AH1-746 Phase I Study Report

v1.00 released 2025-10-29 20:01

Madera - Westover South 115 kV

20.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is CPV Rogue's Wind, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Mid-Atlantic Interstate Transmission, LLC.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Wind facility located in the Mid-Atlantic Interstate Transmission, LLC zone — Clearfield County, Pennsylvania. This project is an increase to the developer’s AF1-086 project(s), which will share the same Point of Interconnection. The AH1-746 project is a 20.0 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 109.9 MW with 40.54 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-746
Project Name:
Madera - Westover South 115 kV
Project Developer Name:
CPV Rogue's Wind, LLC
State:
Pennsylvania
County:
Clearfield
Transmission Owner:
Mid-Atlantic Interstate Transmission, LLC
MFO:
109.9
MWE:
0.0
MWC:
20.0
Fuel Type:
Wind
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-746 will interconnect on the Mid-Atlantic Interstate Transmission, LLC transmission system by tapping the Madera - Westover South 115 kV line as a CIR only uprate to AF1-086.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-746 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-746Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-746

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-746 Project due at DP1
ABA - B
AH1-746$0$80,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AH1-746 did not contribute to any overloads on the FE transmission <100 kV system.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Wind speed (meters/second) - (Required)
  • Wind direction (decimal degrees from true north) - (Required)
  • Ambient air temperature (Fahrenheit) - (Required)
  • Air Pressure (Hectopascals) - (Required)
  • Humidity (Percent) - (Accepted, not required)
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-746 was evaluated as a 0.0 MW (20.0 MW Capacity) injection in the PENELEC area.

AH1-746 was evaluated as part of a plant. The plant consists of AH1-746. The total Energy output of the plant was evaluated at its maximum seasonal capability of 109.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P1-2_WP-500-008_SRT-A
SingleAC122.67 %192.0B235.521.21
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Base Case
SingleAC118.68 %160.0A189.881.07
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P1-2_WP-138-056_SRT-A
SingleAC113.79 %192.0B218.471.37
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P1-2_PN-230-020A_SRT-A
SingleAC113.22 %612.0B692.912.58
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Base Case
SingleAC111.67 %512.0A571.732.39
GD2AP/PENELEC
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
PN_P1-2_PN-230-019_SRT-A
SingleAC111.12 %612.0B680.042.52
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P1-2_WP-500-008_SRT-A
SingleAC126.74 %192.0B243.341.21
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Base Case
SingleAC122.86 %160.0A196.571.07
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P1-2_WP-138-056_SRT-A
SingleAC117.96 %192.0B226.471.37
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC105.44 %980.0B1033.273.44
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC105.43 %980.0B1033.253.44
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Base Case
SingleAC100.25 %809.0A811.022.07
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Base Case
SingleAC131.72 %493.0A649.42.59
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P1-2_PN-115-094_A_SRT-A
SingleAC127.45 %618.0B787.652.88
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P12_000085_SRT-A
SingleAC127.27 %618.0B786.52.66
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P1-2_WP-230-005A_SRT-A
SingleAC105.13 %587.0B617.142.06
GD2AP/PENELEC
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
AP_P1-3_WP-230-005_SRT-A
SingleAC105.12 %587.0B617.052.06
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC104.25 %980.0B1021.655.8
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC104.25 %980.0B1021.635.8

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P1-2_WP-500-008_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-500-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.67 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:235.52
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.362
203940AF1-140 C
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
4.556
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.699
203839AF1-321 GEN
Solar/Wind Harmer
0.677
20084626FORWARD
Solar/Wind Harmer
0
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
20094526CT_V3-030
Solar/Wind Harmer
0.063
970631AG2-411 GEN
Solar/Wind Harmer
2.274
20079426CONEMAGH
50/50
0.826
971541AH1-268 GEN
Solar/Wind Harmer
2.667
972323AH1-746 GEN
Solar/Wind Harmer
1.206
203841AF2-001_GEN
Solar/Wind Harmer
0.677
970125AG2-091 GEN
Solar/Wind Harmer
0.207
971879AH1-460 GEN
Solar/Wind Harmer
2.26
20216026CON.GEN2
50/50
0.022
203818AF1-086 GEN
Solar/Wind Harmer
0.312
945751AF1-240 GEN
Solar/Wind Harmer
0.572
971419AH1-201 GEN
Solar/Wind Harmer
1.232
960051AF2-296 GEN
Solar/Wind Harmer
0.603
20063626IUP CO-G
50/50
0.065
20050326C.SLOPE
50/50
0.162
20091526CHSTN_FL
Solar/Wind Harmer
0.055
970123AG2-090 GEN
Solar/Wind Harmer
0.483
20088926STNY CRK
Solar/Wind Harmer
0.059
20083326SEWRDB34
50/50
1.492
970899AG2-561 GEN
Solar/Wind Harmer
0.841
237043AE2-125 C
Solar/Wind Helper
0.299
971427AH1-205 GEN
Solar/Wind Harmer
0.821
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
50.091
971321AH1-140 GEN
Solar/Wind Harmer
13.914
203844AF2-092 C
Solar/Wind Harmer
0.393
971423AH1-203 GEN
Solar/Wind Harmer
2.122
971279AH1-102 GEN
Solar/Wind Harmer
4.619
237046AF1-021 C
Solar/Wind Helper
0.266
20080526COLVER13
50/50
0.422
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.339
20092526R32
Solar/Wind Harmer
0.104
203850AG1-041 C
Solar/Wind Harmer
0.394
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.68 %
Rating:160.0 MVA
Rating Type:A
MVA to Mitigate:189.88
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.315
972077AH1-588 GEN
Solar/Wind Harmer
3.725
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.609
972079AH1-589 GEN
Solar/Wind Harmer
4.398
23652301WDPWR_K20
Solar/Wind Helper
0.112
20094526CT_V3-030
Solar/Wind Harmer
0.056
20079426CONEMAGH
50/50
0.74
971541AH1-268 GEN
Solar/Wind Harmer
2.397
972323AH1-746 GEN
Solar/Wind Harmer
1.072
970125AG2-091 GEN
Solar/Wind Harmer
0.18
20216026CON.GEN2
50/50
0.021
203818AF1-086 GEN
Solar/Wind Harmer
0.277
20063626IUP CO-G
50/50
0.059
20050326C.SLOPE
50/50
0.141
970899AG2-561 GEN
Solar/Wind Harmer
0.758
237043AE2-125 C
Solar/Wind Helper
0.288
970123AG2-090 GEN
Solar/Wind Harmer
0.42
20215826CON.GEN1
50/50
0.01
971321AH1-140 GEN
Solar/Wind Harmer
50.36
971321AH1-140 GEN
Solar/Wind Harmer
13.989
971279AH1-102 GEN
Solar/Wind Harmer
4.152
237046AF1-021 C
Solar/Wind Helper
0.23
20080526COLVER13
50/50
0.381
20083726HOMER C1
Adder
21.821
20083926HOMER C3
Adder
20.139
20083826HOMER C2
Adder
19.024
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.596
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.402
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.839
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.578
G-007ALTFEXP_G-007A->PJM
CMTX
1.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-056_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-056_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.79 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:218.47
MW Contribution:1.37
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.417
203940AF1-140 C
Solar/Wind Harmer
0
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.8
203839AF1-321 GEN
Solar/Wind Harmer
0.782
20084626FORWARD
Solar/Wind Harmer
0
23652301WDPWR_K20
Solar/Wind Helper
0.095
20094526CT_V3-030
Solar/Wind Harmer
0.072
970631AG2-411 GEN
Solar/Wind Harmer
2.618
20079426CONEMAGH
50/50
0.996
971541AH1-268 GEN
Solar/Wind Harmer
3.172
972323AH1-746 GEN
Solar/Wind Harmer
1.366
203841AF2-001_GEN
Solar/Wind Harmer
0.782
970125AG2-091 GEN
Solar/Wind Harmer
0.238
971879AH1-460 GEN
Solar/Wind Harmer
2.603
20216026CON.GEN2
50/50
0.03
203818AF1-086 GEN
Solar/Wind Harmer
0.353
971419AH1-201 GEN
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
0.652
945751AF1-240 GEN
Solar/Wind Harmer
0.58
20063626IUP CO-G
50/50
0.08
20050326C.SLOPE
50/50
0.186
20091526CHSTN_FL
Solar/Wind Harmer
0.062
20083326SEWRDB34
50/50
1.61
970899AG2-561 GEN
Solar/Wind Harmer
0.982
237043AE2-125 C
Solar/Wind Helper
0.241
971427AH1-205 GEN
Solar/Wind Harmer
0.954
970123AG2-090 GEN
Solar/Wind Harmer
0.556
20088926STNY CRK
Solar/Wind Harmer
0.069
20215826CON.GEN1
50/50
0.014
971321AH1-140 GEN
Solar/Wind Harmer
58.683
971321AH1-140 GEN
Solar/Wind Harmer
16.301
203844AF2-092 C
Solar/Wind Harmer
0.451
203961AE2-224 GEN
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
2.474
971279AH1-102 GEN
Solar/Wind Harmer
5.495
957561AF2-050 GEN
Solar/Wind Harmer
1.503
20080526COLVER13
50/50
0.493
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.391
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
20092526R32
Solar/Wind Harmer
0.119
203850AG1-041 C
Solar/Wind Harmer
0.452
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-020A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-020A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.22 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:692.91
MW Contribution:2.58
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.947
20071526SHAWVL 1
50/50
1.942
962411AG1-090 GEN
Solar/Wind Harmer
6.224
972075AH1-587 GEN
Solar/Wind Harmer
17.841
970305AG2-200 GEN
Solar/Wind Harmer
1.463
972077AH1-588 GEN
Solar/Wind Harmer
16.576
970313AG2-206 GEN
Solar/Wind Harmer
2.503
203848AF2-166 C
Solar/Wind Harmer
0.837
203940AF1-140 C
Solar/Wind Harmer
0
20390526W1-045 C
Solar/Wind Helper
0.279
216419AE2-001 C
Solar/Wind Harmer
5.556
972079AH1-589 GEN
Solar/Wind Harmer
19.568
970715AG2-457 GEN
Solar/Wind Harmer
6.423
20398826ARMNA MT
Solar/Wind Harmer
0.029
203963AG1-253 GEN
Solar/Wind Harmer
0.185
203947AF1-006 C
Solar/Wind Harmer
0.025
971441AH1-212 GEN
Solar/Wind Harmer
0.702
946071AF1-272 GEN
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
0.847
238215AE2-248 C
Solar/Wind Harmer
4.585
203954AE2-126 C
Solar/Wind Harmer
0.002
970713AG2-456 GEN
Solar/Wind Harmer
6.423
971705AH1-358 GEN
Solar/Wind Harmer
2.302
971709AH1-360 GEN
Solar/Wind Harmer
2.302
970337AG2-221 GEN
Solar/Wind Harmer
1.231
970511AG2-327 GEN
Solar/Wind Harmer
0.521
944411AF1-106 GEN
Solar/Wind Harmer
1.658
20094526CT_V3-030
Solar/Wind Harmer
0.08
20084926LAKVU GN
Adder
0.1
200644SENECA#3
50/50
0.235
203854AF2-039 C
Solar/Wind Harmer
0.002
972323AH1-746 GEN
Solar/Wind Harmer
2.583
20334926Z1-069 C
Solar/Wind Harmer
0.451
972271AH1-720 GEN
Adder
5.198
20328326MANOR_T86
Adder
0.106
203932AE1-123
Adder
1.228
20084926LAKVU GN
Adder
0.1
971355AH1-158 GEN
Solar/Wind Harmer
1.984
971541AH1-268 GEN
Solar/Wind Harmer
2.088
970679AG2-439 GEN
Solar/Wind Harmer
0.282
20120126WRREN CT
50/50
7.034
238202AE2-262_GEN
Solar/Wind Harmer
0.014
971703AH1-357 GEN
Solar/Wind Harmer
1.381
971707AH1-359 GEN
Solar/Wind Harmer
1.381
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.668
970647AG2-420 GEN
Solar/Wind Harmer
0.781
203962AF1-287 GEN
Solar/Wind Harmer
0.736
20083126HNSMLK 4
Adder
2.764
971627AH1-313 GEN
Solar/Wind Harmer
22.518
965131AG1-378 GEN
Solar/Wind Harmer
1.245
960051AF2-296 GEN
Solar/Wind Harmer
2.259
203818AF1-086 GEN
Solar/Wind Harmer
0.667
971127AH1-005 GEN
Solar/Wind Harmer
1.216
945751AF1-240 GEN
Solar/Wind Harmer
0.817
203948AG1-140 C
Solar/Wind Harmer
0.116
200917MEHOOPANY_G
Solar/Wind Harmer
0.201
957161AF2-010 GEN
Solar/Wind Harmer
3.067
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971185AH1-051 GEN
Solar/Wind Harmer
1.19
20082926HNSMLK 2
Adder
2.764
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.478
203993AD2-133_GEN1
Solar/Wind Harmer
0.473
970555AG2-356 GEN
Solar/Wind Harmer
1.119
20091526CHSTN_FL
Solar/Wind Harmer
0.09
970677AG2-438 GEN
Solar/Wind Harmer
0.447
966771AG1-548 GEN
Solar/Wind Harmer
1.333
966771AG1-548 GEN
Solar/Wind Harmer
1.666
203975AE1-071-GEN
Solar/Wind Helper
2.84
959381AF2-229 GEN
Solar/Wind Helper
0.284
20335126GROZ1-110
50/50
2.565
20335226CANZ2-011
50/50
2.493
970899AG2-561 GEN
Solar/Wind Harmer
0.921
238219AF1-167 C
Solar/Wind Harmer
0.607
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
0.759
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.8
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.72
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
3.14
970663AG2-429 GEN
Solar/Wind Harmer
0.686
20084926LAKVU GN
Adder
0.113
20083226HNSMLK 5
Adder
2.764
20326126BLOSSBCT
50/50
2.096
238206AE2-263_GEN
Solar/Wind Harmer
0.014
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
1.984
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
2.764
20083026HNSMLK 3
Adder
2.764
209067AE2-060 GEN
Solar/Wind Helper
0.05
20091326SHAW-D
50/50
1.605
200643SENECA#2
50/50
1.711
238183AE2-316 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
4.262
970267AG2-176 GEN
Solar/Wind Harmer
5.244
971279AH1-102 GEN
Solar/Wind Harmer
3.617
20072226SHAWVL 2
50/50
38.959
20064926PENNTECH
50/50
0.501
972169AH1-667 GEN
Solar/Wind Harmer
2.89
20335026MILZ1-092
Adder
1.625
970647AG2-420 GEN
Solar/Wind Harmer
0.13
200642SENECA#1
50/50
1.834
20390726Y2-042
Adder
1.075
20083926HOMER C3
Adder
32.037
20083826HOMER C2
Adder
30.262
20083726HOMER C1
Adder
22.45
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.245
20334726NME_Y1-047
Adder
1.345
203850AG1-041 C
Solar/Wind Harmer
0.36
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.243
MECLTFEXP_MEC->PJM
CLTF
0.79
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.368
WECLTFEXP_WEC->PJM
CLTF
0.194
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.22
LGEELTFEXP_LGEE->PJM
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.336
TVALTFEXP_TVA->PJM
CLTF
0.332

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.67 %
Rating:512.0 MVA
Rating Type:A
MVA to Mitigate:571.73
MW Contribution:2.39
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
3.092
20066526SHAWVL 3
50/50
3.069
20071526SHAWVL 1
50/50
2.005
962411AG1-090 GEN
Solar/Wind Harmer
5.895
972075AH1-587 GEN
Solar/Wind Harmer
17.731
970305AG2-200 GEN
Solar/Wind Harmer
1.448
972077AH1-588 GEN
Solar/Wind Harmer
16.045
970313AG2-206 GEN
Solar/Wind Harmer
2.485
203848AF2-166 C
Solar/Wind Harmer
0.758
20390526W1-045 C
Solar/Wind Helper
0.219
216419AE2-001 C
Solar/Wind Harmer
5.905
972079AH1-589 GEN
Solar/Wind Harmer
18.942
970715AG2-457 GEN
Solar/Wind Harmer
6.217
20398826ARMNA MT
Solar/Wind Harmer
0.029
203963AG1-253 GEN
Solar/Wind Harmer
0.174
203947AF1-006 C
Solar/Wind Harmer
0.024
238215AE2-248 C
Solar/Wind Harmer
4.877
203954AE2-126 C
Solar/Wind Harmer
0.002
970713AG2-456 GEN
Solar/Wind Harmer
6.217
971705AH1-358 GEN
Solar/Wind Harmer
2.228
971709AH1-360 GEN
Solar/Wind Harmer
2.228
970337AG2-221 GEN
Solar/Wind Harmer
1.223
970511AG2-327 GEN
Solar/Wind Harmer
0.518
944411AF1-106 GEN
Solar/Wind Harmer
1.617
20084926LAKVU GN
Adder
0.095
20094526CT_V3-030
Solar/Wind Harmer
0.055
200644SENECA#3
50/50
0.235
203854AF2-039 C
Solar/Wind Harmer
0.002
972323AH1-746 GEN
Solar/Wind Harmer
2.392
20334926Z1-069 C
Solar/Wind Harmer
0.435
972271AH1-720 GEN
Adder
5.345
20328326MANOR_T86
Adder
0.108
203932AE1-123
Adder
1.111
20084926LAKVU GN
Adder
0.095
971355AH1-158 GEN
Solar/Wind Harmer
1.789
970679AG2-439 GEN
Solar/Wind Harmer
0.297
20120126WRREN CT
50/50
6.964
238202AE2-262_GEN
Solar/Wind Harmer
0.015
971703AH1-357 GEN
Solar/Wind Harmer
1.337
971707AH1-359 GEN
Solar/Wind Harmer
1.337
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.655
970647AG2-420 GEN
Solar/Wind Harmer
0.704
203962AF1-287 GEN
Solar/Wind Harmer
0.681
971627AH1-313 GEN
Solar/Wind Harmer
23.741
965131AG1-378 GEN
Solar/Wind Harmer
1.179
960051AF2-296 GEN
Solar/Wind Harmer
2.221
203818AF1-086 GEN
Solar/Wind Harmer
0.618
971127AH1-005 GEN
Solar/Wind Harmer
1.207
200917MEHOOPANY_G
Solar/Wind Harmer
0.208
203948AG1-140 C
Solar/Wind Harmer
0.109
945751AF1-240 GEN
Solar/Wind Harmer
0.706
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
2.851
971185AH1-051 GEN
Solar/Wind Harmer
1.074
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.404
203993AD2-133_GEN1
Solar/Wind Harmer
0.4
970555AG2-356 GEN
Solar/Wind Harmer
1.112
966771AG1-548 GEN
Solar/Wind Harmer
1.242
966771AG1-548 GEN
Solar/Wind Harmer
1.552
970677AG2-438 GEN
Solar/Wind Harmer
0.416
203975AE1-071-GEN
Solar/Wind Helper
2.227
959381AF2-229 GEN
Solar/Wind Helper
0.224
20335126GROZ1-110
50/50
2.622
20335226CANZ2-011
50/50
2.549
238219AF1-167 C
Solar/Wind Harmer
0.563
970899AG2-561 GEN
Solar/Wind Harmer
0.751
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
0.742
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.744
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.664
203926AA2-133 GEN
Adder
1.587
970663AG2-429 GEN
Solar/Wind Harmer
2.877
970663AG2-429 GEN
Solar/Wind Harmer
0.629
20084926LAKVU GN
Adder
0.106
20326126BLOSSBCT
50/50
2.075
238206AE2-263_GEN
Solar/Wind Harmer
0.014
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
1.789
203860AG1-193 C
Solar/Wind Harmer
0
20091326SHAW-D
50/50
1.639
200643SENECA#2
50/50
1.708
238183AE2-316 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
3.943
970267AG2-176 GEN
Solar/Wind Harmer
4.738
20072226SHAWVL 2
50/50
40.577
20064926PENNTECH
50/50
0.512
972169AH1-667 GEN
Solar/Wind Harmer
2.951
20335026MILZ1-092
Adder
1.585
970647AG2-420 GEN
Solar/Wind Harmer
0.117
964391AG1-301 GEN
Solar/Wind Helper
0.298
200642SENECA#1
50/50
1.831
20390726Y2-042
Adder
1.13
20083926HOMER C3
Adder
23.864
20083826HOMER C2
Adder
22.542
20083726HOMER C1
Adder
11.828
941231AE2-117 GEN
Solar/Wind Helper
0.237
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.179
20334726NME_Y1-047
Adder
1.387
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.094
LGEELTFEXP_LGEE->PJM
CLTF
0.226
MECLTFEXP_MEC->PJM
CLTF
0.566
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.9
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.723
WECLTFEXP_WEC->PJM
CLTF
0.141
LAGNLTFEXP_LAGN->PJM
CLTF
0.459
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.04
TVALTFEXP_TVA->PJM
CLTF
0.22

Details for 01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-019_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
01SHINGL-26LEWISTWN 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-019_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:612.0 MVA
Rating Type:B
MVA to Mitigate:680.04
MW Contribution:2.52
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.969
20066526SHAWVL 3
50/50
2.948
20071526SHAWVL 1
50/50
1.934
962411AG1-090 GEN
Solar/Wind Harmer
5.898
972075AH1-587 GEN
Solar/Wind Harmer
17.723
970305AG2-200 GEN
Solar/Wind Harmer
1.453
972077AH1-588 GEN
Solar/Wind Harmer
16.418
970313AG2-206 GEN
Solar/Wind Harmer
2.49
203848AF2-166 C
Solar/Wind Harmer
0.821
20390526W1-045 C
Solar/Wind Helper
0.269
216419AE2-001 C
Solar/Wind Harmer
5.6
972079AH1-589 GEN
Solar/Wind Harmer
19.382
970715AG2-457 GEN
Solar/Wind Harmer
6.362
20398826ARMNA MT
Solar/Wind Harmer
0.029
203963AG1-253 GEN
Solar/Wind Harmer
0.182
203947AF1-006 C
Solar/Wind Harmer
0.025
209137AF2-361 C
Solar/Wind Helper
0.817
238215AE2-248 C
Solar/Wind Harmer
4.623
203954AE2-126 C
Solar/Wind Harmer
0.002
970713AG2-456 GEN
Solar/Wind Harmer
6.362
971705AH1-358 GEN
Solar/Wind Harmer
2.28
971709AH1-360 GEN
Solar/Wind Harmer
2.28
970337AG2-221 GEN
Solar/Wind Harmer
1.225
970511AG2-327 GEN
Solar/Wind Harmer
0.519
944411AF1-106 GEN
Solar/Wind Harmer
1.646
20094526CT_V3-030
Solar/Wind Harmer
0.074
20084926LAKVU GN
Adder
0.099
200644SENECA#3
50/50
0.234
20120126WRREN CT
50/50
6.988
238202AE2-262_GEN
Solar/Wind Harmer
0.014
971703AH1-357 GEN
Solar/Wind Harmer
1.368
971707AH1-359 GEN
Solar/Wind Harmer
1.368
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.66
970647AG2-420 GEN
Solar/Wind Harmer
0.766
203962AF1-287 GEN
Solar/Wind Harmer
0.725
20083126HNSMLK 4
Adder
2.699
971627AH1-313 GEN
Solar/Wind Harmer
22.632
965131AG1-378 GEN
Solar/Wind Harmer
1.18
960051AF2-296 GEN
Solar/Wind Harmer
2.225
203818AF1-086 GEN
Solar/Wind Harmer
0.651
971127AH1-005 GEN
Solar/Wind Harmer
1.21
945751AF1-240 GEN
Solar/Wind Harmer
0.794
203948AG1-140 C
Solar/Wind Harmer
0.115
200917MEHOOPANY_G
Solar/Wind Harmer
0.201
203830AF1-094 GEN
Solar/Wind Harmer
0.001
957161AF2-010 GEN
Solar/Wind Harmer
3.021
971185AH1-051 GEN
Solar/Wind Harmer
1.167
20082926HNSMLK 2
Adder
2.699
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.424
203993AD2-133_GEN1
Solar/Wind Harmer
0.42
970555AG2-356 GEN
Solar/Wind Harmer
1.114
20091526CHSTN_FL
Solar/Wind Harmer
0.074
966771AG1-548 GEN
Solar/Wind Harmer
1.313
966771AG1-548 GEN
Solar/Wind Harmer
1.642
970677AG2-438 GEN
Solar/Wind Harmer
0.44
203975AE1-071-GEN
Solar/Wind Helper
2.743
959381AF2-229 GEN
Solar/Wind Helper
0.275
203854AF2-039 C
Solar/Wind Harmer
0.002
972323AH1-746 GEN
Solar/Wind Harmer
2.521
20334926Z1-069 C
Solar/Wind Harmer
0.447
972271AH1-720 GEN
Adder
5.199
20328326MANOR_T86
Adder
0.106
203932AE1-123
Adder
1.204
20084926LAKVU GN
Adder
0.099
971355AH1-158 GEN
Solar/Wind Harmer
1.945
971541AH1-268 GEN
Solar/Wind Harmer
1.963
970679AG2-439 GEN
Solar/Wind Harmer
0.284
20335126GROZ1-110
50/50
2.562
20335226CANZ2-011
50/50
2.49
970899AG2-561 GEN
Solar/Wind Harmer
0.885
238219AF1-167 C
Solar/Wind Harmer
0.597
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
0.753
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.788
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.709
203926AA2-133 GEN
Adder
1.549
970663AG2-429 GEN
Solar/Wind Harmer
3.087
970663AG2-429 GEN
Solar/Wind Harmer
0.675
20084926LAKVU GN
Adder
0.111
20083226HNSMLK 5
Adder
2.699
20326126BLOSSBCT
50/50
2.084
238206AE2-263_GEN
Solar/Wind Harmer
0.014
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
1.945
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
2.699
20083026HNSMLK 3
Adder
2.699
209067AE2-060 GEN
Solar/Wind Helper
0.048
20091326SHAW-D
50/50
1.591
200643SENECA#2
50/50
1.702
238183AE2-316 GEN
Solar/Wind Harmer
0.005
203813AE2-344_GEN
Solar/Wind Harmer
4.197
970267AG2-176 GEN
Solar/Wind Harmer
5.148
971279AH1-102 GEN
Solar/Wind Harmer
3.4
20072226SHAWVL 2
50/50
38.968
20064926PENNTECH
50/50
0.499
972169AH1-667 GEN
Solar/Wind Harmer
2.864
20335026MILZ1-092
Adder
1.613
970647AG2-420 GEN
Solar/Wind Harmer
0.128
964391AG1-301 GEN
Solar/Wind Helper
0.489
200642SENECA#1
50/50
1.824
20390726Y2-042
Adder
1.079
20083926HOMER C3
Adder
30.8
20083826HOMER C2
Adder
29.094
20083726HOMER C1
Adder
20.945
941231AE2-117 GEN
Solar/Wind Helper
0.407
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.18
20334726NME_Y1-047
Adder
1.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.927
LGEELTFEXP_LGEE->PJM
CLTF
0.306
LAGNLTFEXP_LAGN->PJM
CLTF
0.658
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.28
TVALTFEXP_TVA->PJM
CLTF
0.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.153
WECLTFEXP_WEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.621
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.224
MECLTFEXP_MEC->PJM
CLTF
0.76

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P1-2_WP-500-008_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-500-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.74 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:243.34
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.362
203940AF1-140 C
Solar/Wind Harmer
0
972077AH1-588 GEN
Solar/Wind Harmer
4.556
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.699
203839AF1-321 GEN
Solar/Wind Harmer
0.677
20084626FORWARD
Solar/Wind Harmer
0
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
20094526CT_V3-030
Solar/Wind Harmer
0.063
970631AG2-411 GEN
Solar/Wind Harmer
2.274
20079426CONEMAGH
50/50
0.826
971541AH1-268 GEN
Solar/Wind Harmer
2.667
972323AH1-746 GEN
Solar/Wind Harmer
1.206
203841AF2-001_GEN
Solar/Wind Harmer
0.677
970125AG2-091 GEN
Solar/Wind Harmer
0.207
971879AH1-460 GEN
Solar/Wind Harmer
2.26
20216026CON.GEN2
50/50
0.022
203818AF1-086 GEN
Solar/Wind Harmer
0.312
945751AF1-240 GEN
Solar/Wind Harmer
0.572
971419AH1-201 GEN
Solar/Wind Harmer
1.232
960051AF2-296 GEN
Solar/Wind Harmer
0.603
20063626IUP CO-G
50/50
0.065
20050326C.SLOPE
50/50
0.162
20091526CHSTN_FL
Solar/Wind Harmer
0.055
970123AG2-090 GEN
Solar/Wind Harmer
0.483
20088926STNY CRK
Solar/Wind Harmer
0.059
20083326SEWRDB34
50/50
1.492
970899AG2-561 GEN
Solar/Wind Harmer
0.841
237043AE2-125 C
Solar/Wind Helper
0.299
971427AH1-205 GEN
Solar/Wind Harmer
0.821
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
50.091
971321AH1-140 GEN
Solar/Wind Harmer
13.914
203844AF2-092 C
Solar/Wind Harmer
0.393
971423AH1-203 GEN
Solar/Wind Harmer
2.122
971279AH1-102 GEN
Solar/Wind Harmer
4.619
237046AF1-021 C
Solar/Wind Helper
0.266
20080526COLVER13
50/50
0.422
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.339
20092526R32
Solar/Wind Harmer
0.104
203850AG1-041 C
Solar/Wind Harmer
0.394
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.86 %
Rating:160.0 MVA
Rating Type:A
MVA to Mitigate:196.57
MW Contribution:1.07
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.315
972077AH1-588 GEN
Solar/Wind Harmer
3.725
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.609
972079AH1-589 GEN
Solar/Wind Harmer
4.398
23652301WDPWR_K20
Solar/Wind Helper
0.112
20094526CT_V3-030
Solar/Wind Harmer
0.056
20079426CONEMAGH
50/50
0.74
971541AH1-268 GEN
Solar/Wind Harmer
2.397
972323AH1-746 GEN
Solar/Wind Harmer
1.072
970125AG2-091 GEN
Solar/Wind Harmer
0.18
20216026CON.GEN2
50/50
0.021
203818AF1-086 GEN
Solar/Wind Harmer
0.277
20063626IUP CO-G
50/50
0.059
20050326C.SLOPE
50/50
0.141
970123AG2-090 GEN
Solar/Wind Harmer
0.42
970899AG2-561 GEN
Solar/Wind Harmer
0.758
237043AE2-125 C
Solar/Wind Helper
0.288
20215826CON.GEN1
50/50
0.01
971321AH1-140 GEN
Solar/Wind Harmer
50.36
971321AH1-140 GEN
Solar/Wind Harmer
13.989
971279AH1-102 GEN
Solar/Wind Harmer
4.152
237046AF1-021 C
Solar/Wind Helper
0.23
20080526COLVER13
50/50
0.381
20083726HOMER C1
Adder
21.821
20083926HOMER C3
Adder
20.139
20083826HOMER C2
Adder
19.024
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.596
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.402
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.839
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.578
G-007ALTFEXP_G-007A->PJM
CMTX
1.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.186
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-056_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-056_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.96 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:226.47
MW Contribution:1.37
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
0.417
203940AF1-140 C
Solar/Wind Harmer
0
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.8
203839AF1-321 GEN
Solar/Wind Harmer
0.782
20084626FORWARD
Solar/Wind Harmer
0
23652301WDPWR_K20
Solar/Wind Helper
0.095
20094526CT_V3-030
Solar/Wind Harmer
0.072
970631AG2-411 GEN
Solar/Wind Harmer
2.618
20079426CONEMAGH
50/50
0.996
971541AH1-268 GEN
Solar/Wind Harmer
3.172
972323AH1-746 GEN
Solar/Wind Harmer
1.366
203841AF2-001_GEN
Solar/Wind Harmer
0.782
970125AG2-091 GEN
Solar/Wind Harmer
0.238
971879AH1-460 GEN
Solar/Wind Harmer
2.603
20216026CON.GEN2
50/50
0.03
203818AF1-086 GEN
Solar/Wind Harmer
0.353
971419AH1-201 GEN
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
0.652
945751AF1-240 GEN
Solar/Wind Harmer
0.58
20063626IUP CO-G
50/50
0.08
20050326C.SLOPE
50/50
0.186
20091526CHSTN_FL
Solar/Wind Harmer
0.062
20083326SEWRDB34
50/50
1.61
970899AG2-561 GEN
Solar/Wind Harmer
0.982
237043AE2-125 C
Solar/Wind Helper
0.241
971427AH1-205 GEN
Solar/Wind Harmer
0.954
970123AG2-090 GEN
Solar/Wind Harmer
0.556
20088926STNY CRK
Solar/Wind Harmer
0.069
20215826CON.GEN1
50/50
0.014
971321AH1-140 GEN
Solar/Wind Harmer
58.683
971321AH1-140 GEN
Solar/Wind Harmer
16.301
203844AF2-092 C
Solar/Wind Harmer
0.451
203961AE2-224 GEN
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
2.474
971279AH1-102 GEN
Solar/Wind Harmer
5.495
957561AF2-050 GEN
Solar/Wind Harmer
1.503
20080526COLVER13
50/50
0.493
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.391
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
20092526R32
Solar/Wind Harmer
0.119
203850AG1-041 C
Solar/Wind Harmer
0.452
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.27
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
2.105
203940AF1-140 C
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972075AH1-587 GEN
Solar/Wind Harmer
26.086
962411AG1-090 GEN
Solar/Wind Harmer
6.096
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
3.559
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203947AF1-006 C
Solar/Wind Harmer
0.053
970631AG2-411 GEN
Solar/Wind Harmer
13.547
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
238215AE2-248 C
Solar/Wind Harmer
1.358
20084926LAKVU GN
Adder
0.203
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971419AH1-201 GEN
Solar/Wind Harmer
7.308
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
971127AH1-005 GEN
Solar/Wind Harmer
2.448
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
945751AF1-240 GEN
Solar/Wind Harmer
1.735
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971627AH1-313 GEN
Solar/Wind Harmer
9.109
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
20050326C.SLOPE
50/50
0.866
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
970555AG2-356 GEN
Solar/Wind Harmer
2.168
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
20089126CSLMN_L13
Solar/Wind Harmer
0.099
971541AH1-268 GEN
Solar/Wind Harmer
9.014
20334926Z1-069 C
Solar/Wind Harmer
1.013
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
3.441
971355AH1-158 GEN
Solar/Wind Harmer
4.678
203932AE1-123
Adder
2.599
20328326MANOR_T86
Adder
0.172
20084926LAKVU GN
Adder
0.203
972271AH1-720 GEN
Adder
7.336
970679AG2-439 GEN
Solar/Wind Harmer
0.489
20083326SEWRDB34
50/50
10.964
970899AG2-561 GEN
Solar/Wind Harmer
1.963
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
238219AF1-167 C
Solar/Wind Harmer
1.173
970643AG2-418 GEN
Solar/Wind Harmer
1.033
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
20120126WRREN CT
Adder
9.417
970647AG2-420 GEN
Solar/Wind Harmer
1.873
238202AE2-262_GEN
Solar/Wind Harmer
0.006
203962AF1-287 GEN
Solar/Wind Harmer
1.654
941421AE2-139 GEN
Solar/Wind Harmer
0
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20303426NA_O38_P22
Solar/Wind Harmer
0.002
971427AH1-205 GEN
Solar/Wind Harmer
4.872
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
1.801
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
20080926SITHE
50/50
0.913
970123AG2-090 GEN
Solar/Wind Harmer
2.807
20088626ARWF_N39
Solar/Wind Harmer
0.003
20088926STNY CRK
Solar/Wind Harmer
0.352
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203961AE2-224 GEN
Solar/Wind Harmer
0.015
203844AF2-092 C
Solar/Wind Harmer
2.257
20083226HNSMLK 5
Adder
10.005
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
971055AG2-654 GEN
Solar/Wind Harmer
0.456
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
203860AG1-193 C
Solar/Wind Harmer
0.001
971183AH1-050 GEN
Solar/Wind Harmer
4.678
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
970267AG2-176 GEN
Solar/Wind Harmer
13.758
203813AE2-344_GEN
Solar/Wind Harmer
9.593
970643AG2-418 GEN
Solar/Wind Harmer
0.689
971865AH1-452 GEN
Solar/Wind Harmer
0.492
203843AF2-002_GEN
Solar/Wind Harmer
2.005
20088826HIGHLAND
Solar/Wind Harmer
0.002
20335026MILZ1-092
Adder
3.743
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20072226SHAWVL 2
Adder
19.029
970647AG2-420 GEN
Solar/Wind Harmer
0.312
24035802GEN-Y1-012
Adder
0.228
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20390726Y2-042
Adder
1.86
20092526R32
Solar/Wind Harmer
0.589
203850AG1-041 C
Solar/Wind Harmer
2.251
965121AG1-377 GEN
Solar/Wind Harmer
1.219
203855AF2-088 C
Solar/Wind Harmer
0.001
20334726NME_Y1-047
Adder
2.305
961581Q1080_CY23
External Queue
27.7316951751709
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
MDUPJM->LTFIMP_MDU
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.25
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
203857AF2-221 C
Solar/Wind Harmer
2.105
203940AF1-140 C
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972075AH1-587 GEN
Solar/Wind Harmer
26.086
962411AG1-090 GEN
Solar/Wind Harmer
6.096
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
970631AG2-411 GEN
Solar/Wind Harmer
13.547
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
238215AE2-248 C
Solar/Wind Harmer
1.358
20084926LAKVU GN
Adder
0.203
971441AH1-212 GEN
Solar/Wind Harmer
3.559
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203947AF1-006 C
Solar/Wind Harmer
0.053
971419AH1-201 GEN
Solar/Wind Harmer
7.308
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
971127AH1-005 GEN
Solar/Wind Harmer
2.448
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
945751AF1-240 GEN
Solar/Wind Harmer
1.735
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971627AH1-313 GEN
Solar/Wind Harmer
9.109
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
20089126CSLMN_L13
Solar/Wind Harmer
0.099
971541AH1-268 GEN
Solar/Wind Harmer
9.014
20334926Z1-069 C
Solar/Wind Harmer
1.013
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
3.441
971355AH1-158 GEN
Solar/Wind Harmer
4.678
203932AE1-123
Adder
2.599
20328326MANOR_T86
Adder
0.172
20084926LAKVU GN
Adder
0.203
972271AH1-720 GEN
Adder
7.336
970679AG2-439 GEN
Solar/Wind Harmer
0.489
20083326SEWRDB34
50/50
10.964
970899AG2-561 GEN
Solar/Wind Harmer
1.963
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
238219AF1-167 C
Solar/Wind Harmer
1.173
970643AG2-418 GEN
Solar/Wind Harmer
1.033
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
20120126WRREN CT
Adder
9.417
970647AG2-420 GEN
Solar/Wind Harmer
1.873
238202AE2-262_GEN
Solar/Wind Harmer
0.006
203962AF1-287 GEN
Solar/Wind Harmer
1.654
941421AE2-139 GEN
Solar/Wind Harmer
0
20050326C.SLOPE
50/50
0.866
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
970555AG2-356 GEN
Solar/Wind Harmer
2.168
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20303426NA_O38_P22
Solar/Wind Harmer
0.002
971427AH1-205 GEN
Solar/Wind Harmer
4.872
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
1.801
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
20080926SITHE
50/50
0.913
970123AG2-090 GEN
Solar/Wind Harmer
2.807
20088626ARWF_N39
Solar/Wind Harmer
0.003
20088926STNY CRK
Solar/Wind Harmer
0.352
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203961AE2-224 GEN
Solar/Wind Harmer
0.015
203844AF2-092 C
Solar/Wind Harmer
2.257
20083226HNSMLK 5
Adder
10.005
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
971055AG2-654 GEN
Solar/Wind Harmer
0.456
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
203860AG1-193 C
Solar/Wind Harmer
0.001
971183AH1-050 GEN
Solar/Wind Harmer
4.678
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
970267AG2-176 GEN
Solar/Wind Harmer
13.758
203813AE2-344_GEN
Solar/Wind Harmer
9.593
970643AG2-418 GEN
Solar/Wind Harmer
0.689
971865AH1-452 GEN
Solar/Wind Harmer
0.492
203843AF2-002_GEN
Solar/Wind Harmer
2.005
20088826HIGHLAND
Solar/Wind Harmer
0.002
20335026MILZ1-092
Adder
3.743
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20072226SHAWVL 2
Adder
19.029
970647AG2-420 GEN
Solar/Wind Harmer
0.312
24035802GEN-Y1-012
Adder
0.228
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20390726Y2-042
Adder
1.86
20092526R32
Solar/Wind Harmer
0.589
203850AG1-041 C
Solar/Wind Harmer
2.251
965121AG1-377 GEN
Solar/Wind Harmer
1.219
203855AF2-088 C
Solar/Wind Harmer
0.001
20334726NME_Y1-047
Adder
2.305
961581Q1080_CY23
External Queue
27.7316951751709
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
MDUPJM->LTFIMP_MDU
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:809.0 MVA
Rating Type:A
MVA to Mitigate:811.02
MW Contribution:2.07
Bus #Bus NameTypeMW Contribution
20079426CONEMAGH
50/50
2.219
203841AF2-001_GEN
Solar/Wind Harmer
2.872
20334926Z1-069 C
Solar/Wind Harmer
0.807
20089126CSLMN_L13
Solar/Wind Harmer
0.07
971541AH1-268 GEN
Solar/Wind Harmer
5.544
203854AF2-039 C
Solar/Wind Harmer
0.001
971355AH1-158 GEN
Solar/Wind Harmer
3.471
20328326MANOR_T86
Adder
0.138
203932AE1-123
Adder
1.861
972271AH1-720 GEN
Adder
5.882
20084926LAKVU GN
Adder
0.157
972323AH1-746 GEN
Solar/Wind Harmer
2.072
970679AG2-439 GEN
Solar/Wind Harmer
0.401
20083326SEWRDB34
50/50
7.032
20335126GROZ1-110
Adder
2.469
20335226CANZ2-011
Adder
2.399
238219AF1-167 C
Solar/Wind Harmer
0.869
970899AG2-561 GEN
Solar/Wind Harmer
1.064
970643AG2-418 GEN
Solar/Wind Harmer
0.761
971879AH1-460 GEN
Solar/Wind Harmer
9.383
970125AG2-091 GEN
Solar/Wind Harmer
0.846
971703AH1-357 GEN
Solar/Wind Harmer
2.198
971707AH1-359 GEN
Solar/Wind Harmer
2.198
20089026BF_G21_K23
Solar/Wind Harmer
0.071
20083126HNSMLK 4
Adder
7.883
970335AG2-220 GEN
Solar/Wind Harmer
2.693
20120126WRREN CT
Adder
7.308
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
1.398
238202AE2-262_GEN
Solar/Wind Harmer
0.004
203962AF1-287 GEN
Solar/Wind Harmer
1.276
941421AE2-139 GEN
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
2.872
20084626FORWARD
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
2.409
972079AH1-589 GEN
Solar/Wind Harmer
31.142
970715AG2-457 GEN
Solar/Wind Harmer
10.222
20398826ARMNA MT
Solar/Wind Harmer
0.053
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.297
216419AE2-001 C
Solar/Wind Harmer
1.268
203947AF1-006 C
Solar/Wind Harmer
0.041
946071AF1-272 GEN
Solar/Wind Helper
1.546
20050326C.SLOPE
50/50
0.588
20091526CHSTN_FL
Solar/Wind Harmer
0.208
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.485
971419AH1-201 GEN
Solar/Wind Harmer
5.18
20082926HNSMLK 2
Adder
7.883
965131AG1-378 GEN
Solar/Wind Harmer
0.865
971127AH1-005 GEN
Solar/Wind Harmer
1.964
971185AH1-051 GEN
Solar/Wind Harmer
2.082
971627AH1-313 GEN
Solar/Wind Harmer
6.761
960051AF2-296 GEN
Solar/Wind Harmer
1.349
203948AG1-140 C
Solar/Wind Harmer
0.187
957161AF2-010 GEN
Solar/Wind Harmer
4.943
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203818AF1-086 GEN
Solar/Wind Harmer
0.535
945751AF1-240 GEN
Solar/Wind Harmer
1.105
200917MEHOOPANY_G
Solar/Wind Harmer
0.28
20303426NA_O38_P22
Solar/Wind Harmer
0.002
971427AH1-205 GEN
Solar/Wind Harmer
3.453
203952AE2-129 C
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.449
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.287
20080926SITHE
50/50
0.744
970123AG2-090 GEN
Solar/Wind Harmer
1.975
20088626ARWF_N39
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.25
971931AH1-490 GEN
Solar/Wind Harmer
1.273
970631AG2-411 GEN
Solar/Wind Harmer
9.712
970713AG2-456 GEN
Solar/Wind Harmer
10.222
971705AH1-358 GEN
Solar/Wind Harmer
3.664
971709AH1-360 GEN
Solar/Wind Harmer
3.664
203987AE2-118 C
Solar/Wind Harmer
1.969
944411AF1-106 GEN
Solar/Wind Harmer
3.064
20094526CT_V3-030
Solar/Wind Harmer
0.152
970337AG2-221 GEN
Solar/Wind Harmer
1.909
970511AG2-327 GEN
Solar/Wind Harmer
0.837
203954AE2-126 C
Solar/Wind Harmer
0.001
238215AE2-248 C
Solar/Wind Harmer
1.003
20084926LAKVU GN
Adder
0.157
203961AE2-224 GEN
Solar/Wind Harmer
0.011
203844AF2-092 C
Solar/Wind Harmer
1.584
20083226HNSMLK 5
Adder
7.883
970663AG2-429 GEN
Solar/Wind Harmer
5.172
970663AG2-429 GEN
Solar/Wind Harmer
1.13
20084926LAKVU GN
Adder
0.176
203926AA2-133 GEN
Adder
2.065
971423AH1-203 GEN
Solar/Wind Harmer
9.001
20082826HNSMLK 1
Adder
7.883
20083026HNSMLK 3
Adder
7.883
20326126BLOSSBCT
Adder
3.012
203860AG1-193 C
Solar/Wind Harmer
0.001
971183AH1-050 GEN
Solar/Wind Harmer
3.471
238206AE2-263_GEN
Solar/Wind Harmer
0.004
203835AF1-098 GEN
Solar/Wind Harmer
0.004
203993AD2-133_GEN1
Solar/Wind Harmer
0.48
970555AG2-356 GEN
Solar/Wind Harmer
1.736
970677AG2-438 GEN
Solar/Wind Harmer
0.719
966771AG1-548 GEN
Solar/Wind Harmer
2.139
966771AG1-548 GEN
Solar/Wind Harmer
2.673
203857AF2-221 C
Solar/Wind Harmer
1.481
203940AF1-140 C
Solar/Wind Harmer
0.002
972077AH1-588 GEN
Solar/Wind Harmer
26.379
944781AF1-143 GEN
Solar/Wind Harmer
-0.001
972075AH1-587 GEN
Solar/Wind Harmer
20.422
962411AG1-090 GEN
Solar/Wind Harmer
4.323
970313AG2-206 GEN
Solar/Wind Harmer
4.019
970305AG2-200 GEN
Solar/Wind Harmer
1.613
203848AF2-166 C
Solar/Wind Harmer
1.342
203843AF2-002_GEN
Solar/Wind Harmer
1.436
20088826HIGHLAND
Solar/Wind Harmer
0.001
20335026MILZ1-092
Adder
3.003
972169AH1-667 GEN
Solar/Wind Harmer
1.342
20072226SHAWVL 2
Adder
14.036
970647AG2-420 GEN
Solar/Wind Harmer
0.233
957561AF2-050 GEN
Solar/Wind Harmer
6.927
20089226LOOKOUT
Solar/Wind Harmer
0.201
971279AH1-102 GEN
Solar/Wind Harmer
9.604
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20091326SHAW-D
Adder
0.702
970267AG2-176 GEN
Solar/Wind Harmer
10.629
203813AE2-344_GEN
Solar/Wind Harmer
7.402
970643AG2-418 GEN
Solar/Wind Harmer
0.507
20083726HOMER C1
50/50
231.295
20083926HOMER C3
50/50
187.4
20083826HOMER C2
50/50
177.021
20390726Y2-042
Adder
1.527
20092526R32
Solar/Wind Harmer
0.408
203850AG1-041 C
Solar/Wind Harmer
1.576
965121AG1-377 GEN
Solar/Wind Harmer
0.865
203855AF2-088 C
Solar/Wind Harmer
0
20334726NME_Y1-047
Adder
1.87
961581Q1080_CY23
External Queue
22.834562301635742
VTFLTFEXP_VFT->PJM
CMTX
1.427
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.728
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.959
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.162
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.401
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.145
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:493.0 MVA
Rating Type:A
MVA to Mitigate:649.4
MW Contribution:2.59
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.237
20071526SHAWVL 1
50/50
1.515
962411AG1-090 GEN
Solar/Wind Harmer
6.143
20390526W1-045 C
Solar/Wind Harmer
0.083
972075AH1-587 GEN
Solar/Wind Harmer
15.234
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.263
972077AH1-588 GEN
Solar/Wind Harmer
14.999
203857AF2-221 C
Solar/Wind Harmer
0.565
203848AF2-166 C
Solar/Wind Harmer
0.87
970313AG2-206 GEN
Solar/Wind Harmer
2.048
944781AF1-143 GEN
Solar/Wind Harmer
0
20081226ALY HYDR
50/50
0.385
216419AE2-001 C
Solar/Wind Harmer
3.961
971441AH1-212 GEN
Solar/Wind Harmer
1.512
972079AH1-589 GEN
Solar/Wind Harmer
17.707
970715AG2-457 GEN
Solar/Wind Harmer
5.812
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.001
20398826ARMNA MT
Solar/Wind Harmer
0.025
946071AF1-272 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203947AF1-006 C
Solar/Wind Harmer
0.025
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.532
238215AE2-248 C
Solar/Wind Harmer
3.258
203987AE2-118 C
Solar/Wind Harmer
3.371
203954AE2-126 C
Solar/Wind Harmer
0.002
20094526CT_V3-030
Solar/Wind Harmer
0.122
970713AG2-456 GEN
Solar/Wind Harmer
5.812
971705AH1-358 GEN
Solar/Wind Harmer
2.083
971709AH1-360 GEN
Solar/Wind Harmer
2.083
970631AG2-411 GEN
Solar/Wind Harmer
3.514
970337AG2-221 GEN
Solar/Wind Harmer
1.015
944411AF1-106 GEN
Solar/Wind Harmer
1.425
970511AG2-327 GEN
Solar/Wind Harmer
0.427
20084926LAKVU GN
Adder
0.097
200644SENECA#3
50/50
0.199
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
2.592
20334926Z1-069 C
Solar/Wind Harmer
0.406
971541AH1-268 GEN
Solar/Wind Harmer
3.208
203841AF2-001_GEN
Solar/Wind Harmer
1.001
20079426CONEMAGH
Adder
0.853
203932AE1-123
Adder
1.278
971355AH1-158 GEN
Solar/Wind Harmer
2.076
972271AH1-720 GEN
Adder
3.827
20089126CSLMN_L13
Solar/Wind Harmer
0.027
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
238202AE2-262_GEN
Solar/Wind Harmer
0.01
20120126WRREN CT
Adder
5.725
971703AH1-357 GEN
Solar/Wind Harmer
1.25
971707AH1-359 GEN
Solar/Wind Harmer
1.25
970125AG2-091 GEN
Solar/Wind Harmer
0.323
971879AH1-460 GEN
Solar/Wind Harmer
3.447
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.368
970647AG2-420 GEN
Solar/Wind Harmer
0.817
20089026BF_G21_K23
Solar/Wind Harmer
0.027
20083126HNSMLK 4
Adder
3.113
203962AF1-287 GEN
Solar/Wind Harmer
0.736
202652Y1-033 WT C
Solar/Wind Harmer
0
971627AH1-313 GEN
Solar/Wind Harmer
16.451
965131AG1-378 GEN
Solar/Wind Harmer
1.229
960051AF2-296 GEN
Solar/Wind Harmer
1.997
203818AF1-086 GEN
Solar/Wind Harmer
0.67
971419AH1-201 GEN
Solar/Wind Harmer
2.125
945751AF1-240 GEN
Solar/Wind Harmer
0.92
971127AH1-005 GEN
Solar/Wind Harmer
0.997
971185AH1-051 GEN
Solar/Wind Harmer
1.246
957161AF2-010 GEN
Solar/Wind Harmer
3.04
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.112
20082926HNSMLK 2
Adder
3.113
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.591
203993AD2-133_GEN1
Solar/Wind Harmer
0.585
20091526CHSTN_FL
Solar/Wind Harmer
0.174
203804AE2-113_GEN
Solar/Wind Harmer
0.006
970555AG2-356 GEN
Solar/Wind Harmer
0.923
970677AG2-438 GEN
Solar/Wind Harmer
0.442
966771AG1-548 GEN
Solar/Wind Harmer
1.316
966771AG1-548 GEN
Solar/Wind Harmer
1.645
20088626ARWF_N39
Solar/Wind Harmer
0.002
970123AG2-090 GEN
Solar/Wind Harmer
0.754
20088926STNY CRK
Solar/Wind Harmer
0.103
971931AH1-490 GEN
Solar/Wind Harmer
0.726
970643AG2-418 GEN
Solar/Wind Harmer
4.659
970899AG2-561 GEN
Solar/Wind Harmer
1.133
20335126GROZ1-110
Adder
1.858
20335226CANZ2-011
Adder
1.806
238219AF1-167 C
Solar/Wind Harmer
0.6
20072226SHAWVL 2
50/50
29.573
20064926PENNTECH
50/50
0.4
972169AH1-667 GEN
Solar/Wind Harmer
2.333
20088826HIGHLAND
Solar/Wind Harmer
0.001
203843AF2-002_GEN
Solar/Wind Harmer
0.501
20335026MILZ1-092
Adder
1.397
203952AE2-129 C
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
203982AD2-062_GEN
Solar/Wind Harmer
5.363
971427AH1-205 GEN
Solar/Wind Harmer
1.417
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.792
203859AF2-294 C
Solar/Wind Harmer
0.639
203980AG1-197 GEN
Solar/Wind Harmer
0
238206AE2-263_GEN
Solar/Wind Harmer
0.01
971423AH1-203 GEN
Solar/Wind Harmer
3.585
20326126BLOSSBCT
Adder
1.652
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
2.076
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
3.113
20083026HNSMLK 3
Adder
3.113
209067AE2-060 GEN
Solar/Wind Helper
0.091
203961AE2-224 GEN
Solar/Wind Harmer
0.008
203844AF2-092 C
Solar/Wind Harmer
0.754
970663AG2-429 GEN
Solar/Wind Harmer
3.183
970663AG2-429 GEN
Solar/Wind Harmer
0.696
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.113
203926AA2-133 GEN
Adder
1.132
20091326SHAW-D
50/50
1.296
200643SENECA#2
50/50
1.448
970643AG2-418 GEN
Solar/Wind Harmer
3.106
957561AF2-050 GEN
Solar/Wind Harmer
4.914
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971279AH1-102 GEN
Solar/Wind Harmer
5.556
20089226LOOKOUT
Solar/Wind Harmer
0.077
203813AE2-344_GEN
Solar/Wind Harmer
4.269
970267AG2-176 GEN
Solar/Wind Harmer
5.48
970647AG2-420 GEN
Solar/Wind Harmer
0.136
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.229
203850AG1-041 C
Solar/Wind Harmer
0.775
20092526R32
Solar/Wind Harmer
0.187
23732901CHBRG_I12
Adder
1.148
200642SENECA#1
50/50
1.552
20087026C_T85_W218
Adder
0.504
20083926HOMER C3
Adder
43.507
20083826HOMER C2
Adder
41.097
20083726HOMER C1
Adder
40.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.655
WECLTFEXP_WEC->PJM
CLTF
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
1.478
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.388
TVALTFEXP_TVA->PJM
CLTF
0.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.824
CPLELTFEXP_CPLE->PJM
CLTF
0.381
SIGELTFEXP_SIGE->PJM
CLTF
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.963
LGEELTFEXP_LGEE->PJM
CLTF
0.592
MECLTFEXP_MEC->PJM
CLTF
1.453

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P1-2_PN-115-094_A_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-115-094_A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.45 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:787.65
MW Contribution:2.88
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.492
20066526SHAWVL 3
50/50
2.473
20071526SHAWVL 1
50/50
1.676
962411AG1-090 GEN
Solar/Wind Harmer
6.8
972075AH1-587 GEN
Solar/Wind Harmer
16.919
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.4
972077AH1-588 GEN
Solar/Wind Harmer
16.686
203857AF2-221 C
Solar/Wind Harmer
0.63
970313AG2-206 GEN
Solar/Wind Harmer
2.334
203848AF2-166 C
Solar/Wind Harmer
0.967
944781AF1-143 GEN
Solar/Wind Harmer
0
20081226ALY HYDR
50/50
0.425
216419AE2-001 C
Solar/Wind Harmer
4.372
971441AH1-212 GEN
Solar/Wind Harmer
1.68
972079AH1-589 GEN
Solar/Wind Harmer
19.699
970715AG2-457 GEN
Solar/Wind Harmer
6.466
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.115
20398826ARMNA MT
Solar/Wind Harmer
0.028
946071AF1-272 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.197
203947AF1-006 C
Solar/Wind Harmer
0.028
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.402
238215AE2-248 C
Solar/Wind Harmer
3.596
203987AE2-118 C
Solar/Wind Harmer
3.732
203954AE2-126 C
Solar/Wind Harmer
0.002
20094526CT_V3-030
Solar/Wind Harmer
0.135
970713AG2-456 GEN
Solar/Wind Harmer
6.466
971705AH1-358 GEN
Solar/Wind Harmer
2.318
971709AH1-360 GEN
Solar/Wind Harmer
2.318
970631AG2-411 GEN
Solar/Wind Harmer
3.911
970337AG2-221 GEN
Solar/Wind Harmer
1.152
970511AG2-327 GEN
Solar/Wind Harmer
0.486
944411AF1-106 GEN
Solar/Wind Harmer
1.618
20084926LAKVU GN
Adder
0.107
200644SENECA#3
50/50
0.221
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
2.877
20334926Z1-069 C
Solar/Wind Harmer
0.455
971541AH1-268 GEN
Solar/Wind Harmer
3.577
203841AF2-001_GEN
Solar/Wind Harmer
1.115
20079426CONEMAGH
Adder
0.952
203932AE1-123
Adder
1.42
972271AH1-720 GEN
Adder
4.399
971355AH1-158 GEN
Solar/Wind Harmer
2.305
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.03
20084926LAKVU GN
Adder
0.107
238202AE2-262_GEN
Solar/Wind Harmer
0.012
20120126WRREN CT
Adder
6.346
971703AH1-357 GEN
Solar/Wind Harmer
1.391
971707AH1-359 GEN
Solar/Wind Harmer
1.391
970125AG2-091 GEN
Solar/Wind Harmer
0.36
971879AH1-460 GEN
Solar/Wind Harmer
3.839
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.558
970647AG2-420 GEN
Solar/Wind Harmer
0.907
20089026BF_G21_K23
Solar/Wind Harmer
0.03
20083126HNSMLK 4
Adder
3.459
203962AF1-287 GEN
Solar/Wind Harmer
0.815
202652Y1-033 WT C
Solar/Wind Harmer
0
971627AH1-313 GEN
Solar/Wind Harmer
18.178
965131AG1-378 GEN
Solar/Wind Harmer
1.36
960051AF2-296 GEN
Solar/Wind Harmer
2.213
203818AF1-086 GEN
Solar/Wind Harmer
0.743
971419AH1-201 GEN
Solar/Wind Harmer
2.358
945751AF1-240 GEN
Solar/Wind Harmer
1.024
971127AH1-005 GEN
Solar/Wind Harmer
1.136
971185AH1-051 GEN
Solar/Wind Harmer
1.383
957161AF2-010 GEN
Solar/Wind Harmer
3.367
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.124
20082926HNSMLK 2
Adder
3.459
200917MEHOOPANY_G
Solar/Wind Harmer
0.166
203975AE1-071-GEN
Solar/Wind Harmer
0.044
20090526Q36
Solar/Wind Harmer
0.654
203993AD2-133_GEN1
Solar/Wind Harmer
0.648
20091526CHSTN_FL
Solar/Wind Harmer
0.193
203804AE2-113_GEN
Solar/Wind Harmer
0.007
970555AG2-356 GEN
Solar/Wind Harmer
1.047
970677AG2-438 GEN
Solar/Wind Harmer
0.49
966771AG1-548 GEN
Solar/Wind Harmer
1.458
966771AG1-548 GEN
Solar/Wind Harmer
1.822
20088626ARWF_N39
Solar/Wind Harmer
0.002
970123AG2-090 GEN
Solar/Wind Harmer
0.84
20088926STNY CRK
Solar/Wind Harmer
0.114
971931AH1-490 GEN
Solar/Wind Harmer
0.803
970643AG2-418 GEN
Solar/Wind Harmer
6.667
970899AG2-561 GEN
Solar/Wind Harmer
1.261
20335126GROZ1-110
Adder
2.101
20335226CANZ2-011
Adder
2.042
238219AF1-167 C
Solar/Wind Harmer
0.667
203952AE2-129 C
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
971427AH1-205 GEN
Solar/Wind Harmer
1.572
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.877
203859AF2-294 C
Solar/Wind Harmer
0.732
203980AG1-197 GEN
Solar/Wind Harmer
0
238206AE2-263_GEN
Solar/Wind Harmer
0.011
20326126BLOSSBCT
Adder
1.865
971423AH1-203 GEN
Solar/Wind Harmer
3.977
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
2.305
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
3.459
20083026HNSMLK 3
Adder
3.459
209067AE2-060 GEN
Solar/Wind Helper
0.083
203961AE2-224 GEN
Solar/Wind Harmer
0.008
203844AF2-092 C
Solar/Wind Harmer
0.838
970663AG2-429 GEN
Solar/Wind Harmer
3.539
970663AG2-429 GEN
Solar/Wind Harmer
0.774
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.459
203926AA2-133 GEN
Adder
1.316
20091326SHAW-D
50/50
1.433
200643SENECA#2
50/50
1.605
970643AG2-418 GEN
Solar/Wind Harmer
4.444
957561AF2-050 GEN
Solar/Wind Harmer
5.45
238183AE2-316 GEN
Solar/Wind Harmer
0.005
971279AH1-102 GEN
Solar/Wind Harmer
6.197
20089226LOOKOUT
Solar/Wind Harmer
0.084
203813AE2-344_GEN
Solar/Wind Harmer
4.724
970267AG2-176 GEN
Solar/Wind Harmer
6.072
20072226SHAWVL 2
50/50
32.7
20064926PENNTECH
50/50
0.444
972169AH1-667 GEN
Solar/Wind Harmer
2.581
20088826HIGHLAND
Solar/Wind Harmer
0.001
203843AF2-002_GEN
Solar/Wind Harmer
0.558
20335026MILZ1-092
Adder
1.586
970647AG2-420 GEN
Solar/Wind Harmer
0.151
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.36
203850AG1-041 C
Solar/Wind Harmer
0.861
20092526R32
Solar/Wind Harmer
0.208
20334726NME_Y1-047
Adder
1.11
200642SENECA#1
50/50
1.721
20083926HOMER C3
Adder
48.691
20083826HOMER C2
Adder
45.994
20083726HOMER C1
Adder
45.416
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.969
TVALTFEXP_TVA->PJM
CLTF
0.645
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.763
WECLTFEXP_WEC->PJM
CLTF
0.329
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.494
LGEELTFEXP_LGEE->PJM
CLTF
0.556
MECLTFEXP_MEC->PJM
CLTF
1.368
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.533
CPLELTFEXP_CPLE->PJM
CLTF
0.203
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P12_000085_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P12_000085_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.27 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:786.5
MW Contribution:2.66
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.236
20071526SHAWVL 1
50/50
1.517
962411AG1-090 GEN
Solar/Wind Harmer
6.178
972075AH1-587 GEN
Solar/Wind Harmer
15.512
20390526W1-045 C
Solar/Wind Harmer
0.08
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.3
972077AH1-588 GEN
Solar/Wind Harmer
15.415
203857AF2-221 C
Solar/Wind Harmer
0.595
203848AF2-166 C
Solar/Wind Harmer
0.928
944781AF1-143 GEN
Solar/Wind Harmer
0
970313AG2-206 GEN
Solar/Wind Harmer
2.009
20081226ALY HYDR
50/50
0.384
216419AE2-001 C
Solar/Wind Harmer
3.937
971441AH1-212 GEN
Solar/Wind Harmer
1.558
972079AH1-589 GEN
Solar/Wind Harmer
18.198
970715AG2-457 GEN
Solar/Wind Harmer
5.973
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.059
946071AF1-272 GEN
Solar/Wind Harmer
0
20398826ARMNA MT
Solar/Wind Harmer
0.025
203963AG1-253 GEN
Solar/Wind Harmer
0.188
203947AF1-006 C
Solar/Wind Harmer
0.027
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.69
238215AE2-248 C
Solar/Wind Harmer
3.237
203987AE2-118 C
Solar/Wind Harmer
3.373
203954AE2-126 C
Solar/Wind Harmer
0.002
20094526CT_V3-030
Solar/Wind Harmer
0.126
970713AG2-456 GEN
Solar/Wind Harmer
5.973
971705AH1-358 GEN
Solar/Wind Harmer
2.141
971709AH1-360 GEN
Solar/Wind Harmer
2.141
970631AG2-411 GEN
Solar/Wind Harmer
3.708
970337AG2-221 GEN
Solar/Wind Harmer
1.002
944411AF1-106 GEN
Solar/Wind Harmer
1.417
970511AG2-327 GEN
Solar/Wind Harmer
0.419
20084926LAKVU GN
Adder
0.103
200644SENECA#3
50/50
0.204
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
2.662
971541AH1-268 GEN
Solar/Wind Harmer
3.386
20334926Z1-069 C
Solar/Wind Harmer
0.414
203841AF2-001_GEN
Solar/Wind Harmer
1.059
20079426CONEMAGH
Adder
0.904
203932AE1-123
Adder
1.36
971355AH1-158 GEN
Solar/Wind Harmer
2.218
20089126CSLMN_L13
Solar/Wind Harmer
0.029
20084926LAKVU GN
Adder
0.103
972271AH1-720 GEN
Adder
3.634
20328326MANOR_T86
Adder
0.077
212507AE2-042_GEN
Solar/Wind Helper
0.788
238202AE2-262_GEN
Solar/Wind Harmer
0.01
20120126WRREN CT
Adder
5.889
971703AH1-357 GEN
Solar/Wind Harmer
1.285
971707AH1-359 GEN
Solar/Wind Harmer
1.285
970125AG2-091 GEN
Solar/Wind Harmer
0.34
971879AH1-460 GEN
Solar/Wind Harmer
3.636
970647AG2-420 GEN
Solar/Wind Harmer
0.874
941421AE2-139 GEN
Solar/Wind Harmer
0
20089026BF_G21_K23
Solar/Wind Harmer
0.029
970335AG2-220 GEN
Solar/Wind Harmer
1.343
20083126HNSMLK 4
Adder
3.354
203962AF1-287 GEN
Solar/Wind Harmer
0.788
202652Y1-033 WT C
Solar/Wind Harmer
0
209071AE2-133 GEN
Solar/Wind Helper
0.041
971627AH1-313 GEN
Solar/Wind Harmer
16.392
965131AG1-378 GEN
Solar/Wind Harmer
1.236
960051AF2-296 GEN
Solar/Wind Harmer
2.025
203818AF1-086 GEN
Solar/Wind Harmer
0.688
971419AH1-201 GEN
Solar/Wind Harmer
2.232
945751AF1-240 GEN
Solar/Wind Harmer
0.973
971185AH1-051 GEN
Solar/Wind Harmer
1.331
957161AF2-010 GEN
Solar/Wind Harmer
3.237
203830AF1-094 GEN
Solar/Wind Harmer
0.001
971127AH1-005 GEN
Solar/Wind Harmer
0.979
203948AG1-140 C
Solar/Wind Harmer
0.119
20082926HNSMLK 2
Adder
3.354
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.596
203993AD2-133_GEN1
Solar/Wind Harmer
0.59
20091526CHSTN_FL
Solar/Wind Harmer
0.178
203804AE2-113_GEN
Solar/Wind Harmer
0.006
970555AG2-356 GEN
Solar/Wind Harmer
0.911
970677AG2-438 GEN
Solar/Wind Harmer
0.471
966771AG1-548 GEN
Solar/Wind Harmer
1.401
966771AG1-548 GEN
Solar/Wind Harmer
1.752
20088626ARWF_N39
Solar/Wind Harmer
0.002
970123AG2-090 GEN
Solar/Wind Harmer
0.794
20088926STNY CRK
Solar/Wind Harmer
0.108
971931AH1-490 GEN
Solar/Wind Harmer
0.778
946751AF1-339 GEN
Solar/Wind Helper
0.225
970643AG2-418 GEN
Solar/Wind Harmer
4.603
970899AG2-561 GEN
Solar/Wind Harmer
1.189
20335126GROZ1-110
Adder
1.817
20335226CANZ2-011
Adder
1.766
238219AF1-167 C
Solar/Wind Harmer
0.641
946731AF1-337 GEN
Solar/Wind Helper
0.225
203952AE2-129 C
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
203982AD2-062_GEN
Solar/Wind Harmer
5.202
971427AH1-205 GEN
Solar/Wind Harmer
1.488
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.843
203980AG1-197 GEN
Solar/Wind Harmer
0
203859AF2-294 C
Solar/Wind Harmer
0.627
209054AE2-059 GEN
Solar/Wind Helper
0.04
203961AE2-224 GEN
Solar/Wind Harmer
0.008
203844AF2-092 C
Solar/Wind Harmer
0.785
970663AG2-429 GEN
Solar/Wind Harmer
3.405
970663AG2-429 GEN
Solar/Wind Harmer
0.744
20084926LAKVU GN
Adder
0.116
20083226HNSMLK 5
Adder
3.354
203926AA2-133 GEN
Adder
1.058
959421AF2-233 GEN
Solar/Wind Helper
0.226
238206AE2-263_GEN
Solar/Wind Harmer
0.01
971423AH1-203 GEN
Solar/Wind Harmer
3.774
20326126BLOSSBCT
Adder
1.644
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
2.218
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
3.354
20083026HNSMLK 3
Adder
3.354
209067AE2-060 GEN
Solar/Wind Helper
0.1
20091326SHAW-D
50/50
1.299
200643SENECA#2
50/50
1.48
970643AG2-418 GEN
Solar/Wind Harmer
3.069
957561AF2-050 GEN
Solar/Wind Harmer
5.007
238183AE2-316 GEN
Solar/Wind Harmer
0.004
971279AH1-102 GEN
Solar/Wind Harmer
5.865
20089226LOOKOUT
Solar/Wind Harmer
0.082
970267AG2-176 GEN
Solar/Wind Harmer
5.887
203813AE2-344_GEN
Solar/Wind Harmer
4.571
946691AF1-333 GEN
Solar/Wind Helper
0.225
946741AF1-338 GEN
Solar/Wind Helper
0.225
20072226SHAWVL 2
50/50
29.562
20064926PENNTECH
50/50
0.404
972169AH1-667 GEN
Solar/Wind Harmer
2.339
20088826HIGHLAND
Solar/Wind Harmer
0.001
203843AF2-002_GEN
Solar/Wind Harmer
0.53
970647AG2-420 GEN
Solar/Wind Harmer
0.146
20335026MILZ1-092
Adder
1.389
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.236
203850AG1-041 C
Solar/Wind Harmer
0.805
20092526R32
Solar/Wind Harmer
0.195
23732901CHBRG_I12
Adder
1.103
959431AF2-234 GEN
Solar/Wind Helper
0.452
200642SENECA#1
50/50
1.586
20087026C_T85_W218
Adder
0.48
20083926HOMER C3
Adder
46.584
20083826HOMER C2
Adder
44.004
20083726HOMER C1
Adder
43.869
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.461
NYPJM->LTFIMP_NY
CLTF
0.234
TVALTFEXP_TVA->PJM
CLTF
0.986
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.818
WECLTFEXP_WEC->PJM
CLTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
1.999
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.334
LGEELTFEXP_LGEE->PJM
CLTF
0.793
MECLTFEXP_MEC->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.946
CPLELTFEXP_CPLE->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.06

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P1-2_WP-230-005A_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-230-005A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.13 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:617.14
MW Contribution:2.06
Bus #Bus NameTypeMW Contribution
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
962411AG1-090 GEN
Solar/Wind Harmer
5.11
972075AH1-587 GEN
Solar/Wind Harmer
14.367
970305AG2-200 GEN
Solar/Wind Harmer
1.167
203954AE2-126 C
Solar/Wind Harmer
0.002
970713AG2-456 GEN
Solar/Wind Harmer
5.007
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
970337AG2-221 GEN
Solar/Wind Harmer
0.94
970511AG2-327 GEN
Solar/Wind Harmer
0.398
944411AF1-106 GEN
Solar/Wind Harmer
1.254
20084926LAKVU GN
Adder
0.076
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
5.007
20398826ARMNA MT
Solar/Wind Harmer
0.022
203963AG1-253 GEN
Solar/Wind Harmer
0.14
971627AH1-313 GEN
Solar/Wind Harmer
14.553
965131AG1-378 GEN
Solar/Wind Harmer
1.022
960051AF2-296 GEN
Solar/Wind Harmer
1.915
203818AF1-086 GEN
Solar/Wind Harmer
0.531
971127AH1-005 GEN
Solar/Wind Harmer
0.928
945751AF1-240 GEN
Solar/Wind Harmer
0.587
200917MEHOOPANY_G
Solar/Wind Harmer
0.157
200644SENECA#3
50/50
0.189
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
2.056
20334926Z1-069 C
Solar/Wind Harmer
0.346
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
203932AE1-123
Adder
0.907
20084926LAKVU GN
Adder
0.076
972077AH1-588 GEN
Solar/Wind Harmer
12.921
970313AG2-206 GEN
Solar/Wind Harmer
1.911
203848AF2-166 C
Solar/Wind Harmer
0.617
20390526W1-045 C
Solar/Wind Helper
0.177
20335126GROZ1-110
50/50
1.989
20335226CANZ2-011
50/50
1.933
238219AF1-167 C
Solar/Wind Harmer
0.456
970899AG2-561 GEN
Solar/Wind Harmer
0.639
20120126WRREN CT
50/50
5.61
238202AE2-262_GEN
Solar/Wind Harmer
0.009
971703AH1-357 GEN
Solar/Wind Harmer
1.077
971707AH1-359 GEN
Solar/Wind Harmer
1.077
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.273
203804AE2-113_GEN
Solar/Wind Harmer
0.006
20090526Q36
Solar/Wind Harmer
0.352
203993AD2-133_GEN1
Solar/Wind Harmer
0.348
970555AG2-356 GEN
Solar/Wind Harmer
0.854
966771AG1-548 GEN
Solar/Wind Harmer
1.004
966771AG1-548 GEN
Solar/Wind Harmer
1.255
970677AG2-438 GEN
Solar/Wind Harmer
0.336
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
203948AG1-140 C
Solar/Wind Harmer
0.088
203830AF1-094 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
2.306
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
0.575
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.602
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
2.332
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20084926LAKVU GN
Adder
0.086
20326126BLOSSBCT
50/50
1.6
238206AE2-263_GEN
Solar/Wind Harmer
0.009
203835AF1-098 GEN
Solar/Wind Harmer
0.002
20091326SHAW-D
50/50
1.415
200643SENECA#2
50/50
1.376
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20072226SHAWVL 2
50/50
35.26
20064926PENNTECH
50/50
0.417
972169AH1-667 GEN
Solar/Wind Harmer
2.548
20335026MILZ1-092
Adder
1.229
964391AG1-301 GEN
Solar/Wind Helper
0.232
200642SENECA#1
50/50
1.475
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.022
20334726NME_Y1-047
Adder
1.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
WECLTFEXP_WEC->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
LGEELTFEXP_LGEE->PJM
CLTF
0.188
MECLTFEXP_MEC->PJM
CLTF
0.47

Details for 26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line l/o AP_P1-3_WP-230-005_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_WP-230-005_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.12 %
Rating:587.0 MVA
Rating Type:B
MVA to Mitigate:617.05
MW Contribution:2.06
Bus #Bus NameTypeMW Contribution
203954AE2-126 C
Solar/Wind Harmer
0.002
970713AG2-456 GEN
Solar/Wind Harmer
5.007
971705AH1-358 GEN
Solar/Wind Harmer
1.795
971709AH1-360 GEN
Solar/Wind Harmer
1.795
970337AG2-221 GEN
Solar/Wind Harmer
0.94
970511AG2-327 GEN
Solar/Wind Harmer
0.398
944411AF1-106 GEN
Solar/Wind Harmer
1.254
20084926LAKVU GN
Adder
0.076
972079AH1-589 GEN
Solar/Wind Harmer
15.254
970715AG2-457 GEN
Solar/Wind Harmer
5.007
20398826ARMNA MT
Solar/Wind Harmer
0.022
203963AG1-253 GEN
Solar/Wind Harmer
0.14
200644SENECA#3
50/50
0.189
203854AF2-039 C
Solar/Wind Harmer
0.001
972323AH1-746 GEN
Solar/Wind Harmer
2.056
20334926Z1-069 C
Solar/Wind Harmer
0.346
972271AH1-720 GEN
Adder
4.049
20328326MANOR_T86
Adder
0.082
203932AE1-123
Adder
0.907
20084926LAKVU GN
Adder
0.076
20066626SHAWVL 4
50/50
2.687
20066526SHAWVL 3
50/50
2.647
20071526SHAWVL 1
50/50
1.73
962411AG1-090 GEN
Solar/Wind Harmer
5.11
972075AH1-587 GEN
Solar/Wind Harmer
14.367
970305AG2-200 GEN
Solar/Wind Harmer
1.167
972077AH1-588 GEN
Solar/Wind Harmer
12.921
970313AG2-206 GEN
Solar/Wind Harmer
1.911
203848AF2-166 C
Solar/Wind Harmer
0.617
20390526W1-045 C
Solar/Wind Helper
0.177
20335126GROZ1-110
50/50
1.989
20335226CANZ2-011
50/50
1.933
238219AF1-167 C
Solar/Wind Harmer
0.456
970899AG2-561 GEN
Solar/Wind Harmer
0.639
20120126WRREN CT
50/50
5.61
238202AE2-262_GEN
Solar/Wind Harmer
0.009
971703AH1-357 GEN
Solar/Wind Harmer
1.077
971707AH1-359 GEN
Solar/Wind Harmer
1.077
941421AE2-139 GEN
Solar/Wind Harmer
0
970335AG2-220 GEN
Solar/Wind Harmer
1.273
203804AE2-113_GEN
Solar/Wind Harmer
0.006
20090526Q36
Solar/Wind Harmer
0.352
203993AD2-133_GEN1
Solar/Wind Harmer
0.348
970555AG2-356 GEN
Solar/Wind Harmer
0.854
966771AG1-548 GEN
Solar/Wind Harmer
1.004
966771AG1-548 GEN
Solar/Wind Harmer
1.255
970677AG2-438 GEN
Solar/Wind Harmer
0.336
203975AE1-071-GEN
Solar/Wind Helper
1.795
959381AF2-229 GEN
Solar/Wind Helper
0.181
971627AH1-313 GEN
Solar/Wind Harmer
14.553
965131AG1-378 GEN
Solar/Wind Harmer
1.022
960051AF2-296 GEN
Solar/Wind Harmer
1.915
203818AF1-086 GEN
Solar/Wind Harmer
0.531
971127AH1-005 GEN
Solar/Wind Harmer
0.928
945751AF1-240 GEN
Solar/Wind Harmer
0.587
200917MEHOOPANY_G
Solar/Wind Harmer
0.157
203948AG1-140 C
Solar/Wind Harmer
0.088
203830AF1-094 GEN
Solar/Wind Harmer
0
957161AF2-010 GEN
Solar/Wind Harmer
2.306
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
0.575
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.602
203926AA2-133 GEN
Adder
1.206
970663AG2-429 GEN
Solar/Wind Harmer
2.332
970663AG2-429 GEN
Solar/Wind Harmer
0.51
20084926LAKVU GN
Adder
0.086
20326126BLOSSBCT
50/50
1.6
238206AE2-263_GEN
Solar/Wind Harmer
0.009
203835AF1-098 GEN
Solar/Wind Harmer
0.002
20091326SHAW-D
50/50
1.415
200643SENECA#2
50/50
1.376
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20072226SHAWVL 2
50/50
35.26
20064926PENNTECH
50/50
0.417
972169AH1-667 GEN
Solar/Wind Harmer
2.548
20335026MILZ1-092
Adder
1.229
964391AG1-301 GEN
Solar/Wind Helper
0.232
200642SENECA#1
50/50
1.475
20083926HOMER C3
Adder
19.376
20083826HOMER C2
Adder
18.303
20083726HOMER C1
Adder
9.828
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.022
20334726NME_Y1-047
Adder
1.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.104
WECLTFEXP_WEC->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
0.385
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.547
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.185
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.754
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.032
LGEELTFEXP_LGEE->PJM
CLTF
0.188
MECLTFEXP_MEC->PJM
CLTF
0.47

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.65
MW Contribution:5.8
Bus #Bus NameTypeMW Contribution
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20094526CT_V3-030
Solar/Wind Harmer
0.328
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
203954AE2-126 C
Solar/Wind Harmer
0.002
944411AF1-106 GEN
Solar/Wind Harmer
3.837
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238215AE2-248 C
Solar/Wind Harmer
1.499
20084926LAKVU GN
Adder
0.214
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
4.03
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
216419AE2-001 C
Solar/Wind Harmer
1.896
20079426CONEMAGH
Adder
3.775
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20334926Z1-069 C
Solar/Wind Harmer
1.023
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971355AH1-158 GEN
Solar/Wind Harmer
5.546
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
972271AH1-720 GEN
Adder
7.484
970679AG2-439 GEN
Solar/Wind Harmer
0.491
203857AF2-221 C
Solar/Wind Harmer
2.266
203940AF1-140 C
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
970313AG2-206 GEN
Solar/Wind Harmer
5.051
20083326SEWRDB34
50/50
11.336
970899AG2-561 GEN
Solar/Wind Harmer
3.875
238219AF1-167 C
Solar/Wind Harmer
1.377
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
20089026BF_G21_K23
Solar/Wind Harmer
0.108
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20083126HNSMLK 4
Adder
10.299
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
238202AE2-262_GEN
Solar/Wind Harmer
0.006
203962AF1-287 GEN
Solar/Wind Harmer
1.756
941421AE2-139 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.402
203947AF1-006 C
Solar/Wind Harmer
0.056
20063626IUP CO-G
50/50
0.269
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
203804AE2-113_GEN
Solar/Wind Harmer
0.01
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20216026CON.GEN2
50/50
0.034
971419AH1-201 GEN
Solar/Wind Harmer
7.878
203818AF1-086 GEN
Solar/Wind Harmer
1.499
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20082926HNSMLK 2
Adder
10.299
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971127AH1-005 GEN
Solar/Wind Harmer
2.467
971627AH1-313 GEN
Solar/Wind Harmer
10.129
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
1.807
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
20080926SITHE
50/50
0.88
970123AG2-090 GEN
Solar/Wind Harmer
3.021
20088926STNY CRK
Solar/Wind Harmer
0.38
20088626ARWF_N39
Solar/Wind Harmer
0.003
971931AH1-490 GEN
Solar/Wind Harmer
1.751
20215826CON.GEN1
50/50
0.045
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
20083226HNSMLK 5
Adder
10.299
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
971055AG2-654 GEN
Solar/Wind Harmer
0.567
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20326126BLOSSBCT
Adder
3.813
971183AH1-050 GEN
Solar/Wind Harmer
5.546
203860AG1-193 C
Solar/Wind Harmer
0.001
238206AE2-263_GEN
Solar/Wind Harmer
0.006
203835AF1-098 GEN
Solar/Wind Harmer
0.006
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
20089226LOOKOUT
Solar/Wind Harmer
0.305
20091326SHAW-D
Adder
1.15
238183AE2-316 GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
203813AE2-344_GEN
Solar/Wind Harmer
10.181
203843AF2-002_GEN
Solar/Wind Harmer
2.147
20088826HIGHLAND
Solar/Wind Harmer
0.002
972169AH1-667 GEN
Solar/Wind Harmer
2.196
20335026MILZ1-092
Adder
3.761
20072226SHAWVL 2
Adder
21.555
970647AG2-420 GEN
Solar/Wind Harmer
0.365
24035802GEN-Y1-012
Adder
0.244
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
20083726HOMER C1
50/50
273.666
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20390726Y2-042
Adder
1.869
20092526R32
Solar/Wind Harmer
0.638
203850AG1-041 C
Solar/Wind Harmer
2.443
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203855AF2-088 C
Solar/Wind Harmer
0.001
20334726NME_Y1-047
Adder
2.326
961581Q1080_CY23
External Queue
26.08061408996582
LGEELTFEXP_LGEE->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.037
MECLTFEXP_MEC->PJM
CLTF
0.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.63
MW Contribution:5.8
Bus #Bus NameTypeMW Contribution
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20079426CONEMAGH
Adder
3.775
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20334926Z1-069 C
Solar/Wind Harmer
1.023
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971355AH1-158 GEN
Solar/Wind Harmer
5.546
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
972271AH1-720 GEN
Adder
7.484
970679AG2-439 GEN
Solar/Wind Harmer
0.491
203857AF2-221 C
Solar/Wind Harmer
2.266
20083326SEWRDB34
50/50
11.336
970899AG2-561 GEN
Solar/Wind Harmer
3.875
238219AF1-167 C
Solar/Wind Harmer
1.377
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
203940AF1-140 C
Solar/Wind Harmer
0.002
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
20089026BF_G21_K23
Solar/Wind Harmer
0.108
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20083126HNSMLK 4
Adder
10.299
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
238202AE2-262_GEN
Solar/Wind Harmer
0.006
203962AF1-287 GEN
Solar/Wind Harmer
1.756
941421AE2-139 GEN
Solar/Wind Harmer
0
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
4.03
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
216419AE2-001 C
Solar/Wind Harmer
1.896
203963AG1-253 GEN
Solar/Wind Harmer
0.402
203947AF1-006 C
Solar/Wind Harmer
0.056
20063626IUP CO-G
50/50
0.269
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
203804AE2-113_GEN
Solar/Wind Harmer
0.01
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20216026CON.GEN2
50/50
0.034
971419AH1-201 GEN
Solar/Wind Harmer
7.878
203818AF1-086 GEN
Solar/Wind Harmer
1.499
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20082926HNSMLK 2
Adder
10.299
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971127AH1-005 GEN
Solar/Wind Harmer
2.467
971627AH1-313 GEN
Solar/Wind Harmer
10.129
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203952AE2-129 C
Solar/Wind Harmer
0.002
203859AF2-294 C
Solar/Wind Harmer
1.807
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
20080926SITHE
50/50
0.88
970123AG2-090 GEN
Solar/Wind Harmer
3.021
20088926STNY CRK
Solar/Wind Harmer
0.38
20088626ARWF_N39
Solar/Wind Harmer
0.003
971931AH1-490 GEN
Solar/Wind Harmer
1.751
20094526CT_V3-030
Solar/Wind Harmer
0.328
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
203954AE2-126 C
Solar/Wind Harmer
0.002
944411AF1-106 GEN
Solar/Wind Harmer
3.837
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238215AE2-248 C
Solar/Wind Harmer
1.499
20084926LAKVU GN
Adder
0.214
20215826CON.GEN1
50/50
0.045
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
20083226HNSMLK 5
Adder
10.299
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
971055AG2-654 GEN
Solar/Wind Harmer
0.567
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20326126BLOSSBCT
Adder
3.813
971183AH1-050 GEN
Solar/Wind Harmer
5.546
203860AG1-193 C
Solar/Wind Harmer
0.001
238206AE2-263_GEN
Solar/Wind Harmer
0.006
203835AF1-098 GEN
Solar/Wind Harmer
0.006
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
970313AG2-206 GEN
Solar/Wind Harmer
5.051
203843AF2-002_GEN
Solar/Wind Harmer
2.147
20088826HIGHLAND
Solar/Wind Harmer
0.002
972169AH1-667 GEN
Solar/Wind Harmer
2.196
20335026MILZ1-092
Adder
3.761
20072226SHAWVL 2
Adder
21.555
970647AG2-420 GEN
Solar/Wind Harmer
0.365
24035802GEN-Y1-012
Adder
0.244
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
20089226LOOKOUT
Solar/Wind Harmer
0.305
20091326SHAW-D
Adder
1.15
238183AE2-316 GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
203813AE2-344_GEN
Solar/Wind Harmer
10.181
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
20083726HOMER C1
50/50
273.666
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20390726Y2-042
Adder
1.869
20092526R32
Solar/Wind Harmer
0.638
203850AG1-041 C
Solar/Wind Harmer
2.443
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203855AF2-088 C
Solar/Wind Harmer
0.001
20334726NME_Y1-047
Adder
2.326
961581Q1080_CY23
External Queue
26.08061408996582
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LGEELTFEXP_LGEE->PJM
CLTF
0.014
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
SIGELTFEXP_SIGE->PJM
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0.037
MECLTFEXP_MEC->PJM
CLTF
0.096
CONTINGENCY 'AP_P1-2_WP-500-008_SRT-A'
 DISCONNECT BRANCH FROM BUS 235116 TO BUS 235118 CKT 1   /*01YUKON      500.0 - 01SOBEND     500.0
END
CONTINGENCY 'AP_P1-2_WP-138-056_SRT-A'
 DISCONNECT BRANCH FROM BUS 235241 TO BUS 235794 CKT 2   /*01SALTSB     138.0 - 01SALTSBRG    25.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235241 CKT 1   /*01SOCIAL     138.0 - 01SALTSB     138.0
END
CONTINGENCY 'PN_P1-2_PN-230-020A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200517 CKT 1   /*26LEWISTWN   230.0 - 26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-019_SRT-A'
 DISCONNECT BRANCH FROM BUS 200500 TO BUS 200517 CKT 1   /*26ALTOONA    230.0 - 26RAYSTOWN   230.0
END
CONTINGENCY 'PN_P1-2_PN-230-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 200912 TO BUS 200793 CKT 1   /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P1-3_PN-500-003_SRT-A'
 OPEN BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P1-2_PN-115-094_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
END
CONTINGENCY 'PL_10_P12_000085_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 200011 CKT 1   /*JUNI         500.0 - KEYSTONE     500.0
END
CONTINGENCY 'AP_P1-2_WP-230-005A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1   /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
CONTINGENCY 'AP_P1-3_WP-230-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 235219 TO BUS 236745 CKT 82   /*01MILESB     230.0 - 01MILESBG     46.0
 DISCONNECT BRANCH FROM BUS 238198 TO BUS 235219 CKT 1    /*AE2-262_TAP  230.0 - 01MILESB     230.0
END
235173 to 235618 ckt 1
235248 to 200513 ckt 1
235596 to 235173 ckt 1
200767 to 200795 ckt 1
200513 to 208004 ckt 1
200726 to 235248 ckt 1
200795 to 200810 ckt 1

Winter Peak Analysis

The New Service Request AH1-746 was evaluated as a 0.0 MW (20.0 MW Capacity) injection in the PENELEC area.

AH1-746 was evaluated as part of a plant. The plant consists of AH1-746. The total Energy output of the plant was evaluated at its maximum seasonal capability of 109.9 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-746 was evaluated as a 0.0 MW injection

AH1-746 was evaluated as part of a plant. The plant consists of AH1-746. The total Energy output of the plant was evaluated at its maximum seasonal capability of 109.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA2-133Wyalusing 34.5kVIn Service
AD2-062Roxbury-Greene 138 kVSuspended
AD2-133Eagle Valley 115kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-123Emlenton 34.5 kVIn Service
AE2-001Nittany-Zion 46 kVSuspended
AE2-042Milton 69 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-316Brookville-Squab Hollow 138 kVUnder Construction
AE2-344Edinboro South-Venango Junction 115 kVSuspended
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-106East Sayre 34.5 kVWithdrawn
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-167West Freedom-C&K Coal 25 kVSuspended
AF1-240Timblin 34.5 kVActive
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-287Edinboro South 34.5 kV IISuspended
AF1-321Hooversville 115 kV ISuspended
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-010Union City-Titusville 115 kVActive
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-050Bear Rock-Johnstown 230 kVActive
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-092Snake Spring-Bedford Area 23 kVSuspended
AF2-166Emlenton 34.5 kVWithdrawn
AF2-221Scalp Level 22.9 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVActive
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AG1-041Osterburg-Bedford North 23 kVWithdrawn
AG1-090Philipsburg 115 kVActive
AG1-140Union City 34.5 kVSuspended
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-253Erie East-Union City 34.5 kVSuspended
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-377Philipsburg 115 kVActive
AG1-378Philipsburg 115 kVActive
AG1-548Erie South-Union City 115 kVActive
AG2-090Scalp Level 23 kV IVActive
AG2-091Scalp Level 23 kV VActive
AG2-176Geneva 115 kVActive
AG2-200North Warren–Russell 34.5 kVActive
AG2-206Tennessee Gas-East Towanda 115 kVActive
AG2-220East Towanda-South Troy 115 kVActive
AG2-221South Troy - North Towanda 34.5 kVActive
AG2-327Tennessee Gas-East Towanda 115 kVActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-411Statler Hill 115 kVActive
AG2-418Blain 115 kVActive
AG2-420Eclipse #2 34.5 kVActive
AG2-429Burma - Armstrong 138 kVActive
AG2-438Union City 34.5 kVActive
AG2-439Oxbow 34.5 kVActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AG2-654Craigsville - Leards Crossing 12 kVActive
AH1-005East Towanda-South Troy 115 kV IIActive
AH1-050Eclipse-Piney 115 kVActive
AH1-051Eclipse-Piney 115 kV IIActive
AH1-102Seward-Glory 115 kVActive
AH1-140Vasco 138 kVActive
AH1-158Eclipse-Piney 115 kV IIIActive
AH1-201Allegheny-New Baltimore 115kVActive
AH1-203Allegheny-Somerset 115 kVActive
AH1-205Allegheny-New Baltimore 115kVActive
AH1-212Bethlehem - Lilly 46 kVActive
AH1-268Seward-Glory 115 kV IIActive
AH1-313Moshannon-Milesburg 230 kV VIIActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-452Clementine-Clementine Jct. 25 kVActive
AH1-460Hooversville - Scalp Level 115 kVActive
AH1-490Venango Junction 34.5 kVActive
AH1-491Union City 34.5 kVActive
AH1-587Farmers Valley – Ridgeway 115 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
AH1-720East Towanda 230 kVActive
Y1-033Penn Mar-Rock Wood 115kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-018
Title
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Description
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Total Cost ($USD)
$5,581,666
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / WP-AF2-F-0010
Title
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Description
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Total Cost ($USD)
$19,555,226
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
01EDGEWT-01VASC T 138.0 kV Ckt 1 line(Any)

System Reinforcement: n9116.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9116.0 / TC1-PN-001.d
Title
Rebuild approximately 11 miles of the Homer City-Shelocta 230 kV line with double bundled 795 kcmil 26/7 ACSS conductor
Description
Rebuild the Homer City – Shelocta 230 kV Line, approximately 11 miles, with double bunded 795 kcmil 26/7 ACSS conductor. Terminate new conductor at Homer City substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$39,312,233
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.d
Title
Replace Disc Switches at Shingletown
Description
Replace (2) 1200 Amp 230 kV Disc Switches (LWT_BUS & LWT_LINE) at Shingletown This project has a pre-req of TC2-APS-034.c
Total Cost ($USD)
$711,556
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.a
Title
Replace Bus Riser and Bus Side Disc Leads at Shingletown
Description
Replace (1) 230 kV Bus Riser and (1) 230 kV Bus Side Disc Leads at Shingletown
Total Cost ($USD)
$427,516
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.b
Title
Replace Bus Riser at Shingletown
Description
Replace (1) 230 kV Bus Riser at Shingletown This project has pre-req TC2-APS-034.a
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-034.c
Title
Reconductor Shingletown - Lewistown 230kV line including T-line drop at Shingletown
Description
Reconductor (Possible Rebuild) ~14.4 miles of Shingletown - Lewistown 230kV line [APS Side] including T-line drop at Shingletown This project has a pre-req of TC2-APS-034.b
Total Cost ($USD)
$73,419,183
Allocated Cost ($USD)
$0
Time Estimate
55 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-PN-002.a
Title
Reconductor Shingletown - Lewistown 230kV line [PN Side]
Description
Reconductor (Possible Rebuild) ~11.7 miles of Shingletown - Lewistown 230kV line [PN Side]
Total Cost ($USD)
$58,911,069
Allocated Cost ($USD)
$0
Time Estimate
49 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement: s0945.1
Type
Load Flow
TO
PPL
RTEP ID / TO ID
s0945.1
Title
Rebuild the Juniata 230/69 kV Substation
Description
None
Cost Information
Time Estimate
Dec 31 2025

Not Contingent

Note: AH1-746 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-746 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6818
Type
Load Flow
TO
PPL
RTEP ID / TO ID
n6818
Title
Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.
Description
The FE portion of the line is rated at 546/666 MVA SN/SE. The PPL portion is limiting, which requires n6818. Reinforcement scope no longer includes any substation scope as Juniata 230kV substation is being rebuilt under S0945.1. Actual PPL facility ratings after upgrade: 1245/1431 MVA SN/SE (FE facilities are more limiting)
Total Cost ($USD)
$3,600,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6817.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6817.1
Title
Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line
Description
Total Cost ($USD)
$122,656,404
Allocated Cost ($USD)
$0
Time Estimate
81 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-001.a
Title
Replace 230 kV bus conductor at Shawville
Description
Replace 230 kV bus conductor at Shawville
Total Cost ($USD)
$696,930
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-020.a
Title
Replace Bus Risers at Shingletown substation
Description
Replace (2) Bus Risers at Shingletown substation There is a pre-req for this project TC2-PN-001.a (FE-East Penelec project)
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHAWVL 2-01SHINGL 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9119.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9119.0 / TC1-PN-003.b
Title
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor
Description
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor. Terminate new conductor at Keystone substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$9,533,592
Allocated Cost ($USD)
$0
Time Estimate
23 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-746 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-746 could receive cost allocation. Although AH1-746 may not presently have cost responsibility for this upgrade, AH1-746 is a potential Aggregate Pool Contributor.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

Attachments

AH1-746 One Line Diagram

AH1-746 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.