AG2-384 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:47

Chesterfield 230 kV

24.0 MW Capacity / 60.82 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $5,856,927 $14,043,897 = 0.42 AND ( $5,856,927 - $14,043,897 ) 60.8 = $-134,610 per MW

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Chesterfield County, Virginia. The installed facilities will have a total capability of 60.82 MW with 24.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-384
Project Name:
Chesterfield 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Chesterfield
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
60.82
MWE:
60.82
MWC:
24.0
Battery Storage Specification:
240.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Possum Point 5Deactivated Generator24.0Yes

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-384 will interconnect on the Virginia Electric and Power Company  (d/b/a Dominion Energy Virginia) transmission system at the Chesterfield 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-384 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-384Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$15,552,161$0$0
Other Scope$499,571$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$5,856,927$5,856,927$5,856,927
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$21,908,659$5,856,927$5,856,927

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-384

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-384
Project ID: AG2-384
20% of cost allocation for Phase II Network Upgrades:(A) $1,171,385
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,404,390
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Add one new line position and two new 230kV breakers installed at Chesterfield Substation to support the new battery storage system by Project Developer.

$3,886,977$1,567,590$346,456$55,904$5,856,927$5,856,927
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Metering accuracy coupling capacitor voltage transformers (CCVT), metering accuracy current transformers (CT) and associated metering equipment.

$317,977$33,491$141,737$6,366$499,571$499,571
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The portion of the interconnection switching station which is associated solely with the single feed to the generating facilities collector station. The equipment includes the disconnect switch, conductors and connectors. Due to space constraints in and around Chesterfield substation, the generation line will be underground to the Point of Change in Ownership (PCO) structure adjacent to the Project Developers interconnection facility.

$11,383,201$3,890,887$106,924$171,149$15,552,161$15,552,161
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$21,908,659$21,908,659
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 47 to 48 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-384 was evaluated as a 60.82 MW (24.0 MW Capacity) injection in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.82 MW (60.82 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC108.7 %559.3B607.94
1.34
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.3 %548.02B681.17
1.34
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.53 %548.02B578.33
1.27
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56702_SRT-A
BreakerAC109.86 %1107.0C1216.12
4.31
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: G2T567_SRT-A
BreakerAC102.6 %1107.0C1135.77
4.33
GD2DVP
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
DVP_P4-2: 208T287_SRT-A
BreakerAC108.48 %284.0C308.09
4.0
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC109.98 %548.02B602.71
1.34
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.22 %548.02B680.73
1.34
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.43 %548.02B577.77
1.27
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.35 %571.52B590.65
1.36
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC101.15 %571.52B578.11
1.35
GD2DVP
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.61 %571.52B575.03
1.35
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC104.8 %571.52B598.97
1.34
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC112.93 %559.3B631.64
1.34

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:607.94
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
315749AE2-041 GEN
50/50
4.941
3150921YORKTN3
50/50
1.926
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.043
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.388
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.941
972263AH1-716 GEN
50/50
32.803
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.598
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.865
971317AH1-138 GEN
Solar/Wind Harmer
0.613
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.345
3151221GRAVEL6
50/50
4.34
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.043
316156AD2-030 GEN
Solar/Wind Harmer
0.107
957191AF2-013 GEN
50/50
65.703
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
NYPJM->LTFIMP_NY
CLTF
0.57
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LGEELTFEXP_LGEE->PJM
CLTF
0.268
MECLTFEXP_MEC->PJM
CLTF
0.717
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
CPLELTFEXP_CPLE->PJM
CLTF
1.987
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.3 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.17
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.335
315749AE2-041 GEN
50/50
4.941
3150921YORKTN3
50/50
1.926
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.388
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.043
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.345
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151221GRAVEL6
Adder
4.09
3151211GRAVEL5
Adder
4.043
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.941
972263AH1-716 GEN
50/50
32.803
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.598
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.865
971317AH1-138 GEN
Solar/Wind Harmer
0.613
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
957191AF2-013 GEN
50/50
65.703
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316156AD2-030 GEN
Solar/Wind Harmer
0.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
NYPJM->LTFIMP_NY
CLTF
0.57
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LGEELTFEXP_LGEE->PJM
CLTF
0.268
MECLTFEXP_MEC->PJM
CLTF
0.717
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
CPLELTFEXP_CPLE->PJM
CLTF
1.987
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:578.33
MW Contribution:
1.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
316075AC2-137 C
Solar/Wind Harmer
0.018
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.372
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
2.968
944631AF1-128 GEN
50/50
30.096
971317AH1-138 GEN
Solar/Wind Harmer
0.632
3150331BIRCHWDA
50/50
158.939
315749AE2-041 GEN
50/50
4.972
3150921YORKTN3
50/50
2
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.602
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
958261AF2-120 GEN
Solar/Wind Harmer
7.999
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3141813NORNECK
Solar/Wind Harmer
0.28
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.091
3150641CHESTS8
50/50
0.191
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3141766HARMONY
Solar/Wind Harmer
1.864
3142946ENON
Solar/Wind Harmer
0.022
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3151221GRAVEL6
Adder
4.139
3151211GRAVEL5
Adder
4.091
3141843SHACKLE
50/50
0.748
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3151171GRAVELC
Adder
0.796
315759AF1-018 GEN
50/50
4.972
972263AH1-716 GEN
50/50
35.581
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.052
3141873WAN 176
Solar/Wind Harmer
0.03
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.066
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.104
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3150621CHESTS7
50/50
0.174
957191AF2-013 GEN
50/50
65.957
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
NYPJM->LTFIMP_NY
CLTF
0.471
TVALTFEXP_TVA->PJM
CLTF
0.6
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
WECLTFEXP_WEC->PJM
CLTF
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
LGEELTFEXP_LGEE->PJM
CLTF
0.179
MECLTFEXP_MEC->PJM
CLTF
0.511
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
CPLELTFEXP_CPLE->PJM
CLTF
1.903
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56702_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.86 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1216.12
MW Contribution:
4.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
6.047
3150351NORNECKC2
50/50
2.236
3150611CHESTG7
50/50
1.283
3144216WINCHST
50/50
0.676
3150801HOPHCF4
50/50
0.905
316075AC2-137 C
Solar/Wind Harmer
0.753
316484AD2-074 GEN
Solar/Wind Harmer
6.087
316077AC2-138 C
Solar/Wind Harmer
0.491
315778AD1-151 GEN
Solar/Wind Harmer
14.88
3151101ELIZAR3
Adder
11.505
944601AF1-125 GEN
Solar/Wind Harmer
61.188
316317KELFORD C
Solar/Wind Harmer
0.467
3145823KELFORD
Solar/Wind Harmer
-0.01
966621AG1-532 GEN
Solar/Wind Harmer
0.193
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
0.811
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315722AD1-056 GEN
Solar/Wind Harmer
3.124
964241AG1-285 GEN
Solar/Wind Harmer
5.416
3150631CHESTG8
50/50
1.263
3141913WHIT STONE
Solar/Wind Harmer
-0.025
957831AF2-077 GEN
Solar/Wind Harmer
0.667
315697AD1-025 GEN
Solar/Wind Harmer
3.349
971445AH1-216 GEN
Solar/Wind Harmer
9.499
3151081ELIZAR1
Adder
11.359
3151091ELIZAR2
Adder
11.162
316316AC1-027 C
Solar/Wind Harmer
0.424
957871AF2-081 GEN
Solar/Wind Harmer
6.787
315839AE2-212 C
Solar/Wind Harmer
0.381
971285AH1-108 GEN
Adder
0.791
970673AG2-436 GEN
Solar/Wind Harmer
20.768
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316210AC1-098 GEN
Solar/Wind Harmer
1.46
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
957861AF2-080 GEN
Solar/Wind Harmer
3.889
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
4.188
316238AB2-078_GEN
Solar/Wind Harmer
0.214
316239AB2-077_GEN
Solar/Wind Harmer
0.214
970683AG2-441 GEN
Solar/Wind Harmer
4.52
970681AG2-440 GEN
Solar/Wind Harmer
3
3150351NORNECKC2
50/50
2.199
944631AF1-128 GEN
50/50
102.225
316314AB2-024 C
Solar/Wind Harmer
2.409
964211AG1-282 GEN
Solar/Wind Harmer
0.732
971317AH1-138 GEN
Solar/Wind Harmer
2.654
316072AD1-144
Solar/Wind Harmer
0.293
315671AE2-027_GEN
Solar/Wind Harmer
2.553
944591AF1-124 GEN
Solar/Wind Harmer
62.381
939411AE1-173 GEN
Solar/Wind Harmer
57.212
971547AH1-271 GEN
Solar/Wind Harmer
2.784
315749AE2-041 GEN
50/50
8.56
3150921YORKTN3
50/50
4.616
3150761HOPPOLC
50/50
0.389
316203AE2-005 GEN
Solar/Wind Harmer
10.832
970293AG2-193 GEN
Solar/Wind Harmer
2.761
316223AC1-118
Solar/Wind Harmer
0.528
3144536CHRHLND
Solar/Wind Harmer
-0.002
3142956BIRDNECK
Solar/Wind Harmer
0.742
944581AF1-123 GEN
Solar/Wind Harmer
62.158
316305AF2-043 C
Solar/Wind Harmer
0.411
316320Y1-086
Solar/Wind Harmer
0.779
3146516WINFALL
Solar/Wind Harmer
-0.013
315735AD1-075 GEN1
Solar/Wind Harmer
1.15
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316011AB1-132 GEN
Solar/Wind Harmer
2.022
944011AF1-069 GEN
Solar/Wind Harmer
5.647
961601AG1-000A GEN
Solar/Wind Harmer
3.275
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
315975AC1-164 GENB
Solar/Wind Harmer
0.235
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
2.999
958261AF2-120 GEN
Solar/Wind Harmer
9.255
3142433PROV 92
Solar/Wind Harmer
-0.094
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
972135AH1-637 GEN
Solar/Wind Harmer
1.647
3145336SMITFLD
Solar/Wind Harmer
-0.061
316375AC2-012 GEN
Solar/Wind Harmer
4.826
3146456SLIGO L269
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.033
3146206CASHIE
Solar/Wind Harmer
-0.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.447
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.673
3147043LAWRENC
Adder
0.708
3146083TARBORO
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.468
316359AB2-059 GEN
Solar/Wind Harmer
1.105
3142053HEARTS
Solar/Wind Harmer
0.097
316131AB2-060 GEN
Solar/Wind Harmer
0.761
957601AF2-054 GEN
Solar/Wind Harmer
0.753
3141813NORNECK
Solar/Wind Harmer
-0.023
3138283WHITEMARSH
Solar/Wind Harmer
0.034
3151191GRAVEL3
Adder
10.294
316018AA1-139 ULT2
Solar/Wind Harmer
1.16
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.558
315800Z1-036_GEN1
Solar/Wind Harmer
3.088
315732AD1-074 GEN1
Solar/Wind Harmer
2.3
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
0.092
3145513AHOSKIE
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.582
316426AA2-053 GEN
Solar/Wind Harmer
0.976
315652AC1-086 GEN
Solar/Wind Harmer
10.893
3137643SOCKMAN
Solar/Wind Harmer
-0.038
316233AE1-074 FULL
Solar/Wind Harmer
0.254
971283AH1-107 GEN
Solar/Wind Harmer
1.535
971967AH1-528 GEN
Solar/Wind Harmer
17.218
316327AA2-057 GEN
Solar/Wind Harmer
0.879
970085AG2-068 GEN
Solar/Wind Harmer
5.436
3144303KENBRDG
Solar/Wind Harmer
-0.005
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3141766HARMONY
Solar/Wind Harmer
2.408
3142946ENON
Solar/Wind Harmer
-0.009
961951AG1-038 GEN
Solar/Wind Harmer
3.185
3142416OLDCHRC
Solar/Wind Harmer
1.739
970133AG2-095 GEN
Solar/Wind Harmer
1.937
3145336SMITFLD
Solar/Wind Harmer
-0.006
316017AA1-139 ULT1
Solar/Wind Harmer
1.095
315813AE1-149 C
Solar/Wind Harmer
8.468
3146456SLIGO L269
Solar/Wind Harmer
-0.013
971153AH1-033 GEN
Solar/Wind Harmer
1.566
3145273HOLLAND
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.012
3146206CASHIE
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316181AB2-040 GEN
Solar/Wind Harmer
1.325
3147043LAWRENC
Solar/Wind Harmer
-0.005
316420AA1-050 GEN
Solar/Wind Harmer
0.994
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3138543CONSLDL
Solar/Wind Harmer
-0.006
316478AD1-087 GEN
Solar/Wind Harmer
0.663
959311AF2-222 GEN
Solar/Wind Harmer
6.842
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
970603AG2-384 GEN
50/50
4.312
316059AD1-063 C
Solar/Wind Harmer
0.61
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3151201GRAVEL4
Adder
10.426
3151221GRAVEL6
Adder
10.414
3151211GRAVEL5
Adder
10.294
316311AC2-079 GEN
Solar/Wind Harmer
6.795
313526AB2-022
Solar/Wind Harmer
0.358
3146396TANGLEW
Solar/Wind Harmer
0.243
3146206CASHIE
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.27
315814AE2-033 C
Solar/Wind Harmer
10.023
961941AG1-037 GEN
Solar/Wind Harmer
0.08
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146043SEABORD
Solar/Wind Harmer
-0.01
316274AC1-208 GEN
Solar/Wind Harmer
0.982
316486AD2-202 GEN
Solar/Wind Harmer
0.194
3141843SHACKLE
50/50
1.24
3143096IRON208
50/50
0.698
3143096IRON208
50/50
0.684
3141873WAN 176
Solar/Wind Harmer
2.987
3141906WESTMOR
Solar/Wind Harmer
-0.008
316458AB2-190 GEN2
Solar/Wind Harmer
1.704
961611AG1-000B GEN
Solar/Wind Harmer
3.43
3151171GRAVELC
Adder
2.004
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.73
316321Z2-027
Solar/Wind Harmer
0.355
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3150861SPRUNCD
Adder
0.484
3156081AA2-088 GEN
Solar/Wind Harmer
3.602
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.119
3145933PARMELE
Solar/Wind Harmer
-0.01
970917AG2-570 GEN
Solar/Wind Harmer
22.051
3146233WITAKRS
Solar/Wind Harmer
0.177
3146233WITAKRS
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
2.482
971775AH1-396 GEN
Solar/Wind Harmer
0.467
315759AF1-018 GEN
50/50
8.56
3143873LANEXA
Solar/Wind Harmer
-0.016
3141873WAN 176
Solar/Wind Harmer
-0.005
3138133OCRAN
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.743
316159AE1-175 C
Solar/Wind Harmer
0.662
316236AE1-162_GEN
Solar/Wind Harmer
0.459
944491AF1-114 GEN
Solar/Wind Harmer
4.32
970657AG2-426 GEN
Solar/Wind Harmer
0.852
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.048
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315733AD1-074 GEN2
Solar/Wind Harmer
2.3
970601AG2-382 GEN
Solar/Wind Harmer
4.873
3146033SCOT NK
Solar/Wind Harmer
-0.038
970533AG2-339 GEN
Solar/Wind Harmer
6.464
946281AF1-292 GEN
Solar/Wind Harmer
0.213
971281AH1-106 GEN
Solar/Wind Harmer
1.535
970581AG2-369 GEN
Solar/Wind Harmer
4.675
3143096IRON208
50/50
0.698
3150771HOPHCF1
50/50
0.621
315662AE1-191 GEN
Solar/Wind Harmer
3.063
316280AD1-041 GEN
Solar/Wind Harmer
1.915
3138133OCRAN
Solar/Wind Harmer
-0.015
316404AE1-155 C
Solar/Wind Harmer
4.559
3138126ROCKLANDING
Solar/Wind Harmer
0.059
971069AG2-661 GEN
Solar/Wind Harmer
2.645
316369SG1_INVT
Solar/Wind Harmer
2.96
961611AG1-000B GEN
Solar/Wind Harmer
8.038
3151171GRAVELC
Adder
1.524
957971AF2-091 GEN
Solar/Wind Harmer
1.469
3150981CHESPKA
Adder
1.551
3142543TWELFTH
Solar/Wind Harmer
-0.001
316381AD1-082 GEN
Solar/Wind Harmer
1.236
319010AE1-072 C
Solar/Wind Harmer
2.728
315611Z1-036_GEN2
Solar/Wind Harmer
3.088
3130156CHOWAN
Solar/Wind Harmer
-0.012
315816AE2-034 GEN
Solar/Wind Harmer
0.958
971163AH1-040 GEN
Solar/Wind Harmer
11.126
315737AD1-076 GEN
Solar/Wind Harmer
2.162
3146293MARTNCO
Solar/Wind Harmer
0.06
316087AB2-174 GEN
Solar/Wind Harmer
1.356
970087AG2-069 GEN
Solar/Wind Harmer
8.153
3145493TOT1
Solar/Wind Harmer
0.255
3146233WITAKRS
Solar/Wind Harmer
-0.034
957481AF2-042 GEN
Solar/Wind Harmer
25.188
315693AD1-088 GEN
Solar/Wind Harmer
3.837
3143226MDLTHAN
Solar/Wind Harmer
-0.008
315785AD2-033 C
Solar/Wind Harmer
1.517
3141843SHACKLE
50/50
0.068
3150341NORNECKC1
50/50
2.309
3150341NORNECKC1
50/50
2.291
316487AF1-042 GEN
Solar/Wind Harmer
3.185
3150681DARBY 2
Adder
10.639
316033AB2-134 GEN
Solar/Wind Harmer
5.344
3145506HICKORY
Solar/Wind Harmer
-0.054
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
316339AD2-160 GEN
Solar/Wind Harmer
0.914
316388AE2-253 GEN
Solar/Wind Harmer
0.914
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.079
3145493TOT1
Solar/Wind Harmer
0.133
316049AB1-081 GEN
Solar/Wind Harmer
0.884
313527AB2-043 GEN
Solar/Wind Harmer
1.154
970323AG2-213 GEN
Solar/Wind Harmer
3.309
3150641CHESTS8
50/50
0.65
3141726DUNNSVL
Solar/Wind Harmer
-0.097
962861AG1-135 GEN
Solar/Wind Harmer
8.986
316337AD2-073 GEN
Solar/Wind Harmer
0.583
316132AB2-190 GEN1
Solar/Wind Harmer
1.704
316036AC1-147 C
Solar/Wind Harmer
0.376
315773AC2-141 GEN
Solar/Wind Harmer
5.723
316093AE2-104_GEN
Solar/Wind Harmer
3.909
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
3150851SPRUNCC
Adder
0.484
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
0.322
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.017
316494AC1-189 GEN
Solar/Wind Harmer
0.957
970919AG2-571 GEN
Solar/Wind Harmer
2.791
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3150781HOPHCF2
50/50
0.621
315666AE1-190 GEN
Solar/Wind Harmer
0.766
316156AD2-030 GEN
Solar/Wind Harmer
0.67
3150671DARBY 1
Adder
10.627
3150991CHESPKB
Adder
1.301
3150991CHESPKB
Adder
1.27
315835AF2-110_GEN
Solar/Wind Harmer
1.68
316435W1029_GEN3
Solar/Wind Harmer
2.374
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
316240AF1-291 C
Solar/Wind Harmer
0.389
315614AA2-178 GEN
Solar/Wind Harmer
1.277
316065AD1-022 GEN
Solar/Wind Harmer
5.616
3145893MURPHYS
Solar/Wind Harmer
0.302
3145893MURPHYS
Solar/Wind Harmer
-0.019
316140AB2-099
Solar/Wind Harmer
0.071
316005AA1-067
Solar/Wind Harmer
0.186
972187AH1-678 GEN
Adder
2.327
3145453TOT5
Solar/Wind Harmer
0.08
961601AG1-000A GEN
Solar/Wind Harmer
3.234
971223AH1-071 GEN
Solar/Wind Harmer
0.943
964791AG1-342 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
10.023
3145823KELFORD
Solar/Wind Harmer
-0.01
941031AE2-094 GEN
Solar/Wind Harmer
18.022
960081AF2-299 GEN
Solar/Wind Harmer
1.071
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3143526WINTERP
Solar/Wind Harmer
-0.049
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
0.719
971065AG2-659 GEN
Solar/Wind Harmer
4.056
970401AG2-262 GEN
Solar/Wind Harmer
0.432
316034AC1-036 C
Solar/Wind Harmer
0.122
3150621CHESTS7
50/50
0.589
3150791HOPHCF3
50/50
0.621
316441AF1-014 GEN
Solar/Wind Harmer
1.732
316312AB1-027
Solar/Wind Harmer
0.58
316185AD1-033 GEN
Solar/Wind Harmer
1.445
944641AF1-129 GEN
Adder
55.209
3144356SAPONY
Solar/Wind Harmer
0.377
316315AB2-025 C
Solar/Wind Harmer
0.291
962571AG1-106 GEN
Solar/Wind Harmer
1.392
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
1.121
3145783HORNRTN
Solar/Wind Harmer
0.897
3145783HORNRTN
Solar/Wind Harmer
0.28
3145783HORNRTN
Solar/Wind Harmer
0.112
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.652
315724AD1-057 GEN
Solar/Wind Harmer
1.718
3145603CNETO
Solar/Wind Harmer
0.053
316263AC1-034 GEN
Solar/Wind Harmer
3.851
970099AG2-077 GEN
Solar/Wind Harmer
10.075
315687AD1-152 GEN
Solar/Wind Harmer
0.863
316237AB2-079_GEN
Solar/Wind Harmer
0.214
962561AG1-105 GEN
Solar/Wind Harmer
3.768
3150691DARBY 3
50/50
11.329
3150701DARBY 4
50/50
11.303
315976AC1-164 GENA
Solar/Wind Harmer
7.959
316169AC1-164_GENC
Solar/Wind Harmer
6.876
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
4.423
3142366NRTHEST
Adder
0.395
3146456SLIGO L269
Solar/Wind Harmer
1.598
316083AB2-161 GEN
Solar/Wind Harmer
2.193
316349AD2-085 GEN
Solar/Wind Harmer
1.196
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.374
316433W1029_GEN2
Solar/Wind Harmer
2.374
3146376EDENTON
Solar/Wind Harmer
0.367
3146376EDENTON
Solar/Wind Harmer
0.367
315742AE1-103 GEN
Solar/Wind Harmer
2.939
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
0.673
970933AG2-581 GEN
Solar/Wind Harmer
8.336
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
316118AC1-105 GEN
Solar/Wind Harmer
0.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.559
NYPJM->LTFIMP_NY
CLTF
0.718
TVALTFEXP_TVA->PJM
CLTF
0.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.959
WECLTFEXP_WEC->PJM
CLTF
0.06
LAGNLTFEXP_LAGN->PJM
CLTF
1.863
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.239
LGEELTFEXP_LGEE->PJM
CLTF
0.131
MECLTFEXP_MEC->PJM
CLTF
0.519
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.963
CPLELTFEXP_CPLE->PJM
CLTF
4.002
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: G2T567_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: G2T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.6 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1135.77
MW Contribution:
4.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
6.065
3150351NORNECKC2
50/50
2.242
3150611CHESTG7
50/50
1.287
3144216WINCHST
50/50
0.679
3150801HOPHCF4
50/50
0.908
316075AC2-137 C
Solar/Wind Harmer
0.755
316484AD2-074 GEN
Solar/Wind Harmer
6.105
316077AC2-138 C
Solar/Wind Harmer
0.493
315778AD1-151 GEN
Solar/Wind Harmer
14.944
3151101ELIZAR3
Adder
11.563
944601AF1-125 GEN
Solar/Wind Harmer
61.506
316317KELFORD C
Solar/Wind Harmer
0.47
3145823KELFORD
Solar/Wind Harmer
-0.01
966621AG1-532 GEN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.01
316212AC1-099_GEN
Solar/Wind Harmer
0.817
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315722AD1-056 GEN
Solar/Wind Harmer
3.149
964241AG1-285 GEN
Solar/Wind Harmer
5.472
3150631CHESTG8
50/50
1.267
3141913WHIT STONE
Solar/Wind Harmer
-0.025
957831AF2-077 GEN
Solar/Wind Harmer
0.669
315697AD1-025 GEN
Solar/Wind Harmer
3.364
971445AH1-216 GEN
Solar/Wind Harmer
9.543
3151081ELIZAR1
Adder
11.417
3151091ELIZAR2
Adder
11.219
316316AC1-027 C
Solar/Wind Harmer
0.426
957871AF2-081 GEN
Solar/Wind Harmer
6.822
315839AE2-212 C
Solar/Wind Harmer
0.383
971285AH1-108 GEN
Adder
0.796
970673AG2-436 GEN
Solar/Wind Harmer
20.923
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316210AC1-098 GEN
Solar/Wind Harmer
1.471
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
957861AF2-080 GEN
Solar/Wind Harmer
3.921
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
4.224
316238AB2-078_GEN
Solar/Wind Harmer
0.216
316239AB2-077_GEN
Solar/Wind Harmer
0.216
970683AG2-441 GEN
Solar/Wind Harmer
4.571
970681AG2-440 GEN
Solar/Wind Harmer
3.034
315749AE2-041 GEN
50/50
8.583
3150921YORKTN3
50/50
4.633
3150761HOPPOLC
50/50
0.39
316203AE2-005 GEN
Solar/Wind Harmer
10.862
970293AG2-193 GEN
Solar/Wind Harmer
2.77
316223AC1-118
Solar/Wind Harmer
0.53
3144536CHRHLND
Solar/Wind Harmer
-0.002
3142956BIRDNECK
Solar/Wind Harmer
0.746
944581AF1-123 GEN
Solar/Wind Harmer
62.481
316305AF2-043 C
Solar/Wind Harmer
0.413
316320Y1-086
Solar/Wind Harmer
0.783
3146516WINFALL
Solar/Wind Harmer
-0.013
315735AD1-075 GEN1
Solar/Wind Harmer
1.157
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316011AB1-132 GEN
Solar/Wind Harmer
2.037
944011AF1-069 GEN
Solar/Wind Harmer
5.689
961601AG1-000A GEN
Solar/Wind Harmer
3.304
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
957601AF2-054 GEN
Solar/Wind Harmer
0.755
3141813NORNECK
Solar/Wind Harmer
-0.023
3138283WHITEMARSH
Solar/Wind Harmer
0.034
3151191GRAVEL3
Adder
10.339
316018AA1-139 ULT2
Solar/Wind Harmer
1.166
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.572
315800Z1-036_GEN1
Solar/Wind Harmer
3.105
315732AD1-074 GEN1
Solar/Wind Harmer
2.315
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
0.093
3145513AHOSKIE
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.593
316426AA2-053 GEN
Solar/Wind Harmer
0.983
315652AC1-086 GEN
Solar/Wind Harmer
10.973
3137643SOCKMAN
Solar/Wind Harmer
-0.038
316233AE1-074 FULL
Solar/Wind Harmer
0.256
971283AH1-107 GEN
Solar/Wind Harmer
1.547
971967AH1-528 GEN
Solar/Wind Harmer
17.352
316327AA2-057 GEN
Solar/Wind Harmer
0.886
970085AG2-068 GEN
Solar/Wind Harmer
5.48
3144303KENBRDG
Solar/Wind Harmer
-0.005
3142433PROV 92
50/50
0.436
3142433PROV 92
50/50
0.436
3142433PROV 92
50/50
0.436
3141766HARMONY
Solar/Wind Harmer
2.414
3142946ENON
Solar/Wind Harmer
-0.009
961951AG1-038 GEN
Solar/Wind Harmer
3.195
3142416OLDCHRC
Solar/Wind Harmer
1.747
970133AG2-095 GEN
Solar/Wind Harmer
1.945
3145336SMITFLD
Solar/Wind Harmer
-0.006
316017AA1-139 ULT1
Solar/Wind Harmer
1.101
315813AE1-149 C
Solar/Wind Harmer
8.513
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.574
3145273HOLLAND
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.012
3146206CASHIE
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316181AB2-040 GEN
Solar/Wind Harmer
1.335
3147043LAWRENC
Solar/Wind Harmer
-0.005
316420AA1-050 GEN
Solar/Wind Harmer
1.002
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3138543CONSLDL
Solar/Wind Harmer
-0.006
316478AD1-087 GEN
Solar/Wind Harmer
0.669
959311AF2-222 GEN
Solar/Wind Harmer
6.917
316473AC1-191 GEN
Solar/Wind Harmer
0.686
3141843SHACKLE
50/50
1.243
3143096IRON208
50/50
0.701
3143096IRON208
50/50
0.687
3141873WAN 176
Solar/Wind Harmer
2.996
3141906WESTMOR
Solar/Wind Harmer
-0.008
316458AB2-190 GEN2
Solar/Wind Harmer
1.711
961611AG1-000B GEN
Solar/Wind Harmer
3.445
3151171GRAVELC
Adder
2.012
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.277
970657AG2-426 GEN
Solar/Wind Harmer
2.744
316321Z2-027
Solar/Wind Harmer
0.357
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3150861SPRUNCD
Adder
0.487
3156081AA2-088 GEN
Solar/Wind Harmer
3.625
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.12
3145933PARMELE
Solar/Wind Harmer
-0.01
970917AG2-570 GEN
Solar/Wind Harmer
22.229
3146233WITAKRS
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
2.508
971775AH1-396 GEN
Solar/Wind Harmer
0.472
315759AF1-018 GEN
50/50
8.583
3143873LANEXA
Solar/Wind Harmer
-0.016
3141873WAN 176
Solar/Wind Harmer
-0.005
3138133OCRAN
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.745
316159AE1-175 C
Solar/Wind Harmer
0.664
316236AE1-162_GEN
Solar/Wind Harmer
0.461
944491AF1-114 GEN
Solar/Wind Harmer
4.341
970657AG2-426 GEN
Solar/Wind Harmer
0.856
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.048
3130546PLYMOUTH
Solar/Wind Harmer
-0.012
315733AD1-074 GEN2
Solar/Wind Harmer
2.315
970601AG2-382 GEN
Solar/Wind Harmer
4.904
3146033SCOT NK
Solar/Wind Harmer
-0.039
970533AG2-339 GEN
Solar/Wind Harmer
6.512
946281AF1-292 GEN
Solar/Wind Harmer
0.215
971281AH1-106 GEN
Solar/Wind Harmer
1.547
970581AG2-369 GEN
Solar/Wind Harmer
4.713
3143096IRON208
50/50
0.701
3150771HOPHCF1
50/50
0.624
315662AE1-191 GEN
Solar/Wind Harmer
3.072
316280AD1-041 GEN
Solar/Wind Harmer
1.92
3138133OCRAN
Solar/Wind Harmer
-0.015
316404AE1-155 C
Solar/Wind Harmer
4.573
3138126ROCKLANDING
Solar/Wind Harmer
0.059
971069AG2-661 GEN
Solar/Wind Harmer
2.657
316369SG1_INVT
Solar/Wind Harmer
2.972
961611AG1-000B GEN
Solar/Wind Harmer
8.073
3151171GRAVELC
Adder
1.53
957971AF2-091 GEN
Solar/Wind Harmer
1.476
3150981CHESPKA
Adder
1.559
3142543TWELFTH
Solar/Wind Harmer
-0.001
316381AD1-082 GEN
Solar/Wind Harmer
1.243
319010AE1-072 C
Solar/Wind Harmer
2.742
315611Z1-036_GEN2
Solar/Wind Harmer
3.105
3130156CHOWAN
Solar/Wind Harmer
-0.012
315816AE2-034 GEN
Solar/Wind Harmer
0.963
971163AH1-040 GEN
Solar/Wind Harmer
11.192
315737AD1-076 GEN
Solar/Wind Harmer
2.176
3146293MARTNCO
Solar/Wind Harmer
0.06
316087AB2-174 GEN
Solar/Wind Harmer
1.366
970087AG2-069 GEN
Solar/Wind Harmer
8.22
3145493TOT1
Solar/Wind Harmer
0.257
3146233WITAKRS
Solar/Wind Harmer
-0.034
957481AF2-042 GEN
Solar/Wind Harmer
25.41
315693AD1-088 GEN
Solar/Wind Harmer
3.872
3143226MDLTHAN
Solar/Wind Harmer
-0.008
315785AD2-033 C
Solar/Wind Harmer
1.533
970685AG2-442 GEN
Solar/Wind Harmer
5.58
3141843SHACKLE
50/50
0.068
3150341NORNECKC1
50/50
2.316
3150341NORNECKC1
50/50
2.298
316487AF1-042 GEN
Solar/Wind Harmer
3.195
3150681DARBY 2
Adder
10.685
316033AB2-134 GEN
Solar/Wind Harmer
5.367
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
316339AD2-160 GEN
Solar/Wind Harmer
0.919
316388AE2-253 GEN
Solar/Wind Harmer
0.919
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.769
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
0.08
3145493TOT1
Solar/Wind Harmer
0.134
316049AB1-081 GEN
Solar/Wind Harmer
0.892
313527AB2-043 GEN
Solar/Wind Harmer
1.165
970323AG2-213 GEN
Solar/Wind Harmer
3.344
3150641CHESTS8
50/50
0.652
3141726DUNNSVL
Solar/Wind Harmer
-0.097
962861AG1-135 GEN
Solar/Wind Harmer
9.013
316337AD2-073 GEN
Solar/Wind Harmer
0.585
316132AB2-190 GEN1
Solar/Wind Harmer
1.711
316036AC1-147 C
Solar/Wind Harmer
0.377
315773AC2-141 GEN
Solar/Wind Harmer
5.752
316093AE2-104_GEN
Solar/Wind Harmer
3.929
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
3150851SPRUNCC
Adder
0.487
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
0.324
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.024
316494AC1-189 GEN
Solar/Wind Harmer
0.964
970919AG2-571 GEN
Solar/Wind Harmer
2.814
961671AG1-007 GEN
Solar/Wind Harmer
0.11
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3150351NORNECKC2
50/50
2.205
944631AF1-128 GEN
50/50
102.545
316314AB2-024 C
Solar/Wind Harmer
2.415
964211AG1-282 GEN
Solar/Wind Harmer
0.734
971317AH1-138 GEN
Solar/Wind Harmer
2.663
316072AD1-144
Solar/Wind Harmer
0.294
315671AE2-027_GEN
Solar/Wind Harmer
2.566
944591AF1-124 GEN
Solar/Wind Harmer
62.706
939411AE1-173 GEN
Solar/Wind Harmer
57.568
971547AH1-271 GEN
Solar/Wind Harmer
2.802
940641AE2-051 GEN
Solar/Wind Harmer
10.089
3145823KELFORD
Solar/Wind Harmer
-0.01
941031AE2-094 GEN
Solar/Wind Harmer
18.156
960081AF2-299 GEN
Solar/Wind Harmer
1.079
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
-0.009
3143526WINTERP
Solar/Wind Harmer
-0.049
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
0.725
971065AG2-659 GEN
Solar/Wind Harmer
4.091
970401AG2-262 GEN
Solar/Wind Harmer
0.437
316034AC1-036 C
Solar/Wind Harmer
0.124
3150621CHESTS7
50/50
0.591
3150791HOPHCF3
50/50
0.624
316441AF1-014 GEN
Solar/Wind Harmer
1.737
316312AB1-027
Solar/Wind Harmer
0.582
316185AD1-033 GEN
Solar/Wind Harmer
1.452
944641AF1-129 GEN
Adder
55.511
3144356SAPONY
Solar/Wind Harmer
0.379
316315AB2-025 C
Solar/Wind Harmer
0.293
962571AG1-106 GEN
Solar/Wind Harmer
1.402
3145796HORNRTN
Solar/Wind Harmer
-0.028
3142433PROV 92
50/50
0.436
3142433PROV 92
50/50
0.436
970603AG2-384 GEN
50/50
4.325
316059AD1-063 C
Solar/Wind Harmer
0.612
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3151201GRAVEL4
Adder
10.472
3151221GRAVEL6
Adder
10.46
3151211GRAVEL5
Adder
10.339
316311AC2-079 GEN
Solar/Wind Harmer
6.831
313526AB2-022
Solar/Wind Harmer
0.36
3146396TANGLEW
Solar/Wind Harmer
0.244
3146206CASHIE
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.272
315814AE2-033 C
Solar/Wind Harmer
10.089
961941AG1-037 GEN
Solar/Wind Harmer
0.08
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
316274AC1-208 GEN
Solar/Wind Harmer
0.989
316486AD2-202 GEN
Solar/Wind Harmer
0.196
3147173SINAI
Solar/Wind Harmer
-0.006
3147243WELCO
Solar/Wind Harmer
-0.004
3142433PROV 92
50/50
0.436
315975AC1-164 GENB
Solar/Wind Harmer
0.236
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.007
958261AF2-120 GEN
Solar/Wind Harmer
9.282
3142433PROV 92
Solar/Wind Harmer
-0.095
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
972135AH1-637 GEN
Solar/Wind Harmer
1.654
3145336SMITFLD
Solar/Wind Harmer
-0.061
316375AC2-012 GEN
Solar/Wind Harmer
4.851
3146456SLIGO L269
Solar/Wind Harmer
-0.014
3145663CRESWEL
Solar/Wind Harmer
-0.033
3146206CASHIE
Solar/Wind Harmer
-0.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.456
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
0.678
3147043LAWRENC
Adder
0.713
3146083TARBORO
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.472
316359AB2-059 GEN
Solar/Wind Harmer
1.114
3142053HEARTS
Solar/Wind Harmer
0.097
316131AB2-060 GEN
Solar/Wind Harmer
0.768
3150781HOPHCF2
50/50
0.624
315666AE1-190 GEN
Solar/Wind Harmer
0.768
316156AD2-030 GEN
Solar/Wind Harmer
0.672
3150671DARBY 1
Adder
10.672
3150991CHESPKB
Adder
1.308
3150991CHESPKB
Adder
1.276
315835AF2-110_GEN
Solar/Wind Harmer
1.689
316435W1029_GEN3
Solar/Wind Harmer
2.387
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
316240AF1-291 C
Solar/Wind Harmer
0.391
315614AA2-178 GEN
Solar/Wind Harmer
1.285
316065AD1-022 GEN
Solar/Wind Harmer
5.652
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
-0.02
316140AB2-099
Solar/Wind Harmer
0.072
316005AA1-067
Solar/Wind Harmer
0.188
972187AH1-678 GEN
Adder
2.345
3145453TOT5
Solar/Wind Harmer
0.08
961601AG1-000A GEN
Solar/Wind Harmer
3.262
971223AH1-071 GEN
Solar/Wind Harmer
0.952
964791AG1-342 GEN
Solar/Wind Harmer
1.431
316118AC1-105 GEN
Solar/Wind Harmer
0.447
966871AG1-558 GEN
Solar/Wind Harmer
0.192
966871AG1-558 GEN
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.904
3145783HORNRTN
Solar/Wind Harmer
0.282
3145783HORNRTN
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.687
315724AD1-057 GEN
Solar/Wind Harmer
1.732
3145603CNETO
Solar/Wind Harmer
0.054
316263AC1-034 GEN
Solar/Wind Harmer
3.884
970099AG2-077 GEN
Solar/Wind Harmer
10.164
315687AD1-152 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.216
962561AG1-105 GEN
Solar/Wind Harmer
3.808
316248AF1-058 C
Solar/Wind Harmer
0.191
3150691DARBY 3
50/50
11.377
3150701DARBY 4
50/50
11.351
315976AC1-164 GENA
Solar/Wind Harmer
7.975
316169AC1-164_GENC
Solar/Wind Harmer
6.89
3142946ENON
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
4.446
3142366NRTHEST
Adder
0.398
3146456SLIGO L269
Solar/Wind Harmer
1.606
316083AB2-161 GEN
Solar/Wind Harmer
2.204
316349AD2-085 GEN
Solar/Wind Harmer
1.202
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.387
316433W1029_GEN2
Solar/Wind Harmer
2.387
3146376EDENTON
Solar/Wind Harmer
0.37
3146376EDENTON
Solar/Wind Harmer
0.37
315742AE1-103 GEN
Solar/Wind Harmer
2.956
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
0.678
970933AG2-581 GEN
Solar/Wind Harmer
8.403
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
WECLTFEXP_WEC->PJM
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.267
NYPJM->LTFIMP_NY
CLTF
0.687
TVALTFEXP_TVA->PJM
CLTF
0.969
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.11
CPLELTFEXP_CPLE->PJM
CLTF
4.055
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.892
LGEELTFEXP_LGEE->PJM
CLTF
0.164
MECLTFEXP_MEC->PJM
CLTF
0.6

Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 208T287_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:284.0 MVA
Rating Type:C
MVA to Mitigate:308.09
MW Contribution:
4.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.19
315778AD1-151 GEN
Solar/Wind Harmer
6.055
3150631CHESTG8
50/50
1.171
3142433PROV 92
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
0.999
316458AB2-190 GEN2
Solar/Wind Harmer
0.761
971069AG2-661 GEN
Solar/Wind Harmer
1.077
3142543TWELFTH
Solar/Wind Helper
0.02
3150641CHESTS8
50/50
0.603
316132AB2-190 GEN1
Solar/Wind Harmer
0.761
944631AF1-128 GEN
50/50
94.827
315671AE2-027_GEN
Solar/Wind Helper
1.809
3150621CHESTS7
50/50
0.547
970603AG2-384 GEN
50/50
4
3142946ENON
Solar/Wind Harmer
-0.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.278
TVALTFEXP_TVA->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.003
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.074
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.076
MDUPJM->LTFIMP_MDU
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.164
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.076

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:602.71
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
315749AE2-041 GEN
50/50
4.941
3150921YORKTN3
50/50
1.926
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.043
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.388
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.345
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.941
972263AH1-716 GEN
50/50
32.803
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.598
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.865
971317AH1-138 GEN
Solar/Wind Harmer
0.613
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
3151221GRAVEL6
50/50
4.34
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.043
316156AD2-030 GEN
Solar/Wind Harmer
0.107
957191AF2-013 GEN
50/50
65.703
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
NYPJM->LTFIMP_NY
CLTF
0.57
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LGEELTFEXP_LGEE->PJM
CLTF
0.268
MECLTFEXP_MEC->PJM
CLTF
0.717
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
CPLELTFEXP_CPLE->PJM
CLTF
1.987
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.22 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:680.73
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.335
315749AE2-041 GEN
50/50
4.941
3150921YORKTN3
50/50
1.926
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.388
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.043
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.345
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151221GRAVEL6
Adder
4.09
3151211GRAVEL5
Adder
4.043
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.941
972263AH1-716 GEN
50/50
32.803
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.598
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.865
971317AH1-138 GEN
Solar/Wind Harmer
0.613
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
957191AF2-013 GEN
50/50
65.703
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316156AD2-030 GEN
Solar/Wind Harmer
0.107
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
NYPJM->LTFIMP_NY
CLTF
0.57
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LGEELTFEXP_LGEE->PJM
CLTF
0.268
MECLTFEXP_MEC->PJM
CLTF
0.717
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
CPLELTFEXP_CPLE->PJM
CLTF
1.987
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:577.77
MW Contribution:
1.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
316075AC2-137 C
Solar/Wind Harmer
0.018
3141316ARNOLDS
50/50
0.111
3150631CHESTG8
50/50
0.372
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
2.968
944631AF1-128 GEN
50/50
30.096
971317AH1-138 GEN
Solar/Wind Harmer
0.632
3150331BIRCHWDA
50/50
158.939
315749AE2-041 GEN
50/50
4.972
3150921YORKTN3
50/50
2
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.602
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
958261AF2-120 GEN
Solar/Wind Harmer
7.999
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3141813NORNECK
Solar/Wind Harmer
0.28
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.091
3150641CHESTS8
50/50
0.191
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3141766HARMONY
Solar/Wind Harmer
1.864
3142946ENON
Solar/Wind Harmer
0.022
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3151221GRAVEL6
Adder
4.139
3151211GRAVEL5
Adder
4.091
3141843SHACKLE
50/50
0.748
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3151171GRAVELC
Adder
0.796
315759AF1-018 GEN
50/50
4.972
972263AH1-716 GEN
50/50
35.581
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.052
3141873WAN 176
Solar/Wind Harmer
0.03
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.066
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.104
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3150621CHESTS7
50/50
0.174
957191AF2-013 GEN
50/50
65.957
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
NYPJM->LTFIMP_NY
CLTF
0.471
TVALTFEXP_TVA->PJM
CLTF
0.6
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
WECLTFEXP_WEC->PJM
CLTF
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
LGEELTFEXP_LGEE->PJM
CLTF
0.179
MECLTFEXP_MEC->PJM
CLTF
0.511
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
CPLELTFEXP_CPLE->PJM
CLTF
1.903
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:590.65
MW Contribution:
1.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.011
966661AG1-536 GEN
50/50
6.862
3144216WINCHST
50/50
0.281
3150611CHESTG7
50/50
0.403
316075AC2-137 C
Solar/Wind Harmer
0.019
3150631CHESTG8
50/50
0.397
3141913WHIT STONE
Solar/Wind Harmer
0.167
315697AD1-025 GEN
Solar/Wind Harmer
0.061
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.961
944631AF1-128 GEN
50/50
32.152
971317AH1-138 GEN
Solar/Wind Harmer
0.617
315749AE2-041 GEN
50/50
4.962
3150921YORKTN3
50/50
1.941
3151161SURRY 1
50/50
2.315
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.673
316223AC1-118
Solar/Wind Helper
2.155
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
958261AF2-120 GEN
Solar/Wind Harmer
7.977
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.28
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.084
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3141766HARMONY
Solar/Wind Harmer
1.861
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.559
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
970603AG2-384 GEN
50/50
1.356
3151201GRAVEL4
50/50
4.389
3151221GRAVEL6
50/50
4.384
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.084
3141843SHACKLE
50/50
0.748
3141873WAN 176
Solar/Wind Harmer
2.618
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.51
3141906WESTMOR
Solar/Wind Helper
0.564
315759AF1-018 GEN
50/50
4.962
972263AH1-716 GEN
50/50
33.131
3138133OCRAN
Solar/Wind Harmer
0.052
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.065
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.971
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
3141843SHACKLE
50/50
0.041
316033AB2-134 GEN
Solar/Wind Harmer
0
3150641CHESTS8
50/50
0.205
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.537
316337AD2-073 GEN
Solar/Wind Helper
2.352
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3150621CHESTS7
50/50
0.185
316312AB1-027
Solar/Wind Harmer
0.103
315976AC1-164 GENA
Solar/Wind Harmer
0.846
316169AC1-164_GENC
Solar/Wind Harmer
0.731
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.217
NYPJM->LTFIMP_NY
CLTF
0.542
TVALTFEXP_TVA->PJM
CLTF
0.785
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
WECLTFEXP_WEC->PJM
CLTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
1.553
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.363
LGEELTFEXP_LGEE->PJM
CLTF
0.298
MECLTFEXP_MEC->PJM
CLTF
0.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.493
CPLELTFEXP_CPLE->PJM
CLTF
2.035
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.15 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:578.11
MW Contribution:
1.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.01
966661AG1-536 GEN
50/50
6.86
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.403
316075AC2-137 C
Solar/Wind Harmer
0.019
3150631CHESTG8
50/50
0.397
3141913WHIT STONE
Solar/Wind Harmer
0.167
315697AD1-025 GEN
Solar/Wind Harmer
0.06
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.96
944631AF1-128 GEN
50/50
32.11
971317AH1-138 GEN
Solar/Wind Harmer
0.616
315749AE2-041 GEN
50/50
4.959
3150921YORKTN3
50/50
1.939
3151161SURRY 1
50/50
2.311
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.672
316223AC1-118
Solar/Wind Helper
2.155
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
958261AF2-120 GEN
Solar/Wind Harmer
7.975
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.28
970189AG2-124 GEN
Solar/Wind Harmer
4.091
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.078
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3141766HARMONY
Solar/Wind Harmer
1.86
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.558
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
970603AG2-384 GEN
50/50
1.354
3151201GRAVEL4
50/50
4.383
3151221GRAVEL6
50/50
4.378
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.078
3141843SHACKLE
50/50
0.748
3141873WAN 176
Solar/Wind Harmer
2.617
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3141906WESTMOR
Solar/Wind Helper
0.564
315759AF1-018 GEN
50/50
4.959
972263AH1-716 GEN
50/50
33.083
3138133OCRAN
Solar/Wind Harmer
0.052
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.065
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.966
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
3141843SHACKLE
50/50
0.041
316033AB2-134 GEN
Solar/Wind Harmer
0
3150641CHESTS8
50/50
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.534
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3150621CHESTS7
50/50
0.185
316312AB1-027
Solar/Wind Harmer
0.102
315976AC1-164 GENA
Solar/Wind Harmer
0.845
316169AC1-164_GENC
Solar/Wind Harmer
0.73
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.125
NYPJM->LTFIMP_NY
CLTF
0.546
TVALTFEXP_TVA->PJM
CLTF
0.778
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.685
WECLTFEXP_WEC->PJM
CLTF
0.148
LAGNLTFEXP_LAGN->PJM
CLTF
1.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.278
LGEELTFEXP_LGEE->PJM
CLTF
0.294
MECLTFEXP_MEC->PJM
CLTF
0.78
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.474
CPLELTFEXP_CPLE->PJM
CLTF
2.028
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:575.03
MW Contribution:
1.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.009
966661AG1-536 GEN
50/50
6.857
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.402
316075AC2-137 C
Solar/Wind Harmer
0.019
3150631CHESTG8
50/50
0.396
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.959
944631AF1-128 GEN
50/50
32.063
971317AH1-138 GEN
Solar/Wind Harmer
0.615
315749AE2-041 GEN
50/50
4.955
3150921YORKTN3
50/50
1.937
3151161SURRY 1
50/50
2.308
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.671
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
958261AF2-120 GEN
Solar/Wind Harmer
7.972
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.429
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.089
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.071
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.858
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.557
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.352
3151201GRAVEL4
50/50
4.375
3151221GRAVEL6
50/50
4.37
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.071
3141843SHACKLE
50/50
0.748
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.615
3151171GRAVELC
Adder
0.792
961611AG1-000B GEN
Solar/Wind Harmer
1.506
315759AF1-018 GEN
50/50
4.955
972263AH1-716 GEN
50/50
33.03
3138133OCRAN
Solar/Wind Harmer
0.052
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.065
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3151171GRAVELC
Adder
0.603
961611AG1-000B GEN
Solar/Wind Harmer
2.961
3150341NORNECKC1
50/50
3.108
3150341NORNECKC1
50/50
3.083
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.531
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3150621CHESTS7
50/50
0.185
316312AB1-027
Solar/Wind Harmer
0.102
315976AC1-164 GENA
Solar/Wind Harmer
0.844
316169AC1-164_GENC
Solar/Wind Harmer
0.729
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
NYPJM->LTFIMP_NY
CLTF
0.551
TVALTFEXP_TVA->PJM
CLTF
0.771
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.658
WECLTFEXP_WEC->PJM
CLTF
0.145
LAGNLTFEXP_LAGN->PJM
CLTF
1.526
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.182
LGEELTFEXP_LGEE->PJM
CLTF
0.289
MECLTFEXP_MEC->PJM
CLTF
0.768
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.452
CPLELTFEXP_CPLE->PJM
CLTF
2.02
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:598.97
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.874
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315749AE2-041 GEN
50/50
4.942
3150921YORKTN3
50/50
1.927
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.389
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.044
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.044
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.942
972263AH1-716 GEN
50/50
32.813
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.599
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
962861AG1-135 GEN
Solar/Wind Harmer
7.519
316156AD2-030 GEN
Solar/Wind Harmer
0.107
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
NYPJM->LTFIMP_NY
CLTF
0.569
TVALTFEXP_TVA->PJM
CLTF
0.742
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
LGEELTFEXP_LGEE->PJM
CLTF
0.269
MECLTFEXP_MEC->PJM
CLTF
0.719
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
CPLELTFEXP_CPLE->PJM
CLTF
1.988
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:631.64
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
316075AC2-137 C
Solar/Wind Harmer
0.019
3150631CHESTG8
50/50
0.394
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141426STAFORD
Solar/Wind Helper
0.031
315749AE2-041 GEN
50/50
4.942
3150921YORKTN3
50/50
1.927
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
972135AH1-637 GEN
Solar/Wind Harmer
4.389
958261AF2-120 GEN
Solar/Wind Harmer
7.959
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3141813NORNECK
Solar/Wind Harmer
0.279
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3138283WHITEMARSH
Solar/Wind Harmer
0.025
3151191GRAVEL3
Adder
4.044
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3141766HARMONY
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
0.023
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
970603AG2-384 GEN
50/50
1.344
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3151211GRAVEL5
Adder
4.044
3141843SHACKLE
50/50
0.745
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3151171GRAVELC
Adder
0.787
315759AF1-018 GEN
50/50
4.942
972263AH1-716 GEN
50/50
32.813
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.051
3141873WAN 176
Solar/Wind Harmer
0.029
3143873LANEXA
Solar/Wind Harmer
0.075
316159AE1-175 C
Solar/Wind Harmer
0.064
316404AE1-155 C
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.103
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
0.599
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150641CHESTS8
50/50
0.203
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3150351NORNECKC2
50/50
2.955
944631AF1-128 GEN
50/50
31.874
971317AH1-138 GEN
Solar/Wind Harmer
0.613
3150621CHESTS7
50/50
0.184
316312AB1-027
Solar/Wind Harmer
0.102
316156AD2-030 GEN
Solar/Wind Harmer
0.107
957191AF2-013 GEN
50/50
65.704
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
NYPJM->LTFIMP_NY
CLTF
0.569
TVALTFEXP_TVA->PJM
CLTF
0.742
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
WECLTFEXP_WEC->PJM
CLTF
0.134
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
LGEELTFEXP_LGEE->PJM
CLTF
0.269
MECLTFEXP_MEC->PJM
CLTF
0.719
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
CPLELTFEXP_CPLE->PJM
CLTF
1.988
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56702_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: G2T567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
 OPEN BRANCH FROM BUS 314924 TO BUS 315233 CKT 1   /*8SURRY       500.0 - 1SURRY 2      22.0
 OPEN BUS 315233                                   /*1SURRY 2      22.0
END
CONTINGENCY 'DVP_P4-2: 208T287_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314286 CKT 1   /*6CHCKAHM     230.0 - 6CHESTF A    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1   /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1   /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                   /*6IRON208     230.0
END
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314214 to 314903 ckt 1
314286 to 314284 ckt 1
314175 to 314132 ckt 1
314163 to 314137 ckt 1
314182 to 314183 ckt 1
314183 to 314190 ckt 1
314190 to 314139 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1

Winter Peak Analysis

The New Service Request AG2-384 was evaluated as a 60.82 MW (24.0 MW Capacity) injection in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.82 MW (60.82 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-384 was evaluated as a 60.82 MW injection and 60.0 MW withdrawal in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.82 MW (60.82 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-L
SingleAC100.62 %673.04B677.24
2.92
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: H2T557_SRT-L
BreakerAC122.36 %1212.0C1483.0
13.99
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-L
SingleAC100.56 %673.04B676.83
2.92
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-L
BreakerAC105.16 %4628.0C4866.67
17.69

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.62 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:677.24
MW Contribution:
2.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141906WESTMOR
Solar/Wind Harmer
0.423
3142433PROV 92
Solar/Wind Harmer
1.091
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150331BIRCHWDA
50/50
158.11
3150921YORKTN3
50/50
1.893
3138133OCRAN
Solar/Wind Harmer
0.263
3138133OCRAN
Solar/Wind Harmer
0.132
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3141766HARMONY
Solar/Wind Harmer
1.065
3141766HARMONY
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.281
3141783LANCAST
Solar/Wind Harmer
0.187
3141813NORNECK
Solar/Wind Harmer
0.717
3141913WHIT STONE
Solar/Wind Harmer
0.426
3143873LANEXA
Solar/Wind Harmer
0.191
3141726DUNNSVL
Solar/Wind Harmer
2.679
3141873WAN 176
Solar/Wind Harmer
1.5
3141873WAN 176
Solar/Wind Harmer
0.075
316404AE1-155 C
Solar/Wind Harmer
0
316203AE2-005 GEN
Solar/Wind Harmer
0
315749AE2-041 GEN
50/50
4.897
315759AF1-018 GEN
50/50
4.897
316337AD2-073 GEN
Solar/Wind Harmer
0
3138126ROCKLANDING
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.057
3142946ENON
Solar/Wind Harmer
0.017
944491AF1-114 GEN
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
50/50
31.233
962861AG1-135 GEN
Solar/Wind Harmer
7.23
966661AG1-536 GEN
50/50
15.967
970293AG2-193 GEN
Solar/Wind Harmer
0.632
970603AG2-384 GEN
50/50
2.92
971317AH1-138 GEN
Solar/Wind Harmer
0.833
957191AF2-013 GEN
50/50
65.591
958261AF2-120 GEN
Solar/Wind Harmer
7.656
971777AH1-397 GEN
Solar/Wind Harmer
1.381
972135AH1-637 GEN
Solar/Wind Harmer
4.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.257
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.52
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.892
NYPJM->LTFIMP_NY
CLTF
0.631
LGEELTFEXP_LGEE->PJM
CLTF
0.197
WECLTFEXP_WEC->PJM
CLTF
0.098
CPLELTFEXP_CPLE->PJM
CLTF
1.819
TVALTFEXP_TVA->PJM
CLTF
0.66
MECLTFEXP_MEC->PJM
CLTF
0.562
LAGNLTFEXP_LAGN->PJM
CLTF
1.27
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.397

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: H2T557_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.36 %
Rating:1212.0 MVA
Rating Type:C
MVA to Mitigate:1483.0
MW Contribution:
13.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142416OLDCHRC
Solar/Wind Harmer
2.929
3142416OLDCHRC
Solar/Wind Harmer
2.24
3142416OLDCHRC
Solar/Wind Harmer
0.858
3142433PROV 92
Solar/Wind Harmer
2.516
3142956BIRDNECK
Solar/Wind Harmer
0.84
3143316POE
Solar/Wind Harmer
2.184
3145506HICKORY
Solar/Wind Harmer
1.871
3145506HICKORY
Solar/Wind Harmer
1.123
3145506HICKORY
Solar/Wind Harmer
0.281
3138133OCRAN
Solar/Wind Harmer
0.331
3138133OCRAN
Solar/Wind Harmer
0.166
3138283WHITEMARSH
Solar/Wind Harmer
0.029
3141766HARMONY
Solar/Wind Harmer
1.739
3141766HARMONY
Solar/Wind Harmer
0.116
3141783LANCAST
Solar/Wind Harmer
0.328
3141783LANCAST
Solar/Wind Harmer
0.219
3141813NORNECK
Solar/Wind Harmer
0.5
3141913WHIT STONE
Solar/Wind Harmer
0.554
3143226MDLTHAN
Solar/Wind Harmer
0.525
3143873LANEXA
Solar/Wind Harmer
0.362
3141726DUNNSVL
Solar/Wind Harmer
2.055
3145336SMITFLD
Solar/Wind Harmer
2.062
3145336SMITFLD
Solar/Wind Harmer
0.206
3141873WAN 176
Solar/Wind Harmer
2.256
3141873WAN 176
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
3.172
3143526WINTERP
Solar/Wind Harmer
3.172
316404AE1-155 C
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0
3142543TWELFTH
Solar/Wind Harmer
0.069
316203AE2-005 GEN
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Harmer
-0.125
315671AE2-027_GEN
Solar/Wind Harmer
0
315813AE1-149 C
Solar/Wind Harmer
11.137
315697AD1-025 GEN
Solar/Wind Harmer
0
315778AD1-151 GEN
Solar/Wind Harmer
17.867
316375AC2-012 GEN
Solar/Wind Harmer
0
316311AC2-079 GEN
Solar/Wind Harmer
8.381
315975AC1-164 GENB
Solar/Wind Harmer
-0.22
315976AC1-164 GENA
Solar/Wind Harmer
-7.429
316169AC1-164_GENC
Solar/Wind Harmer
-6.418
316093AE2-104_GEN
Solar/Wind Harmer
4.597
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
0.067
3144536CHRHLND
Solar/Wind Harmer
0.073
3144873MCLAUGH
Solar/Wind Harmer
0.012
944591AF1-124 GEN
Solar/Wind Harmer
22.21
944631AF1-128 GEN
50/50
132.706
944641AF1-129 GEN
50/50
113.774
961611AG1-000B GEN
Solar/Wind Harmer
6.971
961611AG1-000B GEN
Solar/Wind Harmer
10.128
962861AG1-135 GEN
Solar/Wind Harmer
6.256
966871AG1-558 GEN
Solar/Wind Harmer
3.345
966871AG1-558 GEN
Solar/Wind Harmer
-0.715
970133AG2-095 GEN
Solar/Wind Harmer
2.303
970293AG2-193 GEN
Solar/Wind Harmer
3.041
970603AG2-384 GEN
50/50
13.994
970657AG2-426 GEN
Solar/Wind Harmer
2.957
970657AG2-426 GEN
Solar/Wind Harmer
3.143
971069AG2-661 GEN
Solar/Wind Harmer
10.268
971223AH1-071 GEN
Solar/Wind Harmer
2.102
971281AH1-106 GEN
Solar/Wind Harmer
3.172
971283AH1-107 GEN
Solar/Wind Harmer
3.172
971317AH1-138 GEN
Solar/Wind Harmer
2.167
971445AH1-216 GEN
Solar/Wind Harmer
7.429
971445AH1-216 GEN
Solar/Wind Harmer
10.246
958261AF2-120 GEN
Solar/Wind Harmer
6.43
971777AH1-397 GEN
Solar/Wind Harmer
2.283
971781AH1-399 GEN
Solar/Wind Harmer
1.407
970365AG2-240 GEN
Solar/Wind Harmer
3.244
972291SS25-0013
Solar/Wind Harmer
44.551
315835AF2-110_GEN
Solar/Wind Harmer
1.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.177
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.579
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.64
NYPJM->LTFIMP_NY
CLTF
1.429
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
6.164
TVALTFEXP_TVA->PJM
CLTF
1.188
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
MECLTFEXP_MEC->PJM
CLTF
0.149
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
2.289
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
17.005

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:676.83
MW Contribution:
2.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141906WESTMOR
Solar/Wind Harmer
0.423
3142433PROV 92
Solar/Wind Harmer
1.091
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150331BIRCHWDA
50/50
158.11
3150921YORKTN3
50/50
1.893
3138133OCRAN
Solar/Wind Harmer
0.263
3138133OCRAN
Solar/Wind Harmer
0.132
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3141766HARMONY
Solar/Wind Harmer
1.065
3141766HARMONY
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.281
3141783LANCAST
Solar/Wind Harmer
0.187
3141813NORNECK
Solar/Wind Harmer
0.717
3141913WHIT STONE
Solar/Wind Harmer
0.426
3143873LANEXA
Solar/Wind Harmer
0.191
3141726DUNNSVL
Solar/Wind Harmer
2.679
3141873WAN 176
Solar/Wind Harmer
1.5
3141873WAN 176
Solar/Wind Harmer
0.075
316404AE1-155 C
Solar/Wind Harmer
0
316203AE2-005 GEN
Solar/Wind Harmer
0
315749AE2-041 GEN
50/50
4.897
315759AF1-018 GEN
50/50
4.897
316337AD2-073 GEN
Solar/Wind Harmer
0
3138126ROCKLANDING
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.057
3142946ENON
Solar/Wind Harmer
0.017
944491AF1-114 GEN
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
50/50
31.233
962861AG1-135 GEN
Solar/Wind Harmer
7.23
966661AG1-536 GEN
50/50
15.967
970293AG2-193 GEN
Solar/Wind Harmer
0.632
970603AG2-384 GEN
50/50
2.92
971317AH1-138 GEN
Solar/Wind Harmer
0.833
957191AF2-013 GEN
50/50
65.591
958261AF2-120 GEN
Solar/Wind Harmer
7.656
971777AH1-397 GEN
Solar/Wind Harmer
1.381
972135AH1-637 GEN
Solar/Wind Harmer
4.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.257
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.52
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.892
NYPJM->LTFIMP_NY
CLTF
0.631
LGEELTFEXP_LGEE->PJM
CLTF
0.197
WECLTFEXP_WEC->PJM
CLTF
0.098
CPLELTFEXP_CPLE->PJM
CLTF
1.819
TVALTFEXP_TVA->PJM
CLTF
0.66
MECLTFEXP_MEC->PJM
CLTF
0.562
LAGNLTFEXP_LAGN->PJM
CLTF
1.27
SIGELTFEXP_SIGE->PJM
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.397

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.16 %
Rating:4628.0 MVA
Rating Type:C
MVA to Mitigate:4866.67
MW Contribution:
17.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20390526W1-045 C
Solar/Wind Helper
0.458
23546401DTGZ2-030
Solar/Wind Helper
0.319
20634528N27_Y2-018
Solar/Wind Helper
0.062
20641628MLH_W1-032
Solar/Wind Helper
0.09
20671828STAW2-080
Solar/Wind Helper
0.06
20671928W4-073
Solar/Wind Helper
0.236
20673628F1S_V4-069
Solar/Wind Helper
0.09
20673728F2S_V4-070
Solar/Wind Helper
0.09
20673828FLE_V3-070
Solar/Wind Helper
0.239
20674128FR_U2-059
Solar/Wind Helper
0.065
20674328GAR_V4-001
Solar/Wind Helper
0.059
20674528F3S_W2-016
Solar/Wind Helper
0.448
20674628WNG_W3-110
Solar/Wind Helper
0.222
20674828DL_W4-046
Solar/Wind Helper
0.255
20675128HRM_W1-127
Solar/Wind Helper
0.089
20675428EAM_W2-061
Solar/Wind Helper
0.083
20675528CPH_W2-050
Solar/Wind Helper
0.3
20675728RH_W2-091
Solar/Wind Helper
0.296
20675828AU_W4-064
Solar/Wind Helper
0.089
20675928HOL_W4-097
Solar/Wind Helper
0.089
20676128MHD_W3-029
Solar/Wind Helper
0.251
20676228FRD_X1-012
Solar/Wind Helper
0.296
20676328BVR_Y1-020
Solar/Wind Helper
0.147
20676428JCR_X2-075
Solar/Wind Helper
0.179
20676728BRNX1-095
Solar/Wind Helper
0.089
20714428HOW_X1-037
Solar/Wind Helper
0.444
20714528FRN_Y2-051
Solar/Wind Helper
0.151
20714828MDF_W3-079
Solar/Wind Helper
0.211
20714928UPF_X1-085
Solar/Wind Helper
0.151
20715028HAN_X4-015
Solar/Wind Helper
0.151
20715228NPK_W1-113
Solar/Wind Helper
0.217
20715728PEM_W1-119
Solar/Wind Helper
0.266
20715828PEM_W1-120
Solar/Wind Helper
0.266
20716028EGP_W2-019
Solar/Wind Helper
0.182
20716228APLW2-078
Solar/Wind Helper
0.295
20716428NHV_W2-082
Solar/Wind Helper
0.514
20716928W4-060COL
Solar/Wind Helper
0.3
20717128DIX_Z2-102
Solar/Wind Helper
0.393
20720428HOL_W1-112
Solar/Wind Helper
0.12
20720528MAN_W1-024
Solar/Wind Helper
0.114
20720628TIN_W1-124
Solar/Wind Helper
0.508
20720728JCB_W1-129
Solar/Wind Helper
0.151
20720828JCB_W4-025
Solar/Wind Helper
0.212
207408W3-077 C
Solar/Wind Helper
0.26
207439AE1-081 C O1
Solar/Wind Helper
0.037
214067T20SOLAR
Solar/Wind Helper
0.1
217206BARNGR HS C
Solar/Wind Helper
0.016
217208PARK ELE C
Solar/Wind Helper
0.013
217209CENTRL HS C
Solar/Wind Helper
0.023
217211CAMDEN ST C
Solar/Wind Helper
0.013
217213AMBOY SO C
Solar/Wind Helper
0.069
232404W1-003 C
Solar/Wind Helper
0.686
232408W1-005 C
Solar/Wind Helper
0.686
232410W1-006 C
Solar/Wind Helper
0.686
232417X3-008 C
Solar/Wind Helper
0.62
232426Y1-080 FULL
Solar/Wind Helper
0.105
232428Y3-058 C
Solar/Wind Helper
0.514
23777801MSM_W1-116
Solar/Wind Helper
0.522
23777901MDS_W4-102
Solar/Wind Helper
0.723
3142416OLDCHRC
Solar/Wind Harmer
2.931
3142416OLDCHRC
Solar/Wind Harmer
2.241
3142416OLDCHRC
Solar/Wind Harmer
0.859
3143316POE
Solar/Wind Harmer
3.363
209027LOR2_Q27
Solar/Wind Helper
2.145
212266LOR1
Solar/Wind Helper
0.586
217081WEATEXAS C
Solar/Wind Helper
0.042
217169METRODIV C
Solar/Wind Helper
0.018
217197RE CRAN C
Solar/Wind Helper
0.15
217201HACKENSOLA C
Solar/Wind Helper
0.03
217202FBANKSOLAR C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.071
218440SUMMTASSOC C
Solar/Wind Helper
0.06
218449LINSOLAR C
Solar/Wind Helper
0.259
218660EHAMPSOLAR C
Solar/Wind Helper
0.088
219114HARTZY_C
Solar/Wind Helper
0.242
219137THOSOLAR C
Solar/Wind Helper
0.265
219236SOUTHERNHQ C
Solar/Wind Helper
0.028
219249CENTRALDIV C
Solar/Wind Helper
0.022
219272CLEANLIGHT C
Solar/Wind Helper
0.085
219276PARKLANDSO C
Solar/Wind Helper
0.236
219287REEVESEAST C
Solar/Wind Helper
0.335
219291REEVESSOUT C
Solar/Wind Helper
0.03
219348LDSOLAR C
Solar/Wind Helper
0.304
219607WPEMNERT C
Solar/Wind Helper
0.213
219610FLORENCE C
Solar/Wind Helper
0.456
219612MATRIX C
Solar/Wind Helper
0.086
219615MILLCREEK C
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.021
219766PARADISE C
Solar/Wind Helper
0.155
219817TRENTONSOL C
Solar/Wind Helper
0.261
227927V4-067C
Solar/Wind Helper
0.079
228260V4-054C
Solar/Wind Helper
0.306
228711V2-041C
Solar/Wind Helper
0.135
235020AA1-095 C
Solar/Wind Helper
0.138
228728W1-130C
Solar/Wind Helper
0.281
228729W2-030 C
Solar/Wind Helper
0.293
3143226MDLTHAN
Solar/Wind Harmer
0.909
232406W1-004 FULL
Solar/Wind Helper
0.686
232436AB1-176 C
Solar/Wind Helper
0.124
217194REDH C
Solar/Wind Helper
0.149
316303AF2-085
50/50
6.269
223402AF1-300 C
Solar/Wind Helper
0.564
230415AB2-049 C
Solar/Wind Helper
0.092
20742028HF_AC1-207
Solar/Wind Helper
0.394
207454AA2-184 E
Solar/Wind Helper
0.602
207459AE1-142 C O1
Solar/Wind Helper
0.604
207471AF2-354 C
Solar/Wind Helper
0.326
208835TUHI V3-051
Solar/Wind Helper
0.038
208835TUHI V3-051
Solar/Wind Helper
0.038
208923BUSO V4-027
Solar/Wind Helper
0.179
232424Y1-079 C
Solar/Wind Helper
0.31
218524CNTRALGAS1 C
Solar/Wind Helper
0.26
218526CNTRALGAS2 C
Solar/Wind Helper
0.26
226910AB2-157 C
Solar/Wind Helper
0.092
233901CHERRYDALE C
Solar/Wind Helper
0.619
233940AF2-379 C
Solar/Wind Helper
0.121
212507AE2-042_GEN
Solar/Wind Helper
2.042
219727YARDVSOLFA C
Solar/Wind Helper
0.262
219907AC1-030 C
Solar/Wind Helper
0.076
237025AB1-124 C
Solar/Wind Helper
0.741
237030AB1-096 C
Solar/Wind Helper
0.303
237034AC2-136 C
Solar/Wind Helper
0.392
237038AE2-054 C
Solar/Wind Helper
0.637
3143526WINTERP
Solar/Wind Harmer
4.656
3143526WINTERP
Solar/Wind Harmer
4.656
316411AF1-147_GEN1
Solar/Wind Helper
2.056
316415AF1-147_GEN2
Solar/Wind Helper
2.056
316033AB2-134 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Helper
0.07
228351V2-046C
Solar/Wind Helper
0.608
235062AE1-101 C1
Solar/Wind Helper
2.375
205956AE1-196_GEN
Solar/Wind Helper
0.686
217204WCALDSOLAR C
Solar/Wind Helper
0.03
3142543TWELFTH
Solar/Wind Harmer
0.083
237080AD1-060 GEN
Solar/Wind Helper
0.482
235067AD1-061 GEN
Solar/Wind Helper
0.636
237001AB1-127_GEN
Solar/Wind Helper
0.64
237002AB1-128_GEN
Solar/Wind Helper
0.639
238175AF1-290_GEN
Solar/Wind Helper
2.52
238221AF1-254 C O1
Solar/Wind Helper
0.647
238169AE2-226 GEN1
Solar/Wind Helper
1.522
238170AE2-226 GEN2
Solar/Wind Helper
1.522
237085AD2-009_GEN
Solar/Wind Helper
2.203
233944AB2-135 GEN
Solar/Wind Helper
2.196
233946AB2-136 GEN
Solar/Wind Helper
1.753
233994AC2-023 GEN
Solar/Wind Helper
1.571
316312AB1-027
Solar/Wind Harmer
-0.126
315651AD1-115 GEN
Solar/Wind Helper
5.022
237061AD1-155 GEN
Solar/Wind Helper
2.251
237006AB1-125 GEN
Solar/Wind Helper
0.556
23779801AA1-109
Solar/Wind Helper
0.336
233982AB2-133 GEN
Solar/Wind Helper
1.915
233915AB1-141 GEN
Solar/Wind Helper
0.679
233918AB1-142 GEN
Solar/Wind Helper
0.679
315671AE2-027_GEN
Solar/Wind Harmer
0
233930AB2-032 GEN
Solar/Wind Helper
0.62
233987AB2-037 GEN
Solar/Wind Helper
6.26
315813AE1-149 C
Solar/Wind Harmer
16.907
315697AD1-025 GEN
Solar/Wind Harmer
0
233933AB2-153 GEN
Solar/Wind Helper
0.62
233955AB2-172 GEN
Solar/Wind Helper
1.715
315773AC2-141 GEN
Solar/Wind Harmer
0
233935AB2-179 C
Solar/Wind Helper
1.716
316447AC1-158 HLD
Solar/Wind Helper
16.928
316044AC1-158 PL1
Solar/Wind Helper
7.694
316045AC1-158 PL2
Solar/Wind Helper
24.623
316450AC1-158 RIC
Solar/Wind Helper
2.052
315778AD1-151 GEN
Solar/Wind Harmer
25.468
234015AF2-250 C
Solar/Wind Helper
0.067
234036AF2-325 C
Solar/Wind Helper
0.206
207484AF2-139 C O1
Solar/Wind Helper
0.26
207510AF2-138 C
Solar/Wind Helper
0.65
207518AF1-320_GEN
Solar/Wind Helper
2.291
207442AE1-156 GEN
Solar/Wind Helper
0.526
226929AD2-058 GEN
Solar/Wind Helper
0.207
207437AD2-070 GEN
Solar/Wind Helper
0.222
209054AE2-059 GEN
Solar/Wind Helper
0.628
207445AB1-138_GEN
Solar/Wind Helper
0.29
209071AE2-133 GEN
Solar/Wind Helper
0.627
209116AE2-175 GEN
Solar/Wind Helper
2.594
233923SMA
Solar/Wind Helper
2.01
230433AD2-135 GEN
Solar/Wind Helper
0.049
219680HOPEWELLV C1
Solar/Wind Helper
0.03
219686LUMSOLAR_N C
Solar/Wind Helper
0.103
219688LUMSOLAR_S C
Solar/Wind Helper
0.103
219908AB1-139 C
Solar/Wind Helper
0.197
219904AC1-010 C
Solar/Wind Helper
0.183
219906AC1-017 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.156
219258KINSLEYDEP C
Solar/Wind Helper
0.176
219304NAMERICA C
Solar/Wind Helper
0.213
219921AF1-264
Solar/Wind Helper
0.091
203975AE1-071-GEN
Solar/Wind Helper
3.281
211065PSPA IPP
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.292
207530AG1-191 GEN
Solar/Wind Helper
0.505
230511AF1-262
Solar/Wind Helper
0.068
205932AD2-116_GEN
Solar/Wind Helper
0.686
205941AD2-115 GEN
Solar/Wind Helper
0.664
205943AE1-185 GEN
Solar/Wind Helper
0.687
205917AD1-020 ES
Solar/Wind Helper
0.496
205916AD1-020 GEN
Solar/Wind Helper
2.308
316006AB2-029 C
Solar/Wind Helper
0.784
316164AC1-076 GEN
Solar/Wind Helper
3.287
316294AC1-161 GEN
Solar/Wind Harmer
-14.993
315975AC1-164 GENB
Solar/Wind Harmer
-0.283
315976AC1-164 GENA
Solar/Wind Harmer
-9.566
316169AC1-164_GENC
Solar/Wind Harmer
-8.264
230434AG1-499 GEN
Solar/Wind Helper
0.338
233964AF2-378 GEN
Solar/Wind Helper
0.077
207511W3-106 GEN
Solar/Wind Helper
0.147
208972BECR K09
Solar/Wind Helper
0.556
209029WAYMART-WD
Solar/Wind Helper
1.372
223401AF1-299 GEN
Solar/Wind Helper
0.564
230407AD2-065 C
Solar/Wind Helper
0.078
232432Z2-076 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.171
233996TM1833_GEN
Solar/Wind Helper
0.548
233997TMININ_4.2
Solar/Wind Helper
0.548
233998TM1NIN_3.36
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Harmer
0.285
3142946ENON
Solar/Wind Harmer
0.085
944631AF1-128 GEN
50/50
167.753
944641AF1-129 GEN
50/50
168.302
946691AF1-333 GEN
Solar/Wind Helper
0.628
946731AF1-337 GEN
Solar/Wind Helper
0.628
946741AF1-338 GEN
Solar/Wind Helper
0.628
946751AF1-339 GEN
Solar/Wind Helper
0.628
959381AF2-229 GEN
Solar/Wind Helper
0.678
959421AF2-233 GEN
Solar/Wind Helper
0.376
959431AF2-234 GEN
Solar/Wind Helper
0.752
959561AF2-247 GEN
Solar/Wind Helper
0.168
961261AF2-417 GEN
Solar/Wind Helper
0.636
961301AF2-421 GEN
Solar/Wind Helper
0.637
961331AF2-424 GEN
Solar/Wind Helper
0.632
961341AF2-425 GEN
Solar/Wind Helper
0.632
961421AF2-433 GEN
Solar/Wind Helper
0.631
961431AF2-434 GEN
Solar/Wind Helper
0.631
961611AG1-000B GEN
Solar/Wind Harmer
0.183
961611AG1-000B GEN
Solar/Wind Harmer
0.266
963151AG1-164 GEN
Solar/Wind Helper
0.637
963161AG1-165 GEN
Solar/Wind Helper
0.637
970119AG2-088 GEN
50/50
47.017
970133AG2-095 GEN
Solar/Wind Harmer
3.072
970293AG2-193 GEN
Solar/Wind Harmer
3.433
970603AG2-384 GEN
50/50
17.689
971069AG2-661 GEN
Solar/Wind Harmer
14.637
971223AH1-071 GEN
Solar/Wind Harmer
3.636
971281AH1-106 GEN
Solar/Wind Harmer
4.656
971283AH1-107 GEN
Solar/Wind Harmer
4.656
219918AC2-009 C
Solar/Wind Helper
0.01
227287AC2-120 GEN
Solar/Wind Helper
1.012
924131AB2-057 GEN
Solar/Wind Helper
0.332
939411AE1-173 GEN
Solar/Wind Harmer
136.244
940641AE2-051 GEN
Solar/Wind Harmer
25.678
957921AF2-086 GEN
Solar/Wind Helper
0.618
963711AG1-223 GEN
Solar/Wind Helper
0.514
964851AG1-348 GEN
Solar/Wind Helper
0.504
972263AH1-716 GEN
50/50
70.467
970365AG2-240 GEN
Solar/Wind Harmer
3.246
233950AC2-186 GEN
Solar/Wind Helper
0.31
233952AC2-187 GEN
Solar/Wind Helper
0.619
233954AC2-188 GEN
Solar/Wind Helper
0.619
238147AE2-230_GEN1
Solar/Wind Helper
1.032
238148AE2-230_GEN2
Solar/Wind Helper
1.032
238149AF1-291A_GEN
Solar/Wind Helper
0.295
238152AF2-075_GEN
Solar/Wind Helper
1.475
972287SS25-0012
Solar/Wind Harmer
44.57
972291SS25-0013
Solar/Wind Harmer
57.366
972293SS25-0014
50/50
Charging
189.987
232422X3-066 FULL
Solar/Wind Helper
0.186
219919AE1-041 FULL
Solar/Wind Helper
0.018
219912AD2-042 GEN
Solar/Wind Helper
0.402
219914AD2-027 C
Solar/Wind Helper
0.305
235063AE1-101 C2
Solar/Wind Helper
2.375
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
56.648
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.785
NYPJM->LTFIMP_NY
CLTF
5.235
LGEELTFEXP_LGEE->PJM
CLTF
1.705
WECLTFEXP_WEC->PJM
CLTF
0.84
CPLELTFEXP_CPLE->PJM
CLTF
15.623
TVALTFEXP_TVA->PJM
CLTF
5.757
MECLTFEXP_MEC->PJM
CLTF
4.854
LAGNLTFEXP_LAGN->PJM
CLTF
11.056
SIGELTFEXP_SIGE->PJM
CLTF
0.147
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
47.391
CONTINGENCY 'DVP_P1-2: LN 574_SRT-L'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 4708 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 4401 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-L'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-L'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3559 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3559 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
314132 to 314163 ckt 1
314218 to 314908 ckt 1
314163 to 314137 ckt 1
314918 to 314934 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2 (TC2) Cluster 12 are listed in Table 1 below. This report will cover the dynamic analysis of TC2 Cluster 12 projects.

 

Table 1: Transition Cycle 2 Cluster 12 Projects

 

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

12

AG2-088

Battery

Dominion

150

150

150

Midlothian 230 kV Substation

AG2-384

Battery

Dominion

60

60

24

Chesterfield ‘A’ 230 kV Substation

AH1-679

Natural Gas

Dominion

766

766

716

Four Rivers 230 kV Substation

 

The purpose of the transient stability analysis is to determine the system impact of the generation facility. This study will determine system improvements, if any, needed to reduce violations in the transient stability analysis caused by the addition of the projects in TC2 Cluster 12.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2028 summer peak and Light Load cases, modified to include applicable projects. TC2 Cluster 12 projects have been dispatched online at maximum real power output. The reactive power output for TC2 Cluster 12 projects was set to have near unity power factor measured at the high-side of the main substation transformer for the Summer Peak case. For the Light Load case, Dominion Energy’s Light Load Criteria was used to dispatch the TC2 Cluster 12 projects to near 50% of their minimum reactive limits. The Light Load Criteria could not be implemented for AH1-679 due to system constraints.

 

TC2 Cluster 12 projects were tested for compliance with NERC, PJM, Dominion Energy and other applicable criteria. 739 contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • No-fault steady-state operation
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with a stuck breaker
  • Single-phase faults placed at 80% of the line with delayed clearing at remote line end because of primary communications/relaying failure
  • Single-phase faults with loss of multiple circuit tower

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Dominion Energy’s transmission planning criteria:

 

  • TC2 Cluster 12 projects can ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with TC2 Cluster 12 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  • Following fault clearing, all bus voltages recover to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element should trip, other than those either directly connected or designed to trip as a consequence of that fault.

 

TC2 Cluster 12 projects met the above criteria with some facility modifications incorporated; these modifications are provided below. No mitigation is required to connect the TC2 Cluster 12 projects.

 

Facility modification and model tuning is recommended. The generator owner should provide their preferred adjustments for the issues described in the summary of results:

  • AG2-088
    • Plant tripped for the voltage protection model 1.1 p.u. at 2 seconds while the inverter was attempting to regulate grid voltage. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant reactive output appears to not settle within the 20 second simulation for some fault scenarios. A 4% voltage-reactive droop setting along with a +/- 0.001 p.u. deadband is recommended to enable the plant to settle quicker.
  • AG2-384
    • The main transformer high side tap had to be adjusted to 1.025 p.u. in order to pass the power factor requirements. It is requested that future data submittals include this tap adjustment.
  • AG2-583
    • Plant reactive output appears to not settle within the 20 second simulation for some fault scenarios. A 4% voltage-reactive droop setting is recommended to enable the plant to settle quicker.
  • AD1-151/AG2-661
    • Plant controllers froze and tripped for a P5 fault scenario. It is recommended that the AD1-151 REECA1 Vup parameter be adjusted from 1.15 p.u. to 1.20 p.u. and the AG2-661 REECC1 Vup parameter be adjusted from 1.12 p.u. to 1.20 p.u. These adjustments enable the units to ride through the specific fault scenario.
    • Within the PLNTBU1 model, Kp, Ki should be reduced from 2, 50 to 0.5, 3.0, respectively. A 4% voltage-reactive droop setting is recommended to help the plant coordinate voltage regulation with other sources.
  • AF2-110
    • Plant tripped for the voltage protection model 1.2 p.u. at 0.001 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
  • AE2-247
    • Plant tripped for the voltage protection model 1.2 p.u. at 0.017 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
  • AE1-157
    • Plant tripped for the frequency protection model 61.8 Hz at 0.0 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
  • AD2-074
    • Plant tripped for the frequency protection model 61.7 Hz at 0.001 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant tripped for the voltage protection model 1.2 p.u. at 0.001 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant controllers froze and tripped for a few fault scenarios. It is recommended that the REGCAU1 Iqrmax/Iqrmin values should be increased from +/- 0.02 p.u. to +/- 999 p.u. These adjustments enable the units to ride through the specific fault scenarios.
  • AD1-105
    • Plant tripped for the voltage protection model 1.2 p.u. at 0.001 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant tripped for the voltage protection model 1.175 p.u. at 0.2 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant tripped for the frequency protection model 61.7 Hz at 0.001 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant controllers froze and tripped for a few fault scenarios. It is recommended that the REECBU1 Vdip parameter be adjusted from 0.8 p.u. to 0.88 p.u. and the REPCA voltage reactive parameters Kp, Ki, Vfrz be adjusted from 0.01, 25, 0.7 to 4, 6, 0.88, respectively. These adjustments enable the unit to ride through the specific fault scenarios.
  • AD1-025
    • Plant reactive output appears to not settle within the 20 second simulation for some fault scenarios. A 4% voltage-reactive droop setting is recommended to enable the plant to settle quicker.
  • AC2-165
    • Plant tripped for the frequency protection model 61.8 Hz at 0.0 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
    • Plant tripped for the frequency protection model 57.8 Hz at 0.0 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.
  • AC1-158
    • Plant tripped for the voltage protection model 1.31 p.u. at 0.014 seconds. Please increase the tripping time to a reasonably high number considering equipment limitations.

 

Note:

  • PJM will contact the project developer to verify the model tuning recommendation for non-TC2 Cycle project.
  • TO has requested additional fault to be tested at Ladysmith CT substation, which will be evaluated during Phase 3 of the analysis.

Reactive Power Analysis

The AG2-384 facility met the 0.95 leading and 0.95 lagging power factor requirements at the main transformer high side.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-384 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionn9207.0Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).Contingent$0N/A
Dominionb4000.334Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.Contingent$0N/A
Dominionb4000.335At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards.Contingent$0N/A
Dominionb4000.336Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor.Contingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.10
Title
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Description
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.8
Title
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).
Description
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles). The new line will be constructed primarily of double-circuit 500 kV/230 kV monopole structures. The proposed route follows existing 230 kV line No. 2032 from Elmont-Hanover-Four Rivers and 230 kV line No. 256 from Four Rivers-Kings Dominion-St Johns-Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.9
Title
Construct one new 500 kV line terminal position at the existing Elmont substation.
Description
Construct one new 500 kV line terminal position at the existing Elmont substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: H2T557_SRT-S
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9207.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9207.0 / TC1-PH2-DOM-018
Title
Replace 6ELMONT 230 kV to 8ELMONT 500 kV circuit 1 with larger transformer (3-480 MVA single phase transformer).
Description
Replace 6ELMONT 230 KV to 8ELMONT 500 kV ckt 1 with Larger XFRM. (3-480 MVA Single Phase XFRM).
Total Cost ($USD)
$38,254,469
Discounted Total Cost ($USD)
$38,254,469
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2028

Contingent

Note: Based on PJM cost allocation criteria, AG2-384 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-384 may not have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
(All)A1707.0 MVA
(All)B1758.0 MVA
(All)C1873.0 MVA

System Reinforcement: b4000.334
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.334
Title
Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.
Description
Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.
Cost Information
Time Estimate
Jan 10 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.335
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.335
Title
At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards.
Description
At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards. The substation scope includes the installation of 230kV breaker and half GIS bus. Work at Poe subsation is associated with line #121 reconductor.
Cost Information
Time Estimate
Jan 10 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.336
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.336
Title
Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor.
Description
Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor. The substation scope includes the installation of 230kV breakers & 1-115kV breaker along with its associated terminal equipment initially but will have provision for making it a 6-breaker ring (both 230 & 115kV) in future. The existing 230-115kV transformer at Prince George will be relocated to serve this new substation.
Cost Information
Time Estimate
Jan 10 2030

ContingentTopology Changing

Note 1: Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
3CHESTFLD-6CHESTF A 115.0/230.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-384


AG2-384 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4000.334Reconductor 115kV line #121 from Poe - Prince George. Specifically, line #121 will be reconductored and converted to 230kV from Poe substation to Prince George substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.335At Poe substation, install a new 230kV six breaker ultimate ring bus which will fit the station to current 230kV standards.Topology-0.0%Contingent$0
Load FlowDominionb4000.336Build a new 230-115kV Prince George substation along the existing 115 or 230kV corridor.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-384 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-384 One Line Diagram

AG2-384 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.