AG2-405 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:24

Continental 69 kV

10.98 MW Capacity / 0.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Blue Harvest Solar Park LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 11.0 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Electric Power zone — Putnam County, Ohio. This project is an increase to the developer’s AD1-101 project(s), which will share the same Point of Interconnection. The AG2-405 project is a 10.98 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 49.9 MW with 29.94 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-405
Project Name:
Continental 69 kV
Project Developer Name:
Blue Harvest Solar Park LLC
State:
Ohio
County:
Putnam
Transmission Owner:
American Electric Power
MFO:
49.9
MWE:
0.0
MWC:
10.98
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AG2-405 will interconnect on the American Electric Power transmission system at the Continental 69kV Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-405 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-405Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-405

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-405
Project ID: AG2-405
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $43,920
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

No interconnections facilities required to support the interconnection.

(Pending Facilities Study)$0$0
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$0$0
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-405 was evaluated as a 0.0 MW (10.98 MW Capacity) injection in the AEP area.

AG2-405 was evaluated as part of a plant. The plant consists of AG2-405. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
1.91
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC101.22 %4142.0B4192.73
1.6
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
1.38
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
1.38

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
1.91
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
1.62
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
970155AG2-107 GEN
Solar/Wind Harmer
46.922
971995AH1-542 GEN
Solar/Wind Harmer
4.575
965421AG1-410 GEN
Solar/Wind Harmer
33.842
24639705ELKHART HY
Adder
0.237
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
3.072
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
274676JOLIET 29;8U
Adder
44.89
274871GR RIDGE ;2U
Solar/Wind Harmer
0
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970373AG2-245 GEN
Solar/Wind Harmer
22.382
943021AE2-325 GEN
Solar/Wind Harmer
5.553
971917AH1-482 GEN
Solar/Wind Harmer
13.746
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970819AG2-516 GEN
Solar/Wind Harmer
11.727
24721605FLATG1
50/50
3.319
961821AG1-024 GEN
Solar/Wind Harmer
9.821
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
959331AF2-224 GEN
Solar/Wind Harmer
7.844
965041AG1-368 GEN
Solar/Wind Harmer
11.063
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
971609AH1-304 GEN
Solar/Wind Harmer
1.657
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
957471AF2-041 GEN
Solar/Wind Harmer
29.515
970613AG2-401 GEN
Solar/Wind Harmer
7.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
5.071
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
957201AF2-014 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.403
970179AG2-119 GEN
Solar/Wind Harmer
9.709
963791AG1-232 GEN
Solar/Wind Harmer
14.514
958391AF2-133 GEN
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.956
274827FISK ;RP
Adder
11.436
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972227AH1-698 GEN1
Adder
3.84
274735ELWOOD EC;4P
Adder
24.024
274744AC1-111 GEN8
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
25306009OHH W.
Adder
4.15
970169AG2-114 GEN
Solar/Wind Harmer
9.859
959341AF2-225 GEN
Solar/Wind Harmer
10.156
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270120AB2-067 GEN2
50/50
17.244
274746AC1-111 G10
Adder
8.105
964611AG1-324 GEN
Solar/Wind Harmer
3.923
963841AG1-237 GEN
Solar/Wind Harmer
4.303
926823AC1-168 GEN
Solar/Wind Harmer
1.667
963741AG1-226 GEN
Solar/Wind Harmer
23.101
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
970773AG2-487 GEN
Solar/Wind Harmer
1.647
970091AG2-072 GEN
Adder
20.654
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.924
23750501ELLIOTTS
Solar/Wind Helper
0.6
238118U2-030_1
Solar/Wind Helper
0.267
965051AG1-369 GEN
Solar/Wind Harmer
5.558
970031AG2-029 GEN
Solar/Wind Harmer
5.889
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
972037AH1-567 GEN1
Adder
0.27
960591AF2-350 GEN
Solar/Wind Harmer
10.28
972228AH1-698 GEN2
Adder
5.454
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.4
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
972267AH1-718 GEN
Adder
5.748
942861AE2-305 GEN
Solar/Wind Harmer
10.655
970329AG2-216 GEN
Solar/Wind Harmer
5.083
247620Y3-023
Adder
0.71
965791AG1-447 GEN
Solar/Wind Harmer
9.845
25326109MON D
Adder
1.994
944541AF1-119 GEN
Solar/Wind Harmer
0.7
945421AF1-207 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.803
270031AE2-169
Solar/Wind Harmer
5.58
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274695ROCKY RD ;2P
Adder
16.014
958491AF2-143 GEN
Solar/Wind Harmer
14.984
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
12.96
274763LEE CO EC;4U
Adder
12.808
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
235054AD2-180 GEN
Solar/Wind Helper
1.576
235531U2-073 GEN
Solar/Wind Helper
2.548
962761AG1-125 GEN
Solar/Wind Harmer
73.48
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
962781AG1-127 GEN
Solar/Wind Harmer
9.482
274766LEE CO EC;7U
Adder
12.777
270437AC2-090 C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.34
965911AG1-460 GEN
Solar/Wind Harmer
1.103
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
253406AD2-031_GEN
Solar/Wind Harmer
0.684
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
203955AF1-039 C O1
Solar/Wind Helper
0.331
270054AF2-122 C O1
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
270247TR4_N_V136
Solar/Wind Harmer
0.071
970349AG2-230 GEN
Solar/Wind Harmer
16.464
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
960971AF2-388 GEN
Solar/Wind Harmer
6.145
944231AF1-091 GEN
Solar/Wind Harmer
24.097
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
7.391
274674JOLIET 9 ;6U
Adder
22.504
270599AE1-208 GEN
Solar/Wind Harmer
9.3
966841AG1-555 GEN
Solar/Wind Harmer
1.147
958481AF2-142 GEN
Solar/Wind Harmer
15.103
274693ROCKY RD ;1P
Adder
15.856
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.539
274764LEE CO EC;5U
Adder
12.96
926881AC1-175 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
25194408D.CRK1
Adder
9.313
23585401KL_K28_T16
Solar/Wind Helper
1.178
238117U2-030
Solar/Wind Helper
0.267
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
274752CRETE EC ;2U
Adder
12.279
970781AG2-491 GEN
Solar/Wind Harmer
10.354
270475AD2-096_GEN
50/50
14.072
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
971199AH1-059 GEN
Solar/Wind Harmer
2.255
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
12.279
24690905MDL-1G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274803UNIV PARK;6U
Adder
8.599
276843GEN-1.7
Solar/Wind Harmer
0.332
972038AH1-567 GEN2
Adder
0.538
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
270004AE1-209 GEN
Solar/Wind Harmer
2.149
274760LEE CO EC;1U
Adder
12.93
24379505HDWTR1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
965931AG1-462 GEN
Solar/Wind Harmer
23.963
23562501BACKB
Solar/Wind Helper
0.847
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
970707AG2-453 GEN
Solar/Wind Harmer
33.528
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
24.024
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.19
970193AG2-126 GEN
Solar/Wind Harmer
13.784
270541AE2-072 C
Solar/Wind Harmer
0.001
25196608WSDLE5
Adder
10.619
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
270166AC1-044 GEN3
50/50
17.244
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965011AG1-365 GEN
Solar/Wind Harmer
11.206
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274723RIVER EC ;12
Adder
26.668
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
970569AG2-363 GEN
Solar/Wind Harmer
29.408
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
276621W2-048 GEN
Solar/Wind Harmer
0.459
25196008MFTGT1
Adder
1.662
25196808ZIMRHP
Adder
90.149
238126S14_GEN_1
Solar/Wind Helper
0.635
270459AD2-067 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.43
270071AF1-092 GEN
Solar/Wind Harmer
21.261
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
10.756
24729505KEY G4
Adder
9.953
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
24.024
971549AH1-272 GEN
Solar/Wind Harmer
20.903
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.944
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
270119AB2-067 GEN1
50/50
17.244
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.96
942221AE2-234 GEN
Solar/Wind Harmer
4.232
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
274805UNIV PK N;1U
Adder
7.439
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
276893AG1-478 C
Solar/Wind Harmer
0.68
24387305FR-4G C
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
16.391
274697ROCKY RD ;3P
Adder
4.35
962691AG1-118 GEN
Solar/Wind Harmer
29.945
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274762LEE CO EC;3U
Adder
12.93
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
276838X2-022 GEN2
Solar/Wind Harmer
0.516
23751201ROTHROCK
Solar/Wind Helper
0.691
237043AE2-125 C
Solar/Wind Helper
0.16
270051AF1-062 GEN
50/50
23.559
246938BC-WTG3
Solar/Wind Harmer
0.406
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
274772LINCOLN ;3U
Adder
12.619
274724RIVER EC ;11
Adder
26.355
972259AH1-714 GEN
Adder
28.051
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
970825AG2-519 GEN
Solar/Wind Harmer
7.486
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
970571AG2-364 GEN
Solar/Wind Harmer
19.606
270240V3-007_GEN2
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.285
25196008MFTGT1
Adder
1.61
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
942481AE2-261 GEN
Solar/Wind Harmer
16.491
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
4.742
270246TR4_N_V150
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
13.426
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
276776AD2-060 GEN
Solar/Wind Harmer
1.097
971613AH1-306 GEN
Solar/Wind Harmer
4.9
253370AE2-315 SEC1
Adder
2.904
247621Y3-024
Adder
0.348
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
270284AF1-227 GEN1
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.934
270588AE1-091_GEN
Solar/Wind Harmer
8.236
247642Z2-115 C
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
276806AD2-047 C O1
Solar/Wind Harmer
5.825
274676JOLIET 29;8U
Adder
43.287
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
946031AF1-268 GEN
Solar/Wind Harmer
9.47
959091AF2-200 GEN
Solar/Wind Harmer
19.677
274767LEE CO EC;8U
Adder
12.777
971087AG2-675 GEN
Solar/Wind Harmer
5.012
24728505AND G1
Adder
5.071
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
964991AG1-363 GEN
Solar/Wind Helper
3.522
235058AG1-386 C
Solar/Wind Helper
0.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
NYPJM->LTFIMP_NY
CLTF
4.821
TVALTFEXP_TVA->PJM
CLTF
6.29
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
LGEELTFEXP_LGEE->PJM
CLTF
7.242
MECLTFEXP_MEC->PJM
CLTF
20.741
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
SIGELTFEXP_SIGE->PJM
CLTF
0.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
WECLTFEXP_WEC->PJM
CLTF
5.355
LAGNLTFEXP_LAGN->PJM
CLTF
14.301

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4192.73
MW Contribution:
1.6
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
53.025
270120AB2-067 GEN2
50/50
16.019
270160DARBY CT5
50/50
0.863
270466AD2-091
50/50
9.17
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
17.933
270462AD2-086
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.06
970349AG2-230 GEN
Solar/Wind Harmer
14.122
960971AF2-388 GEN
Solar/Wind Harmer
5.398
24697605MDL-3G C
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
18.232
961051AF2-396 GEN
Solar/Wind Harmer
12.155
274808UNIV PK N;4U
Adder
6.449
270599AE1-208 GEN
Solar/Wind Harmer
8.26
966841AG1-555 GEN
Solar/Wind Harmer
1.017
274674JOLIET 9 ;6U
Adder
19.719
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.912
958481AF2-142 GEN
Solar/Wind Harmer
13.279
944231AF1-091 GEN
Solar/Wind Harmer
20.375
274693ROCKY RD ;1P
Adder
13.949
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.132
274764LEE CO EC;5U
Adder
11.5
960611AF2-352 GEN
Solar/Wind Harmer
2.853
945391AF1-204 GEN
Solar/Wind Harmer
8.927
276615X2-022 GEN
Solar/Wind Harmer
0.086
25194408D.CRK1
Adder
8.951
23585401KL_K28_T16
Solar/Wind Helper
1.133
254305AE2-115 C
Solar/Wind Helper
0.19
270159DARBY CT4
50/50
0.866
961821AG1-024 GEN
Solar/Wind Harmer
8.348
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.762
241972AD1-140 GEN
Solar/Wind Harmer
1.127
270432AC2-029 GEN
Solar/Wind Harmer
4.567
959331AF2-224 GEN
Solar/Wind Harmer
6.656
965041AG1-368 GEN
Solar/Wind Harmer
9.38
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
10.998
971609AH1-304 GEN
Solar/Wind Harmer
1.472
964611AG1-324 GEN
Solar/Wind Harmer
3.496
274687WILL CNTY;4U
Adder
35.839
274687WILL CNTY;4U
Adder
35.839
274731ELWOOD EC;2P
Adder
21.052
274733ELWOOD EC;3P
Adder
21.052
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.889
274746AC1-111 G10
Adder
7.116
963841AG1-237 GEN
Solar/Wind Harmer
3.839
926823AC1-168 GEN
Solar/Wind Harmer
1.477
276726Z2-087_GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
23750501ELLIOTTS
Solar/Wind Helper
0.584
961921AG1-034 GEN
Solar/Wind Harmer
12.522
942051AE2-217 GEN
Solar/Wind Harmer
21.484
270166AC1-044 GEN3
50/50
16.019
965011AG1-365 GEN
Solar/Wind Harmer
9.509
246936BC-WTG1
Solar/Wind Harmer
0.382
270489AE1-102 GEN1
Solar/Wind Harmer
1.232
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.504
958861AF2-177 GEN
Solar/Wind Harmer
3.969
957891AF2-083 GEN
Solar/Wind Harmer
15.253
945111AF1-176 GEN
Solar/Wind Harmer
16.322
274773LINCOLN ;4U
Adder
10.998
274774LINCOLN ;5U
Adder
10.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.163
270032AE2-172
Solar/Wind Harmer
6.05
274751CRETE EC ;1U
Adder
10.696
274723RIVER EC ;12
Adder
23.243
24386605FR-22G C
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
3.16
270005AE1-210 C O1
Solar/Wind Harmer
1.926
270119AB2-067 GEN1
50/50
16.019
25326509SID D
50/50
1.973
246937BC-WTG2
Solar/Wind Harmer
0.382
247607V1-011 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.698
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
10.998
274771LINCOLN ;2U
Adder
10.998
970623AG2-406 GEN
Solar/Wind Harmer
1.654
274805UNIV PK N;1U
Adder
6.492
274888KELLY CRK;1U
Solar/Wind Harmer
0.524
970941AG2-585 GEN
Solar/Wind Harmer
4.944
276897AD1-100 C
Solar/Wind Harmer
22.435
24387305FR-4G C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.596
274696ROCKY RD ;4P
Adder
14.42
274697ROCKY RD ;3P
Adder
3.827
962691AG1-118 GEN
Solar/Wind Harmer
26.378
970241AG2-163 GEN
Solar/Wind Harmer
5.107
970621AG2-405 GEN
Solar/Wind Harmer
1.602
938861AE1-114 GEN
Solar/Wind Harmer
4.886
942111AE2-223 GEN
Solar/Wind Harmer
2.802
274762LEE CO EC;3U
Adder
11.473
276645AC1-214 GEN1
Solar/Wind Harmer
0.337
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.382
276838X2-022 GEN2
Solar/Wind Harmer
0.468
237043AE2-125 C
Solar/Wind Helper
0.16
962101AG1-054 GEN
Solar/Wind Helper
0.562
23751201ROTHROCK
Solar/Wind Helper
0.651
270475AD2-096_GEN
50/50
11.402
270161DARBY CT6
50/50
0.851
25326109MON D
50/50
1.91
942861AE2-305 GEN
Solar/Wind Harmer
9.172
970329AG2-216 GEN
Solar/Wind Harmer
4.378
270269AC2-059
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
8.487
247620Y3-023
Adder
0.608
944541AF1-119 GEN
Solar/Wind Harmer
0.615
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270051AF1-062 GEN
50/50
19.835
270031AE2-169
Solar/Wind Harmer
4.956
958011AF2-095 GEN
Solar/Wind Harmer
12.944
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.672
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.971
274695ROCKY RD ;2P
Adder
14.087
270383AD1-128 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.202
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.723
274765LEE CO EC;6U
Adder
11.5
274763LEE CO EC;4U
Adder
11.365
25194508D.CRK3
Adder
1.673
25183208HLCRTG
Solar/Wind Harmer
0.001
254304AE2-114 C
Solar/Wind Helper
0.19
235054AD2-180 GEN
Solar/Wind Helper
1.517
970149AG2-104 GEN
Solar/Wind Harmer
28.634
970373AG2-245 GEN
Solar/Wind Harmer
19.415
971917AH1-482 GEN
Solar/Wind Harmer
11.985
943021AE2-325 GEN
Solar/Wind Harmer
4.749
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.439
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.024
274872LEEDK;1U
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.72
959081AF2-199 GEN
Solar/Wind Harmer
8.698
971067AG2-660 GEN
Solar/Wind Harmer
2.899
274822ROCKFORD ;11
Adder
24.417
970819AG2-516 GEN
Solar/Wind Harmer
10.384
965021AG1-366 GEN
Solar/Wind Harmer
3.17
270043AE2-236 GEN
Solar/Wind Harmer
6.088
246938BC-WTG3
Solar/Wind Harmer
0.341
270505AE1-170 C O1
Solar/Wind Harmer
9.607
945111AF1-176 GEN
Solar/Wind Harmer
7.414
274772LINCOLN ;3U
Adder
10.998
274724RIVER EC ;11
Adder
22.971
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.47
972259AH1-714 GEN
Adder
24.546
274729ELWOOD EC;1P
Adder
21.052
970825AG2-519 GEN
Solar/Wind Harmer
6.707
253394AE2-221_GEN
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0
946671AF1-331 GEN
Solar/Wind Harmer
0.931
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
970571AG2-364 GEN
Solar/Wind Harmer
17.364
971993AH1-541 GEN
Solar/Wind Harmer
3.869
970065AG2-057 GEN
Solar/Wind Harmer
0.833
25196008MFTGT1
Adder
1.556
237048AF1-022 C
Solar/Wind Helper
0.17
237046AF1-021 C
Solar/Wind Helper
0.301
942481AE2-261 GEN
Solar/Wind Harmer
2.388
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.604
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.046
939741AE1-205 GEN
Solar/Wind Harmer
12.07
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.473
276621W2-048 GEN
Solar/Wind Harmer
0.416
252510AF1-249 C
Solar/Wind Harmer
0.062
25196808ZIMRHP
Adder
87.807
25196008MFTGT1
Adder
1.606
254303AC2-168 GEN
Solar/Wind Helper
0.138
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.337
970773AG2-487 GEN
Solar/Wind Harmer
1.513
970091AG2-072 GEN
Adder
14.929
270518AE2-148 GEN
Solar/Wind Harmer
0.922
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270491AE1-102 GEN2
Solar/Wind Harmer
1.232
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970191AG2-125 GEN
Solar/Wind Harmer
2.366
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
10.696
274814UNIV PK N;0U
Adder
6.534
274807UNIV PK N;3U
Adder
6.52
971199AH1-059 GEN
Solar/Wind Harmer
1.894
274803UNIV PARK;6U
Adder
7.515
276843GEN-1.7
Solar/Wind Harmer
0.291
972038AH1-567 GEN2
Adder
0.47
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.926
24379505HDWTR1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.473
274878BISHOP HL;2U
Solar/Wind Harmer
0.286
965091AG1-374 GEN
Solar/Wind Harmer
25.673
965931AG1-462 GEN
Solar/Wind Harmer
21.435
270391AF1-285 GEN3
Solar/Wind Harmer
0.762
971347AH1-153 GEN
Solar/Wind Harmer
4.707
944531AF1-118 GEN
Solar/Wind Harmer
42.014
270063AE2-323 C
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.119
274752CRETE EC ;2U
Adder
10.696
274887GEN-1.85
Solar/Wind Harmer
0.234
274826FISK ;BP
Adder
14.105
970707AG2-453 GEN
Solar/Wind Harmer
29.335
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.052
274862TOP CROP ;2U
Solar/Wind Harmer
1.195
276868AE1-113 GEN
Solar/Wind Harmer
1.756
274879MINONK ;1U
Solar/Wind Harmer
0.366
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.853
970193AG2-126 GEN
Solar/Wind Harmer
12.603
25196608WSDLE5
Adder
10.184
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270273AD2-016 GEN
Solar/Wind Harmer
0.99
25326309TAIT D
Adder
1.47
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
10.696
274802UNIV PARK;5U
Adder
7.515
276903AD2-071 C
Solar/Wind Harmer
10.022
24385905FR-11G C
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
21.052
274674JOLIET 9 ;6U
Adder
19.719
939401AE1-172 GEN
Solar/Wind Harmer
6.617
962781AG1-127 GEN
Solar/Wind Harmer
8.357
270437AC2-090 C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
11.338
276708O09 GEN2
Solar/Wind Harmer
0.302
241813AF1-122_GEN
Solar/Wind Harmer
3.73
971201AH1-060 GEN
Solar/Wind Harmer
1.665
965911AG1-460 GEN
Solar/Wind Harmer
0.16
970155AG2-107 GEN
Solar/Wind Harmer
33.86
971995AH1-542 GEN
Solar/Wind Harmer
3.792
965421AG1-410 GEN
Solar/Wind Harmer
28.445
253370AE2-315 SEC1
Adder
2.657
253371AE2-315 SEC2
Adder
2.513
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.203
965651AG1-433 GEN
Solar/Wind Harmer
2.699
270024AE2-089 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
274812UNIV PK N;8U
Adder
6.477
274676JOLIET 29;8U
Adder
39.32
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.116
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.722
274828WAUKEGAN ;BP
Adder
13.956
970613AG2-401 GEN
Solar/Wind Harmer
6.435
957471AF2-041 GEN
Solar/Wind Harmer
26.094
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.607
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
4.655
25194608D.CRK4
Adder
1.946
252516AE2-318_GEN
Solar/Wind Harmer
9.213
238185AF2-356 C
Solar/Wind Helper
1.967
241966AE1-183 GEN
Solar/Wind Helper
0.22
962771AG1-126 GEN
Solar/Wind Harmer
53.025
970153AG2-106 GEN
Solar/Wind Harmer
33.86
270284AF1-227 GEN1
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.79
253370AE2-315 SEC1
Adder
2.657
253371AE2-315 SEC2
Adder
2.513
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.004
274811UNIV PK N;7U
Adder
6.477
270158DARBY CT3
50/50
0.864
270036AE2-216 BAT
50/50
10.087
965051AG1-369 GEN
Solar/Wind Harmer
4.708
970031AG2-029 GEN
Solar/Wind Harmer
5.031
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.479
274775LINCOLN ;6U
Adder
10.998
274777LINCOLN ;8U
Adder
10.998
945581AF1-223 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.236
960591AF2-350 GEN
Solar/Wind Harmer
8.989
972228AH1-698 GEN2
Adder
4.77
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.358
274675JOLIET 29;7U
Adder
39.32
274675JOLIET 29;7U
Adder
37.916
970833AG2-524 GEN
Solar/Wind Harmer
9.819
970833AG2-524 GEN
Solar/Wind Harmer
6.546
971029AG2-637 GEN
Solar/Wind Harmer
13.318
253406AD2-031_GEN
Solar/Wind Harmer
0.648
971675AH1-338 GEN
Solar/Wind Harmer
3.404
971411AH1-196 GEN
Solar/Wind Harmer
13.089
971171AH1-044 GEN
Solar/Wind Harmer
17.396
274823ROCKFORD ;21
Adder
24.24
972267AH1-718 GEN
Adder
5.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
3.219
946321AF1-296 GEN
Solar/Wind Harmer
4.721
23652301WDPWR_K20
Solar/Wind Helper
0.128
23750701CROSSCHOOL
Solar/Wind Helper
1.083
270156DARBY CT1
50/50
0.88
270157DARBY CT2
50/50
0.878
270459AD2-067 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
18.287
270435AC2-044 GEN
Solar/Wind Harmer
1.201
24729505KEY G4
Adder
8.674
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
9.227
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
21.052
270543AE2-219 C
Solar/Wind Harmer
6.239
970073AG2-061 GEN
Solar/Wind Harmer
2.934
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.885
971549AH1-272 GEN
Solar/Wind Harmer
17.758
25196408WSDLE3
Adder
10.483
25196108MFTGT2
Adder
1.771
25196108MFTGT2
Adder
1.644
276806AD2-047 C O1
Solar/Wind Harmer
5.094
274676JOLIET 29;8U
Adder
37.916
274734ELWOOD EC;8P
Adder
21.052
274736ELWOOD EC;9P
Adder
21.052
946031AF1-268 GEN
Solar/Wind Harmer
8.48
943121AE2-341 GEN
Solar/Wind Harmer
14.899
943591AF1-030 GEN
Solar/Wind Harmer
9.908
274682WAUKEGAN ;7U
Adder
22.722
270588AE1-091_GEN
Solar/Wind Harmer
6.834
959091AF2-200 GEN
Solar/Wind Harmer
17.396
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.189
274767LEE CO EC;8U
Adder
11.338
24728505AND G1
Adder
4.655
971087AG2-675 GEN
Solar/Wind Harmer
4.483
25194608D.CRK4
Adder
1.946
252519AF1-045_GEN
Solar/Wind Harmer
4.291
957381AF2-032 GEN
Solar/Wind Harmer
1.857
235058AG1-386 C
Solar/Wind Helper
0.41
964991AG1-363 GEN
Solar/Wind Helper
3.439
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
3.962
270246TR4_N_V150
Solar/Wind Harmer
0.06
25322209TAIT E
Adder
13.082
25322209TAIT E
Adder
12.788
965681AG1-436 GEN
Solar/Wind Harmer
11.573
253370AE2-315 SEC1
Adder
2.657
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.187
970291AG2-192 GEN
Solar/Wind Harmer
0.548
971613AH1-306 GEN
Solar/Wind Harmer
4.356
276776AD2-060 GEN
Solar/Wind Harmer
0.959
247621Y3-024
Adder
0.31
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
17.396
971343AH1-151 GEN
Solar/Wind Harmer
17.396
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
4.527
943851AF1-053 GEN
Solar/Wind Harmer
3.136
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.548
957201AF2-014 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.342
963791AG1-232 GEN
Solar/Wind Harmer
12.53
253372AE2-315 SEC3
Adder
2.513
253372AE2-315 SEC3
Adder
2.513
958391AF2-133 GEN
Solar/Wind Harmer
0.001
25306009OHH W.
Adder
3.797
970289AG2-191 GEN
Solar/Wind Harmer
1.735
274827FISK ;RP
Adder
9.996
274800UNIV PARK;3U
Adder
7.508
274801UNIV PARK;4U
Adder
7.508
972227AH1-698 GEN1
Adder
3.359
970179AG2-119 GEN
Solar/Wind Harmer
8.005
274735ELWOOD EC;4P
Adder
21.052
274744AC1-111 GEN8
Adder
7.116
970169AG2-114 GEN
Solar/Wind Harmer
8.734
959341AF2-225 GEN
Solar/Wind Harmer
9.052
276741O09 GEN1
Solar/Wind Harmer
0.302
274877BISHOP HL;1U
Solar/Wind Harmer
0.286
276668AB2-070 GEN1
Solar/Wind Harmer
0.329
276848AB2-070 GEN3
Solar/Wind Harmer
0.328
276849AB2-070 GEN2
Solar/Wind Harmer
0.329
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.047
WECLTFEXP_WEC->PJM
CLTF
4.742
LAGNLTFEXP_LAGN->PJM
CLTF
15.297
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.659
CPLELTFEXP_CPLE->PJM
CLTF
0.407
SIGELTFEXP_SIGE->PJM
CLTF
0.561
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.622
LGEELTFEXP_LGEE->PJM
CLTF
7.229
MECLTFEXP_MEC->PJM
CLTF
18.973
AH1-155LTFEXP_AH1-155->PJM
LTF
0.45
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.339
NYPJM->LTFIMP_NY
CLTF
4.811
TVALTFEXP_TVA->PJM
CLTF
7.122
AG2-052LTFEXP_AG2-052->PJM
LTF
0.3

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
1.38
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
11.974
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
23.325
944531AF1-118 GEN
Solar/Wind Harmer
44.295
970781AG2-491 GEN
Solar/Wind Harmer
9.86
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
24344105CKG2
50/50
12.076
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970373AG2-245 GEN
Solar/Wind Harmer
21.825
943021AE2-325 GEN
Solar/Wind Harmer
5.398
971917AH1-482 GEN
Solar/Wind Harmer
13.304
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
962761AG1-125 GEN
Solar/Wind Harmer
93.339
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
11.974
274802UNIV PARK;5U
Adder
8.371
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
939401AE1-172 GEN
Solar/Wind Harmer
7.225
962781AG1-127 GEN
Solar/Wind Harmer
9.154
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
276708O09 GEN2
Solar/Wind Harmer
0.324
276903AD2-071 C
Solar/Wind Harmer
9.571
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270437AC2-090 C
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
11.253
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
21.176
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
270102X2-052 ST
50/50
2.435
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.401
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
274808UNIV PK N;4U
Adder
7.201
274674JOLIET 9 ;6U
Adder
21.855
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274693ROCKY RD ;1P
Adder
15.339
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.399
270247TR4_N_V136
Solar/Wind Harmer
0.06
274764LEE CO EC;5U
Adder
12.402
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
5.429
960611AF2-352 GEN
Solar/Wind Harmer
2.992
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
8.566
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
270054AF2-122 C O1
Solar/Wind Helper
1.203
270143AC1-141 CT2_
50/50
3.606
270101X2-052 CT2
50/50
2.25
247620Y3-023
50/50
0.727
965791AG1-447 GEN
Solar/Wind Harmer
9.691
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.407
270180AB1-006 GEN1
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
15.492
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.955
274765LEE CO EC;6U
Adder
12.402
274763LEE CO EC;4U
Adder
12.256
944541AF1-119 GEN
Solar/Wind Harmer
0.618
270031AE2-169
Solar/Wind Harmer
4.725
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276911AD2-131_GEN
Solar/Wind Harmer
1.118
270144AC1-141 ST1_
50/50
3.196
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.383
959331AF2-224 GEN
Solar/Wind Harmer
7.14
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
7.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
965041AG1-368 GEN
Solar/Wind Harmer
9.581
926823AC1-168 GEN
Solar/Wind Harmer
1.594
963841AG1-237 GEN
Solar/Wind Harmer
3.99
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
270356AE2-297 GEN
Solar/Wind Harmer
0
24344005CKG1
50/50
9.721
24641605TWIN BRNCH
50/50
0.026
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
960591AF2-350 GEN
Solar/Wind Harmer
10.005
972228AH1-698 GEN2
Adder
5.307
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
965051AG1-369 GEN
Solar/Wind Harmer
4.689
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.992
970193AG2-126 GEN
Solar/Wind Harmer
12.093
270541AE2-072 C
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
9.997
24642205MAYFLWER
50/50
0.055
962601AG1-109 GEN
50/50
4.308
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
11.974
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274803UNIV PARK;6U
Adder
8.371
276843GEN-1.7
Solar/Wind Harmer
0.323
972038AH1-567 GEN2
Adder
0.523
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
965091AG1-374 GEN
Solar/Wind Harmer
26.927
965931AG1-462 GEN
Solar/Wind Harmer
22.694
270004AE1-209 GEN
Solar/Wind Harmer
1.763
24379505HDWTR1G C
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
2.25
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
24307105BERRINSP G
50/50
0.032
957891AF2-083 GEN
Solar/Wind Harmer
17.358
945111AF1-176 GEN
Solar/Wind Harmer
18.541
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24386605FR-22G C
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
939741AE1-205 GEN
Solar/Wind Harmer
12.763
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.421
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
276893AG1-478 C
Solar/Wind Harmer
0.66
274696ROCKY RD ;4P
Adder
15.857
274697ROCKY RD ;3P
Adder
4.208
962691AG1-118 GEN
Solar/Wind Harmer
28.923
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274762LEE CO EC;3U
Adder
12.373
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970241AG2-163 GEN
Solar/Wind Harmer
5.219
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
276838X2-022 GEN2
Solar/Wind Harmer
0.473
970621AG2-405 GEN
Solar/Wind Harmer
1.383
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
971771AH1-392 GEN
Solar/Wind Harmer
10.525
274728ELWOOD EC;5P
Adder
23.325
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
9.035
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270435AC2-044 GEN
Solar/Wind Harmer
1.153
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.183
270142AC1-141 CT1_
50/50
3.606
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
274811UNIV PK N;7U
Adder
7.232
276806AD2-047 C O1
Solar/Wind Harmer
5.669
274676JOLIET 29;8U
Adder
42.062
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274682WAUKEGAN ;7U
Adder
24.977
959091AF2-200 GEN
Solar/Wind Harmer
18.917
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
970289AG2-191 GEN
Solar/Wind Harmer
0.995
971087AG2-675 GEN
Solar/Wind Harmer
4.746
957381AF2-032 GEN
Solar/Wind Harmer
1.851
946031AF1-268 GEN
Solar/Wind Harmer
7.675
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
13.215
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276776AD2-060 GEN
Solar/Wind Harmer
1.067
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
270246TR4_N_V150
Solar/Wind Harmer
0.06
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
971613AH1-306 GEN
Solar/Wind Harmer
4.231
276916AD2-100_GEN
Solar/Wind Harmer
16.976
247621Y3-024
Adder
0.274
971587AH1-292 GEN
Solar/Wind Harmer
5.199
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
970155AG2-107 GEN
Solar/Wind Harmer
59.604
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.232
274676JOLIET 29;8U
Adder
43.62
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
957471AF2-041 GEN
Solar/Wind Harmer
28.375
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
23906502RICHG2&3
Adder
1.056
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.468
944961AF1-161 GEN
50/50
4.308
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274724RIVER EC ;11
Adder
25.717
972259AH1-714 GEN
Adder
27.313
274729ELWOOD EC;1P
Adder
23.324
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
970571AG2-364 GEN
Solar/Wind Harmer
18.75
246938BC-WTG3
Solar/Wind Harmer
0.328
971993AH1-541 GEN
Solar/Wind Harmer
3.947
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
970825AG2-519 GEN
Solar/Wind Harmer
6.118
270240V3-007_GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.002
274827FISK ;RP
Adder
11.133
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972227AH1-698 GEN1
Adder
3.737
274735ELWOOD EC;4P
Adder
23.324
274744AC1-111 GEN8
Adder
7.861
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
963791AG1-232 GEN
Solar/Wind Harmer
12.673
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.719
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.487
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.309
971029AG2-637 GEN
Solar/Wind Harmer
10.57
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
LGEELTFEXP_LGEE->PJM
CLTF
4.631
TVALTFEXP_TVA->PJM
CLTF
4.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
WECLTFEXP_WEC->PJM
CLTF
5.141
MECLTFEXP_MEC->PJM
CLTF
19.157
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
NYPJM->LTFIMP_NY
CLTF
2.802
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
11.508

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
1.38
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
970155AG2-107 GEN
Solar/Wind Harmer
59.604
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.232
274676JOLIET 29;8U
Adder
43.62
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
957471AF2-041 GEN
Solar/Wind Harmer
28.375
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
23906502RICHG2&3
Adder
1.056
958391AF2-133 GEN
Solar/Wind Harmer
0.002
274827FISK ;RP
Adder
11.133
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972227AH1-698 GEN1
Adder
3.737
274735ELWOOD EC;4P
Adder
23.324
274744AC1-111 GEN8
Adder
7.861
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
963791AG1-232 GEN
Solar/Wind Harmer
12.673
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.719
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24344105CKG2
50/50
12.076
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970373AG2-245 GEN
Solar/Wind Harmer
21.825
943021AE2-325 GEN
Solar/Wind Harmer
5.398
971917AH1-482 GEN
Solar/Wind Harmer
13.304
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
21.176
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
270144AC1-141 ST1_
50/50
3.196
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.383
959331AF2-224 GEN
Solar/Wind Harmer
7.14
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
7.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
965041AG1-368 GEN
Solar/Wind Harmer
9.581
926823AC1-168 GEN
Solar/Wind Harmer
1.594
963841AG1-237 GEN
Solar/Wind Harmer
3.99
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
270356AE2-297 GEN
Solar/Wind Harmer
0
270101X2-052 CT2
50/50
2.25
247620Y3-023
50/50
0.727
965791AG1-447 GEN
Solar/Wind Harmer
9.691
945421AF1-207 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.407
270180AB1-006 GEN1
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
15.492
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.955
274765LEE CO EC;6U
Adder
12.402
274763LEE CO EC;4U
Adder
12.256
944541AF1-119 GEN
Solar/Wind Harmer
0.618
270031AE2-169
Solar/Wind Harmer
4.725
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276911AD2-131_GEN
Solar/Wind Harmer
1.118
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.468
962761AG1-125 GEN
Solar/Wind Harmer
93.339
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
11.974
274802UNIV PARK;5U
Adder
8.371
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
939401AE1-172 GEN
Solar/Wind Harmer
7.225
962781AG1-127 GEN
Solar/Wind Harmer
9.154
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
276708O09 GEN2
Solar/Wind Harmer
0.324
276903AD2-071 C
Solar/Wind Harmer
9.571
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270437AC2-090 C
Solar/Wind Harmer
0
24344005CKG1
50/50
9.721
24641605TWIN BRNCH
50/50
0.026
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
960591AF2-350 GEN
Solar/Wind Harmer
10.005
972228AH1-698 GEN2
Adder
5.307
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
965051AG1-369 GEN
Solar/Wind Harmer
4.689
972267AH1-718 GEN
Adder
5.487
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.309
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270102X2-052 ST
50/50
2.435
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.401
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
274808UNIV PK N;4U
Adder
7.201
274674JOLIET 9 ;6U
Adder
21.855
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274693ROCKY RD ;1P
Adder
15.339
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.399
270247TR4_N_V136
Solar/Wind Harmer
0.06
274764LEE CO EC;5U
Adder
12.402
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
960971AF2-388 GEN
Solar/Wind Harmer
5.429
960611AF2-352 GEN
Solar/Wind Harmer
2.992
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
24725505WLD G2 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
8.566
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
270054AF2-122 C O1
Solar/Wind Helper
1.203
270475AD2-096_GEN
50/50
9.997
24642205MAYFLWER
50/50
0.055
962601AG1-109 GEN
50/50
4.308
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274753CRETE EC ;3U
Adder
11.974
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274803UNIV PARK;6U
Adder
8.371
276843GEN-1.7
Solar/Wind Harmer
0.323
972038AH1-567 GEN2
Adder
0.523
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
965091AG1-374 GEN
Solar/Wind Harmer
26.927
965931AG1-462 GEN
Solar/Wind Harmer
22.694
270004AE1-209 GEN
Solar/Wind Harmer
1.763
24379505HDWTR1G C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
11.974
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
23.325
944531AF1-118 GEN
Solar/Wind Harmer
44.295
970781AG2-491 GEN
Solar/Wind Harmer
9.86
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.992
970193AG2-126 GEN
Solar/Wind Harmer
12.093
270541AE2-072 C
Solar/Wind Harmer
0
24307105BERRINSP G
50/50
0.032
957891AF2-083 GEN
Solar/Wind Harmer
17.358
945111AF1-176 GEN
Solar/Wind Harmer
18.541
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24386605FR-22G C
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
939741AE1-205 GEN
Solar/Wind Harmer
12.763
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.421
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
971771AH1-392 GEN
Solar/Wind Harmer
10.525
274728ELWOOD EC;5P
Adder
23.325
24691005MDL-2G C
Solar/Wind Harmer
0
24729505KEY G4
Adder
9.035
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270435AC2-044 GEN
Solar/Wind Harmer
1.153
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.183
270100X2-052 CT1
50/50
2.25
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
276893AG1-478 C
Solar/Wind Harmer
0.66
274696ROCKY RD ;4P
Adder
15.857
274697ROCKY RD ;3P
Adder
4.208
962691AG1-118 GEN
Solar/Wind Harmer
28.923
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274762LEE CO EC;3U
Adder
12.373
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970241AG2-163 GEN
Solar/Wind Harmer
5.219
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
276838X2-022 GEN2
Solar/Wind Harmer
0.473
970621AG2-405 GEN
Solar/Wind Harmer
1.383
944961AF1-161 GEN
50/50
4.308
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274724RIVER EC ;11
Adder
25.717
972259AH1-714 GEN
Adder
27.313
274729ELWOOD EC;1P
Adder
23.324
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
970571AG2-364 GEN
Solar/Wind Harmer
18.75
246938BC-WTG3
Solar/Wind Harmer
0.328
971993AH1-541 GEN
Solar/Wind Harmer
3.947
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
970825AG2-519 GEN
Solar/Wind Harmer
6.118
270240V3-007_GEN2
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
13.215
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276776AD2-060 GEN
Solar/Wind Harmer
1.067
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
270246TR4_N_V150
Solar/Wind Harmer
0.06
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
971613AH1-306 GEN
Solar/Wind Harmer
4.231
276916AD2-100_GEN
Solar/Wind Harmer
16.976
247621Y3-024
Adder
0.274
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270142AC1-141 CT1_
50/50
3.606
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
274811UNIV PK N;7U
Adder
7.232
276806AD2-047 C O1
Solar/Wind Harmer
5.669
274676JOLIET 29;8U
Adder
42.062
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274682WAUKEGAN ;7U
Adder
24.977
959091AF2-200 GEN
Solar/Wind Harmer
18.917
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
970289AG2-191 GEN
Solar/Wind Harmer
0.995
971087AG2-675 GEN
Solar/Wind Harmer
4.746
957381AF2-032 GEN
Solar/Wind Harmer
1.851
946031AF1-268 GEN
Solar/Wind Harmer
7.675
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
NYPJM->LTFIMP_NY
CLTF
2.802
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
WECLTFEXP_WEC->PJM
CLTF
5.141
MECLTFEXP_MEC->PJM
CLTF
19.157
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
LGEELTFEXP_LGEE->PJM
CLTF
4.631
TVALTFEXP_TVA->PJM
CLTF
4.677
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
1.14
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
1.14
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
1.34
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
1.3
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
0.94
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC116.27 %1892.0B2199.92
0.86
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.8 %1892.0B2190.94
0.86
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC115.5 %1646.0B1901.19
0.85
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC108.41 %1646.0B1784.35
0.87
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC115.9 %1878.0B2176.69
0.95
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.49 %1878.0B2168.95
0.95
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
1.34
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
1.3
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
1.45
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC110.01 %4571.0B5028.49
1.41
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC110.28 %4571.0B5040.8
1.41
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
1.03
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-810_SRT-A
SingleAC103.63 %1798.0B1863.35
0.84

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
1.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
NYPJM->LTFIMP_NY
CLTF
4.529
TVALTFEXP_TVA->PJM
CLTF
6.974
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
CPLELTFEXP_CPLE->PJM
CLTF
1.222
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
WECLTFEXP_WEC->PJM
CLTF
3.411
LAGNLTFEXP_LAGN->PJM
CLTF
14.046

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
1.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
WECLTFEXP_WEC->PJM
CLTF
3.411
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
CPLELTFEXP_CPLE->PJM
CLTF
1.222
SIGELTFEXP_SIGE->PJM
CLTF
0.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
LGEELTFEXP_LGEE->PJM
CLTF
6.23
MECLTFEXP_MEC->PJM
CLTF
14.364
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
NYPJM->LTFIMP_NY
CLTF
4.529
TVALTFEXP_TVA->PJM
CLTF
6.974
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
1.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
270291AC1-194 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
0.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189802OREGON_CT1
50/50
4.21
944231AF1-091 GEN
Solar/Wind Harmer
11.69
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
6.147
274808UNIV PK N;4U
Adder
2.71
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
274693ROCKY RD ;1P
Adder
5.741
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.284
274764LEE CO EC;5U
Adder
4.704
966841AG1-555 GEN
Solar/Wind Harmer
0.397
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
270599AE1-208 GEN
Solar/Wind Harmer
3.081
276615X2-022 GEN
Solar/Wind Harmer
0.034
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.196
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
241967AE2-285_GEN
Solar/Wind Helper
0.345
23856402BAYSG1
50/50
1.575
241858AF1-205_GEN
Solar/Wind Harmer
3.781
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.135
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
939401AE1-172 GEN
Solar/Wind Harmer
2.702
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.123
276903AD2-071 C
Solar/Wind Harmer
3.645
965911AG1-460 GEN
Solar/Wind Harmer
0.643
970621AG2-405 GEN
Solar/Wind Harmer
0.945
970623AG2-406 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
24189902OREGON_CT2
50/50
4.122
23906502RICHG2&3
Adder
1.343
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.722
274676JOLIET 29;8U
Adder
16.29
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
1.011
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241807AE2-176_GEN
Solar/Wind Helper
1.645
203830AF1-094 GEN
Solar/Wind Helper
0.331
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
965041AG1-368 GEN
Solar/Wind Harmer
4.372
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274776LINCOLN ;7U
Adder
4.514
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274746AC1-111 G10
Adder
2.931
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.603
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
964611AG1-324 GEN
Solar/Wind Harmer
1.3
944221AF1-090 GEN
Solar/Wind Harmer
1.843
241982AE2-343 S C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.646
23888802TROY G4
50/50
1.525
247620Y3-023
Adder
0.296
965791AG1-447 GEN
Solar/Wind Harmer
3.777
958011AF2-095 GEN
Solar/Wind Harmer
5.377
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.798
958491AF2-143 GEN
Solar/Wind Harmer
5.438
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
1.116
274765LEE CO EC;6U
Adder
4.704
274763LEE CO EC;4U
Adder
4.649
944541AF1-119 GEN
Solar/Wind Harmer
0.23
270031AE2-169
Solar/Wind Harmer
1.849
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.25
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965011AG1-365 GEN
Solar/Wind Harmer
4.252
274751CRETE EC ;1U
Adder
4.532
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.781
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
970569AG2-363 GEN
Solar/Wind Harmer
10.659
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
24386605FR-22G C
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
958861AF2-177 GEN
Solar/Wind Harmer
1.481
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
970031AG2-029 GEN
Solar/Wind Harmer
2.388
965051AG1-369 GEN
Solar/Wind Harmer
2.168
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
972228AH1-698 GEN2
Adder
1.977
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
971411AH1-196 GEN
Solar/Wind Harmer
5.374
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
971029AG2-637 GEN
Solar/Wind Harmer
4.677
203846AF2-130 C
Solar/Wind Helper
0.251
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
6.847
961971AG1-040 GEN
Solar/Wind Helper
0.342
254303AC2-168 GEN
Solar/Wind Helper
0.077
246938BC-WTG3
Solar/Wind Harmer
0.167
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270043AE2-236 GEN
Solar/Wind Harmer
2.608
274724RIVER EC ;11
Adder
9.665
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274729ELWOOD EC;1P
Adder
8.712
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
970571AG2-364 GEN
Solar/Wind Harmer
7.106
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
971993AH1-541 GEN
Solar/Wind Harmer
1.533
970825AG2-519 GEN
Solar/Wind Harmer
2.443
942481AE2-261 GEN
Solar/Wind Harmer
9.607
270240V3-007_GEN2
Solar/Wind Harmer
0
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274826FISK ;BP
Adder
5.877
274887GEN-1.85
Solar/Wind Harmer
0.097
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
970781AG2-491 GEN
Solar/Wind Harmer
3.598
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
944531AF1-118 GEN
Solar/Wind Harmer
16.015
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.144
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24728705AND G3
Adder
3.474
254305AE2-115 C
Solar/Wind Helper
0.114
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
274811UNIV PK N;7U
Adder
2.722
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274676JOLIET 29;8U
Adder
15.708
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274682WAUKEGAN ;7U
Adder
9.362
959091AF2-200 GEN
Solar/Wind Harmer
7.132
274767LEE CO EC;8U
Adder
4.638
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.367
946031AF1-268 GEN
Solar/Wind Harmer
3.094
957381AF2-032 GEN
Solar/Wind Harmer
0.73
24728505AND G1
Adder
1.661
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970885AG2-551 GEN
Solar/Wind Harmer
1.065
270383AD1-128 GEN
Solar/Wind Harmer
0
254304AE2-114 C
Solar/Wind Helper
0.114
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
23920202STRYCT
50/50
1.928
943021AE2-325 GEN
Solar/Wind Harmer
2.47
970373AG2-245 GEN
Solar/Wind Harmer
8.303
971917AH1-482 GEN
Solar/Wind Harmer
4.962
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.421
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970819AG2-516 GEN
Solar/Wind Harmer
4.255
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
7.998
274697ROCKY RD ;3P
Adder
1.575
962691AG1-118 GEN
Solar/Wind Harmer
10.839
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274762LEE CO EC;3U
Adder
4.693
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
970241AG2-163 GEN
Solar/Wind Harmer
1.971
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
962101AG1-054 GEN
Solar/Wind Helper
0.331
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
971549AH1-272 GEN
Solar/Wind Harmer
11.979
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
4.384
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270071AF1-092 GEN
Solar/Wind Harmer
7.265
274728ELWOOD EC;5P
Adder
8.713
970073AG2-061 GEN
Solar/Wind Harmer
1.208
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
270543AE2-219 C
Solar/Wind Harmer
2.237
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
963791AG1-232 GEN
Solar/Wind Harmer
5.317
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
972227AH1-698 GEN1
Adder
1.392
274735ELWOOD EC;4P
Adder
8.712
274744AC1-111 GEN8
Adder
2.931
970169AG2-114 GEN
Solar/Wind Harmer
3.545
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
959341AF2-225 GEN
Solar/Wind Harmer
3.643
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.132
24190002OREGON_ST1
50/50
5.546
270246TR4_N_V150
Solar/Wind Harmer
0.028
965681AG1-436 GEN
Solar/Wind Harmer
5.151
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.398
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276916AD2-100_GEN
Solar/Wind Harmer
6.713
203835AF1-098 GEN
Solar/Wind Helper
1.351
241801AE1-079 GEN
Solar/Wind Helper
0.135
203804AE2-113_GEN
Solar/Wind Helper
0.87
270437AC2-090 C
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.391
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274803UNIV PARK;6U
Adder
3.135
972038AH1-567 GEN2
Adder
0.196
276843GEN-1.7
Solar/Wind Harmer
0.121
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
965931AG1-462 GEN
Solar/Wind Harmer
8.718
270004AE1-209 GEN
Solar/Wind Harmer
0.699
24379505HDWTR1G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.35
990527J1329
External Queue
2.0237011909484863
991177J1571 G
External Queue
15.794994354248047
991182J1586 G
External Queue
28.12165069580078
990142J1224
External Queue
14.793254852294922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
WECLTFEXP_WEC->PJM
CLTF
1.945
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
CPLELTFEXP_CPLE->PJM
CLTF
0.731
SIGELTFEXP_SIGE->PJM
CLTF
0.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534
LGEELTFEXP_LGEE->PJM
CLTF
2.4
MECLTFEXP_MEC->PJM
CLTF
7.632
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
NYPJM->LTFIMP_NY
CLTF
1.965
TVALTFEXP_TVA->PJM
CLTF
2.775
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.27 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2199.92
MW Contribution:
0.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
1.777
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
274752CRETE EC ;2U
Adder
3.916
274826FISK ;BP
Adder
5.071
274887GEN-1.85
Solar/Wind Harmer
0.084
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.513
970707AG2-453 GEN
Solar/Wind Harmer
10.414
274862TOP CROP ;2U
Solar/Wind Harmer
0.425
276868AE1-113 GEN
Solar/Wind Harmer
0.621
274879MINONK ;1U
Solar/Wind Harmer
0.13
970781AG2-491 GEN
Solar/Wind Harmer
3.1
944531AF1-118 GEN
Solar/Wind Harmer
13.889
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274857EASY ROAD;U1
Solar/Wind Harmer
0
23856402BAYSG1
50/50
1.208
241858AF1-205_GEN
Solar/Wind Harmer
3.879
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.705
23920202STRYCT
50/50
1.93
943021AE2-325 GEN
Solar/Wind Harmer
2.151
970373AG2-245 GEN
Solar/Wind Harmer
7.184
971917AH1-482 GEN
Solar/Wind Harmer
4.286
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.362
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.068
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.612
970819AG2-516 GEN
Solar/Wind Harmer
3.659
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
274732ELWOOD EC;7P
Adder
7.513
274674JOLIET 9 ;6U
Adder
7.036
939401AE1-172 GEN
Solar/Wind Harmer
2.327
962781AG1-127 GEN
Solar/Wind Harmer
2.955
274766LEE CO EC;7U
Adder
3.986
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.106
203947AF1-006 C
Solar/Wind Helper
0.381
24189802OREGON_CT1
50/50
2.906
944231AF1-091 GEN
Solar/Wind Harmer
10.721
961051AF2-396 GEN
Solar/Wind Harmer
8.175
961051AF2-396 GEN
Solar/Wind Harmer
5.45
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.33
274808UNIV PK N;4U
Adder
2.34
274674JOLIET 9 ;6U
Adder
7.036
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274693ROCKY RD ;1P
Adder
4.945
274683WAUKEGAN ;8U
Adder
9.446
274683WAUKEGAN ;8U
Adder
7.963
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.104
274764LEE CO EC;5U
Adder
4.043
966841AG1-555 GEN
Solar/Wind Harmer
0.342
241967AE2-285_GEN
Solar/Wind Helper
0.341
254305AE2-115 C
Solar/Wind Helper
0.113
24189902OREGON_CT2
50/50
2.845
23906502RICHG2&3
Adder
1.328
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
12.304
24639705ELKHART HY
Adder
0.086
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.35
274676JOLIET 29;8U
Adder
14.047
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.064
274828WAUKEGAN ;BP
Adder
4.951
270024AE2-089 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.204
241807AE2-176_GEN
Solar/Wind Helper
2.245
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.195
241966AE1-183 GEN
Solar/Wind Helper
0.131
23888802TROY G4
50/50
1.902
247620Y3-023
Adder
0.259
965791AG1-447 GEN
Solar/Wind Harmer
3.274
958011AF2-095 GEN
Solar/Wind Harmer
4.639
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
4.994
958491AF2-143 GEN
Solar/Wind Harmer
4.683
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.96
274765LEE CO EC;6U
Adder
4.043
274763LEE CO EC;4U
Adder
3.996
254304AE2-114 C
Solar/Wind Helper
0.113
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
23888702TROY G3
50/50
1.902
972253AH1-711 GEN
50/50
58.161
241885AC2-103 GEN1
Solar/Wind Harmer
0
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
945111AF1-176 GEN
Solar/Wind Harmer
7.189
957891AF2-083 GEN
Solar/Wind Harmer
6.688
965011AG1-365 GEN
Solar/Wind Harmer
3.748
274751CRETE EC ;1U
Adder
3.916
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.448
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.025
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
970569AG2-363 GEN
Solar/Wind Harmer
9.168
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.034
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.061
270499AE1-146 GEN
Solar/Wind Harmer
0.019
965041AG1-368 GEN
Solar/Wind Harmer
3.882
959331AF2-224 GEN
Solar/Wind Harmer
2.624
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
274776LINCOLN ;7U
Adder
3.895
274687WILL CNTY;4U
Adder
12.821
274687WILL CNTY;4U
Adder
12.821
274731ELWOOD EC;2P
Adder
7.512
274733ELWOOD EC;3P
Adder
7.512
274746AC1-111 G10
Adder
2.526
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.519
241982AE2-343 S C
Solar/Wind Helper
0.119
20334926Z1-069 C
Solar/Wind Helper
0.647
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.061
970031AG2-029 GEN
Solar/Wind Harmer
2.091
965051AG1-369 GEN
Solar/Wind Harmer
1.924
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
960591AF2-350 GEN
Solar/Wind Harmer
3.221
274775LINCOLN ;6U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972228AH1-698 GEN2
Adder
1.705
274675JOLIET 29;7U
Adder
14.048
274675JOLIET 29;7U
Adder
13.546
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.326
971411AH1-196 GEN
Solar/Wind Harmer
4.625
971675AH1-338 GEN
Solar/Wind Harmer
1.201
971171AH1-044 GEN
Solar/Wind Harmer
6.136
274823ROCKFORD ;21
Adder
8.55
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.793
203846AF2-130 C
Solar/Wind Helper
0.248
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.129
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274803UNIV PARK;6U
Adder
2.705
972038AH1-567 GEN2
Adder
0.169
276843GEN-1.7
Solar/Wind Harmer
0.104
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.034
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.342
23867002DVBSG1
50/50
15.354
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.805
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.355
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
970941AG2-585 GEN
Solar/Wind Harmer
1.772
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
276897AD1-100 C
Solar/Wind Harmer
7.977
276893AG1-478 C
Solar/Wind Harmer
0.213
942221AE2-234 GEN
Solar/Wind Harmer
1.273
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.112
274697ROCKY RD ;3P
Adder
1.357
962691AG1-118 GEN
Solar/Wind Harmer
9.333
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274762LEE CO EC;3U
Adder
4.034
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.484
962101AG1-054 GEN
Solar/Wind Helper
0.329
24386605FR-22G C
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.334
254303AC2-168 GEN
Solar/Wind Helper
0.077
23888502TROY G1
50/50
1.902
23888602TROY G2
50/50
1.902
241886AC2-103 GEN2
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.493
270435AC2-044 GEN
Solar/Wind Harmer
0.524
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.813
971567AH1-282 GEN
Solar/Wind Harmer
2.667
270071AF1-092 GEN
Solar/Wind Harmer
6.326
274728ELWOOD EC;5P
Adder
7.513
970073AG2-061 GEN
Solar/Wind Harmer
1.041
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
24729505KEY G4
Adder
2.853
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.884
241985AE1-237 GEN
Solar/Wind Helper
0.133
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270588AE1-091_GEN
Solar/Wind Harmer
3.209
24695305TIMB G C
Solar/Wind Harmer
0.337
274811UNIV PK N;7U
Adder
2.35
276806AD2-047 C O1
Solar/Wind Harmer
1.825
274676JOLIET 29;8U
Adder
13.546
274734ELWOOD EC;8P
Adder
7.513
274736ELWOOD EC;9P
Adder
7.513
943121AE2-341 GEN
Solar/Wind Harmer
5.283
943591AF1-030 GEN
Solar/Wind Harmer
3.513
274682WAUKEGAN ;7U
Adder
8.064
959091AF2-200 GEN
Solar/Wind Harmer
6.136
274767LEE CO EC;8U
Adder
3.986
24190002OREGON_ST1
50/50
3.828
270246TR4_N_V150
Solar/Wind Harmer
0.025
965681AG1-436 GEN
Solar/Wind Harmer
4.465
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.344
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.136
971343AH1-151 GEN
Solar/Wind Harmer
6.136
203835AF1-098 GEN
Solar/Wind Helper
1.32
241801AE1-079 GEN
Solar/Wind Helper
0.133
203804AE2-113_GEN
Solar/Wind Helper
0.869
246938BC-WTG3
Solar/Wind Harmer
0.149
945111AF1-176 GEN
Solar/Wind Harmer
3.265
270505AE1-170 C O1
Solar/Wind Harmer
4.228
965021AG1-366 GEN
Solar/Wind Harmer
1.249
270043AE2-236 GEN
Solar/Wind Harmer
2.282
274724RIVER EC ;11
Adder
8.348
274772LINCOLN ;3U
Adder
3.895
972259AH1-714 GEN
Adder
8.742
274729ELWOOD EC;1P
Adder
7.512
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
970571AG2-364 GEN
Solar/Wind Harmer
6.112
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.14
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.517
963791AG1-232 GEN
Solar/Wind Harmer
4.667
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.594
274800UNIV PARK;3U
Adder
2.696
274801UNIV PARK;4U
Adder
2.696
972227AH1-698 GEN1
Adder
1.201
274735ELWOOD EC;4P
Adder
7.512
274744AC1-111 GEN8
Adder
2.526
970169AG2-114 GEN
Solar/Wind Harmer
3.049
276741O09 GEN1
Solar/Wind Harmer
0.106
241997AF1-093 GEN
Solar/Wind Helper
0.131
990527J1329
External Queue
1.907416582107544
991177J1571 G
External Queue
15.850347518920898
991182J1586 G
External Queue
26.14141845703125
990142J1224
External Queue
13.943214416503906
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.332
NYPJM->LTFIMP_NY
CLTF
2.03
TVALTFEXP_TVA->PJM
CLTF
2.246
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.683
LGEELTFEXP_LGEE->PJM
CLTF
2.008
MECLTFEXP_MEC->PJM
CLTF
6.511
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.187
CPLELTFEXP_CPLE->PJM
CLTF
0.328
SIGELTFEXP_SIGE->PJM
CLTF
0.168
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.892
WECLTFEXP_WEC->PJM
CLTF
1.673
LAGNLTFEXP_LAGN->PJM
CLTF
4.961

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2190.94
MW Contribution:
0.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.195
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
945111AF1-176 GEN
Solar/Wind Harmer
7.201
957891AF2-083 GEN
Solar/Wind Harmer
6.7
965011AG1-365 GEN
Solar/Wind Harmer
3.755
274751CRETE EC ;1U
Adder
3.924
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.466
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.903
274774LINCOLN ;5U
Adder
3.903
971605AH1-302 GEN
Solar/Wind Harmer
4.034
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
970569AG2-363 GEN
Solar/Wind Harmer
9.19
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.043
24386605FR-22G C
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.957
961971AG1-040 GEN
Solar/Wind Helper
0.334
254303AC2-168 GEN
Solar/Wind Helper
0.076
23920202STRYCT
50/50
1.931
943021AE2-325 GEN
Solar/Wind Harmer
2.155
970373AG2-245 GEN
Solar/Wind Harmer
7.199
971917AH1-482 GEN
Solar/Wind Harmer
4.296
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.513
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.363
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.075
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.632
970819AG2-516 GEN
Solar/Wind Harmer
3.668
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
23929302BS-PKR
50/50
2.13
958321AF2-126 GEN
Solar/Wind Harmer
1.13
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
274753CRETE EC ;3U
Adder
3.924
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274803UNIV PARK;6U
Adder
2.711
972038AH1-567 GEN2
Adder
0.169
276843GEN-1.7
Solar/Wind Harmer
0.104
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.043
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.341
24189802OREGON_CT1
50/50
2.907
944231AF1-091 GEN
Solar/Wind Harmer
10.737
961051AF2-396 GEN
Solar/Wind Harmer
8.189
961051AF2-396 GEN
Solar/Wind Harmer
5.459
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.34
274808UNIV PK N;4U
Adder
2.345
274674JOLIET 9 ;6U
Adder
7.052
958481AF2-142 GEN
Solar/Wind Harmer
4.736
274693ROCKY RD ;1P
Adder
4.956
274683WAUKEGAN ;8U
Adder
9.467
274683WAUKEGAN ;8U
Adder
7.981
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.107
274764LEE CO EC;5U
Adder
4.053
966841AG1-555 GEN
Solar/Wind Harmer
0.343
241967AE2-285_GEN
Solar/Wind Helper
0.34
254305AE2-115 C
Solar/Wind Helper
0.113
23856402BAYSG1
50/50
1.209
241858AF1-205_GEN
Solar/Wind Harmer
3.882
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.924
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.711
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.052
939401AE1-172 GEN
Solar/Wind Harmer
2.332
962781AG1-127 GEN
Solar/Wind Harmer
2.962
274766LEE CO EC;7U
Adder
3.996
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.106
203947AF1-006 C
Solar/Wind Helper
0.381
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.066
270499AE1-146 GEN
Solar/Wind Harmer
0.019
965041AG1-368 GEN
Solar/Wind Harmer
3.889
959331AF2-224 GEN
Solar/Wind Harmer
2.629
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
274776LINCOLN ;7U
Adder
3.903
274687WILL CNTY;4U
Adder
12.849
274687WILL CNTY;4U
Adder
12.849
274731ELWOOD EC;2P
Adder
7.529
274733ELWOOD EC;3P
Adder
7.529
274746AC1-111 G10
Adder
2.531
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.52
241982AE2-343 S C
Solar/Wind Helper
0.119
20334926Z1-069 C
Solar/Wind Helper
0.645
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.066
970031AG2-029 GEN
Solar/Wind Harmer
2.095
965051AG1-369 GEN
Solar/Wind Harmer
1.928
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
960591AF2-350 GEN
Solar/Wind Harmer
3.228
274775LINCOLN ;6U
Adder
3.903
274777LINCOLN ;8U
Adder
3.903
971611AH1-305 GEN
Solar/Wind Harmer
1.921
972228AH1-698 GEN2
Adder
1.709
274675JOLIET 29;7U
Adder
14.079
274675JOLIET 29;7U
Adder
13.576
970833AG2-524 GEN
Solar/Wind Harmer
3.497
970833AG2-524 GEN
Solar/Wind Harmer
2.332
971411AH1-196 GEN
Solar/Wind Harmer
4.636
971675AH1-338 GEN
Solar/Wind Harmer
1.204
971171AH1-044 GEN
Solar/Wind Harmer
6.15
274823ROCKFORD ;21
Adder
8.57
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.797
203846AF2-130 C
Solar/Wind Helper
0.248
23867002DVBSG1
50/50
15.36
970621AG2-405 GEN
Solar/Wind Harmer
0.865
970623AG2-406 GEN
Solar/Wind Harmer
0.807
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.36
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
970941AG2-585 GEN
Solar/Wind Harmer
1.776
274770LINCOLN ;1U
Adder
3.903
274771LINCOLN ;2U
Adder
3.903
276897AD1-100 C
Solar/Wind Harmer
7.994
276893AG1-478 C
Solar/Wind Harmer
0.213
942221AE2-234 GEN
Solar/Wind Harmer
1.276
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.123
274697ROCKY RD ;3P
Adder
1.36
962691AG1-118 GEN
Solar/Wind Harmer
9.354
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274762LEE CO EC;3U
Adder
4.043
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.485
962101AG1-054 GEN
Solar/Wind Helper
0.328
24190002OREGON_ST1
50/50
3.83
270246TR4_N_V150
Solar/Wind Harmer
0.025
965681AG1-436 GEN
Solar/Wind Harmer
4.474
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.344
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.15
971343AH1-151 GEN
Solar/Wind Harmer
6.15
203835AF1-098 GEN
Solar/Wind Helper
1.318
241801AE1-079 GEN
Solar/Wind Helper
0.133
203804AE2-113_GEN
Solar/Wind Helper
0.867
24189902OREGON_CT2
50/50
2.847
23906502RICHG2&3
Adder
1.329
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
12.325
24639705ELKHART HY
Adder
0.086
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.355
274676JOLIET 29;8U
Adder
14.079
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.531
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.082
274828WAUKEGAN ;BP
Adder
4.963
270024AE2-089 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.225
241807AE2-176_GEN
Solar/Wind Helper
2.243
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.131
23888802TROY G4
50/50
1.904
247620Y3-023
Adder
0.259
965791AG1-447 GEN
Solar/Wind Harmer
3.281
958011AF2-095 GEN
Solar/Wind Harmer
4.649
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.005
958491AF2-143 GEN
Solar/Wind Harmer
4.694
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.962
274765LEE CO EC;6U
Adder
4.053
274763LEE CO EC;4U
Adder
4.005
254304AE2-114 C
Solar/Wind Helper
0.113
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270435AC2-044 GEN
Solar/Wind Harmer
0.525
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.82
971567AH1-282 GEN
Solar/Wind Harmer
2.672
270071AF1-092 GEN
Solar/Wind Harmer
6.34
274728ELWOOD EC;5P
Adder
7.529
970073AG2-061 GEN
Solar/Wind Harmer
1.043
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
24729505KEY G4
Adder
2.859
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.896
241886AC2-103 GEN2
Solar/Wind Helper
3.957
241985AE1-237 GEN
Solar/Wind Helper
0.132
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
1.78
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
274752CRETE EC ;2U
Adder
3.924
274826FISK ;BP
Adder
5.082
274887GEN-1.85
Solar/Wind Harmer
0.084
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
10.437
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
276868AE1-113 GEN
Solar/Wind Harmer
0.623
274879MINONK ;1U
Solar/Wind Harmer
0.13
970781AG2-491 GEN
Solar/Wind Harmer
3.107
944531AF1-118 GEN
Solar/Wind Harmer
13.92
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274857EASY ROAD;U1
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.149
945111AF1-176 GEN
Solar/Wind Harmer
3.271
270505AE1-170 C O1
Solar/Wind Harmer
4.235
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270043AE2-236 GEN
Solar/Wind Harmer
2.286
274724RIVER EC ;11
Adder
8.366
274772LINCOLN ;3U
Adder
3.903
972259AH1-714 GEN
Adder
8.761
274729ELWOOD EC;1P
Adder
7.529
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
970571AG2-364 GEN
Solar/Wind Harmer
6.126
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.329
270588AE1-091_GEN
Solar/Wind Harmer
3.215
24695305TIMB G C
Solar/Wind Harmer
0.338
274811UNIV PK N;7U
Adder
2.355
276806AD2-047 C O1
Solar/Wind Harmer
1.829
274676JOLIET 29;8U
Adder
13.576
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
943121AE2-341 GEN
Solar/Wind Harmer
5.295
943591AF1-030 GEN
Solar/Wind Harmer
3.521
274682WAUKEGAN ;7U
Adder
8.082
959091AF2-200 GEN
Solar/Wind Harmer
6.15
274767LEE CO EC;8U
Adder
3.996
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.14
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.518
963791AG1-232 GEN
Solar/Wind Harmer
4.677
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.602
274800UNIV PARK;3U
Adder
2.702
274801UNIV PARK;4U
Adder
2.702
972227AH1-698 GEN1
Adder
1.203
274735ELWOOD EC;4P
Adder
7.529
274744AC1-111 GEN8
Adder
2.531
970169AG2-114 GEN
Solar/Wind Harmer
3.057
276741O09 GEN1
Solar/Wind Harmer
0.106
241997AF1-093 GEN
Solar/Wind Helper
0.131
990527J1329
External Queue
1.907416582107544
991177J1571 G
External Queue
15.850347518920898
991182J1586 G
External Queue
26.14141845703125
990142J1224
External Queue
13.943214416503906
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.48
NYPJM->LTFIMP_NY
CLTF
2.024
TVALTFEXP_TVA->PJM
CLTF
2.256
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.82
LGEELTFEXP_LGEE->PJM
CLTF
2.015
MECLTFEXP_MEC->PJM
CLTF
6.528
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.218
CPLELTFEXP_CPLE->PJM
CLTF
0.339
SIGELTFEXP_SIGE->PJM
CLTF
0.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.931
WECLTFEXP_WEC->PJM
CLTF
1.677
LAGNLTFEXP_LAGN->PJM
CLTF
4.981

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.5 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:1901.19
MW Contribution:
0.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.794
972253AH1-711 GEN
50/50
54.851
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.161
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
6.884
957891AF2-083 GEN
Solar/Wind Harmer
6.405
965011AG1-365 GEN
Solar/Wind Harmer
3.613
274751CRETE EC ;1U
Adder
3.759
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.111
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.74
274774LINCOLN ;5U
Adder
3.74
971605AH1-302 GEN
Solar/Wind Harmer
3.866
241885AC2-103 GEN1
Solar/Wind Helper
9.125
961971AG1-040 GEN
Solar/Wind Helper
0.324
23920202STRYCT
50/50
1.869
943021AE2-325 GEN
Solar/Wind Harmer
2.059
970373AG2-245 GEN
Solar/Wind Harmer
6.894
971917AH1-482 GEN
Solar/Wind Harmer
4.115
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.492
274861TOP CROP ;1U
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.111
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
274753CRETE EC ;3U
Adder
3.759
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274803UNIV PARK;6U
Adder
2.598
972038AH1-567 GEN2
Adder
0.162
276843GEN-1.7
Solar/Wind Harmer
0.1
962511AG1-100 GEN
Solar/Wind Helper
0.331
24189802OREGON_CT1
50/50
2.723
944231AF1-091 GEN
Solar/Wind Harmer
10.357
961051AF2-396 GEN
Solar/Wind Harmer
7.826
961051AF2-396 GEN
Solar/Wind Harmer
5.217
270247TR4_N_V136
Solar/Wind Harmer
0.024
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.113
274808UNIV PK N;4U
Adder
2.247
274674JOLIET 9 ;6U
Adder
6.758
958481AF2-142 GEN
Solar/Wind Harmer
4.539
274693ROCKY RD ;1P
Adder
4.75
274683WAUKEGAN ;8U
Adder
9.073
274683WAUKEGAN ;8U
Adder
7.648
241967AE2-285_GEN
Solar/Wind Helper
0.329
254305AE2-115 C
Solar/Wind Helper
0.109
23856402BAYSG1
50/50
1.208
241858AF1-205_GEN
Solar/Wind Harmer
3.76
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.759
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.598
274732ELWOOD EC;7P
Adder
7.215
274674JOLIET 9 ;6U
Adder
6.758
203947AF1-006 C
Solar/Wind Helper
0.369
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.2
270499AE1-146 GEN
Solar/Wind Harmer
0.019
965041AG1-368 GEN
Solar/Wind Harmer
3.754
959331AF2-224 GEN
Solar/Wind Harmer
2.529
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.221
274776LINCOLN ;7U
Adder
3.74
274687WILL CNTY;4U
Adder
12.312
274687WILL CNTY;4U
Adder
12.312
274731ELWOOD EC;2P
Adder
7.215
274733ELWOOD EC;3P
Adder
7.215
274746AC1-111 G10
Adder
2.426
241982AE2-343 S C
Solar/Wind Helper
0.115
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.2
965051AG1-369 GEN
Solar/Wind Harmer
1.862
970031AG2-029 GEN
Solar/Wind Harmer
2.008
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.082
960591AF2-350 GEN
Solar/Wind Harmer
3.093
274775LINCOLN ;6U
Adder
3.74
274777LINCOLN ;8U
Adder
3.74
971611AH1-305 GEN
Solar/Wind Harmer
1.841
972228AH1-698 GEN2
Adder
1.637
274675JOLIET 29;7U
Adder
13.491
274675JOLIET 29;7U
Adder
13.009
970833AG2-524 GEN
Solar/Wind Harmer
3.352
970833AG2-524 GEN
Solar/Wind Harmer
2.234
203846AF2-130 C
Solar/Wind Helper
0.24
254303AC2-168 GEN
Solar/Wind Helper
0.074
23867002DVBSG1
50/50
13.924
970621AG2-405 GEN
Solar/Wind Harmer
0.846
970623AG2-406 GEN
Solar/Wind Harmer
0.781
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.161
274805UNIV PK N;1U
Adder
2.261
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
970941AG2-585 GEN
Solar/Wind Harmer
1.701
274770LINCOLN ;1U
Adder
3.74
274771LINCOLN ;2U
Adder
3.74
276897AD1-100 C
Solar/Wind Harmer
7.661
276893AG1-478 C
Solar/Wind Harmer
0.204
942221AE2-234 GEN
Solar/Wind Harmer
1.227
957841AF2-078 GEN
Solar/Wind Harmer
0
274697ROCKY RD ;3P
Adder
1.303
274696ROCKY RD ;4P
Adder
4.91
962101AG1-054 GEN
Solar/Wind Helper
0.317
24190002OREGON_ST1
50/50
3.587
270246TR4_N_V150
Solar/Wind Harmer
0.024
965681AG1-436 GEN
Solar/Wind Harmer
4.282
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.33
203835AF1-098 GEN
Solar/Wind Helper
1.278
241801AE1-079 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.839
24189902OREGON_CT2
50/50
2.666
23906502RICHG2&3
Adder
1.29
965421AG1-410 GEN
Solar/Wind Harmer
11.889
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.256
274676JOLIET 29;8U
Adder
13.491
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.426
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
7.745
270024AE2-089 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
4.756
203830AF1-094 GEN
Solar/Wind Helper
0.314
203979AG1-198 GEN
Solar/Wind Helper
0.188
241966AE1-183 GEN
Solar/Wind Helper
0.126
241807AE2-176_GEN
Solar/Wind Helper
0.767
23888802TROY G4
50/50
1.794
247620Y3-023
Adder
0.248
965791AG1-447 GEN
Solar/Wind Harmer
3.14
958011AF2-095 GEN
Solar/Wind Harmer
4.455
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
4.797
254304AE2-114 C
Solar/Wind Helper
0.109
940863AE2-074 GEN
Solar/Wind Helper
0.218
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.144
945111AF1-176 GEN
Solar/Wind Harmer
3.127
270505AE1-170 C O1
Solar/Wind Harmer
4.048
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270043AE2-236 GEN
Solar/Wind Harmer
2.195
274724RIVER EC ;11
Adder
8.014
274772LINCOLN ;3U
Adder
3.74
972259AH1-714 GEN
Adder
8.395
274729ELWOOD EC;1P
Adder
7.215
971347AH1-153 GEN
Solar/Wind Harmer
1.704
270391AF1-285 GEN3
Solar/Wind Harmer
0.221
274752CRETE EC ;2U
Adder
3.759
274826FISK ;BP
Adder
4.869
274887GEN-1.85
Solar/Wind Harmer
0.08
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.002
274730ELWOOD EC;6P
Adder
7.215
274862TOP CROP ;2U
Solar/Wind Harmer
0.408
23906402RICHG1
Adder
1.292
23906502RICHG2&3
Adder
1.29
270588AE1-091_GEN
Solar/Wind Harmer
3.197
24695305TIMB G C
Solar/Wind Harmer
0.327
274811UNIV PK N;7U
Adder
2.256
276806AD2-047 C O1
Solar/Wind Harmer
1.753
274676JOLIET 29;8U
Adder
13.009
274734ELWOOD EC;8P
Adder
7.215
274736ELWOOD EC;9P
Adder
7.215
943121AE2-341 GEN
Solar/Wind Harmer
5.074
943591AF1-030 GEN
Solar/Wind Harmer
3.375
274682WAUKEGAN ;7U
Adder
7.745
23888502TROY G1
50/50
1.794
23888602TROY G2
50/50
1.794
971549AH1-272 GEN
Solar/Wind Harmer
10.01
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971771AH1-392 GEN
Solar/Wind Harmer
3.654
971567AH1-282 GEN
Solar/Wind Harmer
2.615
270071AF1-092 GEN
Solar/Wind Harmer
6.092
274728ELWOOD EC;5P
Adder
7.215
241886AC2-103 GEN2
Solar/Wind Helper
9.125
241985AE1-237 GEN
Solar/Wind Helper
0.128
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.135
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.502
963791AG1-232 GEN
Solar/Wind Harmer
4.503
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.451
274800UNIV PARK;3U
Adder
2.589
274801UNIV PARK;4U
Adder
2.589
972227AH1-698 GEN1
Adder
1.153
274735ELWOOD EC;4P
Adder
7.215
274744AC1-111 GEN8
Adder
2.426
241997AF1-093 GEN
Solar/Wind Helper
0.126
990527J1329
External Queue
1.8005300760269165
991177J1571 G
External Queue
15.046978950500488
991182J1586 G
External Queue
24.65581703186035
990142J1224
External Queue
13.161874771118164
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.601
WECLTFEXP_WEC->PJM
CLTF
1.607
LAGNLTFEXP_LAGN->PJM
CLTF
4.791
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.145
CPLELTFEXP_CPLE->PJM
CLTF
0.33
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.279
LGEELTFEXP_LGEE->PJM
CLTF
1.942
MECLTFEXP_MEC->PJM
CLTF
6.262
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.855
NYPJM->LTFIMP_NY
CLTF
1.956
TVALTFEXP_TVA->PJM
CLTF
2.172
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:1784.35
MW Contribution:
0.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
53.016
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
6.805
957891AF2-083 GEN
Solar/Wind Harmer
6.33
965011AG1-365 GEN
Solar/Wind Harmer
3.609
274751CRETE EC ;1U
Adder
3.727
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.042
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.835
274773LINCOLN ;4U
Adder
3.71
246938BC-WTG3
Solar/Wind Harmer
0.145
945111AF1-176 GEN
Solar/Wind Harmer
3.091
270505AE1-170 C O1
Solar/Wind Harmer
4.001
965021AG1-366 GEN
Solar/Wind Harmer
1.203
270043AE2-236 GEN
Solar/Wind Harmer
2.185
274724RIVER EC ;11
Adder
7.946
274772LINCOLN ;3U
Adder
3.71
972259AH1-714 GEN
Adder
8.327
274729ELWOOD EC;1P
Adder
7.156
24189802OREGON_CT1
50/50
2.603
944231AF1-091 GEN
Solar/Wind Harmer
10.388
961051AF2-396 GEN
Solar/Wind Harmer
7.732
961051AF2-396 GEN
Solar/Wind Harmer
5.155
270247TR4_N_V136
Solar/Wind Harmer
0.024
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.065
274808UNIV PK N;4U
Adder
2.228
274674JOLIET 9 ;6U
Adder
6.703
958481AF2-142 GEN
Solar/Wind Harmer
4.502
241967AE2-285_GEN
Solar/Wind Helper
0.332
254305AE2-115 C
Solar/Wind Helper
0.111
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.305
270588AE1-091_GEN
Solar/Wind Harmer
3.359
24695305TIMB G C
Solar/Wind Harmer
0.329
274811UNIV PK N;7U
Adder
2.237
276806AD2-047 C O1
Solar/Wind Harmer
1.739
274676JOLIET 29;8U
Adder
12.903
274734ELWOOD EC;8P
Adder
7.156
274736ELWOOD EC;9P
Adder
7.156
943121AE2-341 GEN
Solar/Wind Harmer
5.034
943591AF1-030 GEN
Solar/Wind Harmer
3.348
23888802TROY G4
50/50
1.734
247620Y3-023
Adder
0.246
965791AG1-447 GEN
Solar/Wind Harmer
3.109
958011AF2-095 GEN
Solar/Wind Harmer
4.418
254304AE2-114 C
Solar/Wind Helper
0.111
940863AE2-074 GEN
Solar/Wind Helper
0.22
946381AF1-302 GEN
Solar/Wind Helper
0.103
24189902OREGON_CT2
50/50
2.549
23906502RICHG2&3
Adder
1.305
241807AE2-176_GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
11.924
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.237
274676JOLIET 29;8U
Adder
13.38
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.406
270024AE2-089 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.318
203979AG1-198 GEN
Solar/Wind Helper
0.191
241966AE1-183 GEN
Solar/Wind Helper
0.128
23867002DVBSG1
50/50
12.56
970621AG2-405 GEN
Solar/Wind Harmer
0.867
970623AG2-406 GEN
Solar/Wind Harmer
0.789
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.162
274805UNIV PK N;1U
Adder
2.242
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
970941AG2-585 GEN
Solar/Wind Harmer
1.687
274770LINCOLN ;1U
Adder
3.71
274771LINCOLN ;2U
Adder
3.71
942221AE2-234 GEN
Solar/Wind Harmer
1.226
276897AD1-100 C
Solar/Wind Harmer
7.599
276893AG1-478 C
Solar/Wind Harmer
0.203
962101AG1-054 GEN
Solar/Wind Helper
0.321
270428AC2-015 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
23920202STRYCT
50/50
1.886
943021AE2-325 GEN
Solar/Wind Harmer
2.034
970373AG2-245 GEN
Solar/Wind Harmer
6.831
971917AH1-482 GEN
Solar/Wind Harmer
4.081
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.488
274861TOP CROP ;1U
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.656
270499AE1-146 GEN
Solar/Wind Harmer
0.021
965041AG1-368 GEN
Solar/Wind Harmer
3.768
959331AF2-224 GEN
Solar/Wind Harmer
2.526
24191202EL_AA1-006
Adder
0.112
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
274776LINCOLN ;7U
Adder
3.71
274687WILL CNTY;4U
Adder
12.211
274687WILL CNTY;4U
Adder
12.211
274731ELWOOD EC;2P
Adder
7.156
274733ELWOOD EC;3P
Adder
7.156
274746AC1-111 G10
Adder
2.406
241982AE2-343 S C
Solar/Wind Helper
0.116
20334926Z1-069 C
Solar/Wind Helper
0.632
247521TR3_G114
Solar/Wind Harmer
0.136
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.507
963791AG1-232 GEN
Solar/Wind Harmer
4.502
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.422
274800UNIV PARK;3U
Adder
2.568
274801UNIV PARK;4U
Adder
2.568
972227AH1-698 GEN1
Adder
1.144
274735ELWOOD EC;4P
Adder
7.156
274744AC1-111 GEN8
Adder
2.406
241997AF1-093 GEN
Solar/Wind Helper
0.128
270361_3
Solar/Wind Harmer
4.656
945641AF1-229 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
1.872
970031AG2-029 GEN
Solar/Wind Harmer
1.993
270377AD1-106 GEN
Solar/Wind Harmer
1.238
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
960591AF2-350 GEN
Solar/Wind Harmer
3.068
971611AH1-305 GEN
Solar/Wind Harmer
1.827
274775LINCOLN ;6U
Adder
3.71
274777LINCOLN ;8U
Adder
3.71
972228AH1-698 GEN2
Adder
1.624
274675JOLIET 29;7U
Adder
13.381
274675JOLIET 29;7U
Adder
12.903
970833AG2-524 GEN
Solar/Wind Harmer
3.325
970833AG2-524 GEN
Solar/Wind Harmer
2.216
203846AF2-130 C
Solar/Wind Helper
0.243
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
971549AH1-272 GEN
Solar/Wind Harmer
9.841
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971771AH1-392 GEN
Solar/Wind Harmer
3.616
971567AH1-282 GEN
Solar/Wind Harmer
2.681
270071AF1-092 GEN
Solar/Wind Harmer
6.069
274728ELWOOD EC;5P
Adder
7.156
241886AC2-103 GEN2
Solar/Wind Helper
9.501
241985AE1-237 GEN
Solar/Wind Helper
0.129
274774LINCOLN ;5U
Adder
3.71
241885AC2-103 GEN1
Solar/Wind Helper
9.501
961971AG1-040 GEN
Solar/Wind Helper
0.328
254303AC2-168 GEN
Solar/Wind Helper
0.075
23856402BAYSG1
50/50
1.279
241858AF1-205_GEN
Solar/Wind Harmer
3.799
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.727
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.576
274732ELWOOD EC;7P
Adder
7.156
274674JOLIET 9 ;6U
Adder
6.703
203947AF1-006 C
Solar/Wind Helper
0.374
23929302BS-PKR
50/50
2.254
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
1.688
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
274752CRETE EC ;2U
Adder
3.727
274826FISK ;BP
Adder
4.829
274887GEN-1.85
Solar/Wind Harmer
0.08
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.156
970707AG2-453 GEN
Solar/Wind Harmer
9.921
274862TOP CROP ;2U
Solar/Wind Harmer
0.405
958321AF2-126 GEN
Solar/Wind Harmer
1.148
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
274753CRETE EC ;3U
Adder
3.727
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.257
274807UNIV PK N;3U
Adder
2.252
274803UNIV PARK;6U
Adder
2.576
972038AH1-567 GEN2
Adder
0.161
276843GEN-1.7
Solar/Wind Harmer
0.099
962511AG1-100 GEN
Solar/Wind Helper
0.335
24190002OREGON_ST1
50/50
3.43
270246TR4_N_V150
Solar/Wind Harmer
0.024
965681AG1-436 GEN
Solar/Wind Harmer
4.24
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.327
203835AF1-098 GEN
Solar/Wind Helper
1.295
241801AE1-079 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.849
990527J1329
External Queue
1.7456159591674805
991177J1571 G
External Queue
14.7259521484375
991182J1586 G
External Queue
23.870176315307617
990142J1224
External Queue
12.760451316833496
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.204
NYPJM->LTFIMP_NY
CLTF
1.977
TVALTFEXP_TVA->PJM
CLTF
2.167
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.122
LGEELTFEXP_LGEE->PJM
CLTF
1.943
MECLTFEXP_MEC->PJM
CLTF
6.22
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.138
CPLELTFEXP_CPLE->PJM
CLTF
0.326
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.585
WECLTFEXP_WEC->PJM
CLTF
1.595
LAGNLTFEXP_LAGN->PJM
CLTF
4.772

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2176.69
MW Contribution:
0.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
246938BC-WTG3
Solar/Wind Harmer
0.156
945111AF1-176 GEN
Solar/Wind Harmer
3.312
270505AE1-170 C O1
Solar/Wind Harmer
4.285
965021AG1-366 GEN
Solar/Wind Harmer
1.297
23888702TROY G3
50/50
1.834
972253AH1-711 GEN
50/50
56.063
23860302FRMENG 3
50/50
3.522
241885AC2-103 GEN1
Solar/Wind Harmer
0
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
7.29
957891AF2-083 GEN
Solar/Wind Harmer
6.781
965011AG1-365 GEN
Solar/Wind Harmer
3.892
274751CRETE EC ;1U
Adder
3.998
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.627
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.116
274773LINCOLN ;4U
Adder
3.98
274774LINCOLN ;5U
Adder
3.98
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.661
970569AG2-363 GEN
Solar/Wind Harmer
9.379
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.127
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.326
939741AE1-205 GEN
Solar/Wind Harmer
4.273
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
254303AC2-168 GEN
Solar/Wind Helper
0.081
23920202STRYCT
50/50
2.05
943021AE2-325 GEN
Solar/Wind Harmer
2.178
970373AG2-245 GEN
Solar/Wind Harmer
7.327
971917AH1-482 GEN
Solar/Wind Harmer
4.378
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.523
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.371
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.138
971067AG2-660 GEN
Solar/Wind Harmer
1.046
274822ROCKFORD ;11
Adder
8.809
970819AG2-516 GEN
Solar/Wind Harmer
3.743
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276655WTG1_EQ
Solar/Wind Harmer
0
23929302BS-PKR
50/50
2.522
958321AF2-126 GEN
Solar/Wind Harmer
1.267
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
274753CRETE EC ;3U
Adder
3.998
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.421
274807UNIV PK N;3U
Adder
2.416
274803UNIV PARK;6U
Adder
2.764
972038AH1-567 GEN2
Adder
0.172
276843GEN-1.7
Solar/Wind Harmer
0.106
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.127
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.056
965931AG1-462 GEN
Solar/Wind Harmer
7.656
962511AG1-100 GEN
Solar/Wind Helper
0.367
203854AF2-039 C
Solar/Wind Helper
0.15
24189802OREGON_CT1
50/50
2.733
944231AF1-091 GEN
Solar/Wind Harmer
11.237
961051AF2-396 GEN
Solar/Wind Harmer
8.281
961051AF2-396 GEN
Solar/Wind Harmer
5.52
270247TR4_N_V136
Solar/Wind Harmer
0.026
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.432
274808UNIV PK N;4U
Adder
2.39
274674JOLIET 9 ;6U
Adder
7.191
958481AF2-142 GEN
Solar/Wind Harmer
4.831
274693ROCKY RD ;1P
Adder
5.056
274683WAUKEGAN ;8U
Adder
9.658
274683WAUKEGAN ;8U
Adder
8.141
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.129
274764LEE CO EC;5U
Adder
4.137
966841AG1-555 GEN
Solar/Wind Harmer
0.35
960971AF2-388 GEN
Solar/Wind Harmer
1.812
960611AF2-352 GEN
Solar/Wind Harmer
1.006
270599AE1-208 GEN
Solar/Wind Harmer
2.759
241967AE2-285_GEN
Solar/Wind Helper
0.363
254305AE2-115 C
Solar/Wind Helper
0.121
23856402BAYSG1
50/50
1.431
241858AF1-205_GEN
Solar/Wind Harmer
4.133
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.998
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.764
274732ELWOOD EC;7P
Adder
7.678
274674JOLIET 9 ;6U
Adder
7.191
939401AE1-172 GEN
Solar/Wind Harmer
2.38
962781AG1-127 GEN
Solar/Wind Harmer
3.022
274766LEE CO EC;7U
Adder
4.078
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.109
203947AF1-006 C
Solar/Wind Helper
0.409
203855AF2-088 C
Solar/Wind Helper
0.072
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
5.343
270499AE1-146 GEN
Solar/Wind Harmer
0.024
965041AG1-368 GEN
Solar/Wind Harmer
4.077
959331AF2-224 GEN
Solar/Wind Harmer
2.724
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274776LINCOLN ;7U
Adder
3.98
274687WILL CNTY;4U
Adder
13.101
274687WILL CNTY;4U
Adder
13.101
274731ELWOOD EC;2P
Adder
7.678
274733ELWOOD EC;3P
Adder
7.678
274746AC1-111 G10
Adder
2.582
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.314
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.492
241982AE2-343 S C
Solar/Wind Helper
0.127
20334926Z1-069 C
Solar/Wind Helper
0.691
270361_3
Solar/Wind Harmer
5.343
945641AF1-229 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
2.027
970031AG2-029 GEN
Solar/Wind Harmer
2.141
270377AD1-106 GEN
Solar/Wind Harmer
1.42
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.96
960591AF2-350 GEN
Solar/Wind Harmer
3.292
274775LINCOLN ;6U
Adder
3.98
274777LINCOLN ;8U
Adder
3.98
972228AH1-698 GEN2
Adder
1.742
274675JOLIET 29;7U
Adder
14.356
274675JOLIET 29;7U
Adder
13.843
970833AG2-524 GEN
Solar/Wind Harmer
3.567
970833AG2-524 GEN
Solar/Wind Harmer
2.378
971411AH1-196 GEN
Solar/Wind Harmer
4.73
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.276
274823ROCKFORD ;21
Adder
8.745
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.835
946321AF1-296 GEN
Solar/Wind Harmer
1.688
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
23867002DVBSG1
50/50
12.651
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
274805UNIV PK N;1U
Adder
2.405
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
970941AG2-585 GEN
Solar/Wind Harmer
1.81
274770LINCOLN ;1U
Adder
3.98
274771LINCOLN ;2U
Adder
3.98
942221AE2-234 GEN
Solar/Wind Harmer
1.321
276897AD1-100 C
Solar/Wind Harmer
8.153
276893AG1-478 C
Solar/Wind Harmer
0.217
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.226
274697ROCKY RD ;3P
Adder
1.387
962691AG1-118 GEN
Solar/Wind Harmer
9.543
938861AE1-114 GEN
Solar/Wind Harmer
1.758
274762LEE CO EC;3U
Adder
4.127
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
25326509SID D
Adder
0.577
942111AE2-223 GEN
Solar/Wind Harmer
0.992
962101AG1-054 GEN
Solar/Wind Helper
0.35
24190002OREGON_ST1
50/50
3.601
270246TR4_N_V150
Solar/Wind Harmer
0.026
965681AG1-436 GEN
Solar/Wind Harmer
4.545
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.276
971343AH1-151 GEN
Solar/Wind Harmer
6.276
203835AF1-098 GEN
Solar/Wind Helper
1.417
241801AE1-079 GEN
Solar/Wind Helper
0.142
203804AE2-113_GEN
Solar/Wind Helper
0.929
203853AF1-134 C O1
Solar/Wind Helper
0.22
24189902OREGON_CT2
50/50
2.676
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
23906502RICHG2&3
Adder
1.422
965421AG1-410 GEN
Solar/Wind Harmer
12.893
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.087
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.4
274676JOLIET 29;8U
Adder
14.356
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.582
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.244
274828WAUKEGAN ;BP
Adder
5.062
957471AF2-041 GEN
Solar/Wind Harmer
9.414
965651AG1-433 GEN
Solar/Wind Harmer
0.906
274848CAMPGROVE;RU
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.348
203979AG1-198 GEN
Solar/Wind Helper
0.209
241966AE1-183 GEN
Solar/Wind Helper
0.139
23888802TROY G4
50/50
1.834
247620Y3-023
Adder
0.264
965791AG1-447 GEN
Solar/Wind Harmer
3.333
958011AF2-095 GEN
Solar/Wind Harmer
4.74
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.106
958491AF2-143 GEN
Solar/Wind Harmer
4.789
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.982
274765LEE CO EC;6U
Adder
4.137
274763LEE CO EC;4U
Adder
4.088
944541AF1-119 GEN
Solar/Wind Harmer
0.206
970329AG2-216 GEN
Solar/Wind Harmer
1.308
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.655
254304AE2-114 C
Solar/Wind Helper
0.121
940863AE2-074 GEN
Solar/Wind Helper
0.241
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.234
23888502TROY G1
50/50
1.834
23888602TROY G2
50/50
1.834
23860102FRMENG 1
50/50
1.736
23860202FRMENG 2
50/50
1.736
241886AC2-103 GEN2
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.511
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.876
971567AH1-282 GEN
Solar/Wind Harmer
2.938
270071AF1-092 GEN
Solar/Wind Harmer
6.531
274728ELWOOD EC;5P
Adder
7.678
970073AG2-061 GEN
Solar/Wind Harmer
1.064
24729505KEY G4
Adder
2.953
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
4.997
241985AE1-237 GEN
Solar/Wind Helper
0.141
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.811
274752CRETE EC ;2U
Adder
3.998
274826FISK ;BP
Adder
5.181
274887GEN-1.85
Solar/Wind Harmer
0.086
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.678
970707AG2-453 GEN
Solar/Wind Harmer
10.644
274862TOP CROP ;2U
Solar/Wind Harmer
0.435
944531AF1-118 GEN
Solar/Wind Harmer
14.371
276868AE1-113 GEN
Solar/Wind Harmer
0.635
274879MINONK ;1U
Solar/Wind Harmer
0.133
970781AG2-491 GEN
Solar/Wind Harmer
3.174
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.006
20398826ARMNA MT
Solar/Wind Helper
0.706
270043AE2-236 GEN
Solar/Wind Harmer
2.351
274724RIVER EC ;11
Adder
8.524
274772LINCOLN ;3U
Adder
3.98
972259AH1-714 GEN
Adder
8.934
274729ELWOOD EC;1P
Adder
7.678
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
970571AG2-364 GEN
Solar/Wind Harmer
6.253
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.524
270428AC2-015 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.147
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.55
963791AG1-232 GEN
Solar/Wind Harmer
4.856
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.672
274800UNIV PARK;3U
Adder
2.755
274801UNIV PARK;4U
Adder
2.755
972227AH1-698 GEN1
Adder
1.227
274735ELWOOD EC;4P
Adder
7.678
274744AC1-111 GEN8
Adder
2.582
970169AG2-114 GEN
Solar/Wind Harmer
3.121
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
959341AF2-225 GEN
Solar/Wind Harmer
3.205
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270588AE1-091_GEN
Solar/Wind Harmer
3.737
24695305TIMB G C
Solar/Wind Harmer
0.357
274811UNIV PK N;7U
Adder
2.4
276806AD2-047 C O1
Solar/Wind Harmer
1.865
274676JOLIET 29;8U
Adder
13.843
274734ELWOOD EC;8P
Adder
7.678
274736ELWOOD EC;9P
Adder
7.678
943121AE2-341 GEN
Solar/Wind Harmer
5.401
943591AF1-030 GEN
Solar/Wind Harmer
3.592
274682WAUKEGAN ;7U
Adder
8.244
959091AF2-200 GEN
Solar/Wind Harmer
6.276
274767LEE CO EC;8U
Adder
4.078
971087AG2-675 GEN
Solar/Wind Harmer
1.601
241997AF1-093 GEN
Solar/Wind Helper
0.139
990527J1329
External Queue
1.8514890670776367
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
990142J1224
External Queue
13.534384727478027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.219
WECLTFEXP_WEC->PJM
CLTF
1.711
LAGNLTFEXP_LAGN->PJM
CLTF
5.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.261
CPLELTFEXP_CPLE->PJM
CLTF
0.333
SIGELTFEXP_SIGE->PJM
CLTF
0.174
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.932
LGEELTFEXP_LGEE->PJM
CLTF
2.093
MECLTFEXP_MEC->PJM
CLTF
6.675
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.254
NYPJM->LTFIMP_NY
CLTF
2.163
TVALTFEXP_TVA->PJM
CLTF
2.325
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.49 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2168.95
MW Contribution:
0.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23920202STRYCT
50/50
2.052
943021AE2-325 GEN
Solar/Wind Harmer
2.181
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
274753CRETE EC ;3U
Adder
4.006
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.426
274807UNIV PK N;3U
Adder
2.421
274803UNIV PARK;6U
Adder
2.77
972038AH1-567 GEN2
Adder
0.173
276843GEN-1.7
Solar/Wind Harmer
0.107
24690905MDL-1G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.136
24386205FR-12G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.076
24189802OREGON_CT1
50/50
2.734
944231AF1-091 GEN
Solar/Wind Harmer
11.253
961051AF2-396 GEN
Solar/Wind Harmer
8.294
961051AF2-396 GEN
Solar/Wind Harmer
5.529
270247TR4_N_V136
Solar/Wind Harmer
0.026
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.442
274808UNIV PK N;4U
Adder
2.394
274674JOLIET 9 ;6U
Adder
7.206
958481AF2-142 GEN
Solar/Wind Harmer
4.841
274693ROCKY RD ;1P
Adder
5.066
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.132
274764LEE CO EC;5U
Adder
4.146
966841AG1-555 GEN
Solar/Wind Harmer
0.351
960971AF2-388 GEN
Solar/Wind Harmer
1.816
960611AF2-352 GEN
Solar/Wind Harmer
1.008
270599AE1-208 GEN
Solar/Wind Harmer
2.765
241967AE2-285_GEN
Solar/Wind Helper
0.362
254305AE2-115 C
Solar/Wind Helper
0.12
23856402BAYSG1
50/50
1.432
241858AF1-205_GEN
Solar/Wind Harmer
4.136
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
4.006
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.77
274732ELWOOD EC;7P
Adder
7.694
274674JOLIET 9 ;6U
Adder
7.206
939401AE1-172 GEN
Solar/Wind Harmer
2.385
962781AG1-127 GEN
Solar/Wind Harmer
3.029
274766LEE CO EC;7U
Adder
4.087
24385905FR-11G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.109
203947AF1-006 C
Solar/Wind Helper
0.409
203855AF2-088 C
Solar/Wind Helper
0.072
965931AG1-462 GEN
Solar/Wind Harmer
7.674
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
5.347
270499AE1-146 GEN
Solar/Wind Harmer
0.024
965041AG1-368 GEN
Solar/Wind Harmer
4.084
959331AF2-224 GEN
Solar/Wind Harmer
2.729
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274776LINCOLN ;7U
Adder
3.988
274687WILL CNTY;4U
Adder
13.128
274687WILL CNTY;4U
Adder
13.128
274731ELWOOD EC;2P
Adder
7.694
274733ELWOOD EC;3P
Adder
7.694
274746AC1-111 G10
Adder
2.587
946581AF1-322 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.317
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.493
241982AE2-343 S C
Solar/Wind Helper
0.127
270361_3
Solar/Wind Harmer
5.347
945641AF1-229 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
2.03
970031AG2-029 GEN
Solar/Wind Harmer
2.145
270377AD1-106 GEN
Solar/Wind Harmer
1.423
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.964
960591AF2-350 GEN
Solar/Wind Harmer
3.298
274775LINCOLN ;6U
Adder
3.988
274777LINCOLN ;8U
Adder
3.988
972228AH1-698 GEN2
Adder
1.746
23888702TROY G3
50/50
1.835
23867002DVBSG1
50/50
12.657
970621AG2-405 GEN
Solar/Wind Harmer
0.952
970623AG2-406 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
274805UNIV PK N;1U
Adder
2.41
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
970941AG2-585 GEN
Solar/Wind Harmer
1.814
274770LINCOLN ;1U
Adder
3.988
274771LINCOLN ;2U
Adder
3.988
942221AE2-234 GEN
Solar/Wind Harmer
1.323
276897AD1-100 C
Solar/Wind Harmer
8.17
276893AG1-478 C
Solar/Wind Harmer
0.218
957841AF2-078 GEN
Solar/Wind Harmer
0
274697ROCKY RD ;3P
Adder
1.39
274696ROCKY RD ;4P
Adder
5.238
962691AG1-118 GEN
Solar/Wind Harmer
9.563
938861AE1-114 GEN
Solar/Wind Harmer
1.762
274762LEE CO EC;3U
Adder
4.136
24387305FR-4G C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.497
25326509SID D
Adder
0.579
942111AE2-223 GEN
Solar/Wind Harmer
0.994
962101AG1-054 GEN
Solar/Wind Helper
0.349
24190002OREGON_ST1
50/50
3.603
270246TR4_N_V150
Solar/Wind Harmer
0.026
965681AG1-436 GEN
Solar/Wind Harmer
4.554
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.352
276901AD2-066 C O1
Solar/Wind Harmer
0
24189902OREGON_CT2
50/50
2.678
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
23906502RICHG2&3
Adder
1.423
965421AG1-410 GEN
Solar/Wind Harmer
12.914
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.405
274676JOLIET 29;8U
Adder
14.386
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.587
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.262
274828WAUKEGAN ;BP
Adder
5.073
957471AF2-041 GEN
Solar/Wind Harmer
9.434
965651AG1-433 GEN
Solar/Wind Harmer
0.908
274848CAMPGROVE;RU
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.347
203979AG1-198 GEN
Solar/Wind Helper
0.208
241966AE1-183 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.69
23888802TROY G4
50/50
1.835
247620Y3-023
Adder
0.264
965791AG1-447 GEN
Solar/Wind Harmer
3.34
958011AF2-095 GEN
Solar/Wind Harmer
4.75
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.117
958491AF2-143 GEN
Solar/Wind Harmer
4.799
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
0.984
274765LEE CO EC;6U
Adder
4.146
274763LEE CO EC;4U
Adder
4.097
944541AF1-119 GEN
Solar/Wind Harmer
0.207
970329AG2-216 GEN
Solar/Wind Harmer
1.311
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.659
254304AE2-114 C
Solar/Wind Helper
0.12
940863AE2-074 GEN
Solar/Wind Helper
0.24
946381AF1-302 GEN
Solar/Wind Helper
0.112
203954AE2-126 C
Solar/Wind Helper
0.233
972253AH1-711 GEN
50/50
56.096
23860302FRMENG 3
50/50
3.525
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
7.302
957891AF2-083 GEN
Solar/Wind Harmer
6.792
965011AG1-365 GEN
Solar/Wind Harmer
3.899
274751CRETE EC ;1U
Adder
4.006
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.645
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.124
274773LINCOLN ;4U
Adder
3.988
274774LINCOLN ;5U
Adder
3.988
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.664
970569AG2-363 GEN
Solar/Wind Harmer
9.4
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.136
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.329
939741AE1-205 GEN
Solar/Wind Harmer
4.283
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.613
961971AG1-040 GEN
Solar/Wind Helper
0.358
254303AC2-168 GEN
Solar/Wind Helper
0.081
274675JOLIET 29;7U
Adder
14.386
274675JOLIET 29;7U
Adder
13.872
970833AG2-524 GEN
Solar/Wind Harmer
3.575
970833AG2-524 GEN
Solar/Wind Harmer
2.383
971411AH1-196 GEN
Solar/Wind Harmer
4.74
971675AH1-338 GEN
Solar/Wind Harmer
1.231
971171AH1-044 GEN
Solar/Wind Harmer
6.289
274823ROCKFORD ;21
Adder
8.764
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.839
946321AF1-296 GEN
Solar/Wind Harmer
1.692
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
246938BC-WTG3
Solar/Wind Harmer
0.157
945111AF1-176 GEN
Solar/Wind Harmer
3.317
270505AE1-170 C O1
Solar/Wind Harmer
4.292
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.355
274724RIVER EC ;11
Adder
8.542
274772LINCOLN ;3U
Adder
3.988
972259AH1-714 GEN
Adder
8.953
274729ELWOOD EC;1P
Adder
7.694
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
970571AG2-364 GEN
Solar/Wind Harmer
6.267
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.534
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.814
274752CRETE EC ;2U
Adder
4.006
274826FISK ;BP
Adder
5.192
274887GEN-1.85
Solar/Wind Harmer
0.086
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.667
274730ELWOOD EC;6P
Adder
7.694
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
944531AF1-118 GEN
Solar/Wind Harmer
14.401
276868AE1-113 GEN
Solar/Wind Harmer
0.637
274879MINONK ;1U
Solar/Wind Harmer
0.133
970781AG2-491 GEN
Solar/Wind Harmer
3.181
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
1.008
20398826ARMNA MT
Solar/Wind Helper
0.705
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270588AE1-091_GEN
Solar/Wind Harmer
3.742
24695305TIMB G C
Solar/Wind Harmer
0.357
274811UNIV PK N;7U
Adder
2.405
276806AD2-047 C O1
Solar/Wind Harmer
1.869
274676JOLIET 29;8U
Adder
13.872
274734ELWOOD EC;8P
Adder
7.694
274736ELWOOD EC;9P
Adder
7.694
943121AE2-341 GEN
Solar/Wind Harmer
5.412
943591AF1-030 GEN
Solar/Wind Harmer
3.599
274682WAUKEGAN ;7U
Adder
8.262
959091AF2-200 GEN
Solar/Wind Harmer
6.289
274767LEE CO EC;8U
Adder
4.087
971087AG2-675 GEN
Solar/Wind Harmer
1.605
247642Z2-115 C
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
7.341
971917AH1-482 GEN
Solar/Wind Harmer
4.387
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.524
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.371
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
3.145
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274822ROCKFORD ;11
Adder
8.828
970819AG2-516 GEN
Solar/Wind Harmer
3.751
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276655WTG1_EQ
Solar/Wind Harmer
0
23888502TROY G1
50/50
1.835
23888602TROY G2
50/50
1.835
23860102FRMENG 1
50/50
1.737
23860202FRMENG 2
50/50
1.737
971549AH1-272 GEN
Solar/Wind Harmer
10.525
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.882
971567AH1-282 GEN
Solar/Wind Harmer
2.943
270071AF1-092 GEN
Solar/Wind Harmer
6.544
274728ELWOOD EC;5P
Adder
7.694
970073AG2-061 GEN
Solar/Wind Harmer
1.066
24729505KEY G4
Adder
2.959
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
5.008
241886AC2-103 GEN2
Solar/Wind Helper
4.613
241985AE1-237 GEN
Solar/Wind Helper
0.141
270428AC2-015 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.147
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.551
963791AG1-232 GEN
Solar/Wind Harmer
4.865
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.679
274800UNIV PARK;3U
Adder
2.76
274801UNIV PARK;4U
Adder
2.76
972227AH1-698 GEN1
Adder
1.229
274735ELWOOD EC;4P
Adder
7.694
274744AC1-111 GEN8
Adder
2.587
970169AG2-114 GEN
Solar/Wind Harmer
3.128
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
959341AF2-225 GEN
Solar/Wind Harmer
3.212
241997AF1-093 GEN
Solar/Wind Helper
0.139
971341AH1-150 GEN
Solar/Wind Harmer
6.289
971343AH1-151 GEN
Solar/Wind Harmer
6.289
203835AF1-098 GEN
Solar/Wind Helper
1.415
241801AE1-079 GEN
Solar/Wind Helper
0.142
203804AE2-113_GEN
Solar/Wind Helper
0.927
962511AG1-100 GEN
Solar/Wind Helper
0.366
203854AF2-039 C
Solar/Wind Helper
0.15
990527J1329
External Queue
1.8514890670776367
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
990142J1224
External Queue
13.534384727478027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.396
NYPJM->LTFIMP_NY
CLTF
2.157
TVALTFEXP_TVA->PJM
CLTF
2.335
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.063
LGEELTFEXP_LGEE->PJM
CLTF
2.099
MECLTFEXP_MEC->PJM
CLTF
6.691
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.291
CPLELTFEXP_CPLE->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.175
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.256
WECLTFEXP_WEC->PJM
CLTF
1.715
LAGNLTFEXP_LAGN->PJM
CLTF
5.139

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
1.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
1.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
1.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944961AF1-161 GEN
50/50
4.124
270043AE2-236 GEN
Solar/Wind Harmer
6.765
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
10.472
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
274729ELWOOD EC;1P
Adder
21.939
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
970571AG2-364 GEN
Solar/Wind Harmer
17.631
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
942481AE2-261 GEN
Solar/Wind Harmer
22.758
270240V3-007_GEN2
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.277
24643105BUCHANAN
50/50
0.018
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.061
274808UNIV PK N;4U
Adder
6.766
944231AF1-091 GEN
Solar/Wind Harmer
21.57
274674JOLIET 9 ;6U
Adder
20.564
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274693ROCKY RD ;1P
Adder
14.449
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
274764LEE CO EC;5U
Adder
11.687
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
966841AG1-555 GEN
Solar/Wind Harmer
0.946
24725505WLD G2 C
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.081
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.401
945391AF1-204 GEN
Solar/Wind Harmer
7.788
24728905RICHG2
Adder
3.35
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
247620Y3-023
50/50
0.701
24721805FLATG3
50/50
4.711
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
970155AG2-107 GEN
Solar/Wind Harmer
69.947
270449AD2-020 GEN
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.412
274812UNIV PK N;8U
Adder
6.795
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
274828WAUKEGAN ;BP
Adder
14.44
957471AF2-041 GEN
Solar/Wind Harmer
26.735
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
23906502RICHG2&3
Adder
1.11
270100X2-052 CT1
50/50
2.104
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
274805UNIV PK N;1U
Adder
6.81
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
276893AG1-478 C
Solar/Wind Harmer
0.621
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
962691AG1-118 GEN
Solar/Wind Harmer
27.25
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274762LEE CO EC;3U
Adder
11.659
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
942111AE2-223 GEN
Solar/Wind Harmer
2.774
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
276838X2-022 GEN2
Solar/Wind Harmer
0.442
25326509SID D
Adder
1.142
24344105CKG2
50/50
11.483
970149AG2-104 GEN
Solar/Wind Harmer
59.152
943021AE2-325 GEN
Solar/Wind Harmer
5.166
970373AG2-245 GEN
Solar/Wind Harmer
19.884
941551AE2-152 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.848
970773AG2-487 GEN
Solar/Wind Harmer
1.192
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274776LINCOLN ;7U
Adder
11.612
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274746AC1-111 G10
Adder
7.404
926823AC1-168 GEN
Solar/Wind Harmer
1.499
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.381
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
944221AF1-090 GEN
Solar/Wind Harmer
4.314
270356AE2-297 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
247521TR3_G114
Solar/Wind Harmer
0.347
963791AG1-232 GEN
Solar/Wind Harmer
12.72
274827FISK ;RP
Adder
10.469
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
21.939
274744AC1-111 GEN8
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
8.815
276741O09 GEN1
Solar/Wind Harmer
0.306
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
959341AF2-225 GEN
Solar/Wind Harmer
8.961
970289AG2-191 GEN
Solar/Wind Harmer
1.58
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
970031AG2-029 GEN
Solar/Wind Harmer
5.461
274775LINCOLN ;6U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
965051AG1-369 GEN
Solar/Wind Harmer
4.782
972037AH1-567 GEN1
Adder
0.247
960591AF2-350 GEN
Solar/Wind Harmer
9.405
972228AH1-698 GEN2
Adder
4.989
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
971611AH1-305 GEN
Solar/Wind Harmer
5.334
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
945581AF1-223 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.171
946321AF1-296 GEN
Solar/Wind Harmer
4.723
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
971029AG2-637 GEN
Solar/Wind Harmer
10.609
270101X2-052 CT2
50/50
2.104
965791AG1-447 GEN
Solar/Wind Harmer
9.061
958011AF2-095 GEN
Solar/Wind Harmer
13.543
944541AF1-119 GEN
Solar/Wind Harmer
0.62
274695ROCKY RD ;2P
Adder
14.592
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.785
945421AF1-207 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
11.687
274763LEE CO EC;4U
Adder
11.55
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.65
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
19.599
971771AH1-392 GEN
Solar/Wind Harmer
10.022
24729505KEY G4
Adder
9.105
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274728ELWOOD EC;5P
Adder
21.94
971549AH1-272 GEN
Solar/Wind Harmer
19.166
970073AG2-061 GEN
Solar/Wind Harmer
3.016
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
971681AH1-341 GEN
Solar/Wind Harmer
14.132
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.181
24307105BERRINSP G
50/50
0.03
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.956
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
970825AG2-519 GEN
Solar/Wind Harmer
2.836
276621W2-048 GEN
Solar/Wind Harmer
0.393
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
109.537
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274754CRETE EC ;4U
Adder
11.245
274802UNIV PARK;5U
Adder
7.869
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.936
965911AG1-460 GEN
Solar/Wind Harmer
1.522
270437AC2-090 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.221
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
44.69
274752CRETE EC ;2U
Adder
11.245
970707AG2-453 GEN
Solar/Wind Harmer
30.807
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
21.94
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274857EASY ROAD;U1
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.8
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
270541AE2-072 C
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.483
24642205MAYFLWER
50/50
0.053
962601AG1-109 GEN
50/50
4.124
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274803UNIV PARK;6U
Adder
7.869
276843GEN-1.7
Solar/Wind Harmer
0.304
972038AH1-567 GEN2
Adder
0.492
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
11.659
24690905MDL-1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
965931AG1-462 GEN
Solar/Wind Harmer
21.395
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.752
24379505HDWTR1G C
Solar/Wind Harmer
0
24721705FLATG2
50/50
69.962
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.356
270246TR4_N_V150
Solar/Wind Harmer
0.061
276776AD2-060 GEN
Solar/Wind Harmer
1.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
247621Y3-024
Adder
0.272
276916AD2-100_GEN
Solar/Wind Harmer
15.862
971587AH1-292 GEN
Solar/Wind Harmer
4.757
270142AC1-141 CT1_
50/50
3.456
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
6.795
24695305TIMB G C
Solar/Wind Harmer
0.797
276806AD2-047 C O1
Solar/Wind Harmer
5.33
274676JOLIET 29;8U
Adder
39.574
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
274682WAUKEGAN ;7U
Adder
23.522
959091AF2-200 GEN
Solar/Wind Harmer
17.823
274767LEE CO EC;8U
Adder
11.522
247642Z2-115 C
Solar/Wind Harmer
0.003
971087AG2-675 GEN
Solar/Wind Harmer
4.475
970289AG2-191 GEN
Solar/Wind Harmer
0.915
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
24728505AND G1
Adder
3.831
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
WECLTFEXP_WEC->PJM
CLTF
4.845
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
SIGELTFEXP_SIGE->PJM
CLTF
0.416
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
LGEELTFEXP_LGEE->PJM
CLTF
4.556
MECLTFEXP_MEC->PJM
CLTF
18.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
NYPJM->LTFIMP_NY
CLTF
3.074
TVALTFEXP_TVA->PJM
CLTF
4.815
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5028.49
MW Contribution:
1.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24307105BERRINSP G
50/50
0.031
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
964861AG1-349 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
945371AF1-202 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
4.258
270043AE2-236 GEN
Solar/Wind Harmer
6.98
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
972259AH1-714 GEN
Adder
26.498
274729ELWOOD EC;1P
Adder
22.596
246938BC-WTG3
Solar/Wind Harmer
0.336
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
970571AG2-364 GEN
Solar/Wind Harmer
18.089
971993AH1-541 GEN
Solar/Wind Harmer
3.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
942481AE2-261 GEN
Solar/Wind Harmer
23.025
270240V3-007_GEN2
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.418
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274752CRETE EC ;2U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274826FISK ;BP
Adder
15.225
274887GEN-1.85
Solar/Wind Harmer
0.252
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
22.596
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
270102X2-052 ST
50/50
2.354
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
274808UNIV PK N;4U
Adder
6.974
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
944231AF1-091 GEN
Solar/Wind Harmer
21.933
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274693ROCKY RD ;1P
Adder
14.868
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
270462AD2-086
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
274764LEE CO EC;5U
Adder
11.991
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.858
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270599AE1-208 GEN
Solar/Wind Harmer
7.759
276615X2-022 GEN
Solar/Wind Harmer
0.083
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
970883AG2-550 GEN
Solar/Wind Harmer
7.172
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270142AC1-141 CT1_
50/50
3.573
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
7.005
276806AD2-047 C O1
Solar/Wind Harmer
5.492
274676JOLIET 29;8U
Adder
40.767
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
274682WAUKEGAN ;7U
Adder
24.202
959091AF2-200 GEN
Solar/Wind Harmer
18.31
274767LEE CO EC;8U
Adder
11.822
971087AG2-675 GEN
Solar/Wind Harmer
4.579
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
24721805FLATG3
50/50
5.165
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
970155AG2-107 GEN
Solar/Wind Harmer
76.664
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.005
274676JOLIET 29;8U
Adder
42.277
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
274828WAUKEGAN ;BP
Adder
14.856
957471AF2-041 GEN
Solar/Wind Harmer
27.465
274848CAMPGROVE;RU
Solar/Wind Harmer
0
247620Y3-023
50/50
0.723
270101X2-052 CT2
50/50
2.175
965791AG1-447 GEN
Solar/Wind Harmer
9.363
958011AF2-095 GEN
Solar/Wind Harmer
13.957
944541AF1-119 GEN
Solar/Wind Harmer
0.629
274695ROCKY RD ;2P
Adder
15.016
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.86
274765LEE CO EC;6U
Adder
11.991
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.656
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.056
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.391
24344105CKG2
50/50
11.949
970149AG2-104 GEN
Solar/Wind Harmer
64.832
943021AE2-325 GEN
Solar/Wind Harmer
5.335
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
23906502RICHG2&3
Adder
1.085
270100X2-052 CT1
50/50
2.175
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
276893AG1-478 C
Solar/Wind Harmer
0.639
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
942221AE2-234 GEN
Solar/Wind Harmer
3.701
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274762LEE CO EC;3U
Adder
11.963
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.698
276838X2-022 GEN2
Solar/Wind Harmer
0.449
970621AG2-405 GEN
Solar/Wind Harmer
1.408
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.17
971771AH1-392 GEN
Solar/Wind Harmer
10.358
24729505KEY G4
Adder
9.292
274728ELWOOD EC;5P
Adder
22.596
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
274735ELWOOD EC;4P
Adder
22.596
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.036
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
959341AF2-225 GEN
Solar/Wind Harmer
9.159
970289AG2-191 GEN
Solar/Wind Harmer
1.586
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.466
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
19.06
970773AG2-487 GEN
Solar/Wind Harmer
1.148
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274746AC1-111 G10
Adder
7.624
926823AC1-168 GEN
Solar/Wind Harmer
1.537
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
963841AG1-237 GEN
Solar/Wind Harmer
3.581
964611AG1-324 GEN
Solar/Wind Harmer
3.111
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270356AE2-297 GEN
Solar/Wind Harmer
0
24721705FLATG2
50/50
76.7
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.767
276776AD2-060 GEN
Solar/Wind Harmer
1.034
270246TR4_N_V150
Solar/Wind Harmer
0.062
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
970031AG2-029 GEN
Solar/Wind Harmer
5.617
274775LINCOLN ;6U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
972037AH1-567 GEN1
Adder
0.255
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
971611AH1-305 GEN
Solar/Wind Harmer
5.462
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
972267AH1-718 GEN
Adder
5.303
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.834
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.301
971029AG2-637 GEN
Solar/Wind Harmer
10.16
971549AH1-272 GEN
Solar/Wind Harmer
19.703
270435AC2-044 GEN
Solar/Wind Harmer
1.183
970073AG2-061 GEN
Solar/Wind Harmer
3.1
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
971681AH1-341 GEN
Solar/Wind Harmer
14.503
270007AE1-245 C
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.021
962761AG1-125 GEN
Solar/Wind Harmer
120.056
274754CRETE EC ;4U
Adder
11.595
274802UNIV PARK;5U
Adder
8.11
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
274766LEE CO EC;7U
Adder
11.822
276708O09 GEN2
Solar/Wind Harmer
0.313
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.916
965911AG1-460 GEN
Solar/Wind Harmer
1.54
270437AC2-090 C
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.024
24642205MAYFLWER
50/50
0.054
962601AG1-109 GEN
50/50
4.258
274753CRETE EC ;3U
Adder
11.595
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274803UNIV PARK;6U
Adder
8.11
972038AH1-567 GEN2
Adder
0.507
276843GEN-1.7
Solar/Wind Harmer
0.313
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274760LEE CO EC;1U
Adder
11.963
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
21.892
965091AG1-374 GEN
Solar/Wind Harmer
25.724
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.741
24379505HDWTR1G C
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
959611AF2-252 GEN
Solar/Wind Harmer
2.858
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
270541AE2-072 C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
16.036
971587AH1-292 GEN
Solar/Wind Harmer
4.706
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
WECLTFEXP_WEC->PJM
CLTF
4.975
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
SIGELTFEXP_SIGE->PJM
CLTF
0.4
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
LGEELTFEXP_LGEE->PJM
CLTF
4.166
MECLTFEXP_MEC->PJM
CLTF
18.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
NYPJM->LTFIMP_NY
CLTF
2.987
TVALTFEXP_TVA->PJM
CLTF
4.573
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.28 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5040.8
MW Contribution:
1.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
970031AG2-029 GEN
Solar/Wind Harmer
5.617
274775LINCOLN ;6U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
972037AH1-567 GEN1
Adder
0.255
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
971611AH1-305 GEN
Solar/Wind Harmer
5.462
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
24307105BERRINSP G
50/50
0.031
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
964861AG1-349 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
945371AF1-202 GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
4.258
270043AE2-236 GEN
Solar/Wind Harmer
6.98
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
972259AH1-714 GEN
Adder
26.498
274729ELWOOD EC;1P
Adder
22.596
246938BC-WTG3
Solar/Wind Harmer
0.336
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
970571AG2-364 GEN
Solar/Wind Harmer
18.089
971993AH1-541 GEN
Solar/Wind Harmer
3.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
942481AE2-261 GEN
Solar/Wind Harmer
23.025
270240V3-007_GEN2
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.418
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274752CRETE EC ;2U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274826FISK ;BP
Adder
15.225
274887GEN-1.85
Solar/Wind Harmer
0.252
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
22.596
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
959611AF2-252 GEN
Solar/Wind Harmer
2.858
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
270541AE2-072 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.354
24643105BUCHANAN
50/50
0.019
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
274808UNIV PK N;4U
Adder
6.974
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
944231AF1-091 GEN
Solar/Wind Harmer
21.933
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274693ROCKY RD ;1P
Adder
14.868
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
270462AD2-086
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
274764LEE CO EC;5U
Adder
11.991
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.858
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270599AE1-208 GEN
Solar/Wind Harmer
7.759
276615X2-022 GEN
Solar/Wind Harmer
0.083
24725505WLD G2 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
970883AG2-550 GEN
Solar/Wind Harmer
7.172
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270142AC1-141 CT1_
50/50
3.573
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274811UNIV PK N;7U
Adder
7.005
276806AD2-047 C O1
Solar/Wind Harmer
5.492
274676JOLIET 29;8U
Adder
40.767
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
274682WAUKEGAN ;7U
Adder
24.202
959091AF2-200 GEN
Solar/Wind Harmer
18.31
274767LEE CO EC;8U
Adder
11.822
971087AG2-675 GEN
Solar/Wind Harmer
4.579
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
24721805FLATG3
50/50
5.165
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
970155AG2-107 GEN
Solar/Wind Harmer
76.664
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.005
274676JOLIET 29;8U
Adder
42.277
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
274828WAUKEGAN ;BP
Adder
14.856
957471AF2-041 GEN
Solar/Wind Harmer
27.465
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
23906502RICHG2&3
Adder
1.085
247620Y3-023
50/50
0.723
270101X2-052 CT2
50/50
2.175
965791AG1-447 GEN
Solar/Wind Harmer
9.363
958011AF2-095 GEN
Solar/Wind Harmer
13.957
944541AF1-119 GEN
Solar/Wind Harmer
0.629
274695ROCKY RD ;2P
Adder
15.016
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.86
274765LEE CO EC;6U
Adder
11.991
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
4.656
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
24699105WLD G1 C
Solar/Wind Harmer
0
276911AD2-131_GEN
Solar/Wind Harmer
1.056
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.391
24344105CKG2
50/50
11.949
970149AG2-104 GEN
Solar/Wind Harmer
64.832
943021AE2-325 GEN
Solar/Wind Harmer
5.335
970373AG2-245 GEN
Solar/Wind Harmer
20.466
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
276655WTG1_EQ
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
19.06
970773AG2-487 GEN
Solar/Wind Harmer
1.148
270100X2-052 CT1
50/50
2.175
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
276893AG1-478 C
Solar/Wind Harmer
0.639
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
942221AE2-234 GEN
Solar/Wind Harmer
3.701
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274762LEE CO EC;3U
Adder
11.963
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
24387305FR-4G C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.698
276838X2-022 GEN2
Solar/Wind Harmer
0.449
970621AG2-405 GEN
Solar/Wind Harmer
1.408
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.17
971771AH1-392 GEN
Solar/Wind Harmer
10.358
24729505KEY G4
Adder
9.292
274728ELWOOD EC;5P
Adder
22.596
971549AH1-272 GEN
Solar/Wind Harmer
19.703
270435AC2-044 GEN
Solar/Wind Harmer
1.183
970073AG2-061 GEN
Solar/Wind Harmer
3.1
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
971681AH1-341 GEN
Solar/Wind Harmer
14.503
270007AE1-245 C
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.021
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
274735ELWOOD EC;4P
Adder
22.596
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
9.036
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
959341AF2-225 GEN
Solar/Wind Harmer
9.159
970289AG2-191 GEN
Solar/Wind Harmer
1.586
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274746AC1-111 G10
Adder
7.624
926823AC1-168 GEN
Solar/Wind Harmer
1.537
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
963841AG1-237 GEN
Solar/Wind Harmer
3.581
964611AG1-324 GEN
Solar/Wind Harmer
3.111
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270356AE2-297 GEN
Solar/Wind Harmer
0
24721705FLATG2
50/50
76.7
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
12.767
276776AD2-060 GEN
Solar/Wind Harmer
1.034
270246TR4_N_V150
Solar/Wind Harmer
0.062
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
16.036
971587AH1-292 GEN
Solar/Wind Harmer
4.706
972267AH1-718 GEN
Adder
5.303
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.834
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.301
971029AG2-637 GEN
Solar/Wind Harmer
10.16
962761AG1-125 GEN
Solar/Wind Harmer
120.056
274754CRETE EC ;4U
Adder
11.595
274802UNIV PARK;5U
Adder
8.11
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
274766LEE CO EC;7U
Adder
11.822
276708O09 GEN2
Solar/Wind Harmer
0.313
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.916
965911AG1-460 GEN
Solar/Wind Harmer
1.54
270437AC2-090 C
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
10.024
24642205MAYFLWER
50/50
0.054
962601AG1-109 GEN
50/50
4.258
274753CRETE EC ;3U
Adder
11.595
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274803UNIV PARK;6U
Adder
8.11
972038AH1-567 GEN2
Adder
0.507
276843GEN-1.7
Solar/Wind Harmer
0.313
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
274760LEE CO EC;1U
Adder
11.963
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
21.892
965091AG1-374 GEN
Solar/Wind Harmer
25.724
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.741
24379505HDWTR1G C
Solar/Wind Harmer
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
NYPJM->LTFIMP_NY
CLTF
2.987
TVALTFEXP_TVA->PJM
CLTF
4.573
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
LGEELTFEXP_LGEE->PJM
CLTF
4.166
MECLTFEXP_MEC->PJM
CLTF
18.423
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
SIGELTFEXP_SIGE->PJM
CLTF
0.4
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
WECLTFEXP_WEC->PJM
CLTF
4.975
LAGNLTFEXP_LAGN->PJM
CLTF
11.172

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
1.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24643105BUCHANAN
50/50
0.016
960971AF2-388 GEN
Solar/Wind Harmer
7.331
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270247TR4_N_V136
Solar/Wind Harmer
0.065
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
274808UNIV PK N;4U
Adder
5.568
274674JOLIET 9 ;6U
Adder
16.683
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274693ROCKY RD ;1P
Adder
11.662
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
24697605MDL-3G C
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.583
966841AG1-555 GEN
Solar/Wind Harmer
0.805
274764LEE CO EC;5U
Adder
9.425
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
270143AC1-141 CT2_
50/50
3.096
965651AG1-433 GEN
Solar/Wind Harmer
3.666
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270449AD2-020 GEN
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.593
274676JOLIET 29;8U
Adder
33.312
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
957471AF2-041 GEN
Solar/Wind Harmer
21.562
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
23906502RICHG2&3
Adder
0.869
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
960851AF2-376 GEN
50/50
3.277
942221AE2-234 GEN
Solar/Wind Harmer
4.522
970623AG2-406 GEN
Solar/Wind Harmer
1.54
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
24727005RPMNG1
50/50
1.308
943021AE2-325 GEN
Solar/Wind Harmer
4.637
970373AG2-245 GEN
Solar/Wind Harmer
16.897
971917AH1-482 GEN
Solar/Wind Harmer
10.122
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970819AG2-516 GEN
Solar/Wind Harmer
8.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276655WTG1_EQ
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270144AC1-141 ST1_
50/50
2.734
959331AF2-224 GEN
Solar/Wind Harmer
8.919
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
964611AG1-324 GEN
Solar/Wind Harmer
3.62
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
9.292
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274746AC1-111 G10
Adder
5.972
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
926823AC1-168 GEN
Solar/Wind Harmer
1.213
276726Z2-087_GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
945411AF1-206 GEN
Solar/Wind Harmer
0
24727205RPMNG3
50/50
1.301
963791AG1-232 GEN
Solar/Wind Harmer
15.281
247521TR3_G114
Solar/Wind Harmer
0.367
970289AG2-191 GEN
Solar/Wind Harmer
1.684
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
8.547
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
972227AH1-698 GEN1
Adder
2.852
274735ELWOOD EC;4P
Adder
17.808
274744AC1-111 GEN8
Adder
5.972
970169AG2-114 GEN
Solar/Wind Harmer
7.144
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
959341AF2-225 GEN
Solar/Wind Harmer
7.282
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.276
276615X2-022 GEN
Solar/Wind Harmer
0.066
945391AF1-204 GEN
Solar/Wind Harmer
6.631
24728905RICHG2
Adder
3.1
270054AF2-122 C O1
Solar/Wind Helper
0.78
24641605TWIN BRNCH
50/50
0.023
970031AG2-029 GEN
Solar/Wind Harmer
6.248
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
5.063
247536S-71 GEN
Solar/Wind Harmer
0.341
972037AH1-567 GEN1
Adder
0.202
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274675JOLIET 29;7U
Adder
33.312
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
944541AF1-119 GEN
Solar/Wind Harmer
0.834
270031AE2-169
Solar/Wind Harmer
5.613
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
7.678
270383AD1-128 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
2.649
958011AF2-095 GEN
Solar/Wind Harmer
11.028
945421AF1-207 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.777
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
2.246
274765LEE CO EC;6U
Adder
9.425
274763LEE CO EC;4U
Adder
9.314
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
24729505KEY G4
50/50
13.443
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.488
971771AH1-392 GEN
Solar/Wind Harmer
8.998
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
274675JOLIET 29;7U
Adder
32.122
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
971029AG2-637 GEN
Solar/Wind Harmer
10.958
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.17
946321AF1-296 GEN
Solar/Wind Harmer
3.807
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.536
274754CRETE EC ;4U
Adder
9.326
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.433
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
964571AG1-320 GEN
Solar/Wind Harmer
2.864
946101AF1-275 GEN
Solar/Wind Helper
0.301
24385905FR-11G C
Solar/Wind Harmer
0
274766LEE CO EC;7U
Adder
9.292
276708O09 GEN2
Solar/Wind Harmer
0.247
965911AG1-460 GEN
Solar/Wind Harmer
1.24
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270520AE2-214 GEN
Solar/Wind Helper
1.202
970583AG2-370 GEN
50/50
3.653
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270063AE2-323 C
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
4.396
274752CRETE EC ;2U
Adder
9.326
274826FISK ;BP
Adder
12.06
274887GEN-1.85
Solar/Wind Harmer
0.199
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
274730ELWOOD EC;6P
Adder
17.809
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
970193AG2-126 GEN
Solar/Wind Harmer
9.362
270541AE2-072 C
Solar/Wind Harmer
0
270287AF1-227 GEN3
Solar/Wind Helper
0.431
24642205MAYFLWER
50/50
0.047
962601AG1-109 GEN
50/50
3.701
270004AE1-209 GEN
Solar/Wind Harmer
2.117
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274753CRETE EC ;3U
Adder
9.326
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274803UNIV PARK;6U
Adder
6.433
972038AH1-567 GEN2
Adder
0.401
276843GEN-1.7
Solar/Wind Harmer
0.248
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
965931AG1-462 GEN
Solar/Wind Harmer
17.242
958321AF2-126 GEN
Solar/Wind Harmer
0.443
960861AF2-377 GEN
50/50
3.382
965011AG1-365 GEN
Solar/Wind Harmer
12.741
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
274751CRETE EC ;1U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
964861AG1-349 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
970569AG2-363 GEN
Solar/Wind Harmer
21.445
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
939741AE1-205 GEN
Solar/Wind Harmer
9.71
276621W2-048 GEN
Solar/Wind Harmer
0.32
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
274728ELWOOD EC;5P
Adder
17.809
970073AG2-061 GEN
Solar/Wind Harmer
2.45
24691005MDL-2G C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
971681AH1-341 GEN
Solar/Wind Harmer
11.398
276893AG1-478 C
Solar/Wind Harmer
0.504
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
12.055
274697ROCKY RD ;3P
Adder
3.199
962691AG1-118 GEN
Solar/Wind Harmer
21.97
24387305FR-4G C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274762LEE CO EC;3U
Adder
9.403
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276838X2-022 GEN2
Solar/Wind Harmer
0.361
970621AG2-405 GEN
Solar/Wind Harmer
1.034
944961AF1-161 GEN
50/50
3.701
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
274724RIVER EC ;11
Adder
19.931
274772LINCOLN ;3U
Adder
9.292
972259AH1-714 GEN
Adder
20.761
274729ELWOOD EC;1P
Adder
17.808
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
970571AG2-364 GEN
Solar/Wind Harmer
14.297
971993AH1-541 GEN
Solar/Wind Harmer
3.006
942481AE2-261 GEN
Solar/Wind Harmer
18.539
247621Y3-024
50/50
0.324
270246TR4_N_V150
Solar/Wind Harmer
0.065
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
965681AG1-436 GEN
Solar/Wind Harmer
10.47
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.817
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
276916AD2-100_GEN
Solar/Wind Harmer
12.922
971587AH1-292 GEN
Solar/Wind Harmer
3.867
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24695305TIMB G C
Solar/Wind Harmer
0.832
946031AF1-268 GEN
Solar/Wind Harmer
8.826
970289AG2-191 GEN
Solar/Wind Harmer
0.975
247642Z2-115 C
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
5.593
276806AD2-047 C O1
Solar/Wind Harmer
4.34
274676JOLIET 29;8U
Adder
32.122
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274682WAUKEGAN ;7U
Adder
19.011
959091AF2-200 GEN
Solar/Wind Harmer
14.375
274767LEE CO EC;8U
Adder
9.292
24728505AND G1
Adder
3.747
971087AG2-675 GEN
Solar/Wind Harmer
3.606
957381AF2-032 GEN
Solar/Wind Harmer
1.409
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270284AF1-227 GEN1
Solar/Wind Helper
1.175
990792J1392
External Queue
6.545727729797363
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
NYPJM->LTFIMP_NY
CLTF
1.989
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
SIGELTFEXP_SIGE->PJM
CLTF
0.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
WECLTFEXP_WEC->PJM
CLTF
3.91
MECLTFEXP_MEC->PJM
CLTF
14.518
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
LGEELTFEXP_LGEE->PJM
CLTF
3.263
TVALTFEXP_TVA->PJM
CLTF
3.331
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-810_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-810_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.63 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:1863.35
MW Contribution:
0.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
246938BC-WTG3
Solar/Wind Harmer
0.144
24189802OREGON_CT1
50/50
2.72
944231AF1-091 GEN
Solar/Wind Harmer
10.325
961051AF2-396 GEN
Solar/Wind Harmer
7.798
961051AF2-396 GEN
Solar/Wind Harmer
5.199
270247TR4_N_V136
Solar/Wind Harmer
0.024
270462AD2-086
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
5.092
274808UNIV PK N;4U
Adder
2.237
274674JOLIET 9 ;6U
Adder
6.727
958481AF2-142 GEN
Solar/Wind Harmer
4.518
241967AE2-285_GEN
Solar/Wind Helper
0.33
254305AE2-115 C
Solar/Wind Helper
0.11
24189902OREGON_CT2
50/50
2.663
23906502RICHG2&3
Adder
1.287
965421AG1-410 GEN
Solar/Wind Harmer
11.848
270449AD2-020 GEN
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.247
274676JOLIET 29;8U
Adder
13.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.415
276694AA1-018 GEN2
Solar/Wind Harmer
0
203830AF1-094 GEN
Solar/Wind Helper
0.315
203979AG1-198 GEN
Solar/Wind Helper
0.189
241966AE1-183 GEN
Solar/Wind Helper
0.127
241807AE2-176_GEN
Solar/Wind Helper
0.77
945111AF1-176 GEN
Solar/Wind Harmer
3.116
270505AE1-170 C O1
Solar/Wind Harmer
4.034
965021AG1-366 GEN
Solar/Wind Harmer
1.2
270043AE2-236 GEN
Solar/Wind Harmer
2.186
23867002DVBSG1
50/50
13.913
970621AG2-405 GEN
Solar/Wind Harmer
0.843
970623AG2-406 GEN
Solar/Wind Harmer
0.779
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.161
274805UNIV PK N;1U
Adder
2.251
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
970941AG2-585 GEN
Solar/Wind Harmer
1.694
274770LINCOLN ;1U
Adder
3.724
274771LINCOLN ;2U
Adder
3.724
276897AD1-100 C
Solar/Wind Harmer
7.627
276893AG1-478 C
Solar/Wind Harmer
0.203
942221AE2-234 GEN
Solar/Wind Harmer
1.222
957841AF2-078 GEN
Solar/Wind Harmer
0
962101AG1-054 GEN
Solar/Wind Helper
0.319
23920202STRYCT
50/50
1.866
943021AE2-325 GEN
Solar/Wind Harmer
2.052
970373AG2-245 GEN
Solar/Wind Harmer
6.865
971917AH1-482 GEN
Solar/Wind Harmer
4.098
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274861TOP CROP ;1U
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
270575GUS2 35KV
Solar/Wind Harmer
4.19
270499AE1-146 GEN
Solar/Wind Harmer
0.019
965041AG1-368 GEN
Solar/Wind Harmer
3.74
959331AF2-224 GEN
Solar/Wind Harmer
2.52
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.22
274776LINCOLN ;7U
Adder
3.724
274687WILL CNTY;4U
Adder
12.257
274687WILL CNTY;4U
Adder
12.257
274731ELWOOD EC;2P
Adder
7.182
274733ELWOOD EC;3P
Adder
7.182
274746AC1-111 G10
Adder
2.415
241982AE2-343 S C
Solar/Wind Helper
0.115
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.135
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.5
963791AG1-232 GEN
Solar/Wind Harmer
4.485
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.436
274800UNIV PARK;3U
Adder
2.578
274801UNIV PARK;4U
Adder
2.578
972227AH1-698 GEN1
Adder
1.148
274735ELWOOD EC;4P
Adder
7.182
274744AC1-111 GEN8
Adder
2.415
241997AF1-093 GEN
Solar/Wind Helper
0.127
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.19
965051AG1-369 GEN
Solar/Wind Harmer
1.855
970031AG2-029 GEN
Solar/Wind Harmer
2
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.081
960591AF2-350 GEN
Solar/Wind Harmer
3.08
274775LINCOLN ;6U
Adder
3.724
274777LINCOLN ;8U
Adder
3.724
971611AH1-305 GEN
Solar/Wind Harmer
1.833
972228AH1-698 GEN2
Adder
1.63
274675JOLIET 29;7U
Adder
13.43
274675JOLIET 29;7U
Adder
12.951
970833AG2-524 GEN
Solar/Wind Harmer
3.336
970833AG2-524 GEN
Solar/Wind Harmer
2.224
203846AF2-130 C
Solar/Wind Helper
0.241
23888802TROY G4
50/50
1.792
247620Y3-023
Adder
0.247
965791AG1-447 GEN
Solar/Wind Harmer
3.127
958011AF2-095 GEN
Solar/Wind Harmer
4.435
945421AF1-207 GEN
Solar/Wind Harmer
0
254304AE2-114 C
Solar/Wind Helper
0.11
940863AE2-074 GEN
Solar/Wind Helper
0.219
946381AF1-302 GEN
Solar/Wind Helper
0.102
23888502TROY G1
50/50
1.792
23888602TROY G2
50/50
1.792
241886AC2-103 GEN2
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
9.982
270007AE1-245 C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.505
971771AH1-392 GEN
Solar/Wind Harmer
3.641
971567AH1-282 GEN
Solar/Wind Harmer
2.604
270071AF1-092 GEN
Solar/Wind Harmer
6.065
274728ELWOOD EC;5P
Adder
7.183
241985AE1-237 GEN
Solar/Wind Helper
0.129
23888702TROY G3
50/50
1.792
972253AH1-711 GEN
50/50
54.784
241885AC2-103 GEN1
Solar/Wind Harmer
0
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.161
270489AE1-102 GEN1
Solar/Wind Harmer
0.518
945111AF1-176 GEN
Solar/Wind Harmer
6.86
957891AF2-083 GEN
Solar/Wind Harmer
6.382
965011AG1-365 GEN
Solar/Wind Harmer
3.6
274751CRETE EC ;1U
Adder
3.743
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.076
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.724
274774LINCOLN ;5U
Adder
3.724
971605AH1-302 GEN
Solar/Wind Harmer
3.849
23856402BAYSG1
50/50
1.206
241858AF1-205_GEN
Solar/Wind Harmer
3.755
270317AD1-130_GEN
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
3.743
958381AF2-132 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
2.586
274732ELWOOD EC;7P
Adder
7.183
274674JOLIET 9 ;6U
Adder
6.727
203947AF1-006 C
Solar/Wind Helper
0.37
270541AE2-072 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
1.697
270391AF1-285 GEN3
Solar/Wind Harmer
0.22
274752CRETE EC ;2U
Adder
3.743
274826FISK ;BP
Adder
4.848
274887GEN-1.85
Solar/Wind Harmer
0.08
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.183
970707AG2-453 GEN
Solar/Wind Harmer
9.957
274862TOP CROP ;2U
Solar/Wind Harmer
0.407
23929302BS-PKR
50/50
2.125
958321AF2-126 GEN
Solar/Wind Harmer
1.109
270491AE1-102 GEN2
Solar/Wind Harmer
0.518
274753CRETE EC ;3U
Adder
3.743
964401AG1-302 GEN
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274803UNIV PARK;6U
Adder
2.586
972038AH1-567 GEN2
Adder
0.161
276843GEN-1.7
Solar/Wind Harmer
0.1
962511AG1-100 GEN
Solar/Wind Helper
0.332
961971AG1-040 GEN
Solar/Wind Helper
0.325
254303AC2-168 GEN
Solar/Wind Helper
0.074
274724RIVER EC ;11
Adder
7.979
274772LINCOLN ;3U
Adder
3.724
972259AH1-714 GEN
Adder
8.358
274729ELWOOD EC;1P
Adder
7.182
24190002OREGON_ST1
50/50
3.583
270246TR4_N_V150
Solar/Wind Harmer
0.024
965681AG1-436 GEN
Solar/Wind Harmer
4.265
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.329
203835AF1-098 GEN
Solar/Wind Helper
1.282
241801AE1-079 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.843
23906402RICHG1
Adder
1.29
23906502RICHG2&3
Adder
1.287
270588AE1-091_GEN
Solar/Wind Harmer
3.186
24695305TIMB G C
Solar/Wind Harmer
0.325
274811UNIV PK N;7U
Adder
2.247
276806AD2-047 C O1
Solar/Wind Harmer
1.745
274676JOLIET 29;8U
Adder
12.951
274734ELWOOD EC;8P
Adder
7.183
274736ELWOOD EC;9P
Adder
7.183
943121AE2-341 GEN
Solar/Wind Harmer
5.051
943591AF1-030 GEN
Solar/Wind Harmer
3.359
990527J1329
External Queue
1.8005300760269165
991177J1571 G
External Queue
15.046978950500488
991182J1586 G
External Queue
24.65581703186035
990142J1224
External Queue
13.161874771118164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.567
NYPJM->LTFIMP_NY
CLTF
1.969
TVALTFEXP_TVA->PJM
CLTF
2.152
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.013
LGEELTFEXP_LGEE->PJM
CLTF
1.929
MECLTFEXP_MEC->PJM
CLTF
6.229
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.085
CPLELTFEXP_CPLE->PJM
CLTF
0.308
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.526
WECLTFEXP_WEC->PJM
CLTF
1.6
LAGNLTFEXP_LAGN->PJM
CLTF
4.751
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-810_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238654 CKT 1   /*02HAYES      345.0 - 02DAV-BE     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
235102 to 235235 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
238654 to 239289 ckt 1
238654 to 241877 ckt 1
239289 to 238569 ckt 1
242925 to 235117 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
243232 to 246999 ckt 3
241877 to 238569 ckt 1

Winter Peak Analysis

The New Service Request AG2-405 was evaluated as a 0.0 MW (10.98 MW Capacity) injection in the AEP area.

AG2-405 was evaluated as part of a plant. The plant consists of AG2-405. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.9 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-405 was evaluated as a 0.0 MW injection

AG2-405 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.9 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

PJM has reviewed this project submission and determined that a stability study is not required as this is a CIR only increase with no changes to equipment/electrical parameters (no change to MFO).

Reactive Power Analysis

Not Required

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements based on the project Agreements per PJM’s Tariff, Part IX, Subpart B, App. 2, section 4.6.1.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-078Beatty-London 138kVIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-111Aurora 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-214Crescent RidgeIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVSuspended
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-032Kincaid 345 kVWithdrawn
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-068Jay 138 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-406Payne 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AG2-405 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-405 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-405 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-405 could receive cost allocation. Although AG2-405 may not presently have cost responsibility for this upgrade, AG2-405 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-405 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-405 could receive cost allocation. Although AG2-405 may not presently have cost responsibility for this upgrade, AG2-405 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-405 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-405 could receive cost allocation. Although AG2-405 may not presently have cost responsibility for this upgrade, AG2-405 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-405


AG2-405 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-405 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-405 One Line Diagram

AG2-405 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.