AH1-696 Phase I Study Report

v1.00 released 2025-10-29 21:46

Possum Point 230kV

94.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Prince William County, Virginia. This project is an increase to the developer’s AA2-079 project(s), which will share the same Point of Interconnection. The AH1-696 project is a 0.0 MW uprate (94.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 668.0 MW with 94.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-696
Project Name:
Possum Point 230kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Prince William
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
668.0
MWE:
0.0
MWC:
94.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-696 will interconnect on the Virginia Electric and Power Company (Dominion Virginia Power) transmission system at the Possum Point 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-696 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-696Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-696

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-696 Project due at DP1
ABA - B
AH1-696$0$376,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AH1-696 is sharing a POI and the TOIF with AA2-079, so there are no associated interconnection costs for this project.$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-696 was evaluated as a 0.0 MW (94.0 MW Capacity) injection in the Dominion area.

AH1-696 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 668.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC152.59 %1331.98B2032.499.03
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC146.61 %1417.0B2077.468.57
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC146.6 %1417.0B2077.398.57
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC145.68 %1417.0B2064.298.4
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC140.29 %1417.0B1987.895.63
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC131.46 %1417.0B1862.726.7
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC109.83 %1331.98B1462.935.5
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P7-1: LN 514-2098_SRT-S
TowerAC104.66 %1417.0B1482.996.24
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC140.61 %1478.62B2079.099.03
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC117.42 %1809.0C2124.158.57
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC117.42 %1809.0C2124.088.57
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC116.69 %1809.0C2110.998.4
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC112.48 %1809.0C2034.785.63
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC105.55 %1809.0C1909.416.7
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC102.09 %1478.62B1509.535.5
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.0717.61
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC114.93 %3099.0B3561.8317.6
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC107.21 %3099.0B3322.4215.41
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC105.05 %2913.06B3060.2115.37
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
PEPCO_P4_PP41_SRT-A
BreakerAC103.72 %3099.0B3214.4115.44

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.59 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:2032.49
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
3150021OMF B
50/50
0.216
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
963691AG1-221 GEN
Solar/Wind Harmer
2.312
972199AH1-684 GEN
Adder
1.903
3150371LDYSMT1
Adder
12.251
971781AH1-399 GEN
Solar/Wind Harmer
0.118
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
0.028
970133AG2-095 GEN
Solar/Wind Harmer
0.794
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
3147043LAWRENC
Solar/Wind Harmer
0.044
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
972255AH1-712 GEN
Adder
36.775
959311AF2-222 GEN
Solar/Wind Harmer
6.376
316131AB2-060 GEN
Solar/Wind Harmer
0.224
315724AD1-057 GEN
Solar/Wind Harmer
0.266
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316283AC2-100 C
Solar/Wind Harmer
0.124
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
3152111X4-039 GT1
50/50
1.838
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3132273ORANGE
Solar/Wind Harmer
0.018
316156AD2-030 GEN
Solar/Wind Harmer
0.063
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
0.012
944581AF1-123 GEN
Solar/Wind Harmer
18.149
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.587
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.026
970221AG2-151 GEN
Solar/Wind Harmer
3.817
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
50/50
9.026
3141346CRANES
50/50
0.127
971685AH1-345 GEN
Solar/Wind Harmer
0.73
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.87
3143526WINTERP
Solar/Wind Harmer
0.435
944631AF1-128 GEN
Adder
39.853
971317AH1-138 GEN
Solar/Wind Harmer
0.618
315671AE2-027_GEN
Solar/Wind Harmer
5.273
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.166
940641AE2-051 GEN
Solar/Wind Harmer
6.396
3143336POWHATN
Solar/Wind Harmer
1.412
971547AH1-271 GEN
Solar/Wind Harmer
1.606
960081AF2-299 GEN
Solar/Wind Harmer
0.714
962571AG1-106 GEN
Solar/Wind Harmer
1.046
3145823KELFORD
Solar/Wind Harmer
0.073
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
972277AH1-723 GEN
Adder
42.854
316129AC1-054 GEN
Solar/Wind Harmer
0.27
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
0.404
3147983MERCK5
Solar/Wind Harmer
0.024
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
3140676OCCOQUN
50/50
0.286
3150281M RUN A
Adder
13.357
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
3147666LOUISA
Solar/Wind Harmer
0.355
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
0.008
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.084
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
316388AE2-253 GEN
Solar/Wind Harmer
0.251
316246AF1-032 C
Solar/Wind Harmer
0.036
3130156CHOWAN
Solar/Wind Harmer
0.078
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970087AG2-069 GEN
Solar/Wind Harmer
5.999
957481AF2-042 GEN
Solar/Wind Harmer
19.771
316190AA2-174 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.044
971563AH1-280 GEN
Solar/Wind Harmer
0.77
970685AG2-442 GEN
Solar/Wind Harmer
5.37
3146293MARTNCO
Solar/Wind Harmer
0.067
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3146233WITAKRS
Solar/Wind Harmer
0.278
3145493TOT1
Solar/Wind Harmer
0.31
316049AB1-081 GEN
Solar/Wind Harmer
0.395
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150011OMF A
50/50
0.216
970467AG2-304 GEN
50/50
14.788
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
972197AH1-683 GEN
Adder
1.98
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
316192AB2-158 GEN
Solar/Wind Harmer
0.501
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.08
316336AC2-165 C
Solar/Wind Harmer
0.003
3145663CRESWEL
Solar/Wind Harmer
0.215
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
316023GEN1_S
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.075
3145683EARLEYS
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3147043LAWRENC
Adder
0.664
315722AD1-056 GEN
Solar/Wind Harmer
0.448
3146083TARBORO
Solar/Wind Harmer
0.07
316359AB2-059 GEN
Solar/Wind Harmer
0.248
3142053HEARTS
Solar/Wind Harmer
0.122
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
3150091POSSM6B
50/50
0.848
970317AG2-208 GEN
Solar/Wind Harmer
3.609
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
971223AH1-071 GEN
Solar/Wind Harmer
0.89
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
971741AH1-377 GEN
Solar/Wind Harmer
7.304
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
971489AH1-241 GEN
Solar/Wind Harmer
3.817
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145453TOT5
Solar/Wind Harmer
0.097
961601AG1-000A GEN
Solar/Wind Harmer
1.228
964791AG1-342 GEN
Solar/Wind Harmer
1.322
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.443
946751AF1-339 GEN
Solar/Wind Helper
0.233
316447AC1-158 HLD
Solar/Wind Harmer
1.014
315651AD1-115 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
3.895
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
1.416
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
970933AG2-581 GEN
Solar/Wind Harmer
6.107
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
316274AC1-208 GEN
Solar/Wind Harmer
0.372
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
970053AG2-049 GEN
50/50
2.022
3150381LDYSMT2
Adder
12.172
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.219
315814AE2-033 C
Solar/Wind Harmer
6.204
3146206CASHIE
Solar/Wind Harmer
0.075
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
961791AG1-021 GEN
Solar/Wind Harmer
0.693
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3150071POSSM 5
50/50
52.224
3150391LDYSMT3
Adder
12.655
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
0.435
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
0.657
972185AH1-677 GEN
Adder
4.331
970099AG2-077 GEN
Solar/Wind Harmer
7.908
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
316034AC1-036 C
Solar/Wind Harmer
0.005
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
316263AC1-034 GEN
Solar/Wind Harmer
2.624
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
970327AG2-215 GEN
Solar/Wind Harmer
2.824
3141913WHIT STONE
Solar/Wind Harmer
0.085
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
971285AH1-108 GEN
Adder
0.631
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316315AB2-025 C
Solar/Wind Harmer
0.064
941031AE2-094 GEN
Solar/Wind Harmer
14.412
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
971447AH1-217 GEN
Solar/Wind Harmer
2.163
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
3.032
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3148133STUARTS
Solar/Wind Harmer
0.039
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
972289AH1-729 GEN
50/50
13.249
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
972195AH1-682 GEN
Adder
1.663
315673AE1-157 GEN
Solar/Wind Harmer
6.396
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.599
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
0.005
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3130086AYDLETT
Solar/Wind Harmer
0.32
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.138
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145493TOT1
Solar/Wind Harmer
0.162
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.042
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
972213AH1-691 GEN
Adder
2.059
944491AF1-114 GEN
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.467
3138133OCRAN
Solar/Wind Harmer
0.025
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
3143873LANEXA
Solar/Wind Harmer
0.051
971281AH1-106 GEN
Solar/Wind Harmer
1.161
316369SG1_INVT
Solar/Wind Harmer
0.003
3143316POE
Solar/Wind Harmer
0.321
319010AE1-072 C
Solar/Wind Harmer
0.403
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
970601AG2-382 GEN
Solar/Wind Harmer
2.811
970581AG2-369 GEN
Solar/Wind Harmer
3.44
316087AB2-174 GEN
Solar/Wind Harmer
0.002
972205AH1-687 GEN
Adder
3.134
3146033SCOT NK
Solar/Wind Harmer
0.29
970181AG2-120 GEN
Solar/Wind Harmer
0.883
3148013FISHERV
Solar/Wind Harmer
0.037
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.162
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
3150101POSSM6S
50/50
1.296
3150301M RUN C
Adder
13.349
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3141906WESTMOR
Solar/Wind Harmer
0.036
3147666LOUISA
Solar/Wind Harmer
0.204
316404AE1-155 C
Solar/Wind Harmer
0.019
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
4.984
965281AG1-393 GEN
Solar/Wind Harmer
0.877
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
316405AF2-144 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.079
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
970917AG2-570 GEN
Solar/Wind Harmer
6.681
961681AG1-008 GEN
Solar/Wind Harmer
5.587
962331AG1-082 GEN
Solar/Wind Harmer
0.795
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3146926FARMVIL
Solar/Wind Harmer
0.044
3138216PACIFIC
Solar/Wind Harmer
0.025
3150411LDYSMT5
Adder
12.718
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
316223AC1-118
Solar/Wind Harmer
0.064
3141813NORNECK
Solar/Wind Harmer
0.087
962981AG1-147 GEN
Solar/Wind Harmer
3.203
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
971167AH1-042 GEN
Solar/Wind Harmer
7.477
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971283AH1-107 GEN
Solar/Wind Harmer
1.161
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.01
944011AF1-069 GEN
Solar/Wind Harmer
4.709
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
316005AA1-067
Solar/Wind Harmer
0.076
316118AC1-105 GEN
Solar/Wind Harmer
0.176
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
3150151POSSMC1
50/50
1.143
316006AB2-029 C
Solar/Wind Harmer
0.001
316045AC1-158 PL2
Solar/Wind Harmer
1.475
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
3146776BUCKING
Solar/Wind Harmer
0.029
316174AB2-169 GEN
Solar/Wind Harmer
0.002
963171AG1-166 GEN
Solar/Wind Harmer
0.385
316494AC1-189 GEN
Solar/Wind Harmer
0.238
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
23779801AA1-109
Solar/Wind Helper
0.218
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
315747AE2-019 GEN
50/50
13.176
3150081POSSM6A
50/50
0.848
972217AH1-693 GEN
50/50
1.756
3141196NOKESVL
Solar/Wind Harmer
0.429
3141316ARNOLDS
Adder
0.229
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
315778AD1-151 GEN
Solar/Wind Harmer
6.579
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
17.869
316258AE1-075 C
Solar/Wind Harmer
0.06
3143336POWHATN
Solar/Wind Harmer
1.2
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
971193AH1-056 GEN
Solar/Wind Harmer
4.404
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
964241AG1-285 GEN
Solar/Wind Harmer
4.753
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
970257AG2-171 GEN
Solar/Wind Harmer
2.293
315785AD2-033 C
Solar/Wind Harmer
0.582
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3148013FISHERV
Solar/Wind Harmer
0.065
315616AA1-038_C
Solar/Wind Harmer
0
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.139
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
3148463FAIRFLD
Solar/Wind Harmer
0.06
960921AF2-383 GEN
Solar/Wind Helper
0.279
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
CPLELTFEXP_CPLE->PJM
CLTF
5.065
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.449

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.61 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.46
MW Contribution:8.57
Bus #Bus NameTypeMW Contribution
970317AG2-208 GEN
Solar/Wind Harmer
4.491
3151721LOISA A
Adder
5.569
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
3150071POSSM 5
Adder
49.581
3150391LDYSMT3
Adder
12.669
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
316441AF1-014 GEN
Solar/Wind Harmer
0.641
316075AC2-137 C
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3144356SAPONY
Solar/Wind Harmer
0.308
972185AH1-677 GEN
Adder
4.33
970099AG2-077 GEN
Solar/Wind Harmer
10.411
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
972201AH1-685 GEN
Adder
2.15
972197AH1-683 GEN
Adder
1.982
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
971223AH1-071 GEN
Solar/Wind Harmer
1.172
316240AF1-291 C
Solar/Wind Harmer
0.279
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
3150151POSSMC1
Adder
1.085
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
315693AD1-088 GEN
Solar/Wind Harmer
1.373
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
Adder
8.569
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.427
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.856
971317AH1-138 GEN
Solar/Wind Harmer
1.163
315671AE2-027_GEN
Solar/Wind Harmer
6.943
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
939411AE1-173 GEN
Solar/Wind Harmer
44.981
972213AH1-691 GEN
Adder
2.061
944491AF1-114 GEN
Solar/Wind Harmer
3.051
972189AH1-679 GEN
Adder
1.468
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.528
316369SG1_INVT
Solar/Wind Harmer
1.648
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
316314AB2-024 C
Solar/Wind Harmer
0.813
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316315AB2-025 C
Solar/Wind Harmer
0.238
941031AE2-094 GEN
Solar/Wind Harmer
16.483
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
970053AG2-049 GEN
50/50
2.027
3150381LDYSMT2
Adder
12.185
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.215
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.205
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
316447AC1-158 HLD
Solar/Wind Harmer
2.295
315651AD1-115 GEN
Solar/Wind Harmer
4.661
957411AF2-035 GEN
Solar/Wind Harmer
4.619
958261AF2-120 GEN
Solar/Wind Harmer
3.769
316487AF1-042 GEN
Solar/Wind Harmer
1.275
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3146456SLIGO L269
Solar/Wind Harmer
1.062
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
970933AG2-581 GEN
Solar/Wind Harmer
8.04
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.158
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
315683AE1-153 C
Solar/Wind Harmer
9.501
316192AB2-158 GEN
Solar/Wind Harmer
1.185
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
3150301M RUN C
Adder
13.346
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.876
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.354
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.598
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.833
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
316388AE2-253 GEN
Solar/Wind Harmer
0.608
316246AF1-032 C
Solar/Wind Harmer
0.182
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970087AG2-069 GEN
Solar/Wind Harmer
7.898
957481AF2-042 GEN
Solar/Wind Harmer
26.028
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3152111X4-039 GT1
50/50
1.839
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
316223AC1-118
Solar/Wind Harmer
0.272
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
957601AF2-054 GEN
Solar/Wind Harmer
0.285
315666AE1-190 GEN
Solar/Wind Harmer
0.287
971167AH1-042 GEN
Solar/Wind Harmer
9.109
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.528
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.271
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.165
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
972193AH1-681 GEN
Adder
1.643
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.436
316156AD2-030 GEN
Solar/Wind Harmer
0.254
316203AE2-005 GEN
Solar/Wind Harmer
4.009
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.196
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.644
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.645
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
963691AG1-221 GEN
Solar/Wind Harmer
2.313
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.264
966881AG1-559 GEN
Solar/Wind Harmer
0.309
971781AH1-399 GEN
Solar/Wind Harmer
0.62
970009AG2-005 GEN
Solar/Wind Harmer
1.21
316473AC1-191 GEN
Solar/Wind Harmer
1.04
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.046
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
972255AH1-712 GEN
Adder
36.766
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
972289AH1-729 GEN
50/50
13.252
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
972195AH1-682 GEN
Adder
1.665
315673AE1-157 GEN
Solar/Wind Harmer
7.8
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.598
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
2.975
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
970581AG2-369 GEN
Solar/Wind Harmer
4.528
946281AF1-292 GEN
Solar/Wind Harmer
0.187
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970129AG2-093 GEN
Solar/Wind Harmer
5.216
965281AG1-393 GEN
Solar/Wind Harmer
1.155
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
970917AG2-570 GEN
Solar/Wind Harmer
21.109
961681AG1-008 GEN
Solar/Wind Harmer
6.644
962331AG1-082 GEN
Solar/Wind Harmer
1.047
313506AB2-031 GEN
Solar/Wind Harmer
0.667
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.442
946751AF1-339 GEN
Solar/Wind Helper
0.233
315747AE2-019 GEN
50/50
13.179
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
3141316ARNOLDS
Adder
0.23
3150351NORNECKC2
Adder
0.885
3151761LOISA E
Adder
11.412
972183AH1-676 GEN
Adder
92.015
315778AD1-151 GEN
Solar/Wind Harmer
8.005
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
40.553
316258AE1-075 C
Solar/Wind Harmer
0.217
3143336POWHATN
Solar/Wind Harmer
0.9
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3144293JTRSVLE
Adder
0.23
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.139
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
940641AE2-051 GEN
Solar/Wind Harmer
8.42
3143336POWHATN
Solar/Wind Harmer
1.059
971547AH1-271 GEN
Solar/Wind Harmer
2.115
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.448
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
CPLELTFEXP_CPLE->PJM
CLTF
5.064
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.39
MW Contribution:8.57
Bus #Bus NameTypeMW Contribution
3150071POSSM 5
Adder
49.613
3150391LDYSMT3
Adder
12.67
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
316441AF1-014 GEN
Solar/Wind Harmer
0.641
316075AC2-137 C
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3150151POSSMC1
Adder
1.085
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
315693AD1-088 GEN
Solar/Wind Harmer
1.373
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
316314AB2-024 C
Solar/Wind Harmer
0.813
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
970053AG2-049 GEN
50/50
2.028
3150381LDYSMT2
Adder
12.186
316447AC1-158 HLD
Solar/Wind Harmer
2.294
315651AD1-115 GEN
Solar/Wind Harmer
4.661
957411AF2-035 GEN
Solar/Wind Harmer
4.62
958261AF2-120 GEN
Solar/Wind Harmer
3.769
316487AF1-042 GEN
Solar/Wind Harmer
1.275
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3146456SLIGO L269
Solar/Wind Harmer
1.062
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
970933AG2-581 GEN
Solar/Wind Harmer
8.04
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.158
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
972197AH1-683 GEN
Adder
1.982
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
316192AB2-158 GEN
Solar/Wind Harmer
1.185
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.354
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.597
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.833
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
316388AE2-253 GEN
Solar/Wind Harmer
0.608
316246AF1-032 C
Solar/Wind Harmer
0.182
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970087AG2-069 GEN
Solar/Wind Harmer
7.898
957481AF2-042 GEN
Solar/Wind Harmer
26.028
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
316223AC1-118
Solar/Wind Harmer
0.272
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
957601AF2-054 GEN
Solar/Wind Harmer
0.285
315666AE1-190 GEN
Solar/Wind Harmer
0.287
971167AH1-042 GEN
Solar/Wind Harmer
9.109
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.528
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.271
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.164
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
972193AH1-681 GEN
Adder
1.643
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
3152111X4-039 GT1
50/50
1.839
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3150331BIRCHWDA
Adder
16.699
3150291M RUN B
Adder
13.246
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.436
316156AD2-030 GEN
Solar/Wind Harmer
0.254
316203AE2-005 GEN
Solar/Wind Harmer
4.009
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.195
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.644
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.645
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
963691AG1-221 GEN
Solar/Wind Harmer
2.313
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.265
966881AG1-559 GEN
Solar/Wind Harmer
0.309
971781AH1-399 GEN
Solar/Wind Harmer
0.62
970009AG2-005 GEN
Solar/Wind Harmer
1.21
316473AC1-191 GEN
Solar/Wind Harmer
1.04
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.046
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
972255AH1-712 GEN
Adder
36.765
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
972289AH1-729 GEN
50/50
13.252
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
972195AH1-682 GEN
Adder
1.665
315673AE1-157 GEN
Solar/Wind Harmer
7.801
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.597
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
2.975
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
972213AH1-691 GEN
Adder
2.061
944491AF1-114 GEN
Solar/Wind Harmer
3.051
972189AH1-679 GEN
Adder
1.468
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.528
316369SG1_INVT
Solar/Wind Harmer
1.648
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
970601AG2-382 GEN
Solar/Wind Harmer
3.701
970581AG2-369 GEN
Solar/Wind Harmer
4.528
946281AF1-292 GEN
Solar/Wind Harmer
0.187
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
3150301M RUN C
Adder
13.346
3150401LDYSMT4
Adder
12.694
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.876
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970129AG2-093 GEN
Solar/Wind Harmer
5.216
965281AG1-393 GEN
Solar/Wind Harmer
1.155
961611AG1-000B GEN
Solar/Wind Harmer
1.935
970317AG2-208 GEN
Solar/Wind Harmer
4.491
3151721LOISA A
Adder
5.568
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
971223AH1-071 GEN
Solar/Wind Harmer
1.172
316240AF1-291 C
Solar/Wind Harmer
0.279
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.442
946751AF1-339 GEN
Solar/Wind Helper
0.233
315747AE2-019 GEN
50/50
13.179
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
3141316ARNOLDS
Adder
0.23
3150351NORNECKC2
Adder
0.885
3151761LOISA E
Adder
11.411
972183AH1-676 GEN
Adder
92.013
315778AD1-151 GEN
Solar/Wind Harmer
8.005
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
40.552
316258AE1-075 C
Solar/Wind Harmer
0.217
3143336POWHATN
Solar/Wind Harmer
0.9
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3144293JTRSVLE
Adder
0.23
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
Adder
8.574
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.427
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.856
971317AH1-138 GEN
Solar/Wind Harmer
1.163
315671AE2-027_GEN
Solar/Wind Harmer
6.943
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
939411AE1-173 GEN
Solar/Wind Harmer
44.98
940641AE2-051 GEN
Solar/Wind Harmer
8.42
3143336POWHATN
Solar/Wind Harmer
1.059
971547AH1-271 GEN
Solar/Wind Harmer
2.115
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
970917AG2-570 GEN
Solar/Wind Harmer
21.109
961681AG1-008 GEN
Solar/Wind Harmer
6.644
962331AG1-082 GEN
Solar/Wind Harmer
1.047
313506AB2-031 GEN
Solar/Wind Harmer
0.667
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233952AC2-187 GEN
Solar/Wind Helper
0.139
233940AF2-379 C
Solar/Wind Helper
0.037
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.215
3142433PROV 92
Adder
0.164
3144356SAPONY
Solar/Wind Harmer
0.308
972185AH1-677 GEN
Adder
4.33
970099AG2-077 GEN
Solar/Wind Harmer
10.411
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316315AB2-025 C
Solar/Wind Harmer
0.238
941031AE2-094 GEN
Solar/Wind Harmer
16.482
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.205
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.448
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
CPLELTFEXP_CPLE->PJM
CLTF
5.064
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.68 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2064.29
MW Contribution:8.4
Bus #Bus NameTypeMW Contribution
3150151POSSMC1
Adder
1.063
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.331
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
972197AH1-683 GEN
Adder
1.961
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
316192AB2-158 GEN
Solar/Wind Harmer
1.181
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.521
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.301
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.081
217208PARK ELE C
Solar/Wind Helper
0.003
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.376
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.583
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.429
3143096IRON208
Adder
0.349
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.596
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
316223AC1-118
Solar/Wind Harmer
0.269
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
957601AF2-054 GEN
Solar/Wind Harmer
0.282
315666AE1-190 GEN
Solar/Wind Harmer
0.284
971167AH1-042 GEN
Solar/Wind Harmer
9.035
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971283AH1-107 GEN
Solar/Wind Harmer
1.517
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
972265AH1-717 GEN
Adder
6.291
3151191GRAVEL3
Adder
5.822
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.131
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
972193AH1-681 GEN
Adder
1.633
3151861LOWMORA
Adder
0.618
205956AE1-196_GEN
Solar/Wind Helper
0.384
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
3152111X4-039 GT1
50/50
1.841
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.414
316156AD2-030 GEN
Solar/Wind Harmer
0.252
316203AE2-005 GEN
Solar/Wind Harmer
3.975
316159AE1-175 C
Solar/Wind Harmer
0.248
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
316381AD1-082 GEN
Solar/Wind Harmer
0.827
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
972289AH1-729 GEN
50/50
13.276
3150181POSSMC2
Adder
1.072
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3150681DARBY 2
Adder
6.001
316033AB2-134 GEN
Solar/Wind Harmer
2.953
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.297
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.177
209137AF2-361 C
Solar/Wind Helper
0.706
972213AH1-691 GEN
Adder
2.039
944491AF1-114 GEN
Solar/Wind Harmer
3.014
972189AH1-679 GEN
Adder
1.455
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.517
316369SG1_INVT
Solar/Wind Harmer
1.636
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.806
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
970601AG2-382 GEN
Solar/Wind Harmer
3.676
970581AG2-369 GEN
Solar/Wind Harmer
4.499
946281AF1-292 GEN
Solar/Wind Harmer
0.186
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.386
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.564
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
238208AF1-136 C
Solar/Wind Helper
0.089
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3150921YORKTN3
Adder
2.053
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.904
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.6
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.643
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233997TMININ_4.2
Solar/Wind Helper
0.156
233971AC1-093 C
Solar/Wind Helper
0.213
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.233
970317AG2-208 GEN
Solar/Wind Harmer
4.447
3151721LOISA A
Adder
5.554
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
3150671DARBY 1
Adder
5.994
971223AH1-071 GEN
Solar/Wind Harmer
1.164
316240AF1-291 C
Solar/Wind Harmer
0.277
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.17
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.204
237001AB1-127_GEN
Solar/Wind Helper
0.306
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
972223AH1-696 GEN
Adder
8.401
3141346CRANES
Adder
0.118
971685AH1-345 GEN
Solar/Wind Harmer
0.962
972219AH1-694 GEN
Adder
1.412
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3143526WINTERP
Solar/Wind Harmer
-0.048
944631AF1-128 GEN
Adder
39.551
971317AH1-138 GEN
Solar/Wind Harmer
1.154
315671AE2-027_GEN
Solar/Wind Harmer
6.892
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.674
940641AE2-051 GEN
Solar/Wind Harmer
8.364
3143336POWHATN
Solar/Wind Harmer
1.052
971547AH1-271 GEN
Solar/Wind Harmer
2.101
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
233930AB2-032 GEN
Solar/Wind Helper
0.229
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.016
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.232
3150301M RUN C
Adder
13.368
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.859
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
3141843SHACKLE
Adder
0.429
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970129AG2-093 GEN
Solar/Wind Harmer
5.177
965281AG1-393 GEN
Solar/Wind Harmer
1.147
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151171GRAVELC
Adder
1.133
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
970917AG2-570 GEN
Solar/Wind Harmer
20.974
961681AG1-008 GEN
Solar/Wind Harmer
6.6
962331AG1-082 GEN
Solar/Wind Harmer
1.04
313506AB2-031 GEN
Solar/Wind Harmer
0.663
235067AD1-061 GEN
Solar/Wind Helper
0.311
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.241
961331AF2-424 GEN
Solar/Wind Helper
0.236
316388AE2-253 GEN
Solar/Wind Harmer
0.603
316246AF1-032 C
Solar/Wind Harmer
0.181
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970087AG2-069 GEN
Solar/Wind Harmer
7.848
957481AF2-042 GEN
Solar/Wind Harmer
25.866
223401AF1-299 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.061
233915AB1-141 GEN
Solar/Wind Helper
0.302
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
233972AC1-094 C
Solar/Wind Helper
0.18
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.897
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
235063AE1-101 C2
Solar/Wind Helper
1.061
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.441
946751AF1-339 GEN
Solar/Wind Helper
0.232
963691AG1-221 GEN
Solar/Wind Harmer
2.318
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
3150371LDYSMT1
Adder
12.133
966881AG1-559 GEN
Solar/Wind Harmer
0.306
971781AH1-399 GEN
Solar/Wind Harmer
0.614
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.038
3151221GRAVEL6
Adder
5.89
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
972255AH1-712 GEN
Adder
36.554
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.156
232406W1-004 FULL
Solar/Wind Helper
0.303
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.78
209067AE2-060 GEN
Solar/Wind Helper
0.042
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
957411AF2-035 GEN
Solar/Wind Harmer
4.574
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3146456SLIGO L269
Solar/Wind Harmer
1.055
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
7.988
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.151
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
315747AE2-019 GEN
50/50
13.211
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.657
3141316ARNOLDS
Adder
0.227
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
315778AD1-151 GEN
Solar/Wind Harmer
7.946
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
3151101ELIZAR3
Adder
7.435
944601AF1-125 GEN
Solar/Wind Harmer
40.266
316258AE1-075 C
Solar/Wind Harmer
0.215
3143336POWHATN
Solar/Wind Harmer
0.895
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3144293JTRSVLE
Adder
0.228
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.396
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.215
233952AC2-187 GEN
Solar/Wind Helper
0.139
233940AF2-379 C
Solar/Wind Helper
0.037
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.555
961421AF2-433 GEN
Solar/Wind Helper
0.235
946691AF1-333 GEN
Solar/Wind Helper
0.232
946741AF1-338 GEN
Solar/Wind Helper
0.232
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.232
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.609
3150851SPRUNCC
Adder
0.383
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.236
212507AE2-042_GEN
Solar/Wind Helper
0.826
315693AD1-088 GEN
Solar/Wind Harmer
1.364
3150071POSSM 5
Adder
48.607
3150391LDYSMT3
Adder
12.533
316468AD1-105 GEN
Solar/Wind Harmer
1.109
316077AC2-138 C
Solar/Wind Harmer
0.205
316441AF1-014 GEN
Solar/Wind Harmer
0.636
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
944641AF1-129 GEN
Adder
39.124
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3144356SAPONY
Solar/Wind Harmer
0.306
972185AH1-677 GEN
Adder
4.302
970099AG2-077 GEN
Solar/Wind Harmer
10.347
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
205916AD1-020 GEN
Solar/Wind Helper
1.477
20390526W1-045 C
Solar/Wind Helper
0.251
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
233946AB2-136 GEN
Solar/Wind Helper
0.34
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.096
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.235
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
957871AF2-081 GEN
Solar/Wind Harmer
4.471
316315AB2-025 C
Solar/Wind Harmer
0.237
941031AE2-094 GEN
Solar/Wind Harmer
16.374
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
237085AD2-009_GEN
Solar/Wind Helper
0.968
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.001
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
970053AG2-049 GEN
50/50
2.02
3150381LDYSMT2
Adder
12.055
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.213
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
3151201GRAVEL4
Adder
5.897
3151211GRAVEL5
Adder
5.822
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.149
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.209
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
203975AE1-071-GEN
Solar/Wind Helper
1.709
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
NYPJM->LTFIMP_NY
CLTF
2.566
TVALTFEXP_TVA->PJM
CLTF
3.177
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
WECLTFEXP_WEC->PJM
CLTF
0.96
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853
LGEELTFEXP_LGEE->PJM
CLTF
1.801
MECLTFEXP_MEC->PJM
CLTF
4.438
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
CPLELTFEXP_CPLE->PJM
CLTF
5.037
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.29 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1987.89
MW Contribution:5.63
Bus #Bus NameTypeMW Contribution
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
315683AE1-153 C
Solar/Wind Harmer
8.082
316192AB2-158 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.435
966881AG1-559 GEN
Solar/Wind Harmer
0.078
972135AH1-637 GEN
Solar/Wind Harmer
0.75
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.029
972289AH1-729 GEN
50/50
13.169
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
3150681DARBY 2
Adder
4.634
316033AB2-134 GEN
Solar/Wind Harmer
2.301
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
3147346CASHSCORNER
Solar/Wind Harmer
0.123
972213AH1-691 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
972189AH1-679 GEN
Adder
1.104
971281AH1-106 GEN
Solar/Wind Harmer
1.184
3138133OCRAN
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
3141873WAN 176
Solar/Wind Harmer
-0.001
316369SG1_INVT
Solar/Wind Harmer
1.275
3143316POE
Solar/Wind Harmer
-0.028
319010AE1-072 C
Solar/Wind Harmer
1.418
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3152111X4-039 GT1
50/50
1.829
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.713
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
971685AH1-345 GEN
Solar/Wind Harmer
0.837
972223AH1-696 GEN
Adder
5.63
3141346CRANES
Adder
0.082
972219AH1-694 GEN
Adder
1.033
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3143526WINTERP
Solar/Wind Harmer
-0.038
944631AF1-128 GEN
Adder
30.629
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
3143336POWHATN
Solar/Wind Harmer
0.841
944591AF1-124 GEN
Solar/Wind Harmer
32.182
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
971547AH1-271 GEN
Solar/Wind Harmer
1.673
972277AH1-723 GEN
Adder
35.15
3144293JTRSVLE
Adder
0.186
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.14
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
3150301M RUN C
Adder
11.698
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3147666LOUISA
Solar/Wind Harmer
-0.018
3150401LDYSMT4
Adder
9.192
3141906WESTMOR
Solar/Wind Harmer
-0.003
316404AE1-155 C
Solar/Wind Harmer
1.411
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3150861SPRUNCD
Adder
0.297
316280AD1-041 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
316382AG1-145 C
Solar/Wind Harmer
0.216
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151171GRAVELC
Adder
0.885
316405AF2-144 C
Solar/Wind Harmer
0.182
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
3146926FARMVIL
Solar/Wind Harmer
-0.004
961681AG1-008 GEN
Solar/Wind Harmer
5.262
235067AD1-061 GEN
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
3150281M RUN A
Adder
11.705
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
3147666LOUISA
Solar/Wind Harmer
-0.032
3151751LOISA D
Adder
4.652
957971AF2-091 GEN
Solar/Wind Harmer
0.75
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.193
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
316381AD1-082 GEN
Solar/Wind Harmer
0.648
3150981CHESPKA
Adder
0.784
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316388AE2-253 GEN
Solar/Wind Harmer
0.474
316246AF1-032 C
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
-0.007
971163AH1-040 GEN
Solar/Wind Harmer
6.359
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146926FARMVIL
Solar/Wind Harmer
-0.004
223401AF1-299 GEN
Solar/Wind Helper
0.385
235062AE1-101 C1
Solar/Wind Helper
1.169
233915AB1-141 GEN
Solar/Wind Helper
0.304
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.893
212266LOR1
Solar/Wind Helper
0.025
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.239
961331AF2-424 GEN
Solar/Wind Helper
0.233
3151721LOISA A
Adder
4.628
970317AG2-208 GEN
Solar/Wind Harmer
3.309
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.207
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3150671DARBY 1
Adder
4.629
316240AF1-291 C
Solar/Wind Harmer
0.216
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
971761AH1-387 GEN
Solar/Wind Harmer
3.885
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
972187AH1-678 GEN
Adder
1.728
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
971741AH1-377 GEN
Solar/Wind Harmer
7.747
237034AC2-136 C
Solar/Wind Helper
0.239
237001AB1-127_GEN
Solar/Wind Helper
0.342
226929AD2-058 GEN
Solar/Wind Helper
0.078
235063AE1-101 C2
Solar/Wind Helper
1.169
233987AB2-037 GEN
Solar/Wind Helper
1.409
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.187
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
209029WAYMART-WD
Solar/Wind Helper
0.437
946751AF1-339 GEN
Solar/Wind Helper
0.23
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
970737AG2-469 GEN
Solar/Wind Harmer
3.736
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970293AG2-193 GEN
Solar/Wind Harmer
0.907
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3150921YORKTN3
Adder
1.597
316313AB2-026
Solar/Wind Harmer
0.191
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
32.067
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.262
205917AD1-020 ES
Solar/Wind Helper
0.357
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.23
963691AG1-221 GEN
Solar/Wind Harmer
2.26
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
3150371LDYSMT1
Adder
8.882
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.459
316473AC1-191 GEN
Solar/Wind Harmer
0.788
970009AG2-005 GEN
Solar/Wind Harmer
0.912
3142416OLDCHRC
Solar/Wind Harmer
0.734
3141766HARMONY
Solar/Wind Harmer
0.645
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.807
3151221GRAVEL6
Adder
4.598
315813AE1-149 C
Solar/Wind Harmer
4.431
3145336SMITFLD
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
237030AB1-096 C
Solar/Wind Helper
0.1
227287AC2-120 GEN
Solar/Wind Helper
0.309
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.305
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.773
209067AE2-060 GEN
Solar/Wind Helper
0.042
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.016
207437AD2-070 GEN
Solar/Wind Helper
0.078
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.23
315747AE2-019 GEN
50/50
12.54
3141196NOKESVL
Solar/Wind Harmer
-0.043
972217AH1-693 GEN
Adder
1.452
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3141316ARNOLDS
Adder
0.162
3150351NORNECKC2
Adder
0.662
315778AD1-151 GEN
Solar/Wind Harmer
6.188
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
316258AE1-075 C
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
0.715
3151101ELIZAR3
Adder
5.827
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3144293JTRSVLE
Adder
0.186
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
238221AF1-254 C O1
Solar/Wind Helper
0.197
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.14
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.55
961421AF2-433 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
957411AF2-035 GEN
Solar/Wind Harmer
3.403
958261AF2-120 GEN
Solar/Wind Harmer
2.834
316487AF1-042 GEN
Solar/Wind Harmer
0.961
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3146456SLIGO L269
Solar/Wind Harmer
0.828
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
237025AB1-124 C
Solar/Wind Helper
0.233
23777801MSM_W1-116
Solar/Wind Helper
0.156
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
3.335
237006AB1-125 GEN
Solar/Wind Helper
0.175
237002AB1-128_GEN
Solar/Wind Helper
0.33
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
23777901MDS_W4-102
Solar/Wind Helper
0.113
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.176
209137AF2-361 C
Solar/Wind Helper
0.703
970601AG2-382 GEN
Solar/Wind Harmer
2.928
205943AE1-185 GEN
Solar/Wind Helper
0.409
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
238208AF1-136 C
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3150411LDYSMT5
Adder
9.22
972215AH1-692 GEN
Adder
1.493
316223AC1-118
Solar/Wind Harmer
0.2
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971283AH1-107 GEN
Solar/Wind Harmer
1.184
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
971167AH1-042 GEN
Solar/Wind Harmer
6.965
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
972265AH1-717 GEN
Adder
4.91
3151191GRAVEL3
Adder
4.545
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
944011AF1-069 GEN
Solar/Wind Harmer
4.067
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970085AG2-068 GEN
Solar/Wind Harmer
4.185
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
205956AE1-196_GEN
Solar/Wind Helper
0.406
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
207530AG1-191 GEN
Solar/Wind Helper
0.037
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.229
316006AB2-029 C
Solar/Wind Harmer
0.549
316045AC1-158 PL2
Solar/Wind Harmer
2.734
3150151POSSMC1
Adder
0.713
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
3150851SPRUNCC
Adder
0.297
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
23779801AA1-109
Solar/Wind Helper
0.261
237038AE2-054 C
Solar/Wind Helper
0.19
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
3150071POSSM 5
Adder
32.578
3150391LDYSMT3
Adder
9.175
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3143526WINTERP
Solar/Wind Harmer
-0.038
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
944641AF1-129 GEN
Adder
30.436
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3144356SAPONY
Solar/Wind Harmer
0.242
972185AH1-677 GEN
Adder
3.421
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
205916AD1-020 GEN
Solar/Wind Helper
1.658
20390526W1-045 C
Solar/Wind Helper
0.277
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
233946AB2-136 GEN
Solar/Wind Helper
0.342
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.096
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.233
970099AG2-077 GEN
Solar/Wind Harmer
2.284
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
3141426STAFORD
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.245
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
957831AF2-077 GEN
Solar/Wind Harmer
0.216
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
957871AF2-081 GEN
Solar/Wind Harmer
3.509
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
237085AD2-009_GEN
Solar/Wind Helper
1.049
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.028
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
0.994
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
970053AG2-049 GEN
Adder
1.475
3150381LDYSMT2
Adder
8.824
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.164
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3151201GRAVEL4
Adder
4.603
3151211GRAVEL5
Adder
4.545
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146396TANGLEW
Solar/Wind Harmer
0.128
315814AE2-033 C
Solar/Wind Harmer
6.44
971845AH1-439 GEN
Solar/Wind Harmer
3.571
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.167
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205932AD2-116_GEN
Solar/Wind Helper
0.406
203975AE1-071-GEN
Solar/Wind Helper
1.871
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
316375AC2-012 GEN
Solar/Wind Harmer
2.44
316336AC2-165 C
Solar/Wind Harmer
1.222
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3145663CRESWEL
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.53
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.081
217208PARK ELE C
Solar/Wind Helper
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
NYPJM->LTFIMP_NY
CLTF
2.532
TVALTFEXP_TVA->PJM
CLTF
2.938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
WECLTFEXP_WEC->PJM
CLTF
0.941
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691
LGEELTFEXP_LGEE->PJM
CLTF
1.753
MECLTFEXP_MEC->PJM
CLTF
4.292
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
CPLELTFEXP_CPLE->PJM
CLTF
4.229
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.46 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1862.72
MW Contribution:6.7
Bus #Bus NameTypeMW Contribution
3150281M RUN A
Adder
13.444
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
3147666LOUISA
Solar/Wind Harmer
-0.038
3151751LOISA D
Adder
5.425
957971AF2-091 GEN
Solar/Wind Harmer
0.888
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138133OCRAN
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.389
3143096IRON208
Adder
0.319
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.227
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
3151171GRAVELC
Adder
0.794
316381AD1-082 GEN
Solar/Wind Harmer
0.765
3150981CHESPKA
Adder
0.925
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316388AE2-253 GEN
Solar/Wind Harmer
0.559
316246AF1-032 C
Solar/Wind Harmer
0.167
3130156CHOWAN
Solar/Wind Harmer
-0.008
971163AH1-040 GEN
Solar/Wind Harmer
7.509
970087AG2-069 GEN
Solar/Wind Harmer
7.409
3146926FARMVIL
Solar/Wind Harmer
-0.005
223401AF1-299 GEN
Solar/Wind Helper
0.379
233915AB1-141 GEN
Solar/Wind Helper
0.397
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233950AC2-186 GEN
Solar/Wind Helper
0.091
233972AC1-094 C
Solar/Wind Helper
0.238
228728W1-130C
Solar/Wind Helper
0.041
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
963711AG1-223 GEN
Solar/Wind Helper
0.048
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20675428EAM_W2-061
Solar/Wind Helper
0.012
207518AF1-320_GEN
Solar/Wind Helper
1.156
212266LOR1
Solar/Wind Helper
0.033
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
957481AF2-042 GEN
Solar/Wind Harmer
6.742
3150301M RUN C
Adder
13.435
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3147666LOUISA
Solar/Wind Harmer
-0.022
3150401LDYSMT4
Adder
10.874
3141906WESTMOR
Solar/Wind Harmer
-0.003
316404AE1-155 C
Solar/Wind Harmer
1.667
962971AG1-146 GEN
Solar/Wind Harmer
1.614
316280AD1-041 GEN
Solar/Wind Harmer
0.645
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
316382AG1-145 C
Solar/Wind Harmer
0.255
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151171GRAVELC
Adder
1.044
316405AF2-144 C
Solar/Wind Harmer
0.214
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
315737AD1-076 GEN
Solar/Wind Harmer
1.509
970917AG2-570 GEN
Solar/Wind Harmer
19.793
3146926FARMVIL
Solar/Wind Harmer
-0.005
961681AG1-008 GEN
Solar/Wind Harmer
6.214
3152541MT STMG
Adder
0.593
234015AF2-250 C
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.068
20720528MAN_W1-024
Solar/Wind Helper
0.021
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
963161AG1-165 GEN
Solar/Wind Helper
0.309
961331AF2-424 GEN
Solar/Wind Helper
0.302
235067AD1-061 GEN
Solar/Wind Helper
0.214
3151721LOISA A
Adder
5.397
970317AG2-208 GEN
Solar/Wind Harmer
3.912
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3150671DARBY 1
Adder
5.465
316240AF1-291 C
Solar/Wind Harmer
0.255
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
3152111X4-039 GT1
50/50
2.007
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150331BIRCHWDA
Adder
13.842
970737AG2-469 GEN
Solar/Wind Harmer
4.42
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970293AG2-193 GEN
Solar/Wind Harmer
1.071
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3150921YORKTN3
Adder
1.885
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
970659AG2-427 GEN
Solar/Wind Harmer
0.785
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
37.845
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
971157AH1-035 GEN
Solar/Wind Harmer
0.994
3146776BUCKING
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.214
3151861LOWMORA
Adder
0.674
205917AD1-020 ES
Solar/Wind Helper
0.322
233918AB1-142 GEN
Solar/Wind Helper
0.397
233994AC2-023 GEN
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.206
233971AC1-093 C
Solar/Wind Helper
0.281
228729W2-030 C
Solar/Wind Helper
0.085
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.043
219249CENTRALDIV C
Solar/Wind Helper
0.008
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.298
3142956BIRDNECK
Solar/Wind Harmer
0.446
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
971761AH1-387 GEN
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
2.039
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
971741AH1-377 GEN
Solar/Wind Harmer
9.144
237034AC2-136 C
Solar/Wind Helper
0.157
233987AB2-037 GEN
Solar/Wind Helper
1.847
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
20720628TIN_W1-124
Solar/Wind Helper
0.143
207442AE1-156 GEN
Solar/Wind Helper
0.243
20671828STAW2-080
Solar/Wind Helper
0.02
226929AD2-058 GEN
Solar/Wind Helper
0.066
20674128FR_U2-059
Solar/Wind Helper
0.003
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
209029WAYMART-WD
Solar/Wind Helper
0.566
946751AF1-339 GEN
Solar/Wind Helper
0.297
237001AB1-127_GEN
Solar/Wind Helper
0.221
235063AE1-101 C2
Solar/Wind Helper
0.747
963691AG1-221 GEN
Solar/Wind Harmer
2.52
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
971781AH1-399 GEN
Solar/Wind Harmer
0.543
316473AC1-191 GEN
Solar/Wind Harmer
0.931
970009AG2-005 GEN
Solar/Wind Harmer
1.078
3142416OLDCHRC
Solar/Wind Harmer
0.867
3141766HARMONY
Solar/Wind Harmer
0.762
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
0.953
3151221GRAVEL6
Adder
5.427
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
237030AB1-096 C
Solar/Wind Helper
0.073
227287AC2-120 GEN
Solar/Wind Helper
0.266
233996TM1833_GEN
Solar/Wind Helper
0.206
232406W1-004 FULL
Solar/Wind Helper
0.4
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219906AC1-017 C
Solar/Wind Helper
0.032
20720828JCB_W4-025
Solar/Wind Helper
0.048
20714528FRN_Y2-051
Solar/Wind Helper
0.043
218438BLK ROCK C
Solar/Wind Helper
0.02
219919AE1-041 FULL
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.066
963071AG1-156 GEN
Solar/Wind Helper
1.001
209067AE2-060 GEN
Solar/Wind Helper
0.051
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
971685AH1-345 GEN
Solar/Wind Harmer
0.963
972223AH1-696 GEN
Adder
6.699
3141346CRANES
Adder
0.098
972219AH1-694 GEN
Adder
1.223
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
315747AE2-019 GEN
50/50
14.059
3141196NOKESVL
Solar/Wind Harmer
-0.049
972217AH1-693 GEN
Adder
1.667
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3141316ARNOLDS
Adder
0.192
3150351NORNECKC2
Adder
0.783
315778AD1-151 GEN
Solar/Wind Harmer
7.304
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
316258AE1-075 C
Solar/Wind Harmer
0.203
3143336POWHATN
Solar/Wind Harmer
0.843
3151101ELIZAR3
Adder
6.877
944601AF1-125 GEN
Solar/Wind Harmer
37.254
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
957411AF2-035 GEN
Solar/Wind Harmer
4.024
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3146456SLIGO L269
Solar/Wind Harmer
0.977
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
237025AB1-124 C
Solar/Wind Helper
0.168
23777801MSM_W1-116
Solar/Wind Helper
0.11
230407AD2-065 C
Solar/Wind Helper
0.031
20714928UPF_X1-085
Solar/Wind Helper
0.004
218440SUMMTASSOC C
Solar/Wind Helper
0.012
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.059
209054AE2-059 GEN
Solar/Wind Helper
0.054
972289AH1-729 GEN
50/50
14.564
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
3150681DARBY 2
Adder
5.471
316033AB2-134 GEN
Solar/Wind Harmer
2.716
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
970301AG2-198 GEN
Solar/Wind Harmer
3.936
237006AB1-125 GEN
Solar/Wind Helper
0.126
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
232424Y1-079 C
Solar/Wind Helper
0.092
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
20674928WA_W3-044
Solar/Wind Helper
0.072
966111AG1-480 GEN
Solar/Wind Helper
0.032
208972BECR K09
Solar/Wind Helper
0.227
209137AF2-361 C
Solar/Wind Helper
0.864
237002AB1-128_GEN
Solar/Wind Helper
0.212
3147346CASHSCORNER
Solar/Wind Harmer
0.143
972213AH1-691 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
972189AH1-679 GEN
Adder
1.305
971281AH1-106 GEN
Solar/Wind Harmer
1.396
3138133OCRAN
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.031
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
316369SG1_INVT
Solar/Wind Harmer
1.505
3143316POE
Solar/Wind Harmer
-0.033
319010AE1-072 C
Solar/Wind Harmer
1.673
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
205943AE1-185 GEN
Solar/Wind Helper
0.423
233990AG1-397 GEN
Solar/Wind Helper
0.024
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
214067T20SOLAR
Solar/Wind Helper
0.009
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3150411LDYSMT5
Adder
10.908
972215AH1-692 GEN
Adder
1.766
316223AC1-118
Solar/Wind Harmer
0.237
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971283AH1-107 GEN
Solar/Wind Harmer
1.396
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
971167AH1-042 GEN
Solar/Wind Harmer
8.225
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
972265AH1-717 GEN
Adder
5.796
3151191GRAVEL3
Adder
5.364
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.798
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
970085AG2-068 GEN
Solar/Wind Harmer
4.94
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151861LOWMORA
Adder
0.648
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
219914AD2-027 C
Solar/Wind Helper
0.088
219607WPEMNERT C
Solar/Wind Helper
0.061
20715728PEM_W1-119
Solar/Wind Helper
0.073
20675528CPH_W2-050
Solar/Wind Helper
0.065
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
207530AG1-191 GEN
Solar/Wind Helper
0.049
20675128HRM_W1-127
Solar/Wind Helper
0.022
959421AF2-233 GEN
Solar/Wind Helper
0.297
316006AB2-029 C
Solar/Wind Harmer
0.632
316045AC1-158 PL2
Solar/Wind Harmer
3.177
3150151POSSMC1
Adder
0.848
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
3150851SPRUNCC
Adder
0.351
970659AG2-427 GEN
Solar/Wind Harmer
4.431
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
23779801AA1-109
Solar/Wind Helper
0.182
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
207445AB1-138_GEN
Solar/Wind Helper
0.079
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3144293JTRSVLE
Adder
0.22
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
233982AB2-133 GEN
Solar/Wind Helper
0.282
233940AF2-379 C
Solar/Wind Helper
0.049
233952AC2-187 GEN
Solar/Wind Helper
0.183
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.014
219612MATRIX C
Solar/Wind Helper
0.018
219908AB1-139 C
Solar/Wind Helper
0.055
20673728F2S_V4-070
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
209027LOR2_Q27
Solar/Wind Helper
0.712
961421AF2-433 GEN
Solar/Wind Helper
0.302
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
238221AF1-254 C O1
Solar/Wind Helper
0.122
3150071POSSM 5
Adder
38.76
3150391LDYSMT3
Adder
10.854
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3143526WINTERP
Solar/Wind Harmer
-0.044
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
944641AF1-129 GEN
Adder
35.924
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316316AC1-027 C
Solar/Wind Harmer
0.255
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3144356SAPONY
Solar/Wind Harmer
0.285
972185AH1-677 GEN
Adder
4.036
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
205916AD1-020 GEN
Solar/Wind Helper
1.496
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
233946AB2-136 GEN
Solar/Wind Helper
0.448
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20716928W4-060COL
Solar/Wind Helper
0.039
20673828FLE_V3-070
Solar/Wind Helper
0.068
20676128MHD_W3-029
Solar/Wind Helper
0.072
217081WEATEXAS C
Solar/Wind Helper
0.009
207471AF2-354 C
Solar/Wind Helper
0.124
20676228FRD_X1-012
Solar/Wind Helper
0.067
20390526W1-045 C
Solar/Wind Helper
0.226
961431AF2-434 GEN
Solar/Wind Helper
0.302
970099AG2-077 GEN
Solar/Wind Harmer
2.697
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
3141426STAFORD
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.29
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
971285AH1-108 GEN
Adder
0.574
957831AF2-077 GEN
Solar/Wind Harmer
0.255
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
957871AF2-081 GEN
Solar/Wind Harmer
4.142
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
23544701WINZ1-113
Adder
0.24
228754AB1-001 C
Solar/Wind Helper
0.02
219272CLEANLIGHT C
Solar/Wind Helper
0.019
20675928HOL_W4-097
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
209116AE2-175 GEN
Solar/Wind Helper
1.289
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
3143526WINTERP
Solar/Wind Harmer
-0.044
944631AF1-128 GEN
Adder
36.159
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
3143336POWHATN
Solar/Wind Harmer
0.991
944591AF1-124 GEN
Solar/Wind Harmer
37.981
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
971547AH1-271 GEN
Solar/Wind Harmer
1.976
972277AH1-723 GEN
Adder
41.593
3144293JTRSVLE
Adder
0.22
233930AB2-032 GEN
Solar/Wind Helper
0.301
233954AC2-188 GEN
Solar/Wind Helper
0.183
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219907AC1-030 C
Solar/Wind Helper
0.026
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
20671928W4-073
Solar/Wind Helper
0.066
946731AF1-337 GEN
Solar/Wind Helper
0.297
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
20676328BVR_Y1-020
Solar/Wind Helper
0.02
961261AF2-417 GEN
Solar/Wind Helper
0.308
959431AF2-234 GEN
Solar/Wind Helper
0.594
970053AG2-049 GEN
Adder
1.707
3150381LDYSMT2
Adder
10.439
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.193
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
3151201GRAVEL4
Adder
5.433
3151211GRAVEL5
Adder
5.364
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146396TANGLEW
Solar/Wind Harmer
0.151
315814AE2-033 C
Solar/Wind Harmer
7.6
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.197
972257AH1-713 GEN
Adder
0.697
960921AF2-383 GEN
Solar/Wind Helper
0.152
205932AD2-116_GEN
Solar/Wind Helper
0.422
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
966261AG1-495 GEN
Solar/Wind Helper
0.06
20674828DL_W4-046
Solar/Wind Helper
0.006
207408W3-077 C
Solar/Wind Helper
0.062
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
315683AE1-153 C
Solar/Wind Harmer
9.363
316192AB2-158 GEN
Solar/Wind Harmer
1.122
972197AH1-683 GEN
Adder
1.698
966881AG1-559 GEN
Solar/Wind Harmer
0.092
972135AH1-637 GEN
Solar/Wind Harmer
0.887
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
316375AC2-012 GEN
Solar/Wind Harmer
2.88
316336AC2-165 C
Solar/Wind Harmer
1.441
3146456SLIGO L269
Solar/Wind Harmer
-0.008
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3145663CRESWEL
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.626
966131AG1-482 GEN
Solar/Wind Helper
0.066
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
232434Z2-077 GEN
Solar/Wind Helper
0.1
219904AC1-010 C
Solar/Wind Helper
0.047
20720728JCB_W1-129
Solar/Wind Helper
0.043
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.106
217208PARK ELE C
Solar/Wind Helper
0.003
237080AD1-060 GEN
Solar/Wind Helper
0.151
959381AF2-229 GEN
Solar/Wind Helper
0.23
203975AE1-071-GEN
Solar/Wind Helper
1.563
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
237038AE2-054 C
Solar/Wind Helper
0.119
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
NYPJM->LTFIMP_NY
CLTF
3.269
TVALTFEXP_TVA->PJM
CLTF
3.503
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
WECLTFEXP_WEC->PJM
CLTF
1.126
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
LGEELTFEXP_LGEE->PJM
CLTF
2.098
MECLTFEXP_MEC->PJM
CLTF
5.133
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
CPLELTFEXP_CPLE->PJM
CLTF
5.01
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.83 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1462.93
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.827
971455AH1-223 GEN
Solar/Wind Harmer
2.201
3150291M RUN B
Adder
11.113
316170AC1-121 GEN2
Solar/Wind Harmer
0.08
3132273ORANGE
Solar/Wind Harmer
0.014
3150151POSSMC1
Adder
0.696
3152131X4-039 ST
50/50
2.874
3152121X4-039 GT2
50/50
1.821
971685AH1-345 GEN
Solar/Wind Harmer
0.609
972223AH1-696 GEN
Adder
5.499
3150231REMNGT3
50/50
11.996
3150241REMNGT4
50/50
11.185
963691AG1-221 GEN
Solar/Wind Harmer
2.201
972199AH1-684 GEN
Adder
1.598
3150371LDYSMT1
Adder
8.554
971781AH1-399 GEN
Solar/Wind Harmer
0.084
316473AC1-191 GEN
Solar/Wind Harmer
0.211
970009AG2-005 GEN
Solar/Wind Harmer
0.464
3142416OLDCHRC
Solar/Wind Harmer
0.6
3141766HARMONY
Solar/Wind Harmer
0.822
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142946ENON
Solar/Wind Harmer
0.021
970133AG2-095 GEN
Solar/Wind Harmer
0.585
3151221GRAVEL6
Adder
4.386
315813AE1-149 C
Solar/Wind Harmer
3.21
3150151POSSMC1
Adder
0.696
3150331BIRCHWDA
Adder
11.297
970737AG2-469 GEN
Solar/Wind Harmer
2.728
970293AG2-193 GEN
Solar/Wind Harmer
0.658
316203AE2-005 GEN
Solar/Wind Harmer
0
316156AD2-030 GEN
Solar/Wind Harmer
0.046
3150921YORKTN3
Adder
1.524
315773AC2-141 GEN
Solar/Wind Harmer
2.196
316313AB2-026
Solar/Wind Harmer
0.038
970659AG2-427 GEN
Solar/Wind Harmer
0.635
3144536CHRHLND
Solar/Wind Harmer
0.009
944581AF1-123 GEN
Solar/Wind Harmer
13.468
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
315614AA2-178 GEN
Solar/Wind Harmer
0.329
971157AH1-035 GEN
Solar/Wind Harmer
0.683
3146776BUCKING
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
957521AF2-046 GEN
Solar/Wind Harmer
4.204
205917AD1-020 ES
Solar/Wind Helper
0.292
233918AB1-142 GEN
Solar/Wind Helper
0.283
233994AC2-023 GEN
Solar/Wind Helper
0.539
233997TMININ_4.2
Solar/Wind Helper
0.146
970467AG2-304 GEN
50/50
12.983
3150221REMNGT2
50/50
11.111
972201AH1-685 GEN
50/50
1.917
3150211REMNGT1
Adder
10.402
315683AE1-153 C
Solar/Wind Harmer
5.861
316192AB2-158 GEN
Solar/Wind Harmer
0.388
972197AH1-683 GEN
Adder
1.382
966881AG1-559 GEN
Solar/Wind Harmer
0.075
972135AH1-637 GEN
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
0.161
3142416OLDCHRC
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.012
971777AH1-397 GEN
Solar/Wind Harmer
0.163
3142433PROV 92
Solar/Wind Harmer
0.246
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3145336SMITFLD
Solar/Wind Harmer
0.24
316294AC1-161 GEN
Solar/Wind Harmer
1.042
316375AC2-012 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.059
970937AG2-583 GEN
Solar/Wind Harmer
3.567
3145663CRESWEL
Solar/Wind Harmer
0.161
316023GEN1_S
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3146173TUNIS
Solar/Wind Harmer
0.056
966131AG1-482 GEN
Solar/Wind Helper
0.102
237080AD1-060 GEN
Solar/Wind Helper
0.184
232422X3-066 FULL
Solar/Wind Helper
0.064
233964AF2-378 GEN
Solar/Wind Helper
0.023
232426Y1-080 FULL
Solar/Wind Helper
0.022
232434Z2-077 GEN
Solar/Wind Helper
0.071
205941AD2-115 GEN
Solar/Wind Helper
0.276
219904AC1-010 C
Solar/Wind Helper
0.033
315651AD1-115 GEN
Solar/Wind Harmer
0.002
316447AC1-158 HLD
Solar/Wind Harmer
0.794
957411AF2-035 GEN
Solar/Wind Harmer
2.759
958261AF2-120 GEN
Solar/Wind Harmer
2.062
3142366NRTHEST
Adder
0.202
3150691DARBY 3
Adder
4.444
3150701DARBY 4
Adder
4.434
3142946ENON
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
3146456SLIGO L269
Solar/Wind Harmer
1.052
3146386ELIZ CT
Solar/Wind Harmer
0.059
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
4.601
3146173TUNIS
Solar/Wind Harmer
0.056
3146173TUNIS
Solar/Wind Harmer
0.056
237025AB1-124 C
Solar/Wind Helper
0.177
23777801MSM_W1-116
Solar/Wind Helper
0.118
230407AD2-065 C
Solar/Wind Helper
0.022
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.043
3141346CRANES
Adder
0.08
972219AH1-694 GEN
Adder
0.995
3150351NORNECKC2
Adder
0.624
3143526WINTERP
Solar/Wind Harmer
0.322
944631AF1-128 GEN
Adder
29.257
971317AH1-138 GEN
Solar/Wind Harmer
0.454
315671AE2-027_GEN
Solar/Wind Harmer
3.891
3143336POWHATN
Solar/Wind Harmer
1.067
944591AF1-124 GEN
Solar/Wind Harmer
13.516
316072AD1-144
Solar/Wind Harmer
0.022
939411AE1-173 GEN
Solar/Wind Harmer
25.458
940641AE2-051 GEN
Solar/Wind Harmer
4.772
972003AH1-546 GEN
Solar/Wind Harmer
2.42
316322AB2-045
Solar/Wind Harmer
0
971547AH1-271 GEN
Solar/Wind Harmer
1.207
233930AB2-032 GEN
Solar/Wind Helper
0.215
233954AC2-188 GEN
Solar/Wind Helper
0.13
230511AF1-262
Solar/Wind Helper
0.008
230434AG1-499 GEN
Solar/Wind Helper
0.126
219258KINSLEYDEP C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.003
207528AF2-192 GEN
Solar/Wind Helper
0.04
20673628F1S_V4-069
Solar/Wind Helper
0.016
217213AMBOY SO C
Solar/Wind Helper
0.015
207437AD2-070 GEN
Solar/Wind Helper
0.073
3150071POSSM 5
Adder
31.816
3150391LDYSMT3
Adder
8.836
316468AD1-105 GEN
Solar/Wind Harmer
-0.021
316077AC2-138 C
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.322
316075AC2-137 C
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
29.055
315697AD1-025 GEN
Solar/Wind Harmer
0.068
316316AC1-027 C
Solar/Wind Harmer
0.057
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
0.491
972185AH1-677 GEN
Adder
3.254
205916AD1-020 GEN
Solar/Wind Helper
1.359
20390526W1-045 C
Solar/Wind Helper
0.222
233933AB2-153 GEN
Solar/Wind Helper
0.131
233944AB2-135 GEN
Solar/Wind Helper
0.332
233946AB2-136 GEN
Solar/Wind Helper
0.319
232408W1-005 C
Solar/Wind Helper
0.284
232410W1-006 C
Solar/Wind Helper
0.284
233939AC1-091 C
Solar/Wind Helper
0.196
963401AG1-189 GEN
Solar/Wind Helper
0.03
963391AG1-188 GEN
Solar/Wind Helper
0.044
235020AA1-095 C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.028
20673828FLE_V3-070
Solar/Wind Helper
0.048
20676128MHD_W3-029
Solar/Wind Helper
0.051
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.089
20676228FRD_X1-012
Solar/Wind Helper
0.048
3150281M RUN A
Adder
11.203
3140676OCCOQUN
Adder
0.198
316254AC1-120 GEN1
Solar/Wind Harmer
0.16
3147666LOUISA
Solar/Wind Harmer
0.275
3151751LOISA D
Adder
4.435
3143226MDLTHAN
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.037
3141843SHACKLE
Adder
0.315
3143096IRON208
Adder
0.258
3142543TWELFTH
Solar/Wind Harmer
0.006
316159AE1-175 C
Solar/Wind Harmer
0.053
970129AG2-093 GEN
Solar/Wind Harmer
1.729
316458AB2-190 GEN2
Solar/Wind Harmer
0.326
971069AG2-661 GEN
Solar/Wind Harmer
1.079
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971647AH1-324 GEN
Solar/Wind Harmer
2.582
961611AG1-000B GEN
Solar/Wind Harmer
3.169
3151171GRAVELC
Adder
0.642
316381AD1-082 GEN
Solar/Wind Harmer
0.062
3150981CHESPKA
Adder
0.747
970661AG2-428 GEN
Solar/Wind Harmer
5.952
316388AE2-253 GEN
Solar/Wind Harmer
0.187
316246AF1-032 C
Solar/Wind Harmer
0.027
3130156CHOWAN
Solar/Wind Harmer
0.058
971163AH1-040 GEN
Solar/Wind Harmer
4.594
972289AH1-729 GEN
50/50
12.961
3150181POSSMC2
Adder
0.702
3150181POSSMC2
Adder
0.696
3150181POSSMC2
Adder
0.696
966001AG1-469 GEN
Solar/Wind Harmer
0.04
3151731LOISA B
Adder
4.435
972195AH1-682 GEN
Adder
1.161
315673AE1-157 GEN
Solar/Wind Harmer
4.506
3150341NORNECKC1
Adder
0.656
3150341NORNECKC1
Adder
0.651
3150681DARBY 2
Adder
4.428
316033AB2-134 GEN
Solar/Wind Harmer
0.004
316236AE1-162_GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
2.098
970657AG2-426 GEN
Solar/Wind Harmer
0.44
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.036
316339AD2-160 GEN
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.237
3130086AYDLETT
Solar/Wind Harmer
0.238
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.401
3147346CASHSCORNER
Solar/Wind Harmer
0.156
972213AH1-691 GEN
Adder
1.438
944491AF1-114 GEN
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.058
971281AH1-106 GEN
Solar/Wind Harmer
0.859
3138133OCRAN
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.037
3141873WAN 176
Solar/Wind Harmer
0.012
316369SG1_INVT
Solar/Wind Harmer
0.002
3143316POE
Solar/Wind Harmer
0.238
319010AE1-072 C
Solar/Wind Harmer
0.299
3146486SUNBURY
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.059
316321Z2-027
Solar/Wind Harmer
0.011
3145176PASQUOTANK
Solar/Wind Harmer
0.037
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
315816AE2-034 GEN
Solar/Wind Harmer
0.246
972205AH1-687 GEN
Adder
2.436
3130546PLYMOUTH
Solar/Wind Harmer
0.057
315733AD1-074 GEN2
Solar/Wind Harmer
0.327
970581AG2-369 GEN
Solar/Wind Harmer
2.597
970601AG2-382 GEN
Solar/Wind Harmer
2.113
205943AE1-185 GEN
Solar/Wind Helper
0.354
233990AG1-397 GEN
Solar/Wind Helper
0.151
964001AG1-254 GEN
Solar/Wind Helper
0.525
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.022
214067T20SOLAR
Solar/Wind Helper
0.006
20715828PEM_W1-120
Solar/Wind Helper
0.052
207459AE1-142 C O1
Solar/Wind Helper
0.157
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.086
20676328BVR_Y1-020
Solar/Wind Helper
0.014
961261AF2-417 GEN
Solar/Wind Helper
0.221
3151721LOISA A
Adder
4.412
970317AG2-208 GEN
Solar/Wind Harmer
2.556
966871AG1-558 GEN
Solar/Wind Harmer
0.072
3142296MT RD221
Adder
0.198
971223AH1-071 GEN
Solar/Wind Harmer
0.661
3150671DARBY 1
Adder
4.423
316240AF1-291 C
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.627
3150991CHESPKB
Adder
0.612
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
971761AH1-387 GEN
Solar/Wind Harmer
1.133
972187AH1-678 GEN
Adder
1.643
316065AD1-022 GEN
Solar/Wind Harmer
2.61
3146776BUCKING
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.379
3145893MURPHYS
Solar/Wind Harmer
0.102
237034AC2-136 C
Solar/Wind Helper
0.179
226929AD2-058 GEN
Solar/Wind Helper
0.07
237001AB1-127_GEN
Solar/Wind Helper
0.259
235063AE1-101 C2
Solar/Wind Helper
0.889
233987AB2-037 GEN
Solar/Wind Helper
1.314
234036AF2-325 C
Solar/Wind Helper
0.024
233901CHERRYDALE C
Solar/Wind Helper
0.13
20720628TIN_W1-124
Solar/Wind Helper
0.102
207442AE1-156 GEN
Solar/Wind Helper
0.174
20671828STAW2-080
Solar/Wind Helper
0.014
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.078
211065PSPA IPP
Solar/Wind Helper
0.078
3138216PACIFIC
Solar/Wind Harmer
0.024
316164AC1-076 GEN
Solar/Wind Harmer
0.104
3150411LDYSMT5
Adder
8.881
972215AH1-692 GEN
Adder
1.438
316223AC1-118
Solar/Wind Harmer
0.046
3141813NORNECK
Solar/Wind Harmer
0.063
962981AG1-147 GEN
Solar/Wind Harmer
2.318
316233AE1-074 FULL
Solar/Wind Harmer
0.05
971283AH1-107 GEN
Solar/Wind Harmer
0.859
315666AE1-190 GEN
Solar/Wind Harmer
0
970189AG2-124 GEN
Solar/Wind Harmer
1.827
971167AH1-042 GEN
Solar/Wind Harmer
5.466
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.326
972265AH1-717 GEN
Adder
4.684
3151191GRAVEL3
Adder
4.336
316305AF2-043 C
Solar/Wind Harmer
0
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
3.529
971967AH1-528 GEN
Solar/Wind Harmer
9.279
315732AD1-074 GEN1
Solar/Wind Harmer
0.327
315735AD1-075 GEN1
Solar/Wind Harmer
0.164
965291AG1-394 GEN
Solar/Wind Harmer
0.253
970085AG2-068 GEN
Solar/Wind Harmer
3.019
3145893MURPHYS
Solar/Wind Harmer
0.153
3145893MURPHYS
Solar/Wind Harmer
0.057
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.015
970327AG2-215 GEN
Solar/Wind Harmer
2.041
316312AB1-027
Solar/Wind Harmer
0.111
3141913WHIT STONE
Solar/Wind Harmer
0.062
316314AB2-024 C
Solar/Wind Harmer
0
971285AH1-108 GEN
Adder
0.465
971445AH1-216 GEN
Solar/Wind Harmer
4.236
3151081ELIZAR1
Adder
5.485
3151091ELIZAR2
Adder
5.39
3152611GOSPORTB
Adder
0.762
3152621GOSPORTC
Adder
0.647
3152601GOSPORTA
Adder
0.597
315833AF1-017_GEN
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.964
316315AB2-025 C
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
10.802
970673AG2-436 GEN
Solar/Wind Harmer
12.417
970673AG2-436 GEN
Solar/Wind Harmer
8.278
237085AD2-009_GEN
Solar/Wind Helper
0.799
228754AB1-001 C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.014
20675928HOL_W4-097
Solar/Wind Helper
0.026
207484AF2-139 C O1
Solar/Wind Helper
0.044
20675728RH_W2-091
Solar/Wind Helper
0.072
209116AE2-175 GEN
Solar/Wind Helper
0.921
3150301M RUN C
Adder
11.196
316044AC1-158 PL1
Solar/Wind Harmer
0.361
316450AC1-158 RIC
Solar/Wind Harmer
0.096
3147666LOUISA
Solar/Wind Harmer
0.158
3150401LDYSMT4
Adder
8.853
3141906WESTMOR
Solar/Wind Harmer
0.025
316404AE1-155 C
Solar/Wind Harmer
0.014
962971AG1-146 GEN
Solar/Wind Harmer
0.993
316280AD1-041 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
1.096
3141843SHACKLE
Adder
0.315
3150861SPRUNCD
Adder
0.284
3143096IRON208
Adder
0.258
3143096IRON208
Adder
0.253
316382AG1-145 C
Solar/Wind Harmer
0
970129AG2-093 GEN
Solar/Wind Harmer
3.674
965281AG1-393 GEN
Solar/Wind Harmer
0.648
961611AG1-000B GEN
Solar/Wind Harmer
1.611
3151171GRAVELC
Adder
0.844
316405AF2-144 C
Solar/Wind Harmer
0
3144873MCLAUGH
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.266
3146626S HERTFORD
Solar/Wind Harmer
0.059
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.732
970917AG2-570 GEN
Solar/Wind Harmer
5.042
961681AG1-008 GEN
Solar/Wind Harmer
4.204
3146926FARMVIL
Solar/Wind Harmer
0.034
235067AD1-061 GEN
Solar/Wind Helper
0.259
234015AF2-250 C
Solar/Wind Helper
0.021
219276PARKLANDSO C
Solar/Wind Helper
0.048
20720528MAN_W1-024
Solar/Wind Helper
0.015
217169METRODIV C
Solar/Wind Helper
0.002
970087AG2-069 GEN
Solar/Wind Harmer
4.529
3146926FARMVIL
Solar/Wind Harmer
0.034
223401AF1-299 GEN
Solar/Wind Helper
0.351
235062AE1-101 C1
Solar/Wind Helper
0.889
233915AB1-141 GEN
Solar/Wind Helper
0.283
232428Y3-058 C
Solar/Wind Helper
0.19
233998TM1NIN_3.36
Solar/Wind Helper
0.146
232404W1-003 C
Solar/Wind Helper
0.284
233950AC2-186 GEN
Solar/Wind Helper
0.065
233972AC1-094 C
Solar/Wind Helper
0.169
228728W1-130C
Solar/Wind Helper
0.03
218660EHAMPSOLAR C
Solar/Wind Helper
0.018
963711AG1-223 GEN
Solar/Wind Helper
0.035
207454AA2-184 E
Solar/Wind Helper
0.166
20715228NPK_W1-113
Solar/Wind Helper
0.042
20675428EAM_W2-061
Solar/Wind Helper
0.008
207518AF1-320_GEN
Solar/Wind Helper
0.827
237006AB1-125 GEN
Solar/Wind Helper
0.132
208835TUHI V3-051
Solar/Wind Helper
0.018
208835TUHI V3-051
Solar/Wind Helper
0.018
237002AB1-128_GEN
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.085
232424Y1-079 C
Solar/Wind Helper
0.065
233970AC1-092 C
Solar/Wind Helper
0.196
230433AD2-135 GEN
Solar/Wind Helper
0.009
219921AF1-264
Solar/Wind Helper
0.028
219615MILLCREEK C
Solar/Wind Helper
0.014
20674928WA_W3-044
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.039
316006AB2-029 C
Solar/Wind Harmer
0
316045AC1-158 PL2
Solar/Wind Harmer
1.156
3150151POSSMC1
Adder
0.696
316337AD2-073 GEN
Solar/Wind Harmer
0.055
3141726DUNNSVL
Solar/Wind Harmer
0.25
962861AG1-135 GEN
Solar/Wind Harmer
1.994
3150851SPRUNCC
Adder
0.284
970659AG2-427 GEN
Solar/Wind Harmer
2.901
316093AE2-104_GEN
Solar/Wind Harmer
0.998
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.059
315800Z1-036_GEN1
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.023
3145893MURPHYS
Solar/Wind Harmer
0.226
3145893MURPHYS
Solar/Wind Harmer
0.251
23779801AA1-109
Solar/Wind Helper
0.196
237038AE2-054 C
Solar/Wind Helper
0.144
219686LUMSOLAR_N C
Solar/Wind Helper
0.022
219304NAMERICA C
Solar/Wind Helper
0.072
207445AB1-138_GEN
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.036
217209CENTRL HS C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.012
207439AE1-081 C O1
Solar/Wind Helper
0.01
961301AF2-421 GEN
Solar/Wind Helper
0.221
963151AG1-164 GEN
Solar/Wind Helper
0.221
315747AE2-019 GEN
50/50
12.182
972285AH1-727 GEN
50/50
35.211
972217AH1-693 GEN
50/50
1.475
3141196NOKESVL
Solar/Wind Harmer
0.372
3151761LOISA E
Adder
9.041
972183AH1-676 GEN
Adder
72.988
3141316ARNOLDS
Adder
0.157
3150351NORNECKC2
Adder
0.635
315778AD1-151 GEN
Solar/Wind Harmer
4.854
315839AE2-212 C
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.228
316258AE1-075 C
Solar/Wind Harmer
0.045
3143336POWHATN
Solar/Wind Harmer
0.907
3151101ELIZAR3
Adder
5.556
944601AF1-125 GEN
Solar/Wind Harmer
13.26
970909AG2-566 GEN
Solar/Wind Harmer
0.6
223402AF1-300 C
Solar/Wind Helper
0.351
226910AB2-157 C
Solar/Wind Helper
0.013
238221AF1-254 C O1
Solar/Wind Helper
0.149
233982AB2-133 GEN
Solar/Wind Helper
0.202
233940AF2-379 C
Solar/Wind Helper
0.035
233952AC2-187 GEN
Solar/Wind Helper
0.13
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.01
219612MATRIX C
Solar/Wind Helper
0.013
219908AB1-139 C
Solar/Wind Helper
0.039
20673728F2S_V4-070
Solar/Wind Helper
0.016
207510AF2-138 C
Solar/Wind Helper
0.043
20671928W4-073
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.015
970053AG2-049 GEN
50/50
1.525
3150381LDYSMT2
Adder
8.499
3141783LANCAST
Solar/Wind Harmer
0.037
3141783LANCAST
Solar/Wind Harmer
0.025
316059AD1-063 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
315976AC1-164 GENA
Solar/Wind Harmer
6.381
316169AC1-164_GENC
Solar/Wind Harmer
5.512
315975AC1-164 GENB
Solar/Wind Harmer
0.189
3151201GRAVEL4
Adder
4.391
3151211GRAVEL5
Adder
4.336
316349AD2-085 GEN
Solar/Wind Harmer
0.041
316311AC2-079 GEN
Solar/Wind Harmer
1.71
315835AF2-110_GEN
Solar/Wind Harmer
0.407
313526AB2-022
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
4.636
971845AH1-439 GEN
Solar/Wind Harmer
2.569
970285AG2-188 GEN
Solar/Wind Harmer
4.479
3146206CASHIE
Solar/Wind Harmer
0.057
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
960921AF2-383 GEN
Solar/Wind Helper
0.255
205932AD2-116_GEN
Solar/Wind Helper
0.352
959381AF2-229 GEN
Solar/Wind Helper
0.226
203975AE1-071-GEN
Solar/Wind Helper
1.507
232432Z2-076 GEN
Solar/Wind Helper
0.038
234033AF1-007_GEN
Solar/Wind Helper
3.932
966261AG1-495 GEN
Solar/Wind Helper
0.043
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.044
20720728JCB_W1-129
Solar/Wind Helper
0.031
20714828MDF_W3-079
Solar/Wind Helper
0.07
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.075
217208PARK ELE C
Solar/Wind Helper
0.002
205956AE1-196_GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
0.72
232436AB1-176 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.537
219914AD2-027 C
Solar/Wind Helper
0.063
219607WPEMNERT C
Solar/Wind Helper
0.044
20715728PEM_W1-119
Solar/Wind Helper
0.052
20675528CPH_W2-050
Solar/Wind Helper
0.046
218524CNTRALGAS1 C
Solar/Wind Helper
0.086
207530AG1-191 GEN
Solar/Wind Helper
0.035
20675128HRM_W1-127
Solar/Wind Helper
0.016
20676728BRNX1-095
Solar/Wind Helper
0.016
963161AG1-165 GEN
Solar/Wind Helper
0.221
233971AC1-093 C
Solar/Wind Helper
0.2
228729W2-030 C
Solar/Wind Helper
0.061
219348LDSOLAR C
Solar/Wind Helper
0.062
959561AF2-247 GEN
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
3145336SMITFLD
Solar/Wind Harmer
0.024
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.059
971153AH1-033 GEN
Solar/Wind Harmer
0.687
3145273HOLLAND
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.058
316365GEN2_N
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3146173TUNIS
Solar/Wind Harmer
0.056
237030AB1-096 C
Solar/Wind Helper
0.076
227287AC2-120 GEN
Solar/Wind Helper
0.279
233996TM1833_GEN
Solar/Wind Helper
0.146
232406W1-004 FULL
Solar/Wind Helper
0.284
230430AE1-229_GEN
Solar/Wind Helper
1.854
230415AB2-049 C
Solar/Wind Helper
0.017
219766PARADISE C
Solar/Wind Helper
0.03
219912AD2-042 GEN
Solar/Wind Helper
0.082
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.023
20720828JCB_W4-025
Solar/Wind Helper
0.034
20714528FRN_Y2-051
Solar/Wind Helper
0.031
218438BLK ROCK C
Solar/Wind Helper
0.015
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.047
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.895
WECLTFEXP_WEC->PJM
CLTF
0.855
LAGNLTFEXP_LAGN->PJM
CLTF
5.367
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.688
NYPJM->LTFIMP_NY
CLTF
2.351
TVALTFEXP_TVA->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.069
CPLELTFEXP_CPLE->PJM
CLTF
3.974
SIGELTFEXP_SIGE->PJM
CLTF
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.607
LGEELTFEXP_LGEE->PJM
CLTF
1.596
MECLTFEXP_MEC->PJM
CLTF
3.911

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 514-2098_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 514-2098_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1482.99
MW Contribution:6.24
Bus #Bus NameTypeMW Contribution
972213AH1-691 GEN
Adder
1.58
3147346CASHSCORNER
Solar/Wind Harmer
0.123
944491AF1-114 GEN
Solar/Wind Harmer
2.324
972189AH1-679 GEN
Adder
1.141
3138133OCRAN
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
0.894
3141873WAN 176
Solar/Wind Harmer
-0.001
971281AH1-106 GEN
Solar/Wind Harmer
1.205
3143873LANEXA
Solar/Wind Harmer
-0.004
316369SG1_INVT
Solar/Wind Harmer
1.293
970053AG2-049 GEN
Adder
1.58
3150381LDYSMT2
Adder
9.338
3141783LANCAST
Solar/Wind Harmer
-0.004
3150221REMNGT2
Adder
11.204
3150211REMNGT1
Adder
11.13
972201AH1-685 GEN
Adder
1.933
315683AE1-153 C
Solar/Wind Harmer
8.198
316192AB2-158 GEN
Solar/Wind Harmer
0.98
972197AH1-683 GEN
Adder
1.519
966881AG1-559 GEN
Solar/Wind Harmer
0.081
972135AH1-637 GEN
Solar/Wind Harmer
0.787
961951AG1-038 GEN
Solar/Wind Harmer
0.989
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.872
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.128
315651AD1-115 GEN
Solar/Wind Harmer
4.033
316447AC1-158 HLD
Solar/Wind Harmer
1.939
957411AF2-035 GEN
Solar/Wind Harmer
3.562
958261AF2-120 GEN
Solar/Wind Harmer
2.921
316487AF1-042 GEN
Solar/Wind Harmer
0.989
3142366NRTHEST
Adder
0.216
3150691DARBY 3
Adder
4.75
3150701DARBY 4
Adder
4.739
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.573
3146456SLIGO L269
Solar/Wind Harmer
0.835
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.265
316433W1029_GEN2
Solar/Wind Harmer
1.265
315742AE1-103 GEN
Solar/Wind Harmer
0.72
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
6.344
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
237025AB1-124 C
Solar/Wind Helper
0.191
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.02
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.008
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
3142433PROV 92
Adder
0.128
3145336SMITFLD
Solar/Wind Harmer
-0.029
316294AC1-161 GEN
Solar/Wind Harmer
2.317
316375AC2-012 GEN
Solar/Wind Harmer
2.465
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316336AC2-165 C
Solar/Wind Harmer
1.216
970937AG2-583 GEN
Solar/Wind Harmer
4.871
3145663CRESWEL
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.523
237080AD1-060 GEN
Solar/Wind Helper
0.235
966131AG1-482 GEN
Solar/Wind Helper
0.056
232422X3-066 FULL
Solar/Wind Helper
0.058
205941AD2-115 GEN
Solar/Wind Helper
0.256
233964AF2-378 GEN
Solar/Wind Helper
0.021
232426Y1-080 FULL
Solar/Wind Helper
0.02
232434Z2-077 GEN
Solar/Wind Helper
0.064
219904AC1-010 C
Solar/Wind Helper
0.03
20720728JCB_W1-129
Solar/Wind Helper
0.028
20714828MDF_W3-079
Solar/Wind Helper
0.064
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.069
217208PARK ELE C
Solar/Wind Helper
0.002
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.168
3143316POE
Solar/Wind Harmer
-0.028
319010AE1-072 C
Solar/Wind Harmer
1.429
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.189
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
1.707
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.548
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315733AD1-074 GEN2
Solar/Wind Harmer
1.352
970601AG2-382 GEN
Solar/Wind Harmer
2.908
970581AG2-369 GEN
Solar/Wind Harmer
3.569
972205AH1-687 GEN
Adder
2.506
946281AF1-292 GEN
Solar/Wind Harmer
0.147
205943AE1-185 GEN
Solar/Wind Helper
0.335
238208AF1-136 C
Solar/Wind Helper
0.101
972289AH1-729 GEN
50/50
13.565
3150181POSSMC2
Adder
0.796
3150181POSSMC2
Adder
0.79
3150181POSSMC2
Adder
0.79
966001AG1-469 GEN
Solar/Wind Harmer
0.155
972195AH1-682 GEN
Adder
1.276
3151731LOISA B
Adder
4.689
315673AE1-157 GEN
Solar/Wind Harmer
6.001
3150341NORNECKC1
Adder
0.707
3150341NORNECKC1
Adder
0.702
3150681DARBY 2
Adder
4.734
316033AB2-134 GEN
Solar/Wind Harmer
2.335
316236AE1-162_GEN
Solar/Wind Harmer
0.216
970657AG2-426 GEN
Solar/Wind Harmer
2.229
970657AG2-426 GEN
Solar/Wind Harmer
0.466
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.478
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
237006AB1-125 GEN
Solar/Wind Helper
0.143
237002AB1-128_GEN
Solar/Wind Helper
0.314
23777901MDS_W4-102
Solar/Wind Helper
0.114
208835TUHI V3-051
Solar/Wind Helper
0.015
208835TUHI V3-051
Solar/Wind Helper
0.015
232424Y1-079 C
Solar/Wind Helper
0.059
233970AC1-092 C
Solar/Wind Helper
0.176
230433AD2-135 GEN
Solar/Wind Helper
0.008
219921AF1-264
Solar/Wind Helper
0.025
219615MILLCREEK C
Solar/Wind Helper
0.013
3140676OCCOQUN
Adder
0.219
3150281M RUN A
Adder
11.989
316254AC1-120 GEN1
Solar/Wind Harmer
0.729
3147666LOUISA
Solar/Wind Harmer
-0.033
3151751LOISA D
Adder
4.689
957971AF2-091 GEN
Solar/Wind Harmer
0.79
3138133OCRAN
Solar/Wind Harmer
-0.004
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3141843SHACKLE
Adder
0.337
3143096IRON208
Adder
0.275
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.196
970129AG2-093 GEN
Solar/Wind Harmer
1.657
316458AB2-190 GEN2
Solar/Wind Harmer
0.735
971069AG2-661 GEN
Solar/Wind Harmer
1.147
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.613
961611AG1-000B GEN
Solar/Wind Harmer
3.56
3151171GRAVELC
Adder
0.681
316381AD1-082 GEN
Solar/Wind Harmer
0.655
3150981CHESPKA
Adder
0.791
970661AG2-428 GEN
Solar/Wind Harmer
7.568
316388AE2-253 GEN
Solar/Wind Harmer
0.478
316246AF1-032 C
Solar/Wind Harmer
0.143
3130156CHOWAN
Solar/Wind Harmer
-0.007
971163AH1-040 GEN
Solar/Wind Harmer
6.345
970087AG2-069 GEN
Solar/Wind Harmer
6.225
957481AF2-042 GEN
Solar/Wind Harmer
20.536
223401AF1-299 GEN
Solar/Wind Helper
0.282
235062AE1-101 C1
Solar/Wind Helper
1.123
233915AB1-141 GEN
Solar/Wind Helper
0.254
233998TM1NIN_3.36
Solar/Wind Helper
0.131
232428Y3-058 C
Solar/Wind Helper
0.17
232404W1-003 C
Solar/Wind Helper
0.255
233950AC2-186 GEN
Solar/Wind Helper
0.058
233972AC1-094 C
Solar/Wind Helper
0.152
228728W1-130C
Solar/Wind Helper
0.027
218660EHAMPSOLAR C
Solar/Wind Helper
0.016
963711AG1-223 GEN
Solar/Wind Helper
0.032
207454AA2-184 E
Solar/Wind Helper
0.152
20715228NPK_W1-113
Solar/Wind Helper
0.038
20675428EAM_W2-061
Solar/Wind Helper
0.008
233990AG1-397 GEN
Solar/Wind Helper
0.015
964001AG1-254 GEN
Solar/Wind Helper
0.476
227927V4-067C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.02
214067T20SOLAR
Solar/Wind Helper
0.006
20715828PEM_W1-120
Solar/Wind Helper
0.047
207459AE1-142 C O1
Solar/Wind Helper
0.143
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.079
3150301M RUN C
Adder
11.982
316044AC1-158 PL1
Solar/Wind Harmer
0.882
316450AC1-158 RIC
Solar/Wind Harmer
0.235
3147666LOUISA
Solar/Wind Harmer
-0.019
3150401LDYSMT4
Adder
9.727
3141906WESTMOR
Solar/Wind Harmer
-0.003
316404AE1-155 C
Solar/Wind Harmer
1.454
962971AG1-146 GEN
Solar/Wind Harmer
1.405
316280AD1-041 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
0.88
3141843SHACKLE
Adder
0.337
3143096IRON208
Adder
0.275
3143096IRON208
Adder
0.27
3150861SPRUNCD
Adder
0.303
316382AG1-145 C
Solar/Wind Harmer
0.22
970129AG2-093 GEN
Solar/Wind Harmer
4.092
965281AG1-393 GEN
Solar/Wind Harmer
0.907
961611AG1-000B GEN
Solar/Wind Harmer
1.519
3151171GRAVELC
Adder
0.896
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.341
316405AF2-144 C
Solar/Wind Harmer
0.182
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.173
315737AD1-076 GEN
Solar/Wind Harmer
1.271
970917AG2-570 GEN
Solar/Wind Harmer
16.639
961681AG1-008 GEN
Solar/Wind Harmer
5.222
962331AG1-082 GEN
Solar/Wind Harmer
0.823
235067AD1-061 GEN
Solar/Wind Helper
0.331
234015AF2-250 C
Solar/Wind Helper
0.019
219276PARKLANDSO C
Solar/Wind Helper
0.044
20720528MAN_W1-024
Solar/Wind Helper
0.014
217169METRODIV C
Solar/Wind Helper
0.002
3151721LOISA A
Adder
4.665
970317AG2-208 GEN
Solar/Wind Harmer
3.463
966871AG1-558 GEN
Solar/Wind Harmer
0.226
966871AG1-558 GEN
Solar/Wind Harmer
0.077
3142296MT RD221
Adder
0.212
3150671DARBY 1
Adder
4.728
971223AH1-071 GEN
Solar/Wind Harmer
0.927
316240AF1-291 C
Solar/Wind Harmer
0.219
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.664
3150991CHESPKB
Adder
0.648
3142956BIRDNECK
Solar/Wind Harmer
0.382
316018AA1-139 ULT2
Solar/Wind Harmer
0.606
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
972187AH1-678 GEN
Adder
1.723
316065AD1-022 GEN
Solar/Wind Harmer
3.331
3145893MURPHYS
Solar/Wind Harmer
0.185
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146776BUCKING
Solar/Wind Harmer
-0.026
3146776BUCKING
Solar/Wind Harmer
-0.002
237034AC2-136 C
Solar/Wind Helper
0.211
237001AB1-127_GEN
Solar/Wind Helper
0.322
235063AE1-101 C2
Solar/Wind Helper
1.123
226929AD2-058 GEN
Solar/Wind Helper
0.051
233987AB2-037 GEN
Solar/Wind Helper
1.178
234036AF2-325 C
Solar/Wind Helper
0.021
233901CHERRYDALE C
Solar/Wind Helper
0.117
20720628TIN_W1-124
Solar/Wind Helper
0.093
207442AE1-156 GEN
Solar/Wind Helper
0.159
20671828STAW2-080
Solar/Wind Helper
0.013
316006AB2-029 C
Solar/Wind Harmer
0.563
316045AC1-158 PL2
Solar/Wind Harmer
2.821
3150151POSSMC1
Adder
0.79
316337AD2-073 GEN
Solar/Wind Harmer
0.206
3141726DUNNSVL
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
2.824
3150851SPRUNCC
Adder
0.303
970659AG2-427 GEN
Solar/Wind Harmer
3.796
316093AE2-104_GEN
Solar/Wind Harmer
2.049
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.707
970919AG2-571 GEN
Solar/Wind Harmer
2.106
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.197
3146776BUCKING
Solar/Wind Harmer
-0.003
23779801AA1-109
Solar/Wind Helper
0.218
237038AE2-054 C
Solar/Wind Helper
0.184
219686LUMSOLAR_N C
Solar/Wind Helper
0.02
219304NAMERICA C
Solar/Wind Helper
0.065
207445AB1-138_GEN
Solar/Wind Helper
0.051
20676428JCR_X2-075
Solar/Wind Helper
0.033
217209CENTRL HS C
Solar/Wind Helper
0.004
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.75
3150411LDYSMT5
Adder
9.757
972215AH1-692 GEN
Adder
1.58
316223AC1-118
Solar/Wind Harmer
0.209
3141813NORNECK
Solar/Wind Harmer
-0.008
962981AG1-147 GEN
Solar/Wind Harmer
3.278
315666AE1-190 GEN
Solar/Wind Harmer
0.223
957601AF2-054 GEN
Solar/Wind Harmer
0.222
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971283AH1-107 GEN
Solar/Wind Harmer
1.205
971167AH1-042 GEN
Solar/Wind Harmer
7.117
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.735
972265AH1-717 GEN
Adder
4.974
3151191GRAVEL3
Adder
4.604
316305AF2-043 C
Solar/Wind Harmer
0.213
3146406KITTY HAWK
Solar/Wind Harmer
0.006
944011AF1-069 GEN
Solar/Wind Harmer
4.075
971967AH1-528 GEN
Solar/Wind Harmer
12.856
315732AD1-074 GEN1
Solar/Wind Harmer
1.352
315735AD1-075 GEN1
Solar/Wind Harmer
0.676
965291AG1-394 GEN
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.15
3145513AHOSKIE
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.298
205956AE1-196_GEN
Solar/Wind Helper
0.332
233935AB2-179 C
Solar/Wind Helper
0.644
232436AB1-176 C
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.482
219914AD2-027 C
Solar/Wind Helper
0.057
219607WPEMNERT C
Solar/Wind Helper
0.04
20715728PEM_W1-119
Solar/Wind Helper
0.047
20675528CPH_W2-050
Solar/Wind Helper
0.042
218524CNTRALGAS1 C
Solar/Wind Helper
0.079
3152111X4-039 GT1
50/50
1.893
971455AH1-223 GEN
Solar/Wind Harmer
2.324
3150291M RUN B
Adder
11.893
316170AC1-121 GEN2
Solar/Wind Harmer
0.243
3150151POSSMC1
Adder
0.79
3150151POSSMC1
Adder
0.79
3132273ORANGE
Solar/Wind Harmer
-0.002
3150331BIRCHWDA
Adder
12.528
970737AG2-469 GEN
Solar/Wind Harmer
3.911
316484AD2-074 GEN
Solar/Wind Harmer
1.891
316156AD2-030 GEN
Solar/Wind Harmer
0.198
316203AE2-005 GEN
Solar/Wind Harmer
3.126
970293AG2-193 GEN
Solar/Wind Harmer
0.926
3150921YORKTN3
Adder
1.622
315773AC2-141 GEN
Solar/Wind Harmer
2.997
970659AG2-427 GEN
Solar/Wind Harmer
0.673
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
32.385
316313AB2-026
Solar/Wind Harmer
0.191
316320Y1-086
Solar/Wind Harmer
0.412
316435W1029_GEN3
Solar/Wind Harmer
1.265
3146516WINFALL
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.73
971157AH1-035 GEN
Solar/Wind Harmer
0.837
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.222
316463AE2-346 GEN
Solar/Wind Harmer
0.107
316140AB2-099
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
-0.002
205917AD1-020 ES
Solar/Wind Helper
0.292
233918AB1-142 GEN
Solar/Wind Helper
0.254
233994AC2-023 GEN
Solar/Wind Helper
0.483
233997TMININ_4.2
Solar/Wind Helper
0.131
233971AC1-093 C
Solar/Wind Helper
0.179
228729W2-030 C
Solar/Wind Helper
0.055
219348LDSOLAR C
Solar/Wind Helper
0.057
959561AF2-247 GEN
Solar/Wind Helper
0.01
20715028HAN_X4-015
Solar/Wind Helper
0.028
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
3150071POSSM 5
Adder
36.095
3150391LDYSMT3
Adder
9.709
316468AD1-105 GEN
Solar/Wind Harmer
0.864
316077AC2-138 C
Solar/Wind Harmer
0.16
316441AF1-014 GEN
Solar/Wind Harmer
0.5
3143526WINTERP
Solar/Wind Harmer
-0.038
316075AC2-137 C
Solar/Wind Harmer
0.2
944641AF1-129 GEN
Adder
30.931
315697AD1-025 GEN
Solar/Wind Harmer
1.464
316316AC1-027 C
Solar/Wind Harmer
0.218
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3144356SAPONY
Solar/Wind Harmer
0.242
972185AH1-677 GEN
Adder
3.416
970099AG2-077 GEN
Solar/Wind Harmer
8.214
3144293JTRSVLE
Adder
0.182
3144293JTRSVLE
Adder
0.153
205916AD1-020 GEN
Solar/Wind Helper
1.357
235020AA1-095 C
Solar/Wind Helper
0.032
20390526W1-045 C
Solar/Wind Helper
0.246
233933AB2-153 GEN
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.297
233946AB2-136 GEN
Solar/Wind Helper
0.286
232408W1-005 C
Solar/Wind Helper
0.255
232410W1-006 C
Solar/Wind Helper
0.255
233939AC1-091 C
Solar/Wind Helper
0.176
963401AG1-189 GEN
Solar/Wind Helper
0.028
963391AG1-188 GEN
Solar/Wind Helper
0.041
20716928W4-060COL
Solar/Wind Helper
0.025
20673828FLE_V3-070
Solar/Wind Helper
0.044
20676128MHD_W3-029
Solar/Wind Helper
0.047
217081WEATEXAS C
Solar/Wind Helper
0.006
3152131X4-039 ST
50/50
2.978
3152121X4-039 GT2
50/50
1.887
971685AH1-345 GEN
Solar/Wind Harmer
0.858
972223AH1-696 GEN
Adder
6.238
3141346CRANES
Adder
0.089
972219AH1-694 GEN
Adder
1.094
3150351NORNECKC2
Adder
0.673
964211AG1-282 GEN
Solar/Wind Harmer
0.228
3143526WINTERP
Solar/Wind Harmer
-0.038
944631AF1-128 GEN
Adder
31.219
971317AH1-138 GEN
Solar/Wind Harmer
0.911
315671AE2-027_GEN
Solar/Wind Harmer
5.45
944591AF1-124 GEN
Solar/Wind Harmer
32.501
316072AD1-144
Solar/Wind Harmer
0.144
939411AE1-173 GEN
Solar/Wind Harmer
35.449
3143336POWHATN
Solar/Wind Harmer
0.841
940641AE2-051 GEN
Solar/Wind Harmer
6.642
971547AH1-271 GEN
Solar/Wind Harmer
1.662
972003AH1-546 GEN
Solar/Wind Harmer
3.284
960081AF2-299 GEN
Solar/Wind Harmer
0.74
316322AB2-045
Solar/Wind Harmer
0.221
3144293JTRSVLE
Adder
0.182
972277AH1-723 GEN
Adder
33.84
233930AB2-032 GEN
Solar/Wind Helper
0.192
233954AC2-188 GEN
Solar/Wind Helper
0.117
230511AF1-262
Solar/Wind Helper
0.007
230434AG1-499 GEN
Solar/Wind Helper
0.114
219258KINSLEYDEP C
Solar/Wind Helper
0.038
219907AC1-030 C
Solar/Wind Helper
0.017
207528AF2-192 GEN
Solar/Wind Helper
0.037
20673628F1S_V4-069
Solar/Wind Helper
0.015
218428ETC SOLAR C
Solar/Wind Helper
0.002
217213AMBOY SO C
Solar/Wind Helper
0.014
316411AF1-147_GEN1
Solar/Wind Harmer
1.107
316415AF1-147_GEN2
Solar/Wind Harmer
1.107
3141426STAFORD
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.251
3141913WHIT STONE
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
0.634
971285AH1-108 GEN
Adder
0.495
957831AF2-077 GEN
Solar/Wind Harmer
0.22
971445AH1-216 GEN
Solar/Wind Harmer
4.438
3151081ELIZAR1
Adder
5.812
3151091ELIZAR2
Adder
5.711
3152611GOSPORTB
Adder
0.807
3152621GOSPORTC
Adder
0.685
3152601GOSPORTA
Adder
0.632
315833AF1-017_GEN
Solar/Wind Harmer
1.345
957871AF2-081 GEN
Solar/Wind Harmer
3.539
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
13.006
970673AG2-436 GEN
Solar/Wind Harmer
14.436
970673AG2-436 GEN
Solar/Wind Harmer
7.309
237085AD2-009_GEN
Solar/Wind Helper
1.037
228754AB1-001 C
Solar/Wind Helper
0.013
219272CLEANLIGHT C
Solar/Wind Helper
0.013
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
315976AC1-164 GENA
Solar/Wind Harmer
7.807
316169AC1-164_GENC
Solar/Wind Harmer
6.744
315975AC1-164 GENB
Solar/Wind Harmer
0.231
3151201GRAVEL4
Adder
4.663
3151211GRAVEL5
Adder
4.604
316349AD2-085 GEN
Solar/Wind Harmer
0.63
316311AC2-079 GEN
Solar/Wind Harmer
3.572
315835AF2-110_GEN
Solar/Wind Harmer
0.881
313526AB2-022
Solar/Wind Harmer
0.19
3146396TANGLEW
Solar/Wind Harmer
0.129
315814AE2-033 C
Solar/Wind Harmer
6.458
3146206CASHIE
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.165
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
959381AF2-229 GEN
Solar/Wind Helper
0.251
960921AF2-383 GEN
Solar/Wind Helper
0.119
203975AE1-071-GEN
Solar/Wind Helper
1.667
205932AD2-116_GEN
Solar/Wind Helper
0.332
232432Z2-076 GEN
Solar/Wind Helper
0.034
234033AF1-007_GEN
Solar/Wind Helper
3.527
966261AG1-495 GEN
Solar/Wind Helper
0.04
971845AH1-439 GEN
Solar/Wind Harmer
0.654
963691AG1-221 GEN
Solar/Wind Harmer
2.324
3150231REMNGT3
Adder
12.096
3150241REMNGT4
Adder
11.278
972199AH1-684 GEN
Adder
1.71
3150371LDYSMT1
Adder
9.399
966881AG1-559 GEN
Solar/Wind Harmer
0.238
971781AH1-399 GEN
Solar/Wind Harmer
0.478
316473AC1-191 GEN
Solar/Wind Harmer
0.81
970009AG2-005 GEN
Solar/Wind Harmer
0.939
3142416OLDCHRC
Solar/Wind Harmer
0.751
3141766HARMONY
Solar/Wind Harmer
0.66
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
3142946ENON
Solar/Wind Harmer
-0.002
315747AE2-019 GEN
50/50
12.918
3141196NOKESVL
Solar/Wind Harmer
-0.045
972217AH1-693 GEN
Adder
1.487
3141316ARNOLDS
Adder
0.173
3151761LOISA E
Adder
9.559
972183AH1-676 GEN
Adder
77.132
3150351NORNECKC2
Adder
0.685
315778AD1-151 GEN
Solar/Wind Harmer
6.281
3144216WINCHST
Adder
0.243
315839AE2-212 C
Solar/Wind Harmer
0.218
3151101ELIZAR3
Adder
5.886
944601AF1-125 GEN
Solar/Wind Harmer
31.879
316258AE1-075 C
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
0.715
966621AG1-532 GEN
Solar/Wind Harmer
0.133
3144293JTRSVLE
Adder
0.182
238221AF1-254 C O1
Solar/Wind Helper
0.191
223402AF1-300 C
Solar/Wind Helper
0.282
226910AB2-157 C
Solar/Wind Helper
0.01
233982AB2-133 GEN
Solar/Wind Helper
0.181
233940AF2-379 C
Solar/Wind Helper
0.031
233952AC2-187 GEN
Solar/Wind Helper
0.117
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.009
219612MATRIX C
Solar/Wind Helper
0.012
20673728F2S_V4-070
Solar/Wind Helper
0.015
219908AB1-139 C
Solar/Wind Helper
0.036
970133AG2-095 GEN
Solar/Wind Harmer
0.82
3151221GRAVEL6
Adder
4.658
315813AE1-149 C
Solar/Wind Harmer
4.484
3145336SMITFLD
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
1.159
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.862
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
316365GEN2_N
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.888
972255AH1-712 GEN
Adder
29.04
237030AB1-096 C
Solar/Wind Helper
0.082
227287AC2-120 GEN
Solar/Wind Helper
0.203
233996TM1833_GEN
Solar/Wind Helper
0.131
232406W1-004 FULL
Solar/Wind Helper
0.255
230430AE1-229_GEN
Solar/Wind Helper
1.678
230415AB2-049 C
Solar/Wind Helper
0.015
219766PARADISE C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.074
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.031
20714528FRN_Y2-051
Solar/Wind Helper
0.028
218438BLK ROCK C
Solar/Wind Helper
0.013
219919AE1-041 FULL
Solar/Wind Helper
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.848
WECLTFEXP_WEC->PJM
CLTF
0.721
LAGNLTFEXP_LAGN->PJM
CLTF
4.834
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.501
NYPJM->LTFIMP_NY
CLTF
2.219
TVALTFEXP_TVA->PJM
CLTF
2.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.78
CPLELTFEXP_CPLE->PJM
CLTF
3.96
SIGELTFEXP_SIGE->PJM
CLTF
0.105
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.603
LGEELTFEXP_LGEE->PJM
CLTF
1.359
MECLTFEXP_MEC->PJM
CLTF
3.353

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2079.09
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
3150021OMF B
50/50
0.216
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
963691AG1-221 GEN
Solar/Wind Harmer
2.312
972199AH1-684 GEN
Adder
1.903
3150371LDYSMT1
Adder
12.251
971781AH1-399 GEN
Solar/Wind Harmer
0.118
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
0.028
970133AG2-095 GEN
Solar/Wind Harmer
0.794
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
3147043LAWRENC
Solar/Wind Harmer
0.044
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
972255AH1-712 GEN
Adder
36.775
959311AF2-222 GEN
Solar/Wind Harmer
6.376
316131AB2-060 GEN
Solar/Wind Harmer
0.224
315724AD1-057 GEN
Solar/Wind Harmer
0.266
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316283AC2-100 C
Solar/Wind Harmer
0.124
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
3152111X4-039 GT1
50/50
1.838
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3132273ORANGE
Solar/Wind Harmer
0.018
316156AD2-030 GEN
Solar/Wind Harmer
0.063
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
0.012
944581AF1-123 GEN
Solar/Wind Harmer
18.149
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.587
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.026
970221AG2-151 GEN
Solar/Wind Harmer
3.817
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
50/50
9.026
3141346CRANES
50/50
0.127
971685AH1-345 GEN
Solar/Wind Harmer
0.73
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.87
3143526WINTERP
Solar/Wind Harmer
0.435
944631AF1-128 GEN
Adder
39.853
971317AH1-138 GEN
Solar/Wind Harmer
0.618
315671AE2-027_GEN
Solar/Wind Harmer
5.273
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.166
940641AE2-051 GEN
Solar/Wind Harmer
6.396
3143336POWHATN
Solar/Wind Harmer
1.412
971547AH1-271 GEN
Solar/Wind Harmer
1.606
960081AF2-299 GEN
Solar/Wind Harmer
0.714
962571AG1-106 GEN
Solar/Wind Harmer
1.046
3145823KELFORD
Solar/Wind Harmer
0.073
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
972277AH1-723 GEN
Adder
42.854
316129AC1-054 GEN
Solar/Wind Harmer
0.27
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
0.404
3147983MERCK5
Solar/Wind Harmer
0.024
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
3140676OCCOQUN
50/50
0.286
3150281M RUN A
Adder
13.357
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
3147666LOUISA
Solar/Wind Harmer
0.355
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
0.008
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.084
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
316388AE2-253 GEN
Solar/Wind Harmer
0.251
316246AF1-032 C
Solar/Wind Harmer
0.036
3130156CHOWAN
Solar/Wind Harmer
0.078
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970087AG2-069 GEN
Solar/Wind Harmer
5.999
957481AF2-042 GEN
Solar/Wind Harmer
19.771
316190AA2-174 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.044
971563AH1-280 GEN
Solar/Wind Harmer
0.77
970685AG2-442 GEN
Solar/Wind Harmer
5.37
3146293MARTNCO
Solar/Wind Harmer
0.067
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3146233WITAKRS
Solar/Wind Harmer
0.278
3145493TOT1
Solar/Wind Harmer
0.31
316049AB1-081 GEN
Solar/Wind Harmer
0.395
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
3150011OMF A
50/50
0.216
970467AG2-304 GEN
50/50
14.788
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
972197AH1-683 GEN
Adder
1.98
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
316192AB2-158 GEN
Solar/Wind Harmer
0.501
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.08
316336AC2-165 C
Solar/Wind Harmer
0.003
3145663CRESWEL
Solar/Wind Harmer
0.215
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
316023GEN1_S
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.075
3145683EARLEYS
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3147043LAWRENC
Adder
0.664
315722AD1-056 GEN
Solar/Wind Harmer
0.448
3146083TARBORO
Solar/Wind Harmer
0.07
316359AB2-059 GEN
Solar/Wind Harmer
0.248
3142053HEARTS
Solar/Wind Harmer
0.122
3150091POSSM6B
50/50
0.848
970317AG2-208 GEN
Solar/Wind Harmer
3.609
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
971223AH1-071 GEN
Solar/Wind Harmer
0.89
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
971741AH1-377 GEN
Solar/Wind Harmer
7.304
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
971489AH1-241 GEN
Solar/Wind Harmer
3.817
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145453TOT5
Solar/Wind Harmer
0.097
961601AG1-000A GEN
Solar/Wind Harmer
1.228
964791AG1-342 GEN
Solar/Wind Harmer
1.322
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
316447AC1-158 HLD
Solar/Wind Harmer
1.014
315651AD1-115 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
3.895
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
1.416
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
970933AG2-581 GEN
Solar/Wind Harmer
6.107
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
316274AC1-208 GEN
Solar/Wind Harmer
0.372
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
3150071POSSM 5
50/50
52.224
3150391LDYSMT3
Adder
12.655
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
0.435
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
0.657
972185AH1-677 GEN
Adder
4.331
970099AG2-077 GEN
Solar/Wind Harmer
7.908
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
316034AC1-036 C
Solar/Wind Harmer
0.005
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
316263AC1-034 GEN
Solar/Wind Harmer
2.624
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
970327AG2-215 GEN
Solar/Wind Harmer
2.824
3141913WHIT STONE
Solar/Wind Harmer
0.085
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
972289AH1-729 GEN
50/50
13.249
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
972195AH1-682 GEN
Adder
1.663
315673AE1-157 GEN
Solar/Wind Harmer
6.396
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.599
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
0.005
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3130086AYDLETT
Solar/Wind Harmer
0.32
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.138
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145493TOT1
Solar/Wind Harmer
0.162
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.042
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
972213AH1-691 GEN
Adder
2.059
944491AF1-114 GEN
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.467
3138133OCRAN
Solar/Wind Harmer
0.025
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
3143873LANEXA
Solar/Wind Harmer
0.051
971281AH1-106 GEN
Solar/Wind Harmer
1.161
316369SG1_INVT
Solar/Wind Harmer
0.003
3143316POE
Solar/Wind Harmer
0.321
319010AE1-072 C
Solar/Wind Harmer
0.403
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
970601AG2-382 GEN
Solar/Wind Harmer
2.811
970581AG2-369 GEN
Solar/Wind Harmer
3.44
316087AB2-174 GEN
Solar/Wind Harmer
0.002
972205AH1-687 GEN
Adder
3.134
3146033SCOT NK
Solar/Wind Harmer
0.29
970181AG2-120 GEN
Solar/Wind Harmer
0.883
3148013FISHERV
Solar/Wind Harmer
0.037
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.162
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.443
946751AF1-339 GEN
Solar/Wind Helper
0.233
3138216PACIFIC
Solar/Wind Harmer
0.025
3150411LDYSMT5
Adder
12.718
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
316223AC1-118
Solar/Wind Harmer
0.064
3141813NORNECK
Solar/Wind Harmer
0.087
962981AG1-147 GEN
Solar/Wind Harmer
3.203
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
971167AH1-042 GEN
Solar/Wind Harmer
7.477
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971283AH1-107 GEN
Solar/Wind Harmer
1.161
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.01
944011AF1-069 GEN
Solar/Wind Harmer
4.709
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
316005AA1-067
Solar/Wind Harmer
0.076
316118AC1-105 GEN
Solar/Wind Harmer
0.176
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
971285AH1-108 GEN
Adder
0.631
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316315AB2-025 C
Solar/Wind Harmer
0.064
941031AE2-094 GEN
Solar/Wind Harmer
14.412
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
971447AH1-217 GEN
Solar/Wind Harmer
2.163
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
3.032
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3148133STUARTS
Solar/Wind Harmer
0.039
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
3150101POSSM6S
50/50
1.296
3150301M RUN C
Adder
13.349
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3141906WESTMOR
Solar/Wind Harmer
0.036
3147666LOUISA
Solar/Wind Harmer
0.204
316404AE1-155 C
Solar/Wind Harmer
0.019
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
4.984
965281AG1-393 GEN
Solar/Wind Harmer
0.877
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
316405AF2-144 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.079
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
970917AG2-570 GEN
Solar/Wind Harmer
6.681
961681AG1-008 GEN
Solar/Wind Harmer
5.587
962331AG1-082 GEN
Solar/Wind Harmer
0.795
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3146926FARMVIL
Solar/Wind Harmer
0.044
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
970257AG2-171 GEN
Solar/Wind Harmer
2.293
315785AD2-033 C
Solar/Wind Harmer
0.582
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3148013FISHERV
Solar/Wind Harmer
0.065
315616AA1-038_C
Solar/Wind Harmer
0
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
3150151POSSMC1
50/50
1.143
316006AB2-029 C
Solar/Wind Harmer
0.001
316045AC1-158 PL2
Solar/Wind Harmer
1.475
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
3146776BUCKING
Solar/Wind Harmer
0.029
316174AB2-169 GEN
Solar/Wind Harmer
0.002
963171AG1-166 GEN
Solar/Wind Harmer
0.385
316494AC1-189 GEN
Solar/Wind Harmer
0.238
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
23779801AA1-109
Solar/Wind Helper
0.218
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
315747AE2-019 GEN
50/50
13.176
3150081POSSM6A
50/50
0.848
972217AH1-693 GEN
50/50
1.756
3141196NOKESVL
Solar/Wind Harmer
0.429
3141316ARNOLDS
Adder
0.229
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
315778AD1-151 GEN
Solar/Wind Harmer
6.579
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
17.869
316258AE1-075 C
Solar/Wind Harmer
0.06
3143336POWHATN
Solar/Wind Harmer
1.2
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
971193AH1-056 GEN
Solar/Wind Harmer
4.404
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
964241AG1-285 GEN
Solar/Wind Harmer
4.753
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.139
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
970053AG2-049 GEN
50/50
2.022
3150381LDYSMT2
Adder
12.172
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.219
315814AE2-033 C
Solar/Wind Harmer
6.204
3146206CASHIE
Solar/Wind Harmer
0.075
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
961791AG1-021 GEN
Solar/Wind Harmer
0.693
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
960921AF2-383 GEN
Solar/Wind Helper
0.279
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.188
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
CPLELTFEXP_CPLE->PJM
CLTF
5.065
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.449

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.15
MW Contribution:8.57
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.354
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.598
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
3150301M RUN C
Adder
13.346
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.876
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970129AG2-093 GEN
Solar/Wind Harmer
5.216
965281AG1-393 GEN
Solar/Wind Harmer
1.155
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
970917AG2-570 GEN
Solar/Wind Harmer
21.109
961681AG1-008 GEN
Solar/Wind Harmer
6.644
962331AG1-082 GEN
Solar/Wind Harmer
1.047
313506AB2-031 GEN
Solar/Wind Harmer
0.667
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
3152111X4-039 GT1
50/50
1.839
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.436
316156AD2-030 GEN
Solar/Wind Harmer
0.254
316203AE2-005 GEN
Solar/Wind Harmer
4.009
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.196
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.644
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.645
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
970317AG2-208 GEN
Solar/Wind Harmer
4.491
3151721LOISA A
Adder
5.569
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
971223AH1-071 GEN
Solar/Wind Harmer
1.172
316240AF1-291 C
Solar/Wind Harmer
0.279
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.442
946751AF1-339 GEN
Solar/Wind Helper
0.233
963691AG1-221 GEN
Solar/Wind Harmer
2.313
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.264
966881AG1-559 GEN
Solar/Wind Harmer
0.309
971781AH1-399 GEN
Solar/Wind Harmer
0.62
970009AG2-005 GEN
Solar/Wind Harmer
1.21
316473AC1-191 GEN
Solar/Wind Harmer
1.04
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.046
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
972255AH1-712 GEN
Adder
36.766
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
316447AC1-158 HLD
Solar/Wind Harmer
2.295
315651AD1-115 GEN
Solar/Wind Harmer
4.661
957411AF2-035 GEN
Solar/Wind Harmer
4.619
958261AF2-120 GEN
Solar/Wind Harmer
3.769
316487AF1-042 GEN
Solar/Wind Harmer
1.275
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3146456SLIGO L269
Solar/Wind Harmer
1.062
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
970933AG2-581 GEN
Solar/Wind Harmer
8.04
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.158
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
972289AH1-729 GEN
50/50
13.252
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
972195AH1-682 GEN
Adder
1.665
315673AE1-157 GEN
Solar/Wind Harmer
7.8
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.598
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
2.975
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
316223AC1-118
Solar/Wind Harmer
0.272
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
957601AF2-054 GEN
Solar/Wind Harmer
0.285
315666AE1-190 GEN
Solar/Wind Harmer
0.287
971167AH1-042 GEN
Solar/Wind Harmer
9.109
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.528
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.271
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.165
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
972193AH1-681 GEN
Adder
1.643
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
315747AE2-019 GEN
50/50
13.179
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
3141316ARNOLDS
Adder
0.23
3150351NORNECKC2
Adder
0.885
3151761LOISA E
Adder
11.412
972183AH1-676 GEN
Adder
92.015
315778AD1-151 GEN
Solar/Wind Harmer
8.005
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
40.553
316258AE1-075 C
Solar/Wind Harmer
0.217
3143336POWHATN
Solar/Wind Harmer
0.9
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3144293JTRSVLE
Adder
0.23
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.139
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
3150071POSSM 5
Adder
49.581
3150391LDYSMT3
Adder
12.669
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
316441AF1-014 GEN
Solar/Wind Harmer
0.641
316075AC2-137 C
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Harmer
-0.049
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
316314AB2-024 C
Solar/Wind Harmer
0.813
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316315AB2-025 C
Solar/Wind Harmer
0.238
941031AE2-094 GEN
Solar/Wind Harmer
16.483
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
Adder
8.569
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.427
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.856
971317AH1-138 GEN
Solar/Wind Harmer
1.163
315671AE2-027_GEN
Solar/Wind Harmer
6.943
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
939411AE1-173 GEN
Solar/Wind Harmer
44.981
940641AE2-051 GEN
Solar/Wind Harmer
8.42
3143336POWHATN
Solar/Wind Harmer
1.059
971547AH1-271 GEN
Solar/Wind Harmer
2.115
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
972213AH1-691 GEN
Adder
2.061
944491AF1-114 GEN
Solar/Wind Harmer
3.051
972189AH1-679 GEN
Adder
1.468
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.528
316369SG1_INVT
Solar/Wind Harmer
1.648
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
970601AG2-382 GEN
Solar/Wind Harmer
3.701
970581AG2-369 GEN
Solar/Wind Harmer
4.528
946281AF1-292 GEN
Solar/Wind Harmer
0.187
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.833
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
316388AE2-253 GEN
Solar/Wind Harmer
0.608
316246AF1-032 C
Solar/Wind Harmer
0.182
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970087AG2-069 GEN
Solar/Wind Harmer
7.898
957481AF2-042 GEN
Solar/Wind Harmer
26.028
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
972201AH1-685 GEN
Adder
2.15
972197AH1-683 GEN
Adder
1.982
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
316192AB2-158 GEN
Solar/Wind Harmer
1.185
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
970053AG2-049 GEN
50/50
2.027
3150381LDYSMT2
Adder
12.185
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.215
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.205
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3144356SAPONY
Solar/Wind Harmer
0.308
972185AH1-677 GEN
Adder
4.33
970099AG2-077 GEN
Solar/Wind Harmer
10.411
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
3150151POSSMC1
Adder
1.085
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
315693AD1-088 GEN
Solar/Wind Harmer
1.373
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
964061AG1-260 GEN
Solar/Wind Helper
0.035
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
CPLELTFEXP_CPLE->PJM
CLTF
5.064
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.448

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.08
MW Contribution:8.57
Bus #Bus NameTypeMW Contribution
3150301M RUN C
Adder
13.346
3150401LDYSMT4
Adder
12.694
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.876
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970129AG2-093 GEN
Solar/Wind Harmer
5.216
965281AG1-393 GEN
Solar/Wind Harmer
1.155
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151171GRAVELC
Adder
1.142
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.229
3152111X4-039 GT1
50/50
1.839
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3150331BIRCHWDA
Adder
16.699
3150291M RUN B
Adder
13.246
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.436
316156AD2-030 GEN
Solar/Wind Harmer
0.254
316203AE2-005 GEN
Solar/Wind Harmer
4.009
970293AG2-193 GEN
Solar/Wind Harmer
1.184
970317AG2-208 GEN
Solar/Wind Harmer
4.491
3151721LOISA A
Adder
5.568
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3150671DARBY 1
Adder
6.041
971223AH1-071 GEN
Solar/Wind Harmer
1.172
316240AF1-291 C
Solar/Wind Harmer
0.279
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.184
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.205
237001AB1-127_GEN
Solar/Wind Helper
0.307
235063AE1-101 C2
Solar/Wind Helper
1.064
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
209029WAYMART-WD
Solar/Wind Helper
0.442
946751AF1-339 GEN
Solar/Wind Helper
0.233
963691AG1-221 GEN
Solar/Wind Harmer
2.313
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.265
966881AG1-559 GEN
Solar/Wind Harmer
0.309
971781AH1-399 GEN
Solar/Wind Harmer
0.62
970009AG2-005 GEN
Solar/Wind Harmer
1.21
316473AC1-191 GEN
Solar/Wind Harmer
1.04
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.046
3151221GRAVEL6
Adder
5.934
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
972255AH1-712 GEN
Adder
36.765
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.304
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.783
209067AE2-060 GEN
Solar/Wind Helper
0.042
316447AC1-158 HLD
Solar/Wind Harmer
2.294
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
970917AG2-570 GEN
Solar/Wind Harmer
21.109
961681AG1-008 GEN
Solar/Wind Harmer
6.644
962331AG1-082 GEN
Solar/Wind Harmer
1.047
313506AB2-031 GEN
Solar/Wind Harmer
0.667
235067AD1-061 GEN
Solar/Wind Helper
0.312
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
972289AH1-729 GEN
50/50
13.252
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
972195AH1-682 GEN
Adder
1.665
315673AE1-157 GEN
Solar/Wind Harmer
7.801
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.597
3150681DARBY 2
Adder
6.048
316033AB2-134 GEN
Solar/Wind Harmer
2.975
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.298
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.178
209137AF2-361 C
Solar/Wind Helper
0.708
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
972223AH1-696 GEN
Adder
8.574
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.427
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.856
971317AH1-138 GEN
Solar/Wind Harmer
1.163
315671AE2-027_GEN
Solar/Wind Harmer
6.943
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
939411AE1-173 GEN
Solar/Wind Harmer
44.98
940641AE2-051 GEN
Solar/Wind Harmer
8.42
3143336POWHATN
Solar/Wind Harmer
1.059
971547AH1-271 GEN
Solar/Wind Harmer
2.115
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.139
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
972213AH1-691 GEN
Adder
2.061
944491AF1-114 GEN
Solar/Wind Harmer
3.051
972189AH1-679 GEN
Adder
1.468
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.528
316369SG1_INVT
Solar/Wind Harmer
1.648
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
970601AG2-382 GEN
Solar/Wind Harmer
3.701
970581AG2-369 GEN
Solar/Wind Harmer
4.528
946281AF1-292 GEN
Solar/Wind Harmer
0.187
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
205943AE1-185 GEN
Solar/Wind Helper
0.387
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.354
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.597
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
316381AD1-082 GEN
Solar/Wind Harmer
0.833
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
316388AE2-253 GEN
Solar/Wind Harmer
0.608
316246AF1-032 C
Solar/Wind Harmer
0.182
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970087AG2-069 GEN
Solar/Wind Harmer
7.898
957481AF2-042 GEN
Solar/Wind Harmer
26.028
223401AF1-299 GEN
Solar/Wind Helper
0.397
235062AE1-101 C1
Solar/Wind Helper
1.064
233915AB1-141 GEN
Solar/Wind Helper
0.303
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.9
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
972197AH1-683 GEN
Adder
1.982
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
316192AB2-158 GEN
Solar/Wind Harmer
1.185
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.082
217208PARK ELE C
Solar/Wind Helper
0.003
970053AG2-049 GEN
50/50
2.028
3150071POSSM 5
Adder
49.613
3150391LDYSMT3
Adder
12.67
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
316441AF1-014 GEN
Solar/Wind Harmer
0.641
316075AC2-137 C
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.415
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3144356SAPONY
Solar/Wind Harmer
0.308
972185AH1-677 GEN
Adder
4.33
970099AG2-077 GEN
Solar/Wind Harmer
10.411
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
205916AD1-020 GEN
Solar/Wind Helper
1.48
20390526W1-045 C
Solar/Wind Helper
0.252
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
233946AB2-136 GEN
Solar/Wind Helper
0.341
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.097
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.236
3150151POSSMC1
Adder
1.085
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3150851SPRUNCC
Adder
0.385
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3150921YORKTN3
Adder
2.069
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.195
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.644
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.645
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.234
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
316223AC1-118
Solar/Wind Harmer
0.272
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
957601AF2-054 GEN
Solar/Wind Harmer
0.285
315666AE1-190 GEN
Solar/Wind Harmer
0.287
971167AH1-042 GEN
Solar/Wind Harmer
9.109
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.528
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
972265AH1-717 GEN
Adder
6.337
3151191GRAVEL3
Adder
5.865
316305AF2-043 C
Solar/Wind Harmer
0.271
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.164
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
3150381LDYSMT2
Adder
12.186
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.215
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
3151201GRAVEL4
Adder
5.94
3151211GRAVEL5
Adder
5.865
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.205
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
203975AE1-071-GEN
Solar/Wind Helper
1.713
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
315651AD1-115 GEN
Solar/Wind Harmer
4.661
957411AF2-035 GEN
Solar/Wind Harmer
4.62
958261AF2-120 GEN
Solar/Wind Harmer
3.769
316487AF1-042 GEN
Solar/Wind Harmer
1.275
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3146456SLIGO L269
Solar/Wind Harmer
1.062
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
970933AG2-581 GEN
Solar/Wind Harmer
8.04
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.158
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
315747AE2-019 GEN
50/50
13.179
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
3141316ARNOLDS
Adder
0.23
3150351NORNECKC2
Adder
0.885
3151761LOISA E
Adder
11.411
972183AH1-676 GEN
Adder
92.013
315778AD1-151 GEN
Solar/Wind Harmer
8.005
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
3151101ELIZAR3
Adder
7.489
944601AF1-125 GEN
Solar/Wind Harmer
40.552
316258AE1-075 C
Solar/Wind Harmer
0.217
3143336POWHATN
Solar/Wind Harmer
0.9
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3144293JTRSVLE
Adder
0.23
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.397
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.216
233952AC2-187 GEN
Solar/Wind Helper
0.139
233940AF2-379 C
Solar/Wind Helper
0.037
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.557
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
238208AF1-136 C
Solar/Wind Helper
0.089
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
316314AB2-024 C
Solar/Wind Harmer
0.813
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316315AB2-025 C
Solar/Wind Harmer
0.238
941031AE2-094 GEN
Solar/Wind Harmer
16.482
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
237085AD2-009_GEN
Solar/Wind Helper
0.97
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.004
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
972193AH1-681 GEN
Adder
1.643
3151861LOWMORA
Adder
0.62
205956AE1-196_GEN
Solar/Wind Helper
0.385
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.233
970919AG2-571 GEN
Solar/Wind Harmer
2.672
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
315693AD1-088 GEN
Solar/Wind Harmer
1.373
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
NYPJM->LTFIMP_NY
CLTF
2.575
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
CPLELTFEXP_CPLE->PJM
CLTF
5.064
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
LGEELTFEXP_LGEE->PJM
CLTF
1.805
MECLTFEXP_MEC->PJM
CLTF
4.448

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.69 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2110.99
MW Contribution:8.4
Bus #Bus NameTypeMW Contribution
970317AG2-208 GEN
Solar/Wind Harmer
4.447
3151721LOISA A
Adder
5.554
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
3150671DARBY 1
Adder
5.994
971223AH1-071 GEN
Solar/Wind Harmer
1.164
316240AF1-291 C
Solar/Wind Harmer
0.277
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.17
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
226929AD2-058 GEN
Solar/Wind Helper
0.143
237034AC2-136 C
Solar/Wind Helper
0.204
237001AB1-127_GEN
Solar/Wind Helper
0.306
235063AE1-101 C2
Solar/Wind Helper
1.061
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.188
963691AG1-221 GEN
Solar/Wind Harmer
2.318
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
3150371LDYSMT1
Adder
12.133
966881AG1-559 GEN
Solar/Wind Harmer
0.306
971781AH1-399 GEN
Solar/Wind Harmer
0.614
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.038
3151221GRAVEL6
Adder
5.89
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
972255AH1-712 GEN
Adder
36.554
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
233996TM1833_GEN
Solar/Wind Helper
0.156
232406W1-004 FULL
Solar/Wind Helper
0.303
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.78
209067AE2-060 GEN
Solar/Wind Helper
0.042
3150301M RUN C
Adder
13.368
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
1.859
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
3141843SHACKLE
Adder
0.429
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970129AG2-093 GEN
Solar/Wind Harmer
5.177
972289AH1-729 GEN
50/50
13.276
3150181POSSMC2
Adder
1.072
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
972223AH1-696 GEN
Adder
8.401
3141346CRANES
Adder
0.118
971685AH1-345 GEN
Solar/Wind Harmer
0.962
972219AH1-694 GEN
Adder
1.412
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3143526WINTERP
Solar/Wind Harmer
-0.048
944631AF1-128 GEN
Adder
39.551
971317AH1-138 GEN
Solar/Wind Harmer
1.154
315671AE2-027_GEN
Solar/Wind Harmer
6.892
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.674
940641AE2-051 GEN
Solar/Wind Harmer
8.364
3143336POWHATN
Solar/Wind Harmer
1.052
971547AH1-271 GEN
Solar/Wind Harmer
2.101
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
233930AB2-032 GEN
Solar/Wind Helper
0.229
233954AC2-188 GEN
Solar/Wind Helper
0.139
3140676OCCOQUN
Adder
0.27
3150281M RUN A
Adder
13.376
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
3147666LOUISA
Solar/Wind Harmer
-0.04
3151751LOISA D
Adder
5.583
3138133OCRAN
Solar/Wind Harmer
-0.006
3141843SHACKLE
Adder
0.429
3143096IRON208
Adder
0.349
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.248
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
316381AD1-082 GEN
Solar/Wind Harmer
0.827
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
316388AE2-253 GEN
Solar/Wind Harmer
0.603
316246AF1-032 C
Solar/Wind Harmer
0.181
3130156CHOWAN
Solar/Wind Harmer
-0.009
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970087AG2-069 GEN
Solar/Wind Harmer
7.848
957481AF2-042 GEN
Solar/Wind Harmer
25.866
223401AF1-299 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.061
233915AB1-141 GEN
Solar/Wind Helper
0.302
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
233972AC1-094 C
Solar/Wind Helper
0.18
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.897
212266LOR1
Solar/Wind Helper
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
972197AH1-683 GEN
Adder
1.961
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
316192AB2-158 GEN
Solar/Wind Harmer
1.181
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.521
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.301
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.081
217208PARK ELE C
Solar/Wind Helper
0.003
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.016
207437AD2-070 GEN
Solar/Wind Helper
0.079
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.232
3150071POSSM 5
Adder
48.607
3150391LDYSMT3
Adder
12.533
316468AD1-105 GEN
Solar/Wind Harmer
1.109
316077AC2-138 C
Solar/Wind Harmer
0.205
316441AF1-014 GEN
Solar/Wind Harmer
0.636
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
944641AF1-129 GEN
Adder
39.124
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3144356SAPONY
Solar/Wind Harmer
0.306
972185AH1-677 GEN
Adder
4.302
970099AG2-077 GEN
Solar/Wind Harmer
10.347
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
205916AD1-020 GEN
Solar/Wind Helper
1.477
20390526W1-045 C
Solar/Wind Helper
0.251
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
233946AB2-136 GEN
Solar/Wind Helper
0.34
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.096
20676228FRD_X1-012
Solar/Wind Helper
0.052
3152111X4-039 GT1
50/50
1.841
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
316484AD2-074 GEN
Solar/Wind Harmer
2.414
316156AD2-030 GEN
Solar/Wind Harmer
0.252
316203AE2-005 GEN
Solar/Wind Harmer
3.975
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3150921YORKTN3
Adder
2.053
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.904
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.6
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
3146263WOODLND
Solar/Wind Harmer
-0.008
3151861LOWMORA
Adder
0.643
205917AD1-020 ES
Solar/Wind Helper
0.318
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233997TMININ_4.2
Solar/Wind Helper
0.156
233971AC1-093 C
Solar/Wind Helper
0.213
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.233
970053AG2-049 GEN
50/50
2.02
3150381LDYSMT2
Adder
12.055
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.213
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
3151201GRAVEL4
Adder
5.897
3151211GRAVEL5
Adder
5.822
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.149
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.209
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960921AF2-383 GEN
Solar/Wind Helper
0.139
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
203975AE1-071-GEN
Solar/Wind Helper
1.709
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
957411AF2-035 GEN
Solar/Wind Harmer
4.574
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3146456SLIGO L269
Solar/Wind Harmer
1.055
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
7.988
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.151
237025AB1-124 C
Solar/Wind Helper
0.193
23777801MSM_W1-116
Solar/Wind Helper
0.13
230407AD2-065 C
Solar/Wind Helper
0.024
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
961431AF2-434 GEN
Solar/Wind Helper
0.235
315747AE2-019 GEN
50/50
13.211
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.657
3141316ARNOLDS
Adder
0.227
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
315778AD1-151 GEN
Solar/Wind Harmer
7.946
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
3151101ELIZAR3
Adder
7.435
944601AF1-125 GEN
Solar/Wind Harmer
40.266
316258AE1-075 C
Solar/Wind Harmer
0.215
3143336POWHATN
Solar/Wind Harmer
0.895
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3144293JTRSVLE
Adder
0.228
226910AB2-157 C
Solar/Wind Helper
0.02
223402AF1-300 C
Solar/Wind Helper
0.396
238221AF1-254 C O1
Solar/Wind Helper
0.179
233982AB2-133 GEN
Solar/Wind Helper
0.215
233952AC2-187 GEN
Solar/Wind Helper
0.139
233940AF2-379 C
Solar/Wind Helper
0.037
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.555
961421AF2-433 GEN
Solar/Wind Helper
0.235
946691AF1-333 GEN
Solar/Wind Helper
0.232
972213AH1-691 GEN
Adder
2.039
944491AF1-114 GEN
Solar/Wind Harmer
3.014
972189AH1-679 GEN
Adder
1.455
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.517
316369SG1_INVT
Solar/Wind Harmer
1.636
3143316POE
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
1.806
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
970601AG2-382 GEN
Solar/Wind Harmer
3.676
970581AG2-369 GEN
Solar/Wind Harmer
4.499
946281AF1-292 GEN
Solar/Wind Harmer
0.186
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.386
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.564
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
238208AF1-136 C
Solar/Wind Helper
0.089
946741AF1-338 GEN
Solar/Wind Helper
0.232
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.596
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
316223AC1-118
Solar/Wind Harmer
0.269
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
957601AF2-054 GEN
Solar/Wind Harmer
0.282
315666AE1-190 GEN
Solar/Wind Harmer
0.284
971167AH1-042 GEN
Solar/Wind Harmer
9.035
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971283AH1-107 GEN
Solar/Wind Harmer
1.517
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
972265AH1-717 GEN
Adder
6.291
3151191GRAVEL3
Adder
5.822
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.131
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
972193AH1-681 GEN
Adder
1.633
3151861LOWMORA
Adder
0.618
205956AE1-196_GEN
Solar/Wind Helper
0.384
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
207530AG1-191 GEN
Solar/Wind Helper
0.038
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.232
3150151POSSMC1
Adder
1.063
316006AB2-029 C
Solar/Wind Harmer
0.631
316045AC1-158 PL2
Solar/Wind Harmer
3.331
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.609
3150851SPRUNCC
Adder
0.383
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
3146263WOODLND
Solar/Wind Harmer
-0.008
23779801AA1-109
Solar/Wind Helper
0.217
237038AE2-054 C
Solar/Wind Helper
0.173
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.236
212507AE2-042_GEN
Solar/Wind Helper
0.826
315693AD1-088 GEN
Solar/Wind Harmer
1.364
209029WAYMART-WD
Solar/Wind Helper
0.441
946751AF1-339 GEN
Solar/Wind Helper
0.232
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3150681DARBY 2
Adder
6.001
316033AB2-134 GEN
Solar/Wind Harmer
2.953
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
237006AB1-125 GEN
Solar/Wind Helper
0.145
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237002AB1-128_GEN
Solar/Wind Helper
0.297
23777901MDS_W4-102
Solar/Wind Helper
0.105
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.177
209137AF2-361 C
Solar/Wind Helper
0.706
965281AG1-393 GEN
Solar/Wind Harmer
1.147
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151171GRAVELC
Adder
1.133
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
970917AG2-570 GEN
Solar/Wind Harmer
20.974
961681AG1-008 GEN
Solar/Wind Harmer
6.6
962331AG1-082 GEN
Solar/Wind Harmer
1.04
313506AB2-031 GEN
Solar/Wind Harmer
0.663
235067AD1-061 GEN
Solar/Wind Helper
0.311
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.241
961331AF2-424 GEN
Solar/Wind Helper
0.236
957871AF2-081 GEN
Solar/Wind Harmer
4.471
316315AB2-025 C
Solar/Wind Harmer
0.237
941031AE2-094 GEN
Solar/Wind Harmer
16.374
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
237085AD2-009_GEN
Solar/Wind Helper
0.968
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.029
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
1.001
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
WECLTFEXP_WEC->PJM
CLTF
0.96
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
NYPJM->LTFIMP_NY
CLTF
2.566
TVALTFEXP_TVA->PJM
CLTF
3.177
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
CPLELTFEXP_CPLE->PJM
CLTF
5.037
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853
LGEELTFEXP_LGEE->PJM
CLTF
1.801
MECLTFEXP_MEC->PJM
CLTF
4.438

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.48 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2034.78
MW Contribution:5.63
Bus #Bus NameTypeMW Contribution
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
315683AE1-153 C
Solar/Wind Harmer
8.082
316192AB2-158 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.435
966881AG1-559 GEN
Solar/Wind Harmer
0.078
972135AH1-637 GEN
Solar/Wind Harmer
0.75
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
316375AC2-012 GEN
Solar/Wind Harmer
2.44
316336AC2-165 C
Solar/Wind Harmer
1.222
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3145663CRESWEL
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.53
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
232422X3-066 FULL
Solar/Wind Helper
0.069
3152111X4-039 GT1
50/50
1.829
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.713
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
970737AG2-469 GEN
Solar/Wind Harmer
3.736
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970293AG2-193 GEN
Solar/Wind Harmer
0.907
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3150921YORKTN3
Adder
1.597
316313AB2-026
Solar/Wind Harmer
0.191
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
957411AF2-035 GEN
Solar/Wind Harmer
3.403
958261AF2-120 GEN
Solar/Wind Harmer
2.834
316487AF1-042 GEN
Solar/Wind Harmer
0.961
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3146456SLIGO L269
Solar/Wind Harmer
0.828
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
237025AB1-124 C
Solar/Wind Helper
0.233
23777801MSM_W1-116
Solar/Wind Helper
0.156
230407AD2-065 C
Solar/Wind Helper
0.024
3150071POSSM 5
Adder
32.578
3150391LDYSMT3
Adder
9.175
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3143526WINTERP
Solar/Wind Harmer
-0.038
3147346CASHSCORNER
Solar/Wind Harmer
0.123
972213AH1-691 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
972189AH1-679 GEN
Adder
1.104
971281AH1-106 GEN
Solar/Wind Harmer
1.184
3138133OCRAN
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
3141873WAN 176
Solar/Wind Harmer
-0.001
315747AE2-019 GEN
50/50
12.54
3141196NOKESVL
Solar/Wind Harmer
-0.043
972217AH1-693 GEN
Adder
1.452
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3141316ARNOLDS
Adder
0.162
3150351NORNECKC2
Adder
0.662
315778AD1-151 GEN
Solar/Wind Harmer
6.188
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
316258AE1-075 C
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
0.715
3151101ELIZAR3
Adder
5.827
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3144293JTRSVLE
Adder
0.186
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
238221AF1-254 C O1
Solar/Wind Helper
0.197
233982AB2-133 GEN
Solar/Wind Helper
0.216
233940AF2-379 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.14
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.011
219612MATRIX C
Solar/Wind Helper
0.014
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
207510AF2-138 C
Solar/Wind Helper
0.046
209027LOR2_Q27
Solar/Wind Helper
0.55
961421AF2-433 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.23
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3150411LDYSMT5
Adder
9.22
972215AH1-692 GEN
Adder
1.493
316223AC1-118
Solar/Wind Harmer
0.2
316006AB2-029 C
Solar/Wind Harmer
0.549
316045AC1-158 PL2
Solar/Wind Harmer
2.734
3150151POSSMC1
Adder
0.713
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
3150851SPRUNCC
Adder
0.297
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
23779801AA1-109
Solar/Wind Helper
0.261
237038AE2-054 C
Solar/Wind Helper
0.19
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
207445AB1-138_GEN
Solar/Wind Helper
0.061
20676428JCR_X2-075
Solar/Wind Helper
0.039
217209CENTRL HS C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.011
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
3151721LOISA A
Adder
4.628
970317AG2-208 GEN
Solar/Wind Harmer
3.309
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.207
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3150671DARBY 1
Adder
4.629
316240AF1-291 C
Solar/Wind Harmer
0.216
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
971761AH1-387 GEN
Solar/Wind Harmer
3.885
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
972187AH1-678 GEN
Adder
1.728
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
971741AH1-377 GEN
Solar/Wind Harmer
7.747
237034AC2-136 C
Solar/Wind Helper
0.239
237001AB1-127_GEN
Solar/Wind Helper
0.342
226929AD2-058 GEN
Solar/Wind Helper
0.078
235063AE1-101 C2
Solar/Wind Helper
1.169
233987AB2-037 GEN
Solar/Wind Helper
1.409
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
20720628TIN_W1-124
Solar/Wind Helper
0.11
207442AE1-156 GEN
Solar/Wind Helper
0.187
20671828STAW2-080
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
209029WAYMART-WD
Solar/Wind Helper
0.437
946751AF1-339 GEN
Solar/Wind Helper
0.23
316369SG1_INVT
Solar/Wind Harmer
1.275
3143316POE
Solar/Wind Harmer
-0.028
319010AE1-072 C
Solar/Wind Harmer
1.418
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
970581AG2-369 GEN
Solar/Wind Harmer
3.599
970601AG2-382 GEN
Solar/Wind Harmer
2.928
205943AE1-185 GEN
Solar/Wind Helper
0.409
233990AG1-397 GEN
Solar/Wind Helper
0.018
964001AG1-254 GEN
Solar/Wind Helper
0.565
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
214067T20SOLAR
Solar/Wind Helper
0.007
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
3150281M RUN A
Adder
11.705
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
3147666LOUISA
Solar/Wind Harmer
-0.032
3151751LOISA D
Adder
4.652
957971AF2-091 GEN
Solar/Wind Harmer
0.75
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.193
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
316381AD1-082 GEN
Solar/Wind Harmer
0.648
3150981CHESPKA
Adder
0.784
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316388AE2-253 GEN
Solar/Wind Harmer
0.474
316246AF1-032 C
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
-0.007
971163AH1-040 GEN
Solar/Wind Harmer
6.359
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146926FARMVIL
Solar/Wind Harmer
-0.004
223401AF1-299 GEN
Solar/Wind Helper
0.385
235062AE1-101 C1
Solar/Wind Helper
1.169
233915AB1-141 GEN
Solar/Wind Helper
0.304
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
233972AC1-094 C
Solar/Wind Helper
0.181
228728W1-130C
Solar/Wind Helper
0.032
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
963711AG1-223 GEN
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20675428EAM_W2-061
Solar/Wind Helper
0.009
207518AF1-320_GEN
Solar/Wind Helper
0.893
212266LOR1
Solar/Wind Helper
0.025
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
972289AH1-729 GEN
50/50
13.169
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
3150681DARBY 2
Adder
4.634
316033AB2-134 GEN
Solar/Wind Harmer
2.301
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
3.335
237006AB1-125 GEN
Solar/Wind Helper
0.175
237002AB1-128_GEN
Solar/Wind Helper
0.33
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
23777901MDS_W4-102
Solar/Wind Helper
0.113
232424Y1-079 C
Solar/Wind Helper
0.07
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
20674928WA_W3-044
Solar/Wind Helper
0.056
966111AG1-480 GEN
Solar/Wind Helper
0.025
208972BECR K09
Solar/Wind Helper
0.176
209137AF2-361 C
Solar/Wind Helper
0.703
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.046
209054AE2-059 GEN
Solar/Wind Helper
0.042
963691AG1-221 GEN
Solar/Wind Harmer
2.26
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
3150371LDYSMT1
Adder
8.882
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.459
316473AC1-191 GEN
Solar/Wind Harmer
0.788
970009AG2-005 GEN
Solar/Wind Harmer
0.912
3142416OLDCHRC
Solar/Wind Harmer
0.734
3141766HARMONY
Solar/Wind Harmer
0.645
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.807
3151221GRAVEL6
Adder
4.598
315813AE1-149 C
Solar/Wind Harmer
4.431
3145336SMITFLD
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
237030AB1-096 C
Solar/Wind Helper
0.1
227287AC2-120 GEN
Solar/Wind Helper
0.309
233996TM1833_GEN
Solar/Wind Helper
0.157
232406W1-004 FULL
Solar/Wind Helper
0.305
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
218438BLK ROCK C
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.051
963071AG1-156 GEN
Solar/Wind Helper
0.773
209067AE2-060 GEN
Solar/Wind Helper
0.042
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
3141426STAFORD
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.245
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
957831AF2-077 GEN
Solar/Wind Harmer
0.216
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
957871AF2-081 GEN
Solar/Wind Harmer
3.509
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
237085AD2-009_GEN
Solar/Wind Helper
1.049
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
20675928HOL_W4-097
Solar/Wind Helper
0.028
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
209116AE2-175 GEN
Solar/Wind Helper
0.994
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
971685AH1-345 GEN
Solar/Wind Harmer
0.837
972223AH1-696 GEN
Adder
5.63
3141346CRANES
Adder
0.082
972219AH1-694 GEN
Adder
1.033
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3143526WINTERP
Solar/Wind Harmer
-0.038
944631AF1-128 GEN
Adder
30.629
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
3143336POWHATN
Solar/Wind Harmer
0.841
944591AF1-124 GEN
Solar/Wind Harmer
32.182
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
971547AH1-271 GEN
Solar/Wind Harmer
1.673
972277AH1-723 GEN
Adder
35.15
3144293JTRSVLE
Adder
0.186
233930AB2-032 GEN
Solar/Wind Helper
0.23
233954AC2-188 GEN
Solar/Wind Helper
0.14
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219907AC1-030 C
Solar/Wind Helper
0.02
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.016
207437AD2-070 GEN
Solar/Wind Helper
0.078
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.23
970053AG2-049 GEN
Adder
1.475
3150381LDYSMT2
Adder
8.824
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.164
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3151201GRAVEL4
Adder
4.603
3151211GRAVEL5
Adder
4.545
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146396TANGLEW
Solar/Wind Harmer
0.128
315814AE2-033 C
Solar/Wind Harmer
6.44
971845AH1-439 GEN
Solar/Wind Harmer
3.571
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.167
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205932AD2-116_GEN
Solar/Wind Helper
0.406
203975AE1-071-GEN
Solar/Wind Helper
1.871
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
966261AG1-495 GEN
Solar/Wind Helper
0.047
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971283AH1-107 GEN
Solar/Wind Harmer
1.184
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
971167AH1-042 GEN
Solar/Wind Harmer
6.965
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
972265AH1-717 GEN
Adder
4.91
3151191GRAVEL3
Adder
4.545
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
944011AF1-069 GEN
Solar/Wind Harmer
4.067
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970085AG2-068 GEN
Solar/Wind Harmer
4.185
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
205956AE1-196_GEN
Solar/Wind Helper
0.406
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
219914AD2-027 C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
20715728PEM_W1-119
Solar/Wind Helper
0.056
20675528CPH_W2-050
Solar/Wind Helper
0.05
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
207530AG1-191 GEN
Solar/Wind Helper
0.037
20675128HRM_W1-127
Solar/Wind Helper
0.017
959421AF2-233 GEN
Solar/Wind Helper
0.229
3150301M RUN C
Adder
11.698
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3147666LOUISA
Solar/Wind Harmer
-0.018
3150401LDYSMT4
Adder
9.192
3141906WESTMOR
Solar/Wind Harmer
-0.003
316404AE1-155 C
Solar/Wind Harmer
1.411
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3150861SPRUNCD
Adder
0.297
316280AD1-041 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
316382AG1-145 C
Solar/Wind Harmer
0.216
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151171GRAVELC
Adder
0.885
316405AF2-144 C
Solar/Wind Harmer
0.182
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
3146926FARMVIL
Solar/Wind Harmer
-0.004
961681AG1-008 GEN
Solar/Wind Harmer
5.262
235067AD1-061 GEN
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.023
219276PARKLANDSO C
Solar/Wind Helper
0.052
20720528MAN_W1-024
Solar/Wind Helper
0.016
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
963161AG1-165 GEN
Solar/Wind Helper
0.239
961331AF2-424 GEN
Solar/Wind Helper
0.233
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
20676328BVR_Y1-020
Solar/Wind Helper
0.015
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
238208AF1-136 C
Solar/Wind Helper
0.089
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
944641AF1-129 GEN
Adder
30.436
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3144356SAPONY
Solar/Wind Harmer
0.242
972185AH1-677 GEN
Adder
3.421
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
205916AD1-020 GEN
Solar/Wind Helper
1.658
20390526W1-045 C
Solar/Wind Helper
0.277
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
233946AB2-136 GEN
Solar/Wind Helper
0.342
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
20676128MHD_W3-029
Solar/Wind Helper
0.055
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.096
20676228FRD_X1-012
Solar/Wind Helper
0.052
961431AF2-434 GEN
Solar/Wind Helper
0.233
970099AG2-077 GEN
Solar/Wind Harmer
2.284
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
32.067
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.262
205917AD1-020 ES
Solar/Wind Helper
0.357
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233997TMININ_4.2
Solar/Wind Helper
0.157
233971AC1-093 C
Solar/Wind Helper
0.214
228729W2-030 C
Solar/Wind Helper
0.065
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715028HAN_X4-015
Solar/Wind Helper
0.033
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.23
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
219904AC1-010 C
Solar/Wind Helper
0.036
20720728JCB_W1-129
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.081
217208PARK ELE C
Solar/Wind Helper
0.003
946741AF1-338 GEN
Solar/Wind Helper
0.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
NYPJM->LTFIMP_NY
CLTF
2.532
TVALTFEXP_TVA->PJM
CLTF
2.938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
WECLTFEXP_WEC->PJM
CLTF
0.941
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691
LGEELTFEXP_LGEE->PJM
CLTF
1.753
MECLTFEXP_MEC->PJM
CLTF
4.292
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
CPLELTFEXP_CPLE->PJM
CLTF
4.229
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1909.41
MW Contribution:6.7
Bus #Bus NameTypeMW Contribution
316006AB2-029 C
Solar/Wind Harmer
0.632
316045AC1-158 PL2
Solar/Wind Harmer
3.177
3150151POSSMC1
Adder
0.848
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
3150851SPRUNCC
Adder
0.351
970659AG2-427 GEN
Solar/Wind Harmer
4.431
3150281M RUN A
Adder
13.444
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
3147666LOUISA
Solar/Wind Harmer
-0.038
3151751LOISA D
Adder
5.425
957971AF2-091 GEN
Solar/Wind Harmer
0.888
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138133OCRAN
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.389
3143096IRON208
Adder
0.319
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.227
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
971685AH1-345 GEN
Solar/Wind Harmer
0.963
972223AH1-696 GEN
Adder
6.699
3141346CRANES
Adder
0.098
972219AH1-694 GEN
Adder
1.223
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3143526WINTERP
Solar/Wind Harmer
-0.044
944631AF1-128 GEN
Adder
36.159
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
3143336POWHATN
Solar/Wind Harmer
0.991
944591AF1-124 GEN
Solar/Wind Harmer
37.981
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
971547AH1-271 GEN
Solar/Wind Harmer
1.976
972277AH1-723 GEN
Adder
41.593
3144293JTRSVLE
Adder
0.22
233930AB2-032 GEN
Solar/Wind Helper
0.301
233954AC2-188 GEN
Solar/Wind Helper
0.183
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219907AC1-030 C
Solar/Wind Helper
0.026
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
963691AG1-221 GEN
Solar/Wind Harmer
2.52
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
971781AH1-399 GEN
Solar/Wind Harmer
0.543
316473AC1-191 GEN
Solar/Wind Harmer
0.931
970009AG2-005 GEN
Solar/Wind Harmer
1.078
3142416OLDCHRC
Solar/Wind Harmer
0.867
3141766HARMONY
Solar/Wind Harmer
0.762
970053AG2-049 GEN
Adder
1.707
3150381LDYSMT2
Adder
10.439
3151721LOISA A
Adder
5.397
970317AG2-208 GEN
Solar/Wind Harmer
3.912
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3150671DARBY 1
Adder
5.465
316240AF1-291 C
Solar/Wind Harmer
0.255
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
3142956BIRDNECK
Solar/Wind Harmer
0.446
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
971761AH1-387 GEN
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
2.039
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
971741AH1-377 GEN
Solar/Wind Harmer
9.144
237034AC2-136 C
Solar/Wind Helper
0.157
233987AB2-037 GEN
Solar/Wind Helper
1.847
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
20720628TIN_W1-124
Solar/Wind Helper
0.143
207442AE1-156 GEN
Solar/Wind Helper
0.243
20671828STAW2-080
Solar/Wind Helper
0.02
226929AD2-058 GEN
Solar/Wind Helper
0.066
20674128FR_U2-059
Solar/Wind Helper
0.003
3150301M RUN C
Adder
13.435
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3147666LOUISA
Solar/Wind Harmer
-0.022
3150401LDYSMT4
Adder
10.874
3147346CASHSCORNER
Solar/Wind Harmer
0.143
972213AH1-691 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
972189AH1-679 GEN
Adder
1.305
971281AH1-106 GEN
Solar/Wind Harmer
1.396
3138133OCRAN
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.031
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
316369SG1_INVT
Solar/Wind Harmer
1.505
3143316POE
Solar/Wind Harmer
-0.033
319010AE1-072 C
Solar/Wind Harmer
1.673
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
205943AE1-185 GEN
Solar/Wind Helper
0.423
233990AG1-397 GEN
Solar/Wind Helper
0.024
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
214067T20SOLAR
Solar/Wind Helper
0.009
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
20676328BVR_Y1-020
Solar/Wind Helper
0.02
961261AF2-417 GEN
Solar/Wind Helper
0.308
959431AF2-234 GEN
Solar/Wind Helper
0.594
20671928W4-073
Solar/Wind Helper
0.066
946731AF1-337 GEN
Solar/Wind Helper
0.297
3150071POSSM 5
Adder
38.76
3150391LDYSMT3
Adder
10.854
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3143526WINTERP
Solar/Wind Harmer
-0.044
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
944641AF1-129 GEN
Adder
35.924
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316316AC1-027 C
Solar/Wind Harmer
0.255
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3144356SAPONY
Solar/Wind Harmer
0.285
972185AH1-677 GEN
Adder
4.036
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
205916AD1-020 GEN
Solar/Wind Helper
1.496
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
233946AB2-136 GEN
Solar/Wind Helper
0.448
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20716928W4-060COL
Solar/Wind Helper
0.039
20673828FLE_V3-070
Solar/Wind Helper
0.068
20676128MHD_W3-029
Solar/Wind Helper
0.072
217081WEATEXAS C
Solar/Wind Helper
0.009
207471AF2-354 C
Solar/Wind Helper
0.124
20676228FRD_X1-012
Solar/Wind Helper
0.067
20390526W1-045 C
Solar/Wind Helper
0.226
961431AF2-434 GEN
Solar/Wind Helper
0.302
970099AG2-077 GEN
Solar/Wind Harmer
2.697
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3150411LDYSMT5
Adder
10.908
972215AH1-692 GEN
Adder
1.766
316223AC1-118
Solar/Wind Harmer
0.237
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971283AH1-107 GEN
Solar/Wind Harmer
1.396
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
971167AH1-042 GEN
Solar/Wind Harmer
8.225
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
972265AH1-717 GEN
Adder
5.796
3151191GRAVEL3
Adder
5.364
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.798
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
970085AG2-068 GEN
Solar/Wind Harmer
4.94
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151861LOWMORA
Adder
0.648
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
219914AD2-027 C
Solar/Wind Helper
0.088
219607WPEMNERT C
Solar/Wind Helper
0.061
20715728PEM_W1-119
Solar/Wind Helper
0.073
20675528CPH_W2-050
Solar/Wind Helper
0.065
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
207530AG1-191 GEN
Solar/Wind Helper
0.049
20675128HRM_W1-127
Solar/Wind Helper
0.022
959421AF2-233 GEN
Solar/Wind Helper
0.297
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.193
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
3151201GRAVEL4
Adder
5.433
3151211GRAVEL5
Adder
5.364
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146396TANGLEW
Solar/Wind Harmer
0.151
315814AE2-033 C
Solar/Wind Harmer
7.6
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.197
972257AH1-713 GEN
Adder
0.697
960921AF2-383 GEN
Solar/Wind Helper
0.152
205932AD2-116_GEN
Solar/Wind Helper
0.422
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
966261AG1-495 GEN
Solar/Wind Helper
0.06
20674828DL_W4-046
Solar/Wind Helper
0.006
207408W3-077 C
Solar/Wind Helper
0.062
959381AF2-229 GEN
Solar/Wind Helper
0.23
203975AE1-071-GEN
Solar/Wind Helper
1.563
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3152111X4-039 GT1
50/50
2.007
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150331BIRCHWDA
Adder
13.842
970737AG2-469 GEN
Solar/Wind Harmer
4.42
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970293AG2-193 GEN
Solar/Wind Harmer
1.071
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3150921YORKTN3
Adder
1.885
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
970659AG2-427 GEN
Solar/Wind Harmer
0.785
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
37.845
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
971157AH1-035 GEN
Solar/Wind Harmer
0.994
3146776BUCKING
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.214
3151861LOWMORA
Adder
0.674
205917AD1-020 ES
Solar/Wind Helper
0.322
233918AB1-142 GEN
Solar/Wind Helper
0.397
233994AC2-023 GEN
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.206
233971AC1-093 C
Solar/Wind Helper
0.281
228729W2-030 C
Solar/Wind Helper
0.085
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.043
219249CENTRALDIV C
Solar/Wind Helper
0.008
217211CAMDEN ST C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.298
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
209029WAYMART-WD
Solar/Wind Helper
0.566
946751AF1-339 GEN
Solar/Wind Helper
0.297
237001AB1-127_GEN
Solar/Wind Helper
0.221
235063AE1-101 C2
Solar/Wind Helper
0.747
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
315683AE1-153 C
Solar/Wind Harmer
9.363
316192AB2-158 GEN
Solar/Wind Harmer
1.122
972197AH1-683 GEN
Adder
1.698
966881AG1-559 GEN
Solar/Wind Harmer
0.092
972135AH1-637 GEN
Solar/Wind Harmer
0.887
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
316375AC2-012 GEN
Solar/Wind Harmer
2.88
316336AC2-165 C
Solar/Wind Harmer
1.441
3146456SLIGO L269
Solar/Wind Harmer
-0.008
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3145663CRESWEL
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.626
966131AG1-482 GEN
Solar/Wind Helper
0.066
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
232434Z2-077 GEN
Solar/Wind Helper
0.1
219904AC1-010 C
Solar/Wind Helper
0.047
20720728JCB_W1-129
Solar/Wind Helper
0.043
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.106
217208PARK ELE C
Solar/Wind Helper
0.003
237080AD1-060 GEN
Solar/Wind Helper
0.151
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
957411AF2-035 GEN
Solar/Wind Harmer
4.024
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3142946ENON
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3146456SLIGO L269
Solar/Wind Harmer
0.977
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
237025AB1-124 C
Solar/Wind Helper
0.168
23777801MSM_W1-116
Solar/Wind Helper
0.11
230407AD2-065 C
Solar/Wind Helper
0.031
20714928UPF_X1-085
Solar/Wind Helper
0.004
218440SUMMTASSOC C
Solar/Wind Helper
0.012
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.059
209054AE2-059 GEN
Solar/Wind Helper
0.054
972289AH1-729 GEN
50/50
14.564
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
3150681DARBY 2
Adder
5.471
316033AB2-134 GEN
Solar/Wind Harmer
2.716
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
970301AG2-198 GEN
Solar/Wind Harmer
3.936
237006AB1-125 GEN
Solar/Wind Helper
0.126
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
232424Y1-079 C
Solar/Wind Helper
0.092
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
20674928WA_W3-044
Solar/Wind Helper
0.072
966111AG1-480 GEN
Solar/Wind Helper
0.032
208972BECR K09
Solar/Wind Helper
0.227
209137AF2-361 C
Solar/Wind Helper
0.864
237002AB1-128_GEN
Solar/Wind Helper
0.212
3151171GRAVELC
Adder
0.794
316381AD1-082 GEN
Solar/Wind Harmer
0.765
3150981CHESPKA
Adder
0.925
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316388AE2-253 GEN
Solar/Wind Harmer
0.559
316246AF1-032 C
Solar/Wind Harmer
0.167
3130156CHOWAN
Solar/Wind Harmer
-0.008
971163AH1-040 GEN
Solar/Wind Harmer
7.509
970087AG2-069 GEN
Solar/Wind Harmer
7.409
3146926FARMVIL
Solar/Wind Harmer
-0.005
223401AF1-299 GEN
Solar/Wind Helper
0.379
233915AB1-141 GEN
Solar/Wind Helper
0.397
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233950AC2-186 GEN
Solar/Wind Helper
0.091
233972AC1-094 C
Solar/Wind Helper
0.238
228728W1-130C
Solar/Wind Helper
0.041
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
963711AG1-223 GEN
Solar/Wind Helper
0.048
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20675428EAM_W2-061
Solar/Wind Helper
0.012
207518AF1-320_GEN
Solar/Wind Helper
1.156
212266LOR1
Solar/Wind Helper
0.033
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
957481AF2-042 GEN
Solar/Wind Harmer
6.742
3141906WESTMOR
Solar/Wind Harmer
-0.003
316404AE1-155 C
Solar/Wind Harmer
1.667
962971AG1-146 GEN
Solar/Wind Harmer
1.614
316280AD1-041 GEN
Solar/Wind Harmer
0.645
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
316382AG1-145 C
Solar/Wind Harmer
0.255
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151171GRAVELC
Adder
1.044
316405AF2-144 C
Solar/Wind Harmer
0.214
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
315737AD1-076 GEN
Solar/Wind Harmer
1.509
970917AG2-570 GEN
Solar/Wind Harmer
19.793
3146926FARMVIL
Solar/Wind Harmer
-0.005
961681AG1-008 GEN
Solar/Wind Harmer
6.214
3152541MT STMG
Adder
0.593
234015AF2-250 C
Solar/Wind Helper
0.03
219276PARKLANDSO C
Solar/Wind Helper
0.068
20720528MAN_W1-024
Solar/Wind Helper
0.021
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
963161AG1-165 GEN
Solar/Wind Helper
0.309
961331AF2-424 GEN
Solar/Wind Helper
0.302
235067AD1-061 GEN
Solar/Wind Helper
0.214
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
23779801AA1-109
Solar/Wind Helper
0.182
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
207445AB1-138_GEN
Solar/Wind Helper
0.079
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
237038AE2-054 C
Solar/Wind Helper
0.119
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
3141426STAFORD
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.29
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
971285AH1-108 GEN
Adder
0.574
957831AF2-077 GEN
Solar/Wind Harmer
0.255
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
957871AF2-081 GEN
Solar/Wind Harmer
4.142
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
23544701WINZ1-113
Adder
0.24
228754AB1-001 C
Solar/Wind Helper
0.02
219272CLEANLIGHT C
Solar/Wind Helper
0.019
20675928HOL_W4-097
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
209116AE2-175 GEN
Solar/Wind Helper
1.289
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
315747AE2-019 GEN
50/50
14.059
3141196NOKESVL
Solar/Wind Harmer
-0.049
972217AH1-693 GEN
Adder
1.667
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3141316ARNOLDS
Adder
0.192
3150351NORNECKC2
Adder
0.783
315778AD1-151 GEN
Solar/Wind Harmer
7.304
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
316258AE1-075 C
Solar/Wind Harmer
0.203
3143336POWHATN
Solar/Wind Harmer
0.843
3151101ELIZAR3
Adder
6.877
944601AF1-125 GEN
Solar/Wind Harmer
37.254
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3144293JTRSVLE
Adder
0.22
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
233982AB2-133 GEN
Solar/Wind Helper
0.282
233940AF2-379 C
Solar/Wind Helper
0.049
233952AC2-187 GEN
Solar/Wind Helper
0.183
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.014
219612MATRIX C
Solar/Wind Helper
0.018
219908AB1-139 C
Solar/Wind Helper
0.055
20673728F2S_V4-070
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
209027LOR2_Q27
Solar/Wind Helper
0.712
961421AF2-433 GEN
Solar/Wind Helper
0.302
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
238221AF1-254 C O1
Solar/Wind Helper
0.122
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
0.953
3151221GRAVEL6
Adder
5.427
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
237030AB1-096 C
Solar/Wind Helper
0.073
227287AC2-120 GEN
Solar/Wind Helper
0.266
233996TM1833_GEN
Solar/Wind Helper
0.206
232406W1-004 FULL
Solar/Wind Helper
0.4
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219906AC1-017 C
Solar/Wind Helper
0.032
20720828JCB_W4-025
Solar/Wind Helper
0.048
20714528FRN_Y2-051
Solar/Wind Helper
0.043
218438BLK ROCK C
Solar/Wind Helper
0.02
219919AE1-041 FULL
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.066
963071AG1-156 GEN
Solar/Wind Helper
1.001
209067AE2-060 GEN
Solar/Wind Helper
0.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
WECLTFEXP_WEC->PJM
CLTF
1.126
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
NYPJM->LTFIMP_NY
CLTF
3.269
TVALTFEXP_TVA->PJM
CLTF
3.503
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
CPLELTFEXP_CPLE->PJM
CLTF
5.01
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
LGEELTFEXP_LGEE->PJM
CLTF
2.098
MECLTFEXP_MEC->PJM
CLTF
5.133
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1509.53
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3150281M RUN A
Adder
11.203
3140676OCCOQUN
Adder
0.198
316254AC1-120 GEN1
Solar/Wind Harmer
0.16
3147666LOUISA
Solar/Wind Harmer
0.275
3151751LOISA D
Adder
4.435
3143226MDLTHAN
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.037
3141843SHACKLE
Adder
0.315
3143096IRON208
Adder
0.258
3142543TWELFTH
Solar/Wind Harmer
0.006
316159AE1-175 C
Solar/Wind Harmer
0.053
970129AG2-093 GEN
Solar/Wind Harmer
1.729
316458AB2-190 GEN2
Solar/Wind Harmer
0.326
971069AG2-661 GEN
Solar/Wind Harmer
1.079
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971647AH1-324 GEN
Solar/Wind Harmer
2.582
961611AG1-000B GEN
Solar/Wind Harmer
3.169
3151171GRAVELC
Adder
0.642
316381AD1-082 GEN
Solar/Wind Harmer
0.062
3150981CHESPKA
Adder
0.747
970661AG2-428 GEN
Solar/Wind Harmer
5.952
316388AE2-253 GEN
Solar/Wind Harmer
0.187
316246AF1-032 C
Solar/Wind Harmer
0.027
3151721LOISA A
Adder
4.412
970317AG2-208 GEN
Solar/Wind Harmer
2.556
966871AG1-558 GEN
Solar/Wind Harmer
0.072
3142296MT RD221
Adder
0.198
971223AH1-071 GEN
Solar/Wind Harmer
0.661
3150671DARBY 1
Adder
4.423
316240AF1-291 C
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.627
3150991CHESPKB
Adder
0.612
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
971761AH1-387 GEN
Solar/Wind Harmer
1.133
972187AH1-678 GEN
Adder
1.643
316065AD1-022 GEN
Solar/Wind Harmer
2.61
3146776BUCKING
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.379
3145893MURPHYS
Solar/Wind Harmer
0.102
237034AC2-136 C
Solar/Wind Helper
0.179
226929AD2-058 GEN
Solar/Wind Helper
0.07
237001AB1-127_GEN
Solar/Wind Helper
0.259
235063AE1-101 C2
Solar/Wind Helper
0.889
233987AB2-037 GEN
Solar/Wind Helper
1.314
234036AF2-325 C
Solar/Wind Helper
0.024
233901CHERRYDALE C
Solar/Wind Helper
0.13
20720628TIN_W1-124
Solar/Wind Helper
0.102
207442AE1-156 GEN
Solar/Wind Helper
0.174
20671828STAW2-080
Solar/Wind Helper
0.014
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.078
211065PSPA IPP
Solar/Wind Helper
0.078
3150071POSSM 5
Adder
31.816
3150391LDYSMT3
Adder
8.836
316468AD1-105 GEN
Solar/Wind Harmer
-0.021
316077AC2-138 C
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.322
316075AC2-137 C
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
29.055
315697AD1-025 GEN
Solar/Wind Harmer
0.068
316316AC1-027 C
Solar/Wind Harmer
0.057
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
0.491
972185AH1-677 GEN
Adder
3.254
205916AD1-020 GEN
Solar/Wind Helper
1.359
20390526W1-045 C
Solar/Wind Helper
0.222
233933AB2-153 GEN
Solar/Wind Helper
0.131
233944AB2-135 GEN
Solar/Wind Helper
0.332
233946AB2-136 GEN
Solar/Wind Helper
0.319
232408W1-005 C
Solar/Wind Helper
0.284
232410W1-006 C
Solar/Wind Helper
0.284
233939AC1-091 C
Solar/Wind Helper
0.196
963401AG1-189 GEN
Solar/Wind Helper
0.03
963391AG1-188 GEN
Solar/Wind Helper
0.044
235020AA1-095 C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.028
20673828FLE_V3-070
Solar/Wind Helper
0.048
20676128MHD_W3-029
Solar/Wind Helper
0.051
217081WEATEXAS C
Solar/Wind Helper
0.007
207471AF2-354 C
Solar/Wind Helper
0.089
20676228FRD_X1-012
Solar/Wind Helper
0.048
3152131X4-039 ST
50/50
2.874
970467AG2-304 GEN
50/50
12.983
3150221REMNGT2
50/50
11.111
972201AH1-685 GEN
50/50
1.917
3150211REMNGT1
Adder
10.402
315683AE1-153 C
Solar/Wind Harmer
5.861
316192AB2-158 GEN
Solar/Wind Harmer
0.388
972197AH1-683 GEN
Adder
1.382
966881AG1-559 GEN
Solar/Wind Harmer
0.075
972135AH1-637 GEN
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
0.161
3142416OLDCHRC
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.012
971777AH1-397 GEN
Solar/Wind Harmer
0.163
3142433PROV 92
Solar/Wind Harmer
0.246
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3145336SMITFLD
Solar/Wind Harmer
0.24
316294AC1-161 GEN
Solar/Wind Harmer
1.042
316375AC2-012 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.059
970937AG2-583 GEN
Solar/Wind Harmer
3.567
3145663CRESWEL
Solar/Wind Harmer
0.161
316023GEN1_S
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3146173TUNIS
Solar/Wind Harmer
0.056
966131AG1-482 GEN
Solar/Wind Helper
0.102
237080AD1-060 GEN
Solar/Wind Helper
0.184
232422X3-066 FULL
Solar/Wind Helper
0.064
233964AF2-378 GEN
Solar/Wind Helper
0.023
232426Y1-080 FULL
Solar/Wind Helper
0.022
232434Z2-077 GEN
Solar/Wind Helper
0.071
205941AD2-115 GEN
Solar/Wind Helper
0.276
219904AC1-010 C
Solar/Wind Helper
0.033
20720728JCB_W1-129
Solar/Wind Helper
0.031
20714828MDF_W3-079
Solar/Wind Helper
0.07
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20742028HF_AC1-207
Solar/Wind Helper
0.075
217208PARK ELE C
Solar/Wind Helper
0.002
970053AG2-049 GEN
50/50
1.525
3150381LDYSMT2
Adder
8.499
3141783LANCAST
Solar/Wind Harmer
0.037
3141783LANCAST
Solar/Wind Harmer
0.025
316059AD1-063 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
315976AC1-164 GENA
Solar/Wind Harmer
6.381
316169AC1-164_GENC
Solar/Wind Harmer
5.512
315975AC1-164 GENB
Solar/Wind Harmer
0.189
3151201GRAVEL4
Adder
4.391
3151211GRAVEL5
Adder
4.336
316349AD2-085 GEN
Solar/Wind Harmer
0.041
316311AC2-079 GEN
Solar/Wind Harmer
1.71
315835AF2-110_GEN
Solar/Wind Harmer
0.407
313526AB2-022
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
4.636
971845AH1-439 GEN
Solar/Wind Harmer
2.569
970285AG2-188 GEN
Solar/Wind Harmer
4.479
3146206CASHIE
Solar/Wind Harmer
0.057
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
960921AF2-383 GEN
Solar/Wind Helper
0.255
205932AD2-116_GEN
Solar/Wind Helper
0.352
959381AF2-229 GEN
Solar/Wind Helper
0.226
203975AE1-071-GEN
Solar/Wind Helper
1.507
232432Z2-076 GEN
Solar/Wind Helper
0.038
316006AB2-029 C
Solar/Wind Harmer
0
316045AC1-158 PL2
Solar/Wind Harmer
1.156
3150151POSSMC1
Adder
0.696
316337AD2-073 GEN
Solar/Wind Harmer
0.055
3141726DUNNSVL
Solar/Wind Harmer
0.25
962861AG1-135 GEN
Solar/Wind Harmer
1.994
3150851SPRUNCC
Adder
0.284
970659AG2-427 GEN
Solar/Wind Harmer
2.901
316093AE2-104_GEN
Solar/Wind Harmer
0.998
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.059
315800Z1-036_GEN1
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.023
3145893MURPHYS
Solar/Wind Harmer
0.226
3145893MURPHYS
Solar/Wind Harmer
0.251
23779801AA1-109
Solar/Wind Helper
0.196
237038AE2-054 C
Solar/Wind Helper
0.144
219686LUMSOLAR_N C
Solar/Wind Helper
0.022
219304NAMERICA C
Solar/Wind Helper
0.072
207445AB1-138_GEN
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.036
217209CENTRL HS C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.012
207439AE1-081 C O1
Solar/Wind Helper
0.01
961301AF2-421 GEN
Solar/Wind Helper
0.221
963151AG1-164 GEN
Solar/Wind Helper
0.221
3152121X4-039 GT2
50/50
1.821
971685AH1-345 GEN
Solar/Wind Harmer
0.609
972223AH1-696 GEN
Adder
5.499
3141346CRANES
Adder
0.08
972219AH1-694 GEN
Adder
0.995
3150351NORNECKC2
Adder
0.624
3143526WINTERP
Solar/Wind Harmer
0.322
944631AF1-128 GEN
Adder
29.257
971317AH1-138 GEN
Solar/Wind Harmer
0.454
315671AE2-027_GEN
Solar/Wind Harmer
3.891
3143336POWHATN
Solar/Wind Harmer
1.067
944591AF1-124 GEN
Solar/Wind Harmer
13.516
316072AD1-144
Solar/Wind Harmer
0.022
939411AE1-173 GEN
Solar/Wind Harmer
25.458
940641AE2-051 GEN
Solar/Wind Harmer
4.772
972003AH1-546 GEN
Solar/Wind Harmer
2.42
316322AB2-045
Solar/Wind Harmer
0
971547AH1-271 GEN
Solar/Wind Harmer
1.207
233930AB2-032 GEN
Solar/Wind Helper
0.215
233954AC2-188 GEN
Solar/Wind Helper
0.13
230511AF1-262
Solar/Wind Helper
0.008
230434AG1-499 GEN
Solar/Wind Helper
0.126
219258KINSLEYDEP C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.003
207528AF2-192 GEN
Solar/Wind Helper
0.04
20673628F1S_V4-069
Solar/Wind Helper
0.016
217213AMBOY SO C
Solar/Wind Helper
0.015
207437AD2-070 GEN
Solar/Wind Helper
0.073
20671928W4-073
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.015
972289AH1-729 GEN
50/50
12.961
3150181POSSMC2
Adder
0.702
3150181POSSMC2
Adder
0.696
3150181POSSMC2
Adder
0.696
966001AG1-469 GEN
Solar/Wind Harmer
0.04
3151731LOISA B
Adder
4.435
972195AH1-682 GEN
Adder
1.161
315673AE1-157 GEN
Solar/Wind Harmer
4.506
3150341NORNECKC1
Adder
0.656
3150341NORNECKC1
Adder
0.651
3150681DARBY 2
Adder
4.428
316033AB2-134 GEN
Solar/Wind Harmer
0.004
316236AE1-162_GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
2.098
970657AG2-426 GEN
Solar/Wind Harmer
0.44
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.036
316339AD2-160 GEN
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.237
3130086AYDLETT
Solar/Wind Harmer
0.238
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
970301AG2-198 GEN
Solar/Wind Harmer
2.401
237006AB1-125 GEN
Solar/Wind Helper
0.132
208835TUHI V3-051
Solar/Wind Helper
0.018
208835TUHI V3-051
Solar/Wind Helper
0.018
237002AB1-128_GEN
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.085
232424Y1-079 C
Solar/Wind Helper
0.065
233970AC1-092 C
Solar/Wind Helper
0.196
230433AD2-135 GEN
Solar/Wind Helper
0.009
3147346CASHSCORNER
Solar/Wind Harmer
0.156
972213AH1-691 GEN
Adder
1.438
944491AF1-114 GEN
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.058
971281AH1-106 GEN
Solar/Wind Harmer
0.859
3138133OCRAN
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.037
3141873WAN 176
Solar/Wind Harmer
0.012
316369SG1_INVT
Solar/Wind Harmer
0.002
3143316POE
Solar/Wind Harmer
0.238
319010AE1-072 C
Solar/Wind Harmer
0.299
3146486SUNBURY
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.059
316321Z2-027
Solar/Wind Harmer
0.011
3145176PASQUOTANK
Solar/Wind Harmer
0.037
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
315816AE2-034 GEN
Solar/Wind Harmer
0.246
972205AH1-687 GEN
Adder
2.436
3130546PLYMOUTH
Solar/Wind Harmer
0.057
315733AD1-074 GEN2
Solar/Wind Harmer
0.327
970581AG2-369 GEN
Solar/Wind Harmer
2.597
970601AG2-382 GEN
Solar/Wind Harmer
2.113
205943AE1-185 GEN
Solar/Wind Helper
0.354
233990AG1-397 GEN
Solar/Wind Helper
0.151
964001AG1-254 GEN
Solar/Wind Helper
0.525
227927V4-067C
Solar/Wind Helper
0.006
219688LUMSOLAR_S C
Solar/Wind Helper
0.022
214067T20SOLAR
Solar/Wind Helper
0.006
20715828PEM_W1-120
Solar/Wind Helper
0.052
207459AE1-142 C O1
Solar/Wind Helper
0.157
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.086
20676328BVR_Y1-020
Solar/Wind Helper
0.014
961261AF2-417 GEN
Solar/Wind Helper
0.221
3138216PACIFIC
Solar/Wind Harmer
0.024
316164AC1-076 GEN
Solar/Wind Harmer
0.104
3150411LDYSMT5
Adder
8.881
972215AH1-692 GEN
Adder
1.438
316223AC1-118
Solar/Wind Harmer
0.046
3141813NORNECK
Solar/Wind Harmer
0.063
962981AG1-147 GEN
Solar/Wind Harmer
2.318
316233AE1-074 FULL
Solar/Wind Harmer
0.05
971283AH1-107 GEN
Solar/Wind Harmer
0.859
315666AE1-190 GEN
Solar/Wind Harmer
0
970189AG2-124 GEN
Solar/Wind Harmer
1.827
971167AH1-042 GEN
Solar/Wind Harmer
5.466
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.326
972265AH1-717 GEN
Adder
4.684
3151191GRAVEL3
Adder
4.336
316305AF2-043 C
Solar/Wind Harmer
0
3146406KITTY HAWK
Solar/Wind Harmer
0.007
944011AF1-069 GEN
Solar/Wind Harmer
3.529
971967AH1-528 GEN
Solar/Wind Harmer
9.279
315732AD1-074 GEN1
Solar/Wind Harmer
0.327
315735AD1-075 GEN1
Solar/Wind Harmer
0.164
965291AG1-394 GEN
Solar/Wind Harmer
0.253
970085AG2-068 GEN
Solar/Wind Harmer
3.019
3145893MURPHYS
Solar/Wind Harmer
0.153
3145893MURPHYS
Solar/Wind Harmer
0.057
205956AE1-196_GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
0.72
232436AB1-176 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.537
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.015
970327AG2-215 GEN
Solar/Wind Harmer
2.041
316312AB1-027
Solar/Wind Harmer
0.111
3141913WHIT STONE
Solar/Wind Harmer
0.062
316314AB2-024 C
Solar/Wind Harmer
0
971285AH1-108 GEN
Adder
0.465
971445AH1-216 GEN
Solar/Wind Harmer
4.236
3151081ELIZAR1
Adder
5.485
3151091ELIZAR2
Adder
5.39
3152611GOSPORTB
Adder
0.762
3152621GOSPORTC
Adder
0.647
3152601GOSPORTA
Adder
0.597
315833AF1-017_GEN
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.964
316315AB2-025 C
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
10.802
970673AG2-436 GEN
Solar/Wind Harmer
12.417
970673AG2-436 GEN
Solar/Wind Harmer
8.278
237085AD2-009_GEN
Solar/Wind Helper
0.799
228754AB1-001 C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.014
20675928HOL_W4-097
Solar/Wind Helper
0.026
207484AF2-139 C O1
Solar/Wind Helper
0.044
20675728RH_W2-091
Solar/Wind Helper
0.072
209116AE2-175 GEN
Solar/Wind Helper
0.921
234033AF1-007_GEN
Solar/Wind Helper
3.932
966261AG1-495 GEN
Solar/Wind Helper
0.043
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.044
3150231REMNGT3
50/50
11.996
3150241REMNGT4
50/50
11.185
963691AG1-221 GEN
Solar/Wind Harmer
2.201
972199AH1-684 GEN
Adder
1.598
3150371LDYSMT1
Adder
8.554
971781AH1-399 GEN
Solar/Wind Harmer
0.084
316473AC1-191 GEN
Solar/Wind Harmer
0.211
970009AG2-005 GEN
Solar/Wind Harmer
0.464
3142416OLDCHRC
Solar/Wind Harmer
0.6
3141766HARMONY
Solar/Wind Harmer
0.822
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142946ENON
Solar/Wind Harmer
0.021
970133AG2-095 GEN
Solar/Wind Harmer
0.585
3151221GRAVEL6
Adder
4.386
315651AD1-115 GEN
Solar/Wind Harmer
0.002
316447AC1-158 HLD
Solar/Wind Harmer
0.794
957411AF2-035 GEN
Solar/Wind Harmer
2.759
958261AF2-120 GEN
Solar/Wind Harmer
2.062
3142366NRTHEST
Adder
0.202
3150691DARBY 3
Adder
4.444
3150701DARBY 4
Adder
4.434
3142946ENON
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
3146456SLIGO L269
Solar/Wind Harmer
1.052
3146386ELIZ CT
Solar/Wind Harmer
0.059
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
4.601
3146173TUNIS
Solar/Wind Harmer
0.056
3146173TUNIS
Solar/Wind Harmer
0.056
237025AB1-124 C
Solar/Wind Helper
0.177
23777801MSM_W1-116
Solar/Wind Helper
0.118
230407AD2-065 C
Solar/Wind Helper
0.022
20714928UPF_X1-085
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
217204WCALDSOLAR C
Solar/Wind Helper
0.002
964851AG1-348 GEN
Solar/Wind Helper
0.043
3150301M RUN C
Adder
11.196
316044AC1-158 PL1
Solar/Wind Harmer
0.361
316450AC1-158 RIC
Solar/Wind Harmer
0.096
3147666LOUISA
Solar/Wind Harmer
0.158
3150401LDYSMT4
Adder
8.853
3141906WESTMOR
Solar/Wind Harmer
0.025
316404AE1-155 C
Solar/Wind Harmer
0.014
962971AG1-146 GEN
Solar/Wind Harmer
0.993
316280AD1-041 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
1.096
3141843SHACKLE
Adder
0.315
3150861SPRUNCD
Adder
0.284
3143096IRON208
Adder
0.258
3143096IRON208
Adder
0.253
316382AG1-145 C
Solar/Wind Harmer
0
970129AG2-093 GEN
Solar/Wind Harmer
3.674
965281AG1-393 GEN
Solar/Wind Harmer
0.648
961611AG1-000B GEN
Solar/Wind Harmer
1.611
3151171GRAVELC
Adder
0.844
316405AF2-144 C
Solar/Wind Harmer
0
3144873MCLAUGH
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.266
3146626S HERTFORD
Solar/Wind Harmer
0.059
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.732
970917AG2-570 GEN
Solar/Wind Harmer
5.042
961681AG1-008 GEN
Solar/Wind Harmer
4.204
3146926FARMVIL
Solar/Wind Harmer
0.034
235067AD1-061 GEN
Solar/Wind Helper
0.259
234015AF2-250 C
Solar/Wind Helper
0.021
219276PARKLANDSO C
Solar/Wind Helper
0.048
20720528MAN_W1-024
Solar/Wind Helper
0.015
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.016
963161AG1-165 GEN
Solar/Wind Helper
0.221
3130156CHOWAN
Solar/Wind Harmer
0.058
971163AH1-040 GEN
Solar/Wind Harmer
4.594
970087AG2-069 GEN
Solar/Wind Harmer
4.529
3146926FARMVIL
Solar/Wind Harmer
0.034
223401AF1-299 GEN
Solar/Wind Helper
0.351
235062AE1-101 C1
Solar/Wind Helper
0.889
233915AB1-141 GEN
Solar/Wind Helper
0.283
232428Y3-058 C
Solar/Wind Helper
0.19
233998TM1NIN_3.36
Solar/Wind Helper
0.146
232404W1-003 C
Solar/Wind Helper
0.284
233950AC2-186 GEN
Solar/Wind Helper
0.065
233972AC1-094 C
Solar/Wind Helper
0.169
228728W1-130C
Solar/Wind Helper
0.03
218660EHAMPSOLAR C
Solar/Wind Helper
0.018
963711AG1-223 GEN
Solar/Wind Helper
0.035
207454AA2-184 E
Solar/Wind Helper
0.166
20715228NPK_W1-113
Solar/Wind Helper
0.042
20675428EAM_W2-061
Solar/Wind Helper
0.008
207518AF1-320_GEN
Solar/Wind Helper
0.827
3152111X4-039 GT1
50/50
1.827
971455AH1-223 GEN
Solar/Wind Harmer
2.201
3150291M RUN B
Adder
11.113
316170AC1-121 GEN2
Solar/Wind Harmer
0.08
3132273ORANGE
Solar/Wind Harmer
0.014
3150151POSSMC1
Adder
0.696
3150151POSSMC1
Adder
0.696
3150331BIRCHWDA
Adder
11.297
970737AG2-469 GEN
Solar/Wind Harmer
2.728
970293AG2-193 GEN
Solar/Wind Harmer
0.658
316203AE2-005 GEN
Solar/Wind Harmer
0
316156AD2-030 GEN
Solar/Wind Harmer
0.046
3150921YORKTN3
Adder
1.524
315773AC2-141 GEN
Solar/Wind Harmer
2.196
316313AB2-026
Solar/Wind Harmer
0.038
970659AG2-427 GEN
Solar/Wind Harmer
0.635
3144536CHRHLND
Solar/Wind Harmer
0.009
944581AF1-123 GEN
Solar/Wind Harmer
13.468
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
315614AA2-178 GEN
Solar/Wind Harmer
0.329
971157AH1-035 GEN
Solar/Wind Harmer
0.683
3146776BUCKING
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
957521AF2-046 GEN
Solar/Wind Harmer
4.204
205917AD1-020 ES
Solar/Wind Helper
0.292
233918AB1-142 GEN
Solar/Wind Helper
0.283
233994AC2-023 GEN
Solar/Wind Helper
0.539
233997TMININ_4.2
Solar/Wind Helper
0.146
233971AC1-093 C
Solar/Wind Helper
0.2
228729W2-030 C
Solar/Wind Helper
0.061
219348LDSOLAR C
Solar/Wind Helper
0.062
959561AF2-247 GEN
Solar/Wind Helper
0.011
20715028HAN_X4-015
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
219914AD2-027 C
Solar/Wind Helper
0.063
219607WPEMNERT C
Solar/Wind Helper
0.044
20715728PEM_W1-119
Solar/Wind Helper
0.052
20675528CPH_W2-050
Solar/Wind Helper
0.046
218524CNTRALGAS1 C
Solar/Wind Helper
0.086
207530AG1-191 GEN
Solar/Wind Helper
0.035
20675128HRM_W1-127
Solar/Wind Helper
0.016
315813AE1-149 C
Solar/Wind Harmer
3.21
3145336SMITFLD
Solar/Wind Harmer
0.024
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.059
971153AH1-033 GEN
Solar/Wind Harmer
0.687
3145273HOLLAND
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.058
316365GEN2_N
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3146173TUNIS
Solar/Wind Harmer
0.056
237030AB1-096 C
Solar/Wind Helper
0.076
227287AC2-120 GEN
Solar/Wind Helper
0.279
233996TM1833_GEN
Solar/Wind Helper
0.146
232406W1-004 FULL
Solar/Wind Helper
0.284
230430AE1-229_GEN
Solar/Wind Helper
1.854
230415AB2-049 C
Solar/Wind Helper
0.017
219766PARADISE C
Solar/Wind Helper
0.03
219912AD2-042 GEN
Solar/Wind Helper
0.082
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.023
20720828JCB_W4-025
Solar/Wind Helper
0.034
20714528FRN_Y2-051
Solar/Wind Helper
0.031
218438BLK ROCK C
Solar/Wind Helper
0.015
219919AE1-041 FULL
Solar/Wind Helper
0.002
20674628WNG_W3-110
Solar/Wind Helper
0.047
219921AF1-264
Solar/Wind Helper
0.028
219615MILLCREEK C
Solar/Wind Helper
0.014
20674928WA_W3-044
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.039
315747AE2-019 GEN
50/50
12.182
972285AH1-727 GEN
50/50
35.211
972217AH1-693 GEN
50/50
1.475
3141196NOKESVL
Solar/Wind Harmer
0.372
3151761LOISA E
Adder
9.041
972183AH1-676 GEN
Adder
72.988
3141316ARNOLDS
Adder
0.157
3150351NORNECKC2
Adder
0.635
315778AD1-151 GEN
Solar/Wind Harmer
4.854
315839AE2-212 C
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.228
316258AE1-075 C
Solar/Wind Harmer
0.045
3143336POWHATN
Solar/Wind Harmer
0.907
3151101ELIZAR3
Adder
5.556
944601AF1-125 GEN
Solar/Wind Harmer
13.26
970909AG2-566 GEN
Solar/Wind Harmer
0.6
223402AF1-300 C
Solar/Wind Helper
0.351
226910AB2-157 C
Solar/Wind Helper
0.013
238221AF1-254 C O1
Solar/Wind Helper
0.149
233982AB2-133 GEN
Solar/Wind Helper
0.202
233940AF2-379 C
Solar/Wind Helper
0.035
233952AC2-187 GEN
Solar/Wind Helper
0.13
219623KINSLEYBEA C
Solar/Wind Helper
0.001
20716028EGP_W2-019
Solar/Wind Helper
0.01
219612MATRIX C
Solar/Wind Helper
0.013
219908AB1-139 C
Solar/Wind Helper
0.039
20673728F2S_V4-070
Solar/Wind Helper
0.016
207510AF2-138 C
Solar/Wind Helper
0.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.688
NYPJM->LTFIMP_NY
CLTF
2.351
TVALTFEXP_TVA->PJM
CLTF
2.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.895
WECLTFEXP_WEC->PJM
CLTF
0.855
LAGNLTFEXP_LAGN->PJM
CLTF
5.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.607
LGEELTFEXP_LGEE->PJM
CLTF
1.596
MECLTFEXP_MEC->PJM
CLTF
3.911
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.069
CPLELTFEXP_CPLE->PJM
CLTF
3.974
SIGELTFEXP_SIGE->PJM
CLTF
0.123

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:17.61
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Harmer
3.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
957411AF2-035 GEN
Solar/Wind Harmer
9.794
3142366NRTHEST
Adder
0.693
958261AF2-120 GEN
Solar/Wind Harmer
7.015
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3142946ENON
Solar/Wind Harmer
0.021
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
3.521
3146386ELIZ CT
Solar/Wind Harmer
0.197
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
970933AG2-581 GEN
Solar/Wind Harmer
14.962
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
316181AB2-040 GEN
Solar/Wind Harmer
0.257
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
958211AF2-115 GEN
Solar/Wind Harmer
2.054
316274AC1-208 GEN
Solar/Wind Harmer
0.88
3150391LDYSMT3
Adder
31.782
3150071POSSM 5
Adder
101.873
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
316077AC2-138 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
1.104
316075AC2-137 C
Solar/Wind Harmer
0.058
944641AF1-129 GEN
Adder
98.867
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316316AC1-027 C
Solar/Wind Harmer
0.193
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3144356SAPONY
Solar/Wind Harmer
1.625
972185AH1-677 GEN
Adder
10.672
970099AG2-077 GEN
Solar/Wind Harmer
19.085
3145783HORNRTN
Solar/Wind Harmer
3.102
972213AH1-691 GEN
Adder
5.171
3147346CASHSCORNER
Solar/Wind Harmer
0.532
972189AH1-679 GEN
Adder
3.695
3151721LOISA A
Adder
15.238
970317AG2-208 GEN
Solar/Wind Harmer
9.074
3141426STAFORD
Solar/Wind Harmer
0.05
316312AB1-027
Solar/Wind Harmer
0.381
970327AG2-215 GEN
Solar/Wind Harmer
6.945
971285AH1-108 GEN
Adder
1.591
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
971445AH1-216 GEN
Solar/Wind Harmer
14.282
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3152611GOSPORTB
Adder
2.56
971259AH1-089 GEN
50/50
5.432
3150281M RUN A
50/50
43.576
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
3147666LOUISA
Solar/Wind Harmer
0.979
3151751LOISA D
Adder
15.317
3140676OCCOQUN
Adder
0.566
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.883
3142543TWELFTH
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.126
3141843SHACKLE
Adder
1.073
316159AE1-175 C
Solar/Wind Harmer
0.179
970129AG2-093 GEN
Solar/Wind Harmer
5.871
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
971069AG2-661 GEN
Solar/Wind Harmer
3.658
3138126ROCKLANDING
Solar/Wind Harmer
0.094
971647AH1-324 GEN
Solar/Wind Harmer
8.741
961611AG1-000B GEN
Solar/Wind Harmer
10.718
3151171GRAVELC
Adder
2.168
316381AD1-082 GEN
Solar/Wind Harmer
0.21
3150981CHESPKA
Adder
2.51
970661AG2-428 GEN
Solar/Wind Harmer
19.99
316388AE2-253 GEN
Solar/Wind Harmer
0.625
316246AF1-032 C
Solar/Wind Harmer
0.09
3130156CHOWAN
Solar/Wind Harmer
0.19
971163AH1-040 GEN
Solar/Wind Harmer
14.962
970087AG2-069 GEN
Solar/Wind Harmer
14.579
957481AF2-042 GEN
Solar/Wind Harmer
47.712
316190AA2-174 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.105
971563AH1-280 GEN
Solar/Wind Harmer
1.826
970685AG2-442 GEN
Solar/Wind Harmer
12.717
3146293MARTNCO
Solar/Wind Harmer
0.158
971377AH1-170 GEN
Solar/Wind Harmer
1.79
3146233WITAKRS
Solar/Wind Harmer
0.648
3145493TOT1
Solar/Wind Harmer
0.723
316049AB1-081 GEN
Solar/Wind Harmer
0.917
235062AE1-101 C1
Solar/Wind Helper
1.773
233998TM1NIN_3.36
Solar/Wind Helper
0.269
233972AC1-094 C
Solar/Wind Helper
0.312
232404W1-003 C
Solar/Wind Helper
0.523
232428Y3-058 C
Solar/Wind Helper
0.348
233950AC2-186 GEN
Solar/Wind Helper
0.12
233915AB1-141 GEN
Solar/Wind Helper
0.516
228728W1-130C
Solar/Wind Helper
0.055
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
207454AA2-184 E
Solar/Wind Helper
0.315
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.579
966001AG1-469 GEN
Solar/Wind Harmer
0.139
972195AH1-682 GEN
Adder
4.177
3151731LOISA B
Adder
15.317
315673AE1-157 GEN
Solar/Wind Harmer
16.074
3150181POSSMC2
Adder
2.248
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
3150341NORNECKC1
Adder
2.231
3150341NORNECKC1
Adder
2.213
3150681DARBY 2
Adder
15.207
316033AB2-134 GEN
Solar/Wind Harmer
0.012
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
316339AD2-160 GEN
Solar/Wind Harmer
0.323
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3130086AYDLETT
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
970301AG2-198 GEN
Solar/Wind Harmer
7.522
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.218
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
970323AG2-213 GEN
Solar/Wind Harmer
7.229
971775AH1-396 GEN
Solar/Wind Harmer
0.271
313527AB2-043 GEN
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.377
3132123MT JACKSON
Solar/Wind Harmer
0.381
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
23777901MDS_W4-102
Solar/Wind Helper
0.197
237006AB1-125 GEN
Solar/Wind Helper
0.14
237002AB1-128_GEN
Solar/Wind Helper
0.48
233970AC1-092 C
Solar/Wind Helper
0.361
232424Y1-079 C
Solar/Wind Helper
0.12
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
966111AG1-480 GEN
Solar/Wind Helper
0.074
316006AB2-029 C
Solar/Wind Harmer
0.002
316045AC1-158 PL2
Solar/Wind Harmer
4.376
3150151POSSMC1
Adder
2.229
316337AD2-073 GEN
Solar/Wind Harmer
0.187
3141726DUNNSVL
Solar/Wind Harmer
0.851
962861AG1-135 GEN
Solar/Wind Harmer
6.784
3150851SPRUNCC
Adder
0.972
970659AG2-427 GEN
Solar/Wind Harmer
9.759
316093AE2-104_GEN
Solar/Wind Harmer
3.331
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
970919AG2-571 GEN
Solar/Wind Harmer
6.502
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.809
3146263WOODLND
Solar/Wind Harmer
0.178
315693AD1-088 GEN
Solar/Wind Harmer
8.533
962491AG1-098 GEN
Solar/Wind Harmer
10.141
3145963POPLR C
Solar/Wind Harmer
0.176
316011AB1-132 GEN
Solar/Wind Harmer
3.202
316174AB2-169 GEN
Solar/Wind Harmer
0.005
966871AG1-558 GEN
Solar/Wind Harmer
0.248
3142296MT RD221
Adder
0.683
971223AH1-071 GEN
Solar/Wind Harmer
2.268
3150671DARBY 1
Adder
15.189
316240AF1-291 C
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
2.106
3150991CHESPKB
Adder
2.056
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
972187AH1-678 GEN
Adder
5.366
316065AD1-022 GEN
Solar/Wind Harmer
8.417
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
971741AH1-377 GEN
Solar/Wind Harmer
17.523
316426AA2-053 GEN
Solar/Wind Harmer
0.594
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
971489AH1-241 GEN
Solar/Wind Harmer
8.948
939181AE1-148 GEN
Solar/Wind Harmer
8.005
3145453TOT5
Solar/Wind Harmer
0.226
961601AG1-000A GEN
Solar/Wind Harmer
2.849
964791AG1-342 GEN
Solar/Wind Harmer
3.061
971761AH1-387 GEN
Solar/Wind Harmer
2.843
942751AE2-291 GEN
Solar/Wind Harmer
6.934
237034AC2-136 C
Solar/Wind Helper
0.259
237001AB1-127_GEN
Solar/Wind Helper
0.481
235063AE1-101 C2
Solar/Wind Helper
1.773
233987AB2-037 GEN
Solar/Wind Helper
2.414
233901CHERRYDALE C
Solar/Wind Helper
0.239
234036AF2-325 C
Solar/Wind Helper
0.043
20720628TIN_W1-124
Solar/Wind Helper
0.192
207442AE1-156 GEN
Solar/Wind Helper
0.329
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
972217AH1-693 GEN
50/50
5.373
3141196NOKESVL
Solar/Wind Harmer
1.195
3151761LOISA E
Adder
31.228
972183AH1-676 GEN
Adder
251.695
3141316ARNOLDS
Adder
0.53
3150351NORNECKC2
Adder
2.16
315778AD1-151 GEN
Solar/Wind Harmer
16.459
315839AE2-212 C
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.774
3151101ELIZAR3
Adder
18.67
944601AF1-125 GEN
Solar/Wind Harmer
44.557
316258AE1-075 C
Solar/Wind Harmer
0.149
3143336POWHATN
Solar/Wind Harmer
2.984
970909AG2-566 GEN
Solar/Wind Harmer
1.881
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
963191AG1-168 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.459
316034AC1-036 C
Solar/Wind Harmer
0.012
3145603CNETO
Solar/Wind Harmer
0.151
962561AG1-105 GEN
Solar/Wind Harmer
7.712
316263AC1-034 GEN
Solar/Wind Harmer
6.088
315821AE2-092 GEN
Solar/Wind Harmer
0.01
235020AA1-095 C
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.368
205916AD1-020 GEN
Solar/Wind Helper
1.767
233939AC1-091 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.585
233944AB2-135 GEN
Solar/Wind Helper
0.605
233933AB2-153 GEN
Solar/Wind Helper
0.239
963401AG1-189 GEN
Solar/Wind Helper
0.057
963391AG1-188 GEN
Solar/Wind Helper
0.084
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.092
20676128MHD_W3-029
Solar/Wind Helper
0.097
217081WEATEXAS C
Solar/Wind Helper
0.013
20676228FRD_X1-012
Solar/Wind Helper
0.092
207471AF2-354 C
Solar/Wind Helper
0.169
971685AH1-345 GEN
Solar/Wind Harmer
2.219
972219AH1-694 GEN
Adder
3.58
3141346CRANES
Adder
0.266
972223AH1-696 GEN
Adder
17.606
3150351NORNECKC2
Adder
2.124
3143526WINTERP
Solar/Wind Harmer
1.104
944631AF1-128 GEN
Adder
99.968
971317AH1-138 GEN
Solar/Wind Harmer
1.542
315671AE2-027_GEN
Solar/Wind Harmer
13.209
944591AF1-124 GEN
Solar/Wind Harmer
45.415
316072AD1-144
Solar/Wind Harmer
0.072
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
3143336POWHATN
Solar/Wind Harmer
3.511
971547AH1-271 GEN
Solar/Wind Harmer
3.887
960081AF2-299 GEN
Solar/Wind Harmer
1.72
962571AG1-106 GEN
Solar/Wind Harmer
2.506
3145823KELFORD
Solar/Wind Harmer
0.176
316322AB2-045
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
7.424
3145783HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
3144293JTRSVLE
Adder
0.545
316212AC1-099_GEN
Solar/Wind Harmer
0.882
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.218
3147623JAMES R
Solar/Wind Harmer
0.389
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.005
972277AH1-723 GEN
Adder
97.342
970401AG2-262 GEN
Solar/Wind Harmer
0.935
3147983MERCK5
Solar/Wind Harmer
0.05
233954AC2-188 GEN
Solar/Wind Helper
0.239
233930AB2-032 GEN
Solar/Wind Helper
0.391
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.235
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219907AC1-030 C
Solar/Wind Helper
0.035
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.077
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675828AU_W4-064
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
3150381LDYSMT2
Adder
30.569
970053AG2-049 GEN
Adder
3.548
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
315975AC1-164 GENB
Solar/Wind Harmer
0.646
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3151201GRAVEL4
Adder
14.831
971255AH1-087 GEN
50/50
5.432
3150221REMNGT2
50/50
40.487
972201AH1-685 GEN
50/50
6.985
3150211REMNGT1
Adder
37.902
315683AE1-153 C
Solar/Wind Harmer
20.71
316192AB2-158 GEN
Solar/Wind Harmer
1.381
972197AH1-683 GEN
Adder
4.972
966881AG1-559 GEN
Solar/Wind Harmer
0.265
972135AH1-637 GEN
Solar/Wind Harmer
1.858
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
0.212
3141766HARMONY
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971777AH1-397 GEN
Solar/Wind Harmer
0.554
3145336SMITFLD
Solar/Wind Harmer
0.811
316294AC1-161 GEN
Solar/Wind Harmer
3.512
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3146456SLIGO L269
Solar/Wind Harmer
0.199
316336AC2-165 C
Solar/Wind Harmer
0.008
3145663CRESWEL
Solar/Wind Harmer
0.523
970937AG2-583 GEN
Solar/Wind Harmer
11.244
316023GEN1_S
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3146173TUNIS
Solar/Wind Harmer
0.18
3145683EARLEYS
Solar/Wind Harmer
0.179
971795AH1-408 GEN
Solar/Wind Harmer
11.784
3147043LAWRENC
Adder
1.589
315722AD1-056 GEN
Solar/Wind Harmer
1.053
3146083TARBORO
Solar/Wind Harmer
0.163
316359AB2-059 GEN
Solar/Wind Harmer
0.576
3142053HEARTS
Solar/Wind Harmer
0.282
316003AC1-222 GEN
Solar/Wind Harmer
0.004
315705AF1-075 GEN
Solar/Wind Harmer
4.991
237080AD1-060 GEN
Solar/Wind Helper
0.373
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.138
219904AC1-010 C
Solar/Wind Helper
0.062
20720728JCB_W1-129
Solar/Wind Helper
0.058
20714828MDF_W3-079
Solar/Wind Helper
0.132
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.143
217208PARK ELE C
Solar/Wind Helper
0.004
205941AD2-115 GEN
Solar/Wind Helper
0.494
3151211GRAVEL5
Adder
14.643
316349AD2-085 GEN
Solar/Wind Harmer
0.137
316311AC2-079 GEN
Solar/Wind Harmer
5.725
315835AF2-110_GEN
Solar/Wind Harmer
1.359
313526AB2-022
Solar/Wind Harmer
0.107
3146396TANGLEW
Solar/Wind Harmer
0.542
315814AE2-033 C
Solar/Wind Harmer
15.327
3146206CASHIE
Solar/Wind Harmer
0.182
3146043SEABORD
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
970285AG2-188 GEN
Solar/Wind Harmer
13.847
971845AH1-439 GEN
Solar/Wind Harmer
7.933
961791AG1-021 GEN
Solar/Wind Harmer
1.643
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3147173SINAI
Solar/Wind Harmer
0.154
3147243WELCO
Solar/Wind Harmer
0.096
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970163AG2-111 GEN
Solar/Wind Harmer
1.027
3148463FAIRFLD
Solar/Wind Harmer
0.12
959381AF2-229 GEN
Solar/Wind Helper
0.375
234033AF1-007_GEN
Solar/Wind Helper
7.236
232432Z2-076 GEN
Solar/Wind Helper
0.069
203975AE1-071-GEN
Solar/Wind Helper
2.597
205932AD2-116_GEN
Solar/Wind Helper
0.502
960921AF2-383 GEN
Solar/Wind Helper
0.358
966261AG1-495 GEN
Solar/Wind Helper
0.082
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
3146776BUCKING
Solar/Wind Harmer
0.07
963171AG1-166 GEN
Solar/Wind Harmer
0.913
316494AC1-189 GEN
Solar/Wind Harmer
0.556
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.128
23779801AA1-109
Solar/Wind Helper
0.222
237038AE2-054 C
Solar/Wind Helper
0.293
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219304NAMERICA C
Solar/Wind Helper
0.134
207445AB1-138_GEN
Solar/Wind Helper
0.106
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
316164AC1-076 GEN
Solar/Wind Harmer
0.382
3150411LDYSMT5
Adder
31.941
972215AH1-692 GEN
Adder
5.171
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.17
971283AH1-107 GEN
Solar/Wind Harmer
2.946
962981AG1-147 GEN
Solar/Wind Harmer
7.889
971167AH1-042 GEN
Solar/Wind Harmer
18.654
970189AG2-124 GEN
Solar/Wind Harmer
6.224
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3138283WHITEMARSH
Solar/Wind Harmer
0.048
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
972265AH1-717 GEN
Adder
15.821
3151191GRAVEL3
Adder
14.643
316305AF2-043 C
Solar/Wind Harmer
0.002
3146406KITTY HAWK
Solar/Wind Harmer
0.025
944011AF1-069 GEN
Solar/Wind Harmer
11.68
971967AH1-528 GEN
Solar/Wind Harmer
30.407
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
965291AG1-394 GEN
Solar/Wind Harmer
0.815
970085AG2-068 GEN
Solar/Wind Harmer
9.72
3145893MURPHYS
Solar/Wind Harmer
0.491
3145893MURPHYS
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
0.376
3145513AHOSKIE
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.365
3137643SOCKMAN
Solar/Wind Harmer
0.704
315652AC1-086 GEN
Solar/Wind Harmer
19.374
315657AE1-056 GEN
Solar/Wind Harmer
5.923
946301AF1-294 GEN
Solar/Wind Harmer
3.377
3144303KENBRDG
Solar/Wind Harmer
0.135
971443AH1-215 GEN
Solar/Wind Harmer
2.845
316005AA1-067
Solar/Wind Harmer
0.179
972193AH1-681 GEN
Adder
3.732
316118AC1-105 GEN
Solar/Wind Harmer
0.404
270494AE1-108_GEN
Solar/Wind Harmer
1.806
3151861LOWMORA
Adder
1.233
233923SMA
Solar/Wind Helper
0.988
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.3
219914AD2-027 C
Solar/Wind Helper
0.117
219607WPEMNERT C
Solar/Wind Helper
0.082
20715728PEM_W1-119
Solar/Wind Helper
0.097
205956AE1-196_GEN
Solar/Wind Helper
0.502
20675528CPH_W2-050
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
3152621GOSPORTC
Adder
2.173
3152601GOSPORTA
Adder
2.005
315833AF1-017_GEN
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
9.922
316315AB2-025 C
Solar/Wind Harmer
0.157
941031AE2-094 GEN
Solar/Wind Harmer
35.747
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970831AG2-522 GEN
Solar/Wind Harmer
7.264
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
971447AH1-217 GEN
Solar/Wind Harmer
5.04
957861AF2-080 GEN
Solar/Wind Harmer
7.098
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
970865AG2-541 GEN
Solar/Wind Harmer
4.891
3148133STUARTS
Solar/Wind Harmer
0.083
316123AC1-075 GEN
Solar/Wind Harmer
0.181
237085AD2-009_GEN
Solar/Wind Helper
1.73
228754AB1-001 C
Solar/Wind Helper
0.027
219272CLEANLIGHT C
Solar/Wind Helper
0.026
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.78
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971281AH1-106 GEN
Solar/Wind Harmer
2.946
3138133OCRAN
Solar/Wind Harmer
0.063
3143873LANEXA
Solar/Wind Harmer
0.126
315662AE1-191 GEN
Solar/Wind Harmer
0.007
3141873WAN 176
Solar/Wind Harmer
0.042
316369SG1_INVT
Solar/Wind Harmer
0.008
3143316POE
Solar/Wind Harmer
0.803
319010AE1-072 C
Solar/Wind Harmer
1.001
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
316321Z2-027
Solar/Wind Harmer
0.037
3145176PASQUOTANK
Solar/Wind Harmer
0.122
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
315816AE2-034 GEN
Solar/Wind Harmer
0.803
3130546PLYMOUTH
Solar/Wind Harmer
0.184
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
970581AG2-369 GEN
Solar/Wind Harmer
8.359
970601AG2-382 GEN
Solar/Wind Harmer
6.803
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972205AH1-687 GEN
Adder
7.463
3146033SCOT NK
Solar/Wind Harmer
0.691
970181AG2-120 GEN
Solar/Wind Harmer
2.078
3148013FISHERV
Solar/Wind Harmer
0.079
3151881LOWMORC
Adder
1.273
3151881LOWMORC
Adder
1.253
238208AF1-136 C
Solar/Wind Helper
0.215
233990AG1-397 GEN
Solar/Wind Helper
0.278
964001AG1-254 GEN
Solar/Wind Helper
0.977
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.097
207459AE1-142 C O1
Solar/Wind Helper
0.295
219620RIDERU C
Solar/Wind Helper
0.001
205943AE1-185 GEN
Solar/Wind Helper
0.503
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
20676328BVR_Y1-020
Solar/Wind Helper
0.027
3150301M RUN C
50/50
43.549
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316450AC1-158 RIC
Solar/Wind Harmer
0.365
3147666LOUISA
Solar/Wind Harmer
0.563
3150401LDYSMT4
Adder
31.841
3141906WESTMOR
Solar/Wind Harmer
0.086
316404AE1-155 C
Solar/Wind Harmer
0.048
962971AG1-146 GEN
Solar/Wind Harmer
3.381
3150861SPRUNCD
Adder
0.972
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.866
3141843SHACKLE
Adder
1.073
316280AD1-041 GEN
Solar/Wind Harmer
0.004
3141873WAN 176
Solar/Wind Harmer
3.731
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
12.476
965281AG1-393 GEN
Solar/Wind Harmer
2.197
961611AG1-000B GEN
Solar/Wind Harmer
5.45
3151171GRAVELC
Adder
2.85
3144873MCLAUGH
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
4.252
316405AF2-144 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.194
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315737AD1-076 GEN
Solar/Wind Harmer
2.365
970917AG2-570 GEN
Solar/Wind Harmer
16.254
961681AG1-008 GEN
Solar/Wind Harmer
13.506
962331AG1-082 GEN
Solar/Wind Harmer
1.916
313506AB2-031 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3146926FARMVIL
Solar/Wind Harmer
0.105
963181AG1-167 GEN
Solar/Wind Harmer
0.685
3145933PARMELE
Solar/Wind Harmer
0.17
966801AG1-551 GEN
Solar/Wind Harmer
1.979
970257AG2-171 GEN
Solar/Wind Harmer
5.422
315785AD2-033 C
Solar/Wind Harmer
1.375
971257AH1-088 GEN
50/50
5.432
3150291M RUN B
50/50
43.226
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
3132273ORANGE
Solar/Wind Harmer
0.051
3150331BIRCHWDA
Adder
38.122
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
970737AG2-469 GEN
Solar/Wind Harmer
9.258
970293AG2-193 GEN
Solar/Wind Harmer
2.259
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.155
3150921YORKTN3
Adder
5.164
315773AC2-141 GEN
Solar/Wind Harmer
7.404
970659AG2-427 GEN
Solar/Wind Harmer
2.135
3144536CHRHLND
Solar/Wind Harmer
0.03
944581AF1-123 GEN
Solar/Wind Harmer
45.254
316313AB2-026
Solar/Wind Harmer
0.124
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
315614AA2-178 GEN
Solar/Wind Harmer
1.07
971157AH1-035 GEN
Solar/Wind Harmer
2.212
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.182
957521AF2-046 GEN
Solar/Wind Harmer
13.506
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.178
3145963POPLR C
Solar/Wind Harmer
0.176
3146776BUCKING
Solar/Wind Harmer
0.063
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.174
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
971193AH1-056 GEN
Solar/Wind Harmer
10.456
3144293JTRSVLE
Adder
0.545
316210AC1-098 GEN
Solar/Wind Harmer
1.582
964241AG1-285 GEN
Solar/Wind Harmer
11.211
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.556
971683AH1-343 GEN
Solar/Wind Harmer
5.342
237061AD1-155 GEN
Solar/Wind Harmer
0.003
238221AF1-254 C O1
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.064
233952AC2-187 GEN
Solar/Wind Helper
0.239
233982AB2-133 GEN
Solar/Wind Helper
0.368
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.075
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971253AH1-086 GEN
50/50
24.442
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
972199AH1-684 GEN
Adder
5.823
3150371LDYSMT1
Adder
30.767
971781AH1-399 GEN
Solar/Wind Harmer
0.287
316473AC1-191 GEN
Solar/Wind Harmer
0.726
3142416OLDCHRC
Solar/Wind Harmer
2.065
970009AG2-005 GEN
Solar/Wind Harmer
1.58
3141766HARMONY
Solar/Wind Harmer
2.802
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
3142946ENON
Solar/Wind Harmer
0.07
970133AG2-095 GEN
Solar/Wind Harmer
1.99
3151221GRAVEL6
Adder
14.814
315813AE1-149 C
Solar/Wind Harmer
10.825
3145336SMITFLD
Solar/Wind Harmer
0.081
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.199
971153AH1-033 GEN
Solar/Wind Harmer
2.3
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
316365GEN2_N
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3146173TUNIS
Solar/Wind Harmer
0.18
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
3147043LAWRENC
Solar/Wind Harmer
0.105
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.539
959311AF2-222 GEN
Solar/Wind Harmer
15.084
316131AB2-060 GEN
Solar/Wind Harmer
0.527
315724AD1-057 GEN
Solar/Wind Harmer
0.624
972255AH1-712 GEN
Adder
83.534
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3138543CONSLDL
Solar/Wind Harmer
0.107
971623AH1-311 GEN
Solar/Wind Harmer
0.32
316283AC2-100 C
Solar/Wind Harmer
0.274
237030AB1-096 C
Solar/Wind Helper
0.08
233996TM1833_GEN
Solar/Wind Helper
0.269
232406W1-004 FULL
Solar/Wind Helper
0.523
230430AE1-229_GEN
Solar/Wind Helper
3.449
230415AB2-049 C
Solar/Wind Helper
0.031
219766PARADISE C
Solar/Wind Helper
0.056
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.153
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.043
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.058
218438BLK ROCK C
Solar/Wind Helper
0.028
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
316222AC1-221 GEN
Solar/Wind Harmer
0.583
23777801MSM_W1-116
Solar/Wind Helper
0.131
237025AB1-124 C
Solar/Wind Helper
0.187
230407AD2-065 C
Solar/Wind Helper
0.041
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.111
3148013FISHERV
Solar/Wind Harmer
0.138
315616AA1-038_C
Solar/Wind Harmer
0.001
235067AD1-061 GEN
Solar/Wind Helper
0.532
234015AF2-250 C
Solar/Wind Helper
0.039
219276PARKLANDSO C
Solar/Wind Helper
0.091
20720528MAN_W1-024
Solar/Wind Helper
0.029
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970221AG2-151 GEN
Solar/Wind Harmer
8.948
316327AA2-057 GEN
Solar/Wind Harmer
0.25
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
3151861LOWMORA
Adder
1.283
205917AD1-020 ES
Solar/Wind Helper
0.38
233994AC2-023 GEN
Solar/Wind Helper
0.99
233997TMININ_4.2
Solar/Wind Helper
0.269
233971AC1-093 C
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.516
228729W2-030 C
Solar/Wind Helper
0.113
219348LDSOLAR C
Solar/Wind Helper
0.117
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.058
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
WECLTFEXP_WEC->PJM
CLTF
1.006
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
NYPJM->LTFIMP_NY
CLTF
4.891
TVALTFEXP_TVA->PJM
CLTF
4.772
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
CPLELTFEXP_CPLE->PJM
CLTF
10.838
SIGELTFEXP_SIGE->PJM
CLTF
0.16
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117
LGEELTFEXP_LGEE->PJM
CLTF
2.004
MECLTFEXP_MEC->PJM
CLTF
5.134

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.93 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3561.83
MW Contribution:17.6
Bus #Bus NameTypeMW Contribution
3150021OMF B
50/50
0.367
3140676OCCOQUN
50/50
0.487
957971AF2-091 GEN
Solar/Wind Harmer
1.991
3138133OCRAN
Solar/Wind Harmer
-0.011
3141843SHACKLE
Adder
0.827
3143096IRON208
Adder
0.67
3142543TWELFTH
Solar/Wind Harmer
-0.002
316159AE1-175 C
Solar/Wind Harmer
0.478
3147666LOUISA
Solar/Wind Harmer
-0.071
3143226MDLTHAN
Solar/Wind Harmer
-0.018
970129AG2-093 GEN
Solar/Wind Harmer
4.032
316458AB2-190 GEN2
Solar/Wind Harmer
1.788
3138126ROCKLANDING
Solar/Wind Harmer
0.054
3150011OMF A
50/50
0.367
972197AH1-683 GEN
50/50
4.033
972135AH1-637 GEN
Solar/Wind Harmer
1.978
966881AG1-559 GEN
Solar/Wind Harmer
0.202
961951AG1-038 GEN
Solar/Wind Harmer
2.439
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.137
3142433PROV 92
Solar/Wind Harmer
-0.072
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
316192AB2-158 GEN
Solar/Wind Harmer
2.108
3145336SMITFLD
Solar/Wind Harmer
-0.069
316294AC1-161 GEN
Solar/Wind Harmer
5.624
316375AC2-012 GEN
Solar/Wind Harmer
5.987
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3150221REMNGT2
Adder
19.137
3150211REMNGT1
Adder
19.01
972201AH1-685 GEN
Adder
3.302
315683AE1-153 C
Solar/Wind Harmer
15.812
316336AC2-165 C
Solar/Wind Harmer
2.903
3145663CRESWEL
Solar/Wind Harmer
-0.046
3146206CASHIE
Solar/Wind Harmer
-0.016
316023GEN1_S
Solar/Wind Harmer
1.097
3146173TUNIS
Solar/Wind Harmer
-0.016
970937AG2-583 GEN
Solar/Wind Harmer
11.617
3145683EARLEYS
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.279
232422X3-066 FULL
Solar/Wind Helper
0.156
233964AF2-378 GEN
Solar/Wind Helper
0.057
232426Y1-080 FULL
Solar/Wind Helper
0.053
232434Z2-077 GEN
Solar/Wind Helper
0.172
219904AC1-010 C
Solar/Wind Helper
0.079
20720728JCB_W1-129
Solar/Wind Helper
0.074
20714828MDF_W3-079
Solar/Wind Helper
0.167
219680HOPEWELLV C1
Solar/Wind Helper
0.004
20742028HF_AC1-207
Solar/Wind Helper
0.179
217208PARK ELE C
Solar/Wind Helper
0.006
205941AD2-115 GEN
Solar/Wind Helper
0.613
966131AG1-482 GEN
Solar/Wind Helper
0.075
971795AH1-408 GEN
Solar/Wind Harmer
10.192
3150151POSSMC1
50/50
2.228
3150151POSSMC1
50/50
2.228
3150331BIRCHWDA
50/50
34.1
970737AG2-469 GEN
Solar/Wind Harmer
9.802
316484AD2-074 GEN
Solar/Wind Harmer
4.661
316156AD2-030 GEN
Solar/Wind Harmer
0.486
316203AE2-005 GEN
Solar/Wind Harmer
7.663
970293AG2-193 GEN
Solar/Wind Harmer
2.261
3150921YORKTN3
Adder
3.952
316170AC1-121 GEN2
Solar/Wind Harmer
0.473
315773AC2-141 GEN
Solar/Wind Harmer
7.274
970659AG2-427 GEN
Solar/Wind Harmer
1.634
3144536CHRHLND
Solar/Wind Harmer
-0.003
3132273ORANGE
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
78.643
316320Y1-086
Solar/Wind Harmer
1.002
3150291M RUN B
Adder
20.415
316435W1029_GEN3
Solar/Wind Harmer
3.081
3146516WINFALL
Solar/Wind Harmer
-0.017
316313AB2-026
Solar/Wind Harmer
0.456
315614AA2-178 GEN
Solar/Wind Harmer
1.785
971157AH1-035 GEN
Solar/Wind Harmer
2.049
3145893MURPHYS
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
-0.016
957521AF2-046 GEN
Solar/Wind Harmer
12.788
316463AE2-346 GEN
Solar/Wind Harmer
0.261
316140AB2-099
Solar/Wind Harmer
0.109
3146263WOODLND
Solar/Wind Harmer
-0.016
3145963POPLR C
Solar/Wind Harmer
-0.016
3151861LOWMORA
Adder
1.28
233918AB1-142 GEN
Solar/Wind Helper
0.685
233994AC2-023 GEN
Solar/Wind Helper
1.306
233997TMININ_4.2
Solar/Wind Helper
0.355
233971AC1-093 C
Solar/Wind Helper
0.485
228729W2-030 C
Solar/Wind Helper
0.145
219348LDSOLAR C
Solar/Wind Helper
0.149
959561AF2-247 GEN
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.013
217211CAMDEN ST C
Solar/Wind Helper
0.006
957921AF2-086 GEN
Solar/Wind Helper
0.492
970053AG2-049 GEN
50/50
3.273
3150381LDYSMT2
50/50
24.794
963051AG1-154 GEN
50/50
3.226
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316059AD1-063 C
Solar/Wind Harmer
0.411
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
315976AC1-164 GENA
Solar/Wind Harmer
19.078
316169AC1-164_GENC
Solar/Wind Harmer
16.482
315975AC1-164 GENB
Solar/Wind Harmer
0.564
3151201GRAVEL4
Adder
11.342
3151211GRAVEL5
Adder
11.198
316349AD2-085 GEN
Solar/Wind Harmer
1.531
316311AC2-079 GEN
Solar/Wind Harmer
8.684
315835AF2-110_GEN
Solar/Wind Harmer
2.143
313526AB2-022
Solar/Wind Harmer
0.461
3146396TANGLEW
Solar/Wind Harmer
0.314
315814AE2-033 C
Solar/Wind Harmer
15.687
3146206CASHIE
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.405
961941AG1-037 GEN
Solar/Wind Harmer
0.121
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3146043SEABORD
Solar/Wind Harmer
-0.016
232432Z2-076 GEN
Solar/Wind Helper
0.091
234033AF1-007_GEN
Solar/Wind Helper
9.531
957191AF2-013 GEN
50/50
16.389
957411AF2-035 GEN
Solar/Wind Harmer
8.848
958261AF2-120 GEN
Solar/Wind Harmer
7.213
316487AF1-042 GEN
Solar/Wind Harmer
2.439
316447AC1-158 HLD
Solar/Wind Harmer
3.929
3150691DARBY 3
Adder
11.585
3150701DARBY 4
Adder
11.558
3142366NRTHEST
Adder
0.526
3142946ENON
Solar/Wind Harmer
-0.002
315651AD1-115 GEN
Solar/Wind Harmer
7.681
316017AA1-139 ULT1
Solar/Wind Harmer
1.392
3146456SLIGO L269
Solar/Wind Harmer
2.03
3146386ELIZ CT
Solar/Wind Harmer
-0.017
316431W1029_GEN1
Solar/Wind Harmer
3.081
316433W1029_GEN2
Solar/Wind Harmer
3.081
315742AE1-103 GEN
Solar/Wind Harmer
1.756
3146376EDENTON
Solar/Wind Harmer
0.496
3146376EDENTON
Solar/Wind Harmer
0.496
970933AG2-581 GEN
Solar/Wind Harmer
15.383
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316181AB2-040 GEN
Solar/Wind Harmer
2.231
230407AD2-065 C
Solar/Wind Helper
0.053
20714928UPF_X1-085
Solar/Wind Helper
0.007
218440SUMMTASSOC C
Solar/Wind Helper
0.021
217202FBANKSOLAR C
Solar/Wind Helper
0.004
217201HACKENSOLA C
Solar/Wind Helper
0.004
217206BARNGR HS C
Solar/Wind Helper
0.008
217204WCALDSOLAR C
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.099
209054AE2-059 GEN
Solar/Wind Helper
0.089
3150071POSSM 5
50/50
101.841
3150391LDYSMT3
50/50
25.778
316468AD1-105 GEN
Solar/Wind Harmer
2.147
316077AC2-138 C
Solar/Wind Harmer
0.396
316441AF1-014 GEN
Solar/Wind Harmer
1.225
316075AC2-137 C
Solar/Wind Harmer
0.488
3143526WINTERP
Solar/Wind Harmer
-0.092
944641AF1-129 GEN
Adder
75.175
315697AD1-025 GEN
Solar/Wind Harmer
3.562
316316AC1-027 C
Solar/Wind Harmer
0.53
316185AD1-033 GEN
Solar/Wind Harmer
1.821
3144356SAPONY
Solar/Wind Harmer
0.589
972185AH1-677 GEN
Adder
8.276
970099AG2-077 GEN
Solar/Wind Harmer
19.996
3144293JTRSVLE
Adder
0.442
3144293JTRSVLE
Adder
0.372
233933AB2-153 GEN
Solar/Wind Helper
0.317
233944AB2-135 GEN
Solar/Wind Helper
0.802
233946AB2-136 GEN
Solar/Wind Helper
0.772
232408W1-005 C
Solar/Wind Helper
0.689
232410W1-006 C
Solar/Wind Helper
0.689
233939AC1-091 C
Solar/Wind Helper
0.474
963401AG1-189 GEN
Solar/Wind Helper
0.072
963391AG1-188 GEN
Solar/Wind Helper
0.106
20716928W4-060COL
Solar/Wind Helper
0.065
20673828FLE_V3-070
Solar/Wind Helper
0.114
20676128MHD_W3-029
Solar/Wind Helper
0.121
217081WEATEXAS C
Solar/Wind Helper
0.016
20676228FRD_X1-012
Solar/Wind Helper
0.113
207471AF2-354 C
Solar/Wind Helper
0.208
961431AF2-434 GEN
Solar/Wind Helper
0.497
972213AH1-691 GEN
50/50
4.194
944491AF1-114 GEN
Solar/Wind Harmer
5.857
972189AH1-679 GEN
Adder
2.807
3138133OCRAN
Solar/Wind Harmer
-0.006
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
2.192
3143873LANEXA
Solar/Wind Harmer
-0.011
971281AH1-106 GEN
Solar/Wind Harmer
2.897
316369SG1_INVT
Solar/Wind Harmer
3.146
3143316POE
Solar/Wind Harmer
-0.068
319010AE1-072 C
Solar/Wind Harmer
3.475
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316321Z2-027
Solar/Wind Harmer
0.46
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
315611Z1-036_GEN2
Solar/Wind Harmer
4.161
3147346CASHSCORNER
Solar/Wind Harmer
0.26
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.339
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315733AD1-074 GEN2
Solar/Wind Harmer
3.31
970601AG2-382 GEN
Solar/Wind Harmer
7.123
970581AG2-369 GEN
Solar/Wind Harmer
8.69
946281AF1-292 GEN
Solar/Wind Harmer
0.36
316087AB2-174 GEN
Solar/Wind Harmer
2.286
972205AH1-687 GEN
Adder
5.971
3151881LOWMORC
Adder
1.27
3151881LOWMORC
Adder
1.25
233990AG1-397 GEN
Solar/Wind Helper
0.041
964001AG1-254 GEN
Solar/Wind Helper
1.261
227927V4-067C
Solar/Wind Helper
0.013
219688LUMSOLAR_S C
Solar/Wind Helper
0.052
214067T20SOLAR
Solar/Wind Helper
0.015
20715828PEM_W1-120
Solar/Wind Helper
0.124
207459AE1-142 C O1
Solar/Wind Helper
0.373
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.203
20676328BVR_Y1-020
Solar/Wind Helper
0.033
205943AE1-185 GEN
Solar/Wind Helper
0.575
961261AF2-417 GEN
Solar/Wind Helper
0.512
959431AF2-234 GEN
Solar/Wind Helper
0.976
3150081POSSM6A
50/50
1.654
3141316ARNOLDS
50/50
0.47
3150351NORNECKC2
Adder
1.695
3144216WINCHST
Adder
0.592
315778AD1-151 GEN
Solar/Wind Harmer
15.278
315839AE2-212 C
Solar/Wind Harmer
0.53
3151101ELIZAR3
Adder
14.297
944601AF1-125 GEN
Solar/Wind Harmer
77.415
972217AH1-693 GEN
Adder
2.54
3151761LOISA E
Adder
20.004
972183AH1-676 GEN
Adder
161.171
316258AE1-075 C
Solar/Wind Harmer
0.411
3143336POWHATN
Solar/Wind Harmer
1.707
3141196NOKESVL
Solar/Wind Harmer
-0.067
966621AG1-532 GEN
Solar/Wind Harmer
0.326
3144293JTRSVLE
Adder
0.442
226910AB2-157 C
Solar/Wind Helper
0.049
223402AF1-300 C
Solar/Wind Helper
0.748
233982AB2-133 GEN
Solar/Wind Helper
0.488
233940AF2-379 C
Solar/Wind Helper
0.084
233952AC2-187 GEN
Solar/Wind Helper
0.315
219623KINSLEYBEA C
Solar/Wind Helper
0.003
20716028EGP_W2-019
Solar/Wind Helper
0.024
219612MATRIX C
Solar/Wind Helper
0.03
219908AB1-139 C
Solar/Wind Helper
0.093
20673728F2S_V4-070
Solar/Wind Helper
0.037
207510AF2-138 C
Solar/Wind Helper
0.1
209027LOR2_Q27
Solar/Wind Helper
1.175
961421AF2-433 GEN
Solar/Wind Helper
0.497
946691AF1-333 GEN
Solar/Wind Helper
0.489
946741AF1-338 GEN
Solar/Wind Helper
0.489
3150411LDYSMT5
50/50
25.907
972215AH1-692 GEN
50/50
4.194
316223AC1-118
Solar/Wind Harmer
0.522
3141813NORNECK
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
8.074
957601AF2-054 GEN
Solar/Wind Harmer
0.544
315666AE1-190 GEN
Solar/Wind Harmer
0.548
971167AH1-042 GEN
Solar/Wind Harmer
17.397
316164AC1-076 GEN
Solar/Wind Harmer
1.517
3138283WHITEMARSH
Solar/Wind Harmer
0.028
316233AE1-074 FULL
Solar/Wind Harmer
0.48
971283AH1-107 GEN
Solar/Wind Harmer
2.897
316132AB2-190 GEN1
Solar/Wind Harmer
1.788
972265AH1-717 GEN
Adder
12.099
3151191GRAVEL3
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.518
3146406KITTY HAWK
Solar/Wind Harmer
0.014
944011AF1-069 GEN
Solar/Wind Harmer
9.851
971967AH1-528 GEN
Solar/Wind Harmer
31.136
315732AD1-074 GEN1
Solar/Wind Harmer
3.31
315735AD1-075 GEN1
Solar/Wind Harmer
1.656
965291AG1-394 GEN
Solar/Wind Harmer
1.45
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
-0.016
970085AG2-068 GEN
Solar/Wind Harmer
10.104
3145513AHOSKIE
Solar/Wind Harmer
0.141
3145513AHOSKIE
Solar/Wind Harmer
-0.016
315607AA1-063A GEN
Solar/Wind Harmer
1.624
972193AH1-681 GEN
Adder
3.199
3151861LOWMORA
Adder
1.23
233935AB2-179 C
Solar/Wind Helper
1.735
232436AB1-176 C
Solar/Wind Helper
0.06
233923SMA
Solar/Wind Helper
1.302
219914AD2-027 C
Solar/Wind Helper
0.15
219607WPEMNERT C
Solar/Wind Helper
0.104
20715728PEM_W1-119
Solar/Wind Helper
0.124
20675528CPH_W2-050
Solar/Wind Helper
0.109
218524CNTRALGAS1 C
Solar/Wind Helper
0.203
207530AG1-191 GEN
Solar/Wind Helper
0.081
20675128HRM_W1-127
Solar/Wind Helper
0.036
205956AE1-196_GEN
Solar/Wind Helper
0.581
959421AF2-233 GEN
Solar/Wind Helper
0.488
3150151POSSMC1
50/50
2.228
316337AD2-073 GEN
Solar/Wind Harmer
0.512
3141726DUNNSVL
Solar/Wind Harmer
-0.074
962861AG1-135 GEN
Solar/Wind Harmer
6.97
316045AC1-158 PL2
Solar/Wind Harmer
5.715
3150851SPRUNCC
Adder
0.733
970659AG2-427 GEN
Solar/Wind Harmer
9.221
316093AE2-104_GEN
Solar/Wind Harmer
4.984
316006AB2-029 C
Solar/Wind Harmer
0.983
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
315800Z1-036_GEN1
Solar/Wind Harmer
4.161
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
0.482
970919AG2-571 GEN
Solar/Wind Harmer
5.126
3146263WOODLND
Solar/Wind Harmer
-0.016
3145963POPLR C
Solar/Wind Harmer
-0.016
219686LUMSOLAR_N C
Solar/Wind Helper
0.052
219304NAMERICA C
Solar/Wind Helper
0.171
207445AB1-138_GEN
Solar/Wind Helper
0.134
20676428JCR_X2-075
Solar/Wind Helper
0.085
217209CENTRL HS C
Solar/Wind Helper
0.01
20674328GAR_V4-001
Solar/Wind Helper
0.028
207439AE1-081 C O1
Solar/Wind Helper
0.023
961301AF2-421 GEN
Solar/Wind Helper
0.512
963151AG1-164 GEN
Solar/Wind Helper
0.512
961341AF2-425 GEN
Solar/Wind Helper
0.499
212507AE2-042_GEN
Solar/Wind Helper
1.74
3150091POSSM6B
50/50
1.654
970317AG2-208 GEN
Solar/Wind Harmer
8.602
966871AG1-558 GEN
Solar/Wind Harmer
0.555
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3142296MT RD221
Adder
0.518
3150671DARBY 1
Adder
11.531
971223AH1-071 GEN
Solar/Wind Harmer
2.216
316240AF1-291 C
Solar/Wind Harmer
0.533
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.574
3142956BIRDNECK
Solar/Wind Harmer
0.927
316018AA1-139 ULT2
Solar/Wind Harmer
1.474
3151721LOISA A
Adder
9.761
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
972187AH1-678 GEN
Adder
4.177
316065AD1-022 GEN
Solar/Wind Harmer
8.157
3145893MURPHYS
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.029
226929AD2-058 GEN
Solar/Wind Helper
0.393
233987AB2-037 GEN
Solar/Wind Helper
3.185
234036AF2-325 C
Solar/Wind Helper
0.057
233901CHERRYDALE C
Solar/Wind Helper
0.316
20720628TIN_W1-124
Solar/Wind Helper
0.242
207442AE1-156 GEN
Solar/Wind Helper
0.41
20671828STAW2-080
Solar/Wind Helper
0.033
20674128FR_U2-059
Solar/Wind Helper
0.005
211065PSPA IPP
Solar/Wind Helper
0.182
211065PSPA IPP
Solar/Wind Helper
0.182
209029WAYMART-WD
Solar/Wind Helper
0.936
946751AF1-339 GEN
Solar/Wind Helper
0.489
971069AG2-661 GEN
Solar/Wind Harmer
2.791
971647AH1-324 GEN
Solar/Wind Harmer
8.789
316254AC1-120 GEN1
Solar/Wind Harmer
1.418
961611AG1-000B GEN
Solar/Wind Harmer
8.659
3151171GRAVELC
Adder
1.658
316381AD1-082 GEN
Solar/Wind Harmer
1.591
970661AG2-428 GEN
Solar/Wind Harmer
18.39
3150981CHESPKA
Adder
1.923
316388AE2-253 GEN
Solar/Wind Harmer
1.161
316246AF1-032 C
Solar/Wind Harmer
0.348
3150281M RUN A
Adder
20.58
3151751LOISA D
Adder
9.812
3130156CHOWAN
Solar/Wind Harmer
-0.017
971163AH1-040 GEN
Solar/Wind Harmer
15.508
970087AG2-069 GEN
Solar/Wind Harmer
15.156
957481AF2-042 GEN
Solar/Wind Harmer
49.991
223401AF1-299 GEN
Solar/Wind Helper
0.748
233915AB1-141 GEN
Solar/Wind Helper
0.685
232428Y3-058 C
Solar/Wind Helper
0.459
233998TM1NIN_3.36
Solar/Wind Helper
0.355
232404W1-003 C
Solar/Wind Helper
0.689
233950AC2-186 GEN
Solar/Wind Helper
0.158
233972AC1-094 C
Solar/Wind Helper
0.41
228728W1-130C
Solar/Wind Helper
0.071
218660EHAMPSOLAR C
Solar/Wind Helper
0.043
963711AG1-223 GEN
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.395
20715228NPK_W1-113
Solar/Wind Helper
0.1
20675428EAM_W2-061
Solar/Wind Helper
0.02
207518AF1-320_GEN
Solar/Wind Helper
1.931
212266LOR1
Solar/Wind Helper
0.054
209071AE2-133 GEN
Solar/Wind Helper
0.088
3150181POSSMC2
50/50
2.247
3150181POSSMC2
50/50
2.228
3150181POSSMC2
50/50
2.228
972195AH1-682 GEN
50/50
3.388
315673AE1-157 GEN
Solar/Wind Harmer
14.947
3150341NORNECKC1
Adder
1.751
3150341NORNECKC1
Adder
1.737
3150681DARBY 2
Adder
11.544
316033AB2-134 GEN
Solar/Wind Harmer
5.679
316236AE1-162_GEN
Solar/Wind Harmer
0.525
970657AG2-426 GEN
Solar/Wind Harmer
5.416
970657AG2-426 GEN
Solar/Wind Harmer
1.133
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.161
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3130086AYDLETT
Solar/Wind Harmer
-0.068
966001AG1-469 GEN
Solar/Wind Harmer
0.321
3151731LOISA B
Adder
9.812
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
208835TUHI V3-051
Solar/Wind Helper
0.036
208835TUHI V3-051
Solar/Wind Helper
0.036
232424Y1-079 C
Solar/Wind Helper
0.158
233970AC1-092 C
Solar/Wind Helper
0.474
230433AD2-135 GEN
Solar/Wind Helper
0.022
219921AF1-264
Solar/Wind Helper
0.067
219615MILLCREEK C
Solar/Wind Helper
0.035
20674928WA_W3-044
Solar/Wind Helper
0.121
966111AG1-480 GEN
Solar/Wind Helper
0.054
208972BECR K09
Solar/Wind Helper
0.376
209137AF2-361 C
Solar/Wind Helper
1.35
3150101POSSM6S
50/50
2.528
3150401LDYSMT4
50/50
25.826
3141906WESTMOR
Solar/Wind Harmer
-0.008
316404AE1-155 C
Solar/Wind Harmer
3.591
962971AG1-146 GEN
Solar/Wind Harmer
3.46
316044AC1-158 PL1
Solar/Wind Harmer
1.787
316450AC1-158 RIC
Solar/Wind Harmer
0.476
3141873WAN 176
Solar/Wind Harmer
2.158
316280AD1-041 GEN
Solar/Wind Harmer
1.37
3141843SHACKLE
Adder
0.827
3150371LDYSMT1
50/50
24.955
970497AG2-320 GEN
50/50
16.885
966881AG1-559 GEN
Solar/Wind Harmer
0.591
971781AH1-399 GEN
Solar/Wind Harmer
1.188
970009AG2-005 GEN
Solar/Wind Harmer
2.314
316473AC1-191 GEN
Solar/Wind Harmer
1.987
3142416OLDCHRC
Solar/Wind Harmer
1.836
3141766HARMONY
Solar/Wind Harmer
1.619
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
3142946ENON
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
1.996
3151221GRAVEL6
Adder
11.329
3145336SMITFLD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
10.889
316083AB2-161 GEN
Solar/Wind Harmer
2.815
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.095
3150231REMNGT3
Adder
20.661
3150241REMNGT4
Adder
19.264
972199AH1-684 GEN
Adder
2.921
3145273HOLLAND
Solar/Wind Harmer
-0.013
3146376EDENTON
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.016
316365GEN2_N
Solar/Wind Harmer
1.097
3146173TUNIS
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.177
972255AH1-712 GEN
Adder
71.607
227287AC2-120 GEN
Solar/Wind Helper
1.262
233996TM1833_GEN
Solar/Wind Helper
0.355
232406W1-004 FULL
Solar/Wind Helper
0.689
230430AE1-229_GEN
Solar/Wind Helper
4.448
230415AB2-049 C
Solar/Wind Helper
0.04
219766PARADISE C
Solar/Wind Helper
0.072
219912AD2-042 GEN
Solar/Wind Helper
0.196
219291REEVESSOUT C
Solar/Wind Helper
0.015
219236SOUTHERNHQ C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.054
20720828JCB_W4-025
Solar/Wind Helper
0.082
20714528FRN_Y2-051
Solar/Wind Helper
0.073
218438BLK ROCK C
Solar/Wind Helper
0.035
219919AE1-041 FULL
Solar/Wind Helper
0.005
20674628WNG_W3-110
Solar/Wind Helper
0.11
963071AG1-156 GEN
Solar/Wind Helper
1.658
209067AE2-060 GEN
Solar/Wind Helper
0.08
3141426STAFORD
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.018
316312AB1-027
Solar/Wind Harmer
0.614
316314AB2-024 C
Solar/Wind Harmer
1.555
957831AF2-077 GEN
Solar/Wind Harmer
0.539
971285AH1-108 GEN
Adder
1.2
971445AH1-216 GEN
Solar/Wind Harmer
10.79
3151081ELIZAR1
Adder
14.117
3151091ELIZAR2
Adder
13.871
3152611GOSPORTB
Adder
1.961
3152621GOSPORTC
Adder
1.664
3152601GOSPORTA
Adder
1.535
315833AF1-017_GEN
Solar/Wind Harmer
3.27
957871AF2-081 GEN
Solar/Wind Harmer
8.603
316315AB2-025 C
Solar/Wind Harmer
0.455
941031AE2-094 GEN
Solar/Wind Harmer
31.438
970673AG2-436 GEN
Solar/Wind Harmer
34.947
970673AG2-436 GEN
Solar/Wind Harmer
17.695
228754AB1-001 C
Solar/Wind Helper
0.034
219272CLEANLIGHT C
Solar/Wind Helper
0.033
20675928HOL_W4-097
Solar/Wind Helper
0.061
207484AF2-139 C O1
Solar/Wind Helper
0.103
20675728RH_W2-091
Solar/Wind Helper
0.168
209116AE2-175 GEN
Solar/Wind Helper
2.147
964051AG1-259 GEN
Solar/Wind Helper
0.073
964061AG1-260 GEN
Solar/Wind Helper
0.073
972223AH1-696 GEN
50/50
17.601
3141346CRANES
50/50
0.247
972219AH1-694 GEN
50/50
2.904
3150351NORNECKC2
Adder
1.667
964211AG1-282 GEN
Solar/Wind Harmer
0.563
944631AF1-128 GEN
Adder
76.064
3143526WINTERP
Solar/Wind Harmer
-0.092
971317AH1-138 GEN
Solar/Wind Harmer
2.221
315671AE2-027_GEN
Solar/Wind Harmer
13.243
944591AF1-124 GEN
Solar/Wind Harmer
78.926
316072AD1-144
Solar/Wind Harmer
0.349
939411AE1-173 GEN
Solar/Wind Harmer
85.695
971685AH1-345 GEN
Solar/Wind Harmer
1.499
940641AE2-051 GEN
Solar/Wind Harmer
16.029
3143336POWHATN
Solar/Wind Harmer
2.008
971547AH1-271 GEN
Solar/Wind Harmer
4.071
960081AF2-299 GEN
Solar/Wind Harmer
1.81
972277AH1-723 GEN
Adder
83.443
3144293JTRSVLE
Adder
0.442
233930AB2-032 GEN
Solar/Wind Helper
0.519
233954AC2-188 GEN
Solar/Wind Helper
0.315
230511AF1-262
Solar/Wind Helper
0.019
230434AG1-499 GEN
Solar/Wind Helper
0.303
219258KINSLEYDEP C
Solar/Wind Helper
0.101
219907AC1-030 C
Solar/Wind Helper
0.044
218428ETC SOLAR C
Solar/Wind Helper
0.006
217213AMBOY SO C
Solar/Wind Helper
0.036
207528AF2-192 GEN
Solar/Wind Helper
0.096
20673628F1S_V4-069
Solar/Wind Helper
0.037
20675828AU_W4-064
Solar/Wind Helper
0.036
207437AD2-070 GEN
Solar/Wind Helper
0.169
20671928W4-073
Solar/Wind Helper
0.11
946731AF1-337 GEN
Solar/Wind Helper
0.489
966261AG1-495 GEN
Solar/Wind Helper
0.101
20674828DL_W4-046
Solar/Wind Helper
0.01
207408W3-077 C
Solar/Wind Helper
0.103
960921AF2-383 GEN
Solar/Wind Helper
0.211
205932AD2-116_GEN
Solar/Wind Helper
0.581
3143096IRON208
Adder
0.67
3143096IRON208
Adder
0.657
3150861SPRUNCD
Adder
0.733
316382AG1-145 C
Solar/Wind Harmer
0.537
3147666LOUISA
Solar/Wind Harmer
-0.041
970129AG2-093 GEN
Solar/Wind Harmer
9.954
965281AG1-393 GEN
Solar/Wind Harmer
2.203
961611AG1-000B GEN
Solar/Wind Harmer
3.695
3151171GRAVELC
Adder
2.18
970661AG2-428 GEN
Solar/Wind Harmer
3.259
3144873MCLAUGH
Solar/Wind Harmer
0
3150301M RUN C
Adder
20.568
3146626S HERTFORD
Solar/Wind Harmer
-0.017
316405AF2-144 C
Solar/Wind Harmer
0.433
3156081AA2-088 GEN
Solar/Wind Harmer
5.315
315737AD1-076 GEN
Solar/Wind Harmer
3.111
961681AG1-008 GEN
Solar/Wind Harmer
12.788
970917AG2-570 GEN
Solar/Wind Harmer
40.495
962331AG1-082 GEN
Solar/Wind Harmer
2.017
313506AB2-031 GEN
Solar/Wind Harmer
1.286
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
234015AF2-250 C
Solar/Wind Helper
0.051
219276PARKLANDSO C
Solar/Wind Helper
0.115
20720528MAN_W1-024
Solar/Wind Helper
0.036
217169METRODIV C
Solar/Wind Helper
0.005
20676728BRNX1-095
Solar/Wind Helper
0.037
963161AG1-165 GEN
Solar/Wind Helper
0.512
961331AF2-424 GEN
Solar/Wind Helper
0.499
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.087
WECLTFEXP_WEC->PJM
CLTF
2.182
LAGNLTFEXP_LAGN->PJM
CLTF
13.612
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.121
NYPJM->LTFIMP_NY
CLTF
5.379
TVALTFEXP_TVA->PJM
CLTF
6.85
AG2-052LTFEXP_AG2-052->PJM
LTF
0.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.468
CPLELTFEXP_CPLE->PJM
CLTF
10.068
SIGELTFEXP_SIGE->PJM
CLTF
0.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
85.372
LGEELTFEXP_LGEE->PJM
CLTF
4.06
MECLTFEXP_MEC->PJM
CLTF
9.963
AH1-155LTFEXP_AH1-155->PJM
LTF
0.195

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.21 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3322.42
MW Contribution:15.41
Bus #Bus NameTypeMW Contribution
3150151POSSMC1
50/50
1.951
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.928
316045AC1-158 PL2
Solar/Wind Harmer
4.767
3150851SPRUNCC
Adder
0.62
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316093AE2-104_GEN
Solar/Wind Harmer
4.2
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
315800Z1-036_GEN1
Solar/Wind Harmer
3.503
316006AB2-029 C
Solar/Wind Harmer
0.804
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
970919AG2-571 GEN
Solar/Wind Harmer
4.3
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.795
3150091POSSM6B
50/50
1.448
970317AG2-208 GEN
Solar/Wind Harmer
7.354
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
3150671DARBY 1
Adder
9.764
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3140676OCCOQUN
50/50
0.417
957971AF2-091 GEN
Solar/Wind Harmer
1.709
3138133OCRAN
Solar/Wind Harmer
-0.009
3141843SHACKLE
Adder
0.701
3143096IRON208
Adder
0.567
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.404
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.407
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
3151171GRAVELC
Adder
1.4
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
3150981CHESPKA
Adder
1.622
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
316246AF1-032 C
Solar/Wind Harmer
0.293
3151751LOISA D
Adder
8.139
3130156CHOWAN
Solar/Wind Harmer
-0.014
3150281M RUN A
Adder
16.797
971163AH1-040 GEN
Solar/Wind Harmer
13.037
970087AG2-069 GEN
Solar/Wind Harmer
12.711
957481AF2-042 GEN
Solar/Wind Harmer
41.862
223401AF1-299 GEN
Solar/Wind Helper
0.708
233915AB1-141 GEN
Solar/Wind Helper
0.492
232428Y3-058 C
Solar/Wind Helper
0.328
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
3150181POSSMC2
50/50
1.967
3150181POSSMC2
50/50
1.951
3150181POSSMC2
50/50
1.951
972195AH1-682 GEN
50/50
2.908
315673AE1-157 GEN
Solar/Wind Harmer
12.798
3150341NORNECKC1
Adder
1.491
3150341NORNECKC1
Adder
1.479
3150681DARBY 2
Adder
9.775
316033AB2-134 GEN
Solar/Wind Harmer
4.797
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.267
3151731LOISA B
Adder
8.139
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
957191AF2-013 GEN
50/50
14.124
957411AF2-035 GEN
Solar/Wind Harmer
7.564
958261AF2-120 GEN
Solar/Wind Harmer
6.135
316487AF1-042 GEN
Solar/Wind Harmer
2.073
3150691DARBY 3
Adder
9.809
3150021OMF B
50/50
0.314
3150371LDYSMT1
50/50
21.422
970497AG2-320 GEN
50/50
14.485
966881AG1-559 GEN
Solar/Wind Harmer
0.505
3141426STAFORD
Solar/Wind Harmer
-0.004
3141913WHIT STONE
Solar/Wind Harmer
-0.015
316312AB1-027
Solar/Wind Harmer
0.52
316314AB2-024 C
Solar/Wind Harmer
1.318
957831AF2-077 GEN
Solar/Wind Harmer
0.456
971285AH1-108 GEN
Adder
1.014
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.7
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
957871AF2-081 GEN
Solar/Wind Harmer
7.253
316315AB2-025 C
Solar/Wind Harmer
0.383
941031AE2-094 GEN
Solar/Wind Harmer
26.435
970673AG2-436 GEN
Solar/Wind Harmer
29.368
970673AG2-436 GEN
Solar/Wind Harmer
14.87
972223AH1-696 GEN
50/50
15.409
3141346CRANES
50/50
0.214
972219AH1-694 GEN
50/50
2.493
3150351NORNECKC2
Adder
1.419
964211AG1-282 GEN
Solar/Wind Harmer
0.479
944631AF1-128 GEN
Adder
64.359
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.879
315671AE2-027_GEN
Solar/Wind Harmer
11.189
944591AF1-124 GEN
Solar/Wind Harmer
66.562
316072AD1-144
Solar/Wind Harmer
0.295
939411AE1-173 GEN
Solar/Wind Harmer
72.191
940641AE2-051 GEN
Solar/Wind Harmer
13.499
3143336POWHATN
Solar/Wind Harmer
1.684
971685AH1-345 GEN
Solar/Wind Harmer
1.226
971547AH1-271 GEN
Solar/Wind Harmer
3.418
960081AF2-299 GEN
Solar/Wind Harmer
1.517
3145823KELFORD
Solar/Wind Harmer
-0.013
972277AH1-723 GEN
Adder
69.269
3144293JTRSVLE
Adder
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.373
233954AC2-188 GEN
Solar/Wind Helper
0.226
971781AH1-399 GEN
Solar/Wind Harmer
1.014
970009AG2-005 GEN
Solar/Wind Harmer
1.967
316473AC1-191 GEN
Solar/Wind Harmer
1.687
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.687
3151221GRAVEL6
Adder
9.565
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.189
316083AB2-161 GEN
Solar/Wind Harmer
2.375
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150231REMNGT3
Adder
16.854
3150241REMNGT4
Adder
15.715
972199AH1-684 GEN
Adder
2.383
3146206CASHIE
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.827
972255AH1-712 GEN
Adder
59.443
227287AC2-120 GEN
Solar/Wind Helper
1.292
233996TM1833_GEN
Solar/Wind Helper
0.254
232406W1-004 FULL
Solar/Wind Helper
0.493
970053AG2-049 GEN
50/50
2.783
3150381LDYSMT2
50/50
21.283
963051AG1-154 GEN
50/50
2.769
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.349
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
315976AC1-164 GENA
Solar/Wind Harmer
16.157
316169AC1-164_GENC
Solar/Wind Harmer
13.958
315975AC1-164 GENB
Solar/Wind Harmer
0.478
3151201GRAVEL4
Adder
9.576
3151211GRAVEL5
Adder
9.455
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146396TANGLEW
Solar/Wind Harmer
0.264
315814AE2-033 C
Solar/Wind Harmer
13.2
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.34
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.814
960921AF2-383 GEN
Solar/Wind Helper
0.173
3150991CHESPKB
Adder
1.328
3142956BIRDNECK
Solar/Wind Harmer
0.782
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3151721LOISA A
Adder
8.097
972187AH1-678 GEN
Adder
3.508
316065AD1-022 GEN
Solar/Wind Harmer
6.85
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
226929AD2-058 GEN
Solar/Wind Helper
0.403
233987AB2-037 GEN
Solar/Wind Helper
2.278
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.226
3150411LDYSMT5
50/50
22.239
972215AH1-692 GEN
50/50
3.6
316223AC1-118
Solar/Wind Harmer
0.446
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.86
957601AF2-054 GEN
Solar/Wind Harmer
0.461
315666AE1-190 GEN
Solar/Wind Harmer
0.465
971167AH1-042 GEN
Solar/Wind Harmer
14.738
3138283WHITEMARSH
Solar/Wind Harmer
0.023
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
972265AH1-717 GEN
Adder
10.215
3151191GRAVEL3
Adder
9.455
316305AF2-043 C
Solar/Wind Harmer
0.437
3146406KITTY HAWK
Solar/Wind Harmer
0.012
944011AF1-069 GEN
Solar/Wind Harmer
8.283
971967AH1-528 GEN
Solar/Wind Harmer
26.154
315732AD1-074 GEN1
Solar/Wind Harmer
2.781
315735AD1-075 GEN1
Solar/Wind Harmer
1.391
965291AG1-394 GEN
Solar/Wind Harmer
1.218
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
3150101POSSM6S
50/50
2.213
3150401LDYSMT4
50/50
22.17
3141906WESTMOR
Solar/Wind Harmer
-0.007
316404AE1-155 C
Solar/Wind Harmer
3.054
962971AG1-146 GEN
Solar/Wind Harmer
2.94
3141873WAN 176
Solar/Wind Harmer
1.83
316280AD1-041 GEN
Solar/Wind Harmer
1.161
3141843SHACKLE
Adder
0.701
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970129AG2-093 GEN
Solar/Wind Harmer
8.412
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151171GRAVELC
Adder
1.84
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.014
316405AF2-144 C
Solar/Wind Harmer
0.364
3150301M RUN C
Adder
16.786
3156081AA2-088 GEN
Solar/Wind Harmer
4.464
315737AD1-076 GEN
Solar/Wind Harmer
2.613
961681AG1-008 GEN
Solar/Wind Harmer
10.733
970917AG2-570 GEN
Solar/Wind Harmer
33.966
962331AG1-082 GEN
Solar/Wind Harmer
1.693
313506AB2-031 GEN
Solar/Wind Harmer
1.078
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
234015AF2-250 C
Solar/Wind Helper
0.037
972213AH1-691 GEN
50/50
3.6
944491AF1-114 GEN
Solar/Wind Harmer
5.027
972189AH1-679 GEN
Adder
2.388
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.858
3143873LANEXA
Solar/Wind Harmer
-0.009
971281AH1-106 GEN
Solar/Wind Harmer
2.447
316369SG1_INVT
Solar/Wind Harmer
2.658
3143316POE
Solar/Wind Harmer
-0.058
319010AE1-072 C
Solar/Wind Harmer
2.929
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
315611Z1-036_GEN2
Solar/Wind Harmer
3.503
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.781
970601AG2-382 GEN
Solar/Wind Harmer
5.981
970581AG2-369 GEN
Solar/Wind Harmer
7.288
946281AF1-292 GEN
Solar/Wind Harmer
0.302
316087AB2-174 GEN
Solar/Wind Harmer
1.916
972205AH1-687 GEN
Adder
4.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
3150071POSSM 5
50/50
89.158
3150391LDYSMT3
50/50
22.128
316468AD1-105 GEN
Solar/Wind Harmer
1.833
316077AC2-138 C
Solar/Wind Harmer
0.337
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.531
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316316AC1-027 C
Solar/Wind Harmer
0.447
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3144356SAPONY
Solar/Wind Harmer
0.495
972185AH1-677 GEN
Adder
6.952
970099AG2-077 GEN
Solar/Wind Harmer
16.745
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
233933AB2-153 GEN
Solar/Wind Helper
0.227
233944AB2-135 GEN
Solar/Wind Helper
0.575
233946AB2-136 GEN
Solar/Wind Helper
0.552
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
970085AG2-068 GEN
Solar/Wind Harmer
8.474
3145513AHOSKIE
Solar/Wind Harmer
0.118
3145513AHOSKIE
Solar/Wind Harmer
-0.013
315607AA1-063A GEN
Solar/Wind Harmer
1.361
972193AH1-681 GEN
Adder
2.656
233935AB2-179 C
Solar/Wind Helper
1.252
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.931
315652AC1-086 GEN
Solar/Wind Harmer
5.139
3150151POSSMC1
50/50
1.951
3150151POSSMC1
50/50
1.951
3150331BIRCHWDA
50/50
29.482
970737AG2-469 GEN
Solar/Wind Harmer
8.391
316484AD2-074 GEN
Solar/Wind Harmer
3.962
316156AD2-030 GEN
Solar/Wind Harmer
0.412
316203AE2-005 GEN
Solar/Wind Harmer
6.497
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3150921YORKTN3
Adder
3.34
315773AC2-141 GEN
Solar/Wind Harmer
6.136
3150011OMF A
50/50
0.314
972197AH1-683 GEN
50/50
3.462
972135AH1-637 GEN
Solar/Wind Harmer
1.695
966881AG1-559 GEN
Solar/Wind Harmer
0.173
961951AG1-038 GEN
Solar/Wind Harmer
2.073
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3146456SLIGO L269
Solar/Wind Harmer
-0.014
315683AE1-153 C
Solar/Wind Harmer
13.032
316336AC2-165 C
Solar/Wind Harmer
2.431
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.611
3150211REMNGT1
Adder
15.507
972201AH1-685 GEN
Adder
2.693
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.92
3146173TUNIS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.013
970937AG2-583 GEN
Solar/Wind Harmer
9.686
3147043LAWRENC
Adder
1.071
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232434Z2-077 GEN
Solar/Wind Helper
0.123
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
944581AF1-123 GEN
Solar/Wind Harmer
66.324
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.383
3150291M RUN B
Adder
16.662
315614AA2-178 GEN
Solar/Wind Harmer
1.5
971157AH1-035 GEN
Solar/Wind Harmer
1.722
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
957521AF2-046 GEN
Solar/Wind Harmer
10.733
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.934
233997TMININ_4.2
Solar/Wind Helper
0.254
233971AC1-093 C
Solar/Wind Helper
0.346
3150701DARBY 4
Adder
9.787
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.277
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3146456SLIGO L269
Solar/Wind Harmer
1.711
315651AD1-115 GEN
Solar/Wind Harmer
6.347
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
315742AE1-103 GEN
Solar/Wind Harmer
1.477
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
970933AG2-581 GEN
Solar/Wind Harmer
12.91
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.87
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
232424Y1-079 C
Solar/Wind Helper
0.113
233970AC1-092 C
Solar/Wind Helper
0.339
3150081POSSM6A
50/50
1.448
3141316ARNOLDS
50/50
0.405
3150351NORNECKC2
Adder
1.443
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
12.908
315839AE2-212 C
Solar/Wind Harmer
0.447
3151101ELIZAR3
Adder
12.059
944601AF1-125 GEN
Solar/Wind Harmer
65.289
316258AE1-075 C
Solar/Wind Harmer
0.345
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.592
972183AH1-676 GEN
Adder
133.629
972217AH1-693 GEN
Adder
2.072
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
316317KELFORD C
Solar/Wind Harmer
0.63
3145823KELFORD
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.368
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.708
233982AB2-133 GEN
Solar/Wind Helper
0.35
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.289
NYPJM->LTFIMP_NY
CLTF
3.821
TVALTFEXP_TVA->PJM
CLTF
5.516
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.158
WECLTFEXP_WEC->PJM
CLTF
1.731
LAGNLTFEXP_LAGN->PJM
CLTF
10.958
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.371
LGEELTFEXP_LGEE->PJM
CLTF
3.225
MECLTFEXP_MEC->PJM
CLTF
7.931
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.907
CPLELTFEXP_CPLE->PJM
CLTF
8.326
SIGELTFEXP_SIGE->PJM
CLTF
0.249

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:2913.06 MVA
Rating Type:B
MVA to Mitigate:3060.21
MW Contribution:15.37
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
50/50
0.415
3138133OCRAN
Solar/Wind Harmer
0.082
3141843SHACKLE
Adder
0.697
3143096IRON208
Adder
0.563
3142543TWELFTH
Solar/Wind Harmer
0.013
316159AE1-175 C
Solar/Wind Harmer
0.115
3143226MDLTHAN
Solar/Wind Harmer
0.132
970129AG2-093 GEN
Solar/Wind Harmer
3.759
316458AB2-190 GEN2
Solar/Wind Harmer
0.709
3138126ROCKLANDING
Solar/Wind Harmer
0.061
971069AG2-661 GEN
Solar/Wind Harmer
2.343
971647AH1-324 GEN
Solar/Wind Harmer
5.603
3147666LOUISA
Solar/Wind Harmer
0.525
961611AG1-000B GEN
Solar/Wind Harmer
6.873
3151171GRAVELC
Adder
1.391
316381AD1-082 GEN
Solar/Wind Harmer
0.135
970661AG2-428 GEN
Solar/Wind Harmer
12.841
3150981CHESPKA
Adder
1.611
316254AC1-120 GEN1
Solar/Wind Harmer
0.274
316388AE2-253 GEN
Solar/Wind Harmer
0.402
316246AF1-032 C
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.124
3151751LOISA D
Adder
8.077
971163AH1-040 GEN
Solar/Wind Harmer
9.834
3150281M RUN A
Adder
16.653
970087AG2-069 GEN
Solar/Wind Harmer
9.586
957481AF2-042 GEN
Solar/Wind Harmer
31.564
316190AA2-174 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.07
3146293MARTNCO
Solar/Wind Harmer
0.107
971563AH1-280 GEN
Solar/Wind Harmer
1.225
970685AG2-442 GEN
Solar/Wind Harmer
8.558
971377AH1-170 GEN
Solar/Wind Harmer
1.2
223401AF1-299 GEN
Solar/Wind Helper
0.698
233915AB1-141 GEN
Solar/Wind Helper
0.486
232428Y3-058 C
Solar/Wind Helper
0.325
233998TM1NIN_3.36
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.487
233950AC2-186 GEN
Solar/Wind Helper
0.111
233972AC1-094 C
Solar/Wind Helper
0.289
3150181POSSMC2
50/50
1.962
3150181POSSMC2
50/50
1.946
3150181POSSMC2
50/50
1.946
972195AH1-682 GEN
50/50
2.894
315673AE1-157 GEN
Solar/Wind Harmer
10.452
3150341NORNECKC1
Adder
1.483
3150341NORNECKC1
Adder
1.471
3150681DARBY 2
Adder
9.716
316033AB2-134 GEN
Solar/Wind Harmer
0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.528
970657AG2-426 GEN
Solar/Wind Harmer
0.949
3145506HICKORY
Solar/Wind Harmer
0.514
3145506HICKORY
Solar/Wind Harmer
0.308
3145506HICKORY
Solar/Wind Harmer
0.077
316339AD2-160 GEN
Solar/Wind Harmer
0.208
3137176SLIGO L2192
Solar/Wind Harmer
0.51
3130086AYDLETT
Solar/Wind Harmer
0.512
3146626S HERTFORD
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
966001AG1-469 GEN
Solar/Wind Harmer
0.073
3151731LOISA B
Adder
8.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.118
3150091POSSM6B
50/50
1.444
970317AG2-208 GEN
Solar/Wind Harmer
5.884
966871AG1-558 GEN
Solar/Wind Harmer
0.16
3142296MT RD221
Adder
0.436
3150671DARBY 1
Adder
9.705
971223AH1-071 GEN
Solar/Wind Harmer
1.411
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.024
3150991CHESPKB
Adder
1.352
3150991CHESPKB
Adder
1.319
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3151721LOISA A
Adder
8.035
972187AH1-678 GEN
Adder
3.484
316065AD1-022 GEN
Solar/Wind Harmer
5.575
3145893MURPHYS
Solar/Wind Harmer
0.807
3145893MURPHYS
Solar/Wind Harmer
0.217
316426AA2-053 GEN
Solar/Wind Harmer
0.398
966811AG1-552 GEN
Solar/Wind Harmer
1.276
971741AH1-377 GEN
Solar/Wind Harmer
11.611
3146776BUCKING
Solar/Wind Harmer
0.462
3146776BUCKING
Solar/Wind Harmer
0.037
939181AE1-148 GEN
Solar/Wind Harmer
5.453
971489AH1-241 GEN
Solar/Wind Harmer
6.002
226929AD2-058 GEN
Solar/Wind Helper
0.401
233987AB2-037 GEN
Solar/Wind Helper
2.251
234036AF2-325 C
Solar/Wind Helper
0.04
233901CHERRYDALE C
Solar/Wind Helper
0.223
3150071POSSM 5
50/50
88.927
3150391LDYSMT3
50/50
22.026
316468AD1-105 GEN
Solar/Wind Harmer
-0.047
316077AC2-138 C
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.037
3143526WINTERP
Solar/Wind Harmer
0.692
944641AF1-129 GEN
Adder
63.136
315697AD1-025 GEN
Solar/Wind Harmer
0.148
316316AC1-027 C
Solar/Wind Harmer
0.124
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3144356SAPONY
Solar/Wind Harmer
1.05
972185AH1-677 GEN
Adder
6.905
970099AG2-077 GEN
Solar/Wind Harmer
12.626
3145783HORNRTN
Solar/Wind Harmer
2.085
3145783HORNRTN
Solar/Wind Harmer
1.668
3145783HORNRTN
Solar/Wind Harmer
0.521
3145783HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.351
963191AG1-168 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.308
316034AC1-036 C
Solar/Wind Harmer
0.008
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.546
232408W1-005 C
Solar/Wind Helper
0.487
232410W1-006 C
Solar/Wind Helper
0.487
233939AC1-091 C
Solar/Wind Helper
0.335
972223AH1-696 GEN
50/50
15.369
3141346CRANES
50/50
0.214
972219AH1-694 GEN
50/50
2.481
3150351NORNECKC2
Adder
1.412
944631AF1-128 GEN
Adder
63.967
3143526WINTERP
Solar/Wind Harmer
0.692
971317AH1-138 GEN
Solar/Wind Harmer
0.993
315671AE2-027_GEN
Solar/Wind Harmer
8.445
944591AF1-124 GEN
Solar/Wind Harmer
29.132
316072AD1-144
Solar/Wind Harmer
0.047
939411AE1-173 GEN
Solar/Wind Harmer
54.47
940641AE2-051 GEN
Solar/Wind Harmer
10.185
3143336POWHATN
Solar/Wind Harmer
2.23
971685AH1-345 GEN
Solar/Wind Harmer
0.923
971547AH1-271 GEN
Solar/Wind Harmer
2.578
960081AF2-299 GEN
Solar/Wind Harmer
1.144
3145823KELFORD
Solar/Wind Harmer
0.118
962571AG1-106 GEN
Solar/Wind Harmer
1.679
3145783HORNRTN
Solar/Wind Harmer
0.117
3145796HORNRTN
Solar/Wind Harmer
0.386
3145796HORNRTN
Solar/Wind Harmer
0.117
316212AC1-099_GEN
Solar/Wind Harmer
0.599
316322AB2-045
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
4.897
972277AH1-723 GEN
Adder
68.708
316129AC1-054 GEN
Solar/Wind Harmer
0.433
3144293JTRSVLE
Adder
0.366
971065AG2-659 GEN
Solar/Wind Harmer
4.897
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
3147623JAMES R
Solar/Wind Harmer
0.261
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.223
3150011OMF A
50/50
0.313
972197AH1-683 GEN
50/50
3.446
972135AH1-637 GEN
Solar/Wind Harmer
1.281
966881AG1-559 GEN
Solar/Wind Harmer
0.172
3141766HARMONY
Solar/Wind Harmer
0.027
3142416OLDCHRC
Solar/Wind Harmer
0.355
3142416OLDCHRC
Solar/Wind Harmer
0.136
971777AH1-397 GEN
Solar/Wind Harmer
0.36
3142433PROV 92
Solar/Wind Harmer
0.542
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
316192AB2-158 GEN
Solar/Wind Harmer
0.74
3145336SMITFLD
Solar/Wind Harmer
0.52
316294AC1-161 GEN
Solar/Wind Harmer
2.247
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.128
316336AC2-165 C
Solar/Wind Harmer
0.005
315683AE1-153 C
Solar/Wind Harmer
9.818
3145663CRESWEL
Solar/Wind Harmer
0.344
3150221REMNGT2
Adder
15.477
3150211REMNGT1
Adder
15.375
972201AH1-685 GEN
Adder
2.67
3146206CASHIE
Solar/Wind Harmer
0.121
316023GEN1_S
Solar/Wind Harmer
0.271
3146173TUNIS
Solar/Wind Harmer
0.12
3145683EARLEYS
Solar/Wind Harmer
0.119
970937AG2-583 GEN
Solar/Wind Harmer
7.301
971795AH1-408 GEN
Solar/Wind Harmer
7.87
3147043LAWRENC
Adder
1.063
315722AD1-056 GEN
Solar/Wind Harmer
0.721
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.037
232434Z2-077 GEN
Solar/Wind Helper
0.122
970053AG2-049 GEN
50/50
2.771
3150381LDYSMT2
50/50
21.185
963051AG1-154 GEN
50/50
2.757
3141783LANCAST
Solar/Wind Harmer
0.083
3141783LANCAST
Solar/Wind Harmer
0.055
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
315976AC1-164 GENA
Solar/Wind Harmer
14.027
316169AC1-164_GENC
Solar/Wind Harmer
12.118
315975AC1-164 GENB
Solar/Wind Harmer
0.415
3151201GRAVEL4
Adder
9.516
3151211GRAVEL5
Adder
9.395
316349AD2-085 GEN
Solar/Wind Harmer
0.088
316311AC2-079 GEN
Solar/Wind Harmer
3.686
315835AF2-110_GEN
Solar/Wind Harmer
0.877
313526AB2-022
Solar/Wind Harmer
0.069
3146396TANGLEW
Solar/Wind Harmer
0.35
315814AE2-033 C
Solar/Wind Harmer
9.914
3146206CASHIE
Solar/Wind Harmer
0.121
3145683EARLEYS
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.119
3145683EARLEYS
Solar/Wind Harmer
0.119
3146043SEABORD
Solar/Wind Harmer
0.119
970285AG2-188 GEN
Solar/Wind Harmer
9.159
971845AH1-439 GEN
Solar/Wind Harmer
5.245
961791AG1-021 GEN
Solar/Wind Harmer
1.103
316420AA1-050 GEN
Solar/Wind Harmer
0.004
232432Z2-076 GEN
Solar/Wind Helper
0.064
234033AF1-007_GEN
Solar/Wind Helper
6.733
3150151POSSMC1
50/50
1.946
316337AD2-073 GEN
Solar/Wind Harmer
0.125
3141726DUNNSVL
Solar/Wind Harmer
0.564
962861AG1-135 GEN
Solar/Wind Harmer
4.477
316045AC1-158 PL2
Solar/Wind Harmer
2.091
3150851SPRUNCC
Adder
0.616
970659AG2-427 GEN
Solar/Wind Harmer
6.262
316093AE2-104_GEN
Solar/Wind Harmer
2.148
3146516WINFALL
Solar/Wind Harmer
0.409
3146516WINFALL
Solar/Wind Harmer
0.126
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316006AB2-029 C
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.482
3145893MURPHYS
Solar/Wind Harmer
0.536
970919AG2-571 GEN
Solar/Wind Harmer
4.269
3146263WOODLND
Solar/Wind Harmer
0.119
3145963POPLR C
Solar/Wind Harmer
0.118
316011AB1-132 GEN
Solar/Wind Harmer
2.146
315693AD1-088 GEN
Solar/Wind Harmer
5.655
316174AB2-169 GEN
Solar/Wind Harmer
0.003
962491AG1-098 GEN
Solar/Wind Harmer
6.721
3146776BUCKING
Solar/Wind Harmer
0.046
963171AG1-166 GEN
Solar/Wind Harmer
0.613
316494AC1-189 GEN
Solar/Wind Harmer
0.383
3150411LDYSMT5
50/50
22.136
3141426STAFORD
Solar/Wind Harmer
0.039
970327AG2-215 GEN
Solar/Wind Harmer
4.571
3141913WHIT STONE
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Harmer
0.244
971285AH1-108 GEN
Adder
1.008
971445AH1-216 GEN
Solar/Wind Harmer
9.164
3151081ELIZAR1
Adder
11.83
3151091ELIZAR2
Adder
11.624
3152611GOSPORTB
Adder
1.643
3152621GOSPORTC
Adder
1.395
3152601GOSPORTA
Adder
1.287
315833AF1-017_GEN
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
6.385
316315AB2-025 C
Solar/Wind Harmer
0.101
941031AE2-094 GEN
Solar/Wind Harmer
22.955
970673AG2-436 GEN
Solar/Wind Harmer
26.361
970673AG2-436 GEN
Solar/Wind Harmer
17.574
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.047
970831AG2-522 GEN
Solar/Wind Harmer
4.918
970683AG2-441 GEN
Solar/Wind Harmer
7.642
970681AG2-440 GEN
Solar/Wind Harmer
6.113
3145746EVERETS
Solar/Wind Harmer
0.455
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
3145593CAROLNA
Solar/Wind Harmer
0.118
3145593CAROLNA
Solar/Wind Harmer
0.146
970301AG2-198 GEN
Solar/Wind Harmer
4.984
3145933PARMELE
Solar/Wind Harmer
0.231
3145933PARMELE
Solar/Wind Harmer
0.115
970323AG2-213 GEN
Solar/Wind Harmer
4.879
971775AH1-396 GEN
Solar/Wind Harmer
0.183
313527AB2-043 GEN
Solar/Wind Harmer
0.001
208835TUHI V3-051
Solar/Wind Helper
0.03
208835TUHI V3-051
Solar/Wind Helper
0.03
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.335
972213AH1-691 GEN
50/50
3.584
944491AF1-114 GEN
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
2.375
3138133OCRAN
Solar/Wind Harmer
0.041
3141873WAN 176
Solar/Wind Harmer
0.027
315662AE1-191 GEN
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.082
971281AH1-106 GEN
Solar/Wind Harmer
1.847
316369SG1_INVT
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Harmer
0.514
319010AE1-072 C
Solar/Wind Harmer
0.645
3146486SUNBURY
Solar/Wind Harmer
0.127
3146486SUNBURY
Solar/Wind Harmer
0.127
316321Z2-027
Solar/Wind Harmer
0.024
3145176PASQUOTANK
Solar/Wind Harmer
0.079
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.124
3130156CHOWAN
Solar/Wind Harmer
0.124
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3147346CASHSCORNER
Solar/Wind Harmer
0.285
3130546PLYMOUTH
Solar/Wind Harmer
0.122
315733AD1-074 GEN2
Solar/Wind Harmer
0.698
970601AG2-382 GEN
Solar/Wind Harmer
4.511
970581AG2-369 GEN
Solar/Wind Harmer
5.496
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3146033SCOT NK
Solar/Wind Harmer
0.467
972205AH1-687 GEN
Adder
4.919
970181AG2-120 GEN
Solar/Wind Harmer
1.422
233990AG1-397 GEN
Solar/Wind Helper
0.259
972215AH1-692 GEN
50/50
3.584
316223AC1-118
Solar/Wind Harmer
0.105
3141813NORNECK
Solar/Wind Harmer
0.141
962981AG1-147 GEN
Solar/Wind Harmer
5.181
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.04
971167AH1-042 GEN
Solar/Wind Harmer
12.03
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316233AE1-074 FULL
Solar/Wind Harmer
0.107
971283AH1-107 GEN
Solar/Wind Harmer
1.847
316164AC1-076 GEN
Solar/Wind Harmer
0.186
316132AB2-190 GEN1
Solar/Wind Harmer
0.709
972265AH1-717 GEN
Adder
10.151
3151191GRAVEL3
Adder
9.395
316305AF2-043 C
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.016
944011AF1-069 GEN
Solar/Wind Harmer
7.5
971967AH1-528 GEN
Solar/Wind Harmer
19.675
315732AD1-074 GEN1
Solar/Wind Harmer
0.698
315735AD1-075 GEN1
Solar/Wind Harmer
0.35
965291AG1-394 GEN
Solar/Wind Harmer
0.539
3145893MURPHYS
Solar/Wind Harmer
0.326
3145893MURPHYS
Solar/Wind Harmer
0.121
970085AG2-068 GEN
Solar/Wind Harmer
6.391
3145513AHOSKIE
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
0.12
315607AA1-063A GEN
Solar/Wind Harmer
0.243
315652AC1-086 GEN
Solar/Wind Harmer
12.981
3137643SOCKMAN
Solar/Wind Harmer
0.471
972193AH1-681 GEN
Adder
2.634
315657AE1-056 GEN
Solar/Wind Harmer
3.968
946301AF1-294 GEN
Solar/Wind Harmer
2.267
3144303KENBRDG
Solar/Wind Harmer
0.091
971443AH1-215 GEN
Solar/Wind Harmer
1.921
316005AA1-067
Solar/Wind Harmer
0.123
233935AB2-179 C
Solar/Wind Helper
1.237
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.92
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
4.883
3150081POSSM6A
50/50
1.444
3141316ARNOLDS
50/50
0.404
3150351NORNECKC2
Adder
1.435
3144216WINCHST
Adder
0.497
315778AD1-151 GEN
Solar/Wind Harmer
10.543
315839AE2-212 C
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
11.981
944601AF1-125 GEN
Solar/Wind Harmer
28.582
316258AE1-075 C
Solar/Wind Harmer
0.095
3143336POWHATN
Solar/Wind Harmer
1.895
3151761LOISA E
Adder
16.466
3150021OMF B
50/50
0.313
3150371LDYSMT1
50/50
21.323
970497AG2-320 GEN
50/50
14.416
971781AH1-399 GEN
Solar/Wind Harmer
0.191
970009AG2-005 GEN
Solar/Wind Harmer
1.04
316473AC1-191 GEN
Solar/Wind Harmer
0.469
3141766HARMONY
Solar/Wind Harmer
1.82
3142416OLDCHRC
Solar/Wind Harmer
1.322
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.273
3151221GRAVEL6
Adder
9.505
3145336SMITFLD
Solar/Wind Harmer
0.052
315813AE1-149 C
Solar/Wind Harmer
6.935
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.128
971153AH1-033 GEN
Solar/Wind Harmer
1.481
3145273HOLLAND
Solar/Wind Harmer
0.094
3146376EDENTON
Solar/Wind Harmer
0.124
3150231REMNGT3
Adder
16.71
3150241REMNGT4
Adder
15.58
972199AH1-684 GEN
Adder
2.362
3146206CASHIE
Solar/Wind Harmer
0.121
316365GEN2_N
Solar/Wind Harmer
0.271
3146173TUNIS
Solar/Wind Harmer
0.12
3156021HOLLOMANSOL
Solar/Wind Harmer
0.544
3147043LAWRENC
Solar/Wind Harmer
0.071
316478AD1-087 GEN
Solar/Wind Harmer
0.406
316486AD2-202 GEN
Solar/Wind Harmer
0.119
972255AH1-712 GEN
Adder
58.961
3147133PAMPLIN
Solar/Wind Harmer
0.361
959311AF2-222 GEN
Solar/Wind Harmer
10.172
315724AD1-057 GEN
Solar/Wind Harmer
0.428
316131AB2-060 GEN
Solar/Wind Harmer
0.358
227287AC2-120 GEN
Solar/Wind Helper
1.283
233996TM1833_GEN
Solar/Wind Helper
0.251
232406W1-004 FULL
Solar/Wind Helper
0.487
957191AF2-013 GEN
50/50
14.065
957411AF2-035 GEN
Solar/Wind Harmer
6.351
958261AF2-120 GEN
Solar/Wind Harmer
4.633
3150691DARBY 3
Adder
9.75
3150701DARBY 4
Adder
9.728
3142366NRTHEST
Adder
0.443
3142946ENON
Solar/Wind Harmer
0.013
316447AC1-158 HLD
Solar/Wind Harmer
1.437
316017AA1-139 ULT1
Solar/Wind Harmer
0.072
3146456SLIGO L269
Solar/Wind Harmer
2.267
315651AD1-115 GEN
Solar/Wind Harmer
0.004
3146386ELIZ CT
Solar/Wind Harmer
0.127
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.553
3146376EDENTON
Solar/Wind Harmer
0.553
970933AG2-581 GEN
Solar/Wind Harmer
9.737
3146173TUNIS
Solar/Wind Harmer
0.12
3146173TUNIS
Solar/Wind Harmer
0.12
316181AB2-040 GEN
Solar/Wind Harmer
0.172
316274AC1-208 GEN
Solar/Wind Harmer
0.598
3147133PAMPLIN
Solar/Wind Harmer
0.115
3147133PAMPLIN
Solar/Wind Harmer
0.092
958211AF2-115 GEN
Solar/Wind Harmer
1.378
3150101POSSM6S
50/50
2.207
3150401LDYSMT4
50/50
22.067
3141906WESTMOR
Solar/Wind Harmer
0.059
316404AE1-155 C
Solar/Wind Harmer
0.032
962971AG1-146 GEN
Solar/Wind Harmer
2.22
3141873WAN 176
Solar/Wind Harmer
2.426
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141843SHACKLE
Adder
0.697
3143096IRON208
Adder
0.563
3143096IRON208
Adder
0.552
316044AC1-158 PL1
Solar/Wind Harmer
0.654
316450AC1-158 RIC
Solar/Wind Harmer
0.174
3150861SPRUNCD
Adder
0.616
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.987
965281AG1-393 GEN
Solar/Wind Harmer
1.404
3147666LOUISA
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
3.495
3151171GRAVELC
Adder
1.829
970661AG2-428 GEN
Solar/Wind Harmer
2.731
3144873MCLAUGH
Solar/Wind Harmer
0.003
3146626S HERTFORD
Solar/Wind Harmer
0.126
316405AF2-144 C
Solar/Wind Harmer
0.001
3150301M RUN C
Adder
16.643
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
315737AD1-076 GEN
Solar/Wind Harmer
1.564
961681AG1-008 GEN
Solar/Wind Harmer
8.962
970917AG2-570 GEN
Solar/Wind Harmer
10.673
962331AG1-082 GEN
Solar/Wind Harmer
1.276
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3146926FARMVIL
Solar/Wind Harmer
0.07
3145933PARMELE
Solar/Wind Harmer
0.115
966801AG1-551 GEN
Solar/Wind Harmer
1.346
963181AG1-167 GEN
Solar/Wind Harmer
0.459
970257AG2-171 GEN
Solar/Wind Harmer
3.659
315785AD2-033 C
Solar/Wind Harmer
0.929
234015AF2-250 C
Solar/Wind Helper
0.036
3150151POSSMC1
50/50
1.946
3150151POSSMC1
50/50
1.946
3150331BIRCHWDA
50/50
29.368
970737AG2-469 GEN
Solar/Wind Harmer
6.342
316156AD2-030 GEN
Solar/Wind Harmer
0.101
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.446
3150921YORKTN3
Adder
3.319
315773AC2-141 GEN
Solar/Wind Harmer
4.737
970659AG2-427 GEN
Solar/Wind Harmer
1.37
3144536CHRHLND
Solar/Wind Harmer
0.019
944581AF1-123 GEN
Solar/Wind Harmer
29.029
316170AC1-121 GEN2
Solar/Wind Harmer
0.137
316320Y1-086
Solar/Wind Harmer
0.001
3132273ORANGE
Solar/Wind Harmer
0.025
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
316313AB2-026
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.703
3150291M RUN B
Adder
16.52
971157AH1-035 GEN
Solar/Wind Harmer
1.461
3145893MURPHYS
Solar/Wind Harmer
0.202
3145893MURPHYS
Solar/Wind Harmer
0.121
957521AF2-046 GEN
Solar/Wind Harmer
8.962
316463AE2-346 GEN
Solar/Wind Harmer
0.103
316140AB2-099
Solar/Wind Harmer
0.043
3146263WOODLND
Solar/Wind Harmer
0.119
3145963POPLR C
Solar/Wind Harmer
0.118
3146776BUCKING
Solar/Wind Harmer
0.042
316327AA2-057 GEN
Solar/Wind Harmer
0.171
970221AG2-151 GEN
Solar/Wind Harmer
6.002
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.923
233997TMININ_4.2
Solar/Wind Helper
0.251
233971AC1-093 C
Solar/Wind Helper
0.342
972183AH1-676 GEN
Adder
132.605
972217AH1-693 GEN
Adder
2.054
3141196NOKESVL
Solar/Wind Harmer
0.475
316317KELFORD C
Solar/Wind Harmer
0.011
3145823KELFORD
Solar/Wind Harmer
0.118
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.117
970909AG2-566 GEN
Solar/Wind Harmer
1.246
316210AC1-098 GEN
Solar/Wind Harmer
1.074
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
971193AH1-056 GEN
Solar/Wind Harmer
7.005
3144293JTRSVLE
Adder
0.366
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
964241AG1-285 GEN
Solar/Wind Harmer
7.598
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.698
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.223
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.907
WECLTFEXP_WEC->PJM
CLTF
1.706
LAGNLTFEXP_LAGN->PJM
CLTF
10.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.366
NYPJM->LTFIMP_NY
CLTF
3.769
TVALTFEXP_TVA->PJM
CLTF
5.449
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.705
CPLELTFEXP_CPLE->PJM
CLTF
8.254
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.489
LGEELTFEXP_LGEE->PJM
CLTF
3.18
MECLTFEXP_MEC->PJM
CLTF
7.822
AH1-155LTFEXP_AH1-155->PJM
LTF
0.152

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o PEPCO_P4_PP41_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3214.41
MW Contribution:15.44
Bus #Bus NameTypeMW Contribution
972213AH1-691 GEN
50/50
3.604
944491AF1-114 GEN
Solar/Wind Harmer
5.033
972189AH1-679 GEN
Adder
2.389
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.859
3143873LANEXA
Solar/Wind Harmer
-0.009
971281AH1-106 GEN
Solar/Wind Harmer
2.447
316369SG1_INVT
Solar/Wind Harmer
2.658
3143316POE
Solar/Wind Harmer
-0.058
319010AE1-072 C
Solar/Wind Harmer
2.929
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
315611Z1-036_GEN2
Solar/Wind Harmer
3.502
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.78
970601AG2-382 GEN
Solar/Wind Harmer
5.979
970581AG2-369 GEN
Solar/Wind Harmer
7.285
946281AF1-292 GEN
Solar/Wind Harmer
0.302
316087AB2-174 GEN
Solar/Wind Harmer
1.915
972205AH1-687 GEN
Adder
4.954
233990AG1-397 GEN
Solar/Wind Helper
0.03
972223AH1-696 GEN
50/50
15.444
3141346CRANES
50/50
0.215
972219AH1-694 GEN
50/50
2.495
3150351NORNECKC2
Adder
1.42
964211AG1-282 GEN
Solar/Wind Harmer
0.479
944631AF1-128 GEN
Adder
64.371
3143526WINTERP
Solar/Wind Harmer
-0.078
3150071POSSM 5
50/50
89.359
3150391LDYSMT3
50/50
22.151
316468AD1-105 GEN
Solar/Wind Harmer
1.834
316077AC2-138 C
Solar/Wind Harmer
0.338
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.538
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316316AC1-027 C
Solar/Wind Harmer
0.447
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3144356SAPONY
Solar/Wind Harmer
0.495
972185AH1-677 GEN
Adder
6.951
970099AG2-077 GEN
Solar/Wind Harmer
16.736
3150411LDYSMT5
50/50
22.262
972215AH1-692 GEN
50/50
3.604
316223AC1-118
Solar/Wind Harmer
0.446
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.863
957601AF2-054 GEN
Solar/Wind Harmer
0.462
315666AE1-190 GEN
Solar/Wind Harmer
0.465
971167AH1-042 GEN
Solar/Wind Harmer
14.742
3138283WHITEMARSH
Solar/Wind Harmer
0.023
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
972265AH1-717 GEN
Adder
10.216
3151191GRAVEL3
Adder
9.455
316305AF2-043 C
Solar/Wind Harmer
0.436
3146406KITTY HAWK
Solar/Wind Harmer
0.012
944011AF1-069 GEN
Solar/Wind Harmer
8.281
971967AH1-528 GEN
Solar/Wind Harmer
26.146
315732AD1-074 GEN1
Solar/Wind Harmer
2.78
315735AD1-075 GEN1
Solar/Wind Harmer
1.39
965291AG1-394 GEN
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
-0.037
970053AG2-049 GEN
50/50
2.789
3150381LDYSMT2
50/50
21.306
963051AG1-154 GEN
50/50
2.772
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.349
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
315976AC1-164 GENA
Solar/Wind Harmer
16.161
316169AC1-164_GENC
Solar/Wind Harmer
13.961
315975AC1-164 GENB
Solar/Wind Harmer
0.478
3151201GRAVEL4
Adder
9.577
3151211GRAVEL5
Adder
9.455
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146396TANGLEW
Solar/Wind Harmer
0.264
315814AE2-033 C
Solar/Wind Harmer
13.198
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.34
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.824
3150151POSSMC1
50/50
1.955
3150151POSSMC1
50/50
1.955
3150331BIRCHWDA
50/50
29.526
970737AG2-469 GEN
Solar/Wind Harmer
8.399
316484AD2-074 GEN
Solar/Wind Harmer
3.964
316156AD2-030 GEN
Solar/Wind Harmer
0.412
316203AE2-005 GEN
Solar/Wind Harmer
6.499
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3150921YORKTN3
Adder
3.34
315773AC2-141 GEN
Solar/Wind Harmer
6.136
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
944581AF1-123 GEN
Solar/Wind Harmer
66.322
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.383
3150291M RUN B
Adder
16.656
315614AA2-178 GEN
Solar/Wind Harmer
1.5
971157AH1-035 GEN
Solar/Wind Harmer
1.721
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
957521AF2-046 GEN
Solar/Wind Harmer
10.729
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.935
233997TMININ_4.2
Solar/Wind Helper
0.254
233971AC1-093 C
Solar/Wind Helper
0.347
3150091POSSM6B
50/50
1.451
970317AG2-208 GEN
Solar/Wind Harmer
7.36
966871AG1-558 GEN
Solar/Wind Harmer
0.471
3150011OMF A
50/50
0.315
972197AH1-683 GEN
50/50
3.465
972135AH1-637 GEN
Solar/Wind Harmer
1.697
966881AG1-559 GEN
Solar/Wind Harmer
0.173
961951AG1-038 GEN
Solar/Wind Harmer
2.074
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3146456SLIGO L269
Solar/Wind Harmer
-0.014
315683AE1-153 C
Solar/Wind Harmer
13.027
316336AC2-165 C
Solar/Wind Harmer
2.43
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.606
3150211REMNGT1
Adder
15.502
972201AH1-685 GEN
Adder
2.692
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.92
3146173TUNIS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.013
970937AG2-583 GEN
Solar/Wind Harmer
9.68
3147043LAWRENC
Adder
1.071
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232434Z2-077 GEN
Solar/Wind Helper
0.123
957191AF2-013 GEN
50/50
14.143
957411AF2-035 GEN
Solar/Wind Harmer
7.57
958261AF2-120 GEN
Solar/Wind Harmer
6.138
316487AF1-042 GEN
Solar/Wind Harmer
2.074
3150691DARBY 3
Adder
9.812
3150701DARBY 4
Adder
9.789
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.278
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3146456SLIGO L269
Solar/Wind Harmer
1.711
315651AD1-115 GEN
Solar/Wind Harmer
6.346
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
315742AE1-103 GEN
Solar/Wind Harmer
1.477
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
970933AG2-581 GEN
Solar/Wind Harmer
12.906
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.869
3150181POSSMC2
50/50
1.972
3150181POSSMC2
50/50
1.955
3150181POSSMC2
50/50
1.955
972195AH1-682 GEN
50/50
2.911
315673AE1-157 GEN
Solar/Wind Harmer
12.809
3150341NORNECKC1
Adder
1.492
3150341NORNECKC1
Adder
1.48
3150681DARBY 2
Adder
9.777
316033AB2-134 GEN
Solar/Wind Harmer
4.798
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
232424Y1-079 C
Solar/Wind Helper
0.114
233970AC1-092 C
Solar/Wind Helper
0.339
3140676OCCOQUN
50/50
0.417
957971AF2-091 GEN
Solar/Wind Harmer
1.711
3138133OCRAN
Solar/Wind Harmer
-0.009
3141843SHACKLE
Adder
0.701
3143096IRON208
Adder
0.567
3142543TWELFTH
Solar/Wind Harmer
-0.001
316159AE1-175 C
Solar/Wind Harmer
0.404
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.408
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
3151171GRAVELC
Adder
1.4
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
3150981CHESPKA
Adder
1.622
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
316246AF1-032 C
Solar/Wind Harmer
0.293
3151751LOISA D
Adder
8.136
3130156CHOWAN
Solar/Wind Harmer
-0.014
3150281M RUN A
Adder
16.791
971163AH1-040 GEN
Solar/Wind Harmer
13.033
970087AG2-069 GEN
Solar/Wind Harmer
12.706
957481AF2-042 GEN
Solar/Wind Harmer
41.84
223401AF1-299 GEN
Solar/Wind Helper
0.699
233915AB1-141 GEN
Solar/Wind Helper
0.492
232428Y3-058 C
Solar/Wind Helper
0.329
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
3150101POSSM6S
50/50
2.218
3150401LDYSMT4
50/50
22.193
3141906WESTMOR
Solar/Wind Harmer
-0.007
316404AE1-155 C
Solar/Wind Harmer
3.056
962971AG1-146 GEN
Solar/Wind Harmer
2.941
3141873WAN 176
Solar/Wind Harmer
1.831
316280AD1-041 GEN
Solar/Wind Harmer
1.162
3141843SHACKLE
Adder
0.701
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970129AG2-093 GEN
Solar/Wind Harmer
8.413
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151171GRAVELC
Adder
1.84
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.014
316405AF2-144 C
Solar/Wind Harmer
0.363
3150301M RUN C
Adder
16.781
3156081AA2-088 GEN
Solar/Wind Harmer
4.463
315737AD1-076 GEN
Solar/Wind Harmer
2.612
961681AG1-008 GEN
Solar/Wind Harmer
10.729
970917AG2-570 GEN
Solar/Wind Harmer
33.953
962331AG1-082 GEN
Solar/Wind Harmer
1.692
313506AB2-031 GEN
Solar/Wind Harmer
1.077
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
234015AF2-250 C
Solar/Wind Helper
0.037
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
3150671DARBY 1
Adder
9.766
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3150991CHESPKB
Adder
1.328
3142956BIRDNECK
Solar/Wind Harmer
0.782
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3151721LOISA A
Adder
8.094
972187AH1-678 GEN
Adder
3.507
316065AD1-022 GEN
Solar/Wind Harmer
6.847
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
226929AD2-058 GEN
Solar/Wind Helper
0.4
233987AB2-037 GEN
Solar/Wind Helper
2.282
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.226
3150151POSSMC1
50/50
1.955
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.93
316045AC1-158 PL2
Solar/Wind Harmer
4.768
3150851SPRUNCC
Adder
0.62
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316093AE2-104_GEN
Solar/Wind Harmer
4.2
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
315800Z1-036_GEN1
Solar/Wind Harmer
3.502
316006AB2-029 C
Solar/Wind Harmer
0.804
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
970919AG2-571 GEN
Solar/Wind Harmer
4.298
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.794
3145893MURPHYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.471
3145513AHOSKIE
Solar/Wind Harmer
0.118
3145513AHOSKIE
Solar/Wind Harmer
-0.013
315607AA1-063A GEN
Solar/Wind Harmer
1.361
972193AH1-681 GEN
Adder
2.653
233935AB2-179 C
Solar/Wind Helper
1.253
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.932
315652AC1-086 GEN
Solar/Wind Harmer
5.136
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
233933AB2-153 GEN
Solar/Wind Helper
0.228
233944AB2-135 GEN
Solar/Wind Helper
0.576
233946AB2-136 GEN
Solar/Wind Helper
0.553
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
971317AH1-138 GEN
Solar/Wind Harmer
1.879
315671AE2-027_GEN
Solar/Wind Harmer
11.19
944591AF1-124 GEN
Solar/Wind Harmer
66.561
316072AD1-144
Solar/Wind Harmer
0.295
939411AE1-173 GEN
Solar/Wind Harmer
72.185
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3143336POWHATN
Solar/Wind Harmer
1.683
971685AH1-345 GEN
Solar/Wind Harmer
1.225
971547AH1-271 GEN
Solar/Wind Harmer
3.417
960081AF2-299 GEN
Solar/Wind Harmer
1.517
3145823KELFORD
Solar/Wind Harmer
-0.013
972277AH1-723 GEN
Adder
69.197
3144293JTRSVLE
Adder
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.373
233954AC2-188 GEN
Solar/Wind Helper
0.226
3141426STAFORD
Solar/Wind Harmer
-0.004
3141913WHIT STONE
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
1.319
316312AB1-027
Solar/Wind Harmer
0.52
957831AF2-077 GEN
Solar/Wind Harmer
0.456
971285AH1-108 GEN
Adder
1.015
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.699
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
957871AF2-081 GEN
Solar/Wind Harmer
7.252
316315AB2-025 C
Solar/Wind Harmer
0.383
941031AE2-094 GEN
Solar/Wind Harmer
26.429
970673AG2-436 GEN
Solar/Wind Harmer
29.36
970673AG2-436 GEN
Solar/Wind Harmer
14.866
3150081POSSM6A
50/50
1.451
3141316ARNOLDS
50/50
0.406
3150351NORNECKC2
Adder
1.444
3144216WINCHST
Adder
0.5
3150021OMF B
50/50
0.315
3150371LDYSMT1
50/50
21.444
970497AG2-320 GEN
50/50
14.499
966881AG1-559 GEN
Solar/Wind Harmer
0.506
971781AH1-399 GEN
Solar/Wind Harmer
1.015
970009AG2-005 GEN
Solar/Wind Harmer
1.968
316473AC1-191 GEN
Solar/Wind Harmer
1.687
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.687
3151221GRAVEL6
Adder
9.566
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.19
316083AB2-161 GEN
Solar/Wind Harmer
2.375
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150231REMNGT3
Adder
16.848
3150241REMNGT4
Adder
15.709
972199AH1-684 GEN
Adder
2.382
3146206CASHIE
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.826
972255AH1-712 GEN
Adder
59.381
227287AC2-120 GEN
Solar/Wind Helper
1.281
233996TM1833_GEN
Solar/Wind Helper
0.254
232406W1-004 FULL
Solar/Wind Helper
0.493
315778AD1-151 GEN
Solar/Wind Harmer
12.909
315839AE2-212 C
Solar/Wind Harmer
0.447
3151101ELIZAR3
Adder
12.058
944601AF1-125 GEN
Solar/Wind Harmer
65.287
316258AE1-075 C
Solar/Wind Harmer
0.344
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.586
972183AH1-676 GEN
Adder
133.578
972217AH1-693 GEN
Adder
2.071
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
316317KELFORD C
Solar/Wind Harmer
0.629
3145823KELFORD
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.368
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.699
233982AB2-133 GEN
Solar/Wind Helper
0.351
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.932
NYPJM->LTFIMP_NY
CLTF
3.816
TVALTFEXP_TVA->PJM
CLTF
5.494
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.074
WECLTFEXP_WEC->PJM
CLTF
1.721
LAGNLTFEXP_LAGN->PJM
CLTF
10.915
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.064
LGEELTFEXP_LGEE->PJM
CLTF
3.208
MECLTFEXP_MEC->PJM
CLTF
7.89
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.861
CPLELTFEXP_CPLE->PJM
CLTF
8.313
SIGELTFEXP_SIGE->PJM
CLTF
0.248
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H2T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313908 TO BUS 314922 CKT 1   /*6POS PT TAP2 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H1T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313058 TO BUS 314922 CKT 1   /*6POSS PT TAP 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 560T571_SRT-S'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1                /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313383 TO BUS 314922 CKT 1                /*8OCCOQUN     500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-406T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P7-1: LN 514-2098_SRT-S'
 OPEN BRANCH FROM BUS 235105 TO BUS 314939 CKT 1                /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 1                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 2                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 314005 CKT 1                /*6BREEZYKNOLL 230.0 - 6HAMLTON     230.0
 OPEN BRANCH FROM BUS 313021 TO BUS 314072 CKT 1                /*6DRYMILLS    230.0 - 6PL VIEW     230.0
 OPEN BUS 313010                                                /*6BREEZYKNOLL 230.0
 OPEN BUS 313021                                                /*6DRYMILLS    230.0
 OPEN BUS 314005                                                /*6HAMLTON     230.0
 SET POSTCONTRATING 1315 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
 SET PRECONTRATING 1219 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
CONTINGENCY 'PEPCO_P4_PP41_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 224058 CKT 1   /*BRIGHTON     500.0 - BRG 3T 230   230.0
 OPEN BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
314290 to 223938 ckt 1
313911 to 314290 ckt 1
314933 to 972284 ckt 1
314922 to 200019 ckt 1

Winter Peak Analysis

The New Service Request AH1-696 was evaluated as a 0.0 MW (94.0 MW Capacity) injection in the Dominion area.

AH1-696 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 668.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-696 was evaluated as a 0.0 MW injection

AH1-696 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 668.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-304Liberty 230 kVActive
AG2-320Ladysmith 230 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-712Cunningham 500 kVActive
AH1-713Mt. Storm 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
AH1-727Brambleton-Goose Creek 500kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-696 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-696 could receive cost allocation. Although AH1-696 may not presently have cost responsibility for this upgrade, AH1-696 is a potential Aggregate Pool Contributor.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AH1-696 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-696 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1
Description
Replaces the terminal equipment at Burches Hill 500 kV station (breakers, switches, and stranded bus) that upgrades the ratings.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-696 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-696 could receive cost allocation. Although AH1-696 may not presently have cost responsibility for this upgrade, AH1-696 is a potential Aggregate Pool Contributor.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AH1-696 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-696 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-696 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-696 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-696 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-696 could receive cost allocation. Although AH1-696 may not presently have cost responsibility for this upgrade, AH1-696 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)

Attachments

AH1-696 One Line Diagram

AH1-696 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.