AG2-360 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:42

Broadford 138 kV

250.0 MW Capacity / 250.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Laurel Creek Energy Storage LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Appalachian Power Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $11,841,669 $7,992,018 = 1.48 AND ( $11,841,669 - $7,992,018 ) 250.0 = $15,399 per MW

General

The Project Developer has proposed a Storage facility located in the Appalachian Power Company zone — Smyth County, Virginia. The installed facilities will have a total capability of 250.0 MW with 250.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-360
Project Name:
Broadford 138 kV
Project Developer Name:
Laurel Creek Energy Storage LLC
State:
Virginia
County:
Smyth
Transmission Owner:
Appalachian Power Company
MFO:
250.0
MWE:
250.0
MWC:
250.0
Battery Storage Specification:
1000.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-360 will interconnect on the American Electric Power transmission system at the Broadford 138 kV Substation.

 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-360 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-360Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$2,206,040$0$0
Other Scope$750,157$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$507,722$507,722$507,722
Network Upgrades$10,178,654$10,178,654$10,178,654
System Reliability Network Upgrades
Steady State Thermal & Voltage$1,155,293$1,155,293$1,155,293
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$14,797,866$11,841,669$11,841,669

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-360

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-360
Project ID: AG2-360
20% of cost allocation for Phase II Network Upgrades:(A) $2,368,334
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,000,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,368,334
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

APCO will tie the proposed AG2-360 138 kV project into the existing Broadford 138 kV station by completing the following construction tasks: • Installation of (3) 138 kV RCVTs with (1) three-phase 138 kV RCVT structures & foundations. • Major Equipment • 1 mile of gravel access road. • Extension of one (1) span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire from the BROADFORD 138 kV Station to a take off structure in the Project Developer's collector station yard. • Installation of two 2 breaker controls at the BROADFORD 138KV 138 kV Station. • Appalachian Power Company will review and revise (as needed) the protective relay settings at the BROADFORD 138 kV Station. • Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the BROADFORD 138 kV Station. • Appalachian Power Company will install 1 mile of 144 count all dielectric self supporting (ADSS) fiber-optic cable. • Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable.

$5,749,028$2,338,037$1,461,948$629,641$10,178,654$10,178,654
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the BROADFORD 138 kV Station.

$372,255$211,684$106,855$59,363$750,157$750,157
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of Direct Fiber at the BROADFORD 138 kV Station.

$258,391$122,379$86,150$40,802$507,722$507,722
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. The APCO Interconnection Facilities will include but are not limited to the following: • Installation of one (1) new H-Frame dead-end take off structure for the generation lead circuit termination at the BROADFORD 138 kV Station. • Installation of one (1) new steel, single circuit, single pole dead end structure and one span of ACSR 556 (Dove) transmission line conductor with 7#8 Alumoweld shield wire for the generation lead circuit extending from the BROADFORD 138 kV Station.

$1,138,371$597,197$308,360$162,112$2,206,040$2,206,040
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$13,642,573$13,642,573
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-360 was evaluated as a 250.0 MW (250.0 MW Capacity) injection in the AEP area.

AG2-360 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (250.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ATKINS-05RURALR 138.0 kV Ckt 1 line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.05 %251.0B263.69
29.67
GD2AEP
05BROADF-05BROADX 138.0 kV Ckt ZB line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.1 %278.0B292.19
29.64
GD2AEP
05BROADX-05SMYTH 138.0 kV Ckt 1 line
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
BreakerAC105.23 %278.0B292.55
29.67
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
55.22
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
55.22
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC300.71 %1180.0B3548.35
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.19
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC300.69 %1180.0B3548.09
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC286.57 %1180.0B3381.47
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC286.54 %1180.0B3381.22
35.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC253.24 %1180.0B2988.23
33.92
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC241.49 %1180.0B2849.63
33.34
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC237.35 %1180.0B2800.7
32.41
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC236.49 %1180.0B2790.61
32.61
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC222.44 %1180.0A2624.74
32.44
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC217.41 %1180.0B2565.46
35.77
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC217.41 %1180.0B2565.46
35.77
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC217.41 %1180.0B2565.46
35.77
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC217.39 %1180.0B2565.21
35.77
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC189.36 %1180.0B2234.5
33.92
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC185.67 %1180.0B2190.87
32.3
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC181.67 %1180.0B2143.69
32.43
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 138KV_SRT-A
BusAC181.33 %1180.0B2139.7
32.52
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC177.62 %1180.0A2095.9
32.44
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
55.22
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
55.22
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
BreakerAC110.62 %296.0B327.42
33.38
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
BreakerAC103.73 %296.0B307.05
33.4
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P4_#2916_05J.FERR 765_A_SRT-A
BreakerAC103.45 %296.0B306.22
33.38
GD2AEP
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
AEP_P1-2_#2915_4_SRT-A
SingleAC103.16 %296.0B305.34
33.4
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
BreakerAC117.51 %296.0B347.84
33.38
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
BreakerAC110.63 %296.0B327.47
33.4
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P4_#2916_05J.FERR 765_A_SRT-A
BreakerAC110.35 %296.0B326.65
33.38
GD2AEP
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
AEP_P1-2_#2915_4_SRT-A
SingleAC107.09 %296.0B316.99
33.4

Details for 05ATKINS-05RURALR 138.0 kV Ckt 1 line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05ATKINS-05RURALR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:263.69
MW Contribution:
29.67
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05ATKINS-05RURALR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:95.89 %
Rating:251.0 MVA
Rating Type:B
MVA to Mitigate:240.68
MW Contribution:
29.49
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
3.219
24734905WLF1G5
Adder
3.219
958121AF2-106 GEN
Solar/Wind Helper
0.833
970563AG2-360 GEN
50/50
29.673
971313AH1-133 GEN
Solar/Wind Harmer
3.18
960911AF2-382 GEN
Solar/Wind Harmer
3.536
24735205WLF2G2
Adder
2.649
24734805WLF1G4
Adder
3.219
24735105WLF2G1
Adder
2.649
24728305BUCHG2
Adder
2.603
24728205BUCHG1
Adder
2.603
270214AC2-123 GEN
Solar/Wind Helper
0.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.428
WECLTFEXP_WEC->PJM
CLTF
0.248
MECLTFEXP_MEC->PJM
CLTF
1.228
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.909
LGEELTFEXP_LGEE->PJM
CLTF
0.607
TVALTFEXP_TVA->PJM
CLTF
1.158
NYPJM->LTFIMP_NY
CLTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.824

Details for 05BROADF-05BROADX 138.0 kV Ckt ZB line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05BROADF-05BROADX 138.0 kV Ckt ZB line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.1 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:292.19
MW Contribution:
29.64
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05BROADF-05BROADX 138.0 kV Ckt ZB line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:96.78 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:269.05
MW Contribution:
29.45
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
3.215
24734905WLF1G5
Adder
3.215
958121AF2-106 GEN
Solar/Wind Helper
0.832
970563AG2-360 GEN
50/50
29.636
971313AH1-133 GEN
Solar/Wind Harmer
3.176
960911AF2-382 GEN
Solar/Wind Harmer
3.532
24735205WLF2G2
Adder
2.646
24734805WLF1G4
Adder
3.215
24735105WLF2G1
Adder
2.646
24728305BUCHG2
Adder
2.6
24728205BUCHG1
Adder
2.6
270214AC2-123 GEN
Solar/Wind Helper
0.522
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.413
WECLTFEXP_WEC->PJM
CLTF
0.248
MECLTFEXP_MEC->PJM
CLTF
1.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.898
LGEELTFEXP_LGEE->PJM
CLTF
0.606
TVALTFEXP_TVA->PJM
CLTF
1.157
NYPJM->LTFIMP_NY
CLTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.159
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.822

Details for 05BROADX-05SMYTH 138.0 kV Ckt 1 line l/o AEP_P4_#3098_05BROADF 765_Q1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05BROADX-05SMYTH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:292.55
MW Contribution:
29.67
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05BROADX-05SMYTH 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3098_05BROADF 765_Q1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:96.9 %
Rating:278.0 MVA
Rating Type:B
MVA to Mitigate:269.39
MW Contribution:
29.49
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
3.219
24734905WLF1G5
Adder
3.219
958121AF2-106 GEN
Solar/Wind Helper
0.833
970563AG2-360 GEN
50/50
29.673
971313AH1-133 GEN
Solar/Wind Harmer
3.18
960911AF2-382 GEN
Solar/Wind Harmer
3.536
24735205WLF2G2
Adder
2.649
24734805WLF1G4
Adder
3.219
24735105WLF2G1
Adder
2.649
24728305BUCHG2
Adder
2.603
24728205BUCHG1
Adder
2.603
270214AC2-123 GEN
Solar/Wind Helper
0.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.428
WECLTFEXP_WEC->PJM
CLTF
0.248
MECLTFEXP_MEC->PJM
CLTF
1.228
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.909
LGEELTFEXP_LGEE->PJM
CLTF
0.607
TVALTFEXP_TVA->PJM
CLTF
1.158
NYPJM->LTFIMP_NY
CLTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.15
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.824

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
971461AH1-227 GEN
Solar/Wind Harmer
8.01
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
957381AF2-032 GEN
Solar/Wind Harmer
1.978
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24728205BUCHG1
50/50
8.141
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145336SMITFLD
Solar/Wind Helper
0.094
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316415AF1-147_GEN2
Solar/Wind Helper
0.762
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
3147666LOUISA
Solar/Wind Helper
0.53
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.35
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
24728205BUCHG1
50/50
5.498
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.19
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:300.69 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3548.09
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
1.03
970281AG2-184 GEN
Solar/Wind Harmer
20.395
962211AG1-066 GEN
Solar/Wind Harmer
2.254
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
8.361
972103AH1-617 GEN
Solar/Wind Harmer
19.424
270030AE2-140 GEN
Solar/Wind Harmer
19.172
959091AF2-200 GEN
Solar/Wind Harmer
13.013
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.892
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
9.234
270399AC1-101 GEN
Solar/Wind Harmer
4.127
971981AH1-535 GEN
Solar/Wind Harmer
9.403
971171AH1-044 GEN
Solar/Wind Harmer
13.013
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
6.316
270346AE1-212 GEN
Solar/Wind Harmer
9.919
971461AH1-227 GEN
Solar/Wind Harmer
5.315
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
971329AH1-144 GEN
Solar/Wind Harmer
7.984
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
4.127
957241AF2-018 GEN
Solar/Wind Harmer
4.267
270053AF1-130 C
Solar/Wind Harmer
17.045
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
14.042
944971AF1-162 GEN
Solar/Wind Harmer
6.718
959081AF2-199 GEN
Solar/Wind Harmer
6.507
971067AG2-660 GEN
Solar/Wind Harmer
1.513
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
7.137
971061AG2-657 GEN
Solar/Wind Harmer
7.927
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
270336AE1-100 GEN
Solar/Wind Harmer
1.767
943811AF1-049 GEN
Solar/Wind Harmer
3.467
957471AF2-041 GEN
Solar/Wind Harmer
19.52
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
270214AC2-123 GEN
Solar/Wind Harmer
3.436
270583AD2-179 GEN
Solar/Wind Harmer
13.918
971225AH1-072 GEN
Solar/Wind Harmer
2.072
971227AH1-073 GEN
Solar/Wind Harmer
2.072
24723105RIVRG2
Adder
16.666
971341AH1-150 GEN
Solar/Wind Harmer
13.013
971343AH1-151 GEN
Solar/Wind Harmer
13.013
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
5.696
970913AG2-568 GEN
Solar/Wind Harmer
6.824
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.57 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.47
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:286.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:3381.22
MW Contribution:
35.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
14.229
274735ELWOOD EC;4P
Adder
10.589
315651AD1-115 GEN
Solar/Wind Helper
0.81
316059AD1-063 C
Solar/Wind Helper
0.235
3141783LANCAST
Solar/Wind Helper
0.14
3141783LANCAST
Solar/Wind Helper
0.093
971881AH1-461 GEN
50/50
11.279
24290105CRG2H
50/50
0.879
943031AE2-326 GEN
Solar/Wind Harmer
5.408
960911AF2-382 GEN
Solar/Wind Harmer
5.833
972103AH1-617 GEN
Solar/Wind Harmer
13.552
270030AE2-140 GEN
Solar/Wind Harmer
13.376
274734ELWOOD EC;8P
Adder
10.589
274736ELWOOD EC;9P
Adder
10.589
274676JOLIET 29;8U
Adder
19.051
316447AC1-158 HLD
Solar/Wind Helper
3.247
3142416OLDCHRC
Solar/Wind Helper
0.642
3142416OLDCHRC
Solar/Wind Helper
0.246
315975AC1-164 GENB
Solar/Wind Helper
0.091
3142433PROV 92
Solar/Wind Helper
0.934
970823AG2-518 GEN
50/50
5.367
24290605CLAY-1
50/50
0.168
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.792
971461AH1-227 GEN
Solar/Wind Harmer
3.708
274730ELWOOD EC;6P
Adder
10.589
316044AC1-158 PL1
Solar/Wind Helper
1.476
3143226MDLTHAN
Solar/Wind Helper
0.24
3142543TWELFTH
Solar/Wind Helper
0.023
316404AE1-155 C
Solar/Wind Helper
2.011
3138133OCRAN
Solar/Wind Helper
0.139
315662AE1-191 GEN
Solar/Wind Helper
1.25
316280AD1-041 GEN
Solar/Wind Helper
0.781
3147666LOUISA
Solar/Wind Helper
0.921
24290705CLAY-2
50/50
0.168
971403AH1-188 GEN
Solar/Wind Harmer
9.797
944971AF1-162 GEN
Solar/Wind Harmer
6.718
270494AE1-108_GEN
Solar/Wind Helper
3.46
316223AC1-118
Solar/Wind Helper
0.364
24290005CRG1L
50/50
0.717
971687AH1-348 GEN
Solar/Wind Harmer
0.719
3141196NOKESVL
Solar/Wind Helper
0.99
316075AC2-137 C
Solar/Wind Helper
0.367
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.452
3147312GRETNA
Solar/Wind Helper
0.046
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.856
316450AC1-158 RIC
Solar/Wind Helper
0.393
316487AF1-042 GEN
Solar/Wind Helper
0.237
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
1.529
971331AH1-145 GEN
Solar/Wind Harmer
12.5
24734705WLF1G3
Adder
6.298
24734905WLF1G5
Adder
6.298
270069AE2-166 C O1
Solar/Wind Harmer
6.442
270399AC1-101 GEN
Solar/Wind Harmer
2.148
971981AH1-535 GEN
Solar/Wind Harmer
4.373
274675JOLIET 29;7U
Adder
19.756
274675JOLIET 29;7U
Adder
19.051
3143873LANEXA
Solar/Wind Helper
0.14
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.046
316382AG1-145 C
Solar/Wind Helper
0.305
316159AE1-175 C
Solar/Wind Helper
0.344
971329AH1-144 GEN
Solar/Wind Harmer
4.594
24734805WLF1G4
Adder
6.298
24735105WLF2G1
Adder
6.159
270400AC1-102 GEN
Solar/Wind Harmer
2.148
957241AF2-018 GEN
Solar/Wind Harmer
0.001
24290605CLAY-1
50/50
0.168
24728305BUCHG2
50/50
5.498
274732ELWOOD EC;7P
Adder
10.589
3141906WESTMOR
Solar/Wind Helper
0.095
316197AC1-042 GEN
Solar/Wind Helper
0.219
3147666LOUISA
Solar/Wind Helper
0.53
270053AF1-130 C
Solar/Wind Harmer
14.993
941621AE2-160 GEN
Adder
3.038
274731ELWOOD EC;2P
Adder
10.589
274733ELWOOD EC;3P
Adder
10.589
316164AC1-076 GEN
Solar/Wind Helper
1.187
316233AE1-074 FULL
Solar/Wind Helper
0.367
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.31
24728205BUCHG1
50/50
5.498
971277AH1-098 GEN
Solar/Wind Harmer
3.974
970913AG2-568 GEN
Solar/Wind Harmer
5.608
316045AC1-158 PL2
Solar/Wind Helper
4.721
966871AG1-558 GEN
Solar/Wind Helper
0.337
316006AB2-029 C
Solar/Wind Helper
0.117
315666AE1-190 GEN
Solar/Wind Helper
0.312
316156AD2-030 GEN
Solar/Wind Helper
0.35
316240AF1-291 C
Solar/Wind Helper
0.302
270205AE1-176
50/50
0.003
24735205WLF2G2
Adder
6.159
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
19.756
966881AG1-559 GEN
Solar/Wind Helper
0.348
316473AC1-191 GEN
Solar/Wind Helper
1.53
3142946ENON
Solar/Wind Helper
0.078
270583AD2-179 GEN
Solar/Wind Harmer
9.711
971225AH1-072 GEN
Solar/Wind Harmer
1.446
971227AH1-073 GEN
Solar/Wind Harmer
1.446
24723105RIVRG2
Adder
16.666
315976AC1-164 GENA
Solar/Wind Helper
3.073
316169AC1-164_GENC
Solar/Wind Helper
2.654
3142946ENON
Solar/Wind Helper
0.023
3141766HARMONY
Solar/Wind Helper
0.047
3147123OTTER R
Solar/Wind Helper
0.137
316192AB2-158 GEN
Solar/Wind Helper
1.54
971543AH1-269 GEN
50/50
8.178
24290205CRG2L
50/50
0.737
971313AH1-133 GEN
Solar/Wind Harmer
4.106
971061AG2-657 GEN
Solar/Wind Harmer
3.871
274728ELWOOD EC;5P
Adder
10.589
316468AD1-105 GEN
Solar/Wind Helper
1.202
3141426STAFORD
Solar/Wind Helper
0.054
3141913WHIT STONE
Solar/Wind Helper
0.232
957831AF2-077 GEN
Solar/Wind Helper
0.303
316312AB1-027
Solar/Wind Helper
0.471
3143526WINTERP
Solar/Wind Helper
1.25
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24415905BUCK
50/50
0.026
24290705CLAY-2
50/50
0.168
316337AD2-073 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
0.944
970563AG2-360 GEN
50/50
35.775
24689505VACITY
50/50
4.258
972273AH1-721 GEN
Adder
66.568
274729ELWOOD EC;1P
Adder
10.589
3143526WINTERP
Solar/Wind Helper
1.25
964211AG1-282 GEN
Solar/Wind Helper
0.318
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316415AF1-147_GEN2
Solar/Wind Helper
0.762
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.818
CPLELTFEXP_CPLE->PJM
CLTF
2.114
SIGELTFEXP_SIGE->PJM
CLTF
0.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.429
WECLTFEXP_WEC->PJM
CLTF
2.493
LAGNLTFEXP_LAGN->PJM
CLTF
14.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.786
LGEELTFEXP_LGEE->PJM
CLTF
4.996
MECLTFEXP_MEC->PJM
CLTF
11.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.24
NYPJM->LTFIMP_NY
CLTF
2.66
TVALTFEXP_TVA->PJM
CLTF
7.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.15

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:253.24 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2988.23
MW Contribution:
33.92
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.169
3151861LOWMORA
Adder
1.295
971403AH1-188 GEN
Solar/Wind Harmer
12.423
959081AF2-199 GEN
Solar/Wind Harmer
5.491
971067AG2-660 GEN
Solar/Wind Harmer
1.277
270494AE1-108_GEN
Solar/Wind Helper
3.531
316223AC1-118
Solar/Wind Helper
0.343
24290705CLAY-2
50/50
0.169
24415905BUCK
50/50
0.025
316337AD2-073 GEN
Solar/Wind Helper
0.341
3141726DUNNSVL
Solar/Wind Helper
0.895
24728205BUCHG1
50/50
5.133
971277AH1-098 GEN
Solar/Wind Harmer
5.61
970913AG2-568 GEN
Solar/Wind Harmer
6.125
316045AC1-158 PL2
Solar/Wind Helper
4.379
966871AG1-558 GEN
Solar/Wind Helper
0.321
316006AB2-029 C
Solar/Wind Helper
0.107
24734805WLF1G4
50/50
6.262
24735105WLF2G1
50/50
6.118
971329AH1-144 GEN
Solar/Wind Harmer
7.928
3151861LOWMORA
Adder
1.244
274731ELWOOD EC;2P
Adder
8.897
274733ELWOOD EC;3P
Adder
8.897
316164AC1-076 GEN
Solar/Wind Helper
1.11
316233AE1-074 FULL
Solar/Wind Helper
0.355
3141813NORNECK
Solar/Wind Helper
0.223
971687AH1-348 GEN
Solar/Wind Harmer
0.942
316075AC2-137 C
Solar/Wind Helper
0.351
316077AC2-138 C
Solar/Wind Helper
0.211
970563AG2-360 GEN
50/50
33.924
24689505VACITY
50/50
3.969
274729ELWOOD EC;1P
Adder
8.897
3143526WINTERP
Solar/Wind Helper
1.209
964211AG1-282 GEN
Solar/Wind Helper
0.301
316312AB1-027
Solar/Wind Helper
0.45
3143526WINTERP
Solar/Wind Helper
1.209
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
6.118
270336AE1-100 GEN
Solar/Wind Harmer
1.761
943811AF1-049 GEN
Solar/Wind Harmer
3.46
957471AF2-041 GEN
Solar/Wind Harmer
16.472
274676JOLIET 29;8U
Adder
16.6
966881AG1-559 GEN
Solar/Wind Helper
0.328
316473AC1-191 GEN
Solar/Wind Helper
1.456
3142946ENON
Solar/Wind Helper
0.075
971543AH1-269 GEN
50/50
8.242
971313AH1-133 GEN
Solar/Wind Harmer
6.737
274728ELWOOD EC;5P
Adder
8.897
316468AD1-105 GEN
Solar/Wind Helper
1.134
971881AH1-461 GEN
50/50
10.678
943031AE2-326 GEN
Solar/Wind Harmer
5.324
960911AF2-382 GEN
Solar/Wind Harmer
7.746
270030AE2-140 GEN
Solar/Wind Harmer
19.126
972103AH1-617 GEN
Solar/Wind Harmer
17.445
959091AF2-200 GEN
Solar/Wind Harmer
10.981
274734ELWOOD EC;8P
Adder
8.897
274736ELWOOD EC;9P
Adder
8.897
274676JOLIET 29;8U
Adder
16.007
316447AC1-158 HLD
Solar/Wind Helper
3.012
3142416OLDCHRC
Solar/Wind Helper
0.613
3142416OLDCHRC
Solar/Wind Helper
0.235
315975AC1-164 GENB
Solar/Wind Helper
0.087
3142433PROV 92
Solar/Wind Helper
0.892
270214AC2-123 GEN
Solar/Wind Harmer
3.383
270583AD2-179 GEN
Solar/Wind Harmer
13.976
971225AH1-072 GEN
Solar/Wind Harmer
1.896
971227AH1-073 GEN
Solar/Wind Harmer
1.896
971341AH1-150 GEN
Solar/Wind Harmer
10.981
971343AH1-151 GEN
Solar/Wind Harmer
10.981
315976AC1-164 GENA
Solar/Wind Helper
2.937
316169AC1-164_GENC
Solar/Wind Helper
2.537
3142946ENON
Solar/Wind Helper
0.022
3148463FAIRFLD
Solar/Wind Harmer
-0.014
970281AG2-184 GEN
Solar/Wind Harmer
18.318
274735ELWOOD EC;4P
Adder
8.897
315651AD1-115 GEN
Solar/Wind Helper
0.755
24290605CLAY-1
50/50
0.169
24728305BUCHG2
50/50
5.133
274732ELWOOD EC;7P
Adder
8.897
3141906WESTMOR
Solar/Wind Helper
0.09
970823AG2-518 GEN
50/50
5.477
24290605CLAY-1
50/50
0.169
958121AF2-106 GEN
Solar/Wind Harmer
6.343
270346AE1-212 GEN
Solar/Wind Harmer
9.332
971461AH1-227 GEN
Solar/Wind Harmer
4.864
274730ELWOOD EC;6P
Adder
8.897
316044AC1-158 PL1
Solar/Wind Helper
1.369
3143226MDLTHAN
Solar/Wind Helper
0.233
3142543TWELFTH
Solar/Wind Helper
0.022
316404AE1-155 C
Solar/Wind Helper
1.907
247619Y1-049
50/50
0.036
316450AC1-158 RIC
Solar/Wind Helper
0.365
24416005BYLLESBY
50/50
0.023
24734705WLF1G3
50/50
6.262
24734905WLF1G5
50/50
6.262
966391AG1-508 GEN
Solar/Wind Harmer
4.809
971331AH1-145 GEN
Solar/Wind Harmer
12.412
270069AE2-166 C O1
Solar/Wind Harmer
9.245
315616AA1-038_C
Solar/Wind Harmer
2.777
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.264
971981AH1-535 GEN
Solar/Wind Harmer
8.769
971171AH1-044 GEN
Solar/Wind Harmer
10.981
274675JOLIET 29;7U
Adder
16.6
274675JOLIET 29;7U
Adder
16.007
3143873LANEXA
Solar/Wind Helper
0.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
83.049
LGEELTFEXP_LGEE->PJM
CLTF
4.253
MECLTFEXP_MEC->PJM
CLTF
9.684
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.014
NYPJM->LTFIMP_NY
CLTF
2.107
TVALTFEXP_TVA->PJM
CLTF
6.888
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.088
CPLELTFEXP_CPLE->PJM
CLTF
2.02
SIGELTFEXP_SIGE->PJM
CLTF
0.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.396
WECLTFEXP_WEC->PJM
CLTF
2.106
LAGNLTFEXP_LAGN->PJM
CLTF
12.935

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:241.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2849.63
MW Contribution:
33.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.175
971403AH1-188 GEN
Solar/Wind Harmer
12.255
959081AF2-199 GEN
Solar/Wind Harmer
5.417
971067AG2-660 GEN
Solar/Wind Harmer
1.26
270494AE1-108_GEN
Solar/Wind Helper
4.186
270173AC1-122 GEN
Solar/Wind Helper
2.053
24290705CLAY-2
50/50
0.175
24415905BUCK
50/50
0.025
24728205BUCHG1
50/50
5.054
971277AH1-098 GEN
Solar/Wind Harmer
5.569
970913AG2-568 GEN
Solar/Wind Harmer
6.098
316045AC1-158 PL2
Solar/Wind Helper
4.285
966871AG1-558 GEN
Solar/Wind Helper
0.314
971329AH1-144 GEN
Solar/Wind Harmer
8.141
24734805WLF1G4
Adder
5.791
24735105WLF2G1
Adder
5.652
274731ELWOOD EC;2P
Adder
8.783
274733ELWOOD EC;3P
Adder
8.783
316233AE1-074 FULL
Solar/Wind Helper
0.346
316164AC1-076 GEN
Solar/Wind Helper
1.072
24290005CRG1L
50/50
0.657
971687AH1-348 GEN
Solar/Wind Harmer
0.926
3147312GRETNA
Solar/Wind Helper
0.068
316075AC2-137 C
Solar/Wind Helper
0.344
970563AG2-360 GEN
50/50
33.343
24689505VACITY
50/50
3.901
274729ELWOOD EC;1P
Adder
8.783
3147312GRETNA
Solar/Wind Helper
0.273
3146802CHATHAM
Solar/Wind Helper
0.256
3143526WINTERP
Solar/Wind Helper
1.177
316312AB1-027
Solar/Wind Helper
0.44
3143526WINTERP
Solar/Wind Helper
1.177
270205AE1-176
50/50
0.004
971543AH1-269 GEN
50/50
8.505
24290205CRG2L
50/50
0.675
971313AH1-133 GEN
Solar/Wind Harmer
6.653
274728ELWOOD EC;5P
Adder
8.783
316468AD1-105 GEN
Solar/Wind Helper
1.109
270336AE1-100 GEN
Solar/Wind Harmer
1.752
24735205WLF2G2
Adder
5.652
943811AF1-049 GEN
Solar/Wind Harmer
3.421
957471AF2-041 GEN
Solar/Wind Harmer
16.25
274676JOLIET 29;8U
Adder
16.387
966881AG1-559 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
1.424
971881AH1-461 GEN
50/50
10.6
24290105CRG2H
50/50
0.806
943031AE2-326 GEN
Solar/Wind Harmer
5.244
960911AF2-382 GEN
Solar/Wind Harmer
7.628
270030AE2-140 GEN
Solar/Wind Harmer
18.948
959091AF2-200 GEN
Solar/Wind Harmer
10.834
274734ELWOOD EC;8P
Adder
8.783
274736ELWOOD EC;9P
Adder
8.783
274676JOLIET 29;8U
Adder
15.802
3147123OTTER R
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.947
3142416OLDCHRC
Solar/Wind Helper
0.599
3142416OLDCHRC
Solar/Wind Helper
0.23
315975AC1-164 GENB
Solar/Wind Helper
0.085
270583AD2-179 GEN
Solar/Wind Harmer
14.401
270214AC2-123 GEN
Solar/Wind Harmer
3.332
971225AH1-072 GEN
Solar/Wind Harmer
1.865
971227AH1-073 GEN
Solar/Wind Harmer
1.865
971341AH1-150 GEN
Solar/Wind Harmer
10.834
971343AH1-151 GEN
Solar/Wind Harmer
10.834
315976AC1-164 GENA
Solar/Wind Helper
2.875
316169AC1-164_GENC
Solar/Wind Helper
2.483
274735ELWOOD EC;4P
Adder
8.783
24290605CLAY-1
50/50
0.175
24728305BUCHG2
50/50
5.054
274732ELWOOD EC;7P
Adder
8.783
316197AC1-042 GEN
Solar/Wind Helper
0.322
970823AG2-518 GEN
50/50
5.724
24290605CLAY-1
50/50
0.175
958121AF2-106 GEN
Solar/Wind Harmer
6.537
270346AE1-212 GEN
Solar/Wind Harmer
9.433
971461AH1-227 GEN
Solar/Wind Harmer
4.785
274730ELWOOD EC;6P
Adder
8.783
316044AC1-158 PL1
Solar/Wind Helper
1.339
3143226MDLTHAN
Solar/Wind Helper
0.227
247619Y1-049
50/50
0.036
24289905CRG1H
50/50
0.785
316450AC1-158 RIC
Solar/Wind Helper
0.357
24416005BYLLESBY
50/50
0.023
966391AG1-508 GEN
Solar/Wind Harmer
4.774
971331AH1-145 GEN
Solar/Wind Harmer
12.745
270069AE2-166 C O1
Solar/Wind Harmer
9.341
24734705WLF1G3
Adder
5.791
24734905WLF1G5
Adder
5.791
971171AH1-044 GEN
Solar/Wind Harmer
10.834
274675JOLIET 29;7U
Adder
16.387
274675JOLIET 29;7U
Adder
15.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.507
CPLELTFEXP_CPLE->PJM
CLTF
1.827
SIGELTFEXP_SIGE->PJM
CLTF
0.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.871
WECLTFEXP_WEC->PJM
CLTF
2.077
LAGNLTFEXP_LAGN->PJM
CLTF
12.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.488
LGEELTFEXP_LGEE->PJM
CLTF
4.19
MECLTFEXP_MEC->PJM
CLTF
9.533
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.022
NYPJM->LTFIMP_NY
CLTF
2.036
TVALTFEXP_TVA->PJM
CLTF
6.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:237.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2800.7
MW Contribution:
32.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.159
959081AF2-199 GEN
Solar/Wind Harmer
5.261
971067AG2-660 GEN
Solar/Wind Harmer
1.223
270494AE1-108_GEN
Solar/Wind Helper
3.291
24290705CLAY-2
50/50
0.159
24415905BUCK
50/50
0.024
24728205BUCHG1
50/50
4.902
971277AH1-098 GEN
Solar/Wind Harmer
5.342
316045AC1-158 PL2
Solar/Wind Helper
4.187
966871AG1-558 GEN
Solar/Wind Helper
0.305
24734805WLF1G4
50/50
5.986
24735105WLF2G1
50/50
5.85
971329AH1-144 GEN
Solar/Wind Harmer
7.474
274731ELWOOD EC;2P
Adder
8.525
274733ELWOOD EC;3P
Adder
8.525
971687AH1-348 GEN
Solar/Wind Harmer
0.9
3147312GRETNA
Solar/Wind Helper
0.046
970563AG2-360 GEN
50/50
32.411
24689505VACITY
50/50
3.793
274729ELWOOD EC;1P
Adder
8.525
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
316312AB1-027
Solar/Wind Helper
0.427
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.85
270336AE1-100 GEN
Solar/Wind Harmer
1.667
943811AF1-049 GEN
Solar/Wind Harmer
3.27
957471AF2-041 GEN
Solar/Wind Harmer
15.782
274676JOLIET 29;8U
Adder
15.905
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.383
971543AH1-269 GEN
50/50
7.755
971313AH1-133 GEN
Solar/Wind Harmer
6.428
274728ELWOOD EC;5P
Adder
8.525
316468AD1-105 GEN
Solar/Wind Helper
1.079
971881AH1-461 GEN
50/50
10.173
943031AE2-326 GEN
Solar/Wind Harmer
5.082
960911AF2-382 GEN
Solar/Wind Harmer
7.399
270030AE2-140 GEN
Solar/Wind Harmer
18.085
959091AF2-200 GEN
Solar/Wind Harmer
10.521
274734ELWOOD EC;8P
Adder
8.525
274736ELWOOD EC;9P
Adder
8.525
274676JOLIET 29;8U
Adder
15.337
316447AC1-158 HLD
Solar/Wind Helper
2.88
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.582
3142416OLDCHRC
Solar/Wind Helper
0.223
270214AC2-123 GEN
Solar/Wind Harmer
3.229
270583AD2-179 GEN
Solar/Wind Harmer
13.158
971225AH1-072 GEN
Solar/Wind Harmer
1.812
971227AH1-073 GEN
Solar/Wind Harmer
1.812
971341AH1-150 GEN
Solar/Wind Harmer
10.521
971343AH1-151 GEN
Solar/Wind Harmer
10.521
274735ELWOOD EC;4P
Adder
8.525
970823AG2-518 GEN
50/50
5.131
24290605CLAY-1
50/50
0.159
958121AF2-106 GEN
Solar/Wind Harmer
5.971
270346AE1-212 GEN
Solar/Wind Harmer
8.843
971461AH1-227 GEN
Solar/Wind Harmer
4.649
274730ELWOOD EC;6P
Adder
8.525
316044AC1-158 PL1
Solar/Wind Helper
1.309
24290605CLAY-1
50/50
0.159
24728305BUCHG2
50/50
4.902
274732ELWOOD EC;7P
Adder
8.525
316197AC1-042 GEN
Solar/Wind Helper
0.219
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.986
24734905WLF1G5
50/50
5.986
966391AG1-508 GEN
Solar/Wind Harmer
4.579
971331AH1-145 GEN
Solar/Wind Harmer
11.701
270069AE2-166 C O1
Solar/Wind Harmer
8.726
971171AH1-044 GEN
Solar/Wind Harmer
10.521
274675JOLIET 29;7U
Adder
15.905
274675JOLIET 29;7U
Adder
15.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.525
LGEELTFEXP_LGEE->PJM
CLTF
4.072
MECLTFEXP_MEC->PJM
CLTF
9.276
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.805
NYPJM->LTFIMP_NY
CLTF
2.006
TVALTFEXP_TVA->PJM
CLTF
6.594
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.49
CPLELTFEXP_CPLE->PJM
CLTF
1.94
SIGELTFEXP_SIGE->PJM
CLTF
0.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.311
WECLTFEXP_WEC->PJM
CLTF
2.017
LAGNLTFEXP_LAGN->PJM
CLTF
12.384

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:236.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2790.61
MW Contribution:
32.61
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24290705CLAY-2
50/50
0.161
959081AF2-199 GEN
Solar/Wind Harmer
5.295
971067AG2-660 GEN
Solar/Wind Harmer
1.231
270494AE1-108_GEN
Solar/Wind Helper
3.421
24290705CLAY-2
50/50
0.161
24415905BUCK
50/50
0.024
24728205BUCHG1
50/50
4.933
971277AH1-098 GEN
Solar/Wind Harmer
5.391
970913AG2-568 GEN
Solar/Wind Harmer
5.873
316045AC1-158 PL2
Solar/Wind Helper
4.21
966871AG1-558 GEN
Solar/Wind Helper
0.308
24734805WLF1G4
50/50
6.023
24735105WLF2G1
50/50
5.886
971329AH1-144 GEN
Solar/Wind Harmer
7.561
274731ELWOOD EC;2P
Adder
8.581
274733ELWOOD EC;3P
Adder
8.581
971687AH1-348 GEN
Solar/Wind Harmer
0.906
3147312GRETNA
Solar/Wind Helper
0.083
316123AC1-075 GEN
Solar/Wind Helper
1.523
970563AG2-360 GEN
50/50
32.611
24689505VACITY
50/50
3.816
274729ELWOOD EC;1P
Adder
8.581
3147312GRETNA
Solar/Wind Helper
0.331
3146802CHATHAM
Solar/Wind Helper
0.31
316312AB1-027
Solar/Wind Helper
0.431
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.886
270336AE1-100 GEN
Solar/Wind Harmer
1.727
943811AF1-049 GEN
Solar/Wind Harmer
3.415
957471AF2-041 GEN
Solar/Wind Harmer
15.885
274676JOLIET 29;8U
Adder
16.009
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.394
971543AH1-269 GEN
50/50
7.854
971313AH1-133 GEN
Solar/Wind Harmer
6.472
274728ELWOOD EC;5P
Adder
8.58
316468AD1-105 GEN
Solar/Wind Helper
1.087
971881AH1-461 GEN
50/50
10.248
943031AE2-326 GEN
Solar/Wind Harmer
5.116
960911AF2-382 GEN
Solar/Wind Harmer
7.446
270030AE2-140 GEN
Solar/Wind Harmer
18.83
959091AF2-200 GEN
Solar/Wind Harmer
10.59
274734ELWOOD EC;8P
Adder
8.58
274736ELWOOD EC;9P
Adder
8.58
274676JOLIET 29;8U
Adder
15.437
3147123OTTER R
Solar/Wind Helper
0.234
316447AC1-158 HLD
Solar/Wind Helper
2.895
3142416OLDCHRC
Solar/Wind Helper
0.587
3142416OLDCHRC
Solar/Wind Helper
0.225
270214AC2-123 GEN
Solar/Wind Harmer
3.25
270583AD2-179 GEN
Solar/Wind Harmer
13.324
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
971341AH1-150 GEN
Solar/Wind Harmer
10.59
971343AH1-151 GEN
Solar/Wind Harmer
10.59
274735ELWOOD EC;4P
Adder
8.581
970823AG2-518 GEN
50/50
5.201
24290605CLAY-1
50/50
0.161
24728305BUCHG2
50/50
4.933
274732ELWOOD EC;7P
Adder
8.58
316197AC1-042 GEN
Solar/Wind Helper
0.39
24290605CLAY-1
50/50
0.161
958121AF2-106 GEN
Solar/Wind Harmer
6.047
270346AE1-212 GEN
Solar/Wind Harmer
8.928
971461AH1-227 GEN
Solar/Wind Harmer
4.678
274730ELWOOD EC;6P
Adder
8.58
316044AC1-158 PL1
Solar/Wind Helper
1.316
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.351
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
6.023
24734905WLF1G5
50/50
6.023
966391AG1-508 GEN
Solar/Wind Harmer
4.619
971331AH1-145 GEN
Solar/Wind Harmer
11.838
270069AE2-166 C O1
Solar/Wind Harmer
9.063
971171AH1-044 GEN
Solar/Wind Harmer
10.59
274675JOLIET 29;7U
Adder
16.009
274675JOLIET 29;7U
Adder
15.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.609
CPLELTFEXP_CPLE->PJM
CLTF
1.968
SIGELTFEXP_SIGE->PJM
CLTF
0.308
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.47
WECLTFEXP_WEC->PJM
CLTF
2.031
LAGNLTFEXP_LAGN->PJM
CLTF
12.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.048
LGEELTFEXP_LGEE->PJM
CLTF
4.098
MECLTFEXP_MEC->PJM
CLTF
9.336
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
74.288
NYPJM->LTFIMP_NY
CLTF
2.015
TVALTFEXP_TVA->PJM
CLTF
6.637
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:222.44 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2624.74
MW Contribution:
32.44
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274735ELWOOD EC;4P
Adder
8.538
970823AG2-518 GEN
50/50
5.134
24290605CLAY-1
50/50
0.16
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
6.06
971461AH1-227 GEN
Solar/Wind Harmer
3.246
274730ELWOOD EC;6P
Adder
8.538
316044AC1-158 PL1
Solar/Wind Helper
1.308
24290705CLAY-2
50/50
0.16
270494AE1-108_GEN
Solar/Wind Helper
3.288
971687AH1-348 GEN
Solar/Wind Harmer
0.628
3147312GRETNA
Solar/Wind Helper
0.046
247619Y1-049
50/50
0.034
316450AC1-158 RIC
Solar/Wind Helper
0.349
24416005BYLLESBY
50/50
0.022
24734705WLF1G3
50/50
5.991
24734905WLF1G5
50/50
5.991
966391AG1-508 GEN
Solar/Wind Harmer
1.432
971331AH1-145 GEN
Solar/Wind Harmer
11.709
270069AE2-166 C O1
Solar/Wind Harmer
6.093
274675JOLIET 29;7U
Adder
15.93
274675JOLIET 29;7U
Adder
15.361
24290605CLAY-1
50/50
0.16
24728305BUCHG2
50/50
4.906
274732ELWOOD EC;7P
Adder
8.538
316197AC1-042 GEN
Solar/Wind Helper
0.219
24734805WLF1G4
50/50
5.991
24735105WLF2G1
50/50
5.855
971329AH1-144 GEN
Solar/Wind Harmer
4.303
274731ELWOOD EC;2P
Adder
8.538
274733ELWOOD EC;3P
Adder
8.538
24728205BUCHG1
50/50
4.906
971277AH1-098 GEN
Solar/Wind Harmer
3.729
316045AC1-158 PL2
Solar/Wind Helper
4.183
966871AG1-558 GEN
Solar/Wind Helper
0.305
270205AE1-176
50/50
0.003
24735205WLF2G2
50/50
5.855
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
15.93
966881AG1-559 GEN
Solar/Wind Helper
0.312
316473AC1-191 GEN
Solar/Wind Helper
1.382
270583AD2-179 GEN
Solar/Wind Harmer
9.185
971225AH1-072 GEN
Solar/Wind Harmer
1.266
971227AH1-073 GEN
Solar/Wind Harmer
1.266
971881AH1-461 GEN
50/50
10.18
943031AE2-326 GEN
Solar/Wind Harmer
5.085
960911AF2-382 GEN
Solar/Wind Harmer
5.166
270030AE2-140 GEN
Solar/Wind Harmer
12.629
274734ELWOOD EC;8P
Adder
8.538
274736ELWOOD EC;9P
Adder
8.538
274676JOLIET 29;8U
Adder
15.361
316447AC1-158 HLD
Solar/Wind Helper
2.877
3147123OTTER R
Solar/Wind Helper
0.137
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.223
971543AH1-269 GEN
50/50
7.759
971313AH1-133 GEN
Solar/Wind Harmer
3.701
274728ELWOOD EC;5P
Adder
8.538
316468AD1-105 GEN
Solar/Wind Helper
1.078
316312AB1-027
Solar/Wind Helper
0.427
24290705CLAY-2
50/50
0.16
24415905BUCK
50/50
0.024
970563AG2-360 GEN
50/50
32.435
24689505VACITY
50/50
3.796
274729ELWOOD EC;1P
Adder
8.538
3147312GRETNA
Solar/Wind Helper
0.186
3146802CHATHAM
Solar/Wind Helper
0.174
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.632
LGEELTFEXP_LGEE->PJM
CLTF
4.077
MECLTFEXP_MEC->PJM
CLTF
9.289
AH1-155LTFEXP_AH1-155->PJM
LTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.921
NYPJM->LTFIMP_NY
CLTF
2.001
TVALTFEXP_TVA->PJM
CLTF
6.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.515
CPLELTFEXP_CPLE->PJM
CLTF
1.948
SIGELTFEXP_SIGE->PJM
CLTF
0.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.342
WECLTFEXP_WEC->PJM
CLTF
2.02
LAGNLTFEXP_LAGN->PJM
CLTF
12.4

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:217.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2565.46
MW Contribution:
35.77
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
35.775

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2565.46
MW Contribution:
35.77
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
35.775

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2565.46
MW Contribution:
35.77
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
35.775

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:217.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2565.21
MW Contribution:
35.77
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
35.775

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:189.36 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2234.5
MW Contribution:
33.92
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
33.924

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:185.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2190.87
MW Contribution:
32.3
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.305

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:181.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2143.69
MW Contribution:
32.43
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.428

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 138KV_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 138KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:181.33 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2139.7
MW Contribution:
32.52
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.516

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:177.62 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2095.9
MW Contribution:
32.44
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.435

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
957471AF2-041 GEN
Solar/Wind Harmer
8.663
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
959341AF2-225 GEN
Solar/Wind Harmer
14.414
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
972103AH1-617 GEN
Solar/Wind Harmer
29.061
270030AE2-140 GEN
Solar/Wind Harmer
23.688
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
252524AE2-267 GEN
Solar/Wind Harmer
1.546
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
274767LEE CO EC;8U
Adder
8.816
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
959091AF2-200 GEN
Solar/Wind Harmer
5.775
971461AH1-227 GEN
Solar/Wind Harmer
8.01
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
252507AC2-088 GEN
Solar/Wind Harmer
1.781
970193AG2-126 GEN
Solar/Wind Harmer
14.742
25196608WSDLE5
Adder
8.414
957541AF2-048 GEN
Solar/Wind Harmer
1.534
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274730ELWOOD EC;6P
Adder
15.424
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
10.556
944221AF1-090 GEN
Solar/Wind Harmer
10.902
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
276726Z2-087_GEN
Solar/Wind Harmer
7.598
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274746AC1-111 G10
Adder
5.265
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
5.448
3429421JKCT 10G
Adder
9.312
339221AD2-048_GEN
Solar/Wind Harmer
1.65
970091AG2-072 GEN
Adder
78.951
276686W4-005 GEN3
Solar/Wind Harmer
2.955
960001AF2-291 GEN
Solar/Wind Harmer
2.912
270222AC2-111 GEN
Solar/Wind Harmer
4.299
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
970819AG2-516 GEN
Solar/Wind Harmer
11.469
274822ROCKFORD ;11
Adder
18.727
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.065
972167AH1-666 GEN
Solar/Wind Harmer
8.411
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
29.588
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276603SUBLETTE C
Solar/Wind Harmer
1.006
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
971687AH1-348 GEN
Solar/Wind Harmer
1.552
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.41
276621W2-048 GEN
Solar/Wind Harmer
6.123
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
939741AE1-205 GEN
Solar/Wind Harmer
19.219
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
28.638
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
339236AF1-050_GEN
Solar/Wind Harmer
2.114
970107AG2-081 GEN
Solar/Wind Harmer
3.297
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
276838X2-022 GEN2
Solar/Wind Harmer
0.228
971313AH1-133 GEN
Solar/Wind Harmer
10.065
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
274728ELWOOD EC;5P
Adder
15.424
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
24735205WLF2G2
50/50
10.407
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
943811AF1-049 GEN
Solar/Wind Harmer
4.26
943111AE2-339 GEN
Solar/Wind Harmer
0.973
945681AF1-233 GEN
Solar/Wind Harmer
19.84
252516AE2-318_GEN
Solar/Wind Harmer
9.863
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
4.396
276916AD2-100_GEN
Solar/Wind Harmer
20.818
253370AE2-315 SEC1
Adder
1.882
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
339211AE2-254 GEN
Solar/Wind Harmer
1.749
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
276656WTG2_EQ
Solar/Wind Harmer
1.11
274766LEE CO EC;7U
Adder
8.816
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
971485AH1-239 GEN
Solar/Wind Harmer
9.749
964781AG1-341 GEN
Solar/Wind Harmer
12.421
942891AE2-308 GEN
Solar/Wind Harmer
11.292
972043AH1-570 GEN
Solar/Wind Harmer
2.711
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971981AH1-535 GEN
Solar/Wind Harmer
15.391
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972165AH1-665 GEN
Solar/Wind Harmer
8.445
971985AH1-537 GEN
Solar/Wind Harmer
17.677
946321AF1-296 GEN
Solar/Wind Harmer
10.113
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
253406AD2-031_GEN
Solar/Wind Harmer
1.232
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
971171AH1-044 GEN
Solar/Wind Harmer
5.775
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
7.595
966021AG1-471 GEN
Solar/Wind Harmer
6.598
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964571AG1-320 GEN
Solar/Wind Harmer
9.075
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194508D.CRK3
Adder
1.39
927014AC1-188 GEN
Solar/Wind Harmer
1.534
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
274695ROCKY RD ;2P
Adder
10.525
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
3144873MCLAUGH
Solar/Wind Helper
0.006
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
7.852
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
965931AG1-462 GEN
Solar/Wind Harmer
24.757
965091AG1-374 GEN
Solar/Wind Harmer
28.952
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274760LEE CO EC;1U
Adder
8.921
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
957471AF2-041 GEN
Solar/Wind Harmer
8.663
3145506HICKORY
Solar/Wind Helper
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
21.289
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
55.22
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971461AH1-227 GEN
Solar/Wind Harmer
5.589
3429391JKCT 9G
Adder
9.312
958171AF2-111 GEN
Solar/Wind Harmer
18.095
252507AC2-088 GEN
Solar/Wind Harmer
0.312
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
959611AF2-252 GEN
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
970781AG2-491 GEN
Solar/Wind Harmer
6.551
274730ELWOOD EC;6P
Adder
15.424
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
274887GEN-1.85
Solar/Wind Harmer
0.17
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
3147666LOUISA
Solar/Wind Helper
1.282
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3142543TWELFTH
Solar/Wind Helper
0.026
316404AE1-155 C
Solar/Wind Helper
2.284
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
238152AF2-075_GEN
Solar/Wind Helper
0.614
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
1.199
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
970653AG2-424 GEN
Solar/Wind Harmer
3.801
3429421JKCT 10G
Adder
9.312
970091AG2-072 GEN
Adder
78.951
971687AH1-348 GEN
Solar/Wind Harmer
1.083
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
252510AF1-249 C
Solar/Wind Harmer
0.052
276621W2-048 GEN
Solar/Wind Harmer
0.343
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
9.386
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
970569AG2-363 GEN
Solar/Wind Harmer
19.98
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.474
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734905WLF1G5
50/50
10.494
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971981AH1-535 GEN
Solar/Wind Harmer
7.159
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
971985AH1-537 GEN
Solar/Wind Harmer
2.055
946321AF1-296 GEN
Solar/Wind Harmer
3.787
274853TWINGROVE;U1
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
972267AH1-718 GEN
Adder
4.004
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
24386405FR-21G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.878
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
2.173
3148013FISHERV
Solar/Wind Helper
0.229
316405AF2-144 C
Solar/Wind Helper
0.345
3143873LANEXA
Solar/Wind Helper
0.159
3138133OCRAN
Solar/Wind Helper
0.079
3141873WAN 176
Solar/Wind Helper
0.052
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
3143316POE
Solar/Wind Helper
0.966
316236AE1-162_GEN
Solar/Wind Helper
0.317
24728305BUCHG2
50/50
8.141
24686505CER G6
Adder
10.257
3429241JKCT 3G
Adder
13.348
965911AG1-460 GEN
Solar/Wind Harmer
1.381
276708O09 GEN2
Solar/Wind Harmer
0.237
274766LEE CO EC;7U
Adder
8.816
270437AC2-090 C
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
939401AE1-172 GEN
Solar/Wind Harmer
4.936
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
24734805WLF1G4
50/50
10.494
24735105WLF2G1
50/50
10.407
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
972163AH1-664 GEN
Solar/Wind Harmer
8.2
944221AF1-090 GEN
Solar/Wind Harmer
4.083
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
5.265
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
270263AC1-001 GEN
Solar/Wind Harmer
0.649
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
316164AC1-076 GEN
Solar/Wind Helper
1.46
316233AE1-074 FULL
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.268
957601AF2-054 GEN
Solar/Wind Helper
0.352
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.095
3147666LOUISA
Solar/Wind Helper
0.737
3141906WESTMOR
Solar/Wind Helper
0.108
316458AB2-190 GEN2
Solar/Wind Helper
1.421
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.006
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
972043AH1-570 GEN
Solar/Wind Harmer
1.967
25194408D.CRK1
Adder
7.436
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
960611AF2-352 GEN
Solar/Wind Harmer
2.244
274764LEE CO EC;5U
Adder
8.942
972235AH1-702 GEN1
Adder
2.407
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274693ROCKY RD ;1P
Adder
10.421
958481AF2-142 GEN
Solar/Wind Harmer
9.873
970883AG2-550 GEN
Solar/Wind Harmer
6.563
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
270599AE1-208 GEN
Solar/Wind Harmer
5.99
960971AF2-388 GEN
Solar/Wind Harmer
3.788
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316450AC1-158 RIC
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.269
238148AE2-230_GEN2
Solar/Wind Helper
0.43
316033AB2-134 GEN
Solar/Wind Helper
0.848
3145506HICKORY
Solar/Wind Helper
0.9
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
966021AG1-471 GEN
Solar/Wind Harmer
4.603
964571AG1-320 GEN
Solar/Wind Harmer
7.052
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.39
274765LEE CO EC;6U
Adder
8.942
274763LEE CO EC;4U
Adder
8.837
972236AH1-702 GEN2
Adder
2.093
276872AE1-163_GEN1
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274695ROCKY RD ;2P
Adder
10.525
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970885AG2-551 GEN
Solar/Wind Harmer
2.188
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.594
964611AG1-324 GEN
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
9.391
945421AF1-207 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.802
316045AC1-158 PL2
Solar/Wind Helper
5.375
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.386
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
316240AF1-291 C
Solar/Wind Helper
0.345
238149AF1-291A_GEN
Solar/Wind Helper
0.123
970773AG2-487 GEN
Solar/Wind Harmer
1.193
960001AF2-291 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
970819AG2-516 GEN
Solar/Wind Harmer
8.002
274822ROCKFORD ;11
Adder
18.727
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
971073AG2-665 GEN
Solar/Wind Harmer
1.095
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.385
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270173AC1-122 GEN
Solar/Wind Helper
2.9
270494AE1-108_GEN
Solar/Wind Helper
5.248
3132273ORANGE
Solar/Wind Helper
0.063
3146776BUCKING
Solar/Wind Helper
0.099
316223AC1-118
Solar/Wind Helper
0.414
23546401DTGZ2-030
Solar/Wind Helper
0.079
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.153
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
959341AF2-225 GEN
Solar/Wind Harmer
7.039
970169AG2-114 GEN
Solar/Wind Harmer
6.65
274744AC1-111 GEN8
Adder
5.265
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274735ELWOOD EC;4P
Adder
15.424
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.419
3148463FAIRFLD
Solar/Wind Helper
0.479
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
315651AD1-115 GEN
Solar/Wind Helper
1.023
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
24735205WLF2G2
50/50
10.407
972203AH1-686 GEN
Adder
2.845
964901AG1-354 GEN
Solar/Wind Harmer
12.202
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
945681AF1-233 GEN
Solar/Wind Harmer
13.842
252516AE2-318_GEN
Solar/Wind Harmer
7.707
25194608D.CRK4
Adder
1.616
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
19.952
970613AG2-401 GEN
Solar/Wind Harmer
4.873
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.265
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274676JOLIET 29;8U
Adder
28.777
965651AG1-433 GEN
Solar/Wind Harmer
1.894
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
1.294
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3142946ENON
Solar/Wind Helper
0.089
227287AC2-120 GEN
Solar/Wind Helper
0.324
3145336SMITFLD
Solar/Wind Helper
0.094
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
971125AH1-004 GEN
Solar/Wind Harmer
3.067
971587AH1-292 GEN
Solar/Wind Harmer
5.167
276916AD2-100_GEN
Solar/Wind Harmer
14.524
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
276901AD2-066 C O1
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.152
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
276776AD2-060 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
7.912
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
238147AE2-230_GEN1
Solar/Wind Helper
0.43
316294AC1-161 GEN
Solar/Wind Helper
4.313
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
972103AH1-617 GEN
Solar/Wind Harmer
20.275
270030AE2-140 GEN
Solar/Wind Harmer
16.527
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
24728505AND G1
Adder
3.754
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
971087AG2-675 GEN
Solar/Wind Harmer
3.613
274767LEE CO EC;8U
Adder
8.816
959091AF2-200 GEN
Solar/Wind Harmer
13.301
274682WAUKEGAN ;7U
Adder
16.992
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
247642Z2-115 C
Solar/Wind Harmer
0.003
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
276806AD2-047 C O1
Solar/Wind Harmer
3.695
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
316447AC1-158 HLD
Solar/Wind Helper
3.697
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
315975AC1-164 GENB
Solar/Wind Helper
0.103
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
3145336SMITFLD
Solar/Wind Helper
0.939
316375AC2-012 GEN
Solar/Wind Helper
0.602
971313AH1-133 GEN
Solar/Wind Harmer
5.791
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
25196408WSDLE3
Adder
8.661
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
270543AE2-219 C
Solar/Wind Harmer
4.594
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
270071AF1-092 GEN
Solar/Wind Harmer
12.068
971771AH1-392 GEN
Solar/Wind Harmer
6.242
3148133STUARTS
Solar/Wind Helper
0.239
316258AE1-075 C
Solar/Wind Helper
0.414
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141913WHIT STONE
Solar/Wind Helper
0.263
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
316316AC1-027 C
Solar/Wind Helper
0.36
970107AG2-081 GEN
Solar/Wind Harmer
2.3
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274762LEE CO EC;3U
Adder
8.921
938861AE1-114 GEN
Solar/Wind Harmer
3.787
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
19.833
274696ROCKY RD ;4P
Adder
10.774
274697ROCKY RD ;3P
Adder
2.859
970879AG2-548 GEN
Solar/Wind Harmer
1.095
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
970941AG2-585 GEN
Solar/Wind Harmer
3.587
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3143526WINTERP
Solar/Wind Helper
1.488
316312AB1-027
Solar/Wind Helper
0.538
316411AF1-147_GEN1
Solar/Wind Helper
0.888
237061AD1-155 GEN
Solar/Wind Helper
1.625
316185AD1-033 GEN
Solar/Wind Helper
1.07
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.43
970825AG2-519 GEN
Solar/Wind Harmer
2.341
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
945371AF1-202 GEN
Solar/Wind Harmer
0
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
24415905BUCK
50/50
0.034
24686405CER G5
Adder
10.176
970653AG2-424 GEN
Solar/Wind Harmer
0.788
970455AG2-298 GEN
Solar/Wind Harmer
3.03
965931AG1-462 GEN
Solar/Wind Harmer
17.272
965091AG1-374 GEN
Solar/Wind Harmer
20.199
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274760LEE CO EC;1U
Adder
8.921
24379505HDWTR1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
24690905MDL-1G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
1.683
276843GEN-1.7
Solar/Wind Harmer
0.211
964401AG1-302 GEN
Solar/Wind Harmer
0.001
253325AC1-069 GEN
Solar/Wind Harmer
0.007
3146776BUCKING
Solar/Wind Helper
0.11
316337AD2-073 GEN
Solar/Wind Helper
0.41
3141726DUNNSVL
Solar/Wind Helper
1.072
316132AB2-190 GEN1
Solar/Wind Helper
1.421
315773AC2-141 GEN
Solar/Wind Helper
5.077
316036AC1-147 C
Solar/Wind Helper
0.349
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
964861AG1-349 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.316
3147312GRETNA
Solar/Wind Helper
0.079
315821AE2-092 GEN
Solar/Wind Helper
3.335
3141196NOKESVL
Solar/Wind Helper
1.125
316075AC2-137 C
Solar/Wind Helper
0.419
316077AC2-138 C
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.513
316123AC1-075 GEN
Solar/Wind Helper
1.507
226910AB2-157 C
Solar/Wind Helper
0.013
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24689505VACITY
50/50
6.512
972273AH1-721 GEN
Adder
102.336
970093AG2-073 GEN
Solar/Wind Harmer
6.77
972167AH1-666 GEN
Solar/Wind Harmer
5.868
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
942481AE2-261 GEN
Solar/Wind Harmer
20.643
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
13.32
270240V3-007_GEN2
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
970825AG2-519 GEN
Solar/Wind Harmer
4.967
970879AG2-548 GEN
Solar/Wind Harmer
4.818
274729ELWOOD EC;1P
Adder
15.424
972259AH1-714 GEN
Adder
8.841
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3143526WINTERP
Solar/Wind Helper
1.488
964211AG1-282 GEN
Solar/Wind Helper
0.361
316415AF1-147_GEN2
Solar/Wind Helper
0.888
315671AE2-027_GEN
Solar/Wind Helper
2.046
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
LGEELTFEXP_LGEE->PJM
CLTF
7.385
MECLTFEXP_MEC->PJM
CLTF
16.891
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
NYPJM->LTFIMP_NY
CLTF
3.354
TVALTFEXP_TVA->PJM
CLTF
12.171
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
CPLELTFEXP_CPLE->PJM
CLTF
4.545
SIGELTFEXP_SIGE->PJM
CLTF
0.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
WECLTFEXP_WEC->PJM
CLTF
3.657
LAGNLTFEXP_LAGN->PJM
CLTF
22.903

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:327.42
MW Contribution:
33.38
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:309.28
MW Contribution:
33.1
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
4.417
24734905WLF1G5
Adder
4.417
971461AH1-227 GEN
Solar/Wind Harmer
2.867
970563AG2-360 GEN
50/50
33.379
24689505VACITY
50/50
3.467
972273AH1-721 GEN
Adder
15.55
24290005CRG1L
50/50
0.584
971687AH1-348 GEN
Solar/Wind Harmer
0.543
24290205CRG2L
50/50
0.6
24290105CRG2H
50/50
0.716
24735205WLF2G2
Adder
3.651
24289905CRG1H
50/50
0.697
24734805WLF1G4
Adder
4.417
24735105WLF2G1
Adder
3.651
971225AH1-072 GEN
Solar/Wind Harmer
1.118
971227AH1-073 GEN
Solar/Wind Harmer
1.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.433
CPLELTFEXP_CPLE->PJM
CLTF
0.364
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.09
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
2.913
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.839
LGEELTFEXP_LGEE->PJM
CLTF
0.644
MECLTFEXP_MEC->PJM
CLTF
1.418
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.741
NYPJM->LTFIMP_NY
CLTF
0.199
TVALTFEXP_TVA->PJM
CLTF
1.772

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#14149_05BROADF 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.73 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:307.05
MW Contribution:
33.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:276.62
MW Contribution:
33.23
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
971461AH1-227 GEN
Solar/Wind Harmer
2.861
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.542
24290205CRG2L
50/50
0.598
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.603
24289905CRG1H
50/50
0.695
24734805WLF1G4
Adder
4.382
24735105WLF2G1
Adder
3.603
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LGEELTFEXP_LGEE->PJM
CLTF
0.617
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.291
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
WECLTFEXP_WEC->PJM
CLTF
0.233
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P4_#2916_05J.FERR 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:306.22
MW Contribution:
33.38
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:93.09 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:275.54
MW Contribution:
33.21
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
4.38
24734905WLF1G5
Adder
4.38
971461AH1-227 GEN
Solar/Wind Harmer
2.859
970563AG2-360 GEN
50/50
33.385
24689505VACITY
50/50
3.455
972273AH1-721 GEN
Adder
14.808
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.541
24290205CRG2L
50/50
0.598
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.602
24289905CRG1H
50/50
0.695
24734805WLF1G4
Adder
4.38
24735105WLF2G1
Adder
3.602
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.402
WECLTFEXP_WEC->PJM
CLTF
0.232
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.899
LGEELTFEXP_LGEE->PJM
CLTF
0.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.477
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.16
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.288
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.779
TVALTFEXP_TVA->PJM
CLTF
1.558

Details for 05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line l/o AEP_P1-2_#2915_4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.16 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:305.34
MW Contribution:
33.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.88 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:274.93
MW Contribution:
33.23
Bus #Bus NameTypeMW Contribution
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
1.996
24734805WLF1G4
Adder
4.382
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.378
24290205CRG2L
50/50
0.598
24289905CRG1H
50/50
0.695
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
24735105WLF2G1
Adder
3.603
24735205WLF2G2
Adder
3.603
971225AH1-072 GEN
Solar/Wind Harmer
0.778
971227AH1-073 GEN
Solar/Wind Harmer
0.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.291
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
WECLTFEXP_WEC->PJM
CLTF
0.233
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LGEELTFEXP_LGEE->PJM
CLTF
0.617
LAGNLTFEXP_LAGN->PJM
CLTF
2.473

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.51 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:347.84
MW Contribution:
33.38
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11112_05J.FERR 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:329.6
MW Contribution:
33.1
Bus #Bus NameTypeMW Contribution
24290205CRG2L
50/50
0.6
971313AH1-133 GEN
Solar/Wind Harmer
20.638
24735205WLF2G2
Adder
3.651
24290105CRG2H
50/50
0.716
24289905CRG1H
50/50
0.697
24734705WLF1G3
Adder
4.417
24734905WLF1G5
Adder
4.417
971461AH1-227 GEN
Solar/Wind Harmer
2.867
24734805WLF1G4
Adder
4.417
24735105WLF2G1
Adder
3.651
970563AG2-360 GEN
50/50
33.379
24689505VACITY
50/50
3.467
972273AH1-721 GEN
Adder
15.55
24290005CRG1L
50/50
0.584
971687AH1-348 GEN
Solar/Wind Harmer
0.543
971225AH1-072 GEN
Solar/Wind Harmer
1.118
971227AH1-073 GEN
Solar/Wind Harmer
1.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.433
CPLELTFEXP_CPLE->PJM
CLTF
0.364
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.09
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
2.913
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.839
LGEELTFEXP_LGEE->PJM
CLTF
0.644
MECLTFEXP_MEC->PJM
CLTF
1.418
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.741
NYPJM->LTFIMP_NY
CLTF
0.199
TVALTFEXP_TVA->PJM
CLTF
1.772

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#14149_05BROADF 765_Q2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:327.47
MW Contribution:
33.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14149_05BROADF 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.33 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:296.98
MW Contribution:
33.23
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
971461AH1-227 GEN
Solar/Wind Harmer
2.861
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.542
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.662
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.603
24289905CRG1H
50/50
0.695
24734805WLF1G4
Adder
4.382
24735105WLF2G1
Adder
3.603
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
WECLTFEXP_WEC->PJM
CLTF
0.233
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LGEELTFEXP_LGEE->PJM
CLTF
0.617
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.291

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P4_#2916_05J.FERR 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.35 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:326.65
MW Contribution:
33.38
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2916_05J.FERR 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.96 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:295.89
MW Contribution:
33.21
Bus #Bus NameTypeMW Contribution
24734705WLF1G3
Adder
4.38
24734905WLF1G5
Adder
4.38
971461AH1-227 GEN
Solar/Wind Harmer
2.859
970563AG2-360 GEN
50/50
33.385
24689505VACITY
50/50
3.455
972273AH1-721 GEN
Adder
14.808
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.541
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
20.659
24290105CRG2H
50/50
0.714
24735205WLF2G2
Adder
3.602
24289905CRG1H
50/50
0.695
24734805WLF1G4
Adder
4.38
24735105WLF2G1
Adder
3.602
971225AH1-072 GEN
Solar/Wind Harmer
1.115
971227AH1-073 GEN
Solar/Wind Harmer
1.115
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.16
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.288
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.779
TVALTFEXP_TVA->PJM
CLTF
1.558
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.402
WECLTFEXP_WEC->PJM
CLTF
0.232
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.899
LGEELTFEXP_LGEE->PJM
CLTF
0.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.477

Details for AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line l/o AEP_P1-2_#2915_4_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:316.99
MW Contribution:
33.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AH1-133 TP-05TAZEWE 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#2915_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:96.8 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:286.52
MW Contribution:
33.23
Bus #Bus NameTypeMW Contribution
24290105CRG2H
50/50
0.714
971461AH1-227 GEN
Solar/Wind Harmer
1.996
24734805WLF1G4
Adder
4.382
24735105WLF2G1
Adder
3.603
970563AG2-360 GEN
50/50
33.396
24689505VACITY
50/50
3.456
972273AH1-721 GEN
Adder
14.819
24290005CRG1L
50/50
0.582
971687AH1-348 GEN
Solar/Wind Harmer
0.378
24290205CRG2L
50/50
0.598
971313AH1-133 GEN
Solar/Wind Harmer
11.888
24289905CRG1H
50/50
0.695
24734705WLF1G3
Adder
4.382
24734905WLF1G5
Adder
4.382
24735205WLF2G2
Adder
3.603
971225AH1-072 GEN
Solar/Wind Harmer
0.778
971227AH1-073 GEN
Solar/Wind Harmer
0.778
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.74
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.399
WECLTFEXP_WEC->PJM
CLTF
0.233
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.897
LGEELTFEXP_LGEE->PJM
CLTF
0.617
LAGNLTFEXP_LAGN->PJM
CLTF
2.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.191
NYPJM->LTFIMP_NY
CLTF
0.186
MECLTFEXP_MEC->PJM
CLTF
1.291
CONTINGENCY 'AEP_P4_#3098_05BROADF 765_Q1_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 138KV_SRT-A'
 OPEN BUS 314348   /*2GRETN_1      69.0
 OPEN BUS 314667   /*4ALTVSTA     138.0
 OPEN BUS 314670   /*2ALTVSTA      69.0
 OPEN BUS 314680   /*2CHATHAM      69.0
 OPEN BUS 314685   /*2CHTM TP      69.0
 OPEN BUS 314698   /*2TAYLORS MIL  69.0
 OPEN BUS 314709   /*2GLADYS TAP   69.0
 OPEN BUS 314727   /*2CLIMAX DP    69.0
 OPEN BUS 314728   /*2CLMX TP      69.0
 OPEN BUS 314729   /*2GLADYS       69.0
 OPEN BUS 314730   /*3STONE MILL   69.0
 OPEN BUS 314731   /*2GRETNA       69.0
 OPEN BUS 314733   /*2GRNA DP      69.0
 OPEN BUS 314735   /*2ALTAVISTADP  69.0
 OPEN BUS 314736   /*2SHKO DP      69.0
 OPEN BUS 314738   /*2MT AIRY      69.0
 OPEN BUS 314739   /*2MT A TP      69.0
 OPEN BUS 316193   /*RENANTP       69.0
 OPEN BUS 316194   /*AC1-042 MAIN  69.0
 OPEN BUS 316195   /*AC1-042 COL   34.0
 OPEN BUS 316196   /*AC1-042 TERT  13.0
 OPEN BUS 316197   /*AC1-042 GEN    0.4
 OPEN BUS 316214   /*AC1-145 MAIN  69.0
 OPEN BUS 316215   /*AC1-145 COL2  34.5
 OPEN BUS 316216   /*AC1-145 COL1  34.5
 OPEN BUS 316217   /*AC1-145 GEN    0.6
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1    /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1    /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1    /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1    /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'AEP_P4_#14149_05BROADF 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P4_#2916_05J.FERR 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242509 TO BUS 242545 CKT 1    /*05AXTON      765.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242509 TO BUS 290609 CKT Z1   /*05AXTON      765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290609 CKT 1    /*05J.FERR     765.0 - 05AXTON_RJ   765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT SR   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242544 TO BUS 242545 CKT ZB   /*05AXTON      138.0 - 05AXTONX     138.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
CONTINGENCY 'AEP_P1-2_#2915_4_SRT-A'
 OPEN BRANCH FROM BUS 242511 TO BUS 290615 CKT Z1   /*05BROADF     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290615 CKT 1    /*05J.FERR     765.0 - 05BROADFR_RJ 765.0
 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB   /*05BROADF     138.0 - 05BROADX     138.0
END
242542 to 242780 ckt 1
242566 to 242567 ckt ZB
242567 to 242803 ckt 1
290610 to 242512 ckt Z1
290614 to 242515 ckt 1
242514 to 290610 ckt 1
242788 to 971312 ckt 1
971312 to 242827 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
26.9
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
26.9
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
45.8
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC115.66 %3610.0B4175.28
45.92
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC115.4 %3610.0B4165.98
45.84
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC115.26 %3610.0B4160.96
45.8
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC114.94 %3610.0B4149.41
45.81

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
26.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
959341AF2-225 GEN
Solar/Wind Harmer
7.012
970169AG2-114 GEN
Solar/Wind Harmer
4.633
274744AC1-111 GEN8
Adder
2.557
274735ELWOOD EC;4P
Adder
7.484
3148463FAIRFLD
Solar/Wind Helper
0.399
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316059AD1-063 C
Solar/Wind Helper
0.113
943031AE2-326 GEN
Solar/Wind Harmer
3.912
960911AF2-382 GEN
Solar/Wind Harmer
5.846
972103AH1-617 GEN
Solar/Wind Harmer
13.916
270030AE2-140 GEN
Solar/Wind Harmer
10.987
957381AF2-032 GEN
Solar/Wind Harmer
0.966
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
24728505AND G1
Adder
1.803
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
959091AF2-200 GEN
Solar/Wind Harmer
9.281
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
316192AB2-158 GEN
Solar/Wind Helper
0.989
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
971461AH1-227 GEN
Solar/Wind Harmer
3.852
3429391JKCT 9G
Adder
4.482
958171AF2-111 GEN
Solar/Wind Harmer
12.218
970193AG2-126 GEN
Solar/Wind Harmer
7.158
24728705AND G3
Adder
3.771
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
25196608WSDLE5
Adder
3.933
274730ELWOOD EC;6P
Adder
7.484
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
238152AF2-075_GEN
Solar/Wind Helper
0.306
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316404AE1-155 C
Solar/Wind Helper
0.959
24735105WLF2G1
Adder
4.907
24734805WLF1G4
Adder
4.896
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
972163AH1-664 GEN
Solar/Wind Harmer
4.973
944221AF1-090 GEN
Solar/Wind Harmer
5.329
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
276726Z2-087_GEN
Solar/Wind Harmer
3.696
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
25196508WSDLE4
Adder
3.893
274746AC1-111 G10
Adder
2.557
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
316164AC1-076 GEN
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.113
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970653AG2-424 GEN
Solar/Wind Harmer
0.386
970455AG2-298 GEN
Solar/Wind Harmer
1.905
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
965931AG1-462 GEN
Solar/Wind Harmer
12.097
965091AG1-374 GEN
Solar/Wind Harmer
14.092
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274760LEE CO EC;1U
Adder
4.348
3146776BUCKING
Solar/Wind Helper
0.05
316337AD2-073 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.452
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.667
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
276686W4-005 GEN3
Solar/Wind Harmer
1.44
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
276655WTG1_EQ
Solar/Wind Harmer
4.08
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
3132273ORANGE
Solar/Wind Helper
0.03
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
316223AC1-118
Solar/Wind Helper
0.174
970563AG2-360 GEN
50/50
26.903
962751AG1-124 GEN
Solar/Wind Harmer
9.059
972273AH1-721 GEN
Adder
50.356
970093AG2-073 GEN
Solar/Wind Harmer
2.932
972167AH1-666 GEN
Solar/Wind Harmer
3.959
942481AE2-261 GEN
Solar/Wind Harmer
14.451
971993AH1-541 GEN
Solar/Wind Harmer
4.402
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
276603SUBLETTE C
Solar/Wind Harmer
0.49
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.484
3147983MERCK5
Solar/Wind Helper
0.108
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
971687AH1-348 GEN
Solar/Wind Harmer
0.746
276621W2-048 GEN
Solar/Wind Harmer
2.987
25196008MFTGT1
Adder
0.654
25196808ZIMRHP
Adder
35.505
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
970569AG2-363 GEN
Solar/Wind Harmer
13.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
23583801GRNGAP
Solar/Wind Helper
2.128
316075AC2-137 C
Solar/Wind Helper
0.18
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971313AH1-133 GEN
Solar/Wind Harmer
4.584
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
274728ELWOOD EC;5P
Adder
7.484
3148133STUARTS
Solar/Wind Helper
0.172
316258AE1-075 C
Solar/Wind Helper
0.181
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
3141426STAFORD
Solar/Wind Helper
0.025
276889AE2-281 GEN
Solar/Wind Harmer
0.021
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
971125AH1-004 GEN
Solar/Wind Harmer
2.108
24728305BUCHG2
Adder
3.63
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
3429241JKCT 3G
Adder
6.43
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276708O09 GEN2
Solar/Wind Harmer
1.676
276656WTG2_EQ
Solar/Wind Harmer
0.54
274766LEE CO EC;7U
Adder
4.297
274732ELWOOD EC;7P
Adder
7.484
971485AH1-239 GEN
Solar/Wind Harmer
4.84
964781AG1-341 GEN
Solar/Wind Harmer
6.17
942891AE2-308 GEN
Solar/Wind Harmer
5.443
972043AH1-570 GEN
Solar/Wind Harmer
1.293
276615X2-022 GEN
Solar/Wind Harmer
0.938
945391AF1-204 GEN
Solar/Wind Harmer
6.651
960611AF2-352 GEN
Solar/Wind Harmer
1.092
274764LEE CO EC;5U
Adder
4.358
972235AH1-702 GEN1
Adder
1.172
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
274693ROCKY RD ;1P
Adder
5.064
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316450AC1-158 RIC
Solar/Wind Helper
0.176
316487AF1-042 GEN
Solar/Wind Helper
0.113
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
24734705WLF1G3
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
270399AC1-101 GEN
Solar/Wind Harmer
2.774
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972165AH1-665 GEN
Solar/Wind Harmer
3.979
946321AF1-296 GEN
Solar/Wind Harmer
4.94
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
972267AH1-718 GEN
Adder
1.953
274823ROCKFORD ;21
Adder
9.053
971171AH1-044 GEN
Solar/Wind Harmer
9.281
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148013FISHERV
Solar/Wind Helper
0.165
316405AF2-144 C
Solar/Wind Helper
0.151
3143873LANEXA
Solar/Wind Helper
0.067
274674JOLIET 9 ;6U
Adder
7.01
3148013FISHERV
Solar/Wind Helper
0.287
3147666LOUISA
Solar/Wind Helper
0.335
3141906WESTMOR
Solar/Wind Helper
0.046
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
966021AG1-471 GEN
Solar/Wind Harmer
3.282
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964571AG1-320 GEN
Solar/Wind Harmer
4.43
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276911AD2-131_GEN
Solar/Wind Harmer
2.055
274765LEE CO EC;6U
Adder
4.358
274763LEE CO EC;4U
Adder
4.307
972236AH1-702 GEN2
Adder
1.019
252509AD1-136 GEN
Solar/Wind Harmer
0.119
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.115
24728805RICHG1
Adder
1.729
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316045AC1-158 PL2
Solar/Wind Helper
2.117
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
276916AD2-100_GEN
Solar/Wind Harmer
10.169
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
238147AE2-230_GEN1
Solar/Wind Helper
0.214
316097T157 G90
Solar/Wind Helper
0.557
24735205WLF2G2
Adder
4.907
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
945681AF1-233 GEN
Solar/Wind Harmer
9.341
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
957471AF2-041 GEN
Solar/Wind Harmer
13.921
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274676JOLIET 29;8U
Adder
13.963
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
316095T157 G97
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.038
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
339236AF1-050_GEN
Solar/Wind Harmer
1.045
970107AG2-081 GEN
Solar/Wind Harmer
1.581
276838X2-022 GEN2
Solar/Wind Harmer
0.111
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274762LEE CO EC;3U
Adder
4.348
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
274696ROCKY RD ;4P
Adder
5.236
274697ROCKY RD ;3P
Adder
1.389
237061AD1-155 GEN
Solar/Wind Helper
0.84
316312AB1-027
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Helper
0.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
LGEELTFEXP_LGEE->PJM
CLTF
3.563
MECLTFEXP_MEC->PJM
CLTF
8.317
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
NYPJM->LTFIMP_NY
CLTF
1.48
TVALTFEXP_TVA->PJM
CLTF
6.216
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
CPLELTFEXP_CPLE->PJM
CLTF
3.109
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
11.701

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
26.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970107AG2-081 GEN
Solar/Wind Harmer
1.103
276838X2-022 GEN2
Solar/Wind Harmer
0.188
943031AE2-326 GEN
Solar/Wind Harmer
3.912
960911AF2-382 GEN
Solar/Wind Harmer
4.078
972103AH1-617 GEN
Solar/Wind Harmer
9.709
270030AE2-140 GEN
Solar/Wind Harmer
7.666
957381AF2-032 GEN
Solar/Wind Harmer
0.764
971087AG2-675 GEN
Solar/Wind Harmer
1.765
24728505AND G1
Adder
1.803
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
274734ELWOOD EC;8P
Adder
7.484
24734705WLF1G3
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
270399AC1-101 GEN
Solar/Wind Harmer
1.444
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972165AH1-665 GEN
Solar/Wind Harmer
3.094
946321AF1-296 GEN
Solar/Wind Harmer
1.85
972267AH1-718 GEN
Adder
1.953
274823ROCKFORD ;21
Adder
9.053
971171AH1-044 GEN
Solar/Wind Harmer
6.475
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
24386405FR-21G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
253406AD2-031_GEN
Solar/Wind Harmer
0.23
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
1.809
3148013FISHERV
Solar/Wind Helper
0.165
316405AF2-144 C
Solar/Wind Helper
0.151
3143873LANEXA
Solar/Wind Helper
0.067
971461AH1-227 GEN
Solar/Wind Harmer
2.687
3429391JKCT 9G
Adder
4.482
958171AF2-111 GEN
Solar/Wind Harmer
8.524
970193AG2-126 GEN
Solar/Wind Harmer
4.994
24728705AND G3
Adder
3.771
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274730ELWOOD EC;6P
Adder
7.484
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
24686405CER G5
Adder
4.71
970653AG2-424 GEN
Solar/Wind Harmer
0.386
970455AG2-298 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
8.44
965091AG1-374 GEN
Solar/Wind Harmer
9.832
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274760LEE CO EC;1U
Adder
4.348
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
238152AF2-075_GEN
Solar/Wind Helper
0.306
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316404AE1-155 C
Solar/Wind Helper
0.959
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
970091AG2-072 GEN
Adder
38.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.375
970773AG2-487 GEN
Solar/Wind Harmer
0.568
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
970373AG2-245 GEN
Solar/Wind Harmer
6.5
3132273ORANGE
Solar/Wind Helper
0.03
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
316223AC1-118
Solar/Wind Helper
0.174
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
966021AG1-471 GEN
Solar/Wind Harmer
2.29
964571AG1-320 GEN
Solar/Wind Harmer
3.443
972045AH1-571 GEN
Solar/Wind Harmer
0.751
276911AD2-131_GEN
Solar/Wind Harmer
0.467
274765LEE CO EC;6U
Adder
4.358
274763LEE CO EC;4U
Adder
4.307
971313AH1-133 GEN
Solar/Wind Harmer
2.637
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
962751AG1-124 GEN
Solar/Wind Harmer
6.205
972273AH1-721 GEN
Adder
50.356
970093AG2-073 GEN
Solar/Wind Harmer
3.273
972167AH1-666 GEN
Solar/Wind Harmer
2.762
942481AE2-261 GEN
Solar/Wind Harmer
10.082
971993AH1-541 GEN
Solar/Wind Harmer
1.535
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
274729ELWOOD EC;1P
Adder
7.484
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.365
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
3147983MERCK5
Solar/Wind Helper
0.108
3143526WINTERP
Solar/Wind Helper
0.609
964211AG1-282 GEN
Solar/Wind Helper
0.152
971687AH1-348 GEN
Solar/Wind Harmer
0.521
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
25196808ZIMRHP
Adder
35.505
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
970569AG2-363 GEN
Solar/Wind Harmer
9.723
971997AH1-543 GEN
Solar/Wind Harmer
1.689
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.334
315821AE2-092 GEN
Solar/Wind Helper
1.831
23583801GRNGAP
Solar/Wind Helper
2.128
316075AC2-137 C
Solar/Wind Helper
0.18
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
7.484
270543AE2-219 C
Solar/Wind Harmer
2.176
270071AF1-092 GEN
Solar/Wind Harmer
5.772
3148133STUARTS
Solar/Wind Helper
0.172
316258AE1-075 C
Solar/Wind Helper
0.181
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
3141426STAFORD
Solar/Wind Helper
0.025
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
24735205WLF2G2
50/50
5.207
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
943811AF1-049 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
6.517
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.712
252516AE2-318_GEN
Solar/Wind Harmer
3.594
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
971125AH1-004 GEN
Solar/Wind Harmer
1.471
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
959341AF2-225 GEN
Solar/Wind Harmer
3.424
970169AG2-114 GEN
Solar/Wind Harmer
3.232
274744AC1-111 GEN8
Adder
2.557
274735ELWOOD EC;4P
Adder
7.484
970289AG2-191 GEN
Solar/Wind Harmer
0.599
958391AF2-133 GEN
Solar/Wind Harmer
0
3148463FAIRFLD
Solar/Wind Helper
0.399
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316059AD1-063 C
Solar/Wind Helper
0.113
946181AF1-283 GEN
Solar/Wind Harmer
4.107
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
946031AF1-268 GEN
Solar/Wind Harmer
2.979
316192AB2-158 GEN
Solar/Wind Helper
0.989
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
13.963
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
970613AG2-401 GEN
Solar/Wind Harmer
2.314
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
316499AE2-029_GEN
Solar/Wind Helper
0.937
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
316095T157 G97
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.038
24728305BUCHG2
Adder
3.63
24686505CER G6
Adder
4.748
3429241JKCT 3G
Adder
6.43
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276708O09 GEN2
Solar/Wind Harmer
0.116
274766LEE CO EC;7U
Adder
4.297
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
972043AH1-570 GEN
Solar/Wind Harmer
0.938
276615X2-022 GEN
Solar/Wind Harmer
0.035
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
274764LEE CO EC;5U
Adder
4.358
972235AH1-702 GEN1
Adder
1.172
276876AE1-163_GEN2
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
274693ROCKY RD ;1P
Adder
5.064
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728905RICHG2
Adder
1.729
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
926881AC1-175 GEN
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
2.854
970883AG2-550 GEN
Solar/Wind Harmer
3.108
960971AF2-388 GEN
Solar/Wind Harmer
1.8
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316450AC1-158 RIC
Solar/Wind Helper
0.176
316487AF1-042 GEN
Solar/Wind Helper
0.113
972236AH1-702 GEN2
Adder
1.019
252509AD1-136 GEN
Solar/Wind Harmer
0.016
24735105WLF2G1
50/50
5.207
24734805WLF1G4
50/50
5.196
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
972163AH1-664 GEN
Solar/Wind Harmer
3.863
944221AF1-090 GEN
Solar/Wind Harmer
1.996
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
270356AE2-297 GEN
Solar/Wind Harmer
0
25196508WSDLE4
Adder
3.893
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
971609AH1-304 GEN
Solar/Wind Harmer
0.508
964611AG1-324 GEN
Solar/Wind Harmer
1.21
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141813NORNECK
Solar/Wind Helper
0.113
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
276903AD2-071 C
Solar/Wind Harmer
3.542
270437AC2-090 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
3147666LOUISA
Solar/Wind Helper
0.335
3141906WESTMOR
Solar/Wind Helper
0.046
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.102
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
0.781
3146776BUCKING
Solar/Wind Helper
0.05
316337AD2-073 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.452
276872AE1-163_GEN1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
0.65
274695ROCKY RD ;2P
Adder
5.115
24728805RICHG1
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
4.553
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
965791AG1-447 GEN
Solar/Wind Harmer
2.8
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316045AC1-158 PL2
Solar/Wind Helper
2.117
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274762LEE CO EC;3U
Adder
4.348
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.643
274696ROCKY RD ;4P
Adder
5.236
274697ROCKY RD ;3P
Adder
1.389
276893AG1-478 C
Solar/Wind Harmer
0.212
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
970941AG2-585 GEN
Solar/Wind Harmer
1.739
942221AE2-234 GEN
Solar/Wind Harmer
1.218
237061AD1-155 GEN
Solar/Wind Helper
0.84
316312AB1-027
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Helper
0.609
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.337
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
3.818
238147AE2-230_GEN1
Solar/Wind Helper
0.214
316097T157 G90
Solar/Wind Helper
0.557
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
CPLELTFEXP_CPLE->PJM
CLTF
3.109
SIGELTFEXP_SIGE->PJM
CLTF
0.271
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
LGEELTFEXP_LGEE->PJM
CLTF
3.563
MECLTFEXP_MEC->PJM
CLTF
8.317
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
NYPJM->LTFIMP_NY
CLTF
1.48
TVALTFEXP_TVA->PJM
CLTF
6.216
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
45.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970107AG2-081 GEN
Solar/Wind Harmer
2.085
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
960201AF2-311 GEN
Solar/Wind Harmer
5.7
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
274762LEE CO EC;3U
Adder
8.213
938861AE1-114 GEN
Solar/Wind Harmer
3.487
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
276893AG1-478 C
Solar/Wind Harmer
0.404
276897AD1-100 C
Solar/Wind Harmer
15.124
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
970941AG2-585 GEN
Solar/Wind Harmer
3.319
237061AD1-155 GEN
Solar/Wind Helper
1.647
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
970281AG2-184 GEN
Solar/Wind Harmer
18.909
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
0.13
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
276806AD2-047 C O1
Solar/Wind Harmer
3.42
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
5.792
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
972043AH1-570 GEN
Solar/Wind Harmer
1.794
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276615X2-022 GEN
Solar/Wind Harmer
0.065
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960611AF2-352 GEN
Solar/Wind Harmer
2.071
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270069AE2-166 C O1
Solar/Wind Harmer
10.375
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
2.889
971981AH1-535 GEN
Solar/Wind Harmer
5.838
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
253406AD2-031_GEN
Solar/Wind Harmer
0.464
946321AF1-296 GEN
Solar/Wind Harmer
3.479
270291AC1-194 GEN
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
971029AG2-637 GEN
Solar/Wind Harmer
9.145
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.242
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270346AE1-212 GEN
Solar/Wind Harmer
9.535
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
3429391JKCT 9G
Adder
8.393
958171AF2-111 GEN
Solar/Wind Harmer
16.661
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
276782AC1-033 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
274730ELWOOD EC;6P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
6.744
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
7.559
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.696
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
7.447
24686405CER G5
Adder
9.787
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
2.725
965931AG1-462 GEN
Solar/Wind Harmer
15.863
965091AG1-374 GEN
Solar/Wind Harmer
18.636
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
24690905MDL-1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276843GEN-1.7
Solar/Wind Harmer
0.195
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24290705CLAY-2
50/50
0.252
958131AF2-107 GEN
Solar/Wind Harmer
5.335
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
0
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
970819AG2-516 GEN
Solar/Wind Harmer
7.371
274822ROCKFORD ;11
Adder
17.258
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
941551AE2-152 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
7.838
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
5.174
970913AG2-568 GEN
Solar/Wind Harmer
7.67
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
964571AG1-320 GEN
Solar/Wind Harmer
6.355
972045AH1-571 GEN
Solar/Wind Harmer
1.437
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
276911AD2-131_GEN
Solar/Wind Harmer
0.879
24728805RICHG1
Adder
3.383
24699105WLD G1 C
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
270383AD1-128 GEN
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274695ROCKY RD ;2P
Adder
9.717
970885AG2-551 GEN
Solar/Wind Harmer
2.025
270031AE2-169
Solar/Wind Harmer
3.328
964611AG1-324 GEN
Solar/Wind Harmer
0.453
958011AF2-095 GEN
Solar/Wind Harmer
8.691
270201AC2-176 GEN
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
5.363
971061AG2-657 GEN
Solar/Wind Harmer
5.362
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
24691005MDL-2G C
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.033
270543AE2-219 C
Solar/Wind Harmer
4.252
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
12.886
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
6.071
971191AH1-055 GEN
Solar/Wind Harmer
18.034
972167AH1-666 GEN
Solar/Wind Harmer
5.413
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
4.688
942481AE2-261 GEN
Solar/Wind Harmer
18.979
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
12.283
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
946671AF1-331 GEN
Solar/Wind Harmer
0.653
970825AG2-519 GEN
Solar/Wind Harmer
4.603
274729ELWOOD EC;1P
Adder
14.264
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
3147983MERCK5
Solar/Wind Helper
0.198
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
0.047
971687AH1-348 GEN
Solar/Wind Harmer
0.947
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.048
276621W2-048 GEN
Solar/Wind Harmer
0.315
253398AE2-221_GEN2
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24386605FR-22G C
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
970569AG2-363 GEN
Solar/Wind Harmer
18.425
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276805AD2-038 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
964861AG1-349 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
945681AF1-233 GEN
Solar/Wind Harmer
12.766
252516AE2-318_GEN
Solar/Wind Harmer
7.186
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
957471AF2-041 GEN
Solar/Wind Harmer
18.391
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
276694AA1-018 GEN2
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.865
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
2.78
971587AH1-292 GEN
Solar/Wind Harmer
4.796
276916AD2-100_GEN
Solar/Wind Harmer
13.351
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276901AD2-066 C O1
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.644
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
959341AF2-225 GEN
Solar/Wind Harmer
6.498
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
970169AG2-114 GEN
Solar/Wind Harmer
6.143
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
958391AF2-133 GEN
Solar/Wind Harmer
0.001
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
24686505CER G6
Adder
9.865
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
270437AC2-090 C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
966841AG1-555 GEN
Solar/Wind Harmer
0.701
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
274674JOLIET 9 ;6U
Adder
13.36
270599AE1-208 GEN
Solar/Wind Harmer
5.547
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.044
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.61
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
971609AH1-304 GEN
Solar/Wind Harmer
0.988
964611AG1-324 GEN
Solar/Wind Harmer
2.357
316164AC1-076 GEN
Solar/Wind Helper
1.176
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
NYPJM->LTFIMP_NY
CLTF
3.255
TVALTFEXP_TVA->PJM
CLTF
10.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CPLELTFEXP_CPLE->PJM
CLTF
6.213
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
WECLTFEXP_WEC->PJM
CLTF
3.368
LAGNLTFEXP_LAGN->PJM
CLTF
20.26

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4175.28
MW Contribution:
45.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.18
971277AH1-098 GEN
Solar/Wind Harmer
7.43
970913AG2-568 GEN
Solar/Wind Harmer
9.375
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.774
339231AF1-038_GEN
Solar/Wind Harmer
1.925
964571AG1-320 GEN
Solar/Wind Harmer
8.222
972045AH1-571 GEN
Solar/Wind Harmer
1.989
927014AC1-188 GEN
Solar/Wind Harmer
1.537
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.603
971073AG2-665 GEN
Solar/Wind Harmer
7.39
25194508D.CRK3
Adder
1.304
276911AD2-131_GEN
Solar/Wind Harmer
3.891
24728805RICHG1
Adder
3.406
274765LEE CO EC;6U
Adder
8.284
274763LEE CO EC;4U
Adder
8.186
972236AH1-702 GEN2
Adder
1.94
274695ROCKY RD ;2P
Adder
9.779
238149AF1-291A_GEN
Solar/Wind Helper
0.122
316006AB2-029 C
Solar/Wind Helper
0.114
316313AB2-026
Solar/Wind Helper
0.356
316045AC1-158 PL2
Solar/Wind Helper
4.058
966871AG1-558 GEN
Solar/Wind Helper
0.307
270013AE1-250 PV
Solar/Wind Harmer
3.251
339236AF1-050_GEN
Solar/Wind Harmer
1.88
970107AG2-081 GEN
Solar/Wind Harmer
3.006
962581AG1-107 GEN
Solar/Wind Harmer
4.757
961491AF2-440 GEN
Solar/Wind Harmer
1.977
970879AG2-548 GEN
Solar/Wind Harmer
1.074
276838X2-022 GEN2
Solar/Wind Harmer
0.212
274880W4-005 GEN4
Solar/Wind Harmer
2.739
276174W4-005 GEN2
Solar/Wind Harmer
2.739
970241AG2-163 GEN
Solar/Wind Harmer
22.546
960201AF2-311 GEN
Solar/Wind Harmer
9.005
942111AE2-223 GEN
Solar/Wind Harmer
7.317
274762LEE CO EC;3U
Adder
8.264
274696ROCKY RD ;4P
Adder
10.01
274697ROCKY RD ;3P
Adder
2.656
237061AD1-155 GEN
Solar/Wind Helper
1.655
316312AB1-027
Solar/Wind Helper
0.426
24387305FR-4G C
Solar/Wind Harmer
3.45
971543AH1-269 GEN
50/50
12.26
24684705SMG5
50/50
0.846
971313AH1-133 GEN
Solar/Wind Harmer
9.348
971061AG2-657 GEN
Solar/Wind Harmer
11.048
25196108MFTGT2
Adder
1.433
25196108MFTGT2
Adder
1.331
25196408WSDLE3
Adder
8.125
25196308WSDLE2
Adder
8.054
25196208WSDLE1
Adder
8.034
25196708WSDLE6
Adder
8.014
274728ELWOOD EC;5P
Adder
14.355
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.321
316468AD1-105 GEN
Solar/Wind Helper
1.093
3141426STAFORD
Solar/Wind Helper
0.049
24387005FR-3G C
Solar/Wind Harmer
2.686
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.292
270574AD1-017 GEN2
Solar/Wind Harmer
8.474
270336AE1-100 GEN
Solar/Wind Harmer
2.754
943811AF1-049 GEN
Solar/Wind Harmer
5.701
24735205WLF2G2
Adder
8.042
24723205RIVRG3
Adder
23.046
972203AH1-686 GEN
Adder
2.716
964901AG1-354 GEN
Solar/Wind Harmer
15.55
339241AF1-083 GEN
Solar/Wind Harmer
1.722
943111AE2-339 GEN
Solar/Wind Harmer
0.887
945681AF1-233 GEN
Solar/Wind Harmer
18.414
252516AE2-318_GEN
Solar/Wind Harmer
9.259
25194608D.CRK4
Adder
1.517
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
946171AF1-282 GEN
Solar/Wind Harmer
9.125
24728605AND G2
Adder
3.5
274828WAUKEGAN ;BP
Adder
9.706
274682WAUKEGAN ;7U
Adder
15.786
274745AC1-111 GEN9
Adder
4.896
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
274676JOLIET 29;8U
Adder
22.605
316499AE2-029_GEN
Solar/Wind Helper
1.728
316095T157 G97
Solar/Wind Helper
1.135
966881AG1-559 GEN
Solar/Wind Helper
0.315
316473AC1-191 GEN
Solar/Wind Helper
1.393
270197AD1-017 GEN1
Solar/Wind Harmer
2.542
970281AG2-184 GEN
Solar/Wind Harmer
27.213
962211AG1-066 GEN
Solar/Wind Harmer
3.011
270444AC2-157 GEN1
Solar/Wind Harmer
5.263
270445AC2-157 GEN2
Solar/Wind Harmer
5.263
253433AC1-085 GEN1
Solar/Wind Harmer
4.849
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
276763AC1-053 GEN1
Solar/Wind Harmer
3.586
276764AC1-053 GEN2
Solar/Wind Harmer
3.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.006
276848AB2-070 GEN3
Solar/Wind Harmer
2.006
276849AB2-070 GEN2
Solar/Wind Harmer
2.006
959341AF2-225 GEN
Solar/Wind Harmer
13.389
274744AC1-111 GEN8
Adder
4.896
25306009OHH W.
Adder
2.518
274735ELWOOD EC;4P
Adder
14.355
253372AE2-315 SEC3
Adder
1.655
253372AE2-315 SEC3
Adder
1.655
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.846
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
971881AH1-461 GEN
50/50
15.01
943031AE2-326 GEN
Solar/Wind Harmer
6.794
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.957
960911AF2-382 GEN
Solar/Wind Harmer
10.976
972103AH1-617 GEN
Solar/Wind Harmer
25.917
24721905FLATG4
Adder
21.789
252519AF1-045_GEN
Solar/Wind Harmer
3.37
25194608D.CRK4
Adder
1.517
252524AE2-267 GEN
Solar/Wind Harmer
1.45
957381AF2-032 GEN
Solar/Wind Harmer
1.829
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
946181AF1-283 GEN
Solar/Wind Harmer
11.863
24728505AND G1
Adder
3.5
276785W4-005 GEN1
Solar/Wind Harmer
2.739
971087AG2-675 GEN
Solar/Wind Harmer
3.338
274767LEE CO EC;8U
Adder
8.167
274682WAUKEGAN ;7U
Adder
15.786
274734ELWOOD EC;8P
Adder
14.355
274736ELWOOD EC;9P
Adder
14.355
253370AE2-315 SEC1
Adder
1.749
253371AE2-315 SEC2
Adder
1.655
316192AB2-158 GEN
Solar/Wind Helper
1.852
316447AC1-158 HLD
Solar/Wind Helper
2.79
3142416OLDCHRC
Solar/Wind Helper
0.581
3142416OLDCHRC
Solar/Wind Helper
0.222
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.669
971485AH1-239 GEN
Solar/Wind Harmer
8.528
964781AG1-341 GEN
Solar/Wind Harmer
11.012
942891AE2-308 GEN
Solar/Wind Harmer
10.222
972043AH1-570 GEN
Solar/Wind Harmer
2.487
25194408D.CRK1
Adder
6.977
945391AF1-204 GEN
Solar/Wind Harmer
12.785
276615X2-022 GEN
Solar/Wind Harmer
1.781
24728905RICHG2
Adder
3.406
960251AF2-316 GEN
Solar/Wind Harmer
13.508
960611AF2-352 GEN
Solar/Wind Harmer
2.083
274764LEE CO EC;5U
Adder
8.284
972235AH1-702 GEN1
Adder
2.231
274683WAUKEGAN ;8U
Adder
18.516
274683WAUKEGAN ;8U
Adder
15.608
274693ROCKY RD ;1P
Adder
9.683
274674JOLIET 9 ;6U
Adder
13.445
3132123MT JACKSON
Solar/Wind Helper
1.393
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.426
316450AC1-158 RIC
Solar/Wind Helper
0.338
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.387
966391AG1-508 GEN
Solar/Wind Harmer
6.384
270069AE2-166 C O1
Solar/Wind Harmer
14.894
24734705WLF1G3
Adder
8.213
24734905WLF1G5
Adder
8.213
270399AC1-101 GEN
Solar/Wind Harmer
5.575
971981AH1-535 GEN
Solar/Wind Harmer
12.593
339216AC1-074 GEN
Solar/Wind Harmer
1.652
972165AH1-665 GEN
Solar/Wind Harmer
7.834
971985AH1-537 GEN
Solar/Wind Harmer
17.394
253406AD2-031_GEN
Solar/Wind Harmer
1.153
270291AC1-194 GEN
Solar/Wind Harmer
4.567
946321AF1-296 GEN
Solar/Wind Harmer
9.347
274853TWINGROVE;U1
Solar/Wind Harmer
6.454
972267AH1-718 GEN
Adder
3.707
274823ROCKFORD ;21
Adder
17.239
274675JOLIET 29;7U
Adder
26.781
315616AA1-038_C
Solar/Wind Helper
3.299
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.921
970823AG2-518 GEN
50/50
8.391
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.737
958121AF2-106 GEN
Solar/Wind Harmer
9.417
270346AE1-212 GEN
Solar/Wind Harmer
13.976
270018AE2-047 C O1
Solar/Wind Harmer
1.823
971461AH1-227 GEN
Solar/Wind Harmer
7.023
970223AG2-152 GEN
Solar/Wind Harmer
17.677
270330AC1-082 GEN2
Solar/Wind Harmer
0.514
3429391JKCT 9G
Adder
8.441
957541AF2-048 GEN
Solar/Wind Harmer
1.537
958171AF2-111 GEN
Solar/Wind Harmer
24.034
252507AC2-088 GEN
Solar/Wind Harmer
1.676
25196608WSDLE5
Adder
7.893
970193AG2-126 GEN
Solar/Wind Harmer
13.761
24728705AND G3
Adder
7.32
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274730ELWOOD EC;6P
Adder
14.355
3147666LOUISA
Solar/Wind Helper
1.093
238152AF2-075_GEN
Solar/Wind Helper
0.608
316044AC1-158 PL1
Solar/Wind Helper
1.268
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.745
24734805WLF1G4
Adder
8.213
24735105WLF2G1
Adder
8.042
270400AC1-102 GEN
Solar/Wind Harmer
5.575
941621AE2-160 GEN
Adder
4.304
957241AF2-018 GEN
Solar/Wind Harmer
5.778
270053AF1-130 C
Solar/Wind Harmer
23.086
3429211JKCT 2G
Adder
11.928
972163AH1-664 GEN
Solar/Wind Harmer
9.793
944221AF1-090 GEN
Solar/Wind Harmer
10.074
25196508WSDLE4
Adder
7.812
270356AE2-297 GEN
Solar/Wind Harmer
4.168
963841AG1-237 GEN
Solar/Wind Harmer
9.807
274854TWINGROVE;U2
Solar/Wind Harmer
6.319
270340AC2-060 GEN
Solar/Wind Harmer
2.703
276726Z2-087_GEN
Solar/Wind Harmer
7.058
274746AC1-111 G10
Adder
4.896
274731ELWOOD EC;2P
Adder
14.355
274733ELWOOD EC;3P
Adder
14.355
316164AC1-076 GEN
Solar/Wind Helper
1.182
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.813
24686405CER G5
Adder
9.839
270329AC1-082 GEN1
Solar/Wind Harmer
0.514
339255AE2-071 GEN
Solar/Wind Harmer
1.222
339250AF1-203 GEN
Solar/Wind Harmer
0.629
339206AE1-143 GEN
Solar/Wind Harmer
2.213
970653AG2-424 GEN
Solar/Wind Harmer
0.709
970455AG2-298 GEN
Solar/Wind Harmer
3.536
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
965931AG1-462 GEN
Solar/Wind Harmer
22.875
965091AG1-374 GEN
Solar/Wind Harmer
26.876
274760LEE CO EC;1U
Adder
8.264
24386205FR-12G C
Solar/Wind Harmer
2.911
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.446
958131AF2-107 GEN
Solar/Wind Harmer
7.107
971403AH1-188 GEN
Solar/Wind Harmer
18.915
944971AF1-162 GEN
Solar/Wind Harmer
9.1
960001AF2-291 GEN
Solar/Wind Harmer
3.133
970653AG2-424 GEN
Solar/Wind Harmer
4.903
3429421JKCT 10G
Adder
8.441
339221AD2-048_GEN
Solar/Wind Harmer
1.518
970091AG2-072 GEN
Adder
74.384
971073AG2-665 GEN
Solar/Wind Harmer
1.074
276686W4-005 GEN3
Solar/Wind Harmer
2.739
963741AG1-226 GEN
Solar/Wind Harmer
40.583
270222AC2-111 GEN
Solar/Wind Harmer
4.015
276655WTG1_EQ
Solar/Wind Harmer
7.791
274822ROCKFORD ;11
Adder
17.365
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.197
24728305BUCHG2
50/50
7.18
316217AC1-145 GEN
Solar/Wind Harmer
4.244
316197AC1-042 GEN
Solar/Wind Harmer
3.217
24686505CER G6
Adder
9.917
339211AE2-254 GEN
Solar/Wind Harmer
1.567
3429241JKCT 3G
Adder
12.084
965911AG1-460 GEN
Solar/Wind Harmer
1.277
944031AF1-071 GEN
Solar/Wind Harmer
0.903
276656WTG2_EQ
Solar/Wind Harmer
1.032
274766LEE CO EC;7U
Adder
8.167
274732ELWOOD EC;7P
Adder
14.355
274674JOLIET 9 ;6U
Adder
13.445
3148013FISHERV
Solar/Wind Helper
0.524
3147666LOUISA
Solar/Wind Helper
0.628
24385905FR-11G C
Solar/Wind Harmer
5.645
24684605SMG4
50/50
2.212
970563AG2-360 GEN
50/50
45.925
962751AG1-124 GEN
Solar/Wind Harmer
18.829
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.251
972273AH1-721 GEN
Adder
89.66
970093AG2-073 GEN
Solar/Wind Harmer
5.468
971191AH1-055 GEN
Solar/Wind Harmer
18.939
972167AH1-666 GEN
Solar/Wind Harmer
7.807
270186AC1-089 GEN
Solar/Wind Harmer
5.851
270367AC2-061_GEN
Solar/Wind Harmer
3.02
25196008MFTGT1
Adder
1.259
970879AG2-548 GEN
Solar/Wind Harmer
7.39
942481AE2-261 GEN
Solar/Wind Harmer
27.366
971993AH1-541 GEN
Solar/Wind Harmer
8.371
253394AE2-221_GEN
Solar/Wind Harmer
4.079
274729ELWOOD EC;1P
Adder
14.355
3147983MERCK5
Solar/Wind Helper
0.199
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.363
270331AC1-082 GEN3
Solar/Wind Harmer
0.515
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
71.001
25196008MFTGT1
Adder
1.3
252510AF1-249 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
5.671
253398AE2-221_GEN2
Solar/Wind Harmer
4.079
939741AE1-205 GEN
Solar/Wind Harmer
17.852
274761LEE CO EC;2U
Adder
8.264
315821AE2-092 GEN
Solar/Wind Helper
3.236
23583801GRNGAP
Solar/Wind Helper
4.324
24386605FR-22G C
Solar/Wind Harmer
2.921
270583AD2-179 GEN
Solar/Wind Harmer
20.746
270214AC2-123 GEN
Solar/Wind Harmer
4.317
971225AH1-072 GEN
Solar/Wind Harmer
2.738
971227AH1-073 GEN
Solar/Wind Harmer
2.738
24723005RIVRG1
Adder
23.046
24723105RIVRG2
Adder
23.046
971125AH1-004 GEN
Solar/Wind Harmer
4.008
276916AD2-100_GEN
Solar/Wind Harmer
19.251
253370AE2-315 SEC1
Adder
1.749
316097T157 G90
Solar/Wind Helper
1.135
238147AE2-230_GEN1
Solar/Wind Helper
0.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.642
LGEELTFEXP_LGEE->PJM
CLTF
6.795
MECLTFEXP_MEC->PJM
CLTF
15.488
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.053
NYPJM->LTFIMP_NY
CLTF
3.28
TVALTFEXP_TVA->PJM
CLTF
10.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.582
CPLELTFEXP_CPLE->PJM
CLTF
6.224
SIGELTFEXP_SIGE->PJM
CLTF
0.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.452
WECLTFEXP_WEC->PJM
CLTF
3.389
LAGNLTFEXP_LAGN->PJM
CLTF
20.349

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4165.98
MW Contribution:
45.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.164
971277AH1-098 GEN
Solar/Wind Harmer
7.42
970913AG2-568 GEN
Solar/Wind Harmer
9.345
942751AE2-291 GEN
Solar/Wind Harmer
10.376
966021AG1-471 GEN
Solar/Wind Harmer
5.755
339231AF1-038_GEN
Solar/Wind Harmer
1.919
964571AG1-320 GEN
Solar/Wind Harmer
8.191
972045AH1-571 GEN
Solar/Wind Harmer
1.981
927014AC1-188 GEN
Solar/Wind Harmer
1.529
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.577
971073AG2-665 GEN
Solar/Wind Harmer
7.349
25194508D.CRK3
Adder
1.298
276911AD2-131_GEN
Solar/Wind Harmer
3.875
24728805RICHG1
Adder
3.39
274765LEE CO EC;6U
Adder
8.248
274763LEE CO EC;4U
Adder
8.151
972236AH1-702 GEN2
Adder
1.932
274695ROCKY RD ;2P
Adder
9.736
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.307
316045AC1-158 PL2
Solar/Wind Helper
4.045
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.873
970107AG2-081 GEN
Solar/Wind Harmer
2.994
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
970879AG2-548 GEN
Solar/Wind Harmer
1.068
276838X2-022 GEN2
Solar/Wind Harmer
0.211
274880W4-005 GEN4
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
970241AG2-163 GEN
Solar/Wind Harmer
22.448
960201AF2-311 GEN
Solar/Wind Harmer
8.941
942111AE2-223 GEN
Solar/Wind Harmer
7.286
274762LEE CO EC;3U
Adder
8.229
274696ROCKY RD ;4P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.645
237061AD1-155 GEN
Solar/Wind Helper
1.65
316312AB1-027
Solar/Wind Helper
0.425
24387305FR-4G C
Solar/Wind Harmer
2.471
971543AH1-269 GEN
50/50
12.246
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.329
971061AG2-657 GEN
Solar/Wind Harmer
11.001
25196108MFTGT2
Adder
1.427
25196108MFTGT2
Adder
1.325
25196408WSDLE3
Adder
8.087
25196308WSDLE2
Adder
8.016
25196208WSDLE1
Adder
7.996
25196708WSDLE6
Adder
7.976
274728ELWOOD EC;5P
Adder
14.292
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.09
24387005FR-3G C
Solar/Wind Harmer
1.925
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.025
24723205RIVRG3
Adder
22.967
972203AH1-686 GEN
Adder
2.706
964901AG1-354 GEN
Solar/Wind Harmer
15.496
339241AF1-083 GEN
Solar/Wind Harmer
1.716
943111AE2-339 GEN
Solar/Wind Harmer
0.883
945681AF1-233 GEN
Solar/Wind Harmer
18.334
252516AE2-318_GEN
Solar/Wind Harmer
9.216
25194608D.CRK4
Adder
1.51
24728605AND G2
Adder
3.485
253316AC1-085 GEN3
Solar/Wind Harmer
7.603
946171AF1-282 GEN
Solar/Wind Harmer
9.081
274848CAMPGROVE;RU
Solar/Wind Harmer
5.733
274828WAUKEGAN ;BP
Adder
9.664
274682WAUKEGAN ;7U
Adder
15.718
274745AC1-111 GEN9
Adder
4.874
274676JOLIET 29;8U
Adder
26.663
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.13
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.39
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.137
962211AG1-066 GEN
Solar/Wind Harmer
3.002
270444AC2-157 GEN1
Solar/Wind Harmer
5.241
270445AC2-157 GEN2
Solar/Wind Harmer
5.241
253433AC1-085 GEN1
Solar/Wind Harmer
4.826
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
276668AB2-070 GEN1
Solar/Wind Harmer
1.998
276848AB2-070 GEN3
Solar/Wind Harmer
1.998
276849AB2-070 GEN2
Solar/Wind Harmer
1.998
959341AF2-225 GEN
Solar/Wind Harmer
13.331
274744AC1-111 GEN8
Adder
4.874
274735ELWOOD EC;4P
Adder
14.292
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.844
971881AH1-461 GEN
50/50
14.98
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.922
960911AF2-382 GEN
Solar/Wind Harmer
10.95
972103AH1-617 GEN
Solar/Wind Harmer
25.844
24721905FLATG4
Adder
21.701
252519AF1-045_GEN
Solar/Wind Harmer
3.354
25194608D.CRK4
Adder
1.51
252524AE2-267 GEN
Solar/Wind Harmer
1.443
957381AF2-032 GEN
Solar/Wind Harmer
1.822
24728505AND G1
Adder
3.485
253317AC1-085 GEN4
Solar/Wind Harmer
7.603
946181AF1-283 GEN
Solar/Wind Harmer
11.806
276785W4-005 GEN1
Solar/Wind Harmer
2.728
971087AG2-675 GEN
Solar/Wind Harmer
3.324
274767LEE CO EC;8U
Adder
8.132
274682WAUKEGAN ;7U
Adder
15.718
274734ELWOOD EC;8P
Adder
14.292
274736ELWOOD EC;9P
Adder
14.292
316192AB2-158 GEN
Solar/Wind Helper
1.847
316447AC1-158 HLD
Solar/Wind Helper
2.781
3142416OLDCHRC
Solar/Wind Helper
0.579
3142416OLDCHRC
Solar/Wind Helper
0.222
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.664
971485AH1-239 GEN
Solar/Wind Harmer
8.501
964781AG1-341 GEN
Solar/Wind Harmer
10.975
942891AE2-308 GEN
Solar/Wind Harmer
10.182
972043AH1-570 GEN
Solar/Wind Harmer
2.477
25194408D.CRK1
Adder
6.944
945391AF1-204 GEN
Solar/Wind Harmer
12.73
276615X2-022 GEN
Solar/Wind Harmer
1.774
24728905RICHG2
Adder
3.39
960251AF2-316 GEN
Solar/Wind Harmer
13.412
960611AF2-352 GEN
Solar/Wind Harmer
2.075
274764LEE CO EC;5U
Adder
8.248
972235AH1-702 GEN1
Adder
2.222
274683WAUKEGAN ;8U
Adder
18.436
274683WAUKEGAN ;8U
Adder
15.54
274693ROCKY RD ;1P
Adder
9.64
274674JOLIET 9 ;6U
Adder
13.386
3132123MT JACKSON
Solar/Wind Helper
1.391
966001AG1-469 GEN
Solar/Wind Helper
0.321
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316450AC1-158 RIC
Solar/Wind Helper
0.337
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.362
966391AG1-508 GEN
Solar/Wind Harmer
6.375
270069AE2-166 C O1
Solar/Wind Harmer
14.878
24734705WLF1G3
Adder
8.195
24734905WLF1G5
Adder
8.195
270399AC1-101 GEN
Solar/Wind Harmer
5.558
971981AH1-535 GEN
Solar/Wind Harmer
12.564
339216AC1-074 GEN
Solar/Wind Harmer
1.645
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.311
253406AD2-031_GEN
Solar/Wind Harmer
1.147
270291AC1-194 GEN
Solar/Wind Harmer
4.541
946321AF1-296 GEN
Solar/Wind Harmer
9.308
274853TWINGROVE;U1
Solar/Wind Harmer
6.427
972267AH1-718 GEN
Adder
3.691
274823ROCKFORD ;21
Adder
17.165
274675JOLIET 29;7U
Adder
26.663
274675JOLIET 29;7U
Adder
7.65
315616AA1-038_C
Solar/Wind Helper
3.298
3148013FISHERV
Solar/Wind Helper
0.301
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.093
970823AG2-518 GEN
50/50
8.383
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.406
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.006
970223AG2-152 GEN
Solar/Wind Harmer
17.663
270330AC1-082 GEN2
Solar/Wind Harmer
0.512
3429391JKCT 9G
Adder
8.408
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.928
252507AC2-088 GEN
Solar/Wind Harmer
1.668
25196608WSDLE5
Adder
7.856
970193AG2-126 GEN
Solar/Wind Harmer
13.702
24728705AND G3
Adder
7.288
959611AF2-252 GEN
Solar/Wind Harmer
2.075
274730ELWOOD EC;6P
Adder
14.292
3147666LOUISA
Solar/Wind Helper
1.09
238152AF2-075_GEN
Solar/Wind Helper
0.606
316044AC1-158 PL1
Solar/Wind Helper
1.264
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.729
24734805WLF1G4
Adder
8.195
24735105WLF2G1
Adder
8.025
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.288
957241AF2-018 GEN
Solar/Wind Harmer
5.76
270053AF1-130 C
Solar/Wind Harmer
23.016
3429211JKCT 2G
Adder
11.881
972163AH1-664 GEN
Solar/Wind Harmer
9.75
944221AF1-090 GEN
Solar/Wind Harmer
10.032
25196508WSDLE4
Adder
7.775
270356AE2-297 GEN
Solar/Wind Harmer
4.149
963841AG1-237 GEN
Solar/Wind Harmer
9.765
274854TWINGROVE;U2
Solar/Wind Harmer
6.292
270340AC2-060 GEN
Solar/Wind Harmer
2.689
276726Z2-087_GEN
Solar/Wind Harmer
7.027
274746AC1-111 G10
Adder
4.874
274731ELWOOD EC;2P
Adder
14.292
274733ELWOOD EC;3P
Adder
14.292
316164AC1-076 GEN
Solar/Wind Helper
1.178
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.808
24686405CER G5
Adder
9.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.512
339255AE2-071 GEN
Solar/Wind Harmer
1.218
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.205
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.522
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
965931AG1-462 GEN
Solar/Wind Harmer
22.779
965091AG1-374 GEN
Solar/Wind Harmer
26.762
274760LEE CO EC;1U
Adder
8.229
24386205FR-12G C
Solar/Wind Harmer
2.085
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.104
971403AH1-188 GEN
Solar/Wind Harmer
18.86
944971AF1-162 GEN
Solar/Wind Harmer
9.072
960001AF2-291 GEN
Solar/Wind Harmer
3.117
970653AG2-424 GEN
Solar/Wind Harmer
4.885
3429421JKCT 10G
Adder
8.408
339221AD2-048_GEN
Solar/Wind Harmer
1.511
970091AG2-072 GEN
Adder
74.077
971073AG2-665 GEN
Solar/Wind Harmer
1.068
276686W4-005 GEN3
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.407
270222AC2-111 GEN
Solar/Wind Harmer
3.996
276655WTG1_EQ
Solar/Wind Harmer
7.757
274822ROCKFORD ;11
Adder
17.29
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.164
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.881
339211AE2-254 GEN
Solar/Wind Harmer
1.561
3429241JKCT 3G
Adder
12.037
965911AG1-460 GEN
Solar/Wind Harmer
1.272
944031AF1-071 GEN
Solar/Wind Harmer
0.899
276656WTG2_EQ
Solar/Wind Harmer
1.027
274766LEE CO EC;7U
Adder
8.132
274732ELWOOD EC;7P
Adder
14.292
274674JOLIET 9 ;6U
Adder
13.386
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.627
24385905FR-11G C
Solar/Wind Harmer
4.044
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.836
962751AG1-124 GEN
Solar/Wind Harmer
18.819
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
972273AH1-721 GEN
Adder
89.361
970093AG2-073 GEN
Solar/Wind Harmer
5.447
971191AH1-055 GEN
Solar/Wind Harmer
18.847
972167AH1-666 GEN
Solar/Wind Harmer
7.773
270186AC1-089 GEN
Solar/Wind Harmer
5.824
270367AC2-061_GEN
Solar/Wind Harmer
3.006
25196008MFTGT1
Adder
1.253
970879AG2-548 GEN
Solar/Wind Harmer
7.349
942481AE2-261 GEN
Solar/Wind Harmer
27.253
971993AH1-541 GEN
Solar/Wind Harmer
8.336
253394AE2-221_GEN
Solar/Wind Harmer
4.059
274729ELWOOD EC;1P
Adder
14.292
3147983MERCK5
Solar/Wind Helper
0.199
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.359
270331AC1-082 GEN3
Solar/Wind Harmer
0.513
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.673
25196008MFTGT1
Adder
1.294
252510AF1-249 C
Solar/Wind Harmer
0.384
276621W2-048 GEN
Solar/Wind Harmer
5.648
253398AE2-221_GEN2
Solar/Wind Harmer
4.059
939741AE1-205 GEN
Solar/Wind Harmer
17.775
274761LEE CO EC;2U
Adder
8.229
315821AE2-092 GEN
Solar/Wind Helper
3.232
23583801GRNGAP
Solar/Wind Helper
4.304
24386605FR-22G C
Solar/Wind Harmer
2.093
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971225AH1-072 GEN
Solar/Wind Harmer
2.731
971227AH1-073 GEN
Solar/Wind Harmer
2.731
24723005RIVRG1
Adder
22.967
24723105RIVRG2
Adder
22.967
971125AH1-004 GEN
Solar/Wind Harmer
3.992
276916AD2-100_GEN
Solar/Wind Harmer
19.171
316097T157 G90
Solar/Wind Helper
1.13
238147AE2-230_GEN1
Solar/Wind Helper
0.424
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.539
CPLELTFEXP_CPLE->PJM
CLTF
6.216
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.331
WECLTFEXP_WEC->PJM
CLTF
3.374
LAGNLTFEXP_LAGN->PJM
CLTF
20.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.186
LGEELTFEXP_LGEE->PJM
CLTF
6.768
MECLTFEXP_MEC->PJM
CLTF
15.426
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.511
NYPJM->LTFIMP_NY
CLTF
3.263
TVALTFEXP_TVA->PJM
CLTF
10.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.26 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4160.96
MW Contribution:
45.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.157
971277AH1-098 GEN
Solar/Wind Harmer
7.416
970913AG2-568 GEN
Solar/Wind Harmer
9.332
942751AE2-291 GEN
Solar/Wind Harmer
10.374
966021AG1-471 GEN
Solar/Wind Harmer
5.747
339231AF1-038_GEN
Solar/Wind Harmer
1.916
964571AG1-320 GEN
Solar/Wind Harmer
8.178
972045AH1-571 GEN
Solar/Wind Harmer
1.978
927014AC1-188 GEN
Solar/Wind Harmer
1.526
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.565
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.33
276911AD2-131_GEN
Solar/Wind Harmer
3.867
24728805RICHG1
Adder
3.383
274765LEE CO EC;6U
Adder
8.233
274763LEE CO EC;4U
Adder
8.136
972236AH1-702 GEN2
Adder
1.928
274695ROCKY RD ;2P
Adder
9.717
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
270013AE1-250 PV
Solar/Wind Harmer
3.247
339236AF1-050_GEN
Solar/Wind Harmer
1.871
970107AG2-081 GEN
Solar/Wind Harmer
2.988
962581AG1-107 GEN
Solar/Wind Harmer
4.724
961491AF2-440 GEN
Solar/Wind Harmer
1.963
970879AG2-548 GEN
Solar/Wind Harmer
1.065
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.723
276174W4-005 GEN2
Solar/Wind Harmer
2.723
970241AG2-163 GEN
Solar/Wind Harmer
22.405
960201AF2-311 GEN
Solar/Wind Harmer
8.913
942111AE2-223 GEN
Solar/Wind Harmer
7.272
274762LEE CO EC;3U
Adder
8.213
274696ROCKY RD ;4P
Adder
9.947
274697ROCKY RD ;3P
Adder
2.64
237061AD1-155 GEN
Solar/Wind Helper
1.647
24387305FR-4G C
Solar/Wind Harmer
2.467
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.321
971061AG2-657 GEN
Solar/Wind Harmer
10.98
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
274728ELWOOD EC;5P
Adder
14.264
3148133STUARTS
Solar/Wind Helper
0.314
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.089
24387005FR-3G C
Solar/Wind Harmer
1.921
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.466
270336AE1-100 GEN
Solar/Wind Harmer
2.749
943811AF1-049 GEN
Solar/Wind Harmer
5.692
24735205WLF2G2
Adder
8.017
24723205RIVRG3
Adder
22.932
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
15.473
339241AF1-083 GEN
Solar/Wind Harmer
1.713
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.298
252516AE2-318_GEN
Solar/Wind Harmer
9.197
25194608D.CRK4
Adder
1.506
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
7.586
946171AF1-282 GEN
Solar/Wind Harmer
9.062
274848CAMPGROVE;RU
Solar/Wind Harmer
5.723
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274745AC1-111 GEN9
Adder
4.865
274676JOLIET 29;8U
Adder
26.611
316499AE2-029_GEN
Solar/Wind Helper
1.726
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
270197AD1-017 GEN1
Solar/Wind Harmer
2.54
970281AG2-184 GEN
Solar/Wind Harmer
27.103
962211AG1-066 GEN
Solar/Wind Harmer
2.998
270444AC2-157 GEN1
Solar/Wind Harmer
5.231
270445AC2-157 GEN2
Solar/Wind Harmer
5.231
253433AC1-085 GEN1
Solar/Wind Harmer
4.815
253432AC1-085 GEN2
Solar/Wind Harmer
0.242
276763AC1-053 GEN1
Solar/Wind Harmer
3.564
276764AC1-053 GEN2
Solar/Wind Harmer
3.564
276668AB2-070 GEN1
Solar/Wind Harmer
1.994
276848AB2-070 GEN3
Solar/Wind Harmer
1.994
276849AB2-070 GEN2
Solar/Wind Harmer
1.994
959341AF2-225 GEN
Solar/Wind Harmer
13.306
274744AC1-111 GEN8
Adder
4.865
274735ELWOOD EC;4P
Adder
14.264
25306009OHH W.
Adder
2.5
3148463FAIRFLD
Solar/Wind Helper
0.727
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
971881AH1-461 GEN
50/50
14.967
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.906
960911AF2-382 GEN
Solar/Wind Harmer
10.939
972103AH1-617 GEN
Solar/Wind Harmer
25.812
24721905FLATG4
Adder
21.662
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
252524AE2-267 GEN
Solar/Wind Harmer
1.44
957381AF2-032 GEN
Solar/Wind Harmer
1.819
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
7.586
946181AF1-283 GEN
Solar/Wind Harmer
11.78
276785W4-005 GEN1
Solar/Wind Harmer
2.723
971087AG2-675 GEN
Solar/Wind Harmer
3.318
274767LEE CO EC;8U
Adder
8.117
274682WAUKEGAN ;7U
Adder
15.687
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
316192AB2-158 GEN
Solar/Wind Helper
1.845
316447AC1-158 HLD
Solar/Wind Helper
2.777
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.662
971485AH1-239 GEN
Solar/Wind Harmer
8.488
964781AG1-341 GEN
Solar/Wind Harmer
10.959
942891AE2-308 GEN
Solar/Wind Harmer
10.165
972043AH1-570 GEN
Solar/Wind Harmer
2.472
25194408D.CRK1
Adder
6.93
945391AF1-204 GEN
Solar/Wind Harmer
12.706
276615X2-022 GEN
Solar/Wind Harmer
1.77
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
13.37
960611AF2-352 GEN
Solar/Wind Harmer
2.071
274764LEE CO EC;5U
Adder
8.233
972235AH1-702 GEN1
Adder
2.217
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274693ROCKY RD ;1P
Adder
9.622
274674JOLIET 9 ;6U
Adder
13.36
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.337
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
966391AG1-508 GEN
Solar/Wind Harmer
6.371
270069AE2-166 C O1
Solar/Wind Harmer
14.87
24734705WLF1G3
Adder
8.187
24734905WLF1G5
Adder
8.187
270399AC1-101 GEN
Solar/Wind Harmer
5.551
971981AH1-535 GEN
Solar/Wind Harmer
12.552
339216AC1-074 GEN
Solar/Wind Harmer
1.642
972165AH1-665 GEN
Solar/Wind Harmer
7.785
971985AH1-537 GEN
Solar/Wind Harmer
17.275
253406AD2-031_GEN
Solar/Wind Harmer
1.145
946321AF1-296 GEN
Solar/Wind Harmer
9.291
274853TWINGROVE;U1
Solar/Wind Harmer
6.415
270291AC1-194 GEN
Solar/Wind Harmer
4.529
972267AH1-718 GEN
Adder
3.684
274823ROCKFORD ;21
Adder
17.132
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
315616AA1-038_C
Solar/Wind Helper
3.297
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.267
24386405FR-21G C
Solar/Wind Harmer
2.088
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.731
958121AF2-106 GEN
Solar/Wind Harmer
9.401
270346AE1-212 GEN
Solar/Wind Harmer
13.925
270018AE2-047 C O1
Solar/Wind Harmer
1.82
971461AH1-227 GEN
Solar/Wind Harmer
6.998
970223AG2-152 GEN
Solar/Wind Harmer
17.657
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
3429391JKCT 9G
Adder
8.393
957541AF2-048 GEN
Solar/Wind Harmer
1.526
958171AF2-111 GEN
Solar/Wind Harmer
23.881
252507AC2-088 GEN
Solar/Wind Harmer
1.664
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
13.676
24728705AND G3
Adder
7.274
959611AF2-252 GEN
Solar/Wind Harmer
2.071
274730ELWOOD EC;6P
Adder
14.264
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316044AC1-158 PL1
Solar/Wind Helper
1.262
24684305SMG1
50/50
0.795
971329AH1-144 GEN
Solar/Wind Harmer
11.722
24734805WLF1G4
Adder
8.187
24735105WLF2G1
Adder
8.017
270400AC1-102 GEN
Solar/Wind Harmer
5.551
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
5.752
270053AF1-130 C
Solar/Wind Harmer
22.985
3429211JKCT 2G
Adder
11.861
972163AH1-664 GEN
Solar/Wind Harmer
9.732
944221AF1-090 GEN
Solar/Wind Harmer
10.014
25196508WSDLE4
Adder
7.759
270356AE2-297 GEN
Solar/Wind Harmer
4.141
963841AG1-237 GEN
Solar/Wind Harmer
9.746
274854TWINGROVE;U2
Solar/Wind Harmer
6.28
270340AC2-060 GEN
Solar/Wind Harmer
2.683
276726Z2-087_GEN
Solar/Wind Harmer
7.014
274746AC1-111 G10
Adder
4.865
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
316164AC1-076 GEN
Solar/Wind Helper
1.176
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.805
24686405CER G5
Adder
9.787
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
339255AE2-071 GEN
Solar/Wind Harmer
1.216
339250AF1-203 GEN
Solar/Wind Harmer
0.626
339206AE1-143 GEN
Solar/Wind Harmer
2.202
970653AG2-424 GEN
Solar/Wind Harmer
0.705
970455AG2-298 GEN
Solar/Wind Harmer
3.516
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.737
965091AG1-374 GEN
Solar/Wind Harmer
26.711
274760LEE CO EC;1U
Adder
8.213
24386205FR-12G C
Solar/Wind Harmer
2.081
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.443
958131AF2-107 GEN
Solar/Wind Harmer
7.102
971403AH1-188 GEN
Solar/Wind Harmer
18.836
944971AF1-162 GEN
Solar/Wind Harmer
9.06
960001AF2-291 GEN
Solar/Wind Harmer
3.11
970653AG2-424 GEN
Solar/Wind Harmer
4.877
3429421JKCT 10G
Adder
8.393
339221AD2-048_GEN
Solar/Wind Harmer
1.508
970091AG2-072 GEN
Adder
73.941
971073AG2-665 GEN
Solar/Wind Harmer
1.065
276686W4-005 GEN3
Solar/Wind Harmer
2.723
963741AG1-226 GEN
Solar/Wind Harmer
40.329
270222AC2-111 GEN
Solar/Wind Harmer
3.988
276655WTG1_EQ
Solar/Wind Harmer
7.743
274822ROCKFORD ;11
Adder
17.258
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.195
24728305BUCHG2
50/50
7.157
316217AC1-145 GEN
Solar/Wind Harmer
4.241
316197AC1-042 GEN
Solar/Wind Harmer
3.215
24686505CER G6
Adder
9.865
339211AE2-254 GEN
Solar/Wind Harmer
1.559
3429241JKCT 3G
Adder
12.016
965911AG1-460 GEN
Solar/Wind Harmer
1.269
944031AF1-071 GEN
Solar/Wind Harmer
0.897
276656WTG2_EQ
Solar/Wind Harmer
1.025
274766LEE CO EC;7U
Adder
8.117
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.036
24684605SMG4
50/50
2.21
970563AG2-360 GEN
50/50
45.796
962751AG1-124 GEN
Solar/Wind Harmer
18.814
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.247
972273AH1-721 GEN
Adder
89.23
970093AG2-073 GEN
Solar/Wind Harmer
5.438
971191AH1-055 GEN
Solar/Wind Harmer
18.807
972167AH1-666 GEN
Solar/Wind Harmer
7.758
270186AC1-089 GEN
Solar/Wind Harmer
5.812
270367AC2-061_GEN
Solar/Wind Harmer
3
25196008MFTGT1
Adder
1.251
970879AG2-548 GEN
Solar/Wind Harmer
7.33
942481AE2-261 GEN
Solar/Wind Harmer
27.203
971993AH1-541 GEN
Solar/Wind Harmer
8.32
253394AE2-221_GEN
Solar/Wind Harmer
4.05
274729ELWOOD EC;1P
Adder
14.264
3147983MERCK5
Solar/Wind Helper
0.198
24684505SMG3
50/50
1.341
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.487
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252510AF1-249 C
Solar/Wind Harmer
0.383
276621W2-048 GEN
Solar/Wind Harmer
5.637
253398AE2-221_GEN2
Solar/Wind Harmer
4.05
939741AE1-205 GEN
Solar/Wind Harmer
17.741
274761LEE CO EC;2U
Adder
8.213
315821AE2-092 GEN
Solar/Wind Helper
3.23
23583801GRNGAP
Solar/Wind Helper
4.295
24386605FR-22G C
Solar/Wind Harmer
2.088
270583AD2-179 GEN
Solar/Wind Harmer
20.71
270214AC2-123 GEN
Solar/Wind Harmer
4.308
971225AH1-072 GEN
Solar/Wind Harmer
2.728
971227AH1-073 GEN
Solar/Wind Harmer
2.728
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
971125AH1-004 GEN
Solar/Wind Harmer
3.985
276916AD2-100_GEN
Solar/Wind Harmer
19.136
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LGEELTFEXP_LGEE->PJM
CLTF
6.756
MECLTFEXP_MEC->PJM
CLTF
15.399
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
NYPJM->LTFIMP_NY
CLTF
3.255
TVALTFEXP_TVA->PJM
CLTF
10.596
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
CPLELTFEXP_CPLE->PJM
CLTF
6.213
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
WECLTFEXP_WEC->PJM
CLTF
3.368
LAGNLTFEXP_LAGN->PJM
CLTF
20.26

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4149.41
MW Contribution:
45.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
7.16
971277AH1-098 GEN
Solar/Wind Harmer
7.418
970913AG2-568 GEN
Solar/Wind Harmer
9.337
942751AE2-291 GEN
Solar/Wind Harmer
10.38
966021AG1-471 GEN
Solar/Wind Harmer
5.751
339231AF1-038_GEN
Solar/Wind Harmer
1.917
964571AG1-320 GEN
Solar/Wind Harmer
8.183
972045AH1-571 GEN
Solar/Wind Harmer
1.979
927014AC1-188 GEN
Solar/Wind Harmer
1.527
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.569
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
7.336
276911AD2-131_GEN
Solar/Wind Harmer
3.87
24728805RICHG1
Adder
3.386
270013AE1-250 PV
Solar/Wind Harmer
3.249
339236AF1-050_GEN
Solar/Wind Harmer
1.872
970107AG2-081 GEN
Solar/Wind Harmer
2.99
962581AG1-107 GEN
Solar/Wind Harmer
4.728
961491AF2-440 GEN
Solar/Wind Harmer
1.965
970879AG2-548 GEN
Solar/Wind Harmer
1.066
276838X2-022 GEN2
Solar/Wind Harmer
0.21
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276174W4-005 GEN2
Solar/Wind Harmer
2.725
970241AG2-163 GEN
Solar/Wind Harmer
22.421
960201AF2-311 GEN
Solar/Wind Harmer
8.92
971543AH1-269 GEN
50/50
12.244
24684705SMG5
50/50
0.845
971313AH1-133 GEN
Solar/Wind Harmer
9.325
971061AG2-657 GEN
Solar/Wind Harmer
10.986
25196108MFTGT2
Adder
1.425
270205AE1-176
50/50
0.006
24728405LEESVG
50/50
0.293
24728405LEESVG
50/50
0.291
270574AD1-017 GEN2
Solar/Wind Harmer
8.469
270336AE1-100 GEN
Solar/Wind Harmer
2.751
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24735205WLF2G2
Adder
8.021
24723205RIVRG3
Adder
22.944
972203AH1-686 GEN
Adder
2.703
964901AG1-354 GEN
Solar/Wind Harmer
15.482
339241AF1-083 GEN
Solar/Wind Harmer
1.714
943111AE2-339 GEN
Solar/Wind Harmer
0.882
945681AF1-233 GEN
Solar/Wind Harmer
18.311
252516AE2-318_GEN
Solar/Wind Harmer
9.203
25194608D.CRK4
Adder
1.508
270197AD1-017 GEN1
Solar/Wind Harmer
2.541
970281AG2-184 GEN
Solar/Wind Harmer
27.117
962211AG1-066 GEN
Solar/Wind Harmer
3
270444AC2-157 GEN1
Solar/Wind Harmer
5.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.235
971881AH1-461 GEN
50/50
14.973
943031AE2-326 GEN
Solar/Wind Harmer
6.783
3147123OTTER R
Solar/Wind Harmer
-0.014
270030AE2-140 GEN
Solar/Wind Harmer
30.919
960911AF2-382 GEN
Solar/Wind Harmer
10.944
972103AH1-617 GEN
Solar/Wind Harmer
25.825
247619Y1-049
50/50
0.05
942671AE2-283 GEN
Solar/Wind Harmer
8.665
971485AH1-239 GEN
Solar/Wind Harmer
8.494
964781AG1-341 GEN
Solar/Wind Harmer
10.966
942891AE2-308 GEN
Solar/Wind Harmer
10.171
972043AH1-570 GEN
Solar/Wind Harmer
2.474
25194408D.CRK1
Adder
6.935
945391AF1-204 GEN
Solar/Wind Harmer
12.715
276615X2-022 GEN
Solar/Wind Harmer
1.772
24728905RICHG2
Adder
3.386
960251AF2-316 GEN
Solar/Wind Harmer
13.38
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.357
966391AG1-508 GEN
Solar/Wind Harmer
6.373
270069AE2-166 C O1
Solar/Wind Harmer
14.876
24734705WLF1G3
Adder
8.191
24734905WLF1G5
Adder
8.191
270399AC1-101 GEN
Solar/Wind Harmer
5.554
971981AH1-535 GEN
Solar/Wind Harmer
12.558
339216AC1-074 GEN
Solar/Wind Harmer
1.643
972165AH1-665 GEN
Solar/Wind Harmer
7.79
971985AH1-537 GEN
Solar/Wind Harmer
17.286
970823AG2-518 GEN
50/50
8.382
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
970417AG2-272 GEN
50/50
3.733
958121AF2-106 GEN
Solar/Wind Harmer
9.404
270346AE1-212 GEN
Solar/Wind Harmer
13.931
270018AE2-047 C O1
Solar/Wind Harmer
1.821
971461AH1-227 GEN
Solar/Wind Harmer
7.001
970223AG2-152 GEN
Solar/Wind Harmer
17.666
270330AC1-082 GEN2
Solar/Wind Harmer
0.511
24684305SMG1
50/50
0.796
971329AH1-144 GEN
Solar/Wind Harmer
11.725
24734805WLF1G4
Adder
8.191
24735105WLF2G1
Adder
8.021
270400AC1-102 GEN
Solar/Wind Harmer
5.554
941621AE2-160 GEN
Adder
4.283
957241AF2-018 GEN
Solar/Wind Harmer
5.755
270053AF1-130 C
Solar/Wind Harmer
22.996
3429211JKCT 2G
Adder
11.868
972163AH1-664 GEN
Solar/Wind Harmer
9.738
24290705CLAY-2
50/50
0.252
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
941801AE2-185 GEN
Solar/Wind Harmer
9.809
24686405CER G5
Adder
9.792
270329AC1-082 GEN1
Solar/Wind Harmer
0.511
24290705CLAY-2
50/50
0.252
270173AC1-122 GEN
Solar/Wind Harmer
3.444
958131AF2-107 GEN
Solar/Wind Harmer
7.106
971403AH1-188 GEN
Solar/Wind Harmer
18.845
944971AF1-162 GEN
Solar/Wind Harmer
9.064
960001AF2-291 GEN
Solar/Wind Harmer
3.112
970653AG2-424 GEN
Solar/Wind Harmer
4.88
3429421JKCT 10G
Adder
8.399
339221AD2-048_GEN
Solar/Wind Harmer
1.509
970091AG2-072 GEN
Adder
73.991
971073AG2-665 GEN
Solar/Wind Harmer
1.066
24290605CLAY-1
50/50
0.252
24684405SMG2
50/50
2.196
24728305BUCHG2
50/50
7.16
316217AC1-145 GEN
Solar/Wind Harmer
4.242
316197AC1-042 GEN
Solar/Wind Harmer
3.216
24686505CER G6
Adder
9.87
339211AE2-254 GEN
Solar/Wind Harmer
1.56
3429241JKCT 3G
Adder
12.024
24684605SMG4
50/50
2.211
970563AG2-360 GEN
50/50
45.815
962751AG1-124 GEN
Solar/Wind Harmer
18.82
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
270016AE1-250 BESS
Solar/Wind Harmer
3.249
24684505SMG3
50/50
1.342
3147312GRETNA
Solar/Wind Harmer
-0.005
971687AH1-348 GEN
Solar/Wind Harmer
1.358
270331AC1-082 GEN3
Solar/Wind Harmer
0.512
316123AC1-075 GEN
Solar/Wind Harmer
1.488
25196808ZIMRHP
Adder
70.578
25196008MFTGT1
Adder
1.293
252510AF1-249 C
Solar/Wind Harmer
0.383
270583AD2-179 GEN
Solar/Wind Harmer
20.716
270214AC2-123 GEN
Solar/Wind Harmer
4.31
971225AH1-072 GEN
Solar/Wind Harmer
2.729
971227AH1-073 GEN
Solar/Wind Harmer
2.729
24723005RIVRG1
Adder
22.944
24723105RIVRG2
Adder
22.944
971125AH1-004 GEN
Solar/Wind Harmer
3.987
276916AD2-100_GEN
Solar/Wind Harmer
19.15
253433AC1-085 GEN1
Solar/Wind Harmer
4.819
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
276763AC1-053 GEN1
Solar/Wind Harmer
3.567
276764AC1-053 GEN2
Solar/Wind Harmer
3.567
276668AB2-070 GEN1
Solar/Wind Harmer
1.995
276848AB2-070 GEN3
Solar/Wind Harmer
1.995
276849AB2-070 GEN2
Solar/Wind Harmer
1.995
959341AF2-225 GEN
Solar/Wind Harmer
13.316
274744AC1-111 GEN8
Adder
4.868
274735ELWOOD EC;4P
Adder
14.275
25306009OHH W.
Adder
2.502
3148463FAIRFLD
Solar/Wind Helper
0.726
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.842
24721905FLATG4
Adder
21.675
252519AF1-045_GEN
Solar/Wind Harmer
3.349
25194608D.CRK4
Adder
1.508
252524AE2-267 GEN
Solar/Wind Harmer
1.441
957381AF2-032 GEN
Solar/Wind Harmer
1.82
24728505AND G1
Adder
3.48
253317AC1-085 GEN4
Solar/Wind Harmer
7.592
946181AF1-283 GEN
Solar/Wind Harmer
11.789
276785W4-005 GEN1
Solar/Wind Harmer
2.725
971087AG2-675 GEN
Solar/Wind Harmer
3.32
274767LEE CO EC;8U
Adder
8.123
274682WAUKEGAN ;7U
Adder
15.699
274734ELWOOD EC;8P
Adder
14.275
274736ELWOOD EC;9P
Adder
14.275
316192AB2-158 GEN
Solar/Wind Helper
1.844
316447AC1-158 HLD
Solar/Wind Helper
2.775
3429391JKCT 9G
Adder
8.399
957541AF2-048 GEN
Solar/Wind Harmer
1.527
958171AF2-111 GEN
Solar/Wind Harmer
23.897
252507AC2-088 GEN
Solar/Wind Harmer
1.666
25196608WSDLE5
Adder
7.845
970193AG2-126 GEN
Solar/Wind Harmer
13.686
24728705AND G3
Adder
7.279
959611AF2-252 GEN
Solar/Wind Harmer
2.072
274730ELWOOD EC;6P
Adder
14.275
3147666LOUISA
Solar/Wind Helper
1.088
238152AF2-075_GEN
Solar/Wind Helper
0.604
316044AC1-158 PL1
Solar/Wind Helper
1.261
944221AF1-090 GEN
Solar/Wind Harmer
10.021
25196508WSDLE4
Adder
7.765
270356AE2-297 GEN
Solar/Wind Harmer
4.144
963841AG1-237 GEN
Solar/Wind Harmer
9.753
274854TWINGROVE;U2
Solar/Wind Harmer
6.285
270340AC2-060 GEN
Solar/Wind Harmer
2.685
276726Z2-087_GEN
Solar/Wind Harmer
7.019
274746AC1-111 G10
Adder
4.868
274731ELWOOD EC;2P
Adder
14.275
274733ELWOOD EC;3P
Adder
14.275
316164AC1-076 GEN
Solar/Wind Helper
1.176
339255AE2-071 GEN
Solar/Wind Harmer
1.217
339250AF1-203 GEN
Solar/Wind Harmer
0.627
339206AE1-143 GEN
Solar/Wind Harmer
2.203
970653AG2-424 GEN
Solar/Wind Harmer
0.706
970455AG2-298 GEN
Solar/Wind Harmer
3.519
339243AC2-075 GEN1
Solar/Wind Harmer
0.445
965931AG1-462 GEN
Solar/Wind Harmer
22.754
965091AG1-374 GEN
Solar/Wind Harmer
26.73
274760LEE CO EC;1U
Adder
8.219
24386205FR-12G C
Solar/Wind Harmer
2.082
276686W4-005 GEN3
Solar/Wind Harmer
2.725
963741AG1-226 GEN
Solar/Wind Harmer
40.358
270222AC2-111 GEN
Solar/Wind Harmer
3.991
276655WTG1_EQ
Solar/Wind Harmer
7.748
274822ROCKFORD ;11
Adder
17.27
3132273ORANGE
Solar/Wind Helper
0.056
23546401DTGZ2-030
Solar/Wind Helper
0.079
25196108MFTGT2
Adder
1.323
25196408WSDLE3
Adder
8.076
25196308WSDLE2
Adder
8.005
25196208WSDLE1
Adder
7.985
25196708WSDLE6
Adder
7.965
274728ELWOOD EC;5P
Adder
14.275
972273AH1-721 GEN
Adder
89.284
970093AG2-073 GEN
Solar/Wind Harmer
5.442
971191AH1-055 GEN
Solar/Wind Harmer
18.819
972167AH1-666 GEN
Solar/Wind Harmer
7.764
270186AC1-089 GEN
Solar/Wind Harmer
5.816
270367AC2-061_GEN
Solar/Wind Harmer
3.002
25196008MFTGT1
Adder
1.252
970879AG2-548 GEN
Solar/Wind Harmer
7.336
942481AE2-261 GEN
Solar/Wind Harmer
27.222
971993AH1-541 GEN
Solar/Wind Harmer
8.326
253394AE2-221_GEN
Solar/Wind Harmer
4.053
274729ELWOOD EC;1P
Adder
14.275
3147983MERCK5
Solar/Wind Helper
0.198
276621W2-048 GEN
Solar/Wind Harmer
5.641
253398AE2-221_GEN2
Solar/Wind Harmer
4.053
939741AE1-205 GEN
Solar/Wind Harmer
17.754
274761LEE CO EC;2U
Adder
8.219
315821AE2-092 GEN
Solar/Wind Helper
3.228
23583801GRNGAP
Solar/Wind Helper
4.293
24386605FR-22G C
Solar/Wind Harmer
2.09
3148133STUARTS
Solar/Wind Helper
0.313
316258AE1-075 C
Solar/Wind Helper
0.32
316468AD1-105 GEN
Solar/Wind Helper
1.088
24387005FR-3G C
Solar/Wind Harmer
1.922
24728605AND G2
Adder
3.48
253316AC1-085 GEN3
Solar/Wind Harmer
7.592
946171AF1-282 GEN
Solar/Wind Harmer
9.068
274848CAMPGROVE;RU
Solar/Wind Harmer
5.727
274828WAUKEGAN ;BP
Adder
9.652
274682WAUKEGAN ;7U
Adder
15.699
274745AC1-111 GEN9
Adder
4.868
274676JOLIET 29;8U
Adder
26.631
316499AE2-029_GEN
Solar/Wind Helper
1.725
316095T157 G97
Solar/Wind Helper
1.127
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316097T157 G90
Solar/Wind Helper
1.127
238147AE2-230_GEN1
Solar/Wind Helper
0.423
965911AG1-460 GEN
Solar/Wind Harmer
1.27
944031AF1-071 GEN
Solar/Wind Harmer
0.898
276656WTG2_EQ
Solar/Wind Harmer
1.026
274766LEE CO EC;7U
Adder
8.123
274732ELWOOD EC;7P
Adder
14.275
274674JOLIET 9 ;6U
Adder
13.37
3148013FISHERV
Solar/Wind Helper
0.523
3147666LOUISA
Solar/Wind Helper
0.626
24385905FR-11G C
Solar/Wind Harmer
4.039
960611AF2-352 GEN
Solar/Wind Harmer
2.072
274764LEE CO EC;5U
Adder
8.239
972235AH1-702 GEN1
Adder
2.219
274683WAUKEGAN ;8U
Adder
18.414
274683WAUKEGAN ;8U
Adder
15.522
274693ROCKY RD ;1P
Adder
9.629
274674JOLIET 9 ;6U
Adder
13.37
3132123MT JACKSON
Solar/Wind Helper
1.389
966001AG1-469 GEN
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316450AC1-158 RIC
Solar/Wind Helper
0.336
253406AD2-031_GEN
Solar/Wind Harmer
1.146
946321AF1-296 GEN
Solar/Wind Harmer
9.297
274853TWINGROVE;U1
Solar/Wind Harmer
6.419
270291AC1-194 GEN
Solar/Wind Harmer
4.532
972267AH1-718 GEN
Adder
3.687
274823ROCKFORD ;21
Adder
17.145
274675JOLIET 29;7U
Adder
26.631
274675JOLIET 29;7U
Adder
7.641
315616AA1-038_C
Solar/Wind Helper
3.296
3148013FISHERV
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.266
24386405FR-21G C
Solar/Wind Harmer
2.09
274765LEE CO EC;6U
Adder
8.239
274763LEE CO EC;4U
Adder
8.142
972236AH1-702 GEN2
Adder
1.93
274695ROCKY RD ;2P
Adder
9.725
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.036
942111AE2-223 GEN
Solar/Wind Harmer
7.277
274762LEE CO EC;3U
Adder
8.219
274696ROCKY RD ;4P
Adder
9.954
274697ROCKY RD ;3P
Adder
2.642
237061AD1-155 GEN
Solar/Wind Helper
1.646
24387305FR-4G C
Solar/Wind Harmer
2.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.54
CPLELTFEXP_CPLE->PJM
CLTF
6.22
SIGELTFEXP_SIGE->PJM
CLTF
0.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.302
WECLTFEXP_WEC->PJM
CLTF
3.371
LAGNLTFEXP_LAGN->PJM
CLTF
20.273
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.073
LGEELTFEXP_LGEE->PJM
CLTF
6.761
MECLTFEXP_MEC->PJM
CLTF
15.41
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.367
NYPJM->LTFIMP_NY
CLTF
3.251
TVALTFEXP_TVA->PJM
CLTF
10.603
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
247977 to 242524 ckt 17
242519 to 314912 ckt 1

Winter Peak Analysis

The New Service Request AG2-360 was evaluated as a 250.0 MW (250.0 MW Capacity) injection in the AEP area.

AG2-360 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (250.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC220.41 %1180.0B2600.84
33.67
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC218.08 %1180.0B2573.38
33.71
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC217.06 %1180.0B2561.3
33.73
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.66 %1180.0B2544.77
36.34
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC194.03 %1180.0B2289.58
34.32
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-A_SENS
SingleAC190.51 %1180.0B2248.06
33.67
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC190.04 %1180.0B2242.41
32.68
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 542T553_SRT-W_SENS
BreakerAC188.13 %1180.0B2219.98
33.71
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 553T564_SRT-W_SENS
BreakerAC187.09 %1180.0B2207.63
33.73
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
BusAC186.82 %1180.0B2204.47
32.8
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC186.02 %1180.0B2194.98
32.81
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC181.71 %1180.0B2144.19
36.34
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC180.89 %1180.0A2134.53
32.83
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC162.66 %1180.0B1919.42
34.32
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P7-1: LN 2114-535_SRT-A_SENS
TowerAC160.6 %1180.0B1895.12
32.68
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC156.61 %1180.0B1847.99
32.81
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
BusAC156.23 %1180.0B1843.56
32.99
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Base Case
SingleAC151.92 %1180.0A1792.68
32.83

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:220.41 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2600.84
MW Contribution:
33.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.996
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.684
24728305BUCHG2
50/50
5.51
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.97
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.414
3142956BIRDNECK
Solar/Wind Helper
0.519
3143316POE
Solar/Wind Helper
1.304
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.36
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.189
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
3141726DUNNSVL
Solar/Wind Helper
1.412
24289905CRG1H
50/50
0.807
24290105CRG2H
50/50
0.813
24290005CRG1L
50/50
0.807
24290205CRG2L
50/50
0.807
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.114
316316AC1-027 C
Solar/Wind Helper
0.089
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.284
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.239
3141196NOKESVL
Solar/Wind Helper
1.295
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.88
3143526WINTERP
Solar/Wind Helper
1.88
316404AE1-155 C
Solar/Wind Helper
0.718
316033AB2-134 GEN
Solar/Wind Helper
0.757
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.734
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.52
315651AD1-115 GEN
Solar/Wind Helper
0.758
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.653
315662AE1-191 GEN
Solar/Wind Helper
0.451
315666AE1-190 GEN
Solar/Wind Helper
0.113
315697AD1-025 GEN
Solar/Wind Helper
0.797
316185AD1-033 GEN
Solar/Wind Helper
0.352
316280AD1-041 GEN
Solar/Wind Helper
0.282
316447AC1-158 HLD
Solar/Wind Helper
0.966
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.405
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.439
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.811
270346AE1-212 GEN
Solar/Wind Harmer
0.545
270030AE2-140 GEN
Solar/Wind Harmer
1.083
270069AE2-166 C O1
Solar/Wind Harmer
0.526
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
0.403
316375AC2-012 GEN
Solar/Wind Helper
0.596
316197AC1-042 GEN
Solar/Wind Helper
0.215
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.981
316169AC1-164_GENC
Solar/Wind Helper
0.847
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.036
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.048
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.281
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.468
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.062
970563AG2-360 GEN
50/50
33.666
970823AG2-518 GEN
50/50
5.456
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.457
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.45
971403AH1-188 GEN
Solar/Wind Harmer
0.722
971461AH1-227 GEN
Solar/Wind Harmer
0.281
971543AH1-269 GEN
50/50
8.214
971687AH1-348 GEN
Solar/Wind Harmer
0.054
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.192
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.959
971981AH1-535 GEN
Solar/Wind Harmer
0.503
972103AH1-617 GEN
Solar/Wind Harmer
1.012
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.044
971881AH1-461 GEN
50/50
10.558
315773AC2-141 GEN
Solar/Wind Helper
1.246
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.256
316294AC1-161 GEN
Solar/Wind Helper
1.246
316473AC1-191 GEN
Solar/Wind Helper
0.483
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.657
NYPJM->LTFIMP_NY
CLTF
2.067
LGEELTFEXP_LGEE->PJM
CLTF
4.281
WECLTFEXP_WEC->PJM
CLTF
2.133
CPLELTFEXP_CPLE->PJM
CLTF
1.528
TVALTFEXP_TVA->PJM
CLTF
6.811
MECLTFEXP_MEC->PJM
CLTF
9.763
LAGNLTFEXP_LAGN->PJM
CLTF
12.763
SIGELTFEXP_SIGE->PJM
CLTF
0.322
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.192

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.08 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2573.38
MW Contribution:
33.71
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.693
24728305BUCHG2
50/50
5.518
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.141
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.412
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.302
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.352
3141913WHIT STONE
Solar/Wind Helper
0.35
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.409
24289905CRG1H
50/50
0.808
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.808
24290205CRG2L
50/50
0.808
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.11
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.282
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.293
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.877
3143526WINTERP
Solar/Wind Helper
1.877
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.733
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.15
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.757
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.796
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.965
316044AC1-158 PL1
Solar/Wind Helper
0.439
316045AC1-158 PL2
Solar/Wind Helper
1.403
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.113
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.085
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.846
316381AD1-082 GEN
Solar/Wind Helper
0.344
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.119
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.287
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.563
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.254
966871AG1-558 GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.064
970563AG2-360 GEN
50/50
33.712
970823AG2-518 GEN
50/50
5.462
970913AG2-568 GEN
Solar/Wind Harmer
0.421
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.545
971331AH1-145 GEN
Solar/Wind Harmer
12.465
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.223
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.963
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.051
971881AH1-461 GEN
50/50
10.572
315773AC2-141 GEN
Solar/Wind Helper
1.244
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.244
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.254
316484AD2-074 GEN
Solar/Wind Helper
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.833
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.705
NYPJM->LTFIMP_NY
CLTF
2.056
LGEELTFEXP_LGEE->PJM
CLTF
4.292
WECLTFEXP_WEC->PJM
CLTF
2.14
CPLELTFEXP_CPLE->PJM
CLTF
1.545
TVALTFEXP_TVA->PJM
CLTF
6.827
MECLTFEXP_MEC->PJM
CLTF
9.79
LAGNLTFEXP_LAGN->PJM
CLTF
12.796
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.128
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:217.06 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2561.3
MW Contribution:
33.73
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.997
24290605CLAY-1
50/50
0.169
24290605CLAY-1
50/50
0.169
24290705CLAY-2
50/50
0.169
24290705CLAY-2
50/50
0.169
24728205BUCHG1
50/50
5.696
24728305BUCHG2
50/50
5.522
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.14
3142416OLDCHRC
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.371
3142433PROV 92
Solar/Wind Helper
1.411
3142956BIRDNECK
Solar/Wind Helper
0.518
3143316POE
Solar/Wind Helper
1.301
316075AC2-137 C
Solar/Wind Helper
0.117
316077AC2-138 C
Solar/Wind Helper
0.079
3138133OCRAN
Solar/Wind Helper
0.105
3138133OCRAN
Solar/Wind Helper
0.21
3141766HARMONY
Solar/Wind Helper
0.07
3141783LANCAST
Solar/Wind Helper
0.21
3141783LANCAST
Solar/Wind Helper
0.14
3141813NORNECK
Solar/Wind Helper
0.351
3141913WHIT STONE
Solar/Wind Helper
0.349
3143226MDLTHAN
Solar/Wind Helper
0.359
3143873LANEXA
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3141726DUNNSVL
Solar/Wind Helper
1.408
24289905CRG1H
50/50
0.809
24290105CRG2H
50/50
0.815
24290005CRG1L
50/50
0.809
24290205CRG2L
50/50
0.809
316036AC1-147 C
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.085
316159AE1-175 C
Solar/Wind Helper
0.11
316240AF1-291 C
Solar/Wind Helper
0.109
316314AB2-024 C
Solar/Wind Helper
0.113
316316AC1-027 C
Solar/Wind Helper
0.088
316382AG1-145 C
Solar/Wind Helper
0.111
270205AE1-176
50/50
0.013
3145336SMITFLD
Solar/Wind Helper
1.281
3145336SMITFLD
Solar/Wind Helper
0.128
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.292
3141873WAN 176
Solar/Wind Helper
0.07
3143526WINTERP
Solar/Wind Helper
1.876
3143526WINTERP
Solar/Wind Helper
1.876
316404AE1-155 C
Solar/Wind Helper
0.716
316033AB2-134 GEN
Solar/Wind Helper
0.755
3142543TWELFTH
Solar/Wind Helper
0.034
316203AE2-005 GEN
Solar/Wind Helper
0.732
316441AF1-014 GEN
Solar/Wind Helper
0.112
316312AB1-027
Solar/Wind Helper
0.149
316369SG1_INVT
Solar/Wind Helper
0.519
315651AD1-115 GEN
Solar/Wind Helper
0.756
315839AE2-212 C
Solar/Wind Helper
0.107
315671AE2-027_GEN
Solar/Wind Helper
0.652
315662AE1-191 GEN
Solar/Wind Helper
0.45
315666AE1-190 GEN
Solar/Wind Helper
0.112
315697AD1-025 GEN
Solar/Wind Helper
0.795
316185AD1-033 GEN
Solar/Wind Helper
0.351
316280AD1-041 GEN
Solar/Wind Helper
0.281
316447AC1-158 HLD
Solar/Wind Helper
0.964
316044AC1-158 PL1
Solar/Wind Helper
0.438
316045AC1-158 PL2
Solar/Wind Helper
1.402
316450AC1-158 RIC
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.438
316156AD2-030 GEN
Solar/Wind Helper
0.111
316337AD2-073 GEN
Solar/Wind Helper
0.112
270583AD2-179 GEN
Solar/Wind Harmer
0.812
270346AE1-212 GEN
Solar/Wind Harmer
0.546
270030AE2-140 GEN
Solar/Wind Harmer
1.086
270069AE2-166 C O1
Solar/Wind Harmer
0.527
316006AB2-029 C
Solar/Wind Helper
0.102
316083AB2-161 GEN
Solar/Wind Helper
0.253
316132AB2-190 GEN1
Solar/Wind Helper
0.402
316458AB2-190 GEN2
Solar/Wind Helper
0.402
316375AC2-012 GEN
Solar/Wind Helper
0.595
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.113
315975AC1-164 GENB
Solar/Wind Helper
0.029
315976AC1-164 GENA
Solar/Wind Helper
0.979
316169AC1-164_GENC
Solar/Wind Helper
0.845
316381AD1-082 GEN
Solar/Wind Helper
0.343
316233AE1-074 FULL
Solar/Wind Helper
0.116
316236AE1-162_GEN
Solar/Wind Helper
0.103
3142946ENON
Solar/Wind Helper
0.035
3142946ENON
Solar/Wind Helper
0.118
3144536CHRHLND
Solar/Wind Helper
0.047
3144873MCLAUGH
Solar/Wind Helper
0.008
943031AE2-326 GEN
Solar/Wind Harmer
5.29
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.562
961611AG1-000B GEN
Solar/Wind Helper
0.467
961951AG1-038 GEN
Solar/Wind Helper
0.253
966871AG1-558 GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.122
970281AG2-184 GEN
Solar/Wind Harmer
1.065
970563AG2-360 GEN
50/50
33.733
970823AG2-518 GEN
50/50
5.464
970913AG2-568 GEN
Solar/Wind Harmer
0.422
971225AH1-072 GEN
Solar/Wind Harmer
0.11
971227AH1-073 GEN
Solar/Wind Harmer
0.11
971277AH1-098 GEN
Solar/Wind Harmer
0.324
971313AH1-133 GEN
Solar/Wind Harmer
0.458
971329AH1-144 GEN
Solar/Wind Harmer
0.546
971331AH1-145 GEN
Solar/Wind Harmer
12.472
971403AH1-188 GEN
Solar/Wind Harmer
0.724
971461AH1-227 GEN
Solar/Wind Harmer
0.282
971543AH1-269 GEN
50/50
8.227
971687AH1-348 GEN
Solar/Wind Harmer
0.055
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.047
957601AF2-054 GEN
Solar/Wind Helper
0.112
957831AF2-077 GEN
Solar/Wind Helper
0.11
957971AF2-091 GEN
Solar/Wind Helper
0.191
964211AG1-282 GEN
Solar/Wind Helper
0.113
966391AG1-508 GEN
Solar/Wind Harmer
3.965
971981AH1-535 GEN
Solar/Wind Harmer
0.504
972103AH1-617 GEN
Solar/Wind Harmer
1.014
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.053
971881AH1-461 GEN
50/50
10.579
315773AC2-141 GEN
Solar/Wind Helper
1.243
316164AC1-076 GEN
Solar/Wind Helper
0.336
316217AC1-145 GEN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
1.243
316473AC1-191 GEN
Solar/Wind Helper
0.482
316487AF1-042 GEN
Solar/Wind Helper
0.253
316484AD2-074 GEN
Solar/Wind Helper
0.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.927
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.726
NYPJM->LTFIMP_NY
CLTF
2.052
LGEELTFEXP_LGEE->PJM
CLTF
4.297
WECLTFEXP_WEC->PJM
CLTF
2.142
CPLELTFEXP_CPLE->PJM
CLTF
1.553
TVALTFEXP_TVA->PJM
CLTF
6.834
MECLTFEXP_MEC->PJM
CLTF
9.802
LAGNLTFEXP_LAGN->PJM
CLTF
12.81
SIGELTFEXP_SIGE->PJM
CLTF
0.323
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.442
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.77
MW Contribution:
36.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.018
24290605CLAY-1
50/50
0.171
24290605CLAY-1
50/50
0.171
24290705CLAY-2
50/50
0.171
24290705CLAY-2
50/50
0.171
24728205BUCHG1
50/50
6.231
24728305BUCHG2
50/50
6.04
3141426STAFORD
Solar/Wind Helper
0.074
3141906WESTMOR
Solar/Wind Helper
0.13
3142416OLDCHRC
Solar/Wind Helper
0.878
3142416OLDCHRC
Solar/Wind Helper
0.336
3142433PROV 92
Solar/Wind Helper
1.276
316075AC2-137 C
Solar/Wind Helper
0.106
316077AC2-138 C
Solar/Wind Helper
0.072
3138133OCRAN
Solar/Wind Helper
0.095
3138133OCRAN
Solar/Wind Helper
0.19
3141766HARMONY
Solar/Wind Helper
0.064
3141783LANCAST
Solar/Wind Helper
0.191
3141783LANCAST
Solar/Wind Helper
0.127
3141813NORNECK
Solar/Wind Helper
0.322
3141913WHIT STONE
Solar/Wind Helper
0.317
3143226MDLTHAN
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.191
3147123OTTER R
Solar/Wind Helper
0.187
3147312GRETNA
Solar/Wind Helper
0.063
3147312GRETNA
Solar/Wind Helper
0.254
3147666LOUISA
Solar/Wind Helper
1.258
3147666LOUISA
Solar/Wind Helper
0.723
3141726DUNNSVL
Solar/Wind Helper
1.29
24289905CRG1H
50/50
0.888
24290105CRG2H
50/50
0.895
24290005CRG1L
50/50
0.888
24290205CRG2L
50/50
0.888
316059AD1-063 C
Solar/Wind Helper
0.077
316314AB2-024 C
Solar/Wind Helper
0.103
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.238
3141196NOKESVL
Solar/Wind Helper
1.355
3141873WAN 176
Solar/Wind Helper
0.063
3143526WINTERP
Solar/Wind Helper
1.709
3143526WINTERP
Solar/Wind Helper
1.709
316404AE1-155 C
Solar/Wind Helper
0.655
3142543TWELFTH
Solar/Wind Helper
0.031
316203AE2-005 GEN
Solar/Wind Helper
0.662
316441AF1-014 GEN
Solar/Wind Helper
0.101
316312AB1-027
Solar/Wind Helper
0.136
315651AD1-115 GEN
Solar/Wind Helper
0.792
315662AE1-191 GEN
Solar/Wind Helper
0.407
315666AE1-190 GEN
Solar/Wind Helper
0.102
316280AD1-041 GEN
Solar/Wind Helper
0.254
316447AC1-158 HLD
Solar/Wind Helper
0.936
316044AC1-158 PL1
Solar/Wind Helper
0.425
316045AC1-158 PL2
Solar/Wind Helper
1.361
316450AC1-158 RIC
Solar/Wind Helper
0.113
316468AD1-105 GEN
Solar/Wind Helper
0.407
316156AD2-030 GEN
Solar/Wind Helper
0.1
316337AD2-073 GEN
Solar/Wind Helper
0.104
270399AC1-101 GEN
Solar/Wind Harmer
0.288
270583AD2-179 GEN
Solar/Wind Harmer
0.823
270494AE1-108_GEN
Solar/Wind Helper
0.847
270346AE1-212 GEN
Solar/Wind Harmer
0.589
270030AE2-140 GEN
Solar/Wind Harmer
1.139
270069AE2-166 C O1
Solar/Wind Harmer
0.548
270053AF1-130 C
Solar/Wind Harmer
1.012
316006AB2-029 C
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.442
316197AC1-042 GEN
Solar/Wind Helper
0.214
316223AC1-118
Solar/Wind Helper
0.105
315975AC1-164 GENB
Solar/Wind Helper
0.026
315976AC1-164 GENA
Solar/Wind Helper
0.883
316169AC1-164_GENC
Solar/Wind Helper
0.763
316233AE1-074 FULL
Solar/Wind Helper
0.106
3142946ENON
Solar/Wind Helper
0.032
3142946ENON
Solar/Wind Helper
0.107
943031AE2-326 GEN
Solar/Wind Harmer
5.484
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
0.53
944971AF1-162 GEN
Solar/Wind Harmer
6.858
961951AG1-038 GEN
Solar/Wind Helper
0.231
966871AG1-558 GEN
Solar/Wind Helper
0.11
966881AG1-559 GEN
Solar/Wind Helper
0.114
970281AG2-184 GEN
Solar/Wind Harmer
1.21
970563AG2-360 GEN
50/50
36.34
970823AG2-518 GEN
50/50
5.453
970913AG2-568 GEN
Solar/Wind Harmer
0.477
971061AG2-657 GEN
Solar/Wind Harmer
0.472
971225AH1-072 GEN
Solar/Wind Harmer
0.123
971227AH1-073 GEN
Solar/Wind Harmer
0.123
971277AH1-098 GEN
Solar/Wind Harmer
0.336
971313AH1-133 GEN
Solar/Wind Harmer
0.496
971329AH1-144 GEN
Solar/Wind Harmer
0.558
971331AH1-145 GEN
Solar/Wind Harmer
12.762
971403AH1-188 GEN
Solar/Wind Harmer
0.833
971461AH1-227 GEN
Solar/Wind Harmer
0.315
971543AH1-269 GEN
50/50
8.316
971687AH1-348 GEN
Solar/Wind Harmer
0.061
24415905BUCK
50/50
0.026
24416005BYLLESBY
50/50
0.049
957601AF2-054 GEN
Solar/Wind Helper
0.101
957971AF2-091 GEN
Solar/Wind Helper
0.18
964211AG1-282 GEN
Solar/Wind Helper
0.104
966391AG1-508 GEN
Solar/Wind Harmer
4.12
971981AH1-535 GEN
Solar/Wind Harmer
0.558
972103AH1-617 GEN
Solar/Wind Harmer
1.152
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.448
971881AH1-461 GEN
50/50
11.424
316164AC1-076 GEN
Solar/Wind Helper
0.342
316217AC1-145 GEN
Solar/Wind Helper
0.255
316473AC1-191 GEN
Solar/Wind Helper
0.44
270400AC1-102 GEN
Solar/Wind Harmer
0.288
316487AF1-042 GEN
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.442
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.422
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.119
NYPJM->LTFIMP_NY
CLTF
2.528
LGEELTFEXP_LGEE->PJM
CLTF
5.132
WECLTFEXP_WEC->PJM
CLTF
2.57
CPLELTFEXP_CPLE->PJM
CLTF
2.392
TVALTFEXP_TVA->PJM
CLTF
7.856
MECLTFEXP_MEC->PJM
CLTF
11.663
LAGNLTFEXP_LAGN->PJM
CLTF
14.865
SIGELTFEXP_SIGE->PJM
CLTF
0.385
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.446
AG2-052LTFEXP_AG2-052->PJM
LTF
0.155
AH1-155LTFEXP_AH1-155->PJM
LTF
0.233

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:194.03 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2289.58
MW Contribution:
34.32
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
1.014
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
24728205BUCHG1
50/50
5.791
24728305BUCHG2
50/50
5.614
3142416OLDCHRC
Solar/Wind Helper
0.842
3142416OLDCHRC
Solar/Wind Helper
0.323
316075AC2-137 C
Solar/Wind Helper
0.101
3143226MDLTHAN
Solar/Wind Helper
0.32
270205AE1-176
50/50
0.013
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
3148463FAIRFLD
Solar/Wind Harmer
-0.312
315616AA1-038_C
Solar/Wind Harmer
3.158
316312AB1-027
Solar/Wind Helper
0.13
316447AC1-158 HLD
Solar/Wind Helper
0.871
316044AC1-158 PL1
Solar/Wind Helper
0.396
316045AC1-158 PL2
Solar/Wind Helper
1.267
316450AC1-158 RIC
Solar/Wind Helper
0.106
316468AD1-105 GEN
Solar/Wind Helper
0.386
270399AC1-101 GEN
Solar/Wind Harmer
0.252
270583AD2-179 GEN
Solar/Wind Harmer
0.825
270494AE1-108_GEN
Solar/Wind Helper
0.869
270346AE1-212 GEN
Solar/Wind Harmer
0.553
270030AE2-140 GEN
Solar/Wind Harmer
1.13
270069AE2-166 C O1
Solar/Wind Harmer
0.546
24734705WLF1G3
50/50
7.099
24734805WLF1G4
50/50
7.099
24734905WLF1G5
50/50
7.099
24735105WLF2G1
50/50
6.939
24735205WLF2G2
50/50
6.939
315975AC1-164 GENB
Solar/Wind Helper
0.025
315976AC1-164 GENA
Solar/Wind Helper
0.849
316169AC1-164_GENC
Solar/Wind Helper
0.733
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.381
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.105
966881AG1-559 GEN
Solar/Wind Helper
0.108
970281AG2-184 GEN
Solar/Wind Harmer
1.082
970563AG2-360 GEN
50/50
34.318
970823AG2-518 GEN
50/50
5.548
970913AG2-568 GEN
Solar/Wind Harmer
0.426
971225AH1-072 GEN
Solar/Wind Harmer
0.112
971227AH1-073 GEN
Solar/Wind Harmer
0.112
971277AH1-098 GEN
Solar/Wind Harmer
0.33
971313AH1-133 GEN
Solar/Wind Harmer
0.466
971329AH1-144 GEN
Solar/Wind Harmer
0.554
971331AH1-145 GEN
Solar/Wind Harmer
12.663
971403AH1-188 GEN
Solar/Wind Harmer
0.734
971461AH1-227 GEN
Solar/Wind Harmer
0.287
971543AH1-269 GEN
50/50
8.359
971687AH1-348 GEN
Solar/Wind Harmer
0.056
24415905BUCK
50/50
0.025
24416005BYLLESBY
50/50
0.048
966391AG1-508 GEN
Solar/Wind Harmer
4.035
971981AH1-535 GEN
Solar/Wind Harmer
0.518
972103AH1-617 GEN
Solar/Wind Harmer
1.031
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
4.128
971881AH1-461 GEN
50/50
10.749
316164AC1-076 GEN
Solar/Wind Helper
0.321
316473AC1-191 GEN
Solar/Wind Helper
0.421
270400AC1-102 GEN
Solar/Wind Harmer
0.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.953
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.24
NYPJM->LTFIMP_NY
CLTF
2.009
LGEELTFEXP_LGEE->PJM
CLTF
4.347
WECLTFEXP_WEC->PJM
CLTF
2.162
CPLELTFEXP_CPLE->PJM
CLTF
2.241
TVALTFEXP_TVA->PJM
CLTF
7.056
MECLTFEXP_MEC->PJM
CLTF
9.948
LAGNLTFEXP_LAGN->PJM
CLTF
13.244
SIGELTFEXP_SIGE->PJM
CLTF
0.327
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.194

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:190.51 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2248.06
MW Contribution:
33.67
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
33.666

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:190.04 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2242.41
MW Contribution:
32.68
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.954
24290605CLAY-1
50/50
0.161
24290605CLAY-1
50/50
0.161
24290705CLAY-2
50/50
0.161
24290705CLAY-2
50/50
0.161
24728205BUCHG1
50/50
5.518
24728305BUCHG2
50/50
5.349
3142416OLDCHRC
Solar/Wind Helper
0.834
3142416OLDCHRC
Solar/Wind Helper
0.319
316075AC2-137 C
Solar/Wind Helper
0.1
3143226MDLTHAN
Solar/Wind Helper
0.312
3147123OTTER R
Solar/Wind Helper
0.192
3147312GRETNA
Solar/Wind Helper
0.065
3147312GRETNA
Solar/Wind Helper
0.261
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.245
3143526WINTERP
Solar/Wind Helper
1.627
3143526WINTERP
Solar/Wind Helper
1.627
316312AB1-027
Solar/Wind Helper
0.129
316447AC1-158 HLD
Solar/Wind Helper
0.869
316044AC1-158 PL1
Solar/Wind Helper
0.395
316045AC1-158 PL2
Solar/Wind Helper
1.264
316450AC1-158 RIC
Solar/Wind Helper
0.105
316468AD1-105 GEN
Solar/Wind Helper
0.383
270583AD2-179 GEN
Solar/Wind Harmer
0.773
270494AE1-108_GEN
Solar/Wind Helper
0.825
270346AE1-212 GEN
Solar/Wind Harmer
0.523
270030AE2-140 GEN
Solar/Wind Harmer
1.055
270069AE2-166 C O1
Solar/Wind Harmer
0.509
24734705WLF1G3
50/50
6.764
24734805WLF1G4
50/50
6.764
24734905WLF1G5
50/50
6.764
24735105WLF2G1
50/50
6.612
24735205WLF2G2
50/50
6.612
316197AC1-042 GEN
Solar/Wind Helper
0.22
316233AE1-074 FULL
Solar/Wind Helper
0.101
943031AE2-326 GEN
Solar/Wind Harmer
5.111
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.104
966881AG1-559 GEN
Solar/Wind Helper
0.107
970563AG2-360 GEN
50/50
32.682
970823AG2-518 GEN
50/50
5.169
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.313
971313AH1-133 GEN
Solar/Wind Harmer
0.443
971329AH1-144 GEN
Solar/Wind Harmer
0.52
971331AH1-145 GEN
Solar/Wind Harmer
11.877
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.822
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.825
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.934
971881AH1-461 GEN
50/50
10.218
316164AC1-076 GEN
Solar/Wind Helper
0.317
316217AC1-145 GEN
Solar/Wind Helper
0.262
316473AC1-191 GEN
Solar/Wind Helper
0.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.376
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.235
NYPJM->LTFIMP_NY
CLTF
1.913
LGEELTFEXP_LGEE->PJM
CLTF
4.185
WECLTFEXP_WEC->PJM
CLTF
2.088
CPLELTFEXP_CPLE->PJM
CLTF
1.958
TVALTFEXP_TVA->PJM
CLTF
6.727
MECLTFEXP_MEC->PJM
CLTF
9.577
LAGNLTFEXP_LAGN->PJM
CLTF
12.632
SIGELTFEXP_SIGE->PJM
CLTF
0.315
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.536
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.188

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 542T553_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 542T553_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.13 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2219.98
MW Contribution:
33.71
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
33.712

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 553T564_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 553T564_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:187.09 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2207.63
MW Contribution:
33.73
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
33.733

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_PHILLIPS-BUS_SRT-A/* $ DELCO $ PECO_P2-2_PHILLIPS-BUS $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.82 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2204.47
MW Contribution:
32.8
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.959
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.533
24728305BUCHG2
50/50
5.364
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.256
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.24
316447AC1-158 HLD
Solar/Wind Helper
0.833
316044AC1-158 PL1
Solar/Wind Helper
0.379
316045AC1-158 PL2
Solar/Wind Helper
1.211
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.069
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.789
24734805WLF1G4
50/50
6.789
24734905WLF1G5
50/50
6.789
24735105WLF2G1
50/50
6.638
24735205WLF2G2
50/50
6.638
316197AC1-042 GEN
Solar/Wind Helper
0.216
943031AE2-326 GEN
Solar/Wind Harmer
5.137
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.8
970823AG2-518 GEN
50/50
5.199
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.934
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.866
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.844
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.25
316217AC1-145 GEN
Solar/Wind Helper
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.386
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.91
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.644
NYPJM->LTFIMP_NY
CLTF
1.911
LGEELTFEXP_LGEE->PJM
CLTF
4.164
WECLTFEXP_WEC->PJM
CLTF
2.073
CPLELTFEXP_CPLE->PJM
CLTF
2.153
TVALTFEXP_TVA->PJM
CLTF
6.757
MECLTFEXP_MEC->PJM
CLTF
9.533
LAGNLTFEXP_LAGN->PJM
CLTF
12.686
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:186.02 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2194.98
MW Contribution:
32.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.534
24728305BUCHG2
50/50
5.365
3142416OLDCHRC
Solar/Wind Helper
0.819
3142416OLDCHRC
Solar/Wind Helper
0.314
3143226MDLTHAN
Solar/Wind Helper
0.324
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
316258AE1-075 C
Solar/Wind Helper
0.094
316405AF2-144 C
Solar/Wind Helper
0.088
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
3143526WINTERP
Solar/Wind Helper
1.661
3143526WINTERP
Solar/Wind Helper
1.661
316312AB1-027
Solar/Wind Helper
0.126
316447AC1-158 HLD
Solar/Wind Helper
0.837
316044AC1-158 PL1
Solar/Wind Helper
0.381
316045AC1-158 PL2
Solar/Wind Helper
1.218
316450AC1-158 RIC
Solar/Wind Helper
0.101
316468AD1-105 GEN
Solar/Wind Helper
0.374
316313AB2-026
Solar/Wind Helper
0.104
270583AD2-179 GEN
Solar/Wind Harmer
0.778
270494AE1-108_GEN
Solar/Wind Helper
0.764
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.068
270069AE2-166 C O1
Solar/Wind Harmer
0.515
24734705WLF1G3
50/50
6.788
24734805WLF1G4
50/50
6.788
24734905WLF1G5
50/50
6.788
24735105WLF2G1
50/50
6.636
24735205WLF2G2
50/50
6.636
316197AC1-042 GEN
Solar/Wind Helper
0.215
316233AE1-074 FULL
Solar/Wind Helper
0.103
943031AE2-326 GEN
Solar/Wind Harmer
5.139
943811AF1-049 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Helper
0.102
966881AG1-559 GEN
Solar/Wind Helper
0.104
970563AG2-360 GEN
50/50
32.806
970823AG2-518 GEN
50/50
5.206
970913AG2-568 GEN
Solar/Wind Harmer
0.406
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.523
971331AH1-145 GEN
Solar/Wind Harmer
11.946
971403AH1-188 GEN
Solar/Wind Harmer
0.701
971461AH1-227 GEN
Solar/Wind Harmer
0.274
971543AH1-269 GEN
50/50
7.875
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.947
971881AH1-461 GEN
50/50
10.253
316217AC1-145 GEN
Solar/Wind Helper
0.256
316473AC1-191 GEN
Solar/Wind Helper
0.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.009
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.274
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.872
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.539
NYPJM->LTFIMP_NY
CLTF
1.92
LGEELTFEXP_LGEE->PJM
CLTF
4.162
WECLTFEXP_WEC->PJM
CLTF
2.071
CPLELTFEXP_CPLE->PJM
CLTF
2.099
TVALTFEXP_TVA->PJM
CLTF
6.746
MECLTFEXP_MEC->PJM
CLTF
9.525
LAGNLTFEXP_LAGN->PJM
CLTF
12.662
SIGELTFEXP_SIGE->PJM
CLTF
0.313
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.646
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:181.71 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2144.19
MW Contribution:
36.34
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
36.34

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:180.89 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:2134.53
MW Contribution:
32.83
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.96
24290605CLAY-1
50/50
0.162
24290605CLAY-1
50/50
0.162
24290705CLAY-2
50/50
0.162
24290705CLAY-2
50/50
0.162
24728205BUCHG1
50/50
5.538
24728305BUCHG2
50/50
5.369
3147123OTTER R
Solar/Wind Helper
0.188
3147312GRETNA
Solar/Wind Helper
0.064
3147312GRETNA
Solar/Wind Helper
0.255
270205AE1-176
50/50
0.012
3146802CHATHAM
Solar/Wind Helper
0.239
316447AC1-158 HLD
Solar/Wind Helper
0.832
316044AC1-158 PL1
Solar/Wind Helper
0.378
316045AC1-158 PL2
Solar/Wind Helper
1.21
316450AC1-158 RIC
Solar/Wind Helper
0.101
270583AD2-179 GEN
Solar/Wind Harmer
0.777
270494AE1-108_GEN
Solar/Wind Helper
0.809
270346AE1-212 GEN
Solar/Wind Harmer
0.524
270030AE2-140 GEN
Solar/Wind Harmer
1.07
270069AE2-166 C O1
Solar/Wind Harmer
0.516
24734705WLF1G3
50/50
6.796
24734805WLF1G4
50/50
6.796
24734905WLF1G5
50/50
6.796
24735105WLF2G1
50/50
6.645
24735205WLF2G2
50/50
6.645
316197AC1-042 GEN
Solar/Wind Helper
0.215
943031AE2-326 GEN
Solar/Wind Harmer
5.14
943811AF1-049 GEN
Solar/Wind Harmer
0
966881AG1-559 GEN
Solar/Wind Helper
0.102
970563AG2-360 GEN
50/50
32.828
970823AG2-518 GEN
50/50
5.203
970913AG2-568 GEN
Solar/Wind Harmer
0.407
971225AH1-072 GEN
Solar/Wind Harmer
0.107
971227AH1-073 GEN
Solar/Wind Harmer
0.107
971277AH1-098 GEN
Solar/Wind Harmer
0.314
971313AH1-133 GEN
Solar/Wind Harmer
0.445
971329AH1-144 GEN
Solar/Wind Harmer
0.522
971331AH1-145 GEN
Solar/Wind Harmer
11.943
971403AH1-188 GEN
Solar/Wind Harmer
0.702
971461AH1-227 GEN
Solar/Wind Harmer
0.275
971543AH1-269 GEN
50/50
7.871
971687AH1-348 GEN
Solar/Wind Harmer
0.053
24415905BUCK
50/50
0.024
24416005BYLLESBY
50/50
0.046
966391AG1-508 GEN
Solar/Wind Harmer
3.846
958121AF2-106 GEN
Solar/Wind Harmer
0
24689505VACITY
50/50
3.951
971881AH1-461 GEN
50/50
10.259
316217AC1-145 GEN
Solar/Wind Helper
0.256
CBM West 1LTFEXP_CBM-W1->PJM
CBM
77.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.515
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.946
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.673
NYPJM->LTFIMP_NY
CLTF
1.904
LGEELTFEXP_LGEE->PJM
CLTF
4.171
WECLTFEXP_WEC->PJM
CLTF
2.076
CPLELTFEXP_CPLE->PJM
CLTF
2.163
TVALTFEXP_TVA->PJM
CLTF
6.767
MECLTFEXP_MEC->PJM
CLTF
9.549
LAGNLTFEXP_LAGN->PJM
CLTF
12.705
SIGELTFEXP_SIGE->PJM
CLTF
0.314
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.662
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:162.66 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1919.42
MW Contribution:
34.32
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
34.318

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P7-1: LN 2114-535_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2114-535_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:160.6 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1895.12
MW Contribution:
32.68
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.682

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.61 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1847.99
MW Contribution:
32.81
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.806

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10265_05LEESVI 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10265_05LEESVI 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:156.23 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1843.56
MW Contribution:
32.99
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.995

Details for [AG2-360] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:151.92 %
Rating:1180.0 MVA
Rating Type:A
MVA to Mitigate:1792.68
MW Contribution:
32.83
IPD Plant:AG2-360
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
PJM_IPD
32.828
CONTINGENCY 'DVP_P1-2: LN 553_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314910 TO BUS 313378 CKT 1   /*8CUNINGHAM   500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: 542T553_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P4-2: 553T564_SRT-W_SENS'
 OPEN BRANCH FROM BUS 313378 TO BUS 314910 CKT 1                /*8VONTAY      500.0 - 8CUNINGHAM   500.0
 OPEN BUS 315216                                                /*1CUNINGA      18.0
 OPEN BUS 315219                                                /*1CUNINGD      22.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3403 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 3040 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2114-535_SRT-A_SENS'
 OPEN BRANCH FROM BUS 235110 TO BUS 289543 CKT 1   /*01MDWBRK     500.0 - 05YEAT       500.0
 OPEN BRANCH FROM BUS 314085 TO BUS 314110 CKT 1   /*6REMNGCT     230.0 - 6ELK RUN     230.0
 OPEN BRANCH FROM BUS 314110 TO BUS 314125 CKT 1   /*6ELK RUN     230.0 - 6VINTHIL     230.0
 OPEN BUS 314110                                   /*6ELK RUN     230.0
END
CONTINGENCY 'PECO_P2-2_PHILLIPS-BUS_SRT-A
 DISCONNECT BUS 213888   /*PHLISCT1      18.0
 DISCONNECT BUS 213889   /*PHLISCT2      18.0
 DISCONNECT BUS 213892   /*PHLISL87     230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'AEP_P2-2_#10265_05LEESVI 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-360 was evaluated as a 250.0 MW injection and 250.0 MW withdrawal in the AEP area.

AG2-360 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 250.0 MW (250.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC173.68 %1180.0B2049.45
45.02
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC173.67 %1180.0B2049.35
45.02
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 547T566_SRT-L
BreakerAC173.35 %1180.0B2045.56
45.01
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC171.54 %1180.0B2024.13
45.02
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
37.85
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC138.39 %1180.0B1632.98
37.85
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC136.83 %1180.0B1614.63
37.85
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
BusAC110.97 %1180.0B1309.48
34.77
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17030___SRT-A
TowerAC110.49 %1180.0B1303.74
35.17
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P7-1_#17029___SRT-A
TowerAC110.3 %1180.0B1301.52
35.17
GD2AEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
BusAC109.1 %1180.0B1287.39
34.75

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.68 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.45
MW Contribution:
45.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.67 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2049.35
MW Contribution:
45.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.49
316405AF2-144 C
50/50
Charging
1.175
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
1.962
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316447AC1-158 HLD
Solar/Wind Helper
5.08
316044AC1-158 PL1
Solar/Wind Helper
2.309
316045AC1-158 PL2
Solar/Wind Helper
7.388
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.58
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.054
316169AC1-164_GENC
Solar/Wind Helper
1.775
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
966871AG1-558 GEN
Solar/Wind Helper
0.436
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.824
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.144
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
971981AH1-535 GEN
Solar/Wind Harmer
6.611
971981AH1-535 GEN
Solar/Wind Harmer
7.212
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.178
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 547T566_SRT-L


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 547T566_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.35 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2045.56
MW Contribution:
45.01
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.582
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.419
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.52
316303AF2-085
50/50
Charging
2.246
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
Solar/Wind Helper
0.491
316405AF2-144 C
50/50
Charging
1.177
316404AE1-155 C
Solar/Wind Helper
3.567
316203AE2-005 GEN
Solar/Wind Helper
3.62
316441AF1-014 GEN
Solar/Wind Helper
0.554
315616AA1-038_C
Solar/Wind Helper
2.018
316312AB1-027
Solar/Wind Helper
0.748
315651AD1-115 GEN
Solar/Wind Helper
4.205
315821AE2-092 GEN
Solar/Wind Helper
3.841
315662AE1-191 GEN
Solar/Wind Helper
2.223
315666AE1-190 GEN
Solar/Wind Helper
0.556
316280AD1-041 GEN
Solar/Wind Helper
1.389
316473AC1-191 GEN
Solar/Wind Helper
2.43
316447AC1-158 HLD
Solar/Wind Helper
5.083
316044AC1-158 PL1
Solar/Wind Helper
2.31
316045AC1-158 PL2
Solar/Wind Helper
7.393
316450AC1-158 RIC
Solar/Wind Helper
0.616
316468AD1-105 GEN
Solar/Wind Helper
2.227
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.564
316313AB2-026
Solar/Wind Helper
0.578
270399AC1-101 GEN
Solar/Wind Harmer
1.686
270400AC1-102 GEN
Solar/Wind Harmer
1.686
270583AD2-179 GEN
Solar/Wind Harmer
12.446
270494AE1-108_GEN
Solar/Wind Helper
5.59
270346AE1-212 GEN
Solar/Wind Harmer
8.185
270030AE2-140 GEN
Solar/Wind Harmer
17.478
270069AE2-166 C O1
Solar/Wind Harmer
8.425
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.769
316164AC1-076 GEN
Solar/Wind Helper
1.941
316223AC1-118
Solar/Wind Helper
0.568
315975AC1-164 GENB
Solar/Wind Helper
0.061
315976AC1-164 GENA
Solar/Wind Helper
2.057
316169AC1-164_GENC
Solar/Wind Helper
1.777
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.708
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.859
960911AF2-382 GEN
Solar/Wind Harmer
6.616
961951AG1-038 GEN
Solar/Wind Helper
1.26
963031AG1-152 GEN
50/50
Charging
10.856
966871AG1-558 GEN
Solar/Wind Helper
0.437
966881AG1-559 GEN
Solar/Wind Helper
0.447
970119AG2-088 GEN
50/50
Charging
16.846
970281AG2-184 GEN
Solar/Wind Harmer
15.746
970417AG2-272 GEN
50/50
8.425
970563AG2-360 GEN
50/50
45.014
970823AG2-518 GEN
50/50
19.368
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971277AH1-098 GEN
Solar/Wind Harmer
4.558
971277AH1-098 GEN
Solar/Wind Harmer
4.143
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.832
971331AH1-145 GEN
Solar/Wind Harmer
17.214
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.168
971507AH1-251 GEN
50/50
Charging
5.867
971531AH1-263 GEN
50/50
Charging
23.682
971543AH1-269 GEN
50/50
11.496
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.663
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.972
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.424
966391AG1-508 GEN
Solar/Wind Harmer
10.237
971981AH1-535 GEN
Solar/Wind Harmer
6.61
971981AH1-535 GEN
Solar/Wind Harmer
7.211
972103AH1-617 GEN
Solar/Wind Harmer
14.996
972273AH1-721 GEN
50/50
85.068
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.247
971881AH1-461 GEN
50/50
14.323
972293SS25-0014
50/50
Charging
57.048
316487AF1-042 GEN
Solar/Wind Helper
1.167
316484AD2-074 GEN
Solar/Wind Helper
2.229
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
114.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.652
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
5.764
WECLTFEXP_WEC->PJM
CLTF
2.895
CPLELTFEXP_CPLE->PJM
CLTF
4.745
TVALTFEXP_TVA->PJM
CLTF
9.524
MECLTFEXP_MEC->PJM
CLTF
13.347
LAGNLTFEXP_LAGN->PJM
CLTF
17.991
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.478
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.54 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2024.13
MW Contribution:
45.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316075AC2-137 C
Solar/Wind Helper
0.581
316077AC2-138 C
Solar/Wind Helper
0.394
316059AD1-063 C
Solar/Wind Helper
0.418
316159AE1-175 C
Solar/Wind Helper
0.538
316258AE1-075 C
Solar/Wind Helper
0.519
316303AF2-085
50/50
Charging
2.243
316314AB2-024 C
Solar/Wind Helper
0.561
316382AG1-145 C
Solar/Wind Helper
0.541
316405AF2-144 C
50/50
Charging
1.174
316404AE1-155 C
Solar/Wind Helper
3.563
316203AE2-005 GEN
Solar/Wind Helper
3.616
316441AF1-014 GEN
Solar/Wind Helper
0.553
315616AA1-038_C
Solar/Wind Helper
1.957
315651AD1-115 GEN
Solar/Wind Helper
4.201
315821AE2-092 GEN
Solar/Wind Helper
3.827
315662AE1-191 GEN
Solar/Wind Helper
2.22
315666AE1-190 GEN
Solar/Wind Helper
0.555
316280AD1-041 GEN
Solar/Wind Helper
1.388
316473AC1-191 GEN
Solar/Wind Helper
2.427
316468AD1-105 GEN
Solar/Wind Helper
2.225
316156AD2-030 GEN
Solar/Wind Helper
0.548
316337AD2-073 GEN
Solar/Wind Helper
0.563
316313AB2-026
Solar/Wind Helper
0.577
270399AC1-101 GEN
Solar/Wind Harmer
3.469
270400AC1-102 GEN
Solar/Wind Harmer
3.469
270583AD2-179 GEN
Solar/Wind Harmer
12.447
270494AE1-108_GEN
Solar/Wind Helper
5.579
270346AE1-212 GEN
Solar/Wind Harmer
8.186
270030AE2-140 GEN
Solar/Wind Harmer
17.484
270069AE2-166 C O1
Solar/Wind Harmer
8.427
270053AF1-130 C
Solar/Wind Harmer
12.797
316006AB2-029 C
Solar/Wind Helper
0.541
316192AB2-158 GEN
Solar/Wind Helper
2.765
316164AC1-076 GEN
Solar/Wind Helper
1.94
316223AC1-118
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.6
943031AE2-326 GEN
Solar/Wind Harmer
11.709
943811AF1-049 GEN
Solar/Wind Harmer
0
944491AF1-114 GEN
Solar/Wind Helper
2.856
944971AF1-162 GEN
Solar/Wind Harmer
2.093
960911AF2-382 GEN
Solar/Wind Harmer
6.617
961951AG1-038 GEN
Solar/Wind Helper
1.258
963031AG1-152 GEN
50/50
Charging
10.85
970119AG2-088 GEN
50/50
Charging
16.823
970281AG2-184 GEN
Solar/Wind Harmer
15.747
970417AG2-272 GEN
50/50
8.428
970563AG2-360 GEN
50/50
45.019
970823AG2-518 GEN
50/50
19.371
970913AG2-568 GEN
Solar/Wind Harmer
5.92
971225AH1-072 GEN
Solar/Wind Harmer
1.625
971227AH1-073 GEN
Solar/Wind Harmer
1.625
971313AH1-133 GEN
Solar/Wind Harmer
6.407
971329AH1-144 GEN
Solar/Wind Harmer
7.833
971331AH1-145 GEN
Solar/Wind Harmer
17.216
971403AH1-188 GEN
Solar/Wind Harmer
10.665
971461AH1-227 GEN
Solar/Wind Harmer
4.169
971507AH1-251 GEN
50/50
Charging
5.863
971531AH1-263 GEN
50/50
Charging
23.667
971543AH1-269 GEN
50/50
11.498
971687AH1-348 GEN
Solar/Wind Harmer
0.807
941621AE2-160 GEN
50/50
6.64
957191AF2-013 GEN
50/50
Charging
10.655
957601AF2-054 GEN
Solar/Wind Helper
0.551
957971AF2-091 GEN
Solar/Wind Helper
0.971
964211AG1-282 GEN
Solar/Wind Helper
0.564
966001AG1-469 GEN
Solar/Wind Helper
0.423
966391AG1-508 GEN
Solar/Wind Harmer
10.239
972103AH1-617 GEN
Solar/Wind Harmer
14.997
972273AH1-721 GEN
50/50
85.07
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.246
971881AH1-461 GEN
50/50
14.324
972293SS25-0014
50/50
Charging
57.012
316487AF1-042 GEN
Solar/Wind Helper
1.165
316484AD2-074 GEN
Solar/Wind Helper
2.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
105.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.004
CBM South 1LTFEXP_CBM-S1->PJM
CBM
35.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.666
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
5.763
WECLTFEXP_WEC->PJM
CLTF
2.894
CPLELTFEXP_CPLE->PJM
CLTF
4.752
TVALTFEXP_TVA->PJM
CLTF
9.526
MECLTFEXP_MEC->PJM
CLTF
13.346
LAGNLTFEXP_LAGN->PJM
CLTF
17.994
SIGELTFEXP_SIGE->PJM
CLTF
0.438
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
24.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.174
AH1-155LTFEXP_AH1-155->PJM
LTF
0.26

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
37.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.39 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1632.98
MW Contribution:
37.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Helper
0.693
316473AC1-191 GEN
Solar/Wind Helper
2.25
316447AC1-158 HLD
Solar/Wind Helper
4.798
316044AC1-158 PL1
Solar/Wind Helper
2.181
316045AC1-158 PL2
Solar/Wind Helper
6.979
316450AC1-158 RIC
Solar/Wind Helper
0.582
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
10.409
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
966871AG1-558 GEN
Solar/Wind Helper
0.404
966881AG1-559 GEN
Solar/Wind Helper
0.418
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971277AH1-098 GEN
Solar/Wind Harmer
3.644
971277AH1-098 GEN
Solar/Wind Harmer
3.312
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.83 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1614.63
MW Contribution:
37.85
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316473AC1-191 GEN
Solar/Wind Helper
2.25
316468AD1-105 GEN
Solar/Wind Helper
2.079
270399AC1-101 GEN
Solar/Wind Harmer
3.156
270400AC1-102 GEN
Solar/Wind Harmer
3.156
270583AD2-179 GEN
Solar/Wind Harmer
9.358
270494AE1-108_GEN
Solar/Wind Helper
4.816
270346AE1-212 GEN
Solar/Wind Harmer
6.755
270030AE2-140 GEN
Solar/Wind Harmer
3.161
270069AE2-166 C O1
Solar/Wind Harmer
6.316
270053AF1-130 C
Solar/Wind Harmer
11.711
316006AB2-029 C
Solar/Wind Helper
0.504
316164AC1-076 GEN
Solar/Wind Helper
1.745
943031AE2-326 GEN
Solar/Wind Harmer
9.448
944491AF1-114 GEN
Solar/Wind Helper
2.702
944971AF1-162 GEN
Solar/Wind Harmer
12.03
960911AF2-382 GEN
Solar/Wind Harmer
5.69
963031AG1-152 GEN
50/50
Charging
10.244
970281AG2-184 GEN
Solar/Wind Harmer
14.006
970417AG2-272 GEN
50/50
6.326
970563AG2-360 GEN
50/50
37.854
970823AG2-518 GEN
50/50
14.083
970913AG2-568 GEN
Solar/Wind Harmer
5.207
971225AH1-072 GEN
Solar/Wind Harmer
1.417
971227AH1-073 GEN
Solar/Wind Harmer
1.417
971313AH1-133 GEN
Solar/Wind Harmer
5.386
971329AH1-144 GEN
Solar/Wind Harmer
5.99
971331AH1-145 GEN
Solar/Wind Harmer
13.165
971403AH1-188 GEN
Solar/Wind Harmer
9.621
971461AH1-227 GEN
Solar/Wind Harmer
3.634
971507AH1-251 GEN
50/50
Charging
5.466
971531AH1-263 GEN
50/50
Charging
22.363
971543AH1-269 GEN
50/50
8.594
971687AH1-348 GEN
Solar/Wind Harmer
0.705
941621AE2-160 GEN
50/50
5.904
957191AF2-013 GEN
50/50
Charging
10.139
957971AF2-091 GEN
Solar/Wind Helper
0.919
966391AG1-508 GEN
Solar/Wind Harmer
8.202
972103AH1-617 GEN
Solar/Wind Harmer
13.339
972273AH1-721 GEN
50/50
76.948
957241AF2-018 GEN
Solar/Wind Harmer
0
958121AF2-106 GEN
Solar/Wind Harmer
0
970365AG2-240 GEN
50/50
Charging
1.154
971881AH1-461 GEN
50/50
11.944
972293SS25-0014
50/50
Charging
53.849
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.492
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.58
CBM South 1LTFEXP_CBM-S1->PJM
CBM
31.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.046
NYPJM->LTFIMP_NY
CLTF
2.2
LGEELTFEXP_LGEE->PJM
CLTF
5.464
WECLTFEXP_WEC->PJM
CLTF
2.768
CPLELTFEXP_CPLE->PJM
CLTF
3.423
TVALTFEXP_TVA->PJM
CLTF
8.341
MECLTFEXP_MEC->PJM
CLTF
12.527
LAGNLTFEXP_LAGN->PJM
CLTF
15.911
SIGELTFEXP_SIGE->PJM
CLTF
0.412
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.043
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1309.48
MW Contribution:
34.77
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3147123OTTER R
Solar/Wind Harmer
0.188
3147312GRETNA
Solar/Wind Harmer
0.273
3147312GRETNA
Solar/Wind Harmer
0.068
3146802CHATHAM
Solar/Wind Harmer
0.256
316447AC1-158 HLD
Solar/Wind Helper
4.5
316044AC1-158 PL1
Solar/Wind Helper
2.046
316045AC1-158 PL2
Solar/Wind Helper
6.545
316450AC1-158 RIC
Solar/Wind Helper
0.545
270583AD2-179 GEN
Solar/Wind Harmer
9.646
270346AE1-212 GEN
Solar/Wind Harmer
6.338
270030AE2-140 GEN
Solar/Wind Harmer
14.894
270069AE2-166 C O1
Solar/Wind Harmer
7.142
942671AE2-283 GEN
Solar/Wind Harmer
3.623
943031AE2-326 GEN
Solar/Wind Harmer
9.019
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.121
962751AG1-124 GEN
Solar/Wind Harmer
6.233
966881AG1-559 GEN
Solar/Wind Helper
0.39
970281AG2-184 GEN
Solar/Wind Harmer
11.543
970417AG2-272 GEN
50/50
7.231
970563AG2-360 GEN
50/50
34.767
970823AG2-518 GEN
50/50
14.96
970913AG2-568 GEN
Solar/Wind Harmer
4.573
971225AH1-072 GEN
Solar/Wind Harmer
1.261
971227AH1-073 GEN
Solar/Wind Harmer
1.261
971277AH1-098 GEN
Solar/Wind Harmer
3.537
971277AH1-098 GEN
Solar/Wind Harmer
3.215
971313AH1-133 GEN
Solar/Wind Harmer
4.952
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.329
971403AH1-188 GEN
Solar/Wind Harmer
8.261
971461AH1-227 GEN
Solar/Wind Harmer
3.235
971507AH1-251 GEN
50/50
Charging
5.111
971531AH1-263 GEN
50/50
Charging
20.999
971543AH1-269 GEN
50/50
8.911
971687AH1-348 GEN
Solar/Wind Harmer
0.626
941621AE2-160 GEN
50/50
5.119
941801AE2-185 GEN
Solar/Wind Harmer
4.102
966391AG1-508 GEN
Solar/Wind Harmer
7.933
971981AH1-535 GEN
Solar/Wind Harmer
5.175
971981AH1-535 GEN
Solar/Wind Harmer
5.645
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
Solar/Wind Harmer
2.357
971881AH1-461 GEN
50/50
11.072
972293SS25-0014
50/50
Charging
50.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.09
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.61
NYPJM->LTFIMP_NY
CLTF
1.786
LGEELTFEXP_LGEE->PJM
CLTF
4.54
WECLTFEXP_WEC->PJM
CLTF
2.293
CPLELTFEXP_CPLE->PJM
CLTF
4.184
TVALTFEXP_TVA->PJM
CLTF
7.544
MECLTFEXP_MEC->PJM
CLTF
10.573
LAGNLTFEXP_LAGN->PJM
CLTF
14.289
SIGELTFEXP_SIGE->PJM
CLTF
0.346
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
19.204
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137
AH1-155LTFEXP_AH1-155->PJM
LTF
0.206

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17030___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17030___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1303.74
MW Contribution:
35.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P7-1_#17029___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#17029___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1301.52
MW Contribution:
35.17
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.364
316044AC1-158 PL1
Solar/Wind Helper
1.983
316045AC1-158 PL2
Solar/Wind Helper
6.347
316450AC1-158 RIC
Solar/Wind Helper
0.529
270399AC1-101 GEN
Solar/Wind Harmer
1.329
270400AC1-102 GEN
Solar/Wind Harmer
1.329
270173AC1-122 GEN
Solar/Wind Helper
2.76
270583AD2-179 GEN
Solar/Wind Harmer
9.612
270494AE1-108_GEN
Solar/Wind Helper
5.948
270346AE1-212 GEN
Solar/Wind Harmer
6.395
270030AE2-140 GEN
Solar/Wind Harmer
12.927
270069AE2-166 C O1
Solar/Wind Harmer
6.336
316197AC1-042 GEN
Solar/Wind Helper
1.535
316217AC1-145 GEN
Solar/Wind Helper
1.974
943031AE2-326 GEN
Solar/Wind Harmer
9.122
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.18
970281AG2-184 GEN
Solar/Wind Harmer
12.374
970417AG2-272 GEN
50/50
6.193
970563AG2-360 GEN
50/50
35.173
970823AG2-518 GEN
50/50
14.895
970913AG2-568 GEN
Solar/Wind Harmer
4.649
971225AH1-072 GEN
Solar/Wind Harmer
1.274
971227AH1-073 GEN
Solar/Wind Harmer
1.274
971277AH1-098 GEN
Solar/Wind Harmer
3.545
971277AH1-098 GEN
Solar/Wind Harmer
3.223
971313AH1-133 GEN
Solar/Wind Harmer
5.006
971329AH1-144 GEN
Solar/Wind Harmer
6.065
971331AH1-145 GEN
Solar/Wind Harmer
13.33
971403AH1-188 GEN
Solar/Wind Harmer
8.401
971461AH1-227 GEN
Solar/Wind Harmer
3.267
971531AH1-263 GEN
50/50
Charging
20.391
971543AH1-269 GEN
50/50
8.871
971687AH1-348 GEN
Solar/Wind Harmer
0.633
941621AE2-160 GEN
50/50
5.212
966391AG1-508 GEN
Solar/Wind Harmer
7.965
971981AH1-535 GEN
Solar/Wind Harmer
5.117
971981AH1-535 GEN
Solar/Wind Harmer
5.582
972103AH1-617 GEN
Solar/Wind Harmer
11.785
958121AF2-106 GEN
Solar/Wind Harmer
0
961131AF2-404 GEN
50/50
Charging
2.924
971881AH1-461 GEN
50/50
11.185
972293SS25-0014
50/50
Charging
48.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.371
NYPJM->LTFIMP_NY
CLTF
1.631
LGEELTFEXP_LGEE->PJM
CLTF
4.594
WECLTFEXP_WEC->PJM
CLTF
2.32
CPLELTFEXP_CPLE->PJM
CLTF
3.013
TVALTFEXP_TVA->PJM
CLTF
7.367
MECLTFEXP_MEC->PJM
CLTF
10.609
LAGNLTFEXP_LAGN->PJM
CLTF
13.936
SIGELTFEXP_SIGE->PJM
CLTF
0.348
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.47
AG2-052LTFEXP_AG2-052->PJM
LTF
0.14
AH1-155LTFEXP_AH1-155->PJM
LTF
0.21

Details for 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1287.39
MW Contribution:
34.75
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Helper
4.334
316044AC1-158 PL1
Solar/Wind Helper
1.97
316045AC1-158 PL2
Solar/Wind Helper
6.303
316450AC1-158 RIC
Solar/Wind Helper
0.525
270399AC1-101 GEN
Solar/Wind Harmer
1.311
270400AC1-102 GEN
Solar/Wind Harmer
1.311
270173AC1-122 GEN
Solar/Wind Helper
2.227
270583AD2-179 GEN
Solar/Wind Harmer
9.325
270494AE1-108_GEN
Solar/Wind Helper
4.907
270346AE1-212 GEN
Solar/Wind Harmer
6.24
270030AE2-140 GEN
Solar/Wind Harmer
12.937
270069AE2-166 C O1
Solar/Wind Harmer
6.298
943031AE2-326 GEN
Solar/Wind Harmer
9.004
943811AF1-049 GEN
Solar/Wind Harmer
0
960911AF2-382 GEN
Solar/Wind Harmer
5.113
970281AG2-184 GEN
Solar/Wind Harmer
12.222
970417AG2-272 GEN
50/50
6.208
970563AG2-360 GEN
50/50
34.746
970823AG2-518 GEN
50/50
14.377
970913AG2-568 GEN
Solar/Wind Harmer
4.564
971225AH1-072 GEN
Solar/Wind Harmer
1.258
971227AH1-073 GEN
Solar/Wind Harmer
1.258
971277AH1-098 GEN
Solar/Wind Harmer
3.493
971277AH1-098 GEN
Solar/Wind Harmer
3.175
971313AH1-133 GEN
Solar/Wind Harmer
4.935
971329AH1-144 GEN
Solar/Wind Harmer
5.883
971331AH1-145 GEN
Solar/Wind Harmer
12.93
971403AH1-188 GEN
Solar/Wind Harmer
8.284
971461AH1-227 GEN
Solar/Wind Harmer
3.227
971531AH1-263 GEN
50/50
Charging
20.247
971543AH1-269 GEN
50/50
8.605
971687AH1-348 GEN
Solar/Wind Harmer
0.625
941621AE2-160 GEN
50/50
5.101
966391AG1-508 GEN
Solar/Wind Harmer
7.844
971981AH1-535 GEN
Solar/Wind Harmer
5.078
971981AH1-535 GEN
Solar/Wind Harmer
5.54
972103AH1-617 GEN
Solar/Wind Harmer
11.64
958121AF2-106 GEN
Solar/Wind Harmer
0
971881AH1-461 GEN
50/50
11.002
972293SS25-0014
50/50
Charging
48.638
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.535
NYPJM->LTFIMP_NY
CLTF
1.636
LGEELTFEXP_LGEE->PJM
CLTF
4.537
WECLTFEXP_WEC->PJM
CLTF
2.291
CPLELTFEXP_CPLE->PJM
CLTF
3.149
TVALTFEXP_TVA->PJM
CLTF
7.32
MECLTFEXP_MEC->PJM
CLTF
10.492
LAGNLTFEXP_LAGN->PJM
CLTF
13.848
SIGELTFEXP_SIGE->PJM
CLTF
0.344
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
16.744
AG2-052LTFEXP_AG2-052->PJM
LTF
0.138
AH1-155LTFEXP_AH1-155->PJM
LTF
0.207
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 547T566_SRT-L'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1                /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314901 TO BUS 314987 CKT 1                /*8BATH CO     500.0 - 8LEXINGTN SC 500.0
 OPEN BRANCH FROM BUS 314912 TO BUS 314987 CKT 1                /*8LEXNGTN     500.0 - 8LEXINGTN SC 500.0
 OPEN BUS 314987                                                /*8LEXINGTN SC 500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314901 TO BUS 314991 CKT 1 /*8BATH CO     500.0 - 8VALLEY SC   500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P2-2_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'AEP_P7-1_#17030___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242774 CKT 1   /*05MOSELEY    138.0 - 05ROANO2     138.0
END
CONTINGENCY 'AEP_P7-1_#17029___SRT-A'
 OPEN BRANCH FROM BUS 242589 TO BUS 243883 CKT 1   /*05CENTCR     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243883 CKT 1   /*05CLOVRD     138.0 - 05LAKEFR     138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1   /*05MOSELEY    138.0 - 05REUSENS1   138.0
END
CONTINGENCY 'AEP_P2-2_#10310_05REUSENS1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1    /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242719 TO BUS 242765 CKT 1    /*05MONEL      138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242724 TO BUS 242765 CKT 1    /*05MOSELEY    138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242882 CKT 4    /*05REUSENS1   138.0 - 05REUSENS     69.0
 OPEN BRANCH FROM BUS 242765 TO BUS 242889 CKT 1    /*05REUSENS1   138.0 - 05REUSENS     34.5
 OPEN BRANCH FROM BUS 242765 TO BUS 246229 CKT Z1   /*05REUSENS1   138.0 - 05REUSENS2   138.0
 REMOVE SWSHUNT FROM BUS 242765                     /*05REUSENS1   138.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-360, AH1-072, AH1-073, AH1-133, AH1-188, AH1-227 and AH1-535 in PJM Transition Cycle 2, Cluster 29 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 29 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 29 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 29 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-535 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-535 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-535 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-535 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 29 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 29 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 29 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 29 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 29 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 29 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 29 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Fictitious frequency response at AH1-227 generator bus tripped the queue project for several contingencies. Therefore, the frequency relay pickup times for instance 97146111 was set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

High voltage spikes occurred in the simulations immediately after fault clearing for some of the contingencies studied which tripped the AC1-101 and AC1-102 units. The voltage spike is a known artifact of the WECC generic renewable models as stated in the WECC Solar Plant Dynamic Model Guidelines: “It should be noted that generic dynamic models for inverter-based generator tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception and clearing. These spikes should be ignored in most cases, as they do not represent the performance of actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.”  A single cycle delay was added to the instantaneous over-voltage relays to avoid this fictitious over voltage tripping issue.

 

Similarly, under contingency P5.44, AH1-535 GEN1 tripped due to activation of its overvoltage protection. The issue was resolved by reducing its Vsched to 0.99 pu for this contingency.

 

AH1-227 generating unit exhibited slow active power recovery within the 20 second simulation window for contingency P1.11. This issue did not cause instability in the system,

 

however, the facility’s performance could be improved through model tuning, which can be evaluated in TC2 Phase 3 if active power recovery becomes a critical concern.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 29 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-360

Battery

AEP

250

Broadford substation 138 kV

AH1-072

Solar

AEP

20

Red Onion – VC5 69 kV

AH1-073

Solar

AEP

20

Red Onion – VC5 69 kV

AH1-133

Solar

AEP

70

Saltville – Tazewell 138 kV

AH1-188

Solar

AEP

140

Pigeon Creek substation 138 kV

AH1-227

Solar

AEP

51.3

Flemming - Fremont 69 kV

AH1-535

Solar/Battery

AEP

100

Nagel – Cane River 230 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-360 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVWithdrawn
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-085Midlothian 34.5 kVIn Service
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-404Gladys DP-Stonemill 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-152Remington CT 230 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-088Midlothian 230 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-230Dumont 345 kVActive
AG2-240Old Church 34.5 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-269Claytor 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-461Buckhorn 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-049Wurno 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Study Pending
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-360 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9763.005J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace WavetrapsCost Allocated$555,293N/A
AEPn9770.005ATKINS 138.0 kV to 05RURALR 138.0 kV ckt 1 - Sag StudyCost Allocated$500,000N/A
AEPn9783.005BROADX 138.0 kV to 05SMYTH 138.0 - Replace station conductorCost Allocated$100,000N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPs2572.3Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stationsContingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Grand Total:$1,155,293

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$555,293
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07279.0 MW24.1%$793,888
AG2-184 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
30.5 MW9.3%$306,832
AG2-36055.2 MW16.8%$555,293
AG2-363 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
28.6 MW8.7%$287,968
AG2-364 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
19.1 MW5.8%$191,979
AH1-617 ⧉ Harbert Metering 138 kV (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-184, AH1-617
29.1 MW8.9%$292,222
AH1-72186.7 MW26.4%$871,818

System Reinforcement: n9770.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9770.0 / AEP-TC2-19071
Title
05ATKINS 138.0 kV to 05RURALR 138.0 kV ckt 1 - Sag Study
Description
Sag Study Rural Retreat Loop 138 kV line from Str. 226-203 to Rural Retreat station.
Total Cost ($USD)
$500,000
Discounted Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$500,000
Time Estimate
12 to 24 Months

Contributor

FacilityContingency
05ATKINS-05RURALR 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A251.0 MVA
(All)B330.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-36029.7 MW100.0%$500,000

System Reinforcement: n9783.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9783.0 / AEP-TC2-19115
Title
05BROADX 138.0 kV to 05SMYTH 138.0 - Replace station conductor
Description
Station conductor between Broadford and Broadford reactor towards Smyth needs to be replaced
Total Cost ($USD)
$100,000
Discounted Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$100,000
Time Estimate
24 to 30 Months

Contributor

FacilityContingency
05BROADF-05BROADX 138.0 kV Ckt ZB line(Any)
Rating SetRating TypeRating Value
LLA246.0 MVA
LLB327.0 MVA
SUMA246.0 MVA
SUMB327.0 MVA
WINA311.0 MVA
WINB371.0 MVA
05BROADX-05SMYTH 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA246.0 MVA
LLB327.0 MVA
SUMA246.0 MVA
SUMB327.0 MVA
WINA311.0 MVA
WINB371.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-36059.3 MW100.0%$100,000

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-360 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-360 could receive cost allocation. Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: s2572.3
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2572.3
Title
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Description
Rebuild ~21 miles of the 138KV line between Saltville and Tazewell stations
Cost Information
Time Estimate
Sep 02 2036

Contingent

Note: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05SALTV1-AH1-133 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA296.0 MVA
LLB413.0 MVA
SUMA296.0 MVA
SUMB413.0 MVA
WINA375.0 MVA
WINB464.0 MVA
05TAZEWE-AH1-133 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA296.0 MVA
LLB413.0 MVA
SUMA296.0 MVA
SUMB413.0 MVA
WINA375.0 MVA
WINB464.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-360 may not presently have cost responsibility for this upgrade, AG2-360 may need this upgrade in-service to be deliverable to the PJM system. If AG2-360 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-360


AG2-360 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-360 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-360 One Line Diagram

AG2-360 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.