AG2-124 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:03

Shackleford-Harmony 115 kV

33.34 MW Capacity / 0.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $190,117 $0 = ∞ AND ( $190,117 - $0 ) 33.3 = $5,702 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — King and Queen County, Virginia. This project is an increase to the developer’s AC1-065/AC2-110/AD2-039/AE1-004/AE2-005/AF1-014 project(s), which will share the same Point of Interconnection. The AG2-124 project is a 33.34 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 149.9 MW with 89.94 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-124
Project Name:
Shackleford-Harmony 115 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
King and Queen
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
149.9
MWE:
0.0
MWC:
33.34
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-124 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system as an uprate to AC1-065, AC2-110, AD2-039, AE1-004, AE2-005, and AF1-014 sharing the POI and Interconnection Facilities.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-124 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-124Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$190,117$190,117$190,117
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$190,117$190,117$190,117

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-124

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-124
Project ID: AG2-124
20% of cost allocation for Phase II Network Upgrades:(A) $38,023
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $133,360
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This project is to increase the metering CT ratio from 500/5 to 1000/5 due to the increase in MW at the AC1-065 collector station supporting the addition of Project Developer’s new solar farm AG2-124.

$136,887$37,726$14,963$541$190,117$190,117
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$190,117$190,117
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 15 to 16 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-124 was evaluated as a 0.0 MW (33.34 MW Capacity) injection in the Dominion area.

AG2-124 was evaluated as part of a plant. The plant consists of AG2-124. The total Energy output of the plant was evaluated at its maximum seasonal capability of 149.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6NORNECK-TX#4_SRT-A
SingleAC101.95 %177.38B180.83
3.54

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.95 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:180.83
MW Contribution:
3.54
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.64 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:178.51
MW Contribution:
3.24
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
9.279
3150341NORNECKC1
50/50
9.205
3141843SHACKLE
50/50
0.035
3150351NORNECKC2
50/50
8.982
966661AG1-536 GEN
50/50
20.585
3141843SHACKLE
50/50
0.644
315749AE2-041 GEN
50/50
2.877
3141873WAN 176
Solar/Wind Harmer
3.343
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
1.079
316223AC1-118
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
315759AF1-018 GEN
50/50
2.877
3141813NORNECK
Solar/Wind Harmer
0.834
3141783LANCAST
Solar/Wind Harmer
0.237
3141783LANCAST
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.099
3141913WHIT STONE
Solar/Wind Harmer
0.301
3141873WAN 176
Solar/Wind Harmer
0.038
970189AG2-124 GEN
Solar/Wind Harmer
3.545
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316156AD2-030 GEN
Solar/Wind Harmer
0.138
3150351NORNECKC2
50/50
8.834
316404AE1-155 C
Solar/Wind Harmer
-0.003
958261AF2-120 GEN
Solar/Wind Harmer
23.93
962861AG1-135 GEN
Solar/Wind Harmer
22.115
3138133OCRAN
Solar/Wind Harmer
0.198
971777AH1-397 GEN
Solar/Wind Harmer
0.314
3141766HARMONY
Solar/Wind Harmer
0.016
316337AD2-073 GEN
Solar/Wind Helper
0.192
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.032
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.098
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.077
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.06
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.125
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
314181 to 314182 ckt 2

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2157_SRT-A
SingleAC118.15 %717.22B847.37
2.69
GD2DVP
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2104_SRT-A
SingleAC112.28 %717.22B805.32
2.69
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC108.7 %559.3B607.94
4.08
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.3 %548.02B681.17
4.08
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.53 %548.02B578.33
4.09
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC109.98 %548.02B602.71
4.08
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC131.8 %1331.98B1755.6
2.5
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 557_SRT-S
SingleAC103.69 %888.3B921.03
4.42
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
SingleAC104.2 %879.84B916.78
4.41
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.22 %548.02B680.73
4.08
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.43 %548.02B577.77
4.09
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC166.0 %1123.3B1864.65
3.08
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC112.47 %1123.3B1263.35
2.05
GD2DVP
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
DVP_P1-2: LN 9296_SRT-A
SingleAC106.35 %984.18B1046.68
2.94
GD2DVP
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
DVP_P1-2: LN 2119_SRT-A
SingleAC106.33 %984.18B1046.51
2.94
GD2DVP
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
DVP_P1-2: LN 2157_SRT-A
SingleAC109.58 %717.22B785.94
2.69
GD2DVP
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
DVP_P1-2: LN 2104_SRT-A
SingleAC103.55 %717.22B742.66
2.69
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC121.76 %1057.5B1287.59
2.78
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.35 %571.52B590.65
4.09
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC101.15 %571.52B578.11
4.09
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC120.71 %1478.62B1784.89
3.08
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC121.88 %1478.62B1802.21
2.5
GD2DVP
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.61 %571.52B575.03
4.09
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC127.62 %3220.44B4109.92
4.42
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC115.29 %3220.44B3712.91
4.71
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC119.54 %4070.2B4865.39
6.86
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC113.04 %4070.2B4600.84
6.77
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC128.38 %2442.12B3135.29
9.29
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC127.71 %2442.12B3118.81
8.78
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC159.03 %4070.2B6472.73
10.29
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC141.11 %4070.2B5743.4
8.8
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC109.7 %4070.2A4464.82
7.94
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC116.05 %4070.2B4723.52
7.0
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC114.79 %4070.2B4672.2
6.77
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC121.15 %3220.44B3901.64
5.1
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC120.7 %3220.44B3887.02
5.12
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC159.65 %3220.44B5141.33
7.21
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC122.54 %3220.44B3946.36
6.38
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC101.48 %3193.18A3240.38
4.44
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC154.87 %3220.44B4987.58
6.72
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC154.04 %3220.44B4960.85
6.86
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC108.67 %3193.18A3470.14
4.84
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC161.05 %3220.44B5186.56
6.73
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC156.69 %3220.44B5046.02
6.62
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC115.83 %3220.44A3730.18
4.75
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.16 %1478.62B1835.89
3.08
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC104.8 %571.52B598.97
4.08
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC112.93 %559.3B631.64
4.08

Details for 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:847.37
MW Contribution:
2.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
0.048
3150411LDYSMT5
50/50
22.395
3150381LDYSMT2
50/50
21.433
972213AH1-691 GEN
50/50
3.626
972215AH1-692 GEN
50/50
3.626
315759AF1-018 GEN
50/50
3.24
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.146
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
0.019
970189AG2-124 GEN
Solar/Wind Harmer
2.689
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
957191AF2-013 GEN
50/50
28.8
3150391LDYSMT3
50/50
22.284
972195AH1-682 GEN
50/50
2.928
3150341NORNECKC1
50/50
1.619
3150341NORNECKC1
50/50
1.606
3141843SHACKLE
50/50
0.027
315673AE1-157 GEN
Solar/Wind Harmer
9.437
316156AD2-030 GEN
Solar/Wind Harmer
0.069
972189AH1-679 GEN
Adder
1.469
966871AG1-558 GEN
Solar/Wind Harmer
0.101
315976AC1-164 GENA
Solar/Wind Harmer
0.73
316169AC1-164_GENC
Solar/Wind Harmer
0.631
316312AB1-027
Solar/Wind Harmer
0.119
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.207
3150691DARBY 3
Adder
4.665
3150701DARBY 4
Adder
4.654
3150681DARBY 2
Adder
4.648
3150671DARBY 1
Adder
4.643
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.811
316033AB2-134 GEN
Solar/Wind Harmer
0
3150331BIRCHWDA
50/50
68.117
3150401LDYSMT4
50/50
22.325
3150371LDYSMT1
50/50
21.572
3150501FRIVERG
50/50
1.257
3150351NORNECKC2
50/50
1.567
966661AG1-536 GEN
50/50
3.714
315749AE2-041 GEN
50/50
3.24
3141843SHACKLE
50/50
0.492
316223AC1-118
Solar/Wind Harmer
0.14
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
3141873WAN 176
Solar/Wind Harmer
1.668
3141766HARMONY
Solar/Wind Harmer
1.215
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
316075AC2-137 C
Solar/Wind Harmer
0.018
3142416OLDCHRC
Solar/Wind Harmer
0.647
970293AG2-193 GEN
Solar/Wind Harmer
0.708
3142946ENON
Solar/Wind Harmer
0.022
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.258
3150921YORKTN3
Adder
1.57
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316458AB2-190 GEN2
Solar/Wind Harmer
0.315
315778AD1-151 GEN
Solar/Wind Harmer
4.683
3150861SPRUNCD
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
1.528
3151171GRAVELC
Adder
0.794
3138283WHITEMARSH
Solar/Wind Harmer
0.018
316159AE1-175 C
Solar/Wind Harmer
0.055
971285AH1-108 GEN
Adder
0.44
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3141426STAFORD
Solar/Wind Helper
0.047
972197AH1-683 GEN
50/50
3.486
972219AH1-694 GEN
50/50
2.51
3150351NORNECKC2
50/50
1.541
972135AH1-637 GEN
Solar/Wind Harmer
2.021
316337AD2-073 GEN
Solar/Wind Harmer
0.147
3141726DUNNSVL
Solar/Wind Harmer
0.554
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.317
962861AG1-135 GEN
Solar/Wind Harmer
4.106
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.239
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
315975AC1-164 GENB
Solar/Wind Harmer
0.022
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.498
944631AF1-128 GEN
Adder
30.586
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.315
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.041
3150851SPRUNCC
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
3.004
3151171GRAVELC
Adder
0.603
LAGNLTFEXP_LAGN->PJM
CLTF
1.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.277
NYPJM->LTFIMP_NY
CLTF
0.731
LGEELTFEXP_LGEE->PJM
CLTF
0.352
TVALTFEXP_TVA->PJM
CLTF
0.925
WECLTFEXP_WEC->PJM
CLTF
0.176
CPLELTFEXP_CPLE->PJM
CLTF
2.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.194
MECLTFEXP_MEC->PJM
CLTF
0.929
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2104_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2104_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.28 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:805.32
MW Contribution:
2.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
68.117
3150401LDYSMT4
50/50
22.325
3150371LDYSMT1
50/50
21.572
3150501FRIVERG
50/50
1.257
3150351NORNECKC2
50/50
1.567
966661AG1-536 GEN
50/50
3.714
315749AE2-041 GEN
50/50
3.24
3141843SHACKLE
50/50
0.492
316223AC1-118
Solar/Wind Harmer
0.14
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
3141873WAN 176
Solar/Wind Harmer
1.668
3141766HARMONY
Solar/Wind Harmer
1.215
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
316075AC2-137 C
Solar/Wind Harmer
0.018
3142416OLDCHRC
Solar/Wind Harmer
0.647
970293AG2-193 GEN
Solar/Wind Harmer
0.708
3142946ENON
Solar/Wind Harmer
0.022
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.258
3150921YORKTN3
Adder
1.57
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316458AB2-190 GEN2
Solar/Wind Harmer
0.315
315778AD1-151 GEN
Solar/Wind Harmer
4.683
3150861SPRUNCD
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
1.528
3151171GRAVELC
Adder
0.794
957191AF2-013 GEN
50/50
28.8
3150391LDYSMT3
50/50
22.284
972195AH1-682 GEN
50/50
2.928
3150341NORNECKC1
50/50
1.619
3150341NORNECKC1
50/50
1.606
3141843SHACKLE
50/50
0.027
315673AE1-157 GEN
Solar/Wind Harmer
9.437
316156AD2-030 GEN
Solar/Wind Harmer
0.069
972189AH1-679 GEN
Adder
1.469
966871AG1-558 GEN
Solar/Wind Harmer
0.101
315976AC1-164 GENA
Solar/Wind Harmer
0.73
316169AC1-164_GENC
Solar/Wind Harmer
0.631
316312AB1-027
Solar/Wind Harmer
0.119
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.207
3150691DARBY 3
Adder
4.665
3150701DARBY 4
Adder
4.654
3150681DARBY 2
Adder
4.648
3150671DARBY 1
Adder
4.643
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.811
316033AB2-134 GEN
Solar/Wind Harmer
0
3141316ARNOLDS
50/50
0.048
3150411LDYSMT5
50/50
22.395
3150381LDYSMT2
50/50
21.433
972213AH1-691 GEN
50/50
3.626
972215AH1-692 GEN
50/50
3.626
315759AF1-018 GEN
50/50
3.24
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.146
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
0.019
970189AG2-124 GEN
Solar/Wind Harmer
2.689
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3138283WHITEMARSH
Solar/Wind Harmer
0.018
316159AE1-175 C
Solar/Wind Harmer
0.055
971285AH1-108 GEN
Adder
0.44
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3141426STAFORD
Solar/Wind Helper
0.047
3141346CRANES
50/50
0.542
972197AH1-683 GEN
50/50
3.486
972219AH1-694 GEN
50/50
2.51
3150351NORNECKC2
50/50
1.541
972135AH1-637 GEN
Solar/Wind Harmer
2.021
316337AD2-073 GEN
Solar/Wind Harmer
0.147
3141726DUNNSVL
Solar/Wind Harmer
0.554
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.317
962861AG1-135 GEN
Solar/Wind Harmer
4.106
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.239
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
315975AC1-164 GENB
Solar/Wind Harmer
0.022
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.498
944631AF1-128 GEN
Adder
30.586
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.315
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.041
3150851SPRUNCC
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
3.004
3151171GRAVELC
Adder
0.603
LAGNLTFEXP_LAGN->PJM
CLTF
1.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.277
NYPJM->LTFIMP_NY
CLTF
0.731
LGEELTFEXP_LGEE->PJM
CLTF
0.352
TVALTFEXP_TVA->PJM
CLTF
0.925
WECLTFEXP_WEC->PJM
CLTF
0.176
CPLELTFEXP_CPLE->PJM
CLTF
2.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.194
MECLTFEXP_MEC->PJM
CLTF
0.929
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:607.94
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
3151221GRAVEL6
50/50
4.34
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
TVALTFEXP_TVA->PJM
CLTF
0.74
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.3 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.17
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151221GRAVEL6
Adder
4.09
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.335
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:578.33
MW Contribution:
4.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.957
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.174
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
3150331BIRCHWDA
50/50
158.939
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
315749AE2-041 GEN
50/50
4.972
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150921YORKTN3
50/50
2
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3141766HARMONY
Solar/Wind Harmer
1.864
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.022
3151171GRAVELC
Adder
0.796
970293AG2-193 GEN
Solar/Wind Harmer
0.602
3150351NORNECKC2
50/50
2.968
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150641CHESTS8
50/50
0.191
944631AF1-128 GEN
50/50
30.096
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.999
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
971317AH1-138 GEN
Solar/Wind Harmer
0.632
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.972
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
972263AH1-716 GEN
50/50
35.581
3150631CHESTG8
50/50
0.372
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.03
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.066
3151221GRAVEL6
Adder
4.139
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
3141426STAFORD
Solar/Wind Helper
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
NYPJM->LTFIMP_NY
CLTF
0.471
LGEELTFEXP_LGEE->PJM
CLTF
0.179
WECLTFEXP_WEC->PJM
CLTF
0.088
TVALTFEXP_TVA->PJM
CLTF
0.6
CPLELTFEXP_CPLE->PJM
CLTF
1.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
MECLTFEXP_MEC->PJM
CLTF
0.511
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:602.71
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
3151221GRAVEL6
50/50
4.34
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
TVALTFEXP_TVA->PJM
CLTF
0.74
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.8 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1755.6
MW Contribution:
2.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.161
3150021OMF B
50/50
0.213
3150101POSSM6S
50/50
1.293
3150081POSSM6A
50/50
0.849
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
972217AH1-693 GEN
50/50
1.753
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3141196NOKESVL
Solar/Wind Harmer
0.428
3150301M RUN C
Adder
13.329
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
3150401LDYSMT4
Adder
12.659
3150371LDYSMT1
Adder
12.232
3150091POSSM6B
50/50
0.849
3150071POSSM 5
50/50
52.154
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
3150391LDYSMT3
Adder
12.635
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.15
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.037
3150671DARBY 1
Adder
6.03
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.434
971223AH1-071 GEN
Solar/Wind Harmer
0.889
944641AF1-129 GEN
Adder
39.347
316033AB2-134 GEN
Solar/Wind Harmer
0
316294AC1-161 GEN
Solar/Wind Harmer
1.396
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316349AD2-085 GEN
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3146456SLIGO L269
Solar/Wind Harmer
1.414
3130086AYDLETT
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
0.547
3146386ELIZ CT
Solar/Wind Harmer
0.079
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316065AD1-022 GEN
Solar/Wind Harmer
3.468
316365GEN2_N
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316140AB2-099
Solar/Wind Harmer
0.026
970099AG2-077 GEN
Solar/Wind Harmer
7.893
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.172
972193AH1-681 GEN
Adder
1.64
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
316005AA1-067
Solar/Wind Harmer
0.076
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145493TOT1
Solar/Wind Harmer
0.161
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
961601AG1-000A GEN
Solar/Wind Harmer
1.225
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316263AC1-034 GEN
Solar/Wind Harmer
2.619
964791AG1-342 GEN
Solar/Wind Harmer
1.319
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
970053AG2-049 GEN
50/50
2.019
3140676OCCOQUN
50/50
0.016
3138216PACIFIC
Solar/Wind Harmer
0.025
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.698
3150381LDYSMT2
Adder
12.153
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
315651AD1-115 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Harmer
0.129
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.087
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
970189AG2-124 GEN
Solar/Wind Harmer
2.502
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.071
315697AD1-025 GEN
Solar/Wind Harmer
0.088
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
316311AC2-079 GEN
Solar/Wind Harmer
2.299
957871AF2-081 GEN
Solar/Wind Harmer
3.983
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.042
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.059
3146396TANGLEW
Solar/Wind Harmer
0.218
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315814AE2-033 C
Solar/Wind Harmer
6.193
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
971967AH1-528 GEN
Solar/Wind Harmer
12.296
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.806
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
316223AC1-118
Solar/Wind Harmer
0.064
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.117
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3141873WAN 176
Solar/Wind Harmer
1.502
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.431
970293AG2-193 GEN
Solar/Wind Harmer
0.898
316075AC2-137 C
Solar/Wind Harmer
0.022
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
0.793
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
3144536CHRHLND
Solar/Wind Harmer
0.012
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3151101ELIZAR3
Adder
7.476
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944601AF1-125 GEN
Solar/Wind Harmer
17.837
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
316246AF1-032 C
Solar/Wind Harmer
0.036
3143336POWHATN
Solar/Wind Harmer
1.198
316321Z2-027
Solar/Wind Harmer
0.014
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3145273HOLLAND
Solar/Wind Harmer
0.059
944011AF1-069 GEN
Solar/Wind Harmer
4.7
3146376EDENTON
Solar/Wind Harmer
0.077
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3146206CASHIE
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3146173TUNIS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
972255AH1-712 GEN
Adder
36.701
3145933PARMELE
Solar/Wind Harmer
0.072
959311AF2-222 GEN
Solar/Wind Harmer
6.364
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
970221AG2-151 GEN
Solar/Wind Harmer
3.81
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
315821AE2-092 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
971623AH1-311 GEN
Solar/Wind Harmer
0.138
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3148013FISHERV
Solar/Wind Harmer
0.065
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
316123AC1-075 GEN
Solar/Wind Harmer
0.082
3151861LOWMORA
Adder
0.644
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
942751AE2-291 GEN
Solar/Wind Harmer
3.269
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
3150011OMF A
50/50
0.213
972223AH1-696 GEN
50/50
9.014
3150151POSSMC1
50/50
1.141
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
3150281M RUN A
Adder
13.337
971685AH1-345 GEN
Solar/Wind Harmer
0.729
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
972197AH1-683 GEN
Adder
1.977
972219AH1-694 GEN
Adder
1.423
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3150351NORNECKC2
Adder
0.868
3141726DUNNSVL
Solar/Wind Harmer
0.347
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.855
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.434
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.784
3143226MDLTHAN
Solar/Wind Harmer
0.083
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.324
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.014
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
3146456SLIGO L269
Solar/Wind Harmer
0.08
319010AE1-072 C
Solar/Wind Harmer
0.398
940641AE2-051 GEN
Solar/Wind Harmer
6.384
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3143336POWHATN
Solar/Wind Harmer
1.41
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
941031AE2-094 GEN
Solar/Wind Harmer
14.385
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
3145663CRESWEL
Solar/Wind Harmer
0.214
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.603
316023GEN1_S
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
970087AG2-069 GEN
Solar/Wind Harmer
5.959
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
19.733
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3145963POPLR C
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.663
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
971563AH1-280 GEN
Solar/Wind Harmer
0.768
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
5.367
972277AH1-723 GEN
Adder
42.768
3146293MARTNCO
Solar/Wind Harmer
0.066
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
0.762
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
315785AD2-033 C
Solar/Wind Harmer
0.577
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.237
3146233WITAKRS
Solar/Wind Harmer
0.277
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.309
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.121
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207484AF2-139 C O1
Solar/Wind Helper
0.048
207530AG1-191 GEN
Solar/Wind Helper
0.038
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
970581AG2-369 GEN
Solar/Wind Harmer
3.417
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
972205AH1-687 GEN
Adder
3.128
971845AH1-439 GEN
Solar/Wind Harmer
3.318
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316486AD2-202 GEN
Solar/Wind Harmer
0.074
3146033SCOT NK
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
1.421
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3144303KENBRDG
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958
CPLELTFEXP_CPLE->PJM
CLTF
5.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.69 %
Rating:888.3 MVA
Rating Type:B
MVA to Mitigate:921.03
MW Contribution:
4.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.838
3142366NRTHEST
50/50
0.723
3150691DARBY 3
50/50
15.549
3150701DARBY 4
50/50
15.512
3150681DARBY 2
50/50
15.494
3150671DARBY 1
50/50
15.476
966871AG1-558 GEN
Solar/Wind Harmer
0.268
316312AB1-027
Solar/Wind Harmer
0.392
972189AH1-679 GEN
Adder
3.38
3142946ENON
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
81.675
315976AC1-164 GENA
Solar/Wind Harmer
1.777
316169AC1-164_GENC
Solar/Wind Harmer
1.535
3143526WINTERP
Solar/Wind Harmer
0.815
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.106
971223AH1-071 GEN
Solar/Wind Harmer
1.445
3150341NORNECKC1
Adder
1.351
3150341NORNECKC1
Adder
1.341
316349AD2-085 GEN
Solar/Wind Harmer
0.085
3150991CHESPKB
Adder
1.289
3150991CHESPKB
Adder
1.258
315835AF2-110_GEN
Solar/Wind Harmer
0.832
3145506HICKORY
Solar/Wind Harmer
0.483
3145506HICKORY
Solar/Wind Harmer
0.29
3145506HICKORY
Solar/Wind Harmer
0.073
316294AC1-161 GEN
Solar/Wind Harmer
2.079
316339AD2-160 GEN
Solar/Wind Harmer
0.193
316388AE2-253 GEN
Solar/Wind Harmer
0.374
3137176SLIGO L2192
Solar/Wind Harmer
0.477
315051AA1-145 CT1
50/50
1.597
316473AC1-191 GEN
Solar/Wind Harmer
0.784
3142416OLDCHRC
Solar/Wind Harmer
2.135
970293AG2-193 GEN
Solar/Wind Harmer
2.078
316075AC2-137 C
Solar/Wind Harmer
0.049
3143096IRON208
Adder
0.771
3143096IRON208
Adder
0.756
971781AH1-399 GEN
Solar/Wind Harmer
0.241
3150861SPRUNCD
Adder
0.813
3142946ENON
Solar/Wind Harmer
0.058
970133AG2-095 GEN
Solar/Wind Harmer
1.578
3142433PROV 92
Adder
0.314
3142433PROV 92
Adder
0.314
316458AB2-190 GEN2
Solar/Wind Harmer
0.838
315778AD1-151 GEN
Solar/Wind Harmer
12.258
3141843SHACKLE
Adder
0.763
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
1.989
3141873WAN 176
Solar/Wind Harmer
2.582
961611AG1-000B GEN
Solar/Wind Harmer
3.828
315813AE1-149 C
Solar/Wind Harmer
7.651
3151171GRAVELC
Adder
1.947
3144216WINCHST
Adder
0.517
3150921YORKTN3
Adder
3.441
970657AG2-426 GEN
Solar/Wind Harmer
3.055
3145336SMITFLD
Solar/Wind Harmer
0.053
3150351NORNECKC2
Adder
1.308
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.401
944581AF1-123 GEN
Solar/Wind Harmer
27.214
944601AF1-125 GEN
Solar/Wind Harmer
26.795
316246AF1-032 C
Solar/Wind Harmer
0.054
316017AA1-139 ULT1
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
0.12
971153AH1-033 GEN
Solar/Wind Harmer
1.386
316321Z2-027
Solar/Wind Harmer
0.021
3146516WINFALL
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146376EDENTON
Solar/Wind Harmer
0.112
316223AC1-118
Solar/Wind Harmer
0.078
3141906WESTMOR
Solar/Wind Harmer
0.044
315735AD1-075 GEN1
Solar/Wind Harmer
0.298
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.103
3145893MURPHYS
Solar/Wind Harmer
0.171
3145893MURPHYS
Solar/Wind Harmer
0.102
3146173TUNIS
Solar/Wind Harmer
0.101
3143336POWHATN
Solar/Wind Harmer
1.497
3146263WOODLND
Solar/Wind Harmer
0.098
3145963POPLR C
Solar/Wind Harmer
0.097
944011AF1-069 GEN
Solar/Wind Harmer
5.853
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
316011AB1-132 GEN
Solar/Wind Harmer
1.752
3145823KELFORD
Solar/Wind Harmer
0.096
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3145796HORNRTN
Solar/Wind Harmer
0.377
3145796HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
0.091
3147043LAWRENC
Solar/Wind Harmer
0.054
316212AC1-099_GEN
Solar/Wind Harmer
0.466
970917AG2-570 GEN
Solar/Wind Harmer
7.926
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
2.999
3146073TAR RVR
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
0.083
3146233WITAKRS
Solar/Wind Harmer
0.416
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
961601AG1-000A GEN
Solar/Wind Harmer
5.742
971623AH1-311 GEN
Solar/Wind Harmer
0.161
3145543BTLEBRO
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.081
316478AD1-087 GEN
Solar/Wind Harmer
0.274
964241AG1-285 GEN
Solar/Wind Harmer
4.864
970257AG2-171 GEN
Solar/Wind Harmer
2.269
971775AH1-396 GEN
Solar/Wind Harmer
0.113
959311AF2-222 GEN
Solar/Wind Harmer
6.267
3144293JTRSVLE
Adder
0.163
3147133PAMPLIN
Solar/Wind Harmer
0.211
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.037
316222AC1-221 GEN
Solar/Wind Harmer
0.239
316283AC2-100 C
Solar/Wind Harmer
0.113
3146456SLIGO L269
Solar/Wind Harmer
2.121
3130086AYDLETT
Solar/Wind Harmer
0.478
3146386ELIZ CT
Solar/Wind Harmer
0.118
3144356SAPONY
Solar/Wind Harmer
0.981
316315AB2-025 C
Solar/Wind Harmer
0.094
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
1.699
3146376EDENTON
Solar/Wind Harmer
0.496
3146376EDENTON
Solar/Wind Harmer
0.496
315614AA2-178 GEN
Solar/Wind Harmer
0.615
316065AD1-022 GEN
Solar/Wind Harmer
4.777
316365GEN2_N
Solar/Wind Harmer
0.23
3145893MURPHYS
Solar/Wind Harmer
0.685
3145893MURPHYS
Solar/Wind Harmer
0.184
3146173TUNIS
Solar/Wind Harmer
0.101
3146173TUNIS
Solar/Wind Harmer
0.101
316140AB2-099
Solar/Wind Harmer
0.036
316313AB2-026
Solar/Wind Harmer
0.062
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.374
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145796HORNRTN
Solar/Wind Harmer
0.283
972185AH1-677 GEN
Adder
5.29
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.656
3145783HORNRTN
Solar/Wind Harmer
1.325
3145783HORNRTN
Solar/Wind Harmer
0.414
3145783HORNRTN
Solar/Wind Harmer
0.166
972187AH1-678 GEN
Adder
2.647
3145933PARMELE
Solar/Wind Harmer
0.182
3145933PARMELE
Solar/Wind Harmer
0.091
970933AG2-581 GEN
Solar/Wind Harmer
7.245
316336AC2-165 C
Solar/Wind Harmer
4.535
316005AA1-067
Solar/Wind Harmer
0.094
315724AD1-057 GEN
Solar/Wind Harmer
1.673
3145493TOT1
Solar/Wind Harmer
0.193
3145453TOT5
Solar/Wind Harmer
0.116
3145603CNETO
Solar/Wind Harmer
0.077
970099AG2-077 GEN
Solar/Wind Harmer
8.836
961601AG1-000A GEN
Solar/Wind Harmer
1.435
316049AB1-081 GEN
Solar/Wind Harmer
0.458
316263AC1-034 GEN
Solar/Wind Harmer
3.063
315673AE1-157 GEN
Solar/Wind Harmer
5.073
970323AG2-213 GEN
Solar/Wind Harmer
3.025
970301AG2-198 GEN
Solar/Wind Harmer
2.959
962561AG1-105 GEN
Solar/Wind Harmer
3.321
964791AG1-342 GEN
Solar/Wind Harmer
1.311
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.818
3144293JTRSVLE
Adder
0.163
3147133PAMPLIN
Solar/Wind Harmer
0.067
3147133PAMPLIN
Solar/Wind Harmer
0.054
316118AC1-105 GEN
Solar/Wind Harmer
0.169
315052AA1-145 CT2
50/50
1.607
3142416OLDCHRC
Solar/Wind Harmer
0.573
3142416OLDCHRC
Solar/Wind Harmer
0.219
3143096IRON208
Adder
0.771
3142543TWELFTH
Solar/Wind Harmer
0.018
3150851SPRUNCC
Adder
0.813
944631AF1-128 GEN
Adder
82.76
315975AC1-164 GENB
Solar/Wind Harmer
0.053
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142433PROV 92
Solar/Wind Harmer
0.646
3142433PROV 92
Adder
0.314
3142433PROV 92
Adder
0.314
316132AB2-190 GEN1
Solar/Wind Harmer
0.838
3143526WINTERP
Solar/Wind Harmer
0.815
971069AG2-661 GEN
Solar/Wind Harmer
2.724
971777AH1-397 GEN
Solar/Wind Harmer
0.394
3141766HARMONY
Solar/Wind Harmer
0.03
961611AG1-000B GEN
Solar/Wind Harmer
7.527
3138133OCRAN
Solar/Wind Harmer
0.085
971317AH1-138 GEN
Solar/Wind Harmer
1.043
3151171GRAVELC
Adder
1.48
316381AD1-082 GEN
Solar/Wind Harmer
0.139
3138126ROCKLANDING
Solar/Wind Harmer
0.063
3143226MDLTHAN
Solar/Wind Harmer
0.135
962861AG1-135 GEN
Solar/Wind Harmer
4.303
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.424
3145336SMITFLD
Solar/Wind Harmer
0.532
3141726DUNNSVL
Solar/Wind Harmer
0.53
3150351NORNECKC2
Adder
1.287
316072AD1-144
Solar/Wind Harmer
0.044
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.022
3150981CHESPKA
Adder
1.536
316093AE2-104_GEN
Solar/Wind Harmer
2.04
944591AF1-124 GEN
Solar/Wind Harmer
27.31
315773AC2-141 GEN
Solar/Wind Harmer
4.392
316337AD2-073 GEN
Solar/Wind Harmer
0.104
3146456SLIGO L269
Solar/Wind Harmer
0.12
319010AE1-072 C
Solar/Wind Harmer
0.597
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
3130156CHOWAN
Solar/Wind Harmer
0.112
939411AE1-173 GEN
Solar/Wind Harmer
46.439
315816AE2-034 GEN
Solar/Wind Harmer
0.461
3145663CRESWEL
Solar/Wind Harmer
0.302
971163AH1-040 GEN
Solar/Wind Harmer
8.646
940641AE2-051 GEN
Solar/Wind Harmer
8.384
315737AD1-076 GEN
Solar/Wind Harmer
1.344
966881AG1-559 GEN
Solar/Wind Harmer
0.121
316023GEN1_S
Solar/Wind Harmer
0.23
3146206CASHIE
Solar/Wind Harmer
0.103
971547AH1-271 GEN
Solar/Wind Harmer
2.201
3145893MURPHYS
Solar/Wind Harmer
0.409
3145893MURPHYS
Solar/Wind Harmer
0.455
3146173TUNIS
Solar/Wind Harmer
0.101
3156021HOLLOMANSOL
Solar/Wind Harmer
0.454
3145683EARLEYS
Solar/Wind Harmer
0.099
3143336POWHATN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
0.098
315607AA1-063A GEN
Solar/Wind Harmer
0.197
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145963POPLR C
Solar/Wind Harmer
0.097
941031AE2-094 GEN
Solar/Wind Harmer
17.913
3145823KELFORD
Solar/Wind Harmer
0.096
3145796HORNRTN
Solar/Wind Harmer
0.311
3145796HORNRTN
Solar/Wind Harmer
0.094
972135AH1-637 GEN
Solar/Wind Harmer
0.804
3145783HORNRTN
Solar/Wind Harmer
0.093
3146293MARTNCO
Solar/Wind Harmer
0.084
3147043LAWRENC
Adder
0.818
970919AG2-571 GEN
Solar/Wind Harmer
3.17
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
970087AG2-069 GEN
Solar/Wind Harmer
7.03
316494AC1-189 GEN
Solar/Wind Harmer
0.289
961671AG1-007 GEN
Solar/Wind Harmer
0.013
3146083TARBORO
Solar/Wind Harmer
0.083
3145493TOT1
Solar/Wind Harmer
0.37
3146233WITAKRS
Solar/Wind Harmer
0.33
316129AC1-054 GEN
Solar/Wind Harmer
0.309
957481AF2-042 GEN
Solar/Wind Harmer
22.089
971065AG2-659 GEN
Solar/Wind Harmer
3.492
316359AB2-059 GEN
Solar/Wind Harmer
0.286
3142053HEARTS
Solar/Wind Harmer
0.142
3145543BTLEBRO
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.064
315693AD1-088 GEN
Solar/Wind Harmer
3.833
316131AB2-060 GEN
Solar/Wind Harmer
0.23
315785AD2-033 C
Solar/Wind Harmer
0.578
316034AC1-036 C
Solar/Wind Harmer
0.005
970685AG2-442 GEN
Solar/Wind Harmer
5.142
970401AG2-262 GEN
Solar/Wind Harmer
0.401
971563AH1-280 GEN
Solar/Wind Harmer
0.727
3144293JTRSVLE
Adder
0.163
3144293JTRSVLE
Adder
0.128
970937AG2-583 GEN
Solar/Wind Harmer
3.987
3146926FARMVIL
Solar/Wind Harmer
0.037
971285AH1-108 GEN
Adder
1.33
3142433PROV 92
Adder
0.314
3142433PROV 92
Adder
0.314
316233AE1-074 FULL
Solar/Wind Harmer
0.125
971281AH1-106 GEN
Solar/Wind Harmer
2.175
971283AH1-107 GEN
Solar/Wind Harmer
2.175
3143873LANEXA
Solar/Wind Harmer
0.093
315697AD1-025 GEN
Solar/Wind Harmer
0.162
970189AG2-124 GEN
Solar/Wind Harmer
4.425
316159AE1-175 C
Solar/Wind Harmer
0.126
3141873WAN 176
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.143
3138133OCRAN
Solar/Wind Harmer
0.043
3143316POE
Solar/Wind Harmer
0.563
3138283WHITEMARSH
Solar/Wind Harmer
0.033
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
3151201GRAVEL4
Adder
10.13
3151221GRAVEL6
Adder
10.118
3151191GRAVEL3
Adder
10.001
3151211GRAVEL5
Adder
10.001
970657AG2-426 GEN
Solar/Wind Harmer
1
971445AH1-216 GEN
Solar/Wind Harmer
9.404
3141813NORNECK
Solar/Wind Harmer
0.129
316311AC2-079 GEN
Solar/Wind Harmer
3.656
3151081ELIZAR1
Adder
11.257
3151091ELIZAR2
Adder
11.061
316316AC1-027 C
Solar/Wind Harmer
0.116
957871AF2-081 GEN
Solar/Wind Harmer
5.984
3146406KITTY HAWK
Solar/Wind Harmer
0.015
313526AB2-022
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.118
3146486SUNBURY
Solar/Wind Harmer
0.118
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
9.222
3130156CHOWAN
Solar/Wind Harmer
0.112
3130156CHOWAN
Solar/Wind Harmer
0.112
3130546PLYMOUTH
Solar/Wind Harmer
0.105
315732AD1-074 GEN1
Solar/Wind Harmer
0.597
315733AD1-074 GEN2
Solar/Wind Harmer
0.597
3146206CASHIE
Solar/Wind Harmer
0.103
970601AG2-382 GEN
Solar/Wind Harmer
3.851
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.102
316463AE2-346 GEN
Solar/Wind Harmer
0.085
3145513AHOSKIE
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.1
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.099
3145683EARLEYS
Solar/Wind Harmer
0.099
316258AE1-075 C
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.098
970533AG2-339 GEN
Solar/Wind Harmer
7.348
315652AC1-086 GEN
Solar/Wind Harmer
10.623
970673AG2-436 GEN
Solar/Wind Harmer
11.956
316426AA2-053 GEN
Solar/Wind Harmer
0.317
3137643SOCKMAN
Solar/Wind Harmer
0.378
3145796HORNRTN
Solar/Wind Harmer
0.302
3145796HORNRTN
Solar/Wind Harmer
0.038
971967AH1-528 GEN
Solar/Wind Harmer
14.881
3146033SCOT NK
Solar/Wind Harmer
0.372
316210AC1-098 GEN
Solar/Wind Harmer
0.836
316274AC1-208 GEN
Solar/Wind Harmer
0.46
3145746EVERETS
Solar/Wind Harmer
0.35
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
970085AG2-068 GEN
Solar/Wind Harmer
4.686
970581AG2-369 GEN
Solar/Wind Harmer
4.03
944491AF1-114 GEN
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.683
316327AA2-057 GEN
Solar/Wind Harmer
0.126
970831AG2-522 GEN
Solar/Wind Harmer
3.589
3145573BETHELC
Solar/Wind Harmer
0.083
3145573BETHELC
Solar/Wind Harmer
0.083
316486AD2-202 GEN
Solar/Wind Harmer
0.08
3144303KENBRDG
Solar/Wind Harmer
0.057
970683AG2-441 GEN
Solar/Wind Harmer
4.188
970681AG2-440 GEN
Solar/Wind Harmer
2.78
946301AF1-294 GEN
Solar/Wind Harmer
1.345
961791AG1-021 GEN
Solar/Wind Harmer
0.654
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
1.933
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.749
NYPJM->LTFIMP_NY
CLTF
0.791
LGEELTFEXP_LGEE->PJM
CLTF
0.091
WECLTFEXP_WEC->PJM
CLTF
0.038
TVALTFEXP_TVA->PJM
CLTF
0.95
CPLELTFEXP_CPLE->PJM
CLTF
4.436
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.644
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.015
MECLTFEXP_MEC->PJM
CLTF
0.451
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.2 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:916.78
MW Contribution:
4.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.834
3142366NRTHEST
50/50
0.72
3150691DARBY 3
50/50
15.477
3150701DARBY 4
50/50
15.441
3150681DARBY 2
50/50
15.423
3150671DARBY 1
50/50
15.405
966871AG1-558 GEN
Solar/Wind Harmer
0.267
316312AB1-027
Solar/Wind Harmer
0.39
972189AH1-679 GEN
Adder
3.364
3142946ENON
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
81.299
315976AC1-164 GENA
Solar/Wind Harmer
1.768
316169AC1-164_GENC
Solar/Wind Harmer
1.528
3143526WINTERP
Solar/Wind Harmer
0.811
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.106
971223AH1-071 GEN
Solar/Wind Harmer
1.439
3150341NORNECKC1
Adder
1.345
3150341NORNECKC1
Adder
1.334
316349AD2-085 GEN
Solar/Wind Harmer
0.085
3150991CHESPKB
Adder
1.283
3150991CHESPKB
Adder
1.252
315835AF2-110_GEN
Solar/Wind Harmer
0.829
3145506HICKORY
Solar/Wind Harmer
0.481
3145506HICKORY
Solar/Wind Harmer
0.289
3145506HICKORY
Solar/Wind Harmer
0.072
316294AC1-161 GEN
Solar/Wind Harmer
2.069
316339AD2-160 GEN
Solar/Wind Harmer
0.192
316388AE2-253 GEN
Solar/Wind Harmer
0.373
3137176SLIGO L2192
Solar/Wind Harmer
0.475
3146456SLIGO L269
Solar/Wind Harmer
2.112
3130086AYDLETT
Solar/Wind Harmer
0.476
3146386ELIZ CT
Solar/Wind Harmer
0.118
3144356SAPONY
Solar/Wind Harmer
0.977
316315AB2-025 C
Solar/Wind Harmer
0.093
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
1.691
3146376EDENTON
Solar/Wind Harmer
0.494
3146376EDENTON
Solar/Wind Harmer
0.494
315614AA2-178 GEN
Solar/Wind Harmer
0.612
316065AD1-022 GEN
Solar/Wind Harmer
4.755
316365GEN2_N
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.682
3145893MURPHYS
Solar/Wind Harmer
0.183
3146173TUNIS
Solar/Wind Harmer
0.1
3146173TUNIS
Solar/Wind Harmer
0.1
316140AB2-099
Solar/Wind Harmer
0.035
316313AB2-026
Solar/Wind Harmer
0.061
3142666NORTHAMPTON
Solar/Wind Harmer
0.096
3142666NORTHAMPTON
Solar/Wind Harmer
0.096
3142666NORTHAMPTON
Solar/Wind Harmer
0.096
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.368
313506AB2-031 GEN
Solar/Wind Harmer
0.292
3145796HORNRTN
Solar/Wind Harmer
0.281
972185AH1-677 GEN
Adder
5.266
3145593CAROLNA
Solar/Wind Harmer
0.093
3145593CAROLNA
Solar/Wind Harmer
0.093
3145593CAROLNA
Solar/Wind Harmer
0.116
3145783HORNRTN
Solar/Wind Harmer
1.648
3145783HORNRTN
Solar/Wind Harmer
1.319
3145783HORNRTN
Solar/Wind Harmer
0.412
3145783HORNRTN
Solar/Wind Harmer
0.165
972187AH1-678 GEN
Adder
2.635
3145933PARMELE
Solar/Wind Harmer
0.181
3145933PARMELE
Solar/Wind Harmer
0.09
970933AG2-581 GEN
Solar/Wind Harmer
7.212
316336AC2-165 C
Solar/Wind Harmer
4.514
316005AA1-067
Solar/Wind Harmer
0.093
315724AD1-057 GEN
Solar/Wind Harmer
1.665
3145493TOT1
Solar/Wind Harmer
0.192
3145453TOT5
Solar/Wind Harmer
0.115
3145603CNETO
Solar/Wind Harmer
0.077
970099AG2-077 GEN
Solar/Wind Harmer
8.795
961601AG1-000A GEN
Solar/Wind Harmer
1.429
316049AB1-081 GEN
Solar/Wind Harmer
0.456
316263AC1-034 GEN
Solar/Wind Harmer
3.049
315673AE1-157 GEN
Solar/Wind Harmer
5.05
970323AG2-213 GEN
Solar/Wind Harmer
3.011
970301AG2-198 GEN
Solar/Wind Harmer
2.945
962561AG1-105 GEN
Solar/Wind Harmer
3.306
964791AG1-342 GEN
Solar/Wind Harmer
1.305
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.814
3144293JTRSVLE
Adder
0.162
3147133PAMPLIN
Solar/Wind Harmer
0.067
3147133PAMPLIN
Solar/Wind Harmer
0.053
316118AC1-105 GEN
Solar/Wind Harmer
0.169
315051AA1-145 CT1
50/50
1.59
316473AC1-191 GEN
Solar/Wind Harmer
0.78
3142416OLDCHRC
Solar/Wind Harmer
2.125
970293AG2-193 GEN
Solar/Wind Harmer
2.068
316075AC2-137 C
Solar/Wind Harmer
0.049
3143096IRON208
Adder
0.768
3143096IRON208
Adder
0.753
971781AH1-399 GEN
Solar/Wind Harmer
0.239
3150861SPRUNCD
Adder
0.809
3142946ENON
Solar/Wind Harmer
0.057
970133AG2-095 GEN
Solar/Wind Harmer
1.57
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
316458AB2-190 GEN2
Solar/Wind Harmer
0.834
315778AD1-151 GEN
Solar/Wind Harmer
12.201
3141843SHACKLE
Adder
0.76
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
1.98
3141873WAN 176
Solar/Wind Harmer
2.57
961611AG1-000B GEN
Solar/Wind Harmer
3.81
315813AE1-149 C
Solar/Wind Harmer
7.616
3151171GRAVELC
Adder
1.938
3144216WINCHST
Adder
0.515
3150921YORKTN3
Adder
3.425
970657AG2-426 GEN
Solar/Wind Harmer
3.041
3145336SMITFLD
Solar/Wind Harmer
0.053
3150351NORNECKC2
Adder
1.302
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.348
944581AF1-123 GEN
Solar/Wind Harmer
27.088
944601AF1-125 GEN
Solar/Wind Harmer
26.671
316246AF1-032 C
Solar/Wind Harmer
0.053
316017AA1-139 ULT1
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
0.119
971153AH1-033 GEN
Solar/Wind Harmer
1.379
316321Z2-027
Solar/Wind Harmer
0.021
3146516WINFALL
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146376EDENTON
Solar/Wind Harmer
0.111
316223AC1-118
Solar/Wind Harmer
0.078
3141906WESTMOR
Solar/Wind Harmer
0.044
315735AD1-075 GEN1
Solar/Wind Harmer
0.297
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.103
3145893MURPHYS
Solar/Wind Harmer
0.171
3145893MURPHYS
Solar/Wind Harmer
0.102
3146173TUNIS
Solar/Wind Harmer
0.1
3143336POWHATN
Solar/Wind Harmer
1.49
3146263WOODLND
Solar/Wind Harmer
0.097
3145963POPLR C
Solar/Wind Harmer
0.097
944011AF1-069 GEN
Solar/Wind Harmer
5.826
3142666NORTHAMPTON
Solar/Wind Harmer
0.096
316011AB1-132 GEN
Solar/Wind Harmer
1.744
3145823KELFORD
Solar/Wind Harmer
0.096
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3145796HORNRTN
Solar/Wind Harmer
0.375
3145796HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.054
316212AC1-099_GEN
Solar/Wind Harmer
0.464
970917AG2-570 GEN
Solar/Wind Harmer
7.889
3145746EVERETS
Solar/Wind Harmer
0.087
3145746EVERETS
Solar/Wind Harmer
0.087
315722AD1-056 GEN
Solar/Wind Harmer
2.985
3146073TAR RVR
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
0.083
3146233WITAKRS
Solar/Wind Harmer
0.415
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
5.715
971623AH1-311 GEN
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.08
316478AD1-087 GEN
Solar/Wind Harmer
0.272
964241AG1-285 GEN
Solar/Wind Harmer
4.842
970257AG2-171 GEN
Solar/Wind Harmer
2.258
971775AH1-396 GEN
Solar/Wind Harmer
0.113
959311AF2-222 GEN
Solar/Wind Harmer
6.238
3144293JTRSVLE
Adder
0.162
3147133PAMPLIN
Solar/Wind Harmer
0.21
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.037
316222AC1-221 GEN
Solar/Wind Harmer
0.237
316283AC2-100 C
Solar/Wind Harmer
0.112
315052AA1-145 CT2
50/50
1.6
3142416OLDCHRC
Solar/Wind Harmer
0.57
3142416OLDCHRC
Solar/Wind Harmer
0.218
3143096IRON208
Adder
0.768
3142543TWELFTH
Solar/Wind Harmer
0.018
3150851SPRUNCC
Adder
0.809
944631AF1-128 GEN
Adder
82.378
315975AC1-164 GENB
Solar/Wind Harmer
0.052
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142433PROV 92
Solar/Wind Harmer
0.643
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
316132AB2-190 GEN1
Solar/Wind Harmer
0.834
3143526WINTERP
Solar/Wind Harmer
0.811
971069AG2-661 GEN
Solar/Wind Harmer
2.711
971777AH1-397 GEN
Solar/Wind Harmer
0.393
3141766HARMONY
Solar/Wind Harmer
0.03
961611AG1-000B GEN
Solar/Wind Harmer
7.493
3138133OCRAN
Solar/Wind Harmer
0.085
971317AH1-138 GEN
Solar/Wind Harmer
1.038
3151171GRAVELC
Adder
1.474
316381AD1-082 GEN
Solar/Wind Harmer
0.138
3138126ROCKLANDING
Solar/Wind Harmer
0.063
3143226MDLTHAN
Solar/Wind Harmer
0.135
962861AG1-135 GEN
Solar/Wind Harmer
4.283
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.403
3145336SMITFLD
Solar/Wind Harmer
0.529
3141726DUNNSVL
Solar/Wind Harmer
0.527
3150351NORNECKC2
Adder
1.281
316072AD1-144
Solar/Wind Harmer
0.044
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.022
3150981CHESPKA
Adder
1.529
316093AE2-104_GEN
Solar/Wind Harmer
2.031
944591AF1-124 GEN
Solar/Wind Harmer
27.185
315773AC2-141 GEN
Solar/Wind Harmer
4.372
316337AD2-073 GEN
Solar/Wind Harmer
0.103
3146456SLIGO L269
Solar/Wind Harmer
0.119
319010AE1-072 C
Solar/Wind Harmer
0.595
3146516WINFALL
Solar/Wind Harmer
0.375
3146516WINFALL
Solar/Wind Harmer
0.116
3130156CHOWAN
Solar/Wind Harmer
0.111
939411AE1-173 GEN
Solar/Wind Harmer
46.225
315816AE2-034 GEN
Solar/Wind Harmer
0.459
3145663CRESWEL
Solar/Wind Harmer
0.301
971163AH1-040 GEN
Solar/Wind Harmer
8.606
940641AE2-051 GEN
Solar/Wind Harmer
8.346
315737AD1-076 GEN
Solar/Wind Harmer
1.338
966881AG1-559 GEN
Solar/Wind Harmer
0.12
316023GEN1_S
Solar/Wind Harmer
0.229
3146206CASHIE
Solar/Wind Harmer
0.103
971547AH1-271 GEN
Solar/Wind Harmer
2.19
3145893MURPHYS
Solar/Wind Harmer
0.408
3145893MURPHYS
Solar/Wind Harmer
0.453
3146173TUNIS
Solar/Wind Harmer
0.1
3156021HOLLOMANSOL
Solar/Wind Harmer
0.452
3145683EARLEYS
Solar/Wind Harmer
0.099
3143336POWHATN
Solar/Wind Harmer
1.753
3146263WOODLND
Solar/Wind Harmer
0.097
315607AA1-063A GEN
Solar/Wind Harmer
0.196
960081AF2-299 GEN
Solar/Wind Harmer
0.933
3145963POPLR C
Solar/Wind Harmer
0.097
941031AE2-094 GEN
Solar/Wind Harmer
17.83
3145823KELFORD
Solar/Wind Harmer
0.096
3145796HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.094
972135AH1-637 GEN
Solar/Wind Harmer
0.8
3145783HORNRTN
Solar/Wind Harmer
0.093
3146293MARTNCO
Solar/Wind Harmer
0.084
3147043LAWRENC
Adder
0.815
970919AG2-571 GEN
Solar/Wind Harmer
3.156
3145746EVERETS
Solar/Wind Harmer
0.087
3145746EVERETS
Solar/Wind Harmer
0.087
970087AG2-069 GEN
Solar/Wind Harmer
6.997
316494AC1-189 GEN
Solar/Wind Harmer
0.287
961671AG1-007 GEN
Solar/Wind Harmer
0.013
3146083TARBORO
Solar/Wind Harmer
0.083
3145493TOT1
Solar/Wind Harmer
0.369
3146233WITAKRS
Solar/Wind Harmer
0.329
957481AF2-042 GEN
Solar/Wind Harmer
21.987
316129AC1-054 GEN
Solar/Wind Harmer
0.308
971065AG2-659 GEN
Solar/Wind Harmer
3.476
316359AB2-059 GEN
Solar/Wind Harmer
0.285
3142053HEARTS
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.064
315693AD1-088 GEN
Solar/Wind Harmer
3.815
316131AB2-060 GEN
Solar/Wind Harmer
0.229
315785AD2-033 C
Solar/Wind Harmer
0.575
316034AC1-036 C
Solar/Wind Harmer
0.005
970685AG2-442 GEN
Solar/Wind Harmer
5.119
970401AG2-262 GEN
Solar/Wind Harmer
0.399
971563AH1-280 GEN
Solar/Wind Harmer
0.724
3144293JTRSVLE
Adder
0.162
3144293JTRSVLE
Adder
0.128
970937AG2-583 GEN
Solar/Wind Harmer
3.968
3146926FARMVIL
Solar/Wind Harmer
0.037
971285AH1-108 GEN
Adder
1.324
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
316233AE1-074 FULL
Solar/Wind Harmer
0.125
971281AH1-106 GEN
Solar/Wind Harmer
2.165
971283AH1-107 GEN
Solar/Wind Harmer
2.165
3143873LANEXA
Solar/Wind Harmer
0.093
315697AD1-025 GEN
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.405
316159AE1-175 C
Solar/Wind Harmer
0.125
3141873WAN 176
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.142
3138133OCRAN
Solar/Wind Harmer
0.042
3143316POE
Solar/Wind Harmer
0.56
3138283WHITEMARSH
Solar/Wind Harmer
0.033
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
3151201GRAVEL4
Adder
10.083
3151221GRAVEL6
Adder
10.071
3151191GRAVEL3
Adder
9.955
3151211GRAVEL5
Adder
9.955
970657AG2-426 GEN
Solar/Wind Harmer
0.995
971445AH1-216 GEN
Solar/Wind Harmer
9.36
3141813NORNECK
Solar/Wind Harmer
0.128
316311AC2-079 GEN
Solar/Wind Harmer
3.639
3151081ELIZAR1
Adder
11.205
3151091ELIZAR2
Adder
11.01
316316AC1-027 C
Solar/Wind Harmer
0.116
957871AF2-081 GEN
Solar/Wind Harmer
5.956
3146406KITTY HAWK
Solar/Wind Harmer
0.015
313526AB2-022
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.118
3146486SUNBURY
Solar/Wind Harmer
0.118
3146396TANGLEW
Solar/Wind Harmer
0.323
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
9.18
3130156CHOWAN
Solar/Wind Harmer
0.111
3130156CHOWAN
Solar/Wind Harmer
0.111
3130546PLYMOUTH
Solar/Wind Harmer
0.105
315732AD1-074 GEN1
Solar/Wind Harmer
0.594
315733AD1-074 GEN2
Solar/Wind Harmer
0.594
3146206CASHIE
Solar/Wind Harmer
0.103
970601AG2-382 GEN
Solar/Wind Harmer
3.833
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.102
316463AE2-346 GEN
Solar/Wind Harmer
0.085
3145513AHOSKIE
Solar/Wind Harmer
0.208
3145513AHOSKIE
Solar/Wind Harmer
0.1
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.099
3145683EARLEYS
Solar/Wind Harmer
0.099
316258AE1-075 C
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.098
970533AG2-339 GEN
Solar/Wind Harmer
7.315
315652AC1-086 GEN
Solar/Wind Harmer
10.574
970673AG2-436 GEN
Solar/Wind Harmer
11.901
316426AA2-053 GEN
Solar/Wind Harmer
0.316
3137643SOCKMAN
Solar/Wind Harmer
0.377
3145796HORNRTN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.038
971967AH1-528 GEN
Solar/Wind Harmer
14.812
3146033SCOT NK
Solar/Wind Harmer
0.37
316210AC1-098 GEN
Solar/Wind Harmer
0.832
316274AC1-208 GEN
Solar/Wind Harmer
0.457
3145746EVERETS
Solar/Wind Harmer
0.348
3145746EVERETS
Solar/Wind Harmer
0.087
3145746EVERETS
Solar/Wind Harmer
0.087
3145746EVERETS
Solar/Wind Harmer
0.087
970085AG2-068 GEN
Solar/Wind Harmer
4.665
970581AG2-369 GEN
Solar/Wind Harmer
4.012
944491AF1-114 GEN
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.666
316327AA2-057 GEN
Solar/Wind Harmer
0.125
970831AG2-522 GEN
Solar/Wind Harmer
3.572
3145573BETHELC
Solar/Wind Harmer
0.083
3145573BETHELC
Solar/Wind Harmer
0.083
316486AD2-202 GEN
Solar/Wind Harmer
0.08
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.169
970681AG2-440 GEN
Solar/Wind Harmer
2.767
946301AF1-294 GEN
Solar/Wind Harmer
1.339
961791AG1-021 GEN
Solar/Wind Harmer
0.651
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
NYPJM->LTFIMP_NY
CLTF
0.787
LGEELTFEXP_LGEE->PJM
CLTF
0.09
WECLTFEXP_WEC->PJM
CLTF
0.038
TVALTFEXP_TVA->PJM
CLTF
0.946
CPLELTFEXP_CPLE->PJM
CLTF
4.415
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.147
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.001
MECLTFEXP_MEC->PJM
CLTF
0.448
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.22 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:680.73
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151221GRAVEL6
Adder
4.09
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.335
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:577.77
MW Contribution:
4.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.957
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.174
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
3150331BIRCHWDA
50/50
158.939
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
315749AE2-041 GEN
50/50
4.972
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150921YORKTN3
50/50
2
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3141766HARMONY
Solar/Wind Harmer
1.864
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.022
3151171GRAVELC
Adder
0.796
970293AG2-193 GEN
Solar/Wind Harmer
0.602
3150351NORNECKC2
50/50
2.968
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150641CHESTS8
50/50
0.191
944631AF1-128 GEN
50/50
30.096
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.999
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
971317AH1-138 GEN
Solar/Wind Harmer
0.632
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.972
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
972263AH1-716 GEN
50/50
35.581
3150631CHESTG8
50/50
0.372
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.03
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.066
3151221GRAVEL6
Adder
4.139
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
3141426STAFORD
Solar/Wind Helper
0.029
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
NYPJM->LTFIMP_NY
CLTF
0.471
LGEELTFEXP_LGEE->PJM
CLTF
0.179
WECLTFEXP_WEC->PJM
CLTF
0.088
TVALTFEXP_TVA->PJM
CLTF
0.6
CPLELTFEXP_CPLE->PJM
CLTF
1.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
MECLTFEXP_MEC->PJM
CLTF
0.511
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:166.0 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1864.65
MW Contribution:
3.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.539
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.527
3150691DARBY 3
50/50
11.369
3150701DARBY 4
50/50
11.342
3150681DARBY 2
50/50
11.329
966871AG1-558 GEN
Solar/Wind Harmer
0.187
316312AB1-027
Solar/Wind Harmer
0.287
3150671DARBY 1
Adder
10.664
3142946ENON
Solar/Wind Harmer
0.013
315976AC1-164 GENA
Solar/Wind Harmer
1.325
316169AC1-164_GENC
Solar/Wind Harmer
1.145
944641AF1-129 GEN
Adder
59.831
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.073
316349AD2-085 GEN
Solar/Wind Harmer
0.064
971223AH1-071 GEN
Solar/Wind Harmer
1.026
3150991CHESPKB
Adder
0.984
3150991CHESPKB
Adder
0.961
316294AC1-161 GEN
Solar/Wind Harmer
1.603
315835AF2-110_GEN
Solar/Wind Harmer
0.636
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.148
316388AE2-253 GEN
Solar/Wind Harmer
0.287
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.626
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.734
316315AB2-025 C
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
1.309
3146376EDENTON
Solar/Wind Harmer
0.384
3146376EDENTON
Solar/Wind Harmer
0.384
315614AA2-178 GEN
Solar/Wind Harmer
0.478
316065AD1-022 GEN
Solar/Wind Harmer
3.74
972193AH1-681 GEN
Adder
1.847
3145893MURPHYS
Solar/Wind Harmer
0.537
3145893MURPHYS
Solar/Wind Harmer
0.144
316365GEN2_N
Solar/Wind Harmer
0.178
316313AB2-026
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
316140AB2-099
Solar/Wind Harmer
0.028
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
962571AG1-106 GEN
Solar/Wind Harmer
1.082
313506AB2-031 GEN
Solar/Wind Harmer
0.232
316336AC2-165 C
Solar/Wind Harmer
3.818
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.319
3145783HORNRTN
Solar/Wind Harmer
1.055
3145783HORNRTN
Solar/Wind Harmer
0.33
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
3150341NORNECKC1
Adder
0.759
3150341NORNECKC1
Adder
0.753
316005AA1-067
Solar/Wind Harmer
0.076
972185AH1-677 GEN
Adder
3.987
972187AH1-678 GEN
Adder
2.005
315724AD1-057 GEN
Solar/Wind Harmer
1.352
970933AG2-581 GEN
Solar/Wind Harmer
5.569
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.181
316049AB1-081 GEN
Solar/Wind Harmer
0.377
316263AC1-034 GEN
Solar/Wind Harmer
2.521
970099AG2-077 GEN
Solar/Wind Harmer
7.073
970323AG2-213 GEN
Solar/Wind Harmer
2.672
970301AG2-198 GEN
Solar/Wind Harmer
2.657
958211AF2-115 GEN
Solar/Wind Harmer
0.742
3144293JTRSVLE
Adder
0.148
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.904
964791AG1-342 GEN
Solar/Wind Harmer
1.151
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
316118AC1-105 GEN
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
0.019
315052AA1-145 CT2
50/50
2.93
3142416OLDCHRC
Solar/Wind Harmer
0.419
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.025
3150851SPRUNCC
Adder
0.59
315975AC1-164 GENB
Solar/Wind Harmer
0.039
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.622
3142433PROV 92
Solar/Wind Harmer
0.46
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.025
3143526WINTERP
Solar/Wind Harmer
0.585
961611AG1-000B GEN
Solar/Wind Harmer
5.639
3151171GRAVELC
Adder
1.113
971317AH1-138 GEN
Solar/Wind Harmer
0.778
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3138126ROCKLANDING
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.104
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.017
3150981CHESPKA
Adder
1.173
315773AC2-141 GEN
Solar/Wind Harmer
3.386
316093AE2-104_GEN
Solar/Wind Harmer
1.558
944591AF1-124 GEN
Solar/Wind Harmer
20.914
3146456SLIGO L269
Solar/Wind Harmer
0.092
319010AE1-072 C
Solar/Wind Harmer
0.458
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.089
3130156CHOWAN
Solar/Wind Harmer
0.086
315816AE2-034 GEN
Solar/Wind Harmer
0.359
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.727
315737AD1-076 GEN
Solar/Wind Harmer
1.051
962861AG1-135 GEN
Solar/Wind Harmer
2.615
939411AE1-173 GEN
Solar/Wind Harmer
34.793
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.724
972277AH1-723 GEN
Adder
48.16
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.663
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.178
3143336POWHATN
Solar/Wind Harmer
1.416
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.357
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.229
3146263WOODLND
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.155
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.736
3145823KELFORD
Solar/Wind Harmer
0.076
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.658
941031AE2-094 GEN
Solar/Wind Harmer
13.353
3150351NORNECKC2
Adder
0.722
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.433
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.254
3146233WITAKRS
Solar/Wind Harmer
0.27
970087AG2-069 GEN
Solar/Wind Harmer
5.419
971065AG2-659 GEN
Solar/Wind Harmer
2.876
316359AB2-059 GEN
Solar/Wind Harmer
0.236
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.681
315693AD1-088 GEN
Solar/Wind Harmer
3.139
970937AG2-583 GEN
Solar/Wind Harmer
3.94
316131AB2-060 GEN
Solar/Wind Harmer
0.197
315785AD2-033 C
Solar/Wind Harmer
0.508
316034AC1-036 C
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
4.633
971563AH1-280 GEN
Solar/Wind Harmer
0.66
3144293JTRSVLE
Adder
0.148
3144293JTRSVLE
Adder
0.117
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.352
316337AD2-073 GEN
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Harmer
0.023
315051AA1-145 CT1
50/50
2.912
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.564
970293AG2-193 GEN
Solar/Wind Harmer
1.527
316075AC2-137 C
Solar/Wind Harmer
0.037
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.553
3150861SPRUNCD
Adder
0.59
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.164
316458AB2-190 GEN2
Solar/Wind Harmer
0.622
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.114
961611AG1-000B GEN
Solar/Wind Harmer
2.867
315813AE1-149 C
Solar/Wind Harmer
5.67
3151171GRAVELC
Adder
1.464
3141766HARMONY
Solar/Wind Harmer
1.388
3141843SHACKLE
Adder
0.532
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.593
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970657AG2-426 GEN
Solar/Wind Harmer
2.284
3145336SMITFLD
Solar/Wind Harmer
0.04
3141873WAN 176
Solar/Wind Harmer
1.781
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.711
944581AF1-123 GEN
Solar/Wind Harmer
20.84
944601AF1-125 GEN
Solar/Wind Harmer
20.519
316246AF1-032 C
Solar/Wind Harmer
0.041
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.062
316321Z2-027
Solar/Wind Harmer
0.016
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146376EDENTON
Solar/Wind Harmer
0.086
315735AD1-075 GEN1
Solar/Wind Harmer
0.233
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.328
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
3143336POWHATN
Solar/Wind Harmer
1.204
3146173TUNIS
Solar/Wind Harmer
0.079
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.38
316181AB2-040 GEN
Solar/Wind Harmer
0.108
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
316212AC1-099_GEN
Solar/Wind Harmer
0.374
944011AF1-069 GEN
Solar/Wind Harmer
4.363
3150351NORNECKC2
Adder
0.734
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.423
970917AG2-570 GEN
Solar/Wind Harmer
6.082
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.724
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.223
964241AG1-285 GEN
Solar/Wind Harmer
4.215
970257AG2-171 GEN
Solar/Wind Harmer
2.004
971775AH1-396 GEN
Solar/Wind Harmer
0.1
959311AF2-222 GEN
Solar/Wind Harmer
5.557
3144293JTRSVLE
Adder
0.148
3147133PAMPLIN
Solar/Wind Harmer
0.193
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
966881AG1-559 GEN
Solar/Wind Helper
1.231
971285AH1-108 GEN
Adder
0.965
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.561
971283AH1-107 GEN
Solar/Wind Harmer
1.561
315697AD1-025 GEN
Solar/Wind Harmer
0.121
316159AE1-175 C
Solar/Wind Harmer
0.095
3143873LANEXA
Solar/Wind Harmer
0.066
3143316POE
Solar/Wind Harmer
0.414
3151201GRAVEL4
Adder
7.616
3151221GRAVEL6
Adder
7.608
3151191GRAVEL3
Adder
7.52
3151211GRAVEL5
Adder
7.52
970189AG2-124 GEN
Solar/Wind Harmer
3.083
970657AG2-426 GEN
Solar/Wind Harmer
0.748
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.107
3141873WAN 176
Solar/Wind Harmer
0.02
316311AC2-079 GEN
Solar/Wind Harmer
2.766
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3151081ELIZAR1
Adder
8.601
3151091ELIZAR2
Adder
8.451
316316AC1-027 C
Solar/Wind Harmer
0.089
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
957871AF2-081 GEN
Solar/Wind Harmer
4.585
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.048
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
315814AE2-033 C
Solar/Wind Harmer
6.909
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.467
315733AD1-074 GEN2
Solar/Wind Harmer
0.467
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.018
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
316258AE1-075 C
Solar/Wind Harmer
0.059
316463AE2-346 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315652AC1-086 GEN
Solar/Wind Harmer
8.368
316426AA2-053 GEN
Solar/Wind Harmer
0.252
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
316210AC1-098 GEN
Solar/Wind Harmer
0.671
970533AG2-339 GEN
Solar/Wind Harmer
5.478
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
8.951
316274AC1-208 GEN
Solar/Wind Harmer
0.37
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
971967AH1-528 GEN
Solar/Wind Harmer
11.302
957861AF2-080 GEN
Solar/Wind Harmer
2.995
316327AA2-057 GEN
Solar/Wind Harmer
0.102
970831AG2-522 GEN
Solar/Wind Harmer
2.935
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
970085AG2-068 GEN
Solar/Wind Harmer
3.613
970581AG2-369 GEN
Solar/Wind Harmer
3.107
316486AD2-202 GEN
Solar/Wind Harmer
0.066
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
3.75
970681AG2-440 GEN
Solar/Wind Harmer
2.489
946301AF1-294 GEN
Solar/Wind Harmer
1.22
961791AG1-021 GEN
Solar/Wind Harmer
0.594
971845AH1-439 GEN
Solar/Wind Harmer
2.623
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
LAGNLTFEXP_LAGN->PJM
CLTF
3.247
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.235
NYPJM->LTFIMP_NY
CLTF
1.31
LGEELTFEXP_LGEE->PJM
CLTF
0.629
WECLTFEXP_WEC->PJM
CLTF
0.312
TVALTFEXP_TVA->PJM
CLTF
1.648
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.496
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.75
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.692
MECLTFEXP_MEC->PJM
CLTF
1.648
SIGELTFEXP_SIGE->PJM
CLTF
0.051

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.47 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1263.35
MW Contribution:
2.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
5.93
3142296MT RD221
50/50
0.447
3142366NRTHEST
50/50
0.389
3150691DARBY 3
50/50
8.264
3150701DARBY 4
50/50
8.245
3150681DARBY 2
50/50
8.235
966871AG1-558 GEN
Solar/Wind Harmer
0.136
316312AB1-027
Solar/Wind Harmer
0.203
971285AH1-108 GEN
Adder
0.768
316233AE1-074 FULL
Solar/Wind Harmer
0.079
971281AH1-106 GEN
Solar/Wind Harmer
1.361
971283AH1-107 GEN
Solar/Wind Harmer
1.361
3143316POE
Solar/Wind Harmer
0.336
315697AD1-025 GEN
Solar/Wind Harmer
0.089
3142433PROV 92
Adder
0.155
3142433PROV 92
Adder
0.155
970657AG2-426 GEN
Solar/Wind Harmer
0.581
3151201GRAVEL4
Adder
5.611
3151221GRAVEL6
Adder
5.605
3151191GRAVEL3
Adder
5.54
3151211GRAVEL5
Adder
5.54
971445AH1-216 GEN
Solar/Wind Harmer
5.266
316159AE1-175 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
5.86
316311AC2-079 GEN
Solar/Wind Harmer
2.125
3143873LANEXA
Solar/Wind Harmer
0.044
316258AE1-075 C
Solar/Wind Harmer
0.055
3151081ELIZAR1
Adder
6.45
3151091ELIZAR2
Adder
6.338
316316AC1-027 C
Solar/Wind Harmer
0.067
957871AF2-081 GEN
Solar/Wind Harmer
3.455
3146406KITTY HAWK
Solar/Wind Harmer
0.009
970189AG2-124 GEN
Solar/Wind Harmer
2.048
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
313526AB2-022
Solar/Wind Harmer
0.037
3138283WHITEMARSH
Solar/Wind Harmer
0.016
3146396TANGLEW
Solar/Wind Harmer
0.189
3145176PASQUOTANK
Solar/Wind Harmer
0.042
970533AG2-339 GEN
Solar/Wind Harmer
5.155
970673AG2-436 GEN
Solar/Wind Harmer
8.402
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
3141873WAN 176
Solar/Wind Harmer
0.013
971967AH1-528 GEN
Solar/Wind Harmer
10.529
3130546PLYMOUTH
Solar/Wind Harmer
0.064
315732AD1-074 GEN1
Solar/Wind Harmer
0.364
315733AD1-074 GEN2
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
0.064
3146206CASHIE
Solar/Wind Harmer
0.063
970601AG2-382 GEN
Solar/Wind Harmer
2.368
3141913WHIT STONE
Solar/Wind Harmer
0.063
316463AE2-346 GEN
Solar/Wind Harmer
0.053
3145513AHOSKIE
Solar/Wind Harmer
0.131
3145513AHOSKIE
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
6.871
315052AA1-145 CT2
50/50
2.657
3142416OLDCHRC
Solar/Wind Harmer
0.297
3142416OLDCHRC
Solar/Wind Harmer
0.114
3142543TWELFTH
Solar/Wind Harmer
0.01
3150851SPRUNCC
Adder
0.469
3143096IRON208
Adder
0.419
3143526WINTERP
Solar/Wind Harmer
0.51
3143226MDLTHAN
Solar/Wind Harmer
0.093
944631AF1-128 GEN
Adder
43.786
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.462
971069AG2-661 GEN
Solar/Wind Harmer
1.502
315975AC1-164 GENB
Solar/Wind Harmer
0.026
316381AD1-082 GEN
Solar/Wind Harmer
0.081
3142433PROV 92
Solar/Wind Harmer
0.319
3142433PROV 92
Adder
0.155
3142433PROV 92
Adder
0.155
961611AG1-000B GEN
Solar/Wind Harmer
4.164
3151171GRAVELC
Adder
0.82
3145336SMITFLD
Solar/Wind Harmer
0.298
3143336POWHATN
Solar/Wind Harmer
1.299
3138126ROCKLANDING
Solar/Wind Harmer
0.033
316072AD1-144
Solar/Wind Harmer
0.025
971317AH1-138 GEN
Solar/Wind Harmer
0.528
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.013
316093AE2-104_GEN
Solar/Wind Harmer
1.186
3150981CHESPKA
Adder
0.88
940641AE2-051 GEN
Solar/Wind Harmer
5.617
939411AE1-173 GEN
Solar/Wind Harmer
29.89
944591AF1-124 GEN
Solar/Wind Harmer
15.714
3146456SLIGO L269
Solar/Wind Harmer
0.069
319010AE1-072 C
Solar/Wind Harmer
0.345
971777AH1-397 GEN
Solar/Wind Harmer
0.183
3141766HARMONY
Solar/Wind Harmer
0.014
315773AC2-141 GEN
Solar/Wind Harmer
2.491
941031AE2-094 GEN
Solar/Wind Harmer
12.566
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.068
316023GEN1_S
Solar/Wind Harmer
0.148
3130156CHOWAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.278
3145663CRESWEL
Solar/Wind Harmer
0.182
971163AH1-040 GEN
Solar/Wind Harmer
5.209
315737AD1-076 GEN
Solar/Wind Harmer
0.82
960081AF2-299 GEN
Solar/Wind Harmer
0.613
315051AA1-145 CT1
50/50
2.641
316473AC1-191 GEN
Solar/Wind Harmer
0.398
3142416OLDCHRC
Solar/Wind Harmer
1.109
3150861SPRUNCD
Adder
0.469
970293AG2-193 GEN
Solar/Wind Harmer
1.081
3143096IRON208
Adder
0.419
3143096IRON208
Adder
0.41
316075AC2-137 C
Solar/Wind Harmer
0.025
970133AG2-095 GEN
Solar/Wind Harmer
0.867
3142946ENON
Solar/Wind Harmer
0.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.462
315778AD1-151 GEN
Solar/Wind Harmer
6.759
315813AE1-149 C
Solar/Wind Harmer
4.449
3142433PROV 92
Adder
0.155
3142433PROV 92
Adder
0.155
961611AG1-000B GEN
Solar/Wind Harmer
2.117
970657AG2-426 GEN
Solar/Wind Harmer
1.776
3151171GRAVELC
Adder
1.078
3145336SMITFLD
Solar/Wind Harmer
0.03
3143336POWHATN
Solar/Wind Harmer
1.104
3144216WINCHST
Adder
0.271
3144536CHRHLND
Solar/Wind Harmer
0.011
3150921YORKTN3
Adder
1.789
971781AH1-399 GEN
Solar/Wind Harmer
0.093
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.533
316246AF1-032 C
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
15.658
944601AF1-125 GEN
Solar/Wind Harmer
15.417
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.801
3141843SHACKLE
Adder
0.353
316203AE2-005 GEN
Solar/Wind Harmer
0
3145273HOLLAND
Solar/Wind Harmer
0.051
316321Z2-027
Solar/Wind Harmer
0.012
3141766HARMONY
Solar/Wind Harmer
0.912
944011AF1-069 GEN
Solar/Wind Harmer
4.106
3146516WINFALL
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.066
3141873WAN 176
Solar/Wind Harmer
1.175
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
0.064
3146206CASHIE
Solar/Wind Harmer
0.063
970917AG2-570 GEN
Solar/Wind Harmer
5.626
3146173TUNIS
Solar/Wind Harmer
0.063
316181AB2-040 GEN
Solar/Wind Harmer
0.089
316011AB1-132 GEN
Solar/Wind Harmer
1.133
3142666NORTHAMPTON
Solar/Wind Harmer
0.062
3146263WOODLND
Solar/Wind Harmer
0.062
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.061
3147043LAWRENC
Solar/Wind Harmer
0.037
3145963POPLR C
Solar/Wind Harmer
0.061
316212AC1-099_GEN
Solar/Wind Harmer
0.304
3145933PARMELE
Solar/Wind Harmer
0.058
316478AD1-087 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.991
3145746EVERETS
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.057
966881AG1-559 GEN
Solar/Wind Helper
1.249
3150671DARBY 1
Adder
7.752
3143526WINTERP
Solar/Wind Harmer
0.51
944641AF1-129 GEN
Adder
46.057
971223AH1-071 GEN
Solar/Wind Harmer
0.989
3142946ENON
Solar/Wind Harmer
0.009
316033AB2-134 GEN
Solar/Wind Harmer
0
315976AC1-164 GENA
Solar/Wind Harmer
0.872
316169AC1-164_GENC
Solar/Wind Harmer
0.753
3144356SAPONY
Solar/Wind Harmer
0.623
316315AB2-025 C
Solar/Wind Harmer
0.06
316349AD2-085 GEN
Solar/Wind Harmer
0.049
316313AB2-026
Solar/Wind Harmer
0.045
315835AF2-110_GEN
Solar/Wind Harmer
0.484
3150991CHESPKB
Adder
0.738
3150991CHESPKB
Adder
0.72
3145506HICKORY
Solar/Wind Harmer
0.278
3145506HICKORY
Solar/Wind Harmer
0.167
3145506HICKORY
Solar/Wind Harmer
0.042
316339AD2-160 GEN
Solar/Wind Harmer
0.111
316388AE2-253 GEN
Solar/Wind Harmer
0.216
3137176SLIGO L2192
Solar/Wind Harmer
0.276
3146456SLIGO L269
Solar/Wind Harmer
1.226
3130086AYDLETT
Solar/Wind Harmer
0.277
3146386ELIZ CT
Solar/Wind Harmer
0.069
316294AC1-161 GEN
Solar/Wind Harmer
1.179
3146516WINFALL
Solar/Wind Harmer
0.068
3146516WINFALL
Solar/Wind Harmer
0.068
3146516WINFALL
Solar/Wind Harmer
0.068
316336AC2-165 C
Solar/Wind Harmer
3.44
315742AE1-103 GEN
Solar/Wind Harmer
1.014
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
316365GEN2_N
Solar/Wind Harmer
0.148
972185AH1-677 GEN
Adder
3.728
3146376EDENTON
Solar/Wind Harmer
0.295
3146376EDENTON
Solar/Wind Harmer
0.295
316156AD2-030 GEN
Solar/Wind Harmer
0.048
972187AH1-678 GEN
Adder
1.869
315614AA2-178 GEN
Solar/Wind Harmer
0.37
970933AG2-581 GEN
Solar/Wind Harmer
5.155
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.115
316065AD1-022 GEN
Solar/Wind Harmer
2.929
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
313506AB2-031 GEN
Solar/Wind Harmer
0.192
962571AG1-106 GEN
Solar/Wind Harmer
0.889
3142666NORTHAMPTON
Solar/Wind Harmer
0.062
3142666NORTHAMPTON
Solar/Wind Harmer
0.062
3142666NORTHAMPTON
Solar/Wind Harmer
0.062
3142666NORTHAMPTON
Solar/Wind Harmer
0.037
3145796HORNRTN
Solar/Wind Harmer
0.184
3145593CAROLNA
Solar/Wind Harmer
0.061
3145593CAROLNA
Solar/Wind Harmer
0.061
3145593CAROLNA
Solar/Wind Harmer
0.076
3145783HORNRTN
Solar/Wind Harmer
1.081
3145783HORNRTN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
0.27
3145783HORNRTN
Solar/Wind Harmer
0.108
970099AG2-077 GEN
Solar/Wind Harmer
6.408
3145933PARMELE
Solar/Wind Harmer
0.117
3145933PARMELE
Solar/Wind Harmer
0.058
315724AD1-057 GEN
Solar/Wind Harmer
1.11
316005AA1-067
Solar/Wind Harmer
0.061
970085AG2-068 GEN
Solar/Wind Harmer
3.333
970581AG2-369 GEN
Solar/Wind Harmer
2.866
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.019
3137643SOCKMAN
Solar/Wind Harmer
0.247
316426AA2-053 GEN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
0.025
3141783LANCAST
Solar/Wind Harmer
0.036
3141783LANCAST
Solar/Wind Harmer
0.024
3146033SCOT NK
Solar/Wind Harmer
0.24
316210AC1-098 GEN
Solar/Wind Harmer
0.545
316274AC1-208 GEN
Solar/Wind Harmer
0.302
316486AD2-202 GEN
Solar/Wind Harmer
0.059
970831AG2-522 GEN
Solar/Wind Harmer
2.462
3145746EVERETS
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.057
316327AA2-057 GEN
Solar/Wind Harmer
0.084
3141426STAFORD
Solar/Wind Helper
0.03
3145893MURPHYS
Solar/Wind Harmer
0.255
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.063
971547AH1-271 GEN
Solar/Wind Harmer
1.353
970919AG2-571 GEN
Solar/Wind Harmer
2.25
3146173TUNIS
Solar/Wind Harmer
0.063
3156021HOLLOMANSOL
Solar/Wind Harmer
0.282
315607AA1-063A GEN
Solar/Wind Harmer
0.126
970087AG2-069 GEN
Solar/Wind Harmer
4.999
3145683EARLEYS
Solar/Wind Harmer
0.062
3146263WOODLND
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.037
3145796HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.061
3147043LAWRENC
Adder
0.552
3145963POPLR C
Solar/Wind Harmer
0.061
3145783HORNRTN
Solar/Wind Harmer
0.061
957481AF2-042 GEN
Solar/Wind Harmer
16.02
315693AD1-088 GEN
Solar/Wind Harmer
2.815
3146293MARTNCO
Solar/Wind Harmer
0.054
316129AC1-054 GEN
Solar/Wind Harmer
0.214
3145746EVERETS
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.057
971065AG2-659 GEN
Solar/Wind Harmer
2.427
LAGNLTFEXP_LAGN->PJM
CLTF
2.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.391
NYPJM->LTFIMP_NY
CLTF
0.92
LGEELTFEXP_LGEE->PJM
CLTF
0.385
TVALTFEXP_TVA->PJM
CLTF
1.175
WECLTFEXP_WEC->PJM
CLTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
3.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.043
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.401
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.997
MECLTFEXP_MEC->PJM
CLTF
1.061
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.35 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1046.68
MW Contribution:
2.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
0.052
3150411LDYSMT5
50/50
24.482
3150381LDYSMT2
50/50
23.431
972213AH1-691 GEN
50/50
3.964
972215AH1-692 GEN
50/50
3.964
315759AF1-018 GEN
50/50
3.542
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
970189AG2-124 GEN
Solar/Wind Harmer
2.94
957191AF2-013 GEN
50/50
31.484
3150391LDYSMT3
50/50
24.36
972195AH1-682 GEN
50/50
3.201
3150341NORNECKC1
50/50
1.769
3150341NORNECKC1
50/50
1.755
3141843SHACKLE
50/50
0.029
315673AE1-157 GEN
Solar/Wind Harmer
10.317
316156AD2-030 GEN
Solar/Wind Harmer
0.075
972189AH1-679 GEN
Adder
1.606
966871AG1-558 GEN
Solar/Wind Harmer
0.11
315976AC1-164 GENA
Solar/Wind Harmer
0.798
316169AC1-164_GENC
Solar/Wind Harmer
0.69
316312AB1-027
Solar/Wind Harmer
0.13
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.1
3150701DARBY 4
Adder
5.088
3150681DARBY 2
Adder
5.082
3150671DARBY 1
Adder
5.076
3142366NRTHEST
Adder
0.228
944641AF1-129 GEN
Adder
30.404
316033AB2-134 GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.306
3150991CHESPKB
Adder
0.598
3150991CHESPKB
Adder
0.584
316349AD2-085 GEN
Solar/Wind Harmer
0.038
316294AC1-161 GEN
Solar/Wind Harmer
0.975
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.135
3145506HICKORY
Solar/Wind Harmer
0.034
3150331BIRCHWDA
50/50
74.465
3150401LDYSMT4
50/50
24.406
3150371LDYSMT1
50/50
23.583
3150501FRIVERG
50/50
1.374
3150351NORNECKC2
50/50
1.713
966661AG1-536 GEN
50/50
4.06
315749AE2-041 GEN
50/50
3.542
3141843SHACKLE
50/50
0.538
316223AC1-118
Solar/Wind Harmer
0.153
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
3141873WAN 176
Solar/Wind Harmer
1.824
3141766HARMONY
Solar/Wind Harmer
1.328
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.321
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
316075AC2-137 C
Solar/Wind Harmer
0.02
3142416OLDCHRC
Solar/Wind Harmer
0.708
970293AG2-193 GEN
Solar/Wind Harmer
0.773
3142946ENON
Solar/Wind Harmer
0.024
3143096IRON208
Adder
0.288
3143096IRON208
Adder
0.282
3150921YORKTN3
Adder
1.716
3144216WINCHST
Adder
0.253
970133AG2-095 GEN
Solar/Wind Harmer
0.629
316458AB2-190 GEN2
Solar/Wind Harmer
0.344
315778AD1-151 GEN
Solar/Wind Harmer
5.12
3150861SPRUNCD
Adder
0.294
961611AG1-000B GEN
Solar/Wind Harmer
1.67
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.181
970657AG2-426 GEN
Solar/Wind Harmer
1.312
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.296
944581AF1-123 GEN
Solar/Wind Harmer
12.713
944601AF1-125 GEN
Solar/Wind Harmer
12.518
316246AF1-032 C
Solar/Wind Harmer
0.025
972197AH1-683 GEN
50/50
3.811
972219AH1-694 GEN
50/50
2.744
3150351NORNECKC2
50/50
1.684
972135AH1-637 GEN
Solar/Wind Harmer
2.209
316337AD2-073 GEN
Solar/Wind Harmer
0.161
3141726DUNNSVL
Solar/Wind Harmer
0.606
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.72
962861AG1-135 GEN
Solar/Wind Harmer
4.489
966881AG1-559 GEN
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
315975AC1-164 GENB
Solar/Wind Harmer
0.024
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
944631AF1-128 GEN
Adder
33.437
3143096IRON208
Adder
0.288
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.344
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.138
3150851SPRUNCC
Adder
0.294
961611AG1-000B GEN
Solar/Wind Harmer
3.285
3151171GRAVELC
Adder
0.66
3145336SMITFLD
Solar/Wind Harmer
0.24
3143526WINTERP
Solar/Wind Harmer
0.306
316381AD1-082 GEN
Solar/Wind Harmer
0.059
316072AD1-144
Solar/Wind Harmer
0.021
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.713
315773AC2-141 GEN
Solar/Wind Harmer
2.059
944591AF1-124 GEN
Solar/Wind Harmer
12.759
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316159AE1-175 C
Solar/Wind Harmer
0.061
971285AH1-108 GEN
Adder
0.481
315697AD1-025 GEN
Solar/Wind Harmer
0.068
3151201GRAVEL4
Adder
4.514
3151221GRAVEL6
Adder
4.509
3151191GRAVEL3
Adder
4.457
3151211GRAVEL5
Adder
4.457
971445AH1-216 GEN
Solar/Wind Harmer
4.247
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.818
971283AH1-107 GEN
Solar/Wind Harmer
0.818
970657AG2-426 GEN
Solar/Wind Harmer
0.43
3143316POE
Solar/Wind Harmer
0.231
316311AC2-079 GEN
Solar/Wind Harmer
1.639
3151081ELIZAR1
Adder
5.23
3151091ELIZAR2
Adder
5.139
316316AC1-027 C
Solar/Wind Harmer
0.054
3141426STAFORD
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
2
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.77
NYPJM->LTFIMP_NY
CLTF
0.799
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.193
TVALTFEXP_TVA->PJM
CLTF
1.011
CPLELTFEXP_CPLE->PJM
CLTF
2.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.492
MECLTFEXP_MEC->PJM
CLTF
1.016
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2119_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2119_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.33 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1046.51
MW Contribution:
2.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
31.484
3150391LDYSMT3
50/50
24.36
972195AH1-682 GEN
50/50
3.201
3150341NORNECKC1
50/50
1.769
3150341NORNECKC1
50/50
1.755
3141843SHACKLE
50/50
0.029
315673AE1-157 GEN
Solar/Wind Harmer
10.317
316156AD2-030 GEN
Solar/Wind Harmer
0.075
972189AH1-679 GEN
Adder
1.606
966871AG1-558 GEN
Solar/Wind Harmer
0.11
315976AC1-164 GENA
Solar/Wind Harmer
0.798
316169AC1-164_GENC
Solar/Wind Harmer
0.69
316312AB1-027
Solar/Wind Harmer
0.13
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.1
3150701DARBY 4
Adder
5.088
3150681DARBY 2
Adder
5.082
3150671DARBY 1
Adder
5.076
3142366NRTHEST
Adder
0.228
944641AF1-129 GEN
Adder
30.404
316033AB2-134 GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.306
3150991CHESPKB
Adder
0.598
3150991CHESPKB
Adder
0.584
316349AD2-085 GEN
Solar/Wind Harmer
0.038
316294AC1-161 GEN
Solar/Wind Harmer
0.975
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.135
3145506HICKORY
Solar/Wind Harmer
0.034
3150331BIRCHWDA
50/50
74.465
3150401LDYSMT4
50/50
24.406
3150371LDYSMT1
50/50
23.583
3150501FRIVERG
50/50
1.374
3150351NORNECKC2
50/50
1.713
966661AG1-536 GEN
50/50
4.06
315749AE2-041 GEN
50/50
3.542
3141843SHACKLE
50/50
0.538
316223AC1-118
Solar/Wind Harmer
0.153
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
3141873WAN 176
Solar/Wind Harmer
1.824
3141766HARMONY
Solar/Wind Harmer
1.328
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.321
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
316075AC2-137 C
Solar/Wind Harmer
0.02
3142416OLDCHRC
Solar/Wind Harmer
0.708
970293AG2-193 GEN
Solar/Wind Harmer
0.773
3142946ENON
Solar/Wind Harmer
0.024
3143096IRON208
Adder
0.288
3143096IRON208
Adder
0.282
3150921YORKTN3
Adder
1.716
3144216WINCHST
Adder
0.253
970133AG2-095 GEN
Solar/Wind Harmer
0.629
316458AB2-190 GEN2
Solar/Wind Harmer
0.344
315778AD1-151 GEN
Solar/Wind Harmer
5.12
3150861SPRUNCD
Adder
0.294
961611AG1-000B GEN
Solar/Wind Harmer
1.67
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.181
970657AG2-426 GEN
Solar/Wind Harmer
1.312
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.296
944581AF1-123 GEN
Solar/Wind Harmer
12.713
944601AF1-125 GEN
Solar/Wind Harmer
12.518
316246AF1-032 C
Solar/Wind Harmer
0.025
972197AH1-683 GEN
50/50
3.811
972219AH1-694 GEN
50/50
2.744
3150351NORNECKC2
50/50
1.684
972135AH1-637 GEN
Solar/Wind Harmer
2.209
316337AD2-073 GEN
Solar/Wind Harmer
0.161
3141726DUNNSVL
Solar/Wind Harmer
0.606
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.72
962861AG1-135 GEN
Solar/Wind Harmer
4.489
966881AG1-559 GEN
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
315975AC1-164 GENB
Solar/Wind Harmer
0.024
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
944631AF1-128 GEN
Adder
33.437
3143096IRON208
Adder
0.288
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.344
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.138
3150851SPRUNCC
Adder
0.294
961611AG1-000B GEN
Solar/Wind Harmer
3.285
3151171GRAVELC
Adder
0.66
3145336SMITFLD
Solar/Wind Harmer
0.24
3143526WINTERP
Solar/Wind Harmer
0.306
316381AD1-082 GEN
Solar/Wind Harmer
0.059
316072AD1-144
Solar/Wind Harmer
0.021
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.713
315773AC2-141 GEN
Solar/Wind Harmer
2.059
944591AF1-124 GEN
Solar/Wind Harmer
12.759
3141316ARNOLDS
50/50
0.052
3150411LDYSMT5
50/50
24.482
3150381LDYSMT2
50/50
23.431
972213AH1-691 GEN
50/50
3.964
972215AH1-692 GEN
50/50
3.964
315759AF1-018 GEN
50/50
3.542
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
970189AG2-124 GEN
Solar/Wind Harmer
2.94
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316159AE1-175 C
Solar/Wind Harmer
0.061
971285AH1-108 GEN
Adder
0.481
315697AD1-025 GEN
Solar/Wind Harmer
0.068
3151201GRAVEL4
Adder
4.514
3151221GRAVEL6
Adder
4.509
3151191GRAVEL3
Adder
4.457
3151211GRAVEL5
Adder
4.457
971445AH1-216 GEN
Solar/Wind Harmer
4.247
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.818
971283AH1-107 GEN
Solar/Wind Harmer
0.818
970657AG2-426 GEN
Solar/Wind Harmer
0.43
3143316POE
Solar/Wind Harmer
0.231
316311AC2-079 GEN
Solar/Wind Harmer
1.639
3151081ELIZAR1
Adder
5.23
3151091ELIZAR2
Adder
5.139
316316AC1-027 C
Solar/Wind Harmer
0.054
3141426STAFORD
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
2
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.77
NYPJM->LTFIMP_NY
CLTF
0.799
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.193
TVALTFEXP_TVA->PJM
CLTF
1.011
CPLELTFEXP_CPLE->PJM
CLTF
2.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.492
MECLTFEXP_MEC->PJM
CLTF
1.016
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.58 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:785.94
MW Contribution:
2.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
28.8
3150391LDYSMT3
50/50
22.284
972195AH1-682 GEN
50/50
2.928
3150341NORNECKC1
50/50
1.619
3150341NORNECKC1
50/50
1.606
3141843SHACKLE
50/50
0.027
315673AE1-157 GEN
Solar/Wind Harmer
9.437
316156AD2-030 GEN
Solar/Wind Harmer
0.069
972189AH1-679 GEN
Adder
1.469
966871AG1-558 GEN
Solar/Wind Harmer
0.101
315976AC1-164 GENA
Solar/Wind Harmer
0.73
316169AC1-164_GENC
Solar/Wind Harmer
0.631
316312AB1-027
Solar/Wind Harmer
0.119
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.207
3150691DARBY 3
Adder
4.665
3150701DARBY 4
Adder
4.654
3150681DARBY 2
Adder
4.648
3150671DARBY 1
Adder
4.643
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.811
316033AB2-134 GEN
Solar/Wind Harmer
0
3141316ARNOLDS
50/50
0.048
3150411LDYSMT5
50/50
22.395
3150381LDYSMT2
50/50
21.433
972213AH1-691 GEN
50/50
3.626
972215AH1-692 GEN
50/50
3.626
315759AF1-018 GEN
50/50
3.24
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.146
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
0.019
970189AG2-124 GEN
Solar/Wind Harmer
2.689
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3138283WHITEMARSH
Solar/Wind Harmer
0.018
316159AE1-175 C
Solar/Wind Harmer
0.055
971285AH1-108 GEN
Adder
0.44
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3141426STAFORD
Solar/Wind Helper
0.047
972197AH1-683 GEN
50/50
3.486
972219AH1-694 GEN
50/50
2.51
3150351NORNECKC2
50/50
1.541
972135AH1-637 GEN
Solar/Wind Harmer
2.021
316337AD2-073 GEN
Solar/Wind Harmer
0.147
3141726DUNNSVL
Solar/Wind Harmer
0.554
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.317
962861AG1-135 GEN
Solar/Wind Harmer
4.106
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.239
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
315975AC1-164 GENB
Solar/Wind Harmer
0.022
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.498
944631AF1-128 GEN
Adder
30.586
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.315
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.041
3150851SPRUNCC
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
3.004
3151171GRAVELC
Adder
0.603
3150331BIRCHWDA
50/50
68.117
3150401LDYSMT4
50/50
22.325
3150371LDYSMT1
50/50
21.572
3150501FRIVERG
50/50
1.257
3150351NORNECKC2
50/50
1.567
966661AG1-536 GEN
50/50
3.714
315749AE2-041 GEN
50/50
3.24
3141843SHACKLE
50/50
0.492
316223AC1-118
Solar/Wind Harmer
0.14
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
3141873WAN 176
Solar/Wind Harmer
1.668
3141766HARMONY
Solar/Wind Harmer
1.215
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
316075AC2-137 C
Solar/Wind Harmer
0.018
3142416OLDCHRC
Solar/Wind Harmer
0.647
970293AG2-193 GEN
Solar/Wind Harmer
0.708
3142946ENON
Solar/Wind Harmer
0.022
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.258
3150921YORKTN3
Adder
1.57
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316458AB2-190 GEN2
Solar/Wind Harmer
0.315
315778AD1-151 GEN
Solar/Wind Harmer
4.683
3150861SPRUNCD
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
1.528
3151171GRAVELC
Adder
0.794
LAGNLTFEXP_LAGN->PJM
CLTF
1.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.277
NYPJM->LTFIMP_NY
CLTF
0.731
LGEELTFEXP_LGEE->PJM
CLTF
0.352
WECLTFEXP_WEC->PJM
CLTF
0.176
TVALTFEXP_TVA->PJM
CLTF
0.925
CPLELTFEXP_CPLE->PJM
CLTF
2.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.194
MECLTFEXP_MEC->PJM
CLTF
0.929
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2104_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2104_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.55 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:742.66
MW Contribution:
2.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
68.117
3150401LDYSMT4
50/50
22.325
3150371LDYSMT1
50/50
21.572
3150501FRIVERG
50/50
1.257
3150351NORNECKC2
50/50
1.567
966661AG1-536 GEN
50/50
3.714
957191AF2-013 GEN
50/50
28.8
3150391LDYSMT3
50/50
22.284
972195AH1-682 GEN
50/50
2.928
3150341NORNECKC1
50/50
1.619
3150341NORNECKC1
50/50
1.606
3141843SHACKLE
50/50
0.027
315673AE1-157 GEN
Solar/Wind Harmer
9.437
316156AD2-030 GEN
Solar/Wind Harmer
0.069
972189AH1-679 GEN
Adder
1.469
966871AG1-558 GEN
Solar/Wind Harmer
0.101
315976AC1-164 GENA
Solar/Wind Harmer
0.73
316169AC1-164_GENC
Solar/Wind Harmer
0.631
316312AB1-027
Solar/Wind Harmer
0.119
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.207
3150691DARBY 3
Adder
4.665
3150701DARBY 4
Adder
4.654
3150681DARBY 2
Adder
4.648
3150671DARBY 1
Adder
4.643
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.811
316033AB2-134 GEN
Solar/Wind Harmer
0
3141346CRANES
50/50
0.542
972197AH1-683 GEN
50/50
3.486
972219AH1-694 GEN
50/50
2.51
3150351NORNECKC2
50/50
1.541
972135AH1-637 GEN
Solar/Wind Harmer
2.021
316337AD2-073 GEN
Solar/Wind Harmer
0.147
3141726DUNNSVL
Solar/Wind Harmer
0.554
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.317
962861AG1-135 GEN
Solar/Wind Harmer
4.106
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.239
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
315975AC1-164 GENB
Solar/Wind Harmer
0.022
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.498
944631AF1-128 GEN
Adder
30.586
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.315
315671AE2-027_GEN
Solar/Wind Harmer
0
971069AG2-661 GEN
Solar/Wind Harmer
1.041
3150851SPRUNCC
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
3.004
3151171GRAVELC
Adder
0.603
3141316ARNOLDS
50/50
0.048
3150411LDYSMT5
50/50
22.395
3150381LDYSMT2
50/50
21.433
972213AH1-691 GEN
50/50
3.626
972215AH1-692 GEN
50/50
3.626
315759AF1-018 GEN
50/50
3.24
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.146
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
0.019
970189AG2-124 GEN
Solar/Wind Harmer
2.689
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3138283WHITEMARSH
Solar/Wind Harmer
0.018
316159AE1-175 C
Solar/Wind Harmer
0.055
971285AH1-108 GEN
Adder
0.44
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3141426STAFORD
Solar/Wind Helper
0.047
315749AE2-041 GEN
50/50
3.24
3141843SHACKLE
50/50
0.492
316223AC1-118
Solar/Wind Harmer
0.14
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
3141873WAN 176
Solar/Wind Harmer
1.668
3141766HARMONY
Solar/Wind Harmer
1.215
316203AE2-005 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
316075AC2-137 C
Solar/Wind Harmer
0.018
3142416OLDCHRC
Solar/Wind Harmer
0.647
970293AG2-193 GEN
Solar/Wind Harmer
0.708
3142946ENON
Solar/Wind Harmer
0.022
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.258
3150921YORKTN3
Adder
1.57
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316458AB2-190 GEN2
Solar/Wind Harmer
0.315
315778AD1-151 GEN
Solar/Wind Harmer
4.683
3150861SPRUNCD
Adder
0.269
961611AG1-000B GEN
Solar/Wind Harmer
1.528
3151171GRAVELC
Adder
0.794
LAGNLTFEXP_LAGN->PJM
CLTF
1.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.277
NYPJM->LTFIMP_NY
CLTF
0.731
LGEELTFEXP_LGEE->PJM
CLTF
0.352
WECLTFEXP_WEC->PJM
CLTF
0.176
TVALTFEXP_TVA->PJM
CLTF
0.925
CPLELTFEXP_CPLE->PJM
CLTF
2.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.194
MECLTFEXP_MEC->PJM
CLTF
0.929
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.76 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1287.59
MW Contribution:
2.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142366NRTHEST
50/50
0.482
3150691DARBY 3
50/50
10.157
3150701DARBY 4
50/50
10.134
3150681DARBY 2
50/50
10.122
3150671DARBY 1
50/50
10.11
944641AF1-129 GEN
50/50
66.397
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316313AB2-026
Solar/Wind Harmer
0.183
316336AC2-165 C
Solar/Wind Harmer
13.505
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.194
970301AG2-198 GEN
Solar/Wind Harmer
4.383
315976AC1-164 GENA
Solar/Wind Harmer
1.079
316169AC1-164_GENC
Solar/Wind Harmer
0.932
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.08
958211AF2-115 GEN
Solar/Wind Harmer
1.184
3144293JTRSVLE
Adder
0.236
3144356SAPONY
Solar/Wind Harmer
0.819
316315AB2-025 C
Solar/Wind Harmer
0.078
316349AD2-085 GEN
Solar/Wind Harmer
0.064
970323AG2-213 GEN
Solar/Wind Harmer
3.952
316156AD2-030 GEN
Solar/Wind Harmer
0.066
315835AF2-110_GEN
Solar/Wind Harmer
0.618
3150991CHESPKB
Adder
0.932
3150991CHESPKB
Adder
0.91
316365GEN2_N
Solar/Wind Harmer
0.197
315742AE1-103 GEN
Solar/Wind Harmer
1.313
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.14
316388AE2-253 GEN
Solar/Wind Harmer
0.273
3137176SLIGO L2192
Solar/Wind Harmer
0.348
3146456SLIGO L269
Solar/Wind Harmer
1.549
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.912
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.144
972185AH1-677 GEN
Adder
4.801
313506AB2-031 GEN
Solar/Wind Harmer
0.261
3146376EDENTON
Solar/Wind Harmer
0.378
3146376EDENTON
Solar/Wind Harmer
0.378
972187AH1-678 GEN
Adder
2.418
316294AC1-161 GEN
Solar/Wind Harmer
1.459
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
315614AA2-178 GEN
Solar/Wind Harmer
0.478
962571AG1-106 GEN
Solar/Wind Harmer
1.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
316065AD1-022 GEN
Solar/Wind Harmer
3.806
316140AB2-099
Solar/Wind Harmer
0.029
3145783HORNRTN
Solar/Wind Harmer
1.464
3145783HORNRTN
Solar/Wind Harmer
1.171
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.245
972189AH1-679 GEN
Adder
1.328
962561AG1-105 GEN
Solar/Wind Harmer
3.796
964791AG1-342 GEN
Solar/Wind Harmer
1.496
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
1.486
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
3150341NORNECKC1
Adder
0.794
3150341NORNECKC1
Adder
0.788
316005AA1-067
Solar/Wind Harmer
0.081
316118AC1-105 GEN
Solar/Wind Harmer
0.192
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
316049AB1-081 GEN
Solar/Wind Harmer
0.417
961601AG1-000A GEN
Solar/Wind Harmer
1.302
316263AC1-034 GEN
Solar/Wind Harmer
2.783
316045AC1-158 PL2
Solar/Wind Helper
2.725
316450AC1-158 RIC
Solar/Wind Helper
0.227
316303AF2-085
50/50
7.058
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.264
316233AE1-074 FULL
Solar/Wind Harmer
0.254
971281AH1-106 GEN
Solar/Wind Harmer
4.411
971283AH1-107 GEN
Solar/Wind Harmer
4.411
316258AE1-075 C
Solar/Wind Harmer
0.219
971845AH1-439 GEN
Solar/Wind Harmer
5.594
3143316POE
Solar/Wind Harmer
0.447
315697AD1-025 GEN
Solar/Wind Harmer
0.119
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
970657AG2-426 GEN
Solar/Wind Harmer
0.764
3151201GRAVEL4
Adder
7.309
3151221GRAVEL6
Adder
7.3
3151191GRAVEL3
Adder
7.216
3151211GRAVEL5
Adder
7.216
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.947
961791AG1-021 GEN
Solar/Wind Harmer
0.947
315814AE2-033 C
Solar/Wind Harmer
7.704
971445AH1-216 GEN
Solar/Wind Harmer
6.789
316311AC2-079 GEN
Solar/Wind Harmer
2.749
970683AG2-441 GEN
Solar/Wind Harmer
5.77
970681AG2-440 GEN
Solar/Wind Harmer
3.83
970189AG2-124 GEN
Solar/Wind Harmer
2.784
316159AE1-175 C
Solar/Wind Harmer
0.08
3144303KENBRDG
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
3151081ELIZAR1
Adder
8.141
3151091ELIZAR2
Adder
7.999
316316AC1-027 C
Solar/Wind Harmer
0.084
3141913WHIT STONE
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.364
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.046
970533AG2-339 GEN
Solar/Wind Harmer
6.573
3146396TANGLEW
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
970673AG2-436 GEN
Solar/Wind Harmer
10.754
971967AH1-528 GEN
Solar/Wind Harmer
13.826
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
3146043SEABORD
Solar/Wind Harmer
0.084
316486AD2-202 GEN
Solar/Wind Harmer
0.085
315652AC1-086 GEN
Solar/Wind Harmer
9.161
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.472
315733AD1-074 GEN2
Solar/Wind Harmer
0.472
316426AA2-053 GEN
Solar/Wind Harmer
0.277
316463AE2-346 GEN
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3146206CASHIE
Solar/Wind Harmer
0.082
970601AG2-382 GEN
Solar/Wind Harmer
3.081
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.5
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
970085AG2-068 GEN
Solar/Wind Harmer
4.336
970581AG2-369 GEN
Solar/Wind Harmer
3.729
3146033SCOT NK
Solar/Wind Harmer
0.319
316210AC1-098 GEN
Solar/Wind Harmer
0.729
316274AC1-208 GEN
Solar/Wind Harmer
0.406
316327AA2-057 GEN
Solar/Wind Harmer
0.113
3141813NORNECK
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
957861AF2-080 GEN
Solar/Wind Harmer
3.225
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.282
3143336POWHATN
Solar/Wind Harmer
4.437
972003AH1-546 GEN
Solar/Wind Harmer
4.733
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.605
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.303
3142946ENON
Solar/Wind Harmer
0.04
316458AB2-190 GEN2
Solar/Wind Harmer
0.622
315778AD1-151 GEN
Solar/Wind Harmer
9.046
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.916
316075AC2-137 C
Solar/Wind Harmer
0.029
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
0
961611AG1-000B GEN
Solar/Wind Harmer
2.783
970657AG2-426 GEN
Solar/Wind Harmer
2.335
270494AE1-108_GEN
Solar/Wind Harmer
1.228
3147133PAMPLIN
Solar/Wind Harmer
0.316
3151171GRAVELC
Adder
1.405
3144293JTRSVLE
Adder
0.236
3145336SMITFLD
Solar/Wind Harmer
0.038
3141843SHACKLE
Adder
0.48
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.314
970257AG2-171 GEN
Solar/Wind Harmer
2.964
971775AH1-396 GEN
Solar/Wind Harmer
0.148
3141766HARMONY
Solar/Wind Harmer
1.229
315821AE2-092 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
3141873WAN 176
Solar/Wind Harmer
1.61
3150921YORKTN3
Adder
2.264
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.245
3145273HOLLAND
Solar/Wind Harmer
0.066
316246AF1-032 C
Solar/Wind Harmer
0.039
964241AG1-285 GEN
Solar/Wind Harmer
5.876
316017AA1-139 ULT1
Solar/Wind Harmer
0.047
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.012
944581AF1-123 GEN
Solar/Wind Harmer
19.659
944601AF1-125 GEN
Solar/Wind Harmer
19.356
944011AF1-069 GEN
Solar/Wind Harmer
5.235
316321Z2-027
Solar/Wind Harmer
0.015
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
3156081AA2-088 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.121
3146376EDENTON
Solar/Wind Harmer
0.085
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
316478AD1-087 GEN
Solar/Wind Harmer
0.29
316011AB1-132 GEN
Solar/Wind Harmer
1.511
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
3146206CASHIE
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.308
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
3145823KELFORD
Solar/Wind Harmer
0.081
3145963POPLR C
Solar/Wind Harmer
0.08
316212AC1-099_GEN
Solar/Wind Harmer
0.407
315722AD1-056 GEN
Solar/Wind Harmer
2.665
3145933PARMELE
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.208
971623AH1-311 GEN
Solar/Wind Harmer
0.146
971683AH1-343 GEN
Solar/Wind Harmer
2.428
316222AC1-221 GEN
Solar/Wind Harmer
0.259
316283AC2-100 C
Solar/Wind Harmer
0.122
316223AC1-118
Solar/Wind Harmer
0.043
3141906WESTMOR
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.078
958131AF2-107 GEN
Solar/Wind Harmer
1.631
3147666LOUISA
Solar/Wind Helper
0.269
970119AG2-088 GEN
50/50
52.932
3150851SPRUNCC
50/50
1.044
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.656
3151911BEARGRDN G1
50/50
1.282
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.22
970937AG2-583 GEN
Solar/Wind Harmer
12.085
3142543TWELFTH
Solar/Wind Harmer
0.016
944631AF1-128 GEN
Adder
61.175
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.321
3147623JAMES R
Solar/Wind Harmer
0.287
316132AB2-190 GEN1
Solar/Wind Harmer
0.622
971069AG2-661 GEN
Solar/Wind Harmer
2.01
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
316381AD1-082 GEN
Solar/Wind Harmer
0.106
961611AG1-000B GEN
Solar/Wind Harmer
5.472
315975AC1-164 GENB
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
1.068
971563AH1-280 GEN
Solar/Wind Harmer
1.052
3144293JTRSVLE
Adder
0.236
3144293JTRSVLE
Adder
0.186
970685AG2-442 GEN
Solar/Wind Harmer
7.25
3145336SMITFLD
Solar/Wind Harmer
0.384
971777AH1-397 GEN
Solar/Wind Harmer
0.248
316034AC1-036 C
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
0.018
315785AD2-033 C
Solar/Wind Harmer
0.739
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.032
316093AE2-104_GEN
Solar/Wind Harmer
1.515
971317AH1-138 GEN
Solar/Wind Harmer
0.671
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.016
3150981CHESPKA
Adder
1.111
315693AD1-088 GEN
Solar/Wind Harmer
4.263
316023GEN1_S
Solar/Wind Harmer
0.197
940641AE2-051 GEN
Solar/Wind Harmer
7.05
939411AE1-173 GEN
Solar/Wind Harmer
37.549
3138133OCRAN
Solar/Wind Harmer
0.053
3146456SLIGO L269
Solar/Wind Harmer
0.088
319010AE1-072 C
Solar/Wind Harmer
0.437
944591AF1-124 GEN
Solar/Wind Harmer
19.729
960081AF2-299 GEN
Solar/Wind Harmer
0.837
941031AE2-094 GEN
Solar/Wind Harmer
16.022
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
316131AB2-060 GEN
Solar/Wind Harmer
0.268
957481AF2-042 GEN
Solar/Wind Harmer
22.86
3130156CHOWAN
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.083
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
315816AE2-034 GEN
Solar/Wind Harmer
0.358
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.715
315607AA1-063A GEN
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.083
315737AD1-076 GEN
Solar/Wind Harmer
1.063
3146206CASHIE
Solar/Wind Harmer
0.082
971547AH1-271 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.923
3145683EARLEYS
Solar/Wind Harmer
0.082
3156021HOLLOMANSOL
Solar/Wind Harmer
0.369
316129AC1-054 GEN
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.49
970087AG2-069 GEN
Solar/Wind Harmer
6.503
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.584
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.649
3145963POPLR C
Solar/Wind Harmer
0.08
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.756
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.297
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.329
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.26
3142053HEARTS
Solar/Wind Harmer
0.129
316337AD2-073 GEN
Solar/Wind Harmer
0.059
316447AC1-158 HLD
Solar/Wind Helper
1.874
316044AC1-158 PL1
Solar/Wind Helper
0.852
3147666LOUISA
Solar/Wind Helper
0.468
316192AB2-158 GEN
Solar/Wind Helper
0.767
LAGNLTFEXP_LAGN->PJM
CLTF
3.484
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.332
TVALTFEXP_TVA->PJM
CLTF
1.758
NYPJM->LTFIMP_NY
CLTF
1.089
LGEELTFEXP_LGEE->PJM
CLTF
0.647
WECLTFEXP_WEC->PJM
CLTF
0.325
CPLELTFEXP_CPLE->PJM
CLTF
4.7
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.048
MECLTFEXP_MEC->PJM
CLTF
1.732
SIGELTFEXP_SIGE->PJM
CLTF
0.053

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:590.65
MW Contribution:
4.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.846
316169AC1-164_GENC
Solar/Wind Harmer
0.731
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.103
316033AB2-134 GEN
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
2.961
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.152
3141726DUNNSVL
Solar/Wind Harmer
1.046
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.977
962861AG1-135 GEN
Solar/Wind Harmer
7.537
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.971
316337AD2-073 GEN
Solar/Wind Helper
2.352
315759AF1-018 GEN
50/50
4.962
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150631CHESTG8
50/50
0.397
970603AG2-384 GEN
50/50
1.356
972263AH1-716 GEN
50/50
33.131
3151201GRAVEL4
50/50
4.389
3150351NORNECKC2
50/50
3.011
966661AG1-536 GEN
50/50
6.862
315749AE2-041 GEN
50/50
4.962
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.941
3144216WINCHST
50/50
0.281
3150611CHESTG7
50/50
0.403
3151161SURRY 1
50/50
2.315
3141873WAN 176
Solar/Wind Harmer
2.618
3141766HARMONY
Solar/Wind Harmer
1.861
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
0.559
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.51
316223AC1-118
Solar/Wind Helper
2.155
3141906WESTMOR
Solar/Wind Helper
0.564
3151221GRAVEL6
50/50
4.384
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
315697AD1-025 GEN
Solar/Wind Harmer
0.061
3141426STAFORD
Solar/Wind Helper
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
1.553
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.493
NYPJM->LTFIMP_NY
CLTF
0.542
LGEELTFEXP_LGEE->PJM
CLTF
0.298
WECLTFEXP_WEC->PJM
CLTF
0.15
TVALTFEXP_TVA->PJM
CLTF
0.785
CPLELTFEXP_CPLE->PJM
CLTF
2.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.15 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:578.11
MW Contribution:
4.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.845
316169AC1-164_GENC
Solar/Wind Harmer
0.73
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
316033AB2-134 GEN
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
2.96
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.11
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.975
962861AG1-135 GEN
Solar/Wind Harmer
7.534
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3150351NORNECKC2
50/50
3.01
966661AG1-536 GEN
50/50
6.86
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.403
3151161SURRY 1
50/50
2.311
3141873WAN 176
Solar/Wind Harmer
2.617
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316223AC1-118
Solar/Wind Helper
2.155
3141906WESTMOR
Solar/Wind Helper
0.564
3142433PROV 92
50/50
0.222
3150631CHESTG8
50/50
0.397
970603AG2-384 GEN
50/50
1.354
972263AH1-716 GEN
50/50
33.083
3151201GRAVEL4
50/50
4.383
3151221GRAVEL6
50/50
4.378
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.091
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
315697AD1-025 GEN
Solar/Wind Harmer
0.06
3141426STAFORD
Solar/Wind Helper
0.031
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.966
LAGNLTFEXP_LAGN->PJM
CLTF
1.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.474
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
TVALTFEXP_TVA->PJM
CLTF
0.778
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.125
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.685
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.71 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1784.89
MW Contribution:
3.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.538
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.527
3150691DARBY 3
50/50
11.363
3150701DARBY 4
50/50
11.336
3150681DARBY 2
50/50
11.323
966871AG1-558 GEN
Solar/Wind Harmer
0.187
316312AB1-027
Solar/Wind Harmer
0.287
3150671DARBY 1
Adder
10.658
3142946ENON
Solar/Wind Harmer
0.013
315976AC1-164 GENA
Solar/Wind Harmer
1.324
316169AC1-164_GENC
Solar/Wind Harmer
1.144
944641AF1-129 GEN
Adder
59.793
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.073
316349AD2-085 GEN
Solar/Wind Harmer
0.064
971223AH1-071 GEN
Solar/Wind Harmer
1.025
3150991CHESPKB
Adder
0.984
3150991CHESPKB
Adder
0.96
316294AC1-161 GEN
Solar/Wind Harmer
1.601
315835AF2-110_GEN
Solar/Wind Harmer
0.635
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.147
316388AE2-253 GEN
Solar/Wind Harmer
0.287
3137176SLIGO L2192
Solar/Wind Harmer
0.365
3146456SLIGO L269
Solar/Wind Harmer
1.624
3130086AYDLETT
Solar/Wind Harmer
0.366
3146386ELIZ CT
Solar/Wind Harmer
0.091
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.733
316315AB2-025 C
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
0.384
3146376EDENTON
Solar/Wind Harmer
0.384
315614AA2-178 GEN
Solar/Wind Harmer
0.478
316065AD1-022 GEN
Solar/Wind Harmer
3.737
972193AH1-681 GEN
Adder
1.845
3145893MURPHYS
Solar/Wind Harmer
0.537
3145893MURPHYS
Solar/Wind Harmer
0.144
316365GEN2_N
Solar/Wind Harmer
0.177
316313AB2-026
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
316140AB2-099
Solar/Wind Harmer
0.028
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
962571AG1-106 GEN
Solar/Wind Harmer
1.081
313506AB2-031 GEN
Solar/Wind Harmer
0.232
316336AC2-165 C
Solar/Wind Harmer
3.814
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.318
3145783HORNRTN
Solar/Wind Harmer
1.054
3145783HORNRTN
Solar/Wind Harmer
0.329
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
3150341NORNECKC1
Adder
0.758
3150341NORNECKC1
Adder
0.752
316005AA1-067
Solar/Wind Harmer
0.076
972185AH1-677 GEN
Adder
3.982
972187AH1-678 GEN
Adder
2.003
315724AD1-057 GEN
Solar/Wind Harmer
1.35
970933AG2-581 GEN
Solar/Wind Harmer
5.563
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.18
316049AB1-081 GEN
Solar/Wind Harmer
0.377
316263AC1-034 GEN
Solar/Wind Harmer
2.518
970099AG2-077 GEN
Solar/Wind Harmer
7.064
970323AG2-213 GEN
Solar/Wind Harmer
2.669
970301AG2-198 GEN
Solar/Wind Harmer
2.654
958211AF2-115 GEN
Solar/Wind Harmer
0.741
3144293JTRSVLE
Adder
0.147
3147133PAMPLIN
Solar/Wind Harmer
0.061
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.9
964791AG1-342 GEN
Solar/Wind Harmer
1.149
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
316118AC1-105 GEN
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
0.019
971285AH1-108 GEN
Adder
0.965
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.56
971283AH1-107 GEN
Solar/Wind Harmer
1.56
315697AD1-025 GEN
Solar/Wind Harmer
0.12
316159AE1-175 C
Solar/Wind Harmer
0.095
3143873LANEXA
Solar/Wind Harmer
0.066
3143316POE
Solar/Wind Harmer
0.414
3151201GRAVEL4
Adder
7.611
3151221GRAVEL6
Adder
7.602
3151191GRAVEL3
Adder
7.514
3151211GRAVEL5
Adder
7.514
970189AG2-124 GEN
Solar/Wind Harmer
3.081
970657AG2-426 GEN
Solar/Wind Harmer
0.747
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.101
3141873WAN 176
Solar/Wind Harmer
0.02
316311AC2-079 GEN
Solar/Wind Harmer
2.764
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3151081ELIZAR1
Adder
8.593
3151091ELIZAR2
Adder
8.444
316316AC1-027 C
Solar/Wind Harmer
0.089
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
957871AF2-081 GEN
Solar/Wind Harmer
4.581
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.048
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
315814AE2-033 C
Solar/Wind Harmer
6.903
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.466
315733AD1-074 GEN2
Solar/Wind Harmer
0.466
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.015
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.08
316258AE1-075 C
Solar/Wind Harmer
0.059
316463AE2-346 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315652AC1-086 GEN
Solar/Wind Harmer
8.359
316426AA2-053 GEN
Solar/Wind Harmer
0.252
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.296
316210AC1-098 GEN
Solar/Wind Harmer
0.67
970533AG2-339 GEN
Solar/Wind Harmer
5.472
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
8.941
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
971967AH1-528 GEN
Solar/Wind Harmer
11.289
957861AF2-080 GEN
Solar/Wind Harmer
2.992
316327AA2-057 GEN
Solar/Wind Harmer
0.102
970831AG2-522 GEN
Solar/Wind Harmer
2.932
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
970085AG2-068 GEN
Solar/Wind Harmer
3.609
970581AG2-369 GEN
Solar/Wind Harmer
3.103
316486AD2-202 GEN
Solar/Wind Harmer
0.065
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
3.745
970681AG2-440 GEN
Solar/Wind Harmer
2.486
946301AF1-294 GEN
Solar/Wind Harmer
1.219
961791AG1-021 GEN
Solar/Wind Harmer
0.593
971845AH1-439 GEN
Solar/Wind Harmer
2.619
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.912
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.563
970293AG2-193 GEN
Solar/Wind Harmer
1.526
316075AC2-137 C
Solar/Wind Harmer
0.037
3143096IRON208
Adder
0.564
3143096IRON208
Adder
0.553
3150861SPRUNCD
Adder
0.589
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.163
316458AB2-190 GEN2
Solar/Wind Harmer
0.621
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.108
961611AG1-000B GEN
Solar/Wind Harmer
2.865
315813AE1-149 C
Solar/Wind Harmer
5.666
3151171GRAVELC
Adder
1.463
3141766HARMONY
Solar/Wind Harmer
1.387
3141843SHACKLE
Adder
0.531
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.591
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970657AG2-426 GEN
Solar/Wind Harmer
2.283
3145336SMITFLD
Solar/Wind Harmer
0.04
3141873WAN 176
Solar/Wind Harmer
1.779
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.703
944581AF1-123 GEN
Solar/Wind Harmer
20.822
944601AF1-125 GEN
Solar/Wind Harmer
20.501
316246AF1-032 C
Solar/Wind Harmer
0.041
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.061
316321Z2-027
Solar/Wind Harmer
0.016
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146376EDENTON
Solar/Wind Harmer
0.086
315735AD1-075 GEN1
Solar/Wind Harmer
0.233
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.288
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
3143336POWHATN
Solar/Wind Harmer
1.203
3146173TUNIS
Solar/Wind Harmer
0.079
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.378
316181AB2-040 GEN
Solar/Wind Harmer
0.108
3145796HORNRTN
Solar/Wind Harmer
0.298
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
316212AC1-099_GEN
Solar/Wind Harmer
0.374
944011AF1-069 GEN
Solar/Wind Harmer
4.358
3150351NORNECKC2
Adder
0.734
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.42
970917AG2-570 GEN
Solar/Wind Harmer
6.074
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.34
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.718
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.223
964241AG1-285 GEN
Solar/Wind Harmer
4.21
970257AG2-171 GEN
Solar/Wind Harmer
2.002
971775AH1-396 GEN
Solar/Wind Harmer
0.1
959311AF2-222 GEN
Solar/Wind Harmer
5.55
3144293JTRSVLE
Adder
0.147
3147133PAMPLIN
Solar/Wind Harmer
0.193
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
315052AA1-145 CT2
50/50
2.929
966881AG1-559 GEN
Solar/Wind Harmer
0.766
3142416OLDCHRC
Solar/Wind Harmer
0.419
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.564
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
60.987
3150851SPRUNCC
Adder
0.589
315975AC1-164 GENB
Solar/Wind Harmer
0.039
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.621
3142433PROV 92
Solar/Wind Harmer
0.46
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.024
3143526WINTERP
Solar/Wind Harmer
0.585
961611AG1-000B GEN
Solar/Wind Harmer
5.635
3151171GRAVELC
Adder
1.112
971317AH1-138 GEN
Solar/Wind Harmer
0.778
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3138126ROCKLANDING
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.104
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.017
3150981CHESPKA
Adder
1.172
315773AC2-141 GEN
Solar/Wind Harmer
3.383
316093AE2-104_GEN
Solar/Wind Harmer
1.556
944591AF1-124 GEN
Solar/Wind Harmer
20.896
3146456SLIGO L269
Solar/Wind Harmer
0.092
319010AE1-072 C
Solar/Wind Harmer
0.457
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.089
3130156CHOWAN
Solar/Wind Harmer
0.086
315816AE2-034 GEN
Solar/Wind Harmer
0.358
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.721
315737AD1-076 GEN
Solar/Wind Harmer
1.05
962861AG1-135 GEN
Solar/Wind Harmer
2.613
939411AE1-173 GEN
Solar/Wind Harmer
34.759
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.723
972277AH1-723 GEN
Adder
48.112
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.66
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
1.415
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.356
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.222
3146263WOODLND
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.155
3141726DUNNSVL
Solar/Wind Harmer
0.308
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.736
3145823KELFORD
Solar/Wind Harmer
0.076
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.657
941031AE2-094 GEN
Solar/Wind Harmer
13.339
3150351NORNECKC2
Adder
0.721
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.234
970919AG2-571 GEN
Solar/Wind Harmer
2.43
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.254
3146233WITAKRS
Solar/Wind Harmer
0.27
970087AG2-069 GEN
Solar/Wind Harmer
5.413
971065AG2-659 GEN
Solar/Wind Harmer
2.873
316359AB2-059 GEN
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.66
315693AD1-088 GEN
Solar/Wind Harmer
3.135
970937AG2-583 GEN
Solar/Wind Harmer
3.936
316131AB2-060 GEN
Solar/Wind Harmer
0.197
315785AD2-033 C
Solar/Wind Harmer
0.507
316034AC1-036 C
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
4.627
971563AH1-280 GEN
Solar/Wind Harmer
0.659
3144293JTRSVLE
Adder
0.147
3144293JTRSVLE
Adder
0.116
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.351
316337AD2-073 GEN
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Harmer
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
3.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.216
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
0.625
TVALTFEXP_TVA->PJM
CLTF
1.641
WECLTFEXP_WEC->PJM
CLTF
0.31
CPLELTFEXP_CPLE->PJM
CLTF
4.12
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.661
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.669
MECLTFEXP_MEC->PJM
CLTF
1.638
SIGELTFEXP_SIGE->PJM
CLTF
0.051

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1802.21
MW Contribution:
2.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150091POSSM6B
50/50
0.849
3150071POSSM 5
50/50
52.154
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
3150391LDYSMT3
Adder
12.635
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.15
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.037
3150671DARBY 1
Adder
6.03
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.434
971223AH1-071 GEN
Solar/Wind Harmer
0.889
944641AF1-129 GEN
Adder
39.347
316033AB2-134 GEN
Solar/Wind Harmer
0
316294AC1-161 GEN
Solar/Wind Harmer
1.396
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316349AD2-085 GEN
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3146456SLIGO L269
Solar/Wind Harmer
1.414
3130086AYDLETT
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
0.547
3146386ELIZ CT
Solar/Wind Harmer
0.079
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316065AD1-022 GEN
Solar/Wind Harmer
3.468
316365GEN2_N
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316140AB2-099
Solar/Wind Harmer
0.026
970099AG2-077 GEN
Solar/Wind Harmer
7.893
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.172
972193AH1-681 GEN
Adder
1.64
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
316005AA1-067
Solar/Wind Harmer
0.076
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145493TOT1
Solar/Wind Harmer
0.161
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
961601AG1-000A GEN
Solar/Wind Harmer
1.225
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316263AC1-034 GEN
Solar/Wind Harmer
2.619
964791AG1-342 GEN
Solar/Wind Harmer
1.319
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
942751AE2-291 GEN
Solar/Wind Harmer
3.269
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
970053AG2-049 GEN
50/50
2.019
3140676OCCOQUN
50/50
0.016
3138216PACIFIC
Solar/Wind Harmer
0.025
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.698
3150381LDYSMT2
Adder
12.153
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
315651AD1-115 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Harmer
0.129
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.087
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
970189AG2-124 GEN
Solar/Wind Harmer
2.502
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.071
315697AD1-025 GEN
Solar/Wind Harmer
0.088
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
316311AC2-079 GEN
Solar/Wind Harmer
2.299
957871AF2-081 GEN
Solar/Wind Harmer
3.983
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.042
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.059
3146396TANGLEW
Solar/Wind Harmer
0.218
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315814AE2-033 C
Solar/Wind Harmer
6.193
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
971967AH1-528 GEN
Solar/Wind Harmer
12.296
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.806
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
970581AG2-369 GEN
Solar/Wind Harmer
3.417
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
972205AH1-687 GEN
Adder
3.128
971845AH1-439 GEN
Solar/Wind Harmer
3.318
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316486AD2-202 GEN
Solar/Wind Harmer
0.074
3146033SCOT NK
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
1.421
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3144303KENBRDG
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.161
3150021OMF B
50/50
0.213
3150101POSSM6S
50/50
1.293
3150081POSSM6A
50/50
0.849
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
972217AH1-693 GEN
50/50
1.753
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3141196NOKESVL
Solar/Wind Harmer
0.428
3150301M RUN C
Adder
13.329
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
3150401LDYSMT4
Adder
12.659
3150371LDYSMT1
Adder
12.232
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
3150011OMF A
50/50
0.213
972223AH1-696 GEN
50/50
9.014
3150151POSSMC1
50/50
1.141
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
3150281M RUN A
Adder
13.337
971685AH1-345 GEN
Solar/Wind Harmer
0.729
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
972197AH1-683 GEN
Adder
1.977
972219AH1-694 GEN
Adder
1.423
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3150351NORNECKC2
Adder
0.868
3141726DUNNSVL
Solar/Wind Harmer
0.347
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.855
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.434
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.784
3143226MDLTHAN
Solar/Wind Harmer
0.083
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.324
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.014
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
3146456SLIGO L269
Solar/Wind Harmer
0.08
319010AE1-072 C
Solar/Wind Harmer
0.398
940641AE2-051 GEN
Solar/Wind Harmer
6.384
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3143336POWHATN
Solar/Wind Harmer
1.41
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
941031AE2-094 GEN
Solar/Wind Harmer
14.385
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
3145663CRESWEL
Solar/Wind Harmer
0.214
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.603
316023GEN1_S
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
970087AG2-069 GEN
Solar/Wind Harmer
5.959
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
19.733
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3145963POPLR C
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.663
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
971563AH1-280 GEN
Solar/Wind Harmer
0.768
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
5.367
972277AH1-723 GEN
Adder
42.768
3146293MARTNCO
Solar/Wind Harmer
0.066
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
0.762
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
315785AD2-033 C
Solar/Wind Harmer
0.577
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.237
3146233WITAKRS
Solar/Wind Harmer
0.277
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.309
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.121
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207484AF2-139 C O1
Solar/Wind Helper
0.048
207530AG1-191 GEN
Solar/Wind Helper
0.038
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
316223AC1-118
Solar/Wind Harmer
0.064
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.117
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3141873WAN 176
Solar/Wind Harmer
1.502
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.431
970293AG2-193 GEN
Solar/Wind Harmer
0.898
316075AC2-137 C
Solar/Wind Harmer
0.022
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
0.793
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
3144536CHRHLND
Solar/Wind Harmer
0.012
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3151101ELIZAR3
Adder
7.476
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944601AF1-125 GEN
Solar/Wind Harmer
17.837
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
316246AF1-032 C
Solar/Wind Harmer
0.036
3143336POWHATN
Solar/Wind Harmer
1.198
316321Z2-027
Solar/Wind Harmer
0.014
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3145273HOLLAND
Solar/Wind Harmer
0.059
944011AF1-069 GEN
Solar/Wind Harmer
4.7
3146376EDENTON
Solar/Wind Harmer
0.077
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3146206CASHIE
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3146173TUNIS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
972255AH1-712 GEN
Adder
36.701
3145933PARMELE
Solar/Wind Harmer
0.072
959311AF2-222 GEN
Solar/Wind Harmer
6.364
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
970221AG2-151 GEN
Solar/Wind Harmer
3.81
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
315821AE2-092 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
971623AH1-311 GEN
Solar/Wind Harmer
0.138
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3148013FISHERV
Solar/Wind Harmer
0.065
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
316123AC1-075 GEN
Solar/Wind Harmer
0.082
3151861LOWMORA
Adder
0.644
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958
CPLELTFEXP_CPLE->PJM
CLTF
5.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:575.03
MW Contribution:
4.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
3.108
3150341NORNECKC1
50/50
3.083
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.844
316169AC1-164_GENC
Solar/Wind Harmer
0.729
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
3.009
966661AG1-536 GEN
50/50
6.857
315749AE2-041 GEN
50/50
4.955
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.937
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.402
3151161SURRY 1
50/50
2.308
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.615
3141766HARMONY
Solar/Wind Harmer
1.858
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.671
3142416OLDCHRC
Solar/Wind Harmer
0.557
3151171GRAVELC
Adder
0.792
961611AG1-000B GEN
Solar/Wind Harmer
1.506
315759AF1-018 GEN
50/50
4.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.396
970603AG2-384 GEN
50/50
1.352
972263AH1-716 GEN
50/50
33.03
3151201GRAVEL4
50/50
4.375
3151221GRAVEL6
50/50
4.37
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.089
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.071
3151211GRAVEL5
Adder
4.071
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.959
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.063
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.972
962861AG1-135 GEN
Solar/Wind Harmer
7.531
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.429
971317AH1-138 GEN
Solar/Wind Harmer
0.615
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.603
961611AG1-000B GEN
Solar/Wind Harmer
2.961
LAGNLTFEXP_LAGN->PJM
CLTF
1.526
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.452
NYPJM->LTFIMP_NY
CLTF
0.551
LGEELTFEXP_LGEE->PJM
CLTF
0.289
WECLTFEXP_WEC->PJM
CLTF
0.145
TVALTFEXP_TVA->PJM
CLTF
0.771
CPLELTFEXP_CPLE->PJM
CLTF
2.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.658
MECLTFEXP_MEC->PJM
CLTF
0.768
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.62 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4109.92
MW Contribution:
4.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.019
963041AG1-153 GEN
50/50
9.188
315779AE2-040
50/50
3.991
3151541CLOVER2
50/50
5.868
3151081ELIZAR1
50/50
26.412
970533AG2-339 GEN
Solar/Wind Harmer
27.429
970673AG2-436 GEN
Solar/Wind Harmer
44.548
971967AH1-528 GEN
Solar/Wind Harmer
54.771
970085AG2-068 GEN
Solar/Wind Harmer
17.325
970581AG2-369 GEN
Solar/Wind Harmer
14.899
315814AE2-033 C
Solar/Wind Harmer
22.536
316486AD2-202 GEN
Solar/Wind Harmer
0.28
957871AF2-081 GEN
Solar/Wind Harmer
13.57
316316AC1-027 C
Solar/Wind Harmer
0.259
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.458
313526AB2-022
Solar/Wind Harmer
0.144
3146396TANGLEW
Solar/Wind Harmer
0.742
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.268
3146486SUNBURY
Solar/Wind Harmer
0.268
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.464
315733AD1-074 GEN2
Solar/Wind Harmer
1.464
3146206CASHIE
Solar/Wind Harmer
0.255
970601AG2-382 GEN
Solar/Wind Harmer
9.542
316311AC2-079 GEN
Solar/Wind Harmer
7.328
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.944
316463AE2-346 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.505
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.008
316426AA2-053 GEN
Solar/Wind Harmer
0.84
3145796HORNRTN
Solar/Wind Harmer
0.803
3145796HORNRTN
Solar/Wind Harmer
0.1
3146033SCOT NK
Solar/Wind Harmer
0.988
316210AC1-098 GEN
Solar/Wind Harmer
2.263
970831AG2-522 GEN
Solar/Wind Harmer
10.443
316274AC1-208 GEN
Solar/Wind Harmer
1.258
3143316POE
Solar/Wind Harmer
0.964
971445AH1-216 GEN
Solar/Wind Harmer
17.014
970657AG2-426 GEN
Solar/Wind Harmer
1.768
3145746EVERETS
Solar/Wind Harmer
0.954
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.354
957861AF2-080 GEN
Solar/Wind Harmer
10.253
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
3151201GRAVEL4
Adder
16.455
3151221GRAVEL6
Adder
16.436
3151191GRAVEL3
Adder
16.246
3151211GRAVEL5
Adder
16.246
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.139
315242AE2-183_GT2
50/50
5.77
315241AE2-183_GT1
50/50
5.754
972185AH1-677 GEN
50/50
20.856
3151041BRUNSWICKG3
50/50
4.538
972187AH1-678 GEN
50/50
10.413
970933AG2-581 GEN
Solar/Wind Harmer
26.391
970099AG2-077 GEN
Solar/Wind Harmer
31.101
3144356SAPONY
Solar/Wind Harmer
2.392
316315AB2-025 C
Solar/Wind Harmer
0.229
316294AC1-161 GEN
Solar/Wind Harmer
4.875
3145506HICKORY
Solar/Wind Harmer
1.093
3145506HICKORY
Solar/Wind Harmer
0.656
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.436
316388AE2-253 GEN
Solar/Wind Harmer
0.849
3137176SLIGO L2192
Solar/Wind Harmer
1.083
3146456SLIGO L269
Solar/Wind Harmer
4.816
3130086AYDLETT
Solar/Wind Harmer
1.087
3150991CHESPKB
Adder
2.834
3150991CHESPKB
Adder
2.766
3146386ELIZ CT
Solar/Wind Harmer
0.27
3146516WINFALL
Solar/Wind Harmer
0.267
3146516WINFALL
Solar/Wind Harmer
0.267
3146516WINFALL
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.266
3146626S HERTFORD
Solar/Wind Harmer
0.266
315835AF2-110_GEN
Solar/Wind Harmer
1.819
316365GEN2_N
Solar/Wind Harmer
0.588
3146376EDENTON
Solar/Wind Harmer
1.17
3146376EDENTON
Solar/Wind Harmer
1.17
315742AE1-103 GEN
Solar/Wind Harmer
3.899
315614AA2-178 GEN
Solar/Wind Harmer
1.479
316065AD1-022 GEN
Solar/Wind Harmer
11.791
316349AD2-085 GEN
Solar/Wind Harmer
0.17
3145893MURPHYS
Solar/Wind Harmer
1.705
3145893MURPHYS
Solar/Wind Harmer
0.458
313506AB2-031 GEN
Solar/Wind Harmer
0.779
962571AG1-106 GEN
Solar/Wind Harmer
3.614
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.152
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316140AB2-099
Solar/Wind Harmer
0.09
3145796HORNRTN
Solar/Wind Harmer
0.753
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.312
3145783HORNRTN
Solar/Wind Harmer
4.443
3145783HORNRTN
Solar/Wind Harmer
3.554
3145783HORNRTN
Solar/Wind Harmer
1.111
3145783HORNRTN
Solar/Wind Harmer
0.444
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
315724AD1-057 GEN
Solar/Wind Harmer
4.661
316005AA1-067
Solar/Wind Harmer
0.256
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.161
316049AB1-081 GEN
Solar/Wind Harmer
1.331
316263AC1-034 GEN
Solar/Wind Harmer
8.89
962561AG1-105 GEN
Solar/Wind Harmer
10.78
964791AG1-342 GEN
Solar/Wind Harmer
4.307
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
316118AC1-105 GEN
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
8.776
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
8.502
958211AF2-115 GEN
Solar/Wind Harmer
2.257
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
944641AF1-129 GEN
Adder
78
942751AE2-291 GEN
Solar/Wind Harmer
8.641
316156AD2-030 GEN
Solar/Wind Harmer
0.112
315976AC1-164 GENA
Solar/Wind Harmer
1.441
316169AC1-164_GENC
Solar/Wind Harmer
1.245
3142946ENON
Solar/Wind Harmer
0.013
316045AC1-158 PL2
Solar/Wind Helper
5.241
316450AC1-158 RIC
Solar/Wind Helper
0.437
315243AE2-183_GT3
50/50
5.77
3151051BRUNSWICKS1
50/50
9.422
3151021BRUNSWICKG1
50/50
4.538
971451AH1-221 GEN
50/50
13.782
3151531CLOVER1
50/50
5.913
941031AE2-094 GEN
Solar/Wind Harmer
66.863
940641AE2-051 GEN
Solar/Wind Harmer
28.97
939411AE1-173 GEN
Solar/Wind Harmer
145.166
970919AG2-571 GEN
Solar/Wind Harmer
11.729
970087AG2-069 GEN
Solar/Wind Harmer
25.987
957481AF2-042 GEN
Solar/Wind Harmer
77.752
315773AC2-141 GEN
Solar/Wind Harmer
10.299
944591AF1-124 GEN
Solar/Wind Harmer
62.771
3146456SLIGO L269
Solar/Wind Harmer
0.272
319010AE1-072 C
Solar/Wind Harmer
1.357
315693AD1-088 GEN
Solar/Wind Harmer
13.011
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.048
3150981CHESPKA
Adder
3.378
3146516WINFALL
Solar/Wind Harmer
0.866
3146516WINFALL
Solar/Wind Harmer
0.267
316093AE2-104_GEN
Solar/Wind Harmer
4.457
316023GEN1_S
Solar/Wind Harmer
0.588
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.109
3145663CRESWEL
Solar/Wind Harmer
0.727
971163AH1-040 GEN
Solar/Wind Harmer
20.797
316072AD1-144
Solar/Wind Harmer
0.092
960081AF2-299 GEN
Solar/Wind Harmer
2.467
315737AD1-076 GEN
Solar/Wind Harmer
3.296
3146206CASHIE
Solar/Wind Harmer
0.255
971547AH1-271 GEN
Solar/Wind Harmer
5.453
3145893MURPHYS
Solar/Wind Harmer
1.019
3145893MURPHYS
Solar/Wind Harmer
1.133
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.142
315607AA1-063A GEN
Solar/Wind Harmer
0.509
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
0.828
3145796HORNRTN
Solar/Wind Harmer
0.251
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Adder
2.24
316129AC1-054 GEN
Solar/Wind Harmer
0.911
971065AG2-659 GEN
Solar/Wind Harmer
10.381
3145336SMITFLD
Solar/Wind Harmer
0.972
3146293MARTNCO
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.242
316494AC1-189 GEN
Solar/Wind Harmer
0.803
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316359AB2-059 GEN
Solar/Wind Harmer
0.831
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
3151171GRAVELC
Adder
2.405
316131AB2-060 GEN
Solar/Wind Harmer
0.699
970401AG2-262 GEN
Solar/Wind Harmer
1.316
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.321
315785AD2-033 C
Solar/Wind Harmer
1.692
971317AH1-138 GEN
Solar/Wind Harmer
1.538
316034AC1-036 C
Solar/Wind Harmer
0.014
971069AG2-661 GEN
Solar/Wind Harmer
3.437
970685AG2-442 GEN
Solar/Wind Harmer
14.388
971563AH1-280 GEN
Solar/Wind Harmer
2.006
3144293JTRSVLE
Adder
0.449
3144293JTRSVLE
Adder
0.354
316132AB2-190 GEN1
Solar/Wind Harmer
0.982
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.394
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.556
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
315975AC1-164 GENB
Solar/Wind Harmer
0.043
970223AG2-152 GEN
Solar/Wind Harmer
9.533
944631AF1-128 GEN
Adder
62.313
962861AG1-135 GEN
Solar/Wind Harmer
4.016
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.09
3147123OTTER R
Solar/Wind Harmer
0.07
3141726DUNNSVL
Solar/Wind Harmer
0.457
316447AC1-158 HLD
Solar/Wind Helper
3.604
316044AC1-158 PL1
Solar/Wind Helper
1.638
3147666LOUISA
Solar/Wind Helper
1.004
316192AB2-158 GEN
Solar/Wind Helper
1.665
3144303KENBRDG
Solar/Wind Harmer
0.164
315697AD1-025 GEN
Solar/Wind Harmer
0.215
970683AG2-441 GEN
Solar/Wind Harmer
11.85
970681AG2-440 GEN
Solar/Wind Harmer
7.865
316159AE1-175 C
Solar/Wind Harmer
0.164
946301AF1-294 GEN
Solar/Wind Harmer
3.711
961791AG1-021 GEN
Solar/Wind Harmer
1.805
3138283WHITEMARSH
Solar/Wind Harmer
0.043
3141873WAN 176
Solar/Wind Harmer
0.031
970189AG2-124 GEN
Solar/Wind Harmer
4.425
3141913WHIT STONE
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
270197AD1-017 GEN1
Solar/Wind Harmer
0.762
316164AC1-076 GEN
Solar/Wind Helper
1.175
315651AD1-115 GEN
Solar/Wind Helper
0.756
3151031BRUNSWICKG2
50/50
4.538
970413AG2-270 GEN
50/50
25.751
3151101ELIZAR3
50/50
26.75
944011AF1-069 GEN
Solar/Wind Harmer
21.847
970917AG2-570 GEN
Solar/Wind Harmer
29.322
944581AF1-123 GEN
Solar/Wind Harmer
62.549
944601AF1-125 GEN
Solar/Wind Harmer
61.585
316478AD1-087 GEN
Solar/Wind Harmer
0.954
316017AA1-139 ULT1
Solar/Wind Harmer
0.145
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.146
3144873MCLAUGH
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.12
316321Z2-027
Solar/Wind Harmer
0.048
3146516WINFALL
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.266
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.255
3145893MURPHYS
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
0.255
316181AB2-040 GEN
Solar/Wind Harmer
0.361
316011AB1-132 GEN
Solar/Wind Harmer
4.608
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.004
3145796HORNRTN
Solar/Wind Harmer
0.251
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
1.262
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
315722AD1-056 GEN
Solar/Wind Harmer
8.356
970657AG2-426 GEN
Solar/Wind Harmer
5.404
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3146233WITAKRS
Solar/Wind Harmer
1.188
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.643
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.216
3151171GRAVELC
Adder
3.162
3144216WINCHST
Adder
0.829
964241AG1-285 GEN
Solar/Wind Harmer
14.59
3150921YORKTN3
Adder
5.493
961611AG1-000B GEN
Solar/Wind Harmer
5.756
316222AC1-221 GEN
Solar/Wind Harmer
0.859
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.582
971775AH1-396 GEN
Solar/Wind Harmer
0.329
959311AF2-222 GEN
Solar/Wind Harmer
18.053
971683AH1-343 GEN
Solar/Wind Harmer
7.331
315778AD1-151 GEN
Solar/Wind Harmer
15.468
3144293JTRSVLE
Adder
0.449
316458AB2-190 GEN2
Solar/Wind Harmer
0.982
3147133PAMPLIN
Solar/Wind Harmer
0.571
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970133AG2-095 GEN
Solar/Wind Harmer
1.608
942461AE2-259 GEN
Solar/Wind Harmer
0
3141873WAN 176
Solar/Wind Harmer
2.727
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.763
3141766HARMONY
Solar/Wind Harmer
1.981
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3142946ENON
Solar/Wind Harmer
0.044
316075AC2-137 C
Solar/Wind Harmer
0.032
3147666LOUISA
Solar/Wind Helper
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
11.236
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.656
TVALTFEXP_TVA->PJM
CLTF
5.63
NYPJM->LTFIMP_NY
CLTF
2.883
LGEELTFEXP_LGEE->PJM
CLTF
1.99
WECLTFEXP_WEC->PJM
CLTF
1.018
CPLELTFEXP_CPLE->PJM
CLTF
15.981
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.488
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.292
MECLTFEXP_MEC->PJM
CLTF
5.46
SIGELTFEXP_SIGE->PJM
CLTF
0.164

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.29 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3712.91
MW Contribution:
4.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.916
315241AE2-183_GT1
50/50
5.9
972185AH1-677 GEN
50/50
21.384
3151041BRUNSWICKG3
50/50
4.65
972187AH1-678 GEN
50/50
10.669
3150991CHESPKB
50/50
3.214
3150991CHESPKB
50/50
3.137
970933AG2-581 GEN
Solar/Wind Harmer
26.969
316294AC1-161 GEN
Solar/Wind Harmer
5.303
970099AG2-077 GEN
Solar/Wind Harmer
31.559
3145506HICKORY
Solar/Wind Harmer
1.169
3145506HICKORY
Solar/Wind Harmer
0.702
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.466
316388AE2-253 GEN
Solar/Wind Harmer
0.907
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.141
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.408
316315AB2-025 C
Solar/Wind Harmer
0.23
3146386ELIZ CT
Solar/Wind Harmer
0.287
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
315835AF2-110_GEN
Solar/Wind Harmer
1.922
3146376EDENTON
Solar/Wind Harmer
1.235
3146376EDENTON
Solar/Wind Harmer
1.235
315742AE1-103 GEN
Solar/Wind Harmer
4.084
315614AA2-178 GEN
Solar/Wind Harmer
1.553
316365GEN2_N
Solar/Wind Harmer
0.597
316065AD1-022 GEN
Solar/Wind Harmer
12.298
316349AD2-085 GEN
Solar/Wind Harmer
0.177
3145893MURPHYS
Solar/Wind Harmer
1.765
3145893MURPHYS
Solar/Wind Harmer
0.474
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316140AB2-099
Solar/Wind Harmer
0.093
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.156
962571AG1-106 GEN
Solar/Wind Harmer
3.683
313506AB2-031 GEN
Solar/Wind Harmer
0.792
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.319
3145796HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
4.533
3145783HORNRTN
Solar/Wind Harmer
3.627
3145783HORNRTN
Solar/Wind Harmer
1.133
3145783HORNRTN
Solar/Wind Harmer
0.453
3145933PARMELE
Solar/Wind Harmer
0.5
3145933PARMELE
Solar/Wind Harmer
0.25
316005AA1-067
Solar/Wind Harmer
0.262
315724AD1-057 GEN
Solar/Wind Harmer
4.739
3145493TOT1
Solar/Wind Harmer
0.558
3145453TOT5
Solar/Wind Harmer
0.335
3145603CNETO
Solar/Wind Harmer
0.223
961601AG1-000A GEN
Solar/Wind Harmer
4.223
316049AB1-081 GEN
Solar/Wind Harmer
1.351
316263AC1-034 GEN
Solar/Wind Harmer
9.023
962561AG1-105 GEN
Solar/Wind Harmer
10.753
964791AG1-342 GEN
Solar/Wind Harmer
4.295
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
316118AC1-105 GEN
Solar/Wind Harmer
0.571
970323AG2-213 GEN
Solar/Wind Harmer
8.673
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
8.338
958211AF2-115 GEN
Solar/Wind Harmer
2.206
3144293JTRSVLE
Adder
0.439
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.142
316156AD2-030 GEN
Solar/Wind Harmer
0.121
942751AE2-291 GEN
Solar/Wind Harmer
8.231
944641AF1-129 GEN
Adder
69.336
315976AC1-164 GENA
Solar/Wind Harmer
1.519
316169AC1-164_GENC
Solar/Wind Harmer
1.313
3142946ENON
Solar/Wind Harmer
0.013
3150341NORNECKC1
Adder
1.287
3150341NORNECKC1
Adder
1.277
316045AC1-158 PL2
Solar/Wind Helper
4.426
316450AC1-158 RIC
Solar/Wind Helper
0.369
3151031BRUNSWICKG2
50/50
4.65
3151101ELIZAR3
50/50
28.608
3151161SURRY 1
50/50
9.609
944011AF1-069 GEN
Solar/Wind Harmer
22.433
970917AG2-570 GEN
Solar/Wind Harmer
29.993
944581AF1-123 GEN
Solar/Wind Harmer
67.102
944601AF1-125 GEN
Solar/Wind Harmer
66.069
316017AA1-139 ULT1
Solar/Wind Harmer
0.155
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.359
3144873MCLAUGH
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.128
316321Z2-027
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.042
316478AD1-087 GEN
Solar/Wind Harmer
0.965
3146376EDENTON
Solar/Wind Harmer
0.278
3145273HOLLAND
Solar/Wind Harmer
0.207
315735AD1-075 GEN1
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
0.266
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.441
3145893MURPHYS
Solar/Wind Harmer
0.264
3146173TUNIS
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.26
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
316011AB1-132 GEN
Solar/Wind Harmer
4.696
3145963POPLR C
Solar/Wind Harmer
0.258
316181AB2-040 GEN
Solar/Wind Harmer
0.367
3145823KELFORD
Solar/Wind Harmer
0.257
3145336SMITFLD
Solar/Wind Harmer
0.103
3145796HORNRTN
Solar/Wind Harmer
1.023
3145796HORNRTN
Solar/Wind Harmer
0.256
316212AC1-099_GEN
Solar/Wind Harmer
1.291
3145933PARMELE
Solar/Wind Harmer
0.25
3147043LAWRENC
Solar/Wind Harmer
0.15
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
8.494
970657AG2-426 GEN
Solar/Wind Harmer
5.48
3146233WITAKRS
Solar/Wind Harmer
1.208
3146233WITAKRS
Solar/Wind Harmer
0.164
3146073TAR RVR
Solar/Wind Harmer
0.24
3146083TARBORO
Solar/Wind Harmer
0.24
3138543CONSLDL
Solar/Wind Harmer
0.158
3144216WINCHST
Adder
0.898
3150921YORKTN3
Adder
5.988
961601AG1-000A GEN
Solar/Wind Harmer
16.893
3145543BTLEBRO
Solar/Wind Harmer
0.237
3145543BTLEBRO
Solar/Wind Harmer
0.237
971623AH1-311 GEN
Solar/Wind Harmer
0.475
3151171GRAVELC
Adder
3.3
315813AE1-149 C
Solar/Wind Harmer
12.096
961611AG1-000B GEN
Solar/Wind Harmer
5.935
964241AG1-285 GEN
Solar/Wind Harmer
14.518
316222AC1-221 GEN
Solar/Wind Harmer
0.855
316283AC2-100 C
Solar/Wind Harmer
0.404
970257AG2-171 GEN
Solar/Wind Harmer
6.505
971775AH1-396 GEN
Solar/Wind Harmer
0.325
959311AF2-222 GEN
Solar/Wind Harmer
17.813
971683AH1-343 GEN
Solar/Wind Harmer
7.209
315778AD1-151 GEN
Solar/Wind Harmer
15.448
3144293JTRSVLE
Adder
0.439
316458AB2-190 GEN2
Solar/Wind Harmer
0.966
3147133PAMPLIN
Solar/Wind Harmer
0.556
316123AC1-075 GEN
Solar/Wind Harmer
0.221
3141873WAN 176
Solar/Wind Harmer
2.936
3141766HARMONY
Solar/Wind Harmer
2.128
970133AG2-095 GEN
Solar/Wind Harmer
1.529
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.812
942461AE2-259 GEN
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3146926FARMVIL
Solar/Wind Harmer
0.083
3142946ENON
Solar/Wind Harmer
0.043
3150351NORNECKC2
Adder
1.246
316075AC2-137 C
Solar/Wind Harmer
0.03
3147666LOUISA
Solar/Wind Helper
0.518
315244AE2-183_ST
50/50
10.273
963041AG1-153 GEN
50/50
9.414
3151081ELIZAR1
50/50
28.247
3151091ELIZAR2
50/50
27.756
941591AE2-156 GEN
50/50
25.751
315779AE2-040
50/50
4.018
970533AG2-339 GEN
Solar/Wind Harmer
28.166
970673AG2-436 GEN
Solar/Wind Harmer
45.718
971967AH1-528 GEN
Solar/Wind Harmer
56.081
970085AG2-068 GEN
Solar/Wind Harmer
17.71
970581AG2-369 GEN
Solar/Wind Harmer
15.231
957871AF2-081 GEN
Solar/Wind Harmer
14.495
316316AC1-027 C
Solar/Wind Harmer
0.277
3146406KITTY HAWK
Solar/Wind Harmer
0.036
313526AB2-022
Solar/Wind Harmer
0.153
315814AE2-033 C
Solar/Wind Harmer
22.696
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.285
3146486SUNBURY
Solar/Wind Harmer
0.285
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3130156CHOWAN
Solar/Wind Harmer
0.278
3130156CHOWAN
Solar/Wind Harmer
0.278
3130546PLYMOUTH
Solar/Wind Harmer
0.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.53
315733AD1-074 GEN2
Solar/Wind Harmer
1.53
3146206CASHIE
Solar/Wind Harmer
0.266
970601AG2-382 GEN
Solar/Wind Harmer
9.941
316311AC2-079 GEN
Solar/Wind Harmer
7.625
3145893MURPHYS
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
0.264
316463AE2-346 GEN
Solar/Wind Harmer
0.224
3145513AHOSKIE
Solar/Wind Harmer
0.548
3145513AHOSKIE
Solar/Wind Harmer
0.262
3145683EARLEYS
Solar/Wind Harmer
0.522
3145683EARLEYS
Solar/Wind Harmer
0.261
3145683EARLEYS
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
315652AC1-086 GEN
Solar/Wind Harmer
28.478
3137643SOCKMAN
Solar/Wind Harmer
1.027
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3145796HORNRTN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.102
971445AH1-216 GEN
Solar/Wind Harmer
17.925
3146033SCOT NK
Solar/Wind Harmer
1.014
316210AC1-098 GEN
Solar/Wind Harmer
2.315
316274AC1-208 GEN
Solar/Wind Harmer
1.284
970831AG2-522 GEN
Solar/Wind Harmer
10.574
3145746EVERETS
Solar/Wind Harmer
0.979
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
970657AG2-426 GEN
Solar/Wind Harmer
1.794
316327AA2-057 GEN
Solar/Wind Harmer
0.36
957861AF2-080 GEN
Solar/Wind Harmer
10.482
3145573BETHELC
Solar/Wind Harmer
0.24
3145573BETHELC
Solar/Wind Harmer
0.24
3143316POE
Solar/Wind Harmer
0.942
3151201GRAVEL4
Adder
17.17
3151221GRAVEL6
Adder
17.15
3151191GRAVEL3
Adder
16.952
3151211GRAVEL5
Adder
16.952
3147173SINAI
Solar/Wind Harmer
0.222
3147243WELCO
Solar/Wind Harmer
0.139
316159AE1-175 C
Solar/Wind Harmer
0.178
3138283WHITEMARSH
Solar/Wind Harmer
0.047
3144303KENBRDG
Solar/Wind Harmer
0.162
315697AD1-025 GEN
Solar/Wind Harmer
0.217
970683AG2-441 GEN
Solar/Wind Harmer
11.647
970681AG2-440 GEN
Solar/Wind Harmer
7.73
946301AF1-294 GEN
Solar/Wind Harmer
3.627
961791AG1-021 GEN
Solar/Wind Harmer
1.765
3141873WAN 176
Solar/Wind Harmer
0.033
970189AG2-124 GEN
Solar/Wind Harmer
4.711
3141913WHIT STONE
Solar/Wind Harmer
0.159
3138133OCRAN
Solar/Wind Harmer
0.047
3141783LANCAST
Solar/Wind Harmer
0.092
3141783LANCAST
Solar/Wind Harmer
0.061
3143873LANEXA
Solar/Wind Harmer
0.09
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3141813NORNECK
Solar/Wind Harmer
0.123
315243AE2-183_GT3
50/50
5.916
3151051BRUNSWICKS1
50/50
9.654
3151021BRUNSWICKG1
50/50
4.65
971451AH1-221 GEN
50/50
14.121
3150981CHESPKA
50/50
3.831
3152331SURRY 2
50/50
11.67
940641AE2-051 GEN
Solar/Wind Harmer
30.049
941031AE2-094 GEN
Solar/Wind Harmer
68.658
939411AE1-173 GEN
Solar/Wind Harmer
151.55
970919AG2-571 GEN
Solar/Wind Harmer
11.997
970087AG2-069 GEN
Solar/Wind Harmer
26.565
315773AC2-141 GEN
Solar/Wind Harmer
11.204
944591AF1-124 GEN
Solar/Wind Harmer
67.341
957481AF2-042 GEN
Solar/Wind Harmer
78.897
3146456SLIGO L269
Solar/Wind Harmer
0.29
319010AE1-072 C
Solar/Wind Harmer
1.448
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.919
3146516WINFALL
Solar/Wind Harmer
0.284
316093AE2-104_GEN
Solar/Wind Harmer
4.71
3130156CHOWAN
Solar/Wind Harmer
0.278
316072AD1-144
Solar/Wind Harmer
0.098
315693AD1-088 GEN
Solar/Wind Harmer
13.133
315816AE2-034 GEN
Solar/Wind Harmer
1.164
3145663CRESWEL
Solar/Wind Harmer
0.764
971163AH1-040 GEN
Solar/Wind Harmer
21.833
315737AD1-076 GEN
Solar/Wind Harmer
3.444
316023GEN1_S
Solar/Wind Harmer
0.597
3146206CASHIE
Solar/Wind Harmer
0.266
971547AH1-271 GEN
Solar/Wind Harmer
5.681
3145893MURPHYS
Solar/Wind Harmer
1.054
3145893MURPHYS
Solar/Wind Harmer
1.172
3156021HOLLOMANSOL
Solar/Wind Harmer
1.184
3146173TUNIS
Solar/Wind Harmer
0.262
3145683EARLEYS
Solar/Wind Harmer
0.261
960081AF2-299 GEN
Solar/Wind Harmer
2.5
3146263WOODLND
Solar/Wind Harmer
0.26
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3145963POPLR C
Solar/Wind Harmer
0.258
3145823KELFORD
Solar/Wind Harmer
0.257
3145336SMITFLD
Solar/Wind Harmer
1.025
3145796HORNRTN
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.256
3145783HORNRTN
Solar/Wind Harmer
0.255
3146293MARTNCO
Solar/Wind Harmer
0.232
3147043LAWRENC
Adder
2.26
316129AC1-054 GEN
Solar/Wind Harmer
0.921
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
971065AG2-659 GEN
Solar/Wind Harmer
10.491
316494AC1-189 GEN
Solar/Wind Harmer
0.821
316381AD1-082 GEN
Solar/Wind Harmer
0.245
3146233WITAKRS
Solar/Wind Harmer
0.957
961671AG1-007 GEN
Solar/Wind Harmer
0.037
3146083TARBORO
Solar/Wind Harmer
0.24
3145493TOT1
Solar/Wind Harmer
1.069
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3145543BTLEBRO
Solar/Wind Harmer
0.237
3145543BTLEBRO
Solar/Wind Harmer
0.19
316359AB2-059 GEN
Solar/Wind Harmer
0.844
3142053HEARTS
Solar/Wind Harmer
0.418
3151171GRAVELC
Adder
2.509
971317AH1-138 GEN
Solar/Wind Harmer
1.682
316131AB2-060 GEN
Solar/Wind Harmer
0.697
970401AG2-262 GEN
Solar/Wind Harmer
1.313
961611AG1-000B GEN
Solar/Wind Harmer
11.672
315785AD2-033 C
Solar/Wind Harmer
1.676
316034AC1-036 C
Solar/Wind Harmer
0.014
971069AG2-661 GEN
Solar/Wind Harmer
3.433
970685AG2-442 GEN
Solar/Wind Harmer
14.105
971563AH1-280 GEN
Solar/Wind Harmer
1.961
3144293JTRSVLE
Adder
0.439
3144293JTRSVLE
Adder
0.346
316132AB2-190 GEN1
Solar/Wind Harmer
0.966
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Harmer
0.032
971777AH1-397 GEN
Solar/Wind Harmer
0.419
3138133OCRAN
Solar/Wind Harmer
0.094
315975AC1-164 GENB
Solar/Wind Harmer
0.045
3142433PROV 92
Solar/Wind Harmer
0.555
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3146926FARMVIL
Solar/Wind Harmer
0.083
962861AG1-135 GEN
Solar/Wind Harmer
4.386
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.472
970223AG2-152 GEN
Solar/Wind Harmer
8.948
3141726DUNNSVL
Solar/Wind Harmer
0.501
3150351NORNECKC2
Adder
1.226
944631AF1-128 GEN
Adder
58.387
3143226MDLTHAN
Solar/Wind Helper
0.258
316447AC1-158 HLD
Solar/Wind Helper
3.044
316044AC1-158 PL1
Solar/Wind Helper
1.383
3147666LOUISA
Solar/Wind Helper
0.9
LAGNLTFEXP_LAGN->PJM
CLTF
10.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.774
NYPJM->LTFIMP_NY
CLTF
2.523
LGEELTFEXP_LGEE->PJM
CLTF
1.643
TVALTFEXP_TVA->PJM
CLTF
5.126
WECLTFEXP_WEC->PJM
CLTF
0.841
CPLELTFEXP_CPLE->PJM
CLTF
15.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.042
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.401
MECLTFEXP_MEC->PJM
CLTF
4.673
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.54 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4865.39
MW Contribution:
6.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.339
3150411LDYSMT5
50/50
37.33
3150381LDYSMT2
50/50
35.726
972213AH1-691 GEN
50/50
6.043
972215AH1-692 GEN
50/50
6.043
316233AE1-074 FULL
Solar/Wind Harmer
0.196
3150391LDYSMT3
50/50
37.144
972195AH1-682 GEN
50/50
4.881
972189AH1-679 GEN
50/50
4.546
3142296MT RD221
50/50
0.852
3142366NRTHEST
50/50
0.857
316045AC1-158 PL2
Solar/Wind Harmer
4.839
316450AC1-158 RIC
Solar/Wind Harmer
0.403
315673AE1-157 GEN
Solar/Wind Harmer
17.965
316312AB1-027
Solar/Wind Harmer
0.443
3150691DARBY 3
Adder
17.755
3150701DARBY 4
Adder
17.714
3150681DARBY 2
Adder
17.693
3150671DARBY 1
Adder
17.672
3143526WINTERP
Solar/Wind Harmer
1.272
971223AH1-071 GEN
Solar/Wind Harmer
2.602
966871AG1-558 GEN
Solar/Wind Harmer
0.281
315976AC1-164 GENA
Solar/Wind Harmer
2.554
316169AC1-164_GENC
Solar/Wind Harmer
2.207
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.524
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.056
3150991CHESPKB
Adder
2.434
3150991CHESPKB
Adder
2.375
3145506HICKORY
Solar/Wind Harmer
0.924
3145506HICKORY
Solar/Wind Harmer
0.554
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.368
316388AE2-253 GEN
Solar/Wind Harmer
0.716
316156AD2-030 GEN
Solar/Wind Harmer
0.168
316349AD2-085 GEN
Solar/Wind Harmer
0.153
3137176SLIGO L2192
Solar/Wind Harmer
0.913
3146456SLIGO L269
Solar/Wind Harmer
4.061
3130086AYDLETT
Solar/Wind Harmer
0.916
315835AF2-110_GEN
Solar/Wind Harmer
1.564
3146386ELIZ CT
Solar/Wind Harmer
0.227
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.222
3146626S HERTFORD
Solar/Wind Harmer
0.222
3144356SAPONY
Solar/Wind Harmer
1.859
316315AB2-025 C
Solar/Wind Harmer
0.178
315742AE1-103 GEN
Solar/Wind Harmer
3.271
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
972185AH1-677 GEN
Adder
12.144
972187AH1-678 GEN
Adder
6.093
315614AA2-178 GEN
Solar/Wind Harmer
1.212
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
970933AG2-581 GEN
Solar/Wind Harmer
16.86
316313AB2-026
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
9.539
316365GEN2_N
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
1.375
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.203
316140AB2-099
Solar/Wind Harmer
0.072
316336AC2-165 C
Solar/Wind Harmer
10.224
313506AB2-031 GEN
Solar/Wind Harmer
0.608
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.11
962571AG1-106 GEN
Solar/Wind Harmer
2.81
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.462
3145783HORNRTN
Solar/Wind Harmer
2.769
3145783HORNRTN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
0.583
3145933PARMELE
Solar/Wind Harmer
0.379
3145933PARMELE
Solar/Wind Harmer
0.19
316005AA1-067
Solar/Wind Harmer
0.198
315724AD1-057 GEN
Solar/Wind Harmer
3.558
970301AG2-198 GEN
Solar/Wind Harmer
7.839
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
970323AG2-213 GEN
Solar/Wind Harmer
7.624
958211AF2-115 GEN
Solar/Wind Harmer
2.135
3144293JTRSVLE
Adder
0.425
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.137
316049AB1-081 GEN
Solar/Wind Harmer
1.003
316263AC1-034 GEN
Solar/Wind Harmer
6.702
962561AG1-105 GEN
Solar/Wind Harmer
8.245
964791AG1-342 GEN
Solar/Wind Harmer
3.271
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.675
3146776BUCKING
Solar/Wind Harmer
0.055
316118AC1-105 GEN
Solar/Wind Harmer
0.427
972193AH1-681 GEN
Adder
3.766
942751AE2-291 GEN
Solar/Wind Harmer
6.895
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.017
316411AF1-147_GEN1
Solar/Wind Helper
0.811
971281AH1-106 GEN
Solar/Wind Harmer
3.394
971283AH1-107 GEN
Solar/Wind Harmer
3.394
971285AH1-108 GEN
Adder
1.842
316164AC1-076 GEN
Solar/Wind Harmer
0.334
316159AE1-175 C
Solar/Wind Harmer
0.204
315697AD1-025 GEN
Solar/Wind Harmer
0.255
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.117
3151221GRAVEL6
Adder
17.097
3151191GRAVEL3
Adder
16.9
3151211GRAVEL5
Adder
16.9
971445AH1-216 GEN
Solar/Wind Harmer
16.491
3143316POE
Solar/Wind Harmer
0.926
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3151081ELIZAR1
Adder
21.305
3151091ELIZAR2
Adder
20.935
970657AG2-426 GEN
Solar/Wind Harmer
1.704
316316AC1-027 C
Solar/Wind Harmer
0.221
970189AG2-124 GEN
Solar/Wind Harmer
6.859
957871AF2-081 GEN
Solar/Wind Harmer
11.449
3141873WAN 176
Solar/Wind Harmer
0.046
316311AC2-079 GEN
Solar/Wind Harmer
6.594
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.121
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
0.226
3138133OCRAN
Solar/Wind Harmer
0.068
3146396TANGLEW
Solar/Wind Harmer
0.623
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
970533AG2-339 GEN
Solar/Wind Harmer
16.767
315814AE2-033 C
Solar/Wind Harmer
17.519
970673AG2-436 GEN
Solar/Wind Harmer
27.344
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.357
3141813NORNECK
Solar/Wind Harmer
0.212
316258AE1-075 C
Solar/Wind Harmer
0.157
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.188
315733AD1-074 GEN2
Solar/Wind Harmer
1.188
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.704
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.205
970085AG2-068 GEN
Solar/Wind Harmer
10.883
970581AG2-369 GEN
Solar/Wind Harmer
9.359
316463AE2-346 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.423
3145513AHOSKIE
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
3146043SEABORD
Solar/Wind Harmer
0.201
315652AC1-086 GEN
Solar/Wind Harmer
21.728
3137643SOCKMAN
Solar/Wind Harmer
0.787
316426AA2-053 GEN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.622
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.773
316486AD2-202 GEN
Solar/Wind Harmer
0.194
316210AC1-098 GEN
Solar/Wind Harmer
1.756
316274AC1-208 GEN
Solar/Wind Harmer
0.972
970831AG2-522 GEN
Solar/Wind Harmer
7.993
3145746EVERETS
Solar/Wind Harmer
0.739
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
316327AA2-057 GEN
Solar/Wind Harmer
0.27
957861AF2-080 GEN
Solar/Wind Harmer
7.87
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
10.744
970681AG2-440 GEN
Solar/Wind Harmer
7.131
946301AF1-294 GEN
Solar/Wind Harmer
3.51
961791AG1-021 GEN
Solar/Wind Harmer
1.708
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.683
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.848
3147346CASHSCORNER
Solar/Wind Harmer
0.277
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.393
3150401LDYSMT4
50/50
37.213
3150371LDYSMT1
50/50
35.958
315051AA1-145 CT1
50/50
2.024
3142416OLDCHRC
Solar/Wind Harmer
2.412
970293AG2-193 GEN
Solar/Wind Harmer
2.622
316075AC2-137 C
Solar/Wind Harmer
0.065
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.003
3150861SPRUNCD
Adder
1.126
316473AC1-191 GEN
Solar/Wind Harmer
0.821
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.301
316458AB2-190 GEN2
Solar/Wind Harmer
1.272
315778AD1-151 GEN
Solar/Wind Harmer
19.016
3150921YORKTN3
Adder
5.932
3144216WINCHST
Adder
0.89
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.292
3151171GRAVELC
Adder
3.289
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.487
3144536CHRHLND
Solar/Wind Harmer
0.035
944581AF1-123 GEN
Solar/Wind Harmer
52.325
944601AF1-125 GEN
Solar/Wind Harmer
51.52
3151101ELIZAR3
Adder
21.578
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.208
3141766HARMONY
Solar/Wind Harmer
3.088
3141843SHACKLE
Adder
1.183
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3141873WAN 176
Solar/Wind Harmer
4.085
3146456SLIGO L269
Solar/Wind Harmer
0.229
971153AH1-033 GEN
Solar/Wind Harmer
2.653
316246AF1-032 C
Solar/Wind Harmer
0.102
316321Z2-027
Solar/Wind Harmer
0.04
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.222
3145273HOLLAND
Solar/Wind Harmer
0.166
944011AF1-069 GEN
Solar/Wind Harmer
13.354
3146376EDENTON
Solar/Wind Harmer
0.218
3150351NORNECKC2
Adder
2.146
971781AH1-399 GEN
Solar/Wind Harmer
0.278
3143336POWHATN
Solar/Wind Harmer
3.181
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.362
3146206CASHIE
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.205
3146173TUNIS
Solar/Wind Harmer
0.203
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316011AB1-132 GEN
Solar/Wind Harmer
3.583
3145823KELFORD
Solar/Wind Harmer
0.197
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.194
3147043LAWRENC
Solar/Wind Harmer
0.117
316223AC1-118
Solar/Wind Harmer
0.137
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.661
316212AC1-099_GEN
Solar/Wind Harmer
0.98
3145933PARMELE
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
6.378
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.902
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.954
970257AG2-171 GEN
Solar/Wind Harmer
5.718
971775AH1-396 GEN
Solar/Wind Harmer
0.286
959311AF2-222 GEN
Solar/Wind Harmer
15.874
3144293JTRSVLE
Adder
0.425
3147133PAMPLIN
Solar/Wind Harmer
0.557
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
12.548
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.292
972003AH1-546 GEN
Solar/Wind Harmer
5.592
970221AG2-151 GEN
Solar/Wind Harmer
8.049
971683AH1-343 GEN
Solar/Wind Harmer
5.518
316222AC1-221 GEN
Solar/Wind Harmer
0.612
316283AC2-100 C
Solar/Wind Harmer
0.289
3132273ORANGE
Solar/Wind Harmer
0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.179
270494AE1-108_GEN
Solar/Wind Harmer
1.598
315821AE2-092 GEN
Solar/Wind Harmer
0
3150331BIRCHWDA
Adder
21.248
3151761LOISA E
Adder
16.344
3151721LOISA A
Adder
7.975
3141196NOKESVL
Solar/Wind Helper
1.254
971507AH1-251 GEN
50/50
17.357
3152251N ANNA1
50/50
14.386
972197AH1-683 GEN
50/50
5.811
972219AH1-694 GEN
50/50
4.184
315052AA1-145 CT2
50/50
2.037
316447AC1-158 HLD
Solar/Wind Harmer
3.325
316044AC1-158 PL1
Solar/Wind Harmer
1.512
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.647
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.272
3143096IRON208
Adder
1.024
3150851SPRUNCC
Adder
1.126
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
315975AC1-164 GENB
Solar/Wind Harmer
0.076
944631AF1-128 GEN
Adder
115.543
316132AB2-190 GEN1
Solar/Wind Harmer
1.272
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.226
971317AH1-138 GEN
Solar/Wind Harmer
1.763
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.943
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.373
315773AC2-141 GEN
Solar/Wind Harmer
8.57
3151171GRAVELC
Adder
2.502
3145336SMITFLD
Solar/Wind Harmer
0.936
944591AF1-124 GEN
Solar/Wind Harmer
52.511
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.901
316381AD1-082 GEN
Solar/Wind Harmer
0.236
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.611
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
98.409
940641AE2-051 GEN
Solar/Wind Harmer
18.429
3146456SLIGO L269
Solar/Wind Harmer
0.229
319010AE1-072 C
Solar/Wind Harmer
1.144
316093AE2-104_GEN
Solar/Wind Harmer
3.834
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.726
3146516WINFALL
Solar/Wind Harmer
0.224
941031AE2-094 GEN
Solar/Wind Harmer
40.872
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.968
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.175
3141726DUNNSVL
Solar/Wind Harmer
0.858
315816AE2-034 GEN
Solar/Wind Harmer
0.909
3145663CRESWEL
Solar/Wind Harmer
0.596
971163AH1-040 GEN
Solar/Wind Harmer
17.043
3150351NORNECKC2
Adder
2.111
3143336POWHATN
Solar/Wind Harmer
3.743
315737AD1-076 GEN
Solar/Wind Harmer
2.675
970919AG2-571 GEN
Solar/Wind Harmer
7.345
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.402
316023GEN1_S
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.913
970087AG2-069 GEN
Solar/Wind Harmer
16.324
3146173TUNIS
Solar/Wind Harmer
0.203
3156021HOLLOMANSOL
Solar/Wind Harmer
0.914
316337AD2-073 GEN
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.201
3147666LOUISA
Solar/Wind Harmer
0.803
960081AF2-299 GEN
Solar/Wind Harmer
1.925
315607AA1-063A GEN
Solar/Wind Harmer
0.403
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
957481AF2-042 GEN
Solar/Wind Harmer
52.774
3145823KELFORD
Solar/Wind Harmer
0.197
316192AB2-158 GEN
Solar/Wind Harmer
1.103
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.641
3145796HORNRTN
Solar/Wind Harmer
0.194
315693AD1-088 GEN
Solar/Wind Harmer
9.325
3147043LAWRENC
Adder
1.757
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.695
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.908
316494AC1-189 GEN
Solar/Wind Harmer
0.617
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.799
3146233WITAKRS
Solar/Wind Harmer
0.715
316131AB2-060 GEN
Solar/Wind Harmer
0.559
970937AG2-583 GEN
Solar/Wind Harmer
10.998
315785AD2-033 C
Solar/Wind Harmer
1.446
316034AC1-036 C
Solar/Wind Harmer
0.012
970685AG2-442 GEN
Solar/Wind Harmer
13.298
972135AH1-637 GEN
Solar/Wind Harmer
1.52
971563AH1-280 GEN
Solar/Wind Harmer
1.897
3144293JTRSVLE
Adder
0.425
3144293JTRSVLE
Adder
0.335
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.627
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
0.999
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.225
971377AH1-170 GEN
Solar/Wind Harmer
1.61
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.017
316254AC1-120 GEN1
Solar/Wind Harmer
4.309
316170AC1-121 GEN2
Solar/Wind Harmer
1.48
316415AF1-147_GEN2
Solar/Wind Helper
0.811
LAGNLTFEXP_LAGN->PJM
CLTF
7.995
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.949
NYPJM->LTFIMP_NY
CLTF
3.271
LGEELTFEXP_LGEE->PJM
CLTF
1.325
TVALTFEXP_TVA->PJM
CLTF
4.055
WECLTFEXP_WEC->PJM
CLTF
0.638
CPLELTFEXP_CPLE->PJM
CLTF
11.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.788
MECLTFEXP_MEC->PJM
CLTF
3.599
SIGELTFEXP_SIGE->PJM
CLTF
0.11

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4600.84
MW Contribution:
6.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
36.76
972195AH1-682 GEN
50/50
4.831
972189AH1-679 GEN
50/50
4.491
3142296MT RD221
50/50
0.841
3142366NRTHEST
50/50
0.846
315673AE1-157 GEN
Solar/Wind Harmer
17.771
316312AB1-027
Solar/Wind Harmer
0.437
3150691DARBY 3
Adder
17.527
3150701DARBY 4
Adder
17.486
3150681DARBY 2
Adder
17.466
3150671DARBY 1
Adder
17.445
3143526WINTERP
Solar/Wind Harmer
1.254
971223AH1-071 GEN
Solar/Wind Harmer
2.564
966871AG1-558 GEN
Solar/Wind Harmer
0.277
315976AC1-164 GENA
Solar/Wind Harmer
2.522
316169AC1-164_GENC
Solar/Wind Harmer
2.179
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.017
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.003
3150991CHESPKB
Adder
2.401
3150991CHESPKB
Adder
2.344
3145506HICKORY
Solar/Wind Harmer
0.911
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.363
316388AE2-253 GEN
Solar/Wind Harmer
0.707
316156AD2-030 GEN
Solar/Wind Harmer
0.166
316349AD2-085 GEN
Solar/Wind Harmer
0.151
3137176SLIGO L2192
Solar/Wind Harmer
0.901
3146456SLIGO L269
Solar/Wind Harmer
4.007
3130086AYDLETT
Solar/Wind Harmer
0.904
315835AF2-110_GEN
Solar/Wind Harmer
1.544
3146386ELIZ CT
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.219
3144356SAPONY
Solar/Wind Harmer
1.834
316315AB2-025 C
Solar/Wind Harmer
0.175
315742AE1-103 GEN
Solar/Wind Harmer
3.228
3146376EDENTON
Solar/Wind Harmer
0.956
3146376EDENTON
Solar/Wind Harmer
0.956
972185AH1-677 GEN
Adder
11.976
972187AH1-678 GEN
Adder
6.009
315614AA2-178 GEN
Solar/Wind Harmer
1.196
3150341NORNECKC1
Adder
2.191
3150341NORNECKC1
Adder
2.173
970933AG2-581 GEN
Solar/Wind Harmer
16.621
316313AB2-026
Solar/Wind Harmer
0.129
316065AD1-022 GEN
Solar/Wind Harmer
9.412
316365GEN2_N
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
1.356
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316140AB2-099
Solar/Wind Harmer
0.071
316336AC2-165 C
Solar/Wind Harmer
10.02
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.798
962571AG1-106 GEN
Solar/Wind Harmer
2.772
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.414
3145783HORNRTN
Solar/Wind Harmer
2.731
3145783HORNRTN
Solar/Wind Harmer
0.854
3145783HORNRTN
Solar/Wind Harmer
0.341
3145796HORNRTN
Solar/Wind Harmer
0.575
3145933PARMELE
Solar/Wind Harmer
0.374
3145933PARMELE
Solar/Wind Harmer
0.187
316005AA1-067
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
3.51
970301AG2-198 GEN
Solar/Wind Harmer
7.694
3145493TOT1
Solar/Wind Harmer
0.411
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.164
970323AG2-213 GEN
Solar/Wind Harmer
7.495
958211AF2-115 GEN
Solar/Wind Harmer
2.096
3144293JTRSVLE
Adder
0.417
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.095
316049AB1-081 GEN
Solar/Wind Harmer
0.99
316263AC1-034 GEN
Solar/Wind Harmer
6.613
962561AG1-105 GEN
Solar/Wind Harmer
8.121
964791AG1-342 GEN
Solar/Wind Harmer
3.222
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.659
3146776BUCKING
Solar/Wind Harmer
0.053
316118AC1-105 GEN
Solar/Wind Harmer
0.421
972193AH1-681 GEN
Adder
3.711
942751AE2-291 GEN
Solar/Wind Harmer
6.798
316045AC1-158 PL2
Solar/Wind Helper
6.076
316450AC1-158 RIC
Solar/Wind Helper
0.506
316411AF1-147_GEN1
Solar/Wind Helper
0.788
316006AB2-029 C
Solar/Wind Helper
0.111
3152261N ANNA2
50/50
14.183
3150401LDYSMT4
50/50
36.829
3150371LDYSMT1
50/50
35.587
315051AA1-145 CT1
50/50
2
3142416OLDCHRC
Solar/Wind Harmer
2.382
970293AG2-193 GEN
Solar/Wind Harmer
2.588
316075AC2-137 C
Solar/Wind Harmer
0.064
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.99
3150861SPRUNCD
Adder
1.11
316473AC1-191 GEN
Solar/Wind Harmer
0.811
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.271
316458AB2-190 GEN2
Solar/Wind Harmer
1.255
315778AD1-151 GEN
Solar/Wind Harmer
18.767
3150921YORKTN3
Adder
5.855
3144216WINCHST
Adder
0.878
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.209
3151171GRAVELC
Adder
3.246
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.322
3144536CHRHLND
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
51.631
944601AF1-125 GEN
Solar/Wind Harmer
50.836
3151101ELIZAR3
Adder
21.292
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.139
3141766HARMONY
Solar/Wind Harmer
3.05
3141843SHACKLE
Adder
1.168
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.121
3141873WAN 176
Solar/Wind Harmer
4.033
971531AH1-263 GEN
50/50
73.133
3150411LDYSMT5
50/50
36.944
3150381LDYSMT2
50/50
35.357
972213AH1-691 GEN
50/50
5.981
972215AH1-692 GEN
50/50
5.981
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.346
971283AH1-107 GEN
Solar/Wind Harmer
3.346
971285AH1-108 GEN
Adder
1.817
316159AE1-175 C
Solar/Wind Harmer
0.201
315697AD1-025 GEN
Solar/Wind Harmer
0.252
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3151201GRAVEL4
Adder
16.892
3151221GRAVEL6
Adder
16.873
3151191GRAVEL3
Adder
16.678
3151211GRAVEL5
Adder
16.678
971445AH1-216 GEN
Solar/Wind Harmer
16.274
3143316POE
Solar/Wind Harmer
0.914
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3151081ELIZAR1
Adder
21.023
3151091ELIZAR2
Adder
20.658
970657AG2-426 GEN
Solar/Wind Harmer
1.682
316316AC1-027 C
Solar/Wind Harmer
0.218
970189AG2-124 GEN
Solar/Wind Harmer
6.773
957871AF2-081 GEN
Solar/Wind Harmer
11.297
3141873WAN 176
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
6.506
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.12
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.223
3146486SUNBURY
Solar/Wind Harmer
0.223
3146396TANGLEW
Solar/Wind Harmer
0.615
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
970533AG2-339 GEN
Solar/Wind Harmer
16.536
315814AE2-033 C
Solar/Wind Harmer
17.282
970673AG2-436 GEN
Solar/Wind Harmer
26.967
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
33.875
3141813NORNECK
Solar/Wind Harmer
0.209
316258AE1-075 C
Solar/Wind Harmer
0.154
3130546PLYMOUTH
Solar/Wind Harmer
0.206
315732AD1-074 GEN1
Solar/Wind Harmer
1.172
315733AD1-074 GEN2
Solar/Wind Harmer
1.172
3146206CASHIE
Solar/Wind Harmer
0.203
970601AG2-382 GEN
Solar/Wind Harmer
7.602
3145893MURPHYS
Solar/Wind Harmer
0.547
3145893MURPHYS
Solar/Wind Harmer
0.203
970085AG2-068 GEN
Solar/Wind Harmer
10.733
970581AG2-369 GEN
Solar/Wind Harmer
9.231
316463AE2-346 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315652AC1-086 GEN
Solar/Wind Harmer
21.435
3137643SOCKMAN
Solar/Wind Harmer
0.776
316426AA2-053 GEN
Solar/Wind Harmer
0.649
3145796HORNRTN
Solar/Wind Harmer
0.614
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.763
316486AD2-202 GEN
Solar/Wind Harmer
0.191
316210AC1-098 GEN
Solar/Wind Harmer
1.733
316274AC1-208 GEN
Solar/Wind Harmer
0.959
970831AG2-522 GEN
Solar/Wind Harmer
7.879
3145746EVERETS
Solar/Wind Harmer
0.729
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
316327AA2-057 GEN
Solar/Wind Harmer
0.267
957861AF2-080 GEN
Solar/Wind Harmer
7.766
3145573BETHELC
Solar/Wind Harmer
0.177
3145573BETHELC
Solar/Wind Harmer
0.177
3144303KENBRDG
Solar/Wind Harmer
0.14
970683AG2-441 GEN
Solar/Wind Harmer
10.555
970681AG2-440 GEN
Solar/Wind Harmer
7.006
946301AF1-294 GEN
Solar/Wind Harmer
3.446
961791AG1-021 GEN
Solar/Wind Harmer
1.677
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.501
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.658
3138216PACIFIC
Solar/Wind Helper
0.038
3152251N ANNA1
50/50
14.176
972197AH1-683 GEN
50/50
5.751
972219AH1-694 GEN
50/50
4.141
315052AA1-145 CT2
50/50
2.012
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.254
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.11
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
315975AC1-164 GENB
Solar/Wind Harmer
0.075
944631AF1-128 GEN
Adder
114.046
316132AB2-190 GEN1
Solar/Wind Harmer
1.255
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.17
971317AH1-138 GEN
Solar/Wind Harmer
1.74
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.931
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.211
315773AC2-141 GEN
Solar/Wind Harmer
8.457
3151171GRAVELC
Adder
2.469
3145336SMITFLD
Solar/Wind Harmer
0.924
944591AF1-124 GEN
Solar/Wind Harmer
51.815
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.863
316381AD1-082 GEN
Solar/Wind Harmer
0.232
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.603
316072AD1-144
Solar/Wind Harmer
0.081
939411AE1-173 GEN
Solar/Wind Harmer
97.075
940641AE2-051 GEN
Solar/Wind Harmer
18.178
3146456SLIGO L269
Solar/Wind Harmer
0.226
319010AE1-072 C
Solar/Wind Harmer
1.128
316093AE2-104_GEN
Solar/Wind Harmer
3.783
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.716
3146516WINFALL
Solar/Wind Harmer
0.221
941031AE2-094 GEN
Solar/Wind Harmer
40.308
962861AG1-135 GEN
Solar/Wind Harmer
6.884
3130156CHOWAN
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.088
3141726DUNNSVL
Solar/Wind Harmer
0.847
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3145663CRESWEL
Solar/Wind Harmer
0.588
971163AH1-040 GEN
Solar/Wind Harmer
16.816
3150351NORNECKC2
Adder
2.086
3143336POWHATN
Solar/Wind Harmer
3.673
315737AD1-076 GEN
Solar/Wind Harmer
2.64
970919AG2-571 GEN
Solar/Wind Harmer
7.244
3146206CASHIE
Solar/Wind Harmer
0.203
971547AH1-271 GEN
Solar/Wind Harmer
4.344
316023GEN1_S
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
0.901
970087AG2-069 GEN
Solar/Wind Harmer
16.1
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.902
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145683EARLEYS
Solar/Wind Harmer
0.199
960081AF2-299 GEN
Solar/Wind Harmer
1.899
315607AA1-063A GEN
Solar/Wind Harmer
0.397
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
51.995
3145823KELFORD
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.633
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.732
315693AD1-088 GEN
Solar/Wind Harmer
9.181
3147666LOUISA
Solar/Wind Harmer
0.756
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.035
316129AC1-054 GEN
Solar/Wind Harmer
0.685
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.794
316494AC1-189 GEN
Solar/Wind Harmer
0.608
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.177
3145493TOT1
Solar/Wind Harmer
0.789
3146233WITAKRS
Solar/Wind Harmer
0.706
316131AB2-060 GEN
Solar/Wind Harmer
0.55
972135AH1-637 GEN
Solar/Wind Harmer
1.504
315785AD2-033 C
Solar/Wind Harmer
1.422
316034AC1-036 C
Solar/Wind Harmer
0.012
970937AG2-583 GEN
Solar/Wind Harmer
10.738
970685AG2-442 GEN
Solar/Wind Harmer
13.06
971563AH1-280 GEN
Solar/Wind Harmer
1.863
3144293JTRSVLE
Adder
0.417
3144293JTRSVLE
Adder
0.329
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.618
3142053HEARTS
Solar/Wind Harmer
0.306
3146926FARMVIL
Solar/Wind Harmer
0.103
970401AG2-262 GEN
Solar/Wind Harmer
0.984
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.787
971377AH1-170 GEN
Solar/Wind Harmer
1.565
3147623JAMES R
Solar/Wind Harmer
0.34
316447AC1-158 HLD
Solar/Wind Helper
4.178
316044AC1-158 PL1
Solar/Wind Helper
1.899
316415AF1-147_GEN2
Solar/Wind Helper
0.788
3146456SLIGO L269
Solar/Wind Harmer
0.226
971153AH1-033 GEN
Solar/Wind Harmer
2.618
316246AF1-032 C
Solar/Wind Harmer
0.101
316321Z2-027
Solar/Wind Harmer
0.04
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.219
3145273HOLLAND
Solar/Wind Harmer
0.164
944011AF1-069 GEN
Solar/Wind Harmer
13.17
3146376EDENTON
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.121
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3143336POWHATN
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.585
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.109
3146206CASHIE
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.339
3145893MURPHYS
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.201
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
316181AB2-040 GEN
Solar/Wind Harmer
0.278
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
316011AB1-132 GEN
Solar/Wind Harmer
3.535
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.767
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
316223AC1-118
Solar/Wind Harmer
0.136
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.651
316212AC1-099_GEN
Solar/Wind Harmer
0.966
3145933PARMELE
Solar/Wind Harmer
0.187
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
315722AD1-056 GEN
Solar/Wind Harmer
6.293
3146073TAR RVR
Solar/Wind Harmer
0.177
3146083TARBORO
Solar/Wind Harmer
0.177
3146233WITAKRS
Solar/Wind Harmer
0.89
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
964241AG1-285 GEN
Solar/Wind Harmer
11.761
970257AG2-171 GEN
Solar/Wind Harmer
5.621
971775AH1-396 GEN
Solar/Wind Harmer
0.281
959311AF2-222 GEN
Solar/Wind Harmer
15.601
3144293JTRSVLE
Adder
0.417
3147133PAMPLIN
Solar/Wind Harmer
0.547
961601AG1-000A GEN
Solar/Wind Harmer
12.382
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.348
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.058
972003AH1-546 GEN
Solar/Wind Harmer
5.44
971683AH1-343 GEN
Solar/Wind Harmer
5.439
970221AG2-151 GEN
Solar/Wind Harmer
7.825
316222AC1-221 GEN
Solar/Wind Harmer
0.604
316283AC2-100 C
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.176
270494AE1-108_GEN
Solar/Wind Harmer
1.557
315821AE2-092 GEN
Solar/Wind Harmer
0
3150331BIRCHWDA
Adder
21.106
3141196NOKESVL
Solar/Wind Helper
1.228
LAGNLTFEXP_LAGN->PJM
CLTF
7.97
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.669
NYPJM->LTFIMP_NY
CLTF
3.156
LGEELTFEXP_LGEE->PJM
CLTF
1.343
TVALTFEXP_TVA->PJM
CLTF
4.04
WECLTFEXP_WEC->PJM
CLTF
0.65
CPLELTFEXP_CPLE->PJM
CLTF
11.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.762
MECLTFEXP_MEC->PJM
CLTF
3.637
SIGELTFEXP_SIGE->PJM
CLTF
0.111

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3135.29
MW Contribution:
9.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150991CHESPKB
50/50
3.897
3150991CHESPKB
50/50
3.803
316294AC1-161 GEN
Solar/Wind Harmer
6.584
3145506HICKORY
Solar/Wind Harmer
1.399
3145506HICKORY
Solar/Wind Harmer
0.84
3145506HICKORY
Solar/Wind Harmer
0.21
316339AD2-160 GEN
Solar/Wind Harmer
0.556
316388AE2-253 GEN
Solar/Wind Harmer
1.081
3137176SLIGO L2192
Solar/Wind Harmer
1.375
3146456SLIGO L269
Solar/Wind Harmer
6.114
3130086AYDLETT
Solar/Wind Harmer
1.378
315976AC1-164 GENA
Solar/Wind Harmer
3.57
316169AC1-164_GENC
Solar/Wind Harmer
3.085
3146386ELIZ CT
Solar/Wind Harmer
0.338
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
315835AF2-110_GEN
Solar/Wind Harmer
2.256
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146626S HERTFORD
Solar/Wind Harmer
0.326
316156AD2-030 GEN
Solar/Wind Harmer
0.233
3146376EDENTON
Solar/Wind Harmer
1.394
3146376EDENTON
Solar/Wind Harmer
1.394
316349AD2-085 GEN
Solar/Wind Harmer
0.207
315742AE1-103 GEN
Solar/Wind Harmer
4.564
315614AA2-178 GEN
Solar/Wind Harmer
1.712
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.028
316065AD1-022 GEN
Solar/Wind Harmer
13.123
3145893MURPHYS
Solar/Wind Harmer
1.823
3145893MURPHYS
Solar/Wind Harmer
0.49
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
316140AB2-099
Solar/Wind Harmer
0.095
3150341NORNECKC1
Adder
2.776
3150341NORNECKC1
Adder
2.754
972185AH1-677 GEN
Adder
14.86
972187AH1-678 GEN
Adder
7.433
3144356SAPONY
Solar/Wind Harmer
2.125
316315AB2-025 C
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
20.197
3145933PARMELE
Solar/Wind Harmer
0.495
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.546
962571AG1-106 GEN
Solar/Wind Harmer
3.461
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
4.282
3145783HORNRTN
Solar/Wind Harmer
3.426
3145783HORNRTN
Solar/Wind Harmer
1.071
3145783HORNRTN
Solar/Wind Harmer
0.428
313506AB2-031 GEN
Solar/Wind Harmer
0.736
3145796HORNRTN
Solar/Wind Harmer
0.717
316005AA1-067
Solar/Wind Harmer
0.255
970099AG2-077 GEN
Solar/Wind Harmer
24.343
315724AD1-057 GEN
Solar/Wind Harmer
4.351
3145493TOT1
Solar/Wind Harmer
0.518
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.207
961601AG1-000A GEN
Solar/Wind Harmer
3.822
316049AB1-081 GEN
Solar/Wind Harmer
1.222
316263AC1-034 GEN
Solar/Wind Harmer
8.163
944641AF1-129 GEN
Adder
99.85
962561AG1-105 GEN
Solar/Wind Harmer
8.928
964791AG1-342 GEN
Solar/Wind Harmer
3.543
3146843MT LREL
Solar/Wind Harmer
0.184
3146843MT LREL
Solar/Wind Harmer
0.184
3150691DARBY 3
Adder
13.226
3150701DARBY 4
Adder
13.195
3150681DARBY 2
Adder
13.18
3150671DARBY 1
Adder
13.164
970323AG2-213 GEN
Solar/Wind Harmer
7.762
316118AC1-105 GEN
Solar/Wind Harmer
0.464
970301AG2-198 GEN
Solar/Wind Harmer
7.522
971223AH1-071 GEN
Solar/Wind Harmer
1.834
958211AF2-115 GEN
Solar/Wind Harmer
2.057
3144293JTRSVLE
Adder
0.409
3143526WINTERP
Solar/Wind Harmer
0.883
316312AB1-027
Solar/Wind Harmer
0.301
3147133PAMPLIN
Solar/Wind Harmer
0.168
3147133PAMPLIN
Solar/Wind Harmer
0.134
3142366NRTHEST
Adder
0.518
316313AB2-026
Solar/Wind Harmer
0.084
316336AC2-165 C
Solar/Wind Harmer
6.351
942751AE2-291 GEN
Solar/Wind Harmer
6.403
3146776BUCKING
Solar/Wind Harmer
0.464
3146776BUCKING
Solar/Wind Harmer
0.038
3150921YORKTN3
50/50
9.827
3144216WINCHST
50/50
1.452
3151101ELIZAR3
50/50
34.636
3151161SURRY 1
50/50
13.076
944581AF1-123 GEN
Solar/Wind Harmer
80.334
944601AF1-125 GEN
Solar/Wind Harmer
79.096
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.185
3144536CHRHLND
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.345
971153AH1-033 GEN
Solar/Wind Harmer
3.994
316246AF1-032 C
Solar/Wind Harmer
0.151
316321Z2-027
Solar/Wind Harmer
0.06
3145336SMITFLD
Solar/Wind Harmer
0.133
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3151171GRAVELC
Adder
4.49
3141766HARMONY
Solar/Wind Harmer
4.275
3141873WAN 176
Solar/Wind Harmer
5.649
3146376EDENTON
Solar/Wind Harmer
0.313
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.601
3145273HOLLAND
Solar/Wind Harmer
0.235
961611AG1-000B GEN
Solar/Wind Harmer
8.247
315735AD1-075 GEN1
Solar/Wind Harmer
0.823
3142946ENON
Solar/Wind Harmer
0.095
970657AG2-426 GEN
Solar/Wind Harmer
6.37
315778AD1-151 GEN
Solar/Wind Harmer
22.672
3146206CASHIE
Solar/Wind Harmer
0.282
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
3156081AA2-088 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.074
944011AF1-069 GEN
Solar/Wind Harmer
16.455
316458AB2-190 GEN2
Solar/Wind Harmer
1.455
3145893MURPHYS
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.272
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.687
315813AE1-149 C
Solar/Wind Harmer
13.975
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
970133AG2-095 GEN
Solar/Wind Harmer
2.435
970917AG2-570 GEN
Solar/Wind Harmer
22.276
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
316011AB1-132 GEN
Solar/Wind Harmer
4.412
316181AB2-040 GEN
Solar/Wind Harmer
0.341
3145796HORNRTN
Solar/Wind Harmer
0.956
3145796HORNRTN
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.233
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970293AG2-193 GEN
Solar/Wind Harmer
2.435
315722AD1-056 GEN
Solar/Wind Harmer
7.8
3147043LAWRENC
Solar/Wind Harmer
0.135
3146073TAR RVR
Solar/Wind Harmer
0.223
3146083TARBORO
Solar/Wind Harmer
0.223
3146233WITAKRS
Solar/Wind Harmer
1.106
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.752
961601AG1-000A GEN
Solar/Wind Harmer
15.289
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
3143096IRON208
Adder
0.896
3143096IRON208
Adder
0.878
316223AC1-118
Solar/Wind Harmer
0.151
3141906WESTMOR
Solar/Wind Harmer
0.085
964241AG1-285 GEN
Solar/Wind Harmer
12.653
970257AG2-171 GEN
Solar/Wind Harmer
5.821
971775AH1-396 GEN
Solar/Wind Harmer
0.291
959311AF2-222 GEN
Solar/Wind Harmer
16.033
3150861SPRUNCD
Adder
0.818
3144293JTRSVLE
Adder
0.409
3142416OLDCHRC
Solar/Wind Harmer
1.641
3147133PAMPLIN
Solar/Wind Harmer
0.527
316222AC1-221 GEN
Solar/Wind Harmer
0.676
316283AC2-100 C
Solar/Wind Harmer
0.32
942461AE2-259 GEN
Solar/Wind Harmer
0
971683AH1-343 GEN
Solar/Wind Harmer
5.718
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.04
316123AC1-075 GEN
Solar/Wind Harmer
0.173
3146776BUCKING
Solar/Wind Harmer
0.042
3152331SURRY 2
50/50
17.122
3150981CHESPKA
50/50
4.645
315773AC2-141 GEN
Solar/Wind Harmer
13.911
971317AH1-138 GEN
Solar/Wind Harmer
2.748
3138126ROCKLANDING
Solar/Wind Harmer
0.167
944591AF1-124 GEN
Solar/Wind Harmer
80.619
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.345
319010AE1-072 C
Solar/Wind Harmer
1.721
316072AD1-144
Solar/Wind Harmer
0.121
315975AC1-164 GENB
Solar/Wind Harmer
0.106
3145336SMITFLD
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
1.068
3146516WINFALL
Solar/Wind Harmer
0.33
316093AE2-104_GEN
Solar/Wind Harmer
5.529
3151171GRAVELC
Adder
3.415
3141766HARMONY
Solar/Wind Harmer
0.064
939411AE1-173 GEN
Solar/Wind Harmer
134.476
3130156CHOWAN
Solar/Wind Harmer
0.314
971777AH1-397 GEN
Solar/Wind Harmer
0.827
961611AG1-000B GEN
Solar/Wind Harmer
16.22
3138133OCRAN
Solar/Wind Harmer
0.185
940641AE2-051 GEN
Solar/Wind Harmer
24.223
315816AE2-034 GEN
Solar/Wind Harmer
1.284
3145663CRESWEL
Solar/Wind Harmer
0.842
971163AH1-040 GEN
Solar/Wind Harmer
24.077
315737AD1-076 GEN
Solar/Wind Harmer
3.712
971069AG2-661 GEN
Solar/Wind Harmer
5.038
962861AG1-135 GEN
Solar/Wind Harmer
9.047
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.027
3142433PROV 92
Solar/Wind Harmer
1.127
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
316381AD1-082 GEN
Solar/Wind Harmer
0.284
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
9.274
941031AE2-094 GEN
Solar/Wind Harmer
50.36
316132AB2-190 GEN1
Solar/Wind Harmer
1.455
3156021HOLLOMANSOL
Solar/Wind Harmer
1.227
3145893MURPHYS
Solar/Wind Harmer
1.089
3145893MURPHYS
Solar/Wind Harmer
1.211
3141726DUNNSVL
Solar/Wind Harmer
1.088
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
2.643
944631AF1-128 GEN
Adder
125.485
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.513
970919AG2-571 GEN
Solar/Wind Harmer
8.91
3146293MARTNCO
Solar/Wind Harmer
0.23
970087AG2-069 GEN
Solar/Wind Harmer
19.764
316023GEN1_S
Solar/Wind Harmer
0.546
3145783HORNRTN
Solar/Wind Harmer
0.241
316337AD2-073 GEN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
0.789
3145796HORNRTN
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.286
316494AC1-189 GEN
Solar/Wind Harmer
0.779
957481AF2-042 GEN
Solar/Wind Harmer
60.858
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3147043LAWRENC
Adder
2.033
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.223
3145493TOT1
Solar/Wind Harmer
0.994
3146233WITAKRS
Solar/Wind Harmer
0.877
316129AC1-054 GEN
Solar/Wind Harmer
0.814
315693AD1-088 GEN
Solar/Wind Harmer
10.407
971065AG2-659 GEN
Solar/Wind Harmer
9.207
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.378
3143096IRON208
Adder
0.896
316131AB2-060 GEN
Solar/Wind Harmer
0.601
3142543TWELFTH
Solar/Wind Harmer
0.018
970401AG2-262 GEN
Solar/Wind Harmer
1.083
315785AD2-033 C
Solar/Wind Harmer
1.488
316034AC1-036 C
Solar/Wind Harmer
0.012
3150851SPRUNCC
Adder
0.818
970685AG2-442 GEN
Solar/Wind Harmer
13.003
972135AH1-637 GEN
Solar/Wind Harmer
1.47
3143226MDLTHAN
Solar/Wind Harmer
0.172
971563AH1-280 GEN
Solar/Wind Harmer
1.828
3144293JTRSVLE
Adder
0.409
3144293JTRSVLE
Adder
0.323
3143526WINTERP
Solar/Wind Harmer
0.883
3142416OLDCHRC
Solar/Wind Harmer
0.44
3142416OLDCHRC
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.4
3146776BUCKING
Solar/Wind Harmer
0.046
972263AH1-716 GEN
50/50
238.136
3151081ELIZAR1
50/50
34.198
3151091ELIZAR2
50/50
33.604
941591AE2-156 GEN
50/50
31.212
3151201GRAVEL4
50/50
24.793
316159AE1-175 C
Solar/Wind Harmer
0.312
316316AC1-027 C
Solar/Wind Harmer
0.334
957871AF2-081 GEN
Solar/Wind Harmer
17.268
3146406KITTY HAWK
Solar/Wind Harmer
0.043
3138283WHITEMARSH
Solar/Wind Harmer
0.08
313526AB2-022
Solar/Wind Harmer
0.181
3146396TANGLEW
Solar/Wind Harmer
0.925
3145176PASQUOTANK
Solar/Wind Harmer
0.208
3146486SUNBURY
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
0.335
971445AH1-216 GEN
Solar/Wind Harmer
23.343
3151221GRAVEL6
Adder
23.338
3151191GRAVEL3
Adder
23.069
3151211GRAVEL5
Adder
23.069
3141873WAN 176
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.314
3130156CHOWAN
Solar/Wind Harmer
0.314
970189AG2-124 GEN
Solar/Wind Harmer
9.288
316311AC2-079 GEN
Solar/Wind Harmer
8.918
3141913WHIT STONE
Solar/Wind Harmer
0.31
3138133OCRAN
Solar/Wind Harmer
0.092
3143873LANEXA
Solar/Wind Harmer
0.184
3141783LANCAST
Solar/Wind Harmer
0.182
3141783LANCAST
Solar/Wind Harmer
0.121
3130546PLYMOUTH
Solar/Wind Harmer
0.291
315697AD1-025 GEN
Solar/Wind Harmer
0.313
315732AD1-074 GEN1
Solar/Wind Harmer
1.648
315733AD1-074 GEN2
Solar/Wind Harmer
1.648
970657AG2-426 GEN
Solar/Wind Harmer
2.085
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.547
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
970533AG2-339 GEN
Solar/Wind Harmer
20.659
3145893MURPHYS
Solar/Wind Harmer
0.735
3145893MURPHYS
Solar/Wind Harmer
0.272
970673AG2-436 GEN
Solar/Wind Harmer
33.602
316463AE2-346 GEN
Solar/Wind Harmer
0.229
3145513AHOSKIE
Solar/Wind Harmer
0.561
3145513AHOSKIE
Solar/Wind Harmer
0.268
3145683EARLEYS
Solar/Wind Harmer
0.533
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3141813NORNECK
Solar/Wind Harmer
0.265
971967AH1-528 GEN
Solar/Wind Harmer
41.637
3146043SEABORD
Solar/Wind Harmer
0.257
315814AE2-033 C
Solar/Wind Harmer
20.065
3146033SCOT NK
Solar/Wind Harmer
0.988
970085AG2-068 GEN
Solar/Wind Harmer
13.176
970581AG2-369 GEN
Solar/Wind Harmer
11.332
316426AA2-053 GEN
Solar/Wind Harmer
0.824
3143316POE
Solar/Wind Harmer
0.964
315652AC1-086 GEN
Solar/Wind Harmer
26.755
3137643SOCKMAN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
0.765
3145796HORNRTN
Solar/Wind Harmer
0.096
316210AC1-098 GEN
Solar/Wind Harmer
2.211
3145746EVERETS
Solar/Wind Harmer
0.95
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316274AC1-208 GEN
Solar/Wind Harmer
1.209
957861AF2-080 GEN
Solar/Wind Harmer
9.942
316327AA2-057 GEN
Solar/Wind Harmer
0.334
3145573BETHELC
Solar/Wind Harmer
0.223
3145573BETHELC
Solar/Wind Harmer
0.223
970831AG2-522 GEN
Solar/Wind Harmer
9.419
316486AD2-202 GEN
Solar/Wind Harmer
0.221
3144303KENBRDG
Solar/Wind Harmer
0.145
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971285AH1-108 GEN
Adder
1.339
970683AG2-441 GEN
Solar/Wind Harmer
10.637
970681AG2-440 GEN
Solar/Wind Harmer
7.06
946301AF1-294 GEN
Solar/Wind Harmer
3.382
961791AG1-021 GEN
Solar/Wind Harmer
1.645
316233AE1-074 FULL
Solar/Wind Harmer
0.136
971281AH1-106 GEN
Solar/Wind Harmer
2.357
971283AH1-107 GEN
Solar/Wind Harmer
2.357
944491AF1-114 GEN
Solar/Wind Harmer
0
316258AE1-075 C
Solar/Wind Harmer
0.101
971845AH1-439 GEN
Solar/Wind Harmer
5.382
LAGNLTFEXP_LAGN->PJM
CLTF
7.223
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.225
TVALTFEXP_TVA->PJM
CLTF
3.591
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
0.93
WECLTFEXP_WEC->PJM
CLTF
0.466
CPLELTFEXP_CPLE->PJM
CLTF
12.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.972
MECLTFEXP_MEC->PJM
CLTF
2.839
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.71 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3118.81
MW Contribution:
8.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150991CHESPKB
50/50
3.876
3150991CHESPKB
50/50
3.783
316294AC1-161 GEN
Solar/Wind Harmer
6.594
3145506HICKORY
Solar/Wind Harmer
1.395
3145506HICKORY
Solar/Wind Harmer
0.837
3145506HICKORY
Solar/Wind Harmer
0.209
316339AD2-160 GEN
Solar/Wind Harmer
0.554
316388AE2-253 GEN
Solar/Wind Harmer
1.078
3137176SLIGO L2192
Solar/Wind Harmer
1.371
3146456SLIGO L269
Solar/Wind Harmer
6.093
3130086AYDLETT
Solar/Wind Harmer
1.373
3146386ELIZ CT
Solar/Wind Harmer
0.337
3146516WINFALL
Solar/Wind Harmer
0.328
3146516WINFALL
Solar/Wind Harmer
0.328
3146516WINFALL
Solar/Wind Harmer
0.328
315835AF2-110_GEN
Solar/Wind Harmer
2.238
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146626S HERTFORD
Solar/Wind Harmer
0.325
315976AC1-164 GENA
Solar/Wind Harmer
3.337
316169AC1-164_GENC
Solar/Wind Harmer
2.883
3146376EDENTON
Solar/Wind Harmer
1.39
3146376EDENTON
Solar/Wind Harmer
1.39
316349AD2-085 GEN
Solar/Wind Harmer
0.203
315742AE1-103 GEN
Solar/Wind Harmer
4.533
316156AD2-030 GEN
Solar/Wind Harmer
0.221
315614AA2-178 GEN
Solar/Wind Harmer
1.707
316065AD1-022 GEN
Solar/Wind Harmer
13.089
972185AH1-677 GEN
Adder
15.403
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.815
3145893MURPHYS
Solar/Wind Harmer
0.488
972187AH1-678 GEN
Adder
7.697
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
316140AB2-099
Solar/Wind Harmer
0.095
970933AG2-581 GEN
Solar/Wind Harmer
20.776
3142946ENON
Solar/Wind Harmer
0.026
3144356SAPONY
Solar/Wind Harmer
2.11
316315AB2-025 C
Solar/Wind Harmer
0.202
3150341NORNECKC1
Adder
2.619
3150341NORNECKC1
Adder
2.598
3145933PARMELE
Solar/Wind Harmer
0.495
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.544
962571AG1-106 GEN
Solar/Wind Harmer
3.451
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.268
3145783HORNRTN
Solar/Wind Harmer
3.415
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.427
316005AA1-067
Solar/Wind Harmer
0.255
313506AB2-031 GEN
Solar/Wind Harmer
0.732
3145796HORNRTN
Solar/Wind Harmer
0.716
970099AG2-077 GEN
Solar/Wind Harmer
24.701
315724AD1-057 GEN
Solar/Wind Harmer
4.353
3145493TOT1
Solar/Wind Harmer
0.519
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.832
316049AB1-081 GEN
Solar/Wind Harmer
1.225
316263AC1-034 GEN
Solar/Wind Harmer
8.183
962561AG1-105 GEN
Solar/Wind Harmer
8.839
944641AF1-129 GEN
Adder
87.24
964791AG1-342 GEN
Solar/Wind Harmer
3.514
3150921YORKTN3
50/50
9.598
3144216WINCHST
50/50
1.417
3151101ELIZAR3
50/50
34.466
3151161SURRY 1
50/50
12.65
944581AF1-123 GEN
Solar/Wind Harmer
80.207
944601AF1-125 GEN
Solar/Wind Harmer
78.971
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.184
3146456SLIGO L269
Solar/Wind Harmer
0.344
971153AH1-033 GEN
Solar/Wind Harmer
3.981
3144536CHRHLND
Solar/Wind Harmer
0.051
316246AF1-032 C
Solar/Wind Harmer
0.151
316321Z2-027
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.328
3145336SMITFLD
Solar/Wind Harmer
0.13
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
0.312
3145273HOLLAND
Solar/Wind Harmer
0.233
3151171GRAVELC
Adder
4.344
3141766HARMONY
Solar/Wind Harmer
4.049
3141873WAN 176
Solar/Wind Harmer
5.369
961611AG1-000B GEN
Solar/Wind Harmer
7.907
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.513
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
944011AF1-069 GEN
Solar/Wind Harmer
17.093
3146206CASHIE
Solar/Wind Harmer
0.282
3156081AA2-088 GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
6.158
3145893MURPHYS
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
0.271
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
315778AD1-151 GEN
Solar/Wind Harmer
21.239
3146263WOODLND
Solar/Wind Harmer
0.259
970917AG2-570 GEN
Solar/Wind Harmer
23.033
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3142946ENON
Solar/Wind Harmer
0.086
3145823KELFORD
Solar/Wind Harmer
0.256
316458AB2-190 GEN2
Solar/Wind Harmer
1.348
316075AC2-137 C
Solar/Wind Harmer
0.067
3150351NORNECKC2
Adder
2.536
315813AE1-149 C
Solar/Wind Harmer
13.293
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
316011AB1-132 GEN
Solar/Wind Harmer
4.4
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.232
316181AB2-040 GEN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.954
3145796HORNRTN
Solar/Wind Harmer
0.238
970133AG2-095 GEN
Solar/Wind Harmer
2.207
315722AD1-056 GEN
Solar/Wind Harmer
7.803
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3147043LAWRENC
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
1.108
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.76
961601AG1-000A GEN
Solar/Wind Harmer
15.327
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.431
316223AC1-118
Solar/Wind Harmer
0.142
3141906WESTMOR
Solar/Wind Harmer
0.08
970293AG2-193 GEN
Solar/Wind Harmer
2.104
964241AG1-285 GEN
Solar/Wind Harmer
12.302
970257AG2-171 GEN
Solar/Wind Harmer
5.566
971775AH1-396 GEN
Solar/Wind Harmer
0.278
3143096IRON208
Adder
0.722
3143096IRON208
Adder
0.708
959311AF2-222 GEN
Solar/Wind Harmer
15.274
316222AC1-221 GEN
Solar/Wind Harmer
0.682
316283AC2-100 C
Solar/Wind Harmer
0.322
3152331SURRY 2
50/50
17.021
3150981CHESPKA
50/50
4.62
315773AC2-141 GEN
Solar/Wind Harmer
13.931
971317AH1-138 GEN
Solar/Wind Harmer
2.673
944591AF1-124 GEN
Solar/Wind Harmer
80.492
3138126ROCKLANDING
Solar/Wind Harmer
0.163
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.344
319010AE1-072 C
Solar/Wind Harmer
1.715
316072AD1-144
Solar/Wind Harmer
0.12
3146516WINFALL
Solar/Wind Harmer
1.064
3146516WINFALL
Solar/Wind Harmer
0.328
316093AE2-104_GEN
Solar/Wind Harmer
5.485
3145336SMITFLD
Solar/Wind Harmer
1.301
939411AE1-173 GEN
Solar/Wind Harmer
137.491
315975AC1-164 GENB
Solar/Wind Harmer
0.099
3130156CHOWAN
Solar/Wind Harmer
0.313
940641AE2-051 GEN
Solar/Wind Harmer
25.004
3151171GRAVELC
Adder
3.304
3141766HARMONY
Solar/Wind Harmer
0.061
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3145663CRESWEL
Solar/Wind Harmer
0.84
971163AH1-040 GEN
Solar/Wind Harmer
24.005
961611AG1-000B GEN
Solar/Wind Harmer
15.55
971777AH1-397 GEN
Solar/Wind Harmer
0.782
3138133OCRAN
Solar/Wind Harmer
0.175
315737AD1-076 GEN
Solar/Wind Harmer
3.702
941031AE2-094 GEN
Solar/Wind Harmer
52.313
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.224
3145893MURPHYS
Solar/Wind Harmer
1.085
3145893MURPHYS
Solar/Wind Harmer
1.206
316381AD1-082 GEN
Solar/Wind Harmer
0.274
3146173TUNIS
Solar/Wind Harmer
0.269
962861AG1-135 GEN
Solar/Wind Harmer
8.56
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
971069AG2-661 GEN
Solar/Wind Harmer
4.72
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
8.772
3146263WOODLND
Solar/Wind Harmer
0.259
970919AG2-571 GEN
Solar/Wind Harmer
9.213
3142433PROV 92
Solar/Wind Harmer
1.036
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3141726DUNNSVL
Solar/Wind Harmer
1.026
3145823KELFORD
Solar/Wind Harmer
0.256
970087AG2-069 GEN
Solar/Wind Harmer
20.426
315607AA1-063A GEN
Solar/Wind Harmer
0.511
316132AB2-190 GEN1
Solar/Wind Harmer
1.348
3150351NORNECKC2
Adder
2.494
3146293MARTNCO
Solar/Wind Harmer
0.23
316023GEN1_S
Solar/Wind Harmer
0.544
3145783HORNRTN
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
0.238
960081AF2-299 GEN
Solar/Wind Harmer
2.272
944631AF1-128 GEN
Adder
111.26
957481AF2-042 GEN
Solar/Wind Harmer
61.753
316494AC1-189 GEN
Solar/Wind Harmer
0.78
316337AD2-073 GEN
Solar/Wind Harmer
0.195
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.995
3147043LAWRENC
Adder
2.014
3146233WITAKRS
Solar/Wind Harmer
0.878
315693AD1-088 GEN
Solar/Wind Harmer
10.418
316129AC1-054 GEN
Solar/Wind Harmer
0.81
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.379
971065AG2-659 GEN
Solar/Wind Harmer
9.166
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316131AB2-060 GEN
Solar/Wind Harmer
0.589
970401AG2-262 GEN
Solar/Wind Harmer
1.074
315785AD2-033 C
Solar/Wind Harmer
1.43
972263AH1-716 GEN
50/50
236.196
3151081ELIZAR1
50/50
34.031
3151091ELIZAR2
50/50
33.44
941591AE2-156 GEN
50/50
31.049
3151201GRAVEL4
50/50
23.986
316159AE1-175 C
Solar/Wind Harmer
0.301
316316AC1-027 C
Solar/Wind Harmer
0.333
957871AF2-081 GEN
Solar/Wind Harmer
17.21
3146406KITTY HAWK
Solar/Wind Harmer
0.043
313526AB2-022
Solar/Wind Harmer
0.18
3146396TANGLEW
Solar/Wind Harmer
0.921
3145176PASQUOTANK
Solar/Wind Harmer
0.207
3146486SUNBURY
Solar/Wind Harmer
0.333
3146486SUNBURY
Solar/Wind Harmer
0.333
3138283WHITEMARSH
Solar/Wind Harmer
0.077
971445AH1-216 GEN
Solar/Wind Harmer
22.818
3130156CHOWAN
Solar/Wind Harmer
0.313
3130156CHOWAN
Solar/Wind Harmer
0.313
3151221GRAVEL6
Adder
22.578
3151191GRAVEL3
Adder
22.318
3151211GRAVEL5
Adder
22.318
316311AC2-079 GEN
Solar/Wind Harmer
8.763
3141873WAN 176
Solar/Wind Harmer
0.06
970189AG2-124 GEN
Solar/Wind Harmer
8.775
3141913WHIT STONE
Solar/Wind Harmer
0.294
3138133OCRAN
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.29
315732AD1-074 GEN1
Solar/Wind Harmer
1.644
315733AD1-074 GEN2
Solar/Wind Harmer
1.644
3141783LANCAST
Solar/Wind Harmer
0.173
3141783LANCAST
Solar/Wind Harmer
0.115
3143873LANEXA
Solar/Wind Harmer
0.173
970533AG2-339 GEN
Solar/Wind Harmer
21.46
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.52
970673AG2-436 GEN
Solar/Wind Harmer
34.876
970657AG2-426 GEN
Solar/Wind Harmer
2.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
3145893MURPHYS
Solar/Wind Harmer
0.732
3145893MURPHYS
Solar/Wind Harmer
0.271
971967AH1-528 GEN
Solar/Wind Harmer
43.008
316463AE2-346 GEN
Solar/Wind Harmer
0.228
3145513AHOSKIE
Solar/Wind Harmer
0.559
3145513AHOSKIE
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.532
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3146043SEABORD
Solar/Wind Harmer
0.256
970085AG2-068 GEN
Solar/Wind Harmer
13.617
970581AG2-369 GEN
Solar/Wind Harmer
11.711
315814AE2-033 C
Solar/Wind Harmer
19.928
3141813NORNECK
Solar/Wind Harmer
0.25
3146033SCOT NK
Solar/Wind Harmer
0.986
316426AA2-053 GEN
Solar/Wind Harmer
0.821
315652AC1-086 GEN
Solar/Wind Harmer
26.681
3137643SOCKMAN
Solar/Wind Harmer
0.959
3145746EVERETS
Solar/Wind Harmer
0.95
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.208
3145796HORNRTN
Solar/Wind Harmer
0.763
3145796HORNRTN
Solar/Wind Harmer
0.095
316274AC1-208 GEN
Solar/Wind Harmer
1.208
3143316POE
Solar/Wind Harmer
0.919
957861AF2-080 GEN
Solar/Wind Harmer
9.954
316327AA2-057 GEN
Solar/Wind Harmer
0.334
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
970831AG2-522 GEN
Solar/Wind Harmer
9.378
316486AD2-202 GEN
Solar/Wind Harmer
0.223
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
10.042
970681AG2-440 GEN
Solar/Wind Harmer
6.665
946301AF1-294 GEN
Solar/Wind Harmer
3.152
961791AG1-021 GEN
Solar/Wind Harmer
1.533
944491AF1-114 GEN
Solar/Wind Harmer
0
971285AH1-108 GEN
Adder
0.865
3146843MT LREL
Solar/Wind Harmer
0.183
3146843MT LREL
Solar/Wind Harmer
0.183
316118AC1-105 GEN
Solar/Wind Harmer
0.462
970323AG2-213 GEN
Solar/Wind Harmer
7.421
970301AG2-198 GEN
Solar/Wind Harmer
7.027
958211AF2-115 GEN
Solar/Wind Harmer
1.917
3144293JTRSVLE
Adder
0.381
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
3150691DARBY 3
Adder
10.678
3150701DARBY 4
Adder
10.653
3150681DARBY 2
Adder
10.641
3150671DARBY 1
Adder
10.629
316312AB1-027
Solar/Wind Harmer
0.25
3142366NRTHEST
Adder
0.394
942751AE2-291 GEN
Solar/Wind Harmer
6.318
316034AC1-036 C
Solar/Wind Harmer
0.012
3143096IRON208
Adder
0.722
970685AG2-442 GEN
Solar/Wind Harmer
12.204
972135AH1-637 GEN
Solar/Wind Harmer
1.375
971563AH1-280 GEN
Solar/Wind Harmer
1.704
3144293JTRSVLE
Adder
0.381
3144293JTRSVLE
Adder
0.301
3142543TWELFTH
Solar/Wind Harmer
0.014
3142416OLDCHRC
Solar/Wind Harmer
0.366
3142416OLDCHRC
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.076
3150851SPRUNCC
Adder
0.529
3144293JTRSVLE
Adder
0.381
3147133PAMPLIN
Solar/Wind Harmer
0.486
971683AH1-343 GEN
Solar/Wind Harmer
5.699
942461AE2-259 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
1.365
316123AC1-075 GEN
Solar/Wind Harmer
0.171
3146926FARMVIL
Solar/Wind Harmer
0.076
3150861SPRUNCD
Adder
0.529
LAGNLTFEXP_LAGN->PJM
CLTF
7.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.448
TVALTFEXP_TVA->PJM
CLTF
3.583
NYPJM->LTFIMP_NY
CLTF
2.098
LGEELTFEXP_LGEE->PJM
CLTF
0.91
WECLTFEXP_WEC->PJM
CLTF
0.457
CPLELTFEXP_CPLE->PJM
CLTF
12.852
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.08
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.926
MECLTFEXP_MEC->PJM
CLTF
2.807
SIGELTFEXP_SIGE->PJM
CLTF
0.081

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6472.73
MW Contribution:
10.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
1.309
3150691DARBY 3
50/50
29.078
3150701DARBY 4
50/50
29.01
3150681DARBY 2
50/50
28.977
3150671DARBY 1
50/50
28.943
3142366NRTHEST
50/50
1.316
3150621CHESTS7
50/50
1.097
316312AB1-027
Solar/Wind Harmer
0.691
315976AC1-164 GENA
Solar/Wind Harmer
4.068
316169AC1-164_GENC
Solar/Wind Harmer
3.515
3142946ENON
Solar/Wind Harmer
0.038
316294AC1-161 GEN
Solar/Wind Harmer
6.385
316033AB2-134 GEN
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
173.96
3150991CHESPKB
Adder
3.796
3150991CHESPKB
Adder
3.705
3145506HICKORY
Solar/Wind Harmer
1.441
3145506HICKORY
Solar/Wind Harmer
0.864
3145506HICKORY
Solar/Wind Harmer
0.216
316339AD2-160 GEN
Solar/Wind Harmer
0.574
316388AE2-253 GEN
Solar/Wind Harmer
1.117
3137176SLIGO L2192
Solar/Wind Harmer
1.423
3146456SLIGO L269
Solar/Wind Harmer
6.328
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
1.428
316349AD2-085 GEN
Solar/Wind Harmer
0.236
3143526WINTERP
Solar/Wind Harmer
1.839
315835AF2-110_GEN
Solar/Wind Harmer
2.427
3146386ELIZ CT
Solar/Wind Harmer
0.353
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.659
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315742AE1-103 GEN
Solar/Wind Harmer
5.052
3146376EDENTON
Solar/Wind Harmer
1.502
3146376EDENTON
Solar/Wind Harmer
1.502
3144356SAPONY
Solar/Wind Harmer
2.782
316315AB2-025 C
Solar/Wind Harmer
0.266
315614AA2-178 GEN
Solar/Wind Harmer
1.876
972193AH1-681 GEN
Adder
7.349
316065AD1-022 GEN
Solar/Wind Harmer
14.725
972185AH1-677 GEN
Adder
17.888
3145893MURPHYS
Solar/Wind Harmer
2.11
3145893MURPHYS
Solar/Wind Harmer
0.567
972187AH1-678 GEN
Adder
8.982
3146173TUNIS
Solar/Wind Harmer
0.312
3146173TUNIS
Solar/Wind Harmer
0.312
316365GEN2_N
Solar/Wind Harmer
0.691
316140AB2-099
Solar/Wind Harmer
0.111
970933AG2-581 GEN
Solar/Wind Harmer
24.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
962571AG1-106 GEN
Solar/Wind Harmer
4.273
313506AB2-031 GEN
Solar/Wind Harmer
0.92
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.37
3145796HORNRTN
Solar/Wind Harmer
0.888
3145783HORNRTN
Solar/Wind Harmer
5.262
3145783HORNRTN
Solar/Wind Harmer
4.209
3145783HORNRTN
Solar/Wind Harmer
1.315
3145783HORNRTN
Solar/Wind Harmer
0.526
3145933PARMELE
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.038
316313AB2-026
Solar/Wind Harmer
0.18
316005AA1-067
Solar/Wind Harmer
0.305
315724AD1-057 GEN
Solar/Wind Harmer
5.431
3150341NORNECKC1
Adder
2.892
3150341NORNECKC1
Adder
2.869
3145493TOT1
Solar/Wind Harmer
0.639
3145453TOT5
Solar/Wind Harmer
0.383
3145603CNETO
Solar/Wind Harmer
0.256
316336AC2-165 C
Solar/Wind Harmer
13.939
961601AG1-000A GEN
Solar/Wind Harmer
4.802
316049AB1-081 GEN
Solar/Wind Harmer
1.536
316263AC1-034 GEN
Solar/Wind Harmer
10.258
970301AG2-198 GEN
Solar/Wind Harmer
11.151
970323AG2-213 GEN
Solar/Wind Harmer
11.095
972189AH1-679 GEN
Adder
4.352
962561AG1-105 GEN
Solar/Wind Harmer
12.278
958211AF2-115 GEN
Solar/Wind Harmer
3.066
3144293JTRSVLE
Adder
0.61
964791AG1-342 GEN
Solar/Wind Harmer
4.878
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316118AC1-105 GEN
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.912
3146776BUCKING
Solar/Wind Harmer
0.074
942751AE2-291 GEN
Solar/Wind Harmer
10.74
942671AE2-283 GEN
Solar/Wind Harmer
3.934
316045AC1-158 PL2
Solar/Wind Helper
8.047
316450AC1-158 RIC
Solar/Wind Helper
0.671
316006AB2-029 C
Solar/Wind Helper
0.166
316411AF1-147_GEN1
Solar/Wind Helper
1.085
223401AF1-299 GEN
Solar/Wind Helper
0.395
223402AF1-300 C
Solar/Wind Helper
0.395
237006AB1-125 GEN
Solar/Wind Helper
0.121
238221AF1-254 C O1
Solar/Wind Helper
0.239
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.432
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.935
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.058
219912AD2-042 GEN
Solar/Wind Helper
0.145
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.126
972263AH1-716 GEN
50/50
220.273
3150631CHESTG8
50/50
2.35
316159AE1-175 C
Solar/Wind Harmer
0.323
315697AD1-025 GEN
Solar/Wind Harmer
0.395
3151201GRAVEL4
Adder
26.62
3151221GRAVEL6
Adder
26.59
3151191GRAVEL3
Adder
26.283
3151211GRAVEL5
Adder
26.283
971445AH1-216 GEN
Solar/Wind Harmer
25.675
971285AH1-108 GEN
Adder
2.749
3151081ELIZAR1
Adder
33.238
3151091ELIZAR2
Adder
32.66
316316AC1-027 C
Solar/Wind Harmer
0.345
957871AF2-081 GEN
Solar/Wind Harmer
17.845
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
3146406KITTY HAWK
Solar/Wind Harmer
0.044
970657AG2-426 GEN
Solar/Wind Harmer
2.609
316311AC2-079 GEN
Solar/Wind Harmer
10.174
3143873LANEXA
Solar/Wind Harmer
0.212
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.907
971283AH1-107 GEN
Solar/Wind Harmer
4.907
313526AB2-022
Solar/Wind Harmer
0.189
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.394
3146396TANGLEW
Solar/Wind Harmer
0.969
3145176PASQUOTANK
Solar/Wind Harmer
0.218
970189AG2-124 GEN
Solar/Wind Harmer
10.294
3141873WAN 176
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.332
315814AE2-033 C
Solar/Wind Harmer
26.224
3138133OCRAN
Solar/Wind Harmer
0.099
970533AG2-339 GEN
Solar/Wind Harmer
24.659
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.323
970673AG2-436 GEN
Solar/Wind Harmer
40.239
315732AD1-074 GEN1
Solar/Wind Harmer
1.836
315733AD1-074 GEN2
Solar/Wind Harmer
1.836
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.886
971967AH1-528 GEN
Solar/Wind Harmer
50.538
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.315
316463AE2-346 GEN
Solar/Wind Harmer
0.265
3145513AHOSKIE
Solar/Wind Harmer
0.65
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.619
3145683EARLEYS
Solar/Wind Harmer
0.309
3145683EARLEYS
Solar/Wind Harmer
0.309
3146043SEABORD
Solar/Wind Harmer
0.307
970085AG2-068 GEN
Solar/Wind Harmer
16.114
970581AG2-369 GEN
Solar/Wind Harmer
13.858
315652AC1-086 GEN
Solar/Wind Harmer
33.038
316426AA2-053 GEN
Solar/Wind Harmer
1.002
3137643SOCKMAN
Solar/Wind Harmer
1.193
3145796HORNRTN
Solar/Wind Harmer
0.947
3145796HORNRTN
Solar/Wind Harmer
0.118
3146033SCOT NK
Solar/Wind Harmer
1.183
316210AC1-098 GEN
Solar/Wind Harmer
2.685
316258AE1-075 C
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
1.484
3145746EVERETS
Solar/Wind Harmer
1.136
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
970831AG2-522 GEN
Solar/Wind Harmer
12.02
316486AD2-202 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
12.085
316327AA2-057 GEN
Solar/Wind Harmer
0.413
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.275
3145573BETHELC
Solar/Wind Harmer
0.275
3144303KENBRDG
Solar/Wind Harmer
0.208
970683AG2-441 GEN
Solar/Wind Harmer
15.53
970681AG2-440 GEN
Solar/Wind Harmer
10.308
946301AF1-294 GEN
Solar/Wind Harmer
5.041
961791AG1-021 GEN
Solar/Wind Harmer
2.452
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
971845AH1-439 GEN
Solar/Wind Harmer
10.407
972205AH1-687 GEN
Adder
8.897
270197AD1-017 GEN1
Solar/Wind Harmer
1.05
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.149
3151881LOWMORC
Adder
1.59
3151881LOWMORC
Adder
1.565
3151861LOWMORA
Adder
1.54
270069AE2-166 C O1
Solar/Wind Harmer
6.438
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.855
315651AD1-115 GEN
Solar/Wind Helper
1.155
226929AD2-058 GEN
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.186
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.356
233915AB1-141 GEN
Solar/Wind Helper
0.489
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
3150611CHESTG7
50/50
2.388
3151161SURRY 1
50/50
14.898
3142416OLDCHRC
Solar/Wind Harmer
3.766
316075AC2-137 C
Solar/Wind Harmer
0.103
970293AG2-193 GEN
Solar/Wind Harmer
4.088
3142946ENON
Solar/Wind Harmer
0.127
3143096IRON208
Adder
1.568
3143096IRON208
Adder
1.537
3150921YORKTN3
Adder
9.345
3144216WINCHST
Adder
1.4
970133AG2-095 GEN
Solar/Wind Harmer
3.539
316458AB2-190 GEN2
Solar/Wind Harmer
1.962
315778AD1-151 GEN
Solar/Wind Harmer
29.389
961611AG1-000B GEN
Solar/Wind Harmer
9.766
3151171GRAVELC
Adder
5.116
3150861SPRUNCD
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.688
944601AF1-125 GEN
Solar/Wind Harmer
80.429
3151101ELIZAR3
Adder
33.663
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.191
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
971153AH1-033 GEN
Solar/Wind Harmer
4.134
316473AC1-191 GEN
Solar/Wind Harmer
1.208
316246AF1-032 C
Solar/Wind Harmer
0.158
315813AE1-149 C
Solar/Wind Harmer
18.999
970657AG2-426 GEN
Solar/Wind Harmer
7.973
316321Z2-027
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
4.65
3146516WINFALL
Solar/Wind Harmer
0.348
3141843SHACKLE
Adder
1.775
316203AE2-005 GEN
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.346
3145273HOLLAND
Solar/Wind Harmer
0.257
3141873WAN 176
Solar/Wind Harmer
6.09
3146376EDENTON
Solar/Wind Harmer
0.338
944011AF1-069 GEN
Solar/Wind Harmer
19.64
315735AD1-075 GEN1
Solar/Wind Harmer
0.917
972255AH1-712 GEN
Adder
164.477
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.315
3146173TUNIS
Solar/Wind Harmer
0.312
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.157
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
316011AB1-132 GEN
Solar/Wind Harmer
5.448
316181AB2-040 GEN
Solar/Wind Harmer
0.427
3145796HORNRTN
Solar/Wind Harmer
1.183
3145796HORNRTN
Solar/Wind Harmer
0.296
3145933PARMELE
Solar/Wind Harmer
0.292
3147043LAWRENC
Solar/Wind Harmer
0.175
316212AC1-099_GEN
Solar/Wind Harmer
1.498
3143336POWHATN
Solar/Wind Harmer
4.37
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315722AD1-056 GEN
Solar/Wind Harmer
9.736
316478AD1-087 GEN
Solar/Wind Harmer
0.974
3150351NORNECKC2
Adder
2.799
3146073TAR RVR
Solar/Wind Harmer
0.275
3146083TARBORO
Solar/Wind Harmer
0.275
3146233WITAKRS
Solar/Wind Harmer
1.38
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.208
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.54
964241AG1-285 GEN
Solar/Wind Harmer
17.565
970257AG2-171 GEN
Solar/Wind Harmer
8.322
971775AH1-396 GEN
Solar/Wind Harmer
0.416
959311AF2-222 GEN
Solar/Wind Harmer
23.056
3144293JTRSVLE
Adder
0.61
3147133PAMPLIN
Solar/Wind Harmer
0.797
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.147
3146776BUCKING
Solar/Wind Harmer
0.082
971683AH1-343 GEN
Solar/Wind Harmer
8.387
316222AC1-221 GEN
Solar/Wind Harmer
0.936
316283AC2-100 C
Solar/Wind Harmer
0.443
972003AH1-546 GEN
Solar/Wind Harmer
7.301
316223AC1-118
Solar/Wind Harmer
0.148
3141906WESTMOR
Solar/Wind Harmer
0.083
316123AC1-075 GEN
Solar/Wind Harmer
0.276
970221AG2-151 GEN
Solar/Wind Harmer
10.604
270494AE1-108_GEN
Solar/Wind Harmer
2.19
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.032
3148013FISHERV
Solar/Wind Harmer
0.153
3151861LOWMORA
Adder
1.602
958131AF2-107 GEN
Solar/Wind Harmer
4.284
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3141196NOKESVL
Solar/Wind Helper
1.392
3147666LOUISA
Solar/Wind Helper
0.739
227287AC2-120 GEN
Solar/Wind Helper
0.434
226910AB2-157 C
Solar/Wind Helper
0.018
3132273ORANGE
Solar/Wind Helper
0.053
23777801MSM_W1-116
Solar/Wind Helper
0.111
208835TUHI V3-051
Solar/Wind Helper
0.021
237002AB1-128_GEN
Solar/Wind Helper
0.386
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.384
237085AD2-009_GEN
Solar/Wind Helper
1.397
233935AB2-179 C
Solar/Wind Helper
1.236
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.28
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.732
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.113
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
3152331SURRY 2
50/50
15.655
3150641CHESTS8
50/50
1.21
3142416OLDCHRC
Solar/Wind Harmer
1.01
3142416OLDCHRC
Solar/Wind Harmer
0.387
315975AC1-164 GENB
Solar/Wind Harmer
0.12
944631AF1-128 GEN
Adder
179.295
3143096IRON208
Adder
1.568
3138126ROCKLANDING
Solar/Wind Harmer
0.17
971317AH1-138 GEN
Solar/Wind Harmer
2.77
315773AC2-141 GEN
Solar/Wind Harmer
13.491
3142543TWELFTH
Solar/Wind Harmer
0.035
316132AB2-190 GEN1
Solar/Wind Harmer
1.962
971069AG2-661 GEN
Solar/Wind Harmer
6.531
961611AG1-000B GEN
Solar/Wind Harmer
19.206
3151171GRAVELC
Adder
3.89
3150851SPRUNCC
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
1.457
944591AF1-124 GEN
Solar/Wind Harmer
81.978
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.064
3150981CHESPKA
Adder
4.525
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316072AD1-144
Solar/Wind Harmer
0.128
3142433PROV 92
Solar/Wind Harmer
1.431
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
319010AE1-072 C
Solar/Wind Harmer
1.782
316381AD1-082 GEN
Solar/Wind Harmer
0.36
3143526WINTERP
Solar/Wind Harmer
1.839
316093AE2-104_GEN
Solar/Wind Harmer
5.948
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.128
3146516WINFALL
Solar/Wind Harmer
0.348
971777AH1-397 GEN
Solar/Wind Harmer
0.917
939411AE1-173 GEN
Solar/Wind Harmer
148.2
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.419
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
1.407
3145663CRESWEL
Solar/Wind Harmer
0.923
971163AH1-040 GEN
Solar/Wind Harmer
26.382
941031AE2-094 GEN
Solar/Wind Harmer
60.109
315737AD1-076 GEN
Solar/Wind Harmer
4.134
972277AH1-723 GEN
Adder
191.666
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.792
3145893MURPHYS
Solar/Wind Harmer
1.261
3145893MURPHYS
Solar/Wind Harmer
1.402
3156021HOLLOMANSOL
Solar/Wind Harmer
1.407
3146173TUNIS
Solar/Wind Harmer
0.312
316023GEN1_S
Solar/Wind Harmer
0.691
3145683EARLEYS
Solar/Wind Harmer
0.309
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
315607AA1-063A GEN
Solar/Wind Harmer
0.615
970919AG2-571 GEN
Solar/Wind Harmer
10.863
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.903
970087AG2-069 GEN
Solar/Wind Harmer
24.172
962861AG1-135 GEN
Solar/Wind Harmer
9.549
3145796HORNRTN
Solar/Wind Harmer
0.976
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
9.772
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.634
957481AF2-042 GEN
Solar/Wind Harmer
77.596
3143336POWHATN
Solar/Wind Harmer
5.141
3141726DUNNSVL
Solar/Wind Harmer
1.144
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315693AD1-088 GEN
Solar/Wind Harmer
13.636
316494AC1-189 GEN
Solar/Wind Harmer
0.947
316129AC1-054 GEN
Solar/Wind Harmer
1.044
971065AG2-659 GEN
Solar/Wind Harmer
11.863
3150351NORNECKC2
Adder
2.753
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.275
3145493TOT1
Solar/Wind Harmer
1.225
3146233WITAKRS
Solar/Wind Harmer
1.094
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.475
316131AB2-060 GEN
Solar/Wind Harmer
0.824
315785AD2-033 C
Solar/Wind Harmer
2.11
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
19.165
971563AH1-280 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.61
3144293JTRSVLE
Adder
0.481
970401AG2-262 GEN
Solar/Wind Harmer
1.491
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.21
970937AG2-583 GEN
Solar/Wind Harmer
14.653
3146776BUCKING
Solar/Wind Harmer
0.091
971377AH1-170 GEN
Solar/Wind Harmer
2.121
3147623JAMES R
Solar/Wind Harmer
0.461
970223AG2-152 GEN
Solar/Wind Harmer
12.092
3147123OTTER R
Solar/Wind Harmer
0.099
3147312GRETNA
Solar/Wind Harmer
0.126
3146802CHATHAM
Solar/Wind Harmer
0.118
941801AE2-185 GEN
Solar/Wind Harmer
5.057
972135AH1-637 GEN
Solar/Wind Harmer
1.313
270030AE2-140 GEN
Solar/Wind Harmer
15.083
962751AG1-124 GEN
Solar/Wind Harmer
6.345
316447AC1-158 HLD
Solar/Wind Helper
5.534
316044AC1-158 PL1
Solar/Wind Helper
2.515
316415AF1-147_GEN2
Solar/Wind Helper
1.085
3147666LOUISA
Solar/Wind Helper
1.286
316192AB2-158 GEN
Solar/Wind Helper
2.116
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.387
208835TUHI V3-051
Solar/Wind Helper
0.021
235063AE1-101 C2
Solar/Wind Helper
1.432
205916AD1-020 GEN
Solar/Wind Helper
1.655
233918AB1-142 GEN
Solar/Wind Helper
0.489
233944AB2-135 GEN
Solar/Wind Helper
0.574
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
238175AF1-290_GEN
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
14.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.893
NYPJM->LTFIMP_NY
CLTF
4.657
LGEELTFEXP_LGEE->PJM
CLTF
2.991
TVALTFEXP_TVA->PJM
CLTF
7.369
WECLTFEXP_WEC->PJM
CLTF
1.512
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CPLELTFEXP_CPLE->PJM
CLTF
17.675
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.931
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.074
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.634
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.24

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5743.4
MW Contribution:
8.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
193.959
3151081ELIZAR1
50/50
30.542
3151091ELIZAR2
50/50
30.012
941591AE2-156 GEN
50/50
27.909
3151201GRAVEL4
50/50
24.044
316159AE1-175 C
Solar/Wind Harmer
0.28
316316AC1-027 C
Solar/Wind Harmer
0.299
971445AH1-216 GEN
Solar/Wind Harmer
21.985
3151221GRAVEL6
Adder
22.633
3151191GRAVEL3
Adder
22.373
3151211GRAVEL5
Adder
22.373
957871AF2-081 GEN
Solar/Wind Harmer
15.456
3146406KITTY HAWK
Solar/Wind Harmer
0.038
3138283WHITEMARSH
Solar/Wind Harmer
0.072
315697AD1-025 GEN
Solar/Wind Harmer
0.33
313526AB2-022
Solar/Wind Harmer
0.163
3146486SUNBURY
Solar/Wind Harmer
0.304
3146486SUNBURY
Solar/Wind Harmer
0.304
3146396TANGLEW
Solar/Wind Harmer
0.838
3145176PASQUOTANK
Solar/Wind Harmer
0.188
316311AC2-079 GEN
Solar/Wind Harmer
8.676
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970657AG2-426 GEN
Solar/Wind Harmer
2.194
970189AG2-124 GEN
Solar/Wind Harmer
8.799
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.291
3130156CHOWAN
Solar/Wind Harmer
0.291
3143316POE
Solar/Wind Harmer
1.152
3141913WHIT STONE
Solar/Wind Harmer
0.285
3138133OCRAN
Solar/Wind Harmer
0.085
315814AE2-033 C
Solar/Wind Harmer
22.007
970533AG2-339 GEN
Solar/Wind Harmer
21.004
3130546PLYMOUTH
Solar/Wind Harmer
0.278
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
315732AD1-074 GEN1
Solar/Wind Harmer
1.577
315733AD1-074 GEN2
Solar/Wind Harmer
1.577
970673AG2-436 GEN
Solar/Wind Harmer
34.262
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.197
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.269
971967AH1-528 GEN
Solar/Wind Harmer
42.871
316463AE2-346 GEN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.529
3145683EARLEYS
Solar/Wind Harmer
0.264
3145683EARLEYS
Solar/Wind Harmer
0.264
3146043SEABORD
Solar/Wind Harmer
0.261
970085AG2-068 GEN
Solar/Wind Harmer
13.709
970581AG2-369 GEN
Solar/Wind Harmer
11.79
315652AC1-086 GEN
Solar/Wind Harmer
28.018
316426AA2-053 GEN
Solar/Wind Harmer
0.85
3137643SOCKMAN
Solar/Wind Harmer
1.009
3146033SCOT NK
Solar/Wind Harmer
1.008
3142296MT RD221
50/50
1.095
3150991CHESPKB
50/50
3.487
3150991CHESPKB
50/50
3.403
315976AC1-164 GENA
Solar/Wind Harmer
3.491
316169AC1-164_GENC
Solar/Wind Harmer
3.016
316312AB1-027
Solar/Wind Harmer
0.588
316294AC1-161 GEN
Solar/Wind Harmer
5.584
3142946ENON
Solar/Wind Harmer
0.031
3145506HICKORY
Solar/Wind Harmer
1.248
3145506HICKORY
Solar/Wind Harmer
0.749
3145506HICKORY
Solar/Wind Harmer
0.187
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316388AE2-253 GEN
Solar/Wind Harmer
0.967
3150691DARBY 3
Adder
22.312
3150701DARBY 4
Adder
22.26
3150681DARBY 2
Adder
22.234
3150671DARBY 1
Adder
22.208
3137176SLIGO L2192
Solar/Wind Harmer
1.233
3146456SLIGO L269
Solar/Wind Harmer
5.48
3130086AYDLETT
Solar/Wind Harmer
1.236
316033AB2-134 GEN
Solar/Wind Harmer
0.001
972193AH1-681 GEN
Adder
7.029
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
0.998
315835AF2-110_GEN
Solar/Wind Harmer
2.089
316349AD2-085 GEN
Solar/Wind Harmer
0.201
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
944641AF1-129 GEN
Adder
140.43
316156AD2-030 GEN
Solar/Wind Harmer
0.215
3146376EDENTON
Solar/Wind Harmer
1.295
3146376EDENTON
Solar/Wind Harmer
1.295
315742AE1-103 GEN
Solar/Wind Harmer
4.334
315614AA2-178 GEN
Solar/Wind Harmer
1.614
3144356SAPONY
Solar/Wind Harmer
2.334
316315AB2-025 C
Solar/Wind Harmer
0.223
316065AD1-022 GEN
Solar/Wind Harmer
12.64
972185AH1-677 GEN
Adder
15.221
3145893MURPHYS
Solar/Wind Harmer
1.802
3145893MURPHYS
Solar/Wind Harmer
0.484
972187AH1-678 GEN
Adder
7.639
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.094
316365GEN2_N
Solar/Wind Harmer
0.583
970933AG2-581 GEN
Solar/Wind Harmer
20.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
962571AG1-106 GEN
Solar/Wind Harmer
3.624
313506AB2-031 GEN
Solar/Wind Harmer
0.777
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.753
3145783HORNRTN
Solar/Wind Harmer
4.46
3145783HORNRTN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
1.115
3145783HORNRTN
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.5
3145933PARMELE
Solar/Wind Harmer
0.25
316005AA1-067
Solar/Wind Harmer
0.26
970099AG2-077 GEN
Solar/Wind Harmer
26.001
315724AD1-057 GEN
Solar/Wind Harmer
4.616
3150341NORNECKC1
Adder
2.466
3150341NORNECKC1
Adder
2.447
3145493TOT1
Solar/Wind Harmer
0.545
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.087
316049AB1-081 GEN
Solar/Wind Harmer
1.307
316263AC1-034 GEN
Solar/Wind Harmer
8.73
972189AH1-679 GEN
Adder
3.65
962561AG1-105 GEN
Solar/Wind Harmer
10.202
964791AG1-342 GEN
Solar/Wind Harmer
4.06
3146843MT LREL
Solar/Wind Harmer
0.211
3146843MT LREL
Solar/Wind Harmer
0.211
970323AG2-213 GEN
Solar/Wind Harmer
8.949
316118AC1-105 GEN
Solar/Wind Harmer
0.535
970301AG2-198 GEN
Solar/Wind Harmer
8.779
958211AF2-115 GEN
Solar/Wind Harmer
2.425
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.199
3147133PAMPLIN
Solar/Wind Harmer
0.159
3143526WINTERP
Solar/Wind Harmer
0.966
942751AE2-291 GEN
Solar/Wind Harmer
9.096
3146776BUCKING
Solar/Wind Harmer
0.647
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.372
316336AC2-165 C
Solar/Wind Harmer
6.804
316313AB2-026
Solar/Wind Harmer
0.083
971223AH1-071 GEN
Solar/Wind Harmer
1.425
316045AC1-158 PL2
Solar/Wind Helper
6.574
316450AC1-158 RIC
Solar/Wind Helper
0.548
316006AB2-029 C
Solar/Wind Helper
0.143
316411AF1-147_GEN1
Solar/Wind Helper
0.951
223401AF1-299 GEN
Solar/Wind Helper
0.348
223402AF1-300 C
Solar/Wind Helper
0.348
237006AB1-125 GEN
Solar/Wind Helper
0.105
3150921YORKTN3
50/50
8.613
3144216WINCHST
50/50
1.287
3151101ELIZAR3
50/50
30.933
3151161SURRY 1
50/50
12.681
3142416OLDCHRC
Solar/Wind Harmer
3.204
316075AC2-137 C
Solar/Wind Harmer
0.087
970293AG2-193 GEN
Solar/Wind Harmer
3.393
944581AF1-123 GEN
Solar/Wind Harmer
70.914
944601AF1-125 GEN
Solar/Wind Harmer
69.822
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151171GRAVELC
Adder
4.355
316017AA1-139 ULT1
Solar/Wind Harmer
0.166
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.58
961611AG1-000B GEN
Solar/Wind Harmer
8.261
316246AF1-032 C
Solar/Wind Harmer
0.137
972255AH1-712 GEN
Adder
157.324
315778AD1-151 GEN
Solar/Wind Harmer
24.517
316458AB2-190 GEN2
Solar/Wind Harmer
1.627
316321Z2-027
Solar/Wind Harmer
0.054
970133AG2-095 GEN
Solar/Wind Harmer
2.906
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.012
3141766HARMONY
Solar/Wind Harmer
3.989
970657AG2-426 GEN
Solar/Wind Harmer
6.706
3146626S HERTFORD
Solar/Wind Harmer
0.298
3141843SHACKLE
Adder
1.517
316203AE2-005 GEN
Solar/Wind Harmer
0
315813AE1-149 C
Solar/Wind Harmer
15.797
3145273HOLLAND
Solar/Wind Harmer
0.221
3141873WAN 176
Solar/Wind Harmer
5.225
3143096IRON208
Adder
1.224
3143096IRON208
Adder
1.2
3146376EDENTON
Solar/Wind Harmer
0.291
944011AF1-069 GEN
Solar/Wind Harmer
16.729
315735AD1-075 GEN1
Solar/Wind Harmer
0.788
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.267
3145963POPLR C
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.102
3145823KELFORD
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316011AB1-132 GEN
Solar/Wind Harmer
4.62
316181AB2-040 GEN
Solar/Wind Harmer
0.36
3150861SPRUNCD
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
1.004
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
316212AC1-099_GEN
Solar/Wind Harmer
1.275
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315722AD1-056 GEN
Solar/Wind Harmer
8.274
3150351NORNECKC2
Adder
2.387
316478AD1-087 GEN
Solar/Wind Harmer
0.815
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.174
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.35
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.459
964241AG1-285 GEN
Solar/Wind Harmer
14.365
970257AG2-171 GEN
Solar/Wind Harmer
6.712
971775AH1-396 GEN
Solar/Wind Harmer
0.336
959311AF2-222 GEN
Solar/Wind Harmer
18.544
971781AH1-399 GEN
Solar/Wind Harmer
0.272
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.626
316222AC1-221 GEN
Solar/Wind Harmer
0.794
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.376
971683AH1-343 GEN
Solar/Wind Harmer
7.057
3146926FARMVIL
Solar/Wind Harmer
0.11
316223AC1-118
Solar/Wind Harmer
0.125
3141906WESTMOR
Solar/Wind Harmer
0.07
316123AC1-075 GEN
Solar/Wind Harmer
0.233
3146776BUCKING
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
4.79
3151861LOWMORA
Adder
1.473
3147312GRETNA
Solar/Wind Harmer
0.027
3148013FISHERV
Solar/Wind Harmer
0.135
3143336POWHATN
Solar/Wind Harmer
2.027
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.102
270494AE1-108_GEN
Solar/Wind Harmer
1.538
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.412
3141196NOKESVL
Solar/Wind Helper
1.219
227287AC2-120 GEN
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.593
23777801MSM_W1-116
Solar/Wind Helper
0.097
3132273ORANGE
Solar/Wind Helper
0.045
971285AH1-108 GEN
Adder
1.896
3145796HORNRTN
Solar/Wind Harmer
0.803
3145796HORNRTN
Solar/Wind Harmer
0.1
316210AC1-098 GEN
Solar/Wind Harmer
2.286
316274AC1-208 GEN
Solar/Wind Harmer
1.261
3145746EVERETS
Solar/Wind Harmer
0.971
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957861AF2-080 GEN
Solar/Wind Harmer
10.316
316327AA2-057 GEN
Solar/Wind Harmer
0.352
970831AG2-522 GEN
Solar/Wind Harmer
10.103
3141813NORNECK
Solar/Wind Harmer
0.235
316486AD2-202 GEN
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
3144303KENBRDG
Solar/Wind Harmer
0.168
3147173SINAI
Solar/Wind Harmer
0.206
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
12.403
970681AG2-440 GEN
Solar/Wind Harmer
8.232
946301AF1-294 GEN
Solar/Wind Harmer
3.988
961791AG1-021 GEN
Solar/Wind Harmer
1.94
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.577
971283AH1-107 GEN
Solar/Wind Harmer
2.577
971845AH1-439 GEN
Solar/Wind Harmer
7.42
270197AD1-017 GEN1
Solar/Wind Harmer
0.905
3148463FAIRFLD
Solar/Wind Harmer
0.137
3151881LOWMORC
Adder
1.462
3151881LOWMORC
Adder
1.439
3151861LOWMORA
Adder
1.416
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.767
316258AE1-075 C
Solar/Wind Harmer
0.1
270069AE2-166 C O1
Solar/Wind Harmer
5.596
316164AC1-076 GEN
Solar/Wind Helper
1.581
315651AD1-115 GEN
Solar/Wind Helper
0.988
226929AD2-058 GEN
Solar/Wind Helper
0.113
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.056
23779801AA1-109
Solar/Wind Helper
0.162
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
3152331SURRY 2
50/50
13.811
3150981CHESPKA
50/50
4.157
315975AC1-164 GENB
Solar/Wind Harmer
0.103
3142416OLDCHRC
Solar/Wind Harmer
0.859
3142416OLDCHRC
Solar/Wind Harmer
0.329
315773AC2-141 GEN
Solar/Wind Harmer
11.798
971317AH1-138 GEN
Solar/Wind Harmer
2.407
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.166
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.056
3145336SMITFLD
Solar/Wind Harmer
1.249
3151171GRAVELC
Adder
3.312
316072AD1-144
Solar/Wind Harmer
0.11
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.246
319010AE1-072 C
Solar/Wind Harmer
1.543
944631AF1-128 GEN
Adder
146.631
972277AH1-723 GEN
Adder
183.33
971069AG2-661 GEN
Solar/Wind Harmer
5.448
316132AB2-190 GEN1
Solar/Wind Harmer
1.627
316093AE2-104_GEN
Solar/Wind Harmer
5.119
3146516WINFALL
Solar/Wind Harmer
0.975
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.198
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.42
316381AD1-082 GEN
Solar/Wind Harmer
0.302
971777AH1-397 GEN
Solar/Wind Harmer
0.784
315671AE2-027_GEN
Solar/Wind Harmer
0.002
940641AE2-051 GEN
Solar/Wind Harmer
23.504
3143096IRON208
Adder
1.224
3130156CHOWAN
Solar/Wind Harmer
0.291
315816AE2-034 GEN
Solar/Wind Harmer
1.211
3145663CRESWEL
Solar/Wind Harmer
0.794
971163AH1-040 GEN
Solar/Wind Harmer
22.704
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
941031AE2-094 GEN
Solar/Wind Harmer
51.201
315737AD1-076 GEN
Solar/Wind Harmer
3.552
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.827
3145893MURPHYS
Solar/Wind Harmer
1.077
3145893MURPHYS
Solar/Wind Harmer
1.197
3156021HOLLOMANSOL
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.264
3145963POPLR C
Solar/Wind Harmer
0.262
316023GEN1_S
Solar/Wind Harmer
0.583
3146263WOODLND
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
9.241
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3145823KELFORD
Solar/Wind Harmer
0.258
970087AG2-069 GEN
Solar/Wind Harmer
20.564
962861AG1-135 GEN
Solar/Wind Harmer
8.162
960081AF2-299 GEN
Solar/Wind Harmer
2.444
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
8.351
3150851SPRUNCC
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
0.828
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
3141726DUNNSVL
Solar/Wind Harmer
0.977
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.003
3147043LAWRENC
Adder
2.204
316494AC1-189 GEN
Solar/Wind Harmer
0.808
3150351NORNECKC2
Adder
2.348
315693AD1-088 GEN
Solar/Wind Harmer
11.298
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.045
316129AC1-054 GEN
Solar/Wind Harmer
0.877
3146233WITAKRS
Solar/Wind Harmer
0.931
971065AG2-659 GEN
Solar/Wind Harmer
9.952
316359AB2-059 GEN
Solar/Wind Harmer
0.816
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
3142053HEARTS
Solar/Wind Harmer
0.405
316131AB2-060 GEN
Solar/Wind Harmer
0.678
970401AG2-262 GEN
Solar/Wind Harmer
1.241
315785AD2-033 C
Solar/Wind Harmer
1.709
316034AC1-036 C
Solar/Wind Harmer
0.014
316337AD2-073 GEN
Solar/Wind Harmer
0.178
970685AG2-442 GEN
Solar/Wind Harmer
15.239
971563AH1-280 GEN
Solar/Wind Harmer
2.155
3144293JTRSVLE
Adder
0.482
3144293JTRSVLE
Adder
0.381
3143526WINTERP
Solar/Wind Harmer
0.966
3146926FARMVIL
Solar/Wind Harmer
0.11
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.386
3147123OTTER R
Solar/Wind Harmer
0.085
3147312GRETNA
Solar/Wind Harmer
0.108
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.336
970937AG2-583 GEN
Solar/Wind Harmer
8.26
3143336POWHATN
Solar/Wind Harmer
2.385
3143226MDLTHAN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.42
3147623JAMES R
Solar/Wind Harmer
0.309
972135AH1-637 GEN
Solar/Wind Harmer
1.094
270030AE2-140 GEN
Solar/Wind Harmer
13.071
962751AG1-124 GEN
Solar/Wind Harmer
5.382
316447AC1-158 HLD
Solar/Wind Helper
4.521
316044AC1-158 PL1
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.951
3147666LOUISA
Solar/Wind Helper
1.032
316192AB2-158 GEN
Solar/Wind Helper
1.7
LAGNLTFEXP_LAGN->PJM
CLTF
12.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.213
NYPJM->LTFIMP_NY
CLTF
4.065
LGEELTFEXP_LGEE->PJM
CLTF
2.637
TVALTFEXP_TVA->PJM
CLTF
6.406
WECLTFEXP_WEC->PJM
CLTF
1.334
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.11
CPLELTFEXP_CPLE->PJM
CLTF
15.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.32
MECLTFEXP_MEC->PJM
CLTF
6.832
SIGELTFEXP_SIGE->PJM
CLTF
0.211

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.7 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4464.82
MW Contribution:
7.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152191CUNINGD
50/50
5.572
972255AH1-712 GEN
50/50
168.651
3142416OLDCHRC
Solar/Wind Harmer
3.111
316075AC2-137 C
Solar/Wind Harmer
0.083
970293AG2-193 GEN
Solar/Wind Harmer
3.249
316473AC1-191 GEN
Solar/Wind Harmer
1.005
3142946ENON
Solar/Wind Harmer
0.098
3143096IRON208
Adder
1.179
3143096IRON208
Adder
1.155
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.848
3144216WINCHST
Adder
1.021
3141766HARMONY
Solar/Wind Harmer
3.609
3141843SHACKLE
Adder
1.37
970133AG2-095 GEN
Solar/Wind Harmer
2.573
316203AE2-005 GEN
Solar/Wind Harmer
0
3142296MT RD221
50/50
1.09
3152181CUNINGC
50/50
2.56
3152171CUNINGB
50/50
2.409
3152161CUNINGA
50/50
2.396
972193AH1-681 GEN
50/50
7.535
3150691DARBY 3
50/50
22.92
3150701DARBY 4
50/50
22.867
3150681DARBY 2
50/50
22.84
3150671DARBY 1
50/50
22.813
3142366NRTHEST
50/50
1.032
316312AB1-027
Solar/Wind Harmer
0.571
315976AC1-164 GENA
Solar/Wind Harmer
3.257
316169AC1-164_GENC
Solar/Wind Harmer
2.815
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
124.25
316294AC1-161 GEN
Solar/Wind Harmer
4.34
3150991CHESPKB
Adder
2.566
3150991CHESPKB
Adder
2.504
3145506HICKORY
Solar/Wind Harmer
0.969
3145506HICKORY
Solar/Wind Harmer
0.581
3145506HICKORY
Solar/Wind Harmer
0.145
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316388AE2-253 GEN
Solar/Wind Harmer
0.75
3137176SLIGO L2192
Solar/Wind Harmer
0.956
3146456SLIGO L269
Solar/Wind Harmer
4.248
3130086AYDLETT
Solar/Wind Harmer
0.958
316349AD2-085 GEN
Solar/Wind Harmer
0.159
315835AF2-110_GEN
Solar/Wind Harmer
1.625
3146386ELIZ CT
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146376EDENTON
Solar/Wind Harmer
0.993
3146376EDENTON
Solar/Wind Harmer
0.993
315742AE1-103 GEN
Solar/Wind Harmer
3.329
972189AH1-679 GEN
Adder
3.724
315614AA2-178 GEN
Solar/Wind Harmer
1.231
3143526WINTERP
Solar/Wind Harmer
1.123
3150341NORNECKC1
Adder
2.251
3150341NORNECKC1
Adder
2.233
316065AD1-022 GEN
Solar/Wind Harmer
9.567
3145893MURPHYS
Solar/Wind Harmer
1.355
3145893MURPHYS
Solar/Wind Harmer
0.364
3144356SAPONY
Solar/Wind Harmer
1.694
316315AB2-025 C
Solar/Wind Harmer
0.162
3146173TUNIS
Solar/Wind Harmer
0.2
3146173TUNIS
Solar/Wind Harmer
0.2
316140AB2-099
Solar/Wind Harmer
0.071
316365GEN2_N
Solar/Wind Harmer
0.427
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.113
962571AG1-106 GEN
Solar/Wind Harmer
2.664
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
313506AB2-031 GEN
Solar/Wind Harmer
0.569
3145593CAROLNA
Solar/Wind Harmer
0.185
3145593CAROLNA
Solar/Wind Harmer
0.185
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.28
3145783HORNRTN
Solar/Wind Harmer
2.624
3145783HORNRTN
Solar/Wind Harmer
0.82
3145783HORNRTN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.553
971223AH1-071 GEN
Solar/Wind Harmer
1.934
316005AA1-067
Solar/Wind Harmer
0.193
315724AD1-057 GEN
Solar/Wind Harmer
3.373
972185AH1-677 GEN
Adder
9.672
3145493TOT1
Solar/Wind Harmer
0.399
3145453TOT5
Solar/Wind Harmer
0.239
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.872
970933AG2-581 GEN
Solar/Wind Harmer
13.555
961601AG1-000A GEN
Solar/Wind Harmer
2.976
316049AB1-081 GEN
Solar/Wind Harmer
0.951
316263AC1-034 GEN
Solar/Wind Harmer
6.355
316313AB2-026
Solar/Wind Harmer
0.101
970099AG2-077 GEN
Solar/Wind Harmer
17.361
316336AC2-165 C
Solar/Wind Harmer
8.008
970323AG2-213 GEN
Solar/Wind Harmer
6.629
970301AG2-198 GEN
Solar/Wind Harmer
6.539
958211AF2-115 GEN
Solar/Wind Harmer
1.837
3144293JTRSVLE
Adder
0.366
3147133PAMPLIN
Solar/Wind Harmer
0.152
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.294
964791AG1-342 GEN
Solar/Wind Harmer
2.897
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
316118AC1-105 GEN
Solar/Wind Harmer
0.38
3146776BUCKING
Solar/Wind Harmer
0.568
3146776BUCKING
Solar/Wind Harmer
0.046
942751AE2-291 GEN
Solar/Wind Harmer
6.832
316045AC1-158 PL2
Solar/Wind Helper
5.278
316450AC1-158 RIC
Solar/Wind Helper
0.44
316006AB2-029 C
Solar/Wind Helper
0.118
316411AF1-147_GEN1
Solar/Wind Helper
0.803
316159AE1-175 C
Solar/Wind Harmer
0.245
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.942
3141873WAN 176
Solar/Wind Harmer
0.053
315697AD1-025 GEN
Solar/Wind Harmer
0.282
3151201GRAVEL4
Adder
18.738
3151221GRAVEL6
Adder
18.716
3151191GRAVEL3
Adder
18.501
3151211GRAVEL5
Adder
18.501
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.824
971285AH1-108 GEN
Adder
1.908
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.45
3151091ELIZAR2
Adder
22.06
316316AC1-027 C
Solar/Wind Harmer
0.232
957871AF2-081 GEN
Solar/Wind Harmer
11.986
3146406KITTY HAWK
Solar/Wind Harmer
0.03
970657AG2-426 GEN
Solar/Wind Harmer
1.755
316311AC2-079 GEN
Solar/Wind Harmer
6.826
313526AB2-022
Solar/Wind Harmer
0.126
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
3146396TANGLEW
Solar/Wind Harmer
0.648
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.909
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
2.998
971283AH1-107 GEN
Solar/Wind Harmer
2.998
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.197
315733AD1-074 GEN2
Solar/Wind Harmer
1.197
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.709
3145893MURPHYS
Solar/Wind Harmer
0.547
3145893MURPHYS
Solar/Wind Harmer
0.202
315814AE2-033 C
Solar/Wind Harmer
15.978
316463AE2-346 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.396
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
316426AA2-053 GEN
Solar/Wind Harmer
0.628
315652AC1-086 GEN
Solar/Wind Harmer
20.595
3146033SCOT NK
Solar/Wind Harmer
0.747
3137643SOCKMAN
Solar/Wind Harmer
0.741
3145796HORNRTN
Solar/Wind Harmer
0.59
3145796HORNRTN
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
1.685
3145746EVERETS
Solar/Wind Harmer
0.719
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
316274AC1-208 GEN
Solar/Wind Harmer
0.927
957861AF2-080 GEN
Solar/Wind Harmer
7.595
970533AG2-339 GEN
Solar/Wind Harmer
13.243
316327AA2-057 GEN
Solar/Wind Harmer
0.257
970673AG2-436 GEN
Solar/Wind Harmer
21.668
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.442
970831AG2-522 GEN
Solar/Wind Harmer
7.302
970085AG2-068 GEN
Solar/Wind Harmer
8.84
970581AG2-369 GEN
Solar/Wind Harmer
7.602
316258AE1-075 C
Solar/Wind Harmer
0.122
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
9.293
970681AG2-440 GEN
Solar/Wind Harmer
6.168
946301AF1-294 GEN
Solar/Wind Harmer
3.021
961791AG1-021 GEN
Solar/Wind Harmer
1.47
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
971845AH1-439 GEN
Solar/Wind Harmer
6.462
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.08
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.48
3151881LOWMORC
Adder
1.457
3151861LOWMORA
Adder
1.433
972205AH1-687 GEN
Adder
5.773
316164AC1-076 GEN
Solar/Wind Helper
1.298
226929AD2-058 GEN
Solar/Wind Helper
0.097
315651AD1-115 GEN
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
972277AH1-723 GEN
50/50
196.529
3142416OLDCHRC
Solar/Wind Harmer
0.834
3142416OLDCHRC
Solar/Wind Harmer
0.32
315975AC1-164 GENB
Solar/Wind Harmer
0.096
944631AF1-128 GEN
Adder
136.219
3143096IRON208
Adder
1.179
971317AH1-138 GEN
Solar/Wind Harmer
2.061
3142433PROV 92
Solar/Wind Harmer
1.097
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.708
316132AB2-190 GEN1
Solar/Wind Harmer
1.413
971069AG2-661 GEN
Solar/Wind Harmer
4.681
961611AG1-000B GEN
Solar/Wind Harmer
13.596
3151171GRAVELC
Adder
2.738
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3150851SPRUNCC
Adder
1.166
3145336SMITFLD
Solar/Wind Harmer
1.01
315773AC2-141 GEN
Solar/Wind Harmer
9.17
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.044
3150981CHESPKA
Adder
3.059
316072AD1-144
Solar/Wind Harmer
0.087
944591AF1-124 GEN
Solar/Wind Harmer
55.091
3146456SLIGO L269
Solar/Wind Harmer
0.24
319010AE1-072 C
Solar/Wind Harmer
1.196
316381AD1-082 GEN
Solar/Wind Harmer
0.242
316093AE2-104_GEN
Solar/Wind Harmer
3.983
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.397
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.574
3141726DUNNSVL
Solar/Wind Harmer
0.893
3130156CHOWAN
Solar/Wind Harmer
0.223
315816AE2-034 GEN
Solar/Wind Harmer
0.923
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.314
3143526WINTERP
Solar/Wind Harmer
1.123
3150351NORNECKC2
Adder
2.143
315737AD1-076 GEN
Solar/Wind Harmer
2.694
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.405
939411AE1-173 GEN
Solar/Wind Harmer
87.534
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
0.901
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
3146173TUNIS
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
315607AA1-063A GEN
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
0.192
940641AE2-051 GEN
Solar/Wind Harmer
15.404
316023GEN1_S
Solar/Wind Harmer
0.427
316337AD2-073 GEN
Solar/Wind Harmer
0.164
960081AF2-299 GEN
Solar/Wind Harmer
1.787
3146293MARTNCO
Solar/Wind Harmer
0.172
3145783HORNRTN
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.184
3143226MDLTHAN
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Adder
1.606
316494AC1-189 GEN
Solar/Wind Harmer
0.595
941031AE2-094 GEN
Solar/Wind Harmer
32.283
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.765
3146233WITAKRS
Solar/Wind Harmer
0.679
316129AC1-054 GEN
Solar/Wind Harmer
0.632
971065AG2-659 GEN
Solar/Wind Harmer
7.161
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.594
3142053HEARTS
Solar/Wind Harmer
0.294
970919AG2-571 GEN
Solar/Wind Harmer
5.941
970087AG2-069 GEN
Solar/Wind Harmer
13.26
3143336POWHATN
Solar/Wind Harmer
2.896
957481AF2-042 GEN
Solar/Wind Harmer
43.403
315693AD1-088 GEN
Solar/Wind Harmer
7.714
316131AB2-060 GEN
Solar/Wind Harmer
0.491
315785AD2-033 C
Solar/Wind Harmer
1.26
316034AC1-036 C
Solar/Wind Harmer
0.01
970685AG2-442 GEN
Solar/Wind Harmer
11.476
971563AH1-280 GEN
Solar/Wind Harmer
1.633
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.289
970401AG2-262 GEN
Solar/Wind Harmer
0.885
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.933
3146776BUCKING
Solar/Wind Harmer
0.057
971377AH1-170 GEN
Solar/Wind Harmer
1.418
3147623JAMES R
Solar/Wind Harmer
0.308
972135AH1-637 GEN
Solar/Wind Harmer
1.023
970223AG2-152 GEN
Solar/Wind Harmer
7.914
316447AC1-158 HLD
Solar/Wind Helper
3.629
316044AC1-158 PL1
Solar/Wind Helper
1.649
316415AF1-147_GEN2
Solar/Wind Helper
0.803
316458AB2-190 GEN2
Solar/Wind Harmer
1.413
3141873WAN 176
Solar/Wind Harmer
4.682
315778AD1-151 GEN
Solar/Wind Harmer
21.066
961611AG1-000B GEN
Solar/Wind Harmer
6.913
3151171GRAVELC
Adder
3.601
3150861SPRUNCD
Adder
1.166
3145336SMITFLD
Solar/Wind Harmer
0.101
3144536CHRHLND
Solar/Wind Harmer
0.037
3151101ELIZAR3
Adder
22.737
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.896
944601AF1-125 GEN
Solar/Wind Harmer
54.051
316017AA1-139 ULT1
Solar/Wind Harmer
0.128
315813AE1-149 C
Solar/Wind Harmer
12.81
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.775
316246AF1-032 C
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
5.364
316321Z2-027
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3145273HOLLAND
Solar/Wind Harmer
0.17
3146376EDENTON
Solar/Wind Harmer
0.223
3150351NORNECKC2
Adder
2.179
315735AD1-075 GEN1
Solar/Wind Harmer
0.597
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.206
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.339
3145893MURPHYS
Solar/Wind Harmer
0.202
3146173TUNIS
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
316011AB1-132 GEN
Solar/Wind Harmer
3.396
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
0.737
3145796HORNRTN
Solar/Wind Harmer
0.184
316212AC1-099_GEN
Solar/Wind Harmer
0.94
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
944011AF1-069 GEN
Solar/Wind Harmer
10.548
315722AD1-056 GEN
Solar/Wind Harmer
6.047
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.857
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.112
961601AG1-000A GEN
Solar/Wind Harmer
11.904
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.334
970917AG2-570 GEN
Solar/Wind Harmer
14.853
3143336POWHATN
Solar/Wind Harmer
2.461
316223AC1-118
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.551
964241AG1-285 GEN
Solar/Wind Harmer
10.47
970257AG2-171 GEN
Solar/Wind Harmer
4.971
971775AH1-396 GEN
Solar/Wind Harmer
0.249
959311AF2-222 GEN
Solar/Wind Harmer
13.78
3144293JTRSVLE
Adder
0.366
3147133PAMPLIN
Solar/Wind Harmer
0.478
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.089
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.139
3151861LOWMORA
Adder
1.492
971683AH1-343 GEN
Solar/Wind Harmer
5.088
316222AC1-221 GEN
Solar/Wind Harmer
0.561
972003AH1-546 GEN
Solar/Wind Harmer
4.713
316283AC2-100 C
Solar/Wind Harmer
0.265
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.092
316123AC1-075 GEN
Solar/Wind Harmer
0.173
270494AE1-108_GEN
Solar/Wind Harmer
1.495
3141196NOKESVL
Solar/Wind Helper
1.032
227287AC2-120 GEN
Solar/Wind Helper
0.329
226910AB2-157 C
Solar/Wind Helper
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
9.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.968
NYPJM->LTFIMP_NY
CLTF
3.384
LGEELTFEXP_LGEE->PJM
CLTF
2.155
TVALTFEXP_TVA->PJM
CLTF
4.966
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CPLELTFEXP_CPLE->PJM
CLTF
10.775
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.412
MECLTFEXP_MEC->PJM
CLTF
5.481
SIGELTFEXP_SIGE->PJM
CLTF
0.171

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.05 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4723.52
MW Contribution:
7.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.171
972195AH1-682 GEN
50/50
5.016
972189AH1-679 GEN
50/50
4.649
3142296MT RD221
50/50
0.869
3142366NRTHEST
50/50
0.874
3150691DARBY 3
50/50
19.218
315673AE1-157 GEN
Solar/Wind Harmer
18.436
316312AB1-027
Solar/Wind Harmer
0.452
3150701DARBY 4
Adder
18.069
3150681DARBY 2
Adder
18.048
3150671DARBY 1
Adder
18.027
3143526WINTERP
Solar/Wind Harmer
1.293
966871AG1-558 GEN
Solar/Wind Harmer
0.287
315976AC1-164 GENA
Solar/Wind Harmer
2.606
316169AC1-164_GENC
Solar/Wind Harmer
2.252
971223AH1-071 GEN
Solar/Wind Harmer
2.642
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.711
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.132
3150991CHESPKB
Adder
2.479
3150991CHESPKB
Adder
2.42
3145506HICKORY
Solar/Wind Harmer
0.941
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
316156AD2-030 GEN
Solar/Wind Harmer
0.172
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316388AE2-253 GEN
Solar/Wind Harmer
0.73
316349AD2-085 GEN
Solar/Wind Harmer
0.156
3137176SLIGO L2192
Solar/Wind Harmer
0.93
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
315835AF2-110_GEN
Solar/Wind Harmer
1.593
3146386ELIZ CT
Solar/Wind Harmer
0.231
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.892
316315AB2-025 C
Solar/Wind Harmer
0.181
315742AE1-103 GEN
Solar/Wind Harmer
3.33
3146376EDENTON
Solar/Wind Harmer
0.986
3146376EDENTON
Solar/Wind Harmer
0.986
972185AH1-677 GEN
Adder
12.347
972187AH1-678 GEN
Adder
6.195
315614AA2-178 GEN
Solar/Wind Harmer
1.234
3150341NORNECKC1
Adder
2.268
3150341NORNECKC1
Adder
2.25
970933AG2-581 GEN
Solar/Wind Harmer
17.123
316313AB2-026
Solar/Wind Harmer
0.132
316065AD1-022 GEN
Solar/Wind Harmer
9.708
316365GEN2_N
Solar/Wind Harmer
0.465
3145893MURPHYS
Solar/Wind Harmer
1.399
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316140AB2-099
Solar/Wind Harmer
0.073
316336AC2-165 C
Solar/Wind Harmer
10.238
313506AB2-031 GEN
Solar/Wind Harmer
0.618
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
962571AG1-106 GEN
Solar/Wind Harmer
2.858
970099AG2-077 GEN
Solar/Wind Harmer
21.401
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.518
3145783HORNRTN
Solar/Wind Harmer
2.815
3145783HORNRTN
Solar/Wind Harmer
0.88
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.593
3145933PARMELE
Solar/Wind Harmer
0.386
3145933PARMELE
Solar/Wind Harmer
0.193
316005AA1-067
Solar/Wind Harmer
0.202
315724AD1-057 GEN
Solar/Wind Harmer
3.617
970301AG2-198 GEN
Solar/Wind Harmer
7.87
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.254
3145603CNETO
Solar/Wind Harmer
0.17
970323AG2-213 GEN
Solar/Wind Harmer
7.682
961601AG1-000A GEN
Solar/Wind Harmer
3.189
316049AB1-081 GEN
Solar/Wind Harmer
1.02
316263AC1-034 GEN
Solar/Wind Harmer
6.813
958211AF2-115 GEN
Solar/Wind Harmer
2.144
3144293JTRSVLE
Adder
0.427
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
962561AG1-105 GEN
Solar/Wind Harmer
8.343
964791AG1-342 GEN
Solar/Wind Harmer
3.31
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
316118AC1-105 GEN
Solar/Wind Harmer
0.433
3146776BUCKING
Solar/Wind Harmer
0.668
3146776BUCKING
Solar/Wind Harmer
0.054
972193AH1-681 GEN
Adder
3.811
942751AE2-291 GEN
Solar/Wind Harmer
6.973
316045AC1-158 PL2
Solar/Wind Helper
7.094
316450AC1-158 RIC
Solar/Wind Helper
0.591
316006AB2-029 C
Solar/Wind Helper
0.146
316411AF1-147_GEN1
Solar/Wind Helper
0.804
3152261N ANNA2
50/50
14.634
3150401LDYSMT4
50/50
38.243
3150371LDYSMT1
50/50
36.953
315051AA1-145 CT1
50/50
2.07
3142416OLDCHRC
Solar/Wind Harmer
2.462
970293AG2-193 GEN
Solar/Wind Harmer
2.675
316075AC2-137 C
Solar/Wind Harmer
0.067
3143096IRON208
Adder
1.043
3143096IRON208
Adder
1.023
3150861SPRUNCD
Adder
1.146
316473AC1-191 GEN
Solar/Wind Harmer
0.838
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.346
316458AB2-190 GEN2
Solar/Wind Harmer
1.296
315778AD1-151 GEN
Solar/Wind Harmer
19.38
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3150921YORKTN3
Adder
6.048
3144216WINCHST
Adder
0.907
961611AG1-000B GEN
Solar/Wind Harmer
6.412
3151171GRAVELC
Adder
3.352
3145336SMITFLD
Solar/Wind Harmer
0.095
315813AE1-149 C
Solar/Wind Harmer
12.72
3144536CHRHLND
Solar/Wind Harmer
0.035
944581AF1-123 GEN
Solar/Wind Harmer
53.298
944601AF1-125 GEN
Solar/Wind Harmer
52.477
3151101ELIZAR3
Adder
21.98
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.153
970657AG2-426 GEN
Solar/Wind Harmer
5.304
3141843SHACKLE
Adder
1.207
316203AE2-005 GEN
Solar/Wind Harmer
0
3141873WAN 176
Solar/Wind Harmer
4.17
316017AA1-139 ULT1
Solar/Wind Harmer
0.125
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
316246AF1-032 C
Solar/Wind Harmer
0.104
316321Z2-027
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.169
944011AF1-069 GEN
Solar/Wind Harmer
13.581
3146376EDENTON
Solar/Wind Harmer
0.222
3150351NORNECKC2
Adder
2.195
971781AH1-399 GEN
Solar/Wind Harmer
0.285
315735AD1-075 GEN1
Solar/Wind Harmer
0.604
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.196
3146206CASHIE
Solar/Wind Harmer
0.21
970917AG2-570 GEN
Solar/Wind Harmer
18.667
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.207
3146263WOODLND
Solar/Wind Harmer
0.203
3145963POPLR C
Solar/Wind Harmer
0.202
316181AB2-040 GEN
Solar/Wind Harmer
0.287
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
316011AB1-132 GEN
Solar/Wind Harmer
3.644
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.791
3145796HORNRTN
Solar/Wind Harmer
0.198
316223AC1-118
Solar/Wind Harmer
0.141
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.67
316212AC1-099_GEN
Solar/Wind Harmer
0.996
3145933PARMELE
Solar/Wind Harmer
0.193
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315722AD1-056 GEN
Solar/Wind Harmer
6.485
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.917
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.419
964241AG1-285 GEN
Solar/Wind Harmer
12.07
970257AG2-171 GEN
Solar/Wind Harmer
5.761
971775AH1-396 GEN
Solar/Wind Harmer
0.288
959311AF2-222 GEN
Solar/Wind Harmer
15.987
961601AG1-000A GEN
Solar/Wind Harmer
12.757
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
3144293JTRSVLE
Adder
0.427
3147133PAMPLIN
Solar/Wind Harmer
0.559
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.298
972003AH1-546 GEN
Solar/Wind Harmer
5.488
971683AH1-343 GEN
Solar/Wind Harmer
5.586
316222AC1-221 GEN
Solar/Wind Harmer
0.621
316283AC2-100 C
Solar/Wind Harmer
0.294
970221AG2-151 GEN
Solar/Wind Harmer
7.883
316123AC1-075 GEN
Solar/Wind Harmer
0.181
270494AE1-108_GEN
Solar/Wind Harmer
1.571
3150331BIRCHWDA
Adder
22.077
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.252
3150411LDYSMT5
50/50
38.362
3150381LDYSMT2
50/50
36.714
972213AH1-691 GEN
50/50
6.211
972215AH1-692 GEN
50/50
6.211
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
3.452
971283AH1-107 GEN
Solar/Wind Harmer
3.452
971285AH1-108 GEN
Adder
1.876
316159AE1-175 C
Solar/Wind Harmer
0.208
315697AD1-025 GEN
Solar/Wind Harmer
0.26
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3151201GRAVEL4
Adder
17.442
3151221GRAVEL6
Adder
17.422
3151191GRAVEL3
Adder
17.222
3151211GRAVEL5
Adder
17.222
971445AH1-216 GEN
Solar/Wind Harmer
16.803
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.943
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3151081ELIZAR1
Adder
21.702
3151091ELIZAR2
Adder
21.325
970657AG2-426 GEN
Solar/Wind Harmer
1.736
970189AG2-124 GEN
Solar/Wind Harmer
7.002
316316AC1-027 C
Solar/Wind Harmer
0.225
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.661
316311AC2-079 GEN
Solar/Wind Harmer
6.716
3146406KITTY HAWK
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.123
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.23
3146486SUNBURY
Solar/Wind Harmer
0.23
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
970533AG2-339 GEN
Solar/Wind Harmer
17.052
315814AE2-033 C
Solar/Wind Harmer
17.827
970673AG2-436 GEN
Solar/Wind Harmer
27.806
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
34.913
3141813NORNECK
Solar/Wind Harmer
0.216
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
316258AE1-075 C
Solar/Wind Harmer
0.158
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.841
3145893MURPHYS
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
0.209
970085AG2-068 GEN
Solar/Wind Harmer
11.063
970581AG2-369 GEN
Solar/Wind Harmer
9.514
316463AE2-346 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.41
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.204
315652AC1-086 GEN
Solar/Wind Harmer
22.096
3137643SOCKMAN
Solar/Wind Harmer
0.799
316426AA2-053 GEN
Solar/Wind Harmer
0.669
3145796HORNRTN
Solar/Wind Harmer
0.633
3145796HORNRTN
Solar/Wind Harmer
0.079
3146033SCOT NK
Solar/Wind Harmer
0.786
316486AD2-202 GEN
Solar/Wind Harmer
0.197
316210AC1-098 GEN
Solar/Wind Harmer
1.786
316274AC1-208 GEN
Solar/Wind Harmer
0.988
970831AG2-522 GEN
Solar/Wind Harmer
8.11
3145746EVERETS
Solar/Wind Harmer
0.751
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.275
957861AF2-080 GEN
Solar/Wind Harmer
8.003
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
10.809
970681AG2-440 GEN
Solar/Wind Harmer
7.174
946301AF1-294 GEN
Solar/Wind Harmer
3.526
961791AG1-021 GEN
Solar/Wind Harmer
1.715
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.612
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.712
316164AC1-076 GEN
Solar/Wind Helper
1.956
315651AD1-115 GEN
Solar/Wind Helper
0.968
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
14.627
972197AH1-683 GEN
50/50
5.972
972219AH1-694 GEN
50/50
4.3
315052AA1-145 CT2
50/50
2.083
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.66
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.043
3143526WINTERP
Solar/Wind Harmer
1.293
3150851SPRUNCC
Adder
1.146
3142543TWELFTH
Solar/Wind Harmer
0.024
315975AC1-164 GENB
Solar/Wind Harmer
0.077
3143226MDLTHAN
Solar/Wind Harmer
0.247
944631AF1-128 GEN
Adder
117.82
316132AB2-190 GEN1
Solar/Wind Harmer
1.296
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.307
971317AH1-138 GEN
Solar/Wind Harmer
1.798
3142433PROV 92
Solar/Wind Harmer
0.962
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3138126ROCKLANDING
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
12.609
3151171GRAVELC
Adder
2.549
315773AC2-141 GEN
Solar/Wind Harmer
8.73
3145336SMITFLD
Solar/Wind Harmer
0.954
944591AF1-124 GEN
Solar/Wind Harmer
53.488
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.042
3150981CHESPKA
Adder
2.955
316381AD1-082 GEN
Solar/Wind Harmer
0.24
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.624
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
100.161
940641AE2-051 GEN
Solar/Wind Harmer
18.753
3146456SLIGO L269
Solar/Wind Harmer
0.234
319010AE1-072 C
Solar/Wind Harmer
1.165
316093AE2-104_GEN
Solar/Wind Harmer
3.905
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.739
3146516WINFALL
Solar/Wind Harmer
0.228
941031AE2-094 GEN
Solar/Wind Harmer
41.566
962861AG1-135 GEN
Solar/Wind Harmer
7.123
3130156CHOWAN
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.335
3141726DUNNSVL
Solar/Wind Harmer
0.877
315816AE2-034 GEN
Solar/Wind Harmer
0.925
3145663CRESWEL
Solar/Wind Harmer
0.607
971163AH1-040 GEN
Solar/Wind Harmer
17.349
3150351NORNECKC2
Adder
2.159
315737AD1-076 GEN
Solar/Wind Harmer
2.723
3143336POWHATN
Solar/Wind Harmer
3.761
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.48
970919AG2-571 GEN
Solar/Wind Harmer
7.467
316023GEN1_S
Solar/Wind Harmer
0.465
3145893MURPHYS
Solar/Wind Harmer
0.836
3145893MURPHYS
Solar/Wind Harmer
0.929
316337AD2-073 GEN
Solar/Wind Harmer
0.179
970087AG2-069 GEN
Solar/Wind Harmer
16.594
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.93
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.957
315607AA1-063A GEN
Solar/Wind Harmer
0.41
3146263WOODLND
Solar/Wind Harmer
0.203
3145963POPLR C
Solar/Wind Harmer
0.202
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.504
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.652
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.783
315693AD1-088 GEN
Solar/Wind Harmer
9.436
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.705
971065AG2-659 GEN
Solar/Wind Harmer
8.02
316494AC1-189 GEN
Solar/Wind Harmer
0.627
972135AH1-637 GEN
Solar/Wind Harmer
1.561
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.813
3146233WITAKRS
Solar/Wind Harmer
0.727
3147666LOUISA
Solar/Wind Harmer
0.728
316131AB2-060 GEN
Solar/Wind Harmer
0.565
315785AD2-033 C
Solar/Wind Harmer
1.458
316034AC1-036 C
Solar/Wind Harmer
0.012
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.637
3142053HEARTS
Solar/Wind Harmer
0.316
970685AG2-442 GEN
Solar/Wind Harmer
13.369
971563AH1-280 GEN
Solar/Wind Harmer
1.906
3144293JTRSVLE
Adder
0.427
3144293JTRSVLE
Adder
0.337
970937AG2-583 GEN
Solar/Wind Harmer
10.9
316192AB2-158 GEN
Solar/Wind Harmer
0.993
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.011
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.398
971377AH1-170 GEN
Solar/Wind Harmer
1.577
3147623JAMES R
Solar/Wind Harmer
0.343
316447AC1-158 HLD
Solar/Wind Helper
4.878
316044AC1-158 PL1
Solar/Wind Helper
2.217
316415AF1-147_GEN2
Solar/Wind Helper
0.804
LAGNLTFEXP_LAGN->PJM
CLTF
8.17
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.357
NYPJM->LTFIMP_NY
CLTF
3.219
LGEELTFEXP_LGEE->PJM
CLTF
1.371
TVALTFEXP_TVA->PJM
CLTF
4.141
WECLTFEXP_WEC->PJM
CLTF
0.664
CPLELTFEXP_CPLE->PJM
CLTF
11.555
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.156
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.099
MECLTFEXP_MEC->PJM
CLTF
3.718
SIGELTFEXP_SIGE->PJM
CLTF
0.113

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.79 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4672.2
MW Contribution:
6.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
37.279
972195AH1-682 GEN
50/50
4.899
972189AH1-679 GEN
50/50
4.517
3142296MT RD221
50/50
0.843
3142366NRTHEST
50/50
0.846
3150691DARBY 3
50/50
18.598
316045AC1-158 PL2
Solar/Wind Harmer
4.352
316450AC1-158 RIC
Solar/Wind Harmer
0.363
315673AE1-157 GEN
Solar/Wind Harmer
17.979
316312AB1-027
Solar/Wind Harmer
0.438
3150701DARBY 4
Adder
17.486
3150681DARBY 2
Adder
17.466
3150671DARBY 1
Adder
17.445
966871AG1-558 GEN
Solar/Wind Harmer
0.278
315976AC1-164 GENA
Solar/Wind Harmer
2.522
316169AC1-164_GENC
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.245
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.538
944641AF1-129 GEN
Adder
112.654
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
3.982
3150991CHESPKB
Adder
2.389
3150991CHESPKB
Adder
2.331
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3145506HICKORY
Solar/Wind Harmer
0.906
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.361
316388AE2-253 GEN
Solar/Wind Harmer
0.703
316349AD2-085 GEN
Solar/Wind Harmer
0.15
3137176SLIGO L2192
Solar/Wind Harmer
0.896
3146456SLIGO L269
Solar/Wind Harmer
3.984
3130086AYDLETT
Solar/Wind Harmer
0.899
315835AF2-110_GEN
Solar/Wind Harmer
1.535
3146386ELIZ CT
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.819
316315AB2-025 C
Solar/Wind Harmer
0.174
315742AE1-103 GEN
Solar/Wind Harmer
3.207
3146376EDENTON
Solar/Wind Harmer
0.95
3146376EDENTON
Solar/Wind Harmer
0.95
972185AH1-677 GEN
Adder
11.847
3150341NORNECKC1
Adder
2.194
3150341NORNECKC1
Adder
2.177
315614AA2-178 GEN
Solar/Wind Harmer
1.188
972187AH1-678 GEN
Adder
5.944
970933AG2-581 GEN
Solar/Wind Harmer
16.438
316313AB2-026
Solar/Wind Harmer
0.127
316065AD1-022 GEN
Solar/Wind Harmer
9.345
316365GEN2_N
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
1.346
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316140AB2-099
Solar/Wind Harmer
0.07
316336AC2-165 C
Solar/Wind Harmer
9.886
313506AB2-031 GEN
Solar/Wind Harmer
0.594
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
962571AG1-106 GEN
Solar/Wind Harmer
2.749
970099AG2-077 GEN
Solar/Wind Harmer
20.561
3145593CAROLNA
Solar/Wind Harmer
0.191
3145593CAROLNA
Solar/Wind Harmer
0.191
3145593CAROLNA
Solar/Wind Harmer
0.238
3145783HORNRTN
Solar/Wind Harmer
3.385
3145783HORNRTN
Solar/Wind Harmer
2.708
3145783HORNRTN
Solar/Wind Harmer
0.846
3145783HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.57
3145933PARMELE
Solar/Wind Harmer
0.371
3145933PARMELE
Solar/Wind Harmer
0.186
316005AA1-067
Solar/Wind Harmer
0.194
315724AD1-057 GEN
Solar/Wind Harmer
3.479
970301AG2-198 GEN
Solar/Wind Harmer
7.591
3145493TOT1
Solar/Wind Harmer
0.407
3145453TOT5
Solar/Wind Harmer
0.244
3145603CNETO
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.402
961601AG1-000A GEN
Solar/Wind Harmer
3.066
316049AB1-081 GEN
Solar/Wind Harmer
0.981
316263AC1-034 GEN
Solar/Wind Harmer
6.551
958211AF2-115 GEN
Solar/Wind Harmer
2.069
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
962561AG1-105 GEN
Solar/Wind Harmer
8.026
964791AG1-342 GEN
Solar/Wind Harmer
3.184
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
972193AH1-681 GEN
Adder
3.718
316118AC1-105 GEN
Solar/Wind Harmer
0.416
3146776BUCKING
Solar/Wind Harmer
0.648
3146776BUCKING
Solar/Wind Harmer
0.052
942751AE2-291 GEN
Solar/Wind Harmer
6.709
316006AB2-029 C
Solar/Wind Helper
0.121
316411AF1-147_GEN1
Solar/Wind Helper
0.789
3152261N ANNA2
50/50
13.712
3150401LDYSMT4
50/50
37.349
3150371LDYSMT1
50/50
36.089
315051AA1-145 CT1
50/50
2.012
3142416OLDCHRC
Solar/Wind Harmer
2.386
970293AG2-193 GEN
Solar/Wind Harmer
2.589
316075AC2-137 C
Solar/Wind Harmer
0.064
3143096IRON208
Adder
1.009
3143096IRON208
Adder
0.988
316473AC1-191 GEN
Solar/Wind Harmer
0.813
3150861SPRUNCD
Adder
1.106
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.265
316458AB2-190 GEN2
Solar/Wind Harmer
1.251
315778AD1-151 GEN
Solar/Wind Harmer
18.704
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3150921YORKTN3
Adder
5.839
3144216WINCHST
Adder
0.876
961611AG1-000B GEN
Solar/Wind Harmer
6.185
3151171GRAVELC
Adder
3.233
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.259
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.049
3141843SHACKLE
Adder
1.168
316203AE2-005 GEN
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
21.177
944581AF1-123 GEN
Solar/Wind Harmer
51.344
944601AF1-125 GEN
Solar/Wind Harmer
50.553
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.111
3141873WAN 176
Solar/Wind Harmer
4.032
316017AA1-139 ULT1
Solar/Wind Harmer
0.12
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.603
316246AF1-032 C
Solar/Wind Harmer
0.1
316321Z2-027
Solar/Wind Harmer
0.039
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
944011AF1-069 GEN
Solar/Wind Harmer
13.029
3146376EDENTON
Solar/Wind Harmer
0.213
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.124
315735AD1-075 GEN1
Solar/Wind Harmer
0.581
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.082
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.912
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.199
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
316181AB2-040 GEN
Solar/Wind Harmer
0.276
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.505
3145823KELFORD
Solar/Wind Harmer
0.193
316223AC1-118
Solar/Wind Harmer
0.136
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.761
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316212AC1-099_GEN
Solar/Wind Harmer
0.958
316478AD1-087 GEN
Solar/Wind Harmer
0.643
3145933PARMELE
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315722AD1-056 GEN
Solar/Wind Harmer
6.236
3147666LOUISA
Solar/Wind Harmer
0.411
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.882
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
964241AG1-285 GEN
Solar/Wind Harmer
11.623
970257AG2-171 GEN
Solar/Wind Harmer
5.552
971775AH1-396 GEN
Solar/Wind Harmer
0.278
959311AF2-222 GEN
Solar/Wind Harmer
15.408
961601AG1-000A GEN
Solar/Wind Harmer
12.265
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
3144293JTRSVLE
Adder
0.412
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.54
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.218
3146776BUCKING
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
5.342
971683AH1-343 GEN
Solar/Wind Harmer
5.372
316222AC1-221 GEN
Solar/Wind Harmer
0.597
316283AC2-100 C
Solar/Wind Harmer
0.282
970221AG2-151 GEN
Solar/Wind Harmer
7.681
316123AC1-075 GEN
Solar/Wind Harmer
0.174
270494AE1-108_GEN
Solar/Wind Harmer
1.529
3150331BIRCHWDA
Adder
21.423
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.226
3150411LDYSMT5
50/50
37.466
3150381LDYSMT2
50/50
35.856
972213AH1-691 GEN
50/50
6.065
972215AH1-692 GEN
50/50
6.065
971285AH1-108 GEN
Adder
1.81
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.322
971283AH1-107 GEN
Solar/Wind Harmer
3.322
316159AE1-175 C
Solar/Wind Harmer
0.201
315697AD1-025 GEN
Solar/Wind Harmer
0.251
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3151201GRAVEL4
Adder
16.824
3151221GRAVEL6
Adder
16.805
3151191GRAVEL3
Adder
16.611
3151211GRAVEL5
Adder
16.611
3143873LANEXA
Solar/Wind Harmer
0.138
971445AH1-216 GEN
Solar/Wind Harmer
16.201
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.909
970189AG2-124 GEN
Solar/Wind Harmer
6.771
3151081ELIZAR1
Adder
20.909
3151091ELIZAR2
Adder
20.546
970657AG2-426 GEN
Solar/Wind Harmer
1.673
316316AC1-027 C
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.233
316311AC2-079 GEN
Solar/Wind Harmer
6.47
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3141913WHIT STONE
Solar/Wind Harmer
0.224
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
0.137
315814AE2-033 C
Solar/Wind Harmer
17.143
970533AG2-339 GEN
Solar/Wind Harmer
16.359
970673AG2-436 GEN
Solar/Wind Harmer
26.678
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
3141813NORNECK
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
33.507
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.164
315733AD1-074 GEN2
Solar/Wind Harmer
1.164
316258AE1-075 C
Solar/Wind Harmer
0.152
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.547
3145893MURPHYS
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.616
970581AG2-369 GEN
Solar/Wind Harmer
9.13
316463AE2-346 GEN
Solar/Wind Harmer
0.169
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315652AC1-086 GEN
Solar/Wind Harmer
21.254
3137643SOCKMAN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.644
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.756
316210AC1-098 GEN
Solar/Wind Harmer
1.718
316486AD2-202 GEN
Solar/Wind Harmer
0.189
316274AC1-208 GEN
Solar/Wind Harmer
0.951
970831AG2-522 GEN
Solar/Wind Harmer
7.801
3145746EVERETS
Solar/Wind Harmer
0.723
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316327AA2-057 GEN
Solar/Wind Harmer
0.264
957861AF2-080 GEN
Solar/Wind Harmer
7.697
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
10.422
970681AG2-440 GEN
Solar/Wind Harmer
6.917
946301AF1-294 GEN
Solar/Wind Harmer
3.402
961791AG1-021 GEN
Solar/Wind Harmer
1.655
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.381
3147173SINAI
Solar/Wind Harmer
0.159
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.536
3138216PACIFIC
Solar/Wind Helper
0.038
3152251N ANNA1
50/50
13.705
972197AH1-683 GEN
50/50
5.832
972219AH1-694 GEN
50/50
4.199
315052AA1-145 CT2
50/50
2.024
316447AC1-158 HLD
Solar/Wind Harmer
2.991
316044AC1-158 PL1
Solar/Wind Harmer
1.36
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.64
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.009
3150851SPRUNCC
Adder
1.106
3142543TWELFTH
Solar/Wind Harmer
0.023
315975AC1-164 GENB
Solar/Wind Harmer
0.075
3143526WINTERP
Solar/Wind Harmer
1.245
944631AF1-128 GEN
Adder
113.89
3143226MDLTHAN
Solar/Wind Harmer
0.238
316132AB2-190 GEN1
Solar/Wind Harmer
1.251
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.156
3142433PROV 92
Solar/Wind Harmer
0.931
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
971317AH1-138 GEN
Solar/Wind Harmer
1.737
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.165
3151171GRAVELC
Adder
2.459
315773AC2-141 GEN
Solar/Wind Harmer
8.412
3145336SMITFLD
Solar/Wind Harmer
0.919
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.603
944591AF1-124 GEN
Solar/Wind Harmer
51.527
316381AD1-082 GEN
Solar/Wind Harmer
0.231
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.847
316072AD1-144
Solar/Wind Harmer
0.081
939411AE1-173 GEN
Solar/Wind Harmer
96.242
3146456SLIGO L269
Solar/Wind Harmer
0.225
319010AE1-072 C
Solar/Wind Harmer
1.122
940641AE2-051 GEN
Solar/Wind Harmer
18.003
316093AE2-104_GEN
Solar/Wind Harmer
3.762
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.712
3146516WINFALL
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
39.877
962861AG1-135 GEN
Solar/Wind Harmer
6.891
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.096
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.849
3150351NORNECKC2
Adder
2.089
315816AE2-034 GEN
Solar/Wind Harmer
0.891
3145663CRESWEL
Solar/Wind Harmer
0.584
971163AH1-040 GEN
Solar/Wind Harmer
16.704
315737AD1-076 GEN
Solar/Wind Harmer
2.621
3143336POWHATN
Solar/Wind Harmer
3.626
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.313
970919AG2-571 GEN
Solar/Wind Harmer
7.165
316023GEN1_S
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
0.804
3145893MURPHYS
Solar/Wind Harmer
0.894
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3146173TUNIS
Solar/Wind Harmer
0.199
970087AG2-069 GEN
Solar/Wind Harmer
15.924
3156021HOLLOMANSOL
Solar/Wind Harmer
0.896
3145683EARLEYS
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.394
960081AF2-299 GEN
Solar/Wind Harmer
1.882
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.403
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.627
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.715
315693AD1-088 GEN
Solar/Wind Harmer
9.073
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.678
971065AG2-659 GEN
Solar/Wind Harmer
7.714
3147666LOUISA
Solar/Wind Harmer
0.715
316494AC1-189 GEN
Solar/Wind Harmer
0.603
972135AH1-637 GEN
Solar/Wind Harmer
1.512
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.781
3146233WITAKRS
Solar/Wind Harmer
0.699
316131AB2-060 GEN
Solar/Wind Harmer
0.544
316192AB2-158 GEN
Solar/Wind Harmer
0.979
315785AD2-033 C
Solar/Wind Harmer
1.405
316034AC1-036 C
Solar/Wind Harmer
0.012
970685AG2-442 GEN
Solar/Wind Harmer
12.893
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
316359AB2-059 GEN
Solar/Wind Harmer
0.613
971563AH1-280 GEN
Solar/Wind Harmer
1.839
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.325
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.568
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.973
972277AH1-723 GEN
Adder
96.974
3146776BUCKING
Solar/Wind Harmer
0.065
971377AH1-170 GEN
Solar/Wind Harmer
1.536
3147623JAMES R
Solar/Wind Harmer
0.334
316415AF1-147_GEN2
Solar/Wind Helper
0.789
LAGNLTFEXP_LAGN->PJM
CLTF
7.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.331
NYPJM->LTFIMP_NY
CLTF
3.17
LGEELTFEXP_LGEE->PJM
CLTF
1.29
TVALTFEXP_TVA->PJM
CLTF
3.951
WECLTFEXP_WEC->PJM
CLTF
0.621
CPLELTFEXP_CPLE->PJM
CLTF
11.096
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.435
MECLTFEXP_MEC->PJM
CLTF
3.506
SIGELTFEXP_SIGE->PJM
CLTF
0.107

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.15 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3901.64
MW Contribution:
5.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.436
972195AH1-682 GEN
50/50
3.737
972189AH1-679 GEN
50/50
3.521
3142296MT RD221
50/50
0.659
3142366NRTHEST
50/50
0.655
315673AE1-157 GEN
Solar/Wind Harmer
13.8
316312AB1-027
Solar/Wind Harmer
0.341
3150691DARBY 3
Adder
13.558
3150701DARBY 4
Adder
13.527
3150681DARBY 2
Adder
13.511
3150671DARBY 1
Adder
13.495
315976AC1-164 GENA
Solar/Wind Harmer
1.947
316169AC1-164_GENC
Solar/Wind Harmer
1.682
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.186
3143526WINTERP
Solar/Wind Harmer
0.936
316033AB2-134 GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.883
316294AC1-161 GEN
Solar/Wind Harmer
3.032
3150991CHESPKB
Adder
1.818
3150991CHESPKB
Adder
1.775
3145506HICKORY
Solar/Wind Harmer
0.69
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.275
316388AE2-253 GEN
Solar/Wind Harmer
0.535
316349AD2-085 GEN
Solar/Wind Harmer
0.114
3137176SLIGO L2192
Solar/Wind Harmer
0.682
3146456SLIGO L269
Solar/Wind Harmer
3.034
3130086AYDLETT
Solar/Wind Harmer
0.685
315835AF2-110_GEN
Solar/Wind Harmer
1.169
316156AD2-030 GEN
Solar/Wind Harmer
0.125
3146386ELIZ CT
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.166
3146626S HERTFORD
Solar/Wind Harmer
0.166
3144356SAPONY
Solar/Wind Harmer
1.375
316315AB2-025 C
Solar/Wind Harmer
0.132
315742AE1-103 GEN
Solar/Wind Harmer
2.447
3146376EDENTON
Solar/Wind Harmer
0.725
3146376EDENTON
Solar/Wind Harmer
0.725
315614AA2-178 GEN
Solar/Wind Harmer
0.908
972185AH1-677 GEN
Adder
8.87
972187AH1-678 GEN
Adder
4.457
316313AB2-026
Solar/Wind Harmer
0.097
316065AD1-022 GEN
Solar/Wind Harmer
7.157
970933AG2-581 GEN
Solar/Wind Harmer
12.367
3145893MURPHYS
Solar/Wind Harmer
1.031
3145893MURPHYS
Solar/Wind Harmer
0.277
316365GEN2_N
Solar/Wind Harmer
0.341
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316140AB2-099
Solar/Wind Harmer
0.054
316336AC2-165 C
Solar/Wind Harmer
7.636
3150341NORNECKC1
Adder
1.568
3150341NORNECKC1
Adder
1.555
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
313506AB2-031 GEN
Solar/Wind Harmer
0.455
962571AG1-106 GEN
Solar/Wind Harmer
2.107
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.63
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
3145933PARMELE
Solar/Wind Harmer
0.286
3145933PARMELE
Solar/Wind Harmer
0.143
972193AH1-681 GEN
Adder
3.241
316005AA1-067
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.684
970301AG2-198 GEN
Solar/Wind Harmer
5.907
3145493TOT1
Solar/Wind Harmer
0.315
3145453TOT5
Solar/Wind Harmer
0.189
3145603CNETO
Solar/Wind Harmer
0.126
970323AG2-213 GEN
Solar/Wind Harmer
5.766
958211AF2-115 GEN
Solar/Wind Harmer
1.618
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.376
316049AB1-081 GEN
Solar/Wind Harmer
0.76
316263AC1-034 GEN
Solar/Wind Harmer
5.077
962561AG1-105 GEN
Solar/Wind Harmer
6.247
3146776BUCKING
Solar/Wind Harmer
0.52
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.48
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
316118AC1-105 GEN
Solar/Wind Harmer
0.325
971531AH1-263 GEN
50/50
38.564
3150411LDYSMT5
50/50
28.578
3150381LDYSMT2
50/50
27.35
972213AH1-691 GEN
50/50
4.627
972215AH1-692 GEN
50/50
4.627
971285AH1-108 GEN
Adder
1.379
316159AE1-175 C
Solar/Wind Harmer
0.154
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.497
971283AH1-107 GEN
Solar/Wind Harmer
2.497
315697AD1-025 GEN
Solar/Wind Harmer
0.192
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151201GRAVEL4
Adder
12.843
3151221GRAVEL6
Adder
12.828
3151191GRAVEL3
Adder
12.68
3151211GRAVEL5
Adder
12.68
971445AH1-216 GEN
Solar/Wind Harmer
12.355
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143316POE
Solar/Wind Harmer
0.689
3151081ELIZAR1
Adder
15.915
3151091ELIZAR2
Adder
15.638
970657AG2-426 GEN
Solar/Wind Harmer
1.273
316316AC1-027 C
Solar/Wind Harmer
0.165
970189AG2-124 GEN
Solar/Wind Harmer
5.099
957871AF2-081 GEN
Solar/Wind Harmer
8.553
316311AC2-079 GEN
Solar/Wind Harmer
4.926
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
3146396TANGLEW
Solar/Wind Harmer
0.466
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
315814AE2-033 C
Solar/Wind Harmer
12.96
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
970533AG2-339 GEN
Solar/Wind Harmer
12.209
970673AG2-436 GEN
Solar/Wind Harmer
19.934
971967AH1-528 GEN
Solar/Wind Harmer
25.131
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315732AD1-074 GEN1
Solar/Wind Harmer
0.891
315733AD1-074 GEN2
Solar/Wind Harmer
0.891
316258AE1-075 C
Solar/Wind Harmer
0.117
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.781
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
316463AE2-346 GEN
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
3146043SEABORD
Solar/Wind Harmer
0.151
970085AG2-068 GEN
Solar/Wind Harmer
8.004
970581AG2-369 GEN
Solar/Wind Harmer
6.884
3141813NORNECK
Solar/Wind Harmer
0.15
315652AC1-086 GEN
Solar/Wind Harmer
16.288
316426AA2-053 GEN
Solar/Wind Harmer
0.494
3137643SOCKMAN
Solar/Wind Harmer
0.59
3145796HORNRTN
Solar/Wind Harmer
0.467
3145796HORNRTN
Solar/Wind Harmer
0.058
3146033SCOT NK
Solar/Wind Harmer
0.582
316210AC1-098 GEN
Solar/Wind Harmer
1.323
316274AC1-208 GEN
Solar/Wind Harmer
0.732
316486AD2-202 GEN
Solar/Wind Harmer
0.144
970831AG2-522 GEN
Solar/Wind Harmer
6.009
3145746EVERETS
Solar/Wind Harmer
0.558
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316327AA2-057 GEN
Solar/Wind Harmer
0.204
957861AF2-080 GEN
Solar/Wind Harmer
5.951
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
8.135
970681AG2-440 GEN
Solar/Wind Harmer
5.399
946301AF1-294 GEN
Solar/Wind Harmer
2.66
961791AG1-021 GEN
Solar/Wind Harmer
1.294
971845AH1-439 GEN
Solar/Wind Harmer
5.912
972205AH1-687 GEN
Adder
5.352
3147173SINAI
Solar/Wind Harmer
0.124
3147243WELCO
Solar/Wind Harmer
0.078
226929AD2-058 GEN
Solar/Wind Helper
0.118
3150401LDYSMT4
50/50
28.489
3150371LDYSMT1
50/50
27.528
315051AA1-145 CT1
50/50
1.568
3142416OLDCHRC
Solar/Wind Harmer
1.859
970293AG2-193 GEN
Solar/Wind Harmer
2.002
316075AC2-137 C
Solar/Wind Harmer
0.05
3143096IRON208
Adder
0.775
3143096IRON208
Adder
0.759
316473AC1-191 GEN
Solar/Wind Harmer
0.624
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.843
970133AG2-095 GEN
Solar/Wind Harmer
1.734
316458AB2-190 GEN2
Solar/Wind Harmer
0.957
315778AD1-151 GEN
Solar/Wind Harmer
14.303
3150921YORKTN3
Adder
4.461
3144216WINCHST
Adder
0.669
961611AG1-000B GEN
Solar/Wind Harmer
4.724
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151171GRAVELC
Adder
2.468
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.324
3144536CHRHLND
Solar/Wind Harmer
0.026
3151101ELIZAR3
Adder
16.118
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.063
944601AF1-125 GEN
Solar/Wind Harmer
38.461
970657AG2-426 GEN
Solar/Wind Harmer
3.889
3141766HARMONY
Solar/Wind Harmer
2.298
3141843SHACKLE
Adder
0.879
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3146456SLIGO L269
Solar/Wind Harmer
0.171
971153AH1-033 GEN
Solar/Wind Harmer
1.982
316246AF1-032 C
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
3.026
316321Z2-027
Solar/Wind Harmer
0.03
3146516WINFALL
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.166
3145273HOLLAND
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.163
944011AF1-069 GEN
Solar/Wind Harmer
9.724
315735AD1-075 GEN1
Solar/Wind Harmer
0.445
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
2.358
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
3146173TUNIS
Solar/Wind Harmer
0.153
970917AG2-570 GEN
Solar/Wind Harmer
13.485
3146263WOODLND
Solar/Wind Harmer
0.15
3150351NORNECKC2
Adder
1.518
3145963POPLR C
Solar/Wind Harmer
0.149
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316181AB2-040 GEN
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.148
316011AB1-132 GEN
Solar/Wind Harmer
2.686
3145796HORNRTN
Solar/Wind Harmer
0.584
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.087
3145933PARMELE
Solar/Wind Harmer
0.143
316212AC1-099_GEN
Solar/Wind Harmer
0.738
316478AD1-087 GEN
Solar/Wind Harmer
0.492
972255AH1-712 GEN
Adder
72.54
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315722AD1-056 GEN
Solar/Wind Harmer
4.811
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.682
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
964241AG1-285 GEN
Solar/Wind Harmer
9.026
970257AG2-171 GEN
Solar/Wind Harmer
4.324
971775AH1-396 GEN
Solar/Wind Harmer
0.216
959311AF2-222 GEN
Solar/Wind Harmer
12.009
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.423
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.08
961601AG1-000A GEN
Solar/Wind Harmer
9.505
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.133
971623AH1-311 GEN
Solar/Wind Harmer
0.267
3147666LOUISA
Solar/Wind Harmer
0.307
3146776BUCKING
Solar/Wind Harmer
0.047
316223AC1-118
Solar/Wind Harmer
0.091
3141906WESTMOR
Solar/Wind Harmer
0.051
972003AH1-546 GEN
Solar/Wind Harmer
4.363
970221AG2-151 GEN
Solar/Wind Harmer
6.373
971683AH1-343 GEN
Solar/Wind Harmer
4.262
316222AC1-221 GEN
Solar/Wind Harmer
0.471
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.389
226910AB2-157 C
Solar/Wind Helper
0.016
972197AH1-683 GEN
50/50
4.449
972219AH1-694 GEN
50/50
3.203
315052AA1-145 CT2
50/50
1.577
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.498
3142416OLDCHRC
Solar/Wind Harmer
0.191
315975AC1-164 GENB
Solar/Wind Harmer
0.058
3143096IRON208
Adder
0.775
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.526
3150851SPRUNCC
Adder
0.843
3143526WINTERP
Solar/Wind Harmer
0.936
316132AB2-190 GEN1
Solar/Wind Harmer
0.957
971069AG2-661 GEN
Solar/Wind Harmer
3.178
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971317AH1-138 GEN
Solar/Wind Harmer
1.326
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
9.291
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
0.176
3151171GRAVELC
Adder
1.877
315773AC2-141 GEN
Solar/Wind Harmer
6.405
3145336SMITFLD
Solar/Wind Harmer
0.701
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
3150981CHESPKA
Adder
2.167
316381AD1-082 GEN
Solar/Wind Harmer
0.176
944591AF1-124 GEN
Solar/Wind Harmer
39.202
316072AD1-144
Solar/Wind Harmer
0.061
3141766HARMONY
Solar/Wind Harmer
0.034
971777AH1-397 GEN
Solar/Wind Harmer
0.454
3146456SLIGO L269
Solar/Wind Harmer
0.171
319010AE1-072 C
Solar/Wind Harmer
0.854
316093AE2-104_GEN
Solar/Wind Harmer
2.865
939411AE1-173 GEN
Solar/Wind Harmer
72.216
940641AE2-051 GEN
Solar/Wind Harmer
13.444
3146516WINFALL
Solar/Wind Harmer
0.543
3146516WINFALL
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.1
3130156CHOWAN
Solar/Wind Harmer
0.163
941031AE2-094 GEN
Solar/Wind Harmer
29.76
315816AE2-034 GEN
Solar/Wind Harmer
0.681
3145663CRESWEL
Solar/Wind Harmer
0.447
971163AH1-040 GEN
Solar/Wind Harmer
12.772
962861AG1-135 GEN
Solar/Wind Harmer
5.01
315737AD1-076 GEN
Solar/Wind Harmer
2.007
3143336POWHATN
Solar/Wind Harmer
2.775
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
5.148
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.304
3145893MURPHYS
Solar/Wind Harmer
0.616
3145893MURPHYS
Solar/Wind Harmer
0.685
316023GEN1_S
Solar/Wind Harmer
0.341
3141726DUNNSVL
Solar/Wind Harmer
0.611
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.686
970919AG2-571 GEN
Solar/Wind Harmer
5.394
3145683EARLEYS
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.302
3146263WOODLND
Solar/Wind Harmer
0.15
970087AG2-069 GEN
Solar/Wind Harmer
12.006
960081AF2-299 GEN
Solar/Wind Harmer
1.44
3150351NORNECKC2
Adder
1.493
3145963POPLR C
Solar/Wind Harmer
0.149
3145823KELFORD
Solar/Wind Harmer
0.148
957481AF2-042 GEN
Solar/Wind Harmer
39.076
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.317
315693AD1-088 GEN
Solar/Wind Harmer
6.932
3146293MARTNCO
Solar/Wind Harmer
0.133
972277AH1-723 GEN
Adder
84.53
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.523
316337AD2-073 GEN
Solar/Wind Harmer
0.12
971065AG2-659 GEN
Solar/Wind Harmer
5.948
316494AC1-189 GEN
Solar/Wind Harmer
0.466
970937AG2-583 GEN
Solar/Wind Harmer
8.399
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.605
3146233WITAKRS
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.422
315785AD2-033 C
Solar/Wind Harmer
1.093
316034AC1-036 C
Solar/Wind Harmer
0.009
970685AG2-442 GEN
Solar/Wind Harmer
10.073
971563AH1-280 GEN
Solar/Wind Harmer
1.438
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3146926FARMVIL
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.475
3142053HEARTS
Solar/Wind Harmer
0.235
3147666LOUISA
Solar/Wind Harmer
0.533
316192AB2-158 GEN
Solar/Wind Harmer
0.738
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.758
971377AH1-170 GEN
Solar/Wind Harmer
1.275
3147623JAMES R
Solar/Wind Harmer
0.277
LAGNLTFEXP_LAGN->PJM
CLTF
7.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.159
NYPJM->LTFIMP_NY
CLTF
2.859
LGEELTFEXP_LGEE->PJM
CLTF
1.602
TVALTFEXP_TVA->PJM
CLTF
3.819
WECLTFEXP_WEC->PJM
CLTF
0.813
CPLELTFEXP_CPLE->PJM
CLTF
8.867
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.841
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.334
MECLTFEXP_MEC->PJM
CLTF
4.136
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.7 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3887.02
MW Contribution:
5.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.679
972195AH1-682 GEN
50/50
3.769
972189AH1-679 GEN
50/50
3.542
3142296MT RD221
50/50
0.662
3142366NRTHEST
50/50
0.658
3150691DARBY 3
50/50
14.454
315673AE1-157 GEN
Solar/Wind Harmer
13.908
316312AB1-027
Solar/Wind Harmer
0.343
3150701DARBY 4
Adder
13.59
3150681DARBY 2
Adder
13.574
3150671DARBY 1
Adder
13.558
315976AC1-164 GENA
Solar/Wind Harmer
1.956
316169AC1-164_GENC
Solar/Wind Harmer
1.69
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.526
3143526WINTERP
Solar/Wind Harmer
0.939
316033AB2-134 GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.887
316294AC1-161 GEN
Solar/Wind Harmer
3.042
3150991CHESPKB
Adder
1.824
3150991CHESPKB
Adder
1.781
3145506HICKORY
Solar/Wind Harmer
0.692
3145506HICKORY
Solar/Wind Harmer
0.415
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.276
316388AE2-253 GEN
Solar/Wind Harmer
0.537
316349AD2-085 GEN
Solar/Wind Harmer
0.115
3137176SLIGO L2192
Solar/Wind Harmer
0.685
3146456SLIGO L269
Solar/Wind Harmer
3.044
3130086AYDLETT
Solar/Wind Harmer
0.687
316156AD2-030 GEN
Solar/Wind Harmer
0.125
315835AF2-110_GEN
Solar/Wind Harmer
1.173
3146386ELIZ CT
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.379
316315AB2-025 C
Solar/Wind Harmer
0.132
315742AE1-103 GEN
Solar/Wind Harmer
2.455
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
315614AA2-178 GEN
Solar/Wind Harmer
0.911
972185AH1-677 GEN
Adder
8.889
972187AH1-678 GEN
Adder
4.466
316313AB2-026
Solar/Wind Harmer
0.097
316065AD1-022 GEN
Solar/Wind Harmer
7.178
970933AG2-581 GEN
Solar/Wind Harmer
12.39
3145893MURPHYS
Solar/Wind Harmer
1.034
3145893MURPHYS
Solar/Wind Harmer
0.278
316365GEN2_N
Solar/Wind Harmer
0.342
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316140AB2-099
Solar/Wind Harmer
0.054
3150341NORNECKC1
Adder
1.577
3150341NORNECKC1
Adder
1.564
316336AC2-165 C
Solar/Wind Harmer
7.629
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
313506AB2-031 GEN
Solar/Wind Harmer
0.456
962571AG1-106 GEN
Solar/Wind Harmer
2.112
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.655
3145783HORNRTN
Solar/Wind Harmer
2.606
3145783HORNRTN
Solar/Wind Harmer
2.084
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.439
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
972193AH1-681 GEN
Adder
3.252
316005AA1-067
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.69
970301AG2-198 GEN
Solar/Wind Harmer
5.905
3145493TOT1
Solar/Wind Harmer
0.316
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.126
970323AG2-213 GEN
Solar/Wind Harmer
5.768
958211AF2-115 GEN
Solar/Wind Harmer
1.617
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.382
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
5.089
962561AG1-105 GEN
Solar/Wind Harmer
6.254
3146776BUCKING
Solar/Wind Harmer
0.518
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.483
3150411LDYSMT5
50/50
28.823
3150381LDYSMT2
50/50
27.584
972213AH1-691 GEN
50/50
4.666
972215AH1-692 GEN
50/50
4.666
971285AH1-108 GEN
Adder
1.384
316159AE1-175 C
Solar/Wind Harmer
0.155
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.505
971283AH1-107 GEN
Solar/Wind Harmer
2.505
315697AD1-025 GEN
Solar/Wind Harmer
0.192
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151201GRAVEL4
Adder
12.891
3151221GRAVEL6
Adder
12.876
3151191GRAVEL3
Adder
12.728
3151211GRAVEL5
Adder
12.728
971445AH1-216 GEN
Solar/Wind Harmer
12.4
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143316POE
Solar/Wind Harmer
0.691
3151081ELIZAR1
Adder
15.97
3151091ELIZAR2
Adder
15.693
970657AG2-426 GEN
Solar/Wind Harmer
1.277
316316AC1-027 C
Solar/Wind Harmer
0.166
970189AG2-124 GEN
Solar/Wind Harmer
5.123
957871AF2-081 GEN
Solar/Wind Harmer
8.582
316311AC2-079 GEN
Solar/Wind Harmer
4.942
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.17
3146486SUNBURY
Solar/Wind Harmer
0.17
3146396TANGLEW
Solar/Wind Harmer
0.467
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
315814AE2-033 C
Solar/Wind Harmer
12.997
3130156CHOWAN
Solar/Wind Harmer
0.164
3130156CHOWAN
Solar/Wind Harmer
0.164
970533AG2-339 GEN
Solar/Wind Harmer
12.236
970673AG2-436 GEN
Solar/Wind Harmer
19.978
3130546PLYMOUTH
Solar/Wind Harmer
0.157
971967AH1-528 GEN
Solar/Wind Harmer
25.182
315732AD1-074 GEN1
Solar/Wind Harmer
0.894
315733AD1-074 GEN2
Solar/Wind Harmer
0.894
316258AE1-075 C
Solar/Wind Harmer
0.117
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.798
3145893MURPHYS
Solar/Wind Harmer
0.417
3145893MURPHYS
Solar/Wind Harmer
0.154
316463AE2-346 GEN
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.319
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.152
3146043SEABORD
Solar/Wind Harmer
0.151
3141813NORNECK
Solar/Wind Harmer
0.15
970085AG2-068 GEN
Solar/Wind Harmer
8.021
970581AG2-369 GEN
Solar/Wind Harmer
6.898
315652AC1-086 GEN
Solar/Wind Harmer
16.33
316426AA2-053 GEN
Solar/Wind Harmer
0.495
3137643SOCKMAN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.583
316210AC1-098 GEN
Solar/Wind Harmer
1.326
316274AC1-208 GEN
Solar/Wind Harmer
0.734
316486AD2-202 GEN
Solar/Wind Harmer
0.145
970831AG2-522 GEN
Solar/Wind Harmer
6.021
3145746EVERETS
Solar/Wind Harmer
0.56
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316327AA2-057 GEN
Solar/Wind Harmer
0.205
957861AF2-080 GEN
Solar/Wind Harmer
5.966
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
8.135
970681AG2-440 GEN
Solar/Wind Harmer
5.399
946301AF1-294 GEN
Solar/Wind Harmer
2.66
961791AG1-021 GEN
Solar/Wind Harmer
1.294
971845AH1-439 GEN
Solar/Wind Harmer
5.895
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.326
226929AD2-058 GEN
Solar/Wind Helper
0.118
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
316118AC1-105 GEN
Solar/Wind Harmer
0.325
3150401LDYSMT4
50/50
28.733
3150371LDYSMT1
50/50
27.764
315051AA1-145 CT1
50/50
1.577
3142416OLDCHRC
Solar/Wind Harmer
1.868
970293AG2-193 GEN
Solar/Wind Harmer
2.012
316075AC2-137 C
Solar/Wind Harmer
0.05
3143096IRON208
Adder
0.778
3143096IRON208
Adder
0.763
316473AC1-191 GEN
Solar/Wind Harmer
0.628
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.846
970133AG2-095 GEN
Solar/Wind Harmer
1.741
316458AB2-190 GEN2
Solar/Wind Harmer
0.961
315778AD1-151 GEN
Solar/Wind Harmer
14.359
3150921YORKTN3
Adder
4.479
3144216WINCHST
Adder
0.672
961611AG1-000B GEN
Solar/Wind Harmer
4.742
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151171GRAVELC
Adder
2.477
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.357
3144536CHRHLND
Solar/Wind Harmer
0.026
3151101ELIZAR3
Adder
16.174
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.197
944601AF1-125 GEN
Solar/Wind Harmer
38.593
970657AG2-426 GEN
Solar/Wind Harmer
3.903
3141766HARMONY
Solar/Wind Harmer
2.309
3141843SHACKLE
Adder
0.884
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.989
316246AF1-032 C
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
3.041
316321Z2-027
Solar/Wind Harmer
0.03
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.164
944011AF1-069 GEN
Solar/Wind Harmer
9.745
315735AD1-075 GEN1
Solar/Wind Harmer
0.446
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
2.358
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.154
3146173TUNIS
Solar/Wind Harmer
0.153
970917AG2-570 GEN
Solar/Wind Harmer
13.514
3150351NORNECKC2
Adder
1.526
3146263WOODLND
Solar/Wind Harmer
0.15
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.15
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
316181AB2-040 GEN
Solar/Wind Harmer
0.212
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
0.585
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.143
316212AC1-099_GEN
Solar/Wind Harmer
0.74
972255AH1-712 GEN
Adder
72.785
316478AD1-087 GEN
Solar/Wind Harmer
0.492
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
315722AD1-056 GEN
Solar/Wind Harmer
4.822
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.684
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
964241AG1-285 GEN
Solar/Wind Harmer
9.033
970257AG2-171 GEN
Solar/Wind Harmer
4.326
971775AH1-396 GEN
Solar/Wind Harmer
0.216
959311AF2-222 GEN
Solar/Wind Harmer
12.012
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.422
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
9.528
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.299
3146776BUCKING
Solar/Wind Harmer
0.047
316223AC1-118
Solar/Wind Harmer
0.092
3141906WESTMOR
Solar/Wind Harmer
0.052
972003AH1-546 GEN
Solar/Wind Harmer
4.342
970221AG2-151 GEN
Solar/Wind Harmer
6.341
971683AH1-343 GEN
Solar/Wind Harmer
4.267
316222AC1-221 GEN
Solar/Wind Harmer
0.472
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.487
972219AH1-694 GEN
50/50
3.23
315052AA1-145 CT2
50/50
1.587
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
0.501
3142416OLDCHRC
Solar/Wind Harmer
0.192
315975AC1-164 GENB
Solar/Wind Harmer
0.058
3143096IRON208
Adder
0.778
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.909
3150851SPRUNCC
Adder
0.846
3143526WINTERP
Solar/Wind Harmer
0.939
316132AB2-190 GEN1
Solar/Wind Harmer
0.961
971069AG2-661 GEN
Solar/Wind Harmer
3.191
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971317AH1-138 GEN
Solar/Wind Harmer
1.331
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.327
3142433PROV 92
Solar/Wind Harmer
0.71
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151171GRAVELC
Adder
1.884
3143226MDLTHAN
Solar/Wind Harmer
0.177
315773AC2-141 GEN
Solar/Wind Harmer
6.428
3145336SMITFLD
Solar/Wind Harmer
0.704
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
3150981CHESPKA
Adder
2.175
316381AD1-082 GEN
Solar/Wind Harmer
0.176
944591AF1-124 GEN
Solar/Wind Harmer
39.336
3141766HARMONY
Solar/Wind Harmer
0.035
316072AD1-144
Solar/Wind Harmer
0.062
971777AH1-397 GEN
Solar/Wind Harmer
0.456
3146456SLIGO L269
Solar/Wind Harmer
0.172
319010AE1-072 C
Solar/Wind Harmer
0.857
316093AE2-104_GEN
Solar/Wind Harmer
2.874
939411AE1-173 GEN
Solar/Wind Harmer
72.415
940641AE2-051 GEN
Solar/Wind Harmer
13.478
3146516WINFALL
Solar/Wind Harmer
0.545
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
3130156CHOWAN
Solar/Wind Harmer
0.164
941031AE2-094 GEN
Solar/Wind Harmer
29.826
315816AE2-034 GEN
Solar/Wind Harmer
0.683
3145663CRESWEL
Solar/Wind Harmer
0.448
971163AH1-040 GEN
Solar/Wind Harmer
12.812
962861AG1-135 GEN
Solar/Wind Harmer
5.038
315737AD1-076 GEN
Solar/Wind Harmer
2.013
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
5.177
3143336POWHATN
Solar/Wind Harmer
2.774
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.313
3145893MURPHYS
Solar/Wind Harmer
0.618
3145893MURPHYS
Solar/Wind Harmer
0.687
316023GEN1_S
Solar/Wind Harmer
0.342
3141726DUNNSVL
Solar/Wind Harmer
0.615
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
970919AG2-571 GEN
Solar/Wind Harmer
5.406
3145683EARLEYS
Solar/Wind Harmer
0.152
315607AA1-063A GEN
Solar/Wind Harmer
0.303
3150351NORNECKC2
Adder
1.501
3146263WOODLND
Solar/Wind Harmer
0.15
970087AG2-069 GEN
Solar/Wind Harmer
12.031
960081AF2-299 GEN
Solar/Wind Harmer
1.443
3145963POPLR C
Solar/Wind Harmer
0.15
3145823KELFORD
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
39.136
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.32
315693AD1-088 GEN
Solar/Wind Harmer
6.94
3146293MARTNCO
Solar/Wind Harmer
0.133
972277AH1-723 GEN
Adder
84.817
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316337AD2-073 GEN
Solar/Wind Harmer
0.121
316129AC1-054 GEN
Solar/Wind Harmer
0.524
971065AG2-659 GEN
Solar/Wind Harmer
5.958
316494AC1-189 GEN
Solar/Wind Harmer
0.467
970937AG2-583 GEN
Solar/Wind Harmer
8.375
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
0.542
316131AB2-060 GEN
Solar/Wind Harmer
0.422
315785AD2-033 C
Solar/Wind Harmer
1.094
316034AC1-036 C
Solar/Wind Harmer
0.009
970685AG2-442 GEN
Solar/Wind Harmer
10.072
971563AH1-280 GEN
Solar/Wind Harmer
1.438
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.476
3142053HEARTS
Solar/Wind Harmer
0.236
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.759
316192AB2-158 GEN
Solar/Wind Harmer
0.717
971377AH1-170 GEN
Solar/Wind Harmer
1.268
3147623JAMES R
Solar/Wind Harmer
0.276
LAGNLTFEXP_LAGN->PJM
CLTF
7.548
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.189
NYPJM->LTFIMP_NY
CLTF
2.857
LGEELTFEXP_LGEE->PJM
CLTF
1.602
TVALTFEXP_TVA->PJM
CLTF
3.822
WECLTFEXP_WEC->PJM
CLTF
0.813
CPLELTFEXP_CPLE->PJM
CLTF
8.882
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.864
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.649
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.343
MECLTFEXP_MEC->PJM
CLTF
4.137
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.65 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5141.33
MW Contribution:
7.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.538
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.02
3151041BRUNSWICKG3
50/50
4.37
972187AH1-678 GEN
50/50
10.028
3150991CHESPKB
50/50
3.412
3150991CHESPKB
50/50
3.33
971223AH1-071 GEN
Solar/Wind Harmer
3.928
3143526WINTERP
Solar/Wind Harmer
1.741
970933AG2-581 GEN
Solar/Wind Harmer
25.921
3144356SAPONY
Solar/Wind Harmer
2.643
316315AB2-025 C
Solar/Wind Harmer
0.253
316294AC1-161 GEN
Solar/Wind Harmer
5.37
3145506HICKORY
Solar/Wind Harmer
1.227
3151031BRUNSWICKG2
50/50
4.37
3151101ELIZAR3
50/50
30.278
3150861SPRUNCD
50/50
1.46
3151161SURRY 1
50/50
11.976
944011AF1-069 GEN
Solar/Wind Harmer
20.825
970917AG2-570 GEN
Solar/Wind Harmer
28.384
944581AF1-123 GEN
Solar/Wind Harmer
69.669
944601AF1-125 GEN
Solar/Wind Harmer
68.596
3144873MCLAUGH
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3146456SLIGO L269
Solar/Wind Harmer
0.305
971153AH1-033 GEN
Solar/Wind Harmer
3.53
3144536CHRHLND
Solar/Wind Harmer
0.046
316246AF1-032 C
Solar/Wind Harmer
0.135
970657AG2-426 GEN
Solar/Wind Harmer
6.791
315813AE1-149 C
Solar/Wind Harmer
16.138
316321Z2-027
Solar/Wind Harmer
0.054
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.298
3145273HOLLAND
Solar/Wind Harmer
0.223
3143336POWHATN
Solar/Wind Harmer
4.458
3146376EDENTON
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
4.113
961611AG1-000B GEN
Solar/Wind Harmer
7.79
315778AD1-151 GEN
Solar/Wind Harmer
23.043
3145506HICKORY
Solar/Wind Harmer
0.736
3145506HICKORY
Solar/Wind Harmer
0.184
316339AD2-160 GEN
Solar/Wind Harmer
0.49
316388AE2-253 GEN
Solar/Wind Harmer
0.953
3137176SLIGO L2192
Solar/Wind Harmer
1.215
3146456SLIGO L269
Solar/Wind Harmer
5.404
3130086AYDLETT
Solar/Wind Harmer
1.22
3146386ELIZ CT
Solar/Wind Harmer
0.303
315835AF2-110_GEN
Solar/Wind Harmer
2.079
316349AD2-085 GEN
Solar/Wind Harmer
0.202
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
970099AG2-077 GEN
Solar/Wind Harmer
31.848
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
315742AE1-103 GEN
Solar/Wind Harmer
4.41
316313AB2-026
Solar/Wind Harmer
0.184
3146376EDENTON
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
1.307
316365GEN2_N
Solar/Wind Harmer
0.648
315614AA2-178 GEN
Solar/Wind Harmer
1.645
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
137.077
316065AD1-022 GEN
Solar/Wind Harmer
13.063
3145893MURPHYS
Solar/Wind Harmer
1.895
3145893MURPHYS
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.859
316140AB2-099
Solar/Wind Harmer
0.1
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
962571AG1-106 GEN
Solar/Wind Harmer
3.964
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.344
316336AC2-165 C
Solar/Wind Harmer
13.978
3145796HORNRTN
Solar/Wind Harmer
0.824
3145783HORNRTN
Solar/Wind Harmer
4.881
3145783HORNRTN
Solar/Wind Harmer
3.905
3145783HORNRTN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
0.488
3145933PARMELE
Solar/Wind Harmer
0.53
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
315724AD1-057 GEN
Solar/Wind Harmer
5.057
316005AA1-067
Solar/Wind Harmer
0.278
3142366NRTHEST
Adder
0.843
970301AG2-198 GEN
Solar/Wind Harmer
10.98
3150691DARBY 3
Adder
18.476
3150701DARBY 4
Adder
18.433
3150681DARBY 2
Adder
18.412
3150671DARBY 1
Adder
18.39
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
315976AC1-164 GENA
Solar/Wind Harmer
2.665
316169AC1-164_GENC
Solar/Wind Harmer
2.302
961601AG1-000A GEN
Solar/Wind Harmer
4.482
316049AB1-081 GEN
Solar/Wind Harmer
1.434
316263AC1-034 GEN
Solar/Wind Harmer
9.576
970323AG2-213 GEN
Solar/Wind Harmer
10.736
962561AG1-105 GEN
Solar/Wind Harmer
11.943
964791AG1-342 GEN
Solar/Wind Harmer
4.747
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.957
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.244
3147133PAMPLIN
Solar/Wind Harmer
0.196
316118AC1-105 GEN
Solar/Wind Harmer
0.623
316156AD2-030 GEN
Solar/Wind Harmer
0.177
316312AB1-027
Solar/Wind Harmer
0.426
3142296MT RD221
Adder
0.747
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.847
3146776BUCKING
Solar/Wind Harmer
0.069
3150341NORNECKC1
Adder
1.994
3150341NORNECKC1
Adder
1.978
942751AE2-291 GEN
Solar/Wind Harmer
9.753
972189AH1-679 GEN
Adder
2.484
942671AE2-283 GEN
Solar/Wind Harmer
3.241
972193AH1-681 GEN
Adder
2.943
316045AC1-158 PL2
Solar/Wind Helper
7.063
316450AC1-158 RIC
Solar/Wind Helper
0.589
316006AB2-029 C
Solar/Wind Helper
0.131
316411AF1-147_GEN1
Solar/Wind Helper
0.811
316303AF2-085
50/50
6.546
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.848
315779AE2-040
50/50
4.41
3151081ELIZAR1
50/50
29.895
3151091ELIZAR2
50/50
29.376
941591AE2-156 GEN
50/50
27.307
971285AH1-108 GEN
50/50
2.389
972263AH1-716 GEN
50/50
170.5
970533AG2-339 GEN
Solar/Wind Harmer
26.147
970673AG2-436 GEN
Solar/Wind Harmer
42.579
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.646
971283AH1-107 GEN
Solar/Wind Harmer
4.646
971967AH1-528 GEN
Solar/Wind Harmer
53.128
970085AG2-068 GEN
Solar/Wind Harmer
16.802
970581AG2-369 GEN
Solar/Wind Harmer
14.45
315814AE2-033 C
Solar/Wind Harmer
24.896
3143316POE
Solar/Wind Harmer
1.231
316316AC1-027 C
Solar/Wind Harmer
0.293
957871AF2-081 GEN
Solar/Wind Harmer
15.23
3146406KITTY HAWK
Solar/Wind Harmer
0.038
313526AB2-022
Solar/Wind Harmer
0.162
316311AC2-079 GEN
Solar/Wind Harmer
8.694
970657AG2-426 GEN
Solar/Wind Harmer
2.222
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
3146396TANGLEW
Solar/Wind Harmer
0.832
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.022
316258AE1-075 C
Solar/Wind Harmer
0.22
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
3151201GRAVEL4
Adder
21.4
3151221GRAVEL6
Adder
21.375
3151191GRAVEL3
Adder
21.129
3151211GRAVEL5
Adder
21.129
315697AD1-025 GEN
Solar/Wind Harmer
0.311
316486AD2-202 GEN
Solar/Wind Harmer
0.291
3130546PLYMOUTH
Solar/Wind Harmer
0.285
315732AD1-074 GEN1
Solar/Wind Harmer
1.623
315733AD1-074 GEN2
Solar/Wind Harmer
1.623
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.566
3146043SEABORD
Solar/Wind Harmer
0.28
316463AE2-346 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.648
3137643SOCKMAN
Solar/Wind Harmer
1.11
316426AA2-053 GEN
Solar/Wind Harmer
0.925
3145796HORNRTN
Solar/Wind Harmer
0.879
3145796HORNRTN
Solar/Wind Harmer
0.11
316159AE1-175 C
Solar/Wind Harmer
0.233
3146033SCOT NK
Solar/Wind Harmer
1.083
970831AG2-522 GEN
Solar/Wind Harmer
11.444
316210AC1-098 GEN
Solar/Wind Harmer
2.473
316274AC1-208 GEN
Solar/Wind Harmer
1.374
3138283WHITEMARSH
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
1.038
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.384
957861AF2-080 GEN
Solar/Wind Harmer
11.117
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
15.004
970681AG2-440 GEN
Solar/Wind Harmer
9.958
946301AF1-294 GEN
Solar/Wind Harmer
4.863
961791AG1-021 GEN
Solar/Wind Harmer
2.366
3143873LANEXA
Solar/Wind Harmer
0.147
970189AG2-124 GEN
Solar/Wind Harmer
7.205
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
3141913WHIT STONE
Solar/Wind Harmer
0.233
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.136
3141783LANCAST
Solar/Wind Harmer
0.091
971845AH1-439 GEN
Solar/Wind Harmer
9.695
3141813NORNECK
Solar/Wind Harmer
0.19
972205AH1-687 GEN
Adder
7.904
270197AD1-017 GEN1
Solar/Wind Harmer
0.884
316164AC1-076 GEN
Solar/Wind Helper
1.502
315651AD1-115 GEN
Solar/Wind Helper
0.943
3138216PACIFIC
Solar/Wind Helper
0.039
226929AD2-058 GEN
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Harmer
1.527
3156081AA2-088 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.99
315735AD1-075 GEN1
Solar/Wind Harmer
0.81
3144216WINCHST
Adder
1.071
970133AG2-095 GEN
Solar/Wind Harmer
2.72
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
3150921YORKTN3
Adder
7.096
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.399
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.054
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.099
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
3143096IRON208
Adder
1.123
316212AC1-099_GEN
Solar/Wind Harmer
1.379
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.089
315722AD1-056 GEN
Solar/Wind Harmer
9.066
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3146233WITAKRS
Solar/Wind Harmer
1.285
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.033
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.714
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
961601AG1-000A GEN
Solar/Wind Harmer
17.927
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.504
316075AC2-137 C
Solar/Wind Harmer
0.067
970257AG2-171 GEN
Solar/Wind Harmer
8.052
971775AH1-396 GEN
Solar/Wind Harmer
0.403
959311AF2-222 GEN
Solar/Wind Harmer
22.299
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.768
3141843SHACKLE
Adder
1.242
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.22
3141873WAN 176
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
2.32
3146926FARMVIL
Solar/Wind Harmer
0.14
316222AC1-221 GEN
Solar/Wind Harmer
0.904
316283AC2-100 C
Solar/Wind Harmer
0.427
971683AH1-343 GEN
Solar/Wind Harmer
7.996
316473AC1-191 GEN
Solar/Wind Harmer
0.733
3146776BUCKING
Solar/Wind Harmer
0.076
316123AC1-075 GEN
Solar/Wind Harmer
0.255
3150351NORNECKC2
Adder
1.93
972003AH1-546 GEN
Solar/Wind Harmer
6.525
970221AG2-151 GEN
Solar/Wind Harmer
9.098
270494AE1-108_GEN
Solar/Wind Harmer
1.833
971781AH1-399 GEN
Solar/Wind Harmer
0.197
316223AC1-118
Solar/Wind Harmer
0.101
3141906WESTMOR
Solar/Wind Harmer
0.057
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
972255AH1-712 GEN
Adder
65.866
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.325
3147666LOUISA
Solar/Wind Helper
0.716
3141196NOKESVL
Solar/Wind Helper
1.04
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.095
315243AE2-183_GT3
50/50
5.538
3151051BRUNSWICKS1
50/50
9.073
3151021BRUNSWICKG1
50/50
4.37
971451AH1-221 GEN
50/50
13.272
3150981CHESPKA
50/50
4.067
3150851SPRUNCC
50/50
1.46
3152331SURRY 2
50/50
12.176
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.032
941031AE2-094 GEN
Solar/Wind Harmer
63.736
939411AE1-173 GEN
Solar/Wind Harmer
144.938
3143526WINTERP
Solar/Wind Harmer
1.741
970919AG2-571 GEN
Solar/Wind Harmer
11.354
970087AG2-069 GEN
Solar/Wind Harmer
25.203
315773AC2-141 GEN
Solar/Wind Harmer
11.346
944591AF1-124 GEN
Solar/Wind Harmer
69.917
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.055
3146456SLIGO L269
Solar/Wind Harmer
0.305
319010AE1-072 C
Solar/Wind Harmer
1.522
316093AE2-104_GEN
Solar/Wind Harmer
5.094
316381AD1-082 GEN
Solar/Wind Harmer
0.307
316072AD1-144
Solar/Wind Harmer
0.107
3146516WINFALL
Solar/Wind Harmer
0.971
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.196
957481AF2-042 GEN
Solar/Wind Harmer
79.621
3143336POWHATN
Solar/Wind Harmer
5.245
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.127
961611AG1-000B GEN
Solar/Wind Harmer
15.32
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316023GEN1_S
Solar/Wind Harmer
0.648
315816AE2-034 GEN
Solar/Wind Harmer
1.234
3145663CRESWEL
Solar/Wind Harmer
0.809
971163AH1-040 GEN
Solar/Wind Harmer
23.139
315693AD1-088 GEN
Solar/Wind Harmer
13.86
971069AG2-661 GEN
Solar/Wind Harmer
5.121
316132AB2-190 GEN1
Solar/Wind Harmer
1.527
315737AD1-076 GEN
Solar/Wind Harmer
3.655
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.132
3145893MURPHYS
Solar/Wind Harmer
1.259
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.038
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3156021HOLLOMANSOL
Solar/Wind Harmer
1.261
315607AA1-063A GEN
Solar/Wind Harmer
0.562
3145683EARLEYS
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Adder
2.497
971317AH1-138 GEN
Solar/Wind Harmer
2.055
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.906
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.274
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
944631AF1-128 GEN
Adder
128.737
316129AC1-054 GEN
Solar/Wind Harmer
0.998
971065AG2-659 GEN
Solar/Wind Harmer
11.366
3146293MARTNCO
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.871
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
1.018
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.135
315975AC1-164 GENB
Solar/Wind Harmer
0.079
3142433PROV 92
Solar/Wind Harmer
1.011
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.043
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.201
316359AB2-059 GEN
Solar/Wind Harmer
0.895
3142053HEARTS
Solar/Wind Harmer
0.444
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
18.502
970401AG2-262 GEN
Solar/Wind Harmer
1.45
971563AH1-280 GEN
Solar/Wind Harmer
2.629
3144293JTRSVLE
Adder
0.588
3144293JTRSVLE
Adder
0.464
971777AH1-397 GEN
Solar/Wind Harmer
0.642
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.622
3142416OLDCHRC
Solar/Wind Harmer
0.238
3146926FARMVIL
Solar/Wind Harmer
0.14
3138133OCRAN
Solar/Wind Harmer
0.139
970937AG2-583 GEN
Solar/Wind Harmer
13.903
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.638
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.787
3141726DUNNSVL
Solar/Wind Harmer
0.785
3150351NORNECKC2
Adder
1.898
971377AH1-170 GEN
Solar/Wind Harmer
1.82
3147623JAMES R
Solar/Wind Harmer
0.395
316337AD2-073 GEN
Solar/Wind Harmer
0.144
970223AG2-152 GEN
Solar/Wind Harmer
10.638
3147123OTTER R
Solar/Wind Harmer
0.084
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.167
972277AH1-723 GEN
Adder
76.754
270030AE2-140 GEN
Solar/Wind Harmer
12.682
316447AC1-158 HLD
Solar/Wind Helper
4.857
316044AC1-158 PL1
Solar/Wind Helper
2.207
3147666LOUISA
Solar/Wind Helper
1.246
316192AB2-158 GEN
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.811
LAGNLTFEXP_LAGN->PJM
CLTF
12.446
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.855
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
2.327
WECLTFEXP_WEC->PJM
CLTF
1.181
TVALTFEXP_TVA->PJM
CLTF
6.264
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
CPLELTFEXP_CPLE->PJM
CLTF
16.77
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.214
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.577
MECLTFEXP_MEC->PJM
CLTF
6.248
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.54 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3946.36
MW Contribution:
6.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.288
315241AE2-183_GT1
50/50
5.274
972185AH1-677 GEN
50/50
19.115
3151041BRUNSWICKG3
50/50
4.168
972187AH1-678 GEN
50/50
9.563
3150991CHESPKB
50/50
3.237
3150991CHESPKB
50/50
3.159
971223AH1-071 GEN
Solar/Wind Harmer
3.469
970933AG2-581 GEN
Solar/Wind Harmer
24.61
316294AC1-161 GEN
Solar/Wind Harmer
5.188
3145506HICKORY
Solar/Wind Harmer
1.167
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.175
316339AD2-160 GEN
Solar/Wind Harmer
0.466
316388AE2-253 GEN
Solar/Wind Harmer
0.906
3137176SLIGO L2192
Solar/Wind Harmer
1.155
3146456SLIGO L269
Solar/Wind Harmer
5.134
3130086AYDLETT
Solar/Wind Harmer
1.159
3144356SAPONY
Solar/Wind Harmer
2.424
316315AB2-025 C
Solar/Wind Harmer
0.232
3146386ELIZ CT
Solar/Wind Harmer
0.287
315835AF2-110_GEN
Solar/Wind Harmer
1.954
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.468
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.893
316349AD2-085 GEN
Solar/Wind Harmer
0.187
3146376EDENTON
Solar/Wind Harmer
1.232
3146376EDENTON
Solar/Wind Harmer
1.232
315742AE1-103 GEN
Solar/Wind Harmer
4.13
315614AA2-178 GEN
Solar/Wind Harmer
1.547
316365GEN2_N
Solar/Wind Harmer
0.597
316065AD1-022 GEN
Solar/Wind Harmer
12.234
3145893MURPHYS
Solar/Wind Harmer
1.766
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316140AB2-099
Solar/Wind Harmer
0.093
313506AB2-031 GEN
Solar/Wind Harmer
0.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
962571AG1-106 GEN
Solar/Wind Harmer
3.663
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.158
3145783HORNRTN
Solar/Wind Harmer
4.516
3145783HORNRTN
Solar/Wind Harmer
3.613
3145783HORNRTN
Solar/Wind Harmer
1.129
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.761
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.246
316005AA1-067
Solar/Wind Harmer
0.258
315724AD1-057 GEN
Solar/Wind Harmer
4.666
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
316336AC2-165 C
Solar/Wind Harmer
11.937
944641AF1-129 GEN
Adder
111.423
970301AG2-198 GEN
Solar/Wind Harmer
9.914
961601AG1-000A GEN
Solar/Wind Harmer
4.131
316049AB1-081 GEN
Solar/Wind Harmer
1.321
316263AC1-034 GEN
Solar/Wind Harmer
8.826
970323AG2-213 GEN
Solar/Wind Harmer
9.717
962561AG1-105 GEN
Solar/Wind Harmer
10.908
964791AG1-342 GEN
Solar/Wind Harmer
4.335
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
316118AC1-105 GEN
Solar/Wind Harmer
0.569
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.653
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
315976AC1-164 GENA
Solar/Wind Harmer
2.291
316169AC1-164_GENC
Solar/Wind Harmer
1.979
316156AD2-030 GEN
Solar/Wind Harmer
0.158
3150691DARBY 3
Adder
13.39
3150701DARBY 4
Adder
13.359
3150681DARBY 2
Adder
13.343
3150671DARBY 1
Adder
13.328
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3150341NORNECKC1
Adder
1.8
3150341NORNECKC1
Adder
1.786
316312AB1-027
Solar/Wind Harmer
0.284
942751AE2-291 GEN
Solar/Wind Harmer
8.407
3142296MT RD221
Adder
0.414
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316045AC1-158 PL2
Solar/Wind Helper
5.537
316450AC1-158 RIC
Solar/Wind Helper
0.461
316303AF2-085
50/50
5.781
315244AE2-183_ST
50/50
9.183
963041AG1-153 GEN
50/50
8.438
3151081ELIZAR1
50/50
28.39
3151091ELIZAR2
50/50
27.897
941591AE2-156 GEN
50/50
25.918
315779AE2-040
50/50
4.045
972263AH1-716 GEN
50/50
164.827
970533AG2-339 GEN
Solar/Wind Harmer
25.033
970673AG2-436 GEN
Solar/Wind Harmer
40.723
971967AH1-528 GEN
Solar/Wind Harmer
50.609
970085AG2-068 GEN
Solar/Wind Harmer
15.955
970581AG2-369 GEN
Solar/Wind Harmer
13.722
316316AC1-027 C
Solar/Wind Harmer
0.278
957871AF2-081 GEN
Solar/Wind Harmer
14.474
3146406KITTY HAWK
Solar/Wind Harmer
0.036
315814AE2-033 C
Solar/Wind Harmer
22.84
313526AB2-022
Solar/Wind Harmer
0.153
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.918
971283AH1-107 GEN
Solar/Wind Harmer
3.918
316311AC2-079 GEN
Solar/Wind Harmer
8.039
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.444
3143316POE
Solar/Wind Harmer
1.084
970657AG2-426 GEN
Solar/Wind Harmer
2.004
3151201GRAVEL4
Adder
19.505
3151221GRAVEL6
Adder
19.482
3151191GRAVEL3
Adder
19.258
3151211GRAVEL5
Adder
19.258
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.522
315733AD1-074 GEN2
Solar/Wind Harmer
1.522
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.889
3145893MURPHYS
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
0.264
316463AE2-346 GEN
Solar/Wind Harmer
0.223
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
315652AC1-086 GEN
Solar/Wind Harmer
28.319
3137643SOCKMAN
Solar/Wind Harmer
1.026
316426AA2-053 GEN
Solar/Wind Harmer
0.857
315697AD1-025 GEN
Solar/Wind Harmer
0.274
316258AE1-075 C
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.812
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.005
316159AE1-175 C
Solar/Wind Harmer
0.213
316210AC1-098 GEN
Solar/Wind Harmer
2.291
970831AG2-522 GEN
Solar/Wind Harmer
10.561
316274AC1-208 GEN
Solar/Wind Harmer
1.27
3145746EVERETS
Solar/Wind Harmer
0.963
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3138283WHITEMARSH
Solar/Wind Harmer
0.056
316327AA2-057 GEN
Solar/Wind Harmer
0.355
971285AH1-108 GEN
Adder
1.8
957861AF2-080 GEN
Solar/Wind Harmer
10.29
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
13.519
970681AG2-440 GEN
Solar/Wind Harmer
8.973
946301AF1-294 GEN
Solar/Wind Harmer
4.363
961791AG1-021 GEN
Solar/Wind Harmer
2.122
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.043
970189AG2-124 GEN
Solar/Wind Harmer
6.385
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3143873LANEXA
Solar/Wind Harmer
0.129
3141913WHIT STONE
Solar/Wind Harmer
0.209
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.122
3141783LANCAST
Solar/Wind Harmer
0.082
971845AH1-439 GEN
Solar/Wind Harmer
8.224
3141813NORNECK
Solar/Wind Harmer
0.172
972205AH1-687 GEN
Adder
6.299
316164AC1-076 GEN
Solar/Wind Helper
1.144
3151031BRUNSWICKG2
50/50
4.168
3151101ELIZAR3
50/50
28.753
3151161SURRY 1
50/50
10.916
944011AF1-069 GEN
Solar/Wind Harmer
19.938
970917AG2-570 GEN
Solar/Wind Harmer
26.983
944581AF1-123 GEN
Solar/Wind Harmer
66.518
944601AF1-125 GEN
Solar/Wind Harmer
65.493
3144873MCLAUGH
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.155
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.354
316246AF1-032 C
Solar/Wind Harmer
0.128
3144536CHRHLND
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970657AG2-426 GEN
Solar/Wind Harmer
6.123
3151171GRAVELC
Adder
3.748
315735AD1-075 GEN1
Solar/Wind Harmer
0.76
315813AE1-149 C
Solar/Wind Harmer
14.247
316478AD1-087 GEN
Solar/Wind Harmer
0.925
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.998
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.632
961611AG1-000B GEN
Solar/Wind Harmer
7.007
3146173TUNIS
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.259
316181AB2-040 GEN
Solar/Wind Harmer
0.368
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
316011AB1-132 GEN
Solar/Wind Harmer
4.67
3145963POPLR C
Solar/Wind Harmer
0.256
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
3.841
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315778AD1-151 GEN
Solar/Wind Harmer
20.108
316212AC1-099_GEN
Solar/Wind Harmer
1.277
316458AB2-190 GEN2
Solar/Wind Harmer
1.316
3145933PARMELE
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
8.364
3150861SPRUNCD
Adder
1.1
970133AG2-095 GEN
Solar/Wind Harmer
2.287
3146233WITAKRS
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.155
964241AG1-285 GEN
Solar/Wind Harmer
15.514
961601AG1-000A GEN
Solar/Wind Harmer
16.523
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
970257AG2-171 GEN
Solar/Wind Harmer
7.288
971775AH1-396 GEN
Solar/Wind Harmer
0.364
959311AF2-222 GEN
Solar/Wind Harmer
20.157
3142946ENON
Solar/Wind Harmer
0.074
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.687
3141873WAN 176
Solar/Wind Harmer
3.844
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.101
3143096IRON208
Adder
0.901
3143096IRON208
Adder
0.883
3141766HARMONY
Solar/Wind Harmer
2.864
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.123
316075AC2-137 C
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.822
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.173
970293AG2-193 GEN
Solar/Wind Harmer
2.062
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.742
316123AC1-075 GEN
Solar/Wind Harmer
0.223
3142416OLDCHRC
Solar/Wind Harmer
1.548
972003AH1-546 GEN
Solar/Wind Harmer
5.242
316223AC1-118
Solar/Wind Harmer
0.094
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.035
316473AC1-191 GEN
Solar/Wind Harmer
0.411
270494AE1-108_GEN
Solar/Wind Harmer
1.393
3147666LOUISA
Solar/Wind Helper
0.597
970119AG2-088 GEN
50/50
43.358
315243AE2-183_GT3
50/50
5.288
3151051BRUNSWICKS1
50/50
8.652
3151021BRUNSWICKG1
50/50
4.168
971451AH1-221 GEN
50/50
12.657
3150981CHESPKA
50/50
3.859
3152331SURRY 2
50/50
11.829
940641AE2-051 GEN
Solar/Wind Harmer
26.953
941031AE2-094 GEN
Solar/Wind Harmer
61.021
939411AE1-173 GEN
Solar/Wind Harmer
139.056
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.793
315773AC2-141 GEN
Solar/Wind Harmer
10.96
970087AG2-069 GEN
Solar/Wind Harmer
23.933
944591AF1-124 GEN
Solar/Wind Harmer
66.754
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.29
319010AE1-072 C
Solar/Wind Harmer
1.446
316093AE2-104_GEN
Solar/Wind Harmer
4.79
3146516WINFALL
Solar/Wind Harmer
0.919
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.101
3143526WINTERP
Solar/Wind Harmer
1.468
957481AF2-042 GEN
Solar/Wind Harmer
74.732
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.107
316381AD1-082 GEN
Solar/Wind Harmer
0.276
315816AE2-034 GEN
Solar/Wind Harmer
1.16
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.754
315693AD1-088 GEN
Solar/Wind Harmer
12.912
316023GEN1_S
Solar/Wind Harmer
0.597
3151171GRAVELC
Adder
2.851
315737AD1-076 GEN
Solar/Wind Harmer
3.427
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.651
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.055
3145893MURPHYS
Solar/Wind Harmer
1.173
961611AG1-000B GEN
Solar/Wind Harmer
13.781
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.512
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3145683EARLEYS
Solar/Wind Harmer
0.26
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3146263WOODLND
Solar/Wind Harmer
0.259
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.911
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
4.519
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.837
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.295
971069AG2-661 GEN
Solar/Wind Harmer
4.468
316132AB2-190 GEN1
Solar/Wind Harmer
1.316
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.92
971065AG2-659 GEN
Solar/Wind Harmer
10.482
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3150851SPRUNCC
Adder
1.1
316494AC1-189 GEN
Solar/Wind Harmer
0.806
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.048
316131AB2-060 GEN
Solar/Wind Harmer
0.731
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.825
3142053HEARTS
Solar/Wind Harmer
0.409
315785AD2-033 C
Solar/Wind Harmer
1.852
316034AC1-036 C
Solar/Wind Harmer
0.015
970401AG2-262 GEN
Solar/Wind Harmer
1.325
970685AG2-442 GEN
Solar/Wind Harmer
16.639
944631AF1-128 GEN
Adder
106.053
971563AH1-280 GEN
Solar/Wind Harmer
2.358
3144293JTRSVLE
Adder
0.528
3144293JTRSVLE
Adder
0.417
3142543TWELFTH
Solar/Wind Harmer
0.021
315975AC1-164 GENB
Solar/Wind Harmer
0.068
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3143096IRON208
Adder
0.901
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.859
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3138133OCRAN
Solar/Wind Harmer
0.125
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.523
962861AG1-135 GEN
Solar/Wind Harmer
5.976
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.112
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.705
3150351NORNECKC2
Adder
1.714
3142416OLDCHRC
Solar/Wind Harmer
0.415
3142416OLDCHRC
Solar/Wind Harmer
0.159
316337AD2-073 GEN
Solar/Wind Harmer
0.131
971377AH1-170 GEN
Solar/Wind Harmer
1.407
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
8.971
316447AC1-158 HLD
Solar/Wind Helper
3.807
316044AC1-158 PL1
Solar/Wind Helper
1.73
3147666LOUISA
Solar/Wind Helper
1.038
316192AB2-158 GEN
Solar/Wind Helper
1.716
LAGNLTFEXP_LAGN->PJM
CLTF
10.159
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.539
TVALTFEXP_TVA->PJM
CLTF
5.085
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.69
WECLTFEXP_WEC->PJM
CLTF
0.859
CPLELTFEXP_CPLE->PJM
CLTF
15.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.321
MECLTFEXP_MEC->PJM
CLTF
4.72
SIGELTFEXP_SIGE->PJM
CLTF
0.141

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3240.38
MW Contribution:
4.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
4.548
315241AE2-183_GT1
50/50
4.536
972185AH1-677 GEN
50/50
16.441
3151041BRUNSWICKG3
50/50
3.585
972187AH1-678 GEN
50/50
8.226
971223AH1-071 GEN
Solar/Wind Harmer
3.253
970933AG2-581 GEN
Solar/Wind Harmer
21.195
3143526WINTERP
Solar/Wind Harmer
1.349
3144356SAPONY
Solar/Wind Harmer
2.052
316315AB2-025 C
Solar/Wind Harmer
0.196
970099AG2-077 GEN
Solar/Wind Harmer
25.795
316313AB2-026
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.499
970119AG2-088 GEN
50/50
40.664
315243AE2-183_GT3
50/50
4.548
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.585
971451AH1-221 GEN
50/50
10.887
3151531CLOVER1
50/50
4.945
3143226MDLTHAN
Solar/Wind Harmer
0.305
941031AE2-094 GEN
Solar/Wind Harmer
52.48
940641AE2-051 GEN
Solar/Wind Harmer
22.661
939411AE1-173 GEN
Solar/Wind Harmer
114.417
970919AG2-571 GEN
Solar/Wind Harmer
9.282
3143526WINTERP
Solar/Wind Harmer
1.349
970087AG2-069 GEN
Solar/Wind Harmer
20.58
957481AF2-042 GEN
Solar/Wind Harmer
64.487
3143336POWHATN
Solar/Wind Harmer
4.235
315693AD1-088 GEN
Solar/Wind Harmer
11.17
316023GEN1_S
Solar/Wind Harmer
0.499
944591AF1-124 GEN
Solar/Wind Harmer
50.708
315773AC2-141 GEN
Solar/Wind Harmer
8.149
3151031BRUNSWICKG2
50/50
3.585
970413AG2-270 GEN
50/50
21.534
3151101ELIZAR3
50/50
21.865
944011AF1-069 GEN
Solar/Wind Harmer
17.147
970917AG2-570 GEN
Solar/Wind Harmer
23.205
3143336POWHATN
Solar/Wind Harmer
3.6
316478AD1-087 GEN
Solar/Wind Harmer
0.798
944581AF1-123 GEN
Solar/Wind Harmer
50.528
944601AF1-125 GEN
Solar/Wind Harmer
49.75
316017AA1-139 ULT1
Solar/Wind Harmer
0.118
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.563
3144873MCLAUGH
Solar/Wind Harmer
0.006
316246AF1-032 C
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.039
970657AG2-426 GEN
Solar/Wind Harmer
4.921
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.671
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
316181AB2-040 GEN
Solar/Wind Harmer
0.307
3156081AA2-088 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Solar/Wind Harmer
0.128
316011AB1-132 GEN
Solar/Wind Harmer
3.87
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.212
315735AD1-075 GEN1
Solar/Wind Harmer
0.602
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.21
3150861SPRUNCD
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
0.21
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.205
3151171GRAVELC
Adder
2.857
316212AC1-099_GEN
Solar/Wind Harmer
1.052
961611AG1-000B GEN
Solar/Wind Harmer
5.38
315722AD1-056 GEN
Solar/Wind Harmer
6.957
964241AG1-285 GEN
Solar/Wind Harmer
13.382
3145933PARMELE
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.318
971775AH1-396 GEN
Solar/Wind Harmer
0.316
959311AF2-222 GEN
Solar/Wind Harmer
17.494
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.698
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
316458AB2-190 GEN2
Solar/Wind Harmer
1.034
961601AG1-000A GEN
Solar/Wind Harmer
13.776
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.387
3144293JTRSVLE
Adder
0.461
3147133PAMPLIN
Solar/Wind Harmer
0.601
316294AC1-161 GEN
Solar/Wind Harmer
3.857
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
316339AD2-160 GEN
Solar/Wind Harmer
0.355
316388AE2-253 GEN
Solar/Wind Harmer
0.691
3137176SLIGO L2192
Solar/Wind Harmer
0.882
3146456SLIGO L269
Solar/Wind Harmer
3.923
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.32
3150991CHESPKB
Adder
2.265
316336AC2-165 C
Solar/Wind Harmer
11.186
3146386ELIZ CT
Solar/Wind Harmer
0.22
315835AF2-110_GEN
Solar/Wind Harmer
1.512
316349AD2-085 GEN
Solar/Wind Harmer
0.147
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
3.249
3146376EDENTON
Solar/Wind Harmer
0.96
3146376EDENTON
Solar/Wind Harmer
0.96
313506AB2-031 GEN
Solar/Wind Harmer
0.661
315614AA2-178 GEN
Solar/Wind Harmer
1.216
962571AG1-106 GEN
Solar/Wind Harmer
3.035
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.423
3145893MURPHYS
Solar/Wind Harmer
0.382
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.727
316140AB2-099
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.631
3145783HORNRTN
Solar/Wind Harmer
3.738
3145783HORNRTN
Solar/Wind Harmer
2.99
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.374
970301AG2-198 GEN
Solar/Wind Harmer
8.7
315724AD1-057 GEN
Solar/Wind Harmer
3.881
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316005AA1-067
Solar/Wind Harmer
0.211
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
8.424
944641AF1-129 GEN
Adder
93.755
962561AG1-105 GEN
Solar/Wind Harmer
9.4
3145493TOT1
Solar/Wind Harmer
0.452
3145453TOT5
Solar/Wind Harmer
0.271
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.737
3146843MT LREL
Solar/Wind Harmer
0.194
3146843MT LREL
Solar/Wind Harmer
0.194
961601AG1-000A GEN
Solar/Wind Harmer
3.444
316049AB1-081 GEN
Solar/Wind Harmer
1.102
316263AC1-034 GEN
Solar/Wind Harmer
7.36
958211AF2-115 GEN
Solar/Wind Harmer
2.317
3144293JTRSVLE
Adder
0.461
316118AC1-105 GEN
Solar/Wind Harmer
0.491
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.945
3150701DARBY 4
Adder
10.92
3150681DARBY 2
Adder
10.907
3150671DARBY 1
Adder
10.894
316156AD2-030 GEN
Solar/Wind Harmer
0.109
315976AC1-164 GENA
Solar/Wind Harmer
1.529
316169AC1-164_GENC
Solar/Wind Harmer
1.321
942751AE2-291 GEN
Solar/Wind Harmer
7.371
316312AB1-027
Solar/Wind Harmer
0.227
3142296MT RD221
Adder
0.389
3150341NORNECKC1
Adder
1.209
3150341NORNECKC1
Adder
1.2
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316045AC1-158 PL2
Solar/Wind Helper
5.223
316450AC1-158 RIC
Solar/Wind Helper
0.435
3146456SLIGO L269
Solar/Wind Harmer
0.222
319010AE1-072 C
Solar/Wind Harmer
1.105
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.039
3150981CHESPKA
Adder
2.766
316093AE2-104_GEN
Solar/Wind Harmer
3.705
316381AD1-082 GEN
Solar/Wind Harmer
0.222
960081AF2-299 GEN
Solar/Wind Harmer
2.104
3146516WINFALL
Solar/Wind Harmer
0.709
3146516WINFALL
Solar/Wind Harmer
0.219
3130156CHOWAN
Solar/Wind Harmer
0.216
316072AD1-144
Solar/Wind Harmer
0.077
3147043LAWRENC
Adder
1.937
315816AE2-034 GEN
Solar/Wind Harmer
0.912
3145663CRESWEL
Solar/Wind Harmer
0.598
971163AH1-040 GEN
Solar/Wind Harmer
17.102
3145893MURPHYS
Solar/Wind Harmer
0.85
3145893MURPHYS
Solar/Wind Harmer
0.945
315607AA1-063A GEN
Solar/Wind Harmer
0.427
315737AD1-076 GEN
Solar/Wind Harmer
2.715
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.502
3145336SMITFLD
Solar/Wind Harmer
0.843
3145796HORNRTN
Solar/Wind Harmer
0.694
3145796HORNRTN
Solar/Wind Harmer
0.21
3150851SPRUNCC
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.945
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.777
971065AG2-659 GEN
Solar/Wind Harmer
8.869
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.205
3151171GRAVELC
Adder
2.173
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316131AB2-060 GEN
Solar/Wind Harmer
0.629
961611AG1-000B GEN
Solar/Wind Harmer
10.58
3146293MARTNCO
Solar/Wind Harmer
0.186
315785AD2-033 C
Solar/Wind Harmer
1.604
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316034AC1-036 C
Solar/Wind Harmer
0.013
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.781
971069AG2-661 GEN
Solar/Wind Harmer
3.488
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970401AG2-262 GEN
Solar/Wind Harmer
1.142
970685AG2-442 GEN
Solar/Wind Harmer
14.501
316132AB2-190 GEN1
Solar/Wind Harmer
1.034
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
316359AB2-059 GEN
Solar/Wind Harmer
0.688
3142053HEARTS
Solar/Wind Harmer
0.341
971563AH1-280 GEN
Solar/Wind Harmer
2.059
3144293JTRSVLE
Adder
0.461
3144293JTRSVLE
Adder
0.364
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
971317AH1-138 GEN
Solar/Wind Harmer
1.336
970937AG2-583 GEN
Solar/Wind Harmer
10.788
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.242
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141766HARMONY
Solar/Wind Harmer
0.029
315975AC1-164 GENB
Solar/Wind Harmer
0.045
3138133OCRAN
Solar/Wind Harmer
0.086
3142416OLDCHRC
Solar/Wind Harmer
0.331
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.059
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.146
971377AH1-170 GEN
Solar/Wind Harmer
1.325
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.473
3150351NORNECKC2
Adder
1.151
316447AC1-158 HLD
Solar/Wind Helper
3.591
316044AC1-158 PL1
Solar/Wind Helper
1.632
3147666LOUISA
Solar/Wind Helper
0.979
316192AB2-158 GEN
Solar/Wind Helper
1.615
316303AF2-085
50/50
5.422
315244AE2-183_ST
50/50
7.898
963041AG1-153 GEN
50/50
7.258
315779AE2-040
50/50
3.424
3151541CLOVER2
50/50
4.907
970533AG2-339 GEN
Solar/Wind Harmer
21.529
970673AG2-436 GEN
Solar/Wind Harmer
35.024
971967AH1-528 GEN
Solar/Wind Harmer
43.56
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.6
971283AH1-107 GEN
Solar/Wind Harmer
3.6
970085AG2-068 GEN
Solar/Wind Harmer
13.72
970581AG2-369 GEN
Solar/Wind Harmer
11.799
315814AE2-033 C
Solar/Wind Harmer
19.325
316258AE1-075 C
Solar/Wind Harmer
0.178
3143316POE
Solar/Wind Harmer
0.914
316486AD2-202 GEN
Solar/Wind Harmer
0.234
316316AC1-027 C
Solar/Wind Harmer
0.212
3151081ELIZAR1
Adder
20.345
3151091ELIZAR2
Adder
19.992
957871AF2-081 GEN
Solar/Wind Harmer
11.051
3146406KITTY HAWK
Solar/Wind Harmer
0.028
313526AB2-022
Solar/Wind Harmer
0.118
3146396TANGLEW
Solar/Wind Harmer
0.606
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.314
970657AG2-426 GEN
Solar/Wind Harmer
1.61
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
315652AC1-086 GEN
Solar/Wind Harmer
23.467
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.206
315733AD1-074 GEN2
Solar/Wind Harmer
1.206
316426AA2-053 GEN
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.878
316463AE2-346 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.673
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.586
971445AH1-216 GEN
Solar/Wind Harmer
14.807
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.898
3146033SCOT NK
Solar/Wind Harmer
0.822
3151201GRAVEL4
Adder
14.866
3151221GRAVEL6
Adder
14.849
3151191GRAVEL3
Adder
14.678
3151211GRAVEL5
Adder
14.678
316210AC1-098 GEN
Solar/Wind Harmer
1.886
316274AC1-208 GEN
Solar/Wind Harmer
1.05
316327AA2-057 GEN
Solar/Wind Harmer
0.294
3145746EVERETS
Solar/Wind Harmer
0.787
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
315697AD1-025 GEN
Solar/Wind Harmer
0.213
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.469
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
11.764
970681AG2-440 GEN
Solar/Wind Harmer
7.808
946301AF1-294 GEN
Solar/Wind Harmer
3.81
961791AG1-021 GEN
Solar/Wind Harmer
1.853
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
316159AE1-175 C
Solar/Wind Harmer
0.147
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971845AH1-439 GEN
Solar/Wind Harmer
7.442
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.436
3141873WAN 176
Solar/Wind Harmer
0.03
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.891
3141813NORNECK
Solar/Wind Harmer
0.115
970133AG2-095 GEN
Solar/Wind Harmer
1.823
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.709
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316222AC1-221 GEN
Solar/Wind Harmer
0.708
316283AC2-100 C
Solar/Wind Harmer
0.334
971683AH1-343 GEN
Solar/Wind Harmer
6.222
3142946ENON
Solar/Wind Harmer
0.054
3146776BUCKING
Solar/Wind Harmer
0.058
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.765
316203AE2-005 GEN
Solar/Wind Harmer
0
3141873WAN 176
Solar/Wind Harmer
2.656
970293AG2-193 GEN
Solar/Wind Harmer
1.581
3141766HARMONY
Solar/Wind Harmer
1.962
316123AC1-075 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.038
972003AH1-546 GEN
Solar/Wind Harmer
4.881
3142416OLDCHRC
Solar/Wind Harmer
1.236
970221AG2-151 GEN
Solar/Wind Harmer
6.625
3150351NORNECKC2
Adder
1.171
316473AC1-191 GEN
Solar/Wind Harmer
0.382
3147666LOUISA
Solar/Wind Helper
0.563
LAGNLTFEXP_LAGN->PJM
CLTF
9.042
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.15
NYPJM->LTFIMP_NY
CLTF
2.4
LGEELTFEXP_LGEE->PJM
CLTF
1.575
WECLTFEXP_WEC->PJM
CLTF
0.802
TVALTFEXP_TVA->PJM
CLTF
4.533
CPLELTFEXP_CPLE->PJM
CLTF
13.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.506
MECLTFEXP_MEC->PJM
CLTF
4.337
SIGELTFEXP_SIGE->PJM
CLTF
0.13

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.87 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4987.58
MW Contribution:
6.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
122.63
3142366NRTHEST
50/50
0.835
3150781HOPHCF2
50/50
0.976
3150791HOPHCF3
50/50
0.976
971223AH1-071 GEN
Solar/Wind Harmer
2.831
3143526WINTERP
Solar/Wind Harmer
1.34
316294AC1-161 GEN
Solar/Wind Harmer
4.187
3150691DARBY 3
Adder
17.276
3150701DARBY 4
Adder
17.236
3150681DARBY 2
Adder
17.216
3150671DARBY 1
Adder
17.196
3150991CHESPKB
Adder
2.514
3150991CHESPKB
Adder
2.453
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3142296MT RD221
Adder
0.762
3145506HICKORY
Solar/Wind Harmer
0.956
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.741
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.203
316312AB1-027
Solar/Wind Harmer
0.422
316349AD2-085 GEN
Solar/Wind Harmer
0.158
3130086AYDLETT
Solar/Wind Harmer
0.949
315835AF2-110_GEN
Solar/Wind Harmer
1.619
972185AH1-677 GEN
Adder
13.245
3144356SAPONY
Solar/Wind Harmer
1.97
316315AB2-025 C
Solar/Wind Harmer
0.188
315976AC1-164 GENA
Solar/Wind Harmer
2.477
316169AC1-164_GENC
Solar/Wind Harmer
2.14
3146386ELIZ CT
Solar/Wind Harmer
0.235
972189AH1-679 GEN
Adder
3.909
972187AH1-678 GEN
Adder
6.642
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.348
315742AE1-103 GEN
Solar/Wind Harmer
3.403
316313AB2-026
Solar/Wind Harmer
0.141
3146376EDENTON
Solar/Wind Harmer
1.007
3146376EDENTON
Solar/Wind Harmer
1.007
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315614AA2-178 GEN
Solar/Wind Harmer
1.262
315673AE1-157 GEN
Solar/Wind Harmer
15.346
316365GEN2_N
Solar/Wind Harmer
0.484
3150391LDYSMT3
Adder
29.065
972195AH1-682 GEN
Adder
3.82
316336AC2-165 C
Solar/Wind Harmer
10.968
316065AD1-022 GEN
Solar/Wind Harmer
9.965
3145893MURPHYS
Solar/Wind Harmer
1.44
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.87
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
316140AB2-099
Solar/Wind Harmer
0.075
313506AB2-031 GEN
Solar/Wind Harmer
0.643
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
962571AG1-106 GEN
Solar/Wind Harmer
2.967
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.656
3145783HORNRTN
Solar/Wind Harmer
2.925
3145783HORNRTN
Solar/Wind Harmer
0.914
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.616
3150341NORNECKC1
Adder
2.14
3150341NORNECKC1
Adder
2.123
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.407
316005AA1-067
Solar/Wind Harmer
0.209
315724AD1-057 GEN
Solar/Wind Harmer
3.762
970323AG2-213 GEN
Solar/Wind Harmer
8.144
3145493TOT1
Solar/Wind Harmer
0.44
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.278
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
0.189
3147133PAMPLIN
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
1.062
316263AC1-034 GEN
Solar/Wind Harmer
7.094
962561AG1-105 GEN
Solar/Wind Harmer
8.822
964791AG1-342 GEN
Solar/Wind Harmer
3.5
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Harmer
0.058
316118AC1-105 GEN
Solar/Wind Harmer
0.458
972193AH1-681 GEN
Adder
3.343
942751AE2-291 GEN
Solar/Wind Harmer
7.275
3151731LOISA B
Adder
8.65
316045AC1-158 PL2
Solar/Wind Helper
16.749
316450AC1-158 RIC
Solar/Wind Helper
1.396
316006AB2-029 C
Solar/Wind Helper
0.141
316411AF1-147_GEN1
Solar/Wind Helper
0.794
316303AF2-085
50/50
4.718
971285AH1-108 GEN
50/50
1.988
972263AH1-716 GEN
50/50
138.906
3151081ELIZAR1
50/50
23.355
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
970533AG2-339 GEN
Solar/Wind Harmer
18.309
3151091ELIZAR2
Adder
21.627
315697AD1-025 GEN
Solar/Wind Harmer
0.258
970673AG2-436 GEN
Solar/Wind Harmer
29.845
316316AC1-027 C
Solar/Wind Harmer
0.228
971445AH1-216 GEN
Solar/Wind Harmer
16.871
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3151201GRAVEL4
Adder
17.422
3151221GRAVEL6
Adder
17.402
3151191GRAVEL3
Adder
17.202
3151211GRAVEL5
Adder
17.202
957871AF2-081 GEN
Solar/Wind Harmer
11.848
316311AC2-079 GEN
Solar/Wind Harmer
6.816
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.202
313526AB2-022
Solar/Wind Harmer
0.125
315814AE2-033 C
Solar/Wind Harmer
18.566
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971967AH1-528 GEN
Solar/Wind Harmer
37.439
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.137
970189AG2-124 GEN
Solar/Wind Harmer
6.721
316258AE1-075 C
Solar/Wind Harmer
0.169
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
970085AG2-068 GEN
Solar/Wind Harmer
11.838
970581AG2-369 GEN
Solar/Wind Harmer
10.181
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.24
315733AD1-074 GEN2
Solar/Wind Harmer
1.24
3150411LDYSMT5
Adder
29.211
3150381LDYSMT2
Adder
27.956
972213AH1-691 GEN
Adder
4.729
972215AH1-692 GEN
Adder
4.729
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.052
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315652AC1-086 GEN
Solar/Wind Harmer
22.938
3137643SOCKMAN
Solar/Wind Harmer
0.831
316426AA2-053 GEN
Solar/Wind Harmer
0.694
316486AD2-202 GEN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.657
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.204
3146033SCOT NK
Solar/Wind Harmer
0.814
316210AC1-098 GEN
Solar/Wind Harmer
1.852
970831AG2-522 GEN
Solar/Wind Harmer
8.499
316274AC1-208 GEN
Solar/Wind Harmer
1.026
3145746EVERETS
Solar/Wind Harmer
0.778
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316327AA2-057 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
8.299
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
11.473
970681AG2-440 GEN
Solar/Wind Harmer
7.615
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.747
961791AG1-021 GEN
Solar/Wind Harmer
1.823
971845AH1-439 GEN
Solar/Wind Harmer
8.142
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.192
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.386
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
20.065
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.077
3143096IRON208
50/50
1.055
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151101ELIZAR3
50/50
23.654
3151161SURRY 1
50/50
9.75
3147666LOUISA
Solar/Wind Harmer
0.591
944011AF1-069 GEN
Solar/Wind Harmer
14.582
315813AE1-149 C
Solar/Wind Harmer
12.858
970133AG2-095 GEN
Solar/Wind Harmer
2.311
944581AF1-123 GEN
Solar/Wind Harmer
54.154
944601AF1-125 GEN
Solar/Wind Harmer
53.32
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
315778AD1-151 GEN
Solar/Wind Harmer
19.211
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.096
961611AG1-000B GEN
Solar/Wind Harmer
6.389
970657AG2-426 GEN
Solar/Wind Harmer
5.372
3151171GRAVELC
Adder
3.348
970293AG2-193 GEN
Solar/Wind Harmer
2.545
3142946ENON
Solar/Wind Harmer
0.08
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.746
3142416OLDCHRC
Solar/Wind Harmer
2.302
3144216WINCHST
Adder
0.895
316246AF1-032 C
Solar/Wind Harmer
0.105
3150921YORKTN3
Adder
5.96
316075AC2-137 C
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.777
3141843SHACKLE
Adder
1.159
316203AE2-005 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.425
3146376EDENTON
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
3.02
3141873WAN 176
Solar/Wind Harmer
4.006
970917AG2-570 GEN
Solar/Wind Harmer
19.985
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.619
3150401LDYSMT4
Adder
29.12
3150371LDYSMT1
Adder
28.138
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3146263WOODLND
Solar/Wind Harmer
0.21
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
316011AB1-132 GEN
Solar/Wind Harmer
3.783
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.714
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.821
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.072
316212AC1-099_GEN
Solar/Wind Harmer
1.033
3145933PARMELE
Solar/Wind Harmer
0.199
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.743
964241AG1-285 GEN
Solar/Wind Harmer
12.775
970257AG2-171 GEN
Solar/Wind Harmer
6.108
971775AH1-396 GEN
Solar/Wind Harmer
0.305
959311AF2-222 GEN
Solar/Wind Harmer
16.954
3146233WITAKRS
Solar/Wind Harmer
0.954
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
3144293JTRSVLE
Adder
0.453
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.595
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.28
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.373
316223AC1-118
Solar/Wind Harmer
0.131
3141906WESTMOR
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.064
972003AH1-546 GEN
Solar/Wind Harmer
5.879
971683AH1-343 GEN
Solar/Wind Harmer
5.882
316222AC1-221 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.309
970221AG2-151 GEN
Solar/Wind Harmer
8.401
972255AH1-712 GEN
Adder
74.821
316123AC1-075 GEN
Solar/Wind Harmer
0.189
270494AE1-108_GEN
Solar/Wind Harmer
1.66
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
17.635
3151721LOISA A
Adder
8.605
3141196NOKESVL
Solar/Wind Helper
1.133
3152251N ANNA1
50/50
20.055
970119AG2-088 GEN
50/50
35.386
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.077
3152331SURRY 2
50/50
9.863
3150771HOPHCF1
50/50
0.976
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
3147666LOUISA
Solar/Wind Harmer
1.027
316192AB2-158 GEN
Solar/Wind Harmer
1.403
940641AE2-051 GEN
Solar/Wind Harmer
19.942
939411AE1-173 GEN
Solar/Wind Harmer
105.31
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.846
941031AE2-094 GEN
Solar/Wind Harmer
44.63
315671AE2-027_GEN
Solar/Wind Harmer
0.002
944591AF1-124 GEN
Solar/Wind Harmer
54.347
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
971069AG2-661 GEN
Solar/Wind Harmer
4.269
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
2.996
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.243
944631AF1-128 GEN
Adder
114.228
961611AG1-000B GEN
Solar/Wind Harmer
12.565
3151171GRAVELC
Adder
2.546
3146456SLIGO L269
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
0.617
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.084
319010AE1-072 C
Solar/Wind Harmer
1.184
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316093AE2-104_GEN
Solar/Wind Harmer
3.969
971317AH1-138 GEN
Solar/Wind Harmer
1.76
315975AC1-164 GENB
Solar/Wind Harmer
0.073
3146516WINFALL
Solar/Wind Harmer
0.753
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Solar/Wind Harmer
0.927
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3143336POWHATN
Solar/Wind Harmer
4.029
3130156CHOWAN
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
7.994
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.757
315816AE2-034 GEN
Solar/Wind Harmer
0.947
3145663CRESWEL
Solar/Wind Harmer
0.621
971163AH1-040 GEN
Solar/Wind Harmer
17.754
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.484
315737AD1-076 GEN
Solar/Wind Harmer
2.793
972197AH1-683 GEN
Adder
4.547
972219AH1-694 GEN
Adder
3.274
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.601
3145893MURPHYS
Solar/Wind Harmer
0.861
3145893MURPHYS
Solar/Wind Harmer
0.957
957481AF2-042 GEN
Solar/Wind Harmer
57.175
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.958
960081AF2-299 GEN
Solar/Wind Harmer
2.039
962861AG1-135 GEN
Solar/Wind Harmer
6.765
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.961
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.078
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
3147043LAWRENC
Adder
1.865
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.74
971065AG2-659 GEN
Solar/Wind Harmer
8.423
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316337AD2-073 GEN
Solar/Wind Harmer
0.168
316494AC1-189 GEN
Solar/Wind Harmer
0.65
316131AB2-060 GEN
Solar/Wind Harmer
0.597
315785AD2-033 C
Solar/Wind Harmer
1.545
316034AC1-036 C
Solar/Wind Harmer
0.013
970937AG2-583 GEN
Solar/Wind Harmer
11.679
970685AG2-442 GEN
Solar/Wind Harmer
14.197
3146233WITAKRS
Solar/Wind Harmer
0.756
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.844
971563AH1-280 GEN
Solar/Wind Harmer
2.025
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.358
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.663
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.069
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.68
3147623JAMES R
Solar/Wind Harmer
0.365
972277AH1-723 GEN
Adder
87.189
3151751LOISA D
Adder
8.65
316447AC1-158 HLD
Solar/Wind Helper
11.517
316044AC1-158 PL1
Solar/Wind Helper
5.234
316415AF1-147_GEN2
Solar/Wind Helper
0.794
LAGNLTFEXP_LAGN->PJM
CLTF
8.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.444
NYPJM->LTFIMP_NY
CLTF
3.279
LGEELTFEXP_LGEE->PJM
CLTF
1.357
TVALTFEXP_TVA->PJM
CLTF
4.232
WECLTFEXP_WEC->PJM
CLTF
0.655
CPLELTFEXP_CPLE->PJM
CLTF
12.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.367
MECLTFEXP_MEC->PJM
CLTF
3.719
SIGELTFEXP_SIGE->PJM
CLTF
0.113

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.04 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4960.85
MW Contribution:
6.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
124.896
3142366NRTHEST
50/50
0.852
3150781HOPHCF2
50/50
0.994
3150791HOPHCF3
50/50
0.994
3150691DARBY 3
50/50
18.706
3150701DARBY 4
50/50
18.663
971223AH1-071 GEN
Solar/Wind Harmer
2.872
3143526WINTERP
Solar/Wind Harmer
1.362
316294AC1-161 GEN
Solar/Wind Harmer
4.26
3150681DARBY 2
Adder
17.567
3150671DARBY 1
Adder
17.547
3142296MT RD221
Adder
0.778
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.972
3145506HICKORY
Solar/Wind Harmer
0.583
3145506HICKORY
Solar/Wind Harmer
0.146
316312AB1-027
Solar/Wind Harmer
0.431
316339AD2-160 GEN
Solar/Wind Harmer
0.388
316388AE2-253 GEN
Solar/Wind Harmer
0.754
3137176SLIGO L2192
Solar/Wind Harmer
0.962
3146456SLIGO L269
Solar/Wind Harmer
4.275
316349AD2-085 GEN
Solar/Wind Harmer
0.161
3130086AYDLETT
Solar/Wind Harmer
0.965
315976AC1-164 GENA
Solar/Wind Harmer
2.528
316169AC1-164_GENC
Solar/Wind Harmer
2.185
315835AF2-110_GEN
Solar/Wind Harmer
1.647
972185AH1-677 GEN
Adder
13.436
3144356SAPONY
Solar/Wind Harmer
2.002
316315AB2-025 C
Solar/Wind Harmer
0.191
3146386ELIZ CT
Solar/Wind Harmer
0.239
972189AH1-679 GEN
Adder
4.004
972187AH1-678 GEN
Adder
6.738
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.61
315742AE1-103 GEN
Solar/Wind Harmer
3.46
3146376EDENTON
Solar/Wind Harmer
1.024
3146376EDENTON
Solar/Wind Harmer
1.024
316156AD2-030 GEN
Solar/Wind Harmer
0.168
316313AB2-026
Solar/Wind Harmer
0.143
315673AE1-157 GEN
Solar/Wind Harmer
15.789
315614AA2-178 GEN
Solar/Wind Harmer
1.284
3150391LDYSMT3
Adder
29.965
972195AH1-682 GEN
Adder
3.938
316365GEN2_N
Solar/Wind Harmer
0.492
316065AD1-022 GEN
Solar/Wind Harmer
10.129
316336AC2-165 C
Solar/Wind Harmer
11.098
3145893MURPHYS
Solar/Wind Harmer
1.464
3145893MURPHYS
Solar/Wind Harmer
0.393
970099AG2-077 GEN
Solar/Wind Harmer
23.191
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
316140AB2-099
Solar/Wind Harmer
0.077
313506AB2-031 GEN
Solar/Wind Harmer
0.653
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.127
962571AG1-106 GEN
Solar/Wind Harmer
3.014
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.261
3145783HORNRTN
Solar/Wind Harmer
3.713
3145783HORNRTN
Solar/Wind Harmer
2.97
3145783HORNRTN
Solar/Wind Harmer
0.928
3145783HORNRTN
Solar/Wind Harmer
0.371
3150341NORNECKC1
Adder
2.187
3150341NORNECKC1
Adder
2.169
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.405
3145933PARMELE
Solar/Wind Harmer
0.202
970301AG2-198 GEN
Solar/Wind Harmer
8.511
316005AA1-067
Solar/Wind Harmer
0.212
315724AD1-057 GEN
Solar/Wind Harmer
3.821
970323AG2-213 GEN
Solar/Wind Harmer
8.251
3145493TOT1
Solar/Wind Harmer
0.447
3145453TOT5
Solar/Wind Harmer
0.268
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.307
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
961601AG1-000A GEN
Solar/Wind Harmer
3.372
316049AB1-081 GEN
Solar/Wind Harmer
1.078
316263AC1-034 GEN
Solar/Wind Harmer
7.204
962561AG1-105 GEN
Solar/Wind Harmer
8.945
964791AG1-342 GEN
Solar/Wind Harmer
3.549
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
316118AC1-105 GEN
Solar/Wind Harmer
0.464
3146776BUCKING
Solar/Wind Harmer
0.722
3146776BUCKING
Solar/Wind Harmer
0.058
972193AH1-681 GEN
Adder
3.418
942751AE2-291 GEN
Solar/Wind Harmer
7.377
3151731LOISA B
Adder
8.227
316045AC1-158 PL2
Solar/Wind Helper
16.87
316303AF2-085
50/50
4.786
971285AH1-108 GEN
50/50
2.024
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.634
971283AH1-107 GEN
Solar/Wind Harmer
3.634
3143316POE
Solar/Wind Harmer
0.979
970533AG2-339 GEN
Solar/Wind Harmer
18.574
315697AD1-025 GEN
Solar/Wind Harmer
0.263
3151081ELIZAR1
Adder
22.39
3151091ELIZAR2
Adder
22.001
971445AH1-216 GEN
Solar/Wind Harmer
17.171
316316AC1-027 C
Solar/Wind Harmer
0.232
3151201GRAVEL4
Adder
17.737
3151221GRAVEL6
Adder
17.716
3151191GRAVEL3
Adder
17.512
3151211GRAVEL5
Adder
17.512
970657AG2-426 GEN
Solar/Wind Harmer
1.788
970673AG2-436 GEN
Solar/Wind Harmer
30.277
957871AF2-081 GEN
Solar/Wind Harmer
12.052
316311AC2-079 GEN
Solar/Wind Harmer
6.933
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.206
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.238
3146486SUNBURY
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
18.861
3146396TANGLEW
Solar/Wind Harmer
0.657
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971967AH1-528 GEN
Solar/Wind Harmer
37.977
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
970189AG2-124 GEN
Solar/Wind Harmer
6.858
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
316258AE1-075 C
Solar/Wind Harmer
0.171
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
970085AG2-068 GEN
Solar/Wind Harmer
12.01
970581AG2-369 GEN
Solar/Wind Harmer
10.328
3141783LANCAST
Solar/Wind Harmer
0.134
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.115
3150381LDYSMT2
Adder
28.821
972213AH1-691 GEN
Adder
4.875
972215AH1-692 GEN
Adder
4.875
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.261
315733AD1-074 GEN2
Solar/Wind Harmer
1.261
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.185
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
316463AE2-346 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
0.451
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.429
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315652AC1-086 GEN
Solar/Wind Harmer
23.301
3137643SOCKMAN
Solar/Wind Harmer
0.844
316426AA2-053 GEN
Solar/Wind Harmer
0.705
316486AD2-202 GEN
Solar/Wind Harmer
0.213
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.667
3145796HORNRTN
Solar/Wind Harmer
0.083
3146033SCOT NK
Solar/Wind Harmer
0.827
316210AC1-098 GEN
Solar/Wind Harmer
1.881
316274AC1-208 GEN
Solar/Wind Harmer
1.042
970831AG2-522 GEN
Solar/Wind Harmer
8.626
3145746EVERETS
Solar/Wind Harmer
0.79
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316327AA2-057 GEN
Solar/Wind Harmer
0.29
957861AF2-080 GEN
Solar/Wind Harmer
8.43
3144303KENBRDG
Solar/Wind Harmer
0.155
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
11.621
970681AG2-440 GEN
Solar/Wind Harmer
7.713
946301AF1-294 GEN
Solar/Wind Harmer
3.794
961791AG1-021 GEN
Solar/Wind Harmer
1.846
971845AH1-439 GEN
Solar/Wind Harmer
8.222
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.248
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.205
315651AD1-115 GEN
Solar/Wind Helper
1.033
3138216PACIFIC
Solar/Wind Helper
0.039
316450AC1-158 RIC
Solar/Wind Helper
1.406
316006AB2-029 C
Solar/Wind Helper
0.153
316411AF1-147_GEN1
Solar/Wind Helper
0.806
3152261N ANNA2
50/50
20.176
3150861SPRUNCD
50/50
1.237
3143096IRON208
50/50
1.098
3143096IRON208
50/50
1.076
3150801HOPHCF4
50/50
1.448
3150761HOPPOLC
50/50
0.622
3151161SURRY 1
50/50
9.926
3147666LOUISA
Solar/Wind Harmer
0.584
944011AF1-069 GEN
Solar/Wind Harmer
14.794
315813AE1-149 C
Solar/Wind Harmer
13.082
970133AG2-095 GEN
Solar/Wind Harmer
2.355
316458AB2-190 GEN2
Solar/Wind Harmer
1.306
944581AF1-123 GEN
Solar/Wind Harmer
55.085
944601AF1-125 GEN
Solar/Wind Harmer
54.236
315778AD1-151 GEN
Solar/Wind Harmer
19.565
3151101ELIZAR3
Adder
22.676
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.505
3145336SMITFLD
Solar/Wind Harmer
0.098
3151171GRAVELC
Adder
3.409
970657AG2-426 GEN
Solar/Wind Harmer
5.465
970293AG2-193 GEN
Solar/Wind Harmer
2.597
3142946ENON
Solar/Wind Harmer
0.081
3142416OLDCHRC
Solar/Wind Harmer
2.351
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3144216WINCHST
Adder
0.912
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
0.241
971153AH1-033 GEN
Solar/Wind Harmer
2.793
3150921YORKTN3
Adder
6.071
316246AF1-032 C
Solar/Wind Harmer
0.107
316321Z2-027
Solar/Wind Harmer
0.042
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.183
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.082
3146376EDENTON
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
4.087
3143336POWHATN
Solar/Wind Harmer
3.467
970917AG2-570 GEN
Solar/Wind Harmer
20.275
3150401LDYSMT4
Adder
30.021
3150371LDYSMT1
Adder
29.008
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.629
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.366
3145893MURPHYS
Solar/Wind Harmer
0.219
3146173TUNIS
Solar/Wind Harmer
0.217
3146263WOODLND
Solar/Wind Harmer
0.213
316181AB2-040 GEN
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
316011AB1-132 GEN
Solar/Wind Harmer
3.842
3145963POPLR C
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.724
3150351NORNECKC2
Adder
2.117
3145796HORNRTN
Solar/Wind Harmer
0.834
3145796HORNRTN
Solar/Wind Harmer
0.208
316212AC1-099_GEN
Solar/Wind Harmer
1.049
3145933PARMELE
Solar/Wind Harmer
0.202
971781AH1-399 GEN
Solar/Wind Harmer
0.266
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
315722AD1-056 GEN
Solar/Wind Harmer
6.849
964241AG1-285 GEN
Solar/Wind Harmer
12.949
970257AG2-171 GEN
Solar/Wind Harmer
6.188
971775AH1-396 GEN
Solar/Wind Harmer
0.309
959311AF2-222 GEN
Solar/Wind Harmer
17.176
3146233WITAKRS
Solar/Wind Harmer
0.969
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
0.602
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
13.487
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.189
971623AH1-311 GEN
Solar/Wind Harmer
0.379
316223AC1-118
Solar/Wind Harmer
0.134
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
5.927
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316222AC1-221 GEN
Solar/Wind Harmer
0.664
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.466
972255AH1-712 GEN
Adder
76.496
316123AC1-075 GEN
Solar/Wind Harmer
0.192
270494AE1-108_GEN
Solar/Wind Harmer
1.675
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
16.773
3151721LOISA A
Adder
8.185
3150331BIRCHWDA
Adder
19.202
3141196NOKESVL
Solar/Wind Helper
1.154
3152251N ANNA1
50/50
20.166
970119AG2-088 GEN
50/50
35.895
3150851SPRUNCC
50/50
1.237
3143096IRON208
50/50
1.098
3152331SURRY 2
50/50
10.043
3150771HOPHCF1
50/50
0.994
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.362
3147666LOUISA
Solar/Wind Harmer
1.015
940641AE2-051 GEN
Solar/Wind Harmer
20.241
939411AE1-173 GEN
Solar/Wind Harmer
106.947
3142543TWELFTH
Solar/Wind Harmer
0.024
315773AC2-141 GEN
Solar/Wind Harmer
9
316192AB2-158 GEN
Solar/Wind Harmer
1.386
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
45.277
316132AB2-190 GEN1
Solar/Wind Harmer
1.306
944591AF1-124 GEN
Solar/Wind Harmer
55.281
971069AG2-661 GEN
Solar/Wind Harmer
4.348
944631AF1-128 GEN
Adder
116.464
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
3.048
961611AG1-000B GEN
Solar/Wind Harmer
12.793
3145336SMITFLD
Solar/Wind Harmer
0.975
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3151171GRAVELC
Adder
2.592
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.241
316072AD1-144
Solar/Wind Harmer
0.086
319010AE1-072 C
Solar/Wind Harmer
1.204
315975AC1-164 GENB
Solar/Wind Harmer
0.075
971317AH1-138 GEN
Solar/Wind Harmer
1.794
316093AE2-104_GEN
Solar/Wind Harmer
4.037
3142433PROV 92
Solar/Wind Harmer
0.946
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.765
3146516WINFALL
Solar/Wind Harmer
0.236
971777AH1-397 GEN
Solar/Wind Harmer
0.611
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.079
970919AG2-571 GEN
Solar/Wind Harmer
8.11
3138133OCRAN
Solar/Wind Harmer
0.136
315816AE2-034 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.631
971163AH1-040 GEN
Solar/Wind Harmer
18.05
970087AG2-069 GEN
Solar/Wind Harmer
18.014
972197AH1-683 GEN
Adder
4.688
972219AH1-694 GEN
Adder
3.375
315737AD1-076 GEN
Solar/Wind Harmer
2.839
316023GEN1_S
Solar/Wind Harmer
0.492
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.677
3145893MURPHYS
Solar/Wind Harmer
0.875
3145893MURPHYS
Solar/Wind Harmer
0.973
957481AF2-042 GEN
Solar/Wind Harmer
57.978
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.973
962861AG1-135 GEN
Solar/Wind Harmer
6.908
960081AF2-299 GEN
Solar/Wind Harmer
2.07
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.108
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.431
3146263WOODLND
Solar/Wind Harmer
0.213
315693AD1-088 GEN
Solar/Wind Harmer
10.217
3141726DUNNSVL
Solar/Wind Harmer
0.846
3145963POPLR C
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Adder
1.893
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.082
3145796HORNRTN
Solar/Wind Harmer
0.688
3145796HORNRTN
Solar/Wind Harmer
0.208
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.751
971065AG2-659 GEN
Solar/Wind Harmer
8.547
316337AD2-073 GEN
Solar/Wind Harmer
0.171
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.66
316131AB2-060 GEN
Solar/Wind Harmer
0.605
315785AD2-033 C
Solar/Wind Harmer
1.566
316034AC1-036 C
Solar/Wind Harmer
0.013
3146233WITAKRS
Solar/Wind Harmer
0.768
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.857
970685AG2-442 GEN
Solar/Wind Harmer
14.378
970937AG2-583 GEN
Solar/Wind Harmer
11.795
971563AH1-280 GEN
Solar/Wind Harmer
2.051
3144293JTRSVLE
Adder
0.459
3144293JTRSVLE
Adder
0.362
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.674
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.085
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.463
971377AH1-170 GEN
Solar/Wind Harmer
1.693
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
89.141
3151751LOISA D
Adder
8.227
970223AG2-152 GEN
Solar/Wind Harmer
7.994
316447AC1-158 HLD
Solar/Wind Helper
11.601
316044AC1-158 PL1
Solar/Wind Helper
5.272
316415AF1-147_GEN2
Solar/Wind Helper
0.806
LAGNLTFEXP_LAGN->PJM
CLTF
8.482
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.834
NYPJM->LTFIMP_NY
CLTF
3.323
LGEELTFEXP_LGEE->PJM
CLTF
1.377
TVALTFEXP_TVA->PJM
CLTF
4.295
WECLTFEXP_WEC->PJM
CLTF
0.665
CPLELTFEXP_CPLE->PJM
CLTF
12.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.579
MECLTFEXP_MEC->PJM
CLTF
3.774
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.67 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3470.14
MW Contribution:
4.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
2.994
315241AE2-183_GT1
50/50
2.986
972185AH1-677 GEN
50/50
10.823
3151041BRUNSWICKG3
50/50
2.365
972187AH1-678 GEN
50/50
5.426
3150991CHESPKB
50/50
1.987
3150991CHESPKB
50/50
1.94
971223AH1-071 GEN
Solar/Wind Harmer
2.178
3143526WINTERP
Solar/Wind Harmer
1.011
316294AC1-161 GEN
Solar/Wind Harmer
3.119
3144356SAPONY
Solar/Wind Harmer
1.492
316315AB2-025 C
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.713
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
944641AF1-129 GEN
Adder
84.836
316339AD2-160 GEN
Solar/Wind Harmer
0.284
316388AE2-253 GEN
Solar/Wind Harmer
0.553
3137176SLIGO L2192
Solar/Wind Harmer
0.705
3146456SLIGO L269
Solar/Wind Harmer
3.136
3130086AYDLETT
Solar/Wind Harmer
0.708
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
14.117
315835AF2-110_GEN
Solar/Wind Harmer
1.208
3146386ELIZ CT
Solar/Wind Harmer
0.175
316313AB2-026
Solar/Wind Harmer
0.108
3146516WINFALL
Solar/Wind Harmer
0.173
3146516WINFALL
Solar/Wind Harmer
0.173
3146516WINFALL
Solar/Wind Harmer
0.173
3142366NRTHEST
Adder
0.564
3146626S HERTFORD
Solar/Wind Harmer
0.172
3146626S HERTFORD
Solar/Wind Harmer
0.172
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.373
3150701DARBY 4
Adder
12.344
3150681DARBY 2
Adder
12.33
3150671DARBY 1
Adder
12.316
315742AE1-103 GEN
Solar/Wind Harmer
2.547
3146376EDENTON
Solar/Wind Harmer
0.753
3146376EDENTON
Solar/Wind Harmer
0.753
3142296MT RD221
Adder
0.536
315976AC1-164 GENA
Solar/Wind Harmer
1.77
316169AC1-164_GENC
Solar/Wind Harmer
1.529
316312AB1-027
Solar/Wind Harmer
0.298
315614AA2-178 GEN
Solar/Wind Harmer
0.946
316336AC2-165 C
Solar/Wind Harmer
8.407
316365GEN2_N
Solar/Wind Harmer
0.366
970099AG2-077 GEN
Solar/Wind Harmer
17.56
316065AD1-022 GEN
Solar/Wind Harmer
7.478
316156AD2-030 GEN
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
1.083
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.16
3146173TUNIS
Solar/Wind Harmer
0.16
316140AB2-099
Solar/Wind Harmer
0.057
972189AH1-679 GEN
Adder
2.669
313506AB2-031 GEN
Solar/Wind Harmer
0.486
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
962571AG1-106 GEN
Solar/Wind Harmer
2.241
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.763
3145783HORNRTN
Solar/Wind Harmer
2.21
3145783HORNRTN
Solar/Wind Harmer
0.691
3145783HORNRTN
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
0.465
970301AG2-198 GEN
Solar/Wind Harmer
6.437
3145933PARMELE
Solar/Wind Harmer
0.3
3145933PARMELE
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.844
316005AA1-067
Solar/Wind Harmer
0.157
970323AG2-213 GEN
Solar/Wind Harmer
6.213
3150341NORNECKC1
Adder
1.523
3150341NORNECKC1
Adder
1.511
958211AF2-115 GEN
Solar/Wind Harmer
1.739
3144293JTRSVLE
Adder
0.346
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.199
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.911
961601AG1-000A GEN
Solar/Wind Harmer
2.512
316049AB1-081 GEN
Solar/Wind Harmer
0.803
316263AC1-034 GEN
Solar/Wind Harmer
5.367
962561AG1-105 GEN
Solar/Wind Harmer
6.727
964791AG1-342 GEN
Solar/Wind Harmer
2.669
316303AF2-085
50/50
3.63
971285AH1-108 GEN
50/50
1.467
315244AE2-183_ST
50/50
5.2
963041AG1-153 GEN
50/50
4.788
3151081ELIZAR1
50/50
17.404
3151091ELIZAR2
50/50
17.102
941591AE2-156 GEN
50/50
15.904
315779AE2-040
50/50
2.49
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.699
971283AH1-107 GEN
Solar/Wind Harmer
2.699
970533AG2-339 GEN
Solar/Wind Harmer
14.109
970673AG2-436 GEN
Solar/Wind Harmer
22.993
3143316POE
Solar/Wind Harmer
0.72
971967AH1-528 GEN
Solar/Wind Harmer
28.823
316316AC1-027 C
Solar/Wind Harmer
0.17
970657AG2-426 GEN
Solar/Wind Harmer
1.309
315814AE2-033 C
Solar/Wind Harmer
14.057
957871AF2-081 GEN
Solar/Wind Harmer
8.839
971445AH1-216 GEN
Solar/Wind Harmer
12.494
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316311AC2-079 GEN
Solar/Wind Harmer
5.081
3151201GRAVEL4
Adder
12.861
3151221GRAVEL6
Adder
12.846
3151191GRAVEL3
Adder
12.698
3151211GRAVEL5
Adder
12.698
315697AD1-025 GEN
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.094
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
3146396TANGLEW
Solar/Wind Harmer
0.482
3145176PASQUOTANK
Solar/Wind Harmer
0.108
316258AE1-075 C
Solar/Wind Harmer
0.13
316159AE1-175 C
Solar/Wind Harmer
0.147
970085AG2-068 GEN
Solar/Wind Harmer
9.103
970581AG2-369 GEN
Solar/Wind Harmer
7.829
3130156CHOWAN
Solar/Wind Harmer
0.169
3130156CHOWAN
Solar/Wind Harmer
0.169
3138283WHITEMARSH
Solar/Wind Harmer
0.039
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.93
315733AD1-074 GEN2
Solar/Wind Harmer
0.93
970189AG2-124 GEN
Solar/Wind Harmer
4.836
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.045
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
316463AE2-346 GEN
Solar/Wind Harmer
0.136
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.159
3138133OCRAN
Solar/Wind Harmer
0.048
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
316486AD2-202 GEN
Solar/Wind Harmer
0.161
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.328
3137643SOCKMAN
Solar/Wind Harmer
0.629
316426AA2-053 GEN
Solar/Wind Harmer
0.524
3145796HORNRTN
Solar/Wind Harmer
0.496
3145796HORNRTN
Solar/Wind Harmer
0.062
3146033SCOT NK
Solar/Wind Harmer
0.614
316210AC1-098 GEN
Solar/Wind Harmer
1.398
970831AG2-522 GEN
Solar/Wind Harmer
6.453
316274AC1-208 GEN
Solar/Wind Harmer
0.775
3145746EVERETS
Solar/Wind Harmer
0.586
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316327AA2-057 GEN
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.116
3141813NORNECK
Solar/Wind Harmer
0.145
957861AF2-080 GEN
Solar/Wind Harmer
6.264
970683AG2-441 GEN
Solar/Wind Harmer
8.755
970681AG2-440 GEN
Solar/Wind Harmer
5.811
946301AF1-294 GEN
Solar/Wind Harmer
2.86
961791AG1-021 GEN
Solar/Wind Harmer
1.391
3145573BETHELC
Solar/Wind Harmer
0.143
3145573BETHELC
Solar/Wind Harmer
0.143
971845AH1-439 GEN
Solar/Wind Harmer
6.215
3150411LDYSMT5
Adder
18.379
3150381LDYSMT2
Adder
17.59
972213AH1-691 GEN
Adder
2.976
972215AH1-692 GEN
Adder
2.976
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
972205AH1-687 GEN
Adder
5.48
316164AC1-076 GEN
Solar/Wind Helper
1.643
315651AD1-115 GEN
Solar/Wind Helper
0.751
3152261N ANNA2
50/50
17.378
3150861SPRUNCD
50/50
0.897
3151031BRUNSWICKG2
50/50
2.365
3151101ELIZAR3
50/50
17.627
3147666LOUISA
Solar/Wind Harmer
0.506
944011AF1-069 GEN
Solar/Wind Harmer
11.238
944581AF1-123 GEN
Solar/Wind Harmer
40.402
944601AF1-125 GEN
Solar/Wind Harmer
39.78
315813AE1-149 C
Solar/Wind Harmer
9.563
3144873MCLAUGH
Solar/Wind Harmer
0.004
3144536CHRHLND
Solar/Wind Harmer
0.027
970657AG2-426 GEN
Solar/Wind Harmer
3.999
316017AA1-139 ULT1
Solar/Wind Harmer
0.095
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.049
316246AF1-032 C
Solar/Wind Harmer
0.079
3151171GRAVELC
Adder
2.471
961611AG1-000B GEN
Solar/Wind Harmer
4.709
315778AD1-151 GEN
Solar/Wind Harmer
14.112
316458AB2-190 GEN2
Solar/Wind Harmer
0.94
970133AG2-095 GEN
Solar/Wind Harmer
1.692
3143096IRON208
Adder
0.736
3143096IRON208
Adder
0.721
316321Z2-027
Solar/Wind Harmer
0.031
3144216WINCHST
Adder
0.656
3143336POWHATN
Solar/Wind Harmer
2.627
3146516WINFALL
Solar/Wind Harmer
0.173
3150921YORKTN3
Adder
4.362
970917AG2-570 GEN
Solar/Wind Harmer
15.373
3146626S HERTFORD
Solar/Wind Harmer
0.172
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.057
970293AG2-193 GEN
Solar/Wind Harmer
1.819
3146376EDENTON
Solar/Wind Harmer
0.169
316075AC2-137 C
Solar/Wind Harmer
0.045
3142416OLDCHRC
Solar/Wind Harmer
1.626
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.464
3141843SHACKLE
Adder
0.834
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
2.17
3141873WAN 176
Solar/Wind Harmer
2.884
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.546
3146173TUNIS
Solar/Wind Harmer
0.16
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
316011AB1-132 GEN
Solar/Wind Harmer
2.857
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.62
3145796HORNRTN
Solar/Wind Harmer
0.155
316212AC1-099_GEN
Solar/Wind Harmer
0.78
3145933PARMELE
Solar/Wind Harmer
0.15
315722AD1-056 GEN
Solar/Wind Harmer
5.099
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
964241AG1-285 GEN
Solar/Wind Harmer
9.742
970257AG2-171 GEN
Solar/Wind Harmer
4.66
971775AH1-396 GEN
Solar/Wind Harmer
0.233
959311AF2-222 GEN
Solar/Wind Harmer
12.935
3150351NORNECKC2
Adder
1.474
3144293JTRSVLE
Adder
0.346
3147133PAMPLIN
Solar/Wind Harmer
0.454
942461AE2-259 GEN
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.721
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
0.143
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.047
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.282
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
18.288
972195AH1-682 GEN
Adder
2.403
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316118AC1-105 GEN
Solar/Wind Harmer
0.349
316045AC1-158 PL2
Solar/Wind Helper
17.222
316450AC1-158 RIC
Solar/Wind Helper
1.435
316006AB2-029 C
Solar/Wind Helper
0.113
971781AH1-399 GEN
Solar/Wind Harmer
0.18
3150401LDYSMT4
Adder
18.322
3150371LDYSMT1
Adder
17.704
3146776BUCKING
Solar/Wind Harmer
0.049
316223AC1-118
Solar/Wind Harmer
0.092
3141906WESTMOR
Solar/Wind Harmer
0.052
972003AH1-546 GEN
Solar/Wind Harmer
4.48
971683AH1-343 GEN
Solar/Wind Harmer
4.474
316222AC1-221 GEN
Solar/Wind Harmer
0.498
316283AC2-100 C
Solar/Wind Harmer
0.235
970221AG2-151 GEN
Solar/Wind Harmer
6.378
3152251N ANNA1
50/50
17.37
970119AG2-088 GEN
50/50
27.228
3150851SPRUNCC
50/50
0.897
315243AE2-183_GT3
50/50
2.994
3151051BRUNSWICKS1
50/50
4.91
3151021BRUNSWICKG1
50/50
2.365
971451AH1-221 GEN
50/50
7.182
3150981CHESPKA
50/50
2.369
3147666LOUISA
Solar/Wind Harmer
0.88
316192AB2-158 GEN
Solar/Wind Harmer
1.202
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.011
940641AE2-051 GEN
Solar/Wind Harmer
15.286
939411AE1-173 GEN
Solar/Wind Harmer
80.194
941031AE2-094 GEN
Solar/Wind Harmer
34.394
315773AC2-141 GEN
Solar/Wind Harmer
6.589
944591AF1-124 GEN
Solar/Wind Harmer
40.546
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.032
316381AD1-082 GEN
Solar/Wind Harmer
0.181
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.017
3145336SMITFLD
Solar/Wind Harmer
0.71
3146456SLIGO L269
Solar/Wind Harmer
0.177
319010AE1-072 C
Solar/Wind Harmer
0.883
3151171GRAVELC
Adder
1.88
316072AD1-144
Solar/Wind Harmer
0.063
961611AG1-000B GEN
Solar/Wind Harmer
9.261
971069AG2-661 GEN
Solar/Wind Harmer
3.136
316132AB2-190 GEN1
Solar/Wind Harmer
0.94
316093AE2-104_GEN
Solar/Wind Harmer
2.962
3143096IRON208
Adder
0.736
3143336POWHATN
Solar/Wind Harmer
3.091
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.562
3146516WINFALL
Solar/Wind Harmer
0.173
944631AF1-128 GEN
Adder
82.709
970919AG2-571 GEN
Solar/Wind Harmer
6.149
971317AH1-138 GEN
Solar/Wind Harmer
1.283
970087AG2-069 GEN
Solar/Wind Harmer
13.655
3130156CHOWAN
Solar/Wind Harmer
0.169
315975AC1-164 GENB
Solar/Wind Harmer
0.052
3142416OLDCHRC
Solar/Wind Harmer
0.436
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.668
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.709
3145663CRESWEL
Solar/Wind Harmer
0.465
971163AH1-040 GEN
Solar/Wind Harmer
13.3
316023GEN1_S
Solar/Wind Harmer
0.366
957481AF2-042 GEN
Solar/Wind Harmer
43.899
315737AD1-076 GEN
Solar/Wind Harmer
2.095
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.454
3145893MURPHYS
Solar/Wind Harmer
0.647
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.732
960081AF2-299 GEN
Solar/Wind Harmer
1.543
3146173TUNIS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.72
3138133OCRAN
Solar/Wind Harmer
0.095
315607AA1-063A GEN
Solar/Wind Harmer
0.32
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
3147043LAWRENC
Adder
1.415
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
962861AG1-135 GEN
Solar/Wind Harmer
4.834
316129AC1-054 GEN
Solar/Wind Harmer
0.562
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.972
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.402
3141726DUNNSVL
Solar/Wind Harmer
0.59
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316131AB2-060 GEN
Solar/Wind Harmer
0.455
315785AD2-033 C
Solar/Wind Harmer
1.179
316034AC1-036 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
8.926
3150351NORNECKC2
Adder
1.45
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.835
971563AH1-280 GEN
Solar/Wind Harmer
1.546
3144293JTRSVLE
Adder
0.346
3144293JTRSVLE
Adder
0.273
3146233WITAKRS
Solar/Wind Harmer
0.572
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.143
3145493TOT1
Solar/Wind Harmer
0.638
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.502
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.816
316337AD2-073 GEN
Solar/Wind Harmer
0.119
972197AH1-683 GEN
Adder
2.861
972219AH1-694 GEN
Adder
2.06
3146776BUCKING
Solar/Wind Harmer
0.055
971377AH1-170 GEN
Solar/Wind Harmer
1.276
3147623JAMES R
Solar/Wind Harmer
0.277
972135AH1-637 GEN
Solar/Wind Harmer
0.996
316447AC1-158 HLD
Solar/Wind Helper
11.843
316044AC1-158 PL1
Solar/Wind Helper
5.382
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.005
NYPJM->LTFIMP_NY
CLTF
2.436
LGEELTFEXP_LGEE->PJM
CLTF
0.991
WECLTFEXP_WEC->PJM
CLTF
0.477
TVALTFEXP_TVA->PJM
CLTF
3.158
CPLELTFEXP_CPLE->PJM
CLTF
9.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.862
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.7
MECLTFEXP_MEC->PJM
CLTF
2.734
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.05 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5186.56
MW Contribution:
6.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
122.663
3142366NRTHEST
50/50
0.837
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150691DARBY 3
50/50
18.374
3150701DARBY 4
50/50
18.331
316045AC1-158 PL2
Solar/Wind Harmer
9.684
316450AC1-158 RIC
Solar/Wind Harmer
0.807
971223AH1-071 GEN
Solar/Wind Harmer
2.825
3143526WINTERP
Solar/Wind Harmer
1.339
316294AC1-161 GEN
Solar/Wind Harmer
4.182
3150681DARBY 2
Adder
17.255
3150671DARBY 1
Adder
17.235
3152251N ANNA1
50/50
19.692
971507AH1-251 GEN
50/50
16.761
970119AG2-088 GEN
50/50
35.314
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.861
3150771HOPHCF1
50/50
0.977
316447AC1-158 HLD
Solar/Wind Harmer
6.655
316044AC1-158 PL1
Solar/Wind Harmer
3.026
3152261N ANNA2
50/50
19.702
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151161SURRY 1
50/50
9.746
3147666LOUISA
Solar/Wind Harmer
0.63
944011AF1-069 GEN
Solar/Wind Harmer
14.524
970133AG2-095 GEN
Solar/Wind Harmer
2.312
315813AE1-149 C
Solar/Wind Harmer
12.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
944581AF1-123 GEN
Solar/Wind Harmer
54.082
944601AF1-125 GEN
Solar/Wind Harmer
53.249
315778AD1-151 GEN
Solar/Wind Harmer
19.212
3151101ELIZAR3
Adder
22.264
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.387
3145336SMITFLD
Solar/Wind Harmer
0.096
3151171GRAVELC
Adder
3.347
970657AG2-426 GEN
Solar/Wind Harmer
5.366
970293AG2-193 GEN
Solar/Wind Harmer
2.551
971531AH1-263 GEN
50/50
60.361
316303AF2-085
50/50
4.708
971285AH1-108 GEN
50/50
1.989
316164AC1-076 GEN
Solar/Wind Harmer
0.439
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.573
971283AH1-107 GEN
Solar/Wind Harmer
3.573
3143316POE
Solar/Wind Harmer
0.961
970533AG2-339 GEN
Solar/Wind Harmer
18.235
315697AD1-025 GEN
Solar/Wind Harmer
0.258
3151081ELIZAR1
Adder
21.982
3151091ELIZAR2
Adder
21.6
971445AH1-216 GEN
Solar/Wind Harmer
16.859
316316AC1-027 C
Solar/Wind Harmer
0.228
3151201GRAVEL4
Adder
17.415
3151221GRAVEL6
Adder
17.395
3151191GRAVEL3
Adder
17.195
3151211GRAVEL5
Adder
17.195
970657AG2-426 GEN
Solar/Wind Harmer
1.756
970673AG2-436 GEN
Solar/Wind Harmer
29.727
957871AF2-081 GEN
Solar/Wind Harmer
11.832
316311AC2-079 GEN
Solar/Wind Harmer
6.807
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.45
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316312AB1-027
Solar/Wind Harmer
0.424
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.74
3137176SLIGO L2192
Solar/Wind Harmer
0.944
3146456SLIGO L269
Solar/Wind Harmer
4.197
316349AD2-085 GEN
Solar/Wind Harmer
0.158
3130086AYDLETT
Solar/Wind Harmer
0.947
315976AC1-164 GENA
Solar/Wind Harmer
2.483
316169AC1-164_GENC
Solar/Wind Harmer
2.145
315835AF2-110_GEN
Solar/Wind Harmer
1.617
972185AH1-677 GEN
Adder
13.194
3144356SAPONY
Solar/Wind Harmer
1.966
316315AB2-025 C
Solar/Wind Harmer
0.188
3146386ELIZ CT
Solar/Wind Harmer
0.235
972189AH1-679 GEN
Adder
3.929
972187AH1-678 GEN
Adder
6.617
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
970933AG2-581 GEN
Solar/Wind Harmer
18.296
316313AB2-026
Solar/Wind Harmer
0.142
315742AE1-103 GEN
Solar/Wind Harmer
3.398
3146376EDENTON
Solar/Wind Harmer
1.005
3146376EDENTON
Solar/Wind Harmer
1.005
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315673AE1-157 GEN
Solar/Wind Harmer
15.458
315614AA2-178 GEN
Solar/Wind Harmer
1.26
3150391LDYSMT3
Adder
29.307
972195AH1-682 GEN
Adder
3.851
316336AC2-165 C
Solar/Wind Harmer
11.083
316365GEN2_N
Solar/Wind Harmer
0.483
316065AD1-022 GEN
Solar/Wind Harmer
9.946
3145893MURPHYS
Solar/Wind Harmer
1.438
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.839
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
316140AB2-099
Solar/Wind Harmer
0.075
313506AB2-031 GEN
Solar/Wind Harmer
0.642
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
962571AG1-106 GEN
Solar/Wind Harmer
2.96
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.649
3145783HORNRTN
Solar/Wind Harmer
2.919
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.124
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.471
316005AA1-067
Solar/Wind Harmer
0.208
315724AD1-057 GEN
Solar/Wind Harmer
3.752
970323AG2-213 GEN
Solar/Wind Harmer
8.181
958211AF2-115 GEN
Solar/Wind Harmer
2.295
3144293JTRSVLE
Adder
0.457
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.263
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.311
316049AB1-081 GEN
Solar/Wind Harmer
1.059
316263AC1-034 GEN
Solar/Wind Harmer
7.074
962561AG1-105 GEN
Solar/Wind Harmer
8.825
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316118AC1-105 GEN
Solar/Wind Harmer
0.457
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.875
972193AH1-681 GEN
Adder
3.393
942751AE2-291 GEN
Solar/Wind Harmer
7.272
316411AF1-147_GEN1
Solar/Wind Helper
0.823
3142946ENON
Solar/Wind Harmer
0.08
3142416OLDCHRC
Solar/Wind Harmer
2.309
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3144216WINCHST
Adder
0.895
316075AC2-137 C
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.742
3150921YORKTN3
Adder
5.961
316246AF1-032 C
Solar/Wind Harmer
0.105
316321Z2-027
Solar/Wind Harmer
0.042
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.78
3146626S HERTFORD
Solar/Wind Harmer
0.23
3145273HOLLAND
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.45
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.024
3146376EDENTON
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
4.01
970917AG2-570 GEN
Solar/Wind Harmer
19.909
3150401LDYSMT4
Adder
29.362
3150371LDYSMT1
Adder
28.372
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3146263WOODLND
Solar/Wind Harmer
0.21
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
316011AB1-132 GEN
Solar/Wind Harmer
3.774
3145963POPLR C
Solar/Wind Harmer
0.207
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Solar/Wind Harmer
0.124
316478AD1-087 GEN
Solar/Wind Harmer
0.713
3145796HORNRTN
Solar/Wind Harmer
0.819
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.073
316212AC1-099_GEN
Solar/Wind Harmer
1.031
3145933PARMELE
Solar/Wind Harmer
0.199
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.726
964241AG1-285 GEN
Solar/Wind Harmer
12.809
970257AG2-171 GEN
Solar/Wind Harmer
6.136
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
17.039
3144293JTRSVLE
Adder
0.457
3147133PAMPLIN
Solar/Wind Harmer
0.6
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.952
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.243
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.372
316223AC1-118
Solar/Wind Harmer
0.131
3141906WESTMOR
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.066
972003AH1-546 GEN
Solar/Wind Harmer
6.047
3151761LOISA E
Adder
22.171
3151721LOISA A
Adder
10.819
970221AG2-151 GEN
Solar/Wind Harmer
8.658
971683AH1-343 GEN
Solar/Wind Harmer
5.878
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Harmer
0.308
972255AH1-712 GEN
Adder
75.929
270494AE1-108_GEN
Solar/Wind Harmer
1.705
316123AC1-075 GEN
Solar/Wind Harmer
0.189
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.165
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316159AE1-175 C
Solar/Wind Harmer
0.203
313526AB2-022
Solar/Wind Harmer
0.125
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
18.521
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971967AH1-528 GEN
Solar/Wind Harmer
37.313
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.137
316258AE1-075 C
Solar/Wind Harmer
0.17
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
970085AG2-068 GEN
Solar/Wind Harmer
11.793
970581AG2-369 GEN
Solar/Wind Harmer
10.142
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.454
3150381LDYSMT2
Adder
28.188
972213AH1-691 GEN
Adder
4.768
972215AH1-692 GEN
Adder
4.768
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.238
315733AD1-074 GEN2
Solar/Wind Harmer
1.238
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.037
3145893MURPHYS
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315652AC1-086 GEN
Solar/Wind Harmer
22.888
3137643SOCKMAN
Solar/Wind Harmer
0.83
316426AA2-053 GEN
Solar/Wind Harmer
0.693
316486AD2-202 GEN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.655
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.204
3146033SCOT NK
Solar/Wind Harmer
0.812
316210AC1-098 GEN
Solar/Wind Harmer
1.848
970831AG2-522 GEN
Solar/Wind Harmer
8.491
316274AC1-208 GEN
Solar/Wind Harmer
1.024
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316327AA2-057 GEN
Solar/Wind Harmer
0.285
957861AF2-080 GEN
Solar/Wind Harmer
8.277
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
11.541
970681AG2-440 GEN
Solar/Wind Harmer
7.66
946301AF1-294 GEN
Solar/Wind Harmer
3.774
961791AG1-021 GEN
Solar/Wind Harmer
1.836
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
971845AH1-439 GEN
Solar/Wind Harmer
8.303
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.109
972205AH1-687 GEN
Adder
7.406
3147346CASHSCORNER
Solar/Wind Harmer
0.369
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
315651AD1-115 GEN
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Harmer
1.095
316192AB2-158 GEN
Solar/Wind Harmer
1.504
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.339
940641AE2-051 GEN
Solar/Wind Harmer
19.868
939411AE1-173 GEN
Solar/Wind Harmer
104.983
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.836
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
44.451
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
944591AF1-124 GEN
Solar/Wind Harmer
54.274
971069AG2-661 GEN
Solar/Wind Harmer
4.269
944631AF1-128 GEN
Adder
114.38
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
2.993
961611AG1-000B GEN
Solar/Wind Harmer
12.562
3145336SMITFLD
Solar/Wind Harmer
0.957
316381AD1-082 GEN
Solar/Wind Harmer
0.243
3151171GRAVELC
Adder
2.545
3142416OLDCHRC
Solar/Wind Harmer
0.619
3142416OLDCHRC
Solar/Wind Harmer
0.237
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.084
319010AE1-072 C
Solar/Wind Harmer
1.182
315975AC1-164 GENB
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
1.761
316093AE2-104_GEN
Solar/Wind Harmer
3.964
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
3143336POWHATN
Solar/Wind Harmer
4.059
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.964
3138133OCRAN
Solar/Wind Harmer
0.133
315816AE2-034 GEN
Solar/Wind Harmer
0.945
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.724
970087AG2-069 GEN
Solar/Wind Harmer
17.689
972197AH1-683 GEN
Adder
4.585
972219AH1-694 GEN
Adder
3.301
316023GEN1_S
Solar/Wind Harmer
0.483
315737AD1-076 GEN
Solar/Wind Harmer
2.787
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.593
3145893MURPHYS
Solar/Wind Harmer
0.859
3145893MURPHYS
Solar/Wind Harmer
0.955
957481AF2-042 GEN
Solar/Wind Harmer
57.098
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.956
960081AF2-299 GEN
Solar/Wind Harmer
2.035
962861AG1-135 GEN
Solar/Wind Harmer
6.77
3145683EARLEYS
Solar/Wind Harmer
0.211
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.965
315607AA1-063A GEN
Solar/Wind Harmer
0.423
315693AD1-088 GEN
Solar/Wind Harmer
10.082
3146263WOODLND
Solar/Wind Harmer
0.21
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.864
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.676
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.039
3146293MARTNCO
Solar/Wind Harmer
0.184
316129AC1-054 GEN
Solar/Wind Harmer
0.739
971065AG2-659 GEN
Solar/Wind Harmer
8.417
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316337AD2-073 GEN
Solar/Wind Harmer
0.168
970937AG2-583 GEN
Solar/Wind Harmer
11.909
316131AB2-060 GEN
Solar/Wind Harmer
0.598
316494AC1-189 GEN
Solar/Wind Harmer
0.649
315785AD2-033 C
Solar/Wind Harmer
1.551
316034AC1-036 C
Solar/Wind Harmer
0.013
970685AG2-442 GEN
Solar/Wind Harmer
14.29
971563AH1-280 GEN
Solar/Wind Harmer
2.04
3144293JTRSVLE
Adder
0.457
3144293JTRSVLE
Adder
0.36
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.754
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.842
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.662
3142053HEARTS
Solar/Wind Harmer
0.328
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.07
316254AC1-120 GEN1
Solar/Wind Harmer
6.037
316170AC1-121 GEN2
Solar/Wind Harmer
2.073
3151751LOISA D
Adder
10.875
972135AH1-637 GEN
Solar/Wind Harmer
1.428
971377AH1-170 GEN
Solar/Wind Harmer
1.732
3147623JAMES R
Solar/Wind Harmer
0.376
972277AH1-723 GEN
Adder
88.48
316415AF1-147_GEN2
Solar/Wind Helper
0.823
LAGNLTFEXP_LAGN->PJM
CLTF
8.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.265
NYPJM->LTFIMP_NY
CLTF
3.442
LGEELTFEXP_LGEE->PJM
CLTF
1.281
WECLTFEXP_WEC->PJM
CLTF
0.611
TVALTFEXP_TVA->PJM
CLTF
4.142
CPLELTFEXP_CPLE->PJM
CLTF
12.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.986
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.014
MECLTFEXP_MEC->PJM
CLTF
3.532
SIGELTFEXP_SIGE->PJM
CLTF
0.107

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5046.02
MW Contribution:
6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
120.732
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.961
3150791HOPHCF3
50/50
0.961
3150691DARBY 3
50/50
18.078
3150701DARBY 4
50/50
18.036
316045AC1-158 PL2
Solar/Wind Harmer
9.608
316450AC1-158 RIC
Solar/Wind Harmer
0.801
971223AH1-071 GEN
Solar/Wind Harmer
2.782
3143526WINTERP
Solar/Wind Harmer
1.318
316294AC1-161 GEN
Solar/Wind Harmer
4.117
3150681DARBY 2
Adder
16.977
3150671DARBY 1
Adder
16.957
3142296MT RD221
Adder
0.752
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.472
3150991CHESPKB
Adder
2.412
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316312AB1-027
Solar/Wind Harmer
0.417
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316388AE2-253 GEN
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
0.929
3146456SLIGO L269
Solar/Wind Harmer
4.132
316349AD2-085 GEN
Solar/Wind Harmer
0.156
3130086AYDLETT
Solar/Wind Harmer
0.933
315976AC1-164 GENA
Solar/Wind Harmer
2.443
316169AC1-164_GENC
Solar/Wind Harmer
2.111
315835AF2-110_GEN
Solar/Wind Harmer
1.592
972185AH1-677 GEN
Adder
12.995
3144356SAPONY
Solar/Wind Harmer
1.936
316315AB2-025 C
Solar/Wind Harmer
0.185
3146386ELIZ CT
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.864
972187AH1-678 GEN
Adder
6.517
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
966871AG1-558 GEN
Solar/Wind Harmer
0.262
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.015
316313AB2-026
Solar/Wind Harmer
0.14
315742AE1-103 GEN
Solar/Wind Harmer
3.345
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
316156AD2-030 GEN
Solar/Wind Harmer
0.163
315673AE1-157 GEN
Solar/Wind Harmer
15.198
315614AA2-178 GEN
Solar/Wind Harmer
1.241
3150391LDYSMT3
Adder
28.81
972195AH1-682 GEN
Adder
3.786
316336AC2-165 C
Solar/Wind Harmer
10.886
316365GEN2_N
Solar/Wind Harmer
0.476
316065AD1-022 GEN
Solar/Wind Harmer
9.791
3145893MURPHYS
Solar/Wind Harmer
1.415
3145893MURPHYS
Solar/Wind Harmer
0.38
970099AG2-077 GEN
Solar/Wind Harmer
22.48
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
316140AB2-099
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.632
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
962571AG1-106 GEN
Solar/Wind Harmer
2.914
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.592
3145783HORNRTN
Solar/Wind Harmer
2.873
3145783HORNRTN
Solar/Wind Harmer
0.898
3145783HORNRTN
Solar/Wind Harmer
0.359
3145796HORNRTN
Solar/Wind Harmer
0.605
3150341NORNECKC1
Adder
2.108
3150341NORNECKC1
Adder
2.091
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
970301AG2-198 GEN
Solar/Wind Harmer
8.323
316005AA1-067
Solar/Wind Harmer
0.205
315724AD1-057 GEN
Solar/Wind Harmer
3.693
970323AG2-213 GEN
Solar/Wind Harmer
8.042
958211AF2-115 GEN
Solar/Wind Harmer
2.255
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.259
316049AB1-081 GEN
Solar/Wind Harmer
1.042
316263AC1-034 GEN
Solar/Wind Harmer
6.963
962561AG1-105 GEN
Solar/Wind Harmer
8.681
964791AG1-342 GEN
Solar/Wind Harmer
3.444
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Harmer
0.058
316118AC1-105 GEN
Solar/Wind Harmer
0.45
3151731LOISA B
Adder
10.304
966001AG1-469 GEN
Solar/Wind Harmer
0.09
972193AH1-681 GEN
Adder
3.326
942751AE2-291 GEN
Solar/Wind Harmer
7.147
316411AF1-147_GEN1
Solar/Wind Helper
0.808
316303AF2-085
50/50
4.637
971285AH1-108 GEN
50/50
1.958
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.518
971283AH1-107 GEN
Solar/Wind Harmer
3.518
3143316POE
Solar/Wind Harmer
0.946
970533AG2-339 GEN
Solar/Wind Harmer
17.962
315697AD1-025 GEN
Solar/Wind Harmer
0.254
3151081ELIZAR1
Adder
21.641
3151091ELIZAR2
Adder
21.266
971445AH1-216 GEN
Solar/Wind Harmer
16.596
316316AC1-027 C
Solar/Wind Harmer
0.225
3151201GRAVEL4
Adder
17.143
3151221GRAVEL6
Adder
17.123
3151191GRAVEL3
Adder
16.926
3151211GRAVEL5
Adder
16.926
970657AG2-426 GEN
Solar/Wind Harmer
1.729
970673AG2-436 GEN
Solar/Wind Harmer
29.28
957871AF2-081 GEN
Solar/Wind Harmer
11.649
316164AC1-076 GEN
Solar/Wind Harmer
0.322
316311AC2-079 GEN
Solar/Wind Harmer
6.702
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316159AE1-175 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.123
3146486SUNBURY
Solar/Wind Harmer
0.23
3146486SUNBURY
Solar/Wind Harmer
0.23
315814AE2-033 C
Solar/Wind Harmer
18.237
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971967AH1-528 GEN
Solar/Wind Harmer
36.746
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
316258AE1-075 C
Solar/Wind Harmer
0.168
970189AG2-124 GEN
Solar/Wind Harmer
6.622
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
970085AG2-068 GEN
Solar/Wind Harmer
11.614
970581AG2-369 GEN
Solar/Wind Harmer
9.988
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.955
3150381LDYSMT2
Adder
27.711
972213AH1-691 GEN
Adder
4.688
972215AH1-692 GEN
Adder
4.688
3130546PLYMOUTH
Solar/Wind Harmer
0.214
315732AD1-074 GEN1
Solar/Wind Harmer
1.219
315733AD1-074 GEN2
Solar/Wind Harmer
1.219
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.912
3145893MURPHYS
Solar/Wind Harmer
0.571
3145893MURPHYS
Solar/Wind Harmer
0.211
316463AE2-346 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
0.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.415
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315652AC1-086 GEN
Solar/Wind Harmer
22.53
3137643SOCKMAN
Solar/Wind Harmer
0.817
316426AA2-053 GEN
Solar/Wind Harmer
0.682
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.645
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.799
316210AC1-098 GEN
Solar/Wind Harmer
1.819
970831AG2-522 GEN
Solar/Wind Harmer
8.356
316274AC1-208 GEN
Solar/Wind Harmer
1.008
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
316327AA2-057 GEN
Solar/Wind Harmer
0.281
957861AF2-080 GEN
Solar/Wind Harmer
8.147
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
11.342
970681AG2-440 GEN
Solar/Wind Harmer
7.528
946301AF1-294 GEN
Solar/Wind Harmer
3.708
961791AG1-021 GEN
Solar/Wind Harmer
1.804
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
971845AH1-439 GEN
Solar/Wind Harmer
8.139
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.246
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.349
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
19.472
3150861SPRUNCD
50/50
1.196
3143096IRON208
50/50
1.061
3143096IRON208
50/50
1.04
3150801HOPHCF4
50/50
1.4
3150761HOPPOLC
50/50
0.601
3151161SURRY 1
50/50
9.594
3147666LOUISA
Solar/Wind Harmer
0.613
944011AF1-069 GEN
Solar/Wind Harmer
14.306
315813AE1-149 C
Solar/Wind Harmer
12.647
970133AG2-095 GEN
Solar/Wind Harmer
2.276
316458AB2-190 GEN2
Solar/Wind Harmer
1.262
944581AF1-123 GEN
Solar/Wind Harmer
53.244
944601AF1-125 GEN
Solar/Wind Harmer
52.424
315778AD1-151 GEN
Solar/Wind Harmer
18.91
3151101ELIZAR3
Adder
21.918
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.287
3151171GRAVELC
Adder
3.294
970657AG2-426 GEN
Solar/Wind Harmer
5.282
970293AG2-193 GEN
Solar/Wind Harmer
2.509
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.272
316017AA1-139 ULT1
Solar/Wind Harmer
0.125
3144216WINCHST
Adder
0.881
316075AC2-137 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.233
971153AH1-033 GEN
Solar/Wind Harmer
2.699
3150921YORKTN3
Adder
5.867
316246AF1-032 C
Solar/Wind Harmer
0.104
316321Z2-027
Solar/Wind Harmer
0.041
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3146516WINFALL
Solar/Wind Harmer
0.228
316473AC1-191 GEN
Solar/Wind Harmer
0.767
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
3.391
3141843SHACKLE
Adder
1.142
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
2.976
3146376EDENTON
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
3.946
970917AG2-570 GEN
Solar/Wind Harmer
19.607
3150401LDYSMT4
Adder
28.865
3150371LDYSMT1
Adder
27.891
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.608
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.21
3146263WOODLND
Solar/Wind Harmer
0.206
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
316011AB1-132 GEN
Solar/Wind Harmer
3.715
3145963POPLR C
Solar/Wind Harmer
0.204
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.806
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3145933PARMELE
Solar/Wind Harmer
0.196
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
6.621
964241AG1-285 GEN
Solar/Wind Harmer
12.595
970257AG2-171 GEN
Solar/Wind Harmer
6.032
971775AH1-396 GEN
Solar/Wind Harmer
0.302
959311AF2-222 GEN
Solar/Wind Harmer
16.747
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
0.589
942461AE2-259 GEN
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.937
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.035
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.366
316223AC1-118
Solar/Wind Harmer
0.129
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
972003AH1-546 GEN
Solar/Wind Harmer
5.918
970221AG2-151 GEN
Solar/Wind Harmer
8.468
3151761LOISA E
Adder
21.008
3151721LOISA A
Adder
10.251
971683AH1-343 GEN
Solar/Wind Harmer
5.78
316222AC1-221 GEN
Solar/Wind Harmer
0.642
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.303
972255AH1-712 GEN
Adder
74.433
316123AC1-075 GEN
Solar/Wind Harmer
0.186
270494AE1-108_GEN
Solar/Wind Harmer
1.668
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.14
3152251N ANNA1
50/50
19.462
970119AG2-088 GEN
50/50
34.777
3150851SPRUNCC
50/50
1.196
3143096IRON208
50/50
1.061
3152331SURRY 2
50/50
9.706
3150771HOPHCF1
50/50
0.961
316447AC1-158 HLD
Solar/Wind Harmer
6.603
316044AC1-158 PL1
Solar/Wind Harmer
3.003
3147666LOUISA
Solar/Wind Harmer
1.066
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.463
3143526WINTERP
Solar/Wind Harmer
1.318
940641AE2-051 GEN
Solar/Wind Harmer
19.57
939411AE1-173 GEN
Solar/Wind Harmer
103.394
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.699
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
43.784
316132AB2-190 GEN1
Solar/Wind Harmer
1.262
944591AF1-124 GEN
Solar/Wind Harmer
53.433
971069AG2-661 GEN
Solar/Wind Harmer
4.202
944631AF1-128 GEN
Adder
112.557
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.042
3150981CHESPKA
Adder
2.946
3145336SMITFLD
Solar/Wind Harmer
0.942
961611AG1-000B GEN
Solar/Wind Harmer
12.365
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3151171GRAVELC
Adder
2.505
3142416OLDCHRC
Solar/Wind Harmer
0.609
3142416OLDCHRC
Solar/Wind Harmer
0.233
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.233
316072AD1-144
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.164
315975AC1-164 GENB
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
1.733
316093AE2-104_GEN
Solar/Wind Harmer
3.902
3142433PROV 92
Solar/Wind Harmer
0.913
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
3143336POWHATN
Solar/Wind Harmer
3.989
971777AH1-397 GEN
Solar/Wind Harmer
0.59
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.843
3138133OCRAN
Solar/Wind Harmer
0.131
315816AE2-034 GEN
Solar/Wind Harmer
0.931
3145663CRESWEL
Solar/Wind Harmer
0.61
971163AH1-040 GEN
Solar/Wind Harmer
17.448
970087AG2-069 GEN
Solar/Wind Harmer
17.42
972197AH1-683 GEN
Adder
4.507
972219AH1-694 GEN
Adder
3.245
316023GEN1_S
Solar/Wind Harmer
0.476
315737AD1-076 GEN
Solar/Wind Harmer
2.744
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.521
3145893MURPHYS
Solar/Wind Harmer
0.846
3145893MURPHYS
Solar/Wind Harmer
0.94
957481AF2-042 GEN
Solar/Wind Harmer
56.201
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.941
960081AF2-299 GEN
Solar/Wind Harmer
2.003
962861AG1-135 GEN
Solar/Wind Harmer
6.663
3145683EARLEYS
Solar/Wind Harmer
0.208
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.856
315607AA1-063A GEN
Solar/Wind Harmer
0.417
315693AD1-088 GEN
Solar/Wind Harmer
9.92
3146263WOODLND
Solar/Wind Harmer
0.206
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.816
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.834
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.665
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.007
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.727
971065AG2-659 GEN
Solar/Wind Harmer
8.282
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
316337AD2-073 GEN
Solar/Wind Harmer
0.165
970937AG2-583 GEN
Solar/Wind Harmer
11.675
316131AB2-060 GEN
Solar/Wind Harmer
0.588
316494AC1-189 GEN
Solar/Wind Harmer
0.638
315785AD2-033 C
Solar/Wind Harmer
1.525
316034AC1-036 C
Solar/Wind Harmer
0.013
970685AG2-442 GEN
Solar/Wind Harmer
14.042
971563AH1-280 GEN
Solar/Wind Harmer
2.004
3144293JTRSVLE
Adder
0.449
3144293JTRSVLE
Adder
0.354
3146233WITAKRS
Solar/Wind Harmer
0.742
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.146
316359AB2-059 GEN
Solar/Wind Harmer
0.651
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.052
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.406
971377AH1-170 GEN
Solar/Wind Harmer
1.694
3147623JAMES R
Solar/Wind Harmer
0.368
3151751LOISA D
Adder
10.304
972277AH1-723 GEN
Adder
86.737
316254AC1-120 GEN1
Solar/Wind Harmer
4.284
316170AC1-121 GEN2
Solar/Wind Harmer
1.471
316415AF1-147_GEN2
Solar/Wind Helper
0.808
LAGNLTFEXP_LAGN->PJM
CLTF
8.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.831
NYPJM->LTFIMP_NY
CLTF
3.379
LGEELTFEXP_LGEE->PJM
CLTF
1.254
TVALTFEXP_TVA->PJM
CLTF
4.067
WECLTFEXP_WEC->PJM
CLTF
0.598
CPLELTFEXP_CPLE->PJM
CLTF
11.863
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.756
MECLTFEXP_MEC->PJM
CLTF
3.461
SIGELTFEXP_SIGE->PJM
CLTF
0.105

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.83 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3730.18
MW Contribution:
4.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
2.933
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.603
3151041BRUNSWICKG3
50/50
2.317
972187AH1-678 GEN
50/50
5.316
3150991CHESPKB
50/50
1.95
3150991CHESPKB
50/50
1.903
316045AC1-158 PL2
Solar/Wind Harmer
9.443
316450AC1-158 RIC
Solar/Wind Harmer
0.787
971223AH1-071 GEN
Solar/Wind Harmer
2.139
3143526WINTERP
Solar/Wind Harmer
0.994
316294AC1-161 GEN
Solar/Wind Harmer
3.06
3145506HICKORY
Solar/Wind Harmer
0.699
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
3144356SAPONY
Solar/Wind Harmer
1.463
316315AB2-025 C
Solar/Wind Harmer
0.14
944641AF1-129 GEN
Adder
83.354
316339AD2-160 GEN
Solar/Wind Harmer
0.279
316388AE2-253 GEN
Solar/Wind Harmer
0.543
3137176SLIGO L2192
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
3.077
3130086AYDLETT
Solar/Wind Harmer
0.694
316349AD2-085 GEN
Solar/Wind Harmer
0.116
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
13.846
315835AF2-110_GEN
Solar/Wind Harmer
1.186
316313AB2-026
Solar/Wind Harmer
0.107
3146386ELIZ CT
Solar/Wind Harmer
0.172
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.555
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.175
3150701DARBY 4
Adder
12.147
3150681DARBY 2
Adder
12.133
3150671DARBY 1
Adder
12.119
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
2.499
3146376EDENTON
Solar/Wind Harmer
0.739
3146376EDENTON
Solar/Wind Harmer
0.739
3142296MT RD221
Adder
0.528
315976AC1-164 GENA
Solar/Wind Harmer
1.741
316169AC1-164_GENC
Solar/Wind Harmer
1.505
316336AC2-165 C
Solar/Wind Harmer
8.379
316312AB1-027
Solar/Wind Harmer
0.294
315614AA2-178 GEN
Solar/Wind Harmer
0.928
970099AG2-077 GEN
Solar/Wind Harmer
17.252
316365GEN2_N
Solar/Wind Harmer
0.359
316156AD2-030 GEN
Solar/Wind Harmer
0.117
316065AD1-022 GEN
Solar/Wind Harmer
7.335
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.062
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
972189AH1-679 GEN
Adder
2.631
316140AB2-099
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.477
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
962571AG1-106 GEN
Solar/Wind Harmer
2.198
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
2.168
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.456
970301AG2-198 GEN
Solar/Wind Harmer
6.393
3145933PARMELE
Solar/Wind Harmer
0.294
3145933PARMELE
Solar/Wind Harmer
0.147
315724AD1-057 GEN
Solar/Wind Harmer
2.788
316005AA1-067
Solar/Wind Harmer
0.154
970323AG2-213 GEN
Solar/Wind Harmer
6.147
958211AF2-115 GEN
Solar/Wind Harmer
1.726
3144293JTRSVLE
Adder
0.343
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
3150341NORNECKC1
Adder
1.495
3150341NORNECKC1
Adder
1.483
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.228
315673AE1-157 GEN
Solar/Wind Harmer
9.777
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.195
3152261N ANNA2
50/50
16.858
3150861SPRUNCD
50/50
0.881
3151031BRUNSWICKG2
50/50
2.317
3151101ELIZAR3
50/50
17.297
3147666LOUISA
Solar/Wind Harmer
0.537
944011AF1-069 GEN
Solar/Wind Harmer
11.007
944581AF1-123 GEN
Solar/Wind Harmer
39.644
944601AF1-125 GEN
Solar/Wind Harmer
39.034
315813AE1-149 C
Solar/Wind Harmer
9.387
3144873MCLAUGH
Solar/Wind Harmer
0.004
3144536CHRHLND
Solar/Wind Harmer
0.026
970657AG2-426 GEN
Solar/Wind Harmer
3.925
3145336SMITFLD
Solar/Wind Harmer
0.07
316017AA1-139 ULT1
Solar/Wind Harmer
0.093
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.01
316246AF1-032 C
Solar/Wind Harmer
0.077
3151171GRAVELC
Adder
2.427
961611AG1-000B GEN
Solar/Wind Harmer
4.624
315778AD1-151 GEN
Solar/Wind Harmer
13.863
316458AB2-190 GEN2
Solar/Wind Harmer
0.924
970133AG2-095 GEN
Solar/Wind Harmer
1.662
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.709
3143336POWHATN
Solar/Wind Harmer
2.609
316321Z2-027
Solar/Wind Harmer
0.031
3144216WINCHST
Adder
0.644
3150921YORKTN3
Adder
4.284
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.059
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
970293AG2-193 GEN
Solar/Wind Harmer
1.79
316075AC2-137 C
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.601
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3156081AA2-088 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.819
316203AE2-005 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.456
3141766HARMONY
Solar/Wind Harmer
2.132
3141873WAN 176
Solar/Wind Harmer
2.833
316473AC1-191 GEN
Solar/Wind Harmer
0.537
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.221
316478AD1-087 GEN
Solar/Wind Harmer
0.538
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316011AB1-132 GEN
Solar/Wind Harmer
2.802
3147043LAWRENC
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.152
316212AC1-099_GEN
Solar/Wind Harmer
0.765
3145933PARMELE
Solar/Wind Harmer
0.147
315722AD1-056 GEN
Solar/Wind Harmer
4.998
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
964241AG1-285 GEN
Solar/Wind Harmer
9.615
970257AG2-171 GEN
Solar/Wind Harmer
4.61
971775AH1-396 GEN
Solar/Wind Harmer
0.23
959311AF2-222 GEN
Solar/Wind Harmer
12.803
3144293JTRSVLE
Adder
0.343
3147133PAMPLIN
Solar/Wind Harmer
0.451
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.447
3151761LOISA E
Adder
18.814
3151721LOISA A
Adder
9.181
3146233WITAKRS
Solar/Wind Harmer
0.707
3146233WITAKRS
Solar/Wind Harmer
0.096
3146073TAR RVR
Solar/Wind Harmer
0.14
3146083TARBORO
Solar/Wind Harmer
0.14
3138543CONSLDL
Solar/Wind Harmer
0.093
961601AG1-000A GEN
Solar/Wind Harmer
9.845
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.084
3150371LDYSMT1
Adder
17.474
971781AH1-399 GEN
Solar/Wind Harmer
0.177
972003AH1-546 GEN
Solar/Wind Harmer
4.563
316223AC1-118
Solar/Wind Harmer
0.09
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.511
971683AH1-343 GEN
Solar/Wind Harmer
4.395
316222AC1-221 GEN
Solar/Wind Harmer
0.488
316303AF2-085
50/50
3.565
971285AH1-108 GEN
50/50
1.442
315244AE2-183_ST
50/50
5.094
963041AG1-153 GEN
50/50
4.691
3151081ELIZAR1
50/50
17.079
3151091ELIZAR2
50/50
16.782
3152251N ANNA1
50/50
16.849
971507AH1-251 GEN
50/50
10.955
970119AG2-088 GEN
50/50
26.735
3150851SPRUNCC
50/50
0.881
315243AE2-183_GT3
50/50
2.933
3151051BRUNSWICKS1
50/50
4.81
3151021BRUNSWICKG1
50/50
2.317
971451AH1-221 GEN
50/50
7.036
3150981CHESPKA
50/50
2.325
316447AC1-158 HLD
Solar/Wind Harmer
6.489
316044AC1-158 PL1
Solar/Wind Harmer
2.951
3147666LOUISA
Solar/Wind Harmer
0.934
316192AB2-158 GEN
Solar/Wind Harmer
1.283
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.975
939411AE1-173 GEN
Solar/Wind Harmer
78.594
941031AE2-094 GEN
Solar/Wind Harmer
33.689
315773AC2-141 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
39.785
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
316381AD1-082 GEN
Solar/Wind Harmer
0.177
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.017
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
319010AE1-072 C
Solar/Wind Harmer
0.867
3151171GRAVELC
Adder
1.846
961611AG1-000B GEN
Solar/Wind Harmer
9.095
316072AD1-144
Solar/Wind Harmer
0.062
971069AG2-661 GEN
Solar/Wind Harmer
3.081
316132AB2-190 GEN1
Solar/Wind Harmer
0.924
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.906
3143336POWHATN
Solar/Wind Harmer
3.07
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.325
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.024
971317AH1-138 GEN
Solar/Wind Harmer
1.26
970087AG2-069 GEN
Solar/Wind Harmer
13.376
3130156CHOWAN
Solar/Wind Harmer
0.166
315975AC1-164 GENB
Solar/Wind Harmer
0.052
3142416OLDCHRC
Solar/Wind Harmer
0.429
3142416OLDCHRC
Solar/Wind Harmer
0.164
3142433PROV 92
Solar/Wind Harmer
0.657
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
315816AE2-034 GEN
Solar/Wind Harmer
0.696
3145663CRESWEL
Solar/Wind Harmer
0.456
971163AH1-040 GEN
Solar/Wind Harmer
13.046
957481AF2-042 GEN
Solar/Wind Harmer
43.129
316023GEN1_S
Solar/Wind Harmer
0.359
971777AH1-397 GEN
Solar/Wind Harmer
0.423
315737AD1-076 GEN
Solar/Wind Harmer
2.054
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.388
315693AD1-088 GEN
Solar/Wind Harmer
7.611
960081AF2-299 GEN
Solar/Wind Harmer
1.515
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.706
3138133OCRAN
Solar/Wind Harmer
0.094
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
3147043LAWRENC
Adder
1.39
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.461
316049AB1-081 GEN
Solar/Wind Harmer
0.787
316263AC1-034 GEN
Solar/Wind Harmer
5.259
962561AG1-105 GEN
Solar/Wind Harmer
6.62
3146776BUCKING
Solar/Wind Harmer
0.55
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.626
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.05
972195AH1-682 GEN
Adder
2.372
316118AC1-105 GEN
Solar/Wind Harmer
0.343
316283AC2-100 C
Solar/Wind Harmer
0.231
941591AE2-156 GEN
50/50
15.607
315779AE2-040
50/50
2.441
316164AC1-076 GEN
Solar/Wind Harmer
0.359
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.652
971283AH1-107 GEN
Solar/Wind Harmer
2.652
970533AG2-339 GEN
Solar/Wind Harmer
13.82
970673AG2-436 GEN
Solar/Wind Harmer
22.523
3143316POE
Solar/Wind Harmer
0.706
971967AH1-528 GEN
Solar/Wind Harmer
28.253
316316AC1-027 C
Solar/Wind Harmer
0.167
970657AG2-426 GEN
Solar/Wind Harmer
1.285
957871AF2-081 GEN
Solar/Wind Harmer
8.673
315814AE2-033 C
Solar/Wind Harmer
13.784
971445AH1-216 GEN
Solar/Wind Harmer
12.266
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316311AC2-079 GEN
Solar/Wind Harmer
4.986
3151201GRAVEL4
Adder
12.628
3151221GRAVEL6
Adder
12.614
3151191GRAVEL3
Adder
12.468
3151211GRAVEL5
Adder
12.468
315697AD1-025 GEN
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.129
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
316159AE1-175 C
Solar/Wind Harmer
0.144
970085AG2-068 GEN
Solar/Wind Harmer
8.917
970581AG2-369 GEN
Solar/Wind Harmer
7.669
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
3138283WHITEMARSH
Solar/Wind Harmer
0.038
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.16
970189AG2-124 GEN
Solar/Wind Harmer
4.752
315732AD1-074 GEN1
Solar/Wind Harmer
0.912
315733AD1-074 GEN2
Solar/Wind Harmer
0.912
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.929
3141913WHIT STONE
Solar/Wind Harmer
0.157
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
3138133OCRAN
Solar/Wind Harmer
0.047
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
16.992
3137643SOCKMAN
Solar/Wind Harmer
0.617
316426AA2-053 GEN
Solar/Wind Harmer
0.515
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
3146033SCOT NK
Solar/Wind Harmer
0.602
970831AG2-522 GEN
Solar/Wind Harmer
6.339
316210AC1-098 GEN
Solar/Wind Harmer
1.371
316274AC1-208 GEN
Solar/Wind Harmer
0.76
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
8.676
970681AG2-440 GEN
Solar/Wind Harmer
5.758
946301AF1-294 GEN
Solar/Wind Harmer
2.839
961791AG1-021 GEN
Solar/Wind Harmer
1.381
316327AA2-057 GEN
Solar/Wind Harmer
0.212
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.139
3145573BETHELC
Solar/Wind Harmer
0.14
3145573BETHELC
Solar/Wind Harmer
0.14
971845AH1-439 GEN
Solar/Wind Harmer
6.264
3150411LDYSMT5
Adder
18.14
3150381LDYSMT2
Adder
17.361
972213AH1-691 GEN
Adder
2.937
972215AH1-692 GEN
Adder
2.937
3147346CASHSCORNER
Solar/Wind Harmer
0.311
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.588
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
962861AG1-135 GEN
Solar/Wind Harmer
4.747
316129AC1-054 GEN
Solar/Wind Harmer
0.552
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.881
971065AG2-659 GEN
Solar/Wind Harmer
6.291
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
8.995
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.579
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.449
315785AD2-033 C
Solar/Wind Harmer
1.165
316034AC1-036 C
Solar/Wind Harmer
0.01
316254AC1-120 GEN1
Solar/Wind Harmer
5.066
316170AC1-121 GEN2
Solar/Wind Harmer
1.74
970685AG2-442 GEN
Solar/Wind Harmer
10.745
971563AH1-280 GEN
Solar/Wind Harmer
1.534
3144293JTRSVLE
Adder
0.343
3144293JTRSVLE
Adder
0.271
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.423
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.228
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.14
3145493TOT1
Solar/Wind Harmer
0.625
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.492
3142053HEARTS
Solar/Wind Harmer
0.244
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.802
316337AD2-073 GEN
Solar/Wind Harmer
0.116
972197AH1-683 GEN
Adder
2.824
972219AH1-694 GEN
Adder
2.033
971377AH1-170 GEN
Solar/Wind Harmer
1.302
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.975
LAGNLTFEXP_LAGN->PJM
CLTF
5.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
NYPJM->LTFIMP_NY
CLTF
2.553
LGEELTFEXP_LGEE->PJM
CLTF
0.894
TVALTFEXP_TVA->PJM
CLTF
3.011
WECLTFEXP_WEC->PJM
CLTF
0.423
CPLELTFEXP_CPLE->PJM
CLTF
8.989
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.684
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.151
MECLTFEXP_MEC->PJM
CLTF
2.494
SIGELTFEXP_SIGE->PJM
CLTF
0.075

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1835.89
MW Contribution:
3.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.538
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.527
3150691DARBY 3
50/50
11.363
3150701DARBY 4
50/50
11.336
3150681DARBY 2
50/50
11.323
315673AE1-157 GEN
Solar/Wind Harmer
52.413
966871AG1-558 GEN
Solar/Wind Harmer
0.187
316312AB1-027
Solar/Wind Harmer
0.287
3150671DARBY 1
Adder
10.658
3142946ENON
Solar/Wind Harmer
0.013
315976AC1-164 GENA
Solar/Wind Harmer
1.324
316169AC1-164_GENC
Solar/Wind Harmer
1.144
944641AF1-129 GEN
Adder
59.793
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.073
316349AD2-085 GEN
Solar/Wind Harmer
0.064
971223AH1-071 GEN
Solar/Wind Harmer
1.025
3150991CHESPKB
Adder
0.984
3150991CHESPKB
Adder
0.96
316294AC1-161 GEN
Solar/Wind Harmer
1.601
315835AF2-110_GEN
Solar/Wind Harmer
0.635
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.147
316388AE2-253 GEN
Solar/Wind Harmer
0.287
3137176SLIGO L2192
Solar/Wind Harmer
0.365
3146456SLIGO L269
Solar/Wind Harmer
1.624
3130086AYDLETT
Solar/Wind Harmer
0.366
3146386ELIZ CT
Solar/Wind Harmer
0.091
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.733
316315AB2-025 C
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
0.384
3146376EDENTON
Solar/Wind Harmer
0.384
315614AA2-178 GEN
Solar/Wind Harmer
0.478
316065AD1-022 GEN
Solar/Wind Harmer
3.737
972193AH1-681 GEN
Adder
1.845
3145893MURPHYS
Solar/Wind Harmer
0.537
3145893MURPHYS
Solar/Wind Harmer
0.144
316365GEN2_N
Solar/Wind Harmer
0.177
316313AB2-026
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
316140AB2-099
Solar/Wind Harmer
0.028
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
962571AG1-106 GEN
Solar/Wind Harmer
1.081
313506AB2-031 GEN
Solar/Wind Harmer
0.232
316336AC2-165 C
Solar/Wind Harmer
3.814
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.318
3145783HORNRTN
Solar/Wind Harmer
1.054
3145783HORNRTN
Solar/Wind Harmer
0.329
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
3150341NORNECKC1
Adder
0.758
3150341NORNECKC1
Adder
0.752
316005AA1-067
Solar/Wind Harmer
0.076
972185AH1-677 GEN
Adder
3.982
972187AH1-678 GEN
Adder
2.003
315724AD1-057 GEN
Solar/Wind Harmer
1.35
970933AG2-581 GEN
Solar/Wind Harmer
5.563
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.18
316049AB1-081 GEN
Solar/Wind Harmer
0.377
316263AC1-034 GEN
Solar/Wind Harmer
2.518
970099AG2-077 GEN
Solar/Wind Harmer
7.064
970323AG2-213 GEN
Solar/Wind Harmer
2.669
970301AG2-198 GEN
Solar/Wind Harmer
2.654
958211AF2-115 GEN
Solar/Wind Harmer
0.741
3144293JTRSVLE
Adder
0.147
3147133PAMPLIN
Solar/Wind Harmer
0.061
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.9
964791AG1-342 GEN
Solar/Wind Harmer
1.149
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
316118AC1-105 GEN
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
0.019
315052AA1-145 CT2
50/50
2.929
966881AG1-559 GEN
Solar/Wind Harmer
0.766
3142416OLDCHRC
Solar/Wind Harmer
0.419
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.564
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
60.987
3150851SPRUNCC
Adder
0.589
315975AC1-164 GENB
Solar/Wind Harmer
0.039
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.621
3142433PROV 92
Solar/Wind Harmer
0.46
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.024
3143526WINTERP
Solar/Wind Harmer
0.585
961611AG1-000B GEN
Solar/Wind Harmer
5.635
3151171GRAVELC
Adder
1.112
971317AH1-138 GEN
Solar/Wind Harmer
0.778
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3138126ROCKLANDING
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.104
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.017
3150981CHESPKA
Adder
1.172
315773AC2-141 GEN
Solar/Wind Harmer
3.383
316093AE2-104_GEN
Solar/Wind Harmer
1.556
944591AF1-124 GEN
Solar/Wind Harmer
20.896
3146456SLIGO L269
Solar/Wind Harmer
0.092
319010AE1-072 C
Solar/Wind Harmer
0.457
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.089
3130156CHOWAN
Solar/Wind Harmer
0.086
315816AE2-034 GEN
Solar/Wind Harmer
0.358
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.721
315737AD1-076 GEN
Solar/Wind Harmer
1.05
962861AG1-135 GEN
Solar/Wind Harmer
2.613
939411AE1-173 GEN
Solar/Wind Harmer
34.759
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.723
972277AH1-723 GEN
Adder
48.112
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.66
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
1.415
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.356
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.222
3146263WOODLND
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.155
3141726DUNNSVL
Solar/Wind Harmer
0.308
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.736
3145823KELFORD
Solar/Wind Harmer
0.076
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
971285AH1-108 GEN
Adder
0.965
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.56
971283AH1-107 GEN
Solar/Wind Harmer
1.56
315697AD1-025 GEN
Solar/Wind Harmer
0.12
316159AE1-175 C
Solar/Wind Harmer
0.095
3143873LANEXA
Solar/Wind Harmer
0.066
3143316POE
Solar/Wind Harmer
0.414
3151201GRAVEL4
Adder
7.611
3151221GRAVEL6
Adder
7.602
3151191GRAVEL3
Adder
7.514
3151211GRAVEL5
Adder
7.514
970189AG2-124 GEN
Solar/Wind Harmer
3.081
970657AG2-426 GEN
Solar/Wind Harmer
0.747
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.101
3141873WAN 176
Solar/Wind Harmer
0.02
316311AC2-079 GEN
Solar/Wind Harmer
2.764
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3151081ELIZAR1
Adder
8.593
3151091ELIZAR2
Adder
8.444
316316AC1-027 C
Solar/Wind Harmer
0.089
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
957871AF2-081 GEN
Solar/Wind Harmer
4.581
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.048
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
315814AE2-033 C
Solar/Wind Harmer
6.903
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.466
315733AD1-074 GEN2
Solar/Wind Harmer
0.466
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.015
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.08
316258AE1-075 C
Solar/Wind Harmer
0.059
316463AE2-346 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315652AC1-086 GEN
Solar/Wind Harmer
8.359
316426AA2-053 GEN
Solar/Wind Harmer
0.252
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.296
316210AC1-098 GEN
Solar/Wind Harmer
0.67
970533AG2-339 GEN
Solar/Wind Harmer
5.472
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
8.941
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
971967AH1-528 GEN
Solar/Wind Harmer
11.289
957861AF2-080 GEN
Solar/Wind Harmer
2.992
316327AA2-057 GEN
Solar/Wind Harmer
0.102
970831AG2-522 GEN
Solar/Wind Harmer
2.932
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
970085AG2-068 GEN
Solar/Wind Harmer
3.609
970581AG2-369 GEN
Solar/Wind Harmer
3.103
316486AD2-202 GEN
Solar/Wind Harmer
0.065
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
3.745
970681AG2-440 GEN
Solar/Wind Harmer
2.486
946301AF1-294 GEN
Solar/Wind Harmer
1.219
961791AG1-021 GEN
Solar/Wind Harmer
0.593
971845AH1-439 GEN
Solar/Wind Harmer
2.619
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.912
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.563
970293AG2-193 GEN
Solar/Wind Harmer
1.526
316075AC2-137 C
Solar/Wind Harmer
0.037
3143096IRON208
Adder
0.564
3143096IRON208
Adder
0.553
3150861SPRUNCD
Adder
0.589
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.163
316458AB2-190 GEN2
Solar/Wind Harmer
0.621
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.108
961611AG1-000B GEN
Solar/Wind Harmer
2.865
315813AE1-149 C
Solar/Wind Harmer
5.666
3151171GRAVELC
Adder
1.463
3141766HARMONY
Solar/Wind Harmer
1.387
3141843SHACKLE
Adder
0.531
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.591
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970657AG2-426 GEN
Solar/Wind Harmer
2.283
3145336SMITFLD
Solar/Wind Harmer
0.04
3141873WAN 176
Solar/Wind Harmer
1.779
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.703
944581AF1-123 GEN
Solar/Wind Harmer
20.822
944601AF1-125 GEN
Solar/Wind Harmer
20.501
316246AF1-032 C
Solar/Wind Harmer
0.041
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.061
316321Z2-027
Solar/Wind Harmer
0.016
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146376EDENTON
Solar/Wind Harmer
0.086
315735AD1-075 GEN1
Solar/Wind Harmer
0.233
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.288
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
3143336POWHATN
Solar/Wind Harmer
1.203
3146173TUNIS
Solar/Wind Harmer
0.079
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.378
316181AB2-040 GEN
Solar/Wind Harmer
0.108
3145796HORNRTN
Solar/Wind Harmer
0.298
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
316212AC1-099_GEN
Solar/Wind Harmer
0.374
944011AF1-069 GEN
Solar/Wind Harmer
4.358
3150351NORNECKC2
Adder
0.734
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.42
970917AG2-570 GEN
Solar/Wind Harmer
6.074
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.34
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.718
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.223
964241AG1-285 GEN
Solar/Wind Harmer
4.21
970257AG2-171 GEN
Solar/Wind Harmer
2.002
971775AH1-396 GEN
Solar/Wind Harmer
0.1
959311AF2-222 GEN
Solar/Wind Harmer
5.55
3144293JTRSVLE
Adder
0.147
3147133PAMPLIN
Solar/Wind Harmer
0.193
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
3145783HORNRTN
Solar/Wind Harmer
0.074
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.657
941031AE2-094 GEN
Solar/Wind Harmer
13.339
3150351NORNECKC2
Adder
0.721
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.234
970919AG2-571 GEN
Solar/Wind Harmer
2.43
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.254
3146233WITAKRS
Solar/Wind Harmer
0.27
970087AG2-069 GEN
Solar/Wind Harmer
5.413
971065AG2-659 GEN
Solar/Wind Harmer
2.873
316359AB2-059 GEN
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.66
315693AD1-088 GEN
Solar/Wind Harmer
3.135
970937AG2-583 GEN
Solar/Wind Harmer
3.936
316131AB2-060 GEN
Solar/Wind Harmer
0.197
315785AD2-033 C
Solar/Wind Harmer
0.507
316034AC1-036 C
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
4.627
971563AH1-280 GEN
Solar/Wind Harmer
0.659
3144293JTRSVLE
Adder
0.147
3144293JTRSVLE
Adder
0.116
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.351
316337AD2-073 GEN
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Harmer
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
3.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.216
TVALTFEXP_TVA->PJM
CLTF
1.641
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
0.625
WECLTFEXP_WEC->PJM
CLTF
0.31
CPLELTFEXP_CPLE->PJM
CLTF
4.12
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.414
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.661
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.669
MECLTFEXP_MEC->PJM
CLTF
1.638
SIGELTFEXP_SIGE->PJM
CLTF
0.051

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:598.97
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
315749AE2-041 GEN
50/50
4.942
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.927
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.874
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.599
315759AF1-018 GEN
50/50
4.942
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.813
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.044
3151211GRAVEL5
Adder
4.044
3141426STAFORD
Solar/Wind Helper
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.134
TVALTFEXP_TVA->PJM
CLTF
0.742
CPLELTFEXP_CPLE->PJM
CLTF
1.988
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
MECLTFEXP_MEC->PJM
CLTF
0.719
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:631.64
MW Contribution:
4.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.704
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
315759AF1-018 GEN
50/50
4.942
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.813
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.044
3151211GRAVEL5
Adder
4.044
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.874
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.599
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
315749AE2-041 GEN
50/50
4.942
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.927
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.269
TVALTFEXP_TVA->PJM
CLTF
0.742
WECLTFEXP_WEC->PJM
CLTF
0.134
CPLELTFEXP_CPLE->PJM
CLTF
1.988
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
MECLTFEXP_MEC->PJM
CLTF
0.719
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2104_SRT-A'
 OPEN BRANCH FROM BUS 313421 TO BUS 314134 CKT 1   /*6SPARTAN     230.0 - 6CRANES      230.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
CONTINGENCY 'DVP_P1-2: LN 2119_SRT-A'
 OPEN BRANCH FROM BUS 314140 TO BUS 314145 CKT 1   /*6GARSVL      230.0 - 6AQUI_HARB_B 230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
314145 to 314140 ckt 1
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314175 to 314132 ckt 1
314290 to 223938 ckt 1
314218 to 314908 ckt 1
314218 to 314908 ckt 2
314163 to 314137 ckt 1
314212 to 314150 ckt 1
314137 to 314134 ckt 1
314140 to 314144 ckt 1
314322 to 314914 ckt 1
314182 to 314183 ckt 1
314183 to 314190 ckt 1
314150 to 315672 ckt 1
313911 to 314290 ckt 1
314190 to 314139 ckt 1
314902 to 314914 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1
315672 to 314197 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1

Winter Peak Analysis

The New Service Request AG2-124 was evaluated as a 0.0 MW (33.34 MW Capacity) injection in the Dominion area.

AG2-124 was evaluated as part of a plant. The plant consists of AG2-124. The total Energy output of the plant was evaluated at its maximum seasonal capability of 149.9 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-124 was evaluated as a 0.0 MW injection

AG2-124 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 149.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Not Required

PJM has reviewed this project submission and determined that a stability study is not required as this is a CIR only increase with no changes to equipment/electrical parameters (no change to MFO).

Reactive Power Analysis

Not Required

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements based on the project Agreements per PJM’s Tariff, Part IX, Subpart B, App. 2, section 4.6.1.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AC1-118Westmoreland 34.5kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-041Harmony Village 230 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF2-120Garner-Northern Neck 115 kVPartially in Service - Under Construction
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-536Garner-Northern Neck 115 kVEngineering & Procurement
AH1-397Shacklesfords 34.5 kVActive

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-124 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn7553Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).Contingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n7553
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7553 / dom-427
Title
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,242,347
Discounted Total Cost ($USD)
$7,242,347
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-124 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-124 may not have cost responsibility for this upgrade, AG2-124 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-124 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA310.0 MVA
LLB320.0 MVA
LLC344.0 MVA
SUMA260.0 MVA
SUMB271.0 MVA
SUMC295.0 MVA
WINA332.0 MVA
WINB340.0 MVA
WINC358.0 MVA

System Reinforcement: b4053.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.10
Title
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Description
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.8
Title
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).
Description
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles). The new line will be constructed primarily of double-circuit 500 kV/230 kV monopole structures. The proposed route follows existing 230 kV line No. 2032 from Elmont-Hanover-Four Rivers and 230 kV line No. 256 from Four Rivers-Kings Dominion-St Johns-Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.9
Title
Construct one new 500 kV line terminal position at the existing Elmont substation.
Description
Construct one new 500 kV line terminal position at the existing Elmont substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AG2-124 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not ContingentTopology Changing

Note 1: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
TBD

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: b4052.2
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.2
Title
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work.
Description
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work. (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.3
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.3
Title
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.4
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.4
Title
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.1
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.1
Title
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line
Description
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line. (2025-W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4052.5
Title
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line
Description
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4052.6
Title
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line
Description
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.7
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.7
Title
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit.
Description
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.8
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.8
Title
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location.
Description
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.9
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.9
Title
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Description
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.10
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.10
Title
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation.
Description
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.11
Title
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer.
Description
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AG2-124 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-124 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-124


AG2-124 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-124 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-124 One Line Diagram

AG2-124 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.