AG2-152 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:56

Banister-Bear Skin 138 kV

79.0 MW Capacity / 131.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Appalachian Power Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $15,980,643 $39,101,083 = 0.41 AND ( $15,980,643 - $39,101,083 ) 131.0 = $-176,492 per MW

General

The Project Developer has proposed a Solar generating facility located in the Appalachian Power Company zone — Pittsylvania County, Virginia. The installed facilities will have a total capability of 131.0 MW with 79.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-152
Project Name:
Banister-Bear Skin 138 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Pittsylvania
Transmission Owner:
Appalachian Power Company
MFO:
131.0
MWE:
131.0
MWC:
79.0
Fuel Type:
Solar
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Chesterfield 6Deactivated Generator52.0Yes
Yorktown 3Deactivated Generator27.0Yes

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-152 will interconnect on the American Electric Power  transmission system  tapping the Banister-Bear Skin 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-152 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-152Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,252,162$0$0
Other Scope$750,157$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$13,909,006$13,909,006$13,909,006
Network Upgrades$2,071,637$2,071,637$2,071,637
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$17,982,962$15,980,643$15,980,643

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-152

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-152
Project ID: AG2-152
20% of cost allocation for Phase II Network Upgrades:(A) $3,196,129
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,910,108
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Relay setting modifications at the neighboring Museville & East Danville 138 kV stations

$89,516$24,006$56,774$15,225$185,521$185,521
(Pending)

MUSEVILLE - EAST DANVILLE 138 kV line will be cut and looped into the new interconnection substation.

$887,636$597,906$228,973$171,601$1,886,116$1,886,116
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the New AG2-152 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of Carrier Protection at the New AG2-152 138 kV Station. Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the AG2-152 New Station 138 kV Station.

$300,193$76,107$115,281$29,227$520,808$520,808
(Pending)

A new breaker and a half substation, New AG2-152 138 kV Station, will be constructed along the MUSEVILLE - EAST DANVILLE 138 kV transmission line to interconnect the project with the APCO transmission system. Appalachian Power Company will construct a new 138 kV breaker and a half station, to be operated as a three (3) circuit breaker ring bus, initially expandable to six (6) circuit breakers. This typical arrangement is planned to be designed to accommodate 3000A of continuous current. Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. Installation of two 2 wavetraps. 1 mile of gravel access road.

$7,153,564$3,650,970$1,630,036$953,628$13,388,198$13,388,198
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

- A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer's generator lead line. - Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The APCO Interconnection Facilities will include but are not limited to the following: - Appalachian Power Company will remove one 1 steel lattice structure in the MUSEVILLE - EAST DANVILLE Right of Way. - Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the New AG2-152 138 kV Station.

$596,062$291,482$243,451$121,167$1,252,162$1,252,162
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Relay setting modifications at the neighboring Museville & East Danville 138 kV stations

$89,516$24,006$56,774$15,225$185,521$185,521
(Pending)

MUSEVILLE - EAST DANVILLE 138 kV line will be cut and looped into the new interconnection substation.

$887,636$597,906$228,973$171,601$1,886,116$1,886,116
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of developer design and construction of new interconnection substation

$244,623$83,373$182,825$62,310$573,131$573,131
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the New AG2-152 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$17,982,962$17,982,962
Developer Build Option$3,394,925$3,394,925

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CANDLER MT-05OPOSSUMCK 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC100.36 %284.0B285.01
8.45
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC122.95 %245.0B301.24
6.91
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC122.95 %245.0B301.22
6.91
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC116.61 %245.0B285.69
5.87
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC116.09 %245.0B284.42
6.92
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC116.08 %245.0B284.39
6.92
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC114.61 %245.0B280.8
6.92
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Base Case
SingleAC105.97 %167.0A176.97
4.06
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC101.53 %245.0B248.75
4.12
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC100.98 %245.0B247.41
14.55
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC100.98 %245.0B247.41
14.55
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC120.3 %192.7A231.82
6.97
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC114.1 %266.96B304.6
7.03
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC112.93 %284.0B320.71
29.56
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC112.88 %284.0B320.58
29.63
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC112.85 %284.0B320.5
10.02
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC112.14 %284.0B318.47
29.56
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC112.12 %284.0B318.43
29.56
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC112.12 %284.0B318.43
29.56
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC112.11 %284.0B318.4
29.56
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC112.01 %192.7A215.84
11.56
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
BreakerAC110.34 %284.0B313.37
12.45
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#5471_SRT-A
SingleAC109.33 %266.96B291.88
8.9
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC105.42 %266.96B281.42
11.66
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC104.29 %266.96B278.42
34.36
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC124.35 %245.0B304.66
6.91
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC124.34 %245.0B304.64
6.91
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC118.02 %245.0B289.16
5.87
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC117.48 %245.0B287.82
6.92
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC117.46 %245.0B287.78
6.92
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC115.99 %245.0B284.19
6.92
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Base Case
SingleAC107.95 %167.0A180.28
4.06
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC102.94 %245.0B252.21
4.12
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC102.35 %245.0B250.75
14.55
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC102.35 %245.0B250.75
14.55
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC101.01 %245.0B247.47
7.89
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
TowerAC100.28 %245.0B245.67
5.9
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC100.17 %245.0B245.42
4.84
GD2AEP
05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC106.4 %284.0B302.18
8.45
GD2AEP
05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC100.27 %284.0B284.76
5.93
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC109.06 %255.0B278.11
10.05
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC108.96 %255.0B277.85
29.59
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC108.87 %255.0B277.62
29.66
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC108.09 %255.0B275.62
29.59
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC108.07 %255.0B275.57
29.59
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC108.07 %255.0B275.57
29.59
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC108.06 %255.0B275.55
29.59
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
BreakerAC106.18 %255.0B270.76
12.48
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC102.81 %255.0B262.17
7.05
GD2AEP
05SMITHMTN-05REDEYE 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC101.03 %255.0B257.64
8.49
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC125.21 %245.0B306.77
6.91
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC125.2 %245.0B306.75
6.91
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
BreakerAC118.9 %245.0B291.31
5.87
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC118.33 %245.0B289.9
6.92
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC118.31 %245.0B289.87
6.92
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC116.84 %245.0B286.26
6.92
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Base Case
SingleAC116.12 %156.98A182.29
4.06
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC110.45 %230.3B254.37
4.12
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC107.48 %230.3B247.53
4.84
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC103.18 %245.0B252.79
14.55
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC103.18 %245.0B252.78
14.55
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC101.88 %245.0B249.6
7.89
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
TowerAC101.11 %245.0B247.72
5.9
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC158.88 %541.0B859.54
11.6
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC133.56 %508.54B679.23
8.18
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC129.43 %508.54B658.18
8.18

Details for 05CANDLER MT-05OPOSSUMCK 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CANDLER MT-05OPOSSUMCK 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.36 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:285.01
MW Contribution:
8.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.526
24684505SMG3
50/50
0.931
270173AC1-122 GEN
Solar/Wind Harmer
5.964
270574AD1-017 GEN2
Solar/Wind Harmer
5.144
270013AE1-250 PV
Solar/Wind Harmer
1.687
24684605SMG4
50/50
1.534
270016AE1-250 BESS
Solar/Wind Harmer
1.687
970223AG2-152 GEN
Solar/Wind Harmer
8.45
24684705SMG5
50/50
0.587
24684305SMG1
50/50
0.552
270197AD1-017 GEN1
Solar/Wind Harmer
1.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.906
CPLELTFEXP_CPLE->PJM
CLTF
0.831
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.727
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.147
TVALTFEXP_TVA->PJM
CLTF
0.469
MECLTFEXP_MEC->PJM
CLTF
0.521
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.211
WECLTFEXP_WEC->PJM
CLTF
0.104

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:301.24
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.49 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:273.14
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.497
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.285
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.907
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
LAGNLTFEXP_LAGN->PJM
CLTF
0.229
CPLELTFEXP_CPLE->PJM
CLTF
0.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.937
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.045
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:301.22
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.48 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:273.12
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.905
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.496
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.284
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CPLELTFEXP_CPLE->PJM
CLTF
0.531
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.61 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:285.69
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
-0.035
3146802CHATHAM
Solar/Wind Harmer
-0.033
941801AE2-185 GEN
Solar/Wind Harmer
16.323
3147123OTTER R
Solar/Wind Harmer
-0.023
270016AE1-250 BESS
Solar/Wind Harmer
1.149
970223AG2-152 GEN
Solar/Wind Harmer
5.868
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
316217AC1-145 GEN
Solar/Wind Harmer
7.06
316197AC1-042 GEN
Solar/Wind Harmer
5.352
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.401
971683AH1-343 GEN
Solar/Wind Harmer
6.175
316003AC1-222 GEN
Solar/Wind Harmer
1.034
270574AD1-017 GEN2
Solar/Wind Harmer
3.383
942671AE2-283 GEN
Solar/Wind Harmer
14.419
942751AE2-291 GEN
Solar/Wind Harmer
16.636
270013AE1-250 PV
Solar/Wind Harmer
1.149
316248AF1-058 C
Solar/Wind Harmer
0.221
316118AC1-105 GEN
Solar/Wind Harmer
0.439
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
1.015
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.09 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:284.42
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:256.27
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.08 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:284.39
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:256.23
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.61 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:280.8
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.71
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:167.0 MVA
Rating Type:A
MVA to Mitigate:176.97
MW Contribution:
4.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.13
942671AE2-283 GEN
Solar/Wind Harmer
9.736
942751AE2-291 GEN
Solar/Wind Harmer
12.788
316118AC1-105 GEN
Solar/Wind Harmer
0.15
24728405LEESVG
50/50
0.296
24728405LEESVG
50/50
0.295
24684405SMG2
50/50
0.981
24684505SMG3
50/50
0.599
3147312GRETNA
Solar/Wind Harmer
0.078
316123AC1-075 GEN
Solar/Wind Harmer
0.268
971683AH1-343 GEN
Solar/Wind Harmer
4.763
3151561HALLBR1
50/50
0.898
24684605SMG4
50/50
0.986
3147312GRETNA
Solar/Wind Harmer
0.313
3146802CHATHAM
Solar/Wind Harmer
0.293
941801AE2-185 GEN
Solar/Wind Harmer
12.518
3147123OTTER R
Solar/Wind Harmer
0.207
970223AG2-152 GEN
Solar/Wind Harmer
4.059
24684705SMG5
50/50
0.377
24684305SMG1
50/50
0.355
270197AD1-017 GEN1
Solar/Wind Harmer
0.568
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.041
LAGNLTFEXP_LAGN->PJM
CLTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
1.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.548
TVALTFEXP_TVA->PJM
CLTF
0.181
MECLTFEXP_MEC->PJM
CLTF
0.042
SIGELTFEXP_SIGE->PJM
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.75
MW Contribution:
4.12
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.127
942671AE2-283 GEN
Solar/Wind Harmer
9.643
942751AE2-291 GEN
Solar/Wind Harmer
12.635
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
3147312GRETNA
Solar/Wind Harmer
0.077
316123AC1-075 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
4.69
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
0.31
3146802CHATHAM
Solar/Wind Harmer
0.29
941801AE2-185 GEN
Solar/Wind Harmer
12.398
3147123OTTER R
Solar/Wind Harmer
0.205
316118AC1-105 GEN
Solar/Wind Harmer
0.146
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
0.569
3147173SINAI
Solar/Wind Harmer
0.065
3147243WELCO
Solar/Wind Harmer
0.041
970223AG2-152 GEN
Solar/Wind Harmer
4.115
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.98 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.41
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.424
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CPLELTFEXP_CPLE->PJM
CLTF
0.776
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.44
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.98 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.41
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.425
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CPLELTFEXP_CPLE->PJM
CLTF
0.775
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.3 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:231.82
MW Contribution:
6.97
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:217.04
MW Contribution:
6.91
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Helper
0.167
24684605SMG4
50/50
1.947
970223AG2-152 GEN
Solar/Wind Harmer
6.974
3147312GRETNA
Solar/Wind Helper
0.666
3146802CHATHAM
Solar/Wind Helper
0.624
3147123OTTER R
Solar/Wind Helper
0.446
24728405LEESVG
50/50
0.545
24728405LEESVG
50/50
0.543
24684405SMG2
50/50
1.937
24684505SMG3
50/50
1.182
316197AC1-042 GEN
Solar/Wind Helper
0.785
3147312GRETNA
Solar/Wind Helper
0.166
316123AC1-075 GEN
Solar/Wind Helper
2.582
316003AC1-222 GEN
Solar/Wind Helper
0.822
24684705SMG5
50/50
0.745
24684305SMG1
50/50
0.701
270197AD1-017 GEN1
Solar/Wind Harmer
1.073
3147173SINAI
Solar/Wind Helper
0.124
3147243WELCO
Solar/Wind Helper
0.077
LAGNLTFEXP_LAGN->PJM
CLTF
0.298
CPLELTFEXP_CPLE->PJM
CLTF
0.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.636
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.424
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.863
TVALTFEXP_TVA->PJM
CLTF
0.158
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.577
MECLTFEXP_MEC->PJM
CLTF
0.211
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.068
LGEELTFEXP_LGEE->PJM
CLTF
0.092
WECLTFEXP_WEC->PJM
CLTF
0.045

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.1 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:304.6
MW Contribution:
7.03
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:94.78 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:253.03
MW Contribution:
5.95
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Helper
0.171
24684705SMG5
50/50
0.743
24684305SMG1
50/50
0.7
270197AD1-017 GEN1
Solar/Wind Harmer
1.074
3147173SINAI
Solar/Wind Helper
0.127
3147243WELCO
Solar/Wind Helper
0.079
24728405LEESVG
50/50
0.543
24728405LEESVG
50/50
0.541
24684405SMG2
50/50
1.933
24684505SMG3
50/50
1.18
316197AC1-042 GEN
Solar/Wind Helper
0.792
3147312GRETNA
Solar/Wind Helper
0.168
316123AC1-075 GEN
Solar/Wind Helper
2.612
316003AC1-222 GEN
Solar/Wind Helper
0.836
24684605SMG4
50/50
1.943
970223AG2-152 GEN
Solar/Wind Harmer
7.029
3147312GRETNA
Solar/Wind Helper
0.671
3146802CHATHAM
Solar/Wind Helper
0.629
3147123OTTER R
Solar/Wind Helper
0.45
LAGNLTFEXP_LAGN->PJM
CLTF
0.687
CPLELTFEXP_CPLE->PJM
CLTF
0.149
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.96
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.848
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.367
TVALTFEXP_TVA->PJM
CLTF
0.365
MECLTFEXP_MEC->PJM
CLTF
0.503
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.131
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.109

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.93 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:320.71
MW Contribution:
29.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.45 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:316.51
MW Contribution:
29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.609
24728405LEESVG
50/50
0.607
24684405SMG2
50/50
2.537
24684505SMG3
50/50
1.548
270574AD1-017 GEN2
Solar/Wind Harmer
11.546
270173AC1-122 GEN
Solar/Wind Harmer
2.315
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.412
316003AC1-222 GEN
Solar/Wind Helper
0.814
24684605SMG4
50/50
2.551
270016AE1-250 BESS
Solar/Wind Harmer
5.117
970223AG2-152 GEN
Solar/Wind Harmer
29.562
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
270013AE1-250 PV
Solar/Wind Harmer
5.117
316248AF1-058 C
Solar/Wind Helper
0.174
316118AC1-105 GEN
Solar/Wind Helper
0.442
24684705SMG5
50/50
0.976
24684305SMG1
50/50
0.918
270197AD1-017 GEN1
Solar/Wind Harmer
3.464
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.667
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.048
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.362

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.88 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:320.58
MW Contribution:
29.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.86 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:317.69
MW Contribution:
29.76
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.557
270016AE1-250 BESS
Solar/Wind Harmer
5.129
970223AG2-152 GEN
Solar/Wind Harmer
29.633
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
270013AE1-250 PV
Solar/Wind Harmer
5.129
316248AF1-058 C
Solar/Wind Helper
0.18
316118AC1-105 GEN
Solar/Wind Helper
0.458
24728405LEESVG
50/50
0.61
24728405LEESVG
50/50
0.608
24684405SMG2
50/50
2.544
24684505SMG3
50/50
1.552
270574AD1-017 GEN2
Solar/Wind Harmer
11.573
270173AC1-122 GEN
Solar/Wind Harmer
2.322
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.425
316003AC1-222 GEN
Solar/Wind Helper
0.83
24684705SMG5
50/50
0.978
24684305SMG1
50/50
0.921
270197AD1-017 GEN1
Solar/Wind Harmer
3.472
3147173SINAI
Solar/Wind Helper
0.133
3147243WELCO
Solar/Wind Helper
0.083
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.802
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.055
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.053
WECLTFEXP_WEC->PJM
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.453

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.85 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:320.5
MW Contribution:
10.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
2.036
316248AF1-058 C
Solar/Wind Helper
0.171
24684605SMG4
50/50
1.943
270016AE1-250 BESS
Solar/Wind Harmer
2.036
970223AG2-152 GEN
Solar/Wind Harmer
10.024
3147312GRETNA
Solar/Wind Helper
0.671
3146802CHATHAM
Solar/Wind Helper
0.629
3147123OTTER R
Solar/Wind Helper
0.45
24728405LEESVG
50/50
0.543
24728405LEESVG
50/50
0.541
24684405SMG2
50/50
1.933
24684505SMG3
50/50
1.18
270574AD1-017 GEN2
Solar/Wind Harmer
6.385
270173AC1-122 GEN
Solar/Wind Harmer
1.607
316197AC1-042 GEN
Solar/Wind Helper
0.792
3147312GRETNA
Solar/Wind Helper
0.168
316123AC1-075 GEN
Solar/Wind Helper
2.612
316003AC1-222 GEN
Solar/Wind Helper
0.836
24684705SMG5
50/50
0.743
24684305SMG1
50/50
0.7
270197AD1-017 GEN1
Solar/Wind Harmer
1.916
3147173SINAI
Solar/Wind Helper
0.127
3147243WELCO
Solar/Wind Helper
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.367
LAGNLTFEXP_LAGN->PJM
CLTF
0.687
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.848
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.96
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.342
TVALTFEXP_TVA->PJM
CLTF
0.365
MECLTFEXP_MEC->PJM
CLTF
0.503
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.131
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.109

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.14 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:318.47
MW Contribution:
29.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:314.26
MW Contribution:
29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.609
24728405LEESVG
50/50
0.607
24684405SMG2
50/50
2.537
24684505SMG3
50/50
1.548
270574AD1-017 GEN2
Solar/Wind Harmer
11.546
270173AC1-122 GEN
Solar/Wind Harmer
2.315
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.412
316003AC1-222 GEN
Solar/Wind Helper
0.814
270013AE1-250 PV
Solar/Wind Harmer
5.117
316248AF1-058 C
Solar/Wind Helper
0.174
316118AC1-105 GEN
Solar/Wind Helper
0.442
24684605SMG4
50/50
2.551
270016AE1-250 BESS
Solar/Wind Harmer
5.117
970223AG2-152 GEN
Solar/Wind Harmer
29.562
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
24684705SMG5
50/50
0.976
24684305SMG1
50/50
0.918
270197AD1-017 GEN1
Solar/Wind Harmer
3.464
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.667
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.362

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:318.43
MW Contribution:
29.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.64 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:314.22
MW Contribution:
29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.609
24728405LEESVG
50/50
0.607
24684405SMG2
50/50
2.537
24684505SMG3
50/50
1.548
270574AD1-017 GEN2
Solar/Wind Harmer
11.546
270173AC1-122 GEN
Solar/Wind Harmer
2.315
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.412
316003AC1-222 GEN
Solar/Wind Helper
0.814
24684705SMG5
50/50
0.976
24684305SMG1
50/50
0.918
270197AD1-017 GEN1
Solar/Wind Harmer
3.464
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.081
24684605SMG4
50/50
2.551
270016AE1-250 BESS
Solar/Wind Harmer
5.117
970223AG2-152 GEN
Solar/Wind Harmer
29.563
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
270013AE1-250 PV
Solar/Wind Harmer
5.117
316248AF1-058 C
Solar/Wind Helper
0.174
316118AC1-105 GEN
Solar/Wind Helper
0.442
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.667
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.048
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.362

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:318.43
MW Contribution:
29.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.64 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:314.21
MW Contribution:
29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.609
24728405LEESVG
50/50
0.607
24684405SMG2
50/50
2.537
24684505SMG3
50/50
1.548
270574AD1-017 GEN2
Solar/Wind Harmer
11.546
270173AC1-122 GEN
Solar/Wind Harmer
2.315
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.412
316003AC1-222 GEN
Solar/Wind Helper
0.814
270013AE1-250 PV
Solar/Wind Harmer
5.117
316248AF1-058 C
Solar/Wind Helper
0.174
316118AC1-105 GEN
Solar/Wind Helper
0.442
24684605SMG4
50/50
2.551
270016AE1-250 BESS
Solar/Wind Harmer
5.117
970223AG2-152 GEN
Solar/Wind Harmer
29.563
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
24684705SMG5
50/50
0.976
24684305SMG1
50/50
0.918
270197AD1-017 GEN1
Solar/Wind Harmer
3.464
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.667
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.362

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.11 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:318.4
MW Contribution:
29.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:314.19
MW Contribution:
29.65
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.551
270016AE1-250 BESS
Solar/Wind Harmer
5.117
970223AG2-152 GEN
Solar/Wind Harmer
29.562
3147312GRETNA
Solar/Wind Helper
0.608
3146802CHATHAM
Solar/Wind Helper
0.57
3147123OTTER R
Solar/Wind Helper
0.408
270013AE1-250 PV
Solar/Wind Harmer
5.117
316248AF1-058 C
Solar/Wind Helper
0.174
316118AC1-105 GEN
Solar/Wind Helper
0.442
24728405LEESVG
50/50
0.609
24728405LEESVG
50/50
0.607
24684405SMG2
50/50
2.537
24684505SMG3
50/50
1.548
270574AD1-017 GEN2
Solar/Wind Harmer
11.546
270173AC1-122 GEN
Solar/Wind Harmer
2.315
316197AC1-042 GEN
Solar/Wind Helper
0.717
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.412
316003AC1-222 GEN
Solar/Wind Helper
0.814
24684705SMG5
50/50
0.976
24684305SMG1
50/50
0.918
270197AD1-017 GEN1
Solar/Wind Harmer
3.464
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.143
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.667
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.048
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.362

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.01 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:215.84
MW Contribution:
11.56
IPD Plant:AG2-152
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.52 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:201.41
MW Contribution:
11.46
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
11.564

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.34 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:313.37
MW Contribution:
12.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:287.87
MW Contribution:
12.29
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
2.528
316248AF1-058 C
Solar/Wind Helper
0.162
24684605SMG4
50/50
2.412
270016AE1-250 BESS
Solar/Wind Harmer
2.528
970223AG2-152 GEN
Solar/Wind Harmer
12.45
3147312GRETNA
Solar/Wind Helper
0.66
3146802CHATHAM
Solar/Wind Helper
0.618
3147123OTTER R
Solar/Wind Helper
0.443
24728405LEESVG
50/50
0.581
24728405LEESVG
50/50
0.579
24684405SMG2
50/50
2.399
24684505SMG3
50/50
1.464
270173AC1-122 GEN
Solar/Wind Harmer
3.573
270574AD1-017 GEN2
Solar/Wind Harmer
7.927
316197AC1-042 GEN
Solar/Wind Helper
0.778
3147312GRETNA
Solar/Wind Helper
0.165
316123AC1-075 GEN
Solar/Wind Helper
2.556
316003AC1-222 GEN
Solar/Wind Helper
0.804
24684705SMG5
50/50
0.923
24684305SMG1
50/50
0.868
270197AD1-017 GEN1
Solar/Wind Harmer
2.378
3147173SINAI
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.075
CPLELTFEXP_CPLE->PJM
CLTF
0.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.373
LAGNLTFEXP_LAGN->PJM
CLTF
0.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.755
TVALTFEXP_TVA->PJM
CLTF
0.212
MECLTFEXP_MEC->PJM
CLTF
0.248
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.097
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.051

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#5471_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5471_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.33 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:291.88
MW Contribution:
8.9
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5471_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:98.39 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:262.65
MW Contribution:
8.76
Bus #Bus NameTypeMW Contribution
316248AF1-058 C
Solar/Wind Helper
0.156
24684605SMG4
50/50
2.453
970223AG2-152 GEN
Solar/Wind Harmer
8.9
3147312GRETNA
Solar/Wind Helper
0.642
3146802CHATHAM
Solar/Wind Helper
0.602
3147123OTTER R
Solar/Wind Helper
0.431
24728405LEESVG
50/50
0.59
24728405LEESVG
50/50
0.588
24684405SMG2
50/50
2.44
24684505SMG3
50/50
1.489
316197AC1-042 GEN
Solar/Wind Helper
0.757
3147312GRETNA
Solar/Wind Helper
0.16
316123AC1-075 GEN
Solar/Wind Helper
2.485
316003AC1-222 GEN
Solar/Wind Helper
0.78
24684705SMG5
50/50
0.938
24684305SMG1
50/50
0.883
270197AD1-017 GEN1
Solar/Wind Harmer
1.357
3147173SINAI
Solar/Wind Helper
0.116
3147243WELCO
Solar/Wind Helper
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
0.335
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.939
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.474
TVALTFEXP_TVA->PJM
CLTF
0.222
MECLTFEXP_MEC->PJM
CLTF
0.256
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.106
WECLTFEXP_WEC->PJM
CLTF
0.052

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.42 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:281.42
MW Contribution:
11.66
IPD Plant:AG2-152
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
11.656

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.29 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:278.42
MW Contribution:
34.36
IPD Plant:AG2-152
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:272.43
MW Contribution:
34.45
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
34.358

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.35 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:304.66
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:276.5
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.497
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.907
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.285
LAGNLTFEXP_LAGN->PJM
CLTF
0.229
CPLELTFEXP_CPLE->PJM
CLTF
0.532
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.937
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.045
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.34 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:304.64
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.85 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:276.48
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.496
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.905
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.284
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CPLELTFEXP_CPLE->PJM
CLTF
0.531
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.02 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:289.16
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
316217AC1-145 GEN
Solar/Wind Harmer
7.06
316197AC1-042 GEN
Solar/Wind Harmer
5.352
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.401
971683AH1-343 GEN
Solar/Wind Harmer
6.175
316003AC1-222 GEN
Solar/Wind Harmer
1.034
270574AD1-017 GEN2
Solar/Wind Harmer
3.383
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
1.015
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
-0.035
3146802CHATHAM
Solar/Wind Harmer
-0.033
941801AE2-185 GEN
Solar/Wind Harmer
16.323
942671AE2-283 GEN
Solar/Wind Harmer
14.419
942751AE2-291 GEN
Solar/Wind Harmer
16.636
270013AE1-250 PV
Solar/Wind Harmer
1.149
316248AF1-058 C
Solar/Wind Harmer
0.221
316118AC1-105 GEN
Solar/Wind Harmer
0.439
3147123OTTER R
Solar/Wind Harmer
-0.023
270016AE1-250 BESS
Solar/Wind Harmer
1.149
970223AG2-152 GEN
Solar/Wind Harmer
5.868
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.48 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:287.82
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:259.59
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.46 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:287.78
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.94 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:259.55
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.99 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:284.19
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.5 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:256.02
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.95 %
Rating:167.0 MVA
Rating Type:A
MVA to Mitigate:180.28
MW Contribution:
4.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.13
942671AE2-283 GEN
Solar/Wind Harmer
9.736
942751AE2-291 GEN
Solar/Wind Harmer
12.788
316118AC1-105 GEN
Solar/Wind Harmer
0.15
3151561HALLBR1
50/50
0.898
24684605SMG4
50/50
0.986
3147312GRETNA
Solar/Wind Harmer
0.313
3146802CHATHAM
Solar/Wind Harmer
0.293
24728405LEESVG
50/50
0.296
24728405LEESVG
50/50
0.295
24684405SMG2
50/50
0.981
24684505SMG3
50/50
0.599
3147312GRETNA
Solar/Wind Harmer
0.078
316123AC1-075 GEN
Solar/Wind Harmer
0.268
971683AH1-343 GEN
Solar/Wind Harmer
4.763
941801AE2-185 GEN
Solar/Wind Harmer
12.518
3147123OTTER R
Solar/Wind Harmer
0.207
970223AG2-152 GEN
Solar/Wind Harmer
4.059
24684705SMG5
50/50
0.377
24684305SMG1
50/50
0.355
270197AD1-017 GEN1
Solar/Wind Harmer
0.568
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.041
LAGNLTFEXP_LAGN->PJM
CLTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
1.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.403
TVALTFEXP_TVA->PJM
CLTF
0.181
MECLTFEXP_MEC->PJM
CLTF
0.042
SIGELTFEXP_SIGE->PJM
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.94 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.21
MW Contribution:
4.12
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
3147312GRETNA
Solar/Wind Harmer
0.077
316123AC1-075 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
4.69
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
0.31
3146802CHATHAM
Solar/Wind Harmer
0.29
941801AE2-185 GEN
Solar/Wind Harmer
12.398
3147123OTTER R
Solar/Wind Harmer
0.205
970223AG2-152 GEN
Solar/Wind Harmer
4.115
3152661PLYWOOD A
50/50
0.127
942671AE2-283 GEN
Solar/Wind Harmer
9.643
942751AE2-291 GEN
Solar/Wind Harmer
12.635
316118AC1-105 GEN
Solar/Wind Harmer
0.146
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
0.569
3147173SINAI
Solar/Wind Harmer
0.065
3147243WELCO
Solar/Wind Harmer
0.041
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.35 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.75
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.424
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CPLELTFEXP_CPLE->PJM
CLTF
0.776
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.44
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.35 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.75
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.425
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.775
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.01 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.47
MW Contribution:
7.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.422
24728405LEESVG
50/50
0.42
24684405SMG2
50/50
1.46
24684505SMG3
50/50
0.891
316217AC1-145 GEN
Solar/Wind Harmer
10.019
316197AC1-042 GEN
Solar/Wind Harmer
7.595
3147312GRETNA
Solar/Wind Harmer
-0.012
270574AD1-017 GEN2
Solar/Wind Harmer
4.884
270173AC1-122 GEN
Solar/Wind Harmer
1.092
942671AE2-283 GEN
Solar/Wind Harmer
20.464
270013AE1-250 PV
Solar/Wind Harmer
1.586
24684705SMG5
50/50
0.561
24684305SMG1
50/50
0.528
270197AD1-017 GEN1
Solar/Wind Harmer
1.465
24684605SMG4
50/50
1.467
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
23.167
270016AE1-250 BESS
Solar/Wind Harmer
1.586
970223AG2-152 GEN
Solar/Wind Harmer
7.894
CPLELTFEXP_CPLE->PJM
CLTF
0.64
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.523
LAGNLTFEXP_LAGN->PJM
CLTF
0.329
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.484
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.537
TVALTFEXP_TVA->PJM
CLTF
0.164
MECLTFEXP_MEC->PJM
CLTF
0.108
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.095
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.015

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.28 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.67
MW Contribution:
5.9
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.297
24728405LEESVG
50/50
0.296
24684405SMG2
50/50
0.988
24684505SMG3
50/50
0.603
316217AC1-145 GEN
Solar/Wind Harmer
7.153
316197AC1-042 GEN
Solar/Wind Harmer
5.422
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.473
971683AH1-343 GEN
Solar/Wind Harmer
6.479
316003AC1-222 GEN
Solar/Wind Harmer
1.104
270574AD1-017 GEN2
Solar/Wind Harmer
3.414
942671AE2-283 GEN
Solar/Wind Harmer
14.61
942751AE2-291 GEN
Solar/Wind Harmer
17.054
316248AF1-058 C
Solar/Wind Harmer
0.243
270013AE1-250 PV
Solar/Wind Harmer
1.156
316118AC1-105 GEN
Solar/Wind Harmer
0.491
970099AG2-077 GEN
Solar/Wind Harmer
4.169
3151561HALLBR1
50/50
0.903
24684605SMG4
50/50
0.993
3147312GRETNA
Solar/Wind Harmer
-0.035
3146802CHATHAM
Solar/Wind Harmer
-0.033
941801AE2-185 GEN
Solar/Wind Harmer
16.54
3147123OTTER R
Solar/Wind Harmer
-0.023
270016AE1-250 BESS
Solar/Wind Harmer
1.156
970223AG2-152 GEN
Solar/Wind Harmer
5.899
957481AF2-042 GEN
Solar/Wind Harmer
10.423
24684705SMG5
50/50
0.38
24684305SMG1
50/50
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
1.024
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.009
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.198
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.618
LAGNLTFEXP_LAGN->PJM
CLTF
0.422
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.3
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.62
TVALTFEXP_TVA->PJM
CLTF
0.202
MECLTFEXP_MEC->PJM
CLTF
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.11

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.17 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.42
MW Contribution:
4.84
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
0.386
3146802CHATHAM
Solar/Wind Harmer
0.362
941801AE2-185 GEN
Solar/Wind Harmer
15.465
3147123OTTER R
Solar/Wind Harmer
0.279
970223AG2-152 GEN
Solar/Wind Harmer
4.842
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
3147312GRETNA
Solar/Wind Harmer
0.097
316123AC1-075 GEN
Solar/Wind Harmer
0.619
971683AH1-343 GEN
Solar/Wind Harmer
17.086
942671AE2-283 GEN
Solar/Wind Harmer
12.028
942751AE2-291 GEN
Solar/Wind Harmer
25.257
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
0.72
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CPLELTFEXP_CPLE->PJM
CLTF
0.531
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.4 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:302.18
MW Contribution:
8.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.526
24684505SMG3
50/50
0.931
270173AC1-122 GEN
Solar/Wind Harmer
5.964
270574AD1-017 GEN2
Solar/Wind Harmer
5.144
270013AE1-250 PV
Solar/Wind Harmer
1.687
24684605SMG4
50/50
1.534
270016AE1-250 BESS
Solar/Wind Harmer
1.687
970223AG2-152 GEN
Solar/Wind Harmer
8.45
24684705SMG5
50/50
0.587
24684305SMG1
50/50
0.552
270197AD1-017 GEN1
Solar/Wind Harmer
1.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.906
CPLELTFEXP_CPLE->PJM
CLTF
0.831
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.727
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.147
TVALTFEXP_TVA->PJM
CLTF
0.469
MECLTFEXP_MEC->PJM
CLTF
0.521
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.211
WECLTFEXP_WEC->PJM
CLTF
0.104

Details for 05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05REDEYE-05CANDLER MT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.27 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:284.76
MW Contribution:
5.93
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
1.534
970223AG2-152 GEN
Solar/Wind Harmer
5.926
24684405SMG2
50/50
1.526
24684505SMG3
50/50
0.931
24728405LEESVG
50/50
0.133
24728405LEESVG
50/50
0.133
24684705SMG5
50/50
0.587
24684305SMG1
50/50
0.552
270197AD1-017 GEN1
Solar/Wind Harmer
0.865
LAGNLTFEXP_LAGN->PJM
CLTF
0.906
CPLELTFEXP_CPLE->PJM
CLTF
0.831
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.727
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.124
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.651
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.147
TVALTFEXP_TVA->PJM
CLTF
0.469
MECLTFEXP_MEC->PJM
CLTF
0.521
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.211
WECLTFEXP_WEC->PJM
CLTF
0.104

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.06 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:278.11
MW Contribution:
10.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
1.946
270016AE1-250 BESS
Solar/Wind Harmer
2.041
970223AG2-152 GEN
Solar/Wind Harmer
10.054
3147312GRETNA
Solar/Wind Helper
0.671
3146802CHATHAM
Solar/Wind Helper
0.629
3147123OTTER R
Solar/Wind Helper
0.45
24684405SMG2
50/50
1.936
24684505SMG3
50/50
1.181
270574AD1-017 GEN2
Solar/Wind Harmer
6.397
270173AC1-122 GEN
Solar/Wind Harmer
1.611
316197AC1-042 GEN
Solar/Wind Helper
0.791
3147312GRETNA
Solar/Wind Helper
0.168
316123AC1-075 GEN
Solar/Wind Helper
2.609
316003AC1-222 GEN
Solar/Wind Helper
0.834
270013AE1-250 PV
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Helper
0.17
24684705SMG5
50/50
0.744
24684305SMG1
50/50
0.701
270197AD1-017 GEN1
Solar/Wind Harmer
1.919
3147173SINAI
Solar/Wind Helper
0.126
3147243WELCO
Solar/Wind Helper
0.079
LAGNLTFEXP_LAGN->PJM
CLTF
0.735
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.431
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.682
TVALTFEXP_TVA->PJM
CLTF
0.389
MECLTFEXP_MEC->PJM
CLTF
0.542
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.116
LGEELTFEXP_LGEE->PJM
CLTF
0.237
WECLTFEXP_WEC->PJM
CLTF
0.118

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.96 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.85
MW Contribution:
29.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.41 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:273.91
MW Contribution:
29.68
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.553
270016AE1-250 BESS
Solar/Wind Harmer
5.122
970223AG2-152 GEN
Solar/Wind Harmer
29.593
270013AE1-250 PV
Solar/Wind Harmer
5.122
316248AF1-058 C
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Helper
0.44
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
24684405SMG2
50/50
2.54
24684505SMG3
50/50
1.55
270574AD1-017 GEN2
Solar/Wind Harmer
11.558
270173AC1-122 GEN
Solar/Wind Harmer
2.319
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.408
316003AC1-222 GEN
Solar/Wind Helper
0.811
24684705SMG5
50/50
0.977
24684305SMG1
50/50
0.919
270197AD1-017 GEN1
Solar/Wind Harmer
3.467
3147173SINAI
Solar/Wind Helper
0.128
3147243WELCO
Solar/Wind Helper
0.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.007
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.087
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.87 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:277.62
MW Contribution:
29.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.86 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.06
MW Contribution:
29.79
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.546
24684505SMG3
50/50
1.554
270013AE1-250 PV
Solar/Wind Harmer
5.134
316248AF1-058 C
Solar/Wind Helper
0.179
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684605SMG4
50/50
2.559
270574AD1-017 GEN2
Solar/Wind Harmer
11.585
270173AC1-122 GEN
Solar/Wind Harmer
2.326
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.421
316003AC1-222 GEN
Solar/Wind Helper
0.827
24684705SMG5
50/50
0.979
24684305SMG1
50/50
0.922
270197AD1-017 GEN1
Solar/Wind Harmer
3.476
3147173SINAI
Solar/Wind Helper
0.133
3147243WELCO
Solar/Wind Helper
0.083
270016AE1-250 BESS
Solar/Wind Harmer
5.134
970223AG2-152 GEN
Solar/Wind Harmer
29.664
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.408
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.094
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.437

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.62
MW Contribution:
29.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.66
MW Contribution:
29.68
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.54
24684505SMG3
50/50
1.55
270574AD1-017 GEN2
Solar/Wind Harmer
11.558
270173AC1-122 GEN
Solar/Wind Harmer
2.319
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.408
316003AC1-222 GEN
Solar/Wind Helper
0.811
270013AE1-250 PV
Solar/Wind Harmer
5.122
316248AF1-058 C
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Helper
0.44
24684605SMG4
50/50
2.553
270016AE1-250 BESS
Solar/Wind Harmer
5.122
970223AG2-152 GEN
Solar/Wind Harmer
29.593
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
24684705SMG5
50/50
0.977
24684305SMG1
50/50
0.919
270197AD1-017 GEN1
Solar/Wind Harmer
3.467
3147173SINAI
Solar/Wind Helper
0.128
3147243WELCO
Solar/Wind Helper
0.08
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.148
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.07 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.57
MW Contribution:
29.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.61
MW Contribution:
29.68
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
5.122
316248AF1-058 C
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Helper
0.44
24684405SMG2
50/50
2.54
24684505SMG3
50/50
1.55
270574AD1-017 GEN2
Solar/Wind Harmer
11.558
270173AC1-122 GEN
Solar/Wind Harmer
2.319
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.408
316003AC1-222 GEN
Solar/Wind Helper
0.811
24684705SMG5
50/50
0.977
24684305SMG1
50/50
0.919
270197AD1-017 GEN1
Solar/Wind Harmer
3.467
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.08
24684605SMG4
50/50
2.553
270016AE1-250 BESS
Solar/Wind Harmer
5.122
970223AG2-152 GEN
Solar/Wind Harmer
29.593
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.147
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.07 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.57
MW Contribution:
29.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.61
MW Contribution:
29.68
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.54
24684505SMG3
50/50
1.55
270574AD1-017 GEN2
Solar/Wind Harmer
11.558
270173AC1-122 GEN
Solar/Wind Harmer
2.319
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.408
316003AC1-222 GEN
Solar/Wind Helper
0.811
270013AE1-250 PV
Solar/Wind Harmer
5.122
316248AF1-058 C
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Helper
0.44
24684605SMG4
50/50
2.553
270016AE1-250 BESS
Solar/Wind Harmer
5.122
970223AG2-152 GEN
Solar/Wind Harmer
29.593
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
24684705SMG5
50/50
0.977
24684305SMG1
50/50
0.919
270197AD1-017 GEN1
Solar/Wind Harmer
3.467
3147173SINAI
Solar/Wind Helper
0.129
3147243WELCO
Solar/Wind Helper
0.08
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.007
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.147
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.06 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:275.55
MW Contribution:
29.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.59
MW Contribution:
29.68
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
5.122
316248AF1-058 C
Solar/Wind Helper
0.173
316118AC1-105 GEN
Solar/Wind Helper
0.44
24684405SMG2
50/50
2.54
24684505SMG3
50/50
1.55
270574AD1-017 GEN2
Solar/Wind Harmer
11.558
270173AC1-122 GEN
Solar/Wind Harmer
2.319
316197AC1-042 GEN
Solar/Wind Helper
0.716
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.408
316003AC1-222 GEN
Solar/Wind Helper
0.811
24684705SMG5
50/50
0.977
24684305SMG1
50/50
0.919
270197AD1-017 GEN1
Solar/Wind Harmer
3.467
3147173SINAI
Solar/Wind Helper
0.128
3147243WELCO
Solar/Wind Helper
0.08
24684605SMG4
50/50
2.553
270016AE1-250 BESS
Solar/Wind Harmer
5.122
970223AG2-152 GEN
Solar/Wind Harmer
29.593
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.007
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.087
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.047
LGEELTFEXP_LGEE->PJM
CLTF
0.061
WECLTFEXP_WEC->PJM
CLTF
0.027
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.18 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:270.76
MW Contribution:
12.48
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:96.22 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:245.36
MW Contribution:
12.32
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
2.533
316248AF1-058 C
Solar/Wind Helper
0.161
24684605SMG4
50/50
2.415
270016AE1-250 BESS
Solar/Wind Harmer
2.533
970223AG2-152 GEN
Solar/Wind Harmer
12.481
3147312GRETNA
Solar/Wind Helper
0.659
3146802CHATHAM
Solar/Wind Helper
0.618
3147123OTTER R
Solar/Wind Helper
0.443
24684405SMG2
50/50
2.402
24684505SMG3
50/50
1.466
270173AC1-122 GEN
Solar/Wind Harmer
3.577
270574AD1-017 GEN2
Solar/Wind Harmer
7.939
316197AC1-042 GEN
Solar/Wind Helper
0.777
3147312GRETNA
Solar/Wind Helper
0.165
316123AC1-075 GEN
Solar/Wind Helper
2.552
316003AC1-222 GEN
Solar/Wind Helper
0.802
24684705SMG5
50/50
0.924
24684305SMG1
50/50
0.869
270197AD1-017 GEN1
Solar/Wind Harmer
2.382
3147173SINAI
Solar/Wind Helper
0.119
3147243WELCO
Solar/Wind Helper
0.074
LAGNLTFEXP_LAGN->PJM
CLTF
0.453
CPLELTFEXP_CPLE->PJM
CLTF
0.32
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.157
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.925
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.843
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.687
TVALTFEXP_TVA->PJM
CLTF
0.236
MECLTFEXP_MEC->PJM
CLTF
0.288
SIGELTFEXP_SIGE->PJM
CLTF
0.009
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.12
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.81 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:262.17
MW Contribution:
7.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.936
24684505SMG3
50/50
1.181
316197AC1-042 GEN
Solar/Wind Helper
0.791
3147312GRETNA
Solar/Wind Helper
0.168
316123AC1-075 GEN
Solar/Wind Helper
2.609
316003AC1-222 GEN
Solar/Wind Helper
0.834
24684605SMG4
50/50
1.946
970223AG2-152 GEN
Solar/Wind Harmer
7.05
3147312GRETNA
Solar/Wind Helper
0.671
3146802CHATHAM
Solar/Wind Helper
0.629
3147123OTTER R
Solar/Wind Helper
0.45
316248AF1-058 C
Solar/Wind Helper
0.17
24684705SMG5
50/50
0.744
24684305SMG1
50/50
0.701
270197AD1-017 GEN1
Solar/Wind Harmer
1.076
3147173SINAI
Solar/Wind Helper
0.126
3147243WELCO
Solar/Wind Helper
0.079
LAGNLTFEXP_LAGN->PJM
CLTF
0.735
CPLELTFEXP_CPLE->PJM
CLTF
0.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.682
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.301
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.431
TVALTFEXP_TVA->PJM
CLTF
0.389
MECLTFEXP_MEC->PJM
CLTF
0.542
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.116
LGEELTFEXP_LGEE->PJM
CLTF
0.237
WECLTFEXP_WEC->PJM
CLTF
0.118

Details for 05SMITHMTN-05REDEYE 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05REDEYE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.03 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:257.64
MW Contribution:
8.49
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.529
24684505SMG3
50/50
0.933
270574AD1-017 GEN2
Solar/Wind Harmer
5.158
270173AC1-122 GEN
Solar/Wind Helper
8.9
270013AE1-250 PV
Solar/Wind Harmer
1.693
24684705SMG5
50/50
0.588
24684305SMG1
50/50
0.553
270197AD1-017 GEN1
Solar/Wind Harmer
1.547
24684605SMG4
50/50
1.537
270016AE1-250 BESS
Solar/Wind Harmer
1.693
970223AG2-152 GEN
Solar/Wind Harmer
8.486
CPLELTFEXP_CPLE->PJM
CLTF
0.861
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.515
LAGNLTFEXP_LAGN->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.207
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.126
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.755
TVALTFEXP_TVA->PJM
CLTF
0.497
MECLTFEXP_MEC->PJM
CLTF
0.567
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.17
LGEELTFEXP_LGEE->PJM
CLTF
0.23
WECLTFEXP_WEC->PJM
CLTF
0.114

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.21 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:306.77
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.69 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:278.55
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.907
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.497
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.285
LAGNLTFEXP_LAGN->PJM
CLTF
0.229
CPLELTFEXP_CPLE->PJM
CLTF
0.532
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.937
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.358
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.045
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.2 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:306.75
MW Contribution:
6.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.68 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:278.53
MW Contribution:
6.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.806
316197AC1-042 GEN
Solar/Wind Harmer
6.676
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.613
316003AC1-222 GEN
Solar/Wind Harmer
5.082
971683AH1-343 GEN
Solar/Wind Harmer
22.496
270574AD1-017 GEN2
Solar/Wind Harmer
4.282
270173AC1-122 GEN
Solar/Wind Harmer
0.959
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.284
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.362
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.388
970223AG2-152 GEN
Solar/Wind Harmer
6.905
942671AE2-283 GEN
Solar/Wind Harmer
17.987
942751AE2-291 GEN
Solar/Wind Harmer
33.256
270013AE1-250 PV
Solar/Wind Harmer
1.388
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CPLELTFEXP_CPLE->PJM
CLTF
0.531
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.934
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.9 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:291.31
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
942671AE2-283 GEN
Solar/Wind Harmer
14.419
942751AE2-291 GEN
Solar/Wind Harmer
16.636
270013AE1-250 PV
Solar/Wind Harmer
1.149
316248AF1-058 C
Solar/Wind Harmer
0.221
316118AC1-105 GEN
Solar/Wind Harmer
0.439
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
-0.035
3146802CHATHAM
Solar/Wind Harmer
-0.033
941801AE2-185 GEN
Solar/Wind Harmer
16.323
3147123OTTER R
Solar/Wind Harmer
-0.023
270016AE1-250 BESS
Solar/Wind Harmer
1.149
970223AG2-152 GEN
Solar/Wind Harmer
5.868
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
316217AC1-145 GEN
Solar/Wind Harmer
7.06
316197AC1-042 GEN
Solar/Wind Harmer
5.352
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.401
971683AH1-343 GEN
Solar/Wind Harmer
6.175
316003AC1-222 GEN
Solar/Wind Harmer
1.034
270574AD1-017 GEN2
Solar/Wind Harmer
3.383
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
1.015
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:289.9
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.78 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:261.61
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.31 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:289.87
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:261.57
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.84 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:286.26
MW Contribution:
6.92
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:258.02
MW Contribution:
6.66
Bus #Bus NameTypeMW Contribution
942671AE2-283 GEN
Solar/Wind Harmer
17.991
942751AE2-291 GEN
Solar/Wind Harmer
33.263
270013AE1-250 PV
Solar/Wind Harmer
1.39
3151561HALLBR1
50/50
1.183
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.041
941801AE2-185 GEN
Solar/Wind Harmer
20.367
3147123OTTER R
Solar/Wind Harmer
-0.031
270016AE1-250 BESS
Solar/Wind Harmer
1.39
970223AG2-152 GEN
Solar/Wind Harmer
6.916
24728405LEESVG
50/50
0.371
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.282
24684505SMG3
50/50
0.782
316217AC1-145 GEN
Solar/Wind Harmer
8.808
316197AC1-042 GEN
Solar/Wind Harmer
6.677
3147312GRETNA
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
5.614
971683AH1-343 GEN
Solar/Wind Harmer
22.502
270574AD1-017 GEN2
Solar/Wind Harmer
4.286
270173AC1-122 GEN
Solar/Wind Harmer
0.96
24684705SMG5
50/50
0.493
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
1.286
CPLELTFEXP_CPLE->PJM
CLTF
0.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.042
LAGNLTFEXP_LAGN->PJM
CLTF
0.244
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.104
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.388
TVALTFEXP_TVA->PJM
CLTF
0.122
MECLTFEXP_MEC->PJM
CLTF
0.058
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.096
LGEELTFEXP_LGEE->PJM
CLTF
0.013
WECLTFEXP_WEC->PJM
CLTF
0.005

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.12 %
Rating:156.98 MVA
Rating Type:A
MVA to Mitigate:182.29
MW Contribution:
4.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.13
24684705SMG5
50/50
0.377
24684305SMG1
50/50
0.355
24728405LEESVG
50/50
0.296
24728405LEESVG
50/50
0.295
24684405SMG2
50/50
0.981
24684505SMG3
50/50
0.599
3147312GRETNA
Solar/Wind Harmer
0.078
3151561HALLBR1
50/50
0.898
24684605SMG4
50/50
0.986
3147312GRETNA
Solar/Wind Harmer
0.313
3146802CHATHAM
Solar/Wind Harmer
0.293
941801AE2-185 GEN
Solar/Wind Harmer
12.518
316123AC1-075 GEN
Solar/Wind Harmer
0.268
971683AH1-343 GEN
Solar/Wind Harmer
4.763
270197AD1-017 GEN1
Solar/Wind Harmer
0.568
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
942671AE2-283 GEN
Solar/Wind Harmer
9.736
942751AE2-291 GEN
Solar/Wind Harmer
12.788
316118AC1-105 GEN
Solar/Wind Harmer
0.15
3147123OTTER R
Solar/Wind Harmer
0.207
970223AG2-152 GEN
Solar/Wind Harmer
4.059
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.041
LAGNLTFEXP_LAGN->PJM
CLTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
1.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.403
TVALTFEXP_TVA->PJM
CLTF
0.181
MECLTFEXP_MEC->PJM
CLTF
0.042
SIGELTFEXP_SIGE->PJM
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:254.37
MW Contribution:
4.12
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.127
942671AE2-283 GEN
Solar/Wind Harmer
9.643
942751AE2-291 GEN
Solar/Wind Harmer
12.635
316118AC1-105 GEN
Solar/Wind Harmer
0.146
3151561HALLBR1
50/50
0.889
24684605SMG4
50/50
0.983
3147312GRETNA
Solar/Wind Harmer
0.31
3146802CHATHAM
Solar/Wind Harmer
0.29
941801AE2-185 GEN
Solar/Wind Harmer
12.398
3147123OTTER R
Solar/Wind Harmer
0.205
970223AG2-152 GEN
Solar/Wind Harmer
4.115
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24684405SMG2
50/50
0.978
24684505SMG3
50/50
0.596
3147312GRETNA
Solar/Wind Harmer
0.077
316123AC1-075 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
4.69
24684705SMG5
50/50
0.376
24684305SMG1
50/50
0.354
270197AD1-017 GEN1
Solar/Wind Harmer
0.569
3147173SINAI
Solar/Wind Harmer
0.065
3147243WELCO
Solar/Wind Harmer
0.041
CPLELTFEXP_CPLE->PJM
CLTF
1.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.96
LAGNLTFEXP_LAGN->PJM
CLTF
0.778
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.584
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.077
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.33
TVALTFEXP_TVA->PJM
CLTF
0.393
MECLTFEXP_MEC->PJM
CLTF
0.341
SIGELTFEXP_SIGE->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.121
WECLTFEXP_WEC->PJM
CLTF
0.06

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.48 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:247.53
MW Contribution:
4.84
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:95.63 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:220.24
MW Contribution:
4.66
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.182
24684605SMG4
50/50
1.288
3147312GRETNA
Solar/Wind Harmer
0.386
3146802CHATHAM
Solar/Wind Harmer
0.362
942671AE2-283 GEN
Solar/Wind Harmer
12.028
942751AE2-291 GEN
Solar/Wind Harmer
25.257
941801AE2-185 GEN
Solar/Wind Harmer
15.465
3147123OTTER R
Solar/Wind Harmer
0.279
970223AG2-152 GEN
Solar/Wind Harmer
4.842
24728405LEESVG
50/50
0.37
24728405LEESVG
50/50
0.369
24684405SMG2
50/50
1.281
24684505SMG3
50/50
0.782
3147312GRETNA
Solar/Wind Harmer
0.097
316123AC1-075 GEN
Solar/Wind Harmer
0.619
971683AH1-343 GEN
Solar/Wind Harmer
17.086
24684705SMG5
50/50
0.492
24684305SMG1
50/50
0.464
270197AD1-017 GEN1
Solar/Wind Harmer
0.72
LAGNLTFEXP_LAGN->PJM
CLTF
0.228
CPLELTFEXP_CPLE->PJM
CLTF
0.531
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.357
TVALTFEXP_TVA->PJM
CLTF
0.114
MECLTFEXP_MEC->PJM
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.18 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.79
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.424
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
CPLELTFEXP_CPLE->PJM
CLTF
0.776
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.44
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.18 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.78
MW Contribution:
14.55
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.325
24728405LEESVG
50/50
0.323
24684405SMG2
50/50
1.249
24684505SMG3
50/50
0.762
316217AC1-145 GEN
Solar/Wind Harmer
7.425
316197AC1-042 GEN
Solar/Wind Harmer
5.628
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.51
270574AD1-017 GEN2
Solar/Wind Harmer
5.682
971683AH1-343 GEN
Solar/Wind Harmer
6.395
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.85
942671AE2-283 GEN
Solar/Wind Harmer
15.164
942751AE2-291 GEN
Solar/Wind Harmer
17.435
270013AE1-250 PV
Solar/Wind Harmer
2.518
316248AF1-058 C
Solar/Wind Harmer
0.223
316118AC1-105 GEN
Solar/Wind Harmer
0.443
24684705SMG5
50/50
0.48
24684305SMG1
50/50
0.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.705
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
3151561HALLBR1
50/50
0.936
24684605SMG4
50/50
1.255
3147312GRETNA
Solar/Wind Harmer
-0.037
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
17.167
3147123OTTER R
Solar/Wind Harmer
-0.024
270016AE1-250 BESS
Solar/Wind Harmer
2.518
970223AG2-152 GEN
Solar/Wind Harmer
14.548
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.103
LAGNLTFEXP_LAGN->PJM
CLTF
0.199
CPLELTFEXP_CPLE->PJM
CLTF
0.775
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.439
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.513
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
0.101

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:249.6
MW Contribution:
7.89
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.422
24728405LEESVG
50/50
0.42
24684405SMG2
50/50
1.46
24684505SMG3
50/50
0.891
316217AC1-145 GEN
Solar/Wind Harmer
10.019
316197AC1-042 GEN
Solar/Wind Harmer
7.595
3147312GRETNA
Solar/Wind Harmer
-0.012
270574AD1-017 GEN2
Solar/Wind Harmer
4.884
270173AC1-122 GEN
Solar/Wind Harmer
1.092
942671AE2-283 GEN
Solar/Wind Harmer
20.464
270013AE1-250 PV
Solar/Wind Harmer
1.586
24684605SMG4
50/50
1.467
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
23.167
270016AE1-250 BESS
Solar/Wind Harmer
1.586
970223AG2-152 GEN
Solar/Wind Harmer
7.894
24684705SMG5
50/50
0.561
24684305SMG1
50/50
0.528
270197AD1-017 GEN1
Solar/Wind Harmer
1.465
LAGNLTFEXP_LAGN->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.64
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.484
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.523
TVALTFEXP_TVA->PJM
CLTF
0.164
MECLTFEXP_MEC->PJM
CLTF
0.108
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.095
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.015

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.11 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.72
MW Contribution:
5.9
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.297
24728405LEESVG
50/50
0.296
24684405SMG2
50/50
0.988
24684505SMG3
50/50
0.603
316217AC1-145 GEN
Solar/Wind Harmer
7.153
316197AC1-042 GEN
Solar/Wind Harmer
5.422
3147312GRETNA
Solar/Wind Harmer
-0.009
316123AC1-075 GEN
Solar/Wind Harmer
2.473
971683AH1-343 GEN
Solar/Wind Harmer
6.479
316003AC1-222 GEN
Solar/Wind Harmer
1.104
270574AD1-017 GEN2
Solar/Wind Harmer
3.414
942671AE2-283 GEN
Solar/Wind Harmer
14.61
942751AE2-291 GEN
Solar/Wind Harmer
17.054
316248AF1-058 C
Solar/Wind Harmer
0.243
270013AE1-250 PV
Solar/Wind Harmer
1.156
316118AC1-105 GEN
Solar/Wind Harmer
0.491
970099AG2-077 GEN
Solar/Wind Harmer
4.169
3151561HALLBR1
50/50
0.903
24684605SMG4
50/50
0.993
3147312GRETNA
Solar/Wind Harmer
-0.035
3146802CHATHAM
Solar/Wind Harmer
-0.033
941801AE2-185 GEN
Solar/Wind Harmer
16.54
3147123OTTER R
Solar/Wind Harmer
-0.023
270016AE1-250 BESS
Solar/Wind Harmer
1.156
970223AG2-152 GEN
Solar/Wind Harmer
5.899
957481AF2-042 GEN
Solar/Wind Harmer
10.423
24684705SMG5
50/50
0.38
24684305SMG1
50/50
0.358
270197AD1-017 GEN1
Solar/Wind Harmer
1.024
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.009
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
0.422
CPLELTFEXP_CPLE->PJM
CLTF
1.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.3
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.62
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.618
TVALTFEXP_TVA->PJM
CLTF
0.202
MECLTFEXP_MEC->PJM
CLTF
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.11

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.88 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:859.54
MW Contribution:
11.6
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:198.91 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1076.12
MW Contribution:
12.54
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
14.704
970087AG2-069 GEN
Solar/Wind Harmer
17.735
970919AG2-571 GEN
Solar/Wind Harmer
5.986
970223AG2-152 GEN
Solar/Wind Harmer
11.598
270018AE2-047 C O1
Solar/Wind Harmer
0.982
270016AE1-250 BESS
Solar/Wind Harmer
1.778
270030AE2-140 GEN
Solar/Wind Harmer
13.925
316359AB2-059 GEN
Solar/Wind Harmer
1.142
3142053HEARTS
Solar/Wind Harmer
0.1
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0.377
3146233WITAKRS
Solar/Wind Harmer
-0.027
316494AC1-189 GEN
Solar/Wind Harmer
0.715
274729ELWOOD EC;1P
Adder
3.258
274730ELWOOD EC;6P
Adder
3.258
274734ELWOOD EC;8P
Adder
3.258
274736ELWOOD EC;9P
Adder
3.258
316131AB2-060 GEN
Solar/Wind Helper
2.179
316034AC1-036 C
Solar/Wind Helper
0.371
315785AD2-033 C
Solar/Wind Helper
3.937
3146926FARMVIL
Solar/Wind Helper
0.151
3146776BUCKING
Solar/Wind Helper
0.079
3147123OTTER R
Solar/Wind Helper
0.101
316129AC1-054 GEN
Solar/Wind Helper
0.805
315773AC2-141 GEN
Solar/Wind Helper
2.494
3147312GRETNA
Solar/Wind Helper
0.091
3146802CHATHAM
Solar/Wind Helper
0.085
970917AG2-570 GEN
Solar/Wind Harmer
47.291
943811AF1-049 GEN
Solar/Wind Harmer
2.747
270336AE1-100 GEN
Solar/Wind Harmer
1.062
961601AG1-000A GEN
Solar/Wind Harmer
3.454
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
270574AD1-017 GEN2
Solar/Wind Harmer
2.646
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.816
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
274732ELWOOD EC;7P
Adder
3.258
316283AC2-100 C
Solar/Wind Helper
8.329
316222AC1-221 GEN
Solar/Wind Helper
8.844
316003AC1-222 GEN
Solar/Wind Helper
2.9
316478AD1-087 GEN
Solar/Wind Helper
2.406
316123AC1-075 GEN
Solar/Wind Helper
2.791
3147133PAMPLIN
Solar/Wind Helper
1.004
942461AE2-259 GEN
Solar/Wind Helper
1.921
3146926FARMVIL
Solar/Wind Helper
0.151
3146776BUCKING
Solar/Wind Helper
0.071
3147043LAWRENC
Solar/Wind Helper
0.102
316197AC1-042 GEN
Solar/Wind Helper
0.107
3147312GRETNA
Solar/Wind Helper
0.023
270013AE1-250 PV
Solar/Wind Harmer
1.778
961601AG1-000A GEN
Solar/Wind Harmer
3.411
316049AB1-081 GEN
Solar/Wind Harmer
0.913
316263AC1-034 GEN
Solar/Wind Harmer
3.979
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Helper
0.977
315687AD1-152 GEN
Solar/Wind Helper
3.728
316118AC1-105 GEN
Solar/Wind Helper
2.529
3146843MT LREL
Solar/Wind Helper
0.573
3146843MT LREL
Solar/Wind Helper
0.573
316237AB2-079_GEN
Solar/Wind Helper
0.489
3147133PAMPLIN
Solar/Wind Helper
0.32
3147133PAMPLIN
Solar/Wind Helper
0.256
3146776BUCKING
Solar/Wind Helper
0.794
3146776BUCKING
Solar/Wind Helper
0.064
316294AC1-161 GEN
Solar/Wind Helper
2.119
270455AD2-022 GEN
Solar/Wind Harmer
4.132
270457AD2-023 GEN
Solar/Wind Harmer
2.095
970085AG2-068 GEN
Solar/Wind Harmer
11.823
970581AG2-369 GEN
Solar/Wind Harmer
10.168
270069AE2-166 C O1
Solar/Wind Harmer
5.276
270197AD1-017 GEN1
Solar/Wind Harmer
0.794
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
2.909
274728ELWOOD EC;5P
Adder
3.258
274731ELWOOD EC;2P
Adder
3.258
274733ELWOOD EC;3P
Adder
3.258
274735ELWOOD EC;4P
Adder
3.258
3147173SINAI
Solar/Wind Helper
0.725
3147243WELCO
Solar/Wind Helper
0.453
316486AD2-202 GEN
Solar/Wind Helper
0.705
316238AB2-078_GEN
Solar/Wind Helper
0.489
316239AB2-077_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.266
316322AB2-045
Solar/Wind Helper
0.222
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.754
CPLELTFEXP_CPLE->PJM
CLTF
13.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.858
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.874
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.28
TVALTFEXP_TVA->PJM
CLTF
4.34
MECLTFEXP_MEC->PJM
CLTF
4.325
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
1.535
WECLTFEXP_WEC->PJM
CLTF
0.818

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.56 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:679.23
MW Contribution:
8.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.55 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:862.23
MW Contribution:
8.86
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
14.769
970417AG2-272 GEN
50/50
1.814
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970919AG2-571 GEN
Solar/Wind Harmer
6.012
970223AG2-152 GEN
Solar/Wind Harmer
8.184
270030AE2-140 GEN
Solar/Wind Harmer
9.794
316359AB2-059 GEN
Solar/Wind Harmer
0.271
3142053HEARTS
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.302
3146233WITAKRS
Solar/Wind Harmer
0.244
316494AC1-189 GEN
Solar/Wind Harmer
0.202
274729ELWOOD EC;1P
Adder
3.35
274730ELWOOD EC;6P
Adder
3.35
274734ELWOOD EC;8P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
961601AG1-000A GEN
Solar/Wind Harmer
1.386
316049AB1-081 GEN
Solar/Wind Harmer
0.434
316263AC1-034 GEN
Solar/Wind Harmer
2.899
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Helper
0.975
970917AG2-570 GEN
Solar/Wind Harmer
15.031
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
5.544
971623AH1-311 GEN
Solar/Wind Harmer
0.153
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3138543CONSLDL
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.042
274732ELWOOD EC;7P
Adder
3.35
316283AC2-100 C
Solar/Wind Helper
8.321
316222AC1-221 GEN
Solar/Wind Helper
8.836
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
316123AC1-075 GEN
Solar/Wind Helper
2.782
3147133PAMPLIN
Solar/Wind Helper
0.999
942461AE2-259 GEN
Solar/Wind Helper
1.911
3146926FARMVIL
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.071
3147043LAWRENC
Solar/Wind Helper
0.101
316197AC1-042 GEN
Solar/Wind Helper
0.106
3147312GRETNA
Solar/Wind Helper
0.022
316131AB2-060 GEN
Solar/Wind Helper
2.17
316034AC1-036 C
Solar/Wind Helper
0.37
315785AD2-033 C
Solar/Wind Helper
3.92
3146926FARMVIL
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.079
3147123OTTER R
Solar/Wind Helper
0.1
316129AC1-054 GEN
Solar/Wind Helper
0.798
315773AC2-141 GEN
Solar/Wind Helper
2.463
3147312GRETNA
Solar/Wind Helper
0.09
3146802CHATHAM
Solar/Wind Helper
0.084
315687AD1-152 GEN
Solar/Wind Helper
3.72
316118AC1-105 GEN
Solar/Wind Helper
2.523
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
316237AB2-079_GEN
Solar/Wind Helper
0.487
3147133PAMPLIN
Solar/Wind Helper
0.318
3147133PAMPLIN
Solar/Wind Helper
0.255
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
316294AC1-161 GEN
Solar/Wind Helper
2.092
970085AG2-068 GEN
Solar/Wind Harmer
9.019
970581AG2-369 GEN
Solar/Wind Harmer
7.756
270069AE2-166 C O1
Solar/Wind Harmer
3.716
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
957861AF2-080 GEN
Solar/Wind Harmer
2.583
274728ELWOOD EC;5P
Adder
3.35
274731ELWOOD EC;2P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
274735ELWOOD EC;4P
Adder
3.35
3147173SINAI
Solar/Wind Helper
0.724
3147243WELCO
Solar/Wind Helper
0.452
316486AD2-202 GEN
Solar/Wind Helper
0.703
316238AB2-078_GEN
Solar/Wind Helper
0.487
316239AB2-077_GEN
Solar/Wind Helper
0.487
3144303KENBRDG
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.22
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CPLELTFEXP_CPLE->PJM
CLTF
13.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
TVALTFEXP_TVA->PJM
CLTF
4.397
MECLTFEXP_MEC->PJM
CLTF
4.419
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:658.18
MW Contribution:
8.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:165.33 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:840.79
MW Contribution:
8.86
Bus #Bus NameTypeMW Contribution
961601AG1-000A GEN
Solar/Wind Harmer
1.386
316049AB1-081 GEN
Solar/Wind Harmer
0.434
316263AC1-034 GEN
Solar/Wind Harmer
2.899
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Helper
0.975
315687AD1-152 GEN
Solar/Wind Helper
3.72
316118AC1-105 GEN
Solar/Wind Helper
2.523
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
316237AB2-079_GEN
Solar/Wind Helper
0.487
3147133PAMPLIN
Solar/Wind Helper
0.318
3147133PAMPLIN
Solar/Wind Helper
0.255
971629AH1-314 GEN
50/50
14.769
970417AG2-272 GEN
50/50
1.814
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970223AG2-152 GEN
Solar/Wind Harmer
8.184
270030AE2-140 GEN
Solar/Wind Harmer
9.794
316359AB2-059 GEN
Solar/Wind Harmer
0.271
3142053HEARTS
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.302
3146233WITAKRS
Solar/Wind Harmer
0.244
316494AC1-189 GEN
Solar/Wind Harmer
0.202
274729ELWOOD EC;1P
Adder
3.35
274730ELWOOD EC;6P
Adder
3.35
274734ELWOOD EC;8P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
316131AB2-060 GEN
Solar/Wind Helper
2.17
316034AC1-036 C
Solar/Wind Helper
0.37
315785AD2-033 C
Solar/Wind Helper
3.92
3146926FARMVIL
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.079
3147123OTTER R
Solar/Wind Helper
0.1
316129AC1-054 GEN
Solar/Wind Helper
0.798
315773AC2-141 GEN
Solar/Wind Helper
2.463
3147312GRETNA
Solar/Wind Helper
0.09
3146802CHATHAM
Solar/Wind Helper
0.084
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
316294AC1-161 GEN
Solar/Wind Helper
2.092
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
5.544
971623AH1-311 GEN
Solar/Wind Harmer
0.153
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3138543CONSLDL
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.042
274732ELWOOD EC;7P
Adder
3.35
316283AC2-100 C
Solar/Wind Helper
8.321
316222AC1-221 GEN
Solar/Wind Helper
8.836
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
316123AC1-075 GEN
Solar/Wind Helper
2.782
3147133PAMPLIN
Solar/Wind Helper
0.999
942461AE2-259 GEN
Solar/Wind Helper
1.911
3146926FARMVIL
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.071
3147043LAWRENC
Solar/Wind Helper
0.101
316197AC1-042 GEN
Solar/Wind Helper
0.106
3147312GRETNA
Solar/Wind Helper
0.022
970085AG2-068 GEN
Solar/Wind Harmer
9.019
970581AG2-369 GEN
Solar/Wind Harmer
7.756
270069AE2-166 C O1
Solar/Wind Harmer
3.716
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
957861AF2-080 GEN
Solar/Wind Harmer
2.583
274728ELWOOD EC;5P
Adder
3.35
274731ELWOOD EC;2P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
274735ELWOOD EC;4P
Adder
3.35
3147173SINAI
Solar/Wind Helper
0.724
3147243WELCO
Solar/Wind Helper
0.452
316486AD2-202 GEN
Solar/Wind Helper
0.703
316238AB2-078_GEN
Solar/Wind Helper
0.487
316239AB2-077_GEN
Solar/Wind Helper
0.487
3144303KENBRDG
Solar/Wind Helper
0.265
316322AB2-045
Solar/Wind Helper
0.22
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CPLELTFEXP_CPLE->PJM
CLTF
13.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
TVALTFEXP_TVA->PJM
CLTF
4.397
MECLTFEXP_MEC->PJM
CLTF
4.419
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84
CONTINGENCY 'AEP_P4_#3174_05CLOVRD 765_AA2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290614 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJO 765.0
 OPEN BRANCH FROM BUS 242515 TO BUS 290614 CKT 1    /*05JOSHUA     765.0 - 05CLOVRD_RJO 765.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-2: 1016T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 101672_SRT-A'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 104772_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'AEP_P1-2_#3174_6_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290614 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJO 765.0
 OPEN BRANCH FROM BUS 242515 TO BUS 290614 CKT 1    /*05JOSHUA     765.0 - 05CLOVRD_RJO 765.0
END
CONTINGENCY 'AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10778___SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242770 TO BUS 243988 CKT 1    /*05RIGIS      138.0 - 05RIGIS       69.0
 OPEN BRANCH FROM BUS 243974 TO BUS 243988 CKT 1    /*05GOODYEAR1   69.0 - 05RIGIS       69.0
END
CONTINGENCY 'AEP_P4_#10164_05EDAN 2 138_M_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P4_#10162_05EDAN 1 138_P_SRT-A'
 OPEN BRANCH FROM BUS 242530 TO BUS 242631 CKT 5    /*05EDANV1     230.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1    /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242620 TO BUS 242631 CKT 1    /*05DANVL2     138.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 243962 CKT 1    /*05EDAN 1     138.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 242631 TO BUS 246972 CKT 1    /*05EDAN 1     138.0 - 05ROCKSP     138.0
 OPEN BRANCH FROM BUS 243960 TO BUS 243962 CKT 1    /*05E.DANVIL    69.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 243961 TO BUS 243962 CKT 1    /*05EDANVILL    12.0 - 05EDANV1EQ     1.0
 REMOVE SWSHUNT FROM BUS 242631                     /*05EDAN 1     138.0
 REMOVE SWSHUNT FROM BUS 243960                     /*05E.DANVIL    69.0
END
CONTINGENCY 'AEP_P4_#10687_05EDAN 2 138_N_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 REMOVE SWSHUNT FROM BUS 242629                     /*05E.MONU     138.0
END
CONTINGENCY 'AEP_P4_#8676_05EDANV2 230_S_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1    /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1    /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'AEP_P4_#13922_05OPOSSUMCK 138_D_SRT-A'
 OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1   /*05CANDLER MT 138.0 - 05OPOSSUMCK  138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1   /*05CANDLER MT 138.0 - 05RUSTBR     138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 243814 CKT 1   /*05CANDLER MT 138.0 - 05REDEYE     138.0
 OPEN BRANCH FROM BUS 242737 TO BUS 242785 CKT 1   /*05OPOSSUMCK  138.0 - 05S.LYNC     138.0
END
CONTINGENCY 'AEP_P1-2_#5471_SRT-A'
 OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1   /*05CANDLER MT 138.0 - 05OPOSSUMCK  138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1   /*05CANDLER MT 138.0 - 05RUSTBR     138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 243814 CKT 1   /*05CANDLER MT 138.0 - 05REDEYE     138.0
END
CONTINGENCY 'AEP_P1-2_#5366_SRT-A-1'
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS'
 OPEN BRANCH FROM BUS 313996 TO BUS 888888 CKT 1   /*6FINNEYWOOD  230.0 - AG1-285_230  230.0
 OPEN BRANCH FROM BUS 957480 TO BUS 313995 CKT 1   /*AF2-042 TP   500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
242575 to 242737 ckt 1
242687 to 242734 ckt 1
242701 to 314667 ckt 1
242741 to 242687 ckt 1
243814 to 242575 ckt 1
242802 to 242701 ckt 1
242802 to 243814 ckt 1
314667 to 242741 ckt 1
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC107.28 %388.0B416.23
78.07
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC107.04 %388.0B415.31
78.04
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC104.68 %388.0B406.15
74.56
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC104.5 %388.0B405.47
74.56
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC104.5 %388.0B405.46
74.56
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
12.38
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
17.68
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
17.66
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
17.66
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
17.67
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.54 %997.0C1092.15
13.34
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC102.99 %814.98B839.35
9.43
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC100.81 %814.98B821.61
9.43
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC104.49 %997.0C1041.75
13.38
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.06 %3220.44B3608.77
8.22
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.87 %3940.0C4131.96
12.95
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC136.05 %3940.0C5360.5
0.35
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC126.25 %3118.0C3936.62
9.52
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC125.57 %3940.0C4947.42
1.43
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC125.28 %3940.0C4935.86
1.71
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56722_SRT-A
BreakerAC123.17 %3940.0C4852.84
1.44
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC103.68 %3940.0C4085.15
8.53
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC102.34 %3940.0C4032.02
8.53
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC102.28 %3940.0C4029.66
0.72
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC100.58 %3940.0C3963.04
3.1
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC130.61 %4070.2B5316.1
12.9
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC125.49 %4070.2B5107.87
12.9
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC117.11 %4996.0C5851.06
18.39
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC116.55 %4996.0C5822.84
18.33
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC109.34 %4996.0C5462.74
18.39
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC104.29 %2858.0C2980.61
11.34
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC118.98 %4070.2B4842.86
12.08
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC105.0 %4996.0C5245.63
17.23
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC104.56 %4996.0C5223.84
17.19
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC103.0 %4996.0C5145.98
17.04
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC111.74 %3220.44B3598.36
8.22
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC104.6 %3940.0C4121.29
12.95
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC127.1 %4070.2B5173.4
12.08
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC113.85 %4996.0C5687.87
17.23
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.35 %4996.0C5662.94
17.19
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC111.73 %4996.0C5581.87
17.04
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC108.37 %392.0B424.81
78.07
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC108.13 %392.0B423.88
78.04
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-S
BreakerAC105.82 %392.0B414.81
74.56
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC105.64 %392.0B414.12
74.56
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC105.64 %392.0B414.12
74.56
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10830___SRT-A
TowerAC100.19 %392.0B392.76
75.6
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC100.14 %392.0B392.56
75.6
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC121.2 %4070.2B4933.15
12.08
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC108.55 %4996.0C5423.36
17.23
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.09 %4996.0C5400.34
17.19
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC106.51 %4996.0C5321.19
17.04

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.28 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:416.23
MW Contribution:
78.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
12.496
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684605SMG4
50/50
3.094
3151561HALLBR1
50/50
0.443
970223AG2-152 GEN
Solar/Wind Harmer
78.07
270016AE1-250 BESS
Solar/Wind Harmer
12.496
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.227
24684405SMG2
50/50
3.074
24684505SMG3
50/50
1.878
24728405LEESVG
50/50
0.331
24728405LEESVG
50/50
0.33
270574AD1-017 GEN2
Solar/Wind Harmer
22.144
270173AC1-122 GEN
Solar/Wind Harmer
3.409
316217AC1-145 GEN
Solar/Wind Harmer
3.462
316197AC1-042 GEN
Solar/Wind Harmer
2.624
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
1.007
958131AF2-107 GEN
Solar/Wind Harmer
2.397
24684705SMG5
50/50
1.183
24684305SMG1
50/50
1.113
270197AD1-017 GEN1
Solar/Wind Harmer
6.643
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.77
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.235

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.04 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:415.31
MW Contribution:
78.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
12.491
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.4
24684605SMG4
50/50
3.09
3151561HALLBR1
50/50
0.442
970223AG2-152 GEN
Solar/Wind Harmer
78.039
270016AE1-250 BESS
Solar/Wind Harmer
12.491
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
24684405SMG2
50/50
3.069
24684505SMG3
50/50
1.875
24728405LEESVG
50/50
0.331
24728405LEESVG
50/50
0.33
270574AD1-017 GEN2
Solar/Wind Harmer
22.128
270173AC1-122 GEN
Solar/Wind Harmer
3.403
316217AC1-145 GEN
Solar/Wind Harmer
3.456
316197AC1-042 GEN
Solar/Wind Harmer
2.62
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
1.005
958131AF2-107 GEN
Solar/Wind Harmer
2.39
24684705SMG5
50/50
1.181
24684305SMG1
50/50
1.112
270197AD1-017 GEN1
Solar/Wind Harmer
6.638
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.591
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.773
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:406.15
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.355
970223AG2-152 GEN
Solar/Wind Harmer
74.562
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.139
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.894
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.748
958131AF2-107 GEN
Solar/Wind Harmer
2.282
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.69
942751AE2-291 GEN
Solar/Wind Harmer
5.678
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.679
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.073
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.269

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.5 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.47
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.356
970223AG2-152 GEN
Solar/Wind Harmer
74.563
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.139
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.895
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.749
958131AF2-107 GEN
Solar/Wind Harmer
2.282
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.5 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.46
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.356
970223AG2-152 GEN
Solar/Wind Harmer
74.563
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.895
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.749
958131AF2-107 GEN
Solar/Wind Harmer
2.282
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
962751AG1-124 GEN
Solar/Wind Harmer
5.139
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
12.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
316468AD1-105 GEN
Solar/Wind Helper
1.089
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
TVALTFEXP_TVA->PJM
CLTF
10.596
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
17.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.18
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971277AH1-098 GEN
Solar/Wind Harmer
7.43
942671AE2-283 GEN
Solar/Wind Harmer
8.669
270013AE1-250 PV
Solar/Wind Harmer
3.251
970913AG2-568 GEN
Solar/Wind Harmer
9.375
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728305BUCHG2
50/50
7.18
270173AC1-122 GEN
Solar/Wind Harmer
3.446
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
958131AF2-107 GEN
Solar/Wind Harmer
7.107
24735205WLF2G2
Adder
8.042
971687AH1-348 GEN
Solar/Wind Harmer
1.363
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
24723205RIVRG3
Adder
23.046
24686505CER G6
Adder
9.917
972203AH1-686 GEN
Adder
2.716
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
339211AE2-254 GEN
Solar/Wind Harmer
1.567
964901AG1-354 GEN
Solar/Wind Harmer
15.55
960001AF2-291 GEN
Solar/Wind Harmer
3.133
339241AF1-083 GEN
Solar/Wind Harmer
1.722
3429241JKCT 3G
Adder
12.084
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
943111AE2-339 GEN
Solar/Wind Harmer
0.887
339221AD2-048_GEN
Solar/Wind Harmer
1.518
945681AF1-233 GEN
Solar/Wind Harmer
18.414
970091AG2-072 GEN
Adder
74.384
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
971485AH1-239 GEN
Solar/Wind Harmer
8.528
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964781AG1-341 GEN
Solar/Wind Harmer
11.012
339236AF1-050_GEN
Solar/Wind Harmer
1.88
942891AE2-308 GEN
Solar/Wind Harmer
10.222
964571AG1-320 GEN
Solar/Wind Harmer
8.222
971125AH1-004 GEN
Solar/Wind Harmer
4.008
970107AG2-081 GEN
Solar/Wind Harmer
3.006
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252510AF1-249 C
Solar/Wind Harmer
0.385
971073AG2-665 GEN
Solar/Wind Harmer
1.074
25194608D.CRK4
Adder
1.517
965911AG1-460 GEN
Solar/Wind Harmer
1.277
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
276621W2-048 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
270222AC2-111 GEN
Solar/Wind Harmer
4.015
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276655WTG1_EQ
Solar/Wind Harmer
7.791
276656WTG2_EQ
Solar/Wind Harmer
1.032
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
274766LEE CO EC;7U
Adder
8.167
274822ROCKFORD ;11
Adder
17.365
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
276615X2-022 GEN
Solar/Wind Harmer
1.781
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960611AF2-352 GEN
Solar/Wind Harmer
2.083
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274696ROCKY RD ;4P
Adder
10.01
274695ROCKY RD ;2P
Adder
9.779
274693ROCKY RD ;1P
Adder
9.683
274697ROCKY RD ;3P
Adder
2.656
253370AE2-315 SEC1
Adder
1.749
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.655
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
966871AG1-558 GEN
Solar/Wind Helper
0.307
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
274732ELWOOD EC;7P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274674JOLIET 9 ;6U
Adder
13.445
274676JOLIET 29;8U
Adder
22.605
3148013FISHERV
Solar/Wind Helper
0.524
316499AE2-029_GEN
Solar/Wind Helper
1.728
315821AE2-092 GEN
Solar/Wind Helper
3.236
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.324
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
24385905FR-11G C
Solar/Wind Harmer
5.645
24386605FR-22G C
Solar/Wind Harmer
2.921
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.212
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
15.01
970563AG2-360 GEN
50/50
45.925
970417AG2-272 GEN
50/50
3.737
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.417
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.813
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270018AE2-047 C O1
Solar/Wind Harmer
1.823
960911AF2-382 GEN
Solar/Wind Harmer
10.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24686405CER G5
Adder
9.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
972273AH1-721 GEN
Adder
89.66
24721905FLATG4
Adder
21.789
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970653AG2-424 GEN
Solar/Wind Harmer
0.709
971191AH1-055 GEN
Solar/Wind Harmer
18.939
3429391JKCT 9G
Adder
8.441
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972167AH1-666 GEN
Solar/Wind Harmer
7.807
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196008MFTGT1
Adder
1.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
970879AG2-548 GEN
Solar/Wind Harmer
7.39
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
942481AE2-261 GEN
Solar/Wind Harmer
27.366
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728705AND G3
Adder
7.32
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
965931AG1-462 GEN
Solar/Wind Harmer
22.875
971087AG2-675 GEN
Solar/Wind Harmer
3.338
965091AG1-374 GEN
Solar/Wind Harmer
26.876
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274760LEE CO EC;1U
Adder
8.264
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.852
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.911
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971329AH1-144 GEN
Solar/Wind Harmer
11.745
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270069AE2-166 C O1
Solar/Wind Harmer
14.894
971313AH1-133 GEN
Solar/Wind Harmer
9.348
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
970281AG2-184 GEN
Solar/Wind Harmer
27.213
971981AH1-535 GEN
Solar/Wind Harmer
12.593
962211AG1-066 GEN
Solar/Wind Harmer
3.011
971061AG2-657 GEN
Solar/Wind Harmer
11.048
3429211JKCT 2G
Adder
11.928
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
25196508WSDLE4
Adder
7.812
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
270356AE2-297 GEN
Solar/Wind Harmer
4.168
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
963841AG1-237 GEN
Solar/Wind Harmer
9.807
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
959341AF2-225 GEN
Solar/Wind Harmer
13.389
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274744AC1-111 GEN8
Adder
4.896
274746AC1-111 G10
Adder
4.896
25306009OHH W.
Adder
2.518
274728ELWOOD EC;5P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
316164AC1-076 GEN
Solar/Wind Helper
1.182
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.093
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
3141426STAFORD
Solar/Wind Helper
0.049
24386405FR-21G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
TVALTFEXP_TVA->PJM
CLTF
10.64
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
17.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.164
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
942671AE2-283 GEN
Solar/Wind Harmer
8.664
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.164
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.104
24735205WLF2G2
Adder
8.025
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723205RIVRG3
Adder
22.967
24686505CER G6
Adder
9.881
972203AH1-686 GEN
Adder
2.706
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339211AE2-254 GEN
Solar/Wind Harmer
1.561
339241AF1-083 GEN
Solar/Wind Harmer
1.716
960001AF2-291 GEN
Solar/Wind Harmer
3.117
3429241JKCT 3G
Adder
12.037
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339221AD2-048_GEN
Solar/Wind Harmer
1.511
945681AF1-233 GEN
Solar/Wind Harmer
18.334
970091AG2-072 GEN
Adder
74.077
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252510AF1-249 C
Solar/Wind Harmer
0.384
971073AG2-665 GEN
Solar/Wind Harmer
1.068
25194608D.CRK4
Adder
1.51
965911AG1-460 GEN
Solar/Wind Harmer
1.272
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
276621W2-048 GEN
Solar/Wind Harmer
5.648
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
944031AF1-071 GEN
Solar/Wind Harmer
0.899
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
276655WTG1_EQ
Solar/Wind Harmer
7.757
276656WTG2_EQ
Solar/Wind Harmer
1.027
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274761LEE CO EC;2U
Adder
8.229
274766LEE CO EC;7U
Adder
8.132
274822ROCKFORD ;11
Adder
17.29
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
274676JOLIET 29;8U
Adder
26.663
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.232
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.627
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.304
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
24385905FR-11G C
Solar/Wind Harmer
4.044
24386605FR-22G C
Solar/Wind Harmer
2.093
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
971485AH1-239 GEN
Solar/Wind Harmer
8.501
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964781AG1-341 GEN
Solar/Wind Harmer
10.975
339236AF1-050_GEN
Solar/Wind Harmer
1.873
942891AE2-308 GEN
Solar/Wind Harmer
10.182
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
276615X2-022 GEN
Solar/Wind Harmer
1.774
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960611AF2-352 GEN
Solar/Wind Harmer
2.075
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274696ROCKY RD ;4P
Adder
9.966
274695ROCKY RD ;2P
Adder
9.736
274693ROCKY RD ;1P
Adder
9.64
274697ROCKY RD ;3P
Adder
2.645
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.65
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.98
970563AG2-360 GEN
50/50
45.836
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.819
958121AF2-106 GEN
Solar/Wind Harmer
9.406
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.808
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.95
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24686405CER G5
Adder
9.803
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
972273AH1-721 GEN
Adder
89.361
24721905FLATG4
Adder
21.701
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.408
971191AH1-055 GEN
Solar/Wind Harmer
18.847
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196008MFTGT1
Adder
1.253
252519AF1-045_GEN
Solar/Wind Harmer
3.354
970879AG2-548 GEN
Solar/Wind Harmer
7.349
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
942481AE2-261 GEN
Solar/Wind Harmer
27.253
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728705AND G3
Adder
7.288
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
965931AG1-462 GEN
Solar/Wind Harmer
22.779
971087AG2-675 GEN
Solar/Wind Harmer
3.324
965091AG1-374 GEN
Solar/Wind Harmer
26.762
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274760LEE CO EC;1U
Adder
8.229
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.847
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.085
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
971329AH1-144 GEN
Solar/Wind Harmer
11.729
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.878
971313AH1-133 GEN
Solar/Wind Harmer
9.329
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
970281AG2-184 GEN
Solar/Wind Harmer
27.137
971981AH1-535 GEN
Solar/Wind Harmer
12.564
962211AG1-066 GEN
Solar/Wind Harmer
3.002
971061AG2-657 GEN
Solar/Wind Harmer
11.001
3429211JKCT 2G
Adder
11.881
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
25196508WSDLE4
Adder
7.775
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270356AE2-297 GEN
Solar/Wind Harmer
4.149
253406AD2-031_GEN
Solar/Wind Harmer
1.147
963841AG1-237 GEN
Solar/Wind Harmer
9.765
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
959341AF2-225 GEN
Solar/Wind Harmer
13.331
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274744AC1-111 GEN8
Adder
4.874
274746AC1-111 G10
Adder
4.874
274728ELWOOD EC;5P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316164AC1-076 GEN
Solar/Wind Helper
1.178
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.09
24386405FR-21G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
TVALTFEXP_TVA->PJM
CLTF
10.609
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
17.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971277AH1-098 GEN
Solar/Wind Harmer
7.416
942671AE2-283 GEN
Solar/Wind Harmer
8.662
270013AE1-250 PV
Solar/Wind Harmer
3.247
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
971485AH1-239 GEN
Solar/Wind Harmer
8.488
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964781AG1-341 GEN
Solar/Wind Harmer
10.959
339236AF1-050_GEN
Solar/Wind Harmer
1.871
942891AE2-308 GEN
Solar/Wind Harmer
10.165
964571AG1-320 GEN
Solar/Wind Harmer
8.178
971125AH1-004 GEN
Solar/Wind Harmer
3.985
970107AG2-081 GEN
Solar/Wind Harmer
2.988
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
276615X2-022 GEN
Solar/Wind Harmer
1.77
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
24387305FR-4G C
Solar/Wind Harmer
2.467
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
18.814
958121AF2-106 GEN
Solar/Wind Harmer
9.401
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.805
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270018AE2-047 C O1
Solar/Wind Harmer
1.82
960911AF2-382 GEN
Solar/Wind Harmer
10.939
270016AE1-250 BESS
Solar/Wind Harmer
3.247
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24686405CER G5
Adder
9.787
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.807
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.758
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
7.33
252524AE2-267 GEN
Solar/Wind Harmer
1.44
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
942481AE2-261 GEN
Solar/Wind Harmer
27.203
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
965931AG1-462 GEN
Solar/Wind Harmer
22.737
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
26.711
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
24386205FR-12G C
Solar/Wind Harmer
2.081
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
270173AC1-122 GEN
Solar/Wind Harmer
3.443
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
958131AF2-107 GEN
Solar/Wind Harmer
7.102
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339211AE2-254 GEN
Solar/Wind Harmer
1.559
339241AF1-083 GEN
Solar/Wind Harmer
1.713
960001AF2-291 GEN
Solar/Wind Harmer
3.11
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.508
945681AF1-233 GEN
Solar/Wind Harmer
18.298
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
276621W2-048 GEN
Solar/Wind Harmer
5.637
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
944031AF1-071 GEN
Solar/Wind Harmer
0.897
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
276655WTG1_EQ
Solar/Wind Harmer
7.743
276656WTG2_EQ
Solar/Wind Harmer
1.025
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
274822ROCKFORD ;11
Adder
17.258
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24385905FR-11G C
Solar/Wind Harmer
4.036
24386605FR-22G C
Solar/Wind Harmer
2.088
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
11.722
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270069AE2-166 C O1
Solar/Wind Harmer
14.87
971313AH1-133 GEN
Solar/Wind Harmer
9.321
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
970281AG2-184 GEN
Solar/Wind Harmer
27.103
971981AH1-535 GEN
Solar/Wind Harmer
12.552
962211AG1-066 GEN
Solar/Wind Harmer
2.998
971061AG2-657 GEN
Solar/Wind Harmer
10.98
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
270356AE2-297 GEN
Solar/Wind Harmer
4.141
253406AD2-031_GEN
Solar/Wind Harmer
1.145
963841AG1-237 GEN
Solar/Wind Harmer
9.746
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
959341AF2-225 GEN
Solar/Wind Harmer
13.306
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
24386405FR-21G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
TVALTFEXP_TVA->PJM
CLTF
10.596
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
17.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.16
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.106
24735205WLF2G2
Adder
8.021
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.973
970563AG2-360 GEN
50/50
45.815
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.82
958121AF2-106 GEN
Solar/Wind Harmer
9.404
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.809
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.944
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24686405CER G5
Adder
9.792
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.284
24721905FLATG4
Adder
21.675
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.399
971191AH1-055 GEN
Solar/Wind Harmer
18.819
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.764
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196008MFTGT1
Adder
1.252
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
970879AG2-548 GEN
Solar/Wind Harmer
7.336
252524AE2-267 GEN
Solar/Wind Harmer
1.441
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
942481AE2-261 GEN
Solar/Wind Harmer
27.222
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.16
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971277AH1-098 GEN
Solar/Wind Harmer
7.418
942671AE2-283 GEN
Solar/Wind Harmer
8.665
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
971485AH1-239 GEN
Solar/Wind Harmer
8.494
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964781AG1-341 GEN
Solar/Wind Harmer
10.966
339236AF1-050_GEN
Solar/Wind Harmer
1.872
942891AE2-308 GEN
Solar/Wind Harmer
10.171
964571AG1-320 GEN
Solar/Wind Harmer
8.183
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
24723205RIVRG3
Adder
22.944
24686505CER G6
Adder
9.87
972203AH1-686 GEN
Adder
2.703
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339211AE2-254 GEN
Solar/Wind Harmer
1.56
339241AF1-083 GEN
Solar/Wind Harmer
1.714
960001AF2-291 GEN
Solar/Wind Harmer
3.112
3429241JKCT 3G
Adder
12.024
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.509
945681AF1-233 GEN
Solar/Wind Harmer
18.311
970091AG2-072 GEN
Adder
73.991
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.508
971073AG2-665 GEN
Solar/Wind Harmer
1.066
965911AG1-460 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960611AF2-352 GEN
Solar/Wind Harmer
2.072
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274696ROCKY RD ;4P
Adder
9.954
274695ROCKY RD ;2P
Adder
9.725
274693ROCKY RD ;1P
Adder
9.629
274697ROCKY RD ;3P
Adder
2.642
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.646
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
24387305FR-4G C
Solar/Wind Harmer
2.468
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971329AH1-144 GEN
Solar/Wind Harmer
11.725
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.876
971313AH1-133 GEN
Solar/Wind Harmer
9.325
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
970281AG2-184 GEN
Solar/Wind Harmer
27.117
971981AH1-535 GEN
Solar/Wind Harmer
12.558
962211AG1-066 GEN
Solar/Wind Harmer
3
971061AG2-657 GEN
Solar/Wind Harmer
10.986
3429211JKCT 2G
Adder
11.868
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
25196508WSDLE4
Adder
7.765
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728705AND G3
Adder
7.279
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
965931AG1-462 GEN
Solar/Wind Harmer
22.754
971087AG2-675 GEN
Solar/Wind Harmer
3.32
24728605AND G2
Adder
3.48
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
270356AE2-297 GEN
Solar/Wind Harmer
4.144
253406AD2-031_GEN
Solar/Wind Harmer
1.146
963841AG1-237 GEN
Solar/Wind Harmer
9.753
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
959341AF2-225 GEN
Solar/Wind Harmer
13.316
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
274728ELWOOD EC;5P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
316468AD1-105 GEN
Solar/Wind Helper
1.088
24386405FR-21G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
276621W2-048 GEN
Solar/Wind Harmer
5.641
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
944031AF1-071 GEN
Solar/Wind Harmer
0.898
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
276655WTG1_EQ
Solar/Wind Harmer
7.748
276656WTG2_EQ
Solar/Wind Harmer
1.026
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274761LEE CO EC;2U
Adder
8.219
274766LEE CO EC;7U
Adder
8.123
274822ROCKFORD ;11
Adder
17.27
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
274676JOLIET 29;8U
Adder
26.631
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
315821AE2-092 GEN
Solar/Wind Helper
3.228
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.293
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24385905FR-11G C
Solar/Wind Harmer
4.039
24386605FR-22G C
Solar/Wind Harmer
2.09
965091AG1-374 GEN
Solar/Wind Harmer
26.73
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274760LEE CO EC;1U
Adder
8.219
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.844
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
24386205FR-12G C
Solar/Wind Harmer
2.082
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
TVALTFEXP_TVA->PJM
CLTF
10.603
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.54 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1092.15
MW Contribution:
13.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.135
24728405LEESVG
50/50
0.135
316003AC1-222 GEN
Solar/Wind Harmer
3.847
971683AH1-343 GEN
Solar/Wind Harmer
15.734
316222AC1-221 GEN
Solar/Wind Harmer
3.092
316123AC1-075 GEN
Solar/Wind Harmer
3.227
316283AC2-100 C
Solar/Wind Harmer
2.821
970917AG2-570 GEN
Solar/Wind Harmer
39.781
316217AC1-145 GEN
Solar/Wind Harmer
2.363
3152661PLYWOOD A
50/50
0.676
315687AD1-152 GEN
Solar/Wind Harmer
8.923
316248AF1-058 C
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
2.349
942751AE2-291 GEN
Solar/Wind Harmer
17.164
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.581
962561AG1-105 GEN
Solar/Wind Harmer
12.789
942671AE2-283 GEN
Solar/Wind Harmer
4.827
270013AE1-250 PV
Solar/Wind Harmer
2.224
961601AG1-000A GEN
Solar/Wind Harmer
2.753
316049AB1-081 GEN
Solar/Wind Harmer
0.749
316263AC1-034 GEN
Solar/Wind Harmer
3.262
3146776BUCKING
Solar/Wind Helper
0.778
3146776BUCKING
Solar/Wind Helper
0.063
316294AC1-161 GEN
Solar/Wind Helper
3.081
316185AD1-033 GEN
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.598
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316240AF1-291 C
Solar/Wind Helper
0.198
316033AB2-134 GEN
Solar/Wind Helper
0.505
316339AD2-160 GEN
Solar/Wind Helper
0.556
316388AE2-253 GEN
Solar/Wind Helper
0.556
3137176SLIGO L2192
Solar/Wind Helper
0.568
3130086AYDLETT
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.213
316349AD2-085 GEN
Solar/Wind Helper
0.637
3143526WINTERP
Solar/Wind Helper
0.717
316156AD2-030 GEN
Solar/Wind Helper
0.206
315666AE1-190 GEN
Solar/Wind Helper
0.183
3142946ENON
Solar/Wind Helper
0.014
315976AC1-164 GENA
Solar/Wind Helper
1.72
316169AC1-164_GENC
Solar/Wind Helper
1.486
316487AF1-042 GEN
Solar/Wind Helper
0.133
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.233
316315AB2-025 C
Solar/Wind Helper
0.199
316312AB1-027
Solar/Wind Helper
0.242
966871AG1-558 GEN
Solar/Wind Helper
0.164
316431W1029_GEN1
Solar/Wind Helper
0.484
316433W1029_GEN2
Solar/Wind Helper
0.484
316435W1029_GEN3
Solar/Wind Helper
0.484
3146516WINFALL
Solar/Wind Helper
0.117
971629AH1-314 GEN
50/50
13.497
3151561HALLBR1
50/50
0.369
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.92
970919AG2-571 GEN
Solar/Wind Harmer
5.036
970223AG2-152 GEN
Solar/Wind Harmer
13.344
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.465
270016AE1-250 BESS
Solar/Wind Harmer
2.224
270018AE2-047 C O1
Solar/Wind Harmer
1.017
270030AE2-140 GEN
Solar/Wind Harmer
14.76
316359AB2-059 GEN
Solar/Wind Harmer
0.936
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.078
315773AC2-141 GEN
Solar/Wind Helper
3.625
316375AC2-012 GEN
Solar/Wind Helper
0.406
316036AC1-147 C
Solar/Wind Helper
0.236
3145336SMITFLD
Solar/Wind Helper
0.602
315671AE2-027_GEN
Solar/Wind Helper
1.203
316381AD1-082 GEN
Solar/Wind Helper
0.759
316369SG1_INVT
Solar/Wind Helper
0.703
316132AB2-190 GEN1
Solar/Wind Helper
0.827
3146456SLIGO L269
Solar/Wind Helper
0.142
316072AD1-144
Solar/Wind Helper
0.163
319010AE1-072 C
Solar/Wind Helper
1.621
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3143226MDLTHAN
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
0.717
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.545
315662AE1-191 GEN
Solar/Wind Helper
0.733
316280AD1-041 GEN
Solar/Wind Helper
0.458
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.081
315975AC1-164 GENB
Solar/Wind Helper
0.051
316404AE1-155 C
Solar/Wind Helper
1.113
964211AG1-282 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.513
3142416OLDCHRC
Solar/Wind Helper
0.329
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.379
3146516WINFALL
Solar/Wind Helper
0.117
316197AC1-042 GEN
Solar/Wind Harmer
1.792
3147312GRETNA
Solar/Wind Harmer
-0.003
270574AD1-017 GEN2
Solar/Wind Harmer
4.505
943811AF1-049 GEN
Solar/Wind Harmer
2.871
270336AE1-100 GEN
Solar/Wind Harmer
1.165
270173AC1-122 GEN
Solar/Wind Harmer
1.092
961601AG1-000A GEN
Solar/Wind Harmer
2.787
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.088
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
942461AE2-259 GEN
Solar/Wind Helper
1.132
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.103
3145336SMITFLD
Solar/Wind Helper
0.06
316017AA1-139 ULT1
Solar/Wind Helper
0.662
316458AB2-190 GEN2
Solar/Wind Helper
0.827
3146456SLIGO L269
Solar/Wind Helper
0.142
316305AF2-043 C
Solar/Wind Helper
0.189
316246AF1-032 C
Solar/Wind Helper
0.161
3142946ENON
Solar/Wind Helper
0.045
316075AC2-137 C
Solar/Wind Helper
0.201
316484AD2-074 GEN
Solar/Wind Helper
0.254
316320Y1-086
Solar/Wind Helper
0.059
316077AC2-138 C
Solar/Wind Helper
0.12
316321Z2-027
Solar/Wind Helper
0.193
316473AC1-191 GEN
Solar/Wind Helper
0.745
316223AC1-118
Solar/Wind Helper
0.184
3141906WESTMOR
Solar/Wind Helper
0.048
3146516WINFALL
Solar/Wind Helper
0.117
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
270455AD2-022 GEN
Solar/Wind Harmer
3.533
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.947
970581AG2-369 GEN
Solar/Wind Harmer
8.554
270197AD1-017 GEN1
Solar/Wind Harmer
1.351
270069AE2-166 C O1
Solar/Wind Harmer
5.959
971981AH1-535 GEN
Solar/Wind Harmer
4.612
316486AD2-202 GEN
Solar/Wind Helper
0.904
316322AB2-045
Solar/Wind Helper
0.218
3143316POE
Solar/Wind Helper
0.633
316316AC1-027 C
Solar/Wind Helper
0.242
315839AE2-212 C
Solar/Wind Helper
0.205
316236AE1-162_GEN
Solar/Wind Helper
0.203
315697AD1-025 GEN
Solar/Wind Helper
1.667
316018AA1-139 ULT2
Solar/Wind Helper
0.623
316382AG1-145 C
Solar/Wind Helper
0.194
316159AE1-175 C
Solar/Wind Helper
0.218
957831AF2-077 GEN
Solar/Wind Helper
0.192
316258AE1-075 C
Solar/Wind Helper
0.192
316405AF2-144 C
Solar/Wind Helper
0.16
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.137
3141913WHIT STONE
Solar/Wind Helper
0.135
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.078
316468AD1-105 GEN
Solar/Wind Helper
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
9.216
CPLELTFEXP_CPLE->PJM
CLTF
11.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.64
TVALTFEXP_TVA->PJM
CLTF
4.614
MECLTFEXP_MEC->PJM
CLTF
5.236
SIGELTFEXP_SIGE->PJM
CLTF
0.16
NYPJM->LTFIMP_NY
CLTF
0.751
LGEELTFEXP_LGEE->PJM
CLTF
1.985
WECLTFEXP_WEC->PJM
CLTF
1.051

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.99 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:839.35
MW Contribution:
9.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.678
316118AC1-105 GEN
Solar/Wind Harmer
0.783
942751AE2-291 GEN
Solar/Wind Harmer
13.09
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.484
962561AG1-105 GEN
Solar/Wind Harmer
9.76
942671AE2-283 GEN
Solar/Wind Harmer
3.253
961601AG1-000A GEN
Solar/Wind Harmer
1.126
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
24684405SMG2
50/50
0.846
24684505SMG3
50/50
0.517
971683AH1-343 GEN
Solar/Wind Harmer
11.986
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316049AB1-081 GEN
Solar/Wind Harmer
0.358
316263AC1-034 GEN
Solar/Wind Harmer
2.392
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
316294AC1-161 GEN
Solar/Wind Helper
3.045
316185AD1-033 GEN
Solar/Wind Helper
0.708
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.196
316033AB2-134 GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
0.548
316388AE2-253 GEN
Solar/Wind Helper
0.548
3137176SLIGO L2192
Solar/Wind Helper
0.56
3130086AYDLETT
Solar/Wind Helper
0.556
316313AB2-026
Solar/Wind Helper
0.21
316349AD2-085 GEN
Solar/Wind Helper
0.628
3143526WINTERP
Solar/Wind Helper
0.707
316156AD2-030 GEN
Solar/Wind Helper
0.203
315666AE1-190 GEN
Solar/Wind Helper
0.181
3142946ENON
Solar/Wind Helper
0.013
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
316435W1029_GEN3
Solar/Wind Helper
0.476
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
971629AH1-314 GEN
50/50
13.585
3151561HALLBR1
50/50
0.371
970417AG2-272 GEN
50/50
1.9
24684605SMG4
50/50
0.852
24288905REUSENS
50/50
0.013
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970919AG2-571 GEN
Solar/Wind Harmer
5.071
970223AG2-152 GEN
Solar/Wind Harmer
9.427
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.182
270030AE2-140 GEN
Solar/Wind Harmer
10.404
316359AB2-059 GEN
Solar/Wind Harmer
0.224
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.583
316375AC2-012 GEN
Solar/Wind Helper
0.401
316036AC1-147 C
Solar/Wind Helper
0.233
3145336SMITFLD
Solar/Wind Helper
0.594
315671AE2-027_GEN
Solar/Wind Helper
1.187
316381AD1-082 GEN
Solar/Wind Helper
0.748
316369SG1_INVT
Solar/Wind Helper
0.693
316132AB2-190 GEN1
Solar/Wind Helper
0.816
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.161
319010AE1-072 C
Solar/Wind Helper
1.598
3143226MDLTHAN
Solar/Wind Helper
0.139
3143526WINTERP
Solar/Wind Helper
0.707
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.537
315662AE1-191 GEN
Solar/Wind Helper
0.723
316280AD1-041 GEN
Solar/Wind Helper
0.452
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
315975AC1-164 GENB
Solar/Wind Helper
0.05
316404AE1-155 C
Solar/Wind Helper
1.096
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
316123AC1-075 GEN
Solar/Wind Harmer
0.357
316283AC2-100 C
Solar/Wind Harmer
0.523
970917AG2-570 GEN
Solar/Wind Harmer
12.677
3147312GRETNA
Solar/Wind Harmer
0.026
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.503
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.078
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
942461AE2-259 GEN
Solar/Wind Helper
1.118
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.102
3145336SMITFLD
Solar/Wind Helper
0.059
316017AA1-139 ULT1
Solar/Wind Helper
0.653
316458AB2-190 GEN2
Solar/Wind Helper
0.816
3146456SLIGO L269
Solar/Wind Helper
0.141
316305AF2-043 C
Solar/Wind Helper
0.187
316246AF1-032 C
Solar/Wind Helper
0.159
3142946ENON
Solar/Wind Helper
0.045
316075AC2-137 C
Solar/Wind Helper
0.198
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316077AC2-138 C
Solar/Wind Helper
0.118
316321Z2-027
Solar/Wind Helper
0.19
316473AC1-191 GEN
Solar/Wind Helper
0.733
316223AC1-118
Solar/Wind Helper
0.181
3141906WESTMOR
Solar/Wind Helper
0.047
3146516WINFALL
Solar/Wind Helper
0.115
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
24684705SMG5
50/50
0.326
24684305SMG1
50/50
0.307
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970085AG2-068 GEN
Solar/Wind Harmer
7.608
970581AG2-369 GEN
Solar/Wind Harmer
6.542
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
270069AE2-166 C O1
Solar/Wind Harmer
4.205
971981AH1-535 GEN
Solar/Wind Harmer
2.18
316486AD2-202 GEN
Solar/Wind Helper
0.901
316322AB2-045
Solar/Wind Helper
0.215
3143316POE
Solar/Wind Helper
0.625
316316AC1-027 C
Solar/Wind Helper
0.238
315839AE2-212 C
Solar/Wind Helper
0.203
316236AE1-162_GEN
Solar/Wind Helper
0.2
315697AD1-025 GEN
Solar/Wind Helper
1.645
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316382AG1-145 C
Solar/Wind Helper
0.191
316159AE1-175 C
Solar/Wind Helper
0.215
957831AF2-077 GEN
Solar/Wind Helper
0.189
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.158
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
3145176PASQUOTANK
Solar/Wind Helper
0.077
316468AD1-105 GEN
Solar/Wind Helper
0.539
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CPLELTFEXP_CPLE->PJM
CLTF
11.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
TVALTFEXP_TVA->PJM
CLTF
4.691
MECLTFEXP_MEC->PJM
CLTF
5.364
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:821.61
MW Contribution:
9.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.326
24684305SMG1
50/50
0.307
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970085AG2-068 GEN
Solar/Wind Harmer
7.608
970581AG2-369 GEN
Solar/Wind Harmer
6.542
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
270069AE2-166 C O1
Solar/Wind Harmer
4.205
971981AH1-535 GEN
Solar/Wind Harmer
2.18
316486AD2-202 GEN
Solar/Wind Helper
0.901
316322AB2-045
Solar/Wind Helper
0.215
3143316POE
Solar/Wind Helper
0.625
316316AC1-027 C
Solar/Wind Helper
0.238
315839AE2-212 C
Solar/Wind Helper
0.203
316236AE1-162_GEN
Solar/Wind Helper
0.2
315697AD1-025 GEN
Solar/Wind Helper
1.645
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316382AG1-145 C
Solar/Wind Helper
0.191
316159AE1-175 C
Solar/Wind Helper
0.215
957831AF2-077 GEN
Solar/Wind Helper
0.189
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.158
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
971629AH1-314 GEN
50/50
13.585
3151561HALLBR1
50/50
0.371
970417AG2-272 GEN
50/50
1.9
24684605SMG4
50/50
0.852
24288905REUSENS
50/50
0.013
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970223AG2-152 GEN
Solar/Wind Harmer
9.427
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.182
270030AE2-140 GEN
Solar/Wind Harmer
10.404
316359AB2-059 GEN
Solar/Wind Harmer
0.224
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.583
316375AC2-012 GEN
Solar/Wind Helper
0.401
316036AC1-147 C
Solar/Wind Helper
0.233
3145336SMITFLD
Solar/Wind Helper
0.594
315671AE2-027_GEN
Solar/Wind Helper
1.187
316381AD1-082 GEN
Solar/Wind Helper
0.748
316369SG1_INVT
Solar/Wind Helper
0.693
316132AB2-190 GEN1
Solar/Wind Helper
0.816
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.161
319010AE1-072 C
Solar/Wind Helper
1.598
3143226MDLTHAN
Solar/Wind Helper
0.139
3143526WINTERP
Solar/Wind Helper
0.707
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.537
315662AE1-191 GEN
Solar/Wind Helper
0.723
316280AD1-041 GEN
Solar/Wind Helper
0.452
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
315975AC1-164 GENB
Solar/Wind Helper
0.05
316404AE1-155 C
Solar/Wind Helper
1.096
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
3145176PASQUOTANK
Solar/Wind Helper
0.077
316468AD1-105 GEN
Solar/Wind Helper
0.539
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
24684405SMG2
50/50
0.846
24684505SMG3
50/50
0.517
971683AH1-343 GEN
Solar/Wind Harmer
11.986
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316123AC1-075 GEN
Solar/Wind Harmer
0.357
316283AC2-100 C
Solar/Wind Harmer
0.523
3147312GRETNA
Solar/Wind Harmer
0.026
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.503
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.078
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
942461AE2-259 GEN
Solar/Wind Helper
1.118
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.102
3145336SMITFLD
Solar/Wind Helper
0.059
316017AA1-139 ULT1
Solar/Wind Helper
0.653
316458AB2-190 GEN2
Solar/Wind Helper
0.816
3146456SLIGO L269
Solar/Wind Helper
0.141
316305AF2-043 C
Solar/Wind Helper
0.187
316246AF1-032 C
Solar/Wind Helper
0.159
3142946ENON
Solar/Wind Helper
0.045
316075AC2-137 C
Solar/Wind Helper
0.198
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316077AC2-138 C
Solar/Wind Helper
0.118
316321Z2-027
Solar/Wind Helper
0.19
316473AC1-191 GEN
Solar/Wind Helper
0.733
316223AC1-118
Solar/Wind Helper
0.181
3141906WESTMOR
Solar/Wind Helper
0.047
3146516WINFALL
Solar/Wind Helper
0.115
3152661PLYWOOD A
50/50
0.678
316118AC1-105 GEN
Solar/Wind Harmer
0.783
942751AE2-291 GEN
Solar/Wind Harmer
13.09
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.484
962561AG1-105 GEN
Solar/Wind Harmer
9.76
942671AE2-283 GEN
Solar/Wind Harmer
3.253
961601AG1-000A GEN
Solar/Wind Harmer
1.126
316049AB1-081 GEN
Solar/Wind Harmer
0.358
316263AC1-034 GEN
Solar/Wind Harmer
2.392
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
316294AC1-161 GEN
Solar/Wind Helper
3.045
316185AD1-033 GEN
Solar/Wind Helper
0.708
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.196
316033AB2-134 GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
0.548
316388AE2-253 GEN
Solar/Wind Helper
0.548
3137176SLIGO L2192
Solar/Wind Helper
0.56
3130086AYDLETT
Solar/Wind Helper
0.556
316313AB2-026
Solar/Wind Helper
0.21
316349AD2-085 GEN
Solar/Wind Helper
0.628
3143526WINTERP
Solar/Wind Helper
0.707
316156AD2-030 GEN
Solar/Wind Helper
0.203
315666AE1-190 GEN
Solar/Wind Helper
0.181
3142946ENON
Solar/Wind Helper
0.013
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
316435W1029_GEN3
Solar/Wind Helper
0.476
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CPLELTFEXP_CPLE->PJM
CLTF
11.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
TVALTFEXP_TVA->PJM
CLTF
4.691
MECLTFEXP_MEC->PJM
CLTF
5.364
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1041.75
MW Contribution:
13.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.677
316248AF1-058 C
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
2.352
942751AE2-291 GEN
Solar/Wind Harmer
17.187
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.589
962561AG1-105 GEN
Solar/Wind Harmer
12.809
942671AE2-283 GEN
Solar/Wind Harmer
4.839
270013AE1-250 PV
Solar/Wind Harmer
2.229
961601AG1-000A GEN
Solar/Wind Harmer
2.767
316049AB1-081 GEN
Solar/Wind Harmer
0.753
316263AC1-034 GEN
Solar/Wind Harmer
3.279
315687AD1-152 GEN
Solar/Wind Helper
4.952
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316294AC1-161 GEN
Solar/Wind Helper
3.069
316185AD1-033 GEN
Solar/Wind Helper
0.714
3145506HICKORY
Solar/Wind Helper
0.596
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
24728405LEESVG
50/50
0.135
24728405LEESVG
50/50
0.135
316003AC1-222 GEN
Solar/Wind Harmer
3.851
971683AH1-343 GEN
Solar/Wind Harmer
15.749
316222AC1-221 GEN
Solar/Wind Harmer
3.095
316123AC1-075 GEN
Solar/Wind Harmer
3.231
316283AC2-100 C
Solar/Wind Harmer
2.824
970917AG2-570 GEN
Solar/Wind Harmer
39.871
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
270574AD1-017 GEN2
Solar/Wind Harmer
4.517
943811AF1-049 GEN
Solar/Wind Harmer
2.88
270336AE1-100 GEN
Solar/Wind Harmer
1.169
270173AC1-122 GEN
Solar/Wind Harmer
1.096
961601AG1-000A GEN
Solar/Wind Harmer
2.802
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.085
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.07
942461AE2-259 GEN
Solar/Wind Helper
1.127
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.103
3145336SMITFLD
Solar/Wind Helper
0.06
316017AA1-139 ULT1
Solar/Wind Helper
0.659
316458AB2-190 GEN2
Solar/Wind Helper
0.824
3146456SLIGO L269
Solar/Wind Helper
0.142
316305AF2-043 C
Solar/Wind Helper
0.189
316246AF1-032 C
Solar/Wind Helper
0.16
3142946ENON
Solar/Wind Helper
0.045
316075AC2-137 C
Solar/Wind Helper
0.2
316484AD2-074 GEN
Solar/Wind Helper
0.253
316320Y1-086
Solar/Wind Helper
0.059
316077AC2-138 C
Solar/Wind Helper
0.12
316321Z2-027
Solar/Wind Helper
0.192
316473AC1-191 GEN
Solar/Wind Helper
0.741
316223AC1-118
Solar/Wind Helper
0.183
3141906WESTMOR
Solar/Wind Helper
0.048
3146516WINFALL
Solar/Wind Helper
0.116
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
270455AD2-022 GEN
Solar/Wind Harmer
3.539
270457AD2-023 GEN
Solar/Wind Harmer
1.795
970085AG2-068 GEN
Solar/Wind Harmer
9.969
970581AG2-369 GEN
Solar/Wind Harmer
8.574
270197AD1-017 GEN1
Solar/Wind Harmer
1.355
270069AE2-166 C O1
Solar/Wind Harmer
5.981
971981AH1-535 GEN
Solar/Wind Harmer
4.636
316486AD2-202 GEN
Solar/Wind Helper
0.903
316322AB2-045
Solar/Wind Helper
0.217
3143316POE
Solar/Wind Helper
0.63
316316AC1-027 C
Solar/Wind Helper
0.241
315839AE2-212 C
Solar/Wind Helper
0.205
316236AE1-162_GEN
Solar/Wind Helper
0.202
316240AF1-291 C
Solar/Wind Helper
0.197
316033AB2-134 GEN
Solar/Wind Helper
0.502
316339AD2-160 GEN
Solar/Wind Helper
0.554
316388AE2-253 GEN
Solar/Wind Helper
0.554
3137176SLIGO L2192
Solar/Wind Helper
0.565
3130086AYDLETT
Solar/Wind Helper
0.561
316313AB2-026
Solar/Wind Helper
0.212
316349AD2-085 GEN
Solar/Wind Helper
0.634
3143526WINTERP
Solar/Wind Helper
0.714
316156AD2-030 GEN
Solar/Wind Helper
0.205
315666AE1-190 GEN
Solar/Wind Helper
0.182
3142946ENON
Solar/Wind Helper
0.014
315976AC1-164 GENA
Solar/Wind Helper
1.712
316169AC1-164_GENC
Solar/Wind Helper
1.479
316487AF1-042 GEN
Solar/Wind Helper
0.132
3146386ELIZ CT
Solar/Wind Helper
0.13
3144356SAPONY
Solar/Wind Helper
0.232
316315AB2-025 C
Solar/Wind Helper
0.198
316312AB1-027
Solar/Wind Helper
0.241
966871AG1-558 GEN
Solar/Wind Helper
0.163
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.116
3146516WINFALL
Solar/Wind Helper
0.116
3146516WINFALL
Solar/Wind Helper
0.116
971629AH1-314 GEN
50/50
13.525
3151561HALLBR1
50/50
0.37
970401AG2-262 GEN
Solar/Wind Harmer
1.708
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.954
970919AG2-571 GEN
Solar/Wind Harmer
5.047
970223AG2-152 GEN
Solar/Wind Harmer
13.376
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.478
270016AE1-250 BESS
Solar/Wind Harmer
2.229
270018AE2-047 C O1
Solar/Wind Harmer
1.02
270030AE2-140 GEN
Solar/Wind Harmer
14.809
316359AB2-059 GEN
Solar/Wind Harmer
0.941
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.078
315773AC2-141 GEN
Solar/Wind Helper
3.611
316375AC2-012 GEN
Solar/Wind Helper
0.404
316036AC1-147 C
Solar/Wind Helper
0.235
3145336SMITFLD
Solar/Wind Helper
0.599
315671AE2-027_GEN
Solar/Wind Helper
1.198
315697AD1-025 GEN
Solar/Wind Helper
1.66
316018AA1-139 ULT2
Solar/Wind Helper
0.62
316382AG1-145 C
Solar/Wind Helper
0.193
316159AE1-175 C
Solar/Wind Helper
0.217
957831AF2-077 GEN
Solar/Wind Helper
0.191
316258AE1-075 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.159
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.134
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
3146486SUNBURY
Solar/Wind Helper
0.127
3146486SUNBURY
Solar/Wind Helper
0.127
3141813NORNECK
Solar/Wind Helper
0.127
3145176PASQUOTANK
Solar/Wind Helper
0.078
316468AD1-105 GEN
Solar/Wind Helper
0.546
316381AD1-082 GEN
Solar/Wind Helper
0.755
316369SG1_INVT
Solar/Wind Helper
0.7
316132AB2-190 GEN1
Solar/Wind Helper
0.824
3146456SLIGO L269
Solar/Wind Helper
0.142
316072AD1-144
Solar/Wind Helper
0.162
319010AE1-072 C
Solar/Wind Helper
1.614
3143226MDLTHAN
Solar/Wind Helper
0.14
3143526WINTERP
Solar/Wind Helper
0.714
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.542
315662AE1-191 GEN
Solar/Wind Helper
0.73
316280AD1-041 GEN
Solar/Wind Helper
0.456
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
315975AC1-164 GENB
Solar/Wind Helper
0.051
316404AE1-155 C
Solar/Wind Helper
1.108
964211AG1-282 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.51
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.125
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.377
3146516WINFALL
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
9.266
CPLELTFEXP_CPLE->PJM
CLTF
11.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.529
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.97
TVALTFEXP_TVA->PJM
CLTF
4.639
MECLTFEXP_MEC->PJM
CLTF
5.278
SIGELTFEXP_SIGE->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.735
LGEELTFEXP_LGEE->PJM
CLTF
2.002
WECLTFEXP_WEC->PJM
CLTF
1.06

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3608.77
MW Contribution:
8.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3137383CUSHAW
50/50
0.077
247619Y1-049
50/50
0.033
270583AD2-179 GEN
Solar/Wind Harmer
9.704
942671AE2-283 GEN
Solar/Wind Harmer
4.019
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
3132123MT JACKSON
Solar/Wind Helper
1.116
237061AD1-155 GEN
Solar/Wind Helper
1.4
3152061BATH 6F
50/50
16.198
3152021BATH 2B
50/50
16.153
3151861LOWMORA
50/50
4.077
270205AE1-176
50/50
0.004
24290605CLAY-1
50/50
0.17
24290705CLAY-2
50/50
0.17
24684405SMG2
50/50
1.523
24684505SMG3
50/50
0.93
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
3147312GRETNA
Solar/Wind Harmer
0.032
958131AF2-107 GEN
Solar/Wind Harmer
3.841
943811AF1-049 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
4.099
316499AE2-029_GEN
Solar/Wind Helper
1.226
3148013FISHERV
Solar/Wind Helper
0.304
23583801GRNGAP
Solar/Wind Helper
3.89
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24290605CLAY-1
50/50
0.17
24290705CLAY-2
50/50
0.17
24684605SMG4
50/50
1.533
24415905BUCK
50/50
0.022
962751AG1-124 GEN
Solar/Wind Harmer
9.113
958121AF2-106 GEN
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
941801AE2-185 GEN
Solar/Wind Harmer
5.168
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
960911AF2-382 GEN
Solar/Wind Harmer
4.591
3147983MERCK5
Solar/Wind Helper
0.146
3152031BATH 3C
50/50
16.174
3152051BATH 5E
50/50
16.17
3152011BATH 1A
50/50
16.153
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
3151861LOWMORA
50/50
3.918
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
24684305SMG1
50/50
0.552
24416005BYLLESBY
50/50
0.02
3148463FAIRFLD
Solar/Wind Harmer
0.358
971331AH1-145 GEN
Solar/Wind Harmer
12.166
971329AH1-144 GEN
Solar/Wind Harmer
4.471
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
270069AE2-166 C O1
Solar/Wind Harmer
6.845
971313AH1-133 GEN
Solar/Wind Harmer
3.311
24734705WLF1G3
Adder
4.973
24734805WLF1G4
Adder
4.973
24734905WLF1G5
Adder
4.973
3148133STUARTS
Solar/Wind Helper
0.183
3148013FISHERV
Solar/Wind Helper
0.175
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CPLELTFEXP_CPLE->PJM
CLTF
3.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
TVALTFEXP_TVA->PJM
CLTF
6.026
MECLTFEXP_MEC->PJM
CLTF
8.168
SIGELTFEXP_SIGE->PJM
CLTF
0.27
NYPJM->LTFIMP_NY
CLTF
2.913
LGEELTFEXP_LGEE->PJM
CLTF
3.585
WECLTFEXP_WEC->PJM
CLTF
1.751
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.87 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4131.96
MW Contribution:
12.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3137383CUSHAW
50/50
0.133
247619Y1-049
50/50
0.037
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
24290705CLAY-2
50/50
0.191
24684605SMG4
50/50
1.709
3152061BATH 6F
50/50
17.174
3152021BATH 2B
50/50
17.126
3151861LOWMORA
50/50
7.039
270205AE1-176
50/50
0.005
24290605CLAY-1
50/50
0.191
24290705CLAY-2
50/50
0.191
24684405SMG2
50/50
1.698
24684505SMG3
50/50
1.037
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
942671AE2-283 GEN
Solar/Wind Harmer
6.661
971277AH1-098 GEN
Solar/Wind Harmer
5.459
270013AE1-250 PV
Solar/Wind Harmer
2.406
24728205BUCHG1
Adder
4.632
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
970913AG2-568 GEN
Solar/Wind Harmer
6.181
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
237061AD1-155 GEN
Solar/Wind Helper
1.565
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
238148AE2-230_GEN2
Solar/Wind Helper
0.403
238149AF1-291A_GEN
Solar/Wind Helper
0.115
24415905BUCK
50/50
0.024
962751AG1-124 GEN
Solar/Wind Harmer
14.722
958121AF2-106 GEN
Solar/Wind Harmer
7.113
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
941801AE2-185 GEN
Solar/Wind Harmer
7.541
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
270016AE1-250 BESS
Solar/Wind Harmer
2.406
960911AF2-382 GEN
Solar/Wind Harmer
7.439
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147983MERCK5
Solar/Wind Helper
0.183
316192AB2-158 GEN
Solar/Wind Helper
1.701
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
270173AC1-122 GEN
Solar/Wind Harmer
2.679
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
3147312GRETNA
Solar/Wind Harmer
-0.004
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
958131AF2-107 GEN
Solar/Wind Harmer
5.401
24728305BUCHG2
Adder
4.632
24735205WLF2G2
Adder
5.477
971687AH1-348 GEN
Solar/Wind Harmer
0.905
971403AH1-188 GEN
Solar/Wind Harmer
12.18
316499AE2-029_GEN
Solar/Wind Helper
1.577
3148013FISHERV
Solar/Wind Helper
0.457
315821AE2-092 GEN
Solar/Wind Helper
2.905
3132273ORANGE
Solar/Wind Helper
0.051
3147666LOUISA
Solar/Wind Helper
0.578
23583801GRNGAP
Solar/Wind Helper
4.13
23546401DTGZ2-030
Solar/Wind Helper
0.075
316095T157 G97
Solar/Wind Helper
1.083
3152031BATH 3C
50/50
17.148
3152051BATH 5E
50/50
17.143
3152011BATH 1A
50/50
17.126
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
3151861LOWMORA
50/50
6.764
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
24684305SMG1
50/50
0.615
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
3148463FAIRFLD
Solar/Wind Harmer
-0.069
971331AH1-145 GEN
Solar/Wind Harmer
13.713
971329AH1-144 GEN
Solar/Wind Harmer
8.759
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
270069AE2-166 C O1
Solar/Wind Harmer
10.973
971313AH1-133 GEN
Solar/Wind Harmer
6.499
24734705WLF1G3
Adder
5.611
24734805WLF1G4
Adder
5.611
24734905WLF1G5
Adder
5.611
24735105WLF2G1
Adder
5.477
3148133STUARTS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.263
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315651AD1-115 GEN
Solar/Wind Helper
0.785
316164AC1-076 GEN
Solar/Wind Helper
1.099
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CPLELTFEXP_CPLE->PJM
CLTF
3.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
TVALTFEXP_TVA->PJM
CLTF
6.787
MECLTFEXP_MEC->PJM
CLTF
9.317
SIGELTFEXP_SIGE->PJM
CLTF
0.308
NYPJM->LTFIMP_NY
CLTF
3.203
LGEELTFEXP_LGEE->PJM
CLTF
4.093
WECLTFEXP_WEC->PJM
CLTF
2.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5360.5
MW Contribution:
0.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
6.183
3151051BRUNSWICKS1
50/50
10.097
3151021BRUNSWICKG1
50/50
4.863
971451AH1-221 GEN
50/50
14.769
3150981CHESPKA
50/50
4.118
3152331SURRY 2
50/50
12.573
940641AE2-051 GEN
Solar/Wind Harmer
41.384
941031AE2-094 GEN
Solar/Wind Harmer
81.975
939411AE1-173 GEN
Solar/Wind Harmer
209.802
970919AG2-571 GEN
Solar/Wind Harmer
12.566
970087AG2-069 GEN
Solar/Wind Harmer
36.656
315773AC2-141 GEN
Solar/Wind Harmer
15.407
944591AF1-124 GEN
Solar/Wind Harmer
163.705
957481AF2-042 GEN
Solar/Wind Harmer
109.611
3146456SLIGO L269
Solar/Wind Harmer
-0.035
319010AE1-072 C
Solar/Wind Harmer
7.065
316375AC2-012 GEN
Solar/Wind Harmer
12.076
316036AC1-147 C
Solar/Wind Harmer
0.94
315244AE2-183_ST
50/50
10.737
963041AG1-153 GEN
50/50
9.846
3151081ELIZAR1
50/50
30.344
3151091ELIZAR2
50/50
29.817
941591AE2-156 GEN
50/50
27.672
315779AE2-040
50/50
4.313
972263AH1-716 GEN
50/50
173.708
970533AG2-339 GEN
Solar/Wind Harmer
29.4
970673AG2-436 GEN
Solar/Wind Harmer
94.298
971967AH1-528 GEN
Solar/Wind Harmer
77.483
970085AG2-068 GEN
Solar/Wind Harmer
24.437
970581AG2-369 GEN
Solar/Wind Harmer
21.016
316316AC1-027 C
Solar/Wind Harmer
1.075
316018AA1-139 ULT2
Solar/Wind Harmer
2.999
957871AF2-081 GEN
Solar/Wind Harmer
17.549
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.933
315814AE2-033 C
Solar/Wind Harmer
32.219
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.306
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316486AD2-202 GEN
Solar/Wind Harmer
0.838
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
316311AC2-079 GEN
Solar/Wind Harmer
16.344
315833AF1-017_GEN
Solar/Wind Harmer
6.147
315732AD1-074 GEN1
Solar/Wind Harmer
6.532
315733AD1-074 GEN2
Solar/Wind Harmer
6.532
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.045
316318V4-068
Solar/Wind Harmer
0.793
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.51
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3151031BRUNSWICKG2
50/50
4.863
3151101ELIZAR3
50/50
30.733
3151161SURRY 1
50/50
10.631
944011AF1-069 GEN
Solar/Wind Harmer
25.685
970917AG2-570 GEN
Solar/Wind Harmer
99.27
944581AF1-123 GEN
Solar/Wind Harmer
163.117
944601AF1-125 GEN
Solar/Wind Harmer
160.572
3142956BIRDNECK
Solar/Wind Harmer
1.884
316017AA1-139 ULT1
Solar/Wind Harmer
2.832
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.054
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.03
316305AF2-043 C
Solar/Wind Harmer
1.042
316246AF1-032 C
Solar/Wind Harmer
0.699
316321Z2-027
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.861
315735AD1-075 GEN1
Solar/Wind Harmer
3.265
3146206CASHIE
Solar/Wind Harmer
-0.032
3156081AA2-088 GEN
Solar/Wind Harmer
10.4
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
3145336SMITFLD
Solar/Wind Harmer
-0.012
966621AG1-532 GEN
Solar/Wind Harmer
0.637
3146263WOODLND
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.519
3145963POPLR C
Solar/Wind Harmer
-0.031
316181AB2-040 GEN
Solar/Wind Harmer
4.336
316317KELFORD C
Solar/Wind Harmer
1.436
3145823KELFORD
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.38
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
970657AG2-426 GEN
Solar/Wind Harmer
6.104
316212AC1-099_GEN
Solar/Wind Harmer
2.626
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315242AE2-183_GT2
50/50
6.183
315241AE2-183_GT1
50/50
6.167
972185AH1-677 GEN
50/50
22.351
3151041BRUNSWICKG3
50/50
4.863
972187AH1-678 GEN
50/50
11.159
3150991CHESPKB
50/50
3.454
3150991CHESPKB
50/50
3.371
970933AG2-581 GEN
Solar/Wind Harmer
37.229
316294AC1-161 GEN
Solar/Wind Harmer
11.907
316185AD1-033 GEN
Solar/Wind Harmer
3.714
3145506HICKORY
Solar/Wind Harmer
-0.14
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.362
316388AE2-253 GEN
Solar/Wind Harmer
2.362
970099AG2-077 GEN
Solar/Wind Harmer
43.844
3137176SLIGO L2192
Solar/Wind Harmer
-0.139
3146456SLIGO L269
Solar/Wind Harmer
4.137
3130086AYDLETT
Solar/Wind Harmer
-0.139
3144356SAPONY
Solar/Wind Harmer
1.211
316315AB2-025 C
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.21
316433W1029_GEN2
Solar/Wind Harmer
6.21
316435W1029_GEN3
Solar/Wind Harmer
6.21
3145746EVERETS
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
10.534
3144216WINCHST
Adder
0.991
3150921YORKTN3
Adder
6.598
3151171GRAVELC
Adder
3.65
316420AA1-050 GEN
Solar/Wind Harmer
3.317
3146233WITAKRS
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.031
316236AE1-162_GEN
Solar/Wind Harmer
0.947
946281AF1-292 GEN
Solar/Wind Harmer
0.703
3146043SEABORD
Solar/Wind Harmer
-0.031
971445AH1-216 GEN
Solar/Wind Harmer
19.36
315652AC1-086 GEN
Solar/Wind Harmer
35.113
3137643SOCKMAN
Solar/Wind Harmer
-0.123
316426AA2-053 GEN
Solar/Wind Harmer
3.12
316174AB2-169 GEN
Solar/Wind Harmer
4.766
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970657AG2-426 GEN
Solar/Wind Harmer
1.905
316210AC1-098 GEN
Solar/Wind Harmer
4.726
316274AC1-208 GEN
Solar/Wind Harmer
3.228
970831AG2-522 GEN
Solar/Wind Harmer
14.906
3143316POE
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.958
3151201GRAVEL4
Adder
18.995
3151221GRAVEL6
Adder
18.973
3151191GRAVEL3
Adder
18.755
3151211GRAVEL5
Adder
18.755
957861AF2-080 GEN
Solar/Wind Harmer
12.812
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
316238AB2-078_GEN
Solar/Wind Harmer
0.822
316239AB2-077_GEN
Solar/Wind Harmer
0.822
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
316382AG1-145 C
Solar/Wind Harmer
0.793
316159AE1-175 C
Solar/Wind Harmer
0.706
315697AD1-025 GEN
Solar/Wind Harmer
5.193
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.855
315611Z1-036_GEN2
Solar/Wind Harmer
8.306
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.674
315816AE2-034 GEN
Solar/Wind Harmer
2.655
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.849
315693AD1-088 GEN
Solar/Wind Harmer
16.299
315737AD1-076 GEN
Solar/Wind Harmer
6.141
316023GEN1_S
Solar/Wind Harmer
2.176
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.026
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.944
3156021HOLLOMANSOL
Solar/Wind Harmer
4.262
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145336SMITFLD
Solar/Wind Harmer
-0.125
960081AF2-299 GEN
Solar/Wind Harmer
3.532
3146263WOODLND
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.153
316087AB2-174 GEN
Solar/Wind Harmer
4.445
3145963POPLR C
Solar/Wind Harmer
-0.031
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3147043LAWRENC
Adder
2.427
3146293MARTNCO
Solar/Wind Harmer
0.186
316381AD1-082 GEN
Solar/Wind Harmer
2.739
316129AC1-054 GEN
Solar/Wind Harmer
2.594
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
971065AG2-659 GEN
Solar/Wind Harmer
14.783
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3151171GRAVELC
Adder
2.776
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316319Z2-044 C
Solar/Wind Harmer
1.6
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
316359AB2-059 GEN
Solar/Wind Harmer
3.844
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3142053HEARTS
Solar/Wind Harmer
0.336
971317AH1-138 GEN
Solar/Wind Harmer
3.512
961611AG1-000B GEN
Solar/Wind Harmer
13.784
316131AB2-060 GEN
Solar/Wind Harmer
2.915
970401AG2-262 GEN
Solar/Wind Harmer
1.76
316369SG1_INVT
Solar/Wind Harmer
4.589
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3138543CONSLDL
Solar/Wind Harmer
-0.019
961601AG1-000A GEN
Solar/Wind Harmer
11.385
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
315813AE1-149 C
Solar/Wind Harmer
17.763
961611AG1-000B GEN
Solar/Wind Harmer
5.881
964241AG1-285 GEN
Solar/Wind Harmer
20.609
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.237
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
7.847
315614AA2-178 GEN
Solar/Wind Harmer
3.54
316349AD2-085 GEN
Solar/Wind Harmer
2.874
316365GEN2_N
Solar/Wind Harmer
2.176
316065AD1-022 GEN
Solar/Wind Harmer
16.1
3145893MURPHYS
Solar/Wind Harmer
0.888
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316140AB2-099
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
962571AG1-106 GEN
Solar/Wind Harmer
4.487
313506AB2-031 GEN
Solar/Wind Harmer
2.496
315687AD1-152 GEN
Solar/Wind Harmer
3.719
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
0.256
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.646
3145783HORNRTN
Solar/Wind Harmer
2.917
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
316083AB2-161 GEN
Solar/Wind Harmer
4.858
316005AA1-067
Solar/Wind Harmer
0.598
315724AD1-057 GEN
Solar/Wind Harmer
5.794
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
961601AG1-000A GEN
Solar/Wind Harmer
11.242
316049AB1-081 GEN
Solar/Wind Harmer
3.076
316263AC1-034 GEN
Solar/Wind Harmer
13.4
316237AB2-079_GEN
Solar/Wind Harmer
0.822
313527AB2-043 GEN
Solar/Wind Harmer
4.426
962561AG1-105 GEN
Solar/Wind Harmer
15.191
964791AG1-342 GEN
Solar/Wind Harmer
5.759
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
316118AC1-105 GEN
Solar/Wind Harmer
1.842
316248AF1-058 C
Solar/Wind Harmer
0.804
316033AB2-134 GEN
Solar/Wind Harmer
8.285
315785AD2-033 C
Solar/Wind Harmer
5.703
971069AG2-661 GEN
Solar/Wind Harmer
3.933
316034AC1-036 C
Solar/Wind Harmer
0.458
316132AB2-190 GEN1
Solar/Wind Harmer
2.38
970685AG2-442 GEN
Solar/Wind Harmer
20.273
970323AG2-213 GEN
Solar/Wind Harmer
12.383
970301AG2-198 GEN
Solar/Wind Harmer
11.948
958211AF2-115 GEN
Solar/Wind Harmer
3.532
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316156AD2-030 GEN
Solar/Wind Harmer
0.57
315666AE1-190 GEN
Solar/Wind Harmer
0.633
316240AF1-291 C
Solar/Wind Harmer
0.633
316441AF1-014 GEN
Solar/Wind Harmer
1.403
944641AF1-129 GEN
Adder
84.677
315976AC1-164 GENA
Solar/Wind Harmer
4.487
316169AC1-164_GENC
Solar/Wind Harmer
3.877
942751AE2-291 GEN
Solar/Wind Harmer
11.926
316487AF1-042 GEN
Solar/Wind Harmer
2.436
3142946ENON
Solar/Wind Harmer
-0.002
3150341NORNECKC1
Adder
1.498
3150341NORNECKC1
Adder
1.486
316045AC1-158 PL2
Solar/Wind Helper
5.186
316450AC1-158 RIC
Solar/Wind Helper
0.432
316003AC1-222 GEN
Solar/Wind Harmer
2.469
316222AC1-221 GEN
Solar/Wind Harmer
2.522
316283AC2-100 C
Solar/Wind Harmer
2.342
315778AD1-151 GEN
Solar/Wind Harmer
22.124
970257AG2-171 GEN
Solar/Wind Harmer
9.287
971775AH1-396 GEN
Solar/Wind Harmer
1.747
959311AF2-222 GEN
Solar/Wind Harmer
25.516
971683AH1-343 GEN
Solar/Wind Harmer
10.245
316458AB2-190 GEN2
Solar/Wind Harmer
2.38
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
-0.068
3141873WAN 176
Solar/Wind Harmer
2.539
970133AG2-095 GEN
Solar/Wind Harmer
2.4
3141766HARMONY
Solar/Wind Harmer
1.858
316203AE2-005 GEN
Solar/Wind Harmer
8.774
3141843SHACKLE
Adder
0.946
316123AC1-075 GEN
Solar/Wind Harmer
2.187
942461AE2-259 GEN
Solar/Wind Harmer
2.975
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
316484AD2-074 GEN
Solar/Wind Harmer
4.655
961951AG1-038 GEN
Solar/Wind Harmer
2.436
3142946ENON
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Harmer
-0.01
316075AC2-137 C
Solar/Wind Harmer
0.449
316077AC2-138 C
Solar/Wind Harmer
0.338
3150351NORNECKC2
Adder
1.45
3147666LOUISA
Solar/Wind Helper
0.579
971563AH1-280 GEN
Solar/Wind Harmer
2.825
3144293JTRSVLE
Adder
0.48
3144293JTRSVLE
Adder
0.379
315671AE2-027_GEN
Solar/Wind Harmer
4.072
315662AE1-191 GEN
Solar/Wind Harmer
2.532
316280AD1-041 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.428
316314AB2-024 C
Solar/Wind Harmer
1.757
3138133OCRAN
Solar/Wind Harmer
-0.012
315975AC1-164 GENB
Solar/Wind Harmer
0.133
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
962861AG1-135 GEN
Solar/Wind Harmer
6.696
316404AE1-155 C
Solar/Wind Harmer
3.365
958261AF2-120 GEN
Solar/Wind Harmer
6.831
3146926FARMVIL
Solar/Wind Harmer
-0.01
944631AF1-128 GEN
Adder
73.86
964211AG1-282 GEN
Solar/Wind Harmer
0.495
3141726DUNNSVL
Solar/Wind Harmer
-0.066
3150351NORNECKC2
Adder
1.427
316447AC1-158 HLD
Solar/Wind Helper
3.566
316044AC1-158 PL1
Solar/Wind Helper
1.62
3147666LOUISA
Solar/Wind Helper
1.007
316192AB2-158 GEN
Solar/Wind Helper
1.672
970223AG2-152 GEN
Solar/Wind Harmer
14.028
957831AF2-077 GEN
Solar/Wind Harmer
0.771
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3144303KENBRDG
Solar/Wind Harmer
-0.02
315839AE2-212 C
Solar/Wind Harmer
0.731
970683AG2-441 GEN
Solar/Wind Harmer
16.704
970681AG2-440 GEN
Solar/Wind Harmer
11.087
946301AF1-294 GEN
Solar/Wind Harmer
5.792
961791AG1-021 GEN
Solar/Wind Harmer
2.825
270455AD2-022 GEN
Solar/Wind Harmer
3.829
270457AD2-023 GEN
Solar/Wind Harmer
1.942
957601AF2-054 GEN
Solar/Wind Harmer
0.64
3141873WAN 176
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.471
3141913WHIT STONE
Solar/Wind Harmer
-0.021
3138133OCRAN
Solar/Wind Harmer
-0.006
3143873LANEXA
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
3141813NORNECK
Solar/Wind Harmer
-0.016
316164AC1-076 GEN
Solar/Wind Helper
1.175
315651AD1-115 GEN
Solar/Wind Helper
0.76
LAGNLTFEXP_LAGN->PJM
CLTF
11.549
CPLELTFEXP_CPLE->PJM
CLTF
17.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.65
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.267
TVALTFEXP_TVA->PJM
CLTF
5.777
MECLTFEXP_MEC->PJM
CLTF
5.447
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
2.971
LGEELTFEXP_LGEE->PJM
CLTF
1.957
WECLTFEXP_WEC->PJM
CLTF
1
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 14.03 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.25 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3936.62
MW Contribution:
9.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.738
3151051BRUNSWICKS1
50/50
9.356
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.686
3151531CLOVER1
50/50
5.728
3151591KERR 2
50/50
0.451
3151641KERR 7
50/50
0.451
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.581
3151411GASTONB
50/50
0.581
3151281ROARAP4
50/50
0.256
941031AE2-094 GEN
Solar/Wind Harmer
76.317
970919AG2-571 GEN
Solar/Wind Harmer
11.598
970087AG2-069 GEN
Solar/Wind Harmer
33.781
939411AE1-173 GEN
Solar/Wind Harmer
170.076
957481AF2-042 GEN
Solar/Wind Harmer
99.849
315693AD1-088 GEN
Solar/Wind Harmer
14.725
316023GEN1_S
Solar/Wind Harmer
1.755
960081AF2-299 GEN
Solar/Wind Harmer
2.852
316087AB2-174 GEN
Solar/Wind Harmer
3.548
971065AG2-659 GEN
Solar/Wind Harmer
12.304
316129AC1-054 GEN
Solar/Wind Harmer
2.147
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
970401AG2-262 GEN
Solar/Wind Harmer
1.534
315607AA1-063A GEN
Solar/Wind Harmer
2.364
316131AB2-060 GEN
Solar/Wind Harmer
2.501
3146263WOODLND
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.268
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.074
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.671
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.415
3156021HOLLOMANSOL
Solar/Wind Harmer
3
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.485
315244AE2-183_ST
50/50
9.965
963041AG1-153 GEN
50/50
9.124
3151541CLOVER2
50/50
5.684
315779AE2-040
50/50
3.625
3151601KERR 3
50/50
0.451
3151611KERR 4
50/50
0.451
3151621KERR 5
50/50
0.451
3151631KERR 6
50/50
0.451
3151281ROARAP4
50/50
0.239
970533AG2-339 GEN
Solar/Wind Harmer
27.371
970673AG2-436 GEN
Solar/Wind Harmer
87.683
971967AH1-528 GEN
Solar/Wind Harmer
71.754
970085AG2-068 GEN
Solar/Wind Harmer
22.521
970581AG2-369 GEN
Solar/Wind Harmer
19.368
316486AD2-202 GEN
Solar/Wind Harmer
0.758
315814AE2-033 C
Solar/Wind Harmer
27.024
946281AF1-292 GEN
Solar/Wind Harmer
0.568
970831AG2-522 GEN
Solar/Wind Harmer
12.249
315652AC1-086 GEN
Solar/Wind Harmer
27.486
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
2.395
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.706
316239AB2-077_GEN
Solar/Wind Harmer
0.706
3146043SEABORD
Solar/Wind Harmer
-0.023
316274AC1-208 GEN
Solar/Wind Harmer
2.508
316210AC1-098 GEN
Solar/Wind Harmer
3.62
316327AA2-057 GEN
Solar/Wind Harmer
2.324
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.365
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
957861AF2-080 GEN
Solar/Wind Harmer
9.818
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316174AB2-169 GEN
Solar/Wind Harmer
3.38
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.598
315732AD1-074 GEN1
Solar/Wind Harmer
4.372
315733AD1-074 GEN2
Solar/Wind Harmer
4.372
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.175
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.943
3151391GASTONA
50/50
0.581
3151411GASTONB
50/50
0.581
3151261ROARAP2
50/50
0.263
944011AF1-069 GEN
Solar/Wind Harmer
23.913
970917AG2-570 GEN
Solar/Wind Harmer
91.621
316478AD1-087 GEN
Solar/Wind Harmer
2.589
966621AG1-532 GEN
Solar/Wind Harmer
0.514
3147043LAWRENC
Solar/Wind Harmer
-0.015
316181AB2-040 GEN
Solar/Wind Harmer
3.443
316011AB1-132 GEN
Solar/Wind Harmer
5.103
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
315722AD1-056 GEN
Solar/Wind Harmer
8.354
316212AC1-099_GEN
Solar/Wind Harmer
2.011
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.099
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.054
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
964241AG1-285 GEN
Solar/Wind Harmer
17.656
3146173TUNIS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.569
3156081AA2-088 GEN
Solar/Wind Harmer
7.303
316003AC1-222 GEN
Solar/Wind Harmer
2.171
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.21
316283AC2-100 C
Solar/Wind Harmer
2.052
315735AD1-075 GEN1
Solar/Wind Harmer
2.185
3145273HOLLAND
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
7.926
971775AH1-396 GEN
Solar/Wind Harmer
1.491
3146376EDENTON
Solar/Wind Harmer
-0.021
959311AF2-222 GEN
Solar/Wind Harmer
21.758
971683AH1-343 GEN
Solar/Wind Harmer
8.98
3146626S HERTFORD
Solar/Wind Harmer
-0.021
315242AE2-183_GT2
50/50
5.738
315241AE2-183_GT1
50/50
5.723
972185AH1-677 GEN
50/50
20.743
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.341
3151581KERR 1
50/50
0.161
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.824
3151261ROARAP2
50/50
0.257
3152661PLYWOOD A
50/50
0.467
970933AG2-581 GEN
Solar/Wind Harmer
34.354
970099AG2-077 GEN
Solar/Wind Harmer
39.94
3144356SAPONY
Solar/Wind Harmer
1.018
316315AB2-025 C
Solar/Wind Harmer
0.785
315687AD1-152 GEN
Solar/Wind Harmer
3.341
316365GEN2_N
Solar/Wind Harmer
1.755
313506AB2-031 GEN
Solar/Wind Harmer
1.982
962571AG1-106 GEN
Solar/Wind Harmer
3.512
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.838
3145783HORNRTN
Solar/Wind Harmer
2.271
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316248AF1-058 C
Solar/Wind Harmer
0.709
316118AC1-105 GEN
Solar/Wind Harmer
1.614
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.02
962561AG1-105 GEN
Solar/Wind Harmer
13.21
316237AB2-079_GEN
Solar/Wind Harmer
0.706
315724AD1-057 GEN
Solar/Wind Harmer
4.595
313527AB2-043 GEN
Solar/Wind Harmer
3.8
961601AG1-000A GEN
Solar/Wind Harmer
8.985
316049AB1-081 GEN
Solar/Wind Harmer
2.459
316263AC1-034 GEN
Solar/Wind Harmer
10.714
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316140AB2-099
Solar/Wind Harmer
0.152
316005AA1-067
Solar/Wind Harmer
0.448
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316065AD1-022 GEN
Solar/Wind Harmer
10.919
315742AE1-103 GEN
Solar/Wind Harmer
5.094
315614AA2-178 GEN
Solar/Wind Harmer
2.298
970323AG2-213 GEN
Solar/Wind Harmer
10.568
3145963POPLR C
Solar/Wind Harmer
-0.022
315737AD1-076 GEN
Solar/Wind Harmer
4.11
315785AD2-033 C
Solar/Wind Harmer
4.872
315816AE2-034 GEN
Solar/Wind Harmer
1.724
3145663CRESWEL
Solar/Wind Harmer
-0.059
971163AH1-040 GEN
Solar/Wind Harmer
20.027
316034AC1-036 C
Solar/Wind Harmer
0.391
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.175
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.986
319010AE1-072 C
Solar/Wind Harmer
4.05
3146456SLIGO L269
Solar/Wind Harmer
-0.02
944591AF1-124 GEN
Solar/Wind Harmer
90.901
316381AD1-082 GEN
Solar/Wind Harmer
1.81
970685AG2-442 GEN
Solar/Wind Harmer
17.226
316375AC2-012 GEN
Solar/Wind Harmer
6.712
316036AC1-147 C
Solar/Wind Harmer
0.522
3150981CHESPKA
Adder
2.157
971563AH1-280 GEN
Solar/Wind Harmer
2.397
3144293JTRSVLE
Adder
0.407
3144293JTRSVLE
Adder
0.322
316072AD1-144
Solar/Wind Harmer
0.385
3145336SMITFLD
Solar/Wind Harmer
-0.067
940641AE2-051 GEN
Solar/Wind Harmer
15.103
315773AC2-141 GEN
Solar/Wind Harmer
6.726
3151171GRAVELC
Adder
1.46
961611AG1-000B GEN
Solar/Wind Harmer
7.215
3146926FARMVIL
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
2.607
970223AG2-152 GEN
Solar/Wind Harmer
12.105
316369SG1_INVT
Solar/Wind Harmer
2.382
3138126ROCKLANDING
Solar/Wind Harmer
0.04
270016AE1-250 BESS
Solar/Wind Harmer
1.997
971069AG2-661 GEN
Solar/Wind Harmer
2.034
3143226MDLTHAN
Solar/Wind Helper
0.294
316447AC1-158 HLD
Solar/Wind Helper
2.855
316044AC1-158 PL1
Solar/Wind Helper
1.297
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.43
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.731
316433W1029_GEN2
Solar/Wind Harmer
3.731
316435W1029_GEN3
Solar/Wind Harmer
3.731
315835AF2-110_GEN
Solar/Wind Harmer
2.573
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316349AD2-085 GEN
Solar/Wind Harmer
1.8
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.367
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316339AD2-160 GEN
Solar/Wind Harmer
1.343
316388AE2-253 GEN
Solar/Wind Harmer
1.343
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
316185AD1-033 GEN
Solar/Wind Harmer
2.085
316083AB2-161 GEN
Solar/Wind Harmer
3.21
3150991CHESPKB
Adder
1.809
3150991CHESPKB
Adder
1.766
958211AF2-115 GEN
Solar/Wind Harmer
2.996
3144293JTRSVLE
Adder
0.407
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
942751AE2-291 GEN
Solar/Wind Harmer
10.315
316294AC1-161 GEN
Solar/Wind Harmer
5.198
316033AB2-134 GEN
Solar/Wind Harmer
4.3
316240AF1-291 C
Solar/Wind Harmer
0.391
270013AE1-250 PV
Solar/Wind Harmer
1.997
316045AC1-158 PL2
Solar/Wind Helper
4.151
316450AC1-158 RIC
Solar/Wind Helper
0.346
3146516WINFALL
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.617
316246AF1-032 C
Solar/Wind Harmer
0.414
316321Z2-027
Solar/Wind Harmer
0.549
316320Y1-086
Solar/Wind Harmer
1.188
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.319
316017AA1-139 ULT1
Solar/Wind Harmer
1.614
944581AF1-123 GEN
Solar/Wind Harmer
90.575
944601AF1-125 GEN
Solar/Wind Harmer
89.161
970657AG2-426 GEN
Solar/Wind Harmer
4.009
3142956BIRDNECK
Solar/Wind Harmer
1.055
315813AE1-149 C
Solar/Wind Harmer
12.179
3151101ELIZAR3
Adder
16.086
3144873MCLAUGH
Solar/Wind Harmer
0
3144293JTRSVLE
Adder
0.407
3144536CHRHLND
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
-0.058
316123AC1-075 GEN
Solar/Wind Harmer
1.901
3145336SMITFLD
Solar/Wind Harmer
-0.007
942461AE2-259 GEN
Solar/Wind Harmer
2.499
3151171GRAVELC
Adder
1.92
961611AG1-000B GEN
Solar/Wind Harmer
3.078
3146926FARMVIL
Solar/Wind Harmer
-0.009
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.875
315778AD1-151 GEN
Solar/Wind Harmer
11.439
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.546
316311AC2-079 GEN
Solar/Wind Harmer
10.232
315833AF1-017_GEN
Solar/Wind Harmer
3.851
970683AG2-441 GEN
Solar/Wind Harmer
14.214
970681AG2-440 GEN
Solar/Wind Harmer
9.434
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316018AA1-139 ULT2
Solar/Wind Harmer
1.709
957871AF2-081 GEN
Solar/Wind Harmer
10
970657AG2-426 GEN
Solar/Wind Harmer
1.251
316316AC1-027 C
Solar/Wind Harmer
0.602
3151081ELIZAR1
Adder
15.883
3151091ELIZAR2
Adder
15.607
946301AF1-294 GEN
Solar/Wind Harmer
4.913
961791AG1-021 GEN
Solar/Wind Harmer
2.397
270455AD2-022 GEN
Solar/Wind Harmer
3.324
270457AD2-023 GEN
Solar/Wind Harmer
1.685
316236AE1-162_GEN
Solar/Wind Harmer
0.509
315839AE2-212 C
Solar/Wind Harmer
0.508
971445AH1-216 GEN
Solar/Wind Harmer
10.396
3151201GRAVEL4
Adder
9.989
3151221GRAVEL6
Adder
9.978
3151191GRAVEL3
Adder
9.863
3151211GRAVEL5
Adder
9.863
315697AD1-025 GEN
Solar/Wind Harmer
2.695
LAGNLTFEXP_LAGN->PJM
CLTF
9.955
CPLELTFEXP_CPLE->PJM
CLTF
14.693
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.381
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.635
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.964
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.019
TVALTFEXP_TVA->PJM
CLTF
4.97
MECLTFEXP_MEC->PJM
CLTF
4.722
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.225
LGEELTFEXP_LGEE->PJM
CLTF
1.689
WECLTFEXP_WEC->PJM
CLTF
0.871
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 12.11 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4947.42
MW Contribution:
1.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.791
3151051BRUNSWICKS1
50/50
9.458
3151021BRUNSWICKG1
50/50
4.556
971451AH1-221 GEN
50/50
13.835
3151531CLOVER1
50/50
5.939
941031AE2-094 GEN
Solar/Wind Harmer
76.763
940641AE2-051 GEN
Solar/Wind Harmer
38.301
939411AE1-173 GEN
Solar/Wind Harmer
192.035
970919AG2-571 GEN
Solar/Wind Harmer
11.774
970087AG2-069 GEN
Solar/Wind Harmer
34.349
957481AF2-042 GEN
Solar/Wind Harmer
102.804
315773AC2-141 GEN
Solar/Wind Harmer
13.355
944591AF1-124 GEN
Solar/Wind Harmer
143.497
3146456SLIGO L269
Solar/Wind Harmer
-0.031
319010AE1-072 C
Solar/Wind Harmer
6.213
316375AC2-012 GEN
Solar/Wind Harmer
10.589
316036AC1-147 C
Solar/Wind Harmer
0.824
3150981CHESPKA
Adder
3.403
315693AD1-088 GEN
Solar/Wind Harmer
15.295
3146516WINFALL
Solar/Wind Harmer
-0.097
3146516WINFALL
Solar/Wind Harmer
-0.03
316093AE2-104_GEN
Solar/Wind Harmer
8.721
316023GEN1_S
Solar/Wind Harmer
2.012
315611Z1-036_GEN2
Solar/Wind Harmer
7.379
3130156CHOWAN
Solar/Wind Harmer
-0.03
315816AE2-034 GEN
Solar/Wind Harmer
2.373
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.566
316072AD1-144
Solar/Wind Harmer
0.591
315737AD1-076 GEN
Solar/Wind Harmer
5.512
960081AF2-299 GEN
Solar/Wind Harmer
3.267
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.226
316087AB2-174 GEN
Solar/Wind Harmer
4.104
3145893MURPHYS
Solar/Wind Harmer
-0.115
3145893MURPHYS
Solar/Wind Harmer
0.855
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.855
315607AA1-063A GEN
Solar/Wind Harmer
2.88
3145683EARLEYS
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Adder
2.253
3145336SMITFLD
Solar/Wind Harmer
-0.11
316129AC1-054 GEN
Solar/Wind Harmer
2.409
971065AG2-659 GEN
Solar/Wind Harmer
13.741
3146293MARTNCO
Solar/Wind Harmer
0.17
316381AD1-082 GEN
Solar/Wind Harmer
2.479
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316494AC1-189 GEN
Solar/Wind Harmer
2.892
316319Z2-044 C
Solar/Wind Harmer
1.477
3146233WITAKRS
Solar/Wind Harmer
-0.106
961671AG1-007 GEN
Solar/Wind Harmer
0.337
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
316359AB2-059 GEN
Solar/Wind Harmer
3.554
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3142053HEARTS
Solar/Wind Harmer
0.311
3151171GRAVELC
Adder
2.429
316131AB2-060 GEN
Solar/Wind Harmer
2.73
970401AG2-262 GEN
Solar/Wind Harmer
1.653
3138126ROCKLANDING
Solar/Wind Harmer
0.076
961611AG1-000B GEN
Solar/Wind Harmer
12.1
315785AD2-033 C
Solar/Wind Harmer
5.35
971317AH1-138 GEN
Solar/Wind Harmer
2.928
315244AE2-183_ST
50/50
10.057
963041AG1-153 GEN
50/50
9.223
315779AE2-040
50/50
4.016
3151541CLOVER2
50/50
5.893
3151081ELIZAR1
50/50
26.605
970533AG2-339 GEN
Solar/Wind Harmer
27.531
970673AG2-436 GEN
Solar/Wind Harmer
88.311
971967AH1-528 GEN
Solar/Wind Harmer
72.584
970085AG2-068 GEN
Solar/Wind Harmer
22.899
970581AG2-369 GEN
Solar/Wind Harmer
19.693
315814AE2-033 C
Solar/Wind Harmer
29.988
316486AD2-202 GEN
Solar/Wind Harmer
0.786
316018AA1-139 ULT2
Solar/Wind Harmer
2.636
957871AF2-081 GEN
Solar/Wind Harmer
15.423
316316AC1-027 C
Solar/Wind Harmer
0.943
3146406KITTY HAWK
Solar/Wind Harmer
0.026
3151091ELIZAR2
Adder
24.637
313526AB2-022
Solar/Wind Harmer
0.822
3146396TANGLEW
Solar/Wind Harmer
0.56
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315800Z1-036_GEN1
Solar/Wind Harmer
7.379
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.864
315733AD1-074 GEN2
Solar/Wind Harmer
5.864
946281AF1-292 GEN
Solar/Wind Harmer
0.65
3146206CASHIE
Solar/Wind Harmer
-0.029
316311AC2-079 GEN
Solar/Wind Harmer
14.578
970601AG2-382 GEN
Solar/Wind Harmer
12.646
315833AF1-017_GEN
Solar/Wind Harmer
5.484
316318V4-068
Solar/Wind Harmer
0.718
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.315
316463AE2-346 GEN
Solar/Wind Harmer
0.462
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
-0.029
3146043SEABORD
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.113
316426AA2-053 GEN
Solar/Wind Harmer
2.862
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
4.318
3146033SCOT NK
Solar/Wind Harmer
-0.111
316210AC1-098 GEN
Solar/Wind Harmer
4.335
970831AG2-522 GEN
Solar/Wind Harmer
13.825
3143316POE
Solar/Wind Harmer
-0.109
316274AC1-208 GEN
Solar/Wind Harmer
2.968
316236AE1-162_GEN
Solar/Wind Harmer
0.829
971445AH1-216 GEN
Solar/Wind Harmer
16.953
970657AG2-426 GEN
Solar/Wind Harmer
1.721
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.726
957861AF2-080 GEN
Solar/Wind Harmer
11.759
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
3151201GRAVEL4
Adder
16.621
3151221GRAVEL6
Adder
16.602
3151191GRAVEL3
Adder
16.411
3151211GRAVEL5
Adder
16.411
316238AB2-078_GEN
Solar/Wind Harmer
0.77
316239AB2-077_GEN
Solar/Wind Harmer
0.77
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.019
3151031BRUNSWICKG2
50/50
4.556
970413AG2-270 GEN
50/50
25.863
3151101ELIZAR3
50/50
26.945
944011AF1-069 GEN
Solar/Wind Harmer
24.052
970917AG2-570 GEN
Solar/Wind Harmer
93.014
944581AF1-123 GEN
Solar/Wind Harmer
142.982
944601AF1-125 GEN
Solar/Wind Harmer
140.751
316478AD1-087 GEN
Solar/Wind Harmer
2.685
316017AA1-139 ULT1
Solar/Wind Harmer
2.489
3142956BIRDNECK
Solar/Wind Harmer
1.653
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.564
315242AE2-183_GT2
50/50
5.791
315241AE2-183_GT1
50/50
5.776
972185AH1-677 GEN
50/50
20.935
3151041BRUNSWICKG3
50/50
4.556
972187AH1-678 GEN
50/50
10.453
970933AG2-581 GEN
Solar/Wind Harmer
34.884
970099AG2-077 GEN
Solar/Wind Harmer
41.122
3144356SAPONY
Solar/Wind Harmer
1.127
316315AB2-025 C
Solar/Wind Harmer
0.87
316294AC1-161 GEN
Solar/Wind Harmer
10.322
316185AD1-033 GEN
Solar/Wind Harmer
3.259
3145506HICKORY
Solar/Wind Harmer
-0.123
3145506HICKORY
Solar/Wind Harmer
-0.074
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.076
316388AE2-253 GEN
Solar/Wind Harmer
2.076
3137176SLIGO L2192
Solar/Wind Harmer
-0.122
3146456SLIGO L269
Solar/Wind Harmer
3.637
3130086AYDLETT
Solar/Wind Harmer
-0.122
3150991CHESPKB
Adder
2.854
3150991CHESPKB
Adder
2.786
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.488
316433W1029_GEN2
Solar/Wind Harmer
5.488
316435W1029_GEN3
Solar/Wind Harmer
5.488
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
315835AF2-110_GEN
Solar/Wind Harmer
3.749
316365GEN2_N
Solar/Wind Harmer
2.012
3146376EDENTON
Solar/Wind Harmer
0.884
3146376EDENTON
Solar/Wind Harmer
0.884
315742AE1-103 GEN
Solar/Wind Harmer
7.01
315614AA2-178 GEN
Solar/Wind Harmer
3.164
315687AD1-152 GEN
Solar/Wind Harmer
3.493
316065AD1-022 GEN
Solar/Wind Harmer
14.48
316349AD2-085 GEN
Solar/Wind Harmer
2.564
3145893MURPHYS
Solar/Wind Harmer
0.804
3145893MURPHYS
Solar/Wind Harmer
-0.052
313506AB2-031 GEN
Solar/Wind Harmer
2.303
962571AG1-106 GEN
Solar/Wind Harmer
4.129
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316140AB2-099
Solar/Wind Harmer
0.193
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.352
3145783HORNRTN
Solar/Wind Harmer
2.682
3145783HORNRTN
Solar/Wind Harmer
0.838
3145783HORNRTN
Solar/Wind Harmer
0.335
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.027
315724AD1-057 GEN
Solar/Wind Harmer
5.347
316083AB2-161 GEN
Solar/Wind Harmer
4.397
316005AA1-067
Solar/Wind Harmer
0.547
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.394
316049AB1-081 GEN
Solar/Wind Harmer
2.844
316263AC1-034 GEN
Solar/Wind Harmer
12.39
316237AB2-079_GEN
Solar/Wind Harmer
0.77
313527AB2-043 GEN
Solar/Wind Harmer
4.145
962561AG1-105 GEN
Solar/Wind Harmer
14.266
964791AG1-342 GEN
Solar/Wind Harmer
5.411
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
316118AC1-105 GEN
Solar/Wind Harmer
1.732
316248AF1-058 C
Solar/Wind Harmer
0.757
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.79
316305AF2-043 C
Solar/Wind Harmer
0.918
316246AF1-032 C
Solar/Wind Harmer
0.616
316321Z2-027
Solar/Wind Harmer
0.819
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
-0.03
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315735AD1-075 GEN1
Solar/Wind Harmer
2.931
966621AG1-532 GEN
Solar/Wind Harmer
0.589
3156081AA2-088 GEN
Solar/Wind Harmer
9.401
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
4
316011AB1-132 GEN
Solar/Wind Harmer
5.999
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.348
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.308
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
2.408
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
315722AD1-056 GEN
Solar/Wind Harmer
9.722
970657AG2-426 GEN
Solar/Wind Harmer
5.515
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316420AA1-050 GEN
Solar/Wind Harmer
3.049
3146233WITAKRS
Solar/Wind Harmer
0.56
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.018
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
961601AG1-000A GEN
Solar/Wind Harmer
10.526
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
16.242
3151171GRAVELC
Adder
3.194
3144216WINCHST
Adder
0.838
3150921YORKTN3
Adder
5.554
964241AG1-285 GEN
Solar/Wind Harmer
19.314
961611AG1-000B GEN
Solar/Wind Harmer
5.163
316003AC1-222 GEN
Solar/Wind Harmer
2.331
316222AC1-221 GEN
Solar/Wind Harmer
2.376
316283AC2-100 C
Solar/Wind Harmer
2.207
970323AG2-213 GEN
Solar/Wind Harmer
11.621
316033AB2-134 GEN
Solar/Wind Harmer
7.315
970301AG2-198 GEN
Solar/Wind Harmer
11.258
958211AF2-115 GEN
Solar/Wind Harmer
3.322
3144293JTRSVLE
Adder
0.452
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.016
316240AF1-291 C
Solar/Wind Harmer
0.592
944641AF1-129 GEN
Adder
79.27
942751AE2-291 GEN
Solar/Wind Harmer
11.438
316156AD2-030 GEN
Solar/Wind Harmer
0.468
315666AE1-190 GEN
Solar/Wind Harmer
0.521
316441AF1-014 GEN
Solar/Wind Harmer
1.155
315976AC1-164 GENA
Solar/Wind Harmer
3.576
316169AC1-164_GENC
Solar/Wind Harmer
3.09
3142946ENON
Solar/Wind Harmer
-0.002
316487AF1-042 GEN
Solar/Wind Harmer
1.984
270013AE1-250 PV
Solar/Wind Harmer
2.271
3150341NORNECKC1
Adder
1.208
3150341NORNECKC1
Adder
1.198
316045AC1-158 PL2
Solar/Wind Helper
5.307
316450AC1-158 RIC
Solar/Wind Helper
0.442
316034AC1-036 C
Solar/Wind Harmer
0.43
316369SG1_INVT
Solar/Wind Harmer
4.051
971069AG2-661 GEN
Solar/Wind Harmer
3.482
970685AG2-442 GEN
Solar/Wind Harmer
19.056
971563AH1-280 GEN
Solar/Wind Harmer
2.657
3144293JTRSVLE
Adder
0.452
3144293JTRSVLE
Adder
0.357
316132AB2-190 GEN1
Solar/Wind Harmer
2.116
315671AE2-027_GEN
Solar/Wind Harmer
3.771
315662AE1-191 GEN
Solar/Wind Harmer
2.083
316280AD1-041 GEN
Solar/Wind Harmer
1.302
971777AH1-397 GEN
Solar/Wind Harmer
1.998
3141766HARMONY
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.01
316314AB2-024 C
Solar/Wind Harmer
1.428
3146926FARMVIL
Solar/Wind Harmer
-0.01
3142433PROV 92
Solar/Wind Harmer
-0.064
3142433PROV 92
Adder
0.276
3142433PROV 92
Adder
0.276
315975AC1-164 GENB
Solar/Wind Harmer
0.106
970223AG2-152 GEN
Solar/Wind Harmer
13.67
944631AF1-128 GEN
Adder
63.687
270016AE1-250 BESS
Solar/Wind Harmer
2.271
962861AG1-135 GEN
Solar/Wind Harmer
5.441
316404AE1-155 C
Solar/Wind Harmer
2.731
3150351NORNECKC2
Adder
1.15
316447AC1-158 HLD
Solar/Wind Helper
3.649
316044AC1-158 PL1
Solar/Wind Helper
1.658
3147666LOUISA
Solar/Wind Helper
1.016
316192AB2-158 GEN
Solar/Wind Helper
1.685
958261AF2-120 GEN
Solar/Wind Harmer
2.051
970257AG2-171 GEN
Solar/Wind Harmer
8.716
971775AH1-396 GEN
Solar/Wind Harmer
1.64
959311AF2-222 GEN
Solar/Wind Harmer
23.954
971683AH1-343 GEN
Solar/Wind Harmer
9.7
315778AD1-151 GEN
Solar/Wind Harmer
19.583
3144293JTRSVLE
Adder
0.452
316458AB2-190 GEN2
Solar/Wind Harmer
2.116
3147133PAMPLIN
Solar/Wind Harmer
-0.064
316123AC1-075 GEN
Solar/Wind Harmer
2.088
970133AG2-095 GEN
Solar/Wind Harmer
2.151
942461AE2-259 GEN
Solar/Wind Harmer
2.809
3141873WAN 176
Solar/Wind Harmer
2.087
316203AE2-005 GEN
Solar/Wind Harmer
7.222
3141843SHACKLE
Adder
0.779
3141766HARMONY
Solar/Wind Harmer
1.517
3146926FARMVIL
Solar/Wind Harmer
-0.01
3142433PROV 92
Adder
0.276
3142433PROV 92
Adder
0.276
3142946ENON
Solar/Wind Harmer
-0.005
316484AD2-074 GEN
Solar/Wind Harmer
3.792
961951AG1-038 GEN
Solar/Wind Harmer
1.984
3150351NORNECKC2
Adder
1.169
3147666LOUISA
Solar/Wind Helper
0.584
966661AG1-536 GEN
Solar/Wind Harmer
0
315697AD1-025 GEN
Solar/Wind Harmer
4.585
315839AE2-212 C
Solar/Wind Harmer
0.683
970683AG2-441 GEN
Solar/Wind Harmer
15.694
970681AG2-440 GEN
Solar/Wind Harmer
10.416
316382AG1-145 C
Solar/Wind Harmer
0.656
316159AE1-175 C
Solar/Wind Harmer
0.584
957831AF2-077 GEN
Solar/Wind Harmer
0.643
3138283WHITEMARSH
Solar/Wind Harmer
0.033
946301AF1-294 GEN
Solar/Wind Harmer
5.447
961791AG1-021 GEN
Solar/Wind Harmer
2.657
270455AD2-022 GEN
Solar/Wind Harmer
3.627
270457AD2-023 GEN
Solar/Wind Harmer
1.839
957601AF2-054 GEN
Solar/Wind Harmer
0.526
3141873WAN 176
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.384
3141913WHIT STONE
Solar/Wind Harmer
-0.017
3138133OCRAN
Solar/Wind Harmer
-0.005
3143873LANEXA
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.276
3142433PROV 92
Adder
0.276
316164AC1-076 GEN
Solar/Wind Helper
1.192
315651AD1-115 GEN
Solar/Wind Helper
0.765
LAGNLTFEXP_LAGN->PJM
CLTF
11.294
CPLELTFEXP_CPLE->PJM
CLTF
16.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.829
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.614
TVALTFEXP_TVA->PJM
CLTF
5.659
MECLTFEXP_MEC->PJM
CLTF
5.488
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
2.908
LGEELTFEXP_LGEE->PJM
CLTF
2
WECLTFEXP_WEC->PJM
CLTF
1.023
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 13.67 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4935.86
MW Contribution:
1.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.759
315241AE2-183_GT1
50/50
5.744
972185AH1-677 GEN
50/50
20.819
3151041BRUNSWICKG3
50/50
4.53
972187AH1-678 GEN
50/50
10.395
970933AG2-581 GEN
Solar/Wind Harmer
34.687
970099AG2-077 GEN
Solar/Wind Harmer
40.88
3144356SAPONY
Solar/Wind Harmer
1.115
316315AB2-025 C
Solar/Wind Harmer
0.86
316294AC1-161 GEN
Solar/Wind Harmer
10.262
316185AD1-033 GEN
Solar/Wind Harmer
3.235
3145506HICKORY
Solar/Wind Harmer
-0.122
3145506HICKORY
Solar/Wind Harmer
-0.073
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.06
316388AE2-253 GEN
Solar/Wind Harmer
2.06
3137176SLIGO L2192
Solar/Wind Harmer
-0.121
3146456SLIGO L269
Solar/Wind Harmer
3.61
3130086AYDLETT
Solar/Wind Harmer
-0.122
3150991CHESPKB
Adder
2.832
3150991CHESPKB
Adder
2.764
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.445
316433W1029_GEN2
Solar/Wind Harmer
5.445
316435W1029_GEN3
Solar/Wind Harmer
5.445
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
315835AF2-110_GEN
Solar/Wind Harmer
3.717
316365GEN2_N
Solar/Wind Harmer
1.994
3146376EDENTON
Solar/Wind Harmer
0.877
3146376EDENTON
Solar/Wind Harmer
0.877
315742AE1-103 GEN
Solar/Wind Harmer
6.951
315614AA2-178 GEN
Solar/Wind Harmer
3.139
315687AD1-152 GEN
Solar/Wind Harmer
3.473
316065AD1-022 GEN
Solar/Wind Harmer
14.368
3145893MURPHYS
Solar/Wind Harmer
0.797
3145893MURPHYS
Solar/Wind Harmer
-0.051
316349AD2-085 GEN
Solar/Wind Harmer
2.535
313506AB2-031 GEN
Solar/Wind Harmer
2.283
962571AG1-106 GEN
Solar/Wind Harmer
4.095
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316140AB2-099
Solar/Wind Harmer
0.191
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
3.325
3145783HORNRTN
Solar/Wind Harmer
2.66
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.333
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3151031BRUNSWICKG2
50/50
4.53
970413AG2-270 GEN
50/50
25.71
3151101ELIZAR3
50/50
26.734
944011AF1-069 GEN
Solar/Wind Harmer
23.92
970917AG2-570 GEN
Solar/Wind Harmer
92.502
944581AF1-123 GEN
Solar/Wind Harmer
141.967
944601AF1-125 GEN
Solar/Wind Harmer
139.752
316478AD1-087 GEN
Solar/Wind Harmer
2.669
316017AA1-139 ULT1
Solar/Wind Harmer
2.47
3142956BIRDNECK
Solar/Wind Harmer
1.64
3146456SLIGO L269
Solar/Wind Harmer
-0.03
971153AH1-033 GEN
Solar/Wind Harmer
3.537
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.776
316305AF2-043 C
Solar/Wind Harmer
0.91
316246AF1-032 C
Solar/Wind Harmer
0.611
316321Z2-027
Solar/Wind Harmer
0.813
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
-0.029
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315735AD1-075 GEN1
Solar/Wind Harmer
2.908
966621AG1-532 GEN
Solar/Wind Harmer
0.584
3156081AA2-088 GEN
Solar/Wind Harmer
9.324
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.199
3145893MURPHYS
Solar/Wind Harmer
-0.028
316181AB2-040 GEN
Solar/Wind Harmer
3.966
316011AB1-132 GEN
Solar/Wind Harmer
5.949
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.297
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.016
316212AC1-099_GEN
Solar/Wind Harmer
2.39
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
315722AD1-056 GEN
Solar/Wind Harmer
9.648
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
5.433
316420AA1-050 GEN
Solar/Wind Harmer
3.028
3146233WITAKRS
Solar/Wind Harmer
0.556
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
315724AD1-057 GEN
Solar/Wind Harmer
5.306
316005AA1-067
Solar/Wind Harmer
0.543
316083AB2-161 GEN
Solar/Wind Harmer
4.33
3145493TOT1
Solar/Wind Harmer
0.41
3145453TOT5
Solar/Wind Harmer
0.246
3145603CNETO
Solar/Wind Harmer
0.164
961601AG1-000A GEN
Solar/Wind Harmer
10.321
316049AB1-081 GEN
Solar/Wind Harmer
2.824
316263AC1-034 GEN
Solar/Wind Harmer
12.302
316237AB2-079_GEN
Solar/Wind Harmer
0.764
313527AB2-043 GEN
Solar/Wind Harmer
4.116
962561AG1-105 GEN
Solar/Wind Harmer
14.175
964791AG1-342 GEN
Solar/Wind Harmer
5.377
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
316118AC1-105 GEN
Solar/Wind Harmer
1.722
316248AF1-058 C
Solar/Wind Harmer
0.753
970323AG2-213 GEN
Solar/Wind Harmer
11.533
970301AG2-198 GEN
Solar/Wind Harmer
11.17
316033AB2-134 GEN
Solar/Wind Harmer
7.165
958211AF2-115 GEN
Solar/Wind Harmer
3.295
3144293JTRSVLE
Adder
0.448
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
316240AF1-291 C
Solar/Wind Harmer
0.572
944641AF1-129 GEN
Adder
76.369
942751AE2-291 GEN
Solar/Wind Harmer
11.39
316156AD2-030 GEN
Solar/Wind Harmer
0.456
315666AE1-190 GEN
Solar/Wind Harmer
0.506
316441AF1-014 GEN
Solar/Wind Harmer
1.121
315976AC1-164 GENA
Solar/Wind Harmer
3.462
316169AC1-164_GENC
Solar/Wind Harmer
2.991
270013AE1-250 PV
Solar/Wind Harmer
2.264
3142946ENON
Solar/Wind Harmer
-0.002
316487AF1-042 GEN
Solar/Wind Harmer
1.915
316045AC1-158 PL2
Solar/Wind Helper
5.273
316450AC1-158 RIC
Solar/Wind Helper
0.439
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
961601AG1-000A GEN
Solar/Wind Harmer
10.451
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
15.947
3151171GRAVELC
Adder
3.148
3144216WINCHST
Adder
0.827
964241AG1-285 GEN
Solar/Wind Harmer
19.175
3150921YORKTN3
Adder
5.487
961611AG1-000B GEN
Solar/Wind Harmer
5.077
316003AC1-222 GEN
Solar/Wind Harmer
2.318
316222AC1-221 GEN
Solar/Wind Harmer
2.363
316283AC2-100 C
Solar/Wind Harmer
2.195
970257AG2-171 GEN
Solar/Wind Harmer
8.65
971775AH1-396 GEN
Solar/Wind Harmer
1.627
959311AF2-222 GEN
Solar/Wind Harmer
23.771
971683AH1-343 GEN
Solar/Wind Harmer
9.649
315778AD1-151 GEN
Solar/Wind Harmer
19.146
3144293JTRSVLE
Adder
0.448
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
3147133PAMPLIN
Solar/Wind Harmer
-0.064
316123AC1-075 GEN
Solar/Wind Harmer
2.078
970133AG2-095 GEN
Solar/Wind Harmer
2.084
942461AE2-259 GEN
Solar/Wind Harmer
2.783
3141873WAN 176
Solar/Wind Harmer
2.031
316203AE2-005 GEN
Solar/Wind Harmer
7.015
3141843SHACKLE
Adder
0.756
3141766HARMONY
Solar/Wind Harmer
1.474
3146926FARMVIL
Solar/Wind Harmer
-0.01
3142433PROV 92
Adder
0.266
3142433PROV 92
Adder
0.266
3142946ENON
Solar/Wind Harmer
-0.005
316484AD2-074 GEN
Solar/Wind Harmer
3.659
961951AG1-038 GEN
Solar/Wind Harmer
1.915
3147666LOUISA
Solar/Wind Helper
0.58
966661AG1-536 GEN
Solar/Wind Harmer
0
315243AE2-183_GT3
50/50
5.759
3151051BRUNSWICKS1
50/50
9.406
3151021BRUNSWICKG1
50/50
4.53
971451AH1-221 GEN
50/50
13.758
3151531CLOVER1
50/50
5.904
941031AE2-094 GEN
Solar/Wind Harmer
76.342
940641AE2-051 GEN
Solar/Wind Harmer
38.09
939411AE1-173 GEN
Solar/Wind Harmer
190.903
970919AG2-571 GEN
Solar/Wind Harmer
11.709
970087AG2-069 GEN
Solar/Wind Harmer
34.16
957481AF2-042 GEN
Solar/Wind Harmer
102.2
315773AC2-141 GEN
Solar/Wind Harmer
13.277
944591AF1-124 GEN
Solar/Wind Harmer
142.479
3146456SLIGO L269
Solar/Wind Harmer
-0.03
319010AE1-072 C
Solar/Wind Harmer
6.166
315693AD1-088 GEN
Solar/Wind Harmer
15.201
316375AC2-012 GEN
Solar/Wind Harmer
10.505
316036AC1-147 C
Solar/Wind Harmer
0.817
3150981CHESPKA
Adder
3.376
3146516WINFALL
Solar/Wind Harmer
-0.097
3146516WINFALL
Solar/Wind Harmer
-0.03
316093AE2-104_GEN
Solar/Wind Harmer
8.645
316023GEN1_S
Solar/Wind Harmer
1.994
315611Z1-036_GEN2
Solar/Wind Harmer
7.322
3130156CHOWAN
Solar/Wind Harmer
-0.029
315816AE2-034 GEN
Solar/Wind Harmer
2.355
3145663CRESWEL
Solar/Wind Harmer
-0.081
971163AH1-040 GEN
Solar/Wind Harmer
27.354
316072AD1-144
Solar/Wind Harmer
0.586
315737AD1-076 GEN
Solar/Wind Harmer
5.47
960081AF2-299 GEN
Solar/Wind Harmer
3.239
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.17
3145893MURPHYS
Solar/Wind Harmer
-0.114
3145893MURPHYS
Solar/Wind Harmer
0.848
316087AB2-174 GEN
Solar/Wind Harmer
4.069
3146173TUNIS
Solar/Wind Harmer
-0.028
3156021HOLLOMANSOL
Solar/Wind Harmer
3.825
315607AA1-063A GEN
Solar/Wind Harmer
2.857
3145683EARLEYS
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Adder
2.234
316129AC1-054 GEN
Solar/Wind Harmer
2.392
971065AG2-659 GEN
Solar/Wind Harmer
13.644
3145336SMITFLD
Solar/Wind Harmer
-0.108
3146293MARTNCO
Solar/Wind Harmer
0.169
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316381AD1-082 GEN
Solar/Wind Harmer
2.442
316494AC1-189 GEN
Solar/Wind Harmer
2.871
316319Z2-044 C
Solar/Wind Harmer
1.467
3146233WITAKRS
Solar/Wind Harmer
-0.105
961671AG1-007 GEN
Solar/Wind Harmer
0.335
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.786
316359AB2-059 GEN
Solar/Wind Harmer
3.529
3142053HEARTS
Solar/Wind Harmer
0.308
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3151171GRAVELC
Adder
2.394
316131AB2-060 GEN
Solar/Wind Harmer
2.711
970401AG2-262 GEN
Solar/Wind Harmer
1.643
3138126ROCKLANDING
Solar/Wind Harmer
0.075
961611AG1-000B GEN
Solar/Wind Harmer
11.899
315785AD2-033 C
Solar/Wind Harmer
5.31
971317AH1-138 GEN
Solar/Wind Harmer
2.888
316034AC1-036 C
Solar/Wind Harmer
0.426
316369SG1_INVT
Solar/Wind Harmer
3.968
970685AG2-442 GEN
Solar/Wind Harmer
18.905
971069AG2-661 GEN
Solar/Wind Harmer
3.404
971563AH1-280 GEN
Solar/Wind Harmer
2.636
3144293JTRSVLE
Adder
0.448
3144293JTRSVLE
Adder
0.354
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
315671AE2-027_GEN
Solar/Wind Harmer
3.66
315662AE1-191 GEN
Solar/Wind Harmer
2.025
316280AD1-041 GEN
Solar/Wind Harmer
1.265
971777AH1-397 GEN
Solar/Wind Harmer
1.941
3141766HARMONY
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.01
316314AB2-024 C
Solar/Wind Harmer
1.387
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.266
3142433PROV 92
Adder
0.266
970223AG2-152 GEN
Solar/Wind Harmer
13.626
315975AC1-164 GENB
Solar/Wind Harmer
0.102
270016AE1-250 BESS
Solar/Wind Harmer
2.264
944631AF1-128 GEN
Adder
61.035
962861AG1-135 GEN
Solar/Wind Harmer
5.238
316404AE1-155 C
Solar/Wind Harmer
2.628
316447AC1-158 HLD
Solar/Wind Helper
3.626
316044AC1-158 PL1
Solar/Wind Helper
1.648
3147666LOUISA
Solar/Wind Helper
1.008
316192AB2-158 GEN
Solar/Wind Helper
1.672
3143226MDLTHAN
Solar/Wind Helper
0.228
958261AF2-120 GEN
Solar/Wind Harmer
1.973
315244AE2-183_ST
50/50
10.002
963041AG1-153 GEN
50/50
9.172
315779AE2-040
50/50
3.972
3151541CLOVER2
50/50
5.858
3151081ELIZAR1
50/50
26.397
970533AG2-339 GEN
Solar/Wind Harmer
27.38
970673AG2-436 GEN
Solar/Wind Harmer
87.825
971967AH1-528 GEN
Solar/Wind Harmer
72.179
970085AG2-068 GEN
Solar/Wind Harmer
22.773
970581AG2-369 GEN
Solar/Wind Harmer
19.585
315814AE2-033 C
Solar/Wind Harmer
29.668
316486AD2-202 GEN
Solar/Wind Harmer
0.782
316018AA1-139 ULT2
Solar/Wind Harmer
2.616
957871AF2-081 GEN
Solar/Wind Harmer
15.307
316316AC1-027 C
Solar/Wind Harmer
0.936
3146406KITTY HAWK
Solar/Wind Harmer
0.025
3151091ELIZAR2
Adder
24.444
313526AB2-022
Solar/Wind Harmer
0.816
3146396TANGLEW
Solar/Wind Harmer
0.556
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315800Z1-036_GEN1
Solar/Wind Harmer
7.322
3130156CHOWAN
Solar/Wind Harmer
-0.029
3130156CHOWAN
Solar/Wind Harmer
-0.029
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.819
315733AD1-074 GEN2
Solar/Wind Harmer
5.819
946281AF1-292 GEN
Solar/Wind Harmer
0.645
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.548
316318V4-068
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.028
316311AC2-079 GEN
Solar/Wind Harmer
14.417
315833AF1-017_GEN
Solar/Wind Harmer
5.423
315652AC1-086 GEN
Solar/Wind Harmer
32.044
316463AE2-346 GEN
Solar/Wind Harmer
0.459
3145513AHOSKIE
Solar/Wind Harmer
0.248
961941AG1-037 GEN
Solar/Wind Harmer
0.214
3145513AHOSKIE
Solar/Wind Harmer
-0.028
3146043SEABORD
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.056
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.113
316426AA2-053 GEN
Solar/Wind Harmer
2.839
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
4.285
3146033SCOT NK
Solar/Wind Harmer
-0.11
316210AC1-098 GEN
Solar/Wind Harmer
4.302
970831AG2-522 GEN
Solar/Wind Harmer
13.725
316274AC1-208 GEN
Solar/Wind Harmer
2.946
316236AE1-162_GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
-0.107
971445AH1-216 GEN
Solar/Wind Harmer
16.752
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
1.696
316327AA2-057 GEN
Solar/Wind Harmer
2.706
957861AF2-080 GEN
Solar/Wind Harmer
11.674
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
316238AB2-078_GEN
Solar/Wind Harmer
0.764
316239AB2-077_GEN
Solar/Wind Harmer
0.764
3151201GRAVEL4
Adder
16.382
3151221GRAVEL6
Adder
16.363
3151191GRAVEL3
Adder
16.175
3151211GRAVEL5
Adder
16.175
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.018
315697AD1-025 GEN
Solar/Wind Harmer
4.49
315839AE2-212 C
Solar/Wind Harmer
0.665
970683AG2-441 GEN
Solar/Wind Harmer
15.571
970681AG2-440 GEN
Solar/Wind Harmer
10.335
316382AG1-145 C
Solar/Wind Harmer
0.645
316159AE1-175 C
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
5.403
961791AG1-021 GEN
Solar/Wind Harmer
2.636
957831AF2-077 GEN
Solar/Wind Harmer
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.033
270455AD2-022 GEN
Solar/Wind Harmer
3.61
270457AD2-023 GEN
Solar/Wind Harmer
1.831
957601AF2-054 GEN
Solar/Wind Harmer
0.512
3141873WAN 176
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.373
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
3143873LANEXA
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.266
3142433PROV 92
Adder
0.266
316164AC1-076 GEN
Solar/Wind Helper
1.182
315651AD1-115 GEN
Solar/Wind Helper
0.76
LAGNLTFEXP_LAGN->PJM
CLTF
11.282
CPLELTFEXP_CPLE->PJM
CLTF
15.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.636
TVALTFEXP_TVA->PJM
CLTF
5.654
MECLTFEXP_MEC->PJM
CLTF
5.503
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
2.893
LGEELTFEXP_LGEE->PJM
CLTF
2.009
WECLTFEXP_WEC->PJM
CLTF
1.027
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 13.63 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56722_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56722_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4852.84
MW Contribution:
1.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.582
963041AG1-153 GEN
50/50
9.698
3151081ELIZAR1
50/50
30.032
3151091ELIZAR2
50/50
29.51
941591AE2-156 GEN
50/50
27.368
972263AH1-716 GEN
50/50
176.302
315779AE2-040
50/50
4.11
970533AG2-339 GEN
Solar/Wind Harmer
29.011
970673AG2-436 GEN
Solar/Wind Harmer
93.006
971967AH1-528 GEN
Solar/Wind Harmer
76.268
970085AG2-068 GEN
Solar/Wind Harmer
24.027
970581AG2-369 GEN
Solar/Wind Harmer
20.663
316018AA1-139 ULT2
Solar/Wind Harmer
2.972
957871AF2-081 GEN
Solar/Wind Harmer
17.39
316316AC1-027 C
Solar/Wind Harmer
1.065
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.922
3146396TANGLEW
Solar/Wind Harmer
0.627
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.175
315814AE2-033 C
Solar/Wind Harmer
30.719
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316486AD2-202 GEN
Solar/Wind Harmer
0.816
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
315732AD1-074 GEN1
Solar/Wind Harmer
6.397
315733AD1-074 GEN2
Solar/Wind Harmer
6.397
3146206CASHIE
Solar/Wind Harmer
-0.031
970601AG2-382 GEN
Solar/Wind Harmer
13.732
316311AC2-079 GEN
Solar/Wind Harmer
15.72
315833AF1-017_GEN
Solar/Wind Harmer
5.91
316318V4-068
Solar/Wind Harmer
0.772
3145893MURPHYS
Solar/Wind Harmer
-0.083
3145893MURPHYS
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.496
3145513AHOSKIE
Solar/Wind Harmer
0.268
961941AG1-037 GEN
Solar/Wind Harmer
0.231
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.061
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146043SEABORD
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.651
946281AF1-292 GEN
Solar/Wind Harmer
0.676
316236AE1-162_GEN
Solar/Wind Harmer
0.906
315652AC1-086 GEN
Solar/Wind Harmer
33.907
316426AA2-053 GEN
Solar/Wind Harmer
3.022
3137643SOCKMAN
Solar/Wind Harmer
-0.119
971445AH1-216 GEN
Solar/Wind Harmer
18.499
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.012
315243AE2-183_GT3
50/50
6.094
3151051BRUNSWICKS1
50/50
9.945
3151021BRUNSWICKG1
50/50
4.79
971451AH1-221 GEN
50/50
14.547
3152331SURRY 2
50/50
12.892
3150981CHESPKA
50/50
4.071
940641AE2-051 GEN
Solar/Wind Harmer
41.046
941031AE2-094 GEN
Solar/Wind Harmer
80.89
939411AE1-173 GEN
Solar/Wind Harmer
208.136
970919AG2-571 GEN
Solar/Wind Harmer
12.361
970087AG2-069 GEN
Solar/Wind Harmer
36.041
315773AC2-141 GEN
Solar/Wind Harmer
15.581
944591AF1-124 GEN
Solar/Wind Harmer
163.065
3146456SLIGO L269
Solar/Wind Harmer
-0.035
319010AE1-072 C
Solar/Wind Harmer
6.997
316375AC2-012 GEN
Solar/Wind Harmer
11.939
316036AC1-147 C
Solar/Wind Harmer
0.929
957481AF2-042 GEN
Solar/Wind Harmer
107.048
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.65
315611Z1-036_GEN2
Solar/Wind Harmer
8.175
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.658
315816AE2-034 GEN
Solar/Wind Harmer
2.606
3145663CRESWEL
Solar/Wind Harmer
-0.09
971163AH1-040 GEN
Solar/Wind Harmer
30.277
315737AD1-076 GEN
Solar/Wind Harmer
6.014
315693AD1-088 GEN
Solar/Wind Harmer
15.841
3146206CASHIE
Solar/Wind Harmer
-0.031
971547AH1-271 GEN
Solar/Wind Harmer
7.847
316023GEN1_S
Solar/Wind Harmer
2.091
3145893MURPHYS
Solar/Wind Harmer
-0.123
3151031BRUNSWICKG2
50/50
4.79
3151101ELIZAR3
50/50
30.416
3151161SURRY 1
50/50
9.931
944011AF1-069 GEN
Solar/Wind Harmer
25.346
970917AG2-570 GEN
Solar/Wind Harmer
97.651
944581AF1-123 GEN
Solar/Wind Harmer
162.48
944601AF1-125 GEN
Solar/Wind Harmer
159.944
3142956BIRDNECK
Solar/Wind Harmer
1.866
316017AA1-139 ULT1
Solar/Wind Harmer
2.807
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.016
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.008
316305AF2-043 C
Solar/Wind Harmer
1.027
316246AF1-032 C
Solar/Wind Harmer
0.689
316321Z2-027
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.787
315735AD1-075 GEN1
Solar/Wind Harmer
3.198
3146206CASHIE
Solar/Wind Harmer
-0.031
3156081AA2-088 GEN
Solar/Wind Harmer
10.12
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
966621AG1-532 GEN
Solar/Wind Harmer
0.613
316317KELFORD C
Solar/Wind Harmer
1.396
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.012
316011AB1-132 GEN
Solar/Wind Harmer
6.295
316181AB2-040 GEN
Solar/Wind Harmer
4.182
316190AA2-174 GEN
Solar/Wind Harmer
0.368
3145796HORNRTN
Solar/Wind Harmer
-0.119
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.029
316212AC1-099_GEN
Solar/Wind Harmer
2.546
3147043LAWRENC
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
315722AD1-056 GEN
Solar/Wind Harmer
10.183
316420AA1-050 GEN
Solar/Wind Harmer
3.217
970657AG2-426 GEN
Solar/Wind Harmer
5.696
3146073TAR RVR
Solar/Wind Harmer
-0.028
3146083TARBORO
Solar/Wind Harmer
-0.028
3146233WITAKRS
Solar/Wind Harmer
0.587
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.018
3144216WINCHST
Adder
0.933
3150921YORKTN3
Adder
6.218
961601AG1-000A GEN
Solar/Wind Harmer
11.015
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
3.41
315813AE1-149 C
Solar/Wind Harmer
16.101
961611AG1-000B GEN
Solar/Wind Harmer
5.391
964241AG1-285 GEN
Solar/Wind Harmer
19.724
316003AC1-222 GEN
Solar/Wind Harmer
2.37
316222AC1-221 GEN
Solar/Wind Harmer
2.43
316283AC2-100 C
Solar/Wind Harmer
2.257
970257AG2-171 GEN
Solar/Wind Harmer
8.835
971775AH1-396 GEN
Solar/Wind Harmer
1.662
959311AF2-222 GEN
Solar/Wind Harmer
24.244
971683AH1-343 GEN
Solar/Wind Harmer
9.788
315778AD1-151 GEN
Solar/Wind Harmer
19.269
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
-0.064
316458AB2-190 GEN2
Solar/Wind Harmer
2.021
316123AC1-075 GEN
Solar/Wind Harmer
2.064
942461AE2-259 GEN
Solar/Wind Harmer
2.761
970133AG2-095 GEN
Solar/Wind Harmer
1.925
3141873WAN 176
Solar/Wind Harmer
2.026
316203AE2-005 GEN
Solar/Wind Harmer
6.802
315242AE2-183_GT2
50/50
6.094
315241AE2-183_GT1
50/50
6.078
972185AH1-677 GEN
50/50
22.028
3151041BRUNSWICKG3
50/50
4.79
972187AH1-678 GEN
50/50
10.991
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
970933AG2-581 GEN
Solar/Wind Harmer
36.582
316294AC1-161 GEN
Solar/Wind Harmer
12.042
316185AD1-033 GEN
Solar/Wind Harmer
3.684
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.342
316388AE2-253 GEN
Solar/Wind Harmer
2.342
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.098
3130086AYDLETT
Solar/Wind Harmer
-0.138
3146386ELIZ CT
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.819
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315835AF2-110_GEN
Solar/Wind Harmer
4.149
3144356SAPONY
Solar/Wind Harmer
1.154
316315AB2-025 C
Solar/Wind Harmer
0.89
3146376EDENTON
Solar/Wind Harmer
0.978
3146376EDENTON
Solar/Wind Harmer
0.978
315614AA2-178 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.919
3156021HOLLOMANSOL
Solar/Wind Harmer
4.157
3146173TUNIS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
315607AA1-063A GEN
Solar/Wind Harmer
3.057
960081AF2-299 GEN
Solar/Wind Harmer
3.397
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.12
316087AB2-174 GEN
Solar/Wind Harmer
4.284
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145783HORNRTN
Solar/Wind Harmer
-0.03
3146293MARTNCO
Solar/Wind Harmer
0.182
3147043LAWRENC
Adder
2.333
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316129AC1-054 GEN
Solar/Wind Harmer
2.507
971065AG2-659 GEN
Solar/Wind Harmer
14.285
316494AC1-189 GEN
Solar/Wind Harmer
3.058
961671AG1-007 GEN
Solar/Wind Harmer
0.355
3146083TARBORO
Solar/Wind Harmer
-0.028
3145493TOT1
Solar/Wind Harmer
0.833
316319Z2-044 C
Solar/Wind Harmer
1.549
3146233WITAKRS
Solar/Wind Harmer
-0.111
316381AD1-082 GEN
Solar/Wind Harmer
2.546
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316359AB2-059 GEN
Solar/Wind Harmer
3.72
3142053HEARTS
Solar/Wind Harmer
0.325
3151171GRAVELC
Adder
2.593
316131AB2-060 GEN
Solar/Wind Harmer
2.796
970401AG2-262 GEN
Solar/Wind Harmer
1.692
971317AH1-138 GEN
Solar/Wind Harmer
3.234
961611AG1-000B GEN
Solar/Wind Harmer
12.635
315785AD2-033 C
Solar/Wind Harmer
5.434
316034AC1-036 C
Solar/Wind Harmer
0.435
316369SG1_INVT
Solar/Wind Harmer
4.061
970685AG2-442 GEN
Solar/Wind Harmer
19.156
971069AG2-661 GEN
Solar/Wind Harmer
3.426
971563AH1-280 GEN
Solar/Wind Harmer
2.663
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.357
316132AB2-190 GEN1
Solar/Wind Harmer
2.021
315671AE2-027_GEN
Solar/Wind Harmer
3.365
315662AE1-191 GEN
Solar/Wind Harmer
1.987
316280AD1-041 GEN
Solar/Wind Harmer
1.242
315742AE1-103 GEN
Solar/Wind Harmer
7.663
316065AD1-022 GEN
Solar/Wind Harmer
15.751
316349AD2-085 GEN
Solar/Wind Harmer
2.763
316365GEN2_N
Solar/Wind Harmer
2.091
3145893MURPHYS
Solar/Wind Harmer
0.864
3145893MURPHYS
Solar/Wind Harmer
-0.056
3146173TUNIS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
316140AB2-099
Solar/Wind Harmer
0.207
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
962571AG1-106 GEN
Solar/Wind Harmer
4.333
315687AD1-152 GEN
Solar/Wind Harmer
3.613
313506AB2-031 GEN
Solar/Wind Harmer
2.407
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145783HORNRTN
Solar/Wind Harmer
3.528
3145783HORNRTN
Solar/Wind Harmer
2.822
3145783HORNRTN
Solar/Wind Harmer
0.882
3145783HORNRTN
Solar/Wind Harmer
0.353
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
316005AA1-067
Solar/Wind Harmer
0.581
315724AD1-057 GEN
Solar/Wind Harmer
5.601
3145493TOT1
Solar/Wind Harmer
0.434
3145453TOT5
Solar/Wind Harmer
0.261
3145603CNETO
Solar/Wind Harmer
0.174
316083AB2-161 GEN
Solar/Wind Harmer
4.516
961601AG1-000A GEN
Solar/Wind Harmer
10.878
316049AB1-081 GEN
Solar/Wind Harmer
2.976
316263AC1-034 GEN
Solar/Wind Harmer
12.966
316237AB2-079_GEN
Solar/Wind Harmer
0.789
313527AB2-043 GEN
Solar/Wind Harmer
4.249
962561AG1-105 GEN
Solar/Wind Harmer
14.606
964791AG1-342 GEN
Solar/Wind Harmer
5.539
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316118AC1-105 GEN
Solar/Wind Harmer
1.773
316248AF1-058 C
Solar/Wind Harmer
0.774
970323AG2-213 GEN
Solar/Wind Harmer
11.78
316033AB2-134 GEN
Solar/Wind Harmer
7.333
970301AG2-198 GEN
Solar/Wind Harmer
11.313
958211AF2-115 GEN
Solar/Wind Harmer
3.328
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
942751AE2-291 GEN
Solar/Wind Harmer
11.17
316156AD2-030 GEN
Solar/Wind Harmer
0.455
316240AF1-291 C
Solar/Wind Harmer
0.513
315666AE1-190 GEN
Solar/Wind Harmer
0.497
316441AF1-014 GEN
Solar/Wind Harmer
1.087
3141843SHACKLE
Adder
0.733
3141766HARMONY
Solar/Wind Harmer
1.422
3146926FARMVIL
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
3.594
961951AG1-038 GEN
Solar/Wind Harmer
1.881
944641AF1-129 GEN
Adder
67.017
316487AF1-042 GEN
Solar/Wind Harmer
1.881
270013AE1-250 PV
Solar/Wind Harmer
2.166
316045AC1-158 PL2
Solar/Wind Helper
4.491
316450AC1-158 RIC
Solar/Wind Helper
0.374
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
3147666LOUISA
Solar/Wind Helper
0.525
971777AH1-397 GEN
Solar/Wind Harmer
1.881
3138133OCRAN
Solar/Wind Harmer
-0.01
3141766HARMONY
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
1.308
970223AG2-152 GEN
Solar/Wind Harmer
13.16
270016AE1-250 BESS
Solar/Wind Harmer
2.166
3142433PROV 92
Solar/Wind Harmer
-0.055
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
962861AG1-135 GEN
Solar/Wind Harmer
5.124
316404AE1-155 C
Solar/Wind Harmer
2.566
958261AF2-120 GEN
Solar/Wind Harmer
5.21
3143226MDLTHAN
Solar/Wind Helper
0.266
316447AC1-158 HLD
Solar/Wind Helper
3.088
316044AC1-158 PL1
Solar/Wind Helper
1.404
3147666LOUISA
Solar/Wind Helper
0.913
316192AB2-158 GEN
Solar/Wind Helper
1.518
3146033SCOT NK
Solar/Wind Harmer
-0.118
316210AC1-098 GEN
Solar/Wind Harmer
4.582
316274AC1-208 GEN
Solar/Wind Harmer
3.127
3145746EVERETS
Solar/Wind Harmer
-0.114
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970831AG2-522 GEN
Solar/Wind Harmer
14.407
316327AA2-057 GEN
Solar/Wind Harmer
2.864
957861AF2-080 GEN
Solar/Wind Harmer
12.436
970657AG2-426 GEN
Solar/Wind Harmer
1.778
3145573BETHELC
Solar/Wind Harmer
-0.028
3145573BETHELC
Solar/Wind Harmer
-0.028
3151201GRAVEL4
Adder
17.745
3151221GRAVEL6
Adder
17.724
3151191GRAVEL3
Adder
17.52
3151211GRAVEL5
Adder
17.52
3143316POE
Solar/Wind Harmer
-0.106
316238AB2-078_GEN
Solar/Wind Harmer
0.789
316239AB2-077_GEN
Solar/Wind Harmer
0.789
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.019
316382AG1-145 C
Solar/Wind Harmer
0.688
316159AE1-175 C
Solar/Wind Harmer
0.613
315697AD1-025 GEN
Solar/Wind Harmer
4.596
957831AF2-077 GEN
Solar/Wind Harmer
0.682
3138283WHITEMARSH
Solar/Wind Harmer
0.035
970683AG2-441 GEN
Solar/Wind Harmer
15.818
970681AG2-440 GEN
Solar/Wind Harmer
10.499
946301AF1-294 GEN
Solar/Wind Harmer
5.458
961791AG1-021 GEN
Solar/Wind Harmer
2.663
315839AE2-212 C
Solar/Wind Harmer
0.625
270455AD2-022 GEN
Solar/Wind Harmer
3.659
270457AD2-023 GEN
Solar/Wind Harmer
1.856
957601AF2-054 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
316059AD1-063 C
Solar/Wind Harmer
0.36
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
10.604
CPLELTFEXP_CPLE->PJM
CLTF
16.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.873
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.952
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.553
TVALTFEXP_TVA->PJM
CLTF
5.289
MECLTFEXP_MEC->PJM
CLTF
4.82
SIGELTFEXP_SIGE->PJM
CLTF
0.143
NYPJM->LTFIMP_NY
CLTF
2.594
LGEELTFEXP_LGEE->PJM
CLTF
1.694
WECLTFEXP_WEC->PJM
CLTF
0.868
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 13.16 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4085.15
MW Contribution:
8.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.363
315241AE2-183_GT1
50/50
5.349
972185AH1-677 GEN
50/50
19.387
3151041BRUNSWICKG3
50/50
4.229
972187AH1-678 GEN
50/50
9.703
970909AG2-566 GEN
50/50
3.042
3144293JTRSVLE
50/50
0.671
970535AG2-341 GEN
50/50
4.397
3151581KERR 1
50/50
0.179
3151261ROARAP2
50/50
0.275
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.808
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.318
970099AG2-077 GEN
Solar/Wind Harmer
41.272
970301AG2-198 GEN
Solar/Wind Harmer
16.023
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
315243AE2-183_GT3
50/50
5.363
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.229
971451AH1-221 GEN
50/50
12.843
3151531CLOVER1
50/50
6.014
3144293JTRSVLE
50/50
0.671
3144293JTRSVLE
50/50
0.53
3151591KERR 2
50/50
0.501
3151641KERR 7
50/50
0.501
3147043LAWRENC
50/50
2.31
3151281ROARAP4
50/50
0.274
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
941031AE2-094 GEN
Solar/Wind Harmer
70.715
940641AE2-051 GEN
Solar/Wind Harmer
34.508
970919AG2-571 GEN
Solar/Wind Harmer
10.922
970087AG2-069 GEN
Solar/Wind Harmer
31.857
939411AE1-173 GEN
Solar/Wind Harmer
169.831
957481AF2-042 GEN
Solar/Wind Harmer
103.181
315693AD1-088 GEN
Solar/Wind Harmer
16.286
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.013
971563AH1-280 GEN
Solar/Wind Harmer
3.721
970685AG2-442 GEN
Solar/Wind Harmer
25.864
316034AC1-036 C
Solar/Wind Harmer
0.536
315785AD2-033 C
Solar/Wind Harmer
6.517
316131AB2-060 GEN
Solar/Wind Harmer
3.025
971065AG2-659 GEN
Solar/Wind Harmer
13.518
316129AC1-054 GEN
Solar/Wind Harmer
2.354
960081AF2-299 GEN
Solar/Wind Harmer
2.991
316023GEN1_S
Solar/Wind Harmer
1.781
970401AG2-262 GEN
Solar/Wind Harmer
1.724
316087AB2-174 GEN
Solar/Wind Harmer
3.747
315773AC2-141 GEN
Solar/Wind Harmer
10.899
944591AF1-124 GEN
Solar/Wind Harmer
117.662
3145783HORNRTN
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.572
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.101
3145796HORNRTN
Solar/Wind Harmer
-0.083
958211AF2-115 GEN
Solar/Wind Harmer
4.651
315687AD1-152 GEN
Solar/Wind Harmer
3.504
970323AG2-213 GEN
Solar/Wind Harmer
14.484
313527AB2-043 GEN
Solar/Wind Harmer
4.554
3144356SAPONY
Solar/Wind Harmer
0.978
316315AB2-025 C
Solar/Wind Harmer
0.754
316237AB2-079_GEN
Solar/Wind Harmer
0.84
962561AG1-105 GEN
Solar/Wind Harmer
14.998
316365GEN2_N
Solar/Wind Harmer
1.781
964791AG1-342 GEN
Solar/Wind Harmer
5.642
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.1
316294AC1-161 GEN
Solar/Wind Harmer
8.423
316118AC1-105 GEN
Solar/Wind Harmer
1.771
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.038
3145783HORNRTN
Solar/Wind Harmer
2.43
3145783HORNRTN
Solar/Wind Harmer
0.759
3145783HORNRTN
Solar/Wind Harmer
0.304
962571AG1-106 GEN
Solar/Wind Harmer
3.662
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.666
316339AD2-160 GEN
Solar/Wind Harmer
1.702
316388AE2-253 GEN
Solar/Wind Harmer
1.702
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.985
3130086AYDLETT
Solar/Wind Harmer
-0.101
316248AF1-058 C
Solar/Wind Harmer
0.759
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.538
316433W1029_GEN2
Solar/Wind Harmer
4.538
316435W1029_GEN3
Solar/Wind Harmer
4.538
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315611Z1-036_GEN2
Solar/Wind Harmer
6.164
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.609
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.766
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.004
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.279
3145823KELFORD
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.327
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.187
315737AD1-076 GEN
Solar/Wind Harmer
4.693
316093AE2-104_GEN
Solar/Wind Harmer
7.15
3145963POPLR C
Solar/Wind Harmer
-0.024
316319Z2-044 C
Solar/Wind Harmer
1.326
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.559
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.192
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.476
3145336SMITFLD
Solar/Wind Harmer
-0.085
316381AD1-082 GEN
Solar/Wind Harmer
1.951
3151171GRAVELC
Adder
1.828
3138126ROCKLANDING
Solar/Wind Harmer
0.056
961611AG1-000B GEN
Solar/Wind Harmer
8.906
971317AH1-138 GEN
Solar/Wind Harmer
2.061
316369SG1_INVT
Solar/Wind Harmer
2.862
971069AG2-661 GEN
Solar/Wind Harmer
2.413
315671AE2-027_GEN
Solar/Wind Harmer
2.578
316132AB2-190 GEN1
Solar/Wind Harmer
1.423
970223AG2-152 GEN
Solar/Wind Harmer
12.166
270016AE1-250 BESS
Solar/Wind Harmer
2.007
3143226MDLTHAN
Solar/Wind Helper
0.35
316447AC1-158 HLD
Solar/Wind Helper
2.927
316044AC1-158 PL1
Solar/Wind Helper
1.33
3143526WINTERP
Solar/Wind Helper
1.193
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.168
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.321
3150991CHESPKB
Adder
2.265
315742AE1-103 GEN
Solar/Wind Harmer
5.898
315614AA2-178 GEN
Solar/Wind Harmer
2.672
316065AD1-022 GEN
Solar/Wind Harmer
12.372
315835AF2-110_GEN
Solar/Wind Harmer
3.074
315724AD1-057 GEN
Solar/Wind Harmer
4.774
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
316005AA1-067
Solar/Wind Harmer
0.481
3145493TOT1
Solar/Wind Harmer
0.367
3145453TOT5
Solar/Wind Harmer
0.22
3145603CNETO
Solar/Wind Harmer
0.147
316049AB1-081 GEN
Solar/Wind Harmer
2.554
316263AC1-034 GEN
Solar/Wind Harmer
11.125
961601AG1-000A GEN
Solar/Wind Harmer
9.319
316349AD2-085 GEN
Solar/Wind Harmer
2.072
316083AB2-161 GEN
Solar/Wind Harmer
3.461
942751AE2-291 GEN
Solar/Wind Harmer
10.866
316033AB2-134 GEN
Solar/Wind Harmer
5.167
270013AE1-250 PV
Solar/Wind Harmer
2.007
316240AF1-291 C
Solar/Wind Harmer
0.388
316313AB2-026
Solar/Wind Helper
0.534
316045AC1-158 PL2
Solar/Wind Helper
4.257
316450AC1-158 RIC
Solar/Wind Helper
0.355
3143526WINTERP
Solar/Wind Helper
1.193
3151031BRUNSWICKG2
50/50
4.229
970413AG2-270 GEN
50/50
26.189
3144293JTRSVLE
50/50
0.671
3151261ROARAP2
50/50
0.282
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
944011AF1-069 GEN
Solar/Wind Harmer
22.157
970917AG2-570 GEN
Solar/Wind Harmer
86.288
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
12.856
316478AD1-087 GEN
Solar/Wind Harmer
2.718
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
959311AF2-222 GEN
Solar/Wind Harmer
30.36
970257AG2-171 GEN
Solar/Wind Harmer
10.863
971775AH1-396 GEN
Solar/Wind Harmer
2.044
964241AG1-285 GEN
Solar/Wind Harmer
22.168
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316181AB2-040 GEN
Solar/Wind Harmer
3.647
944581AF1-123 GEN
Solar/Wind Harmer
117.24
944601AF1-125 GEN
Solar/Wind Harmer
115.41
316190AA2-174 GEN
Solar/Wind Harmer
0.314
316011AB1-132 GEN
Solar/Wind Harmer
5.321
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
316017AA1-139 ULT1
Solar/Wind Harmer
2.042
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.925
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.474
3156081AA2-088 GEN
Solar/Wind Harmer
8.16
3142956BIRDNECK
Solar/Wind Harmer
1.349
316321Z2-027
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.752
316246AF1-032 C
Solar/Wind Harmer
0.505
3151101ELIZAR3
Adder
20.667
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316317KELFORD C
Solar/Wind Harmer
1.148
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.495
316212AC1-099_GEN
Solar/Wind Harmer
2.148
315722AD1-056 GEN
Solar/Wind Harmer
8.68
3145963POPLR C
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.502
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.319
316420AA1-050 GEN
Solar/Wind Harmer
2.708
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.437
316222AC1-221 GEN
Solar/Wind Harmer
2.254
316283AC2-100 C
Solar/Wind Harmer
2.091
971683AH1-343 GEN
Solar/Wind Harmer
9.57
970657AG2-426 GEN
Solar/Wind Harmer
4.354
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.544
3151171GRAVELC
Adder
2.404
316123AC1-075 GEN
Solar/Wind Harmer
2.012
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.042
961611AG1-000B GEN
Solar/Wind Harmer
3.8
315778AD1-151 GEN
Solar/Wind Harmer
13.575
316458AB2-190 GEN2
Solar/Wind Harmer
1.423
315244AE2-183_ST
50/50
9.313
963041AG1-153 GEN
50/50
8.562
3151541CLOVER2
50/50
5.968
315779AE2-040
50/50
3.484
3151601KERR 3
50/50
0.501
3151611KERR 4
50/50
0.501
3151621KERR 5
50/50
0.501
3151631KERR 6
50/50
0.501
3151281ROARAP4
50/50
0.256
970533AG2-339 GEN
Solar/Wind Harmer
25.362
970673AG2-436 GEN
Solar/Wind Harmer
81.518
971967AH1-528 GEN
Solar/Wind Harmer
68.252
970085AG2-068 GEN
Solar/Wind Harmer
21.238
970581AG2-369 GEN
Solar/Wind Harmer
18.265
316322AB2-045
Solar/Wind Harmer
1.062
971845AH1-439 GEN
Solar/Wind Harmer
16.816
316486AD2-202 GEN
Solar/Wind Harmer
0.796
946301AF1-294 GEN
Solar/Wind Harmer
7.628
961791AG1-021 GEN
Solar/Wind Harmer
3.721
970683AG2-441 GEN
Solar/Wind Harmer
20.75
970681AG2-440 GEN
Solar/Wind Harmer
13.772
3144303KENBRDG
Solar/Wind Harmer
-0.023
315814AE2-033 C
Solar/Wind Harmer
26.043
316238AB2-078_GEN
Solar/Wind Harmer
0.84
316239AB2-077_GEN
Solar/Wind Harmer
0.84
970831AG2-522 GEN
Solar/Wind Harmer
13.396
946281AF1-292 GEN
Solar/Wind Harmer
0.596
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316426AA2-053 GEN
Solar/Wind Harmer
2.579
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.662
316018AA1-139 ULT2
Solar/Wind Harmer
2.162
957871AF2-081 GEN
Solar/Wind Harmer
12.65
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
313526AB2-022
Solar/Wind Harmer
0.677
3146396TANGLEW
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.769
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3151081ELIZAR1
Adder
20.406
3151091ELIZAR2
Adder
20.051
315800Z1-036_GEN1
Solar/Wind Harmer
6.164
316463AE2-346 GEN
Solar/Wind Harmer
0.402
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316274AC1-208 GEN
Solar/Wind Harmer
2.665
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.827
3146033SCOT NK
Solar/Wind Harmer
-0.098
315732AD1-074 GEN1
Solar/Wind Harmer
4.993
315733AD1-074 GEN2
Solar/Wind Harmer
4.993
316210AC1-098 GEN
Solar/Wind Harmer
3.867
316327AA2-057 GEN
Solar/Wind Harmer
2.445
316174AB2-169 GEN
Solar/Wind Harmer
3.736
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.406
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.782
315833AF1-017_GEN
Solar/Wind Harmer
4.431
3143316POE
Solar/Wind Harmer
-0.086
970657AG2-426 GEN
Solar/Wind Harmer
1.359
316236AE1-162_GEN
Solar/Wind Harmer
0.645
971445AH1-216 GEN
Solar/Wind Harmer
13.157
3151201GRAVEL4
Adder
12.508
3151221GRAVEL6
Adder
12.494
3151191GRAVEL3
Adder
12.35
3151211GRAVEL5
Adder
12.35
270455AD2-022 GEN
Solar/Wind Harmer
3.349
270457AD2-023 GEN
Solar/Wind Harmer
1.698
315839AE2-212 C
Solar/Wind Harmer
0.492
315697AD1-025 GEN
Solar/Wind Harmer
3.238
957831AF2-077 GEN
Solar/Wind Harmer
0.437
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.436
316159AE1-175 C
Solar/Wind Harmer
0.388
316258AE1-075 C
Solar/Wind Helper
0.481
316405AF2-144 C
Solar/Wind Helper
0.401
316233AE1-074 FULL
Solar/Wind Helper
0.35
LAGNLTFEXP_LAGN->PJM
CLTF
9.773
CPLELTFEXP_CPLE->PJM
CLTF
14.696
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.451
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.621
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.799
TVALTFEXP_TVA->PJM
CLTF
4.879
MECLTFEXP_MEC->PJM
CLTF
4.569
SIGELTFEXP_SIGE->PJM
CLTF
0.136
NYPJM->LTFIMP_NY
CLTF
2.278
LGEELTFEXP_LGEE->PJM
CLTF
1.626
WECLTFEXP_WEC->PJM
CLTF
0.836
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 12.17 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.34 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4032.02
MW Contribution:
8.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.534
3151051BRUNSWICKS1
50/50
9.031
3151021BRUNSWICKG1
50/50
4.35
971451AH1-221 GEN
50/50
13.21
3151531CLOVER1
50/50
5.577
315242AE2-183_GT2
50/50
5.534
315241AE2-183_GT1
50/50
5.52
972185AH1-677 GEN
50/50
20.006
3151041BRUNSWICKG3
50/50
4.35
972187AH1-678 GEN
50/50
9.981
3151361ROSEMG1
50/50
0.865
3151371ROSEMS1
50/50
0.536
3151381ROSEMG2
50/50
0.405
3151261ROARAP2
50/50
0.284
3151581KERR 1
50/50
0.164
970933AG2-581 GEN
Solar/Wind Harmer
33.184
3144356SAPONY
Solar/Wind Harmer
1.182
316315AB2-025 C
Solar/Wind Harmer
0.911
970099AG2-077 GEN
Solar/Wind Harmer
38.754
316365GEN2_N
Solar/Wind Harmer
1.99
313506AB2-031 GEN
Solar/Wind Harmer
2.2
962571AG1-106 GEN
Solar/Wind Harmer
3.938
315687AD1-152 GEN
Solar/Wind Harmer
3.269
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.081
316294AC1-161 GEN
Solar/Wind Harmer
8.622
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.221
3145783HORNRTN
Solar/Wind Harmer
3.135
3145783HORNRTN
Solar/Wind Harmer
2.508
3145783HORNRTN
Solar/Wind Harmer
0.784
3145783HORNRTN
Solar/Wind Harmer
0.314
3145893MURPHYS
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
-0.047
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316140AB2-099
Solar/Wind Harmer
0.174
3145506HICKORY
Solar/Wind Harmer
-0.102
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
315724AD1-057 GEN
Solar/Wind Harmer
5.031
316339AD2-160 GEN
Solar/Wind Harmer
1.727
316388AE2-253 GEN
Solar/Wind Harmer
1.727
316185AD1-033 GEN
Solar/Wind Harmer
2.702
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.031
3130086AYDLETT
Solar/Wind Harmer
-0.102
3146386ELIZ CT
Solar/Wind Harmer
-0.026
315742AE1-103 GEN
Solar/Wind Harmer
6.065
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316065AD1-022 GEN
Solar/Wind Harmer
12.774
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.625
316433W1029_GEN2
Solar/Wind Harmer
4.625
316435W1029_GEN3
Solar/Wind Harmer
4.625
3151391GASTONA
50/50
0.652
3146376EDENTON
Solar/Wind Harmer
0.757
3146376EDENTON
Solar/Wind Harmer
0.757
315614AA2-178 GEN
Solar/Wind Harmer
2.745
315835AF2-110_GEN
Solar/Wind Harmer
3.154
3150991CHESPKB
Adder
2.339
3150991CHESPKB
Adder
2.283
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
961601AG1-000A GEN
Solar/Wind Harmer
9.686
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.152
316005AA1-067
Solar/Wind Harmer
0.497
316049AB1-081 GEN
Solar/Wind Harmer
2.648
316263AC1-034 GEN
Solar/Wind Harmer
11.537
316349AD2-085 GEN
Solar/Wind Harmer
2.179
316237AB2-079_GEN
Solar/Wind Harmer
0.713
313527AB2-043 GEN
Solar/Wind Harmer
3.839
962561AG1-105 GEN
Solar/Wind Harmer
13.212
964791AG1-342 GEN
Solar/Wind Harmer
5.011
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
316083AB2-161 GEN
Solar/Wind Harmer
3.802
316118AC1-105 GEN
Solar/Wind Harmer
1.605
316248AF1-058 C
Solar/Wind Harmer
0.701
970323AG2-213 GEN
Solar/Wind Harmer
10.571
970301AG2-198 GEN
Solar/Wind Harmer
10.055
958211AF2-115 GEN
Solar/Wind Harmer
2.965
3144293JTRSVLE
Adder
0.403
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
942751AE2-291 GEN
Solar/Wind Harmer
10.208
316033AB2-134 GEN
Solar/Wind Harmer
4.263
270013AE1-250 PV
Solar/Wind Harmer
1.991
316045AC1-158 PL2
Solar/Wind Helper
4.232
316450AC1-158 RIC
Solar/Wind Helper
0.353
3143526WINTERP
Solar/Wind Helper
1.168
3151411GASTONB
50/50
0.652
3147043LAWRENC
50/50
2.292
3151281ROARAP4
50/50
0.283
3151591KERR 2
50/50
0.459
3151641KERR 7
50/50
0.459
941031AE2-094 GEN
Solar/Wind Harmer
73.492
940641AE2-051 GEN
Solar/Wind Harmer
36.064
970919AG2-571 GEN
Solar/Wind Harmer
11.221
939411AE1-173 GEN
Solar/Wind Harmer
176.578
970087AG2-069 GEN
Solar/Wind Harmer
32.713
957481AF2-042 GEN
Solar/Wind Harmer
96.886
316023GEN1_S
Solar/Wind Harmer
1.99
315693AD1-088 GEN
Solar/Wind Harmer
14.299
960081AF2-299 GEN
Solar/Wind Harmer
3.174
316087AB2-174 GEN
Solar/Wind Harmer
3.941
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.027
315773AC2-141 GEN
Solar/Wind Harmer
11.155
3145783HORNRTN
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.653
944591AF1-124 GEN
Solar/Wind Harmer
119.629
3146263WOODLND
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.769
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
316129AC1-054 GEN
Solar/Wind Harmer
2.248
3145823KELFORD
Solar/Wind Harmer
-0.026
3156021HOLLOMANSOL
Solar/Wind Harmer
3.454
3146456SLIGO L269
Solar/Wind Harmer
-0.026
319010AE1-072 C
Solar/Wind Harmer
5.18
971065AG2-659 GEN
Solar/Wind Harmer
12.819
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.395
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
315611Z1-036_GEN2
Solar/Wind Harmer
6.306
3130156CHOWAN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.058
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.914
315737AD1-076 GEN
Solar/Wind Harmer
4.836
316093AE2-104_GEN
Solar/Wind Harmer
7.337
3145963POPLR C
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.676
316036AC1-147 C
Solar/Wind Harmer
0.675
3150981CHESPKA
Adder
2.788
316319Z2-044 C
Solar/Wind Harmer
1.374
3146233WITAKRS
Solar/Wind Harmer
-0.098
3146293MARTNCO
Solar/Wind Harmer
0.153
961671AG1-007 GEN
Solar/Wind Harmer
0.311
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.731
316494AC1-189 GEN
Solar/Wind Harmer
2.65
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316359AB2-059 GEN
Solar/Wind Harmer
3.31
3142053HEARTS
Solar/Wind Harmer
0.289
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316072AD1-144
Solar/Wind Harmer
0.477
316131AB2-060 GEN
Solar/Wind Harmer
2.525
970401AG2-262 GEN
Solar/Wind Harmer
1.531
316381AD1-082 GEN
Solar/Wind Harmer
2.144
315785AD2-033 C
Solar/Wind Harmer
4.883
316034AC1-036 C
Solar/Wind Harmer
0.391
3145336SMITFLD
Solar/Wind Harmer
-0.082
970685AG2-442 GEN
Solar/Wind Harmer
17.102
971563AH1-280 GEN
Solar/Wind Harmer
2.372
3144293JTRSVLE
Adder
0.403
3144293JTRSVLE
Adder
0.318
3151171GRAVELC
Adder
1.691
3138126ROCKLANDING
Solar/Wind Harmer
0.054
315671AE2-027_GEN
Solar/Wind Harmer
3.076
961611AG1-000B GEN
Solar/Wind Harmer
7.931
971317AH1-138 GEN
Solar/Wind Harmer
1.996
3146926FARMVIL
Solar/Wind Harmer
-0.008
970223AG2-152 GEN
Solar/Wind Harmer
12.074
316369SG1_INVT
Solar/Wind Harmer
2.361
270016AE1-250 BESS
Solar/Wind Harmer
1.991
3143226MDLTHAN
Solar/Wind Helper
0.326
316447AC1-158 HLD
Solar/Wind Helper
2.91
316044AC1-158 PL1
Solar/Wind Helper
1.322
3143526WINTERP
Solar/Wind Helper
1.168
3151031BRUNSWICKG2
50/50
4.35
970413AG2-270 GEN
50/50
24.286
3151391GASTONA
50/50
0.652
3151411GASTONB
50/50
0.652
3151261ROARAP2
50/50
0.291
944011AF1-069 GEN
Solar/Wind Harmer
23.028
970917AG2-570 GEN
Solar/Wind Harmer
88.644
316478AD1-087 GEN
Solar/Wind Harmer
2.521
966621AG1-532 GEN
Solar/Wind Harmer
0.573
316181AB2-040 GEN
Solar/Wind Harmer
3.821
316011AB1-132 GEN
Solar/Wind Harmer
5.721
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3147043LAWRENC
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.324
944581AF1-123 GEN
Solar/Wind Harmer
119.199
944601AF1-125 GEN
Solar/Wind Harmer
117.339
3146263WOODLND
Solar/Wind Harmer
-0.026
3156081AA2-088 GEN
Solar/Wind Harmer
8.413
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316317KELFORD C
Solar/Wind Harmer
1.19
3145823KELFORD
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
9.147
316017AA1-139 ULT1
Solar/Wind Harmer
2.072
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.97
316320Y1-086
Solar/Wind Harmer
1.5
316321Z2-027
Solar/Wind Harmer
0.688
3146206CASHIE
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.224
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.571
3145273HOLLAND
Solar/Wind Harmer
-0.019
316305AF2-043 C
Solar/Wind Harmer
0.765
316246AF1-032 C
Solar/Wind Harmer
0.513
3142956BIRDNECK
Solar/Wind Harmer
1.364
3151101ELIZAR3
Adder
20.853
3145963POPLR C
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.521
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.025
961601AG1-000A GEN
Solar/Wind Harmer
9.808
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
316420AA1-050 GEN
Solar/Wind Harmer
2.806
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
970657AG2-426 GEN
Solar/Wind Harmer
4.76
964241AG1-285 GEN
Solar/Wind Harmer
17.779
315813AE1-149 C
Solar/Wind Harmer
14.218
316003AC1-222 GEN
Solar/Wind Harmer
2.148
316222AC1-221 GEN
Solar/Wind Harmer
2.2
316283AC2-100 C
Solar/Wind Harmer
2.043
970257AG2-171 GEN
Solar/Wind Harmer
7.928
971775AH1-396 GEN
Solar/Wind Harmer
1.492
959311AF2-222 GEN
Solar/Wind Harmer
21.734
3145336SMITFLD
Solar/Wind Harmer
-0.008
971683AH1-343 GEN
Solar/Wind Harmer
8.887
3144293JTRSVLE
Adder
0.403
3147133PAMPLIN
Solar/Wind Harmer
-0.057
3151171GRAVELC
Adder
2.223
3144216WINCHST
Adder
0.593
3150921YORKTN3
Adder
3.938
316123AC1-075 GEN
Solar/Wind Harmer
1.882
942461AE2-259 GEN
Solar/Wind Harmer
2.43
961611AG1-000B GEN
Solar/Wind Harmer
3.384
3146926FARMVIL
Solar/Wind Harmer
-0.008
315244AE2-183_ST
50/50
9.611
963041AG1-153 GEN
50/50
8.806
315779AE2-040
50/50
4.209
3151541CLOVER2
50/50
5.534
3151281ROARAP4
50/50
0.264
3151151S HAMPT1
50/50
0.59
3151601KERR 3
50/50
0.459
3151611KERR 4
50/50
0.459
3151621KERR 5
50/50
0.459
3151631KERR 6
50/50
0.459
970533AG2-339 GEN
Solar/Wind Harmer
26.358
970673AG2-436 GEN
Solar/Wind Harmer
84.488
971967AH1-528 GEN
Solar/Wind Harmer
69.23
970085AG2-068 GEN
Solar/Wind Harmer
21.808
970581AG2-369 GEN
Solar/Wind Harmer
18.755
315814AE2-033 C
Solar/Wind Harmer
31.344
3143316POE
Solar/Wind Harmer
-0.131
316486AD2-202 GEN
Solar/Wind Harmer
0.738
946281AF1-292 GEN
Solar/Wind Harmer
0.632
315652AC1-086 GEN
Solar/Wind Harmer
30.818
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.107
316426AA2-053 GEN
Solar/Wind Harmer
2.663
3146043SEABORD
Solar/Wind Harmer
-0.026
316318V4-068
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.225
961941AG1-037 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
12.907
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
316018AA1-139 ULT2
Solar/Wind Harmer
2.194
957871AF2-081 GEN
Solar/Wind Harmer
12.841
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3146033SCOT NK
Solar/Wind Harmer
-0.102
316274AC1-208 GEN
Solar/Wind Harmer
2.757
313526AB2-022
Solar/Wind Harmer
0.689
3146396TANGLEW
Solar/Wind Harmer
0.471
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.191
316210AC1-098 GEN
Solar/Wind Harmer
4.003
315800Z1-036_GEN1
Solar/Wind Harmer
6.306
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.144
315733AD1-074 GEN2
Solar/Wind Harmer
5.144
316316AC1-027 C
Solar/Wind Harmer
0.778
3151081ELIZAR1
Adder
20.589
3151091ELIZAR2
Adder
20.232
316327AA2-057 GEN
Solar/Wind Harmer
2.532
316174AB2-169 GEN
Solar/Wind Harmer
3.856
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
957861AF2-080 GEN
Solar/Wind Harmer
10.777
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.386
315833AF1-017_GEN
Solar/Wind Harmer
4.66
316238AB2-078_GEN
Solar/Wind Harmer
0.713
316239AB2-077_GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
1.486
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
3144303KENBRDG
Solar/Wind Harmer
-0.017
316236AE1-162_GEN
Solar/Wind Harmer
0.621
971445AH1-216 GEN
Solar/Wind Harmer
12.615
970683AG2-441 GEN
Solar/Wind Harmer
14.145
970681AG2-440 GEN
Solar/Wind Harmer
9.388
946301AF1-294 GEN
Solar/Wind Harmer
4.863
961791AG1-021 GEN
Solar/Wind Harmer
2.372
270455AD2-022 GEN
Solar/Wind Harmer
3.322
270457AD2-023 GEN
Solar/Wind Harmer
1.685
3151201GRAVEL4
Adder
11.57
3151221GRAVEL6
Adder
11.556
3151191GRAVEL3
Adder
11.423
3151211GRAVEL5
Adder
11.423
957831AF2-077 GEN
Solar/Wind Harmer
0.415
3138283WHITEMARSH
Solar/Wind Harmer
0.021
316382AG1-145 C
Solar/Wind Harmer
0.413
316159AE1-175 C
Solar/Wind Harmer
0.368
315697AD1-025 GEN
Solar/Wind Harmer
2.672
316233AE1-074 FULL
Solar/Wind Helper
0.343
LAGNLTFEXP_LAGN->PJM
CLTF
9.91
CPLELTFEXP_CPLE->PJM
CLTF
14.816
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.797
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.727
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.867
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
TVALTFEXP_TVA->PJM
CLTF
4.946
MECLTFEXP_MEC->PJM
CLTF
4.663
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.274
LGEELTFEXP_LGEE->PJM
CLTF
1.663
WECLTFEXP_WEC->PJM
CLTF
0.856
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 12.07 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4029.66
MW Contribution:
0.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.3
315241AE2-183_GT1
50/50
5.286
972185AH1-677 GEN
50/50
19.158
3151041BRUNSWICKG3
50/50
4.165
972187AH1-678 GEN
50/50
9.556
970933AG2-581 GEN
Solar/Wind Harmer
31.74
970099AG2-077 GEN
Solar/Wind Harmer
36.983
3144356SAPONY
Solar/Wind Harmer
1.024
316315AB2-025 C
Solar/Wind Harmer
0.79
316294AC1-161 GEN
Solar/Wind Harmer
8.635
316365GEN2_N
Solar/Wind Harmer
1.798
316185AD1-033 GEN
Solar/Wind Harmer
2.761
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.76
316388AE2-253 GEN
Solar/Wind Harmer
1.76
315243AE2-183_GT3
50/50
5.3
3151051BRUNSWICKS1
50/50
8.646
3151021BRUNSWICKG1
50/50
4.165
971451AH1-221 GEN
50/50
12.647
3151531CLOVER1
50/50
5.317
941031AE2-094 GEN
Solar/Wind Harmer
70.403
940641AE2-051 GEN
Solar/Wind Harmer
34.763
939411AE1-173 GEN
Solar/Wind Harmer
171.933
970919AG2-571 GEN
Solar/Wind Harmer
10.74
970087AG2-069 GEN
Solar/Wind Harmer
31.307
957481AF2-042 GEN
Solar/Wind Harmer
92.457
315693AD1-088 GEN
Solar/Wind Harmer
13.618
315773AC2-141 GEN
Solar/Wind Harmer
11.172
316023GEN1_S
Solar/Wind Harmer
1.798
944591AF1-124 GEN
Solar/Wind Harmer
121.503
3151031BRUNSWICKG2
50/50
4.165
970413AG2-270 GEN
50/50
23.154
3151101ELIZAR3
50/50
22.804
944011AF1-069 GEN
Solar/Wind Harmer
22.06
970917AG2-570 GEN
Solar/Wind Harmer
84.846
316478AD1-087 GEN
Solar/Wind Harmer
2.403
944581AF1-123 GEN
Solar/Wind Harmer
121.067
944601AF1-125 GEN
Solar/Wind Harmer
119.178
316017AA1-139 ULT1
Solar/Wind Harmer
2.111
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.086
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3150991CHESPKB
Adder
2.416
3150991CHESPKB
Adder
2.358
315687AD1-152 GEN
Solar/Wind Harmer
3.115
316431W1029_GEN1
Solar/Wind Harmer
4.674
316433W1029_GEN2
Solar/Wind Harmer
4.674
316435W1029_GEN3
Solar/Wind Harmer
4.674
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315835AF2-110_GEN
Solar/Wind Harmer
3.2
3146376EDENTON
Solar/Wind Harmer
0.757
3146376EDENTON
Solar/Wind Harmer
0.757
313506AB2-031 GEN
Solar/Wind Harmer
2.037
315742AE1-103 GEN
Solar/Wind Harmer
6.03
962571AG1-106 GEN
Solar/Wind Harmer
3.652
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
315614AA2-178 GEN
Solar/Wind Harmer
2.72
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.699
3145893MURPHYS
Solar/Wind Harmer
-0.045
316065AD1-022 GEN
Solar/Wind Harmer
12.514
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.168
316349AD2-085 GEN
Solar/Wind Harmer
2.209
3145783HORNRTN
Solar/Wind Harmer
2.95
3145783HORNRTN
Solar/Wind Harmer
2.36
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
315724AD1-057 GEN
Solar/Wind Harmer
4.719
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
316083AB2-161 GEN
Solar/Wind Harmer
3.853
316005AA1-067
Solar/Wind Harmer
0.478
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.024
3142956BIRDNECK
Solar/Wind Harmer
1.4
316320Y1-086
Solar/Wind Harmer
1.521
316321Z2-027
Solar/Wind Harmer
0.697
316305AF2-043 C
Solar/Wind Harmer
0.779
316246AF1-032 C
Solar/Wind Harmer
0.523
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.524
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
316181AB2-040 GEN
Solar/Wind Harmer
3.538
316011AB1-132 GEN
Solar/Wind Harmer
5.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
8.165
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.528
3145493TOT1
Solar/Wind Harmer
0.362
3145453TOT5
Solar/Wind Harmer
0.217
3145603CNETO
Solar/Wind Harmer
0.145
961601AG1-000A GEN
Solar/Wind Harmer
9.157
316049AB1-081 GEN
Solar/Wind Harmer
2.505
316263AC1-034 GEN
Solar/Wind Harmer
10.913
316237AB2-079_GEN
Solar/Wind Harmer
0.672
3146456SLIGO L269
Solar/Wind Harmer
-0.026
319010AE1-072 C
Solar/Wind Harmer
5.272
316375AC2-012 GEN
Solar/Wind Harmer
8.961
316036AC1-147 C
Solar/Wind Harmer
0.697
3150981CHESPKA
Adder
2.879
960081AF2-299 GEN
Solar/Wind Harmer
2.902
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
316093AE2-104_GEN
Solar/Wind Harmer
7.444
315611Z1-036_GEN2
Solar/Wind Harmer
6.313
316087AB2-174 GEN
Solar/Wind Harmer
3.635
3130156CHOWAN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.04
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.696
3145796HORNRTN
Solar/Wind Harmer
-0.082
3145796HORNRTN
Solar/Wind Harmer
-0.025
315737AD1-076 GEN
Solar/Wind Harmer
4.756
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
315607AA1-063A GEN
Solar/Wind Harmer
2.523
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.251
3146173TUNIS
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.348
3146263WOODLND
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
1.991
316072AD1-144
Solar/Wind Harmer
0.498
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.122
971065AG2-659 GEN
Solar/Wind Harmer
12.104
3146293MARTNCO
Solar/Wind Harmer
0.148
316381AD1-082 GEN
Solar/Wind Harmer
2.173
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.533
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.306
3146263WOODLND
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
1.141
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316212AC1-099_GEN
Solar/Wind Harmer
2.113
315722AD1-056 GEN
Solar/Wind Harmer
8.579
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
4.823
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.493
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
2.675
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.273
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145336SMITFLD
Solar/Wind Harmer
-0.009
315813AE1-149 C
Solar/Wind Harmer
14.398
3151171GRAVELC
Adder
2.682
964241AG1-285 GEN
Solar/Wind Harmer
16.731
316003AC1-222 GEN
Solar/Wind Harmer
2.041
316222AC1-221 GEN
Solar/Wind Harmer
2.095
315244AE2-183_ST
50/50
9.203
963041AG1-153 GEN
50/50
8.432
315779AE2-040
50/50
3.647
3151541CLOVER2
50/50
5.276
3151081ELIZAR1
50/50
22.515
970533AG2-339 GEN
Solar/Wind Harmer
25.25
970673AG2-436 GEN
Solar/Wind Harmer
80.925
971967AH1-528 GEN
Solar/Wind Harmer
66.26
970085AG2-068 GEN
Solar/Wind Harmer
20.872
970581AG2-369 GEN
Solar/Wind Harmer
17.95
315814AE2-033 C
Solar/Wind Harmer
27.212
316486AD2-202 GEN
Solar/Wind Harmer
0.704
316018AA1-139 ULT2
Solar/Wind Harmer
2.236
957871AF2-081 GEN
Solar/Wind Harmer
13.082
961611AG1-000B GEN
Solar/Wind Harmer
4.358
316283AC2-100 C
Solar/Wind Harmer
1.945
970257AG2-171 GEN
Solar/Wind Harmer
7.449
971775AH1-396 GEN
Solar/Wind Harmer
1.402
3144216WINCHST
Adder
0.657
971683AH1-343 GEN
Solar/Wind Harmer
8.441
959311AF2-222 GEN
Solar/Wind Harmer
20.413
3150921YORKTN3
Adder
4.31
315778AD1-151 GEN
Solar/Wind Harmer
16.758
316458AB2-190 GEN2
Solar/Wind Harmer
1.822
3144293JTRSVLE
Adder
0.378
3147133PAMPLIN
Solar/Wind Harmer
-0.053
970133AG2-095 GEN
Solar/Wind Harmer
1.877
316123AC1-075 GEN
Solar/Wind Harmer
1.786
942461AE2-259 GEN
Solar/Wind Harmer
2.267
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316316AC1-027 C
Solar/Wind Harmer
0.799
3151091ELIZAR2
Adder
20.85
313526AB2-022
Solar/Wind Harmer
0.699
3146396TANGLEW
Solar/Wind Harmer
0.477
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
946281AF1-292 GEN
Solar/Wind Harmer
0.578
315800Z1-036_GEN1
Solar/Wind Harmer
6.313
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.585
3143316POE
Solar/Wind Harmer
-0.099
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.059
315733AD1-074 GEN2
Solar/Wind Harmer
5.059
316318V4-068
Solar/Wind Harmer
0.624
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146043SEABORD
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.939
316426AA2-053 GEN
Solar/Wind Harmer
2.514
316463AE2-346 GEN
Solar/Wind Harmer
0.402
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.561
315833AF1-017_GEN
Solar/Wind Harmer
4.726
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.097
970831AG2-522 GEN
Solar/Wind Harmer
12.177
316174AB2-169 GEN
Solar/Wind Harmer
3.748
316210AC1-098 GEN
Solar/Wind Harmer
3.803
316274AC1-208 GEN
Solar/Wind Harmer
2.608
970657AG2-426 GEN
Solar/Wind Harmer
1.505
316327AA2-057 GEN
Solar/Wind Harmer
2.397
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.301
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316236AE1-162_GEN
Solar/Wind Harmer
0.698
971445AH1-216 GEN
Solar/Wind Harmer
14.278
316238AB2-078_GEN
Solar/Wind Harmer
0.672
316239AB2-077_GEN
Solar/Wind Harmer
0.672
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.014
3151201GRAVEL4
Adder
13.956
3151221GRAVEL6
Adder
13.94
3151191GRAVEL3
Adder
13.779
3151211GRAVEL5
Adder
13.779
315839AE2-212 C
Solar/Wind Harmer
0.63
3144303KENBRDG
Solar/Wind Harmer
-0.016
315697AD1-025 GEN
Solar/Wind Harmer
3.907
970683AG2-441 GEN
Solar/Wind Harmer
13.273
970681AG2-440 GEN
Solar/Wind Harmer
8.81
313527AB2-043 GEN
Solar/Wind Harmer
3.615
962561AG1-105 GEN
Solar/Wind Harmer
12.496
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
964791AG1-342 GEN
Solar/Wind Harmer
4.743
316118AC1-105 GEN
Solar/Wind Harmer
1.522
316248AF1-058 C
Solar/Wind Harmer
0.666
970323AG2-213 GEN
Solar/Wind Harmer
9.932
316033AB2-134 GEN
Solar/Wind Harmer
6.234
970301AG2-198 GEN
Solar/Wind Harmer
9.481
316240AF1-291 C
Solar/Wind Harmer
0.559
958211AF2-115 GEN
Solar/Wind Harmer
2.779
3144293JTRSVLE
Adder
0.378
944641AF1-129 GEN
Adder
75.217
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
942751AE2-291 GEN
Solar/Wind Harmer
9.688
3143526WINTERP
Solar/Wind Helper
1.338
316045AC1-158 PL2
Solar/Wind Helper
4.195
316450AC1-158 RIC
Solar/Wind Helper
0.35
316319Z2-044 C
Solar/Wind Harmer
1.3
3146233WITAKRS
Solar/Wind Harmer
-0.093
961671AG1-007 GEN
Solar/Wind Harmer
0.296
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.695
316359AB2-059 GEN
Solar/Wind Harmer
3.131
3142053HEARTS
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
-0.023
946301AF1-294 GEN
Solar/Wind Harmer
4.557
961791AG1-021 GEN
Solar/Wind Harmer
2.223
270455AD2-022 GEN
Solar/Wind Harmer
3.162
270457AD2-023 GEN
Solar/Wind Harmer
1.603
316382AG1-145 C
Solar/Wind Harmer
0.474
316159AE1-175 C
Solar/Wind Harmer
0.422
957831AF2-077 GEN
Solar/Wind Harmer
0.473
3138283WHITEMARSH
Solar/Wind Harmer
0.024
316233AE1-074 FULL
Solar/Wind Helper
0.393
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145336SMITFLD
Solar/Wind Harmer
-0.092
970401AG2-262 GEN
Solar/Wind Harmer
1.449
316131AB2-060 GEN
Solar/Wind Harmer
2.378
3151171GRAVELC
Adder
2.04
961611AG1-000B GEN
Solar/Wind Harmer
10.214
315785AD2-033 C
Solar/Wind Harmer
4.59
316034AC1-036 C
Solar/Wind Harmer
0.367
3138126ROCKLANDING
Solar/Wind Harmer
0.06
316369SG1_INVT
Solar/Wind Harmer
3.452
971069AG2-661 GEN
Solar/Wind Harmer
2.979
970685AG2-442 GEN
Solar/Wind Harmer
16.038
316132AB2-190 GEN1
Solar/Wind Harmer
1.822
971563AH1-280 GEN
Solar/Wind Harmer
2.223
3144293JTRSVLE
Adder
0.378
3144293JTRSVLE
Adder
0.298
971317AH1-138 GEN
Solar/Wind Harmer
2.205
315671AE2-027_GEN
Solar/Wind Harmer
3
970223AG2-152 GEN
Solar/Wind Harmer
11.476
3146926FARMVIL
Solar/Wind Harmer
-0.008
3143226MDLTHAN
Solar/Wind Helper
0.346
3143526WINTERP
Solar/Wind Helper
1.338
316447AC1-158 HLD
Solar/Wind Helper
2.885
316044AC1-158 PL1
Solar/Wind Helper
1.311
LAGNLTFEXP_LAGN->PJM
CLTF
9.367
CPLELTFEXP_CPLE->PJM
CLTF
14.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.191
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.624
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.621
TVALTFEXP_TVA->PJM
CLTF
4.676
MECLTFEXP_MEC->PJM
CLTF
4.362
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.232
LGEELTFEXP_LGEE->PJM
CLTF
1.551
WECLTFEXP_WEC->PJM
CLTF
0.796
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 11.48 MW.

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.58 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:3963.04
MW Contribution:
3.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.21
970413AG2-270 GEN
50/50
23.726
3151391GASTONA
50/50
0.609
3151411GASTONB
50/50
0.609
3151101ELIZAR3
50/50
22.435
944011AF1-069 GEN
Solar/Wind Harmer
22.185
315242AE2-183_GT2
50/50
5.349
315241AE2-183_GT1
50/50
5.335
972185AH1-677 GEN
50/50
19.334
3151041BRUNSWICKG3
50/50
4.21
972187AH1-678 GEN
50/50
9.66
970933AG2-581 GEN
Solar/Wind Harmer
32.109
970099AG2-077 GEN
Solar/Wind Harmer
37.713
3144356SAPONY
Solar/Wind Harmer
0.991
316315AB2-025 C
Solar/Wind Harmer
0.764
315687AD1-152 GEN
Solar/Wind Harmer
3.218
316294AC1-161 GEN
Solar/Wind Harmer
8.598
316365GEN2_N
Solar/Wind Harmer
1.784
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.725
316339AD2-160 GEN
Solar/Wind Harmer
1.739
316388AE2-253 GEN
Solar/Wind Harmer
1.739
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.05
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
962571AG1-106 GEN
Solar/Wind Harmer
3.682
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.634
316433W1029_GEN2
Solar/Wind Harmer
4.634
316435W1029_GEN3
Solar/Wind Harmer
4.634
313506AB2-031 GEN
Solar/Wind Harmer
2.049
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3150991CHESPKB
Adder
2.375
3150991CHESPKB
Adder
2.318
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
3145796HORNRTN
Solar/Wind Harmer
-0.076
315614AA2-178 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
2.991
3145783HORNRTN
Solar/Wind Harmer
2.393
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
316065AD1-022 GEN
Solar/Wind Harmer
12.598
3145893MURPHYS
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
5.97
316140AB2-099
Solar/Wind Harmer
0.169
315243AE2-183_GT3
50/50
5.349
3151051BRUNSWICKS1
50/50
8.74
3151021BRUNSWICKG1
50/50
4.21
971451AH1-221 GEN
50/50
12.785
3151531CLOVER1
50/50
5.448
3151391GASTONA
50/50
0.609
3151411GASTONB
50/50
0.609
941031AE2-094 GEN
Solar/Wind Harmer
70.804
940641AE2-051 GEN
Solar/Wind Harmer
34.785
970919AG2-571 GEN
Solar/Wind Harmer
10.919
939411AE1-173 GEN
Solar/Wind Harmer
171.631
970087AG2-069 GEN
Solar/Wind Harmer
31.895
957481AF2-042 GEN
Solar/Wind Harmer
94.283
315693AD1-088 GEN
Solar/Wind Harmer
13.936
315773AC2-141 GEN
Solar/Wind Harmer
11.125
316023GEN1_S
Solar/Wind Harmer
1.784
944591AF1-124 GEN
Solar/Wind Harmer
120.171
3146456SLIGO L269
Solar/Wind Harmer
-0.026
319010AE1-072 C
Solar/Wind Harmer
5.212
960081AF2-299 GEN
Solar/Wind Harmer
2.904
316087AB2-174 GEN
Solar/Wind Harmer
3.651
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.026
316375AC2-012 GEN
Solar/Wind Harmer
8.809
316036AC1-147 C
Solar/Wind Harmer
0.685
3150981CHESPKA
Adder
2.831
315611Z1-036_GEN2
Solar/Wind Harmer
6.291
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.043
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.739
315607AA1-063A GEN
Solar/Wind Harmer
2.543
315737AD1-076 GEN
Solar/Wind Harmer
4.783
3145783HORNRTN
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.297
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.747
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.379
3145683EARLEYS
Solar/Wind Harmer
-0.025
970917AG2-570 GEN
Solar/Wind Harmer
86.258
316478AD1-087 GEN
Solar/Wind Harmer
2.463
944581AF1-123 GEN
Solar/Wind Harmer
119.739
944601AF1-125 GEN
Solar/Wind Harmer
117.871
316017AA1-139 ULT1
Solar/Wind Harmer
2.086
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.989
966621AG1-532 GEN
Solar/Wind Harmer
0.524
316320Y1-086
Solar/Wind Harmer
1.506
3142956BIRDNECK
Solar/Wind Harmer
1.379
316321Z2-027
Solar/Wind Harmer
0.691
316011AB1-132 GEN
Solar/Wind Harmer
5.349
3146516WINFALL
Solar/Wind Harmer
-0.026
316305AF2-043 C
Solar/Wind Harmer
0.769
316246AF1-032 C
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
3.559
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146376EDENTON
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.31
315735AD1-075 GEN1
Solar/Wind Harmer
2.543
3156081AA2-088 GEN
Solar/Wind Harmer
8.171
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
315244AE2-183_ST
50/50
9.288
963041AG1-153 GEN
50/50
8.523
3151541CLOVER2
50/50
5.406
315779AE2-040
50/50
3.528
970533AG2-339 GEN
Solar/Wind Harmer
25.394
970673AG2-436 GEN
Solar/Wind Harmer
81.496
971967AH1-528 GEN
Solar/Wind Harmer
66.89
970085AG2-068 GEN
Solar/Wind Harmer
21.263
970581AG2-369 GEN
Solar/Wind Harmer
18.286
316486AD2-202 GEN
Solar/Wind Harmer
0.721
315814AE2-033 C
Solar/Wind Harmer
26.361
316018AA1-139 ULT2
Solar/Wind Harmer
2.209
957871AF2-081 GEN
Solar/Wind Harmer
12.927
3146406KITTY HAWK
Solar/Wind Harmer
0.021
946281AF1-292 GEN
Solar/Wind Harmer
0.578
313526AB2-022
Solar/Wind Harmer
0.692
316316AC1-027 C
Solar/Wind Harmer
0.787
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
315652AC1-086 GEN
Solar/Wind Harmer
28.812
3151081ELIZAR1
Adder
20.876
3151091ELIZAR2
Adder
20.513
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.291
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
3137643SOCKMAN
Solar/Wind Harmer
-0.101
316426AA2-053 GEN
Solar/Wind Harmer
2.543
3146043SEABORD
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.088
315733AD1-074 GEN2
Solar/Wind Harmer
5.088
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.019
316318V4-068
Solar/Wind Harmer
0.627
3145893MURPHYS
Solar/Wind Harmer
-0.068
3145893MURPHYS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.406
3145513AHOSKIE
Solar/Wind Harmer
0.219
961941AG1-037 GEN
Solar/Wind Harmer
0.189
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.05
316317KELFORD C
Solar/Wind Harmer
1.158
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145963POPLR C
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.16
315722AD1-056 GEN
Solar/Wind Harmer
8.818
3145933PARMELE
Solar/Wind Harmer
-0.024
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.511
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.016
316420AA1-050 GEN
Solar/Wind Harmer
2.773
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.653
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316222AC1-221 GEN
Solar/Wind Harmer
2.255
970657AG2-426 GEN
Solar/Wind Harmer
4.499
316283AC2-100 C
Solar/Wind Harmer
2.096
3145336SMITFLD
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.302
316003AC1-222 GEN
Solar/Wind Harmer
2.114
315813AE1-149 C
Solar/Wind Harmer
13.05
970257AG2-171 GEN
Solar/Wind Harmer
7.736
971775AH1-396 GEN
Solar/Wind Harmer
1.456
959311AF2-222 GEN
Solar/Wind Harmer
21.219
971683AH1-343 GEN
Solar/Wind Harmer
8.711
3151171GRAVELC
Adder
2.503
3144216WINCHST
Adder
0.639
961611AG1-000B GEN
Solar/Wind Harmer
3.979
3150921YORKTN3
Adder
4.215
3144293JTRSVLE
Adder
0.395
3147133PAMPLIN
Solar/Wind Harmer
-0.056
316123AC1-075 GEN
Solar/Wind Harmer
1.825
315778AD1-151 GEN
Solar/Wind Harmer
14.444
942461AE2-259 GEN
Solar/Wind Harmer
2.398
316458AB2-190 GEN2
Solar/Wind Harmer
1.527
3146926FARMVIL
Solar/Wind Harmer
-0.008
970133AG2-095 GEN
Solar/Wind Harmer
1.481
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
970831AG2-522 GEN
Solar/Wind Harmer
12.46
3146033SCOT NK
Solar/Wind Harmer
-0.099
316210AC1-098 GEN
Solar/Wind Harmer
3.888
316274AC1-208 GEN
Solar/Wind Harmer
2.67
316174AB2-169 GEN
Solar/Wind Harmer
3.819
316327AA2-057 GEN
Solar/Wind Harmer
2.473
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.661
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
12.089
315835AF2-110_GEN
Solar/Wind Harmer
3.14
315724AD1-057 GEN
Solar/Wind Harmer
4.85
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.024
316005AA1-067
Solar/Wind Harmer
0.493
3145493TOT1
Solar/Wind Harmer
0.376
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.15
961601AG1-000A GEN
Solar/Wind Harmer
9.533
316049AB1-081 GEN
Solar/Wind Harmer
2.608
316263AC1-034 GEN
Solar/Wind Harmer
11.364
316349AD2-085 GEN
Solar/Wind Harmer
2.126
316237AB2-079_GEN
Solar/Wind Harmer
0.693
316248AF1-058 C
Solar/Wind Harmer
0.692
316118AC1-105 GEN
Solar/Wind Harmer
1.578
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
4.913
962561AG1-105 GEN
Solar/Wind Harmer
12.935
313527AB2-043 GEN
Solar/Wind Harmer
3.731
316083AB2-161 GEN
Solar/Wind Harmer
3.579
970323AG2-213 GEN
Solar/Wind Harmer
10.315
970301AG2-198 GEN
Solar/Wind Harmer
9.881
958211AF2-115 GEN
Solar/Wind Harmer
2.906
3144293JTRSVLE
Adder
0.395
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316093AE2-104_GEN
Solar/Wind Harmer
7.304
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.009
316129AC1-054 GEN
Solar/Wind Harmer
2.174
3145963POPLR C
Solar/Wind Harmer
-0.025
971065AG2-659 GEN
Solar/Wind Harmer
12.418
3146293MARTNCO
Solar/Wind Harmer
0.152
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316319Z2-044 C
Solar/Wind Harmer
1.347
3146233WITAKRS
Solar/Wind Harmer
-0.097
316494AC1-189 GEN
Solar/Wind Harmer
2.622
961671AG1-007 GEN
Solar/Wind Harmer
0.307
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.721
316359AB2-059 GEN
Solar/Wind Harmer
3.26
3142053HEARTS
Solar/Wind Harmer
0.285
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316072AD1-144
Solar/Wind Harmer
0.488
970401AG2-262 GEN
Solar/Wind Harmer
1.501
316131AB2-060 GEN
Solar/Wind Harmer
2.455
3145336SMITFLD
Solar/Wind Harmer
-0.088
316381AD1-082 GEN
Solar/Wind Harmer
2.018
315785AD2-033 C
Solar/Wind Harmer
4.761
316034AC1-036 C
Solar/Wind Harmer
0.381
3151171GRAVELC
Adder
1.903
970685AG2-442 GEN
Solar/Wind Harmer
16.738
3138126ROCKLANDING
Solar/Wind Harmer
0.058
961611AG1-000B GEN
Solar/Wind Harmer
9.325
971563AH1-280 GEN
Solar/Wind Harmer
2.324
3144293JTRSVLE
Adder
0.395
3144293JTRSVLE
Adder
0.312
971317AH1-138 GEN
Solar/Wind Harmer
2.163
316369SG1_INVT
Solar/Wind Harmer
3.029
971069AG2-661 GEN
Solar/Wind Harmer
2.568
315671AE2-027_GEN
Solar/Wind Harmer
2.77
316132AB2-190 GEN1
Solar/Wind Harmer
1.527
3146926FARMVIL
Solar/Wind Harmer
-0.008
970223AG2-152 GEN
Solar/Wind Harmer
11.904
270016AE1-250 BESS
Solar/Wind Harmer
1.95
3143226MDLTHAN
Solar/Wind Helper
0.287
316447AC1-158 HLD
Solar/Wind Helper
2.744
316044AC1-158 PL1
Solar/Wind Helper
1.247
315833AF1-017_GEN
Solar/Wind Harmer
4.547
316238AB2-078_GEN
Solar/Wind Harmer
0.693
316239AB2-077_GEN
Solar/Wind Harmer
0.693
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
3143316POE
Solar/Wind Harmer
-0.09
970657AG2-426 GEN
Solar/Wind Harmer
1.404
316236AE1-162_GEN
Solar/Wind Harmer
0.667
971445AH1-216 GEN
Solar/Wind Harmer
13.602
3144303KENBRDG
Solar/Wind Harmer
-0.016
3151201GRAVEL4
Adder
13.022
3151221GRAVEL6
Adder
13.007
3151191GRAVEL3
Adder
12.858
3151211GRAVEL5
Adder
12.858
970683AG2-441 GEN
Solar/Wind Harmer
13.83
970681AG2-440 GEN
Solar/Wind Harmer
9.179
270455AD2-022 GEN
Solar/Wind Harmer
3.412
270457AD2-023 GEN
Solar/Wind Harmer
1.73
946301AF1-294 GEN
Solar/Wind Harmer
4.765
961791AG1-021 GEN
Solar/Wind Harmer
2.324
315839AE2-212 C
Solar/Wind Harmer
0.522
315697AD1-025 GEN
Solar/Wind Harmer
3.428
3147133PAMPLIN
Solar/Wind Harmer
-0.014
316033AB2-134 GEN
Solar/Wind Harmer
5.47
942751AE2-291 GEN
Solar/Wind Harmer
9.842
316240AF1-291 C
Solar/Wind Harmer
0.422
944641AF1-129 GEN
Adder
54.781
270013AE1-250 PV
Solar/Wind Harmer
1.95
316045AC1-158 PL2
Solar/Wind Helper
3.991
316450AC1-158 RIC
Solar/Wind Helper
0.333
316382AG1-145 C
Solar/Wind Harmer
0.463
316159AE1-175 C
Solar/Wind Harmer
0.412
957831AF2-077 GEN
Solar/Wind Harmer
0.463
3138283WHITEMARSH
Solar/Wind Harmer
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
10.641
CPLELTFEXP_CPLE->PJM
CLTF
15.812
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.662
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.262
TVALTFEXP_TVA->PJM
CLTF
5.26
MECLTFEXP_MEC->PJM
CLTF
4.515
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.146
LGEELTFEXP_LGEE->PJM
CLTF
1.49
WECLTFEXP_WEC->PJM
CLTF
0.784
MW Contribution was adjusted by a CIR Transfer Study.  Original MW Contribution was 11.9 MW.

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.61 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5316.1
MW Contribution:
12.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970085AG2-068 GEN
Solar/Wind Harmer
31.685
970581AG2-369 GEN
Solar/Wind Harmer
27.249
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
946301AF1-294 GEN
Solar/Wind Harmer
5.342
961791AG1-021 GEN
Solar/Wind Harmer
2.599
970831AG2-522 GEN
Solar/Wind Harmer
8.162
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
941031AE2-094 GEN
Solar/Wind Harmer
118.958
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316131AB2-060 GEN
Solar/Wind Harmer
0.892
315785AD2-033 C
Solar/Wind Harmer
2.263
316034AC1-036 C
Solar/Wind Harmer
0.019
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
970223AG2-152 GEN
Solar/Wind Harmer
12.898
3147123OTTER R
Solar/Wind Harmer
0.097
3146776BUCKING
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.63
270030AE2-140 GEN
Solar/Wind Harmer
14.713
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
944011AF1-069 GEN
Solar/Wind Harmer
38.868
970917AG2-570 GEN
Solar/Wind Harmer
53.986
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
971683AH1-343 GEN
Solar/Wind Harmer
11.193
316283AC2-100 C
Solar/Wind Harmer
0.593
964241AG1-285 GEN
Solar/Wind Harmer
18.935
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3146926FARMVIL
Solar/Wind Harmer
0.152
3146776BUCKING
Solar/Wind Harmer
0.058
3147312GRETNA
Solar/Wind Harmer
0.029
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
51.56
970099AG2-077 GEN
Solar/Wind Harmer
57.909
970301AG2-198 GEN
Solar/Wind Harmer
15.175
316118AC1-105 GEN
Solar/Wind Harmer
0.853
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.163
962561AG1-105 GEN
Solar/Wind Harmer
15.161
970323AG2-213 GEN
Solar/Wind Harmer
11.876
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
316263AC1-034 GEN
Solar/Wind Harmer
4.683
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
TVALTFEXP_TVA->PJM
CLTF
7.703
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5107.87
MW Contribution:
12.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970085AG2-068 GEN
Solar/Wind Harmer
31.685
970581AG2-369 GEN
Solar/Wind Harmer
27.249
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
946301AF1-294 GEN
Solar/Wind Harmer
5.342
961791AG1-021 GEN
Solar/Wind Harmer
2.599
970831AG2-522 GEN
Solar/Wind Harmer
8.162
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316131AB2-060 GEN
Solar/Wind Harmer
0.892
315785AD2-033 C
Solar/Wind Harmer
2.263
316034AC1-036 C
Solar/Wind Harmer
0.019
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
970223AG2-152 GEN
Solar/Wind Harmer
12.898
3147123OTTER R
Solar/Wind Harmer
0.097
3146776BUCKING
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.63
270030AE2-140 GEN
Solar/Wind Harmer
14.713
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
316316AC1-027 C
Solar/Wind Helper
0.639
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
970917AG2-570 GEN
Solar/Wind Harmer
53.986
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
971683AH1-343 GEN
Solar/Wind Harmer
11.193
316283AC2-100 C
Solar/Wind Harmer
0.593
964241AG1-285 GEN
Solar/Wind Harmer
18.935
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3146926FARMVIL
Solar/Wind Harmer
0.152
3146776BUCKING
Solar/Wind Harmer
0.058
3147312GRETNA
Solar/Wind Harmer
0.029
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.558
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
51.56
970099AG2-077 GEN
Solar/Wind Harmer
57.909
970301AG2-198 GEN
Solar/Wind Harmer
15.175
316118AC1-105 GEN
Solar/Wind Harmer
0.853
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.163
962561AG1-105 GEN
Solar/Wind Harmer
15.161
970323AG2-213 GEN
Solar/Wind Harmer
11.876
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
316263AC1-034 GEN
Solar/Wind Harmer
4.683
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316294AC1-161 GEN
Solar/Wind Helper
8.161
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
TVALTFEXP_TVA->PJM
CLTF
7.703
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.11 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5851.06
MW Contribution:
18.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
941031AE2-094 GEN
Solar/Wind Harmer
136.066
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
970401AG2-262 GEN
Solar/Wind Harmer
2.354
316131AB2-060 GEN
Solar/Wind Harmer
3.464
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.464
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.096
270030AE2-140 GEN
Solar/Wind Harmer
21.088
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970673AG2-436 GEN
Solar/Wind Harmer
158.752
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970085AG2-068 GEN
Solar/Wind Harmer
41.719
970581AG2-369 GEN
Solar/Wind Harmer
35.878
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
946301AF1-294 GEN
Solar/Wind Harmer
7.794
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
270457AD2-023 GEN
Solar/Wind Harmer
2.542
970831AG2-522 GEN
Solar/Wind Harmer
10.747
971845AH1-439 GEN
Solar/Wind Harmer
10.037
316322AB2-045
Solar/Wind Harmer
0.605
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
944011AF1-069 GEN
Solar/Wind Harmer
42.634
970917AG2-570 GEN
Solar/Wind Harmer
170.595
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
971683AH1-343 GEN
Solar/Wind Harmer
14.738
316283AC2-100 C
Solar/Wind Harmer
3.207
964241AG1-285 GEN
Solar/Wind Harmer
24.931
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
67.888
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
970301AG2-198 GEN
Solar/Wind Harmer
19.981
316248AF1-058 C
Solar/Wind Harmer
1.167
316118AC1-105 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.704
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.796
270013AE1-250 PV
Solar/Wind Harmer
3.04
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
316263AC1-034 GEN
Solar/Wind Harmer
6.491
961601AG1-000A GEN
Solar/Wind Harmer
5.315
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
TVALTFEXP_TVA->PJM
CLTF
7.703
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5822.84
MW Contribution:
18.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.101
315244AE2-183_ST
50/50
18.346
3151541CLOVER2
50/50
10.523
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
141.954
970673AG2-436 GEN
Solar/Wind Harmer
157.592
970533AG2-339 GEN
Solar/Wind Harmer
48.444
970085AG2-068 GEN
Solar/Wind Harmer
41.425
970581AG2-369 GEN
Solar/Wind Harmer
35.626
316486AD2-202 GEN
Solar/Wind Harmer
1.403
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.978
316239AB2-077_GEN
Solar/Wind Harmer
0.978
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.753
970681AG2-440 GEN
Solar/Wind Harmer
14.438
946301AF1-294 GEN
Solar/Wind Harmer
7.781
961791AG1-021 GEN
Solar/Wind Harmer
3.796
270455AD2-022 GEN
Solar/Wind Harmer
4.996
270457AD2-023 GEN
Solar/Wind Harmer
2.533
970831AG2-522 GEN
Solar/Wind Harmer
10.881
971845AH1-439 GEN
Solar/Wind Harmer
9.987
3151051BRUNSWICKS1
50/50
17.536
3151021BRUNSWICKG1
50/50
8.447
971451AH1-221 GEN
50/50
25.651
315243AE2-183_GT3
50/50
10.565
3151531CLOVER1
50/50
10.604
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.016
3151561HALLBR1
50/50
0.398
941031AE2-094 GEN
Solar/Wind Harmer
135.072
970919AG2-571 GEN
Solar/Wind Harmer
21.441
970087AG2-069 GEN
Solar/Wind Harmer
62.138
3151041BRUNSWICKG3
50/50
8.447
972187AH1-678 GEN
50/50
19.381
315242AE2-183_GT2
50/50
10.565
315241AE2-183_GT1
50/50
10.537
972185AH1-677 GEN
50/50
38.19
970909AG2-566 GEN
50/50
3.771
3152661PLYWOOD A
50/50
0.739
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.158
3144293JTRSVLE
50/50
0.685
970933AG2-581 GEN
Solar/Wind Harmer
67.393
970099AG2-077 GEN
Solar/Wind Harmer
75.739
315687AD1-152 GEN
Solar/Wind Harmer
5.976
970301AG2-198 GEN
Solar/Wind Harmer
19.863
316248AF1-058 C
Solar/Wind Harmer
1.162
316118AC1-105 GEN
Solar/Wind Harmer
2.561
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.689
962561AG1-105 GEN
Solar/Wind Harmer
19.93
316237AB2-079_GEN
Solar/Wind Harmer
0.978
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.633
3151031BRUNSWICKG2
50/50
8.447
970413AG2-270 GEN
50/50
46.18
3144293JTRSVLE
50/50
0.685
944011AF1-069 GEN
Solar/Wind Harmer
42.323
970917AG2-570 GEN
Solar/Wind Harmer
169.383
316478AD1-087 GEN
Solar/Wind Harmer
4.79
316003AC1-222 GEN
Solar/Wind Harmer
3.555
316222AC1-221 GEN
Solar/Wind Harmer
3.451
971683AH1-343 GEN
Solar/Wind Harmer
14.679
316283AC2-100 C
Solar/Wind Harmer
3.195
964241AG1-285 GEN
Solar/Wind Harmer
24.949
970257AG2-171 GEN
Solar/Wind Harmer
11.725
971775AH1-396 GEN
Solar/Wind Harmer
2.206
959311AF2-222 GEN
Solar/Wind Harmer
32.493
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.389
316123AC1-075 GEN
Solar/Wind Harmer
3.093
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
5.986
958211AF2-115 GEN
Solar/Wind Harmer
4.745
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.731
270013AE1-250 PV
Solar/Wind Harmer
3.03
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
942671AE2-283 GEN
Solar/Wind Harmer
5.365
316049AB1-081 GEN
Solar/Wind Harmer
1.526
316263AC1-034 GEN
Solar/Wind Harmer
6.648
961601AG1-000A GEN
Solar/Wind Harmer
5.451
316294AC1-161 GEN
Solar/Wind Helper
8.256
316185AD1-033 GEN
Solar/Wind Helper
1.908
3145506HICKORY
Solar/Wind Helper
1.594
3145506HICKORY
Solar/Wind Helper
0.956
3145506HICKORY
Solar/Wind Helper
0.239
316339AD2-160 GEN
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.482
3137176SLIGO L2192
Solar/Wind Helper
1.514
3130086AYDLETT
Solar/Wind Helper
1.503
316033AB2-134 GEN
Solar/Wind Helper
1.265
316349AD2-085 GEN
Solar/Wind Helper
1.611
3146386ELIZ CT
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.469
316156AD2-030 GEN
Solar/Wind Helper
0.52
315666AE1-190 GEN
Solar/Wind Helper
0.462
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
315976AC1-164 GENA
Solar/Wind Helper
4.26
316169AC1-164_GENC
Solar/Wind Helper
3.68
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
316312AB1-027
Solar/Wind Helper
0.586
3143526WINTERP
Solar/Wind Helper
1.571
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.393
3144356SAPONY
Solar/Wind Helper
0.518
316315AB2-025 C
Solar/Wind Helper
0.441
957481AF2-042 GEN
Solar/Wind Harmer
189.348
315693AD1-088 GEN
Solar/Wind Harmer
27.647
970401AG2-262 GEN
Solar/Wind Harmer
2.349
316131AB2-060 GEN
Solar/Wind Harmer
3.468
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.775
971563AH1-280 GEN
Solar/Wind Harmer
3.796
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.632
316129AC1-054 GEN
Solar/Wind Harmer
2.075
970223AG2-152 GEN
Solar/Wind Harmer
18.332
270016AE1-250 BESS
Solar/Wind Harmer
3.03
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.459
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.074
270030AE2-140 GEN
Solar/Wind Harmer
21.018
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.907
3142053HEARTS
Solar/Wind Harmer
0.167
315773AC2-141 GEN
Solar/Wind Helper
9.714
316375AC2-012 GEN
Solar/Wind Helper
1.078
316036AC1-147 C
Solar/Wind Helper
0.625
3145336SMITFLD
Solar/Wind Helper
1.566
3146456SLIGO L269
Solar/Wind Helper
0.38
319010AE1-072 C
Solar/Wind Helper
4.323
316072AD1-144
Solar/Wind Helper
0.429
316369SG1_INVT
Solar/Wind Helper
1.762
316381AD1-082 GEN
Solar/Wind Helper
1.86
316132AB2-190 GEN1
Solar/Wind Helper
2.044
315671AE2-027_GEN
Solar/Wind Helper
2.846
315662AE1-191 GEN
Solar/Wind Helper
1.847
316280AD1-041 GEN
Solar/Wind Helper
1.154
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.343
315975AC1-164 GENB
Solar/Wind Helper
0.126
316404AE1-155 C
Solar/Wind Helper
2.803
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.287
3146516WINFALL
Solar/Wind Helper
1.015
3146516WINFALL
Solar/Wind Helper
0.313
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.798
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.571
3143226MDLTHAN
Solar/Wind Helper
0.297
315611Z1-036_GEN2
Solar/Wind Helper
1.391
3130156CHOWAN
Solar/Wind Helper
0.24
316217AC1-145 GEN
Solar/Wind Harmer
2.627
316197AC1-042 GEN
Solar/Wind Harmer
1.991
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.084
270336AE1-100 GEN
Solar/Wind Harmer
1.663
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.52
3138543CONSLDL
Solar/Wind Harmer
-0.008
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.274
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.765
3146456SLIGO L269
Solar/Wind Helper
0.38
316305AF2-043 C
Solar/Wind Helper
0.501
316246AF1-032 C
Solar/Wind Helper
0.426
316458AB2-190 GEN2
Solar/Wind Helper
2.044
316320Y1-086
Solar/Wind Helper
0.157
316321Z2-027
Solar/Wind Helper
0.516
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.64
316075AC2-137 C
Solar/Wind Helper
0.493
316077AC2-138 C
Solar/Wind Helper
0.302
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.462
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.782
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.345
3146376EDENTON
Solar/Wind Helper
0.239
316322AB2-045
Solar/Wind Harmer
0.602
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
270069AE2-166 C O1
Solar/Wind Harmer
8.499
316316AC1-027 C
Solar/Wind Helper
0.642
316236AE1-162_GEN
Solar/Wind Helper
0.528
316018AA1-139 ULT2
Solar/Wind Helper
1.661
3143316POE
Solar/Wind Helper
1.484
316382AG1-145 C
Solar/Wind Helper
0.496
316159AE1-175 C
Solar/Wind Helper
0.56
315697AD1-025 GEN
Solar/Wind Helper
4.181
957831AF2-077 GEN
Solar/Wind Helper
0.492
315839AE2-212 C
Solar/Wind Helper
0.483
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.461
3141873WAN 176
Solar/Wind Helper
0.069
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316233AE1-074 FULL
Solar/Wind Helper
0.461
316468AD1-105 GEN
Solar/Wind Helper
1.325
315800Z1-036_GEN1
Solar/Wind Helper
1.391
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.386
CPLELTFEXP_CPLE->PJM
CLTF
20.605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.197
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.424
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.302
TVALTFEXP_TVA->PJM
CLTF
7.676
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.47
LGEELTFEXP_LGEE->PJM
CLTF
2.835
WECLTFEXP_WEC->PJM
CLTF
1.484
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.34 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5462.74
MW Contribution:
18.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.509
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
970917AG2-570 GEN
Solar/Wind Harmer
170.595
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
971683AH1-343 GEN
Solar/Wind Harmer
14.738
316283AC2-100 C
Solar/Wind Harmer
3.207
964241AG1-285 GEN
Solar/Wind Harmer
24.931
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
3151051BRUNSWICKS1
50/50
17.665
3151021BRUNSWICKG1
50/50
8.509
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
971629AH1-314 GEN
50/50
19.08
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
970401AG2-262 GEN
Solar/Wind Harmer
2.354
316131AB2-060 GEN
Solar/Wind Harmer
3.464
315785AD2-033 C
Solar/Wind Harmer
7.115
316034AC1-036 C
Solar/Wind Harmer
0.578
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147123OTTER R
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.007
270018AE2-047 C O1
Solar/Wind Harmer
1.464
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.096
270030AE2-140 GEN
Solar/Wind Harmer
21.088
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
315773AC2-141 GEN
Solar/Wind Helper
9.603
316375AC2-012 GEN
Solar/Wind Helper
1.073
316036AC1-147 C
Solar/Wind Helper
0.622
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
315671AE2-027_GEN
Solar/Wind Helper
3.055
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316072AD1-144
Solar/Wind Helper
0.428
316369SG1_INVT
Solar/Wind Helper
1.805
316132AB2-190 GEN1
Solar/Wind Helper
2.11
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
3138133OCRAN
Solar/Wind Helper
0.206
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.302
3151041BRUNSWICKG3
50/50
8.509
972187AH1-678 GEN
50/50
19.524
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970535AG2-341 GEN
50/50
5.153
3144293JTRSVLE
50/50
0.686
970933AG2-581 GEN
Solar/Wind Harmer
67.888
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
970301AG2-198 GEN
Solar/Wind Harmer
19.981
316248AF1-058 C
Solar/Wind Harmer
1.167
316118AC1-105 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.704
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.796
270013AE1-250 PV
Solar/Wind Harmer
3.04
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
316263AC1-034 GEN
Solar/Wind Harmer
6.491
961601AG1-000A GEN
Solar/Wind Harmer
5.315
316294AC1-161 GEN
Solar/Wind Helper
8.161
316185AD1-033 GEN
Solar/Wind Helper
1.897
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316240AF1-291 C
Solar/Wind Helper
0.501
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316487AF1-042 GEN
Solar/Wind Helper
0.338
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
316435W1029_GEN3
Solar/Wind Helper
1.293
316312AB1-027
Solar/Wind Helper
0.598
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3147312GRETNA
Solar/Wind Harmer
-0.003
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
316305AF2-043 C
Solar/Wind Helper
0.5
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316320Y1-086
Solar/Wind Helper
0.157
3142946ENON
Solar/Wind Helper
0.114
316321Z2-027
Solar/Wind Helper
0.514
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.826
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
316337AD2-073 GEN
Solar/Wind Helper
0.479
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
3143526WINTERP
Solar/Wind Helper
1.594
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
963041AG1-153 GEN
50/50
17.227
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151601KERR 3
50/50
0.597
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
3151631KERR 6
50/50
0.597
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970085AG2-068 GEN
Solar/Wind Harmer
41.719
970581AG2-369 GEN
Solar/Wind Harmer
35.878
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
946301AF1-294 GEN
Solar/Wind Harmer
7.794
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
270457AD2-023 GEN
Solar/Wind Harmer
2.542
970831AG2-522 GEN
Solar/Wind Harmer
10.747
971845AH1-439 GEN
Solar/Wind Harmer
10.037
316322AB2-045
Solar/Wind Harmer
0.605
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316316AC1-027 C
Solar/Wind Helper
0.639
316236AE1-162_GEN
Solar/Wind Helper
0.53
315839AE2-212 C
Solar/Wind Helper
0.524
316018AA1-139 ULT2
Solar/Wind Helper
1.653
315697AD1-025 GEN
Solar/Wind Helper
4.281
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
957831AF2-077 GEN
Solar/Wind Helper
0.494
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141873WAN 176
Solar/Wind Helper
0.07
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
316468AD1-105 GEN
Solar/Wind Helper
1.353
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
TVALTFEXP_TVA->PJM
CLTF
7.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.29 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:2980.61
MW Contribution:
11.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
7.987
3151051BRUNSWICKS1
50/50
8.582
3151021BRUNSWICKG1
50/50
4.134
971451AH1-221 GEN
50/50
12.554
315243AE2-183_GT3
50/50
3.866
3151591KERR 2
50/50
0.435
3151641KERR 7
50/50
0.435
3144293JTRSVLE
50/50
0.518
3144293JTRSVLE
50/50
0.409
971629AH1-314 GEN
50/50
11.606
957481AF2-042 GEN
Solar/Wind Harmer
144.085
315693AD1-088 GEN
Solar/Wind Harmer
21.044
970919AG2-571 GEN
Solar/Wind Harmer
10.571
970087AG2-069 GEN
Solar/Wind Harmer
30.719
970401AG2-262 GEN
Solar/Wind Harmer
1.701
316131AB2-060 GEN
Solar/Wind Harmer
2.562
315785AD2-033 C
Solar/Wind Harmer
5.309
316034AC1-036 C
Solar/Wind Harmer
0.432
970685AG2-442 GEN
Solar/Wind Harmer
20.206
971563AH1-280 GEN
Solar/Wind Harmer
2.874
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.225
316129AC1-054 GEN
Solar/Wind Harmer
1.517
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.336
315773AC2-141 GEN
Solar/Wind Helper
5.481
315671AE2-027_GEN
Solar/Wind Helper
1.833
970413AG2-270 GEN
50/50
34.783
3151031BRUNSWICKG2
50/50
4.134
3144293JTRSVLE
50/50
0.518
316478AD1-087 GEN
Solar/Wind Harmer
3.607
970917AG2-570 GEN
Solar/Wind Harmer
83.508
316003AC1-222 GEN
Solar/Wind Harmer
2.539
971683AH1-343 GEN
Solar/Wind Harmer
10.454
964241AG1-285 GEN
Solar/Wind Harmer
18.498
970257AG2-171 GEN
Solar/Wind Harmer
8.769
971775AH1-396 GEN
Solar/Wind Harmer
1.65
959311AF2-222 GEN
Solar/Wind Harmer
24.346
3147133PAMPLIN
Solar/Wind Harmer
-0.071
942461AE2-259 GEN
Solar/Wind Harmer
3.379
3146926FARMVIL
Solar/Wind Harmer
-0.013
316222AC1-221 GEN
Solar/Wind Harmer
2.214
316283AC2-100 C
Solar/Wind Harmer
2.042
316123AC1-075 GEN
Solar/Wind Harmer
2.185
3146776BUCKING
Solar/Wind Harmer
-0.005
3151041BRUNSWICKG3
50/50
4.134
972187AH1-678 GEN
50/50
9.485
970909AG2-566 GEN
50/50
2.902
3152661PLYWOOD A
50/50
0.531
315242AE2-183_GT2
50/50
3.866
315241AE2-183_GT1
50/50
3.856
972185AH1-677 GEN
50/50
13.975
3151581KERR 1
50/50
0.155
970535AG2-341 GEN
50/50
3.78
3144293JTRSVLE
50/50
0.518
970933AG2-581 GEN
Solar/Wind Harmer
51.867
970099AG2-077 GEN
Solar/Wind Harmer
57.634
315687AD1-152 GEN
Solar/Wind Harmer
4.402
970301AG2-198 GEN
Solar/Wind Harmer
15.282
316248AF1-058 C
Solar/Wind Harmer
0.832
316118AC1-105 GEN
Solar/Wind Harmer
1.844
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.568
962561AG1-105 GEN
Solar/Wind Harmer
14.47
316237AB2-079_GEN
Solar/Wind Harmer
0.72
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.693
958211AF2-115 GEN
Solar/Wind Harmer
3.592
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
942751AE2-291 GEN
Solar/Wind Harmer
11.764
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316294AC1-161 GEN
Solar/Wind Helper
4.658
3151541CLOVER2
50/50
7.926
963041AG1-153 GEN
50/50
8.369
315244AE2-183_ST
50/50
6.714
3151601KERR 3
50/50
0.435
3151611KERR 4
50/50
0.435
3151621KERR 5
50/50
0.435
3151631KERR 6
50/50
0.435
971967AH1-528 GEN
Solar/Wind Harmer
109.533
316486AD2-202 GEN
Solar/Wind Harmer
1.056
970085AG2-068 GEN
Solar/Wind Harmer
20.479
970581AG2-369 GEN
Solar/Wind Harmer
17.612
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.72
316239AB2-077_GEN
Solar/Wind Harmer
0.72
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
16.371
970681AG2-440 GEN
Solar/Wind Harmer
10.866
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.874
270455AD2-022 GEN
Solar/Wind Harmer
3.038
270457AD2-023 GEN
Solar/Wind Harmer
1.541
970831AG2-522 GEN
Solar/Wind Harmer
7.961
971845AH1-439 GEN
Solar/Wind Harmer
8.061
316322AB2-045
Solar/Wind Harmer
0.488
970673AG2-436 GEN
Solar/Wind Harmer
30.81
3143316POE
Solar/Wind Helper
1.003
315839AE2-212 C
Solar/Wind Helper
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
8.951
CPLELTFEXP_CPLE->PJM
CLTF
11.798
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.275
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.693
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.467
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
TVALTFEXP_TVA->PJM
CLTF
4.473
MECLTFEXP_MEC->PJM
CLTF
4.621
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.41
LGEELTFEXP_LGEE->PJM
CLTF
1.7
WECLTFEXP_WEC->PJM
CLTF
0.889

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4842.86
MW Contribution:
12.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5245.63
MW Contribution:
17.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5223.84
MW Contribution:
17.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
TVALTFEXP_TVA->PJM
CLTF
7.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5145.98
MW Contribution:
17.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
316033AB2-134 GEN
Solar/Wind Helper
1.145
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
316433W1029_GEN2
Solar/Wind Helper
1.035
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
TVALTFEXP_TVA->PJM
CLTF
7.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3598.36
MW Contribution:
8.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24288905REUSENS
50/50
0.04
970823AG2-518 GEN
50/50
5.732
24290605CLAY-1
50/50
0.17
24290705CLAY-2
50/50
0.17
24684605SMG4
50/50
1.533
24415905BUCK
50/50
0.022
962751AG1-124 GEN
Solar/Wind Harmer
9.113
958121AF2-106 GEN
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
941801AE2-185 GEN
Solar/Wind Harmer
5.168
943031AE2-326 GEN
Solar/Wind Harmer
4.428
3147123OTTER R
Solar/Wind Harmer
0.09
270030AE2-140 GEN
Solar/Wind Harmer
14.101
270346AE1-212 GEN
Solar/Wind Harmer
5.912
970223AG2-152 GEN
Solar/Wind Harmer
8.217
960911AF2-382 GEN
Solar/Wind Harmer
4.591
3147983MERCK5
Solar/Wind Helper
0.146
3152031BATH 3C
50/50
16.174
3152051BATH 5E
50/50
16.17
3152011BATH 1A
50/50
16.153
3152041BATH 4D
50/50
16.147
3151881LOWMORC
50/50
4.045
3151881LOWMORC
50/50
3.981
3151861LOWMORA
50/50
3.918
971543AH1-269 GEN
50/50
8.255
24684705SMG5
50/50
0.586
24684305SMG1
50/50
0.552
24416005BYLLESBY
50/50
0.02
3148463FAIRFLD
Solar/Wind Harmer
0.358
971331AH1-145 GEN
Solar/Wind Harmer
12.166
971329AH1-144 GEN
Solar/Wind Harmer
4.471
966391AG1-508 GEN
Solar/Wind Harmer
1.298
270197AD1-017 GEN1
Solar/Wind Harmer
0.971
270069AE2-166 C O1
Solar/Wind Harmer
6.845
971313AH1-133 GEN
Solar/Wind Harmer
3.311
24734705WLF1G3
Adder
4.973
24734805WLF1G4
Adder
4.973
24734905WLF1G5
Adder
4.973
3148133STUARTS
Solar/Wind Helper
0.183
3148013FISHERV
Solar/Wind Helper
0.175
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3152061BATH 6F
50/50
16.198
3152021BATH 2B
50/50
16.153
3151861LOWMORA
50/50
4.077
270205AE1-176
50/50
0.004
24290605CLAY-1
50/50
0.17
24290705CLAY-2
50/50
0.17
24684405SMG2
50/50
1.523
24684505SMG3
50/50
0.93
24728405LEESVG
50/50
0.203
24728405LEESVG
50/50
0.202
3147312GRETNA
Solar/Wind Harmer
0.032
958131AF2-107 GEN
Solar/Wind Harmer
3.841
943811AF1-049 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
4.099
316499AE2-029_GEN
Solar/Wind Helper
1.226
3148013FISHERV
Solar/Wind Helper
0.304
23583801GRNGAP
Solar/Wind Helper
3.89
3137383CUSHAW
50/50
0.077
247619Y1-049
50/50
0.033
270583AD2-179 GEN
Solar/Wind Harmer
9.704
942671AE2-283 GEN
Solar/Wind Harmer
4.019
971277AH1-098 GEN
Solar/Wind Harmer
3.382
24728205BUCHG1
Adder
4.099
3132123MT JACKSON
Solar/Wind Helper
1.116
237061AD1-155 GEN
Solar/Wind Helper
1.4
LAGNLTFEXP_LAGN->PJM
CLTF
11.379
CPLELTFEXP_CPLE->PJM
CLTF
3.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.449
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.084
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.738
TVALTFEXP_TVA->PJM
CLTF
6.026
MECLTFEXP_MEC->PJM
CLTF
8.168
SIGELTFEXP_SIGE->PJM
CLTF
0.27
NYPJM->LTFIMP_NY
CLTF
2.913
LGEELTFEXP_LGEE->PJM
CLTF
3.585
WECLTFEXP_WEC->PJM
CLTF
1.751
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.6 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4121.29
MW Contribution:
12.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
6.453
24288905REUSENS
50/50
0.044
24290605CLAY-1
50/50
0.191
24290705CLAY-2
50/50
0.191
24684605SMG4
50/50
1.709
24415905BUCK
50/50
0.024
962751AG1-124 GEN
Solar/Wind Harmer
14.722
958121AF2-106 GEN
Solar/Wind Harmer
7.113
943031AE2-326 GEN
Solar/Wind Harmer
4.988
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
941801AE2-185 GEN
Solar/Wind Harmer
7.541
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
22.56
270346AE1-212 GEN
Solar/Wind Harmer
9.774
270018AE2-047 C O1
Solar/Wind Harmer
1.335
270016AE1-250 BESS
Solar/Wind Harmer
2.406
960911AF2-382 GEN
Solar/Wind Harmer
7.439
970223AG2-152 GEN
Solar/Wind Harmer
12.946
971461AH1-227 GEN
Solar/Wind Harmer
4.675
3147983MERCK5
Solar/Wind Helper
0.183
316192AB2-158 GEN
Solar/Wind Helper
1.701
3147666LOUISA
Solar/Wind Helper
1.004
238152AF2-075_GEN
Solar/Wind Helper
0.575
3137383CUSHAW
50/50
0.133
247619Y1-049
50/50
0.037
270583AD2-179 GEN
Solar/Wind Harmer
15.666
270214AC2-123 GEN
Solar/Wind Harmer
3.169
942671AE2-283 GEN
Solar/Wind Harmer
6.661
971277AH1-098 GEN
Solar/Wind Harmer
5.459
270013AE1-250 PV
Solar/Wind Harmer
2.406
24728205BUCHG1
Adder
4.632
971225AH1-072 GEN
Solar/Wind Harmer
1.823
971227AH1-073 GEN
Solar/Wind Harmer
1.823
970913AG2-568 GEN
Solar/Wind Harmer
6.181
3132123MT JACKSON
Solar/Wind Helper
1.31
966001AG1-469 GEN
Solar/Wind Helper
0.292
237061AD1-155 GEN
Solar/Wind Helper
1.565
316097T157 G90
Solar/Wind Helper
1.083
238147AE2-230_GEN1
Solar/Wind Helper
0.403
238148AE2-230_GEN2
Solar/Wind Helper
0.403
238149AF1-291A_GEN
Solar/Wind Helper
0.115
3152061BATH 6F
50/50
17.174
3152021BATH 2B
50/50
17.126
3151861LOWMORA
50/50
7.039
270205AE1-176
50/50
0.005
24290605CLAY-1
50/50
0.191
24290705CLAY-2
50/50
0.191
24684405SMG2
50/50
1.698
24684505SMG3
50/50
1.037
24728405LEESVG
50/50
0.226
24728405LEESVG
50/50
0.225
270173AC1-122 GEN
Solar/Wind Harmer
2.679
316217AC1-145 GEN
Solar/Wind Harmer
3.261
316197AC1-042 GEN
Solar/Wind Harmer
2.472
3147312GRETNA
Solar/Wind Harmer
-0.004
270574AD1-017 GEN2
Solar/Wind Harmer
6.411
270336AE1-100 GEN
Solar/Wind Harmer
2.015
943811AF1-049 GEN
Solar/Wind Harmer
4.146
958131AF2-107 GEN
Solar/Wind Harmer
5.401
24728305BUCHG2
Adder
4.632
24735205WLF2G2
Adder
5.477
971687AH1-348 GEN
Solar/Wind Harmer
0.905
971403AH1-188 GEN
Solar/Wind Harmer
12.18
316499AE2-029_GEN
Solar/Wind Helper
1.577
3148013FISHERV
Solar/Wind Helper
0.457
315821AE2-092 GEN
Solar/Wind Helper
2.905
3132273ORANGE
Solar/Wind Helper
0.051
3147666LOUISA
Solar/Wind Helper
0.578
23583801GRNGAP
Solar/Wind Helper
4.13
23546401DTGZ2-030
Solar/Wind Helper
0.075
316095T157 G97
Solar/Wind Helper
1.083
3152031BATH 3C
50/50
17.148
3152051BATH 5E
50/50
17.143
3152011BATH 1A
50/50
17.126
3152041BATH 4D
50/50
17.119
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.874
3151861LOWMORA
50/50
6.764
971543AH1-269 GEN
50/50
9.295
24684705SMG5
50/50
0.653
24684305SMG1
50/50
0.615
24416005BYLLESBY
50/50
0.022
315616AA1-038_C
Solar/Wind Harmer
14.227
3148463FAIRFLD
Solar/Wind Harmer
-0.069
971331AH1-145 GEN
Solar/Wind Harmer
13.713
971329AH1-144 GEN
Solar/Wind Harmer
8.759
966391AG1-508 GEN
Solar/Wind Harmer
4.679
270197AD1-017 GEN1
Solar/Wind Harmer
1.923
270069AE2-166 C O1
Solar/Wind Harmer
10.973
971313AH1-133 GEN
Solar/Wind Harmer
6.499
24734705WLF1G3
Adder
5.611
24734805WLF1G4
Adder
5.611
24734905WLF1G5
Adder
5.611
24735105WLF2G1
Adder
5.477
3148133STUARTS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.263
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
315651AD1-115 GEN
Solar/Wind Helper
0.785
316164AC1-076 GEN
Solar/Wind Helper
1.099
LAGNLTFEXP_LAGN->PJM
CLTF
12.819
CPLELTFEXP_CPLE->PJM
CLTF
3.542
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.271
TVALTFEXP_TVA->PJM
CLTF
6.787
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.926
MECLTFEXP_MEC->PJM
CLTF
9.317
SIGELTFEXP_SIGE->PJM
CLTF
0.308
NYPJM->LTFIMP_NY
CLTF
3.203
LGEELTFEXP_LGEE->PJM
CLTF
4.093
WECLTFEXP_WEC->PJM
CLTF
2.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5173.4
MW Contribution:
12.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970673AG2-436 GEN
Solar/Wind Harmer
89.687
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
941031AE2-094 GEN
Solar/Wind Harmer
138.312
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
45.192
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.85 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5687.87
MW Contribution:
17.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
49.571
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
941031AE2-094 GEN
Solar/Wind Harmer
158.204
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970673AG2-436 GEN
Solar/Wind Harmer
177.133
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5662.94
MW Contribution:
17.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
941031AE2-094 GEN
Solar/Wind Harmer
157.057
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
970533AG2-339 GEN
Solar/Wind Harmer
56.328
970673AG2-436 GEN
Solar/Wind Harmer
175.868
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
944011AF1-069 GEN
Solar/Wind Harmer
49.211
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
TVALTFEXP_TVA->PJM
CLTF
7.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5581.87
MW Contribution:
17.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
944011AF1-069 GEN
Solar/Wind Harmer
48.793
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
316033AB2-134 GEN
Solar/Wind Helper
1.145
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
941031AE2-094 GEN
Solar/Wind Harmer
155.721
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
970533AG2-339 GEN
Solar/Wind Harmer
55.849
970673AG2-436 GEN
Solar/Wind Harmer
174.37
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
TVALTFEXP_TVA->PJM
CLTF
7.248
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.37 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:424.81
MW Contribution:
78.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.094
3151561HALLBR1
50/50
0.443
970223AG2-152 GEN
Solar/Wind Harmer
78.07
270016AE1-250 BESS
Solar/Wind Harmer
12.496
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.227
24684405SMG2
50/50
3.074
24684505SMG3
50/50
1.878
24728405LEESVG
50/50
0.331
24728405LEESVG
50/50
0.33
270574AD1-017 GEN2
Solar/Wind Harmer
22.144
270173AC1-122 GEN
Solar/Wind Harmer
3.409
316217AC1-145 GEN
Solar/Wind Harmer
3.462
316197AC1-042 GEN
Solar/Wind Harmer
2.624
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
1.007
958131AF2-107 GEN
Solar/Wind Harmer
2.397
270013AE1-250 PV
Solar/Wind Harmer
12.496
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684705SMG5
50/50
1.183
24684305SMG1
50/50
1.113
270197AD1-017 GEN1
Solar/Wind Harmer
6.643
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.77
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.235

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.13 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:423.88
MW Contribution:
78.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
12.491
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.4
24684605SMG4
50/50
3.09
3151561HALLBR1
50/50
0.442
970223AG2-152 GEN
Solar/Wind Harmer
78.039
270016AE1-250 BESS
Solar/Wind Harmer
12.491
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
24684405SMG2
50/50
3.069
24684505SMG3
50/50
1.875
24728405LEESVG
50/50
0.331
24728405LEESVG
50/50
0.33
270574AD1-017 GEN2
Solar/Wind Harmer
22.128
270173AC1-122 GEN
Solar/Wind Harmer
3.403
316217AC1-145 GEN
Solar/Wind Harmer
3.456
316197AC1-042 GEN
Solar/Wind Harmer
2.62
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
1.005
958131AF2-107 GEN
Solar/Wind Harmer
2.39
24684705SMG5
50/50
1.181
24684305SMG1
50/50
1.112
270197AD1-017 GEN1
Solar/Wind Harmer
6.638
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.228
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.591
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.773
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.82 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:414.81
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.355
970223AG2-152 GEN
Solar/Wind Harmer
74.562
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.139
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.894
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.748
958131AF2-107 GEN
Solar/Wind Harmer
2.282
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.69
942751AE2-291 GEN
Solar/Wind Harmer
5.678
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.679
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.073
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.269

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.64 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:414.12
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.356
970223AG2-152 GEN
Solar/Wind Harmer
74.563
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.139
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.895
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.749
958131AF2-107 GEN
Solar/Wind Harmer
2.282
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.64 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:414.12
MW Contribution:
74.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
11.782
942671AE2-283 GEN
Solar/Wind Harmer
5.691
942751AE2-291 GEN
Solar/Wind Harmer
5.679
24684605SMG4
50/50
2.407
3151561HALLBR1
50/50
0.356
970223AG2-152 GEN
Solar/Wind Harmer
74.563
270016AE1-250 BESS
Solar/Wind Harmer
11.782
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.442
3147123OTTER R
Solar/Wind Harmer
-0.009
962751AG1-124 GEN
Solar/Wind Harmer
5.139
24684405SMG2
50/50
2.391
24684505SMG3
50/50
1.461
24728405LEESVG
50/50
0.261
24728405LEESVG
50/50
0.26
270574AD1-017 GEN2
Solar/Wind Harmer
19.895
270173AC1-122 GEN
Solar/Wind Harmer
2.722
316217AC1-145 GEN
Solar/Wind Harmer
2.786
316197AC1-042 GEN
Solar/Wind Harmer
2.112
3147312GRETNA
Solar/Wind Harmer
-0.003
316123AC1-075 GEN
Solar/Wind Harmer
0.749
958131AF2-107 GEN
Solar/Wind Harmer
2.282
24684705SMG5
50/50
0.92
24684305SMG1
50/50
0.866
270197AD1-017 GEN1
Solar/Wind Harmer
5.968
270455AD2-022 GEN
Solar/Wind Helper
1.03
270457AD2-023 GEN
Solar/Wind Helper
0.678
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.239
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.19
WECLTFEXP_WEC->PJM
CLTF
0.083
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.268

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10830___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10830___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.19 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:392.76
MW Contribution:
75.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
12.013
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.245
24684605SMG4
50/50
2.679
3151561HALLBR1
50/50
0.384
970223AG2-152 GEN
Solar/Wind Harmer
75.601
270016AE1-250 BESS
Solar/Wind Harmer
12.013
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.825
270018AE2-047 C O1
Solar/Wind Helper
0.453
24684405SMG2
50/50
2.661
24684505SMG3
50/50
1.626
24728405LEESVG
50/50
0.287
24728405LEESVG
50/50
0.286
270574AD1-017 GEN2
Solar/Wind Harmer
20.717
270173AC1-122 GEN
Solar/Wind Harmer
2.97
316217AC1-145 GEN
Solar/Wind Harmer
3.011
316197AC1-042 GEN
Solar/Wind Harmer
2.282
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.202
943811AF1-049 GEN
Solar/Wind Helper
0.749
24684705SMG5
50/50
1.024
24684305SMG1
50/50
0.964
270197AD1-017 GEN1
Solar/Wind Harmer
6.215
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.053
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.664
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.769
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.062
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.392

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.14 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:392.56
MW Contribution:
75.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.679
3151561HALLBR1
50/50
0.384
970223AG2-152 GEN
Solar/Wind Harmer
75.601
270016AE1-250 BESS
Solar/Wind Harmer
12.013
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.825
270018AE2-047 C O1
Solar/Wind Helper
0.453
24684405SMG2
50/50
2.661
24684505SMG3
50/50
1.626
24728405LEESVG
50/50
0.287
24728405LEESVG
50/50
0.286
270574AD1-017 GEN2
Solar/Wind Harmer
20.717
270173AC1-122 GEN
Solar/Wind Harmer
2.97
316217AC1-145 GEN
Solar/Wind Harmer
3.011
316197AC1-042 GEN
Solar/Wind Harmer
2.282
3147312GRETNA
Solar/Wind Harmer
-0.004
316123AC1-075 GEN
Solar/Wind Harmer
0.833
958131AF2-107 GEN
Solar/Wind Harmer
2.202
943811AF1-049 GEN
Solar/Wind Helper
0.749
270013AE1-250 PV
Solar/Wind Harmer
12.013
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.245
24684705SMG5
50/50
1.024
24684305SMG1
50/50
0.964
270197AD1-017 GEN1
Solar/Wind Harmer
6.215
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.053
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.664
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.769
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.062
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.392

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4933.15
MW Contribution:
12.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316131AB2-060 GEN
Solar/Wind Harmer
0.788
315785AD2-033 C
Solar/Wind Harmer
1.994
316034AC1-036 C
Solar/Wind Harmer
0.016
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
970223AG2-152 GEN
Solar/Wind Harmer
12.084
3147123OTTER R
Solar/Wind Harmer
0.088
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.219
270030AE2-140 GEN
Solar/Wind Harmer
13.827
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
89.687
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
970581AG2-369 GEN
Solar/Wind Harmer
26.958
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
946301AF1-294 GEN
Solar/Wind Harmer
4.682
961791AG1-021 GEN
Solar/Wind Harmer
2.278
970831AG2-522 GEN
Solar/Wind Harmer
7.24
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
53.44
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.131
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
971623AH1-311 GEN
Solar/Wind Harmer
0.235
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
44.999
970099AG2-077 GEN
Solar/Wind Harmer
50.746
970301AG2-198 GEN
Solar/Wind Harmer
13.237
316118AC1-105 GEN
Solar/Wind Harmer
0.762
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.492
962561AG1-105 GEN
Solar/Wind Harmer
13.495
970323AG2-213 GEN
Solar/Wind Harmer
10.454
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
316263AC1-034 GEN
Solar/Wind Harmer
4.456
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5423.36
MW Contribution:
17.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.436
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
168.871
316478AD1-087 GEN
Solar/Wind Harmer
4.24
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
3151041BRUNSWICKG3
50/50
8.436
972187AH1-678 GEN
50/50
19.356
970909AG2-566 GEN
50/50
3.309
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970535AG2-341 GEN
50/50
4.57
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
59.249
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970301AG2-198 GEN
Solar/Wind Harmer
17.428
316248AF1-058 C
Solar/Wind Harmer
1.044
316118AC1-105 GEN
Solar/Wind Harmer
2.295
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.865
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.125
270013AE1-250 PV
Solar/Wind Harmer
2.845
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
316263AC1-034 GEN
Solar/Wind Harmer
6.176
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316294AC1-161 GEN
Solar/Wind Helper
7.701
316185AD1-033 GEN
Solar/Wind Helper
1.79
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316240AF1-291 C
Solar/Wind Helper
0.475
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.851
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3147312GRETNA
Solar/Wind Harmer
-0.003
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
316305AF2-043 C
Solar/Wind Helper
0.472
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316320Y1-086
Solar/Wind Helper
0.148
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
3151021BRUNSWICKG1
50/50
8.436
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
971629AH1-314 GEN
50/50
17.942
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316131AB2-060 GEN
Solar/Wind Harmer
3.062
315785AD2-033 C
Solar/Wind Harmer
6.268
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.377
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.554
270030AE2-140 GEN
Solar/Wind Harmer
19.819
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
315773AC2-141 GEN
Solar/Wind Helper
9.062
316375AC2-012 GEN
Solar/Wind Helper
1.012
316036AC1-147 C
Solar/Wind Helper
0.587
3145336SMITFLD
Solar/Wind Helper
1.485
315671AE2-027_GEN
Solar/Wind Helper
2.891
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
316072AD1-144
Solar/Wind Helper
0.405
316132AB2-190 GEN1
Solar/Wind Helper
1.996
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316435W1029_GEN3
Solar/Wind Helper
1.221
315244AE2-183_ST
50/50
19.288
963041AG1-153 GEN
50/50
17.078
3151541CLOVER2
50/50
9.313
3151601KERR 3
50/50
0.53
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
177.133
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
970581AG2-369 GEN
Solar/Wind Harmer
35.495
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
946301AF1-294 GEN
Solar/Wind Harmer
6.831
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
270457AD2-023 GEN
Solar/Wind Harmer
2.392
970831AG2-522 GEN
Solar/Wind Harmer
9.533
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
316322AB2-045
Solar/Wind Harmer
0.516
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316316AC1-027 C
Solar/Wind Helper
0.603
316236AE1-162_GEN
Solar/Wind Helper
0.501
315839AE2-212 C
Solar/Wind Helper
0.496
316018AA1-139 ULT2
Solar/Wind Helper
1.56
315697AD1-025 GEN
Solar/Wind Helper
4.048
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
957831AF2-077 GEN
Solar/Wind Helper
0.468
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Helper
0.066
316059AD1-063 C
Solar/Wind Helper
0.33
3141913WHIT STONE
Solar/Wind Helper
0.326
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
316468AD1-105 GEN
Solar/Wind Helper
1.285
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3142946ENON
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.485
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3146516WINFALL
Solar/Wind Helper
0.295
316312AB1-027
Solar/Wind Helper
0.567
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
966871AG1-558 GEN
Solar/Wind Helper
0.382
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
3138133OCRAN
Solar/Wind Helper
0.195
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3143526WINTERP
Solar/Wind Helper
1.518
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
316223AC1-118
Solar/Wind Helper
0.442
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.733
3146626S HERTFORD
Solar/Wind Helper
0.279
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5400.34
MW Contribution:
17.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
3151041BRUNSWICKG3
50/50
8.378
972187AH1-678 GEN
50/50
19.224
970909AG2-566 GEN
50/50
3.293
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970535AG2-341 GEN
50/50
4.581
3144293JTRSVLE
50/50
0.601
970933AG2-581 GEN
Solar/Wind Harmer
58.871
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
970301AG2-198 GEN
Solar/Wind Harmer
17.344
316248AF1-058 C
Solar/Wind Harmer
1.041
316118AC1-105 GEN
Solar/Wind Harmer
2.29
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.859
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.08
270013AE1-250 PV
Solar/Wind Harmer
2.837
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
316263AC1-034 GEN
Solar/Wind Harmer
6.326
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316294AC1-161 GEN
Solar/Wind Helper
7.794
316185AD1-033 GEN
Solar/Wind Helper
1.802
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
3151021BRUNSWICKG1
50/50
8.378
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
971629AH1-314 GEN
50/50
17.894
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316131AB2-060 GEN
Solar/Wind Harmer
3.07
315785AD2-033 C
Solar/Wind Harmer
6.277
316034AC1-036 C
Solar/Wind Harmer
0.509
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.539
270030AE2-140 GEN
Solar/Wind Harmer
19.766
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
315773AC2-141 GEN
Solar/Wind Helper
9.171
316375AC2-012 GEN
Solar/Wind Helper
1.018
316036AC1-147 C
Solar/Wind Helper
0.591
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
319010AE1-072 C
Solar/Wind Helper
4.082
316072AD1-144
Solar/Wind Helper
0.405
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
316132AB2-190 GEN1
Solar/Wind Helper
1.935
315671AE2-027_GEN
Solar/Wind Helper
2.696
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
3142946ENON
Solar/Wind Helper
0.031
316487AF1-042 GEN
Solar/Wind Helper
0.317
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.411
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.497
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.378
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
970917AG2-570 GEN
Solar/Wind Harmer
167.755
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3146926FARMVIL
Solar/Wind Harmer
-0.015
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.841
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3144873MCLAUGH
Solar/Wind Helper
0.01
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
316305AF2-043 C
Solar/Wind Helper
0.474
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316320Y1-086
Solar/Wind Helper
0.149
316321Z2-027
Solar/Wind Helper
0.487
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.154
963041AG1-153 GEN
50/50
16.962
3151541CLOVER2
50/50
9.264
3151601KERR 3
50/50
0.532
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
175.868
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
970581AG2-369 GEN
Solar/Wind Harmer
35.263
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
946301AF1-294 GEN
Solar/Wind Harmer
6.829
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
270457AD2-023 GEN
Solar/Wind Harmer
2.386
970831AG2-522 GEN
Solar/Wind Harmer
9.671
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
316322AB2-045
Solar/Wind Harmer
0.514
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316316AC1-027 C
Solar/Wind Helper
0.607
316236AE1-162_GEN
Solar/Wind Helper
0.499
316018AA1-139 ULT2
Solar/Wind Helper
1.569
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141873WAN 176
Solar/Wind Helper
0.065
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.197
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
316468AD1-105 GEN
Solar/Wind Helper
1.26
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
TVALTFEXP_TVA->PJM
CLTF
7.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5321.19
MW Contribution:
17.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.991
963041AG1-153 GEN
50/50
16.818
3151541CLOVER2
50/50
9.18
3151601KERR 3
50/50
0.526
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
3151631KERR 6
50/50
0.526
970673AG2-436 GEN
Solar/Wind Harmer
174.37
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
970581AG2-369 GEN
Solar/Wind Harmer
34.965
316486AD2-202 GEN
Solar/Wind Harmer
1.224
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
3151041BRUNSWICKG3
50/50
8.307
972187AH1-678 GEN
50/50
19.06
970909AG2-566 GEN
50/50
3.258
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970535AG2-341 GEN
50/50
4.523
3144293JTRSVLE
50/50
0.593
970933AG2-581 GEN
Solar/Wind Harmer
58.356
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
970301AG2-198 GEN
Solar/Wind Harmer
17.157
316248AF1-058 C
Solar/Wind Harmer
1.031
316118AC1-105 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.78
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.933
270013AE1-250 PV
Solar/Wind Harmer
2.814
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316263AC1-034 GEN
Solar/Wind Harmer
6.299
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316294AC1-161 GEN
Solar/Wind Helper
7.251
316240AF1-291 C
Solar/Wind Helper
0.472
316033AB2-134 GEN
Solar/Wind Helper
1.145
316185AD1-033 GEN
Solar/Wind Helper
1.553
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
316156AD2-030 GEN
Solar/Wind Helper
0.471
3142946ENON
Solar/Wind Helper
0.031
315666AE1-190 GEN
Solar/Wind Helper
0.419
3137176SLIGO L2192
Solar/Wind Helper
1.227
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
3151021BRUNSWICKG1
50/50
8.307
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
971629AH1-314 GEN
50/50
17.75
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316131AB2-060 GEN
Solar/Wind Harmer
3.026
315785AD2-033 C
Solar/Wind Harmer
6.188
316034AC1-036 C
Solar/Wind Harmer
0.502
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147123OTTER R
Solar/Wind Harmer
-0.01
270018AE2-047 C O1
Solar/Wind Harmer
1.362
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.486
270030AE2-140 GEN
Solar/Wind Harmer
19.599
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
315773AC2-141 GEN
Solar/Wind Helper
8.532
315671AE2-027_GEN
Solar/Wind Helper
2.884
316381AD1-082 GEN
Solar/Wind Helper
1.75
316375AC2-012 GEN
Solar/Wind Helper
0.883
316036AC1-147 C
Solar/Wind Helper
0.512
3145336SMITFLD
Solar/Wind Helper
1.329
316132AB2-190 GEN1
Solar/Wind Helper
1.896
316369SG1_INVT
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
1.252
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.351
319010AE1-072 C
Solar/Wind Helper
3.502
315975AC1-164 GENB
Solar/Wind Helper
0.116
316404AE1-155 C
Solar/Wind Helper
2.553
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.177
3143526WINTERP
Solar/Wind Helper
1.516
3142416OLDCHRC
Solar/Wind Helper
0.75
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.287
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
3151031BRUNSWICKG2
50/50
8.307
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
970917AG2-570 GEN
Solar/Wind Harmer
166.334
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3146926FARMVIL
Solar/Wind Harmer
-0.014
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.808
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3147312GRETNA
Solar/Wind Harmer
-0.003
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.55
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
3142956BIRDNECK
Solar/Wind Helper
0.223
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316305AF2-043 C
Solar/Wind Helper
0.402
316246AF1-032 C
Solar/Wind Helper
0.342
316077AC2-138 C
Solar/Wind Helper
0.276
316320Y1-086
Solar/Wind Helper
0.127
316473AC1-191 GEN
Solar/Wind Helper
1.701
316223AC1-118
Solar/Wind Helper
0.424
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146516WINFALL
Solar/Wind Helper
0.25
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.235
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3146386ELIZ CT
Solar/Wind Helper
0.282
966871AG1-558 GEN
Solar/Wind Helper
0.375
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
946301AF1-294 GEN
Solar/Wind Harmer
6.735
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270457AD2-023 GEN
Solar/Wind Harmer
2.367
970831AG2-522 GEN
Solar/Wind Harmer
9.555
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316322AB2-045
Solar/Wind Harmer
0.505
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
315839AE2-212 C
Solar/Wind Helper
0.498
316236AE1-162_GEN
Solar/Wind Helper
0.448
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
957831AF2-077 GEN
Solar/Wind Helper
0.436
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.313
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.092
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
313526AB2-022
Solar/Wind Helper
0.431
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316468AD1-105 GEN
Solar/Wind Helper
1.263
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
TVALTFEXP_TVA->PJM
CLTF
7.248
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
CONTINGENCY 'AEP_P4_#10213_05CLOVRD 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242560 TO BUS 242607 CKT 1    /*05BONSCK     138.0 - 05CLOVRD     138.0
 OPEN BRANCH FROM BUS 242560 TO BUS 242840 CKT 1    /*05BONSCK     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242773 TO BUS 242840 CKT 1    /*05ROANO1     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 245675 CKT Z1   /*05ROCKCAS SS 138.0 - 05WHITEHOUS8 138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
END
CONTINGENCY 'AEP_P4_#10210_05CLOVRD 138_A2_SRT-A'
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
 REMOVE LOAD D8 FROM BUS 242607                     /*05CLOVRD     138.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-S'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1   /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1   /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                   /*8LEXINGTN SC 500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 555_SRT-A'
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56722_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1   /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'AEP_P7-1_#10830___SRT-A'
 OPEN BRANCH FROM BUS 242555 TO BUS 242843 CKT 1   /*05BLAINE     138.0 - 05WLAKE      138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
CONTINGENCY 'AEP_P2-2_#6213_05WLAKE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
242549 to 242632 ckt 1
242519 to 314912 ckt 1
315684 to 314690 ckt 1
314697 to 315684 ckt 1
314901 to 314991 ckt 1
314902 to 314914 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314991 to 314926 ckt 1
941030 to 314902 ckt 1
970222 to 242549 ckt 1
970672 to 941030 ckt 1

Winter Peak Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC132.79 %694.0B921.58
0.67
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC121.81 %652.36B794.66
0.68
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC120.43 %652.36B785.66
0.68
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-W
BreakerAC114.25 %694.0B792.92
0.68
IPDCPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC103.78 %694.0B720.24
13.49

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:921.58
MW Contribution:
0.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.07 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:972.07
MW Contribution:
0.73
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.143
3147133PAMPLIN
Solar/Wind Helper
1.404
3147133PAMPLIN
Solar/Wind Helper
0.358
3147133PAMPLIN
Solar/Wind Helper
0.447
3146776BUCKING
Solar/Wind Helper
1.11
3146776BUCKING
Solar/Wind Helper
0.09
3146776BUCKING
Solar/Wind Helper
0.1
3146776BUCKING
Solar/Wind Helper
0.111
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.141
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.127
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.326
3146802CHATHAM
Solar/Wind Helper
0.119
3147243WELCO
Solar/Wind Helper
0.633
3144303KENBRDG
Solar/Wind Helper
0.372
3147173SINAI
Solar/Wind Helper
1.013
316478AD1-087 GEN
Solar/Wind Helper
0.708
316486AD2-202 GEN
Solar/Wind Helper
0.207
315687AD1-152 GEN
Solar/Wind Helper
1.243
315785AD2-033 C
Solar/Wind Helper
0.984
270030AE2-140 GEN
Solar/Wind Harmer
0.81
270069AE2-166 C O1
Solar/Wind Harmer
0.307
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.088
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.641
316123AC1-075 GEN
Solar/Wind Helper
0.821
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316197AC1-042 GEN
Solar/Wind Helper
0.107
3145543BTLEBRO
Solar/Wind Harmer
-0.153
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3138543CONSLDL
Solar/Wind Harmer
-0.105
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.171
3145573BETHELC
Solar/Wind Harmer
-0.171
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.171
3146083TARBORO
Solar/Wind Harmer
-0.171
3146083TARBORO
Solar/Wind Harmer
-0.171
3146233WITAKRS
Solar/Wind Harmer
0.032
3146233WITAKRS
Solar/Wind Harmer
-0.615
3146233WITAKRS
Solar/Wind Harmer
-0.105
942461AE2-259 GEN
Solar/Wind Helper
0.64
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.343
961601AG1-000A GEN
Solar/Wind Harmer
5.492
970085AG2-068 GEN
Solar/Wind Harmer
0.748
970087AG2-069 GEN
Solar/Wind Harmer
1.123
970223AG2-152 GEN
Solar/Wind Harmer
0.674
970581AG2-369 GEN
Solar/Wind Harmer
0.644
970917AG2-570 GEN
Solar/Wind Harmer
2.993
970919AG2-571 GEN
Solar/Wind Harmer
5.986
971629AH1-314 GEN
50/50
14.704
940641AE2-051 GEN
Solar/Wind Helper
0.486
957861AF2-080 GEN
Solar/Wind Harmer
0.184
315773AC2-141 GEN
Solar/Wind Helper
0.623
316003AC1-222 GEN
Solar/Wind Helper
0.969
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.237
316217AC1-145 GEN
Solar/Wind Helper
0.128
316222AC1-221 GEN
Solar/Wind Helper
2.601
316263AC1-034 GEN
Solar/Wind Harmer
0.252
316283AC2-100 C
Solar/Wind Helper
2.45
316294AC1-161 GEN
Solar/Wind Helper
0.623
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.833
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.915
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.82
NYPJM->LTFIMP_NY
CLTF
0.324
LGEELTFEXP_LGEE->PJM
CLTF
1.511
WECLTFEXP_WEC->PJM
CLTF
0.818
CPLELTFEXP_CPLE->PJM
CLTF
13.455
TVALTFEXP_TVA->PJM
CLTF
4.357
MECLTFEXP_MEC->PJM
CLTF
4.35
LAGNLTFEXP_LAGN->PJM
CLTF
8.827
SIGELTFEXP_SIGE->PJM
CLTF
0.128
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:794.66
MW Contribution:
0.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.46 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:824.95
MW Contribution:
0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
970917AG2-570 GEN
Solar/Wind Harmer
3.01
970919AG2-571 GEN
Solar/Wind Harmer
6.019
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.43 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:785.66
MW Contribution:
0.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.53 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:812.37
MW Contribution:
0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-W


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:792.92
MW Contribution:
0.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.41 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:821.74
MW Contribution:
0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970581AG2-369 GEN
Solar/Wind Harmer
0.647
970917AG2-570 GEN
Solar/Wind Harmer
3.01
970919AG2-571 GEN
Solar/Wind Harmer
6.019
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for [AG2-152] 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.78 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:720.24
MW Contribution:
13.49
IPD Plant:AG2-152
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:731.18
MW Contribution:
14.61
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
13.486
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-W'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: XT591_SRT-W
BreakerAC102.09 %694.0B708.49
0.56
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59162_SRT-W
BreakerAC102.09 %694.0B708.49
0.56
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59192-2_SRT-W
BreakerAC102.08 %694.0B708.42
0.56

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: XT591_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT591_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.49
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59162_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59162_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.49
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59192-2_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59192-2_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.42
MW Contribution:
0.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925
CONTINGENCY 'DVP_P4-2: XT591_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59162_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59192-2_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

Light Load Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW injection

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC116.71 %541.0B631.41
7.46
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC106.94 %508.54B543.83
7.55

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:631.41
MW Contribution:
7.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.84 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:615.89
MW Contribution:
8.06
Bus #Bus NameTypeMW Contribution
316034AC1-036 C
Solar/Wind Helper
0.588
316248AF1-058 C
Solar/Wind Helper
1.755
315773AC2-141 GEN
Solar/Wind Helper
3.082
316003AC1-222 GEN
Solar/Wind Helper
5.22
316478AD1-087 GEN
Solar/Wind Helper
3.812
316486AD2-202 GEN
Solar/Wind Helper
1.116
315687AD1-152 GEN
Solar/Wind Helper
6.698
315785AD2-033 C
Solar/Wind Helper
4.903
270030AE2-140 GEN
Solar/Wind Harmer
8.971
270069AE2-166 C O1
Solar/Wind Harmer
3.403
313527AB2-043 GEN
Solar/Wind Helper
2.161
316322AB2-045
Solar/Wind Helper
0.473
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
3.449
316263AC1-034 GEN
Solar/Wind Harmer
2.947
316129AC1-054 GEN
Solar/Wind Helper
1.268
316123AC1-075 GEN
Solar/Wind Helper
4.419
316118AC1-105 GEN
Solar/Wind Helper
4.009
316222AC1-221 GEN
Solar/Wind Helper
14.034
316283AC2-100 C
Solar/Wind Helper
13.217
316239AB2-077_GEN
Solar/Wind Helper
0.878
316238AB2-078_GEN
Solar/Wind Helper
0.878
316237AB2-079_GEN
Solar/Wind Helper
0.878
316197AC1-042 GEN
Solar/Wind Helper
0.53
316217AC1-145 GEN
Solar/Wind Helper
0.682
316294AC1-161 GEN
Solar/Wind Helper
1.112
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.156
3138543CONSLDL
Solar/Wind Harmer
0.107
3142053HEARTS
Solar/Wind Harmer
0.078
3145453TOT5
Solar/Wind Harmer
0.055
3145493TOT1
Solar/Wind Harmer
0.175
3145493TOT1
Solar/Wind Harmer
0.091
3145573BETHELC
Solar/Wind Harmer
0.175
3145573BETHELC
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.037
3146073TAR RVR
Solar/Wind Harmer
0.175
3146083TARBORO
Solar/Wind Harmer
0.175
3146083TARBORO
Solar/Wind Harmer
0.175
3146233WITAKRS
Solar/Wind Harmer
0.63
3146233WITAKRS
Solar/Wind Harmer
0.38
3146233WITAKRS
Solar/Wind Harmer
0.108
942461AE2-259 GEN
Solar/Wind Helper
3.443
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
2.91
961601AG1-000A GEN
Solar/Wind Harmer
4.014
961671AG1-007 GEN
Solar/Wind Harmer
0.329
970085AG2-068 GEN
Solar/Wind Harmer
8.715
970087AG2-069 GEN
Solar/Wind Harmer
13.073
970223AG2-152 GEN
Solar/Wind Harmer
7.46
970413AG2-270 GEN
50/50
Charging
32.717
970535AG2-341 GEN
50/50
Charging
6.427
970581AG2-369 GEN
Solar/Wind Harmer
7.495
970909AG2-566 GEN
50/50
Charging
4.037
970917AG2-570 GEN
Solar/Wind Harmer
34.858
970919AG2-571 GEN
Solar/Wind Harmer
15.025
971629AH1-314 GEN
50/50
14.763
957861AF2-080 GEN
Solar/Wind Harmer
2.16
900033ID_568986
External Queue
3.581075668334961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.096
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.125
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.447
NYPJM->LTFIMP_NY
CLTF
0.292
LGEELTFEXP_LGEE->PJM
CLTF
1.54
WECLTFEXP_WEC->PJM
CLTF
0.841
CPLELTFEXP_CPLE->PJM
CLTF
11.761
TVALTFEXP_TVA->PJM
CLTF
4.501
MECLTFEXP_MEC->PJM
CLTF
4.438
LAGNLTFEXP_LAGN->PJM
CLTF
8.852
SIGELTFEXP_SIGE->PJM
CLTF
0.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.94 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:543.83
MW Contribution:
7.55
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:98.78 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:502.35
MW Contribution:
8.17
Bus #Bus NameTypeMW Contribution
316034AC1-036 C
Solar/Wind Helper
0.583
316248AF1-058 C
Solar/Wind Helper
1.749
315773AC2-141 GEN
Solar/Wind Helper
3.009
316003AC1-222 GEN
Solar/Wind Helper
5.199
316478AD1-087 GEN
Solar/Wind Helper
3.79
316486AD2-202 GEN
Solar/Wind Helper
1.11
315687AD1-152 GEN
Solar/Wind Helper
6.672
315785AD2-033 C
Solar/Wind Helper
4.863
270030AE2-140 GEN
Solar/Wind Harmer
9.106
270069AE2-166 C O1
Solar/Wind Harmer
3.464
313527AB2-043 GEN
Solar/Wind Helper
2.145
316322AB2-045
Solar/Wind Helper
0.467
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
3.422
316263AC1-034 GEN
Solar/Wind Harmer
3
316129AC1-054 GEN
Solar/Wind Helper
1.247
316123AC1-075 GEN
Solar/Wind Helper
4.393
316118AC1-105 GEN
Solar/Wind Helper
3.992
316222AC1-221 GEN
Solar/Wind Helper
14.01
316283AC2-100 C
Solar/Wind Helper
13.194
316239AB2-077_GEN
Solar/Wind Helper
0.871
316238AB2-078_GEN
Solar/Wind Helper
0.871
316237AB2-079_GEN
Solar/Wind Helper
0.871
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.11
3142053HEARTS
Solar/Wind Harmer
0.079
3145453TOT5
Solar/Wind Harmer
0.056
3145493TOT1
Solar/Wind Harmer
0.179
3145493TOT1
Solar/Wind Harmer
0.093
3145573BETHELC
Solar/Wind Harmer
0.179
3145573BETHELC
Solar/Wind Harmer
0.179
3145603CNETO
Solar/Wind Harmer
0.037
3146073TAR RVR
Solar/Wind Harmer
0.179
3146083TARBORO
Solar/Wind Harmer
0.179
3146083TARBORO
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
0.644
3146233WITAKRS
Solar/Wind Harmer
0.388
3146233WITAKRS
Solar/Wind Harmer
0.11
942461AE2-259 GEN
Solar/Wind Helper
3.41
943811AF1-049 GEN
Solar/Wind Harmer
0
961671AG1-007 GEN
Solar/Wind Harmer
0.336
963041AG1-153 GEN
50/50
Charging
6.303
970085AG2-068 GEN
Solar/Wind Harmer
8.786
970087AG2-069 GEN
Solar/Wind Harmer
13.179
970223AG2-152 GEN
Solar/Wind Harmer
7.548
970413AG2-270 GEN
50/50
Charging
32.533
970417AG2-272 GEN
50/50
4.749
970533AG2-339 GEN
50/50
Charging
6.339
970535AG2-341 GEN
50/50
Charging
6.366
970581AG2-369 GEN
Solar/Wind Harmer
7.556
970909AG2-566 GEN
50/50
Charging
4
970917AG2-570 GEN
Solar/Wind Harmer
35.142
970919AG2-571 GEN
Solar/Wind Harmer
15.147
971629AH1-314 GEN
50/50
14.885
957861AF2-080 GEN
Solar/Wind Harmer
2.209
972287SS25-0012
50/50
Charging
12.035
900033ID_568986
External Queue
3.581075668334961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.814
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.766
NYPJM->LTFIMP_NY
CLTF
0.225
LGEELTFEXP_LGEE->PJM
CLTF
1.613
WECLTFEXP_WEC->PJM
CLTF
0.882
CPLELTFEXP_CPLE->PJM
CLTF
11.877
TVALTFEXP_TVA->PJM
CLTF
4.608
MECLTFEXP_MEC->PJM
CLTF
4.615
LAGNLTFEXP_LAGN->PJM
CLTF
9.066
SIGELTFEXP_SIGE->PJM
CLTF
0.136
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-152, AG2-272, AG2-518, AH1-098, AH1-144, AH1-145, AH1-269 and AH1-314 in PJM Transition Cycle 2, Cluster 24 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 24 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 24 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 24 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-098 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-098 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-098 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-098 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 24 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 24 projects have been dispatched online at maximum power output, with 1.01 pu voltage at the terminal bus.

 

Transition Cycle 2 Cluster 24 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 24 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 24 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 24 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 24 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Tripping was observed for several contingencies (P4.081, P4.082, P5.39, and P5.48) under the initial study conditions. Upon updating the fault impedance values based on Aspen short circuit case, the tripping issues were resolved, and the system remained stable for these contingencies.

 

AH1-098 both Solar and BESS units tripped under several contingencies. Upon updating Vdip to 0.8 (Original value was 0.9) and Vup to 1.2 (Original value was 1.1) for both units resolved all tripping issue.

 

Fictitious frequency response at AH1-145 generator bus tripped the queue project for several contingencies (P1.073, P1.075 and P1.076). Therefore, the frequency relay pickup times for were set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

AG2-272 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.15 (original value was 0) which resolved the slow reactive power response.

 

AH1-269 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

AH1-314 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

The active power for AG2-152 did not recover to the pre fault value for contingency P7.21 due inadequate reactive power response. The reactive power droop compensation gain Kc parameter was updated to 0.1 which resolved the active power recovery issue.

 

Smith Mountain generators showed positively damped oscillations which did not settle during the 20 second simulation window. The selected contingencies were run for 30 seconds, and the oscillatory signals achieved a flat response at the end of the 30 second simulation time period.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 24 Queues

Table 1: Transition Cycle 2 Cluster 24 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-152

Solar

AEP

131

Banister – Bearskin 138 kV

AG2-272

Battery

AEP

55

Berry Hill substation 138 kV

AG2-518

Battery

AEP

80

Tech Drive substation 138 kV

AH1-098

Solar/Battery

AEP

40

West Carroll – Wolf Glade 138 kV

AH1-144

Solar

AEP

70

Peter’s Mountain Substation 138 kV

AH1-145

Battery

AEP

80

Peter’s Mountain Substation 138 kV

AH1-269

Battery

AEP

50

Claytor substation 138 kV

AH1-314

Battery

AEP

100

East Danville substation 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-152 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-050Tarboro-Everetts 230kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-161Septa 500kVIn Service
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-100Axton 138 kVIn Service
AE1-250Smith Mountain-E. Danville 138 kVUnder Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-166Stockton 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-080Chinquapin-Everetts 230 kVWithdrawn
AG1-007Tar River 12.5 kVWithdrawn
AG1-153Heritage 500 kVUnder Construction
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-152 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-152 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
AEPb4000.204Rebuild 4 miles of Candler's Mountain - Opossum Creek 138 kV lineContingent$0N/A
AEPb4000.203Rebuild 17.5 miles of Redeye - Candler's Mountain 138 kV lineContingent$0N/A
AEPb4000.211Rebuild 6.5 miles of Johnson Mountain - New London 138 kV lineContingent$0N/A
AEPb4000.210Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.Contingent$0N/A
AEPb4000.202Rebuild 12.5 miles of Smith Mountain - Redeye 138 kV lineContingent$0N/A
AEPb4000.207Leesville Station Upgrade 138 kVContingent$0N/A
Dominionb4000.360Replace two switches, a wave trap and leads to upgrade all related substation equipment to 2000A at Altavista 138 kV substation.Contingent$0N/A
AEPn5613Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.Contingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.204
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.204
Title
Rebuild 4 miles of Candler's Mountain - Opossum Creek 138 kV line
Description
Rebuild 4 miles of Candler's Mountain - Opossum Creek 138 kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05CANDLER MT-05OPOSSUMCK 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA223.0 MVA
LLB296.0 MVA
LLC305.0 MVA
SUMA257.0 MVA
SUMB360.0 MVA
SUMC371.0 MVA
WINA325.0 MVA
WINB404.0 MVA
WINC417.0 MVA

System Reinforcement: b4000.203
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.203
Title
Rebuild 17.5 miles of Redeye - Candler's Mountain 138 kV line
Description
Rebuild 17.5 miles of Redeye - Candler's Mountain 138 kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05CANDLER MT-05REDEYE 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A257.0 MVA
(All)B360.0 MVA
(All)C571.0 MVA

System Reinforcement: b4000.211
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.211
Title
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
Description
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A297.0 MVA
(All)B330.0 MVA

System Reinforcement: b4000.210
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.210
Title
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Description
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05OTTER 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A297.0 MVA
(All)B414.0 MVA

System Reinforcement: b4000.202
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.202
Title
Rebuild 12.5 miles of Smith Mountain - Redeye 138 kV line
Description
Rebuild 12.5 miles of Smith Mountain - Redeye 138 kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA337.0 MVA
SUMB482.0 MVA
WINA426.0 MVA
WINB538.0 MVA
05SMITHMTN-05REDEYE 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA337.0 MVA
SUMB482.0 MVA
WINA427.0 MVA
WINB538.0 MVA

System Reinforcement: b4000.207
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.207
Title
Leesville Station Upgrade 138 kV
Description
Leesville Station Upgrade 138 kV: Replace 795 KCM AAC, 37-Str. IPS Sch. 40 1272 KCM AAC, 61-Str. 1272 KCM AAC, 61-Str. PH A,B,C ALTA VISTA CB-A BUS DISC ALTA VISTA CB-A LINE DISC Wavetrap (1200A) Relay Thermal Limit 1356 Amps
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A297.0 MVA
(All)B414.0 MVA

System Reinforcement: b4000.360
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.360
Title
Replace two switches, a wave trap and leads to upgrade all related substation equipment to 2000A at Altavista 138 kV substation.
Description
Replace two switches, a wave trap and leads to upgrade all related substation equipment to 2000A at Altavista 138 kV substation.
Cost Information
Time Estimate
Dec 31 2031

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA372.0 MVA
LLB392.0 MVA
LLC490.0 MVA
SUMA324.0 MVA
SUMB347.0 MVA
SUMC490.0 MVA
WINA384.0 MVA
WINB404.0 MVA
WINC504.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Description
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
99 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A363.0 MVA
(All)B382.0 MVA
(All)C420.0 MVA

System Reinforcement: n5613
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5613 / AEPA0014a
Title
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Description
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Total Cost ($USD)
$2,740,849
Discounted Total Cost ($USD)
$2,740,849
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-152 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-152 may not have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A257.0 MVA
(All)B360.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A961.0 MVA
(All)B961.0 MVA
(All)C1106.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-152


AG2-152 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-152 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-152 One Line Diagram

AG2-152 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.