AG2-216 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:45

East Sidney-Quincy 138 kV

25.92 MW Capacity / 0.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Clearview Solar I, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is The Dayton Power and Light Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 25.9 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the The Dayton Power and Light Company zone — Champaign County, Ohio. This project is an increase to the developer’s AE2-206/AF1-078 project(s), which will share the same Point of Interconnection. The AG2-216 project is a 25.92 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 144.0 MW with 86.4 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-216
Project Name:
East Sidney-Quincy 138 kV
Project Developer Name:
Clearview Solar I, LLC
State:
Ohio
County:
Champaign
Transmission Owner:
The Dayton Power and Light Company
MFO:
144.0
MWE:
0.0
MWC:
25.92
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AG2-216 will interconnect on the The Dayton Power and Light Company transmission system tapping the East Sidney - Quincy 138 kV line .

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-216 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-216Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-216

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-216
Project ID: AG2-216
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $103,680
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dayton interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-216 was evaluated as a 0.0 MW (25.92 MW Capacity) injection in the Dayton area.

AG2-216 was evaluated as part of a plant. The plant consists of AG2-216. The total Energy output of the plant was evaluated at its maximum seasonal capability of 144.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
4.18
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
5.08
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
1.4

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
4.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
3.99
Bus #Bus NameTypeMW Contribution
270159DARBY CT4
50/50
0.828
961821AG1-024 GEN
Solar/Wind Harmer
7.494
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
241972AD1-140 GEN
Solar/Wind Harmer
1.102
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.469
274776LINCOLN ;7U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274746AC1-111 G10
Adder
7.068
270356AE2-297 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.477
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.695
20089126CSLMN_L13
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
238118U2-030_1
Solar/Wind Helper
0.283
270475AD2-096_GEN
50/50
10.581
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
970191AG2-125 GEN
Solar/Wind Harmer
2.379
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.936
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
276843GEN-1.7
Solar/Wind Harmer
0.288
274803UNIV PARK;6U
Adder
7.433
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
965091AG1-374 GEN
Solar/Wind Harmer
25.867
274760LEE CO EC;1U
Adder
11.496
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965931AG1-462 GEN
Solar/Wind Harmer
21.621
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.893
203854AF2-039 C
Solar/Wind Helper
0.327
961921AG1-034 GEN
Solar/Wind Harmer
11.241
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
944531AF1-118 GEN
Solar/Wind Harmer
41.277
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970781AG2-491 GEN
Solar/Wind Harmer
9.079
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
10.545
274887GEN-1.85
Solar/Wind Harmer
0.231
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
25196608WSDLE5
Adder
10.674
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.384
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
270051AF1-062 GEN
50/50
18.043
270043AE2-236 GEN
Solar/Wind Harmer
5.885
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
970825AG2-519 GEN
Solar/Wind Harmer
6.737
274724RIVER EC ;11
Adder
22.661
972259AH1-714 GEN
Adder
24.311
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
274729ELWOOD EC;1P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
945111AF1-176 GEN
Solar/Wind Harmer
7.15
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
970571AG2-364 GEN
Solar/Wind Harmer
17.368
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
270166AC1-044 GEN3
50/50
13.691
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
945371AF1-202 GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
957891AF2-083 GEN
Solar/Wind Harmer
14.717
945111AF1-176 GEN
Solar/Wind Harmer
15.739
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.591
970569AG2-363 GEN
Solar/Wind Harmer
26.052
939741AE1-205 GEN
Solar/Wind Harmer
12.131
252510AF1-249 C
Solar/Wind Harmer
0.065
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.662
270119AB2-067 GEN1
50/50
13.691
25326509SID D
50/50
1.895
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.637
24387305FR-4G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
274805UNIV PK N;1U
Adder
6.41
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
246937BC-WTG2
Solar/Wind Harmer
0.358
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
962691AG1-118 GEN
Solar/Wind Harmer
26.273
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274762LEE CO EC;3U
Adder
11.496
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.733
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270459AD2-067 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.821
24729505KEY G4
Adder
8.54
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.262
971771AH1-392 GEN
Solar/Wind Harmer
8.94
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274728ELWOOD EC;5P
Adder
20.872
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
25196408WSDLE3
Adder
10.988
270007AE1-245 C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.611
203940AF1-140 C
Solar/Wind Helper
0.411
970149AG2-104 GEN
Solar/Wind Harmer
27.654
971917AH1-482 GEN
Solar/Wind Harmer
11.826
970373AG2-245 GEN
Solar/Wind Harmer
19.061
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
20.916
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
943021AE2-325 GEN
Solar/Wind Harmer
4.573
276882AE2-255 GEN
Solar/Wind Harmer
1.021
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
274822ROCKFORD ;11
Adder
24.404
276655WTG1_EQ
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
10.388
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
970091AG2-072 GEN
Adder
16.07
270161DARBY CT6
50/50
0.813
25326109MON D
50/50
1.903
942861AE2-305 GEN
Solar/Wind Harmer
8.674
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
945421AF1-207 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.609
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.672
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
12.809
247620Y3-023
Adder
0.586
274695ROCKY RD ;2P
Adder
14.015
958491AF2-143 GEN
Solar/Wind Harmer
13.148
276872AE1-163_GEN1
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.757
972236AH1-702 GEN2
Adder
2.723
274765LEE CO EC;6U
Adder
11.523
274763LEE CO EC;4U
Adder
11.388
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
235531U2-073 GEN
Solar/Wind Helper
2.67
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270466AD2-091
50/50
8.422
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
16.303
270462AD2-086
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
13.735
960971AF2-388 GEN
Solar/Wind Harmer
5.346
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
8.243
966841AG1-555 GEN
Solar/Wind Harmer
1.019
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
274808UNIV PK N;4U
Adder
6.368
926881AC1-175 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
19.549
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274693ROCKY RD ;1P
Adder
13.877
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276876AE1-163_GEN2
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
972235AH1-702 GEN1
Adder
3.131
960611AF2-352 GEN
Solar/Wind Harmer
2.874
274764LEE CO EC;5U
Adder
11.523
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276615X2-022 GEN
Solar/Wind Harmer
0.088
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
946071AF1-272 GEN
Solar/Wind Helper
2.879
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
23585401KL_K28_T16
Solar/Wind Helper
1.267
238117U2-030
Solar/Wind Helper
0.283
962761AG1-125 GEN
Solar/Wind Harmer
51.21
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
10.545
274802UNIV PARK;5U
Adder
7.433
270437AC2-090 C
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
939401AE1-172 GEN
Solar/Wind Harmer
6.59
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274766LEE CO EC;7U
Adder
11.361
276708O09 GEN2
Solar/Wind Harmer
0.303
965911AG1-460 GEN
Solar/Wind Harmer
1.674
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
203855AF2-088 C
Solar/Wind Helper
0.158
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
247536S-71 GEN
Solar/Wind Harmer
0.358
965051AG1-369 GEN
Solar/Wind Harmer
4.466
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971029AG2-637 GEN
Solar/Wind Harmer
13.408
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972037AH1-567 GEN1
Adder
0.233
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
971675AH1-338 GEN
Solar/Wind Harmer
3.397
971411AH1-196 GEN
Solar/Wind Harmer
13.063
971171AH1-044 GEN
Solar/Wind Harmer
17.379
274823ROCKFORD ;21
Adder
24.227
274853TWINGROVE;U1
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.127
946321AF1-296 GEN
Solar/Wind Harmer
4.758
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.498
203955AF1-039 C O1
Solar/Wind Helper
0.38
23750701CROSSCHOOL
Solar/Wind Helper
1.182
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
270284AF1-227 GEN1
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
274811UNIV PK N;7U
Adder
6.396
276806AD2-047 C O1
Solar/Wind Harmer
5.041
274676JOLIET 29;8U
Adder
37.578
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
24695305TIMB G C
Solar/Wind Harmer
0.747
274682WAUKEGAN ;7U
Adder
22.607
959091AF2-200 GEN
Solar/Wind Harmer
17.379
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
274767LEE CO EC;8U
Adder
11.361
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
203993AD2-133_GEN1
Solar/Wind Helper
1.055
970155AG2-107 GEN
Solar/Wind Harmer
32.701
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.673
971995AH1-542 GEN
Solar/Wind Harmer
3.337
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
970613AG2-401 GEN
Solar/Wind Harmer
6.512
274676JOLIET 29;8U
Adder
38.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
957471AF2-041 GEN
Solar/Wind Harmer
26.068
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
274848CAMPGROVE;RU
Solar/Wind Harmer
0
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
3.602
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
4.358
965681AG1-436 GEN
Solar/Wind Harmer
11.293
247621Y3-024
Adder
0.31
270246TR4_N_V150
Solar/Wind Harmer
0.057
276776AD2-060 GEN
Solar/Wind Harmer
0.949
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.053
203818AF1-086 GEN
Solar/Wind Helper
1.772
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
25306009OHH W.
Adder
3.829
970289AG2-191 GEN
Solar/Wind Harmer
1.733
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
247521TR3_G114
Solar/Wind Harmer
0.324
972227AH1-698 GEN1
Adder
3.325
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
970169AG2-114 GEN
Solar/Wind Harmer
8.736
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
CPLELTFEXP_CPLE->PJM
CLTF
2.319
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
NYPJM->LTFIMP_NY
CLTF
5.162
TVALTFEXP_TVA->PJM
CLTF
8.46
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
WECLTFEXP_WEC->PJM
CLTF
4.743
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
LGEELTFEXP_LGEE->PJM
CLTF
7.836
MECLTFEXP_MEC->PJM
CLTF
19.491
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
5.08
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
4.2
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
14.072
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
971199AH1-059 GEN
Solar/Wind Harmer
2.255
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
12.279
24690905MDL-1G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274803UNIV PARK;6U
Adder
8.599
276843GEN-1.7
Solar/Wind Harmer
0.332
972038AH1-567 GEN2
Adder
0.538
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
274752CRETE EC ;2U
Adder
12.279
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
970707AG2-453 GEN
Solar/Wind Harmer
33.528
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
24.024
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.19
970193AG2-126 GEN
Solar/Wind Harmer
13.784
270541AE2-072 C
Solar/Wind Harmer
0.001
25196608WSDLE5
Adder
10.619
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
270051AF1-062 GEN
50/50
23.559
246938BC-WTG3
Solar/Wind Harmer
0.406
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
274772LINCOLN ;3U
Adder
12.619
274724RIVER EC ;11
Adder
26.355
972259AH1-714 GEN
Adder
28.051
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
970825AG2-519 GEN
Solar/Wind Harmer
7.486
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
970571AG2-364 GEN
Solar/Wind Harmer
19.606
270240V3-007_GEN2
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.285
25196008MFTGT1
Adder
1.61
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
942481AE2-261 GEN
Solar/Wind Harmer
16.491
270166AC1-044 GEN3
50/50
17.244
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965011AG1-365 GEN
Solar/Wind Harmer
11.206
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274723RIVER EC ;12
Adder
26.668
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
970569AG2-363 GEN
Solar/Wind Harmer
29.408
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
276621W2-048 GEN
Solar/Wind Harmer
0.459
25196008MFTGT1
Adder
1.662
25196808ZIMRHP
Adder
90.149
238126S14_GEN_1
Solar/Wind Helper
0.635
270119AB2-067 GEN1
50/50
17.244
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.96
942221AE2-234 GEN
Solar/Wind Harmer
4.232
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
274805UNIV PK N;1U
Adder
7.439
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
276893AG1-478 C
Solar/Wind Harmer
0.68
24387305FR-4G C
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
16.391
274697ROCKY RD ;3P
Adder
4.35
962691AG1-118 GEN
Solar/Wind Harmer
29.945
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274762LEE CO EC;3U
Adder
12.93
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
276838X2-022 GEN2
Solar/Wind Harmer
0.516
23751201ROTHROCK
Solar/Wind Helper
0.691
237043AE2-125 C
Solar/Wind Helper
0.16
270459AD2-067 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.43
270071AF1-092 GEN
Solar/Wind Harmer
21.261
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
10.756
24729505KEY G4
Adder
9.953
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
24.024
971549AH1-272 GEN
Solar/Wind Harmer
20.903
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.944
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
270004AE1-209 GEN
Solar/Wind Harmer
2.149
274760LEE CO EC;1U
Adder
12.93
24379505HDWTR1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
965931AG1-462 GEN
Solar/Wind Harmer
23.963
23562501BACKB
Solar/Wind Helper
0.847
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970373AG2-245 GEN
Solar/Wind Harmer
22.382
943021AE2-325 GEN
Solar/Wind Harmer
5.553
971917AH1-482 GEN
Solar/Wind Harmer
13.746
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
970773AG2-487 GEN
Solar/Wind Harmer
1.647
970091AG2-072 GEN
Adder
20.654
942861AE2-305 GEN
Solar/Wind Harmer
10.655
970329AG2-216 GEN
Solar/Wind Harmer
5.083
247620Y3-023
Adder
0.71
965791AG1-447 GEN
Solar/Wind Harmer
9.845
25326109MON D
Adder
1.994
944541AF1-119 GEN
Solar/Wind Harmer
0.7
945421AF1-207 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.803
270031AE2-169
Solar/Wind Harmer
5.58
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274695ROCKY RD ;2P
Adder
16.014
958491AF2-143 GEN
Solar/Wind Harmer
14.984
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
12.96
274763LEE CO EC;4U
Adder
12.808
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
235054AD2-180 GEN
Solar/Wind Helper
1.576
235531U2-073 GEN
Solar/Wind Helper
2.548
24721605FLATG1
50/50
3.319
961821AG1-024 GEN
Solar/Wind Harmer
9.821
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
959331AF2-224 GEN
Solar/Wind Harmer
7.844
965041AG1-368 GEN
Solar/Wind Harmer
11.063
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
971609AH1-304 GEN
Solar/Wind Harmer
1.657
274746AC1-111 G10
Adder
8.105
964611AG1-324 GEN
Solar/Wind Harmer
3.923
963841AG1-237 GEN
Solar/Wind Harmer
4.303
926823AC1-168 GEN
Solar/Wind Harmer
1.667
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.924
23750501ELLIOTTS
Solar/Wind Helper
0.6
238118U2-030_1
Solar/Wind Helper
0.267
270120AB2-067 GEN2
50/50
17.244
270054AF2-122 C O1
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
270247TR4_N_V136
Solar/Wind Harmer
0.071
970349AG2-230 GEN
Solar/Wind Harmer
16.464
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
960971AF2-388 GEN
Solar/Wind Harmer
6.145
944231AF1-091 GEN
Solar/Wind Harmer
24.097
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
7.391
274674JOLIET 9 ;6U
Adder
22.504
962761AG1-125 GEN
Solar/Wind Harmer
73.48
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
962781AG1-127 GEN
Solar/Wind Harmer
9.482
274766LEE CO EC;7U
Adder
12.777
270437AC2-090 C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.34
965911AG1-460 GEN
Solar/Wind Harmer
1.103
270599AE1-208 GEN
Solar/Wind Harmer
9.3
966841AG1-555 GEN
Solar/Wind Harmer
1.147
958481AF2-142 GEN
Solar/Wind Harmer
15.103
274693ROCKY RD ;1P
Adder
15.856
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.539
274764LEE CO EC;5U
Adder
12.96
926881AC1-175 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
25194408D.CRK1
Adder
9.313
23585401KL_K28_T16
Solar/Wind Helper
1.178
238117U2-030
Solar/Wind Helper
0.267
965051AG1-369 GEN
Solar/Wind Harmer
5.558
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
270284AF1-227 GEN1
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.934
270588AE1-091_GEN
Solar/Wind Harmer
8.236
247642Z2-115 C
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
276806AD2-047 C O1
Solar/Wind Harmer
5.825
274676JOLIET 29;8U
Adder
43.287
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
946031AF1-268 GEN
Solar/Wind Harmer
9.47
959091AF2-200 GEN
Solar/Wind Harmer
19.677
274767LEE CO EC;8U
Adder
12.777
971087AG2-675 GEN
Solar/Wind Harmer
5.012
24728505AND G1
Adder
5.071
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
964991AG1-363 GEN
Solar/Wind Helper
3.522
235058AG1-386 C
Solar/Wind Helper
0.4
970031AG2-029 GEN
Solar/Wind Harmer
5.889
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
972037AH1-567 GEN1
Adder
0.27
960591AF2-350 GEN
Solar/Wind Harmer
10.28
972228AH1-698 GEN2
Adder
5.454
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.4
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
972267AH1-718 GEN
Adder
5.748
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
253406AD2-031_GEN
Solar/Wind Harmer
0.684
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
203955AF1-039 C O1
Solar/Wind Helper
0.331
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
970155AG2-107 GEN
Solar/Wind Harmer
46.922
971995AH1-542 GEN
Solar/Wind Harmer
4.575
965421AG1-410 GEN
Solar/Wind Harmer
33.842
24639705ELKHART HY
Adder
0.237
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
3.072
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
274676JOLIET 29;8U
Adder
44.89
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
957471AF2-041 GEN
Solar/Wind Harmer
29.515
970613AG2-401 GEN
Solar/Wind Harmer
7.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
5.071
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
4.742
270246TR4_N_V150
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
13.426
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
276776AD2-060 GEN
Solar/Wind Harmer
1.097
971613AH1-306 GEN
Solar/Wind Harmer
4.9
253370AE2-315 SEC1
Adder
2.904
247621Y3-024
Adder
0.348
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
957201AF2-014 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.403
970179AG2-119 GEN
Solar/Wind Harmer
9.709
963791AG1-232 GEN
Solar/Wind Harmer
14.514
958391AF2-133 GEN
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.956
274827FISK ;RP
Adder
11.436
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972227AH1-698 GEN1
Adder
3.84
274735ELWOOD EC;4P
Adder
24.024
274744AC1-111 GEN8
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
25306009OHH W.
Adder
4.15
970169AG2-114 GEN
Solar/Wind Harmer
9.859
959341AF2-225 GEN
Solar/Wind Harmer
10.156
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
NYPJM->LTFIMP_NY
CLTF
4.821
TVALTFEXP_TVA->PJM
CLTF
6.29
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
LGEELTFEXP_LGEE->PJM
CLTF
7.242
MECLTFEXP_MEC->PJM
CLTF
20.741
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
SIGELTFEXP_SIGE->PJM
CLTF
0.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
WECLTFEXP_WEC->PJM
CLTF
5.355
LAGNLTFEXP_LAGN->PJM
CLTF
14.301

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
1.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
1.46
Bus #Bus NameTypeMW Contribution
972163AH1-664 GEN
Solar/Wind Harmer
6.737
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
970191AG2-125 GEN
Solar/Wind Harmer
1.303
24379505HDWTR1G C
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
970653AG2-424 GEN
Solar/Wind Harmer
0.382
270518AE2-148 GEN
Solar/Wind Harmer
0.289
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
252507AC2-088 GEN
Solar/Wind Harmer
0.343
25196608WSDLE5
Adder
8.356
958171AF2-111 GEN
Solar/Wind Harmer
16.332
3429391JKCT 9G
Adder
6.006
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
971191AH1-055 GEN
Solar/Wind Harmer
68.884
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.867
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.902
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
972273AH1-721 GEN
Adder
39.663
24803406KYGER 5HP
50/50
4.094
25196808ZIMRHP
Adder
75.812
252510AF1-249 C
Solar/Wind Harmer
0.051
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
270331AC1-082 GEN3
Solar/Wind Helper
0.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25326509SID D
Adder
0.66
942221AE2-234 GEN
Solar/Wind Harmer
1.259
24803506KYGER 5LP
50/50
2.389
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
270543AE2-219 C
Solar/Wind Harmer
2.892
24729505KEY G4
Adder
2.909
24803206KYGER 4HP
50/50
4.085
3429421JKCT 10G
Adder
6.006
970773AG2-487 GEN
Solar/Wind Harmer
0.807
970653AG2-424 GEN
Solar/Wind Harmer
1.845
970091AG2-072 GEN
Adder
37.335
960001AF2-291 GEN
Solar/Wind Helper
1.682
24803006KYGER 3HP
50/50
4.142
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.38
270269AC2-059
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.148
25326109MON D
Adder
0.942
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
944541AF1-119 GEN
Solar/Wind Harmer
0.224
970329AG2-216 GEN
Solar/Wind Harmer
1.4
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
241972AD1-140 GEN
Solar/Wind Harmer
0.472
964611AG1-324 GEN
Solar/Wind Harmer
1.472
971609AH1-304 GEN
Solar/Wind Harmer
0.584
25194408D.CRK1
Adder
7.38
972043AH1-570 GEN
Solar/Wind Harmer
1.433
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
3.278
960971AF2-388 GEN
Solar/Wind Harmer
1.97
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
270273AD2-016 GEN
Solar/Wind Harmer
0.596
25326309TAIT D
Adder
0.805
3429241JKCT 3G
Adder
8.287
270437AC2-090 C
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.004
276903AD2-071 C
Solar/Wind Harmer
3.979
971985AH1-537 GEN
Solar/Wind Harmer
5.716
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
339216AC1-074 GEN
Solar/Wind Harmer
0.154
971029AG2-637 GEN
Solar/Wind Harmer
6.48
247536S-71 GEN
Solar/Wind Harmer
0.158
945581AF1-223 GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
24728505AND G1
Adder
2.173
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970289AG2-191 GEN
Solar/Wind Harmer
0.368
247642Z2-115 C
Solar/Wind Harmer
0.001
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25194608D.CRK4
Adder
1.604
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.761
945681AF1-233 GEN
Solar/Wind Harmer
11.543
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
247621Y3-024
Adder
0.133
971613AH1-306 GEN
Solar/Wind Harmer
1.669
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
NYPJM->LTFIMP_NY
CLTF
1.348
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
SIGELTFEXP_SIGE->PJM
CLTF
0.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509
WECLTFEXP_WEC->PJM
CLTF
1.3
MECLTFEXP_MEC->PJM
CLTF
5.763
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
LGEELTFEXP_LGEE->PJM
CLTF
4.627
TVALTFEXP_TVA->PJM
CLTF
2.571
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
290623 to 242925 ckt Z1
248005 to 242528 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
2.9
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
2.9
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
2.84
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
2.84
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
3.34
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
3.23
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
1.4
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC115.9 %1878.0B2176.69
1.31
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.49 %1878.0B2168.95
1.31
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
2.95
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
2.95
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
3.34
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
3.23
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
2.66
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
1.44
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
1.61

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
2.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
CPLELTFEXP_CPLE->PJM
CLTF
1.222
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
NYPJM->LTFIMP_NY
CLTF
4.529
TVALTFEXP_TVA->PJM
CLTF
6.974
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
WECLTFEXP_WEC->PJM
CLTF
3.411
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
2.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
WECLTFEXP_WEC->PJM
CLTF
3.411
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
NYPJM->LTFIMP_NY
CLTF
4.529
TVALTFEXP_TVA->PJM
CLTF
6.974
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
CPLELTFEXP_CPLE->PJM
CLTF
1.222
SIGELTFEXP_SIGE->PJM
CLTF
0.464

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
2.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
24318805MLG1
50/50
6.319
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LGEELTFEXP_LGEE->PJM
CLTF
6.118
MECLTFEXP_MEC->PJM
CLTF
14.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
WECLTFEXP_WEC->PJM
CLTF
3.339
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
NYPJM->LTFIMP_NY
CLTF
4.411
TVALTFEXP_TVA->PJM
CLTF
6.885
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
CPLELTFEXP_CPLE->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
2.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
24318805MLG1
50/50
6.319
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
CPLELTFEXP_CPLE->PJM
CLTF
1.296
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
NYPJM->LTFIMP_NY
CLTF
4.411
TVALTFEXP_TVA->PJM
CLTF
6.885
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
WECLTFEXP_WEC->PJM
CLTF
3.339
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
LGEELTFEXP_LGEE->PJM
CLTF
6.118
MECLTFEXP_MEC->PJM
CLTF
14.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
3.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
1.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274826FISK ;BP
Adder
5.877
274887GEN-1.85
Solar/Wind Harmer
0.097
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
970781AG2-491 GEN
Solar/Wind Harmer
3.598
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
944531AF1-118 GEN
Solar/Wind Harmer
16.015
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.144
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24728705AND G3
Adder
3.474
23888802TROY G4
50/50
1.525
247620Y3-023
Adder
0.296
965791AG1-447 GEN
Solar/Wind Harmer
3.777
958011AF2-095 GEN
Solar/Wind Harmer
5.377
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.798
958491AF2-143 GEN
Solar/Wind Harmer
5.438
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.116
274765LEE CO EC;6U
Adder
4.704
274763LEE CO EC;4U
Adder
4.649
944541AF1-119 GEN
Solar/Wind Harmer
0.23
270031AE2-169
Solar/Wind Harmer
1.849
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.25
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970885AG2-551 GEN
Solar/Wind Harmer
1.065
270383AD1-128 GEN
Solar/Wind Harmer
0
254304AE2-114 C
Solar/Wind Helper
0.114
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
23856402BAYSG1
50/50
1.575
241858AF1-205_GEN
Solar/Wind Harmer
3.781
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.135
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
939401AE1-172 GEN
Solar/Wind Harmer
2.702
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.123
276903AD2-071 C
Solar/Wind Harmer
3.645
965911AG1-460 GEN
Solar/Wind Harmer
0.643
270437AC2-090 C
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.391
24189802OREGON_CT1
50/50
4.21
944231AF1-091 GEN
Solar/Wind Harmer
11.69
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
6.147
274808UNIV PK N;4U
Adder
2.71
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
274693ROCKY RD ;1P
Adder
5.741
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.284
274764LEE CO EC;5U
Adder
4.704
966841AG1-555 GEN
Solar/Wind Harmer
0.397
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
270599AE1-208 GEN
Solar/Wind Harmer
3.081
276615X2-022 GEN
Solar/Wind Harmer
0.034
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.196
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
241967AE2-285_GEN
Solar/Wind Helper
0.345
254305AE2-115 C
Solar/Wind Helper
0.114
970621AG2-405 GEN
Solar/Wind Harmer
0.945
970623AG2-406 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
274697ROCKY RD ;3P
Adder
1.575
962691AG1-118 GEN
Solar/Wind Harmer
10.839
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274762LEE CO EC;3U
Adder
4.693
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
970241AG2-163 GEN
Solar/Wind Harmer
1.971
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
962101AG1-054 GEN
Solar/Wind Helper
0.331
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965011AG1-365 GEN
Solar/Wind Harmer
4.252
274751CRETE EC ;1U
Adder
4.532
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.781
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
970569AG2-363 GEN
Solar/Wind Harmer
10.659
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
958861AF2-177 GEN
Solar/Wind Harmer
1.481
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
965041AG1-368 GEN
Solar/Wind Harmer
4.372
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274776LINCOLN ;7U
Adder
4.514
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274746AC1-111 G10
Adder
2.931
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.603
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
964611AG1-324 GEN
Solar/Wind Harmer
1.3
944221AF1-090 GEN
Solar/Wind Harmer
1.843
241982AE2-343 S C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.646
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274803UNIV PARK;6U
Adder
3.135
972038AH1-567 GEN2
Adder
0.196
276843GEN-1.7
Solar/Wind Harmer
0.121
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
965931AG1-462 GEN
Solar/Wind Harmer
8.718
270004AE1-209 GEN
Solar/Wind Harmer
0.699
24379505HDWTR1G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.35
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
970031AG2-029 GEN
Solar/Wind Harmer
2.388
965051AG1-369 GEN
Solar/Wind Harmer
2.168
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
972228AH1-698 GEN2
Adder
1.977
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
971411AH1-196 GEN
Solar/Wind Harmer
5.374
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
971029AG2-637 GEN
Solar/Wind Harmer
4.677
203846AF2-130 C
Solar/Wind Helper
0.251
24189902OREGON_CT2
50/50
4.122
23906502RICHG2&3
Adder
1.343
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.722
274676JOLIET 29;8U
Adder
16.29
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
1.011
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241807AE2-176_GEN
Solar/Wind Helper
1.645
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
963791AG1-232 GEN
Solar/Wind Harmer
5.317
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
972227AH1-698 GEN1
Adder
1.392
274735ELWOOD EC;4P
Adder
8.712
274744AC1-111 GEN8
Adder
2.931
970169AG2-114 GEN
Solar/Wind Harmer
3.545
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
959341AF2-225 GEN
Solar/Wind Harmer
3.643
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.132
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
6.847
961971AG1-040 GEN
Solar/Wind Helper
0.342
254303AC2-168 GEN
Solar/Wind Helper
0.077
246938BC-WTG3
Solar/Wind Harmer
0.167
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270043AE2-236 GEN
Solar/Wind Harmer
2.608
274724RIVER EC ;11
Adder
9.665
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274729ELWOOD EC;1P
Adder
8.712
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
970571AG2-364 GEN
Solar/Wind Harmer
7.106
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
971993AH1-541 GEN
Solar/Wind Harmer
1.533
970825AG2-519 GEN
Solar/Wind Harmer
2.443
942481AE2-261 GEN
Solar/Wind Harmer
9.607
270240V3-007_GEN2
Solar/Wind Harmer
0
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
971549AH1-272 GEN
Solar/Wind Harmer
11.979
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
4.384
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270071AF1-092 GEN
Solar/Wind Harmer
7.265
274728ELWOOD EC;5P
Adder
8.713
970073AG2-061 GEN
Solar/Wind Harmer
1.208
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
270543AE2-219 C
Solar/Wind Harmer
2.237
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
23920202STRYCT
50/50
1.928
943021AE2-325 GEN
Solar/Wind Harmer
2.47
970373AG2-245 GEN
Solar/Wind Harmer
8.303
971917AH1-482 GEN
Solar/Wind Harmer
4.962
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.421
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970819AG2-516 GEN
Solar/Wind Harmer
4.255
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
7.998
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
274811UNIV PK N;7U
Adder
2.722
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274676JOLIET 29;8U
Adder
15.708
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274682WAUKEGAN ;7U
Adder
9.362
959091AF2-200 GEN
Solar/Wind Harmer
7.132
274767LEE CO EC;8U
Adder
4.638
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.367
946031AF1-268 GEN
Solar/Wind Harmer
3.094
957381AF2-032 GEN
Solar/Wind Harmer
0.73
24728505AND G1
Adder
1.661
24190002OREGON_ST1
50/50
5.546
270246TR4_N_V150
Solar/Wind Harmer
0.028
965681AG1-436 GEN
Solar/Wind Harmer
5.151
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.398
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276916AD2-100_GEN
Solar/Wind Harmer
6.713
203835AF1-098 GEN
Solar/Wind Helper
1.351
241801AE1-079 GEN
Solar/Wind Helper
0.135
203804AE2-113_GEN
Solar/Wind Helper
0.87
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991177J1571 G
External Queue
15.794994354248047
991182J1586 G
External Queue
28.12165069580078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
CPLELTFEXP_CPLE->PJM
CLTF
0.731
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
NYPJM->LTFIMP_NY
CLTF
1.965
TVALTFEXP_TVA->PJM
CLTF
2.775
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
WECLTFEXP_WEC->PJM
CLTF
1.945
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534
LGEELTFEXP_LGEE->PJM
CLTF
2.4
MECLTFEXP_MEC->PJM
CLTF
7.632
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2176.69
MW Contribution:
1.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.601
270246TR4_N_V150
Solar/Wind Harmer
0.026
965681AG1-436 GEN
Solar/Wind Harmer
4.545
24189802OREGON_CT1
50/50
2.733
944231AF1-091 GEN
Solar/Wind Harmer
11.237
961051AF2-396 GEN
Solar/Wind Harmer
8.281
961051AF2-396 GEN
Solar/Wind Harmer
5.52
270247TR4_N_V136
Solar/Wind Harmer
0.026
24189902OREGON_CT2
50/50
2.676
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
23906502RICHG2&3
Adder
1.422
965421AG1-410 GEN
Solar/Wind Harmer
12.893
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.087
270055AF2-134 C O1
Solar/Wind Harmer
0
23888802TROY G4
50/50
1.834
247620Y3-023
Adder
0.264
965791AG1-447 GEN
Solar/Wind Harmer
3.333
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.432
23856402BAYSG1
50/50
1.431
241858AF1-205_GEN
Solar/Wind Harmer
4.133
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.998
958381AF2-132 GEN
Solar/Wind Harmer
0
23920202STRYCT
50/50
2.05
943021AE2-325 GEN
Solar/Wind Harmer
2.178
970373AG2-245 GEN
Solar/Wind Harmer
7.327
971917AH1-482 GEN
Solar/Wind Harmer
4.378
23867002DVBSG1
50/50
12.651
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
23888702TROY G3
50/50
1.834
972253AH1-711 GEN
50/50
56.063
23860302FRMENG 3
50/50
3.522
241885AC2-103 GEN1
Solar/Wind Harmer
0
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
7.29
957891AF2-083 GEN
Solar/Wind Harmer
6.781
965011AG1-365 GEN
Solar/Wind Harmer
3.892
274751CRETE EC ;1U
Adder
3.998
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.627
246938BC-WTG3
Solar/Wind Harmer
0.156
945111AF1-176 GEN
Solar/Wind Harmer
3.312
270505AE1-170 C O1
Solar/Wind Harmer
4.285
965021AG1-366 GEN
Solar/Wind Harmer
1.297
270043AE2-236 GEN
Solar/Wind Harmer
2.351
274724RIVER EC ;11
Adder
8.524
274772LINCOLN ;3U
Adder
3.98
972259AH1-714 GEN
Adder
8.934
274729ELWOOD EC;1P
Adder
7.678
23888502TROY G1
50/50
1.834
23888602TROY G2
50/50
1.834
23860102FRMENG 1
50/50
1.736
23860202FRMENG 2
50/50
1.736
241886AC2-103 GEN2
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.511
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.876
971567AH1-282 GEN
Solar/Wind Harmer
2.938
270071AF1-092 GEN
Solar/Wind Harmer
6.531
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270588AE1-091_GEN
Solar/Wind Harmer
3.737
24695305TIMB G C
Solar/Wind Harmer
0.357
274811UNIV PK N;7U
Adder
2.4
276806AD2-047 C O1
Solar/Wind Harmer
1.865
274676JOLIET 29;8U
Adder
13.843
270428AC2-015 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.147
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.55
963791AG1-232 GEN
Solar/Wind Harmer
4.856
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.672
274800UNIV PARK;3U
Adder
2.755
274801UNIV PARK;4U
Adder
2.755
23929302BS-PKR
50/50
2.522
958321AF2-126 GEN
Solar/Wind Harmer
1.267
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
274753CRETE EC ;3U
Adder
3.998
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.421
274807UNIV PK N;3U
Adder
2.416
274803UNIV PARK;6U
Adder
2.764
972038AH1-567 GEN2
Adder
0.172
276843GEN-1.7
Solar/Wind Harmer
0.106
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
5.343
270499AE1-146 GEN
Solar/Wind Harmer
0.024
965041AG1-368 GEN
Solar/Wind Harmer
4.077
959331AF2-224 GEN
Solar/Wind Harmer
2.724
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.811
274752CRETE EC ;2U
Adder
3.998
274826FISK ;BP
Adder
5.181
274887GEN-1.85
Solar/Wind Harmer
0.086
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.678
270361_3
Solar/Wind Harmer
5.343
945641AF1-229 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
2.027
970031AG2-029 GEN
Solar/Wind Harmer
2.141
270377AD1-106 GEN
Solar/Wind Harmer
1.42
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.96
960591AF2-350 GEN
Solar/Wind Harmer
3.292
274728ELWOOD EC;5P
Adder
7.678
970073AG2-061 GEN
Solar/Wind Harmer
1.064
24729505KEY G4
Adder
2.953
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
4.997
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.127
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.056
965931AG1-462 GEN
Solar/Wind Harmer
7.656
962511AG1-100 GEN
Solar/Wind Helper
0.367
203854AF2-039 C
Solar/Wind Helper
0.15
970707AG2-453 GEN
Solar/Wind Harmer
10.644
274862TOP CROP ;2U
Solar/Wind Harmer
0.435
944531AF1-118 GEN
Solar/Wind Harmer
14.371
276868AE1-113 GEN
Solar/Wind Harmer
0.635
274879MINONK ;1U
Solar/Wind Harmer
0.133
970781AG2-491 GEN
Solar/Wind Harmer
3.174
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.006
20398826ARMNA MT
Solar/Wind Helper
0.706
274802UNIV PARK;5U
Adder
2.764
274732ELWOOD EC;7P
Adder
7.678
274674JOLIET 9 ;6U
Adder
7.191
939401AE1-172 GEN
Solar/Wind Harmer
2.38
962781AG1-127 GEN
Solar/Wind Harmer
3.022
274766LEE CO EC;7U
Adder
4.078
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.109
203947AF1-006 C
Solar/Wind Helper
0.409
203855AF2-088 C
Solar/Wind Helper
0.072
274812UNIV PK N;8U
Adder
2.4
274676JOLIET 29;8U
Adder
14.356
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.582
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.244
274828WAUKEGAN ;BP
Adder
5.062
957471AF2-041 GEN
Solar/Wind Harmer
9.414
965651AG1-433 GEN
Solar/Wind Harmer
0.906
274848CAMPGROVE;RU
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.348
203979AG1-198 GEN
Solar/Wind Helper
0.209
241966AE1-183 GEN
Solar/Wind Helper
0.139
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.116
274773LINCOLN ;4U
Adder
3.98
274774LINCOLN ;5U
Adder
3.98
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.661
970569AG2-363 GEN
Solar/Wind Harmer
9.379
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.127
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.326
939741AE1-205 GEN
Solar/Wind Harmer
4.273
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
254303AC2-168 GEN
Solar/Wind Helper
0.081
274805UNIV PK N;1U
Adder
2.405
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
970941AG2-585 GEN
Solar/Wind Harmer
1.81
274770LINCOLN ;1U
Adder
3.98
274771LINCOLN ;2U
Adder
3.98
942221AE2-234 GEN
Solar/Wind Harmer
1.321
276897AD1-100 C
Solar/Wind Harmer
8.153
276893AG1-478 C
Solar/Wind Harmer
0.217
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.226
274697ROCKY RD ;3P
Adder
1.387
962691AG1-118 GEN
Solar/Wind Harmer
9.543
938861AE1-114 GEN
Solar/Wind Harmer
1.758
274762LEE CO EC;3U
Adder
4.127
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
25326509SID D
Adder
0.577
942111AE2-223 GEN
Solar/Wind Harmer
0.992
962101AG1-054 GEN
Solar/Wind Helper
0.35
958011AF2-095 GEN
Solar/Wind Harmer
4.74
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.106
958491AF2-143 GEN
Solar/Wind Harmer
4.789
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.982
274765LEE CO EC;6U
Adder
4.137
274763LEE CO EC;4U
Adder
4.088
944541AF1-119 GEN
Solar/Wind Harmer
0.206
970329AG2-216 GEN
Solar/Wind Harmer
1.308
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.655
254304AE2-114 C
Solar/Wind Helper
0.121
940863AE2-074 GEN
Solar/Wind Helper
0.241
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.234
274808UNIV PK N;4U
Adder
2.39
274674JOLIET 9 ;6U
Adder
7.191
958481AF2-142 GEN
Solar/Wind Harmer
4.831
274693ROCKY RD ;1P
Adder
5.056
274683WAUKEGAN ;8U
Adder
9.658
274683WAUKEGAN ;8U
Adder
8.141
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.129
274764LEE CO EC;5U
Adder
4.137
966841AG1-555 GEN
Solar/Wind Harmer
0.35
960971AF2-388 GEN
Solar/Wind Harmer
1.812
960611AF2-352 GEN
Solar/Wind Harmer
1.006
270599AE1-208 GEN
Solar/Wind Harmer
2.759
241967AE2-285_GEN
Solar/Wind Helper
0.363
254305AE2-115 C
Solar/Wind Helper
0.121
274775LINCOLN ;6U
Adder
3.98
274777LINCOLN ;8U
Adder
3.98
972228AH1-698 GEN2
Adder
1.742
274675JOLIET 29;7U
Adder
14.356
274675JOLIET 29;7U
Adder
13.843
970833AG2-524 GEN
Solar/Wind Harmer
3.567
970833AG2-524 GEN
Solar/Wind Harmer
2.378
971411AH1-196 GEN
Solar/Wind Harmer
4.73
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.276
274823ROCKFORD ;21
Adder
8.745
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.835
946321AF1-296 GEN
Solar/Wind Harmer
1.688
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
274776LINCOLN ;7U
Adder
3.98
274687WILL CNTY;4U
Adder
13.101
274687WILL CNTY;4U
Adder
13.101
274731ELWOOD EC;2P
Adder
7.678
274733ELWOOD EC;3P
Adder
7.678
274746AC1-111 G10
Adder
2.582
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.314
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.492
241982AE2-343 S C
Solar/Wind Helper
0.127
20334926Z1-069 C
Solar/Wind Helper
0.691
972227AH1-698 GEN1
Adder
1.227
274735ELWOOD EC;4P
Adder
7.678
274744AC1-111 GEN8
Adder
2.582
970169AG2-114 GEN
Solar/Wind Harmer
3.121
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
959341AF2-225 GEN
Solar/Wind Harmer
3.205
241997AF1-093 GEN
Solar/Wind Helper
0.139
274734ELWOOD EC;8P
Adder
7.678
274736ELWOOD EC;9P
Adder
7.678
943121AE2-341 GEN
Solar/Wind Harmer
5.401
943591AF1-030 GEN
Solar/Wind Harmer
3.592
274682WAUKEGAN ;7U
Adder
8.244
959091AF2-200 GEN
Solar/Wind Harmer
6.276
274767LEE CO EC;8U
Adder
4.078
971087AG2-675 GEN
Solar/Wind Harmer
1.601
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
970571AG2-364 GEN
Solar/Wind Harmer
6.253
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.524
241985AE1-237 GEN
Solar/Wind Helper
0.141
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.523
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.371
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.138
971067AG2-660 GEN
Solar/Wind Harmer
1.046
274822ROCKFORD ;11
Adder
8.809
970819AG2-516 GEN
Solar/Wind Harmer
3.743
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276655WTG1_EQ
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.276
971343AH1-151 GEN
Solar/Wind Harmer
6.276
203835AF1-098 GEN
Solar/Wind Helper
1.417
241801AE1-079 GEN
Solar/Wind Helper
0.142
203804AE2-113_GEN
Solar/Wind Helper
0.929
203853AF1-134 C O1
Solar/Wind Helper
0.22
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.261
CPLELTFEXP_CPLE->PJM
CLTF
0.333
SIGELTFEXP_SIGE->PJM
CLTF
0.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.254
NYPJM->LTFIMP_NY
CLTF
2.163
TVALTFEXP_TVA->PJM
CLTF
2.325
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.219
WECLTFEXP_WEC->PJM
CLTF
1.711
LAGNLTFEXP_LAGN->PJM
CLTF
5.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.932
LGEELTFEXP_LGEE->PJM
CLTF
2.093
MECLTFEXP_MEC->PJM
CLTF
6.675
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.49 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2168.95
MW Contribution:
1.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
274753CRETE EC ;3U
Adder
4.006
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.426
274807UNIV PK N;3U
Adder
2.421
274803UNIV PARK;6U
Adder
2.77
972038AH1-567 GEN2
Adder
0.173
276843GEN-1.7
Solar/Wind Harmer
0.107
24690905MDL-1G C
Solar/Wind Harmer
0
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.814
274752CRETE EC ;2U
Adder
4.006
274826FISK ;BP
Adder
5.192
274887GEN-1.85
Solar/Wind Harmer
0.086
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.667
274730ELWOOD EC;6P
Adder
7.694
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
944531AF1-118 GEN
Solar/Wind Harmer
14.401
276868AE1-113 GEN
Solar/Wind Harmer
0.637
274879MINONK ;1U
Solar/Wind Harmer
0.133
970781AG2-491 GEN
Solar/Wind Harmer
3.181
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.008
20398826ARMNA MT
Solar/Wind Helper
0.705
23856402BAYSG1
50/50
1.432
241858AF1-205_GEN
Solar/Wind Harmer
4.136
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
4.006
958381AF2-132 GEN
Solar/Wind Harmer
0
24189902OREGON_CT2
50/50
2.678
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
23906502RICHG2&3
Adder
1.423
965421AG1-410 GEN
Solar/Wind Harmer
12.914
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.405
274676JOLIET 29;8U
Adder
14.386
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.587
23888702TROY G3
50/50
1.835
972253AH1-711 GEN
50/50
56.096
23860302FRMENG 3
50/50
3.525
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
23867002DVBSG1
50/50
12.657
970621AG2-405 GEN
Solar/Wind Harmer
0.952
970623AG2-406 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
274805UNIV PK N;1U
Adder
2.41
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
970941AG2-585 GEN
Solar/Wind Harmer
1.814
274770LINCOLN ;1U
Adder
3.988
274771LINCOLN ;2U
Adder
3.988
942221AE2-234 GEN
Solar/Wind Harmer
1.323
276897AD1-100 C
Solar/Wind Harmer
8.17
276893AG1-478 C
Solar/Wind Harmer
0.218
274760LEE CO EC;1U
Adder
4.136
23888802TROY G4
50/50
1.835
247620Y3-023
Adder
0.264
965791AG1-447 GEN
Solar/Wind Harmer
3.34
958011AF2-095 GEN
Solar/Wind Harmer
4.75
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.117
958491AF2-143 GEN
Solar/Wind Harmer
4.799
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.984
274765LEE CO EC;6U
Adder
4.146
274763LEE CO EC;4U
Adder
4.097
944541AF1-119 GEN
Solar/Wind Harmer
0.207
970329AG2-216 GEN
Solar/Wind Harmer
1.311
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.659
254304AE2-114 C
Solar/Wind Helper
0.12
940863AE2-074 GEN
Solar/Wind Helper
0.24
946381AF1-302 GEN
Solar/Wind Helper
0.112
203954AE2-126 C
Solar/Wind Helper
0.233
274802UNIV PARK;5U
Adder
2.77
274732ELWOOD EC;7P
Adder
7.694
274674JOLIET 9 ;6U
Adder
7.206
939401AE1-172 GEN
Solar/Wind Harmer
2.385
962781AG1-127 GEN
Solar/Wind Harmer
3.029
274766LEE CO EC;7U
Adder
4.087
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.109
203947AF1-006 C
Solar/Wind Helper
0.409
203855AF2-088 C
Solar/Wind Helper
0.072
24189802OREGON_CT1
50/50
2.734
944231AF1-091 GEN
Solar/Wind Harmer
11.253
961051AF2-396 GEN
Solar/Wind Harmer
8.294
961051AF2-396 GEN
Solar/Wind Harmer
5.529
270247TR4_N_V136
Solar/Wind Harmer
0.026
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.442
274808UNIV PK N;4U
Adder
2.394
274674JOLIET 9 ;6U
Adder
7.206
958481AF2-142 GEN
Solar/Wind Harmer
4.841
274693ROCKY RD ;1P
Adder
5.066
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.132
274764LEE CO EC;5U
Adder
4.146
966841AG1-555 GEN
Solar/Wind Harmer
0.351
960971AF2-388 GEN
Solar/Wind Harmer
1.816
960611AF2-352 GEN
Solar/Wind Harmer
1.008
270599AE1-208 GEN
Solar/Wind Harmer
2.765
241967AE2-285_GEN
Solar/Wind Helper
0.362
254305AE2-115 C
Solar/Wind Helper
0.12
270361_3
Solar/Wind Harmer
5.347
945641AF1-229 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
2.03
970031AG2-029 GEN
Solar/Wind Harmer
2.145
957841AF2-078 GEN
Solar/Wind Harmer
0
274697ROCKY RD ;3P
Adder
1.39
274696ROCKY RD ;4P
Adder
5.238
962691AG1-118 GEN
Solar/Wind Harmer
9.563
938861AE1-114 GEN
Solar/Wind Harmer
1.762
274762LEE CO EC;3U
Adder
4.136
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.497
25326509SID D
Adder
0.579
942111AE2-223 GEN
Solar/Wind Harmer
0.994
962101AG1-054 GEN
Solar/Wind Helper
0.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
7.302
957891AF2-083 GEN
Solar/Wind Harmer
6.792
965011AG1-365 GEN
Solar/Wind Harmer
3.899
274751CRETE EC ;1U
Adder
4.006
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.645
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.124
274773LINCOLN ;4U
Adder
3.988
274774LINCOLN ;5U
Adder
3.988
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.664
970569AG2-363 GEN
Solar/Wind Harmer
9.4
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.136
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.329
939741AE1-205 GEN
Solar/Wind Harmer
4.283
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.613
961971AG1-040 GEN
Solar/Wind Helper
0.358
254303AC2-168 GEN
Solar/Wind Helper
0.081
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
5.347
270499AE1-146 GEN
Solar/Wind Harmer
0.024
965041AG1-368 GEN
Solar/Wind Harmer
4.084
959331AF2-224 GEN
Solar/Wind Harmer
2.729
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274776LINCOLN ;7U
Adder
3.988
274687WILL CNTY;4U
Adder
13.128
274687WILL CNTY;4U
Adder
13.128
274731ELWOOD EC;2P
Adder
7.694
274733ELWOOD EC;3P
Adder
7.694
274746AC1-111 G10
Adder
2.587
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.317
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.493
241982AE2-343 S C
Solar/Wind Helper
0.127
20334926Z1-069 C
Solar/Wind Helper
0.69
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.076
965931AG1-462 GEN
Solar/Wind Harmer
7.674
962511AG1-100 GEN
Solar/Wind Helper
0.366
203854AF2-039 C
Solar/Wind Helper
0.15
270377AD1-106 GEN
Solar/Wind Harmer
1.423
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.964
960591AF2-350 GEN
Solar/Wind Harmer
3.298
274775LINCOLN ;6U
Adder
3.988
274777LINCOLN ;8U
Adder
3.988
972228AH1-698 GEN2
Adder
1.746
274675JOLIET 29;7U
Adder
14.386
274675JOLIET 29;7U
Adder
13.872
970833AG2-524 GEN
Solar/Wind Harmer
3.575
970833AG2-524 GEN
Solar/Wind Harmer
2.383
971411AH1-196 GEN
Solar/Wind Harmer
4.74
971675AH1-338 GEN
Solar/Wind Harmer
1.231
971171AH1-044 GEN
Solar/Wind Harmer
6.289
274823ROCKFORD ;21
Adder
8.764
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.839
946321AF1-296 GEN
Solar/Wind Harmer
1.692
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.262
274828WAUKEGAN ;BP
Adder
5.073
957471AF2-041 GEN
Solar/Wind Harmer
9.434
965651AG1-433 GEN
Solar/Wind Harmer
0.908
274848CAMPGROVE;RU
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.347
203979AG1-198 GEN
Solar/Wind Helper
0.208
241966AE1-183 GEN
Solar/Wind Helper
0.139
270428AC2-015 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.147
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.551
963791AG1-232 GEN
Solar/Wind Harmer
4.865
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.679
274800UNIV PARK;3U
Adder
2.76
274801UNIV PARK;4U
Adder
2.76
972227AH1-698 GEN1
Adder
1.229
274735ELWOOD EC;4P
Adder
7.694
274744AC1-111 GEN8
Adder
2.587
970169AG2-114 GEN
Solar/Wind Harmer
3.128
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
959341AF2-225 GEN
Solar/Wind Harmer
3.212
241997AF1-093 GEN
Solar/Wind Helper
0.139
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270588AE1-091_GEN
Solar/Wind Harmer
3.742
24695305TIMB G C
Solar/Wind Harmer
0.357
246938BC-WTG3
Solar/Wind Harmer
0.157
945111AF1-176 GEN
Solar/Wind Harmer
3.317
270505AE1-170 C O1
Solar/Wind Harmer
4.292
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.355
274724RIVER EC ;11
Adder
8.542
274772LINCOLN ;3U
Adder
3.988
972259AH1-714 GEN
Adder
8.953
274729ELWOOD EC;1P
Adder
7.694
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
970571AG2-364 GEN
Solar/Wind Harmer
6.267
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.534
23888502TROY G1
50/50
1.835
23888602TROY G2
50/50
1.835
23860102FRMENG 1
50/50
1.737
23860202FRMENG 2
50/50
1.737
971549AH1-272 GEN
Solar/Wind Harmer
10.525
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.882
971567AH1-282 GEN
Solar/Wind Harmer
2.943
270071AF1-092 GEN
Solar/Wind Harmer
6.544
274728ELWOOD EC;5P
Adder
7.694
970073AG2-061 GEN
Solar/Wind Harmer
1.066
24729505KEY G4
Adder
2.959
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
5.008
241886AC2-103 GEN2
Solar/Wind Helper
4.613
241985AE1-237 GEN
Solar/Wind Helper
0.141
23920202STRYCT
50/50
2.052
943021AE2-325 GEN
Solar/Wind Harmer
2.181
970373AG2-245 GEN
Solar/Wind Harmer
7.341
971917AH1-482 GEN
Solar/Wind Harmer
4.387
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.524
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.371
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.145
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274822ROCKFORD ;11
Adder
8.828
970819AG2-516 GEN
Solar/Wind Harmer
3.751
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276655WTG1_EQ
Solar/Wind Harmer
0
274811UNIV PK N;7U
Adder
2.405
276806AD2-047 C O1
Solar/Wind Harmer
1.869
274676JOLIET 29;8U
Adder
13.872
274734ELWOOD EC;8P
Adder
7.694
274736ELWOOD EC;9P
Adder
7.694
943121AE2-341 GEN
Solar/Wind Harmer
5.412
943591AF1-030 GEN
Solar/Wind Harmer
3.599
274682WAUKEGAN ;7U
Adder
8.262
959091AF2-200 GEN
Solar/Wind Harmer
6.289
274767LEE CO EC;8U
Adder
4.087
971087AG2-675 GEN
Solar/Wind Harmer
1.605
247642Z2-115 C
Solar/Wind Harmer
0.001
24190002OREGON_ST1
50/50
3.603
270246TR4_N_V150
Solar/Wind Harmer
0.026
965681AG1-436 GEN
Solar/Wind Harmer
4.554
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.352
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.289
971343AH1-151 GEN
Solar/Wind Harmer
6.289
203835AF1-098 GEN
Solar/Wind Helper
1.415
241801AE1-079 GEN
Solar/Wind Helper
0.142
203804AE2-113_GEN
Solar/Wind Helper
0.927
990142J1224
External Queue
13.534384727478027
990527J1329
External Queue
1.8514890670776367
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.063
LGEELTFEXP_LGEE->PJM
CLTF
2.099
MECLTFEXP_MEC->PJM
CLTF
6.691
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.256
WECLTFEXP_WEC->PJM
CLTF
1.715
LAGNLTFEXP_LAGN->PJM
CLTF
5.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.396
NYPJM->LTFIMP_NY
CLTF
2.157
TVALTFEXP_TVA->PJM
CLTF
2.335
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.291
CPLELTFEXP_CPLE->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.175

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270263AC1-001 GEN
Solar/Wind Harmer
0.702
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
945631AF1-228 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.757
961821AG1-024 GEN
Solar/Wind Harmer
4.113
25196508WSDLE4
Adder
8.396
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
972163AH1-664 GEN
Solar/Wind Harmer
7.573
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.711
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270400AC1-102 GEN
Solar/Wind Harmer
2.112
274776LINCOLN ;7U
Adder
8.061
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274746AC1-111 G10
Adder
5.296
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24686405CER G5
Adder
8.833
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.57
970191AG2-125 GEN
Solar/Wind Harmer
1.771
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.475
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.861
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
276843GEN-1.7
Solar/Wind Harmer
0.215
274803UNIV PARK;6U
Adder
5.55
972038AH1-567 GEN2
Adder
0.347
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
965091AG1-374 GEN
Solar/Wind Harmer
19.702
23562501BACKB
Solar/Wind Helper
1.069
238108AE1-109 GEN1
Solar/Wind Helper
0.096
971985AH1-537 GEN
Solar/Wind Harmer
2.118
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270291AC1-194 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
247536S-71 GEN
Solar/Wind Harmer
0.272
972165AH1-665 GEN
Solar/Wind Harmer
6.065
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
12.564
252507AC2-088 GEN
Solar/Wind Harmer
0.312
961921AG1-034 GEN
Solar/Wind Harmer
6.169
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
944531AF1-118 GEN
Solar/Wind Harmer
30.627
958171AF2-111 GEN
Solar/Wind Harmer
16.988
971347AH1-153 GEN
Solar/Wind Harmer
3.374
970781AG2-491 GEN
Solar/Wind Harmer
6.73
24728705AND G3
Adder
7.73
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.861
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
970707AG2-453 GEN
Solar/Wind Harmer
21.689
274730ELWOOD EC;6P
Adder
15.615
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
276868AE1-113 GEN
Solar/Wind Harmer
1.318
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25306009OHH W.
Adder
2.85
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
970289AG2-191 GEN
Solar/Wind Harmer
1.292
963791AG1-232 GEN
Solar/Wind Harmer
9.106
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
972227AH1-698 GEN1
Adder
2.483
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274735ELWOOD EC;4P
Adder
15.615
957201AF2-014 GEN
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
5.296
970169AG2-114 GEN
Solar/Wind Harmer
6.598
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274879MINONK ;1U
Solar/Wind Harmer
0.275
959611AF2-252 GEN
Solar/Wind Harmer
2.189
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
238127S14_GEN_2
Solar/Wind Helper
0.726
270166AC1-044 GEN3
50/50
5.522
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.052
25196808ZIMRHP
Adder
74.904
25196008MFTGT1
Adder
1.367
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
939741AE1-205 GEN
Solar/Wind Harmer
9.213
970569AG2-363 GEN
Solar/Wind Harmer
19.691
23583801GRNGAP
Solar/Wind Helper
4.45
238126S14_GEN_1
Solar/Wind Helper
0.726
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
270186AC1-089 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.324
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
970825AG2-519 GEN
Solar/Wind Harmer
5.122
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
965021AG1-366 GEN
Solar/Wind Harmer
2.244
274772LINCOLN ;3U
Adder
8.061
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
246938BC-WTG3
Solar/Wind Harmer
0.239
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
237048AF1-022 C
Solar/Wind Helper
0.182
238175AF1-290_GEN
Solar/Wind Helper
0.12
270119AB2-067 GEN1
50/50
5.522
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.164
25326509SID D
Adder
1.282
942221AE2-234 GEN
Solar/Wind Harmer
2.725
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.903
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
274696ROCKY RD ;4P
Adder
10.771
274697ROCKY RD ;3P
Adder
2.859
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
970107AG2-081 GEN
Solar/Wind Harmer
1.973
23751201ROTHROCK
Solar/Wind Helper
0.867
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
24691005MDL-2G C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
274728ELWOOD EC;5P
Adder
15.615
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
24289405MTG1
50/50
6.078
970149AG2-104 GEN
Solar/Wind Harmer
17.497
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.164
970091AG2-072 GEN
Adder
75.485
970773AG2-487 GEN
Solar/Wind Harmer
1.2
944971AF1-162 GEN
Solar/Wind Harmer
6.766
971917AH1-482 GEN
Solar/Wind Harmer
8.743
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
941551AE2-152 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
9.18
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
971073AG2-665 GEN
Solar/Wind Harmer
5.121
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
944541AF1-119 GEN
Solar/Wind Harmer
0.456
970329AG2-216 GEN
Solar/Wind Harmer
2.946
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270031AE2-169
Solar/Wind Harmer
3.738
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.14
247620Y3-023
Adder
0.44
972045AH1-571 GEN
Solar/Wind Harmer
1.386
958011AF2-095 GEN
Solar/Wind Harmer
9.564
274695ROCKY RD ;2P
Adder
10.523
958491AF2-143 GEN
Solar/Wind Harmer
9.89
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.875
235531U2-073 GEN
Solar/Wind Helper
2.924
270120AB2-067 GEN2
50/50
5.522
25194408D.CRK1
Adder
7.485
270054AF2-122 C O1
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.003
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
270462AD2-086
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
6.229
24725505WLD G2 C
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
10.122
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
966841AG1-555 GEN
Solar/Wind Harmer
0.761
270247TR4_N_V136
Solar/Wind Harmer
0.043
972043AH1-570 GEN
Solar/Wind Harmer
1.73
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
958481AF2-142 GEN
Solar/Wind Harmer
9.909
274693ROCKY RD ;1P
Adder
10.419
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23585401KL_K28_T16
Solar/Wind Helper
1.41
238117U2-030
Solar/Wind Helper
0.306
962761AG1-125 GEN
Solar/Wind Harmer
32.401
24686505CER G6
Adder
8.903
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.084
270437AC2-090 C
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.58
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.861
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274674JOLIET 9 ;6U
Adder
14.625
939401AE1-172 GEN
Solar/Wind Harmer
4.951
962781AG1-127 GEN
Solar/Wind Harmer
6.263
24386405FR-21G C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
965051AG1-369 GEN
Solar/Wind Harmer
3.331
270399AC1-101 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972037AH1-567 GEN1
Adder
0.174
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
971171AH1-044 GEN
Solar/Wind Harmer
11.056
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252519AF1-045_GEN
Solar/Wind Harmer
3.611
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.696
274811UNIV PK N;7U
Adder
4.772
276806AD2-047 C O1
Solar/Wind Harmer
3.764
24695305TIMB G C
Solar/Wind Harmer
0.562
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274682WAUKEGAN ;7U
Adder
3.428
964991AG1-363 GEN
Solar/Wind Helper
3.896
238110AE1-109 GEN3
Solar/Wind Helper
0.096
959091AF2-200 GEN
Solar/Wind Harmer
11.056
243186AF1-051 GEN
50/50
6.83
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
252516AE2-318_GEN
Solar/Wind Harmer
7.753
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
965651AG1-433 GEN
Solar/Wind Harmer
2.002
970613AG2-401 GEN
Solar/Wind Harmer
5
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.147
274812UNIV PK N;8U
Adder
4.772
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274676JOLIET 29;8U
Adder
29.146
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
1.983
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.373
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
276776AD2-060 GEN
Solar/Wind Harmer
0.708
276901AD2-066 C O1
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.63
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
CPLELTFEXP_CPLE->PJM
CLTF
2.151
SIGELTFEXP_SIGE->PJM
CLTF
0.488
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
NYPJM->LTFIMP_NY
CLTF
4.02
TVALTFEXP_TVA->PJM
CLTF
7.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
WECLTFEXP_WEC->PJM
CLTF
3.585
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LGEELTFEXP_LGEE->PJM
CLTF
6.53
MECLTFEXP_MEC->PJM
CLTF
15.181
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
2.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270263AC1-001 GEN
Solar/Wind Harmer
0.702
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
945631AF1-228 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.757
961821AG1-024 GEN
Solar/Wind Harmer
4.113
25196508WSDLE4
Adder
8.396
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
972163AH1-664 GEN
Solar/Wind Harmer
7.573
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.711
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270400AC1-102 GEN
Solar/Wind Harmer
2.112
274776LINCOLN ;7U
Adder
8.061
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274746AC1-111 G10
Adder
5.296
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24686405CER G5
Adder
8.833
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.57
970191AG2-125 GEN
Solar/Wind Harmer
1.771
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.475
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.861
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
276843GEN-1.7
Solar/Wind Harmer
0.215
274803UNIV PARK;6U
Adder
5.55
972038AH1-567 GEN2
Adder
0.347
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
965091AG1-374 GEN
Solar/Wind Harmer
19.702
23562501BACKB
Solar/Wind Helper
1.069
238108AE1-109 GEN1
Solar/Wind Helper
0.096
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25306009OHH W.
Adder
2.85
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
970289AG2-191 GEN
Solar/Wind Harmer
1.292
963791AG1-232 GEN
Solar/Wind Harmer
9.106
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
12.564
252507AC2-088 GEN
Solar/Wind Harmer
0.312
961921AG1-034 GEN
Solar/Wind Harmer
6.169
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
944531AF1-118 GEN
Solar/Wind Harmer
30.627
958171AF2-111 GEN
Solar/Wind Harmer
16.988
971347AH1-153 GEN
Solar/Wind Harmer
3.374
970781AG2-491 GEN
Solar/Wind Harmer
6.73
24728705AND G3
Adder
7.73
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.861
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
970707AG2-453 GEN
Solar/Wind Harmer
21.689
274730ELWOOD EC;6P
Adder
15.615
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
959611AF2-252 GEN
Solar/Wind Harmer
2.189
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
238127S14_GEN_2
Solar/Wind Helper
0.726
270166AC1-044 GEN3
50/50
5.522
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.052
25196808ZIMRHP
Adder
74.904
25196008MFTGT1
Adder
1.367
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
940581AE2-045 GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
270186AC1-089 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.324
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
970825AG2-519 GEN
Solar/Wind Harmer
5.122
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
965021AG1-366 GEN
Solar/Wind Harmer
2.244
274772LINCOLN ;3U
Adder
8.061
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
246938BC-WTG3
Solar/Wind Harmer
0.239
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
237048AF1-022 C
Solar/Wind Helper
0.182
238175AF1-290_GEN
Solar/Wind Helper
0.12
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
939741AE1-205 GEN
Solar/Wind Harmer
9.213
970569AG2-363 GEN
Solar/Wind Harmer
19.691
23583801GRNGAP
Solar/Wind Helper
4.45
238126S14_GEN_1
Solar/Wind Helper
0.726
270119AB2-067 GEN1
50/50
5.522
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.164
25326509SID D
Adder
1.282
942221AE2-234 GEN
Solar/Wind Harmer
2.725
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.903
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
274696ROCKY RD ;4P
Adder
10.771
274697ROCKY RD ;3P
Adder
2.859
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
970107AG2-081 GEN
Solar/Wind Harmer
1.973
23751201ROTHROCK
Solar/Wind Helper
0.867
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
24691005MDL-2G C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
274728ELWOOD EC;5P
Adder
15.615
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
24289405MTG1
50/50
6.078
970149AG2-104 GEN
Solar/Wind Harmer
17.497
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.164
970091AG2-072 GEN
Adder
75.485
970773AG2-487 GEN
Solar/Wind Harmer
1.2
944971AF1-162 GEN
Solar/Wind Harmer
6.766
971917AH1-482 GEN
Solar/Wind Harmer
8.743
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
941551AE2-152 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
9.18
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
971073AG2-665 GEN
Solar/Wind Harmer
5.121
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
944541AF1-119 GEN
Solar/Wind Harmer
0.456
970329AG2-216 GEN
Solar/Wind Harmer
2.946
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270031AE2-169
Solar/Wind Harmer
3.738
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.14
247620Y3-023
Adder
0.44
972045AH1-571 GEN
Solar/Wind Harmer
1.386
958011AF2-095 GEN
Solar/Wind Harmer
9.564
274695ROCKY RD ;2P
Adder
10.523
958491AF2-143 GEN
Solar/Wind Harmer
9.89
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.875
235531U2-073 GEN
Solar/Wind Helper
2.924
270120AB2-067 GEN2
50/50
5.522
25194408D.CRK1
Adder
7.485
270054AF2-122 C O1
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
4.003
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
270462AD2-086
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
6.229
24725505WLD G2 C
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
10.122
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
966841AG1-555 GEN
Solar/Wind Harmer
0.761
270247TR4_N_V136
Solar/Wind Harmer
0.043
972043AH1-570 GEN
Solar/Wind Harmer
1.73
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
958481AF2-142 GEN
Solar/Wind Harmer
9.909
274693ROCKY RD ;1P
Adder
10.419
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23585401KL_K28_T16
Solar/Wind Helper
1.41
238117U2-030
Solar/Wind Helper
0.306
962761AG1-125 GEN
Solar/Wind Harmer
32.401
24686505CER G6
Adder
8.903
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.084
270437AC2-090 C
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.58
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.861
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274674JOLIET 9 ;6U
Adder
14.625
939401AE1-172 GEN
Solar/Wind Harmer
4.951
962781AG1-127 GEN
Solar/Wind Harmer
6.263
971985AH1-537 GEN
Solar/Wind Harmer
2.118
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270291AC1-194 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
247536S-71 GEN
Solar/Wind Harmer
0.272
972165AH1-665 GEN
Solar/Wind Harmer
6.065
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
965051AG1-369 GEN
Solar/Wind Harmer
3.331
270399AC1-101 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972037AH1-567 GEN1
Adder
0.174
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
971171AH1-044 GEN
Solar/Wind Harmer
11.056
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252519AF1-045_GEN
Solar/Wind Harmer
3.611
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.696
274811UNIV PK N;7U
Adder
4.772
276806AD2-047 C O1
Solar/Wind Harmer
3.764
24695305TIMB G C
Solar/Wind Harmer
0.562
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274682WAUKEGAN ;7U
Adder
3.428
964991AG1-363 GEN
Solar/Wind Helper
3.896
238110AE1-109 GEN3
Solar/Wind Helper
0.096
959091AF2-200 GEN
Solar/Wind Harmer
11.056
243186AF1-051 GEN
50/50
6.83
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
252516AE2-318_GEN
Solar/Wind Harmer
7.753
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
965651AG1-433 GEN
Solar/Wind Harmer
2.002
970613AG2-401 GEN
Solar/Wind Harmer
5
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.147
274812UNIV PK N;8U
Adder
4.772
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274676JOLIET 29;8U
Adder
29.146
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
1.983
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.373
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
276776AD2-060 GEN
Solar/Wind Harmer
0.708
276901AD2-066 C O1
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.63
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
247521TR3_G114
Solar/Wind Harmer
0.242
972227AH1-698 GEN1
Adder
2.483
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274735ELWOOD EC;4P
Adder
15.615
957201AF2-014 GEN
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
5.296
970169AG2-114 GEN
Solar/Wind Harmer
6.598
959341AF2-225 GEN
Solar/Wind Harmer
6.91
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
LGEELTFEXP_LGEE->PJM
CLTF
6.53
MECLTFEXP_MEC->PJM
CLTF
15.181
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
WECLTFEXP_WEC->PJM
CLTF
3.585
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
NYPJM->LTFIMP_NY
CLTF
4.02
TVALTFEXP_TVA->PJM
CLTF
7.601
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
CPLELTFEXP_CPLE->PJM
CLTF
2.151
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
3.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
957471AF2-041 GEN
Solar/Wind Harmer
13.123
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
2.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971347AH1-153 GEN
Solar/Wind Harmer
5.221
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
44.69
274752CRETE EC ;2U
Adder
11.245
970707AG2-453 GEN
Solar/Wind Harmer
30.807
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.94
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
247620Y3-023
50/50
0.701
270101X2-052 CT2
50/50
2.104
965791AG1-447 GEN
Solar/Wind Harmer
9.061
958011AF2-095 GEN
Solar/Wind Harmer
13.543
944541AF1-119 GEN
Solar/Wind Harmer
0.62
274695ROCKY RD ;2P
Adder
14.592
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.785
945421AF1-207 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
11.687
274763LEE CO EC;4U
Adder
11.55
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.65
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.277
24643105BUCHANAN
50/50
0.018
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.061
274808UNIV PK N;4U
Adder
6.766
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270100X2-052 CT1
50/50
2.104
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
274805UNIV PK N;1U
Adder
6.81
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
276893AG1-478 C
Solar/Wind Harmer
0.621
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
962691AG1-118 GEN
Solar/Wind Harmer
27.25
247607V1-011 GEN
Solar/Wind Harmer
0
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274776LINCOLN ;7U
Adder
11.612
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274746AC1-111 G10
Adder
7.404
926823AC1-168 GEN
Solar/Wind Harmer
1.499
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.381
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
944221AF1-090 GEN
Solar/Wind Harmer
4.314
270356AE2-297 GEN
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.483
24642205MAYFLWER
50/50
0.053
962601AG1-109 GEN
50/50
4.124
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274803UNIV PARK;6U
Adder
7.869
276843GEN-1.7
Solar/Wind Harmer
0.304
972038AH1-567 GEN2
Adder
0.492
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.659
24690905MDL-1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
965931AG1-462 GEN
Solar/Wind Harmer
21.395
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.752
24379505HDWTR1G C
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
970031AG2-029 GEN
Solar/Wind Harmer
5.461
274775LINCOLN ;6U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
965051AG1-369 GEN
Solar/Wind Harmer
4.782
972037AH1-567 GEN1
Adder
0.247
960591AF2-350 GEN
Solar/Wind Harmer
9.405
972228AH1-698 GEN2
Adder
4.989
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
971611AH1-305 GEN
Solar/Wind Harmer
5.334
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
945581AF1-223 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.171
946321AF1-296 GEN
Solar/Wind Harmer
4.723
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
971029AG2-637 GEN
Solar/Wind Harmer
10.609
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.8
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
270541AE2-072 C
Solar/Wind Harmer
0
24721805FLATG3
50/50
4.711
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
247521TR3_G114
Solar/Wind Harmer
0.347
963791AG1-232 GEN
Solar/Wind Harmer
12.72
274827FISK ;RP
Adder
10.469
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
21.939
274744AC1-111 GEN8
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.815
276741O09 GEN1
Solar/Wind Harmer
0.306
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
959341AF2-225 GEN
Solar/Wind Harmer
8.961
970289AG2-191 GEN
Solar/Wind Harmer
1.58
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274693ROCKY RD ;1P
Adder
14.449
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
274764LEE CO EC;5U
Adder
11.687
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
966841AG1-555 GEN
Solar/Wind Harmer
0.946
24725505WLD G2 C
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.081
24307105BERRINSP G
50/50
0.03
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.956
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
970825AG2-519 GEN
Solar/Wind Harmer
2.836
276621W2-048 GEN
Solar/Wind Harmer
0.393
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
4.124
270043AE2-236 GEN
Solar/Wind Harmer
6.765
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
10.472
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
274729ELWOOD EC;1P
Adder
21.939
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
970571AG2-364 GEN
Solar/Wind Harmer
17.631
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
942481AE2-261 GEN
Solar/Wind Harmer
22.758
270240V3-007_GEN2
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274762LEE CO EC;3U
Adder
11.659
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
942111AE2-223 GEN
Solar/Wind Harmer
2.774
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
276838X2-022 GEN2
Solar/Wind Harmer
0.442
25326509SID D
Adder
1.142
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
19.599
971771AH1-392 GEN
Solar/Wind Harmer
10.022
24729505KEY G4
Adder
9.105
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274728ELWOOD EC;5P
Adder
21.94
971549AH1-272 GEN
Solar/Wind Harmer
19.166
970073AG2-061 GEN
Solar/Wind Harmer
3.016
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
971681AH1-341 GEN
Solar/Wind Harmer
14.132
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.181
24344105CKG2
50/50
11.483
970149AG2-104 GEN
Solar/Wind Harmer
59.152
943021AE2-325 GEN
Solar/Wind Harmer
5.166
970373AG2-245 GEN
Solar/Wind Harmer
19.884
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.848
970773AG2-487 GEN
Solar/Wind Harmer
1.192
24728805RICHG1
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.401
945391AF1-204 GEN
Solar/Wind Harmer
7.788
24728905RICHG2
Adder
3.35
962761AG1-125 GEN
Solar/Wind Harmer
109.537
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274754CRETE EC ;4U
Adder
11.245
274802UNIV PARK;5U
Adder
7.869
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.936
965911AG1-460 GEN
Solar/Wind Harmer
1.522
270437AC2-090 C
Solar/Wind Harmer
0
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270142AC1-141 CT1_
50/50
3.456
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
6.795
24695305TIMB G C
Solar/Wind Harmer
0.797
276806AD2-047 C O1
Solar/Wind Harmer
5.33
274676JOLIET 29;8U
Adder
39.574
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
274682WAUKEGAN ;7U
Adder
23.522
959091AF2-200 GEN
Solar/Wind Harmer
17.823
274767LEE CO EC;8U
Adder
11.522
247642Z2-115 C
Solar/Wind Harmer
0.003
971087AG2-675 GEN
Solar/Wind Harmer
4.475
970289AG2-191 GEN
Solar/Wind Harmer
0.915
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
24728505AND G1
Adder
3.831
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
970155AG2-107 GEN
Solar/Wind Harmer
69.947
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.412
274812UNIV PK N;8U
Adder
6.795
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
274828WAUKEGAN ;BP
Adder
14.44
957471AF2-041 GEN
Solar/Wind Harmer
26.735
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
23906502RICHG2&3
Adder
1.11
24721705FLATG2
50/50
69.962
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.356
270246TR4_N_V150
Solar/Wind Harmer
0.061
276776AD2-060 GEN
Solar/Wind Harmer
1.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
247621Y3-024
Adder
0.272
276916AD2-100_GEN
Solar/Wind Harmer
15.862
971587AH1-292 GEN
Solar/Wind Harmer
4.757
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
LGEELTFEXP_LGEE->PJM
CLTF
4.556
MECLTFEXP_MEC->PJM
CLTF
18.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
WECLTFEXP_WEC->PJM
CLTF
4.845
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
NYPJM->LTFIMP_NY
CLTF
3.074
TVALTFEXP_TVA->PJM
CLTF
4.815
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
1.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
971125AH1-004 GEN
Solar/Wind Harmer
2.245
253370AE2-315 SEC1
Adder
1.601
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
247621Y3-024
Adder
0.162
971613AH1-306 GEN
Solar/Wind Harmer
2.151
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
971587AH1-292 GEN
Solar/Wind Harmer
2.993
276916AD2-100_GEN
Solar/Wind Harmer
7.7
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.377
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
965681AG1-436 GEN
Solar/Wind Harmer
4.361
270246TR4_N_V150
Solar/Wind Harmer
0.019
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25194608D.CRK4
Adder
1.689
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
945681AF1-233 GEN
Solar/Wind Harmer
12.031
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970613AG2-401 GEN
Solar/Wind Harmer
3.76
24728605AND G2
Adder
2.628
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.594
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274745AC1-111 GEN9
Adder
2.817
957471AF2-041 GEN
Solar/Wind Harmer
10.473
270449AD2-020 GEN
Solar/Wind Harmer
0
24803206KYGER 4HP
50/50
4.079
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
963741AG1-226 GEN
Solar/Wind Harmer
9.274
971917AH1-482 GEN
Solar/Wind Harmer
4.756
276655WTG1_EQ
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
970819AG2-516 GEN
Solar/Wind Harmer
4.177
943021AE2-325 GEN
Solar/Wind Harmer
1.73
960001AF2-291 GEN
Solar/Wind Helper
1.722
24803406KYGER 5HP
50/50
4.083
25196808ZIMRHP
Adder
79.38
252510AF1-249 C
Solar/Wind Harmer
0.054
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.04
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
965011AG1-365 GEN
Solar/Wind Harmer
3.232
270331AC1-082 GEN3
Solar/Wind Helper
0.193
24803506KYGER 5LP
50/50
2.38
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
270543AE2-219 C
Solar/Wind Harmer
3.433
24729505KEY G4
Adder
3.899
24691005MDL-2G C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
7.11
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
8.311
970073AG2-061 GEN
Solar/Wind Harmer
1.175
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
971771AH1-392 GEN
Solar/Wind Harmer
3.411
971549AH1-272 GEN
Solar/Wind Harmer
6.245
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
970289AG2-191 GEN
Solar/Wind Harmer
0.834
270273AD2-016 GEN
Solar/Wind Harmer
0.594
25326309TAIT D
Adder
0.844
3429241JKCT 3G
Adder
8.835
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
253333AC1-068 GEN
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.732
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.672
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
274802UNIV PARK;5U
Adder
2.945
274754CRETE EC ;4U
Adder
4.155
962781AG1-127 GEN
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
0.123
235780M24_1
Solar/Wind Helper
0.496
970191AG2-125 GEN
Solar/Wind Harmer
1.385
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.04
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970653AG2-424 GEN
Solar/Wind Harmer
0.428
253325AC1-069 GEN
Solar/Wind Harmer
0.005
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.304
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
10.891
276843GEN-1.7
Solar/Wind Harmer
0.114
972038AH1-567 GEN2
Adder
0.184
274803UNIV PARK;6U
Adder
2.945
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274753CRETE EC ;3U
Adder
4.155
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
965931AG1-462 GEN
Solar/Wind Harmer
8.801
270329AC1-082 GEN1
Solar/Wind Helper
0.194
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.684
942221AE2-234 GEN
Solar/Wind Harmer
1.655
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
942111AE2-223 GEN
Solar/Wind Harmer
1.178
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274696ROCKY RD ;4P
Adder
5.728
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
971191AH1-055 GEN
Solar/Wind Harmer
68.684
25196008MFTGT1
Adder
1.326
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
972273AH1-721 GEN
Adder
43.369
274772LINCOLN ;3U
Adder
4.277
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
270043AE2-236 GEN
Solar/Wind Harmer
2.263
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274724RIVER EC ;11
Adder
8.935
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
972227AH1-698 GEN1
Adder
1.321
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
274827FISK ;RP
Adder
3.918
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
276741O09 GEN1
Solar/Wind Harmer
0.123
247521TR3_G114
Solar/Wind Harmer
0.11
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
957381AF2-032 GEN
Solar/Wind Harmer
0.83
276806AD2-047 C O1
Solar/Wind Harmer
2.001
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
274676JOLIET 29;8U
Adder
14.935
274811UNIV PK N;7U
Adder
2.528
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971087AG2-675 GEN
Solar/Wind Harmer
1.841
25196508WSDLE4
Adder
8.708
972163AH1-664 GEN
Solar/Wind Harmer
7.027
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
964611AG1-324 GEN
Solar/Wind Harmer
1.811
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
963841AG1-237 GEN
Solar/Wind Harmer
1.68
946581AF1-322 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274746AC1-111 G10
Adder
2.817
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
945631AF1-228 GEN
Solar/Wind Harmer
0
24803006KYGER 3HP
50/50
4.127
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.452
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
24728805RICHG1
Adder
2.955
25326109MON D
Adder
0.984
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.635
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
964571AG1-320 GEN
Solar/Wind Harmer
4.079
944541AF1-119 GEN
Solar/Wind Harmer
0.292
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.507
958011AF2-095 GEN
Solar/Wind Harmer
5.084
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
5.287
274695ROCKY RD ;2P
Adder
5.596
965791AG1-447 GEN
Solar/Wind Harmer
3.198
970329AG2-216 GEN
Solar/Wind Harmer
1.444
966021AG1-471 GEN
Solar/Wind Harmer
1.739
971985AH1-537 GEN
Solar/Wind Harmer
5.763
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
971029AG2-637 GEN
Solar/Wind Harmer
7.57
247536S-71 GEN
Solar/Wind Harmer
0.191
945581AF1-223 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
972228AH1-698 GEN2
Adder
1.875
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
972037AH1-567 GEN1
Adder
0.092
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
946321AF1-296 GEN
Solar/Wind Harmer
1.935
970031AG2-029 GEN
Solar/Wind Harmer
1.822
965051AG1-369 GEN
Solar/Wind Harmer
1.514
25194408D.CRK1
Adder
7.768
972043AH1-570 GEN
Solar/Wind Harmer
1.516
24728905RICHG2
Adder
2.955
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
970883AG2-550 GEN
Solar/Wind Harmer
4.905
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
4.141
960971AF2-388 GEN
Solar/Wind Harmer
2.564
945391AF1-204 GEN
Solar/Wind Harmer
4.316
966841AG1-555 GEN
Solar/Wind Harmer
0.434
24697605MDL-3G C
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.038
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274674JOLIET 9 ;6U
Adder
7.779
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
274808UNIV PK N;4U
Adder
2.517
274693ROCKY RD ;1P
Adder
5.541
964781AG1-341 GEN
Solar/Wind Harmer
3.705
970349AG2-230 GEN
Solar/Wind Harmer
5.234
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
252507AC2-088 GEN
Solar/Wind Harmer
0.357
25196608WSDLE5
Adder
8.798
958171AF2-111 GEN
Solar/Wind Harmer
17.024
3429391JKCT 9G
Adder
6.396
24728705AND G3
Adder
5.496
944531AF1-118 GEN
Solar/Wind Harmer
18.504
970193AG2-126 GEN
Solar/Wind Harmer
6.094
970781AG2-491 GEN
Solar/Wind Harmer
3.775
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.092
274730ELWOOD EC;6P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274752CRETE EC ;2U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270330AC1-082 GEN2
Solar/Wind Helper
0.194
NYPJM->LTFIMP_NY
CLTF
1.666
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
LGEELTFEXP_LGEE->PJM
CLTF
5.14
TVALTFEXP_TVA->PJM
CLTF
3.106
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
WECLTFEXP_WEC->PJM
CLTF
1.904
MECLTFEXP_MEC->PJM
CLTF
8.009
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
1.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
247621Y3-024
Adder
0.156
971613AH1-306 GEN
Solar/Wind Harmer
2.045
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
276916AD2-100_GEN
Solar/Wind Harmer
7.149
270535AF1-215 GEN1
Solar/Wind Harmer
0
24803506KYGER 5LP
50/50
2.41
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
270543AE2-219 C
Solar/Wind Harmer
3.362
24729505KEY G4
Adder
3.463
24691005MDL-2G C
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
6.13
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.026
274728ELWOOD EC;5P
Adder
7.204
971681AH1-341 GEN
Solar/Wind Harmer
4.906
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
24803206KYGER 4HP
50/50
4.13
3429421JKCT 10G
Adder
6.589
970773AG2-487 GEN
Solar/Wind Harmer
0.935
970091AG2-072 GEN
Adder
49.338
970653AG2-424 GEN
Solar/Wind Harmer
2.069
963741AG1-226 GEN
Solar/Wind Harmer
8.794
971917AH1-482 GEN
Solar/Wind Harmer
4.274
276655WTG1_EQ
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
276882AE2-255 GEN
Solar/Wind Harmer
0.36
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.47
24379505HDWTR1G C
Solar/Wind Harmer
0
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276843GEN-1.7
Solar/Wind Harmer
0.099
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
252507AC2-088 GEN
Solar/Wind Harmer
0.376
25196608WSDLE5
Adder
9.253
958171AF2-111 GEN
Solar/Wind Harmer
17.947
3429391JKCT 9G
Adder
6.589
24728705AND G3
Adder
5.404
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
970781AG2-491 GEN
Solar/Wind Harmer
3.495
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274730ELWOOD EC;6P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274857EASY ROAD;U1
Solar/Wind Harmer
0
274826FISK ;BP
Adder
4.777
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270273AD2-016 GEN
Solar/Wind Harmer
0.667
25326309TAIT D
Adder
0.906
3429241JKCT 3G
Adder
9.074
270437AC2-090 C
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.005
276903AD2-071 C
Solar/Wind Harmer
4.853
24385905FR-11G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.347
276708O09 GEN2
Solar/Wind Harmer
0.108
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274802UNIV PARK;5U
Adder
2.546
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
235780M24_1
Solar/Wind Helper
0.501
24802606KYGER 1HP
50/50
4.207
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25194608D.CRK4
Adder
1.776
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
945681AF1-233 GEN
Solar/Wind Harmer
12.627
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
270055AF2-134 C O1
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
13.407
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
24803406KYGER 5HP
50/50
4.134
25196808ZIMRHP
Adder
83.622
252510AF1-249 C
Solar/Wind Harmer
0.057
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276805AD2-038 GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
270331AC1-082 GEN3
Solar/Wind Helper
0.186
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25326509SID D
Adder
0.755
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942111AE2-223 GEN
Solar/Wind Harmer
1.058
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
276897AD1-100 C
Solar/Wind Harmer
7.68
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
970941AG2-585 GEN
Solar/Wind Harmer
1.679
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274762LEE CO EC;3U
Adder
4.061
274696ROCKY RD ;4P
Adder
4.974
274697ROCKY RD ;3P
Adder
1.32
24803006KYGER 3HP
50/50
4.179
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.262
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
1.601
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.337
944541AF1-119 GEN
Solar/Wind Harmer
0.265
970329AG2-216 GEN
Solar/Wind Harmer
1.606
270180AB1-006 GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
0.471
942861AE2-305 GEN
Solar/Wind Harmer
2.579
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274765LEE CO EC;6U
Adder
4.07
274763LEE CO EC;4U
Adder
4.023
274695ROCKY RD ;2P
Adder
4.859
972236AH1-702 GEN2
Adder
0.956
25196508WSDLE4
Adder
9.159
972163AH1-664 GEN
Solar/Wind Harmer
7.368
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
241972AD1-140 GEN
Solar/Wind Harmer
0.535
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.529
25194408D.CRK1
Adder
8.168
972043AH1-570 GEN
Solar/Wind Harmer
1.575
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
24725505WLD G2 C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
3.895
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
966841AG1-555 GEN
Solar/Wind Harmer
0.406
24697605MDL-3G C
Solar/Wind Harmer
0
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
960611AF2-352 GEN
Solar/Wind Harmer
1.092
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
4.605
274674JOLIET 9 ;6U
Adder
6.739
274764LEE CO EC;5U
Adder
4.07
274693ROCKY RD ;1P
Adder
4.811
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
237033AB1-150 GEN
Solar/Wind Helper
0.404
971985AH1-537 GEN
Solar/Wind Harmer
5.9
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972165AH1-665 GEN
Solar/Wind Harmer
5.901
339216AC1-074 GEN
Solar/Wind Harmer
0.169
971029AG2-637 GEN
Solar/Wind Harmer
7.492
247536S-71 GEN
Solar/Wind Harmer
0.185
945581AF1-223 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.005
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
971411AH1-196 GEN
Solar/Wind Harmer
4.564
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274746AC1-111 G10
Adder
2.441
24802706KYGER 1LP
50/50
2.467
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
4.554
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
959341AF2-225 GEN
Solar/Wind Harmer
3.418
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
276741O09 GEN1
Solar/Wind Harmer
0.108
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
274744AC1-111 GEN8
Adder
2.441
274827FISK ;RP
Adder
3.386
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
24728505AND G1
Adder
2.584
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
957381AF2-032 GEN
Solar/Wind Harmer
0.768
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
276806AD2-047 C O1
Solar/Wind Harmer
1.73
274676JOLIET 29;8U
Adder
12.928
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
971191AH1-055 GEN
Solar/Wind Harmer
70.432
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
972273AH1-721 GEN
Adder
42.335
942481AE2-261 GEN
Solar/Wind Harmer
10.146
971993AH1-541 GEN
Solar/Wind Harmer
1.554
970571AG2-364 GEN
Solar/Wind Harmer
6.202
274729ELWOOD EC;1P
Adder
7.204
972259AH1-714 GEN
Adder
8.342
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270536AF1-215 GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.326
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
WECLTFEXP_WEC->PJM
CLTF
1.662
MECLTFEXP_MEC->PJM
CLTF
7.137
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
LGEELTFEXP_LGEE->PJM
CLTF
5.305
TVALTFEXP_TVA->PJM
CLTF
2.665
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
NYPJM->LTFIMP_NY
CLTF
1.597
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
SIGELTFEXP_SIGE->PJM
CLTF
0.33
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
239289 to 238569 ckt 1
242920 to 235102 ckt 5
242925 to 235117 ckt 1
242926 to 246751 ckt 1
248005 to 242528 ckt 1

Winter Peak Analysis

The New Service Request AG2-216 was evaluated as a 0.0 MW (25.92 MW Capacity) injection in the Dayton area.

AG2-216 was evaluated as part of a plant. The plant consists of AG2-216. The total Energy output of the plant was evaluated at its maximum seasonal capability of 144.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-216 was evaluated as a 0.0 MW injection

AG2-216 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 144.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Not Required

PJM has reviewed this project submission and determined that a stability study is not required as this is a CIR only increase with no changes to equipment/electrical parameters (no change to MFO).

Reactive Power Analysis

Not Required

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements based on the project Agreements per PJM’s Tariff, Part IX, Subpart B, App. 2, section 4.6.1.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-111Aurora 138kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-214Crescent RidgeIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-068Jay 138 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-216 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-216 could receive cost allocation. Although AG2-216 may not presently have cost responsibility for this upgrade, AG2-216 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-216 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-216 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-216 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-216 could receive cost allocation. Although AG2-216 may not presently have cost responsibility for this upgrade, AG2-216 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-216 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-216 could receive cost allocation. Although AG2-216 may not presently have cost responsibility for this upgrade, AG2-216 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-216


AG2-216 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-216 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.