AG2-272 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:36

Berry Hill 138 kV

21.3 MW Capacity / 55.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Tupelo Storage, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Appalachian Power Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $5,906,901 $4,700,651 = 1.26 AND ( $5,906,901 - $4,700,651 ) 55.0 = $21,932 per MW

General

The Project Developer has proposed a Storage facility located in the Appalachian Power Company zone — Pittsylvania County, Virginia. The installed facilities will have a total capability of 55.0 MW with 21.3 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-272
Project Name:
Berry Hill 138 kV
Project Developer Name:
Tupelo Storage, LLC
State:
Virginia
County:
Pittsylvania
Transmission Owner:
Appalachian Power Company
MFO:
55.0
MWE:
55.0
MWC:
21.3
Battery Storage Specification:
220.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-272 will interconnect on the American Electric Power  transmission system at the Berry Hill 138 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-272 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-272Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$986,167$0$0
Other Scope$750,157$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$507,722$507,722$507,722
Network Upgrades$5,399,179$5,399,179$5,399,179
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$7,643,225$5,906,901$5,906,901

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-272

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-272
Project ID: AG2-272
20% of cost allocation for Phase II Network Upgrades:(A) $1,181,380
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $470,065
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $711,315
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

APCO will tie the proposed AG2-272 138 kV project into the existing Berry Hill 138 kV station by completing the following construction tasks: • Major Equipment • Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. • Installation of one (1) new 138 kV line disconnect switch for the generator lead line at the BERRY HILL 138 kV Station. • 1 mile of gravel access road. • Appalachian Power Company will review and revise (as needed) the protective relay settings at the BERRY HILL 138 kV Station. • Installation of one 1 breaker control at the BERRY HILL 138 kV Station. • Appalachian Power Company will install a new battery charging panel at the BERRY HILL 138 kV Station. • Expansion of the existing Drop-In Control Module (DICM) at the BERRY HILL 138 kV Station by 12 feet. • Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the BERRY HILL 138 kV Station. • Appalachian Power Company will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. • Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable. • Appalachian Power Company will install one (1) CES relaying package at the BERRY HILL 138 kV Station.

$2,867,285$1,339,019$802,907$389,968$5,399,179$5,399,179
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the BERRY HILL 138 kV Station

$372,255$211,684$106,855$59,363$750,157$750,157
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of Direct Fiber at the BERRY HILL 138 kV Station.

$258,391$122,379$86,150$40,802$507,722$507,722
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer's generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The APCO Interconnection Facilities will include but are not limited to the following: Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the BERRY HILL 138 kV Station.

$501,438$273,318$136,830$74,581$986,167$986,167
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$7,643,225$7,643,225
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-272 was evaluated as a 55.0 MW (21.3 MW Capacity) injection in the AEP area.

AG2-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 55.0 MW (55.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC133.56 %508.54B679.23
1.81
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC129.43 %508.54B658.18
1.81

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.56 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:679.23
MW Contribution:
1.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.55 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:862.23
MW Contribution:
2.02
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.101
3147133PAMPLIN
Solar/Wind Helper
0.999
3147133PAMPLIN
Solar/Wind Helper
0.255
3147133PAMPLIN
Solar/Wind Helper
0.318
274728ELWOOD EC;5P
Adder
3.35
274729ELWOOD EC;1P
Adder
3.35
274730ELWOOD EC;6P
Adder
3.35
274731ELWOOD EC;2P
Adder
3.35
274732ELWOOD EC;7P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
274734ELWOOD EC;8P
Adder
3.35
274735ELWOOD EC;4P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
3146776BUCKING
Solar/Wind Helper
0.071
3146776BUCKING
Solar/Wind Helper
0.079
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
3146926FARMVIL
Solar/Wind Helper
0.15
3146926FARMVIL
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.1
3147312GRETNA
Solar/Wind Helper
0.022
3147312GRETNA
Solar/Wind Helper
0.09
316034AC1-036 C
Solar/Wind Helper
0.37
316248AF1-058 C
Solar/Wind Helper
0.975
3146802CHATHAM
Solar/Wind Helper
0.084
3147243WELCO
Solar/Wind Helper
0.452
3144303KENBRDG
Solar/Wind Helper
0.265
3147173SINAI
Solar/Wind Helper
0.724
316494AC1-189 GEN
Solar/Wind Harmer
0.202
316049AB1-081 GEN
Solar/Wind Harmer
0.434
315773AC2-141 GEN
Solar/Wind Helper
2.463
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
316486AD2-202 GEN
Solar/Wind Helper
0.703
315687AD1-152 GEN
Solar/Wind Helper
3.72
315785AD2-033 C
Solar/Wind Helper
3.92
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
270030AE2-140 GEN
Solar/Wind Harmer
9.794
270069AE2-166 C O1
Solar/Wind Harmer
3.716
316322AB2-045
Solar/Wind Helper
0.22
316359AB2-059 GEN
Solar/Wind Harmer
0.271
316131AB2-060 GEN
Solar/Wind Helper
2.17
316263AC1-034 GEN
Solar/Wind Harmer
2.899
316129AC1-054 GEN
Solar/Wind Helper
0.798
316123AC1-075 GEN
Solar/Wind Helper
2.782
316118AC1-105 GEN
Solar/Wind Helper
2.523
316222AC1-221 GEN
Solar/Wind Helper
8.836
316283AC2-100 C
Solar/Wind Helper
8.321
316239AB2-077_GEN
Solar/Wind Helper
0.487
316238AB2-078_GEN
Solar/Wind Helper
0.487
316237AB2-079_GEN
Solar/Wind Helper
0.487
316197AC1-042 GEN
Solar/Wind Helper
0.106
316294AC1-161 GEN
Solar/Wind Helper
2.092
3145543BTLEBRO
Solar/Wind Harmer
0.061
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3138543CONSLDL
Solar/Wind Harmer
0.042
3142053HEARTS
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.095
3145493TOT1
Solar/Wind Harmer
0.302
3145493TOT1
Solar/Wind Harmer
0.158
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
3145603CNETO
Solar/Wind Harmer
0.063
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.244
3146233WITAKRS
Solar/Wind Harmer
0.042
942461AE2-259 GEN
Solar/Wind Helper
1.911
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
1.386
961601AG1-000A GEN
Solar/Wind Harmer
5.544
961671AG1-007 GEN
Solar/Wind Harmer
0.01
970085AG2-068 GEN
Solar/Wind Harmer
9.019
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970223AG2-152 GEN
Solar/Wind Harmer
8.184
970417AG2-272 GEN
50/50
1.814
970581AG2-369 GEN
Solar/Wind Harmer
7.756
970917AG2-570 GEN
Solar/Wind Harmer
15.031
970919AG2-571 GEN
Solar/Wind Harmer
6.012
971623AH1-311 GEN
Solar/Wind Harmer
0.153
971629AH1-314 GEN
50/50
14.769
957861AF2-080 GEN
Solar/Wind Harmer
2.583
900033ID_568986
External Queue
3.9371731281280518
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84
CPLELTFEXP_CPLE->PJM
CLTF
13.173
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
TVALTFEXP_TVA->PJM
CLTF
4.397
MECLTFEXP_MEC->PJM
CLTF
4.419
SIGELTFEXP_SIGE->PJM
CLTF
0.131

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:658.18
MW Contribution:
1.81
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:165.33 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:840.79
MW Contribution:
2.02
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.101
3147133PAMPLIN
Solar/Wind Helper
0.999
3147133PAMPLIN
Solar/Wind Helper
0.255
3147133PAMPLIN
Solar/Wind Helper
0.318
274728ELWOOD EC;5P
Adder
3.35
274729ELWOOD EC;1P
Adder
3.35
274730ELWOOD EC;6P
Adder
3.35
274731ELWOOD EC;2P
Adder
3.35
274732ELWOOD EC;7P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
274734ELWOOD EC;8P
Adder
3.35
274735ELWOOD EC;4P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
3146776BUCKING
Solar/Wind Helper
0.071
3146776BUCKING
Solar/Wind Helper
0.079
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
3146926FARMVIL
Solar/Wind Helper
0.15
3146926FARMVIL
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.1
3147312GRETNA
Solar/Wind Helper
0.022
3147312GRETNA
Solar/Wind Helper
0.09
316034AC1-036 C
Solar/Wind Helper
0.37
316248AF1-058 C
Solar/Wind Helper
0.975
3146802CHATHAM
Solar/Wind Helper
0.084
3147243WELCO
Solar/Wind Helper
0.452
3144303KENBRDG
Solar/Wind Helper
0.265
3147173SINAI
Solar/Wind Helper
0.724
316494AC1-189 GEN
Solar/Wind Harmer
0.202
316049AB1-081 GEN
Solar/Wind Harmer
0.434
315773AC2-141 GEN
Solar/Wind Helper
2.463
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
316486AD2-202 GEN
Solar/Wind Helper
0.703
315687AD1-152 GEN
Solar/Wind Helper
3.72
315785AD2-033 C
Solar/Wind Helper
3.92
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
270030AE2-140 GEN
Solar/Wind Harmer
9.794
270069AE2-166 C O1
Solar/Wind Harmer
3.716
316322AB2-045
Solar/Wind Helper
0.22
316359AB2-059 GEN
Solar/Wind Harmer
0.271
316131AB2-060 GEN
Solar/Wind Helper
2.17
316263AC1-034 GEN
Solar/Wind Harmer
2.899
316129AC1-054 GEN
Solar/Wind Helper
0.798
316123AC1-075 GEN
Solar/Wind Helper
2.782
316118AC1-105 GEN
Solar/Wind Helper
2.523
316222AC1-221 GEN
Solar/Wind Helper
8.836
316283AC2-100 C
Solar/Wind Helper
8.321
316239AB2-077_GEN
Solar/Wind Helper
0.487
316238AB2-078_GEN
Solar/Wind Helper
0.487
316237AB2-079_GEN
Solar/Wind Helper
0.487
316197AC1-042 GEN
Solar/Wind Helper
0.106
316294AC1-161 GEN
Solar/Wind Helper
2.092
3145543BTLEBRO
Solar/Wind Harmer
0.061
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3138543CONSLDL
Solar/Wind Harmer
0.042
3142053HEARTS
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.095
3145493TOT1
Solar/Wind Harmer
0.302
3145493TOT1
Solar/Wind Harmer
0.158
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
3145603CNETO
Solar/Wind Harmer
0.063
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.244
3146233WITAKRS
Solar/Wind Harmer
0.042
942461AE2-259 GEN
Solar/Wind Helper
1.911
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
1.386
961601AG1-000A GEN
Solar/Wind Harmer
5.544
961671AG1-007 GEN
Solar/Wind Harmer
0.01
970085AG2-068 GEN
Solar/Wind Harmer
9.019
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970223AG2-152 GEN
Solar/Wind Harmer
8.184
970417AG2-272 GEN
50/50
1.814
970581AG2-369 GEN
Solar/Wind Harmer
7.756
971623AH1-311 GEN
Solar/Wind Harmer
0.153
971629AH1-314 GEN
50/50
14.769
957861AF2-080 GEN
Solar/Wind Harmer
2.583
900033ID_568986
External Queue
3.9371731281280518
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84
CPLELTFEXP_CPLE->PJM
CLTF
13.173
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
TVALTFEXP_TVA->PJM
CLTF
4.397
MECLTFEXP_MEC->PJM
CLTF
4.419
SIGELTFEXP_SIGE->PJM
CLTF
0.131
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
3.73
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
3.74
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
3.73
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
3.73
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
3.73
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC102.99 %814.98B839.35
1.9
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC100.81 %814.98B821.61
1.9

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
3.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686405CER G5
Adder
9.787
24686505CER G6
Adder
9.865
24690905MDL-1G C
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
21.662
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728505AND G1
Adder
3.478
24728605AND G2
Adder
3.478
24728705AND G3
Adder
7.274
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
247619Y1-049
50/50
0.05
247642Z2-115 C
Solar/Wind Harmer
0.003
3151561HALLBR1
50/50
0.562
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24290705CLAY-2
50/50
0.252
25196708WSDLE6
Adder
7.96
25196808ZIMRHP
Adder
70.529
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
274676JOLIET 29;8U
Adder
26.611
274682WAUKEGAN ;7U
Adder
15.687
274682WAUKEGAN ;7U
Adder
15.687
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
274695ROCKY RD ;2P
Adder
9.717
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
274728ELWOOD EC;5P
Adder
14.264
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274732ELWOOD EC;7P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
274822ROCKFORD ;11
Adder
17.258
274823ROCKFORD ;21
Adder
17.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
274861TOP CROP ;1U
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
274879MINONK ;1U
Solar/Wind Harmer
0.255
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
3429211JKCT 2G
Adder
11.861
3429241JKCT 3G
Adder
12.016
3429391JKCT 9G
Adder
8.393
3429421JKCT 10G
Adder
8.393
25196408WSDLE3
Adder
8.07
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
24723205RIVRG3
Adder
22.932
24728205BUCHG1
50/50
7.157
24728305BUCHG2
50/50
7.157
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
25194608D.CRK4
Adder
1.506
25194608D.CRK4
Adder
1.506
25196008MFTGT1
Adder
1.292
25196008MFTGT1
Adder
1.251
25196108MFTGT2
Adder
1.322
25196108MFTGT2
Adder
1.424
25196208WSDLE1
Adder
7.98
25196308WSDLE2
Adder
8
25196508WSDLE4
Adder
7.759
25196608WSDLE5
Adder
7.839
274674JOLIET 9 ;6U
Adder
13.36
274674JOLIET 9 ;6U
Adder
13.36
274828WAUKEGAN ;BP
Adder
9.645
3147123OTTER R
Solar/Wind Harmer
0.13
3147312GRETNA
Solar/Wind Harmer
0.047
3147312GRETNA
Solar/Wind Harmer
0.186
3147666LOUISA
Solar/Wind Helper
1.089
3147666LOUISA
Solar/Wind Helper
0.626
3147983MERCK5
Solar/Wind Helper
0.198
24379505HDWTR1G C
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
252510AF1-249 C
Solar/Wind Harmer
0.048
270201AC2-176 GEN
Solar/Wind Harmer
0
270205AE1-176
50/50
0.006
3148133STUARTS
Solar/Wind Helper
0.314
3146802CHATHAM
Solar/Wind Harmer
0.174
25183208HLCRTG
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
274761LEE CO EC;2U
Adder
8.213
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274766LEE CO EC;7U
Adder
8.117
274767LEE CO EC;8U
Adder
8.117
3148013FISHERV
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.523
3132123MT JACKSON
Solar/Wind Helper
1.39
3132273ORANGE
Solar/Wind Helper
0.056
3148463FAIRFLD
Solar/Wind Helper
0.727
274872LEEDK;1U
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
926823AC1-168 GEN
Solar/Wind Harmer
1.044
276776AD2-060 GEN
Solar/Wind Harmer
0.644
276806AD2-047 C O1
Solar/Wind Harmer
3.42
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276893AG1-478 C
Solar/Wind Harmer
0.404
315616AA1-038_C
Solar/Wind Helper
3.297
276897AD1-100 C
Solar/Wind Harmer
15.124
315651AD1-115 GEN
Solar/Wind Helper
0.843
237061AD1-155 GEN
Solar/Wind Helper
1.647
315821AE2-092 GEN
Solar/Wind Helper
3.23
316499AE2-029_GEN
Solar/Wind Helper
1.726
23583801GRNGAP
Solar/Wind Helper
4.295
316473AC1-191 GEN
Solar/Wind Helper
1.388
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
316468AD1-105 GEN
Solar/Wind Helper
1.089
316313AB2-026
Solar/Wind Helper
0.355
270180AB1-006 GEN1
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
252509AD1-136 GEN
Solar/Wind Harmer
0.032
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252519AF1-045_GEN
Solar/Wind Harmer
3.347
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.713
276868AE1-113 GEN
Solar/Wind Harmer
1.222
253316AC1-085 GEN3
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.182
274744AC1-111 GEN8
Adder
4.865
274745AC1-111 GEN9
Adder
4.865
274746AC1-111 G10
Adder
4.865
276621W2-048 GEN
Solar/Wind Harmer
0.315
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
270263AC1-001 GEN
Solar/Wind Harmer
0.61
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
270209AC1-174_GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.355
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
6.875
276805AD2-038 GEN
Solar/Wind Harmer
0
270583AD2-179 GEN
Solar/Wind Harmer
14.449
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
270599AE1-208 GEN
Solar/Wind Harmer
5.547
270031AE2-169
Solar/Wind Harmer
3.328
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
270069AE2-166 C O1
Solar/Wind Harmer
10.375
270543AE2-219 C
Solar/Wind Harmer
4.252
270356AE2-297 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
20.219
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
316006AB2-029 C
Solar/Wind Helper
0.113
316192AB2-158 GEN
Solar/Wind Helper
1.845
316123AC1-075 GEN
Solar/Wind Harmer
0.164
316164AC1-076 GEN
Solar/Wind Helper
1.176
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
24735205WLF2G2
Adder
8.017
270186AC1-089 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
270004AE1-209 GEN
Solar/Wind Harmer
1.324
270005AE1-210 C O1
Solar/Wind Harmer
1.324
276615X2-022 GEN
Solar/Wind Harmer
0.065
274857EASY ROAD;U1
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.02
316095T157 G97
Solar/Wind Helper
1.128
316097T157 G90
Solar/Wind Helper
1.128
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.487
942111AE2-223 GEN
Solar/Wind Harmer
2.011
942481AE2-261 GEN
Solar/Wind Harmer
18.979
942671AE2-283 GEN
Solar/Wind Harmer
5.792
942751AE2-291 GEN
Solar/Wind Harmer
7.879
942891AE2-308 GEN
Solar/Wind Harmer
7.092
943031AE2-326 GEN
Solar/Wind Harmer
6.78
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
944221AF1-090 GEN
Solar/Wind Harmer
3.75
944971AF1-162 GEN
Solar/Wind Harmer
9.06
945391AF1-204 GEN
Solar/Wind Harmer
6.759
945421AF1-207 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.766
946031AF1-268 GEN
Solar/Wind Harmer
5.802
946171AF1-282 GEN
Solar/Wind Harmer
6.322
946181AF1-283 GEN
Solar/Wind Harmer
8.219
946321AF1-296 GEN
Solar/Wind Harmer
3.479
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.653
958481AF2-142 GEN
Solar/Wind Harmer
9.122
958491AF2-143 GEN
Solar/Wind Harmer
9.149
959081AF2-199 GEN
Solar/Wind Harmer
6.13
959091AF2-200 GEN
Solar/Wind Harmer
12.26
959341AF2-225 GEN
Solar/Wind Harmer
6.498
959611AF2-252 GEN
Solar/Wind Harmer
2.071
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960611AF2-352 GEN
Solar/Wind Harmer
2.071
960911AF2-382 GEN
Solar/Wind Harmer
7.632
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962691AG1-118 GEN
Solar/Wind Harmer
18.303
962751AG1-124 GEN
Solar/Wind Harmer
12.886
962781AG1-127 GEN
Solar/Wind Harmer
5.81
966841AG1-555 GEN
Solar/Wind Harmer
0.701
966871AG1-558 GEN
Solar/Wind Helper
0.306
966881AG1-559 GEN
Solar/Wind Helper
0.314
970091AG2-072 GEN
Adder
73.941
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970107AG2-081 GEN
Solar/Wind Harmer
2.085
970169AG2-114 GEN
Solar/Wind Harmer
6.143
970193AG2-126 GEN
Solar/Wind Harmer
9.542
970223AG2-152 GEN
Solar/Wind Harmer
12.382
970241AG2-163 GEN
Solar/Wind Harmer
3.647
970281AG2-184 GEN
Solar/Wind Harmer
18.909
970289AG2-191 GEN
Solar/Wind Harmer
1.163
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
970417AG2-272 GEN
50/50
3.731
970455AG2-298 GEN
Solar/Wind Harmer
2.725
970563AG2-360 GEN
50/50
45.796
970569AG2-363 GEN
Solar/Wind Harmer
18.425
970571AG2-364 GEN
Solar/Wind Harmer
12.283
970613AG2-401 GEN
Solar/Wind Harmer
4.518
970653AG2-424 GEN
Solar/Wind Harmer
3.403
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970773AG2-487 GEN
Solar/Wind Harmer
1.107
970781AG2-491 GEN
Solar/Wind Harmer
6.138
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970823AG2-518 GEN
50/50
8.379
970825AG2-519 GEN
Solar/Wind Harmer
4.603
970825AG2-519 GEN
Solar/Wind Harmer
2.169
970879AG2-548 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971061AG2-657 GEN
Solar/Wind Harmer
5.362
971067AG2-660 GEN
Solar/Wind Harmer
2.043
971073AG2-665 GEN
Solar/Wind Harmer
4.688
971073AG2-665 GEN
Solar/Wind Harmer
1.065
971125AH1-004 GEN
Solar/Wind Harmer
2.78
971171AH1-044 GEN
Solar/Wind Harmer
12.26
971191AH1-055 GEN
Solar/Wind Harmer
18.034
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
971277AH1-098 GEN
Solar/Wind Harmer
5.174
971313AH1-133 GEN
Solar/Wind Harmer
5.363
971329AH1-144 GEN
Solar/Wind Harmer
6.744
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
971403AH1-188 GEN
Solar/Wind Harmer
13.142
971411AH1-196 GEN
Solar/Wind Harmer
9.181
971461AH1-227 GEN
Solar/Wind Harmer
4.882
971485AH1-239 GEN
Solar/Wind Harmer
5.922
971543AH1-269 GEN
50/50
12.24
971587AH1-292 GEN
Solar/Wind Harmer
4.796
971613AH1-306 GEN
Solar/Wind Harmer
2.938
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971681AH1-341 GEN
Solar/Wind Harmer
9.907
971687AH1-348 GEN
Solar/Wind Harmer
0.947
24288905REUSENS
50/50
0.056
24415905BUCK
50/50
0.033
24416005BYLLESBY
50/50
0.03
270240V3-007_GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276158O29GEN2
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276726Z2-087_GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.218
939401AE1-172 GEN
Solar/Wind Harmer
4.564
939741AE1-205 GEN
Solar/Wind Harmer
8.664
941621AE2-160 GEN
Adder
4.281
941801AE2-185 GEN
Solar/Wind Harmer
7.447
957381AF2-032 GEN
Solar/Wind Harmer
1.438
957471AF2-041 GEN
Solar/Wind Harmer
18.391
958131AF2-107 GEN
Solar/Wind Harmer
5.335
958171AF2-111 GEN
Solar/Wind Harmer
16.661
963741AG1-226 GEN
Solar/Wind Harmer
14.798
963841AG1-237 GEN
Solar/Wind Harmer
2.696
964571AG1-320 GEN
Solar/Wind Harmer
6.355
964781AG1-341 GEN
Solar/Wind Harmer
7.646
964901AG1-354 GEN
Solar/Wind Harmer
10.795
965091AG1-374 GEN
Solar/Wind Harmer
18.636
965911AG1-460 GEN
Solar/Wind Harmer
1.269
965931AG1-462 GEN
Solar/Wind Harmer
15.863
966001AG1-469 GEN
Solar/Wind Helper
0.32
966021AG1-471 GEN
Solar/Wind Harmer
4.01
966391AG1-508 GEN
Solar/Wind Harmer
1.991
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971985AH1-537 GEN
Solar/Wind Harmer
2.009
971993AH1-541 GEN
Solar/Wind Harmer
2.902
971997AH1-543 GEN
Solar/Wind Harmer
3.207
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
972103AH1-617 GEN
Solar/Wind Harmer
18.009
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
972167AH1-666 GEN
Solar/Wind Harmer
5.413
972203AH1-686 GEN
Adder
2.702
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
972267AH1-718 GEN
Adder
3.684
972273AH1-721 GEN
Adder
89.23
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.242
274887GEN-1.85
Solar/Wind Harmer
0.157
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
6.771
945371AF1-202 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
6.035
962031AG1-047 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.033
970191AG2-125 GEN
Solar/Wind Harmer
1.552
970707AG2-453 GEN
Solar/Wind Harmer
19.749
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
970941AG2-585 GEN
Solar/Wind Harmer
3.319
971029AG2-637 GEN
Solar/Wind Harmer
9.145
971087AG2-675 GEN
Solar/Wind Harmer
3.318
971605AH1-302 GEN
Solar/Wind Harmer
7.589
971609AH1-304 GEN
Solar/Wind Harmer
0.988
971611AH1-305 GEN
Solar/Wind Harmer
3.614
971917AH1-482 GEN
Solar/Wind Harmer
7.838
276843GEN-1.7
Solar/Wind Harmer
0.195
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
957841AF2-078 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
8.691
958381AF2-132 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.453
964611AG1-324 GEN
Solar/Wind Harmer
2.357
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971881AH1-461 GEN
50/50
14.967
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
276694AA1-018 GEN2
Solar/Wind Harmer
0
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.605
24684305SMG1
50/50
0.795
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24684605SMG4
50/50
2.21
24684705SMG5
50/50
0.845
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
CPLELTFEXP_CPLE->PJM
CLTF
6.213
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
3.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686405CER G5
Adder
9.839
24686505CER G6
Adder
9.917
24721905FLATG4
Adder
21.789
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
24728505AND G1
Adder
3.5
24728605AND G2
Adder
3.5
24728705AND G3
Adder
7.32
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
247619Y1-049
50/50
0.05
3151561HALLBR1
50/50
0.562
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24290705CLAY-2
50/50
0.252
25196708WSDLE6
Adder
8.014
25196808ZIMRHP
Adder
71.001
25306009OHH W.
Adder
2.518
274675JOLIET 29;7U
Adder
26.781
274676JOLIET 29;8U
Adder
22.605
274682WAUKEGAN ;7U
Adder
15.786
274682WAUKEGAN ;7U
Adder
15.786
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274693ROCKY RD ;1P
Adder
9.683
274695ROCKY RD ;2P
Adder
9.779
274696ROCKY RD ;4P
Adder
10.01
274697ROCKY RD ;3P
Adder
2.656
274728ELWOOD EC;5P
Adder
14.355
274729ELWOOD EC;1P
Adder
14.355
274730ELWOOD EC;6P
Adder
14.355
274731ELWOOD EC;2P
Adder
14.355
274732ELWOOD EC;7P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
274734ELWOOD EC;8P
Adder
14.355
274735ELWOOD EC;4P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
274822ROCKFORD ;11
Adder
17.365
274823ROCKFORD ;21
Adder
17.239
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
3429211JKCT 2G
Adder
11.928
3429241JKCT 3G
Adder
12.084
3429391JKCT 9G
Adder
8.441
3429421JKCT 10G
Adder
8.441
25196408WSDLE3
Adder
8.125
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
24723205RIVRG3
Adder
23.046
24728205BUCHG1
50/50
7.18
24728305BUCHG2
50/50
7.18
3141426STAFORD
Solar/Wind Helper
0.049
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
25194408D.CRK1
Adder
6.977
25194508D.CRK3
Adder
1.304
25194608D.CRK4
Adder
1.517
25194608D.CRK4
Adder
1.517
25196008MFTGT1
Adder
1.3
25196008MFTGT1
Adder
1.259
25196108MFTGT2
Adder
1.331
25196108MFTGT2
Adder
1.433
25196208WSDLE1
Adder
8.034
25196308WSDLE2
Adder
8.054
25196508WSDLE4
Adder
7.812
25196608WSDLE5
Adder
7.893
274674JOLIET 9 ;6U
Adder
13.445
274674JOLIET 9 ;6U
Adder
13.445
274828WAUKEGAN ;BP
Adder
9.706
3147123OTTER R
Solar/Wind Harmer
-0.014
3147312GRETNA
Solar/Wind Harmer
-0.005
3147312GRETNA
Solar/Wind Harmer
-0.021
3147666LOUISA
Solar/Wind Helper
1.093
3147666LOUISA
Solar/Wind Helper
0.628
3147983MERCK5
Solar/Wind Helper
0.199
24385905FR-11G C
Solar/Wind Harmer
5.645
24386205FR-12G C
Solar/Wind Harmer
2.911
24386405FR-21G C
Solar/Wind Harmer
2.921
24386605FR-22G C
Solar/Wind Harmer
2.921
24387005FR-3G C
Solar/Wind Harmer
2.686
24387305FR-4G C
Solar/Wind Harmer
3.45
274760LEE CO EC;1U
Adder
8.264
316258AE1-075 C
Solar/Wind Helper
0.321
316405AF2-144 C
Solar/Wind Helper
0.267
252510AF1-249 C
Solar/Wind Harmer
0.385
270205AE1-176
50/50
0.006
3148133STUARTS
Solar/Wind Helper
0.314
3146802CHATHAM
Solar/Wind Harmer
-0.02
339211AE2-254 GEN
Solar/Wind Harmer
1.567
25183208HLCRTG
Solar/Wind Harmer
5.603
274761LEE CO EC;2U
Adder
8.264
274762LEE CO EC;3U
Adder
8.264
274763LEE CO EC;4U
Adder
8.186
274764LEE CO EC;5U
Adder
8.284
274765LEE CO EC;6U
Adder
8.284
274766LEE CO EC;7U
Adder
8.167
274767LEE CO EC;8U
Adder
8.167
3148013FISHERV
Solar/Wind Helper
0.301
3148013FISHERV
Solar/Wind Helper
0.524
3132123MT JACKSON
Solar/Wind Helper
1.393
3132273ORANGE
Solar/Wind Helper
0.056
3148463FAIRFLD
Solar/Wind Helper
0.727
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
276916AD2-100_GEN
Solar/Wind Harmer
19.251
276911AD2-131_GEN
Solar/Wind Harmer
3.891
315616AA1-038_C
Solar/Wind Helper
3.299
316312AB1-027
Solar/Wind Helper
0.426
315651AD1-115 GEN
Solar/Wind Helper
0.846
237061AD1-155 GEN
Solar/Wind Helper
1.655
315821AE2-092 GEN
Solar/Wind Helper
3.236
316499AE2-029_GEN
Solar/Wind Helper
1.728
23583801GRNGAP
Solar/Wind Helper
4.324
316473AC1-191 GEN
Solar/Wind Helper
1.393
316447AC1-158 HLD
Solar/Wind Helper
2.79
316044AC1-158 PL1
Solar/Wind Helper
1.268
316045AC1-158 PL2
Solar/Wind Helper
4.058
316450AC1-158 RIC
Solar/Wind Helper
0.338
316468AD1-105 GEN
Solar/Wind Helper
1.093
316313AB2-026
Solar/Wind Helper
0.356
253394AE2-221_GEN
Solar/Wind Harmer
4.079
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
252507AC2-088 GEN
Solar/Wind Harmer
1.676
252509AD1-136 GEN
Solar/Wind Harmer
0.239
252524AE2-267 GEN
Solar/Wind Harmer
1.45
252516AE2-318_GEN
Solar/Wind Harmer
9.259
252519AF1-045_GEN
Solar/Wind Harmer
3.37
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
339216AC1-074 GEN
Solar/Wind Harmer
1.652
339221AD2-048_GEN
Solar/Wind Harmer
1.518
339255AE2-071 GEN
Solar/Wind Harmer
1.222
274744AC1-111 GEN8
Adder
4.896
274745AC1-111 GEN9
Adder
4.896
274746AC1-111 G10
Adder
4.896
276621W2-048 GEN
Solar/Wind Harmer
5.671
339231AF1-038_GEN
Solar/Wind Harmer
1.925
339236AF1-050_GEN
Solar/Wind Harmer
1.88
339241AF1-083 GEN
Solar/Wind Harmer
1.722
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276655WTG1_EQ
Solar/Wind Harmer
7.791
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270399AC1-101 GEN
Solar/Wind Harmer
5.575
270400AC1-102 GEN
Solar/Wind Harmer
5.575
270173AC1-122 GEN
Solar/Wind Harmer
3.446
927014AC1-188 GEN
Solar/Wind Harmer
1.537
270291AC1-194 GEN
Solar/Wind Harmer
4.567
270340AC2-060 GEN
Solar/Wind Harmer
2.703
270367AC2-061_GEN
Solar/Wind Harmer
3.02
270222AC2-111 GEN
Solar/Wind Harmer
4.015
270214AC2-123 GEN
Solar/Wind Harmer
4.317
276838X2-022 GEN2
Solar/Wind Harmer
0.212
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270336AE1-100 GEN
Solar/Wind Harmer
2.754
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270016AE1-250 BESS
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
3.251
270018AE2-047 C O1
Solar/Wind Harmer
1.823
270030AE2-140 GEN
Solar/Wind Harmer
30.957
270069AE2-166 C O1
Solar/Wind Harmer
14.894
270356AE2-297 GEN
Solar/Wind Harmer
4.168
270053AF1-130 C
Solar/Wind Harmer
23.086
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
316006AB2-029 C
Solar/Wind Helper
0.114
316192AB2-158 GEN
Solar/Wind Helper
1.852
316123AC1-075 GEN
Solar/Wind Harmer
1.488
316164AC1-076 GEN
Solar/Wind Helper
1.182
24734705WLF1G3
Adder
8.213
24734805WLF1G4
Adder
8.213
24734905WLF1G5
Adder
8.213
24735105WLF2G1
Adder
8.042
24735205WLF2G2
Adder
8.042
270186AC1-089 GEN
Solar/Wind Harmer
5.851
253370AE2-315 SEC1
Adder
1.749
253370AE2-315 SEC1
Adder
1.749
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
253371AE2-315 SEC2
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
339250AF1-203 GEN
Solar/Wind Harmer
0.629
253406AD2-031_GEN
Solar/Wind Harmer
1.153
316197AC1-042 GEN
Solar/Wind Harmer
3.217
316217AC1-145 GEN
Solar/Wind Harmer
4.244
276615X2-022 GEN
Solar/Wind Harmer
1.781
274880W4-005 GEN4
Solar/Wind Harmer
2.739
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.02
316095T157 G97
Solar/Wind Helper
1.135
316097T157 G90
Solar/Wind Helper
1.135
339206AE1-143 GEN
Solar/Wind Harmer
2.213
942111AE2-223 GEN
Solar/Wind Harmer
7.317
942481AE2-261 GEN
Solar/Wind Harmer
27.366
942671AE2-283 GEN
Solar/Wind Harmer
8.669
942751AE2-291 GEN
Solar/Wind Harmer
10.38
942891AE2-308 GEN
Solar/Wind Harmer
10.222
943031AE2-326 GEN
Solar/Wind Harmer
6.794
943111AE2-339 GEN
Solar/Wind Harmer
0.887
943811AF1-049 GEN
Solar/Wind Harmer
5.701
944031AF1-071 GEN
Solar/Wind Harmer
0.903
944221AF1-090 GEN
Solar/Wind Harmer
10.074
944971AF1-162 GEN
Solar/Wind Harmer
9.1
945391AF1-204 GEN
Solar/Wind Harmer
12.785
945681AF1-233 GEN
Solar/Wind Harmer
18.414
946171AF1-282 GEN
Solar/Wind Harmer
9.125
946181AF1-283 GEN
Solar/Wind Harmer
11.863
946321AF1-296 GEN
Solar/Wind Harmer
9.347
959341AF2-225 GEN
Solar/Wind Harmer
13.389
959611AF2-252 GEN
Solar/Wind Harmer
2.083
960201AF2-311 GEN
Solar/Wind Harmer
9.005
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960611AF2-352 GEN
Solar/Wind Harmer
2.083
960911AF2-382 GEN
Solar/Wind Harmer
10.976
961491AF2-440 GEN
Solar/Wind Harmer
1.977
962211AG1-066 GEN
Solar/Wind Harmer
3.011
962581AG1-107 GEN
Solar/Wind Harmer
4.757
962751AG1-124 GEN
Solar/Wind Harmer
18.829
966871AG1-558 GEN
Solar/Wind Helper
0.307
966881AG1-559 GEN
Solar/Wind Helper
0.315
970091AG2-072 GEN
Adder
74.384
970093AG2-073 GEN
Solar/Wind Harmer
5.468
970107AG2-081 GEN
Solar/Wind Harmer
3.006
970193AG2-126 GEN
Solar/Wind Harmer
13.761
970223AG2-152 GEN
Solar/Wind Harmer
17.677
970241AG2-163 GEN
Solar/Wind Harmer
22.546
970281AG2-184 GEN
Solar/Wind Harmer
27.213
970417AG2-272 GEN
50/50
3.737
970455AG2-298 GEN
Solar/Wind Harmer
3.536
970563AG2-360 GEN
50/50
45.925
970653AG2-424 GEN
Solar/Wind Harmer
4.903
970653AG2-424 GEN
Solar/Wind Harmer
0.709
970823AG2-518 GEN
50/50
8.391
970879AG2-548 GEN
Solar/Wind Harmer
7.39
970879AG2-548 GEN
Solar/Wind Harmer
1.074
970913AG2-568 GEN
Solar/Wind Harmer
9.375
971061AG2-657 GEN
Solar/Wind Harmer
11.048
971073AG2-665 GEN
Solar/Wind Harmer
7.39
971073AG2-665 GEN
Solar/Wind Harmer
1.074
971125AH1-004 GEN
Solar/Wind Harmer
4.008
971191AH1-055 GEN
Solar/Wind Harmer
18.939
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
971277AH1-098 GEN
Solar/Wind Harmer
7.43
971313AH1-133 GEN
Solar/Wind Harmer
9.348
971329AH1-144 GEN
Solar/Wind Harmer
11.745
971331AH1-145 GEN
Solar/Wind Harmer
18.387
971403AH1-188 GEN
Solar/Wind Harmer
18.915
971461AH1-227 GEN
Solar/Wind Harmer
7.023
971485AH1-239 GEN
Solar/Wind Harmer
8.528
971543AH1-269 GEN
50/50
12.26
971687AH1-348 GEN
Solar/Wind Harmer
1.363
24288905REUSENS
50/50
0.056
24415905BUCK
50/50
0.033
24416005BYLLESBY
50/50
0.03
276174W4-005 GEN2
Solar/Wind Harmer
2.739
276656WTG2_EQ
Solar/Wind Harmer
1.032
276686W4-005 GEN3
Solar/Wind Harmer
2.739
276726Z2-087_GEN
Solar/Wind Harmer
7.058
276785W4-005 GEN1
Solar/Wind Harmer
2.739
939741AE1-205 GEN
Solar/Wind Harmer
17.852
941621AE2-160 GEN
Adder
4.304
941801AE2-185 GEN
Solar/Wind Harmer
9.813
957381AF2-032 GEN
Solar/Wind Harmer
1.829
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958131AF2-107 GEN
Solar/Wind Harmer
7.107
958171AF2-111 GEN
Solar/Wind Harmer
24.034
963741AG1-226 GEN
Solar/Wind Harmer
40.583
963841AG1-237 GEN
Solar/Wind Harmer
9.807
964571AG1-320 GEN
Solar/Wind Harmer
8.222
964781AG1-341 GEN
Solar/Wind Harmer
11.012
964901AG1-354 GEN
Solar/Wind Harmer
15.55
965091AG1-374 GEN
Solar/Wind Harmer
26.876
965911AG1-460 GEN
Solar/Wind Harmer
1.277
965931AG1-462 GEN
Solar/Wind Harmer
22.875
966001AG1-469 GEN
Solar/Wind Helper
0.321
966021AG1-471 GEN
Solar/Wind Harmer
5.774
966391AG1-508 GEN
Solar/Wind Harmer
6.384
971981AH1-535 GEN
Solar/Wind Harmer
12.593
971985AH1-537 GEN
Solar/Wind Harmer
17.394
971993AH1-541 GEN
Solar/Wind Harmer
8.371
972043AH1-570 GEN
Solar/Wind Harmer
2.487
972045AH1-571 GEN
Solar/Wind Harmer
1.989
972103AH1-617 GEN
Solar/Wind Harmer
25.917
972163AH1-664 GEN
Solar/Wind Harmer
9.793
972165AH1-665 GEN
Solar/Wind Harmer
7.834
972167AH1-666 GEN
Solar/Wind Harmer
7.807
972203AH1-686 GEN
Adder
2.716
972235AH1-702 GEN1
Adder
2.231
972236AH1-702 GEN2
Adder
1.94
972267AH1-718 GEN
Adder
3.707
972273AH1-721 GEN
Adder
89.66
957241AF2-018 GEN
Solar/Wind Harmer
5.778
958121AF2-106 GEN
Solar/Wind Harmer
9.417
960001AF2-291 GEN
Solar/Wind Harmer
3.133
971087AG2-675 GEN
Solar/Wind Harmer
3.338
971881AH1-461 GEN
50/50
15.01
238147AE2-230_GEN1
Solar/Wind Helper
0.426
238148AE2-230_GEN2
Solar/Wind Helper
0.426
238149AF1-291A_GEN
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.608
24684305SMG1
50/50
0.796
24684405SMG2
50/50
2.197
24684505SMG3
50/50
1.342
24684605SMG4
50/50
2.212
24684705SMG5
50/50
0.846
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
6.795
WECLTFEXP_WEC->PJM
CLTF
3.389
CPLELTFEXP_CPLE->PJM
CLTF
6.224
LAGNLTFEXP_LAGN->PJM
CLTF
20.349
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
TVALTFEXP_TVA->PJM
CLTF
10.64
MECLTFEXP_MEC->PJM
CLTF
15.488
SIGELTFEXP_SIGE->PJM
CLTF
0.51
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
3.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686405CER G5
Adder
9.803
24686505CER G6
Adder
9.881
24721905FLATG4
Adder
21.701
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728505AND G1
Adder
3.485
24728605AND G2
Adder
3.485
24728705AND G3
Adder
7.288
24728805RICHG1
Adder
3.39
24728905RICHG2
Adder
3.39
247619Y1-049
50/50
0.05
3151561HALLBR1
50/50
0.562
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24290705CLAY-2
50/50
0.252
25196708WSDLE6
Adder
7.976
25196808ZIMRHP
Adder
70.673
25306009OHH W.
Adder
2.505
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
274676JOLIET 29;8U
Adder
26.663
274682WAUKEGAN ;7U
Adder
15.718
274682WAUKEGAN ;7U
Adder
15.718
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274693ROCKY RD ;1P
Adder
9.64
274695ROCKY RD ;2P
Adder
9.736
274696ROCKY RD ;4P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.645
274728ELWOOD EC;5P
Adder
14.292
274729ELWOOD EC;1P
Adder
14.292
274730ELWOOD EC;6P
Adder
14.292
274731ELWOOD EC;2P
Adder
14.292
274732ELWOOD EC;7P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
274734ELWOOD EC;8P
Adder
14.292
274735ELWOOD EC;4P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
274822ROCKFORD ;11
Adder
17.29
274823ROCKFORD ;21
Adder
17.165
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
3429211JKCT 2G
Adder
11.881
3429241JKCT 3G
Adder
12.037
3429391JKCT 9G
Adder
8.408
3429421JKCT 10G
Adder
8.408
25196408WSDLE3
Adder
8.087
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
24723205RIVRG3
Adder
22.967
24728205BUCHG1
50/50
7.164
24728305BUCHG2
50/50
7.164
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
25194408D.CRK1
Adder
6.944
25194508D.CRK3
Adder
1.298
25194608D.CRK4
Adder
1.51
25194608D.CRK4
Adder
1.51
25196008MFTGT1
Adder
1.294
25196008MFTGT1
Adder
1.253
25196108MFTGT2
Adder
1.325
25196108MFTGT2
Adder
1.427
25196208WSDLE1
Adder
7.996
25196308WSDLE2
Adder
8.016
25196508WSDLE4
Adder
7.775
25196608WSDLE5
Adder
7.856
274674JOLIET 9 ;6U
Adder
13.386
274674JOLIET 9 ;6U
Adder
13.386
274828WAUKEGAN ;BP
Adder
9.664
3147123OTTER R
Solar/Wind Harmer
-0.014
3147312GRETNA
Solar/Wind Harmer
-0.005
3147312GRETNA
Solar/Wind Harmer
-0.021
3147666LOUISA
Solar/Wind Helper
1.09
3147666LOUISA
Solar/Wind Helper
0.627
3147983MERCK5
Solar/Wind Helper
0.199
24385905FR-11G C
Solar/Wind Harmer
4.044
24386205FR-12G C
Solar/Wind Harmer
2.085
24386405FR-21G C
Solar/Wind Harmer
2.093
24386605FR-22G C
Solar/Wind Harmer
2.093
24387005FR-3G C
Solar/Wind Harmer
1.925
24387305FR-4G C
Solar/Wind Harmer
2.471
274760LEE CO EC;1U
Adder
8.229
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
252510AF1-249 C
Solar/Wind Harmer
0.384
270205AE1-176
50/50
0.006
3148133STUARTS
Solar/Wind Helper
0.314
3146802CHATHAM
Solar/Wind Harmer
-0.02
339211AE2-254 GEN
Solar/Wind Harmer
1.561
25183208HLCRTG
Solar/Wind Harmer
5.577
274761LEE CO EC;2U
Adder
8.229
274762LEE CO EC;3U
Adder
8.229
274763LEE CO EC;4U
Adder
8.151
274764LEE CO EC;5U
Adder
8.248
274765LEE CO EC;6U
Adder
8.248
274766LEE CO EC;7U
Adder
8.132
274767LEE CO EC;8U
Adder
8.132
3148013FISHERV
Solar/Wind Helper
0.301
3148013FISHERV
Solar/Wind Helper
0.523
3132123MT JACKSON
Solar/Wind Helper
1.391
3132273ORANGE
Solar/Wind Helper
0.056
3148463FAIRFLD
Solar/Wind Helper
0.727
276916AD2-100_GEN
Solar/Wind Harmer
19.171
276911AD2-131_GEN
Solar/Wind Harmer
3.875
315616AA1-038_C
Solar/Wind Helper
3.298
316312AB1-027
Solar/Wind Helper
0.425
315651AD1-115 GEN
Solar/Wind Helper
0.844
237061AD1-155 GEN
Solar/Wind Helper
1.65
315821AE2-092 GEN
Solar/Wind Helper
3.232
316499AE2-029_GEN
Solar/Wind Helper
1.726
23583801GRNGAP
Solar/Wind Helper
4.304
316473AC1-191 GEN
Solar/Wind Helper
1.39
316447AC1-158 HLD
Solar/Wind Helper
2.781
316044AC1-158 PL1
Solar/Wind Helper
1.264
316045AC1-158 PL2
Solar/Wind Helper
4.045
316450AC1-158 RIC
Solar/Wind Helper
0.337
316468AD1-105 GEN
Solar/Wind Helper
1.09
316313AB2-026
Solar/Wind Helper
0.356
253394AE2-221_GEN
Solar/Wind Harmer
4.059
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
252507AC2-088 GEN
Solar/Wind Harmer
1.668
252509AD1-136 GEN
Solar/Wind Harmer
0.238
252524AE2-267 GEN
Solar/Wind Harmer
1.443
252516AE2-318_GEN
Solar/Wind Harmer
9.216
252519AF1-045_GEN
Solar/Wind Harmer
3.354
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
339216AC1-074 GEN
Solar/Wind Harmer
1.645
339221AD2-048_GEN
Solar/Wind Harmer
1.511
339255AE2-071 GEN
Solar/Wind Harmer
1.218
274744AC1-111 GEN8
Adder
4.874
274745AC1-111 GEN9
Adder
4.874
274746AC1-111 G10
Adder
4.874
276621W2-048 GEN
Solar/Wind Harmer
5.648
339231AF1-038_GEN
Solar/Wind Harmer
1.919
339236AF1-050_GEN
Solar/Wind Harmer
1.873
339241AF1-083 GEN
Solar/Wind Harmer
1.716
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276655WTG1_EQ
Solar/Wind Harmer
7.757
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
270173AC1-122 GEN
Solar/Wind Harmer
3.444
927014AC1-188 GEN
Solar/Wind Harmer
1.529
270291AC1-194 GEN
Solar/Wind Harmer
4.541
270340AC2-060 GEN
Solar/Wind Harmer
2.689
270367AC2-061_GEN
Solar/Wind Harmer
3.006
270222AC2-111 GEN
Solar/Wind Harmer
3.996
270214AC2-123 GEN
Solar/Wind Harmer
4.311
276838X2-022 GEN2
Solar/Wind Harmer
0.211
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270336AE1-100 GEN
Solar/Wind Harmer
2.751
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270016AE1-250 BESS
Solar/Wind Harmer
3.249
270013AE1-250 PV
Solar/Wind Harmer
3.249
270018AE2-047 C O1
Solar/Wind Harmer
1.821
270030AE2-140 GEN
Solar/Wind Harmer
30.922
270069AE2-166 C O1
Solar/Wind Harmer
14.878
270356AE2-297 GEN
Solar/Wind Harmer
4.149
270053AF1-130 C
Solar/Wind Harmer
23.016
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
316006AB2-029 C
Solar/Wind Helper
0.113
316192AB2-158 GEN
Solar/Wind Helper
1.847
316123AC1-075 GEN
Solar/Wind Harmer
1.487
316164AC1-076 GEN
Solar/Wind Helper
1.178
24734705WLF1G3
Adder
8.195
24734805WLF1G4
Adder
8.195
24734905WLF1G5
Adder
8.195
24735105WLF2G1
Adder
8.025
24735205WLF2G2
Adder
8.025
270186AC1-089 GEN
Solar/Wind Harmer
5.824
339250AF1-203 GEN
Solar/Wind Harmer
0.627
253406AD2-031_GEN
Solar/Wind Harmer
1.147
316197AC1-042 GEN
Solar/Wind Harmer
3.216
316217AC1-145 GEN
Solar/Wind Harmer
4.242
276615X2-022 GEN
Solar/Wind Harmer
1.774
274880W4-005 GEN4
Solar/Wind Harmer
2.728
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.02
316095T157 G97
Solar/Wind Helper
1.13
316097T157 G90
Solar/Wind Helper
1.13
339206AE1-143 GEN
Solar/Wind Harmer
2.205
942111AE2-223 GEN
Solar/Wind Harmer
7.286
942481AE2-261 GEN
Solar/Wind Harmer
27.253
942671AE2-283 GEN
Solar/Wind Harmer
8.664
942751AE2-291 GEN
Solar/Wind Harmer
10.376
942891AE2-308 GEN
Solar/Wind Harmer
10.182
943031AE2-326 GEN
Solar/Wind Harmer
6.784
943111AE2-339 GEN
Solar/Wind Harmer
0.883
943811AF1-049 GEN
Solar/Wind Harmer
5.695
944031AF1-071 GEN
Solar/Wind Harmer
0.899
944221AF1-090 GEN
Solar/Wind Harmer
10.032
944971AF1-162 GEN
Solar/Wind Harmer
9.072
945391AF1-204 GEN
Solar/Wind Harmer
12.73
945681AF1-233 GEN
Solar/Wind Harmer
18.334
946171AF1-282 GEN
Solar/Wind Harmer
9.081
946181AF1-283 GEN
Solar/Wind Harmer
11.806
946321AF1-296 GEN
Solar/Wind Harmer
9.308
959341AF2-225 GEN
Solar/Wind Harmer
13.331
959611AF2-252 GEN
Solar/Wind Harmer
2.075
960201AF2-311 GEN
Solar/Wind Harmer
8.941
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960611AF2-352 GEN
Solar/Wind Harmer
2.075
960911AF2-382 GEN
Solar/Wind Harmer
10.95
961491AF2-440 GEN
Solar/Wind Harmer
1.967
962211AG1-066 GEN
Solar/Wind Harmer
3.002
962581AG1-107 GEN
Solar/Wind Harmer
4.734
962751AG1-124 GEN
Solar/Wind Harmer
18.819
966871AG1-558 GEN
Solar/Wind Helper
0.307
966881AG1-559 GEN
Solar/Wind Helper
0.314
970091AG2-072 GEN
Adder
74.077
970093AG2-073 GEN
Solar/Wind Harmer
5.447
970107AG2-081 GEN
Solar/Wind Harmer
2.994
970193AG2-126 GEN
Solar/Wind Harmer
13.702
970223AG2-152 GEN
Solar/Wind Harmer
17.663
970241AG2-163 GEN
Solar/Wind Harmer
22.448
970281AG2-184 GEN
Solar/Wind Harmer
27.137
970417AG2-272 GEN
50/50
3.733
970455AG2-298 GEN
Solar/Wind Harmer
3.522
970563AG2-360 GEN
50/50
45.836
970653AG2-424 GEN
Solar/Wind Harmer
4.885
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970823AG2-518 GEN
50/50
8.383
970879AG2-548 GEN
Solar/Wind Harmer
7.349
970879AG2-548 GEN
Solar/Wind Harmer
1.068
970913AG2-568 GEN
Solar/Wind Harmer
9.345
971061AG2-657 GEN
Solar/Wind Harmer
11.001
971073AG2-665 GEN
Solar/Wind Harmer
7.349
971073AG2-665 GEN
Solar/Wind Harmer
1.068
971125AH1-004 GEN
Solar/Wind Harmer
3.992
971191AH1-055 GEN
Solar/Wind Harmer
18.847
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
971277AH1-098 GEN
Solar/Wind Harmer
7.42
971313AH1-133 GEN
Solar/Wind Harmer
9.329
971329AH1-144 GEN
Solar/Wind Harmer
11.729
971331AH1-145 GEN
Solar/Wind Harmer
18.362
971403AH1-188 GEN
Solar/Wind Harmer
18.86
971461AH1-227 GEN
Solar/Wind Harmer
7.006
971485AH1-239 GEN
Solar/Wind Harmer
8.501
971543AH1-269 GEN
50/50
12.246
971687AH1-348 GEN
Solar/Wind Harmer
1.359
24288905REUSENS
50/50
0.056
24415905BUCK
50/50
0.033
24416005BYLLESBY
50/50
0.03
276174W4-005 GEN2
Solar/Wind Harmer
2.728
276656WTG2_EQ
Solar/Wind Harmer
1.027
276686W4-005 GEN3
Solar/Wind Harmer
2.728
276726Z2-087_GEN
Solar/Wind Harmer
7.027
276785W4-005 GEN1
Solar/Wind Harmer
2.728
939741AE1-205 GEN
Solar/Wind Harmer
17.775
941621AE2-160 GEN
Adder
4.288
941801AE2-185 GEN
Solar/Wind Harmer
9.808
957381AF2-032 GEN
Solar/Wind Harmer
1.822
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958131AF2-107 GEN
Solar/Wind Harmer
7.104
958171AF2-111 GEN
Solar/Wind Harmer
23.928
963741AG1-226 GEN
Solar/Wind Harmer
40.407
963841AG1-237 GEN
Solar/Wind Harmer
9.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
964781AG1-341 GEN
Solar/Wind Harmer
10.975
964901AG1-354 GEN
Solar/Wind Harmer
15.496
965091AG1-374 GEN
Solar/Wind Harmer
26.762
965911AG1-460 GEN
Solar/Wind Harmer
1.272
965931AG1-462 GEN
Solar/Wind Harmer
22.779
966001AG1-469 GEN
Solar/Wind Helper
0.321
966021AG1-471 GEN
Solar/Wind Harmer
5.755
966391AG1-508 GEN
Solar/Wind Harmer
6.375
971981AH1-535 GEN
Solar/Wind Harmer
12.564
971985AH1-537 GEN
Solar/Wind Harmer
17.311
971993AH1-541 GEN
Solar/Wind Harmer
8.336
972043AH1-570 GEN
Solar/Wind Harmer
2.477
972045AH1-571 GEN
Solar/Wind Harmer
1.981
972103AH1-617 GEN
Solar/Wind Harmer
25.844
972163AH1-664 GEN
Solar/Wind Harmer
9.75
972165AH1-665 GEN
Solar/Wind Harmer
7.8
972167AH1-666 GEN
Solar/Wind Harmer
7.773
972203AH1-686 GEN
Adder
2.706
972235AH1-702 GEN1
Adder
2.222
972236AH1-702 GEN2
Adder
1.932
972267AH1-718 GEN
Adder
3.691
972273AH1-721 GEN
Adder
89.361
957241AF2-018 GEN
Solar/Wind Harmer
5.76
958121AF2-106 GEN
Solar/Wind Harmer
9.406
960001AF2-291 GEN
Solar/Wind Harmer
3.117
971087AG2-675 GEN
Solar/Wind Harmer
3.324
971881AH1-461 GEN
50/50
14.98
238147AE2-230_GEN1
Solar/Wind Helper
0.424
238148AE2-230_GEN2
Solar/Wind Helper
0.424
238149AF1-291A_GEN
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.606
24684305SMG1
50/50
0.796
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24684605SMG4
50/50
2.211
24684705SMG5
50/50
0.845
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
6.768
WECLTFEXP_WEC->PJM
CLTF
3.374
CPLELTFEXP_CPLE->PJM
CLTF
6.216
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
TVALTFEXP_TVA->PJM
CLTF
10.609
MECLTFEXP_MEC->PJM
CLTF
15.426
SIGELTFEXP_SIGE->PJM
CLTF
0.508
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
3.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686405CER G5
Adder
9.787
24686505CER G6
Adder
9.865
24721905FLATG4
Adder
21.662
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728505AND G1
Adder
3.478
24728605AND G2
Adder
3.478
24728705AND G3
Adder
7.274
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
247619Y1-049
50/50
0.05
3151561HALLBR1
50/50
0.562
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24290705CLAY-2
50/50
0.252
25196708WSDLE6
Adder
7.96
25196808ZIMRHP
Adder
70.529
25306009OHH W.
Adder
2.5
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
274676JOLIET 29;8U
Adder
26.611
274682WAUKEGAN ;7U
Adder
15.687
274682WAUKEGAN ;7U
Adder
15.687
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
274695ROCKY RD ;2P
Adder
9.717
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
274728ELWOOD EC;5P
Adder
14.264
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274732ELWOOD EC;7P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
274822ROCKFORD ;11
Adder
17.258
274823ROCKFORD ;21
Adder
17.132
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
3429211JKCT 2G
Adder
11.861
3429241JKCT 3G
Adder
12.016
3429391JKCT 9G
Adder
8.393
3429421JKCT 10G
Adder
8.393
25196408WSDLE3
Adder
8.07
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
24723205RIVRG3
Adder
22.932
24728205BUCHG1
50/50
7.157
24728305BUCHG2
50/50
7.157
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
25194608D.CRK4
Adder
1.506
25194608D.CRK4
Adder
1.506
25196008MFTGT1
Adder
1.292
25196008MFTGT1
Adder
1.251
25196108MFTGT2
Adder
1.322
25196108MFTGT2
Adder
1.424
25196208WSDLE1
Adder
7.98
25196308WSDLE2
Adder
8
25196508WSDLE4
Adder
7.759
25196608WSDLE5
Adder
7.839
274674JOLIET 9 ;6U
Adder
13.36
274674JOLIET 9 ;6U
Adder
13.36
274828WAUKEGAN ;BP
Adder
9.645
3147123OTTER R
Solar/Wind Harmer
-0.014
3147312GRETNA
Solar/Wind Harmer
-0.005
3147312GRETNA
Solar/Wind Harmer
-0.021
3147666LOUISA
Solar/Wind Helper
1.089
3147666LOUISA
Solar/Wind Helper
0.626
3147983MERCK5
Solar/Wind Helper
0.198
24385905FR-11G C
Solar/Wind Harmer
4.036
24386205FR-12G C
Solar/Wind Harmer
2.081
24386405FR-21G C
Solar/Wind Harmer
2.088
24386605FR-22G C
Solar/Wind Harmer
2.088
24387005FR-3G C
Solar/Wind Harmer
1.921
24387305FR-4G C
Solar/Wind Harmer
2.467
274760LEE CO EC;1U
Adder
8.213
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
252510AF1-249 C
Solar/Wind Harmer
0.383
270205AE1-176
50/50
0.006
3148133STUARTS
Solar/Wind Helper
0.314
3146802CHATHAM
Solar/Wind Harmer
-0.02
339211AE2-254 GEN
Solar/Wind Harmer
1.559
25183208HLCRTG
Solar/Wind Harmer
5.565
274761LEE CO EC;2U
Adder
8.213
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274766LEE CO EC;7U
Adder
8.117
274767LEE CO EC;8U
Adder
8.117
3148013FISHERV
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.523
3132123MT JACKSON
Solar/Wind Helper
1.39
3132273ORANGE
Solar/Wind Helper
0.056
3148463FAIRFLD
Solar/Wind Helper
0.727
276916AD2-100_GEN
Solar/Wind Harmer
19.136
276911AD2-131_GEN
Solar/Wind Harmer
3.867
315616AA1-038_C
Solar/Wind Helper
3.297
315651AD1-115 GEN
Solar/Wind Helper
0.843
237061AD1-155 GEN
Solar/Wind Helper
1.647
315821AE2-092 GEN
Solar/Wind Helper
3.23
316499AE2-029_GEN
Solar/Wind Helper
1.726
23583801GRNGAP
Solar/Wind Helper
4.295
316473AC1-191 GEN
Solar/Wind Helper
1.388
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
316468AD1-105 GEN
Solar/Wind Helper
1.089
316313AB2-026
Solar/Wind Helper
0.355
253394AE2-221_GEN
Solar/Wind Harmer
4.05
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
252507AC2-088 GEN
Solar/Wind Harmer
1.664
252509AD1-136 GEN
Solar/Wind Harmer
0.238
252524AE2-267 GEN
Solar/Wind Harmer
1.44
252516AE2-318_GEN
Solar/Wind Harmer
9.197
252519AF1-045_GEN
Solar/Wind Harmer
3.347
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
339216AC1-074 GEN
Solar/Wind Harmer
1.642
339221AD2-048_GEN
Solar/Wind Harmer
1.508
339255AE2-071 GEN
Solar/Wind Harmer
1.216
274744AC1-111 GEN8
Adder
4.865
274745AC1-111 GEN9
Adder
4.865
274746AC1-111 G10
Adder
4.865
276621W2-048 GEN
Solar/Wind Harmer
5.637
339231AF1-038_GEN
Solar/Wind Harmer
1.916
339236AF1-050_GEN
Solar/Wind Harmer
1.871
339241AF1-083 GEN
Solar/Wind Harmer
1.713
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276655WTG1_EQ
Solar/Wind Harmer
7.743
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270399AC1-101 GEN
Solar/Wind Harmer
5.551
270400AC1-102 GEN
Solar/Wind Harmer
5.551
270173AC1-122 GEN
Solar/Wind Harmer
3.443
927014AC1-188 GEN
Solar/Wind Harmer
1.526
270291AC1-194 GEN
Solar/Wind Harmer
4.529
270340AC2-060 GEN
Solar/Wind Harmer
2.683
270367AC2-061_GEN
Solar/Wind Harmer
3
270222AC2-111 GEN
Solar/Wind Harmer
3.988
270214AC2-123 GEN
Solar/Wind Harmer
4.308
276838X2-022 GEN2
Solar/Wind Harmer
0.21
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270336AE1-100 GEN
Solar/Wind Harmer
2.749
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270016AE1-250 BESS
Solar/Wind Harmer
3.247
270013AE1-250 PV
Solar/Wind Harmer
3.247
270018AE2-047 C O1
Solar/Wind Harmer
1.82
270030AE2-140 GEN
Solar/Wind Harmer
30.906
270069AE2-166 C O1
Solar/Wind Harmer
14.87
270356AE2-297 GEN
Solar/Wind Harmer
4.141
270053AF1-130 C
Solar/Wind Harmer
22.985
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
316006AB2-029 C
Solar/Wind Helper
0.113
316192AB2-158 GEN
Solar/Wind Helper
1.845
316123AC1-075 GEN
Solar/Wind Harmer
1.487
316164AC1-076 GEN
Solar/Wind Helper
1.176
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
24735205WLF2G2
Adder
8.017
270186AC1-089 GEN
Solar/Wind Harmer
5.812
339250AF1-203 GEN
Solar/Wind Harmer
0.626
253406AD2-031_GEN
Solar/Wind Harmer
1.145
316197AC1-042 GEN
Solar/Wind Harmer
3.215
316217AC1-145 GEN
Solar/Wind Harmer
4.241
276615X2-022 GEN
Solar/Wind Harmer
1.77
274880W4-005 GEN4
Solar/Wind Harmer
2.723
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.02
316095T157 G97
Solar/Wind Helper
1.128
316097T157 G90
Solar/Wind Helper
1.128
339206AE1-143 GEN
Solar/Wind Harmer
2.202
942111AE2-223 GEN
Solar/Wind Harmer
7.272
942481AE2-261 GEN
Solar/Wind Harmer
27.203
942671AE2-283 GEN
Solar/Wind Harmer
8.662
942751AE2-291 GEN
Solar/Wind Harmer
10.374
942891AE2-308 GEN
Solar/Wind Harmer
10.165
943031AE2-326 GEN
Solar/Wind Harmer
6.78
943111AE2-339 GEN
Solar/Wind Harmer
0.882
943811AF1-049 GEN
Solar/Wind Harmer
5.692
944031AF1-071 GEN
Solar/Wind Harmer
0.897
944221AF1-090 GEN
Solar/Wind Harmer
10.014
944971AF1-162 GEN
Solar/Wind Harmer
9.06
945391AF1-204 GEN
Solar/Wind Harmer
12.706
945681AF1-233 GEN
Solar/Wind Harmer
18.298
946171AF1-282 GEN
Solar/Wind Harmer
9.062
946181AF1-283 GEN
Solar/Wind Harmer
11.78
946321AF1-296 GEN
Solar/Wind Harmer
9.291
959341AF2-225 GEN
Solar/Wind Harmer
13.306
959611AF2-252 GEN
Solar/Wind Harmer
2.071
960201AF2-311 GEN
Solar/Wind Harmer
8.913
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960611AF2-352 GEN
Solar/Wind Harmer
2.071
960911AF2-382 GEN
Solar/Wind Harmer
10.939
961491AF2-440 GEN
Solar/Wind Harmer
1.963
962211AG1-066 GEN
Solar/Wind Harmer
2.998
962581AG1-107 GEN
Solar/Wind Harmer
4.724
962751AG1-124 GEN
Solar/Wind Harmer
18.814
966871AG1-558 GEN
Solar/Wind Helper
0.306
966881AG1-559 GEN
Solar/Wind Helper
0.314
970091AG2-072 GEN
Adder
73.941
970093AG2-073 GEN
Solar/Wind Harmer
5.438
970107AG2-081 GEN
Solar/Wind Harmer
2.988
970193AG2-126 GEN
Solar/Wind Harmer
13.676
970223AG2-152 GEN
Solar/Wind Harmer
17.657
970241AG2-163 GEN
Solar/Wind Harmer
22.405
970281AG2-184 GEN
Solar/Wind Harmer
27.103
970417AG2-272 GEN
50/50
3.731
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970563AG2-360 GEN
50/50
45.796
970653AG2-424 GEN
Solar/Wind Harmer
4.877
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970823AG2-518 GEN
50/50
8.379
970879AG2-548 GEN
Solar/Wind Harmer
7.33
970879AG2-548 GEN
Solar/Wind Harmer
1.065
970913AG2-568 GEN
Solar/Wind Harmer
9.332
971061AG2-657 GEN
Solar/Wind Harmer
10.98
971073AG2-665 GEN
Solar/Wind Harmer
7.33
971073AG2-665 GEN
Solar/Wind Harmer
1.065
971125AH1-004 GEN
Solar/Wind Harmer
3.985
971191AH1-055 GEN
Solar/Wind Harmer
18.807
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
971277AH1-098 GEN
Solar/Wind Harmer
7.416
971313AH1-133 GEN
Solar/Wind Harmer
9.321
971329AH1-144 GEN
Solar/Wind Harmer
11.722
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971403AH1-188 GEN
Solar/Wind Harmer
18.836
971461AH1-227 GEN
Solar/Wind Harmer
6.998
971485AH1-239 GEN
Solar/Wind Harmer
8.488
971543AH1-269 GEN
50/50
12.24
971687AH1-348 GEN
Solar/Wind Harmer
1.358
24288905REUSENS
50/50
0.056
24415905BUCK
50/50
0.033
24416005BYLLESBY
50/50
0.03
276174W4-005 GEN2
Solar/Wind Harmer
2.723
276656WTG2_EQ
Solar/Wind Harmer
1.025
276686W4-005 GEN3
Solar/Wind Harmer
2.723
276726Z2-087_GEN
Solar/Wind Harmer
7.014
276785W4-005 GEN1
Solar/Wind Harmer
2.723
939741AE1-205 GEN
Solar/Wind Harmer
17.741
941621AE2-160 GEN
Adder
4.281
941801AE2-185 GEN
Solar/Wind Harmer
9.805
957381AF2-032 GEN
Solar/Wind Harmer
1.819
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958131AF2-107 GEN
Solar/Wind Harmer
7.102
958171AF2-111 GEN
Solar/Wind Harmer
23.881
963741AG1-226 GEN
Solar/Wind Harmer
40.329
963841AG1-237 GEN
Solar/Wind Harmer
9.746
964571AG1-320 GEN
Solar/Wind Harmer
8.178
964781AG1-341 GEN
Solar/Wind Harmer
10.959
964901AG1-354 GEN
Solar/Wind Harmer
15.473
965091AG1-374 GEN
Solar/Wind Harmer
26.711
965911AG1-460 GEN
Solar/Wind Harmer
1.269
965931AG1-462 GEN
Solar/Wind Harmer
22.737
966001AG1-469 GEN
Solar/Wind Helper
0.32
966021AG1-471 GEN
Solar/Wind Harmer
5.747
966391AG1-508 GEN
Solar/Wind Harmer
6.371
971981AH1-535 GEN
Solar/Wind Harmer
12.552
971985AH1-537 GEN
Solar/Wind Harmer
17.275
971993AH1-541 GEN
Solar/Wind Harmer
8.32
972043AH1-570 GEN
Solar/Wind Harmer
2.472
972045AH1-571 GEN
Solar/Wind Harmer
1.978
972103AH1-617 GEN
Solar/Wind Harmer
25.812
972163AH1-664 GEN
Solar/Wind Harmer
9.732
972165AH1-665 GEN
Solar/Wind Harmer
7.785
972167AH1-666 GEN
Solar/Wind Harmer
7.758
972203AH1-686 GEN
Adder
2.702
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
972267AH1-718 GEN
Adder
3.684
972273AH1-721 GEN
Adder
89.23
957241AF2-018 GEN
Solar/Wind Harmer
5.752
958121AF2-106 GEN
Solar/Wind Harmer
9.401
960001AF2-291 GEN
Solar/Wind Harmer
3.11
971087AG2-675 GEN
Solar/Wind Harmer
3.318
971881AH1-461 GEN
50/50
14.967
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.605
24684305SMG1
50/50
0.795
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24684605SMG4
50/50
2.21
24684705SMG5
50/50
0.845
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
CPLELTFEXP_CPLE->PJM
CLTF
6.213
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
3.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24686405CER G5
Adder
9.792
24686505CER G6
Adder
9.87
24721905FLATG4
Adder
21.675
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
24728505AND G1
Adder
3.48
24728605AND G2
Adder
3.48
24728705AND G3
Adder
7.279
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
247619Y1-049
50/50
0.05
3151561HALLBR1
50/50
0.562
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24290705CLAY-2
50/50
0.252
25196708WSDLE6
Adder
7.965
25196808ZIMRHP
Adder
70.578
25306009OHH W.
Adder
2.502
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
274676JOLIET 29;8U
Adder
26.631
274682WAUKEGAN ;7U
Adder
15.699
274682WAUKEGAN ;7U
Adder
15.699
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274693ROCKY RD ;1P
Adder
9.629
274695ROCKY RD ;2P
Adder
9.725
274696ROCKY RD ;4P
Adder
9.954
274697ROCKY RD ;3P
Adder
2.642
274728ELWOOD EC;5P
Adder
14.275
274729ELWOOD EC;1P
Adder
14.275
274730ELWOOD EC;6P
Adder
14.275
274731ELWOOD EC;2P
Adder
14.275
274732ELWOOD EC;7P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
274734ELWOOD EC;8P
Adder
14.275
274735ELWOOD EC;4P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
274822ROCKFORD ;11
Adder
17.27
274823ROCKFORD ;21
Adder
17.145
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
3429211JKCT 2G
Adder
11.868
3429241JKCT 3G
Adder
12.024
3429391JKCT 9G
Adder
8.399
3429421JKCT 10G
Adder
8.399
25196408WSDLE3
Adder
8.076
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
24723205RIVRG3
Adder
22.944
24728205BUCHG1
50/50
7.16
24728305BUCHG2
50/50
7.16
25194408D.CRK1
Adder
6.935
25194508D.CRK3
Adder
1.296
25194608D.CRK4
Adder
1.508
25194608D.CRK4
Adder
1.508
25196008MFTGT1
Adder
1.293
25196008MFTGT1
Adder
1.252
25196108MFTGT2
Adder
1.323
25196108MFTGT2
Adder
1.425
25196208WSDLE1
Adder
7.985
25196308WSDLE2
Adder
8.005
25196508WSDLE4
Adder
7.765
25196608WSDLE5
Adder
7.845
274674JOLIET 9 ;6U
Adder
13.37
274674JOLIET 9 ;6U
Adder
13.37
274828WAUKEGAN ;BP
Adder
9.652
3147123OTTER R
Solar/Wind Harmer
-0.014
3147312GRETNA
Solar/Wind Harmer
-0.005
3147312GRETNA
Solar/Wind Harmer
-0.021
3147666LOUISA
Solar/Wind Helper
1.088
3147666LOUISA
Solar/Wind Helper
0.626
3147983MERCK5
Solar/Wind Helper
0.198
24385905FR-11G C
Solar/Wind Harmer
4.039
24386205FR-12G C
Solar/Wind Harmer
2.082
24386405FR-21G C
Solar/Wind Harmer
2.09
24386605FR-22G C
Solar/Wind Harmer
2.09
24387005FR-3G C
Solar/Wind Harmer
1.922
24387305FR-4G C
Solar/Wind Harmer
2.468
274760LEE CO EC;1U
Adder
8.219
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.266
252510AF1-249 C
Solar/Wind Harmer
0.383
270205AE1-176
50/50
0.006
3148133STUARTS
Solar/Wind Helper
0.313
3146802CHATHAM
Solar/Wind Harmer
-0.02
339211AE2-254 GEN
Solar/Wind Harmer
1.56
25183208HLCRTG
Solar/Wind Harmer
5.569
274761LEE CO EC;2U
Adder
8.219
274762LEE CO EC;3U
Adder
8.219
274763LEE CO EC;4U
Adder
8.142
274764LEE CO EC;5U
Adder
8.239
274765LEE CO EC;6U
Adder
8.239
274766LEE CO EC;7U
Adder
8.123
274767LEE CO EC;8U
Adder
8.123
3148013FISHERV
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.523
3132123MT JACKSON
Solar/Wind Helper
1.389
3132273ORANGE
Solar/Wind Helper
0.056
3148463FAIRFLD
Solar/Wind Helper
0.726
276916AD2-100_GEN
Solar/Wind Harmer
19.15
276911AD2-131_GEN
Solar/Wind Harmer
3.87
315616AA1-038_C
Solar/Wind Helper
3.296
315651AD1-115 GEN
Solar/Wind Helper
0.842
237061AD1-155 GEN
Solar/Wind Helper
1.646
315821AE2-092 GEN
Solar/Wind Helper
3.228
316499AE2-029_GEN
Solar/Wind Helper
1.725
23583801GRNGAP
Solar/Wind Helper
4.293
316473AC1-191 GEN
Solar/Wind Helper
1.387
316447AC1-158 HLD
Solar/Wind Helper
2.775
316044AC1-158 PL1
Solar/Wind Helper
1.261
316045AC1-158 PL2
Solar/Wind Helper
4.036
316450AC1-158 RIC
Solar/Wind Helper
0.336
316468AD1-105 GEN
Solar/Wind Helper
1.088
316313AB2-026
Solar/Wind Helper
0.355
253394AE2-221_GEN
Solar/Wind Harmer
4.053
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
252507AC2-088 GEN
Solar/Wind Harmer
1.666
252509AD1-136 GEN
Solar/Wind Harmer
0.238
252524AE2-267 GEN
Solar/Wind Harmer
1.441
252516AE2-318_GEN
Solar/Wind Harmer
9.203
252519AF1-045_GEN
Solar/Wind Harmer
3.349
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
339216AC1-074 GEN
Solar/Wind Harmer
1.643
339221AD2-048_GEN
Solar/Wind Harmer
1.509
339255AE2-071 GEN
Solar/Wind Harmer
1.217
274744AC1-111 GEN8
Adder
4.868
274745AC1-111 GEN9
Adder
4.868
274746AC1-111 G10
Adder
4.868
276621W2-048 GEN
Solar/Wind Harmer
5.641
339231AF1-038_GEN
Solar/Wind Harmer
1.917
339236AF1-050_GEN
Solar/Wind Harmer
1.872
339241AF1-083 GEN
Solar/Wind Harmer
1.714
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276655WTG1_EQ
Solar/Wind Harmer
7.748
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270399AC1-101 GEN
Solar/Wind Harmer
5.554
270400AC1-102 GEN
Solar/Wind Harmer
5.554
270173AC1-122 GEN
Solar/Wind Harmer
3.444
927014AC1-188 GEN
Solar/Wind Harmer
1.527
270291AC1-194 GEN
Solar/Wind Harmer
4.532
270340AC2-060 GEN
Solar/Wind Harmer
2.685
270367AC2-061_GEN
Solar/Wind Harmer
3.002
270222AC2-111 GEN
Solar/Wind Harmer
3.991
270214AC2-123 GEN
Solar/Wind Harmer
4.31
276838X2-022 GEN2
Solar/Wind Harmer
0.21
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270336AE1-100 GEN
Solar/Wind Harmer
2.751
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270016AE1-250 BESS
Solar/Wind Harmer
3.249
270013AE1-250 PV
Solar/Wind Harmer
3.249
270018AE2-047 C O1
Solar/Wind Harmer
1.821
270030AE2-140 GEN
Solar/Wind Harmer
30.919
270069AE2-166 C O1
Solar/Wind Harmer
14.876
270356AE2-297 GEN
Solar/Wind Harmer
4.144
270053AF1-130 C
Solar/Wind Harmer
22.996
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
316006AB2-029 C
Solar/Wind Helper
0.113
316192AB2-158 GEN
Solar/Wind Helper
1.844
316123AC1-075 GEN
Solar/Wind Harmer
1.488
316164AC1-076 GEN
Solar/Wind Helper
1.176
24734705WLF1G3
Adder
8.191
24734805WLF1G4
Adder
8.191
24734905WLF1G5
Adder
8.191
24735105WLF2G1
Adder
8.021
24735205WLF2G2
Adder
8.021
270186AC1-089 GEN
Solar/Wind Harmer
5.816
339250AF1-203 GEN
Solar/Wind Harmer
0.627
253406AD2-031_GEN
Solar/Wind Harmer
1.146
316197AC1-042 GEN
Solar/Wind Harmer
3.216
316217AC1-145 GEN
Solar/Wind Harmer
4.242
276615X2-022 GEN
Solar/Wind Harmer
1.772
274880W4-005 GEN4
Solar/Wind Harmer
2.725
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.02
316095T157 G97
Solar/Wind Helper
1.127
316097T157 G90
Solar/Wind Helper
1.127
339206AE1-143 GEN
Solar/Wind Harmer
2.203
942111AE2-223 GEN
Solar/Wind Harmer
7.277
942481AE2-261 GEN
Solar/Wind Harmer
27.222
942671AE2-283 GEN
Solar/Wind Harmer
8.665
942751AE2-291 GEN
Solar/Wind Harmer
10.38
942891AE2-308 GEN
Solar/Wind Harmer
10.171
943031AE2-326 GEN
Solar/Wind Harmer
6.783
943111AE2-339 GEN
Solar/Wind Harmer
0.882
943811AF1-049 GEN
Solar/Wind Harmer
5.695
944031AF1-071 GEN
Solar/Wind Harmer
0.898
944221AF1-090 GEN
Solar/Wind Harmer
10.021
944971AF1-162 GEN
Solar/Wind Harmer
9.064
945391AF1-204 GEN
Solar/Wind Harmer
12.715
945681AF1-233 GEN
Solar/Wind Harmer
18.311
946171AF1-282 GEN
Solar/Wind Harmer
9.068
946181AF1-283 GEN
Solar/Wind Harmer
11.789
946321AF1-296 GEN
Solar/Wind Harmer
9.297
959341AF2-225 GEN
Solar/Wind Harmer
13.316
959611AF2-252 GEN
Solar/Wind Harmer
2.072
960201AF2-311 GEN
Solar/Wind Harmer
8.92
960251AF2-316 GEN
Solar/Wind Harmer
13.38
960611AF2-352 GEN
Solar/Wind Harmer
2.072
960911AF2-382 GEN
Solar/Wind Harmer
10.944
961491AF2-440 GEN
Solar/Wind Harmer
1.965
962211AG1-066 GEN
Solar/Wind Harmer
3
962581AG1-107 GEN
Solar/Wind Harmer
4.728
962751AG1-124 GEN
Solar/Wind Harmer
18.82
966871AG1-558 GEN
Solar/Wind Helper
0.306
966881AG1-559 GEN
Solar/Wind Helper
0.313
970091AG2-072 GEN
Adder
73.991
970093AG2-073 GEN
Solar/Wind Harmer
5.442
970107AG2-081 GEN
Solar/Wind Harmer
2.99
970193AG2-126 GEN
Solar/Wind Harmer
13.686
970223AG2-152 GEN
Solar/Wind Harmer
17.666
970241AG2-163 GEN
Solar/Wind Harmer
22.421
970281AG2-184 GEN
Solar/Wind Harmer
27.117
970417AG2-272 GEN
50/50
3.733
970455AG2-298 GEN
Solar/Wind Harmer
3.519
970563AG2-360 GEN
50/50
45.815
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970823AG2-518 GEN
50/50
8.382
970879AG2-548 GEN
Solar/Wind Harmer
7.336
970879AG2-548 GEN
Solar/Wind Harmer
1.066
970913AG2-568 GEN
Solar/Wind Harmer
9.337
971061AG2-657 GEN
Solar/Wind Harmer
10.986
971073AG2-665 GEN
Solar/Wind Harmer
7.336
971073AG2-665 GEN
Solar/Wind Harmer
1.066
971125AH1-004 GEN
Solar/Wind Harmer
3.987
971191AH1-055 GEN
Solar/Wind Harmer
18.819
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
971277AH1-098 GEN
Solar/Wind Harmer
7.418
971313AH1-133 GEN
Solar/Wind Harmer
9.325
971329AH1-144 GEN
Solar/Wind Harmer
11.725
971331AH1-145 GEN
Solar/Wind Harmer
18.357
971403AH1-188 GEN
Solar/Wind Harmer
18.845
971461AH1-227 GEN
Solar/Wind Harmer
7.001
971485AH1-239 GEN
Solar/Wind Harmer
8.494
971543AH1-269 GEN
50/50
12.244
971687AH1-348 GEN
Solar/Wind Harmer
1.358
24288905REUSENS
50/50
0.056
24415905BUCK
50/50
0.033
24416005BYLLESBY
50/50
0.03
276174W4-005 GEN2
Solar/Wind Harmer
2.725
276656WTG2_EQ
Solar/Wind Harmer
1.026
276686W4-005 GEN3
Solar/Wind Harmer
2.725
276726Z2-087_GEN
Solar/Wind Harmer
7.019
276785W4-005 GEN1
Solar/Wind Harmer
2.725
939741AE1-205 GEN
Solar/Wind Harmer
17.754
941621AE2-160 GEN
Adder
4.283
941801AE2-185 GEN
Solar/Wind Harmer
9.809
957381AF2-032 GEN
Solar/Wind Harmer
1.82
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958131AF2-107 GEN
Solar/Wind Harmer
7.106
958171AF2-111 GEN
Solar/Wind Harmer
23.897
963741AG1-226 GEN
Solar/Wind Harmer
40.358
963841AG1-237 GEN
Solar/Wind Harmer
9.753
964571AG1-320 GEN
Solar/Wind Harmer
8.183
964781AG1-341 GEN
Solar/Wind Harmer
10.966
964901AG1-354 GEN
Solar/Wind Harmer
15.482
965091AG1-374 GEN
Solar/Wind Harmer
26.73
965911AG1-460 GEN
Solar/Wind Harmer
1.27
965931AG1-462 GEN
Solar/Wind Harmer
22.754
966001AG1-469 GEN
Solar/Wind Helper
0.32
966021AG1-471 GEN
Solar/Wind Harmer
5.751
966391AG1-508 GEN
Solar/Wind Harmer
6.373
971981AH1-535 GEN
Solar/Wind Harmer
12.558
971985AH1-537 GEN
Solar/Wind Harmer
17.286
971993AH1-541 GEN
Solar/Wind Harmer
8.326
972043AH1-570 GEN
Solar/Wind Harmer
2.474
972045AH1-571 GEN
Solar/Wind Harmer
1.979
972103AH1-617 GEN
Solar/Wind Harmer
25.825
972163AH1-664 GEN
Solar/Wind Harmer
9.738
972165AH1-665 GEN
Solar/Wind Harmer
7.79
972167AH1-666 GEN
Solar/Wind Harmer
7.764
972203AH1-686 GEN
Adder
2.703
972235AH1-702 GEN1
Adder
2.219
972236AH1-702 GEN2
Adder
1.93
972267AH1-718 GEN
Adder
3.687
972273AH1-721 GEN
Adder
89.284
957241AF2-018 GEN
Solar/Wind Harmer
5.755
958121AF2-106 GEN
Solar/Wind Harmer
9.404
960001AF2-291 GEN
Solar/Wind Harmer
3.112
971087AG2-675 GEN
Solar/Wind Harmer
3.32
971881AH1-461 GEN
50/50
14.973
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.604
24684305SMG1
50/50
0.796
24684405SMG2
50/50
2.196
24684505SMG3
50/50
1.342
24684605SMG4
50/50
2.211
24684705SMG5
50/50
0.845
NYPJM->LTFIMP_NY
CLTF
3.251
LGEELTFEXP_LGEE->PJM
CLTF
6.761
WECLTFEXP_WEC->PJM
CLTF
3.371
CPLELTFEXP_CPLE->PJM
CLTF
6.22
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
TVALTFEXP_TVA->PJM
CLTF
10.603
MECLTFEXP_MEC->PJM
CLTF
15.41
SIGELTFEXP_SIGE->PJM
CLTF
0.508
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.99 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:839.35
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
3151561HALLBR1
50/50
0.371
3152661PLYWOOD A
50/50
0.678
3137176SLIGO L2192
Solar/Wind Helper
0.56
3141906WESTMOR
Solar/Wind Helper
0.047
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
3142433PROV 92
Solar/Wind Helper
0.537
3142956BIRDNECK
Solar/Wind Helper
0.102
3143316POE
Solar/Wind Helper
0.625
3144356SAPONY
Solar/Wind Helper
0.23
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
3146386ELIZ CT
Solar/Wind Helper
0.129
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
3146776BUCKING
Solar/Wind Helper
0.069
3146776BUCKING
Solar/Wind Helper
0.077
316075AC2-137 C
Solar/Wind Helper
0.198
316077AC2-138 C
Solar/Wind Helper
0.118
3138133OCRAN
Solar/Wind Helper
0.04
3138133OCRAN
Solar/Wind Helper
0.08
3141766HARMONY
Solar/Wind Helper
0.027
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
3141813NORNECK
Solar/Wind Helper
0.126
3141913WHIT STONE
Solar/Wind Helper
0.133
3143226MDLTHAN
Solar/Wind Helper
0.139
3143873LANEXA
Solar/Wind Helper
0.08
3146456SLIGO L269
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.141
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
3146926FARMVIL
Solar/Wind Helper
0.144
3146926FARMVIL
Solar/Wind Helper
0.144
3147123OTTER R
Solar/Wind Harmer
0.091
3147312GRETNA
Solar/Wind Harmer
0.026
3147312GRETNA
Solar/Wind Harmer
0.104
3141726DUNNSVL
Solar/Wind Helper
0.505
316036AC1-147 C
Solar/Wind Helper
0.233
316059AD1-063 C
Solar/Wind Helper
0.135
316159AE1-175 C
Solar/Wind Helper
0.215
316240AF1-291 C
Solar/Wind Helper
0.196
316246AF1-032 C
Solar/Wind Helper
0.159
316258AE1-075 C
Solar/Wind Helper
0.189
316305AF2-043 C
Solar/Wind Helper
0.187
316315AB2-025 C
Solar/Wind Helper
0.196
316316AC1-027 C
Solar/Wind Helper
0.238
316382AG1-145 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.158
3145336SMITFLD
Solar/Wind Helper
0.594
3145336SMITFLD
Solar/Wind Helper
0.059
3146802CHATHAM
Solar/Wind Harmer
0.098
3147243WELCO
Solar/Wind Harmer
0.235
3141873WAN 176
Solar/Wind Helper
0.027
3143526WINTERP
Solar/Wind Helper
0.707
3143526WINTERP
Solar/Wind Helper
0.707
316404AE1-155 C
Solar/Wind Helper
1.096
316017AA1-139 ULT1
Solar/Wind Helper
0.653
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316033AB2-134 GEN
Solar/Wind Helper
0.498
316388AE2-253 GEN
Solar/Wind Helper
0.548
3145176PASQUOTANK
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.013
3147173SINAI
Solar/Wind Harmer
0.376
316312AB1-027
Solar/Wind Helper
0.238
316049AB1-081 GEN
Solar/Wind Harmer
0.358
316369SG1_INVT
Solar/Wind Helper
0.693
315839AE2-212 C
Solar/Wind Helper
0.203
315671AE2-027_GEN
Solar/Wind Helper
1.187
315662AE1-191 GEN
Solar/Wind Helper
0.723
315666AE1-190 GEN
Solar/Wind Helper
0.181
319010AE1-072 C
Solar/Wind Helper
1.598
315697AD1-025 GEN
Solar/Wind Helper
1.645
316185AD1-033 GEN
Solar/Wind Helper
0.708
315773AC2-141 GEN
Solar/Wind Helper
3.583
316280AD1-041 GEN
Solar/Wind Helper
0.452
316473AC1-191 GEN
Solar/Wind Helper
0.733
316478AD1-087 GEN
Solar/Wind Helper
3.078
316486AD2-202 GEN
Solar/Wind Helper
0.901
316468AD1-105 GEN
Solar/Wind Helper
0.539
316072AD1-144
Solar/Wind Helper
0.161
316156AD2-030 GEN
Solar/Wind Helper
0.203
316337AD2-073 GEN
Solar/Wind Helper
0.185
313526AB2-022
Solar/Wind Helper
0.197
316313AB2-026
Solar/Wind Helper
0.21
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
270030AE2-140 GEN
Solar/Wind Harmer
10.404
270069AE2-166 C O1
Solar/Wind Harmer
4.205
316349AD2-085 GEN
Solar/Wind Helper
0.628
316322AB2-045
Solar/Wind Helper
0.215
316359AB2-059 GEN
Solar/Wind Harmer
0.224
316132AB2-190 GEN1
Solar/Wind Helper
0.816
316458AB2-190 GEN2
Solar/Wind Helper
0.816
316263AC1-034 GEN
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
0.357
316118AC1-105 GEN
Solar/Wind Harmer
0.783
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316375AC2-012 GEN
Solar/Wind Helper
0.401
316283AC2-100 C
Solar/Wind Harmer
0.523
316339AD2-160 GEN
Solar/Wind Helper
0.548
316223AC1-118
Solar/Wind Helper
0.181
316294AC1-161 GEN
Solar/Wind Helper
3.045
315975AC1-164 GENB
Solar/Wind Helper
0.05
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
316381AD1-082 GEN
Solar/Wind Helper
0.748
316233AE1-074 FULL
Solar/Wind Helper
0.208
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145543BTLEBRO
Solar/Wind Harmer
0.05
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Helper
0.556
3142053HEARTS
Solar/Wind Harmer
0.111
3142946ENON
Solar/Wind Helper
0.013
3142946ENON
Solar/Wind Helper
0.045
3144536CHRHLND
Solar/Wind Helper
0.023
3144873MCLAUGH
Solar/Wind Helper
0.004
316320Y1-086
Solar/Wind Helper
0.058
316321Z2-027
Solar/Wind Helper
0.19
942461AE2-259 GEN
Solar/Wind Helper
1.118
942671AE2-283 GEN
Solar/Wind Harmer
3.253
942751AE2-291 GEN
Solar/Wind Harmer
13.09
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
1.126
961601AG1-000A GEN
Solar/Wind Harmer
4.503
962561AG1-105 GEN
Solar/Wind Harmer
9.76
966871AG1-558 GEN
Solar/Wind Helper
0.162
970085AG2-068 GEN
Solar/Wind Harmer
7.608
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970223AG2-152 GEN
Solar/Wind Harmer
9.427
970401AG2-262 GEN
Solar/Wind Harmer
1.37
970417AG2-272 GEN
50/50
1.9
970581AG2-369 GEN
Solar/Wind Harmer
6.542
970917AG2-570 GEN
Solar/Wind Harmer
12.677
970919AG2-571 GEN
Solar/Wind Harmer
5.071
971623AH1-311 GEN
Solar/Wind Harmer
0.126
971629AH1-314 GEN
50/50
13.585
971683AH1-343 GEN
Solar/Wind Harmer
11.986
24288905REUSENS
50/50
0.013
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
316435W1029_GEN3
Solar/Wind Helper
0.476
941801AE2-185 GEN
Solar/Wind Harmer
4.182
957601AF2-054 GEN
Solar/Wind Helper
0.18
957831AF2-077 GEN
Solar/Wind Helper
0.189
964211AG1-282 GEN
Solar/Wind Helper
0.17
964791AG1-342 GEN
Solar/Wind Harmer
4.484
971981AH1-535 GEN
Solar/Wind Harmer
2.18
24684305SMG1
50/50
0.307
24684405SMG2
50/50
0.846
24684505SMG3
50/50
0.517
24684605SMG4
50/50
0.852
24684705SMG5
50/50
0.326
316487AF1-042 GEN
Solar/Wind Helper
0.131
316484AD2-074 GEN
Solar/Wind Helper
0.25
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
CPLELTFEXP_CPLE->PJM
CLTF
11.241
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
TVALTFEXP_TVA->PJM
CLTF
4.691
MECLTFEXP_MEC->PJM
CLTF
5.364
SIGELTFEXP_SIGE->PJM
CLTF
0.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:821.61
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
3151561HALLBR1
50/50
0.371
3152661PLYWOOD A
50/50
0.678
3137176SLIGO L2192
Solar/Wind Helper
0.56
3141906WESTMOR
Solar/Wind Helper
0.047
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
3142433PROV 92
Solar/Wind Helper
0.537
3142956BIRDNECK
Solar/Wind Helper
0.102
3143316POE
Solar/Wind Helper
0.625
3144356SAPONY
Solar/Wind Helper
0.23
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
3146386ELIZ CT
Solar/Wind Helper
0.129
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
3146776BUCKING
Solar/Wind Helper
0.069
3146776BUCKING
Solar/Wind Helper
0.077
316075AC2-137 C
Solar/Wind Helper
0.198
316077AC2-138 C
Solar/Wind Helper
0.118
3138133OCRAN
Solar/Wind Helper
0.04
3138133OCRAN
Solar/Wind Helper
0.08
3141766HARMONY
Solar/Wind Helper
0.027
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
3141813NORNECK
Solar/Wind Helper
0.126
3141913WHIT STONE
Solar/Wind Helper
0.133
3143226MDLTHAN
Solar/Wind Helper
0.139
3143873LANEXA
Solar/Wind Helper
0.08
3146456SLIGO L269
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.141
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
3146926FARMVIL
Solar/Wind Helper
0.144
3146926FARMVIL
Solar/Wind Helper
0.144
3147123OTTER R
Solar/Wind Harmer
0.091
3147312GRETNA
Solar/Wind Harmer
0.026
3147312GRETNA
Solar/Wind Harmer
0.104
3141726DUNNSVL
Solar/Wind Helper
0.505
316036AC1-147 C
Solar/Wind Helper
0.233
316059AD1-063 C
Solar/Wind Helper
0.135
316159AE1-175 C
Solar/Wind Helper
0.215
316240AF1-291 C
Solar/Wind Helper
0.196
316246AF1-032 C
Solar/Wind Helper
0.159
316258AE1-075 C
Solar/Wind Helper
0.189
316305AF2-043 C
Solar/Wind Helper
0.187
316315AB2-025 C
Solar/Wind Helper
0.196
316316AC1-027 C
Solar/Wind Helper
0.238
316382AG1-145 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.158
3145336SMITFLD
Solar/Wind Helper
0.594
3145336SMITFLD
Solar/Wind Helper
0.059
3146802CHATHAM
Solar/Wind Harmer
0.098
3147243WELCO
Solar/Wind Harmer
0.235
3141873WAN 176
Solar/Wind Helper
0.027
3143526WINTERP
Solar/Wind Helper
0.707
3143526WINTERP
Solar/Wind Helper
0.707
316404AE1-155 C
Solar/Wind Helper
1.096
316017AA1-139 ULT1
Solar/Wind Helper
0.653
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316033AB2-134 GEN
Solar/Wind Helper
0.498
316388AE2-253 GEN
Solar/Wind Helper
0.548
3145176PASQUOTANK
Solar/Wind Helper
0.077
3142543TWELFTH
Solar/Wind Helper
0.013
3147173SINAI
Solar/Wind Harmer
0.376
316312AB1-027
Solar/Wind Helper
0.238
316049AB1-081 GEN
Solar/Wind Harmer
0.358
316369SG1_INVT
Solar/Wind Helper
0.693
315839AE2-212 C
Solar/Wind Helper
0.203
315671AE2-027_GEN
Solar/Wind Helper
1.187
315662AE1-191 GEN
Solar/Wind Helper
0.723
315666AE1-190 GEN
Solar/Wind Helper
0.181
319010AE1-072 C
Solar/Wind Helper
1.598
315697AD1-025 GEN
Solar/Wind Helper
1.645
316185AD1-033 GEN
Solar/Wind Helper
0.708
315773AC2-141 GEN
Solar/Wind Helper
3.583
316280AD1-041 GEN
Solar/Wind Helper
0.452
316473AC1-191 GEN
Solar/Wind Helper
0.733
316478AD1-087 GEN
Solar/Wind Helper
3.078
316486AD2-202 GEN
Solar/Wind Helper
0.901
316468AD1-105 GEN
Solar/Wind Helper
0.539
316072AD1-144
Solar/Wind Helper
0.161
316156AD2-030 GEN
Solar/Wind Helper
0.203
316337AD2-073 GEN
Solar/Wind Helper
0.185
313526AB2-022
Solar/Wind Helper
0.197
316313AB2-026
Solar/Wind Helper
0.21
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
270030AE2-140 GEN
Solar/Wind Harmer
10.404
270069AE2-166 C O1
Solar/Wind Harmer
4.205
316349AD2-085 GEN
Solar/Wind Helper
0.628
316322AB2-045
Solar/Wind Helper
0.215
316359AB2-059 GEN
Solar/Wind Harmer
0.224
316132AB2-190 GEN1
Solar/Wind Helper
0.816
316458AB2-190 GEN2
Solar/Wind Helper
0.816
316263AC1-034 GEN
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
0.357
316118AC1-105 GEN
Solar/Wind Harmer
0.783
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316375AC2-012 GEN
Solar/Wind Helper
0.401
316283AC2-100 C
Solar/Wind Harmer
0.523
316339AD2-160 GEN
Solar/Wind Helper
0.548
316223AC1-118
Solar/Wind Helper
0.181
316294AC1-161 GEN
Solar/Wind Helper
3.045
315975AC1-164 GENB
Solar/Wind Helper
0.05
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
316381AD1-082 GEN
Solar/Wind Helper
0.748
316233AE1-074 FULL
Solar/Wind Helper
0.208
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145543BTLEBRO
Solar/Wind Harmer
0.05
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Helper
0.556
3142053HEARTS
Solar/Wind Harmer
0.111
3142946ENON
Solar/Wind Helper
0.013
3142946ENON
Solar/Wind Helper
0.045
3144536CHRHLND
Solar/Wind Helper
0.023
3144873MCLAUGH
Solar/Wind Helper
0.004
316320Y1-086
Solar/Wind Helper
0.058
316321Z2-027
Solar/Wind Helper
0.19
942461AE2-259 GEN
Solar/Wind Helper
1.118
942671AE2-283 GEN
Solar/Wind Harmer
3.253
942751AE2-291 GEN
Solar/Wind Harmer
13.09
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
1.126
961601AG1-000A GEN
Solar/Wind Harmer
4.503
962561AG1-105 GEN
Solar/Wind Harmer
9.76
966871AG1-558 GEN
Solar/Wind Helper
0.162
970085AG2-068 GEN
Solar/Wind Harmer
7.608
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970223AG2-152 GEN
Solar/Wind Harmer
9.427
970401AG2-262 GEN
Solar/Wind Harmer
1.37
970417AG2-272 GEN
50/50
1.9
970581AG2-369 GEN
Solar/Wind Harmer
6.542
971623AH1-311 GEN
Solar/Wind Harmer
0.126
971629AH1-314 GEN
50/50
13.585
971683AH1-343 GEN
Solar/Wind Harmer
11.986
24288905REUSENS
50/50
0.013
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
316435W1029_GEN3
Solar/Wind Helper
0.476
941801AE2-185 GEN
Solar/Wind Harmer
4.182
957601AF2-054 GEN
Solar/Wind Helper
0.18
957831AF2-077 GEN
Solar/Wind Helper
0.189
964211AG1-282 GEN
Solar/Wind Helper
0.17
964791AG1-342 GEN
Solar/Wind Harmer
4.484
971981AH1-535 GEN
Solar/Wind Harmer
2.18
24684305SMG1
50/50
0.307
24684405SMG2
50/50
0.846
24684505SMG3
50/50
0.517
24684605SMG4
50/50
0.852
24684705SMG5
50/50
0.326
316487AF1-042 GEN
Solar/Wind Helper
0.131
316484AD2-074 GEN
Solar/Wind Helper
0.25
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
CPLELTFEXP_CPLE->PJM
CLTF
11.241
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
TVALTFEXP_TVA->PJM
CLTF
4.691
MECLTFEXP_MEC->PJM
CLTF
5.364
SIGELTFEXP_SIGE->PJM
CLTF
0.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
242519 to 314912 ckt 1
315684 to 314690 ckt 1

Winter Peak Analysis

The New Service Request AG2-272 was evaluated as a 55.0 MW (21.3 MW Capacity) injection in the AEP area.

AG2-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 55.0 MW (55.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC121.81 %652.36B794.66
1.82
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC120.43 %652.36B785.66
1.82

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:794.66
MW Contribution:
1.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.46 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:824.95
MW Contribution:
2.03
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
970917AG2-570 GEN
Solar/Wind Harmer
3.01
970919AG2-571 GEN
Solar/Wind Harmer
6.019
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.43 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:785.66
MW Contribution:
1.82
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.53 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:812.37
MW Contribution:
2.03
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-272 was evaluated as a 55.0 MW injection and 55.0 MW withdrawal in the AEP area.

AG2-272 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 55.0 MW (55.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
8.43
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
8.43
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
8.43
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
8.43
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
6.33
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
6.33
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
6.33
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
7.23
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
6.19
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
6.19
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
6.21
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC106.94 %508.54B543.83
4.75

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
8.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.823
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
8.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
971981AH1-535 GEN
Solar/Wind Harmer
6.611
316044AC1-158 PL1
Solar/Wind Helper
2.309
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
270399AC1-101 GEN
Solar/Wind Harmer
1.686
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
315616AA1-038_C
Solar/Wind Helper
1.962
316382AG1-145 C
Solar/Wind Helper
0.541
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971981AH1-535 GEN
Solar/Wind Harmer
7.212
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.175
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316405AF2-144 C
Solar/Wind Helper
0.49
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.581
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.258
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
971881AH1-461 GEN
50/50
14.324
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316447AC1-158 HLD
Solar/Wind Helper
5.08
316192AB2-158 GEN
Solar/Wind Helper
2.765
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.388
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.436
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.824
971277AH1-098 GEN
Solar/Wind Harmer
4.144
270494AE1-108_GEN
Solar/Wind Helper
5.58
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.178
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
8.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
23.682
972293SS25-0014
50/50
Charging
57.048
270346AE1-212 GEN
Solar/Wind Harmer
8.185
971981AH1-535 GEN
Solar/Wind Harmer
6.61
316044AC1-158 PL1
Solar/Wind Helper
2.31
944491AF1-114 GEN
Solar/Wind Helper
2.859
316487AF1-042 GEN
Solar/Wind Helper
1.167
316280AD1-041 GEN
Solar/Wind Helper
1.389
270399AC1-101 GEN
Solar/Wind Harmer
1.686
970417AG2-272 GEN
50/50
8.425
270069AE2-166 C O1
Solar/Wind Harmer
8.425
966001AG1-469 GEN
Solar/Wind Helper
0.424
315616AA1-038_C
Solar/Wind Helper
2.018
316382AG1-145 C
Solar/Wind Helper
0.541
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971981AH1-535 GEN
Solar/Wind Harmer
7.211
316450AC1-158 RIC
Solar/Wind Helper
0.616
957971AF2-091 GEN
Solar/Wind Helper
0.972
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.368
970365AG2-240 GEN
50/50
Charging
1.247
316405AF2-144 C
50/50
Charging
1.177
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971461AH1-227 GEN
Solar/Wind Harmer
4.168
316405AF2-144 C
Solar/Wind Helper
0.491
316404AE1-155 C
Solar/Wind Helper
3.567
315662AE1-191 GEN
Solar/Wind Helper
2.223
971543AH1-269 GEN
50/50
11.496
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.229
315821AE2-092 GEN
Solar/Wind Helper
3.841
316258AE1-075 C
Solar/Wind Helper
0.52
970563AG2-360 GEN
50/50
45.014
972273AH1-721 GEN
50/50
85.068
316468AD1-105 GEN
Solar/Wind Helper
2.227
316312AB1-027
Solar/Wind Helper
0.748
316075AC2-137 C
Solar/Wind Helper
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.554
963031AG1-152 GEN
50/50
Charging
10.856
960911AF2-382 GEN
Solar/Wind Harmer
6.616
270030AE2-140 GEN
Solar/Wind Harmer
17.478
316059AD1-063 C
Solar/Wind Helper
0.419
971507AH1-251 GEN
50/50
Charging
5.867
957191AF2-013 GEN
50/50
Charging
10.663
943031AE2-326 GEN
Solar/Wind Harmer
11.708
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
966881AG1-559 GEN
Solar/Wind Helper
0.447
316473AC1-191 GEN
Solar/Wind Helper
2.43
315651AD1-115 GEN
Solar/Wind Helper
4.205
315975AC1-164 GENB
Solar/Wind Helper
0.061
961951AG1-038 GEN
Solar/Wind Helper
1.26
971881AH1-461 GEN
50/50
14.323
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
316303AF2-085
50/50
Charging
2.246
270583AD2-179 GEN
Solar/Wind Harmer
12.446
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.746
972103AH1-617 GEN
Solar/Wind Harmer
14.996
316447AC1-158 HLD
Solar/Wind Helper
5.083
316192AB2-158 GEN
Solar/Wind Helper
2.769
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
316045AC1-158 PL2
Solar/Wind Helper
7.393
316233AE1-074 FULL
Solar/Wind Helper
0.6
270400AC1-102 GEN
Solar/Wind Harmer
1.686
966871AG1-558 GEN
Solar/Wind Helper
0.437
316337AD2-073 GEN
Solar/Wind Helper
0.564
315666AE1-190 GEN
Solar/Wind Helper
0.556
970119AG2-088 GEN
50/50
Charging
16.846
971277AH1-098 GEN
Solar/Wind Harmer
4.143
270494AE1-108_GEN
Solar/Wind Helper
5.59
316164AC1-076 GEN
Solar/Wind Helper
1.941
316313AB2-026
Solar/Wind Helper
0.578
316223AC1-118
Solar/Wind Helper
0.568
316203AE2-005 GEN
Solar/Wind Helper
3.62
316156AD2-030 GEN
Solar/Wind Helper
0.548
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
CPLELTFEXP_CPLE->PJM
CLTF
4.745
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
NYPJM->LTFIMP_NY
CLTF
2.177
TVALTFEXP_TVA->PJM
CLTF
9.524
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
LGEELTFEXP_LGEE->PJM
CLTF
5.764
MECLTFEXP_MEC->PJM
CLTF
13.347
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
WECLTFEXP_WEC->PJM
CLTF
2.895
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
8.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
23.667
972293SS25-0014
50/50
Charging
57.012
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270399AC1-101 GEN
Solar/Wind Harmer
3.469
944491AF1-114 GEN
Solar/Wind Helper
2.856
316487AF1-042 GEN
Solar/Wind Helper
1.165
316280AD1-041 GEN
Solar/Wind Helper
1.388
970417AG2-272 GEN
50/50
8.428
270069AE2-166 C O1
Solar/Wind Harmer
8.427
966001AG1-469 GEN
Solar/Wind Helper
0.423
316382AG1-145 C
Solar/Wind Helper
0.541
315616AA1-038_C
Solar/Wind Helper
1.957
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
17.216
957971AF2-091 GEN
Solar/Wind Helper
0.971
316159AE1-175 C
Solar/Wind Helper
0.538
970823AG2-518 GEN
50/50
19.371
970365AG2-240 GEN
50/50
Charging
1.246
316405AF2-144 C
50/50
Charging
1.174
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971461AH1-227 GEN
Solar/Wind Harmer
4.169
316404AE1-155 C
Solar/Wind Helper
3.563
315662AE1-191 GEN
Solar/Wind Helper
2.22
971543AH1-269 GEN
50/50
11.498
971313AH1-133 GEN
Solar/Wind Harmer
6.407
964211AG1-282 GEN
Solar/Wind Helper
0.564
316484AD2-074 GEN
Solar/Wind Helper
2.227
315821AE2-092 GEN
Solar/Wind Helper
3.827
316258AE1-075 C
Solar/Wind Helper
0.519
970563AG2-360 GEN
50/50
45.019
972273AH1-721 GEN
50/50
85.07
316468AD1-105 GEN
Solar/Wind Helper
2.225
316075AC2-137 C
Solar/Wind Helper
0.581
971687AH1-348 GEN
Solar/Wind Harmer
0.807
316077AC2-138 C
Solar/Wind Helper
0.394
316314AB2-024 C
Solar/Wind Helper
0.561
316441AF1-014 GEN
Solar/Wind Helper
0.553
963031AG1-152 GEN
50/50
Charging
10.85
960911AF2-382 GEN
Solar/Wind Harmer
6.617
270030AE2-140 GEN
Solar/Wind Harmer
17.484
316059AD1-063 C
Solar/Wind Helper
0.418
971507AH1-251 GEN
50/50
Charging
5.863
957191AF2-013 GEN
50/50
Charging
10.655
943031AE2-326 GEN
Solar/Wind Harmer
11.709
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
316473AC1-191 GEN
Solar/Wind Helper
2.427
315651AD1-115 GEN
Solar/Wind Helper
4.201
961951AG1-038 GEN
Solar/Wind Helper
1.258
971881AH1-461 GEN
50/50
14.324
316303AF2-085
50/50
Charging
2.243
270583AD2-179 GEN
Solar/Wind Harmer
12.447
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
15.747
972103AH1-617 GEN
Solar/Wind Harmer
14.997
316192AB2-158 GEN
Solar/Wind Helper
2.765
941621AE2-160 GEN
50/50
6.64
970913AG2-568 GEN
Solar/Wind Harmer
5.92
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270053AF1-130 C
Solar/Wind Harmer
12.797
316233AE1-074 FULL
Solar/Wind Helper
0.6
957241AF2-018 GEN
Solar/Wind Harmer
0
316337AD2-073 GEN
Solar/Wind Helper
0.563
315666AE1-190 GEN
Solar/Wind Helper
0.555
970119AG2-088 GEN
50/50
Charging
16.823
270494AE1-108_GEN
Solar/Wind Helper
5.579
316164AC1-076 GEN
Solar/Wind Helper
1.94
316313AB2-026
Solar/Wind Helper
0.577
316223AC1-118
Solar/Wind Helper
0.567
316203AE2-005 GEN
Solar/Wind Helper
3.616
316156AD2-030 GEN
Solar/Wind Helper
0.548
944971AF1-162 GEN
Solar/Wind Harmer
2.093
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971403AH1-188 GEN
Solar/Wind Harmer
10.665
316006AB2-029 C
Solar/Wind Helper
0.541
957601AF2-054 GEN
Solar/Wind Helper
0.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
CPLELTFEXP_CPLE->PJM
CLTF
4.752
SIGELTFEXP_SIGE->PJM
CLTF
0.438
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
NYPJM->LTFIMP_NY
CLTF
2.179
TVALTFEXP_TVA->PJM
CLTF
9.526
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
LGEELTFEXP_LGEE->PJM
CLTF
5.763
MECLTFEXP_MEC->PJM
CLTF
13.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
WECLTFEXP_WEC->PJM
CLTF
2.894
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
6.33
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
6.33
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
316044AC1-158 PL1
Solar/Wind Helper
2.181
944491AF1-114 GEN
Solar/Wind Helper
2.702
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
316450AC1-158 RIC
Solar/Wind Helper
0.582
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
316312AB1-027
Solar/Wind Helper
0.693
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
966881AG1-559 GEN
Solar/Wind Helper
0.418
316473AC1-191 GEN
Solar/Wind Helper
2.25
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
316447AC1-158 HLD
Solar/Wind Helper
4.798
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
316045AC1-158 PL2
Solar/Wind Helper
6.979
957241AF2-018 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.404
971277AH1-098 GEN
Solar/Wind Harmer
3.312
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
944971AF1-162 GEN
Solar/Wind Harmer
10.409
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
6.33
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
22.363
972293SS25-0014
50/50
Charging
53.849
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270399AC1-101 GEN
Solar/Wind Harmer
3.156
944491AF1-114 GEN
Solar/Wind Helper
2.702
970417AG2-272 GEN
50/50
6.326
270069AE2-166 C O1
Solar/Wind Harmer
6.316
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.165
957971AF2-091 GEN
Solar/Wind Helper
0.919
970823AG2-518 GEN
50/50
14.083
970365AG2-240 GEN
50/50
Charging
1.154
966391AG1-508 GEN
Solar/Wind Harmer
8.202
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971543AH1-269 GEN
50/50
8.594
971313AH1-133 GEN
Solar/Wind Harmer
5.386
970563AG2-360 GEN
50/50
37.854
972273AH1-721 GEN
50/50
76.948
316468AD1-105 GEN
Solar/Wind Helper
2.079
963031AG1-152 GEN
50/50
Charging
10.244
960911AF2-382 GEN
Solar/Wind Harmer
5.69
270030AE2-140 GEN
Solar/Wind Harmer
3.161
971507AH1-251 GEN
50/50
Charging
5.466
957191AF2-013 GEN
50/50
Charging
10.139
943031AE2-326 GEN
Solar/Wind Harmer
9.448
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
316473AC1-191 GEN
Solar/Wind Helper
2.25
971687AH1-348 GEN
Solar/Wind Harmer
0.705
971881AH1-461 GEN
50/50
11.944
270583AD2-179 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
14.006
972103AH1-617 GEN
Solar/Wind Harmer
13.339
941621AE2-160 GEN
50/50
5.904
970913AG2-568 GEN
Solar/Wind Harmer
5.207
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270053AF1-130 C
Solar/Wind Harmer
11.711
957241AF2-018 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
12.03
270494AE1-108_GEN
Solar/Wind Helper
4.816
316164AC1-076 GEN
Solar/Wind Helper
1.745
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971403AH1-188 GEN
Solar/Wind Harmer
9.621
316006AB2-029 C
Solar/Wind Helper
0.504
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
NYPJM->LTFIMP_NY
CLTF
2.2
TVALTFEXP_TVA->PJM
CLTF
8.341
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
LGEELTFEXP_LGEE->PJM
CLTF
5.464
MECLTFEXP_MEC->PJM
CLTF
12.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
WECLTFEXP_WEC->PJM
CLTF
2.768
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
CPLELTFEXP_CPLE->PJM
CLTF
3.423
SIGELTFEXP_SIGE->PJM
CLTF
0.412

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
7.23
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
20.999
972293SS25-0014
50/50
Charging
50.508
270346AE1-212 GEN
Solar/Wind Harmer
6.338
971981AH1-535 GEN
Solar/Wind Harmer
5.175
316044AC1-158 PL1
Solar/Wind Helper
2.046
970417AG2-272 GEN
50/50
7.231
270069AE2-166 C O1
Solar/Wind Harmer
7.142
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971981AH1-535 GEN
Solar/Wind Harmer
5.645
316450AC1-158 RIC
Solar/Wind Helper
0.545
970823AG2-518 GEN
50/50
14.96
966391AG1-508 GEN
Solar/Wind Harmer
7.933
942671AE2-283 GEN
Solar/Wind Harmer
3.623
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971543AH1-269 GEN
50/50
8.911
971313AH1-133 GEN
Solar/Wind Harmer
4.952
3146802CHATHAM
Solar/Wind Harmer
0.256
3147312GRETNA
Solar/Wind Harmer
0.068
970563AG2-360 GEN
50/50
34.767
962751AG1-124 GEN
Solar/Wind Harmer
6.233
3147312GRETNA
Solar/Wind Harmer
0.273
971687AH1-348 GEN
Solar/Wind Harmer
0.626
270030AE2-140 GEN
Solar/Wind Harmer
14.894
960911AF2-382 GEN
Solar/Wind Harmer
5.121
971507AH1-251 GEN
50/50
Charging
5.111
943031AE2-326 GEN
Solar/Wind Harmer
9.019
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
966881AG1-559 GEN
Solar/Wind Helper
0.39
971881AH1-461 GEN
50/50
11.072
270583AD2-179 GEN
Solar/Wind Harmer
9.646
943811AF1-049 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.188
316447AC1-158 HLD
Solar/Wind Helper
4.5
970281AG2-184 GEN
Solar/Wind Harmer
11.543
941621AE2-160 GEN
50/50
5.119
970913AG2-568 GEN
Solar/Wind Harmer
4.573
316045AC1-158 PL2
Solar/Wind Helper
6.545
961131AF2-404 GEN
Solar/Wind Harmer
2.357
971277AH1-098 GEN
Solar/Wind Harmer
3.215
941801AE2-185 GEN
Solar/Wind Harmer
4.102
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.261
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
WECLTFEXP_WEC->PJM
CLTF
2.293
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
CPLELTFEXP_CPLE->PJM
CLTF
4.184
SIGELTFEXP_SIGE->PJM
CLTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
NYPJM->LTFIMP_NY
CLTF
1.786
TVALTFEXP_TVA->PJM
CLTF
7.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
LGEELTFEXP_LGEE->PJM
CLTF
4.54
MECLTFEXP_MEC->PJM
CLTF
10.573
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
6.19
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
316450AC1-158 RIC
Solar/Wind Helper
0.529
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
970563AG2-360 GEN
50/50
35.173
971687AH1-348 GEN
Solar/Wind Harmer
0.633
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971881AH1-461 GEN
50/50
11.185
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
941621AE2-160 GEN
50/50
5.212
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
961131AF2-404 GEN
50/50
Charging
2.924
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
6.19
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
20.391
972293SS25-0014
50/50
Charging
48.973
270346AE1-212 GEN
Solar/Wind Harmer
6.395
971981AH1-535 GEN
Solar/Wind Harmer
5.117
316217AC1-145 GEN
Solar/Wind Helper
1.974
316044AC1-158 PL1
Solar/Wind Helper
1.983
270399AC1-101 GEN
Solar/Wind Harmer
1.329
970417AG2-272 GEN
50/50
6.193
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971981AH1-535 GEN
Solar/Wind Harmer
5.582
316450AC1-158 RIC
Solar/Wind Helper
0.529
970823AG2-518 GEN
50/50
14.895
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971543AH1-269 GEN
50/50
8.871
971313AH1-133 GEN
Solar/Wind Harmer
5.006
970563AG2-360 GEN
50/50
35.173
960911AF2-382 GEN
Solar/Wind Harmer
5.18
270030AE2-140 GEN
Solar/Wind Harmer
12.927
971687AH1-348 GEN
Solar/Wind Harmer
0.633
943031AE2-326 GEN
Solar/Wind Harmer
9.122
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971881AH1-461 GEN
50/50
11.185
270583AD2-179 GEN
Solar/Wind Harmer
9.612
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.374
972103AH1-617 GEN
Solar/Wind Harmer
11.785
316447AC1-158 HLD
Solar/Wind Helper
4.364
941621AE2-160 GEN
50/50
5.212
970913AG2-568 GEN
Solar/Wind Harmer
4.649
316045AC1-158 PL2
Solar/Wind Helper
6.347
270400AC1-102 GEN
Solar/Wind Harmer
1.329
961131AF2-404 GEN
50/50
Charging
2.924
971277AH1-098 GEN
Solar/Wind Harmer
3.223
270494AE1-108_GEN
Solar/Wind Helper
5.948
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971403AH1-188 GEN
Solar/Wind Harmer
8.401
270173AC1-122 GEN
Solar/Wind Helper
2.76
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
LGEELTFEXP_LGEE->PJM
CLTF
4.594
MECLTFEXP_MEC->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
WECLTFEXP_WEC->PJM
CLTF
2.32
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
CPLELTFEXP_CPLE->PJM
CLTF
3.013
SIGELTFEXP_SIGE->PJM
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
NYPJM->LTFIMP_NY
CLTF
1.631
TVALTFEXP_TVA->PJM
CLTF
7.367
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
6.21
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
Charging
20.247
972293SS25-0014
50/50
Charging
48.638
270346AE1-212 GEN
Solar/Wind Harmer
6.24
971981AH1-535 GEN
Solar/Wind Harmer
5.078
316044AC1-158 PL1
Solar/Wind Helper
1.97
270399AC1-101 GEN
Solar/Wind Harmer
1.311
970417AG2-272 GEN
50/50
6.208
270069AE2-166 C O1
Solar/Wind Harmer
6.298
958121AF2-106 GEN
Solar/Wind Harmer
0
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971981AH1-535 GEN
Solar/Wind Harmer
5.54
316450AC1-158 RIC
Solar/Wind Helper
0.525
970823AG2-518 GEN
50/50
14.377
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971543AH1-269 GEN
50/50
8.605
971313AH1-133 GEN
Solar/Wind Harmer
4.935
970563AG2-360 GEN
50/50
34.746
960911AF2-382 GEN
Solar/Wind Harmer
5.113
270030AE2-140 GEN
Solar/Wind Harmer
12.937
971687AH1-348 GEN
Solar/Wind Harmer
0.625
943031AE2-326 GEN
Solar/Wind Harmer
9.004
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
971881AH1-461 GEN
50/50
11.002
270583AD2-179 GEN
Solar/Wind Harmer
9.325
943811AF1-049 GEN
Solar/Wind Harmer
0
970281AG2-184 GEN
Solar/Wind Harmer
12.222
972103AH1-617 GEN
Solar/Wind Harmer
11.64
316447AC1-158 HLD
Solar/Wind Helper
4.334
941621AE2-160 GEN
50/50
5.101
970913AG2-568 GEN
Solar/Wind Harmer
4.564
316045AC1-158 PL2
Solar/Wind Helper
6.303
270400AC1-102 GEN
Solar/Wind Harmer
1.311
971277AH1-098 GEN
Solar/Wind Harmer
3.175
270494AE1-108_GEN
Solar/Wind Helper
4.907
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971403AH1-188 GEN
Solar/Wind Harmer
8.284
270173AC1-122 GEN
Solar/Wind Helper
2.227
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
CPLELTFEXP_CPLE->PJM
CLTF
3.149
SIGELTFEXP_SIGE->PJM
CLTF
0.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
NYPJM->LTFIMP_NY
CLTF
1.636
TVALTFEXP_TVA->PJM
CLTF
7.32
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
LGEELTFEXP_LGEE->PJM
CLTF
4.537
MECLTFEXP_MEC->PJM
CLTF
10.492
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
WECLTFEXP_WEC->PJM
CLTF
2.291
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.94 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:543.83
MW Contribution:
4.75
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:98.78 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:502.35
MW Contribution:
5.3
Bus #Bus NameTypeMW Contribution
970087AG2-069 GEN
Solar/Wind Harmer
13.179
970223AG2-152 GEN
Solar/Wind Harmer
7.548
3145493TOT1
Solar/Wind Harmer
0.093
315785AD2-033 C
Solar/Wind Helper
4.863
970417AG2-272 GEN
50/50
4.749
270069AE2-166 C O1
Solar/Wind Harmer
3.464
3145493TOT1
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
0.11
970581AG2-369 GEN
Solar/Wind Harmer
7.556
970917AG2-570 GEN
Solar/Wind Harmer
35.142
3146233WITAKRS
Solar/Wind Harmer
0.388
313527AB2-043 GEN
Solar/Wind Helper
2.145
970533AG2-339 GEN
50/50
Charging
6.339
3146233WITAKRS
Solar/Wind Harmer
0.644
316263AC1-034 GEN
Solar/Wind Harmer
3
3145573BETHELC
Solar/Wind Harmer
0.179
3145603CNETO
Solar/Wind Harmer
0.037
316237AB2-079_GEN
Solar/Wind Helper
0.871
316238AB2-078_GEN
Solar/Wind Helper
0.871
316239AB2-077_GEN
Solar/Wind Helper
0.871
970413AG2-270 GEN
50/50
Charging
32.533
970909AG2-566 GEN
50/50
Charging
4
316034AC1-036 C
Solar/Wind Helper
0.583
972287SS25-0012
50/50
Charging
12.035
3145573BETHELC
Solar/Wind Harmer
0.179
315687AD1-152 GEN
Solar/Wind Helper
6.672
942461AE2-259 GEN
Solar/Wind Helper
3.41
957861AF2-080 GEN
Solar/Wind Harmer
2.209
316248AF1-058 C
Solar/Wind Helper
1.749
316123AC1-075 GEN
Solar/Wind Helper
4.393
316322AB2-045
Solar/Wind Helper
0.467
270030AE2-140 GEN
Solar/Wind Harmer
9.106
316283AC2-100 C
Solar/Wind Helper
13.194
963041AG1-153 GEN
50/50
Charging
6.303
3146083TARBORO
Solar/Wind Harmer
0.179
3138543CONSLDL
Solar/Wind Harmer
0.11
316222AC1-221 GEN
Solar/Wind Helper
14.01
316486AD2-202 GEN
Solar/Wind Helper
1.11
316131AB2-060 GEN
Solar/Wind Helper
3.422
316129AC1-054 GEN
Solar/Wind Helper
1.247
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.079
3146083TARBORO
Solar/Wind Harmer
0.179
316478AD1-087 GEN
Solar/Wind Helper
3.79
971629AH1-314 GEN
50/50
14.885
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.179
316003AC1-222 GEN
Solar/Wind Helper
5.199
970085AG2-068 GEN
Solar/Wind Harmer
8.786
970919AG2-571 GEN
Solar/Wind Harmer
15.147
316118AC1-105 GEN
Solar/Wind Helper
3.992
3145543BTLEBRO
Solar/Wind Harmer
0.199
315773AC2-141 GEN
Solar/Wind Helper
3.009
970535AG2-341 GEN
50/50
Charging
6.366
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.159
961671AG1-007 GEN
Solar/Wind Harmer
0.336
3145453TOT5
Solar/Wind Harmer
0.056
900033ID_568986
External Queue
3.581075668334961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.634
NYPJM->LTFIMP_NY
CLTF
0.225
TVALTFEXP_TVA->PJM
CLTF
4.608
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.544
LGEELTFEXP_LGEE->PJM
CLTF
1.613
MECLTFEXP_MEC->PJM
CLTF
4.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.814
WECLTFEXP_WEC->PJM
CLTF
0.882
LAGNLTFEXP_LAGN->PJM
CLTF
9.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.766
CPLELTFEXP_CPLE->PJM
CLTF
11.877
SIGELTFEXP_SIGE->PJM
CLTF
0.136
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
290614 to 242515 ckt 1
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-152, AG2-272, AG2-518, AH1-098, AH1-144, AH1-145, AH1-269 and AH1-314 in PJM Transition Cycle 2, Cluster 24 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 24 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 24 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 24 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-098 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-098 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-098 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-098 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 24 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 24 projects have been dispatched online at maximum power output, with 1.01 pu voltage at the terminal bus.

 

Transition Cycle 2 Cluster 24 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 24 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 24 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 24 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 24 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Tripping was observed for several contingencies (P4.081, P4.082, P5.39, and P5.48) under the initial study conditions. Upon updating the fault impedance values based on Aspen short circuit case, the tripping issues were resolved, and the system remained stable for these contingencies.

 

AH1-098 both Solar and BESS units tripped under several contingencies. Upon updating Vdip to 0.8 (Original value was 0.9) and Vup to 1.2 (Original value was 1.1) for both units resolved all tripping issue.

 

Fictitious frequency response at AH1-145 generator bus tripped the queue project for several contingencies (P1.073, P1.075 and P1.076). Therefore, the frequency relay pickup times for were set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

AG2-272 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.15 (original value was 0) which resolved the slow reactive power response.

 

AH1-269 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

AH1-314 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

The active power for AG2-152 did not recover to the pre fault value for contingency P7.21 due inadequate reactive power response. The reactive power droop compensation gain Kc parameter was updated to 0.1 which resolved the active power recovery issue.

 

Smith Mountain generators showed positively damped oscillations which did not settle during the 20 second simulation window. The selected contingencies were run for 30 seconds, and the oscillatory signals achieved a flat response at the end of the 30 second simulation time period.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 24 Queues

Table 1: Transition Cycle 2 Cluster 24 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-152

Solar

AEP

131

Banister – Bearskin 138 kV

AG2-272

Battery

AEP

55

Berry Hill substation 138 kV

AG2-518

Battery

AEP

80

Tech Drive substation 138 kV

AH1-098

Solar/Battery

AEP

40

West Carroll – Wolf Glade 138 kV

AH1-144

Solar

AEP

70

Peter’s Mountain Substation 138 kV

AH1-145

Battery

AEP

80

Peter’s Mountain Substation 138 kV

AH1-269

Battery

AEP

50

Claytor substation 138 kV

AH1-314

Battery

AEP

100

East Danville substation 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-272 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVWithdrawn
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-382Hurley 69 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-153Heritage 500 kVUnder Construction
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-508Point Lookout 69 kVWithdrawn
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-088Midlothian 230 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-240Old Church 34.5 kVActive
AG2-270Clover 230 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-360Broadford 138 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-518Tech Drive 138 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-348Pound 34.5 kVActive
AH1-461Buckhorn 138 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-721Laurel-Cooper 161 kVActive

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-272 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-272 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-272 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A961.0 MVA
(All)B961.0 MVA
(All)C1106.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-272


AG2-272 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-272 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-272 One Line Diagram

AG2-272 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.