AG2-184 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:56

Harbert Metering 138 kV

126.0 MW Capacity / 210.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is STMO bn, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Kentucky Power Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $34,607,555 $28,644,259 = 1.21 AND ( $34,607,555 - $28,644,259 ) 210.0 = $28,397 per MW

General

The Project Developer has proposed a Solar generating facility located in the Kentucky Power Company zone — Knott County, Kentucky. The installed facilities will have a total capability of 210.0 MW with 126.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-184
Project Name:
Harbert Metering 138 kV
Project Developer Name:
STMO bn, LLC
State:
Kentucky
County:
Knott
Transmission Owner:
Kentucky Power Company
MFO:
210.0
MWE:
210.0
MWC:
126.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-184 will interconnect on the American Electric Power transmission system by tapping the Spicewood Metering - Soft Shell 138 KV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-184 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-184Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$571,120$0$0
Other Scope$677,024$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$17,908,540$17,908,540$17,908,540
Network Upgrades$3,702,614$3,702,614$3,702,614
System Reliability Network Upgrades
Steady State Thermal & Voltage$7,025,822$7,025,822$7,025,822
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$5,970,579$5,970,579$5,970,579
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$35,855,699$34,607,555$34,607,555

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-184

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-184
Project ID: AG2-184
20% of cost allocation for Phase II Network Upgrades:(A) $6,921,511
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $2,864,426
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $4,057,085
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The existing HARBERT METERING 138 kV station must be retired to make space for the new three breaker ring bus station to be built for AG2-184.

$3,519,124$2,450,850$817,999$617,255$7,405,228$3,702,614 (See Note 1)
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the HARBERT METERING 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$375,078 (See Note 1)
(Pending)

Kentucky Power Company will install one (1) metering panel with two (2) primary meters and one (1) ethernet switch in the AH1-617 Project Developer's Collector Station.

$310,265$139,608$106,222$47,796$603,891$301,946 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of Carrier Protection at the HARBERT METERING 138 kV Station. Kentucky Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. Kentucky Power Company will install one (1) new 8340 router at the HARBERT METERING 138 kV Station.

$197,709$68,096$59,181$20,383$345,369$172,684 (See Note 1)
(Pending)

A new three breaker ring bus substation, AG2-184 New Station 138 kV, will be constructed replacing the existing Harbert Station along the SPICEWOOD - SOFT SHELL 138 kV transmission line to interconnect the project with the KPCO transmission system. 1 mile of gravel access road. Kentucky Power Company will review and revise (as needed) the protective relay settings at the HARBERT METERING 138 kV Station.

$26,668,951$2,852,935$5,242,175$707,651$35,471,712$17,735,856 (See Note 1)
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The APCO Interconnection Facilities will include but are not limited to the following: Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the HARBERT METERING 138 kV Station.

$613,301$285,874$164,220$78,845$1,142,240$571,120 (See Note 1)
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The existing HARBERT METERING 138 kV station must be retired to make space for the new three breaker ring bus station to be built for AG2-184.

$3,519,124$2,450,850$817,999$617,255$7,405,228$3,702,614 (See Note 1)
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of developer design and construction of new interconnection substation

$244,623$83,373$182,825$62,310$573,131$286,566 (See Note 1)
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the HARBERT METERING 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$375,078 (See Note 1)
(Pending)

Kentucky Power Company will install one (1) metering panel with two (2) primary meters and one (1) ethernet switch in the AH1-617 Project Developer's Collector Station.

$310,265$139,608$106,222$47,796$603,891$301,946 (See Note 1)
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$45,718,597$22,859,298
Developer Build Option$9,332,407$4,666,204

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts to Distribution Facilities

None


Transmission Owner Identified Network Impacts to Sub-Regional Facilities

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0117.55 %39.28
243710 05BONNYMAN 69.0 - 243718 05COMBS 69.0 CKT 1 AEP_P4_#13977_05BECKHA 138_K_SRT-A
CONTINGENCY 'AEP_P4_#13977_05BECKHA 138_K_SRT-A'  

  OPEN BRANCH FROM BUS 243672 TO BUS 243703 CKT 1                  / 243672 05BECKHA 138 243703 05TOPMOS 138 1

  OPEN BRANCH FROM BUS 243672 TO BUS 243704 CKT 1                  / 243672 05BECKHA 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 243704 CKT 1                  / 243692 05HAZRD1 138 243704 05VICCO 138 1

  OPEN BRANCH FROM BUS 243692 TO BUS 290466 CKT 1                  / 243692 05HAZRD1 138 290466 05HAZARD1EQ 1.00 1

  REMOVE LOAD D1 FROM BUS 243672                                   / 243672 05BECKHA 138 D1

  REMOVE SWSHUNT FROM BUS 243672                                   / 243672 05BECKHA 138

  OPEN BRANCH FROM BUS 243711 TO BUS 243729 CKT 1                  / 243711 05BULAN 69.0 243729 05HAZARD1- 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 243738 CKT 1                  / 243729 05HAZARD1- 69.0 243738 05LESLIE 69.0 1

  OPEN BRANCH FROM BUS 243729 TO BUS 290466 CKT 1                  / 243729 05HAZARD1- 69.0 290466 05HAZARD1EQ 1.00 1

  OPEN BRANCH FROM BUS 290466 TO BUS 290467 CKT 1                  / 290466 05HAZARD1EQ 1.00 290467 05HAZARD T1 13.0 1

END

75.0102.71 %25.27
243718 05COMBS 69.0 - 243709 05BLUEGRAS 69.0 CKT 1 AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A
CONTINGENCY 'AEP_P4_#9507_05BEAVER CR2 138_P_SRT-A'  

  OPEN BRANCH FROM BUS 243656 TO BUS 243671 CKT 1                  / 243656 05BEAVC1EQ 1.00 243671 05BEAVER CR1 138 1

  OPEN BRANCH FROM BUS 243657 TO BUS 244688 CKT 1                  / 243657 05BEAVC2EQ 1.00 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243708 CKT 1                  / 243656 05BEAVC1EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243708 CKT 1                  / 243657 05BEAVC2EQ 1.00 243708 05BEAVERCR 69.0 1

  OPEN BRANCH FROM BUS 243656 TO BUS 243808 CKT 1                  / 243656 05BEAVC1EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243657 TO BUS 243808 CKT 1                  / 243657 05BEAVC2EQ 1.00 243808 05BEAVERCR 46.0 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245913 CKT 1                  / 243671 05BEAVER CR1 138 245913 05KEWANEE 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 243683 CKT 1                  / 243671 05BEAVER CR1 138 243683 05CONSTP 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 245917 CKT 1                  / 243671 05BEAVER CR1 138 245917 05MYRA 138 1

  OPEN BRANCH FROM BUS 243671 TO BUS 244688 CKT ZP                 / 243671 05BEAVER CR1 138 244688 05BEAVER CR2 138 ZP

  OPEN BRANCH FROM BUS 243685 TO BUS 244688 CKT 1                  / 243685 05DORTON 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243698 TO BUS 244688 CKT 1                  / 243698 05MORGFK 138 244688 05BEAVER CR2 138 1

  OPEN BRANCH FROM BUS 243703 TO BUS 244688 CKT 1                  / 243703 05TOPMOS 138 244688 05BEAVER CR2 138 1

  REMOVE SWSHUNT FROM BUS 243671                                   / 243671 05BEAVER CR1 138

  REMOVE SWSHUNT FROM BUS 244688                                   / 244688 05BEAVER CR2 138

END
75.0100.74 %39.28
244480 05CHAUNCEY 46.0 - 244511 05RICH CRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0127.17 %3.29
244511 05RICH CRK 46.0 - 244498 05HUFFCRK 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
29.0112.27 %3.29
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P4_#14137_05LOGAN1 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14137_05LOGAN1 138_F_SRT-A'  

  OPEN BRANCH FROM BUS 242704 TO BUS 242705 CKT Z1                 / 242704 05LOGAN1 138 242705 05LOGAN2 138 Z1

  OPEN BRANCH FROM BUS 242704 TO BUS 242726 CKT 1                  / 242704 05LOGAN1 138 242726 05MUDFRK 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290392 CKT 1                  / 242704 05LOGAN1 138 290392 05ARGYLE 138 1

  OPEN BRANCH FROM BUS 242704 TO BUS 290391 CKT 1                  / 242704 05LOGAN1 138 290391 05TIN BRANCH 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 242735 CKT 1                  / 242705 05LOGAN2 138 242735 05NPOINT 138 1

  OPEN BRANCH FROM BUS 242705 TO BUS 247634 CKT 1                  / 242705 05LOGAN2 138 247634 05LYBURN SS 138 1

  REMOVE LOAD D4 FROM BUS 242704                                   / 242704 05LOGAN1 138 D4

  REMOVE SWSHUNT FROM BUS 242704                                   / 242704 05LOGAN1 138

  REMOVE SWSHUNT FROM BUS 242705                                   / 242705 05LOGAN2 138

END
18.0129.94 %2.03
244558 05SPRIGG 46.0 - 244550 05GRAPEVIN 46.0 CKT 1 AEP_P7-1_#10809___SRT-A
CONTINGENCY 'AEP_P7-1_#10809___SRT-A'  

  OPEN BRANCH FROM BUS 242705 TO BUS 242809 CKT 1                  / 242705 05LOGAN2 138 242809 05SPRIG1 138 1

  OPEN BRANCH FROM BUS 290391 TO BUS 290518 CKT 1                  / 290391 05TIN BRANCH 138 290518 05HOLDEN 138 1

  OPEN BRANCH FROM BUS 242761 TO BUS 290518 CKT 1                  / 242761 05RAGLDZ 138 290518 05HOLDEN 138 1

END
18.0120.09 %1.91

Transmission Owner Identified System Reinforcements on Distribution Facilities

None


Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
AG2-184 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEPn9789.0 / TC2-AEP-167Bonnyman - Combs: Sag study ~3 miles of 69kV line39.3 MW51.2%$13,573
AEPn9793.0 / TC2-AEP-180Bluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass39.3 MW51.2%$12,037
AEPn9796.0 / TC2-AEP-185Rebuild Chauncey - Huff Creek (8.8 miles)6.6 MW16.9%$5,944,969
Grand Total:$5,970,579
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9789.0 / TC2-AEP-167Bonnyman - Combs: Sag study ~3 miles of 69kV line$26,500

Contributor

Description: Bonnyman - Combs: Sag study ~3 miles of 69kV line

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18439.3 MW51.2%$13,573
AH1-61737.4 MW48.8%$12,927
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9793.0 / TC2-AEP-180Bluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass$23,500

Contributor

Description: Bluegrass - Combs: Sag study ~2.5 miles of 69kV line, replace switches at Combs, replace switches at Bluegrass

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-18439.3 MW51.2%$12,037
AH1-61737.4 MW48.8%$11,463
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPn9796.0 / TC2-AEP-185Rebuild Chauncey - Huff Creek (8.8 miles)$35,200,000

Contributor

Description: Rebuild Chauncey - Huff Creek (8.8 miles)

Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1846.6 MW16.9%$5,944,969
AH1-18826.1 MW67.0%$23,581,109
AH1-6176.3 MW16.1%$5,673,922
System Reinforcement
TORTEP ID / TO IDTitleTotal Cost
AEPs3147.30Grapevine Station - Removal of the Distribution station and equipment.$0

Contingent

Note: Although Queue Project AG2-184 may not have cost responsibility for this upgrade, Queue Project AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AG2-184 comes into service prior to completion of the upgrade, Queue Project AG2-184 will need an interim study.

Description: Grapevine Station - Removal of the Distribution station and equipment.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-184 was evaluated as a 210.0 MW (126.0 MW Capacity) injection in the AEP area.

AG2-184 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 210.0 MW (210.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#10335_05SALTV2 138_U_SRT-SL
BreakerAC105.32 %223.0B234.86
15.37
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#6173_05CLNCHR 138_E2_SRT-A
BreakerAC100.88 %223.0B224.97
13.85
GD2AEP
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
AEP_P4_#10332_05SALTV1 138_A_SRT-SL
BreakerAC100.47 %223.0B224.05
13.88
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC106.75 %392.0B418.48
17.82
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
AEP_P7-1_#10868___SRT-SL
TowerAC102.87 %392.0B403.24
20.83
GD2AEP
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Base Case
SingleAC100.45 %296.0A297.33
11.75
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
30.51
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
30.51
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
30.51
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
30.51
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
30.51
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
21.29
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
21.29
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.09
20.39
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC286.57 %1180.0B3381.47
14.23
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC286.54 %1180.0B3381.22
14.23
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC253.24 %1180.0B2988.23
18.32
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC216.42 %1180.0B2553.76
23.72
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC216.42 %1180.0B2553.76
23.72
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC216.42 %1180.0B2553.76
23.72
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC216.32 %1180.0B2552.59
23.72
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC188.35 %1180.0B2222.49
21.3
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC184.7 %1180.0B2179.5
20.35
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC180.7 %1180.0B2132.24
20.37
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 138KV_SRT-A
BusAC180.36 %1180.0B2128.24
20.43
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC176.65 %1180.0A2084.49
20.38
GD2AEP
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC100.83 %392.0B395.24
17.82
GD2AEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC133.02 %184.0A244.75
126.0
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC114.06 %184.0A209.87
210.0
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
SingleAC114.06 %184.0B209.87
210.0
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
30.51
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
30.51
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
30.51
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
30.51
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
30.51
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
21.29
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
21.29
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P7-1_#10868___SRT-SL
TowerAC114.38 %361.0B412.91
20.83
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#9173_05BROADF 765_P_SRT-A
BreakerAC113.39 %361.0B409.35
17.82
GD2AEP
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
AEP_P4_#1375_05BROADF 765_P2_SRT-A
BreakerAC103.51 %361.0B373.67
18.02

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#10335_05SALTV2 138_U_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10335_05SALTV2 138_U_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.32 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:234.86
MW Contribution:
15.37
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10335_05SALTV2 138_U_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.66 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:228.92
MW Contribution:
15.35
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.273
970281AG2-184 GEN
Solar/Wind Harmer
15.366
962211AG1-066 GEN
Solar/Wind Harmer
1.358
24689505VACITY
50/50
7.352
24290105CRG2H
50/50
1.518
971461AH1-227 GEN
Solar/Wind Harmer
6.05
972103AH1-617 GEN
Solar/Wind Harmer
14.635
960911AF2-382 GEN
Solar/Wind Harmer
5.258
24290005CRG1L
50/50
1.238
971687AH1-348 GEN
Solar/Wind Harmer
1.144
24289905CRG1H
50/50
1.479
971225AH1-072 GEN
Solar/Wind Harmer
2.359
971227AH1-073 GEN
Solar/Wind Harmer
2.359
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.247
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.234

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#6173_05CLNCHR 138_E2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6173_05CLNCHR 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.88 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:224.97
MW Contribution:
13.85
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6173_05CLNCHR 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.77 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:220.26
MW Contribution:
13.84
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.151
970281AG2-184 GEN
Solar/Wind Harmer
13.847
962211AG1-066 GEN
Solar/Wind Harmer
1.216
24689505VACITY
50/50
6.648
24290105CRG2H
50/50
1.373
971461AH1-227 GEN
Solar/Wind Harmer
5.472
972103AH1-617 GEN
Solar/Wind Harmer
13.188
960911AF2-382 GEN
Solar/Wind Harmer
4.877
24290005CRG1L
50/50
1.119
971687AH1-348 GEN
Solar/Wind Harmer
1.034
24289905CRG1H
50/50
1.337
971225AH1-072 GEN
Solar/Wind Harmer
2.133
971227AH1-073 GEN
Solar/Wind Harmer
2.133
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.152
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.39
NYPJM->LTFIMP_NY
CLTF
0.086
LGEELTFEXP_LGEE->PJM
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.231

Details for 05CLNCHR-05ABINGD 138.0 kV Ckt 1 line l/o AEP_P4_#10332_05SALTV1 138_A_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10332_05SALTV1 138_A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.47 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:224.05
MW Contribution:
13.88
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05ABINGD 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10332_05SALTV1 138_A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.32 %
Rating:223.0 MVA
Rating Type:B
MVA to Mitigate:219.25
MW Contribution:
13.87
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.153
970281AG2-184 GEN
Solar/Wind Harmer
13.881
962211AG1-066 GEN
Solar/Wind Harmer
1.219
24689505VACITY
50/50
6.658
24290105CRG2H
50/50
1.375
971461AH1-227 GEN
Solar/Wind Harmer
5.482
972103AH1-617 GEN
Solar/Wind Harmer
13.22
960911AF2-382 GEN
Solar/Wind Harmer
4.878
24290005CRG1L
50/50
1.121
971687AH1-348 GEN
Solar/Wind Harmer
1.036
24289905CRG1H
50/50
1.339
971225AH1-072 GEN
Solar/Wind Harmer
2.137
971227AH1-073 GEN
Solar/Wind Harmer
2.137
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.156
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.405
NYPJM->LTFIMP_NY
CLTF
0.086
LGEELTFEXP_LGEE->PJM
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.237

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.75 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:418.48
MW Contribution:
17.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.63 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:390.54
MW Contribution:
17.62
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o AEP_P7-1_#10868___SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.87 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:403.24
MW Contribution:
20.83
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:98.78 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:387.2
MW Contribution:
20.68
Bus #Bus NameTypeMW Contribution
24689505VACITY
50/50
9.797
24290105CRG2H
50/50
2.023
971461AH1-227 GEN
Solar/Wind Harmer
7.997
972103AH1-617 GEN
Solar/Wind Harmer
19.838
960911AF2-382 GEN
Solar/Wind Harmer
5.402
24290005CRG1L
50/50
1.649
24735205WLF2G2
50/50
6.012
971687AH1-348 GEN
Solar/Wind Harmer
1.515
24290205CRG2L
50/50
1.696
24734705WLF1G3
50/50
8.311
24734805WLF1G4
50/50
8.311
24734905WLF1G5
50/50
8.311
24735105WLF2G1
50/50
6.012
970281AG2-184 GEN
Solar/Wind Harmer
20.83
962211AG1-066 GEN
Solar/Wind Harmer
1.962
24289905CRG1H
50/50
1.97
971225AH1-072 GEN
Solar/Wind Harmer
3.118
971227AH1-073 GEN
Solar/Wind Harmer
3.118
LAGNLTFEXP_LAGN->PJM
CLTF
2.432
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
TVALTFEXP_TVA->PJM
CLTF
1.561
CPLELTFEXP_CPLE->PJM
CLTF
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.928
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.385
MECLTFEXP_MEC->PJM
CLTF
1.053
SIGELTFEXP_SIGE->PJM
CLTF
0.041
NYPJM->LTFIMP_NY
CLTF
0.229
LGEELTFEXP_LGEE->PJM
CLTF
0.588
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 05CLNCHR-05LEBANO 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.45 %
Rating:296.0 MVA
Rating Type:A
MVA to Mitigate:297.33
MW Contribution:
11.75
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:96.52 %
Rating:296.0 MVA
Rating Type:A
MVA to Mitigate:285.7
MW Contribution:
11.67
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.376
24734705WLF1G3
50/50
3.501
24734805WLF1G4
50/50
3.501
24734905WLF1G5
50/50
3.501
24735105WLF2G1
50/50
2.696
970281AG2-184 GEN
Solar/Wind Harmer
11.749
24290005CRG1L
50/50
1.339
24735205WLF2G2
50/50
2.696
971687AH1-348 GEN
Solar/Wind Harmer
0.859
24689505VACITY
50/50
7.951
24290105CRG2H
50/50
1.642
971461AH1-227 GEN
Solar/Wind Harmer
4.533
972103AH1-617 GEN
Solar/Wind Harmer
11.189
960911AF2-382 GEN
Solar/Wind Harmer
3.22
24289905CRG1H
50/50
1.599
971225AH1-072 GEN
Solar/Wind Harmer
1.767
971227AH1-073 GEN
Solar/Wind Harmer
1.767
LAGNLTFEXP_LAGN->PJM
CLTF
1.579
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.566
TVALTFEXP_TVA->PJM
CLTF
1.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.698
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.537
MECLTFEXP_MEC->PJM
CLTF
0.693
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.173
LGEELTFEXP_LGEE->PJM
CLTF
0.413
WECLTFEXP_WEC->PJM
CLTF
0.109

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
21.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
21.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.09
MW Contribution:
20.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
6.316
960911AF2-382 GEN
Solar/Wind Harmer
8.361
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
972273AH1-721 GEN
Adder
66.568
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
1.03
270336AE1-100 GEN
Solar/Wind Harmer
1.767
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
270214AC2-123 GEN
Solar/Wind Harmer
3.436
971277AH1-098 GEN
Solar/Wind Harmer
5.696
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
970913AG2-568 GEN
Solar/Wind Harmer
6.824
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
7.984
971313AH1-133 GEN
Solar/Wind Harmer
7.137
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
270400AC1-102 GEN
Solar/Wind Harmer
4.127
970281AG2-184 GEN
Solar/Wind Harmer
20.395
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
971981AH1-535 GEN
Solar/Wind Harmer
9.403
962211AG1-066 GEN
Solar/Wind Harmer
2.254
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
7.927
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.57 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.47
MW Contribution:
14.23
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
4.594
971313AH1-133 GEN
Solar/Wind Harmer
4.106
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
270400AC1-102 GEN
Solar/Wind Harmer
2.148
970281AG2-184 GEN
Solar/Wind Harmer
14.229
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
971981AH1-535 GEN
Solar/Wind Harmer
4.373
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
0.719
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960911AF2-382 GEN
Solar/Wind Harmer
5.833
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
971277AH1-098 GEN
Solar/Wind Harmer
3.974
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
970913AG2-568 GEN
Solar/Wind Harmer
5.608
24723105RIVRG2
Adder
16.666
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.22
MW Contribution:
14.23
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
971329AH1-144 GEN
Solar/Wind Harmer
4.594
971313AH1-133 GEN
Solar/Wind Harmer
4.106
24734705WLF1G3
Adder
6.298
24734805WLF1G4
Adder
6.298
24734905WLF1G5
Adder
6.298
24735105WLF2G1
Adder
6.159
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
270400AC1-102 GEN
Solar/Wind Harmer
2.148
970281AG2-184 GEN
Solar/Wind Harmer
14.229
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
971981AH1-535 GEN
Solar/Wind Harmer
4.373
941621AE2-160 GEN
Adder
3.038
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
274735ELWOOD EC;4P
Adder
10.589
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
316468AD1-105 GEN
Solar/Wind Helper
1.202
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141426STAFORD
Solar/Wind Helper
0.054
316233AE1-074 FULL
Solar/Wind Helper
0.367
315651AD1-115 GEN
Solar/Wind Helper
0.81
3141813NORNECK
Solar/Wind Helper
0.236
3143873LANEXA
Solar/Wind Helper
0.14
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
3138133OCRAN
Solar/Wind Helper
0.07
3141913WHIT STONE
Solar/Wind Helper
0.232
957601AF2-054 GEN
Solar/Wind Helper
0.31
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.303
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.498
24290005CRG1L
50/50
0.717
24735205WLF2G2
Adder
6.159
971687AH1-348 GEN
Solar/Wind Harmer
0.719
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274732ELWOOD EC;7P
Adder
10.589
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
270494AE1-108_GEN
Solar/Wind Helper
3.46
316473AC1-191 GEN
Solar/Wind Helper
1.53
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316223AC1-118
Solar/Wind Helper
0.364
3141906WESTMOR
Solar/Wind Helper
0.095
316077AC2-138 C
Solar/Wind Helper
0.222
3142946ENON
Solar/Wind Helper
0.078
316484AD2-074 GEN
Solar/Wind Helper
0.452
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147312GRETNA
Solar/Wind Helper
0.046
3147666LOUISA
Solar/Wind Helper
0.53
970823AG2-518 GEN
50/50
5.367
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
24290605CLAY-1
50/50
0.168
970563AG2-360 GEN
50/50
35.775
971881AH1-461 GEN
50/50
11.279
24689505VACITY
50/50
4.258
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960911AF2-382 GEN
Solar/Wind Harmer
5.833
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
274730ELWOOD EC;6P
Adder
10.589
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
316044AC1-158 PL1
Solar/Wind Helper
1.476
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
3143526WINTERP
Solar/Wind Helper
1.25
3143226MDLTHAN
Solar/Wind Helper
0.24
315975AC1-164 GENB
Solar/Wind Helper
0.091
316337AD2-073 GEN
Solar/Wind Helper
0.361
3142543TWELFTH
Solar/Wind Helper
0.023
964211AG1-282 GEN
Solar/Wind Helper
0.318
3141726DUNNSVL
Solar/Wind Helper
0.944
316404AE1-155 C
Solar/Wind Helper
2.011
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
316415AF1-147_GEN2
Solar/Wind Helper
0.762
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.498
24289905CRG1H
50/50
0.856
971277AH1-098 GEN
Solar/Wind Harmer
3.974
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
970913AG2-568 GEN
Solar/Wind Harmer
5.608
24723105RIVRG2
Adder
16.666
316045AC1-158 PL2
Solar/Wind Helper
4.721
316450AC1-158 RIC
Solar/Wind Helper
0.393
966871AG1-558 GEN
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.471
316006AB2-029 C
Solar/Wind Helper
0.117
3143526WINTERP
Solar/Wind Helper
1.25
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316487AF1-042 GEN
Solar/Wind Helper
0.237
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316411AF1-147_GEN1
Solar/Wind Helper
0.762
316240AF1-291 C
Solar/Wind Helper
0.302
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
TVALTFEXP_TVA->PJM
CLTF
7.636
CPLELTFEXP_CPLE->PJM
CLTF
2.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
MECLTFEXP_MEC->PJM
CLTF
11.31
SIGELTFEXP_SIGE->PJM
CLTF
0.374
NYPJM->LTFIMP_NY
CLTF
2.66
LGEELTFEXP_LGEE->PJM
CLTF
4.996
WECLTFEXP_WEC->PJM
CLTF
2.493
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:253.24 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2988.23
MW Contribution:
18.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
5.477
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24415905BUCK
50/50
0.025
970563AG2-360 GEN
50/50
33.924
971881AH1-461 GEN
50/50
10.678
24689505VACITY
50/50
3.969
943031AE2-326 GEN
Solar/Wind Harmer
5.324
958121AF2-106 GEN
Solar/Wind Harmer
6.343
270346AE1-212 GEN
Solar/Wind Harmer
9.332
960911AF2-382 GEN
Solar/Wind Harmer
7.746
270030AE2-140 GEN
Solar/Wind Harmer
19.126
971461AH1-227 GEN
Solar/Wind Harmer
4.864
972103AH1-617 GEN
Solar/Wind Harmer
17.445
959091AF2-200 GEN
Solar/Wind Harmer
10.981
274729ELWOOD EC;1P
Adder
8.897
274730ELWOOD EC;6P
Adder
8.897
274734ELWOOD EC;8P
Adder
8.897
274736ELWOOD EC;9P
Adder
8.897
274676JOLIET 29;8U
Adder
16.007
316447AC1-158 HLD
Solar/Wind Helper
3.012
316044AC1-158 PL1
Solar/Wind Helper
1.369
3142416OLDCHRC
Solar/Wind Helper
0.613
3142416OLDCHRC
Solar/Wind Helper
0.235
3143226MDLTHAN
Solar/Wind Helper
0.233
3143526WINTERP
Solar/Wind Helper
1.209
315975AC1-164 GENB
Solar/Wind Helper
0.087
3142543TWELFTH
Solar/Wind Helper
0.022
316337AD2-073 GEN
Solar/Wind Helper
0.341
964211AG1-282 GEN
Solar/Wind Helper
0.301
3141726DUNNSVL
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.892
316404AE1-155 C
Solar/Wind Helper
1.907
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
270205AE1-176
50/50
0.003
24728305BUCHG2
50/50
5.133
24735205WLF2G2
50/50
6.118
270336AE1-100 GEN
Solar/Wind Harmer
1.761
971687AH1-348 GEN
Solar/Wind Harmer
0.942
3151861LOWMORA
Adder
1.295
943811AF1-049 GEN
Solar/Wind Harmer
3.46
971403AH1-188 GEN
Solar/Wind Harmer
12.423
957471AF2-041 GEN
Solar/Wind Harmer
16.472
959081AF2-199 GEN
Solar/Wind Harmer
5.491
971067AG2-660 GEN
Solar/Wind Harmer
1.277
274732ELWOOD EC;7P
Adder
8.897
274676JOLIET 29;8U
Adder
16.6
270494AE1-108_GEN
Solar/Wind Helper
3.531
966881AG1-559 GEN
Solar/Wind Helper
0.328
316473AC1-191 GEN
Solar/Wind Helper
1.456
316075AC2-137 C
Solar/Wind Helper
0.351
316223AC1-118
Solar/Wind Helper
0.343
3141906WESTMOR
Solar/Wind Helper
0.09
3142946ENON
Solar/Wind Helper
0.075
316077AC2-138 C
Solar/Wind Helper
0.211
971543AH1-269 GEN
50/50
8.242
24416005BYLLESBY
50/50
0.023
24734705WLF1G3
50/50
6.262
24734805WLF1G4
50/50
6.262
24734905WLF1G5
50/50
6.262
24735105WLF2G1
50/50
6.118
966391AG1-508 GEN
Solar/Wind Harmer
4.809
971331AH1-145 GEN
Solar/Wind Harmer
12.412
971329AH1-144 GEN
Solar/Wind Harmer
7.928
971313AH1-133 GEN
Solar/Wind Harmer
6.737
270069AE2-166 C O1
Solar/Wind Harmer
9.245
315616AA1-038_C
Solar/Wind Harmer
2.777
3148463FAIRFLD
Solar/Wind Harmer
-0.014
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.264
3151861LOWMORA
Adder
1.244
971981AH1-535 GEN
Solar/Wind Harmer
8.769
970281AG2-184 GEN
Solar/Wind Harmer
18.318
971171AH1-044 GEN
Solar/Wind Harmer
10.981
274728ELWOOD EC;5P
Adder
8.897
274731ELWOOD EC;2P
Adder
8.897
274733ELWOOD EC;3P
Adder
8.897
274735ELWOOD EC;4P
Adder
8.897
274675JOLIET 29;7U
Adder
16.6
274675JOLIET 29;7U
Adder
16.007
316468AD1-105 GEN
Solar/Wind Helper
1.134
316164AC1-076 GEN
Solar/Wind Helper
1.11
316233AE1-074 FULL
Solar/Wind Helper
0.355
315651AD1-115 GEN
Solar/Wind Helper
0.755
3141813NORNECK
Solar/Wind Helper
0.223
3143873LANEXA
Solar/Wind Helper
0.134
247619Y1-049
50/50
0.036
24728205BUCHG1
50/50
5.133
270214AC2-123 GEN
Solar/Wind Harmer
3.383
971277AH1-098 GEN
Solar/Wind Harmer
5.61
270583AD2-179 GEN
Solar/Wind Harmer
13.976
971225AH1-072 GEN
Solar/Wind Harmer
1.896
971227AH1-073 GEN
Solar/Wind Harmer
1.896
970913AG2-568 GEN
Solar/Wind Harmer
6.125
971341AH1-150 GEN
Solar/Wind Harmer
10.981
971343AH1-151 GEN
Solar/Wind Harmer
10.981
316045AC1-158 PL2
Solar/Wind Helper
4.379
316450AC1-158 RIC
Solar/Wind Helper
0.365
966871AG1-558 GEN
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.209
315976AC1-164 GENA
Solar/Wind Helper
2.937
316169AC1-164_GENC
Solar/Wind Helper
2.537
3142946ENON
Solar/Wind Helper
0.022
316006AB2-029 C
Solar/Wind Helper
0.107
LAGNLTFEXP_LAGN->PJM
CLTF
12.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.088
TVALTFEXP_TVA->PJM
CLTF
6.888
CPLELTFEXP_CPLE->PJM
CLTF
2.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
83.049
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.014
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.396
MECLTFEXP_MEC->PJM
CLTF
9.684
SIGELTFEXP_SIGE->PJM
CLTF
0.319
NYPJM->LTFIMP_NY
CLTF
2.107
LGEELTFEXP_LGEE->PJM
CLTF
4.253
WECLTFEXP_WEC->PJM
CLTF
2.106
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.42 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2553.76
MW Contribution:
23.72
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
23.716

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.42 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2553.76
MW Contribution:
23.72
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
23.716

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:216.42 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2553.76
MW Contribution:
23.72
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
23.716

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:216.32 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2552.59
MW Contribution:
23.72
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
23.716

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:188.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2222.49
MW Contribution:
21.3
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
21.3

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:184.7 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2179.5
MW Contribution:
20.35
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.352

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:180.7 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2132.24
MW Contribution:
20.37
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.367

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 138KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 138KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:180.36 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2128.24
MW Contribution:
20.43
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.432

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.65 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2084.49
MW Contribution:
20.38
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.38

Details for 05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.83 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:395.24
MW Contribution:
17.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05ELKGARDNSS-05SALTV1 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.78 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:367.63
MW Contribution:
17.62
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258

Details for 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.02 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:244.75
MW Contribution:
126.0
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.02 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:244.75
MW Contribution:
126.0
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
126
972103AH1-617 GEN
Solar/Wind Harmer
120

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.06 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:209.87
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.07 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:209.89
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.06 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:209.87
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.07 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:209.89
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
30.51
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
21.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
21.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P7-1_#10868___SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.38 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:412.91
MW Contribution:
20.83
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10868___SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.79 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:378.29
MW Contribution:
20.68
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.696
24734705WLF1G3
50/50
8.311
24734805WLF1G4
50/50
8.311
24689505VACITY
50/50
9.797
24290105CRG2H
50/50
2.023
971461AH1-227 GEN
Solar/Wind Harmer
7.997
972103AH1-617 GEN
Solar/Wind Harmer
19.838
960911AF2-382 GEN
Solar/Wind Harmer
5.402
972273AH1-721 GEN
Adder
18.659
24290005CRG1L
50/50
1.649
24735205WLF2G2
50/50
6.012
971687AH1-348 GEN
Solar/Wind Harmer
1.515
24734905WLF1G5
50/50
8.311
24735105WLF2G1
50/50
6.012
970281AG2-184 GEN
Solar/Wind Harmer
20.83
962211AG1-066 GEN
Solar/Wind Harmer
1.962
24289905CRG1H
50/50
1.97
971225AH1-072 GEN
Solar/Wind Harmer
3.118
971227AH1-073 GEN
Solar/Wind Harmer
3.118
LAGNLTFEXP_LAGN->PJM
CLTF
2.432
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.087
TVALTFEXP_TVA->PJM
CLTF
1.561
CPLELTFEXP_CPLE->PJM
CLTF
0.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.928
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.385
MECLTFEXP_MEC->PJM
CLTF
1.053
SIGELTFEXP_SIGE->PJM
CLTF
0.041
NYPJM->LTFIMP_NY
CLTF
0.229
LGEELTFEXP_LGEE->PJM
CLTF
0.588
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#9173_05BROADF 765_P_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.39 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:409.35
MW Contribution:
17.82
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9173_05BROADF 765_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.68 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:381.51
MW Contribution:
17.62
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.406
970281AG2-184 GEN
Solar/Wind Harmer
17.82
962211AG1-066 GEN
Solar/Wind Harmer
1.732
24734705WLF1G3
Adder
3.889
24734805WLF1G4
Adder
3.889
24734905WLF1G5
Adder
3.889
24735105WLF2G1
Adder
3.527
971981AH1-535 GEN
Solar/Wind Harmer
4.339
24689505VACITY
50/50
8.123
24290105CRG2H
50/50
1.678
971461AH1-227 GEN
Solar/Wind Harmer
6.703
972103AH1-617 GEN
Solar/Wind Harmer
16.971
960911AF2-382 GEN
Solar/Wind Harmer
4.56
972273AH1-721 GEN
Adder
22.105
24290005CRG1L
50/50
1.368
971687AH1-348 GEN
Solar/Wind Harmer
1.272
24735205WLF2G2
Adder
3.527
24289905CRG1H
50/50
1.634
971225AH1-072 GEN
Solar/Wind Harmer
2.613
971227AH1-073 GEN
Solar/Wind Harmer
2.613
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.116
TVALTFEXP_TVA->PJM
CLTF
2.094
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.01
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.216
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.057
NYPJM->LTFIMP_NY
CLTF
0.26
LGEELTFEXP_LGEE->PJM
CLTF
0.781
WECLTFEXP_WEC->PJM
CLTF
0.258

Details for 05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line l/o AEP_P4_#1375_05BROADF 765_P2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1375_05BROADF 765_P2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.51 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:373.67
MW Contribution:
18.02
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1375_05BROADF 765_P2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.24 %
Rating:361.0 MVA
Rating Type:B
MVA to Mitigate:354.65
MW Contribution:
17.84
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
1.431
970281AG2-184 GEN
Solar/Wind Harmer
18.025
962211AG1-066 GEN
Solar/Wind Harmer
1.752
24734705WLF1G3
Adder
4.099
24734805WLF1G4
Adder
4.099
24734905WLF1G5
Adder
4.099
24735105WLF2G1
Adder
3.697
971981AH1-535 GEN
Solar/Wind Harmer
4.52
24689505VACITY
50/50
8.264
24290105CRG2H
50/50
1.707
971461AH1-227 GEN
Solar/Wind Harmer
6.818
972103AH1-617 GEN
Solar/Wind Harmer
17.167
960911AF2-382 GEN
Solar/Wind Harmer
4.814
972273AH1-721 GEN
Adder
22.206
24290005CRG1L
50/50
1.391
971687AH1-348 GEN
Solar/Wind Harmer
1.293
24735205WLF2G2
Adder
3.697
24289905CRG1H
50/50
1.662
971225AH1-072 GEN
Solar/Wind Harmer
2.658
971227AH1-073 GEN
Solar/Wind Harmer
2.658
LAGNLTFEXP_LAGN->PJM
CLTF
3.417
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.928
TVALTFEXP_TVA->PJM
CLTF
2.181
CPLELTFEXP_CPLE->PJM
CLTF
0.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.856
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.424
MECLTFEXP_MEC->PJM
CLTF
1.447
SIGELTFEXP_SIGE->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.236
LGEELTFEXP_LGEE->PJM
CLTF
0.721
WECLTFEXP_WEC->PJM
CLTF
0.226
CONTINGENCY 'AEP_P4_#10335_05SALTV2 138_U_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242789 CKT 1    /*05BROADF     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 242789 CKT 1    /*05MEADWV     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
 OPEN BRANCH FROM BUS 242789 TO BUS 243269 CKT 1    /*05SALTV2     138.0 - 05SALTVL 1EQ   1.0
 OPEN BRANCH FROM BUS 242885 TO BUS 243269 CKT 1    /*05SALTVILL    69.0 - 05SALTVL 1EQ   1.0
 OPEN BRANCH FROM BUS 243269 TO BUS 243503 CKT 1    /*05SALTVL 1EQ   1.0 - 05SALTVL T1   34.5
END
CONTINGENCY 'AEP_P4_#6173_05CLNCHR 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 242605 TO BUS 242700 CKT 1   /*05CLNCHR     138.0 - 05LEBANO     138.0
 OPEN BRANCH FROM BUS 242635 TO BUS 246766 CKT 1   /*05ELKGARDN   138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242700 TO BUS 244243 CKT 1   /*05LEBANO     138.0 - 05LEBANON     12.0
 OPEN BRANCH FROM BUS 242700 TO BUS 246766 CKT 1   /*05LEBANO     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1   /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
END
CONTINGENCY 'AEP_P4_#10332_05SALTV1 138_A_SRT-SL'
 OPEN BRANCH FROM BUS 242566 TO BUS 242788 CKT 2    /*05BROADF     138.0 - 05SALTV1     138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242700 CKT 1    /*05CLNCHR     138.0 - 05LEBANO     138.0
 OPEN BRANCH FROM BUS 242635 TO BUS 246766 CKT 1    /*05ELKGARDN   138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242700 TO BUS 244243 CKT 1    /*05LEBANO     138.0 - 05LEBANON     12.0
 OPEN BRANCH FROM BUS 242700 TO BUS 246766 CKT 1    /*05LEBANO     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 242789 CKT Z1   /*05SALTV1     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 246766 CKT 1    /*05SALTV1     138.0 - 05ELKGARDNSS 138.0
 OPEN BRANCH FROM BUS 242788 TO BUS 971312 CKT 1    /*05SALTV1     138.0 - AH1-133 TP   138.0
END
CONTINGENCY 'AEP_P4_#9173_05BROADF 765_P_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 290612 CKT Z1   /*05BAKER      765.0 - 05BAKER_RB   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6    /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290613 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RB 765.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6    /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1    /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6    /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
 OPEN BRANCH FROM BUS 290612 TO BUS 290613 CKT 1    /*05BAKER_RB   765.0 - 05BROADFR_RB 765.0
END
CONTINGENCY 'AEP_P7-1_#10868___SRT-SL'
 OPEN BRANCH FROM BUS 242533 TO BUS 242693 CKT 1   /*05ABINGD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 290135 CKT 1   /*05BROADF     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242605 TO BUS 242665 CKT 1   /*05CLNCHR     138.0 - 05HANSON     138.0
 OPEN BRANCH FROM BUS 242665 TO BUS 242714 CKT 1   /*05HANSON     138.0 - 05MEADWV     138.0
 OPEN BRANCH FROM BUS 242692 TO BUS 242693 CKT 1   /*05KEYWOD     138.0 - 05KEYWSS     138.0
 OPEN BRANCH FROM BUS 242693 TO BUS 290135 CKT 1   /*05KEYWSS     138.0 - 05SALTVL_BP  138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 242789 CKT 1   /*05MEADWV     138.0 - 05SALTV2     138.0
 OPEN BRANCH FROM BUS 242714 TO BUS 290185 CKT 2   /*05MEADWV     138.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244241 CKT 1   /*05MEADWVW     69.0 - 05HILLMAN     69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 244268 CKT 1   /*05MEADWVW     69.0 - 05MEDALLIN    69.0
 OPEN BRANCH FROM BUS 242875 TO BUS 290185 CKT 2   /*05MEADWVW     69.0 - 05MEADWVW2EQ 999.0
 OPEN BRANCH FROM BUS 290184 TO BUS 290185 CKT 2   /*05MEADWVW T2  13.1 - 05MEADWVW2EQ 999.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 138KV_SRT-A'
 OPEN BUS 314348   /*2GRETN_1      69.0
 OPEN BUS 314667   /*4ALTVSTA     138.0
 OPEN BUS 314670   /*2ALTVSTA      69.0
 OPEN BUS 314680   /*2CHATHAM      69.0
 OPEN BUS 314685   /*2CHTM TP      69.0
 OPEN BUS 314698   /*2TAYLORS MIL  69.0
 OPEN BUS 314709   /*2GLADYS TAP   69.0
 OPEN BUS 314727   /*2CLIMAX DP    69.0
 OPEN BUS 314728   /*2CLMX TP      69.0
 OPEN BUS 314729   /*2GLADYS       69.0
 OPEN BUS 314730   /*3STONE MILL   69.0
 OPEN BUS 314731   /*2GRETNA       69.0
 OPEN BUS 314733   /*2GRNA DP      69.0
 OPEN BUS 314735   /*2ALTAVISTADP  69.0
 OPEN BUS 314736   /*2SHKO DP      69.0
 OPEN BUS 314738   /*2MT AIRY      69.0
 OPEN BUS 314739   /*2MT A TP      69.0
 OPEN BUS 316193   /*RENANTP       69.0
 OPEN BUS 316194   /*AC1-042 MAIN  69.0
 OPEN BUS 316195   /*AC1-042 COL   34.0
 OPEN BUS 316196   /*AC1-042 TERT  13.0
 OPEN BUS 316197   /*AC1-042 GEN    0.4
 OPEN BUS 316214   /*AC1-145 MAIN  69.0
 OPEN BUS 316215   /*AC1-145 COL2  34.5
 OPEN BUS 316216   /*AC1-145 COL1  34.5
 OPEN BUS 316217   /*AC1-145 GEN    0.6
END
CONTINGENCY 'AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A'
 DISCONNECT BRANCH FROM BUS 972103 TO BUS 243689 CKT Z1   /*AH1-617 GEN  138.0 - 05HARBER     138.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P4_#1375_05BROADF 765_P2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290422 CKT 6   /*05BROADF     765.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 290422 CKT 6   /*05BROADF     500.0 - 05BROADFD6EQ   1.0
 OPEN BRANCH FROM BUS 242518 TO BUS 360106 CKT 1   /*05BROADF     500.0 - 8SULLIVAN TN 500.0
 OPEN BRANCH FROM BUS 290422 TO BUS 290423 CKT 6   /*05BROADFD6EQ   1.0 - 05BROADFD T6  13.8
END
242605 to 242533 ckt 1
242605 to 242700 ckt 1
290610 to 242512 ckt Z1
290614 to 242515 ckt 1
246766 to 242788 ckt 1
243689 to 243875 ckt 1
242514 to 290610 ckt 1
242700 to 246766 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
14.61
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
10.19
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
18.91
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
27.21
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
27.14
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
27.1
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
27.12
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC119.32 %5523.0B6590.12
31.27
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
32.72
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
22.83
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
33.01
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
32.45
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
20.07
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
34.82
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
30.48
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
24.29
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
32.31
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
32.57
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1445_ZIMMER_SRT-A
BreakerAC107.55 %1532.0B1647.65
13.04
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1449_ZIMMER_SRT-A
BreakerAC107.43 %1532.0B1645.79
13.04
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC106.98 %1532.0B1638.99
9.95
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1373_PORTUNION_SRT-A
BreakerAC106.14 %1532.0B1626.02
10.69
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1493_RED BANK_SRT-A
BreakerAC105.1 %1532.0B1610.06
10.82
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P4_1487_RED BANK_SRT-A
BreakerAC105.05 %1532.0B1609.33
10.82
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
TowerAC104.96 %1532.0B1608.02
10.82
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
BusAC104.95 %1532.0B1607.79
10.82
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Base Case
SingleAC104.93 %1240.0A1301.17
7.04
GD2DAY/EKPC
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
EKPC_P2-2_MELD-SPUR 345_SRT-A
BusAC103.1 %1532.0B1579.46
13.11

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
14.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
Adder
4.907
24734705WLF1G3
Adder
4.896
24734805WLF1G4
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
971313AH1-133 GEN
Solar/Wind Harmer
4.584
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270399AC1-101 GEN
Solar/Wind Harmer
2.774
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972163AH1-664 GEN
Solar/Wind Harmer
4.973
970563AG2-360 GEN
50/50
26.903
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
9.059
960911AF2-382 GEN
Solar/Wind Harmer
5.846
971461AH1-227 GEN
Solar/Wind Harmer
3.852
972103AH1-617 GEN
Solar/Wind Harmer
13.916
972273AH1-721 GEN
Adder
50.356
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
2.932
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
10.987
970455AG2-298 GEN
Solar/Wind Harmer
1.905
3429391JKCT 9G
Adder
4.482
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
972167AH1-666 GEN
Solar/Wind Harmer
3.959
958171AF2-111 GEN
Solar/Wind Harmer
12.218
942481AE2-261 GEN
Solar/Wind Harmer
14.451
957381AF2-032 GEN
Solar/Wind Harmer
0.966
970193AG2-126 GEN
Solar/Wind Harmer
7.158
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971993AH1-541 GEN
Solar/Wind Harmer
4.402
965931AG1-462 GEN
Solar/Wind Harmer
12.097
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
14.092
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
276603SUBLETTE C
Solar/Wind Harmer
0.49
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
959091AF2-200 GEN
Solar/Wind Harmer
9.281
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
3.282
971485AH1-239 GEN
Solar/Wind Harmer
4.84
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964781AG1-341 GEN
Solar/Wind Harmer
6.17
339236AF1-050_GEN
Solar/Wind Harmer
1.045
942891AE2-308 GEN
Solar/Wind Harmer
5.443
964571AG1-320 GEN
Solar/Wind Harmer
4.43
971125AH1-004 GEN
Solar/Wind Harmer
2.108
970107AG2-081 GEN
Solar/Wind Harmer
1.581
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276916AD2-100_GEN
Solar/Wind Harmer
10.169
276911AD2-131_GEN
Solar/Wind Harmer
2.055
276615X2-022 GEN
Solar/Wind Harmer
0.938
276838X2-022 GEN2
Solar/Wind Harmer
0.111
945391AF1-204 GEN
Solar/Wind Harmer
6.651
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
252509AD1-136 GEN
Solar/Wind Harmer
0.119
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
24735205WLF2G2
Adder
4.907
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.746
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.667
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
9.341
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.987
276686W4-005 GEN3
Solar/Wind Harmer
1.44
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
276708O09 GEN2
Solar/Wind Harmer
1.676
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
4.08
276656WTG2_EQ
Solar/Wind Harmer
0.54
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
13.937
957471AF2-041 GEN
Solar/Wind Harmer
13.921
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
972165AH1-665 GEN
Solar/Wind Harmer
3.979
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
944221AF1-090 GEN
Solar/Wind Harmer
5.329
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
946321AF1-296 GEN
Solar/Wind Harmer
4.94
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
3.696
959341AF2-225 GEN
Solar/Wind Harmer
7.012
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
971171AH1-044 GEN
Solar/Wind Harmer
9.281
970169AG2-114 GEN
Solar/Wind Harmer
4.633
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
276889AE2-281 GEN
Solar/Wind Harmer
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
10.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
276882AE2-255 GEN
Solar/Wind Harmer
0.375
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
18.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
27.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971329AH1-144 GEN
Solar/Wind Harmer
11.745
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270069AE2-166 C O1
Solar/Wind Harmer
14.894
971313AH1-133 GEN
Solar/Wind Harmer
9.348
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
970281AG2-184 GEN
Solar/Wind Harmer
27.213
971981AH1-535 GEN
Solar/Wind Harmer
12.593
962211AG1-066 GEN
Solar/Wind Harmer
3.011
971061AG2-657 GEN
Solar/Wind Harmer
11.048
3429211JKCT 2G
Adder
11.928
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
25196508WSDLE4
Adder
7.812
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
270356AE2-297 GEN
Solar/Wind Harmer
4.168
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
963841AG1-237 GEN
Solar/Wind Harmer
9.807
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
959341AF2-225 GEN
Solar/Wind Harmer
13.389
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274744AC1-111 GEN8
Adder
4.896
274746AC1-111 G10
Adder
4.896
25306009OHH W.
Adder
2.518
274728ELWOOD EC;5P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
316164AC1-076 GEN
Solar/Wind Helper
1.182
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.093
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
3141426STAFORD
Solar/Wind Helper
0.049
24386405FR-21G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.212
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
15.01
970563AG2-360 GEN
50/50
45.925
970417AG2-272 GEN
50/50
3.737
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.417
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.813
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270018AE2-047 C O1
Solar/Wind Harmer
1.823
960911AF2-382 GEN
Solar/Wind Harmer
10.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24686405CER G5
Adder
9.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
972273AH1-721 GEN
Adder
89.66
24721905FLATG4
Adder
21.789
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970653AG2-424 GEN
Solar/Wind Harmer
0.709
971191AH1-055 GEN
Solar/Wind Harmer
18.939
3429391JKCT 9G
Adder
8.441
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972167AH1-666 GEN
Solar/Wind Harmer
7.807
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196008MFTGT1
Adder
1.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
970879AG2-548 GEN
Solar/Wind Harmer
7.39
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
942481AE2-261 GEN
Solar/Wind Harmer
27.366
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728705AND G3
Adder
7.32
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
965931AG1-462 GEN
Solar/Wind Harmer
22.875
971087AG2-675 GEN
Solar/Wind Harmer
3.338
965091AG1-374 GEN
Solar/Wind Harmer
26.876
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274760LEE CO EC;1U
Adder
8.264
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.852
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.911
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.18
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971277AH1-098 GEN
Solar/Wind Harmer
7.43
942671AE2-283 GEN
Solar/Wind Harmer
8.669
270013AE1-250 PV
Solar/Wind Harmer
3.251
970913AG2-568 GEN
Solar/Wind Harmer
9.375
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
971485AH1-239 GEN
Solar/Wind Harmer
8.528
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964781AG1-341 GEN
Solar/Wind Harmer
11.012
339236AF1-050_GEN
Solar/Wind Harmer
1.88
942891AE2-308 GEN
Solar/Wind Harmer
10.222
964571AG1-320 GEN
Solar/Wind Harmer
8.222
971125AH1-004 GEN
Solar/Wind Harmer
4.008
970107AG2-081 GEN
Solar/Wind Harmer
3.006
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
276615X2-022 GEN
Solar/Wind Harmer
1.781
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960611AF2-352 GEN
Solar/Wind Harmer
2.083
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274696ROCKY RD ;4P
Adder
10.01
274695ROCKY RD ;2P
Adder
9.779
274693ROCKY RD ;1P
Adder
9.683
274697ROCKY RD ;3P
Adder
2.656
253370AE2-315 SEC1
Adder
1.749
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.655
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
966871AG1-558 GEN
Solar/Wind Helper
0.307
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728305BUCHG2
50/50
7.18
270173AC1-122 GEN
Solar/Wind Harmer
3.446
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
958131AF2-107 GEN
Solar/Wind Harmer
7.107
24735205WLF2G2
Adder
8.042
971687AH1-348 GEN
Solar/Wind Harmer
1.363
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
24723205RIVRG3
Adder
23.046
24686505CER G6
Adder
9.917
972203AH1-686 GEN
Adder
2.716
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
339211AE2-254 GEN
Solar/Wind Harmer
1.567
964901AG1-354 GEN
Solar/Wind Harmer
15.55
960001AF2-291 GEN
Solar/Wind Harmer
3.133
339241AF1-083 GEN
Solar/Wind Harmer
1.722
3429241JKCT 3G
Adder
12.084
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
943111AE2-339 GEN
Solar/Wind Harmer
0.887
339221AD2-048_GEN
Solar/Wind Harmer
1.518
945681AF1-233 GEN
Solar/Wind Harmer
18.414
970091AG2-072 GEN
Adder
74.384
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252510AF1-249 C
Solar/Wind Harmer
0.385
971073AG2-665 GEN
Solar/Wind Harmer
1.074
25194608D.CRK4
Adder
1.517
965911AG1-460 GEN
Solar/Wind Harmer
1.277
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
276621W2-048 GEN
Solar/Wind Harmer
5.671
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
270222AC2-111 GEN
Solar/Wind Harmer
4.015
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276655WTG1_EQ
Solar/Wind Harmer
7.791
276656WTG2_EQ
Solar/Wind Harmer
1.032
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
274766LEE CO EC;7U
Adder
8.167
274822ROCKFORD ;11
Adder
17.365
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
274732ELWOOD EC;7P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274674JOLIET 9 ;6U
Adder
13.445
274676JOLIET 29;8U
Adder
22.605
3148013FISHERV
Solar/Wind Helper
0.524
316499AE2-029_GEN
Solar/Wind Helper
1.728
315821AE2-092 GEN
Solar/Wind Helper
3.236
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.324
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
24385905FR-11G C
Solar/Wind Harmer
5.645
24386605FR-22G C
Solar/Wind Harmer
2.921
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
TVALTFEXP_TVA->PJM
CLTF
10.64
CPLELTFEXP_CPLE->PJM
CLTF
6.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
WECLTFEXP_WEC->PJM
CLTF
3.389
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
27.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.98
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.164
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
942671AE2-283 GEN
Solar/Wind Harmer
8.664
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
971485AH1-239 GEN
Solar/Wind Harmer
8.501
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964781AG1-341 GEN
Solar/Wind Harmer
10.975
339236AF1-050_GEN
Solar/Wind Harmer
1.873
942891AE2-308 GEN
Solar/Wind Harmer
10.182
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
276615X2-022 GEN
Solar/Wind Harmer
1.774
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960611AF2-352 GEN
Solar/Wind Harmer
2.075
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274696ROCKY RD ;4P
Adder
9.966
274695ROCKY RD ;2P
Adder
9.736
274693ROCKY RD ;1P
Adder
9.64
274697ROCKY RD ;3P
Adder
2.645
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
237061AD1-155 GEN
Solar/Wind Helper
1.65
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
970563AG2-360 GEN
50/50
45.836
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.819
958121AF2-106 GEN
Solar/Wind Harmer
9.406
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.808
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.95
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24686405CER G5
Adder
9.803
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
972273AH1-721 GEN
Adder
89.361
24721905FLATG4
Adder
21.701
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.408
971191AH1-055 GEN
Solar/Wind Harmer
18.847
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196008MFTGT1
Adder
1.253
252519AF1-045_GEN
Solar/Wind Harmer
3.354
970879AG2-548 GEN
Solar/Wind Harmer
7.349
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
942481AE2-261 GEN
Solar/Wind Harmer
27.253
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728705AND G3
Adder
7.288
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
965931AG1-462 GEN
Solar/Wind Harmer
22.779
971087AG2-675 GEN
Solar/Wind Harmer
3.324
965091AG1-374 GEN
Solar/Wind Harmer
26.762
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274760LEE CO EC;1U
Adder
8.229
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.847
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
24386205FR-12G C
Solar/Wind Harmer
2.085
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.164
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.104
24735205WLF2G2
Adder
8.025
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723205RIVRG3
Adder
22.967
24686505CER G6
Adder
9.881
972203AH1-686 GEN
Adder
2.706
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339211AE2-254 GEN
Solar/Wind Harmer
1.561
339241AF1-083 GEN
Solar/Wind Harmer
1.716
960001AF2-291 GEN
Solar/Wind Harmer
3.117
3429241JKCT 3G
Adder
12.037
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339221AD2-048_GEN
Solar/Wind Harmer
1.511
945681AF1-233 GEN
Solar/Wind Harmer
18.334
970091AG2-072 GEN
Adder
74.077
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252510AF1-249 C
Solar/Wind Harmer
0.384
971073AG2-665 GEN
Solar/Wind Harmer
1.068
25194608D.CRK4
Adder
1.51
965911AG1-460 GEN
Solar/Wind Harmer
1.272
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
276621W2-048 GEN
Solar/Wind Harmer
5.648
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
944031AF1-071 GEN
Solar/Wind Harmer
0.899
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
276655WTG1_EQ
Solar/Wind Harmer
7.757
276656WTG2_EQ
Solar/Wind Harmer
1.027
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274761LEE CO EC;2U
Adder
8.229
274766LEE CO EC;7U
Adder
8.132
274822ROCKFORD ;11
Adder
17.29
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
274676JOLIET 29;8U
Adder
26.663
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.232
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.627
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.304
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
24385905FR-11G C
Solar/Wind Harmer
4.044
24386605FR-22G C
Solar/Wind Harmer
2.093
971329AH1-144 GEN
Solar/Wind Harmer
11.729
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.878
971313AH1-133 GEN
Solar/Wind Harmer
9.329
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
970281AG2-184 GEN
Solar/Wind Harmer
27.137
971981AH1-535 GEN
Solar/Wind Harmer
12.564
962211AG1-066 GEN
Solar/Wind Harmer
3.002
971061AG2-657 GEN
Solar/Wind Harmer
11.001
3429211JKCT 2G
Adder
11.881
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
25196508WSDLE4
Adder
7.775
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
270356AE2-297 GEN
Solar/Wind Harmer
4.149
253406AD2-031_GEN
Solar/Wind Harmer
1.147
963841AG1-237 GEN
Solar/Wind Harmer
9.765
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
959341AF2-225 GEN
Solar/Wind Harmer
13.331
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274744AC1-111 GEN8
Adder
4.874
274746AC1-111 G10
Adder
4.874
274728ELWOOD EC;5P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
316164AC1-076 GEN
Solar/Wind Helper
1.178
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.09
24386405FR-21G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
TVALTFEXP_TVA->PJM
CLTF
10.609
CPLELTFEXP_CPLE->PJM
CLTF
6.216
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
27.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971277AH1-098 GEN
Solar/Wind Harmer
7.416
942671AE2-283 GEN
Solar/Wind Harmer
8.662
270013AE1-250 PV
Solar/Wind Harmer
3.247
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
971485AH1-239 GEN
Solar/Wind Harmer
8.488
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964781AG1-341 GEN
Solar/Wind Harmer
10.959
339236AF1-050_GEN
Solar/Wind Harmer
1.871
942891AE2-308 GEN
Solar/Wind Harmer
10.165
964571AG1-320 GEN
Solar/Wind Harmer
8.178
971125AH1-004 GEN
Solar/Wind Harmer
3.985
970107AG2-081 GEN
Solar/Wind Harmer
2.988
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
276615X2-022 GEN
Solar/Wind Harmer
1.77
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
24387305FR-4G C
Solar/Wind Harmer
2.467
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
18.814
958121AF2-106 GEN
Solar/Wind Harmer
9.401
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.805
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270018AE2-047 C O1
Solar/Wind Harmer
1.82
960911AF2-382 GEN
Solar/Wind Harmer
10.939
270016AE1-250 BESS
Solar/Wind Harmer
3.247
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24686405CER G5
Adder
9.787
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.807
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.758
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
7.33
252524AE2-267 GEN
Solar/Wind Harmer
1.44
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
942481AE2-261 GEN
Solar/Wind Harmer
27.203
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
965931AG1-462 GEN
Solar/Wind Harmer
22.737
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
26.711
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
24386205FR-12G C
Solar/Wind Harmer
2.081
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
270173AC1-122 GEN
Solar/Wind Harmer
3.443
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
958131AF2-107 GEN
Solar/Wind Harmer
7.102
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.473
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
11.722
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270069AE2-166 C O1
Solar/Wind Harmer
14.87
971313AH1-133 GEN
Solar/Wind Harmer
9.321
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
970281AG2-184 GEN
Solar/Wind Harmer
27.103
971981AH1-535 GEN
Solar/Wind Harmer
12.552
962211AG1-066 GEN
Solar/Wind Harmer
2.998
971061AG2-657 GEN
Solar/Wind Harmer
10.98
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
270356AE2-297 GEN
Solar/Wind Harmer
4.141
253406AD2-031_GEN
Solar/Wind Harmer
1.145
963841AG1-237 GEN
Solar/Wind Harmer
9.746
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
959341AF2-225 GEN
Solar/Wind Harmer
13.306
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
24386405FR-21G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
339211AE2-254 GEN
Solar/Wind Harmer
1.559
339241AF1-083 GEN
Solar/Wind Harmer
1.713
960001AF2-291 GEN
Solar/Wind Harmer
3.11
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.508
945681AF1-233 GEN
Solar/Wind Harmer
18.298
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
276621W2-048 GEN
Solar/Wind Harmer
5.637
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
944031AF1-071 GEN
Solar/Wind Harmer
0.897
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
276655WTG1_EQ
Solar/Wind Harmer
7.743
276656WTG2_EQ
Solar/Wind Harmer
1.025
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
274822ROCKFORD ;11
Adder
17.258
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
24385905FR-11G C
Solar/Wind Harmer
4.036
24386605FR-22G C
Solar/Wind Harmer
2.088
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
27.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.16
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971277AH1-098 GEN
Solar/Wind Harmer
7.418
942671AE2-283 GEN
Solar/Wind Harmer
8.665
270013AE1-250 PV
Solar/Wind Harmer
3.249
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
971485AH1-239 GEN
Solar/Wind Harmer
8.494
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964781AG1-341 GEN
Solar/Wind Harmer
10.966
339236AF1-050_GEN
Solar/Wind Harmer
1.872
942891AE2-308 GEN
Solar/Wind Harmer
10.171
964571AG1-320 GEN
Solar/Wind Harmer
8.183
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.211
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.973
970563AG2-360 GEN
50/50
45.815
970417AG2-272 GEN
50/50
3.733
962751AG1-124 GEN
Solar/Wind Harmer
18.82
958121AF2-106 GEN
Solar/Wind Harmer
9.404
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.809
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270018AE2-047 C O1
Solar/Wind Harmer
1.821
960911AF2-382 GEN
Solar/Wind Harmer
10.944
270016AE1-250 BESS
Solar/Wind Harmer
3.249
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
972103AH1-617 GEN
Solar/Wind Harmer
25.825
24686405CER G5
Adder
9.792
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
972273AH1-721 GEN
Adder
89.284
24721905FLATG4
Adder
21.675
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970653AG2-424 GEN
Solar/Wind Harmer
0.706
3429391JKCT 9G
Adder
8.399
971191AH1-055 GEN
Solar/Wind Harmer
18.819
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
972167AH1-666 GEN
Solar/Wind Harmer
7.764
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196008MFTGT1
Adder
1.252
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
970879AG2-548 GEN
Solar/Wind Harmer
7.336
252524AE2-267 GEN
Solar/Wind Harmer
1.441
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
942481AE2-261 GEN
Solar/Wind Harmer
27.222
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728705AND G3
Adder
7.279
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
965931AG1-462 GEN
Solar/Wind Harmer
22.754
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.796
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971329AH1-144 GEN
Solar/Wind Harmer
11.725
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270069AE2-166 C O1
Solar/Wind Harmer
14.876
971313AH1-133 GEN
Solar/Wind Harmer
9.325
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
970281AG2-184 GEN
Solar/Wind Harmer
27.117
971981AH1-535 GEN
Solar/Wind Harmer
12.558
962211AG1-066 GEN
Solar/Wind Harmer
3
971061AG2-657 GEN
Solar/Wind Harmer
10.986
3429211JKCT 2G
Adder
11.868
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.323
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
25196508WSDLE4
Adder
7.765
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
270356AE2-297 GEN
Solar/Wind Harmer
4.144
253406AD2-031_GEN
Solar/Wind Harmer
1.146
963841AG1-237 GEN
Solar/Wind Harmer
9.753
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
959341AF2-225 GEN
Solar/Wind Harmer
13.316
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
274728ELWOOD EC;5P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
316468AD1-105 GEN
Solar/Wind Helper
1.088
24386405FR-21G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960611AF2-352 GEN
Solar/Wind Harmer
2.072
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274696ROCKY RD ;4P
Adder
9.954
274695ROCKY RD ;2P
Adder
9.725
274693ROCKY RD ;1P
Adder
9.629
274697ROCKY RD ;3P
Adder
2.642
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.646
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
24387305FR-4G C
Solar/Wind Harmer
2.468
971087AG2-675 GEN
Solar/Wind Harmer
3.32
965091AG1-374 GEN
Solar/Wind Harmer
26.73
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274760LEE CO EC;1U
Adder
8.219
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.844
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
24386205FR-12G C
Solar/Wind Harmer
2.082
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.16
270173AC1-122 GEN
Solar/Wind Harmer
3.444
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
3147312GRETNA
Solar/Wind Harmer
-0.005
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
958131AF2-107 GEN
Solar/Wind Harmer
7.106
24735205WLF2G2
Adder
8.021
971687AH1-348 GEN
Solar/Wind Harmer
1.358
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
24723205RIVRG3
Adder
22.944
24686505CER G6
Adder
9.87
972203AH1-686 GEN
Adder
2.703
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339211AE2-254 GEN
Solar/Wind Harmer
1.56
339241AF1-083 GEN
Solar/Wind Harmer
1.714
960001AF2-291 GEN
Solar/Wind Harmer
3.112
3429241JKCT 3G
Adder
12.024
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
943111AE2-339 GEN
Solar/Wind Harmer
0.882
339221AD2-048_GEN
Solar/Wind Harmer
1.509
945681AF1-233 GEN
Solar/Wind Harmer
18.311
970091AG2-072 GEN
Adder
73.991
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252510AF1-249 C
Solar/Wind Harmer
0.383
25194608D.CRK4
Adder
1.508
971073AG2-665 GEN
Solar/Wind Harmer
1.066
965911AG1-460 GEN
Solar/Wind Harmer
1.27
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
276621W2-048 GEN
Solar/Wind Harmer
5.641
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
944031AF1-071 GEN
Solar/Wind Harmer
0.898
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
276655WTG1_EQ
Solar/Wind Harmer
7.748
276656WTG2_EQ
Solar/Wind Harmer
1.026
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274761LEE CO EC;2U
Adder
8.219
274766LEE CO EC;7U
Adder
8.123
274822ROCKFORD ;11
Adder
17.27
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
274676JOLIET 29;8U
Adder
26.631
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
315821AE2-092 GEN
Solar/Wind Helper
3.228
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.293
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
24385905FR-11G C
Solar/Wind Harmer
4.039
24386605FR-22G C
Solar/Wind Harmer
2.09
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
TVALTFEXP_TVA->PJM
CLTF
10.603
CPLELTFEXP_CPLE->PJM
CLTF
6.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6590.12
MW Contribution:
31.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
13.022
24721705FLATG2
50/50
43.628
24723005RIVRG1
Adder
35.405
24723105RIVRG2
Adder
35.405
970913AG2-568 GEN
Solar/Wind Harmer
10.639
24728205BUCHG1
Adder
6.758
971225AH1-072 GEN
Solar/Wind Harmer
2.946
971227AH1-073 GEN
Solar/Wind Harmer
2.946
270214AC2-123 GEN
Solar/Wind Harmer
3.099
971277AH1-098 GEN
Solar/Wind Harmer
5.287
927014AC1-188 GEN
Solar/Wind Harmer
1.995
24387305FR-4G C
Solar/Wind Harmer
6.235
966841AG1-555 GEN
Solar/Wind Harmer
3.081
945391AF1-204 GEN
Solar/Wind Harmer
17.098
970241AG2-163 GEN
Solar/Wind Harmer
30.673
270180AB1-006 GEN1
Solar/Wind Harmer
8.812
24697605MDL-3G C
Solar/Wind Harmer
4.516
24755605MDL-5G
Solar/Wind Harmer
2.954
24697905MDL-4G C
Solar/Wind Harmer
2.811
270181AB1-006 GEN2
Solar/Wind Harmer
0.876
945421AF1-207 GEN
Solar/Wind Harmer
17.195
957841AF2-078 GEN
Solar/Wind Harmer
7.402
270583AD2-179 GEN
Solar/Wind Harmer
12.237
274770LINCOLN ;1U
Adder
7.555
274771LINCOLN ;2U
Adder
7.555
274880W4-005 GEN4
Solar/Wind Harmer
3.683
276174W4-005 GEN2
Solar/Wind Harmer
3.683
276916AD2-100_GEN
Solar/Wind Harmer
25.572
276911AD2-131_GEN
Solar/Wind Harmer
5.168
276615X2-022 GEN
Solar/Wind Harmer
2.385
276838X2-022 GEN2
Solar/Wind Harmer
0.283
960611AF2-352 GEN
Solar/Wind Harmer
2.831
942111AE2-223 GEN
Solar/Wind Harmer
9.977
24289405MTG1
50/50
11.749
24318705GVG2
50/50
12.071
24722005FLATG5
50/50
2.938
24721905FLATG4
50/50
53.66
962771AG1-126 GEN
Solar/Wind Harmer
67.342
970153AG2-106 GEN
Solar/Wind Harmer
29.364
24686405CER G5
Adder
15.004
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.789
960911AF2-382 GEN
Solar/Wind Harmer
11.34
972103AH1-617 GEN
Solar/Wind Harmer
29.779
971461AH1-227 GEN
Solar/Wind Harmer
7.556
971191AH1-055 GEN
Solar/Wind Harmer
27.281
270346AE1-212 GEN
Solar/Wind Harmer
12.339
943031AE2-326 GEN
Solar/Wind Harmer
4.878
957541AF2-048 GEN
Solar/Wind Harmer
1.995
24386205FR-12G C
Solar/Wind Harmer
5.26
970193AG2-126 GEN
Solar/Wind Harmer
18.403
24690905MDL-1G C
Solar/Wind Harmer
9.836
970781AG2-491 GEN
Solar/Wind Harmer
12.252
958121AF2-106 GEN
Solar/Wind Harmer
5.546
274772LINCOLN ;3U
Adder
7.555
276785W4-005 GEN1
Solar/Wind Harmer
3.683
971993AH1-541 GEN
Solar/Wind Harmer
11.253
942481AE2-261 GEN
Solar/Wind Harmer
36.404
957381AF2-032 GEN
Solar/Wind Harmer
2.435
965091AG1-374 GEN
Solar/Wind Harmer
36.515
959611AF2-252 GEN
Solar/Wind Harmer
2.831
970707AG2-453 GEN
Solar/Wind Harmer
34.064
939351AE1-166 GEN
Solar/Wind Harmer
7.204
972259AH1-714 GEN
Adder
23.175
943121AE2-341 GEN
Solar/Wind Harmer
18.219
943591AF1-030 GEN
Solar/Wind Harmer
12.146
972273AH1-721 GEN
Adder
101.006
274729ELWOOD EC;1P
Adder
19.933
274730ELWOOD EC;6P
Adder
19.933
274734ELWOOD EC;8P
Adder
19.933
274736ELWOOD EC;9P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
35.87
972038AH1-567 GEN2
Adder
0.442
274760LEE CO EC;1U
Adder
11.266
274767LEE CO EC;8U
Adder
11.133
274826FISK ;BP
Adder
13.253
237048AF1-022 C
Solar/Wind Helper
0.199
237046AF1-021 C
Solar/Wind Helper
0.345
235058AG1-386 C
Solar/Wind Helper
0.46
23562501BACKB
Solar/Wind Helper
0.911
202652Y1-033 WT C
Solar/Wind Helper
0.565
964991AG1-363 GEN
Solar/Wind Helper
3.718
238127S14_GEN_2
Solar/Wind Helper
0.686
20092526R32
Solar/Wind Helper
1.14
20303426NA_O38_P22
Solar/Wind Helper
0.969
203993AD2-133_GEN1
Solar/Wind Helper
1
203854AF2-039 C
Solar/Wind Helper
0.309
238108AE1-109 GEN1
Solar/Wind Helper
0.086
238110AE1-109 GEN3
Solar/Wind Helper
0.086
20398826ARMNA MT
Solar/Wind Helper
1.443
962511AG1-100 GEN
Solar/Wind Helper
0.445
941421AE2-139 GEN
Solar/Wind Helper
2.224
276897AD1-100 C
Solar/Wind Harmer
56.428
962691AG1-118 GEN
Solar/Wind Harmer
36.394
274696ROCKY RD ;4P
Adder
13.825
274695ROCKY RD ;2P
Adder
13.506
274693ROCKY RD ;1P
Adder
13.373
274697ROCKY RD ;3P
Adder
3.669
274674JOLIET 9 ;6U
Adder
18.672
274683WAUKEGAN ;8U
Adder
25.548
274683WAUKEGAN ;8U
Adder
21.536
972235AH1-702 GEN1
Adder
3.053
972236AH1-702 GEN2
Adder
2.655
274764LEE CO EC;5U
Adder
11.292
274765LEE CO EC;6U
Adder
11.292
274762LEE CO EC;3U
Adder
11.266
274763LEE CO EC;4U
Adder
11.16
237043AE2-125 C
Solar/Wind Helper
0.181
23585401KL_K28_T16
Solar/Wind Helper
1.305
23751201ROTHROCK
Solar/Wind Helper
0.749
254304AE2-114 C
Solar/Wind Helper
0.216
254305AE2-115 C
Solar/Wind Helper
0.216
962101AG1-054 GEN
Solar/Wind Helper
0.644
235054AD2-180 GEN
Solar/Wind Helper
1.728
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.246
238117U2-030
Solar/Wind Helper
0.291
20083426SW_E13_K22
Solar/Wind Helper
0.055
235531U2-073 GEN
Solar/Wind Helper
2.761
946071AF1-272 GEN
Solar/Wind Helper
2.663
20088826HIGHLAND
Solar/Wind Helper
0.88
203818AF1-086 GEN
Solar/Wind Helper
1.65
203961AE2-224 GEN
Solar/Wind Helper
2.354
946381AF1-302 GEN
Solar/Wind Helper
0.217
203853AF1-134 C O1
Solar/Wind Helper
0.466
203946AE2-131 C
Solar/Wind Helper
0.461
203804AE2-113_GEN
Solar/Wind Helper
1.698
940863AE2-074 GEN
Solar/Wind Helper
0.444
203954AE2-126 C
Solar/Wind Helper
0.458
203835AF1-098 GEN
Solar/Wind Helper
1.78
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
13.022
24318705GVG2
50/50
12.071
24721805FLATG3
50/50
2.938
962761AG1-125 GEN
Solar/Wind Harmer
67.342
970149AG2-104 GEN
Solar/Wind Harmer
41.584
970155AG2-107 GEN
Solar/Wind Harmer
29.364
24723205RIVRG3
Adder
35.405
972203AH1-686 GEN
Adder
4.304
24686505CER G6
Adder
15.123
944971AF1-162 GEN
Solar/Wind Harmer
11.902
971403AH1-188 GEN
Solar/Wind Harmer
23.698
270331AC1-082 GEN3
Solar/Wind Harmer
0.791
960001AF2-291 GEN
Solar/Wind Harmer
4.817
24728305BUCHG2
Adder
6.758
971687AH1-348 GEN
Solar/Wind Harmer
1.473
24735205WLF2G2
Adder
7.848
970091AG2-072 GEN
Adder
102.767
24385905FR-11G C
Solar/Wind Harmer
10.201
24386605FR-22G C
Solar/Wind Harmer
5.279
963741AG1-226 GEN
Solar/Wind Harmer
55.212
24791305MDL-5G
Solar/Wind Harmer
2.954
972207SS24-0001
Solar/Wind Harmer
26.861
274773LINCOLN ;4U
Adder
7.555
274774LINCOLN ;5U
Adder
7.555
276686W4-005 GEN3
Solar/Wind Harmer
3.683
276621W2-048 GEN
Solar/Wind Harmer
7.596
940581AE2-045 GEN
Solar/Wind Harmer
12.418
971605AH1-302 GEN
Solar/Wind Harmer
10.618
965911AG1-460 GEN
Solar/Wind Harmer
1.699
276655WTG1_EQ
Solar/Wind Harmer
10.623
276656WTG2_EQ
Solar/Wind Harmer
1.406
939741AE1-205 GEN
Solar/Wind Harmer
24.341
939401AE1-172 GEN
Solar/Wind Harmer
16.947
941551AE2-152 GEN
Solar/Wind Harmer
5.509
274871GR RIDGE ;2U
Solar/Wind Harmer
9.337
274847GR RIDGE ;BU
Solar/Wind Harmer
6.14
274745AC1-111 GEN9
Adder
6.785
971997AH1-543 GEN
Solar/Wind Harmer
19.104
274674JOLIET 9 ;6U
Adder
18.672
274732ELWOOD EC;7P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
37.198
274828WAUKEGAN ;BP
Adder
13.392
274822ROCKFORD ;11
Adder
23.778
274761LEE CO EC;2U
Adder
11.266
274766LEE CO EC;7U
Adder
11.133
274802UNIV PARK;5U
Adder
6.986
238185AF2-356 C
Solar/Wind Helper
2.23
254303AC2-168 GEN
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.252
20089026BF_G21_K23
Solar/Wind Helper
0.468
20084626FORWARD
Solar/Wind Helper
0.35
238120AE2-309 GEN
Solar/Wind Helper
0.432
238126S14_GEN_1
Solar/Wind Helper
0.686
964201AG1-281 GEN
Solar/Wind Helper
0.472
23751101LEADS_P59
Solar/Wind Helper
1.885
20091526CHSTN_FL
Solar/Wind Helper
0.569
20090526Q36
Solar/Wind Helper
1
203952AE2-129 C
Solar/Wind Helper
0.461
203855AF2-088 C
Solar/Wind Helper
0.149
238109AE1-109 GEN2
Solar/Wind Helper
0.086
24721605FLATG1
50/50
2.938
957241AF2-018 GEN
Solar/Wind Harmer
7.557
270053AF1-130 C
Solar/Wind Harmer
30.195
270399AC1-101 GEN
Solar/Wind Harmer
7.142
270400AC1-102 GEN
Solar/Wind Harmer
7.142
941621AE2-160 GEN
Adder
5.016
970281AG2-184 GEN
Solar/Wind Harmer
31.268
971313AH1-133 GEN
Solar/Wind Harmer
8.781
962211AG1-066 GEN
Solar/Wind Harmer
3.415
24734705WLF1G3
Adder
7.988
24734805WLF1G4
Adder
7.988
24734905WLF1G5
Adder
7.988
971061AG2-657 GEN
Solar/Wind Harmer
12.335
24735105WLF2G1
Adder
7.848
966391AG1-508 GEN
Solar/Wind Harmer
4.607
971985AH1-537 GEN
Solar/Wind Harmer
23.357
971331AH1-145 GEN
Solar/Wind Harmer
11.822
971329AH1-144 GEN
Solar/Wind Harmer
7.552
270444AC2-157 GEN1
Solar/Wind Harmer
7.062
270445AC2-157 GEN2
Solar/Wind Harmer
7.062
971981AH1-535 GEN
Solar/Wind Harmer
12.497
24386405FR-21G C
Solar/Wind Harmer
5.279
24387005FR-3G C
Solar/Wind Harmer
4.855
963841AG1-237 GEN
Solar/Wind Harmer
13.411
946581AF1-322 GEN
Solar/Wind Harmer
12.536
24691005MDL-2G C
Solar/Wind Harmer
4.53
274775LINCOLN ;6U
Adder
7.555
274776LINCOLN ;7U
Adder
7.555
274777LINCOLN ;8U
Adder
7.555
944221AF1-090 GEN
Solar/Wind Harmer
13.317
276668AB2-070 GEN1
Solar/Wind Harmer
2.697
276848AB2-070 GEN3
Solar/Wind Harmer
2.697
276849AB2-070 GEN2
Solar/Wind Harmer
2.697
276763AC1-053 GEN1
Solar/Wind Harmer
4.814
276764AC1-053 GEN2
Solar/Wind Harmer
4.814
274853TWINGROVE;U1
Solar/Wind Harmer
8.769
274854TWINGROVE;U2
Solar/Wind Harmer
8.585
276726Z2-087_GEN
Solar/Wind Harmer
9.623
959341AF2-225 GEN
Solar/Wind Harmer
18.256
274863CRW1-WTG
Solar/Wind Harmer
6.788
274864CRW2-WTG
Solar/Wind Harmer
6.788
970169AG2-114 GEN
Solar/Wind Harmer
12.163
959141AF2-205 GEN
Solar/Wind Harmer
7.348
970833AG2-524 GEN
Solar/Wind Harmer
10.601
970833AG2-524 GEN
Solar/Wind Harmer
4.931
274744AC1-111 GEN8
Adder
6.785
274746AC1-111 G10
Adder
6.785
958391AF2-133 GEN
Solar/Wind Harmer
11.004
972228AH1-698 GEN2
Adder
4.493
972227AH1-698 GEN1
Adder
3.164
274728ELWOOD EC;5P
Adder
19.933
274731ELWOOD EC;2P
Adder
19.933
274733ELWOOD EC;3P
Adder
19.933
274735ELWOOD EC;4P
Adder
19.933
274675JOLIET 29;7U
Adder
37.198
274675JOLIET 29;7U
Adder
35.87
274687WILL CNTY;4U
Adder
33.865
274687WILL CNTY;4U
Adder
33.865
274823ROCKFORD ;21
Adder
23.605
274800UNIV PARK;3U
Adder
7.06
274801UNIV PARK;4U
Adder
7.06
274827FISK ;RP
Adder
9.392
972267AH1-718 GEN
Adder
5.041
23750501ELLIOTTS
Solar/Wind Helper
0.679
23652301WDPWR_K20
Solar/Wind Helper
0.146
241997AF1-093 GEN
Solar/Wind Helper
0.252
241985AE1-237 GEN
Solar/Wind Helper
0.246
241982AE2-343 S C
Solar/Wind Helper
0.221
23750701CROSSCHOOL
Solar/Wind Helper
1.209
203955AF1-039 C O1
Solar/Wind Helper
0.373
238118U2-030_1
Solar/Wind Helper
0.291
20089126CSLMN_L13
Solar/Wind Helper
0.591
20089226LOOKOUT
Solar/Wind Helper
0.59
20088926STNY CRK
Solar/Wind Helper
0.806
203940AF1-140 C
Solar/Wind Helper
0.388
20094526CT_V3-030
Solar/Wind Helper
0.462
20088626ARWF_N39
Solar/Wind Helper
1.182
203846AF2-130 C
Solar/Wind Helper
0.443
20334926Z1-069 C
Solar/Wind Helper
1.308
926823AC1-168 GEN
Solar/Wind Harmer
0.606
203830AF1-094 GEN
Solar/Wind Helper
0.449
203979AG1-198 GEN
Solar/Wind Helper
0.27
961971AG1-040 GEN
Solar/Wind Helper
0.447
203947AF1-006 C
Solar/Wind Helper
0.483
LAGNLTFEXP_LAGN->PJM
CLTF
23.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.518
TVALTFEXP_TVA->PJM
CLTF
11.786
CPLELTFEXP_CPLE->PJM
CLTF
6.948
CBM West 2LTFEXP_CBM-W2->PJM
CBM
158.57
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.868
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.575
MECLTFEXP_MEC->PJM
CLTF
20.238
SIGELTFEXP_SIGE->PJM
CLTF
0.64
NYPJM->LTFIMP_NY
CLTF
5.358
LGEELTFEXP_LGEE->PJM
CLTF
8.414
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.421

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
32.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
22.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
33.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
32.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
270214AC2-123 GEN
Solar/Wind Harmer
3.345
971277AH1-098 GEN
Solar/Wind Harmer
5.707
270583AD2-179 GEN
Solar/Wind Harmer
13.318
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971485AH1-239 GEN
Solar/Wind Harmer
9.077
24289405MTG1
50/50
12.684
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
24318705GVG2
50/50
13.247
962761AG1-125 GEN
Solar/Wind Harmer
91.718
970149AG2-104 GEN
Solar/Wind Harmer
56.636
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24686505CER G6
Adder
16.11
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
960001AF2-291 GEN
Solar/Wind Harmer
5.171
24728305BUCHG2
Adder
7.18
971687AH1-348 GEN
Solar/Wind Harmer
1.537
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
970091AG2-072 GEN
Adder
90.254
943811AF1-049 GEN
Solar/Wind Harmer
4.254
339211AE2-254 GEN
Solar/Wind Harmer
1.701
339241AF1-083 GEN
Solar/Wind Harmer
1.857
971073AG2-665 GEN
Solar/Wind Harmer
1.298
964901AG1-354 GEN
Solar/Wind Harmer
16.708
3429241JKCT 3G
Adder
13.15
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
943111AE2-339 GEN
Solar/Wind Harmer
0.965
339221AD2-048_GEN
Solar/Wind Harmer
1.667
945681AF1-233 GEN
Solar/Wind Harmer
20.299
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252516AE2-318_GEN
Solar/Wind Harmer
9.778
252510AF1-249 C
Solar/Wind Harmer
0.407
270173AC1-122 GEN
Solar/Wind Harmer
1.632
25194608D.CRK4
Adder
1.596
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24728605AND G2
Adder
3.684
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276621W2-048 GEN
Solar/Wind Harmer
5.925
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24385905FR-11G C
Solar/Wind Harmer
7.803
24386605FR-22G C
Solar/Wind Harmer
4.038
24791305MDL-5G
Solar/Wind Harmer
2.228
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
276655WTG1_EQ
Solar/Wind Harmer
8.017
276656WTG2_EQ
Solar/Wind Harmer
1.061
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
274766LEE CO EC;7U
Adder
8.294
274822ROCKFORD ;11
Adder
17.595
274828WAUKEGAN ;BP
Adder
9.796
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270399AC1-101 GEN
Solar/Wind Harmer
7.582
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
971313AH1-133 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
32.451
971061AG2-657 GEN
Solar/Wind Harmer
13.518
24734705WLF1G3
Adder
8.32
24734805WLF1G4
Adder
8.32
24734905WLF1G5
Adder
8.32
962211AG1-066 GEN
Solar/Wind Harmer
3.487
966391AG1-508 GEN
Solar/Wind Harmer
4.969
24735105WLF2G1
Adder
8.13
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971329AH1-144 GEN
Solar/Wind Harmer
8.204
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
270291AC1-194 GEN
Solar/Wind Harmer
5.169
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270356AE2-297 GEN
Solar/Wind Harmer
4.331
24386405FR-21G C
Solar/Wind Harmer
4.038
24387005FR-3G C
Solar/Wind Harmer
3.714
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
24691005MDL-2G C
Solar/Wind Harmer
3.418
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
276726Z2-087_GEN
Solar/Wind Harmer
7.262
959341AF2-225 GEN
Solar/Wind Harmer
13.777
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
274744AC1-111 GEN8
Adder
4.935
274746AC1-111 G10
Adder
4.935
274728ELWOOD EC;5P
Adder
14.442
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
274735ELWOOD EC;4P
Adder
14.442
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23750501ELLIOTTS
Solar/Wind Helper
0.617
23652301WDPWR_K20
Solar/Wind Helper
0.134
241997AF1-093 GEN
Solar/Wind Helper
0.235
241985AE1-237 GEN
Solar/Wind Helper
0.229
241982AE2-343 S C
Solar/Wind Helper
0.206
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
20089126CSLMN_L13
Solar/Wind Helper
0.537
20089226LOOKOUT
Solar/Wind Helper
0.536
238118U2-030_1
Solar/Wind Helper
0.261
24289405MTG1
50/50
12.684
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
24318705GVG2
50/50
13.247
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
24686405CER G5
Adder
15.983
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
971461AH1-227 GEN
Solar/Wind Harmer
7.89
971191AH1-055 GEN
Solar/Wind Harmer
28.586
270346AE1-212 GEN
Solar/Wind Harmer
13.435
943031AE2-326 GEN
Solar/Wind Harmer
5.264
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
972273AH1-721 GEN
Adder
96.087
270030AE2-140 GEN
Solar/Wind Harmer
23
970093AG2-073 GEN
Solar/Wind Harmer
5.967
339206AE1-143 GEN
Solar/Wind Harmer
2.39
970879AG2-548 GEN
Solar/Wind Harmer
8.927
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
3429391JKCT 9G
Adder
9.153
270186AC1-089 GEN
Solar/Wind Harmer
6.641
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
25196008MFTGT1
Adder
1.357
970193AG2-126 GEN
Solar/Wind Harmer
14.771
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
25196608WSDLE5
Adder
8.266
942481AE2-261 GEN
Solar/Wind Harmer
28.724
24728705AND G3
Adder
7.705
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
962751AG1-124 GEN
Solar/Wind Harmer
8.593
276785W4-005 GEN1
Solar/Wind Harmer
2.856
971993AH1-541 GEN
Solar/Wind Harmer
8.726
24386205FR-12G C
Solar/Wind Harmer
4.023
965091AG1-374 GEN
Solar/Wind Harmer
27.739
959611AF2-252 GEN
Solar/Wind Harmer
2.15
24690905MDL-1G C
Solar/Wind Harmer
7.42
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274760LEE CO EC;1U
Adder
8.393
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274729ELWOOD EC;1P
Adder
14.442
274730ELWOOD EC;6P
Adder
14.442
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
235058AG1-386 C
Solar/Wind Helper
0.425
202652Y1-033 WT C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
0.816
964991AG1-363 GEN
Solar/Wind Helper
3.339
942891AE2-308 GEN
Solar/Wind Harmer
11.161
971073AG2-665 GEN
Solar/Wind Harmer
8.927
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
964781AG1-341 GEN
Solar/Wind Harmer
11.789
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972043AH1-570 GEN
Solar/Wind Harmer
2.731
972045AH1-571 GEN
Solar/Wind Harmer
2.185
971125AH1-004 GEN
Solar/Wind Harmer
4.363
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
252509AD1-136 GEN
Solar/Wind Harmer
0.26
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25183208HLCRTG
Solar/Wind Harmer
5.886
25194408D.CRK1
Adder
7.34
25194508D.CRK3
Adder
1.372
276916AD2-100_GEN
Solar/Wind Harmer
20.233
276911AD2-131_GEN
Solar/Wind Harmer
4.089
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276615X2-022 GEN
Solar/Wind Harmer
1.861
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
24387305FR-4G C
Solar/Wind Harmer
4.769
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697605MDL-3G C
Solar/Wind Harmer
3.407
24755605MDL-5G
Solar/Wind Harmer
2.228
24697905MDL-4G C
Solar/Wind Harmer
2.121
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
942111AE2-223 GEN
Solar/Wind Harmer
7.529
24728805RICHG1
Adder
3.447
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
274765LEE CO EC;6U
Adder
8.413
274762LEE CO EC;3U
Adder
8.393
274763LEE CO EC;4U
Adder
8.314
972235AH1-702 GEN1
Adder
2.262
972236AH1-702 GEN2
Adder
1.967
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274696ROCKY RD ;4P
Adder
10.103
274695ROCKY RD ;2P
Adder
9.87
274693ROCKY RD ;1P
Adder
9.773
274697ROCKY RD ;3P
Adder
2.681
274674JOLIET 9 ;6U
Adder
13.524
237043AE2-125 C
Solar/Wind Helper
0.166
254304AE2-114 C
Solar/Wind Helper
0.201
254305AE2-115 C
Solar/Wind Helper
0.201
962101AG1-054 GEN
Solar/Wind Helper
0.598
241967AE2-285_GEN
Solar/Wind Helper
0.586
241801AE1-079 GEN
Solar/Wind Helper
0.229
23585401KL_K28_T16
Solar/Wind Helper
1.176
23751201ROTHROCK
Solar/Wind Helper
0.671
235054AD2-180 GEN
Solar/Wind Helper
1.553
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
945421AF1-207 GEN
Solar/Wind Harmer
3.217
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
274676JOLIET 29;8U
Adder
26.921
254303AC2-168 GEN
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
20089026BF_G21_K23
Solar/Wind Helper
0.425
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
TVALTFEXP_TVA->PJM
CLTF
11.07
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
20.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
34.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
8.512
972103AH1-617 GEN
Solar/Wind Harmer
33.161
971191AH1-055 GEN
Solar/Wind Harmer
30.574
270346AE1-212 GEN
Solar/Wind Harmer
14.67
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
26.764
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
5.329
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.453
942481AE2-261 GEN
Solar/Wind Harmer
34.409
957381AF2-032 GEN
Solar/Wind Harmer
2.3
24379505HDWTR1G C
Solar/Wind Harmer
9.002
270240V3-007_GEN2
Solar/Wind Harmer
7.043
276785W4-005 GEN1
Solar/Wind Harmer
3.438
971993AH1-541 GEN
Solar/Wind Harmer
10.504
24386205FR-12G C
Solar/Wind Harmer
4.868
247642Z2-115 C
Solar/Wind Harmer
0.072
965461AG1-414 GEN
Solar/Wind Harmer
2.547
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
971277AH1-098 GEN
Solar/Wind Harmer
6.62
270583AD2-179 GEN
Solar/Wind Harmer
16.289
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
13.25
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972043AH1-570 GEN
Solar/Wind Harmer
3.285
972045AH1-571 GEN
Solar/Wind Harmer
2.628
971125AH1-004 GEN
Solar/Wind Harmer
5.238
970107AG2-081 GEN
Solar/Wind Harmer
3.929
966021AG1-471 GEN
Solar/Wind Harmer
7.071
971485AH1-239 GEN
Solar/Wind Harmer
10.457
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
964781AG1-341 GEN
Solar/Wind Harmer
13.643
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276916AD2-100_GEN
Solar/Wind Harmer
24.22
276911AD2-131_GEN
Solar/Wind Harmer
4.895
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276615X2-022 GEN
Solar/Wind Harmer
2.236
276838X2-022 GEN2
Solar/Wind Harmer
0.266
926881AC1-175 GEN
Solar/Wind Harmer
6.354
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
960001AF2-291 GEN
Solar/Wind Harmer
5.313
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.658
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
339221AD2-048_GEN
Solar/Wind Harmer
2.01
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
970653AG2-424 GEN
Solar/Wind Harmer
6.236
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
12.45
252510AF1-249 C
Solar/Wind Harmer
0.517
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
962761AG1-125 GEN
Solar/Wind Harmer
38.013
970149AG2-104 GEN
Solar/Wind Harmer
23.473
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
3147312GRETNA
Solar/Wind Harmer
-0.003
270222AC2-111 GEN
Solar/Wind Harmer
5.217
944031AF1-071 GEN
Solar/Wind Harmer
1.174
963741AG1-226 GEN
Solar/Wind Harmer
51.846
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270437AC2-090 C
Solar/Wind Harmer
6.354
270239V3-007_GEN1
Solar/Wind Harmer
1.959
276686W4-005 GEN3
Solar/Wind Harmer
3.438
24385905FR-11G C
Solar/Wind Harmer
9.442
24386605FR-22G C
Solar/Wind Harmer
4.886
276903AD2-071 C
Solar/Wind Harmer
11.325
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
274822ROCKFORD ;11
Adder
21.436
25326309TAIT D
Adder
1.195
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
270053AF1-130 C
Solar/Wind Harmer
32.909
270399AC1-101 GEN
Solar/Wind Harmer
7.81
270400AC1-102 GEN
Solar/Wind Harmer
7.81
971313AH1-133 GEN
Solar/Wind Harmer
10.201
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
5.744
970281AG2-184 GEN
Solar/Wind Harmer
34.819
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
962211AG1-066 GEN
Solar/Wind Harmer
3.81
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
14.005
971985AH1-537 GEN
Solar/Wind Harmer
26.103
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
253406AD2-031_GEN
Solar/Wind Harmer
1.524
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
24386405FR-21G C
Solar/Wind Harmer
4.886
24387005FR-3G C
Solar/Wind Harmer
4.493
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
247621Y3-024
Adder
0.264
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
30.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.32
24318705GVG2
50/50
11.469
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
24686405CER G5
Adder
14.607
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
971191AH1-055 GEN
Solar/Wind Harmer
27.435
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
971461AH1-227 GEN
Solar/Wind Harmer
7.34
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
943031AE2-326 GEN
Solar/Wind Harmer
4.698
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
270186AC1-089 GEN
Solar/Wind Harmer
7.225
3429391JKCT 9G
Adder
9.84
270367AC2-061_GEN
Solar/Wind Harmer
3.742
958121AF2-106 GEN
Solar/Wind Harmer
5.343
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
972167AH1-666 GEN
Solar/Wind Harmer
9.374
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
970193AG2-126 GEN
Solar/Wind Harmer
17.459
25196008MFTGT1
Adder
1.55
24386205FR-12G C
Solar/Wind Harmer
4.921
24728705AND G3
Adder
9.201
24728505AND G1
Adder
4.399
252507AC2-088 GEN
Solar/Wind Harmer
2.051
942481AE2-261 GEN
Solar/Wind Harmer
34.173
957381AF2-032 GEN
Solar/Wind Harmer
2.285
24690905MDL-1G C
Solar/Wind Harmer
9.169
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
276785W4-005 GEN1
Solar/Wind Harmer
3.443
971993AH1-541 GEN
Solar/Wind Harmer
10.521
247642Z2-115 C
Solar/Wind Harmer
0.073
965091AG1-374 GEN
Solar/Wind Harmer
33.954
970879AG2-548 GEN
Solar/Wind Harmer
9.054
959611AF2-252 GEN
Solar/Wind Harmer
2.632
965461AG1-414 GEN
Solar/Wind Harmer
2.564
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274760LEE CO EC;1U
Adder
10.407
274767LEE CO EC;8U
Adder
10.284
25196608WSDLE5
Adder
9.576
274682WAUKEGAN ;7U
Adder
20.049
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
274730ELWOOD EC;6P
Adder
18.315
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
927014AC1-188 GEN
Solar/Wind Harmer
2.06
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971277AH1-098 GEN
Solar/Wind Harmer
5.094
942891AE2-308 GEN
Solar/Wind Harmer
11.926
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972043AH1-570 GEN
Solar/Wind Harmer
2.957
972045AH1-571 GEN
Solar/Wind Harmer
2.366
971125AH1-004 GEN
Solar/Wind Harmer
4.718
970107AG2-081 GEN
Solar/Wind Harmer
3.539
270583AD2-179 GEN
Solar/Wind Harmer
11.79
24289405MTG1
50/50
11.32
243186AF1-051 GEN
50/50
12.373
24318705GVG2
50/50
11.469
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
24686505CER G6
Adder
14.723
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
960001AF2-291 GEN
Solar/Wind Harmer
4.782
962761AG1-125 GEN
Solar/Wind Harmer
51.105
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24728305BUCHG2
Adder
6.531
971687AH1-348 GEN
Solar/Wind Harmer
1.432
24735205WLF2G2
Adder
7.594
970091AG2-072 GEN
Adder
98.735
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
970653AG2-424 GEN
Solar/Wind Harmer
5.716
339241AF1-083 GEN
Solar/Wind Harmer
1.965
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
963741AG1-226 GEN
Solar/Wind Harmer
51.931
25196008MFTGT1
Adder
1.6
24385905FR-11G C
Solar/Wind Harmer
9.545
24386605FR-22G C
Solar/Wind Harmer
4.939
24728605AND G2
Adder
4.399
965911AG1-460 GEN
Solar/Wind Harmer
1.595
24791305MDL-5G
Solar/Wind Harmer
2.754
276621W2-048 GEN
Solar/Wind Harmer
7.111
276686W4-005 GEN3
Solar/Wind Harmer
3.443
25196808ZIMRHP
Adder
86.01
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276903AD2-071 C
Solar/Wind Harmer
11.309
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
276655WTG1_EQ
Solar/Wind Harmer
9.862
276656WTG2_EQ
Solar/Wind Harmer
1.306
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
25194608D.CRK4
Adder
1.843
274761LEE CO EC;2U
Adder
10.407
274766LEE CO EC;7U
Adder
10.284
274822ROCKFORD ;11
Adder
21.932
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
238185AF2-356 C
Solar/Wind Helper
2.191
254303AC2-168 GEN
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.455
238120AE2-309 GEN
Solar/Wind Helper
0.424
238126S14_GEN_1
Solar/Wind Helper
0.674
23751101LEADS_P59
Solar/Wind Helper
1.865
20084626FORWARD
Solar/Wind Helper
0.338
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
203855AF2-088 C
Solar/Wind Helper
0.143
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
235058AG1-386 C
Solar/Wind Helper
0.44
23562501BACKB
Solar/Wind Helper
0.897
964991AG1-363 GEN
Solar/Wind Helper
3.654
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270399AC1-101 GEN
Solar/Wind Harmer
6.93
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
970281AG2-184 GEN
Solar/Wind Harmer
30.484
971313AH1-133 GEN
Solar/Wind Harmer
8.48
962211AG1-066 GEN
Solar/Wind Harmer
3.344
24734705WLF1G3
Adder
7.73
24734805WLF1G4
Adder
7.73
24734905WLF1G5
Adder
7.73
971061AG2-657 GEN
Solar/Wind Harmer
11.954
971985AH1-537 GEN
Solar/Wind Harmer
23.681
24735105WLF2G1
Adder
7.594
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971329AH1-144 GEN
Solar/Wind Harmer
7.28
971981AH1-535 GEN
Solar/Wind Harmer
12.094
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
963841AG1-237 GEN
Solar/Wind Harmer
12.582
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24386405FR-21G C
Solar/Wind Harmer
4.939
24387005FR-3G C
Solar/Wind Harmer
4.542
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
24691005MDL-2G C
Solar/Wind Harmer
4.223
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
970289AG2-191 GEN
Solar/Wind Harmer
2.148
276726Z2-087_GEN
Solar/Wind Harmer
8.934
959341AF2-225 GEN
Solar/Wind Harmer
16.948
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
25196508WSDLE4
Adder
9.478
274744AC1-111 GEN8
Adder
6.235
274746AC1-111 G10
Adder
6.235
274775LINCOLN ;6U
Adder
9.41
274776LINCOLN ;7U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
274728ELWOOD EC;5P
Adder
18.315
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
274735ELWOOD EC;4P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
238118U2-030_1
Solar/Wind Helper
0.286
241997AF1-093 GEN
Solar/Wind Helper
0.24
241985AE1-237 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20089226LOOKOUT
Solar/Wind Helper
0.573
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.376
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
966021AG1-471 GEN
Solar/Wind Harmer
6.353
339236AF1-050_GEN
Solar/Wind Harmer
2.134
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
962581AG1-107 GEN
Solar/Wind Harmer
5.847
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
966841AG1-555 GEN
Solar/Wind Harmer
2.883
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276916AD2-100_GEN
Solar/Wind Harmer
24.022
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697605MDL-3G C
Solar/Wind Harmer
4.21
24755605MDL-5G
Solar/Wind Harmer
2.754
24697905MDL-4G C
Solar/Wind Harmer
2.621
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
276838X2-022 GEN2
Solar/Wind Harmer
0.265
945421AF1-207 GEN
Solar/Wind Harmer
16.001
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
9.054
960611AF2-352 GEN
Solar/Wind Harmer
2.632
970879AG2-548 GEN
Solar/Wind Harmer
1.316
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
4.494
24699105WLD G1 C
Solar/Wind Harmer
4.441
942111AE2-223 GEN
Solar/Wind Harmer
9.262
25194408D.CRK1
Adder
8.477
25194508D.CRK3
Adder
1.585
274764LEE CO EC;5U
Adder
10.431
274765LEE CO EC;6U
Adder
10.431
274762LEE CO EC;3U
Adder
10.407
274763LEE CO EC;4U
Adder
10.309
972235AH1-702 GEN1
Adder
2.817
972236AH1-702 GEN2
Adder
2.45
274696ROCKY RD ;4P
Adder
12.719
274695ROCKY RD ;2P
Adder
12.425
274693ROCKY RD ;1P
Adder
12.303
274697ROCKY RD ;3P
Adder
3.375
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
274674JOLIET 9 ;6U
Adder
16.682
237043AE2-125 C
Solar/Wind Helper
0.176
23585401KL_K28_T16
Solar/Wind Helper
1.282
23751201ROTHROCK
Solar/Wind Helper
0.737
235054AD2-180 GEN
Solar/Wind Helper
1.698
238117U2-030
Solar/Wind Helper
0.286
962101AG1-054 GEN
Solar/Wind Helper
0.612
254304AE2-114 C
Solar/Wind Helper
0.205
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
241801AE1-079 GEN
Solar/Wind Helper
0.233
235531U2-073 GEN
Solar/Wind Helper
2.712
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
203961AE2-224 GEN
Solar/Wind Helper
2.277
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
203954AE2-126 C
Solar/Wind Helper
0.44
203804AE2-113_GEN
Solar/Wind Helper
1.631
940863AE2-074 GEN
Solar/Wind Helper
0.426
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
TVALTFEXP_TVA->PJM
CLTF
11.344
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
24.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
32.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.749
24318705GVG2
50/50
11.694
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
971191AH1-055 GEN
Solar/Wind Harmer
33.049
960911AF2-382 GEN
Solar/Wind Harmer
11.685
957541AF2-048 GEN
Solar/Wind Harmer
2.439
972103AH1-617 GEN
Solar/Wind Harmer
30.771
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
943031AE2-326 GEN
Solar/Wind Harmer
5.037
970879AG2-548 GEN
Solar/Wind Harmer
10.456
958121AF2-106 GEN
Solar/Wind Harmer
5.826
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
3429391JKCT 9G
Adder
9.999
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
270399AC1-101 GEN
Solar/Wind Harmer
7.458
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
970281AG2-184 GEN
Solar/Wind Harmer
32.31
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
971985AH1-537 GEN
Solar/Wind Harmer
26.806
962211AG1-066 GEN
Solar/Wind Harmer
3.513
24734705WLF1G3
Adder
8.136
24734805WLF1G4
Adder
8.136
24734905WLF1G5
Adder
8.136
24735105WLF2G1
Adder
7.967
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971329AH1-144 GEN
Solar/Wind Harmer
7.935
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972163AH1-664 GEN
Solar/Wind Harmer
12.156
972165AH1-665 GEN
Solar/Wind Harmer
9.725
3429211JKCT 2G
Adder
14.123
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
25196508WSDLE4
Adder
9.533
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
253406AD2-031_GEN
Solar/Wind Harmer
1.368
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
24386405FR-21G C
Solar/Wind Harmer
4.297
24387005FR-3G C
Solar/Wind Harmer
3.952
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274744AC1-111 GEN8
Adder
5.228
274746AC1-111 G10
Adder
5.228
274728ELWOOD EC;5P
Adder
15.317
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
274735ELWOOD EC;4P
Adder
15.317
274675JOLIET 29;7U
Adder
28.551
23750501ELLIOTTS
Solar/Wind Helper
0.647
23652301WDPWR_K20
Solar/Wind Helper
0.14
241997AF1-093 GEN
Solar/Wind Helper
0.247
241985AE1-237 GEN
Solar/Wind Helper
0.241
241982AE2-343 S C
Solar/Wind Helper
0.216
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089226LOOKOUT
Solar/Wind Helper
0.562
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.371
20094526CT_V3-030
Solar/Wind Helper
0.443
203846AF2-130 C
Solar/Wind Helper
0.428
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
970879AG2-548 GEN
Solar/Wind Harmer
1.52
270583AD2-179 GEN
Solar/Wind Harmer
12.855
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
972045AH1-571 GEN
Solar/Wind Harmer
2.414
971125AH1-004 GEN
Solar/Wind Harmer
4.793
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
971485AH1-239 GEN
Solar/Wind Harmer
9.429
252509AD1-136 GEN
Solar/Wind Harmer
0.301
339236AF1-050_GEN
Solar/Wind Harmer
2.122
964571AG1-320 GEN
Solar/Wind Harmer
9.57
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25183208HLCRTG
Solar/Wind Harmer
6.902
25194408D.CRK1
Adder
8.538
25194508D.CRK3
Adder
1.596
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728805RICHG1
Adder
3.92
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
276916AD2-100_GEN
Solar/Wind Harmer
21.377
276911AD2-131_GEN
Solar/Wind Harmer
4.32
970241AG2-163 GEN
Solar/Wind Harmer
25.444
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
276838X2-022 GEN2
Solar/Wind Harmer
0.234
24725505WLD G2 C
Solar/Wind Harmer
3.981
24699105WLD G1 C
Solar/Wind Harmer
3.935
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
270383AD1-128 GEN
Solar/Wind Harmer
6.1
24387305FR-4G C
Solar/Wind Harmer
5.075
966841AG1-555 GEN
Solar/Wind Harmer
2.508
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
274764LEE CO EC;5U
Adder
8.891
274765LEE CO EC;6U
Adder
8.891
274762LEE CO EC;3U
Adder
8.871
274763LEE CO EC;4U
Adder
8.787
972235AH1-702 GEN1
Adder
2.391
972236AH1-702 GEN2
Adder
2.08
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274696ROCKY RD ;4P
Adder
10.699
274695ROCKY RD ;2P
Adder
10.452
274693ROCKY RD ;1P
Adder
10.349
274697ROCKY RD ;3P
Adder
2.839
274674JOLIET 9 ;6U
Adder
14.342
237043AE2-125 C
Solar/Wind Helper
0.175
254304AE2-114 C
Solar/Wind Helper
0.213
254305AE2-115 C
Solar/Wind Helper
0.213
962101AG1-054 GEN
Solar/Wind Helper
0.63
241967AE2-285_GEN
Solar/Wind Helper
0.617
241801AE1-079 GEN
Solar/Wind Helper
0.241
23585401KL_K28_T16
Solar/Wind Helper
1.231
23751201ROTHROCK
Solar/Wind Helper
0.704
235054AD2-180 GEN
Solar/Wind Helper
1.627
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
235531U2-073 GEN
Solar/Wind Helper
2.597
203818AF1-086 GEN
Solar/Wind Helper
1.582
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203853AF1-134 C O1
Solar/Wind Helper
0.446
203946AE2-131 C
Solar/Wind Helper
0.441
203804AE2-113_GEN
Solar/Wind Helper
1.63
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
12.616
24318705GVG2
50/50
11.694
24721805FLATG3
50/50
2.66
960001AF2-291 GEN
Solar/Wind Harmer
6.049
24723205RIVRG3
Adder
36.981
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
24686505CER G6
Adder
16.193
972203AH1-686 GEN
Adder
4.427
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
24728305BUCHG2
Adder
6.959
971687AH1-348 GEN
Solar/Wind Harmer
1.517
24735205WLF2G2
Adder
7.967
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
945681AF1-233 GEN
Solar/Wind Harmer
22.855
3429241JKCT 3G
Adder
14.309
339221AD2-048_GEN
Solar/Wind Harmer
1.847
339211AE2-254 GEN
Solar/Wind Harmer
1.818
3429421JKCT 10G
Adder
9.999
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
970653AG2-424 GEN
Solar/Wind Harmer
5.656
964901AG1-354 GEN
Solar/Wind Harmer
17.533
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252516AE2-318_GEN
Solar/Wind Harmer
11.412
252510AF1-249 C
Solar/Wind Harmer
0.473
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
270222AC2-111 GEN
Solar/Wind Harmer
4.662
944031AF1-071 GEN
Solar/Wind Harmer
1.049
963741AG1-226 GEN
Solar/Wind Harmer
45.799
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
970149AG2-104 GEN
Solar/Wind Harmer
20.259
970155AG2-107 GEN
Solar/Wind Harmer
14.306
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270437AC2-090 C
Solar/Wind Harmer
5.627
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
276686W4-005 GEN3
Solar/Wind Harmer
3.022
24385905FR-11G C
Solar/Wind Harmer
8.303
24386605FR-22G C
Solar/Wind Harmer
4.297
276903AD2-071 C
Solar/Wind Harmer
9.98
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274761LEE CO EC;2U
Adder
8.871
274766LEE CO EC;7U
Adder
8.766
274822ROCKFORD ;11
Adder
18.607
25326309TAIT D
Adder
1.032
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274732ELWOOD EC;7P
Adder
15.317
274674JOLIET 9 ;6U
Adder
14.342
274676JOLIET 29;8U
Adder
10.069
254303AC2-168 GEN
Solar/Wind Helper
0.154
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
964201AG1-281 GEN
Solar/Wind Helper
0.452
238126S14_GEN_1
Solar/Wind Helper
0.645
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
25196008MFTGT1
Adder
1.543
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
25196608WSDLE5
Adder
9.632
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
24728505AND G1
Adder
4.021
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
24379505HDWTR1G C
Solar/Wind Harmer
7.972
270240V3-007_GEN2
Solar/Wind Harmer
6.237
276785W4-005 GEN1
Solar/Wind Harmer
3.022
971993AH1-541 GEN
Solar/Wind Harmer
9.233
24386205FR-12G C
Solar/Wind Harmer
4.281
247642Z2-115 C
Solar/Wind Harmer
0.063
965461AG1-414 GEN
Solar/Wind Harmer
2.238
970289AG2-191 GEN
Solar/Wind Harmer
0.757
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274760LEE CO EC;1U
Adder
8.871
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274729ELWOOD EC;1P
Adder
15.317
274730ELWOOD EC;6P
Adder
15.317
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
235058AG1-386 C
Solar/Wind Helper
0.455
237046AF1-021 C
Solar/Wind Helper
0.331
202652Y1-033 WT C
Solar/Wind Helper
0.537
23562501BACKB
Solar/Wind Helper
0.856
964991AG1-363 GEN
Solar/Wind Helper
3.486
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
TVALTFEXP_TVA->PJM
CLTF
11.244
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
WECLTFEXP_WEC->PJM
CLTF
3.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
32.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
270399AC1-101 GEN
Solar/Wind Harmer
7.511
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
970281AG2-184 GEN
Solar/Wind Harmer
32.57
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
971985AH1-537 GEN
Solar/Wind Harmer
27.028
962211AG1-066 GEN
Solar/Wind Harmer
3.543
24734705WLF1G3
Adder
8.207
24734805WLF1G4
Adder
8.207
24734905WLF1G5
Adder
8.207
24735105WLF2G1
Adder
8.038
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971329AH1-144 GEN
Solar/Wind Harmer
8.009
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972163AH1-664 GEN
Solar/Wind Harmer
12.28
972165AH1-665 GEN
Solar/Wind Harmer
9.824
3429211JKCT 2G
Adder
14.268
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
25196508WSDLE4
Adder
9.638
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
253406AD2-031_GEN
Solar/Wind Harmer
1.384
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
24386405FR-21G C
Solar/Wind Harmer
4.35
24387005FR-3G C
Solar/Wind Harmer
4.001
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274744AC1-111 GEN8
Adder
5.298
274746AC1-111 G10
Adder
5.298
274728ELWOOD EC;5P
Adder
15.521
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
274735ELWOOD EC;4P
Adder
15.521
274675JOLIET 29;7U
Adder
28.931
23750501ELLIOTTS
Solar/Wind Helper
0.639
23652301WDPWR_K20
Solar/Wind Helper
0.139
241997AF1-093 GEN
Solar/Wind Helper
0.244
241985AE1-237 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.214
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
20089126CSLMN_L13
Solar/Wind Helper
0.556
20089226LOOKOUT
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
203940AF1-140 C
Solar/Wind Helper
0.366
20094526CT_V3-030
Solar/Wind Helper
0.437
203846AF2-130 C
Solar/Wind Helper
0.422
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
24289405MTG1
50/50
11.803
243186AF1-051 GEN
50/50
12.678
24318705GVG2
50/50
11.752
24721805FLATG3
50/50
2.675
960001AF2-291 GEN
Solar/Wind Harmer
6.087
24723205RIVRG3
Adder
37.214
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
24686505CER G6
Adder
16.296
972203AH1-686 GEN
Adder
4.456
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
24728305BUCHG2
Adder
7.015
971687AH1-348 GEN
Solar/Wind Harmer
1.53
24735205WLF2G2
Adder
8.038
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
945681AF1-233 GEN
Solar/Wind Harmer
23.089
3429241JKCT 3G
Adder
14.456
339221AD2-048_GEN
Solar/Wind Harmer
1.866
339211AE2-254 GEN
Solar/Wind Harmer
1.837
3429421JKCT 10G
Adder
10.103
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
970653AG2-424 GEN
Solar/Wind Harmer
5.716
964901AG1-354 GEN
Solar/Wind Harmer
17.72
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252516AE2-318_GEN
Solar/Wind Harmer
11.536
252510AF1-249 C
Solar/Wind Harmer
0.479
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
270222AC2-111 GEN
Solar/Wind Harmer
4.717
944031AF1-071 GEN
Solar/Wind Harmer
1.061
963741AG1-226 GEN
Solar/Wind Harmer
46.357
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
970149AG2-104 GEN
Solar/Wind Harmer
20.507
970155AG2-107 GEN
Solar/Wind Harmer
14.481
942081AE2-220 GEN
Solar/Wind Harmer
6.527
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270437AC2-090 C
Solar/Wind Harmer
5.696
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
276686W4-005 GEN3
Solar/Wind Harmer
3.059
24385905FR-11G C
Solar/Wind Harmer
8.406
24386605FR-22G C
Solar/Wind Harmer
4.35
276903AD2-071 C
Solar/Wind Harmer
10.104
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274761LEE CO EC;2U
Adder
8.986
274766LEE CO EC;7U
Adder
8.88
274822ROCKFORD ;11
Adder
18.851
25326309TAIT D
Adder
1.046
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
274676JOLIET 29;8U
Adder
10.203
254303AC2-168 GEN
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
964201AG1-281 GEN
Solar/Wind Helper
0.445
238126S14_GEN_1
Solar/Wind Helper
0.636
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
24289405MTG1
50/50
11.803
24318705GVG2
50/50
11.752
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
971191AH1-055 GEN
Solar/Wind Harmer
33.281
960911AF2-382 GEN
Solar/Wind Harmer
11.778
957541AF2-048 GEN
Solar/Wind Harmer
2.459
972103AH1-617 GEN
Solar/Wind Harmer
31.019
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
943031AE2-326 GEN
Solar/Wind Harmer
5.082
970879AG2-548 GEN
Solar/Wind Harmer
10.556
958121AF2-106 GEN
Solar/Wind Harmer
5.883
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
3429391JKCT 9G
Adder
10.103
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
25196008MFTGT1
Adder
1.56
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
25196608WSDLE5
Adder
9.738
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
24728505AND G1
Adder
4.069
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
24379505HDWTR1G C
Solar/Wind Harmer
8.07
270240V3-007_GEN2
Solar/Wind Harmer
6.314
276785W4-005 GEN1
Solar/Wind Harmer
3.059
971993AH1-541 GEN
Solar/Wind Harmer
9.348
24386205FR-12G C
Solar/Wind Harmer
4.335
247642Z2-115 C
Solar/Wind Harmer
0.064
965461AG1-414 GEN
Solar/Wind Harmer
2.266
970289AG2-191 GEN
Solar/Wind Harmer
0.767
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274760LEE CO EC;1U
Adder
8.986
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274729ELWOOD EC;1P
Adder
15.521
274730ELWOOD EC;6P
Adder
15.521
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
235058AG1-386 C
Solar/Wind Helper
0.45
237046AF1-021 C
Solar/Wind Helper
0.327
202652Y1-033 WT C
Solar/Wind Helper
0.53
23562501BACKB
Solar/Wind Helper
0.844
964991AG1-363 GEN
Solar/Wind Helper
3.438
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
20303426NA_O38_P22
Solar/Wind Helper
0.913
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
970879AG2-548 GEN
Solar/Wind Harmer
1.534
270583AD2-179 GEN
Solar/Wind Harmer
12.98
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
972045AH1-571 GEN
Solar/Wind Harmer
2.439
971125AH1-004 GEN
Solar/Wind Harmer
4.843
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
971485AH1-239 GEN
Solar/Wind Harmer
9.528
252509AD1-136 GEN
Solar/Wind Harmer
0.304
339236AF1-050_GEN
Solar/Wind Harmer
2.145
964571AG1-320 GEN
Solar/Wind Harmer
9.672
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25183208HLCRTG
Solar/Wind Harmer
6.977
25194408D.CRK1
Adder
8.632
25194508D.CRK3
Adder
1.614
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728805RICHG1
Adder
3.967
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
276916AD2-100_GEN
Solar/Wind Harmer
21.637
276911AD2-131_GEN
Solar/Wind Harmer
4.373
970241AG2-163 GEN
Solar/Wind Harmer
25.754
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
276838X2-022 GEN2
Solar/Wind Harmer
0.237
24725505WLD G2 C
Solar/Wind Harmer
4.03
24699105WLD G1 C
Solar/Wind Harmer
3.983
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
270383AD1-128 GEN
Solar/Wind Harmer
6.175
24387305FR-4G C
Solar/Wind Harmer
5.138
966841AG1-555 GEN
Solar/Wind Harmer
2.539
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
274764LEE CO EC;5U
Adder
9.007
274765LEE CO EC;6U
Adder
9.007
274762LEE CO EC;3U
Adder
8.986
274763LEE CO EC;4U
Adder
8.901
972235AH1-702 GEN1
Adder
2.423
972236AH1-702 GEN2
Adder
2.107
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274696ROCKY RD ;4P
Adder
10.84
274695ROCKY RD ;2P
Adder
10.59
274693ROCKY RD ;1P
Adder
10.485
274697ROCKY RD ;3P
Adder
2.877
274674JOLIET 9 ;6U
Adder
14.533
237043AE2-125 C
Solar/Wind Helper
0.172
254304AE2-114 C
Solar/Wind Helper
0.21
254305AE2-115 C
Solar/Wind Helper
0.21
962101AG1-054 GEN
Solar/Wind Helper
0.622
241967AE2-285_GEN
Solar/Wind Helper
0.609
241801AE1-079 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.215
23751201ROTHROCK
Solar/Wind Helper
0.695
235054AD2-180 GEN
Solar/Wind Helper
1.606
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
235531U2-073 GEN
Solar/Wind Helper
2.561
203818AF1-086 GEN
Solar/Wind Helper
1.56
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
11.37
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1445_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1445_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.55 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1647.65
MW Contribution:
13.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
9.786
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.735
972167AH1-666 GEN
Solar/Wind Harmer
35.72
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.087
970093AG2-073 GEN
Solar/Wind Harmer
12.282
972273AH1-721 GEN
Adder
104.619
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.9
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.472
339255AE2-071 GEN
Solar/Wind Harmer
0.94
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.419
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.196
253325AC1-069 GEN
Solar/Wind Helper
0.827
252507AC2-088 GEN
Solar/Wind Helper
0.993
270518AE2-148 GEN
Solar/Wind Helper
6.125
3429661SPURLK4G
50/50
9.786
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.584
943111AE2-339 GEN
Solar/Wind Harmer
2.559
3429421JKCT 10G
Adder
24.087
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.179
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.64
964901AG1-354 GEN
Solar/Wind Harmer
13.573
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.196
253333AC1-068 GEN
Solar/Wind Helper
0.827
972163AH1-664 GEN
Solar/Wind Harmer
43.025
972165AH1-665 GEN
Solar/Wind Harmer
34.42
339216AC1-074 GEN
Solar/Wind Harmer
4.856
3429211JKCT 2G
Adder
31.762
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.04
253338AC1-165 GEN
Solar/Wind Helper
0.798
253343AC1-166 GEN
Solar/Wind Helper
0.798
253406AD2-031_GEN
Solar/Wind Helper
0.685
945631AF1-228 GEN
Solar/Wind Helper
0.92
241972AD1-140 GEN
Solar/Wind Helper
1.755
3429601SPURLK2G
50/50
18.648
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.529
970107AG2-081 GEN
Solar/Wind Harmer
8.647
972043AH1-570 GEN
Solar/Wind Harmer
7.199
972045AH1-571 GEN
Solar/Wind Harmer
5.759
942891AE2-308 GEN
Solar/Wind Harmer
25.15
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.676
966021AG1-471 GEN
Solar/Wind Harmer
4.849
971485AH1-239 GEN
Solar/Wind Harmer
7.098
964571AG1-320 GEN
Solar/Wind Harmer
7.24
964781AG1-341 GEN
Solar/Wind Harmer
8.124
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.43
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.408
950051AG9-018
External Queue
23.236736297607422
950041AG9-017
External Queue
23.31861114501953
950011AG9-010
External Queue
6.1081342697143555
LAGNLTFEXP_LAGN->PJM
CLTF
6.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.899
TVALTFEXP_TVA->PJM
CLTF
3.738
CPLELTFEXP_CPLE->PJM
CLTF
1.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.881
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.374
MECLTFEXP_MEC->PJM
CLTF
2.567
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
0.555
LGEELTFEXP_LGEE->PJM
CLTF
4.938
WECLTFEXP_WEC->PJM
CLTF
0.326

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1449_ZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1449_ZIMMER_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1645.79
MW Contribution:
13.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
9.787
3429661SPURLK4G
50/50
9.787
25197008MELDL1
50/50
1.25
3429571SPURLK1G
50/50
9.78
945681AF1-233 GEN
Solar/Wind Harmer
83.589
943111AE2-339 GEN
Solar/Wind Harmer
2.559
972163AH1-664 GEN
Solar/Wind Harmer
43.027
972165AH1-665 GEN
Solar/Wind Harmer
34.422
339216AC1-074 GEN
Solar/Wind Harmer
4.855
3429211JKCT 2G
Adder
31.761
962211AG1-066 GEN
Solar/Wind Harmer
2.194
970281AG2-184 GEN
Solar/Wind Harmer
13.039
253338AC1-165 GEN
Solar/Wind Helper
0.797
253343AC1-166 GEN
Solar/Wind Helper
0.797
253406AD2-031_GEN
Solar/Wind Helper
0.683
945631AF1-228 GEN
Solar/Wind Helper
0.919
25197208MELDL3
50/50
1.258
958171AF2-111 GEN
Solar/Wind Harmer
128.745
972167AH1-666 GEN
Solar/Wind Harmer
35.722
339243AC2-075 GEN1
Solar/Wind Harmer
1.315
3429391JKCT 9G
Adder
24.086
970093AG2-073 GEN
Solar/Wind Harmer
12.281
972273AH1-721 GEN
Adder
104.598
339206AE1-143 GEN
Solar/Wind Harmer
2.513
970455AG2-298 GEN
Solar/Wind Harmer
3.899
970653AG2-424 GEN
Solar/Wind Harmer
0.671
270186AC1-089 GEN
Solar/Wind Harmer
5.475
339255AE2-071 GEN
Solar/Wind Harmer
0.939
339250AF1-203 GEN
Solar/Wind Harmer
0.484
972103AH1-617 GEN
Solar/Wind Harmer
12.418
971461AH1-227 GEN
Solar/Wind Harmer
2.266
253394AE2-221_GEN
Solar/Wind Helper
2.194
253325AC1-069 GEN
Solar/Wind Helper
0.826
252507AC2-088 GEN
Solar/Wind Helper
0.996
270518AE2-148 GEN
Solar/Wind Helper
6.113
3429601SPURLK2G
50/50
18.65
25197108MELDL2
50/50
1.268
971125AH1-004 GEN
Solar/Wind Harmer
11.528
970107AG2-081 GEN
Solar/Wind Harmer
8.646
972043AH1-570 GEN
Solar/Wind Harmer
7.198
972045AH1-571 GEN
Solar/Wind Harmer
5.758
942891AE2-308 GEN
Solar/Wind Harmer
25.149
339231AF1-038_GEN
Solar/Wind Harmer
1.929
339236AF1-050_GEN
Solar/Wind Harmer
1.675
966021AG1-471 GEN
Solar/Wind Harmer
4.847
971485AH1-239 GEN
Solar/Wind Harmer
7.096
964571AG1-320 GEN
Solar/Wind Harmer
7.237
964781AG1-341 GEN
Solar/Wind Harmer
8.121
971225AH1-072 GEN
Solar/Wind Harmer
0.883
971227AH1-073 GEN
Solar/Wind Harmer
0.883
25183208HLCRTG
Solar/Wind Helper
2.425
252509AD1-136 GEN
Solar/Wind Helper
0.142
253415AE1-040 GEN
Solar/Wind Helper
0.407
3429421JKCT 10G
Adder
24.086
339221AD2-048_GEN
Solar/Wind Harmer
4.286
3429241JKCT 3G
Adder
32.178
339211AE2-254 GEN
Solar/Wind Harmer
2.559
339241AF1-083 GEN
Solar/Wind Harmer
1.767
970653AG2-424 GEN
Solar/Wind Harmer
4.638
964901AG1-354 GEN
Solar/Wind Harmer
13.568
971687AH1-348 GEN
Solar/Wind Harmer
0.458
253398AE2-221_GEN2
Solar/Wind Helper
2.194
253333AC1-068 GEN
Solar/Wind Helper
0.826
950051AG9-018
External Queue
23.243040084838867
950041AG9-017
External Queue
23.32491683959961
950011AG9-010
External Queue
6.111148357391357
LAGNLTFEXP_LAGN->PJM
CLTF
6.095
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.896
TVALTFEXP_TVA->PJM
CLTF
3.736
CPLELTFEXP_CPLE->PJM
CLTF
1.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.719
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.856
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.363
MECLTFEXP_MEC->PJM
CLTF
2.563
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
0.554
LGEELTFEXP_LGEE->PJM
CLTF
4.934
WECLTFEXP_WEC->PJM
CLTF
0.326

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.98 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1638.99
MW Contribution:
9.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.061
25197208MELDL3
50/50
0.562
958171AF2-111 GEN
Solar/Wind Harmer
93.601
972167AH1-666 GEN
Solar/Wind Harmer
26.206
339243AC2-075 GEN1
Solar/Wind Harmer
1.039
3429391JKCT 9G
Adder
18.489
970093AG2-073 GEN
Solar/Wind Harmer
9.666
972273AH1-721 GEN
Adder
88.699
339206AE1-143 GEN
Solar/Wind Harmer
2.228
970455AG2-298 GEN
Solar/Wind Harmer
3.621
970653AG2-424 GEN
Solar/Wind Harmer
0.639
25196008MFTGT1
Adder
1.024
339255AE2-071 GEN
Solar/Wind Harmer
0.892
339250AF1-203 GEN
Solar/Wind Harmer
0.459
270186AC1-089 GEN
Solar/Wind Harmer
4.247
252524AE2-267 GEN
Solar/Wind Harmer
1.09
25196608WSDLE5
Adder
5.933
25194608D.CRK4
Adder
1.116
972103AH1-617 GEN
Solar/Wind Harmer
9.479
253394AE2-221_GEN
Solar/Wind Helper
3.664
253325AC1-069 GEN
Solar/Wind Helper
1.339
270518AE2-148 GEN
Solar/Wind Helper
9.686
252507AC2-088 GEN
Solar/Wind Helper
0.978
960071AF2-298 GEN
Solar/Wind Helper
0.314
960801AF2-371 GEN
Solar/Wind Helper
0.52
964871AG1-351 GEN
Solar/Wind Helper
0.359
972163AH1-664 GEN
Solar/Wind Harmer
31.649
972165AH1-665 GEN
Solar/Wind Harmer
25.319
339216AC1-074 GEN
Solar/Wind Harmer
3.834
3429211JKCT 2G
Adder
24.533
25196108MFTGT2
Adder
1.166
25196108MFTGT2
Adder
1.082
962211AG1-066 GEN
Solar/Wind Harmer
1.711
25196408WSDLE3
Adder
6.108
25196308WSDLE2
Adder
6.055
25196208WSDLE1
Adder
6.04
25196708WSDLE6
Adder
6.025
25196508WSDLE4
Adder
5.873
970281AG2-184 GEN
Solar/Wind Harmer
9.952
253338AC1-165 GEN
Solar/Wind Helper
1.292
253343AC1-166 GEN
Solar/Wind Helper
1.292
253406AD2-031_GEN
Solar/Wind Helper
1.192
945631AF1-228 GEN
Solar/Wind Helper
1.431
241972AD1-140 GEN
Solar/Wind Helper
2.736
270340AC2-060 GEN
Solar/Wind Helper
1.34
241955AC1-078 GEN
Solar/Wind Helper
1.212
3429601SPURLK2G
50/50
13.454
25197108MELDL2
50/50
0.567
972043AH1-570 GEN
Solar/Wind Harmer
5.598
241973AD2-163_GEN1
Solar/Wind Helper
0.942
241974AD2-163_GEN2
Solar/Wind Helper
0.942
270263AC1-001 GEN
Solar/Wind Helper
0.509
972045AH1-571 GEN
Solar/Wind Harmer
4.479
971125AH1-004 GEN
Solar/Wind Harmer
8.94
970107AG2-081 GEN
Solar/Wind Harmer
6.705
942891AE2-308 GEN
Solar/Wind Harmer
19.644
339231AF1-038_GEN
Solar/Wind Harmer
1.696
964571AG1-320 GEN
Solar/Wind Harmer
7.187
339236AF1-050_GEN
Solar/Wind Harmer
1.554
966021AG1-471 GEN
Solar/Wind Harmer
4.35
971485AH1-239 GEN
Solar/Wind Harmer
6.405
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25194408D.CRK1
Adder
5.134
25194508D.CRK3
Adder
0.96
25183208HLCRTG
Solar/Wind Helper
5.698
253415AE1-040 GEN
Solar/Wind Helper
0.679
252509AD1-136 GEN
Solar/Wind Helper
0.14
946101AF1-275 GEN
Solar/Wind Helper
0.373
253383AE2-342_GEN
Solar/Wind Helper
0.369
3429661SPURLK4G
50/50
7.061
3429571SPURLK1G
50/50
7.129
25197008MELDL1
50/50
0.559
945681AF1-233 GEN
Solar/Wind Harmer
61.342
943111AE2-339 GEN
Solar/Wind Harmer
1.979
3429421JKCT 10G
Adder
18.489
339221AD2-048_GEN
Solar/Wind Harmer
3.377
25196808ZIMRHP
Adder
160.518
3429241JKCT 3G
Adder
24.855
339211AE2-254 GEN
Solar/Wind Harmer
2.125
339241AF1-083 GEN
Solar/Wind Harmer
1.597
970653AG2-424 GEN
Solar/Wind Harmer
4.417
964901AG1-354 GEN
Solar/Wind Harmer
12.634
25196008MFTGT1
Adder
1.057
25194608D.CRK4
Adder
1.116
252510AF1-249 C
Solar/Wind Harmer
0.264
253398AE2-221_GEN2
Solar/Wind Helper
3.664
253333AC1-068 GEN
Solar/Wind Helper
1.339
270520AE2-214 GEN
Solar/Wind Helper
1.493
270273AD2-016 GEN
Solar/Wind Helper
1.381
950051AG9-018
External Queue
14.513641357421875
950041AG9-017
External Queue
14.800519943237305
LAGNLTFEXP_LAGN->PJM
CLTF
6.902
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.204
TVALTFEXP_TVA->PJM
CLTF
3.913
CPLELTFEXP_CPLE->PJM
CLTF
0.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.666
MECLTFEXP_MEC->PJM
CLTF
4.442
SIGELTFEXP_SIGE->PJM
CLTF
0.296
NYPJM->LTFIMP_NY
CLTF
0.774
LGEELTFEXP_LGEE->PJM
CLTF
5.705
WECLTFEXP_WEC->PJM
CLTF
0.798

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1373_PORTUNION_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1373_PORTUNION_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.14 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1626.02
MW Contribution:
10.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
7.899
25197208MELDL3
50/50
0.684
958171AF2-111 GEN
Solar/Wind Harmer
104.309
972167AH1-666 GEN
Solar/Wind Harmer
29.068
339243AC2-075 GEN1
Solar/Wind Harmer
1.115
3429391JKCT 9G
Adder
20.063
970093AG2-073 GEN
Solar/Wind Harmer
10.362
972273AH1-721 GEN
Adder
91.729
339206AE1-143 GEN
Solar/Wind Harmer
2.259
970455AG2-298 GEN
Solar/Wind Harmer
3.596
970653AG2-424 GEN
Solar/Wind Harmer
0.627
339255AE2-071 GEN
Solar/Wind Harmer
0.876
339250AF1-203 GEN
Solar/Wind Harmer
0.451
270186AC1-089 GEN
Solar/Wind Harmer
4.264
972103AH1-617 GEN
Solar/Wind Harmer
10.18
25196008MFTGT1
Adder
0.64
253394AE2-221_GEN
Solar/Wind Helper
2.845
253325AC1-069 GEN
Solar/Wind Helper
1.06
270518AE2-148 GEN
Solar/Wind Helper
7.005
252507AC2-088 GEN
Solar/Wind Helper
0.736
3429601SPURLK2G
50/50
15.051
25197108MELDL2
50/50
0.689
972043AH1-570 GEN
Solar/Wind Harmer
6.04
972045AH1-571 GEN
Solar/Wind Harmer
4.832
971125AH1-004 GEN
Solar/Wind Harmer
9.66
970107AG2-081 GEN
Solar/Wind Harmer
7.245
942891AE2-308 GEN
Solar/Wind Harmer
21.138
339231AF1-038_GEN
Solar/Wind Harmer
1.725
339236AF1-050_GEN
Solar/Wind Harmer
1.543
964571AG1-320 GEN
Solar/Wind Harmer
6.934
966021AG1-471 GEN
Solar/Wind Harmer
4.381
971485AH1-239 GEN
Solar/Wind Harmer
6.435
964781AG1-341 GEN
Solar/Wind Harmer
7.632
25183208HLCRTG
Solar/Wind Helper
2.949
253415AE1-040 GEN
Solar/Wind Helper
0.531
946101AF1-275 GEN
Solar/Wind Helper
0.294
252509AD1-136 GEN
Solar/Wind Helper
0.105
3429661SPURLK4G
50/50
7.899
3429571SPURLK1G
50/50
7.935
25197008MELDL1
50/50
0.68
25196808ZIMRHP
50/50
216.614
945681AF1-233 GEN
Solar/Wind Harmer
68.028
943111AE2-339 GEN
Solar/Wind Harmer
2.141
3429421JKCT 10G
Adder
20.063
339221AD2-048_GEN
Solar/Wind Harmer
3.624
3429241JKCT 3G
Adder
26.889
339211AE2-254 GEN
Solar/Wind Harmer
2.221
339241AF1-083 GEN
Solar/Wind Harmer
1.605
970653AG2-424 GEN
Solar/Wind Harmer
4.338
964901AG1-354 GEN
Solar/Wind Harmer
12.527
25196008MFTGT1
Adder
0.661
253398AE2-221_GEN2
Solar/Wind Helper
2.845
253333AC1-068 GEN
Solar/Wind Helper
1.06
270520AE2-214 GEN
Solar/Wind Helper
1.175
972163AH1-664 GEN
Solar/Wind Harmer
35.056
972165AH1-665 GEN
Solar/Wind Harmer
28.045
339216AC1-074 GEN
Solar/Wind Harmer
4.116
3429211JKCT 2G
Adder
26.54
962211AG1-066 GEN
Solar/Wind Harmer
1.83
970281AG2-184 GEN
Solar/Wind Harmer
10.689
25196108MFTGT2
Adder
0.729
25196108MFTGT2
Adder
0.677
253338AC1-165 GEN
Solar/Wind Helper
1.023
253343AC1-166 GEN
Solar/Wind Helper
1.023
253406AD2-031_GEN
Solar/Wind Helper
0.903
945631AF1-228 GEN
Solar/Wind Helper
1.078
270340AC2-060 GEN
Solar/Wind Helper
1.06
241972AD1-140 GEN
Solar/Wind Helper
1.838
241955AC1-078 GEN
Solar/Wind Helper
0.93
950051AG9-018
External Queue
17.4936466217041
950041AG9-017
External Queue
17.633872985839844
LAGNLTFEXP_LAGN->PJM
CLTF
6.318
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.215
TVALTFEXP_TVA->PJM
CLTF
3.686
CPLELTFEXP_CPLE->PJM
CLTF
0.943
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.569
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.436
MECLTFEXP_MEC->PJM
CLTF
3.587
SIGELTFEXP_SIGE->PJM
CLTF
0.255
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
5.166
WECLTFEXP_WEC->PJM
CLTF
0.598

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1493_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1493_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1610.06
MW Contribution:
10.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.911
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.706
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.879
270518AE2-148 GEN
Solar/Wind Helper
5.932
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.126
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.792
945681AF1-233 GEN
Solar/Wind Harmer
69.595
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
950051AG9-018
External Queue
18.441604614257812
950041AG9-017
External Queue
18.613412857055664
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.691
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.574
MECLTFEXP_MEC->PJM
CLTF
3.122
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P4_1487_RED BANK_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1487_RED BANK_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1609.33
MW Contribution:
10.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.91
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.159
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.878
270518AE2-148 GEN
Solar/Wind Helper
5.933
3429601SPURLK2G
50/50
15.451
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.323
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.881
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.69
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.318
964781AG1-341 GEN
Solar/Wind Harmer
7.405
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.774
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.222
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.218
964901AG1-354 GEN
Solar/Wind Harmer
12.23
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
972163AH1-664 GEN
Solar/Wind Harmer
35.849
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.846
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
950051AG9-018
External Queue
18.441471099853516
950041AG9-017
External Queue
18.61345100402832
LAGNLTFEXP_LAGN->PJM
CLTF
5.925
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.509
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.689
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.573
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.842
WECLTFEXP_WEC->PJM
CLTF
0.494

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1608.02
MW Contribution:
10.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
35.852
972165AH1-665 GEN
Solar/Wind Harmer
28.681
339216AC1-074 GEN
Solar/Wind Harmer
4.135
3429211JKCT 2G
Adder
26.873
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.819
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.944
3429601SPURLK2G
50/50
15.452
25197108MELDL2
50/50
0.736
3429661SPURLK4G
50/50
8.109
3429571SPURLK1G
50/50
8.128
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.827
945681AF1-233 GEN
Solar/Wind Harmer
69.6
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.341
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.226
339211AE2-254 GEN
Solar/Wind Harmer
2.217
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.22
964901AG1-354 GEN
Solar/Wind Harmer
12.233
253398AE2-221_GEN2
Solar/Wind Helper
2.61
253333AC1-068 GEN
Solar/Wind Helper
0.979
3429631SPURLK3G
50/50
8.109
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.917
972167AH1-666 GEN
Solar/Wind Harmer
29.741
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.341
970093AG2-073 GEN
Solar/Wind Harmer
10.453
972273AH1-721 GEN
Adder
91.178
339206AE1-143 GEN
Solar/Wind Harmer
2.227
970455AG2-298 GEN
Solar/Wind Harmer
3.515
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.853
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.304
253394AE2-221_GEN
Solar/Wind Helper
2.61
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.886
270518AE2-148 GEN
Solar/Wind Helper
5.931
971125AH1-004 GEN
Solar/Wind Harmer
9.766
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.103
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.354
339231AF1-038_GEN
Solar/Wind Harmer
1.703
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.692
966021AG1-471 GEN
Solar/Wind Harmer
4.308
971485AH1-239 GEN
Solar/Wind Harmer
6.32
964781AG1-341 GEN
Solar/Wind Harmer
7.407
25183208HLCRTG
Solar/Wind Helper
2.519
252509AD1-136 GEN
Solar/Wind Helper
0.127
253415AE1-040 GEN
Solar/Wind Helper
0.462
950051AG9-018
External Queue
18.440826416015625
950041AG9-017
External Queue
18.613161087036133
LAGNLTFEXP_LAGN->PJM
CLTF
5.927
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.129
TVALTFEXP_TVA->PJM
CLTF
3.51
CPLELTFEXP_CPLE->PJM
CLTF
0.937
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.712
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.579
MECLTFEXP_MEC->PJM
CLTF
3.124
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.844
WECLTFEXP_WEC->PJM
CLTF
0.494

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.95 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1607.79
MW Contribution:
10.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
8.108
3429571SPURLK1G
50/50
8.127
25197008MELDL1
50/50
0.726
25196808ZIMRHP
50/50
235.731
945681AF1-233 GEN
Solar/Wind Harmer
69.594
943111AE2-339 GEN
Solar/Wind Harmer
2.166
3429421JKCT 10G
Adder
20.338
339221AD2-048_GEN
Solar/Wind Harmer
3.648
3429241JKCT 3G
Adder
27.223
339211AE2-254 GEN
Solar/Wind Harmer
2.216
339241AF1-083 GEN
Solar/Wind Harmer
1.576
970653AG2-424 GEN
Solar/Wind Harmer
4.219
964901AG1-354 GEN
Solar/Wind Harmer
12.231
253398AE2-221_GEN2
Solar/Wind Helper
2.611
253333AC1-068 GEN
Solar/Wind Helper
0.979
3429631SPURLK3G
50/50
8.108
25197208MELDL3
50/50
0.73
958171AF2-111 GEN
Solar/Wind Harmer
106.907
972167AH1-666 GEN
Solar/Wind Harmer
29.739
339243AC2-075 GEN1
Solar/Wind Harmer
1.12
3429391JKCT 9G
Adder
20.338
970093AG2-073 GEN
Solar/Wind Harmer
10.451
972273AH1-721 GEN
Adder
91.166
339206AE1-143 GEN
Solar/Wind Harmer
2.226
970455AG2-298 GEN
Solar/Wind Harmer
3.514
970653AG2-424 GEN
Solar/Wind Harmer
0.61
270186AC1-089 GEN
Solar/Wind Harmer
4.707
339255AE2-071 GEN
Solar/Wind Harmer
0.852
339250AF1-203 GEN
Solar/Wind Harmer
0.439
972103AH1-617 GEN
Solar/Wind Harmer
10.305
253394AE2-221_GEN
Solar/Wind Helper
2.611
253325AC1-069 GEN
Solar/Wind Helper
0.979
252507AC2-088 GEN
Solar/Wind Helper
0.876
270518AE2-148 GEN
Solar/Wind Helper
5.934
972163AH1-664 GEN
Solar/Wind Harmer
35.848
972165AH1-665 GEN
Solar/Wind Harmer
28.679
339216AC1-074 GEN
Solar/Wind Harmer
4.134
3429211JKCT 2G
Adder
26.87
962211AG1-066 GEN
Solar/Wind Harmer
1.847
970281AG2-184 GEN
Solar/Wind Harmer
10.82
253338AC1-165 GEN
Solar/Wind Helper
0.945
253343AC1-166 GEN
Solar/Wind Helper
0.945
253406AD2-031_GEN
Solar/Wind Helper
0.782
945631AF1-228 GEN
Solar/Wind Helper
0.945
3429601SPURLK2G
50/50
15.45
25197108MELDL2
50/50
0.736
971125AH1-004 GEN
Solar/Wind Harmer
9.765
970107AG2-081 GEN
Solar/Wind Harmer
7.324
972043AH1-570 GEN
Solar/Wind Harmer
6.102
972045AH1-571 GEN
Solar/Wind Harmer
4.882
942891AE2-308 GEN
Solar/Wind Harmer
21.351
339231AF1-038_GEN
Solar/Wind Harmer
1.702
339236AF1-050_GEN
Solar/Wind Harmer
1.508
964571AG1-320 GEN
Solar/Wind Harmer
6.691
966021AG1-471 GEN
Solar/Wind Harmer
4.307
971485AH1-239 GEN
Solar/Wind Harmer
6.319
964781AG1-341 GEN
Solar/Wind Harmer
7.406
25183208HLCRTG
Solar/Wind Helper
2.518
252509AD1-136 GEN
Solar/Wind Helper
0.125
253415AE1-040 GEN
Solar/Wind Helper
0.462
950051AG9-018
External Queue
18.440135955810547
950041AG9-017
External Queue
18.612449645996094
LAGNLTFEXP_LAGN->PJM
CLTF
5.926
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.131
TVALTFEXP_TVA->PJM
CLTF
3.509
CPLELTFEXP_CPLE->PJM
CLTF
0.938
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.692
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.576
MECLTFEXP_MEC->PJM
CLTF
3.121
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.603
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
0.494

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.93 %
Rating:1240.0 MVA
Rating Type:A
MVA to Mitigate:1301.17
MW Contribution:
7.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
7.499
3429571SPURLK1G
50/50
7.535
25197008MELDL1
50/50
0.54
945681AF1-233 GEN
Solar/Wind Harmer
45.077
3429421JKCT 10G
Adder
19.05
3429241JKCT 3G
Adder
25.531
25196808ZIMRHP
Adder
146.641
970653AG2-424 GEN
Solar/Wind Harmer
2.876
964901AG1-354 GEN
Solar/Wind Harmer
8.3
25196008MFTGT1
Adder
0.625
253398AE2-221_GEN2
Solar/Wind Helper
2.816
253333AC1-068 GEN
Solar/Wind Helper
1.053
270520AE2-214 GEN
Solar/Wind Helper
1.117
972163AH1-664 GEN
Solar/Wind Harmer
25.864
972165AH1-665 GEN
Solar/Wind Harmer
20.714
339216AC1-074 GEN
Solar/Wind Harmer
0.434
3429211JKCT 2G
Adder
25.2
970281AG2-184 GEN
Solar/Wind Harmer
7.039
25196108MFTGT2
Adder
0.689
25196108MFTGT2
Adder
0.64
253338AC1-165 GEN
Solar/Wind Helper
1.016
253343AC1-166 GEN
Solar/Wind Helper
1.016
253406AD2-031_GEN
Solar/Wind Helper
0.85
945631AF1-228 GEN
Solar/Wind Helper
0.992
270340AC2-060 GEN
Solar/Wind Helper
0.994
3429631SPURLK3G
50/50
7.499
25197208MELDL3
50/50
0.543
958171AF2-111 GEN
Solar/Wind Harmer
69.096
972167AH1-666 GEN
Solar/Wind Harmer
19.261
3429391JKCT 9G
Adder
19.05
970093AG2-073 GEN
Solar/Wind Harmer
10.983
972273AH1-721 GEN
Adder
87.068
970455AG2-298 GEN
Solar/Wind Harmer
2.649
970653AG2-424 GEN
Solar/Wind Harmer
0.596
270186AC1-089 GEN
Solar/Wind Harmer
0
972103AH1-617 GEN
Solar/Wind Harmer
6.704
25196008MFTGT1
Adder
0.605
253394AE2-221_GEN
Solar/Wind Helper
2.816
253325AC1-069 GEN
Solar/Wind Helper
1.053
270518AE2-148 GEN
Solar/Wind Helper
6.196
252507AC2-088 GEN
Solar/Wind Helper
0.745
3429601SPURLK2G
50/50
14.29
25197108MELDL2
50/50
0.548
972043AH1-570 GEN
Solar/Wind Harmer
4.163
972045AH1-571 GEN
Solar/Wind Harmer
3.336
971125AH1-004 GEN
Solar/Wind Harmer
6.399
970107AG2-081 GEN
Solar/Wind Harmer
4.799
942891AE2-308 GEN
Solar/Wind Harmer
14.003
964571AG1-320 GEN
Solar/Wind Harmer
5.122
966021AG1-471 GEN
Solar/Wind Harmer
2.901
971485AH1-239 GEN
Solar/Wind Harmer
4.261
964781AG1-341 GEN
Solar/Wind Harmer
5.057
25183208HLCRTG
Solar/Wind Helper
2.669
253415AE1-040 GEN
Solar/Wind Helper
0.5
252509AD1-136 GEN
Solar/Wind Helper
0.106
946101AF1-275 GEN
Solar/Wind Helper
0.279
950051AG9-018
External Queue
16.602676391601562
950041AG9-017
External Queue
16.80695915222168
LAGNLTFEXP_LAGN->PJM
CLTF
5.986
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.932
TVALTFEXP_TVA->PJM
CLTF
3.49
CPLELTFEXP_CPLE->PJM
CLTF
0.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.28
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.592
MECLTFEXP_MEC->PJM
CLTF
3.424
SIGELTFEXP_SIGE->PJM
CLTF
0.243
NYPJM->LTFIMP_NY
CLTF
0.629
LGEELTFEXP_LGEE->PJM
CLTF
4.921
WECLTFEXP_WEC->PJM
CLTF
0.575

Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o EKPC_P2-2_MELD-SPUR 345_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DAY/EKPC
Facility Description:
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
Contingency Name:
EKPC_P2-2_MELD-SPUR 345_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:1532.0 MVA
Rating Type:B
MVA to Mitigate:1579.46
MW Contribution:
13.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3429661SPURLK4G
50/50
9.793
3429571SPURLK1G
50/50
9.787
945681AF1-233 GEN
Solar/Wind Harmer
83.653
943111AE2-339 GEN
Solar/Wind Harmer
2.562
3429421JKCT 10G
Adder
24.115
339221AD2-048_GEN
Solar/Wind Harmer
4.291
3429631SPURLK3G
50/50
9.793
958171AF2-111 GEN
Solar/Wind Harmer
128.831
972167AH1-666 GEN
Solar/Wind Harmer
35.75
339243AC2-075 GEN1
Solar/Wind Harmer
1.316
3429391JKCT 9G
Adder
24.115
970093AG2-073 GEN
Solar/Wind Harmer
12.299
972273AH1-721 GEN
Adder
104.883
339206AE1-143 GEN
Solar/Wind Harmer
2.52
970455AG2-298 GEN
Solar/Wind Harmer
3.911
970653AG2-424 GEN
Solar/Wind Harmer
0.673
270186AC1-089 GEN
Solar/Wind Harmer
5.496
339255AE2-071 GEN
Solar/Wind Harmer
0.943
339250AF1-203 GEN
Solar/Wind Harmer
0.486
972103AH1-617 GEN
Solar/Wind Harmer
12.486
971461AH1-227 GEN
Solar/Wind Harmer
2.283
253394AE2-221_GEN
Solar/Wind Helper
2.188
253325AC1-069 GEN
Solar/Wind Helper
0.822
252507AC2-088 GEN
Solar/Wind Helper
0.99
270518AE2-148 GEN
Solar/Wind Helper
6.07
972163AH1-664 GEN
Solar/Wind Harmer
43.062
972165AH1-665 GEN
Solar/Wind Harmer
34.449
339216AC1-074 GEN
Solar/Wind Harmer
4.861
3429211JKCT 2G
Adder
31.801
962211AG1-066 GEN
Solar/Wind Harmer
2.202
970281AG2-184 GEN
Solar/Wind Harmer
13.111
253338AC1-165 GEN
Solar/Wind Helper
0.794
253343AC1-166 GEN
Solar/Wind Helper
0.794
253406AD2-031_GEN
Solar/Wind Helper
0.679
945631AF1-228 GEN
Solar/Wind Helper
0.912
3429601SPURLK2G
50/50
18.661
971125AH1-004 GEN
Solar/Wind Harmer
11.542
970107AG2-081 GEN
Solar/Wind Harmer
8.656
972043AH1-570 GEN
Solar/Wind Harmer
7.207
972045AH1-571 GEN
Solar/Wind Harmer
5.765
942891AE2-308 GEN
Solar/Wind Harmer
25.183
339231AF1-038_GEN
Solar/Wind Harmer
1.935
339236AF1-050_GEN
Solar/Wind Harmer
1.681
966021AG1-471 GEN
Solar/Wind Harmer
4.866
971485AH1-239 GEN
Solar/Wind Harmer
7.124
964571AG1-320 GEN
Solar/Wind Harmer
7.265
964781AG1-341 GEN
Solar/Wind Harmer
8.157
971225AH1-072 GEN
Solar/Wind Harmer
0.89
971227AH1-073 GEN
Solar/Wind Harmer
0.89
25183208HLCRTG
Solar/Wind Helper
2.416
252509AD1-136 GEN
Solar/Wind Helper
0.141
3429241JKCT 3G
Adder
32.219
339211AE2-254 GEN
Solar/Wind Harmer
2.564
339241AF1-083 GEN
Solar/Wind Harmer
1.773
970653AG2-424 GEN
Solar/Wind Harmer
4.655
964901AG1-354 GEN
Solar/Wind Harmer
13.62
971687AH1-348 GEN
Solar/Wind Harmer
0.461
253398AE2-221_GEN2
Solar/Wind Helper
2.188
253333AC1-068 GEN
Solar/Wind Helper
0.822
950051AG9-018
External Queue
23.243040084838867
950041AG9-017
External Queue
23.32491683959961
950011AG9-010
External Queue
6.111148357391357
LAGNLTFEXP_LAGN->PJM
CLTF
6.165
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5
TVALTFEXP_TVA->PJM
CLTF
3.771
CPLELTFEXP_CPLE->PJM
CLTF
1.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.494
MECLTFEXP_MEC->PJM
CLTF
2.621
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.532
LGEELTFEXP_LGEE->PJM
CLTF
4.958
WECLTFEXP_WEC->PJM
CLTF
0.339
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'DEOK_P4_1445_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1449_ZIMMER_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 249577 CKT 1   /*08MELDAL     345.0 - 08ZIMER      345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'DEOK_P4_1373_PORTUNION_SRT-A'
 OPEN BRANCH FROM BUS 249570 TO BUS 249575 CKT 1   /*08P.UNON     345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1   /*08P.UNON     345.0 - 08ZIMER      345.0
END
CONTINGENCY 'DEOK_P4_1493_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1   /*08REDBK1     345.0 - 08REDBK1     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P4_1487_RED BANK_SRT-A'
 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1   /*08REDBK1     345.0 - 08REDBK2     138.0
 OPEN BUS 249573                                   /*08SGROVE     345.0
END
CONTINGENCY 'DEOK_P_CIRCUIT1883&4545REDBANKSILGRVZIMMER_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
 OPEN BUS 250079   /*08NWTWN1     138.0
END
CONTINGENCY 'DEOK_P2.2_SILVER GROVE 345 BUS_SRT-A'
 OPEN BUS 249573   /*08SGROVE     345.0
END
CONTINGENCY 'EKPC_P2-2_MELD-SPUR 345_SRT-A'
 OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1   /*08MELDAL     345.0 - 7SPURLOCK    345.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1
242516 to 242920 ckt 1
342838 to 253077 ckt 1

Winter Peak Analysis

The New Service Request AG2-184 was evaluated as a 210.0 MW (126.0 MW Capacity) injection in the AEP area.

AG2-184 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 210.0 MW (210.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC220.41 %1180.0B2600.84
1.06
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC218.08 %1180.0B2573.38
1.06
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC217.06 %1180.0B2561.3
1.06
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.66 %1180.0B2544.77
1.21
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC194.03 %1180.0B2289.58
1.08
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC189.53 %1180.0B2236.4
21.25
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC187.12 %1180.0B2207.97
21.29
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC186.11 %1180.0B2196.14
1.06
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC186.07 %1180.0B2195.62
21.3
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#5454_05MOSELEY 138_1_SRT-A
BusAC183.94 %1180.0B2170.52
1.05
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC180.71 %1180.0B2132.35
24.2
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC161.66 %1180.0B1907.61
21.65
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC159.66 %1180.0B1884.01
20.68
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC155.65 %1180.0B1836.67
20.7
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC155.28 %1180.0B1832.29
20.83
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC150.97 %1180.0A1781.48
20.73
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC114.05 %184.0A209.86
210.0
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
SingleAC114.05 %184.0B209.86
210.0

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2600.84
MW Contribution:
1.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.996
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.684
24728305BUCHG2
50/50
5.51
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.97
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.414
3142956BIRDNECK
Solar/Wind Helper
0.519
3143316POE
Solar/Wind Helper
1.304
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.36
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.189
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
3141726DUNNSVL
Solar/Wind Helper
1.412
24289905CRG1H
50/50
0.807
24290105CRG2H
50/50
0.813
24290005CRG1L
50/50
0.807
24290205CRG2L
50/50
0.807
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.114
316316AC1-027 C
Solar/Wind Helper
0.089
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.284
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.239
3141196NOKESVL
Solar/Wind Helper
1.295
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.88
3143526WINTERP
Solar/Wind Helper
1.88
316404AE1-155 C
Solar/Wind Helper
0.718
316033AB2-134 GEN
Solar/Wind Helper
0.757
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.734
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.52
315651AD1-115 GEN
Solar/Wind Helper
0.758
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.653
315662AE1-191 GEN
Solar/Wind Helper
0.451
315666AE1-190 GEN
Solar/Wind Helper
0.113
315697AD1-025 GEN
Solar/Wind Helper
0.797
316185AD1-033 GEN
Solar/Wind Helper
0.352
316280AD1-041 GEN
Solar/Wind Helper
0.282
316447AC1-158 HLD
Solar/Wind Helper
0.966
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.405
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.439
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.811
270346AE1-212 GEN
Solar/Wind Harmer
0.545
270030AE2-140 GEN
Solar/Wind Harmer
1.083
270069AE2-166 C O1
Solar/Wind Harmer
0.526
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
0.403
316375AC2-012 GEN
Solar/Wind Helper
0.596
316197AC1-042 GEN
Solar/Wind Helper
0.215
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.981
316169AC1-164_GENC
Solar/Wind Helper
0.847
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.036
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.048
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.281
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.468
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.062
970563AG2-360 GEN
50/50
33.666
970823AG2-518 GEN
50/50
5.456
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.457
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.45
971403AH1-188 GEN
Solar/Wind Harmer
0.722
971461AH1-227 GEN
Solar/Wind Harmer
0.281
971543AH1-269 GEN
50/50
8.214
971687AH1-348 GEN
Solar/Wind Harmer
0.054
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.192
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.959
971981AH1-535 GEN
Solar/Wind Harmer
0.503
972103AH1-617 GEN
Solar/Wind Harmer
1.012
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.044
971881AH1-461 GEN
50/50
10.558
315773AC2-141 GEN
Solar/Wind Helper
1.246
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.256
316294AC1-161 GEN
Solar/Wind Helper
1.246
316473AC1-191 GEN
Solar/Wind Helper
0.483
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.657
NYPJM->LTFIMP_NY
CLTF
2.067
LGEELTFEXP_LGEE->PJM
CLTF
4.281
WECLTFEXP_WEC->PJM
CLTF
2.133
CPLELTFEXP_CPLE->PJM
CLTF
1.528
TVALTFEXP_TVA->PJM
CLTF
6.811
MECLTFEXP_MEC->PJM
CLTF
9.763
LAGNLTFEXP_LAGN->PJM
CLTF
12.763
SIGELTFEXP_SIGE->PJM
CLTF
0.322
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.08 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2573.38
MW Contribution:
1.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.693
24728305BUCHG2
50/50
5.518
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.412
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.302
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.409
24289905CRG1H
50/50
0.808
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.808
24290205CRG2L
50/50
0.808
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.282
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.293
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.877
3143526WINTERP
Solar/Wind Helper
1.877
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.733
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.757
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.796
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.965
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.403
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.085
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.846
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.287
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.064
970563AG2-360 GEN
50/50
33.712
970823AG2-518 GEN
50/50
5.462
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.465
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.223
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.963
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.051
971881AH1-461 GEN
50/50
10.572
315773AC2-141 GEN
Solar/Wind Helper
1.244
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.244
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.833
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.705
NYPJM->LTFIMP_NY
CLTF
2.056
LGEELTFEXP_LGEE->PJM
CLTF
4.292
WECLTFEXP_WEC->PJM
CLTF
2.14
CPLELTFEXP_CPLE->PJM
CLTF
1.545
TVALTFEXP_TVA->PJM
CLTF
6.827
MECLTFEXP_MEC->PJM
CLTF
9.79
LAGNLTFEXP_LAGN->PJM
CLTF
12.796
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.06 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2561.3
MW Contribution:
1.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.696
24728305BUCHG2
50/50
5.522
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.14
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.411
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.301
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.351
3141913WHIT STONE
Solar/Wind Helper
0.349
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.408
24289905CRG1H
50/50
0.809
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.809
24290205CRG2L
50/50
0.809
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.281
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.292
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.876
3143526WINTERP
Solar/Wind Helper
1.876
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.732
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.149
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.756
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.795
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.964
316044AC1-158 PL1
Solar/Wind Helper
0.438
316045AC1-158 PL2
Solar/Wind Helper
1.402
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.112
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.086
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.845
316381AD1-082 GEN
Solar/Wind Helper
0.343
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.118
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.29
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.562
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.253
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.065
970563AG2-360 GEN
50/50
33.733
970823AG2-518 GEN
50/50
5.464
970913AG2-568 GEN
Solar/Wind Harmer
0.422
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.546
971331AH1-145 GEN
Solar/Wind Harmer
12.472
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.227
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.965
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.053
971881AH1-461 GEN
50/50
10.579
315773AC2-141 GEN
Solar/Wind Helper
1.243
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.243
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.726
NYPJM->LTFIMP_NY
CLTF
2.052
LGEELTFEXP_LGEE->PJM
CLTF
4.297
WECLTFEXP_WEC->PJM
CLTF
2.142
CPLELTFEXP_CPLE->PJM
CLTF
1.553
TVALTFEXP_TVA->PJM
CLTF
6.834
MECLTFEXP_MEC->PJM
CLTF
9.802
LAGNLTFEXP_LAGN->PJM
CLTF
12.81
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.77
MW Contribution:
1.21
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.018
24290605CLAY-1
50/50
0.171
24290605CLAY-1
50/50
0.171
24290705CLAY-2
50/50
0.171
24290705CLAY-2
50/50
0.171
24728205BUCHG1
50/50
6.231
24728305BUCHG2
50/50
6.04
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.13
3142416OLDCHRC
Solar/Wind Helper
0.878
3142416OLDCHRC
Solar/Wind Helper
0.336
3142433PROV 92
Solar/Wind Helper
1.276
316075AC2-137 C
Solar/Wind Helper
0.106
316077AC2-138 C
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.095
3138133OCRAN
Solar/Wind Helper
0.19
3141766HARMONY
Solar/Wind Helper
0.064
3141783LANCAST
Solar/Wind Helper
0.191
3141783LANCAST
Solar/Wind Helper
0.127
3141813NORNECK
Solar/Wind Helper
0.322
3141913WHIT STONE
Solar/Wind Helper
0.317
3143226MDLTHAN
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.191
3147123OTTER R
Solar/Wind Helper
0.187
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3147666LOUISA
Solar/Wind Helper
1.258
3147666LOUISA
Solar/Wind Helper
0.723
3141726DUNNSVL
Solar/Wind Helper
1.29
24289905CRG1H
50/50
0.888
24290105CRG2H
50/50
0.895
24290005CRG1L
50/50
0.888
24290205CRG2L
50/50
0.888
316059AD1-063 C
Solar/Wind Helper
0.077
316314AB2-024 C
Solar/Wind Helper
0.103
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.355
3141873WAN 176
Solar/Wind Helper
0.063
3143526WINTERP
Solar/Wind Helper
1.709
3143526WINTERP
Solar/Wind Helper
1.709
316404AE1-155 C
Solar/Wind Helper
0.655
3142543TWELFTH
Solar/Wind Helper
0.031
316203AE2-005 GEN
Solar/Wind Helper
0.662
316441AF1-014 GEN
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.136
315651AD1-115 GEN
Solar/Wind Helper
0.792
315662AE1-191 GEN
Solar/Wind Helper
0.407
315666AE1-190 GEN
Solar/Wind Helper
0.102
316280AD1-041 GEN
Solar/Wind Helper
0.254
316447AC1-158 HLD
Solar/Wind Helper
0.936
316044AC1-158 PL1
Solar/Wind Helper
0.425
316045AC1-158 PL2
Solar/Wind Helper
1.361
316450AC1-158 RIC
Solar/Wind Helper
0.113
316468AD1-105 GEN
Solar/Wind Helper
0.407
316156AD2-030 GEN
Solar/Wind Helper
0.1
316337AD2-073 GEN
Solar/Wind Helper
0.104
270399AC1-101 GEN
Solar/Wind Harmer
0.288
270583AD2-179 GEN
Solar/Wind Harmer
0.823
270494AE1-108_GEN
Solar/Wind Helper
0.847
270346AE1-212 GEN
Solar/Wind Harmer
0.589
270030AE2-140 GEN
Solar/Wind Harmer
1.139
270069AE2-166 C O1
Solar/Wind Harmer
0.548
270053AF1-130 C
Solar/Wind Harmer
1.012
316006AB2-029 C
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.442
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.105
315975AC1-164 GENB
Solar/Wind Helper
0.026
315976AC1-164 GENA
Solar/Wind Helper
0.883
316169AC1-164_GENC
Solar/Wind Helper
0.763
316233AE1-074 FULL
Solar/Wind Helper
0.106
3142946ENON
Solar/Wind Helper
0.032
3142946ENON
Solar/Wind Helper
0.107
943031AE2-326 GEN
Solar/Wind Harmer
5.484
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.53
944971AF1-162 GEN
Solar/Wind Harmer
6.858
961951AG1-038 GEN
Solar/Wind Helper
0.231
966871AG1-558 GEN
Solar/Wind Helper
0.11
966881AG1-559 GEN
Solar/Wind Helper
0.114
970281AG2-184 GEN
Solar/Wind Harmer
1.21
970563AG2-360 GEN
50/50
36.34
970823AG2-518 GEN
50/50
5.453
970913AG2-568 GEN
Solar/Wind Harmer
0.477
971061AG2-657 GEN
Solar/Wind Harmer
0.472
971225AH1-072 GEN
Solar/Wind Harmer
0.123
971227AH1-073 GEN
Solar/Wind Harmer
0.123
971277AH1-098 GEN
Solar/Wind Harmer
0.336
971313AH1-133 GEN
Solar/Wind Harmer
0.496
971329AH1-144 GEN
Solar/Wind Harmer
0.558
971331AH1-145 GEN
Solar/Wind Harmer
12.762
971403AH1-188 GEN
Solar/Wind Harmer
0.833
971461AH1-227 GEN
Solar/Wind Harmer
0.315
971543AH1-269 GEN
50/50
8.316
971687AH1-348 GEN
Solar/Wind Harmer
0.061
24415905BUCK
50/50
0.026
24416005BYLLESBY
50/50
0.049
957601AF2-054 GEN
Solar/Wind Helper
0.101
957971AF2-091 GEN
Solar/Wind Helper
0.18
964211AG1-282 GEN
Solar/Wind Helper
0.104
966391AG1-508 GEN
Solar/Wind Harmer
4.12
971981AH1-535 GEN
Solar/Wind Harmer
0.558
972103AH1-617 GEN
Solar/Wind Harmer
1.152
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.448
971881AH1-461 GEN
50/50
11.424
316164AC1-076 GEN
Solar/Wind Helper
0.342
316217AC1-145 GEN
Solar/Wind Helper
0.255
316473AC1-191 GEN
Solar/Wind Helper
0.44
270400AC1-102 GEN
Solar/Wind Harmer
0.288
316487AF1-042 GEN
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.442
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.119
NYPJM->LTFIMP_NY
CLTF
2.528
LGEELTFEXP_LGEE->PJM
CLTF
5.132
WECLTFEXP_WEC->PJM
CLTF
2.57
CPLELTFEXP_CPLE->PJM
CLTF
2.392
TVALTFEXP_TVA->PJM
CLTF
7.856
MECLTFEXP_MEC->PJM
CLTF
11.663
LAGNLTFEXP_LAGN->PJM
CLTF
14.865
SIGELTFEXP_SIGE->PJM
CLTF
0.385
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.446
AG2-052LTFEXP_AG2-052->PJM
LTF
0.155
AH1-155LTFEXP_AH1-155->PJM
LTF
0.233

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:194.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2289.58
MW Contribution:
1.08
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.014
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
24728205BUCHG1
50/50
5.791
24728305BUCHG2
50/50
5.614
3142416OLDCHRC
Solar/Wind Helper
0.842
3142416OLDCHRC
Solar/Wind Helper
0.323
316075AC2-137 C
Solar/Wind Helper
0.101
3143226MDLTHAN
Solar/Wind Helper
0.32
270205AE1-176
50/50
0.013
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
3148463FAIRFLD
Solar/Wind Harmer
-0.312
315616AA1-038_C
Solar/Wind Harmer
3.158
316312AB1-027
Solar/Wind Helper
0.13
316447AC1-158 HLD
Solar/Wind Helper
0.871
316044AC1-158 PL1
Solar/Wind Helper
0.396
316045AC1-158 PL2
Solar/Wind Helper
1.267
316450AC1-158 RIC
Solar/Wind Helper
0.106
316468AD1-105 GEN
Solar/Wind Helper
0.386
270399AC1-101 GEN
Solar/Wind Harmer
0.252
270583AD2-179 GEN
Solar/Wind Harmer
0.825
270494AE1-108_GEN
Solar/Wind Helper
0.869
270346AE1-212 GEN
Solar/Wind Harmer
0.553
270030AE2-140 GEN
Solar/Wind Harmer
1.13
270069AE2-166 C O1
Solar/Wind Harmer
0.546
24734705WLF1G3
50/50
7.099
24734805WLF1G4
50/50
7.099
24734905WLF1G5
50/50
7.099
24735105WLF2G1
50/50
6.939
24735205WLF2G2
50/50
6.939
315975AC1-164 GENB
Solar/Wind Helper
0.025
315976AC1-164 GENA
Solar/Wind Helper
0.849
316169AC1-164_GENC
Solar/Wind Helper
0.733
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.381
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.105
966881AG1-559 GEN
Solar/Wind Helper
0.108
970281AG2-184 GEN
Solar/Wind Harmer
1.082
970563AG2-360 GEN
50/50
34.318
970823AG2-518 GEN
50/50
5.548
970913AG2-568 GEN
Solar/Wind Harmer
0.426
971225AH1-072 GEN
Solar/Wind Harmer
0.112
971227AH1-073 GEN
Solar/Wind Harmer
0.112
971277AH1-098 GEN
Solar/Wind Harmer
0.33
971313AH1-133 GEN
Solar/Wind Harmer
0.466
971329AH1-144 GEN
Solar/Wind Harmer
0.554
971331AH1-145 GEN
Solar/Wind Harmer
12.663
971403AH1-188 GEN
Solar/Wind Harmer
0.734
971461AH1-227 GEN
Solar/Wind Harmer
0.287
971543AH1-269 GEN
50/50
8.359
971687AH1-348 GEN
Solar/Wind Harmer
0.056
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.048
966391AG1-508 GEN
Solar/Wind Harmer
4.035
971981AH1-535 GEN
Solar/Wind Harmer
0.518
972103AH1-617 GEN
Solar/Wind Harmer
1.031
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.128
971881AH1-461 GEN
50/50
10.749
316164AC1-076 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
0.421
270400AC1-102 GEN
Solar/Wind Harmer
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.24
NYPJM->LTFIMP_NY
CLTF
2.009
LGEELTFEXP_LGEE->PJM
CLTF
4.347
WECLTFEXP_WEC->PJM
CLTF
2.162
CPLELTFEXP_CPLE->PJM
CLTF
2.241
TVALTFEXP_TVA->PJM
CLTF
7.056
MECLTFEXP_MEC->PJM
CLTF
9.948
LAGNLTFEXP_LAGN->PJM
CLTF
13.244
SIGELTFEXP_SIGE->PJM
CLTF
0.327
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.194

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:189.53 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2236.4
MW Contribution:
21.25
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
21.248

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:187.12 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2207.97
MW Contribution:
21.29
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
21.287

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:186.11 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2196.14
MW Contribution:
1.06
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.028
24290605CLAY-1
50/50
0.177
24290605CLAY-1
50/50
0.177
24290705CLAY-2
50/50
0.177
24290705CLAY-2
50/50
0.177
24728205BUCHG1
50/50
5.7
24728305BUCHG2
50/50
5.525
3142416OLDCHRC
Solar/Wind Helper
0.823
3142416OLDCHRC
Solar/Wind Helper
0.315
3143226MDLTHAN
Solar/Wind Helper
0.311
3147123OTTER R
Solar/Wind Helper
0.275
3147312GRETNA
Solar/Wind Helper
0.094
3147312GRETNA
Solar/Wind Helper
0.378
24289905CRG1H
50/50
0.81
24290105CRG2H
50/50
0.816
24290005CRG1L
50/50
0.81
24290205CRG2L
50/50
0.81
270205AE1-176
50/50
0.016
3146802CHATHAM
Solar/Wind Helper
0.354
316312AB1-027
Solar/Wind Helper
0.127
316447AC1-158 HLD
Solar/Wind Helper
0.852
316044AC1-158 PL1
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
1.24
316450AC1-158 RIC
Solar/Wind Helper
0.103
316468AD1-105 GEN
Solar/Wind Helper
0.377
270173AC1-122 GEN
Solar/Wind Helper
0.533
270583AD2-179 GEN
Solar/Wind Harmer
0.851
270494AE1-108_GEN
Solar/Wind Helper
1.033
270346AE1-212 GEN
Solar/Wind Harmer
0.559
270030AE2-140 GEN
Solar/Wind Harmer
1.12
270069AE2-166 C O1
Solar/Wind Harmer
0.551
316197AC1-042 GEN
Solar/Wind Helper
0.319
943031AE2-326 GEN
Solar/Wind Harmer
5.3
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.103
966881AG1-559 GEN
Solar/Wind Helper
0.105
970281AG2-184 GEN
Solar/Wind Harmer
1.065
970563AG2-360 GEN
50/50
33.718
970823AG2-518 GEN
50/50
5.8
970913AG2-568 GEN
Solar/Wind Harmer
0.425
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.327
971313AH1-133 GEN
Solar/Wind Harmer
0.46
971329AH1-144 GEN
Solar/Wind Harmer
0.57
971331AH1-145 GEN
Solar/Wind Harmer
13.028
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.632
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.048
966391AG1-508 GEN
Solar/Wind Harmer
4.005
971981AH1-535 GEN
Solar/Wind Harmer
0.507
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.056
971881AH1-461 GEN
50/50
10.649
316217AC1-145 GEN
Solar/Wind Helper
0.379
316473AC1-191 GEN
Solar/Wind Helper
0.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
83.37
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.655
NYPJM->LTFIMP_NY
CLTF
1.939
LGEELTFEXP_LGEE->PJM
CLTF
4.284
WECLTFEXP_WEC->PJM
CLTF
2.133
CPLELTFEXP_CPLE->PJM
CLTF
2.043
TVALTFEXP_TVA->PJM
CLTF
6.903
MECLTFEXP_MEC->PJM
CLTF
9.794
LAGNLTFEXP_LAGN->PJM
CLTF
12.957
SIGELTFEXP_SIGE->PJM
CLTF
0.322
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:186.07 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2195.62
MW Contribution:
21.3
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
21.304

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#5454_05MOSELEY 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#5454_05MOSELEY 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.94 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2170.52
MW Contribution:
1.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.999
24290605CLAY-1
50/50
0.171
24290605CLAY-1
50/50
0.171
24290705CLAY-2
50/50
0.171
24290705CLAY-2
50/50
0.171
24728205BUCHG1
50/50
5.624
24728305BUCHG2
50/50
5.452
3142416OLDCHRC
Solar/Wind Helper
0.811
3142416OLDCHRC
Solar/Wind Helper
0.311
3147123OTTER R
Solar/Wind Helper
0.229
3147312GRETNA
Solar/Wind Helper
0.078
3147312GRETNA
Solar/Wind Helper
0.313
270205AE1-176
50/50
0.015
3146802CHATHAM
Solar/Wind Helper
0.294
316312AB1-027
Solar/Wind Helper
0.125
316447AC1-158 HLD
Solar/Wind Helper
0.843
316044AC1-158 PL1
Solar/Wind Helper
0.383
316045AC1-158 PL2
Solar/Wind Helper
1.226
316450AC1-158 RIC
Solar/Wind Helper
0.102
316468AD1-105 GEN
Solar/Wind Helper
0.372
270173AC1-122 GEN
Solar/Wind Helper
0.458
270583AD2-179 GEN
Solar/Wind Harmer
0.82
270494AE1-108_GEN
Solar/Wind Helper
0.917
270346AE1-212 GEN
Solar/Wind Harmer
0.543
270030AE2-140 GEN
Solar/Wind Harmer
1.108
270069AE2-166 C O1
Solar/Wind Harmer
0.542
24734705WLF1G3
50/50
6.885
24734805WLF1G4
50/50
6.885
24734905WLF1G5
50/50
6.885
24735105WLF2G1
50/50
6.728
24735205WLF2G2
50/50
6.728
316197AC1-042 GEN
Solar/Wind Helper
0.264
943031AE2-326 GEN
Solar/Wind Harmer
5.227
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.101
966881AG1-559 GEN
Solar/Wind Helper
0.104
970281AG2-184 GEN
Solar/Wind Harmer
1.051
970563AG2-360 GEN
50/50
33.297
970823AG2-518 GEN
50/50
5.554
970913AG2-568 GEN
Solar/Wind Harmer
0.416
971225AH1-072 GEN
Solar/Wind Harmer
0.109
971227AH1-073 GEN
Solar/Wind Harmer
0.109
971277AH1-098 GEN
Solar/Wind Harmer
0.322
971313AH1-133 GEN
Solar/Wind Harmer
0.453
971329AH1-144 GEN
Solar/Wind Harmer
0.549
971331AH1-145 GEN
Solar/Wind Harmer
12.547
971403AH1-188 GEN
Solar/Wind Harmer
0.713
971461AH1-227 GEN
Solar/Wind Harmer
0.279
971543AH1-269 GEN
50/50
8.315
971687AH1-348 GEN
Solar/Wind Harmer
0.054
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
966391AG1-508 GEN
Solar/Wind Harmer
3.937
971981AH1-535 GEN
Solar/Wind Harmer
0.502
972103AH1-617 GEN
Solar/Wind Harmer
1.001
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.007
971881AH1-461 GEN
50/50
10.468
316217AC1-145 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
0.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
78.323
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.533
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.717
NYPJM->LTFIMP_NY
CLTF
1.924
LGEELTFEXP_LGEE->PJM
CLTF
4.231
WECLTFEXP_WEC->PJM
CLTF
2.106
CPLELTFEXP_CPLE->PJM
CLTF
2.127
TVALTFEXP_TVA->PJM
CLTF
6.843
MECLTFEXP_MEC->PJM
CLTF
9.681
LAGNLTFEXP_LAGN->PJM
CLTF
12.848
SIGELTFEXP_SIGE->PJM
CLTF
0.319
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.648
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.189

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2132.35
MW Contribution:
24.2
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
24.202

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:161.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1907.61
MW Contribution:
21.65
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
21.648

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:159.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1884.01
MW Contribution:
20.68
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.684

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:155.65 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1836.67
MW Contribution:
20.7
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.7

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:155.28 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1832.29
MW Contribution:
20.83
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.827

Details for [AG2-184] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.97 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:1781.48
MW Contribution:
20.73
IPD Plant:AG2-184
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
20.726

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:209.86
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.04 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:209.84
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:209.86
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.04 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:209.84
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210
CONTINGENCY 'DVP_P1-2: LN 553_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314910 TO BUS 313378 CKT 1   /*8CUNINGHAM   500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: 542T553_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P4-2: 553T564_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315216                                                /*1CUNINGA      18.0
 OPEN BUS 315219                                                /*1CUNINGD      22.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P2-2_#5454_05MOSELEY 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 243923 CKT 1   /*05MOSELEY    138.0 - 05MOSELYEQ     1.0
 OPEN BRANCH FROM BUS 242724 TO BUS 243935 CKT 1   /*05MOSELEY    138.0 - 05WHEELBR     13.8
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A'
 DISCONNECT BRANCH FROM BUS 972103 TO BUS 243689 CKT Z1   /*AH1-617 GEN  138.0 - 05HARBER     138.0
END
290614 to 242515 ckt 1
243689 to 243875 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-184 was evaluated as a 210.0 MW injection

AG2-184 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 210.0 MW (210.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
15.75
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
15.75
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
15.75
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
15.75
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
14.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
14.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
14.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
11.54
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
12.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
12.37
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
12.22
GD2AEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC121.83 %184.0A224.17
115.5
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Base Case
SingleAC114.99 %184.0A211.58
210.0
IPDAEP
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
SingleAC114.99 %184.0B211.58
210.0

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
15.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.823
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
15.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
315616AA1-038_C
Solar/Wind Helper
1.962
316382AG1-145 C
Solar/Wind Helper
0.541
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.175
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.824
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.58
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.178
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
15.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316258AE1-075 C
Solar/Wind Helper
0.52
970563AG2-360 GEN
50/50
45.014
972273AH1-721 GEN
50/50
85.068
316468AD1-105 GEN
Solar/Wind Helper
2.227
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
971543AH1-269 GEN
50/50
11.496
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.229
315821AE2-092 GEN
Solar/Wind Helper
3.841
971507AH1-251 GEN
50/50
Charging
5.867
957191AF2-013 GEN
50/50
Charging
10.663
943031AE2-326 GEN
Solar/Wind Harmer
11.708
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.43
315651AD1-115 GEN
Solar/Wind Helper
4.205
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.26
971881AH1-461 GEN
50/50
14.323
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
316303AF2-085
50/50
Charging
2.246
270583AD2-179 GEN
Solar/Wind Harmer
12.446
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.746
972103AH1-617 GEN
Solar/Wind Harmer
14.996
316447AC1-158 HLD
Solar/Wind Helper
5.083
316192AB2-158 GEN
Solar/Wind Helper
2.769
963031AG1-152 GEN
50/50
Charging
10.856
960911AF2-382 GEN
Solar/Wind Harmer
6.616
270030AE2-140 GEN
Solar/Wind Harmer
17.478
316059AD1-063 C
Solar/Wind Helper
0.419
970417AG2-272 GEN
50/50
8.425
270069AE2-166 C O1
Solar/Wind Harmer
8.425
966001AG1-469 GEN
Solar/Wind Helper
0.424
315616AA1-038_C
Solar/Wind Helper
2.018
316382AG1-145 C
Solar/Wind Helper
0.541
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971981AH1-535 GEN
Solar/Wind Harmer
7.211
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.972
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.368
970365AG2-240 GEN
50/50
Charging
1.247
316405AF2-144 C
50/50
Charging
1.177
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971461AH1-227 GEN
Solar/Wind Harmer
4.168
316405AF2-144 C
Solar/Wind Helper
0.491
316404AE1-155 C
Solar/Wind Helper
3.567
315662AE1-191 GEN
Solar/Wind Helper
2.223
971531AH1-263 GEN
50/50
Charging
23.682
972293SS25-0014
50/50
Charging
57.048
270346AE1-212 GEN
Solar/Wind Harmer
8.185
971981AH1-535 GEN
Solar/Wind Harmer
6.61
316044AC1-158 PL1
Solar/Wind Helper
2.31
944491AF1-114 GEN
Solar/Wind Helper
2.859
316487AF1-042 GEN
Solar/Wind Helper
1.167
316280AD1-041 GEN
Solar/Wind Helper
1.389
270399AC1-101 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.437
316337AD2-073 GEN
Solar/Wind Helper
0.564
315666AE1-190 GEN
Solar/Wind Helper
0.556
970119AG2-088 GEN
50/50
Charging
16.846
971277AH1-098 GEN
Solar/Wind Harmer
4.143
270494AE1-108_GEN
Solar/Wind Helper
5.59
316164AC1-076 GEN
Solar/Wind Helper
1.941
316313AB2-026
Solar/Wind Helper
0.578
316223AC1-118
Solar/Wind Helper
0.568
316203AE2-005 GEN
Solar/Wind Helper
3.62
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.393
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
NYPJM->LTFIMP_NY
CLTF
2.177
TVALTFEXP_TVA->PJM
CLTF
9.524
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
LGEELTFEXP_LGEE->PJM
CLTF
5.764
MECLTFEXP_MEC->PJM
CLTF
13.347
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
CPLELTFEXP_CPLE->PJM
CLTF
4.745
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
WECLTFEXP_WEC->PJM
CLTF
2.895
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
15.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316075AC2-137 C
Solar/Wind Helper
0.581
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
961951AG1-038 GEN
Solar/Wind Helper
1.258
971881AH1-461 GEN
50/50
14.324
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316192AB2-158 GEN
Solar/Wind Helper
2.765
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270399AC1-101 GEN
Solar/Wind Harmer
3.469
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
957241AF2-018 GEN
Solar/Wind Harmer
0
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.823
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
944971AF1-162 GEN
Solar/Wind Harmer
2.093
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270053AF1-130 C
Solar/Wind Harmer
12.797
316233AE1-074 FULL
Solar/Wind Helper
0.6
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
14.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
14.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
14.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
316473AC1-191 GEN
Solar/Wind Helper
2.25
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270030AE2-140 GEN
Solar/Wind Harmer
3.161
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
944491AF1-114 GEN
Solar/Wind Helper
2.702
957241AF2-018 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
12.03
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
11.54
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3147312GRETNA
Solar/Wind Harmer
0.068
970563AG2-360 GEN
50/50
34.767
962751AG1-124 GEN
Solar/Wind Harmer
6.233
3147312GRETNA
Solar/Wind Harmer
0.273
971687AH1-348 GEN
Solar/Wind Harmer
0.626
971543AH1-269 GEN
50/50
8.911
971313AH1-133 GEN
Solar/Wind Harmer
4.952
3146802CHATHAM
Solar/Wind Harmer
0.256
971507AH1-251 GEN
50/50
Charging
5.111
943031AE2-326 GEN
Solar/Wind Harmer
9.019
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
966881AG1-559 GEN
Solar/Wind Helper
0.39
971881AH1-461 GEN
50/50
11.072
270583AD2-179 GEN
Solar/Wind Harmer
9.646
943811AF1-049 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.188
316447AC1-158 HLD
Solar/Wind Helper
4.5
970281AG2-184 GEN
Solar/Wind Harmer
11.543
270030AE2-140 GEN
Solar/Wind Harmer
14.894
960911AF2-382 GEN
Solar/Wind Harmer
5.121
970417AG2-272 GEN
50/50
7.231
270069AE2-166 C O1
Solar/Wind Harmer
7.142
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971981AH1-535 GEN
Solar/Wind Harmer
5.645
316450AC1-158 RIC
Solar/Wind Helper
0.545
970823AG2-518 GEN
50/50
14.96
966391AG1-508 GEN
Solar/Wind Harmer
7.933
942671AE2-283 GEN
Solar/Wind Harmer
3.623
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971531AH1-263 GEN
50/50
Charging
20.999
972293SS25-0014
50/50
Charging
50.508
270346AE1-212 GEN
Solar/Wind Harmer
6.338
971981AH1-535 GEN
Solar/Wind Harmer
5.175
316044AC1-158 PL1
Solar/Wind Helper
2.046
961131AF2-404 GEN
Solar/Wind Harmer
2.357
971277AH1-098 GEN
Solar/Wind Harmer
3.215
941801AE2-185 GEN
Solar/Wind Harmer
4.102
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.261
941621AE2-160 GEN
50/50
5.119
970913AG2-568 GEN
Solar/Wind Harmer
4.573
316045AC1-158 PL2
Solar/Wind Helper
6.545
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
CPLELTFEXP_CPLE->PJM
CLTF
4.184
SIGELTFEXP_SIGE->PJM
CLTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
NYPJM->LTFIMP_NY
CLTF
1.786
TVALTFEXP_TVA->PJM
CLTF
7.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
WECLTFEXP_WEC->PJM
CLTF
2.293
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
LGEELTFEXP_LGEE->PJM
CLTF
4.54
MECLTFEXP_MEC->PJM
CLTF
10.573
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
12.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
35.173
971687AH1-348 GEN
Solar/Wind Harmer
0.633
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971881AH1-461 GEN
50/50
11.185
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
316450AC1-158 RIC
Solar/Wind Helper
0.529
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
961131AF2-404 GEN
50/50
Charging
2.924
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
941621AE2-160 GEN
50/50
5.212
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
12.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
35.173
971687AH1-348 GEN
Solar/Wind Harmer
0.633
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971881AH1-461 GEN
50/50
11.185
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
316450AC1-158 RIC
Solar/Wind Helper
0.529
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
961131AF2-404 GEN
50/50
Charging
2.924
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
941621AE2-160 GEN
50/50
5.212
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
12.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
34.746
971687AH1-348 GEN
Solar/Wind Harmer
0.625
971543AH1-269 GEN
50/50
8.605
971313AH1-133 GEN
Solar/Wind Harmer
4.935
943031AE2-326 GEN
Solar/Wind Harmer
9.004
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
971881AH1-461 GEN
50/50
11.002
270583AD2-179 GEN
Solar/Wind Harmer
9.325
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.222
972103AH1-617 GEN
Solar/Wind Harmer
11.64
316447AC1-158 HLD
Solar/Wind Helper
4.334
960911AF2-382 GEN
Solar/Wind Harmer
5.113
270030AE2-140 GEN
Solar/Wind Harmer
12.937
970417AG2-272 GEN
50/50
6.208
270069AE2-166 C O1
Solar/Wind Harmer
6.298
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971981AH1-535 GEN
Solar/Wind Harmer
5.54
316450AC1-158 RIC
Solar/Wind Helper
0.525
970823AG2-518 GEN
50/50
14.377
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971531AH1-263 GEN
50/50
Charging
20.247
972293SS25-0014
50/50
Charging
48.638
270346AE1-212 GEN
Solar/Wind Harmer
6.24
971981AH1-535 GEN
Solar/Wind Harmer
5.078
316044AC1-158 PL1
Solar/Wind Helper
1.97
270399AC1-101 GEN
Solar/Wind Harmer
1.311
971277AH1-098 GEN
Solar/Wind Harmer
3.175
270494AE1-108_GEN
Solar/Wind Helper
4.907
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971403AH1-188 GEN
Solar/Wind Harmer
8.284
270173AC1-122 GEN
Solar/Wind Helper
2.227
941621AE2-160 GEN
50/50
5.101
970913AG2-568 GEN
Solar/Wind Harmer
4.564
316045AC1-158 PL2
Solar/Wind Helper
6.303
270400AC1-102 GEN
Solar/Wind Harmer
1.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
NYPJM->LTFIMP_NY
CLTF
1.636
TVALTFEXP_TVA->PJM
CLTF
7.32
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
LGEELTFEXP_LGEE->PJM
CLTF
4.537
MECLTFEXP_MEC->PJM
CLTF
10.492
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
CPLELTFEXP_CPLE->PJM
CLTF
3.149
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
WECLTFEXP_WEC->PJM
CLTF
2.291
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207

Details for 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.83 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:224.17
MW Contribution:
115.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.84 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:224.18
MW Contribution:
115.5
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
115.5
972103AH1-617 GEN
Solar/Wind Harmer
110

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.99 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:211.58
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.45 %
Rating:184.0 MVA
Rating Type:A
MVA to Mitigate:210.59
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210

Details for [AG2-184] 05HARBER-05SOFTSH 138.0 kV Ckt 1 line l/o AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.99 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:211.58
MW Contribution:
210.0
IPD Plant:AG2-184
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05HARBER-05SOFTSH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.45 %
Rating:184.0 MVA
Rating Type:B
MVA to Mitigate:210.59
MW Contribution:
210.0
IPD Plant:AG2-184
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
PJM_IPD
210
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
CONTINGENCY 'AEP_P1-2_AH1-617 GEN-05HARBER-138_SRT-A'
 DISCONNECT BRANCH FROM BUS 972103 TO BUS 243689 CKT Z1   /*AH1-617 GEN  138.0 - 05HARBER     138.0
END
290614 to 242515 ckt 1
243689 to 243875 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-184 and AH1-617 in PJM Transition Cycle 2, Cluster 31 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 31 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 31 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 31 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 31 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 31 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 31 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 31 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

Here is a list of additional observations:

       •       AG2-184 and AH1-617 exhibited slow voltage recovery for some contingencies. Although this issue did not cause instability in the system, the model was tuned to achieve faster voltage recovery post-fault clearance. This was accomplished by adjusting Ki and Kp parameters in the plant controller (PLNTBU1) for AG2-184 and AH1-617, setting Kp to 0.15 from its original value of 0.1, and Ki to 0.35 from its original value of 0.1.

       •       CRG1H unit exhibited slow damping dynamics in several contingencies. The simulations were run for 30 seconds and were found to be stable.

       •       AC1-101 GEN 1 and AC1-102 GEN 1 experienced breaker time-out for relay instances 92623407 and 92624007, respectively. It was tested and observed that the issue is caused by numerical issues. The pick-up times for these relay instances were increased to 1 cycle to mitigate the issue.

       •       The IPCMD and IQCMD states in the REGCAU1 model of AG2-184 and AH1-617 showed erratic behavior for some contingencies in which AG2-184 and AH1-617 have been disconnected as part of the contingency event. Since the machine is disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 31 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-184

Solar

AEP

210

Harbert Metering 138 kV

AH1-617

Solar

AEP

200

Harbert Metering 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-184 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-088Midlothian 230 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-230Dumont 345 kVActive
AG2-240Old Church 34.5 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-461Buckhorn 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-049Wurno 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-184 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9769.005CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBsCost Allocated$3,387,027N/A
AEPn9771.005LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Rebuild/Reconductor Entrance SpanCost Allocated$1,132,681N/A
AEPn9765.005CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Rebuild Entrance SpanCost Allocated$1,035,670N/A
AEPn9764.005ELKGARDNSS 138.0 kV to 05SALTV1 138.0 kV ckt 1 - Reconductor entrance spanCost Allocated$1,035,670N/A
AEPn9763.005J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace WavetrapsCost Allocated$306,832N/A
AEPn9761.005CLNCHR 138.0 kV to 05ABINGD 138.0 kV ckt 1 - Sag StudyCost Allocated$76,721N/A
AEPn9762.005HARBER 138.0 kV to 05SOFTSH 138.0 kV ckt 1 - Replace sub conductorCost Allocated$51,220N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4068.1b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Contingent$0N/A
AEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardContingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Grand Total:$7,025,821

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$3,387,027
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07279.0 MW35.1%$8,763,492
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
30.5 MW13.5%$3,387,027
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
29.1 MW12.9%$3,225,746
AH1-72186.7 MW38.5%$9,623,735

System Reinforcement: n9771.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9771.0 / AEP-TC2-19073
Title
05LEBANO 138.0 kV to 05ELKGARDNSS 138.0 kV ckt 1 - Rebuild/Reconductor Entrance Span
Description
Rebuild/Reconductor entrance span from Str. 74-34 to Lebanon with 1590 ACSR. Replace station conductor at Lebanon
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,132,681
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05LEBANO-05ELKGARDNSS 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A387.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
20.8 MW28.3%$1,132,681
AH1-072 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
3.1 MW4.2%$169,549
AH1-073 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
3.1 MW4.2%$169,549
AH1-2278.0 MW10.9%$434,856
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
19.8 MW27.0%$1,078,738
AH1-72118.7 MW25.4%$1,014,628

System Reinforcement: n9765.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9765.0 / AEP-TC2-19065
Title
05CLNCHR 138.0 kV to 05LEBANO 138.0 kV ckt 1 - Rebuild Entrance Span
Description
Rebuild/Reconductor entrance span from Clinch River - Str. 74-1 with 1590 ACSR. Rebuild/Reconductor entrance span from Str. 74-33 to Lebanon with 1590 ACSR. Replace station conductor at Clinch River and Lebanon
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,035,670
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05CLNCHR-05LEBANO 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A338.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.8 MW25.9%$1,035,670
AH1-072 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-073 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-2276.7 MW9.7%$389,568
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.0 MW24.7%$986,328
AH1-72122.1 MW32.1%$1,284,708

System Reinforcement: n9764.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9764.0 / AEP-TC2-19061
Title
05ELKGARDNSS 138.0 kV to 05SALTV1 138.0 kV ckt 1 - Reconductor entrance span
Description
Rebuild/Reconductor entrance span from Str 74-102 to Saltville with 1590 ACSR. Replace station conductor at Saltville 138 kV Station
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$1,035,670
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05SALTV1-05ELKGARDNSS 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A387.0 MVA
(All)B446.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.8 MW25.9%$1,035,670
AH1-072 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-073 ⧉ New AH1-072 swyd (Red Onion - VC5 69 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AH1-072, AH1-073
2.6 MW3.8%$151,863
AH1-2276.7 MW9.7%$389,568
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
17.0 MW24.7%$986,328
AH1-72122.1 MW32.1%$1,284,708

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$306,832
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07279.0 MW24.1%$793,888
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
30.5 MW9.3%$306,832
AG2-36055.2 MW16.8%$555,293
AG2-363 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
28.6 MW8.7%$287,968
AG2-364 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
19.1 MW5.8%$191,979
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
29.1 MW8.9%$292,222
AH1-72186.7 MW26.4%$871,818

System Reinforcement: n9761.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9761.0 / AEP-TC2-19056
Title
05CLNCHR 138.0 kV to 05ABINGD 138.0 kV ckt 1 - Sag Study
Description
Sag Study Clinch River - Abingdon 138 kV line between structure 71-84/72 to Clinch River Station
Total Cost ($USD)
$180,000
Discounted Total Cost ($USD)
$180,000
Allocated Cost ($USD)
$76,721
Time Estimate
12 to 24 Months

Contributor

FacilityContingency
05ABINGD-05CLNCHR 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A223.0 MVA
(All)B310.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
15.4 MW42.6%$76,721
AH1-2276.0 MW16.8%$30,207
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
14.6 MW40.6%$73,071

System Reinforcement: n9762.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9762.0 / AEP-TC2-19058
Title
05HARBER 138.0 kV to 05SOFTSH 138.0 kV ckt 1 - Replace sub conductor
Description
Replace Sub conductor 795 AAC 37 Str at Harbert Metering. Address CT Thermal Limit 795 Amps at Softshell.
Total Cost ($USD)
$100,000
Discounted Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$51,220
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05HARBER-05SOFTSH 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A251.0 MVA
(All)B319.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
210.0 MW51.2%$51,220
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
200.0 MW48.8%$48,780

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-184 may not presently have cost responsibility for this upgrade, AG2-184 may need this upgrade in-service to be deliverable to the PJM system. If AG2-184 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1445_ZIMMER_SRT-A
No new ratings for this Flowgate.
09STUART-7SPURLOCK 345.0 kV Ckt 1 lineDEOK_P4_1449_ZIMMER_SRT-A
No new ratings for this Flowgate.
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-184


AG2-184 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4068.1 / AEP-TC2-18693b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Topology-0.0%Contingent$0
Load FlowAEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardTopology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-184 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-184 One Line Diagram

AG2-184 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.