AH1-704 Phase I Study Report

v1.00 released 2025-10-29 20:51

Hannibal 138 kV

20.0 MW Capacity / 24.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Long Ridge Energy Generation LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the American Electric Power zone — Monroe County, Ohio. This project is an increase to the developer’s AB2-093 project(s), which will share the same Point of Interconnection. The AH1-704 project is a 24.0 MW uprate (20.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 509.0 MW with 505.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-704
Project Name:
Hannibal 138 kV
Project Developer Name:
Long Ridge Energy Generation LLC
State:
Ohio
County:
Monroe
Transmission Owner:
American Electric Power
MFO:
509.0
MWE:
24.0
MWC:
20.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-704 will interconnect on the American Electric Power system at the Hannibal 138 kV Substation. 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-704 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-704Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-704

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-704 Project due at DP1
ABA - B
AH1-704$0$108,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)No interconnections facilities required to support the interconnection$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW (20.0 MW Capacity) injection in the AEP area.

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.272.67
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.932.68
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.472.69
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.472.69
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.982.69
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.263.1
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.62.78
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.522.67
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.22.68
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.692.69
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.692.69
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.282.69
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.983.1
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.332.78

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:2.67
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
11.843
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
270485AE1-090_GEN
Solar/Wind Harmer
0.692
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.759
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270043AE2-236 GEN
Solar/Wind Harmer
5.893
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
24318805MLG1
50/50
10.158
270475AD2-096_GEN
50/50
7.165
253338AC1-165 GEN
Solar/Wind Harmer
1.243
972173AH1-669 GEN
Solar/Wind Harmer
5.679
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
270191TR4_S_V150
Solar/Wind Harmer
3.232
959331AF2-224 GEN
Solar/Wind Harmer
10.775
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
270222AC2-111 GEN
Solar/Wind Harmer
8.657
24642205MAYFLWER
Adder
0.667
274753CRETE EC ;3U
Adder
8.515
972038AH1-567 GEN2
Adder
0.375
238118U2-030_1
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237038AE2-054 C
Solar/Wind Helper
0.273
23779801AA1-109
Solar/Wind Helper
0.194
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.149
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
207445AB1-138_GEN
Solar/Wind Helper
0.105
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
961821AG1-024 GEN
Solar/Wind Harmer
10.408
972239AH1-704 GEN
Adder
2.671
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270269AC2-059
Solar/Wind Harmer
10.62
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
253400AC2-068 GEN
Solar/Wind Harmer
2.18
965041AG1-368 GEN
Solar/Wind Harmer
10.749
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.653
25196508WSDLE4
Adder
9.021
270297AD1-101 GEN
Solar/Wind Harmer
2.953
274776LINCOLN ;7U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274746AC1-111 G10
Adder
5.705
238152AF2-075_GEN
Solar/Wind Helper
0.709
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.644
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
10.252
270156DARBY CT1
Adder
10.432
270119AB2-067 GEN1
50/50
7.1
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
270518AE2-148 GEN
Solar/Wind Harmer
13.911
972159AH1-661 GEN
Adder
1.111
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
274695ROCKY RD ;2P
Adder
11.323
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.35
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.327
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970077AG2-063 GEN
Solar/Wind Harmer
6.25
253378AE2-206_GEN
Solar/Wind Harmer
4.016
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
970879AG2-548 GEN
Solar/Wind Harmer
6.788
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
970611AG2-400 GEN
Solar/Wind Harmer
10.775
270007AE1-245 C
Solar/Wind Harmer
6.374
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
942221AE2-234 GEN
Solar/Wind Harmer
0.781
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
972259AH1-714 GEN
Adder
19.596
274696ROCKY RD ;4P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.076
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
4.981
270044AE2-322 C
Solar/Wind Harmer
1.394
25196008MFTGT1
Adder
1.411
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
274800UNIV PARK;3U
Adder
5.993
274729ELWOOD EC;1P
Adder
16.844
237048AF1-022 C
Solar/Wind Helper
0.179
233930AB2-032 GEN
Solar/Wind Helper
0.382
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.231
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
270157DARBY CT2
Adder
10.407
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
970879AG2-548 GEN
Solar/Wind Harmer
4.736
270435AC2-044 GEN
Solar/Wind Harmer
2.165
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
971567AH1-282 GEN
Solar/Wind Harmer
16.053
270071AF1-092 GEN
Solar/Wind Harmer
16.048
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
270543AE2-219 C
Solar/Wind Harmer
5.445
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274728ELWOOD EC;5P
Adder
16.844
238126S14_GEN_1
Solar/Wind Helper
0.832
237085AD2-009_GEN
Solar/Wind Helper
1.655
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.786
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
276820AF1-078_GEN
Solar/Wind Harmer
1.784
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.528
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
970153AG2-106 GEN
Solar/Wind Harmer
17.953
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
253303V4-073 C
Solar/Wind Harmer
0.127
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270302AB2-170 GEN
Solar/Wind Harmer
9.566
970179AG2-119 GEN
Solar/Wind Harmer
8.844
253372AE2-315 SEC3
Adder
2.071
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270588AE1-091_GEN
Solar/Wind Harmer
11.804
25194608D.CRK4
Adder
1.747
24728505AND G1
Adder
3.945
274676JOLIET 29;8U
Adder
30.322
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
237080AD1-060 GEN
Solar/Wind Helper
0.343
966131AG1-482 GEN
Solar/Wind Helper
0.078
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
217208PARK ELE C
Solar/Wind Helper
0.004
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
957201AF2-014 GEN
Solar/Wind Harmer
4.91
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270024AE2-089 GEN
Solar/Wind Harmer
5.004
252524AE2-267 GEN
Solar/Wind Harmer
1.677
274811UNIV PK N;7U
Adder
5.162
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274735ELWOOD EC;4P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.359
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.511
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
203975AE1-071-GEN
Solar/Wind Helper
2.508
966261AG1-495 GEN
Solar/Wind Helper
0.082
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.1
270224U2-072_GEN2
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.626
960971AF2-388 GEN
Solar/Wind Harmer
11.659
970883AG2-550 GEN
Solar/Wind Harmer
10.634
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.981
274803UNIV PARK;6U
Adder
5.997
274674JOLIET 9 ;6U
Adder
15.776
274693ROCKY RD ;1P
Adder
11.211
23559001PLEAS1
50/50
6.365
961921AG1-034 GEN
Solar/Wind Harmer
15.612
942051AE2-217 GEN
Solar/Wind Harmer
21.08
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270273AD2-016 GEN
Solar/Wind Harmer
3.037
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
957541AF2-048 GEN
Solar/Wind Harmer
1.724
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270247TR4_N_V136
Solar/Wind Harmer
0.916
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
944531AF1-118 GEN
Solar/Wind Harmer
37.541
25196608WSDLE5
Adder
9.114
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270404AC1-167 GEN
Solar/Wind Harmer
1.161
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
24728705AND G3
Adder
8.251
274826FISK ;BP
Adder
11.256
972228AH1-698 GEN2
Adder
3.807
274730ELWOOD EC;6P
Adder
16.844
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238127S14_GEN_2
Solar/Wind Helper
0.832
235062AE1-101 C1
Solar/Wind Helper
1.665
223401AF1-299 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.504
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.577
202652Y1-033 WT C
Solar/Wind Helper
0.5
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
270054AF2-122 C O1
Solar/Wind Harmer
3.995
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
270158DARBY CT3
Adder
10.24
270317AD1-130_GEN
Solar/Wind Harmer
3.667
958581AF2-149 GEN
Solar/Wind Harmer
4.732
253349AC2-067 GEN
Solar/Wind Harmer
5.421
965051AG1-369 GEN
Solar/Wind Harmer
5.38
971985AH1-537 GEN
Solar/Wind Harmer
19.051
23585401KL_K28_T16
Solar/Wind Helper
1.493
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.117
233970AC1-092 C
Solar/Wind Helper
0.351
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
966111AG1-480 GEN
Solar/Wind Helper
0.045
203955AF1-039 C O1
Solar/Wind Helper
0.33
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
253343AC1-166 GEN
Solar/Wind Harmer
1.243
971995AH1-542 GEN
Solar/Wind Harmer
12.515
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
965421AG1-410 GEN
Solar/Wind Harmer
32.464
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
25194608D.CRK4
Adder
1.747
24639705ELKHART HY
Adder
0.162
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274676JOLIET 29;8U
Adder
31.445
274745AC1-111 GEN9
Adder
5.705
316095T157 G97
Solar/Wind Helper
1.508
238185AF2-356 C
Solar/Wind Helper
2.662
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.347
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
230430AE1-229_GEN
Solar/Wind Helper
3.385
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270166AC1-044 GEN3
50/50
7.1
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965011AG1-365 GEN
Solar/Wind Harmer
10.775
958861AF2-177 GEN
Solar/Wind Harmer
11.644
945371AF1-202 GEN
Solar/Wind Harmer
7.414
25196808ZIMRHP
Adder
80.055
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274801UNIV PARK;4U
Adder
5.993
23583801GRNGAP
Solar/Wind Helper
5.618
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.359
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971029AG2-637 GEN
Solar/Wind Harmer
15.954
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
274775LINCOLN ;6U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
238208AF1-136 C
Solar/Wind Helper
0.221
205943AE1-185 GEN
Solar/Wind Helper
0.511
233990AG1-397 GEN
Solar/Wind Helper
0.031
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
41.173
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
270462AD2-086
Solar/Wind Harmer
7.958
25326309TAIT D
Adder
1.2
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.305
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
274754CRETE EC ;4U
Adder
8.515
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
235067AD1-061 GEN
Solar/Wind Helper
0.498
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
219276PARKLANDSO C
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
23559101PLEAS2
50/50
6.365
970149AG2-104 GEN
Solar/Wind Harmer
50.849
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270263AC1-001 GEN
Solar/Wind Harmer
1.179
927014AC1-188 GEN
Solar/Wind Harmer
1.729
960001AF2-291 GEN
Solar/Wind Harmer
3.264
970091AG2-072 GEN
Adder
78.03
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
23562501BACKB
Solar/Wind Helper
1.017
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233994AC2-023 GEN
Solar/Wind Helper
0.965
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.359
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
WECLTFEXP_WEC->PJM
CLTF
3.842
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LGEELTFEXP_LGEE->PJM
CLTF
6.781
MECLTFEXP_MEC->PJM
CLTF
15.978
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
NYPJM->LTFIMP_NY
CLTF
4.819
TVALTFEXP_TVA->PJM
CLTF
7.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
CPLELTFEXP_CPLE->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:2.68
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
11.828
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
270485AE1-090_GEN
Solar/Wind Harmer
0.69
970065AG2-057 GEN
Solar/Wind Harmer
1.09
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
971191AH1-055 GEN
Solar/Wind Harmer
23.693
965021AG1-366 GEN
Solar/Wind Harmer
2.499
270043AE2-236 GEN
Solar/Wind Harmer
5.876
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
270044AE2-322 C
Solar/Wind Harmer
1.391
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
274802UNIV PARK;5U
Adder
5.978
274800UNIV PARK;3U
Adder
5.975
274729ELWOOD EC;1P
Adder
16.792
237048AF1-022 C
Solar/Wind Helper
0.178
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.072
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.746
958861AF2-177 GEN
Solar/Wind Harmer
11.61
945371AF1-202 GEN
Solar/Wind Harmer
7.392
25196808ZIMRHP
Adder
79.831
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274801UNIV PARK;4U
Adder
5.975
23583801GRNGAP
Solar/Wind Helper
5.606
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
970153AG2-106 GEN
Solar/Wind Harmer
17.883
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270588AE1-091_GEN
Solar/Wind Harmer
11.789
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.933
274676JOLIET 29;8U
Adder
30.228
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
253343AC1-166 GEN
Solar/Wind Harmer
1.241
971995AH1-542 GEN
Solar/Wind Harmer
12.502
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
965421AG1-410 GEN
Solar/Wind Harmer
32.386
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274676JOLIET 29;8U
Adder
31.348
274745AC1-111 GEN9
Adder
5.687
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.651
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
23559001PLEAS1
50/50
6.183
961921AG1-034 GEN
Solar/Wind Harmer
15.599
942051AE2-217 GEN
Solar/Wind Harmer
21.044
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270273AD2-016 GEN
Solar/Wind Harmer
3.032
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
957541AF2-048 GEN
Solar/Wind Harmer
1.72
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.649
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.432
25196608WSDLE5
Adder
9.089
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270404AC1-167 GEN
Solar/Wind Harmer
1.158
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
24728705AND G3
Adder
8.226
274826FISK ;BP
Adder
11.221
972228AH1-698 GEN2
Adder
3.796
274730ELWOOD EC;6P
Adder
16.792
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238127S14_GEN_2
Solar/Wind Helper
0.829
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.06
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270119AB2-067 GEN1
50/50
7.072
970077AG2-063 GEN
Solar/Wind Harmer
6.239
972269AH1-719 GEN
Adder
2.575
253378AE2-206_GEN
Solar/Wind Harmer
4.007
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
942221AE2-234 GEN
Solar/Wind Harmer
0.779
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
972259AH1-714 GEN
Adder
19.535
274696ROCKY RD ;4P
Adder
11.554
274697ROCKY RD ;3P
Adder
3.066
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270459AD2-067 GEN
Solar/Wind Harmer
10.243
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
970879AG2-548 GEN
Solar/Wind Harmer
4.728
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
24729505KEY G4
Adder
6.928
270071AF1-092 GEN
Solar/Wind Harmer
16.001
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.379
971673AH1-337 GEN
Solar/Wind Harmer
4.88
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
270543AE2-219 C
Solar/Wind Harmer
5.43
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.792
238126S14_GEN_1
Solar/Wind Helper
0.829
237085AD2-009_GEN
Solar/Wind Helper
1.651
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.526
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
962771AG1-126 GEN
Solar/Wind Harmer
41.012
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.837
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.833
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270024AE2-089 GEN
Solar/Wind Harmer
4.99
252524AE2-267 GEN
Solar/Wind Harmer
1.673
274811UNIV PK N;7U
Adder
5.147
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274735ELWOOD EC;4P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
203975AE1-071-GEN
Solar/Wind Helper
2.501
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
962761AG1-125 GEN
Solar/Wind Harmer
41.012
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.974
247536S-71 GEN
Solar/Wind Harmer
4.293
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
274754CRETE EC ;4U
Adder
8.489
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.728
270120AB2-067 GEN2
50/50
7.072
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.179
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.625
970883AG2-550 GEN
Solar/Wind Harmer
10.605
25194408D.CRK1
Adder
8.014
24728905RICHG2
Adder
3.969
274803UNIV PARK;6U
Adder
5.978
274674JOLIET 9 ;6U
Adder
15.727
274693ROCKY RD ;1P
Adder
11.176
23585401KL_K28_T16
Solar/Wind Helper
1.485
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.225
270317AD1-130_GEN
Solar/Wind Harmer
3.66
958581AF2-149 GEN
Solar/Wind Harmer
4.736
253349AC2-067 GEN
Solar/Wind Harmer
5.408
965051AG1-369 GEN
Solar/Wind Harmer
5.366
971985AH1-537 GEN
Solar/Wind Harmer
18.998
971029AG2-637 GEN
Solar/Wind Harmer
15.909
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
944031AF1-071 GEN
Solar/Wind Harmer
1.064
274775LINCOLN ;6U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
24318805MLG1
50/50
10.115
270475AD2-096_GEN
50/50
7.148
253338AC1-165 GEN
Solar/Wind Harmer
1.241
972173AH1-669 GEN
Solar/Wind Harmer
5.669
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.224
959331AF2-224 GEN
Solar/Wind Harmer
10.746
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
270222AC2-111 GEN
Solar/Wind Harmer
8.632
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.489
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.342
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
23559101PLEAS2
50/50
6.183
970149AG2-104 GEN
Solar/Wind Harmer
50.65
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
960001AF2-291 GEN
Solar/Wind Harmer
3.255
970091AG2-072 GEN
Adder
77.755
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
23562501BACKB
Solar/Wind Helper
1.01
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972159AH1-661 GEN
Adder
1.116
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
274695ROCKY RD ;2P
Adder
11.287
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
972239AH1-704 GEN
Adder
2.683
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.461
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.175
965041AG1-368 GEN
Solar/Wind Harmer
10.722
966831AG1-554 GEN
Solar/Wind Harmer
1.279
965101AG1-375 GEN
Solar/Wind Harmer
10.622
25196508WSDLE4
Adder
8.996
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274746AC1-111 G10
Adder
5.687
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.64
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.306
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
CPLELTFEXP_CPLE->PJM
CLTF
0.632
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
WECLTFEXP_WEC->PJM
CLTF
3.83
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LGEELTFEXP_LGEE->PJM
CLTF
6.759
MECLTFEXP_MEC->PJM
CLTF
15.925
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.69
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.463
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.174
965041AG1-368 GEN
Solar/Wind Harmer
10.719
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.618
25196508WSDLE4
Adder
8.994
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274746AC1-111 G10
Adder
5.685
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.637
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972159AH1-661 GEN
Adder
1.119
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
274695ROCKY RD ;2P
Adder
11.282
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
270119AB2-067 GEN1
50/50
7.063
970077AG2-063 GEN
Solar/Wind Harmer
6.24
972269AH1-719 GEN
Adder
2.587
253378AE2-206_GEN
Solar/Wind Harmer
4.007
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
942221AE2-234 GEN
Solar/Wind Harmer
0.778
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
972259AH1-714 GEN
Adder
19.527
274696ROCKY RD ;4P
Adder
11.549
274697ROCKY RD ;3P
Adder
3.065
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.692
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270043AE2-236 GEN
Solar/Wind Harmer
5.874
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
270044AE2-322 C
Solar/Wind Harmer
1.39
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
274802UNIV PARK;5U
Adder
5.976
274800UNIV PARK;3U
Adder
5.972
274729ELWOOD EC;1P
Adder
16.784
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
10.248
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
970879AG2-548 GEN
Solar/Wind Harmer
4.73
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
24729505KEY G4
Adder
6.925
270071AF1-092 GEN
Solar/Wind Harmer
15.995
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.378
971673AH1-337 GEN
Solar/Wind Harmer
4.878
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
270543AE2-219 C
Solar/Wind Harmer
5.429
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.784
238126S14_GEN_1
Solar/Wind Helper
0.826
237085AD2-009_GEN
Solar/Wind Helper
1.65
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.524
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
970153AG2-106 GEN
Solar/Wind Harmer
17.867
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270588AE1-091_GEN
Solar/Wind Harmer
11.792
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.932
274676JOLIET 29;8U
Adder
30.215
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
962771AG1-126 GEN
Solar/Wind Harmer
40.976
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.842
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.838
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270024AE2-089 GEN
Solar/Wind Harmer
4.988
252524AE2-267 GEN
Solar/Wind Harmer
1.672
274811UNIV PK N;7U
Adder
5.144
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274735ELWOOD EC;4P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
203975AE1-071-GEN
Solar/Wind Helper
2.5
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
23559001PLEAS1
50/50
6.112
961921AG1-034 GEN
Solar/Wind Harmer
15.607
942051AE2-217 GEN
Solar/Wind Harmer
21.048
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270273AD2-016 GEN
Solar/Wind Harmer
3.033
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.655
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
25196608WSDLE5
Adder
9.087
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270404AC1-167 GEN
Solar/Wind Harmer
1.158
270120AB2-067 GEN2
50/50
7.063
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.621
970883AG2-550 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
8.013
24728905RICHG2
Adder
3.968
274803UNIV PARK;6U
Adder
5.976
274674JOLIET 9 ;6U
Adder
15.72
274693ROCKY RD ;1P
Adder
11.171
23585401KL_K28_T16
Solar/Wind Helper
1.478
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
24728705AND G3
Adder
8.223
274826FISK ;BP
Adder
11.216
972228AH1-698 GEN2
Adder
3.794
274730ELWOOD EC;6P
Adder
16.784
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238127S14_GEN_2
Solar/Wind Helper
0.826
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.061
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
253343AC1-166 GEN
Solar/Wind Harmer
1.242
971995AH1-542 GEN
Solar/Wind Harmer
12.507
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
965421AG1-410 GEN
Solar/Wind Harmer
32.379
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274676JOLIET 29;8U
Adder
31.334
274745AC1-111 GEN9
Adder
5.685
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.642
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270166AC1-044 GEN3
50/50
7.063
23684101S70BUS1
50/50
0.168
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.743
958861AF2-177 GEN
Solar/Wind Harmer
11.606
945371AF1-202 GEN
Solar/Wind Harmer
7.39
25196808ZIMRHP
Adder
79.816
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274801UNIV PARK;4U
Adder
5.972
23583801GRNGAP
Solar/Wind Helper
5.607
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.228
270317AD1-130_GEN
Solar/Wind Harmer
3.659
958581AF2-149 GEN
Solar/Wind Harmer
4.743
253349AC2-067 GEN
Solar/Wind Harmer
5.407
965051AG1-369 GEN
Solar/Wind Harmer
5.365
971985AH1-537 GEN
Solar/Wind Harmer
18.996
971029AG2-637 GEN
Solar/Wind Harmer
15.905
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
944031AF1-071 GEN
Solar/Wind Harmer
1.064
274775LINCOLN ;6U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
40.976
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.292
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
274754CRETE EC ;4U
Adder
8.485
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
270475AD2-096_GEN
50/50
7.147
253338AC1-165 GEN
Solar/Wind Harmer
1.242
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.223
959331AF2-224 GEN
Solar/Wind Harmer
10.743
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
270222AC2-111 GEN
Solar/Wind Harmer
8.63
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.485
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
23559101PLEAS2
50/50
6.112
970149AG2-104 GEN
Solar/Wind Harmer
50.605
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
927014AC1-188 GEN
Solar/Wind Harmer
1.725
960001AF2-291 GEN
Solar/Wind Harmer
3.256
970091AG2-072 GEN
Adder
77.715
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
23562501BACKB
Solar/Wind Helper
1.001
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
WECLTFEXP_WEC->PJM
CLTF
3.828
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.918
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
CPLELTFEXP_CPLE->PJM
CLTF
0.627
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.69
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.463
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
270269AC2-059
Solar/Wind Harmer
10.605
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972159AH1-661 GEN
Adder
1.119
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
270119AB2-067 GEN1
50/50
7.063
970077AG2-063 GEN
Solar/Wind Harmer
6.24
972269AH1-719 GEN
Adder
2.587
253378AE2-206_GEN
Solar/Wind Harmer
4.007
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
942221AE2-234 GEN
Solar/Wind Harmer
0.778
274770LINCOLN ;1U
Adder
8.684
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.692
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270043AE2-236 GEN
Solar/Wind Harmer
5.874
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
270044AE2-322 C
Solar/Wind Harmer
1.39
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
274802UNIV PARK;5U
Adder
5.976
274800UNIV PARK;3U
Adder
5.972
274729ELWOOD EC;1P
Adder
16.784
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
10.248
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.524
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
970153AG2-106 GEN
Solar/Wind Harmer
17.867
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270588AE1-091_GEN
Solar/Wind Harmer
11.792
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.932
274676JOLIET 29;8U
Adder
30.215
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
962771AG1-126 GEN
Solar/Wind Harmer
40.976
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
270120AB2-067 GEN2
50/50
7.063
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.621
970883AG2-550 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
8.013
24728905RICHG2
Adder
3.968
274803UNIV PARK;6U
Adder
5.976
274674JOLIET 9 ;6U
Adder
15.72
274693ROCKY RD ;1P
Adder
11.171
23585401KL_K28_T16
Solar/Wind Helper
1.478
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
23559001PLEAS1
50/50
6.112
961921AG1-034 GEN
Solar/Wind Harmer
15.607
942051AE2-217 GEN
Solar/Wind Harmer
21.048
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270273AD2-016 GEN
Solar/Wind Harmer
3.033
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.655
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
25196608WSDLE5
Adder
9.087
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270404AC1-167 GEN
Solar/Wind Harmer
1.158
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
24728705AND G3
Adder
8.223
274826FISK ;BP
Adder
11.216
972228AH1-698 GEN2
Adder
3.794
274730ELWOOD EC;6P
Adder
16.784
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
970879AG2-548 GEN
Solar/Wind Harmer
4.73
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
24729505KEY G4
Adder
6.925
270071AF1-092 GEN
Solar/Wind Harmer
15.995
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.378
971673AH1-337 GEN
Solar/Wind Harmer
4.878
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
270543AE2-219 C
Solar/Wind Harmer
5.429
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.784
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.842
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.838
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270024AE2-089 GEN
Solar/Wind Harmer
4.988
252524AE2-267 GEN
Solar/Wind Harmer
1.672
274811UNIV PK N;7U
Adder
5.144
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274735ELWOOD EC;4P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
253343AC1-166 GEN
Solar/Wind Harmer
1.242
971995AH1-542 GEN
Solar/Wind Harmer
12.507
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
965421AG1-410 GEN
Solar/Wind Harmer
32.379
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274676JOLIET 29;8U
Adder
31.334
274745AC1-111 GEN9
Adder
5.685
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.642
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
270166AC1-044 GEN3
50/50
7.063
23684101S70BUS1
50/50
0.168
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.743
958861AF2-177 GEN
Solar/Wind Harmer
11.606
945371AF1-202 GEN
Solar/Wind Harmer
7.39
25196808ZIMRHP
Adder
79.816
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274801UNIV PARK;4U
Adder
5.972
23583801GRNGAP
Solar/Wind Helper
5.607
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
972259AH1-714 GEN
Adder
19.527
274696ROCKY RD ;4P
Adder
11.549
274697ROCKY RD ;3P
Adder
3.065
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.726
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238127S14_GEN_2
Solar/Wind Helper
0.826
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.061
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.228
270317AD1-130_GEN
Solar/Wind Harmer
3.659
958581AF2-149 GEN
Solar/Wind Harmer
4.743
253349AC2-067 GEN
Solar/Wind Harmer
5.407
965051AG1-369 GEN
Solar/Wind Harmer
5.365
971985AH1-537 GEN
Solar/Wind Harmer
18.996
971029AG2-637 GEN
Solar/Wind Harmer
15.905
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
944031AF1-071 GEN
Solar/Wind Harmer
1.064
274775LINCOLN ;6U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
40.976
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.292
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
274754CRETE EC ;4U
Adder
8.485
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.726
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
274695ROCKY RD ;2P
Adder
11.282
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
24318805MLG1
50/50
10.098
270475AD2-096_GEN
50/50
7.147
253338AC1-165 GEN
Solar/Wind Harmer
1.242
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.223
959331AF2-224 GEN
Solar/Wind Harmer
10.743
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
270222AC2-111 GEN
Solar/Wind Harmer
8.63
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.485
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
23559101PLEAS2
50/50
6.112
970149AG2-104 GEN
Solar/Wind Harmer
50.605
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
927014AC1-188 GEN
Solar/Wind Harmer
1.725
960001AF2-291 GEN
Solar/Wind Harmer
3.256
970091AG2-072 GEN
Adder
77.715
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
23562501BACKB
Solar/Wind Helper
1.001
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
238126S14_GEN_1
Solar/Wind Helper
0.826
237085AD2-009_GEN
Solar/Wind Helper
1.65
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
203975AE1-071-GEN
Solar/Wind Helper
2.5
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.174
965041AG1-368 GEN
Solar/Wind Harmer
10.719
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.618
25196508WSDLE4
Adder
8.994
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274746AC1-111 G10
Adder
5.685
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.637
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
CPLELTFEXP_CPLE->PJM
CLTF
0.627
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
WECLTFEXP_WEC->PJM
CLTF
3.828
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.918
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.074
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
NYPJM->LTFIMP_NY
CLTF
4.797
TVALTFEXP_TVA->PJM
CLTF
7.293
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
CPLELTFEXP_CPLE->PJM
CLTF
0.624
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
WECLTFEXP_WEC->PJM
CLTF
3.825
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LGEELTFEXP_LGEE->PJM
CLTF
6.749
MECLTFEXP_MEC->PJM
CLTF
15.901
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:3.1
Bus #Bus NameTypeMW Contribution
970153AG2-106 GEN
Solar/Wind Harmer
17.863
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
24721905FLATG4
Adder
23.506
270588AE1-091_GEN
Solar/Wind Harmer
12.311
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
25194608D.CRK4
Adder
1.752
23906502RICHG2&3
Adder
1.272
274676JOLIET 29;8U
Adder
30.573
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
237080AD1-060 GEN
Solar/Wind Helper
0.367
966131AG1-482 GEN
Solar/Wind Helper
0.079
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
232434Z2-077 GEN
Solar/Wind Helper
0.129
316192AB2-158 GEN
Solar/Wind Helper
1.608
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
217208PARK ELE C
Solar/Wind Helper
0.004
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
971995AH1-542 GEN
Solar/Wind Harmer
12.974
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
965421AG1-410 GEN
Solar/Wind Harmer
33.256
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
24695305TIMB G C
Solar/Wind Harmer
6.051
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
965651AG1-433 GEN
Solar/Wind Harmer
5.885
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
23906502RICHG2&3
Adder
1.272
23906402RICHG1
Adder
1.271
274812UNIV PK N;8U
Adder
5.21
274676JOLIET 29;8U
Adder
31.706
316095T157 G97
Solar/Wind Helper
1.705
238185AF2-356 C
Solar/Wind Helper
2.767
237030AB1-096 C
Solar/Wind Helper
0.075
227287AC2-120 GEN
Solar/Wind Helper
0.375
23751101LEADS_P59
Solar/Wind Helper
1.316
233996TM1833_GEN
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
966881AG1-559 GEN
Solar/Wind Helper
0.312
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270051AF1-062 GEN
50/50
11.999
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
970065AG2-057 GEN
Solar/Wind Harmer
1.148
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270044AE2-322 C
Solar/Wind Harmer
1.435
270043AE2-236 GEN
Solar/Wind Harmer
5.98
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196008MFTGT1
Adder
1.413
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274800UNIV PARK;3U
Adder
6.045
274729ELWOOD EC;1P
Adder
16.983
237048AF1-022 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.387
233954AC2-188 GEN
Solar/Wind Helper
0.236
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.137
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.033
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
247522W1-056 GEN
Solar/Wind Harmer
2.477
965011AG1-365 GEN
Solar/Wind Harmer
10.972
958861AF2-177 GEN
Solar/Wind Harmer
11.752
945371AF1-202 GEN
Solar/Wind Harmer
7.479
25196808ZIMRHP
Adder
80.188
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274801UNIV PARK;4U
Adder
6.045
23583801GRNGAP
Solar/Wind Helper
6.365
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
238221AF1-254 C O1
Solar/Wind Helper
0.295
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
23559001PLEAS1
50/50
5.443
961921AG1-034 GEN
Solar/Wind Harmer
15.919
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
970605AG2-385 GEN
Solar/Wind Harmer
6.332
253333AC1-068 GEN
Solar/Wind Harmer
1.211
270273AD2-016 GEN
Solar/Wind Harmer
3.061
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
958091AF2-103 GEN
Solar/Wind Harmer
0.178
962761AG1-125 GEN
Solar/Wind Harmer
40.965
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270462AD2-086
Solar/Wind Harmer
8.157
241813AF1-122_GEN
Solar/Wind Harmer
7.346
241847AF2-150_GEN
Solar/Wind Harmer
4.622
25326309TAIT D
Adder
1.21
944231AF1-091 GEN
Solar/Wind Harmer
4.078
270063AE2-323 C
Solar/Wind Harmer
2.376
247536S-71 GEN
Solar/Wind Harmer
4.346
972301AH1-735 GEN
Adder
6.357
274754CRETE EC ;4U
Adder
8.598
274732ELWOOD EC;7P
Adder
2.004
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238117U2-030
Solar/Wind Helper
0.356
235067AD1-061 GEN
Solar/Wind Helper
0.532
270247TR4_N_V136
Solar/Wind Harmer
0.936
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
944531AF1-118 GEN
Solar/Wind Harmer
37.943
970031AG2-029 GEN
Solar/Wind Harmer
32.394
270541AE2-072 C
Solar/Wind Harmer
4.881
25196608WSDLE5
Adder
9.143
247604X1-042
Adder
0.444
274752CRETE EC ;2U
Adder
8.598
274826FISK ;BP
Adder
11.355
972228AH1-698 GEN2
Adder
3.84
274730ELWOOD EC;6P
Adder
16.983
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238127S14_GEN_2
Solar/Wind Helper
0.867
235062AE1-101 C1
Solar/Wind Helper
1.776
223401AF1-299 GEN
Solar/Wind Helper
0.387
316254AC1-120 GEN1
Solar/Wind Helper
1.184
233915AB1-141 GEN
Solar/Wind Helper
0.511
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.568
226910AB2-157 C
Solar/Wind Helper
0.015
223402AF1-300 C
Solar/Wind Helper
0.387
233982AB2-133 GEN
Solar/Wind Helper
0.364
233940AF2-379 C
Solar/Wind Helper
0.063
233952AC2-187 GEN
Solar/Wind Helper
0.236
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
970149AG2-104 GEN
Solar/Wind Harmer
50.592
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
253325AC1-069 GEN
Solar/Wind Harmer
1.211
270263AC1-001 GEN
Solar/Wind Harmer
1.187
970515AG2-329 GEN
Solar/Wind Harmer
16.033
927014AC1-188 GEN
Solar/Wind Harmer
1.729
960001AF2-291 GEN
Solar/Wind Harmer
3.244
23920202STRYCT
Adder
1.444
238108AE1-109 GEN1
Solar/Wind Helper
0.121
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
23562501BACKB
Solar/Wind Helper
0.997
316170AC1-121 GEN2
Solar/Wind Helper
0.395
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233994AC2-023 GEN
Solar/Wind Helper
0.977
233997TMININ_4.2
Solar/Wind Helper
0.266
233971AC1-093 C
Solar/Wind Helper
0.363
228729W2-030 C
Solar/Wind Helper
0.112
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
270119AB2-067 GEN1
50/50
7.033
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
253378AE2-206_GEN
Solar/Wind Harmer
4.086
25326509SID D
Adder
1.48
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
270007AE1-245 C
Solar/Wind Harmer
6.539
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
942221AE2-234 GEN
Solar/Wind Harmer
0.79
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
235020AA1-095 C
Solar/Wind Helper
0.057
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
233933AB2-153 GEN
Solar/Wind Helper
0.236
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.091
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
3147666LOUISA
Solar/Wind Helper
0.551
234015AF2-250 C
Solar/Wind Helper
0.039
219276PARKLANDSO C
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
276820AF1-078_GEN
Solar/Wind Harmer
1.815
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
253370AE2-315 SEC1
Adder
2.206
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
247621Y3-024
Adder
0.259
970935AG2-582 GEN
Adder
239.406
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
230407AD2-065 C
Solar/Wind Helper
0.041
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270459AD2-067 GEN
Solar/Wind Harmer
10.453
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
971567AH1-282 GEN
Solar/Wind Harmer
16.984
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
958711AF2-162 GEN
Solar/Wind Harmer
1.089
270543AE2-219 C
Solar/Wind Harmer
5.494
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274728ELWOOD EC;5P
Adder
16.983
238126S14_GEN_1
Solar/Wind Helper
0.867
237085AD2-009_GEN
Solar/Wind Helper
1.767
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.768
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
270302AB2-170 GEN
Solar/Wind Harmer
9.805
970689AG2-444 GEN
Solar/Wind Harmer
19.055
970179AG2-119 GEN
Solar/Wind Harmer
9.26
971989AH1-539 GEN
Solar/Wind Harmer
14.49
957201AF2-014 GEN
Solar/Wind Harmer
5.033
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
25306009OHH W.
Adder
3.166
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270024AE2-089 GEN
Solar/Wind Harmer
5.065
274811UNIV PK N;7U
Adder
5.21
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274735ELWOOD EC;4P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205932AD2-116_GEN
Solar/Wind Helper
0.518
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
203975AE1-071-GEN
Solar/Wind Helper
2.53
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.033
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
971201AH1-060 GEN
Solar/Wind Harmer
2.296
942801AE2-298 GEN
Solar/Wind Harmer
1.667
960971AF2-388 GEN
Solar/Wind Harmer
11.771
970883AG2-550 GEN
Solar/Wind Harmer
10.73
25194408D.CRK1
Adder
8.061
24728905RICHG2
Adder
4.003
274803UNIV PARK;6U
Adder
6.05
23585401KL_K28_T16
Solar/Wind Helper
1.529
23777901MDS_W4-102
Solar/Wind Helper
0.191
237002AB1-128_GEN
Solar/Wind Helper
0.475
237006AB1-125 GEN
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
232424Y1-079 C
Solar/Wind Helper
0.118
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.044
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
270158DARBY CT3
Adder
10.362
270317AD1-130_GEN
Solar/Wind Harmer
3.759
958581AF2-149 GEN
Solar/Wind Harmer
4.968
965051AG1-369 GEN
Solar/Wind Harmer
5.494
253349AC2-067 GEN
Solar/Wind Harmer
5.466
945641AF1-229 GEN
Solar/Wind Harmer
3.923
961761AG1-017 GEN
Solar/Wind Harmer
0.46
971029AG2-637 GEN
Solar/Wind Harmer
16.089
274775LINCOLN ;6U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
972037AH1-567 GEN1
Adder
0.19
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
238208AF1-136 C
Solar/Wind Helper
0.236
205943AE1-185 GEN
Solar/Wind Helper
0.518
233990AG1-397 GEN
Solar/Wind Helper
0.031
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
945581AF1-223 GEN
Solar/Wind Harmer
0.763
24318805MLG1
50/50
10.022
253338AC1-165 GEN
Solar/Wind Harmer
1.256
972173AH1-669 GEN
Solar/Wind Harmer
5.721
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
270191TR4_S_V150
Solar/Wind Harmer
3.3
959331AF2-224 GEN
Solar/Wind Harmer
10.972
270258AD1-119 GEN
Solar/Wind Harmer
3.051
971617AH1-308 GEN
Solar/Wind Harmer
6.274
24642205MAYFLWER
Adder
0.678
274753CRETE EC ;3U
Adder
8.598
972038AH1-567 GEN2
Adder
0.378
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.356
237038AE2-054 C
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
316045AC1-158 PL2
Solar/Wind Helper
4.618
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
207445AB1-138_GEN
Solar/Wind Helper
0.105
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
946101AF1-275 GEN
Solar/Wind Harmer
1.842
942861AE2-305 GEN
Solar/Wind Harmer
9.223
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326109MON D
Adder
1.461
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
944541AF1-119 GEN
Solar/Wind Harmer
4.511
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
237034AC2-136 C
Solar/Wind Helper
0.244
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
226929AD2-058 GEN
Solar/Wind Helper
0.108
233987AB2-037 GEN
Solar/Wind Helper
2.381
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
972239AH1-704 GEN
50/50
3.102
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270432AC2-029 GEN
Solar/Wind Harmer
8.138
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
966831AG1-554 GEN
Solar/Wind Harmer
1.34
270340AC2-060 GEN
Solar/Wind Harmer
3.371
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253400AC2-068 GEN
Solar/Wind Harmer
2.198
965101AG1-375 GEN
Solar/Wind Harmer
10.752
25196508WSDLE4
Adder
9.049
274776LINCOLN ;7U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
219914AD2-027 C
Solar/Wind Helper
0.116
219607WPEMNERT C
Solar/Wind Helper
0.081
20715728PEM_W1-119
Solar/Wind Helper
0.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LGEELTFEXP_LGEE->PJM
CLTF
6.753
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
NYPJM->LTFIMP_NY
CLTF
4.554
MECLTFEXP_MEC->PJM
CLTF
15.979
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
WECLTFEXP_WEC->PJM
CLTF
3.866
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:2.78
Bus #Bus NameTypeMW Contribution
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
270119AB2-067 GEN1
50/50
6.869
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
219607WPEMNERT C
Solar/Wind Helper
0.077
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
970153AG2-106 GEN
Solar/Wind Harmer
21.245
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.532
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
NYPJM->LTFIMP_NY
CLTF
4.628
TVALTFEXP_TVA->PJM
CLTF
7.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
CPLELTFEXP_CPLE->PJM
CLTF
0.567
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
WECLTFEXP_WEC->PJM
CLTF
3.686
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LGEELTFEXP_LGEE->PJM
CLTF
6.497
MECLTFEXP_MEC->PJM
CLTF
15.319
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:2.67
Bus #Bus NameTypeMW Contribution
970153AG2-106 GEN
Solar/Wind Harmer
17.953
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270588AE1-091_GEN
Solar/Wind Harmer
11.804
25194608D.CRK4
Adder
1.747
24728505AND G1
Adder
3.945
274676JOLIET 29;8U
Adder
30.322
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
237080AD1-060 GEN
Solar/Wind Helper
0.343
966131AG1-482 GEN
Solar/Wind Helper
0.078
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
253343AC1-166 GEN
Solar/Wind Harmer
1.243
971995AH1-542 GEN
Solar/Wind Harmer
12.515
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
965421AG1-410 GEN
Solar/Wind Harmer
32.464
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
25194608D.CRK4
Adder
1.747
24639705ELKHART HY
Adder
0.162
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274676JOLIET 29;8U
Adder
31.445
274745AC1-111 GEN9
Adder
5.705
316095T157 G97
Solar/Wind Helper
1.508
238185AF2-356 C
Solar/Wind Helper
2.662
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.347
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
230430AE1-229_GEN
Solar/Wind Helper
3.385
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
217208PARK ELE C
Solar/Wind Helper
0.004
270051AF1-062 GEN
50/50
11.843
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
270485AE1-090_GEN
Solar/Wind Harmer
0.692
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.759
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270043AE2-236 GEN
Solar/Wind Harmer
5.893
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
270044AE2-322 C
Solar/Wind Harmer
1.394
25196008MFTGT1
Adder
1.411
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
274800UNIV PARK;3U
Adder
5.993
274729ELWOOD EC;1P
Adder
16.844
237048AF1-022 C
Solar/Wind Helper
0.179
233930AB2-032 GEN
Solar/Wind Helper
0.382
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.231
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.1
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965011AG1-365 GEN
Solar/Wind Harmer
10.775
958861AF2-177 GEN
Solar/Wind Harmer
11.644
945371AF1-202 GEN
Solar/Wind Harmer
7.414
25196808ZIMRHP
Adder
80.055
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274801UNIV PARK;4U
Adder
5.993
23583801GRNGAP
Solar/Wind Helper
5.618
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.359
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.365
961921AG1-034 GEN
Solar/Wind Harmer
15.612
942051AE2-217 GEN
Solar/Wind Harmer
21.08
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270273AD2-016 GEN
Solar/Wind Harmer
3.037
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
957541AF2-048 GEN
Solar/Wind Harmer
1.724
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270247TR4_N_V136
Solar/Wind Harmer
0.916
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
944531AF1-118 GEN
Solar/Wind Harmer
37.541
25196608WSDLE5
Adder
9.114
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270404AC1-167 GEN
Solar/Wind Harmer
1.161
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
24728705AND G3
Adder
8.251
274826FISK ;BP
Adder
11.256
972228AH1-698 GEN2
Adder
3.807
274730ELWOOD EC;6P
Adder
16.844
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238127S14_GEN_2
Solar/Wind Helper
0.832
235062AE1-101 C1
Solar/Wind Helper
1.665
223401AF1-299 GEN
Solar/Wind Helper
0.369
962761AG1-125 GEN
Solar/Wind Harmer
41.173
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
270462AD2-086
Solar/Wind Harmer
7.958
25326309TAIT D
Adder
1.2
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.305
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
274754CRETE EC ;4U
Adder
8.515
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
235067AD1-061 GEN
Solar/Wind Helper
0.498
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
233915AB1-141 GEN
Solar/Wind Helper
0.504
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.577
202652Y1-033 WT C
Solar/Wind Helper
0.5
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
24318805MLG1
50/50
10.158
270475AD2-096_GEN
50/50
7.165
253338AC1-165 GEN
Solar/Wind Harmer
1.243
972173AH1-669 GEN
Solar/Wind Harmer
5.679
23559101PLEAS2
50/50
6.365
970149AG2-104 GEN
Solar/Wind Harmer
50.849
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270263AC1-001 GEN
Solar/Wind Harmer
1.179
927014AC1-188 GEN
Solar/Wind Harmer
1.729
960001AF2-291 GEN
Solar/Wind Harmer
3.264
970091AG2-072 GEN
Adder
78.03
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
23562501BACKB
Solar/Wind Helper
1.017
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233994AC2-023 GEN
Solar/Wind Helper
0.965
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.359
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
270119AB2-067 GEN1
50/50
7.1
970077AG2-063 GEN
Solar/Wind Harmer
6.25
253378AE2-206_GEN
Solar/Wind Harmer
4.016
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
970879AG2-548 GEN
Solar/Wind Harmer
6.788
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
970611AG2-400 GEN
Solar/Wind Harmer
10.775
270007AE1-245 C
Solar/Wind Harmer
6.374
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
942221AE2-234 GEN
Solar/Wind Harmer
0.781
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
972259AH1-714 GEN
Adder
19.596
274696ROCKY RD ;4P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.076
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
4.981
219276PARKLANDSO C
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
276820AF1-078_GEN
Solar/Wind Harmer
1.784
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.528
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270459AD2-067 GEN
Solar/Wind Harmer
10.252
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
970879AG2-548 GEN
Solar/Wind Harmer
4.736
270435AC2-044 GEN
Solar/Wind Harmer
2.165
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
971567AH1-282 GEN
Solar/Wind Harmer
16.053
270071AF1-092 GEN
Solar/Wind Harmer
16.048
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
270543AE2-219 C
Solar/Wind Harmer
5.445
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274728ELWOOD EC;5P
Adder
16.844
238126S14_GEN_1
Solar/Wind Helper
0.832
237085AD2-009_GEN
Solar/Wind Helper
1.655
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.786
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270302AB2-170 GEN
Solar/Wind Harmer
9.566
970179AG2-119 GEN
Solar/Wind Harmer
8.844
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
957201AF2-014 GEN
Solar/Wind Harmer
4.91
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270024AE2-089 GEN
Solar/Wind Harmer
5.004
252524AE2-267 GEN
Solar/Wind Harmer
1.677
274811UNIV PK N;7U
Adder
5.162
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274735ELWOOD EC;4P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.359
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.511
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
203975AE1-071-GEN
Solar/Wind Helper
2.508
966261AG1-495 GEN
Solar/Wind Helper
0.082
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.1
270224U2-072_GEN2
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.626
960971AF2-388 GEN
Solar/Wind Harmer
11.659
970883AG2-550 GEN
Solar/Wind Harmer
10.634
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.981
274803UNIV PARK;6U
Adder
5.997
274674JOLIET 9 ;6U
Adder
15.776
274693ROCKY RD ;1P
Adder
11.211
23585401KL_K28_T16
Solar/Wind Helper
1.493
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.117
233970AC1-092 C
Solar/Wind Helper
0.351
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
966111AG1-480 GEN
Solar/Wind Helper
0.045
203955AF1-039 C O1
Solar/Wind Helper
0.33
270054AF2-122 C O1
Solar/Wind Harmer
3.995
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
270158DARBY CT3
Adder
10.24
270317AD1-130_GEN
Solar/Wind Harmer
3.667
958581AF2-149 GEN
Solar/Wind Harmer
4.732
253349AC2-067 GEN
Solar/Wind Harmer
5.421
965051AG1-369 GEN
Solar/Wind Harmer
5.38
971985AH1-537 GEN
Solar/Wind Harmer
19.051
971029AG2-637 GEN
Solar/Wind Harmer
15.954
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
274775LINCOLN ;6U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
238208AF1-136 C
Solar/Wind Helper
0.221
205943AE1-185 GEN
Solar/Wind Helper
0.511
233990AG1-397 GEN
Solar/Wind Helper
0.031
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
270518AE2-148 GEN
Solar/Wind Harmer
13.911
972159AH1-661 GEN
Adder
1.111
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
274695ROCKY RD ;2P
Adder
11.323
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.35
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
270191TR4_S_V150
Solar/Wind Harmer
3.232
959331AF2-224 GEN
Solar/Wind Harmer
10.775
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
270222AC2-111 GEN
Solar/Wind Harmer
8.657
24642205MAYFLWER
Adder
0.667
274753CRETE EC ;3U
Adder
8.515
972038AH1-567 GEN2
Adder
0.375
238118U2-030_1
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237038AE2-054 C
Solar/Wind Helper
0.273
23779801AA1-109
Solar/Wind Helper
0.194
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.149
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
207445AB1-138_GEN
Solar/Wind Helper
0.105
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.327
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
961821AG1-024 GEN
Solar/Wind Harmer
10.408
972239AH1-704 GEN
Adder
2.671
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270269AC2-059
Solar/Wind Harmer
10.62
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
253400AC2-068 GEN
Solar/Wind Harmer
2.18
965041AG1-368 GEN
Solar/Wind Harmer
10.749
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.653
25196508WSDLE4
Adder
9.021
270297AD1-101 GEN
Solar/Wind Harmer
2.953
274776LINCOLN ;7U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274746AC1-111 G10
Adder
5.705
238152AF2-075_GEN
Solar/Wind Helper
0.709
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.644
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
WECLTFEXP_WEC->PJM
CLTF
3.842
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LGEELTFEXP_LGEE->PJM
CLTF
6.781
MECLTFEXP_MEC->PJM
CLTF
15.978
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
NYPJM->LTFIMP_NY
CLTF
4.819
TVALTFEXP_TVA->PJM
CLTF
7.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
CPLELTFEXP_CPLE->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:2.68
Bus #Bus NameTypeMW Contribution
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972159AH1-661 GEN
Adder
1.116
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
274695ROCKY RD ;2P
Adder
11.287
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.526
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270119AB2-067 GEN1
50/50
7.072
970077AG2-063 GEN
Solar/Wind Harmer
6.239
972269AH1-719 GEN
Adder
2.575
253378AE2-206_GEN
Solar/Wind Harmer
4.007
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
942221AE2-234 GEN
Solar/Wind Harmer
0.779
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
972259AH1-714 GEN
Adder
19.535
274696ROCKY RD ;4P
Adder
11.554
274697ROCKY RD ;3P
Adder
3.066
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270051AF1-062 GEN
50/50
11.828
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
270485AE1-090_GEN
Solar/Wind Harmer
0.69
970065AG2-057 GEN
Solar/Wind Harmer
1.09
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
971191AH1-055 GEN
Solar/Wind Harmer
23.693
965021AG1-366 GEN
Solar/Wind Harmer
2.499
270043AE2-236 GEN
Solar/Wind Harmer
5.876
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
270044AE2-322 C
Solar/Wind Harmer
1.391
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
274802UNIV PARK;5U
Adder
5.978
274800UNIV PARK;3U
Adder
5.975
274729ELWOOD EC;1P
Adder
16.792
237048AF1-022 C
Solar/Wind Helper
0.178
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
24318805MLG1
50/50
10.115
270475AD2-096_GEN
50/50
7.148
253338AC1-165 GEN
Solar/Wind Harmer
1.241
972173AH1-669 GEN
Solar/Wind Harmer
5.669
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.224
959331AF2-224 GEN
Solar/Wind Harmer
10.746
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
270222AC2-111 GEN
Solar/Wind Harmer
8.632
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.489
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.342
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
972239AH1-704 GEN
Adder
2.683
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.461
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.175
965041AG1-368 GEN
Solar/Wind Harmer
10.722
966831AG1-554 GEN
Solar/Wind Harmer
1.279
965101AG1-375 GEN
Solar/Wind Harmer
10.622
25196508WSDLE4
Adder
8.996
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274746AC1-111 G10
Adder
5.687
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.64
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
10.243
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
970879AG2-548 GEN
Solar/Wind Harmer
4.728
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
24729505KEY G4
Adder
6.928
270071AF1-092 GEN
Solar/Wind Harmer
16.001
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.379
971673AH1-337 GEN
Solar/Wind Harmer
4.88
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
270543AE2-219 C
Solar/Wind Harmer
5.43
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.792
238126S14_GEN_1
Solar/Wind Helper
0.829
237085AD2-009_GEN
Solar/Wind Helper
1.651
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
970153AG2-106 GEN
Solar/Wind Harmer
17.883
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270588AE1-091_GEN
Solar/Wind Harmer
11.789
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.933
274676JOLIET 29;8U
Adder
30.228
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
962771AG1-126 GEN
Solar/Wind Harmer
41.012
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.837
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.833
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270024AE2-089 GEN
Solar/Wind Harmer
4.99
252524AE2-267 GEN
Solar/Wind Harmer
1.673
274811UNIV PK N;7U
Adder
5.147
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274735ELWOOD EC;4P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
203975AE1-071-GEN
Solar/Wind Helper
2.501
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.072
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.179
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.625
970883AG2-550 GEN
Solar/Wind Harmer
10.605
25194408D.CRK1
Adder
8.014
24728905RICHG2
Adder
3.969
274803UNIV PARK;6U
Adder
5.978
274674JOLIET 9 ;6U
Adder
15.727
274693ROCKY RD ;1P
Adder
11.176
23585401KL_K28_T16
Solar/Wind Helper
1.485
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
23559001PLEAS1
50/50
6.183
961921AG1-034 GEN
Solar/Wind Harmer
15.599
942051AE2-217 GEN
Solar/Wind Harmer
21.044
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270273AD2-016 GEN
Solar/Wind Harmer
3.032
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
957541AF2-048 GEN
Solar/Wind Harmer
1.72
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.649
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.432
25196608WSDLE5
Adder
9.089
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270404AC1-167 GEN
Solar/Wind Harmer
1.158
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
24728705AND G3
Adder
8.226
274826FISK ;BP
Adder
11.221
972228AH1-698 GEN2
Adder
3.796
274730ELWOOD EC;6P
Adder
16.792
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238127S14_GEN_2
Solar/Wind Helper
0.829
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.06
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.225
270317AD1-130_GEN
Solar/Wind Harmer
3.66
958581AF2-149 GEN
Solar/Wind Harmer
4.736
253349AC2-067 GEN
Solar/Wind Harmer
5.408
965051AG1-369 GEN
Solar/Wind Harmer
5.366
971985AH1-537 GEN
Solar/Wind Harmer
18.998
971029AG2-637 GEN
Solar/Wind Harmer
15.909
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
944031AF1-071 GEN
Solar/Wind Harmer
1.064
274775LINCOLN ;6U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
253343AC1-166 GEN
Solar/Wind Harmer
1.241
971995AH1-542 GEN
Solar/Wind Harmer
12.502
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
965421AG1-410 GEN
Solar/Wind Harmer
32.386
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274676JOLIET 29;8U
Adder
31.348
274745AC1-111 GEN9
Adder
5.687
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.651
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270166AC1-044 GEN3
50/50
7.072
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.746
958861AF2-177 GEN
Solar/Wind Harmer
11.61
945371AF1-202 GEN
Solar/Wind Harmer
7.392
25196808ZIMRHP
Adder
79.831
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274801UNIV PARK;4U
Adder
5.975
23583801GRNGAP
Solar/Wind Helper
5.606
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
962761AG1-125 GEN
Solar/Wind Harmer
41.012
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.974
247536S-71 GEN
Solar/Wind Harmer
4.293
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
274754CRETE EC ;4U
Adder
8.489
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.728
23559101PLEAS2
50/50
6.183
970149AG2-104 GEN
Solar/Wind Harmer
50.65
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
960001AF2-291 GEN
Solar/Wind Harmer
3.255
970091AG2-072 GEN
Adder
77.755
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
23562501BACKB
Solar/Wind Helper
1.01
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.306
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
CPLELTFEXP_CPLE->PJM
CLTF
0.632
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
WECLTFEXP_WEC->PJM
CLTF
3.83
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LGEELTFEXP_LGEE->PJM
CLTF
6.759
MECLTFEXP_MEC->PJM
CLTF
15.925
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
253343AC1-166 GEN
Solar/Wind Harmer
1.242
971995AH1-542 GEN
Solar/Wind Harmer
12.507
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
965421AG1-410 GEN
Solar/Wind Harmer
32.379
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
970153AG2-106 GEN
Solar/Wind Harmer
17.867
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270588AE1-091_GEN
Solar/Wind Harmer
11.792
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.932
274676JOLIET 29;8U
Adder
30.215
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.692
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270043AE2-236 GEN
Solar/Wind Harmer
5.874
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
270044AE2-322 C
Solar/Wind Harmer
1.39
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
274802UNIV PARK;5U
Adder
5.976
274800UNIV PARK;3U
Adder
5.972
274729ELWOOD EC;1P
Adder
16.784
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
23559001PLEAS1
50/50
6.112
961921AG1-034 GEN
Solar/Wind Harmer
15.607
942051AE2-217 GEN
Solar/Wind Harmer
21.048
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.063
23684101S70BUS1
50/50
0.168
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.743
958861AF2-177 GEN
Solar/Wind Harmer
11.606
945371AF1-202 GEN
Solar/Wind Harmer
7.39
25196808ZIMRHP
Adder
79.816
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274801UNIV PARK;4U
Adder
5.972
23583801GRNGAP
Solar/Wind Helper
5.607
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274676JOLIET 29;8U
Adder
31.334
274745AC1-111 GEN9
Adder
5.685
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.642
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
23559101PLEAS2
50/50
6.112
970149AG2-104 GEN
Solar/Wind Harmer
50.605
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
927014AC1-188 GEN
Solar/Wind Harmer
1.725
960001AF2-291 GEN
Solar/Wind Harmer
3.256
970091AG2-072 GEN
Adder
77.715
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
23562501BACKB
Solar/Wind Helper
1.001
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
270119AB2-067 GEN1
50/50
7.063
270273AD2-016 GEN
Solar/Wind Harmer
3.033
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.655
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
25196608WSDLE5
Adder
9.087
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270404AC1-167 GEN
Solar/Wind Harmer
1.158
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
24728705AND G3
Adder
8.223
274826FISK ;BP
Adder
11.216
972228AH1-698 GEN2
Adder
3.794
274730ELWOOD EC;6P
Adder
16.784
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238127S14_GEN_2
Solar/Wind Helper
0.826
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.061
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
962761AG1-125 GEN
Solar/Wind Harmer
40.976
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.292
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.524
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
970077AG2-063 GEN
Solar/Wind Harmer
6.24
972269AH1-719 GEN
Adder
2.587
253378AE2-206_GEN
Solar/Wind Harmer
4.007
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
942221AE2-234 GEN
Solar/Wind Harmer
0.778
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
972259AH1-714 GEN
Adder
19.527
274696ROCKY RD ;4P
Adder
11.549
274697ROCKY RD ;3P
Adder
3.065
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270459AD2-067 GEN
Solar/Wind Harmer
10.248
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
970879AG2-548 GEN
Solar/Wind Harmer
4.73
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
24729505KEY G4
Adder
6.925
270071AF1-092 GEN
Solar/Wind Harmer
15.995
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.378
971673AH1-337 GEN
Solar/Wind Harmer
4.878
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
270543AE2-219 C
Solar/Wind Harmer
5.429
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.784
238126S14_GEN_1
Solar/Wind Helper
0.826
237085AD2-009_GEN
Solar/Wind Helper
1.65
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
962771AG1-126 GEN
Solar/Wind Harmer
40.976
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.842
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.838
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270024AE2-089 GEN
Solar/Wind Harmer
4.988
252524AE2-267 GEN
Solar/Wind Harmer
1.672
274811UNIV PK N;7U
Adder
5.144
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274735ELWOOD EC;4P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
203975AE1-071-GEN
Solar/Wind Helper
2.5
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
274754CRETE EC ;4U
Adder
8.485
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.726
270120AB2-067 GEN2
50/50
7.063
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.621
970883AG2-550 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
8.013
24728905RICHG2
Adder
3.968
274803UNIV PARK;6U
Adder
5.976
274674JOLIET 9 ;6U
Adder
15.72
274693ROCKY RD ;1P
Adder
11.171
23585401KL_K28_T16
Solar/Wind Helper
1.478
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.228
270317AD1-130_GEN
Solar/Wind Harmer
3.659
958581AF2-149 GEN
Solar/Wind Harmer
4.743
253349AC2-067 GEN
Solar/Wind Harmer
5.407
965051AG1-369 GEN
Solar/Wind Harmer
5.365
971985AH1-537 GEN
Solar/Wind Harmer
18.996
971029AG2-637 GEN
Solar/Wind Harmer
15.905
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
944031AF1-071 GEN
Solar/Wind Harmer
1.064
274775LINCOLN ;6U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
24318805MLG1
50/50
10.098
270475AD2-096_GEN
50/50
7.147
253338AC1-165 GEN
Solar/Wind Harmer
1.242
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.223
959331AF2-224 GEN
Solar/Wind Harmer
10.743
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
270222AC2-111 GEN
Solar/Wind Harmer
8.63
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.485
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972159AH1-661 GEN
Adder
1.119
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
274695ROCKY RD ;2P
Adder
11.282
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
972239AH1-704 GEN
Adder
2.69
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.463
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.174
965041AG1-368 GEN
Solar/Wind Harmer
10.719
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.618
25196508WSDLE4
Adder
8.994
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274746AC1-111 G10
Adder
5.685
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.637
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
WECLTFEXP_WEC->PJM
CLTF
3.828
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.918
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
CPLELTFEXP_CPLE->PJM
CLTF
0.627
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
276820AF1-078_GEN
Solar/Wind Harmer
1.78
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
238120AE2-309 GEN
Solar/Wind Helper
0.524
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
270119AB2-067 GEN1
50/50
7.063
970077AG2-063 GEN
Solar/Wind Harmer
6.24
972269AH1-719 GEN
Adder
2.587
253378AE2-206_GEN
Solar/Wind Harmer
4.007
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
971191AH1-055 GEN
Solar/Wind Harmer
23.692
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270043AE2-236 GEN
Solar/Wind Harmer
5.874
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
270044AE2-322 C
Solar/Wind Harmer
1.39
25196008MFTGT1
Adder
1.406
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
274802UNIV PARK;5U
Adder
5.976
274800UNIV PARK;3U
Adder
5.972
274729ELWOOD EC;1P
Adder
16.784
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972159AH1-661 GEN
Adder
1.119
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
971231AH1-075 GEN
Solar/Wind Harmer
0.862
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
970885AG2-551 GEN
Solar/Wind Harmer
2.465
24318805MLG1
50/50
10.098
270475AD2-096_GEN
50/50
7.147
253338AC1-165 GEN
Solar/Wind Harmer
1.242
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270191TR4_S_V150
Solar/Wind Harmer
3.223
959331AF2-224 GEN
Solar/Wind Harmer
10.743
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
270222AC2-111 GEN
Solar/Wind Harmer
8.63
24642205MAYFLWER
Adder
0.665
274753CRETE EC ;3U
Adder
8.485
972038AH1-567 GEN2
Adder
0.374
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.142
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
972239AH1-704 GEN
Adder
2.69
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
945631AF1-228 GEN
Solar/Wind Harmer
5.463
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
270340AC2-060 GEN
Solar/Wind Harmer
3.346
253400AC2-068 GEN
Solar/Wind Harmer
2.174
965041AG1-368 GEN
Solar/Wind Harmer
10.719
966831AG1-554 GEN
Solar/Wind Harmer
1.28
965101AG1-375 GEN
Solar/Wind Harmer
10.618
25196508WSDLE4
Adder
8.994
270297AD1-101 GEN
Solar/Wind Harmer
2.947
274776LINCOLN ;7U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274746AC1-111 G10
Adder
5.685
238152AF2-075_GEN
Solar/Wind Helper
0.708
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.637
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.03
270201AC2-176 GEN
Solar/Wind Harmer
5.449
270459AD2-067 GEN
Solar/Wind Harmer
10.248
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
970879AG2-548 GEN
Solar/Wind Harmer
4.73
270435AC2-044 GEN
Solar/Wind Harmer
2.16
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
24729505KEY G4
Adder
6.925
270071AF1-092 GEN
Solar/Wind Harmer
15.995
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270367AC2-061_GEN
Solar/Wind Harmer
3.378
971673AH1-337 GEN
Solar/Wind Harmer
4.878
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
270543AE2-219 C
Solar/Wind Harmer
5.429
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
942221AE2-234 GEN
Solar/Wind Harmer
0.778
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
972259AH1-714 GEN
Adder
19.527
274696ROCKY RD ;4P
Adder
11.549
274697ROCKY RD ;3P
Adder
3.065
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
232408W1-005 C
Solar/Wind Helper
0.508
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
274695ROCKY RD ;2P
Adder
11.282
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.344
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.052
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.169
20676228FRD_X1-012
Solar/Wind Helper
0.092
970321AG2-212 GEN
Solar/Wind Harmer
3.726
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.233
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274728ELWOOD EC;5P
Adder
16.784
238126S14_GEN_1
Solar/Wind Helper
0.826
237085AD2-009_GEN
Solar/Wind Helper
1.65
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
209116AE2-175 GEN
Solar/Wind Helper
1.781
970153AG2-106 GEN
Solar/Wind Harmer
17.867
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270588AE1-091_GEN
Solar/Wind Harmer
11.792
25194608D.CRK4
Adder
1.742
24728505AND G1
Adder
3.932
274676JOLIET 29;8U
Adder
30.215
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
237080AD1-060 GEN
Solar/Wind Helper
0.342
962771AG1-126 GEN
Solar/Wind Harmer
40.976
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270302AB2-170 GEN
Solar/Wind Harmer
9.546
970179AG2-119 GEN
Solar/Wind Harmer
8.842
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
957201AF2-014 GEN
Solar/Wind Harmer
4.898
971989AH1-539 GEN
Solar/Wind Harmer
13.838
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270024AE2-089 GEN
Solar/Wind Harmer
4.988
252524AE2-267 GEN
Solar/Wind Harmer
1.672
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
966131AG1-482 GEN
Solar/Wind Helper
0.077
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
217208PARK ELE C
Solar/Wind Helper
0.004
274811UNIV PK N;7U
Adder
5.144
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274735ELWOOD EC;4P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.358
960921AF2-383 GEN
Solar/Wind Helper
0.182
205932AD2-116_GEN
Solar/Wind Helper
0.509
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
203975AE1-071-GEN
Solar/Wind Helper
2.5
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.063
270224U2-072_GEN2
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
971201AH1-060 GEN
Solar/Wind Harmer
2.181
942801AE2-298 GEN
Solar/Wind Harmer
1.622
960971AF2-388 GEN
Solar/Wind Harmer
11.621
970883AG2-550 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
8.013
24728905RICHG2
Adder
3.968
274803UNIV PARK;6U
Adder
5.976
274674JOLIET 9 ;6U
Adder
15.72
274693ROCKY RD ;1P
Adder
11.171
23585401KL_K28_T16
Solar/Wind Helper
1.478
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
23559001PLEAS1
50/50
6.112
961921AG1-034 GEN
Solar/Wind Harmer
15.607
942051AE2-217 GEN
Solar/Wind Harmer
21.048
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270273AD2-016 GEN
Solar/Wind Harmer
3.033
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270377AD1-106 GEN
Solar/Wind Harmer
6.655
270247TR4_N_V136
Solar/Wind Harmer
0.914
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
25196608WSDLE5
Adder
9.087
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270404AC1-167 GEN
Solar/Wind Harmer
1.158
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
24728705AND G3
Adder
8.223
274826FISK ;BP
Adder
11.216
972228AH1-698 GEN2
Adder
3.794
274730ELWOOD EC;6P
Adder
16.784
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238127S14_GEN_2
Solar/Wind Helper
0.826
235062AE1-101 C1
Solar/Wind Helper
1.661
223401AF1-299 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.503
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.061
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.573
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
270158DARBY CT3
Adder
10.228
270317AD1-130_GEN
Solar/Wind Harmer
3.659
958581AF2-149 GEN
Solar/Wind Harmer
4.743
253349AC2-067 GEN
Solar/Wind Harmer
5.407
965051AG1-369 GEN
Solar/Wind Harmer
5.365
971985AH1-537 GEN
Solar/Wind Harmer
18.996
971029AG2-637 GEN
Solar/Wind Harmer
15.905
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
944031AF1-071 GEN
Solar/Wind Harmer
1.064
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.045
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
253343AC1-166 GEN
Solar/Wind Harmer
1.242
971995AH1-542 GEN
Solar/Wind Harmer
12.507
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
965421AG1-410 GEN
Solar/Wind Harmer
32.379
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
25194608D.CRK4
Adder
1.742
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274676JOLIET 29;8U
Adder
31.334
274745AC1-111 GEN9
Adder
5.685
316095T157 G97
Solar/Wind Helper
1.505
238185AF2-356 C
Solar/Wind Helper
2.642
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270166AC1-044 GEN3
50/50
7.063
23684101S70BUS1
50/50
0.168
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965011AG1-365 GEN
Solar/Wind Harmer
10.743
958861AF2-177 GEN
Solar/Wind Harmer
11.606
945371AF1-202 GEN
Solar/Wind Harmer
7.39
25196808ZIMRHP
Adder
79.816
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274801UNIV PARK;4U
Adder
5.972
23583801GRNGAP
Solar/Wind Helper
5.607
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.368
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.233
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
274775LINCOLN ;6U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
972037AH1-567 GEN1
Adder
0.188
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
238208AF1-136 C
Solar/Wind Helper
0.22
205943AE1-185 GEN
Solar/Wind Helper
0.51
233990AG1-397 GEN
Solar/Wind Helper
0.03
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
40.976
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270462AD2-086
Solar/Wind Harmer
7.941
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
247536S-71 GEN
Solar/Wind Harmer
4.292
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
274754CRETE EC ;4U
Adder
8.485
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
970245AG2-165 GEN
Solar/Wind Harmer
3.726
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
23559101PLEAS2
50/50
6.112
970149AG2-104 GEN
Solar/Wind Harmer
50.605
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
927014AC1-188 GEN
Solar/Wind Harmer
1.725
960001AF2-291 GEN
Solar/Wind Harmer
3.256
970091AG2-072 GEN
Adder
77.715
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
23562501BACKB
Solar/Wind Helper
1.001
205917AD1-020 ES
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233997TMININ_4.2
Solar/Wind Helper
0.262
233971AC1-093 C
Solar/Wind Helper
0.358
228729W2-030 C
Solar/Wind Helper
0.111
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
NYPJM->LTFIMP_NY
CLTF
4.803
TVALTFEXP_TVA->PJM
CLTF
7.302
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
CPLELTFEXP_CPLE->PJM
CLTF
0.627
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
WECLTFEXP_WEC->PJM
CLTF
3.828
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.918
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:2.69
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
11.821
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
971191AH1-055 GEN
Solar/Wind Harmer
19.26
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270043AE2-236 GEN
Solar/Wind Harmer
4.777
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
945111AF1-176 GEN
Solar/Wind Harmer
5.919
25196008MFTGT1
Adder
1.405
24441205WTRV SLR C
Solar/Wind Harmer
0
970243AG2-164 GEN
Solar/Wind Harmer
4.205
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
274802UNIV PARK;5U
Adder
5.97
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274800UNIV PARK;3U
Adder
5.966
276897AD1-100 C
Solar/Wind Harmer
0.009
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.177
233930AB2-032 GEN
Solar/Wind Helper
0.381
233954AC2-188 GEN
Solar/Wind Helper
0.232
230511AF1-262
Solar/Wind Helper
0.015
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.854
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
253370AE2-315 SEC1
Adder
2.182
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
971613AH1-306 GEN
Solar/Wind Harmer
3.512
965681AG1-436 GEN
Solar/Wind Harmer
9.095
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
238120AE2-309 GEN
Solar/Wind Helper
0.525
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230407AD2-065 C
Solar/Wind Helper
0.04
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
970153AG2-106 GEN
Solar/Wind Harmer
22.046
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270588AE1-091_GEN
Solar/Wind Harmer
5.845
25194608D.CRK4
Adder
1.74
946031AF1-268 GEN
Solar/Wind Harmer
6.992
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
274676JOLIET 29;8U
Adder
30.185
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
274682WAUKEGAN ;7U
Adder
9.728
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
237080AD1-060 GEN
Solar/Wind Helper
0.342
966131AG1-482 GEN
Solar/Wind Helper
0.137
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232434Z2-077 GEN
Solar/Wind Helper
0.127
270120AB2-067 GEN2
50/50
7.059
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
971201AH1-060 GEN
Solar/Wind Harmer
1.52
970627AG2-408 GEN
Solar/Wind Harmer
2.246
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970883AG2-550 GEN
Solar/Wind Harmer
7.389
25194408D.CRK1
Adder
8.004
270599AE1-208 GEN
Solar/Wind Harmer
6.737
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.964
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274803UNIV PARK;6U
Adder
5.97
274887GEN-1.85
Solar/Wind Harmer
0.188
274674JOLIET 9 ;6U
Adder
15.704
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
274693ROCKY RD ;1P
Adder
11.16
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237006AB1-125 GEN
Solar/Wind Helper
0.123
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
232424Y1-079 C
Solar/Wind Helper
0.116
233970AC1-092 C
Solar/Wind Helper
0.35
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.074
23559001PLEAS1
50/50
6.1
961921AG1-034 GEN
Solar/Wind Harmer
7.615
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.821
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.563
270377AD1-106 GEN
Solar/Wind Harmer
2.855
270247TR4_N_V136
Solar/Wind Harmer
0.048
944531AF1-118 GEN
Solar/Wind Harmer
33.395
25196608WSDLE5
Adder
9.077
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.433
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
24728705AND G3
Adder
8.214
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
970879AG2-548 GEN
Solar/Wind Harmer
6.898
270435AC2-044 GEN
Solar/Wind Harmer
0.953
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.804
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
8.194
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971769AH1-391 GEN
Solar/Wind Harmer
8.134
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.768
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.827
237085AD2-009_GEN
Solar/Wind Helper
1.649
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.117
970179AG2-119 GEN
Solar/Wind Harmer
6.883
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.389
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
5.139
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
274735ELWOOD EC;4P
Adder
16.768
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
959381AF2-229 GEN
Solar/Wind Helper
0.357
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.906
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
965421AG1-410 GEN
Solar/Wind Harmer
22.57
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
25194608D.CRK4
Adder
1.74
970947AG2-589 GEN
Solar/Wind Harmer
0.245
965031AG1-367 GEN
Solar/Wind Harmer
7.338
970613AG2-401 GEN
Solar/Wind Harmer
5.378
24639705ELKHART HY
Adder
0.161
970291AG2-192 GEN
Solar/Wind Harmer
0.95
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274676JOLIET 29;8U
Adder
31.303
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.679
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
238185AF2-356 C
Solar/Wind Helper
2.646
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
227287AC2-120 GEN
Solar/Wind Helper
0.346
233996TM1833_GEN
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.063
20714528FRN_Y2-051
Solar/Wind Helper
0.057
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
219904AC1-010 C
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
217208PARK ELE C
Solar/Wind Helper
0.004
270166AC1-044 GEN3
50/50
7.059
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965011AG1-365 GEN
Solar/Wind Harmer
7.488
958861AF2-177 GEN
Solar/Wind Harmer
3.207
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.59
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.877
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.966
23583801GRNGAP
Solar/Wind Helper
5.601
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.274
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.367
233982AB2-133 GEN
Solar/Wind Helper
0.358
233940AF2-379 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.232
270119AB2-067 GEN1
50/50
7.059
970077AG2-063 GEN
Solar/Wind Harmer
4.631
972269AH1-719 GEN
Adder
2.584
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.451
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
970611AG2-400 GEN
Solar/Wind Harmer
7.488
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
970621AG2-405 GEN
Solar/Wind Harmer
1.351
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
274808UNIV PK N;4U
Adder
5.117
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
972259AH1-714 GEN
Adder
19.507
970241AG2-163 GEN
Solar/Wind Harmer
4.144
274696ROCKY RD ;4P
Adder
11.537
274697ROCKY RD ;3P
Adder
3.062
238175AF1-290_GEN
Solar/Wind Helper
0.153
235020AA1-095 C
Solar/Wind Helper
0.053
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
233946AB2-136 GEN
Solar/Wind Helper
0.568
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20716928W4-060COL
Solar/Wind Helper
0.051
20673828FLE_V3-070
Solar/Wind Helper
0.09
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.092
230434AG1-499 GEN
Solar/Wind Helper
0.23
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
971997AH1-543 GEN
Solar/Wind Harmer
2.724
274826FISK ;BP
Adder
11.205
972228AH1-698 GEN2
Adder
3.79
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274730ELWOOD EC;6P
Adder
16.768
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238127S14_GEN_2
Solar/Wind Helper
0.827
235062AE1-101 C1
Solar/Wind Helper
1.659
223401AF1-299 GEN
Solar/Wind Helper
0.367
233915AB1-141 GEN
Solar/Wind Helper
0.502
232428Y3-058 C
Solar/Wind Helper
0.338
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
10.218
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.381
965051AG1-369 GEN
Solar/Wind Harmer
3.739
971985AH1-537 GEN
Solar/Wind Harmer
2.206
971029AG2-637 GEN
Solar/Wind Harmer
11.085
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
11.025
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.285
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
276868AE1-113 GEN
Solar/Wind Harmer
1.414
238208AF1-136 C
Solar/Wind Helper
0.22
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
316254AC1-120 GEN1
Solar/Wind Helper
1.059
963711AG1-223 GEN
Solar/Wind Helper
0.064
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.571
962761AG1-125 GEN
Solar/Wind Harmer
34.524
270462AD2-086
Solar/Wind Harmer
0.017
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
247536S-71 GEN
Solar/Wind Harmer
0.297
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
944231AF1-091 GEN
Solar/Wind Harmer
1.953
276903AD2-071 C
Solar/Wind Harmer
8.137
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.477
24385905FR-11G C
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
939401AE1-172 GEN
Solar/Wind Harmer
5.301
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
235067AD1-061 GEN
Solar/Wind Helper
0.496
234015AF2-250 C
Solar/Wind Helper
0.038
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
219276PARKLANDSO C
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
942861AE2-305 GEN
Solar/Wind Harmer
6.335
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972159AH1-661 GEN
Adder
1.118
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
971231AH1-075 GEN
Solar/Wind Harmer
0.861
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.496
964611AG1-324 GEN
Solar/Wind Harmer
0.553
24318805MLG1
50/50
10.095
270475AD2-096_GEN
50/50
7.141
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.952
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.242
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
270222AC2-111 GEN
Solar/Wind Harmer
3.739
270004AE1-209 GEN
Solar/Wind Harmer
1.59
24642205MAYFLWER
Adder
0.665
270356AE2-297 GEN
Solar/Wind Harmer
0.01
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
274753CRETE EC ;3U
Adder
8.477
972038AH1-567 GEN2
Adder
0.373
238118U2-030_1
Solar/Wind Helper
0.341
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237038AE2-054 C
Solar/Wind Helper
0.272
23779801AA1-109
Solar/Wind Helper
0.193
316006AB2-029 C
Solar/Wind Helper
0.117
316045AC1-158 PL2
Solar/Wind Helper
4.138
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
207445AB1-138_GEN
Solar/Wind Helper
0.104
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
23559101PLEAS2
50/50
6.1
970149AG2-104 GEN
Solar/Wind Harmer
37.287
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
927014AC1-188 GEN
Solar/Wind Harmer
0.005
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.805
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
23562501BACKB
Solar/Wind Helper
1.007
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233994AC2-023 GEN
Solar/Wind Helper
0.961
233997TMININ_4.2
Solar/Wind Helper
0.261
233971AC1-093 C
Solar/Wind Helper
0.357
228729W2-030 C
Solar/Wind Helper
0.11
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
252509AD1-136 GEN
Solar/Wind Harmer
0.037
270031AE2-169
Solar/Wind Harmer
4.042
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
24728805RICHG1
Adder
3.964
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274695ROCKY RD ;2P
Adder
11.271
958491AF2-143 GEN
Solar/Wind Harmer
10.588
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
226929AD2-058 GEN
Solar/Wind Helper
0.099
233987AB2-037 GEN
Solar/Wind Helper
2.342
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.232
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
3141426STAFORD
Solar/Wind Helper
0.052
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.025
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.778
960921AF2-383 GEN
Solar/Wind Helper
0.364
205932AD2-116_GEN
Solar/Wind Helper
0.509
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
203975AE1-071-GEN
Solar/Wind Helper
2.498
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
205943AE1-185 GEN
Solar/Wind Helper
0.509
233990AG1-397 GEN
Solar/Wind Helper
0.27
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
972239AH1-704 GEN
Adder
2.689
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.958
965041AG1-368 GEN
Solar/Wind Harmer
7.471
965101AG1-375 GEN
Solar/Wind Harmer
7.401
25196508WSDLE4
Adder
8.984
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274746AC1-111 G10
Adder
5.679
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238152AF2-075_GEN
Solar/Wind Helper
0.707
23546401DTGZ2-030
Solar/Wind Helper
0.089
3138216PACIFIC
Solar/Wind Helper
0.044
23750501ELLIOTTS
Solar/Wind Helper
0.638
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
219914AD2-027 C
Solar/Wind Helper
0.115
219607WPEMNERT C
Solar/Wind Helper
0.08
20715728PEM_W1-119
Solar/Wind Helper
0.096
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
WECLTFEXP_WEC->PJM
CLTF
3.825
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LGEELTFEXP_LGEE->PJM
CLTF
6.749
MECLTFEXP_MEC->PJM
CLTF
15.901
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
NYPJM->LTFIMP_NY
CLTF
4.797
TVALTFEXP_TVA->PJM
CLTF
7.293
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
CPLELTFEXP_CPLE->PJM
CLTF
0.624
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:3.1
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
11.999
960801AF2-371 GEN
Solar/Wind Harmer
2.991
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
276820AF1-078_GEN
Solar/Wind Harmer
1.815
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
253370AE2-315 SEC1
Adder
2.206
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
247621Y3-024
Adder
0.259
970935AG2-582 GEN
Adder
239.406
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
971995AH1-542 GEN
Solar/Wind Harmer
12.974
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
965421AG1-410 GEN
Solar/Wind Harmer
33.256
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
24695305TIMB G C
Solar/Wind Harmer
6.051
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
965651AG1-433 GEN
Solar/Wind Harmer
5.885
970153AG2-106 GEN
Solar/Wind Harmer
17.863
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
24721905FLATG4
Adder
23.506
270588AE1-091_GEN
Solar/Wind Harmer
12.311
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
25194608D.CRK4
Adder
1.752
23906502RICHG2&3
Adder
1.272
274676JOLIET 29;8U
Adder
30.573
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
237080AD1-060 GEN
Solar/Wind Helper
0.367
966131AG1-482 GEN
Solar/Wind Helper
0.079
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
232434Z2-077 GEN
Solar/Wind Helper
0.129
316192AB2-158 GEN
Solar/Wind Helper
1.608
219904AC1-010 C
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.057
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
217208PARK ELE C
Solar/Wind Helper
0.004
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
23906502RICHG2&3
Adder
1.272
23906402RICHG1
Adder
1.271
274812UNIV PK N;8U
Adder
5.21
274676JOLIET 29;8U
Adder
31.706
316095T157 G97
Solar/Wind Helper
1.705
238185AF2-356 C
Solar/Wind Helper
2.767
237030AB1-096 C
Solar/Wind Helper
0.075
227287AC2-120 GEN
Solar/Wind Helper
0.375
23751101LEADS_P59
Solar/Wind Helper
1.316
233996TM1833_GEN
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
966881AG1-559 GEN
Solar/Wind Helper
0.312
218438BLK ROCK C
Solar/Wind Helper
0.027
219919AE1-041 FULL
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.089
270119AB2-067 GEN1
50/50
7.033
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
253378AE2-206_GEN
Solar/Wind Harmer
4.086
25326509SID D
Adder
1.48
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
270007AE1-245 C
Solar/Wind Harmer
6.539
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
942221AE2-234 GEN
Solar/Wind Harmer
0.79
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
235020AA1-095 C
Solar/Wind Helper
0.057
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
233933AB2-153 GEN
Solar/Wind Helper
0.236
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20716928W4-060COL
Solar/Wind Helper
0.052
964871AG1-351 GEN
Solar/Wind Harmer
2.065
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
970065AG2-057 GEN
Solar/Wind Harmer
1.148
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270044AE2-322 C
Solar/Wind Harmer
1.435
270043AE2-236 GEN
Solar/Wind Harmer
5.98
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196008MFTGT1
Adder
1.413
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274800UNIV PARK;3U
Adder
6.045
274729ELWOOD EC;1P
Adder
16.983
237048AF1-022 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.387
233954AC2-188 GEN
Solar/Wind Helper
0.236
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219907AC1-030 C
Solar/Wind Helper
0.034
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.137
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.033
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
247522W1-056 GEN
Solar/Wind Harmer
2.477
965011AG1-365 GEN
Solar/Wind Harmer
10.972
958861AF2-177 GEN
Solar/Wind Harmer
11.752
945371AF1-202 GEN
Solar/Wind Harmer
7.479
25196808ZIMRHP
Adder
80.188
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274801UNIV PARK;4U
Adder
6.045
23583801GRNGAP
Solar/Wind Helper
6.365
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
238221AF1-254 C O1
Solar/Wind Helper
0.295
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
226910AB2-157 C
Solar/Wind Helper
0.015
223402AF1-300 C
Solar/Wind Helper
0.387
233982AB2-133 GEN
Solar/Wind Helper
0.364
233940AF2-379 C
Solar/Wind Helper
0.063
233952AC2-187 GEN
Solar/Wind Helper
0.236
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.019
219612MATRIX C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.074
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
23559001PLEAS1
50/50
5.443
961921AG1-034 GEN
Solar/Wind Harmer
15.919
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
970605AG2-385 GEN
Solar/Wind Harmer
6.332
253333AC1-068 GEN
Solar/Wind Harmer
1.211
270273AD2-016 GEN
Solar/Wind Harmer
3.061
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
958091AF2-103 GEN
Solar/Wind Harmer
0.178
270247TR4_N_V136
Solar/Wind Harmer
0.936
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
270158DARBY CT3
Adder
10.362
270317AD1-130_GEN
Solar/Wind Harmer
3.759
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
944531AF1-118 GEN
Solar/Wind Harmer
37.943
970031AG2-029 GEN
Solar/Wind Harmer
32.394
270541AE2-072 C
Solar/Wind Harmer
4.881
25196608WSDLE5
Adder
9.143
247604X1-042
Adder
0.444
274752CRETE EC ;2U
Adder
8.598
274826FISK ;BP
Adder
11.355
972228AH1-698 GEN2
Adder
3.84
274730ELWOOD EC;6P
Adder
16.983
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238127S14_GEN_2
Solar/Wind Helper
0.867
235062AE1-101 C1
Solar/Wind Helper
1.776
223401AF1-299 GEN
Solar/Wind Helper
0.387
316254AC1-120 GEN1
Solar/Wind Helper
1.184
233915AB1-141 GEN
Solar/Wind Helper
0.511
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
228728W1-130C
Solar/Wind Helper
0.054
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20675428EAM_W2-061
Solar/Wind Helper
0.016
207518AF1-320_GEN
Solar/Wind Helper
1.568
962761AG1-125 GEN
Solar/Wind Harmer
40.965
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270462AD2-086
Solar/Wind Harmer
8.157
241813AF1-122_GEN
Solar/Wind Harmer
7.346
241847AF2-150_GEN
Solar/Wind Harmer
4.622
25326309TAIT D
Adder
1.21
944231AF1-091 GEN
Solar/Wind Harmer
4.078
270063AE2-323 C
Solar/Wind Harmer
2.376
247536S-71 GEN
Solar/Wind Harmer
4.346
972301AH1-735 GEN
Adder
6.357
274754CRETE EC ;4U
Adder
8.598
274732ELWOOD EC;7P
Adder
2.004
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238117U2-030
Solar/Wind Helper
0.356
235067AD1-061 GEN
Solar/Wind Helper
0.532
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
3147666LOUISA
Solar/Wind Helper
0.551
234015AF2-250 C
Solar/Wind Helper
0.039
219276PARKLANDSO C
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.028
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
24318805MLG1
50/50
10.022
253338AC1-165 GEN
Solar/Wind Harmer
1.256
972173AH1-669 GEN
Solar/Wind Harmer
5.721
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
270191TR4_S_V150
Solar/Wind Harmer
3.3
959331AF2-224 GEN
Solar/Wind Harmer
10.972
270258AD1-119 GEN
Solar/Wind Harmer
3.051
971617AH1-308 GEN
Solar/Wind Harmer
6.274
24642205MAYFLWER
Adder
0.678
274753CRETE EC ;3U
Adder
8.598
972038AH1-567 GEN2
Adder
0.378
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
970149AG2-104 GEN
Solar/Wind Harmer
50.592
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
253325AC1-069 GEN
Solar/Wind Harmer
1.211
270263AC1-001 GEN
Solar/Wind Harmer
1.187
970515AG2-329 GEN
Solar/Wind Harmer
16.033
927014AC1-188 GEN
Solar/Wind Harmer
1.729
960001AF2-291 GEN
Solar/Wind Harmer
3.244
23920202STRYCT
Adder
1.444
238108AE1-109 GEN1
Solar/Wind Helper
0.121
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
23562501BACKB
Solar/Wind Helper
0.997
316170AC1-121 GEN2
Solar/Wind Helper
0.395
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233994AC2-023 GEN
Solar/Wind Helper
0.977
233997TMININ_4.2
Solar/Wind Helper
0.266
233971AC1-093 C
Solar/Wind Helper
0.363
228729W2-030 C
Solar/Wind Helper
0.112
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715028HAN_X4-015
Solar/Wind Helper
0.057
219249CENTRALDIV C
Solar/Wind Helper
0.01
217211CAMDEN ST C
Solar/Wind Helper
0.005
946101AF1-275 GEN
Solar/Wind Harmer
1.842
942861AE2-305 GEN
Solar/Wind Harmer
9.223
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326109MON D
Adder
1.461
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
944541AF1-119 GEN
Solar/Wind Harmer
4.511
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
20673828FLE_V3-070
Solar/Wind Helper
0.091
20676128MHD_W3-029
Solar/Wind Helper
0.096
217081WEATEXAS C
Solar/Wind Helper
0.013
207471AF2-354 C
Solar/Wind Helper
0.168
20676228FRD_X1-012
Solar/Wind Helper
0.091
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
230407AD2-065 C
Solar/Wind Helper
0.041
20714928UPF_X1-085
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
964851AG1-348 GEN
Solar/Wind Helper
0.081
270459AD2-067 GEN
Solar/Wind Harmer
10.453
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
971567AH1-282 GEN
Solar/Wind Harmer
16.984
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
958711AF2-162 GEN
Solar/Wind Harmer
1.089
270543AE2-219 C
Solar/Wind Harmer
5.494
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274728ELWOOD EC;5P
Adder
16.983
238126S14_GEN_1
Solar/Wind Helper
0.867
237085AD2-009_GEN
Solar/Wind Helper
1.767
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
209116AE2-175 GEN
Solar/Wind Helper
1.768
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
270302AB2-170 GEN
Solar/Wind Harmer
9.805
970689AG2-444 GEN
Solar/Wind Harmer
19.055
970179AG2-119 GEN
Solar/Wind Harmer
9.26
971989AH1-539 GEN
Solar/Wind Harmer
14.49
957201AF2-014 GEN
Solar/Wind Harmer
5.033
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
25306009OHH W.
Adder
3.166
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270024AE2-089 GEN
Solar/Wind Harmer
5.065
274811UNIV PK N;7U
Adder
5.21
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274735ELWOOD EC;4P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205932AD2-116_GEN
Solar/Wind Helper
0.518
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
203975AE1-071-GEN
Solar/Wind Helper
2.53
966261AG1-495 GEN
Solar/Wind Helper
0.081
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
270120AB2-067 GEN2
50/50
7.033
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
971201AH1-060 GEN
Solar/Wind Harmer
2.296
942801AE2-298 GEN
Solar/Wind Harmer
1.667
960971AF2-388 GEN
Solar/Wind Harmer
11.771
970883AG2-550 GEN
Solar/Wind Harmer
10.73
25194408D.CRK1
Adder
8.061
24728905RICHG2
Adder
4.003
274803UNIV PARK;6U
Adder
6.05
23585401KL_K28_T16
Solar/Wind Helper
1.529
23777901MDS_W4-102
Solar/Wind Helper
0.191
237002AB1-128_GEN
Solar/Wind Helper
0.475
237006AB1-125 GEN
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
232424Y1-079 C
Solar/Wind Helper
0.118
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.098
966111AG1-480 GEN
Solar/Wind Helper
0.044
958581AF2-149 GEN
Solar/Wind Harmer
4.968
965051AG1-369 GEN
Solar/Wind Harmer
5.494
253349AC2-067 GEN
Solar/Wind Harmer
5.466
945641AF1-229 GEN
Solar/Wind Harmer
3.923
961761AG1-017 GEN
Solar/Wind Harmer
0.46
971029AG2-637 GEN
Solar/Wind Harmer
16.089
274775LINCOLN ;6U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
972037AH1-567 GEN1
Adder
0.19
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
238208AF1-136 C
Solar/Wind Helper
0.236
205943AE1-185 GEN
Solar/Wind Helper
0.518
233990AG1-397 GEN
Solar/Wind Helper
0.031
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
20676328BVR_Y1-020
Solar/Wind Helper
0.027
945581AF1-223 GEN
Solar/Wind Harmer
0.763
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
237034AC2-136 C
Solar/Wind Helper
0.244
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
226929AD2-058 GEN
Solar/Wind Helper
0.108
233987AB2-037 GEN
Solar/Wind Helper
2.381
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
20720628TIN_W1-124
Solar/Wind Helper
0.19
207442AE1-156 GEN
Solar/Wind Helper
0.326
20671828STAW2-080
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.15
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.356
237038AE2-054 C
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
316045AC1-158 PL2
Solar/Wind Helper
4.618
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
207445AB1-138_GEN
Solar/Wind Helper
0.105
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
972239AH1-704 GEN
50/50
3.102
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270432AC2-029 GEN
Solar/Wind Harmer
8.138
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
966831AG1-554 GEN
Solar/Wind Harmer
1.34
270340AC2-060 GEN
Solar/Wind Harmer
3.371
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253400AC2-068 GEN
Solar/Wind Harmer
2.198
965101AG1-375 GEN
Solar/Wind Harmer
10.752
211065PSPA IPP
Solar/Wind Helper
0.15
25196508WSDLE4
Adder
9.049
274776LINCOLN ;7U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
219914AD2-027 C
Solar/Wind Helper
0.116
219607WPEMNERT C
Solar/Wind Helper
0.081
20715728PEM_W1-119
Solar/Wind Helper
0.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
207530AG1-191 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.029
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
WECLTFEXP_WEC->PJM
CLTF
3.866
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LGEELTFEXP_LGEE->PJM
CLTF
6.753
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
NYPJM->LTFIMP_NY
CLTF
4.554
MECLTFEXP_MEC->PJM
CLTF
15.979
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:2.78
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.758
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970935AG2-582 GEN
Adder
242.403
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
247621Y3-024
Adder
0.246
971613AH1-306 GEN
Solar/Wind Harmer
3.385
965681AG1-436 GEN
Solar/Wind Harmer
8.77
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971677AH1-339 GEN
Solar/Wind Harmer
0.768
270120AB2-067 GEN2
50/50
6.869
270224U2-072_GEN2
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
971201AH1-060 GEN
Solar/Wind Harmer
1.471
970627AG2-408 GEN
Solar/Wind Harmer
2.167
960971AF2-388 GEN
Solar/Wind Harmer
4.192
970883AG2-550 GEN
Solar/Wind Harmer
7.123
25194408D.CRK1
Adder
7.711
270599AE1-208 GEN
Solar/Wind Harmer
6.495
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270216AD2-079_GEN
Solar/Wind Harmer
0.001
24728905RICHG2
Adder
3.82
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274887GEN-1.85
Solar/Wind Harmer
0.181
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
274879MINONK ;1U
Solar/Wind Harmer
0.287
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
253343AC1-166 GEN
Solar/Wind Harmer
0.003
971995AH1-542 GEN
Solar/Wind Harmer
2.81
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
25194608D.CRK4
Adder
1.676
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
970613AG2-401 GEN
Solar/Wind Harmer
5.183
24639705ELKHART HY
Adder
0.155
970291AG2-192 GEN
Solar/Wind Harmer
0.916
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.005
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
238185AF2-356 C
Solar/Wind Helper
2.425
970153AG2-106 GEN
Solar/Wind Harmer
21.245
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
24721905FLATG4
Adder
22.865
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
270588AE1-091_GEN
Solar/Wind Harmer
5.649
25194608D.CRK4
Adder
1.676
946031AF1-268 GEN
Solar/Wind Harmer
6.74
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.901
24728505AND G1
Adder
3.784
274676JOLIET 29;8U
Adder
29.097
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
237080AD1-060 GEN
Solar/Wind Helper
0.33
966131AG1-482 GEN
Solar/Wind Helper
0.132
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.123
219904AC1-010 C
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.055
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
237030AB1-096 C
Solar/Wind Helper
0.068
227287AC2-120 GEN
Solar/Wind Helper
0.335
233996TM1833_GEN
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714528FRN_Y2-051
Solar/Wind Helper
0.055
270119AB2-067 GEN1
50/50
6.869
970077AG2-063 GEN
Solar/Wind Harmer
4.471
972269AH1-719 GEN
Adder
2.501
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.4
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
970611AG2-400 GEN
Solar/Wind Harmer
7.225
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.036
970621AG2-405 GEN
Solar/Wind Harmer
1.305
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
957891AF2-083 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
972259AH1-714 GEN
Adder
18.805
970241AG2-163 GEN
Solar/Wind Harmer
3.993
238175AF1-290_GEN
Solar/Wind Helper
0.148
235020AA1-095 C
Solar/Wind Helper
0.051
270051AF1-062 GEN
50/50
11.434
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
970065AG2-057 GEN
Solar/Wind Harmer
0.735
965021AG1-366 GEN
Solar/Wind Harmer
2.408
971191AH1-055 GEN
Solar/Wind Harmer
18.515
270043AE2-236 GEN
Solar/Wind Harmer
4.607
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
252510AF1-249 C
Solar/Wind Harmer
0.055
945111AF1-176 GEN
Solar/Wind Harmer
5.709
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
970243AG2-164 GEN
Solar/Wind Harmer
4.047
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
274802UNIV PARK;5U
Adder
5.755
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274800UNIV PARK;3U
Adder
5.751
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
274729ELWOOD EC;1P
Adder
16.163
276893AG1-478 C
Solar/Wind Harmer
0.272
276805AD2-038 GEN
Solar/Wind Harmer
0.002
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233954AC2-188 GEN
Solar/Wind Helper
0.225
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219907AC1-030 C
Solar/Wind Helper
0.033
270166AC1-044 GEN3
50/50
6.869
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965011AG1-365 GEN
Solar/Wind Harmer
7.225
958861AF2-177 GEN
Solar/Wind Harmer
3.092
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.532
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.509
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
247522W1-056 GEN
Solar/Wind Harmer
0.001
25196008MFTGT1
Adder
1.397
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
24387305FR-4G C
Solar/Wind Harmer
0.003
274801UNIV PARK;4U
Adder
5.751
23583801GRNGAP
Solar/Wind Helper
5.418
238149AF1-291A_GEN
Solar/Wind Helper
0.137
237061AD1-155 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.265
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
233982AB2-133 GEN
Solar/Wind Helper
0.346
233940AF2-379 C
Solar/Wind Helper
0.06
233952AC2-187 GEN
Solar/Wind Helper
0.225
219623KINSLEYBEA C
Solar/Wind Helper
0.002
20716028EGP_W2-019
Solar/Wind Helper
0.018
971997AH1-543 GEN
Solar/Wind Harmer
1.86
23559001PLEAS1
50/50
5.385
961921AG1-034 GEN
Solar/Wind Harmer
7.364
942051AE2-217 GEN
Solar/Wind Harmer
14.169
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.792
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
970031AG2-029 GEN
Solar/Wind Harmer
4.625
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270437AC2-090 C
Solar/Wind Harmer
0.003
247604X1-042
Adder
0.418
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
972228AH1-698 GEN2
Adder
3.654
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274730ELWOOD EC;6P
Adder
13.491
270541AE2-072 C
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238127S14_GEN_2
Solar/Wind Helper
0.766
235062AE1-101 C1
Solar/Wind Helper
1.6
223401AF1-299 GEN
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.486
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
228728W1-130C
Solar/Wind Helper
0.052
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
316254AC1-120 GEN1
Solar/Wind Helper
1.026
963711AG1-223 GEN
Solar/Wind Helper
0.062
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
962761AG1-125 GEN
Solar/Wind Harmer
33.269
270462AD2-086
Solar/Wind Harmer
0.016
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
247536S-71 GEN
Solar/Wind Harmer
0.287
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
276903AD2-071 C
Solar/Wind Harmer
7.842
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.172
24385905FR-11G C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
5.109
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238117U2-030
Solar/Wind Helper
0.314
235067AD1-061 GEN
Solar/Wind Helper
0.478
234015AF2-250 C
Solar/Wind Helper
0.037
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
219276PARKLANDSO C
Solar/Wind Helper
0.086
20720528MAN_W1-024
Solar/Wind Helper
0.027
24318805MLG1
50/50
9.842
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.811
970191AG2-125 GEN
Solar/Wind Harmer
1.876
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.057
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
270222AC2-111 GEN
Solar/Wind Harmer
3.603
270004AE1-209 GEN
Solar/Wind Harmer
1.532
24642205MAYFLWER
Adder
0.641
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274753CRETE EC ;3U
Adder
8.172
972038AH1-567 GEN2
Adder
0.36
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238118U2-030_1
Solar/Wind Helper
0.314
237038AE2-054 C
Solar/Wind Helper
0.262
23779801AA1-109
Solar/Wind Helper
0.187
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.009
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
207445AB1-138_GEN
Solar/Wind Helper
0.101
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
970149AG2-104 GEN
Solar/Wind Harmer
35.932
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
927014AC1-188 GEN
Solar/Wind Harmer
0.004
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.67
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
971917AH1-482 GEN
Solar/Wind Harmer
9.071
24791305MDL-5G
Solar/Wind Harmer
0.001
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
238108AE1-109 GEN1
Solar/Wind Helper
0.106
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233997TMININ_4.2
Solar/Wind Helper
0.253
233971AC1-093 C
Solar/Wind Helper
0.346
228729W2-030 C
Solar/Wind Helper
0.107
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715028HAN_X4-015
Solar/Wind Helper
0.055
942861AE2-305 GEN
Solar/Wind Harmer
6.118
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972159AH1-661 GEN
Adder
1.082
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971231AH1-075 GEN
Solar/Wind Harmer
0.833
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
7.065
24728805RICHG1
Adder
3.82
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.271
958491AF2-143 GEN
Solar/Wind Harmer
10.205
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230407AD2-065 C
Solar/Wind Helper
0.039
20714928UPF_X1-085
Solar/Wind Helper
0.005
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
970879AG2-548 GEN
Solar/Wind Harmer
6.645
270435AC2-044 GEN
Solar/Wind Harmer
0.92
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
270543AE2-219 C
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
971769AH1-391 GEN
Solar/Wind Harmer
7.844
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24691005MDL-2G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
16.163
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
3141426STAFORD
Solar/Wind Helper
0.051
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270302AB2-170 GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
1.08
970179AG2-119 GEN
Solar/Wind Harmer
6.658
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
957201AF2-014 GEN
Solar/Wind Harmer
0.001
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
270024AE2-089 GEN
Solar/Wind Harmer
0.008
252524AE2-267 GEN
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
1.339
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.954
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
274735ELWOOD EC;4P
Adder
16.163
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
959381AF2-229 GEN
Solar/Wind Helper
0.345
960921AF2-383 GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.492
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
203975AE1-071-GEN
Solar/Wind Helper
2.41
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237002AB1-128_GEN
Solar/Wind Helper
0.427
237006AB1-125 GEN
Solar/Wind Helper
0.119
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
232424Y1-079 C
Solar/Wind Helper
0.112
233970AC1-092 C
Solar/Wind Helper
0.338
230433AD2-135 GEN
Solar/Wind Helper
0.016
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270158DARBY CT3
Adder
9.866
270317AD1-130_GEN
Solar/Wind Harmer
0.011
253349AC2-067 GEN
Solar/Wind Harmer
2.296
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971985AH1-537 GEN
Solar/Wind Harmer
2.123
971029AG2-637 GEN
Solar/Wind Harmer
10.686
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
3.169
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
24386405FR-21G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972165AH1-665 GEN
Solar/Wind Harmer
6.118
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.363
238208AF1-136 C
Solar/Wind Helper
0.211
205943AE1-185 GEN
Solar/Wind Helper
0.492
233990AG1-397 GEN
Solar/Wind Helper
0.261
964001AG1-254 GEN
Solar/Wind Helper
0.924
227927V4-067C
Solar/Wind Helper
0.01
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
214067T20SOLAR
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
219620RIDERU C
Solar/Wind Helper
0.001
237034AC2-136 C
Solar/Wind Helper
0.219
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
226929AD2-058 GEN
Solar/Wind Helper
0.096
233987AB2-037 GEN
Solar/Wind Helper
2.264
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
20720628TIN_W1-124
Solar/Wind Helper
0.183
972239AH1-704 GEN
50/50
2.78
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
270432AC2-029 GEN
Solar/Wind Harmer
3.428
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
270340AC2-060 GEN
Solar/Wind Harmer
0.009
253400AC2-068 GEN
Solar/Wind Harmer
0.923
965041AG1-368 GEN
Solar/Wind Harmer
7.21
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
25196508WSDLE4
Adder
8.656
971609AH1-304 GEN
Solar/Wind Harmer
1.157
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
24386205FR-12G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
972163AH1-664 GEN
Solar/Wind Harmer
7.639
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
3138216PACIFIC
Solar/Wind Helper
0.043
23750501ELLIOTTS
Solar/Wind Helper
0.571
205956AE1-196_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
219914AD2-027 C
Solar/Wind Helper
0.111
219607WPEMNERT C
Solar/Wind Helper
0.077
20715728PEM_W1-119
Solar/Wind Helper
0.093
316164AC1-076 GEN
Solar/Wind Helper
1.062
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
WECLTFEXP_WEC->PJM
CLTF
3.686
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LGEELTFEXP_LGEE->PJM
CLTF
6.497
MECLTFEXP_MEC->PJM
CLTF
15.319
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
NYPJM->LTFIMP_NY
CLTF
4.628
TVALTFEXP_TVA->PJM
CLTF
7.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
CPLELTFEXP_CPLE->PJM
CLTF
0.567
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
235117 to 235111 ckt 1
242925 to 235117 ckt 1

Winter Peak Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW (20.0 MW Capacity) injection in the AEP area.

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW injection

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-245Haviland 138 kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AF1-007Indian River 230 kV ISuspended
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-396Stinger 138 kVActive
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-047Jay 138 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-375Sorenson-Desoto 345 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-153Dumont 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-339West Crawford 69 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X1-042WatervlietIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

Attachments

AH1-704 One Line Diagram

AH1-704 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.