 1511 BRANCH FROM BUS 238850 TO BUS 238781 CKT 1 /*02JUNIPE     345.0 - 02HANNA      345.0
 SET PRECONTRATING 1289 BRANCH FROM BUS 238850 TO BUS 239122 CKT 1 /*02JUNIPE     345.0 - 02STAR       345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238850 TO BUS 238781 CKT 1 /*02JUNIPE     345.0 - 02HANNA      345.0
END
CONTINGENCY 'ATSI_P7-1_CEI-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1   /*02AVON       345.0 - 02JUNIPE     345.0
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 239725 CKT 1   /*02AVON       345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-002I_SRT-A'
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 238850 CKT 1   /*02AVON       345.0 - 02JUNIPE     345.0
 DISCONNECT BRANCH FROM BUS 238551 TO BUS 239725 CKT 1   /*02AVON       345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OES-138-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238745 TO BUS 238746 CKT 4          /*02GALION     345.0 - 02GALION     138.0
 DISCONNECT BRANCH FROM BUS 238746 TO BUS 238747 CKT 2          /*02GALION     138.0 - 02GALION      69.0
 SET POSTCONTRATING 417 BRANCH FROM BUS 238745 TO BUS 238746 CKT 3 /*02GALION     345.0 - 02GALION     138.0
 SET PRECONTRATING 328 BRANCH FROM BUS 238745 TO BUS 238746 CKT 3 /*02GALION     345.0 - 02GALION     138.0
END
CONTINGENCY 'ATSI_P2-3_OES-138-018_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238745 TO BUS 238746 CKT 3          /*02GALION     345.0 - 02GALION     138.0
 DISCONNECT BRANCH FROM BUS 238746 TO BUS 238747 CKT 2          /*02GALION     138.0 - 02GALION      69.0
 SET POSTCONTRATING 411 BRANCH FROM BUS 238745 TO BUS 238746 CKT 4 /*02GALION     345.0 - 02GALION     138.0
 SET PRECONTRATING 329 BRANCH FROM BUS 238745 TO BUS 238746 CKT 4 /*02GALION     345.0 - 02GALION     138.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-021_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-007_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 DISCONNECT BUS 238670                                          /*02DVBSG1      25.0
 REMOVE MACHINE 1 FROM BUS 238670                               /*02DVBSG1      25.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-004_SRT-A'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1   /*02BAY SH     345.0 - 02DAV-BE     345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-005_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238654 CKT 1          /*02BAY SH     345.0 - 02DAV-BE     345.0
 REDUCE BUS 238563 SHUNT BY 100 PERCENT                         /*02BAY SH     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1          /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 241877 CKT 1 /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P4_#17249_05FOSTOR 345_A1_SRT-A'
 OPEN BRANCH FROM BUS 238889 TO BUS 242936 CKT 1   /*02LEMOYN     345.0 - 05FOSTOR     345.0
 OPEN BRANCH FROM BUS 241901 TO BUS 242936 CKT 1   /*02LALLENDORF 345.0 - 05FOSTOR     345.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-S'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1   /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1   /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                   /*8LEXINGTN SC 500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#6497_05MARYSV 345_J2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'AEP_P4_#7105_05MELMOR 138_B2_SRT-A'
 OPEN BRANCH FROM BUS 243039 TO BUS 290946 CKT 1   /*05MELMOR     138.0 - 05CHATFLD_BP 138.0
 OPEN BRANCH FROM BUS 244991 TO BUS 290946 CKT 1   /*05HOWARD2    138.0 - 05CHATFLD_BP 138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P4_#10098_05LCKWRD 138_A_SRT-A'
 OPEN BRANCH FROM BUS 239070 TO BUS 243029 CKT 1   /*02RICHLAND_K 138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 242971 TO BUS 243029 CKT 1   /*05BRYAN      138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 243029 TO BUS 243086 CKT 1   /*05LCKWRD     138.0 - 05S HICK     138.0
 OPEN BRANCH FROM BUS 243086 TO BUS 243179 CKT 1   /*05S HICK     138.0 - 05S HICKSV    69.0
 OPEN BRANCH FROM BUS 243086 TO BUS 247108 CKT 1   /*05S HICK     138.0 - 05SOWERS     138.0
 REMOVE SWSHUNT FROM BUS 243029                    /*05LCKWRD     138.0
END
CONTINGENCY 'AEP_P2-2_#5123_05LCKWRD 138_1_SRT-A'
 OPEN BRANCH FROM BUS 239070 TO BUS 243029 CKT 1   /*02RICHLAND_K 138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 242971 TO BUS 243029 CKT 1   /*05BRYAN      138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 243029 TO BUS 243086 CKT 1   /*05LCKWRD     138.0 - 05S HICK     138.0
 REMOVE SWSHUNT FROM BUS 243029                    /*05LCKWRD     138.0
END
CONTINGENCY 'AEP_P4_#5123_05LCKWRD 138_B_SRT-A'
 OPEN BRANCH FROM BUS 239070 TO BUS 243029 CKT 1   /*02RICHLAND_K 138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 242971 TO BUS 243029 CKT 1   /*05BRYAN      138.0 - 05LCKWRD     138.0
 OPEN BRANCH FROM BUS 243029 TO BUS 243086 CKT 1   /*05LCKWRD     138.0 - 05S HICK     138.0
 REMOVE SWSHUNT FROM BUS 243029                    /*05LCKWRD     138.0
END
CONTINGENCY 'AEP_P2-2_#744_05FOSTOR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 242936 TO BUS 243006 CKT 1   /*05FOSTOR     345.0 - 05FOSTOR     138.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-606_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-002_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 238568 CKT 1          /*02BAY SH     345.0 - 02BAYSHO     138.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1          /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238563 TO BUS 972210 CKT 2 /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'PN_P1-1_PN-230-018_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203923   /*AA1-082 G2    23.0
END
CONTINGENCY 'PN_P1-1_PN-230-017_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203922   /*AA1-082 G1    23.0
END
CONTINGENCY 'PN_P2-2_PN-345-1154-W_SRT-A'
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 1 STEP 1           /*26MAINESBURG 345.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 2 STEP 1           /*26MAINESBURG 345.0
END
CONTINGENCY 'AP_P2-2_WP-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 200726 CKT 1   /*01ELKO       230.0 - 26SHAWVL 2   230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235158 CKT 1   /*01ELKO       230.0 - 01CARB       230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235236 CKT 1   /*01ELKO       230.0 - 01QUEHAN     230.0
END
238546 to 241927 ckt 1
238549 to 239108 ckt 1
238563 to 238654 ckt 1
238569 to 238607 ckt 1
238570 to 238845 ckt 1
238569 to 239725 ckt 1
238569 to 239725 ckt 2
238590 to 238728 ckt 1
238654 to 239289 ckt 1
238654 to 241877 ckt 1
238667 to 239073 ckt 1
238740 to 239050 ckt 1
238745 to 238746 ckt 3
238745 to 238746 ckt 4
238768 to 238974 ckt 1
238768 to 238981 ckt 1
239290 to 238549 ckt 1
239289 to 238569 ckt 1
238874 to 238768 ckt 1
241901 to 242936 ckt 1
238889 to 238654 ckt 1
238974 to 238590 ckt 1
238981 to 238570 ckt 1
239738 to 238570 ckt 1
239030 to 238874 ckt 1
239154 to 243009 ckt 1
290984 to 242939 ckt 1
242563 to 242603 ckt 1
242603 to 242613 ckt 1
242613 to 244423 ckt 1
242935 to 242945 ckt 1
243903 to 290984 ckt 1
244423 to 244446 ckt 1
242792 to 938820 ckt 1
244446 to 242792 ckt 1
247319 to 290306 ckt 1
304070 to 316281 ckt 1
270423 to 243024 ckt 1
241877 to 238569 ckt 1
938820 to 314746 ckt 1
270540 to 242993 ckt 1
970214 to 238745 ckt 1
972210 to 238563 ckt 2
130836 to 200676 ckt 1

Winter Peak Analysis

The New Service Request AH1-690 was evaluated as a 1475.0 MW (1440.0 MW Capacity) injection in the ATSI area.

AH1-690 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1475.0 MW (1475.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-690 was evaluated as a 1475.0 MW injection

AH1-690 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1475.0 MW (1475.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC112.05 %1409.0B1578.76647.24
IPDAEP/ATSI
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-021_SRT-A-1
TowerAC101.19 %1409.0B1425.72787.57
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Base Case
SingleAC124.29 %897.0A1114.8935.6
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %1301.0B1455.9953.82
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P1-2_#6497_SRT-A
SingleAC113.95 %971.0B1106.4962.8
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P1-2_#17561_SRT-A
SingleAC108.46 %971.0B1053.163.33
GD2AEP
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Base Case
SingleAC108.04 %897.0A969.1636.79

Details for 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1578.76
MW Contribution:647.24
Bus #Bus NameTypeMW Contribution
241847AF2-150_GEN
Solar/Wind Helper
1.298
270499AE1-146 GEN
Solar/Wind Helper
2.179
972211AH1-690 GEN
50/50
647.237
247522W1-056 GEN
Solar/Wind Helper
0.923
945641AF1-229 GEN
Solar/Wind Helper
3.188
960841AF2-375 GEN
Solar/Wind Helper
2.48
961961AG1-039 GEN
Solar/Wind Helper
0.826
971549AH1-272 GEN
Solar/Wind Harmer
6.162
990142J1224
External Queue
9.852609634399414
991177J1571 G
External Queue
7.456767559051514
991182J1586 G
External Queue
19.340486526489258
NYPJM->LTFIMP_NY
CLTF
0.483
LGEELTFEXP_LGEE->PJM
CLTF
0.159
WECLTFEXP_WEC->PJM
CLTF
0.621
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.208
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.106
LAGNLTFEXP_LAGN->PJM
CLTF
0.835
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.869
TVALTFEXP_TVA->PJM
CLTF
0.231
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
2.112
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for [AH1-690] 02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-021_SRT-A-1


Base Case Flowgate

Area:AEP/ATSI
Facility Description:
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-021_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.19 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1425.72
MW Contribution:787.57
IPD Plant:AH1-690
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
PJM_IPD
787.573

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.29 %
Rating:897.0 MVA
Rating Type:A
MVA to Mitigate:1114.89
MW Contribution:35.6
Bus #Bus NameTypeMW Contribution
24695305TIMB G C
Solar/Wind Harmer
4.652
247607V1-011 GEN
Solar/Wind Harmer
3.66
247521TR3_G114
Solar/Wind Harmer
2.821
270191TR4_S_V150
Solar/Wind Harmer
2.15
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
1.301
270489AE1-102 GEN1
Solar/Wind Harmer
0.845
246936BC-WTG1
Solar/Wind Harmer
5.898
246937BC-WTG2
Solar/Wind Harmer
5.898
246938BC-WTG3
Solar/Wind Harmer
6
241858AF1-205_GEN
Solar/Wind Harmer
1.403
270297AD1-101 GEN
Solar/Wind Harmer
0.136
270258AD1-119 GEN
Solar/Wind Harmer
0.108
270471AD2-092_GEN
Solar/Wind Helper
3.549
270349AD2-093_GEN
Solar/Wind Helper
3.549
270588AE1-091_GEN
Solar/Wind Harmer
7.158
270499AE1-146 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
5.494
270541AE2-072 C
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.002
270466AD2-091
50/50
22.677
270036AE2-216 BAT
50/50
24.945
270475AD2-096_GEN
50/50
Charging
5.478
270578AF1-285 GEN2
Solar/Wind Harmer
5.239
270391AF1-285 GEN3
Solar/Wind Harmer
5.239
270361_3
Solar/Wind Harmer
4.603
270575GUS2 35KV
Solar/Wind Harmer
4.868
270462AD2-086
Solar/Wind Harmer
-0.002
972211AH1-690 GEN
50/50
35.604
247522W1-056 GEN
Solar/Wind Harmer
2.79
270491AE1-102 GEN2
Solar/Wind Harmer
0.845
960851AF2-376 GEN
50/50
3.62
960861AF2-377 GEN
50/50
3.294
966831AG1-554 GEN
Solar/Wind Harmer
0
970583AG2-370 GEN
50/50
3.186
971677AH1-339 GEN
Solar/Wind Harmer
3.419
971989AH1-539 GEN
Solar/Wind Harmer
7.139
971989AH1-539 GEN
Solar/Wind Harmer
3.501
972253AH1-711 GEN
50/50
18.655
270223U2-072_GEN1
Solar/Wind Harmer
11.265
270224U2-072_GEN2
Solar/Wind Harmer
11.265
270227U2-072_GEN3
Solar/Wind Harmer
11.265
270228U2-072_GEN4
Solar/Wind Harmer
11.265
270231U2-072_GEN5
Solar/Wind Harmer
11.265
270246TR4_N_V150
Solar/Wind Harmer
0.714
270247TR4_N_V136
Solar/Wind Harmer
0.714
957201AF2-014 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0.268
958321AF2-126 GEN
Solar/Wind Harmer
0.485
965041AG1-368 GEN
Solar/Wind Harmer
2.219
965051AG1-369 GEN
Solar/Wind Harmer
1.808
965421AG1-410 GEN
Solar/Wind Harmer
18.546
965431AG1-411 GEN
50/50
11.24
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.063
WECLTFEXP_WEC->PJM
CLTF
0.384
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.663
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.386
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.496
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.341
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
1.186
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1455.99
MW Contribution:53.82
Bus #Bus NameTypeMW Contribution
24695305TIMB G C
Solar/Wind Harmer
5.688
247607V1-011 GEN
Solar/Wind Harmer
4.215
247521TR3_G114
Solar/Wind Harmer
3.536
270191TR4_S_V150
Solar/Wind Harmer
2.695
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
1.441
270489AE1-102 GEN1
Solar/Wind Harmer
0.937
246936BC-WTG1
Solar/Wind Harmer
6.536
246937BC-WTG2
Solar/Wind Harmer
6.536
246938BC-WTG3
Solar/Wind Harmer
6.648
270297AD1-101 GEN
Solar/Wind Harmer
0.149
270258AD1-119 GEN
Solar/Wind Harmer
0.128
270471AD2-092_GEN
Solar/Wind Helper
4.05
270349AD2-093_GEN
Solar/Wind Helper
4.05
270588AE1-091_GEN
Solar/Wind Harmer
7.154
270499AE1-146 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
6.326
270541AE2-072 C
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Helper
3.26
270284AF1-227 GEN1
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Helper
1.466
270466AD2-091
50/50
22.432
270036AE2-216 BAT
50/50
24.675
270475AD2-096_GEN
50/50
Charging
6.251
270459AD2-067 GEN
Solar/Wind Helper
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
5.173
270391AF1-285 GEN3
Solar/Wind Harmer
5.173
270361_3
Solar/Wind Harmer
4.666
270575GUS2 35KV
Solar/Wind Harmer
4.935
270462AD2-086
Solar/Wind Harmer
-0.002
972211AH1-690 GEN
50/50
53.824
247522W1-056 GEN
Solar/Wind Harmer
2.788
270491AE1-102 GEN2
Solar/Wind Harmer
0.937
946101AF1-275 GEN
Solar/Wind Helper
0.71
959331AF2-224 GEN
Solar/Wind Harmer
4.13
960851AF2-376 GEN
50/50
4.427
960861AF2-377 GEN
50/50
4.128
966831AG1-554 GEN
Solar/Wind Harmer
0
970153AG2-106 GEN
50/50
Charging
9.794
970155AG2-107 GEN
50/50
Charging
9.794
970583AG2-370 GEN
50/50
4.103
970615AG2-402 GEN
50/50
3.938
971989AH1-539 GEN
Solar/Wind Harmer
7.065
971989AH1-539 GEN
Solar/Wind Harmer
3.465
972253AH1-711 GEN
50/50
19.684
270223U2-072_GEN1
Solar/Wind Harmer
11.122
270224U2-072_GEN2
Solar/Wind Harmer
11.122
270227U2-072_GEN3
Solar/Wind Harmer
11.122
270228U2-072_GEN4
Solar/Wind Harmer
11.122
270231U2-072_GEN5
Solar/Wind Harmer
11.122
270246TR4_N_V150
Solar/Wind Harmer
0.895
270247TR4_N_V136
Solar/Wind Harmer
0.895
957201AF2-014 GEN
Solar/Wind Harmer
0.001
958091AF2-103 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0.309
965041AG1-368 GEN
Solar/Wind Harmer
4.513
965051AG1-369 GEN
Solar/Wind Harmer
2.266
965421AG1-410 GEN
Solar/Wind Harmer
20.793
965431AG1-411 GEN
50/50
12.602
NYPJM->LTFIMP_NY
CLTF
1.051
LGEELTFEXP_LGEE->PJM
CLTF
0.48
WECLTFEXP_WEC->PJM
CLTF
1.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.836
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.469
LAGNLTFEXP_LAGN->PJM
CLTF
0.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.781
TVALTFEXP_TVA->PJM
CLTF
0.104
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
3.645
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.062
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P1-2_#6497_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#6497_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.95 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1106.49
MW Contribution:62.8
Bus #Bus NameTypeMW Contribution
253303V4-073 C
Solar/Wind Helper
0.041
253378AE2-206_GEN
Solar/Wind Helper
4.948
253394AE2-221_GEN
Solar/Wind Helper
2.176
253398AE2-221_GEN2
Solar/Wind Helper
2.176
253383AE2-342_GEN
Solar/Wind Helper
0.78
270302AB2-170 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.749
270489AE1-102 GEN1
Solar/Wind Harmer
1.137
246936BC-WTG1
Solar/Wind Harmer
7.933
246937BC-WTG2
Solar/Wind Harmer
7.933
246938BC-WTG3
Solar/Wind Harmer
8.069
241974AD2-163_GEN2
Solar/Wind Helper
1.293
241973AD2-163_GEN1
Solar/Wind Helper
1.293
241972AD1-140 GEN
Solar/Wind Helper
3.526
241808AF1-120 C
Solar/Wind Harmer
0
241996AE2-282_GEN
Solar/Wind Harmer
0
241858AF1-205_GEN
Solar/Wind Harmer
1.749
270471AD2-092_GEN
Solar/Wind Helper
2.011
270349AD2-093_GEN
Solar/Wind Helper
2.011
270588AE1-091_GEN
Solar/Wind Harmer
6.24
270499AE1-146 GEN
Solar/Wind Harmer
0
270541AE2-072 C
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
8.068
270284AF1-227 GEN1
Solar/Wind Harmer
0.001
270466AD2-091
50/50
13.886
270036AE2-216 BAT
50/50
15.275
270578AF1-285 GEN2
Solar/Wind Harmer
2.776
270391AF1-285 GEN3
Solar/Wind Harmer
2.776
270361_3
Solar/Wind Harmer
5.383
270575GUS2 35KV
Solar/Wind Harmer
5.693
276820AF1-078_GEN
Solar/Wind Helper
2.227
253406AD2-031_GEN
Solar/Wind Helper
0.773
270462AD2-086
Solar/Wind Harmer
-0.001
972211AH1-690 GEN
50/50
62.802
247522W1-056 GEN
Solar/Wind Harmer
2.666
270491AE1-102 GEN2
Solar/Wind Harmer
1.137
945411AF1-206 GEN
Solar/Wind Harmer
8.536
945641AF1-229 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.753
963581AG1-207 GEN
50/50
Charging
7.883
966831AG1-554 GEN
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
3.753
970817AG2-515 GEN
Solar/Wind Harmer
4.433
971677AH1-339 GEN
Solar/Wind Harmer
3.957
971989AH1-539 GEN
Solar/Wind Harmer
6.421
971989AH1-539 GEN
Solar/Wind Harmer
3.149
972253AH1-711 GEN
50/50
24.832
270223U2-072_GEN1
Solar/Wind Harmer
5.968
270224U2-072_GEN2
Solar/Wind Harmer
5.968
270227U2-072_GEN3
Solar/Wind Harmer
5.968
270228U2-072_GEN4
Solar/Wind Harmer
5.968
270231U2-072_GEN5
Solar/Wind Harmer
5.968
957201AF2-014 GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.541
965011AG1-365 GEN
Solar/Wind Harmer
3.753
965021AG1-366 GEN
Solar/Wind Harmer
0.536
965421AG1-410 GEN
Solar/Wind Harmer
24.806
965431AG1-411 GEN
50/50
15.034
NYPJM->LTFIMP_NY
CLTF
0.286
WECLTFEXP_WEC->PJM
CLTF
0.319
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.756
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.472
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.798
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.119
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.803
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.582
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P1-2_#17561_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17561_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.46 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1053.1
MW Contribution:63.33
Bus #Bus NameTypeMW Contribution
253303V4-073 C
Solar/Wind Helper
0.041
253378AE2-206_GEN
Solar/Wind Helper
4.927
253394AE2-221_GEN
Solar/Wind Helper
2.149
253398AE2-221_GEN2
Solar/Wind Helper
2.149
253383AE2-342_GEN
Solar/Wind Helper
0.773
270302AB2-170 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.757
270489AE1-102 GEN1
Solar/Wind Harmer
1.142
246936BC-WTG1
Solar/Wind Harmer
7.967
246937BC-WTG2
Solar/Wind Harmer
7.967
246938BC-WTG3
Solar/Wind Harmer
8.104
241974AD2-163_GEN2
Solar/Wind Helper
1.277
241973AD2-163_GEN1
Solar/Wind Helper
1.277
241972AD1-140 GEN
Solar/Wind Helper
3.49
241808AF1-120 C
Solar/Wind Harmer
0
241996AE2-282_GEN
Solar/Wind Harmer
0
241858AF1-205_GEN
Solar/Wind Harmer
1.764
270471AD2-092_GEN
Solar/Wind Helper
1.989
270349AD2-093_GEN
Solar/Wind Helper
1.989
270588AE1-091_GEN
Solar/Wind Harmer
6.281
270499AE1-146 GEN
Solar/Wind Harmer
0
270541AE2-072 C
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
7.961
270284AF1-227 GEN1
Solar/Wind Helper
3.085
270286AF1-227 GEN2
Solar/Wind Helper
1.139
270287AF1-227 GEN3
Solar/Wind Helper
1.139
270466AD2-091
50/50
13.92
270036AE2-216 BAT
50/50
15.312
270578AF1-285 GEN2
Solar/Wind Harmer
2.783
270391AF1-285 GEN3
Solar/Wind Harmer
2.783
270361_3
Solar/Wind Harmer
5.419
270575GUS2 35KV
Solar/Wind Harmer
5.732
276820AF1-078_GEN
Solar/Wind Helper
2.218
253406AD2-031_GEN
Solar/Wind Helper
0.763
270462AD2-086
Solar/Wind Harmer
-0.001
972211AH1-690 GEN
50/50
63.33
247522W1-056 GEN
Solar/Wind Harmer
2.686
270491AE1-102 GEN2
Solar/Wind Harmer
1.142
945411AF1-206 GEN
Solar/Wind Harmer
8.61
945641AF1-229 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.791
963581AG1-207 GEN
50/50
Charging
7.825
966831AG1-554 GEN
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
3.791
970817AG2-515 GEN
Solar/Wind Harmer
4.471
971677AH1-339 GEN
Solar/Wind Harmer
3.987
971989AH1-539 GEN
Solar/Wind Harmer
6.47
971989AH1-539 GEN
Solar/Wind Harmer
3.172
972253AH1-711 GEN
50/50
25.032
270223U2-072_GEN1
Solar/Wind Harmer
5.983
270224U2-072_GEN2
Solar/Wind Harmer
5.983
270227U2-072_GEN3
Solar/Wind Harmer
5.983
270228U2-072_GEN4
Solar/Wind Harmer
5.983
270231U2-072_GEN5
Solar/Wind Harmer
5.983
957201AF2-014 GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.545
965011AG1-365 GEN
Solar/Wind Harmer
3.791
965021AG1-366 GEN
Solar/Wind Harmer
0.541
965421AG1-410 GEN
Solar/Wind Harmer
24.919
965431AG1-411 GEN
50/50
15.102
NYPJM->LTFIMP_NY
CLTF
0.248
WECLTFEXP_WEC->PJM
CLTF
0.341
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.716
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.448
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.621
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.988
BlueGrassPJM->LTFIMP_BlueG
CLTF
3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.665
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.681
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:897.0 MVA
Rating Type:A
MVA to Mitigate:969.16
MW Contribution:36.79
Bus #Bus NameTypeMW Contribution
24695305TIMB G C
Solar/Wind Harmer
4.782
247607V1-011 GEN
Solar/Wind Harmer
3.747
247521TR3_G114
Solar/Wind Harmer
2.908
270191TR4_S_V150
Solar/Wind Harmer
2.216
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
1.323
270489AE1-102 GEN1
Solar/Wind Harmer
0.86
246936BC-WTG1
Solar/Wind Harmer
5.999
246937BC-WTG2
Solar/Wind Harmer
5.999
246938BC-WTG3
Solar/Wind Harmer
6.102
241858AF1-205_GEN
Solar/Wind Harmer
1.448
270297AD1-101 GEN
Solar/Wind Harmer
0.139
270258AD1-119 GEN
Solar/Wind Harmer
0.111
270471AD2-092_GEN
Solar/Wind Helper
3.484
270349AD2-093_GEN
Solar/Wind Helper
3.484
270588AE1-091_GEN
Solar/Wind Harmer
7.28
270499AE1-146 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
5.624
270541AE2-072 C
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
12.536
270286AF1-227 GEN2
Solar/Wind Helper
4.626
270287AF1-227 GEN3
Solar/Wind Helper
4.626
270466AD2-091
50/50
22.778
270036AE2-216 BAT
50/50
25.056
270475AD2-096_GEN
50/50
Charging
5.377
270578AF1-285 GEN2
Solar/Wind Harmer
5.26
270391AF1-285 GEN3
Solar/Wind Harmer
5.26
270361_3
Solar/Wind Harmer
4.711
270575GUS2 35KV
Solar/Wind Harmer
4.983
270462AD2-086
Solar/Wind Harmer
-0.002
972211AH1-690 GEN
50/50
36.787
247522W1-056 GEN
Solar/Wind Harmer
2.848
270491AE1-102 GEN2
Solar/Wind Harmer
0.86
960851AF2-376 GEN
50/50
3.721
960861AF2-377 GEN
50/50
3.395
966831AG1-554 GEN
Solar/Wind Harmer
0
970583AG2-370 GEN
50/50
3.287
971677AH1-339 GEN
Solar/Wind Harmer
3.508
971989AH1-539 GEN
Solar/Wind Harmer
7.283
971989AH1-539 GEN
Solar/Wind Harmer
3.571
972253AH1-711 GEN
50/50
19.246
270223U2-072_GEN1
Solar/Wind Harmer
11.308
270224U2-072_GEN2
Solar/Wind Harmer
11.308
270227U2-072_GEN3
Solar/Wind Harmer
11.308
270228U2-072_GEN4
Solar/Wind Harmer
11.308
270231U2-072_GEN5
Solar/Wind Harmer
11.308
270246TR4_N_V150
Solar/Wind Harmer
0.736
270247TR4_N_V136
Solar/Wind Harmer
0.736
957201AF2-014 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0.275
958321AF2-126 GEN
Solar/Wind Harmer
0.498
965041AG1-368 GEN
Solar/Wind Harmer
2.29
965051AG1-369 GEN
Solar/Wind Harmer
1.863
965421AG1-410 GEN
Solar/Wind Harmer
18.879
965431AG1-411 GEN
50/50
11.442
NYPJM->LTFIMP_NY
CLTF
0.514
LGEELTFEXP_LGEE->PJM
CLTF
0.183
WECLTFEXP_WEC->PJM
CLTF
0.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.546
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.316
LAGNLTFEXP_LAGN->PJM
CLTF
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.688
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
1.479
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CONTINGENCY 'ATSI_P7-1_TE-345-021_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 1   /*02BAY SH     345.0 - AH1-690 TP   345.0
 DISCONNECT BRANCH FROM BUS 238563 TO BUS 972210 CKT 2   /*02BAY SH     345.0 - AH1-690 TP   345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#6497_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P1-2_#17561_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
241901 to 242936 ckt 1
290984 to 242939 ckt 1
242935 to 242945 ckt 1
243903 to 290984 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-050Tarboro-Everetts 230kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-111Aurora 138kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-161Septa 500kVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-044Maddox Creek 345kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-119Payne 69 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-079Capitol Ave 34.5kVIn Service
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-100Axton 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-253Hickory-Moyock 230 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-296Garden Plain 138 kVActive
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-107Clifford 138 kVEngineering & Procurement
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-150Galion 138 kVUnder Construction
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-127Crego Rd 138 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-207Vandalia 69 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-494Boxwood-Riverville 138 kVActive
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-149Galion-South Berwick 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-272Berry Hill 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-370Tillman 138 kVActive
AG2-400Allen 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-069Jerome – Mohicanville 69 kVActive
AH1-070Jerome – Mohicanville 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-680Sammis - South Canton 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-072East Lima-Marysville 345kVIn Service
V1-011Haviland 138kVIn Service
V4-073Yankee 12.5kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYISO_CY17_13387
Title
East Sayre-North Waverly 115kV line upgrade - NYSEG (NYISO CY17 driven upgrade)
Description
North Waverly terminal equipment upgrades and a line reconductor of the NYSEG portion of the East Sayre – North Waverly 115kV line. (Install approximately twenty-six (26) new steel pole structures, one (1) 795 kcmil (26/7) ACSR conductor, and 36 Fiber OPGW). Final expected SUM ratings with both NYSEG & Penelec work complete = 218/251 MVA SN/SE. NYSEG uses LTE for Rate B, not STE like FirstEnergy. The earliest projected in-service date for this project is in 2026, but that timeframe may shift to complete the terminal equipment work at North Waverly. The final trip setting for the line will be updated during engineering and construction, but it must meet at least 176 MVA. Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal needs to be upgraded since it is limiting. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$10,525,000
Allocated Cost ($USD)
$0
Time Estimate
32 Months

Info

Note: AH1-690 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AH1-690 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-690 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
ATSI(Pending) / TC2-ATSI-006.aReconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line$128,073,552
ATSI(Pending) / TC2-ATSI-014.aReconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line$122,797,286
ATSI(Pending) / TC2-ATSI-020.dReconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line$106,455,624
ATSI(Pending) / TC2-ATSI-002.dReconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends$89,885,811
ATSI(Pending) / TC2-ATSI-004.cReconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV$85,440,891
ATSI(Pending) / TC2-ATSI-008.fReconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV$82,891,012
ATSI(Pending) / TC2-ATSI-015.aReconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV$68,126,768
ATSI(Pending) / TC2-ATSI-008.cReconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line$68,030,782
AEP(Pending) / AEP-TC2-1870005GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild$43,588,025
ATSI(Pending) / TC2-ATSI-003Reconductor (possible rebuild) 12.19 miles of transmission line on the Beaver- Johnson Ckt 1 138kV$42,140,488
AEP(Pending) / AEP-TC2-1868105E LIMA 345.0 kV to 05SW LIM 345.0 kV ckt 1 - Rebuild$40,254,475
AEP(Pending) / AEP-TC2-1864705JAMES RIVR 138.0 kV to 05SOAPSTONE 138.0 kV ckt 1 - Rebuild$40,000,000
AEP(Pending) / AEP-TC2-1867105SOAPSTONE 138.0 kV to 05SCOTSV 138.0 kV ckt 1 - Rebuild$40,000,000
ATSI(Pending) / TC2-ATSI-005.dReconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV$39,274,455
ATSIn9227.0 / TC1-ATSI-001.bUpgrade T-line drops, overhead substation conductor and TL reconductor$35,718,003
ATSI(Pending) / TC2-ATSI-016.cReconductor (possible rebuild) 10.46 miles of transmission line on the Ottawa-Lakeview 138 kV Q-121 line$30,769,431
AEP(Pending) / AEP-TC2-1863005BOXWD 138.0 kV to 05CLIFFR 138.0 kV ckt 1 - Rebuild$21,800,000
AEP(Pending) / AEP-TC2-1863605COLLEEN SS 138.0 kV to 05JAMES RIVR 138.0 kV ckt 1 - Rebuild$18,000,000
AEP(Pending) / AEP-TC2-1866505CLIFFR 138.0 kV to 05COLLEEN SS 138.0 kV ckt 1 - Rebuild$14,700,000
AEPn6525.3 / AEPO0026fRebuild 7 miles of 138 kV line between Fremont Center and First Energy's We [...] fact that they own a portion of the line conductor that limits the branch.$10,781,492
ATSI(Pending) / TC2-ATSI-001Reconductor (possible rebuild) 1.98 miles of 795 ACSR 36/1 transmission line and 795 ACSR 36/1 line drops on the Avon-Astor T11 Ckt Q11 138 kV line$7,382,665
ATSI(Pending) / TC2-ATSI-002.gUpgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse$5,756,196
ATSI(Pending) / TC2-ATSI-021.aUpgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)$5,690,758
ATSI(Pending) / TC2-ATSI-014.dUpgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)$5,541,172
AEP(Pending) / AEP-TC2-1873305BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor$4,507,618
AEP(Pending) / AEP-TC2-1870205SCOTSV 138.0 kV to AE1-108 POI 138.0 kV ckt 1 - Rebuild$3,800,000
ATSI(Pending) / TC2-ATSI-015.cUpgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne$3,403,380
ATSIn6511Reconductor the 0.8 miles of transmission line between West Fremont-Fremont [...] section of limiting conductor and provide estimates for their replacement.$3,347,779
ATSI(Pending) / TC2-ATSI-006.jUpgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)$3,221,706
ATSI(Pending) / TC2-ATSI-021.hUpgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)$2,814,238
ATSI(Pending) / TC2-ATSI-002.mUpgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse$2,809,622
ATSI(Pending) / TC2-ATSI-006.gUpgrade B66 and B67 circuit breakers at Davis Besse substation$2,771,525
ATSI(Pending) / TC2-ATSI-006.dUpgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes$2,771,525
ATSI(Pending) / TC2-ATSI-014.kUpgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)$2,768,527
ATSI(Pending) / TC2-ATSI-020.aUpgrade B185 and B182 circuit breakers at Beaver$2,748,721
ATSI(Pending) / TC2-ATSI-015.iUpgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)$2,256,287
ATSI(Pending) / TC2-ATSI-021.kUpgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave$1,974,100
ATSI(Pending) / TC2-ATSI-008.hUpgrade Circuit Breaker 34564 at Davis Besse$1,533,593
ATSI(Pending) / TC2-ATSI-008.lUpgrade Circuit Breaker B65 at Davis Besse$1,533,593
ATSI(Pending) / TC2-ATSI-015.gUpgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse$1,220,083
ATSI(Pending) / TC2-ATSI-020.bUpgrade (4) disconnect switches at Beaver (D186,184,181,183)$1,211,059
ATSI(Pending) / TC2-ATSI-015.dUpgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne$1,182,159
ATSI(Pending) / TC2-ATSI-015.fUpgrade the B34502 CB at Lemoyne$1,180,945
ATSI(Pending) / TC2-ATSI-005.aUpgrade (3) disconnect switches at Beaver (D:120,166,165)$1,056,291
ATSI(Pending) / TC2-ATSI-002.bUpgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse$978,827
ATSI(Pending) / TC2-ATSI-017Upgrade (2) 2000A bus and line side disconnect switches at Bayshore$948,616
ATSI(Pending) / TC2-ATSI-002.fUpgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse$898,671
ATSI(Pending) / TC2-ATSI-020.gUpgrade (2) B185 and B182 revenue meter CTs at Beaver$896,798
ATSI(Pending) / TC2-ATSI-006.eUpgrade (2) B12 and B18 CTs at Hayes$895,933
ATSI(Pending) / TC2-ATSI-014.hUpgrade the B88 and B115 CTs at Beaver$878,624
ATSI(Pending) / TC2-ATSI-006.cUpgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes$865,394
ATSI(Pending) / TC2-ATSI-002.aUpgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse$812,704
ATSI(Pending) / TC2-ATSI-002.kUpgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse$738,363
ATSI(Pending) / TC2-ATSI-004.aUpgrade D120 and D125 disconnect switches at Beaver substation$727,201
ATSI(Pending) / TC2-ATSI-006.iUpgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse$725,939
ATSI(Pending) / TC2-ATSI-008.aUpgrade D41 and D42 disconnect switches at Davis Besse$717,344
ATSI(Pending) / TC2-ATSI-014.jUpgrade the B88 and B3 impedance relays at Beaver and Hayes$711,914
ATSI(Pending) / TC2-ATSI-006.kUpgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes$637,420
ATSI(Pending) / TC2-ATSI-005.bUpgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation$635,147
ATSI(Pending) / TC2-ATSI-021.cUpgrade the (3) B216, B219 and B4 1500 CTs$624,011
ATSI(Pending) / TC2-ATSI-015.bUpgrade (4) L300 wavetraps at Davis Besse and Lemoyne$611,784
ATSI(Pending) / TC2-ATSI-006.hUpgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation$606,826
ATSI(Pending) / TC2-ATSI-010Upgrade 4/0 CU sub conductor at FOWLES substation$591,862
ATSI(Pending) / TC2-ATSI-015.eUpgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne$582,117
ATSI(Pending) / TC2-ATSI-008.iUpgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse$560,559
ATSI(Pending) / TC2-ATSI-015.hUpgrade (12) 4.00 SPS.AL PIPE at Lemoyne$548,730
ATSI(Pending) / TC2-ATSI-016.bUpgrade the standalone CT at Ottawa$537,901
ATSI(Pending) / TC2-ATSI-002.iUpgrade B34544 CT at BAYSHORE$526,591
ATSI(Pending) / TC2-ATSI-014.cUpgrade (2) L3000 wavetraps at Beaver and Hayes$509,000
ATSI(Pending) / TC2-ATSI-014.fUpgrade the B6 CT at Hayes$507,727
ATSI(Pending) / TC2-ATSI-021.dUpgrade (3) 1590 line drops at Beaver and Lake Ave$504,767
ATSI(Pending) / TC2-ATSI-008.gUpgrade (2) Wave Traps at Davis Besse$460,035
ATSI(Pending) / TC2-ATSI-020.eUpgrade (2) L3000 wavetraps at Beaver$438,140
ATSI(Pending) / TC2-ATSI-023.aUpgrade (2) line drop strands, one into Greenfield and one into Lakeview$421,055
ATSI(Pending) / TC2-ATSI-016.aUpgrade (1) line drop into Lakeview and (1) line drop into Ottawa$421,055
ATSI(Pending) / TC2-ATSI-014.gUpgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)$413,179
ATSI(Pending) / TC2-ATSI.023.bUpgrade the B242 relay thermal$407,901
ATSI(Pending) / TC2-ATSI-008.mUpgrade (2) B65 Meter Thermals at Davis Besse$377,973
ATSI(Pending) / TC2-ATSI-008.jUpgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse$377,973
ATSI(Pending) / TC2-ATSI-008.kUpgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse$377,973
ATSI(Pending) / TC2-ATSI-021.fUpgrade the (1) B216 relay thermal at Beaver$372,642
ATSI(Pending) / TC2-ATSI-021.iUpgrade the (2) B3 SEL411L impedance relays at Lake Ave$372,642
ATSI(Pending) / TC2-ATSI-021.lUpgrade the (2) B216 SEL411L impedance relays at Lake Ave$372,642
ATSI(Pending) / TC2-ATSI-020.iUpgrade B182 relay thermal at Beaver$363,320
ATSI(Pending) / TC2-ATSI-020.fUpgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)$363,320
ATSI(Pending) / TC2-ATSI-020.jUpgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)$363,320
ATSI(Pending) / TC2-ATSI-014.iUpgrade the 10A B115 relay and B88 meter thermal at Beaver$355,957
AEPn6525.2 / AEPO0026dReplace three Sub Cond 1590 AAC 61 Str at Fremont$308,043
ATSI(Pending) / TC2-ATSI-019Upgrade phase 2 wave trap at Galion$291,889
ATSI(Pending) / TC2-ATSI-002.jUpgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse$291,159
ATSI(Pending) / TC2-ATSI-016.dUpgrade 795 ACSR B6 and B145 breaker leads and shared and (2) shared node subconductors at Lakeview$269,825
ATSI(Pending) / TC2-ATSI-021.eUpgrade the (1) B219 1200 CT to PVD at Beaver$255,752
ATSI(Pending) / TC2-ATSI-020.hUpgrade the B185 CT to PVD at Beaver$249,354
ATSI(Pending) / TC2-ATSI-021.bUpgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave$223,295
ATSI(Pending) / TC2-ATSI-006.fUpgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes$217,221
ATSI(Pending) / TC2-ATSI-004.dUpgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver$207,485
ATSI(Pending) / TC2-ATSI-004.bUpgrade (1) 3000 SAC 169 line drop at Beaver$205,889
AEPn9674.0 / AEPO0026bReplace 1200 A Switch at Fremont$205,362
ATSI(Pending) / TC2-ATSI-006.bUpgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes$202,209
ATSI(Pending) / TC2-ATSI-002.lUpgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line$195,449
ATSI(Pending) / TC2-ATSI-008.dUpgrade (2) 3500 SAC 127 line drops at Davis Besse$195,081
ATSI(Pending) / TC2-ATSI-008.bUpgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse$195,081
ATSI(Pending) / TC2-ATSI-002.cUpgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse$190,544
ATSI(Pending) / TC2-ATSI-002.eUpgrade 345kV 3500 SAC 127 sub conductor at Davis Besse$190,544
ATSI(Pending) / TC2-ATSI-021.mUpgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver$182,734
ATSI(Pending) / TC2-ATSI.023.cUpgrade the (2) B96 and (2) B7 breaker leads at Lakeview and the (1) B242 to D241 lead at Greenfield$175,138
ATSI(Pending) / TC2-ATSI-002.hUpgrade (8) 1590 AAC 61 sub conductor at BAYSHORE$156,064
ATSI(Pending) / TC2-ATSI-005cUpgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver$149,954
ATSI(Pending) / TC2-ATSI-008.eUpgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse$146,470
ATSI(Pending) / TC2-ATSI-020.cUpgrade 3000 AAC B185 and B185 breaker leads at Beaver$133,565
ATSI(Pending) / TC2-ATSI-021.gUpgrade (1) 4.00 SPS.AL PIPE at Beaver$130,151
AEPn9669.0 / AEPO0027eReplace Sub cond 397.5 ACSR 26/7 at Howard$130,000
ATSI(Pending) / TC2-ATSI-021.jUpgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver$126,718
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$123,688
AEPn9675.0 / AEPO0035aSag Study will be required on ACSR ~ 954 ~ 45/7, 18.3 miles line between South Berwick and Galion .$107,857
ATSI(Pending) / TC2-ATSI-014.bUpgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes$106,511
ATSI(Pending) / TC2-ATSI-014.eUpgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver$106,511
AEP(Pending) / AEP-TC2-1873105WOLFCK 138kV to 05W.WATERT 138kV ckt 1 - Replace Equipment$100,000
AEPn9676.0 / AEPO0033aSag Study will be required on 19.2 miles line between Fostoria and Lallen [...] tudy : S/N: 1409MVA S/E: 1887MVA.Rebuild/Reconductor, cost : $ 38.4 million$99,840
AEP(Pending) / AEPAPRJV002Perform sag study on 397 ACSR between Clifford and Boxwood (13.7 miles)$82,200
AEPn8383A sag study will be required on the 3.65 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation$78,000
AEPn8386A sag study will be required on the ~4.0 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation$78,000
AEP(Pending) / AEPAPRJV006_2Sag Study 397 ACSR between James River and Soapstone ~10 miles$60,000
Grand Total:$1,232,419,117

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.a
Title
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line
Description
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$179,916,169
Allocated Cost ($USD)
$128,073,552
Time Estimate
90 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$9,354,606
AG2-165
8.1 MW1.9%$3,373,039
AG2-212
8.1 MW1.9%$3,373,039
AG2-328
8.1 MW1.9%$3,373,039
AG2-660
1.0 MW0.2%$427,374
AH1-044
6.1 MW1.4%$2,563,827
AH1-150
6.1 MW1.4%$2,563,827
AH1-151
6.1 MW1.4%$2,563,827
AH1-690
306.6 MW71.2%$128,073,552
AH1-711
58.0 MW13.5%$24,250,037

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$122,797,286
Time Estimate
90 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$10,237,972
AG2-165
8.3 MW2.0%$3,519,183
AG2-212
8.3 MW2.0%$3,519,183
AG2-328
8.3 MW2.0%$3,519,183
AG2-660
1.0 MW0.3%$446,130
AH1-044
6.3 MW1.5%$2,675,499
AH1-150
6.3 MW1.5%$2,675,499
AH1-151
6.3 MW1.5%$2,675,499
AH1-690
288.2 MW69.8%$122,797,286
AH1-711
55.9 MW13.6%$23,837,042

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$106,455,624
Time Estimate
82 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$5,835,961
AG2-149
22.1 MW5.4%$8,125,408
AG2-165
7.9 MW1.9%$2,891,547
AG2-212
7.9 MW1.9%$2,891,547
AG2-328
7.9 MW1.9%$2,891,547
AH1-690
290.0 MW71.3%$106,455,624
AH1-711
55.3 MW13.6%$20,311,685

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$89,885,811
Time Estimate
71 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$3,726,804
AG2-149
24.2 MW4.0%$4,914,548
AG2-165
9.0 MW1.5%$1,840,616
AG2-212
9.0 MW1.5%$1,840,616
AG2-328
9.0 MW1.5%$1,840,616
AG2-363
10.7 MW1.8%$2,168,781
AG2-364
7.1 MW1.2%$1,445,922
AG2-660
1.2 MW0.2%$241,903
AH1-044
7.1 MW1.2%$1,451,212
AH1-150
7.1 MW1.2%$1,451,212
AH1-151
7.1 MW1.2%$1,451,212
AH1-690
441.8 MW73.9%$89,885,811
AH1-711
45.9 MW7.7%$9,335,525

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.c
Title
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV
Description
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV using dual (2) 795 26/7 "Drake ACSS
Total Cost ($USD)
$109,211,408
Allocated Cost ($USD)
$85,440,891
Time Estimate
63 Months

Contributor

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.6 MW7.4%$8,091,541
AH1-690
238.1 MW78.2%$85,440,891
AH1-711
43.7 MW14.4%$15,678,976

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$82,891,012
Time Estimate
64 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$6,337,596
AG2-165
7.9 MW2.0%$2,258,920
AG2-212
7.9 MW2.0%$2,258,920
AG2-328
7.9 MW2.0%$2,258,920
AH1-690
290.3 MW74.1%$82,891,012
AH1-711
55.4 MW14.1%$15,816,720

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$68,126,768
Time Estimate
73 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.5%$5,726,959
AG2-149
26.0 MW6.1%$7,692,075
AG2-165
9.2 MW2.2%$2,716,066
AG2-212
9.2 MW2.2%$2,716,066
AG2-328
9.2 MW2.2%$2,716,066
AG2-515
20.4 MW4.8%$6,022,672
AG2-660
1.2 MW0.3%$356,864
AH1-044
7.3 MW1.7%$2,142,071
AH1-150
7.3 MW1.7%$2,142,071
AH1-151
7.3 MW1.7%$2,142,071
AH1-690
230.6 MW54.0%$68,126,768
AH1-711
80.0 MW18.7%$23,632,200

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$68,030,782
Time Estimate
57 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$5,201,428
AG2-165
7.9 MW2.0%$1,853,953
AG2-212
7.9 MW2.0%$1,853,953
AG2-328
7.9 MW2.0%$1,853,953
AH1-690
290.3 MW74.1%$68,030,782
AH1-711
55.4 MW14.1%$12,981,188

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18700
Title
05GUNN RD SW 345.0 kV to 05BOKESCRK 345.0 kV ckt 1- Rebuild
Description
AEP owned line, 16.54 miles of 345kV single circuit with PE conductor (1-1275 ACSR/PE 54/19) needs to be rebuilt
Total Cost ($USD)
$66,000,000
Allocated Cost ($USD)
$43,588,025
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05GUNN RD SW-05BOKESCRK 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.7 MW11.7%$7,690,422
AH1-539
10.9 MW8.0%$5,308,563
AH1-690
89.1 MW66.0%$43,588,025
AH1-711
19.2 MW14.3%$9,412,990

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-003
Title
Reconductor (possible rebuild) 12.19 miles of transmission line on the Beaver- Johnson Ckt 1 138kV
Description
Reconductor (possible rebuild) 12.19 miles of transmission line on the Beaver- Johnson Ckt 1 138kV using single (1) 1272 45/7 "Bittern" ACSR
Total Cost ($USD)
$42,140,488
Allocated Cost ($USD)
$42,140,488
Time Estimate
27 Months

Contributor

FacilityContingency
02BEAVER-02JONSON 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
41.5 MW100.0%$42,140,488

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18681
Title
05E LIMA 345.0 kV to 05SW LIM 345.0 kV ckt 1 - Rebuild
Description
AEP owned line, ~14.66 miles (total 21.97 miles) of 345kV single circuit needs to be rebuilt. Existing conductor is 1-1414 ACSR/PE 62/19 & 1-1708.8 ACSR/AE 66/19
Total Cost ($USD)
$58,640,000
Allocated Cost ($USD)
$40,254,475
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05E LIMA-05SW LIM 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
17.4 MW10.4%$6,072,657
AH1-539
10.5 MW6.2%$3,662,823
AH1-690
115.6 MW68.6%$40,254,475
AH1-711
24.8 MW14.8%$8,650,044

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18647
Title
05JAMES RIVR 138.0 kV to 05SOAPSTONE 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~10 miles of 138 kV line between James River and Soapstone
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$40,000,000
Time Estimate
24 to 48 Months

Contributor

FacilityContingency
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$40,000,000

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18671
Title
05SOAPSTONE 138.0 kV to 05SCOTSV 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~10.2 miles of 138 kV line between Soapstone and Scottsville
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$40,000,000
Time Estimate
32 to 48 Months

Contributor

FacilityContingency
05SCOTSV-05SOAPSTONE 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$40,000,000

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.d
Title
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV
Description
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$50,053,445
Allocated Cost ($USD)
$39,274,455
Time Estimate
38 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
19.4 MW7.2%$3,585,590
AH1-690
212.1 MW78.5%$39,274,455
AH1-711
38.8 MW14.4%$7,193,400

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt 2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$35,718,003
Time Estimate
37 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$3,393,878
AG2-165
8.9 MW2.2%$1,069,072
AG2-212
8.9 MW2.2%$1,069,072
AG2-328
8.9 MW2.2%$1,069,072
AH1-690
297.6 MW73.1%$35,718,003
AH1-711
54.6 MW13.4%$6,554,759

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-016.c
Title
Reconductor (possible rebuild) 10.46 miles of transmission line on the Ottawa-Lakeview 138 kV Q-121 line
Description
Reconductor (possible rebuild) 10.46 miles of transmission line on the Ottawa-Lakeview 138 kV Q-121 line
Total Cost ($USD)
$38,463,247
Allocated Cost ($USD)
$30,769,431
Time Estimate
25 Months

Contributor

FacilityContingency
02LAKVEW-02OTTAWA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$1,860,168
AH1-690
89.7 MW80.0%$30,769,431
AH1-711
17.0 MW15.2%$5,833,648

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18630
Title
05BOXWD 138.0 kV to 05CLIFFR 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~5.3 miles of 138 kV line between Boxwood (specifically Structure 265-1) and Clifford (line is 1949 vintage); Replace 795 AAC station conductor at Boxwood; Replace 795 AAC station conductor at Clifford
Total Cost ($USD)
$21,800,000
Allocated Cost ($USD)
$21,800,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$21,800,000

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18636
Title
05COLLEEN SS 138.0 kV to 05JAMES RIVR 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~4.5 miles of 138 kV line between Colleen and James River
Total Cost ($USD)
$18,000,000
Allocated Cost ($USD)
$18,000,000
Time Estimate
24 to 48 Months

Contributor

FacilityContingency
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$18,000,000

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18665
Title
05CLIFFR 138.0 kV to 05COLLEEN SS 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~3.6 miles of 138 kV line between Clifford and Colleen (line is 1949 vintage); Replace 795 AAC station conductor at Clifford
Total Cost ($USD)
$14,700,000
Allocated Cost ($USD)
$14,700,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$14,700,000

System Reinforcement: n6525.3
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6525.3 / AEPO0026f
Title
Rebuild 7 miles of 138 kV line between Fremont Center and First Energy's We [...] fact that they own a portion of the line conductor that limits the branch.
Description
Rebuild 7 miles of 138 kV line between Fremont Center and First Energy's West Fremont station with a bundled 795 ACSR conductor (Replacing ACSR ~ 1033.5 ~ 45/7 ~ ORTOLAN conductor). First Energy will need to be consulted due to the fact that they own a portion of the line conductor that limits the branch.
Total Cost ($USD)
$13,650,000
Allocated Cost ($USD)
$10,781,492
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
02W.FREM-05FRMNT 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
6.0 MW4.8%$659,940
AH1-690
97.6 MW79.0%$10,781,492
AH1-711
20.0 MW16.2%$2,208,568

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-001
Title
Reconductor (possible rebuild) 1.98 miles of 795 ACSR 36/1 transmission line and 795 ACSR 36/1 line drops on the Avon-Astor T11 Ckt Q11 138 kV line
Description
Reconductor (possible rebuild) 1.98 miles of 795 ACSR 36/1 transmission line and 795 ACSR 36/1 line drops on the Avon-Astor T11 Ckt Q11 138 kV line using single (1) 1590 45/7 "Lapwing" ACSR
Total Cost ($USD)
$7,382,665
Allocated Cost ($USD)
$7,382,665
Time Estimate
18 Months

Contributor

FacilityContingency
02ASQ-11-02AVQ1 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
45.2 MW100.0%$7,382,665

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$5,756,196
Time Estimate
60 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$238,661
AG2-149
24.2 MW4.0%$314,723
AG2-165
9.0 MW1.5%$117,871
AG2-212
9.0 MW1.5%$117,871
AG2-328
9.0 MW1.5%$117,871
AG2-363
10.7 MW1.8%$138,887
AG2-364
7.1 MW1.2%$92,595
AG2-660
1.2 MW0.2%$15,491
AH1-044
7.1 MW1.2%$92,934
AH1-150
7.1 MW1.2%$92,934
AH1-151
7.1 MW1.2%$92,934
AH1-690
441.8 MW73.9%$5,756,196
AH1-711
45.9 MW7.7%$597,838

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.a
Title
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Description
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Total Cost ($USD)
$7,786,809
Allocated Cost ($USD)
$5,690,758
Time Estimate
56 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$540,728
AG2-165
8.9 MW2.2%$170,330
AG2-212
8.9 MW2.2%$170,330
AG2-328
8.9 MW2.2%$170,330
AH1-690
297.6 MW73.1%$5,690,758
AH1-711
54.6 MW13.4%$1,044,335

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$5,541,172
Time Estimate
60 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$461,984
AG2-165
8.3 MW2.0%$158,802
AG2-212
8.3 MW2.0%$158,802
AG2-328
8.3 MW2.0%$158,802
AG2-660
1.0 MW0.3%$20,131
AH1-044
6.3 MW1.5%$120,731
AH1-150
6.3 MW1.5%$120,731
AH1-151
6.3 MW1.5%$120,731
AH1-690
288.2 MW69.8%$5,541,172
AH1-711
55.9 MW13.6%$1,075,636

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18733
Title
05BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor
Description
Reconductor line between Marysville - Boke Creek 345 kV due to paper expanded line. New line will be 2-954 ACSR RAIL
Total Cost ($USD)
$6,810,000
Allocated Cost ($USD)
$4,507,618
Time Estimate
48 to 52 Months

Contributor

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.4 MW11.7%$794,214
AH1-539
10.6 MW8.0%$547,769
AH1-690
87.6 MW66.2%$4,507,618
AH1-711
18.7 MW14.1%$960,398

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18702
Title
05SCOTSV 138.0 kV to AE1-108 POI 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~0.9 miles of 138 kV line between AE1-108 and Scottsville
Total Cost ($USD)
$3,800,000
Allocated Cost ($USD)
$3,800,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05SCOTSV-AE1-108 POI 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$3,800,000

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.c
Title
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Description
Upgrade (2) 3000A CBs at Davis Besse and (1) 3000A CB at Lemoyne
Total Cost ($USD)
$5,962,261
Allocated Cost ($USD)
$3,403,380
Time Estimate
56 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$286,099
AG2-149
26.0 MW6.4%$384,270
AG2-165
9.2 MW2.3%$135,685
AG2-212
9.2 MW2.3%$135,685
AG2-328
9.2 MW2.3%$135,685
AG2-515
20.4 MW5.0%$300,872
AH1-690
230.6 MW57.1%$3,403,380
AH1-711
80.0 MW19.8%$1,180,584

System Reinforcement: n6511
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n6511
Title
Reconductor the 0.8 miles of transmission line between West Fremont-Fremont [...] section of limiting conductor and provide estimates for their replacement.
Description
Reconductor the 0.8 miles of transmission line between West Fremont-Fremont 138 kV line. Existing transmission line conductor size 954 ACSR should be replaced with 954 ACSS AEP would need to replace their section of limiting conductor and provide estimates for their replacement.
Total Cost ($USD)
$4,238,484
Allocated Cost ($USD)
$3,347,779
Time Estimate
17 Months

Contributor

FacilityContingency
02W.FREM-05FRMNT 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
6.0 MW4.8%$204,919
AH1-690
97.6 MW79.0%$3,347,779
AH1-711
20.0 MW16.2%$685,786

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.j
Title
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Description
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Total Cost ($USD)
$4,525,814
Allocated Cost ($USD)
$3,221,706
Time Estimate
31 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$235,316
AG2-165
8.1 MW1.9%$84,849
AG2-212
8.1 MW1.9%$84,849
AG2-328
8.1 MW1.9%$84,849
AG2-660
1.0 MW0.2%$10,751
AH1-044
6.1 MW1.4%$64,493
AH1-150
6.1 MW1.4%$64,493
AH1-151
6.1 MW1.4%$64,493
AH1-690
306.6 MW71.2%$3,221,706
AH1-711
58.0 MW13.5%$610,013

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.h
Title
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Description
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Total Cost ($USD)
$3,850,794
Allocated Cost ($USD)
$2,814,238
Time Estimate
39 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$267,405
AG2-165
8.9 MW2.2%$84,233
AG2-212
8.9 MW2.2%$84,233
AG2-328
8.9 MW2.2%$84,233
AH1-690
297.6 MW73.1%$2,814,238
AH1-711
54.6 MW13.4%$516,453

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.m
Title
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Description
Upgrade (7) 3000A disconnect switches (D34545:N,S, D3454:W,E, A34673, D34561C, and 34623)and (2) B34545 impedance relays at Bayshore and Davis Besse
Total Cost ($USD)
$3,544,138
Allocated Cost ($USD)
$2,809,622
Time Estimate
42 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.3%$116,491
AG2-149
24.2 MW4.3%$153,617
AG2-165
9.0 MW1.6%$57,533
AG2-212
9.0 MW1.6%$57,533
AG2-328
9.0 MW1.6%$57,533
AH1-690
441.8 MW79.3%$2,809,622
AH1-711
45.9 MW8.2%$291,807

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.g
Title
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Description
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$2,771,525
Time Estimate
56 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$202,435
AG2-165
8.1 MW1.9%$72,993
AG2-212
8.1 MW1.9%$72,993
AG2-328
8.1 MW1.9%$72,993
AG2-660
1.0 MW0.2%$9,248
AH1-044
6.1 MW1.4%$55,481
AH1-150
6.1 MW1.4%$55,481
AH1-151
6.1 MW1.4%$55,481
AH1-690
306.6 MW71.2%$2,771,525
AH1-711
58.0 MW13.5%$524,773

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.d
Title
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Description
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$2,771,525
Time Estimate
56 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$202,435
AG2-165
8.1 MW1.9%$72,993
AG2-212
8.1 MW1.9%$72,993
AG2-328
8.1 MW1.9%$72,993
AG2-660
1.0 MW0.2%$9,248
AH1-044
6.1 MW1.4%$55,481
AH1-150
6.1 MW1.4%$55,481
AH1-151
6.1 MW1.4%$55,481
AH1-690
306.6 MW71.2%$2,771,525
AH1-711
58.0 MW13.5%$524,773

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.k
Title
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Description
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Total Cost ($USD)
$3,774,791
Allocated Cost ($USD)
$2,768,527
Time Estimate
29 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW6.1%$230,820
AG2-165
8.3 MW2.1%$79,342
AG2-212
8.3 MW2.1%$79,342
AG2-328
8.3 MW2.1%$79,342
AH1-690
288.2 MW73.3%$2,768,527
AH1-711
55.9 MW14.2%$537,418

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$2,748,721
Time Estimate
56 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW4.1%$158,348
AG2-149
22.5 MW5.7%$223,755
AG2-165
7.8 MW2.0%$77,540
AG2-212
7.8 MW2.0%$77,540
AG2-328
7.8 MW2.0%$77,540
AH1-690
275.9 MW70.6%$2,748,721
AH1-711
53.2 MW13.6%$529,961

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.i
Title
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Description
Upgrade (10) 3000A bus and line side disconnect switches at Davis Besse and Lemoyne (34624, A34604, D345:63A,63B,64D,64C,01N,01S,02W,02E)
Total Cost ($USD)
$3,952,709
Allocated Cost ($USD)
$2,256,287
Time Estimate
29 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$189,671
AG2-149
26.0 MW6.4%$254,753
AG2-165
9.2 MW2.3%$89,953
AG2-212
9.2 MW2.3%$89,953
AG2-328
9.2 MW2.3%$89,953
AG2-515
20.4 MW5.0%$199,465
AH1-690
230.6 MW57.1%$2,256,287
AH1-711
80.0 MW19.8%$782,674

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.k
Title
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Description
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Total Cost ($USD)
$2,701,212
Allocated Cost ($USD)
$1,974,100
Time Estimate
17 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$187,576
AG2-165
8.9 MW2.2%$59,087
AG2-212
8.9 MW2.2%$59,087
AG2-328
8.9 MW2.2%$59,087
AH1-690
297.6 MW73.1%$1,974,100
AH1-711
54.6 MW13.4%$362,275

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$1,533,593
Time Estimate
54 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$117,254
AG2-165
7.9 MW2.0%$41,793
AG2-212
7.9 MW2.0%$41,793
AG2-328
7.9 MW2.0%$41,793
AH1-690
290.3 MW74.1%$1,533,593
AH1-711
55.4 MW14.1%$292,630

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.l
Title
Upgrade Circuit Breaker B65 at Davis Besse
Description
Upgrade Circuit Breaker B65 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$1,533,593
Time Estimate
54 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$117,254
AG2-165
7.9 MW2.0%$41,793
AG2-212
7.9 MW2.0%$41,793
AG2-328
7.9 MW2.0%$41,793
AH1-690
290.3 MW74.1%$1,533,593
AH1-711
55.4 MW14.1%$292,630

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.g
Title
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Description
Upgrade (2) B34501 and B34502 relay thermals at Lemoyne and (3) 34563 relay and meter thermals at Davis Besse
Total Cost ($USD)
$2,137,421
Allocated Cost ($USD)
$1,220,083
Time Estimate
20 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$102,564
AG2-149
26.0 MW6.4%$137,758
AG2-165
9.2 MW2.3%$48,642
AG2-212
9.2 MW2.3%$48,642
AG2-328
9.2 MW2.3%$48,642
AG2-515
20.4 MW5.0%$107,860
AH1-690
230.6 MW57.1%$1,220,083
AH1-711
80.0 MW19.8%$423,229

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$1,211,059
Time Estimate
25 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$66,391
AG2-149
22.1 MW5.4%$92,436
AG2-165
7.9 MW1.9%$32,895
AG2-212
7.9 MW1.9%$32,895
AG2-328
7.9 MW1.9%$32,895
AH1-690
290.0 MW71.3%$1,211,059
AH1-711
55.3 MW13.6%$231,070

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.d
Title
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Description
Upgrade (12) dual 1590 ACSR SCCIR at Davis Besse and Lemoyne
Total Cost ($USD)
$2,070,983
Allocated Cost ($USD)
$1,182,159
Time Estimate
12 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$99,376
AG2-149
26.0 MW6.4%$133,476
AG2-165
9.2 MW2.3%$47,130
AG2-212
9.2 MW2.3%$47,130
AG2-328
9.2 MW2.3%$47,130
AG2-515
20.4 MW5.0%$104,507
AH1-690
230.6 MW57.1%$1,182,159
AH1-711
80.0 MW19.8%$410,074

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.f
Title
Upgrade the B34502 CB at Lemoyne
Description
Upgrade the B34502 CB at Lemoyne
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$1,180,945
Time Estimate
54 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$99,274
AG2-149
26.0 MW6.4%$133,338
AG2-165
9.2 MW2.3%$47,082
AG2-212
9.2 MW2.3%$47,082
AG2-328
9.2 MW2.3%$47,082
AG2-515
20.4 MW5.0%$104,400
AH1-690
230.6 MW57.1%$1,180,945
AH1-711
80.0 MW19.8%$409,653

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.a
Title
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Description
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Total Cost ($USD)
$1,350,788
Allocated Cost ($USD)
$1,056,291
Time Estimate
37 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
19.9 MW7.5%$100,649
AH1-690
209.2 MW78.2%$1,056,291
AH1-711
38.4 MW14.4%$193,848

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$978,827
Time Estimate
37 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$40,584
AG2-149
24.2 MW4.0%$53,518
AG2-165
9.0 MW1.5%$20,044
AG2-212
9.0 MW1.5%$20,044
AG2-328
9.0 MW1.5%$20,044
AG2-363
10.7 MW1.8%$23,617
AG2-364
7.1 MW1.2%$15,746
AG2-660
1.2 MW0.2%$2,634
AH1-044
7.1 MW1.2%$15,803
AH1-150
7.1 MW1.2%$15,803
AH1-151
7.1 MW1.2%$15,803
AH1-690
441.8 MW73.9%$978,827
AH1-711
45.9 MW7.7%$101,661

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-017
Title
Upgrade (2) 2000A bus and line side disconnect switches at Bayshore
Description
Upgrade (2) 2000A bus and line side disconnect switches at Bayshore
Total Cost ($USD)
$948,616
Allocated Cost ($USD)
$948,616
Time Estimate
36 Months

Contributor

FacilityContingency
02BAY SH-AH1-690 TP 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
718.0 MW100.0%$948,616

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$898,671
Time Estimate
22 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$37,260
AG2-149
24.2 MW4.0%$49,135
AG2-165
9.0 MW1.5%$18,402
AG2-212
9.0 MW1.5%$18,402
AG2-328
9.0 MW1.5%$18,402
AG2-363
10.7 MW1.8%$21,683
AG2-364
7.1 MW1.2%$14,456
AG2-660
1.2 MW0.2%$2,419
AH1-044
7.1 MW1.2%$14,509
AH1-150
7.1 MW1.2%$14,509
AH1-151
7.1 MW1.2%$14,509
AH1-690
441.8 MW73.9%$898,671
AH1-711
45.9 MW7.7%$93,336

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.g
Title
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Description
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$896,798
Time Estimate
21 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$49,163
AG2-149
22.1 MW5.4%$68,450
AG2-165
7.9 MW1.9%$24,359
AG2-212
7.9 MW1.9%$24,359
AG2-328
7.9 MW1.9%$24,359
AH1-690
290.0 MW71.3%$896,798
AH1-711
55.3 MW13.6%$171,109

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.e
Title
Upgrade (2) B12 and B18 CTs at Hayes
Description
Upgrade (2) B12 and B18 CTs at Hayes
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$895,933
Time Estimate
21 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$65,440
AG2-165
8.1 MW1.9%$23,596
AG2-212
8.1 MW1.9%$23,596
AG2-328
8.1 MW1.9%$23,596
AG2-660
1.0 MW0.2%$2,990
AH1-044
6.1 MW1.4%$17,935
AH1-150
6.1 MW1.4%$17,935
AH1-151
6.1 MW1.4%$17,935
AH1-690
306.6 MW71.2%$895,933
AH1-711
58.0 MW13.5%$169,640

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$878,624
Time Estimate
21 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$73,253
AG2-165
8.3 MW2.0%$25,180
AG2-212
8.3 MW2.0%$25,180
AG2-328
8.3 MW2.0%$25,180
AG2-660
1.0 MW0.3%$3,192
AH1-044
6.3 MW1.5%$19,143
AH1-150
6.3 MW1.5%$19,143
AH1-151
6.3 MW1.5%$19,143
AH1-690
288.2 MW69.8%$878,624
AH1-711
55.9 MW13.6%$170,556

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.c
Title
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Description
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Total Cost ($USD)
$1,215,695
Allocated Cost ($USD)
$865,394
Time Estimate
20 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$63,209
AG2-165
8.1 MW1.9%$22,792
AG2-212
8.1 MW1.9%$22,792
AG2-328
8.1 MW1.9%$22,792
AG2-660
1.0 MW0.2%$2,888
AH1-044
6.1 MW1.4%$17,324
AH1-150
6.1 MW1.4%$17,324
AH1-151
6.1 MW1.4%$17,324
AH1-690
306.6 MW71.2%$865,394
AH1-711
58.0 MW13.5%$163,858

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$812,704
Time Estimate
14 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$33,696
AG2-149
24.2 MW4.0%$44,435
AG2-165
9.0 MW1.5%$16,642
AG2-212
9.0 MW1.5%$16,642
AG2-328
9.0 MW1.5%$16,642
AG2-363
10.7 MW1.8%$19,609
AG2-364
7.1 MW1.2%$13,073
AG2-660
1.2 MW0.2%$2,187
AH1-044
7.1 MW1.2%$13,121
AH1-150
7.1 MW1.2%$13,121
AH1-151
7.1 MW1.2%$13,121
AH1-690
441.8 MW73.9%$812,704
AH1-711
45.9 MW7.7%$84,407

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$738,363
Time Estimate
19 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$30,614
AG2-149
24.2 MW4.0%$40,370
AG2-165
9.0 MW1.5%$15,120
AG2-212
9.0 MW1.5%$15,120
AG2-328
9.0 MW1.5%$15,120
AG2-363
10.7 MW1.8%$17,815
AG2-364
7.1 MW1.2%$11,877
AG2-660
1.2 MW0.2%$1,987
AH1-044
7.1 MW1.2%$11,921
AH1-150
7.1 MW1.2%$11,921
AH1-151
7.1 MW1.2%$11,921
AH1-690
441.8 MW73.9%$738,363
AH1-711
45.9 MW7.7%$76,686

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.a
Title
Upgrade D120 and D125 disconnect switches at Beaver substation
Description
Upgrade D120 and D125 disconnect switches at Beaver substation
Total Cost ($USD)
$929,516
Allocated Cost ($USD)
$727,201
Time Estimate
22 Months

Contributor

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.6 MW7.4%$68,868
AH1-690
238.1 MW78.2%$727,201
AH1-711
43.7 MW14.4%$133,446

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.i
Title
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Description
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$725,939
Time Estimate
19 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$53,023
AG2-165
8.1 MW1.9%$19,119
AG2-212
8.1 MW1.9%$19,119
AG2-328
8.1 MW1.9%$19,119
AG2-660
1.0 MW0.2%$2,422
AH1-044
6.1 MW1.4%$14,532
AH1-150
6.1 MW1.4%$14,532
AH1-151
6.1 MW1.4%$14,532
AH1-690
306.6 MW71.2%$725,939
AH1-711
58.0 MW13.5%$137,453

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$717,344
Time Estimate
36 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$54,846
AG2-165
7.9 MW2.0%$19,549
AG2-212
7.9 MW2.0%$19,549
AG2-328
7.9 MW2.0%$19,549
AH1-690
290.3 MW74.1%$717,344
AH1-711
55.4 MW14.1%$136,879

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$711,914
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$59,354
AG2-165
8.3 MW2.0%$20,402
AG2-212
8.3 MW2.0%$20,402
AG2-328
8.3 MW2.0%$20,402
AG2-660
1.0 MW0.3%$2,586
AH1-044
6.3 MW1.5%$15,511
AH1-150
6.3 MW1.5%$15,511
AH1-151
6.3 MW1.5%$15,511
AH1-690
288.2 MW69.8%$711,914
AH1-711
55.9 MW13.6%$138,195

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.k
Title
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Description
Upgrade (1) 1590 AACSR Phase A/C line drop at Davis Besse substation and (3) Phase 3 "B-B", Phase 1&2 "C-C", and shared node to wave trap line drops at Hayes
Total Cost ($USD)
$855,032
Allocated Cost ($USD)
$637,420
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.4%$46,558
AG2-165
8.1 MW2.0%$16,788
AG2-212
8.1 MW2.0%$16,788
AG2-328
8.1 MW2.0%$16,788
AH1-690
306.6 MW74.5%$637,420
AH1-711
58.0 MW14.1%$120,692

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.b
Title
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Description
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Total Cost ($USD)
$809,465
Allocated Cost ($USD)
$635,147
Time Estimate
15 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
19.4 MW7.2%$57,986
AH1-690
212.1 MW78.5%$635,147
AH1-711
38.8 MW14.4%$116,332

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.c
Title
Upgrade the (3) B216, B219 and B4 1500 CTs
Description
Upgrade the (3) B216, B219 and B4 1500 CTs
Total Cost ($USD)
$853,850
Allocated Cost ($USD)
$624,011
Time Estimate
16 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$59,293
AG2-165
8.9 MW2.2%$18,677
AG2-212
8.9 MW2.2%$18,677
AG2-328
8.9 MW2.2%$18,677
AH1-690
297.6 MW73.1%$624,011
AH1-711
54.6 MW13.4%$114,515

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$611,784
Time Estimate
22 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.5%$51,429
AG2-149
26.0 MW6.1%$69,075
AG2-165
9.2 MW2.2%$24,390
AG2-212
9.2 MW2.2%$24,390
AG2-328
9.2 MW2.2%$24,390
AG2-515
20.4 MW4.8%$54,084
AG2-660
1.2 MW0.3%$3,205
AH1-044
7.3 MW1.7%$19,236
AH1-150
7.3 MW1.7%$19,236
AH1-151
7.3 MW1.7%$19,236
AH1-690
230.6 MW54.0%$611,784
AH1-711
80.0 MW18.7%$212,219

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.h
Title
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Description
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Total Cost ($USD)
$852,462
Allocated Cost ($USD)
$606,826
Time Estimate
19 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$44,323
AG2-165
8.1 MW1.9%$15,982
AG2-212
8.1 MW1.9%$15,982
AG2-328
8.1 MW1.9%$15,982
AG2-660
1.0 MW0.2%$2,025
AH1-044
6.1 MW1.4%$12,148
AH1-150
6.1 MW1.4%$12,148
AH1-151
6.1 MW1.4%$12,148
AH1-690
306.6 MW71.2%$606,826
AH1-711
58.0 MW13.5%$114,899

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-010
Title
Upgrade 4/0 CU sub conductor at FOWLES substation
Description
Upgrade 4/0 CU sub conductor at FOWLES substation
Total Cost ($USD)
$591,862
Allocated Cost ($USD)
$591,862
Time Estimate
13 Months

Contributor

FacilityContingency
02FWLSQ2-02PV Q2 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
28.9 MW100.0%$591,862

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.e
Title
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Description
Upgrade (2) 8.6 Ohm impedance relays at Davis Besse and (2) 7.8 Ohm impedance relays at Lemoyne
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$582,117
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$48,935
AG2-149
26.0 MW6.4%$65,726
AG2-165
9.2 MW2.3%$23,208
AG2-212
9.2 MW2.3%$23,208
AG2-328
9.2 MW2.3%$23,208
AG2-515
20.4 MW5.0%$51,461
AH1-690
230.6 MW57.1%$582,117
AH1-711
80.0 MW19.8%$201,928

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.i
Title
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Description
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Total Cost ($USD)
$756,208
Allocated Cost ($USD)
$560,559
Time Estimate
13 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$42,859
AG2-165
7.9 MW2.0%$15,276
AG2-212
7.9 MW2.0%$15,276
AG2-328
7.9 MW2.0%$15,276
AH1-690
290.3 MW74.1%$560,559
AH1-711
55.4 MW14.1%$106,962

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.h
Title
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Description
Upgrade (12) 4.00 SPS.AL PIPE at Lemoyne
Total Cost ($USD)
$961,300
Allocated Cost ($USD)
$548,730
Time Estimate
22 Months

Contributor

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
19.4 MW4.8%$46,128
AG2-149
26.0 MW6.4%$61,956
AG2-165
9.2 MW2.3%$21,877
AG2-212
9.2 MW2.3%$21,877
AG2-328
9.2 MW2.3%$21,877
AG2-515
20.4 MW5.0%$48,510
AH1-690
230.6 MW57.1%$548,730
AH1-711
80.0 MW19.8%$190,346

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-016.b
Title
Upgrade the standalone CT at Ottawa
Description
Upgrade the standalone CT at Ottawa
Total Cost ($USD)
$672,402
Allocated Cost ($USD)
$537,901
Time Estimate
20 Months

Contributor

FacilityContingency
02LAKVEW-02OTTAWA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$32,519
AH1-690
89.7 MW80.0%$537,901
AH1-711
17.0 MW15.2%$101,982

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$526,591
Time Estimate
20 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$21,833
AG2-149
24.2 MW4.0%$28,792
AG2-165
9.0 MW1.5%$10,783
AG2-212
9.0 MW1.5%$10,783
AG2-328
9.0 MW1.5%$10,783
AG2-363
10.7 MW1.8%$12,706
AG2-364
7.1 MW1.2%$8,471
AG2-660
1.2 MW0.2%$1,417
AH1-044
7.1 MW1.2%$8,502
AH1-150
7.1 MW1.2%$8,502
AH1-151
7.1 MW1.2%$8,502
AH1-690
441.8 MW73.9%$526,591
AH1-711
45.9 MW7.7%$54,692

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$509,000
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$42,437
AG2-165
8.3 MW2.0%$14,587
AG2-212
8.3 MW2.0%$14,587
AG2-328
8.3 MW2.0%$14,587
AG2-660
1.0 MW0.3%$1,849
AH1-044
6.3 MW1.5%$11,090
AH1-150
6.3 MW1.5%$11,090
AH1-151
6.3 MW1.5%$11,090
AH1-690
288.2 MW69.8%$509,000
AH1-711
55.9 MW13.6%$98,806

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$507,727
Time Estimate
20 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$42,331
AG2-165
8.3 MW2.0%$14,551
AG2-212
8.3 MW2.0%$14,551
AG2-328
8.3 MW2.0%$14,551
AG2-660
1.0 MW0.3%$1,845
AH1-044
6.3 MW1.5%$11,062
AH1-150
6.3 MW1.5%$11,062
AH1-151
6.3 MW1.5%$11,062
AH1-690
288.2 MW69.8%$507,727
AH1-711
55.9 MW13.6%$98,558

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.d
Title
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Description
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Total Cost ($USD)
$690,685
Allocated Cost ($USD)
$504,767
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$47,962
AG2-165
8.9 MW2.2%$15,108
AG2-212
8.9 MW2.2%$15,108
AG2-328
8.9 MW2.2%$15,108
AH1-690
297.6 MW73.1%$504,767
AH1-711
54.6 MW13.4%$92,632

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$460,035
Time Estimate
20 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$35,173
AG2-165
7.9 MW2.0%$12,537
AG2-212
7.9 MW2.0%$12,537
AG2-328
7.9 MW2.0%$12,537
AH1-690
290.3 MW74.1%$460,035
AH1-711
55.4 MW14.1%$87,781

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$438,140
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW4.1%$25,240
AG2-149
22.5 MW5.7%$35,666
AG2-165
7.8 MW2.0%$12,360
AG2-212
7.8 MW2.0%$12,360
AG2-328
7.8 MW2.0%$12,360
AH1-690
275.9 MW70.6%$438,140
AH1-711
53.2 MW13.6%$84,475

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-023.a
Title
Upgrade (2) line drop strands, one into Greenfield and one into Lakeview
Description
Upgrade (2) line drop strands, one into Greenfield and one into Lakeview using single (1) 954 45/7 "Rail" ACSR
Total Cost ($USD)
$526,339
Allocated Cost ($USD)
$421,055
Time Estimate
12 Months

Contributor

FacilityContingency
02GRNFLD-02LAKVEW 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$25,455
AH1-690
89.7 MW80.0%$421,055
AH1-711
17.0 MW15.2%$79,829

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-016.a
Title
Upgrade (1) line drop into Lakeview and (1) line drop into Ottawa
Description
Upgrade (1) line drop into Lakeview and (1) line drop into Ottawa
Total Cost ($USD)
$526,339
Allocated Cost ($USD)
$421,055
Time Estimate
13 Months

Contributor

FacilityContingency
02LAKVEW-02OTTAWA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$25,455
AH1-690
89.7 MW80.0%$421,055
AH1-711
17.0 MW15.2%$79,829

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$413,179
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$34,448
AG2-165
8.3 MW2.0%$11,841
AG2-212
8.3 MW2.0%$11,841
AG2-328
8.3 MW2.0%$11,841
AG2-660
1.0 MW0.3%$1,501
AH1-044
6.3 MW1.5%$9,002
AH1-150
6.3 MW1.5%$9,002
AH1-151
6.3 MW1.5%$9,002
AH1-690
288.2 MW69.8%$413,179
AH1-711
55.9 MW13.6%$80,205

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI.023.b
Title
Upgrade the B242 relay thermal
Description
Upgrade the B242 relay thermal
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$407,901
Time Estimate
18 Months

Contributor

FacilityContingency
02GRNFLD-02LAKVEW 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$24,660
AH1-690
89.7 MW80.0%$407,901
AH1-711
17.0 MW15.2%$77,335

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.m
Title
Upgrade (2) B65 Meter Thermals at Davis Besse
Description
Upgrade (2) B65 Meter Thermals at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$377,973
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$28,899
AG2-165
7.9 MW2.0%$10,300
AG2-212
7.9 MW2.0%$10,300
AG2-328
7.9 MW2.0%$10,300
AH1-690
290.3 MW74.1%$377,973
AH1-711
55.4 MW14.1%$72,122

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.j
Title
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$377,973
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$28,899
AG2-165
7.9 MW2.0%$10,300
AG2-212
7.9 MW2.0%$10,300
AG2-328
7.9 MW2.0%$10,300
AH1-690
290.3 MW74.1%$377,973
AH1-711
55.4 MW14.1%$72,122

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.k
Title
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$377,973
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$28,899
AG2-165
7.9 MW2.0%$10,300
AG2-212
7.9 MW2.0%$10,300
AG2-328
7.9 MW2.0%$10,300
AH1-690
290.3 MW74.1%$377,973
AH1-711
55.4 MW14.1%$72,122

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.f
Title
Upgrade the (1) B216 relay thermal at Beaver
Description
Upgrade the (1) B216 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$372,642
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$35,408
AG2-165
8.9 MW2.2%$11,153
AG2-212
8.9 MW2.2%$11,153
AG2-328
8.9 MW2.2%$11,153
AH1-690
297.6 MW73.1%$372,642
AH1-711
54.6 MW13.4%$68,385

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.i
Title
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$372,642
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$35,408
AG2-165
8.9 MW2.2%$11,153
AG2-212
8.9 MW2.2%$11,153
AG2-328
8.9 MW2.2%$11,153
AH1-690
297.6 MW73.1%$372,642
AH1-711
54.6 MW13.4%$68,385

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.l
Title
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$372,642
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$35,408
AG2-165
8.9 MW2.2%$11,153
AG2-212
8.9 MW2.2%$11,153
AG2-328
8.9 MW2.2%$11,153
AH1-690
297.6 MW73.1%$372,642
AH1-711
54.6 MW13.4%$68,385

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.i
Title
Upgrade B182 relay thermal at Beaver
Description
Upgrade B182 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$363,320
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.f
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$363,320
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.j
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z4-BU & Z4-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$363,320
Time Estimate
19 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$19,917
AG2-149
22.1 MW5.4%$27,731
AG2-165
7.9 MW1.9%$9,868
AG2-212
7.9 MW1.9%$9,868
AG2-328
7.9 MW1.9%$9,868
AH1-690
290.0 MW71.3%$363,320
AH1-711
55.3 MW13.6%$69,321

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$355,957
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$29,677
AG2-165
8.3 MW2.0%$10,201
AG2-212
8.3 MW2.0%$10,201
AG2-328
8.3 MW2.0%$10,201
AG2-660
1.0 MW0.3%$1,293
AH1-044
6.3 MW1.5%$7,756
AH1-150
6.3 MW1.5%$7,756
AH1-151
6.3 MW1.5%$7,756
AH1-690
288.2 MW69.8%$355,957
AH1-711
55.9 MW13.6%$69,097

System Reinforcement: n6525.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6525.2 / AEPO0026d
Title
Replace three Sub Cond 1590 AAC 61 Str at Fremont
Description
Total Cost ($USD)
$390,000
Allocated Cost ($USD)
$308,043
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
02W.FREM-05FRMNT 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
6.0 MW4.8%$18,855
AH1-690
97.6 MW79.0%$308,043
AH1-711
20.0 MW16.2%$63,102

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-019
Title
Upgrade phase 2 wave trap at Galion
Description
Upgrade phase 2 wave trap at Galion
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$291,889
Time Estimate
18 Months

Contributor

FacilityContingency
02GALION-AG2-148 TP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
144.6 MW29.8%$184,641
AG2-329
65.6 MW13.5%$83,732
AH1-690
228.6 MW47.0%$291,889
AH1-711
47.3 MW9.7%$60,337

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$291,159
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$12,072
AG2-149
24.2 MW4.0%$15,919
AG2-165
9.0 MW1.5%$5,962
AG2-212
9.0 MW1.5%$5,962
AG2-328
9.0 MW1.5%$5,962
AG2-363
10.7 MW1.8%$7,025
AG2-364
7.1 MW1.2%$4,684
AG2-660
1.2 MW0.2%$784
AH1-044
7.1 MW1.2%$4,701
AH1-150
7.1 MW1.2%$4,701
AH1-151
7.1 MW1.2%$4,701
AH1-690
441.8 MW73.9%$291,159
AH1-711
45.9 MW7.7%$30,240

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-016.d
Title
Upgrade 795 ACSR B6 and B145 breaker leads and shared and (2) shared node subconductors at Lakeview
Description
Upgrade 795 ACSR B6 and B145 breaker leads and shared and (2) shared node subconductors at Lakeview
Total Cost ($USD)
$337,294
Allocated Cost ($USD)
$269,825
Time Estimate
13 Months

Contributor

FacilityContingency
02LAKVEW-02OTTAWA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$16,312
AH1-690
89.7 MW80.0%$269,825
AH1-711
17.0 MW15.2%$51,157

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.e
Title
Upgrade the (1) B219 1200 CT to PVD at Beaver
Description
Upgrade the (1) B219 1200 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$255,752
Time Estimate
16 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$24,301
AG2-165
8.9 MW2.2%$7,655
AG2-212
8.9 MW2.2%$7,655
AG2-328
8.9 MW2.2%$7,655
AH1-690
297.6 MW73.1%$255,752
AH1-711
54.6 MW13.4%$46,934

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.h
Title
Upgrade the B185 CT to PVD at Beaver
Description
Upgrade the B185 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$249,354
Time Estimate
17 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$13,670
AG2-149
22.1 MW5.4%$19,032
AG2-165
7.9 MW1.9%$6,773
AG2-212
7.9 MW1.9%$6,773
AG2-328
7.9 MW1.9%$6,773
AH1-690
290.0 MW71.3%$249,354
AH1-711
55.3 MW13.6%$47,577

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.b
Title
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Description
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Total Cost ($USD)
$305,540
Allocated Cost ($USD)
$223,295
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$21,217
AG2-165
8.9 MW2.2%$6,683
AG2-212
8.9 MW2.2%$6,683
AG2-328
8.9 MW2.2%$6,683
AH1-690
297.6 MW73.1%$223,295
AH1-711
54.6 MW13.4%$40,978

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.f
Title
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Description
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Total Cost ($USD)
$305,149
Allocated Cost ($USD)
$217,221
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$15,866
AG2-165
8.1 MW1.9%$5,721
AG2-212
8.1 MW1.9%$5,721
AG2-328
8.1 MW1.9%$5,721
AG2-660
1.0 MW0.2%$725
AH1-044
6.1 MW1.4%$4,348
AH1-150
6.1 MW1.4%$4,348
AH1-151
6.1 MW1.4%$4,348
AH1-690
306.6 MW71.2%$217,221
AH1-711
58.0 MW13.5%$41,130

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.d
Title
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Description
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Total Cost ($USD)
$265,209
Allocated Cost ($USD)
$207,485
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.6 MW7.4%$19,649
AH1-690
238.1 MW78.2%$207,485
AH1-711
43.7 MW14.4%$38,075

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.b
Title
Upgrade (1) 3000 SAC 169 line drop at Beaver
Description
Upgrade (1) 3000 SAC 169 line drop at Beaver
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$205,889
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.6 MW7.4%$19,498
AH1-690
238.1 MW78.2%$205,889
AH1-711
43.7 MW14.4%$37,782

System Reinforcement: n9674.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9674.0 / AEPO0026b
Title
Replace 1200 A Switch at Fremont
Description
Total Cost ($USD)
$260,000
Allocated Cost ($USD)
$205,362
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
02W.FREM-05FRMNT 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
6.0 MW4.8%$12,570
AH1-690
97.6 MW79.0%$205,362
AH1-711
20.0 MW16.2%$42,068

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.b
Title
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Description
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Total Cost ($USD)
$284,061
Allocated Cost ($USD)
$202,209
Time Estimate
18 Months

Contributor

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.4 MW5.2%$14,770
AG2-165
8.1 MW1.9%$5,326
AG2-212
8.1 MW1.9%$5,326
AG2-328
8.1 MW1.9%$5,326
AG2-660
1.0 MW0.2%$675
AH1-044
6.1 MW1.4%$4,048
AH1-150
6.1 MW1.4%$4,048
AH1-151
6.1 MW1.4%$4,048
AH1-690
306.6 MW71.2%$202,209
AH1-711
58.0 MW13.5%$38,287

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.l
Title
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Description
Upgrade (5) 4.00 SPS AL PIPE 61 sub conductors at BAYSHORE on the Bayshore - Davis Besse 345kV line
Total Cost ($USD)
$246,545
Allocated Cost ($USD)
$195,449
Time Estimate
14 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.3%$8,104
AG2-149
24.2 MW4.3%$10,686
AG2-165
9.0 MW1.6%$4,002
AG2-212
9.0 MW1.6%$4,002
AG2-328
9.0 MW1.6%$4,002
AH1-690
441.8 MW79.3%$195,449
AH1-711
45.9 MW8.2%$20,299

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$195,081
Time Estimate
12 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$14,915
AG2-165
7.9 MW2.0%$5,316
AG2-212
7.9 MW2.0%$5,316
AG2-328
7.9 MW2.0%$5,316
AH1-690
290.3 MW74.1%$195,081
AH1-711
55.4 MW14.1%$37,224

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$195,081
Time Estimate
12 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$14,915
AG2-165
7.9 MW2.0%$5,316
AG2-212
7.9 MW2.0%$5,316
AG2-328
7.9 MW2.0%$5,316
AH1-690
290.3 MW74.1%$195,081
AH1-711
55.4 MW14.1%$37,224

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$190,544
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$7,900
AG2-149
24.2 MW4.0%$10,418
AG2-165
9.0 MW1.5%$3,902
AG2-212
9.0 MW1.5%$3,902
AG2-328
9.0 MW1.5%$3,902
AG2-363
10.7 MW1.8%$4,597
AG2-364
7.1 MW1.2%$3,065
AG2-660
1.2 MW0.2%$513
AH1-044
7.1 MW1.2%$3,076
AH1-150
7.1 MW1.2%$3,076
AH1-151
7.1 MW1.2%$3,076
AH1-690
441.8 MW73.9%$190,544
AH1-711
45.9 MW7.7%$19,790

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$190,544
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$7,900
AG2-149
24.2 MW4.0%$10,418
AG2-165
9.0 MW1.5%$3,902
AG2-212
9.0 MW1.5%$3,902
AG2-328
9.0 MW1.5%$3,902
AG2-363
10.7 MW1.8%$4,597
AG2-364
7.1 MW1.2%$3,065
AG2-660
1.2 MW0.2%$513
AH1-044
7.1 MW1.2%$3,076
AH1-150
7.1 MW1.2%$3,076
AH1-151
7.1 MW1.2%$3,076
AH1-690
441.8 MW73.9%$190,544
AH1-711
45.9 MW7.7%$19,790

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.m
Title
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$250,039
Allocated Cost ($USD)
$182,734
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$17,363
AG2-165
8.9 MW2.2%$5,469
AG2-212
8.9 MW2.2%$5,469
AG2-328
8.9 MW2.2%$5,469
AH1-690
297.6 MW73.1%$182,734
AH1-711
54.6 MW13.4%$33,534

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI.023.c
Title
Upgrade the (2) B96 and (2) B7 breaker leads at Lakeview and the (1) B242 to D241 lead at Greenfield
Description
Upgrade the (2) B96 and (2) B7 breaker leads at Lakeview and the (1) B242 to D241 lead at Greenfield
Total Cost ($USD)
$218,931
Allocated Cost ($USD)
$175,138
Time Estimate
13 Months

Contributor

FacilityContingency
02GRNFLD-02LAKVEW 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-515
5.4 MW4.8%$10,588
AH1-690
89.7 MW80.0%$175,138
AH1-711
17.0 MW15.2%$33,205

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$156,064
Time Estimate
13 Months

Contributor

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
18.3 MW3.1%$6,471
AG2-149
24.2 MW4.0%$8,533
AG2-165
9.0 MW1.5%$3,196
AG2-212
9.0 MW1.5%$3,196
AG2-328
9.0 MW1.5%$3,196
AG2-363
10.7 MW1.8%$3,766
AG2-364
7.1 MW1.2%$2,510
AG2-660
1.2 MW0.2%$420
AH1-044
7.1 MW1.2%$2,520
AH1-150
7.1 MW1.2%$2,520
AH1-151
7.1 MW1.2%$2,520
AH1-690
441.8 MW73.9%$156,064
AH1-711
45.9 MW7.7%$16,209

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005c
Title
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Description
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Total Cost ($USD)
$191,109
Allocated Cost ($USD)
$149,954
Time Estimate
11 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
19.4 MW7.2%$13,690
AH1-690
212.1 MW78.5%$149,954
AH1-711
38.8 MW14.4%$27,465

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$146,470
Time Estimate
13 Months

Contributor

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
22.2 MW5.7%$11,199
AG2-165
7.9 MW2.0%$3,992
AG2-212
7.9 MW2.0%$3,992
AG2-328
7.9 MW2.0%$3,992
AH1-690
290.3 MW74.1%$146,470
AH1-711
55.4 MW14.1%$27,948

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$133,565
Time Estimate
13 Months

Contributor

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
15.9 MW3.9%$7,322
AG2-149
22.1 MW5.4%$10,195
AG2-165
7.9 MW1.9%$3,628
AG2-212
7.9 MW1.9%$3,628
AG2-328
7.9 MW1.9%$3,628
AH1-690
290.0 MW71.3%$133,565
AH1-711
55.3 MW13.6%$25,484

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.g
Title
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Description
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Total Cost ($USD)
$178,089
Allocated Cost ($USD)
$130,151
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$12,367
AG2-165
8.9 MW2.2%$3,896
AG2-212
8.9 MW2.2%$3,896
AG2-328
8.9 MW2.2%$3,896
AH1-690
297.6 MW73.1%$130,151
AH1-711
54.6 MW13.4%$23,885

System Reinforcement: n9669.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9669.0 / AEPO0027e
Title
Replace Sub cond 397.5 ACSR 26/7 at Howard
Description
Total Cost ($USD)
$130,000
Allocated Cost ($USD)
$130,000
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
05HOWARD1-AC2-015 TAP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
26.1 MW100.0%$130,000

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.j
Title
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$173,391
Allocated Cost ($USD)
$126,718
Time Estimate
12 Months

Contributor

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
28.3 MW6.9%$12,041
AG2-165
8.9 MW2.2%$3,793
AG2-212
8.9 MW2.2%$3,793
AG2-328
8.9 MW2.2%$3,793
AH1-690
297.6 MW73.1%$126,718
AH1-711
54.6 MW13.4%$23,254

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$123,688
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement: n9675.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9675.0 / AEPO0035a
Title
Sag Study will be required on ACSR ~ 954 ~ 45/7, 18.3 miles line between South Berwick and Galion .
Description
Sag Study will be required on ACSR ~ 954 ~ 45/7, 18.3 miles line between South Berwick and Galion .The cost is expected to be 73,200.New Ratings after sag study : S/N: 1409 MVA S/E: 1887 MVA.Rebuild/Reconductor, cost : $ 36.6 million
Total Cost ($USD)
$229,320
Allocated Cost ($USD)
$107,857
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
02GALION-AG2-148 TP 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
144.6 MW29.8%$68,228
AG2-329
65.6 MW13.5%$30,940
AH1-690
228.6 MW47.0%$107,857
AH1-711
47.3 MW9.7%$22,295

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$106,511
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$8,880
AG2-165
8.3 MW2.0%$3,052
AG2-212
8.3 MW2.0%$3,052
AG2-328
8.3 MW2.0%$3,052
AG2-660
1.0 MW0.3%$387
AH1-044
6.3 MW1.5%$2,321
AH1-150
6.3 MW1.5%$2,321
AH1-151
6.3 MW1.5%$2,321
AH1-690
288.2 MW69.8%$106,511
AH1-711
55.9 MW13.6%$20,676

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$106,511
Time Estimate
18 Months

Contributor

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-149
24.0 MW5.8%$8,880
AG2-165
8.3 MW2.0%$3,052
AG2-212
8.3 MW2.0%$3,052
AG2-328
8.3 MW2.0%$3,052
AG2-660
1.0 MW0.3%$387
AH1-044
6.3 MW1.5%$2,321
AH1-150
6.3 MW1.5%$2,321
AH1-151
6.3 MW1.5%$2,321
AH1-690
288.2 MW69.8%$106,511
AH1-711
55.9 MW13.6%$20,676

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18731
Title
05WOLFCK 138kV to 05W.WATERT 138kV ckt 1 - Replace Equipment
Description
At Wolf Creek Station replace 795 KCM AAC, 37-Str.
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$100,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05WOLFCK-05W.WATERT 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
15.5 MW100.0%$100,000

System Reinforcement: n9676.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9676.0 / AEPO0033a
Title
Sag Study will be required on 19.2 miles line between Fostoria and Lallen [...] tudy : S/N: 1409MVA S/E: 1887MVA.Rebuild/Reconductor, cost : $ 38.4 million
Description
Sag Study will be required on 19.2 miles line between Fostoria and Lallendorf .The cost is expected to be 76,800.New Ratings after sag study : S/N: 1409MVA S/E: 1887MVA.Rebuild/Reconductor, cost : $ 38.4 million
Total Cost ($USD)
$99,840
Allocated Cost ($USD)
$99,840
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
02LALLENDORF-05FOSTOR 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
788.0 MW100.0%$99,840

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPAPRJV002
Title
Perform sag study on 397 ACSR between Clifford and Boxwood (13.7 miles)
Description
Perform sag study on 397 ACSR between Clifford and Boxwood (13.7 miles)
Total Cost ($USD)
$82,200
Allocated Cost ($USD)
$82,200
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05BOXWD-05CLIFFR 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$82,200

System Reinforcement: n8383
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n8383
Title
A sag study will be required on the 3.65 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation
Description
A sag study will be required on the 3.65 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation would be required (if any) to operate at the conductor's MOT. Depending on the sag study results findings, the cost for this upgrade is expected to be $60,000 (no remediation required, just sag study) and $10.0 million (complete line reconductor/rebuild).AEP will determine the new rating(s) based on the scope of work required to exceed the anticipated loading.
Total Cost ($USD)
$78,000
Allocated Cost ($USD)
$78,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05CLIFFR-05COLLEEN SS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$78,000

System Reinforcement: n8386
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n8386
Title
A sag study will be required on the ~4.0 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation
Description
A sag study will be required on the ~4.0 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK~ Conductor to determine what mitigation would be required (if any) to operate at the conductor's MOT. Depending on the sag study results findings, the cost for this upgrade is expected to be $60,000 (no remediation required, just sag study) and $12.0 million (complete line reconductor/rebuild).AEP will determine the new rating(s) based on the scope of work required to exceed the anticipated loading.
Total Cost ($USD)
$78,000
Allocated Cost ($USD)
$78,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05COLLEEN SS-05JAMES RIVR 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$78,000

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPAPRJV006_2
Title
Sag Study 397 ACSR between James River and Soapstone ~10 miles
Description
Sag Study 397 ACSR between James River and Soapstone ~10 miles
Total Cost ($USD)
$60,000
Allocated Cost ($USD)
$60,000
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05JAMES RIVR-05SOAPSTONE 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-690
9.1 MW100.0%$60,000

System Reinforcement: b3925.3
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
b3925.3
Title
Rebuild the 6.5 miles of Avery-Hayes 138 kV Line with 795 kcmil 26/7 ACSS conductor
Description
Rebuild the 6.5 miles of Avery-Hayes 138 kV Line with 795 kcmil 26/7 ACSS conductor
Cost Information
Time Estimate
Jun 01 2027

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02AVERY-02HAYES 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3925.1
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
b3925.1
Title
Rebuild the 7.46 miles of Avery - Shinrock 138 kV Line with 795 kcmil 26/7 ACSS (7.46 miles)
Description
Rebuild the 7.46 miles of Avery - Shinrock 138 kV Line with 795 kcmil 26/7 ACSS (7.46 miles)
Cost Information
Time Estimate
Dec 10 2027

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02AVERY-02SHNROK 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3925.4
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
b3925.4
Title
Rebuild the Greenfield - Beaver 138 kV corridor (32 miles) with 795 kcmil 26/7 ACSS
Description
Rebuild the Greenfield - Beaver 138 kV corridor (32 miles) with 795 kcmil 26/7 ACSS. This corridor encompasses multiple 138 kV lines that are constructed on common towers.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02BEAVER-02NASA 138.0 kV Ckt 1 line(Any)
02BEAVER-02OAKPOINT 138.0 kV Ckt 1 line(Any)
02BRWELL-02FORD 138.0 kV Ckt 1 line(Any)
02BRWELL-02N DEPT 138.0 kV Ckt 1 line(Any)
02GRNFLD-02N DEPT 138.0 kV Ckt 1 line(Any)
02GRNFLD-02NASA 138.0 kV Ckt 1 line(Any)

System Reinforcement: s3360.1
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
s3360.1
Title
Galion 138kV Upgrades
Description
- Replace 138 kV breakers B-52, B-55, B-58, B-59 and B-60 as well as circuit switchers CS-136 and CS-137. - Replace and install associated disconnect switches and protective relaying. - Replace limiting substation conductor.
Cost Information
Time Estimate
Jun 01 2027

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02GALION-02GALION 345.0/138.0 kV Ckt 3 transformer(Any)
02GALION-02GALION 345.0/138.0 kV Ckt 4 transformer(Any)

System Reinforcement: s3469.1
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
s3469.1 / ATSI-2024-024
Title
Rebuild the double circuit Galion – Roberts North 138 kV Line and Galion – Roberts South 138 kV Line
Description
Rebuild the double circuit Galion – Roberts North 138 kV Line and Galion – Roberts South 138 kV Line on shared structures. - Galion: replace circuit breakers and associated disconnect switches. - Roberts: replace substation conductor https://pjm.com/-/media/committees-groups/committees/teac/2024/20241008/20241008-informational-only---atsi-local-plan-submission-of-supplemental-project-2024.ashx
Cost Information
Time Estimate
Aug 27 2026

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02DUALR+-02ROBERT 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3925.2
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
b3925.2
Title
Rebuild the 13.45 miles of Greenfield - Lakeview 138 kV Line from 2 x 336.4 kcmil 26/7 ACSR to 1 x 795 kcmil 26/7 ACSS
Description
Rebuild the 13.45 miles of Greenfield - Lakeview 138 kV Line from 2 x 336.4 kcmil 26/7 ACSR to 1 x 795 kcmil 26/7 ACSS
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02GRNFLD-02LAKVEW 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3033
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
b3033
Title
Ottawa-Lakeview 138 kV Reconductor and Substation Upgrades
Description
Cost Information
Time Estimate
Oct 31 2025

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
02LAKVEW-02OTTAWA 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3888.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3888.1
Title
Preform sag study and complete mitigations on the 138 kV line between East Leipsic and the AE2-072 tap (Lammer) to allow line's conductor to operate to its maximum operating temperature (MOT).
Description
Preform sag study and complete mitigations on the 138 kV line between East Leipsic and the AE2-072 tap (Lammer) to allow line's conductor to operate to its maximum operating temperature (MOT).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05E.LEIPSIC2-AE2-072 TAP 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
4BREMO-AE1-108 POI 138.0 kV Ckt 1 line(Any)

System Reinforcement: n8471
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8471
Title
East Sayre-North Waverly 115kV line upgrade - FirstEnergy (NYISO CY17 driven upgrade)
Description
East Sayre Substation: Replace one (1) 115 kV circuit breaker on North Waverly (NYSEG) terminal at East Sayre. Revise wiring for the North Waverly 115kV PR and BU line protection relays to utilize the redundant CT’s and trip coils on the new breaker. East Sayre – North Waverly 115kV line: Replace 3 pole wood Structure 141 due to NYSEG reconductor of East Sayre-North Waverly 115kV line. Enable load encroachment such that all protection elements will achieve the required loadability of 221/263/263/301 MVA (SN/SE/WN/WE) Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal is still limiting. Once the scope of work and ratings at East Sayre are finalized, the expected line ratings will be updated. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$1,417,388
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AH1-690 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-690 could receive cost allocation. Although AH1-690 may not presently have cost responsibility for this upgrade, AH1-690 may need this upgrade in-service to be deliverable to the PJM system. If AH1-690 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)

          New AG2-165 765kV swyd - AEP: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-165, AG2-212, AG2-328
        
          Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-660, AH1-044, AH1-150, AH1-151
        
          Powerton ;B 345 kV  (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-363, AG2-364
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        

Attachments

AH1-690 One Line Diagram

AH1-690 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.